Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2018-10-19 09:40:17


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4136.08 527.80 585.86
Net Site Energy 4136.08 527.80 585.86
Total Source Energy 10984.20 1401.68 1555.86
Net Source Energy 10984.20 1401.68 1555.86


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 14.85 19.80 0.00 0.00 0.00 0.00
Cooling 659.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.57 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 640.88 0.00 0.00 0.00 0.00 0.00
Pumps 44.21 0.00 0.00 0.00 0.00 0.00
Heat Rejection 24.64 0.00 0.00 0.00 0.00 2235.35
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 995.45 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3120.83 1015.24 0.00 0.00 0.00 7013.87
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 19.80 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 14.85 0.00 0.00 0.00 0.00 0.00
Cooling General 659.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.57 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 640.88 0.00 0.00 0.00 0.00 0.00
Pumps General 44.21 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 24.64 0.00 0.00 0.00 0.00 2235.35
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 995.45 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.86 0.00 0.00 0.00 0.00 0.00
HVAC 196.03 143.80 0.00 0.00 0.00 0.99
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 442.05 143.80 0.00 0.00 0.00 0.99


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.65 0.00 0.00 0.00 0.00 0.00
HVAC 176.60 129.55 0.00 0.00 0.00 0.90
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 398.24 129.55 0.00 0.00 0.00 0.90


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3120.83 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3120.83 100.00
     
Total On-Site and Utility Electric Sources 3120.83 100.00
Total Electricity End Uses 3120.83 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 7013.87 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 7013.87 100.00
Total Water End Uses 7013.87 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 40.50
Time Setpoint Not Met During Occupied Cooling 294.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 1081.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod El Paso International Ap Ut TX USA TMY3 WMO#=722700
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 17-JUL-19:00 27-DEC-07:30 - - - 14-JUN-17:15
Heating 0.00 59159.29 0.00 0.00 0.00 0.00
Cooling 61623.93 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 20322.08 0.00 0.00 0.00 0.00 0.00
Pumps 1422.06 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2273.08 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 82933.34 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 172060.80 142092.63 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 59159.29 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 61623.93 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 20322.08 0.00 0.00 0.00 0.00 0.00
Pumps General 1422.06 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 2273.08 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 82933.34 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 47.03 21.46 0.00 0.00 0.00
Cooling 2088.19 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.87 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2029.66 0.00 0.00 0.00 0.00
Pumps 140.00 0.00 0.00 0.00 0.00
Heat Rejection 78.02 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1079.07 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9883.68 1100.52 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 6.66 3.04 0.00 0.00 0.00
Cooling 295.78 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.62 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 287.49 0.00 0.00 0.00 0.00
Pumps 19.83 0.00 0.00 0.00 0.00
Heat Rejection 11.05 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 152.84 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1399.97 155.88 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 6.66 3.04 0.00 0.00 0.00
Cooling 295.78 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.62 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 287.49 0.00 0.00 0.00 0.00
Pumps 19.83 0.00 0.00 0.00 0.00
Heat Rejection 11.05 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 152.84 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1399.97 155.88 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.65_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 2.848 0.287 0.200     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.848 0.287 0.200              
North Total or Average           423.59 2.848 0.287 0.200              
Non-North Total or Average           726.80 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.77 83.77 168.57
Exterior Lighting Total 10720.10           168.57



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 249683.30 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 199746.64      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3249.68 2140.77 1108.91 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3218.01 2121.90 1096.12 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4223.95 2796.49 1427.45 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2488.28 1645.63 842.65 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1921.73 1251.37 670.37 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1906.25 1240.97 665.28 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1970.73 1265.14 705.59 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2036.19 1309.46 726.72 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3965.11 2626.31 1338.79 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3915.59 2595.20 1320.39 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3612.81 2380.92 1231.89 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3107.16 2063.61 1043.55 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2392.07 1567.90 824.16 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2379.58 1559.52 820.06 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2454.33 1593.36 860.97 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2471.69 1606.29 865.40 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3967.89 2630.85 1337.04 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3924.39 2603.80 1320.58 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3412.66 2248.73 1163.92 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3135.87 2085.55 1050.32 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2423.14 1590.36 832.79 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2410.87 1582.11 828.76 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2485.63 1616.00 869.63 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2490.29 1620.36 869.93 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3978.02 2639.66 1338.35 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3934.90 2612.89 1322.01 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3410.37 2249.12 1161.25 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3149.32 2096.56 1052.77 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2442.83 1604.77 838.07 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2430.72 1596.62 834.10 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2503.58 1629.25 874.33 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2506.01 1632.11 873.90 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4020.32 2669.74 1350.57 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3978.56 2643.88 1334.68 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3457.37 2282.36 1175.00 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3194.58 2128.63 1065.96 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2492.03 1638.79 853.25 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2480.05 1630.73 849.31 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2550.25 1661.69 888.56 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2552.12 1664.17 887.95 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3972.31 2638.86 1333.46 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3929.39 2612.23 1317.15 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3416.79 2256.37 1160.43 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3148.43 2098.90 1049.53 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2450.64 1611.80 838.85 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2438.82 1603.85 834.97 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2508.70 1634.42 874.28 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2514.76 1638.51 876.25 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3957.58 2630.17 1327.41 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3914.99 2603.79 1311.21 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3408.31 2251.83 1156.48 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3136.20 2091.86 1044.34 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2441.88 1606.63 835.25 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2430.19 1598.77 831.42 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2498.64 1628.32 870.32 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2504.70 1632.41 872.29 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3963.16 2635.03 1328.14 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3920.80 2608.80 1312.00 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3418.62 2259.84 1158.78 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3142.91 2097.45 1045.46 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2452.52 1614.43 838.09 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2440.97 1606.66 834.31 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2507.45 1634.89 872.56 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2513.52 1638.99 874.53 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4089.45 2720.99 1368.45 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4047.73 2695.17 1352.56 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3526.19 2332.14 1194.05 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3278.03 2178.02 1100.01 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2569.27 1693.50 875.77 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2557.77 1685.77 872.00 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2596.17 1695.38 900.79 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2601.78 1699.16 902.62 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4985.04 3319.03 1666.01 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4878.09 3251.28 1626.81 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4361.67 2896.86 1464.81 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4055.89 2689.85 1366.04 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3200.15 2104.73 1095.41 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3196.55 2100.93 1095.62 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3492.06 2300.04 1192.02 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3496.99 2303.35 1193.64 0.66 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3249.68 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   3218.01 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4223.95 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2488.28 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1921.73 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1906.25 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   1970.73 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2036.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3965.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3915.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3612.81 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3107.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2392.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2379.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2454.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2471.69 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3967.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3924.39 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3412.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3135.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2423.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2410.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2485.63 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2490.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3978.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3934.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3410.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3149.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2442.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2430.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2503.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2506.01 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4020.32 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   3978.56 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   3457.37 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   3194.58 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2492.03 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2480.05 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2550.25 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2552.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3972.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3929.39 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3416.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3148.43 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2450.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2438.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2508.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2514.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3957.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3914.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3408.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3136.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2441.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2430.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2498.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2504.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   3963.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3920.80 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3418.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3142.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2452.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2440.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2507.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2513.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4089.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4047.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3526.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3278.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2569.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2557.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2596.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2601.78 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   4985.04 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   4878.09 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4361.67 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   4055.89 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3200.15 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3196.55 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3492.06 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3496.99 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   2219.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   2216.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   2965.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   2213.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   1639.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   1639.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   1638.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   1646.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   2173.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   2168.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   2195.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   2165.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1466.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1466.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1474.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1475.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   2144.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   2140.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   2144.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   2137.76 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1422.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1421.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1426.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1426.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   2156.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   2154.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   2154.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   2151.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1421.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1421.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1423.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1423.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   2148.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   2146.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   2146.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   2144.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1404.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1404.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1407.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1407.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   2210.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   2209.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   2208.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   2208.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1455.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1455.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1456.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1456.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   2246.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   2246.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   2245.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   2245.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1483.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1483.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1483.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1483.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   2286.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   2286.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   2286.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   2286.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   1516.55 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   1516.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   1516.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   1516.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   2439.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   2437.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   2439.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   2437.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   1652.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   1652.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   1654.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   1654.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   2990.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   2995.76 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   2991.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   2995.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   2256.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   2256.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   2248.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   2248.82 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 265.53 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 263.80 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 347.26 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 204.05 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 151.43 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 150.08 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 149.12 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 154.87 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 329.48 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 326.15 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 295.33 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.45 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 192.32 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 191.22 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 191.75 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 193.66 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 330.22 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 327.43 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.14 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.46 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 195.34 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.26 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.79 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 195.57 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.48 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.73 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.29 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 263.01 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.28 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.22 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.58 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.17 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 335.52 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 332.88 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.74 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 267.31 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 201.79 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 200.73 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 200.86 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 201.40 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.54 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.80 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.40 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 263.48 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.30 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.26 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.34 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.88 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 330.46 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 327.76 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.87 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 262.61 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.66 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.63 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.58 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.12 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.16 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.47 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.97 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 263.40 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.72 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.70 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.47 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.01 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 342.50 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 339.87 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 289.28 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 272.70 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 209.10 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.08 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 205.40 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 205.90 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 419.77 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 411.89 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 363.69 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 336.26 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.26 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.49 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.58 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 285.02 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0054 1385.13 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2187.91 2625.49 0.198 0.237 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
G NW APARTMENT 2173.65 2608.39 0.196 0.236 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
OFFICE 2861.36 3433.63 0.258 0.310 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 35.44 0.00682
G NE APARTMENT 1681.28 2017.54 0.152 0.182 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 34.14 0.00682
G N1 APARTMENT 1247.73 1497.27 0.113 0.135 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 34.49 0.00682
G N2 APARTMENT 1236.57 1483.88 0.112 0.134 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 34.49 0.00682
G S1 APARTMENT 1228.67 1474.41 0.111 0.133 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
G S2 APARTMENT 1276.09 1531.31 0.115 0.138 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F2 SW APARTMENT 2714.82 3257.78 0.245 0.294 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F2 NW APARTMENT 2687.39 3224.87 0.243 0.291 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F2 SE APARTMENT 2433.46 2920.15 0.220 0.264 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F2 NE APARTMENT 2129.51 2555.41 0.192 0.231 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F2 N1 APARTMENT 1584.61 1901.53 0.143 0.172 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F2 N2 APARTMENT 1575.57 1890.69 0.142 0.171 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F2 S1 APARTMENT 1579.99 1895.99 0.143 0.171 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F2 S2 APARTMENT 1595.66 1914.79 0.144 0.173 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F3 SW APARTMENT 2720.91 3265.09 0.246 0.295 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F3 NW APARTMENT 2697.89 3237.46 0.244 0.292 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F3 SE APARTMENT 2291.80 2750.15 0.207 0.248 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F3 NE APARTMENT 2154.38 2585.26 0.195 0.233 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F3 N1 APARTMENT 1609.49 1931.39 0.145 0.174 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F3 N2 APARTMENT 1600.61 1920.73 0.145 0.173 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F3 S1 APARTMENT 1604.99 1925.98 0.145 0.174 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F3 S2 APARTMENT 1611.45 1933.74 0.146 0.175 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F4 SW APARTMENT 2731.32 3277.58 0.247 0.296 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F4 NW APARTMENT 2708.60 3250.32 0.245 0.293 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F4 SE APARTMENT 2293.06 2751.68 0.207 0.248 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F4 NE APARTMENT 2167.15 2600.58 0.196 0.235 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F4 N1 APARTMENT 1625.55 1950.65 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F4 N2 APARTMENT 1616.77 1940.12 0.146 0.175 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F4 S1 APARTMENT 1619.73 1943.68 0.146 0.175 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F4 S2 APARTMENT 1624.59 1949.51 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
M SW APARTMENT 2764.59 3317.51 0.250 0.300 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
M NW APARTMENT 2742.87 3291.44 0.248 0.297 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
M SE APARTMENT 2329.67 2795.60 0.210 0.252 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
M NE APARTMENT 2202.55 2643.06 0.199 0.239 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
M N1 APARTMENT 1662.65 1995.17 0.150 0.180 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
M N2 APARTMENT 1653.96 1984.75 0.149 0.179 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
M S1 APARTMENT 1655.03 1986.03 0.149 0.179 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
M S2 APARTMENT 1659.49 1991.39 0.150 0.180 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F6 SW APARTMENT 2731.77 3278.13 0.247 0.296 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F6 NW APARTMENT 2709.23 3251.08 0.245 0.294 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F6 SE APARTMENT 2302.17 2762.60 0.208 0.249 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F6 NE APARTMENT 2170.98 2605.18 0.196 0.235 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F6 N1 APARTMENT 1633.91 1960.69 0.148 0.177 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F6 N2 APARTMENT 1625.35 1950.42 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F6 S1 APARTMENT 1626.04 1951.25 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F6 S2 APARTMENT 1630.44 1956.53 0.147 0.177 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F7 SW APARTMENT 2722.91 3267.49 0.246 0.295 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F7 NW APARTMENT 2700.64 3240.76 0.244 0.293 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F7 SE APARTMENT 2297.79 2757.35 0.207 0.249 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F7 NE APARTMENT 2163.88 2596.65 0.195 0.234 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F7 N1 APARTMENT 1628.66 1954.39 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F7 N2 APARTMENT 1620.19 1944.22 0.146 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F7 S1 APARTMENT 1619.79 1943.74 0.146 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F7 S2 APARTMENT 1624.18 1949.02 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F8 SW APARTMENT 2728.65 3274.38 0.246 0.296 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F8 NW APARTMENT 2706.55 3247.86 0.244 0.293 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F8 SE APARTMENT 2306.90 2768.29 0.208 0.250 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
F8 NE APARTMENT 2170.39 2604.46 0.196 0.235 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 34.62 0.00682
F8 N1 APARTMENT 1637.35 1964.82 0.148 0.177 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F8 N2 APARTMENT 1628.97 1954.77 0.147 0.177 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F8 S1 APARTMENT 1627.13 1952.55 0.147 0.176 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F8 S2 APARTMENT 1631.53 1957.84 0.147 0.177 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F9 SW APARTMENT 2822.14 3386.57 0.255 0.306 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 36.54 0.00682
F9 NW APARTMENT 2800.47 3360.56 0.253 0.303 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 35.95 0.00682
F9 SE APARTMENT 2383.56 2860.28 0.215 0.258 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
F9 NE APARTMENT 2246.96 2696.35 0.203 0.243 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 35.30 0.00682
F9 N1 APARTMENT 1722.89 2067.46 0.156 0.187 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F9 N2 APARTMENT 1714.54 2057.45 0.155 0.186 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98 0.00682
F9 S1 APARTMENT 1692.45 2030.94 0.153 0.183 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 38.10 0.00682
F9 S2 APARTMENT 1696.53 2035.83 0.153 0.184 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 38.10 0.00682
T SW APARTMENT 3458.85 4150.62 0.312 0.375 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 37.52 0.00682
T NW APARTMENT 3393.91 4072.69 0.306 0.368 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80 0.00682
T SE APARTMENT 2996.70 3596.04 0.271 0.325 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 37.94 0.00682
T NE APARTMENT 2770.73 3324.88 0.250 0.300 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 38.10 0.00682
T N1 APARTMENT 2136.21 2563.45 0.193 0.231 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 37.91 0.00682
T N2 APARTMENT 2129.87 2555.84 0.192 0.231 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 38.10 0.00682
T S1 APARTMENT 2344.87 2813.84 0.212 0.254 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682
T S2 APARTMENT 2348.45 2818.14 0.212 0.254 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 38.10 0.00682


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1257.17 1508.60 0.065 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G NW APARTMENT 1255.20 1506.24 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
OFFICE 1598.51 1918.22 0.082 0.098 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -5.20 0.00281
G NE APARTMENT 1252.30 1502.76 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G N1 APARTMENT 767.02 920.42 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G N2 APARTMENT 766.95 920.34 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G S1 APARTMENT 765.80 918.96 0.039 0.047 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
G S2 APARTMENT 772.92 927.51 0.040 0.048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -5.20 0.00281
F2 SW APARTMENT 1218.64 1462.37 0.063 0.075 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 NW APARTMENT 1214.39 1457.27 0.062 0.075 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 SE APARTMENT 1237.29 1484.75 0.063 0.076 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 NE APARTMENT 1211.41 1453.69 0.062 0.075 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 N1 APARTMENT 620.40 744.47 0.032 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 N2 APARTMENT 620.32 744.38 0.032 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 S1 APARTMENT 627.00 752.39 0.032 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F2 S2 APARTMENT 628.38 754.05 0.032 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 SW APARTMENT 1193.60 1432.32 0.061 0.073 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 NW APARTMENT 1190.75 1428.89 0.061 0.073 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 SE APARTMENT 1193.59 1432.31 0.061 0.073 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 NE APARTMENT 1188.29 1425.95 0.061 0.073 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 N1 APARTMENT 582.99 699.59 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 N2 APARTMENT 582.93 699.52 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 S1 APARTMENT 586.50 703.80 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F3 S2 APARTMENT 586.67 704.00 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 SW APARTMENT 1203.72 1444.47 0.062 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 NW APARTMENT 1202.03 1442.44 0.062 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 SE APARTMENT 1202.02 1442.43 0.062 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 NE APARTMENT 1200.07 1440.08 0.062 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 N1 APARTMENT 582.36 698.83 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 N2 APARTMENT 582.31 698.77 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 S1 APARTMENT 584.48 701.37 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F4 S2 APARTMENT 584.46 701.35 0.030 0.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M SW APARTMENT 1197.17 1436.61 0.061 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M NW APARTMENT 1195.34 1434.41 0.061 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M SE APARTMENT 1195.69 1434.82 0.061 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M NE APARTMENT 1193.83 1432.59 0.061 0.074 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M N1 APARTMENT 568.38 682.06 0.029 0.035 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M N2 APARTMENT 568.34 682.01 0.029 0.035 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M S1 APARTMENT 570.59 684.71 0.029 0.035 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
M S2 APARTMENT 570.55 684.66 0.029 0.035 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 SW APARTMENT 1249.58 1499.50 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 NW APARTMENT 1249.21 1499.05 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 SE APARTMENT 1248.47 1498.17 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 NE APARTMENT 1248.09 1497.71 0.064 0.077 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 N1 APARTMENT 611.45 733.74 0.031 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 N2 APARTMENT 611.42 733.70 0.031 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 S1 APARTMENT 612.17 734.60 0.031 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F6 S2 APARTMENT 612.14 734.56 0.031 0.038 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 SW APARTMENT 1280.09 1536.10 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 NW APARTMENT 1280.08 1536.09 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 SE APARTMENT 1279.35 1535.22 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 NE APARTMENT 1279.34 1535.20 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 N1 APARTMENT 634.87 761.84 0.033 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 N2 APARTMENT 634.85 761.81 0.033 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 S1 APARTMENT 635.19 762.22 0.033 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F7 S2 APARTMENT 635.17 762.20 0.033 0.039 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 SW APARTMENT 1314.23 1577.08 0.067 0.081 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 NW APARTMENT 1314.36 1577.24 0.067 0.081 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 SE APARTMENT 1313.83 1576.60 0.067 0.081 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 NE APARTMENT 1313.96 1576.75 0.067 0.081 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 N1 APARTMENT 662.96 795.55 0.034 0.041 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 N2 APARTMENT 662.94 795.53 0.034 0.041 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 S1 APARTMENT 663.11 795.73 0.034 0.041 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F8 S2 APARTMENT 663.10 795.71 0.034 0.041 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 SW APARTMENT 1443.24 1731.89 0.074 0.089 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 NW APARTMENT 1441.65 1729.98 0.074 0.089 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 SE APARTMENT 1443.16 1731.79 0.074 0.089 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 NE APARTMENT 1441.56 1729.87 0.074 0.089 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 N1 APARTMENT 778.23 933.88 0.040 0.048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 N2 APARTMENT 778.23 933.88 0.040 0.048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 S1 APARTMENT 779.72 935.66 0.040 0.048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
F9 S2 APARTMENT 779.71 935.66 0.040 0.048 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T SW APARTMENT 1909.80 2291.76 0.098 0.118 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T NW APARTMENT 1913.87 2296.64 0.098 0.118 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T SE APARTMENT 1909.97 2291.97 0.098 0.118 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T NE APARTMENT 1914.04 2296.84 0.098 0.118 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T N1 APARTMENT 1288.78 1546.53 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T N2 APARTMENT 1288.78 1546.53 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T S1 APARTMENT 1282.20 1538.64 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281
T S2 APARTMENT 1282.21 1538.65 0.066 0.079 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -5.20 0.00281


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.24 0.24 0.08 0.08
AIRLOOP G NW 0.24 0.24 0.08 0.08
AIRLOOP OFFICE 0.31 0.31 0.10 0.10
AIRLOOP G NE 0.18 0.18 0.08 0.08
AIRLOOP G N1 0.14 0.14 0.05 0.05
AIRLOOP G N2 0.13 0.13 0.05 0.05
AIRLOOP G S1 0.13 0.13 0.05 0.05
AIRLOOP G S2 0.14 0.14 0.05 0.05
AIRLOOP F2 SW 0.29 0.29 0.08 0.08
AIRLOOP F2 NW 0.29 0.29 0.07 0.07
AIRLOOP F2 SE 0.26 0.26 0.08 0.08
AIRLOOP F2 NE 0.23 0.23 0.07 0.07
AIRLOOP F2 N1 0.17 0.17 0.04 0.04
AIRLOOP F2 N2 0.17 0.17 0.04 0.04
AIRLOOP F2 S1 0.17 0.17 0.04 0.04
AIRLOOP F2 S2 0.17 0.17 0.04 0.04
AIRLOOP F3 SW 0.29 0.29 0.07 0.07
AIRLOOP F3 NW 0.29 0.29 0.07 0.07
AIRLOOP F3 SE 0.25 0.25 0.07 0.07
AIRLOOP F3 NE 0.23 0.23 0.07 0.07
AIRLOOP F3 N1 0.17 0.17 0.04 0.04
AIRLOOP F3 N2 0.17 0.17 0.04 0.04
AIRLOOP F3 S1 0.17 0.17 0.04 0.04
AIRLOOP F3 S2 0.17 0.17 0.04 0.04
AIRLOOP F4 SW 0.30 0.30 0.07 0.07
AIRLOOP F4 NW 0.29 0.29 0.07 0.07
AIRLOOP F4 SE 0.25 0.25 0.07 0.07
AIRLOOP F4 NE 0.23 0.23 0.07 0.07
AIRLOOP F4 N1 0.18 0.18 0.04 0.04
AIRLOOP F4 N2 0.18 0.18 0.04 0.04
AIRLOOP F4 S1 0.18 0.18 0.04 0.04
AIRLOOP F4 S2 0.18 0.18 0.04 0.04
AIRLOOP M SW 0.30 0.30 0.07 0.07
AIRLOOP M NW 0.30 0.30 0.07 0.07
AIRLOOP M SE 0.25 0.25 0.07 0.07
AIRLOOP M NE 0.24 0.24 0.07 0.07
AIRLOOP M N1 0.18 0.18 0.03 0.03
AIRLOOP M N2 0.18 0.18 0.03 0.03
AIRLOOP M S1 0.18 0.18 0.04 0.04
AIRLOOP M S2 0.18 0.18 0.04 0.04
AIRLOOP F6 SW 0.30 0.30 0.08 0.08
AIRLOOP F6 NW 0.29 0.29 0.08 0.08
AIRLOOP F6 SE 0.25 0.25 0.08 0.08
AIRLOOP F6 NE 0.24 0.24 0.08 0.08
AIRLOOP F6 N1 0.18 0.18 0.04 0.04
AIRLOOP F6 N2 0.18 0.18 0.04 0.04
AIRLOOP F6 S1 0.18 0.18 0.04 0.04
AIRLOOP F6 S2 0.18 0.18 0.04 0.04
AIRLOOP F7 SW 0.30 0.30 0.08 0.08
AIRLOOP F7 NW 0.29 0.29 0.08 0.08
AIRLOOP F7 SE 0.25 0.25 0.08 0.08
AIRLOOP F7 NE 0.23 0.23 0.08 0.08
AIRLOOP F7 N1 0.18 0.18 0.04 0.04
AIRLOOP F7 N2 0.18 0.18 0.04 0.04
AIRLOOP F7 S1 0.18 0.18 0.04 0.04
AIRLOOP F7 S2 0.18 0.18 0.04 0.04
AIRLOOP F8 SW 0.30 0.30 0.08 0.08
AIRLOOP F8 NW 0.29 0.29 0.08 0.08
AIRLOOP F8 SE 0.25 0.25 0.08 0.08
AIRLOOP F8 NE 0.24 0.24 0.08 0.08
AIRLOOP F8 N1 0.18 0.18 0.04 0.04
AIRLOOP F8 N2 0.18 0.18 0.04 0.04
AIRLOOP F8 S1 0.18 0.18 0.04 0.04
AIRLOOP F8 S2 0.18 0.18 0.04 0.04
AIRLOOP F9 SW 0.31 0.31 0.09 0.09
AIRLOOP F9 NW 0.30 0.30 0.09 0.09
AIRLOOP F9 SE 0.26 0.26 0.09 0.09
AIRLOOP F9 NE 0.24 0.24 0.09 0.09
AIRLOOP F9 N1 0.19 0.19 0.05 0.05
AIRLOOP F9 N2 0.19 0.19 0.05 0.05
AIRLOOP F9 S1 0.18 0.18 0.05 0.05
AIRLOOP F9 S2 0.18 0.18 0.05 0.05
AIRLOOP T SW 0.37 0.37 0.12 0.12
AIRLOOP T NW 0.37 0.37 0.12 0.12
AIRLOOP T SE 0.32 0.32 0.12 0.12
AIRLOOP T NE 0.30 0.30 0.12 0.12
AIRLOOP T N1 0.23 0.23 0.08 0.08
AIRLOOP T N2 0.23 0.23 0.08 0.08
AIRLOOP T S1 0.25 0.25 0.08 0.08
AIRLOOP T S2 0.25 0.25 0.08 0.08



