Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2018-10-19 09:40:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3590.03 458.12 508.51
Net Site Energy 3590.03 458.12 508.51
Total Source Energy 9189.84 1172.70 1301.70
Net Source Energy 9189.84 1172.70 1301.70


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 3.29 0.59 0.00 0.00 0.00 0.00
Cooling 267.70 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 488.37 0.00 0.00 0.00 0.00 0.00
Pumps 35.73 0.00 0.00 0.00 0.00 0.00
Heat Rejection 11.58 0.00 0.00 0.00 0.00 811.52
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1045.87 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2543.57 1046.46 0.00 0.00 0.00 5590.04
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 0.59 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 3.29 0.00 0.00 0.00 0.00 0.00
Cooling General 267.70 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 488.37 0.00 0.00 0.00 0.00 0.00
Pumps General 35.73 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 11.58 0.00 0.00 0.00 0.00 811.52
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1045.87 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.86 0.00 0.00 0.00 0.00 0.00
HVAC 114.26 148.23 0.00 0.00 0.00 0.79
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 360.28 148.23 0.00 0.00 0.00 0.79


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.65 0.00 0.00 0.00 0.00 0.00
HVAC 102.94 133.54 0.00 0.00 0.00 0.71
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 324.58 133.54 0.00 0.00 0.00 0.71


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2543.57 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2543.57 100.00
     
Total On-Site and Utility Electric Sources 2543.57 100.00
Total Electricity End Uses 2543.57 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5590.04 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5590.04 100.00
Total Water End Uses 5590.04 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 24.50
Time Setpoint Not Met During Occupied Cooling 153.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1560.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 15-OCT-17:15 30-MAR-06:15 - - - 15-OCT-07:00
Heating 0.00 13019.98 0.00 0.00 0.00 0.00
Cooling 45725.15 0.00 0.00 0.00 0.00 0.00
Interior Lighting 22204.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 56867.52 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 15486.08 0.00 0.00 0.00 0.00 0.00
Pumps 1192.40 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1479.99 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 80594.78 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 154821.26 93614.76 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 13019.98 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 45725.15 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 18331.79 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 3872.61 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56867.52 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 15486.08 0.00 0.00 0.00 0.00 0.00
Pumps General 1192.40 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1479.99 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 80594.78 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 10.41 0.64 0.00 0.00 0.00
Cooling 847.82 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.84 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1546.66 0.00 0.00 0.00 0.00
Pumps 113.17 0.00 0.00 0.00 0.00
Heat Rejection 36.68 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1133.72 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 8055.48 1134.36 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.47 0.09 0.00 0.00 0.00
Cooling 120.09 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.62 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 219.08 0.00 0.00 0.00 0.00
Pumps 16.03 0.00 0.00 0.00 0.00
Heat Rejection 5.20 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 160.59 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1141.02 160.68 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.47 0.09 0.00 0.00 0.00
Cooling 120.09 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.62 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 219.08 0.00 0.00 0.00 0.00
Pumps 16.03 0.00 0.00 0.00 0.00
Heat Rejection 5.20 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 160.59 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1141.02 160.68 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.65_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 2.848 0.287 0.200     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.848 0.287 0.200              
North Total or Average           423.59 2.848 0.287 0.200              
Non-North Total or Average           726.80 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.77 83.77 168.56
Exterior Lighting Total 10720.10           168.56



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 208285.94 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 166628.75      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   2839.53 2106.80 732.73 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   2522.87 1868.55 654.32 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   3844.40 2883.77 960.63 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   1908.88 1416.10 492.78 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1293.49 933.64 359.85 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1273.15 918.20 354.96 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1823.85 1325.85 497.99 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1890.97 1377.58 513.39 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3515.55 2628.17 887.39 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3141.05 2344.50 796.55 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3233.24 2422.84 810.40 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2453.21 1835.33 617.88 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1728.18 1265.02 463.16 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1710.59 1251.62 458.97 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2319.45 1706.73 612.72 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2345.27 1726.58 618.69 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3520.99 2631.89 889.09 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3163.52 2361.34 802.18 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3033.06 2268.66 764.40 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2489.29 1862.85 626.43 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1777.51 1302.55 474.96 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1760.18 1289.34 470.83 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2352.47 1731.90 620.57 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2364.72 1741.32 623.40 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3519.98 2630.78 889.20 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3170.01 2366.00 804.00 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3058.33 2273.89 784.44 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2496.07 1867.86 628.21 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1798.15 1318.21 479.94 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1780.98 1305.12 475.86 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2360.00 1737.52 622.48 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2370.23 1745.38 624.84 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3549.60 2653.26 896.34 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3206.03 2393.40 812.64 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3090.25 2298.15 792.10 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2531.83 1895.20 636.63 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1843.61 1352.84 490.78 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1826.57 1339.85 486.73 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2394.87 1764.18 630.69 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2404.80 1771.81 632.98 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3493.53 2609.96 883.57 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3153.62 2352.97 800.65 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3039.32 2258.82 780.50 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2480.76 1855.77 624.98 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1803.10 1321.84 481.27 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1786.28 1309.02 477.27 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2345.26 1725.94 619.32 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2355.14 1733.54 621.60 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3470.11 2591.77 878.34 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3134.29 2337.96 796.34 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3020.23 2243.97 776.26 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2462.13 1841.32 620.81 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1792.87 1313.96 478.91 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1776.22 1301.27 474.94 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2326.70 1711.58 615.12 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2336.56 1719.17 617.40 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3464.65 2587.40 877.25 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3132.54 2336.45 796.09 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3017.98 2242.08 775.91 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2460.25 1839.76 620.48 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1799.02 1318.60 480.42 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1782.53 1306.04 476.49 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2325.00 1710.19 614.82 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2334.88 1717.78 617.09 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3549.97 2652.75 897.22 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3220.67 2403.89 816.78 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3084.88 2292.33 792.55 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2487.83 1860.84 626.99 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1881.80 1381.72 500.07 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1865.25 1369.11 496.14 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2381.82 1752.79 629.03 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2391.69 1760.39 631.31 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4272.38 3203.58 1068.80 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3859.75 2891.51 968.24 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3733.69 2790.42 943.26 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2958.33 2217.81 740.51 0.75 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2342.21 1720.34 621.88 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2341.28 1719.60 621.67 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3106.45 2309.33 797.11 0.74 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3112.94 2315.26 797.68 0.74 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   2839.53 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   2522.87 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   3844.40 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   1908.88 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1293.49 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1273.15 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   1823.85 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   1890.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3515.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3141.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3233.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2453.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1728.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1710.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2319.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2345.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3520.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3163.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3033.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2489.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1777.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1760.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2352.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2364.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3519.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3170.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3058.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2496.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1798.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1780.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2360.00 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2370.23 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   3549.60 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   3206.03 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   3090.25 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   2531.83 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1843.61 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1826.57 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2394.87 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2404.80 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3493.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3153.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3039.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2480.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1803.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1786.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2345.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2355.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3470.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3134.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3020.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2462.13 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1792.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1776.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2326.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2336.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3464.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3132.54 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3017.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2460.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1799.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1782.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2325.00 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2334.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3549.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3220.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3084.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2487.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1881.80 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1865.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2381.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2391.69 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   4272.38 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   3859.75 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   3733.69 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   2958.33 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2342.21 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2341.28 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3106.45 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3112.94 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   1465.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   1470.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   2103.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   1468.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   1436.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   1439.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   1461.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   1438.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   1421.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   1423.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   1424.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   1422.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   1434.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   1435.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   1434.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   1435.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   1427.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   1427.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   1428.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   1428.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   1486.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   1486.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   1487.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   1487.77 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   1522.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   1521.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   1523.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   1522.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   1558.55 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   1557.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   1559.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   1558.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   1671.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   1668.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   1673.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   1670.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   1115.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   2050.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   2051.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   2052.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   2053.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   1493.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   1493.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   1489.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   1489.36 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 211.58 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.41 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 293.46 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 143.73 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.08 90.96 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.08 89.35 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.50 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 134.93 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 266.83 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.92 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 247.12 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.56 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 125.61 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 124.21 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.46 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 171.54 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.20 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.66 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.87 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 190.45 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.53 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 128.15 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.09 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 173.08 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.07 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 240.14 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 229.14 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 190.97 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 131.17 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.80 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.67 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 173.50 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.42 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 243.01 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.68 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 193.84 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 134.79 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 133.43 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.46 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 176.26 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 264.85 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.74 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 227.53 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 189.68 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 131.54 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.20 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 171.44 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.24 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 262.92 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.15 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.96 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 188.15 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.71 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.38 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.93 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.72 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 262.45 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 236.99 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.75 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.98 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 131.19 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.88 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.78 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.57 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.32 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 244.07 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.87 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 190.19 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 137.80 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 136.48 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 174.10 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 174.89 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 326.66 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 294.67 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.26 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.85 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.39 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.31 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.58 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 233.36 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0045 1155.48 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1972.78 2367.33 0.157 0.189 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 30.90 0.00820
G NW APARTMENT 1747.40 2096.88 0.139 0.167 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 30.23 0.00820
OFFICE 2736.25 3283.50 0.218 0.262 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 28.92 0.00820
G NE APARTMENT 1340.06 1608.07 0.107 0.128 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16 0.00820
G N1 APARTMENT 848.14 1017.76 0.068 0.081 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
G N2 APARTMENT 833.13 999.76 0.066 0.080 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
G S1 APARTMENT 1207.46 1448.95 0.096 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
G S2 APARTMENT 1258.07 1509.68 0.100 0.120 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F2 SW APARTMENT 2487.93 2985.51 0.199 0.238 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F2 NW APARTMENT 2218.31 2661.97 0.177 0.212 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F2 SE APARTMENT 2304.16 2764.99 0.184 0.221 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 29.25 0.00820
F2 NE APARTMENT 1748.82 2098.59 0.140 0.167 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F2 N1 APARTMENT 1171.16 1405.39 0.093 0.112 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F2 N2 APARTMENT 1158.09 1389.70 0.092 0.111 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F2 S1 APARTMENT 1579.99 1895.99 0.126 0.151 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F2 S2 APARTMENT 1599.44 1919.33 0.128 0.153 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F3 SW APARTMENT 2491.36 2989.63 0.199 0.239 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F3 NW APARTMENT 2234.62 2681.54 0.178 0.214 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F3 SE APARTMENT 2152.60 2583.12 0.172 0.206 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 29.25 0.00820
F3 NE APARTMENT 1775.76 2130.91 0.142 0.170 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F3 N1 APARTMENT 1207.75 1449.30 0.096 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F3 N2 APARTMENT 1194.86 1433.83 0.095 0.114 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F3 S1 APARTMENT 1604.54 1925.45 0.128 0.154 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F3 S2 APARTMENT 1613.77 1936.52 0.129 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F4 SW APARTMENT 2490.10 2988.12 0.199 0.238 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F4 NW APARTMENT 2239.04 2686.85 0.179 0.214 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F4 SE APARTMENT 2136.50 2563.80 0.170 0.205 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
F4 NE APARTMENT 1780.58 2136.69 0.142 0.170 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F4 N1 APARTMENT 1222.99 1467.59 0.098 0.117 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F4 N2 APARTMENT 1210.22 1452.26 0.097 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F4 S1 APARTMENT 1609.96 1931.95 0.128 0.154 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F4 S2 APARTMENT 1617.66 1941.20 0.129 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
M SW APARTMENT 2512.02 3014.42 0.200 0.241 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
M NW APARTMENT 2265.78 2718.94 0.181 0.217 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
M SE APARTMENT 2160.16 2592.20 0.172 0.207 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
M NE APARTMENT 1807.35 2168.82 0.144 0.173 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
M N1 APARTMENT 1256.78 1508.14 0.100 0.120 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
M N2 APARTMENT 1244.10 1492.92 0.099 0.119 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
M S1 APARTMENT 1636.00 1963.20 0.131 0.157 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
M S2 APARTMENT 1643.48 1972.17 0.131 0.157 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F6 SW APARTMENT 2469.42 2963.31 0.197 0.236 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F6 NW APARTMENT 2226.03 2671.23 0.178 0.213 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F6 SE APARTMENT 2121.49 2545.79 0.169 0.203 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
F6 NE APARTMENT 1768.54 2122.25 0.141 0.169 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F6 N1 APARTMENT 1226.46 1471.75 0.098 0.117 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F6 N2 APARTMENT 1213.95 1456.74 0.097 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F6 S1 APARTMENT 1598.49 1918.19 0.128 0.153 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F6 S2 APARTMENT 1605.94 1927.13 0.128 0.154 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F7 SW APARTMENT 2451.48 2941.77 0.196 0.235 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F7 NW APARTMENT 2211.21 2653.45 0.176 0.212 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F7 SE APARTMENT 2106.84 2528.20 0.168 0.202 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
F7 NE APARTMENT 1754.28 2105.13 0.140 0.168 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F7 N1 APARTMENT 1218.73 1462.48 0.097 0.117 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F7 N2 APARTMENT 1206.35 1447.62 0.096 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F7 S1 APARTMENT 1584.38 1901.26 0.126 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F7 S2 APARTMENT 1591.82 1910.18 0.127 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F8 SW APARTMENT 2447.09 2936.51 0.195 0.234 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F8 NW APARTMENT 2209.65 2651.58 0.176 0.212 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F8 SE APARTMENT 2104.90 2525.88 0.168 0.202 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.86 0.00820
F8 NE APARTMENT 1752.69 2103.23 0.140 0.168 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F8 N1 APARTMENT 1223.23 1467.88 0.098 0.117 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F8 N2 APARTMENT 1210.98 1453.17 0.097 0.116 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F8 S1 APARTMENT 1582.98 1899.57 0.126 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F8 S2 APARTMENT 1590.42 1908.50 0.127 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F9 SW APARTMENT 2511.12 3013.35 0.200 0.240 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:15:00 30.59 0.00820
F9 NW APARTMENT 2275.71 2730.86 0.182 0.218 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 29.83 0.00820
F9 SE APARTMENT 2152.65 2583.18 0.172 0.206 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
F9 NE APARTMENT 1773.34 2128.00 0.141 0.170 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 27.54 0.00820
F9 N1 APARTMENT 1284.87 1541.85 0.103 0.123 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F9 N2 APARTMENT 1272.56 1527.07 0.102 0.122 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 28.83 0.00820
F9 S1 APARTMENT 1623.26 1947.91 0.130 0.155 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.08 0.00820
F9 S2 APARTMENT 1630.70 1956.84 0.130 0.156 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.08 0.00820
T SW APARTMENT 3045.72 3654.87 0.243 0.292 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 31.03 0.00820
T NW APARTMENT 2747.47 3296.96 0.219 0.263 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41 0.00820
T SE APARTMENT 2641.14 3169.37 0.211 0.253 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820
T NE APARTMENT 2115.08 2538.10 0.169 0.203 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:15:00 28.25 0.00820
T N1 APARTMENT 1588.68 1906.41 0.127 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30 0.00820
T N2 APARTMENT 1587.95 1905.54 0.127 0.152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 31.30 0.00820
T S1 APARTMENT 2168.58 2602.30 0.173 0.208 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.08 0.00820
T S2 APARTMENT 2175.82 2610.99 0.174 0.208 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 30.97 0.00820


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 772.72 927.27 0.035 0.042 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
G NW APARTMENT 776.78 932.14 0.035 0.042 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
OFFICE 1093.66 1312.40 0.050 0.060 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 19:00:00 3.80 0.00506
G NE APARTMENT 775.41 930.49 0.035 0.042 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
G N1 APARTMENT 426.60 511.92 0.019 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
G N2 APARTMENT 426.57 511.88 0.019 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
G S1 APARTMENT 419.26 503.11 0.019 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
G S2 APARTMENT 426.25 511.50 0.019 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 3.80 0.00506
F2 SW APARTMENT 748.24 897.89 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 NW APARTMENT 750.88 901.05 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 SE APARTMENT 769.33 923.20 0.035 0.042 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 NE APARTMENT 749.93 899.92 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 N1 APARTMENT 318.91 382.69 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 N2 APARTMENT 318.88 382.65 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 S1 APARTMENT 318.45 382.15 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F2 S2 APARTMENT 320.02 384.02 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 SW APARTMENT 735.60 882.72 0.033 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 NW APARTMENT 737.17 884.60 0.033 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 SE APARTMENT 737.93 885.52 0.033 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 NE APARTMENT 736.77 884.12 0.033 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 N1 APARTMENT 291.24 349.49 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 N2 APARTMENT 291.23 349.47 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 S1 APARTMENT 290.16 348.19 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F3 S2 APARTMENT 290.43 348.52 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 SW APARTMENT 746.25 895.50 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 NW APARTMENT 747.38 896.86 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 SE APARTMENT 746.60 895.93 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 NE APARTMENT 747.41 896.90 0.034 0.041 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 N1 APARTMENT 290.01 348.02 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 N2 APARTMENT 290.01 348.02 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 S1 APARTMENT 289.16 346.99 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F4 S2 APARTMENT 289.21 347.05 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M SW APARTMENT 741.01 889.21 0.034 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M NW APARTMENT 740.75 888.90 0.034 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M SE APARTMENT 741.43 889.72 0.034 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M NE APARTMENT 741.13 889.36 0.034 0.040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M N1 APARTMENT 277.78 333.34 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M N2 APARTMENT 277.80 333.35 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M S1 APARTMENT 278.29 333.95 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
M S2 APARTMENT 278.31 333.97 0.013 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 SW APARTMENT 790.89 949.07 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 NW APARTMENT 790.95 949.14 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 SE APARTMENT 791.59 949.91 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 NE APARTMENT 791.64 949.97 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 N1 APARTMENT 316.35 379.62 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 N2 APARTMENT 316.37 379.65 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 S1 APARTMENT 316.52 379.83 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F6 S2 APARTMENT 316.54 379.85 0.014 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 SW APARTMENT 820.82 984.98 0.037 0.045 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 NW APARTMENT 820.26 984.31 0.037 0.045 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 SE APARTMENT 821.78 986.14 0.037 0.045 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 NE APARTMENT 821.22 985.47 0.037 0.045 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 N1 APARTMENT 338.69 406.43 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 N2 APARTMENT 338.72 406.46 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 S1 APARTMENT 339.46 407.36 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F7 S2 APARTMENT 339.49 407.39 0.015 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 SW APARTMENT 851.50 1021.80 0.039 0.046 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 NW APARTMENT 850.26 1020.31 0.039 0.046 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 SE APARTMENT 852.70 1023.24 0.039 0.046 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 NE APARTMENT 851.46 1021.75 0.039 0.046 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 N1 APARTMENT 362.84 435.41 0.016 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 N2 APARTMENT 362.88 435.45 0.016 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 S1 APARTMENT 364.27 437.12 0.017 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F8 S2 APARTMENT 364.30 437.16 0.017 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 SW APARTMENT 947.43 1136.92 0.043 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 NW APARTMENT 944.34 1133.21 0.043 0.051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 SE APARTMENT 948.86 1138.63 0.043 0.052 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 NE APARTMENT 945.77 1134.93 0.043 0.051 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 N1 APARTMENT 446.70 536.04 0.020 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 N2 APARTMENT 446.74 536.09 0.020 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 S1 APARTMENT 449.60 539.52 0.020 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
F9 S2 APARTMENT 449.64 539.57 0.020 0.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T SW APARTMENT 1267.81 1521.38 0.057 0.069 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T NW APARTMENT 1268.68 1522.41 0.058 0.069 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T SE APARTMENT 1269.28 1523.13 0.058 0.069 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T NE APARTMENT 1270.14 1524.17 0.058 0.069 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T N1 APARTMENT 796.25 955.50 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T N2 APARTMENT 796.29 955.55 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T S1 APARTMENT 792.94 951.53 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506
T S2 APARTMENT 792.99 951.58 0.036 0.043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 3.80 0.00506


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.19 0.19 0.04 0.04
AIRLOOP G NW 0.17 0.17 0.04 0.04
AIRLOOP OFFICE 0.26 0.26 0.06 0.06
AIRLOOP G NE 0.13 0.13 0.04 0.04
AIRLOOP G N1 0.08 0.08 0.03 0.03
AIRLOOP G N2 0.08 0.08 0.03 0.03
AIRLOOP G S1 0.12 0.12 0.03 0.03
AIRLOOP G S2 0.12 0.12 0.03 0.03
AIRLOOP F2 SW 0.24 0.24 0.04 0.04
AIRLOOP F2 NW 0.21 0.21 0.04 0.04
AIRLOOP F2 SE 0.22 0.22 0.04 0.04
AIRLOOP F2 NE 0.17 0.17 0.04 0.04
AIRLOOP F2 N1 0.11 0.11 0.03 0.03
AIRLOOP F2 N2 0.11 0.11 0.03 0.03
AIRLOOP F2 S1 0.15 0.15 0.03 0.03
AIRLOOP F2 S2 0.15 0.15 0.03 0.03
AIRLOOP F3 SW 0.24 0.24 0.04 0.04
AIRLOOP F3 NW 0.21 0.21 0.04 0.04
AIRLOOP F3 SE 0.21 0.21 0.04 0.04
AIRLOOP F3 NE 0.17 0.17 0.04 0.04
AIRLOOP F3 N1 0.12 0.12 0.03 0.03
AIRLOOP F3 N2 0.11 0.11 0.03 0.03
AIRLOOP F3 S1 0.15 0.15 0.03 0.03
AIRLOOP F3 S2 0.15 0.15 0.03 0.03
AIRLOOP F4 SW 0.24 0.24 0.04 0.04
AIRLOOP F4 NW 0.21 0.21 0.04 0.04
AIRLOOP F4 SE 0.20 0.20 0.04 0.04
AIRLOOP F4 NE 0.17 0.17 0.04 0.04
AIRLOOP F4 N1 0.12 0.12 0.03 0.03
AIRLOOP F4 N2 0.12 0.12 0.03 0.03
AIRLOOP F4 S1 0.15 0.15 0.03 0.03
AIRLOOP F4 S2 0.15 0.15 0.03 0.03
AIRLOOP M SW 0.24 0.24 0.04 0.04
AIRLOOP M NW 0.22 0.22 0.04 0.04
AIRLOOP M SE 0.21 0.21 0.04 0.04
AIRLOOP M NE 0.17 0.17 0.04 0.04
AIRLOOP M N1 0.12 0.12 0.03 0.03
AIRLOOP M N2 0.12 0.12 0.03 0.03
AIRLOOP M S1 0.16 0.16 0.03 0.03
AIRLOOP M S2 0.16 0.16 0.03 0.03
AIRLOOP F6 SW 0.24 0.24 0.04 0.04
AIRLOOP F6 NW 0.21 0.21 0.04 0.04
AIRLOOP F6 SE 0.20 0.20 0.04 0.04
AIRLOOP F6 NE 0.17 0.17 0.04 0.04
AIRLOOP F6 N1 0.12 0.12 0.03 0.03
AIRLOOP F6 N2 0.12 0.12 0.03 0.03
AIRLOOP F6 S1 0.15 0.15 0.03 0.03
AIRLOOP F6 S2 0.15 0.15 0.03 0.03
AIRLOOP F7 SW 0.23 0.23 0.04 0.04
AIRLOOP F7 NW 0.21 0.21 0.04 0.04
AIRLOOP F7 SE 0.20 0.20 0.04 0.04
AIRLOOP F7 NE 0.17 0.17 0.04 0.04
AIRLOOP F7 N1 0.12 0.12 0.03 0.03
AIRLOOP F7 N2 0.12 0.12 0.03 0.03
AIRLOOP F7 S1 0.15 0.15 0.03 0.03
AIRLOOP F7 S2 0.15 0.15 0.03 0.03
AIRLOOP F8 SW 0.23 0.23 0.05 0.05
AIRLOOP F8 NW 0.21 0.21 0.05 0.05
AIRLOOP F8 SE 0.20 0.20 0.05 0.05
AIRLOOP F8 NE 0.17 0.17 0.05 0.05
AIRLOOP F8 N1 0.12 0.12 0.03 0.03
AIRLOOP F8 N2 0.12 0.12 0.03 0.03
AIRLOOP F8 S1 0.15 0.15 0.03 0.03
AIRLOOP F8 S2 0.15 0.15 0.03 0.03
AIRLOOP F9 SW 0.24 0.24 0.05 0.05
AIRLOOP F9 NW 0.22 0.22 0.05 0.05
AIRLOOP F9 SE 0.21 0.21 0.05 0.05
AIRLOOP F9 NE 0.17 0.17 0.05 0.05
AIRLOOP F9 N1 0.12 0.12 0.03 0.03
AIRLOOP F9 N2 0.12 0.12 0.03 0.03
AIRLOOP F9 S1 0.16 0.16 0.03 0.03
AIRLOOP F9 S2 0.16 0.16 0.03 0.03
AIRLOOP T SW 0.29 0.29 0.07 0.07
AIRLOOP T NW 0.26 0.26 0.07 0.07
AIRLOOP T SE 0.25 0.25 0.07 0.07
AIRLOOP T NE 0.20 0.20 0.07 0.07
AIRLOOP T N1 0.15 0.15 0.04 0.04
AIRLOOP T N2 0.15 0.15 0.04 0.04
AIRLOOP T S1 0.21 0.21 0.04 0.04
AIRLOOP T S2 0.21 0.21 0.04 0.04



