Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695

Simulation Timestamp: 2018-10-19 09:40:15


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4625.87 590.30 655.23
Net Site Energy 4625.87 590.30 655.23
Total Source Energy 11329.06 1445.68 1604.71
Net Source Energy 11329.06 1445.68 1604.71


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 123.71 391.48 0.00 0.00 0.00 0.00
Cooling 405.35 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.38 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 708.77 0.00 0.00 0.00 0.00 0.00
Pumps 42.97 0.00 0.00 0.00 0.00 0.00
Heat Rejection 13.98 0.00 0.00 0.00 0.00 1349.23
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1202.88 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3031.50 1594.36 0.00 0.00 0.00 6127.75
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 391.48 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 123.71 0.00 0.00 0.00 0.00 0.00
Cooling General 405.35 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.38 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 708.77 0.00 0.00 0.00 0.00 0.00
Pumps General 42.97 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 13.98 0.00 0.00 0.00 0.00 1349.23
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1202.88 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.83 0.00 0.00 0.00 0.00 0.00
HVAC 183.40 225.83 0.00 0.00 0.00 0.87
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 429.40 225.83 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.62 0.00 0.00 0.00 0.00 0.00
HVAC 165.23 203.45 0.00 0.00 0.00 0.78
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 386.85 203.45 0.00 0.00 0.00 0.78


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3031.50 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3031.50 100.00
     
Total On-Site and Utility Electric Sources 3031.50 100.00
Total Electricity End Uses 3031.50 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6127.75 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6127.75 100.00
Total Water End Uses 6127.75 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 124.75
Time Setpoint Not Met During Occupied Cooling 390.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1493.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Weather File Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Latitude [deg] 39.72
Longitude [deg] -104.8
Elevation [m] 1726.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JUN-19:30 19-MAR-07:15 - - - 26-JUN-17:15
Heating 0.00 195077.61 0.00 0.00 0.00 0.00
Cooling 58819.02 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 22475.07 0.00 0.00 0.00 0.00 0.00
Pumps 1376.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1866.58 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 87982.13 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 170957.00 283059.73 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 195077.61 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 58819.02 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 22475.07 0.00 0.00 0.00 0.00 0.00
Pumps General 1376.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1866.58 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 87982.13 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 391.80 424.37 0.00 0.00 0.00
Cooling 1283.75 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.25 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2244.69 0.00 0.00 0.00 0.00
Pumps 136.09 0.00 0.00 0.00 0.00
Heat Rejection 44.28 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1303.92 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9600.77 1728.29 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 55.50 60.11 0.00 0.00 0.00
Cooling 181.84 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.53 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 317.95 0.00 0.00 0.00 0.00
Pumps 19.28 0.00 0.00 0.00 0.00
Heat Rejection 6.27 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 184.69 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1359.90 244.80 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 55.50 60.11 0.00 0.00 0.00
Cooling 181.84 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.53 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 317.95 0.00 0.00 0.00 0.00
Pumps 19.28 0.00 0.00 0.00 0.00
Heat Rejection 6.27 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 184.69 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1359.90 244.80 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB -17.90 0.00 -17.90 Wetbulb [C] 2.50 180.00
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 33.90 14.80 15.00 Wetbulb [C] 3.60 30.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.36 0.00 0.00 3.36 3.36 2.653 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.653 0.426 0.308              
North Total or Average           423.59 2.653 0.426 0.308              
Non-North Total or Average           726.80 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.67 83.67 168.38
Exterior Lighting Total 10720.10           168.38



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 241504.50 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 193203.60      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3140.46 2013.48 1126.98 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   2982.23 1915.92 1066.31 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4135.24 2650.50 1484.74 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2027.42 1332.72 694.70 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1470.94 968.40 502.54 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1444.78 952.15 492.63 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1851.76 1186.33 665.43 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1922.53 1232.04 690.49 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4095.57 2619.00 1476.57 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3864.28 2475.16 1389.12 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3729.89 2382.43 1347.46 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2775.38 1810.67 964.71 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2024.27 1317.46 706.80 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2002.26 1303.75 698.50 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2485.33 1589.49 895.84 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2514.85 1608.02 906.83 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4115.38 2637.89 1477.49 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3893.13 2498.43 1394.70 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3524.24 2258.52 1265.72 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2810.50 1837.88 972.62 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2072.15 1350.31 721.84 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2050.22 1336.64 713.57 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2536.83 1624.82 912.02 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2551.79 1634.20 917.59 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4126.84 2649.01 1477.83 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3905.42 2510.04 1395.38 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3514.11 2255.96 1258.15 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2813.34 1843.53 969.81 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2089.20 1363.21 725.99 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2067.24 1349.52 717.71 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2554.62 1638.24 916.38 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2567.44 1646.28 921.16 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4168.83 2678.54 1490.29 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3948.84 2540.42 1408.42 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3553.90 2284.05 1269.85 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2847.97 1868.44 979.53 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2134.20 1393.11 741.09 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2112.21 1379.40 732.81 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2599.54 1668.30 931.24 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2611.99 1676.11 935.88 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4116.59 2648.57 1468.03 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3895.27 2509.63 1385.64 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3503.35 2254.97 1248.38 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2789.52 1834.40 955.12 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2086.16 1364.78 721.38 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2064.26 1351.12 713.15 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2552.10 1640.06 912.03 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2564.46 1647.82 916.64 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4098.70 2639.78 1458.92 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3877.62 2500.99 1376.63 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3486.73 2246.87 1239.86 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2766.74 1822.45 944.30 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2072.01 1357.36 714.65 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2050.17 1343.73 706.44 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2537.60 1632.34 905.26 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2549.90 1640.06 909.84 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4100.51 2643.09 1457.41 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3879.85 2504.55 1375.29 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3488.27 2249.94 1238.33 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2762.89 1822.14 940.75 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2077.63 1362.12 715.51 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2055.87 1348.54 707.33 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2541.24 1635.87 905.37 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2553.52 1643.58 909.94 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4241.33 2733.36 1507.97 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4017.93 2593.03 1424.90 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3580.15 2309.60 1270.55 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2797.59 1845.92 951.66 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2200.14 1439.66 760.47 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2177.99 1425.84 752.15 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2621.46 1687.47 933.98 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2635.24 1696.12 939.12 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5319.86 3404.52 1915.35 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4949.54 3177.19 1772.35 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4646.23 2980.52 1665.72 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3614.97 2354.71 1260.26 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2946.98 1891.87 1055.11 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2941.37 1888.32 1053.06 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3828.40 2446.20 1382.20 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3839.15 2452.93 1386.22 0.64 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3140.46 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   2982.23 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4135.24 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2027.42 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1470.94 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1444.78 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   1851.76 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   1922.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4095.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3864.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3729.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2775.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2024.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2002.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2485.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2514.85 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4115.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3893.13 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3524.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2810.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2072.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2050.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2536.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2551.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4126.84 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3905.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3514.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2813.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2089.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2067.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2554.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2567.44 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4168.83 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   3948.84 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   3553.90 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   2847.97 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2134.20 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2112.21 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2599.54 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2611.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4116.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3895.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3503.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2789.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2086.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2064.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2552.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2564.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4098.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3877.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3486.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2766.74 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2072.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2050.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2537.60 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2549.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4100.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3879.85 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3488.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2762.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2077.63 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2055.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2541.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2553.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4241.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4017.93 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3580.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2797.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2200.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2177.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2621.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2635.24 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5319.86 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   4949.54 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4646.23 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   3614.97 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2946.98 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2941.37 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3828.40 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3839.15 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   3345.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   3358.06 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   4259.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   3358.06 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   2544.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   2544.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   2529.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   2537.77 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   3258.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   3264.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   3283.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   3264.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   2279.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   2279.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   2276.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   2277.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   3233.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   3239.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   3236.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   3239.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   2226.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   2226.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   2221.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   2221.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   3266.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   3271.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   3266.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   3271.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   2234.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   2234.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   2230.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   2230.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   3277.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   3279.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   3277.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   3279.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   2226.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   2226.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   2224.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   2224.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   3358.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   3360.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   3358.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   3360.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   2287.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   2287.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   2286.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   2286.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   3409.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   3410.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   3409.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   3410.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   2323.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   2323.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   2323.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   2323.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   3468.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   3467.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   3468.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   3467.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   2368.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   2368.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   2369.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   2369.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   3681.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   3676.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   3681.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   3676.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   2556.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   2556.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   2561.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   2561.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   4489.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   4491.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   4489.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   4491.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   3428.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   3428.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   3423.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   3423.89 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 290.94 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 278.00 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 378.27 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 195.24 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 140.13 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 137.73 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.37 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 172.35 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 381.23 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 360.50 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 342.83 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 265.65 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 191.79 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 189.77 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 224.98 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 227.71 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 383.89 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 364.21 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.80 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.94 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.79 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.77 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.34 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.73 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 385.73 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 366.13 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.62 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 270.97 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.81 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.79 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.44 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 233.63 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 390.27 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 370.79 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.93 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 274.82 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 203.31 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 201.29 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 236.97 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.12 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 385.98 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 366.38 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.78 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.92 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 199.22 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 197.20 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.89 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 234.03 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 384.81 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 365.23 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.70 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 268.27 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.20 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.19 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.82 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.96 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 385.41 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 365.87 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.26 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 268.33 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 198.96 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 196.96 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.40 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 233.54 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 398.86 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 379.05 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 333.18 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 271.95 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 210.46 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.42 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 240.08 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.35 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.44 495.52 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.41 463.59 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.39 432.40 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.56 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 270.01 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 269.48 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 352.12 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 353.11 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0053 1339.76 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2243.73 2692.47 0.216 0.260 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
G NW APARTMENT 2143.94 2572.73 0.207 0.248 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 30.35 0.00543
OFFICE 2917.26 3500.72 0.281 0.338 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 33.34 0.00543
G NE APARTMENT 1505.66 1806.80 0.145 0.174 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 28.28 0.00543
G N1 APARTMENT 1080.62 1296.75 0.104 0.125 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
G N2 APARTMENT 1062.18 1274.62 0.102 0.123 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
G S1 APARTMENT 1275.30 1530.36 0.123 0.148 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
G S2 APARTMENT 1329.17 1595.00 0.128 0.154 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F2 SW APARTMENT 2940.00 3528.00 0.284 0.340 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.09 0.00543
F2 NW APARTMENT 2780.18 3336.21 0.268 0.322 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F2 SE APARTMENT 2643.90 3172.68 0.255 0.306 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F2 NE APARTMENT 2048.66 2458.39 0.198 0.237 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F2 N1 APARTMENT 1479.05 1774.86 0.143 0.171 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F2 N2 APARTMENT 1463.47 1756.16 0.141 0.169 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F2 S1 APARTMENT 1735.03 2082.04 0.167 0.201 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F2 S2 APARTMENT 1756.09 2107.31 0.169 0.203 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F3 SW APARTMENT 2960.54 3552.64 0.286 0.343 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F3 NW APARTMENT 2808.80 3370.56 0.271 0.325 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F3 SE APARTMENT 2504.86 3005.84 0.242 0.290 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F3 NE APARTMENT 2081.75 2498.10 0.201 0.241 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F3 N1 APARTMENT 1517.61 1821.13 0.146 0.176 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F3 N2 APARTMENT 1502.07 1802.49 0.145 0.174 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F3 S1 APARTMENT 1776.40 2131.68 0.171 0.206 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F3 S2 APARTMENT 1787.07 2144.48 0.172 0.207 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F4 SW APARTMENT 2974.81 3569.77 0.287 0.344 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F4 NW APARTMENT 2823.62 3388.34 0.272 0.327 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F4 SE APARTMENT 2503.50 3004.20 0.242 0.290 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F4 NE APARTMENT 2089.74 2507.68 0.202 0.242 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F4 N1 APARTMENT 1533.20 1839.84 0.148 0.177 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F4 N2 APARTMENT 1517.63 1821.15 0.146 0.176 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F4 S1 APARTMENT 1792.56 2151.08 0.173 0.208 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F4 S2 APARTMENT 1801.71 2162.05 0.174 0.209 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
M SW APARTMENT 3009.77 3611.72 0.290 0.348 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
M NW APARTMENT 2859.54 3431.44 0.276 0.331 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
M SE APARTMENT 2536.75 3044.11 0.245 0.294 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
M NE APARTMENT 2119.41 2543.29 0.204 0.245 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
M N1 APARTMENT 1567.94 1881.53 0.151 0.182 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
M N2 APARTMENT 1552.34 1862.81 0.150 0.180 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
M S1 APARTMENT 1827.49 2192.99 0.176 0.212 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
M S2 APARTMENT 1836.37 2203.65 0.177 0.213 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F6 SW APARTMENT 2976.73 3572.08 0.287 0.345 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F6 NW APARTMENT 2825.57 3390.68 0.273 0.327 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F6 SE APARTMENT 2504.71 3005.65 0.242 0.290 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F6 NE APARTMENT 2081.63 2497.96 0.201 0.241 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F6 N1 APARTMENT 1536.36 1843.63 0.148 0.178 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F6 N2 APARTMENT 1520.82 1824.99 0.147 0.176 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F6 S1 APARTMENT 1796.02 2155.23 0.173 0.208 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F6 S2 APARTMENT 1804.84 2165.81 0.174 0.209 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F7 SW APARTMENT 2967.70 3561.24 0.286 0.344 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F7 NW APARTMENT 2816.70 3380.04 0.272 0.326 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F7 SE APARTMENT 2496.43 2995.71 0.241 0.289 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F7 NE APARTMENT 2068.92 2482.71 0.200 0.240 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F7 N1 APARTMENT 1528.49 1834.19 0.147 0.177 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F7 N2 APARTMENT 1512.98 1815.58 0.146 0.175 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F7 S1 APARTMENT 1787.80 2145.36 0.172 0.207 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F7 S2 APARTMENT 1796.57 2155.89 0.173 0.208 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F8 SW APARTMENT 2972.36 3566.83 0.287 0.344 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F8 NW APARTMENT 2821.64 3385.97 0.272 0.327 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F8 SE APARTMENT 2500.77 3000.92 0.241 0.289 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F8 NE APARTMENT 2069.41 2483.29 0.200 0.240 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F8 N1 APARTMENT 1534.40 1841.28 0.148 0.178 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F8 N2 APARTMENT 1518.95 1822.74 0.147 0.176 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F8 S1 APARTMENT 1792.31 2150.77 0.173 0.207 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F8 S2 APARTMENT 1801.08 2161.29 0.174 0.208 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F9 SW APARTMENT 3076.05 3691.26 0.297 0.356 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.46 0.00543
F9 NW APARTMENT 2923.26 3507.91 0.282 0.338 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.72 0.00543
F9 SE APARTMENT 2569.52 3083.43 0.248 0.297 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
F9 NE APARTMENT 2097.33 2516.80 0.202 0.243 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 28.83 0.00543
F9 N1 APARTMENT 1623.07 1947.69 0.157 0.188 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F9 N2 APARTMENT 1607.34 1928.81 0.155 0.186 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 28.68 0.00543
F9 S1 APARTMENT 1851.48 2221.78 0.179 0.214 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
F9 S2 APARTMENT 1861.32 2233.59 0.180 0.215 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
T SW APARTMENT 3821.53 4585.83 0.369 0.442 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 33.23 0.00543
T NW APARTMENT 3575.33 4290.39 0.345 0.414 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.12 0.00543
T SE APARTMENT 3334.77 4001.73 0.322 0.386 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53 0.00543
T NE APARTMENT 2665.03 3198.04 0.257 0.309 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.94 0.00543
T N1 APARTMENT 2082.30 2498.76 0.201 0.241 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.90 0.00543
T N2 APARTMENT 2078.25 2493.90 0.200 0.241 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.90 0.00543
T S1 APARTMENT 2715.58 3258.70 0.262 0.314 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543
T S2 APARTMENT 2723.24 3267.89 0.263 0.315 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.71 0.00543


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1975.48 2370.58 0.108 0.130 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
G NW APARTMENT 1986.15 2383.38 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
OFFICE 2348.90 2818.68 0.129 0.155 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -17.90 0.00096
G NE APARTMENT 1986.15 2383.38 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
G N1 APARTMENT 1298.57 1558.29 0.071 0.085 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
G N2 APARTMENT 1298.57 1558.29 0.071 0.085 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
G S1 APARTMENT 1285.28 1542.33 0.070 0.085 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
G S2 APARTMENT 1292.46 1550.95 0.071 0.085 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -17.90 0.00096
F2 SW APARTMENT 1901.76 2282.12 0.104 0.125 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 NW APARTMENT 1907.12 2288.54 0.105 0.125 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 SE APARTMENT 1922.81 2307.38 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 NE APARTMENT 1907.12 2288.54 0.105 0.125 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 N1 APARTMENT 1074.35 1289.23 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 N2 APARTMENT 1074.35 1289.23 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 S1 APARTMENT 1071.40 1285.68 0.059 0.070 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F2 S2 APARTMENT 1072.74 1287.28 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 SW APARTMENT 1880.81 2256.97 0.103 0.124 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 NW APARTMENT 1886.06 2263.27 0.103 0.124 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 SE APARTMENT 1883.03 2259.63 0.103 0.124 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 NE APARTMENT 1886.06 2263.27 0.103 0.124 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 N1 APARTMENT 1029.59 1235.51 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 N2 APARTMENT 1029.59 1235.51 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 S1 APARTMENT 1025.03 1230.03 0.056 0.067 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F3 S2 APARTMENT 1025.23 1230.27 0.056 0.067 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 SW APARTMENT 1908.65 2290.38 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 NW APARTMENT 1913.07 2295.68 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 SE APARTMENT 1908.87 2290.65 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 NE APARTMENT 1913.07 2295.68 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 N1 APARTMENT 1036.39 1243.67 0.057 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 N2 APARTMENT 1036.39 1243.67 0.057 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 S1 APARTMENT 1032.47 1238.97 0.057 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F4 S2 APARTMENT 1032.50 1239.00 0.057 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M SW APARTMENT 1917.73 2301.27 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M NW APARTMENT 1920.10 2304.13 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M SE APARTMENT 1917.75 2301.30 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M NE APARTMENT 1920.10 2304.13 0.105 0.126 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M N1 APARTMENT 1029.27 1235.13 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M N2 APARTMENT 1029.27 1235.13 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M S1 APARTMENT 1027.41 1232.89 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
M S2 APARTMENT 1027.41 1232.89 0.056 0.068 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 SW APARTMENT 1986.21 2383.46 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 NW APARTMENT 1988.28 2385.93 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 SE APARTMENT 1986.21 2383.46 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 NE APARTMENT 1988.28 2385.93 0.109 0.131 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 N1 APARTMENT 1081.19 1297.42 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 N2 APARTMENT 1081.19 1297.42 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 S1 APARTMENT 1079.58 1295.49 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F6 S2 APARTMENT 1079.58 1295.49 0.059 0.071 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 SW APARTMENT 2029.79 2435.74 0.111 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 NW APARTMENT 2030.60 2436.72 0.111 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 SE APARTMENT 2029.79 2435.74 0.111 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 NE APARTMENT 2030.60 2436.72 0.111 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 N1 APARTMENT 1111.57 1333.88 0.061 0.073 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 N2 APARTMENT 1111.57 1333.88 0.061 0.073 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 S1 APARTMENT 1111.17 1333.41 0.061 0.073 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F7 S2 APARTMENT 1111.17 1333.41 0.061 0.073 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 SW APARTMENT 2079.33 2495.19 0.114 0.137 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 NW APARTMENT 2078.78 2494.54 0.114 0.137 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 SE APARTMENT 2079.33 2495.19 0.114 0.137 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 NE APARTMENT 2078.78 2494.54 0.114 0.137 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 N1 APARTMENT 1149.34 1379.21 0.063 0.076 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 N2 APARTMENT 1149.34 1379.21 0.063 0.076 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 S1 APARTMENT 1150.34 1380.40 0.063 0.076 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F8 S2 APARTMENT 1150.34 1380.40 0.063 0.076 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 SW APARTMENT 2259.69 2711.63 0.124 0.149 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 NW APARTMENT 2255.27 2706.32 0.124 0.148 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 SE APARTMENT 2259.69 2711.63 0.124 0.149 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 NE APARTMENT 2255.27 2706.32 0.124 0.148 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 N1 APARTMENT 1307.92 1569.51 0.072 0.086 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 N2 APARTMENT 1307.92 1569.51 0.072 0.086 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 S1 APARTMENT 1312.44 1574.92 0.072 0.086 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
F9 S2 APARTMENT 1312.44 1574.92 0.072 0.086 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T SW APARTMENT 2942.86 3531.43 0.161 0.194 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T NW APARTMENT 2944.86 3533.84 0.161 0.194 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T SE APARTMENT 2942.86 3531.43 0.161 0.194 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T NE APARTMENT 2944.86 3533.84 0.161 0.194 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T N1 APARTMENT 2046.14 2455.37 0.112 0.135 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T N2 APARTMENT 2046.14 2455.37 0.112 0.135 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T S1 APARTMENT 2041.84 2450.21 0.112 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096
T S2 APARTMENT 2041.84 2450.21 0.112 0.134 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -17.90 0.00096


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.26 0.26 0.13 0.13
AIRLOOP G NW 0.25 0.25 0.13 0.13
AIRLOOP OFFICE 0.34 0.34 0.15 0.15
AIRLOOP G NE 0.17 0.17 0.13 0.13
AIRLOOP G N1 0.13 0.13 0.09 0.09
AIRLOOP G N2 0.12 0.12 0.09 0.09
AIRLOOP G S1 0.15 0.15 0.08 0.08
AIRLOOP G S2 0.15 0.15 0.09 0.09
AIRLOOP F2 SW 0.34 0.34 0.13 0.13
AIRLOOP F2 NW 0.32 0.32 0.13 0.13
AIRLOOP F2 SE 0.31 0.31 0.13 0.13
AIRLOOP F2 NE 0.24 0.24 0.13 0.13
AIRLOOP F2 N1 0.17 0.17 0.07 0.07
AIRLOOP F2 N2 0.17 0.17 0.07 0.07
AIRLOOP F2 S1 0.20 0.20 0.07 0.07
AIRLOOP F2 S2 0.20 0.20 0.07 0.07
AIRLOOP F3 SW 0.34 0.34 0.12 0.12
AIRLOOP F3 NW 0.33 0.33 0.12 0.12
AIRLOOP F3 SE 0.29 0.29 0.12 0.12
AIRLOOP F3 NE 0.24 0.24 0.12 0.12
AIRLOOP F3 N1 0.18 0.18 0.07 0.07
AIRLOOP F3 N2 0.17 0.17 0.07 0.07
AIRLOOP F3 S1 0.21 0.21 0.07 0.07
AIRLOOP F3 S2 0.21 0.21 0.07 0.07
AIRLOOP F4 SW 0.34 0.34 0.13 0.13
AIRLOOP F4 NW 0.33 0.33 0.13 0.13
AIRLOOP F4 SE 0.29 0.29 0.13 0.13
AIRLOOP F4 NE 0.24 0.24 0.13 0.13
AIRLOOP F4 N1 0.18 0.18 0.07 0.07
AIRLOOP F4 N2 0.18 0.18 0.07 0.07
AIRLOOP F4 S1 0.21 0.21 0.07 0.07
AIRLOOP F4 S2 0.21 0.21 0.07 0.07
AIRLOOP M SW 0.35 0.35 0.13 0.13
AIRLOOP M NW 0.33 0.33 0.13 0.13
AIRLOOP M SE 0.29 0.29 0.13 0.13
AIRLOOP M NE 0.25 0.25 0.13 0.13
AIRLOOP M N1 0.18 0.18 0.07 0.07
AIRLOOP M N2 0.18 0.18 0.07 0.07
AIRLOOP M S1 0.21 0.21 0.07 0.07
AIRLOOP M S2 0.21 0.21 0.07 0.07
AIRLOOP F6 SW 0.34 0.34 0.13 0.13
AIRLOOP F6 NW 0.33 0.33 0.13 0.13
AIRLOOP F6 SE 0.29 0.29 0.13 0.13
AIRLOOP F6 NE 0.24 0.24 0.13 0.13
AIRLOOP F6 N1 0.18 0.18 0.07 0.07
AIRLOOP F6 N2 0.18 0.18 0.07 0.07
AIRLOOP F6 S1 0.21 0.21 0.07 0.07
AIRLOOP F6 S2 0.21 0.21 0.07 0.07
AIRLOOP F7 SW 0.34 0.34 0.13 0.13
AIRLOOP F7 NW 0.33 0.33 0.13 0.13
AIRLOOP F7 SE 0.29 0.29 0.13 0.13
AIRLOOP F7 NE 0.24 0.24 0.13 0.13
AIRLOOP F7 N1 0.18 0.18 0.07 0.07
AIRLOOP F7 N2 0.18 0.18 0.07 0.07
AIRLOOP F7 S1 0.21 0.21 0.07 0.07
AIRLOOP F7 S2 0.21 0.21 0.07 0.07
AIRLOOP F8 SW 0.34 0.34 0.14 0.14
AIRLOOP F8 NW 0.33 0.33 0.14 0.14
AIRLOOP F8 SE 0.29 0.29 0.14 0.14
AIRLOOP F8 NE 0.24 0.24 0.14 0.14
AIRLOOP F8 N1 0.18 0.18 0.08 0.08
AIRLOOP F8 N2 0.18 0.18 0.08 0.08
AIRLOOP F8 S1 0.21 0.21 0.08 0.08
AIRLOOP F8 S2 0.21 0.21 0.08 0.08
AIRLOOP F9 SW 0.36 0.36 0.15 0.15
AIRLOOP F9 NW 0.34 0.34 0.15 0.15
AIRLOOP F9 SE 0.30 0.30 0.15 0.15
AIRLOOP F9 NE 0.24 0.24 0.15 0.15
AIRLOOP F9 N1 0.19 0.19 0.09 0.09
AIRLOOP F9 N2 0.19 0.19 0.09 0.09
AIRLOOP F9 S1 0.21 0.21 0.09 0.09
AIRLOOP F9 S2 0.22 0.22 0.09 0.09
AIRLOOP T SW 0.44 0.44 0.19 0.19
AIRLOOP T NW 0.41 0.41 0.19 0.19
AIRLOOP T SE 0.39 0.39 0.19 0.19
AIRLOOP T NE 0.31 0.31 0.19 0.19
AIRLOOP T N1 0.24 0.24 0.13 0.13
AIRLOOP T N2 0.24 0.24 0.13 0.13
AIRLOOP T S1 0.31 0.31 0.13 0.13
AIRLOOP T S2 0.32 0.32 0.13 0.13



