Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2018-10-19 09:40:12


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 6579.21 839.56 931.91
Net Site Energy 6579.21 839.56 931.91
Total Source Energy 13680.19 1745.71 1937.73
Net Source Energy 13680.19 1745.71 1937.73


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 544.10 1951.93 0.00 0.00 0.00 0.00
Cooling 157.30 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 167.13 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 655.48 0.00 0.00 0.00 0.00 0.00
Pumps 45.43 0.00 0.00 0.00 0.00 0.00
Heat Rejection 5.93 0.00 0.00 0.00 0.00 494.48
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1483.57 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3143.70 3435.51 0.00 0.00 0.00 5272.99
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 1951.93 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 544.10 0.00 0.00 0.00 0.00 0.00
Cooling General 157.30 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 167.13 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 655.48 0.00 0.00 0.00 0.00 0.00
Pumps General 45.43 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 5.93 0.00 0.00 0.00 0.00 494.48
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1483.57 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.66 0.00 0.00 0.00 0.00 0.00
HVAC 199.47 486.62 0.00 0.00 0.00 0.75
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 445.29 486.62 0.00 0.00 0.00 0.75


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.47 0.00 0.00 0.00 0.00 0.00
HVAC 179.70 438.40 0.00 0.00 0.00 0.67
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 401.16 438.40 0.00 0.00 0.00 0.67


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3143.70 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3143.70 100.00
     
Total On-Site and Utility Electric Sources 3143.70 100.00
Total Electricity End Uses 3143.70 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5272.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5272.99 100.00
Total Water End Uses 5272.99 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 109.00
Time Setpoint Not Met During Occupied Cooling 25.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 4098.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JAN-23:00 29-JAN-08:15 - - - 11-JUL-17:30
Heating 139844.76 221268.06 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 9687.49 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 29146.79 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 20785.11 0.00 0.00 0.00 0.00 0.00
Pumps 1443.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 95799.50 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 212165.24 317067.56 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 221268.06 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 8336.95 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1350.55 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 29146.79 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 20785.11 0.00 0.00 0.00 0.00 0.00
Pumps General 1443.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 95799.50 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 1723.16 2115.89 0.00 0.00 0.00
Cooling 498.18 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 529.31 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2075.90 0.00 0.00 0.00 0.00
Pumps 143.88 0.00 0.00 0.00 0.00
Heat Rejection 18.77 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1608.19 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9956.10 3724.09 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 244.08 299.71 0.00 0.00 0.00
Cooling 70.56 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 74.97 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 294.04 0.00 0.00 0.00 0.00
Pumps 20.38 0.00 0.00 0.00 0.00
Heat Rejection 2.66 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 227.79 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1410.23 527.50 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 244.08 299.71 0.00 0.00 0.00
Cooling 70.56 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 74.97 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 294.04 0.00 0.00 0.00 0.00
Pumps 20.38 0.00 0.00 0.00 0.00
Heat Rejection 2.66 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 227.79 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1410.23 527.50 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.42_SHGC_0.45 3.36 0.00 0.00 3.36 3.36 2.493 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.42_SHGC_0.45 6.97 0.00 0.00 6.97 6.97 2.493 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.42_SHGC_0.45 10.59 0.00 0.00 10.59 10.59 2.493 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.493 0.426 0.308              
North Total or Average           423.59 2.493 0.426 0.308              
Non-North Total or Average           726.80 2.493 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.06 83.06 167.13
Exterior Lighting Total 10720.10           167.13



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 253505.19 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 202804.15      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3321.35 2582.08 739.27 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   2312.85 1812.32 500.53 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4658.89 3623.19 1035.70 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2157.41 1712.59 444.82 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1441.61 1169.69 271.91 0.81 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1437.68 1168.03 269.65 0.81 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2548.65 1975.51 573.14 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2624.50 2034.02 590.48 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4424.22 3437.60 986.62 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3209.61 2507.62 701.99 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4525.10 3507.25 1017.85 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2563.62 2020.97 542.65 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1744.24 1388.34 355.90 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1723.24 1372.20 351.03 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3439.33 2664.76 774.58 0.77 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3469.18 2687.77 781.41 0.77 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4447.24 3457.72 989.52 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3258.29 2545.70 712.59 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4322.34 3353.21 969.13 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2615.20 2063.04 552.17 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1808.65 1439.32 369.32 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1788.03 1423.48 364.55 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3492.08 2706.85 785.23 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3507.91 2719.06 788.85 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4447.08 3459.37 987.71 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3268.82 2554.69 714.12 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4303.23 3340.23 963.00 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2619.28 2067.87 551.41 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1821.26 1450.14 371.12 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1800.65 1434.30 366.35 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3501.07 2714.85 786.22 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3515.00 2725.59 789.41 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4475.81 3482.98 992.83 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3301.71 2581.47 720.24 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4331.61 3363.56 968.05 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2650.74 2093.53 557.21 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1858.89 1479.98 378.91 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1838.32 1464.16 374.15 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3536.05 2742.71 793.35 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3549.67 2753.21 796.46 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4415.38 3437.62 977.76 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3244.27 2538.56 705.72 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4273.40 3319.89 953.51 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2594.37 2051.18 543.19 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1808.02 1441.68 366.34 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1787.53 1425.93 361.60 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3480.71 2700.77 779.94 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3494.29 2711.24 783.05 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4388.88 3418.27 970.61 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3221.04 2521.79 699.25 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4248.77 3301.97 946.80 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2571.38 2034.45 536.93 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1789.79 1428.36 361.43 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1769.38 1412.67 356.71 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3458.56 2684.34 774.22 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3472.12 2694.80 777.32 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4379.36 3411.92 967.45 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3215.70 2518.68 697.02 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4240.65 3296.67 943.98 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2565.15 2030.56 534.59 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1789.86 1429.03 360.83 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1769.56 1413.42 356.14 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3452.78 2680.48 772.31 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3466.35 2690.94 775.41 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4469.29 3482.19 987.10 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3312.41 2593.97 718.44 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4314.83 3354.80 960.03 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2594.71 2054.23 540.48 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1878.10 1497.40 380.70 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1856.97 1481.16 375.82 0.80 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3515.55 2729.44 786.11 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3530.78 2741.19 789.60 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5312.15 4129.05 1183.09 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3915.30 3059.09 856.20 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5060.75 3931.15 1129.60 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3028.56 2383.52 645.04 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2085.92 1654.19 431.73 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2043.06 1621.23 421.83 0.79 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4462.20 3460.15 1002.05 0.78 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4477.19 3471.71 1005.48 0.78 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3321.35 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   2312.85 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4658.89 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2157.41 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1441.61 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1437.68 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2548.65 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2624.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4424.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3209.61 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4525.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2563.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1744.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1723.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3439.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3469.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4447.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3258.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4322.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2615.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1808.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1788.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3492.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3507.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4447.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3268.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4303.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2619.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1821.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1800.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3501.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3515.00 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4475.81 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   3301.71 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4331.61 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   2650.74 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1858.89 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1838.32 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3536.05 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3549.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4415.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3244.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4273.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2594.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1808.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1787.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3480.71 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3494.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4388.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3221.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4248.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2571.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1789.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1769.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3458.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3472.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4379.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3215.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4240.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2565.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1789.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1769.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3452.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3466.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4469.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3312.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4314.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2594.71 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1878.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1856.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3515.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3530.78 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5312.15 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   3915.30 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   5060.75 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   3028.56 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2085.92 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2043.06 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4462.20 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4477.19 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   5502.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   5512.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   6951.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   5510.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   4507.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   4507.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   4495.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   4504.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   4786.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   4780.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   4807.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   4778.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   3625.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   3625.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   3634.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   3636.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   4612.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   4608.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   4611.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   4605.55 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   3450.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   3450.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   3455.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   3455.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   4585.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   4582.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   4581.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   4578.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   3416.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   3416.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   3421.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   3421.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   4554.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   4550.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   4550.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   4546.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   3382.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   3382.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   3388.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   3388.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   4604.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   4600.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   4600.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   4596.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   3425.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   3425.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   3430.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   3430.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   4628.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   4624.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   4624.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   4619.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   3445.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   3445.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   3451.80 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   3451.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   4671.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   4665.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   4666.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   4660.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   3485.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   3485.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   3492.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   3492.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   4948.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   4938.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   4944.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   4933.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   3745.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   3745.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   3756.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   3756.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   6347.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   6348.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   6343.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   6343.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   5226.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   5226.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   5223.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   5223.42 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.36 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 192.50 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 376.64 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 182.12 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.58 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.58 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 204.42 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 210.55 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 359.49 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 266.20 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 365.30 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 214.17 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 151.47 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 149.78 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 276.76 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.17 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 361.72 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.90 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 349.28 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 218.70 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 156.87 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 155.22 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 281.24 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.52 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 361.99 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 270.58 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 348.01 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 219.29 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 158.06 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 156.40 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.13 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.26 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 364.53 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 273.45 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 350.53 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 222.05 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 161.22 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 159.57 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 285.09 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 286.19 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 359.84 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.03 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.01 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 217.66 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 157.26 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 155.61 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 280.74 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 281.83 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 357.87 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.33 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 344.19 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 215.96 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 155.90 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 154.26 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.05 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 280.14 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 357.25 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.05 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 343.68 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 215.60 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 156.00 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 154.37 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.67 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.77 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 364.66 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 274.98 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 349.82 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 218.12 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.18 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 161.48 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.83 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 285.06 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.39 431.71 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 322.06 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 410.28 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 251.55 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 178.87 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.43 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 360.44 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 361.65 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0055 1406.33 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2519.32 3023.19 0.200 0.240 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 26.58 0.00698
G NW APARTMENT 1800.47 2160.56 0.143 0.172 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
OFFICE 3522.74 4227.29 0.280 0.336 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40 0.00698
G NE APARTMENT 1368.55 1642.26 0.109 0.131 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
G N1 APARTMENT 933.23 1119.88 0.074 0.089 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
G N2 APARTMENT 915.67 1098.81 0.073 0.087 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
G S1 APARTMENT 1911.94 2294.33 0.152 0.183 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
G S2 APARTMENT 1969.27 2363.13 0.157 0.188 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F2 SW APARTMENT 3362.34 4034.80 0.267 0.321 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F2 NW APARTMENT 2489.75 2987.70 0.198 0.238 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 22.86 0.00698
F2 SE APARTMENT 3416.68 4100.02 0.272 0.326 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F2 NE APARTMENT 2003.17 2403.80 0.159 0.191 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F2 N1 APARTMENT 1416.65 1699.98 0.113 0.135 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F2 N2 APARTMENT 1400.88 1681.06 0.111 0.134 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F2 S1 APARTMENT 2588.48 3106.18 0.206 0.247 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F2 S2 APARTMENT 2611.04 3133.25 0.208 0.249 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F3 SW APARTMENT 3383.18 4059.82 0.269 0.323 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F3 NW APARTMENT 2524.38 3029.26 0.201 0.241 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 23.14 0.00698
F3 SE APARTMENT 3266.81 3920.17 0.260 0.312 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F3 NE APARTMENT 2045.48 2454.58 0.163 0.195 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F3 N1 APARTMENT 1467.19 1760.63 0.117 0.140 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F3 N2 APARTMENT 1451.70 1742.04 0.115 0.139 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F3 S1 APARTMENT 2630.41 3156.49 0.209 0.251 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F3 S2 APARTMENT 2642.37 3170.85 0.210 0.252 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F4 SW APARTMENT 3385.65 4062.78 0.269 0.323 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F4 NW APARTMENT 2530.69 3036.82 0.201 0.242 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
F4 SE APARTMENT 3254.92 3905.91 0.259 0.311 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F4 NE APARTMENT 2051.01 2461.21 0.163 0.196 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F4 N1 APARTMENT 1478.29 1773.95 0.118 0.141 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F4 N2 APARTMENT 1462.80 1755.36 0.116 0.140 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F4 S1 APARTMENT 2638.76 3166.51 0.210 0.252 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F4 S2 APARTMENT 2649.28 3179.14 0.211 0.253 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
M SW APARTMENT 3409.49 4091.39 0.271 0.325 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
M NW APARTMENT 2557.60 3069.12 0.203 0.244 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
M SE APARTMENT 3278.48 3934.18 0.261 0.313 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
M NE APARTMENT 2076.82 2492.19 0.165 0.198 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
M N1 APARTMENT 1507.89 1809.46 0.120 0.144 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
M N2 APARTMENT 1492.42 1790.90 0.119 0.142 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
M S1 APARTMENT 2666.47 3199.77 0.212 0.255 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
M S2 APARTMENT 2676.77 3212.12 0.213 0.256 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F6 SW APARTMENT 3365.61 4038.73 0.268 0.321 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F6 NW APARTMENT 2516.19 3019.42 0.200 0.240 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
F6 SE APARTMENT 3236.25 3883.50 0.257 0.309 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F6 NE APARTMENT 2035.82 2442.98 0.162 0.194 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F6 N1 APARTMENT 1470.81 1764.97 0.117 0.140 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F6 N2 APARTMENT 1455.41 1746.49 0.116 0.139 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F6 S1 APARTMENT 2625.72 3150.87 0.209 0.251 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F6 S2 APARTMENT 2635.99 3163.19 0.210 0.252 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F7 SW APARTMENT 3347.16 4016.59 0.266 0.319 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F7 NW APARTMENT 2500.30 3000.36 0.199 0.239 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
F7 SE APARTMENT 3219.19 3863.03 0.256 0.307 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F7 NE APARTMENT 2019.88 2423.85 0.161 0.193 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F7 N1 APARTMENT 1458.10 1749.72 0.116 0.139 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F7 N2 APARTMENT 1442.76 1731.31 0.115 0.138 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F7 S1 APARTMENT 2609.94 3131.93 0.208 0.249 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F7 S2 APARTMENT 2620.18 3144.22 0.208 0.250 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F8 SW APARTMENT 3341.39 4009.67 0.266 0.319 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F8 NW APARTMENT 2497.72 2997.26 0.199 0.238 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
F8 SE APARTMENT 3214.46 3857.35 0.256 0.307 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F8 NE APARTMENT 2016.49 2419.78 0.160 0.192 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F8 N1 APARTMENT 1459.05 1750.85 0.116 0.139 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F8 N2 APARTMENT 1443.78 1732.54 0.115 0.138 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F8 S1 APARTMENT 2606.43 3127.71 0.207 0.249 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F8 S2 APARTMENT 2616.68 3140.02 0.208 0.250 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F9 SW APARTMENT 3410.72 4092.86 0.271 0.326 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
F9 NW APARTMENT 2571.87 3086.25 0.205 0.245 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
F9 SE APARTMENT 3271.88 3926.25 0.260 0.312 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
F9 NE APARTMENT 2040.10 2448.12 0.162 0.195 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
F9 N1 APARTMENT 1526.16 1831.39 0.121 0.146 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F9 N2 APARTMENT 1510.27 1812.32 0.120 0.144 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
F9 S1 APARTMENT 2654.68 3185.61 0.211 0.253 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
F9 S2 APARTMENT 2666.19 3199.43 0.212 0.254 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
T SW APARTMENT 4037.79 4845.35 0.321 0.385 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 26.94 0.00698
T NW APARTMENT 3012.23 3614.67 0.240 0.288 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95 0.00698
T SE APARTMENT 3837.35 4604.82 0.305 0.366 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40 0.00698
T NE APARTMENT 2352.72 2823.26 0.187 0.225 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 25.05 0.00698
T N1 APARTMENT 1672.97 2007.56 0.133 0.160 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:45:00 21.61 0.00698
T N2 APARTMENT 1640.71 1968.86 0.131 0.157 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:45:00 21.61 0.00698
T S1 APARTMENT 3371.19 4045.43 0.268 0.322 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
T S2 APARTMENT 3382.52 4059.03 0.269 0.323 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2990.42 3588.50 0.135 0.162 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G NW APARTMENT 2998.67 3598.40 0.136 0.163 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
OFFICE 3437.56 4125.07 0.155 0.186 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -41.90 0.00006
G NE APARTMENT 2997.18 3596.62 0.135 0.163 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G N1 APARTMENT 2149.00 2578.80 0.097 0.117 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G N2 APARTMENT 2148.97 2578.76 0.097 0.117 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G S1 APARTMENT 2139.32 2567.18 0.097 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G S2 APARTMENT 2146.52 2575.83 0.097 0.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
F2 SW APARTMENT 2385.01 2862.02 0.108 0.129 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 NW APARTMENT 2380.22 2856.27 0.108 0.129 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 SE APARTMENT 2403.10 2883.73 0.109 0.130 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 NE APARTMENT 2377.88 2853.46 0.107 0.129 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 N1 APARTMENT 1403.40 1684.08 0.063 0.076 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 N2 APARTMENT 1403.35 1684.03 0.063 0.076 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 S1 APARTMENT 1411.19 1693.42 0.064 0.077 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F2 S2 APARTMENT 1412.36 1694.83 0.064 0.077 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 SW APARTMENT 2237.80 2685.37 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 NW APARTMENT 2234.78 2681.74 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 SE APARTMENT 2237.06 2684.47 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 NE APARTMENT 2232.00 2678.40 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 N1 APARTMENT 1255.10 1506.12 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 N2 APARTMENT 1255.04 1506.05 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 S1 APARTMENT 1259.45 1511.34 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F3 S2 APARTMENT 1259.57 1511.48 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 SW APARTMENT 2214.88 2657.86 0.100 0.120 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 NW APARTMENT 2212.27 2654.72 0.100 0.120 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 SE APARTMENT 2211.98 2654.38 0.100 0.120 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 NE APARTMENT 2209.17 2651.00 0.100 0.120 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 N1 APARTMENT 1226.88 1472.26 0.055 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 N2 APARTMENT 1226.82 1472.18 0.055 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 S1 APARTMENT 1230.67 1476.81 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F4 S2 APARTMENT 1230.63 1476.75 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M SW APARTMENT 2188.85 2626.63 0.099 0.119 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M NW APARTMENT 2185.12 2622.14 0.099 0.119 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M SE APARTMENT 2185.52 2622.62 0.099 0.119 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M NE APARTMENT 2181.76 2618.11 0.099 0.118 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M N1 APARTMENT 1197.81 1437.37 0.054 0.065 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M N2 APARTMENT 1197.74 1437.29 0.054 0.065 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M S1 APARTMENT 1202.73 1443.28 0.054 0.065 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
M S2 APARTMENT 1202.67 1443.20 0.054 0.065 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 SW APARTMENT 2230.89 2677.07 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 NW APARTMENT 2227.62 2673.15 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 SE APARTMENT 2227.31 2672.77 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 NE APARTMENT 2224.04 2668.85 0.101 0.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 N1 APARTMENT 1234.28 1481.13 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 N2 APARTMENT 1234.20 1481.04 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 S1 APARTMENT 1238.68 1486.41 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F6 S2 APARTMENT 1238.60 1486.32 0.056 0.067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 SW APARTMENT 2251.45 2701.74 0.102 0.122 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 NW APARTMENT 2247.61 2697.14 0.102 0.122 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 SE APARTMENT 2247.68 2697.21 0.102 0.122 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 NE APARTMENT 2243.84 2692.61 0.101 0.122 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 N1 APARTMENT 1251.40 1501.68 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 N2 APARTMENT 1251.32 1501.58 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 S1 APARTMENT 1256.33 1507.60 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F7 S2 APARTMENT 1256.25 1507.51 0.057 0.068 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 SW APARTMENT 2287.44 2744.93 0.103 0.124 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 NW APARTMENT 2282.75 2739.31 0.103 0.124 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 SE APARTMENT 2283.51 2740.21 0.103 0.124 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 NE APARTMENT 2278.81 2734.57 0.103 0.124 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 N1 APARTMENT 1284.81 1541.77 0.058 0.070 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 N2 APARTMENT 1284.73 1541.67 0.058 0.070 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 S1 APARTMENT 1290.57 1548.69 0.058 0.070 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F8 S2 APARTMENT 1290.49 1548.59 0.058 0.070 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 SW APARTMENT 2522.41 3026.89 0.114 0.137 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 NW APARTMENT 2513.87 3016.65 0.114 0.136 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 SE APARTMENT 2518.28 3021.94 0.114 0.137 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 NE APARTMENT 2509.74 3011.69 0.113 0.136 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 N1 APARTMENT 1504.50 1805.40 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 N2 APARTMENT 1504.42 1805.30 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 S1 APARTMENT 1513.70 1816.44 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
F9 S2 APARTMENT 1513.62 1816.34 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T SW APARTMENT 3705.38 4446.45 0.168 0.201 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T NW APARTMENT 3706.12 4447.34 0.168 0.201 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T SE APARTMENT 3701.36 4441.63 0.167 0.201 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T NE APARTMENT 3702.09 4442.51 0.167 0.201 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T N1 APARTMENT 2757.25 3308.70 0.125 0.150 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T N2 APARTMENT 2757.16 3308.59 0.125 0.150 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T S1 APARTMENT 2754.59 3305.51 0.125 0.149 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006
T S2 APARTMENT 2754.50 3305.40 0.125 0.149 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -41.90 0.00006


