Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2018-10-19 09:40:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4021.66 | 513.20 | 569.65 |
Net Site Energy | 4021.66 | 513.20 | 569.65 |
Total Source Energy | 9716.11 | 1239.86 | 1376.24 |
Net Source Energy | 9716.11 | 1239.86 | 1376.24 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 76.28 | 228.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 577.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.40 | 0.00 | 0.00 | 0.00 | 0.00 | 370.65 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1221.51 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2571.60 | 1450.06 | 0.00 | 0.00 | 0.00 | 5149.17 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 228.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 76.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 134.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 577.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 41.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 5.40 | 0.00 | 0.00 | 0.00 | 0.00 | 370.65 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1221.51 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.29 | 205.39 | 0.00 | 0.00 | 0.00 | 0.73 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 364.25 | 205.39 | 0.00 | 0.00 | 0.00 | 0.73 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.56 | 185.04 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 328.16 | 185.04 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2571.60 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2571.60 | 100.00 |
Total On-Site and Utility Electric Sources | 2571.60 | 100.00 |
Total Electricity End Uses | 2571.60 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5149.17 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5149.17 | 100.00 |
Total Water End Uses | 5149.17 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 237.50 |
Time Setpoint Not Met During Occupied Cooling | 12.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 289.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | William R Fairchild WA USA TMY3 WMO#=727885 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-17:15 | 10-JAN-06:45 | - | - | - | 22-JUL-17:00 |
Heating | 0.00 | 82016.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 54432.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18311.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1337.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1864.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 84193.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 156163.15 | 166210.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 82016.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 54432.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 18331.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 3872.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 18311.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1337.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1864.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 84193.77 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 241.59 | 247.75 | 0.00 | 0.00 | 0.00 |
Cooling | 424.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 532.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1828.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 132.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1324.12 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8144.25 | 1571.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 34.22 | 35.09 | 0.00 | 0.00 | 0.00 |
Cooling | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 259.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 187.55 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1153.59 | 222.65 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 34.22 | 35.09 | 0.00 | 0.00 | 0.00 |
Cooling | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 259.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 187.55 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1153.59 | 222.65 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.58 | 83.58 | 168.19 | |
Exterior Lighting Total | 10720.10 | 168.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 234360.46 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 187488.37 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3251.00 | 2480.29 | 770.72 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2290.45 | 1744.95 | 545.51 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4460.74 | 3412.41 | 1048.33 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1627.26 | 1239.17 | 388.09 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 978.24 | 738.41 | 239.84 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 942.99 | 711.80 | 231.18 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2380.63 | 1803.96 | 576.67 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2455.71 | 1862.20 | 593.52 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4209.73 | 3223.62 | 986.11 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3052.70 | 2333.55 | 719.15 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4153.75 | 3177.50 | 976.25 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2271.03 | 1742.51 | 528.53 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1466.34 | 1111.65 | 354.69 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1433.01 | 1086.24 | 346.77 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3133.42 | 2386.87 | 746.55 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3165.13 | 2411.45 | 753.68 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4243.29 | 3247.89 | 995.40 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3102.84 | 2371.86 | 730.98 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3955.57 | 3023.37 | 932.21 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2330.98 | 1788.80 | 542.17 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1530.64 | 1160.78 | 369.86 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1497.08 | 1135.17 | 361.91 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3187.44 | 2428.43 | 759.01 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3204.79 | 2441.88 | 762.91 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4252.01 | 3254.24 | 997.77 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3118.12 | 2383.31 | 734.80 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3941.64 | 3012.16 | 929.48 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2342.27 | 1797.28 | 544.99 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1550.03 | 1175.51 | 374.52 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1516.35 | 1149.80 | 366.54 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3200.89 | 2438.62 | 762.28 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3216.21 | 2450.50 | 765.72 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4287.68 | 3281.55 | 1006.13 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3158.79 | 2414.48 | 744.32 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3974.25 | 3037.10 | 937.15 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2378.78 | 1825.42 | 553.37 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1591.98 | 1207.57 | 384.41 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1558.19 | 1181.77 | 376.42 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3239.23 | 2468.13 | 771.10 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3254.22 | 2479.75 | 774.47 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4233.24 | 3239.06 | 994.18 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3108.22 | 2375.10 | 733.12 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3920.00 | 2994.78 | 925.23 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2326.67 | 1784.68 | 541.99 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1547.17 | 1173.10 | 374.07 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1513.51 | 1147.42 | 366.09 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3187.48 | 2427.86 | 759.62 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3202.43 | 2439.45 | 762.98 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4211.36 | 3221.85 | 989.51 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3090.31 | 2361.02 | 729.29 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3898.13 | 2977.57 | 920.55 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2306.62 | 1768.90 | 537.72 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1532.98 | 1162.13 | 370.84 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1499.38 | 1136.50 | 362.88 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3167.74 | 2412.41 | 755.32 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3182.65 | 2423.98 | 758.67 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4204.64 | 3216.41 | 988.23 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3088.42 | 2359.35 | 729.06 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3890.99 | 2971.82 | 919.17 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2301.75 | 1764.95 | 536.80 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1534.85 | 1163.49 | 371.36 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1501.34 | 1137.93 | 363.42 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3162.87 | 2408.51 | 754.36 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3177.79 | 2420.08 | 757.71 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4289.29 | 3282.99 | 1006.30 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3187.25 | 2435.58 | 751.67 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3950.59 | 3017.78 | 932.81 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2314.77 | 1773.22 | 541.55 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1622.39 | 1230.50 | 391.89 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1588.50 | 1204.63 | 383.87 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3219.48 | 2451.32 | 768.16 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3234.43 | 2462.91 | 771.52 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5324.13 | 4082.55 | 1241.58 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3959.09 | 3031.76 | 927.33 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4921.76 | 3770.27 | 1151.49 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2956.66 | 2265.62 | 691.04 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2202.06 | 1663.23 | 538.83 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2204.71 | 1665.27 | 539.45 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4333.66 | 3315.65 | 1018.01 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4348.33 | 3327.02 | 1021.31 | 0.77 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3251.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2290.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4460.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1627.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 978.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 942.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2380.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2455.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4209.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3052.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4153.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2271.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1466.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1433.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3133.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3165.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4243.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3102.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3955.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2330.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1530.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1497.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3187.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3204.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4252.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3118.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3941.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2342.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1550.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1516.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3200.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3216.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4287.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3158.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3974.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2378.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1591.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1558.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3239.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3254.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4233.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3108.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3920.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2326.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1547.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1513.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3187.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3202.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4211.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3090.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3898.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2306.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1532.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1499.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3167.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3182.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4204.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3088.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3890.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2301.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1534.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1501.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3162.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3177.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4289.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3187.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3950.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2314.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1622.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1588.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3219.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3234.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5324.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3959.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4921.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2956.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2202.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2204.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4333.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4348.33 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2191.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2199.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2975.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2196.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1679.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1679.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1667.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1676.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2039.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2045.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2061.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2041.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1421.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1421.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1418.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1419.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1980.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1987.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1979.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1983.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1976.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1983.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1972.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1979.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1956.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1962.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1953.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1959.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2008.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2014.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2004.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2011.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2035.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2042.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2032.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2038.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1382.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1382.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1376.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1376.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2068.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2074.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2065.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2071.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1411.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1411.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1405.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1405.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2217.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2221.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2214.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2218.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1546.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1546.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1542.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1542.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2810.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2819.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2807.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2816.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2185.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2185.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2173.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2173.32 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.77 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 179.79 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 349.20 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.13 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.07 | 77.38 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.07 | 74.66 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 183.16 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 189.21 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.11 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 240.79 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 325.84 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.61 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 115.84 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 113.23 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.65 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.20 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 333.39 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 244.74 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 309.81 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 186.41 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 120.90 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.27 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.95 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 249.34 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 334.03 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.91 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 308.62 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.27 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 122.42 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 119.77 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 248.99 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 250.22 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 336.85 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 249.12 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 311.20 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.18 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 125.72 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 123.06 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 252.04 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.25 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.42 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.02 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 306.79 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 185.94 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 122.16 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 119.51 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.86 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 249.06 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 330.62 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.55 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 304.99 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 184.29 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 121.02 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.38 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.24 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.44 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 330.04 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.37 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 304.38 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 183.87 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 121.16 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 118.52 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.83 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.03 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 337.15 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.26 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 309.14 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 184.25 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 128.07 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 125.40 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 250.10 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.31 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 419.75 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 312.33 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 387.25 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 234.35 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.31 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.52 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 340.00 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 341.18 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0051 | 1300.12 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2385.38 | 2862.46 | 0.189 | 0.227 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
G NW APARTMENT | 1689.92 | 2027.90 | 0.134 | 0.161 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
OFFICE | 3282.42 | 3938.91 | 0.260 | 0.312 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
G NE APARTMENT | 1213.70 | 1456.44 | 0.096 | 0.115 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
G N1 APARTMENT | 727.36 | 872.83 | 0.058 | 0.069 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
G N2 APARTMENT | 701.79 | 842.15 | 0.056 | 0.067 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
G S1 APARTMENT | 1721.66 | 2065.99 | 0.136 | 0.164 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
G S2 APARTMENT | 1778.51 | 2134.21 | 0.141 | 0.169 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F2 SW APARTMENT | 3112.28 | 3734.74 | 0.246 | 0.296 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 25.85 | 0.00838 |
F2 NW APARTMENT | 2263.33 | 2716.00 | 0.179 | 0.215 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F2 SE APARTMENT | 3062.78 | 3675.34 | 0.242 | 0.291 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F2 NE APARTMENT | 1707.04 | 2048.44 | 0.135 | 0.162 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F2 N1 APARTMENT | 1088.86 | 1306.64 | 0.086 | 0.103 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F2 N2 APARTMENT | 1064.29 | 1277.15 | 0.084 | 0.101 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F2 S1 APARTMENT | 2290.20 | 2748.25 | 0.181 | 0.218 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F2 S2 APARTMENT | 2314.20 | 2777.03 | 0.183 | 0.220 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F3 SW APARTMENT | 3133.76 | 3760.51 | 0.248 | 0.298 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
