Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2018-10-19 09:40:17


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4806.42 613.34 680.81
Net Site Energy 4806.42 613.34 680.81
Total Source Energy 13521.12 1725.41 1915.20
Net Source Energy 13521.12 1725.41 1915.20


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 1.78 0.00 0.00 0.00 0.00 0.00
Cooling 1315.56 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.54 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 807.36 0.00 0.00 0.00 0.00 0.00
Pumps 63.70 0.00 0.00 0.00 0.00 0.00
Heat Rejection 64.63 0.00 0.00 0.00 0.00 3857.91
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 816.51 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3989.90 816.51 0.00 0.00 0.00 8636.43
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 1.78 0.00 0.00 0.00 0.00 0.00
Cooling General 1315.56 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.54 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 807.36 0.00 0.00 0.00 0.00 0.00
Pumps General 63.70 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 64.63 0.00 0.00 0.00 0.00 3857.91
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 816.51 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.86 0.00 0.00 0.00 0.00 0.00
HVAC 319.13 115.66 0.00 0.00 0.00 1.22
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 565.15 115.66 0.00 0.00 0.00 1.22


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.65 0.00 0.00 0.00 0.00 0.00
HVAC 287.51 104.19 0.00 0.00 0.00 1.10
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 509.14 104.19 0.00 0.00 0.00 1.10


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3989.90 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3989.90 100.00
     
Total On-Site and Utility Electric Sources 3989.90 100.00
Total Electricity End Uses 3989.90 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8636.43 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8636.43 100.00
Total Water End Uses 8636.43 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 5.50
Time Setpoint Not Met During Occupied Cooling 456.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2354.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 01-JUL-17:15 10-JAN-07:00 - - - 07-JUN-17:15
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 97251.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting 22204.40 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 56867.52 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25601.20 0.00 0.00 0.00 0.00 0.00
Pumps 2063.51 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3835.78 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 79739.68 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 208969.32 79739.68 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 97251.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 18331.79 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 3872.61 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 56867.52 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 25601.20 0.00 0.00 0.00 0.00 0.00
Pumps General 2063.51 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 3835.78 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 79739.68 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 5.65 0.00 0.00 0.00 0.00
Cooling 4166.38 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.77 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2556.91 0.00 0.00 0.00 0.00
Pumps 201.73 0.00 0.00 0.00 0.00
Heat Rejection 204.68 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 885.10 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 12636.02 885.10 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.80 0.00 0.00 0.00 0.00
Cooling 590.15 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.61 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 362.17 0.00 0.00 0.00 0.00
Pumps 28.57 0.00 0.00 0.00 0.00
Heat Rejection 28.99 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 125.37 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1789.83 125.37 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.80 0.00 0.00 0.00 0.00
Cooling 590.15 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.61 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 362.17 0.00 0.00 0.00 0.00
Pumps 28.57 0.00 0.00 0.00 0.00
Heat Rejection 28.99 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 125.37 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1789.83 125.37 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 5.778 0.306 0.155     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 5.778 0.306 0.155              
North Total or Average           423.59 5.778 0.306 0.155              
Non-North Total or Average           726.80 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.76 83.76 168.54
Exterior Lighting Total 10720.10           168.54



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 365312.36 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 292249.89      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4719.02 3392.18 1326.84 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4766.05 3430.38 1335.67 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   5756.58 4116.18 1640.41 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4065.21 2903.98 1161.23 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3008.39 2096.68 911.70 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2996.57 2087.67 908.90 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2956.72 2040.86 915.86 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3014.41 2085.06 929.34 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5577.89 4043.95 1533.94 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5629.91 4085.75 1544.16 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5165.73 3722.46 1443.27 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4839.07 3490.98 1348.09 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3602.50 2545.53 1056.97 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3593.03 2538.31 1054.72 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3530.44 2477.96 1052.48 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3545.32 2489.35 1055.97 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5586.89 4048.51 1538.37 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5642.66 4093.18 1549.49 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4947.97 3567.53 1380.44 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4875.91 3516.84 1359.07 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3628.33 2563.97 1064.36 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3618.95 2556.83 1062.13 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3559.38 2498.84 1060.54 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3563.69 2502.11 1061.58 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5616.41 4069.31 1547.10 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5671.45 4113.41 1558.04 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5007.86 3598.04 1409.82 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4907.85 3539.52 1368.34 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3657.77 2585.47 1072.30 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3648.49 2578.40 1070.09 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3589.46 2520.89 1068.57 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3592.09 2522.88 1069.21 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5675.84 4113.23 1562.60 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5731.32 4157.66 1573.66 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5072.66 3646.12 1426.53 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4969.83 3585.41 1384.42 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3717.07 2629.91 1087.16 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3707.87 2622.90 1084.97 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3647.96 2564.83 1083.12 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3650.23 2566.55 1083.69 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5645.98 4089.24 1556.74 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5699.41 4132.12 1567.29 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5049.70 3627.44 1422.27 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4940.68 3561.99 1378.69 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3686.31 2605.79 1080.52 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3677.21 2598.86 1078.36 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3618.92 2541.98 1076.95 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3621.06 2543.58 1077.48 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5646.75 4088.76 1557.99 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5699.79 4131.34 1568.45 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5056.38 3631.50 1424.88 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4943.22 3562.89 1380.33 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3687.01 2605.74 1081.27 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3677.99 2598.86 1079.13 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3619.83 2542.08 1077.75 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3621.79 2543.59 1078.20 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5667.50 4103.63 1563.87 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5719.88 4145.70 1574.18 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5081.77 3649.95 1431.83 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4964.42 3578.12 1386.30 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3703.31 2618.61 1084.70 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3694.36 2611.79 1082.57 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3640.12 2557.07 1083.06 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3642.09 2558.58 1083.51 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5829.44 4226.26 1603.17 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5883.32 4269.44 1613.87 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5230.18 3762.33 1467.85 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5159.08 3716.10 1442.98 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3852.86 2732.07 1120.79 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3843.95 2725.29 1118.67 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3763.32 2653.47 1109.85 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3769.68 2655.57 1114.11 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   6779.94 4947.51 1832.43 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6792.44 4959.90 1832.54 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   6127.47 4446.00 1681.47 0.73 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   6010.91 4357.09 1653.83 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4607.03 3302.86 1304.17 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4608.09 3298.09 1309.99 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4711.36 3374.25 1337.11 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4712.76 3375.33 1337.43 0.72 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4719.02 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   4766.05 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   5756.58 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   4065.21 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3008.39 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2996.57 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2956.72 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3014.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5577.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5629.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5165.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4839.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3602.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3593.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3530.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3545.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5586.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5642.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4947.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4875.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3628.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3618.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3559.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3563.69 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5616.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5671.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5007.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4907.85 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3657.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3648.49 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3589.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3592.09 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5675.84 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   5731.32 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   5072.66 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   4969.83 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3717.07 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3707.87 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3647.96 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3650.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5645.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5699.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5049.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4940.68 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3686.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3677.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3618.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3621.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5646.75 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5699.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5056.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4943.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3687.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3677.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3619.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3621.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5667.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5719.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5081.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4964.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3703.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3694.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3640.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3642.09 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5829.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5883.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5230.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   5159.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3852.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3843.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3763.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3769.68 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   6779.94 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   6792.44 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   6127.47 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   6010.91 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   4607.03 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   4608.09 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4711.36 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4712.76 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   1660.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   1660.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   2265.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   1662.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   1152.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   1152.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   1149.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   1156.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   1671.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   1671.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   1699.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   1674.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1061.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1062.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1064.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1066.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   1622.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   1622.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   1628.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   1625.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   1608.81 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   1609.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   1613.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   1613.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   1578.81 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   1578.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   1583.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   1582.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   1619.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   1619.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   1623.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   1623.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   1636.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   1636.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   1640.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   1641.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1031.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   1656.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   1656.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   1661.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   1660.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   1035.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   1035.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   1034.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   1034.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   1764.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   1761.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   1769.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   1766.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   1132.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   1132.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   1134.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   1134.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   2122.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   2125.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   2127.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   2129.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   1549.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   1549.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   1544.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   1544.27 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 334.82 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 339.32 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 402.73 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.60 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 199.44 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.49 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 191.17 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 195.82 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 403.85 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 408.75 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 368.66 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.71 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 246.23 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.47 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.08 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.28 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 404.22 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 409.42 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 354.08 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 349.33 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 248.11 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 247.36 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.22 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.56 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 406.33 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 411.47 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 355.24 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 351.65 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 250.34 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 249.59 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.49 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.70 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 410.93 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 416.10 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 360.26 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 356.45 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.99 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.25 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 246.09 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 246.27 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 408.31 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 413.32 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 358.22 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 353.90 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 252.40 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 251.67 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 243.64 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 243.81 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 408.20 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 413.18 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 358.59 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 353.94 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 252.37 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 251.64 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 243.62 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 243.78 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 409.73 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 414.66 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 360.50 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 355.50 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.93 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.21 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.17 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.33 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 422.72 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 427.77 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 372.38 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 368.73 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 265.91 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 265.19 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.69 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.55 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 498.95 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 500.73 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.40 444.99 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.39 435.54 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 325.29 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.93 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.63 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.74 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0079 2026.59 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 3100.68 3720.81 0.249 0.299 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
G NW APARTMENT 3142.36 3770.83 0.252 0.303 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
OFFICE 3729.62 4475.55 0.300 0.360 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:30:00 40.25 0.00911
G NE APARTMENT 2635.61 3162.73 0.212 0.254 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
G N1 APARTMENT 1847.02 2216.43 0.148 0.178 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
G N2 APARTMENT 1838.23 2205.88 0.148 0.177 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 18:00:00 39.67 0.00911
G S1 APARTMENT 1770.43 2124.52 0.142 0.171 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
G S2 APARTMENT 1813.43 2176.12 0.146 0.175 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F2 SW APARTMENT 3740.02 4488.03 0.300 0.361 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F2 NW APARTMENT 3785.36 4542.43 0.304 0.365 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F2 SE APARTMENT 3414.08 4096.90 0.274 0.329 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F2 NE APARTMENT 3210.80 3852.95 0.258 0.310 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F2 N1 APARTMENT 2280.34 2736.41 0.183 0.220 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F2 N2 APARTMENT 2273.27 2727.92 0.183 0.219 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F2 S1 APARTMENT 2195.58 2634.69 0.176 0.212 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F2 S2 APARTMENT 2206.72 2648.06 0.177 0.213 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F3 SW APARTMENT 3743.35 4492.03 0.301 0.361 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F3 NW APARTMENT 3791.52 4549.82 0.305 0.366 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F3 SE APARTMENT 3279.02 3934.82 0.263 0.316 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:45:00 40.50 0.00911
F3 NE APARTMENT 3235.10 3882.12 0.260 0.312 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F3 N1 APARTMENT 2297.75 2757.30 0.185 0.222 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F3 N2 APARTMENT 2290.75 2748.90 0.184 0.221 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F3 S1 APARTMENT 2215.34 2658.41 0.178 0.214 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F3 S2 APARTMENT 2218.53 2662.23 0.178 0.214 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F4 SW APARTMENT 3762.96 4515.55 0.302 0.363 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F4 NW APARTMENT 3810.56 4572.68 0.306 0.367 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F4 SE APARTMENT 3289.75 3947.70 0.264 0.317 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F4 NE APARTMENT 3256.56 3907.87 0.262 0.314 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F4 N1 APARTMENT 2318.32 2781.98 0.186 0.223 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F4 N2 APARTMENT 2311.39 2773.67 0.186 0.223 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F4 S1 APARTMENT 2236.41 2683.69 0.180 0.216 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F4 S2 APARTMENT 2238.35 2686.01 0.180 0.216 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
M SW APARTMENT 3805.48 4566.58 0.306 0.367 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
M NW APARTMENT 3853.42 4624.11 0.310 0.371 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
M SE APARTMENT 3336.32 4003.59 0.268 0.322 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
M NE APARTMENT 3301.01 3961.21 0.265 0.318 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
M N1 APARTMENT 2361.44 2833.73 0.190 0.228 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
M N2 APARTMENT 2354.57 2825.49 0.189 0.227 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
M S1 APARTMENT 2278.98 2734.78 0.183 0.220 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
M S2 APARTMENT 2280.65 2736.78 0.183 0.220 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F6 SW APARTMENT 3781.25 4537.50 0.304 0.365 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F6 NW APARTMENT 3827.66 4593.19 0.308 0.369 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F6 SE APARTMENT 3317.35 3980.82 0.267 0.320 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F6 NE APARTMENT 3277.37 3932.84 0.263 0.316 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F6 N1 APARTMENT 2337.47 2804.97 0.188 0.225 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F6 N2 APARTMENT 2330.68 2796.82 0.187 0.225 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F6 S1 APARTMENT 2256.29 2707.55 0.181 0.218 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F6 S2 APARTMENT 2257.85 2709.41 0.181 0.218 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F7 SW APARTMENT 3780.24 4536.28 0.304 0.364 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F7 NW APARTMENT 3826.35 4591.62 0.307 0.369 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F7 SE APARTMENT 3320.82 3984.99 0.267 0.320 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F7 NE APARTMENT 3277.72 3933.26 0.263 0.316 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F7 N1 APARTMENT 2337.11 2804.53 0.188 0.225 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F7 N2 APARTMENT 2330.38 2796.46 0.187 0.225 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:30:00 40.16 0.00911
F7 S1 APARTMENT 2256.09 2707.31 0.181 0.217 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F7 S2 APARTMENT 2257.57 2709.08 0.181 0.218 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F8 SW APARTMENT 3794.39 4553.27 0.305 0.366 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F8 NW APARTMENT 3840.01 4608.02 0.308 0.370 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F8 SE APARTMENT 3338.48 4006.18 0.268 0.322 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
F8 NE APARTMENT 3292.23 3950.67 0.264 0.317 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:15:00 40.01 0.00911
F8 N1 APARTMENT 2351.64 2821.97 0.189 0.227 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:45:00 39.91 0.00911
F8 N2 APARTMENT 2344.96 2813.95 0.188 0.226 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:45:00 39.91 0.00911
F8 S1 APARTMENT 2270.47 2724.57 0.182 0.219 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F8 S2 APARTMENT 2271.95 2726.34 0.183 0.219 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F9 SW APARTMENT 3914.69 4697.62 0.314 0.377 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
F9 NW APARTMENT 3961.42 4753.71 0.318 0.382 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:45:00 40.84 0.00911
F9 SE APARTMENT 3448.56 4138.27 0.277 0.332 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
F9 NE APARTMENT 3414.67 4097.61 0.274 0.329 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03 0.00911
F9 N1 APARTMENT 2462.56 2955.07 0.198 0.237 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:45:00 39.91 0.00911
F9 N2 APARTMENT 2455.91 2947.10 0.197 0.237 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 17:45:00 39.91 0.00911
F9 S1 APARTMENT 2367.88 2841.45 0.190 0.228 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 41.71 0.00911
F9 S2 APARTMENT 2366.57 2839.88 0.190 0.228 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:30:00 42.00 0.00911
T SW APARTMENT 4620.61 5544.73 0.371 0.445 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:45:00 41.56 0.00911
T NW APARTMENT 4637.10 5564.52 0.373 0.447 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:15:00 41.22 0.00911
T SE APARTMENT 4120.96 4945.15 0.331 0.397 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
T NE APARTMENT 4033.40 4840.09 0.324 0.389 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:45:00 42.00 0.00911
T N1 APARTMENT 3012.40 3614.89 0.242 0.290 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03 0.00911
T N2 APARTMENT 2999.83 3599.79 0.241 0.289 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 41.71 0.00911
T S1 APARTMENT 3071.12 3685.34 0.247 0.296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911
T S2 APARTMENT 3072.18 3686.62 0.247 0.296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:15:00 42.00 0.00911


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1005.51 1206.62 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
G NW APARTMENT 1005.58 1206.70 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 09:15:00 6.30 0.00607
OFFICE 1330.91 1597.09 0.061 0.073 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 18:45:00 6.30 0.00607
G NE APARTMENT 1007.24 1208.69 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 09:15:00 6.30 0.00607
G N1 APARTMENT 575.63 690.75 0.026 0.032 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
G N2 APARTMENT 575.67 690.80 0.026 0.032 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
G S1 APARTMENT 573.05 687.66 0.026 0.031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
G S2 APARTMENT 578.92 694.71 0.026 0.032 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 09:15:00 6.30 0.00607
F2 SW APARTMENT 1015.15 1218.18 0.046 0.056 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 NW APARTMENT 1014.56 1217.47 0.046 0.056 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 SE APARTMENT 1038.64 1246.37 0.047 0.057 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 NE APARTMENT 1017.16 1220.59 0.046 0.056 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 N1 APARTMENT 499.37 599.24 0.023 0.027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 N2 APARTMENT 499.44 599.32 0.023 0.027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 S1 APARTMENT 501.34 601.61 0.023 0.027 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F2 S2 APARTMENT 502.83 603.40 0.023 0.028 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 SW APARTMENT 973.37 1168.04 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 NW APARTMENT 973.36 1168.03 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 SE APARTMENT 978.74 1174.49 0.045 0.054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 NE APARTMENT 976.37 1171.64 0.045 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 N1 APARTMENT 456.62 547.94 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 N2 APARTMENT 456.69 548.03 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 S1 APARTMENT 456.24 547.49 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F3 S2 APARTMENT 456.55 547.86 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 SW APARTMENT 961.85 1154.22 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 NW APARTMENT 962.19 1154.62 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 SE APARTMENT 965.41 1158.50 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 NE APARTMENT 965.49 1158.59 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 N1 APARTMENT 442.99 531.59 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 N2 APARTMENT 443.08 531.69 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 S1 APARTMENT 442.03 530.44 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F4 S2 APARTMENT 442.15 530.58 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M SW APARTMENT 936.48 1123.77 0.043 0.051 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M NW APARTMENT 935.94 1123.13 0.043 0.051 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M SE APARTMENT 940.04 1128.05 0.043 0.052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M NE APARTMENT 939.47 1127.36 0.043 0.051 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M N1 APARTMENT 416.94 500.33 0.019 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M N2 APARTMENT 417.03 500.44 0.019 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M S1 APARTMENT 416.81 500.17 0.019 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
M S2 APARTMENT 416.90 500.29 0.019 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 SW APARTMENT 970.65 1164.78 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 NW APARTMENT 970.97 1165.16 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 SE APARTMENT 974.38 1169.25 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 NE APARTMENT 974.68 1169.62 0.044 0.053 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 N1 APARTMENT 448.14 537.77 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 N2 APARTMENT 448.23 537.88 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 S1 APARTMENT 447.14 536.57 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F6 S2 APARTMENT 447.24 536.69 0.020 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 SW APARTMENT 985.15 1182.18 0.045 0.054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 NW APARTMENT 985.27 1182.32 0.045 0.054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 SE APARTMENT 989.02 1186.83 0.045 0.054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 NE APARTMENT 989.13 1186.96 0.045 0.054 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 N1 APARTMENT 461.01 553.21 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 N2 APARTMENT 461.11 553.33 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 S1 APARTMENT 460.21 552.25 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F7 S2 APARTMENT 460.31 552.37 0.021 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 SW APARTMENT 1002.16 1202.59 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 NW APARTMENT 1001.89 1202.27 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 SE APARTMENT 1006.16 1207.39 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 NE APARTMENT 1005.89 1207.06 0.046 0.055 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 N1 APARTMENT 476.67 572.00 0.022 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 N2 APARTMENT 476.77 572.12 0.022 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 S1 APARTMENT 476.25 571.50 0.022 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F8 S2 APARTMENT 476.35 571.62 0.022 0.026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 SW APARTMENT 1093.43 1312.11 0.050 0.060 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 NW APARTMENT 1090.88 1309.05 0.050 0.060 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 SE APARTMENT 1097.57 1317.09 0.050 0.060 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 NE APARTMENT 1095.02 1314.02 0.050 0.060 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 N1 APARTMENT 559.24 671.09 0.026 0.031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 N2 APARTMENT 559.35 671.21 0.026 0.031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 S1 APARTMENT 560.85 673.02 0.026 0.031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
F9 S2 APARTMENT 560.96 673.15 0.026 0.031 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T SW APARTMENT 1396.57 1675.88 0.064 0.077 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T NW APARTMENT 1398.67 1678.41 0.064 0.077 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T SE APARTMENT 1400.43 1680.52 0.064 0.077 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T NE APARTMENT 1402.54 1683.05 0.064 0.077 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T N1 APARTMENT 911.65 1093.98 0.042 0.050 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T N2 APARTMENT 911.76 1094.11 0.042 0.050 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T S1 APARTMENT 907.16 1088.59 0.041 0.050 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607
T S2 APARTMENT 907.27 1088.72 0.041 0.050 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6.30 0.00607