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.24 0.24 0.16 0.16
AIRLOOP G NW 0.17 0.17 0.16 0.16
AIRLOOP OFFICE 0.34 0.34 0.19 0.19
AIRLOOP G NE 0.13 0.13 0.16 0.16
AIRLOOP G N1 0.09 0.09 0.12 0.12
AIRLOOP G N2 0.09 0.09 0.12 0.12
AIRLOOP G S1 0.18 0.18 0.12 0.12
AIRLOOP G S2 0.19 0.19 0.12 0.12
AIRLOOP F2 SW 0.32 0.32 0.13 0.13
AIRLOOP F2 NW 0.24 0.24 0.13 0.13
AIRLOOP F2 SE 0.33 0.33 0.13 0.13
AIRLOOP F2 NE 0.19 0.19 0.13 0.13
AIRLOOP F2 N1 0.14 0.14 0.08 0.08
AIRLOOP F2 N2 0.13 0.13 0.08 0.08
AIRLOOP F2 S1 0.25 0.25 0.08 0.08
AIRLOOP F2 S2 0.25 0.25 0.08 0.08
AIRLOOP F3 SW 0.32 0.32 0.12 0.12
AIRLOOP F3 NW 0.24 0.24 0.12 0.12
AIRLOOP F3 SE 0.31 0.31 0.12 0.12
AIRLOOP F3 NE 0.20 0.20 0.12 0.12
AIRLOOP F3 N1 0.14 0.14 0.07 0.07
AIRLOOP F3 N2 0.14 0.14 0.07 0.07
AIRLOOP F3 S1 0.25 0.25 0.07 0.07
AIRLOOP F3 S2 0.25 0.25 0.07 0.07
AIRLOOP F4 SW 0.32 0.32 0.12 0.12
AIRLOOP F4 NW 0.24 0.24 0.12 0.12
AIRLOOP F4 SE 0.31 0.31 0.12 0.12
AIRLOOP F4 NE 0.20 0.20 0.12 0.12
AIRLOOP F4 N1 0.14 0.14 0.07 0.07
AIRLOOP F4 N2 0.14 0.14 0.07 0.07
AIRLOOP F4 S1 0.25 0.25 0.07 0.07
AIRLOOP F4 S2 0.25 0.25 0.07 0.07
AIRLOOP M SW 0.33 0.33 0.12 0.12
AIRLOOP M NW 0.24 0.24 0.12 0.12
AIRLOOP M SE 0.31 0.31 0.12 0.12
AIRLOOP M NE 0.20 0.20 0.12 0.12
AIRLOOP M N1 0.14 0.14 0.06 0.06
AIRLOOP M N2 0.14 0.14 0.06 0.06
AIRLOOP M S1 0.25 0.25 0.07 0.07
AIRLOOP M S2 0.26 0.26 0.07 0.07
AIRLOOP F6 SW 0.32 0.32 0.12 0.12
AIRLOOP F6 NW 0.24 0.24 0.12 0.12
AIRLOOP F6 SE 0.31 0.31 0.12 0.12
AIRLOOP F6 NE 0.19 0.19 0.12 0.12
AIRLOOP F6 N1 0.14 0.14 0.07 0.07
AIRLOOP F6 N2 0.14 0.14 0.07 0.07
AIRLOOP F6 S1 0.25 0.25 0.07 0.07
AIRLOOP F6 S2 0.25 0.25 0.07 0.07
AIRLOOP F7 SW 0.32 0.32 0.12 0.12
AIRLOOP F7 NW 0.24 0.24 0.12 0.12
AIRLOOP F7 SE 0.31 0.31 0.12 0.12
AIRLOOP F7 NE 0.19 0.19 0.12 0.12
AIRLOOP F7 N1 0.14 0.14 0.07 0.07
AIRLOOP F7 N2 0.14 0.14 0.07 0.07
AIRLOOP F7 S1 0.25 0.25 0.07 0.07
AIRLOOP F7 S2 0.25 0.25 0.07 0.07
AIRLOOP F8 SW 0.32 0.32 0.12 0.12
AIRLOOP F8 NW 0.24 0.24 0.12 0.12
AIRLOOP F8 SE 0.31 0.31 0.12 0.12
AIRLOOP F8 NE 0.19 0.19 0.12 0.12
AIRLOOP F8 N1 0.14 0.14 0.07 0.07
AIRLOOP F8 N2 0.14 0.14 0.07 0.07
AIRLOOP F8 S1 0.25 0.25 0.07 0.07
AIRLOOP F8 S2 0.25 0.25 0.07 0.07
AIRLOOP F9 SW 0.33 0.33 0.14 0.14
AIRLOOP F9 NW 0.25 0.25 0.14 0.14
AIRLOOP F9 SE 0.31 0.31 0.14 0.14
AIRLOOP F9 NE 0.19 0.19 0.14 0.14
AIRLOOP F9 N1 0.15 0.15 0.08 0.08
AIRLOOP F9 N2 0.14 0.14 0.08 0.08
AIRLOOP F9 S1 0.25 0.25 0.08 0.08
AIRLOOP F9 S2 0.25 0.25 0.08 0.08
AIRLOOP T SW 0.39 0.39 0.20 0.20
AIRLOOP T NW 0.29 0.29 0.20 0.20
AIRLOOP T SE 0.37 0.37 0.20 0.20
AIRLOOP T NE 0.22 0.22 0.20 0.20
AIRLOOP T N1 0.16 0.16 0.15 0.15
AIRLOOP T N2 0.16 0.16 0.15 0.15
AIRLOOP T S1 0.32 0.32 0.15 0.15
AIRLOOP T S2 0.32 0.32 0.15 0.15



