Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2018-10-19 09:40:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 5182.98 | 661.39 | 734.14 |
Net Site Energy | 5182.98 | 661.39 | 734.14 |
Total Source Energy | 11871.33 | 1514.88 | 1681.52 |
Net Source Energy | 11871.33 | 1514.88 | 1681.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 263.76 | 902.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 702.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.68 | 0.00 | 0.00 | 0.00 | 0.00 | 864.78 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1278.59 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3001.91 | 2181.08 | 0.00 | 0.00 | 0.00 | 5643.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 902.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 263.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 245.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 702.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 45.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 8.68 | 0.00 | 0.00 | 0.00 | 0.00 | 864.78 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1278.59 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 179.23 | 308.94 | 0.00 | 0.00 | 0.00 | 0.80 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 425.21 | 308.94 | 0.00 | 0.00 | 0.00 | 0.80 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.47 | 278.32 | 0.00 | 0.00 | 0.00 | 0.72 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 383.07 | 278.32 | 0.00 | 0.00 | 0.00 | 0.72 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3001.91 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3001.91 | 100.00 |
Total On-Site and Utility Electric Sources | 3001.91 | 100.00 |
Total Electricity End Uses | 3001.91 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5643.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5643.30 | 100.00 |
Total Water End Uses | 5643.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 143.00 |
Time Setpoint Not Met During Occupied Cooling | 147.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2316.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JAN-19:00 | 06-JAN-06:45 | - | - | - | 17-JUL-17:45 |
Heating | 73815.64 | 231254.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51564.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22275.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1453.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 87362.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 185892.94 | 318617.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 231254.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 51564.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22275.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1453.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 87362.79 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 835.33 | 978.29 | 0.00 | 0.00 | 0.00 |
Cooling | 775.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 532.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2224.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 143.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1386.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9507.04 | 2364.29 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 118.32 | 138.57 | 0.00 | 0.00 | 0.00 |
Cooling | 109.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 315.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 196.32 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1346.63 | 334.89 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 118.32 | 138.57 | 0.00 | 0.00 | 0.00 |
Cooling | 109.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 315.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 196.32 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1346.63 | 334.89 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.60 | 83.60 | 168.22 | |
Exterior Lighting Total | 10720.10 | 168.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 255302.01 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 204241.61 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3321.43 | 2275.47 | 1045.96 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2949.73 | 2029.06 | 920.67 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4577.95 | 3120.77 | 1457.18 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2081.33 | 1451.43 | 629.90 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1401.26 | 982.07 | 419.19 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1382.83 | 969.98 | 412.85 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2254.65 | 1527.00 | 727.66 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2330.41 | 1578.49 | 751.91 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4333.48 | 2969.14 | 1364.34 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3817.10 | 2623.83 | 1193.27 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4220.88 | 2879.05 | 1341.82 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2777.95 | 1932.30 | 845.66 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1970.77 | 1369.60 | 601.17 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1948.47 | 1354.58 | 593.89 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2964.33 | 2014.00 | 950.33 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2994.12 | 2034.22 | 959.90 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4338.86 | 2977.99 | 1360.88 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3842.03 | 2645.89 | 1196.14 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4016.05 | 2745.17 | 1270.88 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2824.91 | 1969.13 | 855.78 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2023.57 | 1408.16 | 615.42 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2001.49 | 1393.28 | 608.21 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3011.76 | 2049.21 | 962.55 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3027.15 | 2059.66 | 967.49 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4340.46 | 2982.97 | 1357.50 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3857.98 | 2659.91 | 1198.07 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4004.06 | 2740.82 | 1263.23 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2850.73 | 1986.09 | 864.64 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2040.22 | 1421.62 | 618.60 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2018.24 | 1406.81 | 611.44 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3024.55 | 2060.16 | 964.39 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3037.94 | 2069.24 | 968.70 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4373.53 | 3008.55 | 1364.98 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3896.13 | 2688.92 | 1207.22 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4047.10 | 2771.69 | 1275.41 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2889.37 | 2015.33 | 874.04 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2083.34 | 1452.51 | 630.82 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2061.46 | 1437.75 | 623.71 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3064.80 | 2089.34 | 975.46 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3077.88 | 2098.22 | 979.66 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4315.91 | 2972.23 | 1343.68 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3840.33 | 2653.84 | 1186.49 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3996.27 | 2739.80 | 1256.46 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2836.62 | 1982.01 | 854.60 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2035.60 | 1421.90 | 613.70 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2013.91 | 1407.26 | 606.65 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3014.15 | 2056.52 | 957.64 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3027.21 | 2065.38 | 961.83 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4292.82 | 2958.96 | 1333.85 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3819.94 | 2642.41 | 1177.53 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3979.05 | 2730.42 | 1248.63 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2817.98 | 1971.56 | 846.42 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2020.84 | 1413.32 | 607.52 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1999.30 | 1398.78 | 600.52 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2996.62 | 2045.99 | 950.63 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3009.66 | 2054.84 | 954.82 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4288.38 | 2958.09 | 1330.29 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3818.16 | 2643.33 | 1174.83 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3978.66 | 2732.22 | 1246.44 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2816.33 | 1972.42 | 843.91 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2024.36 | 1416.91 | 607.45 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2002.99 | 1402.48 | 600.51 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2996.17 | 2046.93 | 949.24 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3009.25 | 2055.81 | 953.44 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4410.10 | 3042.56 | 1367.54 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3935.64 | 2724.88 | 1210.76 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4061.64 | 2790.51 | 1271.13 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2848.25 | 1995.97 | 852.28 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2130.01 | 1489.31 | 640.70 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2108.40 | 1474.71 | 633.69 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3065.43 | 2095.16 | 970.27 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3080.16 | 2105.16 | 975.00 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5444.80 | 3736.06 | 1708.74 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4746.24 | 3270.83 | 1475.41 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4976.68 | 3415.03 | 1561.65 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3521.11 | 2448.04 | 1073.07 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2774.22 | 1901.55 | 872.67 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2774.49 | 1900.02 | 874.46 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4141.10 | 2826.61 | 1314.50 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4155.52 | 2836.38 | 1319.14 | 0.68 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3321.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2949.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4577.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2081.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1401.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1382.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2254.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2330.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4333.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3817.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4220.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2777.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1970.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1948.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2964.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2994.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4338.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3842.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4016.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2824.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2023.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2001.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3011.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3027.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4340.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3857.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4004.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2850.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2040.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2018.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3024.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3037.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4373.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3896.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4047.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2889.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2083.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2061.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3064.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3077.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4315.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3840.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3996.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2836.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2035.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2013.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3014.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3027.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4292.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3819.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3979.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2817.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2020.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1999.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2996.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3009.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4288.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3818.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3978.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2816.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2024.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2002.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2996.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3009.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4410.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3935.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4061.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2848.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2130.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2108.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3065.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3080.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5444.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4746.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4976.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3521.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2774.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2774.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4141.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4155.52 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 4534.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 4551.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 5645.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 4557.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 3509.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 3509.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 3490.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 3498.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 4373.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 4380.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 4403.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 4386.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 3123.89 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 3124.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 3120.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 3121.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 4357.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 4363.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 4363.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 4367.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 3065.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 3065.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 3060.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 3060.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 4415.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 4420.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 4417.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 4421.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 3086.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 3086.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 3082.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 3082.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 4450.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 4451.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 4450.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 4451.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 3090.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 3090.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 3089.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 3089.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 4551.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 4552.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 4550.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 4551.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 3164.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 3164.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 3165.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 3165.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 4621.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 4620.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 4619.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 4618.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 3211.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 3211.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 3213.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 3213.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 4699.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 4695.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 4696.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 4692.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 3268.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 3268.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 3273.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 3273.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 4961.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 4952.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 4957.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 4948.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 3496.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 3496.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 3506.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 3505.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 5962.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 5961.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 5958.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 5957.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 4570.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 4570.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 4568.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 4568.76 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 289.74 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.97 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 390.55 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 185.29 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 126.26 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 124.70 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.73 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.39 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 380.10 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 337.48 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 363.90 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 248.24 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 176.61 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.66 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 250.97 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.59 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 381.51 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 340.61 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.81 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.27 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.75 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 179.83 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.68 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 257.04 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 382.36 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 341.86 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.44 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.73 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 183.61 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.69 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 257.22 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.39 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.84 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.79 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 350.30 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.68 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 187.70 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 185.79 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.09 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 262.24 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 381.27 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 341.38 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.30 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.48 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 183.82 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.92 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.92 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.07 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 379.67 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 340.02 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.20 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.23 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 182.78 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 180.89 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.63 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.78 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 379.67 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 340.25 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.54 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.44 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 183.30 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 181.43 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.82 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.97 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 390.73 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 350.92 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 353.20 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.59 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 192.74 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 190.85 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 262.12 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 263.42 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 477.02 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 419.88 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 434.59 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 313.84 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.80 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.25 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 356.96 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 358.23 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0056 | 1416.30 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2407.53 | 2889.03 | 0.216 | 0.259 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
G NW APARTMENT | 2160.14 | 2592.17 | 0.193 | 0.232 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36 | 0.00627 |
OFFICE | 3245.23 | 3894.27 | 0.291 | 0.349 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
G NE APARTMENT | 1493.24 | 1791.88 | 0.134 | 0.160 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 28.52 | 0.00627 |
G N1 APARTMENT | 1049.12 | 1258.94 | 0.094 | 0.113 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
G N2 APARTMENT | 1029.64 | 1235.57 | 0.092 | 0.111 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
G S1 APARTMENT | 1559.88 | 1871.86 | 0.140 | 0.168 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
G S2 APARTMENT | 1615.18 | 1938.21 | 0.145 | 0.174 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
F2 SW APARTMENT | 3158.31 | 3789.97 | 0.283 | 0.339 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F2 NW APARTMENT | 2804.16 | 3365.00 | 0.251 | 0.301 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36 | 0.00627 |
F2 SE APARTMENT | 3023.75 | 3628.50 | 0.271 | 0.325 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
F2 NE APARTMENT | 2062.67 | 2475.20 | 0.185 | 0.222 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 28.52 | 0.00627 |
