Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2018-10-19 09:40:09


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4300.65 548.80 609.17
Net Site Energy 4300.65 548.80 609.17
Total Source Energy 10995.15 1403.07 1557.41
Net Source Energy 10995.15 1403.07 1557.41


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 74.33 229.94 0.00 0.00 0.00 0.00
Cooling 606.11 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.68 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 546.99 0.00 0.00 0.00 0.00 0.00
Pumps 48.82 0.00 0.00 0.00 0.00 0.00
Heat Rejection 27.19 0.00 0.00 0.00 0.00 1647.96
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1030.26 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3040.45 1260.20 0.00 0.00 0.00 6426.48
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 229.94 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 74.33 0.00 0.00 0.00 0.00 0.00
Cooling General 606.11 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.68 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 546.99 0.00 0.00 0.00 0.00 0.00
Pumps General 48.82 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 27.19 0.00 0.00 0.00 0.00 1647.96
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1030.26 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.88 0.00 0.00 0.00 0.00 0.00
HVAC 184.63 178.50 0.00 0.00 0.00 0.91
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 430.66 178.50 0.00 0.00 0.00 0.91


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.66 0.00 0.00 0.00 0.00 0.00
HVAC 166.33 160.81 0.00 0.00 0.00 0.82
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 387.99 160.81 0.00 0.00 0.00 0.82


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3040.45 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3040.45 100.00
     
Total On-Site and Utility Electric Sources 3040.45 100.00
Total Electricity End Uses 3040.45 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6426.48 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6426.48 100.00
Total Water End Uses 6426.48 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 90.75
Time Setpoint Not Met During Occupied Cooling 176.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2544.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JUL-19:00 12-FEB-06:45 - - - 01-AUG-17:15
Heating 0.00 196926.82 0.00 0.00 0.00 0.00
Cooling 70064.65 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 17344.92 0.00 0.00 0.00 0.00 0.00
Pumps 1624.92 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2877.91 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 79629.86 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 178332.06 276556.67 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 196926.82 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 70064.65 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 17344.92 0.00 0.00 0.00 0.00 0.00
Pumps General 1624.92 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 2877.91 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 79629.86 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 235.40 249.25 0.00 0.00 0.00
Cooling 1919.55 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 534.20 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1732.32 0.00 0.00 0.00 0.00
Pumps 154.60 0.00 0.00 0.00 0.00
Heat Rejection 86.13 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1116.80 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9629.10 1366.06 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 33.34 35.31 0.00 0.00 0.00
Cooling 271.90 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.67 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 245.37 0.00 0.00 0.00 0.00
Pumps 21.90 0.00 0.00 0.00 0.00
Heat Rejection 12.20 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 158.19 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1363.92 193.50 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 33.34 35.31 0.00 0.00 0.00
Cooling 271.90 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.67 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 245.37 0.00 0.00 0.00 0.00
Pumps 21.90 0.00 0.00 0.00 0.00
Heat Rejection 12.20 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 158.19 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1363.92 193.50 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.65_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 2.848 0.287 0.200     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.848 0.287 0.200              
North Total or Average           423.59 2.848 0.287 0.200              
Non-North Total or Average           726.80 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.82 83.82 168.68
Exterior Lighting Total 10720.10           168.68



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 286251.16 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 229000.93      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3605.76 2350.37 1255.39 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3599.80 2346.36 1253.44 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4858.16 3168.21 1689.95 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2938.60 1865.94 1072.66 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2300.56 1414.07 886.49 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2283.83 1402.07 881.76 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2335.15 1424.30 910.85 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2402.88 1473.80 929.08 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4363.58 2889.27 1474.31 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4317.02 2854.56 1462.46 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4044.69 2654.41 1390.28 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3597.96 2329.08 1268.87 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2788.52 1757.14 1031.37 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2775.30 1747.57 1027.74 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2854.02 1793.09 1060.93 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2877.47 1810.35 1067.13 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4405.16 2905.73 1499.42 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4359.11 2871.91 1487.20 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3883.26 2521.90 1361.37 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3662.34 2363.90 1298.43 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2840.40 1788.06 1052.34 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2827.41 1778.66 1048.75 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2911.20 1828.12 1083.08 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2921.35 1835.61 1085.75 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4436.76 2918.86 1517.90 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4389.17 2883.87 1505.30 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3899.03 2523.89 1375.14 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3698.32 2381.00 1317.32 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2870.99 1805.18 1065.81 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2858.14 1795.89 1062.25 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2943.91 1846.90 1097.01 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2952.11 1852.95 1099.16 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4495.24 2953.75 1541.49 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4447.34 2918.52 1528.83 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3959.95 2560.93 1399.03 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3760.89 2419.35 1341.54 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2928.16 1842.54 1085.62 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2915.44 1833.35 1082.09 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3001.73 1884.98 1116.75 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3009.66 1890.82 1118.84 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4461.87 2922.08 1539.79 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4411.51 2885.03 1526.49 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3931.03 2533.09 1397.94 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3729.47 2389.91 1339.55 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2893.37 1813.77 1079.60 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2880.80 1804.71 1076.08 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2969.37 1857.76 1111.61 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2977.27 1863.57 1113.70 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4459.38 2914.12 1545.26 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4408.23 2876.48 1531.76 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3932.51 2528.46 1404.05 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3729.83 2384.63 1345.20 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2890.19 1808.41 1081.77 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2877.73 1799.45 1078.28 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2967.16 1853.04 1114.12 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2975.05 1858.85 1116.21 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4475.34 2920.40 1554.94 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4423.39 2882.17 1541.22 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3951.15 2537.04 1414.12 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3747.34 2392.50 1354.84 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2905.53 1816.79 1088.74 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2893.21 1807.93 1085.28 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2982.58 1861.51 1121.07 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2990.50 1867.33 1123.17 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4601.73 3008.87 1592.85 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4550.57 2970.67 1579.90 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4027.92 2588.50 1439.41 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3815.87 2437.94 1377.93 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3020.15 1897.14 1123.01 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3007.87 1888.29 1119.58 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3070.24 1922.68 1147.55 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3079.10 1929.19 1149.90 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5350.32 3555.97 1794.34 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5237.34 3472.87 1764.47 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4809.35 3148.97 1660.38 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4453.07 2898.83 1554.23 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3514.42 2255.53 1258.90 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3487.28 2235.72 1251.56 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3901.54 2530.19 1371.35 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3909.80 2536.35 1373.44 0.65 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3605.76 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   3599.80 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4858.16 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2938.60 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2300.56 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2283.83 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2335.15 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2402.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4363.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4317.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4044.69 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3597.96 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2788.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2775.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2854.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2877.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4405.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4359.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3883.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3662.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2840.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2827.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2911.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2921.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4436.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4389.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3899.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3698.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2870.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2858.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2943.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2952.11 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4495.24 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   4447.34 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   3959.95 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   3760.89 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2928.16 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2915.44 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3001.73 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3009.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4461.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4411.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3931.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3729.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2893.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2880.80 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2969.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2977.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4459.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4408.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3932.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3729.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2890.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2877.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2967.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2975.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4475.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4423.39 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3951.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3747.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2905.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2893.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2982.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2990.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4601.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4550.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4027.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3815.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3020.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3007.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3070.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3079.10 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5350.32 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   5237.34 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4809.35 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   4453.07 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3514.42 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3487.28 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3901.54 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3909.80 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   2787.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   2791.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   3597.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   2791.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   2070.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   2070.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   2063.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   2072.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   2815.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   2820.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   2837.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   2817.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1920.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1920.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1918.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1919.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   2852.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   2862.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   2849.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   2856.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1914.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1914.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1905.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1905.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   2921.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   2933.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   2914.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   2926.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1948.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1948.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1935.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1935.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   2961.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   2974.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   2953.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   2966.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1961.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1960.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1947.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1947.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   3063.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   3079.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   3054.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   3070.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   2037.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   2037.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   2021.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   2021.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   3135.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   3152.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   3125.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   3142.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   2087.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   2086.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   2070.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   2069.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   3207.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   3224.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   3196.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   3214.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   2139.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   2139.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   2122.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   2121.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   3387.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   3403.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   3376.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   3392.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   2292.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   2291.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   2275.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   2275.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   3939.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   3960.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   3928.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   3949.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   2888.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   2888.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   2863.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   2863.52 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.10 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.09 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 303.95 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 174.63 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 127.25 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 125.96 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 125.16 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 130.50 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.30 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.73 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 257.39 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 223.01 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 163.53 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 162.49 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.10 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.96 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.90 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 280.67 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.08 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.88 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.33 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.32 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.35 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.16 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.63 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 281.27 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.61 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 227.05 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.77 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.77 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.98 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.64 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 287.84 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.45 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.06 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.65 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 171.49 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.49 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.76 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 173.40 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 283.91 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 280.32 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.56 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.98 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.08 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.11 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.55 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.18 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.62 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.96 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 240.64 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.99 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.25 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.29 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.79 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.42 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 282.92 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 279.19 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.19 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.47 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.93 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.98 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 169.48 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.12 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 292.40 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 288.43 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 246.42 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.04 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 176.41 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.46 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 175.87 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 176.58 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 350.54 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 342.17 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 304.88 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 280.34 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 214.22 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 212.08 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.39 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.06 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0062 1587.99 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2070.91 2485.09 0.168 0.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
G NW APARTMENT 2070.89 2485.07 0.168 0.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
OFFICE 2783.99 3340.79 0.226 0.271 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 32.69 0.01445
G NE APARTMENT 1599.48 1919.38 0.130 0.156 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.86 0.01445
G N1 APARTMENT 1165.57 1398.68 0.095 0.114 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
G N2 APARTMENT 1153.72 1384.46 0.094 0.112 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
G S1 APARTMENT 1146.40 1375.68 0.093 0.112 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01445
G S2 APARTMENT 1195.32 1434.38 0.097 0.117 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01445
F2 SW APARTMENT 2594.80 3113.76 0.211 0.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.36 0.01445
F2 NW APARTMENT 2562.12 3074.54 0.208 0.250 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F2 SE APARTMENT 2357.40 2828.88 0.191 0.230 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F2 NE APARTMENT 2042.53 2451.03 0.166 0.199 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F2 N1 APARTMENT 1497.82 1797.38 0.122 0.146 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F2 N2 APARTMENT 1488.34 1786.01 0.121 0.145 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F2 S1 APARTMENT 1503.01 1803.61 0.122 0.147 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F2 S2 APARTMENT 1520.12 1824.14 0.123 0.148 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F3 SW APARTMENT 2600.27 3120.33 0.211 0.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
F3 NW APARTMENT 2570.74 3084.88 0.209 0.251 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F3 SE APARTMENT 2217.16 2660.59 0.180 0.216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F3 NE APARTMENT 2068.77 2482.52 0.168 0.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F3 N1 APARTMENT 1523.49 1828.19 0.124 0.148 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F3 N2 APARTMENT 1514.19 1817.03 0.123 0.148 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F3 S1 APARTMENT 1532.80 1839.36 0.125 0.149 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F3 S2 APARTMENT 1540.24 1848.29 0.125 0.150 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F4 SW APARTMENT 2606.88 3128.25 0.212 0.254 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
F4 NW APARTMENT 2576.14 3091.37 0.209 0.251 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F4 SE APARTMENT 2212.81 2655.37 0.180 0.216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F4 NE APARTMENT 2079.46 2495.36 0.169 0.203 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F4 N1 APARTMENT 1536.71 1844.06 0.125 0.150 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F4 N2 APARTMENT 1527.53 1833.04 0.124 0.149 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F4 S1 APARTMENT 1547.70 1857.25 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F4 S2 APARTMENT 1553.72 1864.47 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
M SW APARTMENT 2636.29 3163.54 0.214 0.257 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
M NW APARTMENT 2605.29 3126.35 0.212 0.254 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
M SE APARTMENT 2244.42 2693.31 0.182 0.219 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
M NE APARTMENT 2112.42 2534.90 0.172 0.206 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
M N1 APARTMENT 1570.69 1884.83 0.128 0.153 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
M N2 APARTMENT 1561.61 1873.93 0.127 0.152 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
M S1 APARTMENT 1582.36 1898.83 0.129 0.154 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
M S2 APARTMENT 1588.17 1905.81 0.129 0.155 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F6 SW APARTMENT 2600.31 3120.38 0.211 0.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
F6 NW APARTMENT 2567.47 3080.96 0.209 0.250 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F6 SE APARTMENT 2212.38 2654.86 0.180 0.216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F6 NE APARTMENT 2078.81 2494.57 0.169 0.203 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F6 N1 APARTMENT 1539.54 1847.44 0.125 0.150 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F6 N2 APARTMENT 1530.59 1836.71 0.124 0.149 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F6 S1 APARTMENT 1552.87 1863.44 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F6 S2 APARTMENT 1558.65 1870.39 0.127 0.152 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F7 SW APARTMENT 2588.46 3106.15 0.210 0.252 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
F7 NW APARTMENT 2554.99 3065.99 0.208 0.249 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F7 SE APARTMENT 2203.91 2644.69 0.179 0.215 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F7 NE APARTMENT 2069.72 2483.66 0.168 0.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F7 N1 APARTMENT 1531.92 1838.30 0.124 0.149 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F7 N2 APARTMENT 1523.07 1827.69 0.124 0.148 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F7 S1 APARTMENT 1545.95 1855.14 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F7 S2 APARTMENT 1551.73 1862.07 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F8 SW APARTMENT 2591.15 3109.38 0.210 0.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
F8 NW APARTMENT 2557.08 3068.50 0.208 0.249 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F8 SE APARTMENT 2208.96 2650.75 0.179 0.215 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F8 NE APARTMENT 2074.09 2488.90 0.168 0.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F8 N1 APARTMENT 1538.15 1845.78 0.125 0.150 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F8 N2 APARTMENT 1529.41 1835.30 0.124 0.149 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F8 S1 APARTMENT 1552.30 1862.76 0.126 0.151 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F8 S2 APARTMENT 1558.08 1869.70 0.127 0.152 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F9 SW APARTMENT 2678.01 3213.61 0.218 0.261 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.36 0.01445
F9 NW APARTMENT 2641.69 3170.03 0.215 0.258 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
F9 SE APARTMENT 2256.77 2708.13 0.183 0.220 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.93 0.01445
F9 NE APARTMENT 2115.95 2539.14 0.172 0.206 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.21 0.01445
F9 N1 APARTMENT 1615.83 1939.00 0.131 0.157 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F9 N2 APARTMENT 1607.10 1928.52 0.131 0.157 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
F9 S1 APARTMENT 1610.79 1932.94 0.131 0.157 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
F9 S2 APARTMENT 1617.26 1940.71 0.131 0.158 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
T SW APARTMENT 3210.35 3852.42 0.261 0.313 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.26 0.01445
T NW APARTMENT 3133.79 3760.55 0.255 0.305 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59 0.01445
T SE APARTMENT 2792.19 3350.63 0.227 0.272 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01445
T NE APARTMENT 2567.40 3080.88 0.209 0.250 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 32.45 0.01445
T N1 APARTMENT 1962.07 2354.48 0.159 0.191 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
T N2 APARTMENT 1942.47 2330.96 0.158 0.189 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
T S1 APARTMENT 2210.86 2653.03 0.180 0.216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445
T S2 APARTMENT 2217.03 2660.43 0.180 0.216 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01445


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1640.68 1968.81 0.076 0.091 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G NW APARTMENT 1643.56 1972.28 0.076 0.091 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
OFFICE 1989.56 2387.48 0.092 0.110 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -6.30 0.00230
G NE APARTMENT 1643.73 1972.48 0.076 0.091 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G N1 APARTMENT 1034.23 1241.07 0.048 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G N2 APARTMENT 1034.22 1241.07 0.048 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G S1 APARTMENT 1028.23 1233.87 0.047 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
G S2 APARTMENT 1035.41 1242.49 0.048 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
F2 SW APARTMENT 1663.79 1996.55 0.077 0.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 NW APARTMENT 1668.40 2002.08 0.077 0.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 SE APARTMENT 1682.29 2018.75 0.078 0.093 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 NE APARTMENT 1665.56 1998.67 0.077 0.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 N1 APARTMENT 907.59 1089.11 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 N2 APARTMENT 907.52 1089.03 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 S1 APARTMENT 905.16 1086.19 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F2 S2 APARTMENT 906.50 1087.81 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 SW APARTMENT 1695.17 2034.20 0.078 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 NW APARTMENT 1703.43 2044.12 0.079 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 SE APARTMENT 1692.80 2031.36 0.078 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 NE APARTMENT 1698.70 2038.44 0.078 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 N1 APARTMENT 902.03 1082.44 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 N2 APARTMENT 901.91 1082.30 0.042 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 S1 APARTMENT 894.19 1073.03 0.041 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F3 S2 APARTMENT 894.29 1073.15 0.041 0.050 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 SW APARTMENT 1753.34 2104.01 0.081 0.097 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 NW APARTMENT 1764.08 2116.90 0.081 0.098 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 SE APARTMENT 1747.53 2097.04 0.081 0.097 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 NE APARTMENT 1758.02 2109.63 0.081 0.097 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 N1 APARTMENT 930.70 1116.84 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 N2 APARTMENT 930.55 1116.66 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 S1 APARTMENT 920.11 1104.14 0.042 0.051 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F4 S2 APARTMENT 919.99 1103.99 0.042 0.051 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M SW APARTMENT 1787.42 2144.91 0.082 0.099 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M NW APARTMENT 1798.90 2158.69 0.083 0.100 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M SE APARTMENT 1780.40 2136.47 0.082 0.099 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M NE APARTMENT 1791.86 2150.23 0.083 0.099 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M N1 APARTMENT 941.52 1129.82 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M N2 APARTMENT 941.34 1129.60 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M S1 APARTMENT 930.15 1116.17 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
M S2 APARTMENT 929.97 1115.96 0.043 0.052 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 SW APARTMENT 1873.96 2248.75 0.086 0.104 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 NW APARTMENT 1887.52 2265.02 0.087 0.105 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 SE APARTMENT 1866.09 2239.31 0.086 0.103 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 NE APARTMENT 1879.66 2255.59 0.087 0.104 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 N1 APARTMENT 1006.13 1207.36 0.046 0.056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 N2 APARTMENT 1005.93 1207.12 0.046 0.056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 S1 APARTMENT 992.61 1191.13 0.046 0.055 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F6 S2 APARTMENT 992.41 1190.89 0.046 0.055 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 SW APARTMENT 1934.45 2321.34 0.089 0.107 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 NW APARTMENT 1948.86 2338.63 0.090 0.108 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 SE APARTMENT 1925.92 2311.10 0.089 0.107 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 NE APARTMENT 1940.33 2328.40 0.090 0.107 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 N1 APARTMENT 1048.23 1257.87 0.048 0.058 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 N2 APARTMENT 1048.01 1257.61 0.048 0.058 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 S1 APARTMENT 1033.84 1240.61 0.048 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F7 S2 APARTMENT 1033.63 1240.35 0.048 0.057 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 SW APARTMENT 1995.40 2394.48 0.092 0.111 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 NW APARTMENT 2010.29 2412.35 0.093 0.111 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 SE APARTMENT 1986.30 2383.56 0.092 0.110 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 NE APARTMENT 2001.21 2401.45 0.092 0.111 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 N1 APARTMENT 1092.61 1311.13 0.050 0.061 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 N2 APARTMENT 1092.38 1310.86 0.050 0.060 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 S1 APARTMENT 1077.73 1293.27 0.050 0.060 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F8 S2 APARTMENT 1077.50 1293.00 0.050 0.060 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 SW APARTMENT 2148.15 2577.78 0.099 0.119 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 NW APARTMENT 2161.55 2593.86 0.100 0.120 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 SE APARTMENT 2138.47 2566.17 0.099 0.118 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 NE APARTMENT 2151.89 2582.26 0.099 0.119 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 N1 APARTMENT 1221.61 1465.93 0.056 0.068 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 N2 APARTMENT 1221.36 1465.63 0.056 0.068 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 S1 APARTMENT 1207.84 1449.41 0.056 0.067 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
F9 S2 APARTMENT 1207.60 1449.12 0.056 0.067 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T SW APARTMENT 2614.57 3137.49 0.121 0.145 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T NW APARTMENT 2632.73 3159.28 0.121 0.146 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T SE APARTMENT 2605.29 3126.35 0.120 0.144 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T NE APARTMENT 2623.46 3148.16 0.121 0.145 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T N1 APARTMENT 1725.89 2071.07 0.080 0.096 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T N2 APARTMENT 1725.64 2070.77 0.080 0.096 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T S1 APARTMENT 1704.96 2045.95 0.079 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230
T S2 APARTMENT 1704.71 2045.65 0.079 0.094 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -6.30 0.00230


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.20 0.20 0.09 0.09
AIRLOOP G NW 0.20 0.20 0.09 0.09
AIRLOOP OFFICE 0.27 0.27 0.11 0.11
AIRLOOP G NE 0.16 0.16 0.09 0.09
AIRLOOP G N1 0.11 0.11 0.06 0.06
AIRLOOP G N2 0.11 0.11 0.06 0.06
AIRLOOP G S1 0.11 0.11 0.06 0.06
AIRLOOP G S2 0.12 0.12 0.06 0.06
AIRLOOP F2 SW 0.25 0.25 0.09 0.09
AIRLOOP F2 NW 0.25 0.25 0.09 0.09
AIRLOOP F2 SE 0.23 0.23 0.09 0.09
AIRLOOP F2 NE 0.20 0.20 0.09 0.09
AIRLOOP F2 N1 0.15 0.15 0.05 0.05
AIRLOOP F2 N2 0.15 0.15 0.05 0.05
AIRLOOP F2 S1 0.15 0.15 0.05 0.05
AIRLOOP F2 S2 0.15 0.15 0.05 0.05
AIRLOOP F3 SW 0.25 0.25 0.09 0.09
AIRLOOP F3 NW 0.25 0.25 0.09 0.09
AIRLOOP F3 SE 0.22 0.22 0.09 0.09
AIRLOOP F3 NE 0.20 0.20 0.09 0.09
AIRLOOP F3 N1 0.15 0.15 0.05 0.05
AIRLOOP F3 N2 0.15 0.15 0.05 0.05
AIRLOOP F3 S1 0.15 0.15 0.05 0.05
AIRLOOP F3 S2 0.15 0.15 0.05 0.05
AIRLOOP F4 SW 0.25 0.25 0.10 0.10
AIRLOOP F4 NW 0.25 0.25 0.10 0.10
AIRLOOP F4 SE 0.22 0.22 0.10 0.10
AIRLOOP F4 NE 0.20 0.20 0.10 0.10
AIRLOOP F4 N1 0.15 0.15 0.05 0.05
AIRLOOP F4 N2 0.15 0.15 0.05 0.05
AIRLOOP F4 S1 0.15 0.15 0.05 0.05
AIRLOOP F4 S2 0.15 0.15 0.05 0.05
AIRLOOP M SW 0.26 0.26 0.10 0.10
AIRLOOP M NW 0.25 0.25 0.10 0.10
AIRLOOP M SE 0.22 0.22 0.10 0.10
AIRLOOP M NE 0.21 0.21 0.10 0.10
AIRLOOP M N1 0.15 0.15 0.05 0.05
AIRLOOP M N2 0.15 0.15 0.05 0.05
AIRLOOP M S1 0.15 0.15 0.05 0.05
AIRLOOP M S2 0.15 0.15 0.05 0.05
AIRLOOP F6 SW 0.25 0.25 0.10 0.10
AIRLOOP F6 NW 0.25 0.25 0.10 0.10
AIRLOOP F6 SE 0.22 0.22 0.10 0.10
AIRLOOP F6 NE 0.20 0.20 0.10 0.10
AIRLOOP F6 N1 0.15 0.15 0.06 0.06
AIRLOOP F6 N2 0.15 0.15 0.06 0.06
AIRLOOP F6 S1 0.15 0.15 0.05 0.05
AIRLOOP F6 S2 0.15 0.15 0.05 0.05
AIRLOOP F7 SW 0.25 0.25 0.11 0.11
AIRLOOP F7 NW 0.25 0.25 0.11 0.11
AIRLOOP F7 SE 0.21 0.21 0.11 0.11
AIRLOOP F7 NE 0.20 0.20 0.11 0.11
AIRLOOP F7 N1 0.15 0.15 0.06 0.06
AIRLOOP F7 N2 0.15 0.15 0.06 0.06
AIRLOOP F7 S1 0.15 0.15 0.06 0.06
AIRLOOP F7 S2 0.15 0.15 0.06 0.06
AIRLOOP F8 SW 0.25 0.25 0.11 0.11
AIRLOOP F8 NW 0.25 0.25 0.11 0.11
AIRLOOP F8 SE 0.22 0.22 0.11 0.11
AIRLOOP F8 NE 0.20 0.20 0.11 0.11
AIRLOOP F8 N1 0.15 0.15 0.06 0.06
AIRLOOP F8 N2 0.15 0.15 0.06 0.06
AIRLOOP F8 S1 0.15 0.15 0.06 0.06
AIRLOOP F8 S2 0.15 0.15 0.06 0.06
AIRLOOP F9 SW 0.26 0.26 0.12 0.12
AIRLOOP F9 NW 0.26 0.26 0.12 0.12
AIRLOOP F9 SE 0.22 0.22 0.12 0.12
AIRLOOP F9 NE 0.21 0.21 0.12 0.12
AIRLOOP F9 N1 0.16 0.16 0.07 0.07
AIRLOOP F9 N2 0.16 0.16 0.07 0.07
AIRLOOP F9 S1 0.16 0.16 0.07 0.07
AIRLOOP F9 S2 0.16 0.16 0.07 0.07
AIRLOOP T SW 0.31 0.31 0.14 0.14
AIRLOOP T NW 0.31 0.31 0.15 0.15
AIRLOOP T SE 0.27 0.27 0.14 0.14
AIRLOOP T NE 0.25 0.25 0.15 0.15
AIRLOOP T N1 0.19 0.19 0.10 0.10
AIRLOOP T N2 0.19 0.19 0.10 0.10
AIRLOOP T S1 0.22 0.22 0.09 0.09
AIRLOOP T S2 0.22 0.22 0.09 0.09