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3353.75 5168.00 1034.75
G NW APARTMENT 2699.00 6659.00 1141.25
OFFICE 1472.50 157.75 0.50
G NE APARTMENT 2535.50 6915.00 1214.75
G N1 APARTMENT 2391.00 7411.50 1479.25
G N2 APARTMENT 2372.50 7425.25 1478.50
G S1 APARTMENT 3007.00 5842.75 1274.25
G S2 APARTMENT 3055.25 5724.75 1252.75
F2 SW APARTMENT 5653.75 1910.50 474.75
F2 NW APARTMENT 3877.75 4281.00 632.75
F2 SE APARTMENT 5811.00 1741.00 441.00
F2 NE APARTMENT 3636.50 4730.50 680.75
F2 N1 APARTMENT 3325.00 5279.25 960.75
F2 N2 APARTMENT 3293.75 5337.50 963.75
F2 S1 APARTMENT 5546.75 1969.75 616.25
F2 S2 APARTMENT 5574.75 1943.00 610.25
F3 SW APARTMENT 6164.50 1425.50 443.00
F3 NW APARTMENT 4401.25 3498.00 572.75
F3 SE APARTMENT 6119.50 1488.50 448.00
F3 NE APARTMENT 4142.00 3939.75 614.00
F3 N1 APARTMENT 3945.75 4144.25 829.25
F3 N2 APARTMENT 3907.75 4201.50 832.50
F3 S1 APARTMENT 6256.50 1331.00 566.50
F3 S2 APARTMENT 6253.00 1328.50 565.50
F4 SW APARTMENT 6229.50 1393.25 449.25
F4 NW APARTMENT 4514.00 3336.00 562.50
F4 SE APARTMENT 6130.50 1483.25 447.75
F4 NE APARTMENT 4255.25 3757.25 606.75
F4 N1 APARTMENT 4152.00 3810.50 791.00
F4 N2 APARTMENT 4114.75 3866.50 798.50
F4 S1 APARTMENT 6352.25 1261.25 565.50
F4 S2 APARTMENT 6344.50 1268.00 567.00
M SW APARTMENT 6263.00 1376.00 446.25
M NW APARTMENT 4570.25 3254.00 552.25
M SE APARTMENT 6157.00 1467.50 441.00
M NE APARTMENT 4307.25 3646.00 585.00
M N1 APARTMENT 4262.00 3614.50 750.75
M N2 APARTMENT 4221.00 3673.75 753.75
M S1 APARTMENT 6401.75 1220.25 556.75
M S2 APARTMENT 6396.00 1230.25 557.00
F6 SW APARTMENT 6029.50 1600.25 475.25
F6 NW APARTMENT 4293.00 3611.25 593.50
F6 SE APARTMENT 5878.75 1715.50 470.75
F6 NE APARTMENT 4031.25 4063.50 652.00
F6 N1 APARTMENT 3954.00 4081.75 826.25
F6 N2 APARTMENT 3918.25 4148.00 831.00
F6 S1 APARTMENT 6167.75 1454.25 596.75
F6 S2 APARTMENT 6159.00 1463.00 598.00
F7 SW APARTMENT 5844.50 1780.50 498.25
F7 NW APARTMENT 4103.00 3889.25 620.25
F7 SE APARTMENT 5692.00 1891.25 494.75
F7 NE APARTMENT 3824.50 4359.75 678.25
F7 N1 APARTMENT 3728.25 4427.25 869.00
F7 N2 APARTMENT 3685.50 4487.00 873.50
F7 S1 APARTMENT 5989.00 1641.25 620.75
F7 S2 APARTMENT 5974.50 1655.00 621.00
F8 SW APARTMENT 5683.25 1934.25 510.75
F8 NW APARTMENT 3943.50 4142.75 634.75
F8 SE APARTMENT 5518.75 2054.25 509.75
F8 NE APARTMENT 3662.25 4623.75 702.00
F8 N1 APARTMENT 3545.75 4716.50 888.25
F8 N2 APARTMENT 3510.00 4780.00 895.25
F8 S1 APARTMENT 5807.25 1811.75 636.75
F8 S2 APARTMENT 5794.00 1821.50 636.25
F9 SW APARTMENT 5377.75 2231.25 518.50
F9 NW APARTMENT 3747.25 4447.00 639.50
F9 SE APARTMENT 5250.50 2340.00 514.25
F9 NE APARTMENT 3493.75 4930.50 708.75
F9 N1 APARTMENT 3365.25 5056.75 891.50
F9 N2 APARTMENT 3326.25 5112.00 896.25
F9 S1 APARTMENT 5480.00 2099.25 641.00
F9 S2 APARTMENT 5464.25 2114.00 643.75
T SW APARTMENT 4636.25 3582.25 682.00
T NW APARTMENT 3386.25 5229.50 835.25
T SE APARTMENT 4494.50 3814.75 792.75
T NE APARTMENT 3171.75 5721.75 969.50
T N1 APARTMENT 3079.25 5839.00 1085.25
T N2 APARTMENT 3049.75 5889.75 1095.00
T S1 APARTMENT 4740.25 3475.25 798.75
T S2 APARTMENT 4725.00 3497.50 804.25
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 6936.25 7547.75 1560.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 1.25 11.00 1.25 11.00
G NW APARTMENT 5.75 0.00 5.75 0.00
OFFICE 0.75 13.50 0.00 13.50
G NE APARTMENT 6.50 5.75 6.50 5.75
G N1 APARTMENT 0.00 0.75 0.00 0.75
G N2 APARTMENT 0.00 1.00 0.00 1.00
G S1 APARTMENT 0.00 39.00 0.00 39.00
G S2 APARTMENT 0.00 35.25 0.00 35.25
F2 SW APARTMENT 0.00 25.50 0.00 25.50
F2 NW APARTMENT 0.75 0.00 0.75 0.00
F2 SE APARTMENT 0.00 43.50 0.00 43.50
F2 NE APARTMENT 0.25 5.25 0.25 5.25
F2 N1 APARTMENT 0.00 0.75 0.00 0.75
F2 N2 APARTMENT 0.00 0.75 0.00 0.75
F2 S1 APARTMENT 0.00 93.00 0.00 93.00
F2 S2 APARTMENT 0.00 91.25 0.00 91.25
F3 SW APARTMENT 0.00 30.75 0.00 30.75
F3 NW APARTMENT 0.25 0.00 0.25 0.00
F3 SE APARTMENT 0.00 74.50 0.00 74.50
F3 NE APARTMENT 0.50 7.75 0.50 7.75
F3 N1 APARTMENT 0.00 1.50 0.00 1.50
F3 N2 APARTMENT 0.00 1.75 0.00 1.75
F3 S1 APARTMENT 0.00 121.25 0.00 121.25
F3 S2 APARTMENT 0.00 120.25 0.00 120.25
F4 SW APARTMENT 0.00 31.50 0.00 31.50
F4 NW APARTMENT 0.00 0.00 0.00 0.00
F4 SE APARTMENT 0.00 75.00 0.00 75.00
F4 NE APARTMENT 0.50 8.50 0.50 8.50
F4 N1 APARTMENT 0.00 2.00 0.00 2.00
F4 N2 APARTMENT 0.00 2.00 0.00 2.00
F4 S1 APARTMENT 0.00 125.00 0.00 125.00
F4 S2 APARTMENT 0.00 125.00 0.00 125.00
M SW APARTMENT 0.00 31.25 0.00 31.25
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 74.25 0.00 74.25
M NE APARTMENT 0.25 8.75 0.25 8.75
M N1 APARTMENT 0.00 1.75 0.00 1.75
M N2 APARTMENT 0.00 2.25 0.00 2.25
M S1 APARTMENT 0.00 124.50 0.00 124.50
M S2 APARTMENT 0.00 123.50 0.00 123.50
F6 SW APARTMENT 0.00 32.75 0.00 32.75
F6 NW APARTMENT 0.00 0.00 0.00 0.00
F6 SE APARTMENT 0.00 72.75 0.00 72.75
F6 NE APARTMENT 0.50 10.00 0.50 10.00
F6 N1 APARTMENT 0.00 2.25 0.00 2.25
F6 N2 APARTMENT 0.00 4.00 0.00 4.00
F6 S1 APARTMENT 0.00 121.25 0.00 121.25
F6 S2 APARTMENT 0.00 120.50 0.00 120.50
F7 SW APARTMENT 0.00 32.75 0.00 32.75
F7 NW APARTMENT 0.00 0.00 0.00 0.00
F7 SE APARTMENT 0.25 70.50 0.25 70.50
F7 NE APARTMENT 0.50 10.25 0.50 10.25
F7 N1 APARTMENT 0.00 2.75 0.00 2.75
F7 N2 APARTMENT 0.00 4.00 0.00 4.00
F7 S1 APARTMENT 0.00 116.75 0.00 116.75
F7 S2 APARTMENT 0.00 117.25 0.00 117.25
F8 SW APARTMENT 0.00 32.00 0.00 32.00
F8 NW APARTMENT 0.50 0.00 0.50 0.00
F8 SE APARTMENT 0.00 66.75 0.00 66.75
F8 NE APARTMENT 0.00 10.25 0.00 10.25
F8 N1 APARTMENT 0.00 2.25 0.00 2.25
F8 N2 APARTMENT 0.00 3.75 0.00 3.75
F8 S1 APARTMENT 0.00 109.75 0.00 109.75
F8 S2 APARTMENT 0.00 109.25 0.00 109.25
F9 SW APARTMENT 0.00 25.75 0.00 25.75
F9 NW APARTMENT 0.00 0.00 0.00 0.00
F9 SE APARTMENT 0.00 54.25 0.00 54.25
F9 NE APARTMENT 0.75 8.75 0.75 8.75
F9 N1 APARTMENT 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 0.00 0.75 0.00 0.75
F9 S1 APARTMENT 0.00 88.75 0.00 88.75
F9 S2 APARTMENT 0.00 88.25 0.00 88.25
T SW APARTMENT 0.00 25.25 0.00 25.25
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 54.50 0.00 54.50
T NE APARTMENT 0.00 18.25 0.00 18.25
T N1 APARTMENT 3.00 6.25 3.00 6.25
T N2 APARTMENT 3.00 8.75 3.00 8.75
T S1 APARTMENT 0.75 72.25 0.75 72.25
T S2 APARTMENT 0.50 73.25 0.50 73.25
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 25.00 153.25 24.50 153.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.356 0.064 0.000 0.647
G NW APARTMENT 1.71 2.50 268.96 0.355 0.064 0.000 0.619
OFFICE 0.94 1.00 268.96 0.522 0.088 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.355 0.064 0.000 0.617
G N1 APARTMENT 1.71 2.50 268.96 0.355 0.038 0.000 0.600
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.038 0.000 0.600
G S1 APARTMENT 1.71 2.50 268.96 0.356 0.039 0.000 0.636
G S2 APARTMENT 1.71 2.50 268.97 0.356 0.039 0.000 0.638
F2 SW APARTMENT 1.71 2.50 268.96 0.356 0.092 0.000 0.725
F2 NW APARTMENT 1.71 2.50 268.96 0.356 0.092 0.000 0.701
F2 SE APARTMENT 1.71 2.50 268.96 0.356 0.092 0.000 0.727
F2 NE APARTMENT 1.71 2.50 268.96 0.356 0.092 0.000 0.699
F2 N1 APARTMENT 1.71 2.50 268.96 0.356 0.055 0.000 0.687
F2 N2 APARTMENT 1.71 2.50 268.97 0.356 0.055 0.000 0.687
F2 S1 APARTMENT 1.71 2.50 268.96 0.356 0.055 0.000 0.719
F2 S2 APARTMENT 1.71 2.50 268.97 0.356 0.055 0.000 0.719
F3 SW APARTMENT 1.71 2.50 268.96 0.356 0.109 0.000 0.766
F3 NW APARTMENT 1.71 2.50 268.96 0.356 0.109 0.000 0.744
F3 SE APARTMENT 1.71 2.50 268.96 0.356 0.109 0.000 0.766
F3 NE APARTMENT 1.71 2.50 268.96 0.356 0.109 0.000 0.742
F3 N1 APARTMENT 1.71 2.50 268.96 0.356 0.066 0.000 0.733
F3 N2 APARTMENT 1.71 2.50 268.97 0.356 0.066 0.000 0.732
F3 S1 APARTMENT 1.71 2.50 268.96 0.357 0.066 0.000 0.761
F3 S2 APARTMENT 1.71 2.50 268.97 0.357 0.066 0.000 0.761
F4 SW APARTMENT 1.71 2.50 268.96 0.356 0.122 0.000 0.797
F4 NW APARTMENT 1.71 2.50 268.96 0.356 0.122 0.000 0.775
F4 SE APARTMENT 1.71 2.50 268.96 0.356 0.122 0.000 0.796
F4 NE APARTMENT 1.71 2.50 268.96 0.356 0.122 0.000 0.773
F4 N1 APARTMENT 1.71 2.50 268.96 0.356 0.073 0.000 0.765
F4 N2 APARTMENT 1.71 2.50 268.97 0.356 0.073 0.000 0.765
F4 S1 APARTMENT 1.71 2.50 268.96 0.357 0.073 0.000 0.793
F4 S2 APARTMENT 1.71 2.50 268.97 0.357 0.073 0.000 0.793
M SW APARTMENT 1.71 2.50 268.96 0.356 0.132 0.000 0.824
M NW APARTMENT 1.71 2.50 268.96 0.356 0.132 0.000 0.801
M SE APARTMENT 1.71 2.50 268.96 0.356 0.132 0.000 0.823
M NE APARTMENT 1.71 2.50 268.96 0.356 0.132 0.000 0.800
M N1 APARTMENT 1.71 2.50 268.96 0.356 0.080 0.000 0.792
M N2 APARTMENT 1.71 2.50 268.97 0.356 0.080 0.000 0.792
M S1 APARTMENT 1.71 2.50 268.96 0.356 0.080 0.000 0.820
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.080 0.000 0.820
F6 SW APARTMENT 1.71 2.50 268.96 0.356 0.141 0.000 0.847
F6 NW APARTMENT 1.71 2.50 268.96 0.356 0.141 0.000 0.823
F6 SE APARTMENT 1.71 2.50 268.96 0.356 0.141 0.000 0.846
F6 NE APARTMENT 1.71 2.50 268.96 0.356 0.141 0.000 0.821
F6 N1 APARTMENT 1.71 2.50 268.96 0.356 0.085 0.000 0.813
F6 N2 APARTMENT 1.71 2.50 268.97 0.356 0.085 0.000 0.813
F6 S1 APARTMENT 1.71 2.50 268.96 0.356 0.085 0.000 0.842
F6 S2 APARTMENT 1.71 2.50 268.97 0.356 0.085 0.000 0.842
F7 SW APARTMENT 1.71 2.50 268.96 0.356 0.149 0.000 0.867
F7 NW APARTMENT 1.71 2.50 268.96 0.356 0.149 0.000 0.842
F7 SE APARTMENT 1.71 2.50 268.96 0.356 0.149 0.000 0.866
F7 NE APARTMENT 1.71 2.50 268.96 0.356 0.149 0.000 0.840
F7 N1 APARTMENT 1.71 2.50 268.96 0.356 0.090 0.000 0.832
F7 N2 APARTMENT 1.71 2.50 268.97 0.356 0.090 0.000 0.832
F7 S1 APARTMENT 1.71 2.50 268.96 0.356 0.090 0.000 0.862
F7 S2 APARTMENT 1.71 2.50 268.97 0.356 0.090 0.000 0.862
F8 SW APARTMENT 1.71 2.50 268.96 0.356 0.157 0.000 0.886
F8 NW APARTMENT 1.71 2.50 268.96 0.356 0.156 0.000 0.859
F8 SE APARTMENT 1.71 2.50 268.96 0.356 0.156 0.000 0.885
F8 NE APARTMENT 1.71 2.50 268.96 0.356 0.156 0.000 0.858
F8 N1 APARTMENT 1.71 2.50 268.96 0.356 0.094 0.000 0.850
F8 N2 APARTMENT 1.71 2.50 268.97 0.356 0.094 0.000 0.849
F8 S1 APARTMENT 1.71 2.50 268.96 0.356 0.094 0.000 0.881
F8 S2 APARTMENT 1.71 2.50 268.97 0.356 0.094 0.000 0.881
F9 SW APARTMENT 1.71 2.50 268.96 0.356 0.163 0.000 0.903
F9 NW APARTMENT 1.71 2.50 268.96 0.356 0.163 0.000 0.875
F9 SE APARTMENT 1.71 2.50 268.96 0.356 0.163 0.000 0.902
F9 NE APARTMENT 1.71 2.50 268.96 0.356 0.163 0.000 0.873
F9 N1 APARTMENT 1.71 2.50 268.96 0.356 0.098 0.000 0.865
F9 N2 APARTMENT 1.71 2.50 268.97 0.356 0.098 0.000 0.865
F9 S1 APARTMENT 1.71 2.50 268.96 0.356 0.098 0.000 0.898
F9 S2 APARTMENT 1.71 2.50 268.97 0.356 0.098 0.000 0.898
T SW APARTMENT 1.71 2.50 268.96 0.356 0.169 0.000 0.916
T NW APARTMENT 1.71 2.50 268.96 0.356 0.169 0.000 0.890
T SE APARTMENT 1.71 2.50 268.96 0.356 0.169 0.000 0.916
T NE APARTMENT 1.71 2.50 268.96 0.356 0.169 0.000 0.889
T N1 APARTMENT 1.71 2.50 268.96 0.356 0.102 0.000 0.879
T N2 APARTMENT 1.71 2.50 268.97 0.356 0.102 0.000 0.879
T S1 APARTMENT 1.71 2.50 268.96 0.356 0.102 0.000 0.912
T S2 APARTMENT 1.71 2.50 268.97 0.356 0.102 0.000 0.912
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.509 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 488.37 15486.08 11-JAN-12:30 15486.08 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 780.18 15866.60 26-JAN-03:15 69908.29 18-AUG-14:30
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
ElectricityPurchased:Plant 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
Cogeneration:ElectricityPurchased 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
ElectricityNet:Plant 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
Cogeneration:ElectricityNet 2543.57 53427.09 26-JAN-03:15 154821.26 15-OCT-17:15
ExteriorLights:Electricity 168.56 0.00 01-JAN-07:00 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.56 0.00 01-JAN-07:00 10720.10 01-JAN-00:15
General:Fans:Electricity 488.37 15486.08 11-JAN-12:30 15486.08 01-JAN-00:15
Cooling:Electricity 267.70 0.00 01-JAN-00:15 53765.88 18-AUG-14:30
Heating:Electricity 3.29 0.00 01-JAN-08:00 12640.71 12-FEB-08:45
Electricity:Plant 47.31 36.93 14-JAN-19:30 3130.09 18-AUG-14:45
HeatRejection:Electricity 11.58 0.00 01-JAN-00:15 1937.69 18-AUG-14:45
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 35.73 36.93 14-JAN-19:30 1192.40 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1046.46 9260.51 01-JAN-00:15 93614.76 30-MAR-06:15
Gas:Plant 1046.46 9260.51 01-JAN-00:15 93614.76 30-MAR-06:15
WaterSystems:Gas 1045.87 9260.51 01-JAN-00:15 82165.69 25-JAN-08:00
Water Heater:WaterSystems:Gas 1045.87 9260.51 01-JAN-00:15 82165.69 25-JAN-08:00
Heating:Gas 0.59 0.00 01-JAN-00:15 25727.19 30-MAR-04:00
Boiler:Heating:Gas 0.59 0.00 01-JAN-00:15 25727.19 30-MAR-04:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 1087.37 0.00 01-JAN-00:15 253185.71 18-AUG-14:30
PlantLoopCoolingDemand:HVAC 1087.37 0.00 01-JAN-00:15 253185.71 18-AUG-14:30
CoolingCoils:PlantLoopCoolingDemand 1087.37 0.00 01-JAN-00:15 253185.71 18-AUG-14:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 5590.04 0.00 01-JAN-02:15 0.00 15-OCT-08:00
Water:Plant 5590.04 0.00 01-JAN-02:15 0.00 15-OCT-08:00
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 5590.04 0.00 01-JAN-02:15 0.00 15-OCT-08:00
MainsWater:Plant 5590.04 0.00 01-JAN-02:15 0.00 15-OCT-08:00
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 811.52 0.00 01-JAN-00:15 0.00 16-OCT-11:00
HeatRejection:MainsWater 811.52 0.00 01-JAN-00:15 0.00 16-OCT-11:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 803.01 467.03 04-AUG-01:15 85436.49 12-FEB-08:45
PlantLoopHeatingDemand:Plant 793.92 467.03 04-AUG-01:15 50451.58 01-FEB-07:15
WaterSystems:PlantLoopHeatingDemand 793.92 467.03 04-AUG-01:15 50451.58 01-FEB-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2518.96 4244.55 12-FEB-02:15 358454.33 29-SEP-16:15
EnergyTransfer:Building 865.86 2278.32 07-MAY-15:45 151493.71 30-SEP-15:15
EnergyTransfer:Zone:G SW APARTMENT 8.01 0.03 09-JUL-21:00 2289.94 31-OCT-13:30
Heating:EnergyTransfer 25.41 0.00 01-JAN-07:30 55036.97 12-FEB-09:45
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.36 0.00 01-JAN-00:15 754.62 12-FEB-08:45
Cooling:EnergyTransfer 840.45 0.00 12-FEB-08:45 151493.71 30-SEP-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 7.66 0.00 02-JAN-02:45 2289.94 31-OCT-13:30
EnergyTransfer:Zone:G NW APARTMENT 5.48 0.03 05-SEP-19:30 1761.63 29-SEP-15:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 0.72 0.00 01-JAN-00:15 762.72 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G NW APARTMENT 4.76 0.00 01-JAN-00:30 1761.63 29-SEP-15:30
EnergyTransfer:Zone:OFFICE 17.50 0.08 06-DEC-01:45 2826.94 31-OCT-12:30
Heating:EnergyTransfer:Zone:OFFICE 0.04 0.00 01-JAN-00:15 334.20 30-MAR-05:30
Cooling:EnergyTransfer:Zone:OFFICE 17.45 0.00 01-JAN-00:30 2826.94 31-OCT-12:30
EnergyTransfer:Zone:G NE APARTMENT 5.44 0.01 21-SEP-09:00 1404.49 30-SEP-08:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.56 0.00 01-JAN-00:15 799.09 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G NE APARTMENT 4.88 0.00 01-JAN-00:30 1404.49 30-SEP-08:30
EnergyTransfer:Zone:G N1 APARTMENT 5.52 0.01 06-JAN-12:30 893.01 30-SEP-17:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.53 0.00 01-JAN-00:15 698.06 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 5.00 0.00 03-JAN-01:45 893.01 30-SEP-17:00
EnergyTransfer:Zone:G N2 APARTMENT 5.53 0.02 25-SEP-13:45 878.19 30-SEP-17:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.52 0.00 01-JAN-00:15 703.77 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 5.01 0.00 03-JAN-01:45 878.19 30-SEP-17:00
EnergyTransfer:Zone:G S1 APARTMENT 7.33 0.00 04-MAY-08:15 1504.98 30-OCT-12:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.07 0.00 01-JAN-00:15 648.15 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.27 0.00 13-JAN-16:30 1504.98 30-OCT-12:30
EnergyTransfer:Zone:G S2 APARTMENT 7.40 0.00 02-MAY-17:00 1560.64 30-OCT-12:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.06 0.00 01-JAN-00:15 637.07 12-FEB-08:45
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.34 0.00 13-JAN-16:30 1560.64 30-OCT-12:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 14.92 0.03 24-DEC-12:00 2937.99 31-OCT-14:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.38 0.00 01-JAN-00:15 453.33 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 14.54 0.00 03-JAN-11:15 2937.99 31-OCT-14:30
EnergyTransfer:Zone:F2 NW APARTMENT 8.39 0.01 27-NOV-23:30 2185.76 30-SEP-15:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 0.54 0.00 01-JAN-00:15 505.86 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 7.85 0.00 03-JAN-02:30 2185.76 30-SEP-15:30
EnergyTransfer:Zone:F2 SE APARTMENT 15.37 0.00 19-FEB-14:30 2690.50 31-OCT-13:30
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.25 0.00 01-JAN-00:15 481.27 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 15.12 0.00 03-JAN-11:15 2690.50 31-OCT-13:30
EnergyTransfer:Zone:F2 NE APARTMENT 7.95 0.02 10-OCT-19:30 1771.70 30-SEP-08:30
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.24 0.00 01-JAN-00:15 577.47 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 7.71 0.00 03-JAN-01:45 1771.70 30-SEP-08:30
EnergyTransfer:Zone:F2 N1 APARTMENT 7.08 0.01 10-MAY-13:30 1213.24 30-SEP-17:00
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.09 0.00 01-JAN-00:15 446.64 11-JAN-14:15
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 6.99 0.00 03-JAN-12:15 1213.24 30-SEP-17:00
EnergyTransfer:Zone:F2 N2 APARTMENT 7.07 0.00 13-NOV-13:30 1206.06 30-SEP-17:00
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.09 0.00 01-JAN-00:15 444.14 11-JAN-14:15
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 6.98 0.00 03-JAN-12:30 1206.06 30-SEP-17:00
EnergyTransfer:Zone:F2 S1 APARTMENT 12.82 0.00 11-MAY-15:15 1960.62 31-OCT-14:15
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.03 0.00 01-JAN-00:15 274.26 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 12.78 0.00 14-JAN-08:00 1960.62 31-OCT-14:15
EnergyTransfer:Zone:F2 S2 APARTMENT 12.90 0.00 01-JUL-07:00 1981.61 31-OCT-14:15
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.04 0.00 01-JAN-00:15 270.95 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 12.86 0.00 14-JAN-08:00 1981.61 31-OCT-14:15
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 16.68 0.07 10-JAN-10:30 2953.08 31-OCT-14:45
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.34 0.00 01-JAN-00:15 480.46 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 16.33 0.00 03-JAN-11:15 2953.08 31-OCT-14:45
EnergyTransfer:Zone:F3 NW APARTMENT 9.31 0.03 23-AUG-06:00 2213.31 30-SEP-15:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 0.47 0.00 01-JAN-00:15 578.41 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 8.84 0.00 03-JAN-11:15 2213.31 30-SEP-15:30
EnergyTransfer:Zone:F3 SE APARTMENT 16.14 0.02 20-OCT-19:15 2537.89 31-OCT-13:30
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.17 0.00 01-JAN-00:15 475.22 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 15.97 0.00 03-JAN-16:00 2537.89 31-OCT-13:30
EnergyTransfer:Zone:F3 NE APARTMENT 8.83 0.00 13-JUN-19:00 1812.31 30-SEP-08:30
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.19 0.00 01-JAN-00:15 611.39 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 8.63 0.00 03-JAN-04:00 1812.31 30-SEP-08:30
EnergyTransfer:Zone:F3 N1 APARTMENT 7.90 0.02 03-JUN-14:15 1246.35 14-OCT-17:15
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.05 0.00 01-JAN-00:15 478.05 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 7.85 0.00 03-JAN-12:45 1246.35 14-OCT-17:15
EnergyTransfer:Zone:F3 N2 APARTMENT 7.88 0.00 27-MAY-13:15 1238.89 30-SEP-17:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.05 0.00 01-JAN-00:15 484.64 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 7.83 0.00 03-JAN-12:45 1238.89 30-SEP-17:00
EnergyTransfer:Zone:F3 S1 APARTMENT 14.96 0.01 11-FEB-13:30 2033.76 03-DEC-12:45
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.03 0.00 01-JAN-00:15 463.44 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 14.93 0.00 15-JAN-07:45 2033.76 03-DEC-12:45
EnergyTransfer:Zone:F3 S2 APARTMENT 14.96 0.03 14-APR-15:15 2043.00 03-DEC-12:45
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.03 0.00 01-JAN-00:15 446.73 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 14.93 0.00 15-JAN-07:45 2043.00 03-DEC-12:45
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 16.74 0.01 14-FEB-01:45 2949.22 31-OCT-14:45
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.35 0.00 01-JAN-00:15 485.31 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 16.38 0.00 03-JAN-11:15 2949.22 31-OCT-14:45
EnergyTransfer:Zone:F4 NW APARTMENT 9.41 0.03 23-APR-09:30 2223.14 30-SEP-15:30
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 0.48 0.00 01-JAN-00:15 555.89 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 8.93 0.00 03-JAN-11:15 2223.14 30-SEP-15:30
EnergyTransfer:Zone:F4 SE APARTMENT 16.10 0.00 17-FEB-16:15 2562.12 31-OCT-13:30
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.18 0.00 01-JAN-00:15 504.07 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 15.92 0.00 03-JAN-16:00 2562.12 31-OCT-13:30
EnergyTransfer:Zone:F4 NE APARTMENT 8.96 0.01 16-JUL-19:30 1930.14 30-SEP-08:45
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.19 0.00 01-JAN-00:15 594.56 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 8.76 0.00 03-JAN-11:15 1930.14 30-SEP-08:45
EnergyTransfer:Zone:F4 N1 APARTMENT 8.11 0.01 21-MAY-10:15 1296.15 14-OCT-17:15
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.05 0.00 01-JAN-00:15 464.54 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 8.06 0.00 03-JAN-12:45 1296.15 14-OCT-17:15
EnergyTransfer:Zone:F4 N2 APARTMENT 8.09 0.01 13-MAY-12:30 1286.81 14-OCT-17:15
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.05 0.00 01-JAN-00:15 482.49 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 8.04 0.00 03-JAN-12:45 1286.81 14-OCT-17:15
EnergyTransfer:Zone:F4 S1 APARTMENT 15.29 0.00 24-MAY-08:45 2047.06 03-DEC-12:45
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.03 0.00 01-JAN-00:15 365.97 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 15.26 0.00 15-JAN-07:45 2047.06 03-DEC-12:45
EnergyTransfer:Zone:F4 S2 APARTMENT 15.27 0.01 06-JUN-10:00 2054.96 03-DEC-12:45
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.03 0.00 01-JAN-00:15 371.62 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 15.24 0.00 15-JAN-07:45 2054.96 03-DEC-12:45
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 16.87 0.11 12-FEB-15:30 2970.43 31-OCT-13:45
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.37 0.00 01-JAN-00:15 541.32 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M SW APARTMENT 16.49 0.00 03-JAN-11:15 2970.43 31-OCT-13:45
EnergyTransfer:Zone:M NW APARTMENT 9.57 0.00 28-MAY-12:45 2252.91 30-SEP-15:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.51 0.00 01-JAN-00:15 587.74 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M NW APARTMENT 9.07 0.00 03-JAN-11:15 2252.91 30-SEP-15:30
EnergyTransfer:Zone:M SE APARTMENT 16.24 0.00 18-OCT-20:00 2587.93 31-OCT-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.20 0.00 01-JAN-00:15 568.89 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M SE APARTMENT 16.05 0.00 03-JAN-15:45 2587.93 31-OCT-13:30
EnergyTransfer:Zone:M NE APARTMENT 9.13 0.00 03-AUG-20:45 1962.85 30-SEP-08:45
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.21 0.00 01-JAN-00:15 633.40 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M NE APARTMENT 8.92 0.00 03-JAN-11:15 1962.85 30-SEP-08:45
