Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2018-10-19 09:40:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4096.86 | 522.79 | 580.30 |
Net Site Energy | 4096.86 | 522.79 | 580.30 |
Total Source Energy | 9989.55 | 1274.75 | 1414.97 |
Net Source Energy | 9989.55 | 1274.75 | 1414.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 87.77 | 263.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 606.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7.32 | 0.00 | 0.00 | 0.00 | 0.00 | 580.69 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1170.00 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2663.73 | 1433.14 | 0.00 | 0.00 | 0.00 | 5359.20 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 263.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 87.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 180.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 606.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 45.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 7.32 | 0.00 | 0.00 | 0.00 | 0.00 | 580.69 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1170.00 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 131.33 | 203.00 | 0.00 | 0.00 | 0.00 | 0.76 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 377.30 | 203.00 | 0.00 | 0.00 | 0.00 | 0.76 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.31 | 182.88 | 0.00 | 0.00 | 0.00 | 0.68 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 339.91 | 182.88 | 0.00 | 0.00 | 0.00 | 0.68 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2663.73 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2663.73 | 100.00 |
Total On-Site and Utility Electric Sources | 2663.73 | 100.00 |
Total Electricity End Uses | 2663.73 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5359.20 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5359.20 | 100.00 |
Total Water End Uses | 5359.20 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 205.50 |
Time Setpoint Not Met During Occupied Cooling | 27.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 338.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-19:15 | 19-FEB-06:00 | - | - | - | 10-AUG-17:15 |
Heating | 0.00 | 110560.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19223.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1456.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1995.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 84348.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 164379.17 | 194908.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 110560.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 55284.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19223.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1456.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1995.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 84348.77 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 277.97 | 285.24 | 0.00 | 0.00 | 0.00 |
Cooling | 571.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 532.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1919.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 144.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 23.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1268.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8436.03 | 1553.52 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 39.37 | 40.40 | 0.00 | 0.00 | 0.00 |
Cooling | 80.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 179.65 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1194.92 | 220.05 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 39.37 | 40.40 | 0.00 | 0.00 | 0.00 |
Cooling | 80.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 179.65 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1194.92 | 220.05 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.60 | 83.60 | 168.23 | |
Exterior Lighting Total | 10720.10 | 168.23 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 255898.00 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 204718.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3570.28 | 2668.96 | 901.32 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2659.55 | 1976.02 | 683.53 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4819.63 | 3607.88 | 1211.75 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1911.96 | 1414.84 | 497.12 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1236.46 | 894.20 | 342.25 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1197.23 | 864.68 | 332.55 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2618.64 | 1935.04 | 683.60 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2692.49 | 1992.04 | 700.45 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4521.14 | 3398.87 | 1122.26 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3418.26 | 2556.91 | 861.35 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4444.62 | 3338.06 | 1106.55 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2551.26 | 1907.08 | 644.19 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1723.02 | 1262.72 | 460.30 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1686.10 | 1234.72 | 451.38 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3353.06 | 2499.49 | 853.57 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3383.57 | 2523.04 | 860.53 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4543.13 | 3413.64 | 1129.48 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3461.44 | 2587.72 | 873.72 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4243.33 | 3180.61 | 1062.72 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2597.68 | 1941.12 | 656.56 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1780.93 | 1306.00 | 474.93 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1743.98 | 1277.96 | 466.02 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3399.82 | 2534.29 | 865.53 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3416.31 | 2547.02 | 869.29 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4553.40 | 3419.92 | 1133.48 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3476.41 | 2597.74 | 878.67 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4233.89 | 3171.71 | 1062.18 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2605.84 | 1946.05 | 659.79 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1801.93 | 1321.35 | 480.58 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1764.94 | 1293.28 | 471.65 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3415.65 | 2545.54 | 870.11 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3430.15 | 2556.74 | 873.42 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4592.40 | 3448.66 | 1143.74 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3518.59 | 2628.98 | 889.61 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4271.96 | 3199.75 | 1072.21 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2651.33 | 1977.74 | 673.59 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1846.84 | 1355.05 | 491.79 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1809.81 | 1326.95 | 482.86 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3457.90 | 2577.34 | 880.56 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.05 | 2588.26 | 883.79 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4541.57 | 3408.31 | 1133.26 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3469.51 | 2590.18 | 879.33 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4223.10 | 3160.95 | 1062.15 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2599.82 | 1937.10 | 662.73 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1804.29 | 1322.16 | 482.13 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1767.44 | 1294.22 | 473.22 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3410.24 | 2539.91 | 870.33 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3424.33 | 2550.78 | 873.55 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4523.44 | 3393.33 | 1130.11 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3453.33 | 2576.83 | 876.50 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4206.53 | 3147.19 | 1059.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2580.77 | 1921.59 | 659.18 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1792.49 | 1312.77 | 479.72 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1755.74 | 1284.92 | 470.82 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3394.51 | 2527.19 | 867.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3408.55 | 2538.03 | 870.53 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4521.10 | 3390.63 | 1130.47 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3453.61 | 2576.23 | 877.37 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4205.27 | 3145.34 | 1059.93 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2577.53 | 1918.36 | 659.17 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1797.01 | 1315.86 | 481.15 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1760.38 | 1288.10 | 472.28 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3394.29 | 2526.49 | 867.80 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3408.33 | 2537.32 | 871.00 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4612.02 | 3459.90 | 1152.12 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3551.52 | 2650.77 | 900.74 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4275.33 | 3198.52 | 1076.80 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2597.46 | 1933.00 | 664.47 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1885.32 | 1382.80 | 502.52 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1848.28 | 1354.70 | 493.58 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3454.29 | 2572.24 | 882.05 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3469.94 | 2584.32 | 885.62 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5534.46 | 4167.89 | 1366.57 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4246.05 | 3185.64 | 1060.42 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5109.07 | 3840.68 | 1268.39 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3150.03 | 2354.68 | 795.36 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2411.93 | 1767.73 | 644.19 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2411.74 | 1767.58 | 644.17 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4439.88 | 3331.99 | 1107.89 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4450.59 | 3341.31 | 1109.28 | 0.75 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3570.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2659.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4819.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1911.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1236.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1197.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2618.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2692.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4521.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3418.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4444.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2551.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1723.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1686.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3353.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3383.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4543.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3461.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4243.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2597.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1780.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1743.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3399.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3416.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4553.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3476.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4233.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2605.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1801.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1764.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3415.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3430.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4592.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3518.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4271.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2651.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1846.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1809.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3457.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4541.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3469.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4223.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2599.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1804.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1767.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3410.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3424.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4523.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3453.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4206.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2580.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1792.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1755.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3394.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3408.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4521.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3453.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4205.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2577.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1797.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1760.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3394.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3408.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4612.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3551.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4275.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2597.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1885.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1848.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3454.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3469.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5534.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4246.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5109.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3150.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2411.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2411.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4439.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4450.59 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2402.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2403.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3183.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2402.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1787.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1787.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1781.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1790.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2396.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2398.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2422.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2398.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1634.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1634.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1635.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1637.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2409.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2414.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2414.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2416.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1615.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1615.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1611.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1611.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2455.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2462.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2458.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2465.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1635.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1635.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1629.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1629.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2476.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2483.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2480.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2487.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1637.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1637.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1630.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1631.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2562.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2571.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2566.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2576.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1703.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1703.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1694.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1694.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2619.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2629.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2624.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2634.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1744.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1744.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1734.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1734.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2678.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2688.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2683.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2694.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1788.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1789.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1778.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1779.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2840.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2848.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2846.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2855.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1928.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1929.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1920.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1920.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3371.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3385.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3377.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3391.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2501.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2501.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2484.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2484.52 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.72 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.60 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.07 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 143.53 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.08 | 89.20 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.08 | 86.15 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 192.78 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.73 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.78 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 260.33 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 339.12 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.94 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 127.37 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 124.47 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.59 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.05 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 347.20 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 263.15 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 322.56 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.41 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 131.82 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 128.92 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.16 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.49 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 347.77 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 264.12 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 321.54 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.85 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 133.38 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.47 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.28 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 257.45 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 350.70 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.31 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.40 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.57 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 136.85 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 133.94 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.56 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 260.70 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.43 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 263.20 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 320.29 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.27 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 133.41 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.51 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.61 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.75 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 344.81 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.76 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 318.80 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.61 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 132.41 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.52 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.25 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.39 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 344.48 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.66 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 318.55 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.23 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 132.71 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.83 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.15 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.28 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 351.67 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.39 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.06 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.72 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 139.65 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 136.73 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.90 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 260.16 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 425.13 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.71 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 391.10 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 240.14 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.77 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.75 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 338.23 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 339.39 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0056 | 1419.61 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2525.96 | 3031.15 | 0.201 | 0.241 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
G NW APARTMENT | 1869.26 | 2243.11 | 0.148 | 0.178 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
OFFICE | 3409.57 | 4091.49 | 0.271 | 0.325 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
G NE APARTMENT | 1344.16 | 1612.99 | 0.107 | 0.128 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.45 | 0.00879 |
G N1 APARTMENT | 835.37 | 1002.44 | 0.066 | 0.080 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
G N2 APARTMENT | 806.82 | 968.19 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
G S1 APARTMENT | 1805.36 | 2166.43 | 0.143 | 0.172 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
G S2 APARTMENT | 1861.10 | 2233.32 | 0.148 | 0.177 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F2 SW APARTMENT | 3238.22 | 3885.86 | 0.257 | 0.309 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F2 NW APARTMENT | 2438.00 | 2925.60 | 0.194 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
F2 SE APARTMENT | 3175.88 | 3811.06 | 0.252 | 0.303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F2 NE APARTMENT | 1825.64 | 2190.76 | 0.145 | 0.174 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.45 | 0.00879 |
F2 N1 APARTMENT | 1192.85 | 1431.42 | 0.095 | 0.114 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F2 N2 APARTMENT | 1165.66 | 1398.79 | 0.093 | 0.111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F2 S1 APARTMENT | 2356.17 | 2827.41 | 0.187 | 0.225 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F2 S2 APARTMENT | 2379.21 | 2855.05 | 0.189 | 0.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F3 SW APARTMENT | 3251.56 | 3901.88 | 0.258 | 0.310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F3 NW APARTMENT | 2464.40 | 2957.28 | 0.196 | 0.235 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F3 SE APARTMENT | 3020.74 | 3624.89 | 0.240 | 0.288 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F3 NE APARTMENT | 1858.07 | 2229.68 | 0.148 | 0.177 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.45 | 0.00879 |