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4178.50 6600.50 3063.00
G NW APARTMENT 4312.25 7378.50 3675.75
OFFICE 1245.75 1394.75 731.75
G NE APARTMENT 4429.25 7228.75 3621.00
G N1 APARTMENT 3411.50 7570.25 2979.00
G N2 APARTMENT 3411.25 7555.25 2972.50
G S1 APARTMENT 3292.00 6667.50 2286.50
G S2 APARTMENT 3299.25 6600.25 2253.25
F2 SW APARTMENT 4124.75 5569.75 2143.25
F2 NW APARTMENT 4056.25 6511.75 2743.25
F2 SE APARTMENT 4250.25 5420.75 2022.50
F2 NE APARTMENT 4095.25 6395.25 2652.75
F2 N1 APARTMENT 2291.00 6734.50 1181.00
F2 N2 APARTMENT 2302.50 6711.00 1179.25
F2 S1 APARTMENT 2642.50 5443.75 747.25
F2 S2 APARTMENT 2661.50 5419.50 737.25
F3 SW APARTMENT 4073.25 5413.50 1914.75
F3 NW APARTMENT 3931.75 6286.50 2501.25
F3 SE APARTMENT 4189.75 5333.50 1885.25
F3 NE APARTMENT 3969.00 6189.75 2422.75
F3 N1 APARTMENT 2116.25 6427.25 852.25
F3 N2 APARTMENT 2121.50 6408.00 851.25
F3 S1 APARTMENT 2607.25 5185.25 479.25
F3 S2 APARTMENT 2618.75 5173.25 477.00
F4 SW APARTMENT 4080.50 5391.50 1875.25
F4 NW APARTMENT 3924.00 6204.00 2462.25
F4 SE APARTMENT 4183.25 5323.50 1857.50
F4 NE APARTMENT 3966.25 6133.00 2385.00
F4 N1 APARTMENT 2118.75 6301.00 803.25
F4 N2 APARTMENT 2127.25 6286.25 802.25
F4 S1 APARTMENT 2642.50 5140.00 433.50
F4 S2 APARTMENT 2653.50 5130.00 432.50
M SW APARTMENT 4044.75 5385.75 1827.25
M NW APARTMENT 3869.50 6192.25 2394.25
M SE APARTMENT 4146.50 5317.25 1809.25
M NE APARTMENT 3917.50 6117.75 2321.25
M N1 APARTMENT 2067.75 6259.00 724.25
M N2 APARTMENT 2079.75 6247.25 723.75
M S1 APARTMENT 2630.50 5114.50 393.50
M S2 APARTMENT 2636.75 5104.75 392.75
F6 SW APARTMENT 4037.50 5467.00 1928.25
F6 NW APARTMENT 3910.75 6327.25 2530.25
F6 SE APARTMENT 4147.75 5396.50 1910.50
F6 NE APARTMENT 3968.50 6229.00 2451.25
F6 N1 APARTMENT 2094.75 6380.75 839.50
F6 N2 APARTMENT 2102.50 6366.00 838.50
F6 S1 APARTMENT 2570.25 5203.00 456.00
F6 S2 APARTMENT 2583.75 5195.50 455.25
F7 SW APARTMENT 4032.75 5525.00 1985.75
F7 NW APARTMENT 3925.75 6423.50 2608.00
F7 SE APARTMENT 4137.00 5454.50 1963.75
F7 NE APARTMENT 3986.75 6325.25 2519.00
F7 N1 APARTMENT 2098.75 6490.25 900.00
F7 N2 APARTMENT 2110.00 6470.00 900.75
F7 S1 APARTMENT 2544.75 5271.00 496.25
F7 S2 APARTMENT 2553.25 5259.50 495.25
F8 SW APARTMENT 4031.50 5593.50 2055.75
F8 NW APARTMENT 3968.75 6508.00 2690.75
F8 SE APARTMENT 4146.25 5515.25 2031.50
F8 NE APARTMENT 4019.75 6424.75 2592.75
F8 N1 APARTMENT 2136.00 6598.75 985.50
F8 N2 APARTMENT 2145.75 6581.75 986.00
F8 S1 APARTMENT 2551.00 5357.25 565.50
F8 S2 APARTMENT 2561.25 5344.75 563.75
F9 SW APARTMENT 4226.00 5727.75 2376.00
F9 NW APARTMENT 4234.25 6642.00 3002.25
F9 SE APARTMENT 4341.75 5633.00 2333.75
F9 NE APARTMENT 4273.25 6532.00 2905.25
F9 N1 APARTMENT 2518.75 6738.00 1404.00
F9 N2 APARTMENT 2524.25 6723.75 1401.25
F9 S1 APARTMENT 2801.00 5511.75 949.25
F9 S2 APARTMENT 2815.00 5501.25 948.25
T SW APARTMENT 5237.50 6169.25 3541.50
T NW APARTMENT 5154.00 6790.50 3983.75
T SE APARTMENT 5296.75 6087.75 3488.75
T NE APARTMENT 5212.75 6740.00 3930.50
T N1 APARTMENT 4525.50 6956.50 3490.25
T N2 APARTMENT 4533.75 6944.50 3485.25
T S1 APARTMENT 4624.75 5993.50 2923.00
T S2 APARTMENT 4636.50 5980.00 2919.25
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 6704.75 7663.75 4098.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 1.25 0.00 1.25 0.00
G NW APARTMENT 1.75 0.00 1.75 0.00
OFFICE 1.00 0.00 0.00 0.00
G NE APARTMENT 2.00 0.00 2.00 0.00
G N1 APARTMENT 0.75 0.00 0.75 0.00
G N2 APARTMENT 1.75 0.00 1.75 0.00
G S1 APARTMENT 0.25 0.00 0.25 0.00
G S2 APARTMENT 0.00 0.00 0.00 0.00
F2 SW APARTMENT 4.75 0.00 4.75 0.00
F2 NW APARTMENT 1.00 0.00 1.00 0.00
F2 SE APARTMENT 2.75 0.00 2.75 0.00
F2 NE APARTMENT 1.00 0.00 1.00 0.00
F2 N1 APARTMENT 1.00 1.75 1.00 1.75
F2 N2 APARTMENT 0.50 2.00 0.50 2.00
F2 S1 APARTMENT 2.25 0.00 2.25 0.00
F2 S2 APARTMENT 2.00 0.00 2.00 0.00
F3 SW APARTMENT 2.00 0.00 2.00 0.00
F3 NW APARTMENT 1.00 0.00 1.00 0.00
F3 SE APARTMENT 3.25 0.00 3.25 0.00
F3 NE APARTMENT 0.50 0.00 0.50 0.00
F3 N1 APARTMENT 0.75 3.50 0.75 3.50
F3 N2 APARTMENT 0.75 3.75 0.75 3.75
F3 S1 APARTMENT 3.00 0.00 3.00 0.00
F3 S2 APARTMENT 3.25 0.00 3.25 0.00
F4 SW APARTMENT 4.25 0.00 4.25 0.00
F4 NW APARTMENT 2.50 0.00 2.50 0.00
F4 SE APARTMENT 4.00 0.00 4.00 0.00
F4 NE APARTMENT 1.75 0.00 1.75 0.00
F4 N1 APARTMENT 1.25 4.25 1.25 4.25
F4 N2 APARTMENT 0.50 4.50 0.50 4.50
F4 S1 APARTMENT 2.75 0.00 2.75 0.00
F4 S2 APARTMENT 1.75 0.00 1.75 0.00
M SW APARTMENT 2.75 0.00 2.75 0.00
M NW APARTMENT 2.75 0.00 2.75 0.00
M SE APARTMENT 1.50 0.00 1.50 0.00
M NE APARTMENT 1.00 0.25 1.00 0.25
M N1 APARTMENT 0.50 4.50 0.50 4.50
M N2 APARTMENT 1.00 5.25 1.00 5.25
M S1 APARTMENT 1.75 0.00 1.75 0.00
M S2 APARTMENT 2.25 0.00 2.25 0.00
F6 SW APARTMENT 1.25 0.00 1.25 0.00
F6 NW APARTMENT 2.00 0.00 2.00 0.00
F6 SE APARTMENT 2.25 0.00 2.25 0.00
F6 NE APARTMENT 1.75 0.50 1.75 0.50
F6 N1 APARTMENT 0.75 5.50 0.75 5.50
F6 N2 APARTMENT 1.75 6.00 1.75 6.00
F6 S1 APARTMENT 2.50 0.00 2.50 0.00
F6 S2 APARTMENT 1.50 0.00 1.50 0.00
F7 SW APARTMENT 1.25 0.00 1.25 0.00
F7 NW APARTMENT 2.25 0.75 2.25 0.75
F7 SE APARTMENT 2.00 0.00 2.00 0.00
F7 NE APARTMENT 0.75 0.50 0.75 0.50
F7 N1 APARTMENT 1.25 6.00 1.25 6.00
F7 N2 APARTMENT 0.50 6.25 0.50 6.25
F7 S1 APARTMENT 2.50 0.00 2.50 0.00
F7 S2 APARTMENT 1.75 0.00 1.75 0.00
F8 SW APARTMENT 2.00 0.00 2.00 0.00
F8 NW APARTMENT 1.50 0.75 1.50 0.75
F8 SE APARTMENT 2.75 0.00 2.75 0.00
F8 NE APARTMENT 1.50 0.75 1.50 0.75
F8 N1 APARTMENT 1.50 5.75 1.50 5.75
F8 N2 APARTMENT 1.25 6.25 1.25 6.25
F8 S1 APARTMENT 3.00 0.00 3.00 0.00
F8 S2 APARTMENT 1.75 0.00 1.75 0.00
F9 SW APARTMENT 0.75 0.00 0.75 0.00
F9 NW APARTMENT 2.00 0.50 2.00 0.50
F9 SE APARTMENT 0.50 0.00 0.50 0.00
F9 NE APARTMENT 2.75 1.75 2.75 1.75
F9 N1 APARTMENT 0.75 4.75 0.75 4.75
F9 N2 APARTMENT 1.00 5.00 1.00 5.00
F9 S1 APARTMENT 2.00 0.00 2.00 0.00
F9 S2 APARTMENT 1.75 0.00 1.75 0.00
T SW APARTMENT 0.25 0.00 0.25 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.50 0.00 0.50 0.00
T NE APARTMENT 1.25 0.00 1.25 0.00
T N1 APARTMENT 2.00 22.00 2.00 22.00
T N2 APARTMENT 1.75 25.00 1.75 25.00
T S1 APARTMENT 2.50 0.00 2.50 0.00
T S2 APARTMENT 1.25 0.00 1.25 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 110.00 25.00 109.00 25.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.355 0.063 0.000 0.192
G NW APARTMENT 1.71 2.50 268.96 0.355 0.063 0.000 0.185
OFFICE 0.94 1.00 268.96 0.520 0.061 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.355 0.063 0.000 0.187
G N1 APARTMENT 1.71 2.50 268.96 0.355 0.038 0.000 0.181
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.038 0.000 0.181
G S1 APARTMENT 1.71 2.50 268.96 0.355 0.038 0.000 0.189
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.038 0.000 0.190
F2 SW APARTMENT 1.71 2.50 268.96 0.355 0.091 0.000 0.213
F2 NW APARTMENT 1.71 2.50 268.96 0.355 0.091 0.000 0.210
F2 SE APARTMENT 1.71 2.50 268.96 0.355 0.091 0.000 0.214
F2 NE APARTMENT 1.71 2.50 268.96 0.355 0.091 0.000 0.212
F2 N1 APARTMENT 1.71 2.50 268.96 0.355 0.055 0.000 0.207
F2 N2 APARTMENT 1.71 2.50 268.97 0.355 0.055 0.000 0.207
F2 S1 APARTMENT 1.71 2.50 268.96 0.355 0.055 0.000 0.213
F2 S2 APARTMENT 1.71 2.50 268.97 0.355 0.055 0.000 0.213
F3 SW APARTMENT 1.71 2.50 268.96 0.355 0.108 0.000 0.226
F3 NW APARTMENT 1.71 2.50 268.96 0.355 0.108 0.000 0.224
F3 SE APARTMENT 1.71 2.50 268.96 0.355 0.108 0.000 0.227
F3 NE APARTMENT 1.71 2.50 268.96 0.355 0.108 0.000 0.225
F3 N1 APARTMENT 1.71 2.50 268.96 0.355 0.065 0.000 0.222
F3 N2 APARTMENT 1.71 2.50 268.97 0.355 0.065 0.000 0.222
F3 S1 APARTMENT 1.71 2.50 268.96 0.355 0.065 0.000 0.226
F3 S2 APARTMENT 1.71 2.50 268.97 0.355 0.065 0.000 0.226
F4 SW APARTMENT 1.71 2.50 268.96 0.355 0.121 0.000 0.225
F4 NW APARTMENT 1.71 2.50 268.96 0.355 0.121 0.000 0.224
F4 SE APARTMENT 1.71 2.50 268.96 0.355 0.121 0.000 0.225
F4 NE APARTMENT 1.71 2.50 268.96 0.355 0.121 0.000 0.224
F4 N1 APARTMENT 1.71 2.50 268.96 0.355 0.073 0.000 0.221
F4 N2 APARTMENT 1.71 2.50 268.97 0.355 0.073 0.000 0.221
F4 S1 APARTMENT 1.71 2.50 268.96 0.355 0.073 0.000 0.224
F4 S2 APARTMENT 1.71 2.50 268.97 0.355 0.073 0.000 0.224
M SW APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.233
M NW APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.232
M SE APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.233
M NE APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.233
M N1 APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.230
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.079 0.000 0.230
M S1 APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.232
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.079 0.000 0.233
F6 SW APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.240
F6 NW APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.239
F6 SE APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.241
F6 NE APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.240
F6 N1 APARTMENT 1.71 2.50 268.96 0.355 0.084 0.000 0.236
F6 N2 APARTMENT 1.71 2.50 268.97 0.355 0.084 0.000 0.237
F6 S1 APARTMENT 1.71 2.50 268.96 0.355 0.085 0.000 0.239
F6 S2 APARTMENT 1.71 2.50 268.97 0.355 0.085 0.000 0.239
F7 SW APARTMENT 1.71 2.50 268.96 0.355 0.148 0.000 0.246
F7 NW APARTMENT 1.71 2.50 268.96 0.355 0.148 0.000 0.245
F7 SE APARTMENT 1.71 2.50 268.96 0.355 0.148 0.000 0.247
F7 NE APARTMENT 1.71 2.50 268.96 0.355 0.148 0.000 0.246
F7 N1 APARTMENT 1.71 2.50 268.96 0.355 0.089 0.000 0.242
F7 N2 APARTMENT 1.71 2.50 268.97 0.355 0.089 0.000 0.242
F7 S1 APARTMENT 1.71 2.50 268.96 0.355 0.089 0.000 0.245
F7 S2 APARTMENT 1.71 2.50 268.97 0.355 0.089 0.000 0.245
F8 SW APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.252
F8 NW APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.251
F8 SE APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.253
F8 NE APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.251
F8 N1 APARTMENT 1.71 2.50 268.96 0.355 0.094 0.000 0.248
F8 N2 APARTMENT 1.71 2.50 268.97 0.355 0.094 0.000 0.248
F8 S1 APARTMENT 1.71 2.50 268.96 0.355 0.094 0.000 0.251
F8 S2 APARTMENT 1.71 2.50 268.97 0.355 0.094 0.000 0.251
F9 SW APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.258
F9 NW APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.256
F9 SE APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.258
F9 NE APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.257
F9 N1 APARTMENT 1.71 2.50 268.96 0.355 0.098 0.000 0.254
F9 N2 APARTMENT 1.71 2.50 268.97 0.355 0.098 0.000 0.254
F9 S1 APARTMENT 1.71 2.50 268.96 0.355 0.098 0.000 0.257
F9 S2 APARTMENT 1.71 2.50 268.97 0.355 0.098 0.000 0.257
T SW APARTMENT 1.71 2.50 268.96 0.355 0.168 0.000 0.261
T NW APARTMENT 1.71 2.50 268.96 0.355 0.168 0.000 0.260
T SE APARTMENT 1.71 2.50 268.96 0.355 0.168 0.000 0.262
T NE APARTMENT 1.71 2.50 268.96 0.355 0.168 0.000 0.261
T N1 APARTMENT 1.71 2.50 268.96 0.355 0.101 0.000 0.258
T N2 APARTMENT 1.71 2.50 268.97 0.355 0.101 0.000 0.258
T S1 APARTMENT 1.71 2.50 268.96 0.355 0.101 0.000 0.261
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.101 0.000 0.261
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.503 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 655.48 20785.11 01-JAN-00:15 20785.11 01-JAN-06:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1377.71 21165.63 06-JUN-02:15 161387.04 29-JAN-00:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
ElectricityPurchased:Plant 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
Cogeneration:ElectricityPurchased 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
ElectricityNet:Plant 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
Cogeneration:ElectricityNet 3143.70 48006.02 06-JUN-02:45 212165.24 28-JAN-24:00
ExteriorLights:Electricity 167.13 0.00 01-JAN-11:30 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 167.13 0.00 01-JAN-11:30 10720.10 01-JAN-00:15
General:Fans:Electricity 655.48 20785.11 01-JAN-00:15 20785.11 01-JAN-06:15
Cooling:Electricity 157.30 0.00 01-JAN-00:15 60059.47 21-JUL-14:15
Heating:Electricity 544.10 0.00 11-APR-17:15 140174.76 29-JAN-00:15
Electricity:Plant 51.36 36.93 07-MAY-18:45 3477.59 29-JUL-16:30
HeatRejection:Electricity 5.93 0.00 01-JAN-00:15 2034.33 29-JUL-16:30
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 45.43 36.93 07-MAY-18:45 1443.26 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 3435.51 9260.51 22-MAR-22:30 317067.56 29-JAN-08:15
Gas:Plant 3435.51 9260.51 22-MAR-22:30 317067.56 29-JAN-08:15
WaterSystems:Gas 1483.57 9260.51 01-JAN-00:15 96868.71 18-MAR-07:00
Water Heater:WaterSystems:Gas 1483.57 9260.51 01-JAN-00:15 96868.71 18-MAR-07:00
Heating:Gas 1951.93 0.00 20-MAR-13:00 246772.37 29-JAN-00:30
Boiler:Heating:Gas 1951.93 0.00 20-MAR-13:00 246772.37 29-JAN-00:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 605.52 0.00 01-JAN-00:15 260989.96 30-JUN-12:30
PlantLoopCoolingDemand:HVAC 605.52 0.00 01-JAN-00:15 260989.96 30-JUN-12:30
CoolingCoils:PlantLoopCoolingDemand 605.52 0.00 01-JAN-00:15 260989.96 30-JUN-12:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 5272.99 0.00 01-JAN-02:15 0.00 11-JUL-17:30
Water:Plant 5272.99 0.00 01-JAN-02:15 0.00 11-JUL-17:30
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 5272.99 0.00 01-JAN-02:15 0.00 11-JUL-17:30
MainsWater:Plant 5272.99 0.00 01-JAN-02:15 0.00 11-JUL-17:30
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 494.48 0.00 01-JAN-00:15 0.00 21-JUL-16:00
HeatRejection:MainsWater 494.48 0.00 01-JAN-00:15 0.00 21-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 2722.60 645.72 24-AUG-01:15 249230.42 29-JAN-08:00
PlantLoopHeatingDemand:Plant 1130.27 645.72 24-AUG-01:15 71347.09 01-JAN-07:15
WaterSystems:PlantLoopHeatingDemand 1130.27 645.72 24-AUG-01:15 71347.09 01-JAN-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 6903.27 8268.15 08-AUG-02:00 795761.46 28-JAN-24:00
EnergyTransfer:Building 1642.72 3668.66 18-JUN-17:00 241439.85 29-JAN-00:15
EnergyTransfer:Zone:G SW APARTMENT 22.26 0.03 24-AUG-11:00 2748.36 29-JAN-00:15
Heating:EnergyTransfer 1017.02 0.00 22-MAR-15:15 241439.85 29-JAN-00:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 17.18 0.00 09-FEB-11:30 2748.36 29-JAN-00:15
Cooling:EnergyTransfer 625.70 0.00 01-JAN-00:15 180606.69 11-JUL-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 5.08 0.00 01-JAN-00:15 2406.49 11-AUG-16:15
EnergyTransfer:Zone:G NW APARTMENT 23.26 0.01 24-AUG-20:15 2812.47 29-JAN-00:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 20.17 0.00 22-MAR-14:30 2812.47 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G NW APARTMENT 3.09 0.00 01-JAN-00:15 1877.74 11-JUL-17:30
EnergyTransfer:Zone:OFFICE 26.65 0.01 06-OCT-21:30 3271.51 10-AUG-13:30
Heating:EnergyTransfer:Zone:OFFICE 15.75 0.00 20-JAN-12:00 2888.39 28-JAN-24:00
Cooling:EnergyTransfer:Zone:OFFICE 10.90 0.00 01-JAN-00:15 3271.51 10-AUG-13:30
EnergyTransfer:Zone:G NE APARTMENT 23.16 0.00 30-JUL-20:15 2820.21 29-JAN-00:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 19.68 0.00 20-MAR-09:15 2820.21 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G NE APARTMENT 3.49 0.00 01-JAN-00:15 1499.12 11-JUL-05:30
EnergyTransfer:Zone:G N1 APARTMENT 15.55 0.01 16-JUN-12:15 1859.48 12-JAN-08:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 12.28 0.00 18-MAR-16:15 1859.48 12-JAN-08:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 3.27 0.00 01-JAN-00:15 1079.02 11-JUL-17:30
EnergyTransfer:Zone:G N2 APARTMENT 15.54 0.01 03-JUL-16:00 1859.40 12-JAN-08:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 12.25 0.00 18-MAR-16:15 1859.40 12-JAN-08:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 3.29 0.00 01-JAN-00:15 1074.48 11-JUL-17:30
EnergyTransfer:Zone:G S1 APARTMENT 14.84 0.01 06-MAY-14:15 1897.36 21-JUL-14:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 9.38 0.00 23-JAN-12:45 1831.30 12-JAN-08:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 5.47 0.00 01-JAN-00:15 1897.36 21-JUL-14:15
EnergyTransfer:Zone:G S2 APARTMENT 14.81 0.00 10-JUN-10:15 1944.00 21-JUL-14:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 9.22 0.00 23-JAN-12:30 1821.59 12-JAN-08:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 5.58 0.00 01-JAN-00:15 1944.00 21-JUL-14:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 23.35 0.09 14-JUL-20:15 3198.47 11-AUG-16:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 13.73 0.00 09-FEB-11:15 3036.51 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 9.62 0.00 01-JAN-00:15 3198.47 11-AUG-16:15
EnergyTransfer:Zone:F2 NW APARTMENT 22.33 0.03 06-OCT-06:00 3161.71 29-JAN-00:15
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 17.19 0.00 18-MAR-15:00 3161.71 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 5.14 0.00 01-JAN-00:15 2606.26 11-JUL-17:30
EnergyTransfer:Zone:F2 SE APARTMENT 24.47 0.05 08-NOV-11:15 3302.48 21-JUL-14:15
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 12.92 0.00 05-FEB-11:15 3043.21 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 11.56 0.00 01-JAN-00:15 3302.48 21-JUL-14:15
EnergyTransfer:Zone:F2 NE APARTMENT 22.87 0.03 18-MAR-18:15 3175.45 29-JAN-00:15
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 16.62 0.00 18-MAR-11:00 3175.45 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 6.24 0.00 01-JAN-00:15 2080.54 13-JUN-06:45
EnergyTransfer:Zone:F2 N1 APARTMENT 13.08 0.03 19-JUN-14:00 1797.63 29-JAN-00:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 7.85 0.00 21-JAN-21:00 1797.63 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 5.23 0.00 01-JAN-00:15 1407.14 11-JUL-16:15
EnergyTransfer:Zone:F2 N2 APARTMENT 13.11 0.00 31-MAY-11:30 1797.81 29-JAN-00:30
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 7.82 0.00 21-JAN-21:00 1797.81 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 5.28 0.00 01-JAN-00:15 1392.06 11-JUL-16:15
EnergyTransfer:Zone:F2 S1 APARTMENT 15.62 0.02 09-OCT-03:30 2554.13 21-JUL-14:15
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 5.52 0.00 16-JAN-12:45 1672.31 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 10.10 0.00 01-JAN-00:15 2554.13 21-JUL-14:15
EnergyTransfer:Zone:F2 S2 APARTMENT 15.72 0.06 15-JUL-10:00 2577.04 21-JUL-14:15
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 5.48 0.00 16-JAN-12:45 1671.69 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 10.24 0.00 01-JAN-00:15 2577.04 21-JUL-14:15
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 23.44 0.10 08-AUG-03:15 3254.55 11-AUG-16:15
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 12.86 0.00 23-JAN-12:45 3223.70 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 10.58 0.00 01-JAN-00:15 3254.55 11-AUG-16:15
EnergyTransfer:Zone:F3 NW APARTMENT 22.04 0.20 16-JUN-20:30 3354.49 29-JAN-00:15
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 16.28 0.00 18-MAR-11:45 3354.49 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 5.76 0.00 01-JAN-00:15 2647.12 11-JUL-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 24.55 0.12 25-SEP-04:45 3340.32 22-JUL-12:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 12.49 0.00 23-JAN-12:45 3237.05 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 12.05 0.00 01-JAN-00:15 3340.32 22-JUL-12:00
EnergyTransfer:Zone:F3 NE APARTMENT 22.66 0.09 18-JUL-20:45 3370.71 29-JAN-00:15
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 15.74 0.00 17-MAR-19:00 3370.71 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 6.92 0.00 01-JAN-00:15 2165.50 13-JUN-06:45
EnergyTransfer:Zone:F3 N1 APARTMENT 12.69 0.05 04-JUN-13:45 1864.61 29-JAN-00:30
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 6.78 0.00 19-JAN-18:45 1864.61 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 5.92 0.00 01-JAN-00:15 1464.07 29-JUN-19:45
EnergyTransfer:Zone:F3 N2 APARTMENT 12.73 0.04 13-FEB-17:15 1864.82 29-JAN-00:30
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 6.75 0.00 19-JAN-18:45 1864.82 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 5.97 0.00 01-JAN-00:15 1455.90 29-JUN-19:30
EnergyTransfer:Zone:F3 S1 APARTMENT 16.12 0.03 09-MAY-17:45 2625.38 21-JUL-14:15
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 4.62 0.00 16-JAN-12:30 1731.39 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 11.50 0.00 01-JAN-00:15 2625.38 21-JUL-14:15
EnergyTransfer:Zone:F3 S2 APARTMENT 16.21 0.14 11-FEB-01:00 2642.01 21-JUL-14:15
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 4.61 0.00 16-JAN-12:30 1731.28 29-JAN-00:30
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 11.60 0.00 01-JAN-00:15 2642.01 21-JUL-14:15
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 23.73 0.06 12-AUG-18:45 3434.25 29-JAN-00:15
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 12.94 0.00 23-JAN-13:00 3434.25 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 10.79 0.00 01-JAN-00:15 3277.62 11-JUL-17:30
EnergyTransfer:Zone:F4 NW APARTMENT 22.36 0.36 04-JUN-14:15 3568.53 28-JAN-24:00
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 16.42 0.00 18-MAR-11:15 3568.53 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 5.94 0.00 01-JAN-00:15 2655.32 11-JUL-17:30
EnergyTransfer:Zone:F4 SE APARTMENT 24.82 0.24 06-APR-07:00 3451.00 29-JAN-00:15
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 12.64 0.00 23-JAN-12:15 3451.00 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 12.19 0.00 01-JAN-00:15 3356.10 22-JUL-12:00
EnergyTransfer:Zone:F4 NE APARTMENT 23.00 0.01 16-JUL-12:00 3586.53 28-JAN-24:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 15.88 0.00 10-MAR-08:00 3586.53 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 7.12 0.00 01-JAN-00:15 2201.96 13-JUN-07:00
EnergyTransfer:Zone:F4 N1 APARTMENT 12.88 0.01 12-MAY-19:00 1982.71 29-JAN-00:15
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 6.70 0.00 17-JAN-19:00 1982.71 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 6.18 0.00 01-JAN-00:15 1489.40 29-JUN-19:30
EnergyTransfer:Zone:F4 N2 APARTMENT 12.91 0.00 05-AUG-11:00 1982.95 29-JAN-00:15
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 6.68 0.00 17-JAN-19:00 1982.95 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 6.24 0.00 01-JAN-00:15 1474.99 29-JUN-19:30
EnergyTransfer:Zone:F4 S1 APARTMENT 16.44 0.41 28-JUN-12:30 2646.86 21-JUL-14:15
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 4.54 0.00 16-JAN-12:30 1843.74 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 11.91 0.00 01-JAN-00:15 2646.86 21-JUL-14:15
EnergyTransfer:Zone:F4 S2 APARTMENT 16.52 0.30 16-JUL-14:30 2662.72 21-JUL-14:15
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 4.53 0.00 16-JAN-12:30 1843.85 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 11.99 0.00 01-JAN-00:15 2662.72 21-JUL-14:15
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 23.78 0.10 14-OCT-01:00 3601.52 28-JAN-24:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 12.93 0.00 23-JAN-12:30 3601.52 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 10.85 0.00 01-JAN-00:15 3319.06 11-JUL-17:30
EnergyTransfer:Zone:M NW APARTMENT 22.41 0.22 12-APR-09:30 3738.32 28-JAN-24:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 16.38 0.00 17-MAR-19:00 3738.32 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 6.03 0.00 01-JAN-00:15 2682.02 11-JUL-17:15
EnergyTransfer:Zone:M SE APARTMENT 24.87 0.04 12-FEB-18:30 3619.82 28-JAN-24:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 12.63 0.00 23-JAN-12:00 3619.82 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 12.24 0.00 01-JAN-00:15 3392.28 22-JUL-12:00
EnergyTransfer:Zone:M NE APARTMENT 23.06 0.03 21-AUG-14:15 3757.43 28-JAN-24:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 15.85 0.00 10-MAR-07:45 3757.43 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 7.21 0.00 01-JAN-00:15 2230.73 13-JUN-07:00
EnergyTransfer:Zone:M N1 APARTMENT 12.87 0.00 30-MAY-15:15 2071.72 29-JAN-00:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 6.53 0.00 17-JAN-19:00 2071.72 29-JAN-00:15
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 6.35 0.00 01-JAN-00:15 1524.44 29-JUN-19:30
EnergyTransfer:Zone:M N2 APARTMENT 12.92 0.01 08-JUN-13:30 2071.97 29-JAN-00:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 6.51 0.00 17-JAN-19:00 2071.97 29-JAN-00:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 6.41 0.00 01-JAN-00:15 1509.55 29-JUN-19:30
EnergyTransfer:Zone:M S1 APARTMENT 16.54 0.11 15-MAR-23:30 2682.73 21-JUL-14:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 4.42 0.00 16-JAN-12:30 1932.31 29-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 12.12 0.00 01-JAN-00:15 2682.73 21-JUL-14:15
EnergyTransfer:Zone:M S2 APARTMENT 16.62 0.20 24-MAR-06:45 2698.47 21-JUL-14:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 4.42 0.00 16-JAN-12:30 1932.49 29-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 12.20 0.00 01-JAN-00:15 2698.47 21-JUL-14:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 23.90 0.04 23-JAN-13:30 3806.75 28-JAN-24:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 13.74 0.00 23-JAN-12:45 3806.75 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 10.15 0.00 01-JAN-00:15 3288.62 11-JUL-17:30
EnergyTransfer:Zone:F6 NW APARTMENT 22.89 0.05 06-OCT-06:15 3945.43 28-JAN-24:00
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 17.34 0.00 18-MAR-11:15 3945.43 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 5.56 0.00 01-JAN-00:15 2635.07 11-JUL-17:15
EnergyTransfer:Zone:F6 SE APARTMENT 24.92 0.02 08-AUG-03:00 3826.00 28-JAN-24:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 13.42 0.00 23-JAN-12:15 3826.00 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 11.50 0.00 01-JAN-00:15 3359.61 22-JUL-12:00
EnergyTransfer:Zone:F6 NE APARTMENT 23.48 0.01 18-JUL-19:15 3965.43 28-JAN-24:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 16.78 0.00 10-MAR-08:00 3965.43 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 6.70 0.00 01-JAN-00:15 2190.18 13-JUN-07:00
EnergyTransfer:Zone:F6 N1 APARTMENT 13.07 0.02 21-AUG-18:30 2206.94 29-JAN-00:15
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 7.18 0.00 17-JAN-19:00 2206.94 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 5.89 0.00 01-JAN-00:15 1488.27 29-JUN-19:30
EnergyTransfer:Zone:F6 N2 APARTMENT 13.11 0.01 28-SEP-06:30 2207.20 29-JAN-00:15
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 7.16 0.00 17-JAN-19:00 2207.20 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 5.95 0.00 01-JAN-00:15 1472.75 29-JUN-19:30
EnergyTransfer:Zone:F6 S1 APARTMENT 16.28 0.14 11-OCT-09:00 2646.26 21-JUL-14:15
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 4.90 0.00 16-JAN-12:30 2065.18 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 11.39 0.00 01-JAN-00:15 2646.26 21-JUL-14:15
EnergyTransfer:Zone:F6 S2 APARTMENT 16.35 0.12 16-JUN-10:00 2662.23 21-JUL-14:15
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 4.89 0.00 16-JAN-12:30 2065.38 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 11.46 0.00 01-JAN-00:15 2662.23 21-JUL-14:15
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 23.99 0.03 08-OCT-08:00 3972.93 28-JAN-24:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 14.29 0.00 23-JAN-12:45 3972.93 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 9.71 0.00 01-JAN-00:15 3280.57 11-JUL-17:30
EnergyTransfer:Zone:F7 NW APARTMENT 23.22 0.05 18-APR-01:30 4111.87 28-JAN-24:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 17.94 0.00 18-MAR-11:30 4111.87 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 5.27 0.00 01-JAN-00:15 2615.67 11-JUL-17:15
EnergyTransfer:Zone:F7 SE APARTMENT 24.99 0.03 22-MAY-13:45 3992.91 28-JAN-24:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 13.95 0.00 23-JAN-12:15 3992.91 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 11.04 0.00 01-JAN-00:15 3350.94 22-JUL-12:00
EnergyTransfer:Zone:F7 NE APARTMENT 23.76 0.00 16-JUL-20:15 4132.56 28-JAN-24:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 17.38 0.00 10-MAR-08:00 4132.56 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 6.38 0.00 01-JAN-00:15 2172.92 13-JUN-07:00
EnergyTransfer:Zone:F7 N1 APARTMENT 13.18 0.00 18-JUL-12:45 2311.41 29-JAN-00:15
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 7.57 0.00 19-JAN-18:45 2311.41 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 5.62 0.00 01-JAN-00:15 1476.62 29-JUN-19:30
EnergyTransfer:Zone:F7 N2 APARTMENT 13.21 0.00 02-JUN-15:15 2311.69 29-JAN-00:15
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 7.55 0.00 19-JAN-18:45 2311.69 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 5.67 0.00 01-JAN-00:15 1461.10 29-JUN-19:30
EnergyTransfer:Zone:F7 S1 APARTMENT 16.13 0.05 02-NOV-21:30 2633.16 21-JUL-14:15
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 5.20 0.00 16-JAN-12:30 2169.49 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 10.93 0.00 01-JAN-00:15 2633.16 21-JUL-14:15
EnergyTransfer:Zone:F7 S2 APARTMENT 16.20 0.05 17-OCT-20:30 2649.26 21-JUL-14:15
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 5.20 0.00 16-JAN-12:30 2169.70 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 11.00 0.00 01-JAN-00:15 2649.26 21-JUL-14:15
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 24.22 0.09 24-SEP-23:45 4132.64 28-JAN-24:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 14.92 0.00 23-JAN-12:45 4132.64 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 9.30 0.00 01-JAN-00:15 3281.80 11-JUL-17:30
EnergyTransfer:Zone:F8 NW APARTMENT 23.68 0.05 24-SEP-12:00 4271.58 28-JAN-24:00
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 18.64 0.00 18-MAR-12:00 4271.58 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 5.04 0.00 01-JAN-00:15 2610.74 11-JUL-17:15
EnergyTransfer:Zone:F8 SE APARTMENT 25.20 0.11 09-OCT-07:45 4153.26 28-JAN-24:00
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 14.58 0.00 23-JAN-12:30 4153.26 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 10.63 0.00 01-JAN-00:15 3351.50 22-JUL-12:00
EnergyTransfer:Zone:F8 NE APARTMENT 24.19 0.04 16-AUG-12:00 4292.87 28-JAN-24:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 18.06 0.00 18-MAR-08:00 4292.87 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 6.13 0.00 01-JAN-00:15 2165.80 13-JUN-07:00
EnergyTransfer:Zone:F8 N1 APARTMENT 13.44 0.01 03-JUL-18:00 2415.70 29-JAN-00:15
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 8.07 0.00 19-JAN-18:45 2415.70 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 5.38 0.00 01-JAN-00:15 1476.96 29-JUN-19:30
EnergyTransfer:Zone:F8 N2 APARTMENT 13.48 0.01 05-JUN-15:00 2415.99 29-JAN-00:15
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 8.04 0.00 19-JAN-18:45 2415.99 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 5.43 0.00 01-JAN-00:15 1463.56 29-JUN-19:30
EnergyTransfer:Zone:F8 S1 APARTMENT 16.10 0.15 16-OCT-22:15 2630.02 21-JUL-14:15
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 5.61 0.00 16-JAN-12:45 2274.06 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 10.49 0.00 01-JAN-00:15 2630.02 21-JUL-14:15
EnergyTransfer:Zone:F8 S2 APARTMENT 16.17 0.13 23-JAN-19:15 2646.27 21-JUL-14:15
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 5.60 0.00 16-JAN-12:45 2274.30 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 10.57 0.00 01-JAN-00:15 2646.27 21-JUL-14:15
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 25.84 0.11 26-JUN-03:15 4409.96 28-JAN-24:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 17.14 0.00 09-FEB-11:30 4409.96 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 8.70 0.00 01-JAN-00:15 3353.73 11-JUL-17:30
EnergyTransfer:Zone:F9 NW APARTMENT 25.86 0.27 22-APR-13:45 4548.36 28-JAN-24:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 21.06 0.00 18-MAR-15:00 4548.36 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 4.79 0.00 01-JAN-00:15 2687.44 11-JUL-17:15
EnergyTransfer:Zone:F9 SE APARTMENT 26.75 0.03 08-AUG-03:30 4431.71 28-JAN-24:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 16.76 0.00 05-FEB-12:00 4431.71 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 9.98 0.00 01-JAN-00:15 3392.49 22-JUL-12:00
EnergyTransfer:Zone:F9 NE APARTMENT 26.28 0.03 11-AUG-09:30 4570.72 28-JAN-24:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 20.44 0.00 18-MAR-11:15 4570.72 28-JAN-24:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 5.84 0.00 01-JAN-00:15 2161.83 13-JUN-07:00
EnergyTransfer:Zone:F9 N1 APARTMENT 15.16 0.03 09-AUG-19:15 2633.21 29-JAN-00:15
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 10.12 0.00 21-JAN-21:15 2633.21 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 5.04 0.00 01-JAN-00:15 1543.10 29-JUN-19:30
EnergyTransfer:Zone:F9 N2 APARTMENT 15.19 0.03 09-JUN-18:45 2633.54 29-JAN-00:15
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 10.10 0.00 21-JAN-21:15 2633.54 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 5.09 0.00 01-JAN-00:15 1535.94 29-JUN-19:30
EnergyTransfer:Zone:F9 S1 APARTMENT 16.97 0.01 07-MAR-04:45 2665.28 21-JUL-14:15
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 7.30 0.00 16-JAN-13:00 2491.76 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 9.67 0.00 01-JAN-00:15 2665.28 21-JUL-14:15
EnergyTransfer:Zone:F9 S2 APARTMENT 17.04 0.07 26-JUL-16:00 2683.64 21-JUL-14:15
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 7.29 0.00 16-JAN-13:00 2492.05 29-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 9.75 0.00 01-JAN-00:15 2683.64 21-JUL-14:15
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 35.84 0.04 11-MAY-23:00 5391.40 28-JAN-24:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 28.13 0.00 09-FEB-11:30 5391.40 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 7.71 0.00 01-JAN-00:15 3912.66 20-JUN-16:15
EnergyTransfer:Zone:T NW APARTMENT 36.07 0.01 22-MAY-22:45 5481.27 28-JAN-24:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 31.92 0.00 18-MAR-12:30 5481.27 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 4.15 0.00 01-JAN-00:15 3181.46 11-JUL-17:15
EnergyTransfer:Zone:T SE APARTMENT 36.37 0.01 19-SEP-10:30 5414.07 28-JAN-24:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 27.66 0.00 09-FEB-11:15 5414.07 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 8.71 0.00 01-JAN-00:15 4003.67 22-JUL-12:00
EnergyTransfer:Zone:T NE APARTMENT 36.36 0.09 24-JUL-08:00 5504.17 28-JAN-24:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 31.26 0.00 18-MAR-11:30 5504.17 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 5.09 0.00 01-JAN-00:15 2484.57 22-JUL-12:00
EnergyTransfer:Zone:T N1 APARTMENT 25.07 0.00 17-AUG-18:30 3563.44 29-JAN-00:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 20.84 0.00 18-MAR-11:00 3563.44 29-JAN-00:15
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 4.23 0.00 01-JAN-00:15 1736.01 29-JUN-19:15
EnergyTransfer:Zone:T N2 APARTMENT 25.09 0.01 17-JUN-15:00 3563.92 29-JAN-00:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 20.80 0.00 18-MAR-11:00 3563.92 29-JAN-00:15
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 4.29 0.00 01-JAN-00:15 1701.04 29-JUN-19:15
EnergyTransfer:Zone:T S1 APARTMENT 25.40 0.02 25-JUN-23:15 3467.09 29-JAN-00:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 17.53 0.00 23-JAN-13:00 3467.09 29-JAN-00:15
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 7.88 0.00 01-JAN-00:15 3393.01 21-JUL-14:15
EnergyTransfer:Zone:T S2 APARTMENT 25.45 0.24 27-OCT-14:30 3467.55 29-JAN-00:15
Heating:EnergyTransfer:Zone:T S2 APARTMENT 17.51 0.00 23-JAN-13:00 3467.55 29-JAN-00:15
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 7.95 0.00 01-JAN-00:15 3406.55 21-JUL-14:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 2691.59 645.72 24-AUG-01:15 247456.84 29-JAN-08:00
WaterSystems:EnergyTransfer 1130.26 645.72 24-AUG-01:15 71339.79 01-JAN-07:15
sub cat:WaterSystems:EnergyTransfer 1130.26 645.72 24-AUG-01:15 71339.79 01-JAN-07:15
EnergyTransfer:HVAC 2568.96 0.00 07-MAY-18:45 338328.82 29-JAN-00:15
CoolingCoils:EnergyTransfer 466.56 0.00 01-JAN-00:15 204002.17 30-JUN-12:30
HeatingCoils:EnergyTransfer 2102.40 0.00 11-APR-17:15 338328.82 29-JAN-00:15
PlantLoopHeatingDemand:HVAC 1592.33 0.00 11-APR-17:15 198403.99 29-JAN-00:15
HeatingCoils:PlantLoopHeatingDemand 1592.33 0.00 11-APR-17:15 198403.99 29-JAN-00:15
Boilers:EnergyTransfer 1561.33 0.00 20-MAR-13:00 197417.90 29-JAN-00:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 17.177 -5.080 0.000 0.000 3.907 2.413 12.213 14.099 0.000 0.022 0.000 0.000 -20.551 0.000 -6.309 -17.891
G NW APARTMENT 20.170 -3.087 0.000 0.000 3.946 2.413 12.213 5.741 0.000 0.022 0.000 0.000 -21.893 0.000 -5.915 -13.610
OFFICE 15.751 -10.901 0.000 0.000 0.546 21.954 7.547 15.717 0.000 0.003 0.000 0.000 -20.259 0.000 -3.552 -26.806
G NE APARTMENT 19.677 -3.486 0.000 0.000 3.945 2.413 12.213 7.214 0.000 0.022 0.000 0.000 -21.398 0.000 -6.012 -14.588
G N1 APARTMENT 12.277 -3.269 0.000 0.000 3.955 2.413 12.213 2.234 0.000 0.021 0.000 0.000 -13.579 0.000 -4.344 -11.921
G N2 APARTMENT 12.251 -3.292 0.000 0.000 3.955 2.413 12.213 2.230 0.000 0.021 0.000 0.000 -13.581 0.000 -4.354 -11.856
G S1 APARTMENT 9.377 -5.465 0.000 0.000 3.903 2.413 12.213 10.950 0.000 0.020 0.000 0.000 -12.483 0.000 -4.793 -16.134
G S2 APARTMENT 9.223 -5.583 0.000 0.000 3.900 2.413 12.213 10.938 0.000 0.020 0.000 0.000 -12.491 0.000 -4.818 -15.816
F2 SW APARTMENT 13.726 -9.622 0.000 0.000 3.852 2.413 12.213 13.621 0.000 0.026 0.000 0.000 -21.343 0.000 -8.419 -6.467
F2 NW APARTMENT 17.189 -5.143 0.000 0.000 3.899 2.413 12.213 5.359 0.000 0.026 0.000 0.000 -22.630 0.000 -8.085 -5.241
F2 SE APARTMENT 12.916 -11.557 0.000 0.000 3.847 2.413 12.213 15.198 0.000 0.026 0.000 0.000 -21.006 0.000 -8.477 -5.573
F2 NE APARTMENT 16.624 -6.242 0.000 0.000 3.901 2.413 12.213 6.834 0.000 0.026 0.000 0.000 -22.117 0.000 -8.144 -5.507
F2 N1 APARTMENT 7.850 -5.233 0.000 0.000 3.907 2.413 12.213 2.022 0.000 0.024 0.000 0.000 -14.095 0.000 -5.868 -3.234
F2 N2 APARTMENT 7.824 -5.282 0.000 0.000 3.907 2.413 12.213 2.019 0.000 0.024 0.000 0.000 -14.097 0.000 -5.877 -3.144
F2 S1 APARTMENT 5.517 -10.100 0.000 0.000 3.841 2.413 12.213 10.648 0.000 0.024 0.000 0.000 -12.971 0.000 -6.315 -5.270
F2 S2 APARTMENT 5.480 -10.236 0.000 0.000 3.840 2.413 12.213 10.643 0.000 0.024 0.000 0.000 -12.975 0.000 -6.322 -5.080
F3 SW APARTMENT 12.857 -10.582 0.000 0.000 3.845 2.413 12.213 13.451 0.000 0.033 0.000 0.000 -21.591 0.000 -9.555 -3.084
F3 NW APARTMENT 16.284 -5.756 0.000 0.000 3.889 2.413 12.213 5.235 0.000 0.033 0.000 0.000 -22.892 0.000 -9.237 -2.181
F3 SE APARTMENT 12.494 -12.053 0.000 0.000 3.844 2.413 12.213 15.039 0.000 0.033 0.000 0.000 -21.204 0.000 -9.588 -3.190
F3 NE APARTMENT 15.743 -6.917 0.000 0.000 3.892 2.413 12.213 6.709 0.000 0.033 0.000 0.000 -22.371 0.000 -9.284 -2.432
F3 N1 APARTMENT 6.776 -5.917 0.000 0.000 3.893 2.413 12.213 1.957 0.000 0.030 0.000 0.000 -14.275 0.000 -6.663 -0.426
F3 N2 APARTMENT 6.754 -5.973 0.000 0.000 3.893 2.413 12.213 1.954 0.000 0.030 0.000 0.000 -14.277 0.000 -6.670 -0.336
F3 S1 APARTMENT 4.620 -11.505 0.000 0.000 3.830 2.413 12.213 10.531 0.000 0.031 0.000 0.000 -13.135 0.000 -7.084 -1.914
F3 S2 APARTMENT 4.610 -11.603 0.000 0.000 3.829 2.413 12.213 10.528 0.000 0.031 0.000 0.000 -13.137 0.000 -7.088 -1.796
F4 SW APARTMENT 12.944 -10.789 0.000 0.000 3.845 2.413 12.213 13.350 0.000 0.035 0.000 0.000 -21.722 0.000 -10.151 -2.138
F4 NW APARTMENT 16.421 -5.942 0.000 0.000 3.887 2.413 12.213 5.169 0.000 0.035 0.000 0.000 -23.039 0.000 -9.854 -1.302
F4 SE APARTMENT 12.636 -12.188 0.000 0.000 3.844 2.413 12.213 14.936 0.000 0.035 0.000 0.000 -21.322 0.000 -10.176 -2.390
F4 NE APARTMENT 15.884 -7.115 0.000 0.000 3.890 2.413 12.213 6.641 0.000 0.035 0.000 0.000 -22.513 0.000 -9.892 -1.555
F4 N1 APARTMENT 6.698 -6.179 0.000 0.000 3.888 2.413 12.213 1.924 0.000 0.031 0.400 0.000 -14.376 0.000 -7.012 -0.000
F4 N2 APARTMENT 6.677 -6.237 0.000 0.000 3.888 2.413 12.213 1.921 0.000 0.031 0.491 0.000 -14.378 0.000 -7.018 -0.000
F4 S1 APARTMENT 4.536 -11.906 0.000 0.000 3.827 2.413 12.213 10.462 0.000 0.032 0.001 0.000 -13.219 0.000 -7.400 -0.960
F4 S2 APARTMENT 4.528 -11.988 0.000 0.000 3.827 2.413 12.213 10.460 0.000 0.032 0.002 0.000 -13.221 0.000 -7.403 -0.861
M SW APARTMENT 12.928 -10.855 0.000 0.000 3.845 2.413 12.213 13.270 0.000 0.036 0.000 0.000 -21.833 0.000 -10.857 -1.160
M NW APARTMENT 16.384 -6.030 0.000 0.000 3.886 2.413 12.213 5.121 0.000 0.037 0.000 0.000 -23.162 0.000 -10.549 -0.312
M SE APARTMENT 12.629 -12.241 0.000 0.000 3.844 2.413 12.213 14.851 0.000 0.036 0.000 0.000 -21.426 0.000 -10.882 -1.435
M NE APARTMENT 15.848 -7.207 0.000 0.000 3.889 2.413 12.213 6.589 0.000 0.036 0.000 0.000 -22.632 0.000 -10.586 -0.564
M N1 APARTMENT 6.525 -6.350 0.000 0.000 3.886 2.413 12.213 1.900 0.000 0.032 1.313 0.000 -14.458 0.000 -7.474 -0.000
M N2 APARTMENT 6.507 -6.411 0.000 0.000 3.885 2.413 12.213 1.898 0.000 0.032 1.403 0.000 -14.460 0.000 -7.480 -0.000
M S1 APARTMENT 4.421 -12.120 0.000 0.000 3.827 2.413 12.213 10.408 0.000 0.034 0.000 0.000 -13.288 0.000 -7.869 -0.037
M S2 APARTMENT 4.417 -12.204 0.000 0.000 3.826 2.413 12.213 10.405 0.000 0.034 0.059 0.000 -13.290 0.000 -7.873 -0.000
F6 SW APARTMENT 13.744 -10.154 0.000 0.000 3.850 2.413 12.213 13.230 0.000 0.037 0.000 0.000 -21.865 0.000 -11.441 -2.026
F6 NW APARTMENT 17.335 -5.558 0.000 0.000 3.892 2.413 12.213 5.111 0.000 0.038 0.000 0.000 -23.200 0.000 -11.094 -1.150
F6 SE APARTMENT 13.419 -11.503 0.000 0.000 3.849 2.413 12.213 14.808 0.000 0.037 0.000 0.000 -21.457 0.000 -11.470 -2.309
F6 NE APARTMENT 16.782 -6.698 0.000 0.000 3.895 2.413 12.213 6.575 0.000 0.037 0.000 0.000 -22.667 0.000 -11.138 -1.413
F6 N1 APARTMENT 7.175 -5.892 0.000 0.000 3.892 2.413 12.213 1.899 0.000 0.033 0.557 0.000 -14.480 0.000 -7.812 -0.001
F6 N2 APARTMENT 7.155 -5.951 0.000 0.000 3.892 2.413 12.213 1.896 0.000 0.033 0.648 0.000 -14.482 0.000 -7.818 -0.000
F6 S1 APARTMENT 4.897 -11.385 0.000 0.000 3.832 2.413 12.213 10.379 0.000 0.035 0.000 0.000 -13.306 0.000 -8.244 -0.833
F6 S2 APARTMENT 4.889 -11.464 0.000 0.000 3.831 2.413 12.213 10.376 0.000 0.035 0.000 0.000 -13.307 0.000 -8.249 -0.737
F7 SW APARTMENT 14.285 -9.706 0.000 0.000 3.854 2.413 12.213 13.191 0.000 0.038 0.000 0.000 -21.906 0.000 -11.955 -2.426
F7 NW APARTMENT 17.944 -5.272 0.000 0.000 3.897 2.413 12.213 5.098 0.000 0.038 0.000 0.000 -23.243 0.000 -11.579 -1.509
F7 SE APARTMENT 13.951 -11.038 0.000 0.000 3.853 2.413 12.213 14.765 0.000 0.038 0.000 0.000 -21.495 0.000 -11.986 -2.713
F7 NE APARTMENT 17.375 -6.384 0.000 0.000 3.900 2.413 12.213 6.559 0.000 0.038 0.000 0.000 -22.710 0.000 -11.627 -1.778
F7 N1 APARTMENT 7.569 -5.615 0.000 0.000 3.898 2.413 12.213 1.896 0.000 0.034 0.212 0.000 -14.505 0.000 -8.113 -0.000
F7 N2 APARTMENT 7.545 -5.669 0.000 0.000 3.897 2.413 12.213 1.893 0.000 0.033 0.302 0.000 -14.507 0.000 -8.120 -0.000
F7 S1 APARTMENT 5.204 -10.927 0.000 0.000 3.836 2.413 12.213 10.352 0.000 0.035 0.000 0.000 -13.328 0.000 -8.575 -1.224
F7 S2 APARTMENT 5.196 -11.004 0.000 0.000 3.836 2.413 12.213 10.349 0.000 0.035 0.000 0.000 -13.329 0.000 -8.579 -1.129
F8 SW APARTMENT 14.918 -9.305 0.000 0.000 3.857 2.413 12.213 13.158 0.000 0.039 0.000 0.000 -21.937 0.000 -12.429 -2.927
F8 NW APARTMENT 18.638 -5.043 0.000 0.000 3.902 2.413 12.213 5.088 0.000 0.039 0.000 0.000 -23.278 0.000 -12.026 -1.946
F8 SE APARTMENT 14.576 -10.626 0.000 0.000 3.857 2.413 12.213 14.728 0.000 0.039 0.000 0.000 -21.524 0.000 -12.464 -3.211
F8 NE APARTMENT 18.060 -6.133 0.000 0.000 3.905 2.413 12.213 6.546 0.000 0.039 0.000 0.000 -22.743 0.000 -12.078 -2.221
F8 N1 APARTMENT 8.066 -5.377 0.000 0.000 3.903 2.413 12.213 1.893 0.000 0.034 0.000 0.000 -14.523 0.000 -8.395 -0.226
F8 N2 APARTMENT 8.043 -5.432 0.000 0.000 3.903 2.413 12.213 1.890 0.000 0.034 0.000 0.000 -14.525 0.000 -8.403 -0.135
F8 S1 APARTMENT 5.609 -10.489 0.000 0.000 3.840 2.413 12.213 10.329 0.000 0.036 0.000 0.000 -13.343 0.000 -8.884 -1.725
F8 S2 APARTMENT 5.600 -10.566 0.000 0.000 3.840 2.413 12.213 10.326 0.000 0.036 0.000 0.000 -13.345 0.000 -8.889 -1.628
F9 SW APARTMENT 17.141 -8.697 0.000 0.000 3.864 2.413 12.213 13.149 0.000 0.040 0.000 0.000 -21.902 0.000 -12.854 -5.367
F9 NW APARTMENT 21.063 -4.792 0.000 0.000 3.908 2.413 12.213 5.091 0.000 0.040 0.000 0.000 -23.248 0.000 -12.428 -4.260
F9 SE APARTMENT 16.761 -9.985 0.000 0.000 3.863 2.413 12.213 14.719 0.000 0.040 0.000 0.000 -21.492 0.000 -12.897 -5.636
F9 NE APARTMENT 20.442 -5.841 0.000 0.000 3.911 2.413 12.213 6.548 0.000 0.040 0.000 0.000 -22.713 0.000 -12.484 -4.529
F9 N1 APARTMENT 10.120 -5.040 0.000 0.000 3.910 2.413 12.213 1.897 0.000 0.035 0.000 0.000 -14.496 0.000 -8.650 -2.403
F9 N2 APARTMENT 10.096 -5.089 0.000 0.000 3.910 2.413 12.213 1.894 0.000 0.035 0.000 0.000 -14.498 0.000 -8.658 -2.317
F9 S1 APARTMENT 7.301 -9.666 0.000 0.000 3.848 2.413 12.213 10.324 0.000 0.037 0.000 0.000 -13.315 0.000 -9.162 -3.993
F9 S2 APARTMENT 7.293 -9.748 0.000 0.000 3.848 2.413 12.213 10.321 0.000 0.037 0.000 0.000 -13.316 0.000 -9.168 -3.892
T SW APARTMENT 28.127 -7.713 0.000 0.000 3.898 2.413 12.213 13.046 0.000 0.040 0.000 0.000 -21.237 0.000 -13.174 -17.612
T NW APARTMENT 31.924 -4.150 0.000 0.000 3.931 2.413 12.213 5.027 0.000 0.041 0.000 0.000 -22.647 0.000 -12.786 -15.965
T SE APARTMENT 27.659 -8.707 0.000 0.000 3.898 2.413 12.213 14.656 0.000 0.040 0.000 0.000 -20.871 0.000 -13.192 -18.108
T NE APARTMENT 31.261 -5.095 0.000 0.000 3.937 2.413 12.213 6.515 0.000 0.041 0.000 0.000 -22.135 0.000 -12.792 -16.358
T N1 APARTMENT 20.835 -4.235 0.000 0.000 3.936 2.413 12.213 1.893 0.000 0.032 0.000 0.000 -14.092 0.000 -8.853 -14.142
T N2 APARTMENT 20.801 -4.286 0.000 0.000 3.936 2.413 12.213 1.889 0.000 0.031 0.000 0.000 -14.092 0.000 -8.859 -14.046
T S1 APARTMENT 17.528 -7.876 0.000 0.000 3.883 2.413 12.213 10.274 0.000 0.037 0.000 0.000 -12.937 0.000 -9.369 -16.167
T S2 APARTMENT 17.509 -7.945 0.000 0.000 3.883 2.413 12.213 10.269 0.000 0.037 0.000 0.000 -12.937 0.000 -9.374 -16.068
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 3.280 0.000 0.020 73.585 0.000 -4.615 0.000 -90.798 -0.000
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.295 0.000 0.000 0.000 0.000 -2.760 0.000 -0.921 -16.143
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.260 0.000 0.000 0.000 0.000 -2.852 0.000 -1.118 -15.819
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.242 0.000 0.000 0.000 0.000 -2.889 0.000 -1.260 -15.622
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 1.221 0.000 0.000 0.000 0.000 -2.938 0.000 -1.411 -33.931
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.229 0.000 0.000 0.000 0.000 -2.910 0.000 -1.463 -15.386
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.230 0.000 0.000 0.000 0.000 -2.904 0.000 -1.537 -15.319
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.228 0.000 0.000 0.000 0.000 -2.902 0.000 -1.606 -15.250
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.230 0.000 0.000 0.000 0.000 -2.884 0.000 -1.663 -15.213
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 1.209 0.000 0.000 0.000 0.000 -2.781 0.000 -1.722 -23.172
Total Facility 1016.986 -625.702 0.000 0.000 307.022 416.414 980.287 664.449 0.000 2.645 78.974 0.000 -1460.059 0.000 -824.815 -556.199