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.30 0.30 0.06 0.06
AIRLOOP G NW 0.30 0.30 0.06 0.06
AIRLOOP OFFICE 0.36 0.36 0.07 0.07
AIRLOOP G NE 0.25 0.25 0.06 0.06
AIRLOOP G N1 0.18 0.18 0.03 0.03
AIRLOOP G N2 0.18 0.18 0.03 0.03
AIRLOOP G S1 0.17 0.17 0.03 0.03
AIRLOOP G S2 0.17 0.17 0.03 0.03
AIRLOOP F2 SW 0.36 0.36 0.06 0.06
AIRLOOP F2 NW 0.36 0.36 0.06 0.06
AIRLOOP F2 SE 0.33 0.33 0.06 0.06
AIRLOOP F2 NE 0.31 0.31 0.06 0.06
AIRLOOP F2 N1 0.22 0.22 0.03 0.03
AIRLOOP F2 N2 0.22 0.22 0.03 0.03
AIRLOOP F2 S1 0.21 0.21 0.03 0.03
AIRLOOP F2 S2 0.21 0.21 0.03 0.03
AIRLOOP F3 SW 0.36 0.36 0.05 0.05
AIRLOOP F3 NW 0.37 0.37 0.05 0.05
AIRLOOP F3 SE 0.32 0.32 0.05 0.05
AIRLOOP F3 NE 0.31 0.31 0.05 0.05
AIRLOOP F3 N1 0.22 0.22 0.03 0.03
AIRLOOP F3 N2 0.22 0.22 0.03 0.03
AIRLOOP F3 S1 0.21 0.21 0.03 0.03
AIRLOOP F3 S2 0.21 0.21 0.03 0.03
AIRLOOP F4 SW 0.36 0.36 0.05 0.05
AIRLOOP F4 NW 0.37 0.37 0.05 0.05
AIRLOOP F4 SE 0.32 0.32 0.05 0.05
AIRLOOP F4 NE 0.31 0.31 0.05 0.05
AIRLOOP F4 N1 0.22 0.22 0.03 0.03
AIRLOOP F4 N2 0.22 0.22 0.03 0.03
AIRLOOP F4 S1 0.22 0.22 0.03 0.03
AIRLOOP F4 S2 0.22 0.22 0.03 0.03
AIRLOOP M SW 0.37 0.37 0.05 0.05
AIRLOOP M NW 0.37 0.37 0.05 0.05
AIRLOOP M SE 0.32 0.32 0.05 0.05
AIRLOOP M NE 0.32 0.32 0.05 0.05
AIRLOOP M N1 0.23 0.23 0.03 0.03
AIRLOOP M N2 0.23 0.23 0.03 0.03
AIRLOOP M S1 0.22 0.22 0.03 0.03
AIRLOOP M S2 0.22 0.22 0.03 0.03
AIRLOOP F6 SW 0.36 0.36 0.05 0.05
AIRLOOP F6 NW 0.37 0.37 0.05 0.05
AIRLOOP F6 SE 0.32 0.32 0.05 0.05
AIRLOOP F6 NE 0.32 0.32 0.05 0.05
AIRLOOP F6 N1 0.23 0.23 0.03 0.03
AIRLOOP F6 N2 0.22 0.22 0.03 0.03
AIRLOOP F6 S1 0.22 0.22 0.03 0.03
AIRLOOP F6 S2 0.22 0.22 0.03 0.03
AIRLOOP F7 SW 0.36 0.36 0.05 0.05
AIRLOOP F7 NW 0.37 0.37 0.05 0.05
AIRLOOP F7 SE 0.32 0.32 0.05 0.05
AIRLOOP F7 NE 0.32 0.32 0.05 0.05
AIRLOOP F7 N1 0.23 0.23 0.03 0.03
AIRLOOP F7 N2 0.22 0.22 0.03 0.03
AIRLOOP F7 S1 0.22 0.22 0.03 0.03
AIRLOOP F7 S2 0.22 0.22 0.03 0.03
AIRLOOP F8 SW 0.37 0.37 0.05 0.05
AIRLOOP F8 NW 0.37 0.37 0.05 0.05
AIRLOOP F8 SE 0.32 0.32 0.06 0.06
AIRLOOP F8 NE 0.32 0.32 0.06 0.06
AIRLOOP F8 N1 0.23 0.23 0.03 0.03
AIRLOOP F8 N2 0.23 0.23 0.03 0.03
AIRLOOP F8 S1 0.22 0.22 0.03 0.03
AIRLOOP F8 S2 0.22 0.22 0.03 0.03
AIRLOOP F9 SW 0.38 0.38 0.06 0.06
AIRLOOP F9 NW 0.38 0.38 0.06 0.06
AIRLOOP F9 SE 0.33 0.33 0.06 0.06
AIRLOOP F9 NE 0.33 0.33 0.06 0.06
AIRLOOP F9 N1 0.24 0.24 0.03 0.03
AIRLOOP F9 N2 0.24 0.24 0.03 0.03
AIRLOOP F9 S1 0.23 0.23 0.03 0.03
AIRLOOP F9 S2 0.23 0.23 0.03 0.03
AIRLOOP T SW 0.45 0.45 0.08 0.08
AIRLOOP T NW 0.45 0.45 0.08 0.08
AIRLOOP T SE 0.40 0.40 0.08 0.08
AIRLOOP T NE 0.39 0.39 0.08 0.08
AIRLOOP T N1 0.29 0.29 0.05 0.05
AIRLOOP T N2 0.29 0.29 0.05 0.05
AIRLOOP T S1 0.30 0.30 0.05 0.05
AIRLOOP T S2 0.30 0.30 0.05 0.05



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 6183.75 3519.00 1684.75
G NW APARTMENT 5525.75 4356.25 1790.50
OFFICE 1991.00 140.50 62.75
G NE APARTMENT 5553.00 4335.75 1744.75
G N1 APARTMENT 5363.25 5026.25 2260.75
G N2 APARTMENT 5361.75 5027.75 2265.75
G S1 APARTMENT 6038.75 3704.25 1919.50
G S2 APARTMENT 6071.00 3653.25 1899.00
F2 SW APARTMENT 7210.50 1729.50 990.75
F2 NW APARTMENT 6219.25 2842.25 1065.50
F2 SE APARTMENT 7332.00 1574.75 876.75
F2 NE APARTMENT 6238.50 2822.00 1010.25
F2 N1 APARTMENT 6159.00 3113.25 1269.25
F2 N2 APARTMENT 6158.25 3116.50 1269.25
F2 S1 APARTMENT 7445.00 1609.00 1068.50
F2 S2 APARTMENT 7460.75 1604.25 1068.00
F3 SW APARTMENT 7478.25 1573.25 1005.50
F3 NW APARTMENT 6401.75 2625.00 1071.75
F3 SE APARTMENT 7510.75 1542.75 956.75
F3 NE APARTMENT 6429.75 2604.25 1019.50
F3 N1 APARTMENT 6385.25 2797.25 1255.75
F3 N2 APARTMENT 6384.00 2803.00 1254.25
F3 S1 APARTMENT 7783.25 1388.50 1065.75
F3 S2 APARTMENT 7784.00 1387.25 1065.25
F4 SW APARTMENT 7536.25 1551.50 1031.25
F4 NW APARTMENT 6455.75 2569.75 1091.75
F4 SE APARTMENT 7550.00 1516.50 962.25
F4 NE APARTMENT 6482.50 2540.25 1044.25
F4 N1 APARTMENT 6469.25 2686.25 1267.25
F4 N2 APARTMENT 6466.00 2689.25 1265.75
F4 S1 APARTMENT 7864.75 1361.25 1076.50
F4 S2 APARTMENT 7861.00 1362.75 1076.75
M SW APARTMENT 7582.00 1503.50 1015.00
M NW APARTMENT 6503.50 2503.50 1083.25
M SE APARTMENT 7596.75 1472.75 954.00
M NE APARTMENT 6531.00 2470.00 1036.25
M N1 APARTMENT 6539.50 2561.00 1228.50
M N2 APARTMENT 6537.50 2565.50 1227.75
M S1 APARTMENT 7920.00 1311.25 1054.50
M S2 APARTMENT 7917.00 1314.75 1056.25
F6 SW APARTMENT 7514.75 1621.50 1092.00
F6 NW APARTMENT 6441.75 2644.50 1154.75
F6 SE APARTMENT 7519.50 1582.75 1020.00
F6 NE APARTMENT 6471.25 2619.50 1106.50
F6 N1 APARTMENT 6463.50 2749.25 1330.50
F6 N2 APARTMENT 6463.25 2754.25 1329.00
F6 S1 APARTMENT 7846.00 1417.50 1131.50
F6 S2 APARTMENT 7842.75 1418.50 1131.25
F7 SW APARTMENT 7462.00 1685.25 1127.50
F7 NW APARTMENT 6404.25 2727.75 1194.00
F7 SE APARTMENT 7471.25 1651.75 1060.75
F7 NE APARTMENT 6437.00 2714.75 1142.75
F7 N1 APARTMENT 6420.25 2856.50 1378.00
F7 N2 APARTMENT 6422.00 2861.75 1377.00
F7 S1 APARTMENT 7795.25 1482.00 1177.25
F7 S2 APARTMENT 7794.25 1483.75 1177.50
F8 SW APARTMENT 7415.25 1735.00 1146.25
F8 NW APARTMENT 6372.75 2792.50 1210.25
F8 SE APARTMENT 7422.50 1696.75 1081.00
F8 NE APARTMENT 6406.25 2773.75 1156.75
F8 N1 APARTMENT 6388.75 2930.00 1394.75
F8 N2 APARTMENT 6387.25 2934.75 1393.75
F8 S1 APARTMENT 7747.25 1520.50 1190.25
F8 S2 APARTMENT 7744.50 1524.00 1190.25
F9 SW APARTMENT 7291.25 1775.75 1103.00
F9 NW APARTMENT 6324.75 2824.25 1170.25
F9 SE APARTMENT 7327.25 1730.00 1040.25
F9 NE APARTMENT 6353.50 2802.50 1109.00
F9 N1 APARTMENT 6338.00 2954.50 1327.50
F9 N2 APARTMENT 6338.00 2957.50 1325.50
F9 S1 APARTMENT 7620.75 1568.50 1152.25
F9 S2 APARTMENT 7619.00 1561.25 1143.50
T SW APARTMENT 6794.75 2511.75 1260.50
T NW APARTMENT 6169.50 3224.00 1297.00
T SE APARTMENT 6848.50 2466.00 1206.25
T NE APARTMENT 6165.25 3187.25 1245.25
T N1 APARTMENT 6167.75 3352.00 1451.75
T N2 APARTMENT 6169.50 3341.50 1436.00
T S1 APARTMENT 7026.50 2369.25 1362.75
T S2 APARTMENT 7026.00 2371.75 1362.25
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 7987.75 5120.25 2354.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 31.50 0.00 31.50
G NW APARTMENT 0.00 30.75 0.00 30.75
OFFICE 0.25 0.25 0.00 0.00
G NE APARTMENT 0.00 38.75 0.00 38.75
G N1 APARTMENT 3.75 99.75 3.75 99.75
G N2 APARTMENT 2.50 101.50 2.50 101.50
G S1 APARTMENT 0.00 320.00 0.00 320.00
G S2 APARTMENT 0.00 265.00 0.00 265.00
F2 SW APARTMENT 0.00 16.25 0.00 16.25
F2 NW APARTMENT 0.00 16.50 0.00 16.50
F2 SE APARTMENT 0.00 4.75 0.00 4.75
F2 NE APARTMENT 0.00 14.00 0.00 14.00
F2 N1 APARTMENT 0.25 43.50 0.25 43.50
F2 N2 APARTMENT 0.25 44.25 0.25 44.25
F2 S1 APARTMENT 0.00 239.75 0.00 239.75
F2 S2 APARTMENT 0.00 225.25 0.00 225.25
F3 SW APARTMENT 0.00 17.75 0.00 17.75
F3 NW APARTMENT 0.00 16.25 0.00 16.25
F3 SE APARTMENT 0.00 29.25 0.00 29.25
F3 NE APARTMENT 0.00 13.75 0.00 13.75
F3 N1 APARTMENT 0.00 42.75 0.00 42.75
F3 N2 APARTMENT 0.00 43.50 0.00 43.50
F3 S1 APARTMENT 0.00 261.50 0.00 261.50
F3 S2 APARTMENT 0.00 256.00 0.00 256.00
F4 SW APARTMENT 0.00 16.25 0.00 16.25
F4 NW APARTMENT 0.00 15.25 0.00 15.25
F4 SE APARTMENT 0.00 21.75 0.00 21.75
F4 NE APARTMENT 0.00 14.50 0.00 14.50
F4 N1 APARTMENT 0.00 42.00 0.00 42.00
F4 N2 APARTMENT 0.00 42.75 0.00 42.75
F4 S1 APARTMENT 0.00 249.25 0.00 249.25
F4 S2 APARTMENT 0.00 247.50 0.00 247.50
M SW APARTMENT 0.00 14.50 0.00 14.50
M NW APARTMENT 0.00 14.75 0.00 14.75
M SE APARTMENT 0.00 18.75 0.00 18.75
M NE APARTMENT 0.00 15.00 0.00 15.00
M N1 APARTMENT 0.00 40.75 0.00 40.75
M N2 APARTMENT 0.00 41.00 0.00 41.00
M S1 APARTMENT 0.00 230.25 0.00 230.25
M S2 APARTMENT 0.00 229.00 0.00 229.00
F6 SW APARTMENT 0.00 14.50 0.00 14.50
F6 NW APARTMENT 0.00 16.00 0.00 16.00
F6 SE APARTMENT 0.00 18.75 0.00 18.75
F6 NE APARTMENT 0.00 17.00 0.00 17.00
F6 N1 APARTMENT 0.00 40.25 0.00 40.25
F6 N2 APARTMENT 0.00 40.75 0.00 40.75
F6 S1 APARTMENT 0.00 218.00 0.00 218.00
F6 S2 APARTMENT 0.00 215.25 0.00 215.25
F7 SW APARTMENT 0.00 13.50 0.00 13.50
F7 NW APARTMENT 0.00 14.75 0.00 14.75
F7 SE APARTMENT 0.00 18.00 0.00 18.00
F7 NE APARTMENT 0.00 18.75 0.00 18.75
F7 N1 APARTMENT 0.00 40.00 0.00 40.00
F7 N2 APARTMENT 0.00 41.00 0.00 41.00
F7 S1 APARTMENT 0.00 204.00 0.00 204.00
F7 S2 APARTMENT 0.00 201.50 0.00 201.50
F8 SW APARTMENT 0.00 12.75 0.00 12.75
F8 NW APARTMENT 0.00 13.75 0.00 13.75
F8 SE APARTMENT 0.00 15.75 0.00 15.75
F8 NE APARTMENT 0.00 18.75 0.00 18.75
F8 N1 APARTMENT 0.00 40.25 0.00 40.25
F8 N2 APARTMENT 0.00 40.75 0.00 40.75
F8 S1 APARTMENT 0.00 183.75 0.00 183.75
F8 S2 APARTMENT 0.00 182.50 0.00 182.50
F9 SW APARTMENT 0.00 10.00 0.00 10.00
F9 NW APARTMENT 0.00 14.00 0.00 14.00
F9 SE APARTMENT 0.00 11.75 0.00 11.75
F9 NE APARTMENT 0.00 8.25 0.00 8.25
F9 N1 APARTMENT 0.00 34.50 0.00 34.50
F9 N2 APARTMENT 0.00 35.50 0.00 35.50
F9 S1 APARTMENT 0.00 139.50 0.00 139.50
F9 S2 APARTMENT 0.00 133.75 0.00 133.75
T SW APARTMENT 0.00 19.75 0.00 19.75
T NW APARTMENT 0.00 20.50 0.00 20.50
T SE APARTMENT 0.00 7.00 0.00 7.00
T NE APARTMENT 0.00 1.25 0.00 1.25
T N1 APARTMENT 0.00 27.75 0.00 27.75
T N2 APARTMENT 0.00 23.75 0.00 23.75
T S1 APARTMENT 0.00 72.75 0.00 72.75
T S2 APARTMENT 0.00 73.75 0.00 73.75
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 5.75 456.75 5.50 456.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.360 0.036 0.000 0.275
G NW APARTMENT 1.71 2.50 268.96 0.360 0.036 0.000 0.259
OFFICE 0.94 1.00 268.96 0.527 0.052 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.360 0.036 0.000 0.259
G N1 APARTMENT 1.71 2.50 268.96 0.360 0.022 0.000 0.251
G N2 APARTMENT 1.71 2.50 268.97 0.360 0.022 0.000 0.251
G S1 APARTMENT 1.71 2.50 268.96 0.360 0.022 0.000 0.273
G S2 APARTMENT 1.71 2.50 268.97 0.360 0.022 0.000 0.273
F2 SW APARTMENT 1.71 2.50 268.96 0.360 0.051 0.000 0.294
F2 NW APARTMENT 1.71 2.50 268.96 0.360 0.051 0.000 0.281
F2 SE APARTMENT 1.71 2.50 268.96 0.360 0.051 0.000 0.295
F2 NE APARTMENT 1.71 2.50 268.96 0.360 0.051 0.000 0.281
F2 N1 APARTMENT 1.71 2.50 268.96 0.360 0.031 0.000 0.277
F2 N2 APARTMENT 1.71 2.50 268.97 0.360 0.031 0.000 0.277
F2 S1 APARTMENT 1.71 2.50 268.96 0.360 0.031 0.000 0.294
F2 S2 APARTMENT 1.71 2.50 268.97 0.360 0.031 0.000 0.294
F3 SW APARTMENT 1.71 2.50 268.96 0.360 0.061 0.000 0.305
F3 NW APARTMENT 1.71 2.50 268.96 0.360 0.061 0.000 0.293
F3 SE APARTMENT 1.71 2.50 268.96 0.360 0.061 0.000 0.306
F3 NE APARTMENT 1.71 2.50 268.96 0.360 0.061 0.000 0.293
F3 N1 APARTMENT 1.71 2.50 268.96 0.360 0.037 0.000 0.290
F3 N2 APARTMENT 1.71 2.50 268.97 0.360 0.037 0.000 0.290
F3 S1 APARTMENT 1.71 2.50 268.96 0.360 0.037 0.000 0.305
F3 S2 APARTMENT 1.71 2.50 268.97 0.360 0.037 0.000 0.305
F4 SW APARTMENT 1.71 2.50 268.96 0.360 0.068 0.000 0.312
F4 NW APARTMENT 1.71 2.50 268.96 0.360 0.068 0.000 0.300
F4 SE APARTMENT 1.71 2.50 268.96 0.360 0.068 0.000 0.312
F4 NE APARTMENT 1.71 2.50 268.96 0.360 0.068 0.000 0.300
F4 N1 APARTMENT 1.71 2.50 268.96 0.360 0.041 0.000 0.297
F4 N2 APARTMENT 1.71 2.50 268.97 0.360 0.041 0.000 0.297
F4 S1 APARTMENT 1.71 2.50 268.96 0.360 0.041 0.000 0.311
F4 S2 APARTMENT 1.71 2.50 268.97 0.360 0.041 0.000 0.311
M SW APARTMENT 1.71 2.50 268.96 0.360 0.074 0.000 0.317
M NW APARTMENT 1.71 2.50 268.96 0.360 0.074 0.000 0.306
M SE APARTMENT 1.71 2.50 268.96 0.360 0.074 0.000 0.318
M NE APARTMENT 1.71 2.50 268.96 0.360 0.074 0.000 0.306
M N1 APARTMENT 1.71 2.50 268.96 0.360 0.045 0.000 0.303
M N2 APARTMENT 1.71 2.50 268.97 0.360 0.045 0.000 0.303
M S1 APARTMENT 1.71 2.50 268.96 0.360 0.045 0.000 0.317
M S2 APARTMENT 1.71 2.50 268.97 0.360 0.045 0.000 0.317
F6 SW APARTMENT 1.71 2.50 268.96 0.360 0.079 0.000 0.323
F6 NW APARTMENT 1.71 2.50 268.96 0.360 0.079 0.000 0.310
F6 SE APARTMENT 1.71 2.50 268.96 0.360 0.079 0.000 0.323
F6 NE APARTMENT 1.71 2.50 268.96 0.360 0.079 0.000 0.310
F6 N1 APARTMENT 1.71 2.50 268.96 0.360 0.048 0.000 0.307
F6 N2 APARTMENT 1.71 2.50 268.97 0.360 0.048 0.000 0.307
F6 S1 APARTMENT 1.71 2.50 268.96 0.360 0.048 0.000 0.322
F6 S2 APARTMENT 1.71 2.50 268.97 0.360 0.048 0.000 0.322
F7 SW APARTMENT 1.71 2.50 268.96 0.360 0.083 0.000 0.327
F7 NW APARTMENT 1.71 2.50 268.96 0.360 0.083 0.000 0.314
F7 SE APARTMENT 1.71 2.50 268.96 0.360 0.083 0.000 0.328
F7 NE APARTMENT 1.71 2.50 268.96 0.360 0.083 0.000 0.314
F7 N1 APARTMENT 1.71 2.50 268.96 0.360 0.050 0.000 0.311
F7 N2 APARTMENT 1.71 2.50 268.97 0.360 0.050 0.000 0.311
F7 S1 APARTMENT 1.71 2.50 268.96 0.360 0.050 0.000 0.327
F7 S2 APARTMENT 1.71 2.50 268.97 0.360 0.050 0.000 0.327
F8 SW APARTMENT 1.71 2.50 268.96 0.360 0.087 0.000 0.334
F8 NW APARTMENT 1.71 2.50 268.96 0.360 0.087 0.000 0.320
F8 SE APARTMENT 1.71 2.50 268.96 0.360 0.087 0.000 0.334
F8 NE APARTMENT 1.71 2.50 268.96 0.360 0.087 0.000 0.320
F8 N1 APARTMENT 1.71 2.50 268.96 0.360 0.053 0.000 0.317
F8 N2 APARTMENT 1.71 2.50 268.97 0.360 0.053 0.000 0.317
F8 S1 APARTMENT 1.71 2.50 268.96 0.360 0.053 0.000 0.333
F8 S2 APARTMENT 1.71 2.50 268.97 0.360 0.053 0.000 0.333
F9 SW APARTMENT 1.71 2.50 268.96 0.360 0.091 0.000 0.337
F9 NW APARTMENT 1.71 2.50 268.96 0.360 0.091 0.000 0.322
F9 SE APARTMENT 1.71 2.50 268.96 0.360 0.091 0.000 0.337
F9 NE APARTMENT 1.71 2.50 268.96 0.360 0.091 0.000 0.322
F9 N1 APARTMENT 1.71 2.50 268.96 0.360 0.055 0.000 0.319
F9 N2 APARTMENT 1.71 2.50 268.97 0.360 0.055 0.000 0.319
F9 S1 APARTMENT 1.71 2.50 268.96 0.360 0.055 0.000 0.337
F9 S2 APARTMENT 1.71 2.50 268.97 0.360 0.055 0.000 0.337
T SW APARTMENT 1.71 2.50 268.96 0.360 0.094 0.000 0.338
T NW APARTMENT 1.71 2.50 268.96 0.360 0.094 0.000 0.325
T SE APARTMENT 1.71 2.50 268.96 0.360 0.094 0.000 0.339
T NE APARTMENT 1.71 2.50 268.96 0.360 0.094 0.000 0.326
T N1 APARTMENT 1.71 2.50 268.96 0.360 0.057 0.000 0.322
T N2 APARTMENT 1.71 2.50 268.97 0.360 0.057 0.000 0.322
T S1 APARTMENT 1.71 2.50 268.96 0.360 0.057 0.000 0.338
T S2 APARTMENT 1.71 2.50 268.97 0.360 0.057 0.000 0.338
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.485 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.330 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.330 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.329 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.329 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.327 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.327 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.328 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.328 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 807.36 25601.20 01-JAN-06:15 25601.20 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 2145.53 25981.73 12-JAN-03:15 124109.77 01-JUL-16:45
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
ElectricityPurchased:Plant 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
Cogeneration:ElectricityPurchased 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
ElectricityNet:Plant 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
Cogeneration:ElectricityNet 3989.90 63542.21 12-JAN-03:15 208969.32 01-JUL-17:15
ExteriorLights:Electricity 168.54 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.54 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:Fans:Electricity 807.36 25601.20 01-JAN-06:15 25601.20 01-JAN-00:15
Cooling:Electricity 1315.56 0.00 01-JAN-00:15 97362.94 01-JUL-16:45
Heating:Electricity 1.78 0.00 01-JAN-11:00 13266.21 09-FEB-20:15
Electricity:Plant 128.33 36.93 08-JAN-18:45 5899.29 09-MAY-16:15
HeatRejection:Electricity 64.63 0.00 01-JAN-00:15 3835.78 09-MAY-16:30
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 63.70 36.93 08-JAN-18:45 2063.51 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 816.51 9260.51 01-JAN-00:15 79739.68 10-JAN-08:00
Gas:Plant 816.51 9260.51 01-JAN-00:15 79739.68 10-JAN-08:00
WaterSystems:Gas 816.51 9260.51 01-JAN-00:15 79739.68 10-JAN-08:00
Water Heater:WaterSystems:Gas 816.51 9260.51 01-JAN-00:15 79739.68 10-JAN-08:00
Heating:Gas 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler:Heating:Gas 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 5829.13 0.00 01-JAN-00:15 446058.96 01-JUL-17:15
PlantLoopCoolingDemand:HVAC 5829.13 0.00 01-JAN-00:15 446058.96 01-JUL-17:15
CoolingCoils:PlantLoopCoolingDemand 5829.13 0.00 01-JAN-00:15 446058.96 01-JUL-17:15