F3 N1 APARTMENT | 1234.51 | 1481.41 | 0.098 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F3 N2 APARTMENT | 1207.29 | 1448.75 | 0.096 | 0.115 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F3 S1 APARTMENT | 2389.56 | 2867.47 | 0.190 | 0.228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F3 S2 APARTMENT | 2402.01 | 2882.42 | 0.191 | 0.229 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F4 SW APARTMENT | 3256.88 | 3908.25 | 0.259 | 0.310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F4 NW APARTMENT | 2473.43 | 2968.11 | 0.196 | 0.236 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F4 SE APARTMENT | 3011.22 | 3613.46 | 0.239 | 0.287 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F4 NE APARTMENT | 1862.19 | 2234.62 | 0.148 | 0.178 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.45 | 0.00879 |
F4 N1 APARTMENT | 1249.09 | 1498.91 | 0.099 | 0.119 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F4 N2 APARTMENT | 1221.85 | 1466.22 | 0.097 | 0.116 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F4 S1 APARTMENT | 2400.07 | 2880.09 | 0.191 | 0.229 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F4 S2 APARTMENT | 2411.02 | 2893.23 | 0.192 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
M SW APARTMENT | 3284.32 | 3941.18 | 0.261 | 0.313 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
M NW APARTMENT | 2503.33 | 3004.00 | 0.199 | 0.239 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
M SE APARTMENT | 3037.98 | 3645.58 | 0.241 | 0.290 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
M NE APARTMENT | 1887.68 | 2265.22 | 0.150 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.84 | 0.00879 |
M N1 APARTMENT | 1281.61 | 1537.93 | 0.102 | 0.122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
M N2 APARTMENT | 1254.32 | 1505.19 | 0.100 | 0.120 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
M S1 APARTMENT | 2430.77 | 2916.92 | 0.193 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
M S2 APARTMENT | 2441.45 | 2929.74 | 0.194 | 0.233 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F6 SW APARTMENT | 3244.27 | 3893.12 | 0.258 | 0.309 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F6 NW APARTMENT | 2464.88 | 2957.86 | 0.196 | 0.235 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F6 SE APARTMENT | 2999.46 | 3599.35 | 0.238 | 0.286 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F6 NE APARTMENT | 1847.42 | 2216.90 | 0.147 | 0.176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.84 | 0.00879 |
F6 N1 APARTMENT | 1249.35 | 1499.23 | 0.099 | 0.119 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F6 N2 APARTMENT | 1222.24 | 1466.68 | 0.097 | 0.117 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F6 S1 APARTMENT | 2393.82 | 2872.58 | 0.190 | 0.228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F6 S2 APARTMENT | 2404.46 | 2885.35 | 0.191 | 0.229 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F7 SW APARTMENT | 3229.10 | 3874.92 | 0.257 | 0.308 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F7 NW APARTMENT | 2451.37 | 2941.65 | 0.195 | 0.234 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F7 SE APARTMENT | 2985.50 | 3582.60 | 0.237 | 0.285 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F7 NE APARTMENT | 1831.82 | 2198.19 | 0.146 | 0.175 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.84 | 0.00879 |
F7 N1 APARTMENT | 1240.01 | 1488.01 | 0.099 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F7 N2 APARTMENT | 1212.98 | 1455.58 | 0.096 | 0.116 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F7 S1 APARTMENT | 2381.08 | 2857.30 | 0.189 | 0.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F7 S2 APARTMENT | 2391.68 | 2870.02 | 0.190 | 0.228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F8 SW APARTMENT | 3226.01 | 3871.21 | 0.256 | 0.308 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F8 NW APARTMENT | 2450.37 | 2940.45 | 0.195 | 0.234 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F8 SE APARTMENT | 2983.24 | 3579.89 | 0.237 | 0.284 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F8 NE APARTMENT | 1828.29 | 2193.94 | 0.145 | 0.174 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.84 | 0.00879 |
F8 N1 APARTMENT | 1242.82 | 1491.38 | 0.099 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F8 N2 APARTMENT | 1215.89 | 1459.06 | 0.097 | 0.116 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F8 S1 APARTMENT | 2380.13 | 2856.15 | 0.189 | 0.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F8 S2 APARTMENT | 2390.73 | 2868.87 | 0.190 | 0.228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F9 SW APARTMENT | 3293.34 | 3952.01 | 0.262 | 0.314 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
F9 NW APARTMENT | 2522.82 | 3027.39 | 0.200 | 0.241 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 27.16 | 0.00879 |
F9 SE APARTMENT | 3034.84 | 3641.81 | 0.241 | 0.289 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
F9 NE APARTMENT | 1842.23 | 2210.68 | 0.146 | 0.176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.84 | 0.00879 |
F9 N1 APARTMENT | 1307.77 | 1569.32 | 0.104 | 0.125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F9 N2 APARTMENT | 1280.50 | 1536.60 | 0.102 | 0.122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34 | 0.00879 |
F9 S1 APARTMENT | 2424.60 | 2909.52 | 0.193 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
F9 S2 APARTMENT | 2436.41 | 2923.70 | 0.194 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
T SW APARTMENT | 3981.32 | 4777.58 | 0.316 | 0.380 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 29.24 | 0.00879 |
T NW APARTMENT | 3040.86 | 3649.03 | 0.242 | 0.290 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 27.68 | 0.00879 |
T SE APARTMENT | 3662.61 | 4395.14 | 0.291 | 0.349 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
T NE APARTMENT | 2248.92 | 2698.70 | 0.179 | 0.214 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 26.23 | 0.00879 |
T N1 APARTMENT | 1636.69 | 1964.03 | 0.130 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 29.40 | 0.00879 |
T N2 APARTMENT | 1636.53 | 1963.83 | 0.130 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
T S1 APARTMENT | 3167.50 | 3801.00 | 0.252 | 0.302 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
T S2 APARTMENT | 3178.37 | 3814.04 | 0.252 | 0.303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1353.41 | 1624.09 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
G NW APARTMENT | 1354.59 | 1625.50 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
OFFICE | 1696.39 | 2035.67 | 0.077 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -4.20 | 0.00269 |
G NE APARTMENT | 1353.47 | 1624.17 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
G N1 APARTMENT | 833.40 | 1000.09 | 0.038 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
G N2 APARTMENT | 833.38 | 1000.06 | 0.038 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
G S1 APARTMENT | 828.91 | 994.69 | 0.037 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
G S2 APARTMENT | 836.10 | 1003.32 | 0.038 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
F2 SW APARTMENT | 1348.62 | 1618.35 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 NW APARTMENT | 1350.06 | 1620.08 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 SE APARTMENT | 1370.82 | 1644.99 | 0.062 | 0.074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 NE APARTMENT | 1350.65 | 1620.77 | 0.061 | 0.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 N1 APARTMENT | 704.20 | 845.04 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 N2 APARTMENT | 704.21 | 845.06 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 S1 APARTMENT | 705.00 | 846.00 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F2 S2 APARTMENT | 706.48 | 847.78 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 SW APARTMENT | 1359.73 | 1631.68 | 0.061 | 0.074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 NW APARTMENT | 1363.58 | 1636.30 | 0.062 | 0.074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 SE APARTMENT | 1364.07 | 1636.89 | 0.062 | 0.074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 NE APARTMENT | 1365.43 | 1638.52 | 0.062 | 0.074 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 N1 APARTMENT | 688.18 | 825.82 | 0.031 | 0.037 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 N2 APARTMENT | 688.23 | 825.88 | 0.031 | 0.037 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 S1 APARTMENT | 684.87 | 821.85 | 0.031 | 0.037 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F3 S2 APARTMENT | 685.16 | 822.19 | 0.031 | 0.037 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 SW APARTMENT | 1398.41 | 1678.09 | 0.063 | 0.076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 NW APARTMENT | 1404.08 | 1684.90 | 0.063 | 0.076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 SE APARTMENT | 1401.46 | 1681.75 | 0.063 | 0.076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 NE APARTMENT | 1406.86 | 1688.23 | 0.064 | 0.076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 N1 APARTMENT | 705.31 | 846.37 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 N2 APARTMENT | 705.38 | 846.46 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 S1 APARTMENT | 699.93 | 839.92 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F4 S2 APARTMENT | 700.04 | 840.05 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M SW APARTMENT | 1416.15 | 1699.38 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M NW APARTMENT | 1422.12 | 1706.54 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M SE APARTMENT | 1419.67 | 1703.60 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M NE APARTMENT | 1425.60 | 1710.72 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M N1 APARTMENT | 706.93 | 848.31 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M N2 APARTMENT | 707.02 | 848.42 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M S1 APARTMENT | 701.22 | 841.46 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
M S2 APARTMENT | 701.31 | 841.58 | 0.032 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 SW APARTMENT | 1488.73 | 1786.48 | 0.067 | 0.081 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 NW APARTMENT | 1496.43 | 1795.72 | 0.068 | 0.081 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 SE APARTMENT | 1492.82 | 1791.39 | 0.067 | 0.081 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 NE APARTMENT | 1500.51 | 1800.62 | 0.068 | 0.081 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 N1 APARTMENT | 762.33 | 914.80 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 N2 APARTMENT | 762.44 | 914.93 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 S1 APARTMENT | 754.82 | 905.79 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F6 S2 APARTMENT | 754.93 | 905.92 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 SW APARTMENT | 1537.07 | 1844.49 | 0.069 | 0.083 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 NW APARTMENT | 1545.32 | 1854.38 | 0.070 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 SE APARTMENT | 1541.66 | 1849.99 | 0.070 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 NE APARTMENT | 1549.90 | 1859.88 | 0.070 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 N1 APARTMENT | 797.15 | 956.58 | 0.036 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 N2 APARTMENT | 797.27 | 956.73 | 0.036 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 S1 APARTMENT | 789.04 | 946.84 | 0.036 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F7 S2 APARTMENT | 789.16 | 946.99 | 0.036 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 SW APARTMENT | 1586.79 | 1904.15 | 0.072 | 0.086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 NW APARTMENT | 1595.35 | 1914.42 | 0.072 | 0.086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 SE APARTMENT | 1591.80 | 1910.16 | 0.072 | 0.086 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 NE APARTMENT | 1600.36 | 1920.43 | 0.072 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 N1 APARTMENT | 834.83 | 1001.79 | 0.038 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 N2 APARTMENT | 834.96 | 1001.95 | 0.038 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 S1 APARTMENT | 826.39 | 991.67 | 0.037 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F8 S2 APARTMENT | 826.52 | 991.83 | 0.037 | 0.045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 SW APARTMENT | 1723.92 | 2068.70 | 0.078 | 0.093 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 NW APARTMENT | 1731.08 | 2077.29 | 0.078 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 SE APARTMENT | 1729.35 | 2075.22 | 0.078 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 NE APARTMENT | 1736.50 | 2083.80 | 0.078 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 N1 APARTMENT | 953.25 | 1143.90 | 0.043 | 0.052 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 N2 APARTMENT | 953.39 | 1144.07 | 0.043 | 0.052 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 S1 APARTMENT | 945.83 | 1135.00 | 0.043 | 0.051 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
F9 S2 APARTMENT | 945.97 | 1135.17 | 0.043 | 0.051 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T SW APARTMENT | 2173.31 | 2607.97 | 0.098 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T NW APARTMENT | 2185.25 | 2622.30 | 0.099 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T SE APARTMENT | 2178.57 | 2614.28 | 0.098 | 0.118 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T NE APARTMENT | 2190.51 | 2628.61 | 0.099 | 0.119 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T N1 APARTMENT | 1437.62 | 1725.15 | 0.065 | 0.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T N2 APARTMENT | 1437.77 | 1725.32 | 0.065 | 0.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T S1 APARTMENT | 1422.95 | 1707.54 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
T S2 APARTMENT | 1423.09 | 1707.71 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -4.20 | 0.00269 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.24 | 0.24 | 0.07 | 0.07 |
AIRLOOP G NW | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP OFFICE | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP G NE | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP G N1 | 0.08 | 0.08 | 0.05 | 0.05 |
AIRLOOP G N2 | 0.08 | 0.08 | 0.05 | 0.05 |
AIRLOOP G S1 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP G S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 SW | 0.31 | 0.31 | 0.07 | 0.07 |
AIRLOOP F2 NW | 0.23 | 0.23 | 0.07 | 0.07 |
AIRLOOP F2 SE | 0.30 | 0.30 | 0.07 | 0.07 |
AIRLOOP F2 NE | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F2 N1 | 0.11 | 0.11 | 0.04 | 0.04 |
AIRLOOP F2 N2 | 0.11 | 0.11 | 0.04 | 0.04 |
AIRLOOP F2 S1 | 0.22 | 0.22 | 0.04 | 0.04 |
AIRLOOP F2 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F3 SW | 0.31 | 0.31 | 0.07 | 0.07 |
AIRLOOP F3 NW | 0.23 | 0.23 | 0.07 | 0.07 |
AIRLOOP F3 SE | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP F3 NE | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F3 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F3 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F3 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F3 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F4 SW | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP F4 NW | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP F4 SE | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F4 NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F4 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F4 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F4 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F4 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP M SW | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP M NW | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP M SE | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP M NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP M N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP M N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP M S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP M S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F6 SW | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP F6 NW | 0.23 | 0.23 | 0.08 | 0.08 |
AIRLOOP F6 SE | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F6 NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F6 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F6 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F6 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F6 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F7 SW | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP F7 NW | 0.23 | 0.23 | 0.08 | 0.08 |
AIRLOOP F7 SE | 0.28 | 0.28 | 0.08 | 0.08 |
AIRLOOP F7 NE | 0.17 | 0.17 | 0.08 | 0.08 |
AIRLOOP F7 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F7 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F7 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F7 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F8 SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F8 NW | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F8 SE | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F8 NE | 0.17 | 0.17 | 0.09 | 0.09 |
AIRLOOP F8 N1 | 0.12 | 0.12 | 0.05 | 0.05 |
AIRLOOP F8 N2 | 0.12 | 0.12 | 0.05 | 0.05 |
AIRLOOP F8 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F8 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F9 SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F9 NW | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F9 SE | 0.29 | 0.29 | 0.09 | 0.09 |
AIRLOOP F9 NE | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP F9 N1 | 0.12 | 0.12 | 0.05 | 0.05 |
AIRLOOP F9 N2 | 0.12 | 0.12 | 0.05 | 0.05 |
AIRLOOP F9 S1 | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F9 S2 | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP T SW | 0.38 | 0.38 | 0.12 | 0.12 |
AIRLOOP T NW | 0.29 | 0.29 | 0.12 | 0.12 |
AIRLOOP T SE | 0.35 | 0.35 | 0.12 | 0.12 |
AIRLOOP T NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP T N1 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP T N2 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP T S1 | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP T S2 | 0.30 | 0.30 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1839.75 | 5821.25 | 57.00 |
G NW APARTMENT | 1216.00 | 6787.75 | 100.75 |
OFFICE | 785.00 | 1030.75 | 1.00 |
G NE APARTMENT | 1150.75 | 6942.25 | 112.00 |
G N1 APARTMENT | 826.25 | 7220.25 | 104.75 |
G N2 APARTMENT | 821.50 | 7248.00 | 105.50 |
G S1 APARTMENT | 1660.00 | 5954.00 | 67.25 |
G S2 APARTMENT | 1703.75 | 5860.25 | 65.75 |
F2 SW APARTMENT | 3126.50 | 4201.25 | 7.75 |
F2 NW APARTMENT | 2098.50 | 5549.75 | 26.00 |
F2 SE APARTMENT | 3266.75 | 4095.25 | 7.50 |
F2 NE APARTMENT | 1990.75 | 5803.25 | 44.00 |
F2 N1 APARTMENT | 1719.75 | 6006.00 | 56.50 |
F2 N2 APARTMENT | 1702.25 | 6040.00 | 59.50 |
F2 S1 APARTMENT | 3177.50 | 3856.50 | 9.75 |
F2 S2 APARTMENT | 3201.25 | 3826.25 | 9.25 |
F3 SW APARTMENT | 3467.50 | 3905.50 | 5.75 |
F3 NW APARTMENT | 2322.50 | 5258.75 | 13.75 |
F3 SE APARTMENT | 3427.25 | 3928.25 | 5.75 |
F3 NE APARTMENT | 2192.50 | 5527.25 | 27.50 |
F3 N1 APARTMENT | 2013.25 | 5537.50 | 32.75 |
F3 N2 APARTMENT | 1990.00 | 5578.75 | 34.00 |
F3 S1 APARTMENT | 3671.00 | 3291.50 | 2.25 |
F3 S2 APARTMENT | 3677.00 | 3282.75 | 2.25 |
F4 SW APARTMENT | 3550.75 | 3847.25 | 4.75 |
F4 NW APARTMENT | 2407.00 | 5146.50 | 12.50 |
F4 SE APARTMENT | 3479.00 | 3894.25 | 5.50 |
F4 NE APARTMENT | 2266.75 | 5423.50 | 23.50 |
F4 N1 APARTMENT | 2149.00 | 5342.25 | 26.25 |
F4 N2 APARTMENT | 2128.00 | 5376.00 | 27.25 |
F4 S1 APARTMENT | 3845.00 | 3144.25 | 2.00 |
F4 S2 APARTMENT | 3845.00 | 3147.00 | 2.00 |
M SW APARTMENT | 3563.75 | 3841.75 | 4.00 |
M NW APARTMENT | 2431.75 | 5126.50 | 8.50 |
M SE APARTMENT | 3483.50 | 3894.75 | 5.25 |
M NE APARTMENT | 2293.00 | 5390.75 | 18.50 |
M N1 APARTMENT | 2210.50 | 5261.00 | 21.50 |
M N2 APARTMENT | 2184.25 | 5298.25 | 21.75 |
M S1 APARTMENT | 3901.25 | 3105.00 | 2.00 |
M S2 APARTMENT | 3896.25 | 3105.00 | 2.00 |
F6 SW APARTMENT | 3330.00 | 4019.50 | 5.00 |
F6 NW APARTMENT | 2251.50 | 5344.00 | 14.00 |
F6 SE APARTMENT | 3258.75 | 4075.75 | 5.75 |
F6 NE APARTMENT | 2116.75 | 5623.50 | 28.25 |
F6 N1 APARTMENT | 2015.25 | 5510.25 | 25.00 |
F6 N2 APARTMENT | 1991.50 | 5548.00 | 27.50 |
F6 S1 APARTMENT | 3629.25 | 3316.75 | 1.75 |
F6 S2 APARTMENT | 3628.25 | 3318.25 | 1.75 |
F7 SW APARTMENT | 3176.00 | 4143.00 | 5.75 |
F7 NW APARTMENT | 2136.50 | 5491.25 | 16.25 |
F7 SE APARTMENT | 3098.50 | 4228.25 | 5.75 |
F7 NE APARTMENT | 2011.00 | 5769.25 | 29.75 |
F7 N1 APARTMENT | 1900.25 | 5693.00 | 26.75 |
F7 N2 APARTMENT | 1882.25 | 5729.25 | 27.00 |
F7 S1 APARTMENT | 3456.75 | 3509.75 | 1.75 |
F7 S2 APARTMENT | 3452.75 | 3515.25 | 1.75 |
F8 SW APARTMENT | 3040.00 | 4279.50 | 5.25 |
F8 NW APARTMENT | 2040.50 | 5629.75 | 17.00 |
F8 SE APARTMENT | 2963.00 | 4366.25 | 5.50 |
F8 NE APARTMENT | 1914.00 | 5915.25 | 32.00 |
F8 N1 APARTMENT | 1815.25 | 5852.75 | 27.50 |
F8 N2 APARTMENT | 1790.50 | 5900.25 | 28.50 |
F8 S1 APARTMENT | 3307.00 | 3714.00 | 4.50 |
F8 S2 APARTMENT | 3300.25 | 3720.50 | 4.50 |
F9 SW APARTMENT | 2864.50 | 4508.00 | 7.00 |
F9 NW APARTMENT | 1933.25 | 5793.75 | 30.25 |
F9 SE APARTMENT | 2816.00 | 4594.50 | 8.50 |
F9 NE APARTMENT | 1818.50 | 6074.00 | 46.50 |
F9 N1 APARTMENT | 1693.50 | 6050.00 | 34.00 |
F9 N2 APARTMENT | 1675.00 | 6091.25 | 36.50 |
F9 S1 APARTMENT | 3073.25 | 4042.75 | 6.25 |
F9 S2 APARTMENT | 3069.75 | 4049.25 | 6.25 |
T SW APARTMENT | 2499.75 | 5147.50 | 126.00 |
T NW APARTMENT | 1800.50 | 6221.75 | 222.75 |
T SE APARTMENT | 2497.25 | 5215.50 | 133.00 |
T NE APARTMENT | 1797.75 | 6434.50 | 241.25 |
T N1 APARTMENT | 1477.25 | 6459.50 | 96.50 |
T N2 APARTMENT | 1473.75 | 6474.50 | 96.50 |
T S1 APARTMENT | 2554.00 | 4763.00 | 29.50 |
T S2 APARTMENT | 2544.00 | 4760.25 | 28.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4553.00 | 7484.25 | 338.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
G NW APARTMENT | 6.75 | 3.00 | 6.75 | 3.00 |
OFFICE | 4.25 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 9.00 | 0.00 | 9.00 | 0.00 |
G N1 APARTMENT | 7.25 | 17.50 | 7.25 | 17.50 |
G N2 APARTMENT | 7.00 | 21.50 | 7.00 | 21.50 |
G S1 APARTMENT | 6.50 | 0.00 | 6.50 | 0.00 |
G S2 APARTMENT | 8.50 | 0.00 | 8.50 | 0.00 |
F2 SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F2 NW APARTMENT | 1.25 | 1.75 | 1.25 | 1.75 |
F2 SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F2 NE APARTMENT | 10.50 | 0.00 | 10.50 | 0.00 |
F2 N1 APARTMENT | 3.00 | 9.50 | 3.00 | 9.50 |
F2 N2 APARTMENT | 3.25 | 11.00 | 3.25 | 11.00 |
F2 S1 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F2 S2 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
F3 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F3 NW APARTMENT | 1.50 | 2.50 | 1.50 | 2.50 |
F3 SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F3 NE APARTMENT | 10.25 | 0.00 | 10.25 | 0.00 |
F3 N1 APARTMENT | 2.00 | 11.50 | 2.00 | 11.50 |
F3 N2 APARTMENT | 2.00 | 13.75 | 2.00 | 13.75 |
F3 S1 APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
F3 S2 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
F4 SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F4 NW APARTMENT | 1.75 | 2.50 | 1.75 | 2.50 |
F4 SE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F4 NE APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
F4 N1 APARTMENT | 2.75 | 12.50 | 2.75 | 12.50 |
F4 N2 APARTMENT | 2.50 | 14.50 | 2.50 | 14.50 |
F4 S1 APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
F4 S2 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 2.25 | 2.50 | 2.25 | 2.50 |
M SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M NE APARTMENT | 7.25 | 0.00 | 7.25 | 0.00 |
M N1 APARTMENT | 2.25 | 13.00 | 2.25 | 13.00 |
M N2 APARTMENT | 2.75 | 14.25 | 2.75 | 14.25 |
M S1 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
M S2 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
F6 SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F6 NW APARTMENT | 0.75 | 2.75 | 0.75 | 2.75 |
F6 SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F6 NE APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
F6 N1 APARTMENT | 3.75 | 13.00 | 3.75 | 13.00 |
F6 N2 APARTMENT | 4.00 | 14.50 | 4.00 | 14.50 |
F6 S1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
F6 S2 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
F7 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F7 NW APARTMENT | 0.50 | 2.75 | 0.50 | 2.75 |
F7 SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F7 NE APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
F7 N1 APARTMENT | 6.00 | 12.75 | 6.00 | 12.75 |
F7 N2 APARTMENT | 6.00 | 14.00 | 6.00 | 14.00 |
F7 S1 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F7 S2 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
F8 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F8 NW APARTMENT | 1.00 | 2.75 | 1.00 | 2.75 |
F8 SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F8 NE APARTMENT | 4.75 | 0.25 | 4.75 | 0.25 |
F8 N1 APARTMENT | 7.50 | 14.50 | 7.50 | 14.50 |
F8 N2 APARTMENT | 7.75 | 15.75 | 7.75 | 15.75 |
F8 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F8 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F9 SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F9 NW APARTMENT | 0.25 | 2.25 | 0.25 | 2.25 |
F9 SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F9 NE APARTMENT | 2.75 | 2.00 | 2.75 | 2.00 |
F9 N1 APARTMENT | 11.50 | 11.50 | 11.50 | 11.50 |
F9 N2 APARTMENT | 9.75 | 14.25 | 9.75 | 14.25 |
F9 S1 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
F9 S2 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.75 | 0.50 | 0.75 | 0.50 |
T N1 APARTMENT | 11.25 | 8.75 | 11.25 | 8.75 |
T N2 APARTMENT | 9.25 | 7.25 | 9.25 | 7.25 |