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3490.75 4573.25 613.75
G NW APARTMENT 3239.75 5481.25 680.75
OFFICE 1065.50 429.00 3.50
G NE APARTMENT 3273.50 5493.25 694.75
G N1 APARTMENT 3061.25 5895.25 845.00
G N2 APARTMENT 3062.25 5893.25 844.00
G S1 APARTMENT 3290.50 4898.25 711.25
G S2 APARTMENT 3311.75 4833.00 702.25
F2 SW APARTMENT 4200.75 2657.75 371.75
F2 NW APARTMENT 3639.00 4377.50 429.25
F2 SE APARTMENT 4333.75 2427.75 320.00
F2 NE APARTMENT 3672.50 4377.00 422.75
F2 N1 APARTMENT 3479.75 4640.25 526.50
F2 N2 APARTMENT 3479.75 4642.00 526.00
F2 S1 APARTMENT 4201.50 2460.50 426.00
F2 S2 APARTMENT 4207.25 2436.50 424.75
F3 SW APARTMENT 4344.00 2295.25 365.00
F3 NW APARTMENT 3731.00 4154.50 411.25
F3 SE APARTMENT 4416.25 2261.50 330.50
F3 NE APARTMENT 3752.50 4146.50 406.75
F3 N1 APARTMENT 3596.00 4349.50 495.25
F3 N2 APARTMENT 3593.25 4349.00 494.50
F3 S1 APARTMENT 4434.00 1925.75 410.00
F3 S2 APARTMENT 4436.75 1924.25 410.00
F4 SW APARTMENT 4362.00 2248.25 369.00
F4 NW APARTMENT 3746.75 4111.00 415.00
F4 SE APARTMENT 4419.25 2247.25 340.50
F4 NE APARTMENT 3769.50 4097.25 411.00
F4 N1 APARTMENT 3632.50 4242.25 488.75
F4 N2 APARTMENT 3632.00 4251.50 490.00
F4 S1 APARTMENT 4486.25 1810.00 410.25
F4 S2 APARTMENT 4486.00 1816.50 410.75
M SW APARTMENT 4366.25 2236.00 365.50
M NW APARTMENT 3762.75 4076.25 404.00
M SE APARTMENT 4428.00 2241.75 337.00
M NE APARTMENT 3782.00 4074.75 402.75
M N1 APARTMENT 3661.00 4176.25 476.25
M N2 APARTMENT 3658.75 4185.50 476.75
M S1 APARTMENT 4513.25 1755.75 399.75
M S2 APARTMENT 4512.75 1763.00 401.25
F6 SW APARTMENT 4263.50 2442.00 382.25
F6 NW APARTMENT 3696.25 4221.50 436.50
F6 SE APARTMENT 4316.50 2435.50 357.50
F6 NE APARTMENT 3717.00 4219.50 431.75
F6 N1 APARTMENT 3588.25 4352.50 504.50
F6 N2 APARTMENT 3585.25 4351.25 504.75
F6 S1 APARTMENT 4396.50 1980.25 424.50
F6 S2 APARTMENT 4394.00 1984.75 424.50
F7 SW APARTMENT 4201.75 2609.50 398.00
F7 NW APARTMENT 3657.75 4309.25 453.25
F7 SE APARTMENT 4246.25 2574.50 368.00
F7 NE APARTMENT 3685.00 4302.50 446.00
F7 N1 APARTMENT 3548.50 4448.50 516.75
F7 N2 APARTMENT 3545.25 4446.00 517.00
F7 S1 APARTMENT 4323.25 2152.75 438.00
F7 S2 APARTMENT 4322.25 2156.50 438.00
F8 SW APARTMENT 4145.50 2752.50 406.25
F8 NW APARTMENT 3627.25 4365.50 459.50
F8 SE APARTMENT 4184.00 2702.75 378.50
F8 NE APARTMENT 3666.75 4387.75 458.00
F8 N1 APARTMENT 3525.50 4503.25 522.25
F8 N2 APARTMENT 3520.50 4505.75 521.75
F8 S1 APARTMENT 4246.50 2328.25 443.50
F8 S2 APARTMENT 4243.00 2336.25 443.75
F9 SW APARTMENT 4055.50 2970.75 401.50
F9 NW APARTMENT 3605.25 4442.75 454.50
F9 SE APARTMENT 4087.25 2882.00 374.50
F9 NE APARTMENT 3649.75 4461.00 448.00
F9 N1 APARTMENT 3500.75 4555.00 511.25
F9 N2 APARTMENT 3500.00 4558.50 512.50
F9 S1 APARTMENT 4120.50 2593.50 438.25
F9 S2 APARTMENT 4119.75 2596.75 438.75
T SW APARTMENT 4269.75 3608.50 517.25
T NW APARTMENT 3798.50 4660.50 688.50
T SE APARTMENT 4341.25 3529.00 517.25
T NE APARTMENT 3847.50 4647.25 687.25
T N1 APARTMENT 3568.50 4818.50 610.00
T N2 APARTMENT 3570.75 4818.50 611.25
T S1 APARTMENT 4159.25 3408.00 501.25
T S2 APARTMENT 4166.75 3404.75 500.00
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5293.75 5943.00 1081.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.75 18.75 3.75 18.75
G NW APARTMENT 2.00 22.50 2.00 22.50
OFFICE 2.50 0.25 0.00 0.00
G NE APARTMENT 4.25 34.50 4.25 34.50
G N1 APARTMENT 3.50 36.00 3.50 36.00
G N2 APARTMENT 5.00 36.25 5.00 36.25
G S1 APARTMENT 0.00 136.75 0.00 136.75
G S2 APARTMENT 0.00 111.00 0.00 111.00
F2 SW APARTMENT 0.75 15.75 0.75 15.75
F2 NW APARTMENT 0.50 16.50 0.50 16.50
F2 SE APARTMENT 0.25 19.50 0.25 19.50
F2 NE APARTMENT 1.25 28.50 1.25 28.50
F2 N1 APARTMENT 0.00 23.50 0.00 23.50
F2 N2 APARTMENT 0.25 23.25 0.25 23.25
F2 S1 APARTMENT 0.00 160.00 0.00 160.00
F2 S2 APARTMENT 0.00 151.25 0.00 151.25
F3 SW APARTMENT 0.00 21.50 0.00 21.50
F3 NW APARTMENT 0.50 18.75 0.50 18.75
F3 SE APARTMENT 0.00 70.25 0.00 70.25
F3 NE APARTMENT 1.75 37.50 1.75 37.50
F3 N1 APARTMENT 0.25 29.25 0.25 29.25
F3 N2 APARTMENT 0.25 30.25 0.25 30.25
F3 S1 APARTMENT 0.00 182.25 0.00 182.25
F3 S2 APARTMENT 0.00 181.00 0.00 181.00
F4 SW APARTMENT 0.00 22.75 0.00 22.75
F4 NW APARTMENT 0.00 19.00 0.00 19.00
F4 SE APARTMENT 0.00 74.25 0.00 74.25
F4 NE APARTMENT 1.50 41.50 1.50 41.50
F4 N1 APARTMENT 0.25 32.25 0.25 32.25
F4 N2 APARTMENT 0.25 33.00 0.25 33.00
F4 S1 APARTMENT 0.00 179.75 0.00 179.75
F4 S2 APARTMENT 0.00 180.25 0.00 180.25
M SW APARTMENT 0.00 23.00 0.00 23.00
M NW APARTMENT 0.00 19.50 0.00 19.50
M SE APARTMENT 0.25 71.25 0.25 71.25
M NE APARTMENT 1.50 44.25 1.50 44.25
M N1 APARTMENT 0.00 33.00 0.00 33.00
M N2 APARTMENT 0.25 34.00 0.25 34.00
M S1 APARTMENT 0.00 172.50 0.00 172.50
M S2 APARTMENT 0.00 173.50 0.00 173.50
F6 SW APARTMENT 0.25 24.25 0.25 24.25
F6 NW APARTMENT 0.50 19.75 0.50 19.75
F6 SE APARTMENT 0.25 69.75 0.25 69.75
F6 NE APARTMENT 1.00 47.75 1.00 47.75
F6 N1 APARTMENT 0.25 34.50 0.25 34.50
F6 N2 APARTMENT 0.25 35.75 0.25 35.75
F6 S1 APARTMENT 0.00 166.50 0.00 166.50
F6 S2 APARTMENT 0.00 167.00 0.00 167.00
F7 SW APARTMENT 0.50 23.00 0.50 23.00
F7 NW APARTMENT 0.00 20.25 0.00 20.25
F7 SE APARTMENT 0.00 65.50 0.00 65.50
F7 NE APARTMENT 1.75 49.25 1.75 49.25
F7 N1 APARTMENT 0.75 36.50 0.75 36.50
F7 N2 APARTMENT 1.00 37.25 1.00 37.25
F7 S1 APARTMENT 0.00 161.25 0.00 161.25
F7 S2 APARTMENT 0.00 159.50 0.00 159.50
F8 SW APARTMENT 0.00 21.00 0.00 21.00
F8 NW APARTMENT 0.50 20.25 0.50 20.25
F8 SE APARTMENT 0.50 59.75 0.50 59.75
F8 NE APARTMENT 1.25 52.50 1.25 52.50
F8 N1 APARTMENT 0.25 37.75 0.25 37.75
F8 N2 APARTMENT 0.50 39.25 0.50 39.25
F8 S1 APARTMENT 0.00 152.75 0.00 152.75
F8 S2 APARTMENT 0.00 151.75 0.00 151.75
F9 SW APARTMENT 0.00 17.75 0.00 17.75
F9 NW APARTMENT 0.00 19.75 0.00 19.75
F9 SE APARTMENT 0.50 35.00 0.50 35.00
F9 NE APARTMENT 0.50 36.75 0.50 36.75
F9 N1 APARTMENT 0.50 33.00 0.50 33.00
F9 N2 APARTMENT 2.00 34.00 2.00 34.00
F9 S1 APARTMENT 0.00 127.50 0.00 127.50
F9 S2 APARTMENT 0.00 125.25 0.00 125.25
T SW APARTMENT 0.00 9.75 0.00 9.75
T NW APARTMENT 0.00 16.25 0.00 16.25
T SE APARTMENT 0.00 26.00 0.00 26.00
T NE APARTMENT 0.00 8.50 0.00 8.50
T N1 APARTMENT 0.00 18.25 0.00 18.25
T N2 APARTMENT 1.25 16.00 1.25 16.00
T S1 APARTMENT 1.00 74.25 1.00 74.25
T S2 APARTMENT 1.00 74.25 1.00 74.25
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 43.00 295.00 40.50 294.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.355 0.091 0.000 0.348
G NW APARTMENT 1.71 2.50 268.96 0.354 0.091 0.000 0.332
OFFICE 0.94 1.00 268.96 0.519 0.099 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.354 0.091 0.000 0.331
G N1 APARTMENT 1.71 2.50 268.96 0.354 0.055 0.000 0.324
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.055 0.000 0.324
G S1 APARTMENT 1.71 2.50 268.96 0.355 0.055 0.000 0.344
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.055 0.000 0.345
F2 SW APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.407
F2 NW APARTMENT 1.71 2.50 268.96 0.354 0.130 0.000 0.392
F2 SE APARTMENT 1.71 2.50 268.96 0.355 0.131 0.000 0.408
F2 NE APARTMENT 1.71 2.50 268.96 0.354 0.130 0.000 0.391
F2 N1 APARTMENT 1.71 2.50 268.96 0.354 0.079 0.000 0.387
F2 N2 APARTMENT 1.71 2.50 268.97 0.354 0.079 0.000 0.387
F2 S1 APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.406
F2 S2 APARTMENT 1.71 2.50 268.97 0.355 0.079 0.000 0.406
F3 SW APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.449
F3 NW APARTMENT 1.71 2.50 268.96 0.354 0.154 0.000 0.434
F3 SE APARTMENT 1.71 2.50 268.96 0.355 0.155 0.000 0.449
F3 NE APARTMENT 1.71 2.50 268.96 0.354 0.154 0.000 0.433
F3 N1 APARTMENT 1.71 2.50 268.96 0.355 0.093 0.000 0.430
F3 N2 APARTMENT 1.71 2.50 268.97 0.354 0.093 0.000 0.430
F3 S1 APARTMENT 1.71 2.50 268.96 0.355 0.093 0.000 0.448
F3 S2 APARTMENT 1.71 2.50 268.97 0.355 0.093 0.000 0.448
F4 SW APARTMENT 1.71 2.50 268.96 0.355 0.173 0.000 0.467
F4 NW APARTMENT 1.71 2.50 268.96 0.354 0.172 0.000 0.451
F4 SE APARTMENT 1.71 2.50 268.96 0.355 0.173 0.000 0.467
F4 NE APARTMENT 1.71 2.50 268.96 0.354 0.172 0.000 0.450
F4 N1 APARTMENT 1.71 2.50 268.96 0.355 0.104 0.000 0.448
F4 N2 APARTMENT 1.71 2.50 268.97 0.355 0.104 0.000 0.448
F4 S1 APARTMENT 1.71 2.50 268.96 0.355 0.104 0.000 0.466
F4 S2 APARTMENT 1.71 2.50 268.97 0.355 0.104 0.000 0.466
M SW APARTMENT 1.71 2.50 268.96 0.355 0.188 0.000 0.490
M NW APARTMENT 1.71 2.50 268.96 0.354 0.187 0.000 0.473
M SE APARTMENT 1.71 2.50 268.96 0.355 0.188 0.000 0.490
M NE APARTMENT 1.71 2.50 268.96 0.354 0.187 0.000 0.473
M N1 APARTMENT 1.71 2.50 268.96 0.355 0.113 0.000 0.470
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.113 0.000 0.470
M S1 APARTMENT 1.71 2.50 268.96 0.355 0.113 0.000 0.489
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.113 0.000 0.489
F6 SW APARTMENT 1.71 2.50 268.96 0.355 0.200 0.000 0.510
F6 NW APARTMENT 1.71 2.50 268.96 0.354 0.200 0.000 0.492
F6 SE APARTMENT 1.71 2.50 268.96 0.355 0.200 0.000 0.510
F6 NE APARTMENT 1.71 2.50 268.96 0.354 0.200 0.000 0.491
F6 N1 APARTMENT 1.71 2.50 268.96 0.354 0.121 0.000 0.489
F6 N2 APARTMENT 1.71 2.50 268.97 0.354 0.121 0.000 0.489
F6 S1 APARTMENT 1.71 2.50 268.96 0.355 0.121 0.000 0.509
F6 S2 APARTMENT 1.71 2.50 268.97 0.355 0.121 0.000 0.509
F7 SW APARTMENT 1.71 2.50 268.96 0.355 0.212 0.000 0.526
F7 NW APARTMENT 1.71 2.50 268.96 0.354 0.212 0.000 0.507
F7 SE APARTMENT 1.71 2.50 268.96 0.355 0.212 0.000 0.526
F7 NE APARTMENT 1.71 2.50 268.96 0.354 0.212 0.000 0.507
F7 N1 APARTMENT 1.71 2.50 268.96 0.354 0.128 0.000 0.504
F7 N2 APARTMENT 1.71 2.50 268.97 0.354 0.128 0.000 0.504
F7 S1 APARTMENT 1.71 2.50 268.96 0.355 0.128 0.000 0.525
F7 S2 APARTMENT 1.71 2.50 268.97 0.355 0.128 0.000 0.525
F8 SW APARTMENT 1.71 2.50 268.96 0.355 0.222 0.000 0.544
F8 NW APARTMENT 1.71 2.50 268.96 0.354 0.222 0.000 0.524
F8 SE APARTMENT 1.71 2.50 268.96 0.355 0.222 0.000 0.545
F8 NE APARTMENT 1.71 2.50 268.96 0.354 0.222 0.000 0.524
F8 N1 APARTMENT 1.71 2.50 268.96 0.354 0.134 0.000 0.521
F8 N2 APARTMENT 1.71 2.50 268.97 0.354 0.134 0.000 0.521
F8 S1 APARTMENT 1.71 2.50 268.96 0.355 0.134 0.000 0.543
F8 S2 APARTMENT 1.71 2.50 268.97 0.355 0.134 0.000 0.544
F9 SW APARTMENT 1.71 2.50 268.96 0.355 0.231 0.000 0.560
F9 NW APARTMENT 1.71 2.50 268.96 0.354 0.231 0.000 0.539
F9 SE APARTMENT 1.71 2.50 268.96 0.355 0.231 0.000 0.560
F9 NE APARTMENT 1.71 2.50 268.96 0.354 0.231 0.000 0.539
F9 N1 APARTMENT 1.71 2.50 268.96 0.354 0.139 0.000 0.536
F9 N2 APARTMENT 1.71 2.50 268.97 0.354 0.139 0.000 0.536
F9 S1 APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.559
F9 S2 APARTMENT 1.71 2.50 268.97 0.355 0.140 0.000 0.559
T SW APARTMENT 1.71 2.50 268.96 0.354 0.240 0.000 0.571
T NW APARTMENT 1.71 2.50 268.96 0.354 0.240 0.000 0.551
T SE APARTMENT 1.71 2.50 268.96 0.354 0.240 0.000 0.572
T NE APARTMENT 1.71 2.50 268.96 0.354 0.240 0.000 0.551
T N1 APARTMENT 1.71 2.50 268.96 0.354 0.145 0.000 0.548
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.145 0.000 0.548
T S1 APARTMENT 1.71 2.50 268.96 0.355 0.145 0.000 0.570
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.145 0.000 0.570
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.506 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 640.88 20322.08 12-JAN-22:30 20322.08 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1335.91 20702.61 07-MAR-03:30 85481.08 26-JUL-17:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
ElectricityPurchased:Plant 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
Cogeneration:ElectricityPurchased 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
ElectricityNet:Plant 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
Cogeneration:ElectricityNet 3120.83 58263.09 07-MAR-03:30 172060.80 17-JUL-20:00
ExteriorLights:Electricity 168.57 0.00 01-JAN-07:15 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.57 0.00 01-JAN-07:15 10720.10 01-JAN-00:15
General:Fans:Electricity 640.88 20322.08 12-JAN-22:30 20322.08 01-JAN-00:15
Cooling:Electricity 659.36 0.00 01-JAN-00:45 64061.41 15-JUN-15:30
Heating:Electricity 14.85 0.00 01-JAN-09:30 26280.44 10-APR-17:00
Electricity:Plant 68.84 36.93 16-JAN-10:45 3900.85 20-JUL-16:15
HeatRejection:Electricity 24.64 0.00 01-JAN-01:00 2478.79 20-JUL-16:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 44.21 36.93 16-JAN-10:45 1422.06 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1015.24 9260.51 01-JAN-00:15 142092.63 27-DEC-07:30
Gas:Plant 1015.24 9260.51 01-JAN-00:15 142092.63 27-DEC-07:30
WaterSystems:Gas 995.45 9260.51 01-JAN-00:15 83866.65 07-FEB-08:00
Water Heater:WaterSystems:Gas 995.45 9260.51 01-JAN-00:15 83866.65 07-FEB-08:00
Heating:Gas 19.80 0.00 01-JAN-00:15 63834.18 27-DEC-06:15
Boiler:Heating:Gas 19.80 0.00 01-JAN-00:15 63834.18 27-DEC-06:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 2697.06 0.00 01-JAN-00:45 304693.33 20-JUL-16:15
PlantLoopCoolingDemand:HVAC 2697.06 0.00 01-JAN-00:45 304693.33 20-JUL-16:15
CoolingCoils:PlantLoopCoolingDemand 2697.06 0.00 01-JAN-00:45 304693.33 20-JUL-16:15