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 8636.43 0.00 01-JAN-02:15 0.00 07-JUN-17:15
Water:Plant 8636.43 0.00 01-JAN-02:15 0.00 07-JUN-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 8636.43 0.00 01-JAN-02:15 0.00 07-JUN-17:15
MainsWater:Plant 8636.43 0.00 01-JAN-02:15 0.00 07-JUN-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 3857.91 0.00 01-JAN-00:15 0.00 07-JUN-16:30
HeatRejection:MainsWater 3857.91 0.00 01-JAN-00:15 0.00 07-JUN-16:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 622.06 295.81 19-JUL-01:15 69981.87 09-FEB-20:15
PlantLoopHeatingDemand:Plant 617.66 295.81 19-JUL-01:15 46306.80 18-JAN-07:15
WaterSystems:PlantLoopHeatingDemand 617.66 295.81 19-JUL-01:15 46306.80 18-JAN-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 8028.39 6575.13 27-FEB-03:00 612354.12 06-JUN-16:15
EnergyTransfer:Building 2812.44 4566.28 11-FEB-21:00 259793.60 06-JUN-16:15
EnergyTransfer:Zone:G SW APARTMENT 29.43 0.00 18-DEC-04:45 3514.10 01-OCT-15:15
Heating:EnergyTransfer 39.95 0.00 03-FEB-20:30 58973.60 09-FEB-20:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.69 0.00 01-JAN-08:45 840.07 09-FEB-20:30
Cooling:EnergyTransfer 2772.49 0.00 01-JAN-15:00 259793.60 06-JUN-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 28.74 0.00 01-JAN-00:15 3514.10 01-OCT-15:15
EnergyTransfer:Zone:G NW APARTMENT 24.59 0.00 03-DEC-16:00 3511.90 07-JUN-16:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.42 0.00 01-JAN-19:45 854.50 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G NW APARTMENT 23.17 0.00 01-JAN-00:15 3511.90 07-JUN-16:30
EnergyTransfer:Zone:OFFICE 34.70 0.04 15-NOV-22:15 4054.46 28-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 0.29 0.00 01-JAN-08:45 479.11 02-JAN-07:00
Cooling:EnergyTransfer:Zone:OFFICE 34.41 0.00 01-JAN-00:15 4054.46 28-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 24.00 0.00 01-MAR-06:45 2859.52 07-JUN-16:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.08 0.00 01-JAN-09:30 864.56 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G NE APARTMENT 22.92 0.00 01-JAN-00:15 2859.52 07-JUN-16:30
EnergyTransfer:Zone:G N1 APARTMENT 17.00 0.02 10-JAN-02:45 2001.05 07-JUN-17:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.55 0.00 01-JAN-09:45 656.56 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 16.45 0.00 01-JAN-00:15 2001.05 07-JUN-17:00
EnergyTransfer:Zone:G N2 APARTMENT 16.99 0.05 25-FEB-04:15 1989.98 07-JUN-17:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.54 0.00 01-JAN-09:45 657.65 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 16.45 0.00 01-JAN-00:15 1989.98 07-JUN-17:00
EnergyTransfer:Zone:G S1 APARTMENT 22.27 0.00 20-MAR-00:30 2154.34 27-NOV-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.11 0.00 01-JAN-00:15 603.16 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 22.15 0.00 01-JAN-13:30 2154.34 27-NOV-13:30
EnergyTransfer:Zone:G S2 APARTMENT 22.56 0.06 15-DEC-13:45 2182.62 27-NOV-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.12 0.00 01-JAN-00:15 572.99 09-FEB-20:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 22.44 0.00 01-JAN-13:30 2182.62 27-NOV-13:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 43.02 0.07 08-DEC-03:00 4299.13 27-APR-15:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.42 0.00 01-JAN-00:15 500.09 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 42.61 0.00 01-JAN-13:30 4299.13 27-APR-15:30
EnergyTransfer:Zone:F2 NW APARTMENT 34.86 0.01 20-DEC-01:00 4267.46 05-MAY-16:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 1.11 0.00 01-JAN-23:00 621.69 22-DEC-08:15
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 33.75 0.00 01-JAN-00:15 4267.46 05-MAY-16:30
EnergyTransfer:Zone:F2 SE APARTMENT 44.05 0.00 27-NOV-02:00 3882.65 01-OCT-14:00
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.29 0.00 01-JAN-00:15 384.83 29-DEC-06:15
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 43.77 0.00 01-JAN-05:00 3882.65 01-OCT-14:00
EnergyTransfer:Zone:F2 NE APARTMENT 34.34 0.02 03-MAR-07:00 3506.23 06-JUN-16:15
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.78 0.00 01-JAN-08:00 652.50 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 33.56 0.00 01-JAN-00:15 3506.23 06-JUN-16:15
EnergyTransfer:Zone:F2 N1 APARTMENT 25.55 0.04 26-JAN-01:00 2474.53 07-JUN-16:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.37 0.00 01-JAN-00:15 490.61 01-JAN-16:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 25.18 0.00 01-JAN-03:45 2474.53 07-JUN-16:30
EnergyTransfer:Zone:F2 N2 APARTMENT 25.55 0.11 26-JAN-01:00 2466.35 07-JUN-16:30
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.37 0.00 01-JAN-00:15 491.95 01-JAN-16:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 25.18 0.00 01-JAN-03:45 2466.35 07-JUN-16:30
EnergyTransfer:Zone:F2 S1 APARTMENT 34.26 0.08 25-JAN-10:15 2896.22 27-NOV-13:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.07 0.00 01-JAN-00:15 176.96 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 34.19 0.00 01-JAN-13:30 2896.22 27-NOV-13:00
EnergyTransfer:Zone:F2 S2 APARTMENT 34.35 0.24 25-JAN-10:15 2905.24 27-NOV-13:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.07 0.00 01-JAN-00:15 157.77 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 34.28 0.00 01-JAN-13:30 2905.24 27-NOV-13:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 44.55 0.02 07-FEB-04:15 4312.54 27-APR-15:30
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.35 0.00 01-JAN-00:15 527.17 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 44.20 0.00 01-JAN-13:30 4312.54 27-APR-15:30
EnergyTransfer:Zone:F3 NW APARTMENT 36.02 0.04 01-DEC-05:30 4279.83 05-MAY-16:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 0.94 0.00 01-JAN-22:45 640.20 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 35.08 0.00 01-JAN-00:15 4279.83 05-MAY-16:30
EnergyTransfer:Zone:F3 SE APARTMENT 44.53 0.02 27-DEC-00:30 3737.22 01-OCT-14:15
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.23 0.00 01-JAN-00:15 536.16 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 44.30 0.00 01-JAN-13:30 3737.22 01-OCT-14:15
EnergyTransfer:Zone:F3 NE APARTMENT 35.60 0.01 06-FEB-23:15 3540.07 06-JUN-16:15
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.66 0.00 01-JAN-07:45 674.85 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 34.94 0.00 01-JAN-00:15 3540.07 06-JUN-16:15
EnergyTransfer:Zone:F3 N1 APARTMENT 27.01 0.23 11-JAN-24:00 2512.03 05-MAY-17:15
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.31 0.00 01-JAN-00:15 383.26 01-JAN-16:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 26.69 0.00 01-JAN-13:15 2512.03 05-MAY-17:15
EnergyTransfer:Zone:F3 N2 APARTMENT 27.01 0.19 31-DEC-13:45 2501.77 05-MAY-17:15
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.31 0.00 01-JAN-00:15 386.17 01-JAN-16:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 26.70 0.00 01-JAN-13:30 2501.77 05-MAY-17:15
EnergyTransfer:Zone:F3 S1 APARTMENT 36.20 0.02 24-JAN-11:15 2942.86 27-NOV-12:45
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.05 0.00 01-JAN-00:15 170.93 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 36.14 0.00 01-JAN-13:30 2942.86 27-NOV-12:45
EnergyTransfer:Zone:F3 S2 APARTMENT 36.22 0.01 01-MAR-09:30 2947.26 27-NOV-12:45
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.05 0.00 01-JAN-00:15 170.46 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 36.17 0.00 01-JAN-13:30 2947.26 27-NOV-12:45
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 44.94 0.20 22-DEC-02:15 4333.39 27-APR-15:30
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.34 0.00 01-JAN-00:15 657.96 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 44.60 0.00 01-JAN-13:45 4333.39 27-APR-15:30
EnergyTransfer:Zone:F4 NW APARTMENT 36.38 0.08 07-DEC-06:45 4300.18 05-MAY-16:30
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 0.91 0.00 01-JAN-08:00 750.92 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 35.47 0.00 01-JAN-00:15 4300.18 05-MAY-16:30
EnergyTransfer:Zone:F4 SE APARTMENT 44.83 0.01 21-NOV-04:45 3781.66 15-APR-13:45
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.23 0.00 01-JAN-00:15 686.57 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 44.60 0.00 01-JAN-13:45 3781.66 15-APR-13:45
EnergyTransfer:Zone:F4 NE APARTMENT 35.99 0.03 19-DEC-21:30 3570.87 06-JUN-16:15
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.64 0.00 01-JAN-07:30 783.88 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 35.35 0.00 01-JAN-00:15 3570.87 06-JUN-16:15
EnergyTransfer:Zone:F4 N1 APARTMENT 27.47 0.04 12-JAN-00:45 2552.83 05-MAY-17:15
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.30 0.00 01-JAN-00:15 416.52 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 27.16 0.00 01-JAN-13:30 2552.83 05-MAY-17:15
EnergyTransfer:Zone:F4 N2 APARTMENT 27.47 0.02 26-JAN-00:45 2542.54 05-MAY-17:15
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.30 0.00 01-JAN-00:15 419.38 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 27.17 0.00 01-JAN-13:30 2542.54 05-MAY-17:15
EnergyTransfer:Zone:F4 S1 APARTMENT 36.73 0.13 16-DEC-19:00 2973.32 27-NOV-12:45
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.06 0.00 01-JAN-00:15 301.61 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 36.67 0.00 01-JAN-13:45 2973.32 27-NOV-12:45
EnergyTransfer:Zone:F4 S2 APARTMENT 36.73 0.20 26-DEC-10:45 2976.53 27-NOV-12:45
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.06 0.00 01-JAN-00:15 303.77 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 36.68 0.00 01-JAN-13:45 2976.53 27-NOV-12:45
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 45.69 0.02 24-NOV-04:15 4377.98 27-APR-15:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.34 0.00 01-JAN-00:15 765.63 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M SW APARTMENT 45.35 0.00 01-JAN-13:45 4377.98 27-APR-15:30
EnergyTransfer:Zone:M NW APARTMENT 37.12 0.02 10-NOV-22:00 4351.30 05-MAY-17:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.91 0.00 01-JAN-07:45 845.62 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M NW APARTMENT 36.22 0.00 01-JAN-00:15 4351.30 05-MAY-17:15
EnergyTransfer:Zone:M SE APARTMENT 45.58 0.00 25-DEC-01:15 3837.71 15-APR-13:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.23 0.00 01-JAN-00:15 795.93 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M SE APARTMENT 45.34 0.00 01-JAN-13:45 3837.71 15-APR-13:45
EnergyTransfer:Zone:M NE APARTMENT 36.74 0.01 02-FEB-23:30 3625.43 06-JUN-16:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.63 0.00 01-JAN-00:15 877.76 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M NE APARTMENT 36.11 0.00 01-JAN-00:30 3625.43 06-JUN-16:15
EnergyTransfer:Zone:M N1 APARTMENT 28.26 0.07 03-JAN-11:15 2606.71 05-MAY-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.31 0.00 01-JAN-00:15 500.26 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 27.95 0.00 01-JAN-13:15 2606.71 05-MAY-17:15
EnergyTransfer:Zone:M N2 APARTMENT 28.26 0.11 31-DEC-13:30 2596.48 05-MAY-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.30 0.00 01-JAN-00:15 502.92 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 27.96 0.00 01-JAN-13:30 2596.48 05-MAY-17:15
EnergyTransfer:Zone:M S1 APARTMENT 37.57 0.21 19-JAN-11:45 3021.41 27-NOV-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.06 0.00 01-JAN-00:15 403.81 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 37.51 0.00 01-JAN-13:45 3021.41 27-NOV-12:45
EnergyTransfer:Zone:M S2 APARTMENT 37.58 0.05 03-FEB-19:00 3023.99 27-NOV-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.06 0.00 01-JAN-00:15 406.22 09-FEB-20:30
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 37.52 0.00 01-JAN-13:45 3023.99 27-NOV-12:45
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 44.76 0.04 25-DEC-07:30 4349.87 27-APR-15:30
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.36 0.00 01-JAN-00:15 930.42 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 44.39 0.00 01-JAN-13:45 4349.87 27-APR-15:30
EnergyTransfer:Zone:F6 NW APARTMENT 36.40 0.03 20-DEC-23:30 4332.64 05-MAY-17:15
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 0.95 0.00 01-JAN-08:00 1004.28 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 35.44 0.00 01-JAN-00:15 4332.64 05-MAY-17:15
EnergyTransfer:Zone:F6 SE APARTMENT 44.64 0.07 11-DEC-01:30 3821.00 15-APR-13:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.25 0.00 01-JAN-00:15 959.32 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 44.39 0.00 01-JAN-13:45 3821.00 15-APR-13:45
EnergyTransfer:Zone:F6 NE APARTMENT 36.01 0.01 08-JAN-19:45 3606.13 05-MAY-16:30
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.67 0.00 01-JAN-07:30 1035.78 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 35.34 0.00 01-JAN-00:15 3606.13 05-MAY-16:30
EnergyTransfer:Zone:F6 N1 APARTMENT 27.52 0.08 03-JAN-11:15 2591.28 05-MAY-17:15
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.32 0.00 01-JAN-00:15 656.94 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 27.20 0.00 01-JAN-13:15 2591.28 05-MAY-17:15
EnergyTransfer:Zone:F6 N2 APARTMENT 27.52 0.07 01-JAN-17:00 2581.07 05-MAY-17:15
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.32 0.00 01-JAN-00:15 659.52 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 27.20 0.00 01-JAN-13:30 2581.07 05-MAY-17:15
EnergyTransfer:Zone:F6 S1 APARTMENT 36.62 0.29 30-DEC-13:15 2994.16 27-NOV-12:45
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.06 0.00 01-JAN-00:15 568.71 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 36.56 0.00 01-JAN-13:45 2994.16 27-NOV-12:45
EnergyTransfer:Zone:F6 S2 APARTMENT 36.63 0.05 06-DEC-18:15 2996.70 27-NOV-12:45
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.06 0.00 01-JAN-00:15 570.98 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 36.56 0.00 01-JAN-13:45 2996.70 27-NOV-12:45
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 44.38 0.02 17-JAN-09:15 4347.43 27-APR-15:15
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.38 0.00 01-JAN-00:15 1063.46 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 44.00 0.00 01-JAN-13:45 4347.43 27-APR-15:15
EnergyTransfer:Zone:F7 NW APARTMENT 36.19 0.01 23-DEC-02:15 4333.23 05-MAY-17:15
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 1.00 0.00 01-JAN-23:00 1133.54 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 35.19 0.00 01-JAN-00:15 4333.23 05-MAY-17:15
EnergyTransfer:Zone:F7 SE APARTMENT 44.27 0.15 14-JAN-01:30 3828.20 15-APR-13:45
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.26 0.00 01-JAN-00:15 1091.07 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 44.00 0.00 01-JAN-13:45 3828.20 15-APR-13:45
EnergyTransfer:Zone:F7 NE APARTMENT 35.80 0.04 10-DEC-00:30 3623.60 05-MAY-16:30
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 0.71 0.00 01-JAN-07:30 1162.79 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 35.09 0.00 01-JAN-00:15 3623.60 05-MAY-16:30
EnergyTransfer:Zone:F7 N1 APARTMENT 27.29 0.03 26-JAN-13:45 2598.10 05-MAY-17:15
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.34 0.00 01-JAN-00:15 784.11 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 26.95 0.00 01-JAN-13:15 2598.10 05-MAY-17:15
EnergyTransfer:Zone:F7 N2 APARTMENT 27.29 0.11 03-JAN-11:15 2587.92 05-MAY-17:15
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.33 0.00 01-JAN-00:15 786.47 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 26.96 0.00 01-JAN-13:15 2587.92 05-MAY-17:15
EnergyTransfer:Zone:F7 S1 APARTMENT 36.25 0.02 13-DEC-09:15 2991.23 27-NOV-12:45
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.07 0.00 01-JAN-00:15 699.85 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 36.18 0.00 01-JAN-13:45 2991.23 27-NOV-12:45
EnergyTransfer:Zone:F7 S2 APARTMENT 36.25 0.27 13-DEC-09:15 2993.65 27-NOV-12:45
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.07 0.00 01-JAN-00:15 702.00 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 36.18 0.00 01-JAN-13:45 2993.65 27-NOV-12:45
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 44.28 0.03 01-DEC-04:45 4361.39 27-APR-15:15
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.40 0.00 01-JAN-00:15 1183.20 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 43.87 0.00 01-JAN-13:45 4361.39 27-APR-15:15
EnergyTransfer:Zone:F8 NW APARTMENT 36.24 0.06 03-MAR-07:30 4347.04 05-MAY-17:15
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 1.05 0.00 01-JAN-23:00 1248.73 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 35.19 0.00 01-JAN-00:15 4347.04 05-MAY-17:15
EnergyTransfer:Zone:F8 SE APARTMENT 44.16 0.01 01-MAR-07:00 3849.95 15-APR-13:45
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.28 0.00 01-JAN-00:15 1207.47 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 43.88 0.00 01-JAN-13:45 3849.95 15-APR-13:45
EnergyTransfer:Zone:F8 NE APARTMENT 35.84 0.01 10-JAN-20:30 3652.92 05-MAY-16:30
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 0.75 0.00 01-JAN-07:30 1274.63 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 35.09 0.00 01-JAN-00:15 3652.92 05-MAY-16:30
EnergyTransfer:Zone:F8 N1 APARTMENT 27.32 0.15 25-DEC-15:30 2618.03 05-MAY-17:15
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.36 0.00 01-JAN-00:15 898.19 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 26.96 0.00 01-JAN-13:15 2618.03 05-MAY-17:15
EnergyTransfer:Zone:F8 N2 APARTMENT 27.32 0.05 27-DEC-12:30 2607.90 05-MAY-17:15
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.36 0.00 01-JAN-00:15 900.22 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 26.97 0.00 01-JAN-13:15 2607.90 05-MAY-17:15
EnergyTransfer:Zone:F8 S1 APARTMENT 36.14 0.25 09-DEC-12:45 2999.65 27-NOV-12:45
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.08 0.00 01-JAN-00:15 818.16 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 36.06 0.00 01-JAN-13:45 2999.65 27-NOV-12:45
EnergyTransfer:Zone:F8 S2 APARTMENT 36.14 0.08 27-FEB-19:45 3004.39 27-NOV-12:45
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.08 0.00 01-JAN-00:15 820.03 09-FEB-20:30
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 36.07 0.00 01-JAN-13:45 3004.39 27-NOV-12:45
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 44.97 0.03 23-NOV-06:45 4486.98 27-APR-15:30
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.48 0.00 01-JAN-00:15 1244.11 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 44.49 0.00 01-JAN-11:15 4486.98 27-APR-15:30
EnergyTransfer:Zone:F9 NW APARTMENT 37.21 0.01 02-FEB-15:00 4479.12 05-MAY-17:15
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 1.21 0.00 04-JAN-08:45 1300.83 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 36.01 0.00 01-JAN-00:15 4479.12 05-MAY-17:15
EnergyTransfer:Zone:F9 SE APARTMENT 44.82 0.03 19-FEB-01:30 3963.62 15-APR-14:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.34 0.00 01-JAN-00:15 1263.30 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 44.49 0.00 01-JAN-13:45 3963.62 15-APR-14:00
EnergyTransfer:Zone:F9 NE APARTMENT 36.76 0.01 24-JAN-23:15 3784.79 06-JUN-16:15
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 0.88 0.00 01-JAN-08:00 1322.99 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 35.88 0.00 01-JAN-00:15 3784.79 06-JUN-16:15
EnergyTransfer:Zone:F9 N1 APARTMENT 28.09 0.08 16-JAN-15:15 2724.32 05-MAY-17:15
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.42 0.00 01-JAN-00:15 956.98 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 27.66 0.00 01-JAN-12:45 2724.32 05-MAY-17:15
EnergyTransfer:Zone:F9 N2 APARTMENT 28.09 0.00 14-JAN-03:45 2714.49 05-MAY-17:15
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.42 0.00 01-JAN-00:15 958.77 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 27.67 0.00 01-JAN-12:45 2714.49 05-MAY-17:15
EnergyTransfer:Zone:F9 S1 APARTMENT 36.70 0.03 09-FEB-21:15 3049.07 27-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.10 0.00 01-JAN-00:15 887.23 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 36.60 0.00 01-JAN-13:45 3049.07 27-NOV-13:30
EnergyTransfer:Zone:F9 S2 APARTMENT 36.71 0.01 10-FEB-13:30 3054.35 27-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.10 0.00 01-JAN-00:15 888.75 09-FEB-20:15
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 36.61 0.00 01-JAN-13:45 3054.35 27-NOV-13:30
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 47.51 0.05 21-OCT-04:45 5316.61 28-MAR-15:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.48 0.00 01-JAN-09:45 1697.34 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T SW APARTMENT 46.03 0.00 01-JAN-00:15 5316.61 28-MAR-15:30
EnergyTransfer:Zone:T NW APARTMENT 40.43 0.02 25-NOV-21:15 5219.93 07-JUN-16:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 2.45 0.00 04-JAN-14:00 1717.92 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T NW APARTMENT 37.99 0.00 01-JAN-00:15 5219.93 07-JUN-16:30
EnergyTransfer:Zone:T SE APARTMENT 47.07 0.01 15-DEC-22:00 4699.58 01-OCT-13:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.21 0.00 01-JAN-08:45 1704.82 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T SE APARTMENT 45.86 0.00 01-JAN-00:15 4699.58 01-OCT-13:30
EnergyTransfer:Zone:T NE APARTMENT 39.69 0.32 18-OCT-06:15 4462.91 06-JUN-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 2.03 0.00 05-JAN-09:00 1727.56 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T NE APARTMENT 37.66 0.00 01-JAN-00:15 4462.91 06-JUN-16:15
EnergyTransfer:Zone:T N1 APARTMENT 30.32 0.01 19-JAN-21:30 3321.73 07-JUN-16:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.88 0.00 01-JAN-09:45 1399.53 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 29.44 0.00 01-JAN-00:15 3321.73 07-JUN-16:30
EnergyTransfer:Zone:T N2 APARTMENT 30.32 0.05 15-DEC-03:00 3316.73 07-JUN-16:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.87 0.00 01-JAN-09:45 1400.37 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 29.45 0.00 01-JAN-00:15 3316.73 07-JUN-16:30
EnergyTransfer:Zone:T S1 APARTMENT 38.25 0.02 17-FEB-01:45 3816.86 27-NOV-13:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.35 0.00 01-JAN-00:15 1370.16 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 37.90 0.00 01-JAN-02:30 3816.86 27-NOV-13:30
EnergyTransfer:Zone:T S2 APARTMENT 38.26 0.04 26-JAN-06:00 3820.97 27-NOV-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.35 0.00 01-JAN-00:15 1370.88 09-FEB-20:15
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 37.91 0.00 01-JAN-02:30 3820.97 27-NOV-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 617.66 295.81 19-JUL-01:15 46302.07 18-JAN-07:15
WaterSystems:EnergyTransfer 617.66 295.81 19-JUL-01:15 46302.07 18-JAN-07:15
sub cat:WaterSystems:EnergyTransfer 617.66 295.81 19-JUL-01:15 46302.07 18-JAN-07:15
EnergyTransfer:HVAC 4598.29 0.00 08-JAN-18:45 348859.93 01-JUL-17:15
CoolingCoils:EnergyTransfer 4592.61 0.00 01-JAN-00:15 348859.93 01-JUL-17:15
HeatingCoils:EnergyTransfer 5.69 0.00 01-JAN-11:00 46661.00 09-FEB-20:15
PlantLoopHeatingDemand:HVAC 4.40 0.00 01-JAN-11:00 35844.88 09-FEB-20:15
HeatingCoils:PlantLoopHeatingDemand 4.40 0.00 01-JAN-11:00 35844.88 09-FEB-20:15
Boilers:EnergyTransfer 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.687 -28.740 0.000 0.000 3.600 2.413 12.213 28.855 0.000 0.636 0.000 0.000 -5.693 0.000 -3.030 -10.941
G NW APARTMENT 1.424 -23.169 0.000 0.000 3.632 2.413 12.213 19.418 0.000 0.634 0.000 0.000 -5.599 0.000 -2.492 -8.474
OFFICE 0.292 -34.412 0.000 0.000 0.504 21.954 7.547 28.552 0.000 0.469 0.001 0.000 -5.644 0.000 -0.174 -19.088
G NE APARTMENT 1.076 -22.923 0.000 0.000 3.641 2.413 12.213 19.122 0.000 0.634 0.000 0.000 -5.310 0.000 -2.490 -8.376
G N1 APARTMENT 0.546 -16.450 0.000 0.000 3.639 2.413 12.213 9.302 0.000 0.448 0.000 0.000 -3.375 0.000 -2.210 -6.527
G N2 APARTMENT 0.541 -16.451 0.000 0.000 3.640 2.413 12.213 9.301 0.000 0.448 0.000 0.000 -3.372 0.000 -2.209 -6.524
G S1 APARTMENT 0.113 -22.153 0.000 0.000 3.594 2.413 12.213 18.862 0.000 0.448 0.000 0.000 -3.443 0.000 -2.888 -9.157
G S2 APARTMENT 0.117 -22.437 0.000 0.000 3.593 2.413 12.213 18.850 0.000 0.448 0.000 0.000 -3.449 0.000 -2.905 -8.842
F2 SW APARTMENT 0.415 -42.604 0.000 0.000 3.548 2.413 12.213 28.064 0.000 0.849 5.004 0.000 -6.359 0.000 -3.544 -0.000
F2 NW APARTMENT 1.109 -33.748 0.000 0.000 3.584 2.413 12.213 18.750 0.000 0.847 4.136 0.000 -6.244 0.000 -3.059 -0.000
F2 SE APARTMENT 0.288 -43.766 0.000 0.000 3.549 2.413 12.213 27.869 0.000 0.849 6.418 0.000 -6.251 0.000 -3.583 -0.001
F2 NE APARTMENT 0.781 -33.560 0.000 0.000 3.593 2.413 12.213 18.450 0.000 0.847 4.233 0.000 -5.918 0.000 -3.052 -0.001
F2 N1 APARTMENT 0.370 -25.179 0.000 0.000 3.586 2.413 12.213 8.870 0.000 0.580 3.776 0.000 -3.825 0.000 -2.804 -0.000
F2 N2 APARTMENT 0.367 -25.184 0.000 0.000 3.586 2.413 12.213 8.869 0.000 0.580 3.779 0.000 -3.822 0.000 -2.803 -0.000
F2 S1 APARTMENT 0.070 -34.185 0.000 0.000 3.540 2.413 12.213 18.345 0.000 0.581 4.289 0.000 -3.843 0.000 -3.422 -0.001
F2 S2 APARTMENT 0.071 -34.281 0.000 0.000 3.540 2.413 12.213 18.342 0.000 0.581 4.391 0.000 -3.845 0.000 -3.425 -0.000
F3 SW APARTMENT 0.349 -44.198 0.000 0.000 3.541 2.413 12.213 27.814 0.000 0.984 7.079 0.000 -6.485 0.000 -3.710 -0.000
F3 NW APARTMENT 0.944 -35.076 0.000 0.000 3.573 2.413 12.213 18.565 0.000 0.982 6.056 0.000 -6.406 0.000 -3.265 -0.000
F3 SE APARTMENT 0.234 -44.297 0.000 0.000 3.544 2.413 12.213 27.677 0.000 0.984 7.292 0.000 -6.339 0.000 -3.721 -0.000
F3 NE APARTMENT 0.662 -34.938 0.000 0.000 3.581 2.413 12.213 18.277 0.000 0.982 6.142 0.000 -6.072 0.000 -3.259 -0.000
F3 N1 APARTMENT 0.313 -26.692 0.000 0.000 3.571 2.413 12.213 8.783 0.000 0.667 5.705 0.000 -3.946 0.000 -3.027 -0.000
F3 N2 APARTMENT 0.310 -26.697 0.000 0.000 3.572 2.413 12.213 8.783 0.000 0.667 5.708 0.000 -3.943 0.000 -3.025 -0.000
F3 S1 APARTMENT 0.055 -36.144 0.000 0.000 3.531 2.413 12.213 18.186 0.000 0.667 6.586 0.000 -3.925 0.000 -3.582 -0.000
F3 S2 APARTMENT 0.055 -36.165 0.000 0.000 3.531 2.413 12.213 18.186 0.000 0.667 6.608 0.000 -3.925 0.000 -3.583 -0.000
F4 SW APARTMENT 0.342 -44.598 0.000 0.000 3.539 2.413 12.213 27.654 0.000 1.080 7.674 0.000 -6.532 0.000 -3.786 -0.000
F4 NW APARTMENT 0.914 -35.467 0.000 0.000 3.569 2.413 12.213 18.459 0.000 1.078 6.652 0.000 -6.474 0.000 -3.356 -0.000
F4 SE APARTMENT 0.231 -44.594 0.000 0.000 3.542 2.413 12.213 27.538 0.000 1.080 7.750 0.000 -6.380 0.000 -3.793 -0.000
F4 NE APARTMENT 0.638 -35.348 0.000 0.000 3.577 2.413 12.213 18.180 0.000 1.078 6.737 0.000 -6.137 0.000 -3.351 -0.000
F4 N1 APARTMENT 0.303 -27.163 0.000 0.000 3.566 2.413 12.213 8.741 0.000 0.726 6.321 0.000 -3.998 0.000 -3.121 -0.000
F4 N2 APARTMENT 0.301 -27.168 0.000 0.000 3.566 2.413 12.213 8.740 0.000 0.726 6.324 0.000 -3.995 0.000 -3.119 -0.000
F4 S1 APARTMENT 0.055 -36.671 0.000 0.000 3.529 2.413 12.213 18.090 0.000 0.726 7.245 0.000 -3.956 0.000 -3.646 -0.000
F4 S2 APARTMENT 0.056 -36.677 0.000 0.000 3.530 2.413 12.213 18.090 0.000 0.726 7.252 0.000 -3.955 0.000 -3.647 -0.000
M SW APARTMENT 0.342 -45.351 0.000 0.000 3.537 2.413 12.213 27.505 0.000 1.156 8.635 0.000 -6.580 0.000 -3.869 -0.000
M NW APARTMENT 0.907 -36.215 0.000 0.000 3.566 2.413 12.213 18.355 0.000 1.153 7.591 0.000 -6.535 0.000 -3.448 -0.000
M SE APARTMENT 0.234 -45.343 0.000 0.000 3.541 2.413 12.213 27.399 0.000 1.156 8.690 0.000 -6.427 0.000 -3.876 -0.001
M NE APARTMENT 0.635 -36.107 0.000 0.000 3.574 2.413 12.213 18.084 0.000 1.153 7.675 0.000 -6.195 0.000 -3.445 -0.000
M N1 APARTMENT 0.305 -27.951 0.000 0.000 3.562 2.413 12.213 8.695 0.000 0.772 7.243 0.000 -4.042 0.000 -3.211 -0.000
M N2 APARTMENT 0.303 -27.955 0.000 0.000 3.562 2.413 12.213 8.694 0.000 0.772 7.246 0.000 -4.039 0.000 -3.210 -0.000
M S1 APARTMENT 0.059 -37.513 0.000 0.000 3.528 2.413 12.213 18.001 0.000 0.773 8.232 0.000 -3.985 0.000 -3.720 -0.000
M S2 APARTMENT 0.059 -37.517 0.000 0.000 3.528 2.413 12.213 18.000 0.000 0.773 8.236 0.000 -3.984 0.000 -3.720 -0.000
F6 SW APARTMENT 0.363 -44.394 0.000 0.000 3.539 2.413 12.213 27.440 0.000 1.226 7.675 0.000 -6.567 0.000 -3.907 -0.000
F6 NW APARTMENT 0.954 -35.443 0.000 0.000 3.570 2.413 12.213 18.333 0.000 1.222 6.709 0.000 -6.513 0.000 -3.458 -0.000
F6 SE APARTMENT 0.250 -44.390 0.000 0.000 3.543 2.413 12.213 27.345 0.000 1.226 7.730 0.000 -6.414 0.000 -3.915 -0.000
F6 NE APARTMENT 0.672 -35.339 0.000 0.000 3.578 2.413 12.213 18.073 0.000 1.222 6.795 0.000 -6.173 0.000 -3.454 -0.000
F6 N1 APARTMENT 0.321 -27.197 0.000 0.000 3.566 2.413 12.213 8.700 0.000 0.816 6.405 0.000 -4.028 0.000 -3.208 -0.000
F6 N2 APARTMENT 0.318 -27.203 0.000 0.000 3.566 2.413 12.213 8.699 0.000 0.816 6.409 0.000 -4.025 0.000 -3.206 -0.000
F6 S1 APARTMENT 0.063 -36.558 0.000 0.000 3.530 2.413 12.213 17.963 0.000 0.817 7.286 0.000 -3.979 0.000 -3.748 -0.000
F6 S2 APARTMENT 0.063 -36.563 0.000 0.000 3.530 2.413 12.213 17.963 0.000 0.817 7.290 0.000 -3.978 0.000 -3.748 -0.000
F7 SW APARTMENT 0.383 -44.001 0.000 0.000 3.541 2.413 12.213 27.362 0.000 1.283 7.336 0.000 -6.570 0.000 -3.959 -0.000
F7 NW APARTMENT 0.996 -35.191 0.000 0.000 3.573 2.413 12.213 18.295 0.000 1.280 6.416 0.000 -6.507 0.000 -3.486 -0.000
F7 SE APARTMENT 0.264 -44.002 0.000 0.000 3.544 2.413 12.213 27.275 0.000 1.283 7.392 0.000 -6.415 0.000 -3.968 -0.000
F7 NE APARTMENT 0.709 -35.090 0.000 0.000 3.580 2.413 12.213 18.042 0.000 1.279 6.502 0.000 -6.166 0.000 -3.482 -0.000
F7 N1 APARTMENT 0.336 -26.954 0.000 0.000 3.569 2.413 12.213 8.691 0.000 0.852 6.129 0.000 -4.024 0.000 -3.224 -0.000
F7 N2 APARTMENT 0.334 -26.960 0.000 0.000 3.569 2.413 12.213 8.690 0.000 0.852 6.133 0.000 -4.021 0.000 -3.222 -0.000
F7 S1 APARTMENT 0.068 -36.177 0.000 0.000 3.531 2.413 12.213 17.918 0.000 0.852 6.955 0.000 -3.981 0.000 -3.791 -0.000
F7 S2 APARTMENT 0.068 -36.182 0.000 0.000 3.531 2.413 12.213 17.917 0.000 0.852 6.959 0.000 -3.980 0.000 -3.791 -0.000
F8 SW APARTMENT 0.405 -43.873 0.000 0.000 3.542 2.413 12.213 27.282 0.000 1.343 7.266 0.000 -6.575 0.000 -4.016 -0.000
F8 NW APARTMENT 1.047 -35.194 0.000 0.000 3.575 2.413 12.213 18.250 0.000 1.339 6.384 0.000 -6.505 0.000 -3.521 -0.000
F8 SE APARTMENT 0.283 -43.879 0.000 0.000 3.546 2.413 12.213 27.203 0.000 1.342 7.325 0.000 -6.420 0.000 -4.025 -0.001
F8 NE APARTMENT 0.749 -35.094 0.000 0.000 3.583 2.413 12.213 18.004 0.000 1.339 6.474 0.000 -6.164 0.000 -3.516 -0.000
F8 N1 APARTMENT 0.357 -26.963 0.000 0.000 3.571 2.413 12.213 8.676 0.000 0.892 6.107 0.000 -4.021 0.000 -3.246 -0.000
F8 N2 APARTMENT 0.355 -26.969 0.000 0.000 3.572 2.413 12.213 8.675 0.000 0.892 6.112 0.000 -4.018 0.000 -3.245 -0.000
F8 S1 APARTMENT 0.076 -36.062 0.000 0.000 3.532 2.413 12.213 17.870 0.000 0.893 6.891 0.000 -3.985 0.000 -3.840 -0.000
F8 S2 APARTMENT 0.076 -36.067 0.000 0.000 3.532 2.413 12.213 17.870 0.000 0.893 6.895 0.000 -3.984 0.000 -3.841 -0.000
F9 SW APARTMENT 0.478 -44.494 0.000 0.000 3.545 2.413 12.213 27.187 0.000 1.389 7.871 0.000 -6.570 0.000 -4.032 -0.000
F9 NW APARTMENT 1.206 -36.006 0.000 0.000 3.578 2.413 12.213 18.183 0.000 1.385 7.037 0.000 -6.498 0.000 -3.512 -0.000
F9 SE APARTMENT 0.336 -44.487 0.000 0.000 3.549 2.413 12.213 27.115 0.000 1.389 7.934 0.000 -6.416 0.000 -4.045 -0.000
F9 NE APARTMENT 0.876 -35.881 0.000 0.000 3.586 2.413 12.213 17.946 0.000 1.385 7.135 0.000 -6.161 0.000 -3.512 -0.000
F9 N1 APARTMENT 0.424 -27.663 0.000 0.000 3.575 2.413 12.213 8.647 0.000 0.920 6.705 0.000 -4.012 0.000 -3.223 -0.000
F9 N2 APARTMENT 0.421 -27.670 0.000 0.000 3.576 2.413 12.213 8.646 0.000 0.920 6.712 0.000 -4.009 0.000 -3.222 -0.000
F9 S1 APARTMENT 0.100 -36.602 0.000 0.000 3.535 2.413 12.213 17.816 0.000 0.922 7.436 0.000 -3.984 0.000 -3.849 -0.000
F9 S2 APARTMENT 0.100 -36.612 0.000 0.000 3.536 2.413 12.213 17.816 0.000 0.922 7.445 0.000 -3.982 0.000 -3.849 -0.000
T SW APARTMENT 1.480 -46.025 0.000 0.000 3.577 2.413 12.213 26.573 0.000 1.428 8.447 0.000 -6.126 0.000 -3.981 -0.001
T NW APARTMENT 2.446 -37.988 0.000 0.000 3.601 2.413 12.213 17.634 0.000 1.424 7.898 0.000 -6.108 0.000 -3.533 -0.000
T SE APARTMENT 1.213 -45.854 0.000 0.000 3.583 2.413 12.213 26.524 0.000 1.429 8.471 0.000 -5.989 0.000 -4.002 -0.000
T NE APARTMENT 2.031 -37.655 0.000 0.000 3.609 2.413 12.213 17.442 0.000 1.425 7.910 0.000 -5.815 0.000 -3.572 -0.000
T N1 APARTMENT 0.878 -29.437 0.000 0.000 3.599 2.413 12.213 8.436 0.000 0.945 7.933 0.000 -3.762 0.000 -3.219 -0.000
T N2 APARTMENT 0.874 -29.445 0.000 0.000 3.600 2.413 12.213 8.433 0.000 0.945 7.944 0.000 -3.757 0.000 -3.220 -0.000
T S1 APARTMENT 0.354 -37.895 0.000 0.000 3.568 2.413 12.213 17.504 0.000 0.948 8.437 0.000 -3.758 0.000 -3.783 -0.000
T S2 APARTMENT 0.354 -37.904 0.000 0.000 3.568 2.413 12.213 17.502 0.000 0.948 8.446 0.000 -3.756 0.000 -3.783 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 6.111 0.000 14.314 0.001 0.000 -1.405 0.000 -10.929 -26.621
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.967 0.000 0.074 0.000 0.000 -0.868 0.000 -0.054 -20.649
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.921 0.000 0.087 0.000 0.000 -0.903 0.000 -0.068 -20.566
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.885 0.000 0.095 0.000 0.000 -0.923 0.000 -0.079 -20.508
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 2.813 0.000 0.092 0.000 0.000 -0.968 0.000 -0.095 -38.901
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.859 0.000 0.110 0.000 0.000 -0.929 0.000 -0.092 -20.477
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.862 0.000 0.117 0.000 0.000 -0.920 0.000 -0.095 -20.493
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.854 0.000 0.123 0.000 0.000 -0.920 0.000 -0.099 -20.487
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.836 0.000 0.124 0.000 0.000 -0.923 0.000 -0.103 -20.464
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 2.682 0.000 0.096 0.000 0.000 -0.895 0.000 -0.118 -28.231
Total Facility 39.952 -2772.456 0.000 0.000 282.125 416.414 980.287 1484.049 0.000 90.996 494.045 0.000 -415.618 0.000 -284.465 -315.343


