Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2018-10-19 09:40:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4274.69 | 545.49 | 605.49 |
Net Site Energy | 4274.69 | 545.49 | 605.49 |
Total Source Energy | 11052.84 | 1410.43 | 1565.58 |
Net Source Energy | 11052.84 | 1410.43 | 1565.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 39.47 | 85.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 543.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 699.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 43.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1823.67 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1107.29 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3081.65 | 1193.04 | 0.00 | 0.00 | 0.00 | 6602.18 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 85.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 543.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 699.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 43.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 19.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1823.67 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1107.29 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.50 | 168.99 | 0.00 | 0.00 | 0.00 | 0.94 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 436.50 | 168.99 | 0.00 | 0.00 | 0.00 | 0.94 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 171.62 | 152.24 | 0.00 | 0.00 | 0.00 | 0.84 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 393.24 | 152.24 | 0.00 | 0.00 | 0.00 | 0.84 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3081.65 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3081.65 | 100.00 |
Total On-Site and Utility Electric Sources | 3081.65 | 100.00 |
Total Electricity End Uses | 3081.65 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6602.18 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6602.18 | 100.00 |
Total Water End Uses | 6602.18 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.00 |
Time Setpoint Not Met During Occupied Cooling | 592.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1030.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:15 | 17-JAN-07:00 | - | - | - | 21-JUL-17:15 |
Heating | 0.00 | 87410.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59469.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22185.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1393.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1879.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 86775.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 171347.37 | 174185.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 87410.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 59469.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22185.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1393.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1879.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 86775.67 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 125.00 | 92.95 | 0.00 | 0.00 | 0.00 |
Cooling | 1719.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2215.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 138.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1200.30 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9759.58 | 1293.26 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 17.71 | 13.17 | 0.00 | 0.00 | 0.00 |
Cooling | 243.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 313.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 170.02 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1382.40 | 183.18 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 17.71 | 13.17 | 0.00 | 0.00 | 0.00 |
Cooling | 243.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 313.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 170.02 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1382.40 | 183.18 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.70 | 83.70 | 168.44 | |
Exterior Lighting Total | 10720.10 | 168.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 244450.99 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 195560.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3205.74 | 2069.43 | 1136.32 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3148.90 | 2033.46 | 1115.44 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4016.33 | 2614.97 | 1401.35 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2247.30 | 1476.51 | 770.79 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1649.01 | 1075.73 | 573.28 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1624.43 | 1060.20 | 564.23 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1773.44 | 1138.37 | 635.07 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1845.11 | 1184.20 | 660.92 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4097.56 | 2645.61 | 1451.95 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3998.19 | 2581.99 | 1416.20 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3602.22 | 2322.51 | 1279.72 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2973.18 | 1948.25 | 1024.93 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2184.74 | 1419.81 | 764.93 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2164.71 | 1407.14 | 757.57 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2347.31 | 1509.03 | 838.28 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2369.96 | 1524.60 | 845.36 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4106.84 | 2657.32 | 1449.53 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4016.93 | 2599.68 | 1417.24 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3400.35 | 2199.59 | 1200.76 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3010.14 | 1977.45 | 1032.69 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2227.65 | 1450.30 | 777.35 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2207.81 | 1437.74 | 770.07 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2391.41 | 1540.41 | 851.00 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2400.81 | 1547.54 | 853.27 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4117.02 | 2668.14 | 1448.88 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4028.65 | 2611.48 | 1417.17 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3395.33 | 2200.57 | 1194.76 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3034.38 | 1994.12 | 1040.26 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2247.30 | 1465.24 | 782.06 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2227.55 | 1452.73 | 774.82 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2410.14 | 1554.80 | 855.34 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2417.30 | 1560.51 | 856.78 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4158.84 | 2698.28 | 1460.56 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4072.71 | 2643.02 | 1429.70 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3439.66 | 2232.22 | 1207.44 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3077.10 | 2024.77 | 1052.33 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2295.42 | 1497.75 | 797.67 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2275.75 | 1485.29 | 790.46 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2456.49 | 1586.38 | 870.11 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2463.12 | 1591.76 | 871.36 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4107.38 | 2668.62 | 1438.77 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4020.59 | 2612.95 | 1407.64 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3398.79 | 2207.99 | 1190.80 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3025.97 | 1995.13 | 1030.84 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2250.64 | 1471.15 | 779.48 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2231.12 | 1458.78 | 772.33 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2412.06 | 1559.73 | 852.34 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2418.41 | 1564.94 | 853.47 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4090.25 | 2660.39 | 1429.85 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4004.31 | 2605.28 | 1399.03 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3386.97 | 2203.00 | 1183.97 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3009.82 | 1987.41 | 1022.41 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2239.43 | 1465.59 | 773.83 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2220.02 | 1453.29 | 766.73 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2399.99 | 1553.51 | 846.47 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2406.11 | 1558.60 | 847.52 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4093.59 | 2664.92 | 1428.67 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4008.49 | 2610.33 | 1398.16 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3393.58 | 2209.50 | 1184.08 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3012.60 | 1991.48 | 1021.11 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2248.14 | 1472.49 | 775.65 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2228.86 | 1460.27 | 768.60 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2406.58 | 1559.07 | 847.51 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2412.52 | 1564.04 | 848.48 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4235.91 | 2757.64 | 1478.27 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4151.08 | 2703.15 | 1447.93 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3496.63 | 2277.35 | 1219.28 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3063.96 | 2026.37 | 1037.59 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2375.11 | 1554.21 | 820.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2355.64 | 1541.86 | 813.78 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2496.23 | 1617.52 | 878.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2507.13 | 1624.55 | 882.58 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5241.32 | 3395.82 | 1845.50 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5079.47 | 3295.62 | 1783.85 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4495.28 | 2915.56 | 1579.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3904.45 | 2557.56 | 1346.89 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3104.20 | 2006.55 | 1097.65 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3100.56 | 2004.20 | 1096.36 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3617.14 | 2333.28 | 1283.86 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3623.11 | 2338.17 | 1284.94 | 0.65 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3205.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3148.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4016.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2247.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1649.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1624.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1773.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1845.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4097.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3998.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3602.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2973.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2184.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2164.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2347.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2369.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4106.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4016.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3400.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3010.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2227.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2207.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2391.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2400.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4117.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4028.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3395.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3034.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2247.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2227.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2410.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2417.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4158.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4072.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3439.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3077.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2295.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2275.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2456.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2463.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4107.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4020.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3398.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3025.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2250.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2231.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2412.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2418.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4090.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4004.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3386.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3009.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2239.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2220.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2399.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2406.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4093.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4008.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3393.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3012.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2248.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2228.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2406.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2412.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4235.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4151.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3496.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3063.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2375.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2355.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2496.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2507.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5241.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5079.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4495.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3904.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3104.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3100.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3617.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3623.11 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2438.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2437.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3204.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2437.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1803.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1803.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1801.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1809.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2417.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2415.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2442.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2415.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1636.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1636.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1641.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1643.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2408.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2408.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2410.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2408.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1603.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1603.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1603.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1603.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2437.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2440.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2437.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2440.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1613.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1613.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1611.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1611.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2444.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2447.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2444.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2447.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1605.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1605.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1603.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1603.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2518.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2524.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2518.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2524.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1664.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1664.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1659.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1659.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2566.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2571.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2566.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2571.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1699.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1699.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1693.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1693.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2617.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2623.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2617.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2623.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1739.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1739.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1733.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1733.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2787.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2791.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2787.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2791.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1889.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1889.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1885.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1885.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3391.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3402.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3391.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3402.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2545.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2545.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2531.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2531.48 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.01 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 285.64 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 367.07 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.20 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 148.94 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 146.71 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 152.70 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 159.27 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 373.65 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.28 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.30 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 276.83 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.70 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.88 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.97 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.45 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 375.65 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 368.14 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 306.86 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.34 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.27 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.46 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.65 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 211.92 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 377.44 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 370.07 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.22 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.19 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.55 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.75 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 212.85 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.91 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 381.97 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 374.81 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 311.97 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 287.80 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.34 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.54 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 217.50 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 218.52 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 377.85 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 370.62 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 308.37 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.66 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 206.60 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.82 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.75 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 214.74 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 376.80 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 369.66 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.78 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.68 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.88 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.11 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 212.93 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.91 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 377.58 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 370.51 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 308.84 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.38 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 206.94 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.18 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.80 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 214.76 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 391.09 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 384.03 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 318.74 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 288.54 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 218.78 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 217.00 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 222.28 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 223.29 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 481.77 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 468.45 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 410.99 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 363.83 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.40 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.06 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 325.52 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 326.49 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0053 | 1356.10 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2266.20 | 2719.44 | 0.216 | 0.259 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
G NW APARTMENT | 2232.07 | 2678.49 | 0.213 | 0.255 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
OFFICE | 2868.46 | 3442.15 | 0.273 | 0.328 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.00 | 0.00565 |
G NE APARTMENT | 1626.96 | 1952.35 | 0.155 | 0.186 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 30.48 | 0.00565 |
G N1 APARTMENT | 1163.88 | 1396.65 | 0.111 | 0.133 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
G N2 APARTMENT | 1146.45 | 1375.74 | 0.109 | 0.131 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
G S1 APARTMENT | 1193.20 | 1431.83 | 0.114 | 0.136 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
G S2 APARTMENT | 1244.54 | 1493.45 | 0.118 | 0.142 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F2 SW APARTMENT | 2919.83 | 3503.80 | 0.278 | 0.334 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F2 NW APARTMENT | 2854.39 | 3425.27 | 0.272 | 0.326 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F2 SE APARTMENT | 2534.22 | 3041.07 | 0.241 | 0.290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76 | 0.00565 |
