Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2018-10-19 09:40:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4806.42 | 613.34 | 680.81 |
Net Site Energy | 4806.42 | 613.34 | 680.81 |
Total Source Energy | 13521.12 | 1725.41 | 1915.20 |
Net Source Energy | 13521.12 | 1725.41 | 1915.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 1.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1315.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 807.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3857.91 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 816.51 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3989.90 | 816.51 | 0.00 | 0.00 | 0.00 | 8636.43 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 1.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1315.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 807.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 63.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3857.91 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 816.51 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 319.13 | 115.66 | 0.00 | 0.00 | 0.00 | 1.22 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 565.15 | 115.66 | 0.00 | 0.00 | 0.00 | 1.22 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 287.51 | 104.19 | 0.00 | 0.00 | 0.00 | 1.10 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 509.14 | 104.19 | 0.00 | 0.00 | 0.00 | 1.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3989.90 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3989.90 | 100.00 |
Total On-Site and Utility Electric Sources | 3989.90 | 100.00 |
Total Electricity End Uses | 3989.90 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8636.43 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8636.43 | 100.00 |
Total Water End Uses | 8636.43 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.50 |
Time Setpoint Not Met During Occupied Cooling | 456.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2354.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 01-JUL-17:15 | 10-JAN-07:00 | - | - | - | 07-JUN-17:15 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97251.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25601.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2063.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3835.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 79739.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 208969.32 | 79739.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 97251.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 18331.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 3872.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25601.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2063.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 3835.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 79739.68 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 5.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4166.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2556.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 201.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 204.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 885.10 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12636.02 | 885.10 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 590.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.37 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1789.83 | 125.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 590.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.37 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1789.83 | 125.37 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_1.22_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 5.778 | 0.306 | 0.155 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 423.59 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 726.80 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.76 | 83.76 | 168.54 | |
Exterior Lighting Total | 10720.10 | 168.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 365312.36 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 292249.89 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4719.02 | 3392.18 | 1326.84 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4766.05 | 3430.38 | 1335.67 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5756.58 | 4116.18 | 1640.41 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4065.21 | 2903.98 | 1161.23 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3008.39 | 2096.68 | 911.70 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2996.57 | 2087.67 | 908.90 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2956.72 | 2040.86 | 915.86 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3014.41 | 2085.06 | 929.34 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5577.89 | 4043.95 | 1533.94 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5629.91 | 4085.75 | 1544.16 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5165.73 | 3722.46 | 1443.27 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4839.07 | 3490.98 | 1348.09 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3602.50 | 2545.53 | 1056.97 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3593.03 | 2538.31 | 1054.72 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3530.44 | 2477.96 | 1052.48 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3545.32 | 2489.35 | 1055.97 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5586.89 | 4048.51 | 1538.37 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5642.66 | 4093.18 | 1549.49 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4947.97 | 3567.53 | 1380.44 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4875.91 | 3516.84 | 1359.07 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3628.33 | 2563.97 | 1064.36 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3618.95 | 2556.83 | 1062.13 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3559.38 | 2498.84 | 1060.54 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3563.69 | 2502.11 | 1061.58 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5616.41 | 4069.31 | 1547.10 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5671.45 | 4113.41 | 1558.04 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5007.86 | 3598.04 | 1409.82 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4907.85 | 3539.52 | 1368.34 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3657.77 | 2585.47 | 1072.30 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3648.49 | 2578.40 | 1070.09 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3589.46 | 2520.89 | 1068.57 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3592.09 | 2522.88 | 1069.21 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5675.84 | 4113.23 | 1562.60 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5731.32 | 4157.66 | 1573.66 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5072.66 | 3646.12 | 1426.53 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4969.83 | 3585.41 | 1384.42 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3717.07 | 2629.91 | 1087.16 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3707.87 | 2622.90 | 1084.97 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3647.96 | 2564.83 | 1083.12 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3650.23 | 2566.55 | 1083.69 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5645.98 | 4089.24 | 1556.74 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5699.41 | 4132.12 | 1567.29 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5049.70 | 3627.44 | 1422.27 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4940.68 | 3561.99 | 1378.69 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3686.31 | 2605.79 | 1080.52 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3677.21 | 2598.86 | 1078.36 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3618.92 | 2541.98 | 1076.95 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3621.06 | 2543.58 | 1077.48 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5646.75 | 4088.76 | 1557.99 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5699.79 | 4131.34 | 1568.45 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5056.38 | 3631.50 | 1424.88 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4943.22 | 3562.89 | 1380.33 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3687.01 | 2605.74 | 1081.27 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3677.99 | 2598.86 | 1079.13 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3619.83 | 2542.08 | 1077.75 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3621.79 | 2543.59 | 1078.20 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5667.50 | 4103.63 | 1563.87 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5719.88 | 4145.70 | 1574.18 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5081.77 | 3649.95 | 1431.83 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4964.42 | 3578.12 | 1386.30 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3703.31 | 2618.61 | 1084.70 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3694.36 | 2611.79 | 1082.57 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3640.12 | 2557.07 | 1083.06 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3642.09 | 2558.58 | 1083.51 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5829.44 | 4226.26 | 1603.17 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5883.32 | 4269.44 | 1613.87 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5230.18 | 3762.33 | 1467.85 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5159.08 | 3716.10 | 1442.98 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3852.86 | 2732.07 | 1120.79 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3843.95 | 2725.29 | 1118.67 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3763.32 | 2653.47 | 1109.85 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3769.68 | 2655.57 | 1114.11 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6779.94 | 4947.51 | 1832.43 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6792.44 | 4959.90 | 1832.54 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6127.47 | 4446.00 | 1681.47 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6010.91 | 4357.09 | 1653.83 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4607.03 | 3302.86 | 1304.17 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4608.09 | 3298.09 | 1309.99 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4711.36 | 3374.25 | 1337.11 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4712.76 | 3375.33 | 1337.43 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4719.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4766.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5756.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4065.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3008.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2996.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2956.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3014.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5577.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5629.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5165.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4839.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3602.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3593.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3530.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3545.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5586.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5642.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4947.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4875.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3628.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3618.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3559.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3563.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5616.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5671.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5007.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4907.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3657.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3648.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3589.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3592.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5675.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5731.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5072.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4969.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3717.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3707.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3647.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3650.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5645.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5699.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5049.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4940.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3686.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3677.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3618.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3621.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5646.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5699.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5056.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4943.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3687.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3677.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3619.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3621.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5667.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5719.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5081.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4964.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3703.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3694.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3640.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3642.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5829.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5883.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5230.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5159.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3852.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3843.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3763.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3769.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6779.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6792.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 6127.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 6010.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4607.