Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2018-10-19 09:40:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4625.87 | 590.30 | 655.23 |
Net Site Energy | 4625.87 | 590.30 | 655.23 |
Total Source Energy | 11329.06 | 1445.68 | 1604.71 |
Net Source Energy | 11329.06 | 1445.68 | 1604.71 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 123.71 | 391.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 405.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.23 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1202.88 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3031.50 | 1594.36 | 0.00 | 0.00 | 0.00 | 6127.75 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 391.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 123.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 405.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 42.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 13.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.23 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1202.88 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 183.40 | 225.83 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.40 | 225.83 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 165.23 | 203.45 | 0.00 | 0.00 | 0.00 | 0.78 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 386.85 | 203.45 | 0.00 | 0.00 | 0.00 | 0.78 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3031.50 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3031.50 | 100.00 |
Total On-Site and Utility Electric Sources | 3031.50 | 100.00 |
Total Electricity End Uses | 3031.50 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6127.75 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6127.75 | 100.00 |
Total Water End Uses | 6127.75 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 124.75 |
Time Setpoint Not Met During Occupied Cooling | 390.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1493.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 19-MAR-07:15 | - | - | - | 26-JUN-17:15 |
Heating | 0.00 | 195077.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58819.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22475.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1376.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1866.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 87982.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 170957.00 | 283059.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 195077.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 58819.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22475.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1376.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1866.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 87982.13 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 391.80 | 424.37 | 0.00 | 0.00 | 0.00 |
Cooling | 1283.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2244.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 136.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 44.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1303.92 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9600.77 | 1728.29 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 55.50 | 60.11 | 0.00 | 0.00 | 0.00 |
Cooling | 181.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 317.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 184.69 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1359.90 | 244.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 55.50 | 60.11 | 0.00 | 0.00 | 0.00 |
Cooling | 181.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 317.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 184.69 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1359.90 | 244.80 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.67 | 83.67 | 168.38 | |
Exterior Lighting Total | 10720.10 | 168.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 241504.50 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 193203.60 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3140.46 | 2013.48 | 1126.98 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2982.23 | 1915.92 | 1066.31 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4135.24 | 2650.50 | 1484.74 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2027.42 | 1332.72 | 694.70 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1470.94 | 968.40 | 502.54 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1444.78 | 952.15 | 492.63 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1851.76 | 1186.33 | 665.43 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1922.53 | 1232.04 | 690.49 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4095.57 | 2619.00 | 1476.57 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3864.28 | 2475.16 | 1389.12 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3729.89 | 2382.43 | 1347.46 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2775.38 | 1810.67 | 964.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2024.27 | 1317.46 | 706.80 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2002.26 | 1303.75 | 698.50 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2485.33 | 1589.49 | 895.84 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2514.85 | 1608.02 | 906.83 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4115.38 | 2637.89 | 1477.49 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3893.13 | 2498.43 | 1394.70 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3524.24 | 2258.52 | 1265.72 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2810.50 | 1837.88 | 972.62 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2072.15 | 1350.31 | 721.84 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2050.22 | 1336.64 | 713.57 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2536.83 | 1624.82 | 912.02 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2551.79 | 1634.20 | 917.59 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4126.84 | 2649.01 | 1477.83 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3905.42 | 2510.04 | 1395.38 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3514.11 | 2255.96 | 1258.15 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2813.34 | 1843.53 | 969.81 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2089.20 | 1363.21 | 725.99 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2067.24 | 1349.52 | 717.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2554.62 | 1638.24 | 916.38 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2567.44 | 1646.28 | 921.16 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4168.83 | 2678.54 | 1490.29 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3948.84 | 2540.42 | 1408.42 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3553.90 | 2284.05 | 1269.85 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2847.97 | 1868.44 | 979.53 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2134.20 | 1393.11 | 741.09 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2112.21 | 1379.40 | 732.81 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2599.54 | 1668.30 | 931.24 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2611.99 | 1676.11 | 935.88 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4116.59 | 2648.57 | 1468.03 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3895.27 | 2509.63 | 1385.64 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3503.35 | 2254.97 | 1248.38 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2789.52 | 1834.40 | 955.12 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2086.16 | 1364.78 | 721.38 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2064.26 | 1351.12 | 713.15 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2552.10 | 1640.06 | 912.03 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2564.46 | 1647.82 | 916.64 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4098.70 | 2639.78 | 1458.92 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3877.62 | 2500.99 | 1376.63 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3486.73 | 2246.87 | 1239.86 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2766.74 | 1822.45 | 944.30 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2072.01 | 1357.36 | 714.65 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2050.17 | 1343.73 | 706.44 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2537.60 | 1632.34 | 905.26 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2549.90 | 1640.06 | 909.84 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4100.51 | 2643.09 | 1457.41 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3879.85 | 2504.55 | 1375.29 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3488.27 | 2249.94 | 1238.33 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2762.89 | 1822.14 | 940.75 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2077.63 | 1362.12 | 715.51 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2055.87 | 1348.54 | 707.33 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2541.24 | 1635.87 | 905.37 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2553.52 | 1643.58 | 909.94 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4241.33 | 2733.36 | 1507.97 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4017.93 | 2593.03 | 1424.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3580.15 | 2309.60 | 1270.55 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2797.59 | 1845.92 | 951.66 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2200.14 | 1439.66 | 760.47 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2177.99 | 1425.84 | 752.15 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2621.46 | 1687.47 | 933.98 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2635.24 | 1696.12 | 939.12 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5319.86 | 3404.52 | 1915.35 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4949.54 | 3177.19 | 1772.35 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4646.23 | 2980.52 | 1665.72 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3614.97 | 2354.71 | 1260.26 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2946.98 | 1891.87 | 1055.11 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2941.37 | 1888.32 | 1053.06 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3828.40 | 2446.20 | 1382.20 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3839.15 | 2452.93 | 1386.22 | 0.64 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3140.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2982.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4135.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2027.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1470.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1444.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1851.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1922.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4095.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3864.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3729.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2775.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2024.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2002.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2485.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2514.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4115.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3893.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3524.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2810.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2072.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2050.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2536.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2551.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4126.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3905.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3514.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2813.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2089.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2067.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2554.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2567.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4168.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3948.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3553.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2847.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2134.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2112.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2599.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2611.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4116.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3895.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3503.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2789.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2086.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2064.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2552.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2564.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4098.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3877.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3486.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2766.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2072.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2050.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2537.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2549.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4100.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3879.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3488.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2762.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2077.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2055.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2541.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2553.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4241.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4017.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3580.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2797.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2200.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2177.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2621.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2635.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5319.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4949.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4646.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3614.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2946.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2941.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3828.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3839.15 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 3345.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 3358.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 4259.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 3358.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2544.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2544.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2529.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2537.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 3258.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 3264.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 3283.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 3264.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 2279.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 2279.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 2276.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 2277.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 3233.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 3239.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 3236.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 3239.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 2226.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 2226.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 2221.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 2221.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 3266.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 3271.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 3266.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 3271.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 2234.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 2234.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 2230.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 2230.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 3277.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 3279.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 3277.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 3279.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 2226.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 2226.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 2224.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 2224.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 3358.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 3360.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 3358.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 3360.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 2287.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 2287.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 2286.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 2286.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 3409.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 3410.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 3409.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 3410.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 2323.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 2323.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 2323.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 2323.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 3468.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 3467.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 3468.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 3467.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2368.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2368.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2369.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2369.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 3681.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 3676.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 3681.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 3676.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2556.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2556.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2561.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2561.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 4489.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 4491.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 4489.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 4491.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 3428.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 3428.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 3423.89 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 3423.89 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.94 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.00 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 378.27 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.24 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 140.13 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 137.73 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.37 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 172.35 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 381.23 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.50 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 342.83 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 265.65 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 191.79 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 189.77 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 224.98 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 227.71 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 383.89 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.21 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.80 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.94 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.79 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.77 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.34 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.73 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.73 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 366.13 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.62 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 270.97 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.81 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.79 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.44 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 233.63 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 390.27 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 370.79 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.93 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 274.82 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.31 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.29 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 236.97 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 238.12 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.98 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 366.38 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.78 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.92 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.22 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.20 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.89 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 234.03 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 384.81 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.23 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 323.70 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 268.27 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.20 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.19 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.82 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.96 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.41 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.87 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.26 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 268.33 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.96 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.96 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.40 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 233.54 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 398.86 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 379.05 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 333.18 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 271.95 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.46 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.42 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 240.08 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.35 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 495.52 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 463.59 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 432.40 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.56 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 270.01 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.48 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 352.12 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 353.11 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0053 | 1339.76 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2243.73 | 2692.47 | 0.216 | 0.260 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
G NW APARTMENT | 2143.94 | 2572.73 | 0.207 | 0.248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
OFFICE | 2917.26 | 3500.72 | 0.281 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 33.34 | 0.00543 |
G NE APARTMENT | 1505.66 | 1806.80 | 0.145 | 0.174 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.28 | 0.00543 |
G N1 APARTMENT | 1080.62 | 1296.75 | 0.104 | 0.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
G N2 APARTMENT | 1062.18 | 1274.62 | 0.102 | 0.123 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
G S1 APARTMENT | 1275.30 | 1530.36 | 0.123 | 0.148 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
G S2 APARTMENT | 1329.17 | 1595.00 | 0.128 | 0.154 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F2 SW APARTMENT | 2940.00 | 3528.00 | 0.284 | 0.340 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.09 | 0.00543 |