F2 NE APARTMENT | 2163.28 | 2595.93 | 0.206 | 0.247 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 30.48 | 0.00565 |
F2 N1 APARTMENT | 1552.71 | 1863.25 | 0.148 | 0.177 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F2 N2 APARTMENT | 1538.46 | 1846.15 | 0.146 | 0.176 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F2 S1 APARTMENT | 1609.47 | 1931.37 | 0.153 | 0.184 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F2 S2 APARTMENT | 1628.88 | 1954.66 | 0.155 | 0.186 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F3 SW APARTMENT | 2935.44 | 3522.53 | 0.279 | 0.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F3 NW APARTMENT | 2876.74 | 3452.09 | 0.274 | 0.329 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F3 SE APARTMENT | 2397.97 | 2877.57 | 0.228 | 0.274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76 | 0.00565 |
F3 NE APARTMENT | 2198.53 | 2638.24 | 0.209 | 0.251 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 30.48 | 0.00565 |
F3 N1 APARTMENT | 1588.37 | 1906.05 | 0.151 | 0.181 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F3 N2 APARTMENT | 1574.24 | 1889.09 | 0.150 | 0.180 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F3 S1 APARTMENT | 1646.07 | 1975.28 | 0.157 | 0.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F3 S2 APARTMENT | 1656.00 | 1987.21 | 0.158 | 0.189 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F4 SW APARTMENT | 2949.45 | 3539.34 | 0.281 | 0.337 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F4 NW APARTMENT | 2891.84 | 3470.21 | 0.275 | 0.330 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F4 SE APARTMENT | 2400.78 | 2880.94 | 0.229 | 0.274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76 | 0.00565 |
F4 NE APARTMENT | 2212.97 | 2655.56 | 0.211 | 0.253 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F4 N1 APARTMENT | 1606.21 | 1927.45 | 0.153 | 0.184 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F4 N2 APARTMENT | 1592.13 | 1910.56 | 0.152 | 0.182 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F4 S1 APARTMENT | 1663.25 | 1995.90 | 0.158 | 0.190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F4 S2 APARTMENT | 1671.60 | 2005.92 | 0.159 | 0.191 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
M SW APARTMENT | 2984.92 | 3581.91 | 0.284 | 0.341 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
M NW APARTMENT | 2928.88 | 3514.66 | 0.279 | 0.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
M SE APARTMENT | 2437.87 | 2925.44 | 0.232 | 0.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76 | 0.00565 |
M NE APARTMENT | 2248.97 | 2698.77 | 0.214 | 0.257 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
M N1 APARTMENT | 1643.64 | 1972.36 | 0.156 | 0.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
M N2 APARTMENT | 1629.61 | 1955.53 | 0.155 | 0.186 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
M S1 APARTMENT | 1699.59 | 2039.51 | 0.162 | 0.194 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
M S2 APARTMENT | 1707.57 | 2049.08 | 0.163 | 0.195 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F6 SW APARTMENT | 2952.70 | 3543.24 | 0.281 | 0.337 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F6 NW APARTMENT | 2896.21 | 3475.45 | 0.276 | 0.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F6 SE APARTMENT | 2409.73 | 2891.68 | 0.229 | 0.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F6 NE APARTMENT | 2216.68 | 2660.01 | 0.211 | 0.253 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F6 N1 APARTMENT | 1614.42 | 1937.30 | 0.154 | 0.184 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F6 N2 APARTMENT | 1600.49 | 1920.59 | 0.152 | 0.183 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F6 S1 APARTMENT | 1670.30 | 2004.36 | 0.159 | 0.191 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F6 S2 APARTMENT | 1678.09 | 2013.71 | 0.160 | 0.192 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F7 SW APARTMENT | 2944.52 | 3533.42 | 0.280 | 0.336 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F7 NW APARTMENT | 2888.65 | 3466.38 | 0.275 | 0.330 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F7 SE APARTMENT | 2405.15 | 2886.18 | 0.229 | 0.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F7 NE APARTMENT | 2208.99 | 2650.79 | 0.210 | 0.252 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F7 N1 APARTMENT | 1608.79 | 1930.54 | 0.153 | 0.184 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F7 N2 APARTMENT | 1594.94 | 1913.92 | 0.152 | 0.182 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F7 S1 APARTMENT | 1663.92 | 1996.71 | 0.158 | 0.190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F7 S2 APARTMENT | 1671.57 | 2005.88 | 0.159 | 0.191 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F8 SW APARTMENT | 2950.61 | 3540.73 | 0.281 | 0.337 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F8 NW APARTMENT | 2895.33 | 3474.40 | 0.276 | 0.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F8 SE APARTMENT | 2413.41 | 2896.09 | 0.230 | 0.276 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F8 NE APARTMENT | 2214.53 | 2657.43 | 0.211 | 0.253 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F8 N1 APARTMENT | 1617.11 | 1940.54 | 0.154 | 0.185 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F8 N2 APARTMENT | 1603.35 | 1924.02 | 0.153 | 0.183 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F8 S1 APARTMENT | 1670.72 | 2004.86 | 0.159 | 0.191 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F8 S2 APARTMENT | 1678.24 | 2013.89 | 0.160 | 0.192 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F9 SW APARTMENT | 3056.15 | 3667.38 | 0.291 | 0.349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F9 NW APARTMENT | 3000.97 | 3601.17 | 0.286 | 0.343 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F9 SE APARTMENT | 2490.81 | 2988.97 | 0.237 | 0.285 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F9 NE APARTMENT | 2254.79 | 2705.75 | 0.215 | 0.258 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F9 N1 APARTMENT | 1709.64 | 2051.57 | 0.163 | 0.195 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F9 N2 APARTMENT | 1695.73 | 2034.87 | 0.161 | 0.194 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F9 S1 APARTMENT | 1736.97 | 2084.36 | 0.165 | 0.198 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 35.10 | 0.00565 |
F9 S2 APARTMENT | 1744.91 | 2093.90 | 0.166 | 0.199 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
T SW APARTMENT | 3764.81 | 4517.77 | 0.358 | 0.430 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 34.02 | 0.00565 |
T NW APARTMENT | 3660.74 | 4392.88 | 0.349 | 0.418 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21 | 0.00565 |
T SE APARTMENT | 3211.70 | 3854.04 | 0.306 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
T NE APARTMENT | 2843.22 | 3411.87 | 0.271 | 0.325 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.00 | 0.00565 |
T N1 APARTMENT | 2175.55 | 2610.66 | 0.207 | 0.249 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
T N2 APARTMENT | 2172.89 | 2607.47 | 0.207 | 0.248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
T S1 APARTMENT | 2543.78 | 3052.53 | 0.242 | 0.291 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
T S2 APARTMENT | 2551.30 | 3061.56 | 0.243 | 0.291 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1415.34 | 1698.40 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G NW APARTMENT | 1414.58 | 1697.50 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
OFFICE | 1760.83 | 2113.00 | 0.095 | 0.114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -7.90 | 0.00234 |
G NE APARTMENT | 1414.58 | 1697.50 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G N1 APARTMENT | 878.91 | 1054.69 | 0.048 | 0.057 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G N2 APARTMENT | 878.91 | 1054.69 | 0.048 | 0.057 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G S1 APARTMENT | 876.59 | 1051.90 | 0.047 | 0.057 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G S2 APARTMENT | 883.79 | 1060.54 | 0.048 | 0.057 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
F2 SW APARTMENT | 1397.78 | 1677.34 | 0.076 | 0.091 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 NW APARTMENT | 1395.81 | 1674.97 | 0.076 | 0.091 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 SE APARTMENT | 1419.32 | 1703.19 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 NE APARTMENT | 1395.81 | 1674.97 | 0.076 | 0.091 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 N1 APARTMENT | 737.36 | 884.84 | 0.040 | 0.048 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 N2 APARTMENT | 737.36 | 884.84 | 0.040 | 0.048 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 S1 APARTMENT | 741.62 | 889.94 | 0.040 | 0.048 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 S2 APARTMENT | 743.06 | 891.67 | 0.040 | 0.048 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 SW APARTMENT | 1389.93 | 1667.91 | 0.075 | 0.090 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 NW APARTMENT | 1390.46 | 1668.55 | 0.075 | 0.090 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 SE APARTMENT | 1392.33 | 1670.80 | 0.075 | 0.090 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 NE APARTMENT | 1390.46 | 1668.55 | 0.075 | 0.090 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 N1 APARTMENT | 709.56 | 851.47 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 N2 APARTMENT | 709.56 | 851.47 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 S1 APARTMENT | 709.66 | 851.59 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 S2 APARTMENT | 709.89 | 851.86 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 SW APARTMENT | 1414.80 | 1697.75 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 NW APARTMENT | 1417.11 | 1700.53 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 SE APARTMENT | 1415.05 | 1698.06 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 NE APARTMENT | 1417.11 | 1700.53 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 N1 APARTMENT | 717.91 | 861.49 | 0.039 | 0.047 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 N2 APARTMENT | 717.91 | 861.49 | 0.039 | 0.047 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 S1 APARTMENT | 716.00 | 859.20 | 0.039 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 S2 APARTMENT | 716.03 | 859.23 | 0.039 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M SW APARTMENT | 1420.35 | 1704.42 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M NW APARTMENT | 1422.94 | 1707.52 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M SE APARTMENT | 1420.37 | 1704.45 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M NE APARTMENT | 1422.94 | 1707.52 | 0.077 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M N1 APARTMENT | 711.36 | 853.64 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M N2 APARTMENT | 711.36 | 853.64 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M S1 APARTMENT | 709.12 | 850.95 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M S2 APARTMENT | 709.13 | 850.95 | 0.038 | 0.046 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 SW APARTMENT | 1483.70 | 1780.44 | 0.080 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 NW APARTMENT | 1488.05 | 1785.66 | 0.081 | 0.097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 SE APARTMENT | 1483.70 | 1780.44 | 0.080 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 NE APARTMENT | 1488.05 | 1785.66 | 0.081 | 0.097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 N1 APARTMENT | 761.12 | 913.34 | 0.041 | 0.049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 N2 APARTMENT | 761.12 | 913.34 | 0.041 | 0.049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 S1 APARTMENT | 757.06 | 908.47 | 0.041 | 0.049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 S2 APARTMENT | 757.06 | 908.47 | 0.041 | 0.049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 SW APARTMENT | 1523.49 | 1828.19 | 0.082 | 0.099 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 NW APARTMENT | 1528.44 | 1834.12 | 0.083 | 0.099 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 SE APARTMENT | 1523.49 | 1828.19 | 0.082 | 0.099 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 NE APARTMENT | 1528.44 | 1834.12 | 0.083 | 0.099 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 N1 APARTMENT | 790.33 | 948.40 | 0.043 | 0.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 N2 APARTMENT | 790.33 | 948.40 | 0.043 | 0.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 S1 APARTMENT | 785.64 | 942.76 | 0.043 | 0.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 S2 APARTMENT | 785.64 | 942.76 | 0.043 | 0.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 SW APARTMENT | 1566.67 | 1880.01 | 0.085 | 0.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 NW APARTMENT | 1571.93 | 1886.31 | 0.085 | 0.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 SE APARTMENT | 1566.67 | 1880.01 | 0.085 | 0.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 NE APARTMENT | 1571.93 | 1886.31 | 0.085 | 0.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 N1 APARTMENT | 824.29 | 989.15 | 0.045 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 N2 APARTMENT | 824.29 | 989.15 | 0.045 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 S1 APARTMENT | 819.25 | 983.10 | 0.044 | 0.053 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 S2 APARTMENT | 819.25 | 983.10 | 0.044 | 0.053 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 SW APARTMENT | 1710.73 | 2052.88 | 0.093 | 0.111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 NW APARTMENT | 1714.29 | 2057.14 | 0.093 | 0.111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 SE APARTMENT | 1710.73 | 2052.88 | 0.093 | 0.111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 NE APARTMENT | 1714.29 | 2057.14 | 0.093 | 0.111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 N1 APARTMENT | 951.39 | 1141.66 | 0.051 | 0.062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 N2 APARTMENT | 951.39 | 1141.66 | 0.051 | 0.062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 S1 APARTMENT | 947.61 | 1137.13 | 0.051 | 0.062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 S2 APARTMENT | 947.61 | 1137.13 | 0.051 | 0.062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T SW APARTMENT | 2221.57 | 2665.88 | 0.120 | 0.144 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T NW APARTMENT | 2230.81 | 2676.98 | 0.121 | 0.145 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T SE APARTMENT | 2221.57 | 2665.88 | 0.120 | 0.144 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T NE APARTMENT | 2230.81 | 2676.98 | 0.121 | 0.145 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T N1 APARTMENT | 1506.11 | 1807.33 | 0.081 | 0.098 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T N2 APARTMENT | 1506.11 | 1807.33 | 0.081 | 0.098 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T S1 APARTMENT | 1494.26 | 1793.12 | 0.081 | 0.097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T S2 APARTMENT | 1494.26 | 1793.12 | 0.081 | 0.097 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP G NW | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP OFFICE | 0.33 | 0.33 | 0.11 | 0.11 |
AIRLOOP G NE | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP G N1 | 0.13 | 0.13 | 0.06 | 0.06 |
AIRLOOP G N2 | 0.13 | 0.13 | 0.06 | 0.06 |
AIRLOOP G S1 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP G S2 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP F2 SW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP F2 NW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP F2 SE | 0.29 | 0.29 | 0.09 | 0.09 |
AIRLOOP F2 NE | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F2 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F3 SW | 0.34 | 0.34 | 0.09 | 0.09 |
AIRLOOP F3 NW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP F3 SE | 0.27 | 0.27 | 0.09 | 0.09 |
AIRLOOP F3 NE | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F3 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F3 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F3 S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F3 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F4 SW | 0.34 | 0.34 | 0.09 | 0.09 |
AIRLOOP F4 NW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP F4 SE | 0.27 | 0.27 | 0.09 | 0.09 |
AIRLOOP F4 NE | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F4 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F4 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F4 S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F4 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M SW | 0.34 | 0.34 | 0.09 | 0.09 |
AIRLOOP M NW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP M SE | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP M NE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP M N1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M N2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M S2 | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F6 SW | 0.34 | 0.34 | 0.10 | 0.10 |
AIRLOOP F6 NW | 0.33 | 0.33 | 0.10 | 0.10 |
AIRLOOP F6 SE | 0.28 | 0.28 | 0.10 | 0.10 |
AIRLOOP F6 NE | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F6 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F6 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F6 S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F6 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F7 SW | 0.34 | 0.34 | 0.10 | 0.10 |
AIRLOOP F7 NW | 0.33 | 0.33 | 0.10 | 0.10 |
AIRLOOP F7 SE | 0.27 | 0.27 | 0.10 | 0.10 |
AIRLOOP F7 NE | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F7 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F7 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F8 SW | 0.34 | 0.34 | 0.10 | 0.10 |
AIRLOOP F8 NW | 0.33 | 0.33 | 0.10 | 0.10 |
AIRLOOP F8 SE | 0.28 | 0.28 | 0.10 | 0.10 |
AIRLOOP F8 NE | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F8 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F8 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F9 SW | 0.35 | 0.35 | 0.11 | 0.11 |
AIRLOOP F9 NW | 0.34 | 0.34 | 0.11 | 0.11 |
AIRLOOP F9 SE | 0.28 | 0.28 | 0.11 | 0.11 |
AIRLOOP F9 NE | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F9 N1 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F9 N2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F9 S1 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F9 S2 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP T SW | 0.43 | 0.43 | 0.14 | 0.14 |
AIRLOOP T NW | 0.42 | 0.42 | 0.14 | 0.14 |
AIRLOOP T SE | 0.37 | 0.37 | 0.14 | 0.14 |
AIRLOOP T NE | 0.32 | 0.32 | 0.14 | 0.14 |
AIRLOOP T N1 | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP T N2 | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP T S1 | 0.29 | 0.29 | 0.10 | 0.10 |
AIRLOOP T S2 | 0.29 | 0.29 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2925.75 | 4649.25 | 294.25 |
G NW APARTMENT | 2651.50 | 5764.00 | 406.75 |
OFFICE | 939.25 | 518.75 | 1.25 |
G NE APARTMENT | 2752.75 | 5701.50 | 445.00 |
G N1 APARTMENT | 2413.75 | 6123.75 | 445.25 |
G N2 APARTMENT | 2417.75 | 6119.50 | 447.75 |
G S1 APARTMENT | 2767.25 | 4979.25 | 364.25 |
G S2 APARTMENT | 2794.50 | 4903.75 | 355.25 |
F2 SW APARTMENT | 3772.50 | 2740.75 | 150.00 |
F2 NW APARTMENT | 3067.00 | 4746.50 | 182.00 |
F2 SE APARTMENT | 3942.25 | 2563.50 | 114.75 |
F2 NE APARTMENT | 3188.75 | 4686.25 | 190.75 |
F2 N1 APARTMENT | 2865.00 | 5108.50 | 239.75 |
F2 N2 APARTMENT | 2873.25 | 5102.50 | 239.00 |
F2 S1 APARTMENT | 3724.75 | 2558.50 | 191.25 |
F2 S2 APARTMENT | 3740.75 | 2531.00 | 188.50 |
F3 SW APARTMENT | 3936.75 | 2405.75 | 148.25 |
F3 NW APARTMENT | 3149.00 | 4482.25 | 174.00 |
F3 SE APARTMENT | 4025.00 | 2396.25 | 124.00 |
F3 NE APARTMENT | 3244.50 | 4460.50 | 176.00 |
F3 N1 APARTMENT | 2983.50 | 4748.00 | 215.75 |
F3 N2 APARTMENT | 2989.50 | 4745.50 | 216.00 |
F3 S1 APARTMENT | 3999.50 | 2047.50 | 180.00 |
F3 S2 APARTMENT | 4002.75 | 2042.75 | 178.75 |
F4 SW APARTMENT | 3968.50 | 2374.75 | 150.75 |
F4 NW APARTMENT | 3161.50 | 4407.00 | 175.00 |
F4 SE APARTMENT | 4035.75 | 2393.00 | 128.00 |
F4 NE APARTMENT | 3259.75 | 4406.25 | 175.50 |
F4 N1 APARTMENT | 3007.50 | 4626.75 | 212.25 |
F4 N2 APARTMENT | 3017.25 | 4623.25 | 212.00 |
F4 S1 APARTMENT | 4057.00 | 1948.00 | 177.75 |
F4 S2 APARTMENT | 4058.25 | 1947.75 | 176.50 |
M SW APARTMENT | 3976.00 | 2368.50 | 149.00 |
M NW APARTMENT | 3171.75 | 4374.00 | 172.50 |
M SE APARTMENT | 4034.50 | 2388.25 | 128.50 |
M NE APARTMENT | 3272.00 | 4385.00 | 173.50 |
M N1 APARTMENT | 3028.75 | 4556.50 | 205.00 |
M N2 APARTMENT | 3038.75 | 4560.00 | 204.25 |
M S1 APARTMENT | 4075.50 | 1904.50 | 173.75 |
M S2 APARTMENT | 4074.00 | 1907.00 | 172.75 |
F6 SW APARTMENT | 3858.50 | 2543.25 | 157.50 |
F6 NW APARTMENT | 3120.00 | 4520.50 | 186.00 |
F6 SE APARTMENT | 3921.50 | 2554.75 | 138.25 |
F6 NE APARTMENT | 3226.00 | 4506.00 | 190.25 |
F6 N1 APARTMENT | 2959.50 | 4713.75 | 217.25 |
F6 N2 APARTMENT | 2964.75 | 4717.75 | 217.25 |
F6 S1 APARTMENT | 3946.00 | 2111.25 | 184.00 |
F6 S2 APARTMENT | 3949.25 | 2111.50 | 183.25 |
F7 SW APARTMENT | 3783.25 | 2680.00 | 161.00 |
F7 NW APARTMENT | 3089.00 | 4607.50 | 193.25 |
F7 SE APARTMENT | 3851.00 | 2686.25 | 144.25 |
F7 NE APARTMENT | 3204.50 | 4582.25 | 205.00 |
F7 N1 APARTMENT | 2930.50 | 4815.00 | 224.25 |
F7 N2 APARTMENT | 2934.75 | 4812.00 | 224.50 |
F7 S1 APARTMENT | 3862.00 | 2257.50 | 190.50 |
F7 S2 APARTMENT | 3866.00 | 2260.25 | 189.75 |
F8 SW APARTMENT | 3713.25 | 2807.75 | 163.50 |
F8 NW APARTMENT | 3065.50 | 4675.25 | 199.75 |
F8 SE APARTMENT | 3775.50 | 2815.50 | 147.75 |
F8 NE APARTMENT | 3189.00 | 4662.00 | 218.75 |
F8 N1 APARTMENT | 2908.50 | 4881.75 | 227.25 |
F8 N2 APARTMENT | 2912.25 | 4882.25 | 227.50 |
F8 S1 APARTMENT | 3781.75 | 2406.75 | 193.50 |
F8 S2 APARTMENT | 3785.50 | 2407.00 | 193.50 |
F9 SW APARTMENT | 3613.00 | 3028.50 | 160.00 |
F9 NW APARTMENT | 3065.25 | 4761.00 | 217.50 |
F9 SE APARTMENT | 3653.50 | 3018.25 | 145.75 |
F9 NE APARTMENT | 3188.50 | 4735.00 | 241.25 |
F9 N1 APARTMENT | 2892.00 | 4943.50 | 218.50 |
F9 N2 APARTMENT | 2901.00 | 4940.00 | 218.75 |
F9 S1 APARTMENT | 3621.75 | 2672.75 | 188.50 |
F9 S2 APARTMENT | 3626.50 | 2671.50 | 187.75 |
T SW APARTMENT | 4008.00 | 3812.25 | 386.75 |
T NW APARTMENT | 3445.25 | 4895.25 | 717.50 |
T SE APARTMENT | 4129.00 | 3728.75 | 396.75 |
T NE APARTMENT | 3558.00 | 4896.75 | 741.25 |
T N1 APARTMENT | 3005.75 | 5150.50 | 454.25 |
T N2 APARTMENT | 3010.00 | 5138.50 | 456.50 |
T S1 APARTMENT | 3807.00 | 3609.25 | 262.75 |
T S2 APARTMENT | 3818.50 | 3607.00 | 262.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5369.50 | 6249.50 | 1030.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 2.75 | 50.00 | 2.75 | 50.00 |
G NW APARTMENT | 2.50 | 35.50 | 2.50 | 35.50 |
OFFICE | 1.50 | 24.25 | 0.00 | 24.00 |
G NE APARTMENT | 8.75 | 68.00 | 8.75 | 68.00 |
G N1 APARTMENT | 3.25 | 54.75 | 3.25 | 54.75 |
G N2 APARTMENT | 7.00 | 57.25 | 7.00 | 57.25 |
G S1 APARTMENT | 0.00 | 253.00 | 0.00 | 253.00 |
G S2 APARTMENT | 0.00 | 201.75 | 0.00 | 201.75 |
F2 SW APARTMENT | 0.50 | 52.00 | 0.50 | 52.00 |
F2 NW APARTMENT | 0.25 | 32.50 | 0.25 | 32.50 |
F2 SE APARTMENT | 1.00 | 61.25 | 1.00 | 61.25 |
F2 NE APARTMENT | 3.25 | 78.75 | 3.25 | 78.75 |
F2 N1 APARTMENT | 2.50 | 45.25 | 2.50 | 45.25 |
F2 N2 APARTMENT | 2.00 | 47.50 | 2.00 | 47.50 |
F2 S1 APARTMENT | 0.00 | 289.25 | 0.00 | 289.25 |
F2 S2 APARTMENT | 0.00 | 271.75 | 0.00 | 271.75 |
F3 SW APARTMENT | 0.00 | 70.25 | 0.00 | 70.25 |
F3 NW APARTMENT | 0.00 | 38.75 | 0.00 | 38.75 |
F3 SE APARTMENT | 1.00 | 123.25 | 1.00 | 123.25 |
F3 NE APARTMENT | 2.75 | 92.25 | 2.75 | 92.25 |
F3 N1 APARTMENT | 1.75 | 57.75 | 1.75 | 57.75 |
F3 N2 APARTMENT | 1.25 | 60.00 | 1.25 | 60.00 |
F3 S1 APARTMENT | 0.00 | 349.50 | 0.00 | 349.50 |
F3 S2 APARTMENT | 0.00 | 341.25 | 0.00 | 341.25 |
F4 SW APARTMENT | 0.25 | 76.00 | 0.25 | 76.00 |
F4 NW APARTMENT | 0.25 | 41.25 | 0.25 | 41.25 |
F4 SE APARTMENT | 0.50 | 136.00 | 0.50 | 136.00 |
F4 NE APARTMENT | 2.75 | 93.25 | 2.75 | 93.25 |
F4 N1 APARTMENT | 2.00 | 62.00 | 2.00 | 62.00 |
F4 N2 APARTMENT | 2.25 | 65.00 | 2.25 | 65.00 |
F4 S1 APARTMENT | 0.00 | 367.00 | 0.00 | 367.00 |
F4 S2 APARTMENT | 0.00 | 359.50 | 0.00 | 359.50 |
M SW APARTMENT | 0.25 | 77.50 | 0.25 | 77.50 |
M NW APARTMENT | 0.25 | 43.25 | 0.25 | 43.25 |
M SE APARTMENT | 1.50 | 135.00 | 1.50 | 135.00 |
M NE APARTMENT | 2.50 | 98.25 | 2.50 | 98.25 |
M N1 APARTMENT | 1.75 | 64.25 | 1.75 | 64.25 |
M N2 APARTMENT | 1.25 | 66.50 | 1.25 | 66.50 |
M S1 APARTMENT | 0.00 | 360.25 | 0.00 | 360.25 |
M S2 APARTMENT | 0.00 | 352.75 | 0.00 | 352.75 |
F6 SW APARTMENT | 0.50 | 77.50 | 0.50 | 77.50 |
F6 NW APARTMENT | 0.50 | 44.25 | 0.50 | 44.25 |
F6 SE APARTMENT | 1.25 | 132.50 | 1.25 | 132.50 |
F6 NE APARTMENT | 2.50 | 105.50 | 2.50 | 105.50 |
F6 N1 APARTMENT | 1.75 | 67.25 | 1.75 | 67.25 |
F6 N2 APARTMENT | 1.75 | 70.75 | 1.75 | 70.75 |
F6 S1 APARTMENT | 0.00 | 349.00 | 0.00 | 349.00 |
F6 S2 APARTMENT | 0.00 | 343.25 | 0.00 | 343.25 |
F7 SW APARTMENT | 0.00 | 80.25 | 0.00 | 80.25 |
F7 NW APARTMENT | 0.25 | 45.75 | 0.25 | 45.75 |
F7 SE APARTMENT | 0.00 | 129.00 | 0.00 | 129.00 |
F7 NE APARTMENT | 2.50 | 110.00 | 2.50 | 110.00 |
F7 N1 APARTMENT | 1.75 | 70.00 | 1.75 | 70.00 |
F7 N2 APARTMENT | 1.25 | 74.75 | 1.25 | 74.75 |
F7 S1 APARTMENT | 0.00 | 335.75 | 0.00 | 335.75 |
F7 S2 APARTMENT | 0.00 | 331.25 | 0.00 | 331.25 |
F8 SW APARTMENT | 0.25 | 79.25 | 0.25 | 79.25 |
F8 NW APARTMENT | 0.25 | 46.25 | 0.25 | 46.25 |
F8 SE APARTMENT | 0.50 | 125.50 | 0.50 | 125.50 |
F8 NE APARTMENT | 1.50 | 112.50 | 1.50 | 112.50 |
F8 N1 APARTMENT | 2.00 | 70.75 | 2.00 | 70.75 |
F8 N2 APARTMENT | 3.25 | 75.50 | 3.25 | 75.50 |
F8 S1 APARTMENT | 0.00 | 316.75 | 0.00 | 316.75 |
F8 S2 APARTMENT | 0.00 | 314.75 | 0.00 | 314.75 |
F9 SW APARTMENT | 0.00 | 67.50 | 0.00 | 67.50 |
F9 NW APARTMENT | 0.00 | 45.25 | 0.00 | 45.25 |
