Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Honolulu Intl Arpt HI USA TMY3 WMO#=911820

Simulation Timestamp: 2018-10-19 09:40:04


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4677.93 596.94 662.61
Net Site Energy 4677.93 596.94 662.61
Total Source Energy 13118.38 1674.02 1858.16
Net Source Energy 13118.38 1674.02 1858.16


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1427.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.75 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 578.08 0.00 0.00 0.00 0.00 0.00
Pumps 55.02 0.00 0.00 0.00 0.00 0.00
Heat Rejection 65.97 0.00 0.00 0.00 0.00 3577.33
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 814.51 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3863.42 814.51 0.00 0.00 0.00 8355.85
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1427.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.75 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 578.08 0.00 0.00 0.00 0.00 0.00
Pumps General 55.02 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 65.97 0.00 0.00 0.00 0.00 3577.33
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 814.51 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.88 0.00 0.00 0.00 0.00 0.00
HVAC 301.19 115.37 0.00 0.00 0.00 1.18
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 547.23 115.37 0.00 0.00 0.00 1.18


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.67 0.00 0.00 0.00 0.00 0.00
HVAC 271.34 103.94 0.00 0.00 0.00 1.07
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 493.00 103.94 0.00 0.00 0.00 1.07


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3863.42 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3863.42 100.00
     
Total On-Site and Utility Electric Sources 3863.42 100.00
Total Electricity End Uses 3863.42 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8355.85 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8355.85 100.00
Total Water End Uses 8355.85 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1598.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 4317.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Latitude [deg] 21.32
Longitude [deg] -157.9
Elevation [m] 2.00
Time Zone -10.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 15-SEP-18:45 02-JAN-07:00 - - - 21-JUN-06:00
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 77786.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51564.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 18330.67 0.00 0.00 0.00 0.00 0.00
Pumps 1760.93 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3126.26 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 76144.64 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 189352.70 76144.64 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 77786.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 51564.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 18330.67 0.00 0.00 0.00 0.00 0.00
Pumps General 1760.93 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 3126.26 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 76144.64 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 4520.20 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 534.42 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1830.77 0.00 0.00 0.00 0.00
Pumps 174.24 0.00 0.00 0.00 0.00
Heat Rejection 208.93 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 882.93 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 12235.45 882.93 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 640.26 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.70 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 259.32 0.00 0.00 0.00 0.00
Pumps 24.68 0.00 0.00 0.00 0.00
Heat Rejection 29.59 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 125.06 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1733.09 125.06 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00
Cooling 640.26 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.70 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 259.32 0.00 0.00 0.00 0.00
Pumps 24.68 0.00 0.00 0.00 0.00
Heat Rejection 29.59 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 125.06 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1733.09 125.06 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 16.20 0.00 16.20 Wetbulb [C] 1.90 320.00
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 32.20 7.10 23.30 Wetbulb [C] 6.70 60.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 5.778 0.306 0.155     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 5.778 0.306 0.155              
North Total or Average           423.59 5.778 0.306 0.155              
Non-North Total or Average           726.80 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.86 83.86 168.75
Exterior Lighting Total 10720.10           168.75



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 310768.91 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 248615.13      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4306.67 2968.21 1338.46 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4282.46 2948.86 1333.60 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   5280.69 3616.64 1664.05 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3471.04 2335.55 1135.48 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2357.79 1513.88 843.91 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2333.57 1495.95 837.62 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2446.75 1571.03 875.72 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2513.57 1621.17 892.39 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5064.20 3513.14 1551.07 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5004.91 3466.73 1538.19 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4461.34 3054.29 1407.04 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4058.18 2749.92 1308.27 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2827.09 1849.01 978.08 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2807.62 1834.48 973.13 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2928.11 1917.26 1010.85 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2951.76 1935.27 1016.49 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5105.10 3521.58 1583.53 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5050.72 3479.07 1571.65 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4287.81 2900.08 1387.73 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4102.06 2761.79 1340.27 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2884.62 1881.84 1002.78 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2865.15 1867.36 997.79 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2988.64 1952.33 1036.31 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2999.25 1960.42 1038.82 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5146.84 3536.72 1610.12 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5091.99 3493.94 1598.05 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4294.87 2890.20 1404.67 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4125.86 2765.06 1360.80 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2924.92 1904.40 1020.52 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2905.43 1889.94 1015.49 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3029.25 1975.05 1054.20 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3037.74 1981.53 1056.21 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5213.92 3574.54 1639.37 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5159.64 3532.27 1627.37 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4348.09 2918.47 1429.63 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4178.83 2793.39 1385.44 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2989.84 1946.79 1043.05 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2970.35 1932.35 1038.00 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3093.37 2016.93 1076.44 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3101.36 2023.03 1078.33 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5190.44 3545.14 1645.29 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5134.26 3501.49 1632.77 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4315.31 2883.47 1431.85 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4142.04 2755.75 1386.29 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2963.54 1922.00 1041.54 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2944.07 1907.64 1036.44 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3068.51 1992.88 1075.63 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3076.29 1998.81 1077.48 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5195.90 3539.43 1656.47 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5139.42 3495.62 1643.80 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4312.70 2872.77 1439.92 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4137.04 2743.57 1393.48 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2966.97 1920.13 1046.84 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2947.53 1905.82 1041.71 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3072.02 1990.91 1081.12 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3079.64 1996.69 1082.94 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5217.05 3546.79 1670.25 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5160.18 3502.75 1657.43 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4329.37 2877.19 1452.17 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4148.07 2744.45 1403.62 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2986.15 1930.47 1055.68 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2966.77 1916.22 1050.55 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3090.87 2000.92 1089.95 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3098.35 2006.60 1091.75 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5337.38 3630.47 1706.91 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5277.37 3584.01 1693.36 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4394.51 2919.21 1475.30 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4203.44 2779.23 1424.21 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3088.11 2002.50 1085.61 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3068.64 1988.17 1080.48 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3170.07 2056.64 1113.43 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3179.52 2063.40 1116.13 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5937.57 4081.72 1855.85 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5863.78 4024.88 1838.90 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4962.75 3340.77 1621.99 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4715.42 3156.36 1559.06 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3466.69 2282.32 1184.37 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3428.46 2253.76 1174.69 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3829.51 2549.24 1280.27 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3835.97 2554.29 1281.68 0.67 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4306.67 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   4282.46 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   5280.69 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   3471.04 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2357.79 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2333.57 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2446.75 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2513.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5064.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5004.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4461.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4058.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2827.09 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2807.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2928.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2951.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5105.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5050.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4287.81 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4102.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2884.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2865.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2988.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2999.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5146.84 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5091.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4294.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4125.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2924.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2905.43 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3029.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3037.74 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5213.92 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   5159.64 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4348.09 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   4178.83 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2989.84 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2970.35 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3093.37 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3101.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5190.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5134.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4315.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4142.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2963.54 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2944.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3068.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3076.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5195.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5139.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4312.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4137.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2966.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2947.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3072.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3079.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5217.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5160.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4329.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4148.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2986.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2966.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3090.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3098.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5337.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5277.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4394.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4203.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3088.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3068.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3170.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3179.52 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5937.57 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   5863.78 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4962.75 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   4715.42 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3466.69 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3428.46 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3829.51 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3835.97 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   1097.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   747.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   747.30 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 271.99 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 270.12 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.64 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 209.00 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 127.34 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 125.54 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 131.08 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 136.13 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.69 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 320.08 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.52 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 248.52 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 159.83 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 158.36 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.63 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.46 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.96 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 319.75 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.31 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 247.89 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 162.26 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 160.80 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.30 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.12 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.31 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 320.07 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.16 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 247.08 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.87 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 162.42 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.93 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.59 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 327.19 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.00 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.09 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 249.03 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.61 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.16 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.62 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 173.24 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.39 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 319.06 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.76 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 244.43 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.64 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.20 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.73 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.34 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 322.09 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 317.75 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.98 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.52 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.05 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 162.62 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.13 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.72 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 322.19 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 317.83 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.63 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.00 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.73 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.31 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.78 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.36 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 330.08 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 325.47 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.31 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 244.94 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 171.66 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.23 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.09 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.74 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 375.14 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 369.50 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 300.18 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.17 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 199.28 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.41 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 224.49 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.01 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0068 1724.00 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2583.51 3100.22 0.202 0.243 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
G NW APARTMENT 2565.78 3078.94 0.201 0.241 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
OFFICE 3121.62 3745.94 0.245 0.293 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 30.57 0.01435
G NE APARTMENT 1985.13 2382.16 0.155 0.187 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:30:00 30.03 0.01435
G N1 APARTMENT 1209.58 1451.50 0.095 0.114 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
G N2 APARTMENT 1192.44 1430.93 0.093 0.112 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
G S1 APARTMENT 1245.13 1494.15 0.098 0.117 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
G S2 APARTMENT 1293.10 1551.72 0.101 0.122 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 32.20 0.01435
F2 SW APARTMENT 3084.00 3700.80 0.242 0.290 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F2 NW APARTMENT 3040.21 3648.25 0.238 0.286 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F2 SE APARTMENT 2645.41 3174.49 0.207 0.249 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
F2 NE APARTMENT 2360.48 2832.58 0.185 0.222 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:30:00 30.03 0.01435
F2 N1 APARTMENT 1518.14 1821.77 0.119 0.143 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F2 N2 APARTMENT 1504.25 1805.10 0.118 0.141 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F2 S1 APARTMENT 1563.78 1876.53 0.122 0.147 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F2 S2 APARTMENT 1581.15 1897.38 0.124 0.149 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F3 SW APARTMENT 3077.02 3692.43 0.241 0.289 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F3 NW APARTMENT 3037.02 3644.42 0.238 0.285 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F3 SE APARTMENT 2481.91 2978.29 0.194 0.233 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
F3 NE APARTMENT 2354.42 2825.30 0.184 0.221 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F3 N1 APARTMENT 1541.19 1849.43 0.121 0.145 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F3 N2 APARTMENT 1527.36 1832.84 0.120 0.144 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F3 S1 APARTMENT 1589.04 1906.84 0.124 0.149 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F3 S2 APARTMENT 1596.88 1916.26 0.125 0.150 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F4 SW APARTMENT 3080.34 3696.41 0.241 0.290 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F4 NW APARTMENT 3040.08 3648.09 0.238 0.286 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F4 SE APARTMENT 2461.41 2953.70 0.193 0.231 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
F4 NE APARTMENT 2346.70 2816.04 0.184 0.221 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F4 N1 APARTMENT 1556.51 1867.81 0.122 0.146 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F4 N2 APARTMENT 1542.71 1851.26 0.121 0.145 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F4 S1 APARTMENT 1604.53 1925.43 0.126 0.151 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F4 S2 APARTMENT 1610.82 1932.98 0.126 0.151 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
M SW APARTMENT 3107.60 3729.12 0.243 0.292 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
M NW APARTMENT 3067.84 3681.41 0.240 0.288 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
M SE APARTMENT 2479.72 2975.66 0.194 0.233 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
M NE APARTMENT 2365.13 2838.16 0.185 0.222 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
M N1 APARTMENT 1592.06 1910.47 0.125 0.150 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
M N2 APARTMENT 1578.29 1893.95 0.124 0.148 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
M S1 APARTMENT 1639.56 1967.47 0.128 0.154 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
M S2 APARTMENT 1645.48 1974.57 0.129 0.155 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F6 SW APARTMENT 3071.46 3685.76 0.241 0.289 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F6 NW APARTMENT 3030.36 3636.44 0.237 0.285 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F6 SE APARTMENT 2438.50 2926.20 0.191 0.229 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
F6 NE APARTMENT 2321.47 2785.76 0.182 0.218 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F6 N1 APARTMENT 1563.84 1876.61 0.122 0.147 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F6 N2 APARTMENT 1550.17 1860.20 0.121 0.146 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F6 S1 APARTMENT 1612.12 1934.54 0.126 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F6 S2 APARTMENT 1617.87 1941.45 0.127 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F7 SW APARTMENT 3059.11 3670.93 0.240 0.288 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F7 NW APARTMENT 3017.87 3621.44 0.236 0.284 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F7 SE APARTMENT 2421.62 2905.95 0.190 0.228 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 30.74 0.01435
F7 NE APARTMENT 2303.24 2763.88 0.180 0.217 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F7 N1 APARTMENT 1558.21 1869.85 0.122 0.146 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F7 N2 APARTMENT 1544.60 1853.52 0.121 0.145 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F7 S1 APARTMENT 1606.40 1927.68 0.126 0.151 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F7 S2 APARTMENT 1612.02 1934.43 0.126 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F8 SW APARTMENT 3060.06 3672.08 0.240 0.288 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F8 NW APARTMENT 3018.61 3622.33 0.236 0.284 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F8 SE APARTMENT 2418.31 2901.97 0.189 0.227 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 30.92 0.01435
F8 NE APARTMENT 2298.27 2757.92 0.180 0.216 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F8 N1 APARTMENT 1564.68 1877.62 0.123 0.147 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F8 N2 APARTMENT 1551.14 1861.37 0.121 0.146 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F8 S1 APARTMENT 1612.56 1935.08 0.126 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F8 S2 APARTMENT 1618.09 1941.70 0.127 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
F9 SW APARTMENT 3134.93 3761.92 0.246 0.295 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
F9 NW APARTMENT 3091.14 3709.37 0.242 0.291 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 30.67 0.01435
F9 SE APARTMENT 2453.19 2943.83 0.192 0.231 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 30.92 0.01435
F9 NE APARTMENT 2326.25 2791.50 0.182 0.219 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:45:00 30.30 0.01435
F9 N1 APARTMENT 1630.50 1956.61 0.128 0.153 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F9 N2 APARTMENT 1616.88 1940.26 0.127 0.152 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
F9 S1 APARTMENT 1662.98 1995.58 0.130 0.156 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 32.20 0.01435
F9 S2 APARTMENT 1669.19 2003.02 0.131 0.157 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
T SW APARTMENT 3562.70 4275.24 0.279 0.335 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 31.03 0.01435
T NW APARTMENT 3509.26 4211.12 0.275 0.330 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
T SE APARTMENT 2850.75 3420.90 0.223 0.268 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:45:00 31.10 0.01435
T NE APARTMENT 2679.75 3215.70 0.210 0.252 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 30.57 0.01435
T N1 APARTMENT 1892.82 2271.39 0.148 0.178 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
T N2 APARTMENT 1865.54 2238.65 0.146 0.175 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
T S1 APARTMENT 2132.14 2558.57 0.167 0.200 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435
T S2 APARTMENT 2137.11 2564.53 0.167 0.201 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 32.20 0.01435


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 169.78 203.74 0.008 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
G NW APARTMENT 166.90 200.28 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
OFFICE 433.07 519.69 0.019 0.038 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 18:45:00 16.20 0.01152
G NE APARTMENT 167.15 200.57 0.007 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
G N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
G S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F2 SW APARTMENT 103.11 123.74 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F2 NW APARTMENT 102.39 122.86 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F2 SE APARTMENT 127.58 153.10 0.006 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F2 NE APARTMENT 102.77 123.32 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F2 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F2 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F2 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F2 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F3 SW APARTMENT 58.03 69.64 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F3 NW APARTMENT 56.60 67.93 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F3 SE APARTMENT 63.81 76.57 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F3 NE APARTMENT 57.11 68.53 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F3 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F3 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F3 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F3 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F4 SW APARTMENT 30.10 36.12 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F4 NW APARTMENT 28.24 33.89 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F4 SE APARTMENT 32.11 38.53 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F4 NE APARTMENT 28.84 34.61 0.001 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F4 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F4 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F4 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F4 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M SW APARTMENT 0.28 0.34 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
M NW APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M SE APARTMENT 0.99 1.19 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
M NE APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
M S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F6 SW APARTMENT 45.99 55.19 0.002 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F6 NW APARTMENT 44.65 53.58 0.002 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F6 SE APARTMENT 46.62 55.94 0.002 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F6 NE APARTMENT 45.11 54.13 0.002 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F6 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F6 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F6 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F6 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F7 SW APARTMENT 80.46 96.56 0.004 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F7 NW APARTMENT 79.53 95.43 0.004 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F7 SE APARTMENT 80.83 97.00 0.004 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F7 NE APARTMENT 79.85 95.81 0.004 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F7 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F7 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F7 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F7 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F8 SW APARTMENT 114.37 137.25 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F8 NW APARTMENT 113.36 136.03 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F8 SE APARTMENT 114.61 137.54 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F8 NE APARTMENT 113.58 136.30 0.005 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F8 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F8 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F8 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F8 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F9 SW APARTMENT 180.60 216.72 0.008 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F9 NW APARTMENT 179.11 214.94 0.008 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F9 SE APARTMENT 180.76 216.92 0.008 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F9 NE APARTMENT 179.27 215.12 0.008 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
F9 N1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F9 N2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F9 S1 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
F9 S2 APARTMENT 0.00 0.00 0.000 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
T SW APARTMENT 347.29 416.75 0.015 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T NW APARTMENT 348.67 418.41 0.016 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T SE APARTMENT 347.38 416.85 0.015 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T NE APARTMENT 348.76 418.51 0.016 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T N1 APARTMENT 69.41 83.29 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T N2 APARTMENT 69.42 83.30 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T S1 APARTMENT 66.09 79.30 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152
T S2 APARTMENT 66.09 79.31 0.003 0.026 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 16.20 0.01152


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.24 0.24 0.03 0.03
AIRLOOP G NW 0.24 0.24 0.03 0.03
AIRLOOP OFFICE 0.29 0.29 0.04 0.04
AIRLOOP G NE 0.19 0.19 0.03 0.03
AIRLOOP G N1 0.11 0.11 0.03 0.03
AIRLOOP G N2 0.11 0.11 0.03 0.03
AIRLOOP G S1 0.12 0.12 0.03 0.03
AIRLOOP G S2 0.12 0.12 0.03 0.03
AIRLOOP F2 SW 0.29 0.29 0.03 0.03
AIRLOOP F2 NW 0.29 0.29 0.03 0.03
AIRLOOP F2 SE 0.25 0.25 0.03 0.03
AIRLOOP F2 NE 0.22 0.22 0.03 0.03
AIRLOOP F2 N1 0.14 0.14 0.03 0.03
AIRLOOP F2 N2 0.14 0.14 0.03 0.03
AIRLOOP F2 S1 0.15 0.15 0.03 0.03
AIRLOOP F2 S2 0.15 0.15 0.03 0.03
AIRLOOP F3 SW 0.29 0.29 0.03 0.03
AIRLOOP F3 NW 0.29 0.29 0.03 0.03
AIRLOOP F3 SE 0.23 0.23 0.03 0.03
AIRLOOP F3 NE 0.22 0.22 0.03 0.03
AIRLOOP F3 N1 0.14 0.14 0.03 0.03
AIRLOOP F3 N2 0.14 0.14 0.03 0.03
AIRLOOP F3 S1 0.15 0.15 0.03 0.03
AIRLOOP F3 S2 0.15 0.15 0.03 0.03
AIRLOOP F4 SW 0.29 0.29 0.03 0.03
AIRLOOP F4 NW 0.29 0.29 0.03 0.03
AIRLOOP F4 SE 0.23 0.23 0.03 0.03
AIRLOOP F4 NE 0.22 0.22 0.03 0.03
AIRLOOP F4 N1 0.15 0.15 0.03 0.03
AIRLOOP F4 N2 0.15 0.15 0.03 0.03
AIRLOOP F4 S1 0.15 0.15 0.03 0.03
AIRLOOP F4 S2 0.15 0.15 0.03 0.03
AIRLOOP M SW 0.29 0.29 0.03 0.03
AIRLOOP M NW 0.29 0.29 0.03 0.03
AIRLOOP M SE 0.23 0.23 0.03 0.03
AIRLOOP M NE 0.22 0.22 0.03 0.03
AIRLOOP M N1 0.15 0.15 0.03 0.03
AIRLOOP M N2 0.15 0.15 0.03 0.03
AIRLOOP M S1 0.15 0.15 0.03 0.03
AIRLOOP M S2 0.15 0.15 0.03 0.03
AIRLOOP F6 SW 0.29 0.29 0.03 0.03
AIRLOOP F6 NW 0.28 0.28 0.03 0.03
AIRLOOP F6 SE 0.23 0.23 0.03 0.03
AIRLOOP F6 NE 0.22 0.22 0.03 0.03
AIRLOOP F6 N1 0.15 0.15 0.03 0.03
AIRLOOP F6 N2 0.15 0.15 0.03 0.03
AIRLOOP F6 S1 0.15 0.15 0.03 0.03
AIRLOOP F6 S2 0.15 0.15 0.03 0.03
AIRLOOP F7 SW 0.29 0.29 0.03 0.03
AIRLOOP F7 NW 0.28 0.28 0.03 0.03
AIRLOOP F7 SE 0.23 0.23 0.03 0.03
AIRLOOP F7 NE 0.22 0.22 0.03 0.03
AIRLOOP F7 N1 0.15 0.15 0.03 0.03
AIRLOOP F7 N2 0.15 0.15 0.03 0.03
AIRLOOP F7 S1 0.15 0.15 0.03 0.03
AIRLOOP F7 S2 0.15 0.15 0.03 0.03
AIRLOOP F8 SW 0.29 0.29 0.03 0.03
AIRLOOP F8 NW 0.28 0.28 0.03 0.03
AIRLOOP F8 SE 0.23 0.23 0.03 0.03
AIRLOOP F8 NE 0.22 0.22 0.03 0.03
AIRLOOP F8 N1 0.15 0.15 0.03 0.03
AIRLOOP F8 N2 0.15 0.15 0.03 0.03
AIRLOOP F8 S1 0.15 0.15 0.03 0.03
AIRLOOP F8 S2 0.15 0.15 0.03 0.03
AIRLOOP F9 SW 0.29 0.29 0.03 0.03
AIRLOOP F9 NW 0.29 0.29 0.03 0.03
AIRLOOP F9 SE 0.23 0.23 0.03 0.03
AIRLOOP F9 NE 0.22 0.22 0.03 0.03
AIRLOOP F9 N1 0.15 0.15 0.03 0.03
AIRLOOP F9 N2 0.15 0.15 0.03 0.03
AIRLOOP F9 S1 0.16 0.16 0.03 0.03
AIRLOOP F9 S2 0.16 0.16 0.03 0.03
AIRLOOP T SW 0.33 0.33 0.03 0.03
AIRLOOP T NW 0.33 0.33 0.03 0.03
AIRLOOP T SE 0.27 0.27 0.03 0.03
AIRLOOP T NE 0.25 0.25 0.03 0.03
AIRLOOP T N1 0.18 0.18 0.03 0.03
AIRLOOP T N2 0.18 0.18 0.03 0.03
AIRLOOP T S1 0.20 0.20 0.03 0.03
AIRLOOP T S2 0.20 0.20 0.03 0.03