F2 NW APARTMENT | 2780.18 | 3336.21 | 0.268 | 0.322 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F2 SE APARTMENT | 2643.90 | 3172.68 | 0.255 | 0.306 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F2 NE APARTMENT | 2048.66 | 2458.39 | 0.198 | 0.237 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F2 N1 APARTMENT | 1479.05 | 1774.86 | 0.143 | 0.171 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F2 N2 APARTMENT | 1463.47 | 1756.16 | 0.141 | 0.169 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F2 S1 APARTMENT | 1735.03 | 2082.04 | 0.167 | 0.201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F2 S2 APARTMENT | 1756.09 | 2107.31 | 0.169 | 0.203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F3 SW APARTMENT | 2960.54 | 3552.64 | 0.286 | 0.343 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F3 NW APARTMENT | 2808.80 | 3370.56 | 0.271 | 0.325 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F3 SE APARTMENT | 2504.86 | 3005.84 | 0.242 | 0.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F3 NE APARTMENT | 2081.75 | 2498.10 | 0.201 | 0.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F3 N1 APARTMENT | 1517.61 | 1821.13 | 0.146 | 0.176 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F3 N2 APARTMENT | 1502.07 | 1802.49 | 0.145 | 0.174 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F3 S1 APARTMENT | 1776.40 | 2131.68 | 0.171 | 0.206 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F3 S2 APARTMENT | 1787.07 | 2144.48 | 0.172 | 0.207 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F4 SW APARTMENT | 2974.81 | 3569.77 | 0.287 | 0.344 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F4 NW APARTMENT | 2823.62 | 3388.34 | 0.272 | 0.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F4 SE APARTMENT | 2503.50 | 3004.20 | 0.242 | 0.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F4 NE APARTMENT | 2089.74 | 2507.68 | 0.202 | 0.242 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F4 N1 APARTMENT | 1533.20 | 1839.84 | 0.148 | 0.177 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F4 N2 APARTMENT | 1517.63 | 1821.15 | 0.146 | 0.176 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F4 S1 APARTMENT | 1792.56 | 2151.08 | 0.173 | 0.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F4 S2 APARTMENT | 1801.71 | 2162.05 | 0.174 | 0.209 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
M SW APARTMENT | 3009.77 | 3611.72 | 0.290 | 0.348 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
M NW APARTMENT | 2859.54 | 3431.44 | 0.276 | 0.331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
M SE APARTMENT | 2536.75 | 3044.11 | 0.245 | 0.294 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
M NE APARTMENT | 2119.41 | 2543.29 | 0.204 | 0.245 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
M N1 APARTMENT | 1567.94 | 1881.53 | 0.151 | 0.182 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
M N2 APARTMENT | 1552.34 | 1862.81 | 0.150 | 0.180 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
M S1 APARTMENT | 1827.49 | 2192.99 | 0.176 | 0.212 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
M S2 APARTMENT | 1836.37 | 2203.65 | 0.177 | 0.213 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F6 SW APARTMENT | 2976.73 | 3572.08 | 0.287 | 0.345 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F6 NW APARTMENT | 2825.57 | 3390.68 | 0.273 | 0.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F6 SE APARTMENT | 2504.71 | 3005.65 | 0.242 | 0.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F6 NE APARTMENT | 2081.63 | 2497.96 | 0.201 | 0.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F6 N1 APARTMENT | 1536.36 | 1843.63 | 0.148 | 0.178 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F6 N2 APARTMENT | 1520.82 | 1824.99 | 0.147 | 0.176 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F6 S1 APARTMENT | 1796.02 | 2155.23 | 0.173 | 0.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F6 S2 APARTMENT | 1804.84 | 2165.81 | 0.174 | 0.209 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F7 SW APARTMENT | 2967.70 | 3561.24 | 0.286 | 0.344 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F7 NW APARTMENT | 2816.70 | 3380.04 | 0.272 | 0.326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F7 SE APARTMENT | 2496.43 | 2995.71 | 0.241 | 0.289 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F7 NE APARTMENT | 2068.92 | 2482.71 | 0.200 | 0.240 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F7 N1 APARTMENT | 1528.49 | 1834.19 | 0.147 | 0.177 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F7 N2 APARTMENT | 1512.98 | 1815.58 | 0.146 | 0.175 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F7 S1 APARTMENT | 1787.80 | 2145.36 | 0.172 | 0.207 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F7 S2 APARTMENT | 1796.57 | 2155.89 | 0.173 | 0.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F8 SW APARTMENT | 2972.36 | 3566.83 | 0.287 | 0.344 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F8 NW APARTMENT | 2821.64 | 3385.97 | 0.272 | 0.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F8 SE APARTMENT | 2500.77 | 3000.92 | 0.241 | 0.289 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F8 NE APARTMENT | 2069.41 | 2483.29 | 0.200 | 0.240 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F8 N1 APARTMENT | 1534.40 | 1841.28 | 0.148 | 0.178 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F8 N2 APARTMENT | 1518.95 | 1822.74 | 0.147 | 0.176 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F8 S1 APARTMENT | 1792.31 | 2150.77 | 0.173 | 0.207 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F8 S2 APARTMENT | 1801.08 | 2161.29 | 0.174 | 0.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F9 SW APARTMENT | 3076.05 | 3691.26 | 0.297 | 0.356 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.46 | 0.00543 |
F9 NW APARTMENT | 2923.26 | 3507.91 | 0.282 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.72 | 0.00543 |
F9 SE APARTMENT | 2569.52 | 3083.43 | 0.248 | 0.297 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
F9 NE APARTMENT | 2097.33 | 2516.80 | 0.202 | 0.243 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 28.83 | 0.00543 |
F9 N1 APARTMENT | 1623.07 | 1947.69 | 0.157 | 0.188 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F9 N2 APARTMENT | 1607.34 | 1928.81 | 0.155 | 0.186 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 28.68 | 0.00543 |
F9 S1 APARTMENT | 1851.48 | 2221.78 | 0.179 | 0.214 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
F9 S2 APARTMENT | 1861.32 | 2233.59 | 0.180 | 0.215 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
T SW APARTMENT | 3821.53 | 4585.83 | 0.369 | 0.442 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 33.23 | 0.00543 |
T NW APARTMENT | 3575.33 | 4290.39 | 0.345 | 0.414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.12 | 0.00543 |
T SE APARTMENT | 3334.77 | 4001.73 | 0.322 | 0.386 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
T NE APARTMENT | 2665.03 | 3198.04 | 0.257 | 0.309 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 29.94 | 0.00543 |
T N1 APARTMENT | 2082.30 | 2498.76 | 0.201 | 0.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.90 | 0.00543 |
T N2 APARTMENT | 2078.25 | 2493.90 | 0.200 | 0.241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.90 | 0.00543 |
T S1 APARTMENT | 2715.58 | 3258.70 | 0.262 | 0.314 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
T S2 APARTMENT | 2723.24 | 3267.89 | 0.263 | 0.315 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 33.71 | 0.00543 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1975.48 | 2370.58 | 0.108 | 0.130 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G NW APARTMENT | 1986.15 | 2383.38 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
OFFICE | 2348.90 | 2818.68 | 0.129 | 0.155 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -17.90 | 0.00096 |
G NE APARTMENT | 1986.15 | 2383.38 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G N1 APARTMENT | 1298.57 | 1558.29 | 0.071 | 0.085 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G N2 APARTMENT | 1298.57 | 1558.29 | 0.071 | 0.085 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G S1 APARTMENT | 1285.28 | 1542.33 | 0.070 | 0.085 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
G S2 APARTMENT | 1292.46 | 1550.95 | 0.071 | 0.085 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90 | 0.00096 |
F2 SW APARTMENT | 1901.76 | 2282.12 | 0.104 | 0.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 NW APARTMENT | 1907.12 | 2288.54 | 0.105 | 0.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 SE APARTMENT | 1922.81 | 2307.38 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 NE APARTMENT | 1907.12 | 2288.54 | 0.105 | 0.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 N1 APARTMENT | 1074.35 | 1289.23 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 N2 APARTMENT | 1074.35 | 1289.23 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 S1 APARTMENT | 1071.40 | 1285.68 | 0.059 | 0.070 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F2 S2 APARTMENT | 1072.74 | 1287.28 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 SW APARTMENT | 1880.81 | 2256.97 | 0.103 | 0.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 NW APARTMENT | 1886.06 | 2263.27 | 0.103 | 0.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 SE APARTMENT | 1883.03 | 2259.63 | 0.103 | 0.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 NE APARTMENT | 1886.06 | 2263.27 | 0.103 | 0.124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 N1 APARTMENT | 1029.59 | 1235.51 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 N2 APARTMENT | 1029.59 | 1235.51 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 S1 APARTMENT | 1025.03 | 1230.03 | 0.056 | 0.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F3 S2 APARTMENT | 1025.23 | 1230.27 | 0.056 | 0.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 SW APARTMENT | 1908.65 | 2290.38 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 NW APARTMENT | 1913.07 | 2295.68 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 SE APARTMENT | 1908.87 | 2290.65 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 NE APARTMENT | 1913.07 | 2295.68 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 N1 APARTMENT | 1036.39 | 1243.67 | 0.057 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 N2 APARTMENT | 1036.39 | 1243.67 | 0.057 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 S1 APARTMENT | 1032.47 | 1238.97 | 0.057 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F4 S2 APARTMENT | 1032.50 | 1239.00 | 0.057 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M SW APARTMENT | 1917.73 | 2301.27 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M NW APARTMENT | 1920.10 | 2304.13 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M SE APARTMENT | 1917.75 | 2301.30 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M NE APARTMENT | 1920.10 | 2304.13 | 0.105 | 0.126 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M N1 APARTMENT | 1029.27 | 1235.13 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M N2 APARTMENT | 1029.27 | 1235.13 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M S1 APARTMENT | 1027.41 | 1232.89 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
M S2 APARTMENT | 1027.41 | 1232.89 | 0.056 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 SW APARTMENT | 1986.21 | 2383.46 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 NW APARTMENT | 1988.28 | 2385.93 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 SE APARTMENT | 1986.21 | 2383.46 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 NE APARTMENT | 1988.28 | 2385.93 | 0.109 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 N1 APARTMENT | 1081.19 | 1297.42 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 N2 APARTMENT | 1081.19 | 1297.42 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 S1 APARTMENT | 1079.58 | 1295.49 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F6 S2 APARTMENT | 1079.58 | 1295.49 | 0.059 | 0.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 SW APARTMENT | 2029.79 | 2435.74 | 0.111 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 NW APARTMENT | 2030.60 | 2436.72 | 0.111 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 SE APARTMENT | 2029.79 | 2435.74 | 0.111 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 NE APARTMENT | 2030.60 | 2436.72 | 0.111 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 N1 APARTMENT | 1111.57 | 1333.88 | 0.061 | 0.073 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 N2 APARTMENT | 1111.57 | 1333.88 | 0.061 | 0.073 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 S1 APARTMENT | 1111.17 | 1333.41 | 0.061 | 0.073 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F7 S2 APARTMENT | 1111.17 | 1333.41 | 0.061 | 0.073 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 SW APARTMENT | 2079.33 | 2495.19 | 0.114 | 0.137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 NW APARTMENT | 2078.78 | 2494.54 | 0.114 | 0.137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 SE APARTMENT | 2079.33 | 2495.19 | 0.114 | 0.137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 NE APARTMENT | 2078.78 | 2494.54 | 0.114 | 0.137 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 N1 APARTMENT | 1149.34 | 1379.21 | 0.063 | 0.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 N2 APARTMENT | 1149.34 | 1379.21 | 0.063 | 0.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 S1 APARTMENT | 1150.34 | 1380.40 | 0.063 | 0.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F8 S2 APARTMENT | 1150.34 | 1380.40 | 0.063 | 0.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 SW APARTMENT | 2259.69 | 2711.63 | 0.124 | 0.149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 NW APARTMENT | 2255.27 | 2706.32 | 0.124 | 0.148 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 SE APARTMENT | 2259.69 | 2711.63 | 0.124 | 0.149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 NE APARTMENT | 2255.27 | 2706.32 | 0.124 | 0.148 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 N1 APARTMENT | 1307.92 | 1569.51 | 0.072 | 0.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 N2 APARTMENT | 1307.92 | 1569.51 | 0.072 | 0.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 S1 APARTMENT | 1312.44 | 1574.92 | 0.072 | 0.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
F9 S2 APARTMENT | 1312.44 | 1574.92 | 0.072 | 0.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T SW APARTMENT | 2942.86 | 3531.43 | 0.161 | 0.194 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T NW APARTMENT | 2944.86 | 3533.84 | 0.161 | 0.194 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T SE APARTMENT | 2942.86 | 3531.43 | 0.161 | 0.194 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T NE APARTMENT | 2944.86 | 3533.84 | 0.161 | 0.194 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T N1 APARTMENT | 2046.14 | 2455.37 | 0.112 | 0.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T N2 APARTMENT | 2046.14 | 2455.37 | 0.112 | 0.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T S1 APARTMENT | 2041.84 | 2450.21 | 0.112 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
T S2 APARTMENT | 2041.84 | 2450.21 | 0.112 | 0.134 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -17.90 | 0.00096 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.26 | 0.26 | 0.13 | 0.13 |
AIRLOOP G NW | 0.25 | 0.25 | 0.13 | 0.13 |
AIRLOOP OFFICE | 0.34 | 0.34 | 0.15 | 0.15 |
AIRLOOP G NE | 0.17 | 0.17 | 0.13 | 0.13 |
AIRLOOP G N1 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP G N2 | 0.12 | 0.12 | 0.09 | 0.09 |
AIRLOOP G S1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP G S2 | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F2 SW | 0.34 | 0.34 | 0.13 | 0.13 |
AIRLOOP F2 NW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F2 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F2 NE | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F2 N1 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F2 N2 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F2 S1 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F2 S2 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F3 SW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP F3 NW | 0.33 | 0.33 | 0.12 | 0.12 |
AIRLOOP F3 SE | 0.29 | 0.29 | 0.12 | 0.12 |
AIRLOOP F3 NE | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F3 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F3 N2 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F3 S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F3 S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F4 SW | 0.34 | 0.34 | 0.13 | 0.13 |
AIRLOOP F4 NW | 0.33 | 0.33 | 0.13 | 0.13 |
AIRLOOP F4 SE | 0.29 | 0.29 | 0.13 | 0.13 |
AIRLOOP F4 NE | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F4 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F4 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F4 S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F4 S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP M SW | 0.35 | 0.35 | 0.13 | 0.13 |
AIRLOOP M NW | 0.33 | 0.33 | 0.13 | 0.13 |
AIRLOOP M SE | 0.29 | 0.29 | 0.13 | 0.13 |
AIRLOOP M NE | 0.25 | 0.25 | 0.13 | 0.13 |
AIRLOOP M N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP M N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP M S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP M S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F6 SW | 0.34 | 0.34 | 0.13 | 0.13 |
AIRLOOP F6 NW | 0.33 | 0.33 | 0.13 | 0.13 |
AIRLOOP F6 SE | 0.29 | 0.29 | 0.13 | 0.13 |
AIRLOOP F6 NE | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F6 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F6 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F6 S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F6 S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F7 SW | 0.34 | 0.34 | 0.13 | 0.13 |
AIRLOOP F7 NW | 0.33 | 0.33 | 0.13 | 0.13 |
AIRLOOP F7 SE | 0.29 | 0.29 | 0.13 | 0.13 |
AIRLOOP F7 NE | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F7 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F7 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F7 S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F7 S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F8 SW | 0.34 | 0.34 | 0.14 | 0.14 |
AIRLOOP F8 NW | 0.33 | 0.33 | 0.14 | 0.14 |
AIRLOOP F8 SE | 0.29 | 0.29 | 0.14 | 0.14 |
AIRLOOP F8 NE | 0.24 | 0.24 | 0.14 | 0.14 |
AIRLOOP F8 N1 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F8 N2 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F8 S1 | 0.21 | 0.21 | 0.08 | 0.08 |
AIRLOOP F8 S2 | 0.21 | 0.21 | 0.08 | 0.08 |
AIRLOOP F9 SW | 0.36 | 0.36 | 0.15 | 0.15 |
AIRLOOP F9 NW | 0.34 | 0.34 | 0.15 | 0.15 |
AIRLOOP F9 SE | 0.30 | 0.30 | 0.15 | 0.15 |
AIRLOOP F9 NE | 0.24 | 0.24 | 0.15 | 0.15 |
AIRLOOP F9 N1 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F9 N2 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F9 S1 | 0.21 | 0.21 | 0.09 | 0.09 |
AIRLOOP F9 S2 | 0.22 | 0.22 | 0.09 | 0.09 |
AIRLOOP T SW | 0.44 | 0.44 | 0.19 | 0.19 |
AIRLOOP T NW | 0.41 | 0.41 | 0.19 | 0.19 |
AIRLOOP T SE | 0.39 | 0.39 | 0.19 | 0.19 |
AIRLOOP T NE | 0.31 | 0.31 | 0.19 | 0.19 |
AIRLOOP T N1 | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP T N2 | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP T S1 | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP T S2 | 0.32 | 0.32 | 0.13 | 0.13 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2499.75 | 5246.25 | 518.50 |
G NW APARTMENT | 2290.50 | 6263.50 | 745.75 |
OFFICE | 896.75 | 745.75 | 59.75 |
G NE APARTMENT | 2426.75 | 6279.00 | 794.00 |
G N1 APARTMENT | 1836.75 | 6536.75 | 570.50 |
G N2 APARTMENT | 1844.75 | 6530.25 | 570.75 |
G S1 APARTMENT | 2193.25 | 5447.75 | 421.25 |
G S2 APARTMENT | 2222.00 | 5390.75 | 411.25 |
F2 SW APARTMENT | 3317.25 | 3631.75 | 270.25 |
F2 NW APARTMENT | 2614.00 | 5419.50 | 419.50 |
F2 SE APARTMENT | 3521.25 | 3516.50 | 245.50 |
F2 NE APARTMENT | 2721.25 | 5457.00 | 449.50 |
F2 N1 APARTMENT | 2216.75 | 5698.75 | 301.75 |
F2 N2 APARTMENT | 2221.00 | 5705.00 | 303.00 |
F2 S1 APARTMENT | 3290.25 | 3415.75 | 212.75 |
F2 S2 APARTMENT | 3307.50 | 3384.75 | 209.25 |
F3 SW APARTMENT | 3506.25 | 3380.25 | 254.75 |
F3 NW APARTMENT | 2679.00 | 5214.50 | 390.25 |
F3 SE APARTMENT | 3629.50 | 3404.75 | 252.50 |
F3 NE APARTMENT | 2781.25 | 5263.25 | 412.25 |
F3 N1 APARTMENT | 2331.50 | 5442.00 | 262.50 |
F3 N2 APARTMENT | 2337.75 | 5447.50 | 263.50 |
F3 S1 APARTMENT | 3622.25 | 2990.75 | 193.00 |
F3 S2 APARTMENT | 3625.75 | 2989.75 | 192.75 |
F4 SW APARTMENT | 3513.50 | 3373.00 | 258.50 |
F4 NW APARTMENT | 2679.00 | 5180.00 | 394.00 |
F4 SE APARTMENT | 3614.75 | 3429.00 | 258.25 |
F4 NE APARTMENT | 2784.00 | 5248.50 | 415.75 |
F4 N1 APARTMENT | 2344.25 | 5383.50 | 258.25 |
F4 N2 APARTMENT | 2353.50 | 5387.75 | 258.75 |
F4 S1 APARTMENT | 3656.25 | 2941.00 | 194.00 |
F4 S2 APARTMENT | 3657.50 | 2943.25 | 192.75 |
M SW APARTMENT | 3521.75 | 3365.25 | 254.25 |
M NW APARTMENT | 2686.25 | 5158.00 | 387.25 |
M SE APARTMENT | 3622.75 | 3423.00 | 255.75 |
M NE APARTMENT | 2789.50 | 5236.00 | 408.25 |
M N1 APARTMENT | 2367.75 | 5331.50 | 246.75 |
M N2 APARTMENT | 2374.75 | 5341.00 | 246.75 |
M S1 APARTMENT | 3685.75 | 2912.25 | 187.75 |
M S2 APARTMENT | 3689.00 | 2914.25 | 187.00 |
F6 SW APARTMENT | 3383.00 | 3533.75 | 274.00 |
F6 NW APARTMENT | 2629.50 | 5281.00 | 423.00 |
F6 SE APARTMENT | 3484.50 | 3578.25 | 278.00 |
F6 NE APARTMENT | 2748.00 | 5325.50 | 447.00 |
F6 N1 APARTMENT | 2279.75 | 5466.00 | 271.50 |
F6 N2 APARTMENT | 2287.25 | 5468.50 | 271.00 |
F6 S1 APARTMENT | 3503.00 | 3079.50 | 202.00 |
F6 S2 APARTMENT | 3500.75 | 3081.00 | 200.75 |
F7 SW APARTMENT | 3294.50 | 3644.50 | 287.75 |
F7 NW APARTMENT | 2600.00 | 5366.25 | 445.25 |
F7 SE APARTMENT | 3394.00 | 3682.50 | 292.00 |
F7 NE APARTMENT | 2731.50 | 5391.50 | 470.75 |
F7 N1 APARTMENT | 2233.00 | 5544.75 | 284.50 |
F7 N2 APARTMENT | 2236.25 | 5549.50 | 284.50 |
F7 S1 APARTMENT | 3392.50 | 3195.00 | 210.50 |
F7 S2 APARTMENT | 3396.25 | 3193.75 | 210.00 |
F8 SW APARTMENT | 3235.00 | 3751.75 | 304.00 |
F8 NW APARTMENT | 2594.50 | 5422.75 | 467.00 |
F8 SE APARTMENT | 3323.25 | 3762.75 | 307.50 |
F8 NE APARTMENT | 2721.50 | 5445.25 | 494.00 |
F8 N1 APARTMENT | 2212.50 | 5604.50 | 298.25 |
F8 N2 APARTMENT | 2221.25 | 5608.75 | 298.50 |
F8 S1 APARTMENT | 3298.00 | 3320.75 | 215.50 |
F8 S2 APARTMENT | 3299.75 | 3317.75 | 215.25 |
F9 SW APARTMENT | 3154.25 | 3916.50 | 347.75 |
F9 NW APARTMENT | 2636.00 | 5485.25 | 525.00 |
F9 SE APARTMENT | 3237.75 | 3928.25 | 356.00 |
F9 NE APARTMENT | 2766.50 | 5510.00 | 564.75 |
F9 N1 APARTMENT | 2234.50 | 5663.00 | 328.25 |
F9 N2 APARTMENT | 2240.25 | 5665.75 | 328.50 |
F9 S1 APARTMENT | 3131.75 | 3574.00 | 221.50 |
F9 S2 APARTMENT | 3139.00 | 3574.75 | 221.25 |
T SW APARTMENT | 3747.50 | 4582.50 | 902.50 |
T NW APARTMENT | 3247.25 | 5655.00 | 1253.00 |
T SE APARTMENT | 3857.50 | 4529.50 | 919.00 |
T NE APARTMENT | 3322.50 | 5704.25 | 1263.00 |
T N1 APARTMENT | 2643.75 | 5871.50 | 791.25 |
T N2 APARTMENT | 2648.50 | 5865.00 | 793.00 |
T S1 APARTMENT | 3356.50 | 4336.25 | 533.25 |
T S2 APARTMENT | 3365.25 | 4333.75 | 532.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5427.75 | 6682.00 | 1493.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.25 | 57.25 | 4.25 | 57.25 |
G NW APARTMENT | 2.25 | 21.50 | 2.25 | 21.50 |
OFFICE | 4.50 | 63.75 | 0.25 | 63.25 |
G NE APARTMENT | 5.75 | 92.00 | 5.75 | 92.00 |
G N1 APARTMENT | 6.25 | 68.00 | 6.25 | 68.00 |
G N2 APARTMENT | 4.25 | 75.00 | 4.25 | 75.00 |
G S1 APARTMENT | 1.75 | 137.25 | 1.75 | 137.25 |
G S2 APARTMENT | 2.00 | 121.00 | 2.00 | 121.00 |
F2 SW APARTMENT | 1.00 | 55.50 | 1.00 | 55.50 |
F2 NW APARTMENT | 0.50 | 19.00 | 0.50 | 19.00 |
F2 SE APARTMENT | 1.25 | 51.50 | 1.25 | 51.50 |
F2 NE APARTMENT | 2.75 | 92.00 | 2.75 | 92.00 |
F2 N1 APARTMENT | 3.50 | 57.00 | 3.50 | 57.00 |
F2 N2 APARTMENT | 3.75 | 64.50 | 3.75 | 64.50 |
F2 S1 APARTMENT | 1.00 | 169.75 | 1.00 | 169.75 |
F2 S2 APARTMENT | 0.75 | 162.00 | 0.75 | 162.00 |
F3 SW APARTMENT | 1.00 | 67.00 | 1.00 | 67.00 |
F3 NW APARTMENT | 0.25 | 22.25 | 0.25 | 22.25 |
F3 SE APARTMENT | 1.00 | 95.25 | 1.00 | 95.25 |
F3 NE APARTMENT | 3.00 | 111.25 | 3.00 | 111.25 |
F3 N1 APARTMENT | 4.00 | 70.50 | 4.00 | 70.50 |
F3 N2 APARTMENT | 4.50 | 76.75 | 4.50 | 76.75 |
F3 S1 APARTMENT | 1.75 | 189.75 | 1.75 | 189.75 |
F3 S2 APARTMENT | 1.25 | 185.00 | 1.25 | 185.00 |
F4 SW APARTMENT | 1.00 | 70.50 | 1.00 | 70.50 |
F4 NW APARTMENT | 0.25 | 24.50 | 0.25 | 24.50 |
F4 SE APARTMENT | 0.50 | 110.00 | 0.50 | 110.00 |
F4 NE APARTMENT | 3.00 | 121.00 | 3.00 | 121.00 |
F4 N1 APARTMENT | 3.75 | 76.00 | 3.75 | 76.00 |
F4 N2 APARTMENT | 3.50 | 82.25 | 3.50 | 82.25 |
F4 S1 APARTMENT | 0.75 | 195.75 | 0.75 | 195.75 |
F4 S2 APARTMENT | 1.00 | 192.00 | 1.00 | 192.00 |
M SW APARTMENT | 0.50 | 71.75 | 0.50 | 71.75 |
M NW APARTMENT | 0.00 | 25.50 | 0.00 | 25.50 |
M SE APARTMENT | 0.50 | 112.00 | 0.50 | 112.00 |
M NE APARTMENT | 1.50 | 127.25 | 1.50 | 127.25 |
M N1 APARTMENT | 2.50 | 78.25 | 2.50 | 78.25 |
M N2 APARTMENT | 3.00 | 86.25 | 3.00 | 86.25 |
M S1 APARTMENT | 2.00 | 193.25 | 2.00 | 193.25 |
M S2 APARTMENT | 1.50 | 191.75 | 1.50 | 191.75 |
F6 SW APARTMENT | 1.00 | 71.75 | 1.00 | 71.75 |
F6 NW APARTMENT | 0.50 | 27.50 | 0.50 | 27.50 |
F6 SE APARTMENT | 1.25 | 112.00 | 1.25 | 112.00 |
F6 NE APARTMENT | 3.00 | 141.75 | 3.00 | 141.75 |
F6 N1 APARTMENT | 2.25 | 83.75 | 2.25 | 83.75 |
F6 N2 APARTMENT | 3.50 | 92.50 | 3.50 | 92.50 |
F6 S1 APARTMENT | 1.00 | 193.75 | 1.00 | 193.75 |
F6 S2 APARTMENT | 2.00 | 191.00 | 2.00 | 191.00 |
F7 SW APARTMENT | 0.00 | 72.75 | 0.00 | 72.75 |
F7 NW APARTMENT | 0.25 | 28.00 | 0.25 | 28.00 |
F7 SE APARTMENT | 0.25 | 112.75 | 0.25 | 112.75 |
F7 NE APARTMENT | 1.50 | 149.25 | 1.50 | 149.25 |
F7 N1 APARTMENT | 5.25 | 86.75 | 5.25 | 86.75 |
F7 N2 APARTMENT | 3.75 | 97.75 | 3.75 | 97.75 |
F7 S1 APARTMENT | 1.25 | 193.25 | 1.25 | 193.25 |
F7 S2 APARTMENT | 1.25 | 190.25 | 1.25 | 190.25 |
F8 SW APARTMENT | 0.25 | 69.25 | 0.25 | 69.25 |
F8 NW APARTMENT | 0.00 | 28.50 | 0.00 | 28.50 |
F8 SE APARTMENT | 1.25 | 112.25 | 1.25 | 112.25 |
F8 NE APARTMENT | 2.50 | 157.50 | 2.50 | 157.50 |
F8 N1 APARTMENT | 3.50 | 87.50 | 3.50 | 87.50 |
F8 N2 APARTMENT | 4.50 | 98.00 | 4.50 | 98.00 |
F8 S1 APARTMENT | 1.25 | 190.75 | 1.25 | 190.75 |
F8 S2 APARTMENT | 0.75 | 183.25 | 0.75 | 183.25 |
F9 SW APARTMENT | 0.00 | 61.75 | 0.00 | 61.75 |
F9 NW APARTMENT | 0.00 | 27.50 | 0.00 | 27.50 |
F9 SE APARTMENT | 1.25 | 99.50 | 1.25 | 99.50 |
F9 NE APARTMENT | 2.75 | 175.25 | 2.75 | 175.25 |
F9 N1 APARTMENT | 6.00 | 75.50 | 6.00 | 75.50 |
F9 N2 APARTMENT | 5.25 | 82.75 | 5.25 | 82.75 |
F9 S1 APARTMENT | 1.25 | 169.75 | 1.25 | 169.75 |
F9 S2 APARTMENT | 1.50 | 166.75 | 1.50 | 166.75 |
T SW APARTMENT | 0.00 | 49.50 | 0.00 | 49.50 |
T NW APARTMENT | 0.00 | 30.00 | 0.00 | 30.00 |
T SE APARTMENT | 0.00 | 63.75 | 0.00 | 63.75 |
T NE APARTMENT | 0.00 | 121.25 | 0.00 | 121.25 |
T N1 APARTMENT | 1.50 | 54.50 | 1.50 | 54.50 |
