Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2018-10-19 09:40:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3590.03 | 458.12 | 508.51 |
Net Site Energy | 3590.03 | 458.12 | 508.51 |
Total Source Energy | 9189.84 | 1172.70 | 1301.70 |
Net Source Energy | 9189.84 | 1172.70 | 1301.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 3.29 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 267.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 488.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 35.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.58 | 0.00 | 0.00 | 0.00 | 0.00 | 811.52 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1045.87 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2543.57 | 1046.46 | 0.00 | 0.00 | 0.00 | 5590.04 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 3.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 267.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 488.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 35.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 11.58 | 0.00 | 0.00 | 0.00 | 0.00 | 811.52 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1045.87 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 114.26 | 148.23 | 0.00 | 0.00 | 0.00 | 0.79 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 360.28 | 148.23 | 0.00 | 0.00 | 0.00 | 0.79 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 102.94 | 133.54 | 0.00 | 0.00 | 0.00 | 0.71 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 324.58 | 133.54 | 0.00 | 0.00 | 0.00 | 0.71 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2543.57 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2543.57 | 100.00 |
Total On-Site and Utility Electric Sources | 2543.57 | 100.00 |
Total Electricity End Uses | 2543.57 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5590.04 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5590.04 | 100.00 |
Total Water End Uses | 5590.04 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 24.50 |
Time Setpoint Not Met During Occupied Cooling | 153.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1560.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-OCT-17:15 | 30-MAR-06:15 | - | - | - | 15-OCT-07:00 |
Heating | 0.00 | 13019.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45725.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15486.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1192.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1479.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 80594.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 154821.26 | 93614.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 13019.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45725.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 18331.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 3872.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 15486.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1192.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1479.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 80594.78 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 10.41 | 0.64 | 0.00 | 0.00 | 0.00 |
Cooling | 847.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1546.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 113.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 36.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1133.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8055.48 | 1134.36 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.47 | 0.09 | 0.00 | 0.00 | 0.00 |
Cooling | 120.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 219.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 160.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1141.02 | 160.68 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.47 | 0.09 | 0.00 | 0.00 | 0.00 |
Cooling | 120.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 219.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 160.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1141.02 | 160.68 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.77 | 83.77 | 168.56 | |
Exterior Lighting Total | 10720.10 | 168.56 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 208285.94 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 166628.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2839.53 | 2106.80 | 732.73 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2522.87 | 1868.55 | 654.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3844.40 | 2883.77 | 960.63 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1908.88 | 1416.10 | 492.78 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1293.49 | 933.64 | 359.85 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1273.15 | 918.20 | 354.96 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1823.85 | 1325.85 | 497.99 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1890.97 | 1377.58 | 513.39 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3515.55 | 2628.17 | 887.39 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3141.05 | 2344.50 | 796.55 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3233.24 | 2422.84 | 810.40 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2453.21 | 1835.33 | 617.88 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1728.18 | 1265.02 | 463.16 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1710.59 | 1251.62 | 458.97 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2319.45 | 1706.73 | 612.72 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2345.27 | 1726.58 | 618.69 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3520.99 | 2631.89 | 889.09 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3163.52 | 2361.34 | 802.18 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3033.06 | 2268.66 | 764.40 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2489.29 | 1862.85 | 626.43 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1777.51 | 1302.55 | 474.96 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1760.18 | 1289.34 | 470.83 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2352.47 | 1731.90 | 620.57 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2364.72 | 1741.32 | 623.40 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3519.98 | 2630.78 | 889.20 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3170.01 | 2366.00 | 804.00 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3058.33 | 2273.89 | 784.44 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2496.07 | 1867.86 | 628.21 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1798.15 | 1318.21 | 479.94 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1780.98 | 1305.12 | 475.86 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2360.00 | 1737.52 | 622.48 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2370.23 | 1745.38 | 624.84 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3549.60 | 2653.26 | 896.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3206.03 | 2393.40 | 812.64 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3090.25 | 2298.15 | 792.10 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2531.83 | 1895.20 | 636.63 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1843.61 | 1352.84 | 490.78 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1826.57 | 1339.85 | 486.73 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2394.87 | 1764.18 | 630.69 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2404.80 | 1771.81 | 632.98 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3493.53 | 2609.96 | 883.57 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3153.62 | 2352.97 | 800.65 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3039.32 | 2258.82 | 780.50 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2480.76 | 1855.77 | 624.98 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1803.10 | 1321.84 | 481.27 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1786.28 | 1309.02 | 477.27 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2345.26 | 1725.94 | 619.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2355.14 | 1733.54 | 621.60 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3470.11 | 2591.77 | 878.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3134.29 | 2337.96 | 796.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3020.23 | 2243.97 | 776.26 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2462.13 | 1841.32 | 620.81 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1792.87 | 1313.96 | 478.91 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1776.22 | 1301.27 | 474.94 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2326.70 | 1711.58 | 615.12 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2336.56 | 1719.17 | 617.40 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3464.65 | 2587.40 | 877.25 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3132.54 | 2336.45 | 796.09 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3017.98 | 2242.08 | 775.91 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2460.25 | 1839.76 | 620.48 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1799.02 | 1318.60 | 480.42 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1782.53 | 1306.04 | 476.49 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2325.00 | 1710.19 | 614.82 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2334.88 | 1717.78 | 617.09 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3549.97 | 2652.75 | 897.22 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3220.67 | 2403.89 | 816.78 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3084.88 | 2292.33 | 792.55 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2487.83 | 1860.84 | 626.99 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1881.80 | 1381.72 | 500.07 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1865.25 | 1369.11 | 496.14 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2381.82 | 1752.79 | 629.03 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2391.69 | 1760.39 | 631.31 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4272.38 | 3203.58 | 1068.80 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3859.75 | 2891.51 | 968.24 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3733.69 | 2790.42 | 943.26 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2958.33 | 2217.81 | 740.51 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2342.21 | 1720.34 | 621.88 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2341.28 | 1719.60 | 621.67 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3106.45 | 2309.33 | 797.11 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3112.94 | 2315.26 | 797.68 | 0.74 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2839.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2522.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3844.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1908.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1293.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1273.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1823.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1890.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3515.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3141.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3233.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2453.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1728.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1710.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2319.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2345.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3520.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3163.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3033.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2489.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1777.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1760.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2352.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2364.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3519.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3170.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3058.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2496.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1798.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1780.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2360.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2370.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3549.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3206.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3090.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2531.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1843.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1826.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2394.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2404.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3493.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3153.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3039.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2480.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1803.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1786.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2345.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2355.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3470.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3134.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3020.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2462.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1792.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1776.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2326.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2336.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3464.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3132.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3017.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2460.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1799.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1782.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2325.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2334.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3549.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3220.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3084.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2487.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1881.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1865.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2381.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2391.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4272.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3859.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3733.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2958.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2342.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2341.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3106.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3112.94 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 1465.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 1470.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2103.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 1468.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 1436.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 1439.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 1461.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 1438.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1421.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1423.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1424.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1422.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1434.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1435.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1434.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1435.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1427.89 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1427.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1428.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1428.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 1486.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 1486.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 1487.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 1487.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 1522.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 1521.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 1523.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 1522.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 1558.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 1557.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 1559.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 1558.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 1671.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 1668.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 1673.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 1670.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1115.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2050.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2051.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2052.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2053.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 1493.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 1493.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 1489.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 1489.36 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 211.58 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.41 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 293.46 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 143.73 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.08 | 90.96 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.08 | 89.35 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.50 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 134.93 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 266.83 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.92 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.12 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.56 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 125.61 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 124.21 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.46 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 171.54 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.20 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 239.66 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.87 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.45 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.53 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 128.15 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.09 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 173.08 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.07 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 240.14 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 229.14 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.97 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 131.17 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.80 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.67 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 173.50 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.42 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.01 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.68 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.84 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 134.79 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 133.43 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.46 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 176.26 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 264.85 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 238.74 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 227.53 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 189.68 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 131.54 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.20 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 171.44 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.24 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 262.92 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.15 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 225.96 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 188.15 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.71 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.38 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.93 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.72 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 262.45 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 236.99 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 225.75 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.98 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 131.19 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.88 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.78 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.57 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.32 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 244.07 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.87 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.19 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 137.80 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 136.48 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.10 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.89 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 326.66 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 294.67 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.26 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.85 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.39 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.31 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.58 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 233.36 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0045 | 1155.48 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1972.78 | 2367.33 | 0.157 | 0.189 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 30.90 | 0.00820 |
G NW APARTMENT | 1747.40 | 2096.88 | 0.139 | 0.167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 30.23 | 0.00820 |
OFFICE | 2736.25 | 3283.50 | 0.218 | 0.262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 28.92 | 0.00820 |
G NE APARTMENT | 1340.06 | 1608.07 | 0.107 | 0.128 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
G N1 APARTMENT | 848.14 | 1017.76 | 0.068 | 0.081 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
G N2 APARTMENT | 833.13 | 999.76 | 0.066 | 0.080 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
G S1 APARTMENT | 1207.46 | 1448.95 | 0.096 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
G S2 APARTMENT | 1258.07 | 1509.68 | 0.100 | 0.120 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F2 SW APARTMENT | 2487.93 | 2985.51 | 0.199 | 0.238 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F2 NW APARTMENT | 2218.31 | 2661.97 | 0.177 | 0.212 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F2 SE APARTMENT | 2304.16 | 2764.99 | 0.184 | 0.221 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.25 | 0.00820 |
F2 NE APARTMENT | 1748.82 | 2098.59 | 0.140 | 0.167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F2 N1 APARTMENT | 1171.16 | 1405.39 | 0.093 | 0.112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F2 N2 APARTMENT | 1158.09 | 1389.70 | 0.092 | 0.111 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F2 S1 APARTMENT | 1579.99 | 1895.99 | 0.126 | 0.151 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F2 S2 APARTMENT | 1599.44 | 1919.33 | 0.128 | 0.153 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F3 SW APARTMENT | 2491.36 | 2989.63 | 0.199 | 0.239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F3 NW APARTMENT | 2234.62 | 2681.54 | 0.178 | 0.214 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F3 SE APARTMENT | 2152.60 | 2583.12 | 0.172 | 0.206 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.25 | 0.00820 |
F3 NE APARTMENT | 1775.76 | 2130.91 | 0.142 | 0.170 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F3 N1 APARTMENT | 1207.75 | 1449.30 | 0.096 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F3 N2 APARTMENT | 1194.86 | 1433.83 | 0.095 | 0.114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F3 S1 APARTMENT | 1604.54 | 1925.45 | 0.128 | 0.154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F3 S2 APARTMENT | 1613.77 | 1936.52 | 0.129 | 0.155 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F4 SW APARTMENT | 2490.10 | 2988.12 | 0.199 | 0.238 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F4 NW APARTMENT | 2239.04 | 2686.85 | 0.179 | 0.214 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F4 SE APARTMENT | 2136.50 | 2563.80 | 0.170 | 0.205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.86 | 0.00820 |
F4 NE APARTMENT | 1780.58 | 2136.69 | 0.142 | 0.170 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F4 N1 APARTMENT | 1222.99 | 1467.59 | 0.098 | 0.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F4 N2 APARTMENT | 1210.22 | 1452.26 | 0.097 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F4 S1 APARTMENT | 1609.96 | 1931.95 | 0.128 | 0.154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F4 S2 APARTMENT | 1617.66 | 1941.20 | 0.129 | 0.155 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