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 01-OCT-15:15 0.00 -3514.12 0.00 0.00 48.90 100.83 470.89 4239.32 0.00 28.19 0.00 0.00 0.00 0.00 0.00 -1374.01
G NW APARTMENT 07-JUN-16:30 0.00 -3517.91 0.00 0.00 82.47 144.04 588.62 3808.57 0.00 103.31 0.00 0.00 0.00 0.00 0.00 -1209.09
OFFICE 28-SEP-13:30 0.00 -4054.45 0.00 0.00 64.73 1622.33 544.91 3343.85 0.00 81.13 0.00 0.00 0.00 0.00 0.00 -1602.49
G NE APARTMENT 07-JUN-16:30 0.00 -2859.82 0.00 0.00 84.63 144.04 588.62 2188.16 0.00 105.38 0.00 0.00 0.00 0.00 0.00 -251.01
G N1 APARTMENT 07-JUN-17:00 0.00 -2001.35 0.00 0.00 83.53 144.04 588.62 1443.61 0.00 54.15 0.00 0.00 0.00 0.00 0.00 -312.60
G N2 APARTMENT 07-JUN-17:00 0.00 -1990.29 0.00 0.00 83.58 144.04 588.62 1444.29 0.00 54.18 0.00 0.00 0.00 0.00 0.00 -324.42
G S1 APARTMENT 27-NOV-13:30 0.00 -2153.57 0.00 0.00 40.75 28.81 388.49 3511.30 0.00 122.57 0.00 0.00 0.00 0.00 0.00 -1938.35
G S2 APARTMENT 27-NOV-13:30 0.00 -2181.85 0.00 0.00 40.75 28.81 388.49 3510.28 0.00 122.57 0.00 0.00 0.00 0.00 0.00 -1909.05
F2 SW APARTMENT 27-APR-15:30 0.00 -4298.99 0.00 0.00 48.87 100.83 470.89 3897.53 0.00 261.54 0.00 0.00 0.00 0.00 0.00 -480.68
F2 NW APARTMENT 05-MAY-16:30 0.00 -4269.20 0.00 0.00 84.76 144.04 588.62 3465.38 0.00 282.70 0.00 0.00 0.00 0.00 0.00 -296.29
F2 SE APARTMENT 01-OCT-14:00 0.00 -3882.51 0.00 0.00 40.65 28.81 382.60 3419.24 0.00 49.62 0.00 0.00 0.00 0.00 0.00 -38.41
F2 NE APARTMENT 06-JUN-16:10 0.00 -3508.70 0.00 0.00 84.70 144.04 588.62 2225.98 0.00 234.68 230.68 0.00 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 07-JUN-16:30 0.00 -2474.97 0.00 0.00 84.56 144.04 588.62 1463.54 0.00 91.21 103.00 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 07-JUN-16:30 0.00 -2466.71 0.00 0.00 84.57 144.04 588.62 1463.81 0.00 91.22 94.45 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 27-NOV-13:00 0.00 -2895.38 0.00 0.00 40.75 28.81 406.15 3610.84 0.00 86.47 0.00 0.00 0.00 0.00 0.00 -1277.64
F2 S2 APARTMENT 27-NOV-13:00 0.00 -2904.39 0.00 0.00 40.75 28.81 406.15 3610.60 0.00 86.47 0.00 0.00 0.00 0.00 0.00 -1268.39
F3 SW APARTMENT 27-APR-15:30 0.00 -4312.35 0.00 0.00 48.77 100.83 470.89 3848.10 0.00 308.17 0.00 0.00 0.00 0.00 0.00 -464.42
F3 NW APARTMENT 05-MAY-16:30 0.00 -4283.67 0.00 0.00 84.43 144.04 588.62 3442.22 0.00 333.03 0.00 0.00 0.00 0.00 0.00 -308.67
F3 SE APARTMENT 01-OCT-14:15 0.00 -3737.13 0.00 0.00 40.12 50.41 400.26 3281.23 0.00 55.79 0.00 0.00 0.00 0.00 0.00 -90.69
F3 NE APARTMENT 06-JUN-16:10 0.00 -3542.38 0.00 0.00 84.65 144.04 588.62 2238.59 0.00 277.44 209.04 0.00 0.00 0.00 0.00 0.00
F3 N1 APARTMENT 05-MAY-17:10 0.00 -2512.64 0.00 0.00 141.81 194.45 588.62 1217.09 0.00 181.54 189.12 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 05-MAY-17:10 0.00 -2502.38 0.00 0.00 141.81 194.45 588.62 1217.38 0.00 181.54 178.57 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 27-NOV-12:45 0.00 -2942.29 0.00 0.00 40.74 28.81 406.15 3658.87 0.00 45.08 0.00 0.00 0.00 0.00 0.00 -1237.35
F3 S2 APARTMENT 27-NOV-12:45 0.00 -2946.70 0.00 0.00 40.73 28.81 406.15 3658.62 0.00 44.82 0.00 0.00 0.00 0.00 0.00 -1232.43
F4 SW APARTMENT 27-APR-15:30 0.00 -4333.15 0.00 0.00 48.77 100.83 470.89 3813.98 0.00 343.94 0.00 0.00 0.00 0.00 0.00 -445.25
F4 NW APARTMENT 05-MAY-17:05 0.00 -4310.52 0.00 0.00 141.48 194.45 588.62 2958.28 0.00 335.54 92.14 0.00 0.00 0.00 0.00 0.00
F4 SE APARTMENT 15-APR-13:45 0.00 -3781.74 0.00 0.00 40.75 28.81 382.60 2894.38 0.00 382.68 52.52 0.00 0.00 0.00 0.00 0.00
F4 NE APARTMENT 06-JUN-16:10 0.00 -3573.07 0.00 0.00 84.54 144.04 588.62 2245.74 0.00 309.46 200.67 0.00 0.00 0.00 0.00 0.00
F4 N1 APARTMENT 05-MAY-17:10 0.00 -2553.42 0.00 0.00 141.81 194.45 588.62 1223.91 0.00 202.65 201.98 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 05-MAY-17:10 0.00 -2543.13 0.00 0.00 141.81 194.45 588.62 1224.20 0.00 202.65 191.39 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 27-NOV-12:45 0.00 -2972.77 0.00 0.00 40.72 28.81 406.15 3652.01 0.00 43.72 0.00 0.00 0.00 0.00 0.00 -1198.64
F4 S2 APARTMENT 27-NOV-12:45 0.00 -2975.98 0.00 0.00 40.71 28.81 406.15 3651.75 0.00 43.39 0.00 0.00 0.00 0.00 0.00 -1194.83
M SW APARTMENT 27-APR-15:30 0.00 -4377.72 0.00 0.00 48.78 100.83 470.89 3785.99 0.00 373.40 0.00 0.00 0.00 0.00 0.00 -402.17
M NW APARTMENT 05-MAY-17:05 0.00 -4366.08 0.00 0.00 141.40 194.45 588.62 2949.79 0.00 364.08 127.74 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 15-APR-13:45 0.00 -3837.80 0.00 0.00 40.75 28.81 382.60 2884.47 0.00 415.34 85.83 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 06-JUN-16:10 0.00 -3627.55 0.00 0.00 84.47 144.04 588.62 2249.78 0.00 335.69 224.95 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 05-MAY-17:10 0.00 -2607.27 0.00 0.00 141.81 194.45 588.62 1228.34 0.00 219.94 234.12 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 05-MAY-17:10 0.00 -2597.04 0.00 0.00 141.81 194.45 588.62 1228.63 0.00 219.94 223.59 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 27-NOV-12:45 0.00 -3020.85 0.00 0.00 40.74 28.81 406.15 3646.14 0.00 44.06 0.00 0.00 0.00 0.00 0.00 -1145.05
M S2 APARTMENT 27-NOV-12:45 0.00 -3023.43 0.00 0.00 40.74 28.81 406.15 3645.89 0.00 43.69 0.00 0.00 0.00 0.00 0.00 -1141.83
F6 SW APARTMENT 27-APR-15:30 0.00 -4349.58 0.00 0.00 48.78 100.83 470.89 3765.63 0.00 398.49 0.00 0.00 0.00 0.00 0.00 -435.04
F6 NW APARTMENT 05-MAY-17:05 0.00 -4336.29 0.00 0.00 141.27 194.45 588.62 2944.82 0.00 388.29 78.84 0.00 0.00 0.00 0.00 0.00
F6 SE APARTMENT 15-APR-13:45 0.00 -3821.08 0.00 0.00 40.75 28.81 382.60 2878.93 0.00 443.23 46.76 0.00 0.00 0.00 0.00 0.00
F6 NE APARTMENT 06-JUN-16:10 0.00 -3606.85 0.00 0.00 84.35 144.04 588.62 2254.86 0.00 357.99 176.99 0.00 0.00 0.00 0.00 0.00
F6 N1 APARTMENT 05-MAY-17:10 0.00 -2591.82 0.00 0.00 141.81 194.45 588.62 1233.65 0.00 234.74 198.54 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 05-MAY-17:10 0.00 -2581.62 0.00 0.00 141.81 194.45 588.62 1233.95 0.00 234.74 188.04 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 27-NOV-12:45 0.00 -2993.60 0.00 0.00 40.75 28.81 406.15 3642.71 0.00 43.91 0.00 0.00 0.00 0.00 0.00 -1168.72
F6 S2 APARTMENT 27-NOV-12:45 0.00 -2996.14 0.00 0.00 40.75 28.81 406.15 3642.52 0.00 43.73 0.00 0.00 0.00 0.00 0.00 -1165.81
F7 SW APARTMENT 27-APR-15:15 0.00 -4347.05 0.00 0.00 48.90 100.83 470.89 3772.79 0.00 433.78 0.00 0.00 0.00 0.00 0.00 -480.14
F7 NW APARTMENT 05-MAY-17:15 0.00 -4336.59 0.00 0.00 141.18 194.45 588.62 2939.42 0.00 410.60 62.31 0.00 0.00 0.00 0.00 0.00
F7 SE APARTMENT 15-APR-13:45 0.00 -3828.29 0.00 0.00 40.75 28.81 382.60 2873.05 0.00 467.82 35.27 0.00 0.00 0.00 0.00 0.00
F7 NE APARTMENT 05-MAY-16:30 0.00 -3623.88 0.00 0.00 84.76 144.04 588.62 1988.60 0.00 456.38 361.48 0.00 0.00 0.00 0.00 0.00
F7 N1 APARTMENT 05-MAY-17:10 0.00 -2598.62 0.00 0.00 141.81 194.45 588.62 1237.40 0.00 247.79 188.56 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 05-MAY-17:10 0.00 -2588.44 0.00 0.00 141.81 194.45 588.62 1237.70 0.00 247.79 178.08 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 27-NOV-12:45 0.00 -2990.68 0.00 0.00 40.75 28.81 406.15 3638.91 0.00 43.73 0.00 0.00 0.00 0.00 0.00 -1167.66
F7 S2 APARTMENT 27-NOV-12:45 0.00 -2993.10 0.00 0.00 40.75 28.81 406.15 3638.72 0.00 43.55 0.00 0.00 0.00 0.00 0.00 -1164.86
F8 SW APARTMENT 27-APR-15:15 0.00 -4360.99 0.00 0.00 48.90 100.83 470.89 3755.49 0.00 454.30 0.00 0.00 0.00 0.00 0.00 -469.42
F8 NW APARTMENT 05-MAY-17:15 0.00 -4350.39 0.00 0.00 141.12 194.45 588.62 2933.85 0.00 429.85 62.50 0.00 0.00 0.00 0.00 0.00
F8 SE APARTMENT 15-APR-13:45 0.00 -3850.05 0.00 0.00 40.75 28.81 382.60 2867.14 0.00 489.95 40.80 0.00 0.00 0.00 0.00 0.00
F8 NE APARTMENT 05-MAY-16:30 0.00 -3653.20 0.00 0.00 84.76 144.04 588.62 1992.93 0.00 477.96 364.88 0.00 0.00 0.00 0.00 0.00
F8 N1 APARTMENT 05-MAY-17:10 0.00 -2618.55 0.00 0.00 141.81 194.45 588.62 1240.01 0.00 259.49 194.16 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 05-MAY-17:10 0.00 -2608.42 0.00 0.00 141.81 194.45 588.62 1240.32 0.00 259.49 183.73 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 27-NOV-12:45 0.00 -2999.10 0.00 0.00 40.75 28.81 406.15 3635.40 0.00 44.02 0.00 0.00 0.00 0.00 0.00 -1156.03
F8 S2 APARTMENT 27-NOV-12:45 0.00 -3003.83 0.00 0.00 40.75 28.81 406.15 3635.21 0.00 43.92 0.00 0.00 0.00 0.00 0.00 -1151.01
F9 SW APARTMENT 27-APR-15:30 0.00 -4486.63 0.00 0.00 48.86 100.83 470.89 3710.36 0.00 459.61 0.00 0.00 0.00 0.00 0.00 -303.92
F9 NW APARTMENT 05-MAY-17:15 0.00 -4482.57 0.00 0.00 141.24 194.45 588.62 2923.66 0.00 447.79 186.81 0.00 0.00 0.00 0.00 0.00
F9 SE APARTMENT 15-APR-14:00 0.00 -3963.80 0.00 0.00 40.75 28.81 382.60 2805.73 0.00 533.92 171.99 0.00 0.00 0.00 0.00 0.00
F9 NE APARTMENT 06-JUN-16:10 0.00 -3786.69 0.00 0.00 84.42 144.04 588.62 2259.36 0.00 412.45 297.81 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 05-MAY-17:10 0.00 -2724.83 0.00 0.00 141.81 194.45 588.62 1238.69 0.00 270.15 291.11 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 05-MAY-17:10 0.00 -2715.00 0.00 0.00 141.81 194.45 588.62 1238.98 0.00 270.15 280.99 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 27-NOV-13:30 0.00 -3048.03 0.00 0.00 40.75 28.81 388.49 3436.87 0.00 118.63 0.00 0.00 0.00 0.00 0.00 -965.52
F9 S2 APARTMENT 27-NOV-13:30 0.00 -3053.31 0.00 0.00 40.75 28.81 388.49 3436.73 0.00 118.69 0.00 0.00 0.00 0.00 0.00 -960.15
T SW APARTMENT 28-MAR-15:30 0.00 -5316.82 0.00 0.00 48.90 100.83 470.89 4142.29 0.00 0.00 553.91 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 07-JUN-16:30 0.00 -5225.22 0.00 0.00 82.96 144.04 588.62 3648.97 0.00 272.06 488.58 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 01-OCT-13:30 0.00 -4699.44 0.00 0.00 40.44 28.81 382.60 3471.69 0.00 86.48 689.43 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 06-JUN-16:10 0.00 -4463.47 0.00 0.00 84.76 144.04 588.62 2198.84 0.00 430.04 1017.16 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 07-JUN-16:30 0.00 -3323.20 0.00 0.00 84.36 144.04 588.62 1445.71 0.00 166.18 894.30 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 07-JUN-16:30 0.00 -3317.38 0.00 0.00 84.48 144.04 588.62 1446.91 0.00 166.39 886.95 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 27-NOV-13:30 0.00 -3815.60 0.00 0.00 40.75 28.81 388.49 3394.18 0.00 118.84 0.00 0.00 0.00 0.00 0.00 -155.47
T S2 APARTMENT 27-NOV-13:30 0.00 -3819.71 0.00 0.00 40.75 28.81 388.49 3394.00 0.00 118.84 0.00 0.00 0.00 0.00 0.00 -151.18
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JUN-16:10 0.00 -259946.64 0.00 0.00 6667.06 18221.75 47207.76 174614.87 0.00 29919.95 0.00 0.00 0.00 0.00 0.00 -16684.74


