Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2018-10-19 09:40:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4300.65 | 548.80 | 609.17 |
Net Site Energy | 4300.65 | 548.80 | 609.17 |
Total Source Energy | 10995.15 | 1403.07 | 1557.41 |
Net Source Energy | 10995.15 | 1403.07 | 1557.41 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 74.33 | 229.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 606.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 546.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 27.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.96 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1030.26 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3040.45 | 1260.20 | 0.00 | 0.00 | 0.00 | 6426.48 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 229.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 74.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 606.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 546.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 27.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.96 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1030.26 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 184.63 | 178.50 | 0.00 | 0.00 | 0.00 | 0.91 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 430.66 | 178.50 | 0.00 | 0.00 | 0.00 | 0.91 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.33 | 160.81 | 0.00 | 0.00 | 0.00 | 0.82 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 387.99 | 160.81 | 0.00 | 0.00 | 0.00 | 0.82 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3040.45 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3040.45 | 100.00 |
Total On-Site and Utility Electric Sources | 3040.45 | 100.00 |
Total Electricity End Uses | 3040.45 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6426.48 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6426.48 | 100.00 |
Total Water End Uses | 6426.48 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 90.75 |
Time Setpoint Not Met During Occupied Cooling | 176.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2544.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:00 | 12-FEB-06:45 | - | - | - | 01-AUG-17:15 |
Heating | 0.00 | 196926.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 70064.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17344.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1624.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2877.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 79629.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 178332.06 | 276556.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 196926.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 70064.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 17344.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1624.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2877.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 79629.86 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 235.40 | 249.25 | 0.00 | 0.00 | 0.00 |
Cooling | 1919.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 534.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1732.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 154.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 86.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1116.80 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9629.10 | 1366.06 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 33.34 | 35.31 | 0.00 | 0.00 | 0.00 |
Cooling | 271.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 158.19 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1363.92 | 193.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 33.34 | 35.31 | 0.00 | 0.00 | 0.00 |
Cooling | 271.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 158.19 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1363.92 | 193.50 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.82 | 83.82 | 168.68 | |
Exterior Lighting Total | 10720.10 | 168.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 286251.16 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 229000.93 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3605.76 | 2350.37 | 1255.39 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3599.80 | 2346.36 | 1253.44 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4858.16 | 3168.21 | 1689.95 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2938.60 | 1865.94 | 1072.66 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2300.56 | 1414.07 | 886.49 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2283.83 | 1402.07 | 881.76 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2335.15 | 1424.30 | 910.85 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2402.88 | 1473.80 | 929.08 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4363.58 | 2889.27 | 1474.31 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4317.02 | 2854.56 | 1462.46 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4044.69 | 2654.41 | 1390.28 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3597.96 | 2329.08 | 1268.87 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2788.52 | 1757.14 | 1031.37 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2775.30 | 1747.57 | 1027.74 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2854.02 | 1793.09 | 1060.93 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2877.47 | 1810.35 | 1067.13 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4405.16 | 2905.73 | 1499.42 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4359.11 | 2871.91 | 1487.20 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3883.26 | 2521.90 | 1361.37 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3662.34 | 2363.90 | 1298.43 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2840.40 | 1788.06 | 1052.34 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2827.41 | 1778.66 | 1048.75 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2911.20 | 1828.12 | 1083.08 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2921.35 | 1835.61 | 1085.75 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4436.76 | 2918.86 | 1517.90 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4389.17 | 2883.87 | 1505.30 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3899.03 | 2523.89 | 1375.14 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3698.32 | 2381.00 | 1317.32 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2870.99 | 1805.18 | 1065.81 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2858.14 | 1795.89 | 1062.25 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2943.91 | 1846.90 | 1097.01 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2952.11 | 1852.95 | 1099.16 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4495.24 | 2953.75 | 1541.49 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4447.34 | 2918.52 | 1528.83 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3959.95 | 2560.93 | 1399.03 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3760.89 | 2419.35 | 1341.54 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2928.16 | 1842.54 | 1085.62 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2915.44 | 1833.35 | 1082.09 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3001.73 | 1884.98 | 1116.75 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3009.66 | 1890.82 | 1118.84 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4461.87 | 2922.08 | 1539.79 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4411.51 | 2885.03 | 1526.49 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3931.03 | 2533.09 | 1397.94 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3729.47 | 2389.91 | 1339.55 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2893.37 | 1813.77 | 1079.60 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2880.80 | 1804.71 | 1076.08 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2969.37 | 1857.76 | 1111.61 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2977.27 | 1863.57 | 1113.70 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4459.38 | 2914.12 | 1545.26 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4408.23 | 2876.48 | 1531.76 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3932.51 | 2528.46 | 1404.05 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3729.83 | 2384.63 | 1345.20 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2890.19 | 1808.41 | 1081.77 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2877.73 | 1799.45 | 1078.28 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2967.16 | 1853.04 | 1114.12 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2975.05 | 1858.85 | 1116.21 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4475.34 | 2920.40 | 1554.94 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4423.39 | 2882.17 | 1541.22 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3951.15 | 2537.04 | 1414.12 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3747.34 | 2392.50 | 1354.84 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2905.53 | 1816.79 | 1088.74 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2893.21 | 1807.93 | 1085.28 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2982.58 | 1861.51 | 1121.07 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2990.50 | 1867.33 | 1123.17 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4601.73 | 3008.87 | 1592.85 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4550.57 | 2970.67 | 1579.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4027.92 | 2588.50 | 1439.41 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3815.87 | 2437.94 | 1377.93 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3020.15 | 1897.14 | 1123.01 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3007.87 | 1888.29 | 1119.58 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3070.24 | 1922.68 | 1147.55 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3079.10 | 1929.19 | 1149.90 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5350.32 | 3555.97 | 1794.34 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5237.34 | 3472.87 | 1764.47 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4809.35 | 3148.97 | 1660.38 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4453.07 | 2898.83 | 1554.23 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3514.42 | 2255.53 | 1258.90 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3487.28 | 2235.72 | 1251.56 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3901.54 | 2530.19 | 1371.35 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3909.80 | 2536.35 | 1373.44 | 0.65 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3605.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3599.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4858.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2938.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2300.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2283.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2335.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2402.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4363.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4317.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4044.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3597.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2788.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2775.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2854.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2877.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4405.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4359.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3883.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3662.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2840.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2827.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2911.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2921.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4436.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4389.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3899.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3698.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2870.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2858.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2943.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2952.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4495.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4447.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3959.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3760.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2928.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2915.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3001.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3009.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4461.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4411.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3931.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3729.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2893.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2880.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2969.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2977.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4459.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4408.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3932.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3729.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2890.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2877.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2967.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2975.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4475.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4423.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3951.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3747.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2905.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2893.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2982.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2990.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4601.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4550.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4027.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3815.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3020.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3007.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3070.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3079.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5350.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5237.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4809.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4453.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3514.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3487.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3901.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3909.80 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2787.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2791.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3597.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2791.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2070.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2070.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2063.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2072.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2815.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2820.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2837.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2817.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1920.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1920.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1918.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1919.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2852.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2862.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2849.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2856.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1914.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1914.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1905.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1905.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2921.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2933.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2914.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2926.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1948.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1948.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1935.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1935.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2961.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2974.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2953.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2966.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1961.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1960.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1947.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1947.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 3063.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 3079.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 3054.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 3070.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 2037.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 2037.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 2021.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 2021.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 3135.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 3152.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 3125.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 3142.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 2087.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 2086.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 2070.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 2069.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 3207.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 3224.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 3196.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 3214.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2139.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2139.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2122.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2121.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 3387.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 3403.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 3376.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 3392.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2292.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2291.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2275.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2275.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3939.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3960.89 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3928.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3949.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2888.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2888.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2863.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2863.52 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.10 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.09 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.95 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.63 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 127.25 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 125.96 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 125.16 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.50 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.30 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.73 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 257.39 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 223.01 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 163.53 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 162.49 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.10 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.96 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.90 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.67 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 242.08 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 225.88 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.33 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.32 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.35 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.16 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.63 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.27 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.61 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 227.05 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.77 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.77 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.98 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.64 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 287.84 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.45 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.06 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.65 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 171.49 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.49 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.76 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 173.40 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.91 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.32 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.56 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.98 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.08 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.11 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.55 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.18 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.62 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.96 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 240.64 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 225.99 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.25 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.29 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.79 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.42 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.92 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.19 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.19 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.47 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.93 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.98 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 169.48 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.12 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 292.40 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 288.43 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.42 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.04 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 176.41 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.46 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.87 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 176.58 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 350.54 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 342.17 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 304.88 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.34 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 214.22 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 212.08 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.39 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 242.06 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0062 | 1587.99 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2070.91 | 2485.09 | 0.168 | 0.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
G NW APARTMENT | 2070.89 | 2485.07 | 0.168 | 0.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
OFFICE | 2783.99 | 3340.79 | 0.226 | 0.271 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 32.69 | 0.01445 |
G NE APARTMENT | 1599.48 | 1919.38 | 0.130 | 0.156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.86 | 0.01445 |
G N1 APARTMENT | 1165.57 | 1398.68 | 0.095 | 0.114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
G N2 APARTMENT | 1153.72 | 1384.46 | 0.094 | 0.112 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
G S1 APARTMENT | 1146.40 | 1375.68 | 0.093 | 0.112 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01445 |
G S2 APARTMENT | 1195.32 | 1434.38 | 0.097 | 0.117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01445 |
F2 SW APARTMENT | 2594.80 | 3113.76 | 0.211 | 0.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.36 | 0.01445 |