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 7013.87 0.00 01-JAN-03:30 0.00 14-JUN-17:15
Water:Plant 7013.87 0.00 01-JAN-03:30 0.00 14-JUN-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-03:00 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 7013.87 0.00 01-JAN-03:30 0.00 14-JUN-17:15
MainsWater:Plant 7013.87 0.00 01-JAN-03:30 0.00 14-JUN-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-03:00 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-03:00 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-03:00 0.00 01-JAN-07:15
HeatRejection:Water 2235.35 0.00 01-JAN-01:00 0.00 14-JUN-16:15
HeatRejection:MainsWater 2235.35 0.00 01-JAN-01:00 0.00 14-JUN-16:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 795.42 391.07 31-JUL-01:15 114085.18 10-APR-17:00
PlantLoopHeatingDemand:Plant 755.20 391.07 31-JUL-01:15 53294.57 30-JAN-07:15
WaterSystems:PlantLoopHeatingDemand 755.20 391.07 31-JUL-01:15 53294.57 30-JAN-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 4625.22 5597.82 02-MAY-03:00 424514.20 05-JUN-17:15
EnergyTransfer:Building 1722.05 3581.43 25-AUG-05:45 174532.02 05-JUN-17:00
EnergyTransfer:Zone:G SW APARTMENT 16.52 0.01 22-FEB-22:45 2528.66 29-SEP-15:15
Heating:EnergyTransfer 50.48 0.00 02-JAN-23:45 112307.63 10-APR-17:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.60 0.00 01-JAN-00:15 671.81 27-DEC-06:00
Cooling:EnergyTransfer 1671.57 0.00 03-JAN-18:15 174532.02 05-JUN-17:00
Cooling:EnergyTransfer:Zone:G SW APARTMENT 15.92 0.00 01-JAN-14:00 2528.66 29-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 13.73 0.00 11-APR-20:45 2370.62 12-JUN-17:45
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.60 0.00 01-JAN-00:15 979.79 06-APR-14:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 12.12 0.00 01-JAN-00:30 2370.62 12-JUN-17:45
EnergyTransfer:Zone:OFFICE 22.79 0.04 23-OCT-00:15 3133.75 29-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 0.48 0.00 01-JAN-00:15 764.45 27-DEC-07:30
Cooling:EnergyTransfer:Zone:OFFICE 22.31 0.00 01-JAN-06:45 3133.75 29-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 13.75 0.01 09-DEC-00:30 1767.79 17-JUN-18:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.38 0.00 01-JAN-08:30 967.14 31-JAN-17:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 12.38 0.00 01-JAN-00:15 1767.79 17-JUN-18:15
EnergyTransfer:Zone:G N1 APARTMENT 10.08 0.05 02-NOV-13:30 1327.67 09-JUN-17:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.62 0.00 01-JAN-00:15 992.92 06-APR-14:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 9.47 0.00 01-JAN-14:00 1327.67 09-JUN-17:30
EnergyTransfer:Zone:G N2 APARTMENT 10.09 0.04 02-NOV-13:30 1315.87 09-JUN-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.62 0.00 01-JAN-00:15 983.50 06-APR-14:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 9.48 0.00 01-JAN-14:00 1315.87 09-JUN-17:30
EnergyTransfer:Zone:G S1 APARTMENT 13.62 0.00 05-MAY-08:45 1533.82 30-SEP-11:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.07 0.00 01-JAN-00:15 725.53 06-APR-14:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 13.55 0.00 03-JAN-13:30 1533.82 30-SEP-11:15
EnergyTransfer:Zone:G S2 APARTMENT 13.82 0.00 06-MAR-17:45 1582.19 30-SEP-11:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.07 0.00 01-JAN-00:15 623.70 06-APR-14:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 13.75 0.00 02-JAN-16:00 1582.19 30-SEP-11:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 26.16 0.00 23-APR-01:45 3104.05 29-SEP-15:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.29 0.00 01-JAN-00:15 513.22 27-DEC-06:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 25.86 0.00 01-JAN-15:15 3104.05 29-SEP-15:15
EnergyTransfer:Zone:F2 NW APARTMENT 19.68 0.01 24-JAN-02:30 2905.14 17-JUN-17:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 1.02 0.00 01-JAN-00:15 908.45 31-JAN-17:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 18.66 0.00 01-JAN-10:45 2905.14 17-JUN-17:30
EnergyTransfer:Zone:F2 SE APARTMENT 27.56 0.01 03-DEC-01:30 2779.74 01-OCT-12:30
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.19 0.00 01-JAN-00:15 480.81 27-DEC-06:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 27.37 0.00 01-JAN-14:00 2779.74 01-OCT-12:30
EnergyTransfer:Zone:F2 NE APARTMENT 19.96 0.01 25-DEC-13:00 2295.21 10-JUN-09:15
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.81 0.00 01-JAN-00:15 939.55 31-JAN-17:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 19.15 0.00 01-JAN-11:45 2295.21 10-JUN-09:15
EnergyTransfer:Zone:F2 N1 APARTMENT 15.38 0.22 14-MAR-14:30 1701.34 09-JUN-17:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.28 0.00 01-JAN-00:15 992.68 06-APR-14:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 15.10 0.00 01-JAN-14:00 1701.34 09-JUN-17:30
EnergyTransfer:Zone:F2 N2 APARTMENT 15.39 0.09 23-SEP-19:30 1691.87 09-JUN-17:30
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.29 0.00 01-JAN-00:15 958.26 06-APR-14:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 15.11 0.00 01-JAN-14:00 1691.87 09-JUN-17:30
EnergyTransfer:Zone:F2 S1 APARTMENT 22.24 0.03 06-OCT-12:15 1995.73 28-OCT-14:30
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.05 0.00 01-JAN-00:15 458.93 06-APR-14:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 22.18 0.00 02-JAN-16:30 1995.73 28-OCT-14:30
EnergyTransfer:Zone:F2 S2 APARTMENT 22.34 0.01 26-MAR-12:15 2009.52 28-OCT-14:30
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.05 0.00 01-JAN-00:15 431.33 06-APR-14:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 22.29 0.00 02-JAN-16:30 2009.52 28-OCT-14:30
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 27.78 0.06 16-JAN-20:45 3124.63 22-OCT-14:45
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.27 0.00 01-JAN-00:15 684.37 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 27.52 0.00 01-JAN-15:00 3124.63 22-OCT-14:45
EnergyTransfer:Zone:F3 NW APARTMENT 20.71 0.00 23-FEB-00:15 2906.97 09-JUN-17:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 0.86 0.00 01-JAN-00:15 1043.22 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 19.84 0.00 01-JAN-11:00 2906.97 09-JUN-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 28.26 0.69 19-MAR-16:45 2713.67 01-OCT-10:15
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.17 0.00 01-JAN-00:15 579.05 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 28.09 0.00 01-JAN-14:00 2713.67 01-OCT-10:15
EnergyTransfer:Zone:F3 NE APARTMENT 21.04 0.04 25-JAN-01:30 2350.01 10-JUN-09:15
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.69 0.00 01-JAN-00:15 1030.03 31-JAN-17:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 20.35 0.00 01-JAN-12:00 2350.01 10-JUN-09:15
EnergyTransfer:Zone:F3 N1 APARTMENT 16.66 0.03 23-SEP-19:45 1741.81 20-APR-18:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.23 0.00 01-JAN-00:15 1065.97 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 16.43 0.00 01-JAN-14:00 1741.81 20-APR-18:00
EnergyTransfer:Zone:F3 N2 APARTMENT 16.67 0.04 07-OCT-14:00 1740.25 20-APR-18:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.23 0.00 01-JAN-00:15 1046.64 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 16.44 0.00 01-JAN-14:00 1740.25 20-APR-18:00
EnergyTransfer:Zone:F3 S1 APARTMENT 24.34 0.02 09-DEC-16:30 2031.10 03-NOV-14:30
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.05 0.00 01-JAN-00:15 667.79 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 24.30 0.00 02-JAN-16:45 2031.10 03-NOV-14:30
EnergyTransfer:Zone:F3 S2 APARTMENT 24.38 0.04 14-OCT-10:30 2035.03 03-NOV-14:30
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.05 0.00 01-JAN-00:15 653.22 06-APR-14:00
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 24.33 0.00 02-JAN-16:45 2035.03 03-NOV-14:30
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 28.06 0.08 03-MAR-23:00 3132.08 22-OCT-14:45
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.27 0.00 01-JAN-00:15 707.34 10-APR-17:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 27.79 0.00 01-JAN-14:15 3132.08 22-OCT-14:45
EnergyTransfer:Zone:F4 NW APARTMENT 20.95 0.00 07-FEB-04:15 2914.82 09-JUN-17:30
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 0.85 0.00 01-JAN-00:15 1007.70 06-APR-14:15
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 20.10 0.00 01-JAN-11:00 2914.82 09-JUN-17:30
EnergyTransfer:Zone:F4 SE APARTMENT 28.40 0.01 22-APR-23:30 2717.80 01-OCT-10:15
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.18 0.00 01-JAN-00:15 787.07 10-APR-17:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 28.22 0.00 01-JAN-14:15 2717.80 01-OCT-10:15
EnergyTransfer:Zone:F4 NE APARTMENT 21.29 0.03 17-DEC-17:45 2357.91 10-JUN-09:15
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.67 0.00 01-JAN-00:15 1013.32 10-APR-17:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 20.62 0.00 01-JAN-12:00 2357.91 10-JUN-09:15
EnergyTransfer:Zone:F4 N1 APARTMENT 17.03 0.05 08-NOV-17:00 1786.02 09-MAY-20:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.22 0.00 01-JAN-00:15 1049.85 06-APR-14:15
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 16.82 0.00 01-JAN-14:15 1786.02 09-MAY-20:00
EnergyTransfer:Zone:F4 N2 APARTMENT 17.04 0.05 24-OCT-14:15 1780.77 09-MAY-20:00
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.22 0.00 01-JAN-00:15 1032.00 06-APR-14:15
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 16.82 0.00 01-JAN-14:15 1780.77 09-MAY-20:00
EnergyTransfer:Zone:F4 S1 APARTMENT 24.86 0.05 06-MAR-09:45 2050.42 03-NOV-14:30
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.05 0.00 01-JAN-00:15 773.17 10-APR-17:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 24.81 0.00 02-JAN-16:30 2050.42 03-NOV-14:30
EnergyTransfer:Zone:F4 S2 APARTMENT 24.88 0.02 23-SEP-19:30 2052.58 03-NOV-14:30
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.05 0.00 01-JAN-00:15 772.40 10-APR-17:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 24.82 0.00 02-JAN-16:30 2052.58 03-NOV-14:30
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 28.42 0.05 29-JUN-08:15 3163.81 22-OCT-14:45
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.29 0.00 01-JAN-00:15 1039.17 10-APR-17:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 28.13 0.00 01-JAN-14:15 3163.81 22-OCT-14:45
EnergyTransfer:Zone:M NW APARTMENT 21.40 0.00 28-NOV-13:30 2946.42 19-MAY-17:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.88 0.00 01-JAN-00:15 1258.31 10-APR-17:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 20.52 0.00 01-JAN-11:00 2946.42 19-MAY-17:30
EnergyTransfer:Zone:M SE APARTMENT 28.74 0.35 22-APR-22:30 2757.70 01-OCT-10:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.19 0.00 01-JAN-00:15 1110.00 10-APR-17:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 28.55 0.00 01-JAN-14:15 2757.70 01-OCT-10:15
EnergyTransfer:Zone:M NE APARTMENT 21.74 0.03 31-JAN-19:45 2390.40 10-JUN-09:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.69 0.00 01-JAN-00:15 1323.04 10-APR-17:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 21.05 0.00 01-JAN-12:00 2390.40 10-JUN-09:15
EnergyTransfer:Zone:M N1 APARTMENT 17.54 0.00 12-JUN-06:00 1859.36 09-MAY-20:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.23 0.00 01-JAN-00:15 1303.66 10-APR-17:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 17.31 0.00 01-JAN-14:15 1859.36 09-MAY-20:00
EnergyTransfer:Zone:M N2 APARTMENT 17.55 0.27 10-APR-08:45 1854.24 09-MAY-20:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.23 0.00 01-JAN-00:15 1302.28 10-APR-17:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 17.32 0.00 01-JAN-14:15 1854.24 09-MAY-20:00
EnergyTransfer:Zone:M S1 APARTMENT 25.38 0.01 08-SEP-06:00 2089.13 03-NOV-14:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.07 0.00 01-JAN-00:15 1068.62 10-APR-17:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 25.31 0.00 02-JAN-16:30 2089.13 03-NOV-14:30
EnergyTransfer:Zone:M S2 APARTMENT 25.39 0.06 25-MAR-11:15 2090.83 03-NOV-14:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.07 0.00 01-JAN-00:15 1067.53 10-APR-17:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 25.32 0.00 02-JAN-16:15 2090.83 03-NOV-14:30
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 27.30 0.13 13-FEB-12:45 3123.83 22-OCT-14:45
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.33 0.00 01-JAN-00:15 1403.25 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 26.96 0.00 01-JAN-14:15 3123.83 22-OCT-14:45
EnergyTransfer:Zone:F6 NW APARTMENT 20.80 0.00 23-DEC-10:45 2915.28 19-MAY-17:30
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 1.04 0.00 01-JAN-00:15 1613.64 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 19.76 0.00 01-JAN-11:00 2915.28 19-MAY-17:30
EnergyTransfer:Zone:F6 SE APARTMENT 27.60 0.05 29-NOV-17:00 2723.35 01-OCT-10:30
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.23 0.00 01-JAN-00:15 1467.76 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 27.38 0.00 01-JAN-14:15 2723.35 01-OCT-10:30
EnergyTransfer:Zone:F6 NE APARTMENT 21.11 0.02 22-JAN-14:45 2354.35 10-JUN-09:15
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.83 0.00 01-JAN-00:15 1667.72 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 20.28 0.00 01-JAN-12:00 2354.35 10-JUN-09:15
EnergyTransfer:Zone:F6 N1 APARTMENT 16.89 0.39 30-DEC-01:30 1860.26 09-MAY-20:00
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.28 0.00 01-JAN-00:15 1628.70 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 16.61 0.00 01-JAN-14:15 1860.26 09-MAY-20:00
EnergyTransfer:Zone:F6 N2 APARTMENT 16.89 0.17 25-SEP-08:30 1851.49 09-MAY-20:00
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.27 0.00 01-JAN-00:15 1626.91 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 16.62 0.00 01-JAN-14:15 1851.49 09-MAY-20:00
EnergyTransfer:Zone:F6 S1 APARTMENT 24.28 0.12 21-APR-06:45 2054.81 03-NOV-14:30
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.08 0.00 01-JAN-00:15 1407.77 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 24.20 0.00 02-JAN-16:00 2054.81 03-NOV-14:30
EnergyTransfer:Zone:F6 S2 APARTMENT 24.29 0.01 26-MAR-12:00 2058.77 03-NOV-14:30
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.08 0.00 01-JAN-00:15 1406.44 10-APR-17:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 24.21 0.00 02-JAN-16:00 2058.77 03-NOV-14:30
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 26.68 0.08 26-FEB-00:45 3109.86 22-OCT-14:45
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.37 0.00 01-JAN-00:15 1700.50 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 26.31 0.00 01-JAN-14:15 3109.86 22-OCT-14:45
EnergyTransfer:Zone:F7 NW APARTMENT 20.60 0.00 30-NOV-20:30 2908.12 19-MAY-17:30
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 1.19 0.00 01-JAN-00:15 1901.28 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 19.41 0.00 01-JAN-10:45 2908.12 19-MAY-17:30
EnergyTransfer:Zone:F7 SE APARTMENT 26.98 0.11 29-NOV-16:45 2717.26 01-OCT-10:30
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.26 0.00 01-JAN-00:15 1757.22 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 26.72 0.00 01-JAN-14:15 2717.26 01-OCT-10:30
EnergyTransfer:Zone:F7 NE APARTMENT 20.89 0.06 13-NOV-20:45 2344.10 10-JUN-09:15
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 0.98 0.00 01-JAN-00:15 1949.08 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 19.91 0.00 01-JAN-12:00 2344.10 10-JUN-09:15
EnergyTransfer:Zone:F7 N1 APARTMENT 16.61 0.13 30-DEC-06:45 1893.92 10-APR-17:00
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.33 0.00 01-JAN-00:15 1893.92 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 16.28 0.00 01-JAN-14:15 1853.38 09-MAY-20:00
EnergyTransfer:Zone:F7 N2 APARTMENT 16.61 0.11 26-APR-08:15 1891.83 10-APR-17:00
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.33 0.00 01-JAN-00:15 1891.83 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 16.28 0.00 01-JAN-14:15 1844.71 09-MAY-20:00
EnergyTransfer:Zone:F7 S1 APARTMENT 23.69 0.01 13-OCT-09:45 2045.35 03-NOV-14:30
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.09 0.00 01-JAN-00:15 1680.95 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 23.60 0.00 01-JAN-15:15 2045.35 03-NOV-14:30
EnergyTransfer:Zone:F7 S2 APARTMENT 23.70 0.18 10-FEB-15:45 2049.27 03-NOV-14:30
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.09 0.00 01-JAN-00:15 1679.40 10-APR-17:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 23.61 0.00 01-JAN-15:00 2049.27 03-NOV-14:30
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 26.25 0.02 13-FEB-10:00 3110.89 22-OCT-14:45
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.42 0.00 01-JAN-00:15 1957.45 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 25.83 0.00 01-JAN-14:15 3110.89 22-OCT-14:45
EnergyTransfer:Zone:F8 NW APARTMENT 20.60 0.01 26-OCT-03:30 2912.09 19-MAY-17:30
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 1.37 0.00 01-JAN-00:15 2151.88 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 19.24 0.00 01-JAN-10:45 2912.09 19-MAY-17:30
EnergyTransfer:Zone:F8 SE APARTMENT 26.55 0.03 04-MAR-01:00 2724.34 01-OCT-10:30
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.31 0.00 01-JAN-00:15 2008.06 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 26.25 0.00 01-JAN-14:15 2724.34 01-OCT-10:30
EnergyTransfer:Zone:F8 NE APARTMENT 20.86 0.00 20-NOV-10:45 2348.10 10-JUN-09:15
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 1.14 0.00 01-JAN-00:15 2194.11 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 19.72 0.00 01-JAN-11:45 2348.10 10-JUN-09:15
EnergyTransfer:Zone:F8 N1 APARTMENT 16.50 0.06 23-SEP-20:45 2124.94 10-APR-17:00
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.39 0.00 01-JAN-00:15 2124.94 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 16.11 0.00 01-JAN-14:15 1861.09 09-MAY-20:00
EnergyTransfer:Zone:F8 N2 APARTMENT 16.51 0.41 06-OCT-11:30 2122.52 10-APR-17:00
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.39 0.00 01-JAN-00:15 2122.52 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 16.12 0.00 01-JAN-14:15 1852.54 09-MAY-20:00
EnergyTransfer:Zone:F8 S1 APARTMENT 23.26 0.14 09-OCT-05:45 2049.26 03-NOV-14:30
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.11 0.00 01-JAN-00:15 1918.24 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 23.15 0.00 01-JAN-15:00 2049.26 03-NOV-14:30
EnergyTransfer:Zone:F8 S2 APARTMENT 23.27 0.14 20-FEB-20:15 2053.15 03-NOV-14:30
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.11 0.00 01-JAN-00:15 1916.40 10-APR-17:00
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 23.16 0.00 01-JAN-15:00 2053.15 03-NOV-14:30
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 26.05 0.00 28-FEB-19:30 3207.35 22-OCT-15:15
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.55 0.00 01-JAN-00:15 2169.49 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 25.50 0.00 01-JAN-14:15 3207.35 22-OCT-15:15
EnergyTransfer:Zone:F9 NW APARTMENT 21.18 0.01 20-DEC-19:45 2985.56 27-JUN-17:30
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 1.75 0.00 01-JAN-00:15 2363.98 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 19.43 0.00 01-JAN-10:15 2985.56 27-JUN-17:30
EnergyTransfer:Zone:F9 SE APARTMENT 26.34 0.01 04-MAR-04:00 2772.26 29-SEP-12:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.41 0.00 01-JAN-00:15 2214.88 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 25.92 0.00 01-JAN-14:15 2772.26 29-SEP-12:00
EnergyTransfer:Zone:F9 NE APARTMENT 21.36 0.01 19-MAR-19:00 2442.19 10-JUN-09:15
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 1.46 0.00 01-JAN-00:15 2400.55 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 19.90 0.00 01-JAN-04:00 2442.19 10-JUN-09:15
EnergyTransfer:Zone:F9 N1 APARTMENT 16.73 0.05 21-MAR-22:00 2322.92 10-APR-17:00
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.54 0.00 01-JAN-00:15 2322.92 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 16.19 0.00 01-JAN-14:15 1947.34 09-MAY-20:00
EnergyTransfer:Zone:F9 N2 APARTMENT 16.74 0.17 29-OCT-18:30 2319.96 10-APR-17:00
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.55 0.00 01-JAN-00:15 2319.96 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 16.20 0.00 01-JAN-14:15 1938.82 09-MAY-20:00
EnergyTransfer:Zone:F9 S1 APARTMENT 22.93 0.06 27-OCT-21:00 2118.07 10-APR-17:00
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.14 0.00 01-JAN-00:15 2118.07 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 22.79 0.00 01-JAN-14:15 2108.07 03-NOV-14:30
EnergyTransfer:Zone:F9 S2 APARTMENT 22.95 0.16 03-FEB-15:30 2115.72 10-APR-17:00
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.14 0.00 01-JAN-00:15 2115.72 10-APR-17:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 22.80 0.00 01-JAN-14:15 2105.44 03-NOV-14:30
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 28.30 0.01 31-JAN-09:45 3865.88 22-OCT-15:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 2.42 0.00 01-JAN-06:45 3115.91 10-APR-17:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 25.87 0.00 01-JAN-00:15 3865.88 22-OCT-15:15
EnergyTransfer:Zone:T NW APARTMENT 24.66 0.05 05-DEC-11:30 3650.52 27-JUN-17:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 4.43 0.00 02-JAN-23:45 3225.40 10-APR-17:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 20.23 0.00 01-JAN-00:15 3650.52 27-JUN-17:15
EnergyTransfer:Zone:T SE APARTMENT 28.03 0.01 11-FEB-24:00 3422.93 01-OCT-11:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 2.13 0.00 01-JAN-00:15 3217.25 10-APR-17:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 25.91 0.00 01-JAN-02:30 3422.93 01-OCT-11:15
EnergyTransfer:Zone:T NE APARTMENT 24.05 0.01 19-FEB-03:00 3321.25 10-APR-17:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 3.82 0.00 01-JAN-08:45 3321.25 10-APR-17:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 20.23 0.00 01-JAN-00:15 2954.87 05-JUN-17:00
EnergyTransfer:Zone:T N1 APARTMENT 18.07 0.01 10-DEC-01:00 3141.35 10-APR-17:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 1.80 0.00 01-JAN-00:15 3141.35 10-APR-17:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 16.27 0.00 01-JAN-03:30 2343.60 17-JUN-18:15
EnergyTransfer:Zone:T N2 APARTMENT 18.09 0.00 03-JAN-21:00 3143.05 10-APR-17:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 1.81 0.00 01-JAN-00:15 3143.05 10-APR-17:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 16.28 0.00 01-JAN-03:30 2338.36 17-JUN-18:15
EnergyTransfer:Zone:T S1 APARTMENT 23.10 0.03 15-OCT-04:15 3023.03 10-APR-17:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.68 0.00 01-JAN-00:15 3023.03 10-APR-17:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 22.42 0.00 01-JAN-14:30 2795.84 22-OCT-13:15
EnergyTransfer:Zone:T S2 APARTMENT 23.12 0.01 11-DEC-16:15 3025.13 10-APR-17:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.68 0.00 01-JAN-00:15 3025.13 10-APR-17:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 22.44 0.00 01-JAN-14:30 2799.63 22-OCT-13:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 771.01 391.07 31-JUL-01:15 101089.11 27-DEC-06:15
WaterSystems:EnergyTransfer 755.19 391.07 31-JUL-01:15 53289.12 30-JAN-07:15
sub cat:WaterSystems:EnergyTransfer 755.19 391.07 31-JUL-01:15 53289.12 30-JAN-07:15
EnergyTransfer:HVAC 2132.17 0.00 16-JAN-10:45 241632.72 20-JUL-16:15
CoolingCoils:EnergyTransfer 2079.91 0.00 01-JAN-00:45 241632.72 20-JUL-16:15
HeatingCoils:EnergyTransfer 52.25 0.00 01-JAN-09:30 103009.80 10-APR-17:00
PlantLoopHeatingDemand:HVAC 40.23 0.00 01-JAN-09:30 78856.25 10-APR-17:00
HeatingCoils:PlantLoopHeatingDemand 40.23 0.00 01-JAN-09:30 78856.25 10-APR-17:00
Boilers:EnergyTransfer 15.81 0.00 01-JAN-00:15 51067.35 27-DEC-06:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.600 -15.921 0.000 0.000 3.680 2.413 12.213 23.120 0.000 0.477 0.000 0.000 -7.543 0.000 -4.631 -14.408
G NW APARTMENT 1.604 -12.122 0.000 0.000 3.737 2.413 12.213 13.098 0.000 0.473 0.000 0.000 -7.532 0.000 -4.040 -9.844
OFFICE 0.481 -22.313 0.000 0.000 0.506 21.954 7.547 23.160 0.000 0.324 0.000 0.000 -7.401 0.000 -1.443 -22.814
G NE APARTMENT 1.377 -12.377 0.000 0.000 3.751 2.413 12.213 12.975 0.000 0.472 0.000 0.000 -7.125 0.000 -4.014 -9.686
G N1 APARTMENT 0.618 -9.465 0.000 0.000 3.754 2.413 12.213 4.680 0.000 0.345 0.000 0.000 -4.583 0.000 -3.237 -6.736
G N2 APARTMENT 0.619 -9.475 0.000 0.000 3.755 2.413 12.213 4.677 0.000 0.345 0.000 0.000 -4.579 0.000 -3.237 -6.731
G S1 APARTMENT 0.067 -13.550 0.000 0.000 3.676 2.413 12.213 14.848 0.000 0.346 0.000 0.000 -4.568 0.000 -3.918 -11.527
G S2 APARTMENT 0.071 -13.749 0.000 0.000 3.673 2.413 12.213 14.836 0.000 0.347 0.000 0.000 -4.575 0.000 -3.945 -11.283
F2 SW APARTMENT 0.292 -25.863 0.000 0.000 3.592 2.413 12.213 22.134 0.000 0.647 0.000 0.000 -8.258 0.000 -6.043 -1.127
F2 NW APARTMENT 1.016 -18.663 0.000 0.000 3.673 2.413 12.213 12.419 0.000 0.641 0.000 0.000 -8.182 0.000 -5.415 -0.115
F2 SE APARTMENT 0.195 -27.367 0.000 0.000 3.593 2.413 12.213 22.189 0.000 0.646 0.275 0.000 -8.071 0.000 -6.086 -0.000
F2 NE APARTMENT 0.814 -19.147 0.000 0.000 3.689 2.413 12.213 12.317 0.000 0.640 0.148 0.000 -7.717 0.000 -5.369 -0.000
F2 N1 APARTMENT 0.284 -15.098 0.000 0.000 3.680 2.413 12.213 4.341 0.000 0.457 1.133 0.000 -5.050 0.000 -4.373 -0.000
F2 N2 APARTMENT 0.285 -15.108 0.000 0.000 3.681 2.413 12.213 4.340 0.000 0.457 1.136 0.000 -5.045 0.000 -4.372 -0.000
F2 S1 APARTMENT 0.051 -22.184 0.000 0.000 3.576 2.413 12.213 14.227 0.000 0.459 0.001 0.000 -5.010 0.000 -5.121 -0.623
F2 S2 APARTMENT 0.052 -22.291 0.000 0.000 3.576 2.413 12.213 14.224 0.000 0.459 0.000 0.000 -5.012 0.000 -5.128 -0.506
F3 SW APARTMENT 0.265 -27.517 0.000 0.000 3.579 2.413 12.213 21.720 0.000 0.786 1.696 0.000 -8.419 0.000 -6.736 -0.000
F3 NW APARTMENT 0.865 -19.840 0.000 0.000 3.657 2.413 12.213 12.158 0.000 0.779 2.238 0.000 -8.376 0.000 -6.107 -0.000
F3 SE APARTMENT 0.170 -28.085 0.000 0.000 3.586 2.413 12.213 21.831 0.000 0.783 2.015 0.000 -8.188 0.000 -6.737 -0.000
F3 NE APARTMENT 0.692 -20.351 0.000 0.000 3.674 2.413 12.213 12.072 0.000 0.776 2.465 0.000 -7.897 0.000 -6.057 -0.000
F3 N1 APARTMENT 0.233 -16.432 0.000 0.000 3.656 2.413 12.213 4.237 0.000 0.560 3.267 0.000 -5.205 0.000 -4.943 0.000
F3 N2 APARTMENT 0.232 -16.439 0.000 0.000 3.658 2.413 12.213 4.236 0.000 0.560 3.268 0.000 -5.199 0.000 -4.941 0.000
F3 S1 APARTMENT 0.048 -24.296 0.000 0.000 3.558 2.413 12.213 13.966 0.000 0.561 2.331 0.000 -5.121 0.000 -5.672 -0.000
F3 S2 APARTMENT 0.048 -24.328 0.000 0.000 3.559 2.413 12.213 13.964 0.000 0.561 2.365 0.000 -5.120 0.000 -5.675 -0.000
F4 SW APARTMENT 0.269 -27.790 0.000 0.000 3.577 2.413 12.213 21.454 0.000 0.862 2.522 0.000 -8.481 0.000 -7.039 -0.000
F4 NW APARTMENT 0.853 -20.097 0.000 0.000 3.653 2.413 12.213 12.001 0.000 0.854 3.000 0.000 -8.466 0.000 -6.424 -0.000
F4 SE APARTMENT 0.176 -28.221 0.000 0.000 3.585 2.413 12.213 21.584 0.000 0.859 2.671 0.000 -8.242 0.000 -7.039 -0.001
F4 NE APARTMENT 0.673 -20.620 0.000 0.000 3.669 2.413 12.213 11.925 0.000 0.851 3.230 0.000 -7.979 0.000 -6.376 -0.000
F4 N1 APARTMENT 0.218 -16.815 0.000 0.000 3.647 2.413 12.213 4.181 0.000 0.611 3.977 0.000 -5.280 0.000 -5.165 0.000
F4 N2 APARTMENT 0.216 -16.821 0.000 0.000 3.649 2.413 12.213 4.180 0.000 0.611 3.978 0.000 -5.275 0.000 -5.163 0.000
F4 S1 APARTMENT 0.054 -24.810 0.000 0.000 3.555 2.413 12.213 13.798 0.000 0.612 3.193 0.000 -5.165 0.000 -5.864 -0.000
F4 S2 APARTMENT 0.055 -24.821 0.000 0.000 3.555 2.413 12.213 13.797 0.000 0.612 3.205 0.000 -5.163 0.000 -5.865 -0.000
M SW APARTMENT 0.291 -28.130 0.000 0.000 3.577 2.413 12.213 21.240 0.000 0.923 3.459 0.000 -8.533 0.000 -7.452 -0.000
M NW APARTMENT 0.879 -20.520 0.000 0.000 3.651 2.413 12.213 11.876 0.000 0.914 3.918 0.000 -8.533 0.000 -6.813 -0.000
M SE APARTMENT 0.193 -28.549 0.000 0.000 3.585 2.413 12.213 21.381 0.000 0.920 3.585 0.000 -8.291 0.000 -7.450 -0.000
M NE APARTMENT 0.691 -21.052 0.000 0.000 3.667 2.413 12.213 11.806 0.000 0.911 4.153 0.000 -8.040 0.000 -6.763 0.000
M N1 APARTMENT 0.233 -17.311 0.000 0.000 3.643 2.413 12.213 4.136 0.000 0.651 4.826 0.000 -5.334 0.000 -5.469 0.000
M N2 APARTMENT 0.232 -17.319 0.000 0.000 3.644 2.413 12.213 4.135 0.000 0.651 4.826 0.000 -5.328 0.000 -5.467 0.000
M S1 APARTMENT 0.065 -25.312 0.000 0.000 3.554 2.413 12.213 13.664 0.000 0.652 4.131 0.000 -5.200 0.000 -6.180 -0.000
M S2 APARTMENT 0.066 -25.319 0.000 0.000 3.554 2.413 12.213 13.663 0.000 0.652 4.138 0.000 -5.198 0.000 -6.181 -0.000
F6 SW APARTMENT 0.333 -26.963 0.000 0.000 3.585 2.413 12.213 21.105 0.000 0.974 2.615 0.000 -8.513 0.000 -7.762 -0.000
F6 NW APARTMENT 1.036 -19.764 0.000 0.000 3.662 2.413 12.213 11.820 0.000 0.964 3.216 0.000 -8.502 0.000 -7.058 -0.000
F6 SE APARTMENT 0.227 -27.376 0.000 0.000 3.593 2.413 12.213 21.255 0.000 0.971 2.736 0.000 -8.269 0.000 -7.762 -0.000
F6 NE APARTMENT 0.834 -20.276 0.000 0.000 3.678 2.413 12.213 11.757 0.000 0.961 3.437 0.000 -8.008 0.000 -7.009 0.000
F6 N1 APARTMENT 0.277 -16.609 0.000 0.000 3.655 2.413 12.213 4.126 0.000 0.684 4.191 0.000 -5.314 0.000 -5.635 0.000
F6 N2 APARTMENT 0.275 -16.615 0.000 0.000 3.656 2.413 12.213 4.124 0.000 0.684 4.192 0.000 -5.308 0.000 -5.634 0.000
F6 S1 APARTMENT 0.078 -24.200 0.000 0.000 3.560 2.413 12.213 13.578 0.000 0.686 3.272 0.000 -5.191 0.000 -6.409 -0.000
F6 S2 APARTMENT 0.078 -24.210 0.000 0.000 3.561 2.413 12.213 13.577 0.000 0.686 3.282 0.000 -5.189 0.000 -6.410 -0.000
F7 SW APARTMENT 0.373 -26.307 0.000 0.000 3.591 2.413 12.213 20.980 0.000 1.018 2.244 0.000 -8.505 0.000 -8.020 -0.000
F7 NW APARTMENT 1.191 -19.406 0.000 0.000 3.671 2.413 12.213 11.763 0.000 1.007 2.906 0.000 -8.487 0.000 -7.271 -0.000
F7 SE APARTMENT 0.263 -26.720 0.000 0.000 3.599 2.413 12.213 21.136 0.000 1.015 2.364 0.000 -8.261 0.000 -8.022 -0.000
F7 NE APARTMENT 0.978 -19.910 0.000 0.000 3.686 2.413 12.213 11.705 0.000 1.003 3.126 0.000 -7.992 0.000 -7.222 0.000
F7 N1 APARTMENT 0.328 -16.277 0.000 0.000 3.664 2.413 12.213 4.112 0.000 0.712 3.914 0.000 -5.301 0.000 -5.777 0.000
F7 N2 APARTMENT 0.326 -16.284 0.000 0.000 3.665 2.413 12.213 4.110 0.000 0.712 3.916 0.000 -5.296 0.000 -5.775 0.000
F7 S1 APARTMENT 0.091 -23.597 0.000 0.000 3.566 2.413 12.213 13.498 0.000 0.715 2.885 0.000 -5.189 0.000 -6.595 -0.000
F7 S2 APARTMENT 0.091 -23.607 0.000 0.000 3.566 2.413 12.213 13.497 0.000 0.715 2.895 0.000 -5.187 0.000 -6.597 -0.000
F8 SW APARTMENT 0.423 -25.829 0.000 0.000 3.598 2.413 12.213 20.870 0.000 1.066 2.018 0.000 -8.498 0.000 -8.274 -0.000
F8 NW APARTMENT 1.367 -19.235 0.000 0.000 3.678 2.413 12.213 11.711 0.000 1.055 2.760 0.000 -8.476 0.000 -7.485 -0.000
F8 SE APARTMENT 0.308 -26.245 0.000 0.000 3.606 2.413 12.213 21.030 0.000 1.063 2.143 0.000 -8.253 0.000 -8.277 -0.000
F8 NE APARTMENT 1.138 -19.724 0.000 0.000 3.693 2.413 12.213 11.656 0.000 1.050 2.978 0.000 -7.980 0.000 -7.435 0.000
F8 N1 APARTMENT 0.391 -16.106 0.000 0.000 3.672 2.413 12.213 4.097 0.000 0.746 3.790 0.000 -5.290 0.000 -5.926 0.000
F8 N2 APARTMENT 0.392 -16.117 0.000 0.000 3.674 2.413 12.213 4.096 0.000 0.746 3.792 0.000 -5.285 0.000 -5.924 0.000
F8 S1 APARTMENT 0.106 -23.150 0.000 0.000 3.571 2.413 12.213 13.429 0.000 0.750 2.638 0.000 -5.186 0.000 -6.784 -0.000
F8 S2 APARTMENT 0.107 -23.162 0.000 0.000 3.572 2.413 12.213 13.427 0.000 0.750 2.650 0.000 -5.184 0.000 -6.786 -0.001
F9 SW APARTMENT 0.548 -25.500 0.000 0.000 3.608 2.413 12.213 20.789 0.000 1.108 1.758 0.000 -8.467 0.000 -8.469 -0.000
F9 NW APARTMENT 1.746 -19.433 0.000 0.000 3.685 2.413 12.213 11.669 0.000 1.095 2.725 0.000 -8.456 0.000 -7.657 -0.000
F9 SE APARTMENT 0.413 -25.923 0.000 0.000 3.616 2.413 12.213 20.949 0.000 1.105 1.912 0.000 -8.222 0.000 -8.476 -0.000
F9 NE APARTMENT 1.461 -19.896 0.000 0.000 3.700 2.413 12.213 11.618 0.000 1.092 2.972 0.000 -7.961 0.000 -7.612 -0.000
F9 N1 APARTMENT 0.542 -16.186 0.000 0.000 3.682 2.413 12.213 4.086 0.000 0.775 3.778 0.000 -5.267 0.000 -6.036 0.000
F9 N2 APARTMENT 0.545 -16.198 0.000 0.000 3.684 2.413 12.213 4.084 0.000 0.775 3.782 0.000 -5.262 0.000 -6.036 -0.000
F9 S1 APARTMENT 0.141 -22.788 0.000 0.000 3.583 2.413 12.213 13.377 0.000 0.781 2.363 0.000 -5.165 0.000 -6.919 -0.000
F9 S2 APARTMENT 0.142 -22.804 0.000 0.000 3.584 2.413 12.213 13.376 0.000 0.781 2.380 0.000 -5.163 0.000 -6.922 -0.000
T SW APARTMENT 2.422 -25.873 0.000 0.000 3.661 2.413 12.213 20.472 0.000 1.138 0.076 0.000 -7.991 0.000 -8.531 -0.000
T NW APARTMENT 4.433 -20.227 0.000 0.000 3.707 2.413 12.213 11.384 0.000 1.125 0.893 0.000 -8.086 0.000 -7.854 -0.001
T SE APARTMENT 2.126 -25.907 0.000 0.000 3.668 2.413 12.213 20.645 0.000 1.137 0.030 0.000 -7.772 0.000 -8.553 -0.000
T NE APARTMENT 3.822 -20.230 0.000 0.000 3.722 2.413 12.213 11.389 0.000 1.125 1.013 0.000 -7.651 0.000 -7.816 -0.000
T N1 APARTMENT 1.803 -16.268 0.000 0.000 3.710 2.413 12.213 3.996 0.000 0.797 2.495 0.000 -5.022 0.000 -6.137 -0.000
T N2 APARTMENT 1.812 -16.278 0.000 0.000 3.711 2.413 12.213 3.991 0.000 0.797 2.496 0.000 -5.015 0.000 -6.140 -0.000
T S1 APARTMENT 0.682 -22.416 0.000 0.000 3.643 2.413 12.213 13.218 0.000 0.809 1.279 0.000 -4.903 0.000 -6.938 -0.000
T S2 APARTMENT 0.685 -22.435 0.000 0.000 3.643 2.413 12.213 13.214 0.000 0.809 1.301 0.000 -4.900 0.000 -6.943 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 5.481 0.000 3.855 0.001 0.000 -1.815 0.000 -21.481 -4.570
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.517 0.000 0.046 0.000 0.000 -1.067 0.000 -0.418 -19.607
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.452 0.000 0.052 0.000 0.000 -1.107 0.000 -0.514 -19.413
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.411 0.000 0.056 0.000 0.000 -1.128 0.000 -0.584 -19.285
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 2.366 0.000 0.051 0.000 0.000 -1.159 0.000 -0.675 -37.642
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.372 0.000 0.065 0.000 0.000 -1.134 0.000 -0.677 -19.155
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.365 0.000 0.070 0.000 0.000 -1.125 0.000 -0.707 -19.133
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.355 0.000 0.073 0.000 0.000 -1.122 0.000 -0.737 -19.098
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.345 0.000 0.073 0.000 0.000 -1.120 0.000 -0.762 -19.065
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 2.274 0.000 0.047 0.000 0.000 -1.088 0.000 -0.816 -26.883
Total Facility 50.477 -1671.540 0.000 0.000 287.913 416.414 980.287 1054.244 0.000 65.420 186.366 0.000 -542.117 0.000 -528.212 -299.260