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-AUG-16:15 0.00 -2406.72 0.00 0.00 84.76 144.04 588.62 3115.34 0.00 134.71 0.00 0.00 0.00 0.00 0.00 -1660.74
G NW APARTMENT 11-JUL-17:30 0.00 -1877.50 0.00 0.00 141.57 194.45 588.62 2517.41 0.00 205.45 0.00 0.00 0.00 0.00 0.00 -1770.00
OFFICE 10-AUG-13:30 0.00 -3271.26 0.00 0.00 65.20 1622.33 544.91 3711.83 0.00 0.00 0.00 0.00 0.00 0.00 -20.23 -2652.78
G NE APARTMENT 11-JUL-05:30 0.00 -1499.52 0.00 0.00 163.00 100.83 317.85 3231.18 0.00 0.00 0.00 0.00 0.00 0.00 -50.05 -2263.29
G N1 APARTMENT 11-JUL-17:30 0.00 -1078.88 0.00 0.00 141.81 194.45 588.62 359.03 0.00 208.96 0.00 0.00 0.00 0.00 0.00 -413.99
G N2 APARTMENT 11-JUL-17:30 0.00 -1074.34 0.00 0.00 141.81 194.45 588.62 359.08 0.00 208.96 0.00 0.00 0.00 0.00 0.00 -418.57
G S1 APARTMENT 21-JUL-14:15 0.00 -1896.94 0.00 0.00 40.75 50.41 400.26 2831.96 0.00 196.09 0.00 0.00 0.00 0.00 0.00 -1622.54
G S2 APARTMENT 21-JUL-14:15 0.00 -1943.56 0.00 0.00 40.75 50.41 400.26 2831.06 0.00 196.09 0.00 0.00 0.00 0.00 0.00 -1575.01
F2 SW APARTMENT 11-AUG-16:15 0.00 -3198.78 0.00 0.00 84.76 144.04 588.62 3071.03 0.00 172.65 0.00 0.00 0.00 0.00 0.00 -862.31
F2 NW APARTMENT 11-JUL-17:30 0.00 -2605.87 0.00 0.00 141.81 194.45 588.62 2481.75 0.00 271.82 0.00 0.00 0.00 0.00 0.00 -1072.58
F2 SE APARTMENT 21-JUL-14:15 0.00 -3301.89 0.00 0.00 40.75 50.41 400.26 3117.28 0.00 218.12 0.00 0.00 0.00 0.00 0.00 -524.94
F2 NE APARTMENT 13-JUN-06:40 0.00 -2081.16 0.00 0.00 138.55 93.62 382.60 2695.40 0.00 0.00 0.00 0.00 0.00 0.00 -11.15 -1217.87
F2 N1 APARTMENT 11-JUL-16:15 0.00 -1406.91 0.00 0.00 84.76 144.04 588.62 426.27 0.00 244.88 0.00 0.00 0.00 0.00 0.00 -81.65
F2 N2 APARTMENT 11-JUL-16:15 0.00 -1391.83 0.00 0.00 84.76 144.04 588.62 426.06 0.00 242.43 0.00 0.00 0.00 0.00 0.00 -94.07
F2 S1 APARTMENT 21-JUL-14:15 0.00 -2553.65 0.00 0.00 40.75 50.41 400.26 2811.91 0.00 212.91 0.00 0.00 0.00 0.00 0.00 -962.59
F2 S2 APARTMENT 21-JUL-14:15 0.00 -2576.56 0.00 0.00 40.75 50.41 400.26 2811.56 0.00 212.91 0.00 0.00 0.00 0.00 0.00 -939.33
F3 SW APARTMENT 11-AUG-16:15 0.00 -3254.86 0.00 0.00 84.76 144.04 588.62 3051.67 0.00 194.90 0.00 0.00 0.00 0.00 0.00 -809.13
F3 NW APARTMENT 11-JUL-17:30 0.00 -2646.71 0.00 0.00 141.61 194.45 588.62 2467.43 0.00 299.20 0.00 0.00 0.00 0.00 0.00 -1044.60
F3 SE APARTMENT 22-JUL-12:00 0.00 -3339.64 0.00 0.00 40.75 28.81 406.15 3444.26 0.00 280.38 0.00 0.00 0.00 0.00 0.00 -860.69
F3 NE APARTMENT 13-JUN-06:40 0.00 -2166.13 0.00 0.00 138.55 93.62 382.60 2691.76 0.00 0.00 0.00 0.00 0.00 0.00 -13.22 -1127.18
F3 N1 APARTMENT 29-JUN-19:45 0.00 -1464.27 0.00 0.00 141.81 230.46 523.87 542.14 0.00 69.30 0.00 0.00 0.00 0.00 0.00 -43.31
F3 N2 APARTMENT 29-JUN-19:30 0.00 -1456.18 0.00 0.00 141.81 230.46 523.87 551.68 0.00 76.86 0.00 0.00 0.00 0.00 0.00 -68.50
F3 S1 APARTMENT 21-JUL-14:15 0.00 -2624.92 0.00 0.00 40.75 50.41 400.26 2801.34 0.00 223.89 0.00 0.00 0.00 0.00 0.00 -891.72
F3 S2 APARTMENT 21-JUL-14:15 0.00 -2641.54 0.00 0.00 40.75 50.41 400.26 2801.07 0.00 223.89 0.00 0.00 0.00 0.00 0.00 -874.84
F4 SW APARTMENT 11-JUL-17:30 0.00 -3277.14 0.00 0.00 141.81 194.45 588.62 2671.05 0.00 288.56 0.00 0.00 0.00 0.00 0.00 -607.35
F4 NW APARTMENT 11-JUL-17:30 0.00 -2654.89 0.00 0.00 141.44 194.45 588.62 2457.88 0.00 318.50 0.00 0.00 0.00 0.00 0.00 -1046.00
F4 SE APARTMENT 22-JUL-12:00 0.00 -3355.42 0.00 0.00 40.75 28.81 406.15 3431.79 0.00 294.09 0.00 0.00 0.00 0.00 0.00 -846.16
F4 NE APARTMENT 13-JUN-07:00 0.00 -2202.67 0.00 0.00 138.55 93.62 382.60 2634.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1046.95
F4 N1 APARTMENT 29-JUN-19:30 0.00 -1489.71 0.00 0.00 141.80 230.46 523.87 548.37 0.00 80.59 0.00 0.00 0.00 0.00 0.00 -35.39
F4 N2 APARTMENT 29-JUN-19:30 0.00 -1475.29 0.00 0.00 141.80 230.46 523.87 548.51 0.00 80.14 0.00 0.00 0.00 0.00 0.00 -49.50
F4 S1 APARTMENT 21-JUL-14:15 0.00 -2646.42 0.00 0.00 40.75 50.41 400.26 2793.49 0.00 232.22 0.00 0.00 0.00 0.00 0.00 -870.71
F4 S2 APARTMENT 21-JUL-14:15 0.00 -2662.28 0.00 0.00 40.75 50.41 400.26 2793.24 0.00 232.22 0.00 0.00 0.00 0.00 0.00 -854.61
M SW APARTMENT 11-JUL-17:30 0.00 -3318.55 0.00 0.00 141.81 194.45 588.62 2662.04 0.00 304.84 0.00 0.00 0.00 0.00 0.00 -573.20
M NW APARTMENT 11-JUL-17:30 0.00 -2681.46 0.00 0.00 141.32 194.45 588.62 2449.81 0.00 333.17 0.00 0.00 0.00 0.00 0.00 -1025.92
M SE APARTMENT 22-JUL-12:00 0.00 -3391.58 0.00 0.00 40.75 28.81 406.15 3420.88 0.00 305.19 0.00 0.00 0.00 0.00 0.00 -810.19
M NE APARTMENT 13-JUN-07:00 0.00 -2231.43 0.00 0.00 138.55 93.62 382.60 2633.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1016.86
M N1 APARTMENT 29-JUN-19:30 0.00 -1524.77 0.00 0.00 141.80 230.46 523.87 545.51 0.00 83.22 0.00 0.00 0.00 0.00 0.00 -0.10
M N2 APARTMENT 29-JUN-19:30 0.00 -1509.87 0.00 0.00 141.80 230.46 523.87 545.65 0.00 82.71 0.00 0.00 0.00 0.00 0.00 -14.62
M S1 APARTMENT 21-JUL-14:15 0.00 -2682.29 0.00 0.00 40.75 50.41 400.26 2786.59 0.00 238.90 0.00 0.00 0.00 0.00 0.00 -834.63
M S2 APARTMENT 21-JUL-14:15 0.00 -2698.03 0.00 0.00 40.75 50.41 400.26 2786.35 0.00 238.90 0.00 0.00 0.00 0.00 0.00 -818.64
F6 SW APARTMENT 11-JUL-17:30 0.00 -3288.10 0.00 0.00 141.81 194.45 588.62 2656.31 0.00 318.10 0.00 0.00 0.00 0.00 0.00 -611.18
F6 NW APARTMENT 11-JUL-17:15 0.00 -2634.49 0.00 0.00 141.78 194.45 588.62 2379.22 0.00 364.49 0.00 0.00 0.00 0.00 0.00 -1034.06
F6 SE APARTMENT 22-JUL-12:00 0.00 -3358.90 0.00 0.00 40.75 28.81 406.15 3413.09 0.00 314.46 0.00 0.00 0.00 0.00 0.00 -844.35
F6 NE APARTMENT 13-JUN-07:00 0.00 -2190.86 0.00 0.00 138.55 93.62 382.60 2634.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1058.00
F6 N1 APARTMENT 29-JUN-19:30 0.00 -1488.60 0.00 0.00 141.80 230.46 523.87 544.26 0.00 84.98 0.00 0.00 0.00 0.00 0.00 -36.77
F6 N2 APARTMENT 29-JUN-19:15 0.00 -1473.19 0.00 0.00 141.80 230.46 523.87 489.71 0.00 89.29 0.00 0.00 0.00 0.00 0.00 -1.94
F6 S1 APARTMENT 21-JUL-14:15 0.00 -2645.85 0.00 0.00 40.75 50.41 400.26 2781.65 0.00 244.43 0.00 0.00 0.00 0.00 0.00 -871.66
F6 S2 APARTMENT 21-JUL-14:15 0.00 -2661.81 0.00 0.00 40.75 50.41 400.26 2781.39 0.00 244.43 0.00 0.00 0.00 0.00 0.00 -855.43
F7 SW APARTMENT 11-JUL-17:30 0.00 -3280.05 0.00 0.00 141.81 194.45 588.62 2650.81 0.00 329.14 0.00 0.00 0.00 0.00 0.00 -624.78
F7 NW APARTMENT 11-JUL-17:15 0.00 -2615.08 0.00 0.00 141.68 194.45 588.62 2374.45 0.00 373.97 0.00 0.00 0.00 0.00 0.00 -1058.08
F7 SE APARTMENT 22-JUL-12:00 0.00 -3350.23 0.00 0.00 40.75 28.81 406.15 3405.65 0.00 322.36 0.00 0.00 0.00 0.00 0.00 -853.49
F7 NE APARTMENT 13-JUN-07:00 0.00 -2173.59 0.00 0.00 138.55 93.62 382.60 2634.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1075.20
F7 N1 APARTMENT 29-JUN-19:30 0.00 -1476.96 0.00 0.00 141.80 230.46 523.87 542.79 0.00 86.31 0.00 0.00 0.00 0.00 0.00 -48.28
F7 N2 APARTMENT 29-JUN-19:30 0.00 -1461.43 0.00 0.00 141.80 230.46 523.87 542.92 0.00 85.70 0.00 0.00 0.00 0.00 0.00 -63.32
F7 S1 APARTMENT 21-JUL-14:15 0.00 -2632.76 0.00 0.00 40.75 50.41 400.26 2776.89 0.00 249.08 0.00 0.00 0.00 0.00 0.00 -884.63
F7 S2 APARTMENT 21-JUL-14:15 0.00 -2648.85 0.00 0.00 40.75 50.41 400.26 2776.63 0.00 249.08 0.00 0.00 0.00 0.00 0.00 -868.28
F8 SW APARTMENT 11-JUL-17:30 0.00 -3281.26 0.00 0.00 141.81 194.45 588.62 2645.72 0.00 338.43 0.00 0.00 0.00 0.00 0.00 -627.76
F8 NW APARTMENT 11-JUL-17:15 0.00 -2610.15 0.00 0.00 141.62 194.45 588.62 2369.95 0.00 382.36 0.00 0.00 0.00 0.00 0.00 -1066.86
F8 SE APARTMENT 22-JUL-12:00 0.00 -3350.79 0.00 0.00 40.75 28.81 406.15 3398.73 0.00 329.17 0.00 0.00 0.00 0.00 0.00 -852.81
F8 NE APARTMENT 13-JUN-07:00 0.00 -2166.47 0.00 0.00 138.55 93.62 382.60 2633.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1081.96
F8 N1 APARTMENT 29-JUN-19:30 0.00 -1477.30 0.00 0.00 141.80 230.46 523.87 541.21 0.00 87.18 0.00 0.00 0.00 0.00 0.00 -47.22
F8 N2 APARTMENT 29-JUN-19:30 0.00 -1463.91 0.00 0.00 141.80 230.46 523.87 541.34 0.00 86.71 0.00 0.00 0.00 0.00 0.00 -60.28
F8 S1 APARTMENT 21-JUL-14:15 0.00 -2629.62 0.00 0.00 40.75 50.41 400.26 2772.42 0.00 253.02 0.00 0.00 0.00 0.00 0.00 -887.24
F8 S2 APARTMENT 21-JUL-14:15 0.00 -2645.87 0.00 0.00 40.75 50.41 400.26 2772.16 0.00 253.02 0.00 0.00 0.00 0.00 0.00 -870.73
F9 SW APARTMENT 11-JUL-17:30 0.00 -3353.18 0.00 0.00 141.81 194.45 588.62 2639.01 0.00 346.32 0.00 0.00 0.00 0.00 0.00 -557.03
F9 NW APARTMENT 11-JUL-17:15 0.00 -2686.83 0.00 0.00 141.70 194.45 588.62 2364.06 0.00 395.41 0.00 0.00 0.00 0.00 0.00 -997.41
F9 SE APARTMENT 22-JUL-12:00 0.00 -3391.77 0.00 0.00 40.75 28.81 406.15 3391.26 0.00 335.08 0.00 0.00 0.00 0.00 0.00 -810.27
F9 NE APARTMENT 13-JUN-07:00 0.00 -2162.49 0.00 0.00 138.55 93.62 382.60 2633.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1085.51
F9 N1 APARTMENT 29-JUN-19:30 0.00 -1543.46 0.00 0.00 141.80 230.46 523.87 538.18 0.00 87.61 21.54 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 29-JUN-19:30 0.00 -1536.30 0.00 0.00 141.80 230.46 523.87 538.28 0.00 87.55 14.34 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 21-JUL-14:15 0.00 -2664.89 0.00 0.00 40.75 50.41 400.26 2767.66 0.00 256.38 0.00 0.00 0.00 0.00 0.00 -850.58
F9 S2 APARTMENT 21-JUL-14:15 0.00 -2683.24 0.00 0.00 40.75 50.41 400.26 2767.37 0.00 256.38 0.00 0.00 0.00 0.00 0.00 -831.93
T SW APARTMENT 20-JUN-16:15 0.00 -3912.38 0.00 0.00 84.76 144.04 588.62 3153.58 0.00 186.32 0.00 0.00 0.00 0.00 0.00 -244.94
T NW APARTMENT 11-JUL-17:15 0.00 -3180.73 0.00 0.00 141.81 194.45 588.62 2330.80 0.00 411.72 0.00 0.00 0.00 0.00 0.00 -486.66
T SE APARTMENT 22-JUL-12:00 0.00 -4002.88 0.00 0.00 40.75 28.81 406.15 3346.69 0.00 340.27 0.00 0.00 0.00 0.00 0.00 -159.79
T NE APARTMENT 22-JUL-12:00 0.00 -2483.95 0.00 0.00 40.52 28.81 406.15 1091.84 0.00 320.07 596.57 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-JUN-19:15 0.00 -1736.55 0.00 0.00 140.98 230.46 523.87 474.46 0.00 80.79 285.98 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-19:15 0.00 -1701.57 0.00 0.00 140.70 230.46 523.87 474.44 0.00 77.45 254.65 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 21-JUL-14:15 0.00 -3392.52 0.00 0.00 40.75 50.41 400.26 2740.39 0.00 259.26 0.00 0.00 0.00 0.00 0.00 -98.55
T S2 APARTMENT 21-JUL-14:15 0.00 -3406.06 0.00 0.00 40.75 50.41 400.26 2740.13 0.00 259.26 0.00 0.00 0.00 0.00 0.00 -84.75
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-16:15 0.00 -180580.13 0.00 0.00 6690.15 18221.75 47207.76 114057.36 0.00 23177.74 0.00 0.00 0.00 0.00 -161.80 -28612.82