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4608.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4711.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4712.76 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 1660.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 1660.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2265.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 1662.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1152.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1152.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1149.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1156.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 1671.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 1671.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 1699.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 1674.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1061.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1062.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1064.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1066.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1622.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1622.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1628.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1625.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1608.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1609.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1613.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1613.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1578.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1578.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1583.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1582.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 1619.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 1619.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 1623.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 1623.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 1636.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 1636.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 1640.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 1641.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1031.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 1656.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 1656.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 1661.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 1660.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1035.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1035.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1034.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1034.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 1764.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 1761.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 1769.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 1766.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1132.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1132.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1134.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1134.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2122.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2125.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2127.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2129.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 1549.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 1549.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 1544.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 1544.27 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 334.82 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 339.32 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 402.73 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.60 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.44 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.49 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 191.17 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.82 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 403.85 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.75 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 368.66 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.71 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.23 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.47 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.08 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 238.28 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 404.22 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 409.42 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 354.08 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 349.33 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 248.11 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 247.36 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 239.22 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 239.56 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 406.33 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 411.47 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 355.24 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 351.65 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 250.34 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 249.59 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.49 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 241.70 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 410.93 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 416.10 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.26 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 356.45 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.99 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.25 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.09 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 246.27 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.31 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 413.32 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 358.22 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 353.90 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 252.40 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.67 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.64 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.81 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.20 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 413.18 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 358.59 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 353.94 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 252.37 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.64 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.62 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 243.78 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 409.73 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 414.66 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.50 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 355.50 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.93 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 253.21 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.17 