F3 NW APARTMENT | 2300.45 | 2760.54 | 0.182 | 0.218 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F3 SE APARTMENT | 2912.10 | 3494.52 | 0.230 | 0.277 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F3 NE APARTMENT | 1752.13 | 2102.56 | 0.139 | 0.166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F3 N1 APARTMENT | 1136.45 | 1363.74 | 0.090 | 0.108 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F3 N2 APARTMENT | 1111.67 | 1334.00 | 0.088 | 0.106 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F3 S1 APARTMENT | 2330.60 | 2796.73 | 0.184 | 0.221 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F3 S2 APARTMENT | 2343.73 | 2812.48 | 0.186 | 0.223 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F4 SW APARTMENT | 3139.75 | 3767.70 | 0.249 | 0.298 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
F4 NW APARTMENT | 2311.43 | 2773.72 | 0.183 | 0.220 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F4 SE APARTMENT | 2900.96 | 3481.15 | 0.230 | 0.276 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F4 NE APARTMENT | 1760.26 | 2112.32 | 0.139 | 0.167 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F4 N1 APARTMENT | 1150.67 | 1380.81 | 0.091 | 0.109 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F4 N2 APARTMENT | 1125.79 | 1350.95 | 0.089 | 0.107 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F4 S1 APARTMENT | 2340.43 | 2808.51 | 0.185 | 0.222 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F4 S2 APARTMENT | 2352.02 | 2822.43 | 0.186 | 0.223 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
M SW APARTMENT | 3166.23 | 3799.48 | 0.251 | 0.301 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
M NW APARTMENT | 2341.67 | 2810.00 | 0.185 | 0.222 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
M SE APARTMENT | 2925.13 | 3510.16 | 0.232 | 0.278 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
M NE APARTMENT | 1787.64 | 2145.17 | 0.141 | 0.170 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
M N1 APARTMENT | 1181.73 | 1418.07 | 0.094 | 0.112 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
M N2 APARTMENT | 1156.75 | 1388.10 | 0.092 | 0.110 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
M S1 APARTMENT | 2369.13 | 2842.96 | 0.188 | 0.225 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
M S2 APARTMENT | 2380.47 | 2856.57 | 0.188 | 0.226 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F6 SW APARTMENT | 3124.63 | 3749.55 | 0.247 | 0.297 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
F6 NW APARTMENT | 2303.14 | 2763.77 | 0.182 | 0.219 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F6 SE APARTMENT | 2883.69 | 3460.43 | 0.228 | 0.274 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F6 NE APARTMENT | 1747.71 | 2097.26 | 0.138 | 0.166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F6 N1 APARTMENT | 1148.22 | 1377.87 | 0.091 | 0.109 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F6 N2 APARTMENT | 1123.37 | 1348.04 | 0.089 | 0.107 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F6 S1 APARTMENT | 2329.76 | 2795.71 | 0.184 | 0.221 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F6 S2 APARTMENT | 2341.06 | 2809.28 | 0.185 | 0.222 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F7 SW APARTMENT | 3107.71 | 3729.25 | 0.246 | 0.295 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
F7 NW APARTMENT | 2289.30 | 2747.16 | 0.181 | 0.217 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F7 SE APARTMENT | 2866.78 | 3440.13 | 0.227 | 0.272 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F7 NE APARTMENT | 1732.20 | 2078.64 | 0.137 | 0.165 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F7 N1 APARTMENT | 1137.53 | 1365.04 | 0.090 | 0.108 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F7 N2 APARTMENT | 1112.74 | 1335.28 | 0.088 | 0.106 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F7 S1 APARTMENT | 2314.61 | 2777.53 | 0.183 | 0.220 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F7 S2 APARTMENT | 2325.89 | 2791.07 | 0.184 | 0.221 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F8 SW APARTMENT | 3102.28 | 3722.74 | 0.246 | 0.295 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
F8 NW APARTMENT | 2287.58 | 2745.09 | 0.181 | 0.217 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F8 SE APARTMENT | 2861.05 | 3433.26 | 0.226 | 0.272 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F8 NE APARTMENT | 1728.26 | 2073.91 | 0.137 | 0.164 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94 | 0.00838 |
F8 N1 APARTMENT | 1138.81 | 1366.57 | 0.090 | 0.108 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F8 N2 APARTMENT | 1114.08 | 1336.89 | 0.088 | 0.106 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F8 S1 APARTMENT | 2310.73 | 2772.88 | 0.183 | 0.219 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F8 S2 APARTMENT | 2322.02 | 2786.43 | 0.184 | 0.221 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
F9 SW APARTMENT | 3169.09 | 3802.90 | 0.251 | 0.301 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 25.85 | 0.00838 |
F9 NW APARTMENT | 2361.79 | 2834.15 | 0.187 | 0.224 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.22 | 0.00838 |
F9 SE APARTMENT | 2905.80 | 3486.96 | 0.230 | 0.276 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
F9 NE APARTMENT | 1731.84 | 2078.21 | 0.137 | 0.164 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 23.28 | 0.00838 |
F9 N1 APARTMENT | 1203.77 | 1444.53 | 0.095 | 0.114 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F9 N2 APARTMENT | 1178.73 | 1414.47 | 0.093 | 0.112 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
F9 S1 APARTMENT | 2350.87 | 2821.05 | 0.186 | 0.223 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
F9 S2 APARTMENT | 2362.19 | 2834.63 | 0.187 | 0.224 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
T SW APARTMENT | 3945.45 | 4734.54 | 0.312 | 0.375 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.13 | 0.00838 |
T NW APARTMENT | 2935.75 | 3522.90 | 0.232 | 0.279 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 24.90 | 0.00838 |
T SE APARTMENT | 3640.04 | 4368.05 | 0.288 | 0.346 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17 | 0.00838 |
T NE APARTMENT | 2202.80 | 2643.36 | 0.174 | 0.209 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 23.97 | 0.00838 |
T N1 APARTMENT | 1582.09 | 1898.51 | 0.125 | 0.150 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 26.40 | 0.00838 |
T N2 APARTMENT | 1584.07 | 1900.88 | 0.125 | 0.150 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
T S1 APARTMENT | 3195.83 | 3835.00 | 0.253 | 0.304 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
T S2 APARTMENT | 3206.94 | 3848.33 | 0.254 | 0.305 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 26.29 | 0.00838 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1170.32 | 1404.38 | 0.053 | 0.063 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G NW APARTMENT | 1176.65 | 1411.97 | 0.053 | 0.064 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
OFFICE | 1513.41 | 1816.09 | 0.068 | 0.082 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -4.30 | 0.00266 |
G NE APARTMENT | 1174.59 | 1409.51 | 0.053 | 0.063 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G N1 APARTMENT | 736.85 | 884.23 | 0.033 | 0.040 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G N2 APARTMENT | 736.80 | 884.16 | 0.033 | 0.040 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G S1 APARTMENT | 727.17 | 872.60 | 0.033 | 0.039 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
G S2 APARTMENT | 734.35 | 881.22 | 0.033 | 0.040 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
F2 SW APARTMENT | 1041.30 | 1249.55 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 NW APARTMENT | 1046.29 | 1255.55 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 SE APARTMENT | 1060.10 | 1272.12 | 0.048 | 0.057 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 NE APARTMENT | 1043.53 | 1252.23 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 N1 APARTMENT | 518.96 | 622.76 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 N2 APARTMENT | 518.89 | 622.67 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 S1 APARTMENT | 516.28 | 619.53 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F2 S2 APARTMENT | 517.67 | 621.21 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 SW APARTMENT | 991.64 | 1189.97 | 0.045 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 NW APARTMENT | 997.21 | 1196.65 | 0.045 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 SE APARTMENT | 991.25 | 1189.50 | 0.045 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 NE APARTMENT | 994.33 | 1193.20 | 0.045 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 N1 APARTMENT | 462.30 | 554.76 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 N2 APARTMENT | 462.22 | 554.67 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 S1 APARTMENT | 457.37 | 548.85 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F3 S2 APARTMENT | 457.54 | 549.04 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 SW APARTMENT | 987.93 | 1185.51 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 NW APARTMENT | 993.92 | 1192.71 | 0.045 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 SE APARTMENT | 985.30 | 1182.36 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 NE APARTMENT | 991.02 | 1189.23 | 0.045 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 N1 APARTMENT | 451.64 | 541.97 | 0.020 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 N2 APARTMENT | 451.56 | 541.87 | 0.020 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 S1 APARTMENT | 446.07 | 535.29 | 0.020 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F4 S2 APARTMENT | 446.03 | 535.24 | 0.020 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M SW APARTMENT | 971.46 | 1165.75 | 0.044 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M NW APARTMENT | 976.58 | 1171.89 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M SE APARTMENT | 968.62 | 1162.34 | 0.044 | 0.052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M NE APARTMENT | 973.71 | 1168.45 | 0.044 | 0.053 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M N1 APARTMENT | 430.89 | 517.07 | 0.019 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M N2 APARTMENT | 430.81 | 516.98 | 0.019 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M S1 APARTMENT | 426.18 | 511.42 | 0.019 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
M S2 APARTMENT | 426.11 | 511.33 | 0.019 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 SW APARTMENT | 1014.97 | 1217.96 | 0.046 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 NW APARTMENT | 1020.85 | 1225.02 | 0.046 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 SE APARTMENT | 1012.14 | 1214.56 | 0.046 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 NE APARTMENT | 1018.02 | 1221.62 | 0.046 | 0.055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 N1 APARTMENT | 467.54 | 561.05 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 N2 APARTMENT | 467.46 | 560.96 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 S1 APARTMENT | 462.02 | 554.42 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F6 S2 APARTMENT | 461.94 | 554.33 | 0.021 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 SW APARTMENT | 1038.24 | 1245.89 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 NW APARTMENT | 1043.83 | 1252.60 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 SE APARTMENT | 1035.47 | 1242.56 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 NE APARTMENT | 1041.05 | 1249.26 | 0.047 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 N1 APARTMENT | 486.09 | 583.31 | 0.022 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 N2 APARTMENT | 486.02 | 583.22 | 0.022 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 S1 APARTMENT | 480.85 | 577.02 | 0.022 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F7 S2 APARTMENT | 480.78 | 576.94 | 0.022 | 0.026 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 SW APARTMENT | 1066.51 | 1279.81 | 0.048 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 NW APARTMENT | 1071.62 | 1285.94 | 0.048 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 SE APARTMENT | 1063.80 | 1276.56 | 0.048 | 0.057 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 NE APARTMENT | 1068.91 | 1282.69 | 0.048 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 N1 APARTMENT | 510.41 | 612.50 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 N2 APARTMENT | 510.34 | 612.41 | 0.023 | 0.028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 S1 APARTMENT | 505.63 | 606.75 | 0.023 | 0.027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F8 S2 APARTMENT | 505.55 | 606.66 | 0.023 | 0.027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 SW APARTMENT | 1192.18 | 1430.62 | 0.054 | 0.064 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 NW APARTMENT | 1195.26 | 1434.32 | 0.054 | 0.065 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 SE APARTMENT | 1189.52 | 1427.42 | 0.054 | 0.064 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 NE APARTMENT | 1192.60 | 1431.12 | 0.054 | 0.064 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 N1 APARTMENT | 624.76 | 749.71 | 0.028 | 0.034 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 N2 APARTMENT | 624.69 | 749.62 | 0.028 | 0.034 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 S1 APARTMENT | 621.59 | 745.90 | 0.028 | 0.034 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
F9 S2 APARTMENT | 621.52 | 745.82 | 0.028 | 0.034 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T SW APARTMENT | 1693.21 | 2031.85 | 0.076 | 0.091 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T NW APARTMENT | 1701.00 | 2041.21 | 0.077 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T SE APARTMENT | 1690.81 | 2028.97 | 0.076 | 0.091 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T NE APARTMENT | 1698.61 | 2038.33 | 0.076 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T N1 APARTMENT | 1165.36 | 1398.43 | 0.052 | 0.063 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T N2 APARTMENT | 1165.29 | 1398.35 | 0.052 | 0.063 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T S1 APARTMENT | 1154.83 | 1385.80 | 0.052 | 0.062 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
T S2 APARTMENT | 1154.76 | 1385.72 | 0.052 | 0.062 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -4.30 | 0.00266 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.23 | 0.23 | 0.06 | 0.06 |
AIRLOOP G NW | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP OFFICE | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP G NE | 0.12 | 0.12 | 0.06 | 0.06 |
AIRLOOP G N1 | 0.07 | 0.07 | 0.04 | 0.04 |
AIRLOOP G N2 | 0.07 | 0.07 | 0.04 | 0.04 |
AIRLOOP G S1 | 0.16 | 0.16 | 0.04 | 0.04 |
AIRLOOP G S2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F2 SW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP F2 NW | 0.21 | 0.21 | 0.06 | 0.06 |
AIRLOOP F2 SE | 0.29 | 0.29 | 0.06 | 0.06 |
AIRLOOP F2 NE | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F2 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F2 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F2 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F2 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F3 SW | 0.30 | 0.30 | 0.05 | 0.05 |
AIRLOOP F3 NW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F3 SE | 0.28 | 0.28 | 0.05 | 0.05 |
AIRLOOP F3 NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F3 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F3 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F3 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F3 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F4 SW | 0.30 | 0.30 | 0.05 | 0.05 |
AIRLOOP F4 NW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F4 SE | 0.28 | 0.28 | 0.05 | 0.05 |
AIRLOOP F4 NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F4 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F4 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F4 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F4 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP M SW | 0.30 | 0.30 | 0.05 | 0.05 |
AIRLOOP M NW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP M SE | 0.28 | 0.28 | 0.05 | 0.05 |
AIRLOOP M NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP M N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.30 | 0.30 | 0.05 | 0.05 |
AIRLOOP F6 NW | 0.22 | 0.22 | 0.06 | 0.06 |
AIRLOOP F6 SE | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F6 NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F6 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F6 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F6 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F6 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F7 SW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP F7 NW | 0.22 | 0.22 | 0.06 | 0.06 |
AIRLOOP F7 SE | 0.27 | 0.27 | 0.06 | 0.06 |
AIRLOOP F7 NE | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F7 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F7 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F7 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F7 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F8 SW | 0.29 | 0.29 | 0.06 | 0.06 |
AIRLOOP F8 NW | 0.22 | 0.22 | 0.06 | 0.06 |
AIRLOOP F8 SE | 0.27 | 0.27 | 0.06 | 0.06 |
AIRLOOP F8 NE | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F8 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F8 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F8 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F8 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F9 SW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP F9 NW | 0.22 | 0.22 | 0.06 | 0.06 |
AIRLOOP F9 SE | 0.28 | 0.28 | 0.06 | 0.06 |
AIRLOOP F9 NE | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F9 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F9 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F9 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F9 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP T SW | 0.37 | 0.37 | 0.09 | 0.09 |
AIRLOOP T NW | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP T SE | 0.35 | 0.35 | 0.09 | 0.09 |
AIRLOOP T NE | 0.21 | 0.21 | 0.09 | 0.09 |
AIRLOOP T N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP T N2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP T S1 | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP T S2 | 0.30 | 0.30 | 0.06 | 0.06 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1764.75 | 6073.25 | 26.25 |
G NW APARTMENT | 893.50 | 7196.25 | 67.50 |
OFFICE | 756.50 | 1145.50 | 1.75 |
G NE APARTMENT | 820.75 | 7242.50 | 77.00 |
G N1 APARTMENT | 458.00 | 7796.00 | 98.25 |
G N2 APARTMENT | 451.75 | 7807.50 | 98.75 |
G S1 APARTMENT | 1548.75 | 6189.25 | 45.25 |
G S2 APARTMENT | 1603.00 | 6121.50 | 41.75 |
F2 SW APARTMENT | 3006.00 | 4596.50 | 6.75 |
F2 NW APARTMENT | 1798.50 | 5872.75 | 11.00 |
F2 SE APARTMENT | 3183.75 | 4453.00 | 7.00 |
F2 NE APARTMENT | 1772.50 | 5880.50 | 17.00 |
F2 N1 APARTMENT | 1296.50 | 6438.50 | 27.25 |
F2 N2 APARTMENT | 1286.00 | 6449.75 | 28.75 |
F2 S1 APARTMENT | 3105.75 | 4268.50 | 18.00 |
F2 S2 APARTMENT | 3137.25 | 4241.00 | 18.25 |
F3 SW APARTMENT | 3329.25 | 4218.50 | 3.50 |
F3 NW APARTMENT | 2078.00 | 5509.25 | 6.50 |
F3 SE APARTMENT | 3408.50 | 4225.50 | 4.00 |
F3 NE APARTMENT | 2056.75 | 5511.75 | 8.75 |
F3 N1 APARTMENT | 1632.75 | 5825.50 | 21.75 |
F3 N2 APARTMENT | 1621.25 | 5834.25 | 22.75 |
F3 S1 APARTMENT | 3683.25 | 3625.00 | 3.00 |
F3 S2 APARTMENT | 3696.75 | 3613.50 | 3.00 |
F4 SW APARTMENT | 3408.75 | 4113.50 | 4.00 |
F4 NW APARTMENT | 2135.50 | 5397.25 | 6.50 |
F4 SE APARTMENT | 3453.25 | 4166.50 | 4.25 |
F4 NE APARTMENT | 2110.25 | 5418.75 | 7.75 |
F4 N1 APARTMENT | 1757.25 | 5602.50 | 22.25 |
F4 N2 APARTMENT | 1743.50 | 5610.25 | 24.25 |
F4 S1 APARTMENT | 3866.50 | 3367.50 | 0.00 |
F4 S2 APARTMENT | 3869.25 | 3363.25 | 0.00 |
M SW APARTMENT | 3463.00 | 4050.50 | 3.25 |
M NW APARTMENT | 2171.00 | 5341.50 | 6.25 |
M SE APARTMENT | 3497.75 | 4110.50 | 4.00 |
M NE APARTMENT | 2149.50 | 5358.00 | 7.25 |
M N1 APARTMENT | 1837.25 | 5474.75 | 21.00 |
M N2 APARTMENT | 1830.75 | 5480.50 | 20.00 |
M S1 APARTMENT | 3987.50 | 3232.00 | 0.00 |
M S2 APARTMENT | 3988.75 | 3236.25 | 0.00 |
F6 SW APARTMENT | 3288.50 | 4199.75 | 4.00 |
F6 NW APARTMENT | 1965.25 | 5572.75 | 7.00 |
F6 SE APARTMENT | 3333.75 | 4253.25 | 3.75 |
F6 NE APARTMENT | 1945.75 | 5578.75 | 9.75 |
F6 N1 APARTMENT | 1618.00 | 5765.25 | 23.50 |
F6 N2 APARTMENT | 1605.75 | 5774.25 | 24.50 |
F6 S1 APARTMENT | 3763.00 | 3421.25 | 0.00 |
F6 S2 APARTMENT | 3764.50 | 3424.25 | 0.00 |
F7 SW APARTMENT | 3166.50 | 4330.00 | 3.50 |
F7 NW APARTMENT | 1816.00 | 5750.50 | 9.00 |
F7 SE APARTMENT | 3202.50 | 4369.00 | 3.50 |
F7 NE APARTMENT | 1771.00 | 5742.25 | 12.00 |
F7 N1 APARTMENT | 1441.50 | 6030.25 | 24.25 |
F7 N2 APARTMENT | 1431.25 | 6038.50 | 25.00 |
F7 S1 APARTMENT | 3574.00 | 3601.25 | 0.00 |
F7 S2 APARTMENT | 3578.75 | 3604.00 | 0.00 |
F8 SW APARTMENT | 3051.50 | 4461.00 | 3.25 |
F8 NW APARTMENT | 1695.25 | 5907.50 | 11.00 |
F8 SE APARTMENT | 3092.75 | 4495.25 | 3.00 |
F8 NE APARTMENT | 1641.25 | 5917.25 | 15.00 |
F8 N1 APARTMENT | 1316.75 | 6247.25 | 22.25 |
F8 N2 APARTMENT | 1302.25 | 6263.25 | 22.25 |
F8 S1 APARTMENT | 3389.75 | 3812.50 | 5.00 |
F8 S2 APARTMENT | 3398.00 | 3815.25 | 5.25 |
F9 SW APARTMENT | 2832.75 | 4713.25 | 2.75 |
F9 NW APARTMENT | 1568.25 | 6112.75 | 17.50 |
F9 SE APARTMENT | 2894.75 | 4719.00 | 4.25 |
F9 NE APARTMENT | 1498.75 | 6173.50 | 21.00 |
F9 N1 APARTMENT | 1195.25 | 6507.00 | 17.75 |
F9 N2 APARTMENT | 1181.75 | 6519.50 | 18.00 |
F9 S1 APARTMENT | 3079.25 | 4187.25 | 6.75 |
F9 S2 APARTMENT | 3087.00 | 4186.50 | 6.75 |
T SW APARTMENT | 2397.25 | 5498.50 | 77.25 |
T NW APARTMENT | 1607.75 | 6564.00 | 156.25 |
T SE APARTMENT | 2459.75 | 5468.00 | 83.25 |
T NE APARTMENT | 1650.50 | 6514.00 | 173.25 |
T N1 APARTMENT | 1193.00 | 6801.50 | 46.25 |
T N2 APARTMENT | 1196.25 | 6790.75 | 46.50 |
T S1 APARTMENT | 2526.25 | 5089.00 | 19.75 |
T S2 APARTMENT | 2534.00 | 5089.50 | 20.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4405.25 | 7923.00 | 289.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
G NW APARTMENT | 12.25 | 2.75 | 12.25 | 2.75 |
OFFICE | 6.75 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 10.75 | 3.00 | 10.75 | 3.00 |
G N1 APARTMENT | 2.75 | 8.00 | 2.75 | 8.00 |
G N2 APARTMENT | 3.50 | 9.25 | 3.50 | 9.25 |
G S1 APARTMENT | 5.50 | 0.00 | 5.50 | 0.00 |
G S2 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
F2 SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F2 NW APARTMENT | 6.75 | 2.75 | 6.75 | 2.75 |
F2 SE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F2 NE APARTMENT | 11.00 | 2.50 | 11.00 | 2.50 |
F2 N1 APARTMENT | 0.50 | 7.00 | 0.50 | 7.00 |
F2 N2 APARTMENT | 1.25 | 7.75 | 1.25 | 7.75 |
F2 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F2 S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F3 SW APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F3 NW APARTMENT | 5.25 | 3.25 | 5.25 | 3.25 |
F3 SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F3 NE APARTMENT | 9.75 | 2.75 | 9.75 | 2.75 |
F3 N1 APARTMENT | 0.75 | 8.50 | 0.75 | 8.50 |
F3 N2 APARTMENT | 0.50 | 8.75 | 0.50 | 8.75 |
F3 S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F3 S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F4 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F4 NW APARTMENT | 5.00 | 3.25 | 5.00 | 3.25 |
F4 SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F4 NE APARTMENT | 11.75 | 2.75 | 11.75 | 2.75 |
F4 N1 APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
F4 N2 APARTMENT | 0.25 | 8.75 | 0.25 | 8.75 |
F4 S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F4 S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M NW APARTMENT | 5.00 | 3.25 | 5.00 | 3.25 |
M SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M NE APARTMENT | 11.00 | 2.75 | 11.00 | 2.75 |
M N1 APARTMENT | 0.25 | 8.75 | 0.25 | 8.75 |
M N2 APARTMENT | 0.25 | 8.75 | 0.25 | 8.75 |
M S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F6 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F6 NW APARTMENT | 4.75 | 3.25 | 4.75 | 3.25 |
F6 SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F6 NE APARTMENT | 11.75 | 3.25 | 11.75 | 3.25 |
F6 N1 APARTMENT | 0.25 | 8.50 | 0.25 | 8.50 |
F6 N2 APARTMENT | 0.00 | 9.25 | 0.00 | 9.25 |
F6 S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F6 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F7 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F7 NW APARTMENT | 5.25 | 3.25 | 5.25 | 3.25 |
F7 SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F7 NE APARTMENT | 13.00 | 3.50 | 13.00 | 3.50 |
F7 N1 APARTMENT | 1.00 | 8.00 | 1.00 | 8.00 |
F7 N2 APARTMENT | 1.00 | 8.50 | 1.00 | 8.50 |
F7 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F7 S2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F8 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F8 NW APARTMENT | 4.75 | 3.25 | 4.75 | 3.25 |
F8 SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F8 NE APARTMENT | 14.25 | 3.50 | 14.25 | 3.50 |
F8 N1 APARTMENT | 0.75 | 7.75 | 0.75 | 7.75 |
F8 N2 APARTMENT | 0.25 | 8.50 | 0.25 | 8.50 |
F8 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F8 S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F9 SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F9 NW APARTMENT | 3.25 | 3.25 | 3.25 | 3.25 |
F9 SE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F9 NE APARTMENT | 9.50 | 5.50 | 9.50 | 5.50 |
F9 N1 APARTMENT | 3.25 | 6.75 | 3.25 | 6.75 |
F9 N2 APARTMENT | 3.50 | 7.25 | 3.50 | 7.25 |
F9 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F9 S2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.50 | 3.75 | 0.50 | 3.75 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 4.00 | 2.00 | 4.00 | 2.00 |
T N1 APARTMENT | 13.25 | 9.00 | 13.25 | 9.00 |
T N2 APARTMENT | 15.75 | 7.75 | 15.75 | 7.75 |