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 8407.50 3113.00 3004.00
G NW APARTMENT 8187.25 3640.75 3455.50
OFFICE 2266.25 10.00 10.00
G NE APARTMENT 8250.50 3394.75 3213.75
G N1 APARTMENT 8076.50 4150.50 3927.50
G N2 APARTMENT 8080.00 4129.50 3906.75
G S1 APARTMENT 8425.50 3174.00 3077.00
G S2 APARTMENT 8431.25 3133.50 3041.00
F2 SW APARTMENT 8692.00 1277.50 1267.50
F2 NW APARTMENT 8622.75 1704.50 1681.50
F2 SE APARTMENT 8704.25 908.25 902.00
F2 NE APARTMENT 8645.75 1411.00 1387.75
F2 N1 APARTMENT 8635.75 1851.75 1831.75
F2 N2 APARTMENT 8637.50 1837.25 1817.25
F2 S1 APARTMENT 8713.50 1299.25 1294.00
F2 S2 APARTMENT 8714.00 1285.75 1281.00
F3 SW APARTMENT 8712.75 1327.50 1324.50
F3 NW APARTMENT 8662.25 1709.50 1695.00
F3 SE APARTMENT 8715.75 1006.00 1002.00
F3 NE APARTMENT 8678.75 1411.25 1400.00
F3 N1 APARTMENT 8685.00 1795.50 1787.25
F3 N2 APARTMENT 8686.25 1783.00 1774.75
F3 S1 APARTMENT 8726.50 1337.75 1336.00
F3 S2 APARTMENT 8727.00 1332.75 1331.00
F4 SW APARTMENT 8713.50 1394.50 1391.25
F4 NW APARTMENT 8664.75 1764.25 1751.00
F4 SE APARTMENT 8715.25 1085.25 1081.00
F4 NE APARTMENT 8680.00 1474.50 1463.50
F4 N1 APARTMENT 8688.75 1840.25 1833.00
F4 N2 APARTMENT 8690.00 1829.50 1822.25
F4 S1 APARTMENT 8727.50 1404.00 1402.25
F4 S2 APARTMENT 8727.75 1401.75 1400.00
M SW APARTMENT 8716.75 1417.25 1414.25
M NW APARTMENT 8669.50 1780.00 1767.25
M SE APARTMENT 8719.00 1124.25 1121.25
M NE APARTMENT 8681.50 1502.25 1492.00
M N1 APARTMENT 8694.25 1852.50 1845.50
M N2 APARTMENT 8694.50 1844.75 1838.25
M S1 APARTMENT 8728.75 1426.25 1425.00
M S2 APARTMENT 8728.75 1421.75 1420.25
F6 SW APARTMENT 8707.25 1528.00 1523.25
F6 NW APARTMENT 8647.25 1909.00 1889.75
F6 SE APARTMENT 8707.75 1231.00 1225.50
F6 NE APARTMENT 8665.00 1636.50 1620.75
F6 N1 APARTMENT 8672.50 1984.50 1973.25
F6 N2 APARTMENT 8673.75 1975.75 1964.50
F6 S1 APARTMENT 8723.75 1533.25 1531.25
F6 S2 APARTMENT 8724.00 1529.75 1527.75
F7 SW APARTMENT 8699.50 1592.00 1584.50
F7 NW APARTMENT 8636.25 1984.75 1962.75
F7 SE APARTMENT 8703.50 1305.75 1299.50
F7 NE APARTMENT 8654.00 1724.50 1705.50
F7 N1 APARTMENT 8660.00 2053.25 2037.25
F7 N2 APARTMENT 8660.50 2044.50 2028.50
F7 S1 APARTMENT 8721.75 1603.00 1600.25
F7 S2 APARTMENT 8721.75 1595.75 1593.00
F8 SW APARTMENT 8694.25 1649.00 1640.50
F8 NW APARTMENT 8625.75 2044.50 2019.75
F8 SE APARTMENT 8700.00 1372.00 1363.75
F8 NE APARTMENT 8647.00 1784.50 1764.25
F8 N1 APARTMENT 8648.50 2106.00 2088.00
F8 N2 APARTMENT 8650.50 2094.25 2076.50
F8 S1 APARTMENT 8718.00 1662.00 1659.25
F8 S2 APARTMENT 8718.50 1655.50 1652.75
F9 SW APARTMENT 8682.75 1674.00 1661.50
F9 NW APARTMENT 8611.00 2067.75 2037.25
F9 SE APARTMENT 8691.75 1398.75 1387.50
F9 NE APARTMENT 8637.75 1806.25 1779.00
F9 N1 APARTMENT 8637.50 2131.75 2109.75
F9 N2 APARTMENT 8639.75 2122.00 2100.25
F9 S1 APARTMENT 8713.00 1686.75 1682.75
F9 S2 APARTMENT 8713.25 1680.50 1676.50
T SW APARTMENT 8542.75 2066.25 2000.50
T NW APARTMENT 8460.00 2461.50 2365.25
T SE APARTMENT 8554.25 2013.00 1951.50
T NE APARTMENT 8477.75 2334.50 2240.75
T N1 APARTMENT 8521.00 2428.00 2344.50
T N2 APARTMENT 8522.25 2416.00 2333.00
T S1 APARTMENT 8612.00 2098.00 2046.50
T S2 APARTMENT 8612.50 2105.50 2054.00
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 8735.00 4548.50 4317.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 6.75 0.00 6.75
G NW APARTMENT 0.00 1.25 0.00 1.25
OFFICE 0.00 0.75 0.00 0.50
G NE APARTMENT 0.00 133.00 0.00 133.00
G N1 APARTMENT 0.00 24.00 0.00 24.00
G N2 APARTMENT 0.00 27.00 0.00 27.00
G S1 APARTMENT 0.00 611.25 0.00 611.25
G S2 APARTMENT 0.00 556.75 0.00 556.75
F2 SW APARTMENT 0.00 19.00 0.00 19.00
F2 NW APARTMENT 0.00 1.25 0.00 1.25
F2 SE APARTMENT 0.00 346.75 0.00 346.75
F2 NE APARTMENT 0.00 123.75 0.00 123.75
F2 N1 APARTMENT 0.00 52.00 0.00 52.00
F2 N2 APARTMENT 0.00 62.25 0.00 62.25
F2 S1 APARTMENT 0.00 1071.25 0.00 1071.25
F2 S2 APARTMENT 0.00 1048.25 0.00 1048.25
F3 SW APARTMENT 0.00 30.50 0.00 30.50
F3 NW APARTMENT 0.00 2.00 0.00 2.00
F3 SE APARTMENT 0.00 542.75 0.00 542.75
F3 NE APARTMENT 0.00 146.25 0.00 146.25
F3 N1 APARTMENT 0.00 123.50 0.00 123.50
F3 N2 APARTMENT 0.00 140.00 0.00 140.00
F3 S1 APARTMENT 0.00 1245.75 0.00 1245.75
F3 S2 APARTMENT 0.00 1241.75 0.00 1241.75
F4 SW APARTMENT 0.00 29.25 0.00 29.25
F4 NW APARTMENT 0.00 2.25 0.00 2.25
F4 SE APARTMENT 0.00 562.00 0.00 562.00
F4 NE APARTMENT 0.00 144.50 0.00 144.50
F4 N1 APARTMENT 0.00 148.50 0.00 148.50
F4 N2 APARTMENT 0.00 167.25 0.00 167.25
F4 S1 APARTMENT 0.00 1241.00 0.00 1241.00
F4 S2 APARTMENT 0.00 1242.75 0.00 1242.75
M SW APARTMENT 0.00 26.25 0.00 26.25
M NW APARTMENT 0.00 2.25 0.00 2.25
M SE APARTMENT 0.00 556.75 0.00 556.75
M NE APARTMENT 0.00 144.50 0.00 144.50
M N1 APARTMENT 0.00 166.50 0.00 166.50
M N2 APARTMENT 0.00 183.25 0.00 183.25
M S1 APARTMENT 0.00 1210.50 0.00 1210.50
M S2 APARTMENT 0.00 1212.25 0.00 1212.25
F6 SW APARTMENT 0.00 26.00 0.00 26.00
F6 NW APARTMENT 0.00 2.25 0.00 2.25
F6 SE APARTMENT 0.00 547.50 0.00 547.50
F6 NE APARTMENT 0.00 142.00 0.00 142.00
F6 N1 APARTMENT 0.00 175.75 0.00 175.75
F6 N2 APARTMENT 0.00 193.75 0.00 193.75
F6 S1 APARTMENT 0.00 1185.50 0.00 1185.50
F6 S2 APARTMENT 0.00 1189.00 0.00 1189.00
F7 SW APARTMENT 0.00 25.25 0.00 25.25
F7 NW APARTMENT 0.00 2.25 0.00 2.25
F7 SE APARTMENT 0.00 540.25 0.00 540.25
F7 NE APARTMENT 0.00 141.50 0.00 141.50
F7 N1 APARTMENT 0.00 185.75 0.00 185.75
F7 N2 APARTMENT 0.00 202.50 0.00 202.50
F7 S1 APARTMENT 0.00 1160.25 0.00 1160.25
F7 S2 APARTMENT 0.00 1164.00 0.00 1164.00
F8 SW APARTMENT 0.00 24.00 0.00 24.00
F8 NW APARTMENT 0.00 2.25 0.00 2.25
F8 SE APARTMENT 0.00 532.75 0.00 532.75
F8 NE APARTMENT 0.00 143.50 0.00 143.50
F8 N1 APARTMENT 0.00 195.75 0.00 195.75
F8 N2 APARTMENT 0.00 209.75 0.00 209.75
F8 S1 APARTMENT 0.00 1135.25 0.00 1135.25
F8 S2 APARTMENT 0.00 1136.25 0.00 1136.25
F9 SW APARTMENT 0.00 20.25 0.00 20.25
F9 NW APARTMENT 0.00 2.25 0.00 2.25
F9 SE APARTMENT 0.00 516.25 0.00 516.25
F9 NE APARTMENT 0.00 134.25 0.00 134.25
F9 N1 APARTMENT 0.00 190.50 0.00 190.50
F9 N2 APARTMENT 0.00 203.75 0.00 203.75
F9 S1 APARTMENT 0.00 1083.00 0.00 1083.00
F9 S2 APARTMENT 0.00 1085.00 0.00 1085.00
T SW APARTMENT 0.00 23.75 0.00 23.75
T NW APARTMENT 0.00 2.00 0.00 2.00
T SE APARTMENT 0.00 461.00 0.00 461.00
T NE APARTMENT 0.00 118.75 0.00 118.75
T N1 APARTMENT 0.00 87.50 0.00 87.50
T N2 APARTMENT 0.00 103.50 0.00 103.50
T S1 APARTMENT 0.00 642.25 0.00 642.25
T S2 APARTMENT 0.00 646.25 0.00 646.25
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 0.00 1598.75 0.00 1598.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.358 0.114 0.000 0.401
G NW APARTMENT 1.71 2.50 268.96 0.358 0.114 0.000 0.427
OFFICE 0.94 1.00 268.96 0.523 0.138 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.358 0.114 0.000 0.428
G N1 APARTMENT 1.71 2.50 268.96 0.358 0.069 0.000 0.425
G N2 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.425
G S1 APARTMENT 1.71 2.50 268.96 0.358 0.069 0.000 0.399
G S2 APARTMENT 1.71 2.50 268.97 0.358 0.069 0.000 0.399
F2 SW APARTMENT 1.71 2.50 268.96 0.358 0.164 0.000 0.493
F2 NW APARTMENT 1.71 2.50 268.96 0.358 0.164 0.000 0.536
F2 SE APARTMENT 1.71 2.50 268.96 0.357 0.164 0.000 0.493
F2 NE APARTMENT 1.71 2.50 268.96 0.358 0.164 0.000 0.536
F2 N1 APARTMENT 1.71 2.50 268.96 0.358 0.099 0.000 0.536
F2 N2 APARTMENT 1.71 2.50 268.97 0.358 0.099 0.000 0.536
F2 S1 APARTMENT 1.71 2.50 268.96 0.358 0.099 0.000 0.489
F2 S2 APARTMENT 1.71 2.50 268.97 0.358 0.099 0.000 0.489
F3 SW APARTMENT 1.71 2.50 268.96 0.358 0.194 0.000 0.577
F3 NW APARTMENT 1.71 2.50 268.96 0.358 0.194 0.000 0.632
F3 SE APARTMENT 1.71 2.50 268.96 0.357 0.194 0.000 0.576
F3 NE APARTMENT 1.71 2.50 268.96 0.358 0.194 0.000 0.632
F3 N1 APARTMENT 1.71 2.50 268.96 0.358 0.117 0.000 0.631
F3 N2 APARTMENT 1.71 2.50 268.97 0.358 0.117 0.000 0.631
F3 S1 APARTMENT 1.71 2.50 268.96 0.358 0.117 0.000 0.571
F3 S2 APARTMENT 1.71 2.50 268.97 0.358 0.117 0.000 0.571
F4 SW APARTMENT 1.71 2.50 268.96 0.358 0.217 0.000 0.624
F4 NW APARTMENT 1.71 2.50 268.96 0.358 0.217 0.000 0.687
F4 SE APARTMENT 1.71 2.50 268.96 0.357 0.217 0.000 0.623
F4 NE APARTMENT 1.71 2.50 268.96 0.358 0.217 0.000 0.687
F4 N1 APARTMENT 1.71 2.50 268.96 0.358 0.131 0.000 0.686
F4 N2 APARTMENT 1.71 2.50 268.97 0.358 0.131 0.000 0.686
F4 S1 APARTMENT 1.71 2.50 268.96 0.358 0.131 0.000 0.618
F4 S2 APARTMENT 1.71 2.50 268.97 0.358 0.131 0.000 0.618
M SW APARTMENT 1.71 2.50 268.96 0.358 0.236 0.000 0.664
M NW APARTMENT 1.71 2.50 268.96 0.358 0.236 0.000 0.732
M SE APARTMENT 1.71 2.50 268.96 0.357 0.236 0.000 0.663
M NE APARTMENT 1.71 2.50 268.96 0.358 0.236 0.000 0.732
M N1 APARTMENT 1.71 2.50 268.96 0.358 0.142 0.000 0.732
M N2 APARTMENT 1.71 2.50 268.97 0.358 0.142 0.000 0.731
M S1 APARTMENT 1.71 2.50 268.96 0.358 0.142 0.000 0.658
M S2 APARTMENT 1.71 2.50 268.97 0.358 0.142 0.000 0.658
F6 SW APARTMENT 1.71 2.50 268.96 0.358 0.252 0.000 0.699
F6 NW APARTMENT 1.71 2.50 268.96 0.358 0.252 0.000 0.772
F6 SE APARTMENT 1.71 2.50 268.96 0.358 0.252 0.000 0.697
F6 NE APARTMENT 1.71 2.50 268.96 0.358 0.252 0.000 0.772
F6 N1 APARTMENT 1.71 2.50 268.96 0.358 0.152 0.000 0.771
F6 N2 APARTMENT 1.71 2.50 268.97 0.358 0.152 0.000 0.771
F6 S1 APARTMENT 1.71 2.50 268.96 0.358 0.152 0.000 0.693
F6 S2 APARTMENT 1.71 2.50 268.97 0.358 0.152 0.000 0.693
F7 SW APARTMENT 1.71 2.50 268.96 0.358 0.266 0.000 0.730
F7 NW APARTMENT 1.71 2.50 268.96 0.358 0.266 0.000 0.808
F7 SE APARTMENT 1.71 2.50 268.96 0.358 0.266 0.000 0.728
F7 NE APARTMENT 1.71 2.50 268.96 0.358 0.266 0.000 0.808
F7 N1 APARTMENT 1.71 2.50 268.96 0.358 0.161 0.000 0.807
F7 N2 APARTMENT 1.71 2.50 268.97 0.358 0.161 0.000 0.807
F7 S1 APARTMENT 1.71 2.50 268.96 0.358 0.161 0.000 0.724
F7 S2 APARTMENT 1.71 2.50 268.97 0.358 0.161 0.000 0.724
F8 SW APARTMENT 1.71 2.50 268.96 0.358 0.279 0.000 0.761
F8 NW APARTMENT 1.71 2.50 268.96 0.358 0.279 0.000 0.844
F8 SE APARTMENT 1.71 2.50 268.96 0.358 0.279 0.000 0.760
F8 NE APARTMENT 1.71 2.50 268.96 0.358 0.279 0.000 0.844
F8 N1 APARTMENT 1.71 2.50 268.96 0.358 0.168 0.000 0.843
F8 N2 APARTMENT 1.71 2.50 268.97 0.358 0.168 0.000 0.843
F8 S1 APARTMENT 1.71 2.50 268.96 0.358 0.169 0.000 0.756
F8 S2 APARTMENT 1.71 2.50 268.97 0.358 0.169 0.000 0.756
F9 SW APARTMENT 1.71 2.50 268.96 0.358 0.291 0.000 0.793
F9 NW APARTMENT 1.71 2.50 268.96 0.358 0.291 0.000 0.879
F9 SE APARTMENT 1.71 2.50 268.96 0.358 0.291 0.000 0.792
F9 NE APARTMENT 1.71 2.50 268.96 0.358 0.291 0.000 0.879
F9 N1 APARTMENT 1.71 2.50 268.96 0.358 0.176 0.000 0.878
F9 N2 APARTMENT 1.71 2.50 268.97 0.358 0.176 0.000 0.878
F9 S1 APARTMENT 1.71 2.50 268.96 0.358 0.176 0.000 0.788
F9 S2 APARTMENT 1.71 2.50 268.97 0.358 0.176 0.000 0.787
T SW APARTMENT 1.71 2.50 268.96 0.358 0.302 0.000 0.816
T NW APARTMENT 1.71 2.50 268.96 0.358 0.302 0.000 0.906
T SE APARTMENT 1.71 2.50 268.96 0.358 0.302 0.000 0.814
T NE APARTMENT 1.71 2.50 268.96 0.358 0.302 0.000 0.906
T N1 APARTMENT 1.71 2.50 268.96 0.358 0.182 0.000 0.905
T N2 APARTMENT 1.71 2.50 268.97 0.358 0.182 0.000 0.905
T S1 APARTMENT 1.71 2.50 268.96 0.358 0.182 0.000 0.811
T S2 APARTMENT 1.71 2.50 268.97 0.358 0.182 0.000 0.811
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.514 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.351 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.351 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.351 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.351 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.351 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.350 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.350 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 578.08 18330.67 01-JAN-02:30 18330.67 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 2026.18 18831.73 01-JAN-06:15 98174.42 15-SEP-17:00
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
ElectricityPurchased:Plant 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
Cogeneration:ElectricityPurchased 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
ElectricityNet:Plant 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
Cogeneration:ElectricityNet 3863.42 58680.19 12-FEB-04:00 189352.70 15-SEP-18:45
ExteriorLights:Electricity 168.75 0.00 01-JAN-07:15 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.75 0.00 01-JAN-07:15 10720.10 01-JAN-00:15
General:Fans:Electricity 578.08 18330.67 01-JAN-02:30 18330.67 01-JAN-00:15
Cooling:Electricity 1427.28 0.00 01-JAN-06:15 78695.31 15-SEP-17:00
Heating:Electricity 0.00 0.00 01-JAN-00:15 73.49 11-FEB-06:30
Electricity:Plant 120.99 36.93 01-JAN-06:15 5024.00 20-JUL-14:00
HeatRejection:Electricity 65.97 0.00 01-JAN-06:15 3263.07 20-JUL-14:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 55.02 36.93 01-JAN-06:15 1760.93 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 814.51 9260.51 01-JAN-00:15 76144.64 02-JAN-08:00
Gas:Plant 814.51 9260.51 01-JAN-00:15 76144.64 02-JAN-08:00
WaterSystems:Gas 814.51 9260.51 01-JAN-00:15 76144.64 02-JAN-08:00
Water Heater:WaterSystems:Gas 814.51 9260.51 01-JAN-00:15 76144.64 02-JAN-08:00
Heating:Gas 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler:Heating:Gas 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 6395.67 0.00 01-JAN-06:15 394806.58 15-SEP-17:30
PlantLoopCoolingDemand:HVAC 6395.67 0.00 01-JAN-06:15 394806.58 15-SEP-17:30
CoolingCoils:PlantLoopCoolingDemand 6395.67 0.00 01-JAN-06:15 394806.58 15-SEP-17:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 8355.85 0.00 12-FEB-04:00 0.00 21-JUN-07:00
Water:Plant 8355.85 0.00 12-FEB-04:00 0.00 21-JUN-07:00
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 8355.85 0.00 12-FEB-04:00 0.00 21-JUN-07:00
MainsWater:Plant 8355.85 0.00 12-FEB-04:00 0.00 21-JUN-07:00
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 3577.33 0.00 01-JAN-06:15 0.00 03-SEP-16:00
HeatRejection:MainsWater 3577.33 0.00 01-JAN-06:15 0.00 03-SEP-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 616.15 363.41 19-JUL-01:15 39785.18 12-JAN-07:15
PlantLoopHeatingDemand:Plant 616.15 363.41 19-JUL-01:15 39785.18 12-JAN-07:15
WaterSystems:PlantLoopHeatingDemand 616.15 363.41 19-JUL-01:15 39785.18 12-JAN-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 8441.94 9821.40 12-FEB-04:00 502203.37 03-SEP-16:15
EnergyTransfer:Building 2776.77 3787.95 08-MAR-08:00 186327.37 15-NOV-14:30
EnergyTransfer:Zone:G SW APARTMENT 26.29 0.06 24-JAN-22:00 2944.79 28-SEP-15:30
Heating:EnergyTransfer 6.98 0.00 01-JAN-00:15 12905.46 02-APR-05:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.33 0.00 01-JAN-00:15 220.69 11-JAN-06:15
Cooling:EnergyTransfer 2769.79 0.00 09-JAN-07:00 186327.37 15-NOV-14:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 25.96 0.00 01-JAN-02:30 2944.79 28-SEP-15:30
EnergyTransfer:Zone:G NW APARTMENT 21.32 0.03 05-FEB-03:00 2660.50 03-SEP-16:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 0.47 0.00 01-JAN-00:15 231.57 11-JAN-06:15
Cooling:EnergyTransfer:Zone:G NW APARTMENT 20.85 0.00 01-JAN-00:45 2660.50 03-SEP-16:15
EnergyTransfer:Zone:OFFICE 32.85 0.00 29-DEC-02:30 3731.23 15-DEC-11:30
Heating:EnergyTransfer:Zone:OFFICE 0.20 0.00 01-JAN-00:15 180.35 06-FEB-00:30
Cooling:EnergyTransfer:Zone:OFFICE 32.65 0.00 01-JAN-02:15 3731.23 15-DEC-11:30
EnergyTransfer:Zone:G NE APARTMENT 23.32 0.04 25-MAR-02:00 2252.17 18-JUL-09:45
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.27 0.00 01-JAN-00:15 169.06 11-JAN-06:15
Cooling:EnergyTransfer:Zone:G NE APARTMENT 23.05 0.00 01-JAN-01:00 2252.17 18-JUL-09:45
EnergyTransfer:Zone:G N1 APARTMENT 15.08 0.01 06-JAN-02:30 1378.66 01-JUL-17:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.08 0.00 01-JAN-00:15 104.32 12-FEB-08:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 15.00 0.00 01-JAN-06:45 1378.66 01-JUL-17:15
EnergyTransfer:Zone:G N2 APARTMENT 15.16 0.02 26-NOV-20:00 1370.75 03-JUN-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.07 0.00 01-JAN-00:15 111.00 12-FEB-08:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 15.08 0.00 01-JAN-06:45 1370.75 03-JUN-17:30
EnergyTransfer:Zone:G S1 APARTMENT 20.17 0.09 13-JAN-04:30 1732.98 21-JAN-13:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.03 0.00 01-JAN-00:15 84.18 13-FEB-06:15
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 20.14 0.00 01-JAN-06:45 1732.98 21-JAN-13:00
EnergyTransfer:Zone:G S2 APARTMENT 20.60 0.08 07-FEB-21:15 1783.40 21-JAN-13:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.04 0.00 01-JAN-00:15 88.13 13-FEB-06:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 20.57 0.00 01-JAN-06:15 1783.40 21-JAN-13:00
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 41.25 0.35 12-FEB-06:15 3659.09 29-JAN-15:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.09 0.00 01-JAN-00:15 258.12 15-FEB-06:15
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 41.16 0.00 01-JAN-06:15 3659.09 29-JAN-15:30
EnergyTransfer:Zone:F2 NW APARTMENT 33.51 0.91 19-DEC-20:00 3146.66 03-SEP-16:15
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 0.14 0.00 01-JAN-00:15 275.29 11-FEB-06:15
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 33.37 0.00 01-JAN-06:15 3146.66 03-SEP-16:15
EnergyTransfer:Zone:F2 SE APARTMENT 45.56 0.69 16-APR-06:15 3293.97 21-JAN-12:45
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.05 0.00 01-JAN-00:15 189.46 15-FEB-06:15
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 45.51 0.00 01-JAN-06:15 3293.97 21-JAN-12:45
EnergyTransfer:Zone:F2 NE APARTMENT 36.50 0.13 08-FEB-03:00 2686.86 18-JUL-10:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.07 0.00 01-JAN-00:15 182.64 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 36.43 0.00 01-JAN-06:15 2686.86 18-JUL-10:00
EnergyTransfer:Zone:F2 N1 APARTMENT 26.09 0.03 06-FEB-21:15 1765.63 03-JUN-17:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.02 0.00 01-JAN-00:15 89.18 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 26.07 0.00 01-JAN-06:15 1765.63 03-JUN-17:30
EnergyTransfer:Zone:F2 N2 APARTMENT 26.21 0.02 21-MAR-06:45 1753.18 03-JUN-17:30
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.02 0.00 01-JAN-00:15 87.64 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 26.19 0.00 01-JAN-06:15 1753.18 03-JUN-17:30
EnergyTransfer:Zone:F2 S1 APARTMENT 33.17 0.60 05-MAR-06:45 2221.00 20-JAN-13:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.01 0.00 01-JAN-00:15 70.13 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 33.17 0.00 01-JAN-06:15 2221.00 20-JAN-13:00
EnergyTransfer:Zone:F2 S2 APARTMENT 33.42 0.12 22-DEC-06:45 2241.04 20-JAN-13:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.01 0.00 01-JAN-00:15 71.65 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 33.41 0.00 01-JAN-06:15 2241.04 20-JAN-13:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 43.04 0.81 06-FEB-22:00 3769.29 26-FEB-17:00
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.08 0.00 01-JAN-00:15 238.15 27-APR-05:30
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 42.96 0.00 01-JAN-06:15 3769.29 26-FEB-17:00
EnergyTransfer:Zone:F3 NW APARTMENT 35.58 0.47 10-JAN-07:45 3156.67 03-SEP-16:15
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 0.13 0.00 01-JAN-00:15 270.27 12-FEB-08:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 35.45 0.00 01-JAN-06:15 3156.67 03-SEP-16:15
EnergyTransfer:Zone:F3 SE APARTMENT 45.82 1.24 26-MAR-07:00 3188.28 21-JAN-11:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.04 0.00 01-JAN-00:15 174.46 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 45.77 0.00 01-JAN-06:15 3188.28 21-JAN-11:00
EnergyTransfer:Zone:F3 NE APARTMENT 38.43 0.41 16-JAN-04:45 2695.47 18-JUL-10:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.06 0.00 01-JAN-00:15 182.70 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 38.37 0.00 01-JAN-06:15 2695.47 18-JUL-10:00
EnergyTransfer:Zone:F3 N1 APARTMENT 28.41 0.05 06-FEB-21:45 1841.25 30-MAY-17:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.02 0.00 01-JAN-00:15 90.66 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 28.40 0.00 01-JAN-06:15 1841.25 30-MAY-17:00
EnergyTransfer:Zone:F3 N2 APARTMENT 28.52 0.04 03-FEB-06:45 1829.00 30-MAY-17:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.02 0.00 01-JAN-00:15 89.14 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 28.51 0.00 01-JAN-06:15 1829.00 30-MAY-17:00
EnergyTransfer:Zone:F3 S1 APARTMENT 35.19 0.05 28-NOV-07:00 2270.70 20-JAN-13:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.01 0.00 01-JAN-00:15 70.49 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 35.18 0.00 09-JAN-06:15 2270.70 20-JAN-13:00
EnergyTransfer:Zone:F3 S2 APARTMENT 35.35 0.04 19-FEB-07:00 2280.18 20-JAN-13:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.01 0.00 01-JAN-00:15 71.26 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 35.34 0.00 09-JAN-06:15 2280.18 20-JAN-13:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 43.23 0.14 08-MAR-05:15 3786.73 26-FEB-17:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.08 0.00 01-JAN-00:15 246.03 27-APR-05:30
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 43.15 0.00 01-JAN-06:15 3786.73 26-FEB-17:00
EnergyTransfer:Zone:F4 NW APARTMENT 35.91 0.18 12-FEB-05:30 3168.62 03-SEP-16:15
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 0.13 0.00 01-JAN-00:15 270.97 12-FEB-08:15
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 35.78 0.00 01-JAN-06:15 3168.62 03-SEP-16:15
EnergyTransfer:Zone:F4 SE APARTMENT 45.80 0.03 12-MAR-06:15 3176.33 21-JAN-11:00
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.04 0.00 01-JAN-00:15 177.97 03-MAR-06:15
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 45.76 0.00 01-JAN-06:15 3176.33 21-JAN-11:00
EnergyTransfer:Zone:F4 NE APARTMENT 38.67 0.87 20-MAR-06:15 2699.48 21-MAY-09:30
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.07 0.00 01-JAN-00:15 189.23 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 38.61 0.00 01-JAN-06:15 2699.48 21-MAY-09:30
EnergyTransfer:Zone:F4 N1 APARTMENT 28.88 0.02 07-FEB-22:00 1869.52 30-MAY-17:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.02 0.00 01-JAN-00:15 96.65 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 28.86 0.00 01-JAN-06:15 1869.52 30-MAY-17:00
EnergyTransfer:Zone:F4 N2 APARTMENT 28.99 0.25 12-APR-06:00 1864.34 31-MAY-16:30
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.02 0.00 01-JAN-00:15 95.11 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 28.97 0.00 01-JAN-06:15 1864.34 31-MAY-16:30
EnergyTransfer:Zone:F4 S1 APARTMENT 35.57 0.64 19-FEB-07:00 2297.10 20-JAN-13:00
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.01 0.00 01-JAN-00:15 80.74 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 35.56 0.00 09-JAN-06:15 2297.10 20-JAN-13:00
EnergyTransfer:Zone:F4 S2 APARTMENT 35.71 0.16 09-FEB-06:45 2304.85 20-JAN-13:00
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.01 0.00 01-JAN-00:15 80.82 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 35.70 0.00 09-JAN-06:15 2304.85 20-JAN-13:00
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 43.88 1.43 08-FEB-21:45 3825.61 26-FEB-17:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.08 0.00 01-JAN-00:15 254.24 27-APR-05:30
Cooling:EnergyTransfer:Zone:M SW APARTMENT 43.80 0.00 01-JAN-06:15 3825.61 26-FEB-17:00
EnergyTransfer:Zone:M NW APARTMENT 36.67 0.09 08-DEC-07:00 3203.48 03-SEP-16:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.14 0.00 01-JAN-00:15 279.88 12-FEB-08:15
Cooling:EnergyTransfer:Zone:M NW APARTMENT 36.53 0.00 01-JAN-06:15 3203.48 03-SEP-16:15
EnergyTransfer:Zone:M SE APARTMENT 46.39 1.26 20-APR-06:15 3202.35 21-JAN-11:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.05 0.00 01-JAN-00:15 182.98 03-MAR-06:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 46.34 0.00 01-JAN-06:15 3202.35 21-JAN-11:00