T N2 APARTMENT | 1.75 | 58.25 | 1.75 | 58.25 |
T S1 APARTMENT | 1.25 | 85.25 | 1.25 | 85.25 |
T S2 APARTMENT | 1.00 | 85.50 | 1.00 | 85.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 128.75 | 390.25 | 124.75 | 390.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.098 | 0.000 | 0.289 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.098 | 0.000 | 0.277 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.516 | 0.100 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.098 | 0.000 | 0.277 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.059 | 0.000 | 0.270 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.059 | 0.000 | 0.270 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.059 | 0.000 | 0.286 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.059 | 0.000 | 0.287 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.141 | 0.000 | 0.334 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.141 | 0.000 | 0.322 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.142 | 0.000 | 0.335 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.141 | 0.000 | 0.321 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.085 | 0.000 | 0.317 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.085 | 0.000 | 0.317 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.085 | 0.000 | 0.332 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.085 | 0.000 | 0.333 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.168 | 0.000 | 0.361 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.167 | 0.000 | 0.348 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.168 | 0.000 | 0.361 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.167 | 0.000 | 0.347 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.101 | 0.000 | 0.344 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.101 | 0.000 | 0.344 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.101 | 0.000 | 0.360 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.101 | 0.000 | 0.360 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.187 | 0.000 | 0.382 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.187 | 0.000 | 0.368 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.187 | 0.000 | 0.383 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.187 | 0.000 | 0.368 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.113 | 0.000 | 0.364 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.113 | 0.000 | 0.364 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.113 | 0.000 | 0.381 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.113 | 0.000 | 0.381 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.203 | 0.000 | 0.400 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.203 | 0.000 | 0.385 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.203 | 0.000 | 0.401 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.203 | 0.000 | 0.385 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.122 | 0.000 | 0.382 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.122 | 0.000 | 0.382 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.123 | 0.000 | 0.399 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.123 | 0.000 | 0.399 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.418 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.402 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.419 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.401 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.131 | 0.000 | 0.398 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.398 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.131 | 0.000 | 0.417 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.417 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.230 | 0.000 | 0.432 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.229 | 0.000 | 0.415 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.230 | 0.000 | 0.433 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.229 | 0.000 | 0.414 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.138 | 0.000 | 0.411 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.138 | 0.000 | 0.411 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.139 | 0.000 | 0.431 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.139 | 0.000 | 0.431 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.241 | 0.000 | 0.446 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.240 | 0.000 | 0.427 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.241 | 0.000 | 0.446 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.240 | 0.000 | 0.427 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.145 | 0.000 | 0.423 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.145 | 0.000 | 0.423 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.145 | 0.000 | 0.444 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.145 | 0.000 | 0.444 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.251 | 0.000 | 0.458 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.250 | 0.000 | 0.438 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.251 | 0.000 | 0.458 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.250 | 0.000 | 0.438 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.435 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.151 | 0.000 | 0.435 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.456 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.151 | 0.000 | 0.456 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.260 | 0.000 | 0.469 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.260 | 0.000 | 0.450 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.260 | 0.000 | 0.469 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.260 | 0.000 | 0.450 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.157 | 0.000 | 0.447 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.157 | 0.000 | 0.447 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.157 | 0.000 | 0.467 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.157 | 0.000 | 0.467 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.505 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 708.77 | 22475.07 | 05-SEP-07:15 | 22475.07 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1258.67 | 22855.60 | 08-APR-02:15 | 85628.14 | 16-AUG-16:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
ElectricityNet:Plant | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 3031.50 | 60416.08 | 08-APR-02:15 | 170957.00 | 26-JUN-19:30 |
ExteriorLights:Electricity | 168.38 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.38 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 708.77 | 22475.07 | 05-SEP-07:15 | 22475.07 | 01-JAN-00:15 |
Cooling:Electricity | 405.35 | 0.00 | 01-JAN-00:15 | 62067.43 | 26-JUN-15:15 |
Heating:Electricity | 123.71 | 0.00 | 09-JAN-11:15 | 60951.91 | 22-DEC-04:00 |
Electricity:Plant | 56.95 | 36.93 | 23-MAR-12:30 | 3461.80 | 30-JUL-12:30 |
HeatRejection:Electricity | 13.98 | 0.00 | 01-JAN-00:15 | 2085.11 | 30-JUL-12:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 42.97 | 36.93 | 23-MAR-12:30 | 1376.68 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1594.36 | 9260.51 | 01-JAN-00:15 | 283059.73 | 19-MAR-07:15 |
Gas:Plant | 1594.36 | 9260.51 | 01-JAN-00:15 | 283059.73 | 19-MAR-07:15 |
WaterSystems:Gas | 1202.88 | 9260.51 | 01-JAN-00:15 | 89518.38 | 11-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1202.88 | 9260.51 | 01-JAN-00:15 | 89518.38 | 11-FEB-08:00 |
Heating:Gas | 391.48 | 0.00 | 01-JAN-00:15 | 205688.93 | 22-DEC-04:00 |
Boiler:Heating:Gas | 391.48 | 0.00 | 01-JAN-00:15 | 205688.93 | 22-DEC-04:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 1579.78 | 0.00 | 01-JAN-00:15 | 265403.41 | 26-JUN-15:00 |
PlantLoopCoolingDemand:HVAC | 1579.78 | 0.00 | 01-JAN-00:15 | 265403.41 | 26-JUN-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 1579.78 | 0.00 | 01-JAN-00:15 | 265403.41 | 26-JUN-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6127.75 | 0.00 | 01-JAN-02:30 | 0.00 | 26-JUN-17:15 |
Water:Plant | 6127.75 | 0.00 | 01-JAN-02:30 | 0.00 | 26-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6127.75 | 0.00 | 01-JAN-02:30 | 0.00 | 26-JUN-17:15 |
MainsWater:Plant | 6127.75 | 0.00 | 01-JAN-02:30 | 0.00 | 26-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1349.23 | 0.00 | 01-JAN-00:15 | 0.00 | 26-JUN-15:00 |
HeatRejection:MainsWater | 1349.23 | 0.00 | 01-JAN-00:15 | 0.00 | 26-JUN-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1273.87 | 498.76 | 15-AUG-01:15 | 218052.11 | 19-MAR-07:00 |
PlantLoopHeatingDemand:Plant | 914.60 | 498.76 | 15-AUG-01:15 | 61868.19 | 15-FEB-07:45 |
WaterSystems:PlantLoopHeatingDemand | 914.60 | 498.76 | 15-AUG-01:15 | 61868.19 | 15-FEB-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4364.65 | 6656.50 | 21-MAY-03:00 | 584638.26 | 19-MAR-07:15 |
EnergyTransfer:Building | 1465.59 | 4241.27 | 18-APR-08:00 | 175047.24 | 02-AUG-18:15 |
EnergyTransfer:Zone:G SW APARTMENT | 14.83 | 0.03 | 25-MAY-03:00 | 2422.23 | 02-SEP-17:30 |
Heating:EnergyTransfer | 292.13 | 0.00 | 21-JAN-16:45 | 158995.12 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.72 | 0.00 | 01-JAN-00:15 | 2141.02 | 21-DEC-08:00 |
Cooling:EnergyTransfer | 1173.46 | 0.00 | 04-JAN-23:00 | 175047.24 | 02-AUG-18:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 11.11 | 0.00 | 01-JAN-01:30 | 2422.23 | 02-SEP-17:30 |
EnergyTransfer:Zone:G NW APARTMENT | 13.35 | 0.02 | 13-OCT-18:45 | 2247.01 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.71 | 0.00 | 01-JAN-14:45 | 2145.38 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.64 | 0.00 | 01-JAN-00:15 | 2247.01 | 15-JUN-18:00 |
EnergyTransfer:Zone:OFFICE | 21.54 | 0.09 | 03-JUN-05:00 | 3113.70 | 29-AUG-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 3.73 | 0.00 | 01-JAN-08:15 | 2301.57 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 17.80 | 0.00 | 01-JAN-00:15 | 3113.70 | 29-AUG-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 13.59 | 0.09 | 21-JAN-15:00 | 2182.30 | 21-DEC-18:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.40 | 0.00 | 01-JAN-09:00 | 2182.30 | 21-DEC-18:30 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 7.19 | 0.00 | 01-JAN-00:15 | 1568.40 | 06-JUN-08:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.89 | 0.02 | 19-MAY-14:00 | 1332.11 | 23-DEC-08:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.25 | 0.00 | 01-JAN-17:15 | 1332.11 | 23-DEC-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 5.64 | 0.00 | 01-JAN-00:15 | 1129.63 | 08-JUN-18:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.90 | 0.00 | 24-SEP-10:15 | 1327.51 | 23-DEC-08:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.25 | 0.00 | 01-JAN-17:15 | 1327.51 | 23-DEC-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.65 | 0.00 | 01-JAN-00:15 | 1109.11 | 08-JUN-18:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 12.11 | 0.00 | 09-JUN-18:45 | 1457.38 | 05-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.25 | 0.00 | 01-JAN-00:15 | 1270.22 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 10.86 | 0.00 | 03-JAN-02:45 | 1457.38 | 05-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.26 | 0.00 | 06-NOV-10:45 | 1503.69 | 05-SEP-13:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.23 | 0.00 | 01-JAN-00:15 | 1265.38 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.03 | 0.00 | 03-JAN-03:15 | 1503.69 | 05-SEP-13:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 21.82 | 0.02 | 26-APR-09:00 | 3159.33 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 2.56 | 0.00 | 01-JAN-00:15 | 2135.09 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 19.26 | 0.00 | 03-JAN-04:30 | 3159.33 | 02-SEP-17:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 16.34 | 0.02 | 07-APR-04:15 | 2916.87 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 5.48 | 0.00 | 01-JAN-14:15 | 2323.73 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 10.86 | 0.00 | 01-JAN-00:15 | 2916.87 | 15-JUN-18:00 |
EnergyTransfer:Zone:F2 SE APARTMENT | 23.37 | 0.08 | 17-APR-17:45 | 2901.73 | 31-AUG-09:45 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 2.33 | 0.00 | 01-JAN-00:15 | 2103.00 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 21.04 | 0.00 | 03-JAN-05:00 | 2901.73 | 31-AUG-09:45 |
EnergyTransfer:Zone:F2 NE APARTMENT | 17.02 | 0.04 | 28-JAN-09:15 | 2353.95 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 5.24 | 0.00 | 01-JAN-08:30 | 2353.95 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 11.79 | 0.00 | 01-JAN-00:15 | 2156.73 | 06-JUN-08:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 11.43 | 0.04 | 01-MAR-14:30 | 1566.51 | 08-JUN-18:15 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 1.92 | 0.00 | 01-JAN-00:15 | 1318.34 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 9.51 | 0.00 | 01-JAN-00:30 | 1566.51 | 08-JUN-18:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 11.45 | 0.06 | 26-FEB-04:45 | 1549.33 | 08-JUN-18:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 1.92 | 0.00 | 01-JAN-09:00 | 1320.13 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 9.54 | 0.00 | 01-JAN-00:30 | 1549.33 | 08-JUN-18:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 19.36 | 0.04 | 07-DEC-07:15 | 2184.25 | 16-NOV-12:00 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.69 | 0.00 | 01-JAN-00:15 | 1154.68 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 18.66 | 0.00 | 04-JAN-22:15 | 2184.25 | 16-NOV-12:00 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 19.46 | 0.03 | 30-MAY-12:30 | 2206.26 | 16-NOV-12:00 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.69 | 0.00 | 01-JAN-00:15 | 1152.03 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 18.77 | 0.00 | 04-JAN-22:15 | 2206.26 | 16-NOV-12:00 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 23.05 | 0.11 | 23-MAR-20:15 | 3173.08 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 2.42 | 0.00 | 01-JAN-00:15 | 2179.50 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 20.63 | 0.00 | 03-JAN-05:45 | 3173.08 | 02-SEP-17:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 16.86 | 0.01 | 10-APR-13:45 | 2946.56 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 5.23 | 0.00 | 01-JAN-14:15 | 2371.53 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 11.64 | 0.00 | 01-JAN-00:15 | 2946.56 | 15-JUN-18:15 |
EnergyTransfer:Zone:F3 SE APARTMENT | 23.97 | 0.40 | 08-APR-01:15 | 2751.66 | 31-AUG-09:45 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 2.33 | 0.00 | 01-JAN-00:15 | 2174.06 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 21.64 | 0.00 | 03-JAN-05:45 | 2751.66 | 31-AUG-09:45 |
EnergyTransfer:Zone:F3 NE APARTMENT | 17.59 | 0.01 | 11-APR-13:00 | 2400.31 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 5.02 | 0.00 | 01-JAN-08:30 | 2400.31 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 12.57 | 0.00 | 01-JAN-00:15 | 2187.47 | 06-JUN-08:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 12.19 | 0.02 | 18-AUG-05:45 | 1603.05 | 08-JUN-18:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 1.69 | 0.00 | 01-JAN-00:15 | 1312.22 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 10.51 | 0.00 | 01-JAN-00:45 | 1603.05 | 08-JUN-18:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 12.22 | 0.12 | 13-DEC-13:00 | 1585.96 | 08-JUN-18:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 1.69 | 0.00 | 01-JAN-00:15 | 1314.01 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 10.53 | 0.00 | 01-JAN-00:45 | 1585.96 | 08-JUN-18:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 21.16 | 0.29 | 05-SEP-09:00 | 2284.13 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.60 | 0.00 | 01-JAN-00:15 | 1104.66 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 20.56 | 0.00 | 04-JAN-23:00 | 2284.13 | 18-NOV-13:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 21.20 | 0.09 | 03-APR-22:00 | 2291.99 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.60 | 0.00 | 01-JAN-00:15 | 1104.34 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 20.60 | 0.00 | 04-JAN-23:00 | 2291.99 | 18-NOV-13:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 23.18 | 0.02 | 26-APR-11:30 | 3180.48 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 2.54 | 0.00 | 01-JAN-00:15 | 2295.81 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 20.64 | 0.00 | 03-JAN-06:00 | 3180.48 | 02-SEP-17:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 17.11 | 0.03 | 25-APR-15:45 | 2946.35 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 5.40 | 0.00 | 01-JAN-14:15 | 2455.65 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 11.71 | 0.00 | 01-JAN-00:15 | 2946.35 | 15-JUN-18:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 24.00 | 0.11 | 21-MAY-02:30 | 2752.18 | 07-NOV-10:45 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 2.47 | 0.00 | 01-JAN-00:15 | 2295.05 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 21.52 | 0.00 | 03-JAN-06:00 | 2752.18 | 07-NOV-10:45 |
EnergyTransfer:Zone:F4 NE APARTMENT | 17.82 | 0.02 | 19-JAN-11:15 | 2517.42 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 5.19 | 0.00 | 01-JAN-08:30 | 2517.42 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 12.63 | 0.00 | 01-JAN-00:15 | 2193.21 | 26-JUN-08:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 12.44 | 0.03 | 02-APR-21:30 | 1616.69 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 1.73 | 0.00 | 01-JAN-00:15 | 1350.64 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 10.71 | 0.00 | 01-JAN-01:00 | 1616.69 | 08-JUN-18:30 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 12.46 | 0.01 | 27-JUL-19:45 | 1601.41 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 1.73 | 0.00 | 01-JAN-00:15 | 1352.43 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 10.73 | 0.00 | 01-JAN-01:00 | 1601.41 | 08-JUN-18:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 21.44 | 0.19 | 19-MAR-21:45 | 2305.62 | 18-NOV-12:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.63 | 0.00 | 01-JAN-00:15 | 1113.12 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 20.82 | 0.00 | 04-JAN-23:00 | 2305.62 | 18-NOV-12:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 21.46 | 0.01 | 11-SEP-20:30 | 2314.86 | 18-NOV-12:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.63 | 0.00 | 01-JAN-00:15 | 1113.37 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 20.84 | 0.00 | 04-JAN-23:00 | 2314.86 | 18-NOV-12:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 23.40 | 0.04 | 29-APR-22:45 | 3211.21 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 2.64 | 0.00 | 01-JAN-00:15 | 2405.15 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 20.77 | 0.00 | 03-JAN-06:00 | 3211.21 | 02-SEP-17:30 |
EnergyTransfer:Zone:M NW APARTMENT | 17.42 | 0.02 | 12-DEC-19:15 | 2972.05 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 5.51 | 0.00 | 01-JAN-14:15 | 2543.64 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 11.91 | 0.00 | 01-JAN-00:15 | 2972.05 | 15-JUN-18:15 |
EnergyTransfer:Zone:M SE APARTMENT | 24.19 | 0.01 | 23-MAR-10:45 | 2775.50 | 07-NOV-10:45 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 2.57 | 0.00 | 01-JAN-00:15 | 2405.62 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 21.62 | 0.00 | 03-JAN-06:00 | 2775.50 | 07-NOV-10:45 |
EnergyTransfer:Zone:M NE APARTMENT | 18.10 | 0.03 | 16-JAN-17:15 | 2606.10 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 5.28 | 0.00 | 01-JAN-08:30 | 2606.10 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 12.82 | 0.00 | 01-JAN-00:15 | 2224.16 | 26-JUN-08:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 12.74 | 0.03 | 28-AUG-08:15 | 1650.96 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.73 | 0.00 | 01-JAN-00:15 | 1371.28 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 11.01 | 0.00 | 01-JAN-01:00 | 1650.96 | 08-JUN-18:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 12.77 | 0.04 | 24-NOV-06:45 | 1633.98 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.73 | 0.00 | 01-JAN-00:15 | 1373.07 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 11.03 | 0.00 | 01-JAN-01:00 | 1633.98 | 08-JUN-18:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 21.75 | 0.15 | 05-SEP-09:15 | 2339.27 | 18-NOV-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.65 | 0.00 | 01-JAN-00:15 | 1114.08 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 21.11 | 0.00 | 04-JAN-23:00 | 2339.27 | 18-NOV-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 21.77 | 0.05 | 26-DEC-04:15 | 2348.20 | 18-NOV-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.65 | 0.00 | 01-JAN-00:15 | 1114.44 | 21-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 21.12 | 0.00 | 04-JAN-23:00 | 2348.20 | 18-NOV-12:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 22.70 | 0.02 | 06-APR-10:15 | 3169.28 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 2.97 | 0.00 | 01-JAN-00:15 | 2563.76 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 19.73 | 0.00 | 03-JAN-05:45 | 3169.28 | 02-SEP-17:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 17.41 | 0.00 | 13-MAY-00:45 | 2924.05 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 6.13 | 0.00 | 01-JAN-14:30 | 2679.67 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 11.28 | 0.00 | 01-JAN-00:15 | 2924.05 | 15-JUN-18:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 23.46 | 0.04 | 21-MAY-03:30 | 2726.09 | 07-NOV-10:45 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 2.90 | 0.00 | 01-JAN-00:15 | 2564.13 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 20.56 | 0.00 | 03-JAN-05:45 | 2726.09 | 07-NOV-10:45 |
EnergyTransfer:Zone:F6 NE APARTMENT | 18.04 | 0.03 | 25-NOV-16:00 | 2743.04 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 5.89 | 0.00 | 01-JAN-08:45 | 2743.04 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 12.15 | 0.00 | 01-JAN-00:15 | 2187.05 | 26-JUN-08:45 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 12.37 | 0.01 | 17-AUG-08:30 | 1611.06 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 2.03 | 0.00 | 01-JAN-00:15 | 1447.95 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 10.33 | 0.00 | 01-JAN-00:45 | 1611.06 | 08-JUN-18:30 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 12.39 | 0.06 | 22-NOV-07:30 | 1594.18 | 08-JUN-18:30 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 2.04 | 0.00 | 01-JAN-00:15 | 1449.73 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 10.36 | 0.00 | 01-JAN-00:45 | 1594.18 | 08-JUN-18:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 20.84 | 0.12 | 28-AUG-09:15 | 2294.57 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.76 | 0.00 | 01-JAN-00:15 | 1198.73 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 20.08 | 0.00 | 04-JAN-23:00 | 2294.57 | 18-NOV-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 20.85 | 0.28 | 25-MAY-16:00 | 2303.29 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.76 | 0.00 | 01-JAN-00:15 | 1198.88 | 19-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 20.10 | 0.00 | 04-JAN-23:00 | 2303.29 | 18-NOV-13:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 22.32 | 0.04 | 23-MAR-19:45 | 3153.78 | 02-SEP-17:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 3.25 | 0.00 | 01-JAN-00:15 | 2694.85 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 19.07 | 0.00 | 03-JAN-05:30 | 3153.78 | 02-SEP-17:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 17.54 | 0.03 | 22-FEB-14:30 | 2909.52 | 08-JUN-17:45 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 6.60 | 0.00 | 01-JAN-14:45 | 2783.34 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 10.95 | 0.00 | 01-JAN-00:15 | 2909.52 | 08-JUN-17:45 |
EnergyTransfer:Zone:F7 SE APARTMENT | 23.06 | 0.07 | 26-DEC-15:45 | 2705.81 | 31-AUG-09:45 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 3.17 | 0.00 | 01-JAN-00:15 | 2694.81 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 19.89 | 0.00 | 03-JAN-05:30 | 2705.81 | 31-AUG-09:45 |
EnergyTransfer:Zone:F7 NE APARTMENT | 18.12 | 0.03 | 04-DEC-10:15 | 2847.13 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 6.34 | 0.00 | 01-JAN-08:45 | 2847.13 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 11.78 | 0.00 | 01-JAN-00:15 | 2167.81 | 26-JUN-08:45 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 12.23 | 0.01 | 09-APR-13:15 | 1606.55 | 05-JUN-18:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 2.27 | 0.00 | 01-JAN-00:15 | 1500.34 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 9.96 | 0.00 | 01-JAN-00:30 | 1606.55 | 05-JUN-18:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 12.25 | 0.11 | 25-NOV-05:00 | 1590.68 | 05-JUN-18:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 2.27 | 0.00 | 01-JAN-00:15 | 1502.11 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 9.98 | 0.00 | 01-JAN-00:30 | 1590.68 | 05-JUN-18:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 20.29 | 0.08 | 28-NOV-21:30 | 2269.05 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 1282.66 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 19.44 | 0.00 | 04-JAN-22:45 | 2269.05 | 18-NOV-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 20.31 | 0.03 | 01-MAY-15:00 | 2271.85 | 18-NOV-13:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.86 | 0.00 | 01-JAN-00:15 | 1282.78 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 19.45 | 0.00 | 04-JAN-22:45 | 2271.85 | 18-NOV-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 22.07 | 0.09 | 17-MAR-14:00 | 3154.05 | 02-AUG-18:15 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 3.55 | 0.00 | 01-JAN-00:15 | 2830.55 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 18.52 | 0.00 | 03-JAN-05:00 | 3154.05 | 02-AUG-18:15 |
EnergyTransfer:Zone:F8 NW APARTMENT | 17.80 | 0.03 | 16-MAY-01:45 | 2910.25 | 08-JUN-17:45 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 7.08 | 0.00 | 01-JAN-15:00 | 2895.99 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 10.72 | 0.00 | 01-JAN-00:15 | 2910.25 | 08-JUN-17:45 |
EnergyTransfer:Zone:F8 SE APARTMENT | 22.79 | 0.04 | 04-APR-15:15 | 2830.08 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 3.46 | 0.00 | 01-JAN-00:15 | 2830.08 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 19.33 | 0.00 | 03-JAN-05:00 | 2703.61 | 31-AUG-09:45 |