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2499.75 5246.25 518.50
G NW APARTMENT 2290.50 6263.50 745.75
OFFICE 896.75 745.75 59.75
G NE APARTMENT 2426.75 6279.00 794.00
G N1 APARTMENT 1836.75 6536.75 570.50
G N2 APARTMENT 1844.75 6530.25 570.75
G S1 APARTMENT 2193.25 5447.75 421.25
G S2 APARTMENT 2222.00 5390.75 411.25
F2 SW APARTMENT 3317.25 3631.75 270.25
F2 NW APARTMENT 2614.00 5419.50 419.50
F2 SE APARTMENT 3521.25 3516.50 245.50
F2 NE APARTMENT 2721.25 5457.00 449.50
F2 N1 APARTMENT 2216.75 5698.75 301.75
F2 N2 APARTMENT 2221.00 5705.00 303.00
F2 S1 APARTMENT 3290.25 3415.75 212.75
F2 S2 APARTMENT 3307.50 3384.75 209.25
F3 SW APARTMENT 3506.25 3380.25 254.75
F3 NW APARTMENT 2679.00 5214.50 390.25
F3 SE APARTMENT 3629.50 3404.75 252.50
F3 NE APARTMENT 2781.25 5263.25 412.25
F3 N1 APARTMENT 2331.50 5442.00 262.50
F3 N2 APARTMENT 2337.75 5447.50 263.50
F3 S1 APARTMENT 3622.25 2990.75 193.00
F3 S2 APARTMENT 3625.75 2989.75 192.75
F4 SW APARTMENT 3513.50 3373.00 258.50
F4 NW APARTMENT 2679.00 5180.00 394.00
F4 SE APARTMENT 3614.75 3429.00 258.25
F4 NE APARTMENT 2784.00 5248.50 415.75
F4 N1 APARTMENT 2344.25 5383.50 258.25
F4 N2 APARTMENT 2353.50 5387.75 258.75
F4 S1 APARTMENT 3656.25 2941.00 194.00
F4 S2 APARTMENT 3657.50 2943.25 192.75
M SW APARTMENT 3521.75 3365.25 254.25
M NW APARTMENT 2686.25 5158.00 387.25
M SE APARTMENT 3622.75 3423.00 255.75
M NE APARTMENT 2789.50 5236.00 408.25
M N1 APARTMENT 2367.75 5331.50 246.75
M N2 APARTMENT 2374.75 5341.00 246.75
M S1 APARTMENT 3685.75 2912.25 187.75
M S2 APARTMENT 3689.00 2914.25 187.00
F6 SW APARTMENT 3383.00 3533.75 274.00
F6 NW APARTMENT 2629.50 5281.00 423.00
F6 SE APARTMENT 3484.50 3578.25 278.00
F6 NE APARTMENT 2748.00 5325.50 447.00
F6 N1 APARTMENT 2279.75 5466.00 271.50
F6 N2 APARTMENT 2287.25 5468.50 271.00
F6 S1 APARTMENT 3503.00 3079.50 202.00
F6 S2 APARTMENT 3500.75 3081.00 200.75
F7 SW APARTMENT 3294.50 3644.50 287.75
F7 NW APARTMENT 2600.00 5366.25 445.25
F7 SE APARTMENT 3394.00 3682.50 292.00
F7 NE APARTMENT 2731.50 5391.50 470.75
F7 N1 APARTMENT 2233.00 5544.75 284.50
F7 N2 APARTMENT 2236.25 5549.50 284.50
F7 S1 APARTMENT 3392.50 3195.00 210.50
F7 S2 APARTMENT 3396.25 3193.75 210.00
F8 SW APARTMENT 3235.00 3751.75 304.00
F8 NW APARTMENT 2594.50 5422.75 467.00
F8 SE APARTMENT 3323.25 3762.75 307.50
F8 NE APARTMENT 2721.50 5445.25 494.00
F8 N1 APARTMENT 2212.50 5604.50 298.25
F8 N2 APARTMENT 2221.25 5608.75 298.50
F8 S1 APARTMENT 3298.00 3320.75 215.50
F8 S2 APARTMENT 3299.75 3317.75 215.25
F9 SW APARTMENT 3154.25 3916.50 347.75
F9 NW APARTMENT 2636.00 5485.25 525.00
F9 SE APARTMENT 3237.75 3928.25 356.00
F9 NE APARTMENT 2766.50 5510.00 564.75
F9 N1 APARTMENT 2234.50 5663.00 328.25
F9 N2 APARTMENT 2240.25 5665.75 328.50
F9 S1 APARTMENT 3131.75 3574.00 221.50
F9 S2 APARTMENT 3139.00 3574.75 221.25
T SW APARTMENT 3747.50 4582.50 902.50
T NW APARTMENT 3247.25 5655.00 1253.00
T SE APARTMENT 3857.50 4529.50 919.00
T NE APARTMENT 3322.50 5704.25 1263.00
T N1 APARTMENT 2643.75 5871.50 791.25
T N2 APARTMENT 2648.50 5865.00 793.00
T S1 APARTMENT 3356.50 4336.25 533.25
T S2 APARTMENT 3365.25 4333.75 532.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5427.75 6682.00 1493.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 4.25 57.25 4.25 57.25
G NW APARTMENT 2.25 21.50 2.25 21.50
OFFICE 4.50 63.75 0.25 63.25
G NE APARTMENT 5.75 92.00 5.75 92.00
G N1 APARTMENT 6.25 68.00 6.25 68.00
G N2 APARTMENT 4.25 75.00 4.25 75.00
G S1 APARTMENT 1.75 137.25 1.75 137.25
G S2 APARTMENT 2.00 121.00 2.00 121.00
F2 SW APARTMENT 1.00 55.50 1.00 55.50
F2 NW APARTMENT 0.50 19.00 0.50 19.00
F2 SE APARTMENT 1.25 51.50 1.25 51.50
F2 NE APARTMENT 2.75 92.00 2.75 92.00
F2 N1 APARTMENT 3.50 57.00 3.50 57.00
F2 N2 APARTMENT 3.75 64.50 3.75 64.50
F2 S1 APARTMENT 1.00 169.75 1.00 169.75
F2 S2 APARTMENT 0.75 162.00 0.75 162.00
F3 SW APARTMENT 1.00 67.00 1.00 67.00
F3 NW APARTMENT 0.25 22.25 0.25 22.25
F3 SE APARTMENT 1.00 95.25 1.00 95.25
F3 NE APARTMENT 3.00 111.25 3.00 111.25
F3 N1 APARTMENT 4.00 70.50 4.00 70.50
F3 N2 APARTMENT 4.50 76.75 4.50 76.75
F3 S1 APARTMENT 1.75 189.75 1.75 189.75
F3 S2 APARTMENT 1.25 185.00 1.25 185.00
F4 SW APARTMENT 1.00 70.50 1.00 70.50
F4 NW APARTMENT 0.25 24.50 0.25 24.50
F4 SE APARTMENT 0.50 110.00 0.50 110.00
F4 NE APARTMENT 3.00 121.00 3.00 121.00
F4 N1 APARTMENT 3.75 76.00 3.75 76.00
F4 N2 APARTMENT 3.50 82.25 3.50 82.25
F4 S1 APARTMENT 0.75 195.75 0.75 195.75
F4 S2 APARTMENT 1.00 192.00 1.00 192.00
M SW APARTMENT 0.50 71.75 0.50 71.75
M NW APARTMENT 0.00 25.50 0.00 25.50
M SE APARTMENT 0.50 112.00 0.50 112.00
M NE APARTMENT 1.50 127.25 1.50 127.25
M N1 APARTMENT 2.50 78.25 2.50 78.25
M N2 APARTMENT 3.00 86.25 3.00 86.25
M S1 APARTMENT 2.00 193.25 2.00 193.25
M S2 APARTMENT 1.50 191.75 1.50 191.75
F6 SW APARTMENT 1.00 71.75 1.00 71.75
F6 NW APARTMENT 0.50 27.50 0.50 27.50
F6 SE APARTMENT 1.25 112.00 1.25 112.00
F6 NE APARTMENT 3.00 141.75 3.00 141.75
F6 N1 APARTMENT 2.25 83.75 2.25 83.75
F6 N2 APARTMENT 3.50 92.50 3.50 92.50
F6 S1 APARTMENT 1.00 193.75 1.00 193.75
F6 S2 APARTMENT 2.00 191.00 2.00 191.00
F7 SW APARTMENT 0.00 72.75 0.00 72.75
F7 NW APARTMENT 0.25 28.00 0.25 28.00
F7 SE APARTMENT 0.25 112.75 0.25 112.75
F7 NE APARTMENT 1.50 149.25 1.50 149.25
F7 N1 APARTMENT 5.25 86.75 5.25 86.75
F7 N2 APARTMENT 3.75 97.75 3.75 97.75
F7 S1 APARTMENT 1.25 193.25 1.25 193.25
F7 S2 APARTMENT 1.25 190.25 1.25 190.25
F8 SW APARTMENT 0.25 69.25 0.25 69.25
F8 NW APARTMENT 0.00 28.50 0.00 28.50
F8 SE APARTMENT 1.25 112.25 1.25 112.25
F8 NE APARTMENT 2.50 157.50 2.50 157.50
F8 N1 APARTMENT 3.50 87.50 3.50 87.50
F8 N2 APARTMENT 4.50 98.00 4.50 98.00
F8 S1 APARTMENT 1.25 190.75 1.25 190.75
F8 S2 APARTMENT 0.75 183.25 0.75 183.25
F9 SW APARTMENT 0.00 61.75 0.00 61.75
F9 NW APARTMENT 0.00 27.50 0.00 27.50
F9 SE APARTMENT 1.25 99.50 1.25 99.50
F9 NE APARTMENT 2.75 175.25 2.75 175.25
F9 N1 APARTMENT 6.00 75.50 6.00 75.50
F9 N2 APARTMENT 5.25 82.75 5.25 82.75
F9 S1 APARTMENT 1.25 169.75 1.25 169.75
F9 S2 APARTMENT 1.50 166.75 1.50 166.75
T SW APARTMENT 0.00 49.50 0.00 49.50
T NW APARTMENT 0.00 30.00 0.00 30.00
T SE APARTMENT 0.00 63.75 0.00 63.75
T NE APARTMENT 0.00 121.25 0.00 121.25
T N1 APARTMENT 1.50 54.50 1.50 54.50
T N2 APARTMENT 1.75 58.25 1.75 58.25
T S1 APARTMENT 1.25 85.25 1.25 85.25
T S2 APARTMENT 1.00 85.50 1.00 85.50
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 128.75 390.25 124.75 390.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.353 0.098 0.000 0.289
G NW APARTMENT 1.71 2.50 268.96 0.353 0.098 0.000 0.277
OFFICE 0.94 1.00 268.96 0.516 0.100 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.353 0.098 0.000 0.277
G N1 APARTMENT 1.71 2.50 268.96 0.353 0.059 0.000 0.270
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.059 0.000 0.270
G S1 APARTMENT 1.71 2.50 268.96 0.353 0.059 0.000 0.286
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.059 0.000 0.287
F2 SW APARTMENT 1.71 2.50 268.96 0.353 0.141 0.000 0.334
F2 NW APARTMENT 1.71 2.50 268.96 0.353 0.141 0.000 0.322
F2 SE APARTMENT 1.71 2.50 268.96 0.353 0.142 0.000 0.335
F2 NE APARTMENT 1.71 2.50 268.96 0.353 0.141 0.000 0.321
F2 N1 APARTMENT 1.71 2.50 268.96 0.353 0.085 0.000 0.317
F2 N2 APARTMENT 1.71 2.50 268.97 0.353 0.085 0.000 0.317
F2 S1 APARTMENT 1.71 2.50 268.96 0.354 0.085 0.000 0.332
F2 S2 APARTMENT 1.71 2.50 268.97 0.354 0.085 0.000 0.333
F3 SW APARTMENT 1.71 2.50 268.96 0.353 0.168 0.000 0.361
F3 NW APARTMENT 1.71 2.50 268.96 0.353 0.167 0.000 0.348
F3 SE APARTMENT 1.71 2.50 268.96 0.353 0.168 0.000 0.361
F3 NE APARTMENT 1.71 2.50 268.96 0.353 0.167 0.000 0.347
F3 N1 APARTMENT 1.71 2.50 268.96 0.353 0.101 0.000 0.344
F3 N2 APARTMENT 1.71 2.50 268.97 0.353 0.101 0.000 0.344
F3 S1 APARTMENT 1.71 2.50 268.96 0.354 0.101 0.000 0.360
F3 S2 APARTMENT 1.71 2.50 268.97 0.354 0.101 0.000 0.360
F4 SW APARTMENT 1.71 2.50 268.96 0.353 0.187 0.000 0.382
F4 NW APARTMENT 1.71 2.50 268.96 0.353 0.187 0.000 0.368
F4 SE APARTMENT 1.71 2.50 268.96 0.353 0.187 0.000 0.383
F4 NE APARTMENT 1.71 2.50 268.96 0.353 0.187 0.000 0.368
F4 N1 APARTMENT 1.71 2.50 268.96 0.353 0.113 0.000 0.364
F4 N2 APARTMENT 1.71 2.50 268.97 0.353 0.113 0.000 0.364
F4 S1 APARTMENT 1.71 2.50 268.96 0.354 0.113 0.000 0.381
F4 S2 APARTMENT 1.71 2.50 268.97 0.354 0.113 0.000 0.381
M SW APARTMENT 1.71 2.50 268.96 0.353 0.203 0.000 0.400
M NW APARTMENT 1.71 2.50 268.96 0.353 0.203 0.000 0.385
M SE APARTMENT 1.71 2.50 268.96 0.353 0.203 0.000 0.401
M NE APARTMENT 1.71 2.50 268.96 0.353 0.203 0.000 0.385
M N1 APARTMENT 1.71 2.50 268.96 0.353 0.122 0.000 0.382
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.122 0.000 0.382
M S1 APARTMENT 1.71 2.50 268.96 0.354 0.123 0.000 0.399
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.123 0.000 0.399
F6 SW APARTMENT 1.71 2.50 268.96 0.353 0.217 0.000 0.418
F6 NW APARTMENT 1.71 2.50 268.96 0.353 0.217 0.000 0.402
F6 SE APARTMENT 1.71 2.50 268.96 0.353 0.217 0.000 0.419
F6 NE APARTMENT 1.71 2.50 268.96 0.353 0.217 0.000 0.401
F6 N1 APARTMENT 1.71 2.50 268.96 0.353 0.131 0.000 0.398
F6 N2 APARTMENT 1.71 2.50 268.97 0.353 0.131 0.000 0.398
F6 S1 APARTMENT 1.71 2.50 268.96 0.354 0.131 0.000 0.417
F6 S2 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.417
F7 SW APARTMENT 1.71 2.50 268.96 0.353 0.230 0.000 0.432
F7 NW APARTMENT 1.71 2.50 268.96 0.353 0.229 0.000 0.415
F7 SE APARTMENT 1.71 2.50 268.96 0.353 0.230 0.000 0.433
F7 NE APARTMENT 1.71 2.50 268.96 0.353 0.229 0.000 0.414
F7 N1 APARTMENT 1.71 2.50 268.96 0.353 0.138 0.000 0.411
F7 N2 APARTMENT 1.71 2.50 268.97 0.353 0.138 0.000 0.411
F7 S1 APARTMENT 1.71 2.50 268.96 0.353 0.139 0.000 0.431
F7 S2 APARTMENT 1.71 2.50 268.97 0.353 0.139 0.000 0.431
F8 SW APARTMENT 1.71 2.50 268.96 0.353 0.241 0.000 0.446
F8 NW APARTMENT 1.71 2.50 268.96 0.353 0.240 0.000 0.427
F8 SE APARTMENT 1.71 2.50 268.96 0.353 0.241 0.000 0.446
F8 NE APARTMENT 1.71 2.50 268.96 0.352 0.240 0.000 0.427
F8 N1 APARTMENT 1.71 2.50 268.96 0.353 0.145 0.000 0.423
F8 N2 APARTMENT 1.71 2.50 268.97 0.353 0.145 0.000 0.423
F8 S1 APARTMENT 1.71 2.50 268.96 0.353 0.145 0.000 0.444
F8 S2 APARTMENT 1.71 2.50 268.97 0.353 0.145 0.000 0.444
F9 SW APARTMENT 1.71 2.50 268.96 0.353 0.251 0.000 0.458
F9 NW APARTMENT 1.71 2.50 268.96 0.352 0.250 0.000 0.438
F9 SE APARTMENT 1.71 2.50 268.96 0.353 0.251 0.000 0.458
F9 NE APARTMENT 1.71 2.50 268.96 0.352 0.250 0.000 0.438
F9 N1 APARTMENT 1.71 2.50 268.96 0.353 0.151 0.000 0.435
F9 N2 APARTMENT 1.71 2.50 268.97 0.353 0.151 0.000 0.435
F9 S1 APARTMENT 1.71 2.50 268.96 0.353 0.151 0.000 0.456
F9 S2 APARTMENT 1.71 2.50 268.97 0.353 0.151 0.000 0.456
T SW APARTMENT 1.71 2.50 268.96 0.353 0.260 0.000 0.469
T NW APARTMENT 1.71 2.50 268.96 0.352 0.260 0.000 0.450
T SE APARTMENT 1.71 2.50 268.96 0.353 0.260 0.000 0.469
T NE APARTMENT 1.71 2.50 268.96 0.352 0.260 0.000 0.450
T N1 APARTMENT 1.71 2.50 268.96 0.352 0.157 0.000 0.447
T N2 APARTMENT 1.71 2.50 268.97 0.352 0.157 0.000 0.447
T S1 APARTMENT 1.71 2.50 268.96 0.353 0.157 0.000 0.467
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.157 0.000 0.467
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.505 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 708.77 22475.07 05-SEP-07:15 22475.07 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1258.67 22855.60 08-APR-02:15 85628.14 16-AUG-16:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
ElectricityPurchased:Plant 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
Cogeneration:ElectricityPurchased 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
ElectricityNet:Plant 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
Cogeneration:ElectricityNet 3031.50 60416.08 08-APR-02:15 170957.00 26-JUN-19:30
ExteriorLights:Electricity 168.38 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.38 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:Fans:Electricity 708.77 22475.07 05-SEP-07:15 22475.07 01-JAN-00:15
Cooling:Electricity 405.35 0.00 01-JAN-00:15 62067.43 26-JUN-15:15
Heating:Electricity 123.71 0.00 09-JAN-11:15 60951.91 22-DEC-04:00
Electricity:Plant 56.95 36.93 23-MAR-12:30 3461.80 30-JUL-12:30
HeatRejection:Electricity 13.98 0.00 01-JAN-00:15 2085.11 30-JUL-12:30
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 42.97 36.93 23-MAR-12:30 1376.68 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1594.36 9260.51 01-JAN-00:15 283059.73 19-MAR-07:15
Gas:Plant 1594.36 9260.51 01-JAN-00:15 283059.73 19-MAR-07:15
WaterSystems:Gas 1202.88 9260.51 01-JAN-00:15 89518.38 11-FEB-08:00
Water Heater:WaterSystems:Gas 1202.88 9260.51 01-JAN-00:15 89518.38 11-FEB-08:00
Heating:Gas 391.48 0.00 01-JAN-00:15 205688.93 22-DEC-04:00
Boiler:Heating:Gas 391.48 0.00 01-JAN-00:15 205688.93 22-DEC-04:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 1579.78 0.00 01-JAN-00:15 265403.41 26-JUN-15:00
PlantLoopCoolingDemand:HVAC 1579.78 0.00 01-JAN-00:15 265403.41 26-JUN-15:00
CoolingCoils:PlantLoopCoolingDemand 1579.78 0.00 01-JAN-00:15 265403.41 26-JUN-15:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 6127.75 0.00 01-JAN-02:30 0.00 26-JUN-17:15
Water:Plant 6127.75 0.00 01-JAN-02:30 0.00 26-JUN-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 6127.75 0.00 01-JAN-02:30 0.00 26-JUN-17:15
MainsWater:Plant 6127.75 0.00 01-JAN-02:30 0.00 26-JUN-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
HeatRejection:Water 1349.23 0.00 01-JAN-00:15 0.00 26-JUN-15:00
HeatRejection:MainsWater 1349.23 0.00 01-JAN-00:15 0.00 26-JUN-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 1273.87 498.76 15-AUG-01:15 218052.11 19-MAR-07:00
PlantLoopHeatingDemand:Plant 914.60 498.76 15-AUG-01:15 61868.19 15-FEB-07:45
WaterSystems:PlantLoopHeatingDemand 914.60 498.76 15-AUG-01:15 61868.19 15-FEB-07:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 4364.65 6656.50 21-MAY-03:00 584638.26 19-MAR-07:15
EnergyTransfer:Building 1465.59 4241.27 18-APR-08:00 175047.24 02-AUG-18:15
EnergyTransfer:Zone:G SW APARTMENT 14.83 0.03 25-MAY-03:00 2422.23 02-SEP-17:30
Heating:EnergyTransfer 292.13 0.00 21-JAN-16:45 158995.12 19-MAR-07:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 3.72 0.00 01-JAN-00:15 2141.02 21-DEC-08:00
Cooling:EnergyTransfer 1173.46 0.00 04-JAN-23:00 175047.24 02-AUG-18:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 11.11 0.00 01-JAN-01:30 2422.23 02-SEP-17:30
EnergyTransfer:Zone:G NW APARTMENT 13.35 0.02 13-OCT-18:45 2247.01 15-JUN-18:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 6.71 0.00 01-JAN-14:45 2145.38 21-DEC-08:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 6.64 0.00 01-JAN-00:15 2247.01 15-JUN-18:00
EnergyTransfer:Zone:OFFICE 21.54 0.09 03-JUN-05:00 3113.70 29-AUG-12:30
Heating:EnergyTransfer:Zone:OFFICE 3.73 0.00 01-JAN-08:15 2301.57 21-DEC-08:00
Cooling:EnergyTransfer:Zone:OFFICE 17.80 0.00 01-JAN-00:15 3113.70 29-AUG-12:30
EnergyTransfer:Zone:G NE APARTMENT 13.59 0.09 21-JAN-15:00 2182.30 21-DEC-18:30
Heating:EnergyTransfer:Zone:G NE APARTMENT 6.40 0.00 01-JAN-09:00 2182.30 21-DEC-18:30
Cooling:EnergyTransfer:Zone:G NE APARTMENT 7.19 0.00 01-JAN-00:15 1568.40 06-JUN-08:30
EnergyTransfer:Zone:G N1 APARTMENT 8.89 0.02 19-MAY-14:00 1332.11 23-DEC-08:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.25 0.00 01-JAN-17:15 1332.11 23-DEC-08:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 5.64 0.00 01-JAN-00:15 1129.63 08-JUN-18:15
EnergyTransfer:Zone:G N2 APARTMENT 8.90 0.00 24-SEP-10:15 1327.51 23-DEC-08:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.25 0.00 01-JAN-17:15 1327.51 23-DEC-08:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 5.65 0.00 01-JAN-00:15 1109.11 08-JUN-18:15
EnergyTransfer:Zone:G S1 APARTMENT 12.11 0.00 09-JUN-18:45 1457.38 05-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 1.25 0.00 01-JAN-00:15 1270.22 21-DEC-08:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 10.86 0.00 03-JAN-02:45 1457.38 05-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 12.26 0.00 06-NOV-10:45 1503.69 05-SEP-13:45
Heating:EnergyTransfer:Zone:G S2 APARTMENT 1.23 0.00 01-JAN-00:15 1265.38 21-DEC-08:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 11.03 0.00 03-JAN-03:15 1503.69 05-SEP-13:45
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 21.82 0.02 26-APR-09:00 3159.33 02-SEP-17:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 2.56 0.00 01-JAN-00:15 2135.09 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 19.26 0.00 03-JAN-04:30 3159.33 02-SEP-17:30
EnergyTransfer:Zone:F2 NW APARTMENT 16.34 0.02 07-APR-04:15 2916.87 15-JUN-18:00
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 5.48 0.00 01-JAN-14:15 2323.73 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 10.86 0.00 01-JAN-00:15 2916.87 15-JUN-18:00
EnergyTransfer:Zone:F2 SE APARTMENT 23.37 0.08 17-APR-17:45 2901.73 31-AUG-09:45
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 2.33 0.00 01-JAN-00:15 2103.00 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 21.04 0.00 03-JAN-05:00 2901.73 31-AUG-09:45
EnergyTransfer:Zone:F2 NE APARTMENT 17.02 0.04 28-JAN-09:15 2353.95 22-DEC-04:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 5.24 0.00 01-JAN-08:30 2353.95 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 11.79 0.00 01-JAN-00:15 2156.73 06-JUN-08:30
EnergyTransfer:Zone:F2 N1 APARTMENT 11.43 0.04 01-MAR-14:30 1566.51 08-JUN-18:15
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 1.92 0.00 01-JAN-00:15 1318.34 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 9.51 0.00 01-JAN-00:30 1566.51 08-JUN-18:15
EnergyTransfer:Zone:F2 N2 APARTMENT 11.45 0.06 26-FEB-04:45 1549.33 08-JUN-18:15
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 1.92 0.00 01-JAN-09:00 1320.13 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 9.54 0.00 01-JAN-00:30 1549.33 08-JUN-18:15
EnergyTransfer:Zone:F2 S1 APARTMENT 19.36 0.04 07-DEC-07:15 2184.25 16-NOV-12:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.69 0.00 01-JAN-00:15 1154.68 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 18.66 0.00 04-JAN-22:15 2184.25 16-NOV-12:00
EnergyTransfer:Zone:F2 S2 APARTMENT 19.46 0.03 30-MAY-12:30 2206.26 16-NOV-12:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.69 0.00 01-JAN-00:15 1152.03 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 18.77 0.00 04-JAN-22:15 2206.26 16-NOV-12:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 23.05 0.11 23-MAR-20:15 3173.08 02-SEP-17:30
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 2.42 0.00 01-JAN-00:15 2179.50 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 20.63 0.00 03-JAN-05:45 3173.08 02-SEP-17:30
EnergyTransfer:Zone:F3 NW APARTMENT 16.86 0.01 10-APR-13:45 2946.56 15-JUN-18:15
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 5.23 0.00 01-JAN-14:15 2371.53 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 11.64 0.00 01-JAN-00:15 2946.56 15-JUN-18:15
EnergyTransfer:Zone:F3 SE APARTMENT 23.97 0.40 08-APR-01:15 2751.66 31-AUG-09:45
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 2.33 0.00 01-JAN-00:15 2174.06 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 21.64 0.00 03-JAN-05:45 2751.66 31-AUG-09:45
EnergyTransfer:Zone:F3 NE APARTMENT 17.59 0.01 11-APR-13:00 2400.31 22-DEC-04:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 5.02 0.00 01-JAN-08:30 2400.31 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 12.57 0.00 01-JAN-00:15 2187.47 06-JUN-08:30
EnergyTransfer:Zone:F3 N1 APARTMENT 12.19 0.02 18-AUG-05:45 1603.05 08-JUN-18:15
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 1.69 0.00 01-JAN-00:15 1312.22 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 10.51 0.00 01-JAN-00:45 1603.05 08-JUN-18:15
EnergyTransfer:Zone:F3 N2 APARTMENT 12.22 0.12 13-DEC-13:00 1585.96 08-JUN-18:15
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 1.69 0.00 01-JAN-00:15 1314.01 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 10.53 0.00 01-JAN-00:45 1585.96 08-JUN-18:15
EnergyTransfer:Zone:F3 S1 APARTMENT 21.16 0.29 05-SEP-09:00 2284.13 18-NOV-13:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.60 0.00 01-JAN-00:15 1104.66 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 20.56 0.00 04-JAN-23:00 2284.13 18-NOV-13:00
EnergyTransfer:Zone:F3 S2 APARTMENT 21.20 0.09 03-APR-22:00 2291.99 18-NOV-13:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.60 0.00 01-JAN-00:15 1104.34 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 20.60 0.00 04-JAN-23:00 2291.99 18-NOV-13:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 23.18 0.02 26-APR-11:30 3180.48 02-SEP-17:30
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 2.54 0.00 01-JAN-00:15 2295.81 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 20.64 0.00 03-JAN-06:00 3180.48 02-SEP-17:30
EnergyTransfer:Zone:F4 NW APARTMENT 17.11 0.03 25-APR-15:45 2946.35 15-JUN-18:15
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 5.40 0.00 01-JAN-14:15 2455.65 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 11.71 0.00 01-JAN-00:15 2946.35 15-JUN-18:15
EnergyTransfer:Zone:F4 SE APARTMENT 24.00 0.11 21-MAY-02:30 2752.18 07-NOV-10:45
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 2.47 0.00 01-JAN-00:15 2295.05 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 21.52 0.00 03-JAN-06:00 2752.18 07-NOV-10:45
EnergyTransfer:Zone:F4 NE APARTMENT 17.82 0.02 19-JAN-11:15 2517.42 21-DEC-23:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 5.19 0.00 01-JAN-08:30 2517.42 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 12.63 0.00 01-JAN-00:15 2193.21 26-JUN-08:30
EnergyTransfer:Zone:F4 N1 APARTMENT 12.44 0.03 02-APR-21:30 1616.69 08-JUN-18:30
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 1.73 0.00 01-JAN-00:15 1350.64 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 10.71 0.00 01-JAN-01:00 1616.69 08-JUN-18:30
EnergyTransfer:Zone:F4 N2 APARTMENT 12.46 0.01 27-JUL-19:45 1601.41 08-JUN-18:30
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 1.73 0.00 01-JAN-00:15 1352.43 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 10.73 0.00 01-JAN-01:00 1601.41 08-JUN-18:30
EnergyTransfer:Zone:F4 S1 APARTMENT 21.44 0.19 19-MAR-21:45 2305.62 18-NOV-12:45
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.63 0.00 01-JAN-00:15 1113.12 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 20.82 0.00 04-JAN-23:00 2305.62 18-NOV-12:45
EnergyTransfer:Zone:F4 S2 APARTMENT 21.46 0.01 11-SEP-20:30 2314.86 18-NOV-12:45
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.63 0.00 01-JAN-00:15 1113.37 21-DEC-05:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 20.84 0.00 04-JAN-23:00 2314.86 18-NOV-12:45
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 23.40 0.04 29-APR-22:45 3211.21 02-SEP-17:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 2.64 0.00 01-JAN-00:15 2405.15 19-MAR-07:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 20.77 0.00 03-JAN-06:00 3211.21 02-SEP-17:30
EnergyTransfer:Zone:M NW APARTMENT 17.42 0.02 12-DEC-19:15 2972.05 15-JUN-18:15
Heating:EnergyTransfer:Zone:M NW APARTMENT 5.51 0.00 01-JAN-14:15 2543.64 21-DEC-23:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 11.91 0.00 01-JAN-00:15 2972.05 15-JUN-18:15
EnergyTransfer:Zone:M SE APARTMENT 24.19 0.01 23-MAR-10:45 2775.50 07-NOV-10:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 2.57 0.00 01-JAN-00:15 2405.62 19-MAR-07:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 21.62 0.00 03-JAN-06:00 2775.50 07-NOV-10:45
EnergyTransfer:Zone:M NE APARTMENT 18.10 0.03 16-JAN-17:15 2606.10 21-DEC-23:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 5.28 0.00 01-JAN-08:30 2606.10 21-DEC-23:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 12.82 0.00 01-JAN-00:15 2224.16 26-JUN-08:30
EnergyTransfer:Zone:M N1 APARTMENT 12.74 0.03 28-AUG-08:15 1650.96 08-JUN-18:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 1.73 0.00 01-JAN-00:15 1371.28 22-DEC-04:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 11.01 0.00 01-JAN-01:00 1650.96 08-JUN-18:30
EnergyTransfer:Zone:M N2 APARTMENT 12.77 0.04 24-NOV-06:45 1633.98 08-JUN-18:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 1.73 0.00 01-JAN-00:15 1373.07 22-DEC-04:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 11.03 0.00 01-JAN-01:00 1633.98 08-JUN-18:30
EnergyTransfer:Zone:M S1 APARTMENT 21.75 0.15 05-SEP-09:15 2339.27 18-NOV-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.65 0.00 01-JAN-00:15 1114.08 21-DEC-05:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 21.11 0.00 04-JAN-23:00 2339.27 18-NOV-12:45
EnergyTransfer:Zone:M S2 APARTMENT 21.77 0.05 26-DEC-04:15 2348.20 18-NOV-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.65 0.00 01-JAN-00:15 1114.44 21-DEC-05:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 21.12 0.00 04-JAN-23:00 2348.20 18-NOV-12:45
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 22.70 0.02 06-APR-10:15 3169.28 02-SEP-17:30
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 2.97 0.00 01-JAN-00:15 2563.76 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 19.73 0.00 03-JAN-05:45 3169.28 02-SEP-17:30
EnergyTransfer:Zone:F6 NW APARTMENT 17.41 0.00 13-MAY-00:45 2924.05 15-JUN-18:15
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 6.13 0.00 01-JAN-14:30 2679.67 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 11.28 0.00 01-JAN-00:15 2924.05 15-JUN-18:15
EnergyTransfer:Zone:F6 SE APARTMENT 23.46 0.04 21-MAY-03:30 2726.09 07-NOV-10:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 2.90 0.00 01-JAN-00:15 2564.13 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 20.56 0.00 03-JAN-05:45 2726.09 07-NOV-10:45
EnergyTransfer:Zone:F6 NE APARTMENT 18.04 0.03 25-NOV-16:00 2743.04 21-DEC-23:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 5.89 0.00 01-JAN-08:45 2743.04 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 12.15 0.00 01-JAN-00:15 2187.05 26-JUN-08:45
EnergyTransfer:Zone:F6 N1 APARTMENT 12.37 0.01 17-AUG-08:30 1611.06 08-JUN-18:30
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 2.03 0.00 01-JAN-00:15 1447.95 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 10.33 0.00 01-JAN-00:45 1611.06 08-JUN-18:30
EnergyTransfer:Zone:F6 N2 APARTMENT 12.39 0.06 22-NOV-07:30 1594.18 08-JUN-18:30
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 2.04 0.00 01-JAN-00:15 1449.73 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 10.36 0.00 01-JAN-00:45 1594.18 08-JUN-18:30
EnergyTransfer:Zone:F6 S1 APARTMENT 20.84 0.12 28-AUG-09:15 2294.57 18-NOV-13:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.76 0.00 01-JAN-00:15 1198.73 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 20.08 0.00 04-JAN-23:00 2294.57 18-NOV-13:00
EnergyTransfer:Zone:F6 S2 APARTMENT 20.85 0.28 25-MAY-16:00 2303.29 18-NOV-13:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.76 0.00 01-JAN-00:15 1198.88 19-MAR-08:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 20.10 0.00 04-JAN-23:00 2303.29 18-NOV-13:00
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 22.32 0.04 23-MAR-19:45 3153.78 02-SEP-17:30
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 3.25 0.00 01-JAN-00:15 2694.85 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 19.07 0.00 03-JAN-05:30 3153.78 02-SEP-17:30
EnergyTransfer:Zone:F7 NW APARTMENT 17.54 0.03 22-FEB-14:30 2909.52 08-JUN-17:45
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 6.60 0.00 01-JAN-14:45 2783.34 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 10.95 0.00 01-JAN-00:15 2909.52 08-JUN-17:45
EnergyTransfer:Zone:F7 SE APARTMENT 23.06 0.07 26-DEC-15:45 2705.81 31-AUG-09:45
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 3.17 0.00 01-JAN-00:15 2694.81 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 19.89 0.00 03-JAN-05:30 2705.81 31-AUG-09:45
EnergyTransfer:Zone:F7 NE APARTMENT 18.12 0.03 04-DEC-10:15 2847.13 21-DEC-23:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 6.34 0.00 01-JAN-08:45 2847.13 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 11.78 0.00 01-JAN-00:15 2167.81 26-JUN-08:45
EnergyTransfer:Zone:F7 N1 APARTMENT 12.23 0.01 09-APR-13:15 1606.55 05-JUN-18:15
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 2.27 0.00 01-JAN-00:15 1500.34 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 9.96 0.00 01-JAN-00:30 1606.55 05-JUN-18:15
EnergyTransfer:Zone:F7 N2 APARTMENT 12.25 0.11 25-NOV-05:00 1590.68 05-JUN-18:15
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 2.27 0.00 01-JAN-00:15 1502.11 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 9.98 0.00 01-JAN-00:30 1590.68 05-JUN-18:15
EnergyTransfer:Zone:F7 S1 APARTMENT 20.29 0.08 28-NOV-21:30 2269.05 18-NOV-13:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.85 0.00 01-JAN-00:15 1282.66 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 19.44 0.00 04-JAN-22:45 2269.05 18-NOV-13:00
EnergyTransfer:Zone:F7 S2 APARTMENT 20.31 0.03 01-MAY-15:00 2271.85 18-NOV-13:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.86 0.00 01-JAN-00:15 1282.78 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 19.45 0.00 04-JAN-22:45 2271.85 18-NOV-13:00
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 22.07 0.09 17-MAR-14:00 3154.05 02-AUG-18:15
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 3.55 0.00 01-JAN-00:15 2830.55 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 18.52 0.00 03-JAN-05:00 3154.05 02-AUG-18:15
EnergyTransfer:Zone:F8 NW APARTMENT 17.80 0.03 16-MAY-01:45 2910.25 08-JUN-17:45
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 7.08 0.00 01-JAN-15:00 2895.99 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 10.72 0.00 01-JAN-00:15 2910.25 08-JUN-17:45
EnergyTransfer:Zone:F8 SE APARTMENT 22.79 0.04 04-APR-15:15 2830.08 19-MAR-07:15
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 3.46 0.00 01-JAN-00:15 2830.08 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 19.33 0.00 03-JAN-05:00 2703.61 31-AUG-09:45
EnergyTransfer:Zone:F8 NE APARTMENT 18.33 0.02 07-APR-19:30 2948.66 21-DEC-23:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 6.80 0.00 01-JAN-08:45 2948.66 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 11.53 0.00 01-JAN-00:15 2163.78 26-JUN-08:45
EnergyTransfer:Zone:F8 N1 APARTMENT 12.23 0.05 31-JUL-05:45 1615.39 05-JUN-18:15
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 2.53 0.00 01-JAN-00:15 1555.92 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 9.70 0.00 01-JAN-00:30 1615.39 05-JUN-18:15
EnergyTransfer:Zone:F8 N2 APARTMENT 12.25 0.08 13-JAN-13:30 1599.56 05-JUN-18:15
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 2.53 0.00 01-JAN-00:15 1557.69 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 9.72 0.00 01-JAN-00:30 1599.56 05-JUN-18:15
EnergyTransfer:Zone:F8 S1 APARTMENT 19.84 0.41 16-MAR-15:45 2238.10 15-NOV-13:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.97 0.00 01-JAN-00:15 1375.55 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 18.87 0.00 04-JAN-22:30 2238.10 15-NOV-13:00
EnergyTransfer:Zone:F8 S2 APARTMENT 19.85 0.03 24-MAR-14:30 2244.40 16-NOV-12:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.97 0.00 01-JAN-00:15 1375.62 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 18.88 0.00 04-JAN-22:30 2244.40 16-NOV-12:00
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 22.12 0.01 30-JAN-08:30 3265.26 02-AUG-18:15
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 4.30 0.00 01-JAN-00:15 3089.83 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 17.82 0.00 03-JAN-03:15 3265.26 02-AUG-18:15
EnergyTransfer:Zone:F9 NW APARTMENT 18.86 0.00 19-FEB-03:45 3145.35 19-MAR-07:15
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 8.20 0.00 01-JAN-15:15 3145.35 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 10.66 0.00 01-JAN-00:15 3001.47 15-JUN-18:15
EnergyTransfer:Zone:F9 SE APARTMENT 22.80 0.12 26-MAR-00:45 3088.78 19-MAR-07:15
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 4.17 0.00 01-JAN-00:15 3088.78 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 18.63 0.00 03-JAN-04:30 2767.60 02-AUG-18:15
EnergyTransfer:Zone:F9 NE APARTMENT 19.27 0.13 03-JAN-11:45 3153.18 21-DEC-23:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 7.86 0.00 01-JAN-09:00 3153.18 21-DEC-23:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 11.41 0.00 01-JAN-00:15 2193.48 02-AUG-18:15
EnergyTransfer:Zone:F9 N1 APARTMENT 12.77 0.00 03-JAN-22:45 1724.97 22-DEC-04:00
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 3.28 0.00 01-JAN-16:15 1724.97 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 9.49 0.00 01-JAN-00:15 1708.72 05-JUN-18:15
EnergyTransfer:Zone:F9 N2 APARTMENT 12.80 0.00 19-JUL-16:45 1726.78 22-DEC-04:00
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 3.29 0.00 01-JAN-16:15 1726.78 22-DEC-04:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 9.51 0.00 01-JAN-00:15 1692.60 05-JUN-18:15
EnergyTransfer:Zone:F9 S1 APARTMENT 19.34 0.05 28-MAR-03:00 2254.63 16-NOV-12:15
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 1.33 0.00 01-JAN-00:15 1587.48 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 18.01 0.00 04-JAN-13:30 2254.63 16-NOV-12:15
EnergyTransfer:Zone:F9 S2 APARTMENT 19.37 0.09 07-DEC-08:00 2264.91 16-NOV-12:15
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 1.34 0.00 01-JAN-00:15 1587.49 19-MAR-07:15
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 18.03 0.00 04-JAN-13:30 2264.91 16-NOV-12:15
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 28.24 0.10 03-MAR-20:00 3996.41 12-SEP-15:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 9.82 0.00 01-JAN-08:45 3867.57 19-MAR-07:15
Cooling:EnergyTransfer:Zone:T SW APARTMENT 18.42 0.00 01-JAN-00:15 3996.41 12-SEP-15:15
EnergyTransfer:Zone:T NW APARTMENT 25.37 0.09 28-JAN-16:30 3912.97 19-MAR-07:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 13.92 0.00 01-JAN-15:15 3912.97 19-MAR-07:15
Cooling:EnergyTransfer:Zone:T NW APARTMENT 11.46 0.00 01-JAN-00:15 3653.64 15-JUN-17:30
EnergyTransfer:Zone:T SE APARTMENT 28.09 0.05 05-OCT-05:45 3866.84 19-MAR-07:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 9.46 0.00 01-JAN-08:15 3866.84 19-MAR-07:15
Cooling:EnergyTransfer:Zone:T SE APARTMENT 18.63 0.00 01-JAN-00:15 3567.51 31-AUG-10:45
EnergyTransfer:Zone:T NE APARTMENT 24.81 0.00 08-OCT-23:30 3933.53 21-DEC-23:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 13.19 0.00 01-JAN-09:15 3933.53 21-DEC-23:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 11.63 0.00 01-JAN-00:15 2804.03 26-JUN-08:45
EnergyTransfer:Zone:T N1 APARTMENT 16.82 0.01 22-JAN-20:15 2608.06 22-DEC-04:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 7.53 0.00 03-JAN-11:15 2608.06 22-DEC-04:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 9.30 0.00 01-JAN-00:15 2243.36 29-JUN-17:15
EnergyTransfer:Zone:T N2 APARTMENT 16.86 0.02 05-SEP-19:00 2608.96 22-DEC-04:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 7.54 0.00 01-JAN-12:45 2608.96 22-DEC-04:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 9.31 0.00 01-JAN-00:15 2238.55 29-JUN-17:15
EnergyTransfer:Zone:T S1 APARTMENT 21.32 0.02 30-JAN-10:00 2976.66 16-NOV-12:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 4.48 0.00 01-JAN-00:15 2496.66 22-DEC-04:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 16.85 0.00 01-JAN-01:45 2976.66 16-NOV-12:45
EnergyTransfer:Zone:T S2 APARTMENT 21.36 0.02 27-SEP-01:30 2985.93 16-NOV-12:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 4.49 0.00 01-JAN-00:15 2497.79 22-DEC-04:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 16.88 0.00 01-JAN-01:45 2985.93 16-NOV-12:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 1227.22 498.76 15-AUG-01:15 215210.63 23-DEC-07:15
WaterSystems:EnergyTransfer 914.59 498.76 15-AUG-01:15 61861.86 15-FEB-07:45
sub cat:WaterSystems:EnergyTransfer 914.59 498.76 15-AUG-01:15 61861.86 15-FEB-07:45
EnergyTransfer:HVAC 1671.83 0.00 23-MAR-12:30 226834.52 22-DEC-04:00
CoolingCoils:EnergyTransfer 1203.55 0.00 01-JAN-00:15 205438.93 30-JUL-14:30
HeatingCoils:EnergyTransfer 468.28 0.00 09-JAN-11:15 226834.52 22-DEC-04:00
PlantLoopHeatingDemand:HVAC 359.28 0.00 09-JAN-11:15 166823.24 22-DEC-04:00
HeatingCoils:PlantLoopHeatingDemand 359.28 0.00 09-JAN-11:15 166823.24 22-DEC-04:00
Boilers:EnergyTransfer 312.63 0.00 01-JAN-00:15 164551.15 22-DEC-04:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 3.722 -11.112 0.000 0.000 3.789 2.413 12.213 25.463 0.000 0.205 0.000 0.000 -12.606 0.000 -5.911 -18.176
G NW APARTMENT 6.710 -6.643 0.000 0.000 3.846 2.413 12.213 11.536 0.000 0.204 0.000 0.000 -12.724 0.000 -5.489 -12.066
OFFICE 3.734 -17.804 0.000 0.000 0.516 21.954 7.547 26.081 0.000 0.115 0.001 0.000 -12.492 0.000 -3.052 -26.601
G NE APARTMENT 6.403 -7.187 0.000 0.000 3.861 2.413 12.213 12.121 0.000 0.202 0.000 0.000 -12.445 0.000 -5.473 -12.108
G N1 APARTMENT 3.247 -5.638 0.000 0.000 3.868 2.413 12.213 3.940 0.000 0.157 0.000 0.000 -7.938 0.000 -4.062 -8.199
G N2 APARTMENT 3.247 -5.650 0.000 0.000 3.868 2.413 12.213 3.937 0.000 0.157 0.000 0.000 -7.934 0.000 -4.063 -8.187
G S1 APARTMENT 1.251 -10.860 0.000 0.000 3.787 2.413 12.213 17.993 0.000 0.155 0.001 0.000 -7.713 0.000 -4.582 -14.658
G S2 APARTMENT 1.225 -11.035 0.000 0.000 3.784 2.413 12.213 17.981 0.000 0.156 0.000 0.000 -7.719 0.000 -4.604 -14.414
F2 SW APARTMENT 2.562 -19.261 0.000 0.000 3.697 2.413 12.213 24.792 0.000 0.273 0.003 0.000 -13.518 0.000 -7.869 -5.301
F2 NW APARTMENT 5.479 -10.863 0.000 0.000 3.790 2.413 12.213 11.085 0.000 0.270 0.000 0.000 -13.484 0.000 -7.422 -3.481
F2 SE APARTMENT 2.335 -21.036 0.000 0.000 3.699 2.413 12.213 25.390 0.000 0.272 0.002 0.000 -13.351 0.000 -7.913 -4.021
F2 NE APARTMENT 5.235 -11.789 0.000 0.000 3.807 2.413 12.213 11.657 0.000 0.267 0.000 0.000 -13.166 0.000 -7.389 -3.247
F2 N1 APARTMENT 1.917 -9.514 0.000 0.000 3.807 2.413 12.213 3.702 0.000 0.203 0.000 0.000 -8.465 0.000 -5.471 -0.806
F2 N2 APARTMENT 1.917 -9.537 0.000 0.000 3.809 2.413 12.213 3.700 0.000 0.203 0.000 0.000 -8.460 0.000 -5.471 -0.787
F2 S1 APARTMENT 0.693 -18.663 0.000 0.000 3.677 2.413 12.213 17.556 0.000 0.202 0.001 0.000 -8.289 0.000 -6.046 -3.755
F2 S2 APARTMENT 0.691 -18.768 0.000 0.000 3.676 2.413 12.213 17.552 0.000 0.202 0.001 0.000 -8.292 0.000 -6.052 -3.635
F3 SW APARTMENT 2.423 -20.625 0.000 0.000 3.683 2.413 12.213 24.533 0.000 0.313 0.001 0.000 -13.775 0.000 -8.942 -2.235
F3 NW APARTMENT 5.225 -11.636 0.000 0.000 3.779 2.413 12.213 10.930 0.000 0.310 0.000 0.000 -13.738 0.000 -8.471 -1.024
F3 SE APARTMENT 2.333 -21.640 0.000 0.000 3.692 2.413 12.213 25.152 0.000 0.310 0.000 0.000 -13.556 0.000 -8.961 -1.955
F3 NE APARTMENT 5.017 -12.571 0.000 0.000 3.796 2.413 12.213 11.495 0.000 0.305 0.000 0.000 -13.408 0.000 -8.434 -0.827
F3 N1 APARTMENT 1.686 -10.507 0.000 0.000 3.790 2.413 12.213 3.632 0.000 0.230 1.404 0.000 -8.645 0.000 -6.216 -0.000
F3 N2 APARTMENT 1.691 -10.530 0.000 0.000 3.791 2.413 12.213 3.630 0.000 0.230 1.417 0.000 -8.640 0.000 -6.214 -0.000
F3 S1 APARTMENT 0.603 -20.560 0.000 0.000 3.655 2.413 12.213 17.379 0.000 0.229 0.001 0.000 -8.468 0.000 -6.806 -0.658
F3 S2 APARTMENT 0.603 -20.599 0.000 0.000 3.655 2.413 12.213 17.377 0.000 0.229 0.002 0.000 -8.467 0.000 -6.809 -0.614
F4 SW APARTMENT 2.539 -20.638 0.000 0.000 3.683 2.413 12.213 24.380 0.000 0.342 0.002 0.000 -13.894 0.000 -9.740 -1.300
F4 NW APARTMENT 5.401 -11.709 0.000 0.000 3.778 2.413 12.213 10.847 0.000 0.339 0.000 0.000 -13.867 0.000 -9.236 -0.180
F4 SE APARTMENT 2.472 -21.524 0.000 0.000 3.693 2.413 12.213 24.999 0.000 0.339 0.000 0.000 -13.662 0.000 -9.755 -1.188
F4 NE APARTMENT 5.189 -12.626 0.000 0.000 3.795 2.413 12.213 11.407 0.000 0.333 0.001 0.000 -13.530 0.000 -9.195 -0.000
F4 N1 APARTMENT 1.727 -10.714 0.000 0.000 3.786 2.413 12.213 3.598 0.000 0.250 2.208 0.000 -8.738 0.000 -6.743 -0.000
F4 N2 APARTMENT 1.728 -10.733 0.000 0.000 3.787 2.413 12.213 3.596 0.000 0.250 2.219 0.000 -8.732 0.000 -6.741 -0.000
F4 S1 APARTMENT 0.625 -20.817 0.000 0.000 3.652 2.413 12.213 17.274 0.000 0.250 0.298 0.000 -8.550 0.000 -7.358 -0.000
F4 S2 APARTMENT 0.626 -20.838 0.000 0.000 3.652 2.413 12.213 17.272 0.000 0.250 0.321 0.000 -8.548 0.000 -7.361 -0.000
M SW APARTMENT 2.636 -20.765 0.000 0.000 3.684 2.413 12.213 24.256 0.000 0.366 0.001 0.000 -13.991 0.000 -10.409 -0.401
M NW APARTMENT 5.506 -11.909 0.000 0.000 3.777 2.413 12.213 10.780 0.000 0.362 0.710 0.000 -13.972 0.000 -9.878 -0.000
M SE APARTMENT 2.567 -21.624 0.000 0.000 3.694 2.413 12.213 24.872 0.000 0.362 0.000 0.000 -13.755 0.000 -10.423 -0.318
M NE APARTMENT 5.280 -12.821 0.000 0.000 3.794 2.413 12.213 11.334 0.000 0.355 0.897 0.000 -13.631 0.000 -9.834 -0.000
M N1 APARTMENT 1.731 -11.007 0.000 0.000 3.783 2.413 12.213 3.570 0.000 0.265 3.032 0.000 -8.812 0.000 -7.188 -0.000
M N2 APARTMENT 1.734 -11.031 0.000 0.000 3.784 2.413 12.213 3.569 0.000 0.265 3.045 0.000 -8.806 0.000 -7.186 -0.000
M S1 APARTMENT 0.646 -21.107 0.000 0.000 3.651 2.413 12.213 17.190 0.000 0.265 1.168 0.000 -8.615 0.000 -7.825 -0.000
M S2 APARTMENT 0.646 -21.124 0.000 0.000 3.651 2.413 12.213 17.188 0.000 0.266 1.186 0.000 -8.613 0.000 -7.827 -0.000
F6 SW APARTMENT 2.974 -19.727 0.000 0.000 3.693 2.413 12.213 24.191 0.000 0.397 0.000 0.000 -14.001 0.000 -10.950 -1.202
F6 NW APARTMENT 6.128 -11.284 0.000 0.000 3.786 2.413 12.213 10.762 0.000 0.393 0.000 0.000 -13.982 0.000 -10.372 -0.055
F6 SE APARTMENT 2.896 -20.562 0.000 0.000 3.703 2.413 12.213 24.805 0.000 0.392 0.000 0.000 -13.764 0.000 -10.965 -1.132
F6 NE APARTMENT 5.886 -12.155 0.000 0.000 3.802 2.413 12.213 11.313 0.000 0.384 0.110 0.000 -13.641 0.000 -10.325 -0.000
F6 N1 APARTMENT 2.032 -10.335 0.000 0.000 3.792 2.413 12.213 3.569 0.000 0.290 2.344 0.000 -8.816 0.000 -7.502 -0.000
F6 N2 APARTMENT 2.036 -10.358 0.000 0.000 3.793 2.413 12.213 3.567 0.000 0.289 2.356 0.000 -8.810 0.000 -7.500 -0.000
F6 S1 APARTMENT 0.757 -20.079 0.000 0.000 3.660 2.413 12.213 17.144 0.000 0.289 0.410 0.000 -8.621 0.000 -8.187 -0.000
F6 S2 APARTMENT 0.759 -20.095 0.000 0.000 3.660 2.413 12.213 17.142 0.000 0.290 0.426 0.000 -8.619 0.000 -8.189 -0.000
F7 SW APARTMENT 3.248 -19.072 0.000 0.000 3.700 2.413 12.213 24.129 0.000 0.416 0.000 0.000 -14.022 0.000 -11.431 -1.592
F7 NW APARTMENT 6.599 -10.946 0.000 0.000 3.792 2.413 12.213 10.739 0.000 0.411 0.000 0.000 -14.005 0.000 -10.816 -0.400
F7 SE APARTMENT 3.165 -19.892 0.000 0.000 3.710 2.413 12.213 24.740 0.000 0.411 0.000 0.000 -13.784 0.000 -11.448 -1.528
F7 NE APARTMENT 6.337 -11.781 0.000 0.000 3.808 2.413 12.213 11.286 0.000 0.401 0.000 0.000 -13.663 0.000 -10.768 -0.246
F7 N1 APARTMENT 2.268 -9.965 0.000 0.000 3.799 2.413 12.213 3.564 0.000 0.303 2.021 0.000 -8.828 0.000 -7.788 -0.000
F7 N2 APARTMENT 2.270 -9.983 0.000 0.000 3.800 2.413 12.213 3.562 0.000 0.302 2.033 0.000 -8.822 0.000 -7.787 -0.000
F7 S1 APARTMENT 0.853 -19.435 0.000 0.000 3.667 2.413 12.213 17.101 0.000 0.303 0.029 0.000 -8.634 0.000 -8.510 -0.000
F7 S2 APARTMENT 0.856 -19.453 0.000 0.000 3.668 2.413 12.213 17.099 0.000 0.303 0.046 0.000 -8.632 0.000 -8.512 -0.000
F8 SW APARTMENT 3.550 -18.521 0.000 0.000 3.706 2.413 12.213 24.075 0.000 0.430 0.000 0.000 -14.039 0.000 -11.877 -1.951
F8 NW APARTMENT 7.076 -10.722 0.000 0.000 3.797 2.413 12.213 10.717 0.000 0.426 0.000 0.000 -14.028 0.000 -11.232 -0.660
F8 SE APARTMENT 3.460 -19.334 0.000 0.000 3.716 2.413 12.213 24.683 0.000 0.425 0.001 0.000 -13.799 0.000 -11.894 -1.883
F8 NE APARTMENT 6.799 -11.534 0.000 0.000 3.812 2.413 12.213 11.261 0.000 0.415 0.001 0.000 -13.686 0.000 -11.183 -0.510
F8 N1 APARTMENT 2.527 -9.699 0.000 0.000 3.804 2.413 12.213 3.559 0.000 0.312 1.773 0.000 -8.839 0.000 -8.062 -0.000
F8 N2 APARTMENT 2.529 -9.720 0.000 0.000 3.805 2.413 12.213 3.557 0.000 0.311 1.786 0.000 -8.834 0.000 -8.061 -0.000
F8 S1 APARTMENT 0.970 -18.866 0.000 0.000 3.675 2.413 12.213 17.064 0.000 0.313 0.001 0.000 -8.642 0.000 -8.812 -0.327
F8 S2 APARTMENT 0.972 -18.882 0.000 0.000 3.675 2.413 12.213 17.062 0.000 0.313 0.001 0.000 -8.640 0.000 -8.815 -0.309
F9 SW APARTMENT 4.296 -17.821 0.000 0.000 3.717 2.413 12.213 24.052 0.000 0.444 0.001 0.000 -14.009 0.000 -12.270 -3.035
F9 NW APARTMENT 8.198 -10.664 0.000 0.000 3.801 2.413 12.213 10.707 0.000 0.438 0.000 0.000 -14.026 0.000 -11.609 -1.471
F9 SE APARTMENT 4.171 -18.631 0.000 0.000 3.727 2.413 12.213 24.657 0.000 0.440 0.000 0.000 -13.771 0.000 -12.291 -2.929
F9 NE APARTMENT 7.856 -11.413 0.000 0.000 3.817 2.413 12.213 11.248 0.000 0.426 0.000 0.000 -13.685 0.000 -11.562 -1.312
F9 N1 APARTMENT 3.282 -9.490 0.000 0.000 3.809 2.413 12.213 3.558 0.000 0.322 1.040 0.000 -8.832 0.000 -8.314 -0.000
F9 N2 APARTMENT 3.286 -9.514 0.000 0.000 3.810 2.413 12.213 3.556 0.000 0.321 1.056 0.000 -8.826 0.000 -8.314 -0.000
F9 S1 APARTMENT 1.332 -18.009 0.000 0.000 3.689 2.413 12.213 17.049 0.000 0.323 0.001 0.000 -8.617 0.000 -9.075 -1.316
F9 S2 APARTMENT 1.336 -18.032 0.000 0.000 3.689 2.413 12.213 17.046 0.000 0.323 0.000 0.000 -8.615 0.000 -9.079 -1.294
T SW APARTMENT 9.818 -18.421 0.000 0.000 3.775 2.413 12.213 23.757 0.000 0.455 0.000 0.000 -13.344 0.000 -12.540 -8.125
T NW APARTMENT 13.915 -11.459 0.000 0.000 3.822 2.413 12.213 10.450 0.000 0.450 0.000 0.000 -13.533 0.000 -12.031 -6.240
T SE APARTMENT 9.460 -18.627 0.000 0.000 3.782 2.413 12.213 24.375 0.000 0.454 0.000 0.000 -13.141 0.000 -12.585 -8.343
T NE APARTMENT 13.189 -11.625 0.000 0.000 3.838 2.413 12.213 11.042 0.000 0.443 0.000 0.000 -13.252 0.000 -11.997 -6.263
T N1 APARTMENT 7.526 -9.296 0.000 0.000 3.831 2.413 12.213 3.471 0.000 0.332 0.000 0.000 -8.525 0.000 -8.613 -3.351
T N2 APARTMENT 7.542 -9.313 0.000 0.000 3.832 2.413 12.213 3.465 0.000 0.332 0.000 0.000 -8.519 0.000 -8.618 -3.346
T S1 APARTMENT 4.478 -16.846 0.000 0.000 3.755 2.413 12.213 16.897 0.000 0.336 0.000 0.000 -8.242 0.000 -9.263 -5.741
T S2 APARTMENT 4.486 -16.878 0.000 0.000 3.755 2.413 12.213 16.892 0.000 0.336 0.000 0.000 -8.238 0.000 -9.268 -5.710
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 5.394 0.000 1.263 19.549 0.000 -2.932 0.000 -41.803 -0.001
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.429 0.000 0.015 0.000 0.000 -1.720 0.000 -0.820 -18.433
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.382 0.000 0.017 0.000 0.000 -1.782 0.000 -0.996 -18.150
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.356 0.000 0.018 0.000 0.000 -1.812 0.000 -1.125 -17.967
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 2.325 0.000 0.016 0.000 0.000 -1.854 0.000 -1.271 -36.274
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.336 0.000 0.021 0.000 0.000 -1.828 0.000 -1.304 -17.754
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.336 0.000 0.022 0.000 0.000 -1.821 0.000 -1.368 -17.698
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.332 0.000 0.023 0.000 0.000 -1.820 0.000 -1.429 -17.635
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.331 0.000 0.023 0.000 0.000 -1.816 0.000 -1.481 -17.587
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 2.274 0.000 0.012 0.000 0.000 -1.753 0.000 -1.551 -25.449
Total Facility 292.119 -1173.453 0.000 0.000 297.038 416.414 980.287 1160.157 0.000 26.377 52.910 0.000 -904.477 0.000 -739.985 -407.367