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4173.00 5847.00 1818.75
G NW APARTMENT 4102.75 6286.25 2026.00
OFFICE 1240.25 685.25 19.25
G NE APARTMENT 4090.00 6254.50 1954.25
G N1 APARTMENT 3838.25 6509.75 1965.50
G N2 APARTMENT 3839.25 6506.00 1961.50
G S1 APARTMENT 3945.50 5934.50 1737.00
G S2 APARTMENT 3972.00 5889.25 1731.25
F2 SW APARTMENT 4690.00 4256.50 1170.25
F2 NW APARTMENT 4383.75 5158.25 1329.25
F2 SE APARTMENT 4807.25 4036.00 1069.25
F2 NE APARTMENT 4415.25 5150.50 1278.50
F2 N1 APARTMENT 4198.25 5325.00 1314.00
F2 N2 APARTMENT 4199.75 5330.00 1311.50
F2 S1 APARTMENT 4642.00 4149.00 1184.00
F2 S2 APARTMENT 4653.75 4116.00 1176.50
F3 SW APARTMENT 4828.25 3967.75 1125.50
F3 NW APARTMENT 4479.25 4949.25 1270.75
F3 SE APARTMENT 4868.25 3944.50 1075.50
F3 NE APARTMENT 4490.00 4952.75 1236.50
F3 N1 APARTMENT 4325.50 5009.75 1224.75
F3 N2 APARTMENT 4325.00 5015.25 1224.25
F3 S1 APARTMENT 4841.50 3710.50 1113.25
F3 S2 APARTMENT 4848.00 3706.75 1114.25
F4 SW APARTMENT 4858.00 3950.00 1145.75
F4 NW APARTMENT 4501.75 4929.00 1288.50
F4 SE APARTMENT 4888.00 3962.25 1108.50
F4 NE APARTMENT 4522.25 4919.00 1247.50
F4 N1 APARTMENT 4367.25 4935.75 1221.75
F4 N2 APARTMENT 4365.50 4939.75 1219.50
F4 S1 APARTMENT 4899.25 3637.50 1123.25
F4 S2 APARTMENT 4901.25 3639.00 1123.00
M SW APARTMENT 4860.50 3964.25 1140.00
M NW APARTMENT 4504.75 4917.25 1277.75
M SE APARTMENT 4887.50 3986.00 1108.50
M NE APARTMENT 4526.25 4906.25 1238.25
M N1 APARTMENT 4386.75 4900.25 1205.75
M N2 APARTMENT 4384.00 4906.25 1206.25
M S1 APARTMENT 4913.75 3619.75 1115.25
M S2 APARTMENT 4913.75 3624.75 1116.25
F6 SW APARTMENT 4779.25 4204.50 1205.25
F6 NW APARTMENT 4461.25 5072.00 1350.25
F6 SE APARTMENT 4809.25 4227.00 1171.00
F6 NE APARTMENT 4473.50 5065.00 1306.25
F6 N1 APARTMENT 4314.00 5058.50 1255.25
F6 N2 APARTMENT 4313.00 5066.25 1255.75
F6 S1 APARTMENT 4798.75 3845.25 1158.25
F6 S2 APARTMENT 4803.75 3847.25 1159.25
F7 SW APARTMENT 4727.25 4360.00 1240.50
F7 NW APARTMENT 4426.50 5168.50 1388.75
F7 SE APARTMENT 4752.00 4374.00 1204.50
F7 NE APARTMENT 4445.50 5166.25 1338.50
F7 N1 APARTMENT 4280.75 5170.25 1291.00
F7 N2 APARTMENT 4279.75 5174.25 1289.00
F7 S1 APARTMENT 4737.75 4025.75 1189.25
F7 S2 APARTMENT 4738.25 4028.75 1189.25
F8 SW APARTMENT 4679.25 4490.50 1265.25
F8 NW APARTMENT 4400.25 5253.25 1420.75
F8 SE APARTMENT 4700.75 4496.25 1231.00
F8 NE APARTMENT 4424.75 5235.25 1365.75
F8 N1 APARTMENT 4252.50 5262.75 1315.50
F8 N2 APARTMENT 4252.00 5272.00 1318.00
F8 S1 APARTMENT 4684.25 4184.75 1208.25
F8 S2 APARTMENT 4686.00 4196.25 1212.50
F9 SW APARTMENT 4633.25 4643.00 1288.25
F9 NW APARTMENT 4411.75 5313.00 1464.25
F9 SE APARTMENT 4651.75 4627.25 1259.00
F9 NE APARTMENT 4435.75 5293.75 1411.25
F9 N1 APARTMENT 4232.50 5341.75 1332.25
F9 N2 APARTMENT 4233.25 5346.25 1332.50
F9 S1 APARTMENT 4605.25 4387.00 1217.00
F9 S2 APARTMENT 4607.50 4393.25 1219.00
T SW APARTMENT 4751.00 5048.00 1694.75
T NW APARTMENT 4673.50 5632.25 1942.75
T SE APARTMENT 4793.00 5007.50 1670.50
T NE APARTMENT 4658.00 5637.25 1920.25
T N1 APARTMENT 4418.50 5645.00 1696.25
T N2 APARTMENT 4420.00 5648.75 1697.75
T S1 APARTMENT 4638.00 4872.50 1510.75
T S2 APARTMENT 4639.50 4871.00 1510.25
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5757.25 6627.75 2544.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 2.75 7.00 2.75 7.00
G NW APARTMENT 2.25 0.50 2.25 0.50
OFFICE 2.50 0.00 0.00 0.00
G NE APARTMENT 2.75 13.75 2.75 13.75
G N1 APARTMENT 3.25 11.25 3.25 11.25
G N2 APARTMENT 3.50 11.25 3.50 11.25
G S1 APARTMENT 0.50 97.75 0.50 97.75
G S2 APARTMENT 0.25 67.25 0.25 67.25
F2 SW APARTMENT 1.00 2.25 1.00 2.25
F2 NW APARTMENT 0.25 0.00 0.25 0.00
F2 SE APARTMENT 1.25 2.00 1.25 2.00
F2 NE APARTMENT 2.25 10.75 2.25 10.75
F2 N1 APARTMENT 5.25 6.25 5.25 6.25
F2 N2 APARTMENT 3.75 6.50 3.75 6.50
F2 S1 APARTMENT 0.75 78.75 0.75 78.75
F2 S2 APARTMENT 1.00 66.50 1.00 66.50
F3 SW APARTMENT 0.50 2.75 0.50 2.75
F3 NW APARTMENT 1.25 0.00 1.25 0.00
F3 SE APARTMENT 0.75 17.75 0.75 17.75
F3 NE APARTMENT 1.75 16.75 1.75 16.75
F3 N1 APARTMENT 3.25 13.75 3.25 13.75
F3 N2 APARTMENT 4.50 13.75 4.50 13.75
F3 S1 APARTMENT 1.25 85.75 1.25 85.75
F3 S2 APARTMENT 1.25 80.25 1.25 80.25
F4 SW APARTMENT 0.25 2.75 0.25 2.75
F4 NW APARTMENT 0.25 0.00 0.25 0.00
F4 SE APARTMENT 0.75 19.75 0.75 19.75
F4 NE APARTMENT 1.75 18.50 1.75 18.50
F4 N1 APARTMENT 3.25 16.00 3.25 16.00
F4 N2 APARTMENT 2.75 16.50 2.75 16.50
F4 S1 APARTMENT 1.50 83.50 1.50 83.50
F4 S2 APARTMENT 1.50 80.50 1.50 80.50
M SW APARTMENT 1.00 2.75 1.00 2.75
M NW APARTMENT 0.50 0.25 0.50 0.25
M SE APARTMENT 1.25 20.25 1.25 20.25
M NE APARTMENT 1.00 19.50 1.00 19.50
M N1 APARTMENT 2.75 16.75 2.75 16.75
M N2 APARTMENT 2.25 17.25 2.25 17.25
M S1 APARTMENT 1.25 81.00 1.25 81.00
M S2 APARTMENT 1.25 78.50 1.25 78.50
F6 SW APARTMENT 0.50 3.00 0.50 3.00
F6 NW APARTMENT 0.75 0.25 0.75 0.25
F6 SE APARTMENT 0.75 20.00 0.75 20.00
F6 NE APARTMENT 1.00 19.50 1.00 19.50
F6 N1 APARTMENT 3.00 17.50 3.00 17.50
F6 N2 APARTMENT 2.50 18.00 2.50 18.00
F6 S1 APARTMENT 0.50 81.00 0.50 81.00
F6 S2 APARTMENT 0.75 78.75 0.75 78.75
F7 SW APARTMENT 1.25 3.25 1.25 3.25
F7 NW APARTMENT 0.25 0.50 0.25 0.50
F7 SE APARTMENT 1.50 20.50 1.50 20.50
F7 NE APARTMENT 2.00 19.75 2.00 19.75
F7 N1 APARTMENT 3.50 17.75 3.50 17.75
F7 N2 APARTMENT 4.50 19.75 4.50 19.75
F7 S1 APARTMENT 0.50 80.00 0.50 80.00
F7 S2 APARTMENT 0.50 77.00 0.50 77.00
F8 SW APARTMENT 0.50 3.25 0.50 3.25
F8 NW APARTMENT 0.25 0.50 0.25 0.50
F8 SE APARTMENT 2.00 22.00 2.00 22.00
F8 NE APARTMENT 1.75 22.75 1.75 22.75
F8 N1 APARTMENT 2.25 20.75 2.25 20.75
F8 N2 APARTMENT 2.00 22.00 2.00 22.00
F8 S1 APARTMENT 1.25 78.00 1.25 78.00
F8 S2 APARTMENT 1.00 75.75 1.00 75.75
F9 SW APARTMENT 0.50 3.00 0.50 3.00
F9 NW APARTMENT 0.25 0.25 0.25 0.25
F9 SE APARTMENT 1.25 19.25 1.25 19.25
F9 NE APARTMENT 0.00 21.50 0.00 21.50
F9 N1 APARTMENT 5.00 17.50 5.00 17.50
F9 N2 APARTMENT 4.50 19.50 4.50 19.50
F9 S1 APARTMENT 1.75 67.00 1.75 67.00
F9 S2 APARTMENT 2.00 63.50 2.00 63.50
T SW APARTMENT 0.25 3.00 0.25 3.00
T NW APARTMENT 0.00 1.25 0.00 1.25
T SE APARTMENT 0.00 4.00 0.00 4.00
T NE APARTMENT 0.00 13.00 0.00 13.00
T N1 APARTMENT 2.25 14.50 2.25 14.50
T N2 APARTMENT 1.00 15.50 1.00 15.50
T S1 APARTMENT 2.50 9.50 2.50 9.50
T S2 APARTMENT 1.50 9.75 1.50 9.75
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 93.25 176.00 90.75 176.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.355 0.100 0.000 0.379
G NW APARTMENT 1.71 2.50 268.96 0.354 0.100 0.000 0.364
OFFICE 0.94 1.00 268.96 0.520 0.113 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.354 0.100 0.000 0.363
G N1 APARTMENT 1.71 2.50 268.96 0.354 0.060 0.000 0.357
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.060 0.000 0.357
G S1 APARTMENT 1.71 2.50 268.96 0.355 0.060 0.000 0.376
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.060 0.000 0.376
F2 SW APARTMENT 1.71 2.50 268.96 0.355 0.144 0.000 0.446
F2 NW APARTMENT 1.71 2.50 268.96 0.354 0.144 0.000 0.428
F2 SE APARTMENT 1.71 2.50 268.96 0.355 0.144 0.000 0.447
F2 NE APARTMENT 1.71 2.50 268.96 0.354 0.143 0.000 0.427
F2 N1 APARTMENT 1.71 2.50 268.96 0.354 0.087 0.000 0.424
F2 N2 APARTMENT 1.71 2.50 268.97 0.354 0.087 0.000 0.424
F2 S1 APARTMENT 1.71 2.50 268.96 0.355 0.087 0.000 0.444
F2 S2 APARTMENT 1.71 2.50 268.97 0.355 0.087 0.000 0.444
F3 SW APARTMENT 1.71 2.50 268.96 0.355 0.170 0.000 0.492
F3 NW APARTMENT 1.71 2.50 268.96 0.354 0.170 0.000 0.472
F3 SE APARTMENT 1.71 2.50 268.96 0.355 0.170 0.000 0.492
F3 NE APARTMENT 1.71 2.50 268.96 0.354 0.170 0.000 0.472
F3 N1 APARTMENT 1.71 2.50 268.96 0.355 0.102 0.000 0.469
F3 N2 APARTMENT 1.71 2.50 268.97 0.355 0.102 0.000 0.469
F3 S1 APARTMENT 1.71 2.50 268.96 0.355 0.103 0.000 0.491
F3 S2 APARTMENT 1.71 2.50 268.97 0.355 0.103 0.000 0.491
F4 SW APARTMENT 1.71 2.50 268.96 0.355 0.190 0.000 0.513
F4 NW APARTMENT 1.71 2.50 268.96 0.354 0.190 0.000 0.492
F4 SE APARTMENT 1.71 2.50 268.96 0.355 0.190 0.000 0.513
F4 NE APARTMENT 1.71 2.50 268.96 0.354 0.190 0.000 0.492
F4 N1 APARTMENT 1.71 2.50 268.96 0.355 0.115 0.000 0.490
F4 N2 APARTMENT 1.71 2.50 268.97 0.355 0.115 0.000 0.490
F4 S1 APARTMENT 1.71 2.50 268.96 0.355 0.115 0.000 0.512
F4 S2 APARTMENT 1.71 2.50 268.97 0.355 0.115 0.000 0.512
M SW APARTMENT 1.71 2.50 268.96 0.355 0.207 0.000 0.539
M NW APARTMENT 1.71 2.50 268.96 0.354 0.206 0.000 0.517
M SE APARTMENT 1.71 2.50 268.96 0.355 0.206 0.000 0.538
M NE APARTMENT 1.71 2.50 268.96 0.354 0.206 0.000 0.516
M N1 APARTMENT 1.71 2.50 268.96 0.355 0.124 0.000 0.514
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.124 0.000 0.514
M S1 APARTMENT 1.71 2.50 268.96 0.355 0.125 0.000 0.538
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.125 0.000 0.538
F6 SW APARTMENT 1.71 2.50 268.96 0.355 0.221 0.000 0.560
F6 NW APARTMENT 1.71 2.50 268.96 0.354 0.220 0.000 0.537
F6 SE APARTMENT 1.71 2.50 268.96 0.355 0.221 0.000 0.560
F6 NE APARTMENT 1.71 2.50 268.96 0.354 0.220 0.000 0.536
F6 N1 APARTMENT 1.71 2.50 268.96 0.354 0.133 0.000 0.534
F6 N2 APARTMENT 1.71 2.50 268.97 0.354 0.133 0.000 0.534
F6 S1 APARTMENT 1.71 2.50 268.96 0.355 0.133 0.000 0.559
F6 S2 APARTMENT 1.71 2.50 268.97 0.355 0.133 0.000 0.559
F7 SW APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.579
F7 NW APARTMENT 1.71 2.50 268.96 0.354 0.233 0.000 0.554
F7 SE APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.579
F7 NE APARTMENT 1.71 2.50 268.96 0.354 0.233 0.000 0.553
F7 N1 APARTMENT 1.71 2.50 268.96 0.354 0.140 0.000 0.552
F7 N2 APARTMENT 1.71 2.50 268.97 0.354 0.140 0.000 0.552
F7 S1 APARTMENT 1.71 2.50 268.96 0.355 0.141 0.000 0.578
F7 S2 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.578
F8 SW APARTMENT 1.71 2.50 268.96 0.355 0.244 0.000 0.598
F8 NW APARTMENT 1.71 2.50 268.96 0.354 0.244 0.000 0.573
F8 SE APARTMENT 1.71 2.50 268.96 0.355 0.244 0.000 0.598
F8 NE APARTMENT 1.71 2.50 268.96 0.354 0.244 0.000 0.572
F8 N1 APARTMENT 1.71 2.50 268.96 0.354 0.147 0.000 0.570
F8 N2 APARTMENT 1.71 2.50 268.97 0.354 0.147 0.000 0.570
F8 S1 APARTMENT 1.71 2.50 268.96 0.355 0.147 0.000 0.597
F8 S2 APARTMENT 1.71 2.50 268.97 0.355 0.147 0.000 0.597
F9 SW APARTMENT 1.71 2.50 268.96 0.355 0.255 0.000 0.615
F9 NW APARTMENT 1.71 2.50 268.96 0.354 0.254 0.000 0.589
F9 SE APARTMENT 1.71 2.50 268.96 0.354 0.255 0.000 0.615
F9 NE APARTMENT 1.71 2.50 268.96 0.354 0.254 0.000 0.588
F9 N1 APARTMENT 1.71 2.50 268.96 0.354 0.153 0.000 0.586
F9 N2 APARTMENT 1.71 2.50 268.97 0.354 0.153 0.000 0.586
F9 S1 APARTMENT 1.71 2.50 268.96 0.355 0.154 0.000 0.614
F9 S2 APARTMENT 1.71 2.50 268.97 0.355 0.154 0.000 0.614
T SW APARTMENT 1.71 2.50 268.96 0.354 0.264 0.000 0.628
T NW APARTMENT 1.71 2.50 268.96 0.354 0.264 0.000 0.602
T SE APARTMENT 1.71 2.50 268.96 0.354 0.264 0.000 0.628
T NE APARTMENT 1.71 2.50 268.96 0.354 0.264 0.000 0.601
T N1 APARTMENT 1.71 2.50 268.96 0.354 0.159 0.000 0.599
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.159 0.000 0.599
T S1 APARTMENT 1.71 2.50 268.96 0.355 0.159 0.000 0.627
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.159 0.000 0.627
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.499 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 546.99 17344.92 12-JAN-06:15 17344.92 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1248.25 17725.45 01-MAR-03:15 92115.60 04-AUG-15:30
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
ElectricityPurchased:Plant 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
Cogeneration:ElectricityPurchased 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
ElectricityNet:Plant 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
Cogeneration:ElectricityNet 3040.45 55285.93 01-MAR-03:15 178332.06 26-JUL-20:00
ExteriorLights:Electricity 168.68 0.00 01-JAN-08:00 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.68 0.00 01-JAN-08:00 10720.10 01-JAN-00:15
General:Fans:Electricity 546.99 17344.92 12-JAN-06:15 17344.92 01-JAN-00:15
Cooling:Electricity 606.11 0.00 01-JAN-00:15 73953.27 04-AUG-15:30
Heating:Electricity 74.33 0.00 01-JAN-11:15 50268.05 12-FEB-06:00
Electricity:Plant 76.01 36.93 01-JAN-11:15 4630.55 19-AUG-16:45
HeatRejection:Electricity 27.19 0.00 01-JAN-00:15 3005.64 19-AUG-16:45
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 48.82 36.93 01-JAN-11:15 1624.92 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1260.20 9260.51 01-JAN-15:00 276556.67 12-FEB-06:45
Gas:Plant 1260.20 9260.51 01-JAN-15:00 276556.67 12-FEB-06:45
WaterSystems:Gas 1030.26 9260.51 01-JAN-00:15 85033.90 30-JAN-08:00
Water Heater:WaterSystems:Gas 1030.26 9260.51 01-JAN-00:15 85033.90 30-JAN-08:00
Heating:Gas 229.94 0.00 01-JAN-09:30 205634.57 12-FEB-06:15
Boiler:Heating:Gas 229.94 0.00 01-JAN-09:30 205634.57 12-FEB-06:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 2631.76 0.00 01-JAN-00:15 362166.26 20-AUG-15:30
PlantLoopCoolingDemand:HVAC 2631.76 0.00 01-JAN-00:15 362166.26 20-AUG-15:30
CoolingCoils:PlantLoopCoolingDemand 2631.76 0.00 01-JAN-00:15 362166.26 20-AUG-15:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 6426.48 0.00 01-JAN-02:30 0.00 01-AUG-17:15
Water:Plant 6426.48 0.00 01-JAN-02:30 0.00 01-AUG-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 6426.48 0.00 01-JAN-02:30 0.00 01-AUG-17:15
MainsWater:Plant 6426.48 0.00 01-JAN-02:30 0.00 01-AUG-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
HeatRejection:Water 1647.96 0.00 01-JAN-00:15 0.00 08-JUL-16:00
HeatRejection:MainsWater 1647.96 0.00 01-JAN-00:15 0.00 08-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 991.17 405.47 03-AUG-01:15 217368.33 12-FEB-06:15
PlantLoopHeatingDemand:Plant 781.95 405.47 03-AUG-01:15 55132.33 02-FEB-08:00
WaterSystems:PlantLoopHeatingDemand 781.95 405.47 03-AUG-01:15 55132.33 02-FEB-08:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 4770.98 4558.76 01-OCT-01:15 574305.17 12-FEB-06:15
EnergyTransfer:Building 1468.45 2700.84 30-APR-10:15 169253.98 01-AUG-16:30
EnergyTransfer:Zone:G SW APARTMENT 14.23 0.00 17-FEB-01:15 2300.54 08-SEP-16:30
Heating:EnergyTransfer 167.82 0.00 24-JAN-18:30 149844.47 12-FEB-06:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 2.02 0.00 01-JAN-09:30 1718.34 12-FEB-06:00
Cooling:EnergyTransfer 1300.62 0.00 02-JAN-02:45 169253.98 01-AUG-16:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 12.21 0.00 01-JAN-00:15 2300.54 08-SEP-16:30
EnergyTransfer:Zone:G NW APARTMENT 13.47 0.00 20-MAR-22:45 2215.79 18-AUG-17:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 3.56 0.00 01-JAN-10:45 1766.95 12-FEB-06:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 9.91 0.00 01-JAN-00:15 2215.79 18-AUG-17:00
EnergyTransfer:Zone:OFFICE 19.67 0.02 22-OCT-19:45 2942.65 06-SEP-13:15
Heating:EnergyTransfer:Zone:OFFICE 1.93 0.00 01-JAN-11:15 1830.20 12-FEB-07:00
Cooling:EnergyTransfer:Zone:OFFICE 17.74 0.00 01-JAN-00:15 2942.65 06-SEP-13:15
EnergyTransfer:Zone:G NE APARTMENT 13.40 0.01 30-MAR-03:00 1787.92 12-FEB-06:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 3.33 0.00 01-JAN-10:15 1787.92 12-FEB-06:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 10.07 0.00 01-JAN-00:15 1682.37 08-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 9.77 0.01 01-OCT-05:45 1266.25 06-JUN-17:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 1.69 0.00 01-JAN-05:30 1072.24 24-DEC-10:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 8.08 0.00 01-JAN-00:15 1266.25 06-JUN-17:30
EnergyTransfer:Zone:G N2 APARTMENT 9.77 0.03 23-OCT-14:15 1254.91 06-JUN-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 1.69 0.00 01-JAN-05:30 1072.47 24-DEC-10:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 8.08 0.00 01-JAN-00:15 1254.91 06-JUN-17:30
EnergyTransfer:Zone:G S1 APARTMENT 11.52 0.02 30-APR-18:45 1473.76 15-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.55 0.00 01-JAN-05:15 1028.65 24-DEC-10:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 10.97 0.00 01-JAN-00:15 1473.76 15-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 11.66 0.02 29-MAR-08:45 1512.56 15-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.52 0.00 01-JAN-05:15 1025.85 24-DEC-10:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 11.14 0.00 01-JAN-00:15 1512.56 15-SEP-13:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 20.69 0.02 01-APR-22:45 3011.51 11-OCT-15:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 1.41 0.00 01-JAN-06:00 1904.49 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 19.28 0.00 01-JAN-00:15 3011.51 11-OCT-15:30
EnergyTransfer:Zone:F2 NW APARTMENT 18.20 0.00 19-FEB-23:00 2736.96 21-JUL-17:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 2.96 0.00 01-JAN-06:15 2026.18 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 15.24 0.00 01-JAN-00:15 2736.96 21-JUL-17:30
EnergyTransfer:Zone:F2 SE APARTMENT 21.74 0.04 24-APR-14:15 2607.55 11-OCT-15:30
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 1.21 0.00 01-JAN-05:45 1915.42 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 20.53 0.00 01-JAN-00:15 2607.55 11-OCT-15:30
EnergyTransfer:Zone:F2 NE APARTMENT 18.25 0.07 29-JAN-14:00 2199.39 30-JUN-15:45
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 2.74 0.00 01-JAN-06:30 2054.46 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 15.51 0.00 01-JAN-00:15 2199.39 30-JUN-15:45
EnergyTransfer:Zone:F2 N1 APARTMENT 13.81 0.00 29-JUL-10:45 1633.72 06-JUN-17:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.96 0.00 01-JAN-00:15 1259.54 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 12.84 0.00 02-JAN-00:30 1633.72 06-JUN-17:30
EnergyTransfer:Zone:F2 N2 APARTMENT 13.81 0.03 08-FEB-11:30 1625.63 30-JUN-15:45
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.96 0.00 01-JAN-00:15 1261.10 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 12.85 0.00 02-JAN-00:30 1625.63 30-JUN-15:45
EnergyTransfer:Zone:F2 S1 APARTMENT 17.53 0.02 07-JUN-21:00 1989.11 11-OCT-16:30
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.24 0.00 01-JAN-00:15 1180.23 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 17.29 0.00 02-JAN-01:15 1989.11 11-OCT-16:30
EnergyTransfer:Zone:F2 S2 APARTMENT 17.62 0.02 26-MAY-21:00 2005.65 11-OCT-16:30
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.24 0.00 01-JAN-00:15 1176.21 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 17.38 0.00 02-JAN-01:15 2005.65 11-OCT-16:30
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 21.79 0.07 02-NOV-01:30 3046.91 11-OCT-15:30
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 1.40 0.00 01-JAN-05:15 2014.26 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 20.40 0.00 01-JAN-00:15 3046.91 11-OCT-15:30
EnergyTransfer:Zone:F3 NW APARTMENT 19.11 0.02 08-FEB-18:45 2756.10 02-AUG-17:15
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 2.94 0.00 01-JAN-05:30 2147.79 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 16.17 0.00 01-JAN-00:15 2756.10 02-AUG-17:15
EnergyTransfer:Zone:F3 SE APARTMENT 22.10 0.01 09-APR-11:15 2624.71 11-OCT-15:30
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 1.27 0.00 01-JAN-05:15 2031.70 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 20.83 0.00 01-JAN-00:15 2624.71 11-OCT-15:30
EnergyTransfer:Zone:F3 NE APARTMENT 19.18 0.01 27-NOV-05:30 2234.46 30-JUN-15:45
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 2.74 0.00 01-JAN-05:30 2172.47 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 16.44 0.00 01-JAN-00:15 2234.46 30-JUN-15:45
EnergyTransfer:Zone:F3 N1 APARTMENT 14.80 0.01 30-SEP-19:15 1673.01 06-JUN-17:45
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.88 0.00 01-JAN-00:15 1411.34 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 13.92 0.00 02-JAN-01:30 1673.01 06-JUN-17:45
EnergyTransfer:Zone:F3 N2 APARTMENT 14.81 0.01 05-OCT-12:00 1663.94 06-JUN-17:45
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.88 0.00 01-JAN-00:15 1413.79 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 13.93 0.00 02-JAN-01:30 1663.94 06-JUN-17:45
EnergyTransfer:Zone:F3 S1 APARTMENT 19.00 0.03 27-APR-13:45 2037.26 11-OCT-16:30
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.22 0.00 01-JAN-00:15 1294.31 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 18.78 0.00 02-JAN-02:00 2037.26 11-OCT-16:30
EnergyTransfer:Zone:F3 S2 APARTMENT 19.03 0.05 17-DEC-03:15 2043.75 11-OCT-16:30
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.22 0.00 01-JAN-00:15 1293.47 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 18.81 0.00 02-JAN-02:00 2043.75 11-OCT-16:30
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 21.99 0.01 22-MAR-04:30 3057.56 11-OCT-15:30
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 1.52 0.00 01-JAN-05:15 2137.84 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 20.47 0.00 01-JAN-00:15 3057.56 11-OCT-15:30
EnergyTransfer:Zone:F4 NW APARTMENT 19.41 0.01 17-FEB-12:15 2769.26 02-AUG-17:15
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 3.11 0.00 01-JAN-05:30 2275.64 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 16.31 0.00 01-JAN-00:15 2769.26 02-AUG-17:15
EnergyTransfer:Zone:F4 SE APARTMENT 22.19 0.03 25-MAY-11:00 2627.29 11-OCT-15:30
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 1.41 0.00 01-JAN-05:15 2156.61 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 20.78 0.00 01-JAN-00:15 2627.29 11-OCT-15:30
EnergyTransfer:Zone:F4 NE APARTMENT 19.50 0.05 29-JAN-14:45 2297.66 12-FEB-06:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 2.91 0.00 01-JAN-05:30 2297.66 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 16.59 0.00 01-JAN-00:15 2250.12 30-JUN-15:45
EnergyTransfer:Zone:F4 N1 APARTMENT 15.10 0.02 12-MAR-08:00 1695.14 06-JUN-19:15
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.92 0.00 01-JAN-00:15 1566.33 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 14.17 0.00 02-JAN-01:45 1695.14 06-JUN-19:15
EnergyTransfer:Zone:F4 N2 APARTMENT 15.10 0.02 20-OCT-13:45 1692.41 06-JUN-19:15
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.92 0.00 01-JAN-00:15 1569.03 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 14.18 0.00 02-JAN-01:45 1692.41 06-JUN-19:15
EnergyTransfer:Zone:F4 S1 APARTMENT 19.29 0.02 29-JUL-05:45 2058.21 11-OCT-16:30
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.24 0.00 01-JAN-00:15 1438.68 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 19.05 0.00 02-JAN-02:15 2058.21 11-OCT-16:30
EnergyTransfer:Zone:F4 S2 APARTMENT 19.30 0.00 21-MAY-08:15 2063.30 11-OCT-16:30
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.24 0.00 01-JAN-00:15 1440.18 24-DEC-09:45
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 19.06 0.00 02-JAN-02:15 2063.30 11-OCT-16:30
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 22.30 0.04 14-JAN-21:45 3089.57 11-OCT-15:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 1.63 0.00 01-JAN-03:45 2231.67 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 20.67 0.00 01-JAN-00:15 3089.57 11-OCT-15:30
EnergyTransfer:Zone:M NW APARTMENT 19.85 0.03 19-NOV-15:15 2805.42 02-AUG-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 3.24 0.00 01-JAN-05:15 2368.78 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 16.61 0.00 01-JAN-00:15 2805.42 02-AUG-17:15
EnergyTransfer:Zone:M SE APARTMENT 22.49 0.10 17-FEB-16:00 2662.96 11-OCT-15:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 1.53 0.00 01-JAN-02:00 2249.59 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 20.96 0.00 01-JAN-00:15 2662.96 11-OCT-15:30