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 09-FEB-20:25 840.05 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 293.08 0.00 -878.02 0.00 -1174.46 0.00
G NW APARTMENT 22-DEC-07:55 1097.02 0.00 0.00 0.00 159.12 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -251.79 0.00 -1013.36 -467.21
OFFICE 02-JAN-07:00 479.09 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 36.86 0.00 -1024.22 0.00 0.00 0.00
G NE APARTMENT 09-FEB-20:20 864.54 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 250.09 0.00 -859.52 0.00 -1174.46 0.00
G N1 APARTMENT 22-DEC-07:55 1029.76 0.00 0.00 0.00 157.66 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -161.08 0.00 -998.81 -503.76
G N2 APARTMENT 22-DEC-07:55 1038.67 0.00 0.00 0.00 157.72 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -160.88 0.00 -998.19 -513.55
G S1 APARTMENT 09-FEB-20:20 603.16 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 163.10 0.00 -543.60 0.00 -1142.01 0.00
G S2 APARTMENT 09-FEB-20:20 572.98 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 196.31 0.00 -546.63 0.00 -1142.01 0.00
F2 SW APARTMENT 09-FEB-20:25 510.05 0.00 0.00 0.00 164.98 230.46 523.87 0.00 0.00 0.00 905.36 0.00 -943.92 0.00 -1390.81 0.00
F2 NW APARTMENT 22-DEC-08:00 931.14 0.00 0.00 0.00 155.25 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -314.34 0.00 -1077.65 -170.62
F2 SE APARTMENT 29-DEC-06:10 422.05 0.00 0.00 0.00 162.99 100.83 317.85 0.00 0.00 0.00 1190.03 0.00 -667.08 0.00 -1526.68 0.00
F2 NE APARTMENT 09-FEB-20:25 652.98 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 741.14 0.00 -922.70 0.00 -1390.76 0.00
F2 N1 APARTMENT 24-JAN-10:45 738.32 0.00 0.00 0.00 45.16 28.81 406.15 114.88 0.00 0.00 0.00 0.00 0.00 0.00 -1021.63 -311.69
F2 N2 APARTMENT 24-JAN-10:45 718.44 0.00 0.00 0.00 45.13 28.81 406.15 114.21 0.00 0.00 0.00 0.00 0.00 0.00 -1022.46 -290.27
F2 S1 APARTMENT 09-FEB-20:25 223.11 0.00 0.00 0.00 164.91 230.46 523.87 0.00 0.00 0.00 785.42 0.00 -583.72 0.00 -1344.06 0.00
F2 S2 APARTMENT 09-FEB-20:25 217.37 0.00 0.00 0.00 164.84 230.46 523.87 0.00 0.00 0.00 792.55 0.00 -584.99 0.00 -1344.11 0.00
F3 SW APARTMENT 09-FEB-20:25 535.20 0.00 0.00 0.00 164.99 230.46 523.87 0.00 0.00 0.00 1042.82 0.00 -957.62 0.00 -1539.71 0.00
F3 NW APARTMENT 22-DEC-08:00 794.58 0.00 0.00 0.00 153.42 93.62 382.60 0.00 0.00 0.00 56.18 0.00 -346.63 0.00 -1133.77 0.00
F3 SE APARTMENT 09-FEB-20:25 538.52 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 1037.93 0.00 -956.11 0.00 -1539.68 0.00
F3 NE APARTMENT 09-FEB-20:25 675.32 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 883.41 0.00 -938.39 0.00 -1539.67 0.00
F3 N1 APARTMENT 22-DEC-08:05 523.52 0.00 0.00 0.00 73.85 43.21 388.49 0.00 0.00 0.00 103.46 0.00 -150.11 0.00 -982.41 0.00
F3 N2 APARTMENT 22-DEC-08:05 513.48 0.00 0.00 0.00 73.86 43.21 388.49 0.00 0.00 0.00 112.53 0.00 -149.50 0.00 -982.07 0.00
F3 S1 APARTMENT 09-FEB-20:25 220.73 0.00 0.00 0.00 164.91 230.46 523.87 0.00 0.00 0.00 937.35 0.00 -593.12 0.00 -1484.19 0.00
F3 S2 APARTMENT 09-FEB-20:25 220.87 0.00 0.00 0.00 164.90 230.46 523.87 0.00 0.00 0.00 937.23 0.00 -593.15 0.00 -1484.19 0.00
F4 SW APARTMENT 09-FEB-20:25 659.72 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 1039.54 0.00 -958.46 0.00 -1660.13 0.00
F4 NW APARTMENT 09-FEB-20:25 751.66 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 934.60 0.00 -945.48 0.00 -1660.13 0.00
F4 SE APARTMENT 09-FEB-20:25 687.10 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 1009.00 0.00 -955.32 0.00 -1660.13 0.00
F4 NE APARTMENT 09-FEB-20:25 784.02 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 898.54 0.00 -941.79 0.00 -1660.13 0.00
F4 N1 APARTMENT 09-FEB-20:25 417.38 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 847.74 0.00 -586.63 0.00 -1597.83 0.00
F4 N2 APARTMENT 22-DEC-08:05 447.69 0.00 0.00 0.00 73.74 43.21 388.49 0.00 0.00 0.00 227.50 0.00 -161.62 0.00 -1019.01 0.00
F4 S1 APARTMENT 09-FEB-20:25 307.49 0.00 0.00 0.00 165.00 230.46 523.87 0.00 0.00 0.00 963.90 0.00 -592.89 0.00 -1597.84 0.00
F4 S2 APARTMENT 09-FEB-20:25 309.51 0.00 0.00 0.00 165.00 230.46 523.87 0.00 0.00 0.00 961.76 0.00 -592.76 0.00 -1597.84 0.00
M SW APARTMENT 09-FEB-20:25 766.35 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 1038.44 0.00 -960.26 0.00 -1763.88 0.00
M NW APARTMENT 09-FEB-20:25 845.93 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 947.02 0.00 -948.42 0.00 -1763.87 0.00
M SE APARTMENT 09-FEB-20:25 796.11 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 1005.40 0.00 -956.98 0.00 -1763.87 0.00
M NE APARTMENT 09-FEB-20:25 877.84 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 911.51 0.00 -944.82 0.00 -1763.87 0.00
M N1 APARTMENT 09-FEB-20:25 500.45 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 864.92 0.00 -588.75 0.00 -1695.96 0.00
M N2 APARTMENT 09-FEB-20:25 503.11 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 862.09 0.00 -588.58 0.00 -1695.96 0.00
M S1 APARTMENT 09-FEB-20:25 404.80 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 965.75 0.00 -593.94 0.00 -1695.96 0.00
M S2 APARTMENT 09-FEB-20:25 407.19 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 963.23 0.00 -593.80 0.00 -1695.96 0.00
F6 SW APARTMENT 09-FEB-20:25 930.55 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 961.56 0.00 -955.10 0.00 -1856.36 0.00
F6 NW APARTMENT 09-FEB-20:25 1004.36 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 876.59 0.00 -943.94 0.00 -1856.36 0.00
F6 SE APARTMENT 09-FEB-20:25 959.34 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 929.58 0.00 -951.90 0.00 -1856.36 0.00
F6 NE APARTMENT 09-FEB-20:25 1035.76 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 841.57 0.00 -940.31 0.00 -1856.36 0.00
F6 N1 APARTMENT 24-JAN-10:45 664.37 0.00 0.00 0.00 44.36 28.81 406.15 50.87 0.00 0.00 35.63 0.00 0.00 0.00 -1230.18 0.00
F6 N2 APARTMENT 09-FEB-20:25 659.53 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 790.52 0.00 -585.83 0.00 -1783.56 0.00
F6 S1 APARTMENT 09-FEB-20:25 568.79 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 886.15 0.00 -590.74 0.00 -1783.56 0.00
F6 S2 APARTMENT 09-FEB-20:25 571.06 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 883.75 0.00 -590.60 0.00 -1783.56 0.00
F7 SW APARTMENT 09-FEB-20:25 1063.45 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 910.20 0.00 -952.36 0.00 -1940.64 0.00
F7 NW APARTMENT 09-FEB-20:25 1133.52 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 829.23 0.00 -941.45 0.00 -1940.64 0.00
F7 SE APARTMENT 09-FEB-20:20 1091.05 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 879.51 0.00 -949.27 0.00 -1940.64 0.00
F7 NE APARTMENT 09-FEB-20:20 1162.77 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 796.58 0.00 -938.05 0.00 -1940.64 0.00
F7 N1 APARTMENT 24-JAN-10:45 929.36 0.00 0.00 0.00 44.61 28.81 406.15 48.34 0.00 0.00 0.00 0.00 0.00 0.00 -1259.64 -197.64
F7 N2 APARTMENT 24-JAN-10:45 917.54 0.00 0.00 0.00 44.59 28.81 406.15 47.80 0.00 0.00 0.00 0.00 0.00 0.00 -1260.13 -184.74
F7 S1 APARTMENT 09-FEB-20:25 699.85 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 833.36 0.00 -589.10 0.00 -1863.45 0.00
F7 S2 APARTMENT 09-FEB-20:25 701.99 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 831.09 0.00 -588.97 0.00 -1863.45 0.00
F8 SW APARTMENT 09-FEB-20:20 1183.17 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 866.37 0.00 -950.26 0.00 -2018.62 0.00
F8 NW APARTMENT 09-FEB-20:20 1248.70 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 790.28 0.00 -939.70 0.00 -2018.62 0.00
F8 SE APARTMENT 09-FEB-20:20 1207.45 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 839.35 0.00 -947.52 0.00 -2018.62 0.00
F8 NE APARTMENT 09-FEB-20:20 1274.60 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 761.32 0.00 -936.64 0.00 -2018.62 0.00
F8 N1 APARTMENT 24-JAN-10:45 1063.83 0.00 0.00 0.00 44.86 28.81 406.15 46.83 0.00 0.00 0.00 0.00 0.00 0.00 -1290.53 -299.95
F8 N2 APARTMENT 24-JAN-10:45 1068.44 0.00 0.00 0.00 44.84 28.81 406.15 46.20 0.00 0.00 0.00 0.00 0.00 0.00 -1290.59 -303.85
F8 S1 APARTMENT 09-FEB-20:20 818.14 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 787.78 0.00 -587.83 0.00 -1937.44 0.00
F8 S2 APARTMENT 09-FEB-20:20 820.02 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 785.79 0.00 -587.71 0.00 -1937.44 0.00
F9 SW APARTMENT 09-FEB-20:15 1244.05 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 808.26 0.00 -933.05 0.00 -2038.60 0.00
F9 NW APARTMENT 09-FEB-20:15 1300.76 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 741.71 0.00 -923.22 0.00 -2038.60 0.00
F9 SE APARTMENT 09-FEB-20:15 1263.24 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 786.86 0.00 -930.85 0.00 -2038.60 0.00
F9 NE APARTMENT 09-FEB-20:15 1322.93 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 716.88 0.00 -920.55 0.00 -2038.60 0.00
F9 N1 APARTMENT 22-DEC-08:00 1062.37 0.00 0.00 0.00 152.95 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -242.91 0.00 -1260.07 -188.57
F9 N2 APARTMENT 22-DEC-08:00 1053.45 0.00 0.00 0.00 153.11 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -242.05 0.00 -1259.91 -180.83
F9 S1 APARTMENT 09-FEB-20:15 887.19 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 725.73 0.00 -577.02 0.00 -1955.25 0.00
F9 S2 APARTMENT 09-FEB-20:15 888.71 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 724.12 0.00 -576.92 0.00 -1955.25 0.00
T SW APARTMENT 09-FEB-20:15 1697.27 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 375.64 0.00 -885.44 0.00 -2106.81 0.00
T NW APARTMENT 09-FEB-20:15 1717.83 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 344.41 0.00 -874.78 0.00 -2106.81 0.00
T SE APARTMENT 09-FEB-20:15 1704.74 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 366.79 0.00 -884.07 0.00 -2106.81 0.00
T NE APARTMENT 09-FEB-20:15 1727.47 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 333.18 0.00 -873.19 0.00 -2106.81 0.00
T N1 APARTMENT 09-FEB-20:15 1399.46 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 243.36 0.00 -542.11 0.00 -2020.05 0.00
T N2 APARTMENT 09-FEB-20:15 1400.31 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 242.43 0.00 -542.03 0.00 -2020.05 0.00
T S1 APARTMENT 09-FEB-20:15 1370.09 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 284.99 0.00 -554.37 0.00 -2020.05 0.00
T S2 APARTMENT 09-FEB-20:15 1370.82 0.00 0.00 0.00 165.01 230.46 523.87 0.00 0.00 0.00 284.19 0.00 -554.30 0.00 -2020.05 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-FEB-20:15 58970.59 0.00 0.00 0.00 13030.82 25049.15 41923.99 0.00 0.00 0.00 57155.12 0.00 -61415.63 0.00 -134714.04 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Sec1.1A-General Information