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 02-SEP-17:30 0.00 -2421.42 0.00 0.00 141.80 194.45 588.62 1950.35 0.00 261.26 0.00 0.00 0.00 0.00 0.00 -715.06
G NW APARTMENT 15-JUN-18:00 0.00 -2247.61 0.00 0.00 140.55 194.45 588.62 2982.76 0.00 38.10 0.00 0.00 0.00 0.00 0.00 -1696.86
OFFICE 29-AUG-12:30 0.00 -3113.76 0.00 0.00 65.20 1622.33 544.91 3418.54 0.00 37.21 0.00 0.00 0.00 0.00 0.00 -2574.42
G NE APARTMENT 06-JUN-08:30 0.00 -1567.94 0.00 0.00 40.75 28.81 394.37 2755.58 0.00 226.01 0.00 0.00 0.00 0.00 0.00 -1877.58
G N1 APARTMENT 08-JUN-18:15 0.00 -1129.72 0.00 0.00 141.00 230.46 547.42 739.76 0.00 119.20 0.00 0.00 0.00 0.00 0.00 -648.11
G N2 APARTMENT 08-JUN-18:15 0.00 -1109.20 0.00 0.00 140.91 230.46 547.42 740.07 0.00 118.25 0.00 0.00 0.00 0.00 0.00 -667.91
G S1 APARTMENT 05-SEP-13:30 0.00 -1457.40 0.00 0.00 40.75 28.81 382.60 2234.16 0.00 0.00 0.00 0.00 0.00 0.00 -39.67 -1189.25
G S2 APARTMENT 05-SEP-13:45 0.00 -1503.73 0.00 0.00 40.75 28.81 382.60 2188.11 0.00 0.08 0.00 0.00 0.00 0.00 0.00 -1136.62
F2 SW APARTMENT 02-SEP-17:30 0.00 -3158.14 0.00 0.00 141.80 194.45 588.62 1928.38 0.00 331.87 0.00 0.00 0.00 0.00 0.00 -26.98
F2 NW APARTMENT 15-JUN-18:00 0.00 -2917.58 0.00 0.00 140.85 194.45 588.62 2935.06 0.00 54.77 0.00 0.00 0.00 0.00 0.00 -996.17
F2 SE APARTMENT 31-AUG-09:45 0.00 -2901.09 0.00 0.00 40.75 28.81 406.15 3959.69 0.00 180.40 0.00 0.00 0.00 0.00 0.00 -1714.70
F2 NE APARTMENT 06-JUN-08:30 0.00 -2156.07 0.00 0.00 40.75 28.81 394.37 2714.31 0.00 296.44 0.00 0.00 0.00 0.00 0.00 -1318.61
F2 N1 APARTMENT 08-JUN-18:15 0.00 -1566.60 0.00 0.00 140.67 230.46 547.42 717.86 0.00 144.75 0.00 0.00 0.00 0.00 0.00 -214.56
F2 N2 APARTMENT 08-JUN-18:15 0.00 -1549.41 0.00 0.00 140.60 230.46 547.42 718.00 0.00 143.84 0.00 0.00 0.00 0.00 0.00 -230.91
F2 S1 APARTMENT 16-NOV-12:00 0.00 -2184.10 0.00 0.00 40.75 28.81 412.03 4028.93 0.00 0.00 0.00 0.00 0.00 0.00 -9.05 -2317.37
F2 S2 APARTMENT 16-NOV-12:00 0.00 -2206.10 0.00 0.00 40.75 28.81 412.03 4028.69 0.00 0.00 0.00 0.00 0.00 0.00 -9.05 -2295.14
F3 SW APARTMENT 02-SEP-17:30 0.00 -3171.78 0.00 0.00 141.80 194.45 588.62 1919.79 0.00 371.15 0.00 0.00 0.00 0.00 0.00 -44.03
F3 NW APARTMENT 15-JUN-18:15 0.00 -2947.45 0.00 0.00 140.85 230.46 547.42 2809.01 0.00 48.07 0.00 0.00 0.00 0.00 0.00 -828.34
F3 SE APARTMENT 31-AUG-09:45 0.00 -2751.06 0.00 0.00 40.52 28.81 406.15 3942.25 0.00 174.90 0.00 0.00 0.00 0.00 0.00 -1841.57
F3 NE APARTMENT 06-JUN-08:30 0.00 -2186.75 0.00 0.00 40.75 28.81 394.37 2697.55 0.00 331.11 0.00 0.00 0.00 0.00 0.00 -1305.84
F3 N1 APARTMENT 08-JUN-18:15 0.00 -1603.11 0.00 0.00 140.18 230.46 547.42 711.11 0.00 155.37 0.00 0.00 0.00 0.00 0.00 -181.42
F3 N2 APARTMENT 08-JUN-18:15 0.00 -1586.03 0.00 0.00 140.12 230.46 547.42 711.26 0.00 154.43 0.00 0.00 0.00 0.00 0.00 -197.65
F3 S1 APARTMENT 18-NOV-13:00 0.00 -2284.00 0.00 0.00 40.75 28.81 406.15 3597.06 0.00 0.00 0.00 0.00 0.00 0.00 -71.07 -1717.70
F3 S2 APARTMENT 18-NOV-13:00 0.00 -2291.85 0.00 0.00 40.75 28.81 406.15 3596.97 0.00 0.00 0.00 0.00 0.00 0.00 -71.06 -1709.77
F4 SW APARTMENT 02-SEP-17:30 0.00 -3179.10 0.00 0.00 141.80 194.45 588.62 1913.61 0.00 399.71 0.00 0.00 0.00 0.00 0.00 -59.09
F4 NW APARTMENT 15-JUN-18:15 0.00 -2947.25 0.00 0.00 140.67 230.46 547.42 2794.33 0.00 53.20 0.00 0.00 0.00 0.00 0.00 -818.82
F4 SE APARTMENT 07-NOV-10:45 0.00 -2752.42 0.00 0.00 40.75 28.81 406.15 4478.87 0.00 0.00 0.00 0.00 0.00 0.00 -39.55 -2162.60
F4 NE APARTMENT 26-JUN-08:23 0.00 -2198.04 0.00 0.00 40.75 28.81 394.37 2711.85 0.00 135.75 0.00 0.00 0.00 0.00 0.00 -1113.50
F4 N1 APARTMENT 08-JUN-18:30 0.00 -1616.68 0.00 0.00 140.48 230.46 547.42 640.60 0.00 79.43 0.00 0.00 0.00 0.00 0.00 -21.70
F4 N2 APARTMENT 08-JUN-18:30 0.00 -1601.40 0.00 0.00 140.41 230.46 547.42 640.75 0.00 78.57 0.00 0.00 0.00 0.00 0.00 -36.22
F4 S1 APARTMENT 18-NOV-12:45 0.00 -2305.42 0.00 0.00 40.75 28.81 406.15 3676.01 0.00 0.00 0.00 0.00 0.00 0.00 -77.17 -1769.13
F4 S2 APARTMENT 18-NOV-12:45 0.00 -2314.66 0.00 0.00 40.75 28.81 406.15 3675.94 0.00 0.00 0.00 0.00 0.00 0.00 -77.15 -1759.83
M SW APARTMENT 02-SEP-17:30 0.00 -3209.76 0.00 0.00 141.80 194.45 588.62 1908.07 0.00 422.63 0.00 0.00 0.00 0.00 0.00 -45.81
M NW APARTMENT 15-JUN-18:15 0.00 -2972.97 0.00 0.00 140.58 230.46 547.42 2782.20 0.00 57.37 0.00 0.00 0.00 0.00 0.00 -785.06
M SE APARTMENT 07-NOV-10:45 0.00 -2775.75 0.00 0.00 40.75 28.81 406.15 4471.29 0.00 0.00 0.00 0.00 0.00 0.00 -43.07 -2128.17
M NE APARTMENT 26-JUN-08:30 0.00 -2225.10 0.00 0.00 40.75 28.81 394.37 2704.17 0.00 137.85 0.00 0.00 0.00 0.00 0.00 -1080.84
M N1 APARTMENT 08-JUN-18:30 0.00 -1650.93 0.00 0.00 140.41 230.46 547.42 637.24 0.00 82.06 13.35 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 08-JUN-18:30 0.00 -1633.96 0.00 0.00 140.35 230.46 547.42 637.39 0.00 80.90 0.00 0.00 0.00 0.00 0.00 -2.56
M S1 APARTMENT 18-NOV-12:45 0.00 -2339.06 0.00 0.00 40.75 28.81 406.15 3663.16 0.00 0.00 0.00 0.00 0.00 0.00 -83.95 -1715.86
M S2 APARTMENT 18-NOV-12:45 0.00 -2347.99 0.00 0.00 40.75 28.81 406.15 3663.09 0.00 0.00 0.00 0.00 0.00 0.00 -83.93 -1706.88
F6 SW APARTMENT 02-SEP-17:30 0.00 -3167.80 0.00 0.00 141.80 194.45 588.62 1905.25 0.00 440.72 0.00 0.00 0.00 0.00 0.00 -103.04
F6 NW APARTMENT 15-JUN-18:15 0.00 -2924.97 0.00 0.00 140.45 230.46 547.42 2773.71 0.00 60.79 0.00 0.00 0.00 0.00 0.00 -827.85
F6 SE APARTMENT 07-NOV-10:45 0.00 -2726.34 0.00 0.00 40.75 28.81 406.15 4466.98 0.00 0.00 0.00 0.00 0.00 0.00 -46.07 -2170.27
F6 NE APARTMENT 26-JUN-08:45 0.00 -2187.41 0.00 0.00 40.58 28.81 394.37 2621.29 0.00 228.15 0.00 0.00 0.00 0.00 0.00 -1125.79
F6 N1 APARTMENT 08-JUN-18:30 0.00 -1611.02 0.00 0.00 140.29 230.46 547.42 635.66 0.00 82.07 0.00 0.00 0.00 0.00 0.00 -24.86
F6 N2 APARTMENT 02-AUG-18:15 0.00 -1594.42 0.00 0.00 141.80 230.46 547.42 342.92 0.00 530.85 0.00 0.00 0.00 0.00 0.00 -199.03
F6 S1 APARTMENT 18-NOV-13:00 0.00 -2294.39 0.00 0.00 40.75 28.81 406.15 3558.19 0.00 0.00 0.00 0.00 0.00 0.00 -92.63 -1646.87
F6 S2 APARTMENT 18-NOV-13:00 0.00 -2303.12 0.00 0.00 40.75 28.81 406.15 3558.13 0.00 0.00 0.00 0.00 0.00 0.00 -92.61 -1638.11
F7 SW APARTMENT 02-SEP-17:30 0.00 -3152.28 0.00 0.00 141.80 194.45 588.62 1902.22 0.00 456.21 0.00 0.00 0.00 0.00 0.00 -131.02
F7 NW APARTMENT 08-JUN-17:45 0.00 -2909.68 0.00 0.00 141.80 194.45 588.62 2536.16 0.00 287.61 0.00 0.00 0.00 0.00 0.00 -838.97
F7 SE APARTMENT 31-AUG-09:45 0.00 -2705.24 0.00 0.00 40.48 28.81 406.15 3905.86 0.00 193.43 0.00 0.00 0.00 0.00 0.00 -1869.48
F7 NE APARTMENT 26-JUN-08:45 0.00 -2168.18 0.00 0.00 40.55 28.81 394.37 2616.60 0.00 232.28 0.00 0.00 0.00 0.00 0.00 -1144.44
F7 N1 APARTMENT 05-JUN-18:15 0.00 -1606.00 0.00 0.00 141.81 230.46 547.42 461.30 0.00 372.72 0.00 0.00 0.00 0.00 0.00 -147.71
F7 N2 APARTMENT 05-JUN-18:15 0.00 -1590.14 0.00 0.00 141.81 230.46 547.42 461.56 0.00 372.18 0.00 0.00 0.00 0.00 0.00 -163.29
F7 S1 APARTMENT 18-NOV-13:00 0.00 -2268.87 0.00 0.00 40.75 28.81 406.15 3549.26 0.00 0.00 0.00 0.00 0.00 0.00 -97.96 -1658.14
F7 S2 APARTMENT 18-NOV-13:00 0.00 -2271.67 0.00 0.00 40.75 28.81 406.15 3549.20 0.00 0.00 0.00 0.00 0.00 0.00 -97.96 -1655.28
F8 SW APARTMENT 02-AUG-18:08 0.00 -3155.59 0.00 0.00 141.80 230.46 547.42 1033.93 0.00 1149.61 52.38 0.00 0.00 0.00 0.00 0.00
F8 NW APARTMENT 08-JUN-17:45 0.00 -2910.40 0.00 0.00 141.80 194.45 588.62 2529.51 0.00 294.93 0.00 0.00 0.00 0.00 0.00 -838.92
F8 SE APARTMENT 31-AUG-09:45 0.00 -2703.04 0.00 0.00 40.50 28.81 406.15 3899.91 0.00 197.63 0.00 0.00 0.00 0.00 0.00 -1869.95
F8 NE APARTMENT 26-JUN-08:45 0.00 -2164.16 0.00 0.00 40.53 28.81 394.37 2612.02 0.00 235.85 0.00 0.00 0.00 0.00 0.00 -1147.43
F8 N1 APARTMENT 05-JUN-18:15 0.00 -1614.84 0.00 0.00 141.81 230.46 547.42 460.40 0.00 383.66 0.00 0.00 0.00 0.00 0.00 -148.91
F8 N2 APARTMENT 05-JUN-18:15 0.00 -1599.01 0.00 0.00 141.81 230.46 547.42 460.66 0.00 383.09 0.00 0.00 0.00 0.00 0.00 -164.43
F8 S1 APARTMENT 15-NOV-13:00 0.00 -2237.84 0.00 0.00 40.75 28.81 406.15 3653.09 0.00 0.00 0.00 0.00 0.00 0.00 -60.61 -1830.35
F8 S2 APARTMENT 16-NOV-12:00 0.00 -2244.27 0.00 0.00 40.58 28.81 412.03 4011.98 0.00 0.00 0.00 0.00 0.00 0.00 -15.76 -2233.38
F9 SW APARTMENT 02-AUG-18:08 0.00 -3267.95 0.00 0.00 141.80 230.46 547.42 1028.68 0.00 1188.41 131.18 0.00 0.00 0.00 0.00 0.00
F9 NW APARTMENT 15-JUN-18:15 0.00 -3002.43 0.00 0.00 140.64 230.46 547.42 2750.31 0.00 69.49 0.00 0.00 0.00 0.00 0.00 -735.90
F9 SE APARTMENT 02-AUG-18:15 0.00 -2769.72 0.00 0.00 141.80 230.46 547.42 248.76 0.00 1107.48 493.80 0.00 0.00 0.00 0.00 0.00
F9 NE APARTMENT 02-AUG-18:15 0.00 -2196.36 0.00 0.00 141.80 230.46 547.42 433.89 0.00 685.22 157.56 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 05-JUN-18:15 0.00 -1708.13 0.00 0.00 141.81 230.46 547.42 457.86 0.00 396.51 0.00 0.00 0.00 0.00 0.00 -65.92
F9 N2 APARTMENT 05-JUN-18:15 0.00 -1692.01 0.00 0.00 141.81 230.46 547.42 458.12 0.00 395.91 0.00 0.00 0.00 0.00 0.00 -81.70
F9 S1 APARTMENT 16-NOV-12:15 0.00 -2254.48 0.00 0.00 40.75 28.81 406.15 3984.50 0.00 0.00 0.00 0.00 0.00 0.00 -27.25 -2178.47
F9 S2 APARTMENT 16-NOV-12:15 0.00 -2264.76 0.00 0.00 40.75 28.81 406.15 3984.38 0.00 0.00 0.00 0.00 0.00 0.00 -27.25 -2168.08
T SW APARTMENT 12-SEP-15:15 0.00 -3996.53 0.00 0.00 48.90 100.83 470.89 3525.00 0.00 48.24 0.00 0.00 0.00 0.00 0.00 -197.33
T NW APARTMENT 15-JUN-17:30 0.00 -3657.54 0.00 0.00 140.75 194.45 588.62 2977.69 0.00 203.80 0.00 0.00 0.00 0.00 0.00 -447.77
T SE APARTMENT 31-AUG-10:45 0.00 -3567.67 0.00 0.00 40.30 28.81 412.03 3760.73 0.00 17.26 0.00 0.00 0.00 0.00 0.00 -691.45
T NE APARTMENT 26-JUN-08:45 0.00 -2804.47 0.00 0.00 40.75 28.81 394.37 2573.61 0.00 268.01 0.00 0.00 0.00 0.00 0.00 -501.08
T N1 APARTMENT 29-JUN-17:08 0.00 -2245.36 0.00 0.00 141.80 194.45 588.62 501.23 0.00 648.12 171.14 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-17:08 0.00 -2240.56 0.00 0.00 141.80 194.45 588.62 501.45 0.00 648.73 165.50 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 16-NOV-12:45 0.00 -2976.23 0.00 0.00 40.75 28.81 406.15 3799.23 0.00 0.00 0.00 0.00 0.00 0.00 -45.84 -1252.87
T S2 APARTMENT 16-NOV-12:45 0.00 -2985.50 0.00 0.00 40.75 28.81 406.15 3799.02 0.00 0.00 0.00 0.00 0.00 0.00 -45.84 -1243.39
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-AUG-18:15 0.00 -175434.69 0.00 0.00 11202.54 25049.15 43784.02 41209.79 0.00 57195.12 0.00 0.00 0.00 0.00 -88.21 -2917.72