EnergyTransfer:Zone:M N1 APARTMENT 8.32 0.02 06-FEB-14:15 1340.52 14-OCT-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.06 0.00 01-JAN-00:15 478.13 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 8.27 0.00 03-JAN-12:45 1340.52 14-OCT-17:15
EnergyTransfer:Zone:M N2 APARTMENT 8.30 0.00 09-NOV-10:45 1331.29 14-OCT-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.06 0.00 01-JAN-00:15 494.41 12-FEB-09:45
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 8.24 0.00 03-JAN-12:45 1331.29 14-OCT-17:15
EnergyTransfer:Zone:M S1 APARTMENT 15.60 0.01 19-APR-15:45 2076.00 03-DEC-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.04 0.00 01-JAN-00:15 512.91 12-MAY-15:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 15.56 0.00 14-JAN-08:00 2076.00 03-DEC-12:45
EnergyTransfer:Zone:M S2 APARTMENT 15.57 0.01 16-MAY-11:00 2083.57 03-DEC-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.04 0.00 01-JAN-00:15 517.20 12-MAY-15:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 15.53 0.00 14-JAN-08:00 2083.57 03-DEC-12:45
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 15.61 0.02 15-NOV-15:00 2926.94 30-OCT-14:30
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.40 0.00 01-JAN-00:15 745.89 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 15.21 0.00 03-JAN-11:15 2926.94 30-OCT-14:30
EnergyTransfer:Zone:F6 NW APARTMENT 8.79 0.03 05-JUL-21:00 2213.68 30-SEP-15:30
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 0.55 0.00 01-JAN-00:15 704.88 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 8.25 0.00 03-JAN-11:15 2213.68 30-SEP-15:30
EnergyTransfer:Zone:F6 SE APARTMENT 15.05 0.00 25-APR-20:00 2542.82 30-OCT-12:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.22 0.00 01-JAN-00:15 783.79 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 14.84 0.00 03-JAN-14:00 2542.82 30-OCT-12:45
EnergyTransfer:Zone:F6 NE APARTMENT 8.46 0.00 02-AUG-20:15 1926.84 30-SEP-08:45
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.25 0.00 01-JAN-00:15 768.85 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 8.21 0.00 03-JAN-03:45 1926.84 30-SEP-08:45
EnergyTransfer:Zone:F6 N1 APARTMENT 7.75 0.02 13-NOV-13:30 1311.25 14-OCT-17:15
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.08 0.00 01-JAN-00:15 589.58 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 7.67 0.00 03-JAN-12:45 1311.25 14-OCT-17:15
EnergyTransfer:Zone:F6 N2 APARTMENT 7.73 0.02 10-MAY-12:15 1302.04 14-OCT-17:15
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.08 0.00 01-JAN-00:15 601.45 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 7.65 0.00 03-JAN-12:45 1302.04 14-OCT-17:15
EnergyTransfer:Zone:F6 S1 APARTMENT 14.48 0.00 13-MAR-15:45 2031.29 03-DEC-12:45
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.05 0.00 01-JAN-00:15 759.08 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 14.43 0.00 14-JAN-08:00 2031.29 03-DEC-12:45
EnergyTransfer:Zone:F6 S2 APARTMENT 14.46 0.01 29-MAY-16:45 2038.83 03-DEC-12:45
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.05 0.00 01-JAN-00:15 764.17 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 14.40 0.00 14-JAN-08:00 2038.83 03-DEC-12:45
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 14.82 0.05 02-FEB-10:00 2905.53 30-OCT-14:30
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.44 0.00 01-JAN-00:15 969.86 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 14.38 0.00 03-JAN-11:15 2905.53 30-OCT-14:30
EnergyTransfer:Zone:F7 NW APARTMENT 8.34 0.07 24-OCT-00:45 2198.38 30-SEP-15:30
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 0.60 0.00 01-JAN-00:15 822.97 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 7.74 0.00 03-JAN-03:30 2198.38 30-SEP-15:30
EnergyTransfer:Zone:F7 SE APARTMENT 14.31 0.00 28-APR-09:30 2526.69 30-OCT-12:45
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.24 0.00 01-JAN-00:15 1010.27 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 14.06 0.00 03-JAN-14:00 2526.69 30-OCT-12:45
EnergyTransfer:Zone:F7 NE APARTMENT 8.08 0.01 08-OCT-19:30 1913.43 30-SEP-08:45
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 0.30 0.00 01-JAN-00:15 925.76 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 7.78 0.00 03-JAN-02:00 1913.43 30-SEP-08:45
EnergyTransfer:Zone:F7 N1 APARTMENT 7.42 0.01 12-JUN-15:00 1298.63 14-OCT-17:15
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.11 0.00 01-JAN-00:15 694.28 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 7.31 0.00 03-JAN-12:30 1298.63 14-OCT-17:15
EnergyTransfer:Zone:F7 N2 APARTMENT 7.41 0.00 23-JAN-15:30 1289.41 14-OCT-17:15
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.11 0.00 01-JAN-00:15 704.61 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 7.29 0.00 03-JAN-12:45 1289.41 14-OCT-17:15
EnergyTransfer:Zone:F7 S1 APARTMENT 13.79 0.01 10-NOV-15:30 2011.81 03-DEC-12:45
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.06 0.00 01-JAN-00:15 969.39 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 13.73 0.00 14-JAN-08:00 2011.81 03-DEC-12:45
EnergyTransfer:Zone:F7 S2 APARTMENT 13.76 0.01 06-OCT-18:00 2019.42 03-DEC-12:45
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.07 0.00 01-JAN-00:15 975.33 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 13.70 0.00 14-JAN-08:00 2019.42 03-DEC-12:45
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 14.17 0.03 11-JAN-14:00 2898.08 30-OCT-14:30
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.48 0.00 01-JAN-00:15 1168.35 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 13.69 0.00 03-JAN-11:15 2898.08 30-OCT-14:30
EnergyTransfer:Zone:F8 NW APARTMENT 8.03 0.12 25-APR-11:15 2194.13 30-SEP-15:30
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 0.67 0.00 01-JAN-00:15 962.58 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 7.36 0.00 03-JAN-02:00 2194.13 30-SEP-15:30
EnergyTransfer:Zone:F8 SE APARTMENT 13.70 0.00 21-JUN-20:45 2522.92 30-OCT-12:45
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.28 0.00 01-JAN-00:15 1210.02 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 13.42 0.00 03-JAN-11:15 2522.92 30-OCT-12:45
EnergyTransfer:Zone:F8 NE APARTMENT 7.81 0.00 07-OCT-17:45 1911.01 30-SEP-08:45
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 0.37 0.00 01-JAN-00:15 1092.53 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 7.45 0.00 03-JAN-01:45 1911.01 30-SEP-08:45
EnergyTransfer:Zone:F8 N1 APARTMENT 7.20 0.00 07-JUN-14:30 1295.83 30-SEP-16:45
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.16 0.00 01-JAN-00:15 797.28 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 7.04 0.00 03-JAN-12:15 1295.83 30-SEP-16:45
EnergyTransfer:Zone:F8 N2 APARTMENT 7.19 0.00 05-APR-12:45 1283.45 30-SEP-16:45
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.16 0.00 01-JAN-00:15 806.76 12-FEB-09:45
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 7.03 0.00 03-JAN-12:15 1283.45 30-SEP-16:45
EnergyTransfer:Zone:F8 S1 APARTMENT 13.23 0.01 03-JUL-18:45 2003.69 03-DEC-12:45
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.08 0.00 01-JAN-00:15 1155.30 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 13.14 0.00 14-JAN-08:00 2003.69 03-DEC-12:45
EnergyTransfer:Zone:F8 S2 APARTMENT 13.20 0.01 01-AUG-09:15 2011.26 03-DEC-12:45
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.08 0.00 01-JAN-00:15 1161.70 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 13.12 0.00 14-JAN-08:00 2011.26 03-DEC-12:45
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 13.40 0.02 18-MAY-10:15 2960.95 30-OCT-14:30
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.58 0.00 01-JAN-00:15 1374.98 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 12.82 0.00 03-JAN-11:15 2960.95 30-OCT-14:30
EnergyTransfer:Zone:F9 NW APARTMENT 7.81 0.01 16-DEC-23:00 2240.65 30-SEP-15:30
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 0.85 0.00 01-JAN-00:15 1154.65 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 6.96 0.00 02-JAN-02:15 2240.65 30-SEP-15:30
EnergyTransfer:Zone:F9 SE APARTMENT 12.93 0.00 19-JAN-18:45 2568.08 31-OCT-13:30
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.36 0.00 01-JAN-00:15 1414.10 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 12.57 0.00 03-JAN-11:15 2568.08 31-OCT-13:30
EnergyTransfer:Zone:F9 NE APARTMENT 7.58 0.00 18-SEP-11:00 1913.95 30-SEP-08:45
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 0.50 0.00 01-JAN-00:15 1270.41 12-FEB-08:45
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 7.08 0.00 02-JAN-02:45 1913.95 30-SEP-08:45
EnergyTransfer:Zone:F9 N1 APARTMENT 6.98 0.01 19-MAY-14:15 1359.68 30-SEP-16:45
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.28 0.00 01-JAN-00:15 1005.56 24-FEB-14:45
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 6.70 0.00 03-JAN-11:30 1359.68 30-SEP-16:45
EnergyTransfer:Zone:F9 N2 APARTMENT 6.97 0.01 25-JAN-09:30 1347.30 30-SEP-16:45
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.28 0.00 01-JAN-00:15 1018.43 24-FEB-14:45
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 6.69 0.00 03-JAN-12:00 1347.30 30-SEP-16:45
EnergyTransfer:Zone:F9 S1 APARTMENT 12.45 0.00 14-FEB-12:15 2008.46 31-OCT-13:30
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.12 0.00 01-JAN-00:15 1345.83 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 12.33 0.00 07-JAN-09:15 2008.46 31-OCT-13:30
EnergyTransfer:Zone:F9 S2 APARTMENT 12.42 0.02 08-AUG-18:30 2016.88 31-OCT-13:30
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.12 0.00 01-JAN-00:15 1351.97 12-MAY-15:15
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 12.30 0.00 07-JAN-09:15 2016.88 31-OCT-13:30
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 13.11 0.00 27-MAR-04:00 3558.10 30-OCT-14:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.25 0.00 01-JAN-00:15 1945.47 25-MAR-10:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 11.86 0.00 01-JAN-03:30 3558.10 30-OCT-14:30
EnergyTransfer:Zone:T NW APARTMENT 8.22 0.03 10-JUN-22:30 2805.90 29-SEP-15:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 1.84 0.00 01-JAN-07:30 1524.52 24-FEB-14:45
Cooling:EnergyTransfer:Zone:T NW APARTMENT 6.38 0.00 01-JAN-00:15 2805.90 29-SEP-15:30
EnergyTransfer:Zone:T SE APARTMENT 12.61 0.00 12-NOV-05:15 3102.43 31-OCT-13:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.98 0.00 01-JAN-00:15 1944.46 25-MAR-10:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 11.64 0.00 01-JAN-03:30 3102.43 31-OCT-13:30
EnergyTransfer:Zone:T NE APARTMENT 7.91 0.00 28-JUL-18:15 2198.74 29-SEP-10:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 1.40 0.00 01-JAN-07:15 1590.83 24-FEB-14:45
Cooling:EnergyTransfer:Zone:T NE APARTMENT 6.51 0.00 01-JAN-00:15 2198.74 29-SEP-10:00
EnergyTransfer:Zone:T N1 APARTMENT 6.45 0.01 05-SEP-08:45 1669.81 29-SEP-13:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.61 0.00 01-JAN-00:15 1464.65 24-FEB-14:45
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 5.84 0.00 02-JAN-02:00 1669.81 29-SEP-13:15
EnergyTransfer:Zone:T N2 APARTMENT 6.44 0.00 02-AUG-19:00 1673.62 29-SEP-13:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.62 0.00 01-JAN-00:15 1471.90 24-FEB-14:45
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 5.82 0.00 02-JAN-02:00 1673.62 29-SEP-13:15
EnergyTransfer:Zone:T S1 APARTMENT 11.41 0.03 02-MAR-13:45 2615.76 30-OCT-12:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.50 0.00 01-JAN-00:15 1750.00 25-MAR-10:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.91 0.00 03-JAN-03:30 2615.76 30-OCT-12:45
EnergyTransfer:Zone:T S2 APARTMENT 11.41 0.00 03-MAR-14:30 2620.87 30-OCT-12:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.51 0.00 01-JAN-00:15 1753.22 25-MAR-10:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.90 0.00 03-JAN-03:30 2620.87 30-OCT-12:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 794.39 467.03 04-AUG-01:15 64859.86 30-MAR-05:15
WaterSystems:EnergyTransfer 793.92 467.03 04-AUG-01:15 50446.42 01-FEB-07:15
sub cat:WaterSystems:EnergyTransfer 793.92 467.03 04-AUG-01:15 50446.42 01-FEB-07:15
EnergyTransfer:HVAC 858.71 0.00 14-JAN-19:30 199461.04 18-AUG-14:30
CoolingCoils:EnergyTransfer 847.00 0.00 01-JAN-00:15 199461.04 18-AUG-14:30
HeatingCoils:EnergyTransfer 11.71 0.00 01-JAN-08:00 48120.29 12-FEB-08:45
PlantLoopHeatingDemand:HVAC 9.08 0.00 01-JAN-08:00 37173.69 12-FEB-08:45
HeatingCoils:PlantLoopHeatingDemand 9.08 0.00 01-JAN-08:00 37173.69 12-FEB-08:45
Boilers:EnergyTransfer 0.47 0.00 01-JAN-00:15 20581.75 30-MAR-04:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.358 -7.656 0.000 0.000 3.712 2.413 12.213 20.664 0.000 0.056 0.000 0.000 -7.779 0.000 -9.813 -14.168
G NW APARTMENT 0.720 -4.761 0.000 0.000 3.787 2.413 12.213 11.157 0.000 0.058 0.000 0.000 -7.579 0.000 -8.668 -9.339
OFFICE 0.043 -17.454 0.000 0.000 0.504 21.954 7.547 19.725 0.000 0.017 0.000 0.000 -7.765 0.000 -1.247 -23.326
G NE APARTMENT 0.559 -4.883 0.000 0.000 3.817 2.413 12.213 10.173 0.000 0.056 0.000 0.000 -7.268 0.000 -8.495 -8.585
G N1 APARTMENT 0.525 -4.997 0.000 0.000 3.827 2.413 12.213 3.616 0.000 0.054 0.000 0.000 -4.549 0.000 -7.472 -5.630
G N2 APARTMENT 0.524 -5.005 0.000 0.000 3.830 2.413 12.213 3.616 0.000 0.053 0.000 0.000 -4.541 0.000 -7.458 -5.644
G S1 APARTMENT 0.067 -7.266 0.000 0.000 3.718 2.413 12.213 13.278 0.000 0.048 0.000 0.000 -4.753 0.000 -8.818 -10.899
G S2 APARTMENT 0.064 -7.340 0.000 0.000 3.713 2.413 12.213 13.263 0.000 0.048 0.000 0.000 -4.762 0.000 -8.894 -10.718
F2 SW APARTMENT 0.376 -14.544 0.000 0.000 3.576 2.413 12.213 19.590 0.000 0.069 0.001 0.000 -8.634 0.000 -12.193 -2.868
F2 NW APARTMENT 0.540 -7.855 0.000 0.000 3.655 2.413 12.213 10.309 0.000 0.070 0.000 0.000 -8.395 0.000 -11.003 -1.946
F2 SE APARTMENT 0.248 -15.118 0.000 0.000 3.577 2.413 12.213 18.785 0.000 0.068 0.000 0.000 -8.564 0.000 -12.286 -1.335
F2 NE APARTMENT 0.235 -7.710 0.000 0.000 3.685 2.413 12.213 9.423 0.000 0.069 0.000 0.000 -8.048 0.000 -10.812 -1.469
F2 N1 APARTMENT 0.093 -6.987 0.000 0.000 3.682 2.413 12.213 3.173 0.000 0.060 0.047 0.000 -5.103 0.000 -9.590 -0.000
F2 N2 APARTMENT 0.091 -6.979 0.000 0.000 3.685 2.413 12.213 3.174 0.000 0.060 0.008 0.000 -5.094 0.000 -9.570 -0.000
F2 S1 APARTMENT 0.035 -12.784 0.000 0.000 3.575 2.413 12.213 12.630 0.000 0.054 0.001 0.000 -5.276 0.000 -11.108 -1.753
F2 S2 APARTMENT 0.037 -12.858 0.000 0.000 3.574 2.413 12.213 12.627 0.000 0.054 0.001 0.000 -5.278 0.000 -11.124 -1.658
F3 SW APARTMENT 0.342 -16.335 0.000 0.000 3.561 2.413 12.213 19.132 0.000 0.077 0.550 0.000 -8.822 0.000 -13.130 -0.000
F3 NW APARTMENT 0.475 -8.835 0.000 0.000 3.625 2.413 12.213 9.951 0.000 0.078 0.736 0.000 -8.639 0.000 -12.017 -0.000
F3 SE APARTMENT 0.172 -15.970 0.000 0.000 3.568 2.413 12.213 18.429 0.000 0.073 0.894 0.000 -8.704 0.000 -13.088 -0.000
F3 NE APARTMENT 0.192 -8.635 0.000 0.000 3.651 2.413 12.213 9.127 0.000 0.077 1.081 0.000 -8.293 0.000 -11.827 -0.000
F3 N1 APARTMENT 0.054 -7.847 0.000 0.000 3.639 2.413 12.213 3.006 0.000 0.066 2.295 0.000 -5.287 0.000 -10.551 -0.000
F3 N2 APARTMENT 0.053 -7.830 0.000 0.000 3.641 2.413 12.213 3.007 0.000 0.065 2.246 0.000 -5.278 0.000 -10.531 -0.000
F3 S1 APARTMENT 0.028 -14.933 0.000 0.000 3.556 2.413 12.213 12.356 0.000 0.057 1.683 0.000 -5.406 0.000 -11.968 -0.000
F3 S2 APARTMENT 0.029 -14.932 0.000 0.000 3.556 2.413 12.213 12.355 0.000 0.057 1.682 0.000 -5.404 0.000 -11.968 -0.000
F4 SW APARTMENT 0.352 -16.384 0.000 0.000 3.559 2.413 12.213 18.843 0.000 0.083 1.567 0.000 -8.893 0.000 -13.754 -0.000
F4 NW APARTMENT 0.479 -8.931 0.000 0.000 3.619 2.413 12.213 9.743 0.000 0.084 1.755 0.000 -8.733 0.000 -12.642 -0.000
F4 SE APARTMENT 0.177 -15.924 0.000 0.000 3.568 2.413 12.213 18.197 0.000 0.078 1.727 0.000 -8.765 0.000 -13.685 -0.000
F4 NE APARTMENT 0.194 -8.765 0.000 0.000 3.644 2.413 12.213 8.966 0.000 0.083 2.092 0.000 -8.389 0.000 -12.450 -0.000
F4 N1 APARTMENT 0.052 -8.062 0.000 0.000 3.627 2.413 12.213 2.919 0.000 0.070 3.242 0.000 -5.364 0.000 -11.110 -0.000
F4 N2 APARTMENT 0.050 -8.041 0.000 0.000 3.629 2.413 12.213 2.920 0.000 0.070 3.192 0.000 -5.355 0.000 -11.090 -0.000
F4 S1 APARTMENT 0.031 -15.258 0.000 0.000 3.554 2.413 12.213 12.187 0.000 0.061 2.751 0.000 -5.455 0.000 -12.496 -0.000
F4 S2 APARTMENT 0.033 -15.236 0.000 0.000 3.554 2.413 12.213 12.186 0.000 0.061 2.722 0.000 -5.453 0.000 -12.494 -0.001
M SW APARTMENT 0.373 -16.493 0.000 0.000 3.559 2.413 12.213 18.611 0.000 0.087 2.486 0.000 -8.953 0.000 -14.296 -0.001
M NW APARTMENT 0.506 -9.068 0.000 0.000 3.616 2.413 12.213 9.582 0.000 0.088 2.619 0.000 -8.800 0.000 -13.169 0.000
M SE APARTMENT 0.197 -16.045 0.000 0.000 3.567 2.413 12.213 18.007 0.000 0.082 2.607 0.000 -8.823 0.000 -14.218 -0.000
M NE APARTMENT 0.214 -8.919 0.000 0.000 3.640 2.413 12.213 8.844 0.000 0.087 2.939 0.000 -8.456 0.000 -12.973 -0.000
M N1 APARTMENT 0.057 -8.267 0.000 0.000 3.620 2.413 12.213 2.853 0.000 0.073 4.026 0.000 -5.416 0.000 -11.574 0.000
M N2 APARTMENT 0.055 -8.243 0.000 0.000 3.623 2.413 12.213 2.854 0.000 0.073 3.974 0.000 -5.407 0.000 -11.554 0.000
M S1 APARTMENT 0.040 -15.559 0.000 0.000 3.553 2.413 12.213 12.052 0.000 0.064 3.677 0.000 -5.496 0.000 -12.956 -0.000
M S2 APARTMENT 0.041 -15.531 0.000 0.000 3.553 2.413 12.213 12.052 0.000 0.064 3.641 0.000 -5.494 0.000 -12.952 -0.000
F6 SW APARTMENT 0.401 -15.210 0.000 0.000 3.567 2.413 12.213 18.463 0.000 0.096 1.639 0.000 -8.939 0.000 -14.644 -0.000
F6 NW APARTMENT 0.548 -8.246 0.000 0.000 3.631 2.413 12.213 9.506 0.000 0.098 2.008 0.000 -8.759 0.000 -13.412 0.000
F6 SE APARTMENT 0.217 -14.837 0.000 0.000 3.577 2.413 12.213 17.893 0.000 0.091 1.791 0.000 -8.804 0.000 -14.553 -0.000
F6 NE APARTMENT 0.250 -8.214 0.000 0.000 3.657 2.413 12.213 8.803 0.000 0.096 2.392 0.000 -8.410 0.000 -13.200 -0.000
F6 N1 APARTMENT 0.079 -7.669 0.000 0.000 3.637 2.413 12.213 2.836 0.000 0.081 3.519 0.000 -5.388 0.000 -11.720 0.000
F6 N2 APARTMENT 0.078 -7.653 0.000 0.000 3.639 2.413 12.213 2.837 0.000 0.081 3.471 0.000 -5.380 0.000 -11.700 0.000
F6 S1 APARTMENT 0.051 -14.431 0.000 0.000 3.560 2.413 12.213 11.967 0.000 0.071 2.852 0.000 -5.490 0.000 -13.206 -0.000
F6 S2 APARTMENT 0.053 -14.403 0.000 0.000 3.561 2.413 12.213 11.967 0.000 0.071 2.815 0.000 -5.487 0.000 -13.202 -0.000
F7 SW APARTMENT 0.436 -14.380 0.000 0.000 3.574 2.413 12.213 18.328 0.000 0.099 1.233 0.000 -8.937 0.000 -14.978 -0.000
F7 NW APARTMENT 0.601 -7.738 0.000 0.000 3.644 2.413 12.213 9.435 0.000 0.101 1.720 0.000 -8.731 0.000 -13.658 0.000
F7 SE APARTMENT 0.244 -14.062 0.000 0.000 3.584 2.413 12.213 17.787 0.000 0.094 1.404 0.000 -8.799 0.000 -14.877 -0.000
F7 NE APARTMENT 0.300 -7.779 0.000 0.000 3.671 2.413 12.213 8.763 0.000 0.099 2.130 0.000 -8.377 0.000 -13.433 -0.000
F7 N1 APARTMENT 0.114 -7.307 0.000 0.000 3.650 2.413 12.213 2.819 0.000 0.084 3.269 0.000 -5.368 0.000 -11.885 0.000
F7 N2 APARTMENT 0.113 -7.294 0.000 0.000 3.653 2.413 12.213 2.820 0.000 0.083 3.222 0.000 -5.359 0.000 -11.864 0.000
F7 S1 APARTMENT 0.065 -13.726 0.000 0.000 3.566 2.413 12.213 11.889 0.000 0.074 2.456 0.000 -5.491 0.000 -13.459 -0.000
F7 S2 APARTMENT 0.067 -13.698 0.000 0.000 3.566 2.413 12.213 11.889 0.000 0.074 2.419 0.000 -5.488 0.000 -13.454 -0.000
F8 SW APARTMENT 0.477 -13.691 0.000 0.000 3.580 2.413 12.213 18.209 0.000 0.102 0.922 0.000 -8.935 0.000 -15.290 -0.000
F8 NW APARTMENT 0.673 -7.355 0.000 0.000 3.655 2.413 12.213 9.373 0.000 0.104 1.520 0.000 -8.705 0.000 -13.892 0.000
F8 SE APARTMENT 0.279 -13.422 0.000 0.000 3.591 2.413 12.213 17.694 0.000 0.097 1.109 0.000 -8.795 0.000 -15.180 -0.000
F8 NE APARTMENT 0.368 -7.446 0.000 0.000 3.684 2.413 12.213 8.729 0.000 0.101 1.941 0.000 -8.348 0.000 -13.655 -0.000
F8 N1 APARTMENT 0.165 -7.037 0.000 0.000 3.663 2.413 12.213 2.803 0.000 0.086 3.094 0.000 -5.349 0.000 -12.050 -0.000
F8 N2 APARTMENT 0.165 -7.026 0.000 0.000 3.666 2.413 12.213 2.804 0.000 0.085 3.046 0.000 -5.339 0.000 -12.028 0.000
F8 S1 APARTMENT 0.082 -13.144 0.000 0.000 3.572 2.413 12.213 11.821 0.000 0.076 2.160 0.000 -5.492 0.000 -13.701 -0.000
F8 S2 APARTMENT 0.085 -13.116 0.000 0.000 3.572 2.413 12.213 11.821 0.000 0.076 2.121 0.000 -5.489 0.000 -13.696 -0.000
F9 SW APARTMENT 0.580 -12.824 0.000 0.000 3.591 2.413 12.213 18.131 0.000 0.105 0.226 0.000 -8.908 0.000 -15.526 -0.001
F9 NW APARTMENT 0.847 -6.961 0.000 0.000 3.669 2.413 12.213 9.341 0.000 0.106 1.086 0.000 -8.661 0.000 -14.054 -0.000
F9 SE APARTMENT 0.356 -12.575 0.000 0.000 3.603 2.413 12.213 17.638 0.000 0.101 0.434 0.000 -8.765 0.000 -15.418 -0.000
F9 NE APARTMENT 0.496 -7.083 0.000 0.000 3.700 2.413 12.213 8.722 0.000 0.104 1.548 0.000 -8.302 0.000 -13.811 -0.000
F9 N1 APARTMENT 0.283 -6.701 0.000 0.000 3.679 2.413 12.213 2.803 0.000 0.088 2.700 0.000 -5.316 0.000 -12.161 -0.000
F9 N2 APARTMENT 0.282 -6.690 0.000 0.000 3.682 2.413 12.213 2.804 0.000 0.088 2.654 0.000 -5.306 0.000 -12.138 -0.000
F9 S1 APARTMENT 0.122 -12.328 0.000 0.000 3.581 2.413 12.213 11.776 0.000 0.079 1.505 0.000 -5.480 0.000 -13.881 -0.000
F9 S2 APARTMENT 0.124 -12.298 0.000 0.000 3.582 2.413 12.213 11.775 0.000 0.079 1.465 0.000 -5.476 0.000 -13.877 -0.000
T SW APARTMENT 1.248 -11.863 0.000 0.000 3.663 2.413 12.213 17.863 0.000 0.107 0.000 0.000 -8.382 0.000 -15.552 -1.709
T NW APARTMENT 1.839 -6.381 0.000 0.000 3.727 2.413 12.213 9.118 0.000 0.108 0.000 0.000 -8.188 0.000 -14.200 -0.649
T SE APARTMENT 0.979 -11.636 0.000 0.000 3.680 2.413 12.213 17.409 0.000 0.102 0.000 0.000 -8.254 0.000 -15.459 -1.446
T NE APARTMENT 1.397 -6.514 0.000 0.000 3.763 2.413 12.213 8.552 0.000 0.104 0.000 0.000 -7.858 0.000 -13.965 -0.106
T N1 APARTMENT 0.611 -5.843 0.000 0.000 3.741 2.413 12.213 2.745 0.000 0.088 1.287 0.000 -5.015 0.000 -12.239 -0.000
T N2 APARTMENT 0.618 -5.822 0.000 0.000 3.744 2.413 12.213 2.742 0.000 0.088 1.234 0.000 -5.002 0.000 -12.228 -0.000
T S1 APARTMENT 0.505 -10.909 0.000 0.000 3.646 2.413 12.213 11.643 0.000 0.082 0.001 0.000 -5.217 0.000 -13.928 -0.448
T S2 APARTMENT 0.511 -10.897 0.000 0.000 3.647 2.413 12.213 11.641 0.000 0.082 0.000 0.000 -5.211 0.000 -13.924 -0.473
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 4.534 0.000 0.205 3.474 0.000 -1.854 0.000 -24.889 -0.001
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.095 0.000 0.002 0.000 0.000 -1.114 0.000 -0.375 -19.137
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.023 0.000 0.002 0.000 0.000 -1.162 0.000 -0.466 -18.927
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.981 0.000 0.003 0.000 0.000 -1.185 0.000 -0.531 -18.797
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 1.936 0.000 0.002 0.000 0.000 -1.217 0.000 -0.616 -37.164
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.941 0.000 0.003 0.000 0.000 -1.191 0.000 -0.615 -18.667
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.935 0.000 0.003 0.000 0.000 -1.181 0.000 -0.641 -18.646
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.925 0.000 0.003 0.000 0.000 -1.178 0.000 -0.667 -18.613
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.920 0.000 0.004 0.000 0.000 -1.175 0.000 -0.689 -18.589
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 1.862 0.000 0.002 0.000 0.000 -1.138 0.000 -0.758 -26.434
Total Facility 25.414 -840.451 0.000 0.000 287.619 416.414 980.287 881.495 0.000 6.514 128.113 0.000 -563.868 0.000 -1022.387 -299.154