Data
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 5.50
Number of hours cooling loads not met 456.50
Number of hours not met 462.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 22204.40 0.00 0.00 0.00 0.00
Exterior Lighting 168.54 0.00 0.00 0.00 0.00 0.00
Space Heating 1.78 0.00 0.00 0.00 0.00 0.00
Space Cooling 1315.56 97251.28 0.00 0.00 0.00 0.00
Pumps 63.70 2063.51 0.00 0.00 0.00 0.00
Heat Rejection 64.63 3835.78 0.00 0.00 0.00 0.00
Fans-Interior 807.36 25601.20 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 816.51 79739.68 0.00 0.00
Receptacle Equipment 1131.09 56867.52 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3989.90   816.51   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3989.90
Natural Gas 0.00 816.51
Additional 0.00 0.00
Total 1131.09 4806.42


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 0.23
Space Cooling 167.88
Fans-Interior 103.03
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 40.54
Subtotal 509.14


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 104.19
Miscellaneous 0.00
Subtotal 104.19


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 8.66
Space Heating 0.04
Space Cooling 27.37
Fans-Interior 16.80
Service Water Heating 16.99
Receptacle Equipment 23.53
Miscellaneous 6.61



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.298914
G NW APARTMENT DIRECT AIR 0.302933
OFFICE DIRECT AIR 0.359543
G NE APARTMENT DIRECT AIR 0.254081
G N1 APARTMENT DIRECT AIR 0.178058
G N2 APARTMENT DIRECT AIR 0.177210
G S1 APARTMENT DIRECT AIR 0.170675
G S2 APARTMENT DIRECT AIR 0.174820
F2 SW APARTMENT DIRECT AIR 0.360550
F2 NW APARTMENT DIRECT AIR 0.364920
F2 SE APARTMENT DIRECT AIR 0.329128
F2 NE APARTMENT DIRECT AIR 0.309531
F2 N1 APARTMENT DIRECT AIR 0.219831
F2 N2 APARTMENT DIRECT AIR 0.219149
F2 S1 APARTMENT DIRECT AIR 0.211660
F2 S2 APARTMENT DIRECT AIR 0.212733
F3 SW APARTMENT DIRECT AIR 0.360872
F3 NW APARTMENT DIRECT AIR 0.365515
F3 SE APARTMENT DIRECT AIR 0.316108
F3 NE APARTMENT DIRECT AIR 0.311875
F3 N1 APARTMENT DIRECT AIR 0.221509
F3 N2 APARTMENT DIRECT AIR 0.220835
F3 S1 APARTMENT DIRECT AIR 0.213566
F3 S2 APARTMENT DIRECT AIR 0.213873
F4 SW APARTMENT DIRECT AIR 0.362762
F4 NW APARTMENT DIRECT AIR 0.367352
F4 SE APARTMENT DIRECT AIR 0.317144
F4 NE APARTMENT DIRECT AIR 0.313944
F4 N1 APARTMENT DIRECT AIR 0.223492
F4 N2 APARTMENT DIRECT AIR 0.222825
F4 S1 APARTMENT DIRECT AIR 0.215597
F4 S2 APARTMENT DIRECT AIR 0.215783
M SW APARTMENT DIRECT AIR 0.366862
M NW APARTMENT DIRECT AIR 0.371484
M SE APARTMENT DIRECT AIR 0.321633
M NE APARTMENT DIRECT AIR 0.318230
M N1 APARTMENT DIRECT AIR 0.227649
M N2 APARTMENT DIRECT AIR 0.226987
M S1 APARTMENT DIRECT AIR 0.219701
M S2 APARTMENT DIRECT AIR 0.219861
F6 SW APARTMENT DIRECT AIR 0.364526
F6 NW APARTMENT DIRECT AIR 0.369000
F6 SE APARTMENT DIRECT AIR 0.319805
F6 NE APARTMENT DIRECT AIR 0.315950
F6 N1 APARTMENT DIRECT AIR 0.225339
F6 N2 APARTMENT DIRECT AIR 0.224684
F6 S1 APARTMENT DIRECT AIR 0.217513
F6 S2 APARTMENT DIRECT AIR 0.217663
F7 SW APARTMENT DIRECT AIR 0.364429
F7 NW APARTMENT DIRECT AIR 0.368875
F7 SE APARTMENT DIRECT AIR 0.320140
F7 NE APARTMENT DIRECT AIR 0.315985
F7 N1 APARTMENT DIRECT AIR 0.225304
F7 N2 APARTMENT DIRECT AIR 0.224655
F7 S1 APARTMENT DIRECT AIR 0.217494
F7 S2 APARTMENT DIRECT AIR 0.217637
F8 SW APARTMENT DIRECT AIR 0.365794
F8 NW APARTMENT DIRECT AIR 0.370192
F8 SE APARTMENT DIRECT AIR 0.321843
F8 NE APARTMENT DIRECT AIR 0.317384
F8 N1 APARTMENT DIRECT AIR 0.226705
F8 N2 APARTMENT DIRECT AIR 0.226061
F8 S1 APARTMENT DIRECT AIR 0.218881
F8 S2 APARTMENT DIRECT AIR 0.219023
F9 SW APARTMENT DIRECT AIR 0.377391
F9 NW APARTMENT DIRECT AIR 0.381897
F9 SE APARTMENT DIRECT AIR 0.332454
F9 NE APARTMENT DIRECT AIR 0.329188
F9 N1 APARTMENT DIRECT AIR 0.237398
F9 N2 APARTMENT DIRECT AIR 0.236757
F9 S1 APARTMENT DIRECT AIR 0.228271
F9 S2 APARTMENT DIRECT AIR 0.228145
T SW APARTMENT DIRECT AIR 0.445446
T NW APARTMENT DIRECT AIR 0.447036
T SE APARTMENT DIRECT AIR 0.397278
T NE APARTMENT DIRECT AIR 0.388837
T N1 APARTMENT DIRECT AIR 0.290406
T N2 APARTMENT DIRECT AIR 0.289194
T S1 APARTMENT DIRECT AIR 0.296066
T S2 APARTMENT DIRECT AIR 0.296169


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.298914
AIRLOOP G NW MAIN BRANCH 0.302933
AIRLOOP OFFICE MAIN BRANCH 0.359543
AIRLOOP G NE MAIN BRANCH 0.254081
AIRLOOP G N1 MAIN BRANCH 0.178058
AIRLOOP G N2 MAIN BRANCH 0.177210
AIRLOOP G S1 MAIN BRANCH 0.170675
AIRLOOP G S2 MAIN BRANCH 0.174820
AIRLOOP F2 SW MAIN BRANCH 0.360550
AIRLOOP F2 NW MAIN BRANCH 0.364920
AIRLOOP F2 SE MAIN BRANCH 0.329128
AIRLOOP F2 NE MAIN BRANCH 0.309531
AIRLOOP F2 N1 MAIN BRANCH 0.219831
AIRLOOP F2 N2 MAIN BRANCH 0.219149
AIRLOOP F2 S1 MAIN BRANCH 0.211660
AIRLOOP F2 S2 MAIN BRANCH 0.212733
AIRLOOP F3 SW MAIN BRANCH 0.360872
AIRLOOP F3 NW MAIN BRANCH 0.365515
AIRLOOP F3 SE MAIN BRANCH 0.316108
AIRLOOP F3 NE MAIN BRANCH 0.311875
AIRLOOP F3 N1 MAIN BRANCH 0.221509
AIRLOOP F3 N2 MAIN BRANCH 0.220835
AIRLOOP F3 S1 MAIN BRANCH 0.213566
AIRLOOP F3 S2 MAIN BRANCH 0.213873
AIRLOOP F4 SW MAIN BRANCH 0.362762
AIRLOOP F4 NW MAIN BRANCH 0.367352
AIRLOOP F4 SE MAIN BRANCH 0.317144
AIRLOOP F4 NE MAIN BRANCH 0.313944
AIRLOOP F4 N1 MAIN BRANCH 0.223492
AIRLOOP F4 N2 MAIN BRANCH 0.222825
AIRLOOP F4 S1 MAIN BRANCH 0.215597
AIRLOOP F4 S2 MAIN BRANCH 0.215783
AIRLOOP M SW MAIN BRANCH 0.366862
AIRLOOP M NW MAIN BRANCH 0.371484
AIRLOOP M SE MAIN BRANCH 0.321633
AIRLOOP M NE MAIN BRANCH 0.318230
AIRLOOP M N1 MAIN BRANCH 0.227649
AIRLOOP M N2 MAIN BRANCH 0.226987
AIRLOOP M S1 MAIN BRANCH 0.219701
AIRLOOP M S2 MAIN BRANCH 0.219861
AIRLOOP F6 SW MAIN BRANCH 0.364526
AIRLOOP F6 NW MAIN BRANCH 0.369000
AIRLOOP F6 SE MAIN BRANCH 0.319805
AIRLOOP F6 NE MAIN BRANCH 0.315950
AIRLOOP F6 N1 MAIN BRANCH 0.225339
AIRLOOP F6 N2 MAIN BRANCH 0.224684
AIRLOOP F6 S1 MAIN BRANCH 0.217513
AIRLOOP F6 S2 MAIN BRANCH 0.217663
AIRLOOP F7 SW MAIN BRANCH 0.364429
AIRLOOP F7 NW MAIN BRANCH 0.368875
AIRLOOP F7 SE MAIN BRANCH 0.320140
AIRLOOP F7 NE MAIN BRANCH 0.315985
AIRLOOP F7 N1 MAIN BRANCH 0.225304
AIRLOOP F7 N2 MAIN BRANCH 0.224655
AIRLOOP F7 S1 MAIN BRANCH 0.217494
AIRLOOP F7 S2 MAIN BRANCH 0.217637
AIRLOOP F8 SW MAIN BRANCH 0.365794
AIRLOOP F8 NW MAIN BRANCH 0.370192
AIRLOOP F8 SE MAIN BRANCH 0.321843
AIRLOOP F8 NE MAIN BRANCH 0.317384
AIRLOOP F8 N1 MAIN BRANCH 0.226705
AIRLOOP F8 N2 MAIN BRANCH 0.226061
AIRLOOP F8 S1 MAIN BRANCH 0.218881
AIRLOOP F8 S2 MAIN BRANCH 0.219023
AIRLOOP F9 SW MAIN BRANCH 0.377391
AIRLOOP F9 NW MAIN BRANCH 0.381897
AIRLOOP F9 SE MAIN BRANCH 0.332454
AIRLOOP F9 NE MAIN BRANCH 0.329188
AIRLOOP F9 N1 MAIN BRANCH 0.237398
AIRLOOP F9 N2 MAIN BRANCH 0.236757
AIRLOOP F9 S1 MAIN BRANCH 0.228271
AIRLOOP F9 S2 MAIN BRANCH 0.228145
AIRLOOP T SW MAIN BRANCH 0.445446
AIRLOOP T NW MAIN BRANCH 0.447036
AIRLOOP T SE MAIN BRANCH 0.397278
AIRLOOP T NE MAIN BRANCH 0.388837
AIRLOOP T N1 MAIN BRANCH 0.290406
AIRLOOP T N2 MAIN BRANCH 0.289194
AIRLOOP T S1 MAIN BRANCH 0.296066
AIRLOOP T S2 MAIN BRANCH 0.296169


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.298914
AIRLOOP G NW 0.302933
AIRLOOP OFFICE 0.359543
AIRLOOP G NE 0.254081
AIRLOOP G N1 0.178058
AIRLOOP G N2 0.177210
AIRLOOP G S1 0.170675
AIRLOOP G S2 0.174820
AIRLOOP F2 SW 0.360550
AIRLOOP F2 NW 0.364920
AIRLOOP F2 SE 0.329128
AIRLOOP F2 NE 0.309531
AIRLOOP F2 N1 0.219831
AIRLOOP F2 N2 0.219149
AIRLOOP F2 S1 0.211660
AIRLOOP F2 S2 0.212733
AIRLOOP F3 SW 0.360872
AIRLOOP F3 NW 0.365515
AIRLOOP F3 SE 0.316108
AIRLOOP F3 NE 0.311875
AIRLOOP F3 N1 0.221509
AIRLOOP F3 N2 0.220835
AIRLOOP F3 S1 0.213566
AIRLOOP F3 S2 0.213873
AIRLOOP F4 SW 0.362762
AIRLOOP F4 NW 0.367352
AIRLOOP F4 SE 0.317144
AIRLOOP F4 NE 0.313944
AIRLOOP F4 N1 0.223492
AIRLOOP F4 N2 0.222825
AIRLOOP F4 S1 0.215597
AIRLOOP F4 S2 0.215783
AIRLOOP M SW 0.366862
AIRLOOP M NW 0.371484
AIRLOOP M SE 0.321633
AIRLOOP M NE 0.318230
AIRLOOP M N1 0.227649
AIRLOOP M N2 0.226987
AIRLOOP M S1 0.219701
AIRLOOP M S2 0.219861
AIRLOOP F6 SW 0.364526
AIRLOOP F6 NW 0.369000
AIRLOOP F6 SE 0.319805
AIRLOOP F6 NE 0.315950
AIRLOOP F6 N1 0.225339
AIRLOOP F6 N2 0.224684
AIRLOOP F6 S1 0.217513
AIRLOOP F6 S2 0.217663
AIRLOOP F7 SW 0.364429
AIRLOOP F7 NW 0.368875
AIRLOOP F7 SE 0.320140
AIRLOOP F7 NE 0.315985
AIRLOOP F7 N1 0.225304
AIRLOOP F7 N2 0.224655
AIRLOOP F7 S1 0.217494
AIRLOOP F7 S2 0.217637
AIRLOOP F8 SW 0.365794
AIRLOOP F8 NW 0.370192
AIRLOOP F8 SE 0.321843
AIRLOOP F8 NE 0.317384
AIRLOOP F8 N1 0.226705
AIRLOOP F8 N2 0.226061
AIRLOOP F8 S1 0.218881
AIRLOOP F8 S2 0.219023
AIRLOOP F9 SW 0.377391
AIRLOOP F9 NW 0.381897
AIRLOOP F9 SE 0.332454
AIRLOOP F9 NE 0.329188
AIRLOOP F9 N1 0.237398
AIRLOOP F9 N2 0.236757
AIRLOOP F9 S1 0.228271
AIRLOOP F9 S2 0.228145
AIRLOOP T SW 0.445446
AIRLOOP T NW 0.447036
AIRLOOP T SE 0.397278
AIRLOOP T NE 0.388837
AIRLOOP T N1 0.290406
AIRLOOP T N2 0.289194
AIRLOOP T S1 0.296066
AIRLOOP T S2 0.296169