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.33 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 422.72 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 427.77 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 372.38 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 368.73 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 265.91 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 265.19 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.69 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.55 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 498.95 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 500.73 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 444.99 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 435.54 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 325.29 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 323.93 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.63 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.74 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0079 | 2026.59 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 3100.68 | 3720.81 | 0.249 | 0.299 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
G NW APARTMENT | 3142.36 | 3770.83 | 0.252 | 0.303 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
OFFICE | 3729.62 | 4475.55 | 0.300 | 0.360 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:30:00 | 40.25 | 0.00911 |
G NE APARTMENT | 2635.61 | 3162.73 | 0.212 | 0.254 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
G N1 APARTMENT | 1847.02 | 2216.43 | 0.148 | 0.178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 39.67 | 0.00911 |
G N2 APARTMENT | 1838.23 | 2205.88 | 0.148 | 0.177 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 39.67 | 0.00911 |
G S1 APARTMENT | 1770.43 | 2124.52 | 0.142 | 0.171 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
G S2 APARTMENT | 1813.43 | 2176.12 | 0.146 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F2 SW APARTMENT | 3740.02 | 4488.03 | 0.300 | 0.361 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F2 NW APARTMENT | 3785.36 | 4542.43 | 0.304 | 0.365 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F2 SE APARTMENT | 3414.08 | 4096.90 | 0.274 | 0.329 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F2 NE APARTMENT | 3210.80 | 3852.95 | 0.258 | 0.310 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F2 N1 APARTMENT | 2280.34 | 2736.41 | 0.183 | 0.220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F2 N2 APARTMENT | 2273.27 | 2727.92 | 0.183 | 0.219 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F2 S1 APARTMENT | 2195.58 | 2634.69 | 0.176 | 0.212 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F2 S2 APARTMENT | 2206.72 | 2648.06 | 0.177 | 0.213 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F3 SW APARTMENT | 3743.35 | 4492.03 | 0.301 | 0.361 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F3 NW APARTMENT | 3791.52 | 4549.82 | 0.305 | 0.366 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F3 SE APARTMENT | 3279.02 | 3934.82 | 0.263 | 0.316 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:45:00 | 40.50 | 0.00911 |
F3 NE APARTMENT | 3235.10 | 3882.12 | 0.260 | 0.312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F3 N1 APARTMENT | 2297.75 | 2757.30 | 0.185 | 0.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F3 N2 APARTMENT | 2290.75 | 2748.90 | 0.184 | 0.221 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F3 S1 APARTMENT | 2215.34 | 2658.41 | 0.178 | 0.214 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F3 S2 APARTMENT | 2218.53 | 2662.23 | 0.178 | 0.214 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F4 SW APARTMENT | 3762.96 | 4515.55 | 0.302 | 0.363 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F4 NW APARTMENT | 3810.56 | 4572.68 | 0.306 | 0.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F4 SE APARTMENT | 3289.75 | 3947.70 | 0.264 | 0.317 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F4 NE APARTMENT | 3256.56 | 3907.87 | 0.262 | 0.314 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F4 N1 APARTMENT | 2318.32 | 2781.98 | 0.186 | 0.223 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F4 N2 APARTMENT | 2311.39 | 2773.67 | 0.186 | 0.223 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F4 S1 APARTMENT | 2236.41 | 2683.69 | 0.180 | 0.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F4 S2 APARTMENT | 2238.35 | 2686.01 | 0.180 | 0.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
M SW APARTMENT | 3805.48 | 4566.58 | 0.306 | 0.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
M NW APARTMENT | 3853.42 | 4624.11 | 0.310 | 0.371 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
M SE APARTMENT | 3336.32 | 4003.59 | 0.268 | 0.322 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
M NE APARTMENT | 3301.01 | 3961.21 | 0.265 | 0.318 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
M N1 APARTMENT | 2361.44 | 2833.73 | 0.190 | 0.228 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
M N2 APARTMENT | 2354.57 | 2825.49 | 0.189 | 0.227 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
M S1 APARTMENT | 2278.98 | 2734.78 | 0.183 | 0.220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
M S2 APARTMENT | 2280.65 | 2736.78 | 0.183 | 0.220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F6 SW APARTMENT | 3781.25 | 4537.50 | 0.304 | 0.365 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F6 NW APARTMENT | 3827.66 | 4593.19 | 0.308 | 0.369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F6 SE APARTMENT | 3317.35 | 3980.82 | 0.267 | 0.320 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F6 NE APARTMENT | 3277.37 | 3932.84 | 0.263 | 0.316 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F6 N1 APARTMENT | 2337.47 | 2804.97 | 0.188 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F6 N2 APARTMENT | 2330.68 | 2796.82 | 0.187 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F6 S1 APARTMENT | 2256.29 | 2707.55 | 0.181 | 0.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F6 S2 APARTMENT | 2257.85 | 2709.41 | 0.181 | 0.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F7 SW APARTMENT | 3780.24 | 4536.28 | 0.304 | 0.364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F7 NW APARTMENT | 3826.35 | 4591.62 | 0.307 | 0.369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F7 SE APARTMENT | 3320.82 | 3984.99 | 0.267 | 0.320 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F7 NE APARTMENT | 3277.72 | 3933.26 | 0.263 | 0.316 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F7 N1 APARTMENT | 2337.11 | 2804.53 | 0.188 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F7 N2 APARTMENT | 2330.38 | 2796.46 | 0.187 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
F7 S1 APARTMENT | 2256.09 | 2707.31 | 0.181 | 0.217 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F7 S2 APARTMENT | 2257.57 | 2709.08 | 0.181 | 0.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F8 SW APARTMENT | 3794.39 | 4553.27 | 0.305 | 0.366 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F8 NW APARTMENT | 3840.01 | 4608.02 | 0.308 | 0.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F8 SE APARTMENT | 3338.48 | 4006.18 | 0.268 | 0.322 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
F8 NE APARTMENT | 3292.23 | 3950.67 | 0.264 | 0.317 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:15:00 | 40.01 | 0.00911 |
F8 N1 APARTMENT | 2351.64 | 2821.97 | 0.189 | 0.227 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:45:00 | 39.91 | 0.00911 |