T S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 243.50 | 12.25 | 237.50 | 12.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.057 | 0.000 | 0.208 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.057 | 0.000 | 0.198 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.063 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.057 | 0.000 | 0.199 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.034 | 0.000 | 0.190 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.034 | 0.000 | 0.190 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.034 | 0.000 | 0.204 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.034 | 0.000 | 0.205 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.082 | 0.000 | 0.224 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.082 | 0.000 | 0.218 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.082 | 0.000 | 0.225 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.082 | 0.000 | 0.219 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.049 | 0.000 | 0.212 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.049 | 0.000 | 0.212 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.049 | 0.000 | 0.222 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.049 | 0.000 | 0.222 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.097 | 0.000 | 0.232 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.097 | 0.000 | 0.228 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.097 | 0.000 | 0.233 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.097 | 0.000 | 0.229 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.058 | 0.000 | 0.222 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.058 | 0.000 | 0.222 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.059 | 0.000 | 0.231 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.059 | 0.000 | 0.231 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.109 | 0.000 | 0.239 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.108 | 0.000 | 0.235 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.109 | 0.000 | 0.239 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.108 | 0.000 | 0.235 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.065 | 0.000 | 0.229 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.065 | 0.000 | 0.230 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.065 | 0.000 | 0.237 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.065 | 0.000 | 0.237 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.118 | 0.000 | 0.244 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.118 | 0.000 | 0.241 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.118 | 0.000 | 0.245 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.118 | 0.000 | 0.241 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.071 | 0.000 | 0.236 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.071 | 0.000 | 0.236 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.071 | 0.000 | 0.243 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.071 | 0.000 | 0.243 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.249 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.245 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.250 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.246 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.076 | 0.000 | 0.240 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.076 | 0.000 | 0.240 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.076 | 0.000 | 0.248 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.076 | 0.000 | 0.248 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.133 | 0.000 | 0.254 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.133 | 0.000 | 0.250 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.133 | 0.000 | 0.254 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.133 | 0.000 | 0.250 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.080 | 0.000 | 0.244 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.080 | 0.000 | 0.244 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.080 | 0.000 | 0.252 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.080 | 0.000 | 0.252 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.140 | 0.000 | 0.258 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.254 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.140 | 0.000 | 0.259 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.254 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.084 | 0.000 | 0.248 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.084 | 0.000 | 0.248 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.084 | 0.000 | 0.257 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.084 | 0.000 | 0.257 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.262 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.145 | 0.000 | 0.257 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.263 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.145 | 0.000 | 0.258 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.088 | 0.000 | 0.252 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.088 | 0.000 | 0.252 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.088 | 0.000 | 0.260 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.088 | 0.000 | 0.260 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.151 | 0.000 | 0.266 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.263 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.151 | 0.000 | 0.267 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.264 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.091 | 0.000 | 0.258 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.258 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.091 | 0.000 | 0.265 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.091 | 0.000 | 0.265 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.503 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 577.48 | 18311.89 | 01-JAN-00:15 | 18311.89 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 808.61 | 18692.42 | 20-JUN-02:45 | 74626.72 | 13-JUN-16:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
ElectricityPurchased:Plant | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
Cogeneration:ElectricityPurchased | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
ElectricityNet:Plant | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
Cogeneration:ElectricityNet | 2571.60 | 56252.91 | 20-JUN-02:45 | 156163.15 | 13-JUN-17:15 |
ExteriorLights:Electricity | 168.19 | 0.00 | 01-JAN-08:15 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.19 | 0.00 | 01-JAN-08:15 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 577.48 | 18311.89 | 01-JAN-00:15 | 18311.89 | 01-JAN-00:15 |
Cooling:Electricity | 134.01 | 0.00 | 01-JAN-00:15 | 55166.52 | 13-JUN-16:15 |
Heating:Electricity | 76.28 | 0.00 | 20-MAR-16:15 | 25268.81 | 30-DEC-04:00 |
Electricity:Plant | 47.30 | 36.93 | 09-MAY-06:30 | 3250.37 | 13-JUN-15:30 |
HeatRejection:Electricity | 5.40 | 0.00 | 01-JAN-00:15 | 1913.32 | 13-JUN-15:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 41.90 | 36.93 | 09-MAY-06:30 | 1337.05 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1450.06 | 9260.51 | 15-JAN-14:45 | 166210.44 | 10-JAN-06:45 |
Gas:Plant | 1450.06 | 9260.51 | 15-JAN-14:45 | 166210.44 | 10-JAN-06:45 |
WaterSystems:Gas | 1221.51 | 9260.51 | 01-JAN-00:15 | 87738.95 | 13-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1221.51 | 9260.51 | 01-JAN-00:15 | 87738.95 | 13-FEB-08:00 |
Heating:Gas | 228.55 | 0.00 | 07-JAN-12:30 | 93628.17 | 30-DEC-02:00 |
Boiler:Heating:Gas | 228.55 | 0.00 | 07-JAN-12:30 | 93628.17 | 30-DEC-02:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 517.27 | 0.00 | 01-JAN-00:15 | 246891.40 | 13-JUN-16:15 |
PlantLoopCoolingDemand:HVAC | 517.27 | 0.00 | 01-JAN-00:15 | 246891.40 | 13-JUN-16:15 |
CoolingCoils:PlantLoopCoolingDemand | 517.27 | 0.00 | 01-JAN-00:15 | 246891.40 | 13-JUN-16:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5149.17 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-18:00 |
Water:Plant | 5149.17 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-18:00 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5149.17 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-18:00 |
MainsWater:Plant | 5149.17 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-18:00 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 370.65 | 0.00 | 01-JAN-00:15 | 0.00 | 22-JUL-18:00 |
HeatRejection:MainsWater | 370.65 | 0.00 | 01-JAN-00:15 | 0.00 | 22-JUL-18:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1142.72 | 541.89 | 16-AUG-01:15 | 129164.69 | 10-JAN-06:15 |
PlantLoopHeatingDemand:Plant | 928.90 | 541.89 | 16-AUG-01:15 | 59297.59 | 13-FEB-07:45 |
WaterSystems:PlantLoopHeatingDemand | 928.90 | 541.89 | 16-AUG-01:15 | 59297.59 | 13-FEB-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2623.16 | 9774.13 | 09-AUG-02:00 | 392606.90 | 13-JUN-17:15 |
EnergyTransfer:Building | 832.33 | 4134.72 | 03-SEP-15:30 | 161870.59 | 14-AUG-16:30 |
EnergyTransfer:Zone:G SW APARTMENT | 8.00 | 0.02 | 06-AUG-11:00 | 2395.49 | 14-AUG-16:30 |
Heating:EnergyTransfer | 107.02 | 0.00 | 16-JAN-17:15 | 60028.11 | 26-DEC-04:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.21 | 0.00 | 01-JAN-09:00 | 871.31 | 24-NOV-12:00 |
Cooling:EnergyTransfer | 725.31 | 0.00 | 05-JAN-04:30 | 161870.59 | 14-AUG-16:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 5.79 | 0.00 | 01-JAN-00:15 | 2395.49 | 14-AUG-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 7.27 | 0.02 | 23-AUG-10:00 | 1804.48 | 21-JUL-17:45 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 3.69 | 0.00 | 15-JAN-13:30 | 980.29 | 10-JAN-09:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 3.57 | 0.00 | 01-JAN-00:15 | 1804.48 | 21-JUL-17:45 |
EnergyTransfer:Zone:OFFICE | 14.61 | 0.11 | 19-MAY-03:00 | 2957.18 | 12-SEP-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 2.47 | 0.00 | 01-JAN-09:00 | 928.44 | 28-DEC-08:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 12.14 | 0.00 | 01-JAN-00:15 | 2957.18 | 12-SEP-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 7.48 | 0.02 | 24-JAN-20:45 | 1253.94 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 3.59 | 0.00 | 06-JAN-10:45 | 951.90 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 3.89 | 0.00 | 01-JAN-00:15 | 1253.94 | 22-JUL-11:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 6.11 | 0.00 | 16-JAN-06:30 | 793.24 | 01-JUL-17:45 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.29 | 0.00 | 01-JAN-20:30 | 780.90 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.82 | 0.00 | 01-JAN-00:15 | 793.24 | 01-JUL-17:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 6.13 | 0.02 | 22-MAY-12:00 | 790.46 | 01-JUL-17:45 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.29 | 0.00 | 01-JAN-20:30 | 781.35 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.84 | 0.00 | 01-JAN-00:15 | 790.46 | 01-JUL-17:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.44 | 0.02 | 12-AUG-18:30 | 1522.59 | 30-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 676.03 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.02 | 0.00 | 03-JAN-01:15 | 1522.59 | 30-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.50 | 0.03 | 07-JUL-10:30 | 1531.06 | 30-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 632.17 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.11 | 0.00 | 03-JAN-01:30 | 1531.06 | 30-SEP-13:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 11.81 | 0.02 | 05-SEP-11:30 | 3110.07 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 1.00 | 0.00 | 01-JAN-00:15 | 817.82 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 10.80 | 0.00 | 03-JAN-01:15 | 3110.07 | 13-JUN-17:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 8.04 | 0.00 | 31-MAY-18:15 | 2423.79 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 2.22 | 0.00 | 01-JAN-20:45 | 960.06 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 5.82 | 0.00 | 01-JAN-00:15 | 2423.79 | 21-JUL-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 12.49 | 0.05 | 06-JAN-07:45 | 2707.18 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.81 | 0.00 | 01-JAN-00:15 | 791.54 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 11.68 | 0.00 | 03-JAN-02:15 | 2707.18 | 22-JUL-11:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 8.19 | 0.00 | 16-AUG-18:30 | 1784.50 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 2.09 | 0.00 | 01-JAN-09:45 | 965.04 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 6.11 | 0.00 | 01-JAN-00:15 | 1784.50 | 22-JUL-11:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 7.68 | 0.07 | 15-AUG-13:15 | 1166.22 | 14-AUG-18:15 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 578.58 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 7.35 | 0.00 | 01-JAN-14:45 | 1166.22 | 14-AUG-18:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 7.69 | 0.05 | 22-SEP-11:30 | 1139.55 | 14-AUG-18:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 584.44 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 7.37 | 0.00 | 01-JAN-14:45 | 1139.55 | 14-AUG-18:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 11.89 | 0.01 | 01-SEP-09:30 | 2098.07 | 30-SEP-13:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 363.23 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 11.77 | 0.00 | 04-JAN-01:15 | 2098.07 | 30-SEP-13:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 11.96 | 0.02 | 04-SEP-13:45 | 2105.13 | 30-SEP-13:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 353.78 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 11.85 | 0.00 | 04-JAN-01:15 | 2105.13 | 30-SEP-13:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 12.98 | 0.02 | 18-OCT-11:15 | 3164.75 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.83 | 0.00 | 01-JAN-00:15 | 810.64 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 12.15 | 0.00 | 03-JAN-11:45 | 3164.75 | 13-JUN-17:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 8.55 | 0.00 | 21-MAY-16:00 | 2470.36 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 1.88 | 0.00 | 01-JAN-20:30 | 973.32 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 6.67 | 0.00 | 01-JAN-00:15 | 2470.36 | 21-JUL-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 13.36 | 0.34 | 25-JUN-20:00 | 2736.56 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.75 | 0.00 | 01-JAN-00:15 | 802.70 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 12.61 | 0.00 | 03-JAN-04:45 | 2736.56 | 22-JUL-11:15 |
EnergyTransfer:Zone:F3 NE APARTMENT | 8.75 | 0.01 | 10-AUG-19:00 | 1839.97 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 1.75 | 0.00 | 01-JAN-09:15 | 976.95 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 7.00 | 0.00 | 01-JAN-00:15 | 1839.97 | 22-JUL-11:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 8.58 | 0.05 | 05-AUG-14:30 | 1227.05 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 538.51 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 8.36 | 0.00 | 01-JAN-15:00 | 1227.05 | 14-AUG-16:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 8.60 | 0.02 | 14-SEP-13:30 | 1202.43 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 543.72 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 8.38 | 0.00 | 01-JAN-15:00 | 1202.43 | 14-AUG-16:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 13.65 | 0.00 | 21-AUG-09:15 | 2157.53 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 264.43 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 13.55 | 0.00 | 04-JAN-02:45 | 2157.53 | 30-APR-14:30 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 13.68 | 0.03 | 16-DEC-03:45 | 2167.20 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 263.31 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 13.58 | 0.00 | 04-JAN-03:00 | 2167.20 | 30-APR-14:30 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 13.15 | 0.05 | 03-FEB-08:15 | 3184.64 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.82 | 0.00 | 01-JAN-00:15 | 843.71 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 12.33 | 0.00 | 03-JAN-12:00 | 3184.64 | 13-JUN-17:15 |
EnergyTransfer:Zone:F4 NW APARTMENT | 8.70 | 0.00 | 10-MAR-00:30 | 2485.45 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 1.85 | 0.00 | 01-JAN-20:30 | 1011.25 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 6.84 | 0.00 | 01-JAN-00:15 | 2485.45 | 21-JUL-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 13.46 | 0.08 | 08-DEC-00:15 | 2754.89 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.77 | 0.00 | 01-JAN-00:15 | 838.02 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 12.69 | 0.00 | 03-JAN-12:00 | 2754.89 | 22-JUL-11:15 |
EnergyTransfer:Zone:F4 NE APARTMENT | 8.93 | 0.01 | 01-FEB-08:00 | 1854.15 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 1.73 | 0.00 | 01-JAN-09:30 | 1014.24 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 7.20 | 0.00 | 01-JAN-00:15 | 1854.15 | 22-JUL-11:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 8.89 | 0.08 | 16-AUG-14:00 | 1245.64 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 541.91 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 8.69 | 0.00 | 01-JAN-15:00 | 1245.64 | 14-AUG-16:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 8.91 | 0.01 | 03-DEC-10:15 | 1219.07 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 548.10 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 8.71 | 0.00 | 01-JAN-15:00 | 1219.07 | 14-AUG-16:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 14.10 | 0.06 | 17-JUN-14:30 | 2192.75 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 298.96 | 12-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 14.00 | 0.00 | 04-JAN-03:45 | 2192.75 | 30-APR-14:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 14.11 | 0.11 | 15-SEP-14:00 | 2201.48 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 291.43 | 12-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 14.01 | 0.00 | 04-JAN-03:45 | 2201.48 | 30-APR-14:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 13.30 | 0.09 | 30-DEC-11:30 | 3218.39 | 13-JUN-17:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.81 | 0.00 | 01-JAN-00:15 | 869.27 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 12.48 | 0.00 | 03-JAN-12:00 | 3218.39 | 13-JUN-17:15 |
EnergyTransfer:Zone:M NW APARTMENT | 8.78 | 0.03 | 29-JAN-10:00 | 2519.83 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.79 | 0.00 | 01-JAN-20:30 | 1033.08 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 6.99 | 0.00 | 01-JAN-00:15 | 2519.83 | 21-JUL-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 13.60 | 0.21 | 08-MAR-02:30 | 2792.83 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.77 | 0.00 | 01-JAN-00:15 | 864.64 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 12.83 | 0.00 | 03-JAN-12:00 | 2792.83 | 22-JUL-11:15 |
EnergyTransfer:Zone:M NE APARTMENT | 9.03 | 0.04 | 05-NOV-06:45 | 1887.40 | 22-JUL-11:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.66 | 0.00 | 01-JAN-09:15 | 1035.64 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 7.38 | 0.00 | 01-JAN-00:15 | 1887.40 | 22-JUL-11:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 9.16 | 0.00 | 09-SEP-15:00 | 1280.18 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 538.25 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 8.97 | 0.00 | 01-JAN-15:15 | 1280.18 | 14-AUG-16:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 9.18 | 0.01 | 09-JUL-14:30 | 1253.57 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 545.05 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 8.99 | 0.00 | 01-JAN-15:15 | 1253.57 | 14-AUG-16:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 14.45 | 0.09 | 15-JUN-13:00 | 2221.13 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 281.03 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 14.35 | 0.00 | 04-JAN-04:15 | 2221.13 | 30-APR-14:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 14.45 | 0.05 | 18-SEP-10:30 | 2229.67 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 280.58 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 14.35 | 0.00 | 05-JAN-04:30 | 2229.67 | 30-APR-14:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 12.62 | 0.07 | 04-JAN-13:15 | 3189.40 | 13-JUN-16:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 945.20 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 11.64 | 0.00 | 03-JAN-11:45 | 3189.40 | 13-JUN-16:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 8.47 | 0.01 | 20-JAN-05:30 | 2480.58 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 2.10 | 0.00 | 01-JAN-20:45 | 1105.66 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 6.37 | 0.00 | 01-JAN-00:15 | 2480.58 | 21-JUL-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 12.91 | 0.09 | 15-FEB-08:15 | 2792.26 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.93 | 0.00 | 01-JAN-00:15 | 940.32 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 11.98 | 0.00 | 03-JAN-11:45 | 2792.26 | 22-JUL-11:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 8.72 | 0.00 | 19-AUG-11:45 | 1852.58 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 1.96 | 0.00 | 01-JAN-10:00 | 1108.00 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 6.76 | 0.00 | 01-JAN-00:15 | 1852.58 | 22-JUL-11:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 8.66 | 0.02 | 11-SEP-13:45 | 1241.40 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 625.15 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 8.40 | 0.00 | 01-JAN-14:45 | 1241.40 | 14-AUG-16:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 8.69 | 0.03 | 07-AUG-15:15 | 1214.84 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 631.81 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 8.42 | 0.00 | 01-JAN-14:45 | 1214.84 | 14-AUG-16:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 13.66 | 0.05 | 28-APR-17:45 | 2172.85 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 327.98 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 13.54 | 0.00 | 04-JAN-03:15 | 2172.85 | 30-APR-14:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 13.67 | 0.04 | 15-JUL-13:30 | 2181.69 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 327.57 | 03-DEC-04:45 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 13.54 | 0.00 | 04-JAN-03:15 | 2181.69 | 30-APR-14:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 12.16 | 0.07 | 11-SEP-09:45 | 3175.65 | 13-JUN-16:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 1.10 | 0.00 | 01-JAN-00:15 | 1003.33 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 11.05 | 0.00 | 03-JAN-04:00 | 3175.65 | 13-JUN-16:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 8.28 | 0.03 | 19-NOV-12:15 | 2465.93 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 2.33 | 0.00 | 01-JAN-20:45 | 1157.78 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 5.96 | 0.00 | 01-JAN-00:15 | 2465.93 | 21-JUL-17:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 12.45 | 0.01 | 15-FEB-15:30 | 2783.19 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 1.06 | 0.00 | 01-JAN-00:15 | 998.37 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 11.39 | 0.00 | 03-JAN-03:45 | 2783.19 | 22-JUL-11:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 8.54 | 0.02 | 06-OCT-14:45 | 1838.55 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 2.18 | 0.00 | 01-JAN-20:45 | 1159.89 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 6.36 | 0.00 | 01-JAN-00:15 | 1838.55 | 22-JUL-11:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 8.33 | 0.01 | 16-JUL-13:45 | 1227.94 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 717.54 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 8.01 | 0.00 | 01-JAN-13:00 | 1227.94 | 14-AUG-16:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 8.35 | 0.02 | 29-NOV-16:15 | 1201.42 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 724.39 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 8.03 | 0.00 | 01-JAN-13:00 | 1201.42 | 14-AUG-16:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 13.12 | 0.00 | 23-JUL-08:30 | 2146.49 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 367.89 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 12.98 | 0.00 | 04-JAN-02:15 | 2146.49 | 30-APR-14:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 13.12 | 0.03 | 11-JUN-11:30 | 2155.53 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.15 | 0.00 | 01-JAN-00:15 | 373.30 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 12.98 | 0.00 | 04-JAN-02:15 | 2155.53 | 30-APR-14:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 11.74 | 0.10 | 28-APR-10:45 | 3171.69 | 13-JUN-16:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 1.25 | 0.00 | 01-JAN-00:15 | 1063.47 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 10.49 | 0.00 | 03-JAN-02:45 | 3171.69 | 13-JUN-16:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 8.15 | 0.08 | 28-JAN-07:30 | 2463.69 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 2.56 | 0.00 | 01-JAN-20:45 | 1206.73 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 5.59 | 0.00 | 01-JAN-00:15 | 2463.69 | 21-JUL-17:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 12.04 | 0.01 | 01-JUN-12:30 | 2782.92 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 1.20 | 0.00 | 01-JAN-00:15 | 1058.12 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 10.84 | 0.00 | 03-JAN-02:30 | 2782.92 | 22-JUL-11:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 8.41 | 0.01 | 28-SEP-14:00 | 1836.34 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 2.41 | 0.00 | 01-JAN-20:45 | 1208.73 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 6.00 | 0.00 | 01-JAN-00:15 | 1836.34 | 22-JUL-11:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 8.03 | 0.04 | 27-SEP-11:15 | 1227.64 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 881.90 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 7.64 | 0.00 | 01-JAN-12:30 | 1227.64 | 14-AUG-16:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 8.06 | 0.06 | 29-NOV-16:45 | 1201.24 | 14-AUG-16:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 889.40 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 7.66 | 0.00 | 01-JAN-12:30 | 1201.24 | 14-AUG-16:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 12.59 | 0.01 | 11-JUN-10:15 | 2124.18 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 483.64 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 12.42 | 0.00 | 04-JAN-01:15 | 2124.18 | 30-APR-14:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 12.59 | 0.03 | 05-SEP-11:15 | 2133.55 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 488.25 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 12.42 | 0.00 | 04-JAN-01:15 | 2133.55 | 30-APR-14:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 11.22 | 0.10 | 30-JAN-23:45 | 3240.66 | 13-JUN-16:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 1.66 | 0.00 | 01-JAN-00:15 | 1198.66 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 9.56 | 0.00 | 01-JAN-05:45 | 3240.66 | 13-JUN-16:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 8.30 | 0.01 | 18-JAN-02:15 | 2541.02 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 3.25 | 0.00 | 01-JAN-21:00 | 1310.25 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 5.05 | 0.00 | 01-JAN-00:15 | 2541.02 | 21-JUL-17:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 11.49 | 0.02 | 01-FEB-15:00 | 2802.92 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 1.61 | 0.00 | 01-JAN-00:15 | 1193.02 | 28-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 9.89 | 0.00 | 01-JAN-05:45 | 2802.92 | 22-JUL-11:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 8.53 | 0.02 | 15-JUL-18:15 | 1848.37 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 3.07 | 0.00 | 01-JAN-21:00 | 1312.62 | 26-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 5.46 | 0.00 | 01-JAN-00:15 | 1848.37 | 22-JUL-11:30 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 7.54 | 0.00 | 15-AUG-14:15 | 1284.85 | 14-AUG-16:30 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.66 | 0.00 | 01-JAN-00:15 | 1103.29 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.88 | 0.00 | 01-JAN-00:30 | 1284.85 | 14-AUG-16:30 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 7.55 | 0.03 | 30-APR-10:30 | 1258.40 | 14-AUG-16:30 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.65 | 0.00 | 01-JAN-00:45 | 1109.21 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.90 | 0.00 | 01-JAN-00:15 | 1258.40 | 14-AUG-16:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 11.65 | 0.05 | 03-AUG-10:45 | 2112.81 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.26 | 0.00 | 01-JAN-00:15 | 645.90 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 11.39 | 0.00 | 04-JAN-00:15 | 2112.81 | 30-APR-14:30 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 11.66 | 0.01 | 08-DEC-08:15 | 2124.38 | 30-APR-14:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 649.05 | 24-NOV-12:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 11.39 | 0.00 | 04-JAN-00:15 | 2124.38 | 30-APR-14:30 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 13.25 | 0.02 | 08-SEP-02:30 | 3842.56 | 13-JUN-16:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.93 | 0.00 | 01-JAN-09:30 | 1674.06 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 8.32 | 0.00 | 01-JAN-00:15 | 3842.56 | 13-JUN-16:30 |