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.298914 0.025952
AIRLOOP G NW OA CONTROLLER 0.302933 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.359543 0.038103
AIRLOOP G NE OA CONTROLLER 0.254081 0.025952
AIRLOOP G N1 OA CONTROLLER 0.178058 0.025952
AIRLOOP G N2 OA CONTROLLER 0.177210 0.025952
AIRLOOP G S1 OA CONTROLLER 0.170675 0.025952
AIRLOOP G S2 OA CONTROLLER 0.174820 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.360550 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.364920 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.329128 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.309531 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.219831 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.219149 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.211660 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.212733 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.360872 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.365515 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.316108 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.311875 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.221509 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.220835 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.213566 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.213873 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.362762 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.367352 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.317144 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.313944 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.223492 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.222825 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.215597 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.215783 0.025952
AIRLOOP M SW OA CONTROLLER 0.366862 0.025952
AIRLOOP M NW OA CONTROLLER 0.371484 0.025952
AIRLOOP M SE OA CONTROLLER 0.321633 0.025952
AIRLOOP M NE OA CONTROLLER 0.318230 0.025952
AIRLOOP M N1 OA CONTROLLER 0.227649 0.025952
AIRLOOP M N2 OA CONTROLLER 0.226987 0.025952
AIRLOOP M S1 OA CONTROLLER 0.219701 0.025952
AIRLOOP M S2 OA CONTROLLER 0.219861 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.364526 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.369000 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.319805 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.315950 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.225339 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.224684 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.217513 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.217663 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.364429 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.368875 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.320140 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.315985 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.225304 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.224655 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.217494 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.217637 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.365794 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.370192 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.321843 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.317384 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.226705 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.226061 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.218881 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.219023 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.377391 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.381897 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.332454 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.329188 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.237398 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.236757 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.228271 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.228145 0.025952
AIRLOOP T SW OA CONTROLLER 0.445446 0.025952
AIRLOOP T NW OA CONTROLLER 0.447036 0.025952
AIRLOOP T SE OA CONTROLLER 0.397278 0.025952
AIRLOOP T NE OA CONTROLLER 0.388837 0.025952
AIRLOOP T N1 OA CONTROLLER 0.290406 0.025952
AIRLOOP T N2 OA CONTROLLER 0.289194 0.025952
AIRLOOP T S1 OA CONTROLLER 0.296066 0.025952
AIRLOOP T S2 OA CONTROLLER 0.296169 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.298914 4719.02 3392.18 0.000103
HEAT PUMP COOLING MODE AIRLOOP G NW 0.302933 4766.05 3430.38 0.000104
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.359543 5756.58 4116.18 0.000126
HEAT PUMP COOLING MODE AIRLOOP G NE 0.254081 4065.21 2903.98 0.000089
HEAT PUMP COOLING MODE AIRLOOP G N1 0.178058 3008.39 2096.68 0.000066
HEAT PUMP COOLING MODE AIRLOOP G N2 0.177210 2996.57 2087.67 0.000065
HEAT PUMP COOLING MODE AIRLOOP G S1 0.170675 2956.72 2040.86 0.000065
HEAT PUMP COOLING MODE AIRLOOP G S2 0.174820 3014.41 2085.06 0.000066
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.360550 5577.89 4043.95 0.000122
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.364920 5629.91 4085.75 0.000123
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.329128 5165.73 3722.46 0.000113
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.309531 4839.07 3490.98 0.000106
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.219831 3602.50 2545.53 0.000079
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.219149 3593.03 2538.31 0.000078
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.211660 3530.44 2477.96 0.000077
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.212733 3545.32 2489.35 0.000077
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.360872 5586.89 4048.51 0.000122
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.365515 5642.66 4093.18 0.000123
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.316108 4947.97 3567.53 0.000108
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.311875 4875.91 3516.84 0.000107
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.221509 3628.33 2563.97 0.000079
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.220835 3618.95 2556.83 0.000079
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.213566 3559.38 2498.84 0.000078
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.213873 3563.69 2502.11 0.000078
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.362762 5616.41 4069.31 0.000123
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.367352 5671.45 4113.41 0.000124
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.317144 5007.86 3598.04 0.000109
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.313944 4907.85 3539.52 0.000107
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.223492 3657.77 2585.47 0.000080
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.222825 3648.49 2578.40 0.000080
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.215597 3589.46 2520.89 0.000078
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.215783 3592.09 2522.88 0.000078
HEAT PUMP COOLING MODE AIRLOOP M SW 0.366862 5675.84 4113.23 0.000124
HEAT PUMP COOLING MODE AIRLOOP M NW 0.371484 5731.32 4157.66 0.000125
HEAT PUMP COOLING MODE AIRLOOP M SE 0.321633 5072.66 3646.12 0.000111
HEAT PUMP COOLING MODE AIRLOOP M NE 0.318230 4969.83 3585.41 0.000109
HEAT PUMP COOLING MODE AIRLOOP M N1 0.227649 3717.07 2629.91 0.000081
HEAT PUMP COOLING MODE AIRLOOP M N2 0.226987 3707.87 2622.90 0.000081
HEAT PUMP COOLING MODE AIRLOOP M S1 0.219701 3647.96 2564.83 0.000080
HEAT PUMP COOLING MODE AIRLOOP M S2 0.219861 3650.23 2566.55 0.000080
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.364526 5645.98 4089.24 0.000123
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.369000 5699.41 4132.12 0.000125
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.319805 5049.70 3627.44 0.000110
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.315950 4940.68 3561.99 0.000108
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.225339 3686.31 2605.79 0.000081
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.224684 3677.21 2598.86 0.000080
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.217513 3618.92 2541.98 0.000079
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.217663 3621.06 2543.58 0.000079
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.364429 5646.75 4088.76 0.000123
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.368875 5699.79 4131.34 0.000125
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.320140 5056.38 3631.50 0.000110
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.315985 4943.22 3562.89 0.000108
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.225304 3687.01 2605.74 0.000081
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.224655 3677.99 2598.86 0.000080
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.217494 3619.83 2542.08 0.000079
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.217637 3621.79 2543.59 0.000079
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.365794 5667.50 4103.63 0.000124
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.370192 5719.88 4145.70 0.000125
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.321843 5081.77 3649.95 0.000111
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.317384 4964.42 3578.12 0.000108
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.226705 3703.31 2618.61 0.000081
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.226061 3694.36 2611.79 0.000081
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.218881 3640.12 2557.07 0.000080
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.219023 3642.09 2558.58 0.000080
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.377391 5829.44 4226.26 0.000127
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.381897 5883.32 4269.44 0.000129
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.332454 5230.18 3762.33 0.000114
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.329188 5159.08 3716.10 0.000113
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.237398 3852.86 2732.07 0.000084
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.236757 3843.95 2725.29 0.000084
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.228271 3763.32 2653.47 0.000082
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.228145 3769.68 2655.57 0.000082
HEAT PUMP COOLING MODE AIRLOOP T SW 0.445446 6779.94 4947.51 0.000148
HEAT PUMP COOLING MODE AIRLOOP T NW 0.447036 6792.44 4959.90 0.000148
HEAT PUMP COOLING MODE AIRLOOP T SE 0.397278 6127.47 4446.00 0.000134
HEAT PUMP COOLING MODE AIRLOOP T NE 0.388837 6010.91 4357.09 0.000131
HEAT PUMP COOLING MODE AIRLOOP T N1 0.290406 4607.03 3302.86 0.000101
HEAT PUMP COOLING MODE AIRLOOP T N2 0.289194 4608.09 3298.09 0.000101
HEAT PUMP COOLING MODE AIRLOOP T S1 0.296066 4711.36 3374.25 0.000103
HEAT PUMP COOLING MODE AIRLOOP T S2 0.296169 4712.76 3375.33 0.000103


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.298914 0.298914 0.298914 0.298914 4719.02 4719.02 1660.45 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.302933 0.302933 0.302933 0.302933 4766.05 4766.05 1660.53 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.359543 0.359543 0.359543 0.359543 5756.58 5756.58 2265.94 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.254081 0.254081 0.254081 0.254081 4065.21 4065.21 1662.50 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.178058 0.178058 0.178058 0.178058 3008.39 3008.39 1152.10 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.177210 0.177210 0.177210 0.177210 2996.57 2996.57 1152.15 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.170675 0.170675 0.170675 0.170675 2956.72 2956.72 1149.05 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.174820 0.174820 0.174820 0.174820 3014.41 3014.41 1156.00 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.360550 0.360550 0.360550 0.360550 5577.89 5577.89 1671.84 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.364920 0.364920 0.364920 0.364920 5629.91 5629.91 1671.14 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.329128 0.329128 0.329128 0.329128 5165.73 5165.73 1699.62 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.309531 0.309531 0.309531 0.309531 4839.07 4839.07 1674.21 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.219831 0.219831 0.219831 0.219831 3602.50 3602.50 1061.92 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.219149 0.219149 0.219149 0.219149 3593.03 3593.03 1062.00 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.211660 0.211660 0.211660 0.211660 3530.44 3530.44 1064.25 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.212733 0.212733 0.212733 0.212733 3545.32 3545.32 1066.02 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.360872 0.360872 0.360872 0.360872 5586.89 5586.89 1622.43 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.365515 0.365515 0.365515 0.365515 5642.66 5642.66 1622.42 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.316108 0.316108 0.316108 0.316108 4947.97 4947.97 1628.79 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.311875 0.311875 0.311875 0.311875 4875.91 4875.91 1625.98 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.221509 0.221509 0.221509 0.221509 3628.33 3628.33 1031.58 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.220835 0.220835 0.220835 0.220835 3618.95 3618.95 1031.58 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.213566 0.213566 0.213566 0.213566 3559.38 3559.38 1031.58 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.213873 0.213873 0.213873 0.213873 3563.69 3563.69 1031.58 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.362762 0.362762 0.362762 0.362762 5616.41 5616.41 1608.81 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.367352 0.367352 0.367352 0.367352 5671.45 5671.45 1609.21 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.317144 0.317144 0.317144 0.317144 5007.86 5007.86 1613.03 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.313944 0.313944 0.313944 0.313944 4907.85 4907.85 1613.12 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.223492 0.223492 0.223492 0.223492 3657.77 3657.77 1031.58 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.222825 0.222825 0.222825 0.222825 3648.49 3648.49 1031.58 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.215597 0.215597 0.215597 0.215597 3589.46 3589.46 1031.58 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.215783 0.215783 0.215783 0.215783 3592.09 3592.09 1031.58 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.366862 0.366862 0.366862 0.366862 5675.84 5675.84 1578.81 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.371484 0.371484 0.371484 0.371484 5731.32 5731.32 1578.18 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.321633 0.321633 0.321633 0.321633 5072.66 5072.66 1583.02 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.318230 0.318230 0.318230 0.318230 4969.83 4969.83 1582.34 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.227649 0.227649 0.227649 0.227649 3717.07 3717.07 1031.58 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.226987 0.226987 0.226987 0.226987 3707.87 3707.87 1031.58 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.219701 0.219701 0.219701 0.219701 3647.96 3647.96 1031.58 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.219861 0.219861 0.219861 0.219861 3650.23 3650.23 1031.58 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.364526 0.364526 0.364526 0.364526 5645.98 5645.98 1619.22 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.369000 0.369000 0.369000 0.369000 5699.41 5699.41 1619.59 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.319805 0.319805 0.319805 0.319805 5049.70 5049.70 1623.63 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.315950 0.315950 0.315950 0.315950 4940.68 4940.68 1623.98 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.225339 0.225339 0.225339 0.225339 3686.31 3686.31 1031.58 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.224684 0.224684 0.224684 0.224684 3677.21 3677.21 1031.58 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.217513 0.217513 0.217513 0.217513 3618.92 3618.92 1031.58 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.217663 0.217663 0.217663 0.217663 3621.06 3621.06 1031.58 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.364429 0.364429 0.364429 0.364429 5646.75 5646.75 1636.36 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.368875 0.368875 0.368875 0.368875 5699.79 5699.79 1636.50 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.320140 0.320140 0.320140 0.320140 5056.38 5056.38 1640.94 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.315985 0.315985 0.315985 0.315985 4943.22 4943.22 1641.07 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.225304 0.225304 0.225304 0.225304 3687.01 3687.01 1031.58 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.224655 0.224655 0.224655 0.224655 3677.99 3677.99 1031.58 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.217494 0.217494 0.217494 0.217494 3619.83 3619.83 1031.58 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.217637 0.217637 0.217637 0.217637 3621.79 3621.79 1031.58 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.365794 0.365794 0.365794 0.365794 5667.50 5667.50 1656.48 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.370192 0.370192 0.370192 0.370192 5719.88 5719.88 1656.16 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.321843 0.321843 0.321843 0.321843 5081.77 5081.77 1661.21 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.317384 0.317384 0.317384 0.317384 4964.42 4964.42 1660.88 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.226705 0.226705 0.226705 0.226705 3703.31 3703.31 1035.07 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.226061 0.226061 0.226061 0.226061 3694.36 3694.36 1035.19 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.218881 0.218881 0.218881 0.218881 3640.12 3640.12 1034.58 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.219023 0.219023 0.219023 0.219023 3642.09 3642.09 1034.70 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.377391 0.377391 0.377391 0.377391 5829.44 5829.44 1764.40 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.381897 0.381897 0.381897 0.381897 5883.32 5883.32 1761.39 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.332454 0.332454 0.332454 0.332454 5230.18 5230.18 1769.31 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.329188 0.329188 0.329188 0.329188 5159.08 5159.08 1766.28 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.237398 0.237398 0.237398 0.237398 3852.86 3852.86 1132.72 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.236757 0.236757 0.236757 0.236757 3843.95 3843.95 1132.84 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.228271 0.228271 0.228271 0.228271 3763.32 3763.32 1134.63 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.228145 0.228145 0.228145 0.228145 3769.68 3769.68 1134.75 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.445446 0.445446 0.445446 0.445446 6779.94 6779.94 2122.87 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.447036 0.447036 0.447036 0.447036 6792.44 6792.44 2125.36 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.397278 0.397278 0.397278 0.397278 6127.47 6127.47 2127.45 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.388837 0.388837 0.388837 0.388837 6010.91 6010.91 2129.93 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.290406 0.290406 0.290406 0.290406 4607.03 4607.03 1549.45 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.289194 0.289194 0.289194 0.289194 4608.09 4608.09 1549.58 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.296066 0.296066 0.296066 0.296066 4711.36 4711.36 1544.14 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.296169 0.296169 0.296169 0.296169 4712.76 4712.76 1544.27 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.298914
AIRLOOP G NW SUPPLY FAN 0.302933
AIRLOOP OFFICE SUPPLY FAN 0.359543
AIRLOOP G NE SUPPLY FAN 0.254081
AIRLOOP G N1 SUPPLY FAN 0.178058
AIRLOOP G N2 SUPPLY FAN 0.177210
AIRLOOP G S1 SUPPLY FAN 0.170675
AIRLOOP G S2 SUPPLY FAN 0.174820
AIRLOOP F2 SW SUPPLY FAN 0.360550
AIRLOOP F2 NW SUPPLY FAN 0.364920
AIRLOOP F2 SE SUPPLY FAN 0.329128
AIRLOOP F2 NE SUPPLY FAN 0.309531
AIRLOOP F2 N1 SUPPLY FAN 0.219831
AIRLOOP F2 N2 SUPPLY FAN 0.219149
AIRLOOP F2 S1 SUPPLY FAN 0.211660
AIRLOOP F2 S2 SUPPLY FAN 0.212733
AIRLOOP F3 SW SUPPLY FAN 0.360872
AIRLOOP F3 NW SUPPLY FAN 0.365515
AIRLOOP F3 SE SUPPLY FAN 0.316108
AIRLOOP F3 NE SUPPLY FAN 0.311875
AIRLOOP F3 N1 SUPPLY FAN 0.221509
AIRLOOP F3 N2 SUPPLY FAN 0.220835
AIRLOOP F3 S1 SUPPLY FAN 0.213566
AIRLOOP F3 S2 SUPPLY FAN 0.213873
AIRLOOP F4 SW SUPPLY FAN 0.362762
AIRLOOP F4 NW SUPPLY FAN 0.367352
AIRLOOP F4 SE SUPPLY FAN 0.317144
AIRLOOP F4 NE SUPPLY FAN 0.313944
AIRLOOP F4 N1 SUPPLY FAN 0.223492
AIRLOOP F4 N2 SUPPLY FAN 0.222825
AIRLOOP F4 S1 SUPPLY FAN 0.215597
AIRLOOP F4 S2 SUPPLY FAN 0.215783
AIRLOOP M SW SUPPLY FAN 0.366862
AIRLOOP M NW SUPPLY FAN 0.371484
AIRLOOP M SE SUPPLY FAN 0.321633
AIRLOOP M NE SUPPLY FAN 0.318230
AIRLOOP M N1 SUPPLY FAN 0.227649
AIRLOOP M N2 SUPPLY FAN 0.226987
AIRLOOP M S1 SUPPLY FAN 0.219701
AIRLOOP M S2 SUPPLY FAN 0.219861
AIRLOOP F6 SW SUPPLY FAN 0.364526
AIRLOOP F6 NW SUPPLY FAN 0.369000
AIRLOOP F6 SE SUPPLY FAN 0.319805
AIRLOOP F6 NE SUPPLY FAN 0.315950
AIRLOOP F6 N1 SUPPLY FAN 0.225339
AIRLOOP F6 N2 SUPPLY FAN 0.224684
AIRLOOP F6 S1 SUPPLY FAN 0.217513
AIRLOOP F6 S2 SUPPLY FAN 0.217663
AIRLOOP F7 SW SUPPLY FAN 0.364429
AIRLOOP F7 NW SUPPLY FAN 0.368875
AIRLOOP F7 SE SUPPLY FAN 0.320140
AIRLOOP F7 NE SUPPLY FAN 0.315985
AIRLOOP F7 N1 SUPPLY FAN 0.225304
AIRLOOP F7 N2 SUPPLY FAN 0.224655
AIRLOOP F7 S1 SUPPLY FAN 0.217494
AIRLOOP F7 S2 SUPPLY FAN 0.217637
AIRLOOP F8 SW SUPPLY FAN 0.365794
AIRLOOP F8 NW SUPPLY FAN 0.370192
AIRLOOP F8 SE SUPPLY FAN 0.321843
AIRLOOP F8 NE SUPPLY FAN 0.317384
AIRLOOP F8 N1 SUPPLY FAN 0.226705
AIRLOOP F8 N2 SUPPLY FAN 0.226061
AIRLOOP F8 S1 SUPPLY FAN 0.218881
AIRLOOP F8 S2 SUPPLY FAN 0.219023
AIRLOOP F9 SW SUPPLY FAN 0.377391
AIRLOOP F9 NW SUPPLY FAN 0.381897
AIRLOOP F9 SE SUPPLY FAN 0.332454
AIRLOOP F9 NE SUPPLY FAN 0.329188
AIRLOOP F9 N1 SUPPLY FAN 0.237398
AIRLOOP F9 N2 SUPPLY FAN 0.236757
AIRLOOP F9 S1 SUPPLY FAN 0.228271
AIRLOOP F9 S2 SUPPLY FAN 0.228145
AIRLOOP T SW SUPPLY FAN 0.445446
AIRLOOP T NW SUPPLY FAN 0.447036
AIRLOOP T SE SUPPLY FAN 0.397278
AIRLOOP T NE SUPPLY FAN 0.388837
AIRLOOP T N1 SUPPLY FAN 0.290406
AIRLOOP T N2 SUPPLY FAN 0.289194
AIRLOOP T S1 SUPPLY FAN 0.296066
AIRLOOP T S2 SUPPLY FAN 0.296169


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.298914 4719.02 0.000103
HEAT PUMP HEATING MODE AIRLOOP G NW 0.302933 4766.05 0.000104
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.359543 5756.58 0.000126
HEAT PUMP HEATING MODE AIRLOOP G NE 0.254081 4065.21 0.000089
HEAT PUMP HEATING MODE AIRLOOP G N1 0.178058 3008.39 0.000066
HEAT PUMP HEATING MODE AIRLOOP G N2 0.177210 2996.57 0.000065
HEAT PUMP HEATING MODE AIRLOOP G S1 0.170675 2956.72 0.000065
HEAT PUMP HEATING MODE AIRLOOP G S2 0.174820 3014.41 0.000066
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.360550 5577.89 0.000122
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.364920 5629.91 0.000123
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.329128 5165.73 0.000113
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.309531 4839.07 0.000106
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.219831 3602.50 0.000079
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.219149 3593.03 0.000078
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.211660 3530.44 0.000077
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.212733 3545.32 0.000077
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.360872 5586.89 0.000122
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.365515 5642.66 0.000123
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.316108 4947.97 0.000108
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.311875 4875.91 0.000107
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.221509 3628.33 0.000079
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.220835 3618.95 0.000079
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.213566 3559.38 0.000078
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.213873 3563.69 0.000078
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.362762 5616.41 0.000123
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.367352 5671.45 0.000124
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.317144 5007.86 0.000109
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.313944 4907.85 0.000107
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.223492 3657.77 0.000080
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.222825 3648.49 0.000080
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.215597 3589.46 0.000078
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.215783 3592.09 0.000078
HEAT PUMP HEATING MODE AIRLOOP M SW 0.366862 5675.84 0.000124
HEAT PUMP HEATING MODE AIRLOOP M NW 0.371484 5731.32 0.000125
HEAT PUMP HEATING MODE AIRLOOP M SE 0.321633 5072.66 0.000111
HEAT PUMP HEATING MODE AIRLOOP M NE 0.318230 4969.83 0.000109
HEAT PUMP HEATING MODE AIRLOOP M N1 0.227649 3717.07 0.000081
HEAT PUMP HEATING MODE AIRLOOP M N2 0.226987 3707.87 0.000081
HEAT PUMP HEATING MODE AIRLOOP M S1 0.219701 3647.96 0.000080
HEAT PUMP HEATING MODE AIRLOOP M S2 0.219861 3650.23 0.000080
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.364526 5645.98 0.000123
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.369000 5699.41 0.000125
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.319805 5049.70 0.000110
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.315950 4940.68 0.000108
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.225339 3686.31 0.000081
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.224684 3677.21 0.000080
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.217513 3618.92 0.000079
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.217663 3621.06 0.000079
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.364429 5646.75 0.000123
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.368875 5699.79 0.000125
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.320140 5056.38 0.000110
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.315985 4943.22 0.000108
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.225304 3687.01 0.000081
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.224655 3677.99 0.000080
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.217494 3619.83 0.000079
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.217637 3621.79 0.000079
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.365794 5667.50 0.000124
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.370192 5719.88 0.000125
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.321843 5081.77 0.000111
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.317384 4964.42 0.000108
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.226705 3703.31 0.000081
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.226061 3694.36 0.000081
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.218881 3640.12 0.000080
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.219023 3642.09 0.000080
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.377391 5829.44 0.000127
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.381897 5883.32 0.000129
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.332454 5230.18 0.000114
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.329188 5159.08 0.000113
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.237398 3852.86 0.000084
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.236757 3843.95 0.000084
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.228271 3763.32 0.000082
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.228145 3769.68 0.000082
HEAT PUMP HEATING MODE AIRLOOP T SW 0.445446 6779.94 0.000148
HEAT PUMP HEATING MODE AIRLOOP T NW 0.447036 6792.44 0.000148
HEAT PUMP HEATING MODE AIRLOOP T SE 0.397278 6127.47 0.000134
HEAT PUMP HEATING MODE AIRLOOP T NE 0.388837 6010.91 0.000131
HEAT PUMP HEATING MODE AIRLOOP T N1 0.290406 4607.03 0.000101
HEAT PUMP HEATING MODE AIRLOOP T N2 0.289194 4608.09 0.000101
HEAT PUMP HEATING MODE AIRLOOP T S1 0.296066 4711.36 0.000103
HEAT PUMP HEATING MODE AIRLOOP T S2 0.296169 4712.76 0.000103