EnergyTransfer:Zone:M NE APARTMENT 39.37 0.23 26-MAR-07:00 2729.41 21-MAY-09:30
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.07 0.00 01-JAN-00:15 195.88 11-JAN-06:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 39.30 0.00 01-JAN-06:15 2729.41 21-MAY-09:30
EnergyTransfer:Zone:M N1 APARTMENT 29.72 0.13 03-APR-06:45 1918.33 31-MAY-16:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.02 0.00 01-JAN-00:15 103.34 25-JAN-16:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 29.70 0.00 01-JAN-06:15 1918.33 31-MAY-16:30
EnergyTransfer:Zone:M N2 APARTMENT 29.83 0.06 07-MAR-21:30 1923.24 31-MAY-16:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.02 0.00 01-JAN-00:15 101.64 11-JAN-06:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 29.80 0.00 01-JAN-06:15 1923.24 31-MAY-16:30
EnergyTransfer:Zone:M S1 APARTMENT 36.35 0.14 05-MAR-06:45 2343.49 20-JAN-13:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.01 0.00 01-JAN-00:15 88.41 05-FEB-12:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 36.34 0.00 01-JAN-06:15 2343.49 20-JAN-13:00
EnergyTransfer:Zone:M S2 APARTMENT 36.49 0.46 29-MAR-05:45 2350.81 20-JAN-13:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.01 0.00 01-JAN-00:15 88.98 05-FEB-12:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 36.48 0.00 01-JAN-06:15 2350.81 20-JAN-13:00
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 42.72 0.10 12-FEB-05:15 3786.61 26-FEB-17:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.10 0.00 01-JAN-00:15 258.78 01-APR-05:15
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 42.62 0.00 01-JAN-06:15 3786.61 26-FEB-17:00
EnergyTransfer:Zone:F6 NW APARTMENT 35.61 0.06 01-MAR-07:00 3172.10 03-SEP-16:15
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 0.16 0.00 01-JAN-00:15 281.45 01-APR-05:15
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 35.45 0.00 01-JAN-06:15 3172.10 03-SEP-16:15
EnergyTransfer:Zone:F6 SE APARTMENT 45.16 0.35 20-MAR-05:45 3152.58 21-JAN-11:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.05 0.00 01-JAN-00:15 188.74 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 45.11 0.00 01-JAN-06:15 3152.58 21-JAN-11:00
EnergyTransfer:Zone:F6 NE APARTMENT 38.22 0.17 17-NOV-06:30 2691.38 21-MAY-09:30
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.08 0.00 01-JAN-00:15 201.76 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 38.14 0.00 01-JAN-06:15 2691.38 21-MAY-09:30
EnergyTransfer:Zone:F6 N1 APARTMENT 28.70 0.12 08-FEB-22:00 1907.97 31-MAY-16:30
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.03 0.00 01-JAN-00:15 107.58 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 28.67 0.00 01-JAN-06:15 1907.97 31-MAY-16:30
EnergyTransfer:Zone:F6 N2 APARTMENT 28.80 0.03 11-FEB-20:45 1896.59 31-MAY-16:30
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.03 0.00 01-JAN-00:15 105.98 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 28.77 0.00 01-JAN-06:15 1896.59 31-MAY-16:30
EnergyTransfer:Zone:F6 S1 APARTMENT 35.26 0.17 07-MAR-21:30 2315.30 20-JAN-13:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.01 0.00 01-JAN-00:15 95.00 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 35.25 0.00 01-JAN-06:15 2315.30 20-JAN-13:00
EnergyTransfer:Zone:F6 S2 APARTMENT 35.40 0.08 29-MAR-05:45 2322.42 20-JAN-13:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.01 0.00 01-JAN-00:15 95.58 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 35.38 0.00 01-JAN-06:15 2322.42 20-JAN-13:00
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 42.21 0.02 12-FEB-05:15 3766.23 26-FEB-17:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.11 0.00 01-JAN-00:15 265.90 01-APR-05:15
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 42.11 0.00 01-JAN-06:15 3766.23 26-FEB-17:00
EnergyTransfer:Zone:F7 NW APARTMENT 35.20 0.01 27-JAN-20:30 3164.86 03-SEP-16:15
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 0.18 0.00 01-JAN-00:15 289.64 01-APR-05:15
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 35.02 0.00 01-JAN-06:15 3164.86 03-SEP-16:15
EnergyTransfer:Zone:F7 SE APARTMENT 44.61 0.35 25-DEC-06:45 3124.63 22-DEC-14:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.06 0.00 01-JAN-00:15 206.43 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 44.54 0.00 01-JAN-06:15 3124.63 22-DEC-14:00
EnergyTransfer:Zone:F7 NE APARTMENT 37.74 0.06 26-MAR-07:00 2678.07 21-MAY-09:15
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 0.09 0.00 01-JAN-00:15 207.20 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 37.65 0.00 01-JAN-06:15 2678.07 21-MAY-09:15
EnergyTransfer:Zone:F7 N1 APARTMENT 28.32 0.06 26-FEB-07:00 1905.48 31-MAY-16:30
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.04 0.00 01-JAN-00:15 112.15 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 28.28 0.00 01-JAN-06:15 1905.48 31-MAY-16:30
EnergyTransfer:Zone:F7 N2 APARTMENT 28.42 0.20 11-FEB-20:15 1901.61 05-APR-17:00
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.03 0.00 01-JAN-00:15 110.51 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 28.38 0.00 01-JAN-06:15 1901.61 05-APR-17:00
EnergyTransfer:Zone:F7 S1 APARTMENT 34.82 0.26 06-FEB-21:30 2311.89 20-JAN-13:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.01 0.00 01-JAN-00:15 100.89 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 34.81 0.00 01-JAN-06:15 2311.89 20-JAN-13:00
EnergyTransfer:Zone:F7 S2 APARTMENT 34.96 0.01 19-FEB-07:00 2318.85 20-JAN-13:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.01 0.00 01-JAN-00:15 101.46 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 34.94 0.00 01-JAN-06:15 2318.85 20-JAN-13:00
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 42.04 0.35 12-FEB-05:45 3756.16 26-FEB-17:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.11 0.00 01-JAN-00:15 272.81 01-APR-05:15
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 41.93 0.00 01-JAN-06:15 3756.16 26-FEB-17:00
EnergyTransfer:Zone:F8 NW APARTMENT 35.10 0.00 08-FEB-02:30 3169.78 03-SEP-16:15
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 0.20 0.00 01-JAN-00:15 297.58 01-APR-05:15
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 34.91 0.00 01-JAN-06:15 3169.78 03-SEP-16:15
EnergyTransfer:Zone:F8 SE APARTMENT 44.39 0.99 26-JAN-21:00 3124.83 21-JAN-13:15
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.06 0.00 01-JAN-00:15 202.75 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 44.33 0.00 01-JAN-06:15 3124.83 21-JAN-13:15
EnergyTransfer:Zone:F8 NE APARTMENT 37.58 0.01 27-NOV-03:00 2677.00 21-MAY-09:15
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 0.10 0.00 01-JAN-00:15 212.67 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 37.49 0.00 01-JAN-06:15 2677.00 21-MAY-09:15
EnergyTransfer:Zone:F8 N1 APARTMENT 28.25 0.06 11-FEB-21:00 1928.00 31-MAY-16:15
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.04 0.00 01-JAN-00:15 117.06 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 28.21 0.00 01-JAN-06:15 1928.00 31-MAY-16:15
EnergyTransfer:Zone:F8 N2 APARTMENT 28.35 0.03 01-JAN-07:00 1924.10 05-APR-17:00
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.04 0.00 01-JAN-00:15 115.40 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 28.31 0.00 01-JAN-06:15 1924.10 05-APR-17:00
EnergyTransfer:Zone:F8 S1 APARTMENT 34.71 0.24 19-FEB-07:00 2321.50 20-JAN-13:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.02 0.00 01-JAN-00:15 105.99 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 34.69 0.00 01-JAN-06:15 2321.50 20-JAN-13:00
EnergyTransfer:Zone:F8 S2 APARTMENT 34.84 0.08 06-FEB-21:15 2328.34 20-JAN-13:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.02 0.00 01-JAN-00:15 106.60 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 34.83 0.00 01-JAN-06:15 2328.34 20-JAN-13:00
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 42.65 0.21 15-JAN-20:15 3813.40 26-FEB-17:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.13 0.00 01-JAN-00:15 288.28 01-APR-05:15
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 42.52 0.00 01-JAN-06:15 3813.40 26-FEB-17:00
EnergyTransfer:Zone:F9 NW APARTMENT 35.70 0.76 08-MAR-03:30 3243.14 03-SEP-16:15
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 0.22 0.00 01-JAN-00:15 320.27 27-JAN-06:15
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 35.48 0.00 01-JAN-06:15 3243.14 03-SEP-16:15
EnergyTransfer:Zone:F9 SE APARTMENT 45.00 0.25 20-MAR-06:00 3166.50 21-JAN-13:15
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.07 0.00 01-JAN-00:15 213.04 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 44.92 0.00 01-JAN-06:15 3166.50 21-JAN-13:15
EnergyTransfer:Zone:F9 NE APARTMENT 38.15 0.14 15-FEB-06:00 2694.04 31-MAY-09:30
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 0.11 0.00 01-JAN-00:15 222.24 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 38.04 0.00 01-JAN-06:15 2694.04 31-MAY-09:30
EnergyTransfer:Zone:F9 N1 APARTMENT 28.84 0.22 28-APR-18:30 2000.40 31-MAY-16:15
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.05 0.00 01-JAN-00:15 128.88 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 28.79 0.00 01-JAN-06:15 2000.40 31-MAY-16:15
EnergyTransfer:Zone:F9 N2 APARTMENT 28.94 0.03 27-FEB-06:45 1988.98 31-MAY-16:15
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.05 0.00 01-JAN-00:15 127.19 11-JAN-06:15
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 28.89 0.00 01-JAN-06:15 1988.98 31-MAY-16:15
EnergyTransfer:Zone:F9 S1 APARTMENT 35.33 0.11 07-MAR-21:00 2378.93 20-JAN-13:00
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.02 0.00 01-JAN-00:15 121.44 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 35.31 0.00 01-JAN-06:15 2378.93 20-JAN-13:00
EnergyTransfer:Zone:F9 S2 APARTMENT 35.47 0.50 15-JAN-21:30 2387.16 20-JAN-13:00
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.02 0.00 01-JAN-00:15 122.19 05-FEB-12:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 35.45 0.00 01-JAN-06:15 2387.16 20-JAN-13:00
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 42.53 0.46 25-JAN-09:00 4208.06 04-DEC-14:45
Heating:EnergyTransfer:Zone:T SW APARTMENT 0.31 0.00 01-JAN-00:15 406.34 14-JAN-06:15
Cooling:EnergyTransfer:Zone:T SW APARTMENT 42.22 0.00 01-JAN-04:45 4208.06 04-DEC-14:45
EnergyTransfer:Zone:T NW APARTMENT 36.24 0.03 18-MAR-06:45 3719.23 03-SEP-16:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 0.44 0.00 01-JAN-00:15 418.98 01-APR-05:15
Cooling:EnergyTransfer:Zone:T NW APARTMENT 35.80 0.00 01-JAN-03:00 3719.23 03-SEP-16:15
EnergyTransfer:Zone:T SE APARTMENT 44.49 0.29 27-JAN-02:45 3623.74 28-JAN-12:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 0.20 0.00 01-JAN-00:15 298.25 14-JAN-06:15
Cooling:EnergyTransfer:Zone:T SE APARTMENT 44.29 0.00 01-JAN-06:15 3623.74 28-JAN-12:30
EnergyTransfer:Zone:T NE APARTMENT 38.35 0.14 18-JAN-05:30 3249.96 21-MAY-10:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 0.27 0.00 01-JAN-00:15 302.34 01-APR-05:15
Cooling:EnergyTransfer:Zone:T NE APARTMENT 38.09 0.00 01-JAN-03:00 3249.96 21-MAY-10:00
EnergyTransfer:Zone:T N1 APARTMENT 29.68 0.05 21-MAR-08:45 2285.52 31-MAY-16:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.13 0.00 01-JAN-00:15 182.19 11-JAN-06:15
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 29.55 0.00 01-JAN-06:15 2285.52 31-MAY-16:15
EnergyTransfer:Zone:T N2 APARTMENT 29.77 0.06 16-JAN-02:45 2260.82 31-MAY-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.12 0.00 01-JAN-00:15 178.79 11-JAN-06:15
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 29.65 0.00 01-JAN-06:15 2260.82 31-MAY-16:15
EnergyTransfer:Zone:T S1 APARTMENT 35.89 0.24 22-MAR-02:30 2837.38 22-DEC-14:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.09 0.00 01-JAN-00:15 185.76 11-JAN-06:15
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 35.80 0.00 01-JAN-06:15 2837.38 22-DEC-14:00
EnergyTransfer:Zone:T S2 APARTMENT 36.02 0.20 25-JAN-16:30 2842.99 22-DEC-14:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.09 0.00 01-JAN-00:15 186.28 11-JAN-06:15
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 35.93 0.00 01-JAN-06:15 2842.99 22-DEC-14:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 616.15 363.41 19-JUL-01:15 39781.11 12-JAN-07:15
WaterSystems:EnergyTransfer 616.15 363.41 19-JUL-01:15 39781.11 12-JAN-07:15
sub cat:WaterSystems:EnergyTransfer 616.15 363.41 19-JUL-01:15 39781.11 12-JAN-07:15
EnergyTransfer:HVAC 5049.02 0.00 01-JAN-06:15 316191.30 15-SEP-17:30
CoolingCoils:EnergyTransfer 5049.02 0.00 01-JAN-06:15 316191.30 15-SEP-17:30
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:15 242.41 12-FEB-08:00
PlantLoopHeatingDemand:HVAC 0.00 0.00 01-JAN-00:15 187.98 12-FEB-08:00
HeatingCoils:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 187.98 12-FEB-08:00
Boilers:EnergyTransfer 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.332 -25.956 0.000 0.000 3.525 2.413 12.213 23.559 0.000 1.290 0.000 0.000 -3.340 0.000 -1.499 -12.538
G NW APARTMENT 0.473 -20.846 0.000 0.000 3.528 2.413 12.213 16.658 0.000 1.339 0.000 0.000 -3.175 0.000 -1.497 -11.105
OFFICE 0.199 -32.650 0.000 0.000 0.503 21.954 7.547 26.506 0.000 0.629 0.000 0.000 -3.430 0.000 -0.213 -21.044
G NE APARTMENT 0.270 -23.051 0.000 0.000 3.529 2.413 12.213 19.691 0.000 1.328 0.001 0.000 -3.130 0.000 -1.515 -11.748
G N1 APARTMENT 0.079 -14.997 0.000 0.000 3.533 2.413 12.213 8.034 0.000 1.083 0.000 0.000 -1.809 0.000 -1.354 -9.194
G N2 APARTMENT 0.073 -15.082 0.000 0.000 3.533 2.413 12.213 8.027 0.000 1.081 0.000 0.000 -1.809 0.000 -1.354 -9.096
G S1 APARTMENT 0.033 -20.139 0.000 0.000 3.522 2.413 12.213 14.935 0.000 1.002 0.000 0.000 -1.992 0.000 -1.392 -10.594
G S2 APARTMENT 0.036 -20.568 0.000 0.000 3.522 2.413 12.213 14.923 0.000 1.006 0.000 0.000 -1.997 0.000 -1.397 -10.150
F2 SW APARTMENT 0.089 -41.160 0.000 0.000 3.519 2.413 12.213 22.423 0.000 1.710 4.596 0.000 -3.946 0.000 -1.857 -0.001
F2 NW APARTMENT 0.144 -33.369 0.000 0.000 3.520 2.413 12.213 15.666 0.000 1.787 3.341 0.000 -3.811 0.000 -1.903 -0.000
F2 SE APARTMENT 0.051 -45.511 0.000 0.000 3.517 2.413 12.213 25.276 0.000 1.683 6.183 0.000 -3.961 0.000 -1.864 -0.001
F2 NE APARTMENT 0.069 -36.426 0.000 0.000 3.519 2.413 12.213 18.561 0.000 1.773 3.554 0.000 -3.763 0.000 -1.912 -0.000
F2 N1 APARTMENT 0.022 -26.068 0.000 0.000 3.519 2.413 12.213 7.421 0.000 1.411 3.094 0.000 -2.261 0.000 -1.764 -0.000
F2 N2 APARTMENT 0.021 -26.189 0.000 0.000 3.519 2.413 12.213 7.416 0.000 1.409 3.224 0.000 -2.261 0.000 -1.764 -0.000
F2 S1 APARTMENT 0.008 -33.165 0.000 0.000 3.508 2.413 12.213 14.167 0.000 1.223 3.741 0.000 -2.373 0.000 -1.735 -0.000
F2 S2 APARTMENT 0.008 -33.414 0.000 0.000 3.509 2.413 12.213 14.162 0.000 1.226 3.994 0.000 -2.375 0.000 -1.736 -0.001
F3 SW APARTMENT 0.078 -42.961 0.000 0.000 3.518 2.413 12.213 21.967 0.000 2.121 6.713 0.000 -4.023 0.000 -2.039 -0.001
F3 NW APARTMENT 0.126 -35.449 0.000 0.000 3.519 2.413 12.213 15.313 0.000 2.229 5.646 0.000 -3.901 0.000 -2.109 0.000
F3 SE APARTMENT 0.042 -45.774 0.000 0.000 3.515 2.413 12.213 24.743 0.000 2.055 6.844 0.000 -4.007 0.000 -2.043 -0.001
F3 NE APARTMENT 0.060 -38.372 0.000 0.000 3.519 2.413 12.213 18.125 0.000 2.206 5.802 0.000 -3.848 0.000 -2.117 -0.000
F3 N1 APARTMENT 0.017 -28.395 0.000 0.000 3.518 2.413 12.213 7.235 0.000 1.762 5.516 0.000 -2.327 0.000 -1.952 0.000
F3 N2 APARTMENT 0.016 -28.505 0.000 0.000 3.518 2.413 12.213 7.230 0.000 1.758 5.638 0.000 -2.328 0.000 -1.952 0.000
F3 S1 APARTMENT 0.006 -35.182 0.000 0.000 3.505 2.413 12.213 13.863 0.000 1.490 6.029 0.000 -2.434 0.000 -1.903 -0.001
F3 S2 APARTMENT 0.006 -35.339 0.000 0.000 3.505 2.413 12.213 13.857 0.000 1.489 6.193 0.000 -2.435 0.000 -1.903 -0.001
F4 SW APARTMENT 0.082 -43.145 0.000 0.000 3.518 2.413 12.213 21.666 0.000 2.314 7.172 0.000 -4.052 0.000 -2.182 -0.001
F4 NW APARTMENT 0.135 -35.776 0.000 0.000 3.519 2.413 12.213 15.092 0.000 2.435 6.168 0.000 -3.933 0.000 -2.266 0.000
F4 SE APARTMENT 0.044 -45.757 0.000 0.000 3.515 2.413 12.213 24.380 0.000 2.237 7.172 0.000 -4.031 0.000 -2.186 -0.001
F4 NE APARTMENT 0.065 -38.606 0.000 0.000 3.519 2.413 12.213 17.842 0.000 2.408 6.295 0.000 -3.875 0.000 -2.275 0.000
F4 N1 APARTMENT 0.021 -28.860 0.000 0.000 3.518 2.413 12.213 7.124 0.000 1.910 6.102 0.000 -2.349 0.000 -2.091 0.000
F4 N2 APARTMENT 0.019 -28.966 0.000 0.000 3.517 2.413 12.213 7.119 0.000 1.905 6.221 0.000 -2.350 0.000 -2.091 0.000
F4 S1 APARTMENT 0.007 -35.558 0.000 0.000 3.506 2.413 12.213 13.673 0.000 1.616 6.612 0.000 -2.454 0.000 -2.028 -0.001
F4 S2 APARTMENT 0.007 -35.702 0.000 0.000 3.505 2.413 12.213 13.667 0.000 1.615 6.765 0.000 -2.456 0.000 -2.028 -0.000
M SW APARTMENT 0.085 -43.795 0.000 0.000 3.518 2.413 12.213 21.411 0.000 2.465 8.099 0.000 -4.097 0.000 -2.312 -0.001
M NW APARTMENT 0.140 -36.533 0.000 0.000 3.519 2.413 12.213 14.902 0.000 2.595 7.138 0.000 -3.979 0.000 -2.408 0.000
M SE APARTMENT 0.046 -46.344 0.000 0.000 3.515 2.413 12.213 24.077 0.000 2.383 8.086 0.000 -4.074 0.000 -2.315 -0.001
M NE APARTMENT 0.069 -39.299 0.000 0.000 3.519 2.413 12.213 17.602 0.000 2.564 7.253 0.000 -3.917 0.000 -2.416 0.000
M N1 APARTMENT 0.024 -29.699 0.000 0.000 3.517 2.413 12.213 7.027 0.000 2.023 7.080 0.000 -2.380 0.000 -2.217 0.000
M N2 APARTMENT 0.023 -29.803 0.000 0.000 3.517 2.413 12.213 7.022 0.000 2.017 7.197 0.000 -2.381 0.000 -2.217 0.000
M S1 APARTMENT 0.008 -36.344 0.000 0.000 3.506 2.413 12.213 13.515 0.000 1.720 7.591 0.000 -2.482 0.000 -2.141 -0.001
M S2 APARTMENT 0.009 -36.484 0.000 0.000 3.506 2.413 12.213 13.509 0.000 1.718 7.741 0.000 -2.484 0.000 -2.141 -0.001
F6 SW APARTMENT 0.098 -42.622 0.000 0.000 3.519 2.413 12.213 21.248 0.000 2.590 7.044 0.000 -4.080 0.000 -2.423 -0.001
F6 NW APARTMENT 0.163 -35.446 0.000 0.000 3.520 2.413 12.213 14.794 0.000 2.728 6.102 0.000 -3.961 0.000 -2.525 0.000
F6 SE APARTMENT 0.054 -45.105 0.000 0.000 3.515 2.413 12.213 23.873 0.000 2.504 7.014 0.000 -4.055 0.000 -2.427 -0.000
F6 NE APARTMENT 0.081 -38.136 0.000 0.000 3.519 2.413 12.213 17.452 0.000 2.695 6.195 0.000 -3.898 0.000 -2.534 0.000
F6 N1 APARTMENT 0.030 -28.667 0.000 0.000 3.518 2.413 12.213 6.979 0.000 2.117 6.083 0.000 -2.369 0.000 -2.317 0.000
F6 N2 APARTMENT 0.029 -28.769 0.000 0.000 3.518 2.413 12.213 6.974 0.000 2.112 6.198 0.000 -2.370 0.000 -2.318 0.000
F6 S1 APARTMENT 0.011 -35.246 0.000 0.000 3.507 2.413 12.213 13.414 0.000 1.806 6.588 0.000 -2.471 0.000 -2.236 -0.001
F6 S2 APARTMENT 0.011 -35.384 0.000 0.000 3.507 2.413 12.213 13.408 0.000 1.804 6.736 0.000 -2.472 0.000 -2.237 -0.001
F7 SW APARTMENT 0.107 -42.107 0.000 0.000 3.519 2.413 12.213 21.090 0.000 2.696 6.685 0.000 -4.086 0.000 -2.528 -0.000
F7 NW APARTMENT 0.181 -35.018 0.000 0.000 3.520 2.413 12.213 14.683 0.000 2.840 5.772 0.000 -3.967 0.000 -2.637 0.000
F7 SE APARTMENT 0.060 -44.544 0.000 0.000 3.516 2.413 12.213 23.681 0.000 2.607 6.647 0.000 -4.059 0.000 -2.533 -0.001
F7 NE APARTMENT 0.090 -37.650 0.000 0.000 3.519 2.413 12.213 17.305 0.000 2.804 5.854 0.000 -3.902 0.000 -2.647 -0.000
F7 N1 APARTMENT 0.036 -28.283 0.000 0.000 3.518 2.413 12.213 6.926 0.000 2.195 5.769 0.000 -2.372 0.000 -2.415 0.000
F7 N2 APARTMENT 0.035 -28.383 0.000 0.000 3.518 2.413 12.213 6.921 0.000 2.189 5.883 0.000 -2.373 0.000 -2.415 0.000
F7 S1 APARTMENT 0.014 -34.805 0.000 0.000 3.507 2.413 12.213 13.317 0.000 1.879 6.263 0.000 -2.473 0.000 -2.328 -0.000
F7 S2 APARTMENT 0.014 -34.940 0.000 0.000 3.507 2.413 12.213 13.311 0.000 1.878 6.407 0.000 -2.475 0.000 -2.329 -0.000
F8 SW APARTMENT 0.115 -41.929 0.000 0.000 3.519 2.413 12.213 20.942 0.000 2.808 6.653 0.000 -4.104 0.000 -2.630 -0.001
F8 NW APARTMENT 0.197 -34.906 0.000 0.000 3.520 2.413 12.213 14.577 0.000 2.958 5.757 0.000 -3.985 0.000 -2.744 0.000
F8 SE APARTMENT 0.065 -44.327 0.000 0.000 3.516 2.413 12.213 23.502 0.000 2.715 6.612 0.000 -4.075 0.000 -2.634 -0.001
F8 NE APARTMENT 0.099 -37.485 0.000 0.000 3.520 2.413 12.213 17.166 0.000 2.918 5.828 0.000 -3.917 0.000 -2.755 -0.000
F8 N1 APARTMENT 0.042 -28.211 0.000 0.000 3.518 2.413 12.213 6.873 0.000 2.283 5.761 0.000 -2.384 0.000 -2.509 0.000
F8 N2 APARTMENT 0.041 -28.310 0.000 0.000 3.518 2.413 12.213 6.868 0.000 2.276 5.874 0.000 -2.385 0.000 -2.509 0.000
F8 S1 APARTMENT 0.017 -34.691 0.000 0.000 3.508 2.413 12.213 13.226 0.000 1.962 6.252 0.000 -2.483 0.000 -2.416 -0.001
F8 S2 APARTMENT 0.017 -34.824 0.000 0.000 3.508 2.413 12.213 13.220 0.000 1.960 6.395 0.000 -2.484 0.000 -2.417 -0.001
F9 SW APARTMENT 0.129 -42.516 0.000 0.000 3.519 2.413 12.213 20.788 0.000 2.919 7.411 0.000 -4.150 0.000 -2.726 -0.000
F9 NW APARTMENT 0.218 -35.477 0.000 0.000 3.521 2.413 12.213 14.460 0.000 3.074 6.453 0.000 -4.030 0.000 -2.846 0.000
F9 SE APARTMENT 0.073 -44.922 0.000 0.000 3.516 2.413 12.213 23.318 0.000 2.825 7.411 0.000 -4.118 0.000 -2.730 -0.000
F9 NE APARTMENT 0.111 -38.037 0.000 0.000 3.520 2.413 12.213 17.017 0.000 3.033 6.547 0.000 -3.959 0.000 -2.856 -0.000
F9 N1 APARTMENT 0.054 -28.790 0.000 0.000 3.519 2.413 12.213 6.813 0.000 2.378 6.412 0.000 -2.412 0.000 -2.599 0.000
F9 N2 APARTMENT 0.052 -28.892 0.000 0.000 3.518 2.413 12.213 6.807 0.000 2.372 6.528 0.000 -2.413 0.000 -2.599 0.000
F9 S1 APARTMENT 0.022 -35.311 0.000 0.000 3.509 2.413 12.213 13.136 0.000 2.052 6.975 0.000 -2.509 0.000 -2.500 -0.000
F9 S2 APARTMENT 0.022 -35.452 0.000 0.000 3.509 2.413 12.213 13.130 0.000 2.052 7.124 0.000 -2.510 0.000 -2.500 -0.000
T SW APARTMENT 0.308 -42.219 0.000 0.000 3.522 2.413 12.213 20.157 0.000 2.985 7.329 0.000 -3.951 0.000 -2.756 -0.000
T NW APARTMENT 0.443 -35.800 0.000 0.000 3.524 2.413 12.213 13.909 0.000 3.145 6.847 0.000 -3.824 0.000 -2.870 0.000
T SE APARTMENT 0.202 -44.290 0.000 0.000 3.520 2.413 12.213 22.629 0.000 2.898 7.083 0.000 -3.907 0.000 -2.761 -0.001
T NE APARTMENT 0.267 -38.085 0.000 0.000 3.525 2.413 12.213 16.430 0.000 3.116 6.755 0.000 -3.751 0.000 -2.883 -0.000
T N1 APARTMENT 0.128 -29.553 0.000 0.000 3.524 2.413 12.213 6.587 0.000 2.476 7.076 0.000 -2.259 0.000 -2.604 0.000
T N2 APARTMENT 0.123 -29.651 0.000 0.000 3.524 2.413 12.213 6.580 0.000 2.469 7.191 0.000 -2.258 0.000 -2.603 0.000
T S1 APARTMENT 0.093 -35.800 0.000 0.000 3.517 2.413 12.213 12.808 0.000 2.220 7.470 0.000 -2.422 0.000 -2.512 -0.001
T S2 APARTMENT 0.093 -35.927 0.000 0.000 3.517 2.413 12.213 12.799 0.000 2.218 7.609 0.000 -2.421 0.000 -2.513 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 6.933 0.000 4.690 0.000 0.000 -0.959 0.000 -4.068 -25.126
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.992 0.000 0.057 0.000 0.000 -0.640 0.000 -0.127 -20.811
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.901 0.000 0.063 0.000 0.000 -0.672 0.000 -0.162 -20.659
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.838 0.000 0.066 0.000 0.000 -0.693 0.000 -0.189 -20.551
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 2.745 0.000 0.051 0.000 0.000 -0.755 0.000 -0.255 -38.846
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.772 0.000 0.076 0.000 0.000 -0.701 0.000 -0.221 -20.455
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.758 0.000 0.083 0.000 0.000 -0.690 0.000 -0.228 -20.453
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.736 0.000 0.087 0.000 0.000 -0.693 0.000 -0.240 -20.419
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.708 0.000 0.086 0.000 0.000 -0.708 0.000 -0.257 -20.359
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 2.551 0.000 0.038 0.000 0.000 -0.719 0.000 -0.342 -27.994
Total Facility 6.984 -2769.746 0.000 0.000 278.351 416.414 980.287 1230.438 0.000 174.866 455.395 0.000 -257.352 0.000 -184.496 -331.164