EnergyTransfer:Zone:F8 NE APARTMENT | 18.33 | 0.02 | 07-APR-19:30 | 2948.66 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 6.80 | 0.00 | 01-JAN-08:45 | 2948.66 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 11.53 | 0.00 | 01-JAN-00:15 | 2163.78 | 26-JUN-08:45 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 12.23 | 0.05 | 31-JUL-05:45 | 1615.39 | 05-JUN-18:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 2.53 | 0.00 | 01-JAN-00:15 | 1555.92 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 9.70 | 0.00 | 01-JAN-00:30 | 1615.39 | 05-JUN-18:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 12.25 | 0.08 | 13-JAN-13:30 | 1599.56 | 05-JUN-18:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 2.53 | 0.00 | 01-JAN-00:15 | 1557.69 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 9.72 | 0.00 | 01-JAN-00:30 | 1599.56 | 05-JUN-18:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 19.84 | 0.41 | 16-MAR-15:45 | 2238.10 | 15-NOV-13:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 1375.55 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 18.87 | 0.00 | 04-JAN-22:30 | 2238.10 | 15-NOV-13:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 19.85 | 0.03 | 24-MAR-14:30 | 2244.40 | 16-NOV-12:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 1375.62 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 18.88 | 0.00 | 04-JAN-22:30 | 2244.40 | 16-NOV-12:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 22.12 | 0.01 | 30-JAN-08:30 | 3265.26 | 02-AUG-18:15 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 4.30 | 0.00 | 01-JAN-00:15 | 3089.83 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 17.82 | 0.00 | 03-JAN-03:15 | 3265.26 | 02-AUG-18:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 18.86 | 0.00 | 19-FEB-03:45 | 3145.35 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 8.20 | 0.00 | 01-JAN-15:15 | 3145.35 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 10.66 | 0.00 | 01-JAN-00:15 | 3001.47 | 15-JUN-18:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 22.80 | 0.12 | 26-MAR-00:45 | 3088.78 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 4.17 | 0.00 | 01-JAN-00:15 | 3088.78 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 18.63 | 0.00 | 03-JAN-04:30 | 2767.60 | 02-AUG-18:15 |
EnergyTransfer:Zone:F9 NE APARTMENT | 19.27 | 0.13 | 03-JAN-11:45 | 3153.18 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 7.86 | 0.00 | 01-JAN-09:00 | 3153.18 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 11.41 | 0.00 | 01-JAN-00:15 | 2193.48 | 02-AUG-18:15 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 12.77 | 0.00 | 03-JAN-22:45 | 1724.97 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.28 | 0.00 | 01-JAN-16:15 | 1724.97 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 9.49 | 0.00 | 01-JAN-00:15 | 1708.72 | 05-JUN-18:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 12.80 | 0.00 | 19-JUL-16:45 | 1726.78 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.29 | 0.00 | 01-JAN-16:15 | 1726.78 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 9.51 | 0.00 | 01-JAN-00:15 | 1692.60 | 05-JUN-18:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 19.34 | 0.05 | 28-MAR-03:00 | 2254.63 | 16-NOV-12:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 1.33 | 0.00 | 01-JAN-00:15 | 1587.48 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 18.01 | 0.00 | 04-JAN-13:30 | 2254.63 | 16-NOV-12:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 19.37 | 0.09 | 07-DEC-08:00 | 2264.91 | 16-NOV-12:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 1.34 | 0.00 | 01-JAN-00:15 | 1587.49 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 18.03 | 0.00 | 04-JAN-13:30 | 2264.91 | 16-NOV-12:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 28.24 | 0.10 | 03-MAR-20:00 | 3996.41 | 12-SEP-15:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 9.82 | 0.00 | 01-JAN-08:45 | 3867.57 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 18.42 | 0.00 | 01-JAN-00:15 | 3996.41 | 12-SEP-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 25.37 | 0.09 | 28-JAN-16:30 | 3912.97 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.92 | 0.00 | 01-JAN-15:15 | 3912.97 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 11.46 | 0.00 | 01-JAN-00:15 | 3653.64 | 15-JUN-17:30 |
EnergyTransfer:Zone:T SE APARTMENT | 28.09 | 0.05 | 05-OCT-05:45 | 3866.84 | 19-MAR-07:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 9.46 | 0.00 | 01-JAN-08:15 | 3866.84 | 19-MAR-07:15 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 18.63 | 0.00 | 01-JAN-00:15 | 3567.51 | 31-AUG-10:45 |
EnergyTransfer:Zone:T NE APARTMENT | 24.81 | 0.00 | 08-OCT-23:30 | 3933.53 | 21-DEC-23:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 13.19 | 0.00 | 01-JAN-09:15 | 3933.53 | 21-DEC-23:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 11.63 | 0.00 | 01-JAN-00:15 | 2804.03 | 26-JUN-08:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 16.82 | 0.01 | 22-JAN-20:15 | 2608.06 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.53 | 0.00 | 03-JAN-11:15 | 2608.06 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 9.30 | 0.00 | 01-JAN-00:15 | 2243.36 | 29-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 16.86 | 0.02 | 05-SEP-19:00 | 2608.96 | 22-DEC-04:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.54 | 0.00 | 01-JAN-12:45 | 2608.96 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 9.31 | 0.00 | 01-JAN-00:15 | 2238.55 | 29-JUN-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 21.32 | 0.02 | 30-JAN-10:00 | 2976.66 | 16-NOV-12:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 4.48 | 0.00 | 01-JAN-00:15 | 2496.66 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 16.85 | 0.00 | 01-JAN-01:45 | 2976.66 | 16-NOV-12:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 21.36 | 0.02 | 27-SEP-01:30 | 2985.93 | 16-NOV-12:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 4.49 | 0.00 | 01-JAN-00:15 | 2497.79 | 22-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 16.88 | 0.00 | 01-JAN-01:45 | 2985.93 | 16-NOV-12:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1227.22 | 498.76 | 15-AUG-01:15 | 215210.63 | 23-DEC-07:15 |
WaterSystems:EnergyTransfer | 914.59 | 498.76 | 15-AUG-01:15 | 61861.86 | 15-FEB-07:45 |
sub cat:WaterSystems:EnergyTransfer | 914.59 | 498.76 | 15-AUG-01:15 | 61861.86 | 15-FEB-07:45 |
EnergyTransfer:HVAC | 1671.83 | 0.00 | 23-MAR-12:30 | 226834.52 | 22-DEC-04:00 |
CoolingCoils:EnergyTransfer | 1203.55 | 0.00 | 01-JAN-00:15 | 205438.93 | 30-JUL-14:30 |
HeatingCoils:EnergyTransfer | 468.28 | 0.00 | 09-JAN-11:15 | 226834.52 | 22-DEC-04:00 |
PlantLoopHeatingDemand:HVAC | 359.28 | 0.00 | 09-JAN-11:15 | 166823.24 | 22-DEC-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 359.28 | 0.00 | 09-JAN-11:15 | 166823.24 | 22-DEC-04:00 |
Boilers:EnergyTransfer | 312.63 | 0.00 | 01-JAN-00:15 | 164551.15 | 22-DEC-04:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 3.722 | -11.112 | 0.000 | 0.000 | 3.789 | 2.413 | 12.213 | 25.463 | 0.000 | 0.205 | 0.000 | 0.000 | -12.606 | 0.000 | -5.911 | -18.176 |
G NW APARTMENT | 6.710 | -6.643 | 0.000 | 0.000 | 3.846 | 2.413 | 12.213 | 11.536 | 0.000 | 0.204 | 0.000 | 0.000 | -12.724 | 0.000 | -5.489 | -12.066 |
OFFICE | 3.734 | -17.804 | 0.000 | 0.000 | 0.516 | 21.954 | 7.547 | 26.081 | 0.000 | 0.115 | 0.001 | 0.000 | -12.492 | 0.000 | -3.052 | -26.601 |
G NE APARTMENT | 6.403 | -7.187 | 0.000 | 0.000 | 3.861 | 2.413 | 12.213 | 12.121 | 0.000 | 0.202 | 0.000 | 0.000 | -12.445 | 0.000 | -5.473 | -12.108 |
G N1 APARTMENT | 3.247 | -5.638 | 0.000 | 0.000 | 3.868 | 2.413 | 12.213 | 3.940 | 0.000 | 0.157 | 0.000 | 0.000 | -7.938 | 0.000 | -4.062 | -8.199 |
G N2 APARTMENT | 3.247 | -5.650 | 0.000 | 0.000 | 3.868 | 2.413 | 12.213 | 3.937 | 0.000 | 0.157 | 0.000 | 0.000 | -7.934 | 0.000 | -4.063 | -8.187 |
G S1 APARTMENT | 1.251 | -10.860 | 0.000 | 0.000 | 3.787 | 2.413 | 12.213 | 17.993 | 0.000 | 0.155 | 0.001 | 0.000 | -7.713 | 0.000 | -4.582 | -14.658 |
G S2 APARTMENT | 1.225 | -11.035 | 0.000 | 0.000 | 3.784 | 2.413 | 12.213 | 17.981 | 0.000 | 0.156 | 0.000 | 0.000 | -7.719 | 0.000 | -4.604 | -14.414 |
F2 SW APARTMENT | 2.562 | -19.261 | 0.000 | 0.000 | 3.697 | 2.413 | 12.213 | 24.792 | 0.000 | 0.273 | 0.003 | 0.000 | -13.518 | 0.000 | -7.869 | -5.301 |
F2 NW APARTMENT | 5.479 | -10.863 | 0.000 | 0.000 | 3.790 | 2.413 | 12.213 | 11.085 | 0.000 | 0.270 | 0.000 | 0.000 | -13.484 | 0.000 | -7.422 | -3.481 |
F2 SE APARTMENT | 2.335 | -21.036 | 0.000 | 0.000 | 3.699 | 2.413 | 12.213 | 25.390 | 0.000 | 0.272 | 0.002 | 0.000 | -13.351 | 0.000 | -7.913 | -4.021 |
F2 NE APARTMENT | 5.235 | -11.789 | 0.000 | 0.000 | 3.807 | 2.413 | 12.213 | 11.657 | 0.000 | 0.267 | 0.000 | 0.000 | -13.166 | 0.000 | -7.389 | -3.247 |
F2 N1 APARTMENT | 1.917 | -9.514 | 0.000 | 0.000 | 3.807 | 2.413 | 12.213 | 3.702 | 0.000 | 0.203 | 0.000 | 0.000 | -8.465 | 0.000 | -5.471 | -0.806 |
F2 N2 APARTMENT | 1.917 | -9.537 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 3.700 | 0.000 | 0.203 | 0.000 | 0.000 | -8.460 | 0.000 | -5.471 | -0.787 |
F2 S1 APARTMENT | 0.693 | -18.663 | 0.000 | 0.000 | 3.677 | 2.413 | 12.213 | 17.556 | 0.000 | 0.202 | 0.001 | 0.000 | -8.289 | 0.000 | -6.046 | -3.755 |
F2 S2 APARTMENT | 0.691 | -18.768 | 0.000 | 0.000 | 3.676 | 2.413 | 12.213 | 17.552 | 0.000 | 0.202 | 0.001 | 0.000 | -8.292 | 0.000 | -6.052 | -3.635 |
F3 SW APARTMENT | 2.423 | -20.625 | 0.000 | 0.000 | 3.683 | 2.413 | 12.213 | 24.533 | 0.000 | 0.313 | 0.001 | 0.000 | -13.775 | 0.000 | -8.942 | -2.235 |
F3 NW APARTMENT | 5.225 | -11.636 | 0.000 | 0.000 | 3.779 | 2.413 | 12.213 | 10.930 | 0.000 | 0.310 | 0.000 | 0.000 | -13.738 | 0.000 | -8.471 | -1.024 |
F3 SE APARTMENT | 2.333 | -21.640 | 0.000 | 0.000 | 3.692 | 2.413 | 12.213 | 25.152 | 0.000 | 0.310 | 0.000 | 0.000 | -13.556 | 0.000 | -8.961 | -1.955 |
F3 NE APARTMENT | 5.017 | -12.571 | 0.000 | 0.000 | 3.796 | 2.413 | 12.213 | 11.495 | 0.000 | 0.305 | 0.000 | 0.000 | -13.408 | 0.000 | -8.434 | -0.827 |
F3 N1 APARTMENT | 1.686 | -10.507 | 0.000 | 0.000 | 3.790 | 2.413 | 12.213 | 3.632 | 0.000 | 0.230 | 1.404 | 0.000 | -8.645 | 0.000 | -6.216 | -0.000 |
F3 N2 APARTMENT | 1.691 | -10.530 | 0.000 | 0.000 | 3.791 | 2.413 | 12.213 | 3.630 | 0.000 | 0.230 | 1.417 | 0.000 | -8.640 | 0.000 | -6.214 | -0.000 |
F3 S1 APARTMENT | 0.603 | -20.560 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 17.379 | 0.000 | 0.229 | 0.001 | 0.000 | -8.468 | 0.000 | -6.806 | -0.658 |
F3 S2 APARTMENT | 0.603 | -20.599 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 17.377 | 0.000 | 0.229 | 0.002 | 0.000 | -8.467 | 0.000 | -6.809 | -0.614 |
F4 SW APARTMENT | 2.539 | -20.638 | 0.000 | 0.000 | 3.683 | 2.413 | 12.213 | 24.380 | 0.000 | 0.342 | 0.002 | 0.000 | -13.894 | 0.000 | -9.740 | -1.300 |
F4 NW APARTMENT | 5.401 | -11.709 | 0.000 | 0.000 | 3.778 | 2.413 | 12.213 | 10.847 | 0.000 | 0.339 | 0.000 | 0.000 | -13.867 | 0.000 | -9.236 | -0.180 |
F4 SE APARTMENT | 2.472 | -21.524 | 0.000 | 0.000 | 3.693 | 2.413 | 12.213 | 24.999 | 0.000 | 0.339 | 0.000 | 0.000 | -13.662 | 0.000 | -9.755 | -1.188 |
F4 NE APARTMENT | 5.189 | -12.626 | 0.000 | 0.000 | 3.795 | 2.413 | 12.213 | 11.407 | 0.000 | 0.333 | 0.001 | 0.000 | -13.530 | 0.000 | -9.195 | -0.000 |
F4 N1 APARTMENT | 1.727 | -10.714 | 0.000 | 0.000 | 3.786 | 2.413 | 12.213 | 3.598 | 0.000 | 0.250 | 2.208 | 0.000 | -8.738 | 0.000 | -6.743 | -0.000 |
F4 N2 APARTMENT | 1.728 | -10.733 | 0.000 | 0.000 | 3.787 | 2.413 | 12.213 | 3.596 | 0.000 | 0.250 | 2.219 | 0.000 | -8.732 | 0.000 | -6.741 | -0.000 |
F4 S1 APARTMENT | 0.625 | -20.817 | 0.000 | 0.000 | 3.652 | 2.413 | 12.213 | 17.274 | 0.000 | 0.250 | 0.298 | 0.000 | -8.550 | 0.000 | -7.358 | -0.000 |
F4 S2 APARTMENT | 0.626 | -20.838 | 0.000 | 0.000 | 3.652 | 2.413 | 12.213 | 17.272 | 0.000 | 0.250 | 0.321 | 0.000 | -8.548 | 0.000 | -7.361 | -0.000 |
M SW APARTMENT | 2.636 | -20.765 | 0.000 | 0.000 | 3.684 | 2.413 | 12.213 | 24.256 | 0.000 | 0.366 | 0.001 | 0.000 | -13.991 | 0.000 | -10.409 | -0.401 |
M NW APARTMENT | 5.506 | -11.909 | 0.000 | 0.000 | 3.777 | 2.413 | 12.213 | 10.780 | 0.000 | 0.362 | 0.710 | 0.000 | -13.972 | 0.000 | -9.878 | -0.000 |
M SE APARTMENT | 2.567 | -21.624 | 0.000 | 0.000 | 3.694 | 2.413 | 12.213 | 24.872 | 0.000 | 0.362 | 0.000 | 0.000 | -13.755 | 0.000 | -10.423 | -0.318 |
M NE APARTMENT | 5.280 | -12.821 | 0.000 | 0.000 | 3.794 | 2.413 | 12.213 | 11.334 | 0.000 | 0.355 | 0.897 | 0.000 | -13.631 | 0.000 | -9.834 | -0.000 |
M N1 APARTMENT | 1.731 | -11.007 | 0.000 | 0.000 | 3.783 | 2.413 | 12.213 | 3.570 | 0.000 | 0.265 | 3.032 | 0.000 | -8.812 | 0.000 | -7.188 | -0.000 |
M N2 APARTMENT | 1.734 | -11.031 | 0.000 | 0.000 | 3.784 | 2.413 | 12.213 | 3.569 | 0.000 | 0.265 | 3.045 | 0.000 | -8.806 | 0.000 | -7.186 | -0.000 |
M S1 APARTMENT | 0.646 | -21.107 | 0.000 | 0.000 | 3.651 | 2.413 | 12.213 | 17.190 | 0.000 | 0.265 | 1.168 | 0.000 | -8.615 | 0.000 | -7.825 | -0.000 |
M S2 APARTMENT | 0.646 | -21.124 | 0.000 | 0.000 | 3.651 | 2.413 | 12.213 | 17.188 | 0.000 | 0.266 | 1.186 | 0.000 | -8.613 | 0.000 | -7.827 | -0.000 |
F6 SW APARTMENT | 2.974 | -19.727 | 0.000 | 0.000 | 3.693 | 2.413 | 12.213 | 24.191 | 0.000 | 0.397 | 0.000 | 0.000 | -14.001 | 0.000 | -10.950 | -1.202 |
F6 NW APARTMENT | 6.128 | -11.284 | 0.000 | 0.000 | 3.786 | 2.413 | 12.213 | 10.762 | 0.000 | 0.393 | 0.000 | 0.000 | -13.982 | 0.000 | -10.372 | -0.055 |
F6 SE APARTMENT | 2.896 | -20.562 | 0.000 | 0.000 | 3.703 | 2.413 | 12.213 | 24.805 | 0.000 | 0.392 | 0.000 | 0.000 | -13.764 | 0.000 | -10.965 | -1.132 |
F6 NE APARTMENT | 5.886 | -12.155 | 0.000 | 0.000 | 3.802 | 2.413 | 12.213 | 11.313 | 0.000 | 0.384 | 0.110 | 0.000 | -13.641 | 0.000 | -10.325 | -0.000 |
F6 N1 APARTMENT | 2.032 | -10.335 | 0.000 | 0.000 | 3.792 | 2.413 | 12.213 | 3.569 | 0.000 | 0.290 | 2.344 | 0.000 | -8.816 | 0.000 | -7.502 | -0.000 |
F6 N2 APARTMENT | 2.036 | -10.358 | 0.000 | 0.000 | 3.793 | 2.413 | 12.213 | 3.567 | 0.000 | 0.289 | 2.356 | 0.000 | -8.810 | 0.000 | -7.500 | -0.000 |
F6 S1 APARTMENT | 0.757 | -20.079 | 0.000 | 0.000 | 3.660 | 2.413 | 12.213 | 17.144 | 0.000 | 0.289 | 0.410 | 0.000 | -8.621 | 0.000 | -8.187 | -0.000 |
F6 S2 APARTMENT | 0.759 | -20.095 | 0.000 | 0.000 | 3.660 | 2.413 | 12.213 | 17.142 | 0.000 | 0.290 | 0.426 | 0.000 | -8.619 | 0.000 | -8.189 | -0.000 |
F7 SW APARTMENT | 3.248 | -19.072 | 0.000 | 0.000 | 3.700 | 2.413 | 12.213 | 24.129 | 0.000 | 0.416 | 0.000 | 0.000 | -14.022 | 0.000 | -11.431 | -1.592 |
F7 NW APARTMENT | 6.599 | -10.946 | 0.000 | 0.000 | 3.792 | 2.413 | 12.213 | 10.739 | 0.000 | 0.411 | 0.000 | 0.000 | -14.005 | 0.000 | -10.816 | -0.400 |
F7 SE APARTMENT | 3.165 | -19.892 | 0.000 | 0.000 | 3.710 | 2.413 | 12.213 | 24.740 | 0.000 | 0.411 | 0.000 | 0.000 | -13.784 | 0.000 | -11.448 | -1.528 |
F7 NE APARTMENT | 6.337 | -11.781 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 11.286 | 0.000 | 0.401 | 0.000 | 0.000 | -13.663 | 0.000 | -10.768 | -0.246 |
F7 N1 APARTMENT | 2.268 | -9.965 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 3.564 | 0.000 | 0.303 | 2.021 | 0.000 | -8.828 | 0.000 | -7.788 | -0.000 |
F7 N2 APARTMENT | 2.270 | -9.983 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 3.562 | 0.000 | 0.302 | 2.033 | 0.000 | -8.822 | 0.000 | -7.787 | -0.000 |
F7 S1 APARTMENT | 0.853 | -19.435 | 0.000 | 0.000 | 3.667 | 2.413 | 12.213 | 17.101 | 0.000 | 0.303 | 0.029 | 0.000 | -8.634 | 0.000 | -8.510 | -0.000 |
F7 S2 APARTMENT | 0.856 | -19.453 | 0.000 | 0.000 | 3.668 | 2.413 | 12.213 | 17.099 | 0.000 | 0.303 | 0.046 | 0.000 | -8.632 | 0.000 | -8.512 | -0.000 |
F8 SW APARTMENT | 3.550 | -18.521 | 0.000 | 0.000 | 3.706 | 2.413 | 12.213 | 24.075 | 0.000 | 0.430 | 0.000 | 0.000 | -14.039 | 0.000 | -11.877 | -1.951 |
F8 NW APARTMENT | 7.076 | -10.722 | 0.000 | 0.000 | 3.797 | 2.413 | 12.213 | 10.717 | 0.000 | 0.426 | 0.000 | 0.000 | -14.028 | 0.000 | -11.232 | -0.660 |
F8 SE APARTMENT | 3.460 | -19.334 | 0.000 | 0.000 | 3.716 | 2.413 | 12.213 | 24.683 | 0.000 | 0.425 | 0.001 | 0.000 | -13.799 | 0.000 | -11.894 | -1.883 |
F8 NE APARTMENT | 6.799 | -11.534 | 0.000 | 0.000 | 3.812 | 2.413 | 12.213 | 11.261 | 0.000 | 0.415 | 0.001 | 0.000 | -13.686 | 0.000 | -11.183 | -0.510 |
F8 N1 APARTMENT | 2.527 | -9.699 | 0.000 | 0.000 | 3.804 | 2.413 | 12.213 | 3.559 | 0.000 | 0.312 | 1.773 | 0.000 | -8.839 | 0.000 | -8.062 | -0.000 |
F8 N2 APARTMENT | 2.529 | -9.720 | 0.000 | 0.000 | 3.805 | 2.413 | 12.213 | 3.557 | 0.000 | 0.311 | 1.786 | 0.000 | -8.834 | 0.000 | -8.061 | -0.000 |
F8 S1 APARTMENT | 0.970 | -18.866 | 0.000 | 0.000 | 3.675 | 2.413 | 12.213 | 17.064 | 0.000 | 0.313 | 0.001 | 0.000 | -8.642 | 0.000 | -8.812 | -0.327 |
F8 S2 APARTMENT | 0.972 | -18.882 | 0.000 | 0.000 | 3.675 | 2.413 | 12.213 | 17.062 | 0.000 | 0.313 | 0.001 | 0.000 | -8.640 | 0.000 | -8.815 | -0.309 |
F9 SW APARTMENT | 4.296 | -17.821 | 0.000 | 0.000 | 3.717 | 2.413 | 12.213 | 24.052 | 0.000 | 0.444 | 0.001 | 0.000 | -14.009 | 0.000 | -12.270 | -3.035 |
F9 NW APARTMENT | 8.198 | -10.664 | 0.000 | 0.000 | 3.801 | 2.413 | 12.213 | 10.707 | 0.000 | 0.438 | 0.000 | 0.000 | -14.026 | 0.000 | -11.609 | -1.471 |
F9 SE APARTMENT | 4.171 | -18.631 | 0.000 | 0.000 | 3.727 | 2.413 | 12.213 | 24.657 | 0.000 | 0.440 | 0.000 | 0.000 | -13.771 | 0.000 | -12.291 | -2.929 |
F9 NE APARTMENT | 7.856 | -11.413 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 11.248 | 0.000 | 0.426 | 0.000 | 0.000 | -13.685 | 0.000 | -11.562 | -1.312 |
F9 N1 APARTMENT | 3.282 | -9.490 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 3.558 | 0.000 | 0.322 | 1.040 | 0.000 | -8.832 | 0.000 | -8.314 | -0.000 |
F9 N2 APARTMENT | 3.286 | -9.514 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 3.556 | 0.000 | 0.321 | 1.056 | 0.000 | -8.826 | 0.000 | -8.314 | -0.000 |
F9 S1 APARTMENT | 1.332 | -18.009 | 0.000 | 0.000 | 3.689 | 2.413 | 12.213 | 17.049 | 0.000 | 0.323 | 0.001 | 0.000 | -8.617 | 0.000 | -9.075 | -1.316 |
F9 S2 APARTMENT | 1.336 | -18.032 | 0.000 | 0.000 | 3.689 | 2.413 | 12.213 | 17.046 | 0.000 | 0.323 | 0.000 | 0.000 | -8.615 | 0.000 | -9.079 | -1.294 |
T SW APARTMENT | 9.818 | -18.421 | 0.000 | 0.000 | 3.775 | 2.413 | 12.213 | 23.757 | 0.000 | 0.455 | 0.000 | 0.000 | -13.344 | 0.000 | -12.540 | -8.125 |
T NW APARTMENT | 13.915 | -11.459 | 0.000 | 0.000 | 3.822 | 2.413 | 12.213 | 10.450 | 0.000 | 0.450 | 0.000 | 0.000 | -13.533 | 0.000 | -12.031 | -6.240 |
T SE APARTMENT | 9.460 | -18.627 | 0.000 | 0.000 | 3.782 | 2.413 | 12.213 | 24.375 | 0.000 | 0.454 | 0.000 | 0.000 | -13.141 | 0.000 | -12.585 | -8.343 |
T NE APARTMENT | 13.189 | -11.625 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 11.042 | 0.000 | 0.443 | 0.000 | 0.000 | -13.252 | 0.000 | -11.997 | -6.263 |
T N1 APARTMENT | 7.526 | -9.296 | 0.000 | 0.000 | 3.831 | 2.413 | 12.213 | 3.471 | 0.000 | 0.332 | 0.000 | 0.000 | -8.525 | 0.000 | -8.613 | -3.351 |
T N2 APARTMENT | 7.542 | -9.313 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 3.465 | 0.000 | 0.332 | 0.000 | 0.000 | -8.519 | 0.000 | -8.618 | -3.346 |
T S1 APARTMENT | 4.478 | -16.846 | 0.000 | 0.000 | 3.755 | 2.413 | 12.213 | 16.897 | 0.000 | 0.336 | 0.000 | 0.000 | -8.242 | 0.000 | -9.263 | -5.741 |
T S2 APARTMENT | 4.486 | -16.878 | 0.000 | 0.000 | 3.755 | 2.413 | 12.213 | 16.892 | 0.000 | 0.336 | 0.000 | 0.000 | -8.238 | 0.000 | -9.268 | -5.710 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 5.394 | 0.000 | 1.263 | 19.549 | 0.000 | -2.932 | 0.000 | -41.803 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.429 | 0.000 | 0.015 | 0.000 | 0.000 | -1.720 | 0.000 | -0.820 | -18.433 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.382 | 0.000 | 0.017 | 0.000 | 0.000 | -1.782 | 0.000 | -0.996 | -18.150 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.356 | 0.000 | 0.018 | 0.000 | 0.000 | -1.812 | 0.000 | -1.125 | -17.967 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 2.325 | 0.000 | 0.016 | 0.000 | 0.000 | -1.854 | 0.000 | -1.271 | -36.274 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.336 | 0.000 | 0.021 | 0.000 | 0.000 | -1.828 | 0.000 | -1.304 | -17.754 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.336 | 0.000 | 0.022 | 0.000 | 0.000 | -1.821 | 0.000 | -1.368 | -17.698 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.332 | 0.000 | 0.023 | 0.000 | 0.000 | -1.820 | 0.000 | -1.429 | -17.635 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.331 | 0.000 | 0.023 | 0.000 | 0.000 | -1.816 | 0.000 | -1.481 | -17.587 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 2.274 | 0.000 | 0.012 | 0.000 | 0.000 | -1.753 | 0.000 | -1.551 | -25.449 |
Total Facility | 292.119 | -1173.453 | 0.000 | 0.000 | 297.038 | 416.414 | 980.287 | 1160.157 | 0.000 | 26.377 | 52.910 | 0.000 | -904.477 | 0.000 | -739.985 | -407.367 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 02-SEP-17:30 | 0.00 | -2421.42 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1950.35 | 0.00 | 261.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -715.06 |
G NW APARTMENT | 15-JUN-18:00 | 0.00 | -2247.61 | 0.00 | 0.00 | 140.55 | 194.45 | 588.62 | 2982.76 | 0.00 | 38.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.86 |
OFFICE | 29-AUG-12:30 | 0.00 | -3113.76 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3418.54 | 0.00 | 37.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2574.42 |
G NE APARTMENT | 06-JUN-08:30 | 0.00 | -1567.94 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2755.58 | 0.00 | 226.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1877.58 |
G N1 APARTMENT | 08-JUN-18:15 | 0.00 | -1129.72 | 0.00 | 0.00 | 141.00 | 230.46 | 547.42 | 739.76 | 0.00 | 119.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -648.11 |
G N2 APARTMENT | 08-JUN-18:15 | 0.00 | -1109.20 | 0.00 | 0.00 | 140.91 | 230.46 | 547.42 | 740.07 | 0.00 | 118.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -667.91 |
G S1 APARTMENT | 05-SEP-13:30 | 0.00 | -1457.40 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2234.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39.67 | -1189.25 |
G S2 APARTMENT | 05-SEP-13:45 | 0.00 | -1503.73 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2188.11 | 0.00 | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1136.62 |
F2 SW APARTMENT | 02-SEP-17:30 | 0.00 | -3158.14 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1928.38 | 0.00 | 331.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26.98 |
F2 NW APARTMENT | 15-JUN-18:00 | 0.00 | -2917.58 | 0.00 | 0.00 | 140.85 | 194.45 | 588.62 | 2935.06 | 0.00 | 54.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -996.17 |
F2 SE APARTMENT | 31-AUG-09:45 | 0.00 | -2901.09 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3959.69 | 0.00 | 180.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1714.70 |
F2 NE APARTMENT | 06-JUN-08:30 | 0.00 | -2156.07 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2714.31 | 0.00 | 296.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1318.61 |
F2 N1 APARTMENT | 08-JUN-18:15 | 0.00 | -1566.60 | 0.00 | 0.00 | 140.67 | 230.46 | 547.42 | 717.86 | 0.00 | 144.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -214.56 |
F2 N2 APARTMENT | 08-JUN-18:15 | 0.00 | -1549.41 | 0.00 | 0.00 | 140.60 | 230.46 | 547.42 | 718.00 | 0.00 | 143.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -230.91 |
F2 S1 APARTMENT | 16-NOV-12:00 | 0.00 | -2184.10 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 4028.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9.05 | -2317.37 |
F2 S2 APARTMENT | 16-NOV-12:00 | 0.00 | -2206.10 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 4028.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9.05 | -2295.14 |
F3 SW APARTMENT | 02-SEP-17:30 | 0.00 | -3171.78 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1919.79 | 0.00 | 371.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.03 |
F3 NW APARTMENT | 15-JUN-18:15 | 0.00 | -2947.45 | 0.00 | 0.00 | 140.85 | 230.46 | 547.42 | 2809.01 | 0.00 | 48.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -828.34 |
F3 SE APARTMENT | 31-AUG-09:45 | 0.00 | -2751.06 | 0.00 | 0.00 | 40.52 | 28.81 | 406.15 | 3942.25 | 0.00 | 174.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1841.57 |
F3 NE APARTMENT | 06-JUN-08:30 | 0.00 | -2186.75 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2697.55 | 0.00 | 331.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1305.84 |
F3 N1 APARTMENT | 08-JUN-18:15 | 0.00 | -1603.11 | 0.00 | 0.00 | 140.18 | 230.46 | 547.42 | 711.11 | 0.00 | 155.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -181.42 |
F3 N2 APARTMENT | 08-JUN-18:15 | 0.00 | -1586.03 | 0.00 | 0.00 | 140.12 | 230.46 | 547.42 | 711.26 | 0.00 | 154.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -197.65 |
F3 S1 APARTMENT | 18-NOV-13:00 | 0.00 | -2284.00 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3597.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.07 | -1717.70 |
F3 S2 APARTMENT | 18-NOV-13:00 | 0.00 | -2291.85 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3596.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.06 | -1709.77 |
F4 SW APARTMENT | 02-SEP-17:30 | 0.00 | -3179.10 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1913.61 | 0.00 | 399.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59.09 |
F4 NW APARTMENT | 15-JUN-18:15 | 0.00 | -2947.25 | 0.00 | 0.00 | 140.67 | 230.46 | 547.42 | 2794.33 | 0.00 | 53.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -818.82 |
F4 SE APARTMENT | 07-NOV-10:45 | 0.00 | -2752.42 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 4478.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39.55 | -2162.60 |
F4 NE APARTMENT | 26-JUN-08:23 | 0.00 | -2198.04 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2711.85 | 0.00 | 135.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1113.50 |
F4 N1 APARTMENT | 08-JUN-18:30 | 0.00 | -1616.68 | 0.00 | 0.00 | 140.48 | 230.46 | 547.42 | 640.60 | 0.00 | 79.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.70 |
F4 N2 APARTMENT | 08-JUN-18:30 | 0.00 | -1601.40 | 0.00 | 0.00 | 140.41 | 230.46 | 547.42 | 640.75 | 0.00 | 78.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36.22 |
F4 S1 APARTMENT | 18-NOV-12:45 | 0.00 | -2305.42 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3676.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.17 | -1769.13 |
F4 S2 APARTMENT | 18-NOV-12:45 | 0.00 | -2314.66 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3675.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.15 | -1759.83 |