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-JAN-00:15 2747.89 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1745.11 0.00 -1118.78 -352.95
G NW APARTMENT 29-JAN-00:15 2811.93 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1755.72 0.00 -1118.79 -406.35
OFFICE 28-JAN-24:00 2888.38 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 0.00 0.00 -1757.31 0.00 -1148.06 -491.27
G NE APARTMENT 29-JAN-00:15 2819.66 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1765.40 0.00 -1118.80 -404.40
G N1 APARTMENT 12-JAN-08:30 1860.01 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1197.36 0.00 0.00 -1168.31
G N2 APARTMENT 12-JAN-08:30 1859.92 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1197.36 0.00 0.00 -1168.23
G S1 APARTMENT 12-JAN-08:30 1831.76 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1200.51 0.00 0.00 -1136.92
G S2 APARTMENT 12-JAN-08:30 1822.04 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1200.62 0.00 0.00 -1127.09
F2 SW APARTMENT 29-JAN-00:15 3036.06 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1802.91 0.00 -1608.46 -93.64
F2 NW APARTMENT 29-JAN-00:15 3161.17 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1823.43 0.00 -1608.47 -198.22
F2 SE APARTMENT 29-JAN-00:15 3042.75 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1820.20 0.00 -1608.46 -83.05
F2 NE APARTMENT 29-JAN-00:15 3174.87 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1840.41 0.00 -1608.48 -194.92
F2 N1 APARTMENT 29-JAN-00:30 1797.16 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1120.25 0.00 -944.80 -201.05
F2 N2 APARTMENT 29-JAN-00:30 1797.34 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1120.25 0.00 -944.80 -201.23
F2 S1 APARTMENT 29-JAN-00:30 1671.94 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1096.65 0.00 -944.78 -99.46
F2 S2 APARTMENT 29-JAN-00:30 1671.32 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1096.66 0.00 -944.78 -98.83
F3 SW APARTMENT 29-JAN-00:15 3223.22 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 38.84 0.00 -1826.25 0.00 -1904.77 0.00
F3 NW APARTMENT 29-JAN-00:15 3353.93 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1851.68 0.00 -1904.78 -66.42
F3 SE APARTMENT 29-JAN-00:15 3236.56 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 46.03 0.00 -1846.78 0.00 -1904.77 0.00
F3 NE APARTMENT 29-JAN-00:15 3370.12 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1872.00 0.00 -1904.79 -62.27
F3 N1 APARTMENT 29-JAN-00:30 1864.13 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1140.08 0.00 -1118.85 -74.14
F3 N2 APARTMENT 29-JAN-00:30 1864.34 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1140.08 0.00 -1118.85 -74.36
F3 S1 APARTMENT 29-JAN-00:30 1731.01 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 30.20 0.00 -1111.34 0.00 -1118.83 0.00
F3 S2 APARTMENT 29-JAN-00:30 1730.90 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 30.32 0.00 -1111.34 0.00 -1118.83 0.00
F4 SW APARTMENT 29-JAN-00:15 3433.75 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 66.93 0.00 -1840.11 0.00 -2129.52 0.00
F4 NW APARTMENT 28-JAN-24:00 3567.86 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1870.21 0.00 -2185.29 -79.44
F4 SE APARTMENT 29-JAN-00:15 3450.49 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 72.73 0.00 -1862.64 0.00 -2129.52 0.00
F4 NE APARTMENT 28-JAN-24:00 3585.80 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1893.11 0.00 -2185.30 -74.46
F4 N1 APARTMENT 29-JAN-00:15 1982.31 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1154.73 0.00 -1284.50 -12.03
F4 N2 APARTMENT 29-JAN-00:15 1982.54 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1154.73 0.00 -1284.50 -12.26
F4 S1 APARTMENT 29-JAN-00:15 1843.43 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 94.62 0.00 -1122.53 0.00 -1284.47 0.00
F4 S2 APARTMENT 29-JAN-00:15 1843.54 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 94.50 0.00 -1122.52 0.00 -1284.47 0.00
M SW APARTMENT 28-JAN-24:00 3600.92 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 59.40 0.00 -1851.97 0.00 -2375.43 0.00
M NW APARTMENT 28-JAN-24:00 3737.62 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1883.22 0.00 -2375.45 -46.03
M SE APARTMENT 28-JAN-24:00 3619.21 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 65.60 0.00 -1876.45 0.00 -2375.43 0.00
M NE APARTMENT 28-JAN-24:00 3756.67 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1907.54 0.00 -2375.46 -40.74
M N1 APARTMENT 29-JAN-00:15 2071.30 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 19.81 0.00 -1163.79 0.00 -1396.27 0.00
M N2 APARTMENT 29-JAN-00:15 2071.55 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 19.56 0.00 -1163.79 0.00 -1396.27 0.00
M S1 APARTMENT 29-JAN-00:15 1931.99 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 124.66 0.00 -1129.36 0.00 -1396.25 0.00
M S2 APARTMENT 29-JAN-00:15 1932.17 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 124.48 0.00 -1129.36 0.00 -1396.25 0.00
F6 SW APARTMENT 28-JAN-24:00 3806.12 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 25.00 0.00 -1858.85 0.00 -2539.34 0.00
F6 NW APARTMENT 28-JAN-24:00 3944.70 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1891.74 0.00 -2539.36 -80.67
F6 SE APARTMENT 28-JAN-24:00 3825.35 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 31.29 0.00 -1884.38 0.00 -2539.35 0.00
F6 NE APARTMENT 28-JAN-24:00 3964.63 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1917.09 0.00 -2539.38 -75.23
F6 N1 APARTMENT 29-JAN-00:15 2206.50 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1169.67 0.00 -1492.62 -13.15
F6 N2 APARTMENT 29-JAN-00:15 2206.76 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1169.66 0.00 -1492.62 -13.42
F6 S1 APARTMENT 29-JAN-00:15 2064.83 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 92.33 0.00 -1133.53 0.00 -1492.59 0.00
F6 S2 APARTMENT 29-JAN-00:15 2065.03 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 92.13 0.00 -1133.53 0.00 -1492.59 0.00
F7 SW APARTMENT 28-JAN-24:00 3972.28 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 10.42 0.00 -1865.16 0.00 -2684.61 0.00
F7 NW APARTMENT 28-JAN-24:00 4111.11 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1899.34 0.00 -2684.63 -94.21
F7 SE APARTMENT 28-JAN-24:00 3992.24 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 16.82 0.00 -1891.52 0.00 -2684.62 0.00
F7 NE APARTMENT 28-JAN-24:00 4131.73 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1925.52 0.00 -2684.65 -88.64
F7 N1 APARTMENT 29-JAN-00:15 2310.95 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1174.86 0.00 -1578.01 -27.02
F7 N2 APARTMENT 29-JAN-00:15 2311.22 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1174.86 0.00 -1578.01 -27.30
F7 S1 APARTMENT 29-JAN-00:15 2169.12 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 77.26 0.00 -1137.36 0.00 -1577.98 0.00
F7 S2 APARTMENT 29-JAN-00:15 2169.34 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 77.05 0.00 -1137.36 0.00 -1577.98 0.00
F8 SW APARTMENT 28-JAN-24:00 4131.96 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1870.37 0.00 -2815.85 -12.83
F8 NW APARTMENT 28-JAN-24:00 4270.79 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1905.58 0.00 -2815.87 -116.42
F8 SE APARTMENT 28-JAN-24:00 4152.56 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1897.41 0.00 -2815.85 -6.38
F8 NE APARTMENT 28-JAN-24:00 4292.02 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1932.44 0.00 -2815.88 -110.77
F8 N1 APARTMENT 29-JAN-00:15 2415.22 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1179.08 0.00 -1655.15 -49.94
F8 N2 APARTMENT 29-JAN-00:15 2415.51 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1179.08 0.00 -1655.15 -50.23
F8 S1 APARTMENT 29-JAN-00:15 2273.69 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 52.94 0.00 -1140.47 0.00 -1655.11 0.00
F8 S2 APARTMENT 29-JAN-00:15 2273.92 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 52.70 0.00 -1140.46 0.00 -1655.11 0.00
F9 SW APARTMENT 28-JAN-24:00 4409.24 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1871.15 0.00 -2936.07 -169.11
F9 NW APARTMENT 28-JAN-24:00 4547.53 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1907.09 0.00 -2936.09 -271.43
F9 SE APARTMENT 28-JAN-24:00 4430.97 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1898.67 0.00 -2936.07 -163.31
F9 NE APARTMENT 28-JAN-24:00 4569.83 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1934.43 0.00 -2936.11 -266.36
F9 N1 APARTMENT 29-JAN-00:15 2632.69 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1180.06 0.00 -1725.81 -195.76
F9 N2 APARTMENT 29-JAN-00:15 2633.02 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1180.06 0.00 -1725.81 -196.09
F9 S1 APARTMENT 29-JAN-00:15 2491.35 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1140.66 0.00 -1725.78 -93.86
F9 S2 APARTMENT 29-JAN-00:15 2491.64 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1140.66 0.00 -1725.78 -94.15
T SW APARTMENT 28-JAN-24:00 5390.59 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1836.57 0.00 -3047.13 -1073.97
T NW APARTMENT 28-JAN-24:00 5480.34 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1872.32 0.00 -3047.15 -1127.94
T SE APARTMENT 28-JAN-24:00 5413.23 0.00 0.00 0.00 189.67 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1863.77 0.00 -3047.13 -1069.41
T NE APARTMENT 28-JAN-24:00 5503.15 0.00 0.00 0.00 189.66 36.01 341.40 0.00 0.00 0.00 0.00 0.00 -1899.43 0.00 -3047.17 -1123.63
T N1 APARTMENT 29-JAN-00:15 3562.76 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1157.27 0.00 -1791.17 -1083.26
T N2 APARTMENT 29-JAN-00:15 3563.24 0.00 0.00 0.00 189.66 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1157.26 0.00 -1791.17 -1083.75
T S1 APARTMENT 29-JAN-00:15 3466.57 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1120.72 0.00 -1791.13 -1023.67
T S2 APARTMENT 29-JAN-00:15 3467.03 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1120.71 0.00 -1791.13 -1024.14
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JAN-00:15 241400.42 0.00 0.00 0.00 14983.68 7980.64 21105.27 0.00 0.00 0.00 0.00 0.00 -122450.09 0.00 -149628.08 -13391.85