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 28-SEP-15:30 0.00 -2944.73 0.00 0.00 48.76 100.83 470.89 3513.65 0.00 62.52 0.00 0.00 0.00 0.00 0.00 -1251.91
G NW APARTMENT 03-SEP-16:10 0.00 -2661.95 0.00 0.00 84.77 144.04 588.62 2589.18 0.00 126.84 0.00 0.00 0.00 0.00 0.00 -871.50
OFFICE 15-DEC-11:30 0.00 -3731.17 0.00 0.00 65.18 1622.33 544.91 4093.43 0.00 73.41 0.00 0.00 0.00 0.00 0.00 -2668.09
G NE APARTMENT 18-JUL-09:45 0.00 -2251.91 0.00 0.00 40.05 28.81 406.15 2652.55 0.00 105.49 0.00 0.00 0.00 0.00 0.00 -981.13
G N1 APARTMENT 01-JUL-17:10 0.00 -1379.13 0.00 0.00 141.82 194.45 588.62 692.60 0.00 29.67 0.00 0.00 0.00 0.00 0.00 -268.03
G N2 APARTMENT 03-JUN-17:30 0.00 -1371.61 0.00 0.00 141.82 194.45 588.62 261.07 0.00 305.75 0.00 0.00 0.00 0.00 0.00 -120.10
G S1 APARTMENT 21-JAN-13:00 0.00 -1732.89 0.00 0.00 39.58 28.81 406.15 2856.31 0.00 96.19 0.00 0.00 0.00 0.00 0.00 -1694.15
G S2 APARTMENT 21-JAN-13:00 0.00 -1783.31 0.00 0.00 39.72 28.81 406.15 2856.93 0.00 103.34 0.00 0.00 0.00 0.00 0.00 -1651.64
F2 SW APARTMENT 29-JAN-15:30 0.00 -3658.95 0.00 0.00 40.50 50.41 400.26 3924.34 0.00 15.63 0.00 0.00 0.00 0.00 0.00 -772.19
F2 NW APARTMENT 03-SEP-16:10 0.00 -3148.03 0.00 0.00 84.77 144.04 588.62 2520.47 0.00 181.83 0.00 0.00 0.00 0.00 0.00 -371.70
F2 SE APARTMENT 21-JAN-12:45 0.00 -3293.81 0.00 0.00 40.75 28.81 406.15 3122.66 0.00 183.62 0.00 0.00 0.00 0.00 0.00 -488.18
F2 NE APARTMENT 18-JUL-10:00 0.00 -2686.58 0.00 0.00 40.37 28.81 406.15 2297.78 0.00 171.97 0.00 0.00 0.00 0.00 0.00 -258.51
F2 N1 APARTMENT 03-JUN-17:30 0.00 -1767.04 0.00 0.00 141.82 194.45 588.62 237.91 0.00 378.30 225.94 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 03-JUN-17:30 0.00 -1754.60 0.00 0.00 141.82 194.45 588.62 237.98 0.00 377.10 214.63 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 20-JAN-13:00 0.00 -2220.76 0.00 0.00 40.27 28.81 406.15 2309.69 0.00 131.41 0.00 0.00 0.00 0.00 0.00 -695.58
F2 S2 APARTMENT 20-JAN-13:00 0.00 -2240.79 0.00 0.00 40.28 28.81 406.15 2309.24 0.00 131.88 0.00 0.00 0.00 0.00 0.00 -675.56
F3 SW APARTMENT 26-FEB-17:00 0.00 -3771.59 0.00 0.00 48.90 100.83 470.89 2893.67 0.00 385.67 0.00 0.00 0.00 0.00 0.00 -128.38
F3 NW APARTMENT 03-SEP-16:10 0.00 -3158.17 0.00 0.00 84.77 144.04 588.62 2487.39 0.00 214.71 0.00 0.00 0.00 0.00 0.00 -361.36
F3 SE APARTMENT 21-JAN-11:00 0.00 -3188.34 0.00 0.00 40.75 28.81 406.15 3726.03 0.00 87.00 0.00 0.00 0.00 0.00 0.00 -1100.40
F3 NE APARTMENT 18-JUL-10:00 0.00 -2695.18 0.00 0.00 40.46 28.81 406.15 2228.93 0.00 203.96 0.00 0.00 0.00 0.00 0.00 -213.13
F3 N1 APARTMENT 30-MAY-17:00 0.00 -1842.62 0.00 0.00 84.76 144.04 588.62 440.00 0.00 567.50 17.70 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 30-MAY-17:00 0.00 -1830.38 0.00 0.00 84.76 144.04 588.62 440.01 0.00 565.69 7.26 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 20-JAN-13:00 0.00 -2270.45 0.00 0.00 40.15 28.81 406.15 2260.14 0.00 140.07 0.00 0.00 0.00 0.00 0.00 -604.86
F3 S2 APARTMENT 20-JAN-13:00 0.00 -2279.93 0.00 0.00 40.14 28.81 406.15 2259.64 0.00 139.54 0.00 0.00 0.00 0.00 0.00 -594.35
F4 SW APARTMENT 26-FEB-17:00 0.00 -3789.19 0.00 0.00 48.90 100.83 470.89 2854.99 0.00 414.90 0.00 0.00 0.00 0.00 0.00 -101.32
F4 NW APARTMENT 03-SEP-16:10 0.00 -3170.21 0.00 0.00 84.77 144.04 588.62 2463.65 0.00 239.36 0.00 0.00 0.00 0.00 0.00 -350.23
F4 SE APARTMENT 21-JAN-11:00 0.00 -3176.40 0.00 0.00 40.75 28.81 406.15 3664.12 0.00 94.95 0.00 0.00 0.00 0.00 0.00 -1058.38
F4 NE APARTMENT 21-MAY-09:30 0.00 -2698.68 0.00 0.00 40.76 28.81 406.15 2852.26 0.00 17.59 0.00 0.00 0.00 0.00 0.00 -646.89
F4 N1 APARTMENT 30-MAY-17:00 0.00 -1871.03 0.00 0.00 84.76 144.04 588.62 429.56 0.00 613.78 10.27 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 31-MAY-16:30 0.00 -1865.46 0.00 0.00 84.76 144.04 588.62 401.25 0.00 538.48 108.30 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 20-JAN-13:00 0.00 -2296.84 0.00 0.00 40.22 28.81 406.15 2228.50 0.00 155.44 0.00 0.00 0.00 0.00 0.00 -562.27
F4 S2 APARTMENT 20-JAN-13:00 0.00 -2304.59 0.00 0.00 40.21 28.81 406.15 2228.02 0.00 154.74 0.00 0.00 0.00 0.00 0.00 -553.34
M SW APARTMENT 26-FEB-17:00 0.00 -3828.20 0.00 0.00 48.90 100.83 470.89 2823.76 0.00 439.70 0.00 0.00 0.00 0.00 0.00 -55.88
M NW APARTMENT 03-SEP-16:10 0.00 -3205.13 0.00 0.00 84.77 144.04 588.62 2443.67 0.00 259.44 0.00 0.00 0.00 0.00 0.00 -315.40
M SE APARTMENT 21-JAN-11:00 0.00 -3202.42 0.00 0.00 40.75 28.81 406.15 3614.43 0.00 102.76 0.00 0.00 0.00 0.00 0.00 -990.48
M NE APARTMENT 21-MAY-09:30 0.00 -2728.61 0.00 0.00 40.76 28.81 406.15 2843.79 0.00 19.02 0.00 0.00 0.00 0.00 0.00 -609.92
M N1 APARTMENT 31-MAY-16:30 0.00 -1919.53 0.00 0.00 84.76 144.04 588.62 392.77 0.00 574.87 134.46 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 31-MAY-16:30 0.00 -1924.45 0.00 0.00 84.76 144.04 588.62 392.54 0.00 574.88 139.60 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 20-JAN-13:00 0.00 -2343.22 0.00 0.00 40.32 28.81 406.15 2203.68 0.00 170.43 0.00 0.00 0.00 0.00 0.00 -506.17
M S2 APARTMENT 20-JAN-13:00 0.00 -2350.54 0.00 0.00 40.31 28.81 406.15 2203.21 0.00 169.68 0.00 0.00 0.00 0.00 0.00 -497.61
F6 SW APARTMENT 26-FEB-17:00 0.00 -3789.29 0.00 0.00 48.90 100.83 470.89 2800.91 0.00 459.55 0.00 0.00 0.00 0.00 0.00 -91.80
F6 NW APARTMENT 03-SEP-16:10 0.00 -3173.84 0.00 0.00 84.77 144.04 588.62 2430.07 0.00 276.54 0.00 0.00 0.00 0.00 0.00 -350.20
F6 SE APARTMENT 21-JAN-11:00 0.00 -3152.65 0.00 0.00 40.75 28.81 406.15 3576.50 0.00 107.76 0.00 0.00 0.00 0.00 0.00 -1007.32
F6 NE APARTMENT 21-MAY-09:30 0.00 -2690.58 0.00 0.00 40.76 28.81 406.15 2838.93 0.00 20.23 0.00 0.00 0.00 0.00 0.00 -644.29
F6 N1 APARTMENT 31-MAY-16:30 0.00 -1909.18 0.00 0.00 84.76 144.04 588.62 387.92 0.00 604.60 99.24 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 31-MAY-16:30 0.00 -1897.81 0.00 0.00 84.76 144.04 588.62 387.69 0.00 601.40 91.30 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 20-JAN-13:00 0.00 -2315.03 0.00 0.00 40.39 28.81 406.15 2185.07 0.00 181.91 0.00 0.00 0.00 0.00 0.00 -527.28
F6 S2 APARTMENT 20-JAN-13:00 0.00 -2322.15 0.00 0.00 40.37 28.81 406.15 2184.60 0.00 181.14 0.00 0.00 0.00 0.00 0.00 -518.92
F7 SW APARTMENT 26-FEB-17:00 0.00 -3768.99 0.00 0.00 48.90 100.83 470.89 2780.29 0.00 475.94 0.00 0.00 0.00 0.00 0.00 -107.87
F7 NW APARTMENT 03-SEP-16:10 0.00 -3166.66 0.00 0.00 84.77 144.04 588.62 2417.29 0.00 291.51 0.00 0.00 0.00 0.00 0.00 -359.57
F7 SE APARTMENT 22-DEC-14:00 0.00 -3124.48 0.00 0.00 40.70 28.81 388.49 2567.48 0.00 346.54 0.00 0.00 0.00 0.00 0.00 -247.53
F7 NE APARTMENT 21-MAY-09:15 0.00 -2676.92 0.00 0.00 40.76 28.81 406.15 2979.73 0.00 9.61 0.00 0.00 0.00 0.00 0.00 -788.14
F7 N1 APARTMENT 31-MAY-16:30 0.00 -1906.72 0.00 0.00 84.76 144.04 588.62 383.01 0.00 627.44 78.85 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 05-APR-17:00 0.00 -1901.87 0.00 0.00 84.76 144.04 588.62 169.26 0.00 740.71 174.48 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 20-JAN-13:00 0.00 -2311.62 0.00 0.00 40.45 28.81 406.15 2168.62 0.00 192.43 0.00 0.00 0.00 0.00 0.00 -524.84
F7 S2 APARTMENT 20-JAN-13:00 0.00 -2318.58 0.00 0.00 40.44 28.81 406.15 2168.15 0.00 191.63 0.00 0.00 0.00 0.00 0.00 -516.59
F8 SW APARTMENT 26-FEB-17:00 0.00 -3758.99 0.00 0.00 48.90 100.83 470.89 2761.71 0.00 490.11 0.00 0.00 0.00 0.00 0.00 -113.46
F8 NW APARTMENT 03-SEP-16:10 0.00 -3171.63 0.00 0.00 84.77 144.04 588.62 2405.30 0.00 304.87 0.00 0.00 0.00 0.00 0.00 -355.98
F8 SE APARTMENT 21-JAN-13:15 0.00 -3124.70 0.00 0.00 40.63 28.81 388.49 2618.82 0.00 332.58 0.00 0.00 0.00 0.00 0.00 -284.63
F8 NE APARTMENT 21-MAY-09:15 0.00 -2675.85 0.00 0.00 40.76 28.81 406.15 2976.96 0.00 10.02 0.00 0.00 0.00 0.00 0.00 -786.84
F8 N1 APARTMENT 31-MAY-16:15 0.00 -1929.26 0.00 0.00 84.76 144.04 588.62 396.97 0.00 806.62 0.00 0.00 0.00 0.00 0.00 -91.75
F8 N2 APARTMENT 05-APR-17:00 0.00 -1924.36 0.00 0.00 84.76 144.04 588.62 168.02 0.00 766.95 171.97 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 20-JAN-13:00 0.00 -2321.22 0.00 0.00 40.53 28.81 406.15 2154.15 0.00 203.02 0.00 0.00 0.00 0.00 0.00 -511.44
F8 S2 APARTMENT 20-JAN-13:00 0.00 -2328.07 0.00 0.00 40.52 28.81 406.15 2153.68 0.00 202.19 0.00 0.00 0.00 0.00 0.00 -503.28
F9 SW APARTMENT 26-FEB-17:00 0.00 -3816.31 0.00 0.00 48.90 100.83 470.89 2741.14 0.00 502.49 0.00 0.00 0.00 0.00 0.00 -47.95
F9 NW APARTMENT 03-SEP-16:10 0.00 -3245.00 0.00 0.00 84.77 144.04 588.62 2390.03 0.00 316.96 0.00 0.00 0.00 0.00 0.00 -279.42
F9 SE APARTMENT 21-JAN-13:15 0.00 -3166.36 0.00 0.00 40.71 28.81 388.49 2599.36 0.00 348.53 0.00 0.00 0.00 0.00 0.00 -239.53
F9 NE APARTMENT 31-MAY-09:30 0.00 -2694.16 0.00 0.00 40.62 28.81 406.15 1920.14 0.00 753.04 0.00 0.00 0.00 0.00 0.00 -454.61
F9 N1 APARTMENT 31-MAY-16:15 0.00 -2001.73 0.00 0.00 84.76 144.04 588.62 390.88 0.00 834.85 0.00 0.00 0.00 0.00 0.00 -41.42
F9 N2 APARTMENT 31-MAY-16:15 0.00 -1990.32 0.00 0.00 84.76 144.04 588.62 390.64 0.00 831.05 0.00 0.00 0.00 0.00 0.00 -48.78
F9 S1 APARTMENT 20-JAN-13:15 0.00 -2378.71 0.00 0.00 40.62 28.81 388.49 2065.10 0.00 195.09 0.00 0.00 0.00 0.00 0.00 -339.39
F9 S2 APARTMENT 20-JAN-13:00 0.00 -2386.87 0.00 0.00 40.70 28.81 406.15 2141.39 0.00 220.19 0.00 0.00 0.00 0.00 0.00 -450.36
T SW APARTMENT 04-DEC-14:45 0.00 -4211.05 0.00 0.00 40.75 28.81 382.60 3053.03 0.00 732.46 0.00 0.00 0.00 0.00 0.00 -26.60
T NW APARTMENT 03-SEP-16:10 0.00 -3721.35 0.00 0.00 84.78 144.04 588.62 2315.60 0.00 327.99 260.32 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 28-JAN-12:30 0.00 -3623.24 0.00 0.00 38.16 28.81 406.15 3169.54 0.00 46.11 0.00 0.00 0.00 0.00 0.00 -65.52
T NE APARTMENT 21-MAY-10:00 0.00 -3249.67 0.00 0.00 40.42 28.81 406.15 2374.91 0.00 55.69 343.69 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 31-MAY-16:15 0.00 -2287.16 0.00 0.00 84.76 144.04 588.62 375.23 0.00 885.47 209.04 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 31-MAY-16:15 0.00 -2262.47 0.00 0.00 84.76 144.04 588.62 375.29 0.00 879.52 190.25 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 22-DEC-14:00 0.00 -2837.24 0.00 0.00 39.06 28.81 388.49 2321.10 0.00 205.61 0.00 0.00 0.00 0.00 0.00 -145.83
T S2 APARTMENT 22-DEC-14:00 0.00 -2842.85 0.00 0.00 39.05 28.81 388.49 2320.54 0.00 204.86 0.00 0.00 0.00 0.00 0.00 -138.88
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-NOV-14:23 0.00 -187546.61 0.00 0.00 3264.34 10361.29 30924.05 118389.73 0.00 63090.19 0.00 0.00 0.00 0.00 -51.69 -38431.30