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 31-OCT-13:30 0.00 -2290.19 0.00 0.00 40.75 28.81 382.60 3881.74 0.00 219.40 0.00 0.00 0.00 0.00 0.00 -2263.11
G NW APARTMENT 29-SEP-15:30 0.00 -1761.70 0.00 0.00 48.90 100.83 470.89 2339.26 0.00 67.95 0.00 0.00 0.00 0.00 0.00 -1266.13
OFFICE 31-OCT-12:30 0.00 -2827.52 0.00 0.00 65.19 1622.33 544.91 3304.64 0.00 23.34 0.00 0.00 0.00 0.00 0.00 -2732.88
G NE APARTMENT 30-SEP-08:30 0.00 -1404.23 0.00 0.00 40.75 28.81 394.37 1950.57 0.00 141.46 0.00 0.00 0.00 0.00 0.00 -1151.73
G N1 APARTMENT 30-SEP-16:53 0.00 -894.88 0.00 0.00 84.76 144.04 588.62 61.61 0.00 115.33 0.00 0.00 0.00 0.00 0.00 -99.49
G N2 APARTMENT 30-SEP-16:53 0.00 -879.87 0.00 0.00 84.76 144.04 588.62 61.83 0.00 115.06 0.00 0.00 0.00 0.00 0.00 -114.43
G S1 APARTMENT 30-OCT-12:30 0.00 -1505.83 0.00 0.00 40.75 28.81 388.49 3003.65 0.00 38.17 0.00 0.00 0.00 0.00 0.00 -1994.03
G S2 APARTMENT 30-OCT-12:30 0.00 -1561.53 0.00 0.00 40.75 28.81 388.49 3002.94 0.00 39.47 0.00 0.00 0.00 0.00 0.00 -1938.93
F2 SW APARTMENT 31-OCT-14:30 0.00 -2938.33 0.00 0.00 40.05 50.41 400.26 3580.13 0.00 34.02 0.00 0.00 0.00 0.00 0.00 -1166.55
F2 NW APARTMENT 30-SEP-15:30 0.00 -2186.04 0.00 0.00 48.90 100.83 470.89 2174.74 0.00 35.07 0.00 0.00 0.00 0.00 0.00 -644.39
F2 SE APARTMENT 31-OCT-13:30 0.00 -2690.92 0.00 0.00 39.89 28.81 382.60 2810.07 0.00 197.51 0.00 0.00 0.00 0.00 0.00 -767.96
F2 NE APARTMENT 30-SEP-08:30 0.00 -1771.42 0.00 0.00 40.75 28.81 394.37 1922.35 0.00 146.89 0.00 0.00 0.00 0.00 0.00 -761.75
F2 N1 APARTMENT 30-SEP-16:53 0.00 -1213.55 0.00 0.00 84.76 144.04 588.62 52.76 0.00 115.26 228.11 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 30-SEP-16:53 0.00 -1206.36 0.00 0.00 84.76 144.04 588.62 52.90 0.00 115.26 220.79 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 31-OCT-14:15 0.00 -1960.51 0.00 0.00 38.34 50.41 400.26 2227.01 0.00 23.39 0.00 0.00 0.00 0.00 0.00 -778.90
F2 S2 APARTMENT 31-OCT-14:15 0.00 -1981.50 0.00 0.00 38.37 50.41 400.26 2227.05 0.00 24.75 0.00 0.00 0.00 0.00 0.00 -759.35
F3 SW APARTMENT 31-OCT-14:45 0.00 -2953.69 0.00 0.00 39.85 50.41 400.26 3338.24 0.00 0.00 0.00 0.00 0.00 0.00 -21.23 -853.85
F3 NW APARTMENT 30-SEP-15:30 0.00 -2213.60 0.00 0.00 48.90 100.83 470.89 2161.46 0.00 41.38 0.00 0.00 0.00 0.00 0.00 -609.86
F3 SE APARTMENT 31-OCT-13:30 0.00 -2538.29 0.00 0.00 39.04 28.81 382.60 2770.31 0.00 170.98 0.00 0.00 0.00 0.00 0.00 -853.45
F3 NE APARTMENT 30-SEP-08:30 0.00 -1812.03 0.00 0.00 40.75 28.81 394.37 1909.43 0.00 149.91 0.00 0.00 0.00 0.00 0.00 -711.25
F3 N1 APARTMENT 14-OCT-17:05 0.00 -1246.56 0.00 0.00 141.81 194.45 588.62 0.00 0.00 213.47 147.58 0.00 -39.37 0.00 0.00 0.00
F3 N2 APARTMENT 30-SEP-16:53 0.00 -1239.20 0.00 0.00 84.76 144.04 588.62 52.08 0.00 114.16 255.54 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 03-DEC-12:45 0.00 -2033.62 0.00 0.00 40.72 28.81 406.15 2732.18 0.00 0.00 0.00 0.00 0.00 0.00 -57.39 -1116.84
F3 S2 APARTMENT 03-DEC-12:45 0.00 -2042.85 0.00 0.00 40.73 28.81 406.15 2732.16 0.00 0.00 0.00 0.00 0.00 0.00 -57.35 -1107.64
F4 SW APARTMENT 31-OCT-14:45 0.00 -2949.84 0.00 0.00 39.82 50.41 400.26 3294.30 0.00 0.00 0.00 0.00 0.00 0.00 -26.89 -808.06
F4 NW APARTMENT 30-SEP-15:30 0.00 -2223.44 0.00 0.00 48.90 100.83 470.89 2151.12 0.00 46.09 0.00 0.00 0.00 0.00 0.00 -594.39
F4 SE APARTMENT 31-OCT-13:30 0.00 -2562.52 0.00 0.00 39.06 28.81 382.60 2748.84 0.00 182.31 0.00 0.00 0.00 0.00 0.00 -819.11
F4 NE APARTMENT 30-SEP-08:45 0.00 -1929.73 0.00 0.00 40.75 28.81 394.37 1855.31 0.00 242.31 0.00 0.00 0.00 0.00 0.00 -631.83
F4 N1 APARTMENT 14-OCT-17:05 0.00 -1296.36 0.00 0.00 141.81 194.45 588.62 0.00 0.00 224.94 185.72 0.00 -39.19 0.00 0.00 0.00
F4 N2 APARTMENT 14-OCT-17:05 0.00 -1287.02 0.00 0.00 141.81 194.45 588.62 0.00 0.00 224.94 176.15 0.00 -38.95 0.00 0.00 0.00
F4 S1 APARTMENT 03-DEC-12:45 0.00 -2046.93 0.00 0.00 40.67 28.81 406.15 2712.61 0.00 0.00 0.00 0.00 0.00 0.00 -64.48 -1076.82
F4 S2 APARTMENT 03-DEC-12:45 0.00 -2054.83 0.00 0.00 40.68 28.81 406.15 2712.61 0.00 0.00 0.00 0.00 0.00 0.00 -64.44 -1068.98
M SW APARTMENT 31-OCT-13:45 0.00 -2970.48 0.00 0.00 39.86 28.81 382.60 3656.38 0.00 187.25 0.00 0.00 0.00 0.00 0.00 -1324.42
M NW APARTMENT 30-SEP-15:30 0.00 -2253.24 0.00 0.00 48.90 100.83 470.89 2141.69 0.00 49.91 0.00 0.00 0.00 0.00 0.00 -558.98
M SE APARTMENT 31-OCT-13:30 0.00 -2588.34 0.00 0.00 39.09 28.81 382.60 2731.39 0.00 191.24 0.00 0.00 0.00 0.00 0.00 -784.78
M NE APARTMENT 30-SEP-08:45 0.00 -1962.43 0.00 0.00 40.75 28.81 394.37 1845.75 0.00 246.15 0.00 0.00 0.00 0.00 0.00 -593.40
M N1 APARTMENT 14-OCT-17:05 0.00 -1340.72 0.00 0.00 141.81 194.45 588.62 0.00 0.00 234.08 220.97 0.00 -39.21 0.00 0.00 0.00
M N2 APARTMENT 14-OCT-17:05 0.00 -1331.49 0.00 0.00 141.81 194.45 588.62 0.00 0.00 234.08 211.50 0.00 -38.98 0.00 0.00 0.00
M S1 APARTMENT 03-DEC-12:45 0.00 -2075.88 0.00 0.00 40.69 28.81 406.15 2697.05 0.00 0.00 0.00 0.00 0.00 0.00 -70.13 -1026.69
M S2 APARTMENT 03-DEC-12:45 0.00 -2083.44 0.00 0.00 40.70 28.81 406.15 2697.03 0.00 0.00 0.00 0.00 0.00 0.00 -70.09 -1019.15
F6 SW APARTMENT 30-OCT-14:30 0.00 -2926.96 0.00 0.00 39.82 50.41 400.26 3510.09 0.00 253.77 0.00 0.00 0.00 0.00 0.00 -1327.40
F6 NW APARTMENT 30-SEP-15:30 0.00 -2214.02 0.00 0.00 48.90 100.83 470.89 2135.20 0.00 53.15 0.00 0.00 0.00 0.00 0.00 -594.96
F6 SE APARTMENT 30-OCT-12:45 0.00 -2543.91 0.00 0.00 40.36 28.81 388.49 2990.80 0.00 94.87 0.00 0.00 0.00 0.00 0.00 -999.42
F6 NE APARTMENT 30-SEP-08:45 0.00 -1926.41 0.00 0.00 40.75 28.81 394.37 1839.54 0.00 249.21 0.00 0.00 0.00 0.00 0.00 -626.28
F6 N1 APARTMENT 14-OCT-17:05 0.00 -1311.45 0.00 0.00 141.81 194.45 588.62 0.00 0.00 241.59 182.45 0.00 -37.47 0.00 0.00 0.00
F6 N2 APARTMENT 14-OCT-17:05 0.00 -1302.24 0.00 0.00 141.81 194.45 588.62 0.00 0.00 241.59 173.01 0.00 -37.23 0.00 0.00 0.00
F6 S1 APARTMENT 27-JAN-15:25 0.00 -2038.27 0.00 0.00 41.51 50.41 400.26 1587.01 0.00 0.00 66.46 0.00 0.00 0.00 -107.38 0.00
F6 S2 APARTMENT 03-DEC-12:45 0.00 -2038.70 0.00 0.00 40.73 28.81 406.15 2685.15 0.00 0.00 0.00 0.00 0.00 0.00 -74.91 -1047.22
F7 SW APARTMENT 30-OCT-14:30 0.00 -2905.54 0.00 0.00 39.86 50.41 400.26 3490.42 0.00 263.80 0.00 0.00 0.00 0.00 0.00 -1339.21
F7 NW APARTMENT 30-SEP-15:30 0.00 -2198.74 0.00 0.00 48.90 100.83 470.89 2128.74 0.00 55.98 0.00 0.00 0.00 0.00 0.00 -606.61
F7 SE APARTMENT 30-OCT-12:45 0.00 -2527.77 0.00 0.00 40.44 28.81 388.49 2980.35 0.00 100.13 0.00 0.00 0.00 0.00 0.00 -1010.45
F7 NE APARTMENT 30-SEP-08:45 0.00 -1913.00 0.00 0.00 40.75 28.81 394.37 1833.46 0.00 251.70 0.00 0.00 0.00 0.00 0.00 -636.09
F7 N1 APARTMENT 14-OCT-17:05 0.00 -1298.83 0.00 0.00 141.81 194.45 588.62 0.00 0.00 247.87 162.57 0.00 -36.49 0.00 0.00 0.00
F7 N2 APARTMENT 14-OCT-17:05 0.00 -1289.61 0.00 0.00 141.81 194.45 588.62 0.00 0.00 247.87 153.10 0.00 -36.25 0.00 0.00 0.00
F7 S1 APARTMENT 27-JAN-15:25 0.00 -2073.20 0.00 0.00 41.75 50.41 400.26 1578.95 0.00 0.00 115.58 0.00 0.00 0.00 -113.75 0.00
F7 S2 APARTMENT 27-JAN-15:25 0.00 -2074.15 0.00 0.00 41.76 50.41 400.26 1579.11 0.00 0.00 116.33 0.00 0.00 0.00 -113.72 0.00
F8 SW APARTMENT 30-OCT-14:30 0.00 -2898.08 0.00 0.00 39.95 50.41 400.26 3473.77 0.00 276.21 0.00 0.00 0.00 0.00 0.00 -1342.52
F8 NW APARTMENT 30-SEP-15:30 0.00 -2194.50 0.00 0.00 48.90 100.83 470.89 2122.50 0.00 58.50 0.00 0.00 0.00 0.00 0.00 -607.12
F8 SE APARTMENT 30-OCT-12:45 0.00 -2523.99 0.00 0.00 40.55 28.81 388.49 2971.58 0.00 107.10 0.00 0.00 0.00 0.00 0.00 -1012.54
F8 NE APARTMENT 30-SEP-08:45 0.00 -1910.58 0.00 0.00 40.75 28.81 394.37 1827.63 0.00 253.72 0.00 0.00 0.00 0.00 0.00 -634.70
F8 N1 APARTMENT 30-SEP-16:38 0.00 -1299.69 0.00 0.00 84.76 144.04 588.62 121.71 0.00 198.13 162.43 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 30-SEP-16:38 0.00 -1287.15 0.00 0.00 84.76 144.04 588.62 121.85 0.00 197.87 150.02 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 27-JAN-15:25 0.00 -2074.38 0.00 0.00 41.98 50.41 400.26 1572.19 0.00 0.00 129.20 0.00 0.00 0.00 -119.68 0.00
F8 S2 APARTMENT 27-JAN-15:25 0.00 -2082.04 0.00 0.00 42.00 50.41 400.26 1572.37 0.00 0.00 136.62 0.00 0.00 0.00 -119.61 0.00
F9 SW APARTMENT 30-OCT-14:30 0.00 -2960.96 0.00 0.00 40.33 50.41 400.26 3462.83 0.00 308.15 0.00 0.00 0.00 0.00 0.00 -1301.02
F9 NW APARTMENT 30-SEP-15:30 0.00 -2241.04 0.00 0.00 48.90 100.83 470.89 2114.92 0.00 60.77 0.00 0.00 0.00 0.00 0.00 -555.27
F9 SE APARTMENT 31-OCT-13:30 0.00 -2568.58 0.00 0.00 39.21 28.81 382.60 2691.02 0.00 224.09 0.00 0.00 0.00 0.00 0.00 -797.15
F9 NE APARTMENT 30-SEP-08:45 0.00 -1913.52 0.00 0.00 40.75 28.81 394.37 1822.14 0.00 255.36 0.00 0.00 0.00 0.00 0.00 -627.92
F9 N1 APARTMENT 30-SEP-16:38 0.00 -1364.23 0.00 0.00 84.76 144.04 588.62 120.13 0.00 197.44 229.25 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 30-SEP-16:38 0.00 -1351.67 0.00 0.00 84.76 144.04 588.62 120.26 0.00 197.16 216.84 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 27-JAN-15:25 0.00 -2121.42 0.00 0.00 42.29 50.41 400.26 1567.53 0.00 0.00 185.83 0.00 0.00 0.00 -124.90 0.00
F9 S2 APARTMENT 27-JAN-15:25 0.00 -2129.08 0.00 0.00 42.30 50.41 400.26 1567.70 0.00 0.00 193.24 0.00 0.00 0.00 -124.84 0.00
T SW APARTMENT 30-OCT-14:30 0.00 -3558.12 0.00 0.00 40.44 50.41 400.26 3412.50 0.00 326.68 0.00 0.00 0.00 0.00 0.00 -672.18
T NW APARTMENT 29-SEP-15:30 0.00 -2805.97 0.00 0.00 48.90 100.83 470.89 2130.31 0.00 175.67 0.00 0.00 0.00 0.00 0.00 -120.63
T SE APARTMENT 31-OCT-13:30 0.00 -3103.11 0.00 0.00 38.91 28.81 382.60 2641.20 0.00 213.91 0.00 0.00 0.00 0.00 0.00 -202.32
T NE APARTMENT 29-SEP-10:00 0.00 -2198.67 0.00 0.00 40.75 28.81 406.15 1713.19 0.00 100.64 0.00 0.00 0.00 0.00 0.00 -90.87
T N1 APARTMENT 29-SEP-13:15 0.00 -1669.75 0.00 0.00 40.74 28.81 382.60 654.30 0.00 153.60 409.71 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-SEP-13:15 0.00 -1673.56 0.00 0.00 40.73 28.81 382.60 654.10 0.00 153.53 413.80 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 30-OCT-12:45 0.00 -2616.85 0.00 0.00 40.09 28.81 388.49 2766.75 0.00 74.83 0.00 0.00 0.00 0.00 0.00 -682.11
T S2 APARTMENT 30-OCT-12:45 0.00 -2621.97 0.00 0.00 40.07 28.81 388.49 2766.42 0.00 74.12 0.00 0.00 0.00 0.00 0.00 -675.93
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-SEP-15:15 0.00 -151503.69 0.00 0.00 3757.51 14808.05 37687.72 115151.97 0.00 4185.87 0.00 0.00 0.00 0.00 0.00 -24087.42