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-SEP-15:15 0.00 -2528.74 0.00 0.00 48.64 100.83 470.89 3485.61 0.00 16.16 0.00 0.00 0.00 0.00 0.00 -1593.38
G NW APARTMENT 12-JUN-17:30 0.00 -2374.22 0.00 0.00 141.38 194.45 588.62 2752.36 0.00 65.37 0.00 0.00 0.00 0.00 0.00 -1367.96
OFFICE 29-SEP-13:30 0.00 -3133.26 0.00 0.00 65.20 1622.33 544.91 2666.66 0.00 25.80 0.00 0.00 0.00 0.00 0.00 -1791.63
G NE APARTMENT 17-JUN-18:15 0.00 -1768.15 0.00 0.00 140.92 230.46 547.42 931.11 0.00 112.77 0.00 0.00 0.00 0.00 0.00 -194.54
G N1 APARTMENT 09-JUN-17:20 0.00 -1330.13 0.00 0.00 141.81 194.45 588.62 819.39 0.00 65.25 0.00 0.00 0.00 0.00 0.00 -479.39
G N2 APARTMENT 09-JUN-17:20 0.00 -1318.36 0.00 0.00 141.81 194.45 588.62 819.68 0.00 65.25 0.00 0.00 0.00 0.00 0.00 -491.46
G S1 APARTMENT 30-SEP-11:15 0.00 -1533.89 0.00 0.00 40.29 28.81 406.15 2659.85 0.00 31.95 0.00 0.00 0.00 0.00 0.00 -1633.16
G S2 APARTMENT 30-SEP-11:15 0.00 -1582.26 0.00 0.00 40.39 28.81 406.15 2659.90 0.00 35.00 0.00 0.00 0.00 0.00 0.00 -1587.99
F2 SW APARTMENT 29-SEP-15:15 0.00 -3104.13 0.00 0.00 48.85 100.83 470.89 3432.11 0.00 23.54 0.00 0.00 0.00 0.00 0.00 -972.10
F2 NW APARTMENT 17-JUN-17:30 0.00 -2907.12 0.00 0.00 139.45 194.45 588.62 2627.63 0.00 122.09 0.00 0.00 0.00 0.00 0.00 -765.12
F2 SE APARTMENT 01-OCT-12:30 0.00 -2779.56 0.00 0.00 40.74 28.81 388.49 3046.12 0.00 32.98 0.00 0.00 0.00 0.00 0.00 -757.57
F2 NE APARTMENT 10-JUN-09:15 0.00 -2295.20 0.00 0.00 40.75 28.81 406.15 1890.17 0.00 325.47 0.00 0.00 0.00 0.00 0.00 -396.14
F2 N1 APARTMENT 09-JUN-17:20 0.00 -1705.04 0.00 0.00 141.81 194.45 588.62 794.51 0.00 93.62 0.00 0.00 0.00 0.00 0.00 -107.98
F2 N2 APARTMENT 09-JUN-17:20 0.00 -1695.52 0.00 0.00 141.81 194.45 588.62 794.66 0.00 93.62 0.00 0.00 0.00 0.00 0.00 -117.64
F2 S1 APARTMENT 28-OCT-14:30 0.00 -1995.67 0.00 0.00 40.53 50.41 400.26 2212.94 0.00 0.00 0.00 0.00 0.00 0.00 -107.06 -601.41
F2 S2 APARTMENT 28-OCT-14:30 0.00 -2009.45 0.00 0.00 40.56 50.41 400.26 2213.01 0.00 0.00 0.00 0.00 0.00 0.00 -105.76 -589.02
F3 SW APARTMENT 22-OCT-14:45 0.00 -3124.47 0.00 0.00 40.70 50.41 400.26 3391.38 0.00 186.90 0.00 0.00 0.00 0.00 0.00 -945.18
F3 NW APARTMENT 09-JUN-17:30 0.00 -2907.21 0.00 0.00 141.81 194.45 588.62 2366.61 0.00 183.38 0.00 0.00 0.00 0.00 0.00 -567.65
F3 SE APARTMENT 01-OCT-10:15 0.00 -2713.99 0.00 0.00 40.75 28.81 412.03 3482.51 0.00 35.98 0.00 0.00 0.00 0.00 0.00 -1286.09
F3 NE APARTMENT 10-JUN-09:15 0.00 -2350.04 0.00 0.00 40.75 28.81 406.15 1858.55 0.00 367.17 0.00 0.00 0.00 0.00 0.00 -351.38
F3 N1 APARTMENT 20-APR-18:00 0.00 -1740.07 0.00 0.00 141.81 194.45 588.62 89.19 0.00 625.37 100.64 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 20-APR-18:00 0.00 -1738.51 0.00 0.00 141.81 194.45 588.62 89.22 0.00 625.37 99.04 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 03-NOV-14:30 0.00 -2031.06 0.00 0.00 40.25 50.41 400.26 2342.02 0.00 0.00 0.00 0.00 0.00 0.00 -107.44 -694.44
F3 S2 APARTMENT 03-NOV-14:30 0.00 -2035.00 0.00 0.00 40.26 50.41 400.26 2342.08 0.00 0.00 0.00 0.00 0.00 0.00 -106.87 -691.14
F4 SW APARTMENT 22-OCT-14:45 0.00 -3131.92 0.00 0.00 40.67 50.41 400.26 3377.55 0.00 186.97 0.00 0.00 0.00 0.00 0.00 -923.95
F4 NW APARTMENT 09-JUN-17:30 0.00 -2915.07 0.00 0.00 141.81 194.45 588.62 2337.43 0.00 204.47 0.00 0.00 0.00 0.00 0.00 -551.70
F4 SE APARTMENT 01-OCT-10:15 0.00 -2718.13 0.00 0.00 40.75 28.81 412.03 3481.38 0.00 34.45 0.00 0.00 0.00 0.00 0.00 -1279.29
F4 NE APARTMENT 10-JUN-09:15 0.00 -2357.97 0.00 0.00 40.75 28.81 406.15 1836.71 0.00 395.78 0.00 0.00 0.00 0.00 0.00 -350.23
F4 N1 APARTMENT 09-MAY-20:00 0.00 -1783.18 0.00 0.00 141.81 230.46 523.87 0.00 0.00 593.60 309.52 0.00 -16.08 0.00 0.00 0.00
F4 N2 APARTMENT 09-MAY-20:00 0.00 -1777.94 0.00 0.00 141.81 230.46 523.87 0.00 0.00 593.60 304.13 0.00 -15.93 0.00 0.00 0.00
F4 S1 APARTMENT 10-NOV-14:55 0.00 -2088.71 0.00 0.00 42.18 28.81 382.60 1577.14 0.00 0.00 207.70 0.00 0.00 0.00 -149.72 0.00
F4 S2 APARTMENT 10-NOV-14:55 0.00 -2085.74 0.00 0.00 42.18 28.81 382.60 1577.14 0.00 0.00 204.73 0.00 0.00 0.00 -149.72 0.00
M SW APARTMENT 22-OCT-14:45 0.00 -3163.65 0.00 0.00 40.68 50.41 400.26 3365.77 0.00 188.50 0.00 0.00 0.00 0.00 0.00 -881.98
M NW APARTMENT 19-MAY-17:30 0.00 -2946.48 0.00 0.00 141.81 194.45 588.62 2197.58 0.00 306.85 0.00 0.00 0.00 0.00 0.00 -482.83
M SE APARTMENT 01-OCT-10:15 0.00 -2758.06 0.00 0.00 40.75 28.81 412.03 3479.73 0.00 33.49 0.00 0.00 0.00 0.00 0.00 -1236.76
M NE APARTMENT 10-JUN-09:15 0.00 -2390.48 0.00 0.00 40.75 28.81 406.15 1818.91 0.00 418.68 0.00 0.00 0.00 0.00 0.00 -322.81
M N1 APARTMENT 09-MAY-20:00 0.00 -1856.33 0.00 0.00 141.81 230.46 523.87 0.00 0.00 634.85 341.03 0.00 -15.70 0.00 0.00 0.00
M N2 APARTMENT 09-MAY-20:00 0.00 -1851.20 0.00 0.00 141.81 230.46 523.87 0.00 0.00 634.85 335.76 0.00 -15.55 0.00 0.00 0.00
M S1 APARTMENT 10-NOV-14:55 0.00 -2161.09 0.00 0.00 42.49 28.81 382.60 1560.23 0.00 0.00 309.98 0.00 0.00 0.00 -163.03 0.00
M S2 APARTMENT 10-NOV-14:55 0.00 -2158.17 0.00 0.00 42.50 28.81 382.60 1560.23 0.00 0.00 307.07 0.00 0.00 0.00 -163.03 0.00
F6 SW APARTMENT 22-OCT-14:45 0.00 -3123.68 0.00 0.00 40.69 50.41 400.26 3357.29 0.00 189.51 0.00 0.00 0.00 0.00 0.00 -914.49
F6 NW APARTMENT 19-MAY-17:30 0.00 -2915.32 0.00 0.00 141.81 194.45 588.62 2180.35 0.00 327.19 0.00 0.00 0.00 0.00 0.00 -517.10
F6 SE APARTMENT 01-OCT-10:30 0.00 -2723.17 0.00 0.00 40.75 28.81 412.03 3429.85 0.00 96.99 0.00 0.00 0.00 0.00 0.00 -1285.26
F6 NE APARTMENT 10-JUN-09:15 0.00 -2354.45 0.00 0.00 40.75 28.81 406.15 1806.18 0.00 437.15 0.00 0.00 0.00 0.00 0.00 -364.58
F6 N1 APARTMENT 09-MAY-20:00 0.00 -1857.13 0.00 0.00 141.81 230.46 523.87 0.00 0.00 668.88 306.12 0.00 -14.01 0.00 0.00 0.00
F6 N2 APARTMENT 09-MAY-20:00 0.00 -1848.37 0.00 0.00 141.81 230.46 523.87 0.00 0.00 668.10 298.00 0.00 -13.87 0.00 0.00 0.00
F6 S1 APARTMENT 10-NOV-14:55 0.00 -2167.15 0.00 0.00 42.96 28.81 382.60 1549.04 0.00 0.00 338.71 0.00 0.00 0.00 -174.96 0.00
F6 S2 APARTMENT 10-NOV-14:55 0.00 -2171.34 0.00 0.00 42.96 28.81 382.60 1549.04 0.00 0.00 342.84 0.00 0.00 0.00 -174.91 0.00
F7 SW APARTMENT 22-OCT-14:45 0.00 -3109.71 0.00 0.00 40.71 50.41 400.26 3349.09 0.00 190.56 0.00 0.00 0.00 0.00 0.00 -921.33
F7 NW APARTMENT 19-MAY-17:30 0.00 -2908.14 0.00 0.00 141.81 194.45 588.62 2165.23 0.00 345.02 0.00 0.00 0.00 0.00 0.00 -526.98
F7 SE APARTMENT 01-OCT-10:30 0.00 -2717.11 0.00 0.00 40.75 28.81 412.03 3429.50 0.00 95.64 0.00 0.00 0.00 0.00 0.00 -1289.62
F7 NE APARTMENT 10-JUN-09:15 0.00 -2344.21 0.00 0.00 40.75 28.81 406.15 1794.64 0.00 452.85 0.00 0.00 0.00 0.00 0.00 -378.99
F7 N1 APARTMENT 09-MAY-20:00 0.00 -1850.20 0.00 0.00 141.81 230.46 523.87 0.00 0.00 692.50 274.67 0.00 -13.11 0.00 0.00 0.00
F7 N2 APARTMENT 09-MAY-20:00 0.00 -1841.54 0.00 0.00 141.81 230.46 523.87 0.00 0.00 691.68 266.69 0.00 -12.98 0.00 0.00 0.00
F7 S1 APARTMENT 03-NOV-14:30 0.00 -2045.33 0.00 0.00 40.39 50.41 400.26 2323.38 0.00 0.00 0.00 0.00 0.00 0.00 -115.06 -654.06
F7 S2 APARTMENT 03-NOV-14:30 0.00 -2049.25 0.00 0.00 40.41 50.41 400.26 2323.53 0.00 0.00 0.00 0.00 0.00 0.00 -114.19 -651.17
F8 SW APARTMENT 22-OCT-14:45 0.00 -3110.74 0.00 0.00 40.73 50.41 400.26 3341.55 0.00 192.32 0.00 0.00 0.00 0.00 0.00 -914.53
F8 NW APARTMENT 19-MAY-17:20 0.00 -2912.10 0.00 0.00 141.81 194.45 588.62 2151.80 0.00 360.96 0.00 0.00 0.00 0.00 0.00 -525.54
F8 SE APARTMENT 01-OCT-10:30 0.00 -2724.21 0.00 0.00 40.75 28.81 412.03 3429.01 0.00 94.63 0.00 0.00 0.00 0.00 0.00 -1281.02
F8 NE APARTMENT 10-JUN-09:15 0.00 -2348.22 0.00 0.00 40.75 28.81 406.15 1784.11 0.00 466.54 0.00 0.00 0.00 0.00 0.00 -378.13
F8 N1 APARTMENT 09-MAY-20:00 0.00 -1857.86 0.00 0.00 141.81 230.46 523.87 0.00 0.00 713.42 260.99 0.00 -12.70 0.00 0.00 0.00
F8 N2 APARTMENT 09-MAY-20:00 0.00 -1849.31 0.00 0.00 141.81 230.46 523.87 0.00 0.00 712.57 253.16 0.00 -12.56 0.00 0.00 0.00
F8 S1 APARTMENT 03-NOV-14:30 0.00 -2049.25 0.00 0.00 40.52 50.41 400.26 2321.05 0.00 0.00 0.00 0.00 0.00 0.00 -113.20 -649.79
F8 S2 APARTMENT 03-NOV-14:30 0.00 -2053.13 0.00 0.00 40.54 50.41 400.26 2321.22 0.00 0.00 0.00 0.00 0.00 0.00 -112.30 -647.00
F9 SW APARTMENT 22-OCT-15:15 0.00 -3207.14 0.00 0.00 48.90 100.83 470.89 3170.15 0.00 215.63 0.00 0.00 0.00 0.00 0.00 -799.26
F9 NW APARTMENT 27-JUN-17:20 0.00 -2990.43 0.00 0.00 141.12 194.45 588.62 2603.61 0.00 116.99 0.00 0.00 0.00 0.00 0.00 -654.36
F9 SE APARTMENT 29-SEP-12:00 0.00 -2771.38 0.00 0.00 40.73 28.81 406.15 2406.74 0.00 423.09 0.00 0.00 0.00 0.00 0.00 -534.14
F9 NE APARTMENT 10-JUN-09:15 0.00 -2442.32 0.00 0.00 40.75 28.81 406.15 1773.55 0.00 488.24 0.00 0.00 0.00 0.00 0.00 -295.17
F9 N1 APARTMENT 09-MAY-20:00 0.00 -1943.95 0.00 0.00 141.81 230.46 523.87 0.00 0.00 739.19 322.46 0.00 -13.85 0.00 0.00 0.00
F9 N2 APARTMENT 09-MAY-20:00 0.00 -1935.44 0.00 0.00 141.81 230.46 523.87 0.00 0.00 738.39 314.61 0.00 -13.70 0.00 0.00 0.00
F9 S1 APARTMENT 03-NOV-14:45 0.00 -2108.08 0.00 0.00 40.75 50.41 400.26 2195.43 0.00 0.00 0.00 0.00 0.00 0.00 -85.71 -493.07
F9 S2 APARTMENT 03-NOV-14:30 0.00 -2105.41 0.00 0.00 40.75 50.41 400.26 2319.76 0.00 0.00 0.00 0.00 0.00 0.00 -105.30 -600.48
T SW APARTMENT 22-OCT-15:15 0.00 -3865.65 0.00 0.00 48.90 100.83 470.89 3123.78 0.00 218.94 0.00 0.00 0.00 0.00 0.00 -97.69
T NW APARTMENT 27-JUN-17:10 0.00 -3652.98 0.00 0.00 141.67 194.45 588.62 2583.69 0.00 111.55 33.00 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 01-OCT-11:15 0.00 -3423.44 0.00 0.00 40.75 28.81 406.15 3115.81 0.00 11.93 0.00 0.00 0.00 0.00 0.00 -180.00
T NE APARTMENT 05-JUN-17:00 0.00 -2954.65 0.00 0.00 84.01 144.04 588.62 1151.68 0.00 536.82 449.49 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 17-JUN-18:15 0.00 -2344.00 0.00 0.00 140.07 230.46 547.42 676.55 0.00 175.16 574.35 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 17-JUN-18:15 0.00 -2338.76 0.00 0.00 140.45 230.46 547.42 677.95 0.00 175.86 566.62 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 22-OCT-13:15 0.00 -2796.05 0.00 0.00 40.35 28.81 382.60 2454.46 0.00 58.95 0.00 0.00 0.00 0.00 0.00 -169.12
T S2 APARTMENT 22-OCT-13:15 0.00 -2799.85 0.00 0.00 40.34 28.81 382.60 2454.27 0.00 58.70 0.00 0.00 0.00 0.00 0.00 -164.87
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-JUN-17:00 0.00 -174527.88 0.00 0.00 6633.61 18221.75 47207.76 99464.77 0.00 31984.14 0.00 0.00 0.00 0.00 0.00 -28984.15