F8 N2 APARTMENT | 2344.96 | 2813.95 | 0.188 | 0.226 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:45:00 | 39.91 | 0.00911 |
F8 S1 APARTMENT | 2270.47 | 2724.57 | 0.182 | 0.219 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F8 S2 APARTMENT | 2271.95 | 2726.34 | 0.183 | 0.219 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F9 SW APARTMENT | 3914.69 | 4697.62 | 0.314 | 0.377 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
F9 NW APARTMENT | 3961.42 | 4753.71 | 0.318 | 0.382 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
F9 SE APARTMENT | 3448.56 | 4138.27 | 0.277 | 0.332 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
F9 NE APARTMENT | 3414.67 | 4097.61 | 0.274 | 0.329 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03 | 0.00911 |
F9 N1 APARTMENT | 2462.56 | 2955.07 | 0.198 | 0.237 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:45:00 | 39.91 | 0.00911 |
F9 N2 APARTMENT | 2455.91 | 2947.10 | 0.197 | 0.237 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:45:00 | 39.91 | 0.00911 |
F9 S1 APARTMENT | 2367.88 | 2841.45 | 0.190 | 0.228 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
F9 S2 APARTMENT | 2366.57 | 2839.88 | 0.190 | 0.228 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
T SW APARTMENT | 4620.61 | 5544.73 | 0.371 | 0.445 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
T NW APARTMENT | 4637.10 | 5564.52 | 0.373 | 0.447 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
T SE APARTMENT | 4120.96 | 4945.15 | 0.331 | 0.397 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
T NE APARTMENT | 4033.40 | 4840.09 | 0.324 | 0.389 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:45:00 | 42.00 | 0.00911 |
T N1 APARTMENT | 3012.40 | 3614.89 | 0.242 | 0.290 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03 | 0.00911 |
T N2 APARTMENT | 2999.83 | 3599.79 | 0.241 | 0.289 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
T S1 APARTMENT | 3071.12 | 3685.34 | 0.247 | 0.296 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
T S2 APARTMENT | 3072.18 | 3686.62 | 0.247 | 0.296 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1005.51 | 1206.62 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
G NW APARTMENT | 1005.58 | 1206.70 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
OFFICE | 1330.91 | 1597.09 | 0.061 | 0.073 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 6.30 | 0.00607 |
G NE APARTMENT | 1007.24 | 1208.69 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
G N1 APARTMENT | 575.63 | 690.75 | 0.026 | 0.032 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
G N2 APARTMENT | 575.67 | 690.80 | 0.026 | 0.032 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
G S1 APARTMENT | 573.05 | 687.66 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
G S2 APARTMENT | 578.92 | 694.71 | 0.026 | 0.032 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
F2 SW APARTMENT | 1015.15 | 1218.18 | 0.046 | 0.056 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 NW APARTMENT | 1014.56 | 1217.47 | 0.046 | 0.056 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 SE APARTMENT | 1038.64 | 1246.37 | 0.047 | 0.057 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 NE APARTMENT | 1017.16 | 1220.59 | 0.046 | 0.056 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 N1 APARTMENT | 499.37 | 599.24 | 0.023 | 0.027 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 N2 APARTMENT | 499.44 | 599.32 | 0.023 | 0.027 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 S1 APARTMENT | 501.34 | 601.61 | 0.023 | 0.027 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F2 S2 APARTMENT | 502.83 | 603.40 | 0.023 | 0.028 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 SW APARTMENT | 973.37 | 1168.04 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 NW APARTMENT | 973.36 | 1168.03 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 SE APARTMENT | 978.74 | 1174.49 | 0.045 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 NE APARTMENT | 976.37 | 1171.64 | 0.045 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 N1 APARTMENT | 456.62 | 547.94 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 N2 APARTMENT | 456.69 | 548.03 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 S1 APARTMENT | 456.24 | 547.49 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F3 S2 APARTMENT | 456.55 | 547.86 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 SW APARTMENT | 961.85 | 1154.22 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 NW APARTMENT | 962.19 | 1154.62 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 SE APARTMENT | 965.41 | 1158.50 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 NE APARTMENT | 965.49 | 1158.59 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 N1 APARTMENT | 442.99 | 531.59 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 N2 APARTMENT | 443.08 | 531.69 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 S1 APARTMENT | 442.03 | 530.44 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F4 S2 APARTMENT | 442.15 | 530.58 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M SW APARTMENT | 936.48 | 1123.77 | 0.043 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M NW APARTMENT | 935.94 | 1123.13 | 0.043 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M SE APARTMENT | 940.04 | 1128.05 | 0.043 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M NE APARTMENT | 939.47 | 1127.36 | 0.043 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M N1 APARTMENT | 416.94 | 500.33 | 0.019 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M N2 APARTMENT | 417.03 | 500.44 | 0.019 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M S1 APARTMENT | 416.81 | 500.17 | 0.019 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
M S2 APARTMENT | 416.90 | 500.29 | 0.019 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 SW APARTMENT | 970.65 | 1164.78 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 NW APARTMENT | 970.97 | 1165.16 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 SE APARTMENT | 974.38 | 1169.25 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 NE APARTMENT | 974.68 | 1169.62 | 0.044 | 0.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 N1 APARTMENT | 448.14 | 537.77 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 N2 APARTMENT | 448.23 | 537.88 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 S1 APARTMENT | 447.14 | 536.57 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F6 S2 APARTMENT | 447.24 | 536.69 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 SW APARTMENT | 985.15 | 1182.18 | 0.045 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 NW APARTMENT | 985.27 | 1182.32 | 0.045 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 SE APARTMENT | 989.02 | 1186.83 | 0.045 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 NE APARTMENT | 989.13 | 1186.96 | 0.045 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 N1 APARTMENT | 461.01 | 553.21 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 N2 APARTMENT | 461.11 | 553.33 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 S1 APARTMENT | 460.21 | 552.25 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F7 S2 APARTMENT | 460.31 | 552.37 | 0.021 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 SW APARTMENT | 1002.16 | 1202.59 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 NW APARTMENT | 1001.89 | 1202.27 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 SE APARTMENT | 1006.16 | 1207.39 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 