T S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 209.00 | 27.00 | 205.50 | 27.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.094 | 0.000 | 0.287 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.094 | 0.000 | 0.277 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.520 | 0.101 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.094 | 0.000 | 0.276 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.057 | 0.000 | 0.269 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.057 | 0.000 | 0.269 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.057 | 0.000 | 0.283 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.057 | 0.000 | 0.284 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.135 | 0.000 | 0.322 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.135 | 0.000 | 0.315 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.135 | 0.000 | 0.323 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.135 | 0.000 | 0.314 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.081 | 0.000 | 0.308 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.081 | 0.000 | 0.308 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.082 | 0.000 | 0.320 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.082 | 0.000 | 0.320 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.160 | 0.000 | 0.342 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.160 | 0.000 | 0.336 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.160 | 0.000 | 0.343 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.160 | 0.000 | 0.336 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.096 | 0.000 | 0.331 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.096 | 0.000 | 0.331 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.097 | 0.000 | 0.341 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.097 | 0.000 | 0.341 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.179 | 0.000 | 0.344 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.179 | 0.000 | 0.339 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.179 | 0.000 | 0.345 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.179 | 0.000 | 0.339 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.108 | 0.000 | 0.334 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.108 | 0.000 | 0.334 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.108 | 0.000 | 0.343 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.108 | 0.000 | 0.343 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.357 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.194 | 0.000 | 0.352 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.358 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.194 | 0.000 | 0.352 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.117 | 0.000 | 0.348 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.117 | 0.000 | 0.348 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.117 | 0.000 | 0.356 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.117 | 0.000 | 0.356 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.208 | 0.000 | 0.368 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.207 | 0.000 | 0.363 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.208 | 0.000 | 0.369 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.207 | 0.000 | 0.362 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.125 | 0.000 | 0.358 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.125 | 0.000 | 0.358 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.125 | 0.000 | 0.367 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.125 | 0.000 | 0.367 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.219 | 0.000 | 0.377 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.219 | 0.000 | 0.371 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.219 | 0.000 | 0.377 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.219 | 0.000 | 0.371 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.132 | 0.000 | 0.367 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.132 | 0.000 | 0.367 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.132 | 0.000 | 0.375 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.132 | 0.000 | 0.375 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.230 | 0.000 | 0.387 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.230 | 0.000 | 0.381 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.230 | 0.000 | 0.387 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.230 | 0.000 | 0.380 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.139 | 0.000 | 0.376 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.139 | 0.000 | 0.376 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.139 | 0.000 | 0.385 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.139 | 0.000 | 0.385 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.395 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.239 | 0.000 | 0.389 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.395 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.239 | 0.000 | 0.388 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.144 | 0.000 | 0.384 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.144 | 0.000 | 0.384 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.145 | 0.000 | 0.393 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.145 | 0.000 | 0.393 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.249 | 0.000 | 0.400 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.248 | 0.000 | 0.396 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.249 | 0.000 | 0.401 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.248 | 0.000 | 0.395 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.150 | 0.000 | 0.391 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.150 | 0.000 | 0.391 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.150 | 0.000 | 0.399 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.150 | 0.000 | 0.399 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 606.23 | 19223.46 | 25-MAY-10:45 | 19223.46 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 895.17 | 19603.99 | 07-JUN-02:15 | 81957.21 | 29-AUG-15:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
ElectricityPurchased:Plant | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
Cogeneration:ElectricityPurchased | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
ElectricityNet:Plant | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
Cogeneration:ElectricityNet | 2663.73 | 57164.48 | 07-JUN-02:15 | 164379.17 | 29-AUG-19:15 |
ExteriorLights:Electricity | 168.23 | 0.00 | 01-JAN-08:15 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.23 | 0.00 | 01-JAN-08:15 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 606.23 | 19223.46 | 25-MAY-10:45 | 19223.46 | 01-JAN-00:15 |
Cooling:Electricity | 180.34 | 0.00 | 01-JAN-00:15 | 61916.53 | 29-AUG-15:15 |
Heating:Electricity | 87.77 | 0.00 | 11-JAN-19:30 | 30490.01 | 19-FEB-06:00 |
Electricity:Plant | 52.82 | 36.93 | 11-JAN-19:30 | 3675.59 | 29-AUG-14:45 |
HeatRejection:Electricity | 7.32 | 0.00 | 01-JAN-00:15 | 2219.06 | 29-AUG-14:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 45.50 | 36.93 | 11-JAN-19:30 | 1456.53 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1433.14 | 9260.51 | 20-JAN-15:45 | 194908.94 | 19-FEB-07:00 |
Gas:Plant | 1433.14 | 9260.51 | 20-JAN-15:45 | 194908.94 | 19-FEB-07:00 |
WaterSystems:Gas | 1170.00 | 9260.51 | 01-JAN-00:15 | 86836.29 | 12-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1170.00 | 9260.51 | 01-JAN-00:15 | 86836.29 | 12-FEB-08:00 |
Heating:Gas | 263.14 | 0.00 | 11-JAN-14:00 | 115577.23 | 19-FEB-06:15 |
Boiler:Heating:Gas | 263.14 | 0.00 | 11-JAN-14:00 | 115577.23 | 19-FEB-06:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 712.07 | 0.00 | 01-JAN-00:15 | 279859.01 | 29-AUG-15:15 |
PlantLoopCoolingDemand:HVAC | 712.07 | 0.00 | 01-JAN-00:15 | 279859.01 | 29-AUG-15:15 |
CoolingCoils:PlantLoopCoolingDemand | 712.07 | 0.00 | 01-JAN-00:15 | 279859.01 | 29-AUG-15:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5359.20 | 0.00 | 01-JAN-02:15 | 0.00 | 10-AUG-17:15 |
Water:Plant | 5359.20 | 0.00 | 01-JAN-02:15 | 0.00 | 10-AUG-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5359.20 | 0.00 | 01-JAN-02:15 | 0.00 | 10-AUG-17:15 |
MainsWater:Plant | 5359.20 | 0.00 | 01-JAN-02:15 | 0.00 | 10-AUG-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 580.69 | 0.00 | 01-JAN-00:15 | 0.00 | 10-AUG-17:00 |
HeatRejection:MainsWater | 580.69 | 0.00 | 01-JAN-00:15 | 0.00 | 10-AUG-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1131.01 | 507.56 | 12-AUG-01:15 | 148562.84 | 19-FEB-06:15 |
PlantLoopHeatingDemand:Plant | 889.33 | 507.56 | 12-AUG-01:15 | 57932.84 | 08-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 889.33 | 507.56 | 12-AUG-01:15 | 57932.84 | 08-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2820.85 | 6311.75 | 17-JUL-03:00 | 420013.18 | 10-AUG-17:15 |
EnergyTransfer:Building | 852.89 | 3282.53 | 14-MAY-21:00 | 172110.05 | 07-AUG-13:30 |
EnergyTransfer:Zone:G SW APARTMENT | 8.62 | 0.01 | 06-NOV-21:15 | 2659.06 | 10-AUG-16:30 |
Heating:EnergyTransfer | 160.64 | 0.00 | 03-FEB-11:45 | 73911.44 | 19-FEB-06:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.57 | 0.00 | 03-JAN-10:30 | 995.19 | 19-FEB-06:00 |
Cooling:EnergyTransfer | 692.25 | 0.00 | 01-JAN-00:15 | 172110.05 | 07-AUG-13:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.06 | 0.00 | 01-JAN-00:15 | 2659.06 | 10-AUG-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 7.75 | 0.01 | 05-AUG-10:30 | 2125.70 | 23-JUL-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 3.88 | 0.00 | 11-JAN-14:00 | 1160.12 | 19-FEB-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 3.87 | 0.00 | 01-JAN-00:15 | 2125.70 | 23-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 14.84 | 0.02 | 07-MAY-01:00 | 3299.22 | 29-AUG-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 2.65 | 0.00 | 02-JAN-08:30 | 1152.65 | 19-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 12.19 | 0.00 | 01-JAN-00:15 | 3299.22 | 29-AUG-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 7.81 | 0.01 | 16-JUN-18:30 | 1387.66 | 24-JUL-10:45 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 3.79 | 0.00 | 10-JAN-19:00 | 1044.09 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.03 | 0.00 | 01-JAN-00:15 | 1387.66 | 24-JUL-10:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 5.99 | 0.02 | 23-FEB-11:15 | 975.78 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.39 | 0.00 | 01-JAN-17:30 | 743.95 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.60 | 0.00 | 01-JAN-00:15 | 975.78 | 23-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 6.01 | 0.01 | 15-MAY-14:30 | 945.11 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.39 | 0.00 | 01-JAN-17:30 | 744.87 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.62 | 0.00 | 01-JAN-00:15 | 945.11 | 23-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.31 | 0.02 | 19-AUG-09:45 | 1882.29 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.56 | 0.00 | 01-JAN-18:00 | 592.01 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 6.75 | 0.00 | 01-JAN-00:15 | 1882.29 | 07-AUG-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.38 | 0.01 | 17-JAN-22:45 | 1920.43 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.53 | 0.00 | 01-JAN-18:00 | 534.80 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 6.84 | 0.00 | 01-JAN-00:15 | 1920.43 | 07-AUG-13:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 12.51 | 0.01 | 24-FEB-13:45 | 3420.95 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 1.64 | 0.00 | 03-JAN-10:30 | 983.42 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 10.87 | 0.00 | 01-JAN-00:15 | 3420.95 | 10-AUG-16:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 9.04 | 0.01 | 01-FEB-12:45 | 2702.29 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 2.88 | 0.00 | 03-JAN-18:45 | 1115.66 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 6.16 | 0.00 | 01-JAN-00:15 | 2702.29 | 23-JUL-17:15 |
EnergyTransfer:Zone:F2 SE APARTMENT | 12.79 | 0.01 | 25-FEB-15:15 | 3146.54 | 10-AUG-12:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 1.40 | 0.00 | 02-JAN-20:00 | 958.90 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 11.39 | 0.00 | 01-JAN-00:15 | 3146.54 | 10-AUG-12:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 8.96 | 0.01 | 30-DEC-14:15 | 1906.46 | 24-JUL-10:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 2.73 | 0.00 | 03-JAN-18:45 | 1106.25 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 6.23 | 0.00 | 01-JAN-00:15 | 1906.46 | 24-JUL-10:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 7.33 | 0.03 | 24-DEC-15:30 | 1383.50 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.46 | 0.00 | 01-JAN-06:30 | 514.20 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 6.87 | 0.00 | 01-JAN-00:15 | 1383.50 | 23-JUL-18:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 7.33 | 0.04 | 03-JAN-01:30 | 1354.39 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.46 | 0.00 | 01-JAN-06:30 | 518.46 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 6.87 | 0.00 | 01-JAN-00:15 | 1354.39 | 23-JUL-18:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 11.62 | 0.01 | 25-JAN-03:00 | 2466.75 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.25 | 0.00 | 01-JAN-06:30 | 353.68 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 11.37 | 0.00 | 01-JAN-00:15 | 2466.75 | 07-AUG-13:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 11.68 | 0.06 | 05-SEP-14:00 | 2481.32 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.25 | 0.00 | 01-JAN-06:30 | 351.37 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 11.43 | 0.00 | 01-JAN-00:15 | 2481.32 | 07-AUG-13:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 13.46 | 0.02 | 27-JAN-18:30 | 3442.50 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 1.55 | 0.00 | 03-JAN-10:30 | 995.57 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 11.91 | 0.00 | 01-JAN-00:15 | 3442.50 | 10-AUG-16:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 9.54 | 0.04 | 06-DEC-18:15 | 2772.68 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 2.73 | 0.00 | 03-JAN-18:45 | 1134.89 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 6.81 | 0.00 | 01-JAN-00:15 | 2772.68 | 23-JUL-17:15 |
EnergyTransfer:Zone:F3 SE APARTMENT | 13.32 | 0.09 | 17-AUG-16:00 | 3126.06 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 1.46 | 0.00 | 03-JAN-10:15 | 979.67 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 11.86 | 0.00 | 01-JAN-00:15 | 3126.06 | 07-AUG-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 9.44 | 0.01 | 26-JUN-15:30 | 1975.94 | 20-JUL-17:30 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 2.59 | 0.00 | 03-JAN-18:45 | 1124.98 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 6.85 | 0.00 | 01-JAN-00:15 | 1975.94 | 20-JUL-17:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 8.04 | 0.07 | 19-AUG-14:45 | 1446.42 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.36 | 0.00 | 01-JAN-06:30 | 474.11 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.68 | 0.00 | 01-JAN-00:15 | 1446.42 | 23-JUL-18:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 8.04 | 0.08 | 02-JUL-14:15 | 1417.08 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.36 | 0.00 | 01-JAN-06:30 | 473.40 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.68 | 0.00 | 01-JAN-00:15 | 1417.08 | 23-JUL-18:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 13.12 | 0.02 | 05-SEP-14:00 | 2564.67 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.22 | 0.00 | 01-JAN-06:30 | 338.75 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 12.90 | 0.00 | 01-JAN-00:15 | 2564.67 | 07-AUG-13:30 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 13.13 | 0.05 | 13-JUL-09:30 | 2575.34 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.22 | 0.00 | 01-JAN-06:30 | 337.38 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 12.91 | 0.00 | 01-JAN-00:15 | 2575.34 | 07-AUG-13:30 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 13.69 | 0.02 | 03-NOV-16:00 | 3452.29 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 1.62 | 0.00 | 03-JAN-10:30 | 1039.60 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 12.08 | 0.00 | 01-JAN-00:15 | 3452.29 | 10-AUG-16:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 9.79 | 0.04 | 10-JUN-20:00 | 2800.21 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 2.84 | 0.00 | 03-JAN-19:00 | 1179.95 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 6.94 | 0.00 | 01-JAN-00:15 | 2800.21 | 23-JUL-17:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 13.48 | 0.00 | 12-JUN-23:45 | 3166.91 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 1.56 | 0.00 | 03-JAN-10:15 | 1026.86 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 11.92 | 0.00 | 01-JAN-00:15 | 3166.91 | 07-AUG-13:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 9.69 | 0.04 | 04-JUN-13:30 | 1987.71 | 20-JUL-17:30 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 2.70 | 0.00 | 03-JAN-18:45 | 1169.96 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 6.99 | 0.00 | 01-JAN-00:15 | 1987.71 | 20-JUL-17:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 8.30 | 0.03 | 06-MAR-02:15 | 1468.98 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.37 | 0.00 | 01-JAN-06:30 | 490.84 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 7.93 | 0.00 | 01-JAN-00:15 | 1468.98 | 23-JUL-18:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 8.30 | 0.01 | 04-JUL-13:30 | 1439.51 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.37 | 0.00 | 01-JAN-06:30 | 490.09 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 7.93 | 0.00 | 01-JAN-00:15 | 1439.51 | 23-JUL-18:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 13.56 | 0.02 | 13-SEP-08:30 | 2602.36 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.23 | 0.00 | 01-JAN-06:30 | 360.31 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 13.33 | 0.00 | 01-JAN-00:15 | 2602.36 | 07-AUG-13:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 13.54 | 0.11 | 13-SEP-08:30 | 2614.00 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.23 | 0.00 | 01-JAN-06:30 | 359.38 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 13.31 | 0.00 | 01-JAN-00:15 | 2614.00 | 07-AUG-13:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 13.77 | 0.02 | 10-DEC-03:45 | 3481.83 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.67 | 0.00 | 03-JAN-10:30 | 1066.70 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 12.10 | 0.00 | 01-JAN-00:15 | 3481.83 | 10-AUG-16:30 |
EnergyTransfer:Zone:M NW APARTMENT | 9.90 | 0.03 | 08-MAR-05:15 | 2841.71 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.88 | 0.00 | 03-JAN-19:00 | 1204.78 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 7.02 | 0.00 | 01-JAN-00:15 | 2841.71 | 23-JUL-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 13.56 | 0.07 | 25-DEC-17:00 | 3220.76 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.62 | 0.00 | 03-JAN-10:15 | 1055.16 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 11.94 | 0.00 | 01-JAN-00:15 | 3220.76 | 07-AUG-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 9.80 | 0.02 | 30-JUN-10:30 | 2026.37 | 20-JUL-17:30 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.73 | 0.00 | 03-JAN-18:45 | 1194.85 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 7.07 | 0.00 | 01-JAN-00:15 | 2026.37 | 20-JUL-17:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 8.49 | 0.01 | 26-DEC-05:30 | 1510.11 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.36 | 0.00 | 01-JAN-06:30 | 497.82 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 8.12 | 0.00 | 01-JAN-00:15 | 1510.11 | 23-JUL-18:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 8.49 | 0.02 | 19-AUG-13:45 | 1480.55 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.36 | 0.00 | 01-JAN-06:30 | 497.06 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 8.12 | 0.00 | 01-JAN-00:15 | 1480.55 | 23-JUL-18:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 13.78 | 0.07 | 05-SEP-14:30 | 2640.11 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.24 | 0.00 | 01-JAN-06:30 | 373.66 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 13.54 | 0.00 | 01-JAN-00:15 | 2640.11 | 07-AUG-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 13.76 | 0.32 | 19-DEC-04:15 | 2651.51 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.24 | 0.00 | 01-JAN-06:30 | 372.84 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 13.52 | 0.00 | 01-JAN-00:15 | 2651.51 | 07-AUG-13:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 13.15 | 0.02 | 21-OCT-10:30 | 3441.80 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 1.98 | 0.00 | 03-JAN-10:30 | 1146.62 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 11.17 | 0.00 | 01-JAN-00:15 | 3441.80 | 10-AUG-16:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 9.76 | 0.08 | 05-DEC-12:30 | 2809.81 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 3.38 | 0.00 | 04-JAN-18:15 | 1285.57 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 6.38 | 0.00 | 01-JAN-00:15 | 2809.81 | 23-JUL-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 12.95 | 0.00 | 02-FEB-02:45 | 3201.93 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 1.93 | 0.00 | 03-JAN-10:30 | 1135.33 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 11.02 | 0.00 | 01-JAN-00:15 | 3201.93 | 07-AUG-13:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 9.71 | 0.02 | 08-JUN-19:45 | 2004.55 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 3.23 | 0.00 | 04-JAN-19:00 | 1275.67 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 6.48 | 0.00 | 01-JAN-00:15 | 2004.55 | 23-JUL-17:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 7.99 | 0.02 | 03-MAY-19:00 | 1476.14 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.52 | 0.00 | 01-JAN-06:30 | 593.53 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.47 | 0.00 | 01-JAN-00:15 | 1476.14 | 23-JUL-18:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 7.99 | 0.02 | 12-AUG-20:15 | 1446.46 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.52 | 0.00 | 01-JAN-06:30 | 601.07 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.47 | 0.00 | 01-JAN-00:15 | 1446.46 | 23-JUL-18:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 12.89 | 0.03 | 28-DEC-23:45 | 2604.41 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.31 | 0.00 | 01-JAN-06:30 | 427.58 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 12.59 | 0.00 | 01-JAN-00:15 | 2604.41 | 07-AUG-13:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 12.87 | 0.10 | 30-NOV-17:30 | 2615.78 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.31 | 0.00 | 01-JAN-06:30 | 427.46 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 12.56 | 0.00 | 01-JAN-00:15 | 2615.78 | 07-AUG-13:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 12.80 | 0.01 | 30-JUN-04:15 | 3426.13 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 2.24 | 0.00 | 03-JAN-19:00 | 1204.59 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 10.56 | 0.00 | 01-JAN-00:15 | 3426.13 | 10-AUG-16:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 9.74 | 0.04 | 31-MAR-02:00 | 2801.12 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 3.74 | 0.00 | 05-JAN-15:30 | 1341.95 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 5.99 | 0.00 | 01-JAN-00:15 | 2801.12 | 23-JUL-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 12.61 | 0.02 | 16-JUN-13:45 | 3202.82 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 2.19 | 0.00 | 03-JAN-10:30 | 1193.58 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 10.42 | 0.00 | 01-JAN-00:15 | 3202.82 | 07-AUG-13:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 9.70 | 0.00 | 04-SEP-13:00 | 2008.47 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 3.59 | 0.00 | 10-JAN-17:15 | 1332.17 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 6.10 | 0.00 | 01-JAN-00:15 | 2008.47 | 23-JUL-17:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 7.70 | 0.01 | 16-JUL-14:15 | 1465.26 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.64 | 0.00 | 01-JAN-07:00 | 720.79 | 09-MAR-13:15 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 7.06 | 0.00 | 01-JAN-00:15 | 1465.26 | 23-JUL-18:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 7.70 | 0.00 | 27-AUG-14:00 | 1435.69 | 23-JUL-18:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.64 | 0.00 | 01-JAN-07:00 | 731.40 | 03-OCT-18:45 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 7.06 | 0.00 | 01-JAN-00:15 | 1435.69 | 23-JUL-18:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 12.35 | 0.04 | 09-SEP-10:15 | 2593.60 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.37 | 0.00 | 01-JAN-06:30 | 469.59 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 11.97 | 0.00 | 01-JAN-00:15 | 2593.60 | 07-AUG-13:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 12.33 | 0.01 | 23-DEC-08:30 | 2604.95 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.38 | 0.00 | 01-JAN-06:30 | 469.48 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 11.95 | 0.00 | 01-JAN-00:15 | 2604.95 | 07-AUG-13:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 12.55 | 0.01 | 04-FEB-20:45 | 3422.02 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 2.52 | 0.00 | 04-JAN-18:15 | 1260.60 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 10.03 | 0.00 | 01-JAN-00:15 | 3422.02 | 10-AUG-16:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 9.79 | 0.04 | 24-FEB-09:45 | 2801.52 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 4.11 | 0.00 | 07-JAN-15:45 | 1395.85 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 5.68 | 0.00 | 01-JAN-00:15 | 2801.52 | 23-JUL-17:00 |