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-FEB-06:20 261.46 0.00 0.00 0.00 186.20 100.83 317.85 0.00 0.00 0.00 687.93 0.00 -575.17 0.00 -979.09 0.00
G NW APARTMENT 12-FEB-08:05 466.83 0.00 0.00 0.00 73.80 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -158.89 0.00 -796.45 -16.99
OFFICE 05-FEB-08:08 235.58 0.00 0.00 0.00 0.00 379.58 128.69 119.25 0.00 0.00 0.00 0.00 0.00 0.00 -14.62 -848.48
G NE APARTMENT 11-FEB-06:20 396.61 0.00 0.00 0.00 189.25 100.83 317.85 0.00 0.00 0.00 452.98 0.00 -544.32 0.00 -913.21 0.00
G N1 APARTMENT 12-FEB-08:00 312.93 0.00 0.00 0.00 149.21 93.62 382.60 0.00 0.00 0.00 294.76 0.00 -195.53 0.00 -1037.59 0.00
G N2 APARTMENT 12-FEB-08:00 332.96 0.00 0.00 0.00 149.33 93.62 382.60 0.00 0.00 0.00 273.11 0.00 -195.06 0.00 -1036.56 0.00
G S1 APARTMENT 23-APR-07:38 85.06 0.00 0.00 0.00 63.68 43.21 388.49 207.27 0.00 0.00 0.00 0.00 0.00 0.00 -90.28 -697.44
G S2 APARTMENT 13-FEB-06:15 88.15 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 0.00 0.00 -91.97 0.00 -191.04 -386.81
F2 SW APARTMENT 12-FEB-07:55 287.18 0.00 0.00 0.00 138.54 93.62 382.60 0.00 0.00 0.00 671.91 0.00 -11.06 0.00 -1562.80 0.00
F2 NW APARTMENT 12-FEB-08:05 308.49 0.00 0.00 0.00 71.13 43.21 388.49 0.00 0.00 0.00 468.85 0.00 -257.46 0.00 -1022.71 0.00
F2 SE APARTMENT 27-APR-05:20 213.06 0.00 0.00 0.00 167.47 100.83 317.85 0.00 0.00 0.00 610.23 0.00 -435.13 0.00 -974.32 0.00
F2 NE APARTMENT 11-FEB-06:10 196.52 0.00 0.00 0.00 164.18 100.83 317.85 0.00 0.00 0.00 1336.75 0.00 -689.16 0.00 -1426.97 0.00
F2 N1 APARTMENT 11-JAN-06:15 90.54 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 83.66 0.00 -198.16 0.00 -557.71 0.00
F2 N2 APARTMENT 11-JAN-06:15 88.99 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 85.23 0.00 -198.25 0.00 -557.65 0.00
F2 S1 APARTMENT 27-APR-05:20 77.23 0.00 0.00 0.00 168.08 100.83 317.85 0.00 0.00 0.00 523.33 0.00 -264.71 0.00 -922.61 0.00
F2 S2 APARTMENT 27-APR-05:20 78.97 0.00 0.00 0.00 168.02 100.83 317.85 0.00 0.00 0.00 523.64 0.00 -264.96 0.00 -924.35 0.00
F3 SW APARTMENT 27-APR-05:20 268.62 0.00 0.00 0.00 167.16 100.83 317.85 0.00 0.00 0.00 717.17 0.00 -449.46 0.00 -1122.17 0.00
F3 NW APARTMENT 12-FEB-07:55 312.28 0.00 0.00 0.00 138.90 93.62 382.60 0.00 0.00 0.00 1099.40 0.00 -461.76 0.00 -1565.04 0.00
F3 SE APARTMENT 27-APR-05:20 201.29 0.00 0.00 0.00 168.00 100.83 317.85 0.00 0.00 0.00 751.97 0.00 -443.98 0.00 -1095.96 0.00
F3 NE APARTMENT 11-FEB-06:10 189.05 0.00 0.00 0.00 163.15 100.83 317.85 0.00 0.00 0.00 1446.90 0.00 -711.22 0.00 -1506.56 0.00
F3 N1 APARTMENT 11-JAN-06:15 91.71 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 182.11 0.00 -204.70 0.00 -650.80 0.00
F3 N2 APARTMENT 11-JAN-06:15 90.20 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 183.61 0.00 -204.77 0.00 -650.71 0.00
F3 S1 APARTMENT 27-APR-05:20 79.62 0.00 0.00 0.00 167.76 100.83 317.85 0.00 0.00 0.00 669.97 0.00 -273.95 0.00 -1062.08 0.00
F3 S2 APARTMENT 27-APR-05:20 80.57 0.00 0.00 0.00 167.75 100.83 317.85 0.00 0.00 0.00 669.41 0.00 -273.97 0.00 -1062.43 0.00
F4 SW APARTMENT 27-APR-05:20 281.26 0.00 0.00 0.00 167.78 100.83 317.85 0.00 0.00 0.00 797.21 0.00 -453.76 0.00 -1211.16 0.00
F4 NW APARTMENT 12-FEB-08:10 300.49 0.00 0.00 0.00 63.57 43.21 388.49 0.00 0.00 0.00 906.00 0.00 -339.62 0.00 -1362.14 0.00
F4 SE APARTMENT 27-APR-05:20 209.45 0.00 0.00 0.00 168.71 100.83 317.85 0.00 0.00 0.00 830.41 0.00 -447.15 0.00 -1180.09 0.00
F4 NE APARTMENT 27-APR-05:20 196.76 0.00 0.00 0.00 168.99 100.83 317.85 0.00 0.00 0.00 825.76 0.00 -439.35 0.00 -1170.84 0.00
F4 N1 APARTMENT 11-JAN-06:15 98.01 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 237.05 0.00 -206.76 0.00 -709.98 0.00
F4 N2 APARTMENT 11-JAN-06:15 96.46 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 238.57 0.00 -206.83 0.00 -709.88 0.00
F4 S1 APARTMENT 03-MAR-08:05 88.16 0.00 0.00 0.00 63.57 43.21 388.49 0.00 0.00 0.00 38.05 0.00 -9.61 0.00 -611.87 0.00
F4 S2 APARTMENT 03-MAR-08:05 88.79 0.00 0.00 0.00 63.57 43.21 388.49 0.00 0.00 0.00 37.40 0.00 -9.59 0.00 -611.88 0.00
M SW APARTMENT 27-APR-05:20 292.63 0.00 0.00 0.00 168.16 100.83 317.85 0.00 0.00 0.00 869.64 0.00 -458.76 0.00 -1290.34 0.00
M NW APARTMENT 12-FEB-08:10 309.99 0.00 0.00 0.00 63.57 43.21 388.49 0.00 0.00 0.00 935.49 0.00 -351.29 0.00 -1389.46 0.00
M SE APARTMENT 27-APR-05:20 218.24 0.00 0.00 0.00 169.09 100.83 317.85 0.00 0.00 0.00 903.24 0.00 -452.11 0.00 -1257.14 0.00
M NE APARTMENT 27-APR-05:20 205.01 0.00 0.00 0.00 169.35 100.83 317.85 0.00 0.00 0.00 898.42 0.00 -443.32 0.00 -1248.14 0.00
M N1 APARTMENT 11-JAN-06:15 104.67 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 285.74 0.00 -209.10 0.00 -762.99 0.00
M N2 APARTMENT 11-JAN-06:15 103.11 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 287.26 0.00 -209.17 0.00 -762.88 0.00
M S1 APARTMENT 27-APR-05:20 96.32 0.00 0.00 0.00 168.58 100.83 317.85 0.00 0.00 0.00 822.78 0.00 -280.72 0.00 -1225.65 0.00
M S2 APARTMENT 27-APR-05:20 97.13 0.00 0.00 0.00 168.58 100.83 317.85 0.00 0.00 0.00 821.99 0.00 -280.70 0.00 -1225.68 0.00
F6 SW APARTMENT 27-APR-05:20 303.24 0.00 0.00 0.00 169.10 100.83 317.85 0.00 0.00 0.00 902.88 0.00 -457.87 0.00 -1336.03 0.00
F6 NW APARTMENT 12-FEB-08:10 310.27 0.00 0.00 0.00 63.59 43.21 388.49 0.00 0.00 0.00 959.68 0.00 -355.14 0.00 -1410.11 0.00
F6 SE APARTMENT 27-APR-05:20 225.37 0.00 0.00 0.00 170.06 100.83 317.85 0.00 0.00 0.00 936.41 0.00 -450.20 0.00 -1300.32 0.00
F6 NE APARTMENT 27-APR-05:20 211.42 0.00 0.00 0.00 170.34 100.83 317.85 0.00 0.00 0.00 930.90 0.00 -441.09 0.00 -1290.24 0.00
F6 N1 APARTMENT 11-JAN-06:15 109.66 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 308.02 0.00 -208.43 0.00 -790.93 0.00
F6 N2 APARTMENT 11-JAN-06:15 108.05 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 309.56 0.00 -208.49 0.00 -790.79 0.00
F6 S1 APARTMENT 27-APR-05:20 101.62 0.00 0.00 0.00 169.53 100.83 317.85 0.00 0.00 0.00 858.33 0.00 -279.87 0.00 -1268.29 0.00
F6 S2 APARTMENT 27-APR-05:20 102.44 0.00 0.00 0.00 169.53 100.83 317.85 0.00 0.00 0.00 857.52 0.00 -279.84 0.00 -1268.32 0.00
F7 SW APARTMENT 27-APR-05:20 312.37 0.00 0.00 0.00 169.76 100.83 317.85 0.00 0.00 0.00 940.02 0.00 -458.33 0.00 -1382.50 0.00
F7 NW APARTMENT 08-FEB-07:25 319.87 0.00 0.00 0.00 138.54 93.62 382.60 0.00 0.00 0.00 1234.01 0.00 -598.01 0.00 -1570.64 0.00
F7 SE APARTMENT 27-APR-05:20 231.88 0.00 0.00 0.00 170.74 100.83 317.85 0.00 0.00 0.00 973.80 0.00 -450.36 0.00 -1344.74 0.00
F7 NE APARTMENT 27-APR-05:20 217.35 0.00 0.00 0.00 171.01 100.83 317.85 0.00 0.00 0.00 967.99 0.00 -440.91 0.00 -1334.12 0.00
F7 N1 APARTMENT 11-JAN-06:15 114.60 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 332.68 0.00 -208.74 0.00 -820.21 0.00
F7 N2 APARTMENT 11-JAN-06:15 112.96 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 334.24 0.00 -208.81 0.00 -820.07 0.00
F7 S1 APARTMENT 27-APR-05:20 107.04 0.00 0.00 0.00 170.18 100.83 317.85 0.00 0.00 0.00 896.80 0.00 -280.26 0.00 -1312.43 0.00
F7 S2 APARTMENT 27-APR-05:20 107.85 0.00 0.00 0.00 170.17 100.83 317.85 0.00 0.00 0.00 895.98 0.00 -280.23 0.00 -1312.46 0.00
F8 SW APARTMENT 27-APR-05:20 320.92 0.00 0.00 0.00 170.28 100.83 317.85 0.00 0.00 0.00 977.40 0.00 -459.65 0.00 -1427.62 0.00
F8 NW APARTMENT 08-FEB-07:25 329.12 0.00 0.00 0.00 138.55 93.62 382.60 0.00 0.00 0.00 1242.02 0.00 -602.16 0.00 -1583.75 0.00
F8 SE APARTMENT 27-APR-05:20 238.29 0.00 0.00 0.00 171.26 100.83 317.85 0.00 0.00 0.00 1011.48 0.00 -451.66 0.00 -1388.04 0.00
F8 NE APARTMENT 27-APR-05:20 223.22 0.00 0.00 0.00 171.54 100.83 317.85 0.00 0.00 0.00 1005.34 0.00 -441.88 0.00 -1376.90 0.00
F8 N1 APARTMENT 11-JAN-06:15 119.76 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 356.96 0.00 -209.49 0.00 -848.90 0.00
F8 N2 APARTMENT 11-JAN-06:15 118.10 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 358.55 0.00 -209.56 0.00 -848.76 0.00
F8 S1 APARTMENT 27-APR-05:20 112.66 0.00 0.00 0.00 170.66 100.83 317.85 0.00 0.00 0.00 935.03 0.00 -281.20 0.00 -1355.83 0.00
F8 S2 APARTMENT 27-APR-05:20 113.48 0.00 0.00 0.00 170.66 100.83 317.85 0.00 0.00 0.00 934.20 0.00 -281.17 0.00 -1355.85 0.00
F9 SW APARTMENT 27-APR-05:20 340.07 0.00 0.00 0.00 170.76 100.83 317.85 0.00 0.00 0.00 998.36 0.00 -459.83 0.00 -1468.05 0.00
F9 NW APARTMENT 08-FEB-07:25 346.80 0.00 0.00 0.00 139.03 93.62 382.60 0.00 0.00 0.00 1229.57 0.00 -600.35 0.00 -1591.27 0.00
F9 SE APARTMENT 27-APR-05:20 250.87 0.00 0.00 0.00 171.81 100.83 317.85 0.00 0.00 0.00 1034.34 0.00 -451.39 0.00 -1424.31 0.00
F9 NE APARTMENT 27-APR-05:20 234.51 0.00 0.00 0.00 172.10 100.83 317.85 0.00 0.00 0.00 1028.52 0.00 -441.26 0.00 -1412.55 0.00
F9 N1 APARTMENT 11-JAN-06:15 131.77 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 373.21 0.00 -210.03 0.00 -876.62 0.00
F9 N2 APARTMENT 11-JAN-06:15 130.08 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 374.76 0.00 -210.10 0.00 -876.43 0.00
F9 S1 APARTMENT 27-APR-05:20 124.68 0.00 0.00 0.00 171.12 100.83 317.85 0.00 0.00 0.00 962.14 0.00 -281.69 0.00 -1394.93 0.00
F9 S2 APARTMENT 27-APR-05:20 125.62 0.00 0.00 0.00 171.12 100.83 317.85 0.00 0.00 0.00 961.15 0.00 -281.65 0.00 -1394.92 0.00
T SW APARTMENT 27-APR-05:20 468.50 0.00 0.00 0.00 173.58 100.83 317.85 0.00 0.00 0.00 752.74 0.00 -425.42 0.00 -1388.08 0.00
T NW APARTMENT 27-APR-05:20 461.33 0.00 0.00 0.00 173.68 100.83 317.85 0.00 0.00 0.00 744.60 0.00 -414.91 0.00 -1383.38 0.00
T SE APARTMENT 27-APR-05:20 369.07 0.00 0.00 0.00 174.83 100.83 317.85 0.00 0.00 0.00 787.66 0.00 -417.52 0.00 -1332.71 0.00
T NE APARTMENT 11-FEB-06:20 420.98 0.00 0.00 0.00 188.49 100.83 317.85 0.00 0.00 0.00 863.06 0.00 -612.72 0.00 -1278.49 0.00
T N1 APARTMENT 27-APR-05:20 201.42 0.00 0.00 0.00 174.34 100.83 317.85 0.00 0.00 0.00 754.88 0.00 -250.88 0.00 -1298.45 0.00
T N2 APARTMENT 27-APR-05:20 197.38 0.00 0.00 0.00 174.40 100.83 317.85 0.00 0.00 0.00 756.43 0.00 -250.76 0.00 -1296.13 0.00
T S1 APARTMENT 27-APR-05:20 236.15 0.00 0.00 0.00 173.85 100.83 317.85 0.00 0.00 0.00 756.31 0.00 -265.30 0.00 -1319.69 0.00
T S2 APARTMENT 27-APR-05:20 237.00 0.00 0.00 0.00 173.85 100.83 317.85 0.00 0.00 0.00 755.37 0.00 -265.25 0.00 -1319.64 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-APR-05:20 14883.08 0.00 0.00 0.00 13436.07 14808.05 25648.68 0.00 0.00 0.00 55161.61 0.00 -28835.73 0.00 -95101.75 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Sec1.1A-General Information