F2 NW APARTMENT | 2562.12 | 3074.54 | 0.208 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F2 SE APARTMENT | 2357.40 | 2828.88 | 0.191 | 0.230 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F2 NE APARTMENT | 2042.53 | 2451.03 | 0.166 | 0.199 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F2 N1 APARTMENT | 1497.82 | 1797.38 | 0.122 | 0.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F2 N2 APARTMENT | 1488.34 | 1786.01 | 0.121 | 0.145 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F2 S1 APARTMENT | 1503.01 | 1803.61 | 0.122 | 0.147 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F2 S2 APARTMENT | 1520.12 | 1824.14 | 0.123 | 0.148 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F3 SW APARTMENT | 2600.27 | 3120.33 | 0.211 | 0.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
F3 NW APARTMENT | 2570.74 | 3084.88 | 0.209 | 0.251 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F3 SE APARTMENT | 2217.16 | 2660.59 | 0.180 | 0.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F3 NE APARTMENT | 2068.77 | 2482.52 | 0.168 | 0.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F3 N1 APARTMENT | 1523.49 | 1828.19 | 0.124 | 0.148 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F3 N2 APARTMENT | 1514.19 | 1817.03 | 0.123 | 0.148 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F3 S1 APARTMENT | 1532.80 | 1839.36 | 0.125 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F3 S2 APARTMENT | 1540.24 | 1848.29 | 0.125 | 0.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F4 SW APARTMENT | 2606.88 | 3128.25 | 0.212 | 0.254 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
F4 NW APARTMENT | 2576.14 | 3091.37 | 0.209 | 0.251 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F4 SE APARTMENT | 2212.81 | 2655.37 | 0.180 | 0.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F4 NE APARTMENT | 2079.46 | 2495.36 | 0.169 | 0.203 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F4 N1 APARTMENT | 1536.71 | 1844.06 | 0.125 | 0.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F4 N2 APARTMENT | 1527.53 | 1833.04 | 0.124 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F4 S1 APARTMENT | 1547.70 | 1857.25 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F4 S2 APARTMENT | 1553.72 | 1864.47 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
M SW APARTMENT | 2636.29 | 3163.54 | 0.214 | 0.257 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
M NW APARTMENT | 2605.29 | 3126.35 | 0.212 | 0.254 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
M SE APARTMENT | 2244.42 | 2693.31 | 0.182 | 0.219 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
M NE APARTMENT | 2112.42 | 2534.90 | 0.172 | 0.206 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
M N1 APARTMENT | 1570.69 | 1884.83 | 0.128 | 0.153 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
M N2 APARTMENT | 1561.61 | 1873.93 | 0.127 | 0.152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
M S1 APARTMENT | 1582.36 | 1898.83 | 0.129 | 0.154 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
M S2 APARTMENT | 1588.17 | 1905.81 | 0.129 | 0.155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F6 SW APARTMENT | 2600.31 | 3120.38 | 0.211 | 0.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
F6 NW APARTMENT | 2567.47 | 3080.96 | 0.209 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F6 SE APARTMENT | 2212.38 | 2654.86 | 0.180 | 0.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F6 NE APARTMENT | 2078.81 | 2494.57 | 0.169 | 0.203 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F6 N1 APARTMENT | 1539.54 | 1847.44 | 0.125 | 0.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F6 N2 APARTMENT | 1530.59 | 1836.71 | 0.124 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F6 S1 APARTMENT | 1552.87 | 1863.44 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F6 S2 APARTMENT | 1558.65 | 1870.39 | 0.127 | 0.152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F7 SW APARTMENT | 2588.46 | 3106.15 | 0.210 | 0.252 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
F7 NW APARTMENT | 2554.99 | 3065.99 | 0.208 | 0.249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F7 SE APARTMENT | 2203.91 | 2644.69 | 0.179 | 0.215 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F7 NE APARTMENT | 2069.72 | 2483.66 | 0.168 | 0.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F7 N1 APARTMENT | 1531.92 | 1838.30 | 0.124 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F7 N2 APARTMENT | 1523.07 | 1827.69 | 0.124 | 0.148 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F7 S1 APARTMENT | 1545.95 | 1855.14 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F7 S2 APARTMENT | 1551.73 | 1862.07 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F8 SW APARTMENT | 2591.15 | 3109.38 | 0.210 | 0.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
F8 NW APARTMENT | 2557.08 | 3068.50 | 0.208 | 0.249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F8 SE APARTMENT | 2208.96 | 2650.75 | 0.179 | 0.215 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F8 NE APARTMENT | 2074.09 | 2488.90 | 0.168 | 0.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F8 N1 APARTMENT | 1538.15 | 1845.78 | 0.125 | 0.150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F8 N2 APARTMENT | 1529.41 | 1835.30 | 0.124 | 0.149 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F8 S1 APARTMENT | 1552.30 | 1862.76 | 0.126 | 0.151 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F8 S2 APARTMENT | 1558.08 | 1869.70 | 0.127 | 0.152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F9 SW APARTMENT | 2678.01 | 3213.61 | 0.218 | 0.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.36 | 0.01445 |
F9 NW APARTMENT | 2641.69 | 3170.03 | 0.215 | 0.258 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
F9 SE APARTMENT | 2256.77 | 2708.13 | 0.183 | 0.220 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.93 | 0.01445 |
F9 NE APARTMENT | 2115.95 | 2539.14 | 0.172 | 0.206 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.21 | 0.01445 |
F9 N1 APARTMENT | 1615.83 | 1939.00 | 0.131 | 0.157 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F9 N2 APARTMENT | 1607.10 | 1928.52 | 0.131 | 0.157 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
F9 S1 APARTMENT | 1610.79 | 1932.94 | 0.131 | 0.157 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
F9 S2 APARTMENT | 1617.26 | 1940.71 | 0.131 | 0.158 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
T SW APARTMENT | 3210.35 | 3852.42 | 0.261 | 0.313 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 33.26 | 0.01445 |
T NW APARTMENT | 3133.79 | 3760.55 | 0.255 | 0.305 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59 | 0.01445 |
T SE APARTMENT | 2792.19 | 3350.63 | 0.227 | 0.272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01445 |
T NE APARTMENT | 2567.40 | 3080.88 | 0.209 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 32.45 | 0.01445 |
T N1 APARTMENT | 1962.07 | 2354.48 | 0.159 | 0.191 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
T N2 APARTMENT | 1942.47 | 2330.96 | 0.158 | 0.189 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
T S1 APARTMENT | 2210.86 | 2653.03 | 0.180 | 0.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
T S2 APARTMENT | 2217.03 | 2660.43 | 0.180 | 0.216 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01445 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1640.68 | 1968.81 | 0.076 | 0.091 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G NW APARTMENT | 1643.56 | 1972.28 | 0.076 | 0.091 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
OFFICE | 1989.56 | 2387.48 | 0.092 | 0.110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -6.30 | 0.00230 |
G NE APARTMENT | 1643.73 | 1972.48 | 0.076 | 0.091 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G N1 APARTMENT | 1034.23 | 1241.07 | 0.048 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G N2 APARTMENT | 1034.22 | 1241.07 | 0.048 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G S1 APARTMENT | 1028.23 | 1233.87 | 0.047 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
G S2 APARTMENT | 1035.41 | 1242.49 | 0.048 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
F2 SW APARTMENT | 1663.79 | 1996.55 | 0.077 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 NW APARTMENT | 1668.40 | 2002.08 | 0.077 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 SE APARTMENT | 1682.29 | 2018.75 | 0.078 | 0.093 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 NE APARTMENT | 1665.56 | 1998.67 | 0.077 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 N1 APARTMENT | 907.59 | 1089.11 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 N2 APARTMENT | 907.52 | 1089.03 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 S1 APARTMENT | 905.16 | 1086.19 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F2 S2 APARTMENT | 906.50 | 1087.81 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 SW APARTMENT | 1695.17 | 2034.20 | 0.078 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 NW APARTMENT | 1703.43 | 2044.12 | 0.079 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 SE APARTMENT | 1692.80 | 2031.36 | 0.078 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 NE APARTMENT | 1698.70 | 2038.44 | 0.078 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 N1 APARTMENT | 902.03 | 1082.44 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 N2 APARTMENT | 901.91 | 1082.30 | 0.042 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 S1 APARTMENT | 894.19 | 1073.03 | 0.041 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F3 S2 APARTMENT | 894.29 | 1073.15 | 0.041 | 0.050 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 SW APARTMENT | 1753.34 | 2104.01 | 0.081 | 0.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 NW APARTMENT | 1764.08 | 2116.90 | 0.081 | 0.098 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 SE APARTMENT | 1747.53 | 2097.04 | 0.081 | 0.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 NE APARTMENT | 1758.02 | 2109.63 | 0.081 | 0.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 N1 APARTMENT | 930.70 | 1116.84 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 N2 APARTMENT | 930.55 | 1116.66 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 S1 APARTMENT | 920.11 | 1104.14 | 0.042 | 0.051 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F4 S2 APARTMENT | 919.99 | 1103.99 | 0.042 | 0.051 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M SW APARTMENT | 1787.42 | 2144.91 | 0.082 | 0.099 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M NW APARTMENT | 1798.90 | 2158.69 | 0.083 | 0.100 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M SE APARTMENT | 1780.40 | 2136.47 | 0.082 | 0.099 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M NE APARTMENT | 1791.86 | 2150.23 | 0.083 | 0.099 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M N1 APARTMENT | 941.52 | 1129.82 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M N2 APARTMENT | 941.34 | 1129.60 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M S1 APARTMENT | 930.15 | 1116.17 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
M S2 APARTMENT | 929.97 | 1115.96 | 0.043 | 0.052 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 SW APARTMENT | 1873.96 | 2248.75 | 0.086 | 0.104 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 NW APARTMENT | 1887.52 | 2265.02 | 0.087 | 0.105 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 SE APARTMENT | 1866.09 | 2239.31 | 0.086 | 0.103 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 NE APARTMENT | 1879.66 | 2255.59 | 0.087 | 0.104 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 N1 APARTMENT | 1006.13 | 1207.36 | 0.046 | 0.056 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 N2 APARTMENT | 1005.93 | 1207.12 | 0.046 | 0.056 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 S1 APARTMENT | 992.61 | 1191.13 | 0.046 | 0.055 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F6 S2 APARTMENT | 992.41 | 1190.89 | 0.046 | 0.055 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 SW APARTMENT | 1934.45 | 2321.34 | 0.089 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 NW APARTMENT | 1948.86 | 2338.63 | 0.090 | 0.108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 SE APARTMENT | 1925.92 | 2311.10 | 0.089 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 NE APARTMENT | 1940.33 | 2328.40 | 0.090 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 N1 APARTMENT | 1048.23 | 1257.87 | 0.048 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 N2 APARTMENT | 1048.01 | 1257.61 | 0.048 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 S1 APARTMENT | 1033.84 | 1240.61 | 0.048 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F7 S2 APARTMENT | 1033.63 | 1240.35 | 0.048 | 0.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 SW APARTMENT | 1995.40 | 2394.48 | 0.092 | 0.111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 NW APARTMENT | 2010.29 | 2412.35 | 0.093 | 0.111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 SE APARTMENT | 1986.30 | 2383.56 | 0.092 | 0.110 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 NE APARTMENT | 2001.21 | 2401.45 | 0.092 | 0.111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 N1 APARTMENT | 1092.61 | 1311.13 | 0.050 | 0.061 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 N2 APARTMENT | 1092.38 | 1310.86 | 0.050 | 0.060 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 S1 APARTMENT | 1077.73 | 1293.27 | 0.050 | 0.060 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F8 S2 APARTMENT | 1077.50 | 1293.00 | 0.050 | 0.060 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 SW APARTMENT | 2148.15 | 2577.78 | 0.099 | 0.119 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 NW APARTMENT | 2161.55 | 2593.86 | 0.100 | 0.120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 SE APARTMENT | 2138.47 | 2566.17 | 0.099 | 0.118 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 NE APARTMENT | 2151.89 | 2582.26 | 0.099 | 0.119 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 N1 APARTMENT | 1221.61 | 1465.93 | 0.056 | 0.068 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 N2 APARTMENT | 1221.36 | 1465.63 | 0.056 | 0.068 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 S1 APARTMENT | 1207.84 | 1449.41 | 0.056 | 0.067 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
F9 S2 APARTMENT | 1207.60 | 1449.12 | 0.056 | 0.067 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T SW APARTMENT | 2614.57 | 3137.49 | 0.121 | 0.145 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T NW APARTMENT | 2632.73 | 3159.28 | 0.121 | 0.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T SE APARTMENT | 2605.29 | 3126.35 | 0.120 | 0.144 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T NE APARTMENT | 2623.46 | 3148.16 | 0.121 | 0.145 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T N1 APARTMENT | 1725.89 | 2071.07 | 0.080 | 0.096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T N2 APARTMENT | 1725.64 | 2070.77 | 0.080 | 0.096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T S1 APARTMENT | 1704.96 | 2045.95 | 0.079 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
T S2 APARTMENT | 1704.71 | 2045.65 | 0.079 | 0.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -6.30 | 0.00230 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP G NW | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP OFFICE | 0.27 | 0.27 | 0.11 | 0.11 |
AIRLOOP G NE | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP G N1 | 0.11 | 0.11 | 0.06 | 0.06 |
AIRLOOP G N2 | 0.11 | 0.11 | 0.06 | 0.06 |
AIRLOOP G S1 | 0.11 | 0.11 | 0.06 | 0.06 |
AIRLOOP G S2 | 0.12 | 0.12 | 0.06 | 0.06 |
AIRLOOP F2 SW | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F2 NW | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F2 SE | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F2 NE | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP F2 N1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F2 N2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F2 S1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F2 S2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F3 SW | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F3 NW | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F3 SE | 0.22 | 0.22 | 0.09 | 0.09 |
AIRLOOP F3 NE | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP F3 N1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F3 N2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F3 S1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F3 S2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F4 SW | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F4 NW | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F4 SE | 0.22 | 0.22 | 0.10 | 0.10 |
AIRLOOP F4 NE | 0.20 | 0.20 | 0.10 | 0.10 |
AIRLOOP F4 N1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F4 N2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F4 S1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F4 S2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP M SW | 0.26 | 0.26 | 0.10 | 0.10 |
AIRLOOP M NW | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP M SE | 0.22 | 0.22 | 0.10 | 0.10 |
AIRLOOP M NE | 0.21 | 0.21 | 0.10 | 0.10 |
AIRLOOP M N1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP M N2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP M S1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP M S2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F6 SW | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F6 NW | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F6 SE | 0.22 | 0.22 | 0.10 | 0.10 |
AIRLOOP F6 NE | 0.20 | 0.20 | 0.10 | 0.10 |
AIRLOOP F6 N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F6 N2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F6 S1 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F6 S2 | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP F7 SW | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F7 NW | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F7 SE | 0.21 | 0.21 | 0.11 | 0.11 |
AIRLOOP F7 NE | 0.20 | 0.20 | 0.11 | 0.11 |
AIRLOOP F7 N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F7 N2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F7 S1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F7 S2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F8 SW | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F8 NW | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F8 SE | 0.22 | 0.22 | 0.11 | 0.11 |
AIRLOOP F8 NE | 0.20 | 0.20 | 0.11 | 0.11 |
AIRLOOP F8 N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F8 N2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F8 S1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F8 S2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F9 SW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F9 NW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F9 SE | 0.22 | 0.22 | 0.12 | 0.12 |
AIRLOOP F9 NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP F9 N1 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F9 N2 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F9 S1 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F9 S2 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP T SW | 0.31 | 0.31 | 0.14 | 0.14 |
AIRLOOP T NW | 0.31 | 0.31 | 0.15 | 0.15 |
AIRLOOP T SE | 0.27 | 0.27 | 0.14 | 0.14 |
AIRLOOP T NE | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP T N1 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP T N2 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP T S1 | 0.22 | 0.22 | 0.09 | 0.09 |
AIRLOOP T S2 | 0.22 | 0.22 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4173.00 | 5847.00 | 1818.75 |
G NW APARTMENT | 4102.75 | 6286.25 | 2026.00 |
OFFICE | 1240.25 | 685.25 | 19.25 |
G NE APARTMENT | 4090.00 | 6254.50 | 1954.25 |
G N1 APARTMENT | 3838.25 | 6509.75 | 1965.50 |
G N2 APARTMENT | 3839.25 | 6506.00 | 1961.50 |
G S1 APARTMENT | 3945.50 | 5934.50 | 1737.00 |
G S2 APARTMENT | 3972.00 | 5889.25 | 1731.25 |
F2 SW APARTMENT | 4690.00 | 4256.50 | 1170.25 |
F2 NW APARTMENT | 4383.75 | 5158.25 | 1329.25 |
F2 SE APARTMENT | 4807.25 | 4036.00 | 1069.25 |
F2 NE APARTMENT | 4415.25 | 5150.50 | 1278.50 |
F2 N1 APARTMENT | 4198.25 | 5325.00 | 1314.00 |
F2 N2 APARTMENT | 4199.75 | 5330.00 | 1311.50 |
F2 S1 APARTMENT | 4642.00 | 4149.00 | 1184.00 |
F2 S2 APARTMENT | 4653.75 | 4116.00 | 1176.50 |
F3 SW APARTMENT | 4828.25 | 3967.75 | 1125.50 |
F3 NW APARTMENT | 4479.25 | 4949.25 | 1270.75 |
F3 SE APARTMENT | 4868.25 | 3944.50 | 1075.50 |
F3 NE APARTMENT | 4490.00 | 4952.75 | 1236.50 |
F3 N1 APARTMENT | 4325.50 | 5009.75 | 1224.75 |
F3 N2 APARTMENT | 4325.00 | 5015.25 | 1224.25 |
F3 S1 APARTMENT | 4841.50 | 3710.50 | 1113.25 |
F3 S2 APARTMENT | 4848.00 | 3706.75 | 1114.25 |
F4 SW APARTMENT | 4858.00 | 3950.00 | 1145.75 |
F4 NW APARTMENT | 4501.75 | 4929.00 | 1288.50 |
F4 SE APARTMENT | 4888.00 | 3962.25 | 1108.50 |
F4 NE APARTMENT | 4522.25 | 4919.00 | 1247.50 |
F4 N1 APARTMENT | 4367.25 | 4935.75 | 1221.75 |
F4 N2 APARTMENT | 4365.50 | 4939.75 | 1219.50 |
F4 S1 APARTMENT | 4899.25 | 3637.50 | 1123.25 |
F4 S2 APARTMENT | 4901.25 | 3639.00 | 1123.00 |
M SW APARTMENT | 4860.50 | 3964.25 | 1140.00 |
M NW APARTMENT | 4504.75 | 4917.25 | 1277.75 |
M SE APARTMENT | 4887.50 | 3986.00 | 1108.50 |
M NE APARTMENT | 4526.25 | 4906.25 | 1238.25 |
M N1 APARTMENT | 4386.75 | 4900.25 | 1205.75 |
M N2 APARTMENT | 4384.00 | 4906.25 | 1206.25 |
M S1 APARTMENT | 4913.75 | 3619.75 | 1115.25 |
M S2 APARTMENT | 4913.75 | 3624.75 | 1116.25 |
F6 SW APARTMENT | 4779.25 | 4204.50 | 1205.25 |
F6 NW APARTMENT | 4461.25 | 5072.00 | 1350.25 |
F6 SE APARTMENT | 4809.25 | 4227.00 | 1171.00 |
F6 NE APARTMENT | 4473.50 | 5065.00 | 1306.25 |
F6 N1 APARTMENT | 4314.00 | 5058.50 | 1255.25 |
F6 N2 APARTMENT | 4313.00 | 5066.25 | 1255.75 |
F6 S1 APARTMENT | 4798.75 | 3845.25 | 1158.25 |
F6 S2 APARTMENT | 4803.75 | 3847.25 | 1159.25 |
F7 SW APARTMENT | 4727.25 | 4360.00 | 1240.50 |
F7 NW APARTMENT | 4426.50 | 5168.50 | 1388.75 |
F7 SE APARTMENT | 4752.00 | 4374.00 | 1204.50 |
F7 NE APARTMENT | 4445.50 | 5166.25 | 1338.50 |
F7 N1 APARTMENT | 4280.75 | 5170.25 | 1291.00 |
F7 N2 APARTMENT | 4279.75 | 5174.25 | 1289.00 |
F7 S1 APARTMENT | 4737.75 | 4025.75 | 1189.25 |
F7 S2 APARTMENT | 4738.25 | 4028.75 | 1189.25 |
F8 SW APARTMENT | 4679.25 | 4490.50 | 1265.25 |
F8 NW APARTMENT | 4400.25 | 5253.25 | 1420.75 |
F8 SE APARTMENT | 4700.75 | 4496.25 | 1231.00 |
F8 NE APARTMENT | 4424.75 | 5235.25 | 1365.75 |
F8 N1 APARTMENT | 4252.50 | 5262.75 | 1315.50 |
F8 N2 APARTMENT | 4252.00 | 5272.00 | 1318.00 |
F8 S1 APARTMENT | 4684.25 | 4184.75 | 1208.25 |
F8 S2 APARTMENT | 4686.00 | 4196.25 | 1212.50 |
F9 SW APARTMENT | 4633.25 | 4643.00 | 1288.25 |
F9 NW APARTMENT | 4411.75 | 5313.00 | 1464.25 |
F9 SE APARTMENT | 4651.75 | 4627.25 | 1259.00 |
F9 NE APARTMENT | 4435.75 | 5293.75 | 1411.25 |
F9 N1 APARTMENT | 4232.50 | 5341.75 | 1332.25 |
F9 N2 APARTMENT | 4233.25 | 5346.25 | 1332.50 |
F9 S1 APARTMENT | 4605.25 | 4387.00 | 1217.00 |
F9 S2 APARTMENT | 4607.50 | 4393.25 | 1219.00 |
T SW APARTMENT | 4751.00 | 5048.00 | 1694.75 |
T NW APARTMENT | 4673.50 | 5632.25 | 1942.75 |
T SE APARTMENT | 4793.00 | 5007.50 | 1670.50 |
T NE APARTMENT | 4658.00 | 5637.25 | 1920.25 |
T N1 APARTMENT | 4418.50 | 5645.00 | 1696.25 |
T N2 APARTMENT | 4420.00 | 5648.75 | 1697.75 |
T S1 APARTMENT | 4638.00 | 4872.50 | 1510.75 |
T S2 APARTMENT | 4639.50 | 4871.00 | 1510.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5757.25 | 6627.75 | 2544.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 2.75 | 7.00 | 2.75 | 7.00 |
G NW APARTMENT | 2.25 | 0.50 | 2.25 | 0.50 |
OFFICE | 2.50 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 2.75 | 13.75 | 2.75 | 13.75 |
G N1 APARTMENT | 3.25 | 11.25 | 3.25 | 11.25 |
G N2 APARTMENT | 3.50 | 11.25 | 3.50 | 11.25 |
G S1 APARTMENT | 0.50 | 97.75 | 0.50 | 97.75 |
G S2 APARTMENT | 0.25 | 67.25 | 0.25 | 67.25 |
F2 SW APARTMENT | 1.00 | 2.25 | 1.00 | 2.25 |
F2 NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F2 SE APARTMENT | 1.25 | 2.00 | 1.25 | 2.00 |
F2 NE APARTMENT | 2.25 | 10.75 | 2.25 | 10.75 |
F2 N1 APARTMENT | 5.25 | 6.25 | 5.25 | 6.25 |
F2 N2 APARTMENT | 3.75 | 6.50 | 3.75 | 6.50 |
F2 S1 APARTMENT | 0.75 | 78.75 | 0.75 | 78.75 |
F2 S2 APARTMENT | 1.00 | 66.50 | 1.00 | 66.50 |
F3 SW APARTMENT | 0.50 | 2.75 | 0.50 | 2.75 |
F3 NW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F3 SE APARTMENT | 0.75 | 17.75 | 0.75 | 17.75 |
F3 NE APARTMENT | 1.75 | 16.75 | 1.75 | 16.75 |
F3 N1 APARTMENT | 3.25 | 13.75 | 3.25 | 13.75 |
F3 N2 APARTMENT | 4.50 | 13.75 | 4.50 | 13.75 |
F3 S1 APARTMENT | 1.25 | 85.75 | 1.25 | 85.75 |
F3 S2 APARTMENT | 1.25 | 80.25 | 1.25 | 80.25 |
F4 SW APARTMENT | 0.25 | 2.75 | 0.25 | 2.75 |
F4 NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F4 SE APARTMENT | 0.75 | 19.75 | 0.75 | 19.75 |
F4 NE APARTMENT | 1.75 | 18.50 | 1.75 | 18.50 |
F4 N1 APARTMENT | 3.25 | 16.00 | 3.25 | 16.00 |
F4 N2 APARTMENT | 2.75 | 16.50 | 2.75 | 16.50 |
F4 S1 APARTMENT | 1.50 | 83.50 | 1.50 | 83.50 |
F4 S2 APARTMENT | 1.50 | 80.50 | 1.50 | 80.50 |
M SW APARTMENT | 1.00 | 2.75 | 1.00 | 2.75 |
M NW APARTMENT | 0.50 | 0.25 | 0.50 | 0.25 |
M SE APARTMENT | 1.25 | 20.25 | 1.25 | 20.25 |
M NE APARTMENT | 1.00 | 19.50 | 1.00 | 19.50 |
M N1 APARTMENT | 2.75 | 16.75 | 2.75 | 16.75 |
M N2 APARTMENT | 2.25 | 17.25 | 2.25 | 17.25 |
M S1 APARTMENT | 1.25 | 81.00 | 1.25 | 81.00 |
M S2 APARTMENT | 1.25 | 78.50 | 1.25 | 78.50 |
F6 SW APARTMENT | 0.50 | 3.00 | 0.50 | 3.00 |
F6 NW APARTMENT | 0.75 | 0.25 | 0.75 | 0.25 |
F6 SE APARTMENT | 0.75 | 20.00 | 0.75 | 20.00 |
F6 NE APARTMENT | 1.00 | 19.50 | 1.00 | 19.50 |
F6 N1 APARTMENT | 3.00 | 17.50 | 3.00 | 17.50 |
F6 N2 APARTMENT | 2.50 | 18.00 | 2.50 | 18.00 |
F6 S1 APARTMENT | 0.50 | 81.00 | 0.50 | 81.00 |
F6 S2 APARTMENT | 0.75 | 78.75 | 0.75 | 78.75 |
F7 SW APARTMENT | 1.25 | 3.25 | 1.25 | 3.25 |
F7 NW APARTMENT | 0.25 | 0.50 | 0.25 | 0.50 |
F7 SE APARTMENT | 1.50 | 20.50 | 1.50 | 20.50 |
F7 NE APARTMENT | 2.00 | 19.75 | 2.00 | 19.75 |
F7 N1 APARTMENT | 3.50 | 17.75 | 3.50 | 17.75 |
F7 N2 APARTMENT | 4.50 | 19.75 | 4.50 | 19.75 |
F7 S1 APARTMENT | 0.50 | 80.00 | 0.50 | 80.00 |
F7 S2 APARTMENT | 0.50 | 77.00 | 0.50 | 77.00 |
F8 SW APARTMENT | 0.50 | 3.25 | 0.50 | 3.25 |