EnergyTransfer:Zone:M NE APARTMENT 19.93 0.02 06-DEC-06:00 2388.73 12-FEB-06:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 3.04 0.00 01-JAN-05:15 2388.73 12-FEB-06:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 16.89 0.00 01-JAN-00:15 2287.57 30-JUN-15:45
EnergyTransfer:Zone:M N1 APARTMENT 15.51 0.02 07-OCT-20:15 1749.55 06-JUN-19:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.96 0.00 01-JAN-00:15 1692.25 24-DEC-10:30
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 14.55 0.00 02-JAN-01:45 1749.55 06-JUN-19:15
EnergyTransfer:Zone:M N2 APARTMENT 15.52 0.00 25-AUG-06:45 1746.92 06-JUN-19:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.96 0.00 01-JAN-00:15 1694.86 24-DEC-10:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 14.56 0.00 02-JAN-01:45 1746.92 06-JUN-19:15
EnergyTransfer:Zone:M S1 APARTMENT 19.63 0.03 17-NOV-14:00 2098.09 11-OCT-16:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.27 0.00 01-JAN-00:15 1568.35 24-DEC-10:30
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 19.36 0.00 02-JAN-02:45 2098.09 11-OCT-16:30
EnergyTransfer:Zone:M S2 APARTMENT 19.64 0.00 23-APR-10:00 2102.98 11-OCT-16:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.27 0.00 01-JAN-00:15 1570.63 24-DEC-10:30
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 19.37 0.00 02-JAN-02:45 2102.98 11-OCT-16:30
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 21.60 0.03 20-JAN-04:00 3047.98 11-OCT-15:30
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 1.91 0.00 01-JAN-05:30 2373.12 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 19.69 0.00 01-JAN-00:15 3047.98 11-OCT-15:30
EnergyTransfer:Zone:F6 NW APARTMENT 19.58 0.00 19-DEC-16:30 2774.08 18-AUG-17:15
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 3.69 0.00 01-JAN-06:15 2510.31 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 15.89 0.00 01-JAN-00:15 2774.08 18-AUG-17:15
EnergyTransfer:Zone:F6 SE APARTMENT 21.77 0.01 01-JUL-20:00 2627.15 11-OCT-15:30
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 1.80 0.00 01-JAN-05:30 2389.90 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 19.97 0.00 01-JAN-00:15 2627.15 11-OCT-15:30
EnergyTransfer:Zone:F6 NE APARTMENT 19.65 0.00 27-OCT-23:15 2528.57 12-FEB-06:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 3.49 0.00 01-JAN-06:15 2528.57 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 16.16 0.00 01-JAN-00:15 2260.36 06-JUN-17:30
EnergyTransfer:Zone:F6 N1 APARTMENT 15.02 0.02 04-DEC-12:00 1887.07 24-DEC-10:30
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 1.19 0.00 01-JAN-00:15 1887.07 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 13.84 0.00 02-JAN-01:15 1735.17 06-JUN-19:15
EnergyTransfer:Zone:F6 N2 APARTMENT 15.03 0.02 27-MAY-05:45 1888.85 24-DEC-10:30
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 1.19 0.00 01-JAN-00:15 1888.85 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 13.84 0.00 02-JAN-01:15 1732.67 06-JUN-19:15
EnergyTransfer:Zone:F6 S1 APARTMENT 18.72 0.03 03-MAR-14:15 2066.62 11-OCT-16:30
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.35 0.00 01-JAN-00:15 1776.89 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 18.37 0.00 02-JAN-01:30 2066.62 11-OCT-16:30
EnergyTransfer:Zone:F6 S2 APARTMENT 18.73 0.04 27-MAY-09:15 2071.53 11-OCT-16:30
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.35 0.00 01-JAN-00:15 1779.12 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 18.37 0.00 02-JAN-01:30 2071.53 11-OCT-16:30
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 21.29 0.00 20-FEB-00:45 3032.66 11-OCT-15:30
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 2.16 0.00 01-JAN-06:15 2485.10 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 19.13 0.00 01-JAN-00:15 3032.66 11-OCT-15:30
EnergyTransfer:Zone:F7 NW APARTMENT 19.57 0.00 26-APR-11:30 2767.91 18-AUG-17:15
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 4.05 0.00 01-JAN-06:30 2619.85 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 15.53 0.00 01-JAN-00:15 2767.91 18-AUG-17:15
EnergyTransfer:Zone:F7 SE APARTMENT 21.46 0.12 31-AUG-08:15 2616.59 11-OCT-15:30
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 2.04 0.00 01-JAN-06:15 2500.77 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 19.42 0.00 01-JAN-00:15 2616.59 11-OCT-15:30
EnergyTransfer:Zone:F7 NE APARTMENT 19.65 0.08 20-JAN-02:15 2636.61 12-FEB-06:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 3.84 0.00 01-JAN-06:30 2636.61 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 15.80 0.00 01-JAN-00:15 2260.80 06-JUN-17:30
EnergyTransfer:Zone:F7 N1 APARTMENT 14.86 0.01 04-NOV-13:45 2046.81 24-DEC-10:30
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 1.38 0.00 01-JAN-00:15 2046.81 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 13.48 0.00 02-JAN-00:15 1739.76 06-JUN-19:15
EnergyTransfer:Zone:F7 N2 APARTMENT 14.87 0.02 26-MAY-20:15 2048.01 24-DEC-10:30
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 1.38 0.00 01-JAN-00:15 2048.01 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 13.49 0.00 02-JAN-00:15 1737.37 06-JUN-19:15
EnergyTransfer:Zone:F7 S1 APARTMENT 18.24 0.02 11-OCT-05:45 2059.48 11-OCT-16:30
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.43 0.00 01-JAN-00:15 1953.34 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 17.80 0.00 02-JAN-01:15 2059.48 11-OCT-16:30
EnergyTransfer:Zone:F7 S2 APARTMENT 18.25 0.01 02-OCT-05:45 2064.40 11-OCT-16:30
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.44 0.00 01-JAN-00:15 1955.15 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 17.81 0.00 02-JAN-01:15 2064.40 11-OCT-16:30
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 21.17 0.01 17-FEB-05:15 3031.71 11-OCT-15:30
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 2.41 0.00 01-JAN-06:30 2591.40 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 18.76 0.00 01-JAN-00:15 3031.71 11-OCT-15:30
EnergyTransfer:Zone:F8 NW APARTMENT 19.74 0.01 24-OCT-12:15 2774.33 18-AUG-17:15
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 4.41 0.00 01-JAN-06:30 2722.37 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 15.34 0.00 01-JAN-00:15 2774.33 18-AUG-17:15
EnergyTransfer:Zone:F8 SE APARTMENT 21.34 0.00 18-FEB-12:30 2619.10 11-OCT-15:30
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 2.28 0.00 01-JAN-06:30 2606.48 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 19.05 0.00 01-JAN-00:15 2619.10 11-OCT-15:30
EnergyTransfer:Zone:F8 NE APARTMENT 19.81 0.10 12-DEC-00:30 2737.95 12-FEB-06:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 4.20 0.00 01-JAN-06:30 2737.95 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 15.61 0.00 01-JAN-00:15 2271.55 06-JUN-17:30
EnergyTransfer:Zone:F8 N1 APARTMENT 14.86 0.01 30-SEP-06:00 2188.82 24-DEC-10:30
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 1.57 0.00 01-JAN-00:30 2188.82 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 13.29 0.00 01-JAN-00:15 1752.52 06-JUN-19:15
EnergyTransfer:Zone:F8 N2 APARTMENT 14.87 0.02 01-APR-18:00 2189.76 24-DEC-10:30
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 1.57 0.00 01-JAN-00:30 2189.76 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 13.29 0.00 01-JAN-00:15 1750.19 06-JUN-19:15
EnergyTransfer:Zone:F8 S1 APARTMENT 17.94 0.01 28-MAY-06:00 2110.44 24-DEC-10:30
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.53 0.00 01-JAN-00:15 2110.44 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 17.41 0.00 02-JAN-00:15 2065.76 11-OCT-16:30
EnergyTransfer:Zone:F8 S2 APARTMENT 17.95 0.01 06-MAR-16:30 2111.83 24-DEC-10:30
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.53 0.00 01-JAN-00:15 2111.83 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 17.42 0.00 02-JAN-00:15 2070.70 11-OCT-16:30
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 21.53 0.00 23-OCT-23:15 3103.24 11-OCT-15:30
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 2.89 0.00 01-JAN-09:15 2801.15 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 18.64 0.00 01-JAN-00:15 3103.24 11-OCT-15:30
EnergyTransfer:Zone:F9 NW APARTMENT 20.56 0.01 26-NOV-11:15 2922.20 12-FEB-06:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 5.10 0.00 01-JAN-09:45 2922.20 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 15.46 0.00 01-JAN-00:15 2861.91 18-AUG-17:15
EnergyTransfer:Zone:F9 SE APARTMENT 21.68 0.14 27-OCT-23:45 2815.96 12-FEB-06:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 2.74 0.00 01-JAN-09:00 2815.96 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 18.94 0.00 01-JAN-00:15 2647.28 11-OCT-15:30
EnergyTransfer:Zone:F9 NE APARTMENT 20.59 0.01 17-FEB-16:15 2936.27 12-FEB-06:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 4.86 0.00 01-JAN-09:30 2936.27 12-FEB-06:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 15.73 0.00 01-JAN-00:15 2335.22 06-JUN-17:30
EnergyTransfer:Zone:F9 N1 APARTMENT 15.32 0.00 09-MAY-08:00 2344.30 24-DEC-10:30
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 2.01 0.00 01-JAN-00:45 2344.30 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 13.31 0.00 01-JAN-00:15 1813.65 06-JUN-19:15
EnergyTransfer:Zone:F9 N2 APARTMENT 15.33 0.03 13-DEC-07:45 2344.99 24-DEC-10:30
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 2.01 0.00 01-JAN-00:45 2344.99 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 13.31 0.00 01-JAN-00:15 1811.28 06-JUN-19:15
EnergyTransfer:Zone:F9 S1 APARTMENT 17.91 0.01 24-MAY-09:45 2282.00 24-DEC-10:30
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.73 0.00 01-JAN-00:45 2282.00 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 17.18 0.00 01-JAN-00:15 2108.30 30-MAR-17:00
EnergyTransfer:Zone:F9 S2 APARTMENT 17.92 0.01 12-DEC-12:15 2282.95 24-DEC-10:30
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.74 0.00 01-JAN-00:45 2282.95 24-DEC-10:30
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 17.18 0.00 01-JAN-00:15 2113.17 30-MAR-17:00
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 24.60 0.01 02-NOV-11:45 3627.29 12-FEB-06:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 5.72 0.00 02-JAN-12:15 3627.29 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 18.88 0.00 01-JAN-00:15 3607.97 18-AUG-16:30
EnergyTransfer:Zone:T NW APARTMENT 24.03 0.02 25-NOV-21:30 3699.40 12-FEB-06:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 8.04 0.00 10-JAN-14:45 3699.40 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 15.98 0.00 01-JAN-00:15 3467.36 08-JUL-16:30
EnergyTransfer:Zone:T SE APARTMENT 24.35 0.01 14-SEP-03:45 3624.58 12-FEB-06:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 5.44 0.00 01-JAN-11:15 3624.58 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 18.91 0.00 01-JAN-00:15 3208.21 18-AUG-13:00
EnergyTransfer:Zone:T NE APARTMENT 23.57 0.01 10-NOV-02:45 3695.92 12-FEB-06:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 7.59 0.00 01-JAN-10:45 3695.92 12-FEB-06:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 15.98 0.00 01-JAN-00:15 2832.73 08-JUL-16:30
EnergyTransfer:Zone:T N1 APARTMENT 17.54 0.09 04-NOV-01:45 2563.15 23-FEB-16:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 4.11 0.00 01-JAN-06:30 2563.15 23-FEB-16:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 13.43 0.00 01-JAN-00:15 2168.04 13-JUL-17:30
EnergyTransfer:Zone:T N2 APARTMENT 17.54 0.03 30-OCT-04:15 2558.84 23-FEB-16:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 4.10 0.00 01-JAN-06:30 2558.84 23-FEB-16:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 13.44 0.00 01-JAN-00:15 2147.54 13-JUL-17:30
EnergyTransfer:Zone:T S1 APARTMENT 19.16 0.03 27-SEP-08:30 2652.81 11-OCT-15:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 2.41 0.00 01-JAN-06:30 2463.66 24-DEC-10:30
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 16.76 0.00 01-JAN-00:15 2652.81 11-OCT-15:30
EnergyTransfer:Zone:T S2 APARTMENT 19.18 0.04 24-MAR-00:15 2656.60 11-OCT-15:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 2.42 0.00 01-JAN-06:30 2463.74 24-DEC-10:30
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 16.76 0.00 01-JAN-00:15 2656.60 11-OCT-15:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 965.35 405.47 03-AUG-01:15 217284.23 12-FEB-06:15
WaterSystems:EnergyTransfer 781.94 405.47 03-AUG-01:15 55126.70 02-FEB-08:00
sub cat:WaterSystems:EnergyTransfer 781.94 405.47 03-AUG-01:15 55126.70 02-FEB-08:00
EnergyTransfer:HVAC 2337.18 0.00 01-JAN-11:15 288411.53 20-AUG-15:30
CoolingCoils:EnergyTransfer 2064.82 0.00 01-JAN-00:15 288411.53 20-AUG-15:30
HeatingCoils:EnergyTransfer 272.37 0.00 01-JAN-11:15 216134.00 12-FEB-06:00
PlantLoopHeatingDemand:HVAC 209.22 0.00 01-JAN-11:15 167916.22 12-FEB-06:00
HeatingCoils:PlantLoopHeatingDemand 209.22 0.00 01-JAN-11:15 167916.22 12-FEB-06:00
Boilers:EnergyTransfer 183.41 0.00 01-JAN-09:30 164507.66 12-FEB-06:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 2.022 -12.212 0.000 0.000 3.743 2.413 12.213 17.949 0.000 0.353 0.000 0.000 -7.796 0.000 -5.895 -12.790
G NW APARTMENT 3.557 -9.909 0.000 0.000 3.777 2.413 12.213 10.772 0.000 0.350 0.000 0.000 -8.005 0.000 -5.404 -9.762
OFFICE 1.929 -17.745 0.000 0.000 0.515 21.954 7.547 17.852 0.000 0.196 0.000 0.000 -7.731 0.000 -2.354 -22.163
G NE APARTMENT 3.328 -10.073 0.000 0.000 3.789 2.413 12.213 10.572 0.000 0.350 0.000 0.000 -7.634 0.000 -5.353 -9.604
G N1 APARTMENT 1.689 -8.076 0.000 0.000 3.789 2.413 12.213 4.352 0.000 0.275 0.000 0.000 -4.940 0.000 -4.283 -7.432
G N2 APARTMENT 1.685 -8.081 0.000 0.000 3.790 2.413 12.213 4.351 0.000 0.275 0.000 0.000 -4.937 0.000 -4.281 -7.427
G S1 APARTMENT 0.549 -10.968 0.000 0.000 3.743 2.413 12.213 11.630 0.000 0.273 0.000 0.000 -4.730 0.000 -4.819 -10.304
G S2 APARTMENT 0.525 -11.139 0.000 0.000 3.740 2.413 12.213 11.616 0.000 0.274 0.000 0.000 -4.739 0.000 -4.859 -10.044
F2 SW APARTMENT 1.411 -19.280 0.000 0.000 3.670 2.413 12.213 17.023 0.000 0.467 0.000 0.000 -8.544 0.000 -7.937 -1.435
F2 NW APARTMENT 2.959 -15.237 0.000 0.000 3.724 2.413 12.213 10.120 0.000 0.461 0.000 0.000 -8.714 0.000 -7.293 -0.647
F2 SE APARTMENT 1.213 -20.526 0.000 0.000 3.669 2.413 12.213 16.966 0.000 0.467 0.001 0.000 -8.403 0.000 -8.006 -0.004
F2 NE APARTMENT 2.743 -15.506 0.000 0.000 3.737 2.413 12.213 9.922 0.000 0.460 0.000 0.000 -8.293 0.000 -7.225 -0.463
F2 N1 APARTMENT 0.963 -12.843 0.000 0.000 3.727 2.413 12.213 4.008 0.000 0.349 0.401 0.000 -5.451 0.000 -5.780 -0.000
F2 N2 APARTMENT 0.960 -12.846 0.000 0.000 3.728 2.413 12.213 4.007 0.000 0.349 0.399 0.000 -5.447 0.000 -5.777 -0.000
F2 S1 APARTMENT 0.242 -17.290 0.000 0.000 3.657 2.413 12.213 11.040 0.000 0.351 0.000 0.000 -5.197 0.000 -6.489 -0.940
F2 S2 APARTMENT 0.241 -17.382 0.000 0.000 3.656 2.413 12.213 11.036 0.000 0.352 0.000 0.000 -5.201 0.000 -6.501 -0.826
F3 SW APARTMENT 1.397 -20.397 0.000 0.000 3.661 2.413 12.213 16.634 0.000 0.580 1.186 0.000 -8.739 0.000 -8.947 -0.000
F3 NW APARTMENT 2.941 -16.165 0.000 0.000 3.714 2.413 12.213 9.866 0.000 0.572 1.649 0.000 -8.935 0.000 -8.268 -0.000
F3 SE APARTMENT 1.274 -20.825 0.000 0.000 3.667 2.413 12.213 16.630 0.000 0.578 1.519 0.000 -8.534 0.000 -8.934 -0.000
F3 NE APARTMENT 2.742 -16.437 0.000 0.000 3.726 2.413 12.213 9.674 0.000 0.570 1.798 0.000 -8.500 0.000 -8.199 -0.000
F3 N1 APARTMENT 0.880 -13.923 0.000 0.000 3.712 2.413 12.213 3.893 0.000 0.438 2.537 0.000 -5.617 0.000 -6.545 -0.000
F3 N2 APARTMENT 0.881 -13.930 0.000 0.000 3.713 2.413 12.213 3.892 0.000 0.438 2.534 0.000 -5.613 0.000 -6.541 -0.000
F3 S1 APARTMENT 0.219 -18.783 0.000 0.000 3.641 2.413 12.213 10.789 0.000 0.441 1.686 0.000 -5.335 0.000 -7.284 -0.000
F3 S2 APARTMENT 0.218 -18.809 0.000 0.000 3.641 2.413 12.213 10.787 0.000 0.442 1.717 0.000 -5.335 0.000 -7.287 -0.000
F4 SW APARTMENT 1.516 -20.474 0.000 0.000 3.661 2.413 12.213 16.385 0.000 0.631 1.968 0.000 -8.826 0.000 -9.487 -0.000
F4 NW APARTMENT 3.107 -16.306 0.000 0.000 3.713 2.413 12.213 9.709 0.000 0.623 2.369 0.000 -9.047 0.000 -8.793 -0.000
F4 SE APARTMENT 1.413 -20.775 0.000 0.000 3.668 2.413 12.213 16.399 0.000 0.629 2.106 0.000 -8.606 0.000 -9.459 -0.000
F4 NE APARTMENT 2.908 -16.587 0.000 0.000 3.724 2.413 12.213 9.524 0.000 0.620 2.513 0.000 -8.604 0.000 -8.724 -0.000
F4 N1 APARTMENT 0.922 -14.174 0.000 0.000 3.707 2.413 12.213 3.827 0.000 0.473 3.228 0.000 -5.703 0.000 -6.905 -0.000
F4 N2 APARTMENT 0.920 -14.178 0.000 0.000 3.708 2.413 12.213 3.827 0.000 0.473 3.226 0.000 -5.699 0.000 -6.901 -0.000
F4 S1 APARTMENT 0.242 -19.049 0.000 0.000 3.638 2.413 12.213 10.630 0.000 0.477 2.484 0.000 -5.396 0.000 -7.651 -0.000
F4 S2 APARTMENT 0.243 -19.056 0.000 0.000 3.638 2.413 12.213 10.629 0.000 0.477 2.489 0.000 -5.394 0.000 -7.651 -0.000
M SW APARTMENT 1.629 -20.673 0.000 0.000 3.662 2.413 12.213 16.188 0.000 0.672 2.874 0.000 -8.896 0.000 -10.082 -0.000
M NW APARTMENT 3.240 -16.610 0.000 0.000 3.713 2.413 12.213 9.586 0.000 0.663 3.282 0.000 -9.137 0.000 -9.362 -0.000
M SE APARTMENT 1.527 -20.958 0.000 0.000 3.669 2.413 12.213 16.211 0.000 0.669 2.976 0.000 -8.670 0.000 -10.050 -0.000
M NE APARTMENT 3.037 -16.894 0.000 0.000 3.724 2.413 12.213 9.404 0.000 0.659 3.425 0.000 -8.688 0.000 -9.293 -0.000
M N1 APARTMENT 0.959 -14.548 0.000 0.000 3.705 2.413 12.213 3.776 0.000 0.501 4.084 0.000 -5.770 0.000 -7.333 -0.000
M N2 APARTMENT 0.961 -14.556 0.000 0.000 3.706 2.413 12.213 3.775 0.000 0.500 4.083 0.000 -5.766 0.000 -7.329 -0.000
M S1 APARTMENT 0.270 -19.362 0.000 0.000 3.638 2.413 12.213 10.505 0.000 0.505 3.361 0.000 -5.442 0.000 -8.100 -0.000
M S2 APARTMENT 0.271 -19.365 0.000 0.000 3.638 2.413 12.213 10.504 0.000 0.505 3.361 0.000 -5.440 0.000 -8.099 -0.000
F6 SW APARTMENT 1.913 -19.685 0.000 0.000 3.671 2.413 12.213 16.070 0.000 0.706 2.093 0.000 -8.881 0.000 -10.512 -0.000
F6 NW APARTMENT 3.688 -15.887 0.000 0.000 3.722 2.413 12.213 9.525 0.000 0.696 2.511 0.000 -9.131 0.000 -9.750 -0.000
F6 SE APARTMENT 1.802 -19.972 0.000 0.000 3.679 2.413 12.213 16.100 0.000 0.703 2.193 0.000 -8.653 0.000 -10.478 -0.000
F6 NE APARTMENT 3.485 -16.164 0.000 0.000 3.733 2.413 12.213 9.349 0.000 0.692 2.643 0.000 -8.681 0.000 -9.683 -0.000
F6 N1 APARTMENT 1.186 -13.836 0.000 0.000 3.715 2.413 12.213 3.757 0.000 0.523 3.386 0.000 -5.766 0.000 -7.593 -0.000
F6 N2 APARTMENT 1.187 -13.843 0.000 0.000 3.716 2.413 12.213 3.757 0.000 0.523 3.385 0.000 -5.762 0.000 -7.588 -0.000
F6 S1 APARTMENT 0.352 -18.369 0.000 0.000 3.647 2.413 12.213 10.429 0.000 0.528 2.622 0.000 -5.433 0.000 -8.403 -0.000
F6 S2 APARTMENT 0.355 -18.372 0.000 0.000 3.648 2.413 12.213 10.428 0.000 0.528 2.621 0.000 -5.431 0.000 -8.403 -0.000
F7 SW APARTMENT 2.157 -19.128 0.000 0.000 3.679 2.413 12.213 15.960 0.000 0.734 1.741 0.000 -8.881 0.000 -10.888 -0.000
F7 NW APARTMENT 4.047 -15.525 0.000 0.000 3.729 2.413 12.213 9.464 0.000 0.724 2.174 0.000 -9.140 0.000 -10.099 -0.000
F7 SE APARTMENT 2.041 -19.421 0.000 0.000 3.687 2.413 12.213 15.995 0.000 0.731 1.843 0.000 -8.650 0.000 -10.852 -0.000
F7 NE APARTMENT 3.842 -15.802 0.000 0.000 3.740 2.413 12.213 9.292 0.000 0.720 2.303 0.000 -8.688 0.000 -10.032 -0.000
F7 N1 APARTMENT 1.376 -13.483 0.000 0.000 3.723 2.413 12.213 3.737 0.000 0.542 3.076 0.000 -5.771 0.000 -7.826 -0.000
F7 N2 APARTMENT 1.376 -13.491 0.000 0.000 3.723 2.413 12.213 3.736 0.000 0.542 3.075 0.000 -5.767 0.000 -7.821 -0.000
F7 S1 APARTMENT 0.435 -17.804 0.000 0.000 3.655 2.413 12.213 10.359 0.000 0.548 2.279 0.000 -5.431 0.000 -8.666 -0.000
F7 S2 APARTMENT 0.437 -17.807 0.000 0.000 3.656 2.413 12.213 10.358 0.000 0.548 2.277 0.000 -5.429 0.000 -8.665 -0.000
F8 SW APARTMENT 2.405 -18.760 0.000 0.000 3.685 2.413 12.213 15.862 0.000 0.769 1.542 0.000 -8.882 0.000 -11.248 -0.000
F8 NW APARTMENT 4.406 -15.337 0.000 0.000 3.735 2.413 12.213 9.407 0.000 0.758 1.998 0.000 -9.153 0.000 -10.440 -0.000
F8 SE APARTMENT 2.284 -19.053 0.000 0.000 3.694 2.413 12.213 15.902 0.000 0.764 1.643 0.000 -8.649 0.000 -11.211 -0.000
F8 NE APARTMENT 4.198 -15.608 0.000 0.000 3.745 2.413 12.213 9.239 0.000 0.752 2.120 0.000 -8.700 0.000 -10.373 -0.000
F8 N1 APARTMENT 1.574 -13.286 0.000 0.000 3.729 2.413 12.213 3.717 0.000 0.567 2.911 0.000 -5.777 0.000 -8.061 -0.000
F8 N2 APARTMENT 1.575 -13.293 0.000 0.000 3.730 2.413 12.213 3.717 0.000 0.567 2.910 0.000 -5.773 0.000 -8.057 -0.000
F8 S1 APARTMENT 0.527 -17.412 0.000 0.000 3.662 2.413 12.213 10.298 0.000 0.573 2.079 0.000 -5.430 0.000 -8.923 -0.000
F8 S2 APARTMENT 0.532 -17.418 0.000 0.000 3.663 2.413 12.213 10.297 0.000 0.573 2.078 0.000 -5.428 0.000 -8.923 -0.000
F9 SW APARTMENT 2.886 -18.640 0.000 0.000 3.694 2.413 12.213 15.788 0.000 0.797 1.258 0.000 -8.867 0.000 -11.541 -0.000
F9 NW APARTMENT 5.100 -15.455 0.000 0.000 3.740 2.413 12.213 9.361 0.000 0.785 1.731 0.000 -9.153 0.000 -10.734 -0.000
F9 SE APARTMENT 2.736 -18.943 0.000 0.000 3.702 2.413 12.213 15.831 0.000 0.792 1.392 0.000 -8.633 0.000 -11.503 -0.001
F9 NE APARTMENT 4.861 -15.727 0.000 0.000 3.751 2.413 12.213 9.197 0.000 0.780 1.876 0.000 -8.699 0.000 -10.665 -0.000
F9 N1 APARTMENT 2.014 -13.307 0.000 0.000 3.736 2.413 12.213 3.701 0.000 0.589 2.670 0.000 -5.771 0.000 -8.258 -0.000
F9 N2 APARTMENT 2.015 -13.313 0.000 0.000 3.736 2.413 12.213 3.700 0.000 0.589 2.669 0.000 -5.768 0.000 -8.254 -0.000
F9 S1 APARTMENT 0.732 -17.175 0.000 0.000 3.673 2.413 12.213 10.253 0.000 0.594 1.830 0.000 -5.415 0.000 -9.118 -0.000
F9 S2 APARTMENT 0.736 -17.181 0.000 0.000 3.673 2.413 12.213 10.252 0.000 0.595 1.831 0.000 -5.413 0.000 -9.118 -0.000
T SW APARTMENT 5.716 -18.879 0.000 0.000 3.724 2.413 12.213 15.517 0.000 0.816 0.001 0.000 -8.473 0.000 -11.719 -1.327
T NW APARTMENT 8.045 -15.982 0.000 0.000 3.757 2.413 12.213 9.141 0.000 0.804 0.000 0.000 -8.818 0.000 -10.984 -0.589
T SE APARTMENT 5.439 -18.906 0.000 0.000 3.733 2.413 12.213 15.577 0.000 0.815 0.000 0.000 -8.263 0.000 -11.704 -1.316
T NE APARTMENT 7.589 -15.979 0.000 0.000 3.769 2.413 12.213 9.015 0.000 0.802 0.000 0.000 -8.400 0.000 -10.922 -0.500
T N1 APARTMENT 4.106 -13.432 0.000 0.000 3.756 2.413 12.213 3.630 0.000 0.605 0.625 0.000 -5.537 0.000 -8.378 -0.000
T N2 APARTMENT 4.102 -13.439 0.000 0.000 3.757 2.413 12.213 3.628 0.000 0.604 0.629 0.000 -5.532 0.000 -8.375 -0.000
T S1 APARTMENT 2.409 -16.754 0.000 0.000 3.708 2.413 12.213 10.116 0.000 0.617 0.000 0.000 -5.201 0.000 -9.201 -0.320
T S2 APARTMENT 2.415 -16.762 0.000 0.000 3.709 2.413 12.213 10.113 0.000 0.617 0.001 0.000 -5.198 0.000 -9.204 -0.317
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 4.178 0.000 2.428 2.216 0.000 -1.852 0.000 -25.500 -0.000
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.883 0.000 0.025 0.000 0.000 -1.120 0.000 -0.648 -18.669
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.823 0.000 0.028 0.000 0.000 -1.167 0.000 -0.792 -18.421
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.786 0.000 0.030 0.000 0.000 -1.193 0.000 -0.898 -18.255
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 1.745 0.000 0.026 0.000 0.000 -1.230 0.000 -1.031 -36.569
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.751 0.000 0.035 0.000 0.000 -1.203 0.000 -1.039 -18.073
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.745 0.000 0.037 0.000 0.000 -1.194 0.000 -1.085 -18.033
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.735 0.000 0.039 0.000 0.000 -1.192 0.000 -1.131 -17.980
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.727 0.000 0.039 0.000 0.000 -1.191 0.000 -1.171 -17.933
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 1.668 0.000 0.021 0.000 0.000 -1.167 0.000 -1.247 -25.741
Total Facility 167.816 -1300.580 0.000 0.000 293.221 416.414 980.287 827.874 0.000 47.957 139.491 0.000 -576.391 0.000 -708.197 -287.898