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 25-MAR-09:00 1147.81 0.00 0.00 0.00 43.40 28.81 394.37 376.24 0.00 0.00 0.00 0.00 0.00 0.00 -1454.13 -536.50
G NW APARTMENT 03-JAN-11:10 1053.36 0.00 0.00 0.00 46.62 28.81 412.03 258.06 0.00 0.00 0.00 0.00 0.00 0.00 -984.41 -814.48
OFFICE 10-JAN-04:00 446.47 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 0.00 0.00 -789.09 0.00 -135.70 -29.95
G NE APARTMENT 12-FEB-09:40 1167.36 0.00 0.00 0.00 46.19 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -17.23 0.00 -1142.56 -476.94
G N1 APARTMENT 26-MAR-12:45 1035.19 0.00 0.00 0.00 45.04 28.81 388.49 404.97 0.00 0.00 0.00 0.00 0.00 0.00 -1169.87 -732.62
G N2 APARTMENT 13-MAY-09:45 1157.16 0.00 0.00 0.00 44.76 28.81 406.15 318.50 0.00 0.00 0.00 0.00 0.00 0.00 -1104.46 -850.91
G S1 APARTMENT 25-MAR-09:00 1190.61 0.00 0.00 0.00 43.35 28.81 394.37 255.59 0.00 0.00 0.00 0.00 0.00 0.00 -1400.95 -511.78
G S2 APARTMENT 25-MAR-09:00 1141.38 0.00 0.00 0.00 43.30 28.81 394.37 255.31 0.00 0.00 0.00 0.00 0.00 0.00 -1402.47 -460.71
F2 SW APARTMENT 12-FEB-09:45 899.56 0.00 0.00 0.00 43.54 28.81 394.37 0.00 0.00 0.00 152.71 0.00 -98.53 0.00 -1420.45 0.00
F2 NW APARTMENT 12-FEB-09:45 1166.53 0.00 0.00 0.00 44.29 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -76.50 0.00 -1336.88 -220.62
F2 SE APARTMENT 12-FEB-09:45 1043.53 0.00 0.00 0.00 43.67 28.81 394.37 0.00 0.00 0.00 5.52 0.00 -101.37 0.00 -1414.53 0.00
F2 NE APARTMENT 12-FEB-09:45 1140.95 0.00 0.00 0.00 44.82 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -72.38 0.00 -1331.60 -204.97
F2 N1 APARTMENT 12-FEB-09:45 1227.80 0.00 0.00 0.00 44.05 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -49.33 0.00 -1282.49 -363.21
F2 N2 APARTMENT 12-FEB-09:45 1267.59 0.00 0.00 0.00 44.11 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -48.65 0.00 -1281.06 -405.18
F2 S1 APARTMENT 12-FEB-09:45 682.90 0.00 0.00 0.00 43.02 28.81 394.37 0.00 0.00 0.00 291.05 0.00 -67.60 0.00 -1372.55 0.00
F2 S2 APARTMENT 12-FEB-09:45 666.17 0.00 0.00 0.00 43.01 28.81 394.37 0.00 0.00 0.00 308.59 0.00 -67.75 0.00 -1373.20 0.00
F3 SW APARTMENT 12-FEB-09:45 944.33 0.00 0.00 0.00 42.99 28.81 394.37 0.00 0.00 0.00 290.92 0.00 -125.09 0.00 -1576.32 0.00
F3 NW APARTMENT 12-FEB-09:45 1343.55 0.00 0.00 0.00 43.81 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -99.01 0.00 -1471.22 -240.31
F3 SE APARTMENT 12-FEB-09:45 1057.72 0.00 0.00 0.00 43.31 28.81 394.37 0.00 0.00 0.00 169.10 0.00 -126.25 0.00 -1567.07 0.00
F3 NE APARTMENT 12-FEB-09:45 1293.90 0.00 0.00 0.00 44.38 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -95.40 0.00 -1465.12 -200.94
F3 N1 APARTMENT 12-FEB-09:45 1402.21 0.00 0.00 0.00 43.39 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -64.46 0.00 -1409.08 -395.23
F3 N2 APARTMENT 12-FEB-09:45 1424.76 0.00 0.00 0.00 43.46 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -63.62 0.00 -1407.85 -419.93
F3 S1 APARTMENT 12-FEB-09:45 1197.64 0.00 0.00 0.00 42.29 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -86.31 0.00 -1512.73 -64.07
F3 S2 APARTMENT 12-FEB-09:45 1146.30 0.00 0.00 0.00 42.30 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -86.16 0.00 -1513.51 -12.12
F4 SW APARTMENT 12-FEB-09:45 947.57 0.00 0.00 0.00 42.90 28.81 394.37 0.00 0.00 0.00 421.43 0.00 -137.26 0.00 -1697.82 0.00
F4 NW APARTMENT 12-FEB-09:45 1269.11 0.00 0.00 0.00 43.68 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -110.09 0.00 -1580.58 -45.30
F4 SE APARTMENT 12-FEB-09:45 1137.95 0.00 0.00 0.00 43.27 28.81 394.37 0.00 0.00 0.00 221.18 0.00 -138.56 0.00 -1687.02 0.00
F4 NE APARTMENT 12-FEB-09:45 1290.00 0.00 0.00 0.00 44.26 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -107.31 0.00 -1573.02 -77.11
F4 N1 APARTMENT 12-FEB-09:45 1356.38 0.00 0.00 0.00 43.13 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -72.30 0.00 -1511.78 -238.61
F4 N2 APARTMENT 12-FEB-09:45 1412.27 0.00 0.00 0.00 43.21 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -71.40 0.00 -1510.05 -297.21
F4 S1 APARTMENT 12-FEB-09:45 906.51 0.00 0.00 0.00 42.12 28.81 394.37 0.00 0.00 0.00 355.29 0.00 -95.02 0.00 -1632.09 0.00
F4 S2 APARTMENT 12-FEB-09:45 920.20 0.00 0.00 0.00 42.14 28.81 394.37 0.00 0.00 0.00 340.96 0.00 -94.74 0.00 -1631.74 0.00
M SW APARTMENT 12-FEB-09:45 1092.28 0.00 0.00 0.00 42.91 28.81 394.37 0.00 0.00 0.00 385.71 0.00 -144.80 0.00 -1799.28 0.00
M NW APARTMENT 12-FEB-09:45 1344.95 0.00 0.00 0.00 43.65 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -116.87 0.00 -1671.75 -23.16
M SE APARTMENT 12-FEB-09:45 1309.51 0.00 0.00 0.00 43.29 28.81 394.37 0.00 0.00 0.00 159.15 0.00 -146.72 0.00 -1788.40 0.00
M NE APARTMENT 12-FEB-09:45 1312.84 0.00 0.00 0.00 44.22 28.81 394.37 0.00 0.00 0.00 1.02 0.00 -115.05 0.00 -1666.22 0.00
M N1 APARTMENT 12-FEB-09:45 1382.17 0.00 0.00 0.00 43.01 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -77.17 0.00 -1598.75 -172.44
M N2 APARTMENT 12-FEB-09:45 1435.16 0.00 0.00 0.00 43.09 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -76.28 0.00 -1597.12 -228.03
M S1 APARTMENT 12-FEB-09:45 1021.63 0.00 0.00 0.00 42.08 28.81 394.37 0.00 0.00 0.00 342.43 0.00 -100.58 0.00 -1728.74 0.00
M S2 APARTMENT 12-FEB-09:45 1036.79 0.00 0.00 0.00 42.10 28.81 394.37 0.00 0.00 0.00 326.56 0.00 -100.28 0.00 -1728.35 0.00
F6 SW APARTMENT 12-FEB-09:45 1503.85 0.00 0.00 0.00 43.31 28.81 394.37 0.00 0.00 0.00 52.77 0.00 -143.18 0.00 -1879.92 0.00
F6 NW APARTMENT 12-FEB-09:45 1399.52 0.00 0.00 0.00 44.06 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -114.02 0.00 -1750.88 -1.85
F6 SE APARTMENT 25-MAR-09:00 1639.44 0.00 0.00 0.00 40.75 28.81 394.37 259.25 0.00 0.00 379.84 0.00 0.00 0.00 -2742.46 0.00
F6 NE APARTMENT 12-FEB-20:45 1265.12 0.00 0.00 0.00 154.34 230.46 523.87 0.00 0.00 0.00 0.00 0.00 -359.00 0.00 -1603.83 -210.96
F6 N1 APARTMENT 12-FEB-09:45 1554.18 0.00 0.00 0.00 43.40 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -75.72 0.00 -1670.67 -274.36
F6 N2 APARTMENT 12-FEB-09:45 1540.42 0.00 0.00 0.00 43.47 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -74.88 0.00 -1670.56 -261.63
F6 S1 APARTMENT 12-FEB-09:45 1407.95 0.00 0.00 0.00 42.43 28.81 394.37 0.00 0.00 0.00 33.54 0.00 -100.52 0.00 -1806.58 0.00
F6 S2 APARTMENT 12-FEB-09:45 1423.22 0.00 0.00 0.00 42.45 28.81 394.37 0.00 0.00 0.00 17.51 0.00 -100.19 0.00 -1806.17 0.00
F7 SW APARTMENT 25-MAR-09:00 1870.89 0.00 0.00 0.00 40.75 28.81 394.37 166.21 0.00 0.00 388.04 0.00 0.00 0.00 -2889.07 0.00
F7 NW APARTMENT 18-APR-09:30 1782.34 0.00 0.00 0.00 42.76 28.81 406.15 397.73 0.00 0.00 0.00 0.00 0.00 0.00 -2101.20 -556.58
F7 SE APARTMENT 25-MAR-09:00 2096.24 0.00 0.00 0.00 40.83 28.81 394.37 251.25 0.00 0.00 70.25 0.00 0.00 0.00 -2881.75 0.00
F7 NE APARTMENT 13-MAY-09:45 1611.11 0.00 0.00 0.00 42.37 28.81 406.15 494.17 0.00 0.00 0.00 0.00 0.00 0.00 -1843.65 -738.96
F7 N1 APARTMENT 18-APR-09:30 1895.29 0.00 0.00 0.00 42.34 28.81 406.15 248.65 0.00 0.00 0.00 0.00 0.00 0.00 -2013.29 -607.94
F7 N2 APARTMENT 18-APR-09:30 1881.10 0.00 0.00 0.00 42.36 28.81 406.15 248.80 0.00 0.00 0.00 0.00 0.00 0.00 -2013.23 -593.98
F7 S1 APARTMENT 12-FEB-09:45 1758.02 0.00 0.00 0.00 42.73 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -100.35 0.00 -1878.58 -245.00
F7 S2 APARTMENT 12-FEB-09:45 1754.51 0.00 0.00 0.00 42.75 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -100.02 0.00 -1878.57 -241.85
F8 SW APARTMENT 25-MAR-09:00 2243.75 0.00 0.00 0.00 40.77 28.81 394.37 159.46 0.00 0.00 150.86 0.00 0.00 0.00 -3018.02 0.00
F8 NW APARTMENT 13-MAY-09:45 1752.40 0.00 0.00 0.00 42.90 28.81 406.15 376.46 0.00 0.00 0.00 0.00 0.00 0.00 -1909.15 -697.56
F8 SE APARTMENT 25-MAR-09:00 2214.88 0.00 0.00 0.00 41.03 28.81 394.37 245.18 0.00 0.00 91.41 0.00 0.00 0.00 -3015.68 0.00
F8 NE APARTMENT 13-MAY-09:45 1845.98 0.00 0.00 0.00 42.76 28.81 406.15 494.40 0.00 0.00 0.00 0.00 0.00 0.00 -1907.76 -910.34
F8 N1 APARTMENT 18-APR-09:30 1845.40 0.00 0.00 0.00 42.72 28.81 406.15 249.02 0.00 0.00 0.00 0.00 0.00 0.00 -2099.13 -472.97
F8 N2 APARTMENT 13-MAY-09:45 1843.30 0.00 0.00 0.00 42.57 28.81 406.15 231.88 0.00 0.00 0.00 0.00 0.00 0.00 -1836.31 -716.39
F8 S1 APARTMENT 25-MAR-09:00 2080.25 0.00 0.00 0.00 40.75 28.81 394.37 119.17 0.00 0.00 231.73 0.00 0.00 0.00 -2895.08 0.00
F8 S2 APARTMENT 25-MAR-09:00 2089.55 0.00 0.00 0.00 40.75 28.81 394.37 119.29 0.00 0.00 222.23 0.00 0.00 0.00 -2895.00 0.00
F9 SW APARTMENT 25-MAR-09:00 2282.17 0.00 0.00 0.00 41.17 28.81 394.37 160.75 0.00 0.00 236.90 0.00 0.00 0.00 -3144.18 0.00
F9 NW APARTMENT 13-MAY-09:45 1674.32 0.00 0.00 0.00 43.51 28.81 406.15 381.83 0.00 0.00 0.00 0.00 0.00 0.00 -1975.04 -559.58
F9 SE APARTMENT 25-MAR-09:00 2231.29 0.00 0.00 0.00 41.50 28.81 394.37 246.55 0.00 0.00 199.30 0.00 0.00 0.00 -3141.82 0.00
F9 NE APARTMENT 12-FEB-09:40 1917.03 0.00 0.00 0.00 45.55 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -106.48 0.00 -1966.43 -312.84
F9 N1 APARTMENT 03-FEB-08:00 1796.07 0.00 0.00 0.00 144.89 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -127.49 0.00 -2000.09 -289.59
F9 N2 APARTMENT 03-FEB-08:00 1779.45 0.00 0.00 0.00 145.12 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -126.69 0.00 -1999.98 -274.14
F9 S1 APARTMENT 25-MAR-09:00 2292.30 0.00 0.00 0.00 40.75 28.81 394.37 117.06 0.00 0.00 141.75 0.00 0.00 0.00 -3015.03 0.00
F9 S2 APARTMENT 25-MAR-09:00 2298.32 0.00 0.00 0.00 40.75 28.81 394.37 117.21 0.00 0.00 135.61 0.00 0.00 0.00 -3015.06 0.00
T SW APARTMENT 25-MAR-08:55 2461.72 0.00 0.00 0.00 42.75 28.81 394.37 190.18 0.00 0.00 198.71 0.00 0.00 0.00 -3316.54 0.00
T NW APARTMENT 03-FEB-07:55 2186.30 0.00 0.00 0.00 155.05 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -147.55 0.00 -2180.22 -489.81
T SE APARTMENT 25-MAR-08:55 2595.45 0.00 0.00 0.00 43.05 28.81 394.37 273.84 0.00 0.00 0.00 0.00 0.00 0.00 -3302.52 -33.00
T NE APARTMENT 18-APR-09:30 2038.38 0.00 0.00 0.00 41.69 28.81 406.15 1090.41 0.00 0.00 0.00 0.00 0.00 0.00 -2360.03 -1245.41
T N1 APARTMENT 26-MAR-11:00 1853.20 0.00 0.00 0.00 42.99 28.81 412.03 271.88 0.00 0.00 0.00 0.00 0.00 0.00 -2004.80 -604.12
T N2 APARTMENT 26-MAR-11:00 1855.82 0.00 0.00 0.00 42.92 28.81 412.03 271.00 0.00 0.00 0.00 0.00 0.00 0.00 -2004.89 -605.69
T S1 APARTMENT 25-MAR-09:00 2566.32 0.00 0.00 0.00 41.61 28.81 394.37 128.93 0.00 0.00 0.00 0.00 0.00 0.00 -3130.06 -29.98
T S2 APARTMENT 25-MAR-09:00 2563.47 0.00 0.00 0.00 41.63 28.81 394.37 129.21 0.00 0.00 0.00 0.00 0.00 0.00 -3130.06 -27.43
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-FEB-09:45 101837.73 0.00 0.00 0.00 3471.56 9118.54 31642.60 0.00 0.00 0.00 0.00 0.00 -7490.12 0.00 -135199.89 -3380.43