M SW APARTMENT | 02-SEP-17:30 | 0.00 | -3209.76 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1908.07 | 0.00 | 422.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.81 |
M NW APARTMENT | 15-JUN-18:15 | 0.00 | -2972.97 | 0.00 | 0.00 | 140.58 | 230.46 | 547.42 | 2782.20 | 0.00 | 57.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -785.06 |
M SE APARTMENT | 07-NOV-10:45 | 0.00 | -2775.75 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 4471.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.07 | -2128.17 |
M NE APARTMENT | 26-JUN-08:30 | 0.00 | -2225.10 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2704.17 | 0.00 | 137.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1080.84 |
M N1 APARTMENT | 08-JUN-18:30 | 0.00 | -1650.93 | 0.00 | 0.00 | 140.41 | 230.46 | 547.42 | 637.24 | 0.00 | 82.06 | 13.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 08-JUN-18:30 | 0.00 | -1633.96 | 0.00 | 0.00 | 140.35 | 230.46 | 547.42 | 637.39 | 0.00 | 80.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2.56 |
M S1 APARTMENT | 18-NOV-12:45 | 0.00 | -2339.06 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3663.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.95 | -1715.86 |
M S2 APARTMENT | 18-NOV-12:45 | 0.00 | -2347.99 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3663.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.93 | -1706.88 |
F6 SW APARTMENT | 02-SEP-17:30 | 0.00 | -3167.80 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1905.25 | 0.00 | 440.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.04 |
F6 NW APARTMENT | 15-JUN-18:15 | 0.00 | -2924.97 | 0.00 | 0.00 | 140.45 | 230.46 | 547.42 | 2773.71 | 0.00 | 60.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -827.85 |
F6 SE APARTMENT | 07-NOV-10:45 | 0.00 | -2726.34 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 4466.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46.07 | -2170.27 |
F6 NE APARTMENT | 26-JUN-08:45 | 0.00 | -2187.41 | 0.00 | 0.00 | 40.58 | 28.81 | 394.37 | 2621.29 | 0.00 | 228.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.79 |
F6 N1 APARTMENT | 08-JUN-18:30 | 0.00 | -1611.02 | 0.00 | 0.00 | 140.29 | 230.46 | 547.42 | 635.66 | 0.00 | 82.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24.86 |
F6 N2 APARTMENT | 02-AUG-18:15 | 0.00 | -1594.42 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 342.92 | 0.00 | 530.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -199.03 |
F6 S1 APARTMENT | 18-NOV-13:00 | 0.00 | -2294.39 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3558.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.63 | -1646.87 |
F6 S2 APARTMENT | 18-NOV-13:00 | 0.00 | -2303.12 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3558.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.61 | -1638.11 |
F7 SW APARTMENT | 02-SEP-17:30 | 0.00 | -3152.28 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 1902.22 | 0.00 | 456.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -131.02 |
F7 NW APARTMENT | 08-JUN-17:45 | 0.00 | -2909.68 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 2536.16 | 0.00 | 287.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.97 |
F7 SE APARTMENT | 31-AUG-09:45 | 0.00 | -2705.24 | 0.00 | 0.00 | 40.48 | 28.81 | 406.15 | 3905.86 | 0.00 | 193.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.48 |
F7 NE APARTMENT | 26-JUN-08:45 | 0.00 | -2168.18 | 0.00 | 0.00 | 40.55 | 28.81 | 394.37 | 2616.60 | 0.00 | 232.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1144.44 |
F7 N1 APARTMENT | 05-JUN-18:15 | 0.00 | -1606.00 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 461.30 | 0.00 | 372.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.71 |
F7 N2 APARTMENT | 05-JUN-18:15 | 0.00 | -1590.14 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 461.56 | 0.00 | 372.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -163.29 |
F7 S1 APARTMENT | 18-NOV-13:00 | 0.00 | -2268.87 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3549.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97.96 | -1658.14 |
F7 S2 APARTMENT | 18-NOV-13:00 | 0.00 | -2271.67 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3549.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97.96 | -1655.28 |
F8 SW APARTMENT | 02-AUG-18:08 | 0.00 | -3155.59 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 1033.93 | 0.00 | 1149.61 | 52.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 NW APARTMENT | 08-JUN-17:45 | 0.00 | -2910.40 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 2529.51 | 0.00 | 294.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.92 |
F8 SE APARTMENT | 31-AUG-09:45 | 0.00 | -2703.04 | 0.00 | 0.00 | 40.50 | 28.81 | 406.15 | 3899.91 | 0.00 | 197.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.95 |
F8 NE APARTMENT | 26-JUN-08:45 | 0.00 | -2164.16 | 0.00 | 0.00 | 40.53 | 28.81 | 394.37 | 2612.02 | 0.00 | 235.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1147.43 |
F8 N1 APARTMENT | 05-JUN-18:15 | 0.00 | -1614.84 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 460.40 | 0.00 | 383.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -148.91 |
F8 N2 APARTMENT | 05-JUN-18:15 | 0.00 | -1599.01 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 460.66 | 0.00 | 383.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164.43 |
F8 S1 APARTMENT | 15-NOV-13:00 | 0.00 | -2237.84 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3653.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.61 | -1830.35 |
F8 S2 APARTMENT | 16-NOV-12:00 | 0.00 | -2244.27 | 0.00 | 0.00 | 40.58 | 28.81 | 412.03 | 4011.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15.76 | -2233.38 |
F9 SW APARTMENT | 02-AUG-18:08 | 0.00 | -3267.95 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 1028.68 | 0.00 | 1188.41 | 131.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NW APARTMENT | 15-JUN-18:15 | 0.00 | -3002.43 | 0.00 | 0.00 | 140.64 | 230.46 | 547.42 | 2750.31 | 0.00 | 69.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.90 |
F9 SE APARTMENT | 02-AUG-18:15 | 0.00 | -2769.72 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 248.76 | 0.00 | 1107.48 | 493.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 02-AUG-18:15 | 0.00 | -2196.36 | 0.00 | 0.00 | 141.80 | 230.46 | 547.42 | 433.89 | 0.00 | 685.22 | 157.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 05-JUN-18:15 | 0.00 | -1708.13 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 457.86 | 0.00 | 396.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65.92 |
F9 N2 APARTMENT | 05-JUN-18:15 | 0.00 | -1692.01 | 0.00 | 0.00 | 141.81 | 230.46 | 547.42 | 458.12 | 0.00 | 395.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.70 |
F9 S1 APARTMENT | 16-NOV-12:15 | 0.00 | -2254.48 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3984.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.25 | -2178.47 |
F9 S2 APARTMENT | 16-NOV-12:15 | 0.00 | -2264.76 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3984.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.25 | -2168.08 |
T SW APARTMENT | 12-SEP-15:15 | 0.00 | -3996.53 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3525.00 | 0.00 | 48.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -197.33 |
T NW APARTMENT | 15-JUN-17:30 | 0.00 | -3657.54 | 0.00 | 0.00 | 140.75 | 194.45 | 588.62 | 2977.69 | 0.00 | 203.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -447.77 |
T SE APARTMENT | 31-AUG-10:45 | 0.00 | -3567.67 | 0.00 | 0.00 | 40.30 | 28.81 | 412.03 | 3760.73 | 0.00 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -691.45 |
T NE APARTMENT | 26-JUN-08:45 | 0.00 | -2804.47 | 0.00 | 0.00 | 40.75 | 28.81 | 394.37 | 2573.61 | 0.00 | 268.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.08 |
T N1 APARTMENT | 29-JUN-17:08 | 0.00 | -2245.36 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 501.23 | 0.00 | 648.12 | 171.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUN-17:08 | 0.00 | -2240.56 | 0.00 | 0.00 | 141.80 | 194.45 | 588.62 | 501.45 | 0.00 | 648.73 | 165.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 16-NOV-12:45 | 0.00 | -2976.23 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3799.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.84 | -1252.87 |
T S2 APARTMENT | 16-NOV-12:45 | 0.00 | -2985.50 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3799.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.84 | -1243.39 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-18:15 | 0.00 | -175434.69 | 0.00 | 0.00 | 11202.54 | 25049.15 | 43784.02 | 41209.79 | 0.00 | 57195.12 | 0.00 | 0.00 | 0.00 | 0.00 | -88.21 | -2917.72 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 21-DEC-07:55 | 2141.36 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1955.65 | 0.00 | -348.20 | -474.96 |
G NW APARTMENT | 21-DEC-07:55 | 2145.72 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1952.08 | 0.00 | -348.20 | -482.89 |
OFFICE | 21-DEC-07:50 | 2301.56 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1959.94 | 0.00 | -348.20 | -567.99 |
G NE APARTMENT | 21-DEC-18:30 | 2182.49 | 0.00 | 0.00 | 0.00 | 165.01 | 194.45 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1631.98 | 0.00 | -655.59 | -843.00 |
G N1 APARTMENT | 23-DEC-08:10 | 1332.54 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -781.68 | 0.00 | -245.35 | -811.18 |
G N2 APARTMENT | 23-DEC-08:10 | 1327.95 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -781.75 | 0.00 | -245.35 | -806.53 |
G S1 APARTMENT | 21-DEC-08:00 | 1270.44 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1195.87 | 0.00 | -210.02 | -501.99 |
G S2 APARTMENT | 21-DEC-08:00 | 1265.60 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1196.01 | 0.00 | -210.02 | -497.01 |
F2 SW APARTMENT | 21-DEC-05:00 | 2134.86 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1920.81 | 0.00 | -414.73 | -255.89 |
F2 NW APARTMENT | 22-DEC-04:00 | 2323.42 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1688.45 | 0.00 | -659.38 | -403.35 |
F2 SE APARTMENT | 21-DEC-05:00 | 2102.78 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1922.19 | 0.00 | -414.73 | -222.42 |
F2 NE APARTMENT | 22-DEC-04:00 | 2353.63 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1682.90 | 0.00 | -659.38 | -439.10 |
F2 N1 APARTMENT | 22-DEC-04:00 | 1318.13 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1029.09 | 0.00 | -397.72 | -319.08 |
F2 N2 APARTMENT | 22-DEC-04:00 | 1319.92 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1029.05 | 0.00 | -397.72 | -320.90 |
F2 S1 APARTMENT | 21-DEC-05:00 | 1154.55 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1175.51 | 0.00 | -250.15 | -185.45 |
F2 S2 APARTMENT | 21-DEC-05:00 | 1151.90 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1175.58 | 0.00 | -250.15 | -182.73 |
F3 SW APARTMENT | 19-MAR-07:53 | 2179.63 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 87.14 | 0.00 | -1508.40 | 0.00 | -1264.04 | 0.00 |
F3 NW APARTMENT | 22-DEC-04:00 | 2371.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1711.27 | 0.00 | -780.86 | -306.83 |
F3 SE APARTMENT | 19-MAR-07:53 | 2174.21 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 92.83 | 0.00 | -1508.67 | 0.00 | -1264.04 | 0.00 |
F3 NE APARTMENT | 22-DEC-04:00 | 2399.99 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1702.80 | 0.00 | -780.87 | -344.08 |
F3 N1 APARTMENT | 09-APR-13:30 | 1445.95 | 0.00 | 0.00 | 0.00 | 43.47 | 28.81 | 382.60 | 193.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1861.27 | -233.49 |
F3 N2 APARTMENT | 09-APR-13:30 | 1447.33 | 0.00 | 0.00 | 0.00 | 43.52 | 28.81 | 382.60 | 194.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1861.18 | -235.56 |
F3 S1 APARTMENT | 21-DEC-05:00 | 1104.54 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1178.94 | 0.00 | -296.26 | -85.90 |
F3 S2 APARTMENT | 21-DEC-05:00 | 1104.22 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1178.95 | 0.00 | -296.26 | -85.57 |
F4 SW APARTMENT | 19-MAR-07:53 | 2295.93 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 122.76 | 0.00 | -1510.97 | 0.00 | -1413.39 | 0.00 |
F4 NW APARTMENT | 21-DEC-23:00 | 2455.42 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1619.30 | 0.00 | -1264.60 | -265.54 |
F4 SE APARTMENT | 19-MAR-07:53 | 2295.18 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 123.55 | 0.00 | -1511.01 | 0.00 | -1413.40 | 0.00 |
F4 NE APARTMENT | 21-DEC-23:00 | 2517.17 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1634.94 | 0.00 | -1264.61 | -311.63 |
F4 N1 APARTMENT | 09-APR-13:30 | 1492.74 | 0.00 | 0.00 | 0.00 | 43.41 | 28.81 | 382.60 | 189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2056.76 | -80.22 |
F4 N2 APARTMENT | 09-APR-13:30 | 1481.37 | 0.00 | 0.00 | 0.00 | 43.46 | 28.81 | 382.60 | 190.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2056.67 | -69.61 |
F4 S1 APARTMENT | 21-DEC-05:00 | 1113.00 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.33 | 0.00 | -331.24 | -57.99 |
F4 S2 APARTMENT | 21-DEC-05:00 | 1113.25 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.33 | 0.00 | -331.24 | -58.25 |
M SW APARTMENT | 19-MAR-07:10 | 2405.23 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 156.04 | 0.00 | -1427.95 | 0.00 | -1638.99 | 0.00 |
M NW APARTMENT | 21-DEC-23:00 | 2543.39 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1629.01 | 0.00 | -1374.74 | -233.66 |
M SE APARTMENT | 19-MAR-07:10 | 2405.70 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 155.55 | 0.00 | -1427.93 | 0.00 | -1638.99 | 0.00 |
M NE APARTMENT | 21-DEC-23:00 | 2605.83 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1646.02 | 0.00 | -1374.75 | -279.07 |
M N1 APARTMENT | 09-APR-13:30 | 1544.98 | 0.00 | 0.00 | 0.00 | 43.42 | 28.81 | 382.60 | 186.88 | 0.00 | 0.00 | 35.13 | 0.00 | 0.00 | 0.00 | -2221.83 | 0.00 |
M N2 APARTMENT | 09-APR-13:30 | 1535.57 | 0.00 | 0.00 | 0.00 | 43.48 | 28.81 | 382.60 | 187.53 | 0.00 | 0.00 | 43.74 | 0.00 | 0.00 | 0.00 | -2221.73 | 0.00 |
M S1 APARTMENT | 21-DEC-05:00 | 1113.96 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1181.79 | 0.00 | -360.09 | -28.63 |
M S2 APARTMENT | 21-DEC-05:00 | 1114.32 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1181.78 | 0.00 | -360.09 | -29.01 |
F6 SW APARTMENT | 19-MAR-07:10 | 2563.84 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 117.49 | 0.00 | -1434.72 | 0.00 | -1752.28 | 0.00 |
F6 NW APARTMENT | 21-DEC-23:00 | 2679.41 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1634.95 | 0.00 | -1469.71 | -268.76 |
F6 SE APARTMENT | 19-MAR-07:10 | 2564.21 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 117.10 | 0.00 | -1434.70 | 0.00 | -1752.28 | 0.00 |
F6 NE APARTMENT | 21-DEC-23:00 | 2742.75 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1653.02 | 0.00 | -1469.72 | -314.02 |
F6 N1 APARTMENT | 09-APR-13:25 | 1956.53 | 0.00 | 0.00 | 0.00 | 43.83 | 28.81 | 382.60 | 189.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2386.37 | -214.60 |
F6 N2 APARTMENT | 09-APR-13:25 | 1980.69 | 0.00 | 0.00 | 0.00 | 43.88 | 28.81 | 382.60 | 189.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2385.40 | -240.44 |
F6 S1 APARTMENT | 19-MAR-07:53 | 1198.84 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 215.65 | 0.00 | -929.23 | 0.00 | -990.94 | 0.00 |
F6 S2 APARTMENT | 19-MAR-07:53 | 1199.00 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 215.49 | 0.00 | -929.22 | 0.00 | -990.94 | 0.00 |
F7 SW APARTMENT | 19-MAR-07:10 | 2694.92 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 92.88 | 0.00 | -1440.74 | 0.00 | -1852.73 | 0.00 |
F7 NW APARTMENT | 21-DEC-23:00 | 2783.07 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1640.51 | 0.00 | -1553.90 | -282.67 |
F7 SE APARTMENT | 19-MAR-07:10 | 2694.87 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 92.93 | 0.00 | -1440.74 | 0.00 | -1852.73 | 0.00 |
F7 NE APARTMENT | 21-DEC-23:00 | 2846.83 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1659.21 | 0.00 | -1553.91 | -327.72 |
F7 N1 APARTMENT | 09-APR-13:25 | 2379.35 | 0.00 | 0.00 | 0.00 | 44.11 | 28.81 | 382.60 | 190.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2509.99 | -515.59 |
F7 N2 APARTMENT | 09-APR-13:25 | 2400.72 | 0.00 | 0.00 | 0.00 | 44.16 | 28.81 | 382.60 | 191.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2509.12 | -538.49 |
F7 S1 APARTMENT | 09-APR-13:30 | 1436.02 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 229.30 | 0.00 | 0.00 | 389.69 | 0.00 | 0.00 | 0.00 | -2507.17 | 0.00 |
F7 S2 APARTMENT | 09-APR-13:30 | 1434.08 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 229.32 | 0.00 | 0.00 | 391.71 | 0.00 | 0.00 | 0.00 | -2507.28 | 0.00 |
F8 SW APARTMENT | 19-MAR-07:10 | 2830.62 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 52.52 | 0.00 | -1445.30 | 0.00 | -1943.52 | 0.00 |
F8 NW APARTMENT | 19-MAR-07:10 | 2896.05 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 | -1481.06 | 0.00 | -1943.52 | 0.00 |
F8 SE APARTMENT | 19-MAR-07:10 | 2830.14 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 53.01 | 0.00 | -1445.31 | 0.00 | -1943.52 | 0.00 |
F8 NE APARTMENT | 21-DEC-23:00 | 2948.34 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1664.52 | 0.00 | -1629.99 | -347.84 |
F8 N1 APARTMENT | 09-APR-13:25 | 2726.43 | 0.00 | 0.00 | 0.00 | 44.34 | 28.81 | 382.60 | 191.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2624.29 | -749.68 |
F8 N2 APARTMENT | 09-APR-13:25 | 2746.02 | 0.00 | 0.00 | 0.00 | 44.38 | 28.81 | 382.60 | 192.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2623.54 | -770.59 |
F8 S1 APARTMENT | 09-APR-13:30 | 1842.49 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 229.02 | 0.00 | 0.00 | 97.97 | 0.00 | 0.00 | 0.00 | -2621.65 | 0.00 |
F8 S2 APARTMENT | 09-APR-13:30 | 1844.38 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 229.07 | 0.00 | 0.00 | 96.08 | 0.00 | 0.00 | 0.00 | -2621.70 | 0.00 |
F9 SW APARTMENT | 19-MAR-07:10 | 3089.89 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1444.60 | 0.00 | -2026.72 | -124.24 |
F9 NW APARTMENT | 19-MAR-07:10 | 3145.41 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1481.19 | 0.00 | -2026.72 | -143.17 |
F9 SE APARTMENT | 19-MAR-07:10 | 3088.84 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1444.63 | 0.00 | -2026.72 | -123.15 |
F9 NE APARTMENT | 21-DEC-23:00 | 3152.83 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1665.75 | 0.00 | -1699.70 | -481.39 |
F9 N1 APARTMENT | 09-APR-13:25 | 2960.47 | 0.00 | 0.00 | 0.00 | 44.66 | 28.81 | 382.60 | 194.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2732.05 | -879.22 |
F9 N2 APARTMENT | 09-APR-13:25 | 2957.53 | 0.00 | 0.00 | 0.00 | 44.68 | 28.81 | 382.60 | 194.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2731.96 | -876.61 |
F9 S1 APARTMENT | 09-APR-11:00 | 1942.23 | 0.00 | 0.00 | 0.00 | 40.76 | 28.81 | 412.03 | 1938.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3204.02 | -1158.67 |
F9 S2 APARTMENT | 09-APR-11:00 | 1917.98 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 1938.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3204.08 | -1134.05 |
T SW APARTMENT | 19-MAR-07:10 | 3867.64 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1412.57 | 0.00 | -2103.62 | -857.12 |
T NW APARTMENT | 19-MAR-07:10 | 3913.04 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1448.17 | 0.00 | -2103.62 | -866.91 |
T SE APARTMENT | 19-MAR-07:10 | 3866.91 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1412.60 | 0.00 | -2103.62 | -856.35 |
T NE APARTMENT | 21-DEC-23:00 | 3933.13 | 0.00 | 0.00 | 0.00 | 189.67 | 86.42 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1632.00 | 0.00 | -1764.12 | -1231.02 |
T N1 APARTMENT | 09-APR-13:25 | 3158.13 | 0.00 | 0.00 | 0.00 | 43.89 | 28.81 | 382.60 | 186.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2845.80 | -954.26 |
T N2 APARTMENT | 09-APR-13:25 | 3152.14 | 0.00 | 0.00 | 0.00 | 43.85 | 28.81 | 382.60 | 186.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2846.55 | -946.89 |
T S1 APARTMENT | 22-DEC-04:00 | 2496.33 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1075.49 | 0.00 | -734.42 | -1114.17 |
T S2 APARTMENT | 22-DEC-04:00 | 2497.46 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1075.46 | 0.00 | -734.42 | -1115.33 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-MAR-07:10 | 159001.26 | 0.00 | 0.00 | 0.00 | 5843.75 | 10256.44 | 31331.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93677.15 | 0.00 | -109834.66 | -2920.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Sec1.1A-General InformationData | |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 124.75 |
Number of hours cooling loads not met | 390.25 |
Number of hours not met | 518.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.38 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 123.71 | 0.00 | 391.48 | 195077.61 | 0.00 | 0.00 |
Space Cooling | 405.35 | 58819.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.97 | 1376.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.98 | 1866.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 708.77 | 22475.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1202.88 | 87982.13 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3031.50 | 1594.36 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3031.50 |
Natural Gas | 0.00 | 1594.36 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4625.87 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 15.79 |
Space Cooling | 51.73 |
Fans-Interior | 90.45 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 31.41 |
Subtotal | 386.85 |
Natural Gas [MJ/m2] | |
Space Heating | 49.96 |
Service Water Heating | 153.50 |
Miscellaneous | -0.00 |
Subtotal | 203.45 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.00 |
Space Heating | 11.14 |
Space Cooling | 8.76 |
Fans-Interior | 15.32 |
Service Water Heating | 26.00 |
Receptacle Equipment | 24.45 |
Miscellaneous | 5.32 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.259745 |
G NW APARTMENT DIRECT AIR | 0.248195 |
OFFICE DIRECT AIR | 0.337712 |
G NE APARTMENT DIRECT AIR | 0.174305 |
G N1 APARTMENT DIRECT AIR | 0.125100 |
G N2 APARTMENT DIRECT AIR | 0.122965 |
G S1 APARTMENT DIRECT AIR | 0.147636 |
G S2 APARTMENT DIRECT AIR | 0.153872 |
F2 SW APARTMENT DIRECT AIR | 0.340348 |
F2 NW APARTMENT DIRECT AIR | 0.321846 |
F2 SE APARTMENT DIRECT AIR | 0.306068 |
F2 NE APARTMENT DIRECT AIR | 0.237162 |
F2 N1 APARTMENT DIRECT AIR | 0.171224 |
F2 N2 APARTMENT DIRECT AIR | 0.169420 |
F2 S1 APARTMENT DIRECT AIR | 0.200856 |
F2 S2 APARTMENT DIRECT AIR | 0.203294 |
F3 SW APARTMENT DIRECT AIR | 0.342722 |
F3 NW APARTMENT DIRECT AIR | 0.325158 |
F3 SE APARTMENT DIRECT AIR | 0.289971 |
F3 NE APARTMENT DIRECT AIR | 0.240992 |
F3 N1 APARTMENT DIRECT AIR | 0.175688 |
F3 N2 APARTMENT DIRECT AIR | 0.173889 |
F3 S1 APARTMENT DIRECT AIR | 0.205644 |
F3 S2 APARTMENT DIRECT AIR | 0.206879 |
F4 SW APARTMENT DIRECT AIR | 0.344373 |
F4 NW APARTMENT DIRECT AIR | 0.326873 |
F4 SE APARTMENT DIRECT AIR | 0.289812 |
F4 NE APARTMENT DIRECT AIR | 0.241915 |
F4 N1 APARTMENT DIRECT AIR | 0.177492 |
F4 N2 APARTMENT DIRECT AIR | 0.175689 |
F4 S1 APARTMENT DIRECT AIR | 0.207515 |
F4 S2 APARTMENT DIRECT AIR | 0.208574 |
M SW APARTMENT DIRECT AIR | 0.348419 |
M NW APARTMENT DIRECT AIR | 0.331030 |
M SE APARTMENT DIRECT AIR | 0.293661 |
M NE APARTMENT DIRECT AIR | 0.245349 |
M N1 APARTMENT DIRECT AIR | 0.181513 |
M N2 APARTMENT DIRECT AIR | 0.179708 |
M S1 APARTMENT DIRECT AIR | 0.211558 |
M S2 APARTMENT DIRECT AIR | 0.212586 |
F6 SW APARTMENT DIRECT AIR | 0.344594 |
F6 NW APARTMENT DIRECT AIR | 0.327097 |
F6 SE APARTMENT DIRECT AIR | 0.289950 |
F6 NE APARTMENT DIRECT AIR | 0.240975 |
F6 N1 APARTMENT DIRECT AIR | 0.177857 |
F6 N2 APARTMENT DIRECT AIR | 0.176059 |
F6 S1 APARTMENT DIRECT AIR | 0.207915 |
F6 S2 APARTMENT DIRECT AIR | 0.208935 |
F7 SW APARTMENT DIRECT AIR | 0.343548 |
F7 NW APARTMENT DIRECT AIR | 0.326070 |
F7 SE APARTMENT DIRECT AIR | 0.288991 |
F7 NE APARTMENT DIRECT AIR | 0.239504 |
F7 N1 APARTMENT DIRECT AIR | 0.176946 |
F7 N2 APARTMENT DIRECT AIR | 0.175151 |
F7 S1 APARTMENT DIRECT AIR | 0.206962 |
F7 S2 APARTMENT DIRECT AIR | 0.207978 |
F8 SW APARTMENT DIRECT AIR | 0.344086 |
F8 NW APARTMENT DIRECT AIR | 0.326641 |
F8 SE APARTMENT DIRECT AIR | 0.289492 |
F8 NE APARTMENT DIRECT AIR | 0.239560 |
F8 N1 APARTMENT DIRECT AIR | 0.177630 |
F8 N2 APARTMENT DIRECT AIR | 0.175841 |
F8 S1 APARTMENT DIRECT AIR | 0.207484 |
F8 S2 APARTMENT DIRECT AIR | 0.208499 |
F9 SW APARTMENT DIRECT AIR | 0.356089 |
F9 NW APARTMENT DIRECT AIR | 0.338404 |
F9 SE APARTMENT DIRECT AIR | 0.297451 |
F9 NE APARTMENT DIRECT AIR | 0.242791 |
F9 N1 APARTMENT DIRECT AIR | 0.187895 |
F9 N2 APARTMENT DIRECT AIR | 0.186074 |
F9 S1 APARTMENT DIRECT AIR | 0.214334 |
F9 S2 APARTMENT DIRECT AIR | 0.215473 |
T SW APARTMENT DIRECT AIR | 0.442383 |
T NW APARTMENT DIRECT AIR | 0.413882 |
T SE APARTMENT DIRECT AIR | 0.386035 |
T NE APARTMENT DIRECT AIR | 0.308506 |
T N1 APARTMENT DIRECT AIR | 0.241054 |
T N2 APARTMENT DIRECT AIR | 0.240585 |
T S1 APARTMENT DIRECT AIR | 0.314364 |
T S2 APARTMENT DIRECT AIR | 0.315251 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.259745 |
AIRLOOP G NW MAIN BRANCH | 0.248195 |
AIRLOOP OFFICE MAIN BRANCH | 0.337712 |
AIRLOOP G NE MAIN BRANCH | 0.174305 |
AIRLOOP G N1 MAIN BRANCH | 0.125100 |
AIRLOOP G N2 MAIN BRANCH | 0.122965 |
AIRLOOP G S1 MAIN BRANCH | 0.147636 |
AIRLOOP G S2 MAIN BRANCH | 0.153872 |
AIRLOOP F2 SW MAIN BRANCH | 0.340348 |
AIRLOOP F2 NW MAIN BRANCH | 0.321846 |
AIRLOOP F2 SE MAIN BRANCH | 0.306068 |
AIRLOOP F2 NE MAIN BRANCH | 0.237162 |
AIRLOOP F2 N1 MAIN BRANCH | 0.171224 |
AIRLOOP F2 N2 MAIN BRANCH | 0.169420 |
AIRLOOP F2 S1 MAIN BRANCH | 0.200856 |
AIRLOOP F2 S2 MAIN BRANCH | 0.203294 |
AIRLOOP F3 SW MAIN BRANCH | 0.342722 |
AIRLOOP F3 NW MAIN BRANCH | 0.325158 |
AIRLOOP F3 SE MAIN BRANCH | 0.289971 |
AIRLOOP F3 NE MAIN BRANCH | 0.240992 |
AIRLOOP F3 N1 MAIN BRANCH | 0.175688 |
AIRLOOP F3 N2 MAIN BRANCH | 0.173889 |
AIRLOOP F3 S1 MAIN BRANCH | 0.205644 |
AIRLOOP F3 S2 MAIN BRANCH | 0.206879 |
AIRLOOP F4 SW MAIN BRANCH | 0.344373 |
AIRLOOP F4 NW MAIN BRANCH | 0.326873 |
AIRLOOP F4 SE MAIN BRANCH | 0.289812 |
AIRLOOP F4 NE MAIN BRANCH | 0.241915 |
AIRLOOP F4 N1 MAIN BRANCH | 0.177492 |
AIRLOOP F4 N2 MAIN BRANCH | 0.175689 |
AIRLOOP F4 S1 MAIN BRANCH | 0.207515 |
AIRLOOP F4 S2 MAIN BRANCH | 0.208574 |
AIRLOOP M SW MAIN BRANCH | 0.348419 |
AIRLOOP M NW MAIN BRANCH | 0.331030 |
AIRLOOP M SE MAIN BRANCH | 0.293661 |