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 1660.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 1660.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 2265.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 1662.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 1152.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 1152.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 1149.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 1156.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 1671.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 1671.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 1699.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 1674.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1061.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1062.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1064.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1066.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 1622.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 1622.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 1628.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 1625.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 1608.81
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 1609.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 1613.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 1613.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 1578.81
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 1578.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 1583.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 1582.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 1619.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 1619.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 1623.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 1623.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 1636.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 1636.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 1640.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 1641.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1031.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 1656.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 1656.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 1661.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 1660.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 1035.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 1035.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 1034.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 1034.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 1764.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 1761.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 1769.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 1766.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 1132.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 1132.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 1134.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 1134.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 2122.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 2125.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 2127.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 2129.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 1549.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 1549.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 1544.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 1544.27


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.007946 8.94


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.007946


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.007946 3835.78 10.36 11599.72


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.007946 2026.59



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:17

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.06 13.39
February 23.56 16.97
March 24.19 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.35 25.09
November 24.04 19.63
December 23.35 14.52
     
Annual Sum or Average 24.08 24.88
Minimum of Months 23.06 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.37 13.39
February 23.20 16.97
March 24.13 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.33 25.09
November 23.80 19.63
December 22.65 14.52
     
Annual Sum or Average 23.91 24.88
Minimum of Months 22.37 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.39
February 23.68 16.97
March 24.28 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.09 19.63
December 23.32 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 23.13 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 13.39
February 23.19 16.97
March 24.12 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.33 25.09
November 23.76 19.63
December 22.56 14.52
     
Annual Sum or Average 23.89 24.88
Minimum of Months 22.28 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 13.39
February 23.07 16.97
March 24.06 22.37
April 24.39 29.13
May 24.40 32.98
June 24.43 33.60
July 24.43 31.67
August 24.41 30.03
September 24.40 28.75
October 24.32 25.09
November 23.73 19.63
December 22.49 14.52
     
Annual Sum or Average 23.86 24.88
Minimum of Months 22.19 13.39
Maximum of Months 24.43 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 13.39
February 23.07 16.97
March 24.06 22.37
April 24.39 29.13
May 24.40 32.98
June 24.43 33.60
July 24.43 31.67
August 24.41 30.03
September 24.40 28.75
October 24.32 25.09
November 23.72 19.63
December 22.48 14.52
     
Annual Sum or Average 23.86 24.88
Minimum of Months 22.19 13.39
Maximum of Months 24.43 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.11 13.39
February 23.59 16.97
March 24.17 22.37
April 24.39 29.13
May 24.40 32.98
June 24.43 33.60
July 24.45 31.67
August 24.45 30.03
September 24.47 28.75
October 24.35 25.09
November 24.06 19.63
December 23.43 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 23.11 13.39
Maximum of Months 24.47 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.39
February 23.61 16.97
March 24.17 22.37
April 24.39 29.13
May 24.40 32.98
June 24.42 33.60
July 24.44 31.67
August 24.44 30.03
September 24.46 28.75
October 24.35 25.09
November 24.07 19.63
December 23.45 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 23.13 13.39
Maximum of Months 24.46 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.57 13.39
February 22.19 16.97
March 24.48 22.37
April 26.96 29.13
May 28.21 32.98
June 28.73 33.60
July 28.12 31.67
August 27.60 30.03
September 27.22 28.75
October 25.71 25.09
November 23.57 19.63
December 21.22 14.52
     
Annual Sum or Average 25.39 24.88
Minimum of Months 20.57 13.39
Maximum of Months 28.73 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 13.39
February 24.09 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.34 19.63
December 24.02 14.52
     
Annual Sum or Average 24.28 24.88
Minimum of Months 23.78 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.87 13.39
February 23.78 16.97
March 24.31 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.22 19.63
December 23.33 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 22.87 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.79 13.39
February 24.11 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.34 19.63
December 24.02 14.52
     
Annual Sum or Average 24.28 24.88
Minimum of Months 23.79 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 13.39
February 23.76 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.21 19.63
December 23.21 14.52
     
Annual Sum or Average 24.09 24.88
Minimum of Months 22.76 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 13.39
February 23.75 16.97
March 24.30 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.20 19.63
December 23.27 14.52
     
Annual Sum or Average 24.09 24.88
Minimum of Months 22.76 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.75 13.39
February 23.75 16.97
March 24.30 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.20 19.63
December 23.26 14.52
     
Annual Sum or Average 24.09 24.88
Minimum of Months 22.75 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.91 13.39
February 24.14 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.43 31.67
August 24.43 30.03
September 24.45 28.75
October 24.42 25.09
November 24.35 19.63
December 24.13 14.52
     
Annual Sum or Average 24.32 24.88
Minimum of Months 23.91 13.39
Maximum of Months 24.45 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.92 13.39
February 24.14 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.43 30.03
September 24.45 28.75
October 24.42 25.09
November 24.35 19.63
December 24.13 14.52
     
Annual Sum or Average 24.32 24.88
Minimum of Months 23.92 13.39
Maximum of Months 24.45 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.04 13.39
February 25.02 16.97
March 26.08 22.37
April 26.88 29.13
May 27.24 32.98
June 27.33 33.60
July 27.16 31.67
August 26.98 30.03
September 26.84 28.75
October 26.49 25.09
November 25.75 19.63
December 24.54 14.52
     
Annual Sum or Average 26.20 24.88
Minimum of Months 24.04 13.39
Maximum of Months 27.33 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.93 13.39
February 24.16 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.35 19.63
December 24.13 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.93 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.06 13.39
February 23.90 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.53 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.06 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 13.39
February 24.14 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.35 19.63
December 24.09 14.52
     
Annual Sum or Average 24.30 24.88
Minimum of Months 23.88 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.94 13.39
February 23.88 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.26 19.63
December 23.42 14.52
     
Annual Sum or Average 24.14 24.88
Minimum of Months 22.94 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.02 13.39
February 23.91 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.26 19.63
December 23.54 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.02 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 13.39
February 23.91 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.26 19.63
December 23.53 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.01 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 13.39
February 24.21 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.43 30.03
September 24.45 28.75
October 24.43 25.09
November 24.37 19.63
December 24.23 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.08 13.39
Maximum of Months 24.45 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 13.39
February 24.21 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.43 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.23 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.08 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.55 13.39
February 25.44 16.97
March 26.34 22.37
April 27.01 29.13
May 27.28 32.98
June 27.29 33.60
July 27.14 31.67
August 26.99 30.03
September 26.87 28.75
October 26.66 25.09
November 26.08 19.63
December 25.04 14.52
     
Annual Sum or Average 26.39 24.88
Minimum of Months 24.55 13.39
Maximum of Months 27.29 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.97 13.39
February 24.17 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.15 14.52
     
Annual Sum or Average 24.32 24.88
Minimum of Months 23.97 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 13.39
February 23.92 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.60 14.52
     
Annual Sum or Average 24.17 24.88
Minimum of Months 23.14 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.92 13.39
February 24.15 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.11 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.92 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.02 13.39
February 23.91 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.50 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.02 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 13.39
February 23.95 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.64 14.52
     
Annual Sum or Average 24.18 24.88
Minimum of Months 23.14 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.39
February 23.95 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.63 14.52
     
Annual Sum or Average 24.18 24.88
Minimum of Months 23.13 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 13.39
February 24.22 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.43 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.25 14.52
     
Annual Sum or Average 24.36 24.88
Minimum of Months 24.13 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.12 13.39
February 24.22 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.25 14.52
     
Annual Sum or Average 24.36 24.88
Minimum of Months 24.12 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.77 13.39
February 25.61 16.97
March 26.47 22.37
April 27.10 29.13
May 27.37 32.98
June 27.36 33.60
July 27.21 31.67
August 27.07 30.03
September 26.95 28.75
October 26.77 25.09
November 26.23 19.63
December 25.25 14.52
     
Annual Sum or Average 26.52 24.88
Minimum of Months 24.77 13.39
Maximum of Months 27.37 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.01 13.39
February 24.18 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.17 14.52
     
Annual Sum or Average 24.32 24.88
Minimum of Months 24.01 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 13.39
February 23.95 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.29 19.63
December 23.65 14.52
     
Annual Sum or Average 24.18 24.88
Minimum of Months 23.21 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.96 13.39
February 24.16 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.13 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.96 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.08 13.39
February 23.94 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.29 19.63
December 23.55 14.52
     
Annual Sum or Average 24.17 24.88
Minimum of Months 23.08 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.23 13.39
February 23.99 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.29 19.63
December 23.70 14.52
     
Annual Sum or Average 24.19 24.88
Minimum of Months 23.23 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.22 13.39
February 23.99 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.29 19.63
December 23.70 14.52
     
Annual Sum or Average 24.19 24.88
Minimum of Months 23.22 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 13.39
February 24.23 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.27 14.52
     
Annual Sum or Average 24.36 24.88
Minimum of Months 24.16 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 13.39
February 24.23 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.43 25.09
November 24.38 19.63
December 24.27 14.52
     
Annual Sum or Average 24.36 24.88
Minimum of Months 24.16 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.44 13.39
February 26.24 16.97
March 27.07 22.37
April 27.69 29.13
May 27.95 32.98
June 27.94 33.60
July 27.79 31.67
August 27.65 30.03
September 27.53 28.75
October 27.37 25.09
November 26.85 19.63
December 25.90 14.52
     
Annual Sum or Average 27.12 24.88
Minimum of Months 25.44 13.39
Maximum of Months 27.95 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.97 13.39
February 24.15 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.14 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.97 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 13.39
February 23.90 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.58 14.52
     
Annual Sum or Average 24.17 24.88
Minimum of Months 23.13 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.92 13.39
February 24.13 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.10 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.92 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 13.39
February 23.89 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.48 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.01 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.15 13.39
February 23.94 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.63 14.52
     
Annual Sum or Average 24.18 24.88
Minimum of Months 23.15 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 13.39
February 23.94 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.28 19.63
December 23.62 14.52
     
Annual Sum or Average 24.18 24.88
Minimum of Months 23.14 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 13.39
February 24.21 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.24 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.13 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 13.39
February 24.21 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.43 25.09
November 24.37 19.63
December 24.24 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.13 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.78 13.39
February 25.59 16.97
March 26.46 22.37
April 27.10 29.13
May 27.37 32.98
June 27.35 33.60
July 27.20 31.67
August 27.06 30.03
September 26.93 28.75
October 26.77 25.09
November 26.23 19.63
December 25.25 14.52
     
Annual Sum or Average 26.51 24.88
Minimum of Months 24.78 13.39
Maximum of Months 27.37 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.95 13.39
February 24.14 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.12 14.52
     
Annual Sum or Average 24.31 24.88
Minimum of Months 23.95 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.07 13.39
February 23.87 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.53 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.07 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 13.39
February 24.12 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.36 19.63
December 24.08 14.52
     
Annual Sum or Average 24.30 24.88
Minimum of Months 23.89 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.95 13.39
February 23.86 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.43 14.52
     
Annual Sum or Average 24.14 24.88
Minimum of Months 22.95 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.09 13.39
February 23.90 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.58 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.09 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.07 13.39
February 23.90 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.57 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.07 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.11 13.39
February 24.20 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.42 25.09
November 24.37 19.63
December 24.23 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.11 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.11 13.39
February 24.20 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.44 28.75
October 24.42 25.09
November 24.37 19.63
December 24.23 14.52
     
Annual Sum or Average 24.35 24.88
Minimum of Months 24.11 13.39
Maximum of Months 24.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.64 13.39
February 25.47 16.97
March 26.37 22.37
April 27.02 29.13
May 27.30 32.98
June 27.28 33.60
July 27.13 31.67
August 26.98 30.03
September 26.86 28.75
October 26.68 25.09
November 26.14 19.63
December 25.12 14.52
     
Annual Sum or Average 26.42 24.88
Minimum of Months 24.64 13.39
Maximum of Months 27.30 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.92 13.39
February 24.12 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.35 19.63
December 24.10 14.52
     
Annual Sum or Average 24.30 24.88
Minimum of Months 23.92 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 13.39
February 23.84 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.48 14.52
     
Annual Sum or Average 24.14 24.88
Minimum of Months 23.01 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.86 13.39
February 24.10 16.97
March 24.36 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.35 19.63
December 24.06 14.52
     
Annual Sum or Average 24.29 24.88
Minimum of Months 23.86 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 13.39
February 23.83 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.38 14.52
     
Annual Sum or Average 24.12 24.88
Minimum of Months 22.89 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.02 13.39
February 23.87 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.52 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.02 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 13.39
February 23.87 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.27 19.63
December 23.51 14.52
     
Annual Sum or Average 24.15 24.88
Minimum of Months 23.01 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.09 13.39
February 24.19 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.43 28.75
October 24.42 25.09
November 24.37 19.63
December 24.21 14.52
     
Annual Sum or Average 24.34 24.88
Minimum of Months 24.09 13.39
Maximum of Months 24.43 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.09 13.39
February 24.19 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.43 28.75
October 24.42 25.09
November 24.37 19.63
December 24.21 14.52
     
Annual Sum or Average 24.34 24.88
Minimum of Months 24.09 13.39
Maximum of Months 24.43 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.56 13.39
February 25.41 16.97
March 26.35 22.37
April 27.02 29.13
May 27.31 32.98
June 27.29 33.60
July 27.14 31.67
August 26.99 30.03
September 26.86 28.75
October 26.68 25.09
November 26.11 19.63
December 25.04 14.52
     
Annual Sum or Average 26.40 24.88
Minimum of Months 24.56 13.39
Maximum of Months 27.31 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.85 13.39
February 24.09 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.35 19.63
December 24.04 14.52
     
Annual Sum or Average 24.29 24.88
Minimum of Months 23.85 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.95 13.39
February 23.80 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.26 19.63
December 23.40 14.52
     
Annual Sum or Average 24.13 24.88
Minimum of Months 22.95 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.80 13.39
February 24.07 16.97
March 24.35 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.39 25.09
November 24.35 19.63
December 24.00 14.52
     
Annual Sum or Average 24.28 24.88
Minimum of Months 23.80 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.83 13.39
February 23.80 16.97
March 24.33 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.38 25.09
November 24.26 19.63
December 23.30 14.52
     
Annual Sum or Average 24.11 24.88
Minimum of Months 22.83 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.93 13.39
February 23.83 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.26 19.63
December 23.42 14.52
     
Annual Sum or Average 24.13 24.88
Minimum of Months 22.93 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.92 13.39
February 23.83 16.97
March 24.32 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.41 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.26 19.63
December 23.41 14.52
     
Annual Sum or Average 24.13 24.88
Minimum of Months 22.92 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.02 13.39
February 24.16 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.42 28.75
October 24.41 25.09
November 24.36 19.63
December 24.17 14.52
     
Annual Sum or Average 24.33 24.88
Minimum of Months 24.02 13.39
Maximum of Months 24.42 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.02 13.39
February 24.16 16.97
March 24.34 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.42 31.67
August 24.42 30.03
September 24.42 28.75
October 24.41 25.09
November 24.36 19.63
December 24.17 14.52
     
Annual Sum or Average 24.33 24.88
Minimum of Months 24.02 13.39
Maximum of Months 24.42 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.41 13.39
February 25.34 16.97
March 26.38 22.37
April 27.12 29.13
May 27.44 32.98
June 27.43 33.60
July 27.26 31.67
August 27.10 30.03
September 26.95 28.75
October 26.73 25.09
November 26.08 19.63
December 24.90 14.52
     
Annual Sum or Average 26.43 24.88
Minimum of Months 24.41 13.39
Maximum of Months 27.44 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.43 13.39
February 23.80 16.97
March 24.28 22.37
April 24.40 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.36 25.09
November 24.20 19.63
December 23.59 14.52
     
Annual Sum or Average 24.17 24.88
Minimum of Months 23.43 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.87 13.39
February 23.54 16.97
March 24.25 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.36 25.09
November 24.05 19.63
December 23.09 14.52
     
Annual Sum or Average 24.05 24.88
Minimum of Months 22.87 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 13.39
February 23.78 16.97
March 24.29 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.37 25.09
November 24.18 19.63
December 23.55 14.52
     
Annual Sum or Average 24.16 24.88
Minimum of Months 23.40 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.79 13.39
February 23.56 16.97
March 24.26 22.37
April 24.39 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.35 25.09
November 24.02 19.63
December 23.03 14.52
     
Annual Sum or Average 24.03 24.88
Minimum of Months 22.79 13.39
Maximum of Months 24.40 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.78 13.39
February 23.58 16.97
March 24.24 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.35 25.09
November 24.06 19.63
December 23.08 14.52
     
Annual Sum or Average 24.04 24.88
Minimum of Months 22.78 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.78 13.39
February 23.57 16.97
March 24.24 22.37
April 24.39 29.13
May 24.40 32.98
June 24.41 33.60
July 24.40 31.67
August 24.40 30.03
September 24.40 28.75
October 24.35 25.09
November 24.06 19.63
December 23.07 14.52
     
Annual Sum or Average 24.04 24.88
Minimum of Months 22.78 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.56 13.39
February 23.90 16.97
March 24.29 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.41 28.75
October 24.39 25.09
November 24.24 19.63
December 23.74 14.52
     
Annual Sum or Average 24.21 24.88
Minimum of Months 23.56 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.56 13.39
February 23.90 16.97
March 24.29 22.37
April 24.40 29.13
May 24.40 32.98
June 24.40 33.60
July 24.40 31.67
August 24.40 30.03
September 24.41 28.75
October 24.39 25.09
November 24.24 19.63
December 23.73 14.52
     
Annual Sum or Average 24.21 24.88
Minimum of Months 23.56 13.39
Maximum of Months 24.41 33.60



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:17

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.50 13.39
February 25.59 16.97
March 26.96 22.37
April 27.99 29.13
May 28.48 32.98
June 28.51 33.60
July 28.26 31.67
August 28.03 30.03
September 27.78 28.75
October 27.38 25.09
November 26.40 19.63
December 24.95 14.52
     
Annual Sum or Average 27.07 24.88
Minimum of Months 24.50 13.39
Maximum of Months 28.51 33.60



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:17

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.235902E+12 129407.374 12-JAN-17:45 18221.747 56933.809 25601.197 0.000 13943.308 10720.100 2063.513 775.257 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.231128E+12 161302.870 22-FEB-18:15 22204.399 56867.515 25601.197 0.000 40940.703 10720.100 2063.513 1759.808 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.306650E+12 182977.958 28-MAR-17:15 22204.399 56867.515 25601.197 0.000 72262.411 0.000 2063.513 2833.288 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.350396E+12 195234.301 26-APR-17:15 22204.399 56867.515 25601.197 0.000 83973.716 0.000 2063.513 3378.325 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.396073E+12 201748.952 17-MAY-17:15 22204.399 56867.515 25601.197 0.000 90030.913 0.000 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.397346E+12 207771.157 22-JUN-17:15 22204.399 56867.515 25601.197 0.000 96053.117 0.000 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.416712E+12 208969.319 01-JUL-17:15 22204.399 56867.515 25601.197 0.000 97251.279 0.000 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.409815E+12 204410.294 27-AUG-18:00 25049.151 51564.864 25601.197 0.000 84561.076 10720.100 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.378818E+12 201730.575 14-SEP-18:30 25049.151 51564.864 25601.197 0.000 81881.357 10720.100 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.344007E+12 186823.776 02-OCT-16:15 18221.747 56933.809 25601.197 0.000 79644.615 0.000 2063.513 3210.591 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.279384E+12 172804.858 04-NOV-17:45 22204.399 56867.515 25601.197 0.000 52016.843 10720.100 2063.513 2185.402 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.243671E+12 141480.109 28-DEC-17:30 18221.747 56933.809 25601.197 0.000 25555.929 10720.100 2063.513 1235.372 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.398990E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.231128E+12 129407.374   18221.747 51564.864 25601.197 0.000 13943.308 0.000 2063.513 775.257 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.416712E+12 208969.319   25049.151 56933.809 25601.197 0.000 97251.279 10720.100 2063.513 3835.780 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:17

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.853218E+11 79739.685 10-JAN-07:00 0.000 0.000 0.000 79739.685 79739.685 79739.685 0.000
February 0.754516E+11 79603.175 02-FEB-07:00 0.000 0.000 0.000 79603.175 79603.175 79603.175 0.000
March 0.780819E+11 78340.988 04-MAR-07:45 0.000 0.000 0.000 78340.988 78340.988 78340.988 0.000
April 0.679267E+11 76198.075 05-APR-06:45 0.000 0.000 0.000 76198.075 76198.075 76198.075 0.000
May 0.620914E+11 64901.096 05-MAY-06:45 0.000 0.000 0.000 64901.096 64901.096 64901.096 0.000
June 0.541121E+11 40848.915 01-JUN-06:00 0.000 0.000 0.000 40848.915 40848.915 40848.915 0.000
July 0.534031E+11 40310.895 02-JUL-06:00 0.000 0.000 0.000 40310.895 40310.895 40310.895 0.000
August 0.552099E+11 40742.165 31-AUG-06:00 0.000 0.000 0.000 40742.165 40742.165 40742.165 0.000
September 0.588811E+11 63839.986 30-SEP-06:00 0.000 0.000 0.000 63839.986 63839.986 63839.986 0.000
October 0.687532E+11 76040.068 29-OCT-06:00 0.000 0.000 0.000 76040.068 76040.068 76040.068 0.000
November 0.743755E+11 78096.610 28-NOV-07:00 0.000 0.000 0.000 78096.610 78096.610 78096.610 0.000
December 0.829048E+11 79383.223 25-DEC-07:00 0.000 0.000 0.000 79383.223 79383.223 79383.223 0.000
                     
Annual Sum or Average 0.816513E+12     0.000 0.000 0.000        
Minimum of Months 0.534031E+11 40310.895   0.000 0.000 0.000 40310.895 40310.895 40310.895 0.000
Maximum of Months 0.853218E+11 79739.685   0.000 0.000 0.000 79739.685 79739.685 79739.685 0.000