EnergyTransfer:Zone:T NW APARTMENT | 11.25 | 0.02 | 10-AUG-03:00 | 3220.04 | 21-JUL-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 6.94 | 0.00 | 02-JAN-15:45 | 1774.10 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 4.31 | 0.00 | 01-JAN-00:15 | 3220.04 | 21-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 13.24 | 0.00 | 15-SEP-04:15 | 3416.00 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 4.80 | 0.00 | 01-JAN-09:00 | 1690.42 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 8.44 | 0.00 | 01-JAN-00:15 | 3416.00 | 22-JUL-11:30 |
EnergyTransfer:Zone:T NE APARTMENT | 11.27 | 0.00 | 16-AUG-10:00 | 2378.05 | 22-JUL-11:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 6.73 | 0.00 | 05-JAN-10:30 | 1784.78 | 30-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 4.54 | 0.00 | 01-JAN-00:15 | 2378.05 | 22-JUL-11:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 8.10 | 0.02 | 17-AUG-11:15 | 1776.87 | 14-AUG-16:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.07 | 0.00 | 01-JAN-21:00 | 1555.97 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 5.04 | 0.00 | 01-JAN-00:15 | 1776.87 | 14-AUG-16:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 8.09 | 0.00 | 26-JUN-11:00 | 1776.17 | 14-AUG-16:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.07 | 0.00 | 01-JAN-21:00 | 1563.69 | 29-SEP-15:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 5.02 | 0.00 | 01-JAN-00:15 | 1776.17 | 14-AUG-16:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 10.56 | 0.01 | 24-AUG-01:45 | 2819.31 | 21-JUL-13:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.77 | 0.00 | 01-JAN-08:30 | 1016.93 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 8.80 | 0.00 | 01-JAN-00:15 | 2819.31 | 21-JUL-13:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 10.58 | 0.02 | 29-JAN-09:15 | 2825.22 | 21-JUL-13:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.77 | 0.00 | 01-JAN-08:30 | 1018.39 | 30-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 8.81 | 0.00 | 01-JAN-00:15 | 2825.22 | 21-JUL-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1111.58 | 541.89 | 16-AUG-01:15 | 129481.60 | 10-JAN-06:15 |
WaterSystems:EnergyTransfer | 928.89 | 541.89 | 16-AUG-01:15 | 59291.53 | 13-FEB-07:45 |
sub cat:WaterSystems:EnergyTransfer | 928.89 | 541.89 | 16-AUG-01:15 | 59291.53 | 13-FEB-07:45 |
EnergyTransfer:HVAC | 679.25 | 0.00 | 09-MAY-06:30 | 192506.43 | 13-JUN-16:15 |
CoolingCoils:EnergyTransfer | 401.24 | 0.00 | 01-JAN-00:15 | 192506.43 | 13-JUN-16:15 |
HeatingCoils:EnergyTransfer | 278.01 | 0.00 | 20-MAR-16:15 | 99379.70 | 30-DEC-04:00 |
PlantLoopHeatingDemand:HVAC | 213.82 | 0.00 | 20-MAR-16:15 | 76445.69 | 10-JAN-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 213.82 | 0.00 | 20-MAR-16:15 | 76445.69 | 10-JAN-06:00 |
Boilers:EnergyTransfer | 182.69 | 0.00 | 07-JAN-12:30 | 74902.54 | 30-DEC-02:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 2.209 | -5.788 | 0.000 | 0.000 | 3.868 | 2.413 | 12.213 | 16.544 | 0.000 | 0.007 | 0.000 | 0.000 | -11.567 | 0.000 | -5.472 | -14.427 |
G NW APARTMENT | 3.693 | -3.574 | 0.000 | 0.000 | 3.924 | 2.413 | 12.213 | 8.025 | 0.000 | 0.007 | 0.000 | 0.000 | -11.534 | 0.000 | -4.953 | -10.213 |
OFFICE | 2.472 | -12.142 | 0.000 | 0.000 | 0.526 | 21.954 | 7.547 | 16.536 | 0.000 | 0.001 | 0.000 | 0.000 | -11.480 | 0.000 | -2.029 | -23.385 |
G NE APARTMENT | 3.589 | -3.892 | 0.000 | 0.000 | 3.942 | 2.413 | 12.213 | 8.002 | 0.000 | 0.006 | 0.000 | 0.000 | -11.247 | 0.000 | -4.942 | -10.083 |
G N1 APARTMENT | 1.289 | -4.817 | 0.000 | 0.000 | 3.951 | 2.413 | 12.213 | 2.666 | 0.000 | 0.006 | 0.000 | 0.000 | -7.074 | 0.000 | -3.796 | -6.850 |
G N2 APARTMENT | 1.293 | -4.842 | 0.000 | 0.000 | 3.953 | 2.413 | 12.213 | 2.665 | 0.000 | 0.006 | 0.000 | 0.000 | -7.071 | 0.000 | -3.796 | -6.832 |
G S1 APARTMENT | 0.419 | -7.017 | 0.000 | 0.000 | 3.860 | 2.413 | 12.213 | 11.314 | 0.000 | 0.006 | 0.000 | 0.000 | -7.126 | 0.000 | -4.504 | -11.578 |
G S2 APARTMENT | 0.389 | -7.111 | 0.000 | 0.000 | 3.856 | 2.413 | 12.213 | 11.300 | 0.000 | 0.006 | 0.000 | 0.000 | -7.137 | 0.000 | -4.535 | -11.394 |
F2 SW APARTMENT | 1.003 | -10.804 | 0.000 | 0.000 | 3.761 | 2.413 | 12.213 | 15.962 | 0.000 | 0.008 | 0.001 | 0.000 | -12.412 | 0.000 | -6.918 | -5.224 |
F2 NW APARTMENT | 2.219 | -5.817 | 0.000 | 0.000 | 3.847 | 2.413 | 12.213 | 7.547 | 0.000 | 0.008 | 0.000 | 0.000 | -12.208 | 0.000 | -6.461 | -3.761 |
F2 SE APARTMENT | 0.812 | -11.676 | 0.000 | 0.000 | 3.753 | 2.413 | 12.213 | 15.981 | 0.000 | 0.008 | 0.002 | 0.000 | -12.290 | 0.000 | -6.996 | -4.218 |
F2 NE APARTMENT | 2.087 | -6.108 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 7.533 | 0.000 | 0.008 | 0.000 | 0.000 | -11.892 | 0.000 | -6.484 | -3.633 |
F2 N1 APARTMENT | 0.328 | -7.353 | 0.000 | 0.000 | 3.865 | 2.413 | 12.213 | 2.387 | 0.000 | 0.007 | 0.000 | 0.000 | -7.550 | 0.000 | -4.951 | -1.360 |
F2 N2 APARTMENT | 0.322 | -7.367 | 0.000 | 0.000 | 3.867 | 2.413 | 12.213 | 2.386 | 0.000 | 0.007 | 0.000 | 0.000 | -7.546 | 0.000 | -4.951 | -1.344 |
F2 S1 APARTMENT | 0.117 | -11.772 | 0.000 | 0.000 | 3.727 | 2.413 | 12.213 | 10.953 | 0.000 | 0.007 | 0.000 | 0.000 | -7.691 | 0.000 | -5.655 | -4.313 |
F2 S2 APARTMENT | 0.116 | -11.845 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 10.948 | 0.000 | 0.007 | 0.000 | 0.000 | -7.698 | 0.000 | -5.663 | -4.216 |
F3 SW APARTMENT | 0.828 | -12.154 | 0.000 | 0.000 | 3.733 | 2.413 | 12.213 | 15.740 | 0.000 | 0.009 | 0.000 | 0.000 | -12.692 | 0.000 | -7.653 | -2.438 |
F3 NW APARTMENT | 1.879 | -6.674 | 0.000 | 0.000 | 3.826 | 2.413 | 12.213 | 7.365 | 0.000 | 0.009 | 0.000 | 0.000 | -12.446 | 0.000 | -7.210 | -1.374 |
F3 SE APARTMENT | 0.755 | -12.605 | 0.000 | 0.000 | 3.738 | 2.413 | 12.213 | 15.801 | 0.000 | 0.009 | 0.000 | 0.000 | -12.488 | 0.000 | -7.689 | -2.146 |
F3 NE APARTMENT | 1.753 | -7.002 | 0.000 | 0.000 | 3.842 | 2.413 | 12.213 | 7.361 | 0.000 | 0.009 | 0.000 | 0.000 | -12.119 | 0.000 | -7.230 | -1.238 |
F3 N1 APARTMENT | 0.220 | -8.363 | 0.000 | 0.000 | 3.833 | 2.413 | 12.213 | 2.284 | 0.000 | 0.007 | 0.631 | 0.000 | -7.725 | 0.000 | -5.513 | -0.000 |
F3 N2 APARTMENT | 0.220 | -8.379 | 0.000 | 0.000 | 3.835 | 2.413 | 12.213 | 2.283 | 0.000 | 0.007 | 0.642 | 0.000 | -7.721 | 0.000 | -5.513 | -0.000 |
F3 S1 APARTMENT | 0.094 | -13.554 | 0.000 | 0.000 | 3.688 | 2.413 | 12.213 | 10.811 | 0.000 | 0.008 | 0.000 | 0.000 | -7.898 | 0.000 | -6.180 | -1.595 |
F3 S2 APARTMENT | 0.096 | -13.584 | 0.000 | 0.000 | 3.687 | 2.413 | 12.213 | 10.809 | 0.000 | 0.008 | 0.000 | 0.000 | -7.899 | 0.000 | -6.184 | -1.558 |
F4 SW APARTMENT | 0.824 | -12.331 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 15.615 | 0.000 | 0.009 | 0.001 | 0.000 | -12.823 | 0.000 | -8.191 | -1.453 |
F4 NW APARTMENT | 1.855 | -6.843 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 7.268 | 0.000 | 0.009 | 0.000 | 0.000 | -12.564 | 0.000 | -7.735 | -0.436 |
F4 SE APARTMENT | 0.773 | -12.688 | 0.000 | 0.000 | 3.733 | 2.413 | 12.213 | 15.689 | 0.000 | 0.009 | 0.001 | 0.000 | -12.595 | 0.000 | -8.221 | -1.325 |
F4 NE APARTMENT | 1.729 | -7.204 | 0.000 | 0.000 | 3.836 | 2.413 | 12.213 | 7.271 | 0.000 | 0.009 | 0.000 | 0.000 | -12.230 | 0.000 | -7.751 | -0.286 |
F4 N1 APARTMENT | 0.204 | -8.689 | 0.000 | 0.000 | 3.822 | 2.413 | 12.213 | 2.231 | 0.000 | 0.008 | 1.496 | 0.000 | -7.815 | 0.000 | -5.883 | -0.000 |
F4 N2 APARTMENT | 0.204 | -8.706 | 0.000 | 0.000 | 3.824 | 2.413 | 12.213 | 2.231 | 0.000 | 0.008 | 1.508 | 0.000 | -7.810 | 0.000 | -5.883 | -0.000 |
F4 S1 APARTMENT | 0.097 | -14.003 | 0.000 | 0.000 | 3.675 | 2.413 | 12.213 | 10.733 | 0.000 | 0.008 | 0.001 | 0.000 | -7.993 | 0.000 | -6.551 | -0.592 |
F4 S2 APARTMENT | 0.098 | -14.011 | 0.000 | 0.000 | 3.675 | 2.413 | 12.213 | 10.731 | 0.000 | 0.008 | 0.000 | 0.000 | -7.992 | 0.000 | -6.554 | -0.580 |
M SW APARTMENT | 0.813 | -12.485 | 0.000 | 0.000 | 3.720 | 2.413 | 12.213 | 15.516 | 0.000 | 0.010 | 0.001 | 0.000 | -12.924 | 0.000 | -8.648 | -0.628 |
M NW APARTMENT | 1.791 | -6.992 | 0.000 | 0.000 | 3.816 | 2.413 | 12.213 | 7.193 | 0.000 | 0.010 | 0.397 | 0.000 | -12.661 | 0.000 | -8.179 | -0.000 |
M SE APARTMENT | 0.767 | -12.832 | 0.000 | 0.000 | 3.728 | 2.413 | 12.213 | 15.596 | 0.000 | 0.010 | 0.001 | 0.000 | -12.687 | 0.000 | -8.675 | -0.533 |
M NE APARTMENT | 1.658 | -7.375 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 7.202 | 0.000 | 0.009 | 0.560 | 0.000 | -12.322 | 0.000 | -8.191 | -0.000 |
M N1 APARTMENT | 0.189 | -8.974 | 0.000 | 0.000 | 3.814 | 2.413 | 12.213 | 2.193 | 0.000 | 0.008 | 2.226 | 0.000 | -7.884 | 0.000 | -6.197 | -0.000 |
M N2 APARTMENT | 0.190 | -8.995 | 0.000 | 0.000 | 3.816 | 2.413 | 12.213 | 2.192 | 0.000 | 0.008 | 2.239 | 0.000 | -7.879 | 0.000 | -6.197 | -0.000 |
M S1 APARTMENT | 0.102 | -14.348 | 0.000 | 0.000 | 3.667 | 2.413 | 12.213 | 10.672 | 0.000 | 0.009 | 0.204 | 0.000 | -8.062 | 0.000 | -6.869 | -0.000 |
M S2 APARTMENT | 0.103 | -14.351 | 0.000 | 0.000 | 3.667 | 2.413 | 12.213 | 10.670 | 0.000 | 0.009 | 0.209 | 0.000 | -8.061 | 0.000 | -6.872 | -0.000 |
F6 SW APARTMENT | 0.973 | -11.642 | 0.000 | 0.000 | 3.731 | 2.413 | 12.213 | 15.476 | 0.000 | 0.011 | 0.001 | 0.000 | -12.907 | 0.000 | -9.000 | -1.269 |
F6 NW APARTMENT | 2.102 | -6.373 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 7.177 | 0.000 | 0.011 | 0.000 | 0.000 | -12.645 | 0.000 | -8.481 | -0.245 |
F6 SE APARTMENT | 0.926 | -11.982 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 15.562 | 0.000 | 0.011 | 0.001 | 0.000 | -12.667 | 0.000 | -9.029 | -1.188 |
F6 NE APARTMENT | 1.963 | -6.761 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 7.192 | 0.000 | 0.011 | 0.000 | 0.000 | -12.304 | 0.000 | -8.486 | -0.086 |
F6 N1 APARTMENT | 0.266 | -8.399 | 0.000 | 0.000 | 3.828 | 2.413 | 12.213 | 2.191 | 0.000 | 0.010 | 1.717 | 0.000 | -7.870 | 0.000 | -6.367 | -0.000 |
F6 N2 APARTMENT | 0.267 | -8.419 | 0.000 | 0.000 | 3.829 | 2.413 | 12.213 | 2.190 | 0.000 | 0.009 | 1.729 | 0.000 | -7.865 | 0.000 | -6.367 | -0.000 |
F6 S1 APARTMENT | 0.122 | -13.540 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 10.648 | 0.000 | 0.010 | 0.000 | 0.000 | -8.053 | 0.000 | -7.097 | -0.395 |
F6 S2 APARTMENT | 0.124 | -13.541 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 10.646 | 0.000 | 0.010 | 0.000 | 0.000 | -8.051 | 0.000 | -7.101 | -0.392 |
F7 SW APARTMENT | 1.104 | -11.052 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 15.438 | 0.000 | 0.012 | 0.001 | 0.000 | -12.899 | 0.000 | -9.320 | -1.648 |
F7 NW APARTMENT | 2.326 | -5.955 | 0.000 | 0.000 | 3.836 | 2.413 | 12.213 | 7.160 | 0.000 | 0.012 | 0.000 | 0.000 | -12.641 | 0.000 | -8.760 | -0.602 |
F7 SE APARTMENT | 1.056 | -11.395 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 15.527 | 0.000 | 0.012 | 0.001 | 0.000 | -12.657 | 0.000 | -9.351 | -1.568 |
F7 NE APARTMENT | 2.181 | -6.357 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 7.180 | 0.000 | 0.011 | 0.000 | 0.000 | -12.298 | 0.000 | -8.760 | -0.436 |
F7 N1 APARTMENT | 0.324 | -8.011 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 2.188 | 0.000 | 0.010 | 1.419 | 0.000 | -7.862 | 0.000 | -6.532 | -0.000 |
F7 N2 APARTMENT | 0.323 | -8.027 | 0.000 | 0.000 | 3.840 | 2.413 | 12.213 | 2.188 | 0.000 | 0.010 | 1.430 | 0.000 | -7.857 | 0.000 | -6.531 | -0.000 |
F7 S1 APARTMENT | 0.144 | -12.976 | 0.000 | 0.000 | 3.689 | 2.413 | 12.213 | 10.625 | 0.000 | 0.011 | 0.001 | 0.000 | -8.046 | 0.000 | -7.310 | -0.761 |
F7 S2 APARTMENT | 0.147 | -12.977 | 0.000 | 0.000 | 3.689 | 2.413 | 12.213 | 10.623 | 0.000 | 0.011 | 0.000 | 0.000 | -8.045 | 0.000 | -7.314 | -0.759 |
F8 SW APARTMENT | 1.252 | -10.490 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 15.409 | 0.000 | 0.012 | 0.000 | 0.000 | -12.884 | 0.000 | -9.612 | -2.063 |
F8 NW APARTMENT | 2.563 | -5.585 | 0.000 | 0.000 | 3.845 | 2.413 | 12.213 | 7.148 | 0.000 | 0.012 | 0.000 | 0.000 | -12.635 | 0.000 | -9.016 | -0.957 |
F8 SE APARTMENT | 1.202 | -10.840 | 0.000 | 0.000 | 3.759 | 2.413 | 12.213 | 15.500 | 0.000 | 0.012 | 0.000 | 0.000 | -12.640 | 0.000 | -9.643 | -1.977 |
F8 NE APARTMENT | 2.412 | -5.997 | 0.000 | 0.000 | 3.862 | 2.413 | 12.213 | 7.171 | 0.000 | 0.012 | 0.000 | 0.000 | -12.291 | 0.000 | -9.010 | -0.786 |
F8 N1 APARTMENT | 0.396 | -7.639 | 0.000 | 0.000 | 3.849 | 2.413 | 12.213 | 2.187 | 0.000 | 0.010 | 1.109 | 0.000 | -7.852 | 0.000 | -6.687 | -0.000 |
F8 N2 APARTMENT | 0.397 | -7.659 | 0.000 | 0.000 | 3.851 | 2.413 | 12.213 | 2.187 | 0.000 | 0.010 | 1.121 | 0.000 | -7.847 | 0.000 | -6.685 | -0.000 |
F8 S1 APARTMENT | 0.171 | -12.416 | 0.000 | 0.000 | 3.701 | 2.413 | 12.213 | 10.608 | 0.000 | 0.011 | 0.000 | 0.000 | -8.032 | 0.000 | -7.506 | -1.161 |
F8 S2 APARTMENT | 0.172 | -12.418 | 0.000 | 0.000 | 3.701 | 2.413 | 12.213 | 10.606 | 0.000 | 0.011 | 0.000 | 0.000 | -8.030 | 0.000 | -7.510 | -1.158 |
F9 SW APARTMENT | 1.663 | -9.558 | 0.000 | 0.000 | 3.766 | 2.413 | 12.213 | 15.417 | 0.000 | 0.012 | 0.001 | 0.000 | -12.812 | 0.000 | -9.854 | -3.261 |
F9 NW APARTMENT | 3.253 | -5.049 | 0.000 | 0.000 | 3.855 | 2.413 | 12.213 | 7.163 | 0.000 | 0.012 | 0.000 | 0.000 | -12.591 | 0.000 | -9.222 | -2.047 |
F9 SE APARTMENT | 1.605 | -9.888 | 0.000 | 0.000 | 3.776 | 2.413 | 12.213 | 15.510 | 0.000 | 0.012 | 0.001 | 0.000 | -12.570 | 0.000 | -9.893 | -3.178 |
F9 NE APARTMENT | 3.070 | -5.461 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 7.191 | 0.000 | 0.012 | 0.000 | 0.000 | -12.248 | 0.000 | -9.215 | -1.849 |
F9 N1 APARTMENT | 0.657 | -6.882 | 0.000 | 0.000 | 3.862 | 2.413 | 12.213 | 2.201 | 0.000 | 0.010 | 0.152 | 0.000 | -7.815 | 0.000 | -6.811 | -0.000 |
F9 N2 APARTMENT | 0.654 | -6.898 | 0.000 | 0.000 | 3.863 | 2.413 | 12.213 | 2.200 | 0.000 | 0.010 | 0.165 | 0.000 | -7.810 | 0.000 | -6.811 | -0.000 |
F9 S1 APARTMENT | 0.265 | -11.389 | 0.000 | 0.000 | 3.723 | 2.413 | 12.213 | 10.615 | 0.000 | 0.011 | 0.002 | 0.000 | -7.974 | 0.000 | -7.666 | -2.211 |
F9 S2 APARTMENT | 0.267 | -11.394 | 0.000 | 0.000 | 3.723 | 2.413 | 12.213 | 10.614 | 0.000 | 0.011 | 0.002 | 0.000 | -7.972 | 0.000 | -7.670 | -2.204 |
T SW APARTMENT | 4.928 | -8.319 | 0.000 | 0.000 | 3.834 | 2.413 | 12.213 | 15.243 | 0.000 | 0.012 | 0.000 | 0.000 | -12.172 | 0.000 | -10.064 | -8.088 |
T NW APARTMENT | 6.940 | -4.313 | 0.000 | 0.000 | 3.904 | 2.413 | 12.213 | 7.018 | 0.000 | 0.012 | 0.000 | 0.000 | -12.056 | 0.000 | -9.523 | -6.607 |
T SE APARTMENT | 4.798 | -8.437 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 15.370 | 0.000 | 0.012 | 0.000 | 0.000 | -11.970 | 0.000 | -10.099 | -8.143 |
T NE APARTMENT | 6.731 | -4.543 | 0.000 | 0.000 | 3.923 | 2.413 | 12.213 | 7.082 | 0.000 | 0.012 | 0.000 | 0.000 | -11.753 | 0.000 | -9.542 | -6.537 |
T N1 APARTMENT | 3.066 | -5.036 | 0.000 | 0.000 | 3.912 | 2.413 | 12.213 | 2.162 | 0.000 | 0.010 | 0.000 | 0.000 | -7.465 | 0.000 | -7.082 | -4.194 |
T N2 APARTMENT | 3.074 | -5.020 | 0.000 | 0.000 | 3.913 | 2.413 | 12.213 | 2.158 | 0.000 | 0.010 | 0.000 | 0.000 | -7.459 | 0.000 | -7.090 | -4.211 |
T S1 APARTMENT | 1.766 | -8.797 | 0.000 | 0.000 | 3.798 | 2.413 | 12.213 | 10.534 | 0.000 | 0.011 | 0.000 | 0.000 | -7.600 | 0.000 | -7.852 | -6.485 |
T S2 APARTMENT | 1.770 | -8.808 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 10.530 | 0.000 | 0.011 | 0.000 | 0.000 | -7.597 | 0.000 | -7.857 | -6.474 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 3.669 | 0.000 | 0.018 | 27.855 | 0.000 | -2.658 | 0.000 | -47.414 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.618 | 0.000 | 0.000 | 0.000 | 0.000 | -1.585 | 0.000 | -0.557 | -18.006 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.574 | 0.000 | 0.000 | 0.000 | 0.000 | -1.649 | 0.000 | -0.681 | -17.773 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.551 | 0.000 | 0.000 | 0.000 | 0.000 | -1.681 | 0.000 | -0.771 | -17.629 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.524 | 0.000 | 0.000 | 0.000 | 0.000 | -1.724 | 0.000 | -0.876 | -35.983 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.535 | 0.000 | 0.000 | 0.000 | 0.000 | -1.693 | 0.000 | -0.895 | -17.477 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.536 | 0.000 | 0.000 | 0.000 | 0.000 | -1.681 | 0.000 | -0.937 | -17.447 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.535 | 0.000 | 0.000 | 0.000 | 0.000 | -1.676 | 0.000 | -0.978 | -17.411 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.539 | 0.000 | 0.000 | 0.000 | 0.000 | -1.665 | 0.000 | -1.011 | -17.392 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.505 | 0.000 | 0.000 | 0.000 | 0.000 | -1.608 | 0.000 | -1.070 | -25.293 |
Total Facility | 107.016 | -725.308 | 0.000 | 0.000 | 300.718 | 416.414 | 980.287 | 737.629 | 0.000 | 0.771 | 46.829 | 0.000 | -823.176 | 0.000 | -634.794 | -406.370 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 14-AUG-16:30 | 0.00 | -2394.77 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2737.59 | 0.00 | 211.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1371.76 |
G NW APARTMENT | 21-JUL-17:38 | 0.00 | -1807.29 | 0.00 | 0.00 | 139.86 | 194.45 | 588.62 | 2326.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.72 | -1393.47 |
OFFICE | 12-SEP-12:30 | 0.00 | -2957.35 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3477.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24.02 | -2729.01 |
G NE APARTMENT | 22-JUL-11:15 | 0.00 | -1253.77 | 0.00 | 0.00 | 39.90 | 28.81 | 406.15 | 1467.54 | 0.00 | 220.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -908.83 |
G N1 APARTMENT | 01-JUL-17:45 | 0.00 | -793.50 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 337.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.42 | -404.17 |
G N2 APARTMENT | 01-JUL-17:45 | 0.00 | -790.72 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 337.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.42 | -406.79 |
G S1 APARTMENT | 17-SEP-13:25 | 0.00 | -1713.50 | 0.00 | 0.00 | 42.11 | 28.81 | 382.60 | 2649.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.70 | -1361.40 |
G S2 APARTMENT | 28-SEP-15:25 | 0.00 | -1785.45 | 0.00 | 0.00 | 50.67 | 100.83 | 470.89 | 1549.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47.39 | -338.82 |
F2 SW APARTMENT | 13-JUN-17:15 | 0.00 | -3109.94 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2705.08 | 0.00 | 196.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -716.23 |
F2 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2426.55 | 0.00 | 0.00 | 141.27 | 194.45 | 588.62 | 2507.97 | 0.00 | 75.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.60 |
F2 SE APARTMENT | 22-JUL-11:15 | 0.00 | -2706.89 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2827.22 | 0.00 | 302.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -898.42 |
F2 NE APARTMENT | 22-JUL-11:15 | 0.00 | -1784.28 | 0.00 | 0.00 | 40.03 | 28.81 | 406.15 | 1436.60 | 0.00 | 274.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.43 |
F2 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1388.13 | 0.00 | 0.00 | 152.15 | 194.45 | 588.62 | 283.61 | 0.00 | 0.00 | 243.89 | 0.00 | 0.00 | 0.00 | -74.59 | 0.00 |
F2 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1363.93 | 0.00 | 0.00 | 152.08 | 194.45 | 588.62 | 283.32 | 0.00 | 0.00 | 220.13 | 0.00 | 0.00 | 0.00 | -74.66 | 0.00 |
F2 S1 APARTMENT | 29-SEP-15:10 | 0.00 | -2232.80 | 0.00 | 0.00 | 50.97 | 100.83 | 470.89 | 1583.80 | 0.00 | 0.00 | 186.87 | 0.00 | 0.00 | 0.00 | -160.56 | 0.00 |
F2 S2 APARTMENT | 29-SEP-15:10 | 0.00 | -2227.45 | 0.00 | 0.00 | 50.94 | 100.83 | 470.89 | 1583.59 | 0.00 | 0.00 | 181.76 | 0.00 | 0.00 | 0.00 | -160.56 | 0.00 |
F3 SW APARTMENT | 13-JUN-17:15 | 0.00 | -3164.60 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2694.16 | 0.00 | 210.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -664.98 |
F3 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2473.35 | 0.00 | 0.00 | 141.06 | 194.45 | 588.62 | 2496.95 | 0.00 | 77.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1024.80 |
F3 SE APARTMENT | 22-JUL-11:15 | 0.00 | -2736.26 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2808.19 | 0.00 | 331.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -879.45 |
F3 NE APARTMENT | 22-JUL-11:15 | 0.00 | -1839.74 | 0.00 | 0.00 | 39.98 | 28.81 | 406.15 | 1423.82 | 0.00 | 300.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.37 |
F3 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1368.77 | 0.00 | 0.00 | 151.58 | 194.45 | 588.62 | 273.09 | 0.00 | 0.00 | 249.51 | 0.00 | 0.00 | 0.00 | -88.49 | 0.00 |
F3 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1370.11 | 0.00 | 0.00 | 151.55 | 194.45 | 588.62 | 272.89 | 0.00 | 0.00 | 251.10 | 0.00 | 0.00 | 0.00 | -88.49 | 0.00 |
F3 S1 APARTMENT | 29-SEP-15:10 | 0.00 | -2357.28 | 0.00 | 0.00 | 51.59 | 100.83 | 470.89 | 1562.66 | 0.00 | 0.00 | 361.73 | 0.00 | 0.00 | 0.00 | -190.41 | 0.00 |
F3 S2 APARTMENT | 29-SEP-15:10 | 0.00 | -2349.33 | 0.00 | 0.00 | 51.59 | 100.83 | 470.89 | 1562.68 | 0.00 | 0.00 | 353.75 | 0.00 | 0.00 | 0.00 | -190.41 | 0.00 |
F4 SW APARTMENT | 13-JUN-17:15 | 0.00 | -3184.48 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2686.60 | 0.00 | 221.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -648.26 |
F4 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2488.36 | 0.00 | 0.00 | 141.01 | 194.45 | 588.62 | 2489.35 | 0.00 | 78.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1003.82 |
F4 SE APARTMENT | 22-JUL-11:15 | 0.00 | -2754.59 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2794.52 | 0.00 | 354.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -869.65 |
F4 NE APARTMENT | 22-JUL-11:15 | 0.00 | -1853.92 | 0.00 | 0.00 | 39.94 | 28.81 | 406.15 | 1415.15 | 0.00 | 319.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -355.21 |
F4 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1392.15 | 0.00 | 0.00 | 151.82 | 194.45 | 588.62 | 267.29 | 0.00 | 0.00 | 289.07 | 0.00 | 0.00 | 0.00 | -99.11 | 0.00 |
F4 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1393.88 | 0.00 | 0.00 | 151.79 | 194.45 | 588.62 | 267.10 | 0.00 | 0.00 | 291.03 | 0.00 | 0.00 | 0.00 | -99.11 | 0.00 |
F4 S1 APARTMENT | 30-APR-14:30 | 0.00 | -2192.50 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2289.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.14 | -512.47 |
F4 S2 APARTMENT | 30-APR-14:30 | 0.00 | -2201.23 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.14 | -503.56 |
M SW APARTMENT | 13-JUN-17:15 | 0.00 | -3218.21 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2679.95 | 0.00 | 229.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -616.39 |
M NW APARTMENT | 21-JUL-17:20 | 0.00 | -2522.59 | 0.00 | 0.00 | 141.06 | 194.45 | 588.62 | 2482.84 | 0.00 | 80.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.18 |
M SE APARTMENT | 22-JUL-11:15 | 0.00 | -2792.53 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2783.13 | 0.00 | 371.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.20 |
M NE APARTMENT | 22-JUL-11:15 | 0.00 | -1887.17 | 0.00 | 0.00 | 39.92 | 28.81 | 406.15 | 1407.93 | 0.00 | 334.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -330.46 |
M N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1405.30 | 0.00 | 0.00 | 151.95 | 194.45 | 588.62 | 262.50 | 0.00 | 0.00 | 315.71 | 0.00 | 0.00 | 0.00 | -107.93 | 0.00 |
M N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1407.10 | 0.00 | 0.00 | 151.92 | 194.45 | 588.62 | 262.31 | 0.00 | 0.00 | 317.73 | 0.00 | 0.00 | 0.00 | -107.93 | 0.00 |
M S1 APARTMENT | 30-APR-14:30 | 0.00 | -2220.87 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2284.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.41 | -473.30 |