AIRLOOP M NE MAIN BRANCH | 0.245349 |
AIRLOOP M N1 MAIN BRANCH | 0.181513 |
AIRLOOP M N2 MAIN BRANCH | 0.179708 |
AIRLOOP M S1 MAIN BRANCH | 0.211558 |
AIRLOOP M S2 MAIN BRANCH | 0.212586 |
AIRLOOP F6 SW MAIN BRANCH | 0.344594 |
AIRLOOP F6 NW MAIN BRANCH | 0.327097 |
AIRLOOP F6 SE MAIN BRANCH | 0.289950 |
AIRLOOP F6 NE MAIN BRANCH | 0.240975 |
AIRLOOP F6 N1 MAIN BRANCH | 0.177857 |
AIRLOOP F6 N2 MAIN BRANCH | 0.176059 |
AIRLOOP F6 S1 MAIN BRANCH | 0.207915 |
AIRLOOP F6 S2 MAIN BRANCH | 0.208935 |
AIRLOOP F7 SW MAIN BRANCH | 0.343548 |
AIRLOOP F7 NW MAIN BRANCH | 0.326070 |
AIRLOOP F7 SE MAIN BRANCH | 0.288991 |
AIRLOOP F7 NE MAIN BRANCH | 0.239504 |
AIRLOOP F7 N1 MAIN BRANCH | 0.176946 |
AIRLOOP F7 N2 MAIN BRANCH | 0.175151 |
AIRLOOP F7 S1 MAIN BRANCH | 0.206962 |
AIRLOOP F7 S2 MAIN BRANCH | 0.207978 |
AIRLOOP F8 SW MAIN BRANCH | 0.344086 |
AIRLOOP F8 NW MAIN BRANCH | 0.326641 |
AIRLOOP F8 SE MAIN BRANCH | 0.289492 |
AIRLOOP F8 NE MAIN BRANCH | 0.239560 |
AIRLOOP F8 N1 MAIN BRANCH | 0.177630 |
AIRLOOP F8 N2 MAIN BRANCH | 0.175841 |
AIRLOOP F8 S1 MAIN BRANCH | 0.207484 |
AIRLOOP F8 S2 MAIN BRANCH | 0.208499 |
AIRLOOP F9 SW MAIN BRANCH | 0.356089 |
AIRLOOP F9 NW MAIN BRANCH | 0.338404 |
AIRLOOP F9 SE MAIN BRANCH | 0.297451 |
AIRLOOP F9 NE MAIN BRANCH | 0.242791 |
AIRLOOP F9 N1 MAIN BRANCH | 0.187895 |
AIRLOOP F9 N2 MAIN BRANCH | 0.186074 |
AIRLOOP F9 S1 MAIN BRANCH | 0.214334 |
AIRLOOP F9 S2 MAIN BRANCH | 0.215473 |
AIRLOOP T SW MAIN BRANCH | 0.442383 |
AIRLOOP T NW MAIN BRANCH | 0.413882 |
AIRLOOP T SE MAIN BRANCH | 0.386035 |
AIRLOOP T NE MAIN BRANCH | 0.308506 |
AIRLOOP T N1 MAIN BRANCH | 0.241054 |
AIRLOOP T N2 MAIN BRANCH | 0.240585 |
AIRLOOP T S1 MAIN BRANCH | 0.314364 |
AIRLOOP T S2 MAIN BRANCH | 0.315251 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.259745 |
AIRLOOP G NW | 0.248195 |
AIRLOOP OFFICE | 0.337712 |
AIRLOOP G NE | 0.174305 |
AIRLOOP G N1 | 0.125100 |
AIRLOOP G N2 | 0.122965 |
AIRLOOP G S1 | 0.147636 |
AIRLOOP G S2 | 0.153872 |
AIRLOOP F2 SW | 0.340348 |
AIRLOOP F2 NW | 0.321846 |
AIRLOOP F2 SE | 0.306068 |
AIRLOOP F2 NE | 0.237162 |
AIRLOOP F2 N1 | 0.171224 |
AIRLOOP F2 N2 | 0.169420 |
AIRLOOP F2 S1 | 0.200856 |
AIRLOOP F2 S2 | 0.203294 |
AIRLOOP F3 SW | 0.342722 |
AIRLOOP F3 NW | 0.325158 |
AIRLOOP F3 SE | 0.289971 |
AIRLOOP F3 NE | 0.240992 |
AIRLOOP F3 N1 | 0.175688 |
AIRLOOP F3 N2 | 0.173889 |
AIRLOOP F3 S1 | 0.205644 |
AIRLOOP F3 S2 | 0.206879 |
AIRLOOP F4 SW | 0.344373 |
AIRLOOP F4 NW | 0.326873 |
AIRLOOP F4 SE | 0.289812 |
AIRLOOP F4 NE | 0.241915 |
AIRLOOP F4 N1 | 0.177492 |
AIRLOOP F4 N2 | 0.175689 |
AIRLOOP F4 S1 | 0.207515 |
AIRLOOP F4 S2 | 0.208574 |
AIRLOOP M SW | 0.348419 |
AIRLOOP M NW | 0.331030 |
AIRLOOP M SE | 0.293661 |
AIRLOOP M NE | 0.245349 |
AIRLOOP M N1 | 0.181513 |
AIRLOOP M N2 | 0.179708 |
AIRLOOP M S1 | 0.211558 |
AIRLOOP M S2 | 0.212586 |
AIRLOOP F6 SW | 0.344594 |
AIRLOOP F6 NW | 0.327097 |
AIRLOOP F6 SE | 0.289950 |
AIRLOOP F6 NE | 0.240975 |
AIRLOOP F6 N1 | 0.177857 |
AIRLOOP F6 N2 | 0.176059 |
AIRLOOP F6 S1 | 0.207915 |
AIRLOOP F6 S2 | 0.208935 |
AIRLOOP F7 SW | 0.343548 |
AIRLOOP F7 NW | 0.326070 |
AIRLOOP F7 SE | 0.288991 |
AIRLOOP F7 NE | 0.239504 |
AIRLOOP F7 N1 | 0.176946 |
AIRLOOP F7 N2 | 0.175151 |
AIRLOOP F7 S1 | 0.206962 |
AIRLOOP F7 S2 | 0.207978 |
AIRLOOP F8 SW | 0.344086 |
AIRLOOP F8 NW | 0.326641 |
AIRLOOP F8 SE | 0.289492 |
AIRLOOP F8 NE | 0.239560 |
AIRLOOP F8 N1 | 0.177630 |
AIRLOOP F8 N2 | 0.175841 |
AIRLOOP F8 S1 | 0.207484 |
AIRLOOP F8 S2 | 0.208499 |
AIRLOOP F9 SW | 0.356089 |
AIRLOOP F9 NW | 0.338404 |
AIRLOOP F9 SE | 0.297451 |
AIRLOOP F9 NE | 0.242791 |
AIRLOOP F9 N1 | 0.187895 |
AIRLOOP F9 N2 | 0.186074 |
AIRLOOP F9 S1 | 0.214334 |
AIRLOOP F9 S2 | 0.215473 |
AIRLOOP T SW | 0.442383 |
AIRLOOP T NW | 0.413882 |
AIRLOOP T SE | 0.386035 |
AIRLOOP T NE | 0.308506 |
AIRLOOP T N1 | 0.241054 |
AIRLOOP T N2 | 0.240585 |
AIRLOOP T S1 | 0.314364 |
AIRLOOP T S2 | 0.315251 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.259745 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.248195 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.337712 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.174305 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.125100 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.122965 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.147636 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.153872 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.340348 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.321846 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.306068 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.237162 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.171224 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.169420 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.200856 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.203294 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.342722 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.325158 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.289971 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.240992 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.175688 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.173889 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.205644 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.206879 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.344373 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.326873 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.289812 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.241915 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.177492 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.175689 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.207515 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.208574 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.348419 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.331030 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.293661 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.245349 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.181513 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.179708 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.211558 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.212586 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.344594 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.327097 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.289950 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.240975 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.177857 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.176059 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.207915 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.208935 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.343548 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.326070 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.288991 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.239504 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.176946 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.175151 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.206962 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.207978 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.344086 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.326641 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.289492 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.239560 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.177630 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.175841 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.207484 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.208499 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.356089 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.338404 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.297451 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.242791 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.187895 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.186074 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.214334 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.215473 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.442383 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.413882 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.386035 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.308506 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.241054 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.240585 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.314364 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.315251 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.259745 | 3140.46 | 2013.48 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.248195 | 2982.23 | 1915.92 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.337712 | 4135.24 | 2650.50 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.174305 | 2027.42 | 1332.72 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.125100 | 1470.94 | 968.40 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.122965 | 1444.78 | 952.15 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.147636 | 1851.76 | 1186.33 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.153872 | 1922.53 | 1232.04 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.340348 | 4095.57 | 2619.00 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.321846 | 3864.28 | 2475.16 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.306068 | 3729.89 | 2382.43 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.237162 | 2775.38 | 1810.67 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.171224 | 2024.27 | 1317.46 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.169420 | 2002.26 | 1303.75 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.200856 | 2485.33 | 1589.49 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.203294 | 2514.85 | 1608.02 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.342722 | 4115.38 | 2637.89 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.325158 | 3893.13 | 2498.43 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.289971 | 3524.24 | 2258.52 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.240992 | 2810.50 | 1837.88 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.175688 | 2072.15 | 1350.31 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.173889 | 2050.22 | 1336.64 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.205644 | 2536.83 | 1624.82 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.206879 | 2551.79 | 1634.20 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.344373 | 4126.84 | 2649.01 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.326873 | 3905.42 | 2510.04 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.289812 | 3514.11 | 2255.96 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.241915 | 2813.34 | 1843.53 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.177492 | 2089.20 | 1363.21 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.175689 | 2067.24 | 1349.52 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.207515 | 2554.62 | 1638.24 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.208574 | 2567.44 | 1646.28 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.348419 | 4168.83 | 2678.54 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.331030 | 3948.84 | 2540.42 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.293661 | 3553.90 | 2284.05 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.245349 | 2847.97 | 1868.44 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.181513 | 2134.20 | 1393.11 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.179708 | 2112.21 | 1379.40 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.211558 | 2599.54 | 1668.30 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.212586 | 2611.99 | 1676.11 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.344594 | 4116.59 | 2648.57 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.327097 | 3895.27 | 2509.63 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.289950 | 3503.35 | 2254.97 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.240975 | 2789.52 | 1834.40 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.177857 | 2086.16 | 1364.78 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.176059 | 2064.26 | 1351.12 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.207915 | 2552.10 | 1640.06 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.208935 | 2564.46 | 1647.82 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.343548 | 4098.70 | 2639.78 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.326070 | 3877.62 | 2500.99 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.288991 | 3486.73 | 2246.87 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.239504 | 2766.74 | 1822.45 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.176946 | 2072.01 | 1357.36 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.175151 | 2050.17 | 1343.73 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.206962 | 2537.60 | 1632.34 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.207978 | 2549.90 | 1640.06 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.344086 | 4100.51 | 2643.09 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.326641 | 3879.85 | 2504.55 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.289492 | 3488.27 | 2249.94 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.239560 | 2762.89 | 1822.14 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.177630 | 2077.63 | 1362.12 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.175841 | 2055.87 | 1348.54 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.207484 | 2541.24 | 1635.87 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.208499 | 2553.52 | 1643.58 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.356089 | 4241.33 | 2733.36 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.338404 | 4017.93 | 2593.03 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.297451 | 3580.15 | 2309.60 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.242791 | 2797.59 | 1845.92 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.187895 | 2200.14 | 1439.66 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.186074 | 2177.99 | 1425.84 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.214334 | 2621.46 | 1687.47 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.215473 | 2635.24 | 1696.12 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.442383 | 5319.86 | 3404.52 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.413882 | 4949.54 | 3177.19 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.386035 | 4646.23 | 2980.52 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.308506 | 3614.97 | 2354.71 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.241054 | 2946.98 | 1891.87 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.240585 | 2941.37 | 1888.32 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.314364 | 3828.40 | 2446.20 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.315251 | 3839.15 | 2452.93 | 0.000084 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.259745 | 0.259745 | 0.259745 | 0.259745 | 3140.46 | 3140.46 | 3345.45 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.248195 | 0.248195 | 0.248195 | 0.248195 | 2982.23 | 2982.23 | 3358.06 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.337712 | 0.337712 | 0.337712 | 0.337712 | 4135.24 | 4135.24 | 4259.61 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.174305 | 0.174305 | 0.174305 | 0.174305 | 2027.42 | 2027.42 | 3358.06 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.125100 | 0.125100 | 0.125100 | 0.125100 | 1470.94 | 1470.94 | 2544.99 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.122965 | 0.122965 | 0.122965 | 0.122965 | 1444.78 | 1444.78 | 2544.99 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.147636 | 0.147636 | 0.147636 | 0.147636 | 1851.76 | 1851.76 | 2529.27 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.153872 | 0.153872 | 0.153872 | 0.153872 | 1922.53 | 1922.53 | 2537.77 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.340348 | 0.340348 | 0.340348 | 0.340348 | 4095.57 | 4095.57 | 3258.26 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.321846 | 0.321846 | 0.321846 | 0.321846 | 3864.28 | 3864.28 | 3264.59 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.306068 | 0.306068 | 0.306068 | 0.306068 | 3729.89 | 3729.89 | 3283.15 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.237162 | 0.237162 | 0.237162 | 0.237162 | 2775.38 | 2775.38 | 3264.59 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.171224 | 0.171224 | 0.171224 | 0.171224 | 2024.27 | 2024.27 | 2279.84 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.169420 | 0.169420 | 0.169420 | 0.169420 | 2002.26 | 2002.26 | 2279.84 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.200856 | 0.200856 | 0.200856 | 0.200856 | 2485.33 | 2485.33 | 2276.35 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.203294 | 0.203294 | 0.203294 | 0.203294 | 2514.85 | 2514.85 | 2277.92 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.342722 | 0.342722 | 0.342722 | 0.342722 | 4115.38 | 4115.38 | 3233.47 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.325158 | 0.325158 | 0.325158 | 0.325158 | 3893.13 | 3893.13 | 3239.68 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.289971 | 0.289971 | 0.289971 | 0.289971 | 3524.24 | 3524.24 | 3236.09 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.240992 | 0.240992 | 0.240992 | 0.240992 | 2810.50 | 2810.50 | 3239.68 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.175688 | 0.175688 | 0.175688 | 0.175688 | 2072.15 | 2072.15 | 2226.90 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.173889 | 0.173889 | 0.173889 | 0.173889 | 2050.22 | 2050.22 | 2226.90 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.205644 | 0.205644 | 0.205644 | 0.205644 | 2536.83 | 2536.83 | 2221.50 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.206879 | 0.206879 | 0.206879 | 0.206879 | 2551.79 | 2551.79 | 2221.74 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.344373 | 0.344373 | 0.344373 | 0.344373 | 4126.84 | 4126.84 | 3266.39 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.326873 | 0.326873 | 0.326873 | 0.326873 | 3905.42 | 3905.42 | 3271.61 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.289812 | 0.289812 | 0.289812 | 0.289812 | 3514.11 | 3514.11 | 3266.65 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.241915 | 0.241915 | 0.241915 | 0.241915 | 2813.34 | 2813.34 | 3271.61 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.177492 | 0.177492 | 0.177492 | 0.177492 | 2089.20 | 2089.20 | 2234.94 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.175689 | 0.175689 | 0.175689 | 0.175689 | 2067.24 | 2067.24 | 2234.94 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.207515 | 0.207515 | 0.207515 | 0.207515 | 2554.62 | 2554.62 | 2230.30 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.208574 | 0.208574 | 0.208574 | 0.208574 | 2567.44 | 2567.44 | 2230.34 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.348419 | 0.348419 | 0.348419 | 0.348419 | 4168.83 | 4168.83 | 3277.12 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.331030 | 0.331030 | 0.331030 | 0.331030 | 3948.84 | 3948.84 | 3279.93 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.293661 | 0.293661 | 0.293661 | 0.293661 | 3553.90 | 3553.90 | 3277.14 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.245349 | 0.245349 | 0.245349 | 0.245349 | 2847.97 | 2847.97 | 3279.93 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.181513 | 0.181513 | 0.181513 | 0.181513 | 2134.20 | 2134.20 | 2226.52 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.179708 | 0.179708 | 0.179708 | 0.179708 | 2112.21 | 2112.21 | 2226.52 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.211558 | 0.211558 | 0.211558 | 0.211558 | 2599.54 | 2599.54 | 2224.31 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.212586 | 0.212586 | 0.212586 | 0.212586 | 2611.99 | 2611.99 | 2224.32 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.344594 | 0.344594 | 0.344594 | 0.344594 | 4116.59 | 4116.59 | 3358.10 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.327097 | 0.327097 | 0.327097 | 0.327097 | 3895.27 | 3895.27 | 3360.54 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.289950 | 0.289950 | 0.289950 | 0.289950 | 3503.35 | 3503.35 | 3358.10 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.240975 | 0.240975 | 0.240975 | 0.240975 | 2789.52 | 2789.52 | 3360.54 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.177857 | 0.177857 | 0.177857 | 0.177857 | 2086.16 | 2086.16 | 2287.91 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.176059 | 0.176059 | 0.176059 | 0.176059 | 2064.26 | 2064.26 | 2287.91 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.207915 | 0.207915 | 0.207915 | 0.207915 | 2552.10 | 2552.10 | 2286.00 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.208935 | 0.208935 | 0.208935 | 0.208935 | 2564.46 | 2564.46 | 2286.00 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.343548 | 0.343548 | 0.343548 | 0.343548 | 4098.70 | 4098.70 | 3409.62 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.326070 | 0.326070 | 0.326070 | 0.326070 | 3877.62 | 3877.62 | 3410.59 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.288991 | 0.288991 | 0.288991 | 0.288991 | 3486.73 | 3486.73 | 3409.62 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.239504 | 0.239504 | 0.239504 | 0.239504 | 2766.74 | 2766.74 | 3410.59 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.176946 | 0.176946 | 0.176946 | 0.176946 | 2072.01 | 2072.01 | 2323.83 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.175151 | 0.175151 | 0.175151 | 0.175151 | 2050.17 | 2050.17 | 2323.83 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.206962 | 0.206962 | 0.206962 | 0.206962 | 2537.60 | 2537.60 | 2323.37 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.207978 | 0.207978 | 0.207978 | 0.207978 | 2549.90 | 2549.90 | 2323.37 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.344086 | 0.344086 | 0.344086 | 0.344086 | 4100.51 | 4100.51 | 3468.20 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.326641 | 0.326641 | 0.326641 | 0.326641 | 3879.85 | 3879.85 | 3467.56 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.289492 | 0.289492 | 0.289492 | 0.289492 | 3488.27 | 3488.27 | 3468.20 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.239560 | 0.239560 | 0.239560 | 0.239560 | 2762.89 | 2762.89 | 3467.56 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.177630 | 0.177630 | 0.177630 | 0.177630 | 2077.63 | 2077.63 | 2368.50 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.175841 | 0.175841 | 0.175841 | 0.175841 | 2055.87 | 2055.87 | 2368.50 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.207484 | 0.207484 | 0.207484 | 0.207484 | 2541.24 | 2541.24 | 2369.67 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.208499 | 0.208499 | 0.208499 | 0.208499 | 2553.52 | 2553.52 | 2369.67 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.356089 | 0.356089 | 0.356089 | 0.356089 | 4241.33 | 4241.33 | 3681.49 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.338404 | 0.338404 | 0.338404 | 0.338404 | 4017.93 | 4017.93 | 3676.26 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.297451 | 0.297451 | 0.297451 | 0.297451 | 3580.15 | 3580.15 | 3681.49 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.242791 | 0.242791 | 0.242791 | 0.242791 | 2797.59 | 2797.59 | 3676.26 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.187895 | 0.187895 | 0.187895 | 0.187895 | 2200.14 | 2200.14 | 2556.02 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.186074 | 0.186074 | 0.186074 | 0.186074 | 2177.99 | 2177.99 | 2556.02 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.214334 | 0.214334 | 0.214334 | 0.214334 | 2621.46 | 2621.46 | 2561.36 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.215473 | 0.215473 | 0.215473 | 0.215473 | 2635.24 | 2635.24 | 2561.36 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.442383 | 0.442383 | 0.442383 | 0.442383 | 5319.86 | 5319.86 | 4489.34 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.413882 | 0.413882 | 0.413882 | 0.413882 | 4949.54 | 4949.54 | 4491.71 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.386035 | 0.386035 | 0.386035 | 0.386035 | 4646.23 | 4646.23 | 4489.34 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.308506 | 0.308506 | 0.308506 | 0.308506 | 3614.97 | 3614.97 | 4491.71 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.241054 | 0.241054 | 0.241054 | 0.241054 | 2946.98 | 2946.98 | 3428.98 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.240585 | 0.240585 | 0.240585 | 0.240585 | 2941.37 | 2941.37 | 3428.98 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.314364 | 0.314364 | 0.314364 | 0.314364 | 3828.40 | 3828.40 | 3423.89 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.315251 | 0.315251 | 0.315251 | 0.315251 | 3839.15 | 3839.15 | 3423.89 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.259745 |
AIRLOOP G NW SUPPLY FAN | 0.248195 |
AIRLOOP OFFICE SUPPLY FAN | 0.337712 |
AIRLOOP G NE SUPPLY FAN | 0.174305 |
AIRLOOP G N1 SUPPLY FAN | 0.125100 |
AIRLOOP G N2 SUPPLY FAN | 0.122965 |
AIRLOOP G S1 SUPPLY FAN | 0.147636 |
AIRLOOP G S2 SUPPLY FAN | 0.153872 |
AIRLOOP F2 SW SUPPLY FAN | 0.340348 |
AIRLOOP F2 NW SUPPLY FAN | 0.321846 |
AIRLOOP F2 SE SUPPLY FAN | 0.306068 |
AIRLOOP F2 NE SUPPLY FAN | 0.237162 |
AIRLOOP F2 N1 SUPPLY FAN | 0.171224 |
AIRLOOP F2 N2 SUPPLY FAN | 0.169420 |
AIRLOOP F2 S1 SUPPLY FAN | 0.200856 |
AIRLOOP F2 S2 SUPPLY FAN | 0.203294 |
AIRLOOP F3 SW SUPPLY FAN | 0.342722 |
AIRLOOP F3 NW SUPPLY FAN | 0.325158 |
AIRLOOP F3 SE SUPPLY FAN | 0.289971 |
AIRLOOP F3 NE SUPPLY FAN | 0.240992 |
AIRLOOP F3 N1 SUPPLY FAN | 0.175688 |
AIRLOOP F3 N2 SUPPLY FAN | 0.173889 |
AIRLOOP F3 S1 SUPPLY FAN | 0.205644 |
AIRLOOP F3 S2 SUPPLY FAN | 0.206879 |
AIRLOOP F4 SW SUPPLY FAN | 0.344373 |
AIRLOOP F4 NW SUPPLY FAN | 0.326873 |
AIRLOOP F4 SE SUPPLY FAN | 0.289812 |
AIRLOOP F4 NE SUPPLY FAN | 0.241915 |
AIRLOOP F4 N1 SUPPLY FAN | 0.177492 |
AIRLOOP F4 N2 SUPPLY FAN | 0.175689 |