F8 NW APARTMENT | 0.25 | 0.50 | 0.25 | 0.50 |
F8 SE APARTMENT | 2.00 | 22.00 | 2.00 | 22.00 |
F8 NE APARTMENT | 1.75 | 22.75 | 1.75 | 22.75 |
F8 N1 APARTMENT | 2.25 | 20.75 | 2.25 | 20.75 |
F8 N2 APARTMENT | 2.00 | 22.00 | 2.00 | 22.00 |
F8 S1 APARTMENT | 1.25 | 78.00 | 1.25 | 78.00 |
F8 S2 APARTMENT | 1.00 | 75.75 | 1.00 | 75.75 |
F9 SW APARTMENT | 0.50 | 3.00 | 0.50 | 3.00 |
F9 NW APARTMENT | 0.25 | 0.25 | 0.25 | 0.25 |
F9 SE APARTMENT | 1.25 | 19.25 | 1.25 | 19.25 |
F9 NE APARTMENT | 0.00 | 21.50 | 0.00 | 21.50 |
F9 N1 APARTMENT | 5.00 | 17.50 | 5.00 | 17.50 |
F9 N2 APARTMENT | 4.50 | 19.50 | 4.50 | 19.50 |
F9 S1 APARTMENT | 1.75 | 67.00 | 1.75 | 67.00 |
F9 S2 APARTMENT | 2.00 | 63.50 | 2.00 | 63.50 |
T SW APARTMENT | 0.25 | 3.00 | 0.25 | 3.00 |
T NW APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T SE APARTMENT | 0.00 | 4.00 | 0.00 | 4.00 |
T NE APARTMENT | 0.00 | 13.00 | 0.00 | 13.00 |
T N1 APARTMENT | 2.25 | 14.50 | 2.25 | 14.50 |
T N2 APARTMENT | 1.00 | 15.50 | 1.00 | 15.50 |
T S1 APARTMENT | 2.50 | 9.50 | 2.50 | 9.50 |
T S2 APARTMENT | 1.50 | 9.75 | 1.50 | 9.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 93.25 | 176.00 | 90.75 | 176.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.100 | 0.000 | 0.379 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.100 | 0.000 | 0.364 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.520 | 0.113 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.100 | 0.000 | 0.363 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.060 | 0.000 | 0.357 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.060 | 0.000 | 0.357 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.060 | 0.000 | 0.376 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.060 | 0.000 | 0.376 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.144 | 0.000 | 0.446 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.144 | 0.000 | 0.428 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.144 | 0.000 | 0.447 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.143 | 0.000 | 0.427 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.087 | 0.000 | 0.424 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.087 | 0.000 | 0.424 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.087 | 0.000 | 0.444 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.087 | 0.000 | 0.444 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.170 | 0.000 | 0.492 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.170 | 0.000 | 0.472 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.170 | 0.000 | 0.492 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.170 | 0.000 | 0.472 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.102 | 0.000 | 0.469 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.102 | 0.000 | 0.469 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.103 | 0.000 | 0.491 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.103 | 0.000 | 0.491 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.190 | 0.000 | 0.513 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.190 | 0.000 | 0.492 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.190 | 0.000 | 0.513 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.190 | 0.000 | 0.492 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.115 | 0.000 | 0.490 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.115 | 0.000 | 0.490 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.115 | 0.000 | 0.512 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.115 | 0.000 | 0.512 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.207 | 0.000 | 0.539 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.206 | 0.000 | 0.517 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.206 | 0.000 | 0.538 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.206 | 0.000 | 0.516 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.124 | 0.000 | 0.514 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.124 | 0.000 | 0.514 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.125 | 0.000 | 0.538 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.125 | 0.000 | 0.538 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.221 | 0.000 | 0.560 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.220 | 0.000 | 0.537 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.221 | 0.000 | 0.560 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.220 | 0.000 | 0.536 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.133 | 0.000 | 0.534 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.133 | 0.000 | 0.534 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.133 | 0.000 | 0.559 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.133 | 0.000 | 0.559 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.579 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.233 | 0.000 | 0.554 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.579 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.233 | 0.000 | 0.553 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.140 | 0.000 | 0.552 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.140 | 0.000 | 0.552 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.141 | 0.000 | 0.578 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.578 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.244 | 0.000 | 0.598 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.244 | 0.000 | 0.573 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.244 | 0.000 | 0.598 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.244 | 0.000 | 0.572 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.147 | 0.000 | 0.570 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.147 | 0.000 | 0.570 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.147 | 0.000 | 0.597 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.147 | 0.000 | 0.597 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.255 | 0.000 | 0.615 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.589 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.255 | 0.000 | 0.615 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.588 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.153 | 0.000 | 0.586 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.153 | 0.000 | 0.586 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.154 | 0.000 | 0.614 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.154 | 0.000 | 0.614 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.264 | 0.000 | 0.628 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.264 | 0.000 | 0.602 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.264 | 0.000 | 0.628 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.264 | 0.000 | 0.601 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.159 | 0.000 | 0.599 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.159 | 0.000 | 0.599 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.159 | 0.000 | 0.627 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.159 | 0.000 | 0.627 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.499 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 546.99 | 17344.92 | 12-JAN-06:15 | 17344.92 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1248.25 | 17725.45 | 01-MAR-03:15 | 92115.60 | 04-AUG-15:30 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
ElectricityPurchased:Plant | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
Cogeneration:ElectricityPurchased | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
ElectricityNet:Plant | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
Cogeneration:ElectricityNet | 3040.45 | 55285.93 | 01-MAR-03:15 | 178332.06 | 26-JUL-20:00 |
ExteriorLights:Electricity | 168.68 | 0.00 | 01-JAN-08:00 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.68 | 0.00 | 01-JAN-08:00 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 546.99 | 17344.92 | 12-JAN-06:15 | 17344.92 | 01-JAN-00:15 |
Cooling:Electricity | 606.11 | 0.00 | 01-JAN-00:15 | 73953.27 | 04-AUG-15:30 |
Heating:Electricity | 74.33 | 0.00 | 01-JAN-11:15 | 50268.05 | 12-FEB-06:00 |
Electricity:Plant | 76.01 | 36.93 | 01-JAN-11:15 | 4630.55 | 19-AUG-16:45 |
HeatRejection:Electricity | 27.19 | 0.00 | 01-JAN-00:15 | 3005.64 | 19-AUG-16:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 48.82 | 36.93 | 01-JAN-11:15 | 1624.92 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1260.20 | 9260.51 | 01-JAN-15:00 | 276556.67 | 12-FEB-06:45 |
Gas:Plant | 1260.20 | 9260.51 | 01-JAN-15:00 | 276556.67 | 12-FEB-06:45 |
WaterSystems:Gas | 1030.26 | 9260.51 | 01-JAN-00:15 | 85033.90 | 30-JAN-08:00 |
Water Heater:WaterSystems:Gas | 1030.26 | 9260.51 | 01-JAN-00:15 | 85033.90 | 30-JAN-08:00 |
Heating:Gas | 229.94 | 0.00 | 01-JAN-09:30 | 205634.57 | 12-FEB-06:15 |
Boiler:Heating:Gas | 229.94 | 0.00 | 01-JAN-09:30 | 205634.57 | 12-FEB-06:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 2631.76 | 0.00 | 01-JAN-00:15 | 362166.26 | 20-AUG-15:30 |
PlantLoopCoolingDemand:HVAC | 2631.76 | 0.00 | 01-JAN-00:15 | 362166.26 | 20-AUG-15:30 |
CoolingCoils:PlantLoopCoolingDemand | 2631.76 | 0.00 | 01-JAN-00:15 | 362166.26 | 20-AUG-15:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6426.48 | 0.00 | 01-JAN-02:30 | 0.00 | 01-AUG-17:15 |
Water:Plant | 6426.48 | 0.00 | 01-JAN-02:30 | 0.00 | 01-AUG-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6426.48 | 0.00 | 01-JAN-02:30 | 0.00 | 01-AUG-17:15 |
MainsWater:Plant | 6426.48 | 0.00 | 01-JAN-02:30 | 0.00 | 01-AUG-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1647.96 | 0.00 | 01-JAN-00:15 | 0.00 | 08-JUL-16:00 |
HeatRejection:MainsWater | 1647.96 | 0.00 | 01-JAN-00:15 | 0.00 | 08-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 991.17 | 405.47 | 03-AUG-01:15 | 217368.33 | 12-FEB-06:15 |
PlantLoopHeatingDemand:Plant | 781.95 | 405.47 | 03-AUG-01:15 | 55132.33 | 02-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 781.95 | 405.47 | 03-AUG-01:15 | 55132.33 | 02-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4770.98 | 4558.76 | 01-OCT-01:15 | 574305.17 | 12-FEB-06:15 |
EnergyTransfer:Building | 1468.45 | 2700.84 | 30-APR-10:15 | 169253.98 | 01-AUG-16:30 |
EnergyTransfer:Zone:G SW APARTMENT | 14.23 | 0.00 | 17-FEB-01:15 | 2300.54 | 08-SEP-16:30 |
Heating:EnergyTransfer | 167.82 | 0.00 | 24-JAN-18:30 | 149844.47 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.02 | 0.00 | 01-JAN-09:30 | 1718.34 | 12-FEB-06:00 |
Cooling:EnergyTransfer | 1300.62 | 0.00 | 02-JAN-02:45 | 169253.98 | 01-AUG-16:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 12.21 | 0.00 | 01-JAN-00:15 | 2300.54 | 08-SEP-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 13.47 | 0.00 | 20-MAR-22:45 | 2215.79 | 18-AUG-17:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 3.56 | 0.00 | 01-JAN-10:45 | 1766.95 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 9.91 | 0.00 | 01-JAN-00:15 | 2215.79 | 18-AUG-17:00 |
EnergyTransfer:Zone:OFFICE | 19.67 | 0.02 | 22-OCT-19:45 | 2942.65 | 06-SEP-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 1.93 | 0.00 | 01-JAN-11:15 | 1830.20 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 17.74 | 0.00 | 01-JAN-00:15 | 2942.65 | 06-SEP-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 13.40 | 0.01 | 30-MAR-03:00 | 1787.92 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 3.33 | 0.00 | 01-JAN-10:15 | 1787.92 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 10.07 | 0.00 | 01-JAN-00:15 | 1682.37 | 08-JUL-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.77 | 0.01 | 01-OCT-05:45 | 1266.25 | 06-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.69 | 0.00 | 01-JAN-05:30 | 1072.24 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 8.08 | 0.00 | 01-JAN-00:15 | 1266.25 | 06-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.77 | 0.03 | 23-OCT-14:15 | 1254.91 | 06-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.69 | 0.00 | 01-JAN-05:30 | 1072.47 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 8.08 | 0.00 | 01-JAN-00:15 | 1254.91 | 06-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.52 | 0.02 | 30-APR-18:45 | 1473.76 | 15-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.55 | 0.00 | 01-JAN-05:15 | 1028.65 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 10.97 | 0.00 | 01-JAN-00:15 | 1473.76 | 15-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.66 | 0.02 | 29-MAR-08:45 | 1512.56 | 15-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.52 | 0.00 | 01-JAN-05:15 | 1025.85 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.14 | 0.00 | 01-JAN-00:15 | 1512.56 | 15-SEP-13:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 20.69 | 0.02 | 01-APR-22:45 | 3011.51 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 1.41 | 0.00 | 01-JAN-06:00 | 1904.49 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 19.28 | 0.00 | 01-JAN-00:15 | 3011.51 | 11-OCT-15:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 18.20 | 0.00 | 19-FEB-23:00 | 2736.96 | 21-JUL-17:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 2.96 | 0.00 | 01-JAN-06:15 | 2026.18 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 15.24 | 0.00 | 01-JAN-00:15 | 2736.96 | 21-JUL-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 21.74 | 0.04 | 24-APR-14:15 | 2607.55 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 1.21 | 0.00 | 01-JAN-05:45 | 1915.42 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 20.53 | 0.00 | 01-JAN-00:15 | 2607.55 | 11-OCT-15:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 18.25 | 0.07 | 29-JAN-14:00 | 2199.39 | 30-JUN-15:45 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 2.74 | 0.00 | 01-JAN-06:30 | 2054.46 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 15.51 | 0.00 | 01-JAN-00:15 | 2199.39 | 30-JUN-15:45 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 13.81 | 0.00 | 29-JUL-10:45 | 1633.72 | 06-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1259.54 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 12.84 | 0.00 | 02-JAN-00:30 | 1633.72 | 06-JUN-17:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 13.81 | 0.03 | 08-FEB-11:30 | 1625.63 | 30-JUN-15:45 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1261.10 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 12.85 | 0.00 | 02-JAN-00:30 | 1625.63 | 30-JUN-15:45 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 17.53 | 0.02 | 07-JUN-21:00 | 1989.11 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 1180.23 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 17.29 | 0.00 | 02-JAN-01:15 | 1989.11 | 11-OCT-16:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 17.62 | 0.02 | 26-MAY-21:00 | 2005.65 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 1176.21 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 17.38 | 0.00 | 02-JAN-01:15 | 2005.65 | 11-OCT-16:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 21.79 | 0.07 | 02-NOV-01:30 | 3046.91 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 1.40 | 0.00 | 01-JAN-05:15 | 2014.26 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 20.40 | 0.00 | 01-JAN-00:15 | 3046.91 | 11-OCT-15:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 19.11 | 0.02 | 08-FEB-18:45 | 2756.10 | 02-AUG-17:15 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 2.94 | 0.00 | 01-JAN-05:30 | 2147.79 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 16.17 | 0.00 | 01-JAN-00:15 | 2756.10 | 02-AUG-17:15 |
EnergyTransfer:Zone:F3 SE APARTMENT | 22.10 | 0.01 | 09-APR-11:15 | 2624.71 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 1.27 | 0.00 | 01-JAN-05:15 | 2031.70 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 20.83 | 0.00 | 01-JAN-00:15 | 2624.71 | 11-OCT-15:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 19.18 | 0.01 | 27-NOV-05:30 | 2234.46 | 30-JUN-15:45 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 2.74 | 0.00 | 01-JAN-05:30 | 2172.47 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 16.44 | 0.00 | 01-JAN-00:15 | 2234.46 | 30-JUN-15:45 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 14.80 | 0.01 | 30-SEP-19:15 | 1673.01 | 06-JUN-17:45 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.88 | 0.00 | 01-JAN-00:15 | 1411.34 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 13.92 | 0.00 | 02-JAN-01:30 | 1673.01 | 06-JUN-17:45 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 14.81 | 0.01 | 05-OCT-12:00 | 1663.94 | 06-JUN-17:45 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.88 | 0.00 | 01-JAN-00:15 | 1413.79 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 13.93 | 0.00 | 02-JAN-01:30 | 1663.94 | 06-JUN-17:45 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 19.00 | 0.03 | 27-APR-13:45 | 2037.26 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 1294.31 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 18.78 | 0.00 | 02-JAN-02:00 | 2037.26 | 11-OCT-16:30 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 19.03 | 0.05 | 17-DEC-03:15 | 2043.75 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 1293.47 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 18.81 | 0.00 | 02-JAN-02:00 | 2043.75 | 11-OCT-16:30 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 21.99 | 0.01 | 22-MAR-04:30 | 3057.56 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 1.52 | 0.00 | 01-JAN-05:15 | 2137.84 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 20.47 | 0.00 | 01-JAN-00:15 | 3057.56 | 11-OCT-15:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 19.41 | 0.01 | 17-FEB-12:15 | 2769.26 | 02-AUG-17:15 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 3.11 | 0.00 | 01-JAN-05:30 | 2275.64 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 16.31 | 0.00 | 01-JAN-00:15 | 2769.26 | 02-AUG-17:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 22.19 | 0.03 | 25-MAY-11:00 | 2627.29 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 1.41 | 0.00 | 01-JAN-05:15 | 2156.61 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 20.78 | 0.00 | 01-JAN-00:15 | 2627.29 | 11-OCT-15:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 19.50 | 0.05 | 29-JAN-14:45 | 2297.66 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 2.91 | 0.00 | 01-JAN-05:30 | 2297.66 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 16.59 | 0.00 | 01-JAN-00:15 | 2250.12 | 30-JUN-15:45 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 15.10 | 0.02 | 12-MAR-08:00 | 1695.14 | 06-JUN-19:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.92 | 0.00 | 01-JAN-00:15 | 1566.33 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 14.17 | 0.00 | 02-JAN-01:45 | 1695.14 | 06-JUN-19:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 15.10 | 0.02 | 20-OCT-13:45 | 1692.41 | 06-JUN-19:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.92 | 0.00 | 01-JAN-00:15 | 1569.03 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 14.18 | 0.00 | 02-JAN-01:45 | 1692.41 | 06-JUN-19:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 19.29 | 0.02 | 29-JUL-05:45 | 2058.21 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 1438.68 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 19.05 | 0.00 | 02-JAN-02:15 | 2058.21 | 11-OCT-16:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 19.30 | 0.00 | 21-MAY-08:15 | 2063.30 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 1440.18 | 24-DEC-09:45 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 19.06 | 0.00 | 02-JAN-02:15 | 2063.30 | 11-OCT-16:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 22.30 | 0.04 | 14-JAN-21:45 | 3089.57 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.63 | 0.00 | 01-JAN-03:45 | 2231.67 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 20.67 | 0.00 | 01-JAN-00:15 | 3089.57 | 11-OCT-15:30 |
EnergyTransfer:Zone:M NW APARTMENT | 19.85 | 0.03 | 19-NOV-15:15 | 2805.42 | 02-AUG-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 3.24 | 0.00 | 01-JAN-05:15 | 2368.78 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 16.61 | 0.00 | 01-JAN-00:15 | 2805.42 | 02-AUG-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 22.49 | 0.10 | 17-FEB-16:00 | 2662.96 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.53 | 0.00 | 01-JAN-02:00 | 2249.59 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 20.96 | 0.00 | 01-JAN-00:15 | 2662.96 | 11-OCT-15:30 |
EnergyTransfer:Zone:M NE APARTMENT | 19.93 | 0.02 | 06-DEC-06:00 | 2388.73 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 3.04 | 0.00 | 01-JAN-05:15 | 2388.73 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 16.89 | 0.00 | 01-JAN-00:15 | 2287.57 | 30-JUN-15:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 15.51 | 0.02 | 07-OCT-20:15 | 1749.55 | 06-JUN-19:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1692.25 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 14.55 | 0.00 | 02-JAN-01:45 | 1749.55 | 06-JUN-19:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 15.52 | 0.00 | 25-AUG-06:45 | 1746.92 | 06-JUN-19:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1694.86 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 14.56 | 0.00 | 02-JAN-01:45 | 1746.92 | 06-JUN-19:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 19.63 | 0.03 | 17-NOV-14:00 | 2098.09 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 1568.35 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 19.36 | 0.00 | 02-JAN-02:45 | 2098.09 | 11-OCT-16:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 19.64 | 0.00 | 23-APR-10:00 | 2102.98 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 1570.63 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 19.37 | 0.00 | 02-JAN-02:45 | 2102.98 | 11-OCT-16:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 21.60 | 0.03 | 20-JAN-04:00 | 3047.98 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 1.91 | 0.00 | 01-JAN-05:30 | 2373.12 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 19.69 | 0.00 | 01-JAN-00:15 | 3047.98 | 11-OCT-15:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 19.58 | 0.00 | 19-DEC-16:30 | 2774.08 | 18-AUG-17:15 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 3.69 | 0.00 | 01-JAN-06:15 | 2510.31 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 15.89 | 0.00 | 01-JAN-00:15 | 2774.08 | 18-AUG-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 21.77 | 0.01 | 01-JUL-20:00 | 2627.15 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 1.80 | 0.00 | 01-JAN-05:30 | 2389.90 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 19.97 | 0.00 | 01-JAN-00:15 | 2627.15 | 11-OCT-15:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 19.65 | 0.00 | 27-OCT-23:15 | 2528.57 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 3.49 | 0.00 | 01-JAN-06:15 | 2528.57 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 16.16 | 0.00 | 01-JAN-00:15 | 2260.36 | 06-JUN-17:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 15.02 | 0.02 | 04-DEC-12:00 | 1887.07 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 1887.07 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 13.84 | 0.00 | 02-JAN-01:15 | 1735.17 | 06-JUN-19:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 15.03 | 0.02 | 27-MAY-05:45 | 1888.85 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 1888.85 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 13.84 | 0.00 | 02-JAN-01:15 | 1732.67 | 06-JUN-19:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 18.72 | 0.03 | 03-MAR-14:15 | 2066.62 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1776.89 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 18.37 | 0.00 | 02-JAN-01:30 | 2066.62 | 11-OCT-16:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 18.73 | 0.04 | 27-MAY-09:15 | 2071.53 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1779.12 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 18.37 | 0.00 | 02-JAN-01:30 | 2071.53 | 11-OCT-16:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 21.29 | 0.00 | 20-FEB-00:45 | 3032.66 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 2.16 | 0.00 | 01-JAN-06:15 | 2485.10 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 19.13 | 0.00 | 01-JAN-00:15 | 3032.66 | 11-OCT-15:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 19.57 | 0.00 | 26-APR-11:30 | 2767.91 | 18-AUG-17:15 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 4.05 | 0.00 | 01-JAN-06:30 | 2619.85 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 15.53 | 0.00 | 01-JAN-00:15 | 2767.91 | 18-AUG-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 21.46 | 0.12 | 31-AUG-08:15 | 2616.59 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 2.04 | 0.00 | 01-JAN-06:15 | 2500.77 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 19.42 | 0.00 | 01-JAN-00:15 | 2616.59 | 11-OCT-15:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 19.65 | 0.08 | 20-JAN-02:15 | 2636.61 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 3.84 | 0.00 | 01-JAN-06:30 | 2636.61 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 15.80 | 0.00 | 01-JAN-00:15 | 2260.80 | 06-JUN-17:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 14.86 | 0.01 | 04-NOV-13:45 | 2046.81 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 1.38 | 0.00 | 01-JAN-00:15 | 2046.81 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 13.48 | 0.00 | 02-JAN-00:15 | 1739.76 | 06-JUN-19:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 14.87 | 0.02 | 26-MAY-20:15 | 2048.01 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 1.38 | 0.00 | 01-JAN-00:15 | 2048.01 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 13.49 | 0.00 | 02-JAN-00:15 | 1737.37 | 06-JUN-19:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 18.24 | 0.02 | 11-OCT-05:45 | 2059.48 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.43 | 0.00 | 01-JAN-00:15 | 1953.34 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 17.80 | 0.00 | 02-JAN-01:15 | 2059.48 | 11-OCT-16:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 18.25 | 0.01 | 02-OCT-05:45 | 2064.40 | 11-OCT-16:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.44 | 0.00 | 01-JAN-00:15 | 1955.15 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 17.81 | 0.00 | 02-JAN-01:15 | 2064.40 | 11-OCT-16:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 21.17 | 0.01 | 17-FEB-05:15 | 3031.71 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 2.41 | 0.00 | 01-JAN-06:30 | 2591.40 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 18.76 | 0.00 | 01-JAN-00:15 | 3031.71 | 11-OCT-15:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 19.74 | 0.01 | 24-OCT-12:15 | 2774.33 | 18-AUG-17:15 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 4.41 | 0.00 | 01-JAN-06:30 | 2722.37 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 15.34 | 0.00 | 01-JAN-00:15 | 2774.33 | 18-AUG-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 21.34 | 0.00 | 18-FEB-12:30 | 2619.10 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 2.28 | 0.00 | 01-JAN-06:30 | 2606.48 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 19.05 | 0.00 | 01-JAN-00:15 | 2619.10 | 11-OCT-15:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 19.81 | 0.10 | 12-DEC-00:30 | 2737.95 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 4.20 | 0.00 | 01-JAN-06:30 | 2737.95 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 15.61 | 0.00 | 01-JAN-00:15 | 2271.55 | 06-JUN-17:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 14.86 | 0.01 | 30-SEP-06:00 | 2188.82 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 1.57 | 0.00 | 01-JAN-00:30 | 2188.82 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 13.29 | 0.00 | 01-JAN-00:15 | 1752.52 | 06-JUN-19:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 14.87 | 0.02 | 01-APR-18:00 | 2189.76 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 1.57 | 0.00 | 01-JAN-00:30 | 2189.76 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 13.29 | 0.00 | 01-JAN-00:15 | 1750.19 | 06-JUN-19:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 17.94 | 0.01 | 28-MAY-06:00 | 2110.44 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.53 | 0.00 | 01-JAN-00:15 | 2110.44 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 17.41 | 0.00 | 02-JAN-00:15 | 2065.76 | 11-OCT-16:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 17.95 | 0.01 | 06-MAR-16:30 | 2111.83 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.53 | 0.00 | 01-JAN-00:15 | 2111.83 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 17.42 | 0.00 | 02-JAN-00:15 | 2070.70 | 11-OCT-16:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 21.53 | 0.00 | 23-OCT-23:15 | 3103.24 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 2.89 | 0.00 | 01-JAN-09:15 | 2801.15 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 18.64 | 0.00 | 01-JAN-00:15 | 3103.24 | 11-OCT-15:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 20.56 | 0.01 | 26-NOV-11:15 | 2922.20 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 5.10 | 0.00 | 01-JAN-09:45 | 2922.20 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 15.46 | 0.00 | 01-JAN-00:15 | 2861.91 | 18-AUG-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 21.68 | 0.14 | 27-OCT-23:45 | 2815.96 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 2.74 | 0.00 | 01-JAN-09:00 | 2815.96 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 18.94 | 0.00 | 01-JAN-00:15 | 2647.28 | 11-OCT-15:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 20.59 | 0.01 | 17-FEB-16:15 | 2936.27 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 4.86 | 0.00 | 01-JAN-09:30 | 2936.27 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 15.73 | 0.00 | 01-JAN-00:15 | 2335.22 | 06-JUN-17:30 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 15.32 | 0.00 | 09-MAY-08:00 | 2344.30 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 2.01 | 0.00 | 01-JAN-00:45 | 2344.30 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 13.31 | 0.00 | 01-JAN-00:15 | 1813.65 | 06-JUN-19:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 15.33 | 0.03 | 13-DEC-07:45 | 2344.99 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 2.01 | 0.00 | 01-JAN-00:45 | 2344.99 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 13.31 | 0.00 | 01-JAN-00:15 | 1811.28 | 06-JUN-19:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 17.91 | 0.01 | 24-MAY-09:45 | 2282.00 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.73 | 0.00 | 01-JAN-00:45 | 2282.00 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 17.18 | 0.00 | 01-JAN-00:15 | 2108.30 | 30-MAR-17:00 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 17.92 | 0.01 | 12-DEC-12:15 | 2282.95 | 24-DEC-10:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.74 | 0.00 | 01-JAN-00:45 | 2282.95 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 17.18 | 0.00 | 01-JAN-00:15 | 2113.17 | 30-MAR-17:00 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 24.60 | 0.01 | 02-NOV-11:45 | 3627.29 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 5.72 | 0.00 | 02-JAN-12:15 | 3627.29 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 18.88 | 0.00 | 01-JAN-00:15 | 3607.97 | 18-AUG-16:30 |
EnergyTransfer:Zone:T NW APARTMENT | 24.03 | 0.02 | 25-NOV-21:30 | 3699.40 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.04 | 0.00 | 10-JAN-14:45 | 3699.40 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 15.98 | 0.00 | 01-JAN-00:15 | 3467.36 | 08-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 24.35 | 0.01 | 14-SEP-03:45 | 3624.58 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 5.44 | 0.00 | 01-JAN-11:15 | 3624.58 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 18.91 | 0.00 | 01-JAN-00:15 | 3208.21 | 18-AUG-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 23.57 | 0.01 | 10-NOV-02:45 | 3695.92 | 12-FEB-06:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 7.59 | 0.00 | 01-JAN-10:45 | 3695.92 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 15.98 | 0.00 | 01-JAN-00:15 | 2832.73 | 08-JUL-16:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.54 | 0.09 | 04-NOV-01:45 | 2563.15 | 23-FEB-16:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 4.11 | 0.00 | 01-JAN-06:30 | 2563.15 | 23-FEB-16:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 13.43 | 0.00 | 01-JAN-00:15 | 2168.04 | 13-JUL-17:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.54 | 0.03 | 30-OCT-04:15 | 2558.84 | 23-FEB-16:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 4.10 | 0.00 | 01-JAN-06:30 | 2558.84 | 23-FEB-16:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 13.44 | 0.00 | 01-JAN-00:15 | 2147.54 | 13-JUL-17:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.16 | 0.03 | 27-SEP-08:30 | 2652.81 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.41 | 0.00 | 01-JAN-06:30 | 2463.66 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 16.76 | 0.00 | 01-JAN-00:15 | 2652.81 | 11-OCT-15:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.18 | 0.04 | 24-MAR-00:15 | 2656.60 | 11-OCT-15:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.42 | 0.00 | 01-JAN-06:30 | 2463.74 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 16.76 | 0.00 | 01-JAN-00:15 | 2656.60 | 11-OCT-15:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 965.35 | 405.47 | 03-AUG-01:15 | 217284.23 | 12-FEB-06:15 |
WaterSystems:EnergyTransfer | 781.94 | 405.47 | 03-AUG-01:15 | 55126.70 | 02-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 781.94 | 405.47 | 03-AUG-01:15 | 55126.70 | 02-FEB-08:00 |
EnergyTransfer:HVAC | 2337.18 | 0.00 | 01-JAN-11:15 | 288411.53 | 20-AUG-15:30 |
CoolingCoils:EnergyTransfer | 2064.82 | 0.00 | 01-JAN-00:15 | 288411.53 | 20-AUG-15:30 |
HeatingCoils:EnergyTransfer | 272.37 | 0.00 | 01-JAN-11:15 | 216134.00 | 12-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 209.22 | 0.00 | 01-JAN-11:15 | 167916.22 | 12-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 209.22 | 0.00 | 01-JAN-11:15 | 167916.22 | 12-FEB-06:00 |
Boilers:EnergyTransfer | 183.41 | 0.00 | 01-JAN-09:30 | 164507.66 | 12-FEB-06:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 2.022 | -12.212 | 0.000 | 0.000 | 3.743 | 2.413 | 12.213 | 17.949 | 0.000 | 0.353 | 0.000 | 0.000 | -7.796 | 0.000 | -5.895 | -12.790 |
G NW APARTMENT | 3.557 | -9.909 | 0.000 | 0.000 | 3.777 | 2.413 | 12.213 | 10.772 | 0.000 | 0.350 | 0.000 | 0.000 | -8.005 | 0.000 | -5.404 | -9.762 |
OFFICE | 1.929 | -17.745 | 0.000 | 0.000 | 0.515 | 21.954 | 7.547 | 17.852 | 0.000 | 0.196 | 0.000 | 0.000 | -7.731 | 0.000 | -2.354 | -22.163 |
G NE APARTMENT | 3.328 | -10.073 | 0.000 | 0.000 | 3.789 | 2.413 | 12.213 | 10.572 | 0.000 | 0.350 | 0.000 | 0.000 | -7.634 | 0.000 | -5.353 | -9.604 |
G N1 APARTMENT | 1.689 | -8.076 | 0.000 | 0.000 | 3.789 | 2.413 | 12.213 | 4.352 | 0.000 | 0.275 | 0.000 | 0.000 | -4.940 | 0.000 | -4.283 | -7.432 |
G N2 APARTMENT | 1.685 | -8.081 | 0.000 | 0.000 | 3.790 | 2.413 | 12.213 | 4.351 | 0.000 | 0.275 | 0.000 | 0.000 | -4.937 | 0.000 | -4.281 | -7.427 |
G S1 APARTMENT | 0.549 | -10.968 | 0.000 | 0.000 | 3.743 | 2.413 | 12.213 | 11.630 | 0.000 | 0.273 | 0.000 | 0.000 | -4.730 | 0.000 | -4.819 | -10.304 |
G S2 APARTMENT | 0.525 | -11.139 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 11.616 | 0.000 | 0.274 | 0.000 | 0.000 | -4.739 | 0.000 | -4.859 | -10.044 |
F2 SW APARTMENT | 1.411 | -19.280 | 0.000 | 0.000 | 3.670 | 2.413 | 12.213 | 17.023 | 0.000 | 0.467 | 0.000 | 0.000 | -8.544 | 0.000 | -7.937 | -1.435 |
F2 NW APARTMENT | 2.959 | -15.237 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 10.120 | 0.000 | 0.461 | 0.000 | 0.000 | -8.714 | 0.000 | -7.293 | -0.647 |
F2 SE APARTMENT | 1.213 | -20.526 | 0.000 | 0.000 | 3.669 | 2.413 | 12.213 | 16.966 | 0.000 | 0.467 | 0.001 | 0.000 | -8.403 | 0.000 | -8.006 | -0.004 |
F2 NE APARTMENT | 2.743 | -15.506 | 0.000 | 0.000 | 3.737 | 2.413 | 12.213 | 9.922 | 0.000 | 0.460 | 0.000 | 0.000 | -8.293 | 0.000 | -7.225 | -0.463 |
F2 N1 APARTMENT | 0.963 | -12.843 | 0.000 | 0.000 | 3.727 | 2.413 | 12.213 | 4.008 | 0.000 | 0.349 | 0.401 | 0.000 | -5.451 | 0.000 | -5.780 | -0.000 |
F2 N2 APARTMENT | 0.960 | -12.846 | 0.000 | 0.000 | 3.728 | 2.413 | 12.213 | 4.007 | 0.000 | 0.349 | 0.399 | 0.000 | -5.447 | 0.000 | -5.777 | -0.000 |
F2 S1 APARTMENT | 0.242 | -17.290 | 0.000 | 0.000 | 3.657 | 2.413 | 12.213 | 11.040 | 0.000 | 0.351 | 0.000 | 0.000 | -5.197 | 0.000 | -6.489 | -0.940 |
F2 S2 APARTMENT | 0.241 | -17.382 | 0.000 | 0.000 | 3.656 | 2.413 | 12.213 | 11.036 | 0.000 | 0.352 | 0.000 | 0.000 | -5.201 | 0.000 | -6.501 | -0.826 |
F3 SW APARTMENT | 1.397 | -20.397 | 0.000 | 0.000 | 3.661 | 2.413 | 12.213 | 16.634 | 0.000 | 0.580 | 1.186 | 0.000 | -8.739 | 0.000 | -8.947 | -0.000 |
F3 NW APARTMENT | 2.941 | -16.165 | 0.000 | 0.000 | 3.714 | 2.413 | 12.213 | 9.866 | 0.000 | 0.572 | 1.649 | 0.000 | -8.935 | 0.000 | -8.268 | -0.000 |
F3 SE APARTMENT | 1.274 | -20.825 | 0.000 | 0.000 | 3.667 | 2.413 | 12.213 | 16.630 | 0.000 | 0.578 | 1.519 | 0.000 | -8.534 | 0.000 | -8.934 | -0.000 |
F3 NE APARTMENT | 2.742 | -16.437 | 0.000 | 0.000 | 3.726 | 2.413 | 12.213 | 9.674 | 0.000 | 0.570 | 1.798 | 0.000 | -8.500 | 0.000 | -8.199 | -0.000 |
F3 N1 APARTMENT | 0.880 | -13.923 | 0.000 | 0.000 | 3.712 | 2.413 | 12.213 | 3.893 | 0.000 | 0.438 | 2.537 | 0.000 | -5.617 | 0.000 | -6.545 | -0.000 |
F3 N2 APARTMENT | 0.881 | -13.930 | 0.000 | 0.000 | 3.713 | 2.413 | 12.213 | 3.892 | 0.000 | 0.438 | 2.534 | 0.000 | -5.613 | 0.000 | -6.541 | -0.000 |
F3 S1 APARTMENT | 0.219 | -18.783 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 10.789 | 0.000 | 0.441 | 1.686 | 0.000 | -5.335 | 0.000 | -7.284 | -0.000 |
F3 S2 APARTMENT | 0.218 | -18.809 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 10.787 | 0.000 | 0.442 | 1.717 | 0.000 | -5.335 | 0.000 | -7.287 | -0.000 |
F4 SW APARTMENT | 1.516 | -20.474 | 0.000 | 0.000 | 3.661 | 2.413 | 12.213 | 16.385 | 0.000 | 0.631 | 1.968 | 0.000 | -8.826 | 0.000 | -9.487 | -0.000 |
F4 NW APARTMENT | 3.107 | -16.306 | 0.000 | 0.000 | 3.713 | 2.413 | 12.213 | 9.709 | 0.000 | 0.623 | 2.369 | 0.000 | -9.047 | 0.000 | -8.793 | -0.000 |
F4 SE APARTMENT | 1.413 | -20.775 | 0.000 | 0.000 | 3.668 | 2.413 | 12.213 | 16.399 | 0.000 | 0.629 | 2.106 | 0.000 | -8.606 | 0.000 | -9.459 | -0.000 |
F4 NE APARTMENT | 2.908 | -16.587 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 9.524 | 0.000 | 0.620 | 2.513 | 0.000 | -8.604 | 0.000 | -8.724 | -0.000 |
F4 N1 APARTMENT | 0.922 | -14.174 | 0.000 | 0.000 | 3.707 | 2.413 | 12.213 | 3.827 | 0.000 | 0.473 | 3.228 | 0.000 | -5.703 | 0.000 | -6.905 | -0.000 |
F4 N2 APARTMENT | 0.920 | -14.178 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 3.827 | 0.000 | 0.473 | 3.226 | 0.000 | -5.699 | 0.000 | -6.901 | -0.000 |
F4 S1 APARTMENT | 0.242 | -19.049 | 0.000 | 0.000 | 3.638 | 2.413 | 12.213 | 10.630 | 0.000 | 0.477 | 2.484 | 0.000 | -5.396 | 0.000 | -7.651 | -0.000 |
F4 S2 APARTMENT | 0.243 | -19.056 | 0.000 | 0.000 | 3.638 | 2.413 | 12.213 | 10.629 | 0.000 | 0.477 | 2.489 | 0.000 | -5.394 | 0.000 | -7.651 | -0.000 |
M SW APARTMENT | 1.629 | -20.673 | 0.000 | 0.000 | 3.662 | 2.413 | 12.213 | 16.188 | 0.000 | 0.672 | 2.874 | 0.000 | -8.896 | 0.000 | -10.082 | -0.000 |
M NW APARTMENT | 3.240 | -16.610 | 0.000 | 0.000 | 3.713 | 2.413 | 12.213 | 9.586 | 0.000 | 0.663 | 3.282 | 0.000 | -9.137 | 0.000 | -9.362 | -0.000 |
M SE APARTMENT | 1.527 | -20.958 | 0.000 | 0.000 | 3.669 | 2.413 | 12.213 | 16.211 | 0.000 | 0.669 | 2.976 | 0.000 | -8.670 | 0.000 | -10.050 | -0.000 |
M NE APARTMENT | 3.037 | -16.894 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 9.404 | 0.000 | 0.659 | 3.425 | 0.000 | -8.688 | 0.000 | -9.293 | -0.000 |
M N1 APARTMENT | 0.959 | -14.548 | 0.000 | 0.000 | 3.705 | 2.413 | 12.213 | 3.776 | 0.000 | 0.501 | 4.084 | 0.000 | -5.770 | 0.000 | -7.333 | -0.000 |
M N2 APARTMENT | 0.961 | -14.556 | 0.000 | 0.000 | 3.706 | 2.413 | 12.213 | 3.775 | 0.000 | 0.500 | 4.083 | 0.000 | -5.766 | 0.000 | -7.329 | -0.000 |
M S1 APARTMENT | 0.270 | -19.362 | 0.000 | 0.000 | 3.638 | 2.413 | 12.213 | 10.505 | 0.000 | 0.505 | 3.361 | 0.000 | -5.442 | 0.000 | -8.100 | -0.000 |
M S2 APARTMENT | 0.271 | -19.365 | 0.000 | 0.000 | 3.638 | 2.413 | 12.213 | 10.504 | 0.000 | 0.505 | 3.361 | 0.000 | -5.440 | 0.000 | -8.099 | -0.000 |
F6 SW APARTMENT | 1.913 | -19.685 | 0.000 | 0.000 | 3.671 | 2.413 | 12.213 | 16.070 | 0.000 | 0.706 | 2.093 | 0.000 | -8.881 | 0.000 | -10.512 | -0.000 |
F6 NW APARTMENT | 3.688 | -15.887 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 9.525 | 0.000 | 0.696 | 2.511 | 0.000 | -9.131 | 0.000 | -9.750 | -0.000 |
F6 SE APARTMENT | 1.802 | -19.972 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 16.100 | 0.000 | 0.703 | 2.193 | 0.000 | -8.653 | 0.000 | -10.478 | -0.000 |
F6 NE APARTMENT | 3.485 | -16.164 | 0.000 | 0.000 | 3.733 | 2.413 | 12.213 | 9.349 | 0.000 | 0.692 | 2.643 | 0.000 | -8.681 | 0.000 | -9.683 | -0.000 |
F6 N1 APARTMENT | 1.186 | -13.836 | 0.000 | 0.000 | 3.715 | 2.413 | 12.213 | 3.757 | 0.000 | 0.523 | 3.386 | 0.000 | -5.766 | 0.000 | -7.593 | -0.000 |
F6 N2 APARTMENT | 1.187 | -13.843 | 0.000 | 0.000 | 3.716 | 2.413 | 12.213 | 3.757 | 0.000 | 0.523 | 3.385 | 0.000 | -5.762 | 0.000 | -7.588 | -0.000 |
F6 S1 APARTMENT | 0.352 | -18.369 | 0.000 | 0.000 | 3.647 | 2.413 | 12.213 | 10.429 | 0.000 | 0.528 | 2.622 | 0.000 | -5.433 | 0.000 | -8.403 | -0.000 |
F6 S2 APARTMENT | 0.355 | -18.372 | 0.000 | 0.000 | 3.648 | 2.413 | 12.213 | 10.428 | 0.000 | 0.528 | 2.621 | 0.000 | -5.431 | 0.000 | -8.403 | -0.000 |
F7 SW APARTMENT | 2.157 | -19.128 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 15.960 | 0.000 | 0.734 | 1.741 | 0.000 | -8.881 | 0.000 | -10.888 | -0.000 |
F7 NW APARTMENT | 4.047 | -15.525 | 0.000 | 0.000 | 3.729 | 2.413 | 12.213 | 9.464 | 0.000 | 0.724 | 2.174 | 0.000 | -9.140 | 0.000 | -10.099 | -0.000 |
F7 SE APARTMENT | 2.041 | -19.421 | 0.000 | 0.000 | 3.687 | 2.413 | 12.213 | 15.995 | 0.000 | 0.731 | 1.843 | 0.000 | -8.650 | 0.000 | -10.852 | -0.000 |
F7 NE APARTMENT | 3.842 | -15.802 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 9.292 | 0.000 | 0.720 | 2.303 | 0.000 | -8.688 | 0.000 | -10.032 | -0.000 |
F7 N1 APARTMENT | 1.376 | -13.483 | 0.000 | 0.000 | 3.723 | 2.413 | 12.213 | 3.737 | 0.000 | 0.542 | 3.076 | 0.000 | -5.771 | 0.000 | -7.826 | -0.000 |
F7 N2 APARTMENT | 1.376 | -13.491 | 0.000 | 0.000 | 3.723 | 2.413 | 12.213 | 3.736 | 0.000 | 0.542 | 3.075 | 0.000 | -5.767 | 0.000 | -7.821 | -0.000 |
F7 S1 APARTMENT | 0.435 | -17.804 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 10.359 | 0.000 | 0.548 | 2.279 | 0.000 | -5.431 | 0.000 | -8.666 | -0.000 |
F7 S2 APARTMENT | 0.437 | -17.807 | 0.000 | 0.000 | 3.656 | 2.413 | 12.213 | 10.358 | 0.000 | 0.548 | 2.277 | 0.000 | -5.429 | 0.000 | -8.665 | -0.000 |
F8 SW APARTMENT | 2.405 | -18.760 | 0.000 | 0.000 | 3.685 | 2.413 | 12.213 | 15.862 | 0.000 | 0.769 | 1.542 | 0.000 | -8.882 | 0.000 | -11.248 | -0.000 |
F8 NW APARTMENT | 4.406 | -15.337 | 0.000 | 0.000 | 3.735 | 2.413 | 12.213 | 9.407 | 0.000 | 0.758 | 1.998 | 0.000 | -9.153 | 0.000 | -10.440 | -0.000 |
F8 SE APARTMENT | 2.284 | -19.053 | 0.000 | 0.000 | 3.694 | 2.413 | 12.213 | 15.902 | 0.000 | 0.764 | 1.643 | 0.000 | -8.649 | 0.000 | -11.211 | -0.000 |
F8 NE APARTMENT | 4.198 | -15.608 | 0.000 | 0.000 | 3.745 | 2.413 | 12.213 | 9.239 | 0.000 | 0.752 | 2.120 | 0.000 | -8.700 | 0.000 | -10.373 | -0.000 |
F8 N1 APARTMENT | 1.574 | -13.286 | 0.000 | 0.000 | 3.729 | 2.413 | 12.213 | 3.717 | 0.000 | 0.567 | 2.911 | 0.000 | -5.777 | 0.000 | -8.061 | -0.000 |
F8 N2 APARTMENT | 1.575 | -13.293 | 0.000 | 0.000 | 3.730 | 2.413 | 12.213 | 3.717 | 0.000 | 0.567 | 2.910 | 0.000 | -5.773 | 0.000 | -8.057 | -0.000 |
F8 S1 APARTMENT | 0.527 | -17.412 | 0.000 | 0.000 | 3.662 | 2.413 | 12.213 | 10.298 | 0.000 | 0.573 | 2.079 | 0.000 | -5.430 | 0.000 | -8.923 | -0.000 |
F8 S2 APARTMENT | 0.532 | -17.418 | 0.000 | 0.000 | 3.663 | 2.413 | 12.213 | 10.297 | 0.000 | 0.573 | 2.078 | 0.000 | -5.428 | 0.000 | -8.923 | -0.000 |
F9 SW APARTMENT | 2.886 | -18.640 | 0.000 | 0.000 | 3.694 | 2.413 | 12.213 | 15.788 | 0.000 | 0.797 | 1.258 | 0.000 | -8.867 | 0.000 | -11.541 | -0.000 |
F9 NW APARTMENT | 5.100 | -15.455 | 0.000 | 0.000 | 3.740 | 2.413 | 12.213 | 9.361 | 0.000 | 0.785 | 1.731 | 0.000 | -9.153 | 0.000 | -10.734 | -0.000 |
F9 SE APARTMENT | 2.736 | -18.943 | 0.000 | 0.000 | 3.702 | 2.413 | 12.213 | 15.831 | 0.000 | 0.792 | 1.392 | 0.000 | -8.633 | 0.000 | -11.503 | -0.001 |
F9 NE APARTMENT | 4.861 | -15.727 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 9.197 | 0.000 | 0.780 | 1.876 | 0.000 | -8.699 | 0.000 | -10.665 | -0.000 |
F9 N1 APARTMENT | 2.014 | -13.307 | 0.000 | 0.000 | 3.736 | 2.413 | 12.213 | 3.701 | 0.000 | 0.589 | 2.670 | 0.000 | -5.771 | 0.000 | -8.258 | -0.000 |
F9 N2 APARTMENT | 2.015 | -13.313 | 0.000 | 0.000 | 3.736 | 2.413 | 12.213 | 3.700 | 0.000 | 0.589 | 2.669 | 0.000 | -5.768 | 0.000 | -8.254 | -0.000 |
F9 S1 APARTMENT | 0.732 | -17.175 | 0.000 | 0.000 | 3.673 | 2.413 | 12.213 | 10.253 | 0.000 | 0.594 | 1.830 | 0.000 | -5.415 | 0.000 | -9.118 | -0.000 |
F9 S2 APARTMENT | 0.736 | -17.181 | 0.000 | 0.000 | 3.673 | 2.413 | 12.213 | 10.252 | 0.000 | 0.595 | 1.831 | 0.000 | -5.413 | 0.000 | -9.118 | -0.000 |
T SW APARTMENT | 5.716 | -18.879 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 15.517 | 0.000 | 0.816 | 0.001 | 0.000 | -8.473 | 0.000 | -11.719 | -1.327 |
T NW APARTMENT | 8.045 | -15.982 | 0.000 | 0.000 | 3.757 | 2.413 | 12.213 | 9.141 | 0.000 | 0.804 | 0.000 | 0.000 | -8.818 | 0.000 | -10.984 | -0.589 |
T SE APARTMENT | 5.439 | -18.906 | 0.000 | 0.000 | 3.733 | 2.413 | 12.213 | 15.577 | 0.000 | 0.815 | 0.000 | 0.000 | -8.263 | 0.000 | -11.704 | -1.316 |
T NE APARTMENT | 7.589 | -15.979 | 0.000 | 0.000 | 3.769 | 2.413 | 12.213 | 9.015 | 0.000 | 0.802 | 0.000 | 0.000 | -8.400 | 0.000 | -10.922 | -0.500 |
T N1 APARTMENT | 4.106 | -13.432 | 0.000 | 0.000 | 3.756 | 2.413 | 12.213 | 3.630 | 0.000 | 0.605 | 0.625 | 0.000 | -5.537 | 0.000 | -8.378 | -0.000 |
T N2 APARTMENT | 4.102 | -13.439 | 0.000 | 0.000 | 3.757 | 2.413 | 12.213 | 3.628 | 0.000 | 0.604 | 0.629 | 0.000 | -5.532 | 0.000 | -8.375 | -0.000 |
T S1 APARTMENT | 2.409 | -16.754 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 10.116 | 0.000 | 0.617 | 0.000 | 0.000 | -5.201 | 0.000 | -9.201 | -0.320 |
T S2 APARTMENT | 2.415 | -16.762 | 0.000 | 0.000 | 3.709 | 2.413 | 12.213 | 10.113 | 0.000 | 0.617 | 0.001 | 0.000 | -5.198 | 0.000 | -9.204 | -0.317 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 4.178 | 0.000 | 2.428 | 2.216 | 0.000 | -1.852 | 0.000 | -25.500 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.883 | 0.000 | 0.025 | 0.000 | 0.000 | -1.120 | 0.000 | -0.648 | -18.669 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.823 | 0.000 | 0.028 | 0.000 | 0.000 | -1.167 | 0.000 | -0.792 | -18.421 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.786 | 0.000 | 0.030 | 0.000 | 0.000 | -1.193 | 0.000 | -0.898 | -18.255 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.745 | 0.000 | 0.026 | 0.000 | 0.000 | -1.230 | 0.000 | -1.031 | -36.569 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.751 | 0.000 | 0.035 | 0.000 | 0.000 | -1.203 | 0.000 | -1.039 | -18.073 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.745 | 0.000 | 0.037 | 0.000 | 0.000 | -1.194 | 0.000 | -1.085 | -18.033 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.735 | 0.000 | 0.039 | 0.000 | 0.000 | -1.192 | 0.000 | -1.131 | -17.980 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.727 | 0.000 | 0.039 | 0.000 | 0.000 | -1.191 | 0.000 | -1.171 | -17.933 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.668 | 0.000 | 0.021 | 0.000 | 0.000 | -1.167 | 0.000 | -1.247 | -25.741 |
Total Facility | 167.816 | -1300.580 | 0.000 | 0.000 | 293.221 | 416.414 | 980.287 | 827.874 | 0.000 | 47.957 | 139.491 | 0.000 | -576.391 | 0.000 | -708.197 | -287.898 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 08-SEP-16:30 | 0.00 | -2300.68 | 0.00 | 0.00 | 84.10 | 144.04 | 588.62 | 2747.07 | 0.00 | 56.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1319.18 |
G NW APARTMENT | 18-AUG-17:00 | 0.00 | -2215.74 | 0.00 | 0.00 | 84.75 | 144.04 | 588.62 | 2249.88 | 0.00 | 82.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.78 |
OFFICE | 06-SEP-13:15 | 0.00 | -2942.51 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 2418.81 | 0.00 | 65.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1773.87 |
G NE APARTMENT | 08-JUL-17:20 | 0.00 | -1684.53 | 0.00 | 0.00 | 140.48 | 194.45 | 588.62 | 1035.74 | 0.00 | 41.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -316.26 |
G N1 APARTMENT | 30-JUN-15:38 | 0.00 | -1271.64 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 398.63 | 0.00 | 482.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.98 |
G N2 APARTMENT | 30-JUN-15:38 | 0.00 | -1262.32 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 398.57 | 0.00 | 481.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -238.02 |
G S1 APARTMENT | 15-SEP-13:30 | 0.00 | -1473.65 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2051.96 | 0.00 | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1038.60 |
G S2 APARTMENT | 15-SEP-13:30 | 0.00 | -1512.45 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2051.09 | 0.00 | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -998.93 |
F2 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3011.89 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 3062.40 | 0.00 | 332.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1003.66 |
F2 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2741.71 | 0.00 | 0.00 | 141.10 | 194.45 | 588.62 | 2247.98 | 0.00 | 94.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.38 |
F2 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2608.05 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 1702.30 | 0.00 | 334.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.96 |
F2 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2237.68 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 605.16 | 0.00 | 694.06 | 317.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 30-JUN-15:38 | 0.00 | -1655.21 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 365.45 | 0.00 | 637.85 | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 30-JUN-15:38 | 0.00 | -1647.89 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 365.37 | 0.00 | 636.44 | 25.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 11-OCT-16:38 | 0.00 | -1988.50 | 0.00 | 0.00 | 84.36 | 144.04 | 588.62 | 700.20 | 0.00 | 47.58 | 423.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S2 APARTMENT | 11-OCT-16:30 | 0.00 | -2004.31 | 0.00 | 0.00 | 83.82 | 144.04 | 588.62 | 907.52 | 0.00 | 92.49 | 187.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3047.44 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 3004.44 | 0.00 | 362.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -940.60 |
F3 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2759.36 | 0.00 | 0.00 | 141.14 | 194.45 | 588.62 | 2224.15 | 0.00 | 112.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.21 |
F3 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2625.29 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 1677.32 | 0.00 | 371.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.05 |
F3 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2276.42 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 588.69 | 0.00 | 790.08 | 277.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 30-JUN-15:38 | 0.00 | -1694.82 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 354.13 | 0.00 | 724.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.95 |
F3 N2 APARTMENT | 30-JUN-15:38 | 0.00 | -1687.51 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 354.05 | 0.00 | 722.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9.60 |
F3 S1 APARTMENT | 11-OCT-16:38 | 0.00 | -2100.88 | 0.00 | 0.00 | 83.80 | 144.04 | 588.62 | 683.30 | 0.00 | 43.24 | 557.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S2 APARTMENT | 11-OCT-16:38 | 0.00 | -2107.56 | 0.00 | 0.00 | 83.89 | 144.04 | 588.62 | 683.63 | 0.00 | 45.48 | 561.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3058.13 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2964.46 | 0.00 | 389.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -916.61 |