M S2 APARTMENT | 30-APR-14:30 | 0.00 | -2229.40 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2283.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.41 | -464.58 |
F6 SW APARTMENT | 13-JUN-16:30 | 0.00 | -3189.28 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2869.67 | 0.00 | 315.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -813.27 |
F6 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2483.64 | 0.00 | 0.00 | 141.14 | 194.45 | 588.62 | 2479.11 | 0.00 | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1002.37 |
F6 SE APARTMENT | 22-JUL-11:30 | 0.00 | -2791.96 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2731.13 | 0.00 | 407.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.69 |
F6 NE APARTMENT | 22-JUL-11:30 | 0.00 | -1852.35 | 0.00 | 0.00 | 39.91 | 28.81 | 406.15 | 1263.97 | 0.00 | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -266.32 |
F6 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1459.76 | 0.00 | 0.00 | 152.84 | 194.45 | 588.62 | 260.58 | 0.00 | 0.00 | 378.85 | 0.00 | 0.00 | 0.00 | -115.58 | 0.00 |
F6 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1445.58 | 0.00 | 0.00 | 152.80 | 194.45 | 588.62 | 260.37 | 0.00 | 0.00 | 364.99 | 0.00 | 0.00 | 0.00 | -115.65 | 0.00 |
F6 S1 APARTMENT | 30-APR-14:30 | 0.00 | -2172.59 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2280.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.42 | -513.06 |
F6 S2 APARTMENT | 30-APR-14:30 | 0.00 | -2181.42 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2280.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.42 | -504.04 |
F7 SW APARTMENT | 13-JUN-16:30 | 0.00 | -3175.54 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2865.13 | 0.00 | 322.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -829.46 |
F7 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2468.85 | 0.00 | 0.00 | 141.23 | 194.45 | 588.62 | 2475.28 | 0.00 | 84.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1015.10 |
F7 SE APARTMENT | 22-JUL-11:30 | 0.00 | -2782.89 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2724.35 | 0.00 | 421.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.19 |
F7 NE APARTMENT | 22-JUL-11:30 | 0.00 | -1838.32 | 0.00 | 0.00 | 39.89 | 28.81 | 406.15 | 1260.48 | 0.00 | 391.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -288.42 |
F7 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1452.98 | 0.00 | 0.00 | 153.47 | 194.45 | 588.62 | 258.50 | 0.00 | 0.00 | 380.32 | 0.00 | 0.00 | 0.00 | -122.39 | 0.00 |
F7 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1436.28 | 0.00 | 0.00 | 153.43 | 194.45 | 588.62 | 258.28 | 0.00 | 0.00 | 364.07 | 0.00 | 0.00 | 0.00 | -122.56 | 0.00 |
F7 S1 APARTMENT | 30-APR-14:30 | 0.00 | -2146.23 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2277.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -91.27 | -531.17 |
F7 S2 APARTMENT | 30-APR-14:30 | 0.00 | -2155.27 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2277.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -91.27 | -521.95 |
F8 SW APARTMENT | 13-JUN-16:30 | 0.00 | -3171.57 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2860.84 | 0.00 | 328.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -835.13 |
F8 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2466.35 | 0.00 | 0.00 | 141.35 | 194.45 | 588.62 | 2471.69 | 0.00 | 86.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1016.00 |
F8 SE APARTMENT | 22-JUL-11:30 | 0.00 | -2782.62 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2718.12 | 0.00 | 432.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -843.67 |
F8 NE APARTMENT | 22-JUL-11:30 | 0.00 | -1836.11 | 0.00 | 0.00 | 39.89 | 28.81 | 406.15 | 1257.17 | 0.00 | 401.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -297.86 |
F8 N1 APARTMENT | 01-JUL-17:15 | 0.00 | -1331.92 | 0.00 | 0.00 | 154.06 | 194.45 | 588.62 | 256.77 | 0.00 | 0.00 | 266.59 | 0.00 | 0.00 | 0.00 | -128.57 | 0.00 |
F8 N2 APARTMENT | 01-JUL-17:15 | 0.00 | -1352.98 | 0.00 | 0.00 | 154.00 | 194.45 | 588.62 | 256.50 | 0.00 | 0.00 | 287.98 | 0.00 | 0.00 | 0.00 | -128.57 | 0.00 |
F8 S1 APARTMENT | 30-APR-14:30 | 0.00 | -2123.92 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2274.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96.00 | -545.68 |
F8 S2 APARTMENT | 30-APR-14:30 | 0.00 | -2133.29 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2273.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96.00 | -536.12 |
F9 SW APARTMENT | 13-JUN-16:30 | 0.00 | -3240.53 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2854.72 | 0.00 | 333.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.25 |
F9 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2542.59 | 0.00 | 0.00 | 141.71 | 194.45 | 588.62 | 2466.84 | 0.00 | 90.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -939.78 |
F9 SE APARTMENT | 22-JUL-11:30 | 0.00 | -2802.62 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2711.92 | 0.00 | 442.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -827.46 |
F9 NE APARTMENT | 22-JUL-11:30 | 0.00 | -1848.14 | 0.00 | 0.00 | 39.88 | 28.81 | 406.15 | 1253.43 | 0.00 | 410.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -290.45 |
F9 N1 APARTMENT | 13-JUN-20:25 | 0.00 | -1389.57 | 0.00 | 0.00 | 170.30 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 934.49 | 0.00 | -286.89 | 0.00 | -87.08 | 0.00 |
F9 N2 APARTMENT | 13-JUN-20:25 | 0.00 | -1364.04 | 0.00 | 0.00 | 170.41 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 908.49 | 0.00 | -286.58 | 0.00 | -87.05 | 0.00 |
F9 S1 APARTMENT | 30-APR-14:30 | 0.00 | -2112.55 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2271.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.63 | -549.48 |
F9 S2 APARTMENT | 30-APR-14:30 | 0.00 | -2124.11 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2271.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.63 | -537.67 |
T SW APARTMENT | 13-JUN-16:30 | 0.00 | -3842.42 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2813.37 | 0.00 | 338.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -126.55 |
T NW APARTMENT | 21-JUL-16:30 | 0.00 | -3222.54 | 0.00 | 0.00 | 84.58 | 144.04 | 588.62 | 2821.09 | 0.00 | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -437.99 |
T SE APARTMENT | 22-JUL-11:30 | 0.00 | -3415.65 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2669.50 | 0.00 | 451.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -180.82 |
T NE APARTMENT | 22-JUL-11:30 | 0.00 | -2377.78 | 0.00 | 0.00 | 39.86 | 28.81 | 406.15 | 1216.80 | 0.00 | 416.96 | 269.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 14-AUG-16:30 | 0.00 | -1776.12 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 383.55 | 0.00 | 283.76 | 291.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 14-AUG-16:30 | 0.00 | -1775.42 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 384.08 | 0.00 | 286.17 | 287.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 21-JUL-13:45 | 0.00 | -2818.88 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1900.68 | 0.00 | 282.20 | 183.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 21-JUL-13:45 | 0.00 | -2824.78 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1900.53 | 0.00 | 282.20 | 189.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-16:30 | 0.00 | -161810.63 | 0.00 | 0.00 | 6694.22 | 18221.75 | 47207.76 | 90891.79 | 0.00 | 21059.25 | 0.00 | 0.00 | 0.00 | 0.00 | -23.21 | -22240.91 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 24-NOV-11:55 | 902.55 | 0.00 | 0.00 | 0.00 | 47.34 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18.69 | 0.00 | -947.20 | -424.84 |
G NW APARTMENT | 10-JAN-08:53 | 980.42 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -827.42 | 0.00 | -156.32 | -502.35 |
OFFICE | 28-DEC-07:53 | 928.44 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -854.29 | 0.00 | -244.51 | -404.20 |
G NE APARTMENT | 30-DEC-02:00 | 951.66 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -938.53 | 0.00 | -227.02 | -231.53 |
G N1 APARTMENT | 27-MAY-13:45 | 1059.03 | 0.00 | 0.00 | 0.00 | 44.79 | 28.81 | 382.60 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1033.87 | -868.55 |
G N2 APARTMENT | 27-MAY-13:45 | 1051.33 | 0.00 | 0.00 | 0.00 | 44.79 | 28.81 | 382.60 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1033.80 | -860.88 |
G S1 APARTMENT | 24-NOV-11:55 | 953.86 | 0.00 | 0.00 | 0.00 | 46.90 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18.15 | 0.00 | -928.09 | -495.36 |
G S2 APARTMENT | 24-NOV-11:55 | 1003.43 | 0.00 | 0.00 | 0.00 | 46.74 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19.93 | 0.00 | -928.64 | -542.44 |
F2 SW APARTMENT | 24-NOV-11:55 | 880.85 | 0.00 | 0.00 | 0.00 | 46.23 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49.13 | 0.00 | -1049.58 | -269.21 |
F2 NW APARTMENT | 24-NOV-11:55 | 988.93 | 0.00 | 0.00 | 0.00 | 47.05 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37.13 | 0.00 | -1034.79 | -404.89 |
F2 SE APARTMENT | 24-NOV-12:00 | 806.78 | 0.00 | 0.00 | 0.00 | 46.08 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52.47 | 0.00 | -1036.05 | -205.19 |
F2 NE APARTMENT | 30-DEC-04:00 | 964.94 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -962.45 | 0.00 | -286.71 | -143.53 |
F2 N1 APARTMENT | 24-NOV-11:55 | 1056.88 | 0.00 | 0.00 | 0.00 | 46.61 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.86 | 0.00 | -1005.63 | -508.84 |
F2 N2 APARTMENT | 24-NOV-11:55 | 1049.21 | 0.00 | 0.00 | 0.00 | 46.63 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.69 | 0.00 | -1005.56 | -501.43 |
F2 S1 APARTMENT | 24-NOV-12:00 | 778.86 | 0.00 | 0.00 | 0.00 | 45.19 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.94 | 0.00 | -1012.21 | -210.74 |
F2 S2 APARTMENT | 24-NOV-12:00 | 743.64 | 0.00 | 0.00 | 0.00 | 45.14 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.39 | 0.00 | -1013.72 | -173.52 |
F3 SW APARTMENT | 24-NOV-12:00 | 894.17 | 0.00 | 0.00 | 0.00 | 45.72 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.26 | 0.00 | -1099.93 | -216.55 |
F3 NW APARTMENT | 24-NOV-11:55 | 1090.26 | 0.00 | 0.00 | 0.00 | 46.79 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.02 | 0.00 | -1098.14 | -431.73 |
F3 SE APARTMENT | 24-NOV-12:00 | 859.07 | 0.00 | 0.00 | 0.00 | 45.88 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61.82 | 0.00 | -1098.93 | -185.04 |
F3 NE APARTMENT | 26-DEC-04:00 | 976.85 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 132.60 | 0.00 | -1058.20 | 0.00 | -479.01 | 0.00 |
F3 N1 APARTMENT | 24-NOV-11:55 | 960.29 | 0.00 | 0.00 | 0.00 | 46.19 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38.08 | 0.00 | -1070.14 | -339.11 |
F3 N2 APARTMENT | 24-NOV-11:55 | 985.91 | 0.00 | 0.00 | 0.00 | 46.22 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37.81 | 0.00 | -1069.12 | -366.04 |
F3 S1 APARTMENT | 29-DEC-23:15 | 508.28 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.89 | 0.00 | -206.35 | -232.12 |
F3 S2 APARTMENT | 29-DEC-23:15 | 507.06 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.87 | 0.00 | -206.35 | -230.92 |
F4 SW APARTMENT | 24-NOV-12:00 | 960.54 | 0.00 | 0.00 | 0.00 | 45.46 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.33 | 0.00 | -1153.00 | -220.50 |
F4 NW APARTMENT | 24-NOV-11:55 | 1150.52 | 0.00 | 0.00 | 0.00 | 46.69 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.44 | 0.00 | -1150.65 | -432.96 |
F4 SE APARTMENT | 24-NOV-12:00 | 912.16 | 0.00 | 0.00 | 0.00 | 45.73 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -68.56 | 0.00 | -1151.50 | -178.66 |
F4 NE APARTMENT | 24-NOV-11:55 | 1030.91 | 0.00 | 0.00 | 0.00 | 47.06 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49.43 | 0.00 | -1149.05 | -320.33 |
F4 N1 APARTMENT | 24-NOV-11:55 | 906.81 | 0.00 | 0.00 | 0.00 | 46.01 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.83 | 0.00 | -1121.95 | -228.89 |
F4 N2 APARTMENT | 24-NOV-11:55 | 936.19 | 0.00 | 0.00 | 0.00 | 46.05 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.51 | 0.00 | -1120.80 | -259.77 |
F4 S1 APARTMENT | 29-DEC-23:15 | 507.57 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -642.72 | 0.00 | -230.79 | -201.14 |
F4 S2 APARTMENT | 10-JAN-02:30 | 490.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -615.31 | 0.00 | -133.08 | -175.47 |
M SW APARTMENT | 24-NOV-12:00 | 1004.16 | 0.00 | 0.00 | 0.00 | 45.30 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -80.07 | 0.00 | -1199.63 | -210.61 |
M NW APARTMENT | 24-NOV-11:55 | 1213.37 | 0.00 | 0.00 | 0.00 | 46.56 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.49 | 0.00 | -1197.16 | -443.13 |
M SE APARTMENT | 24-NOV-12:00 | 942.03 | 0.00 | 0.00 | 0.00 | 45.60 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74.18 | 0.00 | -1197.94 | -156.35 |
M NE APARTMENT | 24-NOV-11:55 | 1087.33 | 0.00 | 0.00 | 0.00 | 46.95 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.81 | 0.00 | -1195.40 | -324.91 |
M N1 APARTMENT | 10-JAN-21:10 | 882.07 | 0.00 | 0.00 | 0.00 | 189.67 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -650.39 | 0.00 | -181.28 | -898.84 |
M N2 APARTMENT | 10-JAN-21:10 | 889.17 | 0.00 | 0.00 | 0.00 | 189.67 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -650.35 | 0.00 | -181.28 | -905.97 |
M S1 APARTMENT | 10-JAN-03:30 | 505.87 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -624.31 | 0.00 | -129.75 | -179.56 |
M S2 APARTMENT | 10-JAN-03:30 | 506.23 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -624.28 | 0.00 | -129.75 | -179.95 |
F6 SW APARTMENT | 24-NOV-12:00 | 986.14 | 0.00 | 0.00 | 0.00 | 45.62 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.93 | 0.00 | -1239.93 | -155.74 |
F6 NW APARTMENT | 24-NOV-11:55 | 1186.57 | 0.00 | 0.00 | 0.00 | 46.82 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.81 | 0.00 | -1238.10 | -377.32 |
F6 SE APARTMENT | 24-NOV-11:55 | 956.38 | 0.00 | 0.00 | 0.00 | 45.92 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70.82 | 0.00 | -1256.42 | -115.89 |
F6 NE APARTMENT | 26-DEC-04:00 | 1107.90 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 149.06 | 0.00 | -1061.34 | 0.00 | -623.36 | 0.00 |
F6 N1 APARTMENT | 24-NOV-11:55 | 1144.62 | 0.00 | 0.00 | 0.00 | 46.11 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.88 | 0.00 | -1198.05 | -387.64 |
F6 N2 APARTMENT | 24-NOV-11:55 | 1176.56 | 0.00 | 0.00 | 0.00 | 46.15 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.54 | 0.00 | -1196.87 | -421.14 |
F6 S1 APARTMENT | 29-DEC-22:25 | 551.84 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -634.41 | 0.00 | -303.11 | -308.32 |
F6 S2 APARTMENT | 29-DEC-22:25 | 554.06 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -634.36 | 0.00 | -303.11 | -310.60 |
F7 SW APARTMENT | 24-NOV-11:55 | 1028.49 | 0.00 | 0.00 | 0.00 | 45.90 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.90 | 0.00 | -1295.33 | -146.00 |
F7 NW APARTMENT | 24-NOV-11:55 | 1176.64 | 0.00 | 0.00 | 0.00 | 46.99 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.14 | 0.00 | -1276.30 | -330.03 |
F7 SE APARTMENT | 24-NOV-11:55 | 1220.63 | 0.00 | 0.00 | 0.00 | 46.18 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.92 | 0.00 | -1285.13 | -354.61 |
F7 NE APARTMENT | 26-DEC-04:00 | 1159.79 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 133.34 | 0.00 | -1061.48 | 0.00 | -659.40 | 0.00 |
F7 N1 APARTMENT | 24-NOV-11:55 | 1339.80 | 0.00 | 0.00 | 0.00 | 46.30 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.29 | 0.00 | -1228.41 | -553.23 |
F7 N2 APARTMENT | 24-NOV-11:55 | 1328.76 | 0.00 | 0.00 | 0.00 | 46.33 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.00 | 0.00 | -1228.33 | -542.61 |
F7 S1 APARTMENT | 24-NOV-12:00 | 741.13 | 0.00 | 0.00 | 0.00 | 44.29 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 80.32 | 0.00 | -61.76 | 0.00 | -1244.81 | 0.00 |
F7 S2 APARTMENT | 24-NOV-12:00 | 753.84 | 0.00 | 0.00 | 0.00 | 44.31 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 66.78 | 0.00 | -61.46 | 0.00 | -1244.31 | 0.00 |
F8 SW APARTMENT | 24-NOV-11:55 | 1313.60 | 0.00 | 0.00 | 0.00 | 46.21 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70.15 | 0.00 | -1320.32 | -410.18 |
F8 NW APARTMENT | 26-DEC-04:00 | 1206.62 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 119.38 | 0.00 | -1061.73 | 0.00 | -692.03 | 0.00 |
F8 SE APARTMENT | 24-NOV-11:55 | 1354.96 | 0.00 | 0.00 | 0.00 | 46.47 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.43 | 0.00 | -1315.32 | -462.52 |
F8 NE APARTMENT | 26-DEC-04:00 | 1208.63 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 117.30 | 0.00 | -1061.64 | 0.00 | -692.03 | 0.00 |
F8 N1 APARTMENT | 24-NOV-11:55 | 1310.63 | 0.00 | 0.00 | 0.00 | 46.49 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.46 | 0.00 | -1262.01 | -491.49 |
F8 N2 APARTMENT | 24-NOV-11:55 | 1300.24 | 0.00 | 0.00 | 0.00 | 46.52 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.20 | 0.00 | -1261.93 | -481.46 |
F8 S1 APARTMENT | 24-NOV-12:00 | 1082.81 | 0.00 | 0.00 | 0.00 | 44.69 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.43 | 0.00 | -1266.34 | -243.57 |
F8 S2 APARTMENT | 24-NOV-12:00 | 1093.14 | 0.00 | 0.00 | 0.00 | 44.71 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.17 | 0.00 | -1265.93 | -254.58 |
F9 SW APARTMENT | 24-NOV-11:55 | 1354.19 | 0.00 | 0.00 | 0.00 | 46.71 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61.92 | 0.00 | -1349.15 | -430.66 |
F9 NW APARTMENT | 29-SEP-11:45 | 1414.11 | 0.00 | 0.00 | 0.00 | 42.11 | 28.81 | 406.15 | 384.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2218.37 | -57.59 |
F9 SE APARTMENT | 24-NOV-11:55 | 1288.61 | 0.00 | 0.00 | 0.00 | 46.94 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56.75 | 0.00 | -1347.85 | -371.79 |
F9 NE APARTMENT | 26-DEC-04:00 | 1312.51 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 40.83 | 0.00 | -1059.11 | 0.00 | -721.98 | 0.00 |
F9 N1 APARTMENT | 29-SEP-11:45 | 1481.53 | 0.00 | 0.00 | 0.00 | 41.86 | 28.81 | 406.15 | 228.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2107.21 | -80.09 |
F9 N2 APARTMENT | 29-SEP-11:45 | 1450.86 | 0.00 | 0.00 | 0.00 | 41.84 | 28.81 | 406.15 | 228.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2107.55 | -48.78 |
F9 S1 APARTMENT | 24-NOV-12:00 | 1007.23 | 0.00 | 0.00 | 0.00 | 45.40 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51.30 | 0.00 | -1295.65 | -146.52 |
F9 S2 APARTMENT | 24-NOV-12:00 | 1005.57 | 0.00 | 0.00 | 0.00 | 45.41 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51.11 | 0.00 | -1295.63 | -145.08 |
T SW APARTMENT | 30-DEC-02:00 | 1673.76 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -996.72 | 0.00 | -604.73 | -517.72 |
T NW APARTMENT | 29-SEP-11:45 | 1926.77 | 0.00 | 0.00 | 0.00 | 42.31 | 28.81 | 406.15 | 383.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2285.77 | -502.09 |
T SE APARTMENT | 30-DEC-02:00 | 1690.12 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -989.69 | 0.00 | -604.73 | -541.10 |
T NE APARTMENT | 30-DEC-02:00 | 1784.43 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.95 | 0.00 | -604.73 | -651.16 |
T N1 APARTMENT | 29-SEP-11:45 | 2033.34 | 0.00 | 0.00 | 0.00 | 42.06 | 28.81 | 406.15 | 230.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2170.74 | -569.96 |
T N2 APARTMENT | 29-SEP-11:45 | 2070.10 | 0.00 | 0.00 | 0.00 | 41.89 | 28.81 | 406.15 | 228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2170.98 | -604.21 |
T S1 APARTMENT | 24-NOV-11:55 | 1127.98 | 0.00 | 0.00 | 0.00 | 45.80 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.35 | 0.00 | -1344.57 | -226.70 |
T S2 APARTMENT | 24-NOV-11:55 | 1133.95 | 0.00 | 0.00 | 0.00 | 45.81 | 28.81 | 412.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.21 | 0.00 | -1344.34 | -233.04 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-NOV-11:55 | 69908.47 | 0.00 | 0.00 | 0.00 | 3716.86 | 10361.29 | 33249.10 | 1.60 | 0.00 | 0.00 | 0.00 | 0.00 | -4070.63 | 0.00 | -96165.75 | -17000.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Sec1.1A-General InformationData | |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 237.50 |
Number of hours cooling loads not met | 12.25 |
Number of hours not met | 249.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 76.28 | 0.00 | 228.55 | 82016.67 | 0.00 | 0.00 |
Space Cooling | 134.01 | 54432.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.90 | 1337.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.40 | 1864.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 577.48 | 18311.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1221.51 | 84193.77 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2571.60 | 1450.06 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 2571.60 |
Natural Gas | 0.00 | 1450.06 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4021.66 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 9.73 |
Space Cooling | 17.10 |
Fans-Interior | 73.69 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 30.16 |
Subtotal | 328.16 |
Natural Gas [MJ/m2] | |
Space Heating | 29.16 |
Service Water Heating | 155.87 |
Miscellaneous | -0.00 |
Subtotal | 185.04 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.35 |
Space Heating | 7.58 |
Space Cooling | 3.33 |
Fans-Interior | 14.36 |
Service Water Heating | 30.37 |
Receptacle Equipment | 28.13 |
Miscellaneous | 5.88 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.226562 |
G NW APARTMENT DIRECT AIR | 0.160507 |
OFFICE DIRECT AIR | 0.311759 |
G NE APARTMENT DIRECT AIR | 0.115280 |
G N1 APARTMENT DIRECT AIR | 0.069085 |
G N2 APARTMENT DIRECT AIR | 0.066656 |
G S1 APARTMENT DIRECT AIR | 0.163522 |
G S2 APARTMENT DIRECT AIR | 0.168922 |
F2 SW APARTMENT DIRECT AIR | 0.295602 |
F2 NW APARTMENT DIRECT AIR | 0.214969 |
F2 SE APARTMENT DIRECT AIR | 0.290901 |
F2 NE APARTMENT DIRECT AIR | 0.162135 |
F2 N1 APARTMENT DIRECT AIR | 0.103420 |
F2 N2 APARTMENT DIRECT AIR | 0.101086 |
F2 S1 APARTMENT DIRECT AIR | 0.217522 |
F2 S2 APARTMENT DIRECT AIR | 0.219800 |
F3 SW APARTMENT DIRECT AIR | 0.297642 |
F3 NW APARTMENT DIRECT AIR | 0.218495 |
F3 SE APARTMENT DIRECT AIR | 0.276589 |
F3 NE APARTMENT DIRECT AIR | 0.166418 |
F3 N1 APARTMENT DIRECT AIR | 0.107940 |
F3 N2 APARTMENT DIRECT AIR | 0.105586 |
F3 S1 APARTMENT DIRECT AIR | 0.221359 |
F3 S2 APARTMENT DIRECT AIR | 0.222606 |
F4 SW APARTMENT DIRECT AIR | 0.298211 |
F4 NW APARTMENT DIRECT AIR | 0.219538 |
F4 SE APARTMENT DIRECT AIR | 0.275531 |
F4 NE APARTMENT DIRECT AIR | 0.167190 |
F4 N1 APARTMENT DIRECT AIR | 0.109291 |
F4 N2 APARTMENT DIRECT AIR | 0.106927 |
F4 S1 APARTMENT DIRECT AIR | 0.222292 |
F4 S2 APARTMENT DIRECT AIR | 0.223393 |
M SW APARTMENT DIRECT AIR | 0.300727 |
M NW APARTMENT DIRECT AIR | 0.222410 |
M SE APARTMENT DIRECT AIR | 0.277827 |
M NE APARTMENT DIRECT AIR | 0.169791 |
M N1 APARTMENT DIRECT AIR | 0.112240 |
M N2 APARTMENT DIRECT AIR | 0.109868 |
M S1 APARTMENT DIRECT AIR | 0.225018 |
M S2 APARTMENT DIRECT AIR | 0.226096 |
F6 SW APARTMENT DIRECT AIR | 0.296775 |
F6 NW APARTMENT DIRECT AIR | 0.218751 |
F6 SE APARTMENT DIRECT AIR | 0.273891 |
F6 NE APARTMENT DIRECT AIR | 0.165999 |
F6 N1 APARTMENT DIRECT AIR | 0.109058 |
F6 N2 APARTMENT DIRECT AIR | 0.106697 |
F6 S1 APARTMENT DIRECT AIR | 0.221278 |
F6 S2 APARTMENT DIRECT AIR | 0.222352 |
F7 SW APARTMENT DIRECT AIR | 0.295168 |
F7 NW APARTMENT DIRECT AIR | 0.217436 |
F7 SE APARTMENT DIRECT AIR | 0.272285 |
F7 NE APARTMENT DIRECT AIR | 0.164525 |
F7 N1 APARTMENT DIRECT AIR | 0.108043 |
F7 N2 APARTMENT DIRECT AIR | 0.105688 |
F7 S1 APARTMENT DIRECT AIR | 0.219840 |
F7 S2 APARTMENT DIRECT AIR | 0.220911 |
F8 SW APARTMENT DIRECT AIR | 0.294653 |
F8 NW APARTMENT DIRECT AIR | 0.217273 |
F8 SE APARTMENT DIRECT AIR | 0.271741 |
F8 NE APARTMENT DIRECT AIR | 0.164151 |
F8 N1 APARTMENT DIRECT AIR | 0.108164 |
F8 N2 APARTMENT DIRECT AIR | 0.105815 |
F8 S1 APARTMENT DIRECT AIR | 0.219472 |
F8 S2 APARTMENT DIRECT AIR | 0.220544 |
F9 SW APARTMENT DIRECT AIR | 0.300998 |
F9 NW APARTMENT DIRECT AIR | 0.224321 |
F9 SE APARTMENT DIRECT AIR | 0.275991 |
F9 NE APARTMENT DIRECT AIR | 0.164490 |
F9 N1 APARTMENT DIRECT AIR | 0.114334 |
F9 N2 APARTMENT DIRECT AIR | 0.111956 |
F9 S1 APARTMENT DIRECT AIR | 0.223284 |
F9 S2 APARTMENT DIRECT AIR | 0.224359 |
T SW APARTMENT DIRECT AIR | 0.374737 |
T NW APARTMENT DIRECT AIR | 0.278836 |
T SE APARTMENT DIRECT AIR | 0.345729 |
T NE APARTMENT DIRECT AIR | 0.209222 |
T N1 APARTMENT DIRECT AIR | 0.150266 |
T N2 APARTMENT DIRECT AIR | 0.150454 |
T S1 APARTMENT DIRECT AIR | 0.303538 |
T S2 APARTMENT DIRECT AIR | 0.304593 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.226562 |
AIRLOOP G NW MAIN BRANCH | 0.160507 |
AIRLOOP OFFICE MAIN BRANCH | 0.311759 |
AIRLOOP G NE MAIN BRANCH | 0.115280 |
AIRLOOP G N1 MAIN BRANCH | 0.069085 |
AIRLOOP G N2 MAIN BRANCH | 0.066656 |
AIRLOOP G S1 MAIN BRANCH | 0.163522 |
AIRLOOP G S2 MAIN BRANCH | 0.168922 |
AIRLOOP F2 SW MAIN BRANCH | 0.295602 |
AIRLOOP F2 NW MAIN BRANCH | 0.214969 |
AIRLOOP F2 SE MAIN BRANCH | 0.290901 |
AIRLOOP F2 NE MAIN BRANCH | 0.162135 |
AIRLOOP F2 N1 MAIN BRANCH | 0.103420 |
AIRLOOP F2 N2 MAIN BRANCH | 0.101086 |
AIRLOOP F2 S1 MAIN BRANCH | 0.217522 |
AIRLOOP F2 S2 MAIN BRANCH | 0.219800 |
AIRLOOP F3 SW MAIN BRANCH | 0.297642 |
AIRLOOP F3 NW MAIN BRANCH | 0.218495 |
AIRLOOP F3 SE MAIN BRANCH | 0.276589 |
AIRLOOP F3 NE MAIN BRANCH | 0.166418 |
AIRLOOP F3 N1 MAIN BRANCH | 0.107940 |
AIRLOOP F3 N2 MAIN BRANCH | 0.105586 |
AIRLOOP F3 S1 MAIN BRANCH | 0.221359 |
AIRLOOP F3 S2 MAIN BRANCH | 0.222606 |
AIRLOOP F4 SW MAIN BRANCH | 0.298211 |
AIRLOOP F4 NW MAIN BRANCH | 0.219538 |
AIRLOOP F4 SE MAIN BRANCH | 0.275531 |
AIRLOOP F4 NE MAIN BRANCH | 0.167190 |
AIRLOOP F4 N1 MAIN BRANCH | 0.109291 |
AIRLOOP F4 N2 MAIN BRANCH | 0.106927 |
AIRLOOP F4 S1 MAIN BRANCH | 0.222292 |
AIRLOOP F4 S2 MAIN BRANCH | 0.223393 |
AIRLOOP M SW MAIN BRANCH | 0.300727 |
AIRLOOP M NW MAIN BRANCH | 0.222410 |
AIRLOOP M SE MAIN BRANCH | 0.277827 |
AIRLOOP M NE MAIN BRANCH | 0.169791 |
AIRLOOP M N1 MAIN BRANCH | 0.112240 |
AIRLOOP M N2 MAIN BRANCH | 0.109868 |
AIRLOOP M S1 MAIN BRANCH | 0.225018 |
AIRLOOP M S2 MAIN BRANCH | 0.226096 |
AIRLOOP F6 SW MAIN BRANCH | 0.296775 |
AIRLOOP F6 NW MAIN BRANCH | 0.218751 |
AIRLOOP F6 SE MAIN BRANCH | 0.273891 |
AIRLOOP F6 NE MAIN BRANCH | 0.165999 |
AIRLOOP F6 N1 MAIN BRANCH | 0.109058 |
AIRLOOP F6 N2 MAIN BRANCH | 0.106697 |