F9 SE APARTMENT | 0.25 | 104.75 | 0.25 | 104.75 |
F9 NE APARTMENT | 1.50 | 127.75 | 1.50 | 127.75 |
F9 N1 APARTMENT | 4.00 | 66.00 | 4.00 | 66.00 |
F9 N2 APARTMENT | 3.25 | 69.75 | 3.25 | 69.75 |
F9 S1 APARTMENT | 0.00 | 259.25 | 0.00 | 259.25 |
F9 S2 APARTMENT | 0.25 | 251.50 | 0.25 | 251.50 |
T SW APARTMENT | 0.00 | 63.50 | 0.00 | 63.50 |
T NW APARTMENT | 0.00 | 48.00 | 0.00 | 48.00 |
T SE APARTMENT | 0.00 | 76.75 | 0.00 | 76.75 |
T NE APARTMENT | 0.00 | 77.50 | 0.00 | 77.50 |
T N1 APARTMENT | 1.50 | 57.25 | 1.50 | 57.25 |
T N2 APARTMENT | 2.75 | 51.75 | 2.75 | 51.75 |
T S1 APARTMENT | 1.00 | 129.00 | 1.00 | 129.00 |
T S2 APARTMENT | 0.50 | 128.00 | 0.50 | 128.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 84.25 | 592.25 | 83.00 | 592.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.097 | 0.000 | 0.329 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.097 | 0.000 | 0.314 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.518 | 0.100 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.097 | 0.000 | 0.314 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.058 | 0.000 | 0.307 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.058 | 0.000 | 0.307 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.058 | 0.000 | 0.325 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.058 | 0.000 | 0.326 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.386 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.369 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.387 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.369 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.084 | 0.000 | 0.365 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.084 | 0.000 | 0.365 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.084 | 0.000 | 0.385 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.084 | 0.000 | 0.385 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.165 | 0.000 | 0.430 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.164 | 0.000 | 0.410 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.165 | 0.000 | 0.430 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.164 | 0.000 | 0.410 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.099 | 0.000 | 0.406 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.099 | 0.000 | 0.406 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.099 | 0.000 | 0.428 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.099 | 0.000 | 0.428 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.184 | 0.000 | 0.448 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.184 | 0.000 | 0.426 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.184 | 0.000 | 0.448 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.184 | 0.000 | 0.426 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.111 | 0.000 | 0.423 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.111 | 0.000 | 0.423 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.111 | 0.000 | 0.447 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.111 | 0.000 | 0.447 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.200 | 0.000 | 0.472 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.200 | 0.000 | 0.447 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.200 | 0.000 | 0.472 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.200 | 0.000 | 0.447 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.120 | 0.000 | 0.445 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.120 | 0.000 | 0.445 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.121 | 0.000 | 0.470 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.121 | 0.000 | 0.470 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.214 | 0.000 | 0.492 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.213 | 0.000 | 0.465 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.214 | 0.000 | 0.492 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.213 | 0.000 | 0.465 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.129 | 0.000 | 0.462 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.129 | 0.000 | 0.462 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.129 | 0.000 | 0.490 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.129 | 0.000 | 0.490 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.226 | 0.000 | 0.509 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.225 | 0.000 | 0.481 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.226 | 0.000 | 0.509 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.225 | 0.000 | 0.481 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.136 | 0.000 | 0.478 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.136 | 0.000 | 0.478 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.136 | 0.000 | 0.507 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.136 | 0.000 | 0.507 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.237 | 0.000 | 0.527 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.236 | 0.000 | 0.497 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.237 | 0.000 | 0.527 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.236 | 0.000 | 0.497 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.142 | 0.000 | 0.494 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.142 | 0.000 | 0.494 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.143 | 0.000 | 0.525 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.143 | 0.000 | 0.525 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.247 | 0.000 | 0.543 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.246 | 0.000 | 0.511 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.247 | 0.000 | 0.543 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.246 | 0.000 | 0.512 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.148 | 0.000 | 0.508 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.148 | 0.000 | 0.508 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.149 | 0.000 | 0.541 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.149 | 0.000 | 0.541 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.256 | 0.000 | 0.555 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.255 | 0.000 | 0.523 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.256 | 0.000 | 0.555 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.255 | 0.000 | 0.523 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.154 | 0.000 | 0.520 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.154 | 0.000 | 0.520 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.154 | 0.000 | 0.553 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.154 | 0.000 | 0.553 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 699.65 | 22185.69 | 02-JAN-06:15 | 22185.69 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1302.99 | 22566.22 | 19-APR-03:00 | 85973.28 | 31-JUL-16:30 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
ElectricityPurchased:Plant | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
Cogeneration:ElectricityPurchased | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
ElectricityNet:Plant | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
Cogeneration:ElectricityNet | 3081.65 | 60126.71 | 19-APR-03:00 | 171347.37 | 21-JUL-19:15 |
ExteriorLights:Electricity | 168.44 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.44 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 699.65 | 22185.69 | 02-JAN-06:15 | 22185.69 | 01-JAN-00:15 |
Cooling:Electricity | 543.05 | 0.00 | 01-JAN-00:15 | 62737.86 | 21-JUL-15:30 |
Heating:Electricity | 39.47 | 0.00 | 01-JAN-12:30 | 27969.25 | 18-JAN-01:30 |
Electricity:Plant | 62.72 | 36.93 | 02-MAR-14:00 | 3552.87 | 31-JUL-15:00 |
HeatRejection:Electricity | 19.13 | 0.00 | 01-JAN-00:15 | 2159.84 | 31-JUL-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 43.59 | 36.93 | 02-MAR-14:00 | 1393.03 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1193.04 | 9260.51 | 01-JAN-00:15 | 174185.85 | 17-JAN-08:00 |
Gas:Plant | 1193.04 | 9260.51 | 01-JAN-00:15 | 174185.85 | 17-JAN-08:00 |
WaterSystems:Gas | 1107.29 | 9260.51 | 01-JAN-00:15 | 87083.60 | 05-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1107.29 | 9260.51 | 01-JAN-00:15 | 87083.60 | 05-FEB-08:00 |
Heating:Gas | 85.75 | 0.00 | 01-JAN-00:15 | 101426.39 | 18-JAN-01:45 |
Boiler:Heating:Gas | 85.75 | 0.00 | 01-JAN-00:15 | 101426.39 | 18-JAN-01:45 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 2163.57 | 0.00 | 01-JAN-00:15 | 281617.38 | 31-JUL-16:30 |
PlantLoopCoolingDemand:HVAC | 2163.57 | 0.00 | 01-JAN-00:15 | 281617.38 | 31-JUL-16:30 |
CoolingCoils:PlantLoopCoolingDemand | 2163.57 | 0.00 | 01-JAN-00:15 | 281617.38 | 31-JUL-16:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6602.18 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
Water:Plant | 6602.18 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6602.18 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
MainsWater:Plant | 6602.18 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1823.67 | 0.00 | 01-JAN-00:15 | 0.00 | 28-JUN-16:00 |
HeatRejection:MainsWater | 1823.67 | 0.00 | 01-JAN-00:15 | 0.00 | 28-JUN-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 950.23 | 445.40 | 08-AUG-01:15 | 130319.55 | 17-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 841.13 | 445.40 | 08-AUG-01:15 | 58322.72 | 08-FEB-07:45 |
WaterSystems:PlantLoopHeatingDemand | 841.13 | 445.40 | 08-AUG-01:15 | 58322.72 | 08-FEB-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4320.35 | 6208.78 | 10-JUN-03:00 | 421892.42 | 20-AUG-17:15 |
EnergyTransfer:Building | 1612.33 | 4559.57 | 28-MAR-13:45 | 174874.27 | 20-AUG-17:15 |
EnergyTransfer:Zone:G SW APARTMENT | 15.23 | 0.01 | 03-MAR-08:00 | 2487.78 | 28-SEP-16:30 |
Heating:EnergyTransfer | 94.71 | 0.00 | 03-JAN-21:00 | 80985.99 | 18-JAN-01:30 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.04 | 0.00 | 01-JAN-00:15 | 1024.31 | 18-JAN-01:30 |
Cooling:EnergyTransfer | 1517.62 | 0.00 | 17-JAN-08:15 | 174874.27 | 20-AUG-17:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.19 | 0.00 | 01-JAN-03:00 | 2487.78 | 28-SEP-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 12.09 | 0.00 | 18-FEB-17:00 | 2342.32 | 25-JUN-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.97 | 0.00 | 01-JAN-17:15 | 1128.29 | 17-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 9.12 | 0.00 | 01-JAN-00:15 | 2342.32 | 25-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 22.23 | 0.02 | 01-APR-21:45 | 3084.86 | 12-SEP-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 1.00 | 0.00 | 01-JAN-00:15 | 1090.71 | 17-JAN-08:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 21.23 | 0.00 | 01-JAN-02:00 | 3084.86 | 12-SEP-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 12.41 | 0.04 | 11-AUG-06:45 | 1726.37 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.63 | 0.00 | 01-JAN-08:30 | 1170.53 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 9.78 | 0.00 | 01-JAN-00:15 | 1726.37 | 28-JUN-08:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.47 | 0.01 | 07-NOV-04:15 | 1226.99 | 11-JUN-18:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.12 | 0.00 | 01-JAN-10:30 | 790.14 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 7.35 | 0.00 | 01-JAN-00:15 | 1226.99 | 11-JUN-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.48 | 0.00 | 27-FEB-08:45 | 1206.02 | 11-JUN-18:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.11 | 0.00 | 01-JAN-10:15 | 792.45 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 7.37 | 0.00 | 01-JAN-00:15 | 1206.02 | 11-JUN-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 13.07 | 0.02 | 21-MAY-01:00 | 1425.83 | 29-SEP-11:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 488.28 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 12.94 | 0.00 | 11-JAN-05:15 | 1425.83 | 29-SEP-11:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 13.29 | 0.03 | 27-APR-09:45 | 1482.84 | 29-SEP-11:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 479.49 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 13.15 | 0.00 | 13-JAN-04:00 | 1482.84 | 29-SEP-11:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 25.03 | 0.08 | 25-MAY-03:45 | 3212.00 | 11-OCT-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.45 | 0.00 | 01-JAN-00:15 | 1012.59 | 18-JAN-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 24.58 | 0.00 | 12-JAN-06:00 | 3212.00 | 11-OCT-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 16.86 | 0.00 | 19-MAR-19:45 | 2999.19 | 25-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 1.98 | 0.00 | 01-JAN-10:00 | 1226.55 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 14.88 | 0.00 | 01-JAN-00:15 | 2999.19 | 25-JUN-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 27.05 | 0.04 | 08-DEC-09:15 | 2867.21 | 01-OCT-11:15 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 982.71 | 18-JAN-02:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 26.73 | 0.00 | 01-JAN-15:45 | 2867.21 | 01-OCT-11:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 17.82 | 0.02 | 15-MAR-19:15 | 2303.48 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 1.77 | 0.00 | 01-JAN-07:45 | 1324.20 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 16.06 | 0.00 | 01-JAN-00:15 | 2303.48 | 28-JUN-08:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 12.73 | 0.01 | 19-FEB-13:30 | 1656.05 | 11-JUN-18:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 753.02 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 12.27 | 0.00 | 01-JAN-02:00 | 1656.05 | 11-JUN-18:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 12.77 | 0.00 | 04-JUN-06:30 | 1639.07 | 11-JUN-18:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 757.11 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 12.30 | 0.00 | 01-JAN-02:00 | 1639.07 | 11-JUN-18:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 22.18 | 0.09 | 09-MAR-14:15 | 2100.14 | 01-NOV-12:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 385.67 | 18-JAN-02:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 22.10 | 0.00 | 17-JAN-02:30 | 2100.14 | 01-NOV-12:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 22.31 | 0.05 | 29-AUG-06:30 | 2117.81 | 01-NOV-12:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 383.49 | 18-JAN-02:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 22.23 | 0.00 | 17-JAN-02:30 | 2117.81 | 01-NOV-12:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 26.78 | 0.01 | 20-MAR-19:45 | 3242.79 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 1035.22 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 26.38 | 0.00 | 16-JAN-21:00 | 3242.79 | 10-OCT-16:00 |
EnergyTransfer:Zone:F3 NW APARTMENT | 17.75 | 0.04 | 03-JAN-11:00 | 3017.74 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 1.76 | 0.00 | 01-JAN-00:15 | 1324.73 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 15.99 | 0.00 | 01-JAN-01:15 | 3017.74 | 22-JUL-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 27.93 | 0.16 | 19-OCT-19:15 | 2728.66 | 01-OCT-10:45 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 1048.95 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 27.64 | 0.00 | 01-JAN-15:45 | 2728.66 | 01-OCT-10:45 |
EnergyTransfer:Zone:F3 NE APARTMENT | 18.82 | 0.00 | 05-NOV-13:15 | 2346.49 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 1.59 | 0.00 | 01-JAN-07:30 | 1424.37 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 17.23 | 0.00 | 01-JAN-00:15 | 2346.49 | 28-JUN-08:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 13.91 | 0.09 | 09-SEP-09:15 | 1726.89 | 07-JUN-18:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 800.13 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 13.54 | 0.00 | 01-JAN-03:00 | 1726.89 | 07-JUN-18:00 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 13.95 | 0.01 | 04-JUN-20:45 | 1713.63 | 07-JUN-18:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 807.43 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 13.58 | 0.00 | 01-JAN-03:00 | 1713.63 | 07-JUN-18:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 24.47 | 0.46 | 29-AUG-06:30 | 2169.79 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 382.20 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 24.39 | 0.00 | 17-JAN-08:15 | 2169.79 | 29-DEC-12:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 24.53 | 0.16 | 29-AUG-06:45 | 2177.04 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 382.95 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 24.45 | 0.00 | 17-JAN-08:15 | 2177.04 | 29-DEC-12:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 27.04 | 0.04 | 02-MAR-00:15 | 3266.89 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.41 | 0.00 | 01-JAN-00:15 | 1100.60 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 26.64 | 0.00 | 16-JAN-18:00 | 3266.89 | 10-OCT-16:00 |
EnergyTransfer:Zone:F4 NW APARTMENT | 18.01 | 0.01 | 03-MAR-16:00 | 3032.50 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 1.78 | 0.00 | 01-JAN-00:15 | 1437.42 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 16.22 | 0.00 | 01-JAN-01:15 | 3032.50 | 22-JUL-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 28.08 | 0.12 | 22-MAR-12:45 | 2729.14 | 01-OCT-10:45 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 1120.67 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 27.77 | 0.00 | 01-JAN-15:45 | 2729.14 | 01-OCT-10:45 |
EnergyTransfer:Zone:F4 NE APARTMENT | 19.10 | 0.01 | 20-NOV-12:30 | 2371.73 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 1.62 | 0.00 | 01-JAN-07:30 | 1532.93 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 17.47 | 0.00 | 01-JAN-00:15 | 2371.73 | 28-JUN-08:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 14.28 | 0.01 | 23-SEP-21:00 | 1746.24 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 901.10 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 13.91 | 0.00 | 01-JAN-05:00 | 1746.24 | 23-JUN-21:00 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 14.32 | 0.02 | 29-JAN-04:15 | 1731.76 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 909.64 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 13.94 | 0.00 | 01-JAN-03:15 | 1731.76 | 23-JUN-21:00 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 25.00 | 0.22 | 11-OCT-09:30 | 2187.23 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 410.54 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 24.92 | 0.00 | 17-JAN-08:15 | 2187.23 | 29-DEC-12:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 25.04 | 0.11 | 04-JUN-19:00 | 2192.65 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 411.93 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 24.95 | 0.00 | 17-JAN-08:15 | 2192.65 | 29-DEC-12:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 27.32 | 0.04 | 09-JUN-03:15 | 3311.14 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.43 | 0.00 | 01-JAN-00:15 | 1156.58 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 26.89 | 0.00 | 16-JAN-17:45 | 3311.14 | 10-OCT-16:00 |
EnergyTransfer:Zone:M NW APARTMENT | 18.36 | 0.00 | 07-DEC-16:45 | 3063.85 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.82 | 0.00 | 01-JAN-00:15 | 1525.08 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 16.53 | 0.00 | 01-JAN-01:15 | 3063.85 | 22-JUL-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 28.35 | 0.00 | 18-MAY-04:15 | 2760.88 | 01-OCT-11:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 1176.58 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 28.01 | 0.00 | 01-JAN-15:30 | 2760.88 | 01-OCT-11:00 |
EnergyTransfer:Zone:M NE APARTMENT | 19.44 | 0.00 | 01-MAR-12:15 | 2412.03 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.65 | 0.00 | 01-JAN-07:30 | 1616.15 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 17.79 | 0.00 | 01-JAN-00:15 | 2412.03 | 28-JUN-08:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 14.70 | 0.06 | 19-FEB-13:30 | 1793.16 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 994.49 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 14.31 | 0.00 | 01-JAN-14:00 | 1793.16 | 23-JUN-21:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 14.73 | 0.24 | 30-JAN-14:30 | 1778.71 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 1002.97 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 14.35 | 0.00 | 01-JAN-05:15 | 1778.71 | 23-JUN-21:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 25.45 | 0.12 | 30-MAR-15:15 | 2220.48 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 435.75 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 25.36 | 0.00 | 05-JAN-15:00 | 2220.48 | 29-DEC-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 25.49 | 0.10 | 15-OCT-20:45 | 2225.47 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 437.25 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 25.39 | 0.00 | 05-JAN-15:00 | 2225.47 | 29-DEC-12:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 26.20 | 0.04 | 02-MAR-16:45 | 3278.89 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 1253.90 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 25.69 | 0.00 | 05-JAN-15:00 | 3278.89 | 10-OCT-16:00 |
EnergyTransfer:Zone:F6 NW APARTMENT | 17.92 | 0.00 | 26-JAN-16:45 | 3019.77 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 2.14 | 0.00 | 01-JAN-09:00 | 1657.31 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 15.78 | 0.00 | 01-JAN-00:15 | 3019.77 | 22-JUL-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 27.21 | 0.03 | 02-FEB-02:45 | 2726.32 | 01-OCT-11:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.41 | 0.00 | 01-JAN-00:15 | 1275.03 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 26.80 | 0.00 | 01-JAN-15:15 | 2726.32 | 01-OCT-11:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 18.93 | 0.03 | 17-DEC-16:30 | 2379.49 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 1.94 | 0.00 | 01-JAN-07:30 | 1748.61 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 16.99 | 0.00 | 01-JAN-00:15 | 2379.49 | 28-JUN-08:15 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 14.05 | 0.06 | 24-DEC-11:00 | 1766.38 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1178.75 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 13.57 | 0.00 | 01-JAN-02:45 | 1766.38 | 23-JUN-21:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 14.09 | 0.06 | 18-JUN-05:45 | 1752.02 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1185.19 | 19-FEB-16:15 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 13.61 | 0.00 | 01-JAN-02:30 | 1752.02 | 23-JUN-21:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 24.34 | 0.21 | 25-SEP-08:15 | 2180.81 | 29-DEC-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 509.72 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 24.23 | 0.00 | 05-JAN-15:00 | 2180.81 | 29-DEC-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 24.38 | 0.12 | 30-APR-09:45 | 2185.58 | 29-DEC-12:45 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 511.07 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 24.26 | 0.00 | 05-JAN-15:00 | 2185.58 | 29-DEC-12:45 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 25.55 | 0.02 | 02-MAR-09:45 | 3269.59 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 1335.55 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 24.96 | 0.00 | 05-JAN-14:45 | 3269.59 | 10-OCT-16:00 |
EnergyTransfer:Zone:F7 NW APARTMENT | 17.78 | 0.00 | 15-APR-13:00 | 3004.41 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 2.39 | 0.00 | 01-JAN-10:15 | 1765.17 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 15.39 | 0.00 | 01-JAN-00:15 | 3004.41 | 22-JUL-17:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 26.55 | 0.32 | 06-MAY-23:45 | 2714.55 | 01-OCT-11:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1357.37 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 26.07 | 0.00 | 01-JAN-15:00 | 2714.55 | 01-OCT-11:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 18.76 | 0.01 | 19-FEB-11:45 | 2373.24 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 2.19 | 0.00 | 01-JAN-07:45 | 1853.90 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 16.57 | 0.00 | 01-JAN-00:15 | 2373.24 | 28-JUN-08:15 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 13.76 | 0.09 | 23-FEB-05:30 | 1764.18 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.57 | 0.00 | 01-JAN-00:15 | 1240.38 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 13.19 | 0.00 | 01-JAN-02:15 | 1764.18 | 23-JUN-21:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 13.79 | 0.02 | 11-DEC-10:00 | 1749.89 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.57 | 0.00 | 01-JAN-00:15 | 1237.45 | 19-FEB-16:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 13.22 | 0.00 | 01-JAN-02:15 | 1749.89 | 23-JUN-21:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 23.70 | 0.07 | 24-AUG-08:15 | 2165.87 | 29-DEC-13:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 564.97 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 23.57 | 0.00 | 05-JAN-14:45 | 2165.87 | 29-DEC-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 23.73 | 0.08 | 14-APR-09:15 | 2170.42 | 29-DEC-13:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 566.06 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 23.60 | 0.00 | 05-JAN-14:45 | 2170.42 | 29-DEC-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 25.05 | 0.02 | 04-MAY-00:15 | 3274.38 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 1422.76 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 24.37 | 0.00 | 01-JAN-15:45 | 3274.38 | 10-OCT-16:00 |