F2 N1 APARTMENT | 1467.45 | 1760.94 | 0.131 | 0.158 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F2 N2 APARTMENT | 1451.30 | 1741.56 | 0.130 | 0.156 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F2 S1 APARTMENT | 2085.38 | 2502.45 | 0.187 | 0.224 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F2 S2 APARTMENT | 2107.12 | 2528.55 | 0.189 | 0.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F3 SW APARTMENT | 3170.09 | 3804.11 | 0.284 | 0.341 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F3 NW APARTMENT | 2830.17 | 3396.20 | 0.253 | 0.304 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36 | 0.00627 |
F3 SE APARTMENT | 2881.75 | 3458.10 | 0.258 | 0.310 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
F3 NE APARTMENT | 2104.49 | 2525.38 | 0.188 | 0.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 28.52 | 0.00627 |
F3 N1 APARTMENT | 1510.19 | 1812.23 | 0.135 | 0.162 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F3 N2 APARTMENT | 1494.19 | 1793.03 | 0.134 | 0.161 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F3 S1 APARTMENT | 2124.54 | 2549.45 | 0.190 | 0.228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F3 S2 APARTMENT | 2135.78 | 2562.93 | 0.191 | 0.229 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F4 SW APARTMENT | 3177.14 | 3812.57 | 0.284 | 0.341 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F4 NW APARTMENT | 2840.63 | 3408.75 | 0.254 | 0.305 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
F4 SE APARTMENT | 2878.71 | 3454.45 | 0.258 | 0.309 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
F4 NE APARTMENT | 2116.64 | 2539.97 | 0.190 | 0.227 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
F4 N1 APARTMENT | 1525.63 | 1830.76 | 0.137 | 0.164 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F4 N2 APARTMENT | 1509.69 | 1811.63 | 0.135 | 0.162 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F4 S1 APARTMENT | 2137.30 | 2564.76 | 0.191 | 0.230 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F4 S2 APARTMENT | 2147.07 | 2576.48 | 0.192 | 0.231 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
M SW APARTMENT | 3206.08 | 3847.29 | 0.287 | 0.344 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
M NW APARTMENT | 2873.24 | 3447.89 | 0.257 | 0.309 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
M SE APARTMENT | 2910.77 | 3492.93 | 0.261 | 0.313 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
M NE APARTMENT | 2149.43 | 2579.32 | 0.192 | 0.231 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
M N1 APARTMENT | 1559.64 | 1871.56 | 0.140 | 0.168 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
M N2 APARTMENT | 1543.76 | 1852.51 | 0.138 | 0.166 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
M S1 APARTMENT | 2169.49 | 2603.39 | 0.194 | 0.233 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
M S2 APARTMENT | 2179.04 | 2614.85 | 0.195 | 0.234 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F6 SW APARTMENT | 3168.11 | 3801.73 | 0.284 | 0.340 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F6 NW APARTMENT | 2836.61 | 3403.93 | 0.254 | 0.305 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
F6 SE APARTMENT | 2877.56 | 3453.07 | 0.258 | 0.309 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
F6 NE APARTMENT | 2114.56 | 2537.48 | 0.189 | 0.227 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
F6 N1 APARTMENT | 1527.37 | 1832.85 | 0.137 | 0.164 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F6 N2 APARTMENT | 1511.62 | 1813.95 | 0.135 | 0.162 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F6 S1 APARTMENT | 2134.86 | 2561.83 | 0.191 | 0.229 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F6 S2 APARTMENT | 2144.39 | 2573.27 | 0.192 | 0.230 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F7 SW APARTMENT | 3154.83 | 3785.80 | 0.282 | 0.339 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F7 NW APARTMENT | 2825.31 | 3390.37 | 0.253 | 0.304 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
F7 SE APARTMENT | 2868.44 | 3442.12 | 0.257 | 0.308 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
F7 NE APARTMENT | 2104.22 | 2525.06 | 0.188 | 0.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
F7 N1 APARTMENT | 1518.72 | 1822.46 | 0.136 | 0.163 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F7 N2 APARTMENT | 1503.07 | 1803.68 | 0.135 | 0.161 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F7 S1 APARTMENT | 2124.13 | 2548.95 | 0.190 | 0.228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F7 S2 APARTMENT | 2133.65 | 2560.38 | 0.191 | 0.229 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F8 SW APARTMENT | 3154.81 | 3785.78 | 0.282 | 0.339 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F8 NW APARTMENT | 2827.21 | 3392.65 | 0.253 | 0.304 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
F8 SE APARTMENT | 2871.27 | 3445.53 | 0.257 | 0.308 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
F8 NE APARTMENT | 2105.98 | 2527.18 | 0.189 | 0.226 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
F8 N1 APARTMENT | 1523.10 | 1827.73 | 0.136 | 0.164 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F8 N2 APARTMENT | 1507.57 | 1809.08 | 0.135 | 0.162 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F8 S1 APARTMENT | 2125.67 | 2550.81 | 0.190 | 0.228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F8 S2 APARTMENT | 2135.23 | 2562.27 | 0.191 | 0.229 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F9 SW APARTMENT | 3246.69 | 3896.03 | 0.291 | 0.349 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.96 | 0.00627 |
F9 NW APARTMENT | 2915.93 | 3499.12 | 0.261 | 0.313 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.96 | 0.00627 |
F9 SE APARTMENT | 2934.90 | 3521.88 | 0.263 | 0.315 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
F9 NE APARTMENT | 2132.16 | 2558.60 | 0.191 | 0.229 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.12 | 0.00627 |
F9 N1 APARTMENT | 1601.49 | 1921.79 | 0.143 | 0.172 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F9 N2 APARTMENT | 1585.77 | 1902.93 | 0.142 | 0.170 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
F9 S1 APARTMENT | 2178.07 | 2613.69 | 0.195 | 0.234 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
F9 S2 APARTMENT | 2188.83 | 2626.60 | 0.196 | 0.235 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
T SW APARTMENT | 3963.80 | 4756.56 | 0.355 | 0.426 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 32.68 | 0.00627 |
T NW APARTMENT | 3488.94 | 4186.72 | 0.312 | 0.375 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36 | 0.00627 |
T SE APARTMENT | 3611.24 | 4333.49 | 0.323 | 0.388 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.20 | 0.00627 |
T NE APARTMENT | 2607.84 | 3129.41 | 0.233 | 0.280 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 30.12 | 0.00627 |
T N1 APARTMENT | 1975.93 | 2371.11 | 0.177 | 0.212 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.92 | 0.00627 |
T N2 APARTMENT | 1971.39 | 2365.66 | 0.177 | 0.212 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 33.16 | 0.00627 |
T S1 APARTMENT | 2966.09 | 3559.31 | 0.266 | 0.319 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
T S2 APARTMENT | 2976.62 | 3571.94 | 0.267 | 0.320 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2689.26 | 3227.12 | 0.137 | 0.164 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G NW APARTMENT | 2703.84 | 3244.61 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
OFFICE | 3093.10 | 3711.72 | 0.157 | 0.189 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -27.60 | 0.00034 |
G NE APARTMENT | 2709.22 | 3251.07 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G N1 APARTMENT | 1823.09 | 2187.70 | 0.093 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G N2 APARTMENT | 1823.20 | 2187.85 | 0.093 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G S1 APARTMENT | 1806.35 | 2167.62 | 0.092 | 0.110 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
G S2 APARTMENT | 1813.63 | 2176.36 | 0.092 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
F2 SW APARTMENT | 2553.75 | 3064.50 | 0.130 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 NW APARTMENT | 2559.58 | 3071.49 | 0.130 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 SE APARTMENT | 2578.84 | 3094.61 | 0.131 | 0.157 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 NE APARTMENT | 2564.07 | 3076.88 | 0.130 | 0.157 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 N1 APARTMENT | 1496.74 | 1796.09 | 0.076 | 0.091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 N2 APARTMENT | 1496.84 | 1796.21 | 0.076 | 0.091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 S1 APARTMENT | 1493.49 | 1792.19 | 0.076 | 0.091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F2 S2 APARTMENT | 1494.84 | 1793.81 | 0.076 | 0.091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 SW APARTMENT | 2539.78 | 3047.73 | 0.129 | 0.155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 NW APARTMENT | 2545.33 | 3054.40 | 0.130 | 0.155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 SE APARTMENT | 2544.70 | 3053.64 | 0.129 | 0.155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 NE APARTMENT | 2548.19 | 3057.83 | 0.130 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 N1 APARTMENT | 1447.37 | 1736.85 | 0.074 | 0.088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 N2 APARTMENT | 1447.44 | 1736.93 | 0.074 | 0.088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 S1 APARTMENT | 1442.71 | 1731.26 | 0.073 | 0.088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F3 S2 APARTMENT | 1442.96 | 1731.55 | 0.073 | 0.088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 SW APARTMENT | 2588.92 | 3106.71 | 0.132 | 0.158 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 NW APARTMENT | 2592.97 | 3111.56 | 0.132 | 0.158 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 SE APARTMENT | 2590.58 | 3108.69 | 0.132 | 0.158 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 NE APARTMENT | 2594.43 | 3113.31 | 0.132 | 0.158 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 N1 APARTMENT | 1465.04 | 1758.04 | 0.075 | 0.089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 N2 APARTMENT | 1465.07 | 1758.08 | 0.075 | 0.089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 S1 APARTMENT | 1461.65 | 1753.98 | 0.074 | 0.089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F4 S2 APARTMENT | 1461.70 | 1754.04 | 0.074 | 0.089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M SW APARTMENT | 2618.21 | 3141.85 | 0.133 | 0.160 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M NW APARTMENT | 2619.58 | 3143.49 | 0.133 | 0.160 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M SE APARTMENT | 2618.47 | 3142.16 | 0.133 | 0.160 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M NE APARTMENT | 2619.82 | 3143.78 | 0.133 | 0.160 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M N1 APARTMENT | 1468.09 | 1761.70 | 0.075 | 0.090 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M N2 APARTMENT | 1468.09 | 1761.71 | 0.075 | 0.090 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M S1 APARTMENT | 1467.38 | 1760.86 | 0.075 | 0.090 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
M S2 APARTMENT | 1467.39 | 1760.87 | 0.075 | 0.090 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 SW APARTMENT | 2704.00 | 3244.80 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 NW APARTMENT | 2704.53 | 3245.43 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 SE APARTMENT | 2703.17 | 3243.81 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 NE APARTMENT | 2703.70 | 3244.44 | 0.138 | 0.165 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 N1 APARTMENT | 1531.48 | 1837.77 | 0.078 | 0.094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 N2 APARTMENT | 1531.46 | 1837.75 | 0.078 | 0.094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 S1 APARTMENT | 1531.58 | 1837.90 | 0.078 | 0.094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F6 S2 APARTMENT | 1531.56 | 1837.87 | 0.078 | 0.094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 SW APARTMENT | 2763.25 | 3315.90 | 0.141 | 0.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 NW APARTMENT | 2762.07 | 3314.49 | 0.141 | 0.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 SE APARTMENT | 2761.47 | 3313.76 | 0.140 | 0.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 NE APARTMENT | 2760.29 | 3312.35 | 0.140 | 0.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 N1 APARTMENT | 1571.04 | 1885.25 | 0.080 | 0.096 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 N2 APARTMENT | 1571.00 | 1885.20 | 0.080 | 0.096 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 S1 APARTMENT | 1572.88 | 1887.45 | 0.080 | 0.096 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F7 S2 APARTMENT | 1572.84 | 1887.41 | 0.080 | 0.096 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 SW APARTMENT | 2829.21 | 3395.05 | 0.144 | 0.173 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 NW APARTMENT | 2826.15 | 3391.38 | 0.144 | 0.173 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 SE APARTMENT | 2826.57 | 3391.88 | 0.144 | 0.173 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 NE APARTMENT | 2823.51 | 3388.21 | 0.144 | 0.172 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 N1 APARTMENT | 1619.30 | 1943.16 | 0.082 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 N2 APARTMENT | 1619.24 | 1943.09 | 0.082 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 S1 APARTMENT | 1623.04 | 1947.65 | 0.083 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F8 S2 APARTMENT | 1622.98 | 1947.58 | 0.083 | 0.099 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 SW APARTMENT | 3050.95 | 3661.14 | 0.155 | 0.186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 NW APARTMENT | 3042.89 | 3651.47 | 0.155 | 0.186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 SE APARTMENT | 3047.49 | 3656.99 | 0.155 | 0.186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 NE APARTMENT | 3039.43 | 3647.32 | 0.155 | 0.186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 N1 APARTMENT | 1811.56 | 2173.87 | 0.092 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 N2 APARTMENT | 1811.48 | 2173.78 | 0.092 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 S1 APARTMENT | 1819.95 | 2183.94 | 0.093 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
F9 S2 APARTMENT | 1819.87 | 2183.84 | 0.093 | 0.111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T SW APARTMENT | 3897.38 | 4676.85 | 0.198 | 0.238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T NW APARTMENT | 3896.82 | 4676.19 | 0.198 | 0.238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T SE APARTMENT | 3893.54 | 4672.24 | 0.198 | 0.238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T NE APARTMENT | 3892.98 | 4671.58 | 0.198 | 0.238 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T N1 APARTMENT | 2720.25 | 3264.29 | 0.138 | 0.166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T N2 APARTMENT | 2720.15 | 3264.19 | 0.138 | 0.166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T S1 APARTMENT | 2718.70 | 3262.44 | 0.138 | 0.166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
T S2 APARTMENT | 2718.61 | 3262.33 | 0.138 | 0.166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -27.60 | 0.00034 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.26 | 0.26 | 0.16 | 0.16 |
AIRLOOP G NW | 0.23 | 0.23 | 0.17 | 0.17 |
AIRLOOP OFFICE | 0.35 | 0.35 | 0.19 | 0.19 |
AIRLOOP G NE | 0.16 | 0.16 | 0.17 | 0.17 |
AIRLOOP G N1 | 0.11 | 0.11 | 0.11 | 0.11 |
AIRLOOP G N2 | 0.11 | 0.11 | 0.11 | 0.11 |
AIRLOOP G S1 | 0.17 | 0.17 | 0.11 | 0.11 |
AIRLOOP G S2 | 0.17 | 0.17 | 0.11 | 0.11 |
AIRLOOP F2 SW | 0.34 | 0.34 | 0.16 | 0.16 |
AIRLOOP F2 NW | 0.30 | 0.30 | 0.16 | 0.16 |
AIRLOOP F2 SE | 0.32 | 0.32 | 0.16 | 0.16 |
AIRLOOP F2 NE | 0.22 | 0.22 | 0.16 | 0.16 |
AIRLOOP F2 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F2 N2 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F2 S1 | 0.22 | 0.22 | 0.09 | 0.09 |
AIRLOOP F2 S2 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F3 SW | 0.34 | 0.34 | 0.16 | 0.16 |
AIRLOOP F3 NW | 0.30 | 0.30 | 0.16 | 0.16 |
AIRLOOP F3 SE | 0.31 | 0.31 | 0.16 | 0.16 |
AIRLOOP F3 NE | 0.23 | 0.23 | 0.16 | 0.16 |
AIRLOOP F3 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F3 N2 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F3 S1 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F3 S2 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F4 SW | 0.34 | 0.34 | 0.16 | 0.16 |
AIRLOOP F4 NW | 0.31 | 0.31 | 0.16 | 0.16 |
AIRLOOP F4 SE | 0.31 | 0.31 | 0.16 | 0.16 |
AIRLOOP F4 NE | 0.23 | 0.23 | 0.16 | 0.16 |
AIRLOOP F4 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F4 N2 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F4 S1 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F4 S2 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP M SW | 0.34 | 0.34 | 0.16 | 0.16 |
AIRLOOP M NW | 0.31 | 0.31 | 0.16 | 0.16 |
AIRLOOP M SE | 0.31 | 0.31 | 0.16 | 0.16 |
AIRLOOP M NE | 0.23 | 0.23 | 0.16 | 0.16 |
AIRLOOP M N1 | 0.17 | 0.17 | 0.09 | 0.09 |
AIRLOOP M N2 | 0.17 | 0.17 | 0.09 | 0.09 |
AIRLOOP M S1 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP M S2 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F6 SW | 0.34 | 0.34 | 0.17 | 0.17 |
AIRLOOP F6 NW | 0.30 | 0.30 | 0.17 | 0.17 |
AIRLOOP F6 SE | 0.31 | 0.31 | 0.17 | 0.17 |
AIRLOOP F6 NE | 0.23 | 0.23 | 0.17 | 0.17 |
AIRLOOP F6 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F6 N2 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F6 S1 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F6 S2 | 0.23 | 0.23 | 0.09 | 0.09 |
AIRLOOP F7 SW | 0.34 | 0.34 | 0.17 | 0.17 |
AIRLOOP F7 NW | 0.30 | 0.30 | 0.17 | 0.17 |
AIRLOOP F7 SE | 0.31 | 0.31 | 0.17 | 0.17 |
AIRLOOP F7 NE | 0.23 | 0.23 | 0.17 | 0.17 |
AIRLOOP F7 N1 | 0.16 | 0.16 | 0.10 | 0.10 |
AIRLOOP F7 N2 | 0.16 | 0.16 | 0.10 | 0.10 |
AIRLOOP F7 S1 | 0.23 | 0.23 | 0.10 | 0.10 |
AIRLOOP F7 S2 | 0.23 | 0.23 | 0.10 | 0.10 |
AIRLOOP F8 SW | 0.34 | 0.34 | 0.17 | 0.17 |
AIRLOOP F8 NW | 0.30 | 0.30 | 0.17 | 0.17 |
AIRLOOP F8 SE | 0.31 | 0.31 | 0.17 | 0.17 |
AIRLOOP F8 NE | 0.23 | 0.23 | 0.17 | 0.17 |
AIRLOOP F8 N1 | 0.16 | 0.16 | 0.10 | 0.10 |
AIRLOOP F8 N2 | 0.16 | 0.16 | 0.10 | 0.10 |
AIRLOOP F8 S1 | 0.23 | 0.23 | 0.10 | 0.10 |
AIRLOOP F8 S2 | 0.23 | 0.23 | 0.10 | 0.10 |
AIRLOOP F9 SW | 0.35 | 0.35 | 0.19 | 0.19 |
AIRLOOP F9 NW | 0.31 | 0.31 | 0.19 | 0.19 |
AIRLOOP F9 SE | 0.32 | 0.32 | 0.19 | 0.19 |
AIRLOOP F9 NE | 0.23 | 0.23 | 0.19 | 0.19 |
AIRLOOP F9 N1 | 0.17 | 0.17 | 0.11 | 0.11 |
AIRLOOP F9 N2 | 0.17 | 0.17 | 0.11 | 0.11 |
AIRLOOP F9 S1 | 0.23 | 0.23 | 0.11 | 0.11 |
AIRLOOP F9 S2 | 0.24 | 0.24 | 0.11 | 0.11 |
AIRLOOP T SW | 0.43 | 0.43 | 0.24 | 0.24 |
AIRLOOP T NW | 0.37 | 0.37 | 0.24 | 0.24 |
AIRLOOP T SE | 0.39 | 0.39 | 0.24 | 0.24 |
AIRLOOP T NE | 0.28 | 0.28 | 0.24 | 0.24 |
AIRLOOP T N1 | 0.21 | 0.21 | 0.17 | 0.17 |
AIRLOOP T N2 | 0.21 | 0.21 | 0.17 | 0.17 |
AIRLOOP T S1 | 0.32 | 0.32 | 0.17 | 0.17 |
AIRLOOP T S2 | 0.32 | 0.32 | 0.17 | 0.17 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2279.00 | 6122.50 | 861.75 |
G NW APARTMENT | 2351.50 | 6766.50 | 1344.75 |
OFFICE | 789.00 | 1208.00 | 161.25 |
G NE APARTMENT | 2482.50 | 6819.50 | 1386.00 |
G N1 APARTMENT | 1550.75 | 7045.50 | 847.25 |
G N2 APARTMENT | 1554.00 | 7043.25 | 849.00 |
G S1 APARTMENT | 1670.75 | 6265.75 | 465.00 |
G S2 APARTMENT | 1695.00 | 6213.00 | 455.25 |
F2 SW APARTMENT | 2626.25 | 5052.50 | 530.50 |
F2 NW APARTMENT | 2447.75 | 6122.25 | 902.50 |
F2 SE APARTMENT | 2753.25 | 4896.00 | 496.25 |
F2 NE APARTMENT | 2528.50 | 6219.50 | 912.25 |
F2 N1 APARTMENT | 1664.50 | 6375.25 | 377.00 |
F2 N2 APARTMENT | 1667.50 | 6383.50 | 376.25 |
F2 S1 APARTMENT | 2174.75 | 4875.75 | 177.75 |
F2 S2 APARTMENT | 2196.25 | 4845.75 | 176.25 |
F3 SW APARTMENT | 2688.25 | 4917.25 | 491.00 |
F3 NW APARTMENT | 2471.25 | 6032.25 | 854.75 |
F3 SE APARTMENT | 2752.00 | 4873.50 | 488.00 |
F3 NE APARTMENT | 2531.75 | 6118.25 | 866.25 |
F3 N1 APARTMENT | 1699.50 | 6234.50 | 315.75 |
F3 N2 APARTMENT | 1705.50 | 6238.25 | 316.25 |
F3 S1 APARTMENT | 2315.25 | 4598.00 | 146.50 |
F3 S2 APARTMENT | 2322.00 | 4584.50 | 146.00 |
F4 SW APARTMENT | 2693.50 | 4936.75 | 498.25 |
F4 NW APARTMENT | 2489.50 | 6029.75 | 866.50 |
F4 SE APARTMENT | 2754.25 | 4911.50 | 497.25 |
F4 NE APARTMENT | 2548.25 | 6108.00 | 874.75 |
F4 N1 APARTMENT | 1720.50 | 6203.50 | 313.75 |
F4 N2 APARTMENT | 1723.25 | 6205.50 | 314.50 |
F4 S1 APARTMENT | 2337.50 | 4570.00 | 144.00 |
F4 S2 APARTMENT | 2346.50 | 4565.25 | 144.00 |
M SW APARTMENT | 2686.50 | 4962.25 | 496.25 |
M NW APARTMENT | 2489.50 | 6038.50 | 856.25 |
M SE APARTMENT | 2746.25 | 4948.25 | 495.00 |
M NE APARTMENT | 2545.00 | 6111.75 | 860.75 |
M N1 APARTMENT | 1727.75 | 6192.25 | 301.50 |
M N2 APARTMENT | 1735.25 | 6195.75 | 302.75 |
M S1 APARTMENT | 2344.50 | 4573.50 | 138.50 |
M S2 APARTMENT | 2350.50 | 4567.75 | 138.75 |
F6 SW APARTMENT | 2609.50 | 5122.25 | 544.25 |
F6 NW APARTMENT | 2463.50 | 6140.50 | 921.25 |
F6 SE APARTMENT | 2662.75 | 5111.50 | 543.25 |
F6 NE APARTMENT | 2522.50 | 6217.25 | 929.75 |
F6 N1 APARTMENT | 1669.25 | 6301.00 | 342.25 |
F6 N2 APARTMENT | 1674.25 | 6308.75 | 343.25 |
F6 S1 APARTMENT | 2216.75 | 4773.50 | 155.00 |
F6 S2 APARTMENT | 2223.25 | 4765.75 | 155.50 |
F7 SW APARTMENT | 2567.00 | 5247.00 | 572.50 |
F7 NW APARTMENT | 2445.50 | 6217.50 | 956.75 |
F7 SE APARTMENT | 2619.00 | 5224.00 | 574.75 |
F7 NE APARTMENT | 2512.50 | 6292.25 | 964.00 |
F7 N1 APARTMENT | 1645.50 | 6365.25 | 368.25 |
F7 N2 APARTMENT | 1649.50 | 6370.25 | 369.50 |
F7 S1 APARTMENT | 2133.75 | 4916.25 | 168.00 |
F7 S2 APARTMENT | 2141.50 | 4912.75 | 167.50 |
F8 SW APARTMENT | 2531.50 | 5362.50 | 601.50 |
F8 NW APARTMENT | 2451.75 | 6266.75 | 993.75 |
F8 SE APARTMENT | 2594.50 | 5326.00 | 603.50 |
F8 NE APARTMENT | 2508.75 | 6347.50 | 996.25 |
F8 N1 APARTMENT | 1640.00 | 6427.75 | 398.50 |
F8 N2 APARTMENT | 1644.75 | 6433.00 | 398.00 |
F8 S1 APARTMENT | 2075.75 | 5051.50 | 183.75 |
F8 S2 APARTMENT | 2085.00 | 5042.50 | 184.25 |
F9 SW APARTMENT | 2564.75 | 5509.00 | 706.50 |
F9 NW APARTMENT | 2565.50 | 6335.75 | 1132.75 |
F9 SE APARTMENT | 2626.50 | 5477.00 | 703.75 |
F9 NE APARTMENT | 2636.50 | 6407.25 | 1149.25 |
F9 N1 APARTMENT | 1768.75 | 6499.75 | 549.25 |
F9 N2 APARTMENT | 1774.50 | 6503.00 | 551.00 |
F9 S1 APARTMENT | 2054.50 | 5243.75 | 261.50 |
F9 S2 APARTMENT | 2065.50 | 5234.25 | 262.00 |
T SW APARTMENT | 3380.75 | 5823.00 | 1591.00 |
T NW APARTMENT | 3506.50 | 6515.50 | 2158.00 |
T SE APARTMENT | 3458.50 | 5748.75 | 1583.00 |
T NE APARTMENT | 3590.75 | 6578.50 | 2169.25 |
T N1 APARTMENT | 2597.25 | 6688.75 | 1401.50 |
T N2 APARTMENT | 2606.00 | 6685.75 | 1402.25 |
T S1 APARTMENT | 2669.00 | 5614.25 | 924.00 |
T S2 APARTMENT | 2678.00 | 5604.50 | 923.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5021.00 | 7208.75 | 2316.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.25 | 38.00 | 3.25 | 38.00 |
G NW APARTMENT | 2.75 | 10.75 | 2.75 | 10.75 |
OFFICE | 2.25 | 9.75 | 0.25 | 9.75 |
G NE APARTMENT | 4.00 | 16.25 | 4.00 | 16.25 |
G N1 APARTMENT | 4.00 | 36.50 | 4.00 | 36.50 |
G N2 APARTMENT | 3.25 | 39.00 | 3.25 | 39.00 |
G S1 APARTMENT | 5.00 | 43.00 | 5.00 | 43.00 |
G S2 APARTMENT | 4.25 | 35.25 | 4.25 | 35.25 |
F2 SW APARTMENT | 2.25 | 17.00 | 2.25 | 17.00 |
F2 NW APARTMENT | 0.50 | 7.25 | 0.50 | 7.25 |
F2 SE APARTMENT | 1.00 | 2.75 | 1.00 | 2.75 |
F2 NE APARTMENT | 2.00 | 19.50 | 2.00 | 19.50 |
F2 N1 APARTMENT | 4.00 | 22.75 | 4.00 | 22.75 |
F2 N2 APARTMENT | 3.50 | 24.75 | 3.50 | 24.75 |
F2 S1 APARTMENT | 2.25 | 39.75 | 2.25 | 39.75 |
F2 S2 APARTMENT | 2.25 | 36.75 | 2.25 | 36.75 |
F3 SW APARTMENT | 1.00 | 22.75 | 1.00 | 22.75 |
F3 NW APARTMENT | 0.25 | 8.25 | 0.25 | 8.25 |
F3 SE APARTMENT | 0.25 | 16.25 | 0.25 | 16.25 |
F3 NE APARTMENT | 2.75 | 26.75 | 2.75 | 26.75 |
F3 N1 APARTMENT | 4.75 | 27.00 | 4.75 | 27.00 |
F3 N2 APARTMENT | 5.00 | 30.50 | 5.00 | 30.50 |
F3 S1 APARTMENT | 2.50 | 42.25 | 2.50 | 42.25 |
F3 S2 APARTMENT | 2.25 | 41.75 | 2.25 | 41.75 |
F4 SW APARTMENT | 0.00 | 25.75 | 0.00 | 25.75 |
F4 NW APARTMENT | 1.50 | 9.00 | 1.50 | 9.00 |
F4 SE APARTMENT | 1.00 | 20.75 | 1.00 | 20.75 |
F4 NE APARTMENT | 4.50 | 29.50 | 4.50 | 29.50 |
F4 N1 APARTMENT | 4.50 | 29.50 | 4.50 | 29.50 |
F4 N2 APARTMENT | 4.50 | 34.50 | 4.50 | 34.50 |
F4 S1 APARTMENT | 2.25 | 43.50 | 2.25 | 43.50 |
F4 S2 APARTMENT | 2.25 | 42.25 | 2.25 | 42.25 |
M SW APARTMENT | 0.75 | 28.25 | 0.75 | 28.25 |
M NW APARTMENT | 0.00 | 10.00 | 0.00 | 10.00 |
M SE APARTMENT | 0.25 | 21.00 | 0.25 | 21.00 |
M NE APARTMENT | 1.75 | 33.50 | 1.75 | 33.50 |
M N1 APARTMENT | 3.50 | 32.25 | 3.50 | 32.25 |
M N2 APARTMENT | 5.00 | 37.75 | 5.00 | 37.75 |
M S1 APARTMENT | 3.00 | 43.75 | 3.00 | 43.75 |
M S2 APARTMENT | 2.25 | 42.50 | 2.25 | 42.50 |
F6 SW APARTMENT | 1.75 | 30.00 | 1.75 | 30.00 |
F6 NW APARTMENT | 0.75 | 10.50 | 0.75 | 10.50 |
F6 SE APARTMENT | 0.50 | 22.75 | 0.50 | 22.75 |
F6 NE APARTMENT | 2.75 | 39.50 | 2.75 | 39.50 |
F6 N1 APARTMENT | 6.25 | 35.50 | 6.25 | 35.50 |
F6 N2 APARTMENT | 5.25 | 40.25 | 5.25 | 40.25 |
F6 S1 APARTMENT | 2.50 | 44.25 | 2.50 | 44.25 |
F6 S2 APARTMENT | 3.00 | 43.00 | 3.00 | 43.00 |
F7 SW APARTMENT | 0.75 | 31.75 | 0.75 | 31.75 |
F7 NW APARTMENT | 0.25 | 10.75 | 0.25 | 10.75 |
F7 SE APARTMENT | 1.50 | 23.25 | 1.50 | 23.25 |
F7 NE APARTMENT | 2.00 | 43.00 | 2.00 | 43.00 |
F7 N1 APARTMENT | 4.50 | 37.75 | 4.50 | 37.75 |
F7 N2 APARTMENT | 3.25 | 42.25 | 3.25 | 42.25 |
F7 S1 APARTMENT | 4.00 | 44.25 | 4.00 | 44.25 |
F7 S2 APARTMENT | 4.50 | 42.75 | 4.50 | 42.75 |
F8 SW APARTMENT | 0.50 | 32.25 | 0.50 | 32.25 |
F8 NW APARTMENT | 0.00 | 12.00 | 0.00 | 12.00 |
F8 SE APARTMENT | 0.50 | 23.00 | 0.50 | 23.00 |
F8 NE APARTMENT | 1.25 | 47.00 | 1.25 | 47.00 |
F8 N1 APARTMENT | 4.75 | 39.50 | 4.75 | 39.50 |
F8 N2 APARTMENT | 3.75 | 43.75 | 3.75 | 43.75 |
F8 S1 APARTMENT | 2.75 | 42.75 | 2.75 | 42.75 |
F8 S2 APARTMENT | 3.25 | 41.75 | 3.25 | 41.75 |
F9 SW APARTMENT | 0.75 | 27.00 | 0.75 | 27.00 |
F9 NW APARTMENT | 0.00 | 11.25 | 0.00 | 11.25 |
F9 SE APARTMENT | 0.75 | 22.00 | 0.75 | 22.00 |
F9 NE APARTMENT | 1.00 | 59.50 | 1.00 | 59.50 |
F9 N1 APARTMENT | 2.25 | 32.75 | 2.25 | 32.75 |
F9 N2 APARTMENT | 3.25 | 34.75 | 3.25 | 34.75 |
F9 S1 APARTMENT | 2.75 | 37.00 | 2.75 | 37.00 |
F9 S2 APARTMENT | 4.75 | 35.00 | 4.75 | 35.00 |