F4 NW APARTMENT | 21-JUL-17:20 | 0.00 | -2770.86 | 0.00 | 0.00 | 141.18 | 194.45 | 588.62 | 2206.36 | 0.00 | 125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -484.94 |
F4 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2627.91 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1659.40 | 0.00 | 396.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.94 |
F4 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2294.59 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 577.98 | 0.00 | 858.49 | 237.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 30-JUN-15:38 | 0.00 | -1714.83 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 346.98 | 0.00 | 786.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38.88 |
F4 N2 APARTMENT | 30-JUN-15:38 | 0.00 | -1707.59 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 346.90 | 0.00 | 784.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.32 |
F4 S1 APARTMENT | 11-OCT-16:38 | 0.00 | -2124.89 | 0.00 | 0.00 | 83.80 | 144.04 | 588.62 | 673.73 | 0.00 | 45.38 | 589.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S2 APARTMENT | 11-OCT-16:38 | 0.00 | -2130.14 | 0.00 | 0.00 | 83.87 | 144.04 | 588.62 | 674.04 | 0.00 | 47.56 | 592.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SW APARTMENT | 11-OCT-15:30 | 0.00 | -3090.17 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2932.63 | 0.00 | 412.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.38 |
M NW APARTMENT | 02-AUG-17:10 | 0.00 | -2806.99 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2136.35 | 0.00 | 133.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387.26 |
M SE APARTMENT | 11-OCT-15:30 | 0.00 | -2663.61 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1644.85 | 0.00 | 419.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.18 |
M NE APARTMENT | 30-JUN-15:38 | 0.00 | -2334.80 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 569.09 | 0.00 | 912.14 | 232.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 30-JUN-15:38 | 0.00 | -1755.79 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 341.08 | 0.00 | 834.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40.78 |
M N2 APARTMENT | 30-JUN-15:38 | 0.00 | -1748.62 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 341.00 | 0.00 | 833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46.04 |
M S1 APARTMENT | 11-OCT-16:38 | 0.00 | -2167.68 | 0.00 | 0.00 | 83.92 | 144.04 | 588.62 | 666.44 | 0.00 | 49.85 | 634.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 11-OCT-16:38 | 0.00 | -2172.74 | 0.00 | 0.00 | 83.99 | 144.04 | 588.62 | 666.73 | 0.00 | 52.10 | 637.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3048.56 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2908.33 | 0.00 | 431.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -911.40 |
F6 NW APARTMENT | 18-AUG-17:10 | 0.00 | -2775.55 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 2081.87 | 0.00 | 182.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -414.15 |
F6 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2627.78 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1634.86 | 0.00 | 438.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.72 |
F6 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2302.64 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 564.01 | 0.00 | 954.23 | 163.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 06-JUN-19:08 | 0.00 | -1735.73 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 39.54 | 0.00 | 443.24 | 356.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 06-JUN-19:08 | 0.00 | -1733.23 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 39.61 | 0.00 | 443.25 | 354.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 11-OCT-16:38 | 0.00 | -2137.57 | 0.00 | 0.00 | 84.03 | 144.04 | 588.62 | 661.83 | 0.00 | 53.64 | 605.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S2 APARTMENT | 11-OCT-16:38 | 0.00 | -2142.64 | 0.00 | 0.00 | 84.10 | 144.04 | 588.62 | 662.11 | 0.00 | 55.98 | 607.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3033.24 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2886.99 | 0.00 | 447.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -921.77 |
F7 NW APARTMENT | 18-AUG-17:10 | 0.00 | -2769.42 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 2075.25 | 0.00 | 192.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -423.64 |
F7 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2617.22 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1625.70 | 0.00 | 454.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.52 |
F7 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2296.09 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 559.02 | 0.00 | 989.63 | 126.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 06-JUN-19:08 | 0.00 | -1740.35 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 39.40 | 0.00 | 460.42 | 344.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 06-JUN-19:08 | 0.00 | -1737.96 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 39.47 | 0.00 | 460.43 | 341.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 11-OCT-16:38 | 0.00 | -2111.72 | 0.00 | 0.00 | 84.17 | 144.04 | 588.62 | 657.62 | 0.00 | 55.90 | 581.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S2 APARTMENT | 11-OCT-16:38 | 0.00 | -2090.95 | 0.00 | 0.00 | 84.24 | 144.04 | 588.62 | 657.90 | 0.00 | 56.10 | 560.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3032.28 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2868.09 | 0.00 | 462.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -918.95 |
F8 NW APARTMENT | 18-AUG-17:10 | 0.00 | -2775.86 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 2068.95 | 0.00 | 201.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -419.83 |
F8 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2619.73 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1617.44 | 0.00 | 469.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87.94 |
F8 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2303.08 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 554.25 | 0.00 | 1020.18 | 108.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 06-JUN-19:08 | 0.00 | -1753.13 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 38.94 | 0.00 | 474.65 | 343.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 06-JUN-19:08 | 0.00 | -1750.81 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 39.01 | 0.00 | 474.65 | 341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 11-OCT-16:30 | 0.00 | -2063.97 | 0.00 | 0.00 | 83.56 | 144.04 | 588.62 | 851.73 | 0.00 | 121.12 | 274.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S2 APARTMENT | 11-OCT-16:30 | 0.00 | -2068.90 | 0.00 | 0.00 | 83.63 | 144.04 | 588.62 | 851.97 | 0.00 | 123.49 | 277.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SW APARTMENT | 11-OCT-15:30 | 0.00 | -3103.74 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 2850.50 | 0.00 | 482.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -850.12 |
F9 NW APARTMENT | 18-AUG-17:10 | 0.00 | -2863.43 | 0.00 | 0.00 | 141.83 | 194.45 | 588.62 | 2060.35 | 0.00 | 209.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -331.76 |
F9 SE APARTMENT | 11-OCT-15:30 | 0.00 | -2647.89 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1609.20 | 0.00 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.11 |
F9 NE APARTMENT | 30-JUN-15:38 | 0.00 | -2353.41 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 547.49 | 0.00 | 1044.22 | 141.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 06-JUN-19:08 | 0.00 | -1814.27 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 36.84 | 0.00 | 486.48 | 394.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 06-JUN-19:08 | 0.00 | -1811.90 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 36.90 | 0.00 | 486.48 | 392.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 30-MAR-17:00 | 0.00 | -2109.65 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 587.36 | 0.00 | 676.71 | 28.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S2 APARTMENT | 30-MAR-17:00 | 0.00 | -2114.52 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 587.52 | 0.00 | 679.47 | 30.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 18-AUG-16:30 | 0.00 | -3608.91 | 0.00 | 0.00 | 83.88 | 144.04 | 588.62 | 2315.23 | 0.00 | 203.22 | 273.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 08-JUL-16:30 | 0.00 | -3467.58 | 0.00 | 0.00 | 84.25 | 144.04 | 588.62 | 2261.98 | 0.00 | 120.54 | 268.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 18-AUG-13:00 | 0.00 | -3208.05 | 0.00 | 0.00 | 40.41 | 28.81 | 388.49 | 1967.05 | 0.00 | 108.25 | 675.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 08-JUL-16:30 | 0.00 | -2832.94 | 0.00 | 0.00 | 84.14 | 144.04 | 588.62 | 1140.59 | 0.00 | 120.58 | 754.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 30-JUN-15:38 | 0.00 | -2193.02 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 313.32 | 0.00 | 1011.14 | 247.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 30-JUN-15:38 | 0.00 | -2176.19 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 313.32 | 0.00 | 1007.26 | 234.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 11-OCT-15:30 | 0.00 | -2653.83 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1439.17 | 0.00 | 457.42 | 136.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 11-OCT-15:30 | 0.00 | -2657.61 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 1439.31 | 0.00 | 459.28 | 138.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-AUG-16:30 | 0.00 | -169277.06 | 0.00 | 0.00 | 6657.08 | 18221.75 | 47207.76 | 101373.12 | 0.00 | 16658.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20841.32 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 12-FEB-06:00 | 1718.44 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1463.30 | 0.00 | -669.25 | -122.29 |
G NW APARTMENT | 12-FEB-06:00 | 1767.05 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1467.26 | 0.00 | -669.25 | -166.94 |
OFFICE | 12-FEB-07:00 | 1830.20 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.30 | 0.00 | -600.02 | -281.14 |
G NE APARTMENT | 12-FEB-06:00 | 1788.04 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1460.70 | 0.00 | -669.25 | -194.49 |
G N1 APARTMENT | 23-FEB-15:40 | 1707.66 | 0.00 | 0.00 | 0.00 | 45.87 | 50.41 | 400.26 | 146.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1484.42 | -865.98 |
G N2 APARTMENT | 23-FEB-15:40 | 1695.81 | 0.00 | 0.00 | 0.00 | 45.84 | 50.41 | 400.26 | 145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1484.87 | -853.35 |
G S1 APARTMENT | 24-DEC-09:25 | 1274.23 | 0.00 | 0.00 | 0.00 | 46.75 | 28.81 | 394.37 | 68.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1246.09 | -566.44 |
G S2 APARTMENT | 24-DEC-09:25 | 1291.32 | 0.00 | 0.00 | 0.00 | 46.70 | 28.81 | 394.37 | 67.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1246.22 | -582.94 |
F2 SW APARTMENT | 12-FEB-06:00 | 1904.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 36.22 | 0.00 | -1514.87 | 0.00 | -962.34 | 0.00 |
F2 NW APARTMENT | 12-FEB-06:00 | 2026.28 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1526.54 | 0.00 | -962.34 | -73.80 |
F2 SE APARTMENT | 12-FEB-06:00 | 1915.52 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 | -1502.38 | 0.00 | -962.34 | 0.00 |
F2 NE APARTMENT | 12-FEB-06:00 | 2054.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1513.50 | 0.00 | -962.34 | -115.16 |
F2 N1 APARTMENT | 23-FEB-15:45 | 1601.03 | 0.00 | 0.00 | 0.00 | 43.73 | 50.41 | 400.26 | 97.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1935.37 | -257.77 |
F2 N2 APARTMENT | 23-FEB-15:45 | 1605.09 | 0.00 | 0.00 | 0.00 | 43.70 | 50.41 | 400.26 | 97.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1935.40 | -261.31 |
F2 S1 APARTMENT | 19-JAN-10:55 | 1417.13 | 0.00 | 0.00 | 0.00 | 45.58 | 28.81 | 406.15 | 220.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1558.73 | -559.79 |
F2 S2 APARTMENT | 19-JAN-10:55 | 1380.58 | 0.00 | 0.00 | 0.00 | 45.53 | 28.81 | 406.15 | 220.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1560.01 | -521.41 |
F3 SW APARTMENT | 12-FEB-06:00 | 2014.37 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 125.96 | 0.00 | -1536.94 | 0.00 | -1139.79 | 0.00 |
F3 NW APARTMENT | 12-FEB-06:00 | 2147.91 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 | -1552.47 | 0.00 | -1139.79 | 0.00 |
F3 SE APARTMENT | 12-FEB-06:00 | 2031.83 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 92.74 | 0.00 | -1521.18 | 0.00 | -1139.79 | 0.00 |
F3 NE APARTMENT | 12-FEB-06:00 | 2172.62 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1536.56 | 0.00 | -1139.79 | -32.67 |
F3 N1 APARTMENT | 23-FEB-15:45 | 1937.37 | 0.00 | 0.00 | 0.00 | 43.02 | 50.41 | 400.26 | 78.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2229.35 | -280.01 |
F3 N2 APARTMENT | 23-FEB-15:45 | 1937.91 | 0.00 | 0.00 | 0.00 | 42.99 | 50.41 | 400.26 | 77.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2229.37 | -280.07 |
F3 S1 APARTMENT | 24-DEC-09:25 | 1544.43 | 0.00 | 0.00 | 0.00 | 45.11 | 28.81 | 394.37 | 16.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1776.49 | -252.26 |
F3 S2 APARTMENT | 24-DEC-09:25 | 1539.58 | 0.00 | 0.00 | 0.00 | 45.10 | 28.81 | 394.37 | 15.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1776.67 | -247.18 |
F4 SW APARTMENT | 12-FEB-06:00 | 2137.96 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 150.65 | 0.00 | -1550.53 | 0.00 | -1274.48 | 0.00 |
F4 NW APARTMENT | 12-FEB-06:00 | 2275.78 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 30.94 | 0.00 | -1568.64 | 0.00 | -1274.48 | 0.00 |
F4 SE APARTMENT | 12-FEB-06:00 | 2156.75 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 114.13 | 0.00 | -1532.80 | 0.00 | -1274.48 | 0.00 |
F4 NE APARTMENT | 12-FEB-06:00 | 2297.83 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1550.94 | 0.00 | -1274.48 | -8.81 |
F4 N1 APARTMENT | 23-FEB-15:45 | 1988.91 | 0.00 | 0.00 | 0.00 | 42.90 | 50.41 | 400.26 | 69.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2459.66 | -92.37 |
F4 N2 APARTMENT | 23-FEB-15:45 | 1991.10 | 0.00 | 0.00 | 0.00 | 42.87 | 50.41 | 400.26 | 69.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2459.68 | -94.09 |
F4 S1 APARTMENT | 24-DEC-09:25 | 1848.00 | 0.00 | 0.00 | 0.00 | 45.06 | 28.81 | 394.37 | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1937.60 | -386.57 |
F4 S2 APARTMENT | 24-DEC-09:25 | 1850.27 | 0.00 | 0.00 | 0.00 | 45.06 | 28.81 | 394.37 | 8.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1937.54 | -388.98 |
M SW APARTMENT | 12-FEB-06:00 | 2231.80 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 178.73 | 0.00 | -1561.33 | 0.00 | -1385.60 | 0.00 |
M NW APARTMENT | 12-FEB-06:00 | 2368.92 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 61.64 | 0.00 | -1581.36 | 0.00 | -1385.60 | 0.00 |
M SE APARTMENT | 12-FEB-06:00 | 2249.74 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 141.71 | 0.00 | -1542.25 | 0.00 | -1385.60 | 0.00 |
M NE APARTMENT | 12-FEB-06:00 | 2388.91 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 22.66 | 0.00 | -1562.37 | 0.00 | -1385.60 | 0.00 |
M N1 APARTMENT | 23-FEB-15:45 | 2035.38 | 0.00 | 0.00 | 0.00 | 42.89 | 50.41 | 400.26 | 64.26 | 0.00 | 0.00 | 61.08 | 0.00 | 0.00 | 0.00 | -2654.29 | 0.00 |
M N2 APARTMENT | 23-FEB-15:45 | 2037.20 | 0.00 | 0.00 | 0.00 | 42.85 | 50.41 | 400.26 | 63.84 | 0.00 | 0.00 | 59.74 | 0.00 | 0.00 | 0.00 | -2654.30 | 0.00 |
M S1 APARTMENT | 24-DEC-09:25 | 2095.97 | 0.00 | 0.00 | 0.00 | 45.03 | 28.81 | 394.37 | 1.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2074.97 | -490.98 |
M S2 APARTMENT | 24-DEC-09:25 | 2100.26 | 0.00 | 0.00 | 0.00 | 45.04 | 28.81 | 394.37 | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2074.85 | -495.53 |
F6 SW APARTMENT | 12-FEB-06:00 | 2373.27 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 139.35 | 0.00 | -1567.58 | 0.00 | -1481.44 | 0.00 |
F6 NW APARTMENT | 12-FEB-06:00 | 2510.47 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 23.83 | 0.00 | -1589.26 | 0.00 | -1481.44 | 0.00 |
F6 SE APARTMENT | 12-FEB-06:00 | 2390.07 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 102.51 | 0.00 | -1547.55 | 0.00 | -1481.44 | 0.00 |
F6 NE APARTMENT | 23-FEB-15:40 | 2716.98 | 0.00 | 0.00 | 0.00 | 44.00 | 50.41 | 400.26 | 116.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2978.57 | -349.38 |
F6 N1 APARTMENT | 23-FEB-15:40 | 2479.61 | 0.00 | 0.00 | 0.00 | 43.39 | 50.41 | 400.26 | 65.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2850.92 | -188.70 |
F6 N2 APARTMENT | 23-FEB-15:40 | 2454.53 | 0.00 | 0.00 | 0.00 | 43.36 | 50.41 | 400.26 | 65.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2851.44 | -162.65 |
F6 S1 APARTMENT | 24-DEC-09:25 | 2532.26 | 0.00 | 0.00 | 0.00 | 45.39 | 28.81 | 394.37 | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2189.85 | -812.66 |
F6 S2 APARTMENT | 24-DEC-09:25 | 2529.97 | 0.00 | 0.00 | 0.00 | 45.39 | 28.81 | 394.37 | 1.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2189.86 | -810.49 |
F7 SW APARTMENT | 12-FEB-06:00 | 2485.26 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 118.14 | 0.00 | -1573.37 | 0.00 | -1566.43 | 0.00 |
F7 NW APARTMENT | 23-FEB-15:40 | 2962.33 | 0.00 | 0.00 | 0.00 | 44.16 | 50.41 | 400.26 | 874.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3139.11 | -1192.44 |
F7 SE APARTMENT | 12-FEB-06:00 | 2500.95 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 81.65 | 0.00 | -1552.56 | 0.00 | -1566.43 | 0.00 |
F7 NE APARTMENT | 23-FEB-15:40 | 3252.52 | 0.00 | 0.00 | 0.00 | 44.42 | 50.41 | 400.26 | 118.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3128.83 | -737.38 |
F7 N1 APARTMENT | 23-FEB-15:40 | 3039.63 | 0.00 | 0.00 | 0.00 | 43.80 | 50.41 | 400.26 | 67.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2994.91 | -606.47 |
F7 N2 APARTMENT | 23-FEB-15:40 | 3015.17 | 0.00 | 0.00 | 0.00 | 43.77 | 50.41 | 400.26 | 66.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2995.45 | -581.02 |
F7 S1 APARTMENT | 24-DEC-09:25 | 2568.48 | 0.00 | 0.00 | 0.00 | 45.65 | 28.81 | 394.37 | 1.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2301.28 | -737.23 |
F7 S2 APARTMENT | 24-DEC-09:25 | 2566.84 | 0.00 | 0.00 | 0.00 | 45.65 | 28.81 | 394.37 | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2301.29 | -735.68 |
F8 SW APARTMENT | 12-FEB-06:00 | 2591.57 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 93.51 | 0.00 | -1578.22 | 0.00 | -1643.26 | 0.00 |
F8 NW APARTMENT | 23-FEB-15:40 | 3407.71 | 0.00 | 0.00 | 0.00 | 44.49 | 50.41 | 400.26 | 867.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3277.21 | -1493.28 |
F8 SE APARTMENT | 12-FEB-06:00 | 2606.67 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 56.96 | 0.00 | -1556.77 | 0.00 | -1643.26 | 0.00 |
F8 NE APARTMENT | 23-FEB-15:40 | 3485.49 | 0.00 | 0.00 | 0.00 | 44.75 | 50.41 | 400.26 | 120.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3273.18 | -827.94 |
F8 N1 APARTMENT | 23-FEB-15:40 | 3506.46 | 0.00 | 0.00 | 0.00 | 44.13 | 50.41 | 400.26 | 68.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3128.12 | -941.51 |
F8 N2 APARTMENT | 23-FEB-15:40 | 3484.55 | 0.00 | 0.00 | 0.00 | 44.10 | 50.41 | 400.26 | 67.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3128.65 | -918.65 |
F8 S1 APARTMENT | 24-DEC-09:25 | 2608.05 | 0.00 | 0.00 | 0.00 | 45.87 | 28.81 | 394.37 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2403.97 | -673.87 |
F8 S2 APARTMENT | 24-DEC-09:25 | 2607.01 | 0.00 | 0.00 | 0.00 | 45.87 | 28.81 | 394.37 | 0.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2403.97 | -672.91 |
F9 SW APARTMENT | 12-FEB-06:00 | 2801.33 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1578.62 | 0.00 | -1713.68 | -45.43 |
F9 NW APARTMENT | 23-FEB-15:40 | 3491.24 | 0.00 | 0.00 | 0.00 | 44.89 | 50.41 | 400.26 | 865.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3413.90 | -1438.08 |
F9 SE APARTMENT | 12-FEB-06:00 | 2816.17 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1556.72 | 0.00 | -1713.68 | -82.17 |
F9 NE APARTMENT | 23-FEB-15:40 | 3524.71 | 0.00 | 0.00 | 0.00 | 45.17 | 50.41 | 400.26 | 124.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3411.03 | -734.18 |
F9 N1 APARTMENT | 23-FEB-15:40 | 3699.07 | 0.00 | 0.00 | 0.00 | 44.60 | 50.41 | 400.26 | 72.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3255.42 | -1011.07 |
F9 N2 APARTMENT | 23-FEB-15:40 | 3707.45 | 0.00 | 0.00 | 0.00 | 44.57 | 50.41 | 400.26 | 71.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3255.44 | -1018.97 |
F9 S1 APARTMENT | 24-DEC-09:25 | 2612.31 | 0.00 | 0.00 | 0.00 | 46.19 | 28.81 | 394.37 | 2.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2499.59 | -584.30 |
F9 S2 APARTMENT | 24-DEC-09:25 | 2611.97 | 0.00 | 0.00 | 0.00 | 46.19 | 28.81 | 394.37 | 2.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2499.60 | -584.00 |
T SW APARTMENT | 12-FEB-06:00 | 3627.48 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1544.86 | 0.00 | -1778.78 | -840.24 |
T NW APARTMENT | 23-FEB-15:40 | 3741.60 | 0.00 | 0.00 | 0.00 | 44.49 | 50.41 | 400.26 | 843.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3548.69 | -1532.01 |
T SE APARTMENT | 12-FEB-06:00 | 3624.80 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1523.69 | 0.00 | -1778.78 | -858.73 |
T NE APARTMENT | 23-FEB-15:40 | 3709.80 | 0.00 | 0.00 | 0.00 | 45.12 | 50.41 | 400.26 | 120.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3543.25 | -783.23 |
T N1 APARTMENT | 23-FEB-15:40 | 3934.11 | 0.00 | 0.00 | 0.00 | 44.65 | 50.41 | 400.26 | 73.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3380.95 | -1122.27 |
T N2 APARTMENT | 23-FEB-15:40 | 3944.60 | 0.00 | 0.00 | 0.00 | 44.61 | 50.41 | 400.26 | 73.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3380.92 | -1132.24 |
T S1 APARTMENT | 24-DEC-09:25 | 2624.19 | 0.00 | 0.00 | 0.00 | 46.48 | 28.81 | 394.37 | 6.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2590.34 | -510.28 |
T S2 APARTMENT | 24-DEC-09:25 | 2625.12 | 0.00 | 0.00 | 0.00 | 46.47 | 28.81 | 394.37 | 6.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2590.36 | -511.18 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-06:00 | 149854.66 | 0.00 | 0.00 | 0.00 | 14984.00 | 14239.10 | 20328.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101906.20 | 0.00 | -89615.92 | -7884.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Sec1.1A-General InformationData | |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 90.75 |
Number of hours cooling loads not met | 176.00 |
Number of hours not met | 266.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.68 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 74.33 | 0.00 | 229.94 | 196926.82 | 0.00 | 0.00 |
Space Cooling | 606.11 | 70064.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48.82 | 1624.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 27.19 | 2877.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 546.99 | 17344.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1030.26 | 79629.86 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3040.45 | 1260.20 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3040.45 |
Natural Gas | 0.00 | 1260.20 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4300.65 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 9.48 |
Space Cooling | 77.34 |
Fans-Interior | 69.80 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 33.88 |
Subtotal | 387.99 |
Natural Gas [MJ/m2] | |
Space Heating | 29.34 |
Service Water Heating | 131.47 |
Miscellaneous | -0.00 |
Subtotal | 160.81 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.68 |
Space Heating | 7.07 |
Space Cooling | 14.09 |
Fans-Interior | 12.72 |
Service Water Heating | 23.96 |
Receptacle Equipment | 26.30 |
Miscellaneous | 6.17 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.201855 |
G NW APARTMENT DIRECT AIR | 0.201851 |
OFFICE DIRECT AIR | 0.271360 |
G NE APARTMENT DIRECT AIR | 0.155908 |
G N1 APARTMENT DIRECT AIR | 0.113606 |
G N2 APARTMENT DIRECT AIR | 0.112451 |
G S1 APARTMENT DIRECT AIR | 0.111740 |
G S2 APARTMENT DIRECT AIR | 0.116508 |
F2 SW APARTMENT DIRECT AIR | 0.252921 |
F2 NW APARTMENT DIRECT AIR | 0.249734 |
F2 SE APARTMENT DIRECT AIR | 0.229786 |
F2 NE APARTMENT DIRECT AIR | 0.199095 |
F2 N1 APARTMENT DIRECT AIR | 0.145992 |
F2 N2 APARTMENT DIRECT AIR | 0.145068 |
F2 S1 APARTMENT DIRECT AIR | 0.146501 |
F2 S2 APARTMENT DIRECT AIR | 0.148168 |
F3 SW APARTMENT DIRECT AIR | 0.253459 |
F3 NW APARTMENT DIRECT AIR | 0.250577 |
F3 SE APARTMENT DIRECT AIR | 0.216121 |
F3 NE APARTMENT DIRECT AIR | 0.201657 |
F3 N1 APARTMENT DIRECT AIR | 0.148495 |
F3 N2 APARTMENT DIRECT AIR | 0.147588 |
F3 S1 APARTMENT DIRECT AIR | 0.149406 |
F3 S2 APARTMENT DIRECT AIR | 0.150132 |
F4 SW APARTMENT DIRECT AIR | 0.254105 |
F4 NW APARTMENT DIRECT AIR | 0.251106 |
F4 SE APARTMENT DIRECT AIR | 0.215699 |
F4 NE APARTMENT DIRECT AIR | 0.202702 |
F4 N1 APARTMENT DIRECT AIR | 0.149784 |
F4 N2 APARTMENT DIRECT AIR | 0.148889 |
F4 S1 APARTMENT DIRECT AIR | 0.150860 |
F4 S2 APARTMENT DIRECT AIR | 0.151447 |
M SW APARTMENT DIRECT AIR | 0.256974 |
M NW APARTMENT DIRECT AIR | 0.253949 |
M SE APARTMENT DIRECT AIR | 0.218783 |
M NE APARTMENT DIRECT AIR | 0.205916 |
M N1 APARTMENT DIRECT AIR | 0.153097 |
M N2 APARTMENT DIRECT AIR | 0.152212 |
M S1 APARTMENT DIRECT AIR | 0.154239 |
M S2 APARTMENT DIRECT AIR | 0.154806 |
F6 SW APARTMENT DIRECT AIR | 0.253469 |
F6 NW APARTMENT DIRECT AIR | 0.250263 |
F6 SE APARTMENT DIRECT AIR | 0.215661 |
F6 NE APARTMENT DIRECT AIR | 0.202641 |
F6 N1 APARTMENT DIRECT AIR | 0.150060 |
F6 N2 APARTMENT DIRECT AIR | 0.149188 |
F6 S1 APARTMENT DIRECT AIR | 0.151365 |
F6 S2 APARTMENT DIRECT AIR | 0.151929 |
F7 SW APARTMENT DIRECT AIR | 0.252315 |
F7 NW APARTMENT DIRECT AIR | 0.249049 |
F7 SE APARTMENT DIRECT AIR | 0.214837 |
F7 NE APARTMENT DIRECT AIR | 0.201757 |
F7 N1 APARTMENT DIRECT AIR | 0.149318 |
F7 N2 APARTMENT DIRECT AIR | 0.148456 |
F7 S1 APARTMENT DIRECT AIR | 0.150691 |
F7 S2 APARTMENT DIRECT AIR | 0.151255 |