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Sec1.1A-General Information

Data
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 24.50
Number of hours cooling loads not met 153.25
Number of hours not met 177.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 22204.40 0.00 0.00 0.00 0.00
Exterior Lighting 168.56 10720.10 0.00 0.00 0.00 0.00
Space Heating 3.29 0.00 0.59 13019.98 0.00 0.00
Space Cooling 267.70 45725.15 0.00 0.00 0.00 0.00
Pumps 35.73 1192.40 0.00 0.00 0.00 0.00
Heat Rejection 11.58 1479.99 0.00 0.00 0.00 0.00
Fans-Interior 488.37 15486.08 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1045.87 80594.78 0.00 0.00
Receptacle Equipment 1131.09 56867.52 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 2543.57   1046.46   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 2543.57
Natural Gas 0.00 1046.46
Additional 0.00 0.00
Total 1131.09 3590.03


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 0.42
Space Cooling 34.16
Fans-Interior 62.32
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 30.20
Subtotal 324.58


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.08
Service Water Heating 133.46
Miscellaneous 0.00
Subtotal 133.54


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 11.60
Space Heating 0.11
Space Cooling 7.46
Fans-Interior 13.60
Service Water Heating 29.13
Receptacle Equipment 31.51
Miscellaneous 6.59



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.188894
G NW APARTMENT DIRECT AIR 0.167315
OFFICE DIRECT AIR 0.261994
G NE APARTMENT DIRECT AIR 0.128314
G N1 APARTMENT DIRECT AIR 0.081209
G N2 APARTMENT DIRECT AIR 0.079773
G S1 APARTMENT DIRECT AIR 0.115615
G S2 APARTMENT DIRECT AIR 0.120461
F2 SW APARTMENT DIRECT AIR 0.238219
F2 NW APARTMENT DIRECT AIR 0.212404
F2 SE APARTMENT DIRECT AIR 0.220624
F2 NE APARTMENT DIRECT AIR 0.167452
F2 N1 APARTMENT DIRECT AIR 0.112139
F2 N2 APARTMENT DIRECT AIR 0.110887
F2 S1 APARTMENT DIRECT AIR 0.151285
F2 S2 APARTMENT DIRECT AIR 0.153147
F3 SW APARTMENT DIRECT AIR 0.238548
F3 NW APARTMENT DIRECT AIR 0.213965
F3 SE APARTMENT DIRECT AIR 0.206113
F3 NE APARTMENT DIRECT AIR 0.170031
F3 N1 APARTMENT DIRECT AIR 0.115643
F3 N2 APARTMENT DIRECT AIR 0.114408
F3 S1 APARTMENT DIRECT AIR 0.153635
F3 S2 APARTMENT DIRECT AIR 0.154519
F4 SW APARTMENT DIRECT AIR 0.238428
F4 NW APARTMENT DIRECT AIR 0.214389
F4 SE APARTMENT DIRECT AIR 0.204571
F4 NE APARTMENT DIRECT AIR 0.170493
F4 N1 APARTMENT DIRECT AIR 0.117102
F4 N2 APARTMENT DIRECT AIR 0.115879
F4 S1 APARTMENT DIRECT AIR 0.154154
F4 S2 APARTMENT DIRECT AIR 0.154892
M SW APARTMENT DIRECT AIR 0.240527
M NW APARTMENT DIRECT AIR 0.216949
M SE APARTMENT DIRECT AIR 0.206836
M NE APARTMENT DIRECT AIR 0.173056
M N1 APARTMENT DIRECT AIR 0.120337
M N2 APARTMENT DIRECT AIR 0.119123
M S1 APARTMENT DIRECT AIR 0.156647
M S2 APARTMENT DIRECT AIR 0.157363
F6 SW APARTMENT DIRECT AIR 0.236448
F6 NW APARTMENT DIRECT AIR 0.213143
F6 SE APARTMENT DIRECT AIR 0.203134
F6 NE APARTMENT DIRECT AIR 0.169340
F6 N1 APARTMENT DIRECT AIR 0.117434
F6 N2 APARTMENT DIRECT AIR 0.116236
F6 S1 APARTMENT DIRECT AIR 0.153056
F6 S2 APARTMENT DIRECT AIR 0.153769
F7 SW APARTMENT DIRECT AIR 0.234730
F7 NW APARTMENT DIRECT AIR 0.211724
F7 SE APARTMENT DIRECT AIR 0.201730
F7 NE APARTMENT DIRECT AIR 0.167975
F7 N1 APARTMENT DIRECT AIR 0.116694
F7 N2 APARTMENT DIRECT AIR 0.115509
F7 S1 APARTMENT DIRECT AIR 0.151705
F7 S2 APARTMENT DIRECT AIR 0.152417
F8 SW APARTMENT DIRECT AIR 0.234310
F8 NW APARTMENT DIRECT AIR 0.211575
F8 SE APARTMENT DIRECT AIR 0.201545
F8 NE APARTMENT DIRECT AIR 0.167823
F8 N1 APARTMENT DIRECT AIR 0.117125
F8 N2 APARTMENT DIRECT AIR 0.115952
F8 S1 APARTMENT DIRECT AIR 0.151570
F8 S2 APARTMENT DIRECT AIR 0.152283
F9 SW APARTMENT DIRECT AIR 0.240441
F9 NW APARTMENT DIRECT AIR 0.217900
F9 SE APARTMENT DIRECT AIR 0.206117
F9 NE APARTMENT DIRECT AIR 0.169799
F9 N1 APARTMENT DIRECT AIR 0.123027
F9 N2 APARTMENT DIRECT AIR 0.121848
F9 S1 APARTMENT DIRECT AIR 0.155428
F9 S2 APARTMENT DIRECT AIR 0.156140
T SW APARTMENT DIRECT AIR 0.291629
T NW APARTMENT DIRECT AIR 0.263071
T SE APARTMENT DIRECT AIR 0.252890
T NE APARTMENT DIRECT AIR 0.202521
T N1 APARTMENT DIRECT AIR 0.152116
T N2 APARTMENT DIRECT AIR 0.152047
T S1 APARTMENT DIRECT AIR 0.207642
T S2 APARTMENT DIRECT AIR 0.208336


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.188894
AIRLOOP G NW MAIN BRANCH 0.167315
AIRLOOP OFFICE MAIN BRANCH 0.261994
AIRLOOP G NE MAIN BRANCH 0.128314
AIRLOOP G N1 MAIN BRANCH 0.081209
AIRLOOP G N2 MAIN BRANCH 0.079773
AIRLOOP G S1 MAIN BRANCH 0.115615
AIRLOOP G S2 MAIN BRANCH 0.120461
AIRLOOP F2 SW MAIN BRANCH 0.238219
AIRLOOP F2 NW MAIN BRANCH 0.212404
AIRLOOP F2 SE MAIN BRANCH 0.220624
AIRLOOP F2 NE MAIN BRANCH 0.167452
AIRLOOP F2 N1 MAIN BRANCH 0.112139
AIRLOOP F2 N2 MAIN BRANCH 0.110887
AIRLOOP F2 S1 MAIN BRANCH 0.151285
AIRLOOP F2 S2 MAIN BRANCH 0.153147
AIRLOOP F3 SW MAIN BRANCH 0.238548
AIRLOOP F3 NW MAIN BRANCH 0.213965
AIRLOOP F3 SE MAIN BRANCH 0.206113
AIRLOOP F3 NE MAIN BRANCH 0.170031
AIRLOOP F3 N1 MAIN BRANCH 0.115643
AIRLOOP F3 N2 MAIN BRANCH 0.114408
AIRLOOP F3 S1 MAIN BRANCH 0.153635
AIRLOOP F3 S2 MAIN BRANCH 0.154519
AIRLOOP F4 SW MAIN BRANCH 0.238428
AIRLOOP F4 NW MAIN BRANCH 0.214389
AIRLOOP F4 SE MAIN BRANCH 0.204571
AIRLOOP F4 NE MAIN BRANCH 0.170493
AIRLOOP F4 N1 MAIN BRANCH 0.117102
AIRLOOP F4 N2 MAIN BRANCH 0.115879
AIRLOOP F4 S1 MAIN BRANCH 0.154154
AIRLOOP F4 S2 MAIN BRANCH 0.154892
AIRLOOP M SW MAIN BRANCH 0.240527
AIRLOOP M NW MAIN BRANCH 0.216949
AIRLOOP M SE MAIN BRANCH 0.206836
AIRLOOP M NE MAIN BRANCH 0.173056
AIRLOOP M N1 MAIN BRANCH 0.120337
AIRLOOP M N2 MAIN BRANCH 0.119123
AIRLOOP M S1 MAIN BRANCH 0.156647
AIRLOOP M S2 MAIN BRANCH 0.157363
AIRLOOP F6 SW MAIN BRANCH 0.236448
AIRLOOP F6 NW MAIN BRANCH 0.213143
AIRLOOP F6 SE MAIN BRANCH 0.203134
AIRLOOP F6 NE MAIN BRANCH 0.169340
AIRLOOP F6 N1 MAIN BRANCH 0.117434
AIRLOOP F6 N2 MAIN BRANCH 0.116236
AIRLOOP F6 S1 MAIN BRANCH 0.153056
AIRLOOP F6 S2 MAIN BRANCH 0.153769
AIRLOOP F7 SW MAIN BRANCH 0.234730
AIRLOOP F7 NW MAIN BRANCH 0.211724
AIRLOOP F7 SE MAIN BRANCH 0.201730
AIRLOOP F7 NE MAIN BRANCH 0.167975
AIRLOOP F7 N1 MAIN BRANCH 0.116694
AIRLOOP F7 N2 MAIN BRANCH 0.115509
AIRLOOP F7 S1 MAIN BRANCH 0.151705
AIRLOOP F7 S2 MAIN BRANCH 0.152417
AIRLOOP F8 SW MAIN BRANCH 0.234310
AIRLOOP F8 NW MAIN BRANCH 0.211575
AIRLOOP F8 SE MAIN BRANCH 0.201545
AIRLOOP F8 NE MAIN BRANCH 0.167823
AIRLOOP F8 N1 MAIN BRANCH 0.117125
AIRLOOP F8 N2 MAIN BRANCH 0.115952
AIRLOOP F8 S1 MAIN BRANCH 0.151570
AIRLOOP F8 S2 MAIN BRANCH 0.152283
AIRLOOP F9 SW MAIN BRANCH 0.240441
AIRLOOP F9 NW MAIN BRANCH 0.217900
AIRLOOP F9 SE MAIN BRANCH 0.206117
AIRLOOP F9 NE MAIN BRANCH 0.169799
AIRLOOP F9 N1 MAIN BRANCH 0.123027
AIRLOOP F9 N2 MAIN BRANCH 0.121848
AIRLOOP F9 S1 MAIN BRANCH 0.155428
AIRLOOP F9 S2 MAIN BRANCH 0.156140
AIRLOOP T SW MAIN BRANCH 0.291629
AIRLOOP T NW MAIN BRANCH 0.263071
AIRLOOP T SE MAIN BRANCH 0.252890
AIRLOOP T NE MAIN BRANCH 0.202521
AIRLOOP T N1 MAIN BRANCH 0.152116
AIRLOOP T N2 MAIN BRANCH 0.152047
AIRLOOP T S1 MAIN BRANCH 0.207642
AIRLOOP T S2 MAIN BRANCH 0.208336


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.188894
AIRLOOP G NW 0.167315
AIRLOOP OFFICE 0.261994
AIRLOOP G NE 0.128314
AIRLOOP G N1 0.081209
AIRLOOP G N2 0.079773
AIRLOOP G S1 0.115615
AIRLOOP G S2 0.120461
AIRLOOP F2 SW 0.238219
AIRLOOP F2 NW 0.212404
AIRLOOP F2 SE 0.220624
AIRLOOP F2 NE 0.167452
AIRLOOP F2 N1 0.112139
AIRLOOP F2 N2 0.110887
AIRLOOP F2 S1 0.151285
AIRLOOP F2 S2 0.153147
AIRLOOP F3 SW 0.238548
AIRLOOP F3 NW 0.213965
AIRLOOP F3 SE 0.206113
AIRLOOP F3 NE 0.170031
AIRLOOP F3 N1 0.115643
AIRLOOP F3 N2 0.114408
AIRLOOP F3 S1 0.153635
AIRLOOP F3 S2 0.154519
AIRLOOP F4 SW 0.238428
AIRLOOP F4 NW 0.214389
AIRLOOP F4 SE 0.204571
AIRLOOP F4 NE 0.170493
AIRLOOP F4 N1 0.117102
AIRLOOP F4 N2 0.115879
AIRLOOP F4 S1 0.154154
AIRLOOP F4 S2 0.154892
AIRLOOP M SW 0.240527
AIRLOOP M NW 0.216949
AIRLOOP M SE 0.206836
AIRLOOP M NE 0.173056
AIRLOOP M N1 0.120337
AIRLOOP M N2 0.119123
AIRLOOP M S1 0.156647
AIRLOOP M S2 0.157363
AIRLOOP F6 SW 0.236448
AIRLOOP F6 NW 0.213143
AIRLOOP F6 SE 0.203134
AIRLOOP F6 NE 0.169340
AIRLOOP F6 N1 0.117434
AIRLOOP F6 N2 0.116236
AIRLOOP F6 S1 0.153056
AIRLOOP F6 S2 0.153769
AIRLOOP F7 SW 0.234730
AIRLOOP F7 NW 0.211724
AIRLOOP F7 SE 0.201730
AIRLOOP F7 NE 0.167975
AIRLOOP F7 N1 0.116694
AIRLOOP F7 N2 0.115509
AIRLOOP F7 S1 0.151705
AIRLOOP F7 S2 0.152417
AIRLOOP F8 SW 0.234310
AIRLOOP F8 NW 0.211575
AIRLOOP F8 SE 0.201545
AIRLOOP F8 NE 0.167823
AIRLOOP F8 N1 0.117125
AIRLOOP F8 N2 0.115952
AIRLOOP F8 S1 0.151570
AIRLOOP F8 S2 0.152283
AIRLOOP F9 SW 0.240441
AIRLOOP F9 NW 0.217900
AIRLOOP F9 SE 0.206117
AIRLOOP F9 NE 0.169799
AIRLOOP F9 N1 0.123027
AIRLOOP F9 N2 0.121848
AIRLOOP F9 S1 0.155428
AIRLOOP F9 S2 0.156140
AIRLOOP T SW 0.291629
AIRLOOP T NW 0.263071
AIRLOOP T SE 0.252890
AIRLOOP T NE 0.202521
AIRLOOP T N1 0.152116
AIRLOOP T N2 0.152047
AIRLOOP T S1 0.207642
AIRLOOP T S2 0.208336


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.188894 0.025952
AIRLOOP G NW OA CONTROLLER 0.167315 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.261994 0.038103
AIRLOOP G NE OA CONTROLLER 0.128314 0.025952
AIRLOOP G N1 OA CONTROLLER 0.081209 0.025952
AIRLOOP G N2 OA CONTROLLER 0.079773 0.025952
AIRLOOP G S1 OA CONTROLLER 0.115615 0.025952
AIRLOOP G S2 OA CONTROLLER 0.120461 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.238219 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.212404 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.220624 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.167452 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.112139 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.110887 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.151285 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.153147 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.238548 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.213965 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.206113 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.170031 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.115643 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.114408 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.153635 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.154519 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.238428 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.214389 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.204571 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.170493 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.117102 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.115879 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.154154 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.154892 0.025952
AIRLOOP M SW OA CONTROLLER 0.240527 0.025952
AIRLOOP M NW OA CONTROLLER 0.216949 0.025952
AIRLOOP M SE OA CONTROLLER 0.206836 0.025952
AIRLOOP M NE OA CONTROLLER 0.173056 0.025952
AIRLOOP M N1 OA CONTROLLER 0.120337 0.025952
AIRLOOP M N2 OA CONTROLLER 0.119123 0.025952
AIRLOOP M S1 OA CONTROLLER 0.156647 0.025952
AIRLOOP M S2 OA CONTROLLER 0.157363 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.236448 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.213143 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.203134 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.169340 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.117434 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.116236 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.153056 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.153769 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.234730 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.211724 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.201730 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.167975 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.116694 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.115509 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.151705 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.152417 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.234310 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.211575 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.201545 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.167823 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.117125 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.115952 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.151570 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.152283 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.240441 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.217900 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.206117 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.169799 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.123027 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.121848 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.155428 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.156140 0.025952
AIRLOOP T SW OA CONTROLLER 0.291629 0.025952
AIRLOOP T NW OA CONTROLLER 0.263071 0.025952
AIRLOOP T SE OA CONTROLLER 0.252890 0.025952
AIRLOOP T NE OA CONTROLLER 0.202521 0.025952
AIRLOOP T N1 OA CONTROLLER 0.152116 0.025952
AIRLOOP T N2 OA CONTROLLER 0.152047 0.025952
AIRLOOP T S1 OA CONTROLLER 0.207642 0.025952
AIRLOOP T S2 OA CONTROLLER 0.208336 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.188894 2839.53 2106.80 0.000062
HEAT PUMP COOLING MODE AIRLOOP G NW 0.167315 2522.87 1868.55 0.000055
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.261994 3844.40 2883.77 0.000084
HEAT PUMP COOLING MODE AIRLOOP G NE 0.128314 1908.88 1416.10 0.000042
HEAT PUMP COOLING MODE AIRLOOP G N1 0.081209 1293.49 933.64 0.000028
HEAT PUMP COOLING MODE AIRLOOP G N2 0.079773 1273.15 918.20 0.000028
HEAT PUMP COOLING MODE AIRLOOP G S1 0.115615 1823.85 1325.85 0.000040
HEAT PUMP COOLING MODE AIRLOOP G S2 0.120461 1890.97 1377.58 0.000041
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.238219 3515.55 2628.17 0.000077
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.212404 3141.05 2344.50 0.000069
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.220624 3233.24 2422.84 0.000071
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.167452 2453.21 1835.33 0.000054
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.112139 1728.18 1265.02 0.000038
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.110887 1710.59 1251.62 0.000037
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.151285 2319.45 1706.73 0.000051
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.153147 2345.27 1726.58 0.000051
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.238548 3520.99 2631.89 0.000077
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.213965 3163.52 2361.34 0.000069
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.206113 3033.06 2268.66 0.000066
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.170031 2489.29 1862.85 0.000054
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.115643 1777.51 1302.55 0.000039
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.114408 1760.18 1289.34 0.000038
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.153635 2352.47 1731.90 0.000051
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.154519 2364.72 1741.32 0.000052
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.238428 3519.98 2630.78 0.000077
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.214389 3170.01 2366.00 0.000069
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.204571 3058.33 2273.89 0.000067
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.170493 2496.07 1867.86 0.000055
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.117102 1798.15 1318.21 0.000039
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.115879 1780.98 1305.12 0.000039
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.154154 2360.00 1737.52 0.000052
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.154892 2370.23 1745.38 0.000052
HEAT PUMP COOLING MODE AIRLOOP M SW 0.240527 3549.60 2653.26 0.000078
HEAT PUMP COOLING MODE AIRLOOP M NW 0.216949 3206.03 2393.40 0.000070
HEAT PUMP COOLING MODE AIRLOOP M SE 0.206836 3090.25 2298.15 0.000068
HEAT PUMP COOLING MODE AIRLOOP M NE 0.173056 2531.83 1895.20 0.000055
HEAT PUMP COOLING MODE AIRLOOP M N1 0.120337 1843.61 1352.84 0.000040
HEAT PUMP COOLING MODE AIRLOOP M N2 0.119123 1826.57 1339.85 0.000040
HEAT PUMP COOLING MODE AIRLOOP M S1 0.156647 2394.87 1764.18 0.000052
HEAT PUMP COOLING MODE AIRLOOP M S2 0.157363 2404.80 1771.81 0.000053
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.236448 3493.53 2609.96 0.000076
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.213143 3153.62 2352.97 0.000069
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.203134 3039.32 2258.82 0.000066
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.169340 2480.76 1855.77 0.000054
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.117434 1803.10 1321.84 0.000039
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.116236 1786.28 1309.02 0.000039
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.153056 2345.26 1725.94 0.000051
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.153769 2355.14 1733.54 0.000051
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.234730 3470.11 2591.77 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.211724 3134.29 2337.96 0.000068
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.201730 3020.23 2243.97 0.000066
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.167975 2462.13 1841.32 0.000054
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.116694 1792.87 1313.96 0.000039
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.115509 1776.22 1301.27 0.000039
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.151705 2326.70 1711.58 0.000051
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.152417 2336.56 1719.17 0.000051
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.234310 3464.65 2587.40 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.211575 3132.54 2336.45 0.000068
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.201545 3017.98 2242.08 0.000066
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.167823 2460.25 1839.76 0.000054
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.117125 1799.02 1318.60 0.000039
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.115952 1782.53 1306.04 0.000039
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.151570 2325.00 1710.19 0.000051
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.152283 2334.88 1717.78 0.000051
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.240441 3549.97 2652.75 0.000078
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.217900 3220.67 2403.89 0.000070
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.206117 3084.88 2292.33 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.169799 2487.83 1860.84 0.000054
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.123027 1881.80 1381.72 0.000041
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.121848 1865.25 1369.11 0.000041
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.155428 2381.82 1752.79 0.000052
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.156140 2391.69 1760.39 0.000052
HEAT PUMP COOLING MODE AIRLOOP T SW 0.291629 4272.38 3203.58 0.000093
HEAT PUMP COOLING MODE AIRLOOP T NW 0.263071 3859.75 2891.51 0.000084
HEAT PUMP COOLING MODE AIRLOOP T SE 0.252890 3733.69 2790.42 0.000082
HEAT PUMP COOLING MODE AIRLOOP T NE 0.202521 2958.33 2217.81 0.000065
HEAT PUMP COOLING MODE AIRLOOP T N1 0.152116 2342.21 1720.34 0.000051
HEAT PUMP COOLING MODE AIRLOOP T N2 0.152047 2341.28 1719.60 0.000051
HEAT PUMP COOLING MODE AIRLOOP T S1 0.207642 3106.45 2309.33 0.000068
HEAT PUMP COOLING MODE AIRLOOP T S2 0.208336 3112.94 2315.26 0.000068


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.188894 0.188894 0.188894 0.188894 2839.53 2839.53 1465.42 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.167315 0.167315 0.167315 0.167315 2522.87 2522.87 1470.22 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.261994 0.261994 0.261994 0.261994 3844.40 3844.40 2103.21 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.128314 0.128314 0.128314 0.128314 1908.88 1908.88 1468.59 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.081209 0.081209 0.081209 0.081209 1293.49 1293.49 1115.65 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.079773 0.079773 0.079773 0.079773 1273.15 1273.15 1115.65 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.115615 0.115615 0.115615 0.115615 1823.85 1823.85 1115.65 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.120461 0.120461 0.120461 0.120461 1890.97 1890.97 1115.65 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.238219 0.238219 0.238219 0.238219 3515.55 3515.55 1436.46 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.212404 0.212404 0.212404 0.212404 3141.05 3141.05 1439.57 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.220624 0.220624 0.220624 0.220624 3233.24 3233.24 1461.40 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.167452 0.167452 0.167452 0.167452 2453.21 2453.21 1438.46 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.112139 0.112139 0.112139 0.112139 1728.18 1728.18 1115.65 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.110887 0.110887 0.110887 0.110887 1710.59 1710.59 1115.65 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.151285 0.151285 0.151285 0.151285 2319.45 2319.45 1115.65 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.153147 0.153147 0.153147 0.153147 2345.27 2345.27 1115.65 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.238548 0.238548 0.238548 0.238548 3520.99 3520.99 1421.50 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.213965 0.213965 0.213965 0.213965 3163.52 3163.52 1423.36 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.206113 0.206113 0.206113 0.206113 3033.06 3033.06 1424.26 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.170031 0.170031 0.170031 0.170031 2489.29 2489.29 1422.88 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.115643 0.115643 0.115643 0.115643 1777.51 1777.51 1115.65 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.114408 0.114408 0.114408 0.114408 1760.18 1760.18 1115.65 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.153635 0.153635 0.153635 0.153635 2352.47 2352.47 1115.65 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.154519 0.154519 0.154519 0.154519 2364.72 2364.72 1115.65 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.238428 0.238428 0.238428 0.238428 3519.98 3519.98 1434.10 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.214389 0.214389 0.214389 0.214389 3170.01 3170.01 1435.44 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.204571 0.204571 0.204571 0.204571 3058.33 3058.33 1434.52 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.170493 0.170493 0.170493 0.170493 2496.07 2496.07 1435.47 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.117102 0.117102 0.117102 0.117102 1798.15 1798.15 1115.65 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.115879 0.115879 0.115879 0.115879 1780.98 1780.98 1115.65 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.154154 0.154154 0.154154 0.154154 2360.00 2360.00 1115.65 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.154892 0.154892 0.154892 0.154892 2370.23 2370.23 1115.65 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.240527 0.240527 0.240527 0.240527 3549.60 3549.60 1427.89 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.216949 0.216949 0.216949 0.216949 3206.03 3206.03 1427.59 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.206836 0.206836 0.206836 0.206836 3090.25 3090.25 1428.40 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.173056 0.173056 0.173056 0.173056 2531.83 2531.83 1428.04 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.120337 0.120337 0.120337 0.120337 1843.61 1843.61 1115.65 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.119123 0.119123 0.119123 0.119123 1826.57 1826.57 1115.65 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.156647 0.156647 0.156647 0.156647 2394.87 2394.87 1115.65 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.157363 0.157363 0.157363 0.157363 2404.80 2404.80 1115.65 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.236448 0.236448 0.236448 0.236448 3493.53 3493.53 1486.88 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.213143 0.213143 0.213143 0.213143 3153.62 3153.62 1486.95 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.203134 0.203134 0.203134 0.203134 3039.32 3039.32 1487.71 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.169340 0.169340 0.169340 0.169340 2480.76 2480.76 1487.77 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.117434 0.117434 0.117434 0.117434 1803.10 1803.10 1115.65 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.116236 0.116236 0.116236 0.116236 1786.28 1786.28 1115.65 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.153056 0.153056 0.153056 0.153056 2345.26 2345.26 1115.65 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.153769 0.153769 0.153769 0.153769 2355.14 2355.14 1115.65 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.234730 0.234730 0.234730 0.234730 3470.11 3470.11 1522.27 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.211724 0.211724 0.211724 0.211724 3134.29 3134.29 1521.61 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.201730 0.201730 0.201730 0.201730 3020.23 3020.23 1523.41 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.167975 0.167975 0.167975 0.167975 2462.13 2462.13 1522.75 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.116694 0.116694 0.116694 0.116694 1792.87 1792.87 1115.65 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.115509 0.115509 0.115509 0.115509 1776.22 1776.22 1115.65 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.151705 0.151705 0.151705 0.151705 2326.70 2326.70 1115.65 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.152417 0.152417 0.152417 0.152417 2336.56 2336.56 1115.65 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.234310 0.234310 0.234310 0.234310 3464.65 3464.65 1558.55 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.211575 0.211575 0.211575 0.211575 3132.54 3132.54 1557.08 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.201545 0.201545 0.201545 0.201545 3017.98 3017.98 1559.97 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.167823 0.167823 0.167823 0.167823 2460.25 2460.25 1558.51 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.117125 0.117125 0.117125 0.117125 1799.02 1799.02 1115.65 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.115952 0.115952 0.115952 0.115952 1782.53 1782.53 1115.65 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.151570 0.151570 0.151570 0.151570 2325.00 2325.00 1115.65 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.152283 0.152283 0.152283 0.152283 2334.88 2334.88 1115.65 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.240441 0.240441 0.240441 0.240441 3549.97 3549.97 1671.99 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.217900 0.217900 0.217900 0.217900 3220.67 3220.67 1668.34 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.206117 0.206117 0.206117 0.206117 3084.88 3084.88 1673.68 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.169799 0.169799 0.169799 0.169799 2487.83 2487.83 1670.03 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.123027 0.123027 0.123027 0.123027 1881.80 1881.80 1115.65 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.121848 0.121848 0.121848 0.121848 1865.25 1865.25 1115.65 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.155428 0.155428 0.155428 0.155428 2381.82 2381.82 1115.65 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.156140 0.156140 0.156140 0.156140 2391.69 2391.69 1115.65 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.291629 0.291629 0.291629 0.291629 4272.38 4272.38 2050.85 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.263071 0.263071 0.263071 0.263071 3859.75 3859.75 2051.87 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.252890 0.252890 0.252890 0.252890 3733.69 3733.69 2052.57 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.202521 0.202521 0.202521 0.202521 2958.33 2958.33 2053.59 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.152116 0.152116 0.152116 0.152116 2342.21 2342.21 1493.22 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.152047 0.152047 0.152047 0.152047 2341.28 2341.28 1493.27 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.207642 0.207642 0.207642 0.207642 3106.45 3106.45 1489.31 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.208336 0.208336 0.208336 0.208336 3112.94 3112.94 1489.36 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.188894
AIRLOOP G NW SUPPLY FAN 0.167315
AIRLOOP OFFICE SUPPLY FAN 0.261994
AIRLOOP G NE SUPPLY FAN 0.128314
AIRLOOP G N1 SUPPLY FAN 0.081209
AIRLOOP G N2 SUPPLY FAN 0.079773
AIRLOOP G S1 SUPPLY FAN 0.115615
AIRLOOP G S2 SUPPLY FAN 0.120461
AIRLOOP F2 SW SUPPLY FAN 0.238219
AIRLOOP F2 NW SUPPLY FAN 0.212404
AIRLOOP F2 SE SUPPLY FAN 0.220624
AIRLOOP F2 NE SUPPLY FAN 0.167452
AIRLOOP F2 N1 SUPPLY FAN 0.112139
AIRLOOP F2 N2 SUPPLY FAN 0.110887
AIRLOOP F2 S1 SUPPLY FAN 0.151285
AIRLOOP F2 S2 SUPPLY FAN 0.153147
AIRLOOP F3 SW SUPPLY FAN 0.238548
AIRLOOP F3 NW SUPPLY FAN 0.213965
AIRLOOP F3 SE SUPPLY FAN 0.206113
AIRLOOP F3 NE SUPPLY FAN 0.170031
AIRLOOP F3 N1 SUPPLY FAN 0.115643
AIRLOOP F3 N2 SUPPLY FAN 0.114408
AIRLOOP F3 S1 SUPPLY FAN 0.153635
AIRLOOP F3 S2 SUPPLY FAN 0.154519
AIRLOOP F4 SW SUPPLY FAN 0.238428
AIRLOOP F4 NW SUPPLY FAN 0.214389
AIRLOOP F4 SE SUPPLY FAN 0.204571
AIRLOOP F4 NE SUPPLY FAN 0.170493
AIRLOOP F4 N1 SUPPLY FAN 0.117102
AIRLOOP F4 N2 SUPPLY FAN 0.115879
AIRLOOP F4 S1 SUPPLY FAN 0.154154
AIRLOOP F4 S2 SUPPLY FAN 0.154892
AIRLOOP M SW SUPPLY FAN 0.240527
AIRLOOP M NW SUPPLY FAN 0.216949
AIRLOOP M SE SUPPLY FAN 0.206836
AIRLOOP M NE SUPPLY FAN 0.173056
AIRLOOP M N1 SUPPLY FAN 0.120337
AIRLOOP M N2 SUPPLY FAN 0.119123
AIRLOOP M S1 SUPPLY FAN 0.156647
AIRLOOP M S2 SUPPLY FAN 0.157363
AIRLOOP F6 SW SUPPLY FAN 0.236448
AIRLOOP F6 NW SUPPLY FAN 0.213143
AIRLOOP F6 SE SUPPLY FAN 0.203134
AIRLOOP F6 NE SUPPLY FAN 0.169340
AIRLOOP F6 N1 SUPPLY FAN 0.117434
AIRLOOP F6 N2 SUPPLY FAN 0.116236
AIRLOOP F6 S1 SUPPLY FAN 0.153056
AIRLOOP F6 S2 SUPPLY FAN 0.153769
AIRLOOP F7 SW SUPPLY FAN 0.234730
AIRLOOP F7 NW SUPPLY FAN 0.211724
AIRLOOP F7 SE SUPPLY FAN 0.201730
AIRLOOP F7 NE SUPPLY FAN 0.167975
AIRLOOP F7 N1 SUPPLY FAN 0.116694
AIRLOOP F7 N2 SUPPLY FAN 0.115509
AIRLOOP F7 S1 SUPPLY FAN 0.151705
AIRLOOP F7 S2 SUPPLY FAN 0.152417
AIRLOOP F8 SW SUPPLY FAN 0.234310
AIRLOOP F8 NW SUPPLY FAN 0.211575
AIRLOOP F8 SE SUPPLY FAN 0.201545
AIRLOOP F8 NE SUPPLY FAN 0.167823
AIRLOOP F8 N1 SUPPLY FAN 0.117125
AIRLOOP F8 N2 SUPPLY FAN 0.115952
AIRLOOP F8 S1 SUPPLY FAN 0.151570
AIRLOOP F8 S2 SUPPLY FAN 0.152283
AIRLOOP F9 SW SUPPLY FAN 0.240441
AIRLOOP F9 NW SUPPLY FAN 0.217900
AIRLOOP F9 SE SUPPLY FAN 0.206117
AIRLOOP F9 NE SUPPLY FAN 0.169799
AIRLOOP F9 N1 SUPPLY FAN 0.123027
AIRLOOP F9 N2 SUPPLY FAN 0.121848
AIRLOOP F9 S1 SUPPLY FAN 0.155428
AIRLOOP F9 S2 SUPPLY FAN 0.156140
AIRLOOP T SW SUPPLY FAN 0.291629
AIRLOOP T NW SUPPLY FAN 0.263071
AIRLOOP T SE SUPPLY FAN 0.252890
AIRLOOP T NE SUPPLY FAN 0.202521
AIRLOOP T N1 SUPPLY FAN 0.152116
AIRLOOP T N2 SUPPLY FAN 0.152047
AIRLOOP T S1 SUPPLY FAN 0.207642
AIRLOOP T S2 SUPPLY FAN 0.208336