NE APARTMENT | 1005.89 | 1207.06 | 0.046 | 0.055 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 N1 APARTMENT | 476.67 | 572.00 | 0.022 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 N2 APARTMENT | 476.77 | 572.12 | 0.022 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 S1 APARTMENT | 476.25 | 571.50 | 0.022 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F8 S2 APARTMENT | 476.35 | 571.62 | 0.022 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 SW APARTMENT | 1093.43 | 1312.11 | 0.050 | 0.060 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 NW APARTMENT | 1090.88 | 1309.05 | 0.050 | 0.060 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 SE APARTMENT | 1097.57 | 1317.09 | 0.050 | 0.060 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 NE APARTMENT | 1095.02 | 1314.02 | 0.050 | 0.060 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 N1 APARTMENT | 559.24 | 671.09 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 N2 APARTMENT | 559.35 | 671.21 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 S1 APARTMENT | 560.85 | 673.02 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
F9 S2 APARTMENT | 560.96 | 673.15 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T SW APARTMENT | 1396.57 | 1675.88 | 0.064 | 0.077 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T NW APARTMENT | 1398.67 | 1678.41 | 0.064 | 0.077 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T SE APARTMENT | 1400.43 | 1680.52 | 0.064 | 0.077 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T NE APARTMENT | 1402.54 | 1683.05 | 0.064 | 0.077 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T N1 APARTMENT | 911.65 | 1093.98 | 0.042 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T N2 APARTMENT | 911.76 | 1094.11 | 0.042 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T S1 APARTMENT | 907.16 | 1088.59 | 0.041 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
T S2 APARTMENT | 907.27 | 1088.72 | 0.041 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP G NW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP OFFICE | 0.36 | 0.36 | 0.07 | 0.07 |
AIRLOOP G NE | 0.25 | 0.25 | 0.06 | 0.06 |
AIRLOOP G N1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP G N2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP G S1 | 0.17 | 0.17 | 0.03 | 0.03 |
AIRLOOP G S2 | 0.17 | 0.17 | 0.03 | 0.03 |
AIRLOOP F2 SW | 0.36 | 0.36 | 0.06 | 0.06 |
AIRLOOP F2 NW | 0.36 | 0.36 | 0.06 | 0.06 |
AIRLOOP F2 SE | 0.33 | 0.33 | 0.06 | 0.06 |
AIRLOOP F2 NE | 0.31 | 0.31 | 0.06 | 0.06 |
AIRLOOP F2 N1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F2 N2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F2 S1 | 0.21 | 0.21 | 0.03 | 0.03 |
AIRLOOP F2 S2 | 0.21 | 0.21 | 0.03 | 0.03 |
AIRLOOP F3 SW | 0.36 | 0.36 | 0.05 | 0.05 |
AIRLOOP F3 NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F3 SE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F3 NE | 0.31 | 0.31 | 0.05 | 0.05 |
AIRLOOP F3 N1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F3 N2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F3 S1 | 0.21 | 0.21 | 0.03 | 0.03 |
AIRLOOP F3 S2 | 0.21 | 0.21 | 0.03 | 0.03 |
AIRLOOP F4 SW | 0.36 | 0.36 | 0.05 | 0.05 |
AIRLOOP F4 NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F4 SE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F4 NE | 0.31 | 0.31 | 0.05 | 0.05 |
AIRLOOP F4 N1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F4 N2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F4 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F4 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP M SW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP M NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP M SE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP M NE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP M N1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.36 | 0.36 | 0.05 | 0.05 |
AIRLOOP F6 NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F6 SE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F6 NE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F6 N1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F6 N2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F6 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F6 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F7 SW | 0.36 | 0.36 | 0.05 | 0.05 |
AIRLOOP F7 NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F7 SE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F7 NE | 0.32 | 0.32 | 0.05 | 0.05 |
AIRLOOP F7 N1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F7 N2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F7 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F7 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F8 SW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F8 NW | 0.37 | 0.37 | 0.05 | 0.05 |
AIRLOOP F8 SE | 0.32 | 0.32 | 0.06 | 0.06 |
AIRLOOP F8 NE | 0.32 | 0.32 | 0.06 | 0.06 |
AIRLOOP F8 N1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F8 N2 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F8 S1 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F8 S2 | 0.22 | 0.22 | 0.03 | 0.03 |
AIRLOOP F9 SW | 0.38 | 0.38 | 0.06 | 0.06 |
AIRLOOP F9 NW | 0.38 | 0.38 | 0.06 | 0.06 |
AIRLOOP F9 SE | 0.33 | 0.33 | 0.06 | 0.06 |
AIRLOOP F9 NE | 0.33 | 0.33 | 0.06 | 0.06 |
AIRLOOP F9 N1 | 0.24 | 0.24 | 0.03 | 0.03 |
AIRLOOP F9 N2 | 0.24 | 0.24 | 0.03 | 0.03 |
AIRLOOP F9 S1 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP F9 S2 | 0.23 | 0.23 | 0.03 | 0.03 |
AIRLOOP T SW | 0.45 | 0.45 | 0.08 | 0.08 |
AIRLOOP T NW | 0.45 | 0.45 | 0.08 | 0.08 |
AIRLOOP T SE | 0.40 | 0.40 | 0.08 | 0.08 |
AIRLOOP T NE | 0.39 | 0.39 | 0.08 | 0.08 |
AIRLOOP T N1 | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP T N2 | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP T S1 | 0.30 | 0.30 | 0.05 | 0.05 |
AIRLOOP T S2 | 0.30 | 0.30 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 6183.75 | 3519.00 | 1684.75 |
G NW APARTMENT | 5525.75 | 4356.25 | 1790.50 |
OFFICE | 1991.00 | 140.50 | 62.75 |
G NE APARTMENT | 5553.00 | 4335.75 | 1744.75 |
G N1 APARTMENT | 5363.25 | 5026.25 | 2260.75 |
G N2 APARTMENT | 5361.75 | 5027.75 | 2265.75 |
G S1 APARTMENT | 6038.75 | 3704.25 | 1919.50 |
G S2 APARTMENT | 6071.00 | 3653.25 | 1899.00 |
F2 SW APARTMENT | 7210.50 | 1729.50 | 990.75 |
F2 NW APARTMENT | 6219.25 | 2842.25 | 1065.50 |
F2 SE APARTMENT | 7332.00 | 1574.75 | 876.75 |
F2 NE APARTMENT | 6238.50 | 2822.00 | 1010.25 |
F2 N1 APARTMENT | 6159.00 | 3113.25 | 1269.25 |
F2 N2 APARTMENT | 6158.25 | 3116.50 | 1269.25 |
F2 S1 APARTMENT | 7445.00 | 1609.00 | 1068.50 |
F2 S2 APARTMENT | 7460.75 | 1604.25 | 1068.00 |
F3 SW APARTMENT | 7478.25 | 1573.25 | 1005.50 |
F3 NW APARTMENT | 6401.75 | 2625.00 | 1071.75 |
F3 SE APARTMENT | 7510.75 | 1542.75 | 956.75 |
F3 NE APARTMENT | 6429.75 | 2604.25 | 1019.50 |
F3 N1 APARTMENT | 6385.25 | 2797.25 | 1255.75 |
F3 N2 APARTMENT | 6384.00 | 2803.00 | 1254.25 |
F3 S1 APARTMENT | 7783.25 | 1388.50 | 1065.75 |
F3 S2 APARTMENT | 7784.00 | 1387.25 | 1065.25 |
F4 SW APARTMENT | 7536.25 | 1551.50 | 1031.25 |
F4 NW APARTMENT | 6455.75 | 2569.75 | 1091.75 |
F4 SE APARTMENT | 7550.00 | 1516.50 | 962.25 |
F4 NE APARTMENT | 6482.50 | 2540.25 | 1044.25 |
F4 N1 APARTMENT | 6469.25 | 2686.25 | 1267.25 |
F4 N2 APARTMENT | 6466.00 | 2689.25 | 1265.75 |
F4 S1 APARTMENT | 7864.75 | 1361.25 | 1076.50 |
F4 S2 APARTMENT | 7861.00 | 1362.75 | 1076.75 |
M SW APARTMENT | 7582.00 | 1503.50 | 1015.00 |
M NW APARTMENT | 6503.50 | 2503.50 | 1083.25 |