T SW APARTMENT | 0.00 | 15.50 | 0.00 | 15.50 |
T NW APARTMENT | 0.00 | 17.75 | 0.00 | 17.75 |
T SE APARTMENT | 0.00 | 14.00 | 0.00 | 14.00 |
T NE APARTMENT | 0.25 | 36.50 | 0.25 | 36.50 |
T N1 APARTMENT | 2.75 | 32.00 | 2.75 | 32.00 |
T N2 APARTMENT | 1.50 | 29.50 | 1.50 | 29.50 |
T S1 APARTMENT | 0.50 | 16.00 | 0.50 | 16.00 |
T S2 APARTMENT | 0.50 | 16.00 | 0.50 | 16.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 144.75 | 147.50 | 143.00 | 147.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.133 | 0.000 | 0.260 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.132 | 0.000 | 0.254 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.518 | 0.151 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.132 | 0.000 | 0.254 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.080 | 0.000 | 0.249 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.249 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.080 | 0.000 | 0.258 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.080 | 0.000 | 0.258 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.191 | 0.000 | 0.312 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.190 | 0.000 | 0.307 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.191 | 0.000 | 0.313 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.190 | 0.000 | 0.307 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.115 | 0.000 | 0.303 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.303 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.115 | 0.000 | 0.311 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.115 | 0.000 | 0.311 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.226 | 0.000 | 0.346 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.225 | 0.000 | 0.342 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.226 | 0.000 | 0.347 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.225 | 0.000 | 0.342 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.136 | 0.000 | 0.339 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.136 | 0.000 | 0.339 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.136 | 0.000 | 0.345 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.136 | 0.000 | 0.345 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.252 | 0.000 | 0.361 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.252 | 0.000 | 0.358 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.252 | 0.000 | 0.362 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.252 | 0.000 | 0.358 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.152 | 0.000 | 0.355 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.152 | 0.000 | 0.355 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.152 | 0.000 | 0.360 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.152 | 0.000 | 0.361 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.274 | 0.000 | 0.382 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.274 | 0.000 | 0.378 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.274 | 0.000 | 0.382 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.274 | 0.000 | 0.378 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.165 | 0.000 | 0.376 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.165 | 0.000 | 0.376 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.165 | 0.000 | 0.381 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.165 | 0.000 | 0.381 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.293 | 0.000 | 0.399 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.292 | 0.000 | 0.396 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.293 | 0.000 | 0.400 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.292 | 0.000 | 0.396 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.176 | 0.000 | 0.393 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.393 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.177 | 0.000 | 0.398 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.177 | 0.000 | 0.398 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.309 | 0.000 | 0.413 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.309 | 0.000 | 0.410 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.309 | 0.000 | 0.414 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.309 | 0.000 | 0.410 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.186 | 0.000 | 0.407 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.186 | 0.000 | 0.407 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.187 | 0.000 | 0.413 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.187 | 0.000 | 0.413 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.324 | 0.000 | 0.429 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.324 | 0.000 | 0.425 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.324 | 0.000 | 0.429 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.324 | 0.000 | 0.425 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.195 | 0.000 | 0.422 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.195 | 0.000 | 0.422 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.196 | 0.000 | 0.428 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.196 | 0.000 | 0.428 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.442 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.438 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.443 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.337 | 0.000 | 0.439 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.204 | 0.000 | 0.436 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.204 | 0.000 | 0.436 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.204 | 0.000 | 0.441 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.204 | 0.000 | 0.441 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.350 | 0.000 | 0.451 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.350 | 0.000 | 0.449 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.350 | 0.000 | 0.452 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.350 | 0.000 | 0.449 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.211 | 0.000 | 0.446 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.211 | 0.000 | 0.446 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.211 | 0.000 | 0.451 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.211 | 0.000 | 0.451 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.503 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 702.48 | 22275.35 | 24-JAN-02:15 | 22275.35 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1232.08 | 22655.87 | 26-MAY-02:45 | 113893.96 | 10-JAN-23:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
ElectricityPurchased:Plant | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
Cogeneration:ElectricityPurchased | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
ElectricityNet:Plant | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
Cogeneration:ElectricityNet | 3001.91 | 60216.36 | 26-MAY-02:45 | 185892.94 | 05-JAN-20:00 |
ExteriorLights:Electricity | 168.22 | 0.00 | 01-JAN-08:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.22 | 0.00 | 01-JAN-08:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 702.48 | 22275.35 | 24-JAN-02:15 | 22275.35 | 01-JAN-00:15 |
Cooling:Electricity | 245.02 | 0.00 | 01-JAN-00:15 | 65477.56 | 17-JUL-16:00 |
Heating:Electricity | 263.76 | 0.00 | 20-FEB-15:30 | 91080.75 | 10-JAN-23:15 |
Electricity:Plant | 54.09 | 36.93 | 01-APR-17:30 | 3742.71 | 07-SEP-15:45 |
HeatRejection:Electricity | 8.68 | 0.00 | 01-JAN-00:15 | 2289.48 | 07-SEP-15:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 45.41 | 36.93 | 01-APR-17:30 | 1453.23 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 2181.08 | 9260.51 | 20-FEB-24:00 | 318617.55 | 06-JAN-06:45 |
Gas:Plant | 2181.08 | 9260.51 | 20-FEB-24:00 | 318617.55 | 06-JAN-06:45 |
WaterSystems:Gas | 1278.59 | 9260.51 | 01-JAN-00:15 | 92610.36 | 20-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1278.59 | 9260.51 | 01-JAN-00:15 | 92610.36 | 20-FEB-08:00 |
Heating:Gas | 902.48 | 0.00 | 01-JAN-13:00 | 245754.71 | 10-JAN-23:15 |
Boiler:Heating:Gas | 902.48 | 0.00 | 01-JAN-13:00 | 245754.71 | 10-JAN-23:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 964.33 | 0.00 | 01-JAN-00:15 | 292918.16 | 07-SEP-15:45 |
PlantLoopCoolingDemand:HVAC | 964.33 | 0.00 | 01-JAN-00:15 | 292918.16 | 07-SEP-15:45 |
CoolingCoils:PlantLoopCoolingDemand | 964.33 | 0.00 | 01-JAN-00:15 | 292918.16 | 07-SEP-15:45 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5643.30 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:45 |
Water:Plant | 5643.30 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:45 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5643.30 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:45 |
MainsWater:Plant | 5643.30 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:45 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 864.78 | 0.00 | 01-JAN-00:15 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 864.78 | 0.00 | 01-JAN-00:15 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1737.77 | 527.52 | 20-AUG-01:45 | 249934.32 | 06-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 972.78 | 527.52 | 20-AUG-01:45 | 66040.54 | 20-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 972.78 | 527.52 | 20-AUG-01:45 | 66040.54 | 20-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4852.74 | 6616.08 | 03-MAY-01:15 | 704041.57 | 10-JAN-23:00 |
EnergyTransfer:Building | 1415.17 | 3438.43 | 01-APR-17:30 | 209205.43 | 17-NOV-13:30 |
EnergyTransfer:Zone:G SW APARTMENT | 15.69 | 0.02 | 21-OCT-04:15 | 2621.40 | 11-JAN-08:15 |
Heating:EnergyTransfer | 636.74 | 0.00 | 28-FEB-15:30 | 209205.43 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 7.84 | 0.00 | 01-JAN-10:00 | 2621.40 | 11-JAN-08:15 |
Cooling:EnergyTransfer | 778.43 | 0.00 | 04-JAN-01:45 | 186562.64 | 19-MAY-16:45 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.85 | 0.00 | 01-JAN-00:15 | 2589.52 | 30-AUG-15:30 |
EnergyTransfer:Zone:G NW APARTMENT | 16.42 | 0.09 | 01-JUN-02:00 | 2652.11 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 11.63 | 0.00 | 14-JAN-15:30 | 2652.11 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.79 | 0.00 | 01-JAN-00:15 | 2339.17 | 20-JUL-18:30 |
EnergyTransfer:Zone:OFFICE | 20.84 | 0.03 | 13-DEC-10:00 | 3394.15 | 01-SEP-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 7.56 | 0.00 | 01-JAN-09:45 | 2681.41 | 11-JAN-08:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 13.28 | 0.00 | 01-JAN-00:15 | 3394.15 | 01-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 16.42 | 0.01 | 21-AUG-08:30 | 2652.11 | 11-JAN-08:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 11.31 | 0.00 | 20-FEB-14:30 | 2652.11 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.10 | 0.00 | 01-JAN-00:15 | 1631.80 | 23-JUN-09:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 10.48 | 0.03 | 02-JUL-08:30 | 1734.12 | 27-JAN-08:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 6.16 | 0.00 | 01-JAN-18:45 | 1734.12 | 27-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.31 | 0.00 | 01-JAN-00:15 | 1103.62 | 20-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 10.49 | 0.04 | 29-SEP-13:30 | 1733.00 | 27-JAN-08:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 6.16 | 0.00 | 01-JAN-18:45 | 1733.00 | 27-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.32 | 0.00 | 01-JAN-00:15 | 1088.16 | 20-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.13 | 0.00 | 27-FEB-13:45 | 1784.40 | 30-AUG-12:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 3.16 | 0.00 | 01-JAN-00:15 | 1692.32 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.98 | 0.00 | 01-JAN-03:45 | 1784.40 | 30-AUG-12:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.19 | 0.05 | 29-JUL-09:15 | 1843.22 | 30-AUG-12:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 3.09 | 0.00 | 01-JAN-00:15 | 1686.45 | 11-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.10 | 0.00 | 01-JAN-04:00 | 1843.22 | 30-AUG-12:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 19.16 | 0.01 | 16-FEB-11:15 | 3376.20 | 30-AUG-15:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 6.38 | 0.00 | 01-JAN-00:15 | 2611.59 | 06-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 12.78 | 0.00 | 01-JAN-03:45 | 3376.20 | 30-AUG-15:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 18.31 | 0.00 | 31-MAY-00:15 | 3020.69 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 10.79 | 0.00 | 01-JAN-18:15 | 2686.16 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 7.52 | 0.00 | 01-JAN-00:15 | 3020.69 | 20-JUL-18:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 19.75 | 0.00 | 23-SEP-05:00 | 3287.16 | 30-AUG-13:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 5.91 | 0.00 | 01-JAN-00:15 | 2567.16 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 13.85 | 0.00 | 01-JAN-03:45 | 3287.16 | 30-AUG-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 18.48 | 0.05 | 23-NOV-22:45 | 2693.28 | 11-JAN-01:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 10.46 | 0.00 | 01-JAN-18:15 | 2693.28 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 8.02 | 0.00 | 01-JAN-00:15 | 2213.96 | 23-JUN-09:00 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 11.29 | 0.01 | 20-MAR-09:45 | 1849.98 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 4.47 | 0.00 | 01-JAN-16:15 | 1849.98 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 6.83 | 0.00 | 01-JAN-00:15 | 1568.96 | 20-JUL-18:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 11.29 | 0.01 | 02-AUG-17:00 | 1852.15 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 4.46 | 0.00 | 01-JAN-16:15 | 1852.15 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 6.83 | 0.00 | 01-JAN-00:15 | 1551.07 | 20-JUL-18:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 15.03 | 0.05 | 28-MAY-11:15 | 2353.74 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 2.01 | 0.00 | 01-JAN-00:15 | 1440.66 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 13.02 | 0.00 | 04-JAN-00:30 | 2353.74 | 31-AUG-13:00 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 15.11 | 0.29 | 11-MAR-06:00 | 2375.97 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 2.00 | 0.00 | 01-JAN-00:15 | 1437.95 | 11-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 13.11 | 0.00 | 04-JAN-00:30 | 2375.97 | 31-AUG-13:00 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 19.80 | 0.03 | 24-OCT-01:00 | 3402.13 | 19-MAY-16:45 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 6.41 | 0.00 | 01-JAN-00:15 | 2691.77 | 06-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 13.40 | 0.00 | 01-JAN-05:30 | 3402.13 | 19-MAY-16:45 |
EnergyTransfer:Zone:F3 NW APARTMENT | 18.85 | 0.07 | 18-OCT-05:45 | 3011.80 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 10.87 | 0.00 | 01-JAN-18:15 | 2850.36 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 7.98 | 0.00 | 01-JAN-00:15 | 3011.80 | 20-JUL-18:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 20.14 | 0.03 | 21-APR-22:30 | 3135.80 | 30-AUG-13:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 6.20 | 0.00 | 01-JAN-00:15 | 2685.02 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 13.94 | 0.00 | 01-JAN-05:30 | 3135.80 | 30-AUG-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 19.01 | 0.01 | 17-MAR-16:00 | 2852.77 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 10.54 | 0.00 | 01-JAN-18:15 | 2852.77 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 8.47 | 0.00 | 01-JAN-00:15 | 2272.12 | 23-JUN-09:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 11.75 | 0.02 | 23-MAR-09:30 | 2145.66 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 4.28 | 0.00 | 01-JAN-14:15 | 2145.66 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.48 | 0.00 | 01-JAN-00:45 | 1611.35 | 30-JUN-19:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 11.76 | 0.01 | 16-JUL-06:30 | 2148.57 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 4.27 | 0.00 | 01-JAN-14:00 | 2148.57 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.48 | 0.00 | 01-JAN-00:45 | 1593.54 | 30-JUN-19:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 16.03 | 0.03 | 24-NOV-14:15 | 2395.35 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 1.89 | 0.00 | 01-JAN-00:15 | 1580.22 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 14.13 | 0.00 | 04-JAN-01:45 | 2395.35 | 31-AUG-13:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 16.07 | 0.02 | 24-NOV-15:15 | 2406.93 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 1.89 | 0.00 | 01-JAN-00:15 | 1576.87 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 14.17 | 0.00 | 04-JAN-01:45 | 2406.93 | 31-AUG-13:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 20.14 | 0.07 | 11-SEP-23:00 | 3409.89 | 19-MAY-16:45 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 6.83 | 0.00 | 01-JAN-00:15 | 2886.95 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 13.32 | 0.00 | 01-JAN-05:15 | 3409.89 | 19-MAY-16:45 |
EnergyTransfer:Zone:F4 NW APARTMENT | 19.42 | 0.01 | 23-OCT-06:45 | 3052.45 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 11.41 | 0.00 | 01-JAN-18:15 | 3052.45 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 8.00 | 0.00 | 01-JAN-00:15 | 3021.06 | 20-JUL-18:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 20.44 | 0.01 | 16-NOV-13:00 | 3125.04 | 30-AUG-13:15 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 6.67 | 0.00 | 01-JAN-00:15 | 2886.37 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 13.77 | 0.00 | 01-JAN-05:15 | 3125.04 | 30-AUG-13:15 |
EnergyTransfer:Zone:F4 NE APARTMENT | 19.57 | 0.00 | 14-MAR-14:45 | 3052.72 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 11.06 | 0.00 | 01-JAN-18:15 | 3052.72 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 8.50 | 0.00 | 01-JAN-00:15 | 2295.12 | 23-JUN-09:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 12.06 | 0.01 | 31-MAY-08:15 | 2418.99 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 4.46 | 0.00 | 01-JAN-00:15 | 2418.99 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 7.59 | 0.00 | 01-JAN-00:30 | 1625.19 | 30-JUN-19:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 12.06 | 0.02 | 27-JUN-11:15 | 2421.79 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 4.46 | 0.00 | 01-JAN-00:15 | 2421.79 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 7.60 | 0.00 | 01-JAN-00:30 | 1607.47 | 30-JUN-19:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 16.24 | 0.10 | 06-JUN-09:15 | 2411.17 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 2.00 | 0.00 | 01-JAN-00:15 | 1845.21 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 14.24 | 0.00 | 04-JAN-01:45 | 2411.17 | 31-AUG-12:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 16.26 | 0.02 | 28-APR-13:15 | 2417.34 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 2.00 | 0.00 | 01-JAN-00:15 | 1850.16 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 14.26 | 0.00 | 04-JAN-01:45 | 2417.34 | 31-AUG-12:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 20.43 | 0.11 | 14-JAN-21:15 | 3438.07 | 19-MAY-16:45 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 7.17 | 0.00 | 01-JAN-00:15 | 3039.84 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 13.26 | 0.00 | 01-JAN-05:00 | 3438.07 | 19-MAY-16:45 |
EnergyTransfer:Zone:M NW APARTMENT | 19.85 | 0.01 | 11-MAR-17:00 | 3204.79 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 11.78 | 0.00 | 01-JAN-18:15 | 3204.79 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 8.08 | 0.00 | 01-JAN-00:15 | 3048.61 | 20-JUL-18:30 |
EnergyTransfer:Zone:M SE APARTMENT | 20.70 | 0.01 | 11-SEP-01:30 | 3155.71 | 30-AUG-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 7.00 | 0.00 | 01-JAN-00:15 | 3038.70 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 13.69 | 0.00 | 01-JAN-05:00 | 3155.71 | 30-AUG-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 19.98 | 0.00 | 13-MAR-18:45 | 3203.48 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 11.41 | 0.00 | 01-JAN-18:15 | 3203.48 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 8.57 | 0.00 | 01-JAN-00:15 | 2325.81 | 23-JUN-09:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 12.31 | 0.05 | 25-FEB-10:45 | 2667.04 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 4.57 | 0.00 | 01-JAN-00:15 | 2667.04 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 7.74 | 0.00 | 01-JAN-00:30 | 1660.15 | 30-JUN-19:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 12.31 | 0.02 | 22-JUL-08:15 | 2668.21 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 4.56 | 0.00 | 01-JAN-00:15 | 2668.21 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 7.75 | 0.00 | 01-JAN-00:30 | 1642.53 | 30-JUN-19:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 16.37 | 0.17 | 12-FEB-10:15 | 2447.59 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 2.09 | 0.00 | 01-JAN-00:15 | 1987.15 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 14.28 | 0.00 | 04-JAN-01:30 | 2447.59 | 31-AUG-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 16.39 | 0.03 | 16-FEB-22:45 | 2456.25 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 2.09 | 0.00 | 01-JAN-00:15 | 1989.22 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 14.30 | 0.00 | 04-JAN-01:30 | 2456.25 | 31-AUG-12:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 20.41 | 0.00 | 14-JAN-14:45 | 3393.11 | 19-MAY-16:45 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 7.98 | 0.00 | 01-JAN-00:15 | 3231.38 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 12.42 | 0.00 | 01-JAN-03:45 | 3393.11 | 19-MAY-16:45 |
EnergyTransfer:Zone:F6 NW APARTMENT | 20.45 | 0.02 | 18-OCT-01:30 | 3396.11 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 12.88 | 0.00 | 01-JAN-18:15 | 3396.11 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 7.57 | 0.00 | 01-JAN-00:15 | 3008.97 | 30-JUN-19:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 20.64 | 0.01 | 04-DEC-15:00 | 3229.32 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 7.81 | 0.00 | 01-JAN-00:15 | 3229.32 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 12.83 | 0.00 | 01-JAN-03:45 | 3113.66 | 30-AUG-13:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 20.54 | 0.00 | 02-OCT-13:15 | 3393.78 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 12.49 | 0.00 | 01-JAN-18:15 | 3393.78 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 8.05 | 0.00 | 01-JAN-00:15 | 2282.38 | 23-JUN-09:15 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 12.39 | 0.13 | 10-SEP-14:45 | 2927.81 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 5.21 | 0.00 | 01-JAN-16:15 | 2927.81 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.19 | 0.00 | 01-JAN-00:15 | 1620.66 | 30-JUN-19:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 12.39 | 0.00 | 30-MAY-09:15 | 2928.78 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 5.20 | 0.00 | 01-JAN-16:15 | 2928.78 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.19 | 0.00 | 01-JAN-00:15 | 1603.20 | 30-JUN-19:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 15.76 | 0.11 | 23-JAN-18:30 | 2406.75 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 2234.52 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 13.35 | 0.00 | 04-JAN-00:30 | 2406.75 | 31-AUG-12:45 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 15.77 | 0.05 | 17-MAR-11:15 | 2416.69 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 2235.81 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 13.37 | 0.00 | 04-JAN-00:30 | 2416.69 | 31-AUG-12:45 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 20.54 | 0.00 | 11-JUL-04:00 | 3387.59 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 8.64 | 0.00 | 01-JAN-00:15 | 3387.59 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 11.90 | 0.00 | 01-JAN-01:00 | 3375.08 | 19-MAY-16:45 |
EnergyTransfer:Zone:F7 NW APARTMENT | 21.00 | 0.01 | 17-APR-02:30 | 3549.35 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 13.71 | 0.00 | 01-JAN-18:30 | 3549.35 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 7.29 | 0.00 | 01-JAN-00:15 | 3005.14 | 30-JUN-19:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 20.74 | 0.03 | 01-OCT-00:45 | 3384.58 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 8.45 | 0.00 | 01-JAN-00:15 | 3384.58 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 12.29 | 0.00 | 01-JAN-01:00 | 3098.07 | 30-AUG-13:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 21.05 | 0.04 | 08-NOV-09:00 | 3546.17 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 13.30 | 0.00 | 01-JAN-18:30 | 3546.17 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 7.75 | 0.00 | 01-JAN-00:15 | 2266.60 | 23-JUN-09:15 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 12.54 | 0.02 | 26-AUG-08:45 | 3172.75 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 5.68 | 0.00 | 01-JAN-16:15 | 3172.75 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 6.86 | 0.00 | 01-JAN-00:15 | 1609.20 | 23-JUN-19:45 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 12.54 | 0.01 | 31-AUG-20:30 | 3173.28 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 5.67 | 0.00 | 01-JAN-16:15 | 3173.28 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 6.87 | 0.00 | 01-JAN-00:15 | 1593.29 | 23-JUN-19:45 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 15.41 | 0.00 | 07-SEP-11:30 | 2489.28 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 2.67 | 0.00 | 01-JAN-00:15 | 2489.28 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 12.74 | 0.00 | 03-JAN-24:00 | 2392.04 | 31-AUG-12:45 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 15.44 | 0.07 | 25-NOV-22:15 | 2496.16 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 2.67 | 0.00 | 01-JAN-00:15 | 2496.16 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 12.76 | 0.00 | 03-JAN-24:00 | 2401.99 | 31-AUG-12:45 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 20.78 | 0.01 | 11-SEP-12:45 | 3536.01 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 9.31 | 0.00 | 01-JAN-00:15 | 3536.01 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 11.47 | 0.00 | 01-JAN-01:00 | 3370.16 | 19-MAY-16:45 |