M SW APARTMENT | 2512.02 | 3014.42 | 0.200 | 0.241 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
M NW APARTMENT | 2265.78 | 2718.94 | 0.181 | 0.217 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
M SE APARTMENT | 2160.16 | 2592.20 | 0.172 | 0.207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.86 | 0.00820 |
M NE APARTMENT | 1807.35 | 2168.82 | 0.144 | 0.173 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
M N1 APARTMENT | 1256.78 | 1508.14 | 0.100 | 0.120 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
M N2 APARTMENT | 1244.10 | 1492.92 | 0.099 | 0.119 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
M S1 APARTMENT | 1636.00 | 1963.20 | 0.131 | 0.157 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
M S2 APARTMENT | 1643.48 | 1972.17 | 0.131 | 0.157 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F6 SW APARTMENT | 2469.42 | 2963.31 | 0.197 | 0.236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F6 NW APARTMENT | 2226.03 | 2671.23 | 0.178 | 0.213 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F6 SE APARTMENT | 2121.49 | 2545.79 | 0.169 | 0.203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.86 | 0.00820 |
F6 NE APARTMENT | 1768.54 | 2122.25 | 0.141 | 0.169 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F6 N1 APARTMENT | 1226.46 | 1471.75 | 0.098 | 0.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F6 N2 APARTMENT | 1213.95 | 1456.74 | 0.097 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F6 S1 APARTMENT | 1598.49 | 1918.19 | 0.128 | 0.153 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F6 S2 APARTMENT | 1605.94 | 1927.13 | 0.128 | 0.154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F7 SW APARTMENT | 2451.48 | 2941.77 | 0.196 | 0.235 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F7 NW APARTMENT | 2211.21 | 2653.45 | 0.176 | 0.212 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F7 SE APARTMENT | 2106.84 | 2528.20 | 0.168 | 0.202 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.86 | 0.00820 |
F7 NE APARTMENT | 1754.28 | 2105.13 | 0.140 | 0.168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F7 N1 APARTMENT | 1218.73 | 1462.48 | 0.097 | 0.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F7 N2 APARTMENT | 1206.35 | 1447.62 | 0.096 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F7 S1 APARTMENT | 1584.38 | 1901.26 | 0.126 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F7 S2 APARTMENT | 1591.82 | 1910.18 | 0.127 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F8 SW APARTMENT | 2447.09 | 2936.51 | 0.195 | 0.234 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F8 NW APARTMENT | 2209.65 | 2651.58 | 0.176 | 0.212 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F8 SE APARTMENT | 2104.90 | 2525.88 | 0.168 | 0.202 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.86 | 0.00820 |
F8 NE APARTMENT | 1752.69 | 2103.23 | 0.140 | 0.168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F8 N1 APARTMENT | 1223.23 | 1467.88 | 0.098 | 0.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F8 N2 APARTMENT | 1210.98 | 1453.17 | 0.097 | 0.116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F8 S1 APARTMENT | 1582.98 | 1899.57 | 0.126 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F8 S2 APARTMENT | 1590.42 | 1908.50 | 0.127 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F9 SW APARTMENT | 2511.12 | 3013.35 | 0.200 | 0.240 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
F9 NW APARTMENT | 2275.71 | 2730.86 | 0.182 | 0.218 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 29.83 | 0.00820 |
F9 SE APARTMENT | 2152.65 | 2583.18 | 0.172 | 0.206 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
F9 NE APARTMENT | 1773.34 | 2128.00 | 0.141 | 0.170 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 27.54 | 0.00820 |
F9 N1 APARTMENT | 1284.87 | 1541.85 | 0.103 | 0.123 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F9 N2 APARTMENT | 1272.56 | 1527.07 | 0.102 | 0.122 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 28.83 | 0.00820 |
F9 S1 APARTMENT | 1623.26 | 1947.91 | 0.130 | 0.155 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
F9 S2 APARTMENT | 1630.70 | 1956.84 | 0.130 | 0.156 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
T SW APARTMENT | 3045.72 | 3654.87 | 0.243 | 0.292 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
T NW APARTMENT | 2747.47 | 3296.96 | 0.219 | 0.263 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41 | 0.00820 |
T SE APARTMENT | 2641.14 | 3169.37 | 0.211 | 0.253 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
T NE APARTMENT | 2115.08 | 2538.10 | 0.169 | 0.203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 28.25 | 0.00820 |
T N1 APARTMENT | 1588.68 | 1906.41 | 0.127 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
T N2 APARTMENT | 1587.95 | 1905.54 | 0.127 | 0.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
T S1 APARTMENT | 2168.58 | 2602.30 | 0.173 | 0.208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
T S2 APARTMENT | 2175.82 | 2610.99 | 0.174 | 0.208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 772.72 | 927.27 | 0.035 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
G NW APARTMENT | 776.78 | 932.14 | 0.035 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
OFFICE | 1093.66 | 1312.40 | 0.050 | 0.060 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3.80 | 0.00506 |
G NE APARTMENT | 775.41 | 930.49 | 0.035 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
G N1 APARTMENT | 426.60 | 511.92 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
G N2 APARTMENT | 426.57 | 511.88 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
G S1 APARTMENT | 419.26 | 503.11 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
G S2 APARTMENT | 426.25 | 511.50 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
F2 SW APARTMENT | 748.24 | 897.89 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 NW APARTMENT | 750.88 | 901.05 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 SE APARTMENT | 769.33 | 923.20 | 0.035 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 NE APARTMENT | 749.93 | 899.92 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 N1 APARTMENT | 318.91 | 382.69 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 N2 APARTMENT | 318.88 | 382.65 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 S1 APARTMENT | 318.45 | 382.15 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F2 S2 APARTMENT | 320.02 | 384.02 | 0.015 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 SW APARTMENT | 735.60 | 882.72 | 0.033 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 NW APARTMENT | 737.17 | 884.60 | 0.033 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 SE APARTMENT | 737.93 | 885.52 | 0.033 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 NE APARTMENT | 736.77 | 884.12 | 0.033 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 N1 APARTMENT | 291.24 | 349.49 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 N2 APARTMENT | 291.23 | 349.47 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 S1 APARTMENT | 290.16 | 348.19 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F3 S2 APARTMENT | 290.43 | 348.52 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 SW APARTMENT | 746.25 | 895.50 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 NW APARTMENT | 747.38 | 896.86 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 SE APARTMENT | 746.60 | 895.93 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 NE APARTMENT | 747.41 | 896.90 | 0.034 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 N1 APARTMENT | 290.01 | 348.02 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 N2 APARTMENT | 290.01 | 348.02 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 S1 APARTMENT | 289.16 | 346.99 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F4 S2 APARTMENT | 289.21 | 347.05 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M SW APARTMENT | 741.01 | 889.21 | 0.034 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M NW APARTMENT | 740.75 | 888.90 | 0.034 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M SE APARTMENT | 741.43 | 889.72 | 0.034 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M NE APARTMENT | 741.13 | 889.36 | 0.034 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M N1 APARTMENT | 277.78 | 333.34 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M N2 APARTMENT | 277.80 | 333.35 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M S1 APARTMENT | 278.29 | 333.95 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
M S2 APARTMENT | 278.31 | 333.97 | 0.013 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 SW APARTMENT | 790.89 | 949.07 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 NW APARTMENT | 790.95 | 949.14 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 SE APARTMENT | 791.59 | 949.91 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 NE APARTMENT | 791.64 | 949.97 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 N1 APARTMENT | 316.35 | 379.62 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 N2 APARTMENT | 316.37 | 379.65 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 S1 APARTMENT | 316.52 | 379.83 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F6 S2 APARTMENT | 316.54 | 379.85 | 0.014 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 SW APARTMENT | 820.82 | 984.98 | 0.037 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 NW APARTMENT | 820.26 | 984.31 | 0.037 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 SE APARTMENT | 821.78 | 986.14 | 0.037 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 NE APARTMENT | 821.22 | 985.47 | 0.037 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 N1 APARTMENT | 338.69 | 406.43 | 0.015 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 N2 APARTMENT | 338.72 | 406.46 | 0.015 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 S1 APARTMENT | 339.46 | 407.36 | 0.015 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F7 S2 APARTMENT | 339.49 | 407.39 | 0.015 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 SW APARTMENT | 851.50 | 1021.80 | 0.039 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 NW APARTMENT | 850.26 | 1020.31 | 0.039 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 SE APARTMENT | 852.70 | 1023.24 | 0.039 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 NE APARTMENT | 851.46 | 1021.75 | 0.039 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 N1 APARTMENT | 362.84 | 435.41 | 0.016 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 N2 APARTMENT | 362.88 | 435.45 | 0.016 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 S1 APARTMENT | 364.27 | 437.12 | 0.017 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F8 S2 APARTMENT | 364.30 | 437.16 | 0.017 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 SW APARTMENT | 947.43 | 1136.92 | 0.043 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 NW APARTMENT | 944.34 | 1133.21 | 0.043 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 SE APARTMENT | 948.86 | 1138.63 | 0.043 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 NE APARTMENT | 945.77 | 1134.93 | 0.043 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 N1 APARTMENT | 446.70 | 536.04 | 0.020 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 N2 APARTMENT | 446.74 | 536.09 | 0.020 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 S1 APARTMENT | 449.60 | 539.52 | 0.020 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
F9 S2 APARTMENT | 449.64 | 539.57 | 0.020 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T SW APARTMENT | 1267.81 | 1521.38 | 0.057 | 0.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T NW APARTMENT | 1268.68 | 1522.41 | 0.058 | 0.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T SE APARTMENT | 1269.28 | 1523.13 | 0.058 | 0.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T NE APARTMENT | 1270.14 | 1524.17 | 0.058 | 0.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T N1 APARTMENT | 796.25 | 955.50 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T N2 APARTMENT | 796.29 | 955.55 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T S1 APARTMENT | 792.94 | 951.53 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
T S2 APARTMENT | 792.99 | 951.58 | 0.036 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 3.80 | 0.00506 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.19 | 0.19 | 0.04 | 0.04 |
AIRLOOP G NW | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP OFFICE | 0.26 | 0.26 | 0.06 | 0.06 |
AIRLOOP G NE | 0.13 | 0.13 | 0.04 | 0.04 |
AIRLOOP G N1 | 0.08 | 0.08 | 0.03 | 0.03 |
AIRLOOP G N2 | 0.08 | 0.08 | 0.03 | 0.03 |
AIRLOOP G S1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP G S2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F2 SW | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F2 NW | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F2 SE | 0.22 | 0.22 | 0.04 | 0.04 |
AIRLOOP F2 NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F2 N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F2 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F2 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F2 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F3 SW | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F3 NW | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F3 SE | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F3 NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F3 N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP F3 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F3 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F4 SW | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F4 NW | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F4 SE | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP F4 NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F4 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F4 N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F4 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F4 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP M SW | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP M NW | 0.22 | 0.22 | 0.04 | 0.04 |
AIRLOOP M SE | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP M NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP M N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F6 NW | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F6 SE | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP F6 NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F6 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F6 N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F6 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F6 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F7 SW | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F7 NW | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP F7 SE | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP F7 NE | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F7 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F7 N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F7 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F7 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F8 SW | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F8 NW | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F8 SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F8 NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F8 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F8 N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F8 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F8 S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F9 SW | 0.24 | 0.24 | 0.05 | 0.05 |
AIRLOOP F9 NW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F9 SE | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F9 NE | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F9 N1 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F9 N2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F9 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F9 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP T SW | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP T NW | 0.26 | 0.26 | 0.07 | 0.07 |
AIRLOOP T SE | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP T NE | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP T N1 | 0.15 | 0.15 | 0.04 | 0.04 |
AIRLOOP T N2 | 0.15 | 0.15 | 0.04 | 0.04 |
AIRLOOP T S1 | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP T S2 | 0.21 | 0.21 | 0.04 | 0.04 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3353.75 | 5168.00 | 1034.75 |
G NW APARTMENT | 2699.00 | 6659.00 | 1141.25 |
OFFICE | 1472.50 | 157.75 | 0.50 |
G NE APARTMENT | 2535.50 | 6915.00 | 1214.75 |
G N1 APARTMENT | 2391.00 | 7411.50 | 1479.25 |
G N2 APARTMENT | 2372.50 | 7425.25 | 1478.50 |
G S1 APARTMENT | 3007.00 | 5842.75 | 1274.25 |
G S2 APARTMENT | 3055.25 | 5724.75 | 1252.75 |
F2 SW APARTMENT | 5653.75 | 1910.50 | 474.75 |
F2 NW APARTMENT | 3877.75 | 4281.00 | 632.75 |
F2 SE APARTMENT | 5811.00 | 1741.00 | 441.00 |
F2 NE APARTMENT | 3636.50 | 4730.50 | 680.75 |
F2 N1 APARTMENT | 3325.00 | 5279.25 | 960.75 |
F2 N2 APARTMENT | 3293.75 | 5337.50 | 963.75 |
F2 S1 APARTMENT | 5546.75 | 1969.75 | 616.25 |
F2 S2 APARTMENT | 5574.75 | 1943.00 | 610.25 |
F3 SW APARTMENT | 6164.50 | 1425.50 | 443.00 |
F3 NW APARTMENT | 4401.25 | 3498.00 | 572.75 |
F3 SE APARTMENT | 6119.50 | 1488.50 | 448.00 |
F3 NE APARTMENT | 4142.00 | 3939.75 | 614.00 |
F3 N1 APARTMENT | 3945.75 | 4144.25 | 829.25 |
F3 N2 APARTMENT | 3907.75 | 4201.50 | 832.50 |
F3 S1 APARTMENT | 6256.50 | 1331.00 | 566.50 |
F3 S2 APARTMENT | 6253.00 | 1328.50 | 565.50 |
F4 SW APARTMENT | 6229.50 | 1393.25 | 449.25 |
F4 NW APARTMENT | 4514.00 | 3336.00 | 562.50 |
F4 SE APARTMENT | 6130.50 | 1483.25 | 447.75 |
F4 NE APARTMENT | 4255.25 | 3757.25 | 606.75 |
F4 N1 APARTMENT | 4152.00 | 3810.50 | 791.00 |
F4 N2 APARTMENT | 4114.75 | 3866.50 | 798.50 |
F4 S1 APARTMENT | 6352.25 | 1261.25 | 565.50 |
F4 S2 APARTMENT | 6344.50 | 1268.00 | 567.00 |
M SW APARTMENT | 6263.00 | 1376.00 | 446.25 |
M NW APARTMENT | 4570.25 | 3254.00 | 552.25 |
M SE APARTMENT | 6157.00 | 1467.50 | 441.00 |
M NE APARTMENT | 4307.25 | 3646.00 | 585.00 |
M N1 APARTMENT | 4262.00 | 3614.50 | 750.75 |
M N2 APARTMENT | 4221.00 | 3673.75 | 753.75 |
M S1 APARTMENT | 6401.75 | 1220.25 | 556.75 |
M S2 APARTMENT | 6396.00 | 1230.25 | 557.00 |
F6 SW APARTMENT | 6029.50 | 1600.25 | 475.25 |
F6 NW APARTMENT | 4293.00 | 3611.25 | 593.50 |
F6 SE APARTMENT | 5878.75 | 1715.50 | 470.75 |
F6 NE APARTMENT | 4031.25 | 4063.50 | 652.00 |
F6 N1 APARTMENT | 3954.00 | 4081.75 | 826.25 |
F6 N2 APARTMENT | 3918.25 | 4148.00 | 831.00 |
F6 S1 APARTMENT | 6167.75 | 1454.25 | 596.75 |
F6 S2 APARTMENT | 6159.00 | 1463.00 | 598.00 |
F7 SW APARTMENT | 5844.50 | 1780.50 | 498.25 |
F7 NW APARTMENT | 4103.00 | 3889.25 | 620.25 |
F7 SE APARTMENT | 5692.00 | 1891.25 | 494.75 |
F7 NE APARTMENT | 3824.50 | 4359.75 | 678.25 |
F7 N1 APARTMENT | 3728.25 | 4427.25 | 869.00 |
F7 N2 APARTMENT | 3685.50 | 4487.00 | 873.50 |
F7 S1 APARTMENT | 5989.00 | 1641.25 | 620.75 |
F7 S2 APARTMENT | 5974.50 | 1655.00 | 621.00 |
F8 SW APARTMENT | 5683.25 | 1934.25 | 510.75 |
F8 NW APARTMENT | 3943.50 | 4142.75 | 634.75 |
F8 SE APARTMENT | 5518.75 | 2054.25 | 509.75 |
F8 NE APARTMENT | 3662.25 | 4623.75 | 702.00 |
F8 N1 APARTMENT | 3545.75 | 4716.50 | 888.25 |
F8 N2 APARTMENT | 3510.00 | 4780.00 | 895.25 |
F8 S1 APARTMENT | 5807.25 | 1811.75 | 636.75 |
F8 S2 APARTMENT | 5794.00 | 1821.50 | 636.25 |
F9 SW APARTMENT | 5377.75 | 2231.25 | 518.50 |
F9 NW APARTMENT | 3747.25 | 4447.00 | 639.50 |
F9 SE APARTMENT | 5250.50 | 2340.00 | 514.25 |
F9 NE APARTMENT | 3493.75 | 4930.50 | 708.75 |
F9 N1 APARTMENT | 3365.25 | 5056.75 | 891.50 |
F9 N2 APARTMENT | 3326.25 | 5112.00 | 896.25 |
F9 S1 APARTMENT | 5480.00 | 2099.25 | 641.00 |
F9 S2 APARTMENT | 5464.25 | 2114.00 | 643.75 |
T SW APARTMENT | 4636.25 | 3582.25 | 682.00 |
T NW APARTMENT | 3386.25 | 5229.50 | 835.25 |
T SE APARTMENT | 4494.50 | 3814.75 | 792.75 |
T NE APARTMENT | 3171.75 | 5721.75 | 969.50 |
T N1 APARTMENT | 3079.25 | 5839.00 | 1085.25 |
T N2 APARTMENT | 3049.75 | 5889.75 | 1095.00 |
T S1 APARTMENT | 4740.25 | 3475.25 | 798.75 |
T S2 APARTMENT | 4725.00 | 3497.50 | 804.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6936.25 | 7547.75 | 1560.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.25 | 11.00 | 1.25 | 11.00 |
G NW APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
OFFICE | 0.75 | 13.50 | 0.00 | 13.50 |
G NE APARTMENT | 6.50 | 5.75 | 6.50 | 5.75 |
G N1 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
G N2 APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
G S1 APARTMENT | 0.00 | 39.00 | 0.00 | 39.00 |
G S2 APARTMENT | 0.00 | 35.25 | 0.00 | 35.25 |
F2 SW APARTMENT | 0.00 | 25.50 | 0.00 | 25.50 |
F2 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F2 SE APARTMENT | 0.00 | 43.50 | 0.00 | 43.50 |
F2 NE APARTMENT | 0.25 | 5.25 | 0.25 | 5.25 |
F2 N1 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F2 N2 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F2 S1 APARTMENT | 0.00 | 93.00 | 0.00 | 93.00 |
F2 S2 APARTMENT | 0.00 | 91.25 | 0.00 | 91.25 |
F3 SW APARTMENT | 0.00 | 30.75 | 0.00 | 30.75 |
F3 NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F3 SE APARTMENT | 0.00 | 74.50 | 0.00 | 74.50 |
F3 NE APARTMENT | 0.50 | 7.75 | 0.50 | 7.75 |
F3 N1 APARTMENT | 0.00 | 1.50 | 0.00 | 1.50 |
F3 N2 APARTMENT | 0.00 | 1.75 | 0.00 | 1.75 |
F3 S1 APARTMENT | 0.00 | 121.25 | 0.00 | 121.25 |
F3 S2 APARTMENT | 0.00 | 120.25 | 0.00 | 120.25 |
F4 SW APARTMENT | 0.00 | 31.50 | 0.00 | 31.50 |
F4 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F4 SE APARTMENT | 0.00 | 75.00 | 0.00 | 75.00 |
F4 NE APARTMENT | 0.50 | 8.50 | 0.50 | 8.50 |
F4 N1 APARTMENT | 0.00 | 2.00 | 0.00 | 2.00 |
F4 N2 APARTMENT | 0.00 | 2.00 | 0.00 | 2.00 |
F4 S1 APARTMENT | 0.00 | 125.00 | 0.00 | 125.00 |
F4 S2 APARTMENT | 0.00 | 125.00 | 0.00 | 125.00 |
M SW APARTMENT | 0.00 | 31.25 | 0.00 | 31.25 |
M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 0.00 | 74.25 | 0.00 | 74.25 |
M NE APARTMENT | 0.25 | 8.75 | 0.25 | 8.75 |
M N1 APARTMENT | 0.00 | 1.75 | 0.00 | 1.75 |
M N2 APARTMENT | 0.00 | 2.25 | 0.00 | 2.25 |
M S1 APARTMENT | 0.00 | 124.50 | 0.00 | 124.50 |
M S2 APARTMENT | 0.00 | 123.50 | 0.00 | 123.50 |
F6 SW APARTMENT | 0.00 | 32.75 | 0.00 | 32.75 |
F6 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F6 SE APARTMENT | 0.00 | 72.75 | 0.00 | 72.75 |
F6 NE APARTMENT | 0.50 | 10.00 | 0.50 | 10.00 |
F6 N1 APARTMENT | 0.00 | 2.25 | 0.00 | 2.25 |
F6 N2 APARTMENT | 0.00 | 4.00 | 0.00 | 4.00 |
F6 S1 APARTMENT | 0.00 | 121.25 | 0.00 | 121.25 |
F6 S2 APARTMENT | 0.00 | 120.50 | 0.00 | 120.50 |
F7 SW APARTMENT | 0.00 | 32.75 | 0.00 | 32.75 |
F7 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F7 SE APARTMENT | 0.25 | 70.50 | 0.25 | 70.50 |
F7 NE APARTMENT | 0.50 | 10.25 | 0.50 | 10.25 |
F7 N1 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
F7 N2 APARTMENT | 0.00 | 4.00 | 0.00 | 4.00 |
F7 S1 APARTMENT | 0.00 | 116.75 | 0.00 | 116.75 |
F7 S2 APARTMENT | 0.00 | 117.25 | 0.00 | 117.25 |
F8 SW APARTMENT | 0.00 | 32.00 | 0.00 | 32.00 |
F8 NW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F8 SE APARTMENT | 0.00 | 66.75 | 0.00 | 66.75 |
F8 NE APARTMENT | 0.00 | 10.25 | 0.00 | 10.25 |
F8 N1 APARTMENT | 0.00 | 2.25 | 0.00 | 2.25 |
F8 N2 APARTMENT | 0.00 | 3.75 | 0.00 | 3.75 |
F8 S1 APARTMENT | 0.00 | 109.75 | 0.00 | 109.75 |
F8 S2 APARTMENT | 0.00 | 109.25 | 0.00 | 109.25 |
F9 SW APARTMENT | 0.00 | 25.75 | 0.00 | 25.75 |
F9 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SE APARTMENT | 0.00 | 54.25 | 0.00 | 54.25 |
F9 NE APARTMENT | 0.75 | 8.75 | 0.75 | 8.75 |
F9 N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F9 S1 APARTMENT | 0.00 | 88.75 | 0.00 | 88.75 |
F9 S2 APARTMENT | 0.00 | 88.25 | 0.00 | 88.25 |
T SW APARTMENT | 0.00 | 25.25 | 0.00 | 25.25 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.00 | 54.50 | 0.00 | 54.50 |
T NE APARTMENT | 0.00 | 18.25 | 0.00 | 18.25 |
T N1 APARTMENT | 3.00 | 6.25 | 3.00 | 6.25 |
T N2 APARTMENT | 3.00 | 8.75 | 3.00 | 8.75 |
T S1 APARTMENT | 0.75 | 72.25 | 0.75 | 72.25 |