Data
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1598.50
Number of hours not met 1598.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.75 10720.10 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 0.00 0.00 0.00 0.00
Space Cooling 1427.28 77786.12 0.00 0.00 0.00 0.00
Pumps 55.02 1760.93 0.00 0.00 0.00 0.00
Heat Rejection 65.97 3126.26 0.00 0.00 0.00 0.00
Fans-Interior 578.08 18330.67 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 814.51 76144.64 0.00 0.00
Receptacle Equipment 1131.09 51564.86 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3863.42   814.51   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3863.42
Natural Gas 0.00 814.51
Additional 0.00 0.00
Total 1131.09 4677.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 0.00
Space Cooling 182.13
Fans-Interior 73.77
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 39.63
Subtotal 493.00


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 103.94
Miscellaneous 0.00
Subtotal 103.94


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 8.90
Space Heating 0.00
Space Cooling 30.51
Fans-Interior 12.36
Service Water Heating 17.41
Receptacle Equipment 24.18
Miscellaneous 6.64



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.242824
G NW APARTMENT DIRECT AIR 0.241158
OFFICE DIRECT AIR 0.293404
G NE APARTMENT DIRECT AIR 0.186589
G N1 APARTMENT DIRECT AIR 0.113686
G N2 APARTMENT DIRECT AIR 0.112075
G S1 APARTMENT DIRECT AIR 0.117028
G S2 APARTMENT DIRECT AIR 0.121537
F2 SW APARTMENT DIRECT AIR 0.289872
F2 NW APARTMENT DIRECT AIR 0.285756
F2 SE APARTMENT DIRECT AIR 0.248656
F2 NE APARTMENT DIRECT AIR 0.221876
F2 N1 APARTMENT DIRECT AIR 0.142689
F2 N2 APARTMENT DIRECT AIR 0.141383
F2 S1 APARTMENT DIRECT AIR 0.146980
F2 S2 APARTMENT DIRECT AIR 0.148613
F3 SW APARTMENT DIRECT AIR 0.289222
F3 NW APARTMENT DIRECT AIR 0.285462
F3 SE APARTMENT DIRECT AIR 0.233294
F3 NE APARTMENT DIRECT AIR 0.221311
F3 N1 APARTMENT DIRECT AIR 0.144857
F3 N2 APARTMENT DIRECT AIR 0.143557
F3 S1 APARTMENT DIRECT AIR 0.149356
F3 S2 APARTMENT DIRECT AIR 0.150094
F4 SW APARTMENT DIRECT AIR 0.289539
F4 NW APARTMENT DIRECT AIR 0.285753
F4 SE APARTMENT DIRECT AIR 0.231372
F4 NE APARTMENT DIRECT AIR 0.220589
F4 N1 APARTMENT DIRECT AIR 0.146298
F4 N2 APARTMENT DIRECT AIR 0.145002
F4 S1 APARTMENT DIRECT AIR 0.150814
F4 S2 APARTMENT DIRECT AIR 0.151406
M SW APARTMENT DIRECT AIR 0.292104
M NW APARTMENT DIRECT AIR 0.288366
M SE APARTMENT DIRECT AIR 0.233096
M NE APARTMENT DIRECT AIR 0.222325
M N1 APARTMENT DIRECT AIR 0.149641
M N2 APARTMENT DIRECT AIR 0.148346
M S1 APARTMENT DIRECT AIR 0.154108
M S2 APARTMENT DIRECT AIR 0.154665
F6 SW APARTMENT DIRECT AIR 0.288710
F6 NW APARTMENT DIRECT AIR 0.284846
F6 SE APARTMENT DIRECT AIR 0.229224
F6 NE APARTMENT DIRECT AIR 0.218223
F6 N1 APARTMENT DIRECT AIR 0.146989
F6 N2 APARTMENT DIRECT AIR 0.145704
F6 S1 APARTMENT DIRECT AIR 0.151531
F6 S2 APARTMENT DIRECT AIR 0.152071
F7 SW APARTMENT DIRECT AIR 0.287552
F7 NW APARTMENT DIRECT AIR 0.283674
F7 SE APARTMENT DIRECT AIR 0.227640
F7 NE APARTMENT DIRECT AIR 0.216512
F7 N1 APARTMENT DIRECT AIR 0.146461
F7 N2 APARTMENT DIRECT AIR 0.145181
F7 S1 APARTMENT DIRECT AIR 0.150994
F7 S2 APARTMENT DIRECT AIR 0.151522
F8 SW APARTMENT DIRECT AIR 0.287644
F8 NW APARTMENT DIRECT AIR 0.283746
F8 SE APARTMENT DIRECT AIR 0.227331
F8 NE APARTMENT DIRECT AIR 0.216047
F8 N1 APARTMENT DIRECT AIR 0.147070
F8 N2 APARTMENT DIRECT AIR 0.145797
F8 S1 APARTMENT DIRECT AIR 0.151574
F8 S2 APARTMENT DIRECT AIR 0.152093
F9 SW APARTMENT DIRECT AIR 0.294683
F9 NW APARTMENT DIRECT AIR 0.290566
F9 SE APARTMENT DIRECT AIR 0.230612
F9 NE APARTMENT DIRECT AIR 0.218679
F9 N1 APARTMENT DIRECT AIR 0.153258
F9 N2 APARTMENT DIRECT AIR 0.151977
F9 S1 APARTMENT DIRECT AIR 0.156314
F9 S2 APARTMENT DIRECT AIR 0.156898
T SW APARTMENT DIRECT AIR 0.334911
T NW APARTMENT DIRECT AIR 0.329877
T SE APARTMENT DIRECT AIR 0.267991
T NE APARTMENT DIRECT AIR 0.251917
T N1 APARTMENT DIRECT AIR 0.177914
T N2 APARTMENT DIRECT AIR 0.175350
T S1 APARTMENT DIRECT AIR 0.200417
T S2 APARTMENT DIRECT AIR 0.200884


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.242824
AIRLOOP G NW MAIN BRANCH 0.241158
AIRLOOP OFFICE MAIN BRANCH 0.293404
AIRLOOP G NE MAIN BRANCH 0.186589
AIRLOOP G N1 MAIN BRANCH 0.113686
AIRLOOP G N2 MAIN BRANCH 0.112075
AIRLOOP G S1 MAIN BRANCH 0.117028
AIRLOOP G S2 MAIN BRANCH 0.121537
AIRLOOP F2 SW MAIN BRANCH 0.289872
AIRLOOP F2 NW MAIN BRANCH 0.285756
AIRLOOP F2 SE MAIN BRANCH 0.248656
AIRLOOP F2 NE MAIN BRANCH 0.221876
AIRLOOP F2 N1 MAIN BRANCH 0.142689
AIRLOOP F2 N2 MAIN BRANCH 0.141383
AIRLOOP F2 S1 MAIN BRANCH 0.146980
AIRLOOP F2 S2 MAIN BRANCH 0.148613
AIRLOOP F3 SW MAIN BRANCH 0.289222
AIRLOOP F3 NW MAIN BRANCH 0.285462
AIRLOOP F3 SE MAIN BRANCH 0.233294
AIRLOOP F3 NE MAIN BRANCH 0.221311
AIRLOOP F3 N1 MAIN BRANCH 0.144857
AIRLOOP F3 N2 MAIN BRANCH 0.143557
AIRLOOP F3 S1 MAIN BRANCH 0.149356
AIRLOOP F3 S2 MAIN BRANCH 0.150094
AIRLOOP F4 SW MAIN BRANCH 0.289539
AIRLOOP F4 NW MAIN BRANCH 0.285753
AIRLOOP F4 SE MAIN BRANCH 0.231372
AIRLOOP F4 NE MAIN BRANCH 0.220589
AIRLOOP F4 N1 MAIN BRANCH 0.146298
AIRLOOP F4 N2 MAIN BRANCH 0.145002
AIRLOOP F4 S1 MAIN BRANCH 0.150814
AIRLOOP F4 S2 MAIN BRANCH 0.151406
AIRLOOP M SW MAIN BRANCH 0.292104
AIRLOOP M NW MAIN BRANCH 0.288366
AIRLOOP M SE MAIN BRANCH 0.233096
AIRLOOP M NE MAIN BRANCH 0.222325
AIRLOOP M N1 MAIN BRANCH 0.149641
AIRLOOP M N2 MAIN BRANCH 0.148346
AIRLOOP M S1 MAIN BRANCH 0.154108
AIRLOOP M S2 MAIN BRANCH 0.154665
AIRLOOP F6 SW MAIN BRANCH 0.288710
AIRLOOP F6 NW MAIN BRANCH 0.284846
AIRLOOP F6 SE MAIN BRANCH 0.229224
AIRLOOP F6 NE MAIN BRANCH 0.218223
AIRLOOP F6 N1 MAIN BRANCH 0.146989
AIRLOOP F6 N2 MAIN BRANCH 0.145704
AIRLOOP F6 S1 MAIN BRANCH 0.151531
AIRLOOP F6 S2 MAIN BRANCH 0.152071
AIRLOOP F7 SW MAIN BRANCH 0.287552
AIRLOOP F7 NW MAIN BRANCH 0.283674
AIRLOOP F7 SE MAIN BRANCH 0.227640
AIRLOOP F7 NE MAIN BRANCH 0.216512
AIRLOOP F7 N1 MAIN BRANCH 0.146461
AIRLOOP F7 N2 MAIN BRANCH 0.145181
AIRLOOP F7 S1 MAIN BRANCH 0.150994
AIRLOOP F7 S2 MAIN BRANCH 0.151522
AIRLOOP F8 SW MAIN BRANCH 0.287644
AIRLOOP F8 NW MAIN BRANCH 0.283746
AIRLOOP F8 SE MAIN BRANCH 0.227331
AIRLOOP F8 NE MAIN BRANCH 0.216047
AIRLOOP F8 N1 MAIN BRANCH 0.147070
AIRLOOP F8 N2 MAIN BRANCH 0.145797
AIRLOOP F8 S1 MAIN BRANCH 0.151574
AIRLOOP F8 S2 MAIN BRANCH 0.152093
AIRLOOP F9 SW MAIN BRANCH 0.294683
AIRLOOP F9 NW MAIN BRANCH 0.290566
AIRLOOP F9 SE MAIN BRANCH 0.230612
AIRLOOP F9 NE MAIN BRANCH 0.218679
AIRLOOP F9 N1 MAIN BRANCH 0.153258
AIRLOOP F9 N2 MAIN BRANCH 0.151977
AIRLOOP F9 S1 MAIN BRANCH 0.156314
AIRLOOP F9 S2 MAIN BRANCH 0.156898
AIRLOOP T SW MAIN BRANCH 0.334911
AIRLOOP T NW MAIN BRANCH 0.329877
AIRLOOP T SE MAIN BRANCH 0.267991
AIRLOOP T NE MAIN BRANCH 0.251917
AIRLOOP T N1 MAIN BRANCH 0.177914
AIRLOOP T N2 MAIN BRANCH 0.175350
AIRLOOP T S1 MAIN BRANCH 0.200417
AIRLOOP T S2 MAIN BRANCH 0.200884


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.242824
AIRLOOP G NW 0.241158
AIRLOOP OFFICE 0.293404
AIRLOOP G NE 0.186589
AIRLOOP G N1 0.113686
AIRLOOP G N2 0.112075
AIRLOOP G S1 0.117028
AIRLOOP G S2 0.121537
AIRLOOP F2 SW 0.289872
AIRLOOP F2 NW 0.285756
AIRLOOP F2 SE 0.248656
AIRLOOP F2 NE 0.221876
AIRLOOP F2 N1 0.142689
AIRLOOP F2 N2 0.141383
AIRLOOP F2 S1 0.146980
AIRLOOP F2 S2 0.148613
AIRLOOP F3 SW 0.289222
AIRLOOP F3 NW 0.285462
AIRLOOP F3 SE 0.233294
AIRLOOP F3 NE 0.221311
AIRLOOP F3 N1 0.144857
AIRLOOP F3 N2 0.143557
AIRLOOP F3 S1 0.149356
AIRLOOP F3 S2 0.150094
AIRLOOP F4 SW 0.289539
AIRLOOP F4 NW 0.285753
AIRLOOP F4 SE 0.231372
AIRLOOP F4 NE 0.220589
AIRLOOP F4 N1 0.146298
AIRLOOP F4 N2 0.145002
AIRLOOP F4 S1 0.150814
AIRLOOP F4 S2 0.151406
AIRLOOP M SW 0.292104
AIRLOOP M NW 0.288366
AIRLOOP M SE 0.233096
AIRLOOP M NE 0.222325
AIRLOOP M N1 0.149641
AIRLOOP M N2 0.148346
AIRLOOP M S1 0.154108
AIRLOOP M S2 0.154665
AIRLOOP F6 SW 0.288710
AIRLOOP F6 NW 0.284846
AIRLOOP F6 SE 0.229224
AIRLOOP F6 NE 0.218223
AIRLOOP F6 N1 0.146989
AIRLOOP F6 N2 0.145704
AIRLOOP F6 S1 0.151531
AIRLOOP F6 S2 0.152071
AIRLOOP F7 SW 0.287552
AIRLOOP F7 NW 0.283674
AIRLOOP F7 SE 0.227640
AIRLOOP F7 NE 0.216512
AIRLOOP F7 N1 0.146461
AIRLOOP F7 N2 0.145181
AIRLOOP F7 S1 0.150994
AIRLOOP F7 S2 0.151522
AIRLOOP F8 SW 0.287644
AIRLOOP F8 NW 0.283746
AIRLOOP F8 SE 0.227331
AIRLOOP F8 NE 0.216047
AIRLOOP F8 N1 0.147070
AIRLOOP F8 N2 0.145797
AIRLOOP F8 S1 0.151574
AIRLOOP F8 S2 0.152093
AIRLOOP F9 SW 0.294683
AIRLOOP F9 NW 0.290566
AIRLOOP F9 SE 0.230612
AIRLOOP F9 NE 0.218679
AIRLOOP F9 N1 0.153258
AIRLOOP F9 N2 0.151977
AIRLOOP F9 S1 0.156314
AIRLOOP F9 S2 0.156898
AIRLOOP T SW 0.334911
AIRLOOP T NW 0.329877
AIRLOOP T SE 0.267991
AIRLOOP T NE 0.251917
AIRLOOP T N1 0.177914
AIRLOOP T N2 0.175350
AIRLOOP T S1 0.200417
AIRLOOP T S2 0.200884