EnergyTransfer:Zone:F8 NW APARTMENT | 21.64 | 0.02 | 02-APR-17:45 | 3728.49 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 14.53 | 0.00 | 01-JAN-18:45 | 3728.49 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 7.10 | 0.00 | 01-JAN-00:15 | 2998.77 | 30-JUN-19:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 20.96 | 0.02 | 31-MAY-10:00 | 3532.13 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 9.11 | 0.00 | 01-JAN-00:15 | 3532.13 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 11.85 | 0.00 | 01-JAN-01:00 | 3095.47 | 30-AUG-13:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 21.65 | 0.01 | 29-MAY-19:45 | 3733.85 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 14.10 | 0.00 | 01-JAN-18:45 | 3733.85 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 7.54 | 0.00 | 01-JAN-00:15 | 2264.61 | 23-JUN-09:15 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 12.80 | 0.05 | 10-SEP-14:30 | 3399.27 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 6.19 | 0.00 | 01-JAN-16:45 | 3399.27 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 6.62 | 0.00 | 01-JAN-00:15 | 1615.11 | 23-JUN-19:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 12.80 | 0.01 | 11-MAR-20:45 | 3399.61 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 6.18 | 0.00 | 01-JAN-17:00 | 3399.61 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 6.62 | 0.00 | 01-JAN-00:15 | 1599.34 | 23-JUN-19:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 15.19 | 0.05 | 18-AUG-16:30 | 2775.38 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 2.98 | 0.00 | 01-JAN-00:15 | 2775.38 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 12.22 | 0.00 | 03-JAN-06:00 | 2390.36 | 31-AUG-12:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 15.21 | 0.12 | 03-MAR-06:30 | 2777.93 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 2.98 | 0.00 | 01-JAN-00:15 | 2777.93 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 12.23 | 0.00 | 03-JAN-06:00 | 2400.35 | 31-AUG-12:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 21.84 | 0.02 | 08-JUN-09:15 | 3772.60 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 10.80 | 0.00 | 01-JAN-00:15 | 3772.60 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 11.04 | 0.00 | 01-JAN-00:45 | 3458.81 | 19-MAY-16:45 |
EnergyTransfer:Zone:F9 NW APARTMENT | 23.33 | 0.03 | 11-SEP-04:00 | 3954.58 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 16.31 | 0.00 | 12-FEB-18:15 | 3954.58 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 7.02 | 0.00 | 01-JAN-00:15 | 3089.42 | 30-JUN-19:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 21.93 | 0.01 | 20-AUG-02:00 | 3767.88 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 10.55 | 0.00 | 01-JAN-00:15 | 3767.88 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 11.38 | 0.00 | 01-JAN-00:45 | 3155.68 | 30-AUG-13:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 23.24 | 0.04 | 16-OCT-01:45 | 3942.91 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 15.82 | 0.00 | 20-FEB-17:15 | 3942.91 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 7.42 | 0.00 | 01-JAN-00:15 | 2288.25 | 23-JUN-09:15 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 13.84 | 0.04 | 21-APR-23:15 | 3640.73 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 7.47 | 0.00 | 01-JAN-17:15 | 3640.73 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.36 | 0.00 | 01-JAN-00:15 | 1698.49 | 23-JUN-19:45 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 13.85 | 0.03 | 07-SEP-11:00 | 3640.76 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 7.47 | 0.00 | 01-JAN-17:15 | 3640.76 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.37 | 0.00 | 01-JAN-00:15 | 1682.48 | 23-JUN-19:45 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 15.30 | 0.07 | 15-FEB-08:45 | 3107.11 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 3.79 | 0.00 | 01-JAN-00:15 | 3107.11 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 11.51 | 0.00 | 03-JAN-03:30 | 2430.94 | 31-AUG-13:00 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 15.31 | 0.03 | 12-MAR-04:30 | 3109.21 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 3.79 | 0.00 | 01-JAN-00:15 | 3109.21 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 11.52 | 0.00 | 03-JAN-03:30 | 2442.08 | 31-AUG-13:00 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 29.94 | 0.08 | 27-MAR-20:00 | 4589.70 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 18.60 | 0.00 | 01-JAN-10:45 | 4589.70 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 11.34 | 0.00 | 01-JAN-00:15 | 4215.06 | 30-AUG-15:30 |
EnergyTransfer:Zone:T NW APARTMENT | 30.95 | 0.00 | 20-OCT-18:00 | 4738.95 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 23.52 | 0.00 | 23-FEB-15:45 | 4738.95 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 7.43 | 0.00 | 01-JAN-00:15 | 3706.06 | 14-JUL-18:00 |
EnergyTransfer:Zone:T SE APARTMENT | 29.33 | 0.02 | 12-MAY-02:15 | 4594.72 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 18.09 | 0.00 | 01-JAN-10:00 | 4594.72 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.24 | 0.00 | 01-JAN-00:15 | 3865.40 | 30-AUG-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 30.15 | 0.01 | 05-APR-16:00 | 4744.52 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 22.73 | 0.00 | 25-FEB-18:15 | 4744.52 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.42 | 0.00 | 01-JAN-00:15 | 2826.92 | 23-JUN-09:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 19.66 | 0.11 | 24-NOV-12:00 | 3809.79 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 13.60 | 0.00 | 01-JAN-18:45 | 3809.79 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.06 | 0.00 | 01-JAN-00:15 | 2217.99 | 23-JUN-16:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 19.66 | 0.01 | 16-OCT-06:00 | 3808.70 | 17-NOV-13:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 13.59 | 0.00 | 01-JAN-18:45 | 3808.70 | 17-NOV-13:30 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.07 | 0.00 | 01-JAN-00:15 | 2217.39 | 23-JUN-16:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.60 | 0.01 | 19-DEC-14:00 | 3352.67 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 9.38 | 0.00 | 01-JAN-09:30 | 3352.67 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.22 | 0.00 | 01-JAN-00:30 | 3247.97 | 30-AUG-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.63 | 0.00 | 10-MAR-13:15 | 3352.04 | 17-NOV-13:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 9.38 | 0.00 | 01-JAN-09:30 | 3352.04 | 17-NOV-13:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.24 | 0.00 | 01-JAN-00:30 | 3259.39 | 30-AUG-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1694.01 | 527.52 | 20-AUG-01:45 | 250499.95 | 06-JAN-07:15 |
WaterSystems:EnergyTransfer | 972.77 | 527.52 | 20-AUG-01:45 | 66033.79 | 20-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 972.77 | 527.52 | 20-AUG-01:45 | 66033.79 | 20-FEB-08:00 |
EnergyTransfer:HVAC | 1743.55 | 0.00 | 01-APR-17:30 | 288476.89 | 10-JAN-23:15 |
CoolingCoils:EnergyTransfer | 739.42 | 0.00 | 01-JAN-00:15 | 230418.87 | 07-SEP-15:45 |
HeatingCoils:EnergyTransfer | 1004.13 | 0.00 | 20-FEB-15:30 | 288476.89 | 10-JAN-23:15 |
PlantLoopHeatingDemand:HVAC | 764.99 | 0.00 | 20-FEB-15:30 | 197788.05 | 10-JAN-23:15 |
HeatingCoils:PlantLoopHeatingDemand | 764.99 | 0.00 | 20-FEB-15:30 | 197788.05 | 10-JAN-23:15 |
Boilers:EnergyTransfer | 721.24 | 0.00 | 01-JAN-13:00 | 196603.77 | 10-JAN-23:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 7.836 | -7.853 | 0.000 | 0.000 | 3.857 | 2.413 | 12.213 | 20.833 | 0.000 | 0.138 | 0.000 | 0.000 | -14.291 | 0.000 | -7.878 | -17.267 |
G NW APARTMENT | 11.631 | -4.789 | 0.000 | 0.000 | 3.899 | 2.413 | 12.213 | 9.267 | 0.000 | 0.138 | 0.000 | 0.000 | -14.913 | 0.000 | -7.463 | -12.396 |
OFFICE | 7.556 | -13.284 | 0.000 | 0.000 | 0.531 | 21.954 | 7.547 | 20.970 | 0.000 | 0.072 | 0.000 | 0.000 | -14.115 | 0.000 | -5.118 | -26.113 |
G NE APARTMENT | 11.314 | -5.102 | 0.000 | 0.000 | 3.915 | 2.413 | 12.213 | 9.378 | 0.000 | 0.138 | 0.000 | 0.000 | -14.513 | 0.000 | -7.461 | -12.295 |
G N1 APARTMENT | 6.163 | -4.313 | 0.000 | 0.000 | 3.917 | 2.413 | 12.213 | 3.048 | 0.000 | 0.109 | 0.000 | 0.000 | -9.317 | 0.000 | -5.257 | -8.976 |
G N2 APARTMENT | 6.164 | -4.324 | 0.000 | 0.000 | 3.918 | 2.413 | 12.213 | 3.046 | 0.000 | 0.109 | 0.000 | 0.000 | -9.314 | 0.000 | -5.258 | -8.967 |
G S1 APARTMENT | 3.156 | -7.977 | 0.000 | 0.000 | 3.852 | 2.413 | 12.213 | 14.814 | 0.000 | 0.109 | 0.001 | 0.000 | -8.729 | 0.000 | -5.752 | -14.098 |
G S2 APARTMENT | 3.092 | -8.102 | 0.000 | 0.000 | 3.849 | 2.413 | 12.213 | 14.800 | 0.000 | 0.109 | 0.001 | 0.000 | -8.738 | 0.000 | -5.780 | -13.856 |
F2 SW APARTMENT | 6.380 | -12.782 | 0.000 | 0.000 | 3.790 | 2.413 | 12.213 | 20.092 | 0.000 | 0.185 | 0.001 | 0.000 | -15.199 | 0.000 | -10.896 | -6.195 |
F2 NW APARTMENT | 10.788 | -7.521 | 0.000 | 0.000 | 3.859 | 2.413 | 12.213 | 8.839 | 0.000 | 0.184 | 0.000 | 0.000 | -15.707 | 0.000 | -10.351 | -4.716 |
F2 SE APARTMENT | 5.906 | -13.845 | 0.000 | 0.000 | 3.788 | 2.413 | 12.213 | 20.271 | 0.000 | 0.185 | 0.001 | 0.000 | -14.941 | 0.000 | -10.995 | -4.995 |
F2 NE APARTMENT | 10.455 | -8.022 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 8.966 | 0.000 | 0.184 | 0.000 | 0.000 | -15.247 | 0.000 | -10.330 | -4.508 |
F2 N1 APARTMENT | 4.467 | -6.826 | 0.000 | 0.000 | 3.873 | 2.413 | 12.213 | 2.833 | 0.000 | 0.142 | 0.000 | 0.000 | -9.858 | 0.000 | -7.244 | -2.013 |
F2 N2 APARTMENT | 4.460 | -6.833 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 2.831 | 0.000 | 0.142 | 0.000 | 0.000 | -9.854 | 0.000 | -7.243 | -2.002 |
F2 S1 APARTMENT | 2.010 | -13.021 | 0.000 | 0.000 | 3.768 | 2.413 | 12.213 | 14.318 | 0.000 | 0.142 | 0.001 | 0.000 | -9.305 | 0.000 | -7.906 | -4.632 |
F2 S2 APARTMENT | 1.998 | -13.109 | 0.000 | 0.000 | 3.766 | 2.413 | 12.213 | 14.313 | 0.000 | 0.142 | 0.000 | 0.000 | -9.309 | 0.000 | -7.917 | -4.511 |
F3 SW APARTMENT | 6.407 | -13.396 | 0.000 | 0.000 | 3.783 | 2.413 | 12.213 | 19.801 | 0.000 | 0.229 | 0.001 | 0.000 | -15.476 | 0.000 | -12.575 | -3.398 |
F3 NW APARTMENT | 10.873 | -7.976 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 8.689 | 0.000 | 0.229 | 0.000 | 0.000 | -15.981 | 0.000 | -11.975 | -2.339 |
F3 SE APARTMENT | 6.203 | -13.939 | 0.000 | 0.000 | 3.788 | 2.413 | 12.213 | 20.025 | 0.000 | 0.229 | 0.000 | 0.000 | -15.147 | 0.000 | -12.633 | -3.151 |
F3 NE APARTMENT | 10.538 | -8.474 | 0.000 | 0.000 | 3.870 | 2.413 | 12.213 | 8.827 | 0.000 | 0.228 | 0.000 | 0.000 | -15.499 | 0.000 | -11.949 | -2.166 |
F3 N1 APARTMENT | 4.277 | -7.477 | 0.000 | 0.000 | 3.862 | 2.413 | 12.213 | 2.767 | 0.000 | 0.179 | 0.160 | 0.000 | -10.044 | 0.000 | -8.350 | -0.000 |
F3 N2 APARTMENT | 4.272 | -7.484 | 0.000 | 0.000 | 3.863 | 2.413 | 12.213 | 2.766 | 0.000 | 0.178 | 0.167 | 0.000 | -10.039 | 0.000 | -8.349 | -0.000 |
F3 S1 APARTMENT | 1.894 | -14.134 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 14.114 | 0.000 | 0.178 | 0.000 | 0.000 | -9.500 | 0.000 | -9.065 | -1.864 |
F3 S2 APARTMENT | 1.892 | -14.173 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 14.111 | 0.000 | 0.179 | 0.000 | 0.000 | -9.500 | 0.000 | -9.071 | -1.813 |
F4 SW APARTMENT | 6.827 | -13.316 | 0.000 | 0.000 | 3.785 | 2.413 | 12.213 | 19.629 | 0.000 | 0.250 | 0.000 | 0.000 | -15.613 | 0.000 | -13.642 | -2.545 |
F4 NW APARTMENT | 11.413 | -8.004 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 8.607 | 0.000 | 0.250 | 0.000 | 0.000 | -16.131 | 0.000 | -13.023 | -1.592 |
F4 SE APARTMENT | 6.667 | -13.768 | 0.000 | 0.000 | 3.791 | 2.413 | 12.213 | 19.866 | 0.000 | 0.250 | 0.000 | 0.000 | -15.262 | 0.000 | -13.694 | -2.475 |
F4 NE APARTMENT | 11.063 | -8.503 | 0.000 | 0.000 | 3.870 | 2.413 | 12.213 | 8.751 | 0.000 | 0.248 | 0.000 | 0.000 | -15.637 | 0.000 | -12.992 | -1.425 |
F4 N1 APARTMENT | 4.465 | -7.593 | 0.000 | 0.000 | 3.859 | 2.413 | 12.213 | 2.734 | 0.000 | 0.193 | 0.867 | 0.000 | -10.146 | 0.000 | -9.006 | -0.000 |
F4 N2 APARTMENT | 4.458 | -7.600 | 0.000 | 0.000 | 3.861 | 2.413 | 12.213 | 2.733 | 0.000 | 0.193 | 0.876 | 0.000 | -10.141 | 0.000 | -9.005 | -0.000 |
F4 S1 APARTMENT | 2.000 | -14.237 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 13.993 | 0.000 | 0.194 | 0.001 | 0.000 | -9.594 | 0.000 | -9.739 | -0.993 |
F4 S2 APARTMENT | 2.002 | -14.260 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 13.991 | 0.000 | 0.194 | 0.001 | 0.000 | -9.593 | 0.000 | -9.744 | -0.965 |
M SW APARTMENT | 7.165 | -13.260 | 0.000 | 0.000 | 3.787 | 2.413 | 12.213 | 19.496 | 0.000 | 0.266 | 0.001 | 0.000 | -15.724 | 0.000 | -14.668 | -1.688 |
M NW APARTMENT | 11.776 | -8.077 | 0.000 | 0.000 | 3.855 | 2.413 | 12.213 | 8.542 | 0.000 | 0.266 | 0.000 | 0.000 | -16.256 | 0.000 | -14.019 | -0.713 |
M SE APARTMENT | 7.001 | -13.694 | 0.000 | 0.000 | 3.793 | 2.413 | 12.213 | 19.739 | 0.000 | 0.266 | 0.001 | 0.000 | -15.362 | 0.000 | -14.721 | -1.648 |
M NE APARTMENT | 11.406 | -8.574 | 0.000 | 0.000 | 3.871 | 2.413 | 12.213 | 8.689 | 0.000 | 0.264 | 0.000 | 0.000 | -15.752 | 0.000 | -13.985 | -0.545 |
M N1 APARTMENT | 4.568 | -7.738 | 0.000 | 0.000 | 3.858 | 2.413 | 12.213 | 2.708 | 0.000 | 0.205 | 1.675 | 0.000 | -10.228 | 0.000 | -9.674 | -0.000 |
M N2 APARTMENT | 4.563 | -7.747 | 0.000 | 0.000 | 3.859 | 2.413 | 12.213 | 2.707 | 0.000 | 0.204 | 1.684 | 0.000 | -10.224 | 0.000 | -9.673 | -0.000 |
M S1 APARTMENT | 2.086 | -14.282 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 13.901 | 0.000 | 0.205 | 0.002 | 0.000 | -9.666 | 0.000 | -10.436 | -0.184 |
M S2 APARTMENT | 2.089 | -14.303 | 0.000 | 0.000 | 3.750 | 2.413 | 12.213 | 13.898 | 0.000 | 0.206 | 0.001 | 0.000 | -9.665 | 0.000 | -10.441 | -0.160 |
F6 SW APARTMENT | 7.981 | -12.425 | 0.000 | 0.000 | 3.798 | 2.413 | 12.213 | 19.429 | 0.000 | 0.279 | 0.000 | 0.000 | -15.740 | 0.000 | -15.489 | -2.460 |
F6 NW APARTMENT | 12.875 | -7.572 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 8.526 | 0.000 | 0.279 | 0.000 | 0.000 | -16.282 | 0.000 | -14.805 | -1.510 |
F6 SE APARTMENT | 7.806 | -12.830 | 0.000 | 0.000 | 3.804 | 2.413 | 12.213 | 19.676 | 0.000 | 0.280 | 0.000 | 0.000 | -15.373 | 0.000 | -15.549 | -2.440 |
F6 NE APARTMENT | 12.488 | -8.052 | 0.000 | 0.000 | 3.880 | 2.413 | 12.213 | 8.677 | 0.000 | 0.277 | 0.000 | 0.000 | -15.775 | 0.000 | -14.768 | -1.353 |
F6 N1 APARTMENT | 5.207 | -7.187 | 0.000 | 0.000 | 3.868 | 2.413 | 12.213 | 2.710 | 0.000 | 0.214 | 0.975 | 0.000 | -10.240 | 0.000 | -10.172 | -0.000 |
F6 N2 APARTMENT | 5.199 | -7.193 | 0.000 | 0.000 | 3.869 | 2.413 | 12.213 | 2.708 | 0.000 | 0.214 | 0.984 | 0.000 | -10.236 | 0.000 | -10.171 | -0.000 |
F6 S1 APARTMENT | 2.407 | -13.349 | 0.000 | 0.000 | 3.762 | 2.413 | 12.213 | 13.853 | 0.000 | 0.215 | 0.000 | 0.000 | -9.673 | 0.000 | -10.973 | -0.868 |
F6 S2 APARTMENT | 2.407 | -13.367 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 13.850 | 0.000 | 0.215 | 0.002 | 0.000 | -9.671 | 0.000 | -10.978 | -0.844 |
F7 SW APARTMENT | 8.637 | -11.898 | 0.000 | 0.000 | 3.806 | 2.413 | 12.213 | 19.366 | 0.000 | 0.291 | 0.000 | 0.000 | -15.767 | 0.000 | -16.200 | -2.861 |
F7 NW APARTMENT | 13.705 | -7.294 | 0.000 | 0.000 | 3.871 | 2.413 | 12.213 | 8.505 | 0.000 | 0.291 | 0.000 | 0.000 | -16.321 | 0.000 | -15.496 | -1.887 |
F7 SE APARTMENT | 8.448 | -12.287 | 0.000 | 0.000 | 3.812 | 2.413 | 12.213 | 19.615 | 0.000 | 0.291 | 0.000 | 0.000 | -15.395 | 0.000 | -16.263 | -2.848 |
F7 NE APARTMENT | 13.295 | -7.752 | 0.000 | 0.000 | 3.885 | 2.413 | 12.213 | 8.659 | 0.000 | 0.287 | 0.000 | 0.000 | -15.809 | 0.000 | -15.455 | -1.736 |
F7 N1 APARTMENT | 5.678 | -6.857 | 0.000 | 0.000 | 3.875 | 2.413 | 12.213 | 2.707 | 0.000 | 0.222 | 0.619 | 0.000 | -10.260 | 0.000 | -10.609 | -0.000 |
F7 N2 APARTMENT | 5.674 | -6.866 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 2.705 | 0.000 | 0.221 | 0.627 | 0.000 | -10.256 | 0.000 | -10.607 | -0.000 |
F7 S1 APARTMENT | 2.671 | -12.743 | 0.000 | 0.000 | 3.772 | 2.413 | 12.213 | 13.808 | 0.000 | 0.223 | 0.000 | 0.000 | -9.685 | 0.000 | -11.431 | -1.242 |
F7 S2 APARTMENT | 2.673 | -12.763 | 0.000 | 0.000 | 3.772 | 2.413 | 12.213 | 13.806 | 0.000 | 0.223 | 0.001 | 0.000 | -9.684 | 0.000 | -11.437 | -1.217 |
F8 SW APARTMENT | 9.313 | -11.467 | 0.000 | 0.000 | 3.813 | 2.413 | 12.213 | 19.313 | 0.000 | 0.304 | 0.000 | 0.000 | -15.788 | 0.000 | -16.865 | -3.248 |
F8 NW APARTMENT | 14.533 | -7.103 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 8.485 | 0.000 | 0.304 | 0.000 | 0.000 | -16.356 | 0.000 | -16.148 | -2.217 |
F8 SE APARTMENT | 9.110 | -11.848 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 19.564 | 0.000 | 0.305 | 0.000 | 0.000 | -15.413 | 0.000 | -16.931 | -3.233 |
F8 NE APARTMENT | 14.104 | -7.542 | 0.000 | 0.000 | 3.890 | 2.413 | 12.213 | 8.641 | 0.000 | 0.300 | 0.000 | 0.000 | -15.841 | 0.000 | -16.105 | -2.072 |
F8 N1 APARTMENT | 6.186 | -6.615 | 0.000 | 0.000 | 3.881 | 2.413 | 12.213 | 2.703 | 0.000 | 0.232 | 0.298 | 0.000 | -10.278 | 0.000 | -11.032 | -0.000 |
F8 N2 APARTMENT | 6.180 | -6.623 | 0.000 | 0.000 | 3.882 | 2.413 | 12.213 | 2.702 | 0.000 | 0.231 | 0.308 | 0.000 | -10.274 | 0.000 | -11.031 | -0.000 |
F8 S1 APARTMENT | 2.975 | -12.216 | 0.000 | 0.000 | 3.781 | 2.413 | 12.213 | 13.772 | 0.000 | 0.234 | 0.000 | 0.000 | -9.693 | 0.000 | -11.866 | -1.614 |
F8 S2 APARTMENT | 2.976 | -12.234 | 0.000 | 0.000 | 3.781 | 2.413 | 12.213 | 13.770 | 0.000 | 0.234 | 0.000 | 0.000 | -9.692 | 0.000 | -11.872 | -1.589 |
F9 SW APARTMENT | 10.804 | -11.037 | 0.000 | 0.000 | 3.822 | 2.413 | 12.213 | 19.293 | 0.000 | 0.317 | 0.001 | 0.000 | -15.765 | 0.000 | -17.438 | -4.622 |
F9 NW APARTMENT | 16.311 | -7.018 | 0.000 | 0.000 | 3.880 | 2.413 | 12.213 | 8.480 | 0.000 | 0.316 | 0.000 | 0.000 | -16.355 | 0.000 | -16.732 | -3.509 |
F9 SE APARTMENT | 10.551 | -11.382 | 0.000 | 0.000 | 3.828 | 2.413 | 12.213 | 19.545 | 0.000 | 0.317 | 0.001 | 0.000 | -15.387 | 0.000 | -17.510 | -4.589 |
F9 NE APARTMENT | 15.824 | -7.419 | 0.000 | 0.000 | 3.895 | 2.413 | 12.213 | 8.637 | 0.000 | 0.312 | 0.000 | 0.000 | -15.837 | 0.000 | -16.687 | -3.350 |
F9 N1 APARTMENT | 7.475 | -6.364 | 0.000 | 0.000 | 3.886 | 2.413 | 12.213 | 2.706 | 0.000 | 0.242 | 0.000 | 0.000 | -10.269 | 0.000 | -11.407 | -0.894 |
F9 N2 APARTMENT | 7.470 | -6.375 | 0.000 | 0.000 | 3.887 | 2.413 | 12.213 | 2.704 | 0.000 | 0.242 | 0.000 | 0.000 | -10.266 | 0.000 | -11.406 | -0.882 |
F9 S1 APARTMENT | 3.792 | -11.506 | 0.000 | 0.000 | 3.794 | 2.413 | 12.213 | 13.760 | 0.000 | 0.245 | 0.002 | 0.000 | -9.667 | 0.000 | -12.223 | -2.821 |
F9 S2 APARTMENT | 3.791 | -11.522 | 0.000 | 0.000 | 3.794 | 2.413 | 12.213 | 13.757 | 0.000 | 0.245 | 0.002 | 0.000 | -9.666 | 0.000 | -12.231 | -2.795 |
T SW APARTMENT | 18.602 | -11.342 | 0.000 | 0.000 | 3.858 | 2.413 | 12.213 | 19.062 | 0.000 | 0.326 | 0.000 | 0.000 | -15.147 | 0.000 | -17.920 | -12.064 |
T NW APARTMENT | 23.519 | -7.425 | 0.000 | 0.000 | 3.897 | 2.413 | 12.213 | 8.312 | 0.000 | 0.324 | 0.000 | 0.000 | -15.848 | 0.000 | -17.298 | -10.106 |
T SE APARTMENT | 18.091 | -11.239 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 19.343 | 0.000 | 0.326 | 0.000 | 0.000 | -14.805 | 0.000 | -18.003 | -12.202 |
T NE APARTMENT | 22.724 | -7.421 | 0.000 | 0.000 | 3.913 | 2.413 | 12.213 | 8.505 | 0.000 | 0.323 | 0.000 | 0.000 | -15.367 | 0.000 | -17.253 | -10.050 |
T N1 APARTMENT | 13.598 | -6.063 | 0.000 | 0.000 | 3.904 | 2.413 | 12.213 | 2.657 | 0.000 | 0.250 | 0.000 | 0.000 | -9.937 | 0.000 | -11.759 | -7.275 |
T N2 APARTMENT | 13.594 | -6.066 | 0.000 | 0.000 | 3.905 | 2.413 | 12.213 | 2.653 | 0.000 | 0.251 | 0.000 | 0.000 | -9.932 | 0.000 | -11.763 | -7.267 |
T S1 APARTMENT | 9.382 | -10.219 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 13.644 | 0.000 | 0.252 | 0.000 | 0.000 | -9.315 | 0.000 | -12.519 | -9.689 |
T S2 APARTMENT | 9.383 | -10.242 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 13.639 | 0.000 | 0.252 | 0.000 | 0.000 | -9.312 | 0.000 | -12.529 | -9.657 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 4.312 | 0.000 | 0.728 | 33.006 | 0.000 | -3.291 | 0.000 | -53.284 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.920 | 0.000 | 0.009 | 0.000 | 0.000 | -1.954 | 0.000 | -1.331 | -17.174 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.876 | 0.000 | 0.010 | 0.000 | 0.000 | -2.024 | 0.000 | -1.611 | -16.779 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.852 | 0.000 | 0.011 | 0.000 | 0.000 | -2.058 | 0.000 | -1.816 | -16.518 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.823 | 0.000 | 0.009 | 0.000 | 0.000 | -2.106 | 0.000 | -2.046 | -34.739 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.835 | 0.000 | 0.012 | 0.000 | 0.000 | -2.076 | 0.000 | -2.102 | -16.198 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.836 | 0.000 | 0.013 | 0.000 | 0.000 | -2.068 | 0.000 | -2.203 | -16.107 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.833 | 0.000 | 0.014 | 0.000 | 0.000 | -2.067 | 0.000 | -2.300 | -16.009 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.833 | 0.000 | 0.014 | 0.000 | 0.000 | -2.059 | 0.000 | -2.379 | -15.939 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.793 | 0.000 | 0.007 | 0.000 | 0.000 | -1.991 | 0.000 | -2.484 | -23.791 |
Total Facility | 636.717 | -778.433 | 0.000 | 0.000 | 303.697 | 416.414 | 980.287 | 924.865 | 0.000 | 19.044 | 42.270 | 0.000 | -1033.600 | 0.000 | -1023.765 | -487.474 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-15:30 | 0.00 | -2589.40 | 0.00 | 0.00 | 48.14 | 100.83 | 470.89 | 4027.25 | 0.00 | 166.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2223.74 |
G NW APARTMENT | 20-JUL-18:23 | 0.00 | -2344.48 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2856.48 | 0.00 | 325.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1756.94 |
OFFICE | 01-SEP-13:30 | 0.00 | -3393.91 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3570.71 | 0.00 | 42.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2451.27 |
G NE APARTMENT | 20-JUL-18:23 | 0.00 | -1633.54 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 912.96 | 0.00 | 327.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.26 |
G N1 APARTMENT | 20-JUL-18:23 | 0.00 | -1104.35 | 0.00 | 0.00 | 141.63 | 230.46 | 547.42 | 744.53 | 0.00 | 287.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -847.17 |
G N2 APARTMENT | 20-JUL-18:23 | 0.00 | -1088.80 | 0.00 | 0.00 | 141.59 | 230.46 | 547.42 | 744.82 | 0.00 | 286.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.41 |
G S1 APARTMENT | 30-AUG-12:45 | 0.00 | -1784.49 | 0.00 | 0.00 | 40.50 | 28.81 | 388.49 | 3368.03 | 0.00 | 31.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2072.72 |
G S2 APARTMENT | 30-AUG-12:45 | 0.00 | -1843.31 | 0.00 | 0.00 | 40.55 | 28.81 | 388.49 | 3367.33 | 0.00 | 32.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2014.55 |
F2 SW APARTMENT | 30-AUG-15:30 | 0.00 | -3376.05 | 0.00 | 0.00 | 48.44 | 100.83 | 470.89 | 3991.96 | 0.00 | 198.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1434.42 |
F2 NW APARTMENT | 20-JUL-18:23 | 0.00 | -3031.84 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2796.49 | 0.00 | 434.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1119.11 |
F2 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3287.02 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 3551.77 | 0.00 | 167.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -884.52 |
F2 NE APARTMENT | 23-JUN-09:00 | 0.00 | -2214.38 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2638.01 | 0.00 | 181.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1069.36 |
F2 N1 APARTMENT | 20-JUL-18:23 | 0.00 | -1573.46 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 722.81 | 0.00 | 385.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -454.22 |
F2 N2 APARTMENT | 20-JUL-18:23 | 0.00 | -1555.44 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 723.00 | 0.00 | 384.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.65 |
F2 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2352.64 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2503.85 | 0.00 | 347.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -956.78 |
F2 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2374.87 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2503.66 | 0.00 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -935.91 |
F3 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3409.11 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2669.71 | 0.00 | 793.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.67 |
F3 NW APARTMENT | 20-JUL-18:23 | 0.00 | -3021.43 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2770.78 | 0.00 | 490.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.56 |
F3 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3135.72 | 0.00 | 0.00 | 40.68 | 28.81 | 382.60 | 3578.73 | 0.00 | 128.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.88 |
F3 NE APARTMENT | 23-JUN-09:30 | 0.00 | -2271.96 | 0.00 | 0.00 | 40.45 | 28.81 | 406.15 | 2482.38 | 0.00 | 346.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.03 |
F3 N1 APARTMENT | 30-JUN-19:15 | 0.00 | -1609.79 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 802.81 | 0.00 | 283.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.63 |
F3 N2 APARTMENT | 30-JUN-19:15 | 0.00 | -1591.99 | 0.00 | 0.00 | 141.82 | 230.46 | 523.87 | 803.06 | 0.00 | 283.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -390.22 |
F3 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2394.14 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2477.49 | 0.00 | 393.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -934.55 |
F3 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2405.71 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2477.37 | 0.00 | 394.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -923.72 |
F4 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3417.19 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2656.30 | 0.00 | 857.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.11 |
F4 NW APARTMENT | 20-JUL-18:23 | 0.00 | -3031.47 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2753.43 | 0.00 | 533.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1175.07 |
F4 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3125.06 | 0.00 | 0.00 | 40.66 | 28.81 | 382.60 | 3568.25 | 0.00 | 133.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1028.60 |
F4 NE APARTMENT | 23-JUN-09:15 | 0.00 | -2295.35 | 0.00 | 0.00 | 40.68 | 28.81 | 406.15 | 2551.08 | 0.00 | 301.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1033.02 |