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Sec1.1A-General Information

Data
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 109.00
Number of hours cooling loads not met 25.00
Number of hours not met 134.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 9687.49 0.00 0.00 0.00 0.00
Exterior Lighting 167.13 10720.10 0.00 0.00 0.00 0.00
Space Heating 544.10 139844.76 1951.93 221268.06 0.00 0.00
Space Cooling 157.30 0.00 0.00 0.00 0.00 0.00
Pumps 45.43 1443.26 0.00 0.00 0.00 0.00
Heat Rejection 5.93 0.00 0.00 0.00 0.00 0.00
Fans-Interior 655.48 20785.11 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1483.57 95799.50 0.00 0.00
Receptacle Equipment 1131.09 29146.79 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3143.70   3435.51   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3143.70
Natural Gas 0.00 3435.51
Additional 0.00 0.00
Total 1131.09 6579.21


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 69.43
Space Cooling 20.07
Fans-Interior 83.64
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 30.54
Subtotal 401.16


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 249.08
Service Water Heating 189.32
Miscellaneous -0.00
Subtotal 438.40


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.33
Space Heating 37.94
Space Cooling 2.39
Fans-Interior 9.96
Service Water Heating 22.55
Receptacle Equipment 17.19
Miscellaneous 3.64



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.240478
G NW APARTMENT DIRECT AIR 0.171863
OFFICE DIRECT AIR 0.336255
G NE APARTMENT DIRECT AIR 0.162588
G N1 APARTMENT DIRECT AIR 0.116577
G N2 APARTMENT DIRECT AIR 0.116575
G S1 APARTMENT DIRECT AIR 0.182502
G S2 APARTMENT DIRECT AIR 0.187975
F2 SW APARTMENT DIRECT AIR 0.320945
F2 NW APARTMENT DIRECT AIR 0.237658
F2 SE APARTMENT DIRECT AIR 0.326133
F2 NE APARTMENT DIRECT AIR 0.191209
F2 N1 APARTMENT DIRECT AIR 0.135228
F2 N2 APARTMENT DIRECT AIR 0.133723
F2 S1 APARTMENT DIRECT AIR 0.247080
F2 S2 APARTMENT DIRECT AIR 0.249233
F3 SW APARTMENT DIRECT AIR 0.322935
F3 NW APARTMENT DIRECT AIR 0.240963
F3 SE APARTMENT DIRECT AIR 0.311826
F3 NE APARTMENT DIRECT AIR 0.195248
F3 N1 APARTMENT DIRECT AIR 0.140052
F3 N2 APARTMENT DIRECT AIR 0.138573
F3 S1 APARTMENT DIRECT AIR 0.251081
F3 S2 APARTMENT DIRECT AIR 0.252224
F4 SW APARTMENT DIRECT AIR 0.323170
F4 NW APARTMENT DIRECT AIR 0.241564
F4 SE APARTMENT DIRECT AIR 0.310691
F4 NE APARTMENT DIRECT AIR 0.195775
F4 N1 APARTMENT DIRECT AIR 0.141111
F4 N2 APARTMENT DIRECT AIR 0.139632
F4 S1 APARTMENT DIRECT AIR 0.251878
F4 S2 APARTMENT DIRECT AIR 0.252883
M SW APARTMENT DIRECT AIR 0.325445
M NW APARTMENT DIRECT AIR 0.244132
M SE APARTMENT DIRECT AIR 0.312940
M NE APARTMENT DIRECT AIR 0.198239
M N1 APARTMENT DIRECT AIR 0.143936
M N2 APARTMENT DIRECT AIR 0.142460
M S1 APARTMENT DIRECT AIR 0.254524
M S2 APARTMENT DIRECT AIR 0.255506
F6 SW APARTMENT DIRECT AIR 0.321256
F6 NW APARTMENT DIRECT AIR 0.240179
F6 SE APARTMENT DIRECT AIR 0.308908
F6 NE APARTMENT DIRECT AIR 0.194325
F6 N1 APARTMENT DIRECT AIR 0.140396
F6 N2 APARTMENT DIRECT AIR 0.138927
F6 S1 APARTMENT DIRECT AIR 0.250634
F6 S2 APARTMENT DIRECT AIR 0.251614
F7 SW APARTMENT DIRECT AIR 0.319495
F7 NW APARTMENT DIRECT AIR 0.238662
F7 SE APARTMENT DIRECT AIR 0.307280
F7 NE APARTMENT DIRECT AIR 0.192803
F7 N1 APARTMENT DIRECT AIR 0.139184
F7 N2 APARTMENT DIRECT AIR 0.137719
F7 S1 APARTMENT DIRECT AIR 0.249127
F7 S2 APARTMENT DIRECT AIR 0.250105
F8 SW APARTMENT DIRECT AIR 0.318944
F8 NW APARTMENT DIRECT AIR 0.238416
F8 SE APARTMENT DIRECT AIR 0.306828
F8 NE APARTMENT DIRECT AIR 0.192479
F8 N1 APARTMENT DIRECT AIR 0.139274
F8 N2 APARTMENT DIRECT AIR 0.137817
F8 S1 APARTMENT DIRECT AIR 0.248792
F8 S2 APARTMENT DIRECT AIR 0.249770
F9 SW APARTMENT DIRECT AIR 0.325561
F9 NW APARTMENT DIRECT AIR 0.245494
F9 SE APARTMENT DIRECT AIR 0.312308
F9 NE APARTMENT DIRECT AIR 0.194733
F9 N1 APARTMENT DIRECT AIR 0.145680
F9 N2 APARTMENT DIRECT AIR 0.144163
F9 S1 APARTMENT DIRECT AIR 0.253397
F9 S2 APARTMENT DIRECT AIR 0.254496
T SW APARTMENT DIRECT AIR 0.385416
T NW APARTMENT DIRECT AIR 0.287525
T SE APARTMENT DIRECT AIR 0.366283
T NE APARTMENT DIRECT AIR 0.224572
T N1 APARTMENT DIRECT AIR 0.159694
T N2 APARTMENT DIRECT AIR 0.156615
T S1 APARTMENT DIRECT AIR 0.321790
T S2 APARTMENT DIRECT AIR 0.322872


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.240478
AIRLOOP G NW MAIN BRANCH 0.171863
AIRLOOP OFFICE MAIN BRANCH 0.336255
AIRLOOP G NE MAIN BRANCH 0.162588
AIRLOOP G N1 MAIN BRANCH 0.116577
AIRLOOP G N2 MAIN BRANCH 0.116575
AIRLOOP G S1 MAIN BRANCH 0.182502
AIRLOOP G S2 MAIN BRANCH 0.187975
AIRLOOP F2 SW MAIN BRANCH 0.320945
AIRLOOP F2 NW MAIN BRANCH 0.237658
AIRLOOP F2 SE MAIN BRANCH 0.326133
AIRLOOP F2 NE MAIN BRANCH 0.191209
AIRLOOP F2 N1 MAIN BRANCH 0.135228
AIRLOOP F2 N2 MAIN BRANCH 0.133723
AIRLOOP F2 S1 MAIN BRANCH 0.247080
AIRLOOP F2 S2 MAIN BRANCH 0.249233
AIRLOOP F3 SW MAIN BRANCH 0.322935
AIRLOOP F3 NW MAIN BRANCH 0.240963
AIRLOOP F3 SE MAIN BRANCH 0.311826
AIRLOOP F3 NE MAIN BRANCH 0.195248
AIRLOOP F3 N1 MAIN BRANCH 0.140052
AIRLOOP F3 N2 MAIN BRANCH 0.138573
AIRLOOP F3 S1 MAIN BRANCH 0.251081
AIRLOOP F3 S2 MAIN BRANCH 0.252224
AIRLOOP F4 SW MAIN BRANCH 0.323170
AIRLOOP F4 NW MAIN BRANCH 0.241564
AIRLOOP F4 SE MAIN BRANCH 0.310691
AIRLOOP F4 NE MAIN BRANCH 0.195775
AIRLOOP F4 N1 MAIN BRANCH 0.141111
AIRLOOP F4 N2 MAIN BRANCH 0.139632
AIRLOOP F4 S1 MAIN BRANCH 0.251878
AIRLOOP F4 S2 MAIN BRANCH 0.252883
AIRLOOP M SW MAIN BRANCH 0.325445
AIRLOOP M NW MAIN BRANCH 0.244132
AIRLOOP M SE MAIN BRANCH 0.312940
AIRLOOP M NE MAIN BRANCH 0.198239
AIRLOOP M N1 MAIN BRANCH 0.143936
AIRLOOP M N2 MAIN BRANCH 0.142460
AIRLOOP M S1 MAIN BRANCH 0.254524
AIRLOOP M S2 MAIN BRANCH 0.255506
AIRLOOP F6 SW MAIN BRANCH 0.321256
AIRLOOP F6 NW MAIN BRANCH 0.240179
AIRLOOP F6 SE MAIN BRANCH 0.308908
AIRLOOP F6 NE MAIN BRANCH 0.194325
AIRLOOP F6 N1 MAIN BRANCH 0.140396
AIRLOOP F6 N2 MAIN BRANCH 0.138927
AIRLOOP F6 S1 MAIN BRANCH 0.250634
AIRLOOP F6 S2 MAIN BRANCH 0.251614
AIRLOOP F7 SW MAIN BRANCH 0.319495
AIRLOOP F7 NW MAIN BRANCH 0.238662
AIRLOOP F7 SE MAIN BRANCH 0.307280
AIRLOOP F7 NE MAIN BRANCH 0.192803
AIRLOOP F7 N1 MAIN BRANCH 0.139184
AIRLOOP F7 N2 MAIN BRANCH 0.137719
AIRLOOP F7 S1 MAIN BRANCH 0.249127
AIRLOOP F7 S2 MAIN BRANCH 0.250105
AIRLOOP F8 SW MAIN BRANCH 0.318944
AIRLOOP F8 NW MAIN BRANCH 0.238416
AIRLOOP F8 SE MAIN BRANCH 0.306828
AIRLOOP F8 NE MAIN BRANCH 0.192479
AIRLOOP F8 N1 MAIN BRANCH 0.139274
AIRLOOP F8 N2 MAIN BRANCH 0.137817
AIRLOOP F8 S1 MAIN BRANCH 0.248792
AIRLOOP F8 S2 MAIN BRANCH 0.249770
AIRLOOP F9 SW MAIN BRANCH 0.325561
AIRLOOP F9 NW MAIN BRANCH 0.245494
AIRLOOP F9 SE MAIN BRANCH 0.312308
AIRLOOP F9 NE MAIN BRANCH 0.194733
AIRLOOP F9 N1 MAIN BRANCH 0.145680
AIRLOOP F9 N2 MAIN BRANCH 0.144163
AIRLOOP F9 S1 MAIN BRANCH 0.253397
AIRLOOP F9 S2 MAIN BRANCH 0.254496
AIRLOOP T SW MAIN BRANCH 0.385416
AIRLOOP T NW MAIN BRANCH 0.287525
AIRLOOP T SE MAIN BRANCH 0.366283
AIRLOOP T NE MAIN BRANCH 0.224572
AIRLOOP T N1 MAIN BRANCH 0.159694
AIRLOOP T N2 MAIN BRANCH 0.156615
AIRLOOP T S1 MAIN BRANCH 0.321790
AIRLOOP T S2 MAIN BRANCH 0.322872


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.240478
AIRLOOP G NW 0.171863
AIRLOOP OFFICE 0.336255
AIRLOOP G NE 0.162588
AIRLOOP G N1 0.116577
AIRLOOP G N2 0.116575
AIRLOOP G S1 0.182502
AIRLOOP G S2 0.187975
AIRLOOP F2 SW 0.320945
AIRLOOP F2 NW 0.237658
AIRLOOP F2 SE 0.326133
AIRLOOP F2 NE 0.191209
AIRLOOP F2 N1 0.135228
AIRLOOP F2 N2 0.133723
AIRLOOP F2 S1 0.247080
AIRLOOP F2 S2 0.249233
AIRLOOP F3 SW 0.322935
AIRLOOP F3 NW 0.240963
AIRLOOP F3 SE 0.311826
AIRLOOP F3 NE 0.195248
AIRLOOP F3 N1 0.140052
AIRLOOP F3 N2 0.138573
AIRLOOP F3 S1 0.251081
AIRLOOP F3 S2 0.252224
AIRLOOP F4 SW 0.323170
AIRLOOP F4 NW 0.241564
AIRLOOP F4 SE 0.310691
AIRLOOP F4 NE 0.195775
AIRLOOP F4 N1 0.141111
AIRLOOP F4 N2 0.139632
AIRLOOP F4 S1 0.251878
AIRLOOP F4 S2 0.252883
AIRLOOP M SW 0.325445
AIRLOOP M NW 0.244132
AIRLOOP M SE 0.312940
AIRLOOP M NE 0.198239
AIRLOOP M N1 0.143936
AIRLOOP M N2 0.142460
AIRLOOP M S1 0.254524
AIRLOOP M S2 0.255506
AIRLOOP F6 SW 0.321256
AIRLOOP F6 NW 0.240179
AIRLOOP F6 SE 0.308908
AIRLOOP F6 NE 0.194325
AIRLOOP F6 N1 0.140396
AIRLOOP F6 N2 0.138927
AIRLOOP F6 S1 0.250634
AIRLOOP F6 S2 0.251614
AIRLOOP F7 SW 0.319495
AIRLOOP F7 NW 0.238662
AIRLOOP F7 SE 0.307280
AIRLOOP F7 NE 0.192803
AIRLOOP F7 N1 0.139184
AIRLOOP F7 N2 0.137719
AIRLOOP F7 S1 0.249127
AIRLOOP F7 S2 0.250105
AIRLOOP F8 SW 0.318944
AIRLOOP F8 NW 0.238416
AIRLOOP F8 SE 0.306828
AIRLOOP F8 NE 0.192479
AIRLOOP F8 N1 0.139274
AIRLOOP F8 N2 0.137817
AIRLOOP F8 S1 0.248792
AIRLOOP F8 S2 0.249770
AIRLOOP F9 SW 0.325561
AIRLOOP F9 NW 0.245494
AIRLOOP F9 SE 0.312308
AIRLOOP F9 NE 0.194733
AIRLOOP F9 N1 0.145680
AIRLOOP F9 N2 0.144163
AIRLOOP F9 S1 0.253397
AIRLOOP F9 S2 0.254496
AIRLOOP T SW 0.385416
AIRLOOP T NW 0.287525
AIRLOOP T SE 0.366283
AIRLOOP T NE 0.224572
AIRLOOP T N1 0.159694
AIRLOOP T N2 0.156615
AIRLOOP T S1 0.321790
AIRLOOP T S2 0.322872