AIRLOOP F6 S1 MAIN BRANCH | 0.221278 |
AIRLOOP F6 S2 MAIN BRANCH | 0.222352 |
AIRLOOP F7 SW MAIN BRANCH | 0.295168 |
AIRLOOP F7 NW MAIN BRANCH | 0.217436 |
AIRLOOP F7 SE MAIN BRANCH | 0.272285 |
AIRLOOP F7 NE MAIN BRANCH | 0.164525 |
AIRLOOP F7 N1 MAIN BRANCH | 0.108043 |
AIRLOOP F7 N2 MAIN BRANCH | 0.105688 |
AIRLOOP F7 S1 MAIN BRANCH | 0.219840 |
AIRLOOP F7 S2 MAIN BRANCH | 0.220911 |
AIRLOOP F8 SW MAIN BRANCH | 0.294653 |
AIRLOOP F8 NW MAIN BRANCH | 0.217273 |
AIRLOOP F8 SE MAIN BRANCH | 0.271741 |
AIRLOOP F8 NE MAIN BRANCH | 0.164151 |
AIRLOOP F8 N1 MAIN BRANCH | 0.108164 |
AIRLOOP F8 N2 MAIN BRANCH | 0.105815 |
AIRLOOP F8 S1 MAIN BRANCH | 0.219472 |
AIRLOOP F8 S2 MAIN BRANCH | 0.220544 |
AIRLOOP F9 SW MAIN BRANCH | 0.300998 |
AIRLOOP F9 NW MAIN BRANCH | 0.224321 |
AIRLOOP F9 SE MAIN BRANCH | 0.275991 |
AIRLOOP F9 NE MAIN BRANCH | 0.164490 |
AIRLOOP F9 N1 MAIN BRANCH | 0.114334 |
AIRLOOP F9 N2 MAIN BRANCH | 0.111956 |
AIRLOOP F9 S1 MAIN BRANCH | 0.223284 |
AIRLOOP F9 S2 MAIN BRANCH | 0.224359 |
AIRLOOP T SW MAIN BRANCH | 0.374737 |
AIRLOOP T NW MAIN BRANCH | 0.278836 |
AIRLOOP T SE MAIN BRANCH | 0.345729 |
AIRLOOP T NE MAIN BRANCH | 0.209222 |
AIRLOOP T N1 MAIN BRANCH | 0.150266 |
AIRLOOP T N2 MAIN BRANCH | 0.150454 |
AIRLOOP T S1 MAIN BRANCH | 0.303538 |
AIRLOOP T S2 MAIN BRANCH | 0.304593 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.226562 |
AIRLOOP G NW | 0.160507 |
AIRLOOP OFFICE | 0.311759 |
AIRLOOP G NE | 0.115280 |
AIRLOOP G N1 | 0.069085 |
AIRLOOP G N2 | 0.066656 |
AIRLOOP G S1 | 0.163522 |
AIRLOOP G S2 | 0.168922 |
AIRLOOP F2 SW | 0.295602 |
AIRLOOP F2 NW | 0.214969 |
AIRLOOP F2 SE | 0.290901 |
AIRLOOP F2 NE | 0.162135 |
AIRLOOP F2 N1 | 0.103420 |
AIRLOOP F2 N2 | 0.101086 |
AIRLOOP F2 S1 | 0.217522 |
AIRLOOP F2 S2 | 0.219800 |
AIRLOOP F3 SW | 0.297642 |
AIRLOOP F3 NW | 0.218495 |
AIRLOOP F3 SE | 0.276589 |
AIRLOOP F3 NE | 0.166418 |
AIRLOOP F3 N1 | 0.107940 |
AIRLOOP F3 N2 | 0.105586 |
AIRLOOP F3 S1 | 0.221359 |
AIRLOOP F3 S2 | 0.222606 |
AIRLOOP F4 SW | 0.298211 |
AIRLOOP F4 NW | 0.219538 |
AIRLOOP F4 SE | 0.275531 |
AIRLOOP F4 NE | 0.167190 |
AIRLOOP F4 N1 | 0.109291 |
AIRLOOP F4 N2 | 0.106927 |
AIRLOOP F4 S1 | 0.222292 |
AIRLOOP F4 S2 | 0.223393 |
AIRLOOP M SW | 0.300727 |
AIRLOOP M NW | 0.222410 |
AIRLOOP M SE | 0.277827 |
AIRLOOP M NE | 0.169791 |
AIRLOOP M N1 | 0.112240 |
AIRLOOP M N2 | 0.109868 |
AIRLOOP M S1 | 0.225018 |
AIRLOOP M S2 | 0.226096 |
AIRLOOP F6 SW | 0.296775 |
AIRLOOP F6 NW | 0.218751 |
AIRLOOP F6 SE | 0.273891 |
AIRLOOP F6 NE | 0.165999 |
AIRLOOP F6 N1 | 0.109058 |
AIRLOOP F6 N2 | 0.106697 |
AIRLOOP F6 S1 | 0.221278 |
AIRLOOP F6 S2 | 0.222352 |
AIRLOOP F7 SW | 0.295168 |
AIRLOOP F7 NW | 0.217436 |
AIRLOOP F7 SE | 0.272285 |
AIRLOOP F7 NE | 0.164525 |
AIRLOOP F7 N1 | 0.108043 |
AIRLOOP F7 N2 | 0.105688 |
AIRLOOP F7 S1 | 0.219840 |
AIRLOOP F7 S2 | 0.220911 |
AIRLOOP F8 SW | 0.294653 |
AIRLOOP F8 NW | 0.217273 |
AIRLOOP F8 SE | 0.271741 |
AIRLOOP F8 NE | 0.164151 |
AIRLOOP F8 N1 | 0.108164 |
AIRLOOP F8 N2 | 0.105815 |
AIRLOOP F8 S1 | 0.219472 |
AIRLOOP F8 S2 | 0.220544 |
AIRLOOP F9 SW | 0.300998 |
AIRLOOP F9 NW | 0.224321 |
AIRLOOP F9 SE | 0.275991 |
AIRLOOP F9 NE | 0.164490 |
AIRLOOP F9 N1 | 0.114334 |
AIRLOOP F9 N2 | 0.111956 |
AIRLOOP F9 S1 | 0.223284 |
AIRLOOP F9 S2 | 0.224359 |
AIRLOOP T SW | 0.374737 |
AIRLOOP T NW | 0.278836 |
AIRLOOP T SE | 0.345729 |
AIRLOOP T NE | 0.209222 |
AIRLOOP T N1 | 0.150266 |
AIRLOOP T N2 | 0.150454 |
AIRLOOP T S1 | 0.303538 |
AIRLOOP T S2 | 0.304593 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.226562 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.160507 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.311759 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.115280 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.069085 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.066656 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.163522 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.168922 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.295602 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.214969 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.290901 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.162135 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.103420 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.101086 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.217522 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.219800 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.297642 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.218495 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.276589 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.166418 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.107940 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.105586 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.221359 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.222606 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.298211 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.219538 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.275531 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.167190 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.109291 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.106927 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.222292 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.223393 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.300727 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.222410 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.277827 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.169791 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.112240 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.109868 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.225018 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.226096 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.296775 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.218751 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.273891 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.165999 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.109058 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.106697 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.221278 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.222352 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.295168 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.217436 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.272285 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.164525 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.108043 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.105688 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.219840 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.220911 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.294653 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.217273 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.271741 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.164151 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.108164 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.105815 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.219472 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.220544 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.300998 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.224321 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.275991 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.164490 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.114334 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.111956 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.223284 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.224359 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.374737 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.278836 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.345729 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.209222 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.150266 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.150454 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.303538 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.304593 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.226562 | 3251.00 | 2480.29 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.160507 | 2290.45 | 1744.95 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.311759 | 4460.74 | 3412.41 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.115280 | 1627.26 | 1239.17 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.069085 | 978.24 | 738.41 | 0.000021 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.066656 | 942.99 | 711.80 | 0.000021 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.163522 | 2380.63 | 1803.96 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.168922 | 2455.71 | 1862.20 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.295602 | 4209.73 | 3223.62 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.214969 | 3052.70 | 2333.55 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.290901 | 4153.75 | 3177.50 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.162135 | 2271.03 | 1742.51 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.103420 | 1466.34 | 1111.65 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.101086 | 1433.01 | 1086.24 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.217522 | 3133.42 | 2386.87 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.219800 | 3165.13 | 2411.45 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.297642 | 4243.29 | 3247.89 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.218495 | 3102.84 | 2371.86 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.276589 | 3955.57 | 3023.37 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.166418 | 2330.98 | 1788.80 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.107940 | 1530.64 | 1160.78 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.105586 | 1497.08 | 1135.17 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.221359 | 3187.44 | 2428.43 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.222606 | 3204.79 | 2441.88 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.298211 | 4252.01 | 3254.24 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.219538 | 3118.12 | 2383.31 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.275531 | 3941.64 | 3012.16 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.167190 | 2342.27 | 1797.28 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.109291 | 1550.03 | 1175.51 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.106927 | 1516.35 | 1149.80 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.222292 | 3200.89 | 2438.62 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.223393 | 3216.21 | 2450.50 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.300727 | 4287.68 | 3281.55 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.222410 | 3158.79 | 2414.48 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.277827 | 3974.25 | 3037.10 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.169791 | 2378.78 | 1825.42 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.112240 | 1591.98 | 1207.57 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.109868 | 1558.19 | 1181.77 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.225018 | 3239.23 | 2468.13 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.226096 | 3254.22 | 2479.75 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.296775 | 4233.24 | 3239.06 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.218751 | 3108.22 | 2375.10 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.273891 | 3920.00 | 2994.78 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.165999 | 2326.67 | 1784.68 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.109058 | 1547.17 | 1173.10 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.106697 | 1513.51 | 1147.42 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.221278 | 3187.48 | 2427.86 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.222352 | 3202.43 | 2439.45 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.295168 | 4211.36 | 3221.85 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.217436 | 3090.31 | 2361.02 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.272285 | 3898.13 | 2977.57 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.164525 | 2306.62 | 1768.90 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.108043 | 1532.98 | 1162.13 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.105688 | 1499.38 | 1136.50 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.219840 | 3167.74 | 2412.41 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.220911 | 3182.65 | 2423.98 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.294653 | 4204.64 | 3216.41 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.217273 | 3088.42 | 2359.35 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.271741 | 3890.99 | 2971.82 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.164151 | 2301.75 | 1764.95 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.108164 | 1534.85 | 1163.49 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.105815 | 1501.34 | 1137.93 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.219472 | 3162.87 | 2408.51 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.220544 | 3177.79 | 2420.08 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.300998 | 4289.29 | 3282.99 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.224321 | 3187.25 | 2435.58 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.275991 | 3950.59 | 3017.78 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.164490 | 2314.77 | 1773.22 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.114334 | 1622.39 | 1230.50 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.111956 | 1588.50 | 1204.63 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.223284 | 3219.48 | 2451.32 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.224359 | 3234.43 | 2462.91 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.374737 | 5324.13 | 4082.55 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.278836 | 3959.09 | 3031.76 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.345729 | 4921.76 | 3770.27 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.209222 | 2956.66 | 2265.62 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.150266 | 2202.06 | 1663.23 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.150454 | 2204.71 | 1665.27 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.303538 | 4333.66 | 3315.65 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.304593 | 4348.33 | 3327.02 | 0.000095 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.226562 | 0.226562 | 0.226562 | 0.226562 | 3251.00 | 3251.00 | 2191.73 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.160507 | 0.160507 | 0.160507 | 0.160507 | 2290.45 | 2290.45 | 2199.21 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.311759 | 0.311759 | 0.311759 | 0.311759 | 4460.74 | 4460.74 | 2975.63 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.115280 | 0.115280 | 0.115280 | 0.115280 | 1627.26 | 1627.26 | 2196.78 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.069085 | 0.069085 | 0.069085 | 0.069085 | 978.24 | 978.24 | 1679.15 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.066656 | 0.066656 | 0.066656 | 0.066656 | 942.99 | 942.99 | 1679.09 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.163522 | 0.163522 | 0.163522 | 0.163522 | 2380.63 | 2380.63 | 1667.70 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.168922 | 0.168922 | 0.168922 | 0.168922 | 2455.71 | 2455.71 | 1676.19 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.295602 | 0.295602 | 0.295602 | 0.295602 | 4209.73 | 4209.73 | 2039.14 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.214969 | 0.214969 | 0.214969 | 0.214969 | 3052.70 | 3052.70 | 2045.04 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.290901 | 0.290901 | 0.290901 | 0.290901 | 4153.75 | 4153.75 | 2061.38 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.162135 | 0.162135 | 0.162135 | 0.162135 | 2271.03 | 2271.03 | 2041.78 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.103420 | 0.103420 | 0.103420 | 0.103420 | 1466.34 | 1466.34 | 1421.48 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.101086 | 0.101086 | 0.101086 | 0.101086 | 1433.01 | 1433.01 | 1421.40 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.217522 | 0.217522 | 0.217522 | 0.217522 | 3133.42 | 3133.42 | 1418.30 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.219800 | 0.219800 | 0.219800 | 0.219800 | 3165.13 | 3165.13 | 1419.95 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.297642 | 0.297642 | 0.297642 | 0.297642 | 4243.29 | 4243.29 | 1980.42 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.218495 | 0.218495 | 0.218495 | 0.218495 | 3102.84 | 3102.84 | 1987.00 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.276589 | 0.276589 | 0.276589 | 0.276589 | 3955.57 | 3955.57 | 1979.96 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.166418 | 0.166418 | 0.166418 | 0.166418 | 2330.98 | 2330.98 | 1983.60 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.107940 | 0.107940 | 0.107940 | 0.107940 | 1530.64 | 1530.64 | 1376.37 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.105586 | 0.105586 | 0.105586 | 0.105586 | 1497.08 | 1497.08 | 1376.37 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.221359 | 0.221359 | 0.221359 | 0.221359 | 3187.44 | 3187.44 | 1376.37 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.222606 | 0.222606 | 0.222606 | 0.222606 | 3204.79 | 3204.79 | 1376.37 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.298211 | 0.298211 | 0.298211 | 0.298211 | 4252.01 | 4252.01 | 1976.03 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.219538 | 0.219538 | 0.219538 | 0.219538 | 3118.12 | 3118.12 | 1983.11 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.275531 | 0.275531 | 0.275531 | 0.275531 | 3941.64 | 3941.64 | 1972.92 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.167190 | 0.167190 | 0.167190 | 0.167190 | 2342.27 | 2342.27 | 1979.69 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.109291 | 0.109291 | 0.109291 | 0.109291 | 1550.03 | 1550.03 | 1376.37 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.106927 | 0.106927 | 0.106927 | 0.106927 | 1516.35 | 1516.35 | 1376.37 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.222292 | 0.222292 | 0.222292 | 0.222292 | 3200.89 | 3200.89 | 1376.37 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.223393 | 0.223393 | 0.223393 | 0.223393 | 3216.21 | 3216.21 | 1376.37 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.300727 | 0.300727 | 0.300727 | 0.300727 | 4287.68 | 4287.68 | 1956.55 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.222410 | 0.222410 | 0.222410 | 0.222410 | 3158.79 | 3158.79 | 1962.61 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.277827 | 0.277827 | 0.277827 | 0.277827 | 3974.25 | 3974.25 | 1953.19 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.169791 | 0.169791 | 0.169791 | 0.169791 | 2378.78 | 2378.78 | 1959.21 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.112240 | 0.112240 | 0.112240 | 0.112240 | 1591.98 | 1591.98 | 1376.37 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.109868 | 0.109868 | 0.109868 | 0.109868 | 1558.19 | 1558.19 | 1376.37 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.225018 | 0.225018 | 0.225018 | 0.225018 | 3239.23 | 3239.23 | 1376.37 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.226096 | 0.226096 | 0.226096 | 0.226096 | 3254.22 | 3254.22 | 1376.37 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.296775 | 0.296775 | 0.296775 | 0.296775 | 4233.24 | 4233.24 | 2008.00 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.218751 | 0.218751 | 0.218751 | 0.218751 | 3108.22 | 3108.22 | 2014.96 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.273891 | 0.273891 | 0.273891 | 0.273891 | 3920.00 | 3920.00 | 2004.65 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.165999 | 0.165999 | 0.165999 | 0.165999 | 2326.67 | 2326.67 | 2011.61 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.109058 | 0.109058 | 0.109058 | 0.109058 | 1547.17 | 1547.17 | 1376.37 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.106697 | 0.106697 | 0.106697 | 0.106697 | 1513.51 | 1513.51 | 1376.37 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.221278 | 0.221278 | 0.221278 | 0.221278 | 3187.48 | 3187.48 | 1376.37 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.222352 | 0.222352 | 0.222352 | 0.222352 | 3202.43 | 3202.43 | 1376.37 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.295168 | 0.295168 | 0.295168 | 0.295168 | 4211.36 | 4211.36 | 2035.52 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.217436 | 0.217436 | 0.217436 | 0.217436 | 3090.31 | 3090.31 | 2042.13 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.272285 | 0.272285 | 0.272285 | 0.272285 | 3898.13 | 3898.13 | 2032.24 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.164525 | 0.164525 | 0.164525 | 0.164525 | 2306.62 | 2306.62 | 2038.85 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.108043 | 0.108043 | 0.108043 | 0.108043 | 1532.98 | 1532.98 | 1382.60 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.105688 | 0.105688 | 0.105688 | 0.105688 | 1499.38 | 1499.38 | 1382.52 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.219840 | 0.219840 | 0.219840 | 0.219840 | 3167.74 | 3167.74 | 1376.41 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.220911 | 0.220911 | 0.220911 | 0.220911 | 3182.65 | 3182.65 | 1376.37 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.294653 | 0.294653 | 0.294653 | 0.294653 | 4204.64 | 4204.64 | 2068.94 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.217273 | 0.217273 | 0.217273 | 0.217273 | 3088.42 | 3088.42 | 2074.99 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.271741 | 0.271741 | 0.271741 | 0.271741 | 3890.99 | 3890.99 | 2065.74 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.164151 | 0.164151 | 0.164151 | 0.164151 | 2301.75 | 2301.75 | 2071.79 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.108164 | 0.108164 | 0.108164 | 0.108164 | 1534.85 | 1534.85 | 1411.36 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.105815 | 0.105815 | 0.105815 | 0.105815 | 1501.34 | 1501.34 | 1411.28 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.219472 | 0.219472 | 0.219472 | 0.219472 | 3162.87 | 3162.87 | 1405.70 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.220544 | 0.220544 | 0.220544 | 0.220544 | 3177.79 | 3177.79 | 1405.62 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.300998 | 0.300998 | 0.300998 | 0.300998 | 4289.29 | 4289.29 | 2217.55 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.224321 | 0.224321 | 0.224321 | 0.224321 | 3187.25 | 3187.25 | 2221.20 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.275991 | 0.275991 | 0.275991 | 0.275991 | 3950.59 | 3950.59 | 2214.40 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.164490 | 0.164490 | 0.164490 | 0.164490 | 2314.77 | 2314.77 | 2218.05 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.114334 | 0.114334 | 0.114334 | 0.114334 | 1622.39 | 1622.39 | 1546.58 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.111956 | 0.111956 | 0.111956 | 0.111956 | 1588.50 | 1588.50 | 1546.49 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.223284 | 0.223284 | 0.223284 | 0.223284 | 3219.48 | 3219.48 | 1542.83 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.224359 | 0.224359 | 0.224359 | 0.224359 | 3234.43 | 3234.43 | 1542.74 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.374737 | 0.374737 | 0.374737 | 0.374737 | 5324.13 | 5324.13 | 2810.02 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.278836 | 0.278836 | 0.278836 | 0.278836 | 3959.09 | 3959.09 | 2819.25 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.345729 | 0.345729 | 0.345729 | 0.345729 | 4921.76 | 4921.76 | 2807.19 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.209222 | 0.209222 | 0.209222 | 0.209222 | 2956.66 | 2956.66 | 2816.41 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.150266 | 0.150266 | 0.150266 | 0.150266 | 2202.06 | 2202.06 | 2185.85 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.150454 | 0.150454 | 0.150454 | 0.150454 | 2204.71 | 2204.71 | 2185.77 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.303538 | 0.303538 | 0.303538 | 0.303538 | 4333.66 | 4333.66 | 2173.40 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.304593 | 0.304593 | 0.304593 | 0.304593 | 4348.33 | 4348.33 | 2173.32 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.226562 |
AIRLOOP G NW SUPPLY FAN | 0.160507 |
AIRLOOP OFFICE SUPPLY FAN | 0.311759 |
AIRLOOP G NE SUPPLY FAN | 0.115280 |
AIRLOOP G N1 SUPPLY FAN | 0.069085 |
AIRLOOP G N2 SUPPLY FAN | 0.066656 |
AIRLOOP G S1 SUPPLY FAN | 0.163522 |
AIRLOOP G S2 SUPPLY FAN | 0.168922 |
AIRLOOP F2 SW SUPPLY FAN | 0.295602 |
AIRLOOP F2 NW SUPPLY FAN | 0.214969 |
AIRLOOP F2 SE SUPPLY FAN | 0.290901 |
AIRLOOP F2 NE SUPPLY FAN | 0.162135 |
AIRLOOP F2 N1 SUPPLY FAN | 0.103420 |
AIRLOOP F2 N2 SUPPLY FAN | 0.101086 |
AIRLOOP F2 S1 SUPPLY FAN | 0.217522 |
AIRLOOP F2 S2 SUPPLY FAN | 0.219800 |
AIRLOOP F3 SW SUPPLY FAN | 0.297642 |
AIRLOOP F3 NW SUPPLY FAN | 0.218495 |
AIRLOOP F3 SE SUPPLY FAN | 0.276589 |
AIRLOOP F3 NE SUPPLY FAN | 0.166418 |
AIRLOOP F3 N1 SUPPLY FAN | 0.107940 |
AIRLOOP F3 N2 SUPPLY FAN | 0.105586 |
AIRLOOP F3 S1 SUPPLY FAN | 0.221359 |
AIRLOOP F3 S2 SUPPLY FAN | 0.222606 |
AIRLOOP F4 SW SUPPLY FAN | 0.298211 |
AIRLOOP F4 NW SUPPLY FAN | 0.219538 |
AIRLOOP F4 SE SUPPLY FAN | 0.275531 |
AIRLOOP F4 NE SUPPLY FAN | 0.167190 |
AIRLOOP F4 N1 SUPPLY FAN | 0.109291 |
AIRLOOP F4 N2 SUPPLY FAN | 0.106927 |
AIRLOOP F4 S1 SUPPLY FAN | 0.222292 |
AIRLOOP F4 S2 SUPPLY FAN | 0.223393 |
AIRLOOP M SW SUPPLY FAN | 0.300727 |
AIRLOOP M NW SUPPLY FAN | 0.222410 |
AIRLOOP M SE SUPPLY FAN | 0.277827 |
AIRLOOP M NE SUPPLY FAN | 0.169791 |