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 21-DEC-07:55 2141.36 0.00 0.00 0.00 161.22 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -1955.65 0.00 -348.20 -474.96
G NW APARTMENT 21-DEC-07:55 2145.72 0.00 0.00 0.00 161.22 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -1952.08 0.00 -348.20 -482.89
OFFICE 21-DEC-07:50 2301.56 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -1959.94 0.00 -348.20 -567.99
G NE APARTMENT 21-DEC-18:30 2182.49 0.00 0.00 0.00 165.01 194.45 588.62 0.00 0.00 0.00 0.00 0.00 -1631.98 0.00 -655.59 -843.00
G N1 APARTMENT 23-DEC-08:10 1332.54 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -781.68 0.00 -245.35 -811.18
G N2 APARTMENT 23-DEC-08:10 1327.95 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -781.75 0.00 -245.35 -806.53
G S1 APARTMENT 21-DEC-08:00 1270.44 0.00 0.00 0.00 161.22 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -1195.87 0.00 -210.02 -501.99
G S2 APARTMENT 21-DEC-08:00 1265.60 0.00 0.00 0.00 161.22 93.62 382.60 0.00 0.00 0.00 0.00 0.00 -1196.01 0.00 -210.02 -497.01
F2 SW APARTMENT 21-DEC-05:00 2134.86 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1920.81 0.00 -414.73 -255.89
F2 NW APARTMENT 22-DEC-04:00 2323.42 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1688.45 0.00 -659.38 -403.35
F2 SE APARTMENT 21-DEC-05:00 2102.78 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1922.19 0.00 -414.73 -222.42
F2 NE APARTMENT 22-DEC-04:00 2353.63 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1682.90 0.00 -659.38 -439.10
F2 N1 APARTMENT 22-DEC-04:00 1318.13 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1029.09 0.00 -397.72 -319.08
F2 N2 APARTMENT 22-DEC-04:00 1319.92 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1029.05 0.00 -397.72 -320.90
F2 S1 APARTMENT 21-DEC-05:00 1154.55 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1175.51 0.00 -250.15 -185.45
F2 S2 APARTMENT 21-DEC-05:00 1151.90 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1175.58 0.00 -250.15 -182.73
F3 SW APARTMENT 19-MAR-07:53 2179.63 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 87.14 0.00 -1508.40 0.00 -1264.04 0.00
F3 NW APARTMENT 22-DEC-04:00 2371.22 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1711.27 0.00 -780.86 -306.83
F3 SE APARTMENT 19-MAR-07:53 2174.21 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 92.83 0.00 -1508.67 0.00 -1264.04 0.00
F3 NE APARTMENT 22-DEC-04:00 2399.99 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1702.80 0.00 -780.87 -344.08
F3 N1 APARTMENT 09-APR-13:30 1445.95 0.00 0.00 0.00 43.47 28.81 382.60 193.93 0.00 0.00 0.00 0.00 0.00 0.00 -1861.27 -233.49
F3 N2 APARTMENT 09-APR-13:30 1447.33 0.00 0.00 0.00 43.52 28.81 382.60 194.49 0.00 0.00 0.00 0.00 0.00 0.00 -1861.18 -235.56
F3 S1 APARTMENT 21-DEC-05:00 1104.54 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1178.94 0.00 -296.26 -85.90
F3 S2 APARTMENT 21-DEC-05:00 1104.22 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1178.95 0.00 -296.26 -85.57
F4 SW APARTMENT 19-MAR-07:53 2295.93 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 122.76 0.00 -1510.97 0.00 -1413.39 0.00
F4 NW APARTMENT 21-DEC-23:00 2455.42 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1619.30 0.00 -1264.60 -265.54
F4 SE APARTMENT 19-MAR-07:53 2295.18 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 123.55 0.00 -1511.01 0.00 -1413.40 0.00
F4 NE APARTMENT 21-DEC-23:00 2517.17 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1634.94 0.00 -1264.61 -311.63
F4 N1 APARTMENT 09-APR-13:30 1492.74 0.00 0.00 0.00 43.41 28.81 382.60 189.42 0.00 0.00 0.00 0.00 0.00 0.00 -2056.76 -80.22
F4 N2 APARTMENT 09-APR-13:30 1481.37 0.00 0.00 0.00 43.46 28.81 382.60 190.04 0.00 0.00 0.00 0.00 0.00 0.00 -2056.67 -69.61
F4 S1 APARTMENT 21-DEC-05:00 1113.00 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1180.33 0.00 -331.24 -57.99
F4 S2 APARTMENT 21-DEC-05:00 1113.25 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1180.33 0.00 -331.24 -58.25
M SW APARTMENT 19-MAR-07:10 2405.23 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 156.04 0.00 -1427.95 0.00 -1638.99 0.00
M NW APARTMENT 21-DEC-23:00 2543.39 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1629.01 0.00 -1374.74 -233.66
M SE APARTMENT 19-MAR-07:10 2405.70 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 155.55 0.00 -1427.93 0.00 -1638.99 0.00
M NE APARTMENT 21-DEC-23:00 2605.83 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1646.02 0.00 -1374.75 -279.07
M N1 APARTMENT 09-APR-13:30 1544.98 0.00 0.00 0.00 43.42 28.81 382.60 186.88 0.00 0.00 35.13 0.00 0.00 0.00 -2221.83 0.00
M N2 APARTMENT 09-APR-13:30 1535.57 0.00 0.00 0.00 43.48 28.81 382.60 187.53 0.00 0.00 43.74 0.00 0.00 0.00 -2221.73 0.00
M S1 APARTMENT 21-DEC-05:00 1113.96 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1181.79 0.00 -360.09 -28.63
M S2 APARTMENT 21-DEC-05:00 1114.32 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 0.00 0.00 -1181.78 0.00 -360.09 -29.01
F6 SW APARTMENT 19-MAR-07:10 2563.84 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 117.49 0.00 -1434.72 0.00 -1752.28 0.00
F6 NW APARTMENT 21-DEC-23:00 2679.41 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1634.95 0.00 -1469.71 -268.76
F6 SE APARTMENT 19-MAR-07:10 2564.21 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 117.10 0.00 -1434.70 0.00 -1752.28 0.00
F6 NE APARTMENT 21-DEC-23:00 2742.75 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1653.02 0.00 -1469.72 -314.02
F6 N1 APARTMENT 09-APR-13:25 1956.53 0.00 0.00 0.00 43.83 28.81 382.60 189.21 0.00 0.00 0.00 0.00 0.00 0.00 -2386.37 -214.60
F6 N2 APARTMENT 09-APR-13:25 1980.69 0.00 0.00 0.00 43.88 28.81 382.60 189.86 0.00 0.00 0.00 0.00 0.00 0.00 -2385.40 -240.44
F6 S1 APARTMENT 19-MAR-07:53 1198.84 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 215.65 0.00 -929.23 0.00 -990.94 0.00
F6 S2 APARTMENT 19-MAR-07:53 1199.00 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 215.49 0.00 -929.22 0.00 -990.94 0.00
F7 SW APARTMENT 19-MAR-07:10 2694.92 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 92.88 0.00 -1440.74 0.00 -1852.73 0.00
F7 NW APARTMENT 21-DEC-23:00 2783.07 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1640.51 0.00 -1553.90 -282.67
F7 SE APARTMENT 19-MAR-07:10 2694.87 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 92.93 0.00 -1440.74 0.00 -1852.73 0.00
F7 NE APARTMENT 21-DEC-23:00 2846.83 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1659.21 0.00 -1553.91 -327.72
F7 N1 APARTMENT 09-APR-13:25 2379.35 0.00 0.00 0.00 44.11 28.81 382.60 190.70 0.00 0.00 0.00 0.00 0.00 0.00 -2509.99 -515.59
F7 N2 APARTMENT 09-APR-13:25 2400.72 0.00 0.00 0.00 44.16 28.81 382.60 191.31 0.00 0.00 0.00 0.00 0.00 0.00 -2509.12 -538.49
F7 S1 APARTMENT 09-APR-13:30 1436.02 0.00 0.00 0.00 40.75 28.81 382.60 229.30 0.00 0.00 389.69 0.00 0.00 0.00 -2507.17 0.00
F7 S2 APARTMENT 09-APR-13:30 1434.08 0.00 0.00 0.00 40.75 28.81 382.60 229.32 0.00 0.00 391.71 0.00 0.00 0.00 -2507.28 0.00
F8 SW APARTMENT 19-MAR-07:10 2830.62 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 52.52 0.00 -1445.30 0.00 -1943.52 0.00
F8 NW APARTMENT 19-MAR-07:10 2896.05 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 22.85 0.00 -1481.06 0.00 -1943.52 0.00
F8 SE APARTMENT 19-MAR-07:10 2830.14 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 53.01 0.00 -1445.31 0.00 -1943.52 0.00
F8 NE APARTMENT 21-DEC-23:00 2948.34 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1664.52 0.00 -1629.99 -347.84
F8 N1 APARTMENT 09-APR-13:25 2726.43 0.00 0.00 0.00 44.34 28.81 382.60 191.79 0.00 0.00 0.00 0.00 0.00 0.00 -2624.29 -749.68
F8 N2 APARTMENT 09-APR-13:25 2746.02 0.00 0.00 0.00 44.38 28.81 382.60 192.31 0.00 0.00 0.00 0.00 0.00 0.00 -2623.54 -770.59
F8 S1 APARTMENT 09-APR-13:30 1842.49 0.00 0.00 0.00 40.75 28.81 382.60 229.02 0.00 0.00 97.97 0.00 0.00 0.00 -2621.65 0.00
F8 S2 APARTMENT 09-APR-13:30 1844.38 0.00 0.00 0.00 40.75 28.81 382.60 229.07 0.00 0.00 96.08 0.00 0.00 0.00 -2621.70 0.00
F9 SW APARTMENT 19-MAR-07:10 3089.89 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1444.60 0.00 -2026.72 -124.24
F9 NW APARTMENT 19-MAR-07:10 3145.41 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1481.19 0.00 -2026.72 -143.17
F9 SE APARTMENT 19-MAR-07:10 3088.84 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1444.63 0.00 -2026.72 -123.15
F9 NE APARTMENT 21-DEC-23:00 3152.83 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1665.75 0.00 -1699.70 -481.39
F9 N1 APARTMENT 09-APR-13:25 2960.47 0.00 0.00 0.00 44.66 28.81 382.60 194.73 0.00 0.00 0.00 0.00 0.00 0.00 -2732.05 -879.22
F9 N2 APARTMENT 09-APR-13:25 2957.53 0.00 0.00 0.00 44.68 28.81 382.60 194.94 0.00 0.00 0.00 0.00 0.00 0.00 -2731.96 -876.61
F9 S1 APARTMENT 09-APR-11:00 1942.23 0.00 0.00 0.00 40.76 28.81 412.03 1938.86 0.00 0.00 0.00 0.00 0.00 0.00 -3204.02 -1158.67
F9 S2 APARTMENT 09-APR-11:00 1917.98 0.00 0.00 0.00 40.75 28.81 412.03 1938.55 0.00 0.00 0.00 0.00 0.00 0.00 -3204.08 -1134.05
T SW APARTMENT 19-MAR-07:10 3867.64 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1412.57 0.00 -2103.62 -857.12
T NW APARTMENT 19-MAR-07:10 3913.04 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1448.17 0.00 -2103.62 -866.91
T SE APARTMENT 19-MAR-07:10 3866.91 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1412.60 0.00 -2103.62 -856.35
T NE APARTMENT 21-DEC-23:00 3933.13 0.00 0.00 0.00 189.67 86.42 417.92 0.00 0.00 0.00 0.00 0.00 -1632.00 0.00 -1764.12 -1231.02
T N1 APARTMENT 09-APR-13:25 3158.13 0.00 0.00 0.00 43.89 28.81 382.60 186.62 0.00 0.00 0.00 0.00 0.00 0.00 -2845.80 -954.26
T N2 APARTMENT 09-APR-13:25 3152.14 0.00 0.00 0.00 43.85 28.81 382.60 186.04 0.00 0.00 0.00 0.00 0.00 0.00 -2846.55 -946.89
T S1 APARTMENT 22-DEC-04:00 2496.33 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1075.49 0.00 -734.42 -1114.17
T S2 APARTMENT 22-DEC-04:00 2497.46 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1075.46 0.00 -734.42 -1115.33
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-MAR-07:10 159001.26 0.00 0.00 0.00 5843.75 10256.44 31331.16 0.00 0.00 0.00 0.00 0.00 -93677.15 0.00 -109834.66 -2920.81