F4 N1 APARTMENT | 30-JUN-19:15 | 0.00 | -1623.53 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 797.64 | 0.00 | 302.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.58 |
F4 N2 APARTMENT | 30-JUN-19:15 | 0.00 | -1605.82 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 797.90 | 0.00 | 301.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -390.04 |
F4 S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2410.25 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2628.42 | 0.00 | 322.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -998.61 |
F4 S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2416.43 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2628.31 | 0.00 | 322.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -992.32 |
M SW APARTMENT | 19-MAY-16:38 | 0.00 | -3445.75 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2645.95 | 0.00 | 910.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -927.68 |
M NW APARTMENT | 20-JUL-18:23 | 0.00 | -3059.71 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2739.72 | 0.00 | 566.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1166.05 |
M SE APARTMENT | 30-AUG-13:15 | 0.00 | -3155.72 | 0.00 | 0.00 | 40.66 | 28.81 | 382.60 | 3559.31 | 0.00 | 138.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -994.24 |
M NE APARTMENT | 23-JUN-09:15 | 0.00 | -2326.04 | 0.00 | 0.00 | 40.67 | 28.81 | 406.15 | 2542.89 | 0.00 | 318.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1010.73 |
M N1 APARTMENT | 30-JUN-19:15 | 0.00 | -1658.38 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 793.22 | 0.00 | 317.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -348.80 |
M N2 APARTMENT | 30-JUN-19:15 | 0.00 | -1640.78 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 793.48 | 0.00 | 317.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -366.12 |
M S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2446.61 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2614.02 | 0.00 | 342.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -968.25 |
M S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2455.27 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2613.91 | 0.00 | 343.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -959.93 |
F6 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3400.96 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2639.81 | 0.00 | 952.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1008.81 |
F6 NW APARTMENT | 20-JUL-18:23 | 0.00 | -3014.01 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2730.45 | 0.00 | 592.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1228.38 |
F6 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3113.54 | 0.00 | 0.00 | 40.66 | 28.81 | 382.60 | 3553.40 | 0.00 | 142.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1034.11 |
F6 NE APARTMENT | 23-JUN-09:15 | 0.00 | -2282.60 | 0.00 | 0.00 | 40.65 | 28.81 | 406.15 | 2538.00 | 0.00 | 330.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1061.77 |
F6 N1 APARTMENT | 30-JUN-19:15 | 0.00 | -1618.86 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 790.83 | 0.00 | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -397.62 |
F6 N2 APARTMENT | 19-JUL-18:08 | 0.00 | -1602.27 | 0.00 | 0.00 | 137.34 | 230.46 | 547.42 | 219.35 | 0.00 | 276.12 | 191.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2405.73 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2603.73 | 0.00 | 358.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1014.09 |
F6 S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2415.67 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2603.62 | 0.00 | 358.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.76 |
F7 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3383.14 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2633.95 | 0.00 | 988.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1056.44 |
F7 NW APARTMENT | 30-JUN-19:15 | 0.00 | -3002.57 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 2231.41 | 0.00 | 394.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -519.66 |
F7 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3097.94 | 0.00 | 0.00 | 40.51 | 28.81 | 382.60 | 3492.43 | 0.00 | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1040.19 |
F7 NE APARTMENT | 23-JUN-09:15 | 0.00 | -2266.82 | 0.00 | 0.00 | 40.65 | 28.81 | 406.15 | 2533.19 | 0.00 | 341.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1083.61 |
F7 N1 APARTMENT | 19-JUL-18:08 | 0.00 | -1613.01 | 0.00 | 0.00 | 137.28 | 230.46 | 547.42 | 218.52 | 0.00 | 283.72 | 195.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 19-JUL-18:08 | 0.00 | -1596.57 | 0.00 | 0.00 | 137.23 | 230.46 | 547.42 | 218.72 | 0.00 | 281.43 | 181.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2390.98 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2594.76 | 0.00 | 370.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.69 |
F7 S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2400.93 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2594.65 | 0.00 | 371.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.37 |
F8 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3378.42 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2628.90 | 0.00 | 1020.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1088.68 |
F8 NW APARTMENT | 20-JUL-18:08 | 0.00 | -2998.64 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2682.78 | 0.00 | 771.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1375.79 |
F8 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3095.34 | 0.00 | 0.00 | 40.52 | 28.81 | 382.60 | 3485.38 | 0.00 | 198.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1040.83 |
F8 NE APARTMENT | 23-JUN-09:15 | 0.00 | -2264.83 | 0.00 | 0.00 | 40.65 | 28.81 | 406.15 | 2528.60 | 0.00 | 351.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1090.48 |
F8 N1 APARTMENT | 19-JUL-18:08 | 0.00 | -1620.56 | 0.00 | 0.00 | 137.22 | 230.46 | 547.42 | 217.69 | 0.00 | 288.87 | 198.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 19-JUL-18:08 | 0.00 | -1604.23 | 0.00 | 0.00 | 137.17 | 230.46 | 547.42 | 217.89 | 0.00 | 286.48 | 184.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2389.27 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2586.92 | 0.00 | 382.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1038.02 |
F8 S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2399.26 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2586.80 | 0.00 | 383.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1028.68 |
F9 SW APARTMENT | 19-MAY-16:38 | 0.00 | -3467.34 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2622.87 | 0.00 | 1060.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1033.25 |
F9 NW APARTMENT | 20-JUL-18:08 | 0.00 | -3087.86 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 2673.91 | 0.00 | 797.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1303.11 |
F9 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3155.54 | 0.00 | 0.00 | 40.64 | 28.81 | 382.60 | 3478.98 | 0.00 | 209.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -984.66 |
F9 NE APARTMENT | 19-JUL-18:00 | 0.00 | -2293.57 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 464.47 | 0.00 | 660.59 | 243.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 19-JUL-18:08 | 0.00 | -1706.37 | 0.00 | 0.00 | 137.44 | 230.46 | 547.42 | 215.61 | 0.00 | 303.71 | 271.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 19-JUL-18:08 | 0.00 | -1689.79 | 0.00 | 0.00 | 137.39 | 230.46 | 547.42 | 215.83 | 0.00 | 301.40 | 257.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2429.46 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2416.18 | 0.00 | 530.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -974.76 |
F9 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2440.59 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2416.05 | 0.00 | 531.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -964.58 |
T SW APARTMENT | 30-AUG-15:30 | 0.00 | -4214.90 | 0.00 | 0.00 | 48.69 | 100.83 | 470.89 | 3872.87 | 0.00 | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -547.09 |
T NW APARTMENT | 14-JUL-18:00 | 0.00 | -3706.36 | 0.00 | 0.00 | 137.54 | 194.45 | 588.62 | 3047.73 | 0.00 | 183.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -445.69 |
T SE APARTMENT | 30-AUG-13:30 | 0.00 | -3865.25 | 0.00 | 0.00 | 40.69 | 28.81 | 382.60 | 3430.14 | 0.00 | 217.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -234.11 |
T NE APARTMENT | 23-JUN-09:30 | 0.00 | -2826.65 | 0.00 | 0.00 | 40.71 | 28.81 | 406.15 | 2415.99 | 0.00 | 494.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -559.11 |
T N1 APARTMENT | 23-JUN-16:00 | 0.00 | -2214.74 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 510.03 | 0.00 | 654.94 | 429.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 23-JUN-16:00 | 0.00 | -2214.15 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 510.19 | 0.00 | 656.52 | 426.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 30-AUG-13:15 | 0.00 | -3248.00 | 0.00 | 0.00 | 40.37 | 28.81 | 382.60 | 3198.03 | 0.00 | 125.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.84 |
T S2 APARTMENT | 30-AUG-13:15 | 0.00 | -3259.42 | 0.00 | 0.00 | 40.36 | 28.81 | 382.60 | 3197.64 | 0.00 | 124.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -514.36 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-MAY-16:38 | 0.00 | -186739.11 | 0.00 | 0.00 | 6695.84 | 18221.75 | 47207.76 | 91799.91 | 0.00 | 63421.80 | 0.00 | 0.00 | 0.00 | 0.00 | -75.51 | -40532.43 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-JAN-08:15 | 2622.03 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1455.66 | 0.00 | -577.01 | -1095.02 |
G NW APARTMENT | 11-JAN-08:15 | 2652.77 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1447.67 | 0.00 | -577.01 | -1133.76 |
OFFICE | 11-JAN-08:00 | 2681.52 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1531.32 | 0.00 | -549.68 | -1175.08 |
G NE APARTMENT | 11-JAN-08:15 | 2652.88 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1444.38 | 0.00 | -577.01 | -1137.15 |
G N1 APARTMENT | 27-JAN-08:30 | 1734.64 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.07 | 0.00 | -276.37 | -972.87 |
G N2 APARTMENT | 27-JAN-08:30 | 1733.52 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.08 | 0.00 | -276.37 | -971.74 |
G S1 APARTMENT | 11-JAN-08:15 | 1692.87 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.23 | 0.00 | -348.04 | -959.28 |
G S2 APARTMENT | 11-JAN-08:15 | 1687.00 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.32 | 0.00 | -348.04 | -953.31 |
F2 SW APARTMENT | 06-JAN-04:00 | 2611.30 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1803.90 | 0.00 | -856.53 | -378.62 |
F2 NW APARTMENT | 11-JAN-01:00 | 2685.52 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1974.57 | 0.00 | -629.58 | -550.32 |
F2 SE APARTMENT | 11-JAN-01:00 | 2566.56 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1979.83 | 0.00 | -629.58 | -426.11 |
F2 NE APARTMENT | 11-JAN-01:00 | 2692.56 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1976.00 | 0.00 | -629.59 | -555.92 |
F2 N1 APARTMENT | 17-NOV-13:25 | 2512.05 | 0.00 | 0.00 | 0.00 | 45.96 | 28.81 | 388.49 | 94.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2337.73 | -731.70 |
F2 N2 APARTMENT | 17-NOV-13:25 | 2508.16 | 0.00 | 0.00 | 0.00 | 45.98 | 28.81 | 388.49 | 94.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2337.68 | -728.01 |
F2 S1 APARTMENT | 17-NOV-13:30 | 1872.16 | 0.00 | 0.00 | 0.00 | 42.83 | 28.81 | 388.49 | 148.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2340.08 | -140.84 |
F2 S2 APARTMENT | 17-NOV-13:30 | 1881.97 | 0.00 | 0.00 | 0.00 | 42.73 | 28.81 | 388.49 | 147.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2340.34 | -149.19 |
F3 SW APARTMENT | 17-NOV-13:25 | 3088.81 | 0.00 | 0.00 | 0.00 | 44.12 | 28.81 | 388.49 | 214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2871.99 | -892.82 |
F3 NW APARTMENT | 17-NOV-13:25 | 2899.29 | 0.00 | 0.00 | 0.00 | 46.25 | 28.81 | 388.49 | 172.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2852.80 | -682.31 |
F3 SE APARTMENT | 17-NOV-13:25 | 3070.17 | 0.00 | 0.00 | 0.00 | 44.24 | 28.81 | 388.49 | 198.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2867.20 | -863.11 |
F3 NE APARTMENT | 05-JAN-16:00 | 2852.40 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1572.73 | 0.00 | -1736.14 | -41.63 |
F3 N1 APARTMENT | 17-NOV-13:25 | 2936.77 | 0.00 | 0.00 | 0.00 | 45.80 | 28.81 | 388.49 | 87.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2727.17 | -759.79 |
F3 N2 APARTMENT | 17-NOV-13:25 | 2930.63 | 0.00 | 0.00 | 0.00 | 45.82 | 28.81 | 388.49 | 87.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2727.11 | -753.89 |
F3 S1 APARTMENT | 17-NOV-13:30 | 2227.45 | 0.00 | 0.00 | 0.00 | 42.31 | 28.81 | 388.49 | 133.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2729.47 | -91.44 |
F3 S2 APARTMENT | 17-NOV-13:30 | 2231.04 | 0.00 | 0.00 | 0.00 | 42.28 | 28.81 | 388.49 | 133.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2729.56 | -94.62 |
F4 SW APARTMENT | 17-NOV-13:25 | 3519.88 | 0.00 | 0.00 | 0.00 | 44.37 | 28.81 | 388.49 | 209.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3179.86 | -1011.67 |
F4 NW APARTMENT | 17-NOV-13:25 | 3173.90 | 0.00 | 0.00 | 0.00 | 46.42 | 28.81 | 388.49 | 168.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3169.92 | -635.95 |
F4 SE APARTMENT | 17-NOV-13:25 | 3463.27 | 0.00 | 0.00 | 0.00 | 44.57 | 28.81 | 388.49 | 196.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3177.06 | -945.01 |
F4 NE APARTMENT | 05-JAN-16:00 | 3052.33 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1589.92 | 0.00 | -1941.10 | -19.39 |
F4 N1 APARTMENT | 17-NOV-13:25 | 3227.99 | 0.00 | 0.00 | 0.00 | 45.86 | 28.81 | 388.49 | 84.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3029.72 | -745.51 |
F4 N2 APARTMENT | 17-NOV-13:25 | 3223.83 | 0.00 | 0.00 | 0.00 | 45.88 | 28.81 | 388.49 | 84.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3029.66 | -741.59 |
F4 S1 APARTMENT | 17-NOV-13:25 | 2778.83 | 0.00 | 0.00 | 0.00 | 42.39 | 28.81 | 388.49 | 128.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3071.86 | -295.37 |
F4 S2 APARTMENT | 17-NOV-13:25 | 2785.52 | 0.00 | 0.00 | 0.00 | 42.38 | 28.81 | 388.49 | 128.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3072.05 | -301.89 |
M SW APARTMENT | 17-NOV-13:25 | 3691.64 | 0.00 | 0.00 | 0.00 | 44.58 | 28.81 | 388.49 | 207.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3445.80 | -915.21 |
M NW APARTMENT | 17-NOV-13:25 | 3397.56 | 0.00 | 0.00 | 0.00 | 46.50 | 28.81 | 388.49 | 164.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3436.40 | -589.20 |
M SE APARTMENT | 17-NOV-13:25 | 3643.71 | 0.00 | 0.00 | 0.00 | 44.78 | 28.81 | 388.49 | 195.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3443.15 | -857.68 |
M NE APARTMENT | 17-NOV-13:25 | 3236.87 | 0.00 | 0.00 | 0.00 | 46.90 | 28.81 | 388.49 | 151.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3434.01 | -418.60 |
M N1 APARTMENT | 17-NOV-13:25 | 3478.76 | 0.00 | 0.00 | 0.00 | 45.87 | 28.81 | 388.49 | 81.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3283.99 | -739.30 |
M N2 APARTMENT | 17-NOV-13:25 | 3471.96 | 0.00 | 0.00 | 0.00 | 45.89 | 28.81 | 388.49 | 81.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3283.93 | -732.73 |
M S1 APARTMENT | 17-NOV-13:25 | 3143.15 | 0.00 | 0.00 | 0.00 | 42.54 | 28.81 | 388.49 | 126.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3319.33 | -410.05 |
M S2 APARTMENT | 17-NOV-13:25 | 3145.38 | 0.00 | 0.00 | 0.00 | 42.55 | 28.81 | 388.49 | 126.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3319.41 | -412.30 |
F6 SW APARTMENT | 17-NOV-13:25 | 3819.29 | 0.00 | 0.00 | 0.00 | 45.10 | 28.81 | 388.49 | 213.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3676.91 | -818.04 |
F6 NW APARTMENT | 17-NOV-13:25 | 3519.40 | 0.00 | 0.00 | 0.00 | 46.86 | 28.81 | 388.49 | 166.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3668.34 | -482.17 |
F6 SE APARTMENT | 17-NOV-13:25 | 3774.15 | 0.00 | 0.00 | 0.00 | 45.28 | 28.81 | 388.49 | 200.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3674.71 | -762.38 |
F6 NE APARTMENT | 05-JAN-16:00 | 3393.37 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1611.83 | 0.00 | -2255.87 | -23.77 |
F6 N1 APARTMENT | 17-NOV-13:25 | 3558.75 | 0.00 | 0.00 | 0.00 | 46.23 | 28.81 | 388.49 | 83.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3505.92 | -599.59 |
F6 N2 APARTMENT | 17-NOV-13:25 | 3553.69 | 0.00 | 0.00 | 0.00 | 46.24 | 28.81 | 388.49 | 83.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3505.88 | -594.69 |
F6 S1 APARTMENT | 17-NOV-13:25 | 3837.26 | 0.00 | 0.00 | 0.00 | 43.13 | 28.81 | 388.49 | 130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3524.53 | -903.57 |
F6 S2 APARTMENT | 17-NOV-13:25 | 3837.23 | 0.00 | 0.00 | 0.00 | 43.13 | 28.81 | 388.49 | 130.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3524.61 | -903.53 |
F7 SW APARTMENT | 17-NOV-13:25 | 3945.03 | 0.00 | 0.00 | 0.00 | 45.49 | 28.81 | 388.49 | 216.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3885.13 | -739.66 |
F7 NW APARTMENT | 17-NOV-13:25 | 3664.59 | 0.00 | 0.00 | 0.00 | 47.09 | 28.81 | 388.49 | 167.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3877.37 | -419.45 |
F7 SE APARTMENT | 17-NOV-13:25 | 3907.11 | 0.00 | 0.00 | 0.00 | 45.65 | 28.81 | 388.49 | 203.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3883.28 | -690.62 |
F7 NE APARTMENT | 05-JAN-16:00 | 3545.75 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1619.43 | 0.00 | -2385.05 | -39.36 |
F7 N1 APARTMENT | 17-NOV-13:25 | 3682.69 | 0.00 | 0.00 | 0.00 | 46.47 | 28.81 | 388.49 | 84.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3705.72 | -524.89 |
F7 N2 APARTMENT | 17-NOV-13:25 | 3678.53 | 0.00 | 0.00 | 0.00 | 46.48 | 28.81 | 388.49 | 84.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3705.69 | -520.83 |
F7 S1 APARTMENT | 17-NOV-13:25 | 4307.17 | 0.00 | 0.00 | 0.00 | 43.64 | 28.81 | 388.49 | 134.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3713.51 | -1188.71 |
F7 S2 APARTMENT | 17-NOV-13:25 | 4312.51 | 0.00 | 0.00 | 0.00 | 43.64 | 28.81 | 388.49 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3713.59 | -1194.01 |
F8 SW APARTMENT | 17-NOV-13:25 | 4063.74 | 0.00 | 0.00 | 0.00 | 45.83 | 28.81 | 388.49 | 220.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4075.84 | -671.47 |
F8 NW APARTMENT | 17-NOV-13:25 | 3804.54 | 0.00 | 0.00 | 0.00 | 47.28 | 28.81 | 388.49 | 168.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4068.83 | -368.62 |
F8 SE APARTMENT | 17-NOV-13:25 | 4036.55 | 0.00 | 0.00 | 0.00 | 45.98 | 28.81 | 388.49 | 207.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4074.30 | -632.73 |
F8 NE APARTMENT | 17-NOV-13:25 | 3734.88 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 153.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4068.39 | -284.64 |
F8 N1 APARTMENT | 15-SEP-08:10 | 3817.49 | 0.00 | 0.00 | 0.00 | 43.75 | 28.81 | 394.37 | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3180.56 | -1126.33 |
F8 N2 APARTMENT | 17-NOV-13:25 | 3797.22 | 0.00 | 0.00 | 0.00 | 46.68 | 28.81 | 388.49 | 85.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3888.66 | -457.65 |
F8 S1 APARTMENT | 17-NOV-13:25 | 4364.26 | 0.00 | 0.00 | 0.00 | 44.14 | 28.81 | 388.49 | 138.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3895.60 | -1068.38 |
F8 S2 APARTMENT | 17-NOV-13:25 | 4366.04 | 0.00 | 0.00 | 0.00 | 44.14 | 28.81 | 388.49 | 138.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3895.66 | -1070.13 |
F9 SW APARTMENT | 17-NOV-13:25 | 4170.39 | 0.00 | 0.00 | 0.00 | 46.22 | 28.81 | 388.49 | 226.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4252.62 | -607.78 |
F9 NW APARTMENT | 17-NOV-13:25 | 3955.55 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 169.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4246.62 | -343.52 |
F9 SE APARTMENT | 17-NOV-13:25 | 4125.19 | 0.00 | 0.00 | 0.00 | 46.37 | 28.81 | 388.49 | 213.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4251.13 | -550.80 |
F9 NE APARTMENT | 17-NOV-13:25 | 3943.93 | 0.00 | 0.00 | 0.00 | 47.42 | 28.81 | 388.49 | 153.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4246.68 | -315.94 |
F9 N1 APARTMENT | 15-SEP-08:10 | 4045.34 | 0.00 | 0.00 | 0.00 | 43.88 | 28.81 | 394.37 | 22.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3314.01 | -1221.33 |
F9 N2 APARTMENT | 15-SEP-08:10 | 4001.45 | 0.00 | 0.00 | 0.00 | 43.87 | 28.81 | 394.37 | 22.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3313.83 | -1177.43 |
F9 S1 APARTMENT | 17-NOV-13:25 | 4400.38 | 0.00 | 0.00 | 0.00 | 44.77 | 28.81 | 388.49 | 144.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4064.43 | -942.82 |
F9 S2 APARTMENT | 17-NOV-13:25 | 4402.90 | 0.00 | 0.00 | 0.00 | 44.77 | 28.81 | 388.49 | 144.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4064.49 | -945.27 |
T SW APARTMENT | 05-JAN-16:00 | 4589.11 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1420.54 | 0.00 | -2707.54 | -959.13 |
T NW APARTMENT | 05-JAN-16:00 | 4738.36 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1557.92 | 0.00 | -2707.55 | -970.98 |
T SE APARTMENT | 05-JAN-16:00 | 4594.14 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.19 | 0.00 | -2707.54 | -927.49 |
T NE APARTMENT | 05-JAN-16:00 | 4743.96 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1594.93 | 0.00 | -2707.57 | -939.56 |
T N1 APARTMENT | 15-SEP-08:25 | 4161.15 | 0.00 | 0.00 | 0.00 | 44.33 | 28.81 | 394.37 | 62.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3608.37 | -1082.93 |
T N2 APARTMENT | 15-SEP-08:25 | 4166.64 | 0.00 | 0.00 | 0.00 | 44.19 | 28.81 | 394.37 | 60.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3608.57 | -1086.07 |
T S1 APARTMENT | 17-NOV-13:25 | 4805.64 | 0.00 | 0.00 | 0.00 | 44.12 | 28.81 | 388.49 | 140.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4231.66 | -1175.42 |
T S2 APARTMENT | 17-NOV-13:25 | 4811.39 | 0.00 | 0.00 | 0.00 | 44.11 | 28.81 | 388.49 | 139.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4231.83 | -1180.87 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-NOV-13:25 | 261846.88 | 0.00 | 0.00 | 0.00 | 3667.77 | 10361.29 | 31389.06 | 12444.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -266417.64 | -53292.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sec1.1A-General InformationData | |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 143.00 |
Number of hours cooling loads not met | 147.50 |
Number of hours not met | 290.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.22 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 263.76 | 73815.64 | 902.48 | 231254.76 | 0.00 | 0.00 |
Space Cooling | 245.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.41 | 1453.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 702.48 | 22275.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1278.59 | 87362.79 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 51564.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3001.91 | 2181.08 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3001.91 |
Natural Gas | 0.00 | 2181.08 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 5182.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 33.66 |
Space Cooling | 31.27 |
Fans-Interior | 89.64 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 31.03 |
Subtotal | 383.07 |
Natural Gas [MJ/m2] | |
Space Heating | 115.16 |
Service Water Heating | 163.16 |
Miscellaneous | 0.00 |
Subtotal | 278.32 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.03 |
Space Heating | 22.50 |
Space Cooling | 4.73 |
Fans-Interior | 13.55 |
Service Water Heating | 24.67 |
Receptacle Equipment | 21.82 |
Miscellaneous | 4.69 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.258674 |
G NW APARTMENT DIRECT AIR | 0.232095 |
OFFICE DIRECT AIR | 0.348674 |
G NE APARTMENT DIRECT AIR | 0.165424 |
G N1 APARTMENT DIRECT AIR | 0.112723 |
G N2 APARTMENT DIRECT AIR | 0.111326 |
G S1 APARTMENT DIRECT AIR | 0.167600 |
G S2 APARTMENT DIRECT AIR | 0.173541 |
F2 SW APARTMENT DIRECT AIR | 0.339339 |
F2 NW APARTMENT DIRECT AIR | 0.301290 |
F2 SE APARTMENT DIRECT AIR | 0.324879 |
F2 NE APARTMENT DIRECT AIR | 0.221619 |
F2 N1 APARTMENT DIRECT AIR | 0.157670 |
F2 N2 APARTMENT DIRECT AIR | 0.155935 |
F2 S1 APARTMENT DIRECT AIR | 0.224061 |
F2 S2 APARTMENT DIRECT AIR | 0.226397 |
F3 SW APARTMENT DIRECT AIR | 0.340604 |
F3 NW APARTMENT DIRECT AIR | 0.304082 |
F3 SE APARTMENT DIRECT AIR | 0.309621 |
F3 NE APARTMENT DIRECT AIR | 0.226111 |
F3 N1 APARTMENT DIRECT AIR | 0.162262 |
F3 N2 APARTMENT DIRECT AIR | 0.160543 |
F3 S1 APARTMENT DIRECT AIR | 0.228268 |
F3 S2 APARTMENT DIRECT AIR | 0.229475 |
F4 SW APARTMENT DIRECT AIR | 0.341360 |
F4 NW APARTMENT DIRECT AIR | 0.305205 |
F4 SE APARTMENT DIRECT AIR | 0.309293 |
F4 NE APARTMENT DIRECT AIR | 0.227415 |
F4 N1 APARTMENT DIRECT AIR | 0.163921 |
F4 N2 APARTMENT DIRECT AIR | 0.162208 |
F4 S1 APARTMENT DIRECT AIR | 0.229638 |
F4 S2 APARTMENT DIRECT AIR | 0.230688 |
M SW APARTMENT DIRECT AIR | 0.344468 |
M NW APARTMENT DIRECT AIR | 0.308709 |
M SE APARTMENT DIRECT AIR | 0.312737 |
M NE APARTMENT DIRECT AIR | 0.230938 |
M N1 APARTMENT DIRECT AIR | 0.167574 |
M N2 APARTMENT DIRECT AIR | 0.165868 |
M S1 APARTMENT DIRECT AIR | 0.233097 |
M S2 APARTMENT DIRECT AIR | 0.234123 |
F6 SW APARTMENT DIRECT AIR | 0.340388 |
F6 NW APARTMENT DIRECT AIR | 0.304773 |
F6 SE APARTMENT DIRECT AIR | 0.309168 |
F6 NE APARTMENT DIRECT AIR | 0.227191 |
F6 N1 APARTMENT DIRECT AIR | 0.164107 |
F6 N2 APARTMENT DIRECT AIR | 0.162415 |
F6 S1 APARTMENT DIRECT AIR | 0.229375 |
F6 S2 APARTMENT DIRECT AIR | 0.230399 |
F7 SW APARTMENT DIRECT AIR | 0.338962 |
F7 NW APARTMENT DIRECT AIR | 0.303558 |
F7 SE APARTMENT DIRECT AIR | 0.308187 |
F7 NE APARTMENT DIRECT AIR | 0.226079 |
F7 N1 APARTMENT DIRECT AIR | 0.163177 |
F7 N2 APARTMENT DIRECT AIR | 0.161496 |
F7 S1 APARTMENT DIRECT AIR | 0.228221 |
F7 S2 APARTMENT DIRECT AIR | 0.229245 |
F8 SW APARTMENT DIRECT AIR | 0.338959 |
F8 NW APARTMENT DIRECT AIR | 0.303762 |
F8 SE APARTMENT DIRECT AIR | 0.308491 |
F8 NE APARTMENT DIRECT AIR | 0.226268 |
F8 N1 APARTMENT DIRECT AIR | 0.163648 |
F8 N2 APARTMENT DIRECT AIR | 0.161979 |