AIRLOOP F4 S1 SUPPLY FAN | 0.207515 |
AIRLOOP F4 S2 SUPPLY FAN | 0.208574 |
AIRLOOP M SW SUPPLY FAN | 0.348419 |
AIRLOOP M NW SUPPLY FAN | 0.331030 |
AIRLOOP M SE SUPPLY FAN | 0.293661 |
AIRLOOP M NE SUPPLY FAN | 0.245349 |
AIRLOOP M N1 SUPPLY FAN | 0.181513 |
AIRLOOP M N2 SUPPLY FAN | 0.179708 |
AIRLOOP M S1 SUPPLY FAN | 0.211558 |
AIRLOOP M S2 SUPPLY FAN | 0.212586 |
AIRLOOP F6 SW SUPPLY FAN | 0.344594 |
AIRLOOP F6 NW SUPPLY FAN | 0.327097 |
AIRLOOP F6 SE SUPPLY FAN | 0.289950 |
AIRLOOP F6 NE SUPPLY FAN | 0.240975 |
AIRLOOP F6 N1 SUPPLY FAN | 0.177857 |
AIRLOOP F6 N2 SUPPLY FAN | 0.176059 |
AIRLOOP F6 S1 SUPPLY FAN | 0.207915 |
AIRLOOP F6 S2 SUPPLY FAN | 0.208935 |
AIRLOOP F7 SW SUPPLY FAN | 0.343548 |
AIRLOOP F7 NW SUPPLY FAN | 0.326070 |
AIRLOOP F7 SE SUPPLY FAN | 0.288991 |
AIRLOOP F7 NE SUPPLY FAN | 0.239504 |
AIRLOOP F7 N1 SUPPLY FAN | 0.176946 |
AIRLOOP F7 N2 SUPPLY FAN | 0.175151 |
AIRLOOP F7 S1 SUPPLY FAN | 0.206962 |
AIRLOOP F7 S2 SUPPLY FAN | 0.207978 |
AIRLOOP F8 SW SUPPLY FAN | 0.344086 |
AIRLOOP F8 NW SUPPLY FAN | 0.326641 |
AIRLOOP F8 SE SUPPLY FAN | 0.289492 |
AIRLOOP F8 NE SUPPLY FAN | 0.239560 |
AIRLOOP F8 N1 SUPPLY FAN | 0.177630 |
AIRLOOP F8 N2 SUPPLY FAN | 0.175841 |
AIRLOOP F8 S1 SUPPLY FAN | 0.207484 |
AIRLOOP F8 S2 SUPPLY FAN | 0.208499 |
AIRLOOP F9 SW SUPPLY FAN | 0.356089 |
AIRLOOP F9 NW SUPPLY FAN | 0.338404 |
AIRLOOP F9 SE SUPPLY FAN | 0.297451 |
AIRLOOP F9 NE SUPPLY FAN | 0.242791 |
AIRLOOP F9 N1 SUPPLY FAN | 0.187895 |
AIRLOOP F9 N2 SUPPLY FAN | 0.186074 |
AIRLOOP F9 S1 SUPPLY FAN | 0.214334 |
AIRLOOP F9 S2 SUPPLY FAN | 0.215473 |
AIRLOOP T SW SUPPLY FAN | 0.442383 |
AIRLOOP T NW SUPPLY FAN | 0.413882 |
AIRLOOP T SE SUPPLY FAN | 0.386035 |
AIRLOOP T NE SUPPLY FAN | 0.308506 |
AIRLOOP T N1 SUPPLY FAN | 0.241054 |
AIRLOOP T N2 SUPPLY FAN | 0.240585 |
AIRLOOP T S1 SUPPLY FAN | 0.314364 |
AIRLOOP T S2 SUPPLY FAN | 0.315251 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.259745 | 3140.46 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.248195 | 2982.23 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.337712 | 4135.24 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.174305 | 2027.42 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.125100 | 1470.94 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.122965 | 1444.78 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.147636 | 1851.76 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.153872 | 1922.53 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.340348 | 4095.57 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.321846 | 3864.28 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.306068 | 3729.89 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.237162 | 2775.38 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.171224 | 2024.27 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.169420 | 2002.26 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.200856 | 2485.33 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.203294 | 2514.85 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.342722 | 4115.38 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.325158 | 3893.13 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.289971 | 3524.24 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.240992 | 2810.50 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.175688 | 2072.15 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.173889 | 2050.22 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.205644 | 2536.83 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.206879 | 2551.79 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.344373 | 4126.84 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.326873 | 3905.42 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.289812 | 3514.11 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.241915 | 2813.34 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.177492 | 2089.20 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.175689 | 2067.24 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.207515 | 2554.62 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.208574 | 2567.44 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.348419 | 4168.83 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.331030 | 3948.84 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.293661 | 3553.90 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.245349 | 2847.97 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.181513 | 2134.20 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.179708 | 2112.21 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.211558 | 2599.54 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.212586 | 2611.99 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.344594 | 4116.59 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.327097 | 3895.27 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.289950 | 3503.35 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.240975 | 2789.52 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.177857 | 2086.16 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.176059 | 2064.26 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.207915 | 2552.10 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.208935 | 2564.46 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.343548 | 4098.70 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.326070 | 3877.62 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.288991 | 3486.73 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.239504 | 2766.74 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.176946 | 2072.01 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.175151 | 2050.17 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.206962 | 2537.60 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.207978 | 2549.90 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.344086 | 4100.51 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.326641 | 3879.85 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.289492 | 3488.27 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.239560 | 2762.89 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.177630 | 2077.63 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.175841 | 2055.87 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.207484 | 2541.24 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.208499 | 2553.52 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.356089 | 4241.33 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.338404 | 4017.93 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.297451 | 3580.15 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.242791 | 2797.59 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.187895 | 2200.14 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.186074 | 2177.99 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.214334 | 2621.46 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.215473 | 2635.24 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.442383 | 5319.86 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.413882 | 4949.54 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.386035 | 4646.23 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.308506 | 3614.97 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.241054 | 2946.98 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.240585 | 2941.37 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.314364 | 3828.40 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.315251 | 3839.15 | 0.000084 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 3345.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 3358.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 4259.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 3358.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2544.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2544.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2529.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2537.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 3258.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 3264.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 3283.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 3264.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 2279.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 2279.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 2276.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 2277.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 3233.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 3239.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 3236.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 3239.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 2226.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 2226.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 2221.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 2221.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 3266.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 3271.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 3266.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 3271.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 2234.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 2234.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 2230.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 2230.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 3277.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 3279.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 3277.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 3279.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 2226.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 2226.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 2224.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 2224.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 3358.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 3360.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 3358.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 3360.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 2287.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 2287.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 2286.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 2286.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 3409.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 3410.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 3409.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 3410.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 2323.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 2323.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 2323.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 2323.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 3468.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 3467.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 3468.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 3467.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2368.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2368.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2369.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2369.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 3681.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 3676.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 3681.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 3676.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2556.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2556.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2561.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2561.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 4489.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 4491.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 4489.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 4491.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 3428.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 3428.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 3423.89 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 3423.89 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005253 | 5.91 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005253 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005253 | 2535.80 | 8.22 | 6379.03 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005253 | 1339.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 0.85 |
February | 22.51 | -0.2 |
March | 22.67 | 4.82 |
April | 22.49 | 6.08 |
May | 23.48 | 13.74 |
June | 24.33 | 22.16 |
July | 24.34 | 22.71 |
August | 24.35 | 21.74 |
September | 24.25 | 18.54 |
October | 23.13 | 7.12 |
November | 22.77 | 3.03 |
December | 22.32 | -1.0 |
Annual Sum or Average | 23.27 | 10.02 |
Minimum of Months | 22.32 | -1.0 |
Maximum of Months | 24.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 0.85 |
February | 21.80 | -0.2 |
March | 22.15 | 4.82 |
April | 22.17 | 6.08 |
May | 23.36 | 13.74 |
June | 24.34 | 22.16 |
July | 24.35 | 22.71 |
August | 24.32 | 21.74 |
September | 24.14 | 18.54 |
October | 22.53 | 7.12 |
November | 21.95 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 22.90 | 10.02 |
Minimum of Months | 21.77 | -1.0 |
Maximum of Months | 24.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 0.85 |
February | 22.49 | -0.2 |
March | 22.72 | 4.82 |
April | 22.62 | 6.08 |
May | 23.56 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.42 | 21.74 |
September | 24.28 | 18.54 |
October | 23.03 | 7.12 |
November | 22.65 | 3.03 |
December | 22.35 | -1.0 |
Annual Sum or Average | 23.29 | 10.02 |
Minimum of Months | 22.35 | -1.0 |
Maximum of Months | 24.42 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 0.85 |
February | 21.77 | -0.2 |
March | 22.09 | 4.82 |
April | 22.13 | 6.08 |
May | 23.25 | 13.74 |
June | 24.36 | 22.16 |
July | 24.38 | 22.71 |
August | 24.34 | 21.74 |
September | 24.12 | 18.54 |
October | 22.40 | 7.12 |
November | 21.88 | 3.03 |
December | 21.74 | -1.0 |
Annual Sum or Average | 22.86 | 10.02 |
Minimum of Months | 21.74 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 0.85 |
February | 21.73 | -0.2 |
March | 21.94 | 4.82 |
April | 21.95 | 6.08 |
May | 23.06 | 13.74 |
June | 24.31 | 22.16 |
July | 24.33 | 22.71 |
August | 24.29 | 21.74 |
September | 24.08 | 18.54 |
October | 22.28 | 7.12 |
November | 21.83 | 3.03 |
December | 21.73 | -1.0 |
Annual Sum or Average | 22.78 | 10.02 |
Minimum of Months | 21.73 | -1.0 |
Maximum of Months | 24.33 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 0.85 |
February | 21.73 | -0.2 |
March | 21.94 | 4.82 |
April | 21.95 | 6.08 |
May | 23.05 | 13.74 |
June | 24.31 | 22.16 |
July | 24.34 | 22.71 |
August | 24.29 | 21.74 |
September | 24.08 | 18.54 |
October | 22.27 | 7.12 |
November | 21.82 | 3.03 |
December | 21.73 | -1.0 |
Annual Sum or Average | 22.78 | 10.02 |
Minimum of Months | 21.73 | -1.0 |
Maximum of Months | 24.34 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 0.85 |
February | 22.57 | -0.2 |
March | 22.65 | 4.82 |
April | 22.40 | 6.08 |
May | 23.32 | 13.74 |
June | 24.30 | 22.16 |
July | 24.33 | 22.71 |
August | 24.36 | 21.74 |
September | 24.31 | 18.54 |
October | 23.20 | 7.12 |
November | 22.85 | 3.03 |
December | 22.40 | -1.0 |
Annual Sum or Average | 23.28 | 10.02 |
Minimum of Months | 22.40 | -1.0 |
Maximum of Months | 24.36 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 0.85 |
February | 22.58 | -0.2 |
March | 22.67 | 4.82 |
April | 22.43 | 6.08 |
May | 23.36 | 13.74 |
June | 24.30 | 22.16 |
July | 24.33 | 22.71 |
August | 24.36 | 21.74 |
September | 24.31 | 18.54 |
October | 23.21 | 7.12 |
November | 22.87 | 3.03 |
December | 22.42 | -1.0 |
Annual Sum or Average | 23.30 | 10.02 |
Minimum of Months | 22.42 | -1.0 |
Maximum of Months | 24.36 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.33 | 0.85 |
February | 18.01 | -0.2 |
March | 19.29 | 4.82 |
April | 19.55 | 6.08 |
May | 22.11 | 13.74 |
June | 25.42 | 22.16 |
July | 25.59 | 22.71 |
August | 25.31 | 21.74 |
September | 24.49 | 18.54 |
October | 20.38 | 7.12 |
November | 18.95 | 3.03 |
December | 17.67 | -1.0 |
Annual Sum or Average | 21.28 | 10.02 |
Minimum of Months | 17.67 | -1.0 |
Maximum of Months | 25.59 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.27 | 0.85 |
February | 23.03 | -0.2 |
March | 23.11 | 4.82 |
April | 23.05 | 6.08 |
May | 24.13 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.39 | 21.74 |
September | 24.34 | 18.54 |
October | 23.64 | 7.12 |
November | 23.35 | 3.03 |
December | 22.72 | -1.0 |
Annual Sum or Average | 23.65 | 10.02 |
Minimum of Months | 22.72 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 0.85 |
February | 21.97 | -0.2 |
March | 22.54 | 4.82 |
April | 22.62 | 6.08 |
May | 24.04 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.37 | 21.74 |
September | 24.25 | 18.54 |
October | 23.08 | 7.12 |
November | 22.26 | 3.03 |
December | 21.84 | -1.0 |
Annual Sum or Average | 23.15 | 10.02 |
Minimum of Months | 21.84 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 0.85 |
February | 23.04 | -0.2 |
March | 23.16 | 4.82 |
April | 23.11 | 6.08 |
May | 24.15 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.36 | 18.54 |
October | 23.63 | 7.12 |
November | 23.33 | 3.03 |
December | 22.73 | -1.0 |
Annual Sum or Average | 23.67 | 10.02 |
Minimum of Months | 22.73 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 0.85 |
February | 21.92 | -0.2 |
March | 22.44 | 4.82 |
April | 22.55 | 6.08 |
May | 23.97 | 13.74 |
June | 24.42 | 22.16 |
July | 24.42 | 22.71 |
August | 24.38 | 21.74 |
September | 24.25 | 18.54 |
October | 22.93 | 7.12 |
November | 22.12 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.10 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.42 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 0.85 |
February | 21.85 | -0.2 |
March | 22.33 | 4.82 |
April | 22.42 | 6.08 |
May | 23.93 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.35 | 21.74 |
September | 24.23 | 18.54 |
October | 22.93 | 7.12 |
November | 22.11 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.06 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 0.85 |
February | 21.85 | -0.2 |
March | 22.32 | 4.82 |
April | 22.41 | 6.08 |
May | 23.93 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.23 | 18.54 |
October | 22.91 | 7.12 |
November | 22.10 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.05 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.50 | 0.85 |
February | 23.20 | -0.2 |
March | 23.20 | 4.82 |
April | 23.08 | 6.08 |
May | 24.10 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.76 | 7.12 |
November | 23.54 | 3.03 |
December | 22.96 | -1.0 |
Annual Sum or Average | 23.74 | 10.02 |
Minimum of Months | 22.96 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.50 | 0.85 |
February | 23.21 | -0.2 |
March | 23.21 | 4.82 |
April | 23.10 | 6.08 |
May | 24.11 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.76 | 7.12 |
November | 23.54 | 3.03 |
December | 22.97 | -1.0 |
Annual Sum or Average | 23.75 | 10.02 |
Minimum of Months | 22.97 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 0.85 |
February | 22.85 | -0.2 |
March | 23.39 | 4.82 |
April | 23.46 | 6.08 |
May | 25.23 | 13.74 |
June | 26.51 | 22.16 |
July | 26.53 | 22.71 |
August | 26.46 | 21.74 |
September | 26.14 | 18.54 |
October | 24.24 | 7.12 |
November | 23.36 | 3.03 |
December | 22.48 | -1.0 |
Annual Sum or Average | 24.49 | 10.02 |
Minimum of Months | 22.48 | -1.0 |
Maximum of Months | 26.53 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.42 | 0.85 |
February | 23.12 | -0.2 |
March | 23.17 | 4.82 |
April | 23.14 | 6.08 |
May | 24.19 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.39 | 21.74 |
September | 24.35 | 18.54 |
October | 23.71 | 7.12 |
November | 23.46 | 3.03 |
December | 22.78 | -1.0 |
Annual Sum or Average | 23.71 | 10.02 |
Minimum of Months | 22.78 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 0.85 |
February | 22.02 | -0.2 |
March | 22.61 | 4.82 |
April | 22.72 | 6.08 |
May | 24.11 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.37 | 21.74 |
September | 24.26 | 18.54 |
October | 23.21 | 7.12 |
November | 22.35 | 3.03 |
December | 21.86 | -1.0 |
Annual Sum or Average | 23.21 | 10.02 |
Minimum of Months | 21.86 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 0.85 |
February | 23.08 | -0.2 |
March | 23.17 | 4.82 |
April | 23.13 | 6.08 |
May | 24.18 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.37 | 18.54 |
October | 23.67 | 7.12 |
November | 23.40 | 3.03 |
December | 22.75 | -1.0 |
Annual Sum or Average | 23.69 | 10.02 |
Minimum of Months | 22.75 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 0.85 |
February | 21.97 | -0.2 |
March | 22.52 | 4.82 |
April | 22.64 | 6.08 |
May | 24.07 | 13.74 |
June | 24.43 | 22.16 |
July | 24.42 | 22.71 |
August | 24.38 | 21.74 |
September | 24.25 | 18.54 |
October | 23.07 | 7.12 |
November | 22.21 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 23.15 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.43 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 0.85 |
February | 21.92 | -0.2 |
March | 22.44 | 4.82 |
April | 22.58 | 6.08 |
May | 24.07 | 13.74 |
June | 24.40 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.15 | 7.12 |
November | 22.24 | 3.03 |
December | 21.82 | -1.0 |
Annual Sum or Average | 23.14 | 10.02 |
Minimum of Months | 21.82 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 0.85 |
February | 21.92 | -0.2 |
March | 22.43 | 4.82 |
April | 22.57 | 6.08 |
May | 24.06 | 13.74 |
June | 24.40 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.13 | 7.12 |
November | 22.23 | 3.03 |
December | 21.82 | -1.0 |
Annual Sum or Average | 23.13 | 10.02 |
Minimum of Months | 21.82 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.70 | 0.85 |
February | 23.33 | -0.2 |
March | 23.31 | 4.82 |
April | 23.25 | 6.08 |
May | 24.20 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.85 | 7.12 |
November | 23.68 | 3.03 |
December | 23.10 | -1.0 |
Annual Sum or Average | 23.83 | 10.02 |
Minimum of Months | 23.10 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.70 | 0.85 |
February | 23.33 | -0.2 |
March | 23.31 | 4.82 |
April | 23.25 | 6.08 |
May | 24.20 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.85 | 7.12 |
November | 23.68 | 3.03 |
December | 23.10 | -1.0 |
Annual Sum or Average | 23.83 | 10.02 |
Minimum of Months | 23.10 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 0.85 |
February | 23.37 | -0.2 |
March | 23.87 | 4.82 |
April | 23.94 | 6.08 |
May | 25.70 | 13.74 |
June | 26.66 | 22.16 |
July | 26.65 | 22.71 |
August | 26.59 | 21.74 |
September | 26.31 | 18.54 |
October | 24.72 | 7.12 |
November | 23.88 | 3.03 |
December | 22.96 | -1.0 |
Annual Sum or Average | 24.87 | 10.02 |
Minimum of Months | 22.96 | -1.0 |
Maximum of Months | 26.66 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.44 | 0.85 |
February | 23.11 | -0.2 |
March | 23.16 | 4.82 |
April | 23.13 | 6.08 |
May | 24.19 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.39 | 21.74 |
September | 24.34 | 18.54 |
October | 23.71 | 7.12 |
November | 23.47 | 3.03 |
December | 22.77 | -1.0 |
Annual Sum or Average | 23.71 | 10.02 |
Minimum of Months | 22.77 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 0.85 |
February | 22.03 | -0.2 |
March | 22.61 | 4.82 |
April | 22.72 | 6.08 |
May | 24.12 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.37 | 21.74 |
September | 24.25 | 18.54 |
October | 23.23 | 7.12 |
November | 22.38 | 3.03 |
December | 21.86 | -1.0 |
Annual Sum or Average | 23.21 | 10.02 |
Minimum of Months | 21.86 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 0.85 |
February | 23.07 | -0.2 |
March | 23.16 | 4.82 |
April | 23.11 | 6.08 |
May | 24.17 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.37 | 18.54 |
October | 23.67 | 7.12 |
November | 23.40 | 3.03 |
December | 22.73 | -1.0 |
Annual Sum or Average | 23.69 | 10.02 |
Minimum of Months | 22.73 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 0.85 |
February | 21.97 | -0.2 |
March | 22.52 | 4.82 |
April | 22.64 | 6.08 |
May | 24.07 | 13.74 |
June | 24.43 | 22.16 |
July | 24.42 | 22.71 |
August | 24.38 | 21.74 |
September | 24.24 | 18.54 |
October | 23.09 | 7.12 |
November | 22.23 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 23.15 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.43 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 0.85 |
February | 21.94 | -0.2 |
March | 22.47 | 4.82 |
April | 22.61 | 6.08 |
May | 24.09 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.20 | 7.12 |
November | 22.29 | 3.03 |
December | 21.83 | -1.0 |
Annual Sum or Average | 23.16 | 10.02 |
Minimum of Months | 21.83 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 0.85 |
February | 21.94 | -0.2 |
March | 22.46 | 4.82 |
April | 22.60 | 6.08 |
May | 24.08 | 13.74 |
June | 24.40 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.19 | 7.12 |
November | 22.27 | 3.03 |
December | 21.82 | -1.0 |
Annual Sum or Average | 23.15 | 10.02 |
Minimum of Months | 21.82 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 0.85 |
February | 23.34 | -0.2 |
March | 23.32 | 4.82 |
April | 23.27 | 6.08 |
May | 24.21 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.86 | 7.12 |
November | 23.71 | 3.03 |
December | 23.11 | -1.0 |
Annual Sum or Average | 23.85 | 10.02 |
Minimum of Months | 23.11 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 0.85 |
February | 23.34 | -0.2 |
March | 23.32 | 4.82 |
April | 23.27 | 6.08 |
May | 24.22 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.40 | 21.74 |
September | 24.41 | 18.54 |
October | 23.86 | 7.12 |
November | 23.71 | 3.03 |
December | 23.11 | -1.0 |
Annual Sum or Average | 23.85 | 10.02 |
Minimum of Months | 23.11 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.91 | 0.85 |
February | 23.53 | -0.2 |
March | 24.03 | 4.82 |
April | 24.10 | 6.08 |
May | 25.87 | 13.74 |
June | 26.76 | 22.16 |
July | 26.74 | 22.71 |
August | 26.69 | 21.74 |
September | 26.40 | 18.54 |
October | 24.89 | 7.12 |
November | 24.06 | 3.03 |
December | 23.11 | -1.0 |
Annual Sum or Average | 25.02 | 10.02 |