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 06-APR-14:00 1205.99 0.00 0.00 0.00 40.75 28.81 382.60 1396.31 0.00 0.00 0.00 0.00 0.00 0.00 -2047.57 -1006.89
G NW APARTMENT 06-APR-14:00 1922.19 0.00 0.00 0.00 42.27 28.81 382.60 947.63 0.00 0.00 0.00 0.00 0.00 0.00 -2023.86 -1299.63
OFFICE 27-DEC-07:25 764.45 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -1055.51 0.00 -125.94 -157.56
G NE APARTMENT 06-APR-14:00 1758.01 0.00 0.00 0.00 42.49 28.81 382.60 418.08 0.00 0.00 0.00 0.00 0.00 0.00 -2021.05 -608.94
G N1 APARTMENT 06-APR-14:00 1740.87 0.00 0.00 0.00 43.05 28.81 382.60 264.52 0.00 0.00 0.00 0.00 0.00 0.00 -1930.45 -529.40
G N2 APARTMENT 06-APR-14:00 1745.72 0.00 0.00 0.00 43.00 28.81 382.60 263.96 0.00 0.00 0.00 0.00 0.00 0.00 -1930.46 -533.64
G S1 APARTMENT 06-APR-14:00 1976.52 0.00 0.00 0.00 41.27 28.81 382.60 721.83 0.00 0.00 0.00 0.00 0.00 0.00 -1933.13 -1217.90
G S2 APARTMENT 06-APR-14:00 1655.22 0.00 0.00 0.00 40.96 28.81 382.60 718.64 0.00 0.00 0.00 0.00 0.00 0.00 -1940.00 -886.24
F2 SW APARTMENT 27-DEC-06:00 513.21 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 215.69 0.00 -1072.21 0.00 -193.09 0.00
F2 NW APARTMENT 06-APR-14:00 1573.49 0.00 0.00 0.00 40.75 28.81 382.60 802.88 0.00 0.00 0.00 0.00 0.00 0.00 -2786.70 -41.82
F2 SE APARTMENT 27-DEC-06:00 480.81 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 246.92 0.00 -1071.03 0.00 -193.09 0.00
F2 NE APARTMENT 11-MAR-16:00 1685.32 0.00 0.00 0.00 41.82 50.41 400.26 71.83 0.00 0.00 0.00 0.00 0.00 0.00 -1843.63 -406.02
F2 N1 APARTMENT 06-APR-14:00 2118.72 0.00 0.00 0.00 40.75 28.81 382.60 201.06 0.00 0.00 0.00 0.00 0.00 0.00 -2643.51 -128.43
F2 N2 APARTMENT 06-APR-14:00 2088.08 0.00 0.00 0.00 40.75 28.81 382.60 200.59 0.00 0.00 0.00 0.00 0.00 0.00 -2643.47 -97.36
F2 S1 APARTMENT 06-APR-14:00 1013.45 0.00 0.00 0.00 40.75 28.81 382.60 615.45 0.00 0.00 575.51 0.00 0.00 0.00 -2656.57 0.00
F2 S2 APARTMENT 06-APR-14:00 927.55 0.00 0.00 0.00 40.75 28.81 382.60 614.87 0.00 0.00 663.36 0.00 0.00 0.00 -2657.94 0.00
F3 SW APARTMENT 06-APR-14:00 1107.38 0.00 0.00 0.00 40.75 28.81 382.60 1140.35 0.00 0.00 564.57 0.00 0.00 0.00 -3264.46 0.00
F3 NW APARTMENT 06-APR-14:00 1955.90 0.00 0.00 0.00 40.75 28.81 382.60 753.00 0.00 0.00 87.56 0.00 0.00 0.00 -3248.62 0.00
F3 SE APARTMENT 06-APR-14:00 1007.14 0.00 0.00 0.00 40.75 28.81 382.60 680.65 0.00 0.00 1120.73 0.00 0.00 0.00 -3260.68 0.00
F3 NE APARTMENT 06-APR-14:00 1861.63 0.00 0.00 0.00 40.75 28.81 382.60 293.05 0.00 0.00 638.48 0.00 0.00 0.00 -3245.31 0.00
F3 N1 APARTMENT 06-APR-14:00 2050.87 0.00 0.00 0.00 40.75 28.81 382.60 182.74 0.00 0.00 405.38 0.00 0.00 0.00 -3091.15 0.00
F3 N2 APARTMENT 06-APR-14:00 2034.82 0.00 0.00 0.00 40.75 28.81 382.60 182.35 0.00 0.00 421.79 0.00 0.00 0.00 -3091.12 0.00
F3 S1 APARTMENT 06-APR-14:00 1585.15 0.00 0.00 0.00 40.75 28.81 382.60 575.89 0.00 0.00 480.83 0.00 0.00 0.00 -3094.03 0.00
F3 S2 APARTMENT 06-APR-14:00 1540.51 0.00 0.00 0.00 40.75 28.81 382.60 575.55 0.00 0.00 526.49 0.00 0.00 0.00 -3094.71 0.00
F4 SW APARTMENT 06-APR-14:15 1071.98 0.00 0.00 0.00 40.75 50.41 400.26 1166.16 0.00 0.00 577.47 0.00 0.00 0.00 -3307.03 0.00
F4 NW APARTMENT 06-APR-14:15 1922.18 0.00 0.00 0.00 40.75 50.41 400.26 807.96 0.00 0.00 68.97 0.00 0.00 0.00 -3290.54 0.00
F4 SE APARTMENT 06-APR-14:15 1114.95 0.00 0.00 0.00 40.75 50.41 400.26 614.77 0.00 0.00 1079.32 0.00 0.00 0.00 -3300.46 0.00
F4 NE APARTMENT 06-APR-14:15 1868.80 0.00 0.00 0.00 40.75 50.41 400.26 256.05 0.00 0.00 670.90 0.00 0.00 0.00 -3287.17 0.00
F4 N1 APARTMENT 06-APR-14:15 2036.40 0.00 0.00 0.00 40.75 50.41 400.26 159.78 0.00 0.00 443.01 0.00 0.00 0.00 -3130.61 0.00
F4 N2 APARTMENT 06-APR-14:15 2021.49 0.00 0.00 0.00 40.75 50.41 400.26 159.41 0.00 0.00 458.26 0.00 0.00 0.00 -3130.58 0.00
F4 S1 APARTMENT 06-APR-14:15 1608.95 0.00 0.00 0.00 40.75 50.41 400.26 523.66 0.00 0.00 509.10 0.00 0.00 0.00 -3133.14 0.00
F4 S2 APARTMENT 06-APR-14:15 1571.85 0.00 0.00 0.00 40.75 50.41 400.26 523.36 0.00 0.00 547.06 0.00 0.00 0.00 -3133.69 0.00
M SW APARTMENT 06-APR-14:15 1670.40 0.00 0.00 0.00 40.75 50.41 400.26 1134.14 0.00 0.00 275.13 0.00 0.00 0.00 -3571.09 0.00
M NW APARTMENT 06-APR-14:15 2073.30 0.00 0.00 0.00 40.75 50.41 400.26 785.93 0.00 0.00 216.87 0.00 0.00 0.00 -3567.52 0.00
M SE APARTMENT 06-APR-14:15 1701.96 0.00 0.00 0.00 40.75 50.41 400.26 593.95 0.00 0.00 778.85 0.00 0.00 0.00 -3566.18 0.00
M NE APARTMENT 06-APR-14:15 2005.87 0.00 0.00 0.00 40.75 50.41 400.26 244.92 0.00 0.00 822.07 0.00 0.00 0.00 -3564.28 0.00
M N1 APARTMENT 06-APR-14:15 2148.10 0.00 0.00 0.00 40.75 50.41 400.26 152.83 0.00 0.00 601.63 0.00 0.00 0.00 -3393.97 0.00
M N2 APARTMENT 06-APR-14:15 2133.05 0.00 0.00 0.00 40.75 50.41 400.26 152.45 0.00 0.00 617.02 0.00 0.00 0.00 -3393.95 0.00
M S1 APARTMENT 06-APR-14:15 1849.80 0.00 0.00 0.00 40.75 50.41 400.26 507.06 0.00 0.00 545.88 0.00 0.00 0.00 -3394.16 0.00
M S2 APARTMENT 06-APR-14:15 1838.83 0.00 0.00 0.00 40.75 50.41 400.26 506.76 0.00 0.00 557.18 0.00 0.00 0.00 -3394.19 0.00
F6 SW APARTMENT 06-APR-14:15 1983.96 0.00 0.00 0.00 40.75 50.41 400.26 1112.34 0.00 0.00 222.33 0.00 0.00 0.00 -3810.05 0.00
F6 NW APARTMENT 06-APR-14:15 2246.74 0.00 0.00 0.00 40.93 50.41 400.26 773.44 0.00 0.00 297.31 0.00 0.00 0.00 -3809.10 0.00
F6 SE APARTMENT 06-APR-14:15 1931.23 0.00 0.00 0.00 40.75 50.41 400.26 580.46 0.00 0.00 804.37 0.00 0.00 0.00 -3807.48 0.00
F6 NE APARTMENT 06-APR-14:15 2169.24 0.00 0.00 0.00 40.86 50.41 400.26 239.73 0.00 0.00 905.77 0.00 0.00 0.00 -3806.28 0.00
F6 N1 APARTMENT 06-APR-14:15 2336.46 0.00 0.00 0.00 40.75 50.41 400.26 149.31 0.00 0.00 647.05 0.00 0.00 0.00 -3624.24 0.00
F6 N2 APARTMENT 06-APR-14:15 2319.14 0.00 0.00 0.00 40.75 50.41 400.26 148.89 0.00 0.00 664.77 0.00 0.00 0.00 -3624.22 0.00
F6 S1 APARTMENT 06-APR-14:15 2032.44 0.00 0.00 0.00 40.75 50.41 400.26 496.02 0.00 0.00 604.57 0.00 0.00 0.00 -3624.45 0.00
F6 S2 APARTMENT 06-APR-14:15 2020.61 0.00 0.00 0.00 40.75 50.41 400.26 495.69 0.00 0.00 616.75 0.00 0.00 0.00 -3624.47 0.00
F7 SW APARTMENT 06-APR-14:15 2161.33 0.00 0.00 0.00 40.75 50.41 400.26 1093.92 0.00 0.00 281.00 0.00 0.00 0.00 -4027.67 0.00
F7 NW APARTMENT 06-APR-14:15 2328.31 0.00 0.00 0.00 41.24 50.41 400.26 763.25 0.00 0.00 442.66 0.00 0.00 0.00 -4026.14 0.00
F7 SE APARTMENT 06-APR-14:15 2094.36 0.00 0.00 0.00 40.75 50.41 400.26 568.76 0.00 0.00 870.71 0.00 0.00 0.00 -4025.26 0.00
F7 NE APARTMENT 06-APR-14:15 2249.94 0.00 0.00 0.00 41.16 50.41 400.26 236.31 0.00 0.00 1045.61 0.00 0.00 0.00 -4023.69 0.00
F7 N1 APARTMENT 06-APR-14:10 2471.11 0.00 0.00 0.00 40.92 50.41 400.26 146.54 0.00 0.00 772.27 0.00 0.00 0.00 -3881.51 0.00
F7 N2 APARTMENT 06-APR-14:10 2440.11 0.00 0.00 0.00 40.87 50.41 400.26 145.92 0.00 0.00 804.53 0.00 0.00 0.00 -3882.11 0.00
F7 S1 APARTMENT 06-APR-14:15 2180.02 0.00 0.00 0.00 40.75 50.41 400.26 486.60 0.00 0.00 673.52 0.00 0.00 0.00 -3831.56 0.00
F7 S2 APARTMENT 06-APR-14:15 2167.42 0.00 0.00 0.00 40.75 50.41 400.26 486.25 0.00 0.00 686.50 0.00 0.00 0.00 -3831.59 0.00
F8 SW APARTMENT 06-APR-14:15 2317.93 0.00 0.00 0.00 40.75 50.41 400.26 1078.24 0.00 0.00 339.34 0.00 0.00 0.00 -4226.93 0.00
F8 NW APARTMENT 06-APR-14:10 2669.77 0.00 0.00 0.00 41.48 50.41 400.26 754.28 0.00 0.00 372.80 0.00 0.00 0.00 -4289.00 0.00
F8 SE APARTMENT 06-APR-14:15 2240.19 0.00 0.00 0.00 40.75 50.41 400.26 558.73 0.00 0.00 934.31 0.00 0.00 0.00 -4224.65 0.00
F8 NE APARTMENT 06-APR-14:10 2590.44 0.00 0.00 0.00 41.40 50.41 400.26 233.04 0.00 0.00 961.94 0.00 0.00 0.00 -4277.49 0.00
F8 N1 APARTMENT 06-APR-14:10 2872.51 0.00 0.00 0.00 41.10 50.41 400.26 144.33 0.00 0.00 557.10 0.00 0.00 0.00 -4065.71 0.00
F8 N2 APARTMENT 06-APR-14:10 2841.92 0.00 0.00 0.00 41.05 50.41 400.26 143.72 0.00 0.00 588.97 0.00 0.00 0.00 -4066.34 0.00
F8 S1 APARTMENT 06-APR-14:15 2309.72 0.00 0.00 0.00 40.75 50.41 400.26 478.53 0.00 0.00 741.54 0.00 0.00 0.00 -4021.21 0.00
F8 S2 APARTMENT 06-APR-14:15 2296.67 0.00 0.00 0.00 40.75 50.41 400.26 478.17 0.00 0.00 754.98 0.00 0.00 0.00 -4021.24 0.00
F9 SW APARTMENT 06-APR-14:10 2513.58 0.00 0.00 0.00 40.80 50.41 400.26 1066.62 0.00 0.00 420.30 0.00 0.00 0.00 -4491.97 0.00
F9 NW APARTMENT 06-APR-14:10 3104.68 0.00 0.00 0.00 41.74 50.41 400.26 748.37 0.00 0.00 120.85 0.00 0.00 0.00 -4466.31 0.00
F9 SE APARTMENT 06-APR-14:15 2392.15 0.00 0.00 0.00 40.75 50.41 400.26 550.86 0.00 0.00 975.47 0.00 0.00 0.00 -4409.90 0.00
F9 NE APARTMENT 06-APR-14:10 3015.84 0.00 0.00 0.00 41.64 50.41 400.26 231.30 0.00 0.00 716.90 0.00 0.00 0.00 -4456.35 0.00
F9 N1 APARTMENT 06-APR-14:10 3291.22 0.00 0.00 0.00 41.30 50.41 400.26 143.24 0.00 0.00 310.90 0.00 0.00 0.00 -4237.34 0.00
F9 N2 APARTMENT 06-APR-14:10 3257.54 0.00 0.00 0.00 41.25 50.41 400.26 142.55 0.00 0.00 346.09 0.00 0.00 0.00 -4238.11 0.00
F9 S1 APARTMENT 06-APR-14:10 2610.00 0.00 0.00 0.00 40.75 50.41 400.26 472.19 0.00 0.00 675.73 0.00 0.00 0.00 -4249.34 0.00
F9 S2 APARTMENT 06-APR-14:10 2569.04 0.00 0.00 0.00 40.75 50.41 400.26 471.76 0.00 0.00 717.56 0.00 0.00 0.00 -4249.78 0.00
T SW APARTMENT 10-APR-16:53 3115.86 0.00 0.00 0.00 98.63 144.04 588.62 141.76 0.00 0.00 937.15 0.00 0.00 0.00 -5026.05 0.00
T NW APARTMENT 10-APR-16:53 3225.35 0.00 0.00 0.00 98.63 144.04 588.62 143.26 0.00 0.00 826.16 0.00 0.00 0.00 -5026.05 0.00
T SE APARTMENT 10-APR-16:53 3217.20 0.00 0.00 0.00 98.63 144.04 588.62 0.00 0.00 0.00 1111.28 0.00 -133.71 0.00 -5026.05 0.00
T NE APARTMENT 10-APR-16:53 3321.20 0.00 0.00 0.00 98.63 144.04 588.62 0.00 0.00 0.00 1005.93 0.00 -132.37 0.00 -5026.05 0.00
T N1 APARTMENT 06-APR-14:25 3287.48 0.00 0.00 0.00 41.38 50.41 400.26 130.30 0.00 0.00 79.96 0.00 0.00 0.00 -3989.79 0.00
T N2 APARTMENT 06-APR-14:25 3260.59 0.00 0.00 0.00 41.32 50.41 400.26 129.63 0.00 0.00 108.51 0.00 0.00 0.00 -3990.72 0.00
T S1 APARTMENT 10-APR-16:53 3022.98 0.00 0.00 0.00 98.63 144.04 588.62 0.00 0.00 0.00 1009.28 0.00 -85.23 0.00 -4778.33 0.00
T S2 APARTMENT 10-APR-16:53 3025.09 0.00 0.00 0.00 98.63 144.04 588.62 0.00 0.00 0.00 1007.12 0.00 -85.17 0.00 -4778.33 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-APR-17:00 114007.80 0.00 0.00 0.00 7777.73 18221.75 47207.76 3407.31 0.00 0.00 118705.12 0.00 -6147.23 0.00 -303180.23 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Sec1.1A-General Information