F8 S1 APARTMENT DIRECT AIR | 0.228388 |
F8 S2 APARTMENT DIRECT AIR | 0.229414 |
F9 SW APARTMENT DIRECT AIR | 0.348830 |
F9 NW APARTMENT DIRECT AIR | 0.313294 |
F9 SE APARTMENT DIRECT AIR | 0.315327 |
F9 NE APARTMENT DIRECT AIR | 0.229080 |
F9 N1 APARTMENT DIRECT AIR | 0.172070 |
F9 N2 APARTMENT DIRECT AIR | 0.170381 |
F9 S1 APARTMENT DIRECT AIR | 0.234017 |
F9 S2 APARTMENT DIRECT AIR | 0.235173 |
T SW APARTMENT DIRECT AIR | 0.425870 |
T NW APARTMENT DIRECT AIR | 0.374854 |
T SE APARTMENT DIRECT AIR | 0.387991 |
T NE APARTMENT DIRECT AIR | 0.280186 |
T N1 APARTMENT DIRECT AIR | 0.212298 |
T N2 APARTMENT DIRECT AIR | 0.211810 |
T S1 APARTMENT DIRECT AIR | 0.318683 |
T S2 APARTMENT DIRECT AIR | 0.319814 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.258674 |
AIRLOOP G NW MAIN BRANCH | 0.232095 |
AIRLOOP OFFICE MAIN BRANCH | 0.348674 |
AIRLOOP G NE MAIN BRANCH | 0.165424 |
AIRLOOP G N1 MAIN BRANCH | 0.112723 |
AIRLOOP G N2 MAIN BRANCH | 0.111326 |
AIRLOOP G S1 MAIN BRANCH | 0.167600 |
AIRLOOP G S2 MAIN BRANCH | 0.173541 |
AIRLOOP F2 SW MAIN BRANCH | 0.339339 |
AIRLOOP F2 NW MAIN BRANCH | 0.301290 |
AIRLOOP F2 SE MAIN BRANCH | 0.324879 |
AIRLOOP F2 NE MAIN BRANCH | 0.221619 |
AIRLOOP F2 N1 MAIN BRANCH | 0.157670 |
AIRLOOP F2 N2 MAIN BRANCH | 0.155935 |
AIRLOOP F2 S1 MAIN BRANCH | 0.224061 |
AIRLOOP F2 S2 MAIN BRANCH | 0.226397 |
AIRLOOP F3 SW MAIN BRANCH | 0.340604 |
AIRLOOP F3 NW MAIN BRANCH | 0.304082 |
AIRLOOP F3 SE MAIN BRANCH | 0.309621 |
AIRLOOP F3 NE MAIN BRANCH | 0.226111 |
AIRLOOP F3 N1 MAIN BRANCH | 0.162262 |
AIRLOOP F3 N2 MAIN BRANCH | 0.160543 |
AIRLOOP F3 S1 MAIN BRANCH | 0.228268 |
AIRLOOP F3 S2 MAIN BRANCH | 0.229475 |
AIRLOOP F4 SW MAIN BRANCH | 0.341360 |
AIRLOOP F4 NW MAIN BRANCH | 0.305205 |
AIRLOOP F4 SE MAIN BRANCH | 0.309293 |
AIRLOOP F4 NE MAIN BRANCH | 0.227415 |
AIRLOOP F4 N1 MAIN BRANCH | 0.163921 |
AIRLOOP F4 N2 MAIN BRANCH | 0.162208 |
AIRLOOP F4 S1 MAIN BRANCH | 0.229638 |
AIRLOOP F4 S2 MAIN BRANCH | 0.230688 |
AIRLOOP M SW MAIN BRANCH | 0.344468 |
AIRLOOP M NW MAIN BRANCH | 0.308709 |
AIRLOOP M SE MAIN BRANCH | 0.312737 |
AIRLOOP M NE MAIN BRANCH | 0.230938 |
AIRLOOP M N1 MAIN BRANCH | 0.167574 |
AIRLOOP M N2 MAIN BRANCH | 0.165868 |
AIRLOOP M S1 MAIN BRANCH | 0.233097 |
AIRLOOP M S2 MAIN BRANCH | 0.234123 |
AIRLOOP F6 SW MAIN BRANCH | 0.340388 |
AIRLOOP F6 NW MAIN BRANCH | 0.304773 |
AIRLOOP F6 SE MAIN BRANCH | 0.309168 |
AIRLOOP F6 NE MAIN BRANCH | 0.227191 |
AIRLOOP F6 N1 MAIN BRANCH | 0.164107 |
AIRLOOP F6 N2 MAIN BRANCH | 0.162415 |
AIRLOOP F6 S1 MAIN BRANCH | 0.229375 |
AIRLOOP F6 S2 MAIN BRANCH | 0.230399 |
AIRLOOP F7 SW MAIN BRANCH | 0.338962 |
AIRLOOP F7 NW MAIN BRANCH | 0.303558 |
AIRLOOP F7 SE MAIN BRANCH | 0.308187 |
AIRLOOP F7 NE MAIN BRANCH | 0.226079 |
AIRLOOP F7 N1 MAIN BRANCH | 0.163177 |
AIRLOOP F7 N2 MAIN BRANCH | 0.161496 |
AIRLOOP F7 S1 MAIN BRANCH | 0.228221 |
AIRLOOP F7 S2 MAIN BRANCH | 0.229245 |
AIRLOOP F8 SW MAIN BRANCH | 0.338959 |
AIRLOOP F8 NW MAIN BRANCH | 0.303762 |
AIRLOOP F8 SE MAIN BRANCH | 0.308491 |
AIRLOOP F8 NE MAIN BRANCH | 0.226268 |
AIRLOOP F8 N1 MAIN BRANCH | 0.163648 |
AIRLOOP F8 N2 MAIN BRANCH | 0.161979 |
AIRLOOP F8 S1 MAIN BRANCH | 0.228388 |
AIRLOOP F8 S2 MAIN BRANCH | 0.229414 |
AIRLOOP F9 SW MAIN BRANCH | 0.348830 |
AIRLOOP F9 NW MAIN BRANCH | 0.313294 |
AIRLOOP F9 SE MAIN BRANCH | 0.315327 |
AIRLOOP F9 NE MAIN BRANCH | 0.229080 |
AIRLOOP F9 N1 MAIN BRANCH | 0.172070 |
AIRLOOP F9 N2 MAIN BRANCH | 0.170381 |
AIRLOOP F9 S1 MAIN BRANCH | 0.234017 |
AIRLOOP F9 S2 MAIN BRANCH | 0.235173 |
AIRLOOP T SW MAIN BRANCH | 0.425870 |
AIRLOOP T NW MAIN BRANCH | 0.374854 |
AIRLOOP T SE MAIN BRANCH | 0.387991 |
AIRLOOP T NE MAIN BRANCH | 0.280186 |
AIRLOOP T N1 MAIN BRANCH | 0.212298 |
AIRLOOP T N2 MAIN BRANCH | 0.211810 |
AIRLOOP T S1 MAIN BRANCH | 0.318683 |
AIRLOOP T S2 MAIN BRANCH | 0.319814 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.258674 |
AIRLOOP G NW | 0.232095 |
AIRLOOP OFFICE | 0.348674 |
AIRLOOP G NE | 0.165424 |
AIRLOOP G N1 | 0.112723 |
AIRLOOP G N2 | 0.111326 |
AIRLOOP G S1 | 0.167600 |
AIRLOOP G S2 | 0.173541 |
AIRLOOP F2 SW | 0.339339 |
AIRLOOP F2 NW | 0.301290 |
AIRLOOP F2 SE | 0.324879 |
AIRLOOP F2 NE | 0.221619 |
AIRLOOP F2 N1 | 0.157670 |
AIRLOOP F2 N2 | 0.155935 |
AIRLOOP F2 S1 | 0.224061 |
AIRLOOP F2 S2 | 0.226397 |
AIRLOOP F3 SW | 0.340604 |
AIRLOOP F3 NW | 0.304082 |
AIRLOOP F3 SE | 0.309621 |
AIRLOOP F3 NE | 0.226111 |
AIRLOOP F3 N1 | 0.162262 |
AIRLOOP F3 N2 | 0.160543 |
AIRLOOP F3 S1 | 0.228268 |
AIRLOOP F3 S2 | 0.229475 |
AIRLOOP F4 SW | 0.341360 |
AIRLOOP F4 NW | 0.305205 |
AIRLOOP F4 SE | 0.309293 |
AIRLOOP F4 NE | 0.227415 |
AIRLOOP F4 N1 | 0.163921 |
AIRLOOP F4 N2 | 0.162208 |
AIRLOOP F4 S1 | 0.229638 |
AIRLOOP F4 S2 | 0.230688 |
AIRLOOP M SW | 0.344468 |
AIRLOOP M NW | 0.308709 |
AIRLOOP M SE | 0.312737 |
AIRLOOP M NE | 0.230938 |
AIRLOOP M N1 | 0.167574 |
AIRLOOP M N2 | 0.165868 |
AIRLOOP M S1 | 0.233097 |
AIRLOOP M S2 | 0.234123 |
AIRLOOP F6 SW | 0.340388 |
AIRLOOP F6 NW | 0.304773 |
AIRLOOP F6 SE | 0.309168 |
AIRLOOP F6 NE | 0.227191 |
AIRLOOP F6 N1 | 0.164107 |
AIRLOOP F6 N2 | 0.162415 |
AIRLOOP F6 S1 | 0.229375 |
AIRLOOP F6 S2 | 0.230399 |
AIRLOOP F7 SW | 0.338962 |
AIRLOOP F7 NW | 0.303558 |
AIRLOOP F7 SE | 0.308187 |
AIRLOOP F7 NE | 0.226079 |
AIRLOOP F7 N1 | 0.163177 |
AIRLOOP F7 N2 | 0.161496 |
AIRLOOP F7 S1 | 0.228221 |
AIRLOOP F7 S2 | 0.229245 |
AIRLOOP F8 SW | 0.338959 |
AIRLOOP F8 NW | 0.303762 |
AIRLOOP F8 SE | 0.308491 |
AIRLOOP F8 NE | 0.226268 |
AIRLOOP F8 N1 | 0.163648 |
AIRLOOP F8 N2 | 0.161979 |
AIRLOOP F8 S1 | 0.228388 |
AIRLOOP F8 S2 | 0.229414 |
AIRLOOP F9 SW | 0.348830 |
AIRLOOP F9 NW | 0.313294 |
AIRLOOP F9 SE | 0.315327 |
AIRLOOP F9 NE | 0.229080 |
AIRLOOP F9 N1 | 0.172070 |
AIRLOOP F9 N2 | 0.170381 |
AIRLOOP F9 S1 | 0.234017 |
AIRLOOP F9 S2 | 0.235173 |
AIRLOOP T SW | 0.425870 |
AIRLOOP T NW | 0.374854 |
AIRLOOP T SE | 0.387991 |
AIRLOOP T NE | 0.280186 |
AIRLOOP T N1 | 0.212298 |
AIRLOOP T N2 | 0.211810 |
AIRLOOP T S1 | 0.318683 |
AIRLOOP T S2 | 0.319814 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.258674 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.232095 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.348674 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.165424 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.112723 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.111326 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.167600 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.173541 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.339339 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.301290 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.324879 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.221619 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.157670 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.155935 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.224061 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.226397 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.340604 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.304082 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.309621 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.226111 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.162262 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.160543 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.228268 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.229475 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.341360 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.305205 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.309293 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.227415 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.163921 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.162208 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.229638 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.230688 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.344468 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.308709 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.312737 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.230938 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.167574 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.165868 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.233097 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.234123 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.340388 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.304773 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.309168 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.227191 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.164107 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.162415 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.229375 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.230399 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.338962 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.303558 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.308187 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.226079 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.163177 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.161496 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.228221 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.229245 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.338959 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.303762 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.308491 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.226268 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.163648 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.161979 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.228388 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.229414 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.348830 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.313294 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.315327 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.229080 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.172070 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.170381 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.234017 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.235173 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.425870 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.374854 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.387991 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.280186 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.212298 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.211810 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.318683 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.319814 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.258674 | 3321.43 | 2275.47 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.232095 | 2949.73 | 2029.06 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.348674 | 4577.95 | 3120.77 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.165424 | 2081.33 | 1451.43 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.112723 | 1401.26 | 982.07 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.111326 | 1382.83 | 969.98 | 0.000030 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.167600 | 2254.65 | 1527.00 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.173541 | 2330.41 | 1578.49 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.339339 | 4333.48 | 2969.14 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.301290 | 3817.10 | 2623.83 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.324879 | 4220.88 | 2879.05 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.221619 | 2777.95 | 1932.30 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.157670 | 1970.77 | 1369.60 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.155935 | 1948.47 | 1354.58 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.224061 | 2964.33 | 2014.00 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.226397 | 2994.12 | 2034.22 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.340604 | 4338.86 | 2977.99 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.304082 | 3842.03 | 2645.89 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.309621 | 4016.05 | 2745.17 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.226111 | 2824.91 | 1969.13 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.162262 | 2023.57 | 1408.16 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.160543 | 2001.49 | 1393.28 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.228268 | 3011.76 | 2049.21 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.229475 | 3027.15 | 2059.66 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.341360 | 4340.46 | 2982.97 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.305205 | 3857.98 | 2659.91 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.309293 | 4004.06 | 2740.82 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.227415 | 2850.73 | 1986.09 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.163921 | 2040.22 | 1421.62 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.162208 | 2018.24 | 1406.81 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.229638 | 3024.55 | 2060.16 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.230688 | 3037.94 | 2069.24 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.344468 | 4373.53 | 3008.55 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.308709 | 3896.13 | 2688.92 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.312737 | 4047.10 | 2771.69 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.230938 | 2889.37 | 2015.33 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.167574 | 2083.34 | 1452.51 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.165868 | 2061.46 | 1437.75 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.233097 | 3064.80 | 2089.34 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.234123 | 3077.88 | 2098.22 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.340388 | 4315.91 | 2972.23 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.304773 | 3840.33 | 2653.84 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.309168 | 3996.27 | 2739.80 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.227191 | 2836.62 | 1982.01 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.164107 | 2035.60 | 1421.90 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.162415 | 2013.91 | 1407.26 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.229375 | 3014.15 | 2056.52 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.230399 | 3027.21 | 2065.38 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.338962 | 4292.82 | 2958.96 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.303558 | 3819.94 | 2642.41 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.308187 | 3979.05 | 2730.42 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.226079 | 2817.98 | 1971.56 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.163177 | 2020.84 | 1413.32 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.161496 | 1999.30 | 1398.78 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.228221 | 2996.62 | 2045.99 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.229245 | 3009.66 | 2054.84 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.338959 | 4288.38 | 2958.09 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.303762 | 3818.16 | 2643.33 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.308491 | 3978.66 | 2732.22 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.226268 | 2816.33 | 1972.42 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.163648 | 2024.36 | 1416.91 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.161979 | 2002.99 | 1402.48 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.228388 | 2996.17 | 2046.93 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.229414 | 3009.25 | 2055.81 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.348830 | 4410.10 | 3042.56 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.313294 | 3935.64 | 2724.88 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.315327 | 4061.64 | 2790.51 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.229080 | 2848.25 | 1995.97 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.172070 | 2130.01 | 1489.31 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.170381 | 2108.40 | 1474.71 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.234017 | 3065.43 | 2095.16 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.235173 | 3080.16 | 2105.16 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.425870 | 5444.80 | 3736.06 | 0.000119 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.374854 | 4746.24 | 3270.83 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.387991 | 4976.68 | 3415.03 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.280186 | 3521.11 | 2448.04 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.212298 | 2774.22 | 1901.55 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.211810 | 2774.49 | 1900.02 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.318683 | 4141.10 | 2826.61 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.319814 | 4155.52 | 2836.38 | 0.000091 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.258674 | 0.258674 | 0.258674 | 0.258674 | 3321.43 | 3321.43 | 4534.09 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.232095 | 0.232095 | 0.232095 | 0.232095 | 2949.73 | 2949.73 | 4551.33 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.348674 | 0.348674 | 0.348674 | 0.348674 | 4577.95 | 4577.95 | 5645.56 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.165424 | 0.165424 | 0.165424 | 0.165424 | 2081.33 | 2081.33 | 4557.69 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.112723 | 0.112723 | 0.112723 | 0.112723 | 1401.26 | 1401.26 | 3509.82 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.111326 | 0.111326 | 0.111326 | 0.111326 | 1382.83 | 1382.83 | 3509.96 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.167600 | 0.167600 | 0.167600 | 0.167600 | 2254.65 | 2254.65 | 3490.03 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.173541 | 0.173541 | 0.173541 | 0.173541 | 2330.41 | 2330.41 | 3498.64 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.339339 | 0.339339 | 0.339339 | 0.339339 | 4333.48 | 4333.48 | 4373.81 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.301290 | 0.301290 | 0.301290 | 0.301290 | 3817.10 | 3817.10 | 4380.70 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.324879 | 0.324879 | 0.324879 | 0.324879 | 4220.88 | 4220.88 | 4403.48 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.221619 | 0.221619 | 0.221619 | 0.221619 | 2777.95 | 2777.95 | 4386.02 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.157670 | 0.157670 | 0.157670 | 0.157670 | 1970.77 | 1970.77 | 3123.89 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.155935 | 0.155935 | 0.155935 | 0.155935 | 1948.47 | 1948.47 | 3124.01 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.224061 | 0.224061 | 0.224061 | 0.224061 | 2964.33 | 2964.33 | 3120.05 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.226397 | 0.226397 | 0.226397 | 0.226397 | 2994.12 | 2994.12 | 3121.65 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.340604 | 0.340604 | 0.340604 | 0.340604 | 4338.86 | 4338.86 | 4357.28 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.304082 | 0.304082 | 0.304082 | 0.304082 | 3842.03 | 3842.03 | 4363.85 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.309621 | 0.309621 | 0.309621 | 0.309621 | 4016.05 | 4016.05 | 4363.10 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.226111 | 0.226111 | 0.226111 | 0.226111 | 2824.91 | 2824.91 | 4367.23 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.162262 | 0.162262 | 0.162262 | 0.162262 | 2023.57 | 2023.57 | 3065.51 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.160543 | 0.160543 | 0.160543 | 0.160543 | 2001.49 | 2001.49 | 3065.59 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.228268 | 0.228268 | 0.228268 | 0.228268 | 3011.76 | 3011.76 | 3060.00 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.229475 | 0.229475 | 0.229475 | 0.229475 | 3027.15 | 3027.15 | 3060.29 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.341360 | 0.341360 | 0.341360 | 0.341360 | 4340.46 | 4340.46 | 4415.39 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.305205 | 0.305205 | 0.305205 | 0.305205 | 3857.98 | 3857.98 | 4420.18 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.309293 | 0.309293 | 0.309293 | 0.309293 | 4004.06 | 4004.06 | 4417.35 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.227415 | 0.227415 | 0.227415 | 0.227415 | 2850.73 | 2850.73 | 4421.90 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.163921 | 0.163921 | 0.163921 | 0.163921 | 2040.22 | 2040.22 | 3086.39 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.162208 | 0.162208 | 0.162208 | 0.162208 | 2018.24 | 2018.24 | 3086.43 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.229638 | 0.229638 | 0.229638 | 0.229638 | 3024.55 | 3024.55 | 3082.39 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.230688 | 0.230688 | 0.230688 | 0.230688 | 3037.94 | 3037.94 | 3082.45 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.344468 | 0.344468 | 0.344468 | 0.344468 | 4373.53 | 4373.53 | 4450.02 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.308709 | 0.308709 | 0.308709 | 0.308709 | 3896.13 | 3896.13 | 4451.64 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.312737 | 0.312737 | 0.312737 | 0.312737 | 4047.10 | 4047.10 | 4450.33 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.230938 | 0.230938 | 0.230938 | 0.230938 | 2889.37 | 2889.37 | 4451.92 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.167574 | 0.167574 | 0.167574 | 0.167574 | 2083.34 | 2083.34 | 3090.00 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.165868 | 0.165868 | 0.165868 | 0.165868 | 2061.46 | 2061.46 | 3090.01 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.233097 | 0.233097 | 0.233097 | 0.233097 | 3064.80 | 3064.80 | 3089.17 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.234123 | 0.234123 | 0.234123 | 0.234123 | 3077.88 | 3077.88 | 3089.18 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.340388 | 0.340388 | 0.340388 | 0.340388 | 4315.91 | 4315.91 | 4551.47 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.304773 | 0.304773 | 0.304773 | 0.304773 | 3840.33 | 3840.33 | 4552.09 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.309168 | 0.309168 | 0.309168 | 0.309168 | 3996.27 | 3996.27 | 4550.49 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.227191 | 0.227191 | 0.227191 | 0.227191 | 2836.62 | 2836.62 | 4551.11 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.164107 | 0.164107 | 0.164107 | 0.164107 | 2035.60 | 2035.60 | 3164.95 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.162415 | 0.162415 | 0.162415 | 0.162415 | 2013.91 | 2013.91 | 3164.93 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.229375 | 0.229375 | 0.229375 | 0.229375 | 3014.15 | 3014.15 | 3165.08 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.230399 | 0.230399 | 0.230399 | 0.230399 | 3027.21 | 3027.21 | 3165.06 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.338962 | 0.338962 | 0.338962 | 0.338962 | 4292.82 | 4292.82 | 4621.52 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.303558 | 0.303558 | 0.303558 | 0.303558 | 3819.94 | 3819.94 | 4620.14 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.308187 | 0.308187 | 0.308187 | 0.308187 | 3979.05 | 3979.05 | 4619.42 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.226079 | 0.226079 | 0.226079 | 0.226079 | 2817.98 | 2817.98 | 4618.03 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.163177 | 0.163177 | 0.163177 | 0.163177 | 2020.84 | 2020.84 | 3211.74 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.161496 | 0.161496 | 0.161496 | 0.161496 | 1999.30 | 1999.30 | 3211.69 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.228221 | 0.228221 | 0.228221 | 0.228221 | 2996.62 | 2996.62 | 3213.91 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.229245 | 0.229245 | 0.229245 | 0.229245 | 3009.66 | 3009.66 | 3213.86 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.338959 | 0.338959 | 0.338959 | 0.338959 | 4288.38 | 4288.38 | 4699.52 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.303762 | 0.303762 | 0.303762 | 0.303762 | 3818.16 | 3818.16 | 4695.90 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.308491 | 0.308491 | 0.308491 | 0.308491 | 3978.66 | 3978.66 | 4696.40 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.226268 | 0.226268 | 0.226268 | 0.226268 | 2816.33 | 2816.33 | 4692.78 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.163648 | 0.163648 | 0.163648 | 0.163648 | 2024.36 | 2024.36 | 3268.80 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.161979 | 0.161979 | 0.161979 | 0.161979 | 2002.99 | 2002.99 | 3268.73 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.228388 | 0.228388 | 0.228388 | 0.228388 | 2996.17 | 2996.17 | 3273.23 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.229414 | 0.229414 | 0.229414 | 0.229414 | 3009.25 | 3009.25 | 3273.16 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.348830 | 0.348830 | 0.348830 | 0.348830 | 4410.10 | 4410.10 | 4961.73 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.313294 | 0.313294 | 0.313294 | 0.313294 | 3935.64 | 3935.64 | 4952.20 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.315327 | 0.315327 | 0.315327 | 0.315327 | 4061.64 | 4061.64 | 4957.64 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.229080 | 0.229080 | 0.229080 | 0.229080 | 2848.25 | 2848.25 | 4948.11 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.172070 | 0.172070 | 0.172070 | 0.172070 | 2130.01 | 2130.01 | 3496.16 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.170381 | 0.170381 | 0.170381 | 0.170381 | 2108.40 | 2108.40 | 3496.07 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.234017 | 0.234017 | 0.234017 | 0.234017 | 3065.43 | 3065.43 | 3506.07 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.235173 | 0.235173 | 0.235173 | 0.235173 | 3080.16 | 3080.16 | 3505.98 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.425870 | 0.425870 | 0.425870 | 0.425870 | 5444.80 | 5444.80 | 5962.64 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.374854 | 0.374854 | 0.374854 | 0.374854 | 4746.24 | 4746.24 | 5961.99 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.387991 | 0.387991 | 0.387991 | 0.387991 | 4976.68 | 4976.68 | 5958.10 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.280186 | 0.280186 | 0.280186 | 0.280186 | 3521.11 | 3521.11 | 5957.44 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.212298 | 0.212298 | 0.212298 | 0.212298 | 2774.22 | 2774.22 | 4570.69 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.211810 | 0.211810 | 0.211810 | 0.211810 | 2774.49 | 2774.49 | 4570.58 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.318683 | 0.318683 | 0.318683 | 0.318683 | 4141.10 | 4141.10 | 4568.86 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.319814 | 0.319814 | 0.319814 | 0.319814 | 4155.52 | 4155.52 | 4568.76 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.258674 |