EnergyTransfer:Zone:F8 SE APARTMENT | 12.37 | 0.02 | 20-OCT-18:15 | 3209.72 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 2.47 | 0.00 | 03-JAN-10:30 | 1249.76 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 9.90 | 0.00 | 01-JAN-00:15 | 3209.72 | 07-AUG-13:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 9.77 | 0.04 | 11-DEC-17:00 | 2018.98 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 3.97 | 0.00 | 10-JAN-17:15 | 1386.19 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 5.80 | 0.00 | 01-JAN-00:15 | 2018.98 | 23-JUL-17:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 7.50 | 0.08 | 08-DEC-14:15 | 1468.75 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.79 | 0.00 | 01-JAN-06:45 | 849.05 | 03-OCT-18:45 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 6.71 | 0.00 | 01-JAN-00:15 | 1468.75 | 23-JUL-18:30 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 7.49 | 0.00 | 17-JAN-11:15 | 1439.42 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.79 | 0.00 | 01-JAN-06:45 | 887.83 | 03-OCT-18:45 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 6.71 | 0.00 | 01-JAN-00:15 | 1439.42 | 23-JUL-18:30 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 11.86 | 0.11 | 13-APR-12:45 | 2594.42 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.45 | 0.00 | 01-JAN-06:45 | 514.00 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 11.41 | 0.00 | 01-JAN-00:15 | 2594.42 | 07-AUG-13:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 11.84 | 0.01 | 13-MAY-12:00 | 2605.78 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.45 | 0.00 | 01-JAN-06:45 | 513.92 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 11.39 | 0.00 | 01-JAN-00:15 | 2605.78 | 07-AUG-13:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 12.53 | 0.01 | 24-JUN-01:15 | 3499.14 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 3.15 | 0.00 | 05-JAN-09:45 | 1400.15 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 9.38 | 0.00 | 01-JAN-00:15 | 3499.14 | 10-AUG-16:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 10.28 | 0.01 | 18-MAR-07:45 | 2850.22 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 4.95 | 0.00 | 07-JAN-16:00 | 1526.92 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 5.33 | 0.00 | 01-JAN-00:15 | 2850.22 | 23-JUL-17:00 |
EnergyTransfer:Zone:F9 SE APARTMENT | 12.34 | 0.01 | 06-NOV-11:30 | 3250.09 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 3.09 | 0.00 | 05-JAN-09:00 | 1389.25 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 9.25 | 0.00 | 01-JAN-00:15 | 3250.09 | 07-AUG-13:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 10.28 | 0.01 | 19-SEP-17:00 | 2071.58 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 4.79 | 0.00 | 10-JAN-18:15 | 1517.82 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 5.49 | 0.00 | 01-JAN-00:15 | 2071.58 | 23-JUL-17:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 7.37 | 0.02 | 18-APR-03:45 | 1531.00 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 1.20 | 0.00 | 01-JAN-11:00 | 1018.70 | 03-OCT-18:45 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.17 | 0.00 | 01-JAN-00:15 | 1531.00 | 23-JUL-17:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 7.37 | 0.00 | 01-JUL-15:30 | 1512.45 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 1.20 | 0.00 | 01-JAN-11:00 | 1050.13 | 03-OCT-18:45 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.17 | 0.00 | 01-JAN-00:15 | 1512.45 | 23-JUL-18:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 11.25 | 0.02 | 20-SEP-12:00 | 2639.80 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.66 | 0.00 | 01-JAN-10:15 | 620.95 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 10.60 | 0.00 | 01-JAN-00:15 | 2639.80 | 07-AUG-13:30 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 11.24 | 0.08 | 16-JUL-22:00 | 2652.49 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.66 | 0.00 | 01-JAN-10:15 | 620.92 | 26-DEC-14:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 10.58 | 0.00 | 01-JAN-00:15 | 2652.49 | 07-AUG-13:30 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 15.68 | 0.01 | 05-MAY-02:30 | 4214.05 | 10-AUG-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 6.87 | 0.00 | 05-JAN-13:15 | 2065.84 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 8.81 | 0.00 | 01-JAN-00:15 | 4214.05 | 10-AUG-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 13.58 | 0.00 | 04-AUG-05:45 | 3377.90 | 23-JUL-17:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.61 | 0.00 | 07-JAN-15:45 | 2129.45 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 4.96 | 0.00 | 01-JAN-00:15 | 3377.90 | 23-JUL-17:00 |
EnergyTransfer:Zone:T SE APARTMENT | 15.18 | 0.00 | 14-APR-19:15 | 3809.79 | 10-AUG-12:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 6.66 | 0.00 | 03-JAN-10:30 | 2061.37 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 8.52 | 0.00 | 01-JAN-00:15 | 3809.79 | 10-AUG-12:30 |
EnergyTransfer:Zone:T NE APARTMENT | 13.36 | 0.01 | 26-OCT-20:15 | 2443.70 | 20-JUL-17:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 8.36 | 0.00 | 11-JAN-18:15 | 2126.16 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 5.01 | 0.00 | 01-JAN-00:15 | 2443.70 | 20-JUL-17:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 8.84 | 0.01 | 03-SEP-17:45 | 1961.58 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.74 | 0.00 | 03-JAN-18:45 | 1340.67 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 5.10 | 0.00 | 01-JAN-00:15 | 1961.58 | 23-JUL-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 8.82 | 0.00 | 25-OCT-04:00 | 1957.57 | 23-JUL-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.75 | 0.00 | 03-JAN-18:45 | 1340.31 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 5.08 | 0.00 | 01-JAN-00:15 | 1957.57 | 23-JUL-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 11.20 | 0.01 | 26-JUN-03:30 | 3355.34 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.54 | 0.00 | 03-JAN-10:15 | 1263.95 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 8.66 | 0.00 | 01-JAN-00:15 | 3355.34 | 07-AUG-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 11.20 | 0.00 | 31-MAY-01:00 | 3365.37 | 07-AUG-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.54 | 0.00 | 03-JAN-10:15 | 1263.20 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 8.65 | 0.00 | 01-JAN-00:15 | 3365.37 | 07-AUG-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1099.73 | 507.56 | 12-AUG-01:15 | 147961.05 | 19-FEB-06:15 |
WaterSystems:EnergyTransfer | 889.32 | 507.56 | 12-AUG-01:15 | 57926.91 | 08-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 889.32 | 507.56 | 12-AUG-01:15 | 57926.91 | 08-FEB-08:00 |
EnergyTransfer:HVAC | 868.23 | 0.00 | 11-JAN-19:30 | 218617.46 | 29-AUG-15:15 |
CoolingCoils:EnergyTransfer | 553.03 | 0.00 | 01-JAN-00:15 | 218617.46 | 29-AUG-15:15 |
HeatingCoils:EnergyTransfer | 315.20 | 0.00 | 11-JAN-19:30 | 122744.99 | 19-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 241.68 | 0.00 | 11-JAN-19:30 | 94750.14 | 19-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 241.68 | 0.00 | 11-JAN-19:30 | 94750.14 | 19-FEB-06:00 |
Boilers:EnergyTransfer | 210.41 | 0.00 | 11-JAN-14:00 | 92461.78 | 19-FEB-06:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 2.568 | -6.057 | 0.000 | 0.000 | 3.835 | 2.413 | 12.213 | 16.602 | 0.000 | 0.047 | 0.000 | 0.000 | -10.346 | 0.000 | -7.119 | -14.157 |
G NW APARTMENT | 3.884 | -3.869 | 0.000 | 0.000 | 3.891 | 2.413 | 12.213 | 8.261 | 0.000 | 0.047 | 0.000 | 0.000 | -10.359 | 0.000 | -6.566 | -9.914 |
OFFICE | 2.652 | -12.187 | 0.000 | 0.000 | 0.525 | 21.954 | 7.547 | 16.024 | 0.000 | 0.014 | 0.000 | 0.000 | -10.283 | 0.000 | -3.079 | -23.167 |
G NE APARTMENT | 3.785 | -4.029 | 0.000 | 0.000 | 3.912 | 2.413 | 12.213 | 7.735 | 0.000 | 0.047 | 0.000 | 0.000 | -10.109 | 0.000 | -6.514 | -9.454 |
G N1 APARTMENT | 1.388 | -4.601 | 0.000 | 0.000 | 3.914 | 2.413 | 12.213 | 2.805 | 0.000 | 0.041 | 0.000 | 0.000 | -6.373 | 0.000 | -5.027 | -6.773 |
G N2 APARTMENT | 1.392 | -4.617 | 0.000 | 0.000 | 3.916 | 2.413 | 12.213 | 2.805 | 0.000 | 0.041 | 0.000 | 0.000 | -6.367 | 0.000 | -5.022 | -6.774 |
G S1 APARTMENT | 0.560 | -6.747 | 0.000 | 0.000 | 3.824 | 2.413 | 12.213 | 11.243 | 0.000 | 0.042 | 0.000 | 0.000 | -6.348 | 0.000 | -5.728 | -11.472 |
G S2 APARTMENT | 0.534 | -6.842 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 11.230 | 0.000 | 0.042 | 0.000 | 0.000 | -6.359 | 0.000 | -5.763 | -11.287 |
F2 SW APARTMENT | 1.637 | -10.875 | 0.000 | 0.000 | 3.741 | 2.413 | 12.213 | 15.976 | 0.000 | 0.059 | 0.000 | 0.000 | -11.229 | 0.000 | -9.359 | -4.577 |
F2 NW APARTMENT | 2.883 | -6.159 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 7.798 | 0.000 | 0.059 | 0.000 | 0.000 | -11.101 | 0.000 | -8.769 | -3.157 |
F2 SE APARTMENT | 1.399 | -11.395 | 0.000 | 0.000 | 3.736 | 2.413 | 12.213 | 15.442 | 0.000 | 0.059 | 0.000 | 0.000 | -11.110 | 0.000 | -9.433 | -3.325 |
F2 NE APARTMENT | 2.733 | -6.228 | 0.000 | 0.000 | 3.843 | 2.413 | 12.213 | 7.287 | 0.000 | 0.059 | 0.000 | 0.000 | -10.817 | 0.000 | -8.696 | -2.807 |
F2 N1 APARTMENT | 0.463 | -6.865 | 0.000 | 0.000 | 3.833 | 2.413 | 12.213 | 2.547 | 0.000 | 0.050 | 0.000 | 0.000 | -6.894 | 0.000 | -6.677 | -1.083 |
F2 N2 APARTMENT | 0.461 | -6.870 | 0.000 | 0.000 | 3.835 | 2.413 | 12.213 | 2.548 | 0.000 | 0.050 | 0.000 | 0.000 | -6.887 | 0.000 | -6.667 | -1.096 |
F2 S1 APARTMENT | 0.250 | -11.368 | 0.000 | 0.000 | 3.710 | 2.413 | 12.213 | 10.847 | 0.000 | 0.052 | 0.000 | 0.000 | -6.925 | 0.000 | -7.457 | -3.734 |
F2 S2 APARTMENT | 0.251 | -11.433 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 10.843 | 0.000 | 0.052 | 0.000 | 0.000 | -6.931 | 0.000 | -7.466 | -3.649 |
F3 SW APARTMENT | 1.546 | -11.914 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 15.739 | 0.000 | 0.072 | 0.000 | 0.000 | -11.503 | 0.000 | -10.505 | -1.786 |
F3 NW APARTMENT | 2.734 | -6.808 | 0.000 | 0.000 | 3.805 | 2.413 | 12.213 | 7.630 | 0.000 | 0.071 | 0.000 | 0.000 | -11.359 | 0.000 | -9.910 | -0.790 |
F3 SE APARTMENT | 1.457 | -11.862 | 0.000 | 0.000 | 3.729 | 2.413 | 12.213 | 15.247 | 0.000 | 0.072 | 0.000 | 0.000 | -11.312 | 0.000 | -10.518 | -1.439 |
F3 NE APARTMENT | 2.586 | -6.852 | 0.000 | 0.000 | 3.826 | 2.413 | 12.213 | 7.130 | 0.000 | 0.071 | 0.000 | 0.000 | -11.067 | 0.000 | -9.829 | -0.492 |
F3 N1 APARTMENT | 0.364 | -7.678 | 0.000 | 0.000 | 3.807 | 2.413 | 12.213 | 2.461 | 0.000 | 0.061 | 0.959 | 0.000 | -7.080 | 0.000 | -7.519 | -0.000 |
F3 N2 APARTMENT | 0.364 | -7.680 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 2.462 | 0.000 | 0.060 | 0.940 | 0.000 | -7.072 | 0.000 | -7.509 | -0.000 |
F3 S1 APARTMENT | 0.219 | -12.904 | 0.000 | 0.000 | 3.684 | 2.413 | 12.213 | 10.691 | 0.000 | 0.063 | 0.000 | 0.000 | -7.124 | 0.000 | -8.290 | -0.964 |
F3 S2 APARTMENT | 0.220 | -12.910 | 0.000 | 0.000 | 3.684 | 2.413 | 12.213 | 10.689 | 0.000 | 0.063 | 0.000 | 0.000 | -7.125 | 0.000 | -8.293 | -0.954 |
F4 SW APARTMENT | 1.616 | -12.075 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 15.598 | 0.000 | 0.077 | 0.000 | 0.000 | -11.632 | 0.000 | -11.052 | -0.880 |
F4 NW APARTMENT | 2.844 | -6.944 | 0.000 | 0.000 | 3.801 | 2.413 | 12.213 | 7.538 | 0.000 | 0.076 | 0.016 | 0.000 | -11.491 | 0.000 | -10.466 | -0.000 |
F4 SE APARTMENT | 1.559 | -11.923 | 0.000 | 0.000 | 3.729 | 2.413 | 12.213 | 15.120 | 0.000 | 0.077 | 0.000 | 0.000 | -11.424 | 0.000 | -11.052 | -0.712 |
F4 NE APARTMENT | 2.696 | -6.994 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 7.044 | 0.000 | 0.076 | 0.310 | 0.000 | -11.196 | 0.000 | -10.384 | -0.001 |
F4 N1 APARTMENT | 0.372 | -7.927 | 0.000 | 0.000 | 3.798 | 2.413 | 12.213 | 2.417 | 0.000 | 0.064 | 1.682 | 0.000 | -7.177 | 0.000 | -7.854 | -0.000 |
F4 N2 APARTMENT | 0.371 | -7.926 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 2.418 | 0.000 | 0.064 | 1.661 | 0.000 | -7.169 | 0.000 | -7.844 | -0.000 |
F4 S1 APARTMENT | 0.229 | -13.326 | 0.000 | 0.000 | 3.678 | 2.413 | 12.213 | 10.599 | 0.000 | 0.067 | 0.000 | 0.000 | -7.217 | 0.000 | -8.598 | -0.058 |
F4 S2 APARTMENT | 0.232 | -13.311 | 0.000 | 0.000 | 3.678 | 2.413 | 12.213 | 10.598 | 0.000 | 0.067 | 0.001 | 0.000 | -7.216 | 0.000 | -8.600 | -0.073 |
M SW APARTMENT | 1.670 | -12.105 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 15.490 | 0.000 | 0.081 | 0.001 | 0.000 | -11.732 | 0.000 | -11.750 | -0.002 |
M NW APARTMENT | 2.880 | -7.015 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 7.470 | 0.000 | 0.080 | 0.895 | 0.000 | -11.593 | 0.000 | -11.142 | -0.000 |
M SE APARTMENT | 1.617 | -11.938 | 0.000 | 0.000 | 3.729 | 2.413 | 12.213 | 15.019 | 0.000 | 0.081 | 0.131 | 0.000 | -11.519 | 0.000 | -11.746 | -0.000 |
M NE APARTMENT | 2.729 | -7.075 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 6.982 | 0.000 | 0.080 | 1.189 | 0.000 | -11.295 | 0.000 | -11.055 | -0.000 |
M N1 APARTMENT | 0.364 | -8.125 | 0.000 | 0.000 | 3.793 | 2.413 | 12.213 | 2.387 | 0.000 | 0.068 | 2.471 | 0.000 | -7.249 | 0.000 | -8.334 | -0.000 |
M N2 APARTMENT | 0.363 | -8.123 | 0.000 | 0.000 | 3.796 | 2.413 | 12.213 | 2.388 | 0.000 | 0.067 | 2.449 | 0.000 | -7.241 | 0.000 | -8.324 | -0.000 |
M S1 APARTMENT | 0.241 | -13.540 | 0.000 | 0.000 | 3.676 | 2.413 | 12.213 | 10.529 | 0.000 | 0.070 | 0.778 | 0.000 | -7.287 | 0.000 | -9.093 | -0.000 |
M S2 APARTMENT | 0.244 | -13.519 | 0.000 | 0.000 | 3.676 | 2.413 | 12.213 | 10.528 | 0.000 | 0.070 | 0.755 | 0.000 | -7.285 | 0.000 | -9.095 | -0.000 |
F6 SW APARTMENT | 1.984 | -11.169 | 0.000 | 0.000 | 3.734 | 2.413 | 12.213 | 15.441 | 0.000 | 0.085 | 0.000 | 0.000 | -11.724 | 0.000 | -12.280 | -0.698 |
F6 NW APARTMENT | 3.376 | -6.385 | 0.000 | 0.000 | 3.812 | 2.413 | 12.213 | 7.457 | 0.000 | 0.083 | 0.229 | 0.000 | -11.582 | 0.000 | -11.616 | -0.001 |
F6 SE APARTMENT | 1.933 | -11.015 | 0.000 | 0.000 | 3.742 | 2.413 | 12.213 | 14.976 | 0.000 | 0.085 | 0.000 | 0.000 | -11.509 | 0.000 | -12.273 | -0.565 |
F6 NE APARTMENT | 3.228 | -6.478 | 0.000 | 0.000 | 3.833 | 2.413 | 12.213 | 6.975 | 0.000 | 0.084 | 0.537 | 0.000 | -11.283 | 0.000 | -11.522 | -0.000 |
F6 N1 APARTMENT | 0.516 | -7.470 | 0.000 | 0.000 | 3.807 | 2.413 | 12.213 | 2.389 | 0.000 | 0.070 | 1.926 | 0.000 | -7.238 | 0.000 | -8.626 | -0.000 |
F6 N2 APARTMENT | 0.517 | -7.472 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 2.390 | 0.000 | 0.070 | 1.905 | 0.000 | -7.230 | 0.000 | -8.615 | -0.000 |
F6 S1 APARTMENT | 0.308 | -12.585 | 0.000 | 0.000 | 3.687 | 2.413 | 12.213 | 10.497 | 0.000 | 0.073 | 0.124 | 0.000 | -7.283 | 0.000 | -9.446 | -0.000 |
F6 S2 APARTMENT | 0.311 | -12.563 | 0.000 | 0.000 | 3.688 | 2.413 | 12.213 | 10.496 | 0.000 | 0.073 | 0.100 | 0.000 | -7.281 | 0.000 | -9.448 | -0.000 |
F7 SW APARTMENT | 2.241 | -10.558 | 0.000 | 0.000 | 3.743 | 2.413 | 12.213 | 15.394 | 0.000 | 0.087 | 0.000 | 0.000 | -11.728 | 0.000 | -12.730 | -1.076 |
F7 NW APARTMENT | 3.742 | -5.995 | 0.000 | 0.000 | 3.822 | 2.413 | 12.213 | 7.441 | 0.000 | 0.086 | 0.000 | 0.000 | -11.584 | 0.000 | -12.024 | -0.114 |
F7 SE APARTMENT | 2.191 | -10.417 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 14.934 | 0.000 | 0.087 | 0.000 | 0.000 | -11.512 | 0.000 | -12.718 | -0.943 |
F7 NE APARTMENT | 3.594 | -6.104 | 0.000 | 0.000 | 3.843 | 2.413 | 12.213 | 6.964 | 0.000 | 0.086 | 0.198 | 0.000 | -11.285 | 0.000 | -11.922 | -0.000 |
F7 N1 APARTMENT | 0.639 | -7.060 | 0.000 | 0.000 | 3.818 | 2.413 | 12.213 | 2.388 | 0.000 | 0.072 | 1.626 | 0.000 | -7.234 | 0.000 | -8.876 | -0.000 |
F7 N2 APARTMENT | 0.639 | -7.060 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 2.389 | 0.000 | 0.072 | 1.604 | 0.000 | -7.226 | 0.000 | -8.864 | -0.000 |
F7 S1 APARTMENT | 0.374 | -11.971 | 0.000 | 0.000 | 3.697 | 2.413 | 12.213 | 10.466 | 0.000 | 0.075 | 0.001 | 0.000 | -7.285 | 0.000 | -9.742 | -0.241 |
F7 S2 APARTMENT | 0.377 | -11.950 | 0.000 | 0.000 | 3.697 | 2.413 | 12.213 | 10.465 | 0.000 | 0.075 | 0.000 | 0.000 | -7.283 | 0.000 | -9.743 | -0.264 |
F8 SW APARTMENT | 2.519 | -10.029 | 0.000 | 0.000 | 3.752 | 2.413 | 12.213 | 15.355 | 0.000 | 0.092 | 0.000 | 0.000 | -11.727 | 0.000 | -13.169 | -1.419 |
F8 NW APARTMENT | 4.115 | -5.677 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 7.427 | 0.000 | 0.091 | 0.000 | 0.000 | -11.587 | 0.000 | -12.425 | -0.399 |
F8 SE APARTMENT | 2.469 | -9.898 | 0.000 | 0.000 | 3.760 | 2.413 | 12.213 | 14.898 | 0.000 | 0.092 | 0.000 | 0.000 | -11.511 | 0.000 | -13.155 | -1.282 |
F8 NE APARTMENT | 3.968 | -5.799 | 0.000 | 0.000 | 3.851 | 2.413 | 12.213 | 6.955 | 0.000 | 0.091 | 0.000 | 0.000 | -11.288 | 0.000 | -12.318 | -0.086 |
F8 N1 APARTMENT | 0.789 | -6.709 | 0.000 | 0.000 | 3.828 | 2.413 | 12.213 | 2.387 | 0.000 | 0.076 | 1.367 | 0.000 | -7.230 | 0.000 | -9.134 | -0.000 |
F8 N2 APARTMENT | 0.788 | -6.706 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 2.388 | 0.000 | 0.076 | 1.342 | 0.000 | -7.222 | 0.000 | -9.122 | -0.000 |
F8 S1 APARTMENT | 0.451 | -11.411 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 10.441 | 0.000 | 0.079 | 0.001 | 0.000 | -7.281 | 0.000 | -10.041 | -0.572 |
F8 S2 APARTMENT | 0.453 | -11.390 | 0.000 | 0.000 | 3.708 | 2.413 | 12.213 | 10.440 | 0.000 | 0.079 | 0.000 | 0.000 | -7.279 | 0.000 | -10.042 | -0.596 |
F9 SW APARTMENT | 3.147 | -9.382 | 0.000 | 0.000 | 3.765 | 2.413 | 12.213 | 15.344 | 0.000 | 0.096 | 0.000 | 0.000 | -11.683 | 0.000 | -13.529 | -2.383 |
F9 NW APARTMENT | 4.949 | -5.331 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 7.430 | 0.000 | 0.094 | 0.000 | 0.000 | -11.562 | 0.000 | -12.762 | -1.283 |
F9 SE APARTMENT | 3.086 | -9.251 | 0.000 | 0.000 | 3.773 | 2.413 | 12.213 | 14.891 | 0.000 | 0.096 | 0.000 | 0.000 | -11.467 | 0.000 | -13.517 | -2.236 |
F9 NE APARTMENT | 4.790 | -5.488 | 0.000 | 0.000 | 3.861 | 2.413 | 12.213 | 6.964 | 0.000 | 0.094 | 0.000 | 0.000 | -11.263 | 0.000 | -12.653 | -0.931 |
F9 N1 APARTMENT | 1.200 | -6.172 | 0.000 | 0.000 | 3.839 | 2.413 | 12.213 | 2.396 | 0.000 | 0.080 | 0.585 | 0.000 | -7.204 | 0.000 | -9.349 | -0.000 |
F9 N2 APARTMENT | 1.200 | -6.173 | 0.000 | 0.000 | 3.841 | 2.413 | 12.213 | 2.397 | 0.000 | 0.079 | 0.564 | 0.000 | -7.196 | 0.000 | -9.338 | -0.000 |
F9 S1 APARTMENT | 0.656 | -10.599 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 10.436 | 0.000 | 0.083 | 0.000 | 0.000 | -7.243 | 0.000 | -10.277 | -1.407 |
F9 S2 APARTMENT | 0.659 | -10.577 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 10.435 | 0.000 | 0.083 | 0.000 | 0.000 | -7.241 | 0.000 | -10.279 | -1.430 |
T SW APARTMENT | 6.871 | -8.810 | 0.000 | 0.000 | 3.813 | 2.413 | 12.213 | 15.156 | 0.000 | 0.097 | 0.000 | 0.000 | -11.139 | 0.000 | -13.788 | -6.826 |
T NW APARTMENT | 8.614 | -4.962 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 7.282 | 0.000 | 0.096 | 0.000 | 0.000 | -11.102 | 0.000 | -13.114 | -5.312 |
T SE APARTMENT | 6.663 | -8.521 | 0.000 | 0.000 | 3.823 | 2.413 | 12.213 | 14.731 | 0.000 | 0.097 | 0.000 | 0.000 | -10.948 | 0.000 | -13.778 | -6.692 |
T NE APARTMENT | 8.356 | -5.006 | 0.000 | 0.000 | 3.897 | 2.413 | 12.213 | 6.847 | 0.000 | 0.096 | 0.000 | 0.000 | -10.835 | 0.000 | -13.011 | -4.969 |
T N1 APARTMENT | 3.737 | -5.104 | 0.000 | 0.000 | 3.877 | 2.413 | 12.213 | 2.357 | 0.000 | 0.081 | 0.000 | 0.000 | -6.891 | 0.000 | -9.574 | -3.109 |
T N2 APARTMENT | 3.745 | -5.076 | 0.000 | 0.000 | 3.879 | 2.413 | 12.213 | 2.356 | 0.000 | 0.082 | 0.000 | 0.000 | -6.884 | 0.000 | -9.573 | -3.155 |
T S1 APARTMENT | 2.538 | -8.664 | 0.000 | 0.000 | 3.779 | 2.413 | 12.213 | 10.345 | 0.000 | 0.084 | 0.000 | 0.000 | -6.931 | 0.000 | -10.456 | -5.321 |
T S2 APARTMENT | 2.545 | -8.653 | 0.000 | 0.000 | 3.779 | 2.413 | 12.213 | 10.343 | 0.000 | 0.084 | 0.000 | 0.000 | -6.927 | 0.000 | -10.459 | -5.338 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 3.431 | 0.000 | 0.124 | 21.314 | 0.000 | -2.389 | 0.000 | -41.009 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.564 | 0.000 | 0.001 | 0.000 | 0.000 | -1.453 | 0.000 | -0.840 | -17.802 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.523 | 0.000 | 0.001 | 0.000 | 0.000 | -1.519 | 0.000 | -1.027 | -17.508 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.500 | 0.000 | 0.001 | 0.000 | 0.000 | -1.552 | 0.000 | -1.162 | -17.316 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.473 | 0.000 | 0.001 | 0.000 | 0.000 | -1.599 | 0.000 | -1.324 | -35.610 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.483 | 0.000 | 0.001 | 0.000 | 0.000 | -1.566 | 0.000 | -1.347 | -17.101 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.484 | 0.000 | 0.001 | 0.000 | 0.000 | -1.556 | 0.000 | -1.409 | -17.050 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.482 | 0.000 | 0.001 | 0.000 | 0.000 | -1.553 | 0.000 | -1.469 | -16.991 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.483 | 0.000 | 0.001 | 0.000 | 0.000 | -1.545 | 0.000 | -1.519 | -16.949 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.445 | 0.000 | 0.000 | 0.000 | 0.000 | -1.501 | 0.000 | -1.606 | -24.804 |
Total Facility | 160.634 | -692.253 | 0.000 | 0.000 | 299.629 | 416.414 | 980.287 | 732.099 | 0.000 | 5.957 | 47.658 | 0.000 | -749.947 | 0.000 | -836.120 | -364.358 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 10-AUG-16:23 | 0.00 | -2659.82 | 0.00 | 0.00 | 84.65 | 144.04 | 588.62 | 3251.96 | 0.00 | 29.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1439.31 |
G NW APARTMENT | 23-JUL-17:30 | 0.00 | -2125.05 | 0.00 | 0.00 | 141.68 | 194.45 | 588.62 | 2648.46 | 0.00 | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1674.49 |
OFFICE | 29-AUG-12:30 | 0.00 | -3299.27 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3749.09 | 0.00 | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2709.76 |
G NE APARTMENT | 24-JUL-10:45 | 0.00 | -1387.50 | 0.00 | 0.00 | 40.73 | 28.81 | 412.03 | 1608.95 | 0.00 | 155.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.02 |
G N1 APARTMENT | 23-JUL-18:30 | 0.00 | -975.82 | 0.00 | 0.00 | 141.13 | 230.46 | 547.42 | 682.04 | 0.00 | 89.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -714.77 |
G N2 APARTMENT | 23-JUL-18:30 | 0.00 | -945.15 | 0.00 | 0.00 | 140.89 | 230.46 | 547.42 | 682.21 | 0.00 | 86.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -742.41 |
G S1 APARTMENT | 07-AUG-13:30 | 0.00 | -1882.07 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2468.52 | 0.00 | 338.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1377.07 |
G S2 APARTMENT | 07-AUG-13:30 | 0.00 | -1920.22 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2467.71 | 0.00 | 338.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.11 |
F2 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3421.11 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3233.24 | 0.00 | 42.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -672.44 |
F2 NW APARTMENT | 23-JUL-17:15 | 0.00 | -2701.39 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2621.09 | 0.00 | 320.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1164.71 |
F2 SE APARTMENT | 10-AUG-12:30 | 0.00 | -3146.55 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3055.40 | 0.00 | 248.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -615.71 |
F2 NE APARTMENT | 24-JUL-10:15 | 0.00 | -1906.48 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 1867.93 | 0.00 | 47.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -490.61 |
F2 N1 APARTMENT | 23-JUL-18:30 | 0.00 | -1383.54 | 0.00 | 0.00 | 141.74 | 230.46 | 547.42 | 663.36 | 0.00 | 126.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.95 |
F2 N2 APARTMENT | 23-JUL-18:30 | 0.00 | -1354.43 | 0.00 | 0.00 | 141.54 | 230.46 | 547.42 | 663.33 | 0.00 | 123.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.40 |
F2 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2466.53 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2422.02 | 0.00 | 437.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -844.71 |
F2 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2481.11 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2421.76 | 0.00 | 437.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -829.88 |
F3 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3442.67 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3224.12 | 0.00 | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -649.51 |
F3 NW APARTMENT | 23-JUL-17:15 | 0.00 | -2771.57 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2600.44 | 0.00 | 355.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1109.37 |
F3 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3125.89 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2733.63 | 0.00 | 517.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -576.90 |
F3 NE APARTMENT | 20-JUL-17:30 | 0.00 | -1976.98 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 816.70 | 0.00 | 396.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -160.89 |
F3 N1 APARTMENT | 23-JUL-18:15 | 0.00 | -1446.66 | 0.00 | 0.00 | 141.57 | 230.46 | 547.42 | 568.29 | 0.00 | 175.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -216.63 |
F3 N2 APARTMENT | 23-JUL-18:15 | 0.00 | -1417.32 | 0.00 | 0.00 | 141.35 | 230.46 | 547.42 | 568.23 | 0.00 | 171.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -242.11 |
F3 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2564.48 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2398.60 | 0.00 | 497.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -783.75 |
F3 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2575.14 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2398.40 | 0.00 | 497.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.89 |
F4 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3452.45 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3217.16 | 0.00 | 56.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -638.56 |
F4 NW APARTMENT | 23-JUL-17:15 | 0.00 | -2799.05 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2586.50 | 0.00 | 382.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1094.54 |
F4 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3166.75 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2716.09 | 0.00 | 563.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -565.42 |
F4 NE APARTMENT | 20-JUL-17:30 | 0.00 | -1989.58 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 813.35 | 0.00 | 422.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -170.96 |
F4 N1 APARTMENT | 23-JUL-18:15 | 0.00 | -1469.23 | 0.00 | 0.00 | 141.44 | 230.46 | 547.42 | 563.67 | 0.00 | 187.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.07 |
F4 N2 APARTMENT | 23-JUL-18:15 | 0.00 | -1439.76 | 0.00 | 0.00 | 141.22 | 230.46 | 547.42 | 563.61 | 0.00 | 183.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -226.41 |
F4 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2602.18 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2382.61 | 0.00 | 540.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.35 |
F4 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2613.82 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2382.41 | 0.00 | 540.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -761.70 |
M SW APARTMENT | 10-AUG-16:30 | 0.00 | -3481.99 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3210.54 | 0.00 | 61.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.12 |
M NW APARTMENT | 23-JUL-17:15 | 0.00 | -2840.50 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2575.02 | 0.00 | 403.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1062.93 |
M SE APARTMENT | 07-AUG-13:30 | 0.00 | -3220.62 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2701.84 | 0.00 | 601.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -534.73 |