F8 SW APARTMENT DIRECT AIR | 0.252579 |
F8 NW APARTMENT DIRECT AIR | 0.249254 |
F8 SE APARTMENT DIRECT AIR | 0.215331 |
F8 NE APARTMENT DIRECT AIR | 0.202184 |
F8 N1 APARTMENT DIRECT AIR | 0.149926 |
F8 N2 APARTMENT DIRECT AIR | 0.149075 |
F8 S1 APARTMENT DIRECT AIR | 0.151311 |
F8 S2 APARTMENT DIRECT AIR | 0.151875 |
F9 SW APARTMENT DIRECT AIR | 0.261045 |
F9 NW APARTMENT DIRECT AIR | 0.257502 |
F9 SE APARTMENT DIRECT AIR | 0.219993 |
F9 NE APARTMENT DIRECT AIR | 0.206266 |
F9 N1 APARTMENT DIRECT AIR | 0.157498 |
F9 N2 APARTMENT DIRECT AIR | 0.156647 |
F9 S1 APARTMENT DIRECT AIR | 0.157012 |
F9 S2 APARTMENT DIRECT AIR | 0.157643 |
T SW APARTMENT DIRECT AIR | 0.312952 |
T NW APARTMENT DIRECT AIR | 0.305479 |
T SE APARTMENT DIRECT AIR | 0.272189 |
T NE APARTMENT DIRECT AIR | 0.250279 |
T N1 APARTMENT DIRECT AIR | 0.191249 |
T N2 APARTMENT DIRECT AIR | 0.189338 |
T S1 APARTMENT DIRECT AIR | 0.215507 |
T S2 APARTMENT DIRECT AIR | 0.216108 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.201855 |
AIRLOOP G NW MAIN BRANCH | 0.201851 |
AIRLOOP OFFICE MAIN BRANCH | 0.271360 |
AIRLOOP G NE MAIN BRANCH | 0.155908 |
AIRLOOP G N1 MAIN BRANCH | 0.113606 |
AIRLOOP G N2 MAIN BRANCH | 0.112451 |
AIRLOOP G S1 MAIN BRANCH | 0.111740 |
AIRLOOP G S2 MAIN BRANCH | 0.116508 |
AIRLOOP F2 SW MAIN BRANCH | 0.252921 |
AIRLOOP F2 NW MAIN BRANCH | 0.249734 |
AIRLOOP F2 SE MAIN BRANCH | 0.229786 |
AIRLOOP F2 NE MAIN BRANCH | 0.199095 |
AIRLOOP F2 N1 MAIN BRANCH | 0.145992 |
AIRLOOP F2 N2 MAIN BRANCH | 0.145068 |
AIRLOOP F2 S1 MAIN BRANCH | 0.146501 |
AIRLOOP F2 S2 MAIN BRANCH | 0.148168 |
AIRLOOP F3 SW MAIN BRANCH | 0.253459 |
AIRLOOP F3 NW MAIN BRANCH | 0.250577 |
AIRLOOP F3 SE MAIN BRANCH | 0.216121 |
AIRLOOP F3 NE MAIN BRANCH | 0.201657 |
AIRLOOP F3 N1 MAIN BRANCH | 0.148495 |
AIRLOOP F3 N2 MAIN BRANCH | 0.147588 |
AIRLOOP F3 S1 MAIN BRANCH | 0.149406 |
AIRLOOP F3 S2 MAIN BRANCH | 0.150132 |
AIRLOOP F4 SW MAIN BRANCH | 0.254105 |
AIRLOOP F4 NW MAIN BRANCH | 0.251106 |
AIRLOOP F4 SE MAIN BRANCH | 0.215699 |
AIRLOOP F4 NE MAIN BRANCH | 0.202702 |
AIRLOOP F4 N1 MAIN BRANCH | 0.149784 |
AIRLOOP F4 N2 MAIN BRANCH | 0.148889 |
AIRLOOP F4 S1 MAIN BRANCH | 0.150860 |
AIRLOOP F4 S2 MAIN BRANCH | 0.151447 |
AIRLOOP M SW MAIN BRANCH | 0.256974 |
AIRLOOP M NW MAIN BRANCH | 0.253949 |
AIRLOOP M SE MAIN BRANCH | 0.218783 |
AIRLOOP M NE MAIN BRANCH | 0.205916 |
AIRLOOP M N1 MAIN BRANCH | 0.153097 |
AIRLOOP M N2 MAIN BRANCH | 0.152212 |
AIRLOOP M S1 MAIN BRANCH | 0.154239 |
AIRLOOP M S2 MAIN BRANCH | 0.154806 |
AIRLOOP F6 SW MAIN BRANCH | 0.253469 |
AIRLOOP F6 NW MAIN BRANCH | 0.250263 |
AIRLOOP F6 SE MAIN BRANCH | 0.215661 |
AIRLOOP F6 NE MAIN BRANCH | 0.202641 |
AIRLOOP F6 N1 MAIN BRANCH | 0.150060 |
AIRLOOP F6 N2 MAIN BRANCH | 0.149188 |
AIRLOOP F6 S1 MAIN BRANCH | 0.151365 |
AIRLOOP F6 S2 MAIN BRANCH | 0.151929 |
AIRLOOP F7 SW MAIN BRANCH | 0.252315 |
AIRLOOP F7 NW MAIN BRANCH | 0.249049 |
AIRLOOP F7 SE MAIN BRANCH | 0.214837 |
AIRLOOP F7 NE MAIN BRANCH | 0.201757 |
AIRLOOP F7 N1 MAIN BRANCH | 0.149318 |
AIRLOOP F7 N2 MAIN BRANCH | 0.148456 |
AIRLOOP F7 S1 MAIN BRANCH | 0.150691 |
AIRLOOP F7 S2 MAIN BRANCH | 0.151255 |
AIRLOOP F8 SW MAIN BRANCH | 0.252579 |
AIRLOOP F8 NW MAIN BRANCH | 0.249254 |
AIRLOOP F8 SE MAIN BRANCH | 0.215331 |
AIRLOOP F8 NE MAIN BRANCH | 0.202184 |
AIRLOOP F8 N1 MAIN BRANCH | 0.149926 |
AIRLOOP F8 N2 MAIN BRANCH | 0.149075 |
AIRLOOP F8 S1 MAIN BRANCH | 0.151311 |
AIRLOOP F8 S2 MAIN BRANCH | 0.151875 |
AIRLOOP F9 SW MAIN BRANCH | 0.261045 |
AIRLOOP F9 NW MAIN BRANCH | 0.257502 |
AIRLOOP F9 SE MAIN BRANCH | 0.219993 |
AIRLOOP F9 NE MAIN BRANCH | 0.206266 |
AIRLOOP F9 N1 MAIN BRANCH | 0.157498 |
AIRLOOP F9 N2 MAIN BRANCH | 0.156647 |
AIRLOOP F9 S1 MAIN BRANCH | 0.157012 |
AIRLOOP F9 S2 MAIN BRANCH | 0.157643 |
AIRLOOP T SW MAIN BRANCH | 0.312952 |
AIRLOOP T NW MAIN BRANCH | 0.305479 |
AIRLOOP T SE MAIN BRANCH | 0.272189 |
AIRLOOP T NE MAIN BRANCH | 0.250279 |
AIRLOOP T N1 MAIN BRANCH | 0.191249 |
AIRLOOP T N2 MAIN BRANCH | 0.189338 |
AIRLOOP T S1 MAIN BRANCH | 0.215507 |
AIRLOOP T S2 MAIN BRANCH | 0.216108 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.201855 |
AIRLOOP G NW | 0.201851 |
AIRLOOP OFFICE | 0.271360 |
AIRLOOP G NE | 0.155908 |
AIRLOOP G N1 | 0.113606 |
AIRLOOP G N2 | 0.112451 |
AIRLOOP G S1 | 0.111740 |
AIRLOOP G S2 | 0.116508 |
AIRLOOP F2 SW | 0.252921 |
AIRLOOP F2 NW | 0.249734 |
AIRLOOP F2 SE | 0.229786 |
AIRLOOP F2 NE | 0.199095 |
AIRLOOP F2 N1 | 0.145992 |
AIRLOOP F2 N2 | 0.145068 |
AIRLOOP F2 S1 | 0.146501 |
AIRLOOP F2 S2 | 0.148168 |
AIRLOOP F3 SW | 0.253459 |
AIRLOOP F3 NW | 0.250577 |
AIRLOOP F3 SE | 0.216121 |
AIRLOOP F3 NE | 0.201657 |
AIRLOOP F3 N1 | 0.148495 |
AIRLOOP F3 N2 | 0.147588 |
AIRLOOP F3 S1 | 0.149406 |
AIRLOOP F3 S2 | 0.150132 |
AIRLOOP F4 SW | 0.254105 |
AIRLOOP F4 NW | 0.251106 |
AIRLOOP F4 SE | 0.215699 |
AIRLOOP F4 NE | 0.202702 |
AIRLOOP F4 N1 | 0.149784 |
AIRLOOP F4 N2 | 0.148889 |
AIRLOOP F4 S1 | 0.150860 |
AIRLOOP F4 S2 | 0.151447 |
AIRLOOP M SW | 0.256974 |
AIRLOOP M NW | 0.253949 |
AIRLOOP M SE | 0.218783 |
AIRLOOP M NE | 0.205916 |
AIRLOOP M N1 | 0.153097 |
AIRLOOP M N2 | 0.152212 |
AIRLOOP M S1 | 0.154239 |
AIRLOOP M S2 | 0.154806 |
AIRLOOP F6 SW | 0.253469 |
AIRLOOP F6 NW | 0.250263 |
AIRLOOP F6 SE | 0.215661 |
AIRLOOP F6 NE | 0.202641 |
AIRLOOP F6 N1 | 0.150060 |
AIRLOOP F6 N2 | 0.149188 |
AIRLOOP F6 S1 | 0.151365 |
AIRLOOP F6 S2 | 0.151929 |
AIRLOOP F7 SW | 0.252315 |
AIRLOOP F7 NW | 0.249049 |
AIRLOOP F7 SE | 0.214837 |
AIRLOOP F7 NE | 0.201757 |
AIRLOOP F7 N1 | 0.149318 |
AIRLOOP F7 N2 | 0.148456 |
AIRLOOP F7 S1 | 0.150691 |
AIRLOOP F7 S2 | 0.151255 |
AIRLOOP F8 SW | 0.252579 |
AIRLOOP F8 NW | 0.249254 |
AIRLOOP F8 SE | 0.215331 |
AIRLOOP F8 NE | 0.202184 |
AIRLOOP F8 N1 | 0.149926 |
AIRLOOP F8 N2 | 0.149075 |
AIRLOOP F8 S1 | 0.151311 |
AIRLOOP F8 S2 | 0.151875 |
AIRLOOP F9 SW | 0.261045 |
AIRLOOP F9 NW | 0.257502 |
AIRLOOP F9 SE | 0.219993 |
AIRLOOP F9 NE | 0.206266 |
AIRLOOP F9 N1 | 0.157498 |
AIRLOOP F9 N2 | 0.156647 |
AIRLOOP F9 S1 | 0.157012 |
AIRLOOP F9 S2 | 0.157643 |
AIRLOOP T SW | 0.312952 |
AIRLOOP T NW | 0.305479 |
AIRLOOP T SE | 0.272189 |
AIRLOOP T NE | 0.250279 |
AIRLOOP T N1 | 0.191249 |
AIRLOOP T N2 | 0.189338 |
AIRLOOP T S1 | 0.215507 |
AIRLOOP T S2 | 0.216108 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.201855 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.201851 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.271360 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.155908 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.113606 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.112451 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.111740 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.116508 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.252921 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.249734 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.229786 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.199095 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.145992 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.145068 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.146501 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.148168 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.253459 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.250577 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.216121 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.201657 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.148495 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.147588 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.149406 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.150132 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.254105 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.251106 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.215699 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.202702 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.149784 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.148889 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.150860 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.151447 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.256974 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.253949 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.218783 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.205916 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.153097 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.152212 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.154239 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.154806 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.253469 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.250263 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.215661 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.202641 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.150060 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.149188 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.151365 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.151929 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.252315 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.249049 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.214837 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.201757 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.149318 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.148456 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.150691 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.151255 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.252579 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.249254 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.215331 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.202184 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.149926 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.149075 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.151311 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.151875 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.261045 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.257502 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.219993 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.206266 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.157498 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.156647 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.157012 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.157643 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.312952 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.305479 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.272189 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.250279 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.191249 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.189338 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.215507 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.216108 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.201855 | 3605.76 | 2350.37 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.201851 | 3599.80 | 2346.36 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.271360 | 4858.16 | 3168.21 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.155908 | 2938.60 | 1865.94 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.113606 | 2300.56 | 1414.07 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.112451 | 2283.83 | 1402.07 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.111740 | 2335.15 | 1424.30 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.116508 | 2402.88 | 1473.80 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.252921 | 4363.58 | 2889.27 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.249734 | 4317.02 | 2854.56 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.229786 | 4044.69 | 2654.41 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.199095 | 3597.96 | 2329.08 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.145992 | 2788.52 | 1757.14 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.145068 | 2775.30 | 1747.57 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.146501 | 2854.02 | 1793.09 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.148168 | 2877.47 | 1810.35 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.253459 | 4405.16 | 2905.73 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.250577 | 4359.11 | 2871.91 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.216121 | 3883.26 | 2521.90 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.201657 | 3662.34 | 2363.90 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.148495 | 2840.40 | 1788.06 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.147588 | 2827.41 | 1778.66 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.149406 | 2911.20 | 1828.12 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.150132 | 2921.35 | 1835.61 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.254105 | 4436.76 | 2918.86 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.251106 | 4389.17 | 2883.87 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.215699 | 3899.03 | 2523.89 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.202702 | 3698.32 | 2381.00 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.149784 | 2870.99 | 1805.18 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.148889 | 2858.14 | 1795.89 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.150860 | 2943.91 | 1846.90 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.151447 | 2952.11 | 1852.95 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.256974 | 4495.24 | 2953.75 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.253949 | 4447.34 | 2918.52 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.218783 | 3959.95 | 2560.93 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.205916 | 3760.89 | 2419.35 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.153097 | 2928.16 | 1842.54 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.152212 | 2915.44 | 1833.35 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.154239 | 3001.73 | 1884.98 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.154806 | 3009.66 | 1890.82 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.253469 | 4461.87 | 2922.08 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.250263 | 4411.51 | 2885.03 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.215661 | 3931.03 | 2533.09 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.202641 | 3729.47 | 2389.91 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.150060 | 2893.37 | 1813.77 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.149188 | 2880.80 | 1804.71 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.151365 | 2969.37 | 1857.76 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.151929 | 2977.27 | 1863.57 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.252315 | 4459.38 | 2914.12 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.249049 | 4408.23 | 2876.48 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.214837 | 3932.51 | 2528.46 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.201757 | 3729.83 | 2384.63 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.149318 | 2890.19 | 1808.41 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.148456 | 2877.73 | 1799.45 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.150691 | 2967.16 | 1853.04 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.151255 | 2975.05 | 1858.85 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.252579 | 4475.34 | 2920.40 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.249254 | 4423.39 | 2882.17 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.215331 | 3951.15 | 2537.04 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.202184 | 3747.34 | 2392.50 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.149926 | 2905.53 | 1816.79 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.149075 | 2893.21 | 1807.93 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.151311 | 2982.58 | 1861.51 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.151875 | 2990.50 | 1867.33 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.261045 | 4601.73 | 3008.87 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.257502 | 4550.57 | 2970.67 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.219993 | 4027.92 | 2588.50 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.206266 | 3815.87 | 2437.94 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.157498 | 3020.15 | 1897.14 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.156647 | 3007.87 | 1888.29 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.157012 | 3070.24 | 1922.68 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.157643 | 3079.10 | 1929.19 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.312952 | 5350.32 | 3555.97 | 0.000117 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.305479 | 5237.34 | 3472.87 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.272189 | 4809.35 | 3148.97 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.250279 | 4453.07 | 2898.83 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.191249 | 3514.42 | 2255.53 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.189338 | 3487.28 | 2235.72 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.215507 | 3901.54 | 2530.19 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.216108 | 3909.80 | 2536.35 | 0.000085 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.201855 | 0.201855 | 0.201855 | 0.201855 | 3605.76 | 3605.76 | 2787.85 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.201851 | 0.201851 | 0.201851 | 0.201851 | 3599.80 | 3599.80 | 2791.26 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.271360 | 0.271360 | 0.271360 | 0.271360 | 4858.16 | 4858.16 | 3597.31 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.155908 | 0.155908 | 0.155908 | 0.155908 | 2938.60 | 2938.60 | 2791.46 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.113606 | 0.113606 | 0.113606 | 0.113606 | 2300.56 | 2300.56 | 2070.73 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.112451 | 0.112451 | 0.112451 | 0.112451 | 2283.83 | 2283.83 | 2070.72 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.111740 | 0.111740 | 0.111740 | 0.111740 | 2335.15 | 2335.15 | 2063.63 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.116508 | 0.116508 | 0.116508 | 0.116508 | 2402.88 | 2402.88 | 2072.12 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.252921 | 0.252921 | 0.252921 | 0.252921 | 4363.58 | 4363.58 | 2815.15 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.249734 | 0.249734 | 0.249734 | 0.249734 | 4317.02 | 4317.02 | 2820.60 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.229786 | 0.229786 | 0.229786 | 0.229786 | 4044.69 | 4044.69 | 2837.02 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.199095 | 0.199095 | 0.199095 | 0.199095 | 3597.96 | 3597.96 | 2817.24 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.145992 | 0.145992 | 0.145992 | 0.145992 | 2788.52 | 2788.52 | 1920.95 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.145068 | 0.145068 | 0.145068 | 0.145068 | 2775.30 | 2775.30 | 1920.87 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.146501 | 0.146501 | 0.146501 | 0.146501 | 2854.02 | 2854.02 | 1918.08 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.148168 | 0.148168 | 0.148168 | 0.148168 | 2877.47 | 2877.47 | 1919.67 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.253459 | 0.253459 | 0.253459 | 0.253459 | 4405.16 | 4405.16 | 2852.24 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.250577 | 0.250577 | 0.250577 | 0.250577 | 4359.11 | 4359.11 | 2862.02 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.216121 | 0.216121 | 0.216121 | 0.216121 | 3883.26 | 3883.26 | 2849.45 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.201657 | 0.201657 | 0.201657 | 0.201657 | 3662.34 | 3662.34 | 2856.42 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.148495 | 0.148495 | 0.148495 | 0.148495 | 2840.40 | 2840.40 | 1914.37 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.147588 | 0.147588 | 0.147588 | 0.147588 | 2827.41 | 2827.41 | 1914.23 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.149406 | 0.149406 | 0.149406 | 0.149406 | 2911.20 | 2911.20 | 1905.10 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.150132 | 0.150132 | 0.150132 | 0.150132 | 2921.35 | 2921.35 | 1905.22 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.254105 | 0.254105 | 0.254105 | 0.254105 | 4436.76 | 4436.76 | 2921.03 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.251106 | 0.251106 | 0.251106 | 0.251106 | 4389.17 | 4389.17 | 2933.73 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.215699 | 0.215699 | 0.215699 | 0.215699 | 3899.03 | 3899.03 | 2914.16 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.202702 | 0.202702 | 0.202702 | 0.202702 | 3698.32 | 3698.32 | 2926.56 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.149784 | 0.149784 | 0.149784 | 0.149784 | 2870.99 | 2870.99 | 1948.27 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.148889 | 0.148889 | 0.148889 | 0.148889 | 2858.14 | 2858.14 | 1948.09 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.150860 | 0.150860 | 0.150860 | 0.150860 | 2943.91 | 2943.91 | 1935.75 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.151447 | 0.151447 | 0.151447 | 0.151447 | 2952.11 | 2952.11 | 1935.60 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.256974 | 0.256974 | 0.256974 | 0.256974 | 4495.24 | 4495.24 | 2961.32 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.253949 | 0.253949 | 0.253949 | 0.253949 | 4447.34 | 4447.34 | 2974.90 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.218783 | 0.218783 | 0.218783 | 0.218783 | 3959.95 | 3959.95 | 2953.01 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.205916 | 0.205916 | 0.205916 | 0.205916 | 3760.89 | 3760.89 | 2966.57 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.153097 | 0.153097 | 0.153097 | 0.153097 | 2928.16 | 2928.16 | 1961.05 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.152212 | 0.152212 | 0.152212 | 0.152212 | 2915.44 | 2915.44 | 1960.84 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.154239 | 0.154239 | 0.154239 | 0.154239 | 3001.73 | 3001.73 | 1947.61 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.154806 | 0.154806 | 0.154806 | 0.154806 | 3009.66 | 3009.66 | 1947.40 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.253469 | 0.253469 | 0.253469 | 0.253469 | 4461.87 | 4461.87 | 3063.65 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.250263 | 0.250263 | 0.250263 | 0.250263 | 4411.51 | 4411.51 | 3079.68 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.215661 | 0.215661 | 0.215661 | 0.215661 | 3931.03 | 3931.03 | 3054.34 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.202641 | 0.202641 | 0.202641 | 0.202641 | 3729.47 | 3729.47 | 3070.38 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.150060 | 0.150060 | 0.150060 | 0.150060 | 2893.37 | 2893.37 | 2037.46 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.149188 | 0.149188 | 0.149188 | 0.149188 | 2880.80 | 2880.80 | 2037.22 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.151365 | 0.151365 | 0.151365 | 0.151365 | 2969.37 | 2969.37 | 2021.47 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.151929 | 0.151929 | 0.151929 | 0.151929 | 2977.27 | 2977.27 | 2021.23 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.252315 | 0.252315 | 0.252315 | 0.252315 | 4459.38 | 4459.38 | 3135.18 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.249049 | 0.249049 | 0.249049 | 0.249049 | 4408.23 | 4408.23 | 3152.21 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.214837 | 0.214837 | 0.214837 | 0.214837 | 3932.51 | 3932.51 | 3125.08 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.201757 | 0.201757 | 0.201757 | 0.201757 | 3729.83 | 3729.83 | 3142.13 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.149318 | 0.149318 | 0.149318 | 0.149318 | 2890.19 | 2890.19 | 2087.23 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.148456 | 0.148456 | 0.148456 | 0.148456 | 2877.73 | 2877.73 | 2086.98 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.150691 | 0.150691 | 0.150691 | 0.150691 | 2967.16 | 2967.16 | 2070.23 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.151255 | 0.151255 | 0.151255 | 0.151255 | 2975.05 | 2975.05 | 2069.97 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.252579 | 0.252579 | 0.252579 | 0.252579 | 4475.34 | 4475.34 | 3207.25 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.249254 | 0.249254 | 0.249254 | 0.249254 | 4423.39 | 4423.39 | 3224.86 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.215331 | 0.215331 | 0.215331 | 0.215331 | 3951.15 | 3951.15 | 3196.49 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.202184 | 0.202184 | 0.202184 | 0.202184 | 3747.34 | 3747.34 | 3214.11 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.149926 | 0.149926 | 0.149926 | 0.149926 | 2905.53 | 2905.53 | 2139.72 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.149075 | 0.149075 | 0.149075 | 0.149075 | 2893.21 | 2893.21 | 2139.44 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.151311 | 0.151311 | 0.151311 | 0.151311 | 2982.58 | 2982.58 | 2122.12 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.151875 | 0.151875 | 0.151875 | 0.151875 | 2990.50 | 2990.50 | 2121.85 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.261045 | 0.261045 | 0.261045 | 0.261045 | 4601.73 | 4601.73 | 3387.87 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.257502 | 0.257502 | 0.257502 | 0.257502 | 4550.57 | 4550.57 | 3403.72 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.219993 | 0.219993 | 0.219993 | 0.219993 | 4027.92 | 4027.92 | 3376.43 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.206266 | 0.206266 | 0.206266 | 0.206266 | 3815.87 | 3815.87 | 3392.29 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.157498 | 0.157498 | 0.157498 | 0.157498 | 3020.15 | 3020.15 | 2292.25 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.156647 | 0.156647 | 0.156647 | 0.156647 | 3007.87 | 3007.87 | 2291.96 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.157012 | 0.157012 | 0.157012 | 0.157012 | 3070.24 | 3070.24 | 2275.98 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.157643 | 0.157643 | 0.157643 | 0.157643 | 3079.10 | 3079.10 | 2275.69 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.312952 | 0.312952 | 0.312952 | 0.312952 | 5350.32 | 5350.32 | 3939.41 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.305479 | 0.305479 | 0.305479 | 0.305479 | 5237.34 | 5237.34 | 3960.89 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.272189 | 0.272189 | 0.272189 | 0.272189 | 4809.35 | 4809.35 | 3928.44 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.250279 | 0.250279 | 0.250279 | 0.250279 | 4453.07 | 4453.07 | 3949.93 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.191249 | 0.191249 | 0.191249 | 0.191249 | 3514.42 | 3514.42 | 2888.57 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.189338 | 0.189338 | 0.189338 | 0.189338 | 3487.28 | 3487.28 | 2888.27 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.215507 | 0.215507 | 0.215507 | 0.215507 | 3901.54 | 3901.54 | 2863.82 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.216108 | 0.216108 | 0.216108 | 0.216108 | 3909.80 | 3909.80 | 2863.52 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.201855 |