AIRLOOP G NW SUPPLY FAN | 0.232095 |
AIRLOOP OFFICE SUPPLY FAN | 0.348674 |
AIRLOOP G NE SUPPLY FAN | 0.165424 |
AIRLOOP G N1 SUPPLY FAN | 0.112723 |
AIRLOOP G N2 SUPPLY FAN | 0.111326 |
AIRLOOP G S1 SUPPLY FAN | 0.167600 |
AIRLOOP G S2 SUPPLY FAN | 0.173541 |
AIRLOOP F2 SW SUPPLY FAN | 0.339339 |
AIRLOOP F2 NW SUPPLY FAN | 0.301290 |
AIRLOOP F2 SE SUPPLY FAN | 0.324879 |
AIRLOOP F2 NE SUPPLY FAN | 0.221619 |
AIRLOOP F2 N1 SUPPLY FAN | 0.157670 |
AIRLOOP F2 N2 SUPPLY FAN | 0.155935 |
AIRLOOP F2 S1 SUPPLY FAN | 0.224061 |
AIRLOOP F2 S2 SUPPLY FAN | 0.226397 |
AIRLOOP F3 SW SUPPLY FAN | 0.340604 |
AIRLOOP F3 NW SUPPLY FAN | 0.304082 |
AIRLOOP F3 SE SUPPLY FAN | 0.309621 |
AIRLOOP F3 NE SUPPLY FAN | 0.226111 |
AIRLOOP F3 N1 SUPPLY FAN | 0.162262 |
AIRLOOP F3 N2 SUPPLY FAN | 0.160543 |
AIRLOOP F3 S1 SUPPLY FAN | 0.228268 |
AIRLOOP F3 S2 SUPPLY FAN | 0.229475 |
AIRLOOP F4 SW SUPPLY FAN | 0.341360 |
AIRLOOP F4 NW SUPPLY FAN | 0.305205 |
AIRLOOP F4 SE SUPPLY FAN | 0.309293 |
AIRLOOP F4 NE SUPPLY FAN | 0.227415 |
AIRLOOP F4 N1 SUPPLY FAN | 0.163921 |
AIRLOOP F4 N2 SUPPLY FAN | 0.162208 |
AIRLOOP F4 S1 SUPPLY FAN | 0.229638 |
AIRLOOP F4 S2 SUPPLY FAN | 0.230688 |
AIRLOOP M SW SUPPLY FAN | 0.344468 |
AIRLOOP M NW SUPPLY FAN | 0.308709 |
AIRLOOP M SE SUPPLY FAN | 0.312737 |
AIRLOOP M NE SUPPLY FAN | 0.230938 |
AIRLOOP M N1 SUPPLY FAN | 0.167574 |
AIRLOOP M N2 SUPPLY FAN | 0.165868 |
AIRLOOP M S1 SUPPLY FAN | 0.233097 |
AIRLOOP M S2 SUPPLY FAN | 0.234123 |
AIRLOOP F6 SW SUPPLY FAN | 0.340388 |
AIRLOOP F6 NW SUPPLY FAN | 0.304773 |
AIRLOOP F6 SE SUPPLY FAN | 0.309168 |
AIRLOOP F6 NE SUPPLY FAN | 0.227191 |
AIRLOOP F6 N1 SUPPLY FAN | 0.164107 |
AIRLOOP F6 N2 SUPPLY FAN | 0.162415 |
AIRLOOP F6 S1 SUPPLY FAN | 0.229375 |
AIRLOOP F6 S2 SUPPLY FAN | 0.230399 |
AIRLOOP F7 SW SUPPLY FAN | 0.338962 |
AIRLOOP F7 NW SUPPLY FAN | 0.303558 |
AIRLOOP F7 SE SUPPLY FAN | 0.308187 |
AIRLOOP F7 NE SUPPLY FAN | 0.226079 |
AIRLOOP F7 N1 SUPPLY FAN | 0.163177 |
AIRLOOP F7 N2 SUPPLY FAN | 0.161496 |
AIRLOOP F7 S1 SUPPLY FAN | 0.228221 |
AIRLOOP F7 S2 SUPPLY FAN | 0.229245 |
AIRLOOP F8 SW SUPPLY FAN | 0.338959 |
AIRLOOP F8 NW SUPPLY FAN | 0.303762 |
AIRLOOP F8 SE SUPPLY FAN | 0.308491 |
AIRLOOP F8 NE SUPPLY FAN | 0.226268 |
AIRLOOP F8 N1 SUPPLY FAN | 0.163648 |
AIRLOOP F8 N2 SUPPLY FAN | 0.161979 |
AIRLOOP F8 S1 SUPPLY FAN | 0.228388 |
AIRLOOP F8 S2 SUPPLY FAN | 0.229414 |
AIRLOOP F9 SW SUPPLY FAN | 0.348830 |
AIRLOOP F9 NW SUPPLY FAN | 0.313294 |
AIRLOOP F9 SE SUPPLY FAN | 0.315327 |
AIRLOOP F9 NE SUPPLY FAN | 0.229080 |
AIRLOOP F9 N1 SUPPLY FAN | 0.172070 |
AIRLOOP F9 N2 SUPPLY FAN | 0.170381 |
AIRLOOP F9 S1 SUPPLY FAN | 0.234017 |
AIRLOOP F9 S2 SUPPLY FAN | 0.235173 |
AIRLOOP T SW SUPPLY FAN | 0.425870 |
AIRLOOP T NW SUPPLY FAN | 0.374854 |
AIRLOOP T SE SUPPLY FAN | 0.387991 |
AIRLOOP T NE SUPPLY FAN | 0.280186 |
AIRLOOP T N1 SUPPLY FAN | 0.212298 |
AIRLOOP T N2 SUPPLY FAN | 0.211810 |
AIRLOOP T S1 SUPPLY FAN | 0.318683 |
AIRLOOP T S2 SUPPLY FAN | 0.319814 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.258674 | 3321.43 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.232095 | 2949.73 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.348674 | 4577.95 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.165424 | 2081.33 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.112723 | 1401.26 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.111326 | 1382.83 | 0.000030 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.167600 | 2254.65 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.173541 | 2330.41 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.339339 | 4333.48 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.301290 | 3817.10 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.324879 | 4220.88 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.221619 | 2777.95 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.157670 | 1970.77 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.155935 | 1948.47 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.224061 | 2964.33 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.226397 | 2994.12 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.340604 | 4338.86 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.304082 | 3842.03 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.309621 | 4016.05 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.226111 | 2824.91 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.162262 | 2023.57 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.160543 | 2001.49 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.228268 | 3011.76 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.229475 | 3027.15 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.341360 | 4340.46 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.305205 | 3857.98 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.309293 | 4004.06 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.227415 | 2850.73 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.163921 | 2040.22 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.162208 | 2018.24 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.229638 | 3024.55 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.230688 | 3037.94 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.344468 | 4373.53 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.308709 | 3896.13 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.312737 | 4047.10 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.230938 | 2889.37 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.167574 | 2083.34 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.165868 | 2061.46 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.233097 | 3064.80 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.234123 | 3077.88 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.340388 | 4315.91 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.304773 | 3840.33 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.309168 | 3996.27 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.227191 | 2836.62 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.164107 | 2035.60 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.162415 | 2013.91 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.229375 | 3014.15 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.230399 | 3027.21 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.338962 | 4292.82 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.303558 | 3819.94 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.308187 | 3979.05 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.226079 | 2817.98 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.163177 | 2020.84 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.161496 | 1999.30 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.228221 | 2996.62 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.229245 | 3009.66 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.338959 | 4288.38 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.303762 | 3818.16 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.308491 | 3978.66 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.226268 | 2816.33 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.163648 | 2024.36 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.161979 | 2002.99 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.228388 | 2996.17 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.229414 | 3009.25 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.348830 | 4410.10 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.313294 | 3935.64 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.315327 | 4061.64 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.229080 | 2848.25 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.172070 | 2130.01 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.170381 | 2108.40 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.234017 | 3065.43 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.235173 | 3080.16 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.425870 | 5444.80 | 0.000119 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.374854 | 4746.24 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.387991 | 4976.68 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.280186 | 3521.11 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.212298 | 2774.22 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.211810 | 2774.49 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.318683 | 4141.10 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.319814 | 4155.52 | 0.000091 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 4534.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 4551.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 5645.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 4557.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 3509.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 3509.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 3490.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 3498.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 4373.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 4380.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 4403.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 4386.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 3123.89 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 3124.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 3120.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 3121.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 4357.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 4363.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 4363.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 4367.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 3065.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 3065.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 3060.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 3060.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 4415.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 4420.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 4417.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 4421.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 3086.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 3086.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 3082.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 3082.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 4450.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 4451.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 4450.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 4451.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 3090.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 3090.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 3089.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 3089.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 4551.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 4552.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 4550.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 4551.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 3164.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 3164.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 3165.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 3165.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 4621.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 4620.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 4619.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 4618.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 3211.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 3211.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 3213.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 3213.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 4699.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 4695.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 4696.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 4692.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 3268.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 3268.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 3273.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 3273.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 4961.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 4952.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 4957.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 4948.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 3496.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 3496.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 3506.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 3505.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 5962.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 5961.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 5958.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 5957.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 4570.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 4570.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 4568.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 4568.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005553 | 6.25 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005553 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005553 | 2680.67 | 8.07 | 7267.99 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005553 | 1416.30 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -8.8 |
February | 22.02 | -2.2 |
March | 22.12 | 0.30 |
April | 22.51 | 6.67 |
May | 22.94 | 10.10 |
June | 24.00 | 16.46 |
July | 24.28 | 20.57 |
August | 24.23 | 19.17 |
September | 23.80 | 14.69 |
October | 22.90 | 8.64 |
November | 22.22 | 2.84 |
December | 21.78 | -4.1 |
Annual Sum or Average | 22.89 | 7.07 |
Minimum of Months | 21.78 | -8.8 |
Maximum of Months | 24.28 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.06 | 6.67 |
May | 22.66 | 10.10 |
June | 23.93 | 16.46 |
July | 24.26 | 20.57 |
August | 24.14 | 19.17 |
September | 23.45 | 14.69 |
October | 22.17 | 8.64 |
November | 21.76 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.61 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.26 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.09 | -2.2 |
March | 22.21 | 0.30 |
April | 22.61 | 6.67 |
May | 23.10 | 10.10 |
June | 24.07 | 16.46 |
July | 24.32 | 20.57 |
August | 24.29 | 19.17 |
September | 23.88 | 14.69 |
October | 22.92 | 8.64 |
November | 22.31 | 2.84 |
December | 21.89 | -4.1 |
Annual Sum or Average | 22.96 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.71 | -2.2 |
March | 21.72 | 0.30 |
April | 22.01 | 6.67 |
May | 22.54 | 10.10 |
June | 23.88 | 16.46 |
July | 24.25 | 20.57 |
August | 24.14 | 19.17 |
September | 23.39 | 14.69 |
October | 22.05 | 8.64 |
November | 21.72 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.57 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.25 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.70 | -2.2 |
March | 21.71 | 0.30 |
April | 21.87 | 6.67 |
May | 22.36 | 10.10 |
June | 23.79 | 16.46 |
July | 24.21 | 20.57 |
August | 24.08 | 19.17 |
September | 23.35 | 14.69 |
October | 22.04 | 8.64 |
November | 21.74 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.52 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.21 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.70 | -2.2 |
March | 21.71 | 0.30 |
April | 21.87 | 6.67 |
May | 22.36 | 10.10 |
June | 23.79 | 16.46 |
July | 24.21 | 20.57 |
August | 24.08 | 19.17 |
September | 23.35 | 14.69 |
October | 22.03 | 8.64 |
November | 21.73 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.52 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.21 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | -8.8 |
February | 22.07 | -2.2 |
March | 22.15 | 0.30 |
April | 22.46 | 6.67 |
May | 22.79 | 10.10 |
June | 23.97 | 16.46 |
July | 24.26 | 20.57 |
August | 24.24 | 19.17 |
September | 23.91 | 14.69 |
October | 23.04 | 8.64 |
November | 22.34 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 22.91 | 7.07 |
Minimum of Months | 21.81 | -8.8 |
Maximum of Months | 24.26 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.08 | -2.2 |
March | 22.17 | 0.30 |
April | 22.49 | 6.67 |
May | 22.83 | 10.10 |
June | 23.99 | 16.46 |
July | 24.27 | 20.57 |
August | 24.25 | 19.17 |
September | 23.93 | 14.69 |
October | 23.07 | 8.64 |
November | 22.37 | 2.84 |
December | 21.84 | -4.1 |
Annual Sum or Average | 22.93 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.27 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.16 | -8.8 |
February | 16.90 | -2.2 |
March | 17.74 | 0.30 |
April | 19.54 | 6.67 |
May | 20.73 | 10.10 |
June | 23.69 | 16.46 |
July | 25.07 | 20.57 |
August | 24.57 | 19.17 |
September | 23.03 | 14.69 |
October | 20.28 | 8.64 |
November | 18.26 | 2.84 |
December | 16.27 | -4.1 |
Annual Sum or Average | 20.12 | 7.07 |
Minimum of Months | 15.16 | -8.8 |
Maximum of Months | 25.07 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.22 | -2.2 |
March | 22.45 | 0.30 |
April | 23.09 | 6.67 |
May | 23.54 | 10.10 |
June | 24.26 | 16.46 |
July | 24.36 | 20.57 |
August | 24.33 | 19.17 |
September | 23.99 | 14.69 |
October | 23.54 | 8.64 |
November | 22.63 | 2.84 |
December | 21.84 | -4.1 |
Annual Sum or Average | 23.18 | 7.07 |
Minimum of Months | 21.84 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.83 | 0.30 |
April | 22.48 | 6.67 |
May | 23.23 | 10.10 |
June | 24.20 | 16.46 |
July | 24.35 | 20.57 |
August | 24.27 | 19.17 |
September | 23.59 | 14.69 |
October | 22.58 | 8.64 |
November | 21.84 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.80 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.24 | -2.2 |
March | 22.52 | 0.30 |
April | 23.15 | 6.67 |
May | 23.59 | 10.10 |
June | 24.29 | 16.46 |
July | 24.37 | 20.57 |
August | 24.36 | 19.17 |
September | 24.04 | 14.69 |
October | 23.59 | 8.64 |
November | 22.67 | 2.84 |
December | 21.86 | -4.1 |
Annual Sum or Average | 23.22 | 7.07 |
Minimum of Months | 21.86 | -8.8 |
Maximum of Months | 24.37 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.78 | 0.30 |
April | 22.41 | 6.67 |
May | 23.12 | 10.10 |
June | 24.17 | 16.46 |
July | 24.35 | 20.57 |
August | 24.29 | 19.17 |
September | 23.52 | 14.69 |
October | 22.38 | 8.64 |
November | 21.77 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.75 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.25 | 6.67 |
May | 22.99 | 10.10 |
June | 24.14 | 16.46 |
July | 24.32 | 20.57 |
August | 24.25 | 19.17 |
September | 23.52 | 14.69 |
October | 22.48 | 8.64 |
November | 21.84 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.73 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.25 | 6.67 |
May | 22.98 | 10.10 |
June | 24.13 | 16.46 |
July | 24.32 | 20.57 |
August | 24.25 | 19.17 |
September | 23.52 | 14.69 |
October | 22.47 | 8.64 |
November | 21.84 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.73 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | -8.8 |
February | 22.37 | -2.2 |
March | 22.65 | 0.30 |
April | 23.18 | 6.67 |
May | 23.50 | 10.10 |
June | 24.24 | 16.46 |
July | 24.34 | 20.57 |
August | 24.34 | 19.17 |
September | 24.11 | 14.69 |
October | 23.78 | 8.64 |
November | 22.92 | 2.84 |
December | 21.99 | -4.1 |
Annual Sum or Average | 23.29 | 7.07 |
Minimum of Months | 21.98 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | -8.8 |
February | 22.38 | -2.2 |
March | 22.66 | 0.30 |
April | 23.20 | 6.67 |
May | 23.50 | 10.10 |
June | 24.25 | 16.46 |
July | 24.35 | 20.57 |
August | 24.35 | 19.17 |
September | 24.12 | 14.69 |
October | 23.79 | 8.64 |
November | 22.93 | 2.84 |
December | 22.00 | -4.1 |
Annual Sum or Average | 23.30 | 7.07 |
Minimum of Months | 21.98 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | -8.8 |
February | 21.90 | -2.2 |
March | 22.47 | 0.30 |
April | 23.50 | 6.67 |
May | 24.26 | 10.10 |
June | 25.92 | 16.46 |
July | 26.43 | 20.57 |
August | 26.22 | 19.17 |
September | 25.27 | 14.69 |
October | 23.92 | 8.64 |
November | 22.54 | 2.84 |
December | 21.43 | -4.1 |
Annual Sum or Average | 23.76 | 7.07 |
Minimum of Months | 21.08 | -8.8 |
Maximum of Months | 26.43 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | -8.8 |
February | 22.23 | -2.2 |
March | 22.51 | 0.30 |
April | 23.19 | 6.67 |
May | 23.61 | 10.10 |
June | 24.27 | 16.46 |
July | 24.36 | 20.57 |
August | 24.33 | 19.17 |
September | 23.98 | 14.69 |
October | 23.64 | 8.64 |
November | 22.69 | 2.84 |
December | 21.84 | -4.1 |
Annual Sum or Average | 23.21 | 7.07 |
Minimum of Months | 21.84 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.77 | -2.2 |
March | 21.83 | 0.30 |
April | 22.58 | 6.67 |
May | 23.32 | 10.10 |
June | 24.22 | 16.46 |
July | 24.35 | 20.57 |
August | 24.27 | 19.17 |
September | 23.55 | 14.69 |
October | 22.67 | 8.64 |
November | 21.86 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.82 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.22 | -2.2 |
March | 22.53 | 0.30 |
April | 23.19 | 6.67 |
May | 23.60 | 10.10 |
June | 24.27 | 16.46 |
July | 24.37 | 20.57 |
August | 24.35 | 19.17 |
September | 23.99 | 14.69 |
October | 23.62 | 8.64 |
November | 22.67 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.21 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.37 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.51 | 6.67 |
May | 23.22 | 10.10 |
June | 24.19 | 16.46 |
July | 24.35 | 20.57 |
August | 24.29 | 19.17 |
September | 23.49 | 14.69 |
October | 22.47 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.77 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.41 | 6.67 |
May | 23.14 | 10.10 |
June | 24.17 | 16.46 |
July | 24.33 | 20.57 |
August | 24.26 | 19.17 |
September | 23.52 | 14.69 |
October | 22.65 | 8.64 |
November | 21.88 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.78 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.40 | 6.67 |
May | 23.13 | 10.10 |
June | 24.17 | 16.46 |
July | 24.33 | 20.57 |
August | 24.26 | 19.17 |
September | 23.51 | 14.69 |
October | 22.63 | 8.64 |
November | 21.88 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.78 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | -8.8 |
February | 22.42 | -2.2 |
March | 22.78 | 0.30 |
April | 23.36 | 6.67 |
May | 23.62 | 10.10 |
June | 24.26 | 16.46 |
July | 24.34 | 20.57 |
August | 24.35 | 19.17 |
September | 24.12 | 14.69 |
October | 23.93 | 8.64 |
November | 23.05 | 2.84 |
December | 22.03 | -4.1 |
Annual Sum or Average | 23.36 | 7.07 |
Minimum of Months | 22.03 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | -8.8 |
February | 22.43 | -2.2 |
March | 22.78 | 0.30 |
April | 23.37 | 6.67 |
May | 23.62 | 10.10 |
June | 24.27 | 16.46 |
July | 24.34 | 20.57 |
August | 24.35 | 19.17 |
September | 24.12 | 14.69 |
October | 23.93 | 8.64 |
November | 23.06 | 2.84 |
December | 22.03 | -4.1 |
Annual Sum or Average | 23.36 | 7.07 |
Minimum of Months | 22.03 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | -8.8 |
February | 22.36 | -2.2 |
March | 22.94 | 0.30 |
April | 23.99 | 6.67 |
May | 24.73 | 10.10 |
June | 26.17 | 16.46 |
July | 26.58 | 20.57 |
August | 26.39 | 19.17 |
September | 25.44 | 14.69 |
October | 24.36 | 8.64 |
November | 22.97 | 2.84 |
December | 21.87 | -4.1 |
Annual Sum or Average | 24.12 | 7.07 |
Minimum of Months | 21.60 | -8.8 |
Maximum of Months | 26.58 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.20 | -2.2 |
March | 22.49 | 0.30 |
April | 23.18 | 6.67 |
May | 23.61 | 10.10 |
June | 24.26 | 16.46 |
July | 24.36 | 20.57 |
August | 24.33 | 19.17 |
September | 23.94 | 14.69 |
October | 23.63 | 8.64 |
November | 22.67 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.20 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.83 | 0.30 |
April | 22.58 | 6.67 |
May | 23.32 | 10.10 |
June | 24.21 | 16.46 |
July | 24.34 | 20.57 |
August | 24.27 | 19.17 |
September | 23.52 | 14.69 |
October | 22.68 | 8.64 |
November | 21.86 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.82 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | -8.8 |
February | 22.20 | -2.2 |
March | 22.50 | 0.30 |
April | 23.17 | 6.67 |
May | 23.59 | 10.10 |
June | 24.26 | 16.46 |
July | 24.36 | 20.57 |
August | 24.35 | 19.17 |
September | 23.95 | 14.69 |
October | 23.61 | 8.64 |
November | 22.64 | 2.84 |
December | 21.81 | -4.1 |
Annual Sum or Average | 23.19 | 7.07 |
Minimum of Months | 21.81 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.51 | 6.67 |
May | 23.23 | 10.10 |
June | 24.18 | 16.46 |
July | 24.35 | 20.57 |
August | 24.28 | 19.17 |
September | 23.46 | 14.69 |
October | 22.48 | 8.64 |
November | 21.78 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.77 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.45 | 6.67 |
May | 23.18 | 10.10 |
June | 24.18 | 16.46 |
July | 24.33 | 20.57 |
August | 24.26 | 19.17 |
September | 23.50 | 14.69 |