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.188894 2839.53 0.000062
HEAT PUMP HEATING MODE AIRLOOP G NW 0.167315 2522.87 0.000055
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.261994 3844.40 0.000084
HEAT PUMP HEATING MODE AIRLOOP G NE 0.128314 1908.88 0.000042
HEAT PUMP HEATING MODE AIRLOOP G N1 0.081209 1293.49 0.000028
HEAT PUMP HEATING MODE AIRLOOP G N2 0.079773 1273.15 0.000028
HEAT PUMP HEATING MODE AIRLOOP G S1 0.115615 1823.85 0.000040
HEAT PUMP HEATING MODE AIRLOOP G S2 0.120461 1890.97 0.000041
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.238219 3515.55 0.000077
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.212404 3141.05 0.000069
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.220624 3233.24 0.000071
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.167452 2453.21 0.000054
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.112139 1728.18 0.000038
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.110887 1710.59 0.000037
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.151285 2319.45 0.000051
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.153147 2345.27 0.000051
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.238548 3520.99 0.000077
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.213965 3163.52 0.000069
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.206113 3033.06 0.000066
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.170031 2489.29 0.000054
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.115643 1777.51 0.000039
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.114408 1760.18 0.000038
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.153635 2352.47 0.000051
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.154519 2364.72 0.000052
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.238428 3519.98 0.000077
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.214389 3170.01 0.000069
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.204571 3058.33 0.000067
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.170493 2496.07 0.000055
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.117102 1798.15 0.000039
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.115879 1780.98 0.000039
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.154154 2360.00 0.000052
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.154892 2370.23 0.000052
HEAT PUMP HEATING MODE AIRLOOP M SW 0.240527 3549.60 0.000078
HEAT PUMP HEATING MODE AIRLOOP M NW 0.216949 3206.03 0.000070
HEAT PUMP HEATING MODE AIRLOOP M SE 0.206836 3090.25 0.000068
HEAT PUMP HEATING MODE AIRLOOP M NE 0.173056 2531.83 0.000055
HEAT PUMP HEATING MODE AIRLOOP M N1 0.120337 1843.61 0.000040
HEAT PUMP HEATING MODE AIRLOOP M N2 0.119123 1826.57 0.000040
HEAT PUMP HEATING MODE AIRLOOP M S1 0.156647 2394.87 0.000052
HEAT PUMP HEATING MODE AIRLOOP M S2 0.157363 2404.80 0.000053
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.236448 3493.53 0.000076
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.213143 3153.62 0.000069
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.203134 3039.32 0.000066
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.169340 2480.76 0.000054
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.117434 1803.10 0.000039
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.116236 1786.28 0.000039
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.153056 2345.26 0.000051
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.153769 2355.14 0.000051
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.234730 3470.11 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.211724 3134.29 0.000068
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.201730 3020.23 0.000066
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.167975 2462.13 0.000054
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.116694 1792.87 0.000039
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.115509 1776.22 0.000039
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.151705 2326.70 0.000051
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.152417 2336.56 0.000051
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.234310 3464.65 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.211575 3132.54 0.000068
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.201545 3017.98 0.000066
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.167823 2460.25 0.000054
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.117125 1799.02 0.000039
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.115952 1782.53 0.000039
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.151570 2325.00 0.000051
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.152283 2334.88 0.000051
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.240441 3549.97 0.000078
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.217900 3220.67 0.000070
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.206117 3084.88 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.169799 2487.83 0.000054
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.123027 1881.80 0.000041
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.121848 1865.25 0.000041
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.155428 2381.82 0.000052
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.156140 2391.69 0.000052
HEAT PUMP HEATING MODE AIRLOOP T SW 0.291629 4272.38 0.000093
HEAT PUMP HEATING MODE AIRLOOP T NW 0.263071 3859.75 0.000084
HEAT PUMP HEATING MODE AIRLOOP T SE 0.252890 3733.69 0.000082
HEAT PUMP HEATING MODE AIRLOOP T NE 0.202521 2958.33 0.000065
HEAT PUMP HEATING MODE AIRLOOP T N1 0.152116 2342.21 0.000051
HEAT PUMP HEATING MODE AIRLOOP T N2 0.152047 2341.28 0.000051
HEAT PUMP HEATING MODE AIRLOOP T S1 0.207642 3106.45 0.000068
HEAT PUMP HEATING MODE AIRLOOP T S2 0.208336 3112.94 0.000068


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 1465.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 1470.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 2103.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 1468.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 1436.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 1439.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 1461.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 1438.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 1421.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 1423.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 1424.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 1422.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 1434.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 1435.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 1434.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 1435.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 1427.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 1427.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 1428.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 1428.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 1486.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 1486.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 1487.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 1487.77
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 1522.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 1521.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 1523.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 1522.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 1558.55
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 1557.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 1559.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 1558.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 1671.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 1668.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 1673.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 1670.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 1115.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 2050.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 2051.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 2052.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 2053.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 1493.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 1493.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 1489.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 1489.36


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.004530 5.10


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.004530


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.004530 2187.00 5.86 6659.14


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.004530 1155.48



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:37

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 13.22
February 23.13 13.28
March 23.04 12.64
April 23.46 15.30
May 23.25 15.56
June 23.93 17.67
July 24.19 19.43
August 24.21 19.66
September 24.12 18.47
October 23.84 18.77
November 23.42 14.32
December 23.38 13.59
     
Annual Sum or Average 23.61 16.01
Minimum of Months 23.04 12.64
Maximum of Months 24.21 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.37 13.22
February 22.36 13.28
March 22.51 12.64
April 23.11 15.30
May 23.14 15.56
June 23.94 17.67
July 24.19 19.43
August 24.18 19.66
September 24.01 18.47
October 23.52 18.77
November 22.53 14.32
December 22.47 13.59
     
Annual Sum or Average 23.20 16.01
Minimum of Months 22.36 12.64
Maximum of Months 24.19 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.26 13.22
February 23.11 13.28
March 23.09 12.64
April 23.51 15.30
May 23.52 15.56
June 24.23 17.67
July 24.39 19.43
August 24.39 19.66
September 24.35 18.47
October 24.06 18.77
November 23.46 14.32
December 23.31 13.59
     
Annual Sum or Average 23.73 16.01
Minimum of Months 23.09 12.64
Maximum of Months 24.39 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 13.22
February 22.23 13.28
March 22.40 12.64
April 22.95 15.30
May 22.95 15.56
June 23.84 17.67
July 24.19 19.43
August 24.17 19.66
September 23.91 18.47
October 23.42 18.77
November 22.41 14.32
December 22.38 13.59
     
Annual Sum or Average 23.10 16.01
Minimum of Months 22.23 12.64
Maximum of Months 24.19 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.23 13.22
February 22.18 13.28
March 22.28 12.64
April 22.70 15.30
May 22.72 15.56
June 23.72 17.67
July 24.11 19.43
August 24.10 19.66
September 23.82 18.47
October 23.32 18.77
November 22.34 14.32
December 22.31 13.59
     
Annual Sum or Average 22.99 16.01
Minimum of Months 22.18 12.64
Maximum of Months 24.11 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 13.22
February 22.17 13.28
March 22.27 12.64
April 22.69 15.30
May 22.70 15.56
June 23.71 17.67
July 24.11 19.43
August 24.10 19.66
September 23.81 18.47
October 23.31 18.77
November 22.33 14.32
December 22.30 13.59
     
Annual Sum or Average 22.98 16.01
Minimum of Months 22.17 12.64
Maximum of Months 24.11 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.38 13.22
February 23.17 13.28
March 23.01 12.64
April 23.25 15.30
May 22.95 15.56
June 23.78 17.67
July 24.12 19.43
August 24.16 19.66
September 24.08 18.47
October 23.82 18.77
November 23.45 14.32
December 23.48 13.59
     
Annual Sum or Average 23.56 16.01
Minimum of Months 22.95 12.64
Maximum of Months 24.16 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.41 13.22
February 23.20 13.28
March 23.04 12.64
April 23.29 15.30
May 22.99 15.56
June 23.80 17.67
July 24.13 19.43
August 24.17 19.66
September 24.09 18.47
October 23.84 18.77
November 23.48 14.32
December 23.50 13.59
     
Annual Sum or Average 23.58 16.01
Minimum of Months 22.99 12.64
Maximum of Months 24.17 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.25 13.22
February 21.13 13.28
March 21.06 12.64
April 22.04 15.30
May 22.09 15.56
June 23.50 17.67
July 24.27 19.43
August 24.35 19.66
September 23.84 18.47
October 23.28 18.77
November 21.67 14.32
December 21.43 13.59
     
Annual Sum or Average 22.50 16.01
Minimum of Months 21.06 12.64
Maximum of Months 24.35 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 13.22
February 23.95 13.28
March 23.90 12.64
April 24.18 15.30
May 24.03 15.56
June 24.18 17.67
July 24.31 19.43
August 24.32 19.66
September 24.28 18.47
October 24.26 18.77
November 24.16 14.32
December 24.12 13.59
     
Annual Sum or Average 24.15 16.01
Minimum of Months 23.90 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 13.22
February 23.21 13.28
March 23.37 12.64
April 23.95 15.30
May 23.95 15.56
June 24.18 17.67
July 24.31 19.43
August 24.30 19.66
September 24.19 18.47
October 24.05 18.77
November 23.37 14.32
December 23.25 13.59
     
Annual Sum or Average 23.77 16.01
Minimum of Months 23.05 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.09 13.22
February 23.95 13.28
March 23.93 12.64
April 24.20 15.30
May 24.06 15.56
June 24.19 17.67
July 24.32 19.43
August 24.33 19.66
September 24.28 18.47
October 24.28 18.77
November 24.16 14.32
December 24.13 13.59
     
Annual Sum or Average 24.16 16.01
Minimum of Months 23.93 12.64
Maximum of Months 24.33 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.96 13.22
February 22.99 13.28
March 23.22 12.64
April 23.83 15.30
May 23.83 15.56
June 24.12 17.67
July 24.30 19.43
August 24.30 19.66
September 24.14 18.47
October 23.97 18.77
November 23.18 14.32
December 23.11 13.59
     
Annual Sum or Average 23.67 16.01
Minimum of Months 22.96 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.95 13.22
February 23.04 13.28
March 23.21 12.64
April 23.68 15.30
May 23.68 15.56
June 24.05 17.67
July 24.26 19.43
August 24.25 19.66
September 24.07 18.47
October 23.93 18.77
November 23.18 14.32
December 23.15 13.59
     
Annual Sum or Average 23.62 16.01
Minimum of Months 22.95 12.64
Maximum of Months 24.26 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.95 13.22
February 23.02 13.28
March 23.19 12.64
April 23.66 15.30
May 23.66 15.56
June 24.05 17.67
July 24.25 19.43
August 24.24 19.66
September 24.06 18.47
October 23.92 18.77
November 23.16 14.32
December 23.13 13.59
     
Annual Sum or Average 23.61 16.01
Minimum of Months 22.95 12.64
Maximum of Months 24.25 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.03 13.28
March 23.97 12.64
April 24.10 15.30
May 23.86 15.56
June 24.08 17.67
July 24.26 19.43
August 24.28 19.66
September 24.24 18.47
October 24.28 18.77
November 24.19 14.32
December 24.21 13.59
     
Annual Sum or Average 24.14 16.01
Minimum of Months 23.86 12.64
Maximum of Months 24.28 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.03 13.28
March 23.97 12.64
April 24.11 15.30
May 23.87 15.56
June 24.08 17.67
July 24.26 19.43
August 24.29 19.66
September 24.24 18.47
October 24.28 18.77
November 24.20 14.32
December 24.22 13.59
     
Annual Sum or Average 24.14 16.01
Minimum of Months 23.87 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.59 13.22
February 24.52 13.28
March 24.57 12.64
April 25.15 15.30
May 25.09 15.56
June 25.67 17.67
July 26.05 19.43
August 26.07 19.66
September 25.82 18.47
October 25.58 18.77
November 24.84 14.32
December 24.73 13.59
     
Annual Sum or Average 25.23 16.01
Minimum of Months 24.52 12.64
Maximum of Months 26.07 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.07 13.28
March 24.04 12.64
April 24.25 15.30
May 24.12 15.56
June 24.19 17.67
July 24.31 19.43
August 24.32 19.66
September 24.28 18.47
October 24.29 18.77
November 24.24 14.32
December 24.21 13.59
     
Annual Sum or Average 24.21 16.01
Minimum of Months 24.04 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.28 13.22
February 23.46 13.28
March 23.62 12.64
April 24.07 15.30
May 24.06 15.56
June 24.19 17.67
July 24.31 19.43
August 24.30 19.66
September 24.20 18.47
October 24.12 18.77
November 23.61 14.32
December 23.51 13.59
     
Annual Sum or Average 23.90 16.01
Minimum of Months 23.28 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 13.22
February 24.03 13.28
March 24.01 12.64
April 24.24 15.30
May 24.09 15.56
June 24.17 17.67
July 24.31 19.43
August 24.33 19.66
September 24.28 18.47
October 24.30 18.77
November 24.21 14.32
December 24.19 13.59
     
Annual Sum or Average 24.19 16.01
Minimum of Months 24.01 12.64
Maximum of Months 24.33 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 13.22
February 23.26 13.28
March 23.48 12.64
April 23.99 15.30
May 23.98 15.56
June 24.15 17.67
July 24.31 19.43
August 24.30 19.66
September 24.15 18.47
October 24.07 18.77
November 23.42 14.32
December 23.37 13.59
     
Annual Sum or Average 23.81 16.01
Minimum of Months 23.20 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.25 13.22
February 23.38 13.28
March 23.56 12.64
April 23.90 15.30
May 23.88 15.56
June 24.09 17.67
July 24.27 19.43
August 24.26 19.66
September 24.10 18.47
October 24.05 18.77
November 23.48 14.32
December 23.48 13.59
     
Annual Sum or Average 23.81 16.01
Minimum of Months 23.25 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.24 13.22
February 23.36 13.28
March 23.54 12.64
April 23.89 15.30
May 23.87 15.56
June 24.08 17.67
July 24.27 19.43
August 24.26 19.66
September 24.09 18.47
October 24.04 18.77
November 23.46 14.32
December 23.47 13.59
     
Annual Sum or Average 23.80 16.01
Minimum of Months 23.24 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 13.22
February 24.16 13.28
March 24.13 12.64
April 24.20 15.30
May 24.01 15.56
June 24.10 17.67
July 24.27 19.43
August 24.29 19.66
September 24.25 18.47
October 24.32 18.77
November 24.28 14.32
December 24.30 13.59
     
Annual Sum or Average 24.22 16.01
Minimum of Months 24.01 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 13.22
February 24.16 13.28
March 24.13 12.64
April 24.20 15.30
May 24.01 15.56
June 24.10 17.67
July 24.27 19.43
August 24.29 19.66
September 24.25 18.47
October 24.32 18.77
November 24.28 14.32
December 24.30 13.59
     
Annual Sum or Average 24.22 16.01
Minimum of Months 24.01 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.11 13.22
February 25.06 13.28
March 25.14 12.64
April 25.64 15.30
May 25.56 15.56
June 25.89 17.67
July 26.22 19.43
August 26.24 19.66
September 26.01 18.47
October 25.93 18.77
November 25.33 14.32
December 25.26 13.59
     
Annual Sum or Average 25.62 16.01
Minimum of Months 25.06 12.64
Maximum of Months 26.24 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 13.22
February 24.09 13.28
March 24.06 12.64
April 24.24 15.30
May 24.12 15.56
June 24.18 17.67
July 24.31 19.43
August 24.32 19.66
September 24.28 18.47
October 24.29 18.77
November 24.24 14.32
December 24.22 13.59
     
Annual Sum or Average 24.21 16.01
Minimum of Months 24.06 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.34 13.22
February 23.52 13.28
March 23.67 12.64
April 24.08 15.30
May 24.07 15.56
June 24.18 17.67
July 24.31 19.43
August 24.30 19.66
September 24.20 18.47
October 24.13 18.77
November 23.66 14.32
December 23.57 13.59
     
Annual Sum or Average 23.92 16.01
Minimum of Months 23.34 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.03 13.28
March 24.02 12.64
April 24.23 15.30
May 24.08 15.56
June 24.15 17.67
July 24.31 19.43
August 24.32 19.66
September 24.27 18.47
October 24.30 18.77
November 24.20 14.32
December 24.19 13.59
     
Annual Sum or Average 24.19 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.27 13.22
February 23.32 13.28
March 23.54 12.64
April 24.01 15.30
May 23.99 15.56
June 24.14 17.67
July 24.31 19.43
August 24.30 19.66
September 24.15 18.47
October 24.08 18.77
November 23.48 14.32
December 23.44 13.59
     
Annual Sum or Average 23.84 16.01
Minimum of Months 23.27 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.35 13.22
February 23.49 13.28
March 23.67 12.64
April 23.94 15.30
May 23.91 15.56
June 24.08 17.67
July 24.27 19.43
August 24.26 19.66
September 24.09 18.47
October 24.06 18.77
November 23.57 14.32
December 23.59 13.59
     
Annual Sum or Average 23.86 16.01
Minimum of Months 23.35 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.35 13.22
February 23.46 13.28
March 23.65 12.64
April 23.93 15.30
May 23.90 15.56
June 24.08 17.67
July 24.27 19.43
August 24.26 19.66
September 24.09 18.47
October 24.06 18.77
November 23.55 14.32
December 23.57 13.59
     
Annual Sum or Average 23.85 16.01
Minimum of Months 23.35 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 13.22
February 24.18 13.28
March 24.16 12.64
April 24.21 15.30
May 24.02 15.56
June 24.09 17.67
July 24.27 19.43
August 24.29 19.66
September 24.25 18.47
October 24.32 18.77
November 24.29 14.32
December 24.31 13.59
     
Annual Sum or Average 24.22 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 13.22
February 24.18 13.28
March 24.16 12.64
April 24.21 15.30
May 24.02 15.56
June 24.09 17.67
July 24.27 19.43
August 24.29 19.66
September 24.25 18.47
October 24.32 18.77
November 24.28 14.32
December 24.31 13.59
     
Annual Sum or Average 24.22 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.32 13.22
February 25.26 13.28
March 25.35 12.64
April 25.81 15.30
May 25.72 15.56
June 26.00 17.67
July 26.32 19.43
August 26.33 19.66
September 26.11 18.47
October 26.07 18.77
November 25.52 14.32
December 25.46 13.59
     
Annual Sum or Average 25.78 16.01
Minimum of Months 25.26 12.64
Maximum of Months 26.33 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 13.22
February 24.09 13.28
March 24.06 12.64
April 24.24 15.30
May 24.11 15.56
June 24.18 17.67
July 24.31 19.43
August 24.32 19.66
September 24.28 18.47
October 24.28 18.77
November 24.24 14.32
December 24.22 13.59
     