T S2 APARTMENT | 0.50 | 73.25 | 0.50 | 73.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 25.00 | 153.25 | 24.50 | 153.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.064 | 0.000 | 0.647 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.064 | 0.000 | 0.619 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.522 | 0.088 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.064 | 0.000 | 0.617 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.038 | 0.000 | 0.600 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.038 | 0.000 | 0.600 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.039 | 0.000 | 0.636 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.039 | 0.000 | 0.638 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.092 | 0.000 | 0.725 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.092 | 0.000 | 0.701 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.092 | 0.000 | 0.727 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.092 | 0.000 | 0.699 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.055 | 0.000 | 0.687 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.055 | 0.000 | 0.687 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.055 | 0.000 | 0.719 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.055 | 0.000 | 0.719 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.109 | 0.000 | 0.766 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.109 | 0.000 | 0.744 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.109 | 0.000 | 0.766 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.109 | 0.000 | 0.742 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.066 | 0.000 | 0.733 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.066 | 0.000 | 0.732 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.066 | 0.000 | 0.761 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.066 | 0.000 | 0.761 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.122 | 0.000 | 0.797 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.122 | 0.000 | 0.775 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.122 | 0.000 | 0.796 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.122 | 0.000 | 0.773 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.073 | 0.000 | 0.765 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.073 | 0.000 | 0.765 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.073 | 0.000 | 0.793 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.073 | 0.000 | 0.793 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.132 | 0.000 | 0.824 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.132 | 0.000 | 0.801 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.132 | 0.000 | 0.823 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.132 | 0.000 | 0.800 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.080 | 0.000 | 0.792 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.080 | 0.000 | 0.792 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.080 | 0.000 | 0.820 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.080 | 0.000 | 0.820 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.141 | 0.000 | 0.847 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.141 | 0.000 | 0.823 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.141 | 0.000 | 0.846 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.141 | 0.000 | 0.821 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.085 | 0.000 | 0.813 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.085 | 0.000 | 0.813 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.085 | 0.000 | 0.842 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.085 | 0.000 | 0.842 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.149 | 0.000 | 0.867 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.149 | 0.000 | 0.842 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.149 | 0.000 | 0.866 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.149 | 0.000 | 0.840 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.090 | 0.000 | 0.832 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.090 | 0.000 | 0.832 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.090 | 0.000 | 0.862 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.090 | 0.000 | 0.862 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.157 | 0.000 | 0.886 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.156 | 0.000 | 0.859 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.156 | 0.000 | 0.885 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.156 | 0.000 | 0.858 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.094 | 0.000 | 0.850 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.094 | 0.000 | 0.849 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.094 | 0.000 | 0.881 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.094 | 0.000 | 0.881 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.163 | 0.000 | 0.903 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.163 | 0.000 | 0.875 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.163 | 0.000 | 0.902 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.163 | 0.000 | 0.873 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.098 | 0.000 | 0.865 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.098 | 0.000 | 0.865 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.098 | 0.000 | 0.898 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.098 | 0.000 | 0.898 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.169 | 0.000 | 0.916 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.169 | 0.000 | 0.890 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.169 | 0.000 | 0.916 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.169 | 0.000 | 0.889 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.102 | 0.000 | 0.879 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.102 | 0.000 | 0.879 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.102 | 0.000 | 0.912 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.102 | 0.000 | 0.912 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.509 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 488.37 | 15486.08 | 11-JAN-12:30 | 15486.08 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 780.18 | 15866.60 | 26-JAN-03:15 | 69908.29 | 18-AUG-14:30 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
ElectricityPurchased:Plant | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
Cogeneration:ElectricityPurchased | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
ElectricityNet:Plant | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
Cogeneration:ElectricityNet | 2543.57 | 53427.09 | 26-JAN-03:15 | 154821.26 | 15-OCT-17:15 |
ExteriorLights:Electricity | 168.56 | 0.00 | 01-JAN-07:00 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.56 | 0.00 | 01-JAN-07:00 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 488.37 | 15486.08 | 11-JAN-12:30 | 15486.08 | 01-JAN-00:15 |
Cooling:Electricity | 267.70 | 0.00 | 01-JAN-00:15 | 53765.88 | 18-AUG-14:30 |
Heating:Electricity | 3.29 | 0.00 | 01-JAN-08:00 | 12640.71 | 12-FEB-08:45 |
Electricity:Plant | 47.31 | 36.93 | 14-JAN-19:30 | 3130.09 | 18-AUG-14:45 |
HeatRejection:Electricity | 11.58 | 0.00 | 01-JAN-00:15 | 1937.69 | 18-AUG-14:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 35.73 | 36.93 | 14-JAN-19:30 | 1192.40 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1046.46 | 9260.51 | 01-JAN-00:15 | 93614.76 | 30-MAR-06:15 |
Gas:Plant | 1046.46 | 9260.51 | 01-JAN-00:15 | 93614.76 | 30-MAR-06:15 |
WaterSystems:Gas | 1045.87 | 9260.51 | 01-JAN-00:15 | 82165.69 | 25-JAN-08:00 |
Water Heater:WaterSystems:Gas | 1045.87 | 9260.51 | 01-JAN-00:15 | 82165.69 | 25-JAN-08:00 |
Heating:Gas | 0.59 | 0.00 | 01-JAN-00:15 | 25727.19 | 30-MAR-04:00 |
Boiler:Heating:Gas | 0.59 | 0.00 | 01-JAN-00:15 | 25727.19 | 30-MAR-04:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 1087.37 | 0.00 | 01-JAN-00:15 | 253185.71 | 18-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 1087.37 | 0.00 | 01-JAN-00:15 | 253185.71 | 18-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 1087.37 | 0.00 | 01-JAN-00:15 | 253185.71 | 18-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5590.04 | 0.00 | 01-JAN-02:15 | 0.00 | 15-OCT-08:00 |
Water:Plant | 5590.04 | 0.00 | 01-JAN-02:15 | 0.00 | 15-OCT-08:00 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5590.04 | 0.00 | 01-JAN-02:15 | 0.00 | 15-OCT-08:00 |
MainsWater:Plant | 5590.04 | 0.00 | 01-JAN-02:15 | 0.00 | 15-OCT-08:00 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 811.52 | 0.00 | 01-JAN-00:15 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 811.52 | 0.00 | 01-JAN-00:15 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 803.01 | 467.03 | 04-AUG-01:15 | 85436.49 | 12-FEB-08:45 |
PlantLoopHeatingDemand:Plant | 793.92 | 467.03 | 04-AUG-01:15 | 50451.58 | 01-FEB-07:15 |
WaterSystems:PlantLoopHeatingDemand | 793.92 | 467.03 | 04-AUG-01:15 | 50451.58 | 01-FEB-07:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2518.96 | 4244.55 | 12-FEB-02:15 | 358454.33 | 29-SEP-16:15 |
EnergyTransfer:Building | 865.86 | 2278.32 | 07-MAY-15:45 | 151493.71 | 30-SEP-15:15 |
EnergyTransfer:Zone:G SW APARTMENT | 8.01 | 0.03 | 09-JUL-21:00 | 2289.94 | 31-OCT-13:30 |
Heating:EnergyTransfer | 25.41 | 0.00 | 01-JAN-07:30 | 55036.97 | 12-FEB-09:45 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 754.62 | 12-FEB-08:45 |
Cooling:EnergyTransfer | 840.45 | 0.00 | 12-FEB-08:45 | 151493.71 | 30-SEP-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.66 | 0.00 | 02-JAN-02:45 | 2289.94 | 31-OCT-13:30 |
EnergyTransfer:Zone:G NW APARTMENT | 5.48 | 0.03 | 05-SEP-19:30 | 1761.63 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.72 | 0.00 | 01-JAN-00:15 | 762.72 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.76 | 0.00 | 01-JAN-00:30 | 1761.63 | 29-SEP-15:30 |
EnergyTransfer:Zone:OFFICE | 17.50 | 0.08 | 06-DEC-01:45 | 2826.94 | 31-OCT-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.04 | 0.00 | 01-JAN-00:15 | 334.20 | 30-MAR-05:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 17.45 | 0.00 | 01-JAN-00:30 | 2826.94 | 31-OCT-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 5.44 | 0.01 | 21-SEP-09:00 | 1404.49 | 30-SEP-08:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.56 | 0.00 | 01-JAN-00:15 | 799.09 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.88 | 0.00 | 01-JAN-00:30 | 1404.49 | 30-SEP-08:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 5.52 | 0.01 | 06-JAN-12:30 | 893.01 | 30-SEP-17:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.53 | 0.00 | 01-JAN-00:15 | 698.06 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 5.00 | 0.00 | 03-JAN-01:45 | 893.01 | 30-SEP-17:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 5.53 | 0.02 | 25-SEP-13:45 | 878.19 | 30-SEP-17:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.52 | 0.00 | 01-JAN-00:15 | 703.77 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.01 | 0.00 | 03-JAN-01:45 | 878.19 | 30-SEP-17:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.33 | 0.00 | 04-MAY-08:15 | 1504.98 | 30-OCT-12:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 648.15 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.27 | 0.00 | 13-JAN-16:30 | 1504.98 | 30-OCT-12:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.40 | 0.00 | 02-MAY-17:00 | 1560.64 | 30-OCT-12:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 637.07 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.34 | 0.00 | 13-JAN-16:30 | 1560.64 | 30-OCT-12:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 14.92 | 0.03 | 24-DEC-12:00 | 2937.99 | 31-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 453.33 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 14.54 | 0.00 | 03-JAN-11:15 | 2937.99 | 31-OCT-14:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 8.39 | 0.01 | 27-NOV-23:30 | 2185.76 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 0.54 | 0.00 | 01-JAN-00:15 | 505.86 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 7.85 | 0.00 | 03-JAN-02:30 | 2185.76 | 30-SEP-15:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 15.37 | 0.00 | 19-FEB-14:30 | 2690.50 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 481.27 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 15.12 | 0.00 | 03-JAN-11:15 | 2690.50 | 31-OCT-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 7.95 | 0.02 | 10-OCT-19:30 | 1771.70 | 30-SEP-08:30 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 577.47 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 7.71 | 0.00 | 03-JAN-01:45 | 1771.70 | 30-SEP-08:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 7.08 | 0.01 | 10-MAY-13:30 | 1213.24 | 30-SEP-17:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 446.64 | 11-JAN-14:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 6.99 | 0.00 | 03-JAN-12:15 | 1213.24 | 30-SEP-17:00 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 7.07 | 0.00 | 13-NOV-13:30 | 1206.06 | 30-SEP-17:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 444.14 | 11-JAN-14:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 6.98 | 0.00 | 03-JAN-12:30 | 1206.06 | 30-SEP-17:00 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 12.82 | 0.00 | 11-MAY-15:15 | 1960.62 | 31-OCT-14:15 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 274.26 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 12.78 | 0.00 | 14-JAN-08:00 | 1960.62 | 31-OCT-14:15 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 12.90 | 0.00 | 01-JUL-07:00 | 1981.61 | 31-OCT-14:15 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 270.95 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 12.86 | 0.00 | 14-JAN-08:00 | 1981.61 | 31-OCT-14:15 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 16.68 | 0.07 | 10-JAN-10:30 | 2953.08 | 31-OCT-14:45 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 480.46 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 16.33 | 0.00 | 03-JAN-11:15 | 2953.08 | 31-OCT-14:45 |
EnergyTransfer:Zone:F3 NW APARTMENT | 9.31 | 0.03 | 23-AUG-06:00 | 2213.31 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 578.41 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 8.84 | 0.00 | 03-JAN-11:15 | 2213.31 | 30-SEP-15:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 16.14 | 0.02 | 20-OCT-19:15 | 2537.89 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 475.22 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 15.97 | 0.00 | 03-JAN-16:00 | 2537.89 | 31-OCT-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 8.83 | 0.00 | 13-JUN-19:00 | 1812.31 | 30-SEP-08:30 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 611.39 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 8.63 | 0.00 | 03-JAN-04:00 | 1812.31 | 30-SEP-08:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 7.90 | 0.02 | 03-JUN-14:15 | 1246.35 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 478.05 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.85 | 0.00 | 03-JAN-12:45 | 1246.35 | 14-OCT-17:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 7.88 | 0.00 | 27-MAY-13:15 | 1238.89 | 30-SEP-17:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 484.64 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.83 | 0.00 | 03-JAN-12:45 | 1238.89 | 30-SEP-17:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 14.96 | 0.01 | 11-FEB-13:30 | 2033.76 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 463.44 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 14.93 | 0.00 | 15-JAN-07:45 | 2033.76 | 03-DEC-12:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 14.96 | 0.03 | 14-APR-15:15 | 2043.00 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 446.73 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 14.93 | 0.00 | 15-JAN-07:45 | 2043.00 | 03-DEC-12:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 16.74 | 0.01 | 14-FEB-01:45 | 2949.22 | 31-OCT-14:45 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 485.31 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 16.38 | 0.00 | 03-JAN-11:15 | 2949.22 | 31-OCT-14:45 |
EnergyTransfer:Zone:F4 NW APARTMENT | 9.41 | 0.03 | 23-APR-09:30 | 2223.14 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 555.89 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 8.93 | 0.00 | 03-JAN-11:15 | 2223.14 | 30-SEP-15:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 16.10 | 0.00 | 17-FEB-16:15 | 2562.12 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 504.07 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 15.92 | 0.00 | 03-JAN-16:00 | 2562.12 | 31-OCT-13:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 8.96 | 0.01 | 16-JUL-19:30 | 1930.14 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 594.56 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 8.76 | 0.00 | 03-JAN-11:15 | 1930.14 | 30-SEP-08:45 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 8.11 | 0.01 | 21-MAY-10:15 | 1296.15 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 464.54 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 8.06 | 0.00 | 03-JAN-12:45 | 1296.15 | 14-OCT-17:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 8.09 | 0.01 | 13-MAY-12:30 | 1286.81 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 482.49 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 8.04 | 0.00 | 03-JAN-12:45 | 1286.81 | 14-OCT-17:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 15.29 | 0.00 | 24-MAY-08:45 | 2047.06 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 365.97 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 15.26 | 0.00 | 15-JAN-07:45 | 2047.06 | 03-DEC-12:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 15.27 | 0.01 | 06-JUN-10:00 | 2054.96 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 371.62 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 15.24 | 0.00 | 15-JAN-07:45 | 2054.96 | 03-DEC-12:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 16.87 | 0.11 | 12-FEB-15:30 | 2970.43 | 31-OCT-13:45 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 541.32 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 16.49 | 0.00 | 03-JAN-11:15 | 2970.43 | 31-OCT-13:45 |
EnergyTransfer:Zone:M NW APARTMENT | 9.57 | 0.00 | 28-MAY-12:45 | 2252.91 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 587.74 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 9.07 | 0.00 | 03-JAN-11:15 | 2252.91 | 30-SEP-15:30 |
EnergyTransfer:Zone:M SE APARTMENT | 16.24 | 0.00 | 18-OCT-20:00 | 2587.93 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 568.89 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 16.05 | 0.00 | 03-JAN-15:45 | 2587.93 | 31-OCT-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 9.13 | 0.00 | 03-AUG-20:45 | 1962.85 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 633.40 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 8.92 | 0.00 | 03-JAN-11:15 | 1962.85 | 30-SEP-08:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 8.32 | 0.02 | 06-FEB-14:15 | 1340.52 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 478.13 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 8.27 | 0.00 | 03-JAN-12:45 | 1340.52 | 14-OCT-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 8.30 | 0.00 | 09-NOV-10:45 | 1331.29 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 494.41 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 8.24 | 0.00 | 03-JAN-12:45 | 1331.29 | 14-OCT-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 15.60 | 0.01 | 19-APR-15:45 | 2076.00 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 512.91 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 15.56 | 0.00 | 14-JAN-08:00 | 2076.00 | 03-DEC-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 15.57 | 0.01 | 16-MAY-11:00 | 2083.57 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 517.20 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 15.53 | 0.00 | 14-JAN-08:00 | 2083.57 | 03-DEC-12:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 15.61 | 0.02 | 15-NOV-15:00 | 2926.94 | 30-OCT-14:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 745.89 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 15.21 | 0.00 | 03-JAN-11:15 | 2926.94 | 30-OCT-14:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 8.79 | 0.03 | 05-JUL-21:00 | 2213.68 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 0.55 | 0.00 | 01-JAN-00:15 | 704.88 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 8.25 | 0.00 | 03-JAN-11:15 | 2213.68 | 30-SEP-15:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 15.05 | 0.00 | 25-APR-20:00 | 2542.82 | 30-OCT-12:45 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 783.79 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 14.84 | 0.00 | 03-JAN-14:00 | 2542.82 | 30-OCT-12:45 |
EnergyTransfer:Zone:F6 NE APARTMENT | 8.46 | 0.00 | 02-AUG-20:15 | 1926.84 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 768.85 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 8.21 | 0.00 | 03-JAN-03:45 | 1926.84 | 30-SEP-08:45 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 7.75 | 0.02 | 13-NOV-13:30 | 1311.25 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 589.58 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.67 | 0.00 | 03-JAN-12:45 | 1311.25 | 14-OCT-17:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 7.73 | 0.02 | 10-MAY-12:15 | 1302.04 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 601.45 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.65 | 0.00 | 03-JAN-12:45 | 1302.04 | 14-OCT-17:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 14.48 | 0.00 | 13-MAR-15:45 | 2031.29 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 759.08 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 14.43 | 0.00 | 14-JAN-08:00 | 2031.29 | 03-DEC-12:45 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 14.46 | 0.01 | 29-MAY-16:45 | 2038.83 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 764.17 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 14.40 | 0.00 | 14-JAN-08:00 | 2038.83 | 03-DEC-12:45 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 14.82 | 0.05 | 02-FEB-10:00 | 2905.53 | 30-OCT-14:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.44 | 0.00 | 01-JAN-00:15 | 969.86 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 14.38 | 0.00 | 03-JAN-11:15 | 2905.53 | 30-OCT-14:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 8.34 | 0.07 | 24-OCT-00:45 | 2198.38 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 0.60 | 0.00 | 01-JAN-00:15 | 822.97 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 7.74 | 0.00 | 03-JAN-03:30 | 2198.38 | 30-SEP-15:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 14.31 | 0.00 | 28-APR-09:30 | 2526.69 | 30-OCT-12:45 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 1010.27 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 14.06 | 0.00 | 03-JAN-14:00 | 2526.69 | 30-OCT-12:45 |
EnergyTransfer:Zone:F7 NE APARTMENT | 8.08 | 0.01 | 08-OCT-19:30 | 1913.43 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 925.76 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 7.78 | 0.00 | 03-JAN-02:00 | 1913.43 | 30-SEP-08:45 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 7.42 | 0.01 | 12-JUN-15:00 | 1298.63 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 694.28 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 7.31 | 0.00 | 03-JAN-12:30 | 1298.63 | 14-OCT-17:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 7.41 | 0.00 | 23-JAN-15:30 | 1289.41 | 14-OCT-17:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 704.61 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 7.29 | 0.00 | 03-JAN-12:45 | 1289.41 | 14-OCT-17:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 13.79 | 0.01 | 10-NOV-15:30 | 2011.81 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 969.39 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 13.73 | 0.00 | 14-JAN-08:00 | 2011.81 | 03-DEC-12:45 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 13.76 | 0.01 | 06-OCT-18:00 | 2019.42 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 975.33 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 13.70 | 0.00 | 14-JAN-08:00 | 2019.42 | 03-DEC-12:45 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 14.17 | 0.03 | 11-JAN-14:00 | 2898.08 | 30-OCT-14:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1168.35 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 13.69 | 0.00 | 03-JAN-11:15 | 2898.08 | 30-OCT-14:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 8.03 | 0.12 | 25-APR-11:15 | 2194.13 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 0.67 | 0.00 | 01-JAN-00:15 | 962.58 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 7.36 | 0.00 | 03-JAN-02:00 | 2194.13 | 30-SEP-15:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 13.70 | 0.00 | 21-JUN-20:45 | 2522.92 | 30-OCT-12:45 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1210.02 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 13.42 | 0.00 | 03-JAN-11:15 | 2522.92 | 30-OCT-12:45 |
EnergyTransfer:Zone:F8 NE APARTMENT | 7.81 | 0.00 | 07-OCT-17:45 | 1911.01 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1092.53 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 7.45 | 0.00 | 03-JAN-01:45 | 1911.01 | 30-SEP-08:45 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 7.20 | 0.00 | 07-JUN-14:30 | 1295.83 | 30-SEP-16:45 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.16 | 0.00 | 01-JAN-00:15 | 797.28 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 7.04 | 0.00 | 03-JAN-12:15 | 1295.83 | 30-SEP-16:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 7.19 | 0.00 | 05-APR-12:45 | 1283.45 | 30-SEP-16:45 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.16 | 0.00 | 01-JAN-00:15 | 806.76 | 12-FEB-09:45 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 7.03 | 0.00 | 03-JAN-12:15 | 1283.45 | 30-SEP-16:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 13.23 | 0.01 | 03-JUL-18:45 | 2003.69 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1155.30 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 13.14 | 0.00 | 14-JAN-08:00 | 2003.69 | 03-DEC-12:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 13.20 | 0.01 | 01-AUG-09:15 | 2011.26 | 03-DEC-12:45 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1161.70 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 13.12 | 0.00 | 14-JAN-08:00 | 2011.26 | 03-DEC-12:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 13.40 | 0.02 | 18-MAY-10:15 | 2960.95 | 30-OCT-14:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 0.58 | 0.00 | 01-JAN-00:15 | 1374.98 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 12.82 | 0.00 | 03-JAN-11:15 | 2960.95 | 30-OCT-14:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 7.81 | 0.01 | 16-DEC-23:00 | 2240.65 | 30-SEP-15:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 1154.65 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 6.96 | 0.00 | 02-JAN-02:15 | 2240.65 | 30-SEP-15:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 12.93 | 0.00 | 19-JAN-18:45 | 2568.08 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 1414.10 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 12.57 | 0.00 | 03-JAN-11:15 | 2568.08 | 31-OCT-13:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 7.58 | 0.00 | 18-SEP-11:00 | 1913.95 | 30-SEP-08:45 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 0.50 | 0.00 | 01-JAN-00:15 | 1270.41 | 12-FEB-08:45 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 7.08 | 0.00 | 02-JAN-02:45 | 1913.95 | 30-SEP-08:45 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 6.98 | 0.01 | 19-MAY-14:15 | 1359.68 | 30-SEP-16:45 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1005.56 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.70 | 0.00 | 03-JAN-11:30 | 1359.68 | 30-SEP-16:45 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 6.97 | 0.01 | 25-JAN-09:30 | 1347.30 | 30-SEP-16:45 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1018.43 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.69 | 0.00 | 03-JAN-12:00 | 1347.30 | 30-SEP-16:45 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 12.45 | 0.00 | 14-FEB-12:15 | 2008.46 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 1345.83 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 12.33 | 0.00 | 07-JAN-09:15 | 2008.46 | 31-OCT-13:30 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 12.42 | 0.02 | 08-AUG-18:30 | 2016.88 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 1351.97 | 12-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 12.30 | 0.00 | 07-JAN-09:15 | 2016.88 | 31-OCT-13:30 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 13.11 | 0.00 | 27-MAR-04:00 | 3558.10 | 30-OCT-14:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.25 | 0.00 | 01-JAN-00:15 | 1945.47 | 25-MAR-10:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 11.86 | 0.00 | 01-JAN-03:30 | 3558.10 | 30-OCT-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 8.22 | 0.03 | 10-JUN-22:30 | 2805.90 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 1.84 | 0.00 | 01-JAN-07:30 | 1524.52 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 6.38 | 0.00 | 01-JAN-00:15 | 2805.90 | 29-SEP-15:30 |