October | 22.71 | 8.64 |
November | 21.89 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.79 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.44 | 6.67 |
May | 23.17 | 10.10 |
June | 24.18 | 16.46 |
July | 24.33 | 20.57 |
August | 24.26 | 19.17 |
September | 23.49 | 14.69 |
October | 22.68 | 8.64 |
November | 21.89 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.79 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | -8.8 |
February | 22.41 | -2.2 |
March | 22.78 | 0.30 |
April | 23.39 | 6.67 |
May | 23.63 | 10.10 |
June | 24.26 | 16.46 |
July | 24.34 | 20.57 |
August | 24.35 | 19.17 |
September | 24.11 | 14.69 |
October | 23.95 | 8.64 |
November | 23.07 | 2.84 |
December | 22.02 | -4.1 |
Annual Sum or Average | 23.37 | 7.07 |
Minimum of Months | 22.02 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | -8.8 |
February | 22.41 | -2.2 |
March | 22.79 | 0.30 |
April | 23.39 | 6.67 |
May | 23.63 | 10.10 |
June | 24.26 | 16.46 |
July | 24.34 | 20.57 |
August | 24.35 | 19.17 |
September | 24.11 | 14.69 |
October | 23.95 | 8.64 |
November | 23.06 | 2.84 |
December | 22.02 | -4.1 |
Annual Sum or Average | 23.37 | 7.07 |
Minimum of Months | 22.02 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -8.8 |
February | 22.49 | -2.2 |
March | 23.09 | 0.30 |
April | 24.15 | 6.67 |
May | 24.89 | 10.10 |
June | 26.27 | 16.46 |
July | 26.67 | 20.57 |
August | 26.48 | 19.17 |
September | 25.52 | 14.69 |
October | 24.51 | 8.64 |
November | 23.11 | 2.84 |
December | 22.00 | -4.1 |
Annual Sum or Average | 24.25 | 7.07 |
Minimum of Months | 21.74 | -8.8 |
Maximum of Months | 26.67 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | -8.8 |
February | 22.19 | -2.2 |
March | 22.47 | 0.30 |
April | 23.16 | 6.67 |
May | 23.59 | 10.10 |
June | 24.25 | 16.46 |
July | 24.36 | 20.57 |
August | 24.32 | 19.17 |
September | 23.92 | 14.69 |
October | 23.61 | 8.64 |
November | 22.65 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 23.19 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.82 | 0.30 |
April | 22.57 | 6.67 |
May | 23.32 | 10.10 |
June | 24.20 | 16.46 |
July | 24.34 | 20.57 |
August | 24.26 | 19.17 |
September | 23.50 | 14.69 |
October | 22.67 | 8.64 |
November | 21.86 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.81 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | -8.8 |
February | 22.18 | -2.2 |
March | 22.48 | 0.30 |
April | 23.15 | 6.67 |
May | 23.57 | 10.10 |
June | 24.25 | 16.46 |
July | 24.36 | 20.57 |
August | 24.34 | 19.17 |
September | 23.93 | 14.69 |
October | 23.59 | 8.64 |
November | 22.62 | 2.84 |
December | 21.80 | -4.1 |
Annual Sum or Average | 23.18 | 7.07 |
Minimum of Months | 21.80 | -8.8 |
Maximum of Months | 24.36 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.50 | 6.67 |
May | 23.22 | 10.10 |
June | 24.17 | 16.46 |
July | 24.35 | 20.57 |
August | 24.28 | 19.17 |
September | 23.44 | 14.69 |
October | 22.48 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.77 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.75 | -2.2 |
March | 21.79 | 0.30 |
April | 22.46 | 6.67 |
May | 23.19 | 10.10 |
June | 24.18 | 16.46 |
July | 24.33 | 20.57 |
August | 24.25 | 19.17 |
September | 23.49 | 14.69 |
October | 22.73 | 8.64 |
November | 21.90 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.80 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.75 | -2.2 |
March | 21.79 | 0.30 |
April | 22.46 | 6.67 |
May | 23.18 | 10.10 |
June | 24.18 | 16.46 |
July | 24.33 | 20.57 |
August | 24.26 | 19.17 |
September | 23.48 | 14.69 |
October | 22.70 | 8.64 |
November | 21.89 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.79 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | -8.8 |
February | 22.40 | -2.2 |
March | 22.78 | 0.30 |
April | 23.39 | 6.67 |
May | 23.63 | 10.10 |
June | 24.26 | 16.46 |
July | 24.34 | 20.57 |
August | 24.34 | 19.17 |
September | 24.09 | 14.69 |
October | 23.95 | 8.64 |
November | 23.06 | 2.84 |
December | 22.01 | -4.1 |
Annual Sum or Average | 23.36 | 7.07 |
Minimum of Months | 22.01 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | -8.8 |
February | 22.40 | -2.2 |
March | 22.79 | 0.30 |
April | 23.40 | 6.67 |
May | 23.63 | 10.10 |
June | 24.26 | 16.46 |
July | 24.34 | 20.57 |
August | 24.34 | 19.17 |
September | 24.09 | 14.69 |
October | 23.95 | 8.64 |
November | 23.06 | 2.84 |
December | 22.01 | -4.1 |
Annual Sum or Average | 23.36 | 7.07 |
Minimum of Months | 22.01 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | -8.8 |
February | 23.13 | -2.2 |
March | 23.71 | 0.30 |
April | 24.78 | 6.67 |
May | 25.50 | 10.10 |
June | 26.87 | 16.46 |
July | 27.27 | 20.57 |
August | 27.08 | 19.17 |
September | 26.11 | 14.69 |
October | 25.13 | 8.64 |
November | 23.74 | 2.84 |
December | 22.66 | -4.1 |
Annual Sum or Average | 24.87 | 7.07 |
Minimum of Months | 22.39 | -8.8 |
Maximum of Months | 27.27 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | -8.8 |
February | 22.15 | -2.2 |
March | 22.39 | 0.30 |
April | 23.08 | 6.67 |
May | 23.52 | 10.10 |
June | 24.21 | 16.46 |
July | 24.34 | 20.57 |
August | 24.31 | 19.17 |
September | 23.86 | 14.69 |
October | 23.52 | 8.64 |
November | 22.57 | 2.84 |
December | 21.79 | -4.1 |
Annual Sum or Average | 23.14 | 7.07 |
Minimum of Months | 21.79 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.75 | -2.2 |
March | 21.80 | 0.30 |
April | 22.48 | 6.67 |
May | 23.24 | 10.10 |
June | 24.16 | 16.46 |
July | 24.33 | 20.57 |
August | 24.23 | 19.17 |
September | 23.42 | 14.69 |
October | 22.55 | 8.64 |
November | 21.82 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.77 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.14 | -2.2 |
March | 22.40 | 0.30 |
April | 23.07 | 6.67 |
May | 23.50 | 10.10 |
June | 24.22 | 16.46 |
July | 24.35 | 20.57 |
August | 24.33 | 19.17 |
September | 23.86 | 14.69 |
October | 23.49 | 8.64 |
November | 22.53 | 2.84 |
December | 21.78 | -4.1 |
Annual Sum or Average | 23.13 | 7.07 |
Minimum of Months | 21.78 | -8.8 |
Maximum of Months | 24.35 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.41 | 6.67 |
May | 23.14 | 10.10 |
June | 24.13 | 16.46 |
July | 24.33 | 20.57 |
August | 24.25 | 19.17 |
September | 23.36 | 14.69 |
October | 22.36 | 8.64 |
November | 21.76 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.73 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.77 | 0.30 |
April | 22.36 | 6.67 |
May | 23.11 | 10.10 |
June | 24.13 | 16.46 |
July | 24.31 | 20.57 |
August | 24.22 | 19.17 |
September | 23.40 | 14.69 |
October | 22.60 | 8.64 |
November | 21.86 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.75 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.77 | 0.30 |
April | 22.35 | 6.67 |
May | 23.10 | 10.10 |
June | 24.13 | 16.46 |
July | 24.31 | 20.57 |
August | 24.22 | 19.17 |
September | 23.39 | 14.69 |
October | 22.58 | 8.64 |
November | 21.85 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.74 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | -8.8 |
February | 22.35 | -2.2 |
March | 22.70 | 0.30 |
April | 23.30 | 6.67 |
May | 23.55 | 10.10 |
June | 24.22 | 16.46 |
July | 24.33 | 20.57 |
August | 24.33 | 19.17 |
September | 24.03 | 14.69 |
October | 23.87 | 8.64 |
November | 22.97 | 2.84 |
December | 21.96 | -4.1 |
Annual Sum or Average | 23.30 | 7.07 |
Minimum of Months | 21.96 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | -8.8 |
February | 22.35 | -2.2 |
March | 22.70 | 0.30 |
April | 23.30 | 6.67 |
May | 23.55 | 10.10 |
June | 24.23 | 16.46 |
July | 24.33 | 20.57 |
August | 24.33 | 19.17 |
September | 24.03 | 14.69 |
October | 23.87 | 8.64 |
November | 22.97 | 2.84 |
December | 21.96 | -4.1 |
Annual Sum or Average | 23.30 | 7.07 |
Minimum of Months | 21.96 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -8.8 |
February | 22.42 | -2.2 |
March | 23.00 | 0.30 |
April | 24.06 | 6.67 |
May | 24.80 | 10.10 |
June | 26.21 | 16.46 |
July | 26.65 | 20.57 |
August | 26.44 | 19.17 |
September | 25.42 | 14.69 |
October | 24.40 | 8.64 |
November | 23.03 | 2.84 |
December | 21.94 | -4.1 |
Annual Sum or Average | 24.18 | 7.07 |
Minimum of Months | 21.68 | -8.8 |
Maximum of Months | 26.65 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | -8.8 |
February | 22.12 | -2.2 |
March | 22.33 | 0.30 |
April | 23.01 | 6.67 |
May | 23.47 | 10.10 |
June | 24.19 | 16.46 |
July | 24.34 | 20.57 |
August | 24.29 | 19.17 |
September | 23.81 | 14.69 |
October | 23.44 | 8.64 |
November | 22.50 | 2.84 |
December | 21.78 | -4.1 |
Annual Sum or Average | 23.10 | 7.07 |
Minimum of Months | 21.78 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.79 | 0.30 |
April | 22.41 | 6.67 |
May | 23.18 | 10.10 |
June | 24.12 | 16.46 |
July | 24.32 | 20.57 |
August | 24.21 | 19.17 |
September | 23.37 | 14.69 |
October | 22.46 | 8.64 |
November | 21.80 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.74 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -8.8 |
February | 22.12 | -2.2 |
March | 22.35 | 0.30 |
April | 23.01 | 6.67 |
May | 23.45 | 10.10 |
June | 24.19 | 16.46 |
July | 24.34 | 20.57 |
August | 24.31 | 19.17 |
September | 23.82 | 14.69 |
October | 23.42 | 8.64 |
November | 22.47 | 2.84 |
December | 21.76 | -4.1 |
Annual Sum or Average | 23.09 | 7.07 |
Minimum of Months | 21.76 | -8.8 |
Maximum of Months | 24.34 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.75 | 0.30 |
April | 22.35 | 6.67 |
May | 23.09 | 10.10 |
June | 24.09 | 16.46 |
July | 24.32 | 20.57 |
August | 24.22 | 19.17 |
September | 23.31 | 14.69 |
October | 22.29 | 8.64 |
November | 21.75 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.70 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.28 | 6.67 |
May | 23.05 | 10.10 |
June | 24.10 | 16.46 |
July | 24.30 | 20.57 |
August | 24.20 | 19.17 |
September | 23.34 | 14.69 |
October | 22.50 | 8.64 |
November | 21.83 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.71 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.76 | 0.30 |
April | 22.28 | 6.67 |
May | 23.05 | 10.10 |
June | 24.10 | 16.46 |
July | 24.30 | 20.57 |
August | 24.20 | 19.17 |
September | 23.34 | 14.69 |
October | 22.48 | 8.64 |
November | 21.83 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.71 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | -8.8 |
February | 22.31 | -2.2 |
March | 22.63 | 0.30 |
April | 23.22 | 6.67 |
May | 23.50 | 10.10 |
June | 24.20 | 16.46 |
July | 24.32 | 20.57 |
August | 24.32 | 19.17 |
September | 23.97 | 14.69 |
October | 23.80 | 8.64 |
November | 22.90 | 2.84 |
December | 21.92 | -4.1 |
Annual Sum or Average | 23.26 | 7.07 |
Minimum of Months | 21.92 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | -8.8 |
February | 22.31 | -2.2 |
March | 22.63 | 0.30 |
April | 23.23 | 6.67 |
May | 23.50 | 10.10 |
June | 24.20 | 16.46 |
July | 24.32 | 20.57 |
August | 24.32 | 19.17 |
September | 23.97 | 14.69 |
October | 23.80 | 8.64 |
November | 22.90 | 2.84 |
December | 21.92 | -4.1 |
Annual Sum or Average | 23.26 | 7.07 |
Minimum of Months | 21.92 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | -8.8 |
February | 22.25 | -2.2 |
March | 22.83 | 0.30 |
April | 23.87 | 6.67 |
May | 24.64 | 10.10 |
June | 26.08 | 16.46 |
July | 26.55 | 20.57 |
August | 26.34 | 19.17 |
September | 25.27 | 14.69 |
October | 24.21 | 8.64 |
November | 22.85 | 2.84 |
December | 21.79 | -4.1 |
Annual Sum or Average | 24.03 | 7.07 |
Minimum of Months | 21.52 | -8.8 |
Maximum of Months | 26.55 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -8.8 |
February | 22.10 | -2.2 |
March | 22.28 | 0.30 |
April | 22.95 | 6.67 |
May | 23.43 | 10.10 |
June | 24.16 | 16.46 |
July | 24.33 | 20.57 |
August | 24.28 | 19.17 |
September | 23.76 | 14.69 |
October | 23.36 | 8.64 |
November | 22.45 | 2.84 |
December | 21.76 | -4.1 |
Annual Sum or Average | 23.06 | 7.07 |
Minimum of Months | 21.76 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.74 | -2.2 |
March | 21.78 | 0.30 |
April | 22.36 | 6.67 |
May | 23.14 | 10.10 |
June | 24.09 | 16.46 |
July | 24.31 | 20.57 |
August | 24.19 | 19.17 |
September | 23.33 | 14.69 |
October | 22.39 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.72 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | -8.8 |
February | 22.09 | -2.2 |
March | 22.30 | 0.30 |
April | 22.96 | 6.67 |
May | 23.41 | 10.10 |
June | 24.17 | 16.46 |
July | 24.33 | 20.57 |
August | 24.30 | 19.17 |
September | 23.77 | 14.69 |
October | 23.34 | 8.64 |
November | 22.41 | 2.84 |
December | 21.75 | -4.1 |
Annual Sum or Average | 23.06 | 7.07 |
Minimum of Months | 21.75 | -8.8 |
Maximum of Months | 24.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.74 | 0.30 |
April | 22.30 | 6.67 |
May | 23.04 | 10.10 |
June | 24.06 | 16.46 |
July | 24.32 | 20.57 |
August | 24.20 | 19.17 |
September | 23.27 | 14.69 |
October | 22.23 | 8.64 |
November | 21.74 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.67 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.75 | 0.30 |
April | 22.23 | 6.67 |
May | 23.01 | 10.10 |
June | 24.06 | 16.46 |
July | 24.29 | 20.57 |
August | 24.18 | 19.17 |
September | 23.29 | 14.69 |
October | 22.42 | 8.64 |
November | 21.81 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.69 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.29 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.75 | 0.30 |
April | 22.23 | 6.67 |
May | 23.00 | 10.10 |
June | 24.06 | 16.46 |
July | 24.29 | 20.57 |
August | 24.18 | 19.17 |
September | 23.29 | 14.69 |
October | 22.40 | 8.64 |
November | 21.81 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.68 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.29 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | -8.8 |
February | 22.27 | -2.2 |
March | 22.57 | 0.30 |
April | 23.15 | 6.67 |
May | 23.45 | 10.10 |
June | 24.17 | 16.46 |
July | 24.31 | 20.57 |
August | 24.30 | 19.17 |
September | 23.92 | 14.69 |
October | 23.72 | 8.64 |
November | 22.83 | 2.84 |
December | 21.89 | -4.1 |
Annual Sum or Average | 23.21 | 7.07 |
Minimum of Months | 21.89 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | -8.8 |
February | 22.27 | -2.2 |
March | 22.57 | 0.30 |
April | 23.16 | 6.67 |
May | 23.45 | 10.10 |
June | 24.18 | 16.46 |
July | 24.31 | 20.57 |
August | 24.30 | 19.17 |
September | 23.92 | 14.69 |
October | 23.72 | 8.64 |
November | 22.83 | 2.84 |
December | 21.89 | -4.1 |
Annual Sum or Average | 23.22 | 7.07 |
Minimum of Months | 21.89 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | -8.8 |
February | 22.16 | -2.2 |
March | 22.73 | 0.30 |
April | 23.76 | 6.67 |
May | 24.56 | 10.10 |
June | 26.03 | 16.46 |
July | 26.53 | 20.57 |
August | 26.30 | 19.17 |
September | 25.19 | 14.69 |
October | 24.08 | 8.64 |
November | 22.74 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 23.94 | 7.07 |
Minimum of Months | 21.42 | -8.8 |
Maximum of Months | 26.53 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -8.8 |
February | 22.06 | -2.2 |
March | 22.22 | 0.30 |
April | 22.87 | 6.67 |
May | 23.38 | 10.10 |
June | 24.12 | 16.46 |
July | 24.32 | 20.57 |
August | 24.26 | 19.17 |
September | 23.70 | 14.69 |
October | 23.24 | 8.64 |
November | 22.36 | 2.84 |
December | 21.75 | -4.1 |
Annual Sum or Average | 23.01 | 7.07 |
Minimum of Months | 21.75 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.77 | 0.30 |
April | 22.32 | 6.67 |
May | 23.10 | 10.10 |
June | 24.04 | 16.46 |
July | 24.30 | 20.57 |
August | 24.17 | 19.17 |
September | 23.29 | 14.69 |
October | 22.32 | 8.64 |
November | 21.77 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.69 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | -8.8 |
February | 22.06 | -2.2 |
March | 22.24 | 0.30 |
April | 22.89 | 6.67 |
May | 23.37 | 10.10 |
June | 24.13 | 16.46 |
July | 24.32 | 20.57 |
August | 24.28 | 19.17 |
September | 23.71 | 14.69 |
October | 23.22 | 8.64 |
November | 22.33 | 2.84 |
December | 21.74 | -4.1 |
Annual Sum or Average | 23.01 | 7.07 |
Minimum of Months | 21.74 | -8.8 |
Maximum of Months | 24.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.71 | -2.2 |
March | 21.73 | 0.30 |
April | 22.26 | 6.67 |
May | 23.01 | 10.10 |
June | 24.01 | 16.46 |
July | 24.31 | 20.57 |
August | 24.18 | 19.17 |
September | 23.22 | 14.69 |
October | 22.16 | 8.64 |
November | 21.73 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.65 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.31 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.74 | 0.30 |
April | 22.19 | 6.67 |
May | 22.98 | 10.10 |
June | 24.01 | 16.46 |
July | 24.28 | 20.57 |
August | 24.15 | 19.17 |
September | 23.25 | 14.69 |
October | 22.32 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.66 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.28 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.74 | 0.30 |
April | 22.19 | 6.67 |
May | 22.97 | 10.10 |
June | 24.01 | 16.46 |
July | 24.28 | 20.57 |
August | 24.15 | 19.17 |
September | 23.24 | 14.69 |
October | 22.31 | 8.64 |
November | 21.78 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.66 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.28 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | -8.8 |
February | 22.22 | -2.2 |
March | 22.47 | 0.30 |
April | 23.04 | 6.67 |
May | 23.41 | 10.10 |
June | 24.14 | 16.46 |
July | 24.30 | 20.57 |
August | 24.28 | 19.17 |
September | 23.83 | 14.69 |
October | 23.56 | 8.64 |
November | 22.70 | 2.84 |
December | 21.85 | -4.1 |
Annual Sum or Average | 23.15 | 7.07 |
Minimum of Months | 21.85 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | -8.8 |
February | 22.22 | -2.2 |
March | 22.47 | 0.30 |
April | 23.05 | 6.67 |
May | 23.41 | 10.10 |
June | 24.14 | 16.46 |
July | 24.30 | 20.57 |
August | 24.28 | 19.17 |
September | 23.84 | 14.69 |
October | 23.57 | 8.64 |
November | 22.70 | 2.84 |
December | 21.85 | -4.1 |
Annual Sum or Average | 23.15 | 7.07 |
Minimum of Months | 21.85 | -8.8 |
Maximum of Months | 24.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | -8.8 |
February | 21.97 | -2.2 |
March | 22.53 | 0.30 |
April | 23.62 | 6.67 |
May | 24.48 | 10.10 |
June | 26.00 | 16.46 |
July | 26.57 | 20.57 |
August | 26.30 | 19.17 |
September | 25.10 | 14.69 |
October | 23.88 | 8.64 |
November | 22.53 | 2.84 |
December | 21.49 | -4.1 |
Annual Sum or Average | 23.81 | 7.07 |
Minimum of Months | 21.19 | -8.8 |
Maximum of Months | 26.57 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -8.8 |
February | 22.04 | -2.2 |
March | 22.19 | 0.30 |
April | 22.68 | 6.67 |
May | 23.23 | 10.10 |
June | 23.90 | 16.46 |
July | 24.23 | 20.57 |
August | 24.14 | 19.17 |
September | 23.50 | 14.69 |
October | 22.90 | 8.64 |
November | 22.27 | 2.84 |
December | 21.78 | -4.1 |
Annual Sum or Average | 22.89 | 7.07 |
Minimum of Months | 21.78 | -8.8 |
Maximum of Months | 24.23 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.76 | -2.2 |
March | 21.84 | 0.30 |
April | 22.33 | 6.67 |
May | 23.02 | 10.10 |
June | 23.83 | 16.46 |
July | 24.20 | 20.57 |
August | 24.03 | 19.17 |
September | 23.18 | 14.69 |
October | 22.29 | 8.64 |
November | 21.79 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.65 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.20 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -8.8 |
February | 22.05 | -2.2 |
March | 22.20 | 0.30 |
April | 22.71 | 6.67 |
May | 23.23 | 10.10 |
June | 23.93 | 16.46 |
July | 24.24 | 20.57 |
August | 24.16 | 19.17 |
September | 23.51 | 14.69 |
October | 22.89 | 8.64 |
November | 22.23 | 2.84 |
December | 21.77 | -4.1 |
Annual Sum or Average | 22.90 | 7.07 |
Minimum of Months | 21.77 | -8.8 |
Maximum of Months | 24.24 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.72 | -2.2 |
March | 21.78 | 0.30 |
April | 22.29 | 6.67 |
May | 22.96 | 10.10 |
June | 23.80 | 16.46 |
July | 24.20 | 20.57 |
August | 24.02 | 19.17 |
September | 23.11 | 14.69 |
October | 22.15 | 8.64 |
November | 21.73 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.60 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.20 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.78 | 0.30 |
April | 22.23 | 6.67 |
May | 22.93 | 10.10 |
June | 23.79 | 16.46 |
July | 24.19 | 20.57 |
August | 24.00 | 19.17 |
September | 23.12 | 14.69 |
October | 22.21 | 8.64 |
November | 21.78 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.60 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.19 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -8.8 |
February | 21.73 | -2.2 |
March | 21.78 | 0.30 |
April | 22.23 | 6.67 |
May | 22.93 | 10.10 |
June | 23.79 | 16.46 |
July | 24.18 | 20.57 |
August | 24.01 | 19.17 |
September | 23.12 | 14.69 |
October | 22.21 | 8.64 |
November | 21.78 | 2.84 |
December | 21.70 | -4.1 |
Annual Sum or Average | 22.60 | 7.07 |
Minimum of Months | 21.70 | -8.8 |
Maximum of Months | 24.18 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.15 | -2.2 |
March | 22.31 | 0.30 |
April | 22.79 | 6.67 |
May | 23.28 | 10.10 |
June | 23.95 | 16.46 |
July | 24.24 | 20.57 |
August | 24.18 | 19.17 |
September | 23.61 | 14.69 |
October | 23.14 | 8.64 |
November | 22.48 | 2.84 |
December | 21.87 | -4.1 |
Annual Sum or Average | 22.99 | 7.07 |
Minimum of Months | 21.86 | -8.8 |
Maximum of Months | 24.24 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | -8.8 |
February | 22.15 | -2.2 |
March | 22.31 | 0.30 |
April | 22.80 | 6.67 |
May | 23.29 | 10.10 |
June | 23.95 | 16.46 |
July | 24.24 | 20.57 |
August | 24.19 | 19.17 |
September | 23.61 | 14.69 |
October | 23.14 | 8.64 |
November | 22.48 | 2.84 |
December | 21.87 | -4.1 |
Annual Sum or Average | 22.99 | 7.07 |
Minimum of Months | 21.86 | -8.8 |
Maximum of Months | 24.24 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | -8.8 |
February | 21.75 | -2.2 |
March | 22.38 | 0.30 |
April | 23.71 | 6.67 |
May | 24.80 | 10.10 |
June | 26.49 | 16.46 |
July | 27.24 | 20.57 |
August | 26.84 | 19.17 |
September | 25.39 | 14.69 |
October | 23.86 | 8.64 |
November | 22.35 | 2.84 |
December | 21.13 | -4.1 |
Annual Sum or Average | 23.90 | 7.07 |
Minimum of Months | 20.69 | -8.8 |
Maximum of Months | 27.24 | 20.57 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.297319E+12 | 185892.936 | 05-JAN-19:00 | 25049.151 | 51564.864 | 22275.346 | 73815.635 | 0.000 | 10720.100 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.237230E+12 | 157694.425 | 04-FEB-18:00 | 22204.399 | 56867.515 | 22275.346 | 43027.950 | 0.000 | 10720.100 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.243131E+12 | 145101.685 | 03-MAR-20:00 | 25049.151 | 49704.829 | 22275.346 | 34953.461 | 0.000 | 10720.100 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.216544E+12 | 131932.657 | 01-APR-17:15 | 22204.399 | 56867.515 | 22275.346 | 27986.535 | 0.000 | 0.000 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.228744E+12 | 166964.555 | 19-MAY-17:15 | 22204.399 | 56867.515 | 22275.346 | 0.000 | 61086.701 | 0.000 | 1453.226 | 1931.732 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.245642E+12 | 167508.421 | 24-JUN-17:45 | 22204.399 | 56867.515 | 22275.346 | 0.000 | 61758.985 | 0.000 | 1453.226 | 1803.062 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.284402E+12 | 170401.690 | 17-JUL-17:15 | 22204.399 | 56867.515 | 22275.346 | 0.000 | 64339.206 | 0.000 | 1453.226 | 2116.362 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.272220E+12 | 170815.141 | 06-AUG-17:15 | 22204.399 | 56867.515 | 22275.346 | 0.000 | 64827.690 | 0.000 | 1453.226 | 2041.329 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.238775E+12 | 170215.841 | 02-SEP-17:15 | 22204.399 | 56867.515 | 22275.346 | 0.000 | 64191.456 | 0.000 | 1453.226 | 2078.263 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.226771E+12 | 141234.864 | 18-OCT-16:15 | 18221.747 | 56933.809 | 22275.346 | 0.000 | 39847.865 | 0.000 | 1453.226 | 1354.568 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.237659E+12 | 149334.110 | 26-NOV-18:00 | 22204.399 | 56867.515 | 22275.346 | 34667.635 | 0.000 | 10720.100 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.273470E+12 | 160958.956 | 31-DEC-07:00 | 14239.096 | 40592.208 | 22275.346 | 71066.841 | 0.000 | 10720.100 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.300191E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.216544E+12 | 131932.657 | 14239.096 | 40592.208 | 22275.346 | 0.000 | 0.000 | 0.000 | 1453.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.297319E+12 | 185892.936 | 25049.151 | 56933.809 | 22275.346 | 73815.635 | 64827.690 | 10720.100 | 1453.226 | 2116.362 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.408550E+12 | 318617.549 | 06-JAN-06:45 | 0.000 | 0.000 | 0.000 | 318617.549 | 87362.788 | 87362.788 | 231254.761 |
February | 0.262293E+12 | 278020.181 | 04-FEB-08:15 | 0.000 | 0.000 | 0.000 | 278020.181 | 91397.847 | 91397.847 | 186622.335 |
March | 0.218772E+12 | 259220.214 | 06-MAR-06:45 | 0.000 | 0.000 | 0.000 | 259220.214 | 88368.614 | 88368.614 | 170851.599 |
April | 0.136762E+12 | 168219.111 | 29-APR-06:15 | 0.000 | 0.000 | 0.000 | 168219.111 | 87871.947 | 87871.947 | 80347.164 |
May | 0.129397E+12 | 173997.258 | 08-MAY-05:45 | 0.000 | 0.000 | 0.000 | 173997.258 | 85202.416 | 85202.416 | 88794.842 |
June | 0.996738E+11 | 86490.137 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 86490.137 | 86490.137 | 86490.137 | 0.000 |
July | 0.978559E+11 | 84376.229 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 84376.229 | 84376.229 | 84376.229 | 0.000 |
August | 0.956117E+11 | 83040.009 | 01-AUG-06:45 | 0.000 | 0.000 | 0.000 | 83040.009 | 83040.009 | 83040.009 | 0.000 |
September | 0.967012E+11 | 108819.257 | 20-SEP-06:15 | 0.000 | 0.000 | 0.000 | 108819.257 | 82345.281 | 82345.281 | 26473.976 |
October | 0.114173E+12 | 162309.508 | 10-OCT-06:15 | 0.000 | 0.000 | 0.000 | 162309.508 | 83372.659 | 83372.659 | 78936.849 |
November | 0.195771E+12 | 242569.667 | 27-NOV-07:15 | 0.000 | 0.000 | 0.000 | 242569.667 | 86794.104 | 86794.104 | 155775.563 |
December | 0.325518E+12 | 316076.380 | 31-DEC-08:15 | 0.000 | 0.000 | 0.000 | 316076.380 | 89879.636 | 89879.636 | 226196.744 |
Annual Sum or Average | 0.218108E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.956117E+11 | 83040.009 | 0.000 | 0.000 | 0.000 | 83040.009 | 82345.281 | 82345.281 | 0.000 | |
Maximum of Months | 0.408550E+12 | 318617.549 | 0.000 | 0.000 | 0.000 | 318617.549 | 91397.847 | 91397.847 | 231254.761 |