EnergyTransfer:Zone:F8 NW APARTMENT | 17.83 | 0.04 | 30-NOV-19:00 | 3005.49 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 2.67 | 0.00 | 01-JAN-10:15 | 1865.43 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 15.16 | 0.00 | 01-JAN-00:15 | 3005.49 | 22-JUL-17:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 26.05 | 0.09 | 09-NOV-05:45 | 2716.21 | 01-OCT-11:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.56 | 0.00 | 01-JAN-00:15 | 1445.04 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 25.48 | 0.00 | 01-JAN-14:45 | 2716.21 | 01-OCT-11:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 18.75 | 0.01 | 01-DEC-06:00 | 2377.51 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 2.43 | 0.00 | 01-JAN-07:45 | 1952.41 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 16.32 | 0.00 | 01-JAN-00:15 | 2377.51 | 28-JUN-08:15 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 13.63 | 0.00 | 16-DEC-14:30 | 1776.36 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 1431.12 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 12.95 | 0.00 | 01-JAN-02:00 | 1776.36 | 23-JUN-21:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 13.67 | 0.02 | 19-DEC-01:30 | 1762.15 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 1424.75 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 12.99 | 0.00 | 01-JAN-02:00 | 1762.15 | 23-JUN-21:00 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 23.16 | 0.15 | 09-SEP-09:30 | 2161.31 | 29-DEC-13:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.15 | 0.00 | 01-JAN-00:15 | 618.66 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 23.01 | 0.00 | 01-JAN-15:30 | 2161.31 | 29-DEC-13:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 23.20 | 0.00 | 15-OCT-20:45 | 2165.75 | 29-DEC-13:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.15 | 0.00 | 01-JAN-00:15 | 619.77 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 23.05 | 0.00 | 01-JAN-15:30 | 2165.75 | 29-DEC-13:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 24.63 | 0.05 | 05-MAY-20:45 | 3391.00 | 10-OCT-15:45 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 0.91 | 0.00 | 01-JAN-00:15 | 1589.94 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 23.72 | 0.00 | 01-JAN-15:30 | 3391.00 | 10-OCT-15:45 |
EnergyTransfer:Zone:F9 NW APARTMENT | 18.53 | 0.04 | 09-OCT-01:45 | 3116.37 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 3.29 | 0.00 | 01-JAN-10:30 | 2005.93 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 15.25 | 0.00 | 01-JAN-00:15 | 3116.37 | 22-JUL-17:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 25.61 | 0.01 | 21-DEC-02:45 | 2790.58 | 10-OCT-15:45 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 0.78 | 0.00 | 01-JAN-00:15 | 1611.62 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 24.83 | 0.00 | 01-JAN-14:15 | 2790.58 | 10-OCT-15:45 |
EnergyTransfer:Zone:F9 NE APARTMENT | 19.29 | 0.00 | 26-OCT-15:00 | 2416.76 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 2.96 | 0.00 | 01-JAN-08:00 | 2098.90 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 16.33 | 0.00 | 01-JAN-00:15 | 2416.76 | 28-JUN-08:15 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 13.85 | 0.11 | 24-FEB-08:45 | 1879.83 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 1627.86 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 12.88 | 0.00 | 01-JAN-01:30 | 1879.83 | 23-JUN-21:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 13.88 | 0.03 | 07-JAN-10:00 | 1865.35 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 1619.39 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 12.92 | 0.00 | 01-JAN-01:30 | 1865.35 | 23-JUN-21:00 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 22.53 | 0.42 | 03-JUN-09:00 | 2179.64 | 07-NOV-11:45 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 728.39 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 22.32 | 0.00 | 01-JAN-15:00 | 2179.64 | 07-NOV-11:45 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 22.57 | 0.13 | 26-MAY-20:15 | 2188.38 | 07-NOV-11:45 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 729.61 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 22.37 | 0.00 | 01-JAN-15:00 | 2188.38 | 07-NOV-11:45 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 28.83 | 0.05 | 26-DEC-20:45 | 4134.36 | 10-OCT-15:45 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.35 | 0.00 | 01-JAN-08:15 | 2195.28 | 17-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 24.47 | 0.00 | 01-JAN-00:15 | 4134.36 | 10-OCT-15:45 |
EnergyTransfer:Zone:T NW APARTMENT | 23.92 | 0.00 | 28-DEC-15:30 | 3845.25 | 18-JUL-16:45 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 7.50 | 0.00 | 02-JAN-14:15 | 2635.33 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 16.42 | 0.00 | 01-JAN-00:15 | 3845.25 | 18-JUL-16:45 |
EnergyTransfer:Zone:T SE APARTMENT | 28.97 | 0.02 | 04-NOV-22:00 | 3588.54 | 01-OCT-12:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.99 | 0.00 | 01-JAN-07:45 | 2217.23 | 17-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 24.97 | 0.00 | 01-JAN-00:15 | 3588.54 | 01-OCT-12:00 |
EnergyTransfer:Zone:T NE APARTMENT | 23.57 | 0.00 | 23-APR-10:45 | 3012.35 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 6.73 | 0.00 | 01-JAN-08:45 | 2684.09 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 16.83 | 0.00 | 01-JAN-00:15 | 3012.35 | 28-JUN-08:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 16.44 | 0.00 | 27-MAY-02:00 | 2384.35 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.45 | 0.00 | 01-JAN-10:00 | 1869.38 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 13.00 | 0.00 | 01-JAN-00:15 | 2384.35 | 23-JUN-21:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 16.50 | 0.01 | 13-JAN-16:00 | 2380.35 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.47 | 0.00 | 01-JAN-10:00 | 1862.49 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 13.04 | 0.00 | 01-JAN-00:15 | 2380.35 | 23-JUN-21:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 23.10 | 0.01 | 03-NOV-23:45 | 2931.13 | 07-NOV-12:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.38 | 0.00 | 01-JAN-00:15 | 1443.18 | 09-NOV-16:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 21.73 | 0.00 | 01-JAN-02:45 | 2931.13 | 07-NOV-12:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 23.15 | 0.05 | 11-APR-03:30 | 2943.00 | 07-NOV-12:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.38 | 0.00 | 01-JAN-00:15 | 1441.80 | 09-NOV-16:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 21.77 | 0.00 | 01-JAN-02:45 | 2943.00 | 07-NOV-12:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 909.56 | 445.40 | 08-AUG-01:15 | 127712.13 | 17-JAN-08:00 |
WaterSystems:EnergyTransfer | 841.12 | 445.40 | 08-AUG-01:15 | 58316.75 | 08-FEB-07:45 |
sub cat:WaterSystems:EnergyTransfer | 841.12 | 445.40 | 08-AUG-01:15 | 58316.75 | 08-FEB-07:45 |
EnergyTransfer:HVAC | 1798.46 | 0.00 | 02-MAR-14:00 | 219388.79 | 31-JUL-16:45 |
CoolingCoils:EnergyTransfer | 1656.38 | 0.00 | 01-JAN-00:15 | 219388.79 | 31-JUL-16:45 |
HeatingCoils:EnergyTransfer | 142.08 | 0.00 | 01-JAN-12:30 | 107781.56 | 18-JAN-01:30 |
PlantLoopHeatingDemand:HVAC | 109.10 | 0.00 | 01-JAN-12:30 | 82437.39 | 18-JAN-01:30 |
HeatingCoils:PlantLoopHeatingDemand | 109.10 | 0.00 | 01-JAN-12:30 | 82437.39 | 18-JAN-01:30 |
Boilers:EnergyTransfer | 68.44 | 0.00 | 01-JAN-00:15 | 81141.11 | 18-JAN-01:45 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.039 | -14.193 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 27.859 | 0.000 | 0.284 | 0.001 | 0.000 | -9.884 | 0.000 | -5.245 | -18.209 |
G NW APARTMENT | 2.969 | -9.121 | 0.000 | 0.000 | 3.786 | 2.413 | 12.213 | 14.033 | 0.000 | 0.278 | 0.000 | 0.000 | -9.897 | 0.000 | -4.838 | -11.836 |
OFFICE | 0.997 | -21.233 | 0.000 | 0.000 | 0.509 | 21.954 | 7.547 | 28.561 | 0.000 | 0.166 | 0.000 | 0.000 | -9.682 | 0.000 | -2.232 | -26.586 |
G NE APARTMENT | 2.628 | -9.785 | 0.000 | 0.000 | 3.803 | 2.413 | 12.213 | 14.565 | 0.000 | 0.276 | 0.001 | 0.000 | -9.404 | 0.000 | -4.834 | -11.875 |
G N1 APARTMENT | 1.117 | -7.349 | 0.000 | 0.000 | 3.812 | 2.413 | 12.213 | 4.629 | 0.000 | 0.212 | 0.000 | 0.000 | -6.053 | 0.000 | -3.720 | -7.274 |
G N2 APARTMENT | 1.112 | -7.370 | 0.000 | 0.000 | 3.813 | 2.413 | 12.213 | 4.625 | 0.000 | 0.212 | 0.000 | 0.000 | -6.048 | 0.000 | -3.723 | -7.248 |
G S1 APARTMENT | 0.136 | -12.935 | 0.000 | 0.000 | 3.721 | 2.413 | 12.213 | 18.643 | 0.000 | 0.209 | 0.001 | 0.000 | -5.996 | 0.000 | -4.216 | -14.188 |
G S2 APARTMENT | 0.141 | -13.150 | 0.000 | 0.000 | 3.719 | 2.413 | 12.213 | 18.630 | 0.000 | 0.210 | 0.000 | 0.000 | -6.001 | 0.000 | -4.243 | -13.932 |
F2 SW APARTMENT | 0.445 | -24.580 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 27.139 | 0.000 | 0.380 | 0.002 | 0.000 | -10.697 | 0.000 | -6.960 | -3.975 |
F2 NW APARTMENT | 1.983 | -14.878 | 0.000 | 0.000 | 3.720 | 2.413 | 12.213 | 13.509 | 0.000 | 0.372 | 0.000 | 0.000 | -10.581 | 0.000 | -6.519 | -2.231 |
F2 SE APARTMENT | 0.320 | -26.730 | 0.000 | 0.000 | 3.626 | 2.413 | 12.213 | 27.844 | 0.000 | 0.378 | 0.001 | 0.000 | -10.441 | 0.000 | -7.005 | -2.618 |
F2 NE APARTMENT | 1.765 | -16.058 | 0.000 | 0.000 | 3.739 | 2.413 | 12.213 | 14.040 | 0.000 | 0.369 | 0.000 | 0.000 | -10.035 | 0.000 | -6.496 | -1.950 |
F2 N1 APARTMENT | 0.468 | -12.266 | 0.000 | 0.000 | 3.739 | 2.413 | 12.213 | 4.350 | 0.000 | 0.277 | 0.363 | 0.000 | -6.529 | 0.000 | -5.028 | -0.000 |
F2 N2 APARTMENT | 0.468 | -12.300 | 0.000 | 0.000 | 3.741 | 2.413 | 12.213 | 4.347 | 0.000 | 0.277 | 0.395 | 0.000 | -6.524 | 0.000 | -5.030 | -0.000 |
F2 S1 APARTMENT | 0.081 | -22.100 | 0.000 | 0.000 | 3.602 | 2.413 | 12.213 | 18.189 | 0.000 | 0.270 | 0.002 | 0.000 | -6.505 | 0.000 | -5.583 | -2.579 |
F2 S2 APARTMENT | 0.083 | -22.231 | 0.000 | 0.000 | 3.601 | 2.413 | 12.213 | 18.185 | 0.000 | 0.271 | 0.002 | 0.000 | -6.507 | 0.000 | -5.590 | -2.438 |
F3 SW APARTMENT | 0.395 | -26.383 | 0.000 | 0.000 | 3.606 | 2.413 | 12.213 | 26.867 | 0.000 | 0.481 | 0.000 | 0.000 | -10.893 | 0.000 | -7.856 | -0.843 |
F3 NW APARTMENT | 1.761 | -15.992 | 0.000 | 0.000 | 3.706 | 2.413 | 12.213 | 13.327 | 0.000 | 0.470 | 0.289 | 0.000 | -10.791 | 0.000 | -7.395 | -0.000 |
F3 SE APARTMENT | 0.294 | -27.638 | 0.000 | 0.000 | 3.616 | 2.413 | 12.213 | 27.610 | 0.000 | 0.474 | 0.001 | 0.000 | -10.590 | 0.000 | -7.868 | -0.525 |
F3 NE APARTMENT | 1.588 | -17.230 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 13.864 | 0.000 | 0.466 | 0.553 | 0.000 | -10.229 | 0.000 | -7.363 | -0.000 |
F3 N1 APARTMENT | 0.372 | -13.542 | 0.000 | 0.000 | 3.716 | 2.413 | 12.213 | 4.268 | 0.000 | 0.357 | 2.583 | 0.000 | -6.689 | 0.000 | -5.692 | 0.000 |
F3 N2 APARTMENT | 0.373 | -13.575 | 0.000 | 0.000 | 3.718 | 2.413 | 12.213 | 4.266 | 0.000 | 0.357 | 2.612 | 0.000 | -6.683 | 0.000 | -5.693 | 0.000 |
F3 S1 APARTMENT | 0.075 | -24.394 | 0.000 | 0.000 | 3.580 | 2.413 | 12.213 | 18.014 | 0.000 | 0.345 | 0.649 | 0.000 | -6.642 | 0.000 | -6.250 | -0.000 |
F3 S2 APARTMENT | 0.075 | -24.451 | 0.000 | 0.000 | 3.580 | 2.413 | 12.213 | 18.011 | 0.000 | 0.345 | 0.709 | 0.000 | -6.641 | 0.000 | -6.254 | -0.000 |
F4 SW APARTMENT | 0.406 | -26.634 | 0.000 | 0.000 | 3.605 | 2.413 | 12.213 | 26.708 | 0.000 | 0.525 | 0.075 | 0.000 | -10.972 | 0.000 | -8.338 | -0.001 |
F4 NW APARTMENT | 1.785 | -16.223 | 0.000 | 0.000 | 3.703 | 2.413 | 12.213 | 13.229 | 0.000 | 0.513 | 1.119 | 0.000 | -10.889 | 0.000 | -7.863 | -0.000 |
F4 SE APARTMENT | 0.311 | -27.766 | 0.000 | 0.000 | 3.617 | 2.413 | 12.213 | 27.462 | 0.000 | 0.517 | 0.234 | 0.000 | -10.658 | 0.000 | -8.342 | -0.001 |
F4 NE APARTMENT | 1.623 | -17.475 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 13.768 | 0.000 | 0.509 | 1.374 | 0.000 | -10.319 | 0.000 | -7.828 | -0.000 |
F4 N1 APARTMENT | 0.376 | -13.906 | 0.000 | 0.000 | 3.709 | 2.413 | 12.213 | 4.229 | 0.000 | 0.387 | 3.347 | 0.000 | -6.767 | 0.000 | -6.000 | 0.000 |
F4 N2 APARTMENT | 0.378 | -13.938 | 0.000 | 0.000 | 3.710 | 2.413 | 12.213 | 4.226 | 0.000 | 0.387 | 3.373 | 0.000 | -6.761 | 0.000 | -6.001 | 0.000 |
F4 S1 APARTMENT | 0.083 | -24.916 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 17.912 | 0.000 | 0.374 | 1.597 | 0.000 | -6.698 | 0.000 | -6.554 | -0.000 |
F4 S2 APARTMENT | 0.083 | -24.953 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 17.910 | 0.000 | 0.374 | 1.637 | 0.000 | -6.696 | 0.000 | -6.557 | -0.000 |
M SW APARTMENT | 0.433 | -26.886 | 0.000 | 0.000 | 3.605 | 2.413 | 12.213 | 26.580 | 0.000 | 0.560 | 1.008 | 0.000 | -11.038 | 0.000 | -8.888 | -0.001 |
M NW APARTMENT | 1.822 | -16.534 | 0.000 | 0.000 | 3.702 | 2.413 | 12.213 | 13.152 | 0.000 | 0.547 | 2.034 | 0.000 | -10.965 | 0.000 | -8.383 | -0.000 |
M SE APARTMENT | 0.338 | -28.008 | 0.000 | 0.000 | 3.617 | 2.413 | 12.213 | 27.340 | 0.000 | 0.552 | 1.146 | 0.000 | -10.719 | 0.000 | -8.891 | -0.000 |
M NE APARTMENT | 1.649 | -17.793 | 0.000 | 0.000 | 3.721 | 2.413 | 12.213 | 13.692 | 0.000 | 0.542 | 2.298 | 0.000 | -10.389 | 0.000 | -8.346 | -0.000 |
M N1 APARTMENT | 0.383 | -14.314 | 0.000 | 0.000 | 3.705 | 2.413 | 12.213 | 4.198 | 0.000 | 0.411 | 4.193 | 0.000 | -6.825 | 0.000 | -6.377 | 0.000 |
M N2 APARTMENT | 0.384 | -14.347 | 0.000 | 0.000 | 3.706 | 2.413 | 12.213 | 4.196 | 0.000 | 0.411 | 4.221 | 0.000 | -6.819 | 0.000 | -6.378 | 0.000 |
M S1 APARTMENT | 0.095 | -25.356 | 0.000 | 0.000 | 3.574 | 2.413 | 12.213 | 17.832 | 0.000 | 0.397 | 2.528 | 0.000 | -6.742 | 0.000 | -6.953 | -0.000 |
M S2 APARTMENT | 0.095 | -25.390 | 0.000 | 0.000 | 3.575 | 2.413 | 12.213 | 17.830 | 0.000 | 0.398 | 2.562 | 0.000 | -6.740 | 0.000 | -6.956 | -0.000 |
F6 SW APARTMENT | 0.514 | -25.688 | 0.000 | 0.000 | 3.614 | 2.413 | 12.213 | 26.515 | 0.000 | 0.589 | 0.180 | 0.000 | -11.026 | 0.000 | -9.325 | -0.001 |
F6 NW APARTMENT | 2.136 | -15.781 | 0.000 | 0.000 | 3.712 | 2.413 | 12.213 | 13.133 | 0.000 | 0.576 | 1.311 | 0.000 | -10.948 | 0.000 | -8.765 | -0.000 |
F6 SE APARTMENT | 0.411 | -26.797 | 0.000 | 0.000 | 3.626 | 2.413 | 12.213 | 27.279 | 0.000 | 0.581 | 0.310 | 0.000 | -10.706 | 0.000 | -9.329 | -0.001 |
F6 NE APARTMENT | 1.944 | -16.987 | 0.000 | 0.000 | 3.730 | 2.413 | 12.213 | 13.674 | 0.000 | 0.570 | 1.546 | 0.000 | -10.373 | 0.000 | -8.730 | -0.000 |
F6 N1 APARTMENT | 0.483 | -13.571 | 0.000 | 0.000 | 3.716 | 2.413 | 12.213 | 4.200 | 0.000 | 0.430 | 3.556 | 0.000 | -6.813 | 0.000 | -6.627 | 0.000 |
F6 N2 APARTMENT | 0.483 | -13.605 | 0.000 | 0.000 | 3.718 | 2.413 | 12.213 | 4.197 | 0.000 | 0.430 | 3.585 | 0.000 | -6.807 | 0.000 | -6.627 | 0.000 |
F6 S1 APARTMENT | 0.112 | -24.232 | 0.000 | 0.000 | 3.582 | 2.413 | 12.213 | 17.790 | 0.000 | 0.417 | 1.702 | 0.000 | -6.738 | 0.000 | -7.259 | -0.000 |
F6 S2 APARTMENT | 0.111 | -24.264 | 0.000 | 0.000 | 3.583 | 2.413 | 12.213 | 17.788 | 0.000 | 0.417 | 1.736 | 0.000 | -6.736 | 0.000 | -7.262 | -0.000 |
F7 SW APARTMENT | 0.591 | -24.962 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 26.452 | 0.000 | 0.614 | 0.000 | 0.000 | -11.027 | 0.000 | -9.708 | -0.207 |
F7 NW APARTMENT | 2.394 | -15.389 | 0.000 | 0.000 | 3.720 | 2.413 | 12.213 | 13.109 | 0.000 | 0.600 | 0.991 | 0.000 | -10.946 | 0.000 | -9.104 | -0.000 |
F7 SE APARTMENT | 0.480 | -26.068 | 0.000 | 0.000 | 3.633 | 2.413 | 12.213 | 27.218 | 0.000 | 0.606 | 0.000 | 0.000 | -10.706 | 0.000 | -9.712 | -0.077 |
F7 NE APARTMENT | 2.186 | -16.571 | 0.000 | 0.000 | 3.737 | 2.413 | 12.213 | 13.650 | 0.000 | 0.594 | 1.217 | 0.000 | -10.370 | 0.000 | -9.070 | -0.000 |
F7 N1 APARTMENT | 0.574 | -13.187 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 4.197 | 0.000 | 0.447 | 3.275 | 0.000 | -6.808 | 0.000 | -6.849 | 0.000 |
F7 N2 APARTMENT | 0.574 | -13.220 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 4.194 | 0.000 | 0.447 | 3.305 | 0.000 | -6.802 | 0.000 | -6.850 | 0.000 |
F7 S1 APARTMENT | 0.128 | -23.570 | 0.000 | 0.000 | 3.589 | 2.413 | 12.213 | 17.750 | 0.000 | 0.434 | 1.309 | 0.000 | -6.740 | 0.000 | -7.526 | -0.000 |
F7 S2 APARTMENT | 0.129 | -23.603 | 0.000 | 0.000 | 3.589 | 2.413 | 12.213 | 17.748 | 0.000 | 0.434 | 1.344 | 0.000 | -6.738 | 0.000 | -7.529 | -0.000 |
F8 SW APARTMENT | 0.678 | -24.369 | 0.000 | 0.000 | 3.629 | 2.413 | 12.213 | 26.398 | 0.000 | 0.644 | 0.000 | 0.000 | -11.025 | 0.000 | -10.066 | -0.514 |
F8 NW APARTMENT | 2.668 | -15.159 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 13.086 | 0.000 | 0.628 | 0.798 | 0.000 | -10.947 | 0.000 | -9.426 | -0.001 |
F8 SE APARTMENT | 0.564 | -25.480 | 0.000 | 0.000 | 3.640 | 2.413 | 12.213 | 27.166 | 0.000 | 0.635 | 0.001 | 0.000 | -10.704 | 0.000 | -10.071 | -0.376 |
F8 NE APARTMENT | 2.433 | -16.316 | 0.000 | 0.000 | 3.743 | 2.413 | 12.213 | 13.628 | 0.000 | 0.621 | 1.027 | 0.000 | -10.370 | 0.000 | -9.391 | -0.000 |
F8 N1 APARTMENT | 0.682 | -12.949 | 0.000 | 0.000 | 3.732 | 2.413 | 12.213 | 4.193 | 0.000 | 0.468 | 3.118 | 0.000 | -6.805 | 0.000 | -7.065 | 0.000 |
F8 N2 APARTMENT | 0.684 | -12.986 | 0.000 | 0.000 | 3.734 | 2.413 | 12.213 | 4.190 | 0.000 | 0.467 | 3.151 | 0.000 | -6.799 | 0.000 | -7.066 | 0.000 |
F8 S1 APARTMENT | 0.150 | -23.014 | 0.000 | 0.000 | 3.596 | 2.413 | 12.213 | 17.717 | 0.000 | 0.455 | 0.988 | 0.000 | -6.739 | 0.000 | -7.779 | -0.000 |
F8 S2 APARTMENT | 0.151 | -23.048 | 0.000 | 0.000 | 3.597 | 2.413 | 12.213 | 17.714 | 0.000 | 0.456 | 1.024 | 0.000 | -6.737 | 0.000 | -7.782 | -0.000 |
F9 SW APARTMENT | 0.909 | -23.721 | 0.000 | 0.000 | 3.642 | 2.413 | 12.213 | 26.376 | 0.000 | 0.672 | 0.003 | 0.000 | -10.988 | 0.000 | -10.361 | -1.154 |
F9 NW APARTMENT | 3.285 | -15.249 | 0.000 | 0.000 | 3.733 | 2.413 | 12.213 | 13.076 | 0.000 | 0.653 | 0.517 | 0.000 | -10.937 | 0.000 | -9.704 | -0.000 |
F9 SE APARTMENT | 0.777 | -24.833 | 0.000 | 0.000 | 3.653 | 2.413 | 12.213 | 27.143 | 0.000 | 0.664 | 0.001 | 0.000 | -10.670 | 0.000 | -10.369 | -0.991 |
F9 NE APARTMENT | 2.959 | -16.327 | 0.000 | 0.000 | 3.749 | 2.413 | 12.213 | 13.619 | 0.000 | 0.645 | 0.760 | 0.000 | -10.362 | 0.000 | -9.669 | -0.000 |
F9 N1 APARTMENT | 0.965 | -12.882 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 4.194 | 0.000 | 0.488 | 2.912 | 0.000 | -6.792 | 0.000 | -7.251 | -0.000 |
F9 N2 APARTMENT | 0.968 | -12.917 | 0.000 | 0.000 | 3.741 | 2.413 | 12.213 | 4.190 | 0.000 | 0.488 | 2.944 | 0.000 | -6.787 | 0.000 | -7.254 | -0.000 |
F9 S1 APARTMENT | 0.205 | -22.324 | 0.000 | 0.000 | 3.612 | 2.413 | 12.213 | 17.705 | 0.000 | 0.478 | 0.389 | 0.000 | -6.712 | 0.000 | -7.979 | -0.000 |
F9 S2 APARTMENT | 0.205 | -22.369 | 0.000 | 0.000 | 3.612 | 2.413 | 12.213 | 17.702 | 0.000 | 0.479 | 0.437 | 0.000 | -6.710 | 0.000 | -7.983 | -0.000 |
T SW APARTMENT | 4.351 | -24.474 | 0.000 | 0.000 | 3.706 | 2.413 | 12.213 | 26.051 | 0.000 | 0.693 | 0.000 | 0.000 | -10.372 | 0.000 | -10.481 | -4.099 |
T NW APARTMENT | 7.501 | -16.418 | 0.000 | 0.000 | 3.754 | 2.413 | 12.213 | 12.764 | 0.000 | 0.669 | 0.000 | 0.000 | -10.494 | 0.000 | -9.988 | -2.414 |
T SE APARTMENT | 3.990 | -24.974 | 0.000 | 0.000 | 3.715 | 2.413 | 12.213 | 26.840 | 0.000 | 0.690 | 0.001 | 0.000 | -10.092 | 0.000 | -10.500 | -4.293 |
T NE APARTMENT | 6.733 | -16.832 | 0.000 | 0.000 | 3.771 | 2.413 | 12.213 | 13.375 | 0.000 | 0.668 | 0.000 | 0.000 | -9.990 | 0.000 | -9.944 | -2.406 |
T N1 APARTMENT | 3.445 | -12.998 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 4.084 | 0.000 | 0.503 | 0.550 | 0.000 | -6.525 | 0.000 | -7.448 | -0.000 |
T N2 APARTMENT | 3.465 | -13.035 | 0.000 | 0.000 | 3.764 | 2.413 | 12.213 | 4.078 | 0.000 | 0.503 | 0.572 | 0.000 | -6.519 | 0.000 | -7.455 | -0.000 |
T S1 APARTMENT | 1.375 | -21.725 | 0.000 | 0.000 | 3.688 | 2.413 | 12.213 | 17.546 | 0.000 | 0.514 | 0.001 | 0.000 | -6.368 | 0.000 | -8.047 | -1.610 |
T S2 APARTMENT | 1.382 | -21.771 | 0.000 | 0.000 | 3.688 | 2.413 | 12.213 | 17.541 | 0.000 | 0.514 | 0.002 | 0.000 | -6.364 | 0.000 | -8.053 | -1.564 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 6.542 | 0.000 | 1.857 | 7.411 | 0.000 | -2.333 | 0.000 | -32.007 | -0.003 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.983 | 0.000 | 0.021 | 0.000 | 0.000 | -1.358 | 0.000 | -0.628 | -19.546 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.931 | 0.000 | 0.023 | 0.000 | 0.000 | -1.406 | 0.000 | -0.767 | -19.311 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.902 | 0.000 | 0.025 | 0.000 | 0.000 | -1.429 | 0.000 | -0.869 | -19.159 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 2.867 | 0.000 | 0.022 | 0.000 | 0.000 | -1.464 | 0.000 | -0.991 | -37.494 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.880 | 0.000 | 0.029 | 0.000 | 0.000 | -1.438 | 0.000 | -1.008 | -18.993 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.880 | 0.000 | 0.031 | 0.000 | 0.000 | -1.430 | 0.000 | -1.055 | -18.956 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.876 | 0.000 | 0.032 | 0.000 | 0.000 | -1.428 | 0.000 | -1.101 | -18.909 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.875 | 0.000 | 0.032 | 0.000 | 0.000 | -1.426 | 0.000 | -1.141 | -18.869 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 2.808 | 0.000 | 0.017 | 0.000 | 0.000 | -1.377 | 0.000 | -1.214 | -26.699 |
Total Facility | 94.704 | -1517.590 | 0.000 | 0.000 | 291.295 | 416.414 | 980.287 | 1287.450 | 0.000 | 39.107 | 92.883 | 0.000 | -702.118 | 0.000 | -636.464 | -345.962 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 28-SEP-16:30 | 0.00 | -2488.03 | 0.00 | 0.00 | 81.74 | 144.04 | 588.62 | 3337.83 | 0.00 | 33.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1697.58 |
G NW APARTMENT | 25-JUN-17:20 | 0.00 | -2345.92 | 0.00 | 0.00 | 139.30 | 194.45 | 588.62 | 3265.26 | 0.00 | 93.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1935.13 |
OFFICE | 12-SEP-12:30 | 0.00 | -3084.83 | 0.00 | 0.00 | 65.17 | 1622.33 | 544.91 | 3069.56 | 0.00 | 31.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2248.34 |
G NE APARTMENT | 28-JUN-08:15 | 0.00 | -1726.35 | 0.00 | 0.00 | 40.58 | 28.81 | 394.37 | 2858.43 | 0.00 | 180.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1776.16 |
G N1 APARTMENT | 11-JUN-18:30 | 0.00 | -1226.35 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 969.60 | 0.00 | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -829.44 |
G N2 APARTMENT | 11-JUN-18:30 | 0.00 | -1205.39 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 970.08 | 0.00 | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -850.88 |
G S1 APARTMENT | 29-SEP-11:30 | 0.00 | -1425.86 | 0.00 | 0.00 | 39.53 | 28.81 | 406.15 | 3271.56 | 0.00 | 60.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2381.18 |
G S2 APARTMENT | 29-SEP-11:30 | 0.00 | -1482.87 | 0.00 | 0.00 | 39.59 | 28.81 | 406.15 | 3270.96 | 0.00 | 63.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2325.85 |
F2 SW APARTMENT | 11-OCT-15:08 | 0.00 | -3223.15 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3366.29 | 0.00 | 727.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1491.66 |
F2 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3003.09 | 0.00 | 0.00 | 139.62 | 194.45 | 588.62 | 3229.62 | 0.00 | 134.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1283.77 |
F2 SE APARTMENT | 01-OCT-11:15 | 0.00 | -2867.70 | 0.00 | 0.00 | 40.64 | 28.81 | 406.15 | 3919.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6.86 | -1520.86 |
F2 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2303.47 | 0.00 | 0.00 | 40.49 | 28.81 | 394.37 | 2829.86 | 0.00 | 198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1188.55 |
F2 N1 APARTMENT | 11-JUN-18:30 | 0.00 | -1655.17 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 951.22 | 0.00 | 189.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -405.38 |
F2 N2 APARTMENT | 11-JUN-18:30 | 0.00 | -1638.19 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 951.52 | 0.00 | 189.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -422.65 |
F2 S1 APARTMENT | 01-NOV-12:30 | 0.00 | -2099.95 | 0.00 | 0.00 | 40.20 | 28.81 | 388.49 | 3593.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -192.22 | -1758.55 |
F2 S2 APARTMENT | 01-NOV-12:30 | 0.00 | -2117.61 | 0.00 | 0.00 | 40.21 | 28.81 | 388.49 | 3593.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -192.16 | -1740.75 |
F3 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3259.67 | 0.00 | 0.00 | 48.80 | 100.83 | 470.89 | 3282.69 | 0.00 | 600.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1243.88 |
F3 NW APARTMENT | 22-JUL-17:30 | 0.00 | -3019.42 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 3026.50 | 0.00 | 184.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1116.57 |
F3 SE APARTMENT | 01-OCT-10:45 | 0.00 | -2728.91 | 0.00 | 0.00 | 40.69 | 28.81 | 412.03 | 4054.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.76 | -1713.93 |
F3 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2346.50 | 0.00 | 0.00 | 40.46 | 28.81 | 394.37 | 2818.12 | 0.00 | 210.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1145.76 |
F3 N1 APARTMENT | 07-JUN-18:00 | 0.00 | -1725.93 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 204.72 | 0.00 | 471.70 | 124.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 07-JUN-18:00 | 0.00 | -1712.68 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 204.54 | 0.00 | 468.53 | 114.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 29-DEC-12:45 | 0.00 | -2169.49 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3969.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61.84 | -2214.32 |
F3 S2 APARTMENT | 29-DEC-12:45 | 0.00 | -2176.74 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3969.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61.84 | -2206.93 |
F4 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3284.93 | 0.00 | 0.00 | 48.80 | 100.83 | 470.89 | 3264.25 | 0.00 | 647.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1247.27 |
F4 NW APARTMENT | 22-JUL-17:30 | 0.00 | -3036.35 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 3012.46 | 0.00 | 205.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1106.62 |
F4 SE APARTMENT | 01-OCT-10:45 | 0.00 | -2729.32 | 0.00 | 0.00 | 40.69 | 28.81 | 412.03 | 4044.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98.67 | -1697.76 |
F4 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2371.75 | 0.00 | 0.00 | 40.49 | 28.81 | 394.37 | 2810.43 | 0.00 | 222.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1124.56 |
F4 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1752.74 | 0.00 | 0.00 | 162.98 | 158.44 | 500.33 | 3.62 | 0.00 | 606.02 | 321.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1738.37 | 0.00 | 0.00 | 162.98 | 158.44 | 500.33 | 3.75 | 0.00 | 603.27 | 309.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 29-DEC-12:45 | 0.00 | -2186.92 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 3957.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.35 | -2176.75 |