M NE APARTMENT | 20-JUL-17:30 | 0.00 | -2028.58 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 810.11 | 0.00 | 444.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151.26 |
M N1 APARTMENT | 23-JUL-18:15 | 0.00 | -1510.38 | 0.00 | 0.00 | 141.41 | 230.46 | 547.42 | 559.78 | 0.00 | 197.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -166.30 |
M N2 APARTMENT | 23-JUL-18:15 | 0.00 | -1480.81 | 0.00 | 0.00 | 141.20 | 230.46 | 547.42 | 559.71 | 0.00 | 193.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -191.53 |
M S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2639.95 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2369.88 | 0.00 | 573.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -755.52 |
M S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2651.34 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2369.69 | 0.00 | 573.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -744.10 |
F6 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3441.95 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3206.47 | 0.00 | 65.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -647.08 |
F6 NW APARTMENT | 23-JUL-17:15 | 0.00 | -2808.57 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2567.53 | 0.00 | 421.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1105.06 |
F6 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3201.80 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2692.03 | 0.00 | 632.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.78 |
F6 NE APARTMENT | 23-JUL-17:00 | 0.00 | -2003.48 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 436.90 | 0.00 | 496.55 | 252.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 23-JUL-18:15 | 0.00 | -1476.41 | 0.00 | 0.00 | 141.34 | 230.46 | 547.42 | 557.82 | 0.00 | 204.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.32 |
F6 N2 APARTMENT | 23-JUL-18:15 | 0.00 | -1446.73 | 0.00 | 0.00 | 141.13 | 230.46 | 547.42 | 557.75 | 0.00 | 200.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.39 |
F6 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2604.26 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2360.69 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -808.54 |
F6 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2615.62 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2360.49 | 0.00 | 600.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -797.14 |
F7 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3426.28 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3202.24 | 0.00 | 68.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -662.03 |
F7 NW APARTMENT | 23-JUL-17:15 | 0.00 | -2799.86 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2560.52 | 0.00 | 436.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.78 |
F7 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3202.70 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2683.12 | 0.00 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -591.34 |
F7 NE APARTMENT | 23-JUL-17:00 | 0.00 | -2007.37 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 437.07 | 0.00 | 515.22 | 237.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 23-JUL-18:15 | 0.00 | -1465.54 | 0.00 | 0.00 | 141.33 | 230.46 | 547.42 | 555.79 | 0.00 | 210.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -220.24 |
F7 N2 APARTMENT | 23-JUL-18:15 | 0.00 | -1435.96 | 0.00 | 0.00 | 141.11 | 230.46 | 547.42 | 555.72 | 0.00 | 206.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -245.00 |
F7 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2593.45 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2352.56 | 0.00 | 622.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.01 |
F7 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2604.81 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2352.36 | 0.00 | 622.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.60 |
F8 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3422.17 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3198.10 | 0.00 | 71.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -665.12 |
F8 NW APARTMENT | 23-JUL-17:00 | 0.00 | -2800.07 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2584.17 | 0.00 | 531.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1132.90 |
F8 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3209.60 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2675.15 | 0.00 | 681.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -599.23 |
F8 NE APARTMENT | 23-JUL-17:00 | 0.00 | -2017.85 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 436.84 | 0.00 | 531.37 | 232.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 23-JUL-18:30 | 0.00 | -1468.89 | 0.00 | 0.00 | 141.53 | 230.46 | 547.42 | 645.47 | 0.00 | 173.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.62 |
F8 N2 APARTMENT | 23-JUL-18:30 | 0.00 | -1439.55 | 0.00 | 0.00 | 141.32 | 230.46 | 547.42 | 645.40 | 0.00 | 168.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -293.25 |
F8 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2594.28 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2345.35 | 0.00 | 642.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -846.13 |
F8 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2605.65 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2345.15 | 0.00 | 643.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.70 |
F9 SW APARTMENT | 10-AUG-16:30 | 0.00 | -3499.28 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3192.04 | 0.00 | 74.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -584.76 |
F9 NW APARTMENT | 23-JUL-17:00 | 0.00 | -2848.72 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2576.75 | 0.00 | 545.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1090.92 |
F9 SE APARTMENT | 07-AUG-13:30 | 0.00 | -3249.98 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2666.95 | 0.00 | 701.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -570.50 |
F9 NE APARTMENT | 23-JUL-17:00 | 0.00 | -2070.40 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 434.69 | 0.00 | 545.47 | 272.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 23-JUL-17:15 | 0.00 | -1529.98 | 0.00 | 0.00 | 141.01 | 194.45 | 588.62 | 288.85 | 0.00 | 408.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -91.19 |
F9 N2 APARTMENT | 23-JUL-18:30 | 0.00 | -1512.59 | 0.00 | 0.00 | 141.65 | 230.46 | 547.42 | 643.10 | 0.00 | 179.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.28 |
F9 S1 APARTMENT | 07-AUG-13:30 | 0.00 | -2639.66 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2338.49 | 0.00 | 664.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -815.29 |
F9 S2 APARTMENT | 07-AUG-13:30 | 0.00 | -2652.36 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2338.25 | 0.00 | 664.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -802.46 |
T SW APARTMENT | 10-AUG-16:10 | 0.00 | -4214.72 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3265.69 | 0.00 | 65.41 | 66.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 23-JUL-17:00 | 0.00 | -3376.18 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2534.27 | 0.00 | 557.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.38 |
T SE APARTMENT | 10-AUG-12:30 | 0.00 | -3809.83 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2941.49 | 0.00 | 308.62 | 101.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 20-JUL-17:30 | 0.00 | -2447.16 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 775.66 | 0.00 | 513.53 | 233.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 23-JUL-17:15 | 0.00 | -1960.41 | 0.00 | 0.00 | 141.38 | 194.45 | 588.62 | 277.11 | 0.00 | 434.90 | 323.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 23-JUL-17:15 | 0.00 | -1956.40 | 0.00 | 0.00 | 141.52 | 194.45 | 588.62 | 277.95 | 0.00 | 441.04 | 312.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 07-AUG-13:30 | 0.00 | -3355.21 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2307.92 | 0.00 | 690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95.26 |
T S2 APARTMENT | 07-AUG-13:30 | 0.00 | -3365.24 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2307.68 | 0.00 | 690.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.98 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-13:30 | 0.00 | -172099.00 | 0.00 | 0.00 | 3284.51 | 10361.29 | 30924.05 | 144996.64 | 0.00 | 37706.66 | 0.00 | 0.00 | 0.00 | 0.00 | -27.14 | -55147.01 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 19-FEB-06:00 | 995.19 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1092.95 | 0.00 | -293.49 | -145.14 |
G NW APARTMENT | 19-FEB-08:15 | 1160.25 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.32 | 0.00 | -318.43 | -513.17 |
OFFICE | 19-FEB-07:05 | 1152.65 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1010.78 | 0.00 | -323.85 | -326.29 |
G NE APARTMENT | 19-FEB-06:00 | 1044.13 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.20 | 0.00 | -293.50 | -200.83 |
G N1 APARTMENT | 01-MAY-13:00 | 1302.88 | 0.00 | 0.00 | 0.00 | 44.18 | 28.81 | 388.49 | 700.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1201.48 | -1262.98 |
G N2 APARTMENT | 01-MAY-13:00 | 1286.96 | 0.00 | 0.00 | 0.00 | 44.24 | 28.81 | 388.49 | 700.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1201.34 | -1247.70 |
G S1 APARTMENT | 09-MAR-11:30 | 752.13 | 0.00 | 0.00 | 0.00 | 45.09 | 28.81 | 412.03 | 262.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -937.42 | -563.12 |
G S2 APARTMENT | 19-FEB-09:00 | 590.23 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 1369.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -181.64 | -2283.58 |
F2 SW APARTMENT | 19-FEB-06:00 | 983.41 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 | -1126.67 | 0.00 | -422.08 | 0.00 |
F2 NW APARTMENT | 19-FEB-06:00 | 1115.67 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1122.51 | 0.00 | -422.08 | -107.48 |
F2 SE APARTMENT | 19-FEB-06:00 | 958.89 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 54.45 | 0.00 | -1127.66 | 0.00 | -422.08 | 0.00 |
F2 NE APARTMENT | 19-FEB-06:00 | 1106.28 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1122.87 | 0.00 | -422.08 | -97.73 |
F2 N1 APARTMENT | 14-MAR-14:00 | 959.48 | 0.00 | 0.00 | 0.00 | 44.93 | 28.81 | 382.60 | 199.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1082.50 | -533.23 |
F2 N2 APARTMENT | 14-MAR-14:00 | 964.87 | 0.00 | 0.00 | 0.00 | 44.89 | 28.81 | 382.60 | 199.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1082.49 | -538.10 |
F2 S1 APARTMENT | 15-JAN-07:45 | 543.79 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -626.36 | 0.00 | -136.38 | -418.50 |
F2 S2 APARTMENT | 15-JAN-07:45 | 539.76 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -626.37 | 0.00 | -136.38 | -414.45 |
F3 SW APARTMENT | 19-FEB-06:00 | 995.57 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 109.45 | 0.00 | -1141.43 | 0.00 | -499.98 | 0.00 |
F3 NW APARTMENT | 19-FEB-06:00 | 1134.90 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1139.23 | 0.00 | -499.98 | -32.08 |
F3 SE APARTMENT | 19-FEB-06:00 | 979.67 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 125.91 | 0.00 | -1141.99 | 0.00 | -499.98 | 0.00 |
F3 NE APARTMENT | 19-FEB-06:00 | 1125.00 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1139.50 | 0.00 | -499.99 | -21.92 |
F3 N1 APARTMENT | 08-JAN-07:25 | 800.00 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -582.13 | 0.00 | -45.85 | -809.46 |
F3 N2 APARTMENT | 08-JAN-07:25 | 808.81 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -582.08 | 0.00 | -45.85 | -818.32 |
F3 S1 APARTMENT | 15-JAN-08:10 | 640.71 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -380.39 | 0.00 | -160.83 | -605.16 |
F3 S2 APARTMENT | 15-JAN-08:10 | 637.90 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -380.37 | 0.00 | -160.83 | -602.37 |
F4 SW APARTMENT | 19-FEB-06:00 | 1039.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 133.63 | 0.00 | -1150.47 | 0.00 | -559.15 | 0.00 |
F4 NW APARTMENT | 19-FEB-06:00 | 1179.97 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1149.92 | 0.00 | -559.15 | -7.30 |
F4 SE APARTMENT | 19-FEB-06:00 | 1026.85 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 146.79 | 0.00 | -1150.90 | 0.00 | -559.15 | 0.00 |
F4 NE APARTMENT | 19-FEB-06:00 | 1169.99 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 | -1150.19 | 0.00 | -559.15 | 0.00 |
F4 N1 APARTMENT | 20-JAN-07:10 | 687.32 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -542.78 | 0.00 | -112.32 | -669.67 |
F4 N2 APARTMENT | 20-JAN-07:10 | 693.27 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -542.77 | 0.00 | -112.32 | -675.63 |
F4 S1 APARTMENT | 19-FEB-08:25 | 633.91 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 762.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.15 | -1542.81 |
F4 S2 APARTMENT | 16-JAN-06:10 | 574.24 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -562.35 | 0.00 | -106.35 | -513.89 |
M SW APARTMENT | 19-FEB-06:00 | 1066.70 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 162.78 | 0.00 | -1157.89 | 0.00 | -607.98 | 0.00 |
M NW APARTMENT | 19-FEB-06:00 | 1204.79 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 | -1158.83 | 0.00 | -607.98 | 0.00 |
M SE APARTMENT | 19-FEB-06:00 | 1055.16 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 174.70 | 0.00 | -1158.28 | 0.00 | -607.98 | 0.00 |
M NE APARTMENT | 19-FEB-06:00 | 1194.88 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 35.81 | 0.00 | -1159.11 | 0.00 | -607.98 | 0.00 |
M N1 APARTMENT | 18-FEB-18:25 | 736.64 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.72 | 0.00 | -348.30 | -768.71 |
M N2 APARTMENT | 18-FEB-18:25 | 743.21 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.75 | 0.00 | -348.30 | -775.24 |
M S1 APARTMENT | 25-DEC-06:10 | 500.77 | 0.00 | 0.00 | 0.00 | 189.67 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.06 | 0.00 | -124.55 | -459.51 |
M S2 APARTMENT | 19-FEB-08:25 | 611.85 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 753.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -390.55 | -1480.12 |
F6 SW APARTMENT | 19-FEB-06:00 | 1146.62 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 128.76 | 0.00 | -1161.65 | 0.00 | -650.12 | 0.00 |
F6 NW APARTMENT | 19-FEB-06:00 | 1285.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.87 | 0.00 | -650.12 | -7.99 |
F6 SE APARTMENT | 19-FEB-06:00 | 1135.33 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 140.41 | 0.00 | -1162.02 | 0.00 | -650.12 | 0.00 |
F6 NE APARTMENT | 30-SEP-13:30 | 1411.76 | 0.00 | 0.00 | 0.00 | 42.10 | 28.81 | 382.60 | 436.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2175.13 | -126.39 |
F6 N1 APARTMENT | 30-SEP-13:30 | 1064.86 | 0.00 | 0.00 | 0.00 | 41.00 | 28.81 | 382.60 | 251.74 | 0.00 | 0.00 | 329.59 | 0.00 | 0.00 | 0.00 | -2098.60 | 0.00 |
F6 N2 APARTMENT | 30-SEP-13:30 | 1160.96 | 0.00 | 0.00 | 0.00 | 41.14 | 28.81 | 382.60 | 253.29 | 0.00 | 0.00 | 229.25 | 0.00 | 0.00 | 0.00 | -2096.05 | 0.00 |
F6 S1 APARTMENT | 17-FEB-24:00 | 450.72 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -552.14 | 0.00 | -142.02 | -323.64 |
F6 S2 APARTMENT | 18-FEB-22:45 | 451.46 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.81 | 0.00 | -293.12 | -249.54 |
F7 SW APARTMENT | 19-FEB-06:00 | 1204.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 111.99 | 0.00 | -1165.46 | 0.00 | -687.52 | 0.00 |
F7 NW APARTMENT | 19-FEB-06:00 | 1341.97 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1168.75 | 0.00 | -687.52 | -22.11 |
F7 SE APARTMENT | 19-FEB-06:00 | 1193.59 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 123.35 | 0.00 | -1165.82 | 0.00 | -687.52 | 0.00 |
F7 NE APARTMENT | 30-SEP-13:30 | 1799.78 | 0.00 | 0.00 | 0.00 | 42.47 | 28.81 | 382.60 | 437.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2273.16 | -417.79 |
F7 N1 APARTMENT | 30-SEP-13:30 | 1483.25 | 0.00 | 0.00 | 0.00 | 41.31 | 28.81 | 382.60 | 251.81 | 0.00 | 0.00 | 4.51 | 0.00 | 0.00 | 0.00 | -2192.30 | 0.00 |
F7 N2 APARTMENT | 30-SEP-13:30 | 1586.03 | 0.00 | 0.00 | 0.00 | 41.46 | 28.81 | 382.60 | 253.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2189.72 | -102.65 |
F7 S1 APARTMENT | 26-DEC-14:00 | 469.51 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.86 | 0.00 | -483.40 | -127.96 |
F7 S2 APARTMENT | 26-DEC-14:00 | 469.40 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.87 | 0.00 | -483.40 | -127.85 |
F8 SW APARTMENT | 19-FEB-06:00 | 1260.60 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 93.04 | 0.00 | -1168.71 | 0.00 | -721.34 | 0.00 |
F8 NW APARTMENT | 23-APR-12:15 | 1506.38 | 0.00 | 0.00 | 0.00 | 42.51 | 28.81 | 388.49 | 741.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1842.54 | -865.47 |
F8 SE APARTMENT | 19-FEB-06:00 | 1249.76 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 104.24 | 0.00 | -1169.07 | 0.00 | -721.34 | 0.00 |
F8 NE APARTMENT | 30-SEP-13:30 | 1786.46 | 0.00 | 0.00 | 0.00 | 42.82 | 28.81 | 382.60 | 439.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2371.84 | -307.97 |
F8 N1 APARTMENT | 30-SEP-13:30 | 1900.37 | 0.00 | 0.00 | 0.00 | 41.62 | 28.81 | 382.60 | 252.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2278.62 | -327.25 |
F8 N2 APARTMENT | 30-SEP-13:30 | 2008.67 | 0.00 | 0.00 | 0.00 | 41.78 | 28.81 | 382.60 | 254.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2276.02 | -440.06 |
F8 S1 APARTMENT | 07-JAN-08:25 | 606.78 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -462.55 | 0.00 | -207.91 | -442.00 |
F8 S2 APARTMENT | 07-JAN-08:25 | 604.90 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -462.50 | 0.00 | -207.91 | -440.16 |
F9 SW APARTMENT | 19-FEB-06:00 | 1400.15 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1168.66 | 0.00 | -752.35 | -15.54 |
F9 NW APARTMENT | 23-APR-12:15 | 1784.56 | 0.00 | 0.00 | 0.00 | 43.04 | 28.81 | 388.49 | 747.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1895.63 | -1097.12 |
F9 SE APARTMENT | 19-FEB-06:00 | 1389.26 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1168.84 | 0.00 | -752.35 | -4.46 |
F9 NE APARTMENT | 30-SEP-13:30 | 1757.65 | 0.00 | 0.00 | 0.00 | 43.42 | 28.81 | 382.60 | 447.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2463.56 | -196.16 |
F9 N1 APARTMENT | 30-SEP-13:30 | 1979.88 | 0.00 | 0.00 | 0.00 | 42.17 | 28.81 | 382.60 | 256.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2364.23 | -326.05 |
F9 N2 APARTMENT | 01-OCT-08:15 | 1975.32 | 0.00 | 0.00 | 0.00 | 42.16 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.20 | 0.00 | -1969.10 | -468.35 |
F9 S1 APARTMENT | 26-DEC-14:00 | 620.85 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.94 | 0.00 | -529.24 | -230.38 |
F9 S2 APARTMENT | 26-DEC-14:00 | 620.82 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.95 | 0.00 | -529.24 | -230.35 |
T SW APARTMENT | 19-FEB-06:00 | 2065.82 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.87 | 0.00 | -781.04 | -680.30 |
T NW APARTMENT | 19-FEB-06:00 | 2129.46 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1147.76 | 0.00 | -781.04 | -737.06 |
T SE APARTMENT | 19-FEB-06:00 | 2061.36 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.81 | 0.00 | -781.04 | -675.90 |
T NE APARTMENT | 19-FEB-06:00 | 2126.20 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1147.65 | 0.00 | -781.04 | -733.91 |
T N1 APARTMENT | 30-SEP-13:30 | 2046.83 | 0.00 | 0.00 | 0.00 | 42.46 | 28.81 | 382.60 | 258.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2448.19 | -310.91 |
T N2 APARTMENT | 30-SEP-13:30 | 2030.63 | 0.00 | 0.00 | 0.00 | 42.59 | 28.81 | 382.60 | 260.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2448.02 | -296.66 |
T S1 APARTMENT | 19-FEB-06:00 | 1263.94 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -693.53 | 0.00 | -471.12 | -635.70 |
T S2 APARTMENT | 19-FEB-06:00 | 1263.19 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -693.55 | 0.00 | -471.12 | -634.92 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-FEB-06:00 | 73912.39 | 0.00 | 0.00 | 0.00 | 14984.03 | 14239.10 | 20328.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75577.39 | 0.00 | -39348.37 | -8538.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Sec1.1A-General InformationData | |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 205.50 |
Number of hours cooling loads not met | 27.00 |
Number of hours not met | 232.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.23 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 87.77 | 0.00 | 263.14 | 110560.17 | 0.00 | 0.00 |
Space Cooling | 180.34 | 55284.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.50 | 1456.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7.32 | 1995.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 606.23 | 19223.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1170.00 | 84348.77 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2663.73 | 1433.14 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 2663.73 |
Natural Gas | 0.00 | 1433.14 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4096.86 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 11.20 |
Space Cooling | 23.01 |
Fans-Interior | 77.36 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 30.87 |
Subtotal | 339.91 |
Natural Gas [MJ/m2] | |
Space Heating | 33.58 |
Service Water Heating | 149.30 |
Miscellaneous | -0.00 |
Subtotal | 182.88 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.16 |
Space Heating | 8.57 |
Space Cooling | 4.40 |
Fans-Interior | 14.80 |
Service Water Heating | 28.56 |
Receptacle Equipment | 27.61 |
Miscellaneous | 5.90 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.240801 |
G NW APARTMENT DIRECT AIR | 0.178198 |
OFFICE DIRECT AIR | 0.325033 |
G NE APARTMENT DIRECT AIR | 0.128142 |
G N1 APARTMENT DIRECT AIR | 0.079637 |
G N2 APARTMENT DIRECT AIR | 0.076916 |
G S1 APARTMENT DIRECT AIR | 0.172105 |
G S2 APARTMENT DIRECT AIR | 0.177419 |
F2 SW APARTMENT DIRECT AIR | 0.308701 |
F2 NW APARTMENT DIRECT AIR | 0.232417 |
F2 SE APARTMENT DIRECT AIR | 0.302758 |
F2 NE APARTMENT DIRECT AIR | 0.174041 |
F2 N1 APARTMENT DIRECT AIR | 0.113716 |
F2 N2 APARTMENT DIRECT AIR | 0.111124 |
F2 S1 APARTMENT DIRECT AIR | 0.224615 |
F2 S2 APARTMENT DIRECT AIR | 0.226810 |
F3 SW APARTMENT DIRECT AIR | 0.309974 |
F3 NW APARTMENT DIRECT AIR | 0.234934 |
F3 SE APARTMENT DIRECT AIR | 0.287969 |
F3 NE APARTMENT DIRECT AIR | 0.177133 |
F3 N1 APARTMENT DIRECT AIR | 0.117688 |
F3 N2 APARTMENT DIRECT AIR | 0.115093 |
F3 S1 APARTMENT DIRECT AIR | 0.227798 |
F3 S2 APARTMENT DIRECT AIR | 0.228985 |
F4 SW APARTMENT DIRECT AIR | 0.310481 |
F4 NW APARTMENT DIRECT AIR | 0.235795 |
F4 SE APARTMENT DIRECT AIR | 0.287062 |
F4 NE APARTMENT DIRECT AIR | 0.177526 |
F4 N1 APARTMENT DIRECT AIR | 0.119078 |
F4 N2 APARTMENT DIRECT AIR | 0.116481 |
F4 S1 APARTMENT DIRECT AIR | 0.228800 |
F4 S2 APARTMENT DIRECT AIR | 0.229844 |
M SW APARTMENT DIRECT AIR | 0.313097 |
M NW APARTMENT DIRECT AIR | 0.238646 |
M SE APARTMENT DIRECT AIR | 0.289614 |
M NE APARTMENT DIRECT AIR | 0.179956 |
M N1 APARTMENT DIRECT AIR | 0.122178 |
M N2 APARTMENT DIRECT AIR | 0.119577 |
M S1 APARTMENT DIRECT AIR | 0.231726 |
M S2 APARTMENT DIRECT AIR | 0.232745 |
F6 SW APARTMENT DIRECT AIR | 0.309279 |
F6 NW APARTMENT DIRECT AIR | 0.234980 |
F6 SE APARTMENT DIRECT AIR | 0.285942 |
F6 NE APARTMENT DIRECT AIR | 0.176118 |
F6 N1 APARTMENT DIRECT AIR | 0.119103 |
F6 N2 APARTMENT DIRECT AIR | 0.116518 |
F6 S1 APARTMENT DIRECT AIR | 0.228204 |
F6 S2 APARTMENT DIRECT AIR | 0.229218 |
F7 SW APARTMENT DIRECT AIR | 0.307834 |
F7 NW APARTMENT DIRECT AIR | 0.233693 |
F7 SE APARTMENT DIRECT AIR | 0.284611 |
F7 NE APARTMENT DIRECT AIR | 0.174631 |
F7 N1 APARTMENT DIRECT AIR | 0.118212 |
F7 N2 APARTMENT DIRECT AIR | 0.115636 |
F7 S1 APARTMENT DIRECT AIR | 0.226990 |
F7 S2 APARTMENT DIRECT AIR | 0.228001 |
F8 SW APARTMENT DIRECT AIR | 0.307539 |
F8 NW APARTMENT DIRECT AIR | 0.233598 |
F8 SE APARTMENT DIRECT AIR | 0.284396 |
F8 NE APARTMENT DIRECT AIR | 0.174294 |
F8 N1 APARTMENT DIRECT AIR | 0.118480 |
F8 N2 APARTMENT DIRECT AIR | 0.115913 |
F8 S1 APARTMENT DIRECT AIR | 0.226899 |
F8 S2 APARTMENT DIRECT AIR | 0.227910 |
F9 SW APARTMENT DIRECT AIR | 0.313959 |
F9 NW APARTMENT DIRECT AIR | 0.240505 |
F9 SE APARTMENT DIRECT AIR | 0.289315 |
F9 NE APARTMENT DIRECT AIR | 0.175624 |
F9 N1 APARTMENT DIRECT AIR | 0.124672 |
F9 N2 APARTMENT DIRECT AIR | 0.122072 |
F9 S1 APARTMENT DIRECT AIR | 0.231139 |
F9 S2 APARTMENT DIRECT AIR | 0.232265 |
T SW APARTMENT DIRECT AIR | 0.379546 |
T NW APARTMENT DIRECT AIR | 0.289890 |
T SE APARTMENT DIRECT AIR | 0.349163 |
T NE APARTMENT DIRECT AIR | 0.214394 |
T N1 APARTMENT DIRECT AIR | 0.156027 |
T N2 APARTMENT DIRECT AIR | 0.156012 |
T S1 APARTMENT DIRECT AIR | 0.301961 |
T S2 APARTMENT DIRECT AIR | 0.302997 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.240801 |
AIRLOOP G NW MAIN BRANCH | 0.178198 |
AIRLOOP OFFICE MAIN BRANCH | 0.325033 |
AIRLOOP G NE MAIN BRANCH | 0.128142 |
AIRLOOP G N1 MAIN BRANCH | 0.079637 |
AIRLOOP G N2 MAIN BRANCH | 0.076916 |
AIRLOOP G S1 MAIN BRANCH | 0.172105 |
AIRLOOP G S2 MAIN BRANCH | 0.177419 |
AIRLOOP F2 SW MAIN BRANCH | 0.308701 |
AIRLOOP F2 NW MAIN BRANCH | 0.232417 |
AIRLOOP F2 SE MAIN BRANCH | 0.302758 |
AIRLOOP F2 NE MAIN BRANCH | 0.174041 |
AIRLOOP F2 N1 MAIN BRANCH | 0.113716 |
AIRLOOP F2 N2 MAIN BRANCH | 0.111124 |
AIRLOOP F2 S1 MAIN BRANCH | 0.224615 |
AIRLOOP F2 S2 MAIN BRANCH | 0.226810 |
AIRLOOP F3 SW MAIN BRANCH | 0.309974 |
AIRLOOP F3 NW MAIN BRANCH | 0.234934 |
AIRLOOP F3 SE MAIN BRANCH | 0.287969 |
AIRLOOP F3 NE MAIN BRANCH | 0.177133 |
AIRLOOP F3 N1 MAIN BRANCH | 0.117688 |
AIRLOOP F3 N2 MAIN BRANCH | 0.115093 |
AIRLOOP F3 S1 MAIN BRANCH | 0.227798 |
AIRLOOP F3 S2 MAIN BRANCH | 0.228985 |
AIRLOOP F4 SW MAIN BRANCH | 0.310481 |
AIRLOOP F4 NW MAIN BRANCH | 0.235795 |
AIRLOOP F4 SE MAIN BRANCH | 0.287062 |
AIRLOOP F4 NE MAIN BRANCH | 0.177526 |
AIRLOOP F4 N1 MAIN BRANCH | 0.119078 |
AIRLOOP F4 N2 MAIN BRANCH | 0.116481 |
AIRLOOP F4 S1 MAIN BRANCH | 0.228800 |
AIRLOOP F4 S2 MAIN BRANCH | 0.229844 |
AIRLOOP M SW MAIN BRANCH | 0.313097 |
AIRLOOP M NW MAIN BRANCH | 0.238646 |
AIRLOOP M SE MAIN BRANCH | 0.289614 |
AIRLOOP M NE MAIN BRANCH | 0.179956 |
AIRLOOP M N1 MAIN BRANCH | 0.122178 |
AIRLOOP M N2 MAIN BRANCH | 0.119577 |
AIRLOOP M S1 MAIN BRANCH | 0.231726 |
AIRLOOP M S2 MAIN BRANCH | 0.232745 |
AIRLOOP F6 SW MAIN BRANCH | 0.309279 |
AIRLOOP F6 NW MAIN BRANCH | 0.234980 |
AIRLOOP F6 SE MAIN BRANCH | 0.285942 |