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 08-SEP-16:30 0.00 -2300.68 0.00 0.00 84.10 144.04 588.62 2747.07 0.00 56.03 0.00 0.00 0.00 0.00 0.00 -1319.18
G NW APARTMENT 18-AUG-17:00 0.00 -2215.74 0.00 0.00 84.75 144.04 588.62 2249.88 0.00 82.23 0.00 0.00 0.00 0.00 0.00 -933.78
OFFICE 06-SEP-13:15 0.00 -2942.51 0.00 0.00 65.20 1622.33 544.91 2418.81 0.00 65.13 0.00 0.00 0.00 0.00 0.00 -1773.87
G NE APARTMENT 08-JUL-17:20 0.00 -1684.53 0.00 0.00 140.48 194.45 588.62 1035.74 0.00 41.51 0.00 0.00 0.00 0.00 0.00 -316.26
G N1 APARTMENT 30-JUN-15:38 0.00 -1271.64 0.00 0.00 48.90 100.83 470.89 398.63 0.00 482.36 0.00 0.00 0.00 0.00 0.00 -229.98
G N2 APARTMENT 30-JUN-15:38 0.00 -1262.32 0.00 0.00 48.90 100.83 470.89 398.57 0.00 481.14 0.00 0.00 0.00 0.00 0.00 -238.02
G S1 APARTMENT 15-SEP-13:30 0.00 -1473.65 0.00 0.00 40.75 28.81 382.60 2051.96 0.00 8.12 0.00 0.00 0.00 0.00 0.00 -1038.60
G S2 APARTMENT 15-SEP-13:30 0.00 -1512.45 0.00 0.00 40.75 28.81 382.60 2051.09 0.00 8.12 0.00 0.00 0.00 0.00 0.00 -998.93
F2 SW APARTMENT 11-OCT-15:30 0.00 -3011.89 0.00 0.00 48.91 100.83 470.89 3062.40 0.00 332.53 0.00 0.00 0.00 0.00 0.00 -1003.66
F2 NW APARTMENT 21-JUL-17:20 0.00 -2741.71 0.00 0.00 141.10 194.45 588.62 2247.98 0.00 94.95 0.00 0.00 0.00 0.00 0.00 -525.38
F2 SE APARTMENT 11-OCT-15:30 0.00 -2608.05 0.00 0.00 48.90 100.83 470.89 1702.30 0.00 334.08 0.00 0.00 0.00 0.00 0.00 -48.96
F2 NE APARTMENT 30-JUN-15:38 0.00 -2237.68 0.00 0.00 48.90 100.83 470.89 605.16 0.00 694.06 317.84 0.00 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 30-JUN-15:38 0.00 -1655.21 0.00 0.00 48.90 100.83 470.89 365.45 0.00 637.85 31.28 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 30-JUN-15:38 0.00 -1647.89 0.00 0.00 48.90 100.83 470.89 365.37 0.00 636.44 25.46 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 11-OCT-16:38 0.00 -1988.50 0.00 0.00 84.36 144.04 588.62 700.20 0.00 47.58 423.70 0.00 0.00 0.00 0.00 0.00
F2 S2 APARTMENT 11-OCT-16:30 0.00 -2004.31 0.00 0.00 83.82 144.04 588.62 907.52 0.00 92.49 187.83 0.00 0.00 0.00 0.00 0.00
F3 SW APARTMENT 11-OCT-15:30 0.00 -3047.44 0.00 0.00 48.91 100.83 470.89 3004.44 0.00 362.97 0.00 0.00 0.00 0.00 0.00 -940.60
F3 NW APARTMENT 21-JUL-17:20 0.00 -2759.36 0.00 0.00 141.14 194.45 588.62 2224.15 0.00 112.21 0.00 0.00 0.00 0.00 0.00 -501.21
F3 SE APARTMENT 11-OCT-15:30 0.00 -2625.29 0.00 0.00 48.90 100.83 470.89 1677.32 0.00 371.39 0.00 0.00 0.00 0.00 0.00 -44.05
F3 NE APARTMENT 30-JUN-15:38 0.00 -2276.42 0.00 0.00 48.90 100.83 470.89 588.69 0.00 790.08 277.03 0.00 0.00 0.00 0.00 0.00
F3 N1 APARTMENT 30-JUN-15:38 0.00 -1694.82 0.00 0.00 48.90 100.83 470.89 354.13 0.00 724.02 0.00 0.00 0.00 0.00 0.00 -3.95
F3 N2 APARTMENT 30-JUN-15:38 0.00 -1687.51 0.00 0.00 48.90 100.83 470.89 354.05 0.00 722.44 0.00 0.00 0.00 0.00 0.00 -9.60
F3 S1 APARTMENT 11-OCT-16:38 0.00 -2100.88 0.00 0.00 83.80 144.04 588.62 683.30 0.00 43.24 557.87 0.00 0.00 0.00 0.00 0.00
F3 S2 APARTMENT 11-OCT-16:38 0.00 -2107.56 0.00 0.00 83.89 144.04 588.62 683.63 0.00 45.48 561.90 0.00 0.00 0.00 0.00 0.00
F4 SW APARTMENT 11-OCT-15:30 0.00 -3058.13 0.00 0.00 48.91 100.83 470.89 2964.46 0.00 389.66 0.00 0.00 0.00 0.00 0.00 -916.61
F4 NW APARTMENT 21-JUL-17:20 0.00 -2770.86 0.00 0.00 141.18 194.45 588.62 2206.36 0.00 125.18 0.00 0.00 0.00 0.00 0.00 -484.94
F4 SE APARTMENT 11-OCT-15:30 0.00 -2627.91 0.00 0.00 48.91 100.83 470.89 1659.40 0.00 396.82 0.00 0.00 0.00 0.00 0.00 -48.94
F4 NE APARTMENT 30-JUN-15:38 0.00 -2294.59 0.00 0.00 48.90 100.83 470.89 577.98 0.00 858.49 237.49 0.00 0.00 0.00 0.00 0.00
F4 N1 APARTMENT 30-JUN-15:38 0.00 -1714.83 0.00 0.00 48.90 100.83 470.89 346.98 0.00 786.11 0.00 0.00 0.00 0.00 0.00 -38.88
F4 N2 APARTMENT 30-JUN-15:38 0.00 -1707.59 0.00 0.00 48.90 100.83 470.89 346.90 0.00 784.39 0.00 0.00 0.00 0.00 0.00 -44.32
F4 S1 APARTMENT 11-OCT-16:38 0.00 -2124.89 0.00 0.00 83.80 144.04 588.62 673.73 0.00 45.38 589.32 0.00 0.00 0.00 0.00 0.00
F4 S2 APARTMENT 11-OCT-16:38 0.00 -2130.14 0.00 0.00 83.87 144.04 588.62 674.04 0.00 47.56 592.02 0.00 0.00 0.00 0.00 0.00
M SW APARTMENT 11-OCT-15:30 0.00 -3090.17 0.00 0.00 48.91 100.83 470.89 2932.63 0.00 412.30 0.00 0.00 0.00 0.00 0.00 -875.38
M NW APARTMENT 02-AUG-17:10 0.00 -2806.99 0.00 0.00 141.82 194.45 588.62 2136.35 0.00 133.01 0.00 0.00 0.00 0.00 0.00 -387.26
M SE APARTMENT 11-OCT-15:30 0.00 -2663.61 0.00 0.00 48.91 100.83 470.89 1644.85 0.00 419.31 0.00 0.00 0.00 0.00 0.00 -21.18
M NE APARTMENT 30-JUN-15:38 0.00 -2334.80 0.00 0.00 48.90 100.83 470.89 569.09 0.00 912.14 232.94 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 30-JUN-15:38 0.00 -1755.79 0.00 0.00 48.90 100.83 470.89 341.08 0.00 834.87 0.00 0.00 0.00 0.00 0.00 -40.78
M N2 APARTMENT 30-JUN-15:38 0.00 -1748.62 0.00 0.00 48.90 100.83 470.89 341.00 0.00 833.04 0.00 0.00 0.00 0.00 0.00 -46.04
M S1 APARTMENT 11-OCT-16:38 0.00 -2167.68 0.00 0.00 83.92 144.04 588.62 666.44 0.00 49.85 634.81 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 11-OCT-16:38 0.00 -2172.74 0.00 0.00 83.99 144.04 588.62 666.73 0.00 52.10 637.26 0.00 0.00 0.00 0.00 0.00
F6 SW APARTMENT 11-OCT-15:30 0.00 -3048.56 0.00 0.00 48.91 100.83 470.89 2908.33 0.00 431.00 0.00 0.00 0.00 0.00 0.00 -911.40
F6 NW APARTMENT 18-AUG-17:10 0.00 -2775.55 0.00 0.00 141.83 194.45 588.62 2081.87 0.00 182.93 0.00 0.00 0.00 0.00 0.00 -414.15
F6 SE APARTMENT 11-OCT-15:30 0.00 -2627.78 0.00 0.00 48.91 100.83 470.89 1634.86 0.00 438.01 0.00 0.00 0.00 0.00 0.00 -65.72
F6 NE APARTMENT 30-JUN-15:38 0.00 -2302.64 0.00 0.00 48.90 100.83 470.89 564.01 0.00 954.23 163.77 0.00 0.00 0.00 0.00 0.00
F6 N1 APARTMENT 06-JUN-19:08 0.00 -1735.73 0.00 0.00 141.82 230.46 523.87 39.54 0.00 443.24 356.80 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 06-JUN-19:08 0.00 -1733.23 0.00 0.00 141.82 230.46 523.87 39.61 0.00 443.25 354.23 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 11-OCT-16:38 0.00 -2137.57 0.00 0.00 84.03 144.04 588.62 661.83 0.00 53.64 605.41 0.00 0.00 0.00 0.00 0.00
F6 S2 APARTMENT 11-OCT-16:38 0.00 -2142.64 0.00 0.00 84.10 144.04 588.62 662.11 0.00 55.98 607.78 0.00 0.00 0.00 0.00 0.00
F7 SW APARTMENT 11-OCT-15:30 0.00 -3033.24 0.00 0.00 48.91 100.83 470.89 2886.99 0.00 447.40 0.00 0.00 0.00 0.00 0.00 -921.77
F7 NW APARTMENT 18-AUG-17:10 0.00 -2769.42 0.00 0.00 141.83 194.45 588.62 2075.25 0.00 192.92 0.00 0.00 0.00 0.00 0.00 -423.64
F7 SE APARTMENT 11-OCT-15:30 0.00 -2617.22 0.00 0.00 48.91 100.83 470.89 1625.70 0.00 454.41 0.00 0.00 0.00 0.00 0.00 -83.52
F7 NE APARTMENT 30-JUN-15:38 0.00 -2296.09 0.00 0.00 48.90 100.83 470.89 559.02 0.00 989.63 126.81 0.00 0.00 0.00 0.00 0.00
F7 N1 APARTMENT 06-JUN-19:08 0.00 -1740.35 0.00 0.00 141.82 230.46 523.87 39.40 0.00 460.42 344.38 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 06-JUN-19:08 0.00 -1737.96 0.00 0.00 141.82 230.46 523.87 39.47 0.00 460.43 341.92 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 11-OCT-16:38 0.00 -2111.72 0.00 0.00 84.17 144.04 588.62 657.62 0.00 55.90 581.37 0.00 0.00 0.00 0.00 0.00
F7 S2 APARTMENT 11-OCT-16:38 0.00 -2090.95 0.00 0.00 84.24 144.04 588.62 657.90 0.00 56.10 560.05 0.00 0.00 0.00 0.00 0.00
F8 SW APARTMENT 11-OCT-15:30 0.00 -3032.28 0.00 0.00 48.91 100.83 470.89 2868.09 0.00 462.52 0.00 0.00 0.00 0.00 0.00 -918.95
F8 NW APARTMENT 18-AUG-17:10 0.00 -2775.86 0.00 0.00 141.83 194.45 588.62 2068.95 0.00 201.85 0.00 0.00 0.00 0.00 0.00 -419.83
F8 SE APARTMENT 11-OCT-15:30 0.00 -2619.73 0.00 0.00 48.91 100.83 470.89 1617.44 0.00 469.60 0.00 0.00 0.00 0.00 0.00 -87.94
F8 NE APARTMENT 30-JUN-15:38 0.00 -2303.08 0.00 0.00 48.90 100.83 470.89 554.25 0.00 1020.18 108.02 0.00 0.00 0.00 0.00 0.00
F8 N1 APARTMENT 06-JUN-19:08 0.00 -1753.13 0.00 0.00 141.82 230.46 523.87 38.94 0.00 474.65 343.39 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 06-JUN-19:08 0.00 -1750.81 0.00 0.00 141.82 230.46 523.87 39.01 0.00 474.65 341.00 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 11-OCT-16:30 0.00 -2063.97 0.00 0.00 83.56 144.04 588.62 851.73 0.00 121.12 274.89 0.00 0.00 0.00 0.00 0.00
F8 S2 APARTMENT 11-OCT-16:30 0.00 -2068.90 0.00 0.00 83.63 144.04 588.62 851.97 0.00 123.49 277.15 0.00 0.00 0.00 0.00 0.00
F9 SW APARTMENT 11-OCT-15:30 0.00 -3103.74 0.00 0.00 48.91 100.83 470.89 2850.50 0.00 482.74 0.00 0.00 0.00 0.00 0.00 -850.12
F9 NW APARTMENT 18-AUG-17:10 0.00 -2863.43 0.00 0.00 141.83 194.45 588.62 2060.35 0.00 209.95 0.00 0.00 0.00 0.00 0.00 -331.76
F9 SE APARTMENT 11-OCT-15:30 0.00 -2647.89 0.00 0.00 48.91 100.83 470.89 1609.20 0.00 483.17 0.00 0.00 0.00 0.00 0.00 -65.11
F9 NE APARTMENT 30-JUN-15:38 0.00 -2353.41 0.00 0.00 48.90 100.83 470.89 547.49 0.00 1044.22 141.07 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 06-JUN-19:08 0.00 -1814.27 0.00 0.00 141.82 230.46 523.87 36.84 0.00 486.48 394.80 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 06-JUN-19:08 0.00 -1811.90 0.00 0.00 141.82 230.46 523.87 36.90 0.00 486.48 392.36 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 30-MAR-17:00 0.00 -2109.65 0.00 0.00 84.76 144.04 588.62 587.36 0.00 676.71 28.16 0.00 0.00 0.00 0.00 0.00
F9 S2 APARTMENT 30-MAR-17:00 0.00 -2114.52 0.00 0.00 84.76 144.04 588.62 587.52 0.00 679.47 30.11 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 18-AUG-16:30 0.00 -3608.91 0.00 0.00 83.88 144.04 588.62 2315.23 0.00 203.22 273.91 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 08-JUL-16:30 0.00 -3467.58 0.00 0.00 84.25 144.04 588.62 2261.98 0.00 120.54 268.16 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 18-AUG-13:00 0.00 -3208.05 0.00 0.00 40.41 28.81 388.49 1967.05 0.00 108.25 675.04 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 08-JUL-16:30 0.00 -2832.94 0.00 0.00 84.14 144.04 588.62 1140.59 0.00 120.58 754.96 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 30-JUN-15:38 0.00 -2193.02 0.00 0.00 48.90 100.83 470.89 313.32 0.00 1011.14 247.94 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 30-JUN-15:38 0.00 -2176.19 0.00 0.00 48.90 100.83 470.89 313.32 0.00 1007.26 234.99 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 11-OCT-15:30 0.00 -2653.83 0.00 0.00 48.91 100.83 470.89 1439.17 0.00 457.42 136.61 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 11-OCT-15:30 0.00 -2657.61 0.00 0.00 48.91 100.83 470.89 1439.31 0.00 459.28 138.39 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 01-AUG-16:30 0.00 -169277.06 0.00 0.00 6657.08 18221.75 47207.76 101373.12 0.00 16658.67 0.00 0.00 0.00 0.00 0.00 -20841.32