F4 S2 APARTMENT | 29-DEC-12:45 | 0.00 | -2192.35 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 3957.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.36 | -2171.21 |
M SW APARTMENT | 10-OCT-16:00 | 0.00 | -3330.29 | 0.00 | 0.00 | 48.84 | 100.83 | 470.89 | 3250.08 | 0.00 | 687.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1227.47 |
M NW APARTMENT | 22-JUL-17:30 | 0.00 | -3068.06 | 0.00 | 0.00 | 141.68 | 194.45 | 588.62 | 3000.66 | 0.00 | 222.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1079.91 |
M SE APARTMENT | 01-OCT-11:00 | 0.00 | -2761.16 | 0.00 | 0.00 | 40.47 | 28.81 | 412.03 | 3967.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.13 | -1639.49 |
M NE APARTMENT | 28-JUN-08:15 | 0.00 | -2412.05 | 0.00 | 0.00 | 40.50 | 28.81 | 394.37 | 2803.49 | 0.00 | 231.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.31 |
M N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1799.55 | 0.00 | 0.00 | 162.98 | 158.44 | 500.33 | 3.96 | 0.00 | 638.84 | 335.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1785.22 | 0.00 | 0.00 | 162.98 | 158.44 | 500.33 | 4.08 | 0.00 | 635.79 | 323.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 29-DEC-12:45 | 0.00 | -2220.17 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3946.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.43 | -2127.03 |
M S2 APARTMENT | 29-DEC-12:45 | 0.00 | -2225.16 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3946.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.44 | -2121.93 |
F6 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3298.03 | 0.00 | 0.00 | 48.87 | 100.83 | 470.89 | 3240.59 | 0.00 | 717.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1280.31 |
F6 NW APARTMENT | 22-JUL-17:30 | 0.00 | -3024.47 | 0.00 | 0.00 | 141.48 | 194.45 | 588.62 | 2992.56 | 0.00 | 236.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1129.34 |
F6 SE APARTMENT | 01-OCT-11:00 | 0.00 | -2726.59 | 0.00 | 0.00 | 40.51 | 28.81 | 412.03 | 3962.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.51 | -1666.85 |
F6 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2379.53 | 0.00 | 0.00 | 40.51 | 28.81 | 394.37 | 2799.26 | 0.00 | 237.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.38 |
F6 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1772.80 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 5.45 | 0.00 | 661.53 | 284.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1758.55 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 5.56 | 0.00 | 658.18 | 273.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 29-DEC-13:00 | 0.00 | -2180.55 | 0.00 | 0.00 | 40.61 | 28.81 | 406.15 | 3923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.96 | -2159.49 |
F6 S2 APARTMENT | 29-DEC-12:45 | 0.00 | -2185.27 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3939.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -80.61 | -2149.22 |
F7 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3286.10 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3232.15 | 0.00 | 742.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1309.13 |
F7 NW APARTMENT | 22-JUL-17:30 | 0.00 | -3009.50 | 0.00 | 0.00 | 141.33 | 194.45 | 588.62 | 2985.28 | 0.00 | 249.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1149.28 |
F7 SE APARTMENT | 01-OCT-11:00 | 0.00 | -2714.81 | 0.00 | 0.00 | 40.54 | 28.81 | 412.03 | 3957.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52.84 | -1671.32 |
F7 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2373.29 | 0.00 | 0.00 | 40.52 | 28.81 | 394.37 | 2794.96 | 0.00 | 243.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1129.35 |
F7 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1770.51 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 6.15 | 0.00 | 680.91 | 261.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1756.34 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 6.25 | 0.00 | 677.29 | 251.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 29-DEC-13:00 | 0.00 | -2165.61 | 0.00 | 0.00 | 40.68 | 28.81 | 406.15 | 3919.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.24 | -2166.80 |
F7 S2 APARTMENT | 29-DEC-13:00 | 0.00 | -2170.16 | 0.00 | 0.00 | 40.67 | 28.81 | 406.15 | 3918.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.25 | -2162.16 |
F8 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3288.25 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3224.59 | 0.00 | 766.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1323.59 |
F8 NW APARTMENT | 18-JUL-17:20 | 0.00 | -3013.65 | 0.00 | 0.00 | 138.55 | 194.45 | 588.62 | 3226.43 | 0.00 | 264.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1399.39 |
F8 SE APARTMENT | 01-OCT-11:00 | 0.00 | -2716.47 | 0.00 | 0.00 | 40.57 | 28.81 | 412.03 | 3952.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.75 | -1662.98 |
F8 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2377.57 | 0.00 | 0.00 | 40.51 | 28.81 | 394.37 | 2790.52 | 0.00 | 248.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.05 |
F8 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1782.52 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 6.37 | 0.00 | 698.26 | 256.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1768.44 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 6.46 | 0.00 | 694.40 | 245.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 29-DEC-13:00 | 0.00 | -2161.05 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3915.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.08 | -2165.06 |
F8 S2 APARTMENT | 29-DEC-13:00 | 0.00 | -2165.50 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3915.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.09 | -2160.52 |
F9 SW APARTMENT | 10-OCT-15:45 | 0.00 | -3393.77 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3489.85 | 0.00 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1522.61 |
F9 NW APARTMENT | 18-JUL-17:20 | 0.00 | -3126.35 | 0.00 | 0.00 | 138.76 | 194.45 | 588.62 | 3217.10 | 0.00 | 276.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1288.81 |
F9 SE APARTMENT | 10-OCT-15:45 | 0.00 | -2793.28 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 1466.77 | 0.00 | 818.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -112.17 |
F9 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2416.81 | 0.00 | 0.00 | 40.54 | 28.81 | 394.37 | 2786.02 | 0.00 | 254.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1087.34 |
F9 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1885.38 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 4.21 | 0.00 | 720.34 | 339.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1871.02 | 0.00 | 0.00 | 162.97 | 158.44 | 500.33 | 4.34 | 0.00 | 716.79 | 328.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 07-NOV-11:45 | 0.00 | -2179.44 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3912.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.07 | -2151.82 |
F9 S2 APARTMENT | 07-NOV-11:45 | 0.00 | -2188.17 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3912.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.08 | -2142.88 |
T SW APARTMENT | 10-OCT-15:45 | 0.00 | -4143.12 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3446.67 | 0.00 | 958.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -883.00 |
T NW APARTMENT | 18-JUL-17:20 | 0.00 | -3852.45 | 0.00 | 0.00 | 138.91 | 194.45 | 588.62 | 3166.24 | 0.00 | 286.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -522.48 |
T SE APARTMENT | 01-OCT-12:00 | 0.00 | -3588.82 | 0.00 | 0.00 | 39.87 | 28.81 | 406.15 | 3622.47 | 0.00 | 44.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -553.27 |
T NE APARTMENT | 28-JUN-08:15 | 0.00 | -3012.37 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2753.66 | 0.00 | 284.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -489.98 |
T N1 APARTMENT | 23-JUN-20:53 | 0.00 | -2389.01 | 0.00 | 0.00 | 162.99 | 158.44 | 500.33 | 4.34 | 0.00 | 943.84 | 619.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 23-JUN-20:53 | 0.00 | -2385.19 | 0.00 | 0.00 | 162.99 | 158.44 | 500.33 | 4.76 | 0.00 | 945.87 | 612.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 07-NOV-12:45 | 0.00 | -2930.81 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3641.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.50 | -1119.14 |
T S2 APARTMENT | 07-NOV-12:45 | 0.00 | -2942.68 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.50 | -1107.02 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-17:30 | 0.00 | -174963.77 | 0.00 | 0.00 | 11106.11 | 22204.40 | 47141.46 | 102332.50 | 0.00 | 14789.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22610.52 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 18-JAN-01:30 | 1023.99 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -979.11 | 0.00 | -424.83 | -65.46 |
G NW APARTMENT | 17-JAN-08:05 | 1128.54 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -808.40 | 0.00 | -433.66 | -392.15 |
OFFICE | 17-JAN-07:50 | 1090.71 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -783.55 | 0.00 | -446.29 | -435.43 |
G NE APARTMENT | 14-DEC-04:00 | 1170.18 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 44.33 | 0.00 | -988.95 | 0.00 | -653.30 | 0.00 |
G N1 APARTMENT | 24-JAN-14:55 | 1055.52 | 0.00 | 0.00 | 0.00 | 46.29 | 28.81 | 382.60 | 211.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -962.01 | -762.82 |
G N2 APARTMENT | 24-JAN-14:55 | 1057.77 | 0.00 | 0.00 | 0.00 | 46.29 | 28.81 | 382.60 | 211.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -961.94 | -765.13 |
G S1 APARTMENT | 05-FEB-06:55 | 730.62 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.17 | 0.00 | -155.94 | -486.86 |
G S2 APARTMENT | 05-FEB-06:55 | 718.74 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.18 | 0.00 | -155.94 | -474.98 |
F2 SW APARTMENT | 18-JAN-02:00 | 1012.34 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 152.18 | 0.00 | -1015.78 | 0.00 | -594.15 | 0.00 |
F2 NW APARTMENT | 14-DEC-04:00 | 1226.20 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 325.84 | 0.00 | -1040.12 | 0.00 | -939.67 | 0.00 |
F2 SE APARTMENT | 18-JAN-02:00 | 982.46 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 191.81 | 0.00 | -1025.53 | 0.00 | -594.15 | 0.00 |
F2 NE APARTMENT | 14-DEC-04:00 | 1323.81 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 211.98 | 0.00 | -1023.88 | 0.00 | -939.67 | 0.00 |
F2 N1 APARTMENT | 24-JAN-15:00 | 902.54 | 0.00 | 0.00 | 0.00 | 44.95 | 28.81 | 382.60 | 183.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1181.84 | -360.40 |
F2 N2 APARTMENT | 24-JAN-15:00 | 901.84 | 0.00 | 0.00 | 0.00 | 44.95 | 28.81 | 382.60 | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1181.81 | -359.70 |
F2 S1 APARTMENT | 18-JAN-23:15 | 560.14 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.41 | 0.00 | -128.93 | -324.87 |
F2 S2 APARTMENT | 18-JAN-23:15 | 555.12 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.47 | 0.00 | -128.93 | -319.79 |
F3 SW APARTMENT | 18-JAN-01:30 | 1034.92 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 281.82 | 0.00 | -1038.28 | 0.00 | -723.88 | 0.00 |
F3 NW APARTMENT | 14-DEC-04:00 | 1324.34 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 417.60 | 0.00 | -1056.44 | 0.00 | -1113.25 | 0.00 |
F3 SE APARTMENT | 18-JAN-01:30 | 1048.63 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 277.62 | 0.00 | -1047.78 | 0.00 | -723.88 | 0.00 |
F3 NE APARTMENT | 14-DEC-04:00 | 1423.96 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 299.79 | 0.00 | -1038.24 | 0.00 | -1113.25 | 0.00 |
F3 N1 APARTMENT | 24-JAN-15:00 | 1035.29 | 0.00 | 0.00 | 0.00 | 44.44 | 28.81 | 382.60 | 172.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1331.35 | -331.86 |
F3 N2 APARTMENT | 24-JAN-15:00 | 1033.20 | 0.00 | 0.00 | 0.00 | 44.44 | 28.81 | 382.60 | 172.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1331.31 | -329.88 |
F3 S1 APARTMENT | 19-JAN-05:45 | 457.24 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -570.48 | 0.00 | -51.29 | -371.87 |
F3 S2 APARTMENT | 17-JAN-08:45 | 392.42 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.79 | 0.00 | -419.83 | -76.47 |
F4 SW APARTMENT | 18-JAN-01:30 | 1100.28 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 312.21 | 0.00 | -1048.29 | 0.00 | -809.61 | 0.00 |
F4 NW APARTMENT | 14-DEC-04:00 | 1437.00 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 445.76 | 0.00 | -1065.36 | 0.00 | -1245.16 | 0.00 |
F4 SE APARTMENT | 18-JAN-01:30 | 1120.33 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 302.35 | 0.00 | -1058.47 | 0.00 | -809.61 | 0.00 |
F4 NE APARTMENT | 14-DEC-04:00 | 1532.48 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 331.30 | 0.00 | -1046.37 | 0.00 | -1245.16 | 0.00 |
F4 N1 APARTMENT | 24-JAN-15:00 | 1119.33 | 0.00 | 0.00 | 0.00 | 44.24 | 28.81 | 382.60 | 166.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1450.58 | -290.69 |
F4 N2 APARTMENT | 24-JAN-15:00 | 1115.88 | 0.00 | 0.00 | 0.00 | 44.25 | 28.81 | 382.60 | 166.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1450.53 | -287.40 |
F4 S1 APARTMENT | 18-JAN-01:30 | 410.41 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 283.66 | 0.00 | -651.14 | 0.00 | -488.34 | 0.00 |
F4 S2 APARTMENT | 18-JAN-01:30 | 411.79 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 282.22 | 0.00 | -651.08 | 0.00 | -488.34 | 0.00 |
M SW APARTMENT | 18-JAN-01:30 | 1156.25 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 334.88 | 0.00 | -1056.13 | 0.00 | -880.41 | 0.00 |
M NW APARTMENT | 14-DEC-04:00 | 1524.64 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 473.98 | 0.00 | -1072.27 | 0.00 | -1354.10 | 0.00 |
M SE APARTMENT | 18-JAN-01:30 | 1176.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 325.85 | 0.00 | -1067.07 | 0.00 | -880.41 | 0.00 |
M NE APARTMENT | 14-DEC-04:00 | 1615.68 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 363.61 | 0.00 | -1052.94 | 0.00 | -1354.10 | 0.00 |
M N1 APARTMENT | 09-NOV-10:15 | 1376.53 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 96.05 | 0.00 | 0.00 | 23.83 | 0.00 | 0.00 | 0.00 | -1972.11 | 0.00 |
M N2 APARTMENT | 09-NOV-10:15 | 1388.69 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 96.04 | 0.00 | 0.00 | 11.35 | 0.00 | 0.00 | 0.00 | -1971.78 | 0.00 |
M S1 APARTMENT | 18-JAN-01:30 | 435.61 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 306.43 | 0.00 | -656.41 | 0.00 | -531.04 | 0.00 |
M S2 APARTMENT | 18-JAN-01:30 | 437.10 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 304.87 | 0.00 | -656.34 | 0.00 | -531.04 | 0.00 |
F6 SW APARTMENT | 18-JAN-01:30 | 1253.54 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 301.92 | 0.00 | -1059.33 | 0.00 | -941.54 | 0.00 |
F6 NW APARTMENT | 09-NOV-10:15 | 1790.61 | 0.00 | 0.00 | 0.00 | 41.24 | 28.81 | 406.15 | 167.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2197.71 | -236.77 |
F6 SE APARTMENT | 18-JAN-01:30 | 1274.65 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 292.30 | 0.00 | -1070.82 | 0.00 | -941.54 | 0.00 |
F6 NE APARTMENT | 14-DEC-04:00 | 1748.10 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 327.48 | 0.00 | -1055.16 | 0.00 | -1448.17 | 0.00 |
F6 N1 APARTMENT | 09-NOV-10:15 | 2003.91 | 0.00 | 0.00 | 0.00 | 40.84 | 28.81 | 406.15 | 95.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2081.58 | -493.71 |
F6 N2 APARTMENT | 09-NOV-10:15 | 1955.52 | 0.00 | 0.00 | 0.00 | 40.85 | 28.81 | 406.15 | 95.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2082.07 | -444.89 |
F6 S1 APARTMENT | 18-JAN-01:30 | 509.54 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 271.50 | 0.00 | -658.54 | 0.00 | -567.91 | 0.00 |
F6 S2 APARTMENT | 18-JAN-01:30 | 510.90 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 270.08 | 0.00 | -658.48 | 0.00 | -567.91 | 0.00 |
F7 SW APARTMENT | 18-JAN-01:30 | 1335.18 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 277.68 | 0.00 | -1062.47 | 0.00 | -995.79 | 0.00 |
F7 NW APARTMENT | 09-NOV-10:15 | 1902.06 | 0.00 | 0.00 | 0.00 | 41.60 | 28.81 | 406.15 | 169.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2306.71 | -241.13 |
F7 SE APARTMENT | 18-JAN-01:30 | 1356.97 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 267.83 | 0.00 | -1074.41 | 0.00 | -995.79 | 0.00 |
F7 NE APARTMENT | 14-DEC-04:00 | 1853.37 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 308.12 | 0.00 | -1057.56 | 0.00 | -1531.68 | 0.00 |
F7 N1 APARTMENT | 09-NOV-10:15 | 2066.98 | 0.00 | 0.00 | 0.00 | 41.15 | 28.81 | 406.15 | 96.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2189.71 | -449.69 |
F7 N2 APARTMENT | 09-NOV-10:15 | 2060.21 | 0.00 | 0.00 | 0.00 | 41.17 | 28.81 | 406.15 | 96.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2189.61 | -443.15 |
F7 S1 APARTMENT | 18-JAN-01:30 | 564.78 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 251.03 | 0.00 | -660.58 | 0.00 | -600.63 | 0.00 |
F7 S2 APARTMENT | 18-JAN-01:30 | 565.87 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 249.88 | 0.00 | -660.52 | 0.00 | -600.63 | 0.00 |
F8 SW APARTMENT | 18-JAN-01:15 | 1422.33 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 258.14 | 0.00 | -1066.56 | 0.00 | -1059.32 | 0.00 |
F8 NW APARTMENT | 09-NOV-10:15 | 1889.78 | 0.00 | 0.00 | 0.00 | 41.94 | 28.81 | 406.15 | 171.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2411.93 | -126.10 |
F8 SE APARTMENT | 18-JAN-01:15 | 1444.58 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 248.22 | 0.00 | -1078.89 | 0.00 | -1059.31 | 0.00 |
F8 NE APARTMENT | 14-DEC-04:00 | 1951.85 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 287.14 | 0.00 | -1059.49 | 0.00 | -1607.25 | 0.00 |
F8 N1 APARTMENT | 09-NOV-10:15 | 1994.71 | 0.00 | 0.00 | 0.00 | 41.47 | 28.81 | 406.15 | 97.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2289.93 | -278.76 |
F8 N2 APARTMENT | 09-NOV-10:15 | 1985.84 | 0.00 | 0.00 | 0.00 | 41.49 | 28.81 | 406.15 | 97.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2289.83 | -270.17 |
F8 S1 APARTMENT | 18-JAN-01:30 | 618.45 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 228.30 | 0.00 | -661.92 | 0.00 | -630.24 | 0.00 |
F8 S2 APARTMENT | 18-JAN-01:30 | 619.57 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 227.13 | 0.00 | -661.87 | 0.00 | -630.24 | 0.00 |
F9 SW APARTMENT | 18-JAN-01:30 | 1589.50 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 117.67 | 0.00 | -1062.66 | 0.00 | -1089.92 | 0.00 |
F9 NW APARTMENT | 14-DEC-04:00 | 2005.36 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 320.46 | 0.00 | -1076.97 | 0.00 | -1676.59 | 0.00 |
F9 SE APARTMENT | 18-JAN-01:30 | 1611.15 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 108.70 | 0.00 | -1075.33 | 0.00 | -1089.92 | 0.00 |
F9 NE APARTMENT | 14-DEC-04:00 | 2098.29 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 209.03 | 0.00 | -1058.48 | 0.00 | -1676.59 | 0.00 |
F9 N1 APARTMENT | 09-NOV-10:15 | 2023.33 | 0.00 | 0.00 | 0.00 | 41.89 | 28.81 | 406.15 | 100.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2383.49 | -217.56 |
F9 N2 APARTMENT | 09-NOV-10:15 | 2026.59 | 0.00 | 0.00 | 0.00 | 41.91 | 28.81 | 406.15 | 101.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2383.40 | -221.11 |
F9 S1 APARTMENT | 09-NOV-10:15 | 761.50 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 120.98 | 0.00 | 0.00 | 1044.65 | 0.00 | 0.00 | 0.00 | -2402.84 | 0.00 |
F9 S2 APARTMENT | 09-NOV-10:15 | 742.39 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 120.88 | 0.00 | 0.00 | 1064.25 | 0.00 | 0.00 | 0.00 | -2403.22 | 0.00 |
T SW APARTMENT | 17-JAN-04:00 | 2195.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1072.01 | 0.00 | -1156.57 | -394.33 |
T NW APARTMENT | 14-DEC-04:00 | 2634.60 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1044.98 | 0.00 | -1740.77 | -276.60 |
T SE APARTMENT | 17-JAN-04:00 | 2217.12 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.03 | 0.00 | -1156.57 | -402.26 |
T NE APARTMENT | 14-DEC-04:00 | 2683.33 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1029.45 | 0.00 | -1740.77 | -340.86 |
T N1 APARTMENT | 24-OCT-12:15 | 2124.88 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 384.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2165.05 | -802.34 |
T N2 APARTMENT | 24-OCT-12:15 | 2127.19 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 384.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2165.05 | -804.45 |
T S1 APARTMENT | 09-NOV-16:45 | 1443.11 | 0.00 | 0.00 | 0.00 | 56.90 | 100.83 | 470.89 | 0.00 | 0.00 | 0.00 | 528.17 | 0.00 | -178.91 | 0.00 | -2420.99 | 0.00 |
T S2 APARTMENT | 09-NOV-16:45 | 1441.73 | 0.00 | 0.00 | 0.00 | 56.90 | 100.83 | 470.89 | 0.00 | 0.00 | 0.00 | 529.59 | 0.00 | -178.95 | 0.00 | -2420.99 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JAN-01:30 | 80961.58 | 0.00 | 0.00 | 0.00 | 14984.05 | 7980.64 | 19245.24 | 0.00 | 0.00 | 0.00 | 2793.32 | 0.00 | -68974.78 | 0.00 | -56990.06 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sec1.1A-General InformationData | |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 83.00 |
Number of hours cooling loads not met | 592.00 |
Number of hours not met | 675.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.44 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 39.47 | 0.00 | 85.75 | 87410.18 | 0.00 | 0.00 |
Space Cooling | 543.05 | 59469.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 43.59 | 1393.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 19.13 | 1879.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 699.65 | 22185.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1107.29 | 86775.67 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3081.65 | 1193.04 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3081.65 |
Natural Gas | 0.00 | 1193.04 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4274.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 5.04 |
Space Cooling | 69.30 |
Fans-Interior | 89.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 32.15 |
Subtotal | 393.24 |
Natural Gas [MJ/m2] | |
Space Heating | 10.94 |
Service Water Heating | 141.30 |
Miscellaneous | -0.00 |
Subtotal | 152.24 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.74 |
Space Heating | 2.93 |
Space Cooling | 12.70 |
Fans-Interior | 16.37 |
Service Water Heating | 25.90 |
Receptacle Equipment | 26.46 |
Miscellaneous | 5.89 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.258910 |
G NW APARTMENT DIRECT AIR | 0.255012 |
OFFICE DIRECT AIR | 0.327712 |
G NE APARTMENT DIRECT AIR | 0.185878 |
G N1 APARTMENT DIRECT AIR | 0.132973 |
G N2 APARTMENT DIRECT AIR | 0.130982 |
G S1 APARTMENT DIRECT AIR | 0.136322 |
G S2 APARTMENT DIRECT AIR | 0.142188 |
F2 SW APARTMENT DIRECT AIR | 0.333584 |
F2 NW APARTMENT DIRECT AIR | 0.326109 |
F2 SE APARTMENT DIRECT AIR | 0.289528 |
F2 NE APARTMENT DIRECT AIR | 0.247149 |
F2 N1 APARTMENT DIRECT AIR | 0.177396 |
F2 N2 APARTMENT DIRECT AIR | 0.175768 |
F2 S1 APARTMENT DIRECT AIR | 0.183880 |
F2 S2 APARTMENT DIRECT AIR | 0.186098 |
F3 SW APARTMENT DIRECT AIR | 0.335365 |
F3 NW APARTMENT DIRECT AIR | 0.328661 |
F3 SE APARTMENT DIRECT AIR | 0.273960 |
F3 NE APARTMENT DIRECT AIR | 0.251176 |
F3 N1 APARTMENT DIRECT AIR | 0.181470 |
F3 N2 APARTMENT DIRECT AIR | 0.179856 |
F3 S1 APARTMENT DIRECT AIR | 0.188061 |
F3 S2 APARTMENT DIRECT AIR | 0.189196 |
F4 SW APARTMENT DIRECT AIR | 0.336964 |
F4 NW APARTMENT DIRECT AIR | 0.330385 |
F4 SE APARTMENT DIRECT AIR | 0.274280 |
F4 NE APARTMENT DIRECT AIR | 0.252823 |
F4 N1 APARTMENT DIRECT AIR | 0.183508 |
F4 N2 APARTMENT DIRECT AIR | 0.181900 |
F4 S1 APARTMENT DIRECT AIR | 0.190023 |
F4 S2 APARTMENT DIRECT AIR | 0.190976 |
M SW APARTMENT DIRECT AIR | 0.341016 |
M NW APARTMENT DIRECT AIR | 0.334616 |
M SE APARTMENT DIRECT AIR | 0.278516 |
M NE APARTMENT DIRECT AIR | 0.256935 |
M N1 APARTMENT DIRECT AIR | 0.187784 |
M N2 APARTMENT DIRECT AIR | 0.186181 |
M S1 APARTMENT DIRECT AIR | 0.194174 |
M S2 APARTMENT DIRECT AIR | 0.195086 |
F6 SW APARTMENT DIRECT AIR | 0.337333 |
F6 NW APARTMENT DIRECT AIR | 0.330882 |
F6 SE APARTMENT DIRECT AIR | 0.275301 |
F6 NE APARTMENT DIRECT AIR | 0.253245 |
F6 N1 APARTMENT DIRECT AIR | 0.184445 |
F6 N2 APARTMENT DIRECT AIR | 0.182854 |
F6 S1 APARTMENT DIRECT AIR | 0.190827 |
F6 S2 APARTMENT DIRECT AIR | 0.191718 |
F7 SW APARTMENT DIRECT AIR | 0.336398 |
F7 NW APARTMENT DIRECT AIR | 0.330018 |
F7 SE APARTMENT DIRECT AIR | 0.274776 |
F7 NE APARTMENT DIRECT AIR | 0.252366 |
F7 N1 APARTMENT DIRECT AIR | 0.183802 |
F7 N2 APARTMENT DIRECT AIR | 0.182219 |
F7 S1 APARTMENT DIRECT AIR | 0.190098 |
F7 S2 APARTMENT DIRECT AIR | 0.190972 |
F8 SW APARTMENT DIRECT AIR | 0.337093 |
F8 NW APARTMENT DIRECT AIR | 0.330781 |
F8 SE APARTMENT DIRECT AIR | 0.275720 |
F8 NE APARTMENT DIRECT AIR | 0.252998 |
F8 N1 APARTMENT DIRECT AIR | 0.184753 |
F8 N2 APARTMENT DIRECT AIR | 0.183180 |
F8 S1 APARTMENT DIRECT AIR | 0.190874 |
F8 S2 APARTMENT DIRECT AIR | 0.191734 |
F9 SW APARTMENT DIRECT AIR | 0.349150 |
F9 NW APARTMENT DIRECT AIR | 0.342849 |
F9 SE APARTMENT DIRECT AIR | 0.284561 |
F9 NE APARTMENT DIRECT AIR | 0.257598 |
F9 N1 APARTMENT DIRECT AIR | 0.195323 |
F9 N2 APARTMENT DIRECT AIR | 0.193734 |
F9 S1 APARTMENT DIRECT AIR | 0.198443 |
F9 S2 APARTMENT DIRECT AIR | 0.199351 |
T SW APARTMENT DIRECT AIR | 0.430106 |
T NW APARTMENT DIRECT AIR | 0.418217 |
T SE APARTMENT DIRECT AIR | 0.366917 |
T NE APARTMENT DIRECT AIR | 0.324820 |
T N1 APARTMENT DIRECT AIR | 0.248549 |
T N2 APARTMENT DIRECT AIR | 0.248245 |
T S1 APARTMENT DIRECT AIR | 0.290618 |
T S2 APARTMENT DIRECT AIR | 0.291477 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.258910 |
AIRLOOP G NW MAIN BRANCH | 0.255012 |
AIRLOOP OFFICE MAIN BRANCH | 0.327712 |
AIRLOOP G NE MAIN BRANCH | 0.185878 |
AIRLOOP G N1 MAIN BRANCH | 0.132973 |
AIRLOOP G N2 MAIN BRANCH | 0.130982 |
AIRLOOP G S1 MAIN BRANCH | 0.136322 |
AIRLOOP G S2 MAIN BRANCH | 0.142188 |