EnergyTransfer:Zone:T SE APARTMENT | 12.61 | 0.00 | 12-NOV-05:15 | 3102.43 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.98 | 0.00 | 01-JAN-00:15 | 1944.46 | 25-MAR-10:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.64 | 0.00 | 01-JAN-03:30 | 3102.43 | 31-OCT-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 7.91 | 0.00 | 28-JUL-18:15 | 2198.74 | 29-SEP-10:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 1.40 | 0.00 | 01-JAN-07:15 | 1590.83 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 6.51 | 0.00 | 01-JAN-00:15 | 2198.74 | 29-SEP-10:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 6.45 | 0.01 | 05-SEP-08:45 | 1669.81 | 29-SEP-13:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.61 | 0.00 | 01-JAN-00:15 | 1464.65 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 5.84 | 0.00 | 02-JAN-02:00 | 1669.81 | 29-SEP-13:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 6.44 | 0.00 | 02-AUG-19:00 | 1673.62 | 29-SEP-13:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.62 | 0.00 | 01-JAN-00:15 | 1471.90 | 24-FEB-14:45 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 5.82 | 0.00 | 02-JAN-02:00 | 1673.62 | 29-SEP-13:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 11.41 | 0.03 | 02-MAR-13:45 | 2615.76 | 30-OCT-12:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.50 | 0.00 | 01-JAN-00:15 | 1750.00 | 25-MAR-10:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.91 | 0.00 | 03-JAN-03:30 | 2615.76 | 30-OCT-12:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 11.41 | 0.00 | 03-MAR-14:30 | 2620.87 | 30-OCT-12:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 1753.22 | 25-MAR-10:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.90 | 0.00 | 03-JAN-03:30 | 2620.87 | 30-OCT-12:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 794.39 | 467.03 | 04-AUG-01:15 | 64859.86 | 30-MAR-05:15 |
WaterSystems:EnergyTransfer | 793.92 | 467.03 | 04-AUG-01:15 | 50446.42 | 01-FEB-07:15 |
sub cat:WaterSystems:EnergyTransfer | 793.92 | 467.03 | 04-AUG-01:15 | 50446.42 | 01-FEB-07:15 |
EnergyTransfer:HVAC | 858.71 | 0.00 | 14-JAN-19:30 | 199461.04 | 18-AUG-14:30 |
CoolingCoils:EnergyTransfer | 847.00 | 0.00 | 01-JAN-00:15 | 199461.04 | 18-AUG-14:30 |
HeatingCoils:EnergyTransfer | 11.71 | 0.00 | 01-JAN-08:00 | 48120.29 | 12-FEB-08:45 |
PlantLoopHeatingDemand:HVAC | 9.08 | 0.00 | 01-JAN-08:00 | 37173.69 | 12-FEB-08:45 |
HeatingCoils:PlantLoopHeatingDemand | 9.08 | 0.00 | 01-JAN-08:00 | 37173.69 | 12-FEB-08:45 |
Boilers:EnergyTransfer | 0.47 | 0.00 | 01-JAN-00:15 | 20581.75 | 30-MAR-04:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.358 | -7.656 | 0.000 | 0.000 | 3.712 | 2.413 | 12.213 | 20.664 | 0.000 | 0.056 | 0.000 | 0.000 | -7.779 | 0.000 | -9.813 | -14.168 |
G NW APARTMENT | 0.720 | -4.761 | 0.000 | 0.000 | 3.787 | 2.413 | 12.213 | 11.157 | 0.000 | 0.058 | 0.000 | 0.000 | -7.579 | 0.000 | -8.668 | -9.339 |
OFFICE | 0.043 | -17.454 | 0.000 | 0.000 | 0.504 | 21.954 | 7.547 | 19.725 | 0.000 | 0.017 | 0.000 | 0.000 | -7.765 | 0.000 | -1.247 | -23.326 |
G NE APARTMENT | 0.559 | -4.883 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 10.173 | 0.000 | 0.056 | 0.000 | 0.000 | -7.268 | 0.000 | -8.495 | -8.585 |
G N1 APARTMENT | 0.525 | -4.997 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 3.616 | 0.000 | 0.054 | 0.000 | 0.000 | -4.549 | 0.000 | -7.472 | -5.630 |
G N2 APARTMENT | 0.524 | -5.005 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 3.616 | 0.000 | 0.053 | 0.000 | 0.000 | -4.541 | 0.000 | -7.458 | -5.644 |
G S1 APARTMENT | 0.067 | -7.266 | 0.000 | 0.000 | 3.718 | 2.413 | 12.213 | 13.278 | 0.000 | 0.048 | 0.000 | 0.000 | -4.753 | 0.000 | -8.818 | -10.899 |
G S2 APARTMENT | 0.064 | -7.340 | 0.000 | 0.000 | 3.713 | 2.413 | 12.213 | 13.263 | 0.000 | 0.048 | 0.000 | 0.000 | -4.762 | 0.000 | -8.894 | -10.718 |
F2 SW APARTMENT | 0.376 | -14.544 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 19.590 | 0.000 | 0.069 | 0.001 | 0.000 | -8.634 | 0.000 | -12.193 | -2.868 |
F2 NW APARTMENT | 0.540 | -7.855 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 10.309 | 0.000 | 0.070 | 0.000 | 0.000 | -8.395 | 0.000 | -11.003 | -1.946 |
F2 SE APARTMENT | 0.248 | -15.118 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 18.785 | 0.000 | 0.068 | 0.000 | 0.000 | -8.564 | 0.000 | -12.286 | -1.335 |
F2 NE APARTMENT | 0.235 | -7.710 | 0.000 | 0.000 | 3.685 | 2.413 | 12.213 | 9.423 | 0.000 | 0.069 | 0.000 | 0.000 | -8.048 | 0.000 | -10.812 | -1.469 |
F2 N1 APARTMENT | 0.093 | -6.987 | 0.000 | 0.000 | 3.682 | 2.413 | 12.213 | 3.173 | 0.000 | 0.060 | 0.047 | 0.000 | -5.103 | 0.000 | -9.590 | -0.000 |
F2 N2 APARTMENT | 0.091 | -6.979 | 0.000 | 0.000 | 3.685 | 2.413 | 12.213 | 3.174 | 0.000 | 0.060 | 0.008 | 0.000 | -5.094 | 0.000 | -9.570 | -0.000 |
F2 S1 APARTMENT | 0.035 | -12.784 | 0.000 | 0.000 | 3.575 | 2.413 | 12.213 | 12.630 | 0.000 | 0.054 | 0.001 | 0.000 | -5.276 | 0.000 | -11.108 | -1.753 |
F2 S2 APARTMENT | 0.037 | -12.858 | 0.000 | 0.000 | 3.574 | 2.413 | 12.213 | 12.627 | 0.000 | 0.054 | 0.001 | 0.000 | -5.278 | 0.000 | -11.124 | -1.658 |
F3 SW APARTMENT | 0.342 | -16.335 | 0.000 | 0.000 | 3.561 | 2.413 | 12.213 | 19.132 | 0.000 | 0.077 | 0.550 | 0.000 | -8.822 | 0.000 | -13.130 | -0.000 |
F3 NW APARTMENT | 0.475 | -8.835 | 0.000 | 0.000 | 3.625 | 2.413 | 12.213 | 9.951 | 0.000 | 0.078 | 0.736 | 0.000 | -8.639 | 0.000 | -12.017 | -0.000 |
F3 SE APARTMENT | 0.172 | -15.970 | 0.000 | 0.000 | 3.568 | 2.413 | 12.213 | 18.429 | 0.000 | 0.073 | 0.894 | 0.000 | -8.704 | 0.000 | -13.088 | -0.000 |
F3 NE APARTMENT | 0.192 | -8.635 | 0.000 | 0.000 | 3.651 | 2.413 | 12.213 | 9.127 | 0.000 | 0.077 | 1.081 | 0.000 | -8.293 | 0.000 | -11.827 | -0.000 |
F3 N1 APARTMENT | 0.054 | -7.847 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 3.006 | 0.000 | 0.066 | 2.295 | 0.000 | -5.287 | 0.000 | -10.551 | -0.000 |
F3 N2 APARTMENT | 0.053 | -7.830 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 3.007 | 0.000 | 0.065 | 2.246 | 0.000 | -5.278 | 0.000 | -10.531 | -0.000 |
F3 S1 APARTMENT | 0.028 | -14.933 | 0.000 | 0.000 | 3.556 | 2.413 | 12.213 | 12.356 | 0.000 | 0.057 | 1.683 | 0.000 | -5.406 | 0.000 | -11.968 | -0.000 |
F3 S2 APARTMENT | 0.029 | -14.932 | 0.000 | 0.000 | 3.556 | 2.413 | 12.213 | 12.355 | 0.000 | 0.057 | 1.682 | 0.000 | -5.404 | 0.000 | -11.968 | -0.000 |
F4 SW APARTMENT | 0.352 | -16.384 | 0.000 | 0.000 | 3.559 | 2.413 | 12.213 | 18.843 | 0.000 | 0.083 | 1.567 | 0.000 | -8.893 | 0.000 | -13.754 | -0.000 |
F4 NW APARTMENT | 0.479 | -8.931 | 0.000 | 0.000 | 3.619 | 2.413 | 12.213 | 9.743 | 0.000 | 0.084 | 1.755 | 0.000 | -8.733 | 0.000 | -12.642 | -0.000 |
F4 SE APARTMENT | 0.177 | -15.924 | 0.000 | 0.000 | 3.568 | 2.413 | 12.213 | 18.197 | 0.000 | 0.078 | 1.727 | 0.000 | -8.765 | 0.000 | -13.685 | -0.000 |
F4 NE APARTMENT | 0.194 | -8.765 | 0.000 | 0.000 | 3.644 | 2.413 | 12.213 | 8.966 | 0.000 | 0.083 | 2.092 | 0.000 | -8.389 | 0.000 | -12.450 | -0.000 |
F4 N1 APARTMENT | 0.052 | -8.062 | 0.000 | 0.000 | 3.627 | 2.413 | 12.213 | 2.919 | 0.000 | 0.070 | 3.242 | 0.000 | -5.364 | 0.000 | -11.110 | -0.000 |
F4 N2 APARTMENT | 0.050 | -8.041 | 0.000 | 0.000 | 3.629 | 2.413 | 12.213 | 2.920 | 0.000 | 0.070 | 3.192 | 0.000 | -5.355 | 0.000 | -11.090 | -0.000 |
F4 S1 APARTMENT | 0.031 | -15.258 | 0.000 | 0.000 | 3.554 | 2.413 | 12.213 | 12.187 | 0.000 | 0.061 | 2.751 | 0.000 | -5.455 | 0.000 | -12.496 | -0.000 |
F4 S2 APARTMENT | 0.033 | -15.236 | 0.000 | 0.000 | 3.554 | 2.413 | 12.213 | 12.186 | 0.000 | 0.061 | 2.722 | 0.000 | -5.453 | 0.000 | -12.494 | -0.001 |
M SW APARTMENT | 0.373 | -16.493 | 0.000 | 0.000 | 3.559 | 2.413 | 12.213 | 18.611 | 0.000 | 0.087 | 2.486 | 0.000 | -8.953 | 0.000 | -14.296 | -0.001 |
M NW APARTMENT | 0.506 | -9.068 | 0.000 | 0.000 | 3.616 | 2.413 | 12.213 | 9.582 | 0.000 | 0.088 | 2.619 | 0.000 | -8.800 | 0.000 | -13.169 | 0.000 |
M SE APARTMENT | 0.197 | -16.045 | 0.000 | 0.000 | 3.567 | 2.413 | 12.213 | 18.007 | 0.000 | 0.082 | 2.607 | 0.000 | -8.823 | 0.000 | -14.218 | -0.000 |
M NE APARTMENT | 0.214 | -8.919 | 0.000 | 0.000 | 3.640 | 2.413 | 12.213 | 8.844 | 0.000 | 0.087 | 2.939 | 0.000 | -8.456 | 0.000 | -12.973 | -0.000 |
M N1 APARTMENT | 0.057 | -8.267 | 0.000 | 0.000 | 3.620 | 2.413 | 12.213 | 2.853 | 0.000 | 0.073 | 4.026 | 0.000 | -5.416 | 0.000 | -11.574 | 0.000 |
M N2 APARTMENT | 0.055 | -8.243 | 0.000 | 0.000 | 3.623 | 2.413 | 12.213 | 2.854 | 0.000 | 0.073 | 3.974 | 0.000 | -5.407 | 0.000 | -11.554 | 0.000 |
M S1 APARTMENT | 0.040 | -15.559 | 0.000 | 0.000 | 3.553 | 2.413 | 12.213 | 12.052 | 0.000 | 0.064 | 3.677 | 0.000 | -5.496 | 0.000 | -12.956 | -0.000 |
M S2 APARTMENT | 0.041 | -15.531 | 0.000 | 0.000 | 3.553 | 2.413 | 12.213 | 12.052 | 0.000 | 0.064 | 3.641 | 0.000 | -5.494 | 0.000 | -12.952 | -0.000 |
F6 SW APARTMENT | 0.401 | -15.210 | 0.000 | 0.000 | 3.567 | 2.413 | 12.213 | 18.463 | 0.000 | 0.096 | 1.639 | 0.000 | -8.939 | 0.000 | -14.644 | -0.000 |
F6 NW APARTMENT | 0.548 | -8.246 | 0.000 | 0.000 | 3.631 | 2.413 | 12.213 | 9.506 | 0.000 | 0.098 | 2.008 | 0.000 | -8.759 | 0.000 | -13.412 | 0.000 |
F6 SE APARTMENT | 0.217 | -14.837 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 17.893 | 0.000 | 0.091 | 1.791 | 0.000 | -8.804 | 0.000 | -14.553 | -0.000 |
F6 NE APARTMENT | 0.250 | -8.214 | 0.000 | 0.000 | 3.657 | 2.413 | 12.213 | 8.803 | 0.000 | 0.096 | 2.392 | 0.000 | -8.410 | 0.000 | -13.200 | -0.000 |
F6 N1 APARTMENT | 0.079 | -7.669 | 0.000 | 0.000 | 3.637 | 2.413 | 12.213 | 2.836 | 0.000 | 0.081 | 3.519 | 0.000 | -5.388 | 0.000 | -11.720 | 0.000 |
F6 N2 APARTMENT | 0.078 | -7.653 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 2.837 | 0.000 | 0.081 | 3.471 | 0.000 | -5.380 | 0.000 | -11.700 | 0.000 |
F6 S1 APARTMENT | 0.051 | -14.431 | 0.000 | 0.000 | 3.560 | 2.413 | 12.213 | 11.967 | 0.000 | 0.071 | 2.852 | 0.000 | -5.490 | 0.000 | -13.206 | -0.000 |
F6 S2 APARTMENT | 0.053 | -14.403 | 0.000 | 0.000 | 3.561 | 2.413 | 12.213 | 11.967 | 0.000 | 0.071 | 2.815 | 0.000 | -5.487 | 0.000 | -13.202 | -0.000 |
F7 SW APARTMENT | 0.436 | -14.380 | 0.000 | 0.000 | 3.574 | 2.413 | 12.213 | 18.328 | 0.000 | 0.099 | 1.233 | 0.000 | -8.937 | 0.000 | -14.978 | -0.000 |
F7 NW APARTMENT | 0.601 | -7.738 | 0.000 | 0.000 | 3.644 | 2.413 | 12.213 | 9.435 | 0.000 | 0.101 | 1.720 | 0.000 | -8.731 | 0.000 | -13.658 | 0.000 |
F7 SE APARTMENT | 0.244 | -14.062 | 0.000 | 0.000 | 3.584 | 2.413 | 12.213 | 17.787 | 0.000 | 0.094 | 1.404 | 0.000 | -8.799 | 0.000 | -14.877 | -0.000 |
F7 NE APARTMENT | 0.300 | -7.779 | 0.000 | 0.000 | 3.671 | 2.413 | 12.213 | 8.763 | 0.000 | 0.099 | 2.130 | 0.000 | -8.377 | 0.000 | -13.433 | -0.000 |
F7 N1 APARTMENT | 0.114 | -7.307 | 0.000 | 0.000 | 3.650 | 2.413 | 12.213 | 2.819 | 0.000 | 0.084 | 3.269 | 0.000 | -5.368 | 0.000 | -11.885 | 0.000 |
F7 N2 APARTMENT | 0.113 | -7.294 | 0.000 | 0.000 | 3.653 | 2.413 | 12.213 | 2.820 | 0.000 | 0.083 | 3.222 | 0.000 | -5.359 | 0.000 | -11.864 | 0.000 |
F7 S1 APARTMENT | 0.065 | -13.726 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 11.889 | 0.000 | 0.074 | 2.456 | 0.000 | -5.491 | 0.000 | -13.459 | -0.000 |
F7 S2 APARTMENT | 0.067 | -13.698 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 11.889 | 0.000 | 0.074 | 2.419 | 0.000 | -5.488 | 0.000 | -13.454 | -0.000 |
F8 SW APARTMENT | 0.477 | -13.691 | 0.000 | 0.000 | 3.580 | 2.413 | 12.213 | 18.209 | 0.000 | 0.102 | 0.922 | 0.000 | -8.935 | 0.000 | -15.290 | -0.000 |
F8 NW APARTMENT | 0.673 | -7.355 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 9.373 | 0.000 | 0.104 | 1.520 | 0.000 | -8.705 | 0.000 | -13.892 | 0.000 |
F8 SE APARTMENT | 0.279 | -13.422 | 0.000 | 0.000 | 3.591 | 2.413 | 12.213 | 17.694 | 0.000 | 0.097 | 1.109 | 0.000 | -8.795 | 0.000 | -15.180 | -0.000 |
F8 NE APARTMENT | 0.368 | -7.446 | 0.000 | 0.000 | 3.684 | 2.413 | 12.213 | 8.729 | 0.000 | 0.101 | 1.941 | 0.000 | -8.348 | 0.000 | -13.655 | -0.000 |
F8 N1 APARTMENT | 0.165 | -7.037 | 0.000 | 0.000 | 3.663 | 2.413 | 12.213 | 2.803 | 0.000 | 0.086 | 3.094 | 0.000 | -5.349 | 0.000 | -12.050 | -0.000 |
F8 N2 APARTMENT | 0.165 | -7.026 | 0.000 | 0.000 | 3.666 | 2.413 | 12.213 | 2.804 | 0.000 | 0.085 | 3.046 | 0.000 | -5.339 | 0.000 | -12.028 | 0.000 |
F8 S1 APARTMENT | 0.082 | -13.144 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 11.821 | 0.000 | 0.076 | 2.160 | 0.000 | -5.492 | 0.000 | -13.701 | -0.000 |
F8 S2 APARTMENT | 0.085 | -13.116 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 11.821 | 0.000 | 0.076 | 2.121 | 0.000 | -5.489 | 0.000 | -13.696 | -0.000 |
F9 SW APARTMENT | 0.580 | -12.824 | 0.000 | 0.000 | 3.591 | 2.413 | 12.213 | 18.131 | 0.000 | 0.105 | 0.226 | 0.000 | -8.908 | 0.000 | -15.526 | -0.001 |
F9 NW APARTMENT | 0.847 | -6.961 | 0.000 | 0.000 | 3.669 | 2.413 | 12.213 | 9.341 | 0.000 | 0.106 | 1.086 | 0.000 | -8.661 | 0.000 | -14.054 | -0.000 |
F9 SE APARTMENT | 0.356 | -12.575 | 0.000 | 0.000 | 3.603 | 2.413 | 12.213 | 17.638 | 0.000 | 0.101 | 0.434 | 0.000 | -8.765 | 0.000 | -15.418 | -0.000 |
F9 NE APARTMENT | 0.496 | -7.083 | 0.000 | 0.000 | 3.700 | 2.413 | 12.213 | 8.722 | 0.000 | 0.104 | 1.548 | 0.000 | -8.302 | 0.000 | -13.811 | -0.000 |
F9 N1 APARTMENT | 0.283 | -6.701 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 2.803 | 0.000 | 0.088 | 2.700 | 0.000 | -5.316 | 0.000 | -12.161 | -0.000 |
F9 N2 APARTMENT | 0.282 | -6.690 | 0.000 | 0.000 | 3.682 | 2.413 | 12.213 | 2.804 | 0.000 | 0.088 | 2.654 | 0.000 | -5.306 | 0.000 | -12.138 | -0.000 |
F9 S1 APARTMENT | 0.122 | -12.328 | 0.000 | 0.000 | 3.581 | 2.413 | 12.213 | 11.776 | 0.000 | 0.079 | 1.505 | 0.000 | -5.480 | 0.000 | -13.881 | -0.000 |
F9 S2 APARTMENT | 0.124 | -12.298 | 0.000 | 0.000 | 3.582 | 2.413 | 12.213 | 11.775 | 0.000 | 0.079 | 1.465 | 0.000 | -5.476 | 0.000 | -13.877 | -0.000 |
T SW APARTMENT | 1.248 | -11.863 | 0.000 | 0.000 | 3.663 | 2.413 | 12.213 | 17.863 | 0.000 | 0.107 | 0.000 | 0.000 | -8.382 | 0.000 | -15.552 | -1.709 |
T NW APARTMENT | 1.839 | -6.381 | 0.000 | 0.000 | 3.727 | 2.413 | 12.213 | 9.118 | 0.000 | 0.108 | 0.000 | 0.000 | -8.188 | 0.000 | -14.200 | -0.649 |
T SE APARTMENT | 0.979 | -11.636 | 0.000 | 0.000 | 3.680 | 2.413 | 12.213 | 17.409 | 0.000 | 0.102 | 0.000 | 0.000 | -8.254 | 0.000 | -15.459 | -1.446 |
T NE APARTMENT | 1.397 | -6.514 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 8.552 | 0.000 | 0.104 | 0.000 | 0.000 | -7.858 | 0.000 | -13.965 | -0.106 |
T N1 APARTMENT | 0.611 | -5.843 | 0.000 | 0.000 | 3.741 | 2.413 | 12.213 | 2.745 | 0.000 | 0.088 | 1.287 | 0.000 | -5.015 | 0.000 | -12.239 | -0.000 |
T N2 APARTMENT | 0.618 | -5.822 | 0.000 | 0.000 | 3.744 | 2.413 | 12.213 | 2.742 | 0.000 | 0.088 | 1.234 | 0.000 | -5.002 | 0.000 | -12.228 | -0.000 |
T S1 APARTMENT | 0.505 | -10.909 | 0.000 | 0.000 | 3.646 | 2.413 | 12.213 | 11.643 | 0.000 | 0.082 | 0.001 | 0.000 | -5.217 | 0.000 | -13.928 | -0.448 |
T S2 APARTMENT | 0.511 | -10.897 | 0.000 | 0.000 | 3.647 | 2.413 | 12.213 | 11.641 | 0.000 | 0.082 | 0.000 | 0.000 | -5.211 | 0.000 | -13.924 | -0.473 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 4.534 | 0.000 | 0.205 | 3.474 | 0.000 | -1.854 | 0.000 | -24.889 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.095 | 0.000 | 0.002 | 0.000 | 0.000 | -1.114 | 0.000 | -0.375 | -19.137 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.023 | 0.000 | 0.002 | 0.000 | 0.000 | -1.162 | 0.000 | -0.466 | -18.927 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.981 | 0.000 | 0.003 | 0.000 | 0.000 | -1.185 | 0.000 | -0.531 | -18.797 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.936 | 0.000 | 0.002 | 0.000 | 0.000 | -1.217 | 0.000 | -0.616 | -37.164 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.941 | 0.000 | 0.003 | 0.000 | 0.000 | -1.191 | 0.000 | -0.615 | -18.667 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.935 | 0.000 | 0.003 | 0.000 | 0.000 | -1.181 | 0.000 | -0.641 | -18.646 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.925 | 0.000 | 0.003 | 0.000 | 0.000 | -1.178 | 0.000 | -0.667 | -18.613 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.920 | 0.000 | 0.004 | 0.000 | 0.000 | -1.175 | 0.000 | -0.689 | -18.589 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.862 | 0.000 | 0.002 | 0.000 | 0.000 | -1.138 | 0.000 | -0.758 | -26.434 |
Total Facility | 25.414 | -840.451 | 0.000 | 0.000 | 287.619 | 416.414 | 980.287 | 881.495 | 0.000 | 6.514 | 128.113 | 0.000 | -563.868 | 0.000 | -1022.387 | -299.154 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 31-OCT-13:30 | 0.00 | -2290.19 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 3881.74 | 0.00 | 219.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2263.11 |
G NW APARTMENT | 29-SEP-15:30 | 0.00 | -1761.70 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2339.26 | 0.00 | 67.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1266.13 |
OFFICE | 31-OCT-12:30 | 0.00 | -2827.52 | 0.00 | 0.00 | 65.19 | 1622.33 | 544.91 | 3304.64 | 0.00 | 23.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2732.88 |
G NE APARTMENT | 30-SEP-08:30 | 0.00 | -1404.23 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1950.57 | 0.00 | 141.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1151.73 |
G N1 APARTMENT | 30-SEP-16:53 | 0.00 | -894.88 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 61.61 | 0.00 | 115.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -99.49 |
G N2 APARTMENT | 30-SEP-16:53 | 0.00 | -879.87 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 61.83 | 0.00 | 115.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -114.43 |
G S1 APARTMENT | 30-OCT-12:30 | 0.00 | -1505.83 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3003.65 | 0.00 | 38.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1994.03 |
G S2 APARTMENT | 30-OCT-12:30 | 0.00 | -1561.53 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3002.94 | 0.00 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1938.93 |
F2 SW APARTMENT | 31-OCT-14:30 | 0.00 | -2938.33 | 0.00 | 0.00 | 40.05 | 50.41 | 400.26 | 3580.13 | 0.00 | 34.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1166.55 |
F2 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2186.04 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2174.74 | 0.00 | 35.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -644.39 |
F2 SE APARTMENT | 31-OCT-13:30 | 0.00 | -2690.92 | 0.00 | 0.00 | 39.89 | 28.81 | 382.60 | 2810.07 | 0.00 | 197.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -767.96 |
F2 NE APARTMENT | 30-SEP-08:30 | 0.00 | -1771.42 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1922.35 | 0.00 | 146.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -761.75 |
F2 N1 APARTMENT | 30-SEP-16:53 | 0.00 | -1213.55 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 52.76 | 0.00 | 115.26 | 228.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 30-SEP-16:53 | 0.00 | -1206.36 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 52.90 | 0.00 | 115.26 | 220.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 31-OCT-14:15 | 0.00 | -1960.51 | 0.00 | 0.00 | 38.34 | 50.41 | 400.26 | 2227.01 | 0.00 | 23.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -778.90 |
F2 S2 APARTMENT | 31-OCT-14:15 | 0.00 | -1981.50 | 0.00 | 0.00 | 38.37 | 50.41 | 400.26 | 2227.05 | 0.00 | 24.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -759.35 |
F3 SW APARTMENT | 31-OCT-14:45 | 0.00 | -2953.69 | 0.00 | 0.00 | 39.85 | 50.41 | 400.26 | 3338.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.23 | -853.85 |
F3 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2213.60 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2161.46 | 0.00 | 41.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -609.86 |
F3 SE APARTMENT | 31-OCT-13:30 | 0.00 | -2538.29 | 0.00 | 0.00 | 39.04 | 28.81 | 382.60 | 2770.31 | 0.00 | 170.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -853.45 |
F3 NE APARTMENT | 30-SEP-08:30 | 0.00 | -1812.03 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1909.43 | 0.00 | 149.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -711.25 |
F3 N1 APARTMENT | 14-OCT-17:05 | 0.00 | -1246.56 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 213.47 | 147.58 | 0.00 | -39.37 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 30-SEP-16:53 | 0.00 | -1239.20 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 52.08 | 0.00 | 114.16 | 255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 03-DEC-12:45 | 0.00 | -2033.62 | 0.00 | 0.00 | 40.72 | 28.81 | 406.15 | 2732.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57.39 | -1116.84 |
F3 S2 APARTMENT | 03-DEC-12:45 | 0.00 | -2042.85 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 2732.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57.35 | -1107.64 |
F4 SW APARTMENT | 31-OCT-14:45 | 0.00 | -2949.84 | 0.00 | 0.00 | 39.82 | 50.41 | 400.26 | 3294.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26.89 | -808.06 |
F4 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2223.44 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2151.12 | 0.00 | 46.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -594.39 |
F4 SE APARTMENT | 31-OCT-13:30 | 0.00 | -2562.52 | 0.00 | 0.00 | 39.06 | 28.81 | 382.60 | 2748.84 | 0.00 | 182.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -819.11 |
F4 NE APARTMENT | 30-SEP-08:45 | 0.00 | -1929.73 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1855.31 | 0.00 | 242.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.83 |
F4 N1 APARTMENT | 14-OCT-17:05 | 0.00 | -1296.36 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 224.94 | 185.72 | 0.00 | -39.19 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 14-OCT-17:05 | 0.00 | -1287.02 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 224.94 | 176.15 | 0.00 | -38.95 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 03-DEC-12:45 | 0.00 | -2046.93 | 0.00 | 0.00 | 40.67 | 28.81 | 406.15 | 2712.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.48 | -1076.82 |
F4 S2 APARTMENT | 03-DEC-12:45 | 0.00 | -2054.83 | 0.00 | 0.00 | 40.68 | 28.81 | 406.15 | 2712.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.44 | -1068.98 |
M SW APARTMENT | 31-OCT-13:45 | 0.00 | -2970.48 | 0.00 | 0.00 | 39.86 | 28.81 | 382.60 | 3656.38 | 0.00 | 187.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1324.42 |
M NW APARTMENT | 30-SEP-15:30 | 0.00 | -2253.24 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2141.69 | 0.00 | 49.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -558.98 |
M SE APARTMENT | 31-OCT-13:30 | 0.00 | -2588.34 | 0.00 | 0.00 | 39.09 | 28.81 | 382.60 | 2731.39 | 0.00 | 191.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -784.78 |
M NE APARTMENT | 30-SEP-08:45 | 0.00 | -1962.43 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1845.75 | 0.00 | 246.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.40 |
M N1 APARTMENT | 14-OCT-17:05 | 0.00 | -1340.72 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 234.08 | 220.97 | 0.00 | -39.21 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 14-OCT-17:05 | 0.00 | -1331.49 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 234.08 | 211.50 | 0.00 | -38.98 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 03-DEC-12:45 | 0.00 | -2075.88 | 0.00 | 0.00 | 40.69 | 28.81 | 406.15 | 2697.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70.13 | -1026.69 |
M S2 APARTMENT | 03-DEC-12:45 | 0.00 | -2083.44 | 0.00 | 0.00 | 40.70 | 28.81 | 406.15 | 2697.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70.09 | -1019.15 |
F6 SW APARTMENT | 30-OCT-14:30 | 0.00 | -2926.96 | 0.00 | 0.00 | 39.82 | 50.41 | 400.26 | 3510.09 | 0.00 | 253.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1327.40 |
F6 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2214.02 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2135.20 | 0.00 | 53.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -594.96 |
F6 SE APARTMENT | 30-OCT-12:45 | 0.00 | -2543.91 | 0.00 | 0.00 | 40.36 | 28.81 | 388.49 | 2990.80 | 0.00 | 94.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -999.42 |
F6 NE APARTMENT | 30-SEP-08:45 | 0.00 | -1926.41 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1839.54 | 0.00 | 249.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -626.28 |
F6 N1 APARTMENT | 14-OCT-17:05 | 0.00 | -1311.45 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 241.59 | 182.45 | 0.00 | -37.47 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 14-OCT-17:05 | 0.00 | -1302.24 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 241.59 | 173.01 | 0.00 | -37.23 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 27-JAN-15:25 | 0.00 | -2038.27 | 0.00 | 0.00 | 41.51 | 50.41 | 400.26 | 1587.01 | 0.00 | 0.00 | 66.46 | 0.00 | 0.00 | 0.00 | -107.38 | 0.00 |