M SE APARTMENT | 7596.75 | 1472.75 | 954.00 |
M NE APARTMENT | 6531.00 | 2470.00 | 1036.25 |
M N1 APARTMENT | 6539.50 | 2561.00 | 1228.50 |
M N2 APARTMENT | 6537.50 | 2565.50 | 1227.75 |
M S1 APARTMENT | 7920.00 | 1311.25 | 1054.50 |
M S2 APARTMENT | 7917.00 | 1314.75 | 1056.25 |
F6 SW APARTMENT | 7514.75 | 1621.50 | 1092.00 |
F6 NW APARTMENT | 6441.75 | 2644.50 | 1154.75 |
F6 SE APARTMENT | 7519.50 | 1582.75 | 1020.00 |
F6 NE APARTMENT | 6471.25 | 2619.50 | 1106.50 |
F6 N1 APARTMENT | 6463.50 | 2749.25 | 1330.50 |
F6 N2 APARTMENT | 6463.25 | 2754.25 | 1329.00 |
F6 S1 APARTMENT | 7846.00 | 1417.50 | 1131.50 |
F6 S2 APARTMENT | 7842.75 | 1418.50 | 1131.25 |
F7 SW APARTMENT | 7462.00 | 1685.25 | 1127.50 |
F7 NW APARTMENT | 6404.25 | 2727.75 | 1194.00 |
F7 SE APARTMENT | 7471.25 | 1651.75 | 1060.75 |
F7 NE APARTMENT | 6437.00 | 2714.75 | 1142.75 |
F7 N1 APARTMENT | 6420.25 | 2856.50 | 1378.00 |
F7 N2 APARTMENT | 6422.00 | 2861.75 | 1377.00 |
F7 S1 APARTMENT | 7795.25 | 1482.00 | 1177.25 |
F7 S2 APARTMENT | 7794.25 | 1483.75 | 1177.50 |
F8 SW APARTMENT | 7415.25 | 1735.00 | 1146.25 |
F8 NW APARTMENT | 6372.75 | 2792.50 | 1210.25 |
F8 SE APARTMENT | 7422.50 | 1696.75 | 1081.00 |
F8 NE APARTMENT | 6406.25 | 2773.75 | 1156.75 |
F8 N1 APARTMENT | 6388.75 | 2930.00 | 1394.75 |
F8 N2 APARTMENT | 6387.25 | 2934.75 | 1393.75 |
F8 S1 APARTMENT | 7747.25 | 1520.50 | 1190.25 |
F8 S2 APARTMENT | 7744.50 | 1524.00 | 1190.25 |
F9 SW APARTMENT | 7291.25 | 1775.75 | 1103.00 |
F9 NW APARTMENT | 6324.75 | 2824.25 | 1170.25 |
F9 SE APARTMENT | 7327.25 | 1730.00 | 1040.25 |
F9 NE APARTMENT | 6353.50 | 2802.50 | 1109.00 |
F9 N1 APARTMENT | 6338.00 | 2954.50 | 1327.50 |
F9 N2 APARTMENT | 6338.00 | 2957.50 | 1325.50 |
F9 S1 APARTMENT | 7620.75 | 1568.50 | 1152.25 |
F9 S2 APARTMENT | 7619.00 | 1561.25 | 1143.50 |
T SW APARTMENT | 6794.75 | 2511.75 | 1260.50 |
T NW APARTMENT | 6169.50 | 3224.00 | 1297.00 |
T SE APARTMENT | 6848.50 | 2466.00 | 1206.25 |
T NE APARTMENT | 6165.25 | 3187.25 | 1245.25 |
T N1 APARTMENT | 6167.75 | 3352.00 | 1451.75 |
T N2 APARTMENT | 6169.50 | 3341.50 | 1436.00 |
T S1 APARTMENT | 7026.50 | 2369.25 | 1362.75 |
T S2 APARTMENT | 7026.00 | 2371.75 | 1362.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 7987.75 | 5120.25 | 2354.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 31.50 | 0.00 | 31.50 |
G NW APARTMENT | 0.00 | 30.75 | 0.00 | 30.75 |
OFFICE | 0.25 | 0.25 | 0.00 | 0.00 |
G NE APARTMENT | 0.00 | 38.75 | 0.00 | 38.75 |
G N1 APARTMENT | 3.75 | 99.75 | 3.75 | 99.75 |
G N2 APARTMENT | 2.50 | 101.50 | 2.50 | 101.50 |
G S1 APARTMENT | 0.00 | 320.00 | 0.00 | 320.00 |
G S2 APARTMENT | 0.00 | 265.00 | 0.00 | 265.00 |
F2 SW APARTMENT | 0.00 | 16.25 | 0.00 | 16.25 |
F2 NW APARTMENT | 0.00 | 16.50 | 0.00 | 16.50 |
F2 SE APARTMENT | 0.00 | 4.75 | 0.00 | 4.75 |
F2 NE APARTMENT | 0.00 | 14.00 | 0.00 | 14.00 |
F2 N1 APARTMENT | 0.25 | 43.50 | 0.25 | 43.50 |
F2 N2 APARTMENT | 0.25 | 44.25 | 0.25 | 44.25 |
F2 S1 APARTMENT | 0.00 | 239.75 | 0.00 | 239.75 |
F2 S2 APARTMENT | 0.00 | 225.25 | 0.00 | 225.25 |
F3 SW APARTMENT | 0.00 | 17.75 | 0.00 | 17.75 |
F3 NW APARTMENT | 0.00 | 16.25 | 0.00 | 16.25 |
F3 SE APARTMENT | 0.00 | 29.25 | 0.00 | 29.25 |
F3 NE APARTMENT | 0.00 | 13.75 | 0.00 | 13.75 |
F3 N1 APARTMENT | 0.00 | 42.75 | 0.00 | 42.75 |
F3 N2 APARTMENT | 0.00 | 43.50 | 0.00 | 43.50 |
F3 S1 APARTMENT | 0.00 | 261.50 | 0.00 | 261.50 |
F3 S2 APARTMENT | 0.00 | 256.00 | 0.00 | 256.00 |
F4 SW APARTMENT | 0.00 | 16.25 | 0.00 | 16.25 |
F4 NW APARTMENT | 0.00 | 15.25 | 0.00 | 15.25 |
F4 SE APARTMENT | 0.00 | 21.75 | 0.00 | 21.75 |
F4 NE APARTMENT | 0.00 | 14.50 | 0.00 | 14.50 |
F4 N1 APARTMENT | 0.00 | 42.00 | 0.00 | 42.00 |
F4 N2 APARTMENT | 0.00 | 42.75 | 0.00 | 42.75 |
F4 S1 APARTMENT | 0.00 | 249.25 | 0.00 | 249.25 |
F4 S2 APARTMENT | 0.00 | 247.50 | 0.00 | 247.50 |
M SW APARTMENT | 0.00 | 14.50 | 0.00 | 14.50 |
M NW APARTMENT | 0.00 | 14.75 | 0.00 | 14.75 |
M SE APARTMENT | 0.00 | 18.75 | 0.00 | 18.75 |
M NE APARTMENT | 0.00 | 15.00 | 0.00 | 15.00 |
M N1 APARTMENT | 0.00 | 40.75 | 0.00 | 40.75 |
M N2 APARTMENT | 0.00 | 41.00 | 0.00 | 41.00 |
M S1 APARTMENT | 0.00 | 230.25 | 0.00 | 230.25 |
M S2 APARTMENT | 0.00 | 229.00 | 0.00 | 229.00 |
F6 SW APARTMENT | 0.00 | 14.50 | 0.00 | 14.50 |
F6 NW APARTMENT | 0.00 | 16.00 | 0.00 | 16.00 |
F6 SE APARTMENT | 0.00 | 18.75 | 0.00 | 18.75 |
F6 NE APARTMENT | 0.00 | 17.00 | 0.00 | 17.00 |
F6 N1 APARTMENT | 0.00 | 40.25 | 0.00 | 40.25 |
F6 N2 APARTMENT | 0.00 | 40.75 | 0.00 | 40.75 |
F6 S1 APARTMENT | 0.00 | 218.00 | 0.00 | 218.00 |
F6 S2 APARTMENT | 0.00 | 215.25 | 0.00 | 215.25 |
F7 SW APARTMENT | 0.00 | 13.50 | 0.00 | 13.50 |
F7 NW APARTMENT | 0.00 | 14.75 | 0.00 | 14.75 |
F7 SE APARTMENT | 0.00 | 18.00 | 0.00 | 18.00 |
F7 NE APARTMENT | 0.00 | 18.75 | 0.00 | 18.75 |
F7 N1 APARTMENT | 0.00 | 40.00 | 0.00 | 40.00 |
F7 N2 APARTMENT | 0.00 | 41.00 | 0.00 | 41.00 |
F7 S1 APARTMENT | 0.00 | 204.00 | 0.00 | 204.00 |
F7 S2 APARTMENT | 0.00 | 201.50 | 0.00 | 201.50 |
F8 SW APARTMENT | 0.00 | 12.75 | 0.00 | 12.75 |
F8 NW APARTMENT | 0.00 | 13.75 | 0.00 | 13.75 |
F8 SE APARTMENT | 0.00 | 15.75 | 0.00 | 15.75 |
F8 NE APARTMENT | 0.00 | 18.75 | 0.00 | 18.75 |
F8 N1 APARTMENT | 0.00 | 40.25 | 0.00 | 40.25 |
F8 N2 APARTMENT | 0.00 | 40.75 | 0.00 | 40.75 |
F8 S1 APARTMENT | 0.00 | 183.75 | 0.00 | 183.75 |
F8 S2 APARTMENT | 0.00 | 182.50 | 0.00 | 182.50 |
F9 SW APARTMENT | 0.00 | 10.00 | 0.00 | 10.00 |
F9 NW APARTMENT | 0.00 | 14.00 | 0.00 | 14.00 |
F9 SE APARTMENT | 0.00 | 11.75 | 0.00 | 11.75 |
F9 NE APARTMENT | 0.00 | 8.25 | 0.00 | 8.25 |
F9 N1 APARTMENT | 0.00 | 34.50 | 0.00 | 34.50 |
F9 N2 APARTMENT | 0.00 | 35.50 | 0.00 | 35.50 |
F9 S1 APARTMENT | 0.00 | 139.50 | 0.00 | 139.50 |
F9 S2 APARTMENT | 0.00 | 133.75 | 0.00 | 133.75 |
T SW APARTMENT | 0.00 | 19.75 | 0.00 | 19.75 |
T NW APARTMENT | 0.00 | 20.50 | 0.00 | 20.50 |
T SE APARTMENT | 0.00 | 7.00 | 0.00 | 7.00 |
T NE APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T N1 APARTMENT | 0.00 | 27.75 | 0.00 | 27.75 |
T N2 APARTMENT | 0.00 | 23.75 | 0.00 | 23.75 |
T S1 APARTMENT | 0.00 | 72.75 | 0.00 | 72.75 |
T S2 APARTMENT | 0.00 | 73.75 | 0.00 | 73.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 5.75 | 456.75 | 5.50 | 456.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.036 | 0.000 | 0.275 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.036 | 0.000 | 0.259 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.527 | 0.052 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.036 | 0.000 | 0.259 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.022 | 0.000 | 0.251 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.022 | 0.000 | 0.251 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.022 | 0.000 | 0.273 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.022 | 0.000 | 0.273 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.051 | 0.000 | 0.294 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.051 | 0.000 | 0.281 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.051 | 0.000 | 0.295 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.051 | 0.000 | 0.281 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.031 | 0.000 | 0.277 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.031 | 0.000 | 0.277 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.031 | 0.000 | 0.294 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.031 | 0.000 | 0.294 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.061 | 0.000 | 0.305 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.061 | 0.000 | 0.293 