AIRLOOP F2 SW MAIN BRANCH | 0.333584 |
AIRLOOP F2 NW MAIN BRANCH | 0.326109 |
AIRLOOP F2 SE MAIN BRANCH | 0.289528 |
AIRLOOP F2 NE MAIN BRANCH | 0.247149 |
AIRLOOP F2 N1 MAIN BRANCH | 0.177396 |
AIRLOOP F2 N2 MAIN BRANCH | 0.175768 |
AIRLOOP F2 S1 MAIN BRANCH | 0.183880 |
AIRLOOP F2 S2 MAIN BRANCH | 0.186098 |
AIRLOOP F3 SW MAIN BRANCH | 0.335365 |
AIRLOOP F3 NW MAIN BRANCH | 0.328661 |
AIRLOOP F3 SE MAIN BRANCH | 0.273960 |
AIRLOOP F3 NE MAIN BRANCH | 0.251176 |
AIRLOOP F3 N1 MAIN BRANCH | 0.181470 |
AIRLOOP F3 N2 MAIN BRANCH | 0.179856 |
AIRLOOP F3 S1 MAIN BRANCH | 0.188061 |
AIRLOOP F3 S2 MAIN BRANCH | 0.189196 |
AIRLOOP F4 SW MAIN BRANCH | 0.336964 |
AIRLOOP F4 NW MAIN BRANCH | 0.330385 |
AIRLOOP F4 SE MAIN BRANCH | 0.274280 |
AIRLOOP F4 NE MAIN BRANCH | 0.252823 |
AIRLOOP F4 N1 MAIN BRANCH | 0.183508 |
AIRLOOP F4 N2 MAIN BRANCH | 0.181900 |
AIRLOOP F4 S1 MAIN BRANCH | 0.190023 |
AIRLOOP F4 S2 MAIN BRANCH | 0.190976 |
AIRLOOP M SW MAIN BRANCH | 0.341016 |
AIRLOOP M NW MAIN BRANCH | 0.334616 |
AIRLOOP M SE MAIN BRANCH | 0.278516 |
AIRLOOP M NE MAIN BRANCH | 0.256935 |
AIRLOOP M N1 MAIN BRANCH | 0.187784 |
AIRLOOP M N2 MAIN BRANCH | 0.186181 |
AIRLOOP M S1 MAIN BRANCH | 0.194174 |
AIRLOOP M S2 MAIN BRANCH | 0.195086 |
AIRLOOP F6 SW MAIN BRANCH | 0.337333 |
AIRLOOP F6 NW MAIN BRANCH | 0.330882 |
AIRLOOP F6 SE MAIN BRANCH | 0.275301 |
AIRLOOP F6 NE MAIN BRANCH | 0.253245 |
AIRLOOP F6 N1 MAIN BRANCH | 0.184445 |
AIRLOOP F6 N2 MAIN BRANCH | 0.182854 |
AIRLOOP F6 S1 MAIN BRANCH | 0.190827 |
AIRLOOP F6 S2 MAIN BRANCH | 0.191718 |
AIRLOOP F7 SW MAIN BRANCH | 0.336398 |
AIRLOOP F7 NW MAIN BRANCH | 0.330018 |
AIRLOOP F7 SE MAIN BRANCH | 0.274776 |
AIRLOOP F7 NE MAIN BRANCH | 0.252366 |
AIRLOOP F7 N1 MAIN BRANCH | 0.183802 |
AIRLOOP F7 N2 MAIN BRANCH | 0.182219 |
AIRLOOP F7 S1 MAIN BRANCH | 0.190098 |
AIRLOOP F7 S2 MAIN BRANCH | 0.190972 |
AIRLOOP F8 SW MAIN BRANCH | 0.337093 |
AIRLOOP F8 NW MAIN BRANCH | 0.330781 |
AIRLOOP F8 SE MAIN BRANCH | 0.275720 |
AIRLOOP F8 NE MAIN BRANCH | 0.252998 |
AIRLOOP F8 N1 MAIN BRANCH | 0.184753 |
AIRLOOP F8 N2 MAIN BRANCH | 0.183180 |
AIRLOOP F8 S1 MAIN BRANCH | 0.190874 |
AIRLOOP F8 S2 MAIN BRANCH | 0.191734 |
AIRLOOP F9 SW MAIN BRANCH | 0.349150 |
AIRLOOP F9 NW MAIN BRANCH | 0.342849 |
AIRLOOP F9 SE MAIN BRANCH | 0.284561 |
AIRLOOP F9 NE MAIN BRANCH | 0.257598 |
AIRLOOP F9 N1 MAIN BRANCH | 0.195323 |
AIRLOOP F9 N2 MAIN BRANCH | 0.193734 |
AIRLOOP F9 S1 MAIN BRANCH | 0.198443 |
AIRLOOP F9 S2 MAIN BRANCH | 0.199351 |
AIRLOOP T SW MAIN BRANCH | 0.430106 |
AIRLOOP T NW MAIN BRANCH | 0.418217 |
AIRLOOP T SE MAIN BRANCH | 0.366917 |
AIRLOOP T NE MAIN BRANCH | 0.324820 |
AIRLOOP T N1 MAIN BRANCH | 0.248549 |
AIRLOOP T N2 MAIN BRANCH | 0.248245 |
AIRLOOP T S1 MAIN BRANCH | 0.290618 |
AIRLOOP T S2 MAIN BRANCH | 0.291477 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.258910 |
AIRLOOP G NW | 0.255012 |
AIRLOOP OFFICE | 0.327712 |
AIRLOOP G NE | 0.185878 |
AIRLOOP G N1 | 0.132973 |
AIRLOOP G N2 | 0.130982 |
AIRLOOP G S1 | 0.136322 |
AIRLOOP G S2 | 0.142188 |
AIRLOOP F2 SW | 0.333584 |
AIRLOOP F2 NW | 0.326109 |
AIRLOOP F2 SE | 0.289528 |
AIRLOOP F2 NE | 0.247149 |
AIRLOOP F2 N1 | 0.177396 |
AIRLOOP F2 N2 | 0.175768 |
AIRLOOP F2 S1 | 0.183880 |
AIRLOOP F2 S2 | 0.186098 |
AIRLOOP F3 SW | 0.335365 |
AIRLOOP F3 NW | 0.328661 |
AIRLOOP F3 SE | 0.273960 |
AIRLOOP F3 NE | 0.251176 |
AIRLOOP F3 N1 | 0.181470 |
AIRLOOP F3 N2 | 0.179856 |
AIRLOOP F3 S1 | 0.188061 |
AIRLOOP F3 S2 | 0.189196 |
AIRLOOP F4 SW | 0.336964 |
AIRLOOP F4 NW | 0.330385 |
AIRLOOP F4 SE | 0.274280 |
AIRLOOP F4 NE | 0.252823 |
AIRLOOP F4 N1 | 0.183508 |
AIRLOOP F4 N2 | 0.181900 |
AIRLOOP F4 S1 | 0.190023 |
AIRLOOP F4 S2 | 0.190976 |
AIRLOOP M SW | 0.341016 |
AIRLOOP M NW | 0.334616 |
AIRLOOP M SE | 0.278516 |
AIRLOOP M NE | 0.256935 |
AIRLOOP M N1 | 0.187784 |
AIRLOOP M N2 | 0.186181 |
AIRLOOP M S1 | 0.194174 |
AIRLOOP M S2 | 0.195086 |
AIRLOOP F6 SW | 0.337333 |
AIRLOOP F6 NW | 0.330882 |
AIRLOOP F6 SE | 0.275301 |
AIRLOOP F6 NE | 0.253245 |
AIRLOOP F6 N1 | 0.184445 |
AIRLOOP F6 N2 | 0.182854 |
AIRLOOP F6 S1 | 0.190827 |
AIRLOOP F6 S2 | 0.191718 |
AIRLOOP F7 SW | 0.336398 |
AIRLOOP F7 NW | 0.330018 |
AIRLOOP F7 SE | 0.274776 |
AIRLOOP F7 NE | 0.252366 |
AIRLOOP F7 N1 | 0.183802 |
AIRLOOP F7 N2 | 0.182219 |
AIRLOOP F7 S1 | 0.190098 |
AIRLOOP F7 S2 | 0.190972 |
AIRLOOP F8 SW | 0.337093 |
AIRLOOP F8 NW | 0.330781 |
AIRLOOP F8 SE | 0.275720 |
AIRLOOP F8 NE | 0.252998 |
AIRLOOP F8 N1 | 0.184753 |
AIRLOOP F8 N2 | 0.183180 |
AIRLOOP F8 S1 | 0.190874 |
AIRLOOP F8 S2 | 0.191734 |
AIRLOOP F9 SW | 0.349150 |
AIRLOOP F9 NW | 0.342849 |
AIRLOOP F9 SE | 0.284561 |
AIRLOOP F9 NE | 0.257598 |
AIRLOOP F9 N1 | 0.195323 |
AIRLOOP F9 N2 | 0.193734 |
AIRLOOP F9 S1 | 0.198443 |
AIRLOOP F9 S2 | 0.199351 |
AIRLOOP T SW | 0.430106 |
AIRLOOP T NW | 0.418217 |
AIRLOOP T SE | 0.366917 |
AIRLOOP T NE | 0.324820 |
AIRLOOP T N1 | 0.248549 |
AIRLOOP T N2 | 0.248245 |
AIRLOOP T S1 | 0.290618 |
AIRLOOP T S2 | 0.291477 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.258910 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.255012 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.327712 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.185878 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.132973 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.130982 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.136322 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.142188 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.333584 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.326109 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.289528 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.247149 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.177396 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.175768 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.183880 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.186098 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.335365 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.328661 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.273960 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.251176 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.181470 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.179856 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.188061 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.189196 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.336964 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.330385 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.274280 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.252823 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.183508 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.181900 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.190023 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.190976 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.341016 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.334616 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.278516 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.256935 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.187784 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.186181 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.194174 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.195086 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.337333 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.330882 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.275301 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.253245 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.184445 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.182854 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.190827 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.191718 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.336398 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.330018 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.274776 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.252366 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.183802 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.182219 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.190098 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.190972 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.337093 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.330781 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.275720 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.252998 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.184753 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.183180 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.190874 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.191734 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.349150 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.342849 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.284561 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.257598 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.195323 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.193734 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.198443 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.199351 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.430106 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.418217 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.366917 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.324820 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.248549 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.248245 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.290618 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.291477 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.258910 | 3205.74 | 2069.43 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.255012 | 3148.90 | 2033.46 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.327712 | 4016.33 | 2614.97 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.185878 | 2247.30 | 1476.51 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.132973 | 1649.01 | 1075.73 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.130982 | 1624.43 | 1060.20 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.136322 | 1773.44 | 1138.37 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.142188 | 1845.11 | 1184.20 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.333584 | 4097.56 | 2645.61 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.326109 | 3998.19 | 2581.99 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.289528 | 3602.22 | 2322.51 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.247149 | 2973.18 | 1948.25 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.177396 | 2184.74 | 1419.81 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.175768 | 2164.71 | 1407.14 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.183880 | 2347.31 | 1509.03 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.186098 | 2369.96 | 1524.60 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.335365 | 4106.84 | 2657.32 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.328661 | 4016.93 | 2599.68 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.273960 | 3400.35 | 2199.59 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.251176 | 3010.14 | 1977.45 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.181470 | 2227.65 | 1450.30 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.179856 | 2207.81 | 1437.74 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.188061 | 2391.41 | 1540.41 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.189196 | 2400.81 | 1547.54 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.336964 | 4117.02 | 2668.14 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.330385 | 4028.65 | 2611.48 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.274280 | 3395.33 | 2200.57 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.252823 | 3034.38 | 1994.12 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.183508 | 2247.30 | 1465.24 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.181900 | 2227.55 | 1452.73 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.190023 | 2410.14 | 1554.80 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.190976 | 2417.30 | 1560.51 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.341016 | 4158.84 | 2698.28 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.334616 | 4072.71 | 2643.02 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.278516 | 3439.66 | 2232.22 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.256935 | 3077.10 | 2024.77 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.187784 | 2295.42 | 1497.75 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.186181 | 2275.75 | 1485.29 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.194174 | 2456.49 | 1586.38 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.195086 | 2463.12 | 1591.76 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.337333 | 4107.38 | 2668.62 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.330882 | 4020.59 | 2612.95 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.275301 | 3398.79 | 2207.99 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.253245 | 3025.97 | 1995.13 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.184445 | 2250.64 | 1471.15 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.182854 | 2231.12 | 1458.78 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.190827 | 2412.06 | 1559.73 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.191718 | 2418.41 | 1564.94 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.336398 | 4090.25 | 2660.39 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.330018 | 4004.31 | 2605.28 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.274776 | 3386.97 | 2203.00 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.252366 | 3009.82 | 1987.41 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.183802 | 2239.43 | 1465.59 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.182219 | 2220.02 | 1453.29 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.190098 | 2399.99 | 1553.51 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.190972 | 2406.11 | 1558.60 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.337093 | 4093.59 | 2664.92 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.330781 | 4008.49 | 2610.33 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.275720 | 3393.58 | 2209.50 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.252998 | 3012.60 | 1991.48 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.184753 | 2248.14 | 1472.49 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.183180 | 2228.86 | 1460.27 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.190874 | 2406.58 | 1559.07 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.191734 | 2412.52 | 1564.04 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.349150 | 4235.91 | 2757.64 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.342849 | 4151.08 | 2703.15 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.284561 | 3496.63 | 2277.35 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.257598 | 3063.96 | 2026.37 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.195323 | 2375.11 | 1554.21 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.193734 | 2355.64 | 1541.86 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.198443 | 2496.23 | 1617.52 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.199351 | 2507.13 | 1624.55 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.430106 | 5241.32 | 3395.82 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.418217 | 5079.47 | 3295.62 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.366917 | 4495.28 | 2915.56 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.324820 | 3904.45 | 2557.56 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.248549 | 3104.20 | 2006.55 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.248245 | 3100.56 | 2004.20 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.290618 | 3617.14 | 2333.28 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.291477 | 3623.11 | 2338.17 | 0.000079 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.258910 | 0.258910 | 0.258910 | 0.258910 | 3205.74 | 3205.74 | 2438.18 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.255012 | 0.255012 | 0.255012 | 0.255012 | 3148.90 | 3148.90 | 2437.28 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.327712 | 0.327712 | 0.327712 | 0.327712 | 4016.33 | 4016.33 | 3204.67 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.185878 | 0.185878 | 0.185878 | 0.185878 | 2247.30 | 2247.30 | 2437.28 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.132973 | 0.132973 | 0.132973 | 0.132973 | 1649.01 | 1649.01 | 1803.85 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.130982 | 0.130982 | 0.130982 | 0.130982 | 1624.43 | 1624.43 | 1803.85 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.136322 | 0.136322 | 0.136322 | 0.136322 | 1773.44 | 1773.44 | 1801.10 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.142188 | 0.142188 | 0.142188 | 0.142188 | 1845.11 | 1845.11 | 1809.61 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.333584 | 0.333584 | 0.333584 | 0.333584 | 4097.56 | 4097.56 | 2417.40 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.326109 | 0.326109 | 0.326109 | 0.326109 | 3998.19 | 3998.19 | 2415.07 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.289528 | 0.289528 | 0.289528 | 0.289528 | 3602.22 | 3602.22 | 2442.87 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.247149 | 0.247149 | 0.247149 | 0.247149 | 2973.18 | 2973.18 | 2415.07 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.177396 | 0.177396 | 0.177396 | 0.177396 | 2184.74 | 2184.74 | 1636.45 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.175768 | 0.175768 | 0.175768 | 0.175768 | 2164.71 | 2164.71 | 1636.45 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.183880 | 0.183880 | 0.183880 | 0.183880 | 2347.31 | 2347.31 | 1641.48 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.186098 | 0.186098 | 0.186098 | 0.186098 | 2369.96 | 2369.96 | 1643.18 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.335365 | 0.335365 | 0.335365 | 0.335365 | 4106.84 | 4106.84 | 2408.10 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.328661 | 0.328661 | 0.328661 | 0.328661 | 4016.93 | 4016.93 | 2408.73 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.273960 | 0.273960 | 0.273960 | 0.273960 | 3400.35 | 3400.35 | 2410.95 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.251176 | 0.251176 | 0.251176 | 0.251176 | 3010.14 | 3010.14 | 2408.73 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.181470 | 0.181470 | 0.181470 | 0.181470 | 2227.65 | 2227.65 | 1603.57 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.179856 | 0.179856 | 0.179856 | 0.179856 | 2207.81 | 2207.81 | 1603.57 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.188061 | 0.188061 | 0.188061 | 0.188061 | 2391.41 | 2391.41 | 1603.68 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.189196 | 0.189196 | 0.189196 | 0.189196 | 2400.81 | 2400.81 | 1603.96 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.336964 | 0.336964 | 0.336964 | 0.336964 | 4117.02 | 4117.02 | 2437.51 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.330385 | 0.330385 | 0.330385 | 0.330385 | 4028.65 | 4028.65 | 2440.24 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.274280 | 0.274280 | 0.274280 | 0.274280 | 3395.33 | 3395.33 | 2437.81 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.252823 | 0.252823 | 0.252823 | 0.252823 | 3034.38 | 3034.38 | 2440.24 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.183508 | 0.183508 | 0.183508 | 0.183508 | 2247.30 | 2247.30 | 1613.44 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.181900 | 0.181900 | 0.181900 | 0.181900 | 2227.55 | 2227.55 | 1613.44 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.190023 | 0.190023 | 0.190023 | 0.190023 | 2410.14 | 2410.14 | 1611.18 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.190976 | 0.190976 | 0.190976 | 0.190976 | 2417.30 | 2417.30 | 1611.22 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.341016 | 0.341016 | 0.341016 | 0.341016 | 4158.84 | 4158.84 | 2444.07 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.334616 | 0.334616 | 0.334616 | 0.334616 | 4072.71 | 4072.71 | 2447.13 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.278516 | 0.278516 | 0.278516 | 0.278516 | 3439.66 | 3439.66 | 2444.10 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.256935 | 0.256935 | 0.256935 | 0.256935 | 3077.10 | 3077.10 | 2447.13 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.187784 | 0.187784 | 0.187784 | 0.187784 | 2295.42 | 2295.42 | 1605.70 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.186181 | 0.186181 | 0.186181 | 0.186181 | 2275.75 | 2275.75 | 1605.70 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.194174 | 0.194174 | 0.194174 | 0.194174 | 2456.49 | 2456.49 | 1603.05 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.195086 | 0.195086 | 0.195086 | 0.195086 | 2463.12 | 2463.12 | 1603.05 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.337333 | 0.337333 | 0.337333 | 0.337333 | 4107.38 | 4107.38 | 2518.98 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.330882 | 0.330882 | 0.330882 | 0.330882 | 4020.59 | 4020.59 | 2524.13 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.275301 | 0.275301 | 0.275301 | 0.275301 | 3398.79 | 3398.79 | 2518.98 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.253245 | 0.253245 | 0.253245 | 0.253245 | 3025.97 | 3025.97 | 2524.13 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.184445 | 0.184445 | 0.184445 | 0.184445 | 2250.64 | 2250.64 | 1664.53 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.182854 | 0.182854 | 0.182854 | 0.182854 | 2231.12 | 2231.12 | 1664.53 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.190827 | 0.190827 | 0.190827 | 0.190827 | 2412.06 | 2412.06 | 1659.73 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.191718 | 0.191718 | 0.191718 | 0.191718 | 2418.41 | 2418.41 | 1659.73 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.336398 | 0.336398 | 0.336398 | 0.336398 | 4090.25 | 4090.25 | 2566.03 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.330018 | 0.330018 | 0.330018 | 0.330018 | 4004.31 | 4004.31 | 2571.88 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.274776 | 0.274776 | 0.274776 | 0.274776 | 3386.97 | 3386.97 | 2566.03 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.252366 | 0.252366 | 0.252366 | 0.252366 | 3009.82 | 3009.82 | 2571.88 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.183802 | 0.183802 | 0.183802 | 0.183802 | 2239.43 | 2239.43 | 1699.07 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.182219 | 0.182219 | 0.182219 | 0.182219 | 2220.02 | 2220.02 | 1699.07 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.190098 | 0.190098 | 0.190098 | 0.190098 | 2399.99 | 2399.99 | 1693.52 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.190972 | 0.190972 | 0.190972 | 0.190972 | 2406.11 | 2406.11 | 1693.52 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.337093 | 0.337093 | 0.337093 | 0.337093 | 4093.59 | 4093.59 | 2617.09 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.330781 | 0.330781 | 0.330781 | 0.330781 | 4008.49 | 4008.49 | 2623.31 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.275720 | 0.275720 | 0.275720 | 0.275720 | 3393.58 | 3393.58 | 2617.09 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.252998 | 0.252998 | 0.252998 | 0.252998 | 3012.60 | 3012.60 | 2623.31 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.184753 | 0.184753 | 0.184753 | 0.184753 | 2248.14 | 2248.14 | 1739.23 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.183180 | 0.183180 | 0.183180 | 0.183180 | 2228.86 | 2228.86 | 1739.23 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.190874 | 0.190874 | 0.190874 | 0.190874 | 2406.58 | 2406.58 | 1733.27 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.191734 | 0.191734 | 0.191734 | 0.191734 | 2412.52 | 2412.52 | 1733.27 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.349150 | 0.349150 | 0.349150 | 0.349150 | 4235.91 | 4235.91 | 2787.45 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.342849 | 0.342849 | 0.342849 | 0.342849 | 4151.08 | 4151.08 | 2791.65 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.284561 | 0.284561 | 0.284561 | 0.284561 | 3496.63 | 3496.63 | 2787.45 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.257598 | 0.257598 | 0.257598 | 0.257598 | 3063.96 | 3063.96 | 2791.65 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.195323 | 0.195323 | 0.195323 | 0.195323 | 2375.11 | 2375.11 | 1889.52 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.193734 | 0.193734 | 0.193734 | 0.193734 | 2355.64 | 2355.64 | 1889.52 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.198443 | 0.198443 | 0.198443 | 0.198443 | 2496.23 | 2496.23 | 1885.05 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.199351 | 0.199351 | 0.199351 | 0.199351 | 2507.13 | 2507.13 | 1885.05 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.430106 | 0.430106 | 0.430106 | 0.430106 | 5241.32 | 5241.32 | 3391.52 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.418217 | 0.418217 | 0.418217 | 0.418217 | 5079.47 | 5079.47 | 3402.45 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.366917 | 0.366917 | 0.366917 | 0.366917 | 4495.28 | 4495.28 | 3391.52 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.324820 | 0.324820 | 0.324820 | 0.324820 | 3904.45 | 3904.45 | 3402.45 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.248549 | 0.248549 | 0.248549 | 0.248549 | 3104.20 | 3104.20 | 2545.49 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.248245 | 0.248245 | 0.248245 | 0.248245 | 3100.56 | 3100.56 | 2545.49 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.290618 | 0.290618 | 0.290618 | 0.290618 | 3617.14 | 3617.14 | 2531.48 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.291477 | 0.291477 | 0.291477 | 0.291477 | 3623.11 | 3623.11 | 2531.48 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.258910 |