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.242824 0.025952
AIRLOOP G NW OA CONTROLLER 0.241158 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.293404 0.038103
AIRLOOP G NE OA CONTROLLER 0.186589 0.025952
AIRLOOP G N1 OA CONTROLLER 0.113686 0.025952
AIRLOOP G N2 OA CONTROLLER 0.112075 0.025952
AIRLOOP G S1 OA CONTROLLER 0.117028 0.025952
AIRLOOP G S2 OA CONTROLLER 0.121537 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.289872 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.285756 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.248656 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.221876 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.142689 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.141383 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.146980 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.148613 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.289222 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.285462 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.233294 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.221311 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.144857 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.143557 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.149356 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.150094 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.289539 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.285753 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.231372 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.220589 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.146298 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.145002 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.150814 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.151406 0.025952
AIRLOOP M SW OA CONTROLLER 0.292104 0.025952
AIRLOOP M NW OA CONTROLLER 0.288366 0.025952
AIRLOOP M SE OA CONTROLLER 0.233096 0.025952
AIRLOOP M NE OA CONTROLLER 0.222325 0.025952
AIRLOOP M N1 OA CONTROLLER 0.149641 0.025952
AIRLOOP M N2 OA CONTROLLER 0.148346 0.025952
AIRLOOP M S1 OA CONTROLLER 0.154108 0.025952
AIRLOOP M S2 OA CONTROLLER 0.154665 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.288710 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.284846 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.229224 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.218223 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.146989 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.145704 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.151531 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.152071 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.287552 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.283674 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.227640 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.216512 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.146461 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.145181 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.150994 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.151522 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.287644 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.283746 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.227331 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.216047 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.147070 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.145797 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.151574 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.152093 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.294683 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.290566 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.230612 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.218679 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.153258 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.151977 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.156314 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.156898 0.025952
AIRLOOP T SW OA CONTROLLER 0.334911 0.025952
AIRLOOP T NW OA CONTROLLER 0.329877 0.025952
AIRLOOP T SE OA CONTROLLER 0.267991 0.025952
AIRLOOP T NE OA CONTROLLER 0.251917 0.025952
AIRLOOP T N1 OA CONTROLLER 0.177914 0.025952
AIRLOOP T N2 OA CONTROLLER 0.175350 0.025952
AIRLOOP T S1 OA CONTROLLER 0.200417 0.025952
AIRLOOP T S2 OA CONTROLLER 0.200884 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.242824 4306.67 2968.21 0.000094
HEAT PUMP COOLING MODE AIRLOOP G NW 0.241158 4282.46 2948.86 0.000094
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.293404 5280.69 3616.64 0.000115
HEAT PUMP COOLING MODE AIRLOOP G NE 0.186589 3471.04 2335.55 0.000076
HEAT PUMP COOLING MODE AIRLOOP G N1 0.113686 2357.79 1513.88 0.000052
HEAT PUMP COOLING MODE AIRLOOP G N2 0.112075 2333.57 1495.95 0.000051
HEAT PUMP COOLING MODE AIRLOOP G S1 0.117028 2446.75 1571.03 0.000053
HEAT PUMP COOLING MODE AIRLOOP G S2 0.121537 2513.57 1621.17 0.000055
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.289872 5064.20 3513.14 0.000111
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.285756 5004.91 3466.73 0.000109
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.248656 4461.34 3054.29 0.000097
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.221876 4058.18 2749.92 0.000089
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.142689 2827.09 1849.01 0.000062
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.141383 2807.62 1834.48 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.146980 2928.11 1917.26 0.000064
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.148613 2951.76 1935.27 0.000064
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.289222 5105.10 3521.58 0.000112
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.285462 5050.72 3479.07 0.000110
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.233294 4287.81 2900.08 0.000094
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.221311 4102.06 2761.79 0.000090
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.144857 2884.62 1881.84 0.000063
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.143557 2865.15 1867.36 0.000063
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.149356 2988.64 1952.33 0.000065
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.150094 2999.25 1960.42 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.289539 5146.84 3536.72 0.000112
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.285753 5091.99 3493.94 0.000111
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.231372 4294.87 2890.20 0.000094
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.220589 4125.86 2765.06 0.000090
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.146298 2924.92 1904.40 0.000064
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.145002 2905.43 1889.94 0.000063
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.150814 3029.25 1975.05 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.151406 3037.74 1981.53 0.000066
HEAT PUMP COOLING MODE AIRLOOP M SW 0.292104 5213.92 3574.54 0.000114
HEAT PUMP COOLING MODE AIRLOOP M NW 0.288366 5159.64 3532.27 0.000113
HEAT PUMP COOLING MODE AIRLOOP M SE 0.233096 4348.09 2918.47 0.000095
HEAT PUMP COOLING MODE AIRLOOP M NE 0.222325 4178.83 2793.39 0.000091
HEAT PUMP COOLING MODE AIRLOOP M N1 0.149641 2989.84 1946.79 0.000065
HEAT PUMP COOLING MODE AIRLOOP M N2 0.148346 2970.35 1932.35 0.000065
HEAT PUMP COOLING MODE AIRLOOP M S1 0.154108 3093.37 2016.93 0.000068
HEAT PUMP COOLING MODE AIRLOOP M S2 0.154665 3101.36 2023.03 0.000068
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.288710 5190.44 3545.14 0.000113
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.284846 5134.26 3501.49 0.000112
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.229224 4315.31 2883.47 0.000094
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.218223 4142.04 2755.75 0.000090
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.146989 2963.54 1922.00 0.000065
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.145704 2944.07 1907.64 0.000064
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.151531 3068.51 1992.88 0.000067
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.152071 3076.29 1998.81 0.000067
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.287552 5195.90 3539.43 0.000114
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.283674 5139.42 3495.62 0.000112
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.227640 4312.70 2872.77 0.000094
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.216512 4137.04 2743.57 0.000090
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.146461 2966.97 1920.13 0.000065
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.145181 2947.53 1905.82 0.000064
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.150994 3072.02 1990.91 0.000067
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.151522 3079.64 1996.69 0.000067
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.287644 5217.05 3546.79 0.000114
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.283746 5160.18 3502.75 0.000113
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.227331 4329.37 2877.19 0.000095
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.216047 4148.07 2744.45 0.000091
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.147070 2986.15 1930.47 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.145797 2966.77 1916.22 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.151574 3090.87 2000.92 0.000068
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.152093 3098.35 2006.60 0.000068
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.294683 5337.38 3630.47 0.000117
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.290566 5277.37 3584.01 0.000115
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.230612 4394.51 2919.21 0.000096
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.218679 4203.44 2779.23 0.000092
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.153258 3088.11 2002.50 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.151977 3068.64 1988.17 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.156314 3170.07 2056.64 0.000069
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.156898 3179.52 2063.40 0.000069
HEAT PUMP COOLING MODE AIRLOOP T SW 0.334911 5937.57 4081.72 0.000130
HEAT PUMP COOLING MODE AIRLOOP T NW 0.329877 5863.78 4024.88 0.000128
HEAT PUMP COOLING MODE AIRLOOP T SE 0.267991 4962.75 3340.77 0.000108
HEAT PUMP COOLING MODE AIRLOOP T NE 0.251917 4715.42 3156.36 0.000103
HEAT PUMP COOLING MODE AIRLOOP T N1 0.177914 3466.69 2282.32 0.000076
HEAT PUMP COOLING MODE AIRLOOP T N2 0.175350 3428.46 2253.76 0.000075
HEAT PUMP COOLING MODE AIRLOOP T S1 0.200417 3829.51 2549.24 0.000084
HEAT PUMP COOLING MODE AIRLOOP T S2 0.200884 3835.97 2554.29 0.000084


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.242824 0.242824 0.242824 0.242824 4306.67 4306.67 747.30 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.241158 0.241158 0.241158 0.241158 4282.46 4282.46 747.30 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.293404 0.293404 0.293404 0.293404 5280.69 5280.69 1097.19 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.186589 0.186589 0.186589 0.186589 3471.04 3471.04 747.30 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.113686 0.113686 0.113686 0.113686 2357.79 2357.79 747.30 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.112075 0.112075 0.112075 0.112075 2333.57 2333.57 747.30 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.117028 0.117028 0.117028 0.117028 2446.75 2446.75 747.30 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.121537 0.121537 0.121537 0.121537 2513.57 2513.57 747.30 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.289872 0.289872 0.289872 0.289872 5064.20 5064.20 747.30 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.285756 0.285756 0.285756 0.285756 5004.91 5004.91 747.30 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.248656 0.248656 0.248656 0.248656 4461.34 4461.34 747.30 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.221876 0.221876 0.221876 0.221876 4058.18 4058.18 747.30 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.142689 0.142689 0.142689 0.142689 2827.09 2827.09 747.30 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.141383 0.141383 0.141383 0.141383 2807.62 2807.62 747.30 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.146980 0.146980 0.146980 0.146980 2928.11 2928.11 747.30 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.148613 0.148613 0.148613 0.148613 2951.76 2951.76 747.30 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.289222 0.289222 0.289222 0.289222 5105.10 5105.10 747.30 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.285462 0.285462 0.285462 0.285462 5050.72 5050.72 747.30 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.233294 0.233294 0.233294 0.233294 4287.81 4287.81 747.30 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.221311 0.221311 0.221311 0.221311 4102.06 4102.06 747.30 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.144857 0.144857 0.144857 0.144857 2884.62 2884.62 747.30 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.143557 0.143557 0.143557 0.143557 2865.15 2865.15 747.30 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.149356 0.149356 0.149356 0.149356 2988.64 2988.64 747.30 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.150094 0.150094 0.150094 0.150094 2999.25 2999.25 747.30 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.289539 0.289539 0.289539 0.289539 5146.84 5146.84 747.30 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.285753 0.285753 0.285753 0.285753 5091.99 5091.99 747.30 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.231372 0.231372 0.231372 0.231372 4294.87 4294.87 747.30 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.220589 0.220589 0.220589 0.220589 4125.86 4125.86 747.30 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.146298 0.146298 0.146298 0.146298 2924.92 2924.92 747.30 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.145002 0.145002 0.145002 0.145002 2905.43 2905.43 747.30 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.150814 0.150814 0.150814 0.150814 3029.25 3029.25 747.30 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.151406 0.151406 0.151406 0.151406 3037.74 3037.74 747.30 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.292104 0.292104 0.292104 0.292104 5213.92 5213.92 747.30 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.288366 0.288366 0.288366 0.288366 5159.64 5159.64 747.30 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.233096 0.233096 0.233096 0.233096 4348.09 4348.09 747.30 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.222325 0.222325 0.222325 0.222325 4178.83 4178.83 747.30 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.149641 0.149641 0.149641 0.149641 2989.84 2989.84 747.30 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.148346 0.148346 0.148346 0.148346 2970.35 2970.35 747.30 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.154108 0.154108 0.154108 0.154108 3093.37 3093.37 747.30 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.154665 0.154665 0.154665 0.154665 3101.36 3101.36 747.30 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.288710 0.288710 0.288710 0.288710 5190.44 5190.44 747.30 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.284846 0.284846 0.284846 0.284846 5134.26 5134.26 747.30 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.229224 0.229224 0.229224 0.229224 4315.31 4315.31 747.30 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.218223 0.218223 0.218223 0.218223 4142.04 4142.04 747.30 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.146989 0.146989 0.146989 0.146989 2963.54 2963.54 747.30 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.145704 0.145704 0.145704 0.145704 2944.07 2944.07 747.30 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.151531 0.151531 0.151531 0.151531 3068.51 3068.51 747.30 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.152071 0.152071 0.152071 0.152071 3076.29 3076.29 747.30 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.287552 0.287552 0.287552 0.287552 5195.90 5195.90 747.30 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.283674 0.283674 0.283674 0.283674 5139.42 5139.42 747.30 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.227640 0.227640 0.227640 0.227640 4312.70 4312.70 747.30 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.216512 0.216512 0.216512 0.216512 4137.04 4137.04 747.30 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.146461 0.146461 0.146461 0.146461 2966.97 2966.97 747.30 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.145181 0.145181 0.145181 0.145181 2947.53 2947.53 747.30 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.150994 0.150994 0.150994 0.150994 3072.02 3072.02 747.30 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.151522 0.151522 0.151522 0.151522 3079.64 3079.64 747.30 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.287644 0.287644 0.287644 0.287644 5217.05 5217.05 747.30 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.283746 0.283746 0.283746 0.283746 5160.18 5160.18 747.30 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.227331 0.227331 0.227331 0.227331 4329.37 4329.37 747.30 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.216047 0.216047 0.216047 0.216047 4148.07 4148.07 747.30 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.147070 0.147070 0.147070 0.147070 2986.15 2986.15 747.30 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.145797 0.145797 0.145797 0.145797 2966.77 2966.77 747.30 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.151574 0.151574 0.151574 0.151574 3090.87 3090.87 747.30 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.152093 0.152093 0.152093 0.152093 3098.35 3098.35 747.30 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.294683 0.294683 0.294683 0.294683 5337.38 5337.38 747.30 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.290566 0.290566 0.290566 0.290566 5277.37 5277.37 747.30 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.230612 0.230612 0.230612 0.230612 4394.51 4394.51 747.30 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.218679 0.218679 0.218679 0.218679 4203.44 4203.44 747.30 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.153258 0.153258 0.153258 0.153258 3088.11 3088.11 747.30 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.151977 0.151977 0.151977 0.151977 3068.64 3068.64 747.30 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.156314 0.156314 0.156314 0.156314 3170.07 3170.07 747.30 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.156898 0.156898 0.156898 0.156898 3179.52 3179.52 747.30 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.334911 0.334911 0.334911 0.334911 5937.57 5937.57 747.30 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.329877 0.329877 0.329877 0.329877 5863.78 5863.78 747.30 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.267991 0.267991 0.267991 0.267991 4962.75 4962.75 747.30 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.251917 0.251917 0.251917 0.251917 4715.42 4715.42 747.30 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.177914 0.177914 0.177914 0.177914 3466.69 3466.69 747.30 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.175350 0.175350 0.175350 0.175350 3428.46 3428.46 747.30 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.200417 0.200417 0.200417 0.200417 3829.51 3829.51 747.30 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.200884 0.200884 0.200884 0.200884 3835.97 3835.97 747.30 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.242824
AIRLOOP G NW SUPPLY FAN 0.241158
AIRLOOP OFFICE SUPPLY FAN 0.293404
AIRLOOP G NE SUPPLY FAN 0.186589
AIRLOOP G N1 SUPPLY FAN 0.113686
AIRLOOP G N2 SUPPLY FAN 0.112075
AIRLOOP G S1 SUPPLY FAN 0.117028
AIRLOOP G S2 SUPPLY FAN 0.121537
AIRLOOP F2 SW SUPPLY FAN 0.289872
AIRLOOP F2 NW SUPPLY FAN 0.285756
AIRLOOP F2 SE SUPPLY FAN 0.248656
AIRLOOP F2 NE SUPPLY FAN 0.221876
AIRLOOP F2 N1 SUPPLY FAN 0.142689
AIRLOOP F2 N2 SUPPLY FAN 0.141383
AIRLOOP F2 S1 SUPPLY FAN 0.146980
AIRLOOP F2 S2 SUPPLY FAN 0.148613
AIRLOOP F3 SW SUPPLY FAN 0.289222
AIRLOOP F3 NW SUPPLY FAN 0.285462
AIRLOOP F3 SE SUPPLY FAN 0.233294
AIRLOOP F3 NE SUPPLY FAN 0.221311
AIRLOOP F3 N1 SUPPLY FAN 0.144857
AIRLOOP F3 N2 SUPPLY FAN 0.143557
AIRLOOP F3 S1 SUPPLY FAN 0.149356
AIRLOOP F3 S2 SUPPLY FAN 0.150094
AIRLOOP F4 SW SUPPLY FAN 0.289539
AIRLOOP F4 NW SUPPLY FAN 0.285753
AIRLOOP F4 SE SUPPLY FAN 0.231372
AIRLOOP F4 NE SUPPLY FAN 0.220589
AIRLOOP F4 N1 SUPPLY FAN 0.146298
AIRLOOP F4 N2 SUPPLY FAN 0.145002
AIRLOOP F4 S1 SUPPLY FAN 0.150814
AIRLOOP F4 S2 SUPPLY FAN 0.151406
AIRLOOP M SW SUPPLY FAN 0.292104
AIRLOOP M NW SUPPLY FAN 0.288366
AIRLOOP M SE SUPPLY FAN 0.233096
AIRLOOP M NE SUPPLY FAN 0.222325
AIRLOOP M N1 SUPPLY FAN 0.149641
AIRLOOP M N2 SUPPLY FAN 0.148346
AIRLOOP M S1 SUPPLY FAN 0.154108
AIRLOOP M S2 SUPPLY FAN 0.154665
AIRLOOP F6 SW SUPPLY FAN 0.288710
AIRLOOP F6 NW SUPPLY FAN 0.284846
AIRLOOP F6 SE SUPPLY FAN 0.229224
AIRLOOP F6 NE SUPPLY FAN 0.218223
AIRLOOP F6 N1 SUPPLY FAN 0.146989
AIRLOOP F6 N2 SUPPLY FAN 0.145704
AIRLOOP F6 S1 SUPPLY FAN 0.151531
AIRLOOP F6 S2 SUPPLY FAN 0.152071
AIRLOOP F7 SW SUPPLY FAN 0.287552
AIRLOOP F7 NW SUPPLY FAN 0.283674
AIRLOOP F7 SE SUPPLY FAN 0.227640
AIRLOOP F7 NE SUPPLY FAN 0.216512
AIRLOOP F7 N1 SUPPLY FAN 0.146461
AIRLOOP F7 N2 SUPPLY FAN 0.145181
AIRLOOP F7 S1 SUPPLY FAN 0.150994
AIRLOOP F7 S2 SUPPLY FAN 0.151522
AIRLOOP F8 SW SUPPLY FAN 0.287644
AIRLOOP F8 NW SUPPLY FAN 0.283746
AIRLOOP F8 SE SUPPLY FAN 0.227331
AIRLOOP F8 NE SUPPLY FAN 0.216047
AIRLOOP F8 N1 SUPPLY FAN 0.147070
AIRLOOP F8 N2 SUPPLY FAN 0.145797
AIRLOOP F8 S1 SUPPLY FAN 0.151574
AIRLOOP F8 S2 SUPPLY FAN 0.152093
AIRLOOP F9 SW SUPPLY FAN 0.294683
AIRLOOP F9 NW SUPPLY FAN 0.290566
AIRLOOP F9 SE SUPPLY FAN 0.230612
AIRLOOP F9 NE SUPPLY FAN 0.218679
AIRLOOP F9 N1 SUPPLY FAN 0.153258
AIRLOOP F9 N2 SUPPLY FAN 0.151977
AIRLOOP F9 S1 SUPPLY FAN 0.156314
AIRLOOP F9 S2 SUPPLY FAN 0.156898
AIRLOOP T SW SUPPLY FAN 0.334911
AIRLOOP T NW SUPPLY FAN 0.329877
AIRLOOP T SE SUPPLY FAN 0.267991
AIRLOOP T NE SUPPLY FAN 0.251917
AIRLOOP T N1 SUPPLY FAN 0.177914
AIRLOOP T N2 SUPPLY FAN 0.175350
AIRLOOP T S1 SUPPLY FAN 0.200417
AIRLOOP T S2 SUPPLY FAN 0.200884