F6 S2 APARTMENT | 03-DEC-12:45 | 0.00 | -2038.70 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 2685.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74.91 | -1047.22 |
F7 SW APARTMENT | 30-OCT-14:30 | 0.00 | -2905.54 | 0.00 | 0.00 | 39.86 | 50.41 | 400.26 | 3490.42 | 0.00 | 263.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1339.21 |
F7 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2198.74 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2128.74 | 0.00 | 55.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -606.61 |
F7 SE APARTMENT | 30-OCT-12:45 | 0.00 | -2527.77 | 0.00 | 0.00 | 40.44 | 28.81 | 388.49 | 2980.35 | 0.00 | 100.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1010.45 |
F7 NE APARTMENT | 30-SEP-08:45 | 0.00 | -1913.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1833.46 | 0.00 | 251.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.09 |
F7 N1 APARTMENT | 14-OCT-17:05 | 0.00 | -1298.83 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 247.87 | 162.57 | 0.00 | -36.49 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 14-OCT-17:05 | 0.00 | -1289.61 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 0.00 | 0.00 | 247.87 | 153.10 | 0.00 | -36.25 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 27-JAN-15:25 | 0.00 | -2073.20 | 0.00 | 0.00 | 41.75 | 50.41 | 400.26 | 1578.95 | 0.00 | 0.00 | 115.58 | 0.00 | 0.00 | 0.00 | -113.75 | 0.00 |
F7 S2 APARTMENT | 27-JAN-15:25 | 0.00 | -2074.15 | 0.00 | 0.00 | 41.76 | 50.41 | 400.26 | 1579.11 | 0.00 | 0.00 | 116.33 | 0.00 | 0.00 | 0.00 | -113.72 | 0.00 |
F8 SW APARTMENT | 30-OCT-14:30 | 0.00 | -2898.08 | 0.00 | 0.00 | 39.95 | 50.41 | 400.26 | 3473.77 | 0.00 | 276.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1342.52 |
F8 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2194.50 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2122.50 | 0.00 | 58.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.12 |
F8 SE APARTMENT | 30-OCT-12:45 | 0.00 | -2523.99 | 0.00 | 0.00 | 40.55 | 28.81 | 388.49 | 2971.58 | 0.00 | 107.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1012.54 |
F8 NE APARTMENT | 30-SEP-08:45 | 0.00 | -1910.58 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1827.63 | 0.00 | 253.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -634.70 |
F8 N1 APARTMENT | 30-SEP-16:38 | 0.00 | -1299.69 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 121.71 | 0.00 | 198.13 | 162.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 30-SEP-16:38 | 0.00 | -1287.15 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 121.85 | 0.00 | 197.87 | 150.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 27-JAN-15:25 | 0.00 | -2074.38 | 0.00 | 0.00 | 41.98 | 50.41 | 400.26 | 1572.19 | 0.00 | 0.00 | 129.20 | 0.00 | 0.00 | 0.00 | -119.68 | 0.00 |
F8 S2 APARTMENT | 27-JAN-15:25 | 0.00 | -2082.04 | 0.00 | 0.00 | 42.00 | 50.41 | 400.26 | 1572.37 | 0.00 | 0.00 | 136.62 | 0.00 | 0.00 | 0.00 | -119.61 | 0.00 |
F9 SW APARTMENT | 30-OCT-14:30 | 0.00 | -2960.96 | 0.00 | 0.00 | 40.33 | 50.41 | 400.26 | 3462.83 | 0.00 | 308.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1301.02 |
F9 NW APARTMENT | 30-SEP-15:30 | 0.00 | -2241.04 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2114.92 | 0.00 | 60.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -555.27 |
F9 SE APARTMENT | 31-OCT-13:30 | 0.00 | -2568.58 | 0.00 | 0.00 | 39.21 | 28.81 | 382.60 | 2691.02 | 0.00 | 224.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -797.15 |
F9 NE APARTMENT | 30-SEP-08:45 | 0.00 | -1913.52 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 1822.14 | 0.00 | 255.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.92 |
F9 N1 APARTMENT | 30-SEP-16:38 | 0.00 | -1364.23 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 120.13 | 0.00 | 197.44 | 229.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 30-SEP-16:38 | 0.00 | -1351.67 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 120.26 | 0.00 | 197.16 | 216.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 27-JAN-15:25 | 0.00 | -2121.42 | 0.00 | 0.00 | 42.29 | 50.41 | 400.26 | 1567.53 | 0.00 | 0.00 | 185.83 | 0.00 | 0.00 | 0.00 | -124.90 | 0.00 |
F9 S2 APARTMENT | 27-JAN-15:25 | 0.00 | -2129.08 | 0.00 | 0.00 | 42.30 | 50.41 | 400.26 | 1567.70 | 0.00 | 0.00 | 193.24 | 0.00 | 0.00 | 0.00 | -124.84 | 0.00 |
T SW APARTMENT | 30-OCT-14:30 | 0.00 | -3558.12 | 0.00 | 0.00 | 40.44 | 50.41 | 400.26 | 3412.50 | 0.00 | 326.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -672.18 |
T NW APARTMENT | 29-SEP-15:30 | 0.00 | -2805.97 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 2130.31 | 0.00 | 175.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -120.63 |
T SE APARTMENT | 31-OCT-13:30 | 0.00 | -3103.11 | 0.00 | 0.00 | 38.91 | 28.81 | 382.60 | 2641.20 | 0.00 | 213.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -202.32 |
T NE APARTMENT | 29-SEP-10:00 | 0.00 | -2198.67 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1713.19 | 0.00 | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.87 |
T N1 APARTMENT | 29-SEP-13:15 | 0.00 | -1669.75 | 0.00 | 0.00 | 40.74 | 28.81 | 382.60 | 654.30 | 0.00 | 153.60 | 409.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-SEP-13:15 | 0.00 | -1673.56 | 0.00 | 0.00 | 40.73 | 28.81 | 382.60 | 654.10 | 0.00 | 153.53 | 413.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 30-OCT-12:45 | 0.00 | -2616.85 | 0.00 | 0.00 | 40.09 | 28.81 | 388.49 | 2766.75 | 0.00 | 74.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -682.11 |
T S2 APARTMENT | 30-OCT-12:45 | 0.00 | -2621.97 | 0.00 | 0.00 | 40.07 | 28.81 | 388.49 | 2766.42 | 0.00 | 74.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -675.93 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-SEP-15:15 | 0.00 | -151503.69 | 0.00 | 0.00 | 3757.51 | 14808.05 | 37687.72 | 115151.97 | 0.00 | 4185.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24087.42 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 25-MAR-09:00 | 1147.81 | 0.00 | 0.00 | 0.00 | 43.40 | 28.81 | 394.37 | 376.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1454.13 | -536.50 |
G NW APARTMENT | 03-JAN-11:10 | 1053.36 | 0.00 | 0.00 | 0.00 | 46.62 | 28.81 | 412.03 | 258.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -984.41 | -814.48 |
OFFICE | 10-JAN-04:00 | 446.47 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -789.09 | 0.00 | -135.70 | -29.95 |
G NE APARTMENT | 12-FEB-09:40 | 1167.36 | 0.00 | 0.00 | 0.00 | 46.19 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17.23 | 0.00 | -1142.56 | -476.94 |
G N1 APARTMENT | 26-MAR-12:45 | 1035.19 | 0.00 | 0.00 | 0.00 | 45.04 | 28.81 | 388.49 | 404.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.87 | -732.62 |
G N2 APARTMENT | 13-MAY-09:45 | 1157.16 | 0.00 | 0.00 | 0.00 | 44.76 | 28.81 | 406.15 | 318.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1104.46 | -850.91 |
G S1 APARTMENT | 25-MAR-09:00 | 1190.61 | 0.00 | 0.00 | 0.00 | 43.35 | 28.81 | 394.37 | 255.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1400.95 | -511.78 |
G S2 APARTMENT | 25-MAR-09:00 | 1141.38 | 0.00 | 0.00 | 0.00 | 43.30 | 28.81 | 394.37 | 255.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1402.47 | -460.71 |
F2 SW APARTMENT | 12-FEB-09:45 | 899.56 | 0.00 | 0.00 | 0.00 | 43.54 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 152.71 | 0.00 | -98.53 | 0.00 | -1420.45 | 0.00 |
F2 NW APARTMENT | 12-FEB-09:45 | 1166.53 | 0.00 | 0.00 | 0.00 | 44.29 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.50 | 0.00 | -1336.88 | -220.62 |
F2 SE APARTMENT | 12-FEB-09:45 | 1043.53 | 0.00 | 0.00 | 0.00 | 43.67 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 | -101.37 | 0.00 | -1414.53 | 0.00 |
F2 NE APARTMENT | 12-FEB-09:45 | 1140.95 | 0.00 | 0.00 | 0.00 | 44.82 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72.38 | 0.00 | -1331.60 | -204.97 |
F2 N1 APARTMENT | 12-FEB-09:45 | 1227.80 | 0.00 | 0.00 | 0.00 | 44.05 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49.33 | 0.00 | -1282.49 | -363.21 |
F2 N2 APARTMENT | 12-FEB-09:45 | 1267.59 | 0.00 | 0.00 | 0.00 | 44.11 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.65 | 0.00 | -1281.06 | -405.18 |
F2 S1 APARTMENT | 12-FEB-09:45 | 682.90 | 0.00 | 0.00 | 0.00 | 43.02 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 291.05 | 0.00 | -67.60 | 0.00 | -1372.55 | 0.00 |
F2 S2 APARTMENT | 12-FEB-09:45 | 666.17 | 0.00 | 0.00 | 0.00 | 43.01 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 308.59 | 0.00 | -67.75 | 0.00 | -1373.20 | 0.00 |
F3 SW APARTMENT | 12-FEB-09:45 | 944.33 | 0.00 | 0.00 | 0.00 | 42.99 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 290.92 | 0.00 | -125.09 | 0.00 | -1576.32 | 0.00 |
F3 NW APARTMENT | 12-FEB-09:45 | 1343.55 | 0.00 | 0.00 | 0.00 | 43.81 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -99.01 | 0.00 | -1471.22 | -240.31 |
F3 SE APARTMENT | 12-FEB-09:45 | 1057.72 | 0.00 | 0.00 | 0.00 | 43.31 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 169.10 | 0.00 | -126.25 | 0.00 | -1567.07 | 0.00 |
F3 NE APARTMENT | 12-FEB-09:45 | 1293.90 | 0.00 | 0.00 | 0.00 | 44.38 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95.40 | 0.00 | -1465.12 | -200.94 |
F3 N1 APARTMENT | 12-FEB-09:45 | 1402.21 | 0.00 | 0.00 | 0.00 | 43.39 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.46 | 0.00 | -1409.08 | -395.23 |
F3 N2 APARTMENT | 12-FEB-09:45 | 1424.76 | 0.00 | 0.00 | 0.00 | 43.46 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.62 | 0.00 | -1407.85 | -419.93 |
F3 S1 APARTMENT | 12-FEB-09:45 | 1197.64 | 0.00 | 0.00 | 0.00 | 42.29 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.31 | 0.00 | -1512.73 | -64.07 |
F3 S2 APARTMENT | 12-FEB-09:45 | 1146.30 | 0.00 | 0.00 | 0.00 | 42.30 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.16 | 0.00 | -1513.51 | -12.12 |
F4 SW APARTMENT | 12-FEB-09:45 | 947.57 | 0.00 | 0.00 | 0.00 | 42.90 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 421.43 | 0.00 | -137.26 | 0.00 | -1697.82 | 0.00 |
F4 NW APARTMENT | 12-FEB-09:45 | 1269.11 | 0.00 | 0.00 | 0.00 | 43.68 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -110.09 | 0.00 | -1580.58 | -45.30 |
F4 SE APARTMENT | 12-FEB-09:45 | 1137.95 | 0.00 | 0.00 | 0.00 | 43.27 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 221.18 | 0.00 | -138.56 | 0.00 | -1687.02 | 0.00 |
F4 NE APARTMENT | 12-FEB-09:45 | 1290.00 | 0.00 | 0.00 | 0.00 | 44.26 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.31 | 0.00 | -1573.02 | -77.11 |
F4 N1 APARTMENT | 12-FEB-09:45 | 1356.38 | 0.00 | 0.00 | 0.00 | 43.13 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72.30 | 0.00 | -1511.78 | -238.61 |
F4 N2 APARTMENT | 12-FEB-09:45 | 1412.27 | 0.00 | 0.00 | 0.00 | 43.21 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.40 | 0.00 | -1510.05 | -297.21 |
F4 S1 APARTMENT | 12-FEB-09:45 | 906.51 | 0.00 | 0.00 | 0.00 | 42.12 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 355.29 | 0.00 | -95.02 | 0.00 | -1632.09 | 0.00 |
F4 S2 APARTMENT | 12-FEB-09:45 | 920.20 | 0.00 | 0.00 | 0.00 | 42.14 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 340.96 | 0.00 | -94.74 | 0.00 | -1631.74 | 0.00 |
M SW APARTMENT | 12-FEB-09:45 | 1092.28 | 0.00 | 0.00 | 0.00 | 42.91 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 385.71 | 0.00 | -144.80 | 0.00 | -1799.28 | 0.00 |
M NW APARTMENT | 12-FEB-09:45 | 1344.95 | 0.00 | 0.00 | 0.00 | 43.65 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -116.87 | 0.00 | -1671.75 | -23.16 |
M SE APARTMENT | 12-FEB-09:45 | 1309.51 | 0.00 | 0.00 | 0.00 | 43.29 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 159.15 | 0.00 | -146.72 | 0.00 | -1788.40 | 0.00 |
M NE APARTMENT | 12-FEB-09:45 | 1312.84 | 0.00 | 0.00 | 0.00 | 44.22 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 | -115.05 | 0.00 | -1666.22 | 0.00 |
M N1 APARTMENT | 12-FEB-09:45 | 1382.17 | 0.00 | 0.00 | 0.00 | 43.01 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.17 | 0.00 | -1598.75 | -172.44 |
M N2 APARTMENT | 12-FEB-09:45 | 1435.16 | 0.00 | 0.00 | 0.00 | 43.09 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.28 | 0.00 | -1597.12 | -228.03 |
M S1 APARTMENT | 12-FEB-09:45 | 1021.63 | 0.00 | 0.00 | 0.00 | 42.08 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 342.43 | 0.00 | -100.58 | 0.00 | -1728.74 | 0.00 |
M S2 APARTMENT | 12-FEB-09:45 | 1036.79 | 0.00 | 0.00 | 0.00 | 42.10 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 326.56 | 0.00 | -100.28 | 0.00 | -1728.35 | 0.00 |
F6 SW APARTMENT | 12-FEB-09:45 | 1503.85 | 0.00 | 0.00 | 0.00 | 43.31 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 52.77 | 0.00 | -143.18 | 0.00 | -1879.92 | 0.00 |
F6 NW APARTMENT | 12-FEB-09:45 | 1399.52 | 0.00 | 0.00 | 0.00 | 44.06 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -114.02 | 0.00 | -1750.88 | -1.85 |
F6 SE APARTMENT | 25-MAR-09:00 | 1639.44 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 259.25 | 0.00 | 0.00 | 379.84 | 0.00 | 0.00 | 0.00 | -2742.46 | 0.00 |
F6 NE APARTMENT | 12-FEB-20:45 | 1265.12 | 0.00 | 0.00 | 0.00 | 154.34 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.00 | 0.00 | -1603.83 | -210.96 |
F6 N1 APARTMENT | 12-FEB-09:45 | 1554.18 | 0.00 | 0.00 | 0.00 | 43.40 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.72 | 0.00 | -1670.67 | -274.36 |
F6 N2 APARTMENT | 12-FEB-09:45 | 1540.42 | 0.00 | 0.00 | 0.00 | 43.47 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74.88 | 0.00 | -1670.56 | -261.63 |
F6 S1 APARTMENT | 12-FEB-09:45 | 1407.95 | 0.00 | 0.00 | 0.00 | 42.43 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 33.54 | 0.00 | -100.52 | 0.00 | -1806.58 | 0.00 |
F6 S2 APARTMENT | 12-FEB-09:45 | 1423.22 | 0.00 | 0.00 | 0.00 | 42.45 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 17.51 | 0.00 | -100.19 | 0.00 | -1806.17 | 0.00 |
F7 SW APARTMENT | 25-MAR-09:00 | 1870.89 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 166.21 | 0.00 | 0.00 | 388.04 | 0.00 | 0.00 | 0.00 | -2889.07 | 0.00 |
F7 NW APARTMENT | 18-APR-09:30 | 1782.34 | 0.00 | 0.00 | 0.00 | 42.76 | 28.81 | 406.15 | 397.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2101.20 | -556.58 |
F7 SE APARTMENT | 25-MAR-09:00 | 2096.24 | 0.00 | 0.00 | 0.00 | 40.83 | 28.81 | 394.37 | 251.25 | 0.00 | 0.00 | 70.25 | 0.00 | 0.00 | 0.00 | -2881.75 | 0.00 |
F7 NE APARTMENT | 13-MAY-09:45 | 1611.11 | 0.00 | 0.00 | 0.00 | 42.37 | 28.81 | 406.15 | 494.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1843.65 | -738.96 |
F7 N1 APARTMENT | 18-APR-09:30 | 1895.29 | 0.00 | 0.00 | 0.00 | 42.34 | 28.81 | 406.15 | 248.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2013.29 | -607.94 |
F7 N2 APARTMENT | 18-APR-09:30 | 1881.10 | 0.00 | 0.00 | 0.00 | 42.36 | 28.81 | 406.15 | 248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2013.23 | -593.98 |
F7 S1 APARTMENT | 12-FEB-09:45 | 1758.02 | 0.00 | 0.00 | 0.00 | 42.73 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.35 | 0.00 | -1878.58 | -245.00 |
F7 S2 APARTMENT | 12-FEB-09:45 | 1754.51 | 0.00 | 0.00 | 0.00 | 42.75 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.02 | 0.00 | -1878.57 | -241.85 |
F8 SW APARTMENT | 25-MAR-09:00 | 2243.75 | 0.00 | 0.00 | 0.00 | 40.77 | 28.81 | 394.37 | 159.46 | 0.00 | 0.00 | 150.86 | 0.00 | 0.00 | 0.00 | -3018.02 | 0.00 |
F8 NW APARTMENT | 13-MAY-09:45 | 1752.40 | 0.00 | 0.00 | 0.00 | 42.90 | 28.81 | 406.15 | 376.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1909.15 | -697.56 |
F8 SE APARTMENT | 25-MAR-09:00 | 2214.88 | 0.00 | 0.00 | 0.00 | 41.03 | 28.81 | 394.37 | 245.18 | 0.00 | 0.00 | 91.41 | 0.00 | 0.00 | 0.00 | -3015.68 | 0.00 |
F8 NE APARTMENT | 13-MAY-09:45 | 1845.98 | 0.00 | 0.00 | 0.00 | 42.76 | 28.81 | 406.15 | 494.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1907.76 | -910.34 |
F8 N1 APARTMENT | 18-APR-09:30 | 1845.40 | 0.00 | 0.00 | 0.00 | 42.72 | 28.81 | 406.15 | 249.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2099.13 | -472.97 |
F8 N2 APARTMENT | 13-MAY-09:45 | 1843.30 | 0.00 | 0.00 | 0.00 | 42.57 | 28.81 | 406.15 | 231.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1836.31 | -716.39 |
F8 S1 APARTMENT | 25-MAR-09:00 | 2080.25 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 119.17 | 0.00 | 0.00 | 231.73 | 0.00 | 0.00 | 0.00 | -2895.08 | 0.00 |
F8 S2 APARTMENT | 25-MAR-09:00 | 2089.55 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 119.29 | 0.00 | 0.00 | 222.23 | 0.00 | 0.00 | 0.00 | -2895.00 | 0.00 |
F9 SW APARTMENT | 25-MAR-09:00 | 2282.17 | 0.00 | 0.00 | 0.00 | 41.17 | 28.81 | 394.37 | 160.75 | 0.00 | 0.00 | 236.90 | 0.00 | 0.00 | 0.00 | -3144.18 | 0.00 |
F9 NW APARTMENT | 13-MAY-09:45 | 1674.32 | 0.00 | 0.00 | 0.00 | 43.51 | 28.81 | 406.15 | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1975.04 | -559.58 |
F9 SE APARTMENT | 25-MAR-09:00 | 2231.29 | 0.00 | 0.00 | 0.00 | 41.50 | 28.81 | 394.37 | 246.55 | 0.00 | 0.00 | 199.30 | 0.00 | 0.00 | 0.00 | -3141.82 | 0.00 |
F9 NE APARTMENT | 12-FEB-09:40 | 1917.03 | 0.00 | 0.00 | 0.00 | 45.55 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -106.48 | 0.00 | -1966.43 | -312.84 |
F9 N1 APARTMENT | 03-FEB-08:00 | 1796.07 | 0.00 | 0.00 | 0.00 | 144.89 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -127.49 | 0.00 | -2000.09 | -289.59 |
F9 N2 APARTMENT | 03-FEB-08:00 | 1779.45 | 0.00 | 0.00 | 0.00 | 145.12 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -126.69 | 0.00 | -1999.98 | -274.14 |
F9 S1 APARTMENT | 25-MAR-09:00 | 2292.30 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 117.06 | 0.00 | 0.00 | 141.75 | 0.00 | 0.00 | 0.00 | -3015.03 | 0.00 |
F9 S2 APARTMENT | 25-MAR-09:00 | 2298.32 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 117.21 | 0.00 | 0.00 | 135.61 | 0.00 | 0.00 | 0.00 | -3015.06 | 0.00 |
T SW APARTMENT | 25-MAR-08:55 | 2461.72 | 0.00 | 0.00 | 0.00 | 42.75 | 28.81 | 394.37 | 190.18 | 0.00 | 0.00 | 198.71 | 0.00 | 0.00 | 0.00 | -3316.54 | 0.00 |
T NW APARTMENT | 03-FEB-07:55 | 2186.30 | 0.00 | 0.00 | 0.00 | 155.05 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.55 | 0.00 | -2180.22 | -489.81 |
T SE APARTMENT | 25-MAR-08:55 | 2595.45 | 0.00 | 0.00 | 0.00 | 43.05 | 28.81 | 394.37 | 273.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3302.52 | -33.00 |
T NE APARTMENT | 18-APR-09:30 | 2038.38 | 0.00 | 0.00 | 0.00 | 41.69 | 28.81 | 406.15 | 1090.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2360.03 | -1245.41 |
T N1 APARTMENT | 26-MAR-11:00 | 1853.20 | 0.00 | 0.00 | 0.00 | 42.99 | 28.81 | 412.03 | 271.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2004.80 | -604.12 |
T N2 APARTMENT | 26-MAR-11:00 | 1855.82 | 0.00 | 0.00 | 0.00 | 42.92 | 28.81 | 412.03 | 271.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2004.89 | -605.69 |
T S1 APARTMENT | 25-MAR-09:00 | 2566.32 | 0.00 | 0.00 | 0.00 | 41.61 | 28.81 | 394.37 | 128.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3130.06 | -29.98 |
T S2 APARTMENT | 25-MAR-09:00 | 2563.47 | 0.00 | 0.00 | 0.00 | 41.63 | 28.81 | 394.37 | 129.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3130.06 | -27.43 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-09:45 | 101837.73 | 0.00 | 0.00 | 0.00 | 3471.56 | 9118.54 | 31642.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7490.12 | 0.00 | -135199.89 | -3380.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Sec1.1A-General InformationData | |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 24.50 |
Number of hours cooling loads not met | 153.25 |
Number of hours not met | 177.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.56 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 3.29 | 0.00 | 0.59 | 13019.98 | 0.00 | 0.00 |
Space Cooling | 267.70 | 45725.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 35.73 | 1192.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.58 | 1479.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 488.37 | 15486.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1045.87 | 80594.78 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2543.57 | 1046.46 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 2543.57 |
Natural Gas | 0.00 | 1046.46 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 3590.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 0.42 |
Space Cooling | 34.16 |
Fans-Interior | 62.32 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 30.20 |
Subtotal | 324.58 |
Natural Gas [MJ/m2] | |
Space Heating | 0.08 |
Service Water Heating | 133.46 |
Miscellaneous | 0.00 |
Subtotal | 133.54 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 11.60 |
Space Heating | 0.11 |
Space Cooling | 7.46 |
Fans-Interior | 13.60 |
Service Water Heating | 29.13 |
Receptacle Equipment | 31.51 |
Miscellaneous | 6.59 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.188894 |
G NW APARTMENT DIRECT AIR | 0.167315 |
OFFICE DIRECT AIR | 0.261994 |
G NE APARTMENT DIRECT AIR | 0.128314 |
G N1 APARTMENT DIRECT AIR | 0.081209 |
G N2 APARTMENT DIRECT AIR | 0.079773 |
G S1 APARTMENT DIRECT AIR | 0.115615 |
G S2 APARTMENT DIRECT AIR | 0.120461 |
F2 SW APARTMENT DIRECT AIR | 0.238219 |
F2 NW APARTMENT DIRECT AIR | 0.212404 |
F2 SE APARTMENT DIRECT AIR | 0.220624 |
F2 NE APARTMENT DIRECT AIR | 0.167452 |
F2 N1 APARTMENT DIRECT AIR | 0.112139 |
F2 N2 APARTMENT DIRECT AIR | 0.110887 |
F2 S1 APARTMENT DIRECT AIR | 0.151285 |
F2 S2 APARTMENT DIRECT AIR | 0.153147 |
F3 SW APARTMENT DIRECT AIR | 0.238548 |
F3 NW APARTMENT DIRECT AIR | 0.213965 |
F3 SE APARTMENT DIRECT AIR | 0.206113 |
F3 NE APARTMENT DIRECT AIR | 0.170031 |
F3 N1 APARTMENT DIRECT AIR | 0.115643 |
F3 N2 APARTMENT DIRECT AIR | 0.114408 |
F3 S1 APARTMENT DIRECT AIR | 0.153635 |
F3 S2 APARTMENT DIRECT AIR | 0.154519 |
F4 SW APARTMENT DIRECT AIR | 0.238428 |
F4 NW APARTMENT DIRECT AIR | 0.214389 |
F4 SE APARTMENT DIRECT AIR | 0.204571 |
F4 NE APARTMENT DIRECT AIR | 0.170493 |
F4 N1 APARTMENT DIRECT AIR | 0.117102 |
F4 N2 APARTMENT DIRECT AIR | 0.115879 |
F4 S1 APARTMENT DIRECT AIR | 0.154154 |
F4 S2 APARTMENT DIRECT AIR | 0.154892 |
M SW APARTMENT DIRECT AIR | 0.240527 |
M NW APARTMENT DIRECT AIR | 0.216949 |
M SE APARTMENT DIRECT AIR | 0.206836 |
M NE APARTMENT DIRECT AIR | 0.173056 |
M N1 APARTMENT DIRECT AIR | 0.120337 |
M N2 APARTMENT DIRECT AIR | 0.119123 |
M S1 APARTMENT DIRECT AIR | 0.156647 |
M S2 APARTMENT DIRECT AIR | 0.157363 |
F6 SW APARTMENT DIRECT AIR | 0.236448 |
F6 NW APARTMENT DIRECT AIR | 0.213143 |
F6 SE APARTMENT DIRECT AIR | 0.203134 |
F6 NE APARTMENT DIRECT AIR | 0.169340 |
F6 N1 APARTMENT DIRECT AIR | 0.117434 |
F6 N2 APARTMENT DIRECT AIR | 0.116236 |
F6 S1 APARTMENT DIRECT AIR | 0.153056 |
F6 S2 APARTMENT DIRECT AIR | 0.153769 |
F7 SW APARTMENT DIRECT AIR | 0.234730 |
F7 NW APARTMENT DIRECT AIR | 0.211724 |
F7 SE APARTMENT DIRECT AIR | 0.201730 |
F7 NE APARTMENT DIRECT AIR | 0.167975 |
F7 N1 APARTMENT DIRECT AIR | 0.116694 |
F7 N2 APARTMENT DIRECT AIR | 0.115509 |
F7 S1 APARTMENT DIRECT AIR | 0.151705 |
F7 S2 APARTMENT DIRECT AIR | 0.152417 |
F8 SW APARTMENT DIRECT AIR | 0.234310 |
F8 NW APARTMENT DIRECT AIR | 0.211575 |
F8 SE APARTMENT DIRECT AIR | 0.201545 |
F8 NE APARTMENT DIRECT AIR | 0.167823 |
F8 N1 APARTMENT DIRECT AIR | 0.117125 |
F8 N2 APARTMENT DIRECT AIR | 0.115952 |
F8 S1 APARTMENT DIRECT AIR | 0.151570 |
F8 S2 APARTMENT DIRECT AIR | 0.152283 |
F9 SW APARTMENT DIRECT AIR | 0.240441 |
F9 NW APARTMENT DIRECT AIR | 0.217900 |
F9 SE APARTMENT DIRECT AIR | 0.206117 |
F9 NE APARTMENT DIRECT AIR | 0.169799 |
F9 N1 APARTMENT DIRECT AIR | 0.123027 |
F9 N2 APARTMENT DIRECT AIR | 0.121848 |
F9 S1 APARTMENT DIRECT AIR | 0.155428 |
F9 S2 APARTMENT DIRECT AIR | 0.156140 |
T SW APARTMENT DIRECT AIR | 0.291629 |
T NW APARTMENT DIRECT AIR | 0.263071 |
T SE APARTMENT DIRECT AIR | 0.252890 |
T NE APARTMENT DIRECT AIR | 0.202521 |
T N1 APARTMENT DIRECT AIR | 0.152116 |
T N2 APARTMENT DIRECT AIR | 0.152047 |
T S1 APARTMENT DIRECT AIR | 0.207642 |
T S2 APARTMENT DIRECT AIR | 0.208336 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.188894 |
AIRLOOP G NW MAIN BRANCH | 0.167315 |
AIRLOOP OFFICE MAIN BRANCH | 0.261994 |
AIRLOOP G NE MAIN BRANCH | 0.128314 |
AIRLOOP G N1 MAIN BRANCH | 0.081209 |
AIRLOOP G N2 MAIN BRANCH | 0.079773 |
AIRLOOP G S1 MAIN BRANCH | 0.115615 |
AIRLOOP G S2 MAIN BRANCH | 0.120461 |
AIRLOOP F2 SW MAIN BRANCH | 0.238219 |
AIRLOOP F2 NW MAIN BRANCH | 0.212404 |
AIRLOOP F2 SE MAIN BRANCH | 0.220624 |
AIRLOOP F2 NE MAIN BRANCH | 0.167452 |
AIRLOOP F2 N1 MAIN BRANCH | 0.112139 |
AIRLOOP F2 N2 MAIN BRANCH | 0.110887 |
AIRLOOP F2 S1 MAIN BRANCH | 0.151285 |
AIRLOOP F2 S2 MAIN BRANCH | 0.153147 |
AIRLOOP F3 SW MAIN BRANCH | 0.238548 |
AIRLOOP F3 NW MAIN BRANCH | 0.213965 |
AIRLOOP F3 SE MAIN BRANCH | 0.206113 |
AIRLOOP F3 NE MAIN BRANCH | 0.170031 |
AIRLOOP F3 N1 MAIN BRANCH | 0.115643 |
AIRLOOP F3 N2 MAIN BRANCH | 0.114408 |
AIRLOOP F3 S1 MAIN BRANCH | 0.153635 |
AIRLOOP F3 S2 MAIN BRANCH | 0.154519 |
AIRLOOP F4 SW MAIN BRANCH | 0.238428 |
AIRLOOP F4 NW MAIN BRANCH | 0.214389 |
AIRLOOP F4 SE MAIN BRANCH | 0.204571 |
AIRLOOP F4 NE MAIN BRANCH | 0.170493 |
AIRLOOP F4 N1 MAIN BRANCH | 0.117102 |
AIRLOOP F4 N2 MAIN BRANCH | 0.115879 |
AIRLOOP F4 S1 MAIN BRANCH | 0.154154 |
AIRLOOP F4 S2 MAIN BRANCH | 0.154892 |
AIRLOOP M SW MAIN BRANCH | 0.240527 |
AIRLOOP M NW MAIN BRANCH | 0.216949 |
AIRLOOP M SE MAIN BRANCH | 0.206836 |
AIRLOOP M NE MAIN BRANCH | 0.173056 |
AIRLOOP M N1 MAIN BRANCH | 0.120337 |
AIRLOOP M N2 MAIN BRANCH | 0.119123 |
AIRLOOP M S1 MAIN BRANCH | 0.156647 |
AIRLOOP M S2 MAIN BRANCH | 0.157363 |
AIRLOOP F6 SW MAIN BRANCH | 0.236448 |
AIRLOOP F6 NW MAIN BRANCH | 0.213143 |
AIRLOOP F6 SE MAIN BRANCH | 0.203134 |
AIRLOOP F6 NE MAIN BRANCH | 0.169340 |
AIRLOOP F6 N1 MAIN BRANCH | 0.117434 |
AIRLOOP F6 N2 MAIN BRANCH | 0.116236 |
AIRLOOP F6 S1 MAIN BRANCH | 0.153056 |
AIRLOOP F6 S2 MAIN BRANCH | 0.153769 |
AIRLOOP F7 SW MAIN BRANCH | 0.234730 |
AIRLOOP F7 NW MAIN BRANCH | 0.211724 |
AIRLOOP F7 SE MAIN BRANCH | 0.201730 |
AIRLOOP F7 NE MAIN BRANCH | 0.167975 |
AIRLOOP F7 N1 MAIN BRANCH | 0.116694 |
AIRLOOP F7 N2 MAIN BRANCH | 0.115509 |
AIRLOOP F7 S1 MAIN BRANCH | 0.151705 |