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Sec1.1A-General Information

Data
Weather File Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 124.75
Number of hours cooling loads not met 390.25
Number of hours not met 518.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.38 10720.10 0.00 0.00 0.00 0.00
Space Heating 123.71 0.00 391.48 195077.61 0.00 0.00
Space Cooling 405.35 58819.02 0.00 0.00 0.00 0.00
Pumps 42.97 1376.68 0.00 0.00 0.00 0.00
Heat Rejection 13.98 1866.58 0.00 0.00 0.00 0.00
Fans-Interior 708.77 22475.07 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1202.88 87982.13 0.00 0.00
Receptacle Equipment 1131.09 49704.83 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3031.50   1594.36   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3031.50
Natural Gas 0.00 1594.36
Additional 0.00 0.00
Total 1131.09 4625.87


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 15.79
Space Cooling 51.73
Fans-Interior 90.45
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 31.41
Subtotal 386.85


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 49.96
Service Water Heating 153.50
Miscellaneous -0.00
Subtotal 203.45


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 9.00
Space Heating 11.14
Space Cooling 8.76
Fans-Interior 15.32
Service Water Heating 26.00
Receptacle Equipment 24.45
Miscellaneous 5.32



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.259745
G NW APARTMENT DIRECT AIR 0.248195
OFFICE DIRECT AIR 0.337712
G NE APARTMENT DIRECT AIR 0.174305
G N1 APARTMENT DIRECT AIR 0.125100
G N2 APARTMENT DIRECT AIR 0.122965
G S1 APARTMENT DIRECT AIR 0.147636
G S2 APARTMENT DIRECT AIR 0.153872
F2 SW APARTMENT DIRECT AIR 0.340348
F2 NW APARTMENT DIRECT AIR 0.321846
F2 SE APARTMENT DIRECT AIR 0.306068
F2 NE APARTMENT DIRECT AIR 0.237162
F2 N1 APARTMENT DIRECT AIR 0.171224
F2 N2 APARTMENT DIRECT AIR 0.169420
F2 S1 APARTMENT DIRECT AIR 0.200856
F2 S2 APARTMENT DIRECT AIR 0.203294
F3 SW APARTMENT DIRECT AIR 0.342722
F3 NW APARTMENT DIRECT AIR 0.325158
F3 SE APARTMENT DIRECT AIR 0.289971
F3 NE APARTMENT DIRECT AIR 0.240992
F3 N1 APARTMENT DIRECT AIR 0.175688
F3 N2 APARTMENT DIRECT AIR 0.173889
F3 S1 APARTMENT DIRECT AIR 0.205644
F3 S2 APARTMENT DIRECT AIR 0.206879
F4 SW APARTMENT DIRECT AIR 0.344373
F4 NW APARTMENT DIRECT AIR 0.326873
F4 SE APARTMENT DIRECT AIR 0.289812
F4 NE APARTMENT DIRECT AIR 0.241915
F4 N1 APARTMENT DIRECT AIR 0.177492
F4 N2 APARTMENT DIRECT AIR 0.175689
F4 S1 APARTMENT DIRECT AIR 0.207515
F4 S2 APARTMENT DIRECT AIR 0.208574
M SW APARTMENT DIRECT AIR 0.348419
M NW APARTMENT DIRECT AIR 0.331030
M SE APARTMENT DIRECT AIR 0.293661
M NE APARTMENT DIRECT AIR 0.245349
M N1 APARTMENT DIRECT AIR 0.181513
M N2 APARTMENT DIRECT AIR 0.179708
M S1 APARTMENT DIRECT AIR 0.211558
M S2 APARTMENT DIRECT AIR 0.212586
F6 SW APARTMENT DIRECT AIR 0.344594
F6 NW APARTMENT DIRECT AIR 0.327097
F6 SE APARTMENT DIRECT AIR 0.289950
F6 NE APARTMENT DIRECT AIR 0.240975
F6 N1 APARTMENT DIRECT AIR 0.177857
F6 N2 APARTMENT DIRECT AIR 0.176059
F6 S1 APARTMENT DIRECT AIR 0.207915
F6 S2 APARTMENT DIRECT AIR 0.208935
F7 SW APARTMENT DIRECT AIR 0.343548
F7 NW APARTMENT DIRECT AIR 0.326070
F7 SE APARTMENT DIRECT AIR 0.288991
F7 NE APARTMENT DIRECT AIR 0.239504
F7 N1 APARTMENT DIRECT AIR 0.176946
F7 N2 APARTMENT DIRECT AIR 0.175151
F7 S1 APARTMENT DIRECT AIR 0.206962
F7 S2 APARTMENT DIRECT AIR 0.207978
F8 SW APARTMENT DIRECT AIR 0.344086
F8 NW APARTMENT DIRECT AIR 0.326641
F8 SE APARTMENT DIRECT AIR 0.289492
F8 NE APARTMENT DIRECT AIR 0.239560
F8 N1 APARTMENT DIRECT AIR 0.177630
F8 N2 APARTMENT DIRECT AIR 0.175841
F8 S1 APARTMENT DIRECT AIR 0.207484
F8 S2 APARTMENT DIRECT AIR 0.208499
F9 SW APARTMENT DIRECT AIR 0.356089
F9 NW APARTMENT DIRECT AIR 0.338404
F9 SE APARTMENT DIRECT AIR 0.297451
F9 NE APARTMENT DIRECT AIR 0.242791
F9 N1 APARTMENT DIRECT AIR 0.187895
F9 N2 APARTMENT DIRECT AIR 0.186074
F9 S1 APARTMENT DIRECT AIR 0.214334
F9 S2 APARTMENT DIRECT AIR 0.215473
T SW APARTMENT DIRECT AIR 0.442383
T NW APARTMENT DIRECT AIR 0.413882
T SE APARTMENT DIRECT AIR 0.386035
T NE APARTMENT DIRECT AIR 0.308506
T N1 APARTMENT DIRECT AIR 0.241054
T N2 APARTMENT DIRECT AIR 0.240585
T S1 APARTMENT DIRECT AIR 0.314364
T S2 APARTMENT DIRECT AIR 0.315251