AIRLOOP G NW SUPPLY FAN | 0.201851 |
AIRLOOP OFFICE SUPPLY FAN | 0.271360 |
AIRLOOP G NE SUPPLY FAN | 0.155908 |
AIRLOOP G N1 SUPPLY FAN | 0.113606 |
AIRLOOP G N2 SUPPLY FAN | 0.112451 |
AIRLOOP G S1 SUPPLY FAN | 0.111740 |
AIRLOOP G S2 SUPPLY FAN | 0.116508 |
AIRLOOP F2 SW SUPPLY FAN | 0.252921 |
AIRLOOP F2 NW SUPPLY FAN | 0.249734 |
AIRLOOP F2 SE SUPPLY FAN | 0.229786 |
AIRLOOP F2 NE SUPPLY FAN | 0.199095 |
AIRLOOP F2 N1 SUPPLY FAN | 0.145992 |
AIRLOOP F2 N2 SUPPLY FAN | 0.145068 |
AIRLOOP F2 S1 SUPPLY FAN | 0.146501 |
AIRLOOP F2 S2 SUPPLY FAN | 0.148168 |
AIRLOOP F3 SW SUPPLY FAN | 0.253459 |
AIRLOOP F3 NW SUPPLY FAN | 0.250577 |
AIRLOOP F3 SE SUPPLY FAN | 0.216121 |
AIRLOOP F3 NE SUPPLY FAN | 0.201657 |
AIRLOOP F3 N1 SUPPLY FAN | 0.148495 |
AIRLOOP F3 N2 SUPPLY FAN | 0.147588 |
AIRLOOP F3 S1 SUPPLY FAN | 0.149406 |
AIRLOOP F3 S2 SUPPLY FAN | 0.150132 |
AIRLOOP F4 SW SUPPLY FAN | 0.254105 |
AIRLOOP F4 NW SUPPLY FAN | 0.251106 |
AIRLOOP F4 SE SUPPLY FAN | 0.215699 |
AIRLOOP F4 NE SUPPLY FAN | 0.202702 |
AIRLOOP F4 N1 SUPPLY FAN | 0.149784 |
AIRLOOP F4 N2 SUPPLY FAN | 0.148889 |
AIRLOOP F4 S1 SUPPLY FAN | 0.150860 |
AIRLOOP F4 S2 SUPPLY FAN | 0.151447 |
AIRLOOP M SW SUPPLY FAN | 0.256974 |
AIRLOOP M NW SUPPLY FAN | 0.253949 |
AIRLOOP M SE SUPPLY FAN | 0.218783 |
AIRLOOP M NE SUPPLY FAN | 0.205916 |
AIRLOOP M N1 SUPPLY FAN | 0.153097 |
AIRLOOP M N2 SUPPLY FAN | 0.152212 |
AIRLOOP M S1 SUPPLY FAN | 0.154239 |
AIRLOOP M S2 SUPPLY FAN | 0.154806 |
AIRLOOP F6 SW SUPPLY FAN | 0.253469 |
AIRLOOP F6 NW SUPPLY FAN | 0.250263 |
AIRLOOP F6 SE SUPPLY FAN | 0.215661 |
AIRLOOP F6 NE SUPPLY FAN | 0.202641 |
AIRLOOP F6 N1 SUPPLY FAN | 0.150060 |
AIRLOOP F6 N2 SUPPLY FAN | 0.149188 |
AIRLOOP F6 S1 SUPPLY FAN | 0.151365 |
AIRLOOP F6 S2 SUPPLY FAN | 0.151929 |
AIRLOOP F7 SW SUPPLY FAN | 0.252315 |
AIRLOOP F7 NW SUPPLY FAN | 0.249049 |
AIRLOOP F7 SE SUPPLY FAN | 0.214837 |
AIRLOOP F7 NE SUPPLY FAN | 0.201757 |
AIRLOOP F7 N1 SUPPLY FAN | 0.149318 |
AIRLOOP F7 N2 SUPPLY FAN | 0.148456 |
AIRLOOP F7 S1 SUPPLY FAN | 0.150691 |
AIRLOOP F7 S2 SUPPLY FAN | 0.151255 |
AIRLOOP F8 SW SUPPLY FAN | 0.252579 |
AIRLOOP F8 NW SUPPLY FAN | 0.249254 |
AIRLOOP F8 SE SUPPLY FAN | 0.215331 |
AIRLOOP F8 NE SUPPLY FAN | 0.202184 |
AIRLOOP F8 N1 SUPPLY FAN | 0.149926 |
AIRLOOP F8 N2 SUPPLY FAN | 0.149075 |
AIRLOOP F8 S1 SUPPLY FAN | 0.151311 |
AIRLOOP F8 S2 SUPPLY FAN | 0.151875 |
AIRLOOP F9 SW SUPPLY FAN | 0.261045 |
AIRLOOP F9 NW SUPPLY FAN | 0.257502 |
AIRLOOP F9 SE SUPPLY FAN | 0.219993 |
AIRLOOP F9 NE SUPPLY FAN | 0.206266 |
AIRLOOP F9 N1 SUPPLY FAN | 0.157498 |
AIRLOOP F9 N2 SUPPLY FAN | 0.156647 |
AIRLOOP F9 S1 SUPPLY FAN | 0.157012 |
AIRLOOP F9 S2 SUPPLY FAN | 0.157643 |
AIRLOOP T SW SUPPLY FAN | 0.312952 |
AIRLOOP T NW SUPPLY FAN | 0.305479 |
AIRLOOP T SE SUPPLY FAN | 0.272189 |
AIRLOOP T NE SUPPLY FAN | 0.250279 |
AIRLOOP T N1 SUPPLY FAN | 0.191249 |
AIRLOOP T N2 SUPPLY FAN | 0.189338 |
AIRLOOP T S1 SUPPLY FAN | 0.215507 |
AIRLOOP T S2 SUPPLY FAN | 0.216108 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.201855 | 3605.76 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.201851 | 3599.80 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.271360 | 4858.16 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.155908 | 2938.60 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.113606 | 2300.56 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.112451 | 2283.83 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.111740 | 2335.15 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.116508 | 2402.88 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.252921 | 4363.58 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.249734 | 4317.02 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.229786 | 4044.69 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.199095 | 3597.96 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.145992 | 2788.52 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.145068 | 2775.30 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.146501 | 2854.02 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.148168 | 2877.47 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.253459 | 4405.16 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.250577 | 4359.11 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.216121 | 3883.26 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.201657 | 3662.34 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.148495 | 2840.40 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.147588 | 2827.41 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.149406 | 2911.20 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.150132 | 2921.35 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.254105 | 4436.76 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.251106 | 4389.17 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.215699 | 3899.03 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.202702 | 3698.32 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.149784 | 2870.99 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.148889 | 2858.14 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.150860 | 2943.91 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.151447 | 2952.11 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.256974 | 4495.24 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.253949 | 4447.34 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.218783 | 3959.95 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.205916 | 3760.89 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.153097 | 2928.16 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.152212 | 2915.44 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.154239 | 3001.73 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.154806 | 3009.66 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.253469 | 4461.87 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.250263 | 4411.51 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.215661 | 3931.03 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.202641 | 3729.47 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.150060 | 2893.37 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.149188 | 2880.80 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.151365 | 2969.37 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.151929 | 2977.27 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.252315 | 4459.38 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.249049 | 4408.23 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.214837 | 3932.51 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.201757 | 3729.83 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.149318 | 2890.19 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.148456 | 2877.73 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.150691 | 2967.16 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.151255 | 2975.05 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.252579 | 4475.34 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.249254 | 4423.39 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.215331 | 3951.15 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.202184 | 3747.34 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.149926 | 2905.53 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.149075 | 2893.21 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.151311 | 2982.58 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.151875 | 2990.50 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.261045 | 4601.73 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.257502 | 4550.57 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.219993 | 4027.92 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.206266 | 3815.87 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.157498 | 3020.15 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.156647 | 3007.87 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.157012 | 3070.24 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.157643 | 3079.10 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.312952 | 5350.32 | 0.000117 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.305479 | 5237.34 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.272189 | 4809.35 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.250279 | 4453.07 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.191249 | 3514.42 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.189338 | 3487.28 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.215507 | 3901.54 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.216108 | 3909.80 | 0.000085 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2787.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2791.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3597.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2791.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2070.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2070.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2063.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2072.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2815.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2820.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2837.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2817.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1920.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1920.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1918.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1919.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2852.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2862.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2849.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2856.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1914.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1914.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1905.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1905.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2921.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2933.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2914.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2926.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1948.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1948.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1935.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1935.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2961.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2974.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2953.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2966.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1961.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1960.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1947.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1947.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 3063.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 3079.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 3054.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 3070.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 2037.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 2037.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 2021.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 2021.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 3135.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 3152.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 3125.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 3142.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 2087.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 2086.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 2070.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 2069.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 3207.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 3224.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 3196.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 3214.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2139.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2139.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2122.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2121.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 3387.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 3403.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 3376.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 3392.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2292.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2291.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2275.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2275.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3939.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3960.89 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3928.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3949.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2888.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2888.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2863.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2863.52 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.006226 | 7.00 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.006226 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.006226 | 3005.64 | 8.20 | 8989.24 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.006226 | 1587.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 3.96 |
February | 22.29 | 7.94 |
March | 22.98 | 13.76 |
April | 23.51 | 17.21 |
May | 23.97 | 20.84 |
June | 24.37 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.27 | 22.53 |
October | 23.47 | 16.03 |
November | 22.88 | 11.94 |
December | 22.30 | 7.70 |
Annual Sum or Average | 23.41 | 16.65 |
Minimum of Months | 22.00 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.96 |
February | 21.97 | 7.94 |
March | 22.55 | 13.76 |
April | 23.39 | 17.21 |
May | 23.98 | 20.84 |
June | 24.37 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.26 | 22.53 |
October | 23.11 | 16.03 |
November | 22.28 | 11.94 |
December | 21.83 | 7.70 |
Annual Sum or Average | 23.19 | 16.65 |
Minimum of Months | 21.73 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 3.96 |
February | 22.47 | 7.94 |
March | 23.28 | 13.76 |
April | 23.74 | 17.21 |
May | 24.18 | 20.84 |
June | 24.39 | 24.80 |
July | 24.40 | 26.06 |
August | 24.40 | 26.55 |
September | 24.37 | 22.53 |
October | 23.60 | 16.03 |
November | 23.05 | 11.94 |
December | 22.43 | 7.70 |
Annual Sum or Average | 23.55 | 16.65 |
Minimum of Months | 22.18 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.96 |
February | 21.95 | 7.94 |
March | 22.46 | 13.76 |
April | 23.34 | 17.21 |
May | 23.96 | 20.84 |
June | 24.38 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.25 | 22.53 |
October | 23.05 | 16.03 |
November | 22.18 | 11.94 |
December | 21.78 | 7.70 |
Annual Sum or Average | 23.16 | 16.65 |
Minimum of Months | 21.72 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.96 |
February | 21.92 | 7.94 |
March | 22.37 | 13.76 |
April | 23.23 | 17.21 |
May | 23.87 | 20.84 |
June | 24.37 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.25 | 22.53 |
October | 23.01 | 16.03 |
November | 22.17 | 11.94 |
December | 21.79 | 7.70 |
Annual Sum or Average | 23.13 | 16.65 |
Minimum of Months | 21.72 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.96 |
February | 21.92 | 7.94 |
March | 22.37 | 13.76 |
April | 23.23 | 17.21 |
May | 23.87 | 20.84 |
June | 24.37 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.24 | 22.53 |
October | 23.00 | 16.03 |
November | 22.17 | 11.94 |
December | 21.79 | 7.70 |
Annual Sum or Average | 23.13 | 16.65 |
Minimum of Months | 21.72 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 3.96 |
February | 22.30 | 7.94 |
March | 22.92 | 13.76 |
April | 23.42 | 17.21 |
May | 23.90 | 20.84 |
June | 24.36 | 24.80 |
July | 24.38 | 26.06 |
August | 24.44 | 26.55 |
September | 24.28 | 22.53 |
October | 23.51 | 16.03 |
November | 22.92 | 11.94 |
December | 22.36 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 22.02 | 3.96 |
Maximum of Months | 24.44 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 3.96 |
February | 22.33 | 7.94 |
March | 22.96 | 13.76 |
April | 23.45 | 17.21 |
May | 23.92 | 20.84 |
June | 24.36 | 24.80 |
July | 24.37 | 26.06 |
August | 24.42 | 26.55 |
September | 24.28 | 22.53 |
October | 23.53 | 16.03 |
November | 22.95 | 11.94 |
December | 22.38 | 7.70 |
Annual Sum or Average | 23.42 | 16.65 |
Minimum of Months | 22.04 | 3.96 |
Maximum of Months | 24.42 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.03 | 3.96 |
February | 19.27 | 7.94 |
March | 21.31 | 13.76 |
April | 22.73 | 17.21 |
May | 23.99 | 20.84 |
June | 25.86 | 24.80 |
July | 26.24 | 26.06 |
August | 26.38 | 26.55 |
September | 25.13 | 22.53 |
October | 22.35 | 16.03 |
November | 20.77 | 11.94 |
December | 19.19 | 7.70 |
Annual Sum or Average | 22.62 | 16.65 |
Minimum of Months | 18.03 | 3.96 |
Maximum of Months | 26.38 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 3.96 |
February | 22.67 | 7.94 |
March | 23.70 | 13.76 |
April | 24.04 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.31 | 22.53 |
October | 23.97 | 16.03 |
November | 23.58 | 11.94 |
December | 22.69 | 7.70 |
Annual Sum or Average | 23.72 | 16.65 |
Minimum of Months | 22.23 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.21 | 7.94 |
March | 23.13 | 13.76 |
April | 23.91 | 17.21 |
May | 24.26 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.62 | 16.03 |
November | 22.72 | 11.94 |
December | 21.98 | 7.70 |
Annual Sum or Average | 23.43 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 3.96 |
February | 22.71 | 7.94 |
March | 23.74 | 13.76 |
April | 24.09 | 17.21 |
May | 24.30 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.32 | 22.53 |
October | 23.99 | 16.03 |
November | 23.62 | 11.94 |
December | 22.74 | 7.70 |
Annual Sum or Average | 23.75 | 16.65 |
Minimum of Months | 22.25 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 3.96 |
February | 22.18 | 7.94 |
March | 23.02 | 13.76 |
April | 23.88 | 17.21 |
May | 24.26 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.54 | 16.03 |
November | 22.59 | 11.94 |
December | 21.90 | 7.70 |
Annual Sum or Average | 23.39 | 16.65 |
Minimum of Months | 21.76 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.21 | 7.94 |
March | 23.01 | 13.76 |
April | 23.84 | 17.21 |
May | 24.23 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.29 | 22.53 |
October | 23.61 | 16.03 |
November | 22.69 | 11.94 |
December | 21.98 | 7.70 |
Annual Sum or Average | 23.41 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.21 | 7.94 |
March | 23.00 | 13.76 |
April | 23.83 | 17.21 |
May | 24.23 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.29 | 22.53 |
October | 23.61 | 16.03 |
November | 22.67 | 11.94 |
December | 21.97 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 3.96 |
February | 22.77 | 7.94 |
March | 23.73 | 13.76 |
April | 24.02 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.43 | 26.55 |
September | 24.32 | 22.53 |
October | 24.05 | 16.03 |
November | 23.74 | 11.94 |
December | 22.92 | 7.70 |
Annual Sum or Average | 23.78 | 16.65 |
Minimum of Months | 22.37 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 3.96 |
February | 22.79 | 7.94 |
March | 23.74 | 13.76 |
April | 24.02 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.42 | 26.55 |
September | 24.32 | 22.53 |
October | 24.05 | 16.03 |
November | 23.75 | 11.94 |
December | 22.93 | 7.70 |
Annual Sum or Average | 23.79 | 16.65 |
Minimum of Months | 22.38 | 3.96 |
Maximum of Months | 24.42 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.24 | 3.96 |
February | 22.93 | 7.94 |
March | 24.41 | 13.76 |
April | 25.25 | 17.21 |
May | 25.87 | 20.84 |
June | 26.47 | 24.80 |
July | 26.59 | 26.06 |
August | 26.65 | 26.55 |
September | 26.18 | 22.53 |
October | 24.99 | 16.03 |
November | 24.02 | 11.94 |
December | 22.89 | 7.70 |
Annual Sum or Average | 24.88 | 16.65 |
Minimum of Months | 22.24 | 3.96 |
Maximum of Months | 26.65 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 3.96 |
February | 22.72 | 7.94 |
March | 23.80 | 13.76 |
April | 24.10 | 17.21 |
May | 24.29 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.31 | 22.53 |
October | 24.02 | 16.03 |
November | 23.69 | 11.94 |
December | 22.76 | 7.70 |
Annual Sum or Average | 23.76 | 16.65 |
Minimum of Months | 22.25 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.96 |
February | 22.27 | 7.94 |
March | 23.26 | 13.76 |
April | 23.98 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.71 | 16.03 |
November | 22.83 | 11.94 |
December | 22.01 | 7.70 |
Annual Sum or Average | 23.47 | 16.65 |
Minimum of Months | 21.79 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 3.96 |
February | 22.69 | 7.94 |
March | 23.77 | 13.76 |
April | 24.11 | 17.21 |
May | 24.30 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.41 | 26.55 |
September | 24.32 | 22.53 |
October | 24.00 | 16.03 |
November | 23.65 | 11.94 |
December | 22.73 | 7.70 |
Annual Sum or Average | 23.75 | 16.65 |
Minimum of Months | 22.22 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.24 | 7.94 |
March | 23.16 | 13.76 |
April | 23.96 | 17.21 |
May | 24.29 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.64 | 16.03 |
November | 22.71 | 11.94 |
December | 21.94 | 7.70 |
Annual Sum or Average | 23.44 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 3.96 |
February | 22.30 | 7.94 |
March | 23.21 | 13.76 |
April | 23.96 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.29 | 22.53 |
October | 23.76 | 16.03 |
November | 22.88 | 11.94 |
December | 22.05 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 21.81 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.96 |
February | 22.30 | 7.94 |
March | 23.20 | 13.76 |
April | 23.95 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.41 | 26.55 |
September | 24.29 | 22.53 |
October | 23.75 | 16.03 |
November | 22.86 | 11.94 |
December | 22.05 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 21.80 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 3.96 |
February | 22.87 | 7.94 |
March | 23.89 | 13.76 |
April | 24.11 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.32 | 22.53 |
October | 24.13 | 16.03 |
November | 23.89 | 11.94 |
December | 23.06 | 7.70 |
Annual Sum or Average | 23.86 | 16.65 |
Minimum of Months | 22.46 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 3.96 |
February | 22.87 | 7.94 |
March | 23.89 | 13.76 |
April | 24.11 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.32 | 22.53 |
October | 24.13 | 16.03 |
November | 23.89 | 11.94 |
December | 23.07 | 7.70 |
Annual Sum or Average | 23.86 | 16.65 |
Minimum of Months | 22.46 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.64 | 3.96 |
February | 23.34 | 7.94 |
March | 24.86 | 13.76 |
April | 25.65 | 17.21 |
May | 26.17 | 20.84 |
June | 26.58 | 24.80 |
July | 26.66 | 26.06 |
August | 26.71 | 26.55 |
September | 26.29 | 22.53 |
October | 25.36 | 16.03 |
November | 24.46 | 11.94 |
December | 23.29 | 7.70 |
Annual Sum or Average | 25.18 | 16.65 |
Minimum of Months | 22.64 | 3.96 |
Maximum of Months | 26.71 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.24 | 3.96 |
February | 22.72 | 7.94 |
March | 23.80 | 13.76 |
April | 24.13 | 17.21 |
May | 24.29 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.32 | 22.53 |
October | 24.02 | 16.03 |
November | 23.69 | 11.94 |
December | 22.74 | 7.70 |
Annual Sum or Average | 23.76 | 16.65 |
Minimum of Months | 22.24 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.96 |
February | 22.29 | 7.94 |
March | 23.28 | 13.76 |
April | 24.02 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.71 | 16.03 |
November | 22.85 | 11.94 |
December | 22.01 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 21.79 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 3.96 |
February | 22.68 | 7.94 |
March | 23.76 | 13.76 |
April | 24.14 | 17.21 |
May | 24.30 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.32 | 22.53 |
October | 23.98 | 16.03 |
November | 23.64 | 11.94 |
December | 22.71 | 7.70 |
Annual Sum or Average | 23.75 | 16.65 |