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 12-FEB-06:00 1718.44 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1463.30 0.00 -669.25 -122.29
G NW APARTMENT 12-FEB-06:00 1767.05 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1467.26 0.00 -669.25 -166.94
OFFICE 12-FEB-07:00 1830.20 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 0.00 0.00 -1457.30 0.00 -600.02 -281.14
G NE APARTMENT 12-FEB-06:00 1788.04 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1460.70 0.00 -669.25 -194.49
G N1 APARTMENT 23-FEB-15:40 1707.66 0.00 0.00 0.00 45.87 50.41 400.26 146.19 0.00 0.00 0.00 0.00 0.00 0.00 -1484.42 -865.98
G N2 APARTMENT 23-FEB-15:40 1695.81 0.00 0.00 0.00 45.84 50.41 400.26 145.90 0.00 0.00 0.00 0.00 0.00 0.00 -1484.87 -853.35
G S1 APARTMENT 24-DEC-09:25 1274.23 0.00 0.00 0.00 46.75 28.81 394.37 68.37 0.00 0.00 0.00 0.00 0.00 0.00 -1246.09 -566.44
G S2 APARTMENT 24-DEC-09:25 1291.32 0.00 0.00 0.00 46.70 28.81 394.37 67.96 0.00 0.00 0.00 0.00 0.00 0.00 -1246.22 -582.94
F2 SW APARTMENT 12-FEB-06:00 1904.59 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 36.22 0.00 -1514.87 0.00 -962.34 0.00
F2 NW APARTMENT 12-FEB-06:00 2026.28 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1526.54 0.00 -962.34 -73.80
F2 SE APARTMENT 12-FEB-06:00 1915.52 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 12.80 0.00 -1502.38 0.00 -962.34 0.00
F2 NE APARTMENT 12-FEB-06:00 2054.59 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1513.50 0.00 -962.34 -115.16
F2 N1 APARTMENT 23-FEB-15:45 1601.03 0.00 0.00 0.00 43.73 50.41 400.26 97.71 0.00 0.00 0.00 0.00 0.00 0.00 -1935.37 -257.77
F2 N2 APARTMENT 23-FEB-15:45 1605.09 0.00 0.00 0.00 43.70 50.41 400.26 97.24 0.00 0.00 0.00 0.00 0.00 0.00 -1935.40 -261.31
F2 S1 APARTMENT 19-JAN-10:55 1417.13 0.00 0.00 0.00 45.58 28.81 406.15 220.86 0.00 0.00 0.00 0.00 0.00 0.00 -1558.73 -559.79
F2 S2 APARTMENT 19-JAN-10:55 1380.58 0.00 0.00 0.00 45.53 28.81 406.15 220.36 0.00 0.00 0.00 0.00 0.00 0.00 -1560.01 -521.41
F3 SW APARTMENT 12-FEB-06:00 2014.37 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 125.96 0.00 -1536.94 0.00 -1139.79 0.00
F3 NW APARTMENT 12-FEB-06:00 2147.91 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 7.95 0.00 -1552.47 0.00 -1139.79 0.00
F3 SE APARTMENT 12-FEB-06:00 2031.83 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 92.74 0.00 -1521.18 0.00 -1139.79 0.00
F3 NE APARTMENT 12-FEB-06:00 2172.62 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1536.56 0.00 -1139.79 -32.67
F3 N1 APARTMENT 23-FEB-15:45 1937.37 0.00 0.00 0.00 43.02 50.41 400.26 78.30 0.00 0.00 0.00 0.00 0.00 0.00 -2229.35 -280.01
F3 N2 APARTMENT 23-FEB-15:45 1937.91 0.00 0.00 0.00 42.99 50.41 400.26 77.87 0.00 0.00 0.00 0.00 0.00 0.00 -2229.37 -280.07
F3 S1 APARTMENT 24-DEC-09:25 1544.43 0.00 0.00 0.00 45.11 28.81 394.37 16.03 0.00 0.00 0.00 0.00 0.00 0.00 -1776.49 -252.26
F3 S2 APARTMENT 24-DEC-09:25 1539.58 0.00 0.00 0.00 45.10 28.81 394.37 15.98 0.00 0.00 0.00 0.00 0.00 0.00 -1776.67 -247.18
F4 SW APARTMENT 12-FEB-06:00 2137.96 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 150.65 0.00 -1550.53 0.00 -1274.48 0.00
F4 NW APARTMENT 12-FEB-06:00 2275.78 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 30.94 0.00 -1568.64 0.00 -1274.48 0.00
F4 SE APARTMENT 12-FEB-06:00 2156.75 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 114.13 0.00 -1532.80 0.00 -1274.48 0.00
F4 NE APARTMENT 12-FEB-06:00 2297.83 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1550.94 0.00 -1274.48 -8.81
F4 N1 APARTMENT 23-FEB-15:45 1988.91 0.00 0.00 0.00 42.90 50.41 400.26 69.54 0.00 0.00 0.00 0.00 0.00 0.00 -2459.66 -92.37
F4 N2 APARTMENT 23-FEB-15:45 1991.10 0.00 0.00 0.00 42.87 50.41 400.26 69.12 0.00 0.00 0.00 0.00 0.00 0.00 -2459.68 -94.09
F4 S1 APARTMENT 24-DEC-09:25 1848.00 0.00 0.00 0.00 45.06 28.81 394.37 7.94 0.00 0.00 0.00 0.00 0.00 0.00 -1937.60 -386.57
F4 S2 APARTMENT 24-DEC-09:25 1850.27 0.00 0.00 0.00 45.06 28.81 394.37 8.01 0.00 0.00 0.00 0.00 0.00 0.00 -1937.54 -388.98
M SW APARTMENT 12-FEB-06:00 2231.80 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 178.73 0.00 -1561.33 0.00 -1385.60 0.00
M NW APARTMENT 12-FEB-06:00 2368.92 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 61.64 0.00 -1581.36 0.00 -1385.60 0.00
M SE APARTMENT 12-FEB-06:00 2249.74 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 141.71 0.00 -1542.25 0.00 -1385.60 0.00
M NE APARTMENT 12-FEB-06:00 2388.91 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 22.66 0.00 -1562.37 0.00 -1385.60 0.00
M N1 APARTMENT 23-FEB-15:45 2035.38 0.00 0.00 0.00 42.89 50.41 400.26 64.26 0.00 0.00 61.08 0.00 0.00 0.00 -2654.29 0.00
M N2 APARTMENT 23-FEB-15:45 2037.20 0.00 0.00 0.00 42.85 50.41 400.26 63.84 0.00 0.00 59.74 0.00 0.00 0.00 -2654.30 0.00
M S1 APARTMENT 24-DEC-09:25 2095.97 0.00 0.00 0.00 45.03 28.81 394.37 1.78 0.00 0.00 0.00 0.00 0.00 0.00 -2074.97 -490.98
M S2 APARTMENT 24-DEC-09:25 2100.26 0.00 0.00 0.00 45.04 28.81 394.37 1.90 0.00 0.00 0.00 0.00 0.00 0.00 -2074.85 -495.53
F6 SW APARTMENT 12-FEB-06:00 2373.27 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 139.35 0.00 -1567.58 0.00 -1481.44 0.00
F6 NW APARTMENT 12-FEB-06:00 2510.47 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 23.83 0.00 -1589.26 0.00 -1481.44 0.00
F6 SE APARTMENT 12-FEB-06:00 2390.07 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 102.51 0.00 -1547.55 0.00 -1481.44 0.00
F6 NE APARTMENT 23-FEB-15:40 2716.98 0.00 0.00 0.00 44.00 50.41 400.26 116.31 0.00 0.00 0.00 0.00 0.00 0.00 -2978.57 -349.38
F6 N1 APARTMENT 23-FEB-15:40 2479.61 0.00 0.00 0.00 43.39 50.41 400.26 65.95 0.00 0.00 0.00 0.00 0.00 0.00 -2850.92 -188.70
F6 N2 APARTMENT 23-FEB-15:40 2454.53 0.00 0.00 0.00 43.36 50.41 400.26 65.53 0.00 0.00 0.00 0.00 0.00 0.00 -2851.44 -162.65
F6 S1 APARTMENT 24-DEC-09:25 2532.26 0.00 0.00 0.00 45.39 28.81 394.37 1.69 0.00 0.00 0.00 0.00 0.00 0.00 -2189.85 -812.66
F6 S2 APARTMENT 24-DEC-09:25 2529.97 0.00 0.00 0.00 45.39 28.81 394.37 1.81 0.00 0.00 0.00 0.00 0.00 0.00 -2189.86 -810.49
F7 SW APARTMENT 12-FEB-06:00 2485.26 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 118.14 0.00 -1573.37 0.00 -1566.43 0.00
F7 NW APARTMENT 23-FEB-15:40 2962.33 0.00 0.00 0.00 44.16 50.41 400.26 874.39 0.00 0.00 0.00 0.00 0.00 0.00 -3139.11 -1192.44
F7 SE APARTMENT 12-FEB-06:00 2500.95 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 81.65 0.00 -1552.56 0.00 -1566.43 0.00
F7 NE APARTMENT 23-FEB-15:40 3252.52 0.00 0.00 0.00 44.42 50.41 400.26 118.60 0.00 0.00 0.00 0.00 0.00 0.00 -3128.83 -737.38
F7 N1 APARTMENT 23-FEB-15:40 3039.63 0.00 0.00 0.00 43.80 50.41 400.26 67.28 0.00 0.00 0.00 0.00 0.00 0.00 -2994.91 -606.47
F7 N2 APARTMENT 23-FEB-15:40 3015.17 0.00 0.00 0.00 43.77 50.41 400.26 66.86 0.00 0.00 0.00 0.00 0.00 0.00 -2995.45 -581.02
F7 S1 APARTMENT 24-DEC-09:25 2568.48 0.00 0.00 0.00 45.65 28.81 394.37 1.20 0.00 0.00 0.00 0.00 0.00 0.00 -2301.28 -737.23
F7 S2 APARTMENT 24-DEC-09:25 2566.84 0.00 0.00 0.00 45.65 28.81 394.37 1.30 0.00 0.00 0.00 0.00 0.00 0.00 -2301.29 -735.68
F8 SW APARTMENT 12-FEB-06:00 2591.57 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 93.51 0.00 -1578.22 0.00 -1643.26 0.00
F8 NW APARTMENT 23-FEB-15:40 3407.71 0.00 0.00 0.00 44.49 50.41 400.26 867.61 0.00 0.00 0.00 0.00 0.00 0.00 -3277.21 -1493.28
F8 SE APARTMENT 12-FEB-06:00 2606.67 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 56.96 0.00 -1556.77 0.00 -1643.26 0.00
F8 NE APARTMENT 23-FEB-15:40 3485.49 0.00 0.00 0.00 44.75 50.41 400.26 120.21 0.00 0.00 0.00 0.00 0.00 0.00 -3273.18 -827.94
F8 N1 APARTMENT 23-FEB-15:40 3506.46 0.00 0.00 0.00 44.13 50.41 400.26 68.37 0.00 0.00 0.00 0.00 0.00 0.00 -3128.12 -941.51
F8 N2 APARTMENT 23-FEB-15:40 3484.55 0.00 0.00 0.00 44.10 50.41 400.26 67.98 0.00 0.00 0.00 0.00 0.00 0.00 -3128.65 -918.65
F8 S1 APARTMENT 24-DEC-09:25 2608.05 0.00 0.00 0.00 45.87 28.81 394.37 0.74 0.00 0.00 0.00 0.00 0.00 0.00 -2403.97 -673.87
F8 S2 APARTMENT 24-DEC-09:25 2607.01 0.00 0.00 0.00 45.87 28.81 394.37 0.81 0.00 0.00 0.00 0.00 0.00 0.00 -2403.97 -672.91
F9 SW APARTMENT 12-FEB-06:00 2801.33 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1578.62 0.00 -1713.68 -45.43
F9 NW APARTMENT 23-FEB-15:40 3491.24 0.00 0.00 0.00 44.89 50.41 400.26 865.17 0.00 0.00 0.00 0.00 0.00 0.00 -3413.90 -1438.08
F9 SE APARTMENT 12-FEB-06:00 2816.17 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1556.72 0.00 -1713.68 -82.17
F9 NE APARTMENT 23-FEB-15:40 3524.71 0.00 0.00 0.00 45.17 50.41 400.26 124.66 0.00 0.00 0.00 0.00 0.00 0.00 -3411.03 -734.18
F9 N1 APARTMENT 23-FEB-15:40 3699.07 0.00 0.00 0.00 44.60 50.41 400.26 72.15 0.00 0.00 0.00 0.00 0.00 0.00 -3255.42 -1011.07
F9 N2 APARTMENT 23-FEB-15:40 3707.45 0.00 0.00 0.00 44.57 50.41 400.26 71.71 0.00 0.00 0.00 0.00 0.00 0.00 -3255.44 -1018.97
F9 S1 APARTMENT 24-DEC-09:25 2612.31 0.00 0.00 0.00 46.19 28.81 394.37 2.21 0.00 0.00 0.00 0.00 0.00 0.00 -2499.59 -584.30
F9 S2 APARTMENT 24-DEC-09:25 2611.97 0.00 0.00 0.00 46.19 28.81 394.37 2.25 0.00 0.00 0.00 0.00 0.00 0.00 -2499.60 -584.00
T SW APARTMENT 12-FEB-06:00 3627.48 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1544.86 0.00 -1778.78 -840.24
T NW APARTMENT 23-FEB-15:40 3741.60 0.00 0.00 0.00 44.49 50.41 400.26 843.94 0.00 0.00 0.00 0.00 0.00 0.00 -3548.69 -1532.01
T SE APARTMENT 12-FEB-06:00 3624.80 0.00 0.00 0.00 189.67 93.62 253.11 0.00 0.00 0.00 0.00 0.00 -1523.69 0.00 -1778.78 -858.73
T NE APARTMENT 23-FEB-15:40 3709.80 0.00 0.00 0.00 45.12 50.41 400.26 120.89 0.00 0.00 0.00 0.00 0.00 0.00 -3543.25 -783.23
T N1 APARTMENT 23-FEB-15:40 3934.11 0.00 0.00 0.00 44.65 50.41 400.26 73.79 0.00 0.00 0.00 0.00 0.00 0.00 -3380.95 -1122.27
T N2 APARTMENT 23-FEB-15:40 3944.60 0.00 0.00 0.00 44.61 50.41 400.26 73.27 0.00 0.00 0.00 0.00 0.00 0.00 -3380.92 -1132.24
T S1 APARTMENT 24-DEC-09:25 2624.19 0.00 0.00 0.00 46.48 28.81 394.37 6.78 0.00 0.00 0.00 0.00 0.00 0.00 -2590.34 -510.28
T S2 APARTMENT 24-DEC-09:25 2625.12 0.00 0.00 0.00 46.47 28.81 394.37 6.77 0.00 0.00 0.00 0.00 0.00 0.00 -2590.36 -511.18
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-FEB-06:00 149854.66 0.00 0.00 0.00 14984.00 14239.10 20328.82 0.00 0.00 0.00 0.00 0.00 -101906.20 0.00 -89615.92 -7884.45