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.240478 0.025952
AIRLOOP G NW OA CONTROLLER 0.171863 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.336255 0.038103
AIRLOOP G NE OA CONTROLLER 0.162588 0.025952
AIRLOOP G N1 OA CONTROLLER 0.116577 0.025952
AIRLOOP G N2 OA CONTROLLER 0.116575 0.025952
AIRLOOP G S1 OA CONTROLLER 0.182502 0.025952
AIRLOOP G S2 OA CONTROLLER 0.187975 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.320945 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.237658 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.326133 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.191209 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.135228 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.133723 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.247080 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.249233 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.322935 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.240963 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.311826 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.195248 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.140052 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.138573 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.251081 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.252224 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.323170 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.241564 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.310691 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.195775 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.141111 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.139632 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.251878 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.252883 0.025952
AIRLOOP M SW OA CONTROLLER 0.325445 0.025952
AIRLOOP M NW OA CONTROLLER 0.244132 0.025952
AIRLOOP M SE OA CONTROLLER 0.312940 0.025952
AIRLOOP M NE OA CONTROLLER 0.198239 0.025952
AIRLOOP M N1 OA CONTROLLER 0.143936 0.025952
AIRLOOP M N2 OA CONTROLLER 0.142460 0.025952
AIRLOOP M S1 OA CONTROLLER 0.254524 0.025952
AIRLOOP M S2 OA CONTROLLER 0.255506 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.321256 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.240179 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.308908 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.194325 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.140396 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.138927 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.250634 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.251614 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.319495 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.238662 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.307280 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.192803 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.139184 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.137719 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.249127 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.250105 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.318944 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.238416 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.306828 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.192479 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.139274 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.137817 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.248792 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.249770 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.325561 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.245494 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.312308 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.194733 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.145680 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.144163 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.253397 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.254496 0.025952
AIRLOOP T SW OA CONTROLLER 0.385416 0.025952
AIRLOOP T NW OA CONTROLLER 0.287525 0.025952
AIRLOOP T SE OA CONTROLLER 0.366283 0.025952
AIRLOOP T NE OA CONTROLLER 0.224572 0.025952
AIRLOOP T N1 OA CONTROLLER 0.159694 0.025952
AIRLOOP T N2 OA CONTROLLER 0.156615 0.025952
AIRLOOP T S1 OA CONTROLLER 0.321790 0.025952
AIRLOOP T S2 OA CONTROLLER 0.322872 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.240478 3321.35 2582.08 0.000073
HEAT PUMP COOLING MODE AIRLOOP G NW 0.171863 2312.85 1812.32 0.000051
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.336255 4658.89 3623.19 0.000102
HEAT PUMP COOLING MODE AIRLOOP G NE 0.162588 2157.41 1712.59 0.000047
HEAT PUMP COOLING MODE AIRLOOP G N1 0.116577 1441.61 1169.69 0.000031
HEAT PUMP COOLING MODE AIRLOOP G N2 0.116575 1437.68 1168.03 0.000031
HEAT PUMP COOLING MODE AIRLOOP G S1 0.182502 2548.65 1975.51 0.000056
HEAT PUMP COOLING MODE AIRLOOP G S2 0.187975 2624.50 2034.02 0.000057
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.320945 4424.22 3437.60 0.000097
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.237658 3209.61 2507.62 0.000070
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.326133 4525.10 3507.25 0.000099
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.191209 2563.62 2020.97 0.000056
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.135228 1744.24 1388.34 0.000038
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.133723 1723.24 1372.20 0.000038
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.247080 3439.33 2664.76 0.000075
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.249233 3469.18 2687.77 0.000076
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.322935 4447.24 3457.72 0.000097
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.240963 3258.29 2545.70 0.000071
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.311826 4322.34 3353.21 0.000094
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.195248 2615.20 2063.04 0.000057
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.140052 1808.65 1439.32 0.000040
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.138573 1788.03 1423.48 0.000039
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.251081 3492.08 2706.85 0.000076
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.252224 3507.91 2719.06 0.000077
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.323170 4447.08 3459.37 0.000097
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.241564 3268.82 2554.69 0.000071
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.310691 4303.23 3340.23 0.000094
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.195775 2619.28 2067.87 0.000057
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.141111 1821.26 1450.14 0.000040
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.139632 1800.65 1434.30 0.000039
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.251878 3501.07 2714.85 0.000076
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.252883 3515.00 2725.59 0.000077
HEAT PUMP COOLING MODE AIRLOOP M SW 0.325445 4475.81 3482.98 0.000098
HEAT PUMP COOLING MODE AIRLOOP M NW 0.244132 3301.71 2581.47 0.000072
HEAT PUMP COOLING MODE AIRLOOP M SE 0.312940 4331.61 3363.56 0.000095
HEAT PUMP COOLING MODE AIRLOOP M NE 0.198239 2650.74 2093.53 0.000058
HEAT PUMP COOLING MODE AIRLOOP M N1 0.143936 1858.89 1479.98 0.000041
HEAT PUMP COOLING MODE AIRLOOP M N2 0.142460 1838.32 1464.16 0.000040
HEAT PUMP COOLING MODE AIRLOOP M S1 0.254524 3536.05 2742.71 0.000077
HEAT PUMP COOLING MODE AIRLOOP M S2 0.255506 3549.67 2753.21 0.000078
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.321256 4415.38 3437.62 0.000096
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.240179 3244.27 2538.56 0.000071
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.308908 4273.40 3319.89 0.000093
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.194325 2594.37 2051.18 0.000057
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.140396 1808.02 1441.68 0.000039
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.138927 1787.53 1425.93 0.000039
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.250634 3480.71 2700.77 0.000076
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.251614 3494.29 2711.24 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.319495 4388.88 3418.27 0.000096
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.238662 3221.04 2521.79 0.000070
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.307280 4248.77 3301.97 0.000093
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.192803 2571.38 2034.45 0.000056
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.139184 1789.79 1428.36 0.000039
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.137719 1769.38 1412.67 0.000039
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.249127 3458.56 2684.34 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.250105 3472.12 2694.80 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.318944 4379.36 3411.92 0.000096
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.238416 3215.70 2518.68 0.000070
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.306828 4240.65 3296.67 0.000093
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.192479 2565.15 2030.56 0.000056
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.139274 1789.86 1429.03 0.000039
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.137817 1769.56 1413.42 0.000039
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.248792 3452.78 2680.48 0.000075
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.249770 3466.35 2690.94 0.000076
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.325561 4469.29 3482.19 0.000098
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.245494 3312.41 2593.97 0.000072
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.312308 4314.83 3354.80 0.000094
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.194733 2594.71 2054.23 0.000057
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.145680 1878.10 1497.40 0.000041
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.144163 1856.97 1481.16 0.000041
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.253397 3515.55 2729.44 0.000077
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.254496 3530.78 2741.19 0.000077
HEAT PUMP COOLING MODE AIRLOOP T SW 0.385416 5312.15 4129.05 0.000116
HEAT PUMP COOLING MODE AIRLOOP T NW 0.287525 3915.30 3059.09 0.000086
HEAT PUMP COOLING MODE AIRLOOP T SE 0.366283 5060.75 3931.15 0.000111
HEAT PUMP COOLING MODE AIRLOOP T NE 0.224572 3028.56 2383.52 0.000066
HEAT PUMP COOLING MODE AIRLOOP T N1 0.159694 2085.92 1654.19 0.000046
HEAT PUMP COOLING MODE AIRLOOP T N2 0.156615 2043.06 1621.23 0.000045
HEAT PUMP COOLING MODE AIRLOOP T S1 0.321790 4462.20 3460.15 0.000097
HEAT PUMP COOLING MODE AIRLOOP T S2 0.322872 4477.19 3471.71 0.000098


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.240478 0.240478 0.240478 0.240478 3321.35 3321.35 5502.40 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.171863 0.171863 0.171863 0.171863 2312.85 2312.85 5512.16 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.336255 0.336255 0.336255 0.336255 4658.89 4658.89 6951.70 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.162588 0.162588 0.162588 0.162588 2157.41 2157.41 5510.40 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.116577 0.116577 0.116577 0.116577 1441.61 1441.61 4507.40 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.116575 0.116575 0.116575 0.116575 1437.68 1437.68 4507.37 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.182502 0.182502 0.182502 0.182502 2548.65 2548.65 4495.96 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.187975 0.187975 0.187975 0.187975 2624.50 2624.50 4504.48 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.320945 0.320945 0.320945 0.320945 4424.22 4424.22 4786.49 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.237658 0.237658 0.237658 0.237658 3209.61 3209.61 4780.83 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.326133 0.326133 0.326133 0.326133 4525.10 4525.10 4807.88 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.191209 0.191209 0.191209 0.191209 2563.62 2563.62 4778.05 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.135228 0.135228 0.135228 0.135228 1744.24 1744.24 3625.72 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.133723 0.133723 0.133723 0.133723 1723.24 1723.24 3625.66 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.247080 0.247080 0.247080 0.247080 3439.33 3439.33 3634.92 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.249233 0.249233 0.249233 0.249233 3469.18 3469.18 3636.30 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.322935 0.322935 0.322935 0.322935 4447.24 4447.24 4612.41 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.240963 0.240963 0.240963 0.240963 3258.29 3258.29 4608.83 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.311826 0.311826 0.311826 0.311826 4322.34 4322.34 4611.53 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.195248 0.195248 0.195248 0.195248 2615.20 2615.20 4605.55 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.140052 0.140052 0.140052 0.140052 1808.65 1808.65 3450.35 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.138573 0.138573 0.138573 0.138573 1788.03 1788.03 3450.28 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.251081 0.251081 0.251081 0.251081 3492.08 3492.08 3455.49 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.252224 0.252224 0.252224 0.252224 3507.91 3507.91 3455.63 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.323170 0.323170 0.323170 0.323170 4447.08 4447.08 4585.30 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.241564 0.241564 0.241564 0.241564 3268.82 3268.82 4582.21 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.310691 0.310691 0.310691 0.310691 4303.23 4303.23 4581.87 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.195775 0.195775 0.195775 0.195775 2619.28 2619.28 4578.54 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.141111 0.141111 0.141111 0.141111 1821.26 1821.26 3416.97 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.139632 0.139632 0.139632 0.139632 1800.65 1800.65 3416.90 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.251878 0.251878 0.251878 0.251878 3501.07 3501.07 3421.46 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.252883 0.252883 0.252883 0.252883 3515.00 3515.00 3421.40 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.325445 0.325445 0.325445 0.325445 4475.81 4475.81 4554.52 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.244132 0.244132 0.244132 0.244132 3301.71 3301.71 4550.10 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.312940 0.312940 0.312940 0.312940 4331.61 4331.61 4550.58 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.198239 0.198239 0.198239 0.198239 2650.74 2650.74 4546.13 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.143936 0.143936 0.143936 0.143936 1858.89 1858.89 3382.60 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.142460 0.142460 0.142460 0.142460 1838.32 1838.32 3382.51 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.254524 0.254524 0.254524 0.254524 3536.05 3536.05 3388.42 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.255506 0.255506 0.255506 0.255506 3549.67 3549.67 3388.34 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.321256 0.321256 0.321256 0.321256 4415.38 4415.38 4604.23 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.240179 0.240179 0.240179 0.240179 3244.27 3244.27 4600.37 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.308908 0.308908 0.308908 0.308908 4273.40 4273.40 4600.00 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.194325 0.194325 0.194325 0.194325 2594.37 2594.37 4596.13 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.140396 0.140396 0.140396 0.140396 1808.02 1808.02 3425.72 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.138927 0.138927 0.138927 0.138927 1787.53 1787.53 3425.63 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.250634 0.250634 0.250634 0.250634 3480.71 3480.71 3430.92 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.251614 0.251614 0.251614 0.251614 3494.29 3494.29 3430.83 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.319495 0.319495 0.319495 0.319495 4388.88 4388.88 4628.54 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.238662 0.238662 0.238662 0.238662 3221.04 3221.04 4624.01 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.307280 0.307280 0.307280 0.307280 4248.77 4248.77 4624.08 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.192803 0.192803 0.192803 0.192803 2571.38 2571.38 4619.54 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.139184 0.139184 0.139184 0.139184 1789.79 1789.79 3445.97 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.137719 0.137719 0.137719 0.137719 1769.38 1769.38 3445.87 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.249127 0.249127 0.249127 0.249127 3458.56 3458.56 3451.80 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.250105 0.250105 0.250105 0.250105 3472.12 3472.12 3451.71 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.318944 0.318944 0.318944 0.318944 4379.36 4379.36 4671.11 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.238416 0.238416 0.238416 0.238416 3215.70 3215.70 4665.56 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.306828 0.306828 0.306828 0.306828 4240.65 4240.65 4666.45 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.192479 0.192479 0.192479 0.192479 2565.15 2565.15 4660.90 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.139274 0.139274 0.139274 0.139274 1789.86 1789.86 3485.47 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.137817 0.137817 0.137817 0.137817 1769.56 1769.56 3485.38 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.248792 0.248792 0.248792 0.248792 3452.78 3452.78 3492.29 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.249770 0.249770 0.249770 0.249770 3466.35 3466.35 3492.19 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.325561 0.325561 0.325561 0.325561 4469.29 4469.29 4948.96 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.245494 0.245494 0.245494 0.245494 3312.41 3312.41 4938.86 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.312308 0.312308 0.312308 0.312308 4314.83 4314.83 4944.08 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.194733 0.194733 0.194733 0.194733 2594.71 2594.71 4933.98 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.145680 0.145680 0.145680 0.145680 1878.10 1878.10 3745.27 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.144163 0.144163 0.144163 0.144163 1856.97 1856.97 3745.16 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.253397 0.253397 0.253397 0.253397 3515.55 3515.55 3756.15 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.254496 0.254496 0.254496 0.254496 3530.78 3530.78 3756.04 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.385416 0.385416 0.385416 0.385416 5312.15 5312.15 6347.84 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.287525 0.287525 0.287525 0.287525 3915.30 3915.30 6348.72 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.366283 0.366283 0.366283 0.366283 5060.75 5060.75 6343.09 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.224572 0.224572 0.224572 0.224572 3028.56 3028.56 6343.96 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.159694 0.159694 0.159694 0.159694 2085.92 2085.92 5226.67 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.156615 0.156615 0.156615 0.156615 2043.06 2043.06 5226.56 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.321790 0.321790 0.321790 0.321790 4462.20 4462.20 5223.52 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.322872 0.322872 0.322872 0.322872 4477.19 4477.19 5223.42 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.240478
AIRLOOP G NW SUPPLY FAN 0.171863
AIRLOOP OFFICE SUPPLY FAN 0.336255
AIRLOOP G NE SUPPLY FAN 0.162588
AIRLOOP G N1 SUPPLY FAN 0.116577
AIRLOOP G N2 SUPPLY FAN 0.116575
AIRLOOP G S1 SUPPLY FAN 0.182502
AIRLOOP G S2 SUPPLY FAN 0.187975
AIRLOOP F2 SW SUPPLY FAN 0.320945
AIRLOOP F2 NW SUPPLY FAN 0.237658
AIRLOOP F2 SE SUPPLY FAN 0.326133
AIRLOOP F2 NE SUPPLY FAN 0.191209
AIRLOOP F2 N1 SUPPLY FAN 0.135228
AIRLOOP F2 N2 SUPPLY FAN 0.133723
AIRLOOP F2 S1 SUPPLY FAN 0.247080
AIRLOOP F2 S2 SUPPLY FAN 0.249233
AIRLOOP F3 SW SUPPLY FAN 0.322935
AIRLOOP F3 NW SUPPLY FAN 0.240963
AIRLOOP F3 SE SUPPLY FAN 0.311826
AIRLOOP F3 NE SUPPLY FAN 0.195248
AIRLOOP F3 N1 SUPPLY FAN 0.140052
AIRLOOP F3 N2 SUPPLY FAN 0.138573
AIRLOOP F3 S1 SUPPLY FAN 0.251081
AIRLOOP F3 S2 SUPPLY FAN 0.252224
AIRLOOP F4 SW SUPPLY FAN 0.323170
AIRLOOP F4 NW SUPPLY FAN 0.241564
AIRLOOP F4 SE SUPPLY FAN 0.310691
AIRLOOP F4 NE SUPPLY FAN 0.195775
AIRLOOP F4 N1 SUPPLY FAN 0.141111
AIRLOOP F4 N2 SUPPLY FAN 0.139632
AIRLOOP F4 S1 SUPPLY FAN 0.251878
AIRLOOP F4 S2 SUPPLY FAN 0.252883
AIRLOOP M SW SUPPLY FAN 0.325445
AIRLOOP M NW SUPPLY FAN 0.244132
AIRLOOP M SE SUPPLY FAN 0.312940
AIRLOOP M NE SUPPLY FAN 0.198239
AIRLOOP M N1 SUPPLY FAN 0.143936
AIRLOOP M N2 SUPPLY FAN 0.142460
AIRLOOP M S1 SUPPLY FAN 0.254524
AIRLOOP M S2 SUPPLY FAN 0.255506
AIRLOOP F6 SW SUPPLY FAN 0.321256
AIRLOOP F6 NW SUPPLY FAN 0.240179
AIRLOOP F6 SE SUPPLY FAN 0.308908
AIRLOOP F6 NE SUPPLY FAN 0.194325
AIRLOOP F6 N1 SUPPLY FAN 0.140396
AIRLOOP F6 N2 SUPPLY FAN 0.138927
AIRLOOP F6 S1 SUPPLY FAN 0.250634
AIRLOOP F6 S2 SUPPLY FAN 0.251614
AIRLOOP F7 SW SUPPLY FAN 0.319495
AIRLOOP F7 NW SUPPLY FAN 0.238662
AIRLOOP F7 SE SUPPLY FAN 0.307280
AIRLOOP F7 NE SUPPLY FAN 0.192803
AIRLOOP F7 N1 SUPPLY FAN 0.139184
AIRLOOP F7 N2 SUPPLY FAN 0.137719
AIRLOOP F7 S1 SUPPLY FAN 0.249127
AIRLOOP F7 S2 SUPPLY FAN 0.250105
AIRLOOP F8 SW SUPPLY FAN 0.318944
AIRLOOP F8 NW SUPPLY FAN 0.238416
AIRLOOP F8 SE SUPPLY FAN 0.306828
AIRLOOP F8 NE SUPPLY FAN 0.192479
AIRLOOP F8 N1 SUPPLY FAN 0.139274
AIRLOOP F8 N2 SUPPLY FAN 0.137817
AIRLOOP F8 S1 SUPPLY FAN 0.248792
AIRLOOP F8 S2 SUPPLY FAN 0.249770
AIRLOOP F9 SW SUPPLY FAN 0.325561
AIRLOOP F9 NW SUPPLY FAN 0.245494
AIRLOOP F9 SE SUPPLY FAN 0.312308
AIRLOOP F9 NE SUPPLY FAN 0.194733
AIRLOOP F9 N1 SUPPLY FAN 0.145680
AIRLOOP F9 N2 SUPPLY FAN 0.144163
AIRLOOP F9 S1 SUPPLY FAN 0.253397
AIRLOOP F9 S2 SUPPLY FAN 0.254496
AIRLOOP T SW SUPPLY FAN 0.385416
AIRLOOP T NW SUPPLY FAN 0.287525
AIRLOOP T SE SUPPLY FAN 0.366283
AIRLOOP T NE SUPPLY FAN 0.224572
AIRLOOP T N1 SUPPLY FAN 0.159694
AIRLOOP T N2 SUPPLY FAN 0.156615
AIRLOOP T S1 SUPPLY FAN 0.321790
AIRLOOP T S2 SUPPLY FAN 0.322872


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.240478 3321.35 0.000073
HEAT PUMP HEATING MODE AIRLOOP G NW 0.171863 2312.85 0.000051
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.336255 4658.89 0.000102
HEAT PUMP HEATING MODE AIRLOOP G NE 0.162588 2157.41 0.000047
HEAT PUMP HEATING MODE AIRLOOP G N1 0.116577 1441.61 0.000031
HEAT PUMP HEATING MODE AIRLOOP G N2 0.116575 1437.68 0.000031
HEAT PUMP HEATING MODE AIRLOOP G S1 0.182502 2548.65 0.000056
HEAT PUMP HEATING MODE AIRLOOP G S2 0.187975 2624.50 0.000057
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.320945 4424.22 0.000097
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.237658 3209.61 0.000070
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.326133 4525.10 0.000099
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.191209 2563.62 0.000056
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.135228 1744.24 0.000038
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.133723 1723.24 0.000038
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.247080 3439.33 0.000075
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.249233 3469.18 0.000076
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.322935 4447.24 0.000097
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.240963 3258.29 0.000071
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.311826 4322.34 0.000094
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.195248 2615.20 0.000057
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.140052 1808.65 0.000040
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.138573 1788.03 0.000039
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.251081 3492.08 0.000076
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.252224 3507.91 0.000077
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.323170 4447.08 0.000097
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.241564 3268.82 0.000071
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.310691 4303.23 0.000094
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.195775 2619.28 0.000057
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.141111 1821.26 0.000040
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.139632 1800.65 0.000039
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.251878 3501.07 0.000076
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.252883 3515.00 0.000077
HEAT PUMP HEATING MODE AIRLOOP M SW 0.325445 4475.81 0.000098
HEAT PUMP HEATING MODE AIRLOOP M NW 0.244132 3301.71 0.000072
HEAT PUMP HEATING MODE AIRLOOP M SE 0.312940 4331.61 0.000095
HEAT PUMP HEATING MODE AIRLOOP M NE 0.198239 2650.74 0.000058
HEAT PUMP HEATING MODE AIRLOOP M N1 0.143936 1858.89 0.000041
HEAT PUMP HEATING MODE AIRLOOP M N2 0.142460 1838.32 0.000040
HEAT PUMP HEATING MODE AIRLOOP M S1 0.254524 3536.05 0.000077
HEAT PUMP HEATING MODE AIRLOOP M S2 0.255506 3549.67 0.000078
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.321256 4415.38 0.000096
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.240179 3244.27 0.000071
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.308908 4273.40 0.000093
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.194325 2594.37 0.000057
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.140396 1808.02 0.000039
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.138927 1787.53 0.000039
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.250634 3480.71 0.000076
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.251614 3494.29 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.319495 4388.88 0.000096
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.238662 3221.04 0.000070
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.307280 4248.77 0.000093
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.192803 2571.38 0.000056
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.139184 1789.79 0.000039
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.137719 1769.38 0.000039
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.249127 3458.56 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.250105 3472.12 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.318944 4379.36 0.000096
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.238416 3215.70 0.000070
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.306828 4240.65 0.000093
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.192479 2565.15 0.000056
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.139274 1789.86 0.000039
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.137817 1769.56 0.000039
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.248792 3452.78 0.000075
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.249770 3466.35 0.000076
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.325561 4469.29 0.000098
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.245494 3312.41 0.000072
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.312308 4314.83 0.000094
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.194733 2594.71 0.000057
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.145680 1878.10 0.000041
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.144163 1856.97 0.000041
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.253397 3515.55 0.000077
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.254496 3530.78 0.000077
HEAT PUMP HEATING MODE AIRLOOP T SW 0.385416 5312.15 0.000116
HEAT PUMP HEATING MODE AIRLOOP T NW 0.287525 3915.30 0.000086
HEAT PUMP HEATING MODE AIRLOOP T SE 0.366283 5060.75 0.000111
HEAT PUMP HEATING MODE AIRLOOP T NE 0.224572 3028.56 0.000066
HEAT PUMP HEATING MODE AIRLOOP T N1 0.159694 2085.92 0.000046
HEAT PUMP HEATING MODE AIRLOOP T N2 0.156615 2043.06 0.000045
HEAT PUMP HEATING MODE AIRLOOP T S1 0.321790 4462.20 0.000097
HEAT PUMP HEATING MODE AIRLOOP T S2 0.322872 4477.19 0.000098


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 5502.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 5512.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 6951.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 5510.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 4507.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 4507.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 4495.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 4504.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 4786.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 4780.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 4807.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 4778.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 3625.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 3625.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 3634.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 3636.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 4612.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 4608.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 4611.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 4605.55
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 3450.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 3450.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 3455.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 3455.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 4585.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 4582.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 4581.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 4578.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 3416.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 3416.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 3421.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 3421.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 4554.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 4550.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 4550.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 4546.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 3382.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 3382.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 3388.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 3388.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 4604.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 4600.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 4600.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 4596.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 3425.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 3425.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 3430.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 3430.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 4628.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 4624.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 4624.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 4619.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 3445.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 3445.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 3451.80
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 3451.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 4671.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 4665.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 4666.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 4660.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 3485.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 3485.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 3492.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 3492.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 4948.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 4938.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 4944.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 4933.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 3745.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 3745.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 3756.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 3756.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 6347.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 6348.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 6343.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 6343.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 5226.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 5226.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 5223.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 5223.42


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.005514 6.20


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.005514


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.005514 2661.80 7.12 8130.20