AIRLOOP G NW SUPPLY FAN | 0.255012 |
AIRLOOP OFFICE SUPPLY FAN | 0.327712 |
AIRLOOP G NE SUPPLY FAN | 0.185878 |
AIRLOOP G N1 SUPPLY FAN | 0.132973 |
AIRLOOP G N2 SUPPLY FAN | 0.130982 |
AIRLOOP G S1 SUPPLY FAN | 0.136322 |
AIRLOOP G S2 SUPPLY FAN | 0.142188 |
AIRLOOP F2 SW SUPPLY FAN | 0.333584 |
AIRLOOP F2 NW SUPPLY FAN | 0.326109 |
AIRLOOP F2 SE SUPPLY FAN | 0.289528 |
AIRLOOP F2 NE SUPPLY FAN | 0.247149 |
AIRLOOP F2 N1 SUPPLY FAN | 0.177396 |
AIRLOOP F2 N2 SUPPLY FAN | 0.175768 |
AIRLOOP F2 S1 SUPPLY FAN | 0.183880 |
AIRLOOP F2 S2 SUPPLY FAN | 0.186098 |
AIRLOOP F3 SW SUPPLY FAN | 0.335365 |
AIRLOOP F3 NW SUPPLY FAN | 0.328661 |
AIRLOOP F3 SE SUPPLY FAN | 0.273960 |
AIRLOOP F3 NE SUPPLY FAN | 0.251176 |
AIRLOOP F3 N1 SUPPLY FAN | 0.181470 |
AIRLOOP F3 N2 SUPPLY FAN | 0.179856 |
AIRLOOP F3 S1 SUPPLY FAN | 0.188061 |
AIRLOOP F3 S2 SUPPLY FAN | 0.189196 |
AIRLOOP F4 SW SUPPLY FAN | 0.336964 |
AIRLOOP F4 NW SUPPLY FAN | 0.330385 |
AIRLOOP F4 SE SUPPLY FAN | 0.274280 |
AIRLOOP F4 NE SUPPLY FAN | 0.252823 |
AIRLOOP F4 N1 SUPPLY FAN | 0.183508 |
AIRLOOP F4 N2 SUPPLY FAN | 0.181900 |
AIRLOOP F4 S1 SUPPLY FAN | 0.190023 |
AIRLOOP F4 S2 SUPPLY FAN | 0.190976 |
AIRLOOP M SW SUPPLY FAN | 0.341016 |
AIRLOOP M NW SUPPLY FAN | 0.334616 |
AIRLOOP M SE SUPPLY FAN | 0.278516 |
AIRLOOP M NE SUPPLY FAN | 0.256935 |
AIRLOOP M N1 SUPPLY FAN | 0.187784 |
AIRLOOP M N2 SUPPLY FAN | 0.186181 |
AIRLOOP M S1 SUPPLY FAN | 0.194174 |
AIRLOOP M S2 SUPPLY FAN | 0.195086 |
AIRLOOP F6 SW SUPPLY FAN | 0.337333 |
AIRLOOP F6 NW SUPPLY FAN | 0.330882 |
AIRLOOP F6 SE SUPPLY FAN | 0.275301 |
AIRLOOP F6 NE SUPPLY FAN | 0.253245 |
AIRLOOP F6 N1 SUPPLY FAN | 0.184445 |
AIRLOOP F6 N2 SUPPLY FAN | 0.182854 |
AIRLOOP F6 S1 SUPPLY FAN | 0.190827 |
AIRLOOP F6 S2 SUPPLY FAN | 0.191718 |
AIRLOOP F7 SW SUPPLY FAN | 0.336398 |
AIRLOOP F7 NW SUPPLY FAN | 0.330018 |
AIRLOOP F7 SE SUPPLY FAN | 0.274776 |
AIRLOOP F7 NE SUPPLY FAN | 0.252366 |
AIRLOOP F7 N1 SUPPLY FAN | 0.183802 |
AIRLOOP F7 N2 SUPPLY FAN | 0.182219 |
AIRLOOP F7 S1 SUPPLY FAN | 0.190098 |
AIRLOOP F7 S2 SUPPLY FAN | 0.190972 |
AIRLOOP F8 SW SUPPLY FAN | 0.337093 |
AIRLOOP F8 NW SUPPLY FAN | 0.330781 |
AIRLOOP F8 SE SUPPLY FAN | 0.275720 |
AIRLOOP F8 NE SUPPLY FAN | 0.252998 |
AIRLOOP F8 N1 SUPPLY FAN | 0.184753 |
AIRLOOP F8 N2 SUPPLY FAN | 0.183180 |
AIRLOOP F8 S1 SUPPLY FAN | 0.190874 |
AIRLOOP F8 S2 SUPPLY FAN | 0.191734 |
AIRLOOP F9 SW SUPPLY FAN | 0.349150 |
AIRLOOP F9 NW SUPPLY FAN | 0.342849 |
AIRLOOP F9 SE SUPPLY FAN | 0.284561 |
AIRLOOP F9 NE SUPPLY FAN | 0.257598 |
AIRLOOP F9 N1 SUPPLY FAN | 0.195323 |
AIRLOOP F9 N2 SUPPLY FAN | 0.193734 |
AIRLOOP F9 S1 SUPPLY FAN | 0.198443 |
AIRLOOP F9 S2 SUPPLY FAN | 0.199351 |
AIRLOOP T SW SUPPLY FAN | 0.430106 |
AIRLOOP T NW SUPPLY FAN | 0.418217 |
AIRLOOP T SE SUPPLY FAN | 0.366917 |
AIRLOOP T NE SUPPLY FAN | 0.324820 |
AIRLOOP T N1 SUPPLY FAN | 0.248549 |
AIRLOOP T N2 SUPPLY FAN | 0.248245 |
AIRLOOP T S1 SUPPLY FAN | 0.290618 |
AIRLOOP T S2 SUPPLY FAN | 0.291477 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.258910 | 3205.74 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.255012 | 3148.90 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.327712 | 4016.33 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.185878 | 2247.30 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.132973 | 1649.01 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.130982 | 1624.43 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.136322 | 1773.44 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.142188 | 1845.11 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.333584 | 4097.56 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.326109 | 3998.19 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.289528 | 3602.22 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.247149 | 2973.18 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.177396 | 2184.74 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.175768 | 2164.71 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.183880 | 2347.31 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.186098 | 2369.96 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.335365 | 4106.84 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.328661 | 4016.93 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.273960 | 3400.35 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.251176 | 3010.14 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.181470 | 2227.65 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.179856 | 2207.81 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.188061 | 2391.41 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.189196 | 2400.81 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.336964 | 4117.02 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.330385 | 4028.65 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.274280 | 3395.33 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.252823 | 3034.38 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.183508 | 2247.30 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.181900 | 2227.55 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.190023 | 2410.14 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.190976 | 2417.30 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.341016 | 4158.84 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.334616 | 4072.71 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.278516 | 3439.66 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.256935 | 3077.10 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.187784 | 2295.42 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.186181 | 2275.75 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.194174 | 2456.49 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.195086 | 2463.12 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.337333 | 4107.38 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.330882 | 4020.59 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.275301 | 3398.79 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.253245 | 3025.97 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.184445 | 2250.64 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.182854 | 2231.12 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.190827 | 2412.06 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.191718 | 2418.41 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.336398 | 4090.25 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.330018 | 4004.31 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.274776 | 3386.97 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.252366 | 3009.82 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.183802 | 2239.43 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.182219 | 2220.02 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.190098 | 2399.99 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.190972 | 2406.11 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.337093 | 4093.59 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.330781 | 4008.49 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.275720 | 3393.58 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.252998 | 3012.60 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.184753 | 2248.14 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.183180 | 2228.86 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.190874 | 2406.58 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.191734 | 2412.52 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.349150 | 4235.91 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.342849 | 4151.08 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.284561 | 3496.63 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.257598 | 3063.96 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.195323 | 2375.11 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.193734 | 2355.64 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.198443 | 2496.23 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.199351 | 2507.13 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.430106 | 5241.32 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.418217 | 5079.47 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.366917 | 4495.28 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.324820 | 3904.45 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.248549 | 3104.20 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.248245 | 3100.56 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.290618 | 3617.14 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.291477 | 3623.11 | 0.000079 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2438.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2437.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3204.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2437.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1803.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1803.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1801.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1809.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2417.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2415.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2442.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2415.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1636.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1636.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1641.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1643.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2408.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2408.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2410.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2408.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1603.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1603.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1603.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1603.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2437.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2440.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2437.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2440.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1613.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1613.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1611.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1611.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2444.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2447.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2444.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2447.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1605.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1605.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1603.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1603.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2518.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2524.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2518.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2524.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1664.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1664.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1659.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1659.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2566.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2571.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2566.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2571.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1699.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1699.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1693.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1693.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2617.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2623.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2617.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2623.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1739.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1739.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1733.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1733.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2787.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2791.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2787.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2791.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1889.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1889.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1885.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1885.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3391.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3402.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3391.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3402.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2545.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2545.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2531.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2531.48 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005317 | 5.98 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005317 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005317 | 2566.74 | 8.21 | 6542.85 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005317 | 1356.10 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 2.60 |
February | 22.78 | 4.29 |
March | 22.98 | 8.77 |
April | 23.64 | 13.91 |
May | 23.86 | 17.82 |
June | 24.30 | 23.21 |
July | 24.40 | 25.63 |
August | 24.37 | 24.08 |
September | 24.33 | 20.49 |
October | 23.84 | 13.71 |
November | 23.19 | 6.96 |
December | 22.67 | 2.07 |
Annual Sum or Average | 23.58 | 13.68 |
Minimum of Months | 22.61 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 2.60 |
February | 22.00 | 4.29 |
March | 22.33 | 8.77 |
April | 23.34 | 13.91 |
May | 23.83 | 17.82 |
June | 24.32 | 23.21 |
July | 24.40 | 25.63 |
August | 24.36 | 24.08 |
September | 24.30 | 20.49 |
October | 23.31 | 13.71 |
November | 22.21 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.17 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.56 | 2.60 |
February | 22.73 | 4.29 |
March | 23.04 | 8.77 |
April | 23.68 | 13.91 |
May | 24.03 | 17.82 |
June | 24.36 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.41 | 20.49 |
October | 23.80 | 13.71 |
November | 23.03 | 6.96 |
December | 22.61 | 2.07 |
Annual Sum or Average | 23.59 | 13.68 |
Minimum of Months | 22.56 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 2.60 |
February | 21.88 | 4.29 |
March | 22.25 | 8.77 |
April | 23.35 | 13.91 |
May | 23.83 | 17.82 |
June | 24.32 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.24 | 13.71 |
November | 22.05 | 6.96 |
December | 21.71 | 2.07 |
Annual Sum or Average | 23.13 | 13.68 |
Minimum of Months | 21.71 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 2.60 |
February | 21.82 | 4.29 |
March | 22.05 | 8.77 |
April | 22.99 | 13.91 |
May | 23.62 | 17.82 |
June | 24.29 | 23.21 |
July | 24.41 | 25.63 |
August | 24.35 | 24.08 |
September | 24.26 | 20.49 |
October | 23.06 | 13.71 |
November | 21.99 | 6.96 |
December | 21.71 | 2.07 |
Annual Sum or Average | 23.03 | 13.68 |
Minimum of Months | 21.71 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 2.60 |
February | 21.81 | 4.29 |
March | 22.05 | 8.77 |
April | 23.00 | 13.91 |
May | 23.62 | 17.82 |
June | 24.29 | 23.21 |
July | 24.41 | 25.63 |
August | 24.35 | 24.08 |
September | 24.26 | 20.49 |
October | 23.05 | 13.71 |
November | 21.98 | 6.96 |
December | 21.71 | 2.07 |
Annual Sum or Average | 23.03 | 13.68 |
Minimum of Months | 21.71 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 2.60 |
February | 22.82 | 4.29 |
March | 22.95 | 8.77 |
April | 23.48 | 13.91 |
May | 23.72 | 17.82 |
June | 24.27 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.40 | 20.49 |
October | 23.86 | 13.71 |
November | 23.29 | 6.96 |
December | 22.77 | 2.07 |
Annual Sum or Average | 23.59 | 13.68 |
Minimum of Months | 22.67 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 2.60 |
February | 22.84 | 4.29 |
March | 22.99 | 8.77 |
April | 23.52 | 13.91 |
May | 23.75 | 17.82 |
June | 24.28 | 23.21 |
July | 24.39 | 25.63 |
August | 24.39 | 24.08 |
September | 24.40 | 20.49 |
October | 23.87 | 13.71 |
November | 23.30 | 6.96 |
December | 22.79 | 2.07 |
Annual Sum or Average | 23.60 | 13.68 |
Minimum of Months | 22.69 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.74 | 2.60 |
February | 19.29 | 4.29 |
March | 20.56 | 8.77 |
April | 22.20 | 13.91 |
May | 23.33 | 17.82 |
June | 25.64 | 23.21 |
July | 26.32 | 25.63 |
August | 25.94 | 24.08 |
September | 25.00 | 20.49 |
October | 22.36 | 13.71 |
November | 20.13 | 6.96 |
December | 18.62 | 2.07 |
Annual Sum or Average | 22.36 | 13.68 |
Minimum of Months | 18.62 | 2.07 |
Maximum of Months | 26.32 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 2.60 |
February | 23.42 | 4.29 |
March | 23.82 | 8.77 |
April | 24.24 | 13.91 |
May | 24.27 | 17.82 |
June | 24.37 | 23.21 |
July | 24.40 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.22 | 13.71 |
November | 23.89 | 6.96 |
December | 23.29 | 2.07 |
Annual Sum or Average | 24.00 | 13.68 |
Minimum of Months | 23.23 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 2.60 |
February | 22.30 | 4.29 |
March | 23.03 | 8.77 |
April | 24.07 | 13.91 |
May | 24.24 | 17.82 |
June | 24.38 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.87 | 13.71 |
November | 22.79 | 6.96 |
December | 21.92 | 2.07 |
Annual Sum or Average | 23.48 | 13.68 |
Minimum of Months | 21.92 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 2.60 |
February | 23.41 | 4.29 |
March | 23.84 | 8.77 |
April | 24.25 | 13.91 |
May | 24.31 | 17.82 |
June | 24.38 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.40 | 20.49 |
October | 24.22 | 13.71 |
November | 23.87 | 6.96 |
December | 23.29 | 2.07 |
Annual Sum or Average | 24.00 | 13.68 |
Minimum of Months | 23.21 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 2.60 |
February | 22.15 | 4.29 |
March | 22.93 | 8.77 |
April | 24.06 | 13.91 |
May | 24.26 | 17.82 |
June | 24.39 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.36 | 20.49 |
October | 23.79 | 13.71 |
November | 22.58 | 6.96 |
December | 21.79 | 2.07 |
Annual Sum or Average | 23.42 | 13.68 |
Minimum of Months | 21.79 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 2.60 |
February | 22.10 | 4.29 |
March | 22.77 | 8.77 |
April | 23.90 | 13.91 |
May | 24.18 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.73 | 13.71 |
November | 22.60 | 6.96 |
December | 21.81 | 2.07 |
Annual Sum or Average | 23.38 | 13.68 |
Minimum of Months | 21.81 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.09 | 4.29 |
March | 22.76 | 8.77 |
April | 23.90 | 13.91 |
May | 24.18 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.72 | 13.71 |
November | 22.58 | 6.96 |
December | 21.80 | 2.07 |
Annual Sum or Average | 23.37 | 13.68 |
Minimum of Months | 21.80 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.47 | 2.60 |
February | 23.62 | 4.29 |
March | 23.91 | 8.77 |
April | 24.21 | 13.91 |
May | 24.22 | 17.82 |
June | 24.35 | 23.21 |
July | 24.40 | 25.63 |
August | 24.43 | 24.08 |
September | 24.46 | 20.49 |
October | 24.30 | 13.71 |
November | 24.04 | 6.96 |
December | 23.56 | 2.07 |
Annual Sum or Average | 24.08 | 13.68 |
Minimum of Months | 23.47 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.47 | 2.60 |
February | 23.62 | 4.29 |
March | 23.92 | 8.77 |
April | 24.22 | 13.91 |
May | 24.23 | 17.82 |
June | 24.35 | 23.21 |
July | 24.40 | 25.63 |
August | 24.42 | 24.08 |
September | 24.46 | 20.49 |
October | 24.30 | 13.71 |
November | 24.04 | 6.96 |
December | 23.57 | 2.07 |
Annual Sum or Average | 24.09 | 13.68 |
Minimum of Months | 23.47 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 2.60 |
February | 23.55 | 4.29 |
March | 24.31 | 8.77 |
April | 25.43 | 13.91 |
May | 25.79 | 17.82 |
June | 26.52 | 23.21 |
July | 26.76 | 25.63 |
August | 26.69 | 24.08 |
September | 26.40 | 20.49 |
October | 25.41 | 13.71 |
November | 24.21 | 6.96 |
December | 23.21 | 2.07 |
Annual Sum or Average | 25.13 | 13.68 |
Minimum of Months | 23.21 | 2.07 |
Maximum of Months | 26.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 2.60 |
February | 23.54 | 4.29 |
March | 23.95 | 8.77 |
April | 24.29 | 13.91 |
May | 24.29 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.26 | 13.71 |
November | 24.00 | 6.96 |
December | 23.43 | 2.07 |
Annual Sum or Average | 24.06 | 13.68 |
Minimum of Months | 23.37 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 2.60 |
February | 22.40 | 4.29 |
March | 23.23 | 8.77 |
April | 24.17 | 13.91 |
May | 24.27 | 17.82 |
June | 24.38 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.96 | 13.71 |
November | 22.99 | 6.96 |
December | 21.97 | 2.07 |
Annual Sum or Average | 23.55 | 13.68 |
Minimum of Months | 21.97 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 2.60 |
February | 23.47 | 4.29 |
March | 23.91 | 8.77 |
April | 24.27 | 13.91 |
May | 24.32 | 17.82 |
June | 24.38 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.41 | 20.49 |
October | 24.25 | 13.71 |
November | 23.93 | 6.96 |
December | 23.37 | 2.07 |
Annual Sum or Average | 24.04 | 13.68 |
Minimum of Months | 23.29 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 2.60 |
February | 22.24 | 4.29 |
March | 23.13 | 8.77 |
April | 24.15 | 13.91 |
May | 24.29 | 17.82 |
June | 24.40 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.36 | 20.49 |
October | 23.90 | 13.71 |
November | 22.78 | 6.96 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.49 | 13.68 |
Minimum of Months | 21.82 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 2.60 |
February | 22.24 | 4.29 |
March | 23.08 | 8.77 |
April | 24.08 | 13.91 |
May | 24.24 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.89 | 13.71 |
November | 22.90 | 6.96 |
December | 21.88 | 2.07 |
Annual Sum or Average | 23.49 | 13.68 |
Minimum of Months | 21.88 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 2.60 |
February | 22.23 | 4.29 |
March | 23.07 | 8.77 |
April | 24.08 | 13.91 |
May | 24.24 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.88 | 13.71 |
November | 22.87 | 6.96 |
December | 21.87 | 2.07 |
Annual Sum or Average | 23.48 | 13.68 |
Minimum of Months | 21.87 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.66 | 2.60 |
February | 23.81 | 4.29 |
March | 24.09 | 8.77 |
April | 24.29 | 13.91 |
May | 24.27 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.46 | 20.49 |
October | 24.36 | 13.71 |
November | 24.17 | 6.96 |
December | 23.77 | 2.07 |
Annual Sum or Average | 24.17 | 13.68 |
Minimum of Months | 23.66 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 2.60 |
February | 23.81 | 4.29 |
March | 24.09 | 8.77 |
April | 24.29 | 13.91 |
May | 24.27 | 17.82 |
June | 24.35 | 23.21 |
July | 24.40 | 25.63 |
August | 24.42 | 24.08 |
September | 24.46 | 20.49 |
October | 24.36 | 13.71 |
November | 24.17 | 6.96 |
December | 23.76 | 2.07 |
Annual Sum or Average | 24.17 | 13.68 |
Minimum of Months | 23.65 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 2.60 |
February | 24.07 | 4.29 |
March | 24.86 | 8.77 |
April | 25.90 | 13.91 |
May | 26.15 | 17.82 |
June | 26.66 | 23.21 |
July | 26.84 | 25.63 |
August | 26.79 | 24.08 |
September | 26.54 | 20.49 |
October | 25.83 | 13.71 |
November | 24.76 | 6.96 |
December | 23.73 | 2.07 |
Annual Sum or Average | 25.50 | 13.68 |
Minimum of Months | 23.73 | 2.07 |
Maximum of Months | 26.84 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 2.60 |
February | 23.55 | 4.29 |
March | 23.96 | 8.77 |
April | 24.29 | 13.91 |
May | 24.29 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.26 | 13.71 |
November | 24.00 | 6.96 |
December | 23.44 | 2.07 |
Annual Sum or Average | 24.06 | 13.68 |
Minimum of Months | 23.38 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 2.60 |
February | 22.42 | 4.29 |
March | 23.26 | 8.77 |
April | 24.18 | 13.91 |
May | 24.27 | 17.82 |
June | 24.38 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.36 | 20.49 |
October | 23.98 | 13.71 |
November | 23.05 | 6.96 |
December | 21.98 | 2.07 |
Annual Sum or Average | 23.57 | 13.68 |
Minimum of Months | 21.98 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 2.60 |
February | 23.46 | 4.29 |
March | 23.91 | 8.77 |
April | 24.28 | 13.91 |
May | 24.31 | 17.82 |
June | 24.38 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.41 | 20.49 |
October | 24.25 | 13.71 |
November | 23.94 | 6.96 |
December | 23.37 | 2.07 |
Annual Sum or Average | 24.04 | 13.68 |
Minimum of Months | 23.29 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 2.60 |
February | 22.26 | 4.29 |
March | 23.17 | 8.77 |
April | 24.16 | 13.91 |
May | 24.29 | 17.82 |
June | 24.41 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.36 | 20.49 |
October | 23.92 | 13.71 |
November | 22.85 | 6.96 |
December | 21.83 | 2.07 |
Annual Sum or Average | 23.51 | 13.68 |
Minimum of Months | 21.83 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 2.60 |
February | 22.30 | 4.29 |
March | 23.18 | 8.77 |
April | 24.12 | 13.91 |
May | 24.25 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.94 | 13.71 |
November | 23.03 | 6.96 |
December | 21.90 | 2.07 |
Annual Sum or Average | 23.52 | 13.68 |