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Sec1.1A-General Information

Data
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 90.75
Number of hours cooling loads not met 176.00
Number of hours not met 266.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.68 10720.10 0.00 0.00 0.00 0.00
Space Heating 74.33 0.00 229.94 196926.82 0.00 0.00
Space Cooling 606.11 70064.65 0.00 0.00 0.00 0.00
Pumps 48.82 1624.92 0.00 0.00 0.00 0.00
Heat Rejection 27.19 2877.91 0.00 0.00 0.00 0.00
Fans-Interior 546.99 17344.92 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1030.26 79629.86 0.00 0.00
Receptacle Equipment 1131.09 49704.83 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3040.45   1260.20   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3040.45
Natural Gas 0.00 1260.20
Additional 0.00 0.00
Total 1131.09 4300.65


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 9.48
Space Cooling 77.34
Fans-Interior 69.80
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 33.88
Subtotal 387.99


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 29.34
Service Water Heating 131.47
Miscellaneous -0.00
Subtotal 160.81


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 9.68
Space Heating 7.07
Space Cooling 14.09
Fans-Interior 12.72
Service Water Heating 23.96
Receptacle Equipment 26.30
Miscellaneous 6.17



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.201855
G NW APARTMENT DIRECT AIR 0.201851
OFFICE DIRECT AIR 0.271360
G NE APARTMENT DIRECT AIR 0.155908
G N1 APARTMENT DIRECT AIR 0.113606
G N2 APARTMENT DIRECT AIR 0.112451
G S1 APARTMENT DIRECT AIR 0.111740
G S2 APARTMENT DIRECT AIR 0.116508
F2 SW APARTMENT DIRECT AIR 0.252921
F2 NW APARTMENT DIRECT AIR 0.249734
F2 SE APARTMENT DIRECT AIR 0.229786
F2 NE APARTMENT DIRECT AIR 0.199095
F2 N1 APARTMENT DIRECT AIR 0.145992
F2 N2 APARTMENT DIRECT AIR 0.145068
F2 S1 APARTMENT DIRECT AIR 0.146501
F2 S2 APARTMENT DIRECT AIR 0.148168
F3 SW APARTMENT DIRECT AIR 0.253459
F3 NW APARTMENT DIRECT AIR 0.250577
F3 SE APARTMENT DIRECT AIR 0.216121
F3 NE APARTMENT DIRECT AIR 0.201657
F3 N1 APARTMENT DIRECT AIR 0.148495
F3 N2 APARTMENT DIRECT AIR 0.147588
F3 S1 APARTMENT DIRECT AIR 0.149406
F3 S2 APARTMENT DIRECT AIR 0.150132
F4 SW APARTMENT DIRECT AIR 0.254105
F4 NW APARTMENT DIRECT AIR 0.251106
F4 SE APARTMENT DIRECT AIR 0.215699
F4 NE APARTMENT DIRECT AIR 0.202702
F4 N1 APARTMENT DIRECT AIR 0.149784
F4 N2 APARTMENT DIRECT AIR 0.148889
F4 S1 APARTMENT DIRECT AIR 0.150860
F4 S2 APARTMENT DIRECT AIR 0.151447
M SW APARTMENT DIRECT AIR 0.256974
M NW APARTMENT DIRECT AIR 0.253949
M SE APARTMENT DIRECT AIR 0.218783
M NE APARTMENT DIRECT AIR 0.205916
M N1 APARTMENT DIRECT AIR 0.153097
M N2 APARTMENT DIRECT AIR 0.152212
M S1 APARTMENT DIRECT AIR 0.154239
M S2 APARTMENT DIRECT AIR 0.154806
F6 SW APARTMENT DIRECT AIR 0.253469
F6 NW APARTMENT DIRECT AIR 0.250263
F6 SE APARTMENT DIRECT AIR 0.215661
F6 NE APARTMENT DIRECT AIR 0.202641
F6 N1 APARTMENT DIRECT AIR 0.150060
F6 N2 APARTMENT DIRECT AIR 0.149188
F6 S1 APARTMENT DIRECT AIR 0.151365
F6 S2 APARTMENT DIRECT AIR 0.151929
F7 SW APARTMENT DIRECT AIR 0.252315
F7 NW APARTMENT DIRECT AIR 0.249049
F7 SE APARTMENT DIRECT AIR 0.214837
F7 NE APARTMENT DIRECT AIR 0.201757
F7 N1 APARTMENT DIRECT AIR 0.149318
F7 N2 APARTMENT DIRECT AIR 0.148456
F7 S1 APARTMENT DIRECT AIR 0.150691
F7 S2 APARTMENT DIRECT AIR 0.151255
F8 SW APARTMENT DIRECT AIR 0.252579
F8 NW APARTMENT DIRECT AIR 0.249254
F8 SE APARTMENT DIRECT AIR 0.215331
F8 NE APARTMENT DIRECT AIR 0.202184
F8 N1 APARTMENT DIRECT AIR 0.149926
F8 N2 APARTMENT DIRECT AIR 0.149075
F8 S1 APARTMENT DIRECT AIR 0.151311
F8 S2 APARTMENT DIRECT AIR 0.151875
F9 SW APARTMENT DIRECT AIR 0.261045
F9 NW APARTMENT DIRECT AIR 0.257502
F9 SE APARTMENT DIRECT AIR 0.219993
F9 NE APARTMENT DIRECT AIR 0.206266
F9 N1 APARTMENT DIRECT AIR 0.157498
F9 N2 APARTMENT DIRECT AIR 0.156647
F9 S1 APARTMENT DIRECT AIR 0.157012
F9 S2 APARTMENT DIRECT AIR 0.157643
T SW APARTMENT DIRECT AIR 0.312952
T NW APARTMENT DIRECT AIR 0.305479
T SE APARTMENT DIRECT AIR 0.272189
T NE APARTMENT DIRECT AIR 0.250279
T N1 APARTMENT DIRECT AIR 0.191249
T N2 APARTMENT DIRECT AIR 0.189338
T S1 APARTMENT DIRECT AIR 0.215507
T S2 APARTMENT DIRECT AIR 0.216108


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.201855
AIRLOOP G NW MAIN BRANCH 0.201851
AIRLOOP OFFICE MAIN BRANCH 0.271360
AIRLOOP G NE MAIN BRANCH 0.155908
AIRLOOP G N1 MAIN BRANCH 0.113606
AIRLOOP G N2 MAIN BRANCH 0.112451
AIRLOOP G S1 MAIN BRANCH 0.111740
AIRLOOP G S2 MAIN BRANCH 0.116508
AIRLOOP F2 SW MAIN BRANCH 0.252921
AIRLOOP F2 NW MAIN BRANCH 0.249734
AIRLOOP F2 SE MAIN BRANCH 0.229786
AIRLOOP F2 NE MAIN BRANCH 0.199095
AIRLOOP F2 N1 MAIN BRANCH 0.145992
AIRLOOP F2 N2 MAIN BRANCH 0.145068
AIRLOOP F2 S1 MAIN BRANCH 0.146501
AIRLOOP F2 S2 MAIN BRANCH 0.148168
AIRLOOP F3 SW MAIN BRANCH 0.253459
AIRLOOP F3 NW MAIN BRANCH 0.250577
AIRLOOP F3 SE MAIN BRANCH 0.216121
AIRLOOP F3 NE MAIN BRANCH 0.201657
AIRLOOP F3 N1 MAIN BRANCH 0.148495
AIRLOOP F3 N2 MAIN BRANCH 0.147588
AIRLOOP F3 S1 MAIN BRANCH 0.149406
AIRLOOP F3 S2 MAIN BRANCH 0.150132
AIRLOOP F4 SW MAIN BRANCH 0.254105
AIRLOOP F4 NW MAIN BRANCH 0.251106
AIRLOOP F4 SE MAIN BRANCH 0.215699
AIRLOOP F4 NE MAIN BRANCH 0.202702
AIRLOOP F4 N1 MAIN BRANCH 0.149784
AIRLOOP F4 N2 MAIN BRANCH 0.148889
AIRLOOP F4 S1 MAIN BRANCH 0.150860
AIRLOOP F4 S2 MAIN BRANCH 0.151447
AIRLOOP M SW MAIN BRANCH 0.256974
AIRLOOP M NW MAIN BRANCH 0.253949
AIRLOOP M SE MAIN BRANCH 0.218783
AIRLOOP M NE MAIN BRANCH 0.205916
AIRLOOP M N1 MAIN BRANCH 0.153097
AIRLOOP M N2 MAIN BRANCH 0.152212
AIRLOOP M S1 MAIN BRANCH 0.154239
AIRLOOP M S2 MAIN BRANCH 0.154806
AIRLOOP F6 SW MAIN BRANCH 0.253469
AIRLOOP F6 NW MAIN BRANCH 0.250263
AIRLOOP F6 SE MAIN BRANCH 0.215661
AIRLOOP F6 NE MAIN BRANCH 0.202641
AIRLOOP F6 N1 MAIN BRANCH 0.150060
AIRLOOP F6 N2 MAIN BRANCH 0.149188
AIRLOOP F6 S1 MAIN BRANCH 0.151365
AIRLOOP F6 S2 MAIN BRANCH 0.151929
AIRLOOP F7 SW MAIN BRANCH 0.252315
AIRLOOP F7 NW MAIN BRANCH 0.249049
AIRLOOP F7 SE MAIN BRANCH 0.214837
AIRLOOP F7 NE MAIN BRANCH 0.201757
AIRLOOP F7 N1 MAIN BRANCH 0.149318
AIRLOOP F7 N2 MAIN BRANCH 0.148456
AIRLOOP F7 S1 MAIN BRANCH 0.150691
AIRLOOP F7 S2 MAIN BRANCH 0.151255
AIRLOOP F8 SW MAIN BRANCH 0.252579
AIRLOOP F8 NW MAIN BRANCH 0.249254
AIRLOOP F8 SE MAIN BRANCH 0.215331
AIRLOOP F8 NE MAIN BRANCH 0.202184
AIRLOOP F8 N1 MAIN BRANCH 0.149926
AIRLOOP F8 N2 MAIN BRANCH 0.149075
AIRLOOP F8 S1 MAIN BRANCH 0.151311
AIRLOOP F8 S2 MAIN BRANCH 0.151875
AIRLOOP F9 SW MAIN BRANCH 0.261045
AIRLOOP F9 NW MAIN BRANCH 0.257502
AIRLOOP F9 SE MAIN BRANCH 0.219993
AIRLOOP F9 NE MAIN BRANCH 0.206266
AIRLOOP F9 N1 MAIN BRANCH 0.157498
AIRLOOP F9 N2 MAIN BRANCH 0.156647
AIRLOOP F9 S1 MAIN BRANCH 0.157012
AIRLOOP F9 S2 MAIN BRANCH 0.157643
AIRLOOP T SW MAIN BRANCH 0.312952
AIRLOOP T NW MAIN BRANCH 0.305479
AIRLOOP T SE MAIN BRANCH 0.272189
AIRLOOP T NE MAIN BRANCH 0.250279
AIRLOOP T N1 MAIN BRANCH 0.191249
AIRLOOP T N2 MAIN BRANCH 0.189338
AIRLOOP T S1 MAIN BRANCH 0.215507
AIRLOOP T S2 MAIN BRANCH 0.216108


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.201855
AIRLOOP G NW 0.201851
AIRLOOP OFFICE 0.271360
AIRLOOP G NE 0.155908
AIRLOOP G N1 0.113606
AIRLOOP G N2 0.112451
AIRLOOP G S1 0.111740
AIRLOOP G S2 0.116508
AIRLOOP F2 SW 0.252921
AIRLOOP F2 NW 0.249734
AIRLOOP F2 SE 0.229786
AIRLOOP F2 NE 0.199095
AIRLOOP F2 N1 0.145992
AIRLOOP F2 N2 0.145068
AIRLOOP F2 S1 0.146501
AIRLOOP F2 S2 0.148168
AIRLOOP F3 SW 0.253459
AIRLOOP F3 NW 0.250577
AIRLOOP F3 SE 0.216121
AIRLOOP F3 NE 0.201657
AIRLOOP F3 N1 0.148495
AIRLOOP F3 N2 0.147588
AIRLOOP F3 S1 0.149406
AIRLOOP F3 S2 0.150132
AIRLOOP F4 SW 0.254105
AIRLOOP F4 NW 0.251106
AIRLOOP F4 SE 0.215699
AIRLOOP F4 NE 0.202702
AIRLOOP F4 N1 0.149784
AIRLOOP F4 N2 0.148889
AIRLOOP F4 S1 0.150860
AIRLOOP F4 S2 0.151447
AIRLOOP M SW 0.256974
AIRLOOP M NW 0.253949
AIRLOOP M SE 0.218783
AIRLOOP M NE 0.205916
AIRLOOP M N1 0.153097
AIRLOOP M N2 0.152212
AIRLOOP M S1 0.154239
AIRLOOP M S2 0.154806
AIRLOOP F6 SW 0.253469
AIRLOOP F6 NW 0.250263
AIRLOOP F6 SE 0.215661
AIRLOOP F6 NE 0.202641
AIRLOOP F6 N1 0.150060
AIRLOOP F6 N2 0.149188
AIRLOOP F6 S1 0.151365
AIRLOOP F6 S2 0.151929
AIRLOOP F7 SW 0.252315
AIRLOOP F7 NW 0.249049
AIRLOOP F7 SE 0.214837
AIRLOOP F7 NE 0.201757
AIRLOOP F7 N1 0.149318
AIRLOOP F7 N2 0.148456
AIRLOOP F7 S1 0.150691
AIRLOOP F7 S2 0.151255
AIRLOOP F8 SW 0.252579
AIRLOOP F8 NW 0.249254
AIRLOOP F8 SE 0.215331
AIRLOOP F8 NE 0.202184
AIRLOOP F8 N1 0.149926
AIRLOOP F8 N2 0.149075
AIRLOOP F8 S1 0.151311
AIRLOOP F8 S2 0.151875
AIRLOOP F9 SW 0.261045
AIRLOOP F9 NW 0.257502
AIRLOOP F9 SE 0.219993
AIRLOOP F9 NE 0.206266
AIRLOOP F9 N1 0.157498
AIRLOOP F9 N2 0.156647
AIRLOOP F9 S1 0.157012
AIRLOOP F9 S2 0.157643
AIRLOOP T SW 0.312952
AIRLOOP T NW 0.305479
AIRLOOP T SE 0.272189
AIRLOOP T NE 0.250279
AIRLOOP T N1 0.191249
AIRLOOP T N2 0.189338
AIRLOOP T S1 0.215507
AIRLOOP T S2 0.216108


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.201855 0.025952
AIRLOOP G NW OA CONTROLLER 0.201851 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.271360 0.038103
AIRLOOP G NE OA CONTROLLER 0.155908 0.025952
AIRLOOP G N1 OA CONTROLLER 0.113606 0.025952
AIRLOOP G N2 OA CONTROLLER 0.112451 0.025952
AIRLOOP G S1 OA CONTROLLER 0.111740 0.025952
AIRLOOP G S2 OA CONTROLLER 0.116508 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.252921 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.249734 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.229786 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.199095 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.145992 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.145068 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.146501 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.148168 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.253459 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.250577 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.216121 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.201657 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.148495 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.147588 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.149406 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.150132 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.254105 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.251106 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.215699 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.202702 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.149784 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.148889 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.150860 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.151447 0.025952
AIRLOOP M SW OA CONTROLLER 0.256974 0.025952
AIRLOOP M NW OA CONTROLLER 0.253949 0.025952
AIRLOOP M SE OA CONTROLLER 0.218783 0.025952
AIRLOOP M NE OA CONTROLLER 0.205916 0.025952
AIRLOOP M N1 OA CONTROLLER 0.153097 0.025952
AIRLOOP M N2 OA CONTROLLER 0.152212 0.025952
AIRLOOP M S1 OA CONTROLLER 0.154239 0.025952
AIRLOOP M S2 OA CONTROLLER 0.154806 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.253469 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.250263 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.215661 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.202641 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.150060 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.149188 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.151365 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.151929 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.252315 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.249049 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.214837 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.201757 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.149318 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.148456 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.150691 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.151255 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.252579 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.249254 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.215331 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.202184 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.149926 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.149075 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.151311 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.151875 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.261045 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.257502 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.219993 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.206266 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.157498 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.156647 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.157012 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.157643 0.025952
AIRLOOP T SW OA CONTROLLER 0.312952 0.025952
AIRLOOP T NW OA CONTROLLER 0.305479 0.025952
AIRLOOP T SE OA CONTROLLER 0.272189 0.025952
AIRLOOP T NE OA CONTROLLER 0.250279 0.025952
AIRLOOP T N1 OA CONTROLLER 0.191249 0.025952
AIRLOOP T N2 OA CONTROLLER 0.189338 0.025952
AIRLOOP T S1 OA CONTROLLER 0.215507 0.025952
AIRLOOP T S2 OA CONTROLLER 0.216108 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.201855 3605.76 2350.37 0.000079
HEAT PUMP COOLING MODE AIRLOOP G NW 0.201851 3599.80 2346.36 0.000079
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.271360 4858.16 3168.21 0.000106
HEAT PUMP COOLING MODE AIRLOOP G NE 0.155908 2938.60 1865.94 0.000064
HEAT PUMP COOLING MODE AIRLOOP G N1 0.113606 2300.56 1414.07 0.000050
HEAT PUMP COOLING MODE AIRLOOP G N2 0.112451 2283.83 1402.07 0.000050
HEAT PUMP COOLING MODE AIRLOOP G S1 0.111740 2335.15 1424.30 0.000051
HEAT PUMP COOLING MODE AIRLOOP G S2 0.116508 2402.88 1473.80 0.000052
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.252921 4363.58 2889.27 0.000095
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.249734 4317.02 2854.56 0.000094
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.229786 4044.69 2654.41 0.000088
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.199095 3597.96 2329.08 0.000079
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.145992 2788.52 1757.14 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.145068 2775.30 1747.57 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.146501 2854.02 1793.09 0.000062
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.148168 2877.47 1810.35 0.000063
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.253459 4405.16 2905.73 0.000096
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.250577 4359.11 2871.91 0.000095
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.216121 3883.26 2521.90 0.000085
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.201657 3662.34 2363.90 0.000080
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.148495 2840.40 1788.06 0.000062
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.147588 2827.41 1778.66 0.000062
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.149406 2911.20 1828.12 0.000064
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.150132 2921.35 1835.61 0.000064
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.254105 4436.76 2918.86 0.000097
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.251106 4389.17 2883.87 0.000096
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.215699 3899.03 2523.89 0.000085
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.202702 3698.32 2381.00 0.000081
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.149784 2870.99 1805.18 0.000063
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.148889 2858.14 1795.89 0.000062
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.150860 2943.91 1846.90 0.000064
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.151447 2952.11 1852.95 0.000064
HEAT PUMP COOLING MODE AIRLOOP M SW 0.256974 4495.24 2953.75 0.000098
HEAT PUMP COOLING MODE AIRLOOP M NW 0.253949 4447.34 2918.52 0.000097
HEAT PUMP COOLING MODE AIRLOOP M SE 0.218783 3959.95 2560.93 0.000087
HEAT PUMP COOLING MODE AIRLOOP M NE 0.205916 3760.89 2419.35 0.000082
HEAT PUMP COOLING MODE AIRLOOP M N1 0.153097 2928.16 1842.54 0.000064
HEAT PUMP COOLING MODE AIRLOOP M N2 0.152212 2915.44 1833.35 0.000064
HEAT PUMP COOLING MODE AIRLOOP M S1 0.154239 3001.73 1884.98 0.000066
HEAT PUMP COOLING MODE AIRLOOP M S2 0.154806 3009.66 1890.82 0.000066
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.253469 4461.87 2922.08 0.000097
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.250263 4411.51 2885.03 0.000096
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.215661 3931.03 2533.09 0.000086
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.202641 3729.47 2389.91 0.000081
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.150060 2893.37 1813.77 0.000063
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.149188 2880.80 1804.71 0.000063
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.151365 2969.37 1857.76 0.000065
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.151929 2977.27 1863.57 0.000065
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.252315 4459.38 2914.12 0.000097
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.249049 4408.23 2876.48 0.000096
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.214837 3932.51 2528.46 0.000086
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.201757 3729.83 2384.63 0.000081
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.149318 2890.19 1808.41 0.000063
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.148456 2877.73 1799.45 0.000063
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.150691 2967.16 1853.04 0.000065
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.151255 2975.05 1858.85 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.252579 4475.34 2920.40 0.000098
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.249254 4423.39 2882.17 0.000097
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.215331 3951.15 2537.04 0.000086
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.202184 3747.34 2392.50 0.000082
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.149926 2905.53 1816.79 0.000063
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.149075 2893.21 1807.93 0.000063
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.151311 2982.58 1861.51 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.151875 2990.50 1867.33 0.000065
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.261045 4601.73 3008.87 0.000101
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.257502 4550.57 2970.67 0.000099
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.219993 4027.92 2588.50 0.000088
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.206266 3815.87 2437.94 0.000083
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.157498 3020.15 1897.14 0.000066
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.156647 3007.87 1888.29 0.000066
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.157012 3070.24 1922.68 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.157643 3079.10 1929.19 0.000067
HEAT PUMP COOLING MODE AIRLOOP T SW 0.312952 5350.32 3555.97 0.000117
HEAT PUMP COOLING MODE AIRLOOP T NW 0.305479 5237.34 3472.87 0.000114
HEAT PUMP COOLING MODE AIRLOOP T SE 0.272189 4809.35 3148.97 0.000105
HEAT PUMP COOLING MODE AIRLOOP T NE 0.250279 4453.07 2898.83 0.000097
HEAT PUMP COOLING MODE AIRLOOP T N1 0.191249 3514.42 2255.53 0.000077
HEAT PUMP COOLING MODE AIRLOOP T N2 0.189338 3487.28 2235.72 0.000076
HEAT PUMP COOLING MODE AIRLOOP T S1 0.215507 3901.54 2530.19 0.000085
HEAT PUMP COOLING MODE AIRLOOP T S2 0.216108 3909.80 2536.35 0.000085