Annual Sum or Average 24.21 16.01
Minimum of Months 24.06 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.38 13.22
February 23.53 13.28
March 23.69 12.64
April 24.08 15.30
May 24.06 15.56
June 24.18 17.67
July 24.31 19.43
August 24.31 19.66
September 24.20 18.47
October 24.13 18.77
November 23.68 14.32
December 23.60 13.59
     
Annual Sum or Average 23.93 16.01
Minimum of Months 23.38 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 13.22
February 24.03 13.28
March 24.02 12.64
April 24.22 15.30
May 24.06 15.56
June 24.14 17.67
July 24.31 19.43
August 24.33 19.66
September 24.27 18.47
October 24.29 18.77
November 24.20 14.32
December 24.20 13.59
     
Annual Sum or Average 24.19 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.33 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.30 13.22
February 23.35 13.28
March 23.56 12.64
April 24.01 15.30
May 23.98 15.56
June 24.13 17.67
July 24.31 19.43
August 24.30 19.66
September 24.15 18.47
October 24.08 18.77
November 23.51 14.32
December 23.47 13.59
     
Annual Sum or Average 23.85 16.01
Minimum of Months 23.30 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.41 13.22
February 23.54 13.28
March 23.71 12.64
April 23.95 15.30
May 23.91 15.56
June 24.08 17.67
July 24.27 19.43
August 24.26 19.66
September 24.10 18.47
October 24.08 18.77
November 23.61 14.32
December 23.65 13.59
     
Annual Sum or Average 23.88 16.01
Minimum of Months 23.41 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.41 13.22
February 23.51 13.28
March 23.70 12.64
April 23.94 15.30
May 23.90 15.56
June 24.08 17.67
July 24.27 19.43
August 24.26 19.66
September 24.09 18.47
October 24.07 18.77
November 23.59 14.32
December 23.63 13.59
     
Annual Sum or Average 23.87 16.01
Minimum of Months 23.41 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 13.22
February 24.18 13.28
March 24.17 12.64
April 24.20 15.30
May 24.02 15.56
June 24.09 17.67
July 24.27 19.43
August 24.30 19.66
September 24.25 18.47
October 24.32 18.77
November 24.29 14.32
December 24.32 13.59
     
Annual Sum or Average 24.23 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 13.22
February 24.18 13.28
March 24.17 12.64
April 24.20 15.30
May 24.02 15.56
June 24.09 17.67
July 24.27 19.43
August 24.30 19.66
September 24.25 18.47
October 24.32 18.77
November 24.29 14.32
December 24.31 13.59
     
Annual Sum or Average 24.22 16.01
Minimum of Months 24.02 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.97 13.22
February 25.89 13.28
March 25.98 12.64
April 26.42 15.30
May 26.32 15.56
June 26.59 17.67
July 26.92 19.43
August 26.94 19.66
September 26.72 18.47
October 26.68 18.77
November 26.16 14.32
December 26.11 13.59
     
Annual Sum or Average 26.39 16.01
Minimum of Months 25.89 12.64
Maximum of Months 26.94 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 13.22
February 24.02 13.28
March 24.00 12.64
April 24.20 15.30
May 24.05 15.56
June 24.15 17.67
July 24.30 19.43
August 24.31 19.66
September 24.26 18.47
October 24.26 18.77
November 24.20 14.32
December 24.19 13.59
     
Annual Sum or Average 24.18 16.01
Minimum of Months 24.00 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.27 13.22
February 23.40 13.28
March 23.57 12.64
April 24.01 15.30
May 23.99 15.56
June 24.15 17.67
July 24.30 19.43
August 24.29 19.66
September 24.17 18.47
October 24.08 18.77
November 23.57 14.32
December 23.50 13.59
     
Annual Sum or Average 23.86 16.01
Minimum of Months 23.27 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 13.22
February 23.96 13.28
March 23.95 12.64
April 24.18 15.30
May 23.99 15.56
June 24.10 17.67
July 24.30 19.43
August 24.32 19.66
September 24.25 18.47
October 24.27 18.77
November 24.16 14.32
December 24.16 13.59
     
Annual Sum or Average 24.15 16.01
Minimum of Months 23.95 12.64
Maximum of Months 24.32 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 13.22
February 23.20 13.28
March 23.43 12.64
April 23.93 15.30
May 23.90 15.56
June 24.09 17.67
July 24.30 19.43
August 24.29 19.66
September 24.12 18.47
October 24.03 18.77
November 23.39 14.32
December 23.36 13.59
     
Annual Sum or Average 23.77 16.01
Minimum of Months 23.20 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 13.22
February 23.40 13.28
March 23.60 12.64
April 23.87 15.30
May 23.82 15.56
June 24.03 17.67
July 24.25 19.43
August 24.24 19.66
September 24.06 18.47
October 24.02 18.77
November 23.51 14.32
December 23.54 13.59
     
Annual Sum or Average 23.81 16.01
Minimum of Months 23.31 12.64
Maximum of Months 24.25 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.30 13.22
February 23.38 13.28
March 23.58 12.64
April 23.86 15.30
May 23.81 15.56
June 24.03 17.67
July 24.25 19.43
August 24.24 19.66
September 24.05 18.47
October 24.02 18.77
November 23.48 14.32
December 23.53 13.59
     
Annual Sum or Average 23.80 16.01
Minimum of Months 23.30 12.64
Maximum of Months 24.25 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.27 13.22
February 24.13 13.28
March 24.12 12.64
April 24.16 15.30
May 23.94 15.56
June 24.05 17.67
July 24.25 19.43
August 24.28 19.66
September 24.23 18.47
October 24.30 18.77
November 24.26 14.32
December 24.29 13.59
     
Annual Sum or Average 24.19 16.01
Minimum of Months 23.94 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.27 13.22
February 24.13 13.28
March 24.12 12.64
April 24.16 15.30
May 23.94 15.56
June 24.05 17.67
July 24.25 19.43
August 24.28 19.66
September 24.23 18.47
October 24.30 18.77
November 24.26 14.32
December 24.29 13.59
     
Annual Sum or Average 24.19 16.01
Minimum of Months 23.94 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.29 13.22
February 25.19 13.28
March 25.28 12.64
April 25.74 15.30
May 25.63 15.56
June 25.93 17.67
July 26.29 19.43
August 26.31 19.66
September 26.07 18.47
October 26.03 18.77
November 25.47 14.32
December 25.43 13.59
     
Annual Sum or Average 25.73 16.01
Minimum of Months 25.19 12.64
Maximum of Months 26.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 13.22
February 23.97 13.28
March 23.94 12.64
April 24.17 15.30
May 24.00 15.56
June 24.12 17.67
July 24.29 19.43
August 24.31 19.66
September 24.25 18.47
October 24.24 18.77
November 24.17 14.32
December 24.16 13.59
     
Annual Sum or Average 24.15 16.01
Minimum of Months 23.94 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 13.22
February 23.28 13.28
March 23.47 12.64
April 23.96 15.30
May 23.93 15.56
June 24.12 17.67
July 24.29 19.43
August 24.28 19.66
September 24.16 18.47
October 24.05 18.77
November 23.48 14.32
December 23.41 13.59
     
Annual Sum or Average 23.80 16.01
Minimum of Months 23.18 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.11 13.22
February 23.91 13.28
March 23.90 12.64
April 24.14 15.30
May 23.93 15.56
June 24.07 17.67
July 24.29 19.43
August 24.31 19.66
September 24.24 18.47
October 24.25 18.77
November 24.13 14.32
December 24.13 13.59
     
Annual Sum or Average 24.12 16.01
Minimum of Months 23.90 12.64
Maximum of Months 24.31 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.11 13.22
February 23.07 13.28
March 23.32 12.64
April 23.87 15.30
May 23.83 15.56
June 24.05 17.67
July 24.29 19.43
August 24.28 19.66
September 24.09 18.47
October 23.99 18.77
November 23.29 14.32
December 23.27 13.59
     
Annual Sum or Average 23.71 16.01
Minimum of Months 23.07 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.22 13.22
February 23.29 13.28
March 23.49 12.64
April 23.81 15.30
May 23.75 15.56
June 23.99 17.67
July 24.24 19.43
August 24.23 19.66
September 24.03 18.47
October 23.98 18.77
November 23.41 14.32
December 23.45 13.59
     
Annual Sum or Average 23.75 16.01
Minimum of Months 23.22 12.64
Maximum of Months 24.24 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 13.22
February 23.26 13.28
March 23.47 12.64
April 23.80 15.30
May 23.74 15.56
June 23.99 17.67
July 24.24 19.43
August 24.23 19.66
September 24.02 18.47
October 23.98 18.77
November 23.39 14.32
December 23.44 13.59
     
Annual Sum or Average 23.73 16.01
Minimum of Months 23.21 12.64
Maximum of Months 24.24 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 13.22
February 24.09 13.28
March 24.08 12.64
April 24.13 15.30
May 23.88 15.56
June 24.01 17.67
July 24.24 19.43
August 24.27 19.66
September 24.22 18.47
October 24.28 18.77
November 24.23 14.32
December 24.27 13.59
     
Annual Sum or Average 24.16 16.01
Minimum of Months 23.88 12.64
Maximum of Months 24.28 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 13.22
February 24.09 13.28
March 24.07 12.64
April 24.12 15.30
May 23.88 15.56
June 24.01 17.67
July 24.24 19.43
August 24.27 19.66
September 24.22 18.47
October 24.28 18.77
November 24.23 14.32
December 24.27 13.59
     
Annual Sum or Average 24.16 16.01
Minimum of Months 23.88 12.64
Maximum of Months 24.28 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.13 13.22
February 25.01 13.28
March 25.11 12.64
April 25.60 15.30
May 25.48 15.56
June 25.81 17.67
July 26.20 19.43
August 26.21 19.66
September 25.96 18.47
October 25.91 18.77
November 25.31 14.32
December 25.27 13.59
     
Annual Sum or Average 25.59 16.01
Minimum of Months 25.01 12.64
Maximum of Months 26.21 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.11 13.22
February 23.91 13.28
March 23.89 12.64
April 24.13 15.30
May 23.95 15.56
June 24.10 17.67
July 24.29 19.43
August 24.30 19.66
September 24.24 18.47
October 24.22 18.77
November 24.14 14.32
December 24.13 13.59
     
Annual Sum or Average 24.12 16.01
Minimum of Months 23.89 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.10 13.22
February 23.17 13.28
March 23.37 12.64
April 23.91 15.30
May 23.88 15.56
June 24.09 17.67
July 24.29 19.43
August 24.28 19.66
September 24.14 18.47
October 24.01 18.77
November 23.39 14.32
December 23.32 13.59
     
Annual Sum or Average 23.75 16.01
Minimum of Months 23.10 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 13.22
February 23.85 13.28
March 23.84 12.64
April 24.10 15.30
May 23.88 15.56
June 24.04 17.67
July 24.28 19.43
August 24.30 19.66
September 24.23 18.47
October 24.23 18.77
November 24.10 14.32
December 24.10 13.59
     
Annual Sum or Average 24.09 16.01
Minimum of Months 23.84 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.03 13.22
February 22.96 13.28
March 23.22 12.64
April 23.81 15.30
May 23.76 15.56
June 24.02 17.67
July 24.29 19.43
August 24.28 19.66
September 24.07 18.47
October 23.95 18.77
November 23.19 14.32
December 23.18 13.59
     
Annual Sum or Average 23.65 16.01
Minimum of Months 22.96 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.22
February 23.18 13.28
March 23.38 12.64
April 23.75 15.30
May 23.69 15.56
June 23.96 17.67
July 24.24 19.43
August 24.23 19.66
September 24.01 18.47
October 23.95 18.77
November 23.32 14.32
December 23.36 13.59
     
Annual Sum or Average 23.69 16.01
Minimum of Months 23.13 12.64
Maximum of Months 24.24 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.22
February 23.15 13.28
March 23.36 12.64
April 23.74 15.30
May 23.68 15.56
June 23.95 17.67
July 24.24 19.43
August 24.23 19.66
September 24.00 18.47
October 23.94 18.77
November 23.30 14.32
December 23.34 13.59
     
Annual Sum or Average 23.67 16.01
Minimum of Months 23.13 12.64
Maximum of Months 24.24 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.23 13.22
February 24.05 13.28
March 24.03 12.64
April 24.09 15.30
May 23.83 15.56
June 23.98 17.67
July 24.24 19.43
August 24.27 19.66
September 24.21 18.47
October 24.26 18.77
November 24.21 14.32
December 24.25 13.59
     
Annual Sum or Average 24.14 16.01
Minimum of Months 23.83 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.23 13.22
February 24.05 13.28
March 24.02 12.64
April 24.09 15.30
May 23.83 15.56
June 23.98 17.67
July 24.23 19.43
August 24.27 19.66
September 24.21 18.47
October 24.26 18.77
November 24.21 14.32
December 24.25 13.59
     
Annual Sum or Average 24.14 16.01
Minimum of Months 23.83 12.64
Maximum of Months 24.27 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.03 13.22
February 24.89 13.28
March 24.98 12.64
April 25.52 15.30
May 25.39 15.56
June 25.76 17.67
July 26.18 19.43
August 26.19 19.66
September 25.93 18.47
October 25.85 18.77
November 25.21 14.32
December 25.17 13.59
     
Annual Sum or Average 25.51 16.01
Minimum of Months 24.89 12.64
Maximum of Months 26.19 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.03 13.22
February 23.81 13.28
March 23.78 12.64
April 24.08 15.30
May 23.90 15.56
June 24.07 17.67
July 24.28 19.43
August 24.30 19.66
September 24.23 18.47
October 24.19 18.77
November 24.08 14.32
December 24.06 13.59
     
Annual Sum or Average 24.07 16.01
Minimum of Months 23.78 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 13.22
February 23.03 13.28
March 23.24 12.64
April 23.85 15.30
May 23.82 15.56
June 24.07 17.67
July 24.29 19.43
August 24.27 19.66
September 24.13 18.47
October 23.97 18.77
November 23.26 14.32
December 23.19 13.59
     
Annual Sum or Average 23.68 16.01
Minimum of Months 23.00 12.64
Maximum of Months 24.29 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.00 13.22
February 23.74 13.28
March 23.73 12.64
April 24.05 15.30
May 23.82 15.56
June 24.01 17.67
July 24.28 19.43
August 24.30 19.66
September 24.22 18.47
October 24.19 18.77
November 24.03 14.32
December 24.02 13.59
     
Annual Sum or Average 24.03 16.01
Minimum of Months 23.73 12.64
Maximum of Months 24.30 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.91 13.22
February 22.81 13.28
March 23.09 12.64
April 23.74 15.30
May 23.69 15.56
June 23.99 17.67
July 24.28 19.43
August 24.27 19.66
September 24.05 18.47
October 23.89 18.77
November 23.06 14.32
December 23.04 13.59
     
Annual Sum or Average 23.57 16.01
Minimum of Months 22.81 12.64
Maximum of Months 24.28 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 13.22
February 23.03 13.28
March 23.24 12.64
April 23.69 15.30
May 23.62 15.56
June 23.93 17.67
July 24.23 19.43
August 24.22 19.66
September 23.99 18.47
October 23.90 18.77
November 23.19 14.32
December 23.20 13.59
     
Annual Sum or Average 23.61 16.01
Minimum of Months 23.01 12.64
Maximum of Months 24.23 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 13.22
February 23.01 13.28
March 23.22 12.64
April 23.68 15.30
May 23.61 15.56
June 23.92 17.67
July 24.23 19.43
August 24.22 19.66
September 23.98 18.47
October 23.89 18.77
November 23.17 14.32
December 23.18 13.59
     
Annual Sum or Average 23.60 16.01
Minimum of Months 23.00 12.64
Maximum of Months 24.23 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 13.22
February 23.96 13.28
March 23.93 12.64
April 24.04 15.30
May 23.77 15.56
June 23.96 17.67
July 24.23 19.43
August 24.26 19.66
September 24.20 18.47
October 24.23 18.77
November 24.15 14.32
December 24.19 13.59
     
Annual Sum or Average 24.09 16.01
Minimum of Months 23.77 12.64
Maximum of Months 24.26 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 13.22
February 23.96 13.28
March 23.93 12.64
April 24.04 15.30
May 23.77 15.56
June 23.95 17.67
July 24.23 19.43
August 24.26 19.66
September 24.20 18.47
October 24.23 18.77
November 24.15 14.32
December 24.19 13.59
     
Annual Sum or Average 24.09 16.01
Minimum of Months 23.77 12.64
Maximum of Months 24.26 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.87 13.22
February 24.71 13.28
March 24.82 12.64
April 25.44 15.30
May 25.32 15.56
June 25.74 17.67
July 26.21 19.43
August 26.21 19.66
September 25.91 18.47
October 25.80 18.77
November 25.06 14.32
December 24.99 13.59
     
Annual Sum or Average 25.43 16.01
Minimum of Months 24.71 12.64
Maximum of Months 26.21 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.62 13.22
February 23.41 13.28
March 23.42 12.64
April 23.85 15.30
May 23.67 15.56
June 23.94 17.67
July 24.21 19.43
August 24.23 19.66
September 24.12 18.47
October 23.99 18.77
November 23.70 14.32
December 23.61 13.59
     
Annual Sum or Average 23.82 16.01
Minimum of Months 23.41 12.64
Maximum of Months 24.23 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.81 13.22
February 22.76 13.28
March 22.99 12.64
April 23.62 15.30
May 23.59 15.56
June 23.93 17.67
July 24.22 19.43
August 24.20 19.66
September 24.00 18.47
October 23.74 18.77
November 22.96 14.32
December 22.92 13.59
     
Annual Sum or Average 23.48 16.01
Minimum of Months 22.76 12.64
Maximum of Months 24.22 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.59 13.22
February 23.34 13.28
March 23.37 12.64
April 23.79 15.30
May 23.59 15.56
June 23.86 17.67
July 24.21 19.43
August 24.23 19.66
September 24.09 18.47
October 23.98 18.77
November 23.64 14.32
December 23.58 13.59
     
Annual Sum or Average 23.77 16.01
Minimum of Months 23.34 12.64
Maximum of Months 24.23 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.70 13.22
February 22.57 13.28
March 22.86 12.64
April 23.47 15.30
May 23.43 15.56
June 23.82 17.67
July 24.20 19.43
August 24.18 19.66
September 23.88 18.47
October 23.65 18.77
November 22.78 14.32
December 22.78 13.59
     
Annual Sum or Average 23.37 16.01
Minimum of Months 22.57 12.64
Maximum of Months 24.20 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.74 13.22
February 22.70 13.28
March 22.94 12.64
April 23.46 15.30
May 23.41 15.56
June 23.80 17.67
July 24.17 19.43
August 24.15 19.66
September 23.87 18.47
October 23.68 18.77
November 22.84 14.32
December 22.85 13.59
     
Annual Sum or Average 23.39 16.01
Minimum of Months 22.70 12.64
Maximum of Months 24.17 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.73 13.22
February 22.69 13.28
March 22.93 12.64
April 23.45 15.30
May 23.40 15.56
June 23.79 17.67
July 24.16 19.43
August 24.14 19.66
September 23.86 18.47
October 23.67 18.77
November 22.83 14.32
December 22.84 13.59
     
Annual Sum or Average 23.38 16.01
Minimum of Months 22.69 12.64
Maximum of Months 24.16 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 13.22
February 23.60 13.28
March 23.57 12.64
April 23.86 15.30
May 23.60 15.56
June 23.85 17.67
July 24.17 19.43
August 24.20 19.66
September 24.10 18.47
October 24.06 18.77
November 23.83 14.32
December 23.79 13.59
     
Annual Sum or Average 23.87 16.01
Minimum of Months 23.57 12.64
Maximum of Months 24.20 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 13.22
February 23.60 13.28
March 23.57 12.64
April 23.85 15.30
May 23.60 15.56
June 23.84 17.67
July 24.17 19.43
August 24.20 19.66
September 24.10 18.47
October 24.06 18.77
November 23.83 14.32
December 23.79 13.59
     
Annual Sum or Average 23.87 16.01
Minimum of Months 23.57 12.64
Maximum of Months 24.20 19.66



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.96 13.22
February 24.82 13.28
March 24.95 12.64
April 25.78 15.30
May 25.67 15.56
June 26.23 17.67
July 26.79 19.43
August 26.79 19.66
September 26.35 18.47
October 26.15 18.77
November 25.19 14.32
December 25.04 13.59
     
Annual Sum or Average 25.73 16.01
Minimum of Months 24.82 12.64
Maximum of Months 26.79 19.66



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:37

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.210869E+12 126093.771 14-JAN-17:15 18221.747 56867.515 15486.076 0.000 21649.308 10720.100 1192.402 811.203 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.184034E+12 124366.017 01-FEB-18:15 22204.399 56867.515 15486.076 0.000 16080.503 10720.100 1192.402 669.386 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.202667E+12 123798.093 19-MAR-17:00 22204.399 56867.515 15486.076 0.000 15520.371 10720.100 1192.402 661.341 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.200576E+12 125927.569 12-APR-18:00 25049.151 51564.864 15486.076 0.000 20136.334 10720.100 1192.402 764.029 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.199177E+12 121594.552 24-MAY-18:45 25049.151 51564.864 15486.076 0.000 15937.068 10720.100 1192.402 630.277 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.205073E+12 138044.420 29-JUN-17:15 22204.399 56867.515 15486.076 0.000 39585.427 0.000 1192.402 1562.965 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.236212E+12 147397.081 18-JUL-17:30 22204.399 56867.515 15486.076 0.000 48676.944 0.000 1192.402 1823.856 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.242549E+12 145640.189 17-AUG-16:15 18221.747 56933.809 15486.076 0.000 50794.902 0.000 1192.402 1862.949 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.216721E+12 154358.706 29-SEP-17:45 22204.399 56867.515 15486.076 0.000 45161.621 10720.100 1192.402 1580.704 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.229257E+12 154821.262 15-OCT-17:15 22204.399 56867.515 15486.076 0.000 45725.146 10720.100 1192.402 1479.988 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.202701E+12 123653.449 29-NOV-18:15 22204.399 56867.515 15486.076 0.000 15494.497 10720.100 1192.402 542.824 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.213730E+12 125503.672 19-DEC-18:30 22204.399 56867.515 15486.076 0.000 17413.966 10720.100 1192.402 473.326 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.254357E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.184034E+12 121594.552   18221.747 51564.864 15486.076 0.000 15494.497 0.000 1192.402 473.326 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.242549E+12 154821.262   25049.151 56933.809 15486.076 0.000 50794.902 10720.100 1192.402 1862.949 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:37

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.930176E+11 84317.395 09-JAN-07:30 0.000 0.000 0.000 84317.395 81847.482 81847.482 2469.913
February 0.842781E+11 83559.289 13-FEB-18:15 0.000 0.000 0.000 83559.289 76533.806 76533.806 7025.482
March 0.925349E+11 93614.760 30-MAR-06:15 0.000 0.000 0.000 93614.760 80594.781 80594.781 13019.979
April 0.873389E+11 81526.145 01-APR-06:00 0.000 0.000 0.000 81526.145 81526.145 81526.145 0.000
May 0.879814E+11 80825.042 02-MAY-06:00 0.000 0.000 0.000 80825.042 80825.042 80825.042 0.000
June 0.831476E+11 80124.675 01-JUN-06:45 0.000 0.000 0.000 80124.675 80124.675 80124.675 0.000
July 0.846811E+11 79606.241 05-JUL-06:00 0.000 0.000 0.000 79606.241 79606.241 79606.241 0.000
August 0.845365E+11 79545.878 28-AUG-06:00 0.000 0.000 0.000 79545.878 79545.878 79545.878 0.000
September 0.827884E+11 79996.439 30-SEP-06:45 0.000 0.000 0.000 79996.439 79996.439 79996.439 0.000
October 0.874942E+11 80644.378 30-OCT-06:45 0.000 0.000 0.000 80644.378 80644.378 80644.378 0.000
November 0.868575E+11 81391.699 30-NOV-07:00 0.000 0.000 0.000 81391.699 81391.699 81391.699 0.000
December 0.918054E+11 81937.554 31-DEC-07:00 0.000 0.000 0.000 81937.554 81937.554 81937.554 0.000
                     
Annual Sum or Average 0.104646E+13     0.000 0.000 0.000        
Minimum of Months 0.827884E+11 79545.878   0.000 0.000 0.000 79545.878 76533.806 76533.806 0.000
Maximum of Months 0.930176E+11 93614.760   0.000 0.000 0.000 93614.760 81937.554 81937.554 13019.979