Minimum of Months | 21.90 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 2.60 |
February | 22.28 | 4.29 |
March | 23.17 | 8.77 |
April | 24.12 | 13.91 |
May | 24.25 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.93 | 13.71 |
November | 23.00 | 6.96 |
December | 21.89 | 2.07 |
Annual Sum or Average | 23.52 | 13.68 |
Minimum of Months | 21.89 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 2.60 |
February | 23.84 | 4.29 |
March | 24.11 | 8.77 |
April | 24.30 | 13.91 |
May | 24.28 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.43 | 24.08 |
September | 24.46 | 20.49 |
October | 24.37 | 13.71 |
November | 24.20 | 6.96 |
December | 23.81 | 2.07 |
Annual Sum or Average | 24.19 | 13.68 |
Minimum of Months | 23.69 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 2.60 |
February | 23.83 | 4.29 |
March | 24.11 | 8.77 |
April | 24.30 | 13.91 |
May | 24.28 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.43 | 24.08 |
September | 24.46 | 20.49 |
October | 24.37 | 13.71 |
November | 24.20 | 6.96 |
December | 23.80 | 2.07 |
Annual Sum or Average | 24.19 | 13.68 |
Minimum of Months | 23.69 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 2.60 |
February | 24.25 | 4.29 |
March | 25.05 | 8.77 |
April | 26.07 | 13.91 |
May | 26.29 | 17.82 |
June | 26.76 | 23.21 |
July | 26.93 | 25.63 |
August | 26.88 | 24.08 |
September | 26.64 | 20.49 |
October | 25.99 | 13.71 |
November | 24.96 | 6.96 |
December | 23.91 | 2.07 |
Annual Sum or Average | 25.64 | 13.68 |
Minimum of Months | 23.91 | 2.07 |
Maximum of Months | 26.93 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 2.60 |
February | 23.54 | 4.29 |
March | 23.95 | 8.77 |
April | 24.29 | 13.91 |
May | 24.29 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.26 | 13.71 |
November | 24.00 | 6.96 |
December | 23.45 | 2.07 |
Annual Sum or Average | 24.06 | 13.68 |
Minimum of Months | 23.38 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 2.60 |
February | 22.43 | 4.29 |
March | 23.26 | 8.77 |
April | 24.18 | 13.91 |
May | 24.27 | 17.82 |
June | 24.38 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.99 | 13.71 |
November | 23.07 | 6.96 |
December | 22.00 | 2.07 |
Annual Sum or Average | 23.57 | 13.68 |
Minimum of Months | 22.00 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 2.60 |
February | 23.46 | 4.29 |
March | 23.89 | 8.77 |
April | 24.27 | 13.91 |
May | 24.31 | 17.82 |
June | 24.38 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.41 | 20.49 |
October | 24.25 | 13.71 |
November | 23.94 | 6.96 |
December | 23.38 | 2.07 |
Annual Sum or Average | 24.03 | 13.68 |
Minimum of Months | 23.30 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 2.60 |
February | 22.27 | 4.29 |
March | 23.17 | 8.77 |
April | 24.16 | 13.91 |
May | 24.29 | 17.82 |
June | 24.41 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.36 | 20.49 |
October | 23.93 | 13.71 |
November | 22.87 | 6.96 |
December | 21.84 | 2.07 |
Annual Sum or Average | 23.51 | 13.68 |
Minimum of Months | 21.84 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 2.60 |
February | 22.33 | 4.29 |
March | 23.21 | 8.77 |
April | 24.13 | 13.91 |
May | 24.25 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.96 | 13.71 |
November | 23.09 | 6.96 |
December | 21.93 | 2.07 |
Annual Sum or Average | 23.54 | 13.68 |
Minimum of Months | 21.93 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 2.60 |
February | 22.31 | 4.29 |
March | 23.20 | 8.77 |
April | 24.13 | 13.91 |
May | 24.25 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.96 | 13.71 |
November | 23.07 | 6.96 |
December | 21.92 | 2.07 |
Annual Sum or Average | 23.54 | 13.68 |
Minimum of Months | 21.92 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 2.60 |
February | 23.85 | 4.29 |
March | 24.12 | 8.77 |
April | 24.30 | 13.91 |
May | 24.28 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.46 | 20.49 |
October | 24.37 | 13.71 |
November | 24.21 | 6.96 |
December | 23.83 | 2.07 |
Annual Sum or Average | 24.19 | 13.68 |
Minimum of Months | 23.71 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.70 | 2.60 |
February | 23.84 | 4.29 |
March | 24.12 | 8.77 |
April | 24.30 | 13.91 |
May | 24.28 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.46 | 20.49 |
October | 24.37 | 13.71 |
November | 24.20 | 6.96 |
December | 23.82 | 2.07 |
Annual Sum or Average | 24.19 | 13.68 |
Minimum of Months | 23.70 | 2.07 |
Maximum of Months | 24.46 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.57 | 2.60 |
February | 24.88 | 4.29 |
March | 25.68 | 8.77 |
April | 26.68 | 13.91 |
May | 26.89 | 17.82 |
June | 27.35 | 23.21 |
July | 27.53 | 25.63 |
August | 27.48 | 24.08 |
September | 27.24 | 20.49 |
October | 26.61 | 13.71 |
November | 25.61 | 6.96 |
December | 24.55 | 2.07 |
Annual Sum or Average | 26.26 | 13.68 |
Minimum of Months | 24.55 | 2.07 |
Maximum of Months | 27.53 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 2.60 |
February | 23.46 | 4.29 |
March | 23.87 | 8.77 |
April | 24.26 | 13.91 |
May | 24.26 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.24 | 13.71 |
November | 23.95 | 6.96 |
December | 23.38 | 2.07 |
Annual Sum or Average | 24.02 | 13.68 |
Minimum of Months | 23.31 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 2.60 |
February | 22.35 | 4.29 |
March | 23.11 | 8.77 |
April | 24.12 | 13.91 |
May | 24.23 | 17.82 |
June | 24.38 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.35 | 20.49 |
October | 23.94 | 13.71 |
November | 22.95 | 6.96 |
December | 21.95 | 2.07 |
Annual Sum or Average | 23.52 | 13.68 |
Minimum of Months | 21.95 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 2.60 |
February | 23.38 | 4.29 |
March | 23.81 | 8.77 |
April | 24.24 | 13.91 |
May | 24.28 | 17.82 |
June | 24.37 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.40 | 20.49 |
October | 24.22 | 13.71 |
November | 23.88 | 6.96 |
December | 23.31 | 2.07 |
Annual Sum or Average | 24.00 | 13.68 |
Minimum of Months | 23.22 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 2.60 |
February | 22.21 | 4.29 |
March | 23.02 | 8.77 |
April | 24.11 | 13.91 |
May | 24.26 | 17.82 |
June | 24.40 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.87 | 13.71 |
November | 22.76 | 6.96 |
December | 21.81 | 2.07 |
Annual Sum or Average | 23.47 | 13.68 |
Minimum of Months | 21.81 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 2.60 |
February | 22.25 | 4.29 |
March | 23.05 | 8.77 |
April | 24.07 | 13.91 |
May | 24.22 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.32 | 20.49 |
October | 23.90 | 13.71 |
November | 22.96 | 6.96 |
December | 21.88 | 2.07 |
Annual Sum or Average | 23.49 | 13.68 |
Minimum of Months | 21.88 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 2.60 |
February | 22.23 | 4.29 |
March | 23.04 | 8.77 |
April | 24.07 | 13.91 |
May | 24.22 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.32 | 20.49 |
October | 23.90 | 13.71 |
November | 22.93 | 6.96 |
December | 21.87 | 2.07 |
Annual Sum or Average | 23.48 | 13.68 |
Minimum of Months | 21.87 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 2.60 |
February | 23.78 | 4.29 |
March | 24.05 | 8.77 |
April | 24.26 | 13.91 |
May | 24.25 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.45 | 20.49 |
October | 24.35 | 13.71 |
November | 24.16 | 6.96 |
December | 23.76 | 2.07 |
Annual Sum or Average | 24.16 | 13.68 |
Minimum of Months | 23.65 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.64 | 2.60 |
February | 23.77 | 4.29 |
March | 24.05 | 8.77 |
April | 24.27 | 13.91 |
May | 24.25 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.45 | 20.49 |
October | 24.35 | 13.71 |
November | 24.16 | 6.96 |
December | 23.76 | 2.07 |
Annual Sum or Average | 24.16 | 13.68 |
Minimum of Months | 23.64 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 2.60 |
February | 24.18 | 4.29 |
March | 24.95 | 8.77 |
April | 26.02 | 13.91 |
May | 26.25 | 17.82 |
June | 26.74 | 23.21 |
July | 26.92 | 25.63 |
August | 26.87 | 24.08 |
September | 26.62 | 20.49 |
October | 25.96 | 13.71 |
November | 24.91 | 6.96 |
December | 23.87 | 2.07 |
Annual Sum or Average | 25.60 | 13.68 |
Minimum of Months | 23.87 | 2.07 |
Maximum of Months | 26.92 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 2.60 |
February | 23.40 | 4.29 |
March | 23.80 | 8.77 |
April | 24.23 | 13.91 |
May | 24.24 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.22 | 13.71 |
November | 23.90 | 6.96 |
December | 23.32 | 2.07 |
Annual Sum or Average | 23.99 | 13.68 |
Minimum of Months | 23.25 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 2.60 |
February | 22.30 | 4.29 |
March | 22.99 | 8.77 |
April | 24.08 | 13.91 |
May | 24.21 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.90 | 13.71 |
November | 22.86 | 6.96 |
December | 21.92 | 2.07 |
Annual Sum or Average | 23.49 | 13.68 |
Minimum of Months | 21.92 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 2.60 |
February | 23.32 | 4.29 |
March | 23.73 | 8.77 |
April | 24.21 | 13.91 |
May | 24.27 | 17.82 |
June | 24.37 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.40 | 20.49 |
October | 24.20 | 13.71 |
November | 23.83 | 6.96 |
December | 23.26 | 2.07 |
Annual Sum or Average | 23.97 | 13.68 |
Minimum of Months | 23.17 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 2.60 |
February | 22.17 | 4.29 |
March | 22.90 | 8.77 |
April | 24.06 | 13.91 |
May | 24.23 | 17.82 |
June | 24.40 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.83 | 13.71 |
November | 22.67 | 6.96 |
December | 21.80 | 2.07 |
Annual Sum or Average | 23.43 | 13.68 |
Minimum of Months | 21.80 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 2.60 |
February | 22.19 | 4.29 |
March | 22.92 | 8.77 |
April | 24.01 | 13.91 |
May | 24.19 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.86 | 13.71 |
November | 22.85 | 6.96 |
December | 21.86 | 2.07 |
Annual Sum or Average | 23.45 | 13.68 |
Minimum of Months | 21.86 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 2.60 |
February | 22.18 | 4.29 |
March | 22.91 | 8.77 |
April | 24.01 | 13.91 |
May | 24.19 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.85 | 13.71 |
November | 22.82 | 6.96 |
December | 21.85 | 2.07 |
Annual Sum or Average | 23.44 | 13.68 |
Minimum of Months | 21.85 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.60 | 2.60 |
February | 23.72 | 4.29 |
March | 24.00 | 8.77 |
April | 24.24 | 13.91 |
May | 24.23 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.44 | 20.49 |
October | 24.34 | 13.71 |
November | 24.13 | 6.96 |
December | 23.71 | 2.07 |
Annual Sum or Average | 24.13 | 13.68 |
Minimum of Months | 23.60 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 2.60 |
February | 23.71 | 4.29 |
March | 23.99 | 8.77 |
April | 24.24 | 13.91 |
May | 24.23 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.42 | 24.08 |
September | 24.44 | 20.49 |
October | 24.34 | 13.71 |
November | 24.12 | 6.96 |
December | 23.71 | 2.07 |
Annual Sum or Average | 24.13 | 13.68 |
Minimum of Months | 23.59 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.72 | 2.60 |
February | 24.02 | 4.29 |
March | 24.75 | 8.77 |
April | 25.88 | 13.91 |
May | 26.13 | 17.82 |
June | 26.65 | 23.21 |
July | 26.84 | 25.63 |
August | 26.78 | 24.08 |
September | 26.52 | 20.49 |
October | 25.83 | 13.71 |
November | 24.73 | 6.96 |
December | 23.72 | 2.07 |
Annual Sum or Average | 25.47 | 13.68 |
Minimum of Months | 23.72 | 2.07 |
Maximum of Months | 26.84 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 2.60 |
February | 23.34 | 4.29 |
March | 23.72 | 8.77 |
April | 24.20 | 13.91 |
May | 24.22 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.36 | 20.49 |
October | 24.20 | 13.71 |
November | 23.85 | 6.96 |
December | 23.26 | 2.07 |
Annual Sum or Average | 23.96 | 13.68 |
Minimum of Months | 23.19 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 2.60 |
February | 22.26 | 4.29 |
March | 22.89 | 8.77 |
April | 24.03 | 13.91 |
May | 24.19 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.86 | 13.71 |
November | 22.78 | 6.96 |
December | 21.90 | 2.07 |
Annual Sum or Average | 23.45 | 13.68 |
Minimum of Months | 21.90 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 2.60 |
February | 23.26 | 4.29 |
March | 23.66 | 8.77 |
April | 24.19 | 13.91 |
May | 24.25 | 17.82 |
June | 24.36 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.39 | 20.49 |
October | 24.18 | 13.71 |
November | 23.79 | 6.96 |
December | 23.20 | 2.07 |
Annual Sum or Average | 23.94 | 13.68 |
Minimum of Months | 23.11 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.14 | 4.29 |
March | 22.81 | 8.77 |
April | 24.02 | 13.91 |
May | 24.21 | 17.82 |
June | 24.40 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.34 | 20.49 |
October | 23.79 | 13.71 |
November | 22.59 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.40 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 2.60 |
February | 22.15 | 4.29 |
March | 22.80 | 8.77 |
April | 23.96 | 13.91 |
May | 24.17 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.81 | 13.71 |
November | 22.74 | 6.96 |
December | 21.83 | 2.07 |
Annual Sum or Average | 23.41 | 13.68 |
Minimum of Months | 21.83 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 2.60 |
February | 22.14 | 4.29 |
March | 22.79 | 8.77 |
April | 23.96 | 13.91 |
May | 24.17 | 17.82 |
June | 24.36 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.81 | 13.71 |
November | 22.72 | 6.96 |
December | 21.83 | 2.07 |
Annual Sum or Average | 23.40 | 13.68 |
Minimum of Months | 21.83 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.54 | 2.60 |
February | 23.66 | 4.29 |
March | 23.93 | 8.77 |
April | 24.21 | 13.91 |
May | 24.21 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.43 | 20.49 |
October | 24.32 | 13.71 |
November | 24.08 | 6.96 |
December | 23.65 | 2.07 |
Annual Sum or Average | 24.10 | 13.68 |
Minimum of Months | 23.54 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 2.60 |
February | 23.65 | 4.29 |
March | 23.93 | 8.77 |
April | 24.21 | 13.91 |
May | 24.21 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.43 | 20.49 |
October | 24.32 | 13.71 |
November | 24.08 | 6.96 |
December | 23.64 | 2.07 |
Annual Sum or Average | 24.10 | 13.68 |
Minimum of Months | 23.53 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 2.60 |
February | 23.91 | 4.29 |
March | 24.62 | 8.77 |
April | 25.80 | 13.91 |
May | 26.09 | 17.82 |
June | 26.64 | 23.21 |
July | 26.85 | 25.63 |
August | 26.78 | 24.08 |
September | 26.50 | 20.49 |
October | 25.77 | 13.71 |
November | 24.61 | 6.96 |
December | 23.61 | 2.07 |
Annual Sum or Average | 25.41 | 13.68 |
Minimum of Months | 23.61 | 2.07 |
Maximum of Months | 26.85 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.07 | 2.60 |
February | 23.23 | 4.29 |
March | 23.60 | 8.77 |
April | 24.15 | 13.91 |
May | 24.19 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.36 | 20.49 |
October | 24.16 | 13.71 |
November | 23.75 | 6.96 |
December | 23.14 | 2.07 |
Annual Sum or Average | 23.90 | 13.68 |
Minimum of Months | 23.07 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 2.60 |
February | 22.23 | 4.29 |
March | 22.80 | 8.77 |
April | 23.96 | 13.91 |
May | 24.16 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.81 | 13.71 |
November | 22.68 | 6.96 |
December | 21.88 | 2.07 |
Annual Sum or Average | 23.42 | 13.68 |
Minimum of Months | 21.88 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 2.60 |
February | 23.15 | 4.29 |
March | 23.54 | 8.77 |
April | 24.14 | 13.91 |
May | 24.22 | 17.82 |
June | 24.36 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.38 | 20.49 |
October | 24.14 | 13.71 |
November | 23.69 | 6.96 |
December | 23.09 | 2.07 |
Annual Sum or Average | 23.88 | 13.68 |
Minimum of Months | 23.00 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 2.60 |
February | 22.11 | 4.29 |
March | 22.71 | 8.77 |
April | 23.96 | 13.91 |
May | 24.18 | 17.82 |
June | 24.40 | 23.21 |
July | 24.44 | 25.63 |
August | 24.39 | 24.08 |
September | 24.34 | 20.49 |
October | 23.73 | 13.71 |
November | 22.49 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.37 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.11 | 4.29 |
March | 22.69 | 8.77 |
April | 23.88 | 13.91 |
May | 24.14 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.37 | 24.08 |
September | 24.30 | 20.49 |
October | 23.74 | 13.71 |
November | 22.61 | 6.96 |
December | 21.81 | 2.07 |
Annual Sum or Average | 23.36 | 13.68 |
Minimum of Months | 21.81 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.10 | 4.29 |
March | 22.69 | 8.77 |
April | 23.88 | 13.91 |
May | 24.14 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.37 | 24.08 |
September | 24.30 | 20.49 |
October | 23.74 | 13.71 |
November | 22.60 | 6.96 |
December | 21.80 | 2.07 |
Annual Sum or Average | 23.36 | 13.68 |
Minimum of Months | 21.80 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 2.60 |
February | 23.51 | 4.29 |
March | 23.80 | 8.77 |
April | 24.16 | 13.91 |
May | 24.18 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.41 | 20.49 |
October | 24.27 | 13.71 |
November | 23.97 | 6.96 |
December | 23.48 | 2.07 |
Annual Sum or Average | 24.03 | 13.68 |
Minimum of Months | 23.39 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 2.60 |
February | 23.51 | 4.29 |
March | 23.80 | 8.77 |
April | 24.16 | 13.91 |
May | 24.19 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.41 | 20.49 |
October | 24.27 | 13.71 |
November | 23.97 | 6.96 |
December | 23.48 | 2.07 |
Annual Sum or Average | 24.03 | 13.68 |
Minimum of Months | 23.38 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 2.60 |
February | 23.72 | 4.29 |
March | 24.45 | 8.77 |
April | 25.72 | 13.91 |
May | 26.09 | 17.82 |
June | 26.72 | 23.21 |
July | 26.96 | 25.63 |
August | 26.87 | 24.08 |
September | 26.54 | 20.49 |
October | 25.67 | 13.71 |
November | 24.40 | 6.96 |
December | 23.39 | 2.07 |
Annual Sum or Average | 25.34 | 13.68 |
Minimum of Months | 23.39 | 2.07 |
Maximum of Months | 26.96 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 2.60 |
February | 22.90 | 4.29 |
March | 23.14 | 8.77 |
April | 23.85 | 13.91 |
May | 24.08 | 17.82 |
June | 24.30 | 23.21 |
July | 24.40 | 25.63 |
August | 24.36 | 24.08 |
September | 24.32 | 20.49 |
October | 23.88 | 13.71 |
November | 23.25 | 6.96 |
December | 22.78 | 2.07 |
Annual Sum or Average | 23.67 | 13.68 |
Minimum of Months | 22.73 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 2.60 |
February | 22.32 | 4.29 |
March | 22.72 | 8.77 |
April | 23.70 | 13.91 |
May | 24.04 | 17.82 |
June | 24.32 | 23.21 |
July | 24.40 | 25.63 |
August | 24.36 | 24.08 |
September | 24.29 | 20.49 |
October | 23.59 | 13.71 |
November | 22.62 | 6.96 |
December | 21.99 | 2.07 |
Annual Sum or Average | 23.38 | 13.68 |
Minimum of Months | 21.99 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 2.60 |
February | 22.89 | 4.29 |
March | 23.13 | 8.77 |
April | 23.85 | 13.91 |
May | 24.09 | 17.82 |
June | 24.31 | 23.21 |
July | 24.39 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.85 | 13.71 |
November | 23.22 | 6.96 |
December | 22.77 | 2.07 |
Annual Sum or Average | 23.66 | 13.68 |
Minimum of Months | 22.71 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 2.60 |
February | 22.24 | 4.29 |
March | 22.70 | 8.77 |
April | 23.70 | 13.91 |
May | 24.03 | 17.82 |
June | 24.33 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.28 | 20.49 |
October | 23.55 | 13.71 |
November | 22.49 | 6.96 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.33 | 13.68 |
Minimum of Months | 21.82 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 2.60 |
February | 22.21 | 4.29 |
March | 22.63 | 8.77 |
April | 23.64 | 13.91 |
May | 24.01 | 17.82 |
June | 24.31 | 23.21 |
July | 24.40 | 25.63 |
August | 24.35 | 24.08 |
September | 24.26 | 20.49 |
October | 23.54 | 13.71 |
November | 22.51 | 6.96 |
December | 21.84 | 2.07 |
Annual Sum or Average | 23.31 | 13.68 |
Minimum of Months | 21.84 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 2.60 |
February | 22.20 | 4.29 |
March | 22.63 | 8.77 |
April | 23.64 | 13.91 |
May | 24.02 | 17.82 |
June | 24.31 | 23.21 |
July | 24.40 | 25.63 |
August | 24.35 | 24.08 |
September | 24.26 | 20.49 |
October | 23.54 | 13.71 |
November | 22.50 | 6.96 |
December | 21.83 | 2.07 |
Annual Sum or Average | 23.31 | 13.68 |
Minimum of Months | 21.83 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 2.60 |
February | 23.04 | 4.29 |
March | 23.29 | 8.77 |
April | 23.90 | 13.91 |
May | 24.08 | 17.82 |
June | 24.29 | 23.21 |
July | 24.39 | 25.63 |
August | 24.37 | 24.08 |
September | 24.35 | 20.49 |
October | 23.99 | 13.71 |
November | 23.42 | 6.96 |
December | 22.94 | 2.07 |
Annual Sum or Average | 23.75 | 13.68 |
Minimum of Months | 22.88 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 2.60 |
February | 23.04 | 4.29 |
March | 23.30 | 8.77 |
April | 23.90 | 13.91 |
May | 24.09 | 17.82 |
June | 24.29 | 23.21 |
July | 24.39 | 25.63 |
August | 24.37 | 24.08 |
September | 24.35 | 20.49 |
October | 23.99 | 13.71 |
November | 23.42 | 6.96 |
December | 22.94 | 2.07 |
Annual Sum or Average | 23.75 | 13.68 |
Minimum of Months | 22.88 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 2.60 |
February | 23.70 | 4.29 |
March | 24.54 | 8.77 |
April | 26.05 | 13.91 |
May | 26.64 | 17.82 |
June | 27.52 | 23.21 |
July | 27.89 | 25.63 |
August | 27.75 | 24.08 |
September | 27.19 | 20.49 |
October | 25.92 | 13.71 |
November | 24.32 | 6.96 |
December | 23.16 | 2.07 |
Annual Sum or Average | 25.67 | 13.68 |
Minimum of Months | 23.16 | 2.07 |
Maximum of Months | 27.89 | 25.63 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.237169E+12 | 130472.786 | 16-JAN-18:15 | 22204.399 | 56867.515 | 22185.692 | 15956.414 | 0.000 | 10720.100 | 1393.029 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.210733E+12 | 136384.175 | 13-FEB-18:15 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 21261.760 | 10720.100 | 1393.029 | 606.043 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.224605E+12 | 133979.800 | 11-MAR-18:15 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 18945.256 | 10720.100 | 1393.029 | 518.173 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.235395E+12 | 162221.941 | 13-APR-17:15 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 56789.242 | 0.000 | 1393.029 | 1636.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.260386E+12 | 166716.692 | 15-MAY-18:00 | 25049.151 | 51564.864 | 22185.692 | 0.000 | 53201.550 | 10720.100 | 1393.029 | 1587.691 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.286543E+12 | 170392.020 | 18-JUN-19:00 | 25049.151 | 49704.829 | 22185.692 | 0.000 | 58785.509 | 10720.100 | 1393.029 | 1608.137 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.320301E+12 | 171347.369 | 21-JUL-19:15 | 25049.151 | 49704.829 | 22185.692 | 0.000 | 59469.484 | 10720.100 | 1393.029 | 1879.511 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.311567E+12 | 170218.882 | 17-AUG-18:00 | 25049.151 | 51564.864 | 22185.692 | 0.000 | 56390.312 | 10720.100 | 1393.029 | 1901.119 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.276042E+12 | 166673.626 | 28-SEP-17:00 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 50447.099 | 10720.100 | 1393.029 | 1709.903 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.254150E+12 | 167059.450 | 05-OCT-17:45 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 50949.277 | 10720.100 | 1393.029 | 1593.549 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.227893E+12 | 137235.574 | 02-NOV-17:45 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 21980.893 | 10720.100 | 1393.029 | 738.057 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.236865E+12 | 128436.112 | 31-DEC-18:15 | 22204.399 | 56867.515 | 22185.692 | 0.000 | 13463.748 | 10720.100 | 1393.029 | 455.993 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.308165E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.210733E+12 | 128436.112 | 22204.399 | 49704.829 | 22185.692 | 0.000 | 0.000 | 0.000 | 1393.029 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.320301E+12 | 171347.369 | 25049.151 | 56867.515 | 22185.692 | 15956.414 | 59469.484 | 10720.100 | 1393.029 | 1901.119 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.139627E+12 | 174185.847 | 17-JAN-07:00 | 0.000 | 0.000 | 0.000 | 174185.847 | 86775.670 | 86775.670 | 87410.178 |
February | 0.116033E+12 | 162259.267 | 06-FEB-07:15 | 0.000 | 0.000 | 0.000 | 162259.267 | 85871.086 | 85871.086 | 76388.180 |
March | 0.105969E+12 | 112812.620 | 04-MAR-07:15 | 0.000 | 0.000 | 0.000 | 112812.620 | 85422.328 | 85422.328 | 27390.292 |
April | 0.960973E+11 | 85039.522 | 03-APR-06:00 | 0.000 | 0.000 | 0.000 | 85039.522 | 85039.522 | 85039.522 | 0.000 |
May | 0.923582E+11 | 82656.354 | 03-MAY-06:30 | 0.000 | 0.000 | 0.000 | 82656.354 | 82656.354 | 82656.354 | 0.000 |
June | 0.831437E+11 | 80576.604 | 03-JUN-06:45 | 0.000 | 0.000 | 0.000 | 80576.604 | 80576.604 | 80576.604 | 0.000 |
July | 0.816351E+11 | 79051.018 | 02-JUL-06:00 | 0.000 | 0.000 | 0.000 | 79051.018 | 79051.018 | 79051.018 | 0.000 |
August | 0.807378E+11 | 78554.494 | 31-AUG-06:45 | 0.000 | 0.000 | 0.000 | 78554.494 | 78554.494 | 78554.494 | 0.000 |
September | 0.807261E+11 | 79722.266 | 28-SEP-06:00 | 0.000 | 0.000 | 0.000 | 79722.266 | 79722.266 | 79722.266 | 0.000 |
October | 0.899689E+11 | 107114.289 | 26-OCT-05:00 | 0.000 | 0.000 | 0.000 | 107114.289 | 79577.887 | 79577.887 | 27536.402 |
November | 0.952883E+11 | 121253.649 | 26-NOV-07:15 | 0.000 | 0.000 | 0.000 | 121253.649 | 82648.696 | 82648.696 | 38604.953 |
December | 0.131457E+12 | 161025.081 | 22-DEC-07:30 | 0.000 | 0.000 | 0.000 | 161025.081 | 85376.451 | 85376.451 | 75648.630 |
Annual Sum or Average | 0.119304E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.807261E+11 | 78554.494 | 0.000 | 0.000 | 0.000 | 78554.494 | 78554.494 | 78554.494 | 0.000 | |
Maximum of Months | 0.139627E+12 | 174185.847 | 0.000 | 0.000 | 0.000 | 174185.847 | 86775.670 | 86775.670 | 87410.178 |