AIRLOOP M N1 SUPPLY FAN | 0.112240 |
AIRLOOP M N2 SUPPLY FAN | 0.109868 |
AIRLOOP M S1 SUPPLY FAN | 0.225018 |
AIRLOOP M S2 SUPPLY FAN | 0.226096 |
AIRLOOP F6 SW SUPPLY FAN | 0.296775 |
AIRLOOP F6 NW SUPPLY FAN | 0.218751 |
AIRLOOP F6 SE SUPPLY FAN | 0.273891 |
AIRLOOP F6 NE SUPPLY FAN | 0.165999 |
AIRLOOP F6 N1 SUPPLY FAN | 0.109058 |
AIRLOOP F6 N2 SUPPLY FAN | 0.106697 |
AIRLOOP F6 S1 SUPPLY FAN | 0.221278 |
AIRLOOP F6 S2 SUPPLY FAN | 0.222352 |
AIRLOOP F7 SW SUPPLY FAN | 0.295168 |
AIRLOOP F7 NW SUPPLY FAN | 0.217436 |
AIRLOOP F7 SE SUPPLY FAN | 0.272285 |
AIRLOOP F7 NE SUPPLY FAN | 0.164525 |
AIRLOOP F7 N1 SUPPLY FAN | 0.108043 |
AIRLOOP F7 N2 SUPPLY FAN | 0.105688 |
AIRLOOP F7 S1 SUPPLY FAN | 0.219840 |
AIRLOOP F7 S2 SUPPLY FAN | 0.220911 |
AIRLOOP F8 SW SUPPLY FAN | 0.294653 |
AIRLOOP F8 NW SUPPLY FAN | 0.217273 |
AIRLOOP F8 SE SUPPLY FAN | 0.271741 |
AIRLOOP F8 NE SUPPLY FAN | 0.164151 |
AIRLOOP F8 N1 SUPPLY FAN | 0.108164 |
AIRLOOP F8 N2 SUPPLY FAN | 0.105815 |
AIRLOOP F8 S1 SUPPLY FAN | 0.219472 |
AIRLOOP F8 S2 SUPPLY FAN | 0.220544 |
AIRLOOP F9 SW SUPPLY FAN | 0.300998 |
AIRLOOP F9 NW SUPPLY FAN | 0.224321 |
AIRLOOP F9 SE SUPPLY FAN | 0.275991 |
AIRLOOP F9 NE SUPPLY FAN | 0.164490 |
AIRLOOP F9 N1 SUPPLY FAN | 0.114334 |
AIRLOOP F9 N2 SUPPLY FAN | 0.111956 |
AIRLOOP F9 S1 SUPPLY FAN | 0.223284 |
AIRLOOP F9 S2 SUPPLY FAN | 0.224359 |
AIRLOOP T SW SUPPLY FAN | 0.374737 |
AIRLOOP T NW SUPPLY FAN | 0.278836 |
AIRLOOP T SE SUPPLY FAN | 0.345729 |
AIRLOOP T NE SUPPLY FAN | 0.209222 |
AIRLOOP T N1 SUPPLY FAN | 0.150266 |
AIRLOOP T N2 SUPPLY FAN | 0.150454 |
AIRLOOP T S1 SUPPLY FAN | 0.303538 |
AIRLOOP T S2 SUPPLY FAN | 0.304593 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.226562 | 3251.00 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.160507 | 2290.45 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.311759 | 4460.74 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.115280 | 1627.26 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.069085 | 978.24 | 0.000021 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.066656 | 942.99 | 0.000021 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.163522 | 2380.63 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.168922 | 2455.71 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.295602 | 4209.73 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.214969 | 3052.70 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.290901 | 4153.75 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.162135 | 2271.03 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.103420 | 1466.34 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.101086 | 1433.01 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.217522 | 3133.42 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.219800 | 3165.13 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.297642 | 4243.29 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.218495 | 3102.84 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.276589 | 3955.57 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.166418 | 2330.98 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.107940 | 1530.64 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.105586 | 1497.08 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.221359 | 3187.44 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.222606 | 3204.79 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.298211 | 4252.01 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.219538 | 3118.12 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.275531 | 3941.64 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.167190 | 2342.27 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.109291 | 1550.03 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.106927 | 1516.35 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.222292 | 3200.89 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.223393 | 3216.21 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.300727 | 4287.68 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.222410 | 3158.79 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.277827 | 3974.25 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.169791 | 2378.78 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.112240 | 1591.98 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.109868 | 1558.19 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.225018 | 3239.23 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.226096 | 3254.22 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.296775 | 4233.24 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.218751 | 3108.22 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.273891 | 3920.00 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.165999 | 2326.67 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.109058 | 1547.17 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.106697 | 1513.51 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.221278 | 3187.48 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.222352 | 3202.43 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.295168 | 4211.36 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.217436 | 3090.31 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.272285 | 3898.13 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.164525 | 2306.62 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.108043 | 1532.98 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.105688 | 1499.38 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.219840 | 3167.74 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.220911 | 3182.65 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.294653 | 4204.64 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.217273 | 3088.42 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.271741 | 3890.99 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.164151 | 2301.75 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.108164 | 1534.85 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.105815 | 1501.34 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.219472 | 3162.87 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.220544 | 3177.79 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.300998 | 4289.29 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.224321 | 3187.25 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.275991 | 3950.59 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.164490 | 2314.77 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.114334 | 1622.39 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.111956 | 1588.50 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.223284 | 3219.48 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.224359 | 3234.43 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.374737 | 5324.13 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.278836 | 3959.09 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.345729 | 4921.76 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.209222 | 2956.66 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.150266 | 2202.06 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.150454 | 2204.71 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.303538 | 4333.66 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.304593 | 4348.33 | 0.000095 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2191.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2199.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2975.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2196.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1679.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1679.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1667.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1676.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2039.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2045.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2061.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2041.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1421.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1421.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1418.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1419.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1980.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1987.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1979.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1983.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1976.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1983.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1972.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1979.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1956.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1962.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1953.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1959.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2008.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2014.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2004.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2011.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2035.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2042.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2032.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2038.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1382.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1382.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1376.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1376.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2068.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2074.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2065.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2071.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1411.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1411.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1405.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1405.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2217.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2221.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2214.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2218.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1546.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1546.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1542.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1542.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2810.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2819.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2807.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2816.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2185.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2185.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2173.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2173.32 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005098 | 5.73 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005098 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005098 | 2460.78 | 6.55 | 7554.19 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005098 | 1300.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 4.18 |
February | 21.98 | 4.25 |
March | 21.87 | 5.90 |
April | 22.98 | 8.96 |
May | 22.99 | 9.99 |
June | 23.99 | 13.31 |
July | 24.06 | 15.02 |
August | 24.05 | 15.65 |
September | 24.02 | 13.43 |
October | 22.62 | 9.33 |
November | 21.93 | 6.66 |
December | 21.75 | 4.10 |
Annual Sum or Average | 22.85 | 9.26 |
Minimum of Months | 21.75 | 4.10 |
Maximum of Months | 24.06 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.72 | 5.90 |
April | 22.30 | 8.96 |
May | 22.50 | 9.99 |
June | 23.79 | 13.31 |
July | 23.84 | 15.02 |
August | 23.68 | 15.65 |
September | 23.46 | 13.43 |
October | 21.97 | 9.33 |
November | 21.71 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.51 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.84 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 4.18 |
February | 22.13 | 4.25 |
March | 22.11 | 5.90 |
April | 22.94 | 8.96 |
May | 22.99 | 9.99 |
June | 23.88 | 13.31 |
July | 24.09 | 15.02 |
August | 24.20 | 15.65 |
September | 23.96 | 13.43 |
October | 22.64 | 9.33 |
November | 22.14 | 6.66 |
December | 21.90 | 4.10 |
Annual Sum or Average | 22.92 | 9.26 |
Minimum of Months | 21.90 | 4.10 |
Maximum of Months | 24.20 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.71 | 5.90 |
April | 22.29 | 8.96 |
May | 22.44 | 9.99 |
June | 23.70 | 13.31 |
July | 23.73 | 15.02 |
August | 23.61 | 15.65 |
September | 23.45 | 13.43 |
October | 21.92 | 9.33 |
November | 21.70 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.47 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.73 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.71 | 5.90 |
April | 22.01 | 8.96 |
May | 22.16 | 9.99 |
June | 23.57 | 13.31 |
July | 23.59 | 15.02 |
August | 23.38 | 15.65 |
September | 23.27 | 13.43 |
October | 21.89 | 9.33 |
November | 21.70 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.37 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.59 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.70 | 5.90 |
April | 22.01 | 8.96 |
May | 22.15 | 9.99 |
June | 23.56 | 13.31 |
July | 23.58 | 15.02 |
August | 23.38 | 15.65 |
September | 23.27 | 13.43 |
October | 21.88 | 9.33 |
November | 21.70 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.36 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.58 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.18 |
February | 22.00 | 4.25 |
March | 21.89 | 5.90 |
April | 22.98 | 8.96 |
May | 22.95 | 9.99 |
June | 23.97 | 13.31 |
July | 24.01 | 15.02 |
August | 24.02 | 15.65 |
September | 24.09 | 13.43 |
October | 22.81 | 9.33 |
November | 22.03 | 6.66 |
December | 21.77 | 4.10 |
Annual Sum or Average | 22.87 | 9.26 |
Minimum of Months | 21.77 | 4.10 |
Maximum of Months | 24.09 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.18 |
February | 22.03 | 4.25 |
March | 21.92 | 5.90 |
April | 23.02 | 8.96 |
May | 22.99 | 9.99 |
June | 23.99 | 13.31 |
July | 24.03 | 15.02 |
August | 24.04 | 15.65 |
September | 24.11 | 13.43 |
October | 22.85 | 9.33 |
November | 22.06 | 6.66 |
December | 21.78 | 4.10 |
Annual Sum or Average | 22.90 | 9.26 |
Minimum of Months | 21.78 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.95 | 4.18 |
February | 18.13 | 4.25 |
March | 18.52 | 5.90 |
April | 20.26 | 8.96 |
May | 20.59 | 9.99 |
June | 22.52 | 13.31 |
July | 23.11 | 15.02 |
August | 23.22 | 15.65 |
September | 22.56 | 13.43 |
October | 19.96 | 9.33 |
November | 18.62 | 6.66 |
December | 17.76 | 4.10 |
Annual Sum or Average | 20.28 | 9.26 |
Minimum of Months | 17.76 | 4.10 |
Maximum of Months | 23.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.18 |
February | 22.42 | 4.25 |
March | 22.38 | 5.90 |
April | 23.95 | 8.96 |
May | 23.96 | 9.99 |
June | 24.33 | 13.31 |
July | 24.30 | 15.02 |
August | 24.29 | 15.65 |
September | 24.31 | 13.43 |
October | 23.50 | 9.33 |
November | 22.43 | 6.66 |
December | 21.83 | 4.10 |
Annual Sum or Average | 23.33 | 9.26 |
Minimum of Months | 21.83 | 4.10 |
Maximum of Months | 24.33 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.18 |
February | 21.73 | 4.25 |
March | 21.86 | 5.90 |
April | 23.19 | 8.96 |
May | 23.52 | 9.99 |
June | 24.23 | 13.31 |
July | 24.19 | 15.02 |
August | 24.08 | 15.65 |
September | 23.89 | 13.43 |
October | 22.46 | 9.33 |
November | 21.77 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.87 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.23 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.32 | 4.18 |
February | 22.48 | 4.25 |
March | 22.47 | 5.90 |
April | 24.01 | 8.96 |
May | 24.03 | 9.99 |
June | 24.34 | 13.31 |
July | 24.32 | 15.02 |
August | 24.33 | 15.65 |
September | 24.33 | 13.43 |
October | 23.57 | 9.33 |
November | 22.53 | 6.66 |
December | 21.87 | 4.10 |
Annual Sum or Average | 23.39 | 9.26 |
Minimum of Months | 21.87 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.80 | 5.90 |
April | 23.20 | 8.96 |
May | 23.45 | 9.99 |
June | 24.16 | 13.31 |
July | 24.12 | 15.02 |
August | 24.05 | 15.65 |
September | 23.89 | 13.43 |
October | 22.35 | 9.33 |
November | 21.73 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.83 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.16 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.71 | 4.25 |
March | 21.84 | 5.90 |
April | 22.93 | 8.96 |
May | 23.31 | 9.99 |
June | 24.12 | 13.31 |
July | 24.03 | 15.02 |
August | 23.84 | 15.65 |
September | 23.76 | 13.43 |
October | 22.45 | 9.33 |
November | 21.78 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.77 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.12 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.71 | 4.25 |
March | 21.83 | 5.90 |
April | 22.94 | 8.96 |
May | 23.30 | 9.99 |
June | 24.12 | 13.31 |
July | 24.02 | 15.02 |
August | 23.84 | 15.65 |
September | 23.76 | 13.43 |
October | 22.44 | 9.33 |
November | 21.77 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.77 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.12 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 4.18 |
February | 22.71 | 4.25 |
March | 22.61 | 5.90 |
April | 24.05 | 8.96 |
May | 24.05 | 9.99 |
June | 24.32 | 13.31 |
July | 24.28 | 15.02 |
August | 24.26 | 15.65 |
September | 24.34 | 13.43 |
October | 23.80 | 9.33 |
November | 22.84 | 6.66 |
December | 21.95 | 4.10 |
Annual Sum or Average | 23.48 | 9.26 |
Minimum of Months | 21.95 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.59 | 4.18 |
February | 22.73 | 4.25 |
March | 22.63 | 5.90 |
April | 24.06 | 8.96 |
May | 24.06 | 9.99 |
June | 24.32 | 13.31 |
July | 24.28 | 15.02 |
August | 24.26 | 15.65 |
September | 24.34 | 13.43 |
October | 23.82 | 9.33 |
November | 22.86 | 6.66 |
December | 21.97 | 4.10 |
Annual Sum or Average | 23.49 | 9.26 |
Minimum of Months | 21.97 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 4.18 |
February | 22.58 | 4.25 |
March | 22.71 | 5.90 |
April | 24.55 | 8.96 |
May | 24.78 | 9.99 |
June | 25.69 | 13.31 |
July | 25.82 | 15.02 |
August | 25.76 | 15.65 |
September | 25.50 | 13.43 |
October | 23.82 | 9.33 |
November | 22.66 | 6.66 |
December | 21.91 | 4.10 |
Annual Sum or Average | 24.02 | 9.26 |
Minimum of Months | 21.91 | 4.10 |
Maximum of Months | 25.82 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.45 | 4.18 |
February | 22.61 | 4.25 |
March | 22.62 | 5.90 |
April | 24.12 | 8.96 |
May | 24.13 | 9.99 |
June | 24.35 | 13.31 |
July | 24.32 | 15.02 |
August | 24.30 | 15.65 |
September | 24.32 | 13.43 |
October | 23.74 | 9.33 |
November | 22.66 | 6.66 |
December | 21.86 | 4.10 |
Annual Sum or Average | 23.46 | 9.26 |
Minimum of Months | 21.86 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.18 |
February | 21.75 | 4.25 |
March | 21.95 | 5.90 |
April | 23.51 | 8.96 |
May | 23.79 | 9.99 |
June | 24.27 | 13.31 |
July | 24.21 | 15.02 |
August | 24.12 | 15.65 |
September | 23.96 | 13.43 |
October | 22.70 | 9.33 |
November | 21.81 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.97 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.27 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | 4.18 |
February | 22.57 | 4.25 |
March | 22.59 | 5.90 |
April | 24.14 | 8.96 |
May | 24.14 | 9.99 |
June | 24.34 | 13.31 |
July | 24.32 | 15.02 |
August | 24.31 | 15.65 |
September | 24.34 | 13.43 |
October | 23.71 | 9.33 |
November | 22.63 | 6.66 |
December | 21.86 | 4.10 |
Annual Sum or Average | 23.45 | 9.26 |
Minimum of Months | 21.86 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.71 | 4.25 |
March | 21.87 | 5.90 |
April | 23.52 | 8.96 |
May | 23.74 | 9.99 |
June | 24.22 | 13.31 |
July | 24.16 | 15.02 |
August | 24.09 | 15.65 |
September | 23.96 | 13.43 |
October | 22.57 | 9.33 |
November | 21.76 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.92 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.18 |
February | 21.73 | 4.25 |
March | 21.96 | 5.90 |
April | 23.38 | 8.96 |
May | 23.73 | 9.99 |
June | 24.20 | 13.31 |
July | 24.09 | 15.02 |
August | 23.91 | 15.65 |
September | 23.87 | 13.43 |
October | 22.78 | 9.33 |
November | 21.86 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.92 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.20 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.18 |
February | 21.73 | 4.25 |
March | 21.95 | 5.90 |
April | 23.38 | 8.96 |
May | 23.72 | 9.99 |
June | 24.20 | 13.31 |
July | 24.08 | 15.02 |
August | 23.91 | 15.65 |
September | 23.87 | 13.43 |
October | 22.76 | 9.33 |
November | 21.85 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.91 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.20 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 4.18 |
February | 23.04 | 4.25 |
March | 23.00 | 5.90 |
April | 24.23 | 8.96 |
May | 24.24 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.27 | 15.65 |
September | 24.35 | 13.43 |
October | 24.05 | 9.33 |
November | 23.18 | 6.66 |
December | 22.04 | 4.10 |
Annual Sum or Average | 23.66 | 9.26 |
Minimum of Months | 22.04 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 4.18 |
February | 23.04 | 4.25 |
March | 23.01 | 5.90 |
April | 24.23 | 8.96 |
May | 24.24 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.27 | 15.65 |
September | 24.35 | 13.43 |
October | 24.05 | 9.33 |
November | 23.19 | 6.66 |
December | 22.05 | 4.10 |
Annual Sum or Average | 23.66 | 9.26 |
Minimum of Months | 22.05 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.94 | 4.18 |
February | 23.11 | 4.25 |
March | 23.27 | 5.90 |
April | 25.24 | 8.96 |
May | 25.43 | 9.99 |
June | 26.02 | 13.31 |
July | 26.08 | 15.02 |
August | 26.00 | 15.65 |
September | 25.79 | 13.43 |
October | 24.40 | 9.33 |
November | 23.17 | 6.66 |
December | 22.32 | 4.10 |
Annual Sum or Average | 24.49 | 9.26 |
Minimum of Months | 22.32 | 4.10 |
Maximum of Months | 26.08 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.53 | 4.18 |
February | 22.67 | 4.25 |
March | 22.73 | 5.90 |
April | 24.16 | 8.96 |
May | 24.15 | 9.99 |
June | 24.35 | 13.31 |
July | 24.31 | 15.02 |
August | 24.29 | 15.65 |
September | 24.32 | 13.43 |
October | 23.80 | 9.33 |
November | 22.74 | 6.66 |
December | 21.86 | 4.10 |
Annual Sum or Average | 23.50 | 9.26 |
Minimum of Months | 21.86 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.18 |
February | 21.76 | 4.25 |
March | 21.99 | 5.90 |
April | 23.62 | 8.96 |
May | 23.85 | 9.99 |
June | 24.27 | 13.31 |
July | 24.20 | 15.02 |
August | 24.11 | 15.65 |
September | 23.96 | 13.43 |
October | 22.79 | 9.33 |
November | 21.84 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.99 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.27 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 4.18 |
February | 22.61 | 4.25 |
March | 22.66 | 5.90 |
April | 24.16 | 8.96 |
May | 24.15 | 9.99 |
June | 24.34 | 13.31 |
July | 24.31 | 15.02 |
August | 24.31 | 15.65 |
September | 24.33 | 13.43 |
October | 23.76 | 9.33 |
November | 22.68 | 6.66 |
December | 21.87 | 4.10 |
Annual Sum or Average | 23.47 | 9.26 |
Minimum of Months | 21.87 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.72 | 4.25 |
March | 21.90 | 5.90 |
April | 23.63 | 8.96 |
May | 23.80 | 9.99 |
June | 24.21 | 13.31 |
July | 24.15 | 15.02 |
August | 24.09 | 15.65 |
September | 23.96 | 13.43 |
October | 22.66 | 9.33 |
November | 21.78 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.95 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.21 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.74 | 4.25 |
March | 22.03 | 5.90 |
April | 23.55 | 8.96 |
May | 23.85 | 9.99 |
June | 24.21 | 13.31 |
July | 24.09 | 15.02 |
August | 23.92 | 15.65 |
September | 23.89 | 13.43 |
October | 22.93 | 9.33 |
November | 21.90 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.97 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.21 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.74 | 4.25 |
March | 22.01 | 5.90 |
April | 23.56 | 8.96 |
May | 23.84 | 9.99 |
June | 24.21 | 13.31 |
July | 24.08 | 15.02 |
August | 23.91 | 15.65 |
September | 23.89 | 13.43 |
October | 22.91 | 9.33 |
November | 21.89 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.97 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.21 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 4.18 |
February | 23.15 | 4.25 |
March | 23.17 | 5.90 |
April | 24.27 | 8.96 |
May | 24.26 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.26 | 15.65 |
September | 24.35 | 13.43 |
October | 24.12 | 9.33 |
November | 23.30 | 6.66 |
December | 22.08 | 4.10 |
Annual Sum or Average | 23.72 | 9.26 |
Minimum of Months | 22.08 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 4.18 |
February | 23.15 | 4.25 |
March | 23.17 | 5.90 |
April | 24.27 | 8.96 |
May | 24.27 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.26 | 15.65 |
September | 24.35 | 13.43 |
October | 24.12 | 9.33 |
November | 23.30 | 6.66 |
December | 22.08 | 4.10 |
Annual Sum or Average | 23.72 | 9.26 |
Minimum of Months | 22.08 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.16 | 4.18 |
February | 23.31 | 4.25 |
March | 23.52 | 5.90 |
April | 25.50 | 8.96 |
May | 25.65 | 9.99 |
June | 26.15 | 13.31 |
July | 26.19 | 15.02 |
August | 26.11 | 15.65 |
September | 25.92 | 13.43 |
October | 24.65 | 9.33 |
November | 23.38 | 6.66 |
December | 22.47 | 4.10 |
Annual Sum or Average | 24.67 | 9.26 |
Minimum of Months | 22.47 | 4.10 |
Maximum of Months | 26.19 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 4.18 |
February | 22.71 | 4.25 |
March | 22.79 | 5.90 |
April | 24.19 | 8.96 |
May | 24.16 | 9.99 |
June | 24.35 | 13.31 |
July | 24.31 | 15.02 |
August | 24.29 | 15.65 |
September | 24.32 | 13.43 |
October | 23.84 | 9.33 |
November | 22.79 | 6.66 |
December | 21.87 | 4.10 |
Annual Sum or Average | 23.52 | 9.26 |
Minimum of Months | 21.87 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.18 |
February | 21.77 | 4.25 |
March | 22.03 | 5.90 |
April | 23.68 | 8.96 |