Minimum of Months | 23.11 | -1.0 |
Maximum of Months | 26.76 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.46 | 0.85 |
February | 23.11 | -0.2 |
March | 23.15 | 4.82 |
April | 23.12 | 6.08 |
May | 24.19 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.38 | 21.74 |
September | 24.34 | 18.54 |
October | 23.71 | 7.12 |
November | 23.47 | 3.03 |
December | 22.76 | -1.0 |
Annual Sum or Average | 23.71 | 10.02 |
Minimum of Months | 22.76 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.13 | 0.85 |
February | 22.03 | -0.2 |
March | 22.61 | 4.82 |
April | 22.71 | 6.08 |
May | 24.12 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.37 | 21.74 |
September | 24.25 | 18.54 |
October | 23.24 | 7.12 |
November | 22.40 | 3.03 |
December | 21.86 | -1.0 |
Annual Sum or Average | 23.21 | 10.02 |
Minimum of Months | 21.86 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 0.85 |
February | 23.06 | -0.2 |
March | 23.15 | 4.82 |
April | 23.09 | 6.08 |
May | 24.17 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.36 | 18.54 |
October | 23.67 | 7.12 |
November | 23.41 | 3.03 |
December | 22.72 | -1.0 |
Annual Sum or Average | 23.69 | 10.02 |
Minimum of Months | 22.72 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 0.85 |
February | 21.97 | -0.2 |
March | 22.52 | 4.82 |
April | 22.63 | 6.08 |
May | 24.07 | 13.74 |
June | 24.44 | 22.16 |
July | 24.43 | 22.71 |
August | 24.38 | 21.74 |
September | 24.24 | 18.54 |
October | 23.10 | 7.12 |
November | 22.24 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 23.16 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.44 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 0.85 |
February | 21.95 | -0.2 |
March | 22.48 | 4.82 |
April | 22.62 | 6.08 |
May | 24.09 | 13.74 |
June | 24.40 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.23 | 7.12 |
November | 22.32 | 3.03 |
December | 21.83 | -1.0 |
Annual Sum or Average | 23.17 | 10.02 |
Minimum of Months | 21.83 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 0.85 |
February | 21.95 | -0.2 |
March | 22.47 | 4.82 |
April | 22.61 | 6.08 |
May | 24.09 | 13.74 |
June | 24.40 | 22.16 |
July | 24.39 | 22.71 |
August | 24.35 | 21.74 |
September | 24.24 | 18.54 |
October | 23.22 | 7.12 |
November | 22.31 | 3.03 |
December | 21.83 | -1.0 |
Annual Sum or Average | 23.17 | 10.02 |
Minimum of Months | 21.83 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 0.85 |
February | 23.35 | -0.2 |
March | 23.32 | 4.82 |
April | 23.27 | 6.08 |
May | 24.22 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.39 | 21.74 |
September | 24.41 | 18.54 |
October | 23.87 | 7.12 |
November | 23.72 | 3.03 |
December | 23.11 | -1.0 |
Annual Sum or Average | 23.85 | 10.02 |
Minimum of Months | 23.11 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 0.85 |
February | 23.34 | -0.2 |
March | 23.32 | 4.82 |
April | 23.27 | 6.08 |
May | 24.22 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.39 | 21.74 |
September | 24.41 | 18.54 |
October | 23.87 | 7.12 |
November | 23.72 | 3.03 |
December | 23.11 | -1.0 |
Annual Sum or Average | 23.85 | 10.02 |
Minimum of Months | 23.11 | -1.0 |
Maximum of Months | 24.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.57 | 0.85 |
February | 24.16 | -0.2 |
March | 24.66 | 4.82 |
April | 24.72 | 6.08 |
May | 26.48 | 13.74 |
June | 27.35 | 22.16 |
July | 27.34 | 22.71 |
August | 27.29 | 21.74 |
September | 27.00 | 18.54 |
October | 25.53 | 7.12 |
November | 24.71 | 3.03 |
December | 23.73 | -1.0 |
Annual Sum or Average | 25.64 | 10.02 |
Minimum of Months | 23.73 | -1.0 |
Maximum of Months | 27.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 0.85 |
February | 23.05 | -0.2 |
March | 23.09 | 4.82 |
April | 23.03 | 6.08 |
May | 24.15 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.38 | 21.74 |
September | 24.33 | 18.54 |
October | 23.67 | 7.12 |
November | 23.42 | 3.03 |
December | 22.70 | -1.0 |
Annual Sum or Average | 23.67 | 10.02 |
Minimum of Months | 22.70 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 0.85 |
February | 21.98 | -0.2 |
March | 22.56 | 4.82 |
April | 22.61 | 6.08 |
May | 24.07 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.36 | 21.74 |
September | 24.22 | 18.54 |
October | 23.16 | 7.12 |
November | 22.34 | 3.03 |
December | 21.84 | -1.0 |
Annual Sum or Average | 23.17 | 10.02 |
Minimum of Months | 21.84 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 0.85 |
February | 23.00 | -0.2 |
March | 23.09 | 4.82 |
April | 23.01 | 6.08 |
May | 24.13 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.40 | 21.74 |
September | 24.35 | 18.54 |
October | 23.63 | 7.12 |
November | 23.35 | 3.03 |
December | 22.65 | -1.0 |
Annual Sum or Average | 23.65 | 10.02 |
Minimum of Months | 22.65 | -1.0 |
Maximum of Months | 24.40 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 0.85 |
February | 21.93 | -0.2 |
March | 22.46 | 4.82 |
April | 22.54 | 6.08 |
May | 24.02 | 13.74 |
June | 24.44 | 22.16 |
July | 24.43 | 22.71 |
August | 24.37 | 21.74 |
September | 24.21 | 18.54 |
October | 23.01 | 7.12 |
November | 22.19 | 3.03 |
December | 21.78 | -1.0 |
Annual Sum or Average | 23.12 | 10.02 |
Minimum of Months | 21.78 | -1.0 |
Maximum of Months | 24.44 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 0.85 |
February | 21.91 | -0.2 |
March | 22.43 | 4.82 |
April | 22.52 | 6.08 |
May | 24.04 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.34 | 21.74 |
September | 24.21 | 18.54 |
October | 23.15 | 7.12 |
November | 22.26 | 3.03 |
December | 21.81 | -1.0 |
Annual Sum or Average | 23.13 | 10.02 |
Minimum of Months | 21.81 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 0.85 |
February | 21.91 | -0.2 |
March | 22.42 | 4.82 |
April | 22.51 | 6.08 |
May | 24.04 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.34 | 21.74 |
September | 24.21 | 18.54 |
October | 23.13 | 7.12 |
November | 22.25 | 3.03 |
December | 21.81 | -1.0 |
Annual Sum or Average | 23.12 | 10.02 |
Minimum of Months | 21.81 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 0.85 |
February | 23.30 | -0.2 |
March | 23.26 | 4.82 |
April | 23.18 | 6.08 |
May | 24.17 | 13.74 |
June | 24.36 | 22.16 |
July | 24.37 | 22.71 |
August | 24.39 | 21.74 |
September | 24.39 | 18.54 |
October | 23.83 | 7.12 |
November | 23.68 | 3.03 |
December | 23.04 | -1.0 |
Annual Sum or Average | 23.81 | 10.02 |
Minimum of Months | 23.04 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 0.85 |
February | 23.30 | -0.2 |
March | 23.26 | 4.82 |
April | 23.18 | 6.08 |
May | 24.17 | 13.74 |
June | 24.36 | 22.16 |
July | 24.37 | 22.71 |
August | 24.39 | 21.74 |
September | 24.39 | 18.54 |
October | 23.83 | 7.12 |
November | 23.67 | 3.03 |
December | 23.03 | -1.0 |
Annual Sum or Average | 23.81 | 10.02 |
Minimum of Months | 23.03 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 0.85 |
February | 23.47 | -0.2 |
March | 23.96 | 4.82 |
April | 24.00 | 6.08 |
May | 25.82 | 13.74 |
June | 26.74 | 22.16 |
July | 26.73 | 22.71 |
August | 26.67 | 21.74 |
September | 26.37 | 18.54 |
October | 24.84 | 7.12 |
November | 24.02 | 3.03 |
December | 23.04 | -1.0 |
Annual Sum or Average | 24.97 | 10.02 |
Minimum of Months | 23.04 | -1.0 |
Maximum of Months | 26.74 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 0.85 |
February | 23.00 | -0.2 |
March | 23.05 | 4.82 |
April | 22.97 | 6.08 |
May | 24.12 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.37 | 21.74 |
September | 24.32 | 18.54 |
October | 23.64 | 7.12 |
November | 23.38 | 3.03 |
December | 22.65 | -1.0 |
Annual Sum or Average | 23.64 | 10.02 |
Minimum of Months | 22.65 | -1.0 |
Maximum of Months | 24.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 0.85 |
February | 21.95 | -0.2 |
March | 22.52 | 4.82 |
April | 22.54 | 6.08 |
May | 24.04 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.35 | 21.74 |
September | 24.21 | 18.54 |
October | 23.10 | 7.12 |
November | 22.30 | 3.03 |
December | 21.82 | -1.0 |
Annual Sum or Average | 23.14 | 10.02 |
Minimum of Months | 21.82 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.27 | 0.85 |
February | 22.96 | -0.2 |
March | 23.05 | 4.82 |
April | 22.94 | 6.08 |
May | 24.10 | 13.74 |
June | 24.39 | 22.16 |
July | 24.39 | 22.71 |
August | 24.39 | 21.74 |
September | 24.34 | 18.54 |
October | 23.60 | 7.12 |
November | 23.31 | 3.03 |
December | 22.61 | -1.0 |
Annual Sum or Average | 23.62 | 10.02 |
Minimum of Months | 22.61 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 0.85 |
February | 21.90 | -0.2 |
March | 22.43 | 4.82 |
April | 22.47 | 6.08 |
May | 23.98 | 13.74 |
June | 24.44 | 22.16 |
July | 24.43 | 22.71 |
August | 24.37 | 21.74 |
September | 24.20 | 18.54 |
October | 22.95 | 7.12 |
November | 22.16 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.77 | -1.0 |
Maximum of Months | 24.44 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 0.85 |
February | 21.89 | -0.2 |
March | 22.39 | 4.82 |
April | 22.44 | 6.08 |
May | 24.00 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.33 | 21.74 |
September | 24.19 | 18.54 |
October | 23.07 | 7.12 |
November | 22.22 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 23.10 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 0.85 |
February | 21.88 | -0.2 |
March | 22.38 | 4.82 |
April | 22.44 | 6.08 |
May | 24.00 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.33 | 21.74 |
September | 24.19 | 18.54 |
October | 23.05 | 7.12 |
November | 22.20 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 0.85 |
February | 23.26 | -0.2 |
March | 23.22 | 4.82 |
April | 23.10 | 6.08 |
May | 24.14 | 13.74 |
June | 24.36 | 22.16 |
July | 24.36 | 22.71 |
August | 24.38 | 21.74 |
September | 24.39 | 18.54 |
October | 23.81 | 7.12 |
November | 23.64 | 3.03 |
December | 22.98 | -1.0 |
Annual Sum or Average | 23.78 | 10.02 |
Minimum of Months | 22.98 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 0.85 |
February | 23.26 | -0.2 |
March | 23.22 | 4.82 |
April | 23.11 | 6.08 |
May | 24.14 | 13.74 |
June | 24.36 | 22.16 |
July | 24.36 | 22.71 |
August | 24.38 | 21.74 |
September | 24.39 | 18.54 |
October | 23.80 | 7.12 |
November | 23.64 | 3.03 |
December | 22.98 | -1.0 |
Annual Sum or Average | 23.78 | 10.02 |
Minimum of Months | 22.98 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 0.85 |
February | 23.32 | -0.2 |
March | 23.80 | 4.82 |
April | 23.82 | 6.08 |
May | 25.68 | 13.74 |
June | 26.65 | 22.16 |
July | 26.64 | 22.71 |
August | 26.58 | 21.74 |
September | 26.26 | 18.54 |
October | 24.68 | 7.12 |
November | 23.87 | 3.03 |
December | 22.88 | -1.0 |
Annual Sum or Average | 24.84 | 10.02 |
Minimum of Months | 22.88 | -1.0 |
Maximum of Months | 26.65 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 0.85 |
February | 22.96 | -0.2 |
March | 23.02 | 4.82 |
April | 22.91 | 6.08 |
May | 24.09 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.37 | 21.74 |
September | 24.31 | 18.54 |
October | 23.61 | 7.12 |
November | 23.35 | 3.03 |
December | 22.61 | -1.0 |
Annual Sum or Average | 23.61 | 10.02 |
Minimum of Months | 22.61 | -1.0 |
Maximum of Months | 24.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 0.85 |
February | 21.93 | -0.2 |
March | 22.49 | 4.82 |
April | 22.49 | 6.08 |
May | 24.01 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.35 | 21.74 |
September | 24.19 | 18.54 |
October | 23.04 | 7.12 |
November | 22.27 | 3.03 |
December | 21.81 | -1.0 |
Annual Sum or Average | 23.12 | 10.02 |
Minimum of Months | 21.81 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 0.85 |
February | 22.92 | -0.2 |
March | 23.01 | 4.82 |
April | 22.89 | 6.08 |
May | 24.07 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.39 | 21.74 |
September | 24.33 | 18.54 |
October | 23.56 | 7.12 |
November | 23.27 | 3.03 |
December | 22.56 | -1.0 |
Annual Sum or Average | 23.59 | 10.02 |
Minimum of Months | 22.56 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 0.85 |
February | 21.88 | -0.2 |
March | 22.40 | 4.82 |
April | 22.42 | 6.08 |
May | 23.95 | 13.74 |
June | 24.44 | 22.16 |
July | 24.43 | 22.71 |
August | 24.37 | 21.74 |
September | 24.18 | 18.54 |
October | 22.88 | 7.12 |
November | 22.13 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 23.07 | 10.02 |
Minimum of Months | 21.77 | -1.0 |
Maximum of Months | 24.44 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 0.85 |
February | 21.86 | -0.2 |
March | 22.36 | 4.82 |
April | 22.39 | 6.08 |
May | 23.97 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.33 | 21.74 |
September | 24.17 | 18.54 |
October | 23.00 | 7.12 |
November | 22.18 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.07 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 0.85 |
February | 21.86 | -0.2 |
March | 22.35 | 4.82 |
April | 22.39 | 6.08 |
May | 23.97 | 13.74 |
June | 24.39 | 22.16 |
July | 24.38 | 22.71 |
August | 24.33 | 21.74 |
September | 24.17 | 18.54 |
October | 22.98 | 7.12 |
November | 22.17 | 3.03 |
December | 21.78 | -1.0 |
Annual Sum or Average | 23.07 | 10.02 |
Minimum of Months | 21.78 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 0.85 |
February | 23.22 | -0.2 |
March | 23.17 | 4.82 |
April | 23.04 | 6.08 |
May | 24.10 | 13.74 |
June | 24.35 | 22.16 |
July | 24.36 | 22.71 |
August | 24.38 | 21.74 |
September | 24.37 | 18.54 |
October | 23.78 | 7.12 |
November | 23.60 | 3.03 |
December | 22.92 | -1.0 |
Annual Sum or Average | 23.75 | 10.02 |
Minimum of Months | 22.92 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.61 | 0.85 |
February | 23.22 | -0.2 |
March | 23.18 | 4.82 |
April | 23.04 | 6.08 |
May | 24.10 | 13.74 |
June | 24.35 | 22.16 |
July | 24.36 | 22.71 |
August | 24.38 | 21.74 |
September | 24.38 | 18.54 |
October | 23.78 | 7.12 |
November | 23.60 | 3.03 |
December | 22.92 | -1.0 |
Annual Sum or Average | 23.75 | 10.02 |
Minimum of Months | 22.92 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.63 | 0.85 |
February | 23.22 | -0.2 |
March | 23.71 | 4.82 |
April | 23.72 | 6.08 |
May | 25.62 | 13.74 |
June | 26.65 | 22.16 |
July | 26.63 | 22.71 |
August | 26.57 | 21.74 |
September | 26.23 | 18.54 |
October | 24.57 | 7.12 |
November | 23.78 | 3.03 |
December | 22.78 | -1.0 |
Annual Sum or Average | 24.77 | 10.02 |
Minimum of Months | 22.78 | -1.0 |
Maximum of Months | 26.65 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 0.85 |
February | 22.87 | -0.2 |
March | 22.97 | 4.82 |
April | 22.84 | 6.08 |
May | 24.06 | 13.74 |
June | 24.37 | 22.16 |
July | 24.37 | 22.71 |
August | 24.37 | 21.74 |
September | 24.28 | 18.54 |
October | 23.54 | 7.12 |
November | 23.26 | 3.03 |
December | 22.53 | -1.0 |
Annual Sum or Average | 23.56 | 10.02 |
Minimum of Months | 22.53 | -1.0 |
Maximum of Months | 24.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 0.85 |
February | 21.91 | -0.2 |
March | 22.46 | 4.82 |
April | 22.46 | 6.08 |
May | 23.97 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.35 | 21.74 |
September | 24.17 | 18.54 |
October | 22.96 | 7.12 |
November | 22.23 | 3.03 |
December | 21.81 | -1.0 |
Annual Sum or Average | 23.09 | 10.02 |
Minimum of Months | 21.81 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.10 | 0.85 |
February | 22.84 | -0.2 |
March | 22.96 | 4.82 |
April | 22.82 | 6.08 |
May | 24.04 | 13.74 |
June | 24.38 | 22.16 |
July | 24.38 | 22.71 |
August | 24.39 | 21.74 |
September | 24.31 | 18.54 |
October | 23.49 | 7.12 |
November | 23.19 | 3.03 |
December | 22.49 | -1.0 |
Annual Sum or Average | 23.54 | 10.02 |
Minimum of Months | 22.49 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 0.85 |
February | 21.86 | -0.2 |
March | 22.37 | 4.82 |
April | 22.39 | 6.08 |
May | 23.91 | 13.74 |
June | 24.45 | 22.16 |
July | 24.43 | 22.71 |
August | 24.37 | 21.74 |
September | 24.16 | 18.54 |
October | 22.80 | 7.12 |
November | 22.10 | 3.03 |
December | 21.76 | -1.0 |
Annual Sum or Average | 23.05 | 10.02 |
Minimum of Months | 21.76 | -1.0 |
Maximum of Months | 24.45 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 0.85 |
February | 21.85 | -0.2 |
March | 22.33 | 4.82 |
April | 22.36 | 6.08 |
May | 23.93 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.33 | 21.74 |
September | 24.15 | 18.54 |
October | 22.89 | 7.12 |
November | 22.14 | 3.03 |
December | 21.78 | -1.0 |
Annual Sum or Average | 23.04 | 10.02 |
Minimum of Months | 21.78 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 0.85 |
February | 21.85 | -0.2 |
March | 22.33 | 4.82 |
April | 22.35 | 6.08 |
May | 23.93 | 13.74 |
June | 24.38 | 22.16 |
July | 24.37 | 22.71 |
August | 24.33 | 21.74 |
September | 24.15 | 18.54 |
October | 22.88 | 7.12 |
November | 22.13 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 23.04 | 10.02 |
Minimum of Months | 21.77 | -1.0 |
Maximum of Months | 24.38 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.47 | 0.85 |
February | 23.12 | -0.2 |
March | 23.10 | 4.82 |
April | 22.94 | 6.08 |
May | 24.06 | 13.74 |
June | 24.35 | 22.16 |
July | 24.36 | 22.71 |
August | 24.37 | 21.74 |
September | 24.35 | 18.54 |
October | 23.70 | 7.12 |
November | 23.49 | 3.03 |
December | 22.81 | -1.0 |
Annual Sum or Average | 23.68 | 10.02 |
Minimum of Months | 22.81 | -1.0 |
Maximum of Months | 24.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.47 | 0.85 |
February | 23.12 | -0.2 |
March | 23.10 | 4.82 |
April | 22.95 | 6.08 |
May | 24.06 | 13.74 |
June | 24.35 | 22.16 |
July | 24.36 | 22.71 |
August | 24.37 | 21.74 |
September | 24.35 | 18.54 |
October | 23.70 | 7.12 |
November | 23.49 | 3.03 |
December | 22.81 | -1.0 |
Annual Sum or Average | 23.68 | 10.02 |
Minimum of Months | 22.81 | -1.0 |
Maximum of Months | 24.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 0.85 |
February | 23.03 | -0.2 |
March | 23.56 | 4.82 |
April | 23.58 | 6.08 |
May | 25.56 | 13.74 |
June | 26.72 | 22.16 |
July | 26.70 | 22.71 |
August | 26.63 | 21.74 |
September | 26.21 | 18.54 |
October | 24.39 | 7.12 |
November | 23.58 | 3.03 |
December | 22.56 | -1.0 |
Annual Sum or Average | 24.67 | 10.02 |
Minimum of Months | 22.56 | -1.0 |
Maximum of Months | 26.72 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 0.85 |
February | 22.62 | -0.2 |
March | 22.80 | 4.82 |
April | 22.67 | 6.08 |
May | 23.84 | 13.74 |
June | 24.33 | 22.16 |
July | 24.33 | 22.71 |
August | 24.33 | 21.74 |
September | 24.16 | 18.54 |
October | 23.14 | 7.12 |
November | 22.89 | 3.03 |
December | 22.38 | -1.0 |
Annual Sum or Average | 23.36 | 10.02 |
Minimum of Months | 22.38 | -1.0 |
Maximum of Months | 24.33 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 0.85 |
February | 22.00 | -0.2 |
March | 22.43 | 4.82 |
April | 22.43 | 6.08 |
May | 23.76 | 13.74 |
June | 24.35 | 22.16 |
July | 24.33 | 22.71 |
August | 24.31 | 21.74 |
September | 24.03 | 18.54 |
October | 22.78 | 7.12 |
November | 22.26 | 3.03 |
December | 21.86 | -1.0 |
Annual Sum or Average | 23.06 | 10.02 |
Minimum of Months | 21.86 | -1.0 |
Maximum of Months | 24.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 0.85 |
February | 22.62 | -0.2 |
March | 22.80 | 4.82 |
April | 22.68 | 6.08 |
May | 23.82 | 13.74 |
June | 24.35 | 22.16 |
July | 24.34 | 22.71 |
August | 24.35 | 21.74 |
September | 24.17 | 18.54 |
October | 23.12 | 7.12 |
November | 22.85 | 3.03 |
December | 22.37 | -1.0 |
Annual Sum or Average | 23.36 | 10.02 |
Minimum of Months | 22.37 | -1.0 |
Maximum of Months | 24.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 0.85 |
February | 21.94 | -0.2 |
March | 22.35 | 4.82 |
April | 22.41 | 6.08 |
May | 23.67 | 13.74 |
June | 24.39 | 22.16 |
July | 24.37 | 22.71 |
August | 24.33 | 21.74 |
September | 24.01 | 18.54 |
October | 22.71 | 7.12 |
November | 22.15 | 3.03 |
December | 21.79 | -1.0 |
Annual Sum or Average | 23.01 | 10.02 |
Minimum of Months | 21.79 | -1.0 |
Maximum of Months | 24.39 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 0.85 |
February | 21.89 | -0.2 |
March | 22.32 | 4.82 |
April | 22.35 | 6.08 |
May | 23.73 | 13.74 |
June | 24.34 | 22.16 |
July | 24.32 | 22.71 |
August | 24.29 | 21.74 |
September | 24.01 | 18.54 |
October | 22.70 | 7.12 |
November | 22.14 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 22.99 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.34 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 0.85 |
February | 21.89 | -0.2 |
March | 22.32 | 4.82 |
April | 22.35 | 6.08 |
May | 23.72 | 13.74 |
June | 24.34 | 22.16 |
July | 24.32 | 22.71 |
August | 24.29 | 21.74 |
September | 24.01 | 18.54 |
October | 22.69 | 7.12 |
November | 22.14 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 22.99 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 24.34 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 0.85 |
February | 22.77 | -0.2 |
March | 22.91 | 4.82 |
April | 22.74 | 6.08 |
May | 23.91 | 13.74 |
June | 24.32 | 22.16 |
July | 24.32 | 22.71 |
August | 24.33 | 21.74 |
September | 24.21 | 18.54 |
October | 23.29 | 7.12 |
November | 23.04 | 3.03 |
December | 22.52 | -1.0 |
Annual Sum or Average | 23.45 | 10.02 |
Minimum of Months | 22.52 | -1.0 |
Maximum of Months | 24.33 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.94 | 0.85 |
February | 22.77 | -0.2 |
March | 22.91 | 4.82 |
April | 22.75 | 6.08 |
May | 23.91 | 13.74 |
June | 24.32 | 22.16 |
July | 24.32 | 22.71 |
August | 24.33 | 21.74 |
September | 24.22 | 18.54 |
October | 23.29 | 7.12 |
November | 23.04 | 3.03 |
December | 22.52 | -1.0 |
Annual Sum or Average | 23.45 | 10.02 |
Minimum of Months | 22.52 | -1.0 |
Maximum of Months | 24.33 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:15
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 0.85 |
February | 22.85 | -0.2 |
March | 23.59 | 4.82 |
April | 23.67 | 6.08 |
May | 25.95 | 13.74 |
June | 27.49 | 22.16 |
July | 27.45 | 22.71 |
August | 27.37 | 21.74 |
September | 26.70 | 18.54 |
October | 24.34 | 7.12 |
November | 23.44 | 3.03 |
December | 22.28 | -1.0 |
Annual Sum or Average | 24.86 | 10.02 |
Minimum of Months | 22.28 | -1.0 |
Maximum of Months | 27.49 | 22.71 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:15
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.241401E+12 | 141167.040 | 05-JAN-18:00 | 22204.399 | 56867.515 | 22475.067 | 26377.387 | 0.000 | 10720.100 | 1376.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.223260E+12 | 139569.831 | 05-FEB-18:00 | 22204.399 | 56867.515 | 22475.067 | 24780.177 | 0.000 | 10720.100 | 1376.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.240074E+12 | 147298.139 | 13-MAR-16:15 | 18221.747 | 56933.809 | 22475.067 | 0.000 | 45836.877 | 0.000 | 1376.683 | 1305.652 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.219773E+12 | 132420.058 | 16-APR-19:00 | 25049.151 | 49704.829 | 22475.067 | 22148.656 | 0.000 | 10720.100 | 1376.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.236722E+12 | 160114.209 | 31-MAY-17:30 | 22204.399 | 56867.515 | 22475.067 | 0.000 | 54275.666 | 0.000 | 1376.683 | 1768.989 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.284369E+12 | 170956.999 | 26-JUN-19:30 | 25049.151 | 49704.829 | 22475.067 | 0.000 | 58819.019 | 10720.100 | 1376.683 | 1866.578 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.296402E+12 | 167161.888 | 15-JUL-17:15 | 22204.399 | 56867.515 | 22475.067 | 0.000 | 61240.819 | 0.000 | 1376.683 | 1851.768 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.292625E+12 | 170661.974 | 11-AUG-18:00 | 25049.151 | 51564.864 | 22475.067 | 0.000 | 56748.550 | 10720.100 | 1376.683 | 1712.945 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.264658E+12 | 169446.088 | 12-SEP-18:30 | 25049.151 | 51564.864 | 22475.067 | 0.000 | 55518.577 | 10720.100 | 1376.683 | 1727.031 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.243839E+12 | 154813.222 | 10-OCT-17:30 | 22204.399 | 56867.515 | 22475.067 | 0.000 | 38782.519 | 10720.100 | 1376.683 | 1241.050 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.234399E+12 | 139972.661 | 05-NOV-17:15 | 22204.399 | 56867.515 | 22475.067 | 0.000 | 24450.813 | 10720.100 | 1376.683 | 732.447 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.253981E+12 | 168284.434 | 21-DEC-18:00 | 22204.399 | 56867.515 | 22475.067 | 53494.780 | 0.000 | 10720.100 | 1376.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.303150E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.219773E+12 | 132420.058 | 18221.747 | 49704.829 | 22475.067 | 0.000 | 0.000 | 0.000 | 1376.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.296402E+12 | 170956.999 | 25049.151 | 56933.809 | 22475.067 | 53494.780 | 61240.819 | 10720.100 | 1376.683 | 1866.578 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:15
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.157034E+12 | 209105.073 | 05-JAN-09:15 | 0.000 | 0.000 | 0.000 | 209105.073 | 84568.570 | 84568.570 | 124536.503 |
February | 0.175744E+12 | 230672.436 | 12-FEB-06:00 | 0.000 | 0.000 | 0.000 | 230672.436 | 86797.487 | 86797.487 | 143874.948 |
March | 0.164204E+12 | 283059.733 | 19-MAR-07:15 | 0.000 | 0.000 | 0.000 | 283059.733 | 87982.126 | 87982.126 | 195077.608 |
April | 0.139890E+12 | 184493.878 | 17-APR-05:00 | 0.000 | 0.000 | 0.000 | 184493.878 | 84601.127 | 84601.127 | 99892.751 |
May | 0.103221E+12 | 112282.801 | 02-MAY-05:00 | 0.000 | 0.000 | 0.000 | 112282.801 | 83695.731 | 83695.731 | 28587.070 |
June | 0.930200E+11 | 83964.548 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 83964.548 | 83964.548 | 83964.548 | 0.000 |
July | 0.918066E+11 | 82241.089 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 82241.089 | 82241.089 | 82241.089 | 0.000 |
August | 0.903294E+11 | 81293.350 | 30-AUG-06:45 | 0.000 | 0.000 | 0.000 | 81293.350 | 81293.350 | 81293.350 | 0.000 |
September | 0.890835E+11 | 82324.511 | 30-SEP-06:00 | 0.000 | 0.000 | 0.000 | 82324.511 | 82324.511 | 82324.511 | 0.000 |
October | 0.126171E+12 | 172540.152 | 31-OCT-06:30 | 0.000 | 0.000 | 0.000 | 172540.152 | 83944.565 | 83944.565 | 88595.588 |
November | 0.140091E+12 | 205510.102 | 30-NOV-06:00 | 0.000 | 0.000 | 0.000 | 205510.102 | 79732.759 | 79732.759 | 125777.343 |
December | 0.223768E+12 | 281517.327 | 23-DEC-07:15 | 0.000 | 0.000 | 0.000 | 281517.327 | 86693.205 | 86693.205 | 194824.122 |
Annual Sum or Average | 0.159436E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.890835E+11 | 81293.350 | 0.000 | 0.000 | 0.000 | 81293.350 | 79732.759 | 79732.759 | 0.000 | |
Maximum of Months | 0.223768E+12 | 283059.733 | 0.000 | 0.000 | 0.000 | 283059.733 | 87982.126 | 87982.126 | 195077.608 |