AIRLOOP F6 NE MAIN BRANCH | 0.176118 |
AIRLOOP F6 N1 MAIN BRANCH | 0.119103 |
AIRLOOP F6 N2 MAIN BRANCH | 0.116518 |
AIRLOOP F6 S1 MAIN BRANCH | 0.228204 |
AIRLOOP F6 S2 MAIN BRANCH | 0.229218 |
AIRLOOP F7 SW MAIN BRANCH | 0.307834 |
AIRLOOP F7 NW MAIN BRANCH | 0.233693 |
AIRLOOP F7 SE MAIN BRANCH | 0.284611 |
AIRLOOP F7 NE MAIN BRANCH | 0.174631 |
AIRLOOP F7 N1 MAIN BRANCH | 0.118212 |
AIRLOOP F7 N2 MAIN BRANCH | 0.115636 |
AIRLOOP F7 S1 MAIN BRANCH | 0.226990 |
AIRLOOP F7 S2 MAIN BRANCH | 0.228001 |
AIRLOOP F8 SW MAIN BRANCH | 0.307539 |
AIRLOOP F8 NW MAIN BRANCH | 0.233598 |
AIRLOOP F8 SE MAIN BRANCH | 0.284396 |
AIRLOOP F8 NE MAIN BRANCH | 0.174294 |
AIRLOOP F8 N1 MAIN BRANCH | 0.118480 |
AIRLOOP F8 N2 MAIN BRANCH | 0.115913 |
AIRLOOP F8 S1 MAIN BRANCH | 0.226899 |
AIRLOOP F8 S2 MAIN BRANCH | 0.227910 |
AIRLOOP F9 SW MAIN BRANCH | 0.313959 |
AIRLOOP F9 NW MAIN BRANCH | 0.240505 |
AIRLOOP F9 SE MAIN BRANCH | 0.289315 |
AIRLOOP F9 NE MAIN BRANCH | 0.175624 |
AIRLOOP F9 N1 MAIN BRANCH | 0.124672 |
AIRLOOP F9 N2 MAIN BRANCH | 0.122072 |
AIRLOOP F9 S1 MAIN BRANCH | 0.231139 |
AIRLOOP F9 S2 MAIN BRANCH | 0.232265 |
AIRLOOP T SW MAIN BRANCH | 0.379546 |
AIRLOOP T NW MAIN BRANCH | 0.289890 |
AIRLOOP T SE MAIN BRANCH | 0.349163 |
AIRLOOP T NE MAIN BRANCH | 0.214394 |
AIRLOOP T N1 MAIN BRANCH | 0.156027 |
AIRLOOP T N2 MAIN BRANCH | 0.156012 |
AIRLOOP T S1 MAIN BRANCH | 0.301961 |
AIRLOOP T S2 MAIN BRANCH | 0.302997 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.240801 |
AIRLOOP G NW | 0.178198 |
AIRLOOP OFFICE | 0.325033 |
AIRLOOP G NE | 0.128142 |
AIRLOOP G N1 | 0.079637 |
AIRLOOP G N2 | 0.076916 |
AIRLOOP G S1 | 0.172105 |
AIRLOOP G S2 | 0.177419 |
AIRLOOP F2 SW | 0.308701 |
AIRLOOP F2 NW | 0.232417 |
AIRLOOP F2 SE | 0.302758 |
AIRLOOP F2 NE | 0.174041 |
AIRLOOP F2 N1 | 0.113716 |
AIRLOOP F2 N2 | 0.111124 |
AIRLOOP F2 S1 | 0.224615 |
AIRLOOP F2 S2 | 0.226810 |
AIRLOOP F3 SW | 0.309974 |
AIRLOOP F3 NW | 0.234934 |
AIRLOOP F3 SE | 0.287969 |
AIRLOOP F3 NE | 0.177133 |
AIRLOOP F3 N1 | 0.117688 |
AIRLOOP F3 N2 | 0.115093 |
AIRLOOP F3 S1 | 0.227798 |
AIRLOOP F3 S2 | 0.228985 |
AIRLOOP F4 SW | 0.310481 |
AIRLOOP F4 NW | 0.235795 |
AIRLOOP F4 SE | 0.287062 |
AIRLOOP F4 NE | 0.177526 |
AIRLOOP F4 N1 | 0.119078 |
AIRLOOP F4 N2 | 0.116481 |
AIRLOOP F4 S1 | 0.228800 |
AIRLOOP F4 S2 | 0.229844 |
AIRLOOP M SW | 0.313097 |
AIRLOOP M NW | 0.238646 |
AIRLOOP M SE | 0.289614 |
AIRLOOP M NE | 0.179956 |
AIRLOOP M N1 | 0.122178 |
AIRLOOP M N2 | 0.119577 |
AIRLOOP M S1 | 0.231726 |
AIRLOOP M S2 | 0.232745 |
AIRLOOP F6 SW | 0.309279 |
AIRLOOP F6 NW | 0.234980 |
AIRLOOP F6 SE | 0.285942 |
AIRLOOP F6 NE | 0.176118 |
AIRLOOP F6 N1 | 0.119103 |
AIRLOOP F6 N2 | 0.116518 |
AIRLOOP F6 S1 | 0.228204 |
AIRLOOP F6 S2 | 0.229218 |
AIRLOOP F7 SW | 0.307834 |
AIRLOOP F7 NW | 0.233693 |
AIRLOOP F7 SE | 0.284611 |
AIRLOOP F7 NE | 0.174631 |
AIRLOOP F7 N1 | 0.118212 |
AIRLOOP F7 N2 | 0.115636 |
AIRLOOP F7 S1 | 0.226990 |
AIRLOOP F7 S2 | 0.228001 |
AIRLOOP F8 SW | 0.307539 |
AIRLOOP F8 NW | 0.233598 |
AIRLOOP F8 SE | 0.284396 |
AIRLOOP F8 NE | 0.174294 |
AIRLOOP F8 N1 | 0.118480 |
AIRLOOP F8 N2 | 0.115913 |
AIRLOOP F8 S1 | 0.226899 |
AIRLOOP F8 S2 | 0.227910 |
AIRLOOP F9 SW | 0.313959 |
AIRLOOP F9 NW | 0.240505 |
AIRLOOP F9 SE | 0.289315 |
AIRLOOP F9 NE | 0.175624 |
AIRLOOP F9 N1 | 0.124672 |
AIRLOOP F9 N2 | 0.122072 |
AIRLOOP F9 S1 | 0.231139 |
AIRLOOP F9 S2 | 0.232265 |
AIRLOOP T SW | 0.379546 |
AIRLOOP T NW | 0.289890 |
AIRLOOP T SE | 0.349163 |
AIRLOOP T NE | 0.214394 |
AIRLOOP T N1 | 0.156027 |
AIRLOOP T N2 | 0.156012 |
AIRLOOP T S1 | 0.301961 |
AIRLOOP T S2 | 0.302997 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.240801 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.178198 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.325033 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.128142 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.079637 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.076916 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.172105 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.177419 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.308701 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.232417 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.302758 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.174041 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.113716 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.111124 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.224615 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.226810 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.309974 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.234934 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.287969 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.177133 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.117688 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.115093 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.227798 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.228985 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.310481 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.235795 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.287062 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.177526 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.119078 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.116481 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.228800 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.229844 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.313097 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.238646 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.289614 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.179956 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.122178 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.119577 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.231726 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.232745 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.309279 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.234980 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.285942 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.176118 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.119103 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.116518 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.228204 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.229218 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.307834 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.233693 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.284611 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.174631 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.118212 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.115636 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.226990 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.228001 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.307539 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.233598 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.284396 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.174294 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.118480 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.115913 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.226899 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.227910 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.313959 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.240505 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.289315 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.175624 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.124672 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.122072 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.231139 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.232265 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.379546 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.289890 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.349163 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.214394 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.156027 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.156012 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.301961 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.302997 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.240801 | 3570.28 | 2668.96 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.178198 | 2659.55 | 1976.02 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.325033 | 4819.63 | 3607.88 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.128142 | 1911.96 | 1414.84 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.079637 | 1236.46 | 894.20 | 0.000027 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.076916 | 1197.23 | 864.68 | 0.000026 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.172105 | 2618.64 | 1935.04 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.177419 | 2692.49 | 1992.04 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.308701 | 4521.14 | 3398.87 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.232417 | 3418.26 | 2556.91 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.302758 | 4444.62 | 3338.06 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.174041 | 2551.26 | 1907.08 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.113716 | 1723.02 | 1262.72 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.111124 | 1686.10 | 1234.72 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.224615 | 3353.06 | 2499.49 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.226810 | 3383.57 | 2523.04 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.309974 | 4543.13 | 3413.64 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.234934 | 3461.44 | 2587.72 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.287969 | 4243.33 | 3180.61 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.177133 | 2597.68 | 1941.12 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.117688 | 1780.93 | 1306.00 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.115093 | 1743.98 | 1277.96 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.227798 | 3399.82 | 2534.29 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.228985 | 3416.31 | 2547.02 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.310481 | 4553.40 | 3419.92 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.235795 | 3476.41 | 2597.74 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.287062 | 4233.89 | 3171.71 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.177526 | 2605.84 | 1946.05 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.119078 | 1801.93 | 1321.35 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.116481 | 1764.94 | 1293.28 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.228800 | 3415.65 | 2545.54 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.229844 | 3430.15 | 2556.74 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.313097 | 4592.40 | 3448.66 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.238646 | 3518.59 | 2628.98 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.289614 | 4271.96 | 3199.75 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.179956 | 2651.33 | 1977.74 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.122178 | 1846.84 | 1355.05 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.119577 | 1809.81 | 1326.95 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.231726 | 3457.90 | 2577.34 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.232745 | 3472.05 | 2588.26 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.309279 | 4541.57 | 3408.31 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.234980 | 3469.51 | 2590.18 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.285942 | 4223.10 | 3160.95 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.176118 | 2599.82 | 1937.10 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.119103 | 1804.29 | 1322.16 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.116518 | 1767.44 | 1294.22 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.228204 | 3410.24 | 2539.91 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.229218 | 3424.33 | 2550.78 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.307834 | 4523.44 | 3393.33 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.233693 | 3453.33 | 2576.83 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.284611 | 4206.53 | 3147.19 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.174631 | 2580.77 | 1921.59 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.118212 | 1792.49 | 1312.77 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.115636 | 1755.74 | 1284.92 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.226990 | 3394.51 | 2527.19 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.228001 | 3408.55 | 2538.03 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.307539 | 4521.10 | 3390.63 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.233598 | 3453.61 | 2576.23 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.284396 | 4205.27 | 3145.34 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.174294 | 2577.53 | 1918.36 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.118480 | 1797.01 | 1315.86 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.115913 | 1760.38 | 1288.10 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.226899 | 3394.29 | 2526.49 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.227910 | 3408.33 | 2537.32 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.313959 | 4612.02 | 3459.90 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.240505 | 3551.52 | 2650.77 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.289315 | 4275.33 | 3198.52 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.175624 | 2597.46 | 1933.00 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.124672 | 1885.32 | 1382.80 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.122072 | 1848.28 | 1354.70 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.231139 | 3454.29 | 2572.24 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.232265 | 3469.94 | 2584.32 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.379546 | 5534.46 | 4167.89 | 0.000121 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.289890 | 4246.05 | 3185.64 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.349163 | 5109.07 | 3840.68 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.214394 | 3150.03 | 2354.68 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.156027 | 2411.93 | 1767.73 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.156012 | 2411.74 | 1767.58 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.301961 | 4439.88 | 3331.99 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.302997 | 4450.59 | 3341.31 | 0.000097 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.240801 | 0.240801 | 0.240801 | 0.240801 | 3570.28 | 3570.28 | 2402.14 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.178198 | 0.178198 | 0.178198 | 0.178198 | 2659.55 | 2659.55 | 2403.54 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.325033 | 0.325033 | 0.325033 | 0.325033 | 4819.63 | 4819.63 | 3183.08 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.128142 | 0.128142 | 0.128142 | 0.128142 | 1911.96 | 1911.96 | 2402.22 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.079637 | 0.079637 | 0.079637 | 0.079637 | 1236.46 | 1236.46 | 1787.24 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.076916 | 0.076916 | 0.076916 | 0.076916 | 1197.23 | 1197.23 | 1787.22 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.172105 | 0.172105 | 0.172105 | 0.172105 | 2618.64 | 2618.64 | 1781.93 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.177419 | 0.177419 | 0.177419 | 0.177419 | 2692.49 | 2692.49 | 1790.43 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.308701 | 0.308701 | 0.308701 | 0.308701 | 4521.14 | 4521.14 | 2396.46 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.232417 | 0.232417 | 0.232417 | 0.232417 | 3418.26 | 3418.26 | 2398.16 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.302758 | 0.302758 | 0.302758 | 0.302758 | 4444.62 | 4444.62 | 2422.71 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.174041 | 0.174041 | 0.174041 | 0.174041 | 2551.26 | 2551.26 | 2398.85 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.113716 | 0.113716 | 0.113716 | 0.113716 | 1723.02 | 1723.02 | 1634.44 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.111124 | 0.111124 | 0.111124 | 0.111124 | 1686.10 | 1686.10 | 1634.45 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.224615 | 0.224615 | 0.224615 | 0.224615 | 3353.06 | 3353.06 | 1635.38 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.226810 | 0.226810 | 0.226810 | 0.226810 | 3383.57 | 3383.57 | 1637.14 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.309974 | 0.309974 | 0.309974 | 0.309974 | 4543.13 | 4543.13 | 2409.59 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.234934 | 0.234934 | 0.234934 | 0.234934 | 3461.44 | 3461.44 | 2414.14 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.287969 | 0.287969 | 0.287969 | 0.287969 | 4243.33 | 4243.33 | 2414.72 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.177133 | 0.177133 | 0.177133 | 0.177133 | 2597.68 | 2597.68 | 2416.33 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.117688 | 0.117688 | 0.117688 | 0.117688 | 1780.93 | 1780.93 | 1615.49 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.115093 | 0.115093 | 0.115093 | 0.115093 | 1743.98 | 1743.98 | 1615.55 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.227798 | 0.227798 | 0.227798 | 0.227798 | 3399.82 | 3399.82 | 1611.58 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.228985 | 0.228985 | 0.228985 | 0.228985 | 3416.31 | 3416.31 | 1611.92 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.310481 | 0.310481 | 0.310481 | 0.310481 | 4553.40 | 4553.40 | 2455.32 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.235795 | 0.235795 | 0.235795 | 0.235795 | 3476.41 | 3476.41 | 2462.03 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.287062 | 0.287062 | 0.287062 | 0.287062 | 4233.89 | 4233.89 | 2458.93 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.177526 | 0.177526 | 0.177526 | 0.177526 | 2605.84 | 2605.84 | 2465.31 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.119078 | 0.119078 | 0.119078 | 0.119078 | 1801.93 | 1801.93 | 1635.74 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.116481 | 0.116481 | 0.116481 | 0.116481 | 1764.94 | 1764.94 | 1635.82 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.228800 | 0.228800 | 0.228800 | 0.228800 | 3415.65 | 3415.65 | 1629.38 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.229844 | 0.229844 | 0.229844 | 0.229844 | 3430.15 | 3430.15 | 1629.51 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.313097 | 0.313097 | 0.313097 | 0.313097 | 4592.40 | 4592.40 | 2476.30 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.238646 | 0.238646 | 0.238646 | 0.238646 | 3518.59 | 3518.59 | 2483.35 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.289614 | 0.289614 | 0.289614 | 0.289614 | 4271.96 | 4271.96 | 2480.45 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.179956 | 0.179956 | 0.179956 | 0.179956 | 2651.33 | 2651.33 | 2487.47 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.122178 | 0.122178 | 0.122178 | 0.122178 | 1846.84 | 1846.84 | 1637.65 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.119577 | 0.119577 | 0.119577 | 0.119577 | 1809.81 | 1809.81 | 1637.76 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.231726 | 0.231726 | 0.231726 | 0.231726 | 3457.90 | 3457.90 | 1630.90 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.232745 | 0.232745 | 0.232745 | 0.232745 | 3472.05 | 3472.05 | 1631.01 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.309279 | 0.309279 | 0.309279 | 0.309279 | 4541.57 | 4541.57 | 2562.12 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.234980 | 0.234980 | 0.234980 | 0.234980 | 3469.51 | 3469.51 | 2571.22 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.285942 | 0.285942 | 0.285942 | 0.285942 | 4223.10 | 4223.10 | 2566.96 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.176118 | 0.176118 | 0.176118 | 0.176118 | 2599.82 | 2599.82 | 2576.05 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.119103 | 0.119103 | 0.119103 | 0.119103 | 1804.29 | 1804.29 | 1703.16 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.116518 | 0.116518 | 0.116518 | 0.116518 | 1767.44 | 1767.44 | 1703.29 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.228204 | 0.228204 | 0.228204 | 0.228204 | 3410.24 | 3410.24 | 1694.28 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.229218 | 0.229218 | 0.229218 | 0.229218 | 3424.33 | 3424.33 | 1694.41 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.307834 | 0.307834 | 0.307834 | 0.307834 | 4523.44 | 4523.44 | 2619.28 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.233693 | 0.233693 | 0.233693 | 0.233693 | 3453.33 | 3453.33 | 2629.03 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.284611 | 0.284611 | 0.284611 | 0.284611 | 4206.53 | 4206.53 | 2624.70 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.174631 | 0.174631 | 0.174631 | 0.174631 | 2580.77 | 2580.77 | 2634.45 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.118212 | 0.118212 | 0.118212 | 0.118212 | 1792.49 | 1792.49 | 1744.34 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.115636 | 0.115636 | 0.115636 | 0.115636 | 1755.74 | 1755.74 | 1744.48 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.226990 | 0.226990 | 0.226990 | 0.226990 | 3394.51 | 3394.51 | 1734.74 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.228001 | 0.228001 | 0.228001 | 0.228001 | 3408.55 | 3408.55 | 1734.88 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.307539 | 0.307539 | 0.307539 | 0.307539 | 4521.10 | 4521.10 | 2678.07 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.233598 | 0.233598 | 0.233598 | 0.233598 | 3453.61 | 3453.61 | 2688.19 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.284396 | 0.284396 | 0.284396 | 0.284396 | 4205.27 | 4205.27 | 2683.99 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.174294 | 0.174294 | 0.174294 | 0.174294 | 2577.53 | 2577.53 | 2694.11 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.118480 | 0.118480 | 0.118480 | 0.118480 | 1797.01 | 1797.01 | 1788.88 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.115913 | 0.115913 | 0.115913 | 0.115913 | 1760.38 | 1760.38 | 1789.04 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.226899 | 0.226899 | 0.226899 | 0.226899 | 3394.29 | 3394.29 | 1778.91 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.227910 | 0.227910 | 0.227910 | 0.227910 | 3408.33 | 3408.33 | 1779.06 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.313959 | 0.313959 | 0.313959 | 0.313959 | 4612.02 | 4612.02 | 2840.23 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.240505 | 0.240505 | 0.240505 | 0.240505 | 3551.52 | 3551.52 | 2848.69 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.289315 | 0.289315 | 0.289315 | 0.289315 | 4275.33 | 4275.33 | 2846.64 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.175624 | 0.175624 | 0.175624 | 0.175624 | 2597.46 | 2597.46 | 2855.10 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.124672 | 0.124672 | 0.124672 | 0.124672 | 1885.32 | 1885.32 | 1928.92 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.122072 | 0.122072 | 0.122072 | 0.122072 | 1848.28 | 1848.28 | 1929.09 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.231139 | 0.231139 | 0.231139 | 0.231139 | 3454.29 | 3454.29 | 1920.15 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.232265 | 0.232265 | 0.232265 | 0.232265 | 3469.94 | 3469.94 | 1920.32 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.379546 | 0.379546 | 0.379546 | 0.379546 | 5534.46 | 5534.46 | 3371.62 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.289890 | 0.289890 | 0.289890 | 0.289890 | 4246.05 | 4246.05 | 3385.75 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.349163 | 0.349163 | 0.349163 | 0.349163 | 5109.07 | 5109.07 | 3377.85 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.214394 | 0.214394 | 0.214394 | 0.214394 | 3150.03 | 3150.03 | 3391.97 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.156027 | 0.156027 | 0.156027 | 0.156027 | 2411.93 | 2411.93 | 2501.70 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.156012 | 0.156012 | 0.156012 | 0.156012 | 2411.74 | 2411.74 | 2501.87 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.301961 | 0.301961 | 0.301961 | 0.301961 | 4439.88 | 4439.88 | 2484.34 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.302997 | 0.302997 | 0.302997 | 0.302997 | 4450.59 | 4450.59 | 2484.52 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.240801 |
AIRLOOP G NW SUPPLY FAN | 0.178198 |
AIRLOOP OFFICE SUPPLY FAN | 0.325033 |
AIRLOOP G NE SUPPLY FAN | 0.128142 |
AIRLOOP G N1 SUPPLY FAN | 0.079637 |
AIRLOOP G N2 SUPPLY FAN | 0.076916 |
AIRLOOP G S1 SUPPLY FAN | 0.172105 |
AIRLOOP G S2 SUPPLY FAN | 0.177419 |
AIRLOOP F2 SW SUPPLY FAN | 0.308701 |
AIRLOOP F2 NW SUPPLY FAN | 0.232417 |
AIRLOOP F2 SE SUPPLY FAN | 0.302758 |
AIRLOOP F2 NE SUPPLY FAN | 0.174041 |
AIRLOOP F2 N1 SUPPLY FAN | 0.113716 |
AIRLOOP F2 N2 SUPPLY FAN | 0.111124 |
AIRLOOP F2 S1 SUPPLY FAN | 0.224615 |
AIRLOOP F2 S2 SUPPLY FAN | 0.226810 |
AIRLOOP F3 SW SUPPLY FAN | 0.309974 |
AIRLOOP F3 NW SUPPLY FAN | 0.234934 |
AIRLOOP F3 SE SUPPLY FAN | 0.287969 |
AIRLOOP F3 NE SUPPLY FAN | 0.177133 |
AIRLOOP F3 N1 SUPPLY FAN | 0.117688 |
AIRLOOP F3 N2 SUPPLY FAN | 0.115093 |
AIRLOOP F3 S1 SUPPLY FAN | 0.227798 |
AIRLOOP F3 S2 SUPPLY FAN | 0.228985 |
AIRLOOP F4 SW SUPPLY FAN | 0.310481 |
AIRLOOP F4 NW SUPPLY FAN | 0.235795 |
AIRLOOP F4 SE SUPPLY FAN | 0.287062 |
AIRLOOP F4 NE SUPPLY FAN | 0.177526 |
AIRLOOP F4 N1 SUPPLY FAN | 0.119078 |
AIRLOOP F4 N2 SUPPLY FAN | 0.116481 |
AIRLOOP F4 S1 SUPPLY FAN | 0.228800 |
AIRLOOP F4 S2 SUPPLY FAN | 0.229844 |
AIRLOOP M SW SUPPLY FAN | 0.313097 |
AIRLOOP M NW SUPPLY FAN | 0.238646 |
AIRLOOP M SE SUPPLY FAN | 0.289614 |
AIRLOOP M NE SUPPLY FAN | 0.179956 |
AIRLOOP M N1 SUPPLY FAN | 0.122178 |
AIRLOOP M N2 SUPPLY FAN | 0.119577 |
AIRLOOP M S1 SUPPLY FAN | 0.231726 |
AIRLOOP M S2 SUPPLY FAN | 0.232745 |