AIRLOOP F7 S2 MAIN BRANCH | 0.152417 |
AIRLOOP F8 SW MAIN BRANCH | 0.234310 |
AIRLOOP F8 NW MAIN BRANCH | 0.211575 |
AIRLOOP F8 SE MAIN BRANCH | 0.201545 |
AIRLOOP F8 NE MAIN BRANCH | 0.167823 |
AIRLOOP F8 N1 MAIN BRANCH | 0.117125 |
AIRLOOP F8 N2 MAIN BRANCH | 0.115952 |
AIRLOOP F8 S1 MAIN BRANCH | 0.151570 |
AIRLOOP F8 S2 MAIN BRANCH | 0.152283 |
AIRLOOP F9 SW MAIN BRANCH | 0.240441 |
AIRLOOP F9 NW MAIN BRANCH | 0.217900 |
AIRLOOP F9 SE MAIN BRANCH | 0.206117 |
AIRLOOP F9 NE MAIN BRANCH | 0.169799 |
AIRLOOP F9 N1 MAIN BRANCH | 0.123027 |
AIRLOOP F9 N2 MAIN BRANCH | 0.121848 |
AIRLOOP F9 S1 MAIN BRANCH | 0.155428 |
AIRLOOP F9 S2 MAIN BRANCH | 0.156140 |
AIRLOOP T SW MAIN BRANCH | 0.291629 |
AIRLOOP T NW MAIN BRANCH | 0.263071 |
AIRLOOP T SE MAIN BRANCH | 0.252890 |
AIRLOOP T NE MAIN BRANCH | 0.202521 |
AIRLOOP T N1 MAIN BRANCH | 0.152116 |
AIRLOOP T N2 MAIN BRANCH | 0.152047 |
AIRLOOP T S1 MAIN BRANCH | 0.207642 |
AIRLOOP T S2 MAIN BRANCH | 0.208336 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.188894 |
AIRLOOP G NW | 0.167315 |
AIRLOOP OFFICE | 0.261994 |
AIRLOOP G NE | 0.128314 |
AIRLOOP G N1 | 0.081209 |
AIRLOOP G N2 | 0.079773 |
AIRLOOP G S1 | 0.115615 |
AIRLOOP G S2 | 0.120461 |
AIRLOOP F2 SW | 0.238219 |
AIRLOOP F2 NW | 0.212404 |
AIRLOOP F2 SE | 0.220624 |
AIRLOOP F2 NE | 0.167452 |
AIRLOOP F2 N1 | 0.112139 |
AIRLOOP F2 N2 | 0.110887 |
AIRLOOP F2 S1 | 0.151285 |
AIRLOOP F2 S2 | 0.153147 |
AIRLOOP F3 SW | 0.238548 |
AIRLOOP F3 NW | 0.213965 |
AIRLOOP F3 SE | 0.206113 |
AIRLOOP F3 NE | 0.170031 |
AIRLOOP F3 N1 | 0.115643 |
AIRLOOP F3 N2 | 0.114408 |
AIRLOOP F3 S1 | 0.153635 |
AIRLOOP F3 S2 | 0.154519 |
AIRLOOP F4 SW | 0.238428 |
AIRLOOP F4 NW | 0.214389 |
AIRLOOP F4 SE | 0.204571 |
AIRLOOP F4 NE | 0.170493 |
AIRLOOP F4 N1 | 0.117102 |
AIRLOOP F4 N2 | 0.115879 |
AIRLOOP F4 S1 | 0.154154 |
AIRLOOP F4 S2 | 0.154892 |
AIRLOOP M SW | 0.240527 |
AIRLOOP M NW | 0.216949 |
AIRLOOP M SE | 0.206836 |
AIRLOOP M NE | 0.173056 |
AIRLOOP M N1 | 0.120337 |
AIRLOOP M N2 | 0.119123 |
AIRLOOP M S1 | 0.156647 |
AIRLOOP M S2 | 0.157363 |
AIRLOOP F6 SW | 0.236448 |
AIRLOOP F6 NW | 0.213143 |
AIRLOOP F6 SE | 0.203134 |
AIRLOOP F6 NE | 0.169340 |
AIRLOOP F6 N1 | 0.117434 |
AIRLOOP F6 N2 | 0.116236 |
AIRLOOP F6 S1 | 0.153056 |
AIRLOOP F6 S2 | 0.153769 |
AIRLOOP F7 SW | 0.234730 |
AIRLOOP F7 NW | 0.211724 |
AIRLOOP F7 SE | 0.201730 |
AIRLOOP F7 NE | 0.167975 |
AIRLOOP F7 N1 | 0.116694 |
AIRLOOP F7 N2 | 0.115509 |
AIRLOOP F7 S1 | 0.151705 |
AIRLOOP F7 S2 | 0.152417 |
AIRLOOP F8 SW | 0.234310 |
AIRLOOP F8 NW | 0.211575 |
AIRLOOP F8 SE | 0.201545 |
AIRLOOP F8 NE | 0.167823 |
AIRLOOP F8 N1 | 0.117125 |
AIRLOOP F8 N2 | 0.115952 |
AIRLOOP F8 S1 | 0.151570 |
AIRLOOP F8 S2 | 0.152283 |
AIRLOOP F9 SW | 0.240441 |
AIRLOOP F9 NW | 0.217900 |
AIRLOOP F9 SE | 0.206117 |
AIRLOOP F9 NE | 0.169799 |
AIRLOOP F9 N1 | 0.123027 |
AIRLOOP F9 N2 | 0.121848 |
AIRLOOP F9 S1 | 0.155428 |
AIRLOOP F9 S2 | 0.156140 |
AIRLOOP T SW | 0.291629 |
AIRLOOP T NW | 0.263071 |
AIRLOOP T SE | 0.252890 |
AIRLOOP T NE | 0.202521 |
AIRLOOP T N1 | 0.152116 |
AIRLOOP T N2 | 0.152047 |
AIRLOOP T S1 | 0.207642 |
AIRLOOP T S2 | 0.208336 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.188894 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.167315 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.261994 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.128314 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.081209 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.079773 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.115615 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.120461 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.238219 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.212404 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.220624 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.167452 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.112139 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.110887 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.151285 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.153147 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.238548 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.213965 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.206113 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.170031 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.115643 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.114408 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.153635 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.154519 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.238428 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.214389 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.204571 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.170493 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.117102 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.115879 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.154154 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.154892 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.240527 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.216949 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.206836 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.173056 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.120337 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.119123 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.156647 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.157363 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.236448 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.213143 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.203134 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.169340 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.117434 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.116236 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.153056 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.153769 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.234730 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.211724 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.201730 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.167975 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.116694 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.115509 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.151705 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.152417 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.234310 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.211575 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.201545 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.167823 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.117125 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.115952 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.151570 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.152283 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.240441 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.217900 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.206117 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.169799 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.123027 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.121848 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.155428 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.156140 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.291629 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.263071 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.252890 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.202521 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.152116 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.152047 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.207642 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.208336 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.188894 | 2839.53 | 2106.80 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.167315 | 2522.87 | 1868.55 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.261994 | 3844.40 | 2883.77 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.128314 | 1908.88 | 1416.10 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.081209 | 1293.49 | 933.64 | 0.000028 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.079773 | 1273.15 | 918.20 | 0.000028 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.115615 | 1823.85 | 1325.85 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.120461 | 1890.97 | 1377.58 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.238219 | 3515.55 | 2628.17 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.212404 | 3141.05 | 2344.50 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.220624 | 3233.24 | 2422.84 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.167452 | 2453.21 | 1835.33 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.112139 | 1728.18 | 1265.02 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.110887 | 1710.59 | 1251.62 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.151285 | 2319.45 | 1706.73 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.153147 | 2345.27 | 1726.58 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.238548 | 3520.99 | 2631.89 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.213965 | 3163.52 | 2361.34 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.206113 | 3033.06 | 2268.66 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.170031 | 2489.29 | 1862.85 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.115643 | 1777.51 | 1302.55 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.114408 | 1760.18 | 1289.34 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.153635 | 2352.47 | 1731.90 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.154519 | 2364.72 | 1741.32 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.238428 | 3519.98 | 2630.78 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.214389 | 3170.01 | 2366.00 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.204571 | 3058.33 | 2273.89 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.170493 | 2496.07 | 1867.86 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.117102 | 1798.15 | 1318.21 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.115879 | 1780.98 | 1305.12 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.154154 | 2360.00 | 1737.52 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.154892 | 2370.23 | 1745.38 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.240527 | 3549.60 | 2653.26 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.216949 | 3206.03 | 2393.40 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.206836 | 3090.25 | 2298.15 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.173056 | 2531.83 | 1895.20 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.120337 | 1843.61 | 1352.84 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.119123 | 1826.57 | 1339.85 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.156647 | 2394.87 | 1764.18 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.157363 | 2404.80 | 1771.81 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.236448 | 3493.53 | 2609.96 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.213143 | 3153.62 | 2352.97 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.203134 | 3039.32 | 2258.82 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.169340 | 2480.76 | 1855.77 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.117434 | 1803.10 | 1321.84 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.116236 | 1786.28 | 1309.02 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.153056 | 2345.26 | 1725.94 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.153769 | 2355.14 | 1733.54 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.234730 | 3470.11 | 2591.77 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.211724 | 3134.29 | 2337.96 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.201730 | 3020.23 | 2243.97 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.167975 | 2462.13 | 1841.32 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.116694 | 1792.87 | 1313.96 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.115509 | 1776.22 | 1301.27 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.151705 | 2326.70 | 1711.58 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.152417 | 2336.56 | 1719.17 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.234310 | 3464.65 | 2587.40 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.211575 | 3132.54 | 2336.45 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.201545 | 3017.98 | 2242.08 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.167823 | 2460.25 | 1839.76 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.117125 | 1799.02 | 1318.60 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.115952 | 1782.53 | 1306.04 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.151570 | 2325.00 | 1710.19 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.152283 | 2334.88 | 1717.78 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.240441 | 3549.97 | 2652.75 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.217900 | 3220.67 | 2403.89 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.206117 | 3084.88 | 2292.33 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.169799 | 2487.83 | 1860.84 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.123027 | 1881.80 | 1381.72 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.121848 | 1865.25 | 1369.11 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.155428 | 2381.82 | 1752.79 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.156140 | 2391.69 | 1760.39 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.291629 | 4272.38 | 3203.58 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.263071 | 3859.75 | 2891.51 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.252890 | 3733.69 | 2790.42 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.202521 | 2958.33 | 2217.81 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.152116 | 2342.21 | 1720.34 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.152047 | 2341.28 | 1719.60 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.207642 | 3106.45 | 2309.33 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.208336 | 3112.94 | 2315.26 | 0.000068 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.188894 | 0.188894 | 0.188894 | 0.188894 | 2839.53 | 2839.53 | 1465.42 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.167315 | 0.167315 | 0.167315 | 0.167315 | 2522.87 | 2522.87 | 1470.22 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.261994 | 0.261994 | 0.261994 | 0.261994 | 3844.40 | 3844.40 | 2103.21 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.128314 | 0.128314 | 0.128314 | 0.128314 | 1908.88 | 1908.88 | 1468.59 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.081209 | 0.081209 | 0.081209 | 0.081209 | 1293.49 | 1293.49 | 1115.65 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.079773 | 0.079773 | 0.079773 | 0.079773 | 1273.15 | 1273.15 | 1115.65 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.115615 | 0.115615 | 0.115615 | 0.115615 | 1823.85 | 1823.85 | 1115.65 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.120461 | 0.120461 | 0.120461 | 0.120461 | 1890.97 | 1890.97 | 1115.65 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.238219 | 0.238219 | 0.238219 | 0.238219 | 3515.55 | 3515.55 | 1436.46 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.212404 | 0.212404 | 0.212404 | 0.212404 | 3141.05 | 3141.05 | 1439.57 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.220624 | 0.220624 | 0.220624 | 0.220624 | 3233.24 | 3233.24 | 1461.40 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.167452 | 0.167452 | 0.167452 | 0.167452 | 2453.21 | 2453.21 | 1438.46 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.112139 | 0.112139 | 0.112139 | 0.112139 | 1728.18 | 1728.18 | 1115.65 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.110887 | 0.110887 | 0.110887 | 0.110887 | 1710.59 | 1710.59 | 1115.65 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.151285 | 0.151285 | 0.151285 | 0.151285 | 2319.45 | 2319.45 | 1115.65 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.153147 | 0.153147 | 0.153147 | 0.153147 | 2345.27 | 2345.27 | 1115.65 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.238548 | 0.238548 | 0.238548 | 0.238548 | 3520.99 | 3520.99 | 1421.50 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.213965 | 0.213965 | 0.213965 | 0.213965 | 3163.52 | 3163.52 | 1423.36 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.206113 | 0.206113 | 0.206113 | 0.206113 | 3033.06 | 3033.06 | 1424.26 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.170031 | 0.170031 | 0.170031 | 0.170031 | 2489.29 | 2489.29 | 1422.88 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.115643 | 0.115643 | 0.115643 | 0.115643 | 1777.51 | 1777.51 | 1115.65 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.114408 | 0.114408 | 0.114408 | 0.114408 | 1760.18 | 1760.18 | 1115.65 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.153635 | 0.153635 | 0.153635 | 0.153635 | 2352.47 | 2352.47 | 1115.65 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.154519 | 0.154519 | 0.154519 | 0.154519 | 2364.72 | 2364.72 | 1115.65 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.238428 | 0.238428 | 0.238428 | 0.238428 | 3519.98 | 3519.98 | 1434.10 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.214389 | 0.214389 | 0.214389 | 0.214389 | 3170.01 | 3170.01 | 1435.44 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.204571 | 0.204571 | 0.204571 | 0.204571 | 3058.33 | 3058.33 | 1434.52 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.170493 | 0.170493 | 0.170493 | 0.170493 | 2496.07 | 2496.07 | 1435.47 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.117102 | 0.117102 | 0.117102 | 0.117102 | 1798.15 | 1798.15 | 1115.65 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.115879 | 0.115879 | 0.115879 | 0.115879 | 1780.98 | 1780.98 | 1115.65 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.154154 | 0.154154 | 0.154154 | 0.154154 | 2360.00 | 2360.00 | 1115.65 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.154892 | 0.154892 | 0.154892 | 0.154892 | 2370.23 | 2370.23 | 1115.65 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.240527 | 0.240527 | 0.240527 | 0.240527 | 3549.60 | 3549.60 | 1427.89 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.216949 | 0.216949 | 0.216949 | 0.216949 | 3206.03 | 3206.03 | 1427.59 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.206836 | 0.206836 | 0.206836 | 0.206836 | 3090.25 | 3090.25 | 1428.40 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.173056 | 0.173056 | 0.173056 | 0.173056 | 2531.83 | 2531.83 | 1428.04 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.120337 | 0.120337 | 0.120337 | 0.120337 | 1843.61 | 1843.61 | 1115.65 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.119123 | 0.119123 | 0.119123 | 0.119123 | 1826.57 | 1826.57 | 1115.65 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.156647 | 0.156647 | 0.156647 | 0.156647 | 2394.87 | 2394.87 | 1115.65 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.157363 | 0.157363 | 0.157363 | 0.157363 | 2404.80 | 2404.80 | 1115.65 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.236448 | 0.236448 | 0.236448 | 0.236448 | 3493.53 | 3493.53 | 1486.88 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.213143 | 0.213143 | 0.213143 | 0.213143 | 3153.62 | 3153.62 | 1486.95 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.203134 | 0.203134 | 0.203134 | 0.203134 | 3039.32 | 3039.32 | 1487.71 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.169340 | 0.169340 | 0.169340 | 0.169340 | 2480.76 | 2480.76 | 1487.77 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.117434 | 0.117434 | 0.117434 | 0.117434 | 1803.10 | 1803.10 | 1115.65 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.116236 | 0.116236 | 0.116236 | 0.116236 | 1786.28 | 1786.28 | 1115.65 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.153056 | 0.153056 | 0.153056 | 0.153056 | 2345.26 | 2345.26 | 1115.65 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.153769 | 0.153769 | 0.153769 | 0.153769 | 2355.14 | 2355.14 | 1115.65 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.234730 | 0.234730 | 0.234730 | 0.234730 | 3470.11 | 3470.11 | 1522.27 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.211724 | 0.211724 | 0.211724 | 0.211724 | 3134.29 | 3134.29 | 1521.61 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.201730 | 0.201730 | 0.201730 | 0.201730 | 3020.23 | 3020.23 | 1523.41 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.167975 | 0.167975 | 0.167975 | 0.167975 | 2462.13 | 2462.13 | 1522.75 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.116694 | 0.116694 | 0.116694 | 0.116694 | 1792.87 | 1792.87 | 1115.65 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.115509 | 0.115509 | 0.115509 | 0.115509 | 1776.22 | 1776.22 | 1115.65 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.151705 | 0.151705 | 0.151705 | 0.151705 | 2326.70 | 2326.70 | 1115.65 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.152417 | 0.152417 | 0.152417 | 0.152417 | 2336.56 | 2336.56 | 1115.65 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.234310 | 0.234310 | 0.234310 | 0.234310 | 3464.65 | 3464.65 | 1558.55 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.211575 | 0.211575 | 0.211575 | 0.211575 | 3132.54 | 3132.54 | 1557.08 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.201545 | 0.201545 | 0.201545 | 0.201545 | 3017.98 | 3017.98 | 1559.97 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.167823 | 0.167823 | 0.167823 | 0.167823 | 2460.25 | 2460.25 | 1558.51 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.117125 | 0.117125 | 0.117125 | 0.117125 | 1799.02 | 1799.02 | 1115.65 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.115952 | 0.115952 | 0.115952 | 0.115952 | 1782.53 | 1782.53 | 1115.65 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.151570 | 0.151570 | 0.151570 | 0.151570 | 2325.00 | 2325.00 | 1115.65 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.152283 | 0.152283 | 0.152283 | 0.152283 | 2334.88 | 2334.88 | 1115.65 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.240441 | 0.240441 | 0.240441 | 0.240441 | 3549.97 | 3549.97 | 1671.99 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.217900 | 0.217900 | 0.217900 | 0.217900 | 3220.67 | 3220.67 | 1668.34 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.206117 | 0.206117 | 0.206117 | 0.206117 | 3084.88 | 3084.88 | 1673.68 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.169799 | 0.169799 | 0.169799 | 0.169799 | 2487.83 | 2487.83 | 1670.03 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.123027 | 0.123027 | 0.123027 | 0.123027 | 1881.80 | 1881.80 | 1115.65 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.121848 | 0.121848 | 0.121848 | 0.121848 | 1865.25 | 1865.25 | 1115.65 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.155428 | 0.155428 | 0.155428 | 0.155428 | 2381.82 | 2381.82 | 1115.65 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.156140 | 0.156140 | 0.156140 | 0.156140 | 2391.69 | 2391.69 | 1115.65 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.291629 | 0.291629 | 0.291629 | 0.291629 | 4272.38 | 4272.38 | 2050.85 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.263071 | 0.263071 | 0.263071 | 0.263071 | 3859.75 | 3859.75 | 2051.87 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.252890 | 0.252890 | 0.252890 | 0.252890 | 3733.69 | 3733.69 | 2052.57 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.202521 | 0.202521 | 0.202521 | 0.202521 | 2958.33 | 2958.33 | 2053.59 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.152116 | 0.152116 | 0.152116 | 0.152116 | 2342.21 | 2342.21 | 1493.22 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.152047 | 0.152047 | 0.152047 | 0.152047 | 2341.28 | 2341.28 | 1493.27 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.207642 | 0.207642 | 0.207642 | 0.207642 | 3106.45 | 3106.45 | 1489.31 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.208336 | 0.208336 | 0.208336 | 0.208336 | 3112.94 | 3112.94 | 1489.36 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.188894 |
AIRLOOP G NW SUPPLY FAN | 0.167315 |
AIRLOOP OFFICE SUPPLY FAN | 0.261994 |
AIRLOOP G NE SUPPLY FAN | 0.128314 |
AIRLOOP G N1 SUPPLY FAN | 0.081209 |
AIRLOOP G N2 SUPPLY FAN | 0.079773 |
AIRLOOP G S1 SUPPLY FAN | 0.115615 |
AIRLOOP G S2 SUPPLY FAN | 0.120461 |
AIRLOOP F2 SW SUPPLY FAN | 0.238219 |
AIRLOOP F2 NW SUPPLY FAN | 0.212404 |
AIRLOOP F2 SE SUPPLY FAN | 0.220624 |
AIRLOOP F2 NE SUPPLY FAN | 0.167452 |
AIRLOOP F2 N1 SUPPLY FAN | 0.112139 |
AIRLOOP F2 N2 SUPPLY FAN | 0.110887 |
AIRLOOP F2 S1 SUPPLY FAN | 0.151285 |
AIRLOOP F2 S2 SUPPLY FAN | 0.153147 |
AIRLOOP F3 SW SUPPLY FAN | 0.238548 |
AIRLOOP F3 NW SUPPLY FAN | 0.213965 |
AIRLOOP F3 SE SUPPLY FAN | 0.206113 |
AIRLOOP F3 NE SUPPLY FAN | 0.170031 |
AIRLOOP F3 N1 SUPPLY FAN | 0.115643 |
AIRLOOP F3 N2 SUPPLY FAN | 0.114408 |
AIRLOOP F3 S1 SUPPLY FAN | 0.153635 |
AIRLOOP F3 S2 SUPPLY FAN | 0.154519 |
AIRLOOP F4 SW SUPPLY FAN | 0.238428 |
AIRLOOP F4 NW SUPPLY FAN | 0.214389 |
AIRLOOP F4 SE SUPPLY FAN | 0.204571 |
AIRLOOP F4 NE SUPPLY FAN | 0.170493 |
AIRLOOP F4 N1 SUPPLY FAN | 0.117102 |
AIRLOOP F4 N2 SUPPLY FAN | 0.115879 |
AIRLOOP F4 S1 SUPPLY FAN | 0.154154 |
AIRLOOP F4 S2 SUPPLY FAN | 0.154892 |
AIRLOOP M SW SUPPLY FAN | 0.240527 |
AIRLOOP M NW SUPPLY FAN | 0.216949 |
AIRLOOP M SE SUPPLY FAN | 0.206836 |
AIRLOOP M NE SUPPLY FAN | 0.173056 |
AIRLOOP M N1 SUPPLY FAN | 0.120337 |
AIRLOOP M N2 SUPPLY FAN | 0.119123 |
AIRLOOP M S1 SUPPLY FAN | 0.156647 |
AIRLOOP M S2 SUPPLY FAN | 0.157363 |
AIRLOOP F6 SW SUPPLY FAN | 0.236448 |
AIRLOOP F6 NW SUPPLY FAN | 0.213143 |
AIRLOOP F6 SE SUPPLY FAN | 0.203134 |