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.201855 0.201855 0.201855 0.201855 3605.76 3605.76 2787.85 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.201851 0.201851 0.201851 0.201851 3599.80 3599.80 2791.26 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.271360 0.271360 0.271360 0.271360 4858.16 4858.16 3597.31 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.155908 0.155908 0.155908 0.155908 2938.60 2938.60 2791.46 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.113606 0.113606 0.113606 0.113606 2300.56 2300.56 2070.73 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.112451 0.112451 0.112451 0.112451 2283.83 2283.83 2070.72 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.111740 0.111740 0.111740 0.111740 2335.15 2335.15 2063.63 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.116508 0.116508 0.116508 0.116508 2402.88 2402.88 2072.12 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.252921 0.252921 0.252921 0.252921 4363.58 4363.58 2815.15 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.249734 0.249734 0.249734 0.249734 4317.02 4317.02 2820.60 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.229786 0.229786 0.229786 0.229786 4044.69 4044.69 2837.02 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.199095 0.199095 0.199095 0.199095 3597.96 3597.96 2817.24 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.145992 0.145992 0.145992 0.145992 2788.52 2788.52 1920.95 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.145068 0.145068 0.145068 0.145068 2775.30 2775.30 1920.87 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.146501 0.146501 0.146501 0.146501 2854.02 2854.02 1918.08 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.148168 0.148168 0.148168 0.148168 2877.47 2877.47 1919.67 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.253459 0.253459 0.253459 0.253459 4405.16 4405.16 2852.24 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.250577 0.250577 0.250577 0.250577 4359.11 4359.11 2862.02 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.216121 0.216121 0.216121 0.216121 3883.26 3883.26 2849.45 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.201657 0.201657 0.201657 0.201657 3662.34 3662.34 2856.42 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.148495 0.148495 0.148495 0.148495 2840.40 2840.40 1914.37 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.147588 0.147588 0.147588 0.147588 2827.41 2827.41 1914.23 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.149406 0.149406 0.149406 0.149406 2911.20 2911.20 1905.10 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.150132 0.150132 0.150132 0.150132 2921.35 2921.35 1905.22 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.254105 0.254105 0.254105 0.254105 4436.76 4436.76 2921.03 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.251106 0.251106 0.251106 0.251106 4389.17 4389.17 2933.73 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.215699 0.215699 0.215699 0.215699 3899.03 3899.03 2914.16 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.202702 0.202702 0.202702 0.202702 3698.32 3698.32 2926.56 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.149784 0.149784 0.149784 0.149784 2870.99 2870.99 1948.27 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.148889 0.148889 0.148889 0.148889 2858.14 2858.14 1948.09 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.150860 0.150860 0.150860 0.150860 2943.91 2943.91 1935.75 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.151447 0.151447 0.151447 0.151447 2952.11 2952.11 1935.60 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.256974 0.256974 0.256974 0.256974 4495.24 4495.24 2961.32 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.253949 0.253949 0.253949 0.253949 4447.34 4447.34 2974.90 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.218783 0.218783 0.218783 0.218783 3959.95 3959.95 2953.01 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.205916 0.205916 0.205916 0.205916 3760.89 3760.89 2966.57 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.153097 0.153097 0.153097 0.153097 2928.16 2928.16 1961.05 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.152212 0.152212 0.152212 0.152212 2915.44 2915.44 1960.84 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.154239 0.154239 0.154239 0.154239 3001.73 3001.73 1947.61 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.154806 0.154806 0.154806 0.154806 3009.66 3009.66 1947.40 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.253469 0.253469 0.253469 0.253469 4461.87 4461.87 3063.65 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.250263 0.250263 0.250263 0.250263 4411.51 4411.51 3079.68 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.215661 0.215661 0.215661 0.215661 3931.03 3931.03 3054.34 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.202641 0.202641 0.202641 0.202641 3729.47 3729.47 3070.38 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.150060 0.150060 0.150060 0.150060 2893.37 2893.37 2037.46 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.149188 0.149188 0.149188 0.149188 2880.80 2880.80 2037.22 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.151365 0.151365 0.151365 0.151365 2969.37 2969.37 2021.47 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.151929 0.151929 0.151929 0.151929 2977.27 2977.27 2021.23 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.252315 0.252315 0.252315 0.252315 4459.38 4459.38 3135.18 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.249049 0.249049 0.249049 0.249049 4408.23 4408.23 3152.21 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.214837 0.214837 0.214837 0.214837 3932.51 3932.51 3125.08 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.201757 0.201757 0.201757 0.201757 3729.83 3729.83 3142.13 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.149318 0.149318 0.149318 0.149318 2890.19 2890.19 2087.23 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.148456 0.148456 0.148456 0.148456 2877.73 2877.73 2086.98 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.150691 0.150691 0.150691 0.150691 2967.16 2967.16 2070.23 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.151255 0.151255 0.151255 0.151255 2975.05 2975.05 2069.97 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.252579 0.252579 0.252579 0.252579 4475.34 4475.34 3207.25 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.249254 0.249254 0.249254 0.249254 4423.39 4423.39 3224.86 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.215331 0.215331 0.215331 0.215331 3951.15 3951.15 3196.49 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.202184 0.202184 0.202184 0.202184 3747.34 3747.34 3214.11 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.149926 0.149926 0.149926 0.149926 2905.53 2905.53 2139.72 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.149075 0.149075 0.149075 0.149075 2893.21 2893.21 2139.44 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.151311 0.151311 0.151311 0.151311 2982.58 2982.58 2122.12 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.151875 0.151875 0.151875 0.151875 2990.50 2990.50 2121.85 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.261045 0.261045 0.261045 0.261045 4601.73 4601.73 3387.87 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.257502 0.257502 0.257502 0.257502 4550.57 4550.57 3403.72 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.219993 0.219993 0.219993 0.219993 4027.92 4027.92 3376.43 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.206266 0.206266 0.206266 0.206266 3815.87 3815.87 3392.29 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.157498 0.157498 0.157498 0.157498 3020.15 3020.15 2292.25 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.156647 0.156647 0.156647 0.156647 3007.87 3007.87 2291.96 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.157012 0.157012 0.157012 0.157012 3070.24 3070.24 2275.98 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.157643 0.157643 0.157643 0.157643 3079.10 3079.10 2275.69 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.312952 0.312952 0.312952 0.312952 5350.32 5350.32 3939.41 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.305479 0.305479 0.305479 0.305479 5237.34 5237.34 3960.89 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.272189 0.272189 0.272189 0.272189 4809.35 4809.35 3928.44 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.250279 0.250279 0.250279 0.250279 4453.07 4453.07 3949.93 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.191249 0.191249 0.191249 0.191249 3514.42 3514.42 2888.57 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.189338 0.189338 0.189338 0.189338 3487.28 3487.28 2888.27 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.215507 0.215507 0.215507 0.215507 3901.54 3901.54 2863.82 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.216108 0.216108 0.216108 0.216108 3909.80 3909.80 2863.52 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.201855
AIRLOOP G NW SUPPLY FAN 0.201851
AIRLOOP OFFICE SUPPLY FAN 0.271360
AIRLOOP G NE SUPPLY FAN 0.155908
AIRLOOP G N1 SUPPLY FAN 0.113606
AIRLOOP G N2 SUPPLY FAN 0.112451
AIRLOOP G S1 SUPPLY FAN 0.111740
AIRLOOP G S2 SUPPLY FAN 0.116508
AIRLOOP F2 SW SUPPLY FAN 0.252921
AIRLOOP F2 NW SUPPLY FAN 0.249734
AIRLOOP F2 SE SUPPLY FAN 0.229786
AIRLOOP F2 NE SUPPLY FAN 0.199095
AIRLOOP F2 N1 SUPPLY FAN 0.145992
AIRLOOP F2 N2 SUPPLY FAN 0.145068
AIRLOOP F2 S1 SUPPLY FAN 0.146501
AIRLOOP F2 S2 SUPPLY FAN 0.148168
AIRLOOP F3 SW SUPPLY FAN 0.253459
AIRLOOP F3 NW SUPPLY FAN 0.250577
AIRLOOP F3 SE SUPPLY FAN 0.216121
AIRLOOP F3 NE SUPPLY FAN 0.201657
AIRLOOP F3 N1 SUPPLY FAN 0.148495
AIRLOOP F3 N2 SUPPLY FAN 0.147588
AIRLOOP F3 S1 SUPPLY FAN 0.149406
AIRLOOP F3 S2 SUPPLY FAN 0.150132
AIRLOOP F4 SW SUPPLY FAN 0.254105
AIRLOOP F4 NW SUPPLY FAN 0.251106
AIRLOOP F4 SE SUPPLY FAN 0.215699
AIRLOOP F4 NE SUPPLY FAN 0.202702
AIRLOOP F4 N1 SUPPLY FAN 0.149784
AIRLOOP F4 N2 SUPPLY FAN 0.148889
AIRLOOP F4 S1 SUPPLY FAN 0.150860
AIRLOOP F4 S2 SUPPLY FAN 0.151447
AIRLOOP M SW SUPPLY FAN 0.256974
AIRLOOP M NW SUPPLY FAN 0.253949
AIRLOOP M SE SUPPLY FAN 0.218783
AIRLOOP M NE SUPPLY FAN 0.205916
AIRLOOP M N1 SUPPLY FAN 0.153097
AIRLOOP M N2 SUPPLY FAN 0.152212
AIRLOOP M S1 SUPPLY FAN 0.154239
AIRLOOP M S2 SUPPLY FAN 0.154806
AIRLOOP F6 SW SUPPLY FAN 0.253469
AIRLOOP F6 NW SUPPLY FAN 0.250263
AIRLOOP F6 SE SUPPLY FAN 0.215661
AIRLOOP F6 NE SUPPLY FAN 0.202641
AIRLOOP F6 N1 SUPPLY FAN 0.150060
AIRLOOP F6 N2 SUPPLY FAN 0.149188
AIRLOOP F6 S1 SUPPLY FAN 0.151365
AIRLOOP F6 S2 SUPPLY FAN 0.151929
AIRLOOP F7 SW SUPPLY FAN 0.252315
AIRLOOP F7 NW SUPPLY FAN 0.249049
AIRLOOP F7 SE SUPPLY FAN 0.214837
AIRLOOP F7 NE SUPPLY FAN 0.201757
AIRLOOP F7 N1 SUPPLY FAN 0.149318
AIRLOOP F7 N2 SUPPLY FAN 0.148456
AIRLOOP F7 S1 SUPPLY FAN 0.150691
AIRLOOP F7 S2 SUPPLY FAN 0.151255
AIRLOOP F8 SW SUPPLY FAN 0.252579
AIRLOOP F8 NW SUPPLY FAN 0.249254
AIRLOOP F8 SE SUPPLY FAN 0.215331
AIRLOOP F8 NE SUPPLY FAN 0.202184
AIRLOOP F8 N1 SUPPLY FAN 0.149926
AIRLOOP F8 N2 SUPPLY FAN 0.149075
AIRLOOP F8 S1 SUPPLY FAN 0.151311
AIRLOOP F8 S2 SUPPLY FAN 0.151875
AIRLOOP F9 SW SUPPLY FAN 0.261045
AIRLOOP F9 NW SUPPLY FAN 0.257502
AIRLOOP F9 SE SUPPLY FAN 0.219993
AIRLOOP F9 NE SUPPLY FAN 0.206266
AIRLOOP F9 N1 SUPPLY FAN 0.157498
AIRLOOP F9 N2 SUPPLY FAN 0.156647
AIRLOOP F9 S1 SUPPLY FAN 0.157012
AIRLOOP F9 S2 SUPPLY FAN 0.157643
AIRLOOP T SW SUPPLY FAN 0.312952
AIRLOOP T NW SUPPLY FAN 0.305479
AIRLOOP T SE SUPPLY FAN 0.272189
AIRLOOP T NE SUPPLY FAN 0.250279
AIRLOOP T N1 SUPPLY FAN 0.191249
AIRLOOP T N2 SUPPLY FAN 0.189338
AIRLOOP T S1 SUPPLY FAN 0.215507
AIRLOOP T S2 SUPPLY FAN 0.216108


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.201855 3605.76 0.000079
HEAT PUMP HEATING MODE AIRLOOP G NW 0.201851 3599.80 0.000079
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.271360 4858.16 0.000106
HEAT PUMP HEATING MODE AIRLOOP G NE 0.155908 2938.60 0.000064
HEAT PUMP HEATING MODE AIRLOOP G N1 0.113606 2300.56 0.000050
HEAT PUMP HEATING MODE AIRLOOP G N2 0.112451 2283.83 0.000050
HEAT PUMP HEATING MODE AIRLOOP G S1 0.111740 2335.15 0.000051
HEAT PUMP HEATING MODE AIRLOOP G S2 0.116508 2402.88 0.000052
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.252921 4363.58 0.000095
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.249734 4317.02 0.000094
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.229786 4044.69 0.000088
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.199095 3597.96 0.000079
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.145992 2788.52 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.145068 2775.30 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.146501 2854.02 0.000062
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.148168 2877.47 0.000063
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.253459 4405.16 0.000096
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.250577 4359.11 0.000095
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.216121 3883.26 0.000085
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.201657 3662.34 0.000080
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.148495 2840.40 0.000062
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.147588 2827.41 0.000062
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.149406 2911.20 0.000064
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.150132 2921.35 0.000064
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.254105 4436.76 0.000097
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.251106 4389.17 0.000096
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.215699 3899.03 0.000085
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.202702 3698.32 0.000081
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.149784 2870.99 0.000063
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.148889 2858.14 0.000062
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.150860 2943.91 0.000064
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.151447 2952.11 0.000064
HEAT PUMP HEATING MODE AIRLOOP M SW 0.256974 4495.24 0.000098
HEAT PUMP HEATING MODE AIRLOOP M NW 0.253949 4447.34 0.000097
HEAT PUMP HEATING MODE AIRLOOP M SE 0.218783 3959.95 0.000087
HEAT PUMP HEATING MODE AIRLOOP M NE 0.205916 3760.89 0.000082
HEAT PUMP HEATING MODE AIRLOOP M N1 0.153097 2928.16 0.000064
HEAT PUMP HEATING MODE AIRLOOP M N2 0.152212 2915.44 0.000064
HEAT PUMP HEATING MODE AIRLOOP M S1 0.154239 3001.73 0.000066
HEAT PUMP HEATING MODE AIRLOOP M S2 0.154806 3009.66 0.000066
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.253469 4461.87 0.000097
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.250263 4411.51 0.000096
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.215661 3931.03 0.000086
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.202641 3729.47 0.000081
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.150060 2893.37 0.000063
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.149188 2880.80 0.000063
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.151365 2969.37 0.000065
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.151929 2977.27 0.000065
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.252315 4459.38 0.000097
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.249049 4408.23 0.000096
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.214837 3932.51 0.000086
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.201757 3729.83 0.000081
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.149318 2890.19 0.000063
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.148456 2877.73 0.000063
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.150691 2967.16 0.000065
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.151255 2975.05 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.252579 4475.34 0.000098
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.249254 4423.39 0.000097
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.215331 3951.15 0.000086
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.202184 3747.34 0.000082
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.149926 2905.53 0.000063
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.149075 2893.21 0.000063
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.151311 2982.58 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.151875 2990.50 0.000065
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.261045 4601.73 0.000101
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.257502 4550.57 0.000099
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.219993 4027.92 0.000088
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.206266 3815.87 0.000083
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.157498 3020.15 0.000066
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.156647 3007.87 0.000066
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.157012 3070.24 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.157643 3079.10 0.000067
HEAT PUMP HEATING MODE AIRLOOP T SW 0.312952 5350.32 0.000117
HEAT PUMP HEATING MODE AIRLOOP T NW 0.305479 5237.34 0.000114
HEAT PUMP HEATING MODE AIRLOOP T SE 0.272189 4809.35 0.000105
HEAT PUMP HEATING MODE AIRLOOP T NE 0.250279 4453.07 0.000097
HEAT PUMP HEATING MODE AIRLOOP T N1 0.191249 3514.42 0.000077
HEAT PUMP HEATING MODE AIRLOOP T N2 0.189338 3487.28 0.000076
HEAT PUMP HEATING MODE AIRLOOP T S1 0.215507 3901.54 0.000085
HEAT PUMP HEATING MODE AIRLOOP T S2 0.216108 3909.80 0.000085


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 2787.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 2791.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 3597.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 2791.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 2070.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 2070.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 2063.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 2072.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 2815.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 2820.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 2837.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 2817.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1920.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1920.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1918.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1919.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 2852.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 2862.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 2849.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 2856.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1914.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1914.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1905.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1905.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 2921.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 2933.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 2914.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 2926.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1948.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1948.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1935.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1935.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 2961.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 2974.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 2953.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 2966.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1961.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1960.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1947.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1947.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 3063.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 3079.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 3054.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 3070.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 2037.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 2037.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 2021.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 2021.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 3135.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 3152.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 3125.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 3142.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 2087.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 2086.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 2070.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 2069.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 3207.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 3224.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 3196.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 3214.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 2139.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 2139.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 2122.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 2121.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 3387.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 3403.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 3376.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 3392.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 2292.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 2291.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 2275.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 2275.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 3939.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 3960.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 3928.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 3949.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 2888.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 2888.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 2863.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 2863.52


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.006226 7.00


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.006226


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.006226 3005.64 8.20 8989.24


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.006226 1587.99



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:09

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 3.96
February 22.29 7.94
March 22.98 13.76
April 23.51 17.21
May 23.97 20.84
June 24.37 24.80
July 24.38 26.06
August 24.40 26.55
September 24.27 22.53
October 23.47 16.03
November 22.88 11.94
December 22.30 7.70
     
Annual Sum or Average 23.41 16.65
Minimum of Months 22.00 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 3.96
February 21.97 7.94
March 22.55 13.76
April 23.39 17.21
May 23.98 20.84
June 24.37 24.80
July 24.38 26.06
August 24.40 26.55
September 24.26 22.53
October 23.11 16.03
November 22.28 11.94
December 21.83 7.70
     
Annual Sum or Average 23.19 16.65
Minimum of Months 21.73 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 3.96
February 22.47 7.94
March 23.28 13.76
April 23.74 17.21
May 24.18 20.84
June 24.39 24.80
July 24.40 26.06
August 24.40 26.55
September 24.37 22.53
October 23.60 16.03
November 23.05 11.94
December 22.43 7.70
     
Annual Sum or Average 23.55 16.65
Minimum of Months 22.18 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 3.96
February 21.95 7.94
March 22.46 13.76
April 23.34 17.21
May 23.96 20.84
June 24.38 24.80
July 24.38 26.06
August 24.40 26.55
September 24.25 22.53
October 23.05 16.03
November 22.18 11.94
December 21.78 7.70
     
Annual Sum or Average 23.16 16.65
Minimum of Months 21.72 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 3.96
February 21.92 7.94
March 22.37 13.76
April 23.23 17.21
May 23.87 20.84
June 24.37 24.80
July 24.38 26.06
August 24.40 26.55
September 24.25 22.53
October 23.01 16.03
November 22.17 11.94
December 21.79 7.70
     
Annual Sum or Average 23.13 16.65
Minimum of Months 21.72 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 3.96
February 21.92 7.94
March 22.37 13.76
April 23.23 17.21
May 23.87 20.84
June 24.37 24.80
July 24.38 26.06
August 24.40 26.55
September 24.24 22.53
October 23.00 16.03
November 22.17 11.94
December 21.79 7.70
     
Annual Sum or Average 23.13 16.65
Minimum of Months 21.72 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 3.96
February 22.30 7.94
March 22.92 13.76
April 23.42 17.21
May 23.90 20.84
June 24.36 24.80
July 24.38 26.06
August 24.44 26.55
September 24.28 22.53
October 23.51 16.03
November 22.92 11.94
December 22.36 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 22.02 3.96
Maximum of Months 24.44 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 3.96
February 22.33 7.94
March 22.96 13.76
April 23.45 17.21
May 23.92 20.84
June 24.36 24.80
July 24.37 26.06
August 24.42 26.55
September 24.28 22.53
October 23.53 16.03
November 22.95 11.94
December 22.38 7.70
     
Annual Sum or Average 23.42 16.65
Minimum of Months 22.04 3.96
Maximum of Months 24.42 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.03 3.96
February 19.27 7.94
March 21.31 13.76
April 22.73 17.21
May 23.99 20.84
June 25.86 24.80
July 26.24 26.06
August 26.38 26.55
September 25.13 22.53
October 22.35 16.03
November 20.77 11.94
December 19.19 7.70
     
Annual Sum or Average 22.62 16.65
Minimum of Months 18.03 3.96
Maximum of Months 26.38 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.23 3.96
February 22.67 7.94
March 23.70 13.76
April 24.04 17.21
May 24.27 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.31 22.53
October 23.97 16.03
November 23.58 11.94
December 22.69 7.70
     
Annual Sum or Average 23.72 16.65
Minimum of Months 22.23 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.21 7.94
March 23.13 13.76
April 23.91 17.21
May 24.26 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.62 16.03
November 22.72 11.94
December 21.98 7.70
     
Annual Sum or Average 23.43 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.25 3.96
February 22.71 7.94
March 23.74 13.76
April 24.09 17.21
May 24.30 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.32 22.53
October 23.99 16.03
November 23.62 11.94
December 22.74 7.70
     
Annual Sum or Average 23.75 16.65
Minimum of Months 22.25 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 3.96
February 22.18 7.94
March 23.02 13.76
April 23.88 17.21
May 24.26 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.54 16.03
November 22.59 11.94
December 21.90 7.70
     
Annual Sum or Average 23.39 16.65
Minimum of Months 21.76 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.21 7.94
March 23.01 13.76
April 23.84 17.21
May 24.23 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.29 22.53
October 23.61 16.03
November 22.69 11.94
December 21.98 7.70
     
Annual Sum or Average 23.41 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.21 7.94
March 23.00 13.76
April 23.83 17.21
May 24.23 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.29 22.53
October 23.61 16.03
November 22.67 11.94
December 21.97 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.37 3.96
February 22.77 7.94
March 23.73 13.76
April 24.02 17.21
May 24.25 20.84
June 24.39 24.80
July 24.39 26.06
August 24.43 26.55
September 24.32 22.53
October 24.05 16.03
November 23.74 11.94
December 22.92 7.70
     
Annual Sum or Average 23.78 16.65
Minimum of Months 22.37 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 3.96
February 22.79 7.94
March 23.74 13.76
April 24.02 17.21
May 24.25 20.84
June 24.39 24.80
July 24.39 26.06
August 24.42 26.55
September 24.32 22.53
October 24.05 16.03
November 23.75 11.94
December 22.93 7.70
     
Annual Sum or Average 23.79 16.65
Minimum of Months 22.38 3.96
Maximum of Months 24.42 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.24 3.96
February 22.93 7.94
March 24.41 13.76
April 25.25 17.21
May 25.87 20.84
June 26.47 24.80
July 26.59 26.06
August 26.65 26.55
September 26.18 22.53
October 24.99 16.03
November 24.02 11.94
December 22.89 7.70
     
Annual Sum or Average 24.88 16.65
Minimum of Months 22.24 3.96
Maximum of Months 26.65 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.25 3.96
February 22.72 7.94
March 23.80 13.76
April 24.10 17.21
May 24.29 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.31 22.53
October 24.02 16.03
November 23.69 11.94
December 22.76 7.70
     
Annual Sum or Average 23.76 16.65
Minimum of Months 22.25 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 3.96
February 22.27 7.94
March 23.26 13.76
April 23.98 17.21
May 24.28 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.71 16.03
November 22.83 11.94
December 22.01 7.70
     
Annual Sum or Average 23.47 16.65
Minimum of Months 21.79 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 3.96
February 22.69 7.94
March 23.77 13.76
April 24.11 17.21
May 24.30 20.84
June 24.39 24.80
July 24.39 26.06
August 24.41 26.55
September 24.32 22.53
October 24.00 16.03
November 23.65 11.94
December 22.73 7.70
     
Annual Sum or Average 23.75 16.65
Minimum of Months 22.22 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.24 7.94
March 23.16 13.76
April 23.96 17.21
May 24.29 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.64 16.03
November 22.71 11.94
December 21.94 7.70
     
Annual Sum or Average 23.44 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 3.96
February 22.30 7.94
March 23.21 13.76
April 23.96 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.29 22.53
October 23.76 16.03
November 22.88 11.94
December 22.05 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 21.81 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 3.96
February 22.30 7.94
March 23.20 13.76
April 23.95 17.21
May 24.27 20.84
June 24.39 24.80
July 24.39 26.06
August 24.41 26.55
September 24.29 22.53
October 23.75 16.03
November 22.86 11.94
December 22.05 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 21.80 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 3.96
February 22.87 7.94
March 23.89 13.76
April 24.11 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.32 22.53
October 24.13 16.03
November 23.89 11.94
December 23.06 7.70
     
Annual Sum or Average 23.86 16.65
Minimum of Months 22.46 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 3.96
February 22.87 7.94
March 23.89 13.76
April 24.11 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.32 22.53
October 24.13 16.03
November 23.89 11.94
December 23.07 7.70
     
Annual Sum or Average 23.86 16.65
Minimum of Months 22.46 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.64 3.96
February 23.34 7.94
March 24.86 13.76
April 25.65 17.21
May 26.17 20.84
June 26.58 24.80
July 26.66 26.06
August 26.71 26.55
September 26.29 22.53
October 25.36 16.03
November 24.46 11.94
December 23.29 7.70
     