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.005514 1406.33



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:12

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.74 -10.3
April 22.42 0.73
May 23.15 10.60
June 24.11 15.96
July 24.18 16.86
August 24.03 14.24
September 23.07 6.72
October 21.80 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.61 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.18 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.87 0.73
May 22.48 10.60
June 23.94 15.96
July 24.06 16.86
August 23.67 14.24
September 22.37 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.39 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.06 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.81 -10.3
April 22.42 0.73
May 23.30 10.60
June 24.21 15.96
July 24.27 16.86
August 24.10 14.24
September 23.06 6.72
October 21.87 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.66 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.84 0.73
May 22.73 10.60
June 23.99 15.96
July 24.11 16.86
August 23.75 14.24
September 22.46 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.43 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.11 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.76 0.73
May 22.27 10.60
June 23.81 15.96
July 23.99 16.86
August 23.61 14.24
September 22.41 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.34 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 23.99 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.76 0.73
May 22.30 10.60
June 23.82 15.96
July 23.99 16.86
August 23.62 14.24
September 22.43 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.35 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 23.99 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.75 -10.3
April 22.40 0.73
May 23.12 10.60
June 24.07 15.96
July 24.16 16.86
August 24.07 14.24
September 23.28 6.72
October 21.86 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.63 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.16 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.75 -10.3
April 22.42 0.73
May 23.17 10.60
June 24.09 15.96
July 24.18 16.86
August 24.10 14.24
September 23.32 6.72
October 21.87 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.65 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.18 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.35 -17.6
February 13.17 -15.4
March 14.62 -10.3
April 17.87 0.73
May 20.97 10.60
June 23.35 15.96
July 23.77 16.86
August 22.84 14.24
September 20.26 6.72
October 16.40 -3.1
November 12.59 -17.6
December 11.98 -19.3
     
Annual Sum or Average 17.54 -1.4
Minimum of Months 11.98 -19.3
Maximum of Months 23.77 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.84 -10.3
April 23.00 0.73
May 24.06 10.60
June 24.34 15.96
July 24.35 16.86
August 24.29 14.24
September 23.54 6.72
October 21.97 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.86 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.17 0.73
May 23.57 10.60
June 24.25 15.96
July 24.30 16.86
August 24.06 14.24
September 22.73 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.61 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.30 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.91 -10.3
April 23.06 0.73
May 24.14 10.60
June 24.37 15.96
July 24.38 16.86
August 24.32 14.24
September 23.65 6.72
October 22.06 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.90 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.38 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.12 0.73
May 23.68 10.60
June 24.27 15.96
July 24.31 16.86
August 24.08 14.24
September 22.78 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.63 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.31 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.98 0.73
May 23.40 10.60
June 24.17 15.96
July 24.24 16.86
August 24.00 14.24
September 22.77 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.57 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.24 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.98 0.73
May 23.42 10.60
June 24.17 15.96
July 24.25 16.86
August 24.01 14.24
September 22.79 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.58 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.25 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.92 -10.3
April 23.11 0.73
May 24.11 10.60
June 24.32 15.96
July 24.33 16.86
August 24.31 14.24
September 23.77 6.72
October 22.15 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.93 -10.3
April 23.12 0.73
May 24.13 10.60
June 24.33 15.96
July 24.34 16.86
August 24.31 14.24
September 23.79 6.72
October 22.17 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.92 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.34 -17.6
February 20.81 -15.4
March 21.46 -10.3
April 23.17 0.73
May 25.06 10.60
June 26.13 15.96
July 26.19 16.86
August 25.74 14.24
September 24.16 6.72
October 21.82 -3.1
November 20.59 -17.6
December 20.17 -19.3
     
Annual Sum or Average 22.98 -1.4
Minimum of Months 20.17 -19.3
Maximum of Months 26.19 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.86 -10.3
April 23.10 0.73
May 24.16 10.60
June 24.35 15.96
July 24.36 16.86
August 24.30 14.24
September 23.61 6.72
October 22.03 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.89 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.27 0.73
May 23.81 10.60
June 24.26 15.96
July 24.31 16.86
August 24.10 14.24
September 22.85 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.66 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.31 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.91 -10.3
April 23.11 0.73
May 24.19 10.60
June 24.36 15.96
July 24.37 16.86
August 24.32 14.24
September 23.67 6.72
October 22.08 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.37 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.24 0.73
May 23.85 10.60
June 24.28 15.96
July 24.33 16.86
August 24.12 14.24
September 22.90 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.12 0.73
May 23.74 10.60
June 24.19 15.96
July 24.27 16.86
August 24.07 14.24
September 22.94 6.72
October 21.74 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.64 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.11 0.73
May 23.75 10.60
June 24.20 15.96
July 24.27 16.86
August 24.08 14.24
September 22.95 6.72
October 21.74 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.64 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.99 -10.3
April 23.27 0.73
May 24.24 10.60
June 24.33 15.96
July 24.34 16.86
August 24.32 14.24
September 23.87 6.72
October 22.26 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.96 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 22.00 -10.3
April 23.28 0.73
May 24.25 10.60
June 24.33 15.96
July 24.34 16.86
August 24.32 14.24
September 23.88 6.72
October 22.27 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.96 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.10 -17.6
February 21.55 -15.4
March 22.14 -10.3
April 23.78 0.73
May 25.68 10.60
June 26.42 15.96
July 26.44 16.86
August 26.03 14.24
September 24.57 6.72
October 22.34 -3.1
November 21.37 -17.6
December 20.97 -19.3
     
Annual Sum or Average 23.54 -1.4
Minimum of Months 20.97 -19.3
Maximum of Months 26.44 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.86 -10.3
April 23.10 0.73
May 24.17 10.60
June 24.35 15.96
July 24.36 16.86
August 24.30 14.24
September 23.62 6.72
October 22.03 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.89 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.29 0.73
May 23.86 10.60
June 24.26 15.96
July 24.32 16.86
August 24.12 14.24
September 22.90 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.91 -10.3
April 23.10 0.73
May 24.20 10.60
June 24.36 15.96
July 24.38 16.86
August 24.32 14.24
September 23.67 6.72
October 22.08 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.38 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.26 0.73
May 23.90 10.60
June 24.27 15.96
July 24.34 16.86
August 24.14 14.24
September 22.96 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.68 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.16 0.73
May 23.85 10.60
June 24.20 15.96
July 24.29 16.86
August 24.10 14.24
September 23.03 6.72
October 21.75 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.66 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.16 0.73
May 23.86 10.60
June 24.20 15.96
July 24.29 16.86
August 24.11 14.24
September 23.05 6.72
October 21.75 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.73 -15.4
March 22.00 -10.3
April 23.29 0.73
May 24.27 10.60
June 24.33 15.96
July 24.35 16.86
August 24.32 14.24
September 23.90 6.72
October 22.29 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.97 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.73 -15.4
March 22.01 -10.3
April 23.30 0.73
May 24.27 10.60
June 24.33 15.96
July 24.35 16.86
August 24.33 14.24
September 23.91 6.72
October 22.30 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.97 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.29 -17.6
February 21.75 -15.4
March 22.33 -10.3
April 23.97 0.73
May 25.89 10.60
June 26.53 15.96
July 26.55 16.86
August 26.16 14.24
September 24.75 6.72
October 22.51 -3.1
November 21.56 -17.6
December 21.16 -19.3
     
Annual Sum or Average 23.72 -1.4
Minimum of Months 21.16 -19.3
Maximum of Months 26.55 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.86 -10.3
April 23.09 0.73
May 24.17 10.60
June 24.34 15.96
July 24.36 16.86
August 24.30 14.24
September 23.63 6.72
October 22.03 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.89 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.30 0.73
May 23.87 10.60
June 24.25 15.96
July 24.32 16.86
August 24.12 14.24
September 22.93 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.68 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.91 -10.3
April 23.10 0.73
May 24.19 10.60
June 24.35 15.96
July 24.38 16.86
August 24.31 14.24
September 23.68 6.72
October 22.08 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.38 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.27 0.73
May 23.90 10.60
June 24.26 15.96
July 24.34 16.86
August 24.14 14.24
September 22.99 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.68 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.19 0.73
May 23.87 10.60
June 24.19 15.96
July 24.29 16.86
August 24.11 14.24
September 23.08 6.72
October 21.75 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.18 0.73
May 23.88 10.60
June 24.19 15.96
July 24.29 16.86
August 24.11 14.24
September 23.10 6.72
October 21.75 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.73 -15.4
March 22.01 -10.3
April 23.30 0.73
May 24.27 10.60
June 24.32 15.96
July 24.35 16.86
August 24.32 14.24
September 23.91 6.72
October 22.30 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.97 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.73 -15.4
March 22.02 -10.3
April 23.30 0.73
May 24.27 10.60
June 24.33 15.96
July 24.35 16.86
August 24.32 14.24
September 23.92 6.72
October 22.31 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.98 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 -17.6
February 22.42 -15.4
March 23.00 -10.3
April 24.60 0.73
May 26.52 10.60
June 27.13 15.96
July 27.16 16.86
August 26.77 14.24
September 25.40 6.72
October 23.18 -3.1
November 22.25 -17.6
December 21.86 -19.3
     
Annual Sum or Average 24.37 -1.4
Minimum of Months 21.86 -19.3
Maximum of Months 27.16 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.85 -10.3
April 23.04 0.73
May 24.13 10.60
June 24.32 15.96
July 24.35 16.86
August 24.28 14.24
September 23.57 6.72
October 21.99 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.87 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.24 0.73
May 23.78 10.60
June 24.21 15.96
July 24.31 16.86
August 24.07 14.24
September 22.83 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.65 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.31 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.88 -10.3
April 23.04 0.73
May 24.15 10.60
June 24.33 15.96
July 24.37 16.86
August 24.29 14.24
September 23.61 6.72
October 22.03 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.88 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.37 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.21 0.73
May 23.83 10.60
June 24.23 15.96
July 24.32 16.86
August 24.09 14.24
September 22.89 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.65 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.13 0.73
May 23.79 10.60
June 24.15 15.96
July 24.27 16.86
August 24.06 14.24
September 22.98 6.72
October 21.74 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.64 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.12 0.73
May 23.80 10.60
June 24.16 15.96
July 24.27 16.86
August 24.06 14.24
September 22.99 6.72
October 21.74 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.64 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.97 -10.3
April 23.24 0.73
May 24.24 10.60
June 24.30 15.96
July 24.34 16.86
August 24.31 14.24
September 23.85 6.72
October 22.25 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.95 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.98 -10.3
April 23.24 0.73
May 24.24 10.60
June 24.31 15.96
July 24.34 16.86
August 24.31 14.24
September 23.86 6.72
October 22.26 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.95 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.29 -17.6
February 21.75 -15.4
March 22.30 -10.3
April 23.90 0.73
May 25.84 10.60
June 26.49 15.96
July 26.53 16.86
August 26.12 14.24
September 24.69 6.72
October 22.47 -3.1
November 21.58 -17.6
December 21.17 -19.3
     
Annual Sum or Average 23.69 -1.4
Minimum of Months 21.17 -19.3
Maximum of Months 26.53 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.83 -10.3
April 22.99 0.73
May 24.10 10.60
June 24.30 15.96
July 24.35 16.86
August 24.26 14.24
September 23.51 6.72
October 21.95 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.85 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.20 0.73
May 23.71 10.60
June 24.19 15.96
July 24.29 16.86
August 24.03 14.24
September 22.74 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.62 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.87 -10.3
April 23.00 0.73
May 24.12 10.60
June 24.32 15.96
July 24.36 16.86
August 24.28 14.24
September 23.56 6.72
October 21.99 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.87 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.16 0.73
May 23.77 10.60
June 24.20 15.96
July 24.31 16.86
August 24.05 14.24
September 22.80 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.63 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.31 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.08 0.73
May 23.71 10.60
June 24.12 15.96
July 24.25 16.86
August 24.02 14.24
September 22.88 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.61 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.25 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.08 0.73
May 23.72 10.60
June 24.13 15.96
July 24.26 16.86
August 24.02 14.24
September 22.90 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.62 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.26 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.95 -10.3
April 23.19 0.73
May 24.20 10.60
June 24.29 15.96
July 24.33 16.86
August 24.29 14.24
September 23.80 6.72
October 22.20 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.93 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.96 -10.3
April 23.20 0.73
May 24.21 10.60
June 24.29 15.96
July 24.33 16.86
August 24.30 14.24
September 23.81 6.72
October 22.21 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.93 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 -17.6
February 21.62 -15.4
March 22.16 -10.3
April 23.74 0.73
May 25.68 10.60
June 26.37 15.96
July 26.43 16.86
August 25.99 14.24
September 24.51 6.72
October 22.32 -3.1
November 21.46 -17.6
December 21.04 -19.3
     
Annual Sum or Average 23.55 -1.4
Minimum of Months 21.04 -19.3
Maximum of Months 26.43 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.82 -10.3
April 22.95 0.73
May 24.07 10.60
June 24.29 15.96
July 24.34 16.86
August 24.24 14.24
September 23.46 6.72
October 21.92 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.83 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.34 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.16 0.73
May 23.64 10.60
June 24.16 15.96
July 24.28 16.86
August 23.99 14.24
September 22.65 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.60 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.28 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.85 -10.3
April 22.97 0.73
May 24.09 10.60
June 24.31 15.96
July 24.36 16.86
August 24.26 14.24
September 23.50 6.72
October 21.96 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.85 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.13 0.73
May 23.71 10.60
June 24.18 15.96
July 24.30 16.86
August 24.01 14.24
September 22.70 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.61 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.30 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.05 0.73
May 23.63 10.60
June 24.10 15.96
July 24.24 16.86
August 23.98 14.24
September 22.77 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.59 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.24 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.05 0.73
May 23.64 10.60
June 24.10 15.96
July 24.24 16.86
August 23.98 14.24
September 22.78 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.59 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.24 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.93 -10.3
April 23.15 0.73
May 24.17 10.60
June 24.27 15.96
July 24.33 16.86
August 24.28 14.24
September 23.74 6.72
October 22.15 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.93 -10.3
April 23.15 0.73
May 24.18 10.60
June 24.28 15.96
July 24.33 16.86
August 24.28 14.24
September 23.75 6.72
October 22.16 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.91 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.09 -17.6
February 21.53 -15.4
March 22.06 -10.3
April 23.64 0.73
May 25.58 10.60
June 26.33 15.96
July 26.41 16.86
August 25.94 14.24
September 24.37 6.72
October 22.21 -3.1
November 21.38 -17.6
December 20.96 -19.3
     
Annual Sum or Average 23.47 -1.4
Minimum of Months 20.96 -19.3
Maximum of Months 26.41 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.81 -10.3
April 22.88 0.73
May 24.00 10.60
June 24.27 15.96
July 24.33 16.86
August 24.21 14.24
September 23.34 6.72
October 21.87 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.80 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.12 0.73
May 23.53 10.60
June 24.14 15.96
July 24.27 16.86
August 23.93 14.24
September 22.51 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.57 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.83 -10.3
April 22.90 0.73
May 24.04 10.60
June 24.29 15.96
July 24.36 16.86
August 24.23 14.24
September 23.38 6.72
October 21.90 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.82 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.36 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.10 0.73
May 23.63 10.60
June 24.15 15.96
July 24.29 16.86
August 23.94 14.24
September 22.55 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.58 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.02 0.73
May 23.52 10.60
June 24.07 15.96
July 24.23 16.86
August 23.91 14.24
September 22.59 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.55 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.23 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.02 0.73
May 23.54 10.60
June 24.08 15.96
July 24.23 16.86
August 23.91 14.24
September 22.61 6.72
October 21.72 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.56 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.23 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.89 -10.3
April 23.06 0.73
May 24.11 10.60
June 24.26 15.96
July 24.32 16.86
August 24.26 14.24
September 23.61 6.72
October 22.07 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.87 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.89 -10.3
April 23.07 0.73
May 24.11 10.60
June 24.26 15.96
July 24.32 16.86
August 24.26 14.24
September 23.62 6.72
October 22.07 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.87 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.79 -17.6
February 21.25 -15.4
March 21.82 -10.3
April 23.46 0.73
May 25.44 10.60
June 26.33 15.96
July 26.42 16.86
August 25.87 14.24
September 24.12 6.72
October 21.98 -3.1
November 21.08 -17.6
December 20.66 -19.3
     
Annual Sum or Average 23.28 -1.4
Minimum of Months 20.66 -19.3
Maximum of Months 26.42 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.85 -10.3
April 22.66 0.73
May 23.56 10.60
June 24.16 15.96
July 24.27 16.86
August 24.01 14.24
September 22.91 6.72
October 21.83 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.68 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.27 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.71 -10.3
April 22.16 0.73
May 23.22 10.60
June 24.01 15.96
July 24.18 16.86
August 23.70 14.24
September 22.33 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.49 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.18 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.87 -10.3
April 22.68 0.73
May 23.63 10.60
June 24.18 15.96
July 24.29 16.86
August 24.04 14.24
September 22.96 6.72
October 21.85 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.70 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.29 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.71 -10.3
April 22.14 0.73
May 23.31 10.60
June 23.99 15.96
July 24.17 16.86
August 23.68 14.24
September 22.35 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.49 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.17 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.06 0.73
May 23.17 10.60
June 23.95 15.96
July 24.13 16.86
August 23.65 14.24
September 22.31 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.13 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.05 0.73
May 23.18 10.60
June 23.95 15.96
July 24.13 16.86
August 23.65 14.24
September 22.31 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.13 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.92 -10.3
April 22.76 0.73
May 23.72 10.60
June 24.18 15.96
July 24.28 16.86
August 24.11 14.24
September 23.15 6.72
October 21.94 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.75 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.28 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.72 -15.4
March 21.93 -10.3
April 22.76 0.73
May 23.73 10.60
June 24.19 15.96
July 24.28 16.86
August 24.11 14.24
September 23.15 6.72
October 21.94 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.75 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.28 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:12

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.81 -17.6
February 20.38 -15.4
March 21.30 -10.3
April 23.39 0.73
May 25.61 10.60
June 26.86 15.96
July 26.97 16.86
August 26.16 14.24
September 23.95 6.72
October 21.57 -3.1
November 20.04 -17.6
December 19.61 -19.3
     
Annual Sum or Average 22.99 -1.4
Minimum of Months 19.61 -19.3
Maximum of Months 26.97 16.86



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:12

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.330807E+12 212165.244 28-JAN-23:00 9687.493 29146.786 20785.106 139844.757 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.275646E+12 181916.998 23-FEB-18:00 22204.399 56867.515 20785.106 68750.732 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.270900E+12 147395.837 02-MAR-07:00 14239.096 40658.501 20785.106 58936.037 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.227255E+12 141022.346 02-APR-19:00 25049.151 49704.829 20785.106 32374.331 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.221765E+12 141023.760 31-MAY-17:15 22204.399 56867.515 20785.106 0.000 37357.518 0.000 1443.258 1220.328 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.231845E+12 160896.699 20-JUN-17:15 22204.399 56867.515 20785.106 0.000 56603.269 0.000 1443.258 1847.516 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.248951E+12 163016.961 11-JUL-17:15 22204.399 56867.515 20785.106 0.000 58650.281 0.000 1443.258 1920.766 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.234383E+12 160656.534 11-AUG-17:15 22204.399 56867.515 20785.106 0.000 56386.568 0.000 1443.258 1824.052 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.212999E+12 124580.558 08-SEP-17:15 22204.399 56867.515 20785.106 0.000 21346.171 0.000 1443.258 788.473 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.255827E+12 144518.302 30-OCT-19:00 25049.151 49704.829 20785.106 35870.287 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.299231E+12 165590.040 27-NOV-18:00 22204.399 56867.515 20785.106 52423.774 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.334095E+12 175181.031 15-DEC-17:00 18221.747 56933.809 20785.106 65928.569 0.000 10720.100 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.314370E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.212999E+12 124580.558   9687.493 29146.786 20785.106 0.000 0.000 0.000 1443.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.334095E+12 212165.244   25049.151 56933.809 20785.106 139844.757 58650.281 10720.100 1443.258 1920.766 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:12

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.530012E+12 317067.558 29-JAN-08:15 0.000 0.000 0.000 317067.558 95799.498 95799.498 221268.060
February 0.415445E+12 312146.566 24-FEB-08:00 0.000 0.000 0.000 312146.566 94509.378 94509.378 217637.188
March 0.363470E+12 284814.468 02-MAR-07:00 0.000 0.000 0.000 284814.468 96848.250 96848.250 187966.219
April 0.200030E+12 250714.235 02-APR-06:00 0.000 0.000 0.000 250714.235 96848.005 96848.005 153866.230
May 0.132126E+12 116486.430 27-MAY-07:45 0.000 0.000 0.000 116486.430 93543.817 93543.817 22942.613
June 0.121621E+12 95362.514 01-JUN-06:00 0.000 0.000 0.000 95362.514 95362.514 95362.514 0.000
July 0.121024E+12 93134.745 01-JUL-06:00 0.000 0.000 0.000 93134.745 93134.745 93134.745 0.000
August 0.118047E+12 91480.430 01-AUG-06:00 0.000 0.000 0.000 91480.430 91480.430 91480.430 0.000
September 0.127170E+12 148223.112 28-SEP-06:00 0.000 0.000 0.000 148223.112 91121.540 91121.540 57101.572
October 0.285880E+12 261284.082 31-OCT-07:15 0.000 0.000 0.000 261284.082 91646.596 91646.596 169637.486
November 0.468362E+12 299230.905 29-NOV-07:00 0.000 0.000 0.000 299230.905 94616.098 94616.098 204614.807
December 0.552318E+12 309979.907 15-DEC-09:45 0.000 0.000 0.000 309979.907 87625.421 87625.421 222354.486
                     
Annual Sum or Average 0.343551E+13     0.000 0.000 0.000        
Minimum of Months 0.118047E+12 91480.430   0.000 0.000 0.000 91480.430 87625.421 87625.421 0.000
Maximum of Months 0.552318E+12 317067.558   0.000 0.000 0.000 317067.558 96848.250 96848.250 222354.486