AIRLOOP F6 NE SUPPLY FAN | 0.169340 |
AIRLOOP F6 N1 SUPPLY FAN | 0.117434 |
AIRLOOP F6 N2 SUPPLY FAN | 0.116236 |
AIRLOOP F6 S1 SUPPLY FAN | 0.153056 |
AIRLOOP F6 S2 SUPPLY FAN | 0.153769 |
AIRLOOP F7 SW SUPPLY FAN | 0.234730 |
AIRLOOP F7 NW SUPPLY FAN | 0.211724 |
AIRLOOP F7 SE SUPPLY FAN | 0.201730 |
AIRLOOP F7 NE SUPPLY FAN | 0.167975 |
AIRLOOP F7 N1 SUPPLY FAN | 0.116694 |
AIRLOOP F7 N2 SUPPLY FAN | 0.115509 |
AIRLOOP F7 S1 SUPPLY FAN | 0.151705 |
AIRLOOP F7 S2 SUPPLY FAN | 0.152417 |
AIRLOOP F8 SW SUPPLY FAN | 0.234310 |
AIRLOOP F8 NW SUPPLY FAN | 0.211575 |
AIRLOOP F8 SE SUPPLY FAN | 0.201545 |
AIRLOOP F8 NE SUPPLY FAN | 0.167823 |
AIRLOOP F8 N1 SUPPLY FAN | 0.117125 |
AIRLOOP F8 N2 SUPPLY FAN | 0.115952 |
AIRLOOP F8 S1 SUPPLY FAN | 0.151570 |
AIRLOOP F8 S2 SUPPLY FAN | 0.152283 |
AIRLOOP F9 SW SUPPLY FAN | 0.240441 |
AIRLOOP F9 NW SUPPLY FAN | 0.217900 |
AIRLOOP F9 SE SUPPLY FAN | 0.206117 |
AIRLOOP F9 NE SUPPLY FAN | 0.169799 |
AIRLOOP F9 N1 SUPPLY FAN | 0.123027 |
AIRLOOP F9 N2 SUPPLY FAN | 0.121848 |
AIRLOOP F9 S1 SUPPLY FAN | 0.155428 |
AIRLOOP F9 S2 SUPPLY FAN | 0.156140 |
AIRLOOP T SW SUPPLY FAN | 0.291629 |
AIRLOOP T NW SUPPLY FAN | 0.263071 |
AIRLOOP T SE SUPPLY FAN | 0.252890 |
AIRLOOP T NE SUPPLY FAN | 0.202521 |
AIRLOOP T N1 SUPPLY FAN | 0.152116 |
AIRLOOP T N2 SUPPLY FAN | 0.152047 |
AIRLOOP T S1 SUPPLY FAN | 0.207642 |
AIRLOOP T S2 SUPPLY FAN | 0.208336 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.188894 | 2839.53 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.167315 | 2522.87 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.261994 | 3844.40 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.128314 | 1908.88 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.081209 | 1293.49 | 0.000028 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.079773 | 1273.15 | 0.000028 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.115615 | 1823.85 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.120461 | 1890.97 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.238219 | 3515.55 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.212404 | 3141.05 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.220624 | 3233.24 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.167452 | 2453.21 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.112139 | 1728.18 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.110887 | 1710.59 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.151285 | 2319.45 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.153147 | 2345.27 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.238548 | 3520.99 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.213965 | 3163.52 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.206113 | 3033.06 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.170031 | 2489.29 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.115643 | 1777.51 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.114408 | 1760.18 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.153635 | 2352.47 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.154519 | 2364.72 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.238428 | 3519.98 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.214389 | 3170.01 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.204571 | 3058.33 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.170493 | 2496.07 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.117102 | 1798.15 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.115879 | 1780.98 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.154154 | 2360.00 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.154892 | 2370.23 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.240527 | 3549.60 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.216949 | 3206.03 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.206836 | 3090.25 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.173056 | 2531.83 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.120337 | 1843.61 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.119123 | 1826.57 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.156647 | 2394.87 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.157363 | 2404.80 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.236448 | 3493.53 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.213143 | 3153.62 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.203134 | 3039.32 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.169340 | 2480.76 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.117434 | 1803.10 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.116236 | 1786.28 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.153056 | 2345.26 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.153769 | 2355.14 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.234730 | 3470.11 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.211724 | 3134.29 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.201730 | 3020.23 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.167975 | 2462.13 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.116694 | 1792.87 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.115509 | 1776.22 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.151705 | 2326.70 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.152417 | 2336.56 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.234310 | 3464.65 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.211575 | 3132.54 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.201545 | 3017.98 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.167823 | 2460.25 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.117125 | 1799.02 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.115952 | 1782.53 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.151570 | 2325.00 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.152283 | 2334.88 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.240441 | 3549.97 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.217900 | 3220.67 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.206117 | 3084.88 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.169799 | 2487.83 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.123027 | 1881.80 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.121848 | 1865.25 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.155428 | 2381.82 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.156140 | 2391.69 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.291629 | 4272.38 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.263071 | 3859.75 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.252890 | 3733.69 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.202521 | 2958.33 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.152116 | 2342.21 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.152047 | 2341.28 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.207642 | 3106.45 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.208336 | 3112.94 | 0.000068 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 1465.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 1470.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2103.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 1468.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 1436.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 1439.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 1461.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 1438.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1421.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1423.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1424.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1422.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1434.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1435.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1434.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1435.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1427.89 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1427.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1428.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1428.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 1486.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 1486.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 1487.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 1487.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 1522.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 1521.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 1523.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 1522.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 1558.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 1557.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 1559.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 1558.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 1671.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 1668.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 1673.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 1670.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1115.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2050.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2051.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2052.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2053.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 1493.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 1493.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 1489.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 1489.36 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.004530 | 5.10 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.004530 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.004530 | 2187.00 | 5.86 | 6659.14 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.004530 | 1155.48 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 13.22 |
February | 23.13 | 13.28 |
March | 23.04 | 12.64 |
April | 23.46 | 15.30 |
May | 23.25 | 15.56 |
June | 23.93 | 17.67 |
July | 24.19 | 19.43 |
August | 24.21 | 19.66 |
September | 24.12 | 18.47 |
October | 23.84 | 18.77 |
November | 23.42 | 14.32 |
December | 23.38 | 13.59 |
Annual Sum or Average | 23.61 | 16.01 |
Minimum of Months | 23.04 | 12.64 |
Maximum of Months | 24.21 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 13.22 |
February | 22.36 | 13.28 |
March | 22.51 | 12.64 |
April | 23.11 | 15.30 |
May | 23.14 | 15.56 |
June | 23.94 | 17.67 |
July | 24.19 | 19.43 |
August | 24.18 | 19.66 |
September | 24.01 | 18.47 |
October | 23.52 | 18.77 |
November | 22.53 | 14.32 |
December | 22.47 | 13.59 |
Annual Sum or Average | 23.20 | 16.01 |
Minimum of Months | 22.36 | 12.64 |
Maximum of Months | 24.19 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.26 | 13.22 |
February | 23.11 | 13.28 |
March | 23.09 | 12.64 |
April | 23.51 | 15.30 |
May | 23.52 | 15.56 |
June | 24.23 | 17.67 |
July | 24.39 | 19.43 |
August | 24.39 | 19.66 |
September | 24.35 | 18.47 |
October | 24.06 | 18.77 |
November | 23.46 | 14.32 |
December | 23.31 | 13.59 |
Annual Sum or Average | 23.73 | 16.01 |
Minimum of Months | 23.09 | 12.64 |
Maximum of Months | 24.39 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 13.22 |
February | 22.23 | 13.28 |
March | 22.40 | 12.64 |
April | 22.95 | 15.30 |
May | 22.95 | 15.56 |
June | 23.84 | 17.67 |
July | 24.19 | 19.43 |
August | 24.17 | 19.66 |
September | 23.91 | 18.47 |
October | 23.42 | 18.77 |
November | 22.41 | 14.32 |
December | 22.38 | 13.59 |
Annual Sum or Average | 23.10 | 16.01 |
Minimum of Months | 22.23 | 12.64 |
Maximum of Months | 24.19 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 13.22 |
February | 22.18 | 13.28 |
March | 22.28 | 12.64 |
April | 22.70 | 15.30 |
May | 22.72 | 15.56 |
June | 23.72 | 17.67 |
July | 24.11 | 19.43 |
August | 24.10 | 19.66 |
September | 23.82 | 18.47 |
October | 23.32 | 18.77 |
November | 22.34 | 14.32 |
December | 22.31 | 13.59 |
Annual Sum or Average | 22.99 | 16.01 |
Minimum of Months | 22.18 | 12.64 |
Maximum of Months | 24.11 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 13.22 |
February | 22.17 | 13.28 |
March | 22.27 | 12.64 |
April | 22.69 | 15.30 |
May | 22.70 | 15.56 |
June | 23.71 | 17.67 |
July | 24.11 | 19.43 |
August | 24.10 | 19.66 |
September | 23.81 | 18.47 |
October | 23.31 | 18.77 |
November | 22.33 | 14.32 |
December | 22.30 | 13.59 |
Annual Sum or Average | 22.98 | 16.01 |
Minimum of Months | 22.17 | 12.64 |
Maximum of Months | 24.11 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 13.22 |
February | 23.17 | 13.28 |
March | 23.01 | 12.64 |
April | 23.25 | 15.30 |
May | 22.95 | 15.56 |
June | 23.78 | 17.67 |
July | 24.12 | 19.43 |
August | 24.16 | 19.66 |
September | 24.08 | 18.47 |
October | 23.82 | 18.77 |
November | 23.45 | 14.32 |
December | 23.48 | 13.59 |
Annual Sum or Average | 23.56 | 16.01 |
Minimum of Months | 22.95 | 12.64 |
Maximum of Months | 24.16 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 13.22 |
February | 23.20 | 13.28 |
March | 23.04 | 12.64 |
April | 23.29 | 15.30 |
May | 22.99 | 15.56 |
June | 23.80 | 17.67 |
July | 24.13 | 19.43 |
August | 24.17 | 19.66 |
September | 24.09 | 18.47 |
October | 23.84 | 18.77 |
November | 23.48 | 14.32 |
December | 23.50 | 13.59 |
Annual Sum or Average | 23.58 | 16.01 |
Minimum of Months | 22.99 | 12.64 |
Maximum of Months | 24.17 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 13.22 |
February | 21.13 | 13.28 |
March | 21.06 | 12.64 |
April | 22.04 | 15.30 |
May | 22.09 | 15.56 |
June | 23.50 | 17.67 |
July | 24.27 | 19.43 |
August | 24.35 | 19.66 |
September | 23.84 | 18.47 |
October | 23.28 | 18.77 |
November | 21.67 | 14.32 |
December | 21.43 | 13.59 |
Annual Sum or Average | 22.50 | 16.01 |
Minimum of Months | 21.06 | 12.64 |
Maximum of Months | 24.35 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.22 |
February | 23.95 | 13.28 |
March | 23.90 | 12.64 |
April | 24.18 | 15.30 |
May | 24.03 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.32 | 19.66 |
September | 24.28 | 18.47 |
October | 24.26 | 18.77 |
November | 24.16 | 14.32 |
December | 24.12 | 13.59 |
Annual Sum or Average | 24.15 | 16.01 |
Minimum of Months | 23.90 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 13.22 |
February | 23.21 | 13.28 |
March | 23.37 | 12.64 |
April | 23.95 | 15.30 |
May | 23.95 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.19 | 18.47 |
October | 24.05 | 18.77 |
November | 23.37 | 14.32 |
December | 23.25 | 13.59 |
Annual Sum or Average | 23.77 | 16.01 |
Minimum of Months | 23.05 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.09 | 13.22 |
February | 23.95 | 13.28 |
March | 23.93 | 12.64 |
April | 24.20 | 15.30 |
May | 24.06 | 15.56 |
June | 24.19 | 17.67 |
July | 24.32 | 19.43 |
August | 24.33 | 19.66 |
September | 24.28 | 18.47 |
October | 24.28 | 18.77 |
November | 24.16 | 14.32 |
December | 24.13 | 13.59 |
Annual Sum or Average | 24.16 | 16.01 |
Minimum of Months | 23.93 | 12.64 |
Maximum of Months | 24.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 13.22 |
February | 22.99 | 13.28 |
March | 23.22 | 12.64 |
April | 23.83 | 15.30 |
May | 23.83 | 15.56 |
June | 24.12 | 17.67 |
July | 24.30 | 19.43 |
August | 24.30 | 19.66 |
September | 24.14 | 18.47 |
October | 23.97 | 18.77 |
November | 23.18 | 14.32 |
December | 23.11 | 13.59 |
Annual Sum or Average | 23.67 | 16.01 |
Minimum of Months | 22.96 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 13.22 |
February | 23.04 | 13.28 |
March | 23.21 | 12.64 |
April | 23.68 | 15.30 |
May | 23.68 | 15.56 |
June | 24.05 | 17.67 |
July | 24.26 | 19.43 |
August | 24.25 | 19.66 |
September | 24.07 | 18.47 |
October | 23.93 | 18.77 |
November | 23.18 | 14.32 |
December | 23.15 | 13.59 |
Annual Sum or Average | 23.62 | 16.01 |
Minimum of Months | 22.95 | 12.64 |
Maximum of Months | 24.26 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 13.22 |
February | 23.02 | 13.28 |
March | 23.19 | 12.64 |
April | 23.66 | 15.30 |
May | 23.66 | 15.56 |
June | 24.05 | 17.67 |
July | 24.25 | 19.43 |
August | 24.24 | 19.66 |
September | 24.06 | 18.47 |
October | 23.92 | 18.77 |
November | 23.16 | 14.32 |
December | 23.13 | 13.59 |
Annual Sum or Average | 23.61 | 16.01 |
Minimum of Months | 22.95 | 12.64 |
Maximum of Months | 24.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 13.22 |
February | 24.03 | 13.28 |
March | 23.97 | 12.64 |
April | 24.10 | 15.30 |
May | 23.86 | 15.56 |
June | 24.08 | 17.67 |
July | 24.26 | 19.43 |
August | 24.28 | 19.66 |
September | 24.24 | 18.47 |
October | 24.28 | 18.77 |
November | 24.19 | 14.32 |
December | 24.21 | 13.59 |
Annual Sum or Average | 24.14 | 16.01 |
Minimum of Months | 23.86 | 12.64 |
Maximum of Months | 24.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 13.22 |
February | 24.03 | 13.28 |
March | 23.97 | 12.64 |
April | 24.11 | 15.30 |
May | 23.87 | 15.56 |
June | 24.08 | 17.67 |
July | 24.26 | 19.43 |
August | 24.29 | 19.66 |
September | 24.24 | 18.47 |
October | 24.28 | 18.77 |
November | 24.20 | 14.32 |
December | 24.22 | 13.59 |
Annual Sum or Average | 24.14 | 16.01 |
Minimum of Months | 23.87 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.59 | 13.22 |
February | 24.52 | 13.28 |
March | 24.57 | 12.64 |
April | 25.15 | 15.30 |
May | 25.09 | 15.56 |
June | 25.67 | 17.67 |
July | 26.05 | 19.43 |
August | 26.07 | 19.66 |
September | 25.82 | 18.47 |
October | 25.58 | 18.77 |
November | 24.84 | 14.32 |
December | 24.73 | 13.59 |
Annual Sum or Average | 25.23 | 16.01 |
Minimum of Months | 24.52 | 12.64 |
Maximum of Months | 26.07 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 13.22 |
February | 24.07 | 13.28 |
March | 24.04 | 12.64 |
April | 24.25 | 15.30 |
May | 24.12 | 15.56 |
June | 24.19 | 17.67 |
July | 24.31 | 19.43 |
August | 24.32 | 19.66 |
September | 24.28 | 18.47 |
October | 24.29 | 18.77 |
November | 24.24 | 14.32 |
December | 24.21 | 13.59 |
Annual Sum or Average | 24.21 | 16.01 |
Minimum of Months | 24.04 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 13.22 |
February | 23.46 | 13.28 |
March | 23.62 | 12.64 |
April | 24.07 | 15.30 |
May | 24.06 | 15.56 |
June | 24.19 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.20 | 18.47 |
October | 24.12 | 18.77 |
November | 23.61 | 14.32 |
December | 23.51 | 13.59 |
Annual Sum or Average | 23.90 | 16.01 |
Minimum of Months | 23.28 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 13.22 |
February | 24.03 | 13.28 |
March | 24.01 | 12.64 |
April | 24.24 | 15.30 |
May | 24.09 | 15.56 |
June | 24.17 | 17.67 |
July | 24.31 | 19.43 |
August | 24.33 | 19.66 |
September | 24.28 | 18.47 |
October | 24.30 | 18.77 |
November | 24.21 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.19 | 16.01 |
Minimum of Months | 24.01 | 12.64 |
Maximum of Months | 24.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 13.22 |
February | 23.26 | 13.28 |
March | 23.48 | 12.64 |
April | 23.99 | 15.30 |
May | 23.98 | 15.56 |
June | 24.15 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.15 | 18.47 |
October | 24.07 | 18.77 |
November | 23.42 | 14.32 |
December | 23.37 | 13.59 |
Annual Sum or Average | 23.81 | 16.01 |
Minimum of Months | 23.20 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 13.22 |
February | 23.38 | 13.28 |
March | 23.56 | 12.64 |
April | 23.90 | 15.30 |
May | 23.88 | 15.56 |
June | 24.09 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.10 | 18.47 |
October | 24.05 | 18.77 |
November | 23.48 | 14.32 |
December | 23.48 | 13.59 |
Annual Sum or Average | 23.81 | 16.01 |
Minimum of Months | 23.25 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.24 | 13.22 |
February | 23.36 | 13.28 |
March | 23.54 | 12.64 |
April | 23.89 | 15.30 |
May | 23.87 | 15.56 |
June | 24.08 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.09 | 18.47 |
October | 24.04 | 18.77 |
November | 23.46 | 14.32 |
December | 23.47 | 13.59 |
Annual Sum or Average | 23.80 | 16.01 |
Minimum of Months | 23.24 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.28 | 13.22 |
February | 24.16 | 13.28 |
March | 24.13 | 12.64 |
April | 24.20 | 15.30 |
May | 24.01 | 15.56 |
June | 24.10 | 17.67 |
July | 24.27 | 19.43 |
August | 24.29 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.28 | 14.32 |
December | 24.30 | 13.59 |
Annual Sum or Average | 24.22 | 16.01 |
Minimum of Months | 24.01 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.28 | 13.22 |
February | 24.16 | 13.28 |
March | 24.13 | 12.64 |
April | 24.20 | 15.30 |
May | 24.01 | 15.56 |
June | 24.10 | 17.67 |
July | 24.27 | 19.43 |
August | 24.29 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.28 | 14.32 |
December | 24.30 | 13.59 |
Annual Sum or Average | 24.22 | 16.01 |
Minimum of Months | 24.01 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.11 | 13.22 |
February | 25.06 | 13.28 |
March | 25.14 | 12.64 |
April | 25.64 | 15.30 |
May | 25.56 | 15.56 |
June | 25.89 | 17.67 |
July | 26.22 | 19.43 |
August | 26.24 | 19.66 |
September | 26.01 | 18.47 |
October | 25.93 | 18.77 |
November | 25.33 | 14.32 |
December | 25.26 | 13.59 |
Annual Sum or Average | 25.62 | 16.01 |
Minimum of Months | 25.06 | 12.64 |
Maximum of Months | 26.24 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.20 | 13.22 |
February | 24.09 | 13.28 |
March | 24.06 | 12.64 |
April | 24.24 | 15.30 |
May | 24.12 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.32 | 19.66 |
September | 24.28 | 18.47 |
October | 24.29 | 18.77 |
November | 24.24 | 14.32 |
December | 24.22 | 13.59 |
Annual Sum or Average | 24.21 | 16.01 |
Minimum of Months | 24.06 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 13.22 |
February | 23.52 | 13.28 |
March | 23.67 | 12.64 |
April | 24.08 | 15.30 |
May | 24.07 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.20 | 18.47 |
October | 24.13 | 18.77 |
November | 23.66 | 14.32 |
December | 23.57 | 13.59 |
Annual Sum or Average | 23.92 | 16.01 |
Minimum of Months | 23.34 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 13.22 |
February | 24.03 | 13.28 |
March | 24.02 | 12.64 |
April | 24.23 | 15.30 |
May | 24.08 | 15.56 |
June | 24.15 | 17.67 |
July | 24.31 | 19.43 |
August | 24.32 | 19.66 |
September | 24.27 | 18.47 |
October | 24.30 | 18.77 |
November | 24.20 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.19 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.27 | 13.22 |
February | 23.32 | 13.28 |
March | 23.54 | 12.64 |
April | 24.01 | 15.30 |
May | 23.99 | 15.56 |
June | 24.14 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.15 | 18.47 |
October | 24.08 | 18.77 |
November | 23.48 | 14.32 |
December | 23.44 | 13.59 |
Annual Sum or Average | 23.84 | 16.01 |
Minimum of Months | 23.27 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 13.22 |
February | 23.49 | 13.28 |
March | 23.67 | 12.64 |
April | 23.94 | 15.30 |
May | 23.91 | 15.56 |
June | 24.08 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.09 | 18.47 |
October | 24.06 | 18.77 |
November | 23.57 | 14.32 |
December | 23.59 | 13.59 |
Annual Sum or Average | 23.86 | 16.01 |
Minimum of Months | 23.35 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 13.22 |
February | 23.46 | 13.28 |
March | 23.65 | 12.64 |
April | 23.93 | 15.30 |
May | 23.90 | 15.56 |
June | 24.08 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.09 | 18.47 |
October | 24.06 | 18.77 |
November | 23.55 | 14.32 |
December | 23.57 | 13.59 |
Annual Sum or Average | 23.85 | 16.01 |
Minimum of Months | 23.35 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.29 | 13.22 |
February | 24.18 | 13.28 |
March | 24.16 | 12.64 |
April | 24.21 | 15.30 |
May | 24.02 | 15.56 |
June | 24.09 | 17.67 |
July | 24.27 | 19.43 |
August | 24.29 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.29 | 14.32 |
December | 24.31 | 13.59 |
Annual Sum or Average | 24.22 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.29 | 13.22 |
February | 24.18 | 13.28 |
March | 24.16 | 12.64 |
April | 24.21 | 15.30 |
May | 24.02 | 15.56 |
June | 24.09 | 17.67 |
July | 24.27 | 19.43 |
August | 24.29 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.28 | 14.32 |
December | 24.31 | 13.59 |
Annual Sum or Average | 24.22 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.32 | 13.22 |
February | 25.26 | 13.28 |
March | 25.35 | 12.64 |
April | 25.81 | 15.30 |
May | 25.72 | 15.56 |
June | 26.00 | 17.67 |
July | 26.32 | 19.43 |
August | 26.33 | 19.66 |
September | 26.11 | 18.47 |
October | 26.07 | 18.77 |
November | 25.52 | 14.32 |
December | 25.46 | 13.59 |
Annual Sum or Average | 25.78 | 16.01 |
Minimum of Months | 25.26 | 12.64 |
Maximum of Months | 26.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.20 | 13.22 |
February | 24.09 | 13.28 |
March | 24.06 | 12.64 |
April | 24.24 | 15.30 |
May | 24.11 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.32 | 19.66 |
September | 24.28 | 18.47 |
October | 24.28 | 18.77 |
November | 24.24 | 14.32 |
December | 24.22 | 13.59 |
Annual Sum or Average | 24.21 | 16.01 |
Minimum of Months | 24.06 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 13.22 |
February | 23.53 | 13.28 |
March | 23.69 | 12.64 |
April | 24.08 | 15.30 |
May | 24.06 | 15.56 |
June | 24.18 | 17.67 |
July | 24.31 | 19.43 |
August | 24.31 | 19.66 |
September | 24.20 | 18.47 |
October | 24.13 | 18.77 |
November | 23.68 | 14.32 |
December | 23.60 | 13.59 |
Annual Sum or Average | 23.93 | 16.01 |
Minimum of Months | 23.38 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 13.22 |
February | 24.03 | 13.28 |
March | 24.02 | 12.64 |
April | 24.22 | 15.30 |
May | 24.06 | 15.56 |
June | 24.14 | 17.67 |
July | 24.31 | 19.43 |
August | 24.33 | 19.66 |
September | 24.27 | 18.47 |
October | 24.29 | 18.77 |
November | 24.20 | 14.32 |
December | 24.20 | 13.59 |
Annual Sum or Average | 24.19 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 13.22 |
February | 23.35 | 13.28 |
March | 23.56 | 12.64 |
April | 24.01 | 15.30 |