Data
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 40.50
Number of hours cooling loads not met 294.75
Number of hours not met 335.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.57 10720.10 0.00 0.00 0.00 0.00
Space Heating 14.85 0.00 19.80 59159.29 0.00 0.00
Space Cooling 659.36 61623.93 0.00 0.00 0.00 0.00
Pumps 44.21 1422.06 0.00 0.00 0.00 0.00
Heat Rejection 24.64 2273.08 0.00 0.00 0.00 0.00
Fans-Interior 640.88 20322.08 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 995.45 82933.34 0.00 0.00
Receptacle Equipment 1131.09 49704.83 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3120.83   1015.24   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3120.83
Natural Gas 0.00 1015.24
Additional 0.00 0.00
Total 1131.09 4136.08


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 1.90
Space Cooling 84.14
Fans-Interior 81.78
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 32.95
Subtotal 398.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 2.53
Service Water Heating 127.03
Miscellaneous 0.00
Subtotal 129.55


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 10.07
Space Heating 0.84
Space Cooling 15.94
Fans-Interior 15.49
Service Water Heating 24.07
Receptacle Equipment 27.35
Miscellaneous 6.24



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.237061
G NW APARTMENT DIRECT AIR 0.235517
OFFICE DIRECT AIR 0.310027
G NE APARTMENT DIRECT AIR 0.182169
G N1 APARTMENT DIRECT AIR 0.135193
G N2 APARTMENT DIRECT AIR 0.133984
G S1 APARTMENT DIRECT AIR 0.133128
G S2 APARTMENT DIRECT AIR 0.138266
F2 SW APARTMENT DIRECT AIR 0.294151
F2 NW APARTMENT DIRECT AIR 0.291180
F2 SE APARTMENT DIRECT AIR 0.263666
F2 NE APARTMENT DIRECT AIR 0.230733
F2 N1 APARTMENT DIRECT AIR 0.171694
F2 N2 APARTMENT DIRECT AIR 0.170715
F2 S1 APARTMENT DIRECT AIR 0.171193
F2 S2 APARTMENT DIRECT AIR 0.172891
F3 SW APARTMENT DIRECT AIR 0.294810
F3 NW APARTMENT DIRECT AIR 0.292316
F3 SE APARTMENT DIRECT AIR 0.248316
F3 NE APARTMENT DIRECT AIR 0.233427
F3 N1 APARTMENT DIRECT AIR 0.174390
F3 N2 APARTMENT DIRECT AIR 0.173428
F3 S1 APARTMENT DIRECT AIR 0.173901
F3 S2 APARTMENT DIRECT AIR 0.174602
F4 SW APARTMENT DIRECT AIR 0.295938
F4 NW APARTMENT DIRECT AIR 0.293476
F4 SE APARTMENT DIRECT AIR 0.248453
F4 NE APARTMENT DIRECT AIR 0.234810
F4 N1 APARTMENT DIRECT AIR 0.176129
F4 N2 APARTMENT DIRECT AIR 0.175178
F4 S1 APARTMENT DIRECT AIR 0.175499
F4 S2 APARTMENT DIRECT AIR 0.176025
M SW APARTMENT DIRECT AIR 0.299542
M NW APARTMENT DIRECT AIR 0.297189
M SE APARTMENT DIRECT AIR 0.252418
M NE APARTMENT DIRECT AIR 0.238645
M N1 APARTMENT DIRECT AIR 0.180149
M N2 APARTMENT DIRECT AIR 0.179208
M S1 APARTMENT DIRECT AIR 0.179323
M S2 APARTMENT DIRECT AIR 0.179806
F6 SW APARTMENT DIRECT AIR 0.295986
F6 NW APARTMENT DIRECT AIR 0.293544
F6 SE APARTMENT DIRECT AIR 0.249439
F6 NE APARTMENT DIRECT AIR 0.235224
F6 N1 APARTMENT DIRECT AIR 0.177036
F6 N2 APARTMENT DIRECT AIR 0.176107
F6 S1 APARTMENT DIRECT AIR 0.176182
F6 S2 APARTMENT DIRECT AIR 0.176659
F7 SW APARTMENT DIRECT AIR 0.295025
F7 NW APARTMENT DIRECT AIR 0.292612
F7 SE APARTMENT DIRECT AIR 0.248964
F7 NE APARTMENT DIRECT AIR 0.234454
F7 N1 APARTMENT DIRECT AIR 0.176466
F7 N2 APARTMENT DIRECT AIR 0.175548
F7 S1 APARTMENT DIRECT AIR 0.175504
F7 S2 APARTMENT DIRECT AIR 0.175980
F8 SW APARTMENT DIRECT AIR 0.295647
F8 NW APARTMENT DIRECT AIR 0.293252
F8 SE APARTMENT DIRECT AIR 0.249951
F8 NE APARTMENT DIRECT AIR 0.235159
F8 N1 APARTMENT DIRECT AIR 0.177408
F8 N2 APARTMENT DIRECT AIR 0.176500
F8 S1 APARTMENT DIRECT AIR 0.176299
F8 S2 APARTMENT DIRECT AIR 0.176776
F9 SW APARTMENT DIRECT AIR 0.305776
F9 NW APARTMENT DIRECT AIR 0.303429
F9 SE APARTMENT DIRECT AIR 0.258257
F9 NE APARTMENT DIRECT AIR 0.243457
F9 N1 APARTMENT DIRECT AIR 0.186676
F9 N2 APARTMENT DIRECT AIR 0.185772
F9 S1 APARTMENT DIRECT AIR 0.183377
F9 S2 APARTMENT DIRECT AIR 0.183819
T SW APARTMENT DIRECT AIR 0.374762
T NW APARTMENT DIRECT AIR 0.367726
T SE APARTMENT DIRECT AIR 0.324688
T NE APARTMENT DIRECT AIR 0.300205
T N1 APARTMENT DIRECT AIR 0.231458
T N2 APARTMENT DIRECT AIR 0.230771
T S1 APARTMENT DIRECT AIR 0.254066
T S2 APARTMENT DIRECT AIR 0.254454


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.237061
AIRLOOP G NW MAIN BRANCH 0.235517
AIRLOOP OFFICE MAIN BRANCH 0.310027
AIRLOOP G NE MAIN BRANCH 0.182169
AIRLOOP G N1 MAIN BRANCH 0.135193
AIRLOOP G N2 MAIN BRANCH 0.133984
AIRLOOP G S1 MAIN BRANCH 0.133128
AIRLOOP G S2 MAIN BRANCH 0.138266
AIRLOOP F2 SW MAIN BRANCH 0.294151
AIRLOOP F2 NW MAIN BRANCH 0.291180
AIRLOOP F2 SE MAIN BRANCH 0.263666
AIRLOOP F2 NE MAIN BRANCH 0.230733
AIRLOOP F2 N1 MAIN BRANCH 0.171694
AIRLOOP F2 N2 MAIN BRANCH 0.170715
AIRLOOP F2 S1 MAIN BRANCH 0.171193
AIRLOOP F2 S2 MAIN BRANCH 0.172891
AIRLOOP F3 SW MAIN BRANCH 0.294810
AIRLOOP F3 NW MAIN BRANCH 0.292316
AIRLOOP F3 SE MAIN BRANCH 0.248316
AIRLOOP F3 NE MAIN BRANCH 0.233427
AIRLOOP F3 N1 MAIN BRANCH 0.174390
AIRLOOP F3 N2 MAIN BRANCH 0.173428
AIRLOOP F3 S1 MAIN BRANCH 0.173901
AIRLOOP F3 S2 MAIN BRANCH 0.174602
AIRLOOP F4 SW MAIN BRANCH 0.295938
AIRLOOP F4 NW MAIN BRANCH 0.293476
AIRLOOP F4 SE MAIN BRANCH 0.248453
AIRLOOP F4 NE MAIN BRANCH 0.234810
AIRLOOP F4 N1 MAIN BRANCH 0.176129
AIRLOOP F4 N2 MAIN BRANCH 0.175178
AIRLOOP F4 S1 MAIN BRANCH 0.175499
AIRLOOP F4 S2 MAIN BRANCH 0.176025
AIRLOOP M SW MAIN BRANCH 0.299542
AIRLOOP M NW MAIN BRANCH 0.297189
AIRLOOP M SE MAIN BRANCH 0.252418
AIRLOOP M NE MAIN BRANCH 0.238645
AIRLOOP M N1 MAIN BRANCH 0.180149
AIRLOOP M N2 MAIN BRANCH 0.179208
AIRLOOP M S1 MAIN BRANCH 0.179323
AIRLOOP M S2 MAIN BRANCH 0.179806
AIRLOOP F6 SW MAIN BRANCH 0.295986
AIRLOOP F6 NW MAIN BRANCH 0.293544
AIRLOOP F6 SE MAIN BRANCH 0.249439
AIRLOOP F6 NE MAIN BRANCH 0.235224
AIRLOOP F6 N1 MAIN BRANCH 0.177036
AIRLOOP F6 N2 MAIN BRANCH 0.176107
AIRLOOP F6 S1 MAIN BRANCH 0.176182
AIRLOOP F6 S2 MAIN BRANCH 0.176659
AIRLOOP F7 SW MAIN BRANCH 0.295025
AIRLOOP F7 NW MAIN BRANCH 0.292612
AIRLOOP F7 SE MAIN BRANCH 0.248964
AIRLOOP F7 NE MAIN BRANCH 0.234454
AIRLOOP F7 N1 MAIN BRANCH 0.176466
AIRLOOP F7 N2 MAIN BRANCH 0.175548
AIRLOOP F7 S1 MAIN BRANCH 0.175504
AIRLOOP F7 S2 MAIN BRANCH 0.175980
AIRLOOP F8 SW MAIN BRANCH 0.295647
AIRLOOP F8 NW MAIN BRANCH 0.293252
AIRLOOP F8 SE MAIN BRANCH 0.249951
AIRLOOP F8 NE MAIN BRANCH 0.235159
AIRLOOP F8 N1 MAIN BRANCH 0.177408
AIRLOOP F8 N2 MAIN BRANCH 0.176500
AIRLOOP F8 S1 MAIN BRANCH 0.176299
AIRLOOP F8 S2 MAIN BRANCH 0.176776
AIRLOOP F9 SW MAIN BRANCH 0.305776
AIRLOOP F9 NW MAIN BRANCH 0.303429
AIRLOOP F9 SE MAIN BRANCH 0.258257
AIRLOOP F9 NE MAIN BRANCH 0.243457
AIRLOOP F9 N1 MAIN BRANCH 0.186676
AIRLOOP F9 N2 MAIN BRANCH 0.185772
AIRLOOP F9 S1 MAIN BRANCH 0.183377
AIRLOOP F9 S2 MAIN BRANCH 0.183819
AIRLOOP T SW MAIN BRANCH 0.374762
AIRLOOP T NW MAIN BRANCH 0.367726
AIRLOOP T SE MAIN BRANCH 0.324688
AIRLOOP T NE MAIN BRANCH 0.300205
AIRLOOP T N1 MAIN BRANCH 0.231458
AIRLOOP T N2 MAIN BRANCH 0.230771
AIRLOOP T S1 MAIN BRANCH 0.254066
AIRLOOP T S2 MAIN BRANCH 0.254454


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.237061
AIRLOOP G NW 0.235517
AIRLOOP OFFICE 0.310027
AIRLOOP G NE 0.182169
AIRLOOP G N1 0.135193
AIRLOOP G N2 0.133984
AIRLOOP G S1 0.133128
AIRLOOP G S2 0.138266
AIRLOOP F2 SW 0.294151
AIRLOOP F2 NW 0.291180
AIRLOOP F2 SE 0.263666
AIRLOOP F2 NE 0.230733
AIRLOOP F2 N1 0.171694
AIRLOOP F2 N2 0.170715
AIRLOOP F2 S1 0.171193
AIRLOOP F2 S2 0.172891
AIRLOOP F3 SW 0.294810
AIRLOOP F3 NW 0.292316
AIRLOOP F3 SE 0.248316
AIRLOOP F3 NE 0.233427
AIRLOOP F3 N1 0.174390
AIRLOOP F3 N2 0.173428
AIRLOOP F3 S1 0.173901
AIRLOOP F3 S2 0.174602
AIRLOOP F4 SW 0.295938
AIRLOOP F4 NW 0.293476
AIRLOOP F4 SE 0.248453
AIRLOOP F4 NE 0.234810
AIRLOOP F4 N1 0.176129
AIRLOOP F4 N2 0.175178
AIRLOOP F4 S1 0.175499
AIRLOOP F4 S2 0.176025
AIRLOOP M SW 0.299542
AIRLOOP M NW 0.297189
AIRLOOP M SE 0.252418
AIRLOOP M NE 0.238645
AIRLOOP M N1 0.180149
AIRLOOP M N2 0.179208
AIRLOOP M S1 0.179323
AIRLOOP M S2 0.179806
AIRLOOP F6 SW 0.295986
AIRLOOP F6 NW 0.293544
AIRLOOP F6 SE 0.249439
AIRLOOP F6 NE 0.235224
AIRLOOP F6 N1 0.177036
AIRLOOP F6 N2 0.176107
AIRLOOP F6 S1 0.176182
AIRLOOP F6 S2 0.176659
AIRLOOP F7 SW 0.295025
AIRLOOP F7 NW 0.292612
AIRLOOP F7 SE 0.248964
AIRLOOP F7 NE 0.234454
AIRLOOP F7 N1 0.176466
AIRLOOP F7 N2 0.175548
AIRLOOP F7 S1 0.175504
AIRLOOP F7 S2 0.175980
AIRLOOP F8 SW 0.295647
AIRLOOP F8 NW 0.293252
AIRLOOP F8 SE 0.249951
AIRLOOP F8 NE 0.235159
AIRLOOP F8 N1 0.177408
AIRLOOP F8 N2 0.176500
AIRLOOP F8 S1 0.176299
AIRLOOP F8 S2 0.176776
AIRLOOP F9 SW 0.305776
AIRLOOP F9 NW 0.303429
AIRLOOP F9 SE 0.258257
AIRLOOP F9 NE 0.243457
AIRLOOP F9 N1 0.186676
AIRLOOP F9 N2 0.185772
AIRLOOP F9 S1 0.183377
AIRLOOP F9 S2 0.183819
AIRLOOP T SW 0.374762
AIRLOOP T NW 0.367726
AIRLOOP T SE 0.324688
AIRLOOP T NE 0.300205
AIRLOOP T N1 0.231458
AIRLOOP T N2 0.230771
AIRLOOP T S1 0.254066
AIRLOOP T S2 0.254454


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.237061 0.025952
AIRLOOP G NW OA CONTROLLER 0.235517 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.310027 0.038103
AIRLOOP G NE OA CONTROLLER 0.182169 0.025952
AIRLOOP G N1 OA CONTROLLER 0.135193 0.025952
AIRLOOP G N2 OA CONTROLLER 0.133984 0.025952
AIRLOOP G S1 OA CONTROLLER 0.133128 0.025952
AIRLOOP G S2 OA CONTROLLER 0.138266 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.294151 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.291180 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.263666 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.230733 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.171694 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.170715 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.171193 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.172891 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.294810 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.292316 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.248316 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.233427 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.174390 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.173428 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.173901 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.174602 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.295938 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.293476 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.248453 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.234810 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.176129 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.175178 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.175499 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.176025 0.025952
AIRLOOP M SW OA CONTROLLER 0.299542 0.025952
AIRLOOP M NW OA CONTROLLER 0.297189 0.025952
AIRLOOP M SE OA CONTROLLER 0.252418 0.025952
AIRLOOP M NE OA CONTROLLER 0.238645 0.025952
AIRLOOP M N1 OA CONTROLLER 0.180149 0.025952
AIRLOOP M N2 OA CONTROLLER 0.179208 0.025952
AIRLOOP M S1 OA CONTROLLER 0.179323 0.025952
AIRLOOP M S2 OA CONTROLLER 0.179806 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.295986 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.293544 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.249439 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.235224 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.177036 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.176107 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.176182 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.176659 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.295025 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.292612 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.248964 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.234454 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.176466 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.175548 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.175504 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.175980 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.295647 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.293252 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.249951 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.235159 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.177408 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.176500 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.176299 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.176776 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.305776 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.303429 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.258257 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.243457 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.186676 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.185772 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.183377 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.183819 0.025952
AIRLOOP T SW OA CONTROLLER 0.374762 0.025952
AIRLOOP T NW OA CONTROLLER 0.367726 0.025952
AIRLOOP T SE OA CONTROLLER 0.324688 0.025952
AIRLOOP T NE OA CONTROLLER 0.300205 0.025952
AIRLOOP T N1 OA CONTROLLER 0.231458 0.025952
AIRLOOP T N2 OA CONTROLLER 0.230771 0.025952
AIRLOOP T S1 OA CONTROLLER 0.254066 0.025952
AIRLOOP T S2 OA CONTROLLER 0.254454 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.237061 3249.68 2140.77 0.000071
HEAT PUMP COOLING MODE AIRLOOP G NW 0.235517 3218.01 2121.90 0.000070
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.310027 4223.95 2796.49 0.000092
HEAT PUMP COOLING MODE AIRLOOP G NE 0.182169 2488.28 1645.63 0.000054
HEAT PUMP COOLING MODE AIRLOOP G N1 0.135193 1921.73 1251.37 0.000042
HEAT PUMP COOLING MODE AIRLOOP G N2 0.133984 1906.25 1240.97 0.000042
HEAT PUMP COOLING MODE AIRLOOP G S1 0.133128 1970.73 1265.14 0.000043
HEAT PUMP COOLING MODE AIRLOOP G S2 0.138266 2036.19 1309.46 0.000044
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.294151 3965.11 2626.31 0.000087
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.291180 3915.59 2595.20 0.000086
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.263666 3612.81 2380.92 0.000079
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.230733 3107.16 2063.61 0.000068
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.171694 2392.07 1567.90 0.000052
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.170715 2379.58 1559.52 0.000052
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.171193 2454.33 1593.36 0.000054
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.172891 2471.69 1606.29 0.000054
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.294810 3967.89 2630.85 0.000087
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.292316 3924.39 2603.80 0.000086
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.248316 3412.66 2248.73 0.000075
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.233427 3135.87 2085.55 0.000069
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.174390 2423.14 1590.36 0.000053
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.173428 2410.87 1582.11 0.000053
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.173901 2485.63 1616.00 0.000054
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.174602 2490.29 1620.36 0.000054
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.295938 3978.02 2639.66 0.000087
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.293476 3934.90 2612.89 0.000086
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.248453 3410.37 2249.12 0.000074
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.234810 3149.32 2096.56 0.000069
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.176129 2442.83 1604.77 0.000053
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.175178 2430.72 1596.62 0.000053
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.175499 2503.58 1629.25 0.000055
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.176025 2506.01 1632.11 0.000055
HEAT PUMP COOLING MODE AIRLOOP M SW 0.299542 4020.32 2669.74 0.000088
HEAT PUMP COOLING MODE AIRLOOP M NW 0.297189 3978.56 2643.88 0.000087
HEAT PUMP COOLING MODE AIRLOOP M SE 0.252418 3457.37 2282.36 0.000076
HEAT PUMP COOLING MODE AIRLOOP M NE 0.238645 3194.58 2128.63 0.000070
HEAT PUMP COOLING MODE AIRLOOP M N1 0.180149 2492.03 1638.79 0.000054
HEAT PUMP COOLING MODE AIRLOOP M N2 0.179208 2480.05 1630.73 0.000054
HEAT PUMP COOLING MODE AIRLOOP M S1 0.179323 2550.25 1661.69 0.000056
HEAT PUMP COOLING MODE AIRLOOP M S2 0.179806 2552.12 1664.17 0.000056
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.295986 3972.31 2638.86 0.000087
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.293544 3929.39 2612.23 0.000086
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.249439 3416.79 2256.37 0.000075
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.235224 3148.43 2098.90 0.000069
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.177036 2450.64 1611.80 0.000054
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.176107 2438.82 1603.85 0.000053
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.176182 2508.70 1634.42 0.000055
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.176659 2514.76 1638.51 0.000055
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.295025 3957.58 2630.17 0.000086
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.292612 3914.99 2603.79 0.000086
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.248964 3408.31 2251.83 0.000074
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.234454 3136.20 2091.86 0.000069
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.176466 2441.88 1606.63 0.000053
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.175548 2430.19 1598.77 0.000053
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.175504 2498.64 1628.32 0.000055
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.175980 2504.70 1632.41 0.000055
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.295647 3963.16 2635.03 0.000087
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.293252 3920.80 2608.80 0.000086
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.249951 3418.62 2259.84 0.000075
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.235159 3142.91 2097.45 0.000069
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.177408 2452.52 1614.43 0.000054
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.176500 2440.97 1606.66 0.000053
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.176299 2507.45 1634.89 0.000055
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.176776 2513.52 1638.99 0.000055
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.305776 4089.45 2720.99 0.000089
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.303429 4047.73 2695.17 0.000088
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.258257 3526.19 2332.14 0.000077
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.243457 3278.03 2178.02 0.000072
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.186676 2569.27 1693.50 0.000056
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.185772 2557.77 1685.77 0.000056
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.183377 2596.17 1695.38 0.000057
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.183819 2601.78 1699.16 0.000057
HEAT PUMP COOLING MODE AIRLOOP T SW 0.374762 4985.04 3319.03 0.000109
HEAT PUMP COOLING MODE AIRLOOP T NW 0.367726 4878.09 3251.28 0.000107
HEAT PUMP COOLING MODE AIRLOOP T SE 0.324688 4361.67 2896.86 0.000095
HEAT PUMP COOLING MODE AIRLOOP T NE 0.300205 4055.89 2689.85 0.000089
HEAT PUMP COOLING MODE AIRLOOP T N1 0.231458 3200.15 2104.73 0.000070
HEAT PUMP COOLING MODE AIRLOOP T N2 0.230771 3196.55 2100.93 0.000070
HEAT PUMP COOLING MODE AIRLOOP T S1 0.254066 3492.06 2300.04 0.000076
HEAT PUMP COOLING MODE AIRLOOP T S2 0.254454 3496.99 2303.35 0.000076