May | 23.87 | 9.99 |
June | 24.27 | 13.31 |
July | 24.20 | 15.02 |
August | 24.11 | 15.65 |
September | 23.97 | 13.43 |
October | 22.86 | 9.33 |
November | 21.86 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 23.01 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.27 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.52 | 4.18 |
February | 22.64 | 4.25 |
March | 22.72 | 5.90 |
April | 24.18 | 8.96 |
May | 24.15 | 9.99 |
June | 24.34 | 13.31 |
July | 24.31 | 15.02 |
August | 24.30 | 15.65 |
September | 24.33 | 13.43 |
October | 23.79 | 9.33 |
November | 22.72 | 6.66 |
December | 21.87 | 4.10 |
Annual Sum or Average | 23.49 | 9.26 |
Minimum of Months | 21.87 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.18 |
February | 21.73 | 4.25 |
March | 21.93 | 5.90 |
April | 23.69 | 8.96 |
May | 23.82 | 9.99 |
June | 24.22 | 13.31 |
July | 24.15 | 15.02 |
August | 24.08 | 15.65 |
September | 23.97 | 13.43 |
October | 22.72 | 9.33 |
November | 21.79 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.97 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 4.18 |
February | 21.76 | 4.25 |
March | 22.09 | 5.90 |
April | 23.65 | 8.96 |
May | 23.90 | 9.99 |
June | 24.22 | 13.31 |
July | 24.09 | 15.02 |
August | 23.92 | 15.65 |
September | 23.91 | 13.43 |
October | 23.03 | 9.33 |
November | 21.95 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 23.01 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 4.18 |
February | 21.76 | 4.25 |
March | 22.07 | 5.90 |
April | 23.65 | 8.96 |
May | 23.89 | 9.99 |
June | 24.22 | 13.31 |
July | 24.08 | 15.02 |
August | 23.92 | 15.65 |
September | 23.91 | 13.43 |
October | 23.01 | 9.33 |
November | 21.94 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 23.00 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.22 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 4.18 |
February | 23.22 | 4.25 |
March | 23.27 | 5.90 |
April | 24.29 | 8.96 |
May | 24.28 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.26 | 15.65 |
September | 24.35 | 13.43 |
October | 24.16 | 9.33 |
November | 23.36 | 6.66 |
December | 22.10 | 4.10 |
Annual Sum or Average | 23.75 | 9.26 |
Minimum of Months | 22.10 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 4.18 |
February | 23.21 | 4.25 |
March | 23.27 | 5.90 |
April | 24.29 | 8.96 |
May | 24.28 | 9.99 |
June | 24.34 | 13.31 |
July | 24.29 | 15.02 |
August | 24.26 | 15.65 |
September | 24.35 | 13.43 |
October | 24.16 | 9.33 |
November | 23.36 | 6.66 |
December | 22.11 | 4.10 |
Annual Sum or Average | 23.75 | 9.26 |
Minimum of Months | 22.11 | 4.10 |
Maximum of Months | 24.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.85 | 4.18 |
February | 23.99 | 4.25 |
March | 24.21 | 5.90 |
April | 26.17 | 8.96 |
May | 26.29 | 9.99 |
June | 26.76 | 13.31 |
July | 26.80 | 15.02 |
August | 26.72 | 15.65 |
September | 26.54 | 13.43 |
October | 25.33 | 9.33 |
November | 24.06 | 6.66 |
December | 23.14 | 4.10 |
Annual Sum or Average | 25.33 | 9.26 |
Minimum of Months | 23.14 | 4.10 |
Maximum of Months | 26.80 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.50 | 4.18 |
February | 22.62 | 4.25 |
March | 22.69 | 5.90 |
April | 24.15 | 8.96 |
May | 24.11 | 9.99 |
June | 24.33 | 13.31 |
July | 24.29 | 15.02 |
August | 24.27 | 15.65 |
September | 24.30 | 13.43 |
October | 23.76 | 9.33 |
November | 22.68 | 6.66 |
December | 21.85 | 4.10 |
Annual Sum or Average | 23.47 | 9.26 |
Minimum of Months | 21.85 | 4.10 |
Maximum of Months | 24.33 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.18 |
February | 21.75 | 4.25 |
March | 21.98 | 5.90 |
April | 23.59 | 8.96 |
May | 23.77 | 9.99 |
June | 24.23 | 13.31 |
July | 24.16 | 15.02 |
August | 24.05 | 15.65 |
September | 23.89 | 13.43 |
October | 22.74 | 9.33 |
November | 21.83 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.96 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.23 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.45 | 4.18 |
February | 22.56 | 4.25 |
March | 22.61 | 5.90 |
April | 24.15 | 8.96 |
May | 24.10 | 9.99 |
June | 24.31 | 13.31 |
July | 24.29 | 15.02 |
August | 24.28 | 15.65 |
September | 24.31 | 13.43 |
October | 23.71 | 9.33 |
November | 22.62 | 6.66 |
December | 21.85 | 4.10 |
Annual Sum or Average | 23.44 | 9.26 |
Minimum of Months | 21.85 | 4.10 |
Maximum of Months | 24.31 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.72 | 4.25 |
March | 21.89 | 5.90 |
April | 23.60 | 8.96 |
May | 23.71 | 9.99 |
June | 24.17 | 13.31 |
July | 24.10 | 15.02 |
August | 24.01 | 15.65 |
September | 23.89 | 13.43 |
October | 22.61 | 9.33 |
November | 21.77 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.91 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.17 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.18 |
February | 21.74 | 4.25 |
March | 22.02 | 5.90 |
April | 23.55 | 8.96 |
May | 23.79 | 9.99 |
June | 24.18 | 13.31 |
July | 24.04 | 15.02 |
August | 23.84 | 15.65 |
September | 23.83 | 13.43 |
October | 22.91 | 9.33 |
November | 21.90 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.94 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.18 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.18 |
February | 21.74 | 4.25 |
March | 22.01 | 5.90 |
April | 23.56 | 8.96 |
May | 23.78 | 9.99 |
June | 24.18 | 13.31 |
July | 24.03 | 15.02 |
August | 23.84 | 15.65 |
September | 23.83 | 13.43 |
October | 22.89 | 9.33 |
November | 21.89 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.94 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.18 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 4.18 |
February | 23.12 | 4.25 |
March | 23.16 | 5.90 |
April | 24.27 | 8.96 |
May | 24.24 | 9.99 |
June | 24.33 | 13.31 |
July | 24.27 | 15.02 |
August | 24.24 | 15.65 |
September | 24.33 | 13.43 |
October | 24.10 | 9.33 |
November | 23.26 | 6.66 |
December | 22.05 | 4.10 |
Annual Sum or Average | 23.70 | 9.26 |
Minimum of Months | 22.05 | 4.10 |
Maximum of Months | 24.33 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 4.18 |
February | 23.12 | 4.25 |
March | 23.16 | 5.90 |
April | 24.27 | 8.96 |
May | 24.24 | 9.99 |
June | 24.33 | 13.31 |
July | 24.27 | 15.02 |
August | 24.24 | 15.65 |
September | 24.34 | 13.43 |
October | 24.10 | 9.33 |
November | 23.26 | 6.66 |
December | 22.05 | 4.10 |
Annual Sum or Average | 23.70 | 9.26 |
Minimum of Months | 22.05 | 4.10 |
Maximum of Months | 24.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.16 | 4.18 |
February | 23.30 | 4.25 |
March | 23.52 | 5.90 |
April | 25.50 | 8.96 |
May | 25.61 | 9.99 |
June | 26.11 | 13.31 |
July | 26.15 | 15.02 |
August | 26.05 | 15.65 |
September | 25.87 | 13.43 |
October | 24.63 | 9.33 |
November | 23.36 | 6.66 |
December | 22.46 | 4.10 |
Annual Sum or Average | 24.65 | 9.26 |
Minimum of Months | 22.46 | 4.10 |
Maximum of Months | 26.15 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.44 | 4.18 |
February | 22.55 | 4.25 |
March | 22.61 | 5.90 |
April | 24.12 | 8.96 |
May | 24.06 | 9.99 |
June | 24.32 | 13.31 |
July | 24.28 | 15.02 |
August | 24.25 | 15.65 |
September | 24.28 | 13.43 |
October | 23.69 | 9.33 |
November | 22.60 | 6.66 |
December | 21.83 | 4.10 |
Annual Sum or Average | 23.42 | 9.26 |
Minimum of Months | 21.83 | 4.10 |
Maximum of Months | 24.32 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.18 |
February | 21.74 | 4.25 |
March | 21.94 | 5.90 |
April | 23.51 | 8.96 |
May | 23.68 | 9.99 |
June | 24.20 | 13.31 |
July | 24.13 | 15.02 |
August | 24.00 | 15.65 |
September | 23.83 | 13.43 |
October | 22.65 | 9.33 |
November | 21.81 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.92 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.20 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 4.18 |
February | 22.49 | 4.25 |
March | 22.53 | 5.90 |
April | 24.13 | 8.96 |
May | 24.06 | 9.99 |
June | 24.30 | 13.31 |
July | 24.27 | 15.02 |
August | 24.26 | 15.65 |
September | 24.29 | 13.43 |
October | 23.64 | 9.33 |
November | 22.53 | 6.66 |
December | 21.83 | 4.10 |
Annual Sum or Average | 23.40 | 9.26 |
Minimum of Months | 21.83 | 4.10 |
Maximum of Months | 24.30 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.71 | 4.25 |
March | 21.86 | 5.90 |
April | 23.52 | 8.96 |
May | 23.62 | 9.99 |
June | 24.14 | 13.31 |
July | 24.06 | 15.02 |
August | 23.96 | 15.65 |
September | 23.83 | 13.43 |
October | 22.52 | 9.33 |
November | 21.75 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.87 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.14 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.18 |
February | 21.73 | 4.25 |
March | 21.98 | 5.90 |
April | 23.47 | 8.96 |
May | 23.69 | 9.99 |
June | 24.15 | 13.31 |
July | 24.00 | 15.02 |
August | 23.78 | 15.65 |
September | 23.76 | 13.43 |
October | 22.79 | 9.33 |
November | 21.86 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.89 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.15 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.18 |
February | 21.73 | 4.25 |
March | 21.96 | 5.90 |
April | 23.47 | 8.96 |
May | 23.68 | 9.99 |
June | 24.15 | 13.31 |
July | 23.99 | 15.02 |
August | 23.77 | 15.65 |
September | 23.76 | 13.43 |
October | 22.77 | 9.33 |
November | 21.85 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.89 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.15 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 4.18 |
February | 23.03 | 4.25 |
March | 23.06 | 5.90 |
April | 24.25 | 8.96 |
May | 24.21 | 9.99 |
June | 24.32 | 13.31 |
July | 24.25 | 15.02 |
August | 24.22 | 15.65 |
September | 24.32 | 13.43 |
October | 24.05 | 9.33 |
November | 23.16 | 6.66 |
December | 22.01 | 4.10 |
Annual Sum or Average | 23.65 | 9.26 |
Minimum of Months | 22.01 | 4.10 |
Maximum of Months | 24.32 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 4.18 |
February | 23.03 | 4.25 |
March | 23.06 | 5.90 |
April | 24.25 | 8.96 |
May | 24.22 | 9.99 |
June | 24.32 | 13.31 |
July | 24.25 | 15.02 |
August | 24.22 | 15.65 |
September | 24.32 | 13.43 |
October | 24.05 | 9.33 |
November | 23.15 | 6.66 |
December | 22.02 | 4.10 |
Annual Sum or Average | 23.65 | 9.26 |
Minimum of Months | 22.02 | 4.10 |
Maximum of Months | 24.32 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 4.18 |
February | 23.14 | 4.25 |
March | 23.35 | 5.90 |
April | 25.35 | 8.96 |
May | 25.43 | 9.99 |
June | 25.99 | 13.31 |
July | 26.02 | 15.02 |
August | 25.92 | 15.65 |
September | 25.73 | 13.43 |
October | 24.45 | 9.33 |
November | 23.19 | 6.66 |
December | 22.32 | 4.10 |
Annual Sum or Average | 24.50 | 9.26 |
Minimum of Months | 22.32 | 4.10 |
Maximum of Months | 26.02 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 4.18 |
February | 22.48 | 4.25 |
March | 22.52 | 5.90 |
April | 24.09 | 8.96 |
May | 24.01 | 9.99 |
June | 24.30 | 13.31 |
July | 24.26 | 15.02 |
August | 24.24 | 15.65 |
September | 24.27 | 13.43 |
October | 23.60 | 9.33 |
November | 22.50 | 6.66 |
December | 21.82 | 4.10 |
Annual Sum or Average | 23.37 | 9.26 |
Minimum of Months | 21.82 | 4.10 |
Maximum of Months | 24.30 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.18 |
February | 21.74 | 4.25 |
March | 21.91 | 5.90 |
April | 23.44 | 8.96 |
May | 23.58 | 9.99 |
June | 24.17 | 13.31 |
July | 24.11 | 15.02 |
August | 23.96 | 15.65 |
September | 23.77 | 13.43 |
October | 22.55 | 9.33 |
November | 21.79 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.88 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.17 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 4.18 |
February | 22.42 | 4.25 |
March | 22.45 | 5.90 |
April | 24.10 | 8.96 |
May | 24.01 | 9.99 |
June | 24.28 | 13.31 |
July | 24.25 | 15.02 |
August | 24.25 | 15.65 |
September | 24.28 | 13.43 |
October | 23.55 | 9.33 |
November | 22.44 | 6.66 |
December | 21.82 | 4.10 |
Annual Sum or Average | 23.35 | 9.26 |
Minimum of Months | 21.82 | 4.10 |
Maximum of Months | 24.28 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.71 | 4.25 |
March | 21.84 | 5.90 |
April | 23.45 | 8.96 |
May | 23.52 | 9.99 |
June | 24.11 | 13.31 |
July | 24.02 | 15.02 |
August | 23.91 | 15.65 |
September | 23.77 | 13.43 |
October | 22.42 | 9.33 |
November | 21.74 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.83 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.18 |
February | 21.72 | 4.25 |
March | 21.94 | 5.90 |
April | 23.38 | 8.96 |
May | 23.58 | 9.99 |
June | 24.12 | 13.31 |
July | 23.97 | 15.02 |
August | 23.72 | 15.65 |
September | 23.69 | 13.43 |
October | 22.66 | 9.33 |
November | 21.83 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.84 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.12 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.18 |
February | 21.72 | 4.25 |
March | 21.93 | 5.90 |
April | 23.38 | 8.96 |
May | 23.57 | 9.99 |
June | 24.12 | 13.31 |
July | 23.96 | 15.02 |
August | 23.72 | 15.65 |
September | 23.69 | 13.43 |
October | 22.64 | 9.33 |
November | 21.83 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.84 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.12 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 4.18 |
February | 22.93 | 4.25 |
March | 22.94 | 5.90 |
April | 24.23 | 8.96 |
May | 24.18 | 9.99 |
June | 24.31 | 13.31 |
July | 24.24 | 15.02 |
August | 24.20 | 15.65 |
September | 24.31 | 13.43 |
October | 23.98 | 9.33 |
November | 23.04 | 6.66 |
December | 21.98 | 4.10 |
Annual Sum or Average | 23.60 | 9.26 |
Minimum of Months | 21.98 | 4.10 |
Maximum of Months | 24.31 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 4.18 |
February | 22.92 | 4.25 |
March | 22.94 | 5.90 |
April | 24.23 | 8.96 |
May | 24.18 | 9.99 |
June | 24.31 | 13.31 |
July | 24.24 | 15.02 |
August | 24.20 | 15.65 |
September | 24.31 | 13.43 |
October | 23.98 | 9.33 |
November | 23.03 | 6.66 |
December | 21.98 | 4.10 |
Annual Sum or Average | 23.60 | 9.26 |
Minimum of Months | 21.98 | 4.10 |
Maximum of Months | 24.31 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | 4.18 |
February | 23.04 | 4.25 |
March | 23.24 | 5.90 |
April | 25.26 | 8.96 |
May | 25.32 | 9.99 |
June | 25.93 | 13.31 |
July | 25.98 | 15.02 |
August | 25.86 | 15.65 |
September | 25.65 | 13.43 |
October | 24.30 | 9.33 |
November | 23.07 | 6.66 |
December | 22.25 | 4.10 |
Annual Sum or Average | 24.41 | 9.26 |
Minimum of Months | 22.25 | 4.10 |
Maximum of Months | 25.98 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.18 |
February | 22.37 | 4.25 |
March | 22.40 | 5.90 |
April | 24.00 | 8.96 |
May | 23.91 | 9.99 |
June | 24.27 | 13.31 |
July | 24.24 | 15.02 |
August | 24.21 | 15.65 |
September | 24.23 | 13.43 |
October | 23.43 | 9.33 |
November | 22.35 | 6.66 |
December | 21.80 | 4.10 |
Annual Sum or Average | 23.29 | 9.26 |
Minimum of Months | 21.80 | 4.10 |
Maximum of Months | 24.27 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.73 | 4.25 |
March | 21.88 | 5.90 |
April | 23.32 | 8.96 |
May | 23.45 | 9.99 |
June | 24.13 | 13.31 |
July | 24.07 | 15.02 |
August | 23.91 | 15.65 |
September | 23.67 | 13.43 |
October | 22.41 | 9.33 |
November | 21.77 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.82 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.13 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.18 |
February | 22.31 | 4.25 |
March | 22.33 | 5.90 |
April | 24.02 | 8.96 |
May | 23.92 | 9.99 |
June | 24.26 | 13.31 |
July | 24.23 | 15.02 |
August | 24.23 | 15.65 |
September | 24.24 | 13.43 |
October | 23.38 | 9.33 |
November | 22.29 | 6.66 |
December | 21.80 | 4.10 |
Annual Sum or Average | 23.27 | 9.26 |
Minimum of Months | 21.80 | 4.10 |
Maximum of Months | 24.26 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.18 |
February | 21.70 | 4.25 |
March | 21.81 | 5.90 |
April | 23.33 | 8.96 |
May | 23.38 | 9.99 |
June | 24.06 | 13.31 |
July | 23.98 | 15.02 |
August | 23.85 | 15.65 |
September | 23.66 | 13.43 |
October | 22.30 | 9.33 |
November | 21.73 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.77 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.06 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.18 |
February | 21.71 | 4.25 |
March | 21.89 | 5.90 |
April | 23.24 | 8.96 |
May | 23.43 | 9.99 |
June | 24.08 | 13.31 |
July | 23.94 | 15.02 |
August | 23.68 | 15.65 |
September | 23.58 | 13.43 |
October | 22.48 | 9.33 |
November | 21.79 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.77 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.08 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.18 |
February | 21.71 | 4.25 |
March | 21.88 | 5.90 |
April | 23.25 | 8.96 |
May | 23.42 | 9.99 |
June | 24.07 | 13.31 |
July | 23.93 | 15.02 |
August | 23.67 | 15.65 |
September | 23.58 | 13.43 |
October | 22.46 | 9.33 |
November | 21.78 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.77 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 24.07 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 4.18 |
February | 22.73 | 4.25 |
March | 22.74 | 5.90 |
April | 24.15 | 8.96 |
May | 24.10 | 9.99 |
June | 24.29 | 13.31 |
July | 24.22 | 15.02 |
August | 24.18 | 15.65 |
September | 24.28 | 13.43 |
October | 23.81 | 9.33 |
November | 22.81 | 6.66 |
December | 21.92 | 4.10 |
Annual Sum or Average | 23.49 | 9.26 |
Minimum of Months | 21.92 | 4.10 |
Maximum of Months | 24.29 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 4.18 |
February | 22.73 | 4.25 |
March | 22.74 | 5.90 |
April | 24.16 | 8.96 |
May | 24.10 | 9.99 |
June | 24.29 | 13.31 |
July | 24.22 | 15.02 |
August | 24.18 | 15.65 |
September | 24.29 | 13.43 |
October | 23.81 | 9.33 |
November | 22.81 | 6.66 |
December | 21.92 | 4.10 |
Annual Sum or Average | 23.49 | 9.26 |
Minimum of Months | 21.92 | 4.10 |
Maximum of Months | 24.29 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 4.18 |
February | 22.85 | 4.25 |
March | 23.06 | 5.90 |
April | 25.10 | 8.96 |
May | 25.16 | 9.99 |
June | 25.88 | 13.31 |
July | 25.95 | 15.02 |
August | 25.82 | 15.65 |
September | 25.54 | 13.43 |
October | 24.06 | 9.33 |
November | 22.85 | 6.66 |
December | 22.09 | 4.10 |
Annual Sum or Average | 24.26 | 9.26 |
Minimum of Months | 22.09 | 4.10 |
Maximum of Months | 25.95 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.13 | 4.18 |
February | 22.29 | 4.25 |
March | 22.36 | 5.90 |
April | 23.48 | 8.96 |
May | 23.45 | 9.99 |
June | 24.01 | 13.31 |
July | 24.06 | 15.02 |
August | 24.04 | 15.65 |
September | 23.89 | 13.43 |
October | 22.98 | 9.33 |
November | 22.20 | 6.66 |
December | 21.84 | 4.10 |
Annual Sum or Average | 23.06 | 9.26 |
Minimum of Months | 21.84 | 4.10 |
Maximum of Months | 24.06 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.18 |
February | 21.77 | 4.25 |
March | 21.94 | 5.90 |
April | 23.05 | 8.96 |
May | 23.11 | 9.99 |
June | 23.82 | 13.31 |
July | 23.84 | 15.02 |
August | 23.66 | 15.65 |
September | 23.30 | 13.43 |
October | 22.31 | 9.33 |
November | 21.77 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.67 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.84 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 4.18 |
February | 22.26 | 4.25 |
March | 22.32 | 5.90 |
April | 23.52 | 8.96 |
May | 23.47 | 9.99 |
June | 23.99 | 13.31 |
July | 24.03 | 15.02 |
August | 24.02 | 15.65 |
September | 23.90 | 13.43 |
October | 22.94 | 9.33 |
November | 22.17 | 6.66 |
December | 21.85 | 4.10 |
Annual Sum or Average | 23.05 | 9.26 |
Minimum of Months | 21.85 | 4.10 |
Maximum of Months | 24.03 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.71 | 4.25 |
March | 21.85 | 5.90 |
April | 23.11 | 8.96 |
May | 23.08 | 9.99 |
June | 23.73 | 13.31 |
July | 23.73 | 15.02 |
August | 23.58 | 15.65 |
September | 23.29 | 13.43 |
October | 22.25 | 9.33 |
November | 21.73 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.63 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.73 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.18 |
February | 21.71 | 4.25 |
March | 21.88 | 5.90 |
April | 22.97 | 8.96 |
May | 23.09 | 9.99 |
June | 23.79 | 13.31 |
July | 23.74 | 15.02 |
August | 23.47 | 15.65 |
September | 23.22 | 13.43 |
October | 22.27 | 9.33 |
November | 21.75 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.61 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.79 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.18 |
February | 21.71 | 4.25 |
March | 21.88 | 5.90 |
April | 22.99 | 8.96 |
May | 23.09 | 9.99 |
June | 23.79 | 13.31 |
July | 23.73 | 15.02 |
August | 23.47 | 15.65 |
September | 23.23 | 13.43 |
October | 22.27 | 9.33 |
November | 21.75 | 6.66 |
December | 21.70 | 4.10 |
Annual Sum or Average | 22.61 | 9.26 |
Minimum of Months | 21.70 | 4.10 |
Maximum of Months | 23.79 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 4.18 |
February | 22.44 | 4.25 |
March | 22.53 | 5.90 |
April | 23.66 | 8.96 |
May | 23.67 | 9.99 |
June | 24.11 | 13.31 |
July | 24.11 | 15.02 |
August | 24.08 | 15.65 |
September | 24.05 | 13.43 |
October | 23.28 | 9.33 |
November | 22.45 | 6.66 |
December | 21.91 | 4.10 |
Annual Sum or Average | 23.22 | 9.26 |
Minimum of Months | 21.91 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 4.18 |
February | 22.44 | 4.25 |
March | 22.53 | 5.90 |
April | 23.66 | 8.96 |
May | 23.67 | 9.99 |
June | 24.11 | 13.31 |
July | 24.11 | 15.02 |
August | 24.08 | 15.65 |
September | 24.05 | 13.43 |
October | 23.28 | 9.33 |
November | 22.45 | 6.66 |
December | 21.91 | 4.10 |
Annual Sum or Average | 23.22 | 9.26 |
Minimum of Months | 21.91 | 4.10 |
Maximum of Months | 24.11 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 4.18 |
February | 22.74 | 4.25 |
March | 23.05 | 5.90 |
April | 25.22 | 8.96 |
May | 25.34 | 9.99 |
June | 26.26 | 13.31 |
July | 26.43 | 15.02 |
August | 26.25 | 15.65 |
September | 25.73 | 13.43 |
October | 23.98 | 9.33 |
November | 22.73 | 6.66 |
December | 21.97 | 4.10 |
Annual Sum or Average | 24.35 | 9.26 |
Minimum of Months | 21.97 | 4.10 |
Maximum of Months | 26.43 | 15.65 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:14
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.220591E+12 | 123361.463 | 10-JAN-18:15 | 22204.399 | 56867.515 | 18311.893 | 12774.868 | 0.000 | 10720.100 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.196284E+12 | 117594.379 | 01-FEB-18:00 | 22204.399 | 56867.515 | 18311.893 | 7007.532 | 0.000 | 10720.100 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.208419E+12 | 113989.349 | 03-MAR-18:00 | 22204.399 | 56867.515 | 18311.893 | 3402.502 | 0.000 | 10720.100 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.209383E+12 | 148194.327 | 30-APR-17:15 | 22204.399 | 56867.515 | 18311.893 | 0.000 | 46820.362 | 0.000 | 1337.052 | 1507.470 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.210783E+12 | 131530.178 | 22-MAY-16:15 | 18221.747 | 56933.809 | 18311.893 | 0.000 | 34215.226 | 0.000 | 1337.052 | 1362.147 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.216528E+12 | 156163.154 | 13-JUN-17:15 | 22204.399 | 56867.515 | 18311.893 | 0.000 | 54432.104 | 0.000 | 1337.052 | 1864.556 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.222774E+12 | 155770.796 | 22-JUL-19:00 | 25049.151 | 49704.829 | 18311.893 | 0.000 | 47962.950 | 10720.100 | 1337.052 | 1739.250 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.219756E+12 | 151192.922 | 14-AUG-16:30 | 18221.747 | 56933.809 | 18311.893 | 0.000 | 53488.027 | 0.000 | 1337.052 | 1751.953 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.216068E+12 | 140866.231 | 11-SEP-17:15 | 22204.399 | 56867.515 | 18311.893 | 0.000 | 39481.639 | 0.000 | 1337.052 | 1518.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.211635E+12 | 126941.955 | 03-OCT-17:00 | 22204.399 | 56867.515 | 18311.893 | 0.000 | 15749.770 | 10720.100 | 1337.052 | 605.337 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.208346E+12 | 119782.024 | 29-NOV-18:15 | 22204.399 | 56867.515 | 18311.893 | 9195.429 | 0.000 | 10720.100 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.231032E+12 | 126349.941 | 02-DEC-18:15 | 22204.399 | 56867.515 | 18311.893 | 15763.347 | 0.000 | 10720.100 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.257160E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.196284E+12 | 113989.349 | 18221.747 | 49704.829 | 18311.893 | 0.000 | 0.000 | 0.000 | 1337.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.231032E+12 | 156163.154 | 25049.151 | 56933.809 | 18311.893 | 15763.347 | 54432.104 | 10720.100 | 1337.052 | 1864.556 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:14
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.157949E+12 | 166210.440 | 10-JAN-06:45 | 0.000 | 0.000 | 0.000 | 166210.440 | 84193.772 | 84193.772 | 82016.668 |
February | 0.136473E+12 | 141967.037 | 17-FEB-06:00 | 0.000 | 0.000 | 0.000 | 141967.037 | 85123.317 | 85123.317 | 56843.721 |
March | 0.129355E+12 | 118637.868 | 31-MAR-07:45 | 0.000 | 0.000 | 0.000 | 118637.868 | 85680.118 | 85680.118 | 32957.750 |
April | 0.103573E+12 | 95194.146 | 01-APR-05:45 | 0.000 | 0.000 | 0.000 | 95194.146 | 83498.975 | 83498.975 | 11695.170 |
May | 0.103780E+12 | 86144.601 | 02-MAY-06:45 | 0.000 | 0.000 | 0.000 | 86144.601 | 86144.601 | 86144.601 | 0.000 |
June | 0.977232E+11 | 85068.374 | 04-JUN-06:00 | 0.000 | 0.000 | 0.000 | 85068.374 | 85068.374 | 85068.374 | 0.000 |
July | 0.988918E+11 | 84288.515 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 84288.515 | 84288.515 | 84288.515 | 0.000 |
August | 0.981004E+11 | 83777.299 | 29-AUG-06:00 | 0.000 | 0.000 | 0.000 | 83777.299 | 83777.299 | 83777.299 | 0.000 |
September | 0.956971E+11 | 84241.368 | 30-SEP-06:45 | 0.000 | 0.000 | 0.000 | 84241.368 | 84241.368 | 84241.368 | 0.000 |
October | 0.102278E+12 | 101917.528 | 28-OCT-06:00 | 0.000 | 0.000 | 0.000 | 101917.528 | 85071.418 | 85071.418 | 16846.110 |
November | 0.130952E+12 | 144040.765 | 29-NOV-07:45 | 0.000 | 0.000 | 0.000 | 144040.765 | 86115.273 | 86115.273 | 57925.492 |
December | 0.195287E+12 | 162067.250 | 28-DEC-07:15 | 0.000 | 0.000 | 0.000 | 162067.250 | 84726.338 | 84726.338 | 77340.912 |
Annual Sum or Average | 0.145006E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.956971E+11 | 83777.299 | 0.000 | 0.000 | 0.000 | 83777.299 | 83498.975 | 83498.975 | 0.000 | |
Maximum of Months | 0.195287E+12 | 166210.440 | 0.000 | 0.000 | 0.000 | 166210.440 | 86144.601 | 86144.601 | 82016.668 |