May | 23.98 | 15.56 |
June | 24.13 | 17.67 |
July | 24.31 | 19.43 |
August | 24.30 | 19.66 |
September | 24.15 | 18.47 |
October | 24.08 | 18.77 |
November | 23.51 | 14.32 |
December | 23.47 | 13.59 |
Annual Sum or Average | 23.85 | 16.01 |
Minimum of Months | 23.30 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 13.22 |
February | 23.54 | 13.28 |
March | 23.71 | 12.64 |
April | 23.95 | 15.30 |
May | 23.91 | 15.56 |
June | 24.08 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.10 | 18.47 |
October | 24.08 | 18.77 |
November | 23.61 | 14.32 |
December | 23.65 | 13.59 |
Annual Sum or Average | 23.88 | 16.01 |
Minimum of Months | 23.41 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 13.22 |
February | 23.51 | 13.28 |
March | 23.70 | 12.64 |
April | 23.94 | 15.30 |
May | 23.90 | 15.56 |
June | 24.08 | 17.67 |
July | 24.27 | 19.43 |
August | 24.26 | 19.66 |
September | 24.09 | 18.47 |
October | 24.07 | 18.77 |
November | 23.59 | 14.32 |
December | 23.63 | 13.59 |
Annual Sum or Average | 23.87 | 16.01 |
Minimum of Months | 23.41 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.30 | 13.22 |
February | 24.18 | 13.28 |
March | 24.17 | 12.64 |
April | 24.20 | 15.30 |
May | 24.02 | 15.56 |
June | 24.09 | 17.67 |
July | 24.27 | 19.43 |
August | 24.30 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.29 | 14.32 |
December | 24.32 | 13.59 |
Annual Sum or Average | 24.23 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.30 | 13.22 |
February | 24.18 | 13.28 |
March | 24.17 | 12.64 |
April | 24.20 | 15.30 |
May | 24.02 | 15.56 |
June | 24.09 | 17.67 |
July | 24.27 | 19.43 |
August | 24.30 | 19.66 |
September | 24.25 | 18.47 |
October | 24.32 | 18.77 |
November | 24.29 | 14.32 |
December | 24.31 | 13.59 |
Annual Sum or Average | 24.22 | 16.01 |
Minimum of Months | 24.02 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.97 | 13.22 |
February | 25.89 | 13.28 |
March | 25.98 | 12.64 |
April | 26.42 | 15.30 |
May | 26.32 | 15.56 |
June | 26.59 | 17.67 |
July | 26.92 | 19.43 |
August | 26.94 | 19.66 |
September | 26.72 | 18.47 |
October | 26.68 | 18.77 |
November | 26.16 | 14.32 |
December | 26.11 | 13.59 |
Annual Sum or Average | 26.39 | 16.01 |
Minimum of Months | 25.89 | 12.64 |
Maximum of Months | 26.94 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 13.22 |
February | 24.02 | 13.28 |
March | 24.00 | 12.64 |
April | 24.20 | 15.30 |
May | 24.05 | 15.56 |
June | 24.15 | 17.67 |
July | 24.30 | 19.43 |
August | 24.31 | 19.66 |
September | 24.26 | 18.47 |
October | 24.26 | 18.77 |
November | 24.20 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.18 | 16.01 |
Minimum of Months | 24.00 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.27 | 13.22 |
February | 23.40 | 13.28 |
March | 23.57 | 12.64 |
April | 24.01 | 15.30 |
May | 23.99 | 15.56 |
June | 24.15 | 17.67 |
July | 24.30 | 19.43 |
August | 24.29 | 19.66 |
September | 24.17 | 18.47 |
October | 24.08 | 18.77 |
November | 23.57 | 14.32 |
December | 23.50 | 13.59 |
Annual Sum or Average | 23.86 | 16.01 |
Minimum of Months | 23.27 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 13.22 |
February | 23.96 | 13.28 |
March | 23.95 | 12.64 |
April | 24.18 | 15.30 |
May | 23.99 | 15.56 |
June | 24.10 | 17.67 |
July | 24.30 | 19.43 |
August | 24.32 | 19.66 |
September | 24.25 | 18.47 |
October | 24.27 | 18.77 |
November | 24.16 | 14.32 |
December | 24.16 | 13.59 |
Annual Sum or Average | 24.15 | 16.01 |
Minimum of Months | 23.95 | 12.64 |
Maximum of Months | 24.32 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 13.22 |
February | 23.20 | 13.28 |
March | 23.43 | 12.64 |
April | 23.93 | 15.30 |
May | 23.90 | 15.56 |
June | 24.09 | 17.67 |
July | 24.30 | 19.43 |
August | 24.29 | 19.66 |
September | 24.12 | 18.47 |
October | 24.03 | 18.77 |
November | 23.39 | 14.32 |
December | 23.36 | 13.59 |
Annual Sum or Average | 23.77 | 16.01 |
Minimum of Months | 23.20 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 13.22 |
February | 23.40 | 13.28 |
March | 23.60 | 12.64 |
April | 23.87 | 15.30 |
May | 23.82 | 15.56 |
June | 24.03 | 17.67 |
July | 24.25 | 19.43 |
August | 24.24 | 19.66 |
September | 24.06 | 18.47 |
October | 24.02 | 18.77 |
November | 23.51 | 14.32 |
December | 23.54 | 13.59 |
Annual Sum or Average | 23.81 | 16.01 |
Minimum of Months | 23.31 | 12.64 |
Maximum of Months | 24.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 13.22 |
February | 23.38 | 13.28 |
March | 23.58 | 12.64 |
April | 23.86 | 15.30 |
May | 23.81 | 15.56 |
June | 24.03 | 17.67 |
July | 24.25 | 19.43 |
August | 24.24 | 19.66 |
September | 24.05 | 18.47 |
October | 24.02 | 18.77 |
November | 23.48 | 14.32 |
December | 23.53 | 13.59 |
Annual Sum or Average | 23.80 | 16.01 |
Minimum of Months | 23.30 | 12.64 |
Maximum of Months | 24.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.27 | 13.22 |
February | 24.13 | 13.28 |
March | 24.12 | 12.64 |
April | 24.16 | 15.30 |
May | 23.94 | 15.56 |
June | 24.05 | 17.67 |
July | 24.25 | 19.43 |
August | 24.28 | 19.66 |
September | 24.23 | 18.47 |
October | 24.30 | 18.77 |
November | 24.26 | 14.32 |
December | 24.29 | 13.59 |
Annual Sum or Average | 24.19 | 16.01 |
Minimum of Months | 23.94 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.27 | 13.22 |
February | 24.13 | 13.28 |
March | 24.12 | 12.64 |
April | 24.16 | 15.30 |
May | 23.94 | 15.56 |
June | 24.05 | 17.67 |
July | 24.25 | 19.43 |
August | 24.28 | 19.66 |
September | 24.23 | 18.47 |
October | 24.30 | 18.77 |
November | 24.26 | 14.32 |
December | 24.29 | 13.59 |
Annual Sum or Average | 24.19 | 16.01 |
Minimum of Months | 23.94 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.29 | 13.22 |
February | 25.19 | 13.28 |
March | 25.28 | 12.64 |
April | 25.74 | 15.30 |
May | 25.63 | 15.56 |
June | 25.93 | 17.67 |
July | 26.29 | 19.43 |
August | 26.31 | 19.66 |
September | 26.07 | 18.47 |
October | 26.03 | 18.77 |
November | 25.47 | 14.32 |
December | 25.43 | 13.59 |
Annual Sum or Average | 25.73 | 16.01 |
Minimum of Months | 25.19 | 12.64 |
Maximum of Months | 26.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 13.22 |
February | 23.97 | 13.28 |
March | 23.94 | 12.64 |
April | 24.17 | 15.30 |
May | 24.00 | 15.56 |
June | 24.12 | 17.67 |
July | 24.29 | 19.43 |
August | 24.31 | 19.66 |
September | 24.25 | 18.47 |
October | 24.24 | 18.77 |
November | 24.17 | 14.32 |
December | 24.16 | 13.59 |
Annual Sum or Average | 24.15 | 16.01 |
Minimum of Months | 23.94 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 13.22 |
February | 23.28 | 13.28 |
March | 23.47 | 12.64 |
April | 23.96 | 15.30 |
May | 23.93 | 15.56 |
June | 24.12 | 17.67 |
July | 24.29 | 19.43 |
August | 24.28 | 19.66 |
September | 24.16 | 18.47 |
October | 24.05 | 18.77 |
November | 23.48 | 14.32 |
December | 23.41 | 13.59 |
Annual Sum or Average | 23.80 | 16.01 |
Minimum of Months | 23.18 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.11 | 13.22 |
February | 23.91 | 13.28 |
March | 23.90 | 12.64 |
April | 24.14 | 15.30 |
May | 23.93 | 15.56 |
June | 24.07 | 17.67 |
July | 24.29 | 19.43 |
August | 24.31 | 19.66 |
September | 24.24 | 18.47 |
October | 24.25 | 18.77 |
November | 24.13 | 14.32 |
December | 24.13 | 13.59 |
Annual Sum or Average | 24.12 | 16.01 |
Minimum of Months | 23.90 | 12.64 |
Maximum of Months | 24.31 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 13.22 |
February | 23.07 | 13.28 |
March | 23.32 | 12.64 |
April | 23.87 | 15.30 |
May | 23.83 | 15.56 |
June | 24.05 | 17.67 |
July | 24.29 | 19.43 |
August | 24.28 | 19.66 |
September | 24.09 | 18.47 |
October | 23.99 | 18.77 |
November | 23.29 | 14.32 |
December | 23.27 | 13.59 |
Annual Sum or Average | 23.71 | 16.01 |
Minimum of Months | 23.07 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 13.22 |
February | 23.29 | 13.28 |
March | 23.49 | 12.64 |
April | 23.81 | 15.30 |
May | 23.75 | 15.56 |
June | 23.99 | 17.67 |
July | 24.24 | 19.43 |
August | 24.23 | 19.66 |
September | 24.03 | 18.47 |
October | 23.98 | 18.77 |
November | 23.41 | 14.32 |
December | 23.45 | 13.59 |
Annual Sum or Average | 23.75 | 16.01 |
Minimum of Months | 23.22 | 12.64 |
Maximum of Months | 24.24 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 13.22 |
February | 23.26 | 13.28 |
March | 23.47 | 12.64 |
April | 23.80 | 15.30 |
May | 23.74 | 15.56 |
June | 23.99 | 17.67 |
July | 24.24 | 19.43 |
August | 24.23 | 19.66 |
September | 24.02 | 18.47 |
October | 23.98 | 18.77 |
November | 23.39 | 14.32 |
December | 23.44 | 13.59 |
Annual Sum or Average | 23.73 | 16.01 |
Minimum of Months | 23.21 | 12.64 |
Maximum of Months | 24.24 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.25 | 13.22 |
February | 24.09 | 13.28 |
March | 24.08 | 12.64 |
April | 24.13 | 15.30 |
May | 23.88 | 15.56 |
June | 24.01 | 17.67 |
July | 24.24 | 19.43 |
August | 24.27 | 19.66 |
September | 24.22 | 18.47 |
October | 24.28 | 18.77 |
November | 24.23 | 14.32 |
December | 24.27 | 13.59 |
Annual Sum or Average | 24.16 | 16.01 |
Minimum of Months | 23.88 | 12.64 |
Maximum of Months | 24.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.25 | 13.22 |
February | 24.09 | 13.28 |
March | 24.07 | 12.64 |
April | 24.12 | 15.30 |
May | 23.88 | 15.56 |
June | 24.01 | 17.67 |
July | 24.24 | 19.43 |
August | 24.27 | 19.66 |
September | 24.22 | 18.47 |
October | 24.28 | 18.77 |
November | 24.23 | 14.32 |
December | 24.27 | 13.59 |
Annual Sum or Average | 24.16 | 16.01 |
Minimum of Months | 23.88 | 12.64 |
Maximum of Months | 24.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.13 | 13.22 |
February | 25.01 | 13.28 |
March | 25.11 | 12.64 |
April | 25.60 | 15.30 |
May | 25.48 | 15.56 |
June | 25.81 | 17.67 |
July | 26.20 | 19.43 |
August | 26.21 | 19.66 |
September | 25.96 | 18.47 |
October | 25.91 | 18.77 |
November | 25.31 | 14.32 |
December | 25.27 | 13.59 |
Annual Sum or Average | 25.59 | 16.01 |
Minimum of Months | 25.01 | 12.64 |
Maximum of Months | 26.21 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.11 | 13.22 |
February | 23.91 | 13.28 |
March | 23.89 | 12.64 |
April | 24.13 | 15.30 |
May | 23.95 | 15.56 |
June | 24.10 | 17.67 |
July | 24.29 | 19.43 |
August | 24.30 | 19.66 |
September | 24.24 | 18.47 |
October | 24.22 | 18.77 |
November | 24.14 | 14.32 |
December | 24.13 | 13.59 |
Annual Sum or Average | 24.12 | 16.01 |
Minimum of Months | 23.89 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.10 | 13.22 |
February | 23.17 | 13.28 |
March | 23.37 | 12.64 |
April | 23.91 | 15.30 |
May | 23.88 | 15.56 |
June | 24.09 | 17.67 |
July | 24.29 | 19.43 |
August | 24.28 | 19.66 |
September | 24.14 | 18.47 |
October | 24.01 | 18.77 |
November | 23.39 | 14.32 |
December | 23.32 | 13.59 |
Annual Sum or Average | 23.75 | 16.01 |
Minimum of Months | 23.10 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.22 |
February | 23.85 | 13.28 |
March | 23.84 | 12.64 |
April | 24.10 | 15.30 |
May | 23.88 | 15.56 |
June | 24.04 | 17.67 |
July | 24.28 | 19.43 |
August | 24.30 | 19.66 |
September | 24.23 | 18.47 |
October | 24.23 | 18.77 |
November | 24.10 | 14.32 |
December | 24.10 | 13.59 |
Annual Sum or Average | 24.09 | 16.01 |
Minimum of Months | 23.84 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.03 | 13.22 |
February | 22.96 | 13.28 |
March | 23.22 | 12.64 |
April | 23.81 | 15.30 |
May | 23.76 | 15.56 |
June | 24.02 | 17.67 |
July | 24.29 | 19.43 |
August | 24.28 | 19.66 |
September | 24.07 | 18.47 |
October | 23.95 | 18.77 |
November | 23.19 | 14.32 |
December | 23.18 | 13.59 |
Annual Sum or Average | 23.65 | 16.01 |
Minimum of Months | 22.96 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.22 |
February | 23.18 | 13.28 |
March | 23.38 | 12.64 |
April | 23.75 | 15.30 |
May | 23.69 | 15.56 |
June | 23.96 | 17.67 |
July | 24.24 | 19.43 |
August | 24.23 | 19.66 |
September | 24.01 | 18.47 |
October | 23.95 | 18.77 |
November | 23.32 | 14.32 |
December | 23.36 | 13.59 |
Annual Sum or Average | 23.69 | 16.01 |
Minimum of Months | 23.13 | 12.64 |
Maximum of Months | 24.24 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.22 |
February | 23.15 | 13.28 |
March | 23.36 | 12.64 |
April | 23.74 | 15.30 |
May | 23.68 | 15.56 |
June | 23.95 | 17.67 |
July | 24.24 | 19.43 |
August | 24.23 | 19.66 |
September | 24.00 | 18.47 |
October | 23.94 | 18.77 |
November | 23.30 | 14.32 |
December | 23.34 | 13.59 |
Annual Sum or Average | 23.67 | 16.01 |
Minimum of Months | 23.13 | 12.64 |
Maximum of Months | 24.24 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.23 | 13.22 |
February | 24.05 | 13.28 |
March | 24.03 | 12.64 |
April | 24.09 | 15.30 |
May | 23.83 | 15.56 |
June | 23.98 | 17.67 |
July | 24.24 | 19.43 |
August | 24.27 | 19.66 |
September | 24.21 | 18.47 |
October | 24.26 | 18.77 |
November | 24.21 | 14.32 |
December | 24.25 | 13.59 |
Annual Sum or Average | 24.14 | 16.01 |
Minimum of Months | 23.83 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.23 | 13.22 |
February | 24.05 | 13.28 |
March | 24.02 | 12.64 |
April | 24.09 | 15.30 |
May | 23.83 | 15.56 |
June | 23.98 | 17.67 |
July | 24.23 | 19.43 |
August | 24.27 | 19.66 |
September | 24.21 | 18.47 |
October | 24.26 | 18.77 |
November | 24.21 | 14.32 |
December | 24.25 | 13.59 |
Annual Sum or Average | 24.14 | 16.01 |
Minimum of Months | 23.83 | 12.64 |
Maximum of Months | 24.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.03 | 13.22 |
February | 24.89 | 13.28 |
March | 24.98 | 12.64 |
April | 25.52 | 15.30 |
May | 25.39 | 15.56 |
June | 25.76 | 17.67 |
July | 26.18 | 19.43 |
August | 26.19 | 19.66 |
September | 25.93 | 18.47 |
October | 25.85 | 18.77 |
November | 25.21 | 14.32 |
December | 25.17 | 13.59 |
Annual Sum or Average | 25.51 | 16.01 |
Minimum of Months | 24.89 | 12.64 |
Maximum of Months | 26.19 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 13.22 |
February | 23.81 | 13.28 |
March | 23.78 | 12.64 |
April | 24.08 | 15.30 |
May | 23.90 | 15.56 |
June | 24.07 | 17.67 |
July | 24.28 | 19.43 |
August | 24.30 | 19.66 |
September | 24.23 | 18.47 |
October | 24.19 | 18.77 |
November | 24.08 | 14.32 |
December | 24.06 | 13.59 |
Annual Sum or Average | 24.07 | 16.01 |
Minimum of Months | 23.78 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 13.22 |
February | 23.03 | 13.28 |
March | 23.24 | 12.64 |
April | 23.85 | 15.30 |
May | 23.82 | 15.56 |
June | 24.07 | 17.67 |
July | 24.29 | 19.43 |
August | 24.27 | 19.66 |
September | 24.13 | 18.47 |
October | 23.97 | 18.77 |
November | 23.26 | 14.32 |
December | 23.19 | 13.59 |
Annual Sum or Average | 23.68 | 16.01 |
Minimum of Months | 23.00 | 12.64 |
Maximum of Months | 24.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.00 | 13.22 |
February | 23.74 | 13.28 |
March | 23.73 | 12.64 |
April | 24.05 | 15.30 |
May | 23.82 | 15.56 |
June | 24.01 | 17.67 |
July | 24.28 | 19.43 |
August | 24.30 | 19.66 |
September | 24.22 | 18.47 |
October | 24.19 | 18.77 |
November | 24.03 | 14.32 |
December | 24.02 | 13.59 |
Annual Sum or Average | 24.03 | 16.01 |
Minimum of Months | 23.73 | 12.64 |
Maximum of Months | 24.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | 13.22 |
February | 22.81 | 13.28 |
March | 23.09 | 12.64 |
April | 23.74 | 15.30 |
May | 23.69 | 15.56 |
June | 23.99 | 17.67 |
July | 24.28 | 19.43 |
August | 24.27 | 19.66 |
September | 24.05 | 18.47 |
October | 23.89 | 18.77 |
November | 23.06 | 14.32 |
December | 23.04 | 13.59 |
Annual Sum or Average | 23.57 | 16.01 |
Minimum of Months | 22.81 | 12.64 |
Maximum of Months | 24.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.22 |
February | 23.03 | 13.28 |
March | 23.24 | 12.64 |
April | 23.69 | 15.30 |
May | 23.62 | 15.56 |
June | 23.93 | 17.67 |
July | 24.23 | 19.43 |
August | 24.22 | 19.66 |
September | 23.99 | 18.47 |
October | 23.90 | 18.77 |
November | 23.19 | 14.32 |
December | 23.20 | 13.59 |
Annual Sum or Average | 23.61 | 16.01 |
Minimum of Months | 23.01 | 12.64 |
Maximum of Months | 24.23 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 13.22 |
February | 23.01 | 13.28 |
March | 23.22 | 12.64 |
April | 23.68 | 15.30 |
May | 23.61 | 15.56 |
June | 23.92 | 17.67 |
July | 24.23 | 19.43 |
August | 24.22 | 19.66 |
September | 23.98 | 18.47 |
October | 23.89 | 18.77 |
November | 23.17 | 14.32 |
December | 23.18 | 13.59 |
Annual Sum or Average | 23.60 | 16.01 |
Minimum of Months | 23.00 | 12.64 |
Maximum of Months | 24.23 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 13.22 |
February | 23.96 | 13.28 |
March | 23.93 | 12.64 |
April | 24.04 | 15.30 |
May | 23.77 | 15.56 |
June | 23.96 | 17.67 |
July | 24.23 | 19.43 |
August | 24.26 | 19.66 |
September | 24.20 | 18.47 |
October | 24.23 | 18.77 |
November | 24.15 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.09 | 16.01 |
Minimum of Months | 23.77 | 12.64 |
Maximum of Months | 24.26 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 13.22 |
February | 23.96 | 13.28 |
March | 23.93 | 12.64 |
April | 24.04 | 15.30 |
May | 23.77 | 15.56 |
June | 23.95 | 17.67 |
July | 24.23 | 19.43 |
August | 24.26 | 19.66 |
September | 24.20 | 18.47 |
October | 24.23 | 18.77 |
November | 24.15 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.09 | 16.01 |
Minimum of Months | 23.77 | 12.64 |
Maximum of Months | 24.26 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.87 | 13.22 |
February | 24.71 | 13.28 |
March | 24.82 | 12.64 |
April | 25.44 | 15.30 |
May | 25.32 | 15.56 |
June | 25.74 | 17.67 |
July | 26.21 | 19.43 |
August | 26.21 | 19.66 |
September | 25.91 | 18.47 |
October | 25.80 | 18.77 |
November | 25.06 | 14.32 |
December | 24.99 | 13.59 |
Annual Sum or Average | 25.43 | 16.01 |
Minimum of Months | 24.71 | 12.64 |
Maximum of Months | 26.21 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 13.22 |
February | 23.41 | 13.28 |
March | 23.42 | 12.64 |
April | 23.85 | 15.30 |
May | 23.67 | 15.56 |
June | 23.94 | 17.67 |
July | 24.21 | 19.43 |
August | 24.23 | 19.66 |
September | 24.12 | 18.47 |
October | 23.99 | 18.77 |
November | 23.70 | 14.32 |
December | 23.61 | 13.59 |
Annual Sum or Average | 23.82 | 16.01 |
Minimum of Months | 23.41 | 12.64 |
Maximum of Months | 24.23 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 13.22 |
February | 22.76 | 13.28 |
March | 22.99 | 12.64 |
April | 23.62 | 15.30 |
May | 23.59 | 15.56 |
June | 23.93 | 17.67 |
July | 24.22 | 19.43 |
August | 24.20 | 19.66 |
September | 24.00 | 18.47 |
October | 23.74 | 18.77 |
November | 22.96 | 14.32 |
December | 22.92 | 13.59 |
Annual Sum or Average | 23.48 | 16.01 |
Minimum of Months | 22.76 | 12.64 |
Maximum of Months | 24.22 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 13.22 |
February | 23.34 | 13.28 |
March | 23.37 | 12.64 |
April | 23.79 | 15.30 |
May | 23.59 | 15.56 |
June | 23.86 | 17.67 |
July | 24.21 | 19.43 |
August | 24.23 | 19.66 |
September | 24.09 | 18.47 |
October | 23.98 | 18.77 |
November | 23.64 | 14.32 |
December | 23.58 | 13.59 |
Annual Sum or Average | 23.77 | 16.01 |
Minimum of Months | 23.34 | 12.64 |
Maximum of Months | 24.23 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 13.22 |
February | 22.57 | 13.28 |
March | 22.86 | 12.64 |
April | 23.47 | 15.30 |
May | 23.43 | 15.56 |
June | 23.82 | 17.67 |
July | 24.20 | 19.43 |
August | 24.18 | 19.66 |
September | 23.88 | 18.47 |
October | 23.65 | 18.77 |
November | 22.78 | 14.32 |
December | 22.78 | 13.59 |
Annual Sum or Average | 23.37 | 16.01 |
Minimum of Months | 22.57 | 12.64 |
Maximum of Months | 24.20 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.74 | 13.22 |
February | 22.70 | 13.28 |
March | 22.94 | 12.64 |
April | 23.46 | 15.30 |
May | 23.41 | 15.56 |
June | 23.80 | 17.67 |
July | 24.17 | 19.43 |
August | 24.15 | 19.66 |
September | 23.87 | 18.47 |
October | 23.68 | 18.77 |
November | 22.84 | 14.32 |
December | 22.85 | 13.59 |
Annual Sum or Average | 23.39 | 16.01 |
Minimum of Months | 22.70 | 12.64 |
Maximum of Months | 24.17 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 13.22 |
February | 22.69 | 13.28 |
March | 22.93 | 12.64 |
April | 23.45 | 15.30 |
May | 23.40 | 15.56 |
June | 23.79 | 17.67 |
July | 24.16 | 19.43 |
August | 24.14 | 19.66 |
September | 23.86 | 18.47 |
October | 23.67 | 18.77 |
November | 22.83 | 14.32 |
December | 22.84 | 13.59 |
Annual Sum or Average | 23.38 | 16.01 |
Minimum of Months | 22.69 | 12.64 |
Maximum of Months | 24.16 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.78 | 13.22 |
February | 23.60 | 13.28 |
March | 23.57 | 12.64 |
April | 23.86 | 15.30 |
May | 23.60 | 15.56 |
June | 23.85 | 17.67 |
July | 24.17 | 19.43 |
August | 24.20 | 19.66 |
September | 24.10 | 18.47 |
October | 24.06 | 18.77 |
November | 23.83 | 14.32 |
December | 23.79 | 13.59 |
Annual Sum or Average | 23.87 | 16.01 |
Minimum of Months | 23.57 | 12.64 |
Maximum of Months | 24.20 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.78 | 13.22 |
February | 23.60 | 13.28 |
March | 23.57 | 12.64 |
April | 23.85 | 15.30 |
May | 23.60 | 15.56 |
June | 23.84 | 17.67 |
July | 24.17 | 19.43 |
August | 24.20 | 19.66 |
September | 24.10 | 18.47 |
October | 24.06 | 18.77 |
November | 23.83 | 14.32 |
December | 23.79 | 13.59 |
Annual Sum or Average | 23.87 | 16.01 |
Minimum of Months | 23.57 | 12.64 |
Maximum of Months | 24.20 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.96 | 13.22 |
February | 24.82 | 13.28 |
March | 24.95 | 12.64 |
April | 25.78 | 15.30 |
May | 25.67 | 15.56 |
June | 26.23 | 17.67 |
July | 26.79 | 19.43 |
August | 26.79 | 19.66 |
September | 26.35 | 18.47 |
October | 26.15 | 18.77 |
November | 25.19 | 14.32 |
December | 25.04 | 13.59 |
Annual Sum or Average | 25.73 | 16.01 |
Minimum of Months | 24.82 | 12.64 |
Maximum of Months | 26.79 | 19.66 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:37
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.210869E+12 | 126093.771 | 14-JAN-17:15 | 18221.747 | 56867.515 | 15486.076 | 0.000 | 21649.308 | 10720.100 | 1192.402 | 811.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.184034E+12 | 124366.017 | 01-FEB-18:15 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 16080.503 | 10720.100 | 1192.402 | 669.386 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.202667E+12 | 123798.093 | 19-MAR-17:00 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 15520.371 | 10720.100 | 1192.402 | 661.341 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.200576E+12 | 125927.569 | 12-APR-18:00 | 25049.151 | 51564.864 | 15486.076 | 0.000 | 20136.334 | 10720.100 | 1192.402 | 764.029 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.199177E+12 | 121594.552 | 24-MAY-18:45 | 25049.151 | 51564.864 | 15486.076 | 0.000 | 15937.068 | 10720.100 | 1192.402 | 630.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.205073E+12 | 138044.420 | 29-JUN-17:15 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 39585.427 | 0.000 | 1192.402 | 1562.965 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.236212E+12 | 147397.081 | 18-JUL-17:30 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 48676.944 | 0.000 | 1192.402 | 1823.856 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.242549E+12 | 145640.189 | 17-AUG-16:15 | 18221.747 | 56933.809 | 15486.076 | 0.000 | 50794.902 | 0.000 | 1192.402 | 1862.949 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.216721E+12 | 154358.706 | 29-SEP-17:45 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 45161.621 | 10720.100 | 1192.402 | 1580.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.229257E+12 | 154821.262 | 15-OCT-17:15 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 45725.146 | 10720.100 | 1192.402 | 1479.988 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.202701E+12 | 123653.449 | 29-NOV-18:15 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 15494.497 | 10720.100 | 1192.402 | 542.824 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.213730E+12 | 125503.672 | 19-DEC-18:30 | 22204.399 | 56867.515 | 15486.076 | 0.000 | 17413.966 | 10720.100 | 1192.402 | 473.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.254357E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.184034E+12 | 121594.552 | 18221.747 | 51564.864 | 15486.076 | 0.000 | 15494.497 | 0.000 | 1192.402 | 473.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.242549E+12 | 154821.262 | 25049.151 | 56933.809 | 15486.076 | 0.000 | 50794.902 | 10720.100 | 1192.402 | 1862.949 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:37
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.930176E+11 | 84317.395 | 09-JAN-07:30 | 0.000 | 0.000 | 0.000 | 84317.395 | 81847.482 | 81847.482 | 2469.913 |
February | 0.842781E+11 | 83559.289 | 13-FEB-18:15 | 0.000 | 0.000 | 0.000 | 83559.289 | 76533.806 | 76533.806 | 7025.482 |
March | 0.925349E+11 | 93614.760 | 30-MAR-06:15 | 0.000 | 0.000 | 0.000 | 93614.760 | 80594.781 | 80594.781 | 13019.979 |
April | 0.873389E+11 | 81526.145 | 01-APR-06:00 | 0.000 | 0.000 | 0.000 | 81526.145 | 81526.145 | 81526.145 | 0.000 |
May | 0.879814E+11 | 80825.042 | 02-MAY-06:00 | 0.000 | 0.000 | 0.000 | 80825.042 | 80825.042 | 80825.042 | 0.000 |
June | 0.831476E+11 | 80124.675 | 01-JUN-06:45 | 0.000 | 0.000 | 0.000 | 80124.675 | 80124.675 | 80124.675 | 0.000 |
July | 0.846811E+11 | 79606.241 | 05-JUL-06:00 | 0.000 | 0.000 | 0.000 | 79606.241 | 79606.241 | 79606.241 | 0.000 |
August | 0.845365E+11 | 79545.878 | 28-AUG-06:00 | 0.000 | 0.000 | 0.000 | 79545.878 | 79545.878 | 79545.878 | 0.000 |
September | 0.827884E+11 | 79996.439 | 30-SEP-06:45 | 0.000 | 0.000 | 0.000 | 79996.439 | 79996.439 | 79996.439 | 0.000 |
October | 0.874942E+11 | 80644.378 | 30-OCT-06:45 | 0.000 | 0.000 | 0.000 | 80644.378 | 80644.378 | 80644.378 | 0.000 |
November | 0.868575E+11 | 81391.699 | 30-NOV-07:00 | 0.000 | 0.000 | 0.000 | 81391.699 | 81391.699 | 81391.699 | 0.000 |
December | 0.918054E+11 | 81937.554 | 31-DEC-07:00 | 0.000 | 0.000 | 0.000 | 81937.554 | 81937.554 | 81937.554 | 0.000 |
Annual Sum or Average | 0.104646E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.827884E+11 | 79545.878 | 0.000 | 0.000 | 0.000 | 79545.878 | 76533.806 | 76533.806 | 0.000 | |
Maximum of Months | 0.930176E+11 | 93614.760 | 0.000 | 0.000 | 0.000 | 93614.760 | 81937.554 | 81937.554 | 13019.979 |