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.259745
AIRLOOP G NW MAIN BRANCH 0.248195
AIRLOOP OFFICE MAIN BRANCH 0.337712
AIRLOOP G NE MAIN BRANCH 0.174305
AIRLOOP G N1 MAIN BRANCH 0.125100
AIRLOOP G N2 MAIN BRANCH 0.122965
AIRLOOP G S1 MAIN BRANCH 0.147636
AIRLOOP G S2 MAIN BRANCH 0.153872
AIRLOOP F2 SW MAIN BRANCH 0.340348
AIRLOOP F2 NW MAIN BRANCH 0.321846
AIRLOOP F2 SE MAIN BRANCH 0.306068
AIRLOOP F2 NE MAIN BRANCH 0.237162
AIRLOOP F2 N1 MAIN BRANCH 0.171224
AIRLOOP F2 N2 MAIN BRANCH 0.169420
AIRLOOP F2 S1 MAIN BRANCH 0.200856
AIRLOOP F2 S2 MAIN BRANCH 0.203294
AIRLOOP F3 SW MAIN BRANCH 0.342722
AIRLOOP F3 NW MAIN BRANCH 0.325158
AIRLOOP F3 SE MAIN BRANCH 0.289971
AIRLOOP F3 NE MAIN BRANCH 0.240992
AIRLOOP F3 N1 MAIN BRANCH 0.175688
AIRLOOP F3 N2 MAIN BRANCH 0.173889
AIRLOOP F3 S1 MAIN BRANCH 0.205644
AIRLOOP F3 S2 MAIN BRANCH 0.206879
AIRLOOP F4 SW MAIN BRANCH 0.344373
AIRLOOP F4 NW MAIN BRANCH 0.326873
AIRLOOP F4 SE MAIN BRANCH 0.289812
AIRLOOP F4 NE MAIN BRANCH 0.241915
AIRLOOP F4 N1 MAIN BRANCH 0.177492
AIRLOOP F4 N2 MAIN BRANCH 0.175689
AIRLOOP F4 S1 MAIN BRANCH 0.207515
AIRLOOP F4 S2 MAIN BRANCH 0.208574
AIRLOOP M SW MAIN BRANCH 0.348419
AIRLOOP M NW MAIN BRANCH 0.331030
AIRLOOP M SE MAIN BRANCH 0.293661
AIRLOOP M NE MAIN BRANCH 0.245349
AIRLOOP M N1 MAIN BRANCH 0.181513
AIRLOOP M N2 MAIN BRANCH 0.179708
AIRLOOP M S1 MAIN BRANCH 0.211558
AIRLOOP M S2 MAIN BRANCH 0.212586
AIRLOOP F6 SW MAIN BRANCH 0.344594
AIRLOOP F6 NW MAIN BRANCH 0.327097
AIRLOOP F6 SE MAIN BRANCH 0.289950
AIRLOOP F6 NE MAIN BRANCH 0.240975
AIRLOOP F6 N1 MAIN BRANCH 0.177857
AIRLOOP F6 N2 MAIN BRANCH 0.176059
AIRLOOP F6 S1 MAIN BRANCH 0.207915
AIRLOOP F6 S2 MAIN BRANCH 0.208935
AIRLOOP F7 SW MAIN BRANCH 0.343548
AIRLOOP F7 NW MAIN BRANCH 0.326070
AIRLOOP F7 SE MAIN BRANCH 0.288991
AIRLOOP F7 NE MAIN BRANCH 0.239504
AIRLOOP F7 N1 MAIN BRANCH 0.176946
AIRLOOP F7 N2 MAIN BRANCH 0.175151
AIRLOOP F7 S1 MAIN BRANCH 0.206962
AIRLOOP F7 S2 MAIN BRANCH 0.207978
AIRLOOP F8 SW MAIN BRANCH 0.344086
AIRLOOP F8 NW MAIN BRANCH 0.326641
AIRLOOP F8 SE MAIN BRANCH 0.289492
AIRLOOP F8 NE MAIN BRANCH 0.239560
AIRLOOP F8 N1 MAIN BRANCH 0.177630
AIRLOOP F8 N2 MAIN BRANCH 0.175841
AIRLOOP F8 S1 MAIN BRANCH 0.207484
AIRLOOP F8 S2 MAIN BRANCH 0.208499
AIRLOOP F9 SW MAIN BRANCH 0.356089
AIRLOOP F9 NW MAIN BRANCH 0.338404
AIRLOOP F9 SE MAIN BRANCH 0.297451
AIRLOOP F9 NE MAIN BRANCH 0.242791
AIRLOOP F9 N1 MAIN BRANCH 0.187895
AIRLOOP F9 N2 MAIN BRANCH 0.186074
AIRLOOP F9 S1 MAIN BRANCH 0.214334
AIRLOOP F9 S2 MAIN BRANCH 0.215473
AIRLOOP T SW MAIN BRANCH 0.442383
AIRLOOP T NW MAIN BRANCH 0.413882
AIRLOOP T SE MAIN BRANCH 0.386035
AIRLOOP T NE MAIN BRANCH 0.308506
AIRLOOP T N1 MAIN BRANCH 0.241054
AIRLOOP T N2 MAIN BRANCH 0.240585
AIRLOOP T S1 MAIN BRANCH 0.314364
AIRLOOP T S2 MAIN BRANCH 0.315251


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.259745
AIRLOOP G NW 0.248195
AIRLOOP OFFICE 0.337712
AIRLOOP G NE 0.174305
AIRLOOP G N1 0.125100
AIRLOOP G N2 0.122965
AIRLOOP G S1 0.147636
AIRLOOP G S2 0.153872
AIRLOOP F2 SW 0.340348
AIRLOOP F2 NW 0.321846
AIRLOOP F2 SE 0.306068
AIRLOOP F2 NE 0.237162
AIRLOOP F2 N1 0.171224
AIRLOOP F2 N2 0.169420
AIRLOOP F2 S1 0.200856
AIRLOOP F2 S2 0.203294
AIRLOOP F3 SW 0.342722
AIRLOOP F3 NW 0.325158
AIRLOOP F3 SE 0.289971
AIRLOOP F3 NE 0.240992
AIRLOOP F3 N1 0.175688
AIRLOOP F3 N2 0.173889
AIRLOOP F3 S1 0.205644
AIRLOOP F3 S2 0.206879
AIRLOOP F4 SW 0.344373
AIRLOOP F4 NW 0.326873
AIRLOOP F4 SE 0.289812
AIRLOOP F4 NE 0.241915
AIRLOOP F4 N1 0.177492
AIRLOOP F4 N2 0.175689
AIRLOOP F4 S1 0.207515
AIRLOOP F4 S2 0.208574
AIRLOOP M SW 0.348419
AIRLOOP M NW 0.331030
AIRLOOP M SE 0.293661
AIRLOOP M NE 0.245349
AIRLOOP M N1 0.181513
AIRLOOP M N2 0.179708
AIRLOOP M S1 0.211558
AIRLOOP M S2 0.212586
AIRLOOP F6 SW 0.344594
AIRLOOP F6 NW 0.327097
AIRLOOP F6 SE 0.289950
AIRLOOP F6 NE 0.240975
AIRLOOP F6 N1 0.177857
AIRLOOP F6 N2 0.176059
AIRLOOP F6 S1 0.207915
AIRLOOP F6 S2 0.208935
AIRLOOP F7 SW 0.343548
AIRLOOP F7 NW 0.326070
AIRLOOP F7 SE 0.288991
AIRLOOP F7 NE 0.239504
AIRLOOP F7 N1 0.176946
AIRLOOP F7 N2 0.175151
AIRLOOP F7 S1 0.206962
AIRLOOP F7 S2 0.207978
AIRLOOP F8 SW 0.344086
AIRLOOP F8 NW 0.326641
AIRLOOP F8 SE 0.289492
AIRLOOP F8 NE 0.239560
AIRLOOP F8 N1 0.177630
AIRLOOP F8 N2 0.175841
AIRLOOP F8 S1 0.207484
AIRLOOP F8 S2 0.208499
AIRLOOP F9 SW 0.356089
AIRLOOP F9 NW 0.338404
AIRLOOP F9 SE 0.297451
AIRLOOP F9 NE 0.242791
AIRLOOP F9 N1 0.187895
AIRLOOP F9 N2 0.186074
AIRLOOP F9 S1 0.214334
AIRLOOP F9 S2 0.215473
AIRLOOP T SW 0.442383
AIRLOOP T NW 0.413882
AIRLOOP T SE 0.386035
AIRLOOP T NE 0.308506
AIRLOOP T N1 0.241054
AIRLOOP T N2 0.240585
AIRLOOP T S1 0.314364
AIRLOOP T S2 0.315251


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.259745 0.025952
AIRLOOP G NW OA CONTROLLER 0.248195 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.337712 0.038103
AIRLOOP G NE OA CONTROLLER 0.174305 0.025952
AIRLOOP G N1 OA CONTROLLER 0.125100 0.025952
AIRLOOP G N2 OA CONTROLLER 0.122965 0.025952
AIRLOOP G S1 OA CONTROLLER 0.147636 0.025952
AIRLOOP G S2 OA CONTROLLER 0.153872 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.340348 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.321846 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.306068 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.237162 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.171224 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.169420 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.200856 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.203294 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.342722 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.325158 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.289971 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.240992 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.175688 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.173889 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.205644 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.206879 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.344373 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.326873 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.289812 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.241915 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.177492 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.175689 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.207515 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.208574 0.025952
AIRLOOP M SW OA CONTROLLER 0.348419 0.025952
AIRLOOP M NW OA CONTROLLER 0.331030 0.025952
AIRLOOP M SE OA CONTROLLER 0.293661 0.025952
AIRLOOP M NE OA CONTROLLER 0.245349 0.025952
AIRLOOP M N1 OA CONTROLLER 0.181513 0.025952
AIRLOOP M N2 OA CONTROLLER 0.179708 0.025952
AIRLOOP M S1 OA CONTROLLER 0.211558 0.025952
AIRLOOP M S2 OA CONTROLLER 0.212586 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.344594 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.327097 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.289950 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.240975 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.177857 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.176059 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.207915 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.208935 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.343548 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.326070 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.288991 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.239504 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.176946 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.175151 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.206962 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.207978 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.344086 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.326641 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.289492 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.239560 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.177630 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.175841 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.207484 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.208499 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.356089 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.338404 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.297451 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.242791 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.187895 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.186074 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.214334 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.215473 0.025952
AIRLOOP T SW OA CONTROLLER 0.442383 0.025952
AIRLOOP T NW OA CONTROLLER 0.413882 0.025952
AIRLOOP T SE OA CONTROLLER 0.386035 0.025952
AIRLOOP T NE OA CONTROLLER 0.308506 0.025952
AIRLOOP T N1 OA CONTROLLER 0.241054 0.025952
AIRLOOP T N2 OA CONTROLLER 0.240585 0.025952
AIRLOOP T S1 OA CONTROLLER 0.314364 0.025952
AIRLOOP T S2 OA CONTROLLER 0.315251 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.259745 3140.46 2013.48 0.000069
HEAT PUMP COOLING MODE AIRLOOP G NW 0.248195 2982.23 1915.92 0.000065
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.337712 4135.24 2650.50 0.000090
HEAT PUMP COOLING MODE AIRLOOP G NE 0.174305 2027.42 1332.72 0.000044
HEAT PUMP COOLING MODE AIRLOOP G N1 0.125100 1470.94 968.40 0.000032
HEAT PUMP COOLING MODE AIRLOOP G N2 0.122965 1444.78 952.15 0.000032
HEAT PUMP COOLING MODE AIRLOOP G S1 0.147636 1851.76 1186.33 0.000040
HEAT PUMP COOLING MODE AIRLOOP G S2 0.153872 1922.53 1232.04 0.000042
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.340348 4095.57 2619.00 0.000089
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.321846 3864.28 2475.16 0.000084
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.306068 3729.89 2382.43 0.000081
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.237162 2775.38 1810.67 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.171224 2024.27 1317.46 0.000044
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.169420 2002.26 1303.75 0.000044
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.200856 2485.33 1589.49 0.000054
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.203294 2514.85 1608.02 0.000055
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.342722 4115.38 2637.89 0.000090
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.325158 3893.13 2498.43 0.000085
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.289971 3524.24 2258.52 0.000077
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.240992 2810.50 1837.88 0.000061
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.175688 2072.15 1350.31 0.000045
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.173889 2050.22 1336.64 0.000045
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.205644 2536.83 1624.82 0.000055
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.206879 2551.79 1634.20 0.000056
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.344373 4126.84 2649.01 0.000090
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.326873 3905.42 2510.04 0.000085
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.289812 3514.11 2255.96 0.000077
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.241915 2813.34 1843.53 0.000061
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.177492 2089.20 1363.21 0.000046
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.175689 2067.24 1349.52 0.000045
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.207515 2554.62 1638.24 0.000056
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.208574 2567.44 1646.28 0.000056
HEAT PUMP COOLING MODE AIRLOOP M SW 0.348419 4168.83 2678.54 0.000091
HEAT PUMP COOLING MODE AIRLOOP M NW 0.331030 3948.84 2540.42 0.000086
HEAT PUMP COOLING MODE AIRLOOP M SE 0.293661 3553.90 2284.05 0.000078
HEAT PUMP COOLING MODE AIRLOOP M NE 0.245349 2847.97 1868.44 0.000062
HEAT PUMP COOLING MODE AIRLOOP M N1 0.181513 2134.20 1393.11 0.000047
HEAT PUMP COOLING MODE AIRLOOP M N2 0.179708 2112.21 1379.40 0.000046
HEAT PUMP COOLING MODE AIRLOOP M S1 0.211558 2599.54 1668.30 0.000057
HEAT PUMP COOLING MODE AIRLOOP M S2 0.212586 2611.99 1676.11 0.000057
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.344594 4116.59 2648.57 0.000090
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.327097 3895.27 2509.63 0.000085
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.289950 3503.35 2254.97 0.000077
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.240975 2789.52 1834.40 0.000061
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.177857 2086.16 1364.78 0.000046
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.176059 2064.26 1351.12 0.000045
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.207915 2552.10 1640.06 0.000056
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.208935 2564.46 1647.82 0.000056
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.343548 4098.70 2639.78 0.000090
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.326070 3877.62 2500.99 0.000085
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.288991 3486.73 2246.87 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.239504 2766.74 1822.45 0.000060
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.176946 2072.01 1357.36 0.000045
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.175151 2050.17 1343.73 0.000045
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.206962 2537.60 1632.34 0.000055
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.207978 2549.90 1640.06 0.000056
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.344086 4100.51 2643.09 0.000090
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.326641 3879.85 2504.55 0.000085
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.289492 3488.27 2249.94 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.239560 2762.89 1822.14 0.000060
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.177630 2077.63 1362.12 0.000045
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.175841 2055.87 1348.54 0.000045
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.207484 2541.24 1635.87 0.000056
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.208499 2553.52 1643.58 0.000056
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.356089 4241.33 2733.36 0.000093
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.338404 4017.93 2593.03 0.000088
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.297451 3580.15 2309.60 0.000078
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.242791 2797.59 1845.92 0.000061
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.187895 2200.14 1439.66 0.000048
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.186074 2177.99 1425.84 0.000048
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.214334 2621.46 1687.47 0.000057
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.215473 2635.24 1696.12 0.000058
HEAT PUMP COOLING MODE AIRLOOP T SW 0.442383 5319.86 3404.52 0.000116
HEAT PUMP COOLING MODE AIRLOOP T NW 0.413882 4949.54 3177.19 0.000108
HEAT PUMP COOLING MODE AIRLOOP T SE 0.386035 4646.23 2980.52 0.000101
HEAT PUMP COOLING MODE AIRLOOP T NE 0.308506 3614.97 2354.71 0.000079
HEAT PUMP COOLING MODE AIRLOOP T N1 0.241054 2946.98 1891.87 0.000064
HEAT PUMP COOLING MODE AIRLOOP T N2 0.240585 2941.37 1888.32 0.000064
HEAT PUMP COOLING MODE AIRLOOP T S1 0.314364 3828.40 2446.20 0.000084
HEAT PUMP COOLING MODE AIRLOOP T S2 0.315251 3839.15 2452.93 0.000084