AIRLOOP F6 SW SUPPLY FAN | 0.309279 |
AIRLOOP F6 NW SUPPLY FAN | 0.234980 |
AIRLOOP F6 SE SUPPLY FAN | 0.285942 |
AIRLOOP F6 NE SUPPLY FAN | 0.176118 |
AIRLOOP F6 N1 SUPPLY FAN | 0.119103 |
AIRLOOP F6 N2 SUPPLY FAN | 0.116518 |
AIRLOOP F6 S1 SUPPLY FAN | 0.228204 |
AIRLOOP F6 S2 SUPPLY FAN | 0.229218 |
AIRLOOP F7 SW SUPPLY FAN | 0.307834 |
AIRLOOP F7 NW SUPPLY FAN | 0.233693 |
AIRLOOP F7 SE SUPPLY FAN | 0.284611 |
AIRLOOP F7 NE SUPPLY FAN | 0.174631 |
AIRLOOP F7 N1 SUPPLY FAN | 0.118212 |
AIRLOOP F7 N2 SUPPLY FAN | 0.115636 |
AIRLOOP F7 S1 SUPPLY FAN | 0.226990 |
AIRLOOP F7 S2 SUPPLY FAN | 0.228001 |
AIRLOOP F8 SW SUPPLY FAN | 0.307539 |
AIRLOOP F8 NW SUPPLY FAN | 0.233598 |
AIRLOOP F8 SE SUPPLY FAN | 0.284396 |
AIRLOOP F8 NE SUPPLY FAN | 0.174294 |
AIRLOOP F8 N1 SUPPLY FAN | 0.118480 |
AIRLOOP F8 N2 SUPPLY FAN | 0.115913 |
AIRLOOP F8 S1 SUPPLY FAN | 0.226899 |
AIRLOOP F8 S2 SUPPLY FAN | 0.227910 |
AIRLOOP F9 SW SUPPLY FAN | 0.313959 |
AIRLOOP F9 NW SUPPLY FAN | 0.240505 |
AIRLOOP F9 SE SUPPLY FAN | 0.289315 |
AIRLOOP F9 NE SUPPLY FAN | 0.175624 |
AIRLOOP F9 N1 SUPPLY FAN | 0.124672 |
AIRLOOP F9 N2 SUPPLY FAN | 0.122072 |
AIRLOOP F9 S1 SUPPLY FAN | 0.231139 |
AIRLOOP F9 S2 SUPPLY FAN | 0.232265 |
AIRLOOP T SW SUPPLY FAN | 0.379546 |
AIRLOOP T NW SUPPLY FAN | 0.289890 |
AIRLOOP T SE SUPPLY FAN | 0.349163 |
AIRLOOP T NE SUPPLY FAN | 0.214394 |
AIRLOOP T N1 SUPPLY FAN | 0.156027 |
AIRLOOP T N2 SUPPLY FAN | 0.156012 |
AIRLOOP T S1 SUPPLY FAN | 0.301961 |
AIRLOOP T S2 SUPPLY FAN | 0.302997 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.240801 | 3570.28 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.178198 | 2659.55 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.325033 | 4819.63 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.128142 | 1911.96 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.079637 | 1236.46 | 0.000027 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.076916 | 1197.23 | 0.000026 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.172105 | 2618.64 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.177419 | 2692.49 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.308701 | 4521.14 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.232417 | 3418.26 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.302758 | 4444.62 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.174041 | 2551.26 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.113716 | 1723.02 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.111124 | 1686.10 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.224615 | 3353.06 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.226810 | 3383.57 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.309974 | 4543.13 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.234934 | 3461.44 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.287969 | 4243.33 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.177133 | 2597.68 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.117688 | 1780.93 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.115093 | 1743.98 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.227798 | 3399.82 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.228985 | 3416.31 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.310481 | 4553.40 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.235795 | 3476.41 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.287062 | 4233.89 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.177526 | 2605.84 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.119078 | 1801.93 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.116481 | 1764.94 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.228800 | 3415.65 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.229844 | 3430.15 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.313097 | 4592.40 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.238646 | 3518.59 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.289614 | 4271.96 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.179956 | 2651.33 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.122178 | 1846.84 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.119577 | 1809.81 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.231726 | 3457.90 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.232745 | 3472.05 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.309279 | 4541.57 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.234980 | 3469.51 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.285942 | 4223.10 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.176118 | 2599.82 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.119103 | 1804.29 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.116518 | 1767.44 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.228204 | 3410.24 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.229218 | 3424.33 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.307834 | 4523.44 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.233693 | 3453.33 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.284611 | 4206.53 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.174631 | 2580.77 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.118212 | 1792.49 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.115636 | 1755.74 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.226990 | 3394.51 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.228001 | 3408.55 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.307539 | 4521.10 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.233598 | 3453.61 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.284396 | 4205.27 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.174294 | 2577.53 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.118480 | 1797.01 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.115913 | 1760.38 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.226899 | 3394.29 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.227910 | 3408.33 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.313959 | 4612.02 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.240505 | 3551.52 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.289315 | 4275.33 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.175624 | 2597.46 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.124672 | 1885.32 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.122072 | 1848.28 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.231139 | 3454.29 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.232265 | 3469.94 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.379546 | 5534.46 | 0.000121 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.289890 | 4246.05 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.349163 | 5109.07 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.214394 | 3150.03 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.156027 | 2411.93 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.156012 | 2411.74 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.301961 | 4439.88 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.302997 | 4450.59 | 0.000097 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2402.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2403.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3183.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2402.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1787.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1787.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1781.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1790.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2396.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2398.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2422.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2398.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1634.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1634.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1635.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1637.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2409.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2414.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2414.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2416.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1615.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1615.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1611.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1611.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2455.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2462.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2458.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2465.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1635.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1635.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1629.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1629.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2476.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2483.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2480.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2487.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1637.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1637.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1630.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1631.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2562.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2571.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2566.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2576.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1703.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1703.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1694.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1694.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2619.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2629.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2624.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2634.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1744.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1744.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1734.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1734.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2678.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2688.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2683.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2694.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1788.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1789.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1778.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1779.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2840.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2848.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2846.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2855.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1928.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1929.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1920.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1920.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3371.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3385.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3377.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3391.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2501.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2501.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2484.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2484.52 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005566 | 6.26 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005566 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005566 | 2686.93 | 7.17 | 8217.78 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005566 | 1419.61 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.50 |
February | 22.05 | 5.82 |
March | 22.36 | 8.33 |
April | 22.90 | 10.85 |
May | 23.31 | 12.97 |
June | 23.99 | 15.59 |
July | 24.18 | 17.66 |
August | 24.18 | 18.80 |
September | 24.13 | 15.09 |
October | 22.94 | 11.43 |
November | 22.04 | 8.07 |
December | 21.86 | 5.42 |
Annual Sum or Average | 22.98 | 11.24 |
Minimum of Months | 21.75 | 4.50 |
Maximum of Months | 24.18 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.75 | 5.82 |
March | 21.84 | 8.33 |
April | 22.31 | 10.85 |
May | 22.87 | 12.97 |
June | 23.77 | 15.59 |
July | 24.06 | 17.66 |
August | 24.06 | 18.80 |
September | 23.79 | 15.09 |
October | 22.13 | 11.43 |
November | 21.78 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.65 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.06 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 4.50 |
February | 22.15 | 5.82 |
March | 22.51 | 8.33 |
April | 22.93 | 10.85 |
May | 23.33 | 12.97 |
June | 24.10 | 15.59 |
July | 24.29 | 17.66 |
August | 24.32 | 18.80 |
September | 24.12 | 15.09 |
October | 22.98 | 11.43 |
November | 22.24 | 8.07 |
December | 21.97 | 5.42 |
Annual Sum or Average | 23.07 | 11.24 |
Minimum of Months | 21.88 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.72 | 5.82 |
March | 21.77 | 8.33 |
April | 22.25 | 10.85 |
May | 22.70 | 12.97 |
June | 23.71 | 15.59 |
July | 23.98 | 17.66 |
August | 24.02 | 18.80 |
September | 23.62 | 15.09 |
October | 22.03 | 11.43 |
November | 21.75 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.58 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.02 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.73 | 5.82 |
March | 21.76 | 8.33 |
April | 22.11 | 10.85 |
May | 22.55 | 12.97 |
June | 23.56 | 15.59 |
July | 23.88 | 17.66 |
August | 23.95 | 18.80 |
September | 23.57 | 15.09 |
October | 22.03 | 11.43 |
November | 21.77 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.53 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 23.95 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.73 | 5.82 |
March | 21.76 | 8.33 |
April | 22.10 | 10.85 |
May | 22.53 | 12.97 |
June | 23.55 | 15.59 |
July | 23.87 | 17.66 |
August | 23.94 | 18.80 |
September | 23.56 | 15.09 |
October | 22.02 | 11.43 |
November | 21.77 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.52 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 23.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.50 |
February | 22.12 | 5.82 |
March | 22.47 | 8.33 |
April | 22.95 | 10.85 |
May | 23.25 | 12.97 |
June | 23.96 | 15.59 |
July | 24.13 | 17.66 |
August | 24.16 | 18.80 |
September | 24.14 | 15.09 |
October | 23.14 | 11.43 |
November | 22.16 | 8.07 |
December | 21.91 | 5.42 |
Annual Sum or Average | 23.02 | 11.24 |
Minimum of Months | 21.78 | 4.50 |
Maximum of Months | 24.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.50 |
February | 22.15 | 5.82 |
March | 22.51 | 8.33 |
April | 22.99 | 10.85 |
May | 23.28 | 12.97 |
June | 23.99 | 15.59 |
July | 24.15 | 17.66 |
August | 24.18 | 18.80 |
September | 24.15 | 15.09 |
October | 23.18 | 11.43 |
November | 22.19 | 8.07 |
December | 21.92 | 5.42 |
Annual Sum or Average | 23.04 | 11.24 |
Minimum of Months | 21.79 | 4.50 |
Maximum of Months | 24.18 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.88 | 4.50 |
February | 18.50 | 5.82 |
March | 19.46 | 8.33 |
April | 20.57 | 10.85 |
May | 21.46 | 12.97 |
June | 23.05 | 15.59 |
July | 23.87 | 17.66 |
August | 24.19 | 18.80 |
September | 22.95 | 15.09 |
October | 20.65 | 11.43 |
November | 19.04 | 8.07 |
December | 18.19 | 5.42 |
Annual Sum or Average | 20.83 | 11.24 |
Minimum of Months | 17.88 | 4.50 |
Maximum of Months | 24.19 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 4.50 |
February | 22.42 | 5.82 |
March | 23.12 | 8.33 |
April | 23.76 | 10.85 |
May | 24.13 | 12.97 |
June | 24.28 | 15.59 |
July | 24.31 | 17.66 |
August | 24.31 | 18.80 |
September | 24.32 | 15.09 |
October | 23.77 | 11.43 |
November | 22.47 | 8.07 |
December | 22.04 | 5.42 |
Annual Sum or Average | 23.40 | 11.24 |
Minimum of Months | 21.84 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.85 | 5.82 |
March | 22.13 | 8.33 |
April | 23.01 | 10.85 |
May | 23.83 | 12.97 |
June | 24.15 | 15.59 |
July | 24.25 | 17.66 |
August | 24.24 | 18.80 |
September | 24.13 | 15.09 |
October | 22.74 | 11.43 |
November | 21.94 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.98 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.25 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.50 |
February | 22.48 | 5.82 |
March | 23.23 | 8.33 |
April | 23.83 | 10.85 |
May | 24.13 | 12.97 |
June | 24.32 | 15.59 |
July | 24.33 | 17.66 |
August | 24.33 | 18.80 |
September | 24.33 | 15.09 |
October | 23.81 | 11.43 |
November | 22.54 | 8.07 |
December | 22.07 | 5.42 |
Annual Sum or Average | 23.44 | 11.24 |
Minimum of Months | 21.86 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.80 | 5.82 |
March | 22.01 | 8.33 |
April | 22.93 | 10.85 |
May | 23.67 | 12.97 |
June | 24.12 | 15.59 |
July | 24.22 | 17.66 |
August | 24.22 | 18.80 |
September | 24.00 | 15.09 |
October | 22.53 | 11.43 |
November | 21.88 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.90 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.22 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.85 | 5.82 |
March | 22.07 | 8.33 |
April | 22.87 | 10.85 |
May | 23.66 | 12.97 |
June | 24.04 | 15.59 |
July | 24.15 | 17.66 |
August | 24.17 | 18.80 |
September | 23.99 | 15.09 |
October | 22.72 | 11.43 |
November | 21.98 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.91 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.85 | 5.82 |
March | 22.05 | 8.33 |
April | 22.86 | 10.85 |
May | 23.64 | 12.97 |
June | 24.03 | 15.59 |
July | 24.14 | 17.66 |
August | 24.17 | 18.80 |
September | 23.97 | 15.09 |
October | 22.69 | 11.43 |
November | 21.97 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.90 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 4.50 |
February | 22.69 | 5.82 |
March | 23.45 | 8.33 |
April | 23.93 | 10.85 |
May | 24.15 | 12.97 |
June | 24.26 | 15.59 |
July | 24.28 | 17.66 |
August | 24.29 | 18.80 |
September | 24.31 | 15.09 |
October | 24.01 | 11.43 |
November | 22.82 | 8.07 |
December | 22.25 | 5.42 |
Annual Sum or Average | 23.54 | 11.24 |
Minimum of Months | 21.98 | 4.50 |
Maximum of Months | 24.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.50 |
February | 22.71 | 5.82 |
March | 23.47 | 8.33 |
April | 23.94 | 10.85 |
May | 24.16 | 12.97 |
June | 24.26 | 15.59 |
July | 24.28 | 17.66 |
August | 24.29 | 18.80 |
September | 24.31 | 15.09 |
October | 24.02 | 11.43 |
November | 22.84 | 8.07 |
December | 22.26 | 5.42 |
Annual Sum or Average | 23.55 | 11.24 |
Minimum of Months | 21.99 | 4.50 |
Maximum of Months | 24.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.50 |
February | 22.56 | 5.82 |
March | 23.41 | 8.33 |
April | 24.33 | 10.85 |
May | 25.08 | 12.97 |
June | 25.72 | 15.59 |
July | 26.01 | 17.66 |
August | 26.06 | 18.80 |
September | 25.62 | 15.09 |
October | 24.17 | 11.43 |
November | 22.76 | 8.07 |
December | 22.15 | 5.42 |
Annual Sum or Average | 24.16 | 11.24 |
Minimum of Months | 21.95 | 4.50 |
Maximum of Months | 26.06 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.50 |
February | 22.51 | 5.82 |
March | 23.32 | 8.33 |
April | 23.91 | 10.85 |
May | 24.22 | 12.97 |
June | 24.29 | 15.59 |
July | 24.31 | 17.66 |
August | 24.31 | 18.80 |
September | 24.33 | 15.09 |
October | 23.92 | 11.43 |
November | 22.58 | 8.07 |
December | 22.09 | 5.42 |
Annual Sum or Average | 23.48 | 11.24 |
Minimum of Months | 21.86 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.89 | 5.82 |
March | 22.24 | 8.33 |
April | 23.22 | 10.85 |
May | 24.01 | 12.97 |
June | 24.18 | 15.59 |
July | 24.25 | 17.66 |
August | 24.24 | 18.80 |
September | 24.17 | 15.09 |
October | 22.95 | 11.43 |
November | 22.00 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.05 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.25 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 4.50 |
February | 22.50 | 5.82 |
March | 23.32 | 8.33 |
April | 23.92 | 10.85 |
May | 24.19 | 12.97 |
June | 24.30 | 15.59 |
July | 24.32 | 17.66 |
August | 24.32 | 18.80 |
September | 24.32 | 15.09 |
October | 23.88 | 11.43 |
November | 22.56 | 8.07 |
December | 22.08 | 5.42 |
Annual Sum or Average | 23.47 | 11.24 |
Minimum of Months | 21.85 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.83 | 5.82 |
March | 22.10 | 8.33 |
April | 23.15 | 10.85 |
May | 23.88 | 12.97 |
June | 24.15 | 15.59 |
July | 24.23 | 17.66 |
August | 24.23 | 18.80 |
September | 24.06 | 15.09 |
October | 22.73 | 11.43 |
November | 21.93 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.98 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.23 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.91 | 5.82 |
March | 22.24 | 8.33 |
April | 23.18 | 10.85 |
May | 23.95 | 12.97 |
June | 24.10 | 15.59 |
July | 24.16 | 17.66 |
August | 24.18 | 18.80 |
September | 24.06 | 15.09 |
October | 23.03 | 11.43 |
November | 22.08 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.03 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.18 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.90 | 5.82 |
March | 22.22 | 8.33 |
April | 23.17 | 10.85 |
May | 23.93 | 12.97 |
June | 24.10 | 15.59 |
July | 24.16 | 17.66 |
August | 24.18 | 18.80 |
September | 24.05 | 15.09 |
October | 22.99 | 11.43 |
November | 22.07 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.02 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.18 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.50 |
February | 22.87 | 5.82 |
March | 23.73 | 8.33 |
April | 24.12 | 10.85 |
May | 24.27 | 12.97 |
June | 24.27 | 15.59 |
July | 24.27 | 17.66 |
August | 24.29 | 18.80 |
September | 24.32 | 15.09 |
October | 24.16 | 11.43 |
November | 23.05 | 8.07 |
December | 22.38 | 5.42 |
Annual Sum or Average | 23.65 | 11.24 |
Minimum of Months | 22.06 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.50 |
February | 22.87 | 5.82 |
March | 23.74 | 8.33 |
April | 24.12 | 10.85 |
May | 24.27 | 12.97 |
June | 24.27 | 15.59 |
July | 24.28 | 17.66 |
August | 24.29 | 18.80 |
September | 24.32 | 15.09 |
October | 24.17 | 11.43 |
November | 23.06 | 8.07 |
December | 22.39 | 5.42 |
Annual Sum or Average | 23.66 | 11.24 |
Minimum of Months | 22.06 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 4.50 |
February | 23.00 | 5.82 |
March | 23.93 | 8.33 |
April | 24.90 | 10.85 |
May | 25.64 | 12.97 |
June | 25.99 | 15.59 |
July | 26.21 | 17.66 |
August | 26.23 | 18.80 |
September | 25.89 | 15.09 |
October | 24.68 | 11.43 |
November | 23.21 | 8.07 |
December | 22.54 | 5.42 |
Annual Sum or Average | 24.55 | 11.24 |
Minimum of Months | 22.34 | 4.50 |
Maximum of Months | 26.23 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.50 |
February | 22.51 | 5.82 |
March | 23.35 | 8.33 |
April | 23.93 | 10.85 |
May | 24.23 | 12.97 |
June | 24.29 | 15.59 |
July | 24.31 | 17.66 |
August | 24.30 | 18.80 |
September | 24.34 | 15.09 |
October | 23.95 | 11.43 |
November | 22.60 | 8.07 |
December | 22.10 | 5.42 |
Annual Sum or Average | 23.49 | 11.24 |
Minimum of Months | 21.86 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.89 | 5.82 |
March | 22.27 | 8.33 |
April | 23.28 | 10.85 |
May | 24.05 | 12.97 |
June | 24.19 | 15.59 |
July | 24.25 | 17.66 |
August | 24.23 | 18.80 |
September | 24.20 | 15.09 |
October | 23.03 | 11.43 |
November | 22.02 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.07 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.25 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 4.50 |
February | 22.49 | 5.82 |
March | 23.33 | 8.33 |
April | 23.93 | 10.85 |
May | 24.20 | 12.97 |
June | 24.30 | 15.59 |
July | 24.32 | 17.66 |
August | 24.31 | 18.80 |
September | 24.34 | 15.09 |
October | 23.90 | 11.43 |
November | 22.56 | 8.07 |
December | 22.07 | 5.42 |
Annual Sum or Average | 23.47 | 11.24 |
Minimum of Months | 21.84 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.83 | 5.82 |
March | 22.13 | 8.33 |
April | 23.21 | 10.85 |
May | 23.92 | 12.97 |
June | 24.16 | 15.59 |
July | 24.23 | 17.66 |
August | 24.21 | 18.80 |
September | 24.11 | 15.09 |
October | 22.81 | 11.43 |
November | 21.94 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.00 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.23 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.92 | 5.82 |
March | 22.32 | 8.33 |
April | 23.30 | 10.85 |
May | 24.03 | 12.97 |
June | 24.12 | 15.59 |
July | 24.17 | 17.66 |
August | 24.18 | 18.80 |
September | 24.12 | 15.09 |
October | 23.17 | 11.43 |
November | 22.12 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.08 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.18 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.92 | 5.82 |
March | 22.30 | 8.33 |
April | 23.29 | 10.85 |
May | 24.01 | 12.97 |
June | 24.12 | 15.59 |
July | 24.17 | 17.66 |
August | 24.17 | 18.80 |
September | 24.11 | 15.09 |
October | 23.13 | 11.43 |
November | 22.11 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.07 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 4.50 |
February | 22.90 | 5.82 |
March | 23.81 | 8.33 |
April | 24.16 | 10.85 |
May | 24.29 | 12.97 |
June | 24.28 | 15.59 |
July | 24.28 | 17.66 |
August | 24.28 | 18.80 |
September | 24.34 | 15.09 |
October | 24.20 | 11.43 |
November | 23.12 | 8.07 |
December | 22.42 | 5.42 |
Annual Sum or Average | 23.68 | 11.24 |
Minimum of Months | 22.07 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 4.50 |
February | 22.91 | 5.82 |
March | 23.81 | 8.33 |
April | 24.16 | 10.85 |
May | 24.29 | 12.97 |
June | 24.28 | 15.59 |
July | 24.28 | 17.66 |
August | 24.28 | 18.80 |
September | 24.34 | 15.09 |
October | 24.20 | 11.43 |
November | 23.12 | 8.07 |
December | 22.42 | 5.42 |
Annual Sum or Average | 23.68 | 11.24 |
Minimum of Months | 22.07 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 4.50 |
February | 23.15 | 5.82 |
March | 24.13 | 8.33 |
April | 25.10 | 10.85 |
May | 25.83 | 12.97 |
June | 26.11 | 15.59 |
July | 26.32 | 17.66 |
August | 26.33 | 18.80 |
September | 26.03 | 15.09 |
October | 24.89 | 11.43 |
November | 23.38 | 8.07 |
December | 22.69 | 5.42 |