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.061 | 0.000 | 0.306 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.061 | 0.000 | 0.293 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.037 | 0.000 | 0.290 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.037 | 0.000 | 0.290 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.037 | 0.000 | 0.305 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.037 | 0.000 | 0.305 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.068 | 0.000 | 0.312 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.068 | 0.000 | 0.300 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.068 | 0.000 | 0.312 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.068 | 0.000 | 0.300 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.041 | 0.000 | 0.297 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.041 | 0.000 | 0.297 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.041 | 0.000 | 0.311 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.041 | 0.000 | 0.311 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.074 | 0.000 | 0.317 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.074 | 0.000 | 0.306 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.074 | 0.000 | 0.318 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.074 | 0.000 | 0.306 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.045 | 0.000 | 0.303 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.045 | 0.000 | 0.303 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.045 | 0.000 | 0.317 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.045 | 0.000 | 0.317 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.079 | 0.000 | 0.323 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.079 | 0.000 | 0.310 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.079 | 0.000 | 0.323 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.079 | 0.000 | 0.310 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.048 | 0.000 | 0.307 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.048 | 0.000 | 0.307 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.048 | 0.000 | 0.322 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.048 | 0.000 | 0.322 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.083 | 0.000 | 0.327 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.083 | 0.000 | 0.314 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.083 | 0.000 | 0.328 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.083 | 0.000 | 0.314 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.050 | 0.000 | 0.311 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.050 | 0.000 | 0.311 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.050 | 0.000 | 0.327 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.050 | 0.000 | 0.327 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.087 | 0.000 | 0.334 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.087 | 0.000 | 0.320 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.087 | 0.000 | 0.334 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.087 | 0.000 | 0.320 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.053 | 0.000 | 0.317 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.053 | 0.000 | 0.317 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.053 | 0.000 | 0.333 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.053 | 0.000 | 0.333 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.091 | 0.000 | 0.337 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.091 | 0.000 | 0.322 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.091 | 0.000 | 0.337 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.091 | 0.000 | 0.322 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.055 | 0.000 | 0.319 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.055 | 0.000 | 0.319 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.055 | 0.000 | 0.337 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.055 | 0.000 | 0.337 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.094 | 0.000 | 0.338 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.094 | 0.000 | 0.325 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.094 | 0.000 | 0.339 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.094 | 0.000 | 0.326 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.057 | 0.000 | 0.322 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.057 | 0.000 | 0.322 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.360 | 0.057 | 0.000 | 0.338 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.057 | 0.000 | 0.338 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.485 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.330 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.330 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.329 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.327 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.328 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 807.36 | 25601.20 | 01-JAN-06:15 | 25601.20 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 2145.53 | 25981.73 | 12-JAN-03:15 | 124109.77 | 01-JUL-16:45 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
ElectricityPurchased:Plant | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
Cogeneration:ElectricityPurchased | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
ElectricityNet:Plant | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
Cogeneration:ElectricityNet | 3989.90 | 63542.21 | 12-JAN-03:15 | 208969.32 | 01-JUL-17:15 |
ExteriorLights:Electricity | 168.54 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.54 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 807.36 | 25601.20 | 01-JAN-06:15 | 25601.20 | 01-JAN-00:15 |
Cooling:Electricity | 1315.56 | 0.00 | 01-JAN-00:15 | 97362.94 | 01-JUL-16:45 |
Heating:Electricity | 1.78 | 0.00 | 01-JAN-11:00 | 13266.21 | 09-FEB-20:15 |
Electricity:Plant | 128.33 | 36.93 | 08-JAN-18:45 | 5899.29 | 09-MAY-16:15 |
HeatRejection:Electricity | 64.63 | 0.00 | 01-JAN-00:15 | 3835.78 | 09-MAY-16:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 63.70 | 36.93 | 08-JAN-18:45 | 2063.51 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 816.51 | 9260.51 | 01-JAN-00:15 | 79739.68 | 10-JAN-08:00 |
Gas:Plant | 816.51 | 9260.51 | 01-JAN-00:15 | 79739.68 | 10-JAN-08:00 |
WaterSystems:Gas | 816.51 | 9260.51 | 01-JAN-00:15 | 79739.68 | 10-JAN-08:00 |
Water Heater:WaterSystems:Gas | 816.51 | 9260.51 | 01-JAN-00:15 | 79739.68 | 10-JAN-08:00 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler:Heating:Gas | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 5829.13 | 0.00 | 01-JAN-00:15 | 446058.96 | 01-JUL-17:15 |
PlantLoopCoolingDemand:HVAC | 5829.13 | 0.00 | 01-JAN-00:15 | 446058.96 | 01-JUL-17:15 |
CoolingCoils:PlantLoopCoolingDemand | 5829.13 | 0.00 | 01-JAN-00:15 | 446058.96 | 01-JUL-17:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 8636.43 | 0.00 | 01-JAN-02:15 | 0.00 | 07-JUN-17:15 |
Water:Plant | 8636.43 | 0.00 | 01-JAN-02:15 | 0.00 | 07-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 8636.43 | 0.00 | 01-JAN-02:15 | 0.00 | 07-JUN-17:15 |
MainsWater:Plant | 8636.43 | 0.00 | 01-JAN-02:15 | 0.00 | 07-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 3857.91 | 0.00 | 01-JAN-00:15 | 0.00 | 07-JUN-16:30 |
HeatRejection:MainsWater | 3857.91 | 0.00 | 01-JAN-00:15 | 0.00 | 07-JUN-16:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 622.06 | 295.81 | 19-JUL-01:15 | 69981.87 | 09-FEB-20:15 |
PlantLoopHeatingDemand:Plant | 617.66 | 295.81 