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.259745 0.259745 0.259745 0.259745 3140.46 3140.46 3345.45 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.248195 0.248195 0.248195 0.248195 2982.23 2982.23 3358.06 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.337712 0.337712 0.337712 0.337712 4135.24 4135.24 4259.61 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.174305 0.174305 0.174305 0.174305 2027.42 2027.42 3358.06 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.125100 0.125100 0.125100 0.125100 1470.94 1470.94 2544.99 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.122965 0.122965 0.122965 0.122965 1444.78 1444.78 2544.99 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.147636 0.147636 0.147636 0.147636 1851.76 1851.76 2529.27 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.153872 0.153872 0.153872 0.153872 1922.53 1922.53 2537.77 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.340348 0.340348 0.340348 0.340348 4095.57 4095.57 3258.26 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.321846 0.321846 0.321846 0.321846 3864.28 3864.28 3264.59 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.306068 0.306068 0.306068 0.306068 3729.89 3729.89 3283.15 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.237162 0.237162 0.237162 0.237162 2775.38 2775.38 3264.59 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.171224 0.171224 0.171224 0.171224 2024.27 2024.27 2279.84 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.169420 0.169420 0.169420 0.169420 2002.26 2002.26 2279.84 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.200856 0.200856 0.200856 0.200856 2485.33 2485.33 2276.35 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.203294 0.203294 0.203294 0.203294 2514.85 2514.85 2277.92 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.342722 0.342722 0.342722 0.342722 4115.38 4115.38 3233.47 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.325158 0.325158 0.325158 0.325158 3893.13 3893.13 3239.68 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.289971 0.289971 0.289971 0.289971 3524.24 3524.24 3236.09 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.240992 0.240992 0.240992 0.240992 2810.50 2810.50 3239.68 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.175688 0.175688 0.175688 0.175688 2072.15 2072.15 2226.90 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.173889 0.173889 0.173889 0.173889 2050.22 2050.22 2226.90 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.205644 0.205644 0.205644 0.205644 2536.83 2536.83 2221.50 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.206879 0.206879 0.206879 0.206879 2551.79 2551.79 2221.74 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.344373 0.344373 0.344373 0.344373 4126.84 4126.84 3266.39 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.326873 0.326873 0.326873 0.326873 3905.42 3905.42 3271.61 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.289812 0.289812 0.289812 0.289812 3514.11 3514.11 3266.65 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.241915 0.241915 0.241915 0.241915 2813.34 2813.34 3271.61 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.177492 0.177492 0.177492 0.177492 2089.20 2089.20 2234.94 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.175689 0.175689 0.175689 0.175689 2067.24 2067.24 2234.94 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.207515 0.207515 0.207515 0.207515 2554.62 2554.62 2230.30 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.208574 0.208574 0.208574 0.208574 2567.44 2567.44 2230.34 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.348419 0.348419 0.348419 0.348419 4168.83 4168.83 3277.12 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.331030 0.331030 0.331030 0.331030 3948.84 3948.84 3279.93 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.293661 0.293661 0.293661 0.293661 3553.90 3553.90 3277.14 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.245349 0.245349 0.245349 0.245349 2847.97 2847.97 3279.93 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.181513 0.181513 0.181513 0.181513 2134.20 2134.20 2226.52 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.179708 0.179708 0.179708 0.179708 2112.21 2112.21 2226.52 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.211558 0.211558 0.211558 0.211558 2599.54 2599.54 2224.31 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.212586 0.212586 0.212586 0.212586 2611.99 2611.99 2224.32 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.344594 0.344594 0.344594 0.344594 4116.59 4116.59 3358.10 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.327097 0.327097 0.327097 0.327097 3895.27 3895.27 3360.54 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.289950 0.289950 0.289950 0.289950 3503.35 3503.35 3358.10 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.240975 0.240975 0.240975 0.240975 2789.52 2789.52 3360.54 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.177857 0.177857 0.177857 0.177857 2086.16 2086.16 2287.91 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.176059 0.176059 0.176059 0.176059 2064.26 2064.26 2287.91 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.207915 0.207915 0.207915 0.207915 2552.10 2552.10 2286.00 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.208935 0.208935 0.208935 0.208935 2564.46 2564.46 2286.00 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.343548 0.343548 0.343548 0.343548 4098.70 4098.70 3409.62 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.326070 0.326070 0.326070 0.326070 3877.62 3877.62 3410.59 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.288991 0.288991 0.288991 0.288991 3486.73 3486.73 3409.62 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.239504 0.239504 0.239504 0.239504 2766.74 2766.74 3410.59 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.176946 0.176946 0.176946 0.176946 2072.01 2072.01 2323.83 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.175151 0.175151 0.175151 0.175151 2050.17 2050.17 2323.83 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.206962 0.206962 0.206962 0.206962 2537.60 2537.60 2323.37 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.207978 0.207978 0.207978 0.207978 2549.90 2549.90 2323.37 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.344086 0.344086 0.344086 0.344086 4100.51 4100.51 3468.20 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.326641 0.326641 0.326641 0.326641 3879.85 3879.85 3467.56 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.289492 0.289492 0.289492 0.289492 3488.27 3488.27 3468.20 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.239560 0.239560 0.239560 0.239560 2762.89 2762.89 3467.56 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.177630 0.177630 0.177630 0.177630 2077.63 2077.63 2368.50 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.175841 0.175841 0.175841 0.175841 2055.87 2055.87 2368.50 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.207484 0.207484 0.207484 0.207484 2541.24 2541.24 2369.67 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.208499 0.208499 0.208499 0.208499 2553.52 2553.52 2369.67 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.356089 0.356089 0.356089 0.356089 4241.33 4241.33 3681.49 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.338404 0.338404 0.338404 0.338404 4017.93 4017.93 3676.26 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.297451 0.297451 0.297451 0.297451 3580.15 3580.15 3681.49 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.242791 0.242791 0.242791 0.242791 2797.59 2797.59 3676.26 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.187895 0.187895 0.187895 0.187895 2200.14 2200.14 2556.02 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.186074 0.186074 0.186074 0.186074 2177.99 2177.99 2556.02 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.214334 0.214334 0.214334 0.214334 2621.46 2621.46 2561.36 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.215473 0.215473 0.215473 0.215473 2635.24 2635.24 2561.36 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.442383 0.442383 0.442383 0.442383 5319.86 5319.86 4489.34 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.413882 0.413882 0.413882 0.413882 4949.54 4949.54 4491.71 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.386035 0.386035 0.386035 0.386035 4646.23 4646.23 4489.34 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.308506 0.308506 0.308506 0.308506 3614.97 3614.97 4491.71 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.241054 0.241054 0.241054 0.241054 2946.98 2946.98 3428.98 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.240585 0.240585 0.240585 0.240585 2941.37 2941.37 3428.98 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.314364 0.314364 0.314364 0.314364 3828.40 3828.40 3423.89 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.315251 0.315251 0.315251 0.315251 3839.15 3839.15 3423.89 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.259745
AIRLOOP G NW SUPPLY FAN 0.248195
AIRLOOP OFFICE SUPPLY FAN 0.337712
AIRLOOP G NE SUPPLY FAN 0.174305
AIRLOOP G N1 SUPPLY FAN 0.125100
AIRLOOP G N2 SUPPLY FAN 0.122965
AIRLOOP G S1 SUPPLY FAN 0.147636
AIRLOOP G S2 SUPPLY FAN 0.153872
AIRLOOP F2 SW SUPPLY FAN 0.340348
AIRLOOP F2 NW SUPPLY FAN 0.321846
AIRLOOP F2 SE SUPPLY FAN 0.306068
AIRLOOP F2 NE SUPPLY FAN 0.237162
AIRLOOP F2 N1 SUPPLY FAN 0.171224
AIRLOOP F2 N2 SUPPLY FAN 0.169420
AIRLOOP F2 S1 SUPPLY FAN 0.200856
AIRLOOP F2 S2 SUPPLY FAN 0.203294
AIRLOOP F3 SW SUPPLY FAN 0.342722
AIRLOOP F3 NW SUPPLY FAN 0.325158
AIRLOOP F3 SE SUPPLY FAN 0.289971
AIRLOOP F3 NE SUPPLY FAN 0.240992
AIRLOOP F3 N1 SUPPLY FAN 0.175688
AIRLOOP F3 N2 SUPPLY FAN 0.173889
AIRLOOP F3 S1 SUPPLY FAN 0.205644
AIRLOOP F3 S2 SUPPLY FAN 0.206879
AIRLOOP F4 SW SUPPLY FAN 0.344373
AIRLOOP F4 NW SUPPLY FAN 0.326873
AIRLOOP F4 SE SUPPLY FAN 0.289812
AIRLOOP F4 NE SUPPLY FAN 0.241915
AIRLOOP F4 N1 SUPPLY FAN 0.177492
AIRLOOP F4 N2 SUPPLY FAN 0.175689
AIRLOOP F4 S1 SUPPLY FAN 0.207515
AIRLOOP F4 S2 SUPPLY FAN 0.208574
AIRLOOP M SW SUPPLY FAN 0.348419
AIRLOOP M NW SUPPLY FAN 0.331030
AIRLOOP M SE SUPPLY FAN 0.293661
AIRLOOP M NE SUPPLY FAN 0.245349
AIRLOOP M N1 SUPPLY FAN 0.181513
AIRLOOP M N2 SUPPLY FAN 0.179708
AIRLOOP M S1 SUPPLY FAN 0.211558
AIRLOOP M S2 SUPPLY FAN 0.212586
AIRLOOP F6 SW SUPPLY FAN 0.344594
AIRLOOP F6 NW SUPPLY FAN 0.327097
AIRLOOP F6 SE SUPPLY FAN 0.289950
AIRLOOP F6 NE SUPPLY FAN 0.240975
AIRLOOP F6 N1 SUPPLY FAN 0.177857
AIRLOOP F6 N2 SUPPLY FAN 0.176059
AIRLOOP F6 S1 SUPPLY FAN 0.207915
AIRLOOP F6 S2 SUPPLY FAN 0.208935
AIRLOOP F7 SW SUPPLY FAN 0.343548
AIRLOOP F7 NW SUPPLY FAN 0.326070
AIRLOOP F7 SE SUPPLY FAN 0.288991
AIRLOOP F7 NE SUPPLY FAN 0.239504
AIRLOOP F7 N1 SUPPLY FAN 0.176946
AIRLOOP F7 N2 SUPPLY FAN 0.175151
AIRLOOP F7 S1 SUPPLY FAN 0.206962
AIRLOOP F7 S2 SUPPLY FAN 0.207978
AIRLOOP F8 SW SUPPLY FAN 0.344086
AIRLOOP F8 NW SUPPLY FAN 0.326641
AIRLOOP F8 SE SUPPLY FAN 0.289492
AIRLOOP F8 NE SUPPLY FAN 0.239560
AIRLOOP F8 N1 SUPPLY FAN 0.177630
AIRLOOP F8 N2 SUPPLY FAN 0.175841
AIRLOOP F8 S1 SUPPLY FAN 0.207484
AIRLOOP F8 S2 SUPPLY FAN 0.208499
AIRLOOP F9 SW SUPPLY FAN 0.356089
AIRLOOP F9 NW SUPPLY FAN 0.338404
AIRLOOP F9 SE SUPPLY FAN 0.297451
AIRLOOP F9 NE SUPPLY FAN 0.242791
AIRLOOP F9 N1 SUPPLY FAN 0.187895
AIRLOOP F9 N2 SUPPLY FAN 0.186074
AIRLOOP F9 S1 SUPPLY FAN 0.214334
AIRLOOP F9 S2 SUPPLY FAN 0.215473
AIRLOOP T SW SUPPLY FAN 0.442383
AIRLOOP T NW SUPPLY FAN 0.413882
AIRLOOP T SE SUPPLY FAN 0.386035
AIRLOOP T NE SUPPLY FAN 0.308506
AIRLOOP T N1 SUPPLY FAN 0.241054
AIRLOOP T N2 SUPPLY FAN 0.240585
AIRLOOP T S1 SUPPLY FAN 0.314364
AIRLOOP T S2 SUPPLY FAN 0.315251


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.259745 3140.46 0.000069
HEAT PUMP HEATING MODE AIRLOOP G NW 0.248195 2982.23 0.000065
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.337712 4135.24 0.000090
HEAT PUMP HEATING MODE AIRLOOP G NE 0.174305 2027.42 0.000044
HEAT PUMP HEATING MODE AIRLOOP G N1 0.125100 1470.94 0.000032
HEAT PUMP HEATING MODE AIRLOOP G N2 0.122965 1444.78 0.000032
HEAT PUMP HEATING MODE AIRLOOP G S1 0.147636 1851.76 0.000040
HEAT PUMP HEATING MODE AIRLOOP G S2 0.153872 1922.53 0.000042
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.340348 4095.57 0.000089
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.321846 3864.28 0.000084
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.306068 3729.89 0.000081
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.237162 2775.38 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.171224 2024.27 0.000044
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.169420 2002.26 0.000044
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.200856 2485.33 0.000054
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.203294 2514.85 0.000055
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.342722 4115.38 0.000090
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.325158 3893.13 0.000085
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.289971 3524.24 0.000077
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.240992 2810.50 0.000061
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.175688 2072.15 0.000045
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.173889 2050.22 0.000045
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.205644 2536.83 0.000055
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.206879 2551.79 0.000056
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.344373 4126.84 0.000090
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.326873 3905.42 0.000085
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.289812 3514.11 0.000077
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.241915 2813.34 0.000061
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.177492 2089.20 0.000046
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.175689 2067.24 0.000045
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.207515 2554.62 0.000056
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.208574 2567.44 0.000056
HEAT PUMP HEATING MODE AIRLOOP M SW 0.348419 4168.83 0.000091
HEAT PUMP HEATING MODE AIRLOOP M NW 0.331030 3948.84 0.000086
HEAT PUMP HEATING MODE AIRLOOP M SE 0.293661 3553.90 0.000078
HEAT PUMP HEATING MODE AIRLOOP M NE 0.245349 2847.97 0.000062
HEAT PUMP HEATING MODE AIRLOOP M N1 0.181513 2134.20 0.000047
HEAT PUMP HEATING MODE AIRLOOP M N2 0.179708 2112.21 0.000046
HEAT PUMP HEATING MODE AIRLOOP M S1 0.211558 2599.54 0.000057
HEAT PUMP HEATING MODE AIRLOOP M S2 0.212586 2611.99 0.000057
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.344594 4116.59 0.000090
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.327097 3895.27 0.000085
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.289950 3503.35 0.000077
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.240975 2789.52 0.000061
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.177857 2086.16 0.000046
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.176059 2064.26 0.000045
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.207915 2552.10 0.000056
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.208935 2564.46 0.000056
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.343548 4098.70 0.000090
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.326070 3877.62 0.000085
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.288991 3486.73 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.239504 2766.74 0.000060
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.176946 2072.01 0.000045
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.175151 2050.17 0.000045
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.206962 2537.60 0.000055
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.207978 2549.90 0.000056
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.344086 4100.51 0.000090
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.326641 3879.85 0.000085
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.289492 3488.27 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.239560 2762.89 0.000060
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.177630 2077.63 0.000045
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.175841 2055.87 0.000045
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.207484 2541.24 0.000056
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.208499 2553.52 0.000056
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.356089 4241.33 0.000093
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.338404 4017.93 0.000088
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.297451 3580.15 0.000078
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.242791 2797.59 0.000061
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.187895 2200.14 0.000048
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.186074 2177.99 0.000048
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.214334 2621.46 0.000057
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.215473 2635.24 0.000058
HEAT PUMP HEATING MODE AIRLOOP T SW 0.442383 5319.86 0.000116
HEAT PUMP HEATING MODE AIRLOOP T NW 0.413882 4949.54 0.000108
HEAT PUMP HEATING MODE AIRLOOP T SE 0.386035 4646.23 0.000101
HEAT PUMP HEATING MODE AIRLOOP T NE 0.308506 3614.97 0.000079
HEAT PUMP HEATING MODE AIRLOOP T N1 0.241054 2946.98 0.000064
HEAT PUMP HEATING MODE AIRLOOP T N2 0.240585 2941.37 0.000064
HEAT PUMP HEATING MODE AIRLOOP T S1 0.314364 3828.40 0.000084
HEAT PUMP HEATING MODE AIRLOOP T S2 0.315251 3839.15 0.000084


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 3345.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 3358.06
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 4259.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 3358.06
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 2544.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 2544.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 2529.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 2537.77
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 3258.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 3264.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 3283.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 3264.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 2279.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 2279.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 2276.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 2277.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 3233.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 3239.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 3236.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 3239.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 2226.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 2226.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 2221.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 2221.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 3266.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 3271.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 3266.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 3271.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 2234.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 2234.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 2230.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 2230.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 3277.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 3279.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 3277.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 3279.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 2226.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 2226.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 2224.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 2224.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 3358.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 3360.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 3358.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 3360.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 2287.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 2287.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 2286.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 2286.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 3409.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 3410.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 3409.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 3410.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 2323.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 2323.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 2323.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 2323.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 3468.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 3467.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 3468.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 3467.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 2368.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 2368.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 2369.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 2369.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 3681.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 3676.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 3681.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 3676.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 2556.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 2556.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 2561.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 2561.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 4489.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 4491.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 4489.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 4491.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 3428.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 3428.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 3423.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 3423.89


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.005253 5.91


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.005253


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.005253 2535.80 8.22 6379.03


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.005253 1339.76



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:15

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.60 0.85
February 22.51 -0.2
March 22.67 4.82
April 22.49 6.08
May 23.48 13.74
June 24.33 22.16
July 24.34 22.71
August 24.35 21.74
September 24.25 18.54
October 23.13 7.12
November 22.77 3.03
December 22.32 -1.0
     
Annual Sum or Average 23.27 10.02
Minimum of Months 22.32 -1.0
Maximum of Months 24.35 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 0.85
February 21.80 -0.2
March 22.15 4.82
April 22.17 6.08
May 23.36 13.74
June 24.34 22.16
July 24.35 22.71
August 24.32 21.74
September 24.14 18.54
October 22.53 7.12
November 21.95 3.03
December 21.77 -1.0
     
Annual Sum or Average 22.90 10.02
Minimum of Months 21.77 -1.0
Maximum of Months 24.35 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 0.85
February 22.49 -0.2
March 22.72 4.82
April 22.62 6.08
May 23.56 13.74
June 24.39 22.16
July 24.39 22.71
August 24.42 21.74
September 24.28 18.54
October 23.03 7.12
November 22.65 3.03
December 22.35 -1.0
     
Annual Sum or Average 23.29 10.02
Minimum of Months 22.35 -1.0
Maximum of Months 24.42 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 0.85
February 21.77 -0.2
March 22.09 4.82
April 22.13 6.08
May 23.25 13.74
June 24.36 22.16
July 24.38 22.71
August 24.34 21.74
September 24.12 18.54
October 22.40 7.12
November 21.88 3.03
December 21.74 -1.0
     
Annual Sum or Average 22.86 10.02
Minimum of Months 21.74 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 0.85
February 21.73 -0.2
March 21.94 4.82
April 21.95 6.08
May 23.06 13.74
June 24.31 22.16
July 24.33 22.71
August 24.29 21.74
September 24.08 18.54
October 22.28 7.12
November 21.83 3.03
December 21.73 -1.0
     
Annual Sum or Average 22.78 10.02
Minimum of Months 21.73 -1.0
Maximum of Months 24.33 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 0.85
February 21.73 -0.2
March 21.94 4.82
April 21.95 6.08
May 23.05 13.74
June 24.31 22.16
July 24.34 22.71
August 24.29 21.74
September 24.08 18.54
October 22.27 7.12
November 21.82 3.03
December 21.73 -1.0
     
Annual Sum or Average 22.78 10.02
Minimum of Months 21.73 -1.0
Maximum of Months 24.34 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 0.85
February 22.57 -0.2
March 22.65 4.82
April 22.40 6.08
May 23.32 13.74
June 24.30 22.16
July 24.33 22.71
August 24.36 21.74
September 24.31 18.54
October 23.20 7.12
November 22.85 3.03
December 22.40 -1.0
     
Annual Sum or Average 23.28 10.02
Minimum of Months 22.40 -1.0
Maximum of Months 24.36 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.71 0.85
February 22.58 -0.2
March 22.67 4.82
April 22.43 6.08
May 23.36 13.74
June 24.30 22.16
July 24.33 22.71
August 24.36 21.74
September 24.31 18.54
October 23.21 7.12
November 22.87 3.03
December 22.42 -1.0
     
Annual Sum or Average 23.30 10.02
Minimum of Months 22.42 -1.0
Maximum of Months 24.36 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.33 0.85
February 18.01 -0.2
March 19.29 4.82
April 19.55 6.08
May 22.11 13.74
June 25.42 22.16
July 25.59 22.71
August 25.31 21.74
September 24.49 18.54
October 20.38 7.12
November 18.95 3.03
December 17.67 -1.0
     
Annual Sum or Average 21.28 10.02
Minimum of Months 17.67 -1.0
Maximum of Months 25.59 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.27 0.85
February 23.03 -0.2
March 23.11 4.82
April 23.05 6.08
May 24.13 13.74
June 24.38 22.16
July 24.38 22.71
August 24.39 21.74
September 24.34 18.54
October 23.64 7.12
November 23.35 3.03
December 22.72 -1.0
     
Annual Sum or Average 23.65 10.02
Minimum of Months 22.72 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 0.85
February 21.97 -0.2
March 22.54 4.82
April 22.62 6.08
May 24.04 13.74
June 24.39 22.16
July 24.38 22.71
August 24.37 21.74
September 24.25 18.54
October 23.08 7.12
November 22.26 3.03
December 21.84 -1.0
     
Annual Sum or Average 23.15 10.02
Minimum of Months 21.84 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.25 0.85
February 23.04 -0.2
March 23.16 4.82
April 23.11 6.08
May 24.15 13.74
June 24.39 22.16
July 24.39 22.71
August 24.40 21.74
September 24.36 18.54
October 23.63 7.12
November 23.33 3.03
December 22.73 -1.0
     
Annual Sum or Average 23.67 10.02
Minimum of Months 22.73 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 0.85
February 21.92 -0.2
March 22.44 4.82
April 22.55 6.08
May 23.97 13.74
June 24.42 22.16
July 24.42 22.71
August 24.38 21.74
September 24.25 18.54
October 22.93 7.12
November 22.12 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.10 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.42 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 0.85
February 21.85 -0.2
March 22.33 4.82
April 22.42 6.08
May 23.93 13.74
June 24.39 22.16
July 24.38 22.71
August 24.35 21.74
September 24.23 18.54
October 22.93 7.12
November 22.11 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.06 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 0.85
February 21.85 -0.2
March 22.32 4.82
April 22.41 6.08
May 23.93 13.74
June 24.39 22.16
July 24.39 22.71
August 24.35 21.74
September 24.23 18.54
October 22.91 7.12
November 22.10 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.05 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 0.85
February 23.20 -0.2
March 23.20 4.82
April 23.08 6.08
May 24.10 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.76 7.12
November 23.54 3.03
December 22.96 -1.0
     
Annual Sum or Average 23.74 10.02
Minimum of Months 22.96 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 0.85
February 23.21 -0.2
March 23.21 4.82
April 23.10 6.08
May 24.11 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.76 7.12
November 23.54 3.03
December 22.97 -1.0
     
Annual Sum or Average 23.75 10.02
Minimum of Months 22.97 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 0.85
February 22.85 -0.2
March 23.39 4.82
April 23.46 6.08
May 25.23 13.74
June 26.51 22.16
July 26.53 22.71
August 26.46 21.74
September 26.14 18.54
October 24.24 7.12
November 23.36 3.03
December 22.48 -1.0
     
Annual Sum or Average 24.49 10.02
Minimum of Months 22.48 -1.0
Maximum of Months 26.53 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.42 0.85
February 23.12 -0.2
March 23.17 4.82
April 23.14 6.08
May 24.19 13.74
June 24.39 22.16
July 24.38 22.71
August 24.39 21.74
September 24.35 18.54
October 23.71 7.12
November 23.46 3.03
December 22.78 -1.0
     
Annual Sum or Average 23.71 10.02
Minimum of Months 22.78 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.09 0.85
February 22.02 -0.2
March 22.61 4.82
April 22.72 6.08
May 24.11 13.74
June 24.39 22.16
July 24.38 22.71
August 24.37 21.74
September 24.26 18.54
October 23.21 7.12
November 22.35 3.03
December 21.86 -1.0
     
Annual Sum or Average 23.21 10.02
Minimum of Months 21.86 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.35 0.85
February 23.08 -0.2
March 23.17 4.82
April 23.13 6.08
May 24.18 13.74
June 24.39 22.16
July 24.39 22.71
August 24.40 21.74
September 24.37 18.54
October 23.67 7.12
November 23.40 3.03
December 22.75 -1.0
     
Annual Sum or Average 23.69 10.02
Minimum of Months 22.75 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 0.85
February 21.97 -0.2
March 22.52 4.82
April 22.64 6.08
May 24.07 13.74
June 24.43 22.16
July 24.42 22.71
August 24.38 21.74
September 24.25 18.54
October 23.07 7.12
November 22.21 3.03
December 21.80 -1.0
     
Annual Sum or Average 23.15 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.43 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 0.85
February 21.92 -0.2
March 22.44 4.82
April 22.58 6.08
May 24.07 13.74
June 24.40 22.16
July 24.39 22.71
August 24.35 21.74
September 24.24 18.54
October 23.15 7.12
November 22.24 3.03
December 21.82 -1.0
     
Annual Sum or Average 23.14 10.02
Minimum of Months 21.82 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 0.85
February 21.92 -0.2
March 22.43 4.82
April 22.57 6.08
May 24.06 13.74
June 24.40 22.16
July 24.39 22.71
August 24.35 21.74
September 24.24 18.54
October 23.13 7.12
November 22.23 3.03
December 21.82 -1.0
     
Annual Sum or Average 23.13 10.02
Minimum of Months 21.82 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.70 0.85
February 23.33 -0.2
March 23.31 4.82
April 23.25 6.08
May 24.20 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.85 7.12
November 23.68 3.03
December 23.10 -1.0
     
Annual Sum or Average 23.83 10.02
Minimum of Months 23.10 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.70 0.85
February 23.33 -0.2
March 23.31 4.82
April 23.25 6.08
May 24.20 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.85 7.12
November 23.68 3.03
December 23.10 -1.0
     
Annual Sum or Average 23.83 10.02
Minimum of Months 23.10 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 0.85
February 23.37 -0.2
March 23.87 4.82
April 23.94 6.08
May 25.70 13.74
June 26.66 22.16
July 26.65 22.71
August 26.59 21.74
September 26.31 18.54
October 24.72 7.12
November 23.88 3.03
December 22.96 -1.0
     
Annual Sum or Average 24.87 10.02
Minimum of Months 22.96 -1.0
Maximum of Months 26.66 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.44 0.85
February 23.11 -0.2
March 23.16 4.82
April 23.13 6.08
May 24.19 13.74
June 24.38 22.16
July 24.38 22.71
August 24.39 21.74
September 24.34 18.54
October 23.71 7.12
November 23.47 3.03
December 22.77 -1.0
     
Annual Sum or Average 23.71 10.02
Minimum of Months 22.77 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.11 0.85
February 22.03 -0.2
March 22.61 4.82
April 22.72 6.08
May 24.12 13.74
June 24.39 22.16
July 24.38 22.71
August 24.37 21.74
September 24.25 18.54
October 23.23 7.12
November 22.38 3.03
December 21.86 -1.0
     
Annual Sum or Average 23.21 10.02
Minimum of Months 21.86 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.37 0.85
February 23.07 -0.2
March 23.16 4.82
April 23.11 6.08
May 24.17 13.74
June 24.39 22.16
July 24.39 22.71
August 24.40 21.74
September 24.37 18.54
October 23.67 7.12
November 23.40 3.03
December 22.73 -1.0
     
Annual Sum or Average 23.69 10.02
Minimum of Months 22.73 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.97 0.85
February 21.97 -0.2
March 22.52 4.82
April 22.64 6.08
May 24.07 13.74
June 24.43 22.16
July 24.42 22.71
August 24.38 21.74
September 24.24 18.54
October 23.09 7.12
November 22.23 3.03
December 21.80 -1.0
     
Annual Sum or Average 23.15 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.43 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 0.85
February 21.94 -0.2
March 22.47 4.82
April 22.61 6.08
May 24.09 13.74
June 24.39 22.16
July 24.38 22.71
August 24.35 21.74
September 24.24 18.54
October 23.20 7.12
November 22.29 3.03
December 21.83 -1.0
     
Annual Sum or Average 23.16 10.02
Minimum of Months 21.83 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 0.85
February 21.94 -0.2
March 22.46 4.82
April 22.60 6.08
May 24.08 13.74
June 24.40 22.16
July 24.39 22.71
August 24.35 21.74
September 24.24 18.54
October 23.19 7.12
November 22.27 3.03
December 21.82 -1.0
     
Annual Sum or Average 23.15 10.02
Minimum of Months 21.82 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 0.85
February 23.34 -0.2
March 23.32 4.82
April 23.27 6.08
May 24.21 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.86 7.12
November 23.71 3.03
December 23.11 -1.0
     
Annual Sum or Average 23.85 10.02
Minimum of Months 23.11 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 0.85
February 23.34 -0.2
March 23.32 4.82
April 23.27 6.08
May 24.22 13.74
June 24.37 22.16
July 24.37 22.71
August 24.40 21.74
September 24.41 18.54
October 23.86 7.12
November 23.71 3.03
December 23.11 -1.0
     
Annual Sum or Average 23.85 10.02
Minimum of Months 23.11 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.91 0.85
February 23.53 -0.2
March 24.03 4.82
April 24.10 6.08
May 25.87 13.74
June 26.76 22.16
July 26.74 22.71
August 26.69 21.74
September 26.40 18.54
October 24.89 7.12
November 24.06 3.03
December 23.11 -1.0
     
Annual Sum or Average 25.02 10.02
Minimum of Months 23.11 -1.0
Maximum of Months 26.76 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.46 0.85
February 23.11 -0.2
March 23.15 4.82
April 23.12 6.08
May 24.19 13.74
June 24.38 22.16
July 24.38 22.71
August 24.38 21.74
September 24.34 18.54
October 23.71 7.12
November 23.47 3.03
December 22.76 -1.0
     