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.237061 0.237061 0.237061 0.237061 3249.68 3249.68 2219.23 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.235517 0.235517 0.235517 0.235517 3218.01 3218.01 2216.91 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.310027 0.310027 0.310027 0.310027 4223.95 4223.95 2965.88 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.182169 0.182169 0.182169 0.182169 2488.28 2488.28 2213.47 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.135193 0.135193 0.135193 0.135193 1921.73 1921.73 1639.63 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.133984 0.133984 0.133984 0.133984 1906.25 1906.25 1639.54 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.133128 0.133128 0.133128 0.133128 1970.73 1970.73 1638.19 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.138266 0.138266 0.138266 0.138266 2036.19 2036.19 1646.61 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.294151 0.294151 0.294151 0.294151 3965.11 3965.11 2173.66 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.291180 0.291180 0.291180 0.291180 3915.59 3915.59 2168.64 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.263666 0.263666 0.263666 0.263666 3612.81 3612.81 2195.72 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.230733 0.230733 0.230733 0.230733 3107.16 3107.16 2165.11 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.171694 0.171694 0.171694 0.171694 2392.07 2392.07 1466.23 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.170715 0.170715 0.170715 0.170715 2379.58 2379.58 1466.14 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.171193 0.171193 0.171193 0.171193 2454.33 2454.33 1474.04 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.172891 0.172891 0.172891 0.172891 2471.69 2471.69 1475.67 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.294810 0.294810 0.294810 0.294810 3967.89 3967.89 2144.04 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.292316 0.292316 0.292316 0.292316 3924.39 3924.39 2140.67 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.248316 0.248316 0.248316 0.248316 3412.66 3412.66 2144.04 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.233427 0.233427 0.233427 0.233427 3135.87 3135.87 2137.76 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.174390 0.174390 0.174390 0.174390 2423.14 2423.14 1422.00 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.173428 0.173428 0.173428 0.173428 2410.87 2410.87 1421.92 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.173901 0.173901 0.173901 0.173901 2485.63 2485.63 1426.15 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.174602 0.174602 0.174602 0.174602 2490.29 2490.29 1426.35 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.295938 0.295938 0.295938 0.295938 3978.02 3978.02 2156.01 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.293476 0.293476 0.293476 0.293476 3934.90 3934.90 2154.01 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.248453 0.248453 0.248453 0.248453 3410.37 3410.37 2154.00 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.234810 0.234810 0.234810 0.234810 3149.32 3149.32 2151.69 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.176129 0.176129 0.176129 0.176129 2442.83 2442.83 1421.25 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.175178 0.175178 0.175178 0.175178 2430.72 2430.72 1421.18 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.175499 0.175499 0.175499 0.175499 2503.58 2503.58 1423.75 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.176025 0.176025 0.176025 0.176025 2506.01 2506.01 1423.73 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.299542 0.299542 0.299542 0.299542 4020.32 4020.32 2148.27 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.297189 0.297189 0.297189 0.297189 3978.56 3978.56 2146.10 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.252418 0.252418 0.252418 0.252418 3457.37 3457.37 2146.51 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.238645 0.238645 0.238645 0.238645 3194.58 3194.58 2144.31 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.180149 0.180149 0.180149 0.180149 2492.03 2492.03 1404.72 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.179208 0.179208 0.179208 0.179208 2480.05 2480.05 1404.67 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.179323 0.179323 0.179323 0.179323 2550.25 2550.25 1407.33 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.179806 0.179806 0.179806 0.179806 2552.12 2552.12 1407.29 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.295986 0.295986 0.295986 0.295986 3972.31 3972.31 2210.24 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.293544 0.293544 0.293544 0.293544 3929.39 3929.39 2209.79 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.249439 0.249439 0.249439 0.249439 3416.79 3416.79 2208.93 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.235224 0.235224 0.235224 0.235224 3148.43 3148.43 2208.48 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.177036 0.177036 0.177036 0.177036 2450.64 2450.64 1455.64 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.176107 0.176107 0.176107 0.176107 2438.82 2438.82 1455.61 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.176182 0.176182 0.176182 0.176182 2508.70 2508.70 1456.49 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.176659 0.176659 0.176659 0.176659 2514.76 2514.76 1456.46 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.295025 0.295025 0.295025 0.295025 3957.58 3957.58 2246.31 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.292612 0.292612 0.292612 0.292612 3914.99 3914.99 2246.30 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.248964 0.248964 0.248964 0.248964 3408.31 3408.31 2245.43 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.234454 0.234454 0.234454 0.234454 3136.20 3136.20 2245.42 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.176466 0.176466 0.176466 0.176466 2441.88 2441.88 1483.33 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.175548 0.175548 0.175548 0.175548 2430.19 2430.19 1483.31 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.175504 0.175504 0.175504 0.175504 2498.64 2498.64 1483.71 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.175980 0.175980 0.175980 0.175980 2504.70 2504.70 1483.69 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.295647 0.295647 0.295647 0.295647 3963.16 3963.16 2286.68 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.293252 0.293252 0.293252 0.293252 3920.80 3920.80 2286.84 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.249951 0.249951 0.249951 0.249951 3418.62 3418.62 2286.21 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.235159 0.235159 0.235159 0.235159 3142.91 3142.91 2286.37 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.177408 0.177408 0.177408 0.177408 2452.52 2452.52 1516.55 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.176500 0.176500 0.176500 0.176500 2440.97 2440.97 1516.54 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.176299 0.176299 0.176299 0.176299 2507.45 2507.45 1516.73 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.176776 0.176776 0.176776 0.176776 2513.52 2513.52 1516.72 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.305776 0.305776 0.305776 0.305776 4089.45 4089.45 2439.24 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.303429 0.303429 0.303429 0.303429 4047.73 4047.73 2437.35 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.258257 0.258257 0.258257 0.258257 3526.19 3526.19 2439.14 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.243457 0.243457 0.243457 0.243457 3278.03 3278.03 2437.25 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.186676 0.186676 0.186676 0.186676 2569.27 2569.27 1652.87 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.185772 0.185772 0.185772 0.185772 2557.77 2557.77 1652.86 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.183377 0.183377 0.183377 0.183377 2596.17 2596.17 1654.62 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.183819 0.183819 0.183819 0.183819 2601.78 2601.78 1654.62 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.374762 0.374762 0.374762 0.374762 4985.04 4985.04 2990.95 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.367726 0.367726 0.367726 0.367726 4878.09 4878.09 2995.76 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.324688 0.324688 0.324688 0.324688 4361.67 4361.67 2991.15 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.300205 0.300205 0.300205 0.300205 4055.89 4055.89 2995.96 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.231458 0.231458 0.231458 0.231458 3200.15 3200.15 2256.59 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.230771 0.230771 0.230771 0.230771 3196.55 3196.55 2256.60 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.254066 0.254066 0.254066 0.254066 3492.06 3492.06 2248.82 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.254454 0.254454 0.254454 0.254454 3496.99 3496.99 2248.82 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.237061
AIRLOOP G NW SUPPLY FAN 0.235517
AIRLOOP OFFICE SUPPLY FAN 0.310027
AIRLOOP G NE SUPPLY FAN 0.182169
AIRLOOP G N1 SUPPLY FAN 0.135193
AIRLOOP G N2 SUPPLY FAN 0.133984
AIRLOOP G S1 SUPPLY FAN 0.133128
AIRLOOP G S2 SUPPLY FAN 0.138266
AIRLOOP F2 SW SUPPLY FAN 0.294151
AIRLOOP F2 NW SUPPLY FAN 0.291180
AIRLOOP F2 SE SUPPLY FAN 0.263666
AIRLOOP F2 NE SUPPLY FAN 0.230733
AIRLOOP F2 N1 SUPPLY FAN 0.171694
AIRLOOP F2 N2 SUPPLY FAN 0.170715
AIRLOOP F2 S1 SUPPLY FAN 0.171193
AIRLOOP F2 S2 SUPPLY FAN 0.172891
AIRLOOP F3 SW SUPPLY FAN 0.294810
AIRLOOP F3 NW SUPPLY FAN 0.292316
AIRLOOP F3 SE SUPPLY FAN 0.248316
AIRLOOP F3 NE SUPPLY FAN 0.233427
AIRLOOP F3 N1 SUPPLY FAN 0.174390
AIRLOOP F3 N2 SUPPLY FAN 0.173428
AIRLOOP F3 S1 SUPPLY FAN 0.173901
AIRLOOP F3 S2 SUPPLY FAN 0.174602
AIRLOOP F4 SW SUPPLY FAN 0.295938
AIRLOOP F4 NW SUPPLY FAN 0.293476
AIRLOOP F4 SE SUPPLY FAN 0.248453
AIRLOOP F4 NE SUPPLY FAN 0.234810
AIRLOOP F4 N1 SUPPLY FAN 0.176129
AIRLOOP F4 N2 SUPPLY FAN 0.175178
AIRLOOP F4 S1 SUPPLY FAN 0.175499
AIRLOOP F4 S2 SUPPLY FAN 0.176025
AIRLOOP M SW SUPPLY FAN 0.299542
AIRLOOP M NW SUPPLY FAN 0.297189
AIRLOOP M SE SUPPLY FAN 0.252418
AIRLOOP M NE SUPPLY FAN 0.238645
AIRLOOP M N1 SUPPLY FAN 0.180149
AIRLOOP M N2 SUPPLY FAN 0.179208
AIRLOOP M S1 SUPPLY FAN 0.179323
AIRLOOP M S2 SUPPLY FAN 0.179806
AIRLOOP F6 SW SUPPLY FAN 0.295986
AIRLOOP F6 NW SUPPLY FAN 0.293544
AIRLOOP F6 SE SUPPLY FAN 0.249439
AIRLOOP F6 NE SUPPLY FAN 0.235224
AIRLOOP F6 N1 SUPPLY FAN 0.177036
AIRLOOP F6 N2 SUPPLY FAN 0.176107
AIRLOOP F6 S1 SUPPLY FAN 0.176182
AIRLOOP F6 S2 SUPPLY FAN 0.176659
AIRLOOP F7 SW SUPPLY FAN 0.295025
AIRLOOP F7 NW SUPPLY FAN 0.292612
AIRLOOP F7 SE SUPPLY FAN 0.248964
AIRLOOP F7 NE SUPPLY FAN 0.234454
AIRLOOP F7 N1 SUPPLY FAN 0.176466
AIRLOOP F7 N2 SUPPLY FAN 0.175548
AIRLOOP F7 S1 SUPPLY FAN 0.175504
AIRLOOP F7 S2 SUPPLY FAN 0.175980
AIRLOOP F8 SW SUPPLY FAN 0.295647
AIRLOOP F8 NW SUPPLY FAN 0.293252
AIRLOOP F8 SE SUPPLY FAN 0.249951
AIRLOOP F8 NE SUPPLY FAN 0.235159
AIRLOOP F8 N1 SUPPLY FAN 0.177408
AIRLOOP F8 N2 SUPPLY FAN 0.176500
AIRLOOP F8 S1 SUPPLY FAN 0.176299
AIRLOOP F8 S2 SUPPLY FAN 0.176776
AIRLOOP F9 SW SUPPLY FAN 0.305776
AIRLOOP F9 NW SUPPLY FAN 0.303429
AIRLOOP F9 SE SUPPLY FAN 0.258257
AIRLOOP F9 NE SUPPLY FAN 0.243457
AIRLOOP F9 N1 SUPPLY FAN 0.186676
AIRLOOP F9 N2 SUPPLY FAN 0.185772
AIRLOOP F9 S1 SUPPLY FAN 0.183377
AIRLOOP F9 S2 SUPPLY FAN 0.183819
AIRLOOP T SW SUPPLY FAN 0.374762
AIRLOOP T NW SUPPLY FAN 0.367726
AIRLOOP T SE SUPPLY FAN 0.324688
AIRLOOP T NE SUPPLY FAN 0.300205
AIRLOOP T N1 SUPPLY FAN 0.231458
AIRLOOP T N2 SUPPLY FAN 0.230771
AIRLOOP T S1 SUPPLY FAN 0.254066
AIRLOOP T S2 SUPPLY FAN 0.254454


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.237061 3249.68 0.000071
HEAT PUMP HEATING MODE AIRLOOP G NW 0.235517 3218.01 0.000070
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.310027 4223.95 0.000092
HEAT PUMP HEATING MODE AIRLOOP G NE 0.182169 2488.28 0.000054
HEAT PUMP HEATING MODE AIRLOOP G N1 0.135193 1921.73 0.000042
HEAT PUMP HEATING MODE AIRLOOP G N2 0.133984 1906.25 0.000042
HEAT PUMP HEATING MODE AIRLOOP G S1 0.133128 1970.73 0.000043
HEAT PUMP HEATING MODE AIRLOOP G S2 0.138266 2036.19 0.000044
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.294151 3965.11 0.000087
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.291180 3915.59 0.000086
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.263666 3612.81 0.000079
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.230733 3107.16 0.000068
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.171694 2392.07 0.000052
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.170715 2379.58 0.000052
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.171193 2454.33 0.000054
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.172891 2471.69 0.000054
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.294810 3967.89 0.000087
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.292316 3924.39 0.000086
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.248316 3412.66 0.000075
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.233427 3135.87 0.000069
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.174390 2423.14 0.000053
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.173428 2410.87 0.000053
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.173901 2485.63 0.000054
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.174602 2490.29 0.000054
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.295938 3978.02 0.000087
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.293476 3934.90 0.000086
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.248453 3410.37 0.000074
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.234810 3149.32 0.000069
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.176129 2442.83 0.000053
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.175178 2430.72 0.000053
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.175499 2503.58 0.000055
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.176025 2506.01 0.000055
HEAT PUMP HEATING MODE AIRLOOP M SW 0.299542 4020.32 0.000088
HEAT PUMP HEATING MODE AIRLOOP M NW 0.297189 3978.56 0.000087
HEAT PUMP HEATING MODE AIRLOOP M SE 0.252418 3457.37 0.000076
HEAT PUMP HEATING MODE AIRLOOP M NE 0.238645 3194.58 0.000070
HEAT PUMP HEATING MODE AIRLOOP M N1 0.180149 2492.03 0.000054
HEAT PUMP HEATING MODE AIRLOOP M N2 0.179208 2480.05 0.000054
HEAT PUMP HEATING MODE AIRLOOP M S1 0.179323 2550.25 0.000056
HEAT PUMP HEATING MODE AIRLOOP M S2 0.179806 2552.12 0.000056
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.295986 3972.31 0.000087
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.293544 3929.39 0.000086
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.249439 3416.79 0.000075
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.235224 3148.43 0.000069
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.177036 2450.64 0.000054
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.176107 2438.82 0.000053
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.176182 2508.70 0.000055
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.176659 2514.76 0.000055
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.295025 3957.58 0.000086
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.292612 3914.99 0.000086
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.248964 3408.31 0.000074
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.234454 3136.20 0.000069
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.176466 2441.88 0.000053
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.175548 2430.19 0.000053
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.175504 2498.64 0.000055
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.175980 2504.70 0.000055
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.295647 3963.16 0.000087
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.293252 3920.80 0.000086
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.249951 3418.62 0.000075
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.235159 3142.91 0.000069
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.177408 2452.52 0.000054
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.176500 2440.97 0.000053
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.176299 2507.45 0.000055
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.176776 2513.52 0.000055
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.305776 4089.45 0.000089
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.303429 4047.73 0.000088
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.258257 3526.19 0.000077
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.243457 3278.03 0.000072
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.186676 2569.27 0.000056
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.185772 2557.77 0.000056
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.183377 2596.17 0.000057
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.183819 2601.78 0.000057
HEAT PUMP HEATING MODE AIRLOOP T SW 0.374762 4985.04 0.000109
HEAT PUMP HEATING MODE AIRLOOP T NW 0.367726 4878.09 0.000107
HEAT PUMP HEATING MODE AIRLOOP T SE 0.324688 4361.67 0.000095
HEAT PUMP HEATING MODE AIRLOOP T NE 0.300205 4055.89 0.000089
HEAT PUMP HEATING MODE AIRLOOP T N1 0.231458 3200.15 0.000070
HEAT PUMP HEATING MODE AIRLOOP T N2 0.230771 3196.55 0.000070
HEAT PUMP HEATING MODE AIRLOOP T S1 0.254066 3492.06 0.000076
HEAT PUMP HEATING MODE AIRLOOP T S2 0.254454 3496.99 0.000076


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 2219.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 2216.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 2965.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 2213.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 1639.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 1639.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 1638.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 1646.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 2173.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 2168.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 2195.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 2165.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1466.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1466.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1474.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1475.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 2144.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 2140.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 2144.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 2137.76
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1422.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1421.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1426.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1426.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 2156.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 2154.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 2154.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 2151.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1421.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1421.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1423.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1423.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 2148.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 2146.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 2146.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 2144.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1404.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1404.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1407.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1407.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 2210.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 2209.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 2208.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 2208.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1455.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1455.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1456.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1456.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 2246.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 2246.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 2245.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 2245.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1483.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1483.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1483.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1483.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 2286.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 2286.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 2286.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 2286.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 1516.55
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 1516.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 1516.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 1516.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 2439.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 2437.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 2439.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 2437.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 1652.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 1652.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 1654.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 1654.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 2990.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 2995.76
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 2991.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 2995.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 2256.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 2256.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 2248.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 2248.82


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.005431 6.11


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.005431


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.005431 2621.67 7.96 7048.30


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.005431 1385.13



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.87 8.14
February 23.05 10.27
March 23.21 12.55
April 23.90 19.23
May 24.24 23.84
June 24.39 27.86
July 24.40 27.54
August 24.39 26.28
September 24.35 23.38
October 24.09 18.30
November 23.35 11.18
December 22.83 6.79
     
Annual Sum or Average 23.76 17.98
Minimum of Months 22.83 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 8.14
February 22.26 10.27
March 22.67 12.55
April 23.79 19.23
May 24.25 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.34 23.38
October 23.85 18.30
November 22.52 11.18
December 21.94 6.79
     
Annual Sum or Average 23.40 17.98
Minimum of Months 21.94 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.81 8.14
February 23.10 10.27
March 23.33 12.55
April 24.05 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.10 18.30
November 23.27 11.18
December 22.76 6.79
     
Annual Sum or Average 23.78 17.98
Minimum of Months 22.76 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 8.14
February 22.20 10.27
March 22.62 12.55
April 23.81 19.23
May 24.26 23.84
June 24.39 27.86
July 24.42 27.54
August 24.39 26.28
September 24.34 23.38
October 23.77 18.30
November 22.39 11.18
December 21.85 6.79
     
Annual Sum or Average 23.37 17.98
Minimum of Months 21.85 6.79
Maximum of Months 24.42 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 8.14
February 22.10 10.27
March 22.43 12.55
April 23.65 19.23
May 24.20 23.84
June 24.39 27.86
July 24.41 27.54
August 24.38 26.28
September 24.32 23.38
October 23.70 18.30
November 22.31 11.18
December 21.84 6.79
     
Annual Sum or Average 23.31 17.98
Minimum of Months 21.84 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 8.14
February 22.10 10.27
March 22.43 12.55
April 23.65 19.23
May 24.20 23.84
June 24.39 27.86
July 24.41 27.54
August 24.38 26.28
September 24.32 23.38
October 23.69 18.30
November 22.30 11.18
December 21.84 6.79
     
Annual Sum or Average 23.30 17.98
Minimum of Months 21.84 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.96 8.14
February 23.10 10.27
March 23.18 12.55
April 23.82 19.23
May 24.20 23.84
June 24.39 27.86
July 24.40 27.54
August 24.39 26.28
September 24.41 23.38
October 24.06 18.30
November 23.41 11.18
December 22.91 6.79
     
Annual Sum or Average 23.77 17.98
Minimum of Months 22.91 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.98 8.14
February 23.14 10.27
March 23.21 12.55
April 23.85 19.23
May 24.21 23.84
June 24.39 27.86
July 24.40 27.54
August 24.39 26.28
September 24.40 23.38
October 24.08 18.30
November 23.43 11.18
December 22.94 6.79
     
Annual Sum or Average 23.79 17.98
Minimum of Months 22.94 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.90 8.14
February 20.62 10.27
March 21.40 12.55
April 23.53 19.23
May 24.98 23.84
June 26.67 27.86
July 26.67 27.54
August 26.33 26.28
September 25.71 23.38
October 23.48 18.30
November 21.10 11.18
December 19.60 6.79
     
Annual Sum or Average 23.35 17.98
Minimum of Months 19.60 6.79
Maximum of Months 26.67 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.59 8.14
February 23.79 10.27
March 23.97 12.55
April 24.25 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.38 23.38
October 24.36 18.30
November 23.97 11.18
December 23.48 6.79
     
Annual Sum or Average 24.11 17.98
Minimum of Months 23.48 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.35 8.14
February 22.82 10.27
March 23.40 12.55
April 24.17 19.23
May 24.35 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.25 18.30
November 23.18 11.18
December 22.22 6.79
     
Annual Sum or Average 23.70 17.98
Minimum of Months 22.22 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.57 8.14
February 23.82 10.27
March 23.99 12.55
April 24.29 19.23
May 24.38 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.40 23.38
October 24.36 18.30
November 23.96 11.18
December 23.50 6.79
     
Annual Sum or Average 24.12 17.98
Minimum of Months 23.50 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 8.14
February 22.74 10.27
March 23.33 12.55
April 24.18 19.23
May 24.37 23.84
June 24.40 27.86
July 24.41 27.54
August 24.39 26.28
September 24.38 23.38
October 24.21 18.30
November 23.02 11.18
December 22.11 6.79
     
Annual Sum or Average 23.65 17.98
Minimum of Months 22.11 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.29 8.14
February 22.73 10.27
March 23.26 12.55
April 24.11 19.23
May 24.34 23.84
June 24.40 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.20 18.30
November 23.06 11.18
December 22.17 6.79
     
Annual Sum or Average 23.65 17.98
Minimum of Months 22.17 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 8.14
February 22.73 10.27
March 23.25 12.55
April 24.11 19.23
May 24.34 23.84
June 24.40 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.20 18.30
November 23.04 11.18
December 22.16 6.79
     
Annual Sum or Average 23.64 17.98
Minimum of Months 22.16 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.80 8.14
February 23.93 10.27
March 24.01 12.55
April 24.22 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.38 18.30
November 24.07 11.18
December 23.72 6.79
     
Annual Sum or Average 24.18 17.98
Minimum of Months 23.72 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.81 8.14
February 23.94 10.27
March 24.02 12.55
April 24.23 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.38 18.30
November 24.07 11.18
December 23.73 6.79
     
Annual Sum or Average 24.18 17.98
Minimum of Months 23.73 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.69 8.14
February 24.16 10.27
March 24.65 12.55
April 25.67 19.23
May 26.22 23.84
June 26.74 27.86
July 26.72 27.54
August 26.63 26.28
September 26.49 23.38
October 25.78 18.30
November 24.53 11.18
December 23.54 6.79
     
Annual Sum or Average 25.41 17.98
Minimum of Months 23.54 6.79
Maximum of Months 26.74 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 8.14
February 23.90 10.27
March 24.06 12.55
April 24.27 19.23
May 24.36 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.38 23.38
October 24.37 18.30
November 24.06 11.18
December 23.63 6.79
     
Annual Sum or Average 24.16 17.98
Minimum of Months 23.63 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.51 8.14
February 22.99 10.27
March 23.57 12.55
April 24.20 19.23
May 24.35 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.29 18.30
November 23.38 11.18
December 22.33 6.79
     
Annual Sum or Average 23.77 17.98
Minimum of Months 22.33 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.66 8.14
February 23.88 10.27
March 24.03 12.55
April 24.28 19.23
May 24.37 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.41 23.38
October 24.37 18.30
November 24.01 11.18
December 23.58 6.79
     
Annual Sum or Average 24.15 17.98
Minimum of Months 23.58 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.30 8.14
February 22.92 10.27
March 23.51 12.55
April 24.21 19.23
May 24.37 23.84
June 24.41 27.86
July 24.41 27.54
August 24.40 26.28
September 24.38 23.38
October 24.26 18.30
November 23.22 11.18
December 22.21 6.79
     