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.242824 4306.67 0.000094
HEAT PUMP HEATING MODE AIRLOOP G NW 0.241158 4282.46 0.000094
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.293404 5280.69 0.000115
HEAT PUMP HEATING MODE AIRLOOP G NE 0.186589 3471.04 0.000076
HEAT PUMP HEATING MODE AIRLOOP G N1 0.113686 2357.79 0.000052
HEAT PUMP HEATING MODE AIRLOOP G N2 0.112075 2333.57 0.000051
HEAT PUMP HEATING MODE AIRLOOP G S1 0.117028 2446.75 0.000053
HEAT PUMP HEATING MODE AIRLOOP G S2 0.121537 2513.57 0.000055
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.289872 5064.20 0.000111
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.285756 5004.91 0.000109
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.248656 4461.34 0.000097
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.221876 4058.18 0.000089
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.142689 2827.09 0.000062
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.141383 2807.62 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.146980 2928.11 0.000064
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.148613 2951.76 0.000064
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.289222 5105.10 0.000112
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.285462 5050.72 0.000110
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.233294 4287.81 0.000094
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.221311 4102.06 0.000090
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.144857 2884.62 0.000063
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.143557 2865.15 0.000063
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.149356 2988.64 0.000065
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.150094 2999.25 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.289539 5146.84 0.000112
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.285753 5091.99 0.000111
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.231372 4294.87 0.000094
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.220589 4125.86 0.000090
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.146298 2924.92 0.000064
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.145002 2905.43 0.000063
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.150814 3029.25 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.151406 3037.74 0.000066
HEAT PUMP HEATING MODE AIRLOOP M SW 0.292104 5213.92 0.000114
HEAT PUMP HEATING MODE AIRLOOP M NW 0.288366 5159.64 0.000113
HEAT PUMP HEATING MODE AIRLOOP M SE 0.233096 4348.09 0.000095
HEAT PUMP HEATING MODE AIRLOOP M NE 0.222325 4178.83 0.000091
HEAT PUMP HEATING MODE AIRLOOP M N1 0.149641 2989.84 0.000065
HEAT PUMP HEATING MODE AIRLOOP M N2 0.148346 2970.35 0.000065
HEAT PUMP HEATING MODE AIRLOOP M S1 0.154108 3093.37 0.000068
HEAT PUMP HEATING MODE AIRLOOP M S2 0.154665 3101.36 0.000068
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.288710 5190.44 0.000113
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.284846 5134.26 0.000112
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.229224 4315.31 0.000094
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.218223 4142.04 0.000090
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.146989 2963.54 0.000065
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.145704 2944.07 0.000064
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.151531 3068.51 0.000067
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.152071 3076.29 0.000067
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.287552 5195.90 0.000114
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.283674 5139.42 0.000112
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.227640 4312.70 0.000094
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.216512 4137.04 0.000090
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.146461 2966.97 0.000065
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.145181 2947.53 0.000064
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.150994 3072.02 0.000067
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.151522 3079.64 0.000067
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.287644 5217.05 0.000114
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.283746 5160.18 0.000113
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.227331 4329.37 0.000095
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.216047 4148.07 0.000091
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.147070 2986.15 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.145797 2966.77 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.151574 3090.87 0.000068
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.152093 3098.35 0.000068
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.294683 5337.38 0.000117
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.290566 5277.37 0.000115
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.230612 4394.51 0.000096
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.218679 4203.44 0.000092
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.153258 3088.11 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.151977 3068.64 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.156314 3170.07 0.000069
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.156898 3179.52 0.000069
HEAT PUMP HEATING MODE AIRLOOP T SW 0.334911 5937.57 0.000130
HEAT PUMP HEATING MODE AIRLOOP T NW 0.329877 5863.78 0.000128
HEAT PUMP HEATING MODE AIRLOOP T SE 0.267991 4962.75 0.000108
HEAT PUMP HEATING MODE AIRLOOP T NE 0.251917 4715.42 0.000103
HEAT PUMP HEATING MODE AIRLOOP T N1 0.177914 3466.69 0.000076
HEAT PUMP HEATING MODE AIRLOOP T N2 0.175350 3428.46 0.000075
HEAT PUMP HEATING MODE AIRLOOP T S1 0.200417 3829.51 0.000084
HEAT PUMP HEATING MODE AIRLOOP T S2 0.200884 3835.97 0.000084


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 1097.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 747.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 747.30


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.006759 7.60


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.006759


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.006759 3263.07 8.59 10124.55


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.006759 1724.00



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:04

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.32 22.49
February 24.31 22.80
March 24.30 23.17
April 24.37 23.76
May 24.39 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.38 24.76
December 24.38 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.30 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.26 22.49
February 24.27 22.80
March 24.28 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.39 26.22
November 24.37 24.76
December 24.36 23.69
     
Annual Sum or Average 24.36 24.91
Minimum of Months 24.26 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.35 22.80
March 24.35 23.17
April 24.40 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.26 22.49
February 24.25 22.80
March 24.27 23.17
April 24.37 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.42 27.06
September 24.40 26.87
October 24.39 26.22
November 24.37 24.76
December 24.36 23.69
     
Annual Sum or Average 24.36 24.91
Minimum of Months 24.25 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 22.49
February 24.22 22.80
March 24.24 23.17
April 24.34 23.76
May 24.39 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.41 26.87
October 24.39 26.22
November 24.36 24.76
December 24.33 23.69
     
Annual Sum or Average 24.34 24.91
Minimum of Months 24.20 22.49
Maximum of Months 24.41 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 22.49
February 24.22 22.80
March 24.24 23.17
April 24.34 23.76
May 24.39 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.41 26.87
October 24.39 26.22
November 24.36 24.76
December 24.33 23.69
     
Annual Sum or Average 24.34 24.91
Minimum of Months 24.20 22.49
Maximum of Months 24.41 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.34 22.80
March 24.28 23.17
April 24.35 23.76
May 24.39 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.51 26.87
October 24.49 26.22
November 24.48 24.76
December 24.50 23.69
     
Annual Sum or Average 24.41 24.91
Minimum of Months 24.28 22.49
Maximum of Months 24.51 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.34 22.80
March 24.28 23.17
April 24.35 23.76
May 24.39 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.49 26.87
October 24.48 26.22
November 24.47 24.76
December 24.49 23.69
     
Annual Sum or Average 24.41 24.91
Minimum of Months 24.28 22.49
Maximum of Months 24.49 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.33 22.49
February 24.50 22.80
March 24.68 23.17
April 24.86 23.76
May 25.51 25.23
June 26.19 25.87
July 26.66 26.90
August 26.74 27.06
September 26.64 26.87
October 25.98 26.22
November 25.29 24.76
December 24.84 23.69
     
Annual Sum or Average 25.52 24.91
Minimum of Months 24.33 22.49
Maximum of Months 26.74 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.36 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.42 22.49
February 24.39 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.48 26.22
November 24.45 24.76
December 24.47 23.69
     
Annual Sum or Average 24.42 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.48 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 22.49
February 24.36 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.36 22.80
March 24.36 23.17
April 24.39 23.76
May 24.40 25.23
June 24.41 25.87
July 24.42 26.90
August 24.40 27.06
September 24.41 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.42 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.36 22.80
March 24.36 23.17
April 24.39 23.76
May 24.40 25.23
June 24.41 25.87
July 24.42 26.90
August 24.40 27.06
September 24.41 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.42 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.52 22.49
February 24.50 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.50 26.87
October 24.61 26.22
November 24.63 24.76
December 24.63 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.63 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.52 22.49
February 24.50 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.49 26.87
October 24.61 26.22
November 24.62 24.76
December 24.63 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.63 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.08 22.49
February 26.12 22.80
March 26.14 23.17
April 26.19 23.76
May 26.42 25.23
June 26.62 25.87
July 26.76 26.90
August 26.76 27.06
September 26.79 26.87
October 26.63 26.22
November 26.41 24.76
December 26.26 23.69
     
Annual Sum or Average 26.43 24.91
Minimum of Months 26.08 22.49
Maximum of Months 26.79 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 22.49
February 24.39 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.45 22.49
February 24.43 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.41 26.87
October 24.54 26.22
November 24.49 24.76
December 24.50 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.54 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.42 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.54 22.49
February 24.54 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.50 26.87
October 24.65 26.22
November 24.67 24.76
December 24.66 23.69
     
Annual Sum or Average 24.50 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.67 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.55 22.49
February 24.54 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.66 26.22
November 24.67 24.76
December 24.67 23.69
     
Annual Sum or Average 24.50 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.67 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.33 22.49
February 26.38 22.80
March 26.37 23.17
April 26.41 23.76
May 26.61 25.23
June 26.70 25.87
July 26.80 26.90
August 26.80 27.06
September 26.84 26.87
October 26.80 26.22
November 26.62 24.76
December 26.50 23.69
     
Annual Sum or Average 26.60 24.91
Minimum of Months 26.33 22.49
Maximum of Months 26.84 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 22.49
February 24.39 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.45 22.49
February 24.43 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.41 26.87
October 24.55 26.22
November 24.49 24.76
December 24.50 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.55 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.42 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.54 22.49
February 24.54 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.65 26.22
November 24.66 24.76
December 24.66 23.69
     
Annual Sum or Average 24.49 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.66 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.54 22.49
February 24.54 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.66 26.22
November 24.67 24.76
December 24.66 23.69
     
Annual Sum or Average 24.50 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.67 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.45 22.49
February 26.49 22.80
March 26.48 23.17
April 26.51 23.76
May 26.71 25.23
June 26.78 25.87
July 26.88 26.90
August 26.88 27.06
September 26.92 26.87
October 26.90 26.22
November 26.72 24.76
December 26.61 23.69
     
Annual Sum or Average 26.70 24.91
Minimum of Months 26.45 22.49
Maximum of Months 26.92 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 22.49
February 24.39 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.45 22.49
February 24.43 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.42 26.87
October 24.54 26.22
November 24.49 24.76
December 24.50 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.54 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.37 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.53 22.49
February 24.53 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.64 26.22
November 24.65 24.76
December 24.65 23.69
     
Annual Sum or Average 24.49 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.65 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.53 22.49
February 24.53 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.64 26.22
November 24.66 24.76
December 24.65 23.69
     
Annual Sum or Average 24.49 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.66 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 27.04 22.49
February 27.08 22.80
March 27.07 23.17
April 27.10 23.76
May 27.30 25.23
June 27.36 25.87
July 27.46 26.90
August 27.46 27.06
September 27.50 26.87
October 27.49 26.22
November 27.31 24.76
December 27.20 23.69
     
Annual Sum or Average 27.28 24.91
Minimum of Months 27.04 22.49
Maximum of Months 27.50 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.37 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.44 22.49
February 24.42 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.42 26.87
October 24.54 26.22
November 24.49 24.76
December 24.50 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.54 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.36 22.80
March 24.37 23.17
April 24.39 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.42 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.52 22.49
February 24.52 22.80
March 24.40 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.63 26.22
November 24.64 24.76
December 24.64 23.69
     
Annual Sum or Average 24.49 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.64 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.52 22.49
February 24.52 22.80
March 24.39 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.64 26.22
November 24.65 24.76
December 24.64 23.69
     
Annual Sum or Average 24.49 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.65 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.42 22.49
February 26.47 22.80
March 26.46 23.17
April 26.49 23.76
May 26.69 25.23
June 26.76 25.87
July 26.86 26.90
August 26.86 27.06
September 26.90 26.87
October 26.89 26.22
November 26.70 24.76
December 26.58 23.69
     
Annual Sum or Average 26.67 24.91
Minimum of Months 26.42 22.49
Maximum of Months 26.90 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.44 22.49
February 24.42 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.42 26.87
October 24.54 26.22
November 24.49 24.76
December 24.49 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.54 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 22.49
February 24.36 22.80
March 24.36 23.17
April 24.39 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.40 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.41 25.23
June 24.43 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.51 22.49
February 24.51 22.80
March 24.39 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.49 26.87
October 24.62 26.22
November 24.63 24.76
December 24.63 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.63 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.52 22.49
February 24.52 22.80
March 24.39 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.48 26.87
October 24.63 26.22
November 24.64 24.76
December 24.63 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.64 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.32 22.49
February 26.37 22.80
March 26.36 23.17
April 26.40 23.76
May 26.61 25.23
June 26.68 25.87
July 26.78 26.90
August 26.78 27.06
September 26.82 26.87
October 26.80 26.22
November 26.61 24.76
December 26.49 23.69
     
Annual Sum or Average 26.59 24.91
Minimum of Months 26.32 22.49
Maximum of Months 26.82 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.38 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.36 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.43 22.49
February 24.42 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.42 26.87
October 24.53 26.22
November 24.48 24.76
December 24.49 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.53 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.36 22.80
March 24.36 23.17
April 24.38 23.76
May 24.41 25.23
June 24.43 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.37 22.80
March 24.36 23.17
April 24.38 23.76
May 24.41 25.23
June 24.43 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.39 23.69
     
Annual Sum or Average 24.40 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.50 22.49
February 24.51 22.80
March 24.39 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.48 26.87
October 24.61 26.22
November 24.63 24.76
December 24.62 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.63 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.51 22.49
February 24.51 22.80
March 24.39 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.48 26.87
October 24.62 26.22
November 24.63 24.76
December 24.63 23.69
     
Annual Sum or Average 24.48 24.91
Minimum of Months 24.39 22.49
Maximum of Months 24.63 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.30 22.49
February 26.36 22.80
March 26.35 23.17
April 26.39 23.76
May 26.60 25.23
June 26.67 25.87
July 26.78 26.90
August 26.78 27.06
September 26.81 26.87
October 26.80 26.22
November 26.60 24.76
December 26.48 23.69
     
Annual Sum or Average 26.58 24.91
Minimum of Months 26.30 22.49
Maximum of Months 26.81 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 22.49
February 24.38 22.80
March 24.36 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.40 24.76
December 24.40 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.36 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.36 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.38 23.69
     
Annual Sum or Average 24.38 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.43 22.49
February 24.41 22.80
March 24.37 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.42 26.87
October 24.53 26.22
November 24.48 24.76
December 24.49 23.69
     
Annual Sum or Average 24.43 24.91
Minimum of Months 24.37 22.49
Maximum of Months 24.53 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.35 22.80
March 24.36 23.17
April 24.38 23.76
May 24.41 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.35 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.36 22.80
March 24.36 23.17
April 24.38 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.38 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 22.49
February 24.36 22.80
March 24.36 23.17
April 24.38 23.76
May 24.41 25.23
June 24.42 25.87
July 24.44 26.90
August 24.41 27.06
September 24.43 26.87
October 24.41 26.22
November 24.40 24.76
December 24.38 23.69
     
Annual Sum or Average 24.39 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.44 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.49 22.49
February 24.50 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.48 26.87
October 24.59 26.22
November 24.61 24.76
December 24.61 23.69
     
Annual Sum or Average 24.47 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.61 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.49 22.49
February 24.50 22.80
March 24.38 23.17
April 24.39 23.76
May 24.40 25.23
June 24.40 25.87
July 24.41 26.90
August 24.40 27.06
September 24.48 26.87
October 24.60 26.22
November 24.61 24.76
December 24.61 23.69
     
Annual Sum or Average 24.47 24.91
Minimum of Months 24.38 22.49
Maximum of Months 24.61 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.32 22.49
February 26.38 22.80
March 26.38 23.17
April 26.43 23.76
May 26.67 25.23
June 26.74 25.87
July 26.86 26.90
August 26.87 27.06
September 26.89 26.87
October 26.86 26.22
November 26.64 24.76
December 26.51 23.69
     
Annual Sum or Average 26.63 24.91
Minimum of Months 26.32 22.49
Maximum of Months 26.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 22.49
February 24.34 22.80
March 24.33 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.39 24.76
December 24.39 23.69
     
Annual Sum or Average 24.38 24.91
Minimum of Months 24.33 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 22.49
February 24.31 22.80
March 24.32 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.40 26.87
October 24.40 26.22
November 24.38 24.76
December 24.37 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.31 22.49
Maximum of Months 24.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.41 22.49
February 24.38 22.80
March 24.33 23.17
April 24.38 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.41 26.87
October 24.54 26.22
November 24.46 24.76
December 24.49 23.69
     
Annual Sum or Average 24.42 24.91
Minimum of Months 24.33 22.49
Maximum of Months 24.54 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 22.49
February 24.30 22.80
March 24.31 23.17
April 24.37 23.76
May 24.40 25.23
June 24.42 25.87
July 24.43 26.90
August 24.41 27.06
September 24.40 26.87
October 24.40 26.22
November 24.38 24.76
December 24.37 23.69
     
Annual Sum or Average 24.38 24.91
Minimum of Months 24.30 22.49
Maximum of Months 24.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 22.49
February 24.31 22.80
March 24.32 23.17
April 24.36 23.76
May 24.40 25.23
June 24.41 25.87
July 24.42 26.90
August 24.40 27.06
September 24.42 26.87
October 24.40 26.22
November 24.38 24.76
December 24.37 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.29 22.49
Maximum of Months 24.42 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 22.49
February 24.31 22.80
March 24.32 23.17
April 24.36 23.76
May 24.40 25.23
June 24.41 25.87
July 24.42 26.90
August 24.40 27.06
September 24.42 26.87
October 24.40 26.22
November 24.38 24.76
December 24.37 23.69
     
Annual Sum or Average 24.37 24.91
Minimum of Months 24.29 22.49
Maximum of Months 24.42 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.45 22.49
February 24.44 22.80
March 24.34 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.43 26.87
October 24.53 26.22
November 24.52 24.76
December 24.55 23.69
     
Annual Sum or Average 24.44 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.55 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.45 22.49
February 24.44 22.80
March 24.34 23.17
April 24.37 23.76
May 24.40 25.23
June 24.40 25.87
July 24.40 26.90
August 24.40 27.06
September 24.43 26.87
October 24.54 26.22
November 24.53 24.76
December 24.56 23.69
     
Annual Sum or Average 24.44 24.91
Minimum of Months 24.34 22.49
Maximum of Months 24.56 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.89 22.49
February 26.98 22.80
March 27.01 23.17
April 27.10 23.76
May 27.43 25.23
June 27.51 25.87
July 27.67 26.90
August 27.68 27.06
September 27.67 26.87
October 27.59 26.22
November 27.30 24.76
December 27.12 23.69
     
Annual Sum or Average 27.33 24.91
Minimum of Months 26.89 22.49
Maximum of Months 27.68 27.06



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:04

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.290909E+12 173724.743 03-JAN-18:15 22204.399 56867.515 18330.667 0.000 60078.715 10720.100 1760.931 2616.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.277681E+12 182809.012 17-FEB-18:30 22204.399 56867.515 18330.667 0.000 68710.919 10720.100 1760.931 3068.592 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.302707E+12 176953.559 17-MAR-17:30 22204.399 56867.515 18330.667 0.000 73822.576 0.000 1760.931 2821.582 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.292312E+12 171401.970 19-APR-17:45 22204.399 56867.515 18330.667 0.000 68404.972 0.000 1760.931 2687.597 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.327337E+12 179692.497 09-MAY-19:45 25049.151 49704.829 18330.667 0.000 70203.381 10720.100 1760.931 2977.866 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.331250E+12 177619.928 17-JUN-19:15 25049.151 49704.829 18330.667 0.000 68258.089 10720.100 1760.931 2850.589 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.354014E+12 182336.531 22-JUL-19:00 25049.151 49704.829 18330.667 0.000 72696.637 10720.100 1760.931 3128.645 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.352617E+12 182002.243 01-AUG-19:45 25049.151 49704.829 18330.667 0.000 72463.696 10720.100 1760.931 3027.297 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.348007E+12 189352.702 15-SEP-18:45 25049.151 51564.864 18330.667 0.000 77786.118 10720.100 1760.931 3126.257 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.347025E+12 183632.622 28-OCT-17:00 22204.399 56867.515 18330.667 0.000 69834.177 10720.100 1760.931 2768.944 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.322755E+12 185253.413 04-NOV-17:00 22204.399 56867.515 18330.667 0.000 71434.024 10720.100 1760.931 2789.889 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.316806E+12 181307.258 01-DEC-18:45 22204.399 56867.515 18330.667 0.000 67413.992 10720.100 1760.931 2863.765 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.386342E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.277681E+12 171401.970   22204.399 49704.829 18330.667 0.000 60078.715 0.000 1760.931 2616.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.354014E+12 189352.702   25049.151 56867.515 18330.667 0.000 77786.118 10720.100 1760.931 3128.645 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:04

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.728175E+11 76144.636 02-JAN-07:00 0.000 0.000 0.000 76144.636 76144.636 76144.636 0.000
February 0.654109E+11 76117.972 06-FEB-07:00 0.000 0.000 0.000 76117.972 76117.972 76117.972 0.000
March 0.711815E+11 75661.427 19-MAR-06:45 0.000 0.000 0.000 75661.427 75661.427 75661.427 0.000
April 0.671230E+11 75468.431 02-APR-06:00 0.000 0.000 0.000 75468.431 75468.431 75468.431 0.000
May 0.674947E+11 73112.114 02-MAY-06:45 0.000 0.000 0.000 73112.114 73112.114 73112.114 0.000
June 0.639716E+11 70274.776 06-JUN-06:00 0.000 0.000 0.000 70274.776 70274.776 70274.776 0.000
July 0.655540E+11 67642.479 04-JUL-06:00 0.000 0.000 0.000 67642.479 67642.479 67642.479 0.000
August 0.659552E+11 69033.149 20-AUG-06:00 0.000 0.000 0.000 69033.149 69033.149 69033.149 0.000
September 0.650839E+11 72457.903 17-SEP-06:45 0.000 0.000 0.000 72457.903 72457.903 72457.903 0.000
October 0.690551E+11 74644.684 31-OCT-06:00 0.000 0.000 0.000 74644.684 74644.684 74644.684 0.000
November 0.685832E+11 75841.696 29-NOV-07:00 0.000 0.000 0.000 75841.696 75841.696 75841.696 0.000
December 0.722824E+11 76099.837 29-DEC-07:45 0.000 0.000 0.000 76099.837 76099.837 76099.837 0.000
                     
Annual Sum or Average 0.814513E+12     0.000 0.000 0.000        
Minimum of Months 0.639716E+11 67642.479   0.000 0.000 0.000 67642.479 67642.479 67642.479 0.000
Maximum of Months 0.728175E+11 76144.636   0.000 0.000 0.000 76144.636 76144.636 76144.636 0.000