Annual Sum or Average 23.71 10.02
Minimum of Months 22.76 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.13 0.85
February 22.03 -0.2
March 22.61 4.82
April 22.71 6.08
May 24.12 13.74
June 24.39 22.16
July 24.38 22.71
August 24.37 21.74
September 24.25 18.54
October 23.24 7.12
November 22.40 3.03
December 21.86 -1.0
     
Annual Sum or Average 23.21 10.02
Minimum of Months 21.86 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.38 0.85
February 23.06 -0.2
March 23.15 4.82
April 23.09 6.08
May 24.17 13.74
June 24.39 22.16
July 24.39 22.71
August 24.40 21.74
September 24.36 18.54
October 23.67 7.12
November 23.41 3.03
December 22.72 -1.0
     
Annual Sum or Average 23.69 10.02
Minimum of Months 22.72 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 0.85
February 21.97 -0.2
March 22.52 4.82
April 22.63 6.08
May 24.07 13.74
June 24.44 22.16
July 24.43 22.71
August 24.38 21.74
September 24.24 18.54
October 23.10 7.12
November 22.24 3.03
December 21.80 -1.0
     
Annual Sum or Average 23.16 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.44 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.08 0.85
February 21.95 -0.2
March 22.48 4.82
April 22.62 6.08
May 24.09 13.74
June 24.40 22.16
July 24.39 22.71
August 24.35 21.74
September 24.24 18.54
October 23.23 7.12
November 22.32 3.03
December 21.83 -1.0
     
Annual Sum or Average 23.17 10.02
Minimum of Months 21.83 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.06 0.85
February 21.95 -0.2
March 22.47 4.82
April 22.61 6.08
May 24.09 13.74
June 24.40 22.16
July 24.39 22.71
August 24.35 21.74
September 24.24 18.54
October 23.22 7.12
November 22.31 3.03
December 21.83 -1.0
     
Annual Sum or Average 23.17 10.02
Minimum of Months 21.83 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.77 0.85
February 23.35 -0.2
March 23.32 4.82
April 23.27 6.08
May 24.22 13.74
June 24.37 22.16
July 24.37 22.71
August 24.39 21.74
September 24.41 18.54
October 23.87 7.12
November 23.72 3.03
December 23.11 -1.0
     
Annual Sum or Average 23.85 10.02
Minimum of Months 23.11 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 0.85
February 23.34 -0.2
March 23.32 4.82
April 23.27 6.08
May 24.22 13.74
June 24.37 22.16
July 24.37 22.71
August 24.39 21.74
September 24.41 18.54
October 23.87 7.12
November 23.72 3.03
December 23.11 -1.0
     
Annual Sum or Average 23.85 10.02
Minimum of Months 23.11 -1.0
Maximum of Months 24.41 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.57 0.85
February 24.16 -0.2
March 24.66 4.82
April 24.72 6.08
May 26.48 13.74
June 27.35 22.16
July 27.34 22.71
August 27.29 21.74
September 27.00 18.54
October 25.53 7.12
November 24.71 3.03
December 23.73 -1.0
     
Annual Sum or Average 25.64 10.02
Minimum of Months 23.73 -1.0
Maximum of Months 27.35 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 0.85
February 23.05 -0.2
March 23.09 4.82
April 23.03 6.08
May 24.15 13.74
June 24.38 22.16
July 24.38 22.71
August 24.38 21.74
September 24.33 18.54
October 23.67 7.12
November 23.42 3.03
December 22.70 -1.0
     
Annual Sum or Average 23.67 10.02
Minimum of Months 22.70 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.08 0.85
February 21.98 -0.2
March 22.56 4.82
April 22.61 6.08
May 24.07 13.74
June 24.39 22.16
July 24.38 22.71
August 24.36 21.74
September 24.22 18.54
October 23.16 7.12
November 22.34 3.03
December 21.84 -1.0
     
Annual Sum or Average 23.17 10.02
Minimum of Months 21.84 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 0.85
February 23.00 -0.2
March 23.09 4.82
April 23.01 6.08
May 24.13 13.74
June 24.39 22.16
July 24.39 22.71
August 24.40 21.74
September 24.35 18.54
October 23.63 7.12
November 23.35 3.03
December 22.65 -1.0
     
Annual Sum or Average 23.65 10.02
Minimum of Months 22.65 -1.0
Maximum of Months 24.40 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 0.85
February 21.93 -0.2
March 22.46 4.82
April 22.54 6.08
May 24.02 13.74
June 24.44 22.16
July 24.43 22.71
August 24.37 21.74
September 24.21 18.54
October 23.01 7.12
November 22.19 3.03
December 21.78 -1.0
     
Annual Sum or Average 23.12 10.02
Minimum of Months 21.78 -1.0
Maximum of Months 24.44 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 0.85
February 21.91 -0.2
March 22.43 4.82
April 22.52 6.08
May 24.04 13.74
June 24.39 22.16
July 24.38 22.71
August 24.34 21.74
September 24.21 18.54
October 23.15 7.12
November 22.26 3.03
December 21.81 -1.0
     
Annual Sum or Average 23.13 10.02
Minimum of Months 21.81 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 0.85
February 21.91 -0.2
March 22.42 4.82
April 22.51 6.08
May 24.04 13.74
June 24.39 22.16
July 24.38 22.71
August 24.34 21.74
September 24.21 18.54
October 23.13 7.12
November 22.25 3.03
December 21.81 -1.0
     
Annual Sum or Average 23.12 10.02
Minimum of Months 21.81 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 0.85
February 23.30 -0.2
March 23.26 4.82
April 23.18 6.08
May 24.17 13.74
June 24.36 22.16
July 24.37 22.71
August 24.39 21.74
September 24.39 18.54
October 23.83 7.12
November 23.68 3.03
December 23.04 -1.0
     
Annual Sum or Average 23.81 10.02
Minimum of Months 23.04 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 0.85
February 23.30 -0.2
March 23.26 4.82
April 23.18 6.08
May 24.17 13.74
June 24.36 22.16
July 24.37 22.71
August 24.39 21.74
September 24.39 18.54
October 23.83 7.12
November 23.67 3.03
December 23.03 -1.0
     
Annual Sum or Average 23.81 10.02
Minimum of Months 23.03 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 0.85
February 23.47 -0.2
March 23.96 4.82
April 24.00 6.08
May 25.82 13.74
June 26.74 22.16
July 26.73 22.71
August 26.67 21.74
September 26.37 18.54
October 24.84 7.12
November 24.02 3.03
December 23.04 -1.0
     
Annual Sum or Average 24.97 10.02
Minimum of Months 23.04 -1.0
Maximum of Months 26.74 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.35 0.85
February 23.00 -0.2
March 23.05 4.82
April 22.97 6.08
May 24.12 13.74
June 24.37 22.16
July 24.37 22.71
August 24.37 21.74
September 24.32 18.54
October 23.64 7.12
November 23.38 3.03
December 22.65 -1.0
     
Annual Sum or Average 23.64 10.02
Minimum of Months 22.65 -1.0
Maximum of Months 24.37 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 0.85
February 21.95 -0.2
March 22.52 4.82
April 22.54 6.08
May 24.04 13.74
June 24.38 22.16
July 24.37 22.71
August 24.35 21.74
September 24.21 18.54
October 23.10 7.12
November 22.30 3.03
December 21.82 -1.0
     
Annual Sum or Average 23.14 10.02
Minimum of Months 21.82 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.27 0.85
February 22.96 -0.2
March 23.05 4.82
April 22.94 6.08
May 24.10 13.74
June 24.39 22.16
July 24.39 22.71
August 24.39 21.74
September 24.34 18.54
October 23.60 7.12
November 23.31 3.03
December 22.61 -1.0
     
Annual Sum or Average 23.62 10.02
Minimum of Months 22.61 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 0.85
February 21.90 -0.2
March 22.43 4.82
April 22.47 6.08
May 23.98 13.74
June 24.44 22.16
July 24.43 22.71
August 24.37 21.74
September 24.20 18.54
October 22.95 7.12
November 22.16 3.03
December 21.77 -1.0
     
Annual Sum or Average 23.09 10.02
Minimum of Months 21.77 -1.0
Maximum of Months 24.44 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 0.85
February 21.89 -0.2
March 22.39 4.82
April 22.44 6.08
May 24.00 13.74
June 24.39 22.16
July 24.38 22.71
August 24.33 21.74
September 24.19 18.54
October 23.07 7.12
November 22.22 3.03
December 21.80 -1.0
     
Annual Sum or Average 23.10 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.97 0.85
February 21.88 -0.2
March 22.38 4.82
April 22.44 6.08
May 24.00 13.74
June 24.39 22.16
July 24.38 22.71
August 24.33 21.74
September 24.19 18.54
October 23.05 7.12
November 22.20 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.09 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 0.85
February 23.26 -0.2
March 23.22 4.82
April 23.10 6.08
May 24.14 13.74
June 24.36 22.16
July 24.36 22.71
August 24.38 21.74
September 24.39 18.54
October 23.81 7.12
November 23.64 3.03
December 22.98 -1.0
     
Annual Sum or Average 23.78 10.02
Minimum of Months 22.98 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 0.85
February 23.26 -0.2
March 23.22 4.82
April 23.11 6.08
May 24.14 13.74
June 24.36 22.16
July 24.36 22.71
August 24.38 21.74
September 24.39 18.54
October 23.80 7.12
November 23.64 3.03
December 22.98 -1.0
     
Annual Sum or Average 23.78 10.02
Minimum of Months 22.98 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 0.85
February 23.32 -0.2
March 23.80 4.82
April 23.82 6.08
May 25.68 13.74
June 26.65 22.16
July 26.64 22.71
August 26.58 21.74
September 26.26 18.54
October 24.68 7.12
November 23.87 3.03
December 22.88 -1.0
     
Annual Sum or Average 24.84 10.02
Minimum of Months 22.88 -1.0
Maximum of Months 26.65 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.29 0.85
February 22.96 -0.2
March 23.02 4.82
April 22.91 6.08
May 24.09 13.74
June 24.37 22.16
July 24.37 22.71
August 24.37 21.74
September 24.31 18.54
October 23.61 7.12
November 23.35 3.03
December 22.61 -1.0
     
Annual Sum or Average 23.61 10.02
Minimum of Months 22.61 -1.0
Maximum of Months 24.37 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 0.85
February 21.93 -0.2
March 22.49 4.82
April 22.49 6.08
May 24.01 13.74
June 24.38 22.16
July 24.37 22.71
August 24.35 21.74
September 24.19 18.54
October 23.04 7.12
November 22.27 3.03
December 21.81 -1.0
     
Annual Sum or Average 23.12 10.02
Minimum of Months 21.81 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.22 0.85
February 22.92 -0.2
March 23.01 4.82
April 22.89 6.08
May 24.07 13.74
June 24.38 22.16
July 24.38 22.71
August 24.39 21.74
September 24.33 18.54
October 23.56 7.12
November 23.27 3.03
December 22.56 -1.0
     
Annual Sum or Average 23.59 10.02
Minimum of Months 22.56 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 0.85
February 21.88 -0.2
March 22.40 4.82
April 22.42 6.08
May 23.95 13.74
June 24.44 22.16
July 24.43 22.71
August 24.37 21.74
September 24.18 18.54
October 22.88 7.12
November 22.13 3.03
December 21.77 -1.0
     
Annual Sum or Average 23.07 10.02
Minimum of Months 21.77 -1.0
Maximum of Months 24.44 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 0.85
February 21.86 -0.2
March 22.36 4.82
April 22.39 6.08
May 23.97 13.74
June 24.38 22.16
July 24.37 22.71
August 24.33 21.74
September 24.17 18.54
October 23.00 7.12
November 22.18 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.07 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 0.85
February 21.86 -0.2
March 22.35 4.82
April 22.39 6.08
May 23.97 13.74
June 24.39 22.16
July 24.38 22.71
August 24.33 21.74
September 24.17 18.54
October 22.98 7.12
November 22.17 3.03
December 21.78 -1.0
     
Annual Sum or Average 23.07 10.02
Minimum of Months 21.78 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.62 0.85
February 23.22 -0.2
March 23.17 4.82
April 23.04 6.08
May 24.10 13.74
June 24.35 22.16
July 24.36 22.71
August 24.38 21.74
September 24.37 18.54
October 23.78 7.12
November 23.60 3.03
December 22.92 -1.0
     
Annual Sum or Average 23.75 10.02
Minimum of Months 22.92 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.61 0.85
February 23.22 -0.2
March 23.18 4.82
April 23.04 6.08
May 24.10 13.74
June 24.35 22.16
July 24.36 22.71
August 24.38 21.74
September 24.38 18.54
October 23.78 7.12
November 23.60 3.03
December 22.92 -1.0
     
Annual Sum or Average 23.75 10.02
Minimum of Months 22.92 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.63 0.85
February 23.22 -0.2
March 23.71 4.82
April 23.72 6.08
May 25.62 13.74
June 26.65 22.16
July 26.63 22.71
August 26.57 21.74
September 26.23 18.54
October 24.57 7.12
November 23.78 3.03
December 22.78 -1.0
     
Annual Sum or Average 24.77 10.02
Minimum of Months 22.78 -1.0
Maximum of Months 26.65 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.17 0.85
February 22.87 -0.2
March 22.97 4.82
April 22.84 6.08
May 24.06 13.74
June 24.37 22.16
July 24.37 22.71
August 24.37 21.74
September 24.28 18.54
October 23.54 7.12
November 23.26 3.03
December 22.53 -1.0
     
Annual Sum or Average 23.56 10.02
Minimum of Months 22.53 -1.0
Maximum of Months 24.37 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 0.85
February 21.91 -0.2
March 22.46 4.82
April 22.46 6.08
May 23.97 13.74
June 24.38 22.16
July 24.37 22.71
August 24.35 21.74
September 24.17 18.54
October 22.96 7.12
November 22.23 3.03
December 21.81 -1.0
     
Annual Sum or Average 23.09 10.02
Minimum of Months 21.81 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.10 0.85
February 22.84 -0.2
March 22.96 4.82
April 22.82 6.08
May 24.04 13.74
June 24.38 22.16
July 24.38 22.71
August 24.39 21.74
September 24.31 18.54
October 23.49 7.12
November 23.19 3.03
December 22.49 -1.0
     
Annual Sum or Average 23.54 10.02
Minimum of Months 22.49 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 0.85
February 21.86 -0.2
March 22.37 4.82
April 22.39 6.08
May 23.91 13.74
June 24.45 22.16
July 24.43 22.71
August 24.37 21.74
September 24.16 18.54
October 22.80 7.12
November 22.10 3.03
December 21.76 -1.0
     
Annual Sum or Average 23.05 10.02
Minimum of Months 21.76 -1.0
Maximum of Months 24.45 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 0.85
February 21.85 -0.2
March 22.33 4.82
April 22.36 6.08
May 23.93 13.74
June 24.38 22.16
July 24.37 22.71
August 24.33 21.74
September 24.15 18.54
October 22.89 7.12
November 22.14 3.03
December 21.78 -1.0
     
Annual Sum or Average 23.04 10.02
Minimum of Months 21.78 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 0.85
February 21.85 -0.2
March 22.33 4.82
April 22.35 6.08
May 23.93 13.74
June 24.38 22.16
July 24.37 22.71
August 24.33 21.74
September 24.15 18.54
October 22.88 7.12
November 22.13 3.03
December 21.77 -1.0
     
Annual Sum or Average 23.04 10.02
Minimum of Months 21.77 -1.0
Maximum of Months 24.38 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.47 0.85
February 23.12 -0.2
March 23.10 4.82
April 22.94 6.08
May 24.06 13.74
June 24.35 22.16
July 24.36 22.71
August 24.37 21.74
September 24.35 18.54
October 23.70 7.12
November 23.49 3.03
December 22.81 -1.0
     
Annual Sum or Average 23.68 10.02
Minimum of Months 22.81 -1.0
Maximum of Months 24.37 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.47 0.85
February 23.12 -0.2
March 23.10 4.82
April 22.95 6.08
May 24.06 13.74
June 24.35 22.16
July 24.36 22.71
August 24.37 21.74
September 24.35 18.54
October 23.70 7.12
November 23.49 3.03
December 22.81 -1.0
     
Annual Sum or Average 23.68 10.02
Minimum of Months 22.81 -1.0
Maximum of Months 24.37 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 0.85
February 23.03 -0.2
March 23.56 4.82
April 23.58 6.08
May 25.56 13.74
June 26.72 22.16
July 26.70 22.71
August 26.63 21.74
September 26.21 18.54
October 24.39 7.12
November 23.58 3.03
December 22.56 -1.0
     
Annual Sum or Average 24.67 10.02
Minimum of Months 22.56 -1.0
Maximum of Months 26.72 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.79 0.85
February 22.62 -0.2
March 22.80 4.82
April 22.67 6.08
May 23.84 13.74
June 24.33 22.16
July 24.33 22.71
August 24.33 21.74
September 24.16 18.54
October 23.14 7.12
November 22.89 3.03
December 22.38 -1.0
     
Annual Sum or Average 23.36 10.02
Minimum of Months 22.38 -1.0
Maximum of Months 24.33 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.05 0.85
February 22.00 -0.2
March 22.43 4.82
April 22.43 6.08
May 23.76 13.74
June 24.35 22.16
July 24.33 22.71
August 24.31 21.74
September 24.03 18.54
October 22.78 7.12
November 22.26 3.03
December 21.86 -1.0
     
Annual Sum or Average 23.06 10.02
Minimum of Months 21.86 -1.0
Maximum of Months 24.35 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 0.85
February 22.62 -0.2
March 22.80 4.82
April 22.68 6.08
May 23.82 13.74
June 24.35 22.16
July 24.34 22.71
August 24.35 21.74
September 24.17 18.54
October 23.12 7.12
November 22.85 3.03
December 22.37 -1.0
     
Annual Sum or Average 23.36 10.02
Minimum of Months 22.37 -1.0
Maximum of Months 24.35 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 0.85
February 21.94 -0.2
March 22.35 4.82
April 22.41 6.08
May 23.67 13.74
June 24.39 22.16
July 24.37 22.71
August 24.33 21.74
September 24.01 18.54
October 22.71 7.12
November 22.15 3.03
December 21.79 -1.0
     
Annual Sum or Average 23.01 10.02
Minimum of Months 21.79 -1.0
Maximum of Months 24.39 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 0.85
February 21.89 -0.2
March 22.32 4.82
April 22.35 6.08
May 23.73 13.74
June 24.34 22.16
July 24.32 22.71
August 24.29 21.74
September 24.01 18.54
October 22.70 7.12
November 22.14 3.03
December 21.80 -1.0
     
Annual Sum or Average 22.99 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.34 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 0.85
February 21.89 -0.2
March 22.32 4.82
April 22.35 6.08
May 23.72 13.74
June 24.34 22.16
July 24.32 22.71
August 24.29 21.74
September 24.01 18.54
October 22.69 7.12
November 22.14 3.03
December 21.80 -1.0
     
Annual Sum or Average 22.99 10.02
Minimum of Months 21.80 -1.0
Maximum of Months 24.34 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.95 0.85
February 22.77 -0.2
March 22.91 4.82
April 22.74 6.08
May 23.91 13.74
June 24.32 22.16
July 24.32 22.71
August 24.33 21.74
September 24.21 18.54
October 23.29 7.12
November 23.04 3.03
December 22.52 -1.0
     
Annual Sum or Average 23.45 10.02
Minimum of Months 22.52 -1.0
Maximum of Months 24.33 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.94 0.85
February 22.77 -0.2
March 22.91 4.82
April 22.75 6.08
May 23.91 13.74
June 24.32 22.16
July 24.32 22.71
August 24.33 21.74
September 24.22 18.54
October 23.29 7.12
November 23.04 3.03
December 22.52 -1.0
     
Annual Sum or Average 23.45 10.02
Minimum of Months 22.52 -1.0
Maximum of Months 24.33 22.71



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:15

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.11 0.85
February 22.85 -0.2
March 23.59 4.82
April 23.67 6.08
May 25.95 13.74
June 27.49 22.16
July 27.45 22.71
August 27.37 21.74
September 26.70 18.54
October 24.34 7.12
November 23.44 3.03
December 22.28 -1.0
     
Annual Sum or Average 24.86 10.02
Minimum of Months 22.28 -1.0
Maximum of Months 27.49 22.71



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:15

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.241401E+12 141167.040 05-JAN-18:00 22204.399 56867.515 22475.067 26377.387 0.000 10720.100 1376.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.223260E+12 139569.831 05-FEB-18:00 22204.399 56867.515 22475.067 24780.177 0.000 10720.100 1376.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.240074E+12 147298.139 13-MAR-16:15 18221.747 56933.809 22475.067 0.000 45836.877 0.000 1376.683 1305.652 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.219773E+12 132420.058 16-APR-19:00 25049.151 49704.829 22475.067 22148.656 0.000 10720.100 1376.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.236722E+12 160114.209 31-MAY-17:30 22204.399 56867.515 22475.067 0.000 54275.666 0.000 1376.683 1768.989 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.284369E+12 170956.999 26-JUN-19:30 25049.151 49704.829 22475.067 0.000 58819.019 10720.100 1376.683 1866.578 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.296402E+12 167161.888 15-JUL-17:15 22204.399 56867.515 22475.067 0.000 61240.819 0.000 1376.683 1851.768 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.292625E+12 170661.974 11-AUG-18:00 25049.151 51564.864 22475.067 0.000 56748.550 10720.100 1376.683 1712.945 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.264658E+12 169446.088 12-SEP-18:30 25049.151 51564.864 22475.067 0.000 55518.577 10720.100 1376.683 1727.031 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.243839E+12 154813.222 10-OCT-17:30 22204.399 56867.515 22475.067 0.000 38782.519 10720.100 1376.683 1241.050 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.234399E+12 139972.661 05-NOV-17:15 22204.399 56867.515 22475.067 0.000 24450.813 10720.100 1376.683 732.447 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.253981E+12 168284.434 21-DEC-18:00 22204.399 56867.515 22475.067 53494.780 0.000 10720.100 1376.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.303150E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.219773E+12 132420.058   18221.747 49704.829 22475.067 0.000 0.000 0.000 1376.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.296402E+12 170956.999   25049.151 56933.809 22475.067 53494.780 61240.819 10720.100 1376.683 1866.578 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:15

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.157034E+12 209105.073 05-JAN-09:15 0.000 0.000 0.000 209105.073 84568.570 84568.570 124536.503
February 0.175744E+12 230672.436 12-FEB-06:00 0.000 0.000 0.000 230672.436 86797.487 86797.487 143874.948
March 0.164204E+12 283059.733 19-MAR-07:15 0.000 0.000 0.000 283059.733 87982.126 87982.126 195077.608
April 0.139890E+12 184493.878 17-APR-05:00 0.000 0.000 0.000 184493.878 84601.127 84601.127 99892.751
May 0.103221E+12 112282.801 02-MAY-05:00 0.000 0.000 0.000 112282.801 83695.731 83695.731 28587.070
June 0.930200E+11 83964.548 01-JUN-06:00 0.000 0.000 0.000 83964.548 83964.548 83964.548 0.000
July 0.918066E+11 82241.089 01-JUL-06:00 0.000 0.000 0.000 82241.089 82241.089 82241.089 0.000
August 0.903294E+11 81293.350 30-AUG-06:45 0.000 0.000 0.000 81293.350 81293.350 81293.350 0.000
September 0.890835E+11 82324.511 30-SEP-06:00 0.000 0.000 0.000 82324.511 82324.511 82324.511 0.000
October 0.126171E+12 172540.152 31-OCT-06:30 0.000 0.000 0.000 172540.152 83944.565 83944.565 88595.588
November 0.140091E+12 205510.102 30-NOV-06:00 0.000 0.000 0.000 205510.102 79732.759 79732.759 125777.343
December 0.223768E+12 281517.327 23-DEC-07:15 0.000 0.000 0.000 281517.327 86693.205 86693.205 194824.122
                     
Annual Sum or Average 0.159436E+13     0.000 0.000 0.000        
Minimum of Months 0.890835E+11 81293.350   0.000 0.000 0.000 81293.350 79732.759 79732.759 0.000
Maximum of Months 0.223768E+12 283059.733   0.000 0.000 0.000 283059.733 87982.126 87982.126 195077.608