Annual Sum or Average 25.18 16.65
Minimum of Months 22.64 3.96
Maximum of Months 26.71 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.24 3.96
February 22.72 7.94
March 23.80 13.76
April 24.13 17.21
May 24.29 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.32 22.53
October 24.02 16.03
November 23.69 11.94
December 22.74 7.70
     
Annual Sum or Average 23.76 16.65
Minimum of Months 22.24 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 3.96
February 22.29 7.94
March 23.28 13.76
April 24.02 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.30 22.53
October 23.71 16.03
November 22.85 11.94
December 22.01 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 21.79 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 3.96
February 22.68 7.94
March 23.76 13.76
April 24.14 17.21
May 24.30 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.32 22.53
October 23.98 16.03
November 23.64 11.94
December 22.71 7.70
     
Annual Sum or Average 23.75 16.65
Minimum of Months 22.19 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.25 7.94
March 23.18 13.76
April 24.01 17.21
May 24.29 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.64 16.03
November 22.72 11.94
December 21.94 7.70
     
Annual Sum or Average 23.45 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 3.96
February 22.34 7.94
March 23.26 13.76
April 24.02 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.30 22.53
October 23.78 16.03
November 22.93 11.94
December 22.07 7.70
     
Annual Sum or Average 23.50 16.65
Minimum of Months 21.81 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 3.96
February 22.34 7.94
March 23.25 13.76
April 24.02 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.30 22.53
October 23.78 16.03
November 22.92 11.94
December 22.06 7.70
     
Annual Sum or Average 23.50 16.65
Minimum of Months 21.81 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.47 3.96
February 22.89 7.94
March 23.92 13.76
April 24.16 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.33 22.53
October 24.14 16.03
November 23.91 11.94
December 23.08 7.70
     
Annual Sum or Average 23.87 16.65
Minimum of Months 22.47 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 3.96
February 22.89 7.94
March 23.92 13.76
April 24.16 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.33 22.53
October 24.14 16.03
November 23.90 11.94
December 23.08 7.70
     
Annual Sum or Average 23.87 16.65
Minimum of Months 22.46 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.77 3.96
February 23.48 7.94
March 25.02 13.76
April 25.82 17.21
May 26.30 20.84
June 26.67 24.80
July 26.74 26.06
August 26.80 26.55
September 26.39 22.53
October 25.50 16.03
November 24.62 11.94
December 23.44 7.70
     
Annual Sum or Average 25.30 16.65
Minimum of Months 22.77 3.96
Maximum of Months 26.80 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.22 3.96
February 22.71 7.94
March 23.78 13.76
April 24.13 17.21
May 24.29 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.31 22.53
October 24.01 16.03
November 23.68 11.94
December 22.73 7.70
     
Annual Sum or Average 23.76 16.65
Minimum of Months 22.22 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 3.96
February 22.28 7.94
March 23.27 13.76
April 24.02 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.30 22.53
October 23.71 16.03
November 22.85 11.94
December 22.02 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 21.80 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 3.96
February 22.67 7.94
March 23.73 13.76
April 24.13 17.21
May 24.30 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.32 22.53
October 23.97 16.03
November 23.63 11.94
December 22.69 7.70
     
Annual Sum or Average 23.74 16.65
Minimum of Months 22.18 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.25 7.94
March 23.17 13.76
April 24.00 17.21
May 24.28 20.84
June 24.39 24.80
July 24.39 26.06
August 24.40 26.55
September 24.30 22.53
October 23.64 16.03
November 22.73 11.94
December 21.94 7.70
     
Annual Sum or Average 23.45 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 3.96
February 22.36 7.94
March 23.28 13.76
April 24.03 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.30 22.53
October 23.79 16.03
November 22.95 11.94
December 22.09 7.70
     
Annual Sum or Average 23.51 16.65
Minimum of Months 21.82 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 3.96
February 22.36 7.94
March 23.27 13.76
April 24.03 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.30 22.53
October 23.79 16.03
November 22.94 11.94
December 22.08 7.70
     
Annual Sum or Average 23.51 16.65
Minimum of Months 21.82 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 3.96
February 22.89 7.94
March 23.91 13.76
April 24.16 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.33 22.53
October 24.14 16.03
November 23.91 11.94
December 23.08 7.70
     
Annual Sum or Average 23.87 16.65
Minimum of Months 22.46 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 3.96
February 22.89 7.94
March 23.91 13.76
April 24.16 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.43 26.55
September 24.33 22.53
October 24.14 16.03
November 23.91 11.94
December 23.08 7.70
     
Annual Sum or Average 23.87 16.65
Minimum of Months 22.46 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.41 3.96
February 24.11 7.94
March 25.63 13.76
April 26.43 17.21
May 26.90 20.84
June 27.26 24.80
July 27.33 26.06
August 27.39 26.55
September 26.99 22.53
October 26.10 16.03
November 25.24 11.94
December 24.06 7.70
     
Annual Sum or Average 25.91 16.65
Minimum of Months 23.41 3.96
Maximum of Months 27.39 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.16 3.96
February 22.63 7.94
March 23.69 13.76
April 24.08 17.21
May 24.27 20.84
June 24.38 24.80
July 24.38 26.06
August 24.40 26.55
September 24.30 22.53
October 23.94 16.03
November 23.59 11.94
December 22.65 7.70
     
Annual Sum or Average 23.71 16.65
Minimum of Months 22.16 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.22 7.94
March 23.15 13.76
April 23.96 17.21
May 24.26 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.29 22.53
October 23.62 16.03
November 22.74 11.94
December 21.97 7.70
     
Annual Sum or Average 23.43 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.12 3.96
February 22.60 7.94
March 23.63 13.76
April 24.08 17.21
May 24.28 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.31 22.53
October 23.89 16.03
November 23.53 11.94
December 22.60 7.70
     
Annual Sum or Average 23.69 16.65
Minimum of Months 22.12 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 3.96
February 22.19 7.94
March 23.05 13.76
April 23.94 17.21
May 24.26 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.29 22.53
October 23.55 16.03
November 22.62 11.94
December 21.90 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 21.76 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 3.96
February 22.29 7.94
March 23.15 13.76
April 23.97 17.21
May 24.25 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.29 22.53
October 23.70 16.03
November 22.83 11.94
December 22.02 7.70
     
Annual Sum or Average 23.46 16.65
Minimum of Months 21.80 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 3.96
February 22.29 7.94
March 23.14 13.76
April 23.97 17.21
May 24.25 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.29 22.53
October 23.70 16.03
November 22.81 11.94
December 22.02 7.70
     
Annual Sum or Average 23.46 16.65
Minimum of Months 21.80 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 3.96
February 22.81 7.94
March 23.82 13.76
April 24.12 17.21
May 24.26 20.84
June 24.38 24.80
July 24.38 26.06
August 24.43 26.55
September 24.32 22.53
October 24.08 16.03
November 23.83 11.94
December 22.98 7.70
     
Annual Sum or Average 23.82 16.65
Minimum of Months 22.38 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 3.96
February 22.81 7.94
March 23.82 13.76
April 24.12 17.21
May 24.26 20.84
June 24.38 24.80
July 24.38 26.06
August 24.43 26.55
September 24.32 22.53
October 24.07 16.03
November 23.83 11.94
December 22.98 7.70
     
Annual Sum or Average 23.82 16.65
Minimum of Months 22.38 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.70 3.96
February 23.39 7.94
March 24.91 13.76
April 25.76 17.21
May 26.27 20.84
June 26.65 24.80
July 26.72 26.06
August 26.79 26.55
September 26.37 22.53
October 25.41 16.03
November 24.53 11.94
December 23.35 7.70
     
Annual Sum or Average 25.25 16.65
Minimum of Months 22.70 3.96
Maximum of Months 26.79 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.12 3.96
February 22.58 7.94
March 23.61 13.76
April 24.04 17.21
May 24.26 20.84
June 24.38 24.80
July 24.38 26.06
August 24.40 26.55
September 24.30 22.53
October 23.88 16.03
November 23.51 11.94
December 22.58 7.70
     
Annual Sum or Average 23.67 16.65
Minimum of Months 22.12 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.18 7.94
March 23.05 13.76
April 23.92 17.21
May 24.25 20.84
June 24.39 24.80
July 24.37 26.06
August 24.40 26.55
September 24.28 22.53
October 23.55 16.03
November 22.66 11.94
December 21.94 7.70
     
Annual Sum or Average 23.40 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.08 3.96
February 22.54 7.94
March 23.55 13.76
April 24.04 17.21
May 24.27 20.84
June 24.39 24.80
July 24.38 26.06
August 24.41 26.55
September 24.30 22.53
October 23.84 16.03
November 23.45 11.94
December 22.54 7.70
     
Annual Sum or Average 23.65 16.65
Minimum of Months 22.08 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 22.15 7.94
March 22.96 13.76
April 23.89 17.21
May 24.25 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.28 22.53
October 23.49 16.03
November 22.55 11.94
December 21.88 7.70
     
Annual Sum or Average 23.37 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 3.96
February 22.24 7.94
March 23.06 13.76
April 23.92 17.21
May 24.23 20.84
June 24.38 24.80
July 24.37 26.06
August 24.41 26.55
September 24.28 22.53
October 23.63 16.03
November 22.73 11.94
December 21.98 7.70
     
Annual Sum or Average 23.42 16.65
Minimum of Months 21.79 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.24 7.94
March 23.06 13.76
April 23.92 17.21
May 24.23 20.84
June 24.39 24.80
July 24.37 26.06
August 24.41 26.55
September 24.28 22.53
October 23.63 16.03
November 22.71 11.94
December 21.98 7.70
     
Annual Sum or Average 23.42 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.32 3.96
February 22.75 7.94
March 23.74 13.76
April 24.08 17.21
May 24.25 20.84
June 24.38 24.80
July 24.37 26.06
August 24.43 26.55
September 24.31 22.53
October 24.03 16.03
November 23.77 11.94
December 22.90 7.70
     
Annual Sum or Average 23.78 16.65
Minimum of Months 22.32 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.32 3.96
February 22.75 7.94
March 23.74 13.76
April 24.08 17.21
May 24.25 20.84
June 24.38 24.80
July 24.37 26.06
August 24.43 26.55
September 24.31 22.53
October 24.02 16.03
November 23.77 11.94
December 22.90 7.70
     
Annual Sum or Average 23.78 16.65
Minimum of Months 22.32 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.53 3.96
February 23.22 7.94
March 24.72 13.76
April 25.62 17.21
May 26.17 20.84
June 26.57 24.80
July 26.64 26.06
August 26.71 26.55
September 26.28 22.53
October 25.26 16.03
November 24.34 11.94
December 23.17 7.70
     
Annual Sum or Average 25.11 16.65
Minimum of Months 22.53 3.96
Maximum of Months 26.71 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.08 3.96
February 22.53 7.94
March 23.53 13.76
April 24.00 17.21
May 24.25 20.84
June 24.38 24.80
July 24.37 26.06
August 24.40 26.55
September 24.29 22.53
October 23.83 16.03
November 23.44 11.94
December 22.53 7.70
     
Annual Sum or Average 23.64 16.65
Minimum of Months 22.08 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 3.96
February 22.14 7.94
March 22.97 13.76
April 23.88 17.21
May 24.24 20.84
June 24.38 24.80
July 24.37 26.06
August 24.40 26.55
September 24.27 22.53
October 23.49 16.03
November 22.59 11.94
December 21.91 7.70
     
Annual Sum or Average 23.37 16.65
Minimum of Months 21.76 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 3.96
February 22.50 7.94
March 23.47 13.76
April 24.00 17.21
May 24.26 20.84
June 24.39 24.80
July 24.37 26.06
August 24.41 26.55
September 24.30 22.53
October 23.79 16.03
November 23.37 11.94
December 22.49 7.70
     
Annual Sum or Average 23.62 16.65
Minimum of Months 22.04 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 22.11 7.94
March 22.88 13.76
April 23.85 17.21
May 24.24 20.84
June 24.39 24.80
July 24.38 26.06
August 24.40 26.55
September 24.27 22.53
October 23.44 16.03
November 22.48 11.94
December 21.86 7.70
     
Annual Sum or Average 23.34 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.20 7.94
March 22.99 13.76
April 23.88 17.21
May 24.22 20.84
June 24.38 24.80
July 24.37 26.06
August 24.41 26.55
September 24.27 22.53
October 23.57 16.03
November 22.64 11.94
December 21.95 7.70
     
Annual Sum or Average 23.39 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.20 7.94
March 22.98 13.76
April 23.87 17.21
May 24.22 20.84
June 24.38 24.80
July 24.37 26.06
August 24.41 26.55
September 24.27 22.53
October 23.56 16.03
November 22.63 11.94
December 21.95 7.70
     
Annual Sum or Average 23.39 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.27 3.96
February 22.70 7.94
March 23.67 13.76
April 24.04 17.21
May 24.24 20.84
June 24.38 24.80
July 24.37 26.06
August 24.43 26.55
September 24.30 22.53
October 23.97 16.03
November 23.70 11.94
December 22.83 7.70
     
Annual Sum or Average 23.75 16.65
Minimum of Months 22.27 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.27 3.96
February 22.70 7.94
March 23.66 13.76
April 24.04 17.21
May 24.24 20.84
June 24.38 24.80
July 24.37 26.06
August 24.43 26.55
September 24.30 22.53
October 23.97 16.03
November 23.70 11.94
December 22.83 7.70
     
Annual Sum or Average 23.75 16.65
Minimum of Months 22.27 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.44 3.96
February 23.12 7.94
March 24.61 13.76
April 25.55 17.21
May 26.14 20.84
June 26.57 24.80
July 26.64 26.06
August 26.71 26.55
September 26.26 22.53
October 25.17 16.03
November 24.22 11.94
December 23.07 7.70
     
Annual Sum or Average 25.05 16.65
Minimum of Months 22.44 3.96
Maximum of Months 26.71 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 3.96
February 22.47 7.94
March 23.43 13.76
April 23.95 17.21
May 24.24 20.84
June 24.38 24.80
July 24.37 26.06
August 24.40 26.55
September 24.28 22.53
October 23.76 16.03
November 23.33 11.94
December 22.46 7.70
     
Annual Sum or Average 23.60 16.65
Minimum of Months 22.04 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 22.12 7.94
March 22.89 13.76
April 23.83 17.21
May 24.22 20.84
June 24.38 24.80
July 24.37 26.06
August 24.40 26.55
September 24.26 22.53
October 23.41 16.03
November 22.54 11.94
December 21.89 7.70
     
Annual Sum or Average 23.34 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 3.96
February 22.44 7.94
March 23.37 13.76
April 23.95 17.21
May 24.25 20.84
June 24.39 24.80
July 24.37 26.06
August 24.41 26.55
September 24.29 22.53
October 23.72 16.03
November 23.26 11.94
December 22.41 7.70
     
Annual Sum or Average 23.58 16.65
Minimum of Months 22.00 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 3.96
February 22.08 7.94
March 22.79 13.76
April 23.80 17.21
May 24.22 20.84
June 24.39 24.80
July 24.37 26.06
August 24.40 26.55
September 24.26 22.53
October 23.36 16.03
November 22.42 11.94
December 21.84 7.70
     
Annual Sum or Average 23.31 16.65
Minimum of Months 21.74 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.17 7.94
March 22.90 13.76
April 23.82 17.21
May 24.21 20.84
June 24.38 24.80
July 24.37 26.06
August 24.41 26.55
September 24.26 22.53
October 23.48 16.03
November 22.56 11.94
December 21.92 7.70
     
Annual Sum or Average 23.36 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.16 7.94
March 22.89 13.76
April 23.82 17.21
May 24.21 20.84
June 24.38 24.80
July 24.37 26.06
August 24.41 26.55
September 24.26 22.53
October 23.47 16.03
November 22.55 11.94
December 21.91 7.70
     
Annual Sum or Average 23.36 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.41 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.20 3.96
February 22.63 7.94
March 23.56 13.76
April 23.99 17.21
May 24.23 20.84
June 24.38 24.80
July 24.37 26.06
August 24.43 26.55
September 24.29 22.53
October 23.89 16.03
November 23.58 11.94
December 22.72 7.70
     
Annual Sum or Average 23.69 16.65
Minimum of Months 22.20 3.96
Maximum of Months 24.43 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.20 3.96
February 22.63 7.94
March 23.56 13.76
April 23.99 17.21
May 24.23 20.84
June 24.38 24.80
July 24.37 26.06
August 24.42 26.55
September 24.29 22.53
October 23.89 16.03
November 23.58 11.94
December 22.72 7.70
     
Annual Sum or Average 23.69 16.65
Minimum of Months 22.20 3.96
Maximum of Months 24.42 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.29 3.96
February 22.98 7.94
March 24.48 13.76
April 25.50 17.21
May 26.16 20.84
June 26.64 24.80
July 26.72 26.06
August 26.80 26.55
September 26.29 22.53
October 25.06 16.03
November 24.06 11.94
December 22.90 7.70
     
Annual Sum or Average 25.00 16.65
Minimum of Months 22.29 3.96
Maximum of Months 26.80 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 3.96
February 22.41 7.94
March 23.14 13.76
April 23.76 17.21
May 24.12 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.23 22.53
October 23.50 16.03
November 23.06 11.94
December 22.38 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 22.04 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.96
February 22.10 7.94
March 22.76 13.76
April 23.65 17.21
May 24.11 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.21 22.53
October 23.17 16.03
November 22.49 11.94
December 21.93 7.70
     
Annual Sum or Average 23.28 16.65
Minimum of Months 21.78 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 3.96
February 22.37 7.94
March 23.10 13.76
April 23.76 17.21
May 24.14 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.23 22.53
October 23.47 16.03
November 23.01 11.94
December 22.35 7.70
     
Annual Sum or Average 23.47 16.65
Minimum of Months 22.01 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 3.96
February 22.06 7.94
March 22.68 13.76
April 23.62 17.21
May 24.11 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.21 22.53
October 23.15 16.03
November 22.38 11.94
December 21.86 7.70
     
Annual Sum or Average 23.25 16.65
Minimum of Months 21.75 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.12 7.94
March 22.71 13.76
April 23.65 17.21
May 24.10 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.21 22.53
October 23.20 16.03
November 22.45 11.94
December 21.91 7.70
     
Annual Sum or Average 23.27 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.96
February 22.11 7.94
March 22.70 13.76
April 23.64 17.21
May 24.10 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.21 22.53
October 23.19 16.03
November 22.44 11.94
December 21.90 7.70
     
Annual Sum or Average 23.27 16.65
Minimum of Months 21.77 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.15 3.96
February 22.53 7.94
March 23.25 13.76
April 23.81 17.21
May 24.13 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.24 22.53
October 23.64 16.03
November 23.22 11.94
December 22.54 7.70
     
Annual Sum or Average 23.56 16.65
Minimum of Months 22.15 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.15 3.96
February 22.53 7.94
March 23.25 13.76
April 23.81 17.21
May 24.13 20.84
June 24.36 24.80
July 24.36 26.06
August 24.40 26.55
September 24.24 22.53
October 23.64 16.03
November 23.21 11.94
December 22.54 7.70
     
Annual Sum or Average 23.56 16.65
Minimum of Months 22.15 3.96
Maximum of Months 24.40 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:09

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.26 3.96
February 23.08 7.94
March 24.70 13.76
April 25.89 17.21
May 26.77 20.84
June 27.41 24.80
July 27.56 26.06
August 27.63 26.55
September 26.86 22.53
October 25.30 16.03
November 24.17 11.94
December 22.92 7.70
     
Annual Sum or Average 25.39 16.65
Minimum of Months 22.26 3.96
Maximum of Months 27.63 26.55



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:09

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.232535E+12 145568.029 07-JAN-18:15 22204.399 56867.515 17344.921 35660.540 0.000 10720.100 1624.917 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.202735E+12 144064.273 11-FEB-18:00 22204.399 56867.515 17344.921 34156.532 0.000 10720.100 1624.917 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.211697E+12 164280.104 30-MAR-17:15 22204.399 56867.515 17344.921 0.000 62877.193 0.000 1624.917 2215.522 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.224515E+12 154586.846 11-APR-17:15 22204.399 56867.515 17344.921 0.000 53517.416 0.000 1624.917 1882.042 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.263014E+12 170257.627 21-MAY-17:15 22204.399 56867.515 17344.921 0.000 68562.778 0.000 1624.917 2507.461 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.302410E+12 172968.367 06-JUN-17:15 22204.399 56867.515 17344.921 0.000 71145.064 0.000 1624.917 2635.914 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.327158E+12 178332.056 26-JUL-19:00 25049.151 49704.829 17344.921 0.000 70064.654 10720.100 1624.917 2877.912 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.342228E+12 177527.002 19-AUG-19:00 25049.151 49704.829 17344.921 0.000 69321.677 10720.100 1624.917 2815.835 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.281198E+12 171360.493 07-SEP-17:15 22204.399 56867.515 17344.921 0.000 69400.207 0.000 1624.917 2772.897 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.230012E+12 169562.852 18-OCT-17:00 22204.399 56867.515 17344.921 0.000 57013.727 10720.100 1624.917 2641.384 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.204000E+12 137757.478 05-NOV-16:15 18221.747 56867.515 17344.921 0.000 40790.728 0.000 1624.917 1762.230 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.218947E+12 121949.691 25-DEC-18:00 22204.399 56867.515 17344.921 12041.950 0.000 10720.100 1624.917 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.304045E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.202735E+12 121949.691   18221.747 49704.829 17344.921 0.000 0.000 0.000 1624.917 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.342228E+12 178332.056   25049.151 56867.515 17344.921 35660.540 71145.064 10720.100 1624.917 2877.912 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:09

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.207105E+12 225999.328 07-JAN-10:15 0.000 0.000 0.000 225999.328 78369.977 78369.977 147629.351
February 0.156365E+12 276556.671 12-FEB-06:45 0.000 0.000 0.000 276556.671 79629.855 79629.855 196926.815
March 0.101091E+12 114531.939 18-MAR-06:00 0.000 0.000 0.000 114531.939 83624.369 83624.369 30907.570
April 0.889063E+11 84025.182 06-APR-07:45 0.000 0.000 0.000 84025.182 75240.114 75240.114 8785.068
May 0.844359E+11 80472.022 02-MAY-06:00 0.000 0.000 0.000 80472.022 80472.022 80472.022 0.000
June 0.754149E+11 78198.235 03-JUN-06:45 0.000 0.000 0.000 78198.235 78198.235 78198.235 0.000
July 0.739818E+11 76791.383 02-JUL-06:45 0.000 0.000 0.000 76791.383 76791.383 76791.383 0.000
August 0.736849E+11 76649.320 30-AUG-06:45 0.000 0.000 0.000 76649.320 76649.320 76649.320 0.000
September 0.746917E+11 77980.008 28-SEP-06:00 0.000 0.000 0.000 77980.008 77980.008 77980.008 0.000
October 0.837388E+11 104173.618 26-OCT-06:30 0.000 0.000 0.000 104173.618 79670.598 79670.598 24503.021
November 0.963587E+11 160794.046 22-NOV-07:15 0.000 0.000 0.000 160794.046 80895.622 80895.622 79898.424
December 0.144425E+12 180125.845 02-DEC-07:45 0.000 0.000 0.000 180125.845 82567.237 82567.237 97558.608
                     
Annual Sum or Average 0.126020E+13     0.000 0.000 0.000        
Minimum of Months 0.736849E+11 76649.320   0.000 0.000 0.000 76649.320 75240.114 75240.114 0.000
Maximum of Months 0.207105E+12 276556.671   0.000 0.000 0.000 276556.671 83624.369 83624.369 196926.815