Annual Sum or Average | 24.71 | 11.24 |
Minimum of Months | 22.48 | 4.50 |
Maximum of Months | 26.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.50 |
February | 22.51 | 5.82 |
March | 23.35 | 8.33 |
April | 23.93 | 10.85 |
May | 24.23 | 12.97 |
June | 24.28 | 15.59 |
July | 24.31 | 17.66 |
August | 24.30 | 18.80 |
September | 24.35 | 15.09 |
October | 23.95 | 11.43 |
November | 22.60 | 8.07 |
December | 22.10 | 5.42 |
Annual Sum or Average | 23.48 | 11.24 |
Minimum of Months | 21.86 | 4.50 |
Maximum of Months | 24.35 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.90 | 5.82 |
March | 22.28 | 8.33 |
April | 23.28 | 10.85 |
May | 24.05 | 12.97 |
June | 24.18 | 15.59 |
July | 24.24 | 17.66 |
August | 24.23 | 18.80 |
September | 24.21 | 15.09 |
October | 23.05 | 11.43 |
November | 22.02 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.08 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.24 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 4.50 |
February | 22.48 | 5.82 |
March | 23.32 | 8.33 |
April | 23.92 | 10.85 |
May | 24.19 | 12.97 |
June | 24.29 | 15.59 |
July | 24.31 | 17.66 |
August | 24.30 | 18.80 |
September | 24.34 | 15.09 |
October | 23.90 | 11.43 |
November | 22.55 | 8.07 |
December | 22.08 | 5.42 |
Annual Sum or Average | 23.47 | 11.24 |
Minimum of Months | 21.84 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.84 | 5.82 |
March | 22.14 | 8.33 |
April | 23.21 | 10.85 |
May | 23.93 | 12.97 |
June | 24.15 | 15.59 |
July | 24.23 | 17.66 |
August | 24.21 | 18.80 |
September | 24.12 | 15.09 |
October | 22.83 | 11.43 |
November | 21.95 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.01 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.23 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.94 | 5.82 |
March | 22.36 | 8.33 |
April | 23.34 | 10.85 |
May | 24.05 | 12.97 |
June | 24.12 | 15.59 |
July | 24.17 | 17.66 |
August | 24.17 | 18.80 |
September | 24.13 | 15.09 |
October | 23.22 | 11.43 |
November | 22.15 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.10 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.93 | 5.82 |
March | 22.34 | 8.33 |
April | 23.33 | 10.85 |
May | 24.04 | 12.97 |
June | 24.12 | 15.59 |
July | 24.16 | 17.66 |
August | 24.17 | 18.80 |
September | 24.12 | 15.09 |
October | 23.19 | 11.43 |
November | 22.14 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 23.09 | 11.24 |
Minimum of Months | 21.71 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.50 |
February | 22.92 | 5.82 |
March | 23.83 | 8.33 |
April | 24.17 | 10.85 |
May | 24.29 | 12.97 |
June | 24.27 | 15.59 |
July | 24.27 | 17.66 |
August | 24.27 | 18.80 |
September | 24.34 | 15.09 |
October | 24.21 | 11.43 |
November | 23.15 | 8.07 |
December | 22.44 | 5.42 |
Annual Sum or Average | 23.69 | 11.24 |
Minimum of Months | 22.09 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.50 |
February | 22.92 | 5.82 |
March | 23.83 | 8.33 |
April | 24.17 | 10.85 |
May | 24.29 | 12.97 |
June | 24.27 | 15.59 |
July | 24.28 | 17.66 |
August | 24.27 | 18.80 |
September | 24.34 | 15.09 |
October | 24.21 | 11.43 |
November | 23.15 | 8.07 |
December | 22.44 | 5.42 |
Annual Sum or Average | 23.69 | 11.24 |
Minimum of Months | 22.09 | 4.50 |
Maximum of Months | 24.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 4.50 |
February | 23.80 | 5.82 |
March | 24.77 | 8.33 |
April | 25.73 | 10.85 |
May | 26.45 | 12.97 |
June | 26.71 | 15.59 |
July | 26.92 | 17.66 |
August | 26.92 | 18.80 |
September | 26.66 | 15.09 |
October | 25.54 | 11.43 |
November | 24.03 | 8.07 |
December | 23.35 | 5.42 |
Annual Sum or Average | 25.34 | 11.24 |
Minimum of Months | 23.14 | 4.50 |
Maximum of Months | 26.92 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 4.50 |
February | 22.43 | 5.82 |
March | 23.23 | 8.33 |
April | 23.84 | 10.85 |
May | 24.19 | 12.97 |
June | 24.25 | 15.59 |
July | 24.29 | 17.66 |
August | 24.28 | 18.80 |
September | 24.33 | 15.09 |
October | 23.86 | 11.43 |
November | 22.50 | 8.07 |
December | 22.06 | 5.42 |
Annual Sum or Average | 23.43 | 11.24 |
Minimum of Months | 21.83 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.86 | 5.82 |
March | 22.18 | 8.33 |
April | 23.14 | 10.85 |
May | 23.97 | 12.97 |
June | 24.13 | 15.59 |
July | 24.21 | 17.66 |
August | 24.19 | 18.80 |
September | 24.17 | 15.09 |
October | 22.89 | 11.43 |
November | 21.98 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.02 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.21 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 4.50 |
February | 22.40 | 5.82 |
March | 23.20 | 8.33 |
April | 23.83 | 10.85 |
May | 24.14 | 12.97 |
June | 24.26 | 15.59 |
July | 24.29 | 17.66 |
August | 24.28 | 18.80 |
September | 24.32 | 15.09 |
October | 23.80 | 11.43 |
November | 22.46 | 8.07 |
December | 22.03 | 5.42 |
Annual Sum or Average | 23.41 | 11.24 |
Minimum of Months | 21.82 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.81 | 5.82 |
March | 22.06 | 8.33 |
April | 23.07 | 10.85 |
May | 23.84 | 12.97 |
June | 24.09 | 15.59 |
July | 24.19 | 17.66 |
August | 24.17 | 18.80 |
September | 24.06 | 15.09 |
October | 22.68 | 11.43 |
November | 21.91 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.95 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.19 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.90 | 5.82 |
March | 22.24 | 8.33 |
April | 23.20 | 10.85 |
May | 23.97 | 12.97 |
June | 24.06 | 15.59 |
July | 24.13 | 17.66 |
August | 24.13 | 18.80 |
September | 24.09 | 15.09 |
October | 23.06 | 11.43 |
November | 22.08 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.03 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.13 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.89 | 5.82 |
March | 22.22 | 8.33 |
April | 23.18 | 10.85 |
May | 23.96 | 12.97 |
June | 24.06 | 15.59 |
July | 24.12 | 17.66 |
August | 24.13 | 18.80 |
September | 24.08 | 15.09 |
October | 23.03 | 11.43 |
November | 22.07 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 23.02 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.13 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 4.50 |
February | 22.83 | 5.82 |
March | 23.73 | 8.33 |
April | 24.11 | 10.85 |
May | 24.26 | 12.97 |
June | 24.24 | 15.59 |
July | 24.25 | 17.66 |
August | 24.25 | 18.80 |
September | 24.33 | 15.09 |
October | 24.16 | 11.43 |
November | 23.03 | 8.07 |
December | 22.37 | 5.42 |
Annual Sum or Average | 23.64 | 11.24 |
Minimum of Months | 22.03 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 4.50 |
February | 22.83 | 5.82 |
March | 23.73 | 8.33 |
April | 24.11 | 10.85 |
May | 24.26 | 12.97 |
June | 24.25 | 15.59 |
July | 24.25 | 17.66 |
August | 24.25 | 18.80 |
September | 24.33 | 15.09 |
October | 24.16 | 11.43 |
November | 23.03 | 8.07 |
December | 22.37 | 5.42 |
Annual Sum or Average | 23.64 | 11.24 |
Minimum of Months | 22.03 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.44 | 4.50 |
February | 23.09 | 5.82 |
March | 24.05 | 8.33 |
April | 25.01 | 10.85 |
May | 25.78 | 12.97 |
June | 26.05 | 15.59 |
July | 26.27 | 17.66 |
August | 26.28 | 18.80 |
September | 26.01 | 15.09 |
October | 24.81 | 11.43 |
November | 23.31 | 8.07 |
December | 22.66 | 5.42 |
Annual Sum or Average | 24.65 | 11.24 |
Minimum of Months | 22.44 | 4.50 |
Maximum of Months | 26.28 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 4.50 |
February | 22.37 | 5.82 |
March | 23.13 | 8.33 |
April | 23.76 | 10.85 |
May | 24.15 | 12.97 |
June | 24.23 | 15.59 |
July | 24.27 | 17.66 |
August | 24.26 | 18.80 |
September | 24.33 | 15.09 |
October | 23.78 | 11.43 |
November | 22.43 | 8.07 |
December | 22.03 | 5.42 |
Annual Sum or Average | 23.38 | 11.24 |
Minimum of Months | 21.81 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.84 | 5.82 |
March | 22.11 | 8.33 |
April | 23.03 | 10.85 |
May | 23.91 | 12.97 |
June | 24.09 | 15.59 |
July | 24.19 | 17.66 |
August | 24.17 | 18.80 |
September | 24.15 | 15.09 |
October | 22.76 | 11.43 |
November | 21.94 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.97 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.19 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 4.50 |
February | 22.34 | 5.82 |
March | 23.10 | 8.33 |
April | 23.76 | 10.85 |
May | 24.10 | 12.97 |
June | 24.23 | 15.59 |
July | 24.28 | 17.66 |
August | 24.26 | 18.80 |
September | 24.31 | 15.09 |
October | 23.72 | 11.43 |
November | 22.39 | 8.07 |
December | 22.01 | 5.42 |
Annual Sum or Average | 23.36 | 11.24 |
Minimum of Months | 21.80 | 4.50 |
Maximum of Months | 24.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.79 | 5.82 |
March | 22.01 | 8.33 |
April | 22.95 | 10.85 |
May | 23.77 | 12.97 |
June | 24.05 | 15.59 |
July | 24.16 | 17.66 |
August | 24.13 | 18.80 |
September | 24.02 | 15.09 |
October | 22.56 | 11.43 |
November | 21.88 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.90 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.50 |
February | 21.87 | 5.82 |
March | 22.16 | 8.33 |
April | 23.08 | 10.85 |
May | 23.91 | 12.97 |
June | 24.02 | 15.59 |
July | 24.10 | 17.66 |
August | 24.10 | 18.80 |
September | 24.06 | 15.09 |
October | 22.92 | 11.43 |
November | 22.03 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.98 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.10 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.87 | 5.82 |
March | 22.15 | 8.33 |
April | 23.06 | 10.85 |
May | 23.89 | 12.97 |
June | 24.02 | 15.59 |
July | 24.09 | 17.66 |
August | 24.10 | 18.80 |
September | 24.05 | 15.09 |
October | 22.89 | 11.43 |
November | 22.02 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.97 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.10 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.50 |
February | 22.75 | 5.82 |
March | 23.64 | 8.33 |
April | 24.05 | 10.85 |
May | 24.23 | 12.97 |
June | 24.23 | 15.59 |
July | 24.24 | 17.66 |
August | 24.24 | 18.80 |
September | 24.33 | 15.09 |
October | 24.11 | 11.43 |
November | 22.92 | 8.07 |
December | 22.32 | 5.42 |
Annual Sum or Average | 23.59 | 11.24 |
Minimum of Months | 21.99 | 4.50 |
Maximum of Months | 24.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.50 |
February | 22.75 | 5.82 |
March | 23.64 | 8.33 |
April | 24.05 | 10.85 |
May | 24.23 | 12.97 |
June | 24.23 | 15.59 |
July | 24.24 | 17.66 |
August | 24.24 | 18.80 |
September | 24.32 | 15.09 |
October | 24.11 | 11.43 |
November | 22.92 | 8.07 |
December | 22.32 | 5.42 |
Annual Sum or Average | 23.59 | 11.24 |
Minimum of Months | 21.99 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 4.50 |
February | 22.93 | 5.82 |
March | 23.86 | 8.33 |
April | 24.81 | 10.85 |
May | 25.63 | 12.97 |
June | 25.92 | 15.59 |
July | 26.15 | 17.66 |
August | 26.16 | 18.80 |
September | 25.90 | 15.09 |
October | 24.61 | 11.43 |
November | 23.13 | 8.07 |
December | 22.51 | 5.42 |
Annual Sum or Average | 24.50 | 11.24 |
Minimum of Months | 22.30 | 4.50 |
Maximum of Months | 26.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 4.50 |
February | 22.32 | 5.82 |
March | 23.03 | 8.33 |
April | 23.68 | 10.85 |
May | 24.12 | 12.97 |
June | 24.21 | 15.59 |
July | 24.26 | 17.66 |
August | 24.24 | 18.80 |
September | 24.32 | 15.09 |
October | 23.69 | 11.43 |
November | 22.36 | 8.07 |
December | 22.00 | 5.42 |
Annual Sum or Average | 23.34 | 11.24 |
Minimum of Months | 21.80 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.82 | 5.82 |
March | 22.06 | 8.33 |
April | 22.93 | 10.85 |
May | 23.85 | 12.97 |
June | 24.06 | 15.59 |
July | 24.17 | 17.66 |
August | 24.14 | 18.80 |
September | 24.12 | 15.09 |
October | 22.64 | 11.43 |
November | 21.91 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.93 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.50 |
February | 22.30 | 5.82 |
March | 23.00 | 8.33 |
April | 23.69 | 10.85 |
May | 24.06 | 12.97 |
June | 24.21 | 15.59 |
July | 24.26 | 17.66 |
August | 24.25 | 18.80 |
September | 24.30 | 15.09 |
October | 23.63 | 11.43 |
November | 22.33 | 8.07 |
December | 21.98 | 5.42 |
Annual Sum or Average | 23.32 | 11.24 |
Minimum of Months | 21.79 | 4.50 |
Maximum of Months | 24.30 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.78 | 5.82 |
March | 21.96 | 8.33 |
April | 22.86 | 10.85 |
May | 23.71 | 12.97 |
June | 24.00 | 15.59 |
July | 24.13 | 17.66 |
August | 24.10 | 18.80 |
September | 23.98 | 15.09 |
October | 22.45 | 11.43 |
November | 21.86 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.86 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.13 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.85 | 5.82 |
March | 22.10 | 8.33 |
April | 22.97 | 10.85 |
May | 23.84 | 12.97 |
June | 23.98 | 15.59 |
July | 24.07 | 17.66 |
August | 24.07 | 18.80 |
September | 24.03 | 15.09 |
October | 22.78 | 11.43 |
November | 21.99 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.93 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.07 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.85 | 5.82 |
March | 22.09 | 8.33 |
April | 22.96 | 10.85 |
May | 23.83 | 12.97 |
June | 23.98 | 15.59 |
July | 24.07 | 17.66 |
August | 24.07 | 18.80 |
September | 24.01 | 15.09 |
October | 22.76 | 11.43 |
November | 21.98 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.92 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.07 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.50 |
February | 22.68 | 5.82 |
March | 23.54 | 8.33 |
April | 23.98 | 10.85 |
May | 24.21 | 12.97 |
June | 24.21 | 15.59 |
July | 24.22 | 17.66 |
August | 24.22 | 18.80 |
September | 24.32 | 15.09 |
October | 24.05 | 11.43 |
November | 22.81 | 8.07 |
December | 22.26 | 5.42 |
Annual Sum or Average | 23.54 | 11.24 |
Minimum of Months | 21.95 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.50 |
February | 22.68 | 5.82 |
March | 23.54 | 8.33 |
April | 23.98 | 10.85 |
May | 24.20 | 12.97 |
June | 24.21 | 15.59 |
July | 24.23 | 17.66 |
August | 24.22 | 18.80 |
September | 24.32 | 15.09 |
October | 24.04 | 11.43 |
November | 22.81 | 8.07 |
December | 22.26 | 5.42 |
Annual Sum or Average | 23.54 | 11.24 |
Minimum of Months | 21.95 | 4.50 |
Maximum of Months | 24.32 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 4.50 |
February | 22.83 | 5.82 |
March | 23.74 | 8.33 |
April | 24.69 | 10.85 |
May | 25.54 | 12.97 |
June | 25.86 | 15.59 |
July | 26.11 | 17.66 |
August | 26.12 | 18.80 |
September | 25.84 | 15.09 |
October | 24.46 | 11.43 |
November | 23.02 | 8.07 |
December | 22.43 | 5.42 |
Annual Sum or Average | 24.41 | 11.24 |
Minimum of Months | 22.22 | 4.50 |
Maximum of Months | 26.12 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.50 |
February | 22.26 | 5.82 |
March | 22.89 | 8.33 |
April | 23.56 | 10.85 |
May | 24.05 | 12.97 |
June | 24.18 | 15.59 |
July | 24.25 | 17.66 |
August | 24.23 | 18.80 |
September | 24.30 | 15.09 |
October | 23.54 | 11.43 |
November | 22.28 | 8.07 |
December | 21.96 | 5.42 |
Annual Sum or Average | 23.28 | 11.24 |
Minimum of Months | 21.78 | 4.50 |
Maximum of Months | 24.30 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.81 | 5.82 |
March | 22.02 | 8.33 |
April | 22.84 | 10.85 |
May | 23.76 | 12.97 |
June | 24.01 | 15.59 |
July | 24.15 | 17.66 |
August | 24.12 | 18.80 |
September | 24.07 | 15.09 |
October | 22.50 | 11.43 |
November | 21.88 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.88 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.15 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.50 |
February | 22.24 | 5.82 |
March | 22.85 | 8.33 |
April | 23.58 | 10.85 |
May | 24.00 | 12.97 |
June | 24.18 | 15.59 |
July | 24.25 | 17.66 |
August | 24.23 | 18.80 |
September | 24.28 | 15.09 |
October | 23.47 | 11.43 |
November | 22.25 | 8.07 |
December | 21.94 | 5.42 |
Annual Sum or Average | 23.26 | 11.24 |
Minimum of Months | 21.77 | 4.50 |
Maximum of Months | 24.28 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.77 | 5.82 |
March | 21.92 | 8.33 |
April | 22.76 | 10.85 |
May | 23.60 | 12.97 |
June | 23.94 | 15.59 |
July | 24.10 | 17.66 |
August | 24.07 | 18.80 |
September | 23.91 | 15.09 |
October | 22.33 | 11.43 |
November | 21.83 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.81 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.10 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.83 | 5.82 |
March | 22.04 | 8.33 |
April | 22.86 | 10.85 |
May | 23.75 | 12.97 |
June | 23.93 | 15.59 |
July | 24.05 | 17.66 |
August | 24.05 | 18.80 |
September | 23.97 | 15.09 |
October | 22.61 | 11.43 |
November | 21.94 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.87 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.05 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.83 | 5.82 |
March | 22.02 | 8.33 |
April | 22.85 | 10.85 |
May | 23.73 | 12.97 |
June | 23.93 | 15.59 |
July | 24.04 | 17.66 |
August | 24.04 | 18.80 |
September | 23.95 | 15.09 |
October | 22.58 | 11.43 |
November | 21.94 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.86 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.04 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.50 |
February | 22.56 | 5.82 |
March | 23.35 | 8.33 |
April | 23.86 | 10.85 |
May | 24.15 | 12.97 |
June | 24.18 | 15.59 |
July | 24.21 | 17.66 |
August | 24.21 | 18.80 |
September | 24.31 | 15.09 |
October | 23.91 | 11.43 |
November | 22.64 | 8.07 |
December | 22.17 | 5.42 |
Annual Sum or Average | 23.46 | 11.24 |
Minimum of Months | 21.89 | 4.50 |
Maximum of Months | 24.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.50 |
February | 22.56 | 5.82 |
March | 23.35 | 8.33 |
April | 23.86 | 10.85 |
May | 24.15 | 12.97 |
June | 24.18 | 15.59 |
July | 24.21 | 17.66 |
August | 24.21 | 18.80 |
September | 24.31 | 15.09 |
October | 23.91 | 11.43 |
November | 22.64 | 8.07 |
December | 22.17 | 5.42 |
Annual Sum or Average | 23.46 | 11.24 |
Minimum of Months | 21.89 | 4.50 |
Maximum of Months | 24.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.50 |
February | 22.67 | 5.82 |
March | 23.56 | 8.33 |
April | 24.54 | 10.85 |
May | 25.43 | 12.97 |
June | 25.83 | 15.59 |
July | 26.12 | 17.66 |
August | 26.12 | 18.80 |
September | 25.78 | 15.09 |
October | 24.25 | 11.43 |
November | 22.83 | 8.07 |
December | 22.26 | 5.42 |
Annual Sum or Average | 24.30 | 11.24 |
Minimum of Months | 22.06 | 4.50 |
Maximum of Months | 26.12 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 4.50 |
February | 22.21 | 5.82 |
March | 22.63 | 8.33 |
April | 23.22 | 10.85 |
May | 23.72 | 12.97 |
June | 24.00 | 15.59 |
July | 24.17 | 17.66 |
August | 24.13 | 18.80 |
September | 24.15 | 15.09 |
October | 23.12 | 11.43 |
November | 22.19 | 8.07 |
December | 21.94 | 5.42 |
Annual Sum or Average | 23.11 | 11.24 |
Minimum of Months | 21.80 | 4.50 |
Maximum of Months | 24.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.82 | 5.82 |
March | 22.09 | 8.33 |
April | 22.73 | 10.85 |
May | 23.44 | 12.97 |
June | 23.79 | 15.59 |
July | 24.03 | 17.66 |
August | 23.97 | 18.80 |
September | 23.81 | 15.09 |
October | 22.34 | 11.43 |
November | 21.87 | 8.07 |
December | 21.71 | 5.42 |
Annual Sum or Average | 22.78 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 24.03 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.50 |
February | 22.19 | 5.82 |
March | 22.62 | 8.33 |
April | 23.24 | 10.85 |
May | 23.67 | 12.97 |
June | 23.99 | 15.59 |
July | 24.16 | 17.66 |
August | 24.13 | 18.80 |
September | 24.10 | 15.09 |
October | 23.06 | 11.43 |
November | 22.17 | 8.07 |
December | 21.93 | 5.42 |
Annual Sum or Average | 23.09 | 11.24 |
Minimum of Months | 21.79 | 4.50 |
Maximum of Months | 24.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.78 | 5.82 |
March | 21.99 | 8.33 |
April | 22.69 | 10.85 |
May | 23.31 | 12.97 |
June | 23.69 | 15.59 |
July | 23.94 | 17.66 |
August | 23.91 | 18.80 |
September | 23.61 | 15.09 |
October | 22.23 | 11.43 |
November | 21.82 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.70 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 23.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.81 | 5.82 |
March | 22.04 | 8.33 |
April | 22.70 | 10.85 |
May | 23.42 | 12.97 |
June | 23.72 | 15.59 |
July | 23.94 | 17.66 |
August | 23.90 | 18.80 |
September | 23.70 | 15.09 |
October | 22.33 | 11.43 |
November | 21.88 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.74 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 23.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.81 | 5.82 |
March | 22.03 | 8.33 |
April | 22.70 | 10.85 |
May | 23.41 | 12.97 |
June | 23.72 | 15.59 |
July | 23.93 | 17.66 |
August | 23.90 | 18.80 |
September | 23.69 | 15.09 |
October | 22.32 | 11.43 |
November | 21.87 | 8.07 |
December | 21.70 | 5.42 |
Annual Sum or Average | 22.74 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 23.93 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.50 |
February | 22.38 | 5.82 |
March | 22.91 | 8.33 |
April | 23.48 | 10.85 |
May | 23.88 | 12.97 |
June | 24.07 | 15.59 |
July | 24.17 | 17.66 |
August | 24.15 | 18.80 |
September | 24.22 | 15.09 |
October | 23.46 | 11.43 |
November | 22.42 | 8.07 |
December | 22.04 | 5.42 |
Annual Sum or Average | 23.26 | 11.24 |
Minimum of Months | 21.87 | 4.50 |
Maximum of Months | 24.22 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.50 |
February | 22.38 | 5.82 |
March | 22.91 | 8.33 |
April | 23.48 | 10.85 |
May | 23.88 | 12.97 |
June | 24.08 | 15.59 |
July | 24.17 | 17.66 |
August | 24.15 | 18.80 |
September | 24.22 | 15.09 |
October | 23.46 | 11.43 |
November | 22.42 | 8.07 |
December | 22.04 | 5.42 |
Annual Sum or Average | 23.26 | 11.24 |
Minimum of Months | 21.87 | 4.50 |
Maximum of Months | 24.22 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:22
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.50 |
February | 22.67 | 5.82 |
March | 23.62 | 8.33 |
April | 24.76 | 10.85 |
May | 25.73 | 12.97 |
June | 26.28 | 15.59 |
July | 26.71 | 17.66 |
August | 26.66 | 18.80 |
September | 26.08 | 15.09 |
October | 24.28 | 11.43 |
November | 22.83 | 8.07 |
December | 22.18 | 5.42 |
Annual Sum or Average | 24.49 | 11.24 |
Minimum of Months | 22.00 | 4.50 |
Maximum of Months | 26.71 | 18.80 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:22
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.234604E+12 | 125331.846 | 14-JAN-18:00 | 22204.399 | 56867.515 | 19223.461 | 13713.950 | 0.000 | 10720.100 | 1456.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.203521E+12 | 128167.627 | 18-FEB-19:00 | 25049.151 | 51564.864 | 19223.461 | 19138.904 | 0.000 | 10720.100 | 1456.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.212755E+12 | 122197.413 | 02-MAR-18:15 | 22204.399 | 56867.515 | 19223.461 | 0.000 | 10172.479 | 10720.100 | 1456.532 | 407.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.207318E+12 | 154437.580 | 27-APR-16:30 | 18221.747 | 56933.809 | 19223.461 | 0.000 | 55561.534 | 0.000 | 1456.532 | 1892.054 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.218137E+12 | 145346.410 | 15-MAY-16:30 | 18221.747 | 56933.809 | 19223.461 | 0.000 | 46819.369 | 0.000 | 1456.532 | 1543.050 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.216138E+12 | 156965.030 | 28-JUN-17:15 | 22204.399 | 56867.515 | 19223.461 | 0.000 | 54161.539 | 0.000 | 1456.532 | 1905.948 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.239652E+12 | 163317.969 | 31-JUL-17:00 | 22204.399 | 56867.515 | 19223.461 | 0.000 | 60306.921 | 0.000 | 1456.532 | 2113.252 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.249060E+12 | 164379.169 | 29-AUG-19:15 | 25049.151 | 49704.829 | 19223.461 | 0.000 | 55284.511 | 10720.100 | 1456.532 | 1995.013 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.224711E+12 | 152510.244 | 14-SEP-16:30 | 18221.747 | 56933.809 | 19223.461 | 0.000 | 53606.948 | 0.000 | 1456.532 | 1919.304 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.214394E+12 | 127035.657 | 07-OCT-17:45 | 22204.399 | 56867.515 | 19223.461 | 0.000 | 14799.710 | 10720.100 | 1456.532 | 618.051 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.212684E+12 | 126197.813 | 29-NOV-18:15 | 22204.399 | 56867.515 | 19223.461 | 14580.169 | 0.000 | 10720.100 | 1456.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.230755E+12 | 128004.368 | 26-DEC-18:00 | 22204.399 | 56867.515 | 19223.461 | 16386.472 | 0.000 | 10720.100 | 1456.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.266373E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.203521E+12 | 122197.413 | 18221.747 | 49704.829 | 19223.461 | 0.000 | 0.000 | 0.000 | 1456.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.249060E+12 | 164379.169 | 25049.151 | 56933.809 | 19223.461 | 19138.904 | 60306.921 | 10720.100 | 1456.532 | 2113.252 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:22
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.197866E+12 | 164756.663 | 15-JAN-08:30 | 0.000 | 0.000 | 0.000 | 164756.663 | 85232.026 | 85232.026 | 79524.637 |
February | 0.149855E+12 | 194908.942 | 19-FEB-06:00 | 0.000 | 0.000 | 0.000 | 194908.942 | 84348.768 | 84348.768 | 110560.175 |
March | 0.115078E+12 | 127502.905 | 24-MAR-06:15 | 0.000 | 0.000 | 0.000 | 127502.905 | 85127.539 | 85127.539 | 42375.366 |
April | 0.101254E+12 | 101537.833 | 18-APR-06:30 | 0.000 | 0.000 | 0.000 | 101537.833 | 85044.310 | 85044.310 | 16493.523 |
May | 0.989931E+11 | 84671.740 | 02-MAY-06:00 | 0.000 | 0.000 | 0.000 | 84671.740 | 84671.740 | 84671.740 | 0.000 |
June | 0.922229E+11 | 83352.739 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 83352.739 | 83352.739 | 83352.739 | 0.000 |
July | 0.926743E+11 | 82317.397 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 82317.397 | 82317.397 | 82317.397 | 0.000 |
August | 0.918707E+11 | 81787.482 | 29-AUG-06:00 | 0.000 | 0.000 | 0.000 | 81787.482 | 81787.482 | 81787.482 | 0.000 |
September | 0.901155E+11 | 82440.072 | 28-SEP-06:00 | 0.000 | 0.000 | 0.000 | 82440.072 | 82440.072 | 82440.072 | 0.000 |
October | 0.970510E+11 | 95931.753 | 28-OCT-06:45 | 0.000 | 0.000 | 0.000 | 95931.753 | 83508.074 | 83508.074 | 12423.679 |
November | 0.130734E+12 | 133237.510 | 30-NOV-10:00 | 0.000 | 0.000 | 0.000 | 133237.510 | 77511.325 | 77511.325 | 55726.185 |
December | 0.175423E+12 | 160663.071 | 26-DEC-08:00 | 0.000 | 0.000 | 0.000 | 160663.071 | 84571.359 | 84571.359 | 76091.712 |
Annual Sum or Average | 0.143314E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.901155E+11 | 81787.482 | 0.000 | 0.000 | 0.000 | 81787.482 | 77511.325 | 77511.325 | 0.000 | |
Maximum of Months | 0.197866E+12 | 194908.942 | 0.000 | 0.000 | 0.000 | 194908.942 | 85232.026 | 85232.026 | 110560.175 |