Annual Sum or Average 23.72 17.98
Minimum of Months 22.21 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 8.14
February 22.98 10.27
March 23.51 12.55
April 24.17 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.26 18.30
November 23.34 11.18
December 22.35 6.79
     
Annual Sum or Average 23.76 17.98
Minimum of Months 22.35 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.51 8.14
February 22.98 10.27
March 23.50 12.55
April 24.17 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.25 18.30
November 23.32 11.18
December 22.35 6.79
     
Annual Sum or Average 23.75 17.98
Minimum of Months 22.35 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.99 8.14
February 24.08 10.27
March 24.14 12.55
April 24.26 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.18 11.18
December 23.90 6.79
     
Annual Sum or Average 24.25 17.98
Minimum of Months 23.90 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.99 8.14
February 24.08 10.27
March 24.14 12.55
April 24.26 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.18 11.18
December 23.90 6.79
     
Annual Sum or Average 24.25 17.98
Minimum of Months 23.90 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 8.14
February 24.67 10.27
March 25.15 12.55
April 26.01 19.23
May 26.46 23.84
June 26.81 27.86
July 26.78 27.54
August 26.69 26.28
September 26.59 23.38
October 26.11 18.30
November 25.03 11.18
December 24.05 6.79
     
Annual Sum or Average 25.72 17.98
Minimum of Months 24.05 6.79
Maximum of Months 26.81 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 8.14
February 23.92 10.27
March 24.08 12.55
April 24.27 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.37 18.30
November 24.07 11.18
December 23.65 6.79
     
Annual Sum or Average 24.17 17.98
Minimum of Months 23.65 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.58 8.14
February 23.03 10.27
March 23.61 12.55
April 24.20 19.23
May 24.35 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.29 18.30
November 23.43 11.18
December 22.38 6.79
     
Annual Sum or Average 23.79 17.98
Minimum of Months 22.38 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.68 8.14
February 23.88 10.27
March 24.04 12.55
April 24.28 19.23
May 24.37 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.41 23.38
October 24.37 18.30
November 24.01 11.18
December 23.59 6.79
     
Annual Sum or Average 24.15 17.98
Minimum of Months 23.59 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.36 8.14
February 22.96 10.27
March 23.55 12.55
April 24.21 19.23
May 24.37 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.38 23.38
October 24.27 18.30
November 23.28 11.18
December 22.25 6.79
     
Annual Sum or Average 23.74 17.98
Minimum of Months 22.25 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.66 8.14
February 23.07 10.27
March 23.59 12.55
April 24.18 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.27 18.30
November 23.44 11.18
December 22.44 6.79
     
Annual Sum or Average 23.80 17.98
Minimum of Months 22.44 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.63 8.14
February 23.07 10.27
March 23.59 12.55
April 24.18 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.27 18.30
November 23.43 11.18
December 22.43 6.79
     
Annual Sum or Average 23.80 17.98
Minimum of Months 22.43 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.04 8.14
February 24.10 10.27
March 24.17 12.55
April 24.26 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.20 11.18
December 23.94 6.79
     
Annual Sum or Average 24.26 17.98
Minimum of Months 23.94 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.03 8.14
February 24.10 10.27
March 24.17 12.55
April 24.26 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.20 11.18
December 23.94 6.79
     
Annual Sum or Average 24.26 17.98
Minimum of Months 23.94 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.42 8.14
February 24.86 10.27
March 25.34 12.55
April 26.14 19.23
May 26.57 23.84
June 26.90 27.86
July 26.86 27.54
August 26.78 26.28
September 26.68 23.38
October 26.24 18.30
November 25.23 11.18
December 24.25 6.79
     
Annual Sum or Average 25.86 17.98
Minimum of Months 24.25 6.79
Maximum of Months 26.90 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 8.14
February 23.91 10.27
March 24.07 12.55
April 24.26 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.39 23.38
October 24.37 18.30
November 24.07 11.18
December 23.66 6.79
     
Annual Sum or Average 24.17 17.98
Minimum of Months 23.66 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.61 8.14
February 23.05 10.27
March 23.60 12.55
April 24.19 19.23
May 24.35 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.29 18.30
November 23.45 11.18
December 22.41 6.79
     
Annual Sum or Average 23.80 17.98
Minimum of Months 22.41 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.69 8.14
February 23.88 10.27
March 24.03 12.55
April 24.27 19.23
May 24.37 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.41 23.38
October 24.37 18.30
November 24.02 11.18
December 23.60 6.79
     
Annual Sum or Average 24.15 17.98
Minimum of Months 23.60 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 8.14
February 22.98 10.27
March 23.55 12.55
April 24.20 19.23
May 24.37 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.38 23.38
October 24.27 18.30
November 23.30 11.18
December 22.28 6.79
     
Annual Sum or Average 23.75 17.98
Minimum of Months 22.28 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.72 8.14
February 23.11 10.27
March 23.62 12.55
April 24.18 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.27 18.30
November 23.49 11.18
December 22.50 6.79
     
Annual Sum or Average 23.82 17.98
Minimum of Months 22.50 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 8.14
February 23.11 10.27
March 23.61 12.55
April 24.18 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.27 18.30
November 23.47 11.18
December 22.49 6.79
     
Annual Sum or Average 23.81 17.98
Minimum of Months 22.49 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.05 8.14
February 24.11 10.27
March 24.17 12.55
April 24.26 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.21 11.18
December 23.96 6.79
     
Annual Sum or Average 24.26 17.98
Minimum of Months 23.96 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.05 8.14
February 24.11 10.27
March 24.17 12.55
April 24.26 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.41 18.30
November 24.21 11.18
December 23.95 6.79
     
Annual Sum or Average 24.26 17.98
Minimum of Months 23.95 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.07 8.14
February 25.49 10.27
March 25.95 12.55
April 26.73 19.23
May 27.16 23.84
June 27.49 27.86
July 27.45 27.54
August 27.37 26.28
September 27.28 23.38
October 26.85 18.30
November 25.87 11.18
December 24.90 6.79
     
Annual Sum or Average 26.47 17.98
Minimum of Months 24.90 6.79
Maximum of Months 27.49 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.68 8.14
February 23.84 10.27
March 24.00 12.55
April 24.23 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.36 18.30
November 24.02 11.18
December 23.58 6.79
     
Annual Sum or Average 24.14 17.98
Minimum of Months 23.58 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.48 8.14
February 22.92 10.27
March 23.49 12.55
April 24.15 19.23
May 24.34 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.27 18.30
November 23.33 11.18
December 22.32 6.79
     
Annual Sum or Average 23.74 17.98
Minimum of Months 22.32 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.60 8.14
February 23.81 10.27
March 23.97 12.55
April 24.24 19.23
May 24.36 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.41 23.38
October 24.36 18.30
November 23.96 11.18
December 23.52 6.79
     
Annual Sum or Average 24.12 17.98
Minimum of Months 23.52 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 8.14
February 22.85 10.27
March 23.43 12.55
April 24.17 19.23
May 24.36 23.84
June 24.41 27.86
July 24.42 27.54
August 24.39 26.28
September 24.38 23.38
October 24.24 18.30
November 23.18 11.18
December 22.19 6.79
     
Annual Sum or Average 23.70 17.98
Minimum of Months 22.19 6.79
Maximum of Months 24.42 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.59 8.14
February 22.98 10.27
March 23.50 12.55
April 24.14 19.23
May 24.33 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.25 18.30
November 23.37 11.18
December 22.39 6.79
     
Annual Sum or Average 23.76 17.98
Minimum of Months 22.39 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.56 8.14
February 22.98 10.27
March 23.50 12.55
April 24.14 19.23
May 24.33 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.25 18.30
November 23.36 11.18
December 22.38 6.79
     
Annual Sum or Average 23.76 17.98
Minimum of Months 22.38 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.99 8.14
February 24.06 10.27
March 24.11 12.55
April 24.23 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.43 23.38
October 24.40 18.30
November 24.17 11.18
December 23.90 6.79
     
Annual Sum or Average 24.24 17.98
Minimum of Months 23.90 6.79
Maximum of Months 24.43 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.99 8.14
February 24.06 10.27
March 24.11 12.55
April 24.23 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.44 23.38
October 24.40 18.30
November 24.17 11.18
December 23.90 6.79
     
Annual Sum or Average 24.23 17.98
Minimum of Months 23.90 6.79
Maximum of Months 24.44 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 8.14
February 24.78 10.27
March 25.25 12.55
April 26.09 19.23
May 26.55 23.84
June 26.89 27.86
July 26.85 27.54
August 26.76 26.28
September 26.66 23.38
October 26.22 18.30
November 25.17 11.18
December 24.19 6.79
     
Annual Sum or Average 25.82 17.98
Minimum of Months 24.19 6.79
Maximum of Months 26.89 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.61 8.14
February 23.78 10.27
March 23.94 12.55
April 24.20 19.23
May 24.34 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.35 18.30
November 23.98 11.18
December 23.52 6.79
     
Annual Sum or Average 24.11 17.98
Minimum of Months 23.52 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 8.14
February 22.83 10.27
March 23.39 12.55
April 24.12 19.23
May 24.34 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.26 18.30
November 23.25 11.18
December 22.26 6.79
     
Annual Sum or Average 23.70 17.98
Minimum of Months 22.26 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.53 8.14
February 23.75 10.27
March 23.91 12.55
April 24.22 19.23
May 24.36 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.40 23.38
October 24.35 18.30
November 23.93 11.18
December 23.46 6.79
     
Annual Sum or Average 24.09 17.98
Minimum of Months 23.46 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.21 8.14
February 22.76 10.27
March 23.34 12.55
April 24.14 19.23
May 24.35 23.84
June 24.41 27.86
July 24.42 27.54
August 24.39 26.28
September 24.38 23.38
October 24.22 18.30
November 23.08 11.18
December 22.14 6.79
     
Annual Sum or Average 23.66 17.98
Minimum of Months 22.14 6.79
Maximum of Months 24.42 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.48 8.14
February 22.88 10.27
March 23.40 12.55
April 24.11 19.23
May 24.32 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.23 18.30
November 23.28 11.18
December 22.31 6.79
     
Annual Sum or Average 23.72 17.98
Minimum of Months 22.31 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 8.14
February 22.88 10.27
March 23.40 12.55
April 24.11 19.23
May 24.32 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.23 18.30
November 23.26 11.18
December 22.30 6.79
     
Annual Sum or Average 23.72 17.98
Minimum of Months 22.30 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.93 8.14
February 24.01 10.27
March 24.06 12.55
April 24.21 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.43 23.38
October 24.39 18.30
November 24.14 11.18
December 23.85 6.79
     
Annual Sum or Average 24.21 17.98
Minimum of Months 23.85 6.79
Maximum of Months 24.43 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.93 8.14
February 24.01 10.27
March 24.06 12.55
April 24.21 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.40 26.28
September 24.43 23.38
October 24.39 18.30
November 24.14 11.18
December 23.85 6.79
     
Annual Sum or Average 24.21 17.98
Minimum of Months 23.85 6.79
Maximum of Months 24.43 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 8.14
February 24.61 10.27
March 25.07 12.55
April 25.97 19.23
May 26.46 23.84
June 26.81 27.86
July 26.77 27.54
August 26.68 26.28
September 26.58 23.38
October 26.11 18.30
November 25.00 11.18
December 24.02 6.79
     
Annual Sum or Average 25.69 17.98
Minimum of Months 24.02 6.79
Maximum of Months 26.81 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.53 8.14
February 23.72 10.27
March 23.88 12.55
April 24.18 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.34 18.30
November 23.94 11.18
December 23.45 6.79
     
Annual Sum or Average 24.08 17.98
Minimum of Months 23.45 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 8.14
February 22.75 10.27
March 23.30 12.55
April 24.10 19.23
May 24.33 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.24 18.30
November 23.16 11.18
December 22.20 6.79
     
Annual Sum or Average 23.67 17.98
Minimum of Months 22.20 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.45 8.14
February 23.69 10.27
March 23.86 12.55
April 24.20 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.40 23.38
October 24.34 18.30
November 23.89 11.18
December 23.40 6.79
     
Annual Sum or Average 24.06 17.98
Minimum of Months 23.40 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.15 8.14
February 22.69 10.27
March 23.25 12.55
April 24.12 19.23
May 24.35 23.84
June 24.41 27.86
July 24.42 27.54
August 24.39 26.28
September 24.37 23.38
October 24.20 18.30
November 23.00 11.18
December 22.09 6.79
     
Annual Sum or Average 23.62 17.98
Minimum of Months 22.09 6.79
Maximum of Months 24.42 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 8.14
February 22.79 10.27
March 23.31 12.55
April 24.09 19.23
May 24.32 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.22 18.30
November 23.18 11.18
December 22.24 6.79
     
Annual Sum or Average 23.68 17.98
Minimum of Months 22.24 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.36 8.14
February 22.79 10.27
March 23.30 12.55
April 24.09 19.23
May 24.32 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.21 18.30
November 23.16 11.18
December 22.23 6.79
     
Annual Sum or Average 23.67 17.98
Minimum of Months 22.23 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.87 8.14
February 23.96 10.27
March 24.01 12.55
April 24.19 19.23
May 24.32 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.43 23.38
October 24.38 18.30
November 24.10 11.18
December 23.79 6.79
     
Annual Sum or Average 24.19 17.98
Minimum of Months 23.79 6.79
Maximum of Months 24.43 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.86 8.14
February 23.96 10.27
March 24.01 12.55
April 24.19 19.23
May 24.32 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.43 23.38
October 24.38 18.30
November 24.10 11.18
December 23.79 6.79
     
Annual Sum or Average 24.19 17.98
Minimum of Months 23.79 6.79
Maximum of Months 24.43 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.04 8.14
February 24.49 10.27
March 24.95 12.55
April 25.92 19.23
May 26.44 23.84
June 26.81 27.86
July 26.78 27.54
August 26.68 26.28
September 26.57 23.38
October 26.07 18.30
November 24.89 11.18
December 23.91 6.79
     
Annual Sum or Average 25.63 17.98
Minimum of Months 23.91 6.79
Maximum of Months 26.81 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 8.14
February 23.61 10.27
March 23.78 12.55
April 24.15 19.23
May 24.33 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.38 23.38
October 24.33 18.30
November 23.86 11.18
December 23.33 6.79
     
Annual Sum or Average 24.03 17.98
Minimum of Months 23.33 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.24 8.14
February 22.67 10.27
March 23.19 12.55
April 24.07 19.23
May 24.33 23.84
June 24.41 27.86
July 24.40 27.54
August 24.39 26.28
September 24.37 23.38
October 24.22 18.30
November 23.05 11.18
December 22.15 6.79
     
Annual Sum or Average 23.63 17.98
Minimum of Months 22.15 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 8.14
February 23.58 10.27
March 23.76 12.55
April 24.17 19.23
May 24.35 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.39 23.38
October 24.32 18.30
November 23.81 11.18
December 23.28 6.79
     
Annual Sum or Average 24.02 17.98
Minimum of Months 23.28 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.08 8.14
February 22.60 10.27
March 23.14 12.55
April 24.09 19.23
May 24.34 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.37 23.38
October 24.17 18.30
November 22.88 11.18
December 22.04 6.79
     
Annual Sum or Average 23.58 17.98
Minimum of Months 22.04 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.26 8.14
February 22.68 10.27
March 23.18 12.55
April 24.06 19.23
May 24.31 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.19 18.30
November 23.03 11.18
December 22.15 6.79
     
Annual Sum or Average 23.62 17.98
Minimum of Months 22.15 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.25 8.14
February 22.68 10.27
March 23.18 12.55
April 24.06 19.23
May 24.31 23.84
June 24.41 27.86
July 24.41 27.54
August 24.39 26.28
September 24.36 23.38
October 24.19 18.30
November 23.02 11.18
December 22.14 6.79
     
Annual Sum or Average 23.62 17.98
Minimum of Months 22.14 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.72 8.14
February 23.86 10.27
March 23.91 12.55
April 24.16 19.23
May 24.32 23.84
June 24.40 27.86
July 24.41 27.54
August 24.39 26.28
September 24.41 23.38
October 24.36 18.30
November 24.02 11.18
December 23.65 6.79
     
Annual Sum or Average 24.13 17.98
Minimum of Months 23.65 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.72 8.14
February 23.86 10.27
March 23.91 12.55
April 24.16 19.23
May 24.32 23.84
June 24.40 27.86
July 24.40 27.54
August 24.39 26.28
September 24.41 23.38
October 24.36 18.30
November 24.02 11.18
December 23.65 6.79
     
Annual Sum or Average 24.13 17.98
Minimum of Months 23.65 6.79
Maximum of Months 24.41 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.83 8.14
February 24.31 10.27
March 24.78 12.55
April 25.90 19.23
May 26.49 23.84
June 26.92 27.86
July 26.88 27.54
August 26.77 26.28
September 26.62 23.38
October 26.03 18.30
November 24.70 11.18
December 23.70 6.79
     
Annual Sum or Average 25.58 17.98
Minimum of Months 23.70 6.79
Maximum of Months 26.92 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 8.14
February 23.23 10.27
March 23.38 12.55
April 24.00 19.23
May 24.28 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.34 23.38
October 24.19 18.30
November 23.46 11.18
December 22.97 6.79
     
Annual Sum or Average 23.84 17.98
Minimum of Months 22.97 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 8.14
February 22.61 10.27
March 22.96 12.55
April 23.92 19.23
May 24.28 23.84
June 24.40 27.86
July 24.40 27.54
August 24.38 26.28
September 24.33 23.38
October 24.03 18.30
November 22.87 11.18
December 22.25 6.79
     
Annual Sum or Average 23.57 17.98
Minimum of Months 22.25 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.98 8.14
February 23.21 10.27
March 23.39 12.55
April 24.03 19.23
May 24.31 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.36 23.38
October 24.16 18.30
November 23.42 11.18
December 22.96 6.79
     
Annual Sum or Average 23.83 17.98
Minimum of Months 22.96 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.15 8.14
February 22.56 10.27
March 22.95 12.55
April 23.95 19.23
May 24.30 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.34 23.38
October 23.97 18.30
November 22.75 11.18
December 22.10 6.79
     
Annual Sum or Average 23.52 17.98
Minimum of Months 22.10 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.21 8.14
February 22.55 10.27
March 22.91 12.55
April 23.91 19.23
May 24.27 23.84
June 24.40 27.86
July 24.40 27.54
August 24.38 26.28
September 24.32 23.38
October 24.02 18.30
November 22.79 11.18
December 22.14 6.79
     
Annual Sum or Average 23.53 17.98
Minimum of Months 22.14 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.20 8.14
February 22.55 10.27
March 22.91 12.55
April 23.91 19.23
May 24.27 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.32 23.38
October 24.02 18.30
November 22.78 11.18
December 22.13 6.79
     
Annual Sum or Average 23.53 17.98
Minimum of Months 22.13 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 8.14
February 23.41 10.27
March 23.50 12.55
April 24.02 19.23
May 24.28 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.37 23.38
October 24.25 18.30
November 23.61 11.18
December 23.14 6.79
     
Annual Sum or Average 23.91 17.98
Minimum of Months 23.14 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 8.14
February 23.40 10.27
March 23.50 12.55
April 24.02 19.23
May 24.28 23.84
June 24.39 27.86
July 24.40 27.54
August 24.38 26.28
September 24.37 23.38
October 24.24 18.30
November 23.61 11.18
December 23.14 6.79
     
Annual Sum or Average 23.91 17.98
Minimum of Months 23.14 6.79
Maximum of Months 24.40 27.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 8.14
February 24.35 10.27
March 24.89 12.55
April 26.37 19.23
May 27.18 23.84
June 27.82 27.86
July 27.79 27.54
August 27.61 26.28
September 27.31 23.38
October 26.42 18.30
November 24.72 11.18
December 23.58 6.79
     
Annual Sum or Average 25.99 17.98
Minimum of Months 23.58 6.79
Maximum of Months 27.82 27.86



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:17

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.221720E+12 123965.794 02-JAN-18:15 22204.399 56867.515 20322.080 0.000 10887.635 10720.100 1422.056 396.374 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.199686E+12 129919.711 20-FEB-18:15 22204.399 56867.515 20322.080 0.000 16621.958 10720.100 1422.056 615.968 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.219484E+12 142203.164 14-MAR-17:15 22204.399 56867.515 20322.080 0.000 38992.665 0.000 1422.056 1248.814 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.249050E+12 166075.200 21-APR-19:30 25049.151 49704.829 20322.080 0.000 56265.373 10720.100 1422.056 1646.039 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.286695E+12 166454.780 27-MAY-19:15 25049.151 49704.829 20322.080 0.000 56398.302 10720.100 1422.056 1892.691 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.307967E+12 170699.538 19-JUN-19:30 25049.151 49704.829 20322.080 0.000 60441.163 10720.100 1422.056 2094.588 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.330114E+12 172060.798 17-JUL-19:00 25049.151 49704.829 20322.080 0.000 61623.927 10720.100 1422.056 2273.083 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.314640E+12 170633.223 07-AUG-18:00 25049.151 51564.864 20322.080 0.000 58484.893 10720.100 1422.056 2055.466 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.291957E+12 167060.769 15-SEP-18:30 25049.151 51564.864 20322.080 0.000 55021.227 10720.100 1422.056 1946.678 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.257615E+12 167466.101 04-OCT-17:45 22204.399 56867.515 20322.080 0.000 52749.096 10720.100 1422.056 2034.966 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.218912E+12 132600.551 03-NOV-16:15 18221.747 56933.809 20322.080 0.000 33237.638 0.000 1422.056 1314.917 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.222992E+12 123000.158 07-DEC-18:00 22204.399 56867.515 20322.080 0.000 9970.489 10720.100 1422.056 347.631 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.312083E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.199686E+12 123000.158   18221.747 49704.829 20322.080 0.000 9970.489 0.000 1422.056 347.631 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.330114E+12 172060.798   25049.151 56933.809 20322.080 0.000 61623.927 10720.100 1422.056 2273.083 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:17

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.102867E+12 130846.030 27-JAN-07:45 0.000 0.000 0.000 130846.030 83854.880 83854.880 46991.150
February 0.916185E+11 122948.240 02-FEB-06:00 0.000 0.000 0.000 122948.240 80148.585 80148.585 42799.656
March 0.951894E+11 109179.837 02-MAR-07:30 0.000 0.000 0.000 109179.837 83038.893 83038.893 26140.944
April 0.853551E+11 81506.640 02-APR-06:45 0.000 0.000 0.000 81506.640 81506.640 81506.640 0.000
May 0.809973E+11 79473.733 01-MAY-06:00 0.000 0.000 0.000 79473.733 79473.733 79473.733 0.000
June 0.723494E+11 77189.888 05-JUN-06:00 0.000 0.000 0.000 77189.888 77189.888 77189.888 0.000
July 0.711767E+11 75763.954 11-JUL-06:00 0.000 0.000 0.000 75763.954 75763.954 75763.954 0.000
August 0.712052E+11 75885.391 25-AUG-06:00 0.000 0.000 0.000 75885.391 75885.391 75885.391 0.000
September 0.724190E+11 77341.751 28-SEP-06:00 0.000 0.000 0.000 77341.751 77341.751 77341.751 0.000
October 0.811183E+11 79429.009 30-OCT-06:00 0.000 0.000 0.000 79429.009 79429.009 79429.009 0.000
November 0.873252E+11 113818.082 28-NOV-06:00 0.000 0.000 0.000 113818.082 79554.230 79554.230 34263.853
December 0.103623E+12 142092.631 27-DEC-07:30 0.000 0.000 0.000 142092.631 82933.344 82933.344 59159.287
                     
Annual Sum or Average 0.101524E+13     0.000 0.000 0.000        
Minimum of Months 0.711767E+11 75763.954   0.000 0.000 0.000 75763.954 75763.954 75763.954 0.000
Maximum of Months 0.103623E+12 142092.631   0.000 0.000 0.000 142092.631 83854.880 83854.880 59159.287