Minimum of Months | 22.19 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.25 | 7.94 |
March | 23.18 | 13.76 |
April | 24.01 | 17.21 |
May | 24.29 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.64 | 16.03 |
November | 22.72 | 11.94 |
December | 21.94 | 7.70 |
Annual Sum or Average | 23.45 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 3.96 |
February | 22.34 | 7.94 |
March | 23.26 | 13.76 |
April | 24.02 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.78 | 16.03 |
November | 22.93 | 11.94 |
December | 22.07 | 7.70 |
Annual Sum or Average | 23.50 | 16.65 |
Minimum of Months | 21.81 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 3.96 |
February | 22.34 | 7.94 |
March | 23.25 | 13.76 |
April | 24.02 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.78 | 16.03 |
November | 22.92 | 11.94 |
December | 22.06 | 7.70 |
Annual Sum or Average | 23.50 | 16.65 |
Minimum of Months | 21.81 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.47 | 3.96 |
February | 22.89 | 7.94 |
March | 23.92 | 13.76 |
April | 24.16 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.33 | 22.53 |
October | 24.14 | 16.03 |
November | 23.91 | 11.94 |
December | 23.08 | 7.70 |
Annual Sum or Average | 23.87 | 16.65 |
Minimum of Months | 22.47 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 3.96 |
February | 22.89 | 7.94 |
March | 23.92 | 13.76 |
April | 24.16 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.33 | 22.53 |
October | 24.14 | 16.03 |
November | 23.90 | 11.94 |
December | 23.08 | 7.70 |
Annual Sum or Average | 23.87 | 16.65 |
Minimum of Months | 22.46 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 3.96 |
February | 23.48 | 7.94 |
March | 25.02 | 13.76 |
April | 25.82 | 17.21 |
May | 26.30 | 20.84 |
June | 26.67 | 24.80 |
July | 26.74 | 26.06 |
August | 26.80 | 26.55 |
September | 26.39 | 22.53 |
October | 25.50 | 16.03 |
November | 24.62 | 11.94 |
December | 23.44 | 7.70 |
Annual Sum or Average | 25.30 | 16.65 |
Minimum of Months | 22.77 | 3.96 |
Maximum of Months | 26.80 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 3.96 |
February | 22.71 | 7.94 |
March | 23.78 | 13.76 |
April | 24.13 | 17.21 |
May | 24.29 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.31 | 22.53 |
October | 24.01 | 16.03 |
November | 23.68 | 11.94 |
December | 22.73 | 7.70 |
Annual Sum or Average | 23.76 | 16.65 |
Minimum of Months | 22.22 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.96 |
February | 22.28 | 7.94 |
March | 23.27 | 13.76 |
April | 24.02 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.71 | 16.03 |
November | 22.85 | 11.94 |
December | 22.02 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 21.80 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 3.96 |
February | 22.67 | 7.94 |
March | 23.73 | 13.76 |
April | 24.13 | 17.21 |
May | 24.30 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.32 | 22.53 |
October | 23.97 | 16.03 |
November | 23.63 | 11.94 |
December | 22.69 | 7.70 |
Annual Sum or Average | 23.74 | 16.65 |
Minimum of Months | 22.18 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.25 | 7.94 |
March | 23.17 | 13.76 |
April | 24.00 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.39 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.64 | 16.03 |
November | 22.73 | 11.94 |
December | 21.94 | 7.70 |
Annual Sum or Average | 23.45 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 3.96 |
February | 22.36 | 7.94 |
March | 23.28 | 13.76 |
April | 24.03 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.79 | 16.03 |
November | 22.95 | 11.94 |
December | 22.09 | 7.70 |
Annual Sum or Average | 23.51 | 16.65 |
Minimum of Months | 21.82 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 3.96 |
February | 22.36 | 7.94 |
March | 23.27 | 13.76 |
April | 24.03 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.79 | 16.03 |
November | 22.94 | 11.94 |
December | 22.08 | 7.70 |
Annual Sum or Average | 23.51 | 16.65 |
Minimum of Months | 21.82 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 3.96 |
February | 22.89 | 7.94 |
March | 23.91 | 13.76 |
April | 24.16 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.33 | 22.53 |
October | 24.14 | 16.03 |
November | 23.91 | 11.94 |
December | 23.08 | 7.70 |
Annual Sum or Average | 23.87 | 16.65 |
Minimum of Months | 22.46 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 3.96 |
February | 22.89 | 7.94 |
March | 23.91 | 13.76 |
April | 24.16 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.33 | 22.53 |
October | 24.14 | 16.03 |
November | 23.91 | 11.94 |
December | 23.08 | 7.70 |
Annual Sum or Average | 23.87 | 16.65 |
Minimum of Months | 22.46 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 3.96 |
February | 24.11 | 7.94 |
March | 25.63 | 13.76 |
April | 26.43 | 17.21 |
May | 26.90 | 20.84 |
June | 27.26 | 24.80 |
July | 27.33 | 26.06 |
August | 27.39 | 26.55 |
September | 26.99 | 22.53 |
October | 26.10 | 16.03 |
November | 25.24 | 11.94 |
December | 24.06 | 7.70 |
Annual Sum or Average | 25.91 | 16.65 |
Minimum of Months | 23.41 | 3.96 |
Maximum of Months | 27.39 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 3.96 |
February | 22.63 | 7.94 |
March | 23.69 | 13.76 |
April | 24.08 | 17.21 |
May | 24.27 | 20.84 |
June | 24.38 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.94 | 16.03 |
November | 23.59 | 11.94 |
December | 22.65 | 7.70 |
Annual Sum or Average | 23.71 | 16.65 |
Minimum of Months | 22.16 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.22 | 7.94 |
March | 23.15 | 13.76 |
April | 23.96 | 17.21 |
May | 24.26 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.29 | 22.53 |
October | 23.62 | 16.03 |
November | 22.74 | 11.94 |
December | 21.97 | 7.70 |
Annual Sum or Average | 23.43 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.12 | 3.96 |
February | 22.60 | 7.94 |
March | 23.63 | 13.76 |
April | 24.08 | 17.21 |
May | 24.28 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.31 | 22.53 |
October | 23.89 | 16.03 |
November | 23.53 | 11.94 |
December | 22.60 | 7.70 |
Annual Sum or Average | 23.69 | 16.65 |
Minimum of Months | 22.12 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 3.96 |
February | 22.19 | 7.94 |
March | 23.05 | 13.76 |
April | 23.94 | 17.21 |
May | 24.26 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.29 | 22.53 |
October | 23.55 | 16.03 |
November | 22.62 | 11.94 |
December | 21.90 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 21.76 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.96 |
February | 22.29 | 7.94 |
March | 23.15 | 13.76 |
April | 23.97 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.29 | 22.53 |
October | 23.70 | 16.03 |
November | 22.83 | 11.94 |
December | 22.02 | 7.70 |
Annual Sum or Average | 23.46 | 16.65 |
Minimum of Months | 21.80 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.96 |
February | 22.29 | 7.94 |
March | 23.14 | 13.76 |
April | 23.97 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.29 | 22.53 |
October | 23.70 | 16.03 |
November | 22.81 | 11.94 |
December | 22.02 | 7.70 |
Annual Sum or Average | 23.46 | 16.65 |
Minimum of Months | 21.80 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 3.96 |
February | 22.81 | 7.94 |
March | 23.82 | 13.76 |
April | 24.12 | 17.21 |
May | 24.26 | 20.84 |
June | 24.38 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.32 | 22.53 |
October | 24.08 | 16.03 |
November | 23.83 | 11.94 |
December | 22.98 | 7.70 |
Annual Sum or Average | 23.82 | 16.65 |
Minimum of Months | 22.38 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 3.96 |
February | 22.81 | 7.94 |
March | 23.82 | 13.76 |
April | 24.12 | 17.21 |
May | 24.26 | 20.84 |
June | 24.38 | 24.80 |
July | 24.38 | 26.06 |
August | 24.43 | 26.55 |
September | 24.32 | 22.53 |
October | 24.07 | 16.03 |
November | 23.83 | 11.94 |
December | 22.98 | 7.70 |
Annual Sum or Average | 23.82 | 16.65 |
Minimum of Months | 22.38 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 3.96 |
February | 23.39 | 7.94 |
March | 24.91 | 13.76 |
April | 25.76 | 17.21 |
May | 26.27 | 20.84 |
June | 26.65 | 24.80 |
July | 26.72 | 26.06 |
August | 26.79 | 26.55 |
September | 26.37 | 22.53 |
October | 25.41 | 16.03 |
November | 24.53 | 11.94 |
December | 23.35 | 7.70 |
Annual Sum or Average | 25.25 | 16.65 |
Minimum of Months | 22.70 | 3.96 |
Maximum of Months | 26.79 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.12 | 3.96 |
February | 22.58 | 7.94 |
March | 23.61 | 13.76 |
April | 24.04 | 17.21 |
May | 24.26 | 20.84 |
June | 24.38 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.30 | 22.53 |
October | 23.88 | 16.03 |
November | 23.51 | 11.94 |
December | 22.58 | 7.70 |
Annual Sum or Average | 23.67 | 16.65 |
Minimum of Months | 22.12 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.18 | 7.94 |
March | 23.05 | 13.76 |
April | 23.92 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.28 | 22.53 |
October | 23.55 | 16.03 |
November | 22.66 | 11.94 |
December | 21.94 | 7.70 |
Annual Sum or Average | 23.40 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 3.96 |
February | 22.54 | 7.94 |
March | 23.55 | 13.76 |
April | 24.04 | 17.21 |
May | 24.27 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.84 | 16.03 |
November | 23.45 | 11.94 |
December | 22.54 | 7.70 |
Annual Sum or Average | 23.65 | 16.65 |
Minimum of Months | 22.08 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 22.15 | 7.94 |
March | 22.96 | 13.76 |
April | 23.89 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.28 | 22.53 |
October | 23.49 | 16.03 |
November | 22.55 | 11.94 |
December | 21.88 | 7.70 |
Annual Sum or Average | 23.37 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.96 |
February | 22.24 | 7.94 |
March | 23.06 | 13.76 |
April | 23.92 | 17.21 |
May | 24.23 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.28 | 22.53 |
October | 23.63 | 16.03 |
November | 22.73 | 11.94 |
December | 21.98 | 7.70 |
Annual Sum or Average | 23.42 | 16.65 |
Minimum of Months | 21.79 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.24 | 7.94 |
March | 23.06 | 13.76 |
April | 23.92 | 17.21 |
May | 24.23 | 20.84 |
June | 24.39 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.28 | 22.53 |
October | 23.63 | 16.03 |
November | 22.71 | 11.94 |
December | 21.98 | 7.70 |
Annual Sum or Average | 23.42 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.32 | 3.96 |
February | 22.75 | 7.94 |
March | 23.74 | 13.76 |
April | 24.08 | 17.21 |
May | 24.25 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.43 | 26.55 |
September | 24.31 | 22.53 |
October | 24.03 | 16.03 |
November | 23.77 | 11.94 |
December | 22.90 | 7.70 |
Annual Sum or Average | 23.78 | 16.65 |
Minimum of Months | 22.32 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.32 | 3.96 |
February | 22.75 | 7.94 |
March | 23.74 | 13.76 |
April | 24.08 | 17.21 |
May | 24.25 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.43 | 26.55 |
September | 24.31 | 22.53 |
October | 24.02 | 16.03 |
November | 23.77 | 11.94 |
December | 22.90 | 7.70 |
Annual Sum or Average | 23.78 | 16.65 |
Minimum of Months | 22.32 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.53 | 3.96 |
February | 23.22 | 7.94 |
March | 24.72 | 13.76 |
April | 25.62 | 17.21 |
May | 26.17 | 20.84 |
June | 26.57 | 24.80 |
July | 26.64 | 26.06 |
August | 26.71 | 26.55 |
September | 26.28 | 22.53 |
October | 25.26 | 16.03 |
November | 24.34 | 11.94 |
December | 23.17 | 7.70 |
Annual Sum or Average | 25.11 | 16.65 |
Minimum of Months | 22.53 | 3.96 |
Maximum of Months | 26.71 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 3.96 |
February | 22.53 | 7.94 |
March | 23.53 | 13.76 |
April | 24.00 | 17.21 |
May | 24.25 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.29 | 22.53 |
October | 23.83 | 16.03 |
November | 23.44 | 11.94 |
December | 22.53 | 7.70 |
Annual Sum or Average | 23.64 | 16.65 |
Minimum of Months | 22.08 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 3.96 |
February | 22.14 | 7.94 |
March | 22.97 | 13.76 |
April | 23.88 | 17.21 |
May | 24.24 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.27 | 22.53 |
October | 23.49 | 16.03 |
November | 22.59 | 11.94 |
December | 21.91 | 7.70 |
Annual Sum or Average | 23.37 | 16.65 |
Minimum of Months | 21.76 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 3.96 |
February | 22.50 | 7.94 |
March | 23.47 | 13.76 |
April | 24.00 | 17.21 |
May | 24.26 | 20.84 |
June | 24.39 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.30 | 22.53 |
October | 23.79 | 16.03 |
November | 23.37 | 11.94 |
December | 22.49 | 7.70 |
Annual Sum or Average | 23.62 | 16.65 |
Minimum of Months | 22.04 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 22.11 | 7.94 |
March | 22.88 | 13.76 |
April | 23.85 | 17.21 |
May | 24.24 | 20.84 |
June | 24.39 | 24.80 |
July | 24.38 | 26.06 |
August | 24.40 | 26.55 |
September | 24.27 | 22.53 |
October | 23.44 | 16.03 |
November | 22.48 | 11.94 |
December | 21.86 | 7.70 |
Annual Sum or Average | 23.34 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.20 | 7.94 |
March | 22.99 | 13.76 |
April | 23.88 | 17.21 |
May | 24.22 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.27 | 22.53 |
October | 23.57 | 16.03 |
November | 22.64 | 11.94 |
December | 21.95 | 7.70 |
Annual Sum or Average | 23.39 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.20 | 7.94 |
March | 22.98 | 13.76 |
April | 23.87 | 17.21 |
May | 24.22 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.27 | 22.53 |
October | 23.56 | 16.03 |
November | 22.63 | 11.94 |
December | 21.95 | 7.70 |
Annual Sum or Average | 23.39 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 3.96 |
February | 22.70 | 7.94 |
March | 23.67 | 13.76 |
April | 24.04 | 17.21 |
May | 24.24 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.43 | 26.55 |
September | 24.30 | 22.53 |
October | 23.97 | 16.03 |
November | 23.70 | 11.94 |
December | 22.83 | 7.70 |
Annual Sum or Average | 23.75 | 16.65 |
Minimum of Months | 22.27 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 3.96 |
February | 22.70 | 7.94 |
March | 23.66 | 13.76 |
April | 24.04 | 17.21 |
May | 24.24 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.43 | 26.55 |
September | 24.30 | 22.53 |
October | 23.97 | 16.03 |
November | 23.70 | 11.94 |
December | 22.83 | 7.70 |
Annual Sum or Average | 23.75 | 16.65 |
Minimum of Months | 22.27 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.44 | 3.96 |
February | 23.12 | 7.94 |
March | 24.61 | 13.76 |
April | 25.55 | 17.21 |
May | 26.14 | 20.84 |
June | 26.57 | 24.80 |
July | 26.64 | 26.06 |
August | 26.71 | 26.55 |
September | 26.26 | 22.53 |
October | 25.17 | 16.03 |
November | 24.22 | 11.94 |
December | 23.07 | 7.70 |
Annual Sum or Average | 25.05 | 16.65 |
Minimum of Months | 22.44 | 3.96 |
Maximum of Months | 26.71 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 3.96 |
February | 22.47 | 7.94 |
March | 23.43 | 13.76 |
April | 23.95 | 17.21 |
May | 24.24 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.28 | 22.53 |
October | 23.76 | 16.03 |
November | 23.33 | 11.94 |
December | 22.46 | 7.70 |
Annual Sum or Average | 23.60 | 16.65 |
Minimum of Months | 22.04 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 22.12 | 7.94 |
March | 22.89 | 13.76 |
April | 23.83 | 17.21 |
May | 24.22 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.26 | 22.53 |
October | 23.41 | 16.03 |
November | 22.54 | 11.94 |
December | 21.89 | 7.70 |
Annual Sum or Average | 23.34 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 3.96 |
February | 22.44 | 7.94 |
March | 23.37 | 13.76 |
April | 23.95 | 17.21 |
May | 24.25 | 20.84 |
June | 24.39 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.29 | 22.53 |
October | 23.72 | 16.03 |
November | 23.26 | 11.94 |
December | 22.41 | 7.70 |
Annual Sum or Average | 23.58 | 16.65 |
Minimum of Months | 22.00 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.96 |
February | 22.08 | 7.94 |
March | 22.79 | 13.76 |
April | 23.80 | 17.21 |
May | 24.22 | 20.84 |
June | 24.39 | 24.80 |
July | 24.37 | 26.06 |
August | 24.40 | 26.55 |
September | 24.26 | 22.53 |
October | 23.36 | 16.03 |
November | 22.42 | 11.94 |
December | 21.84 | 7.70 |
Annual Sum or Average | 23.31 | 16.65 |
Minimum of Months | 21.74 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.17 | 7.94 |
March | 22.90 | 13.76 |
April | 23.82 | 17.21 |
May | 24.21 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.26 | 22.53 |
October | 23.48 | 16.03 |
November | 22.56 | 11.94 |
December | 21.92 | 7.70 |
Annual Sum or Average | 23.36 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.16 | 7.94 |
March | 22.89 | 13.76 |
April | 23.82 | 17.21 |
May | 24.21 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.41 | 26.55 |
September | 24.26 | 22.53 |
October | 23.47 | 16.03 |
November | 22.55 | 11.94 |
December | 21.91 | 7.70 |
Annual Sum or Average | 23.36 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.41 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.20 | 3.96 |
February | 22.63 | 7.94 |
March | 23.56 | 13.76 |
April | 23.99 | 17.21 |
May | 24.23 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.43 | 26.55 |
September | 24.29 | 22.53 |
October | 23.89 | 16.03 |
November | 23.58 | 11.94 |
December | 22.72 | 7.70 |
Annual Sum or Average | 23.69 | 16.65 |
Minimum of Months | 22.20 | 3.96 |
Maximum of Months | 24.43 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.20 | 3.96 |
February | 22.63 | 7.94 |
March | 23.56 | 13.76 |
April | 23.99 | 17.21 |
May | 24.23 | 20.84 |
June | 24.38 | 24.80 |
July | 24.37 | 26.06 |
August | 24.42 | 26.55 |
September | 24.29 | 22.53 |
October | 23.89 | 16.03 |
November | 23.58 | 11.94 |
December | 22.72 | 7.70 |
Annual Sum or Average | 23.69 | 16.65 |
Minimum of Months | 22.20 | 3.96 |
Maximum of Months | 24.42 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.29 | 3.96 |
February | 22.98 | 7.94 |
March | 24.48 | 13.76 |
April | 25.50 | 17.21 |
May | 26.16 | 20.84 |
June | 26.64 | 24.80 |
July | 26.72 | 26.06 |
August | 26.80 | 26.55 |
September | 26.29 | 22.53 |
October | 25.06 | 16.03 |
November | 24.06 | 11.94 |
December | 22.90 | 7.70 |
Annual Sum or Average | 25.00 | 16.65 |
Minimum of Months | 22.29 | 3.96 |
Maximum of Months | 26.80 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 3.96 |
February | 22.41 | 7.94 |
March | 23.14 | 13.76 |
April | 23.76 | 17.21 |
May | 24.12 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.23 | 22.53 |
October | 23.50 | 16.03 |
November | 23.06 | 11.94 |
December | 22.38 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 22.04 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.96 |
February | 22.10 | 7.94 |
March | 22.76 | 13.76 |
April | 23.65 | 17.21 |
May | 24.11 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.21 | 22.53 |
October | 23.17 | 16.03 |
November | 22.49 | 11.94 |
December | 21.93 | 7.70 |
Annual Sum or Average | 23.28 | 16.65 |
Minimum of Months | 21.78 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 3.96 |
February | 22.37 | 7.94 |
March | 23.10 | 13.76 |
April | 23.76 | 17.21 |
May | 24.14 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.23 | 22.53 |
October | 23.47 | 16.03 |
November | 23.01 | 11.94 |
December | 22.35 | 7.70 |
Annual Sum or Average | 23.47 | 16.65 |
Minimum of Months | 22.01 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.96 |
February | 22.06 | 7.94 |
March | 22.68 | 13.76 |
April | 23.62 | 17.21 |
May | 24.11 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.21 | 22.53 |
October | 23.15 | 16.03 |
November | 22.38 | 11.94 |
December | 21.86 | 7.70 |
Annual Sum or Average | 23.25 | 16.65 |
Minimum of Months | 21.75 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.12 | 7.94 |
March | 22.71 | 13.76 |
April | 23.65 | 17.21 |
May | 24.10 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.21 | 22.53 |
October | 23.20 | 16.03 |
November | 22.45 | 11.94 |
December | 21.91 | 7.70 |
Annual Sum or Average | 23.27 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.96 |
February | 22.11 | 7.94 |
March | 22.70 | 13.76 |
April | 23.64 | 17.21 |
May | 24.10 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.21 | 22.53 |
October | 23.19 | 16.03 |
November | 22.44 | 11.94 |
December | 21.90 | 7.70 |
Annual Sum or Average | 23.27 | 16.65 |
Minimum of Months | 21.77 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 3.96 |
February | 22.53 | 7.94 |
March | 23.25 | 13.76 |
April | 23.81 | 17.21 |
May | 24.13 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.24 | 22.53 |
October | 23.64 | 16.03 |
November | 23.22 | 11.94 |
December | 22.54 | 7.70 |
Annual Sum or Average | 23.56 | 16.65 |
Minimum of Months | 22.15 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 3.96 |
February | 22.53 | 7.94 |
March | 23.25 | 13.76 |
April | 23.81 | 17.21 |
May | 24.13 | 20.84 |
June | 24.36 | 24.80 |
July | 24.36 | 26.06 |
August | 24.40 | 26.55 |
September | 24.24 | 22.53 |
October | 23.64 | 16.03 |
November | 23.21 | 11.94 |
December | 22.54 | 7.70 |
Annual Sum or Average | 23.56 | 16.65 |
Minimum of Months | 22.15 | 3.96 |
Maximum of Months | 24.40 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 3.96 |
February | 23.08 | 7.94 |
March | 24.70 | 13.76 |
April | 25.89 | 17.21 |
May | 26.77 | 20.84 |
June | 27.41 | 24.80 |
July | 27.56 | 26.06 |
August | 27.63 | 26.55 |
September | 26.86 | 22.53 |
October | 25.30 | 16.03 |
November | 24.17 | 11.94 |
December | 22.92 | 7.70 |
Annual Sum or Average | 25.39 | 16.65 |
Minimum of Months | 22.26 | 3.96 |
Maximum of Months | 27.63 | 26.55 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:09
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.232535E+12 | 145568.029 | 07-JAN-18:15 | 22204.399 | 56867.515 | 17344.921 | 35660.540 | 0.000 | 10720.100 | 1624.917 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.202735E+12 | 144064.273 | 11-FEB-18:00 | 22204.399 | 56867.515 | 17344.921 | 34156.532 | 0.000 | 10720.100 | 1624.917 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.211697E+12 | 164280.104 | 30-MAR-17:15 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 62877.193 | 0.000 | 1624.917 | 2215.522 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.224515E+12 | 154586.846 | 11-APR-17:15 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 53517.416 | 0.000 | 1624.917 | 1882.042 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.263014E+12 | 170257.627 | 21-MAY-17:15 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 68562.778 | 0.000 | 1624.917 | 2507.461 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.302410E+12 | 172968.367 | 06-JUN-17:15 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 71145.064 | 0.000 | 1624.917 | 2635.914 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.327158E+12 | 178332.056 | 26-JUL-19:00 | 25049.151 | 49704.829 | 17344.921 | 0.000 | 70064.654 | 10720.100 | 1624.917 | 2877.912 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.342228E+12 | 177527.002 | 19-AUG-19:00 | 25049.151 | 49704.829 | 17344.921 | 0.000 | 69321.677 | 10720.100 | 1624.917 | 2815.835 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.281198E+12 | 171360.493 | 07-SEP-17:15 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 69400.207 | 0.000 | 1624.917 | 2772.897 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.230012E+12 | 169562.852 | 18-OCT-17:00 | 22204.399 | 56867.515 | 17344.921 | 0.000 | 57013.727 | 10720.100 | 1624.917 | 2641.384 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.204000E+12 | 137757.478 | 05-NOV-16:15 | 18221.747 | 56867.515 | 17344.921 | 0.000 | 40790.728 | 0.000 | 1624.917 | 1762.230 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.218947E+12 | 121949.691 | 25-DEC-18:00 | 22204.399 | 56867.515 | 17344.921 | 12041.950 | 0.000 | 10720.100 | 1624.917 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.304045E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.202735E+12 | 121949.691 | 18221.747 | 49704.829 | 17344.921 | 0.000 | 0.000 | 0.000 | 1624.917 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.342228E+12 | 178332.056 | 25049.151 | 56867.515 | 17344.921 | 35660.540 | 71145.064 | 10720.100 | 1624.917 | 2877.912 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:09
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.207105E+12 | 225999.328 | 07-JAN-10:15 | 0.000 | 0.000 | 0.000 | 225999.328 | 78369.977 | 78369.977 | 147629.351 |
February | 0.156365E+12 | 276556.671 | 12-FEB-06:45 | 0.000 | 0.000 | 0.000 | 276556.671 | 79629.855 | 79629.855 | 196926.815 |
March | 0.101091E+12 | 114531.939 | 18-MAR-06:00 | 0.000 | 0.000 | 0.000 | 114531.939 | 83624.369 | 83624.369 | 30907.570 |
April | 0.889063E+11 | 84025.182 | 06-APR-07:45 | 0.000 | 0.000 | 0.000 | 84025.182 | 75240.114 | 75240.114 | 8785.068 |
May | 0.844359E+11 | 80472.022 | 02-MAY-06:00 | 0.000 | 0.000 | 0.000 | 80472.022 | 80472.022 | 80472.022 | 0.000 |
June | 0.754149E+11 | 78198.235 | 03-JUN-06:45 | 0.000 | 0.000 | 0.000 | 78198.235 | 78198.235 | 78198.235 | 0.000 |
July | 0.739818E+11 | 76791.383 | 02-JUL-06:45 | 0.000 | 0.000 | 0.000 | 76791.383 | 76791.383 | 76791.383 | 0.000 |
August | 0.736849E+11 | 76649.320 | 30-AUG-06:45 | 0.000 | 0.000 | 0.000 | 76649.320 | 76649.320 | 76649.320 | 0.000 |
September | 0.746917E+11 | 77980.008 | 28-SEP-06:00 | 0.000 | 0.000 | 0.000 | 77980.008 | 77980.008 | 77980.008 | 0.000 |
October | 0.837388E+11 | 104173.618 | 26-OCT-06:30 | 0.000 | 0.000 | 0.000 | 104173.618 | 79670.598 | 79670.598 | 24503.021 |
November | 0.963587E+11 | 160794.046 | 22-NOV-07:15 | 0.000 | 0.000 | 0.000 | 160794.046 | 80895.622 | 80895.622 | 79898.424 |
December | 0.144425E+12 | 180125.845 | 02-DEC-07:45 | 0.000 | 0.000 | 0.000 | 180125.845 | 82567.237 | 82567.237 | 97558.608 |
Annual Sum or Average | 0.126020E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.736849E+11 | 76649.320 | 0.000 | 0.000 | 0.000 | 76649.320 | 75240.114 | 75240.114 | 0.000 | |
Maximum of Months | 0.207105E+12 | 276556.671 | 0.000 | 0.000 | 0.000 | 276556.671 | 83624.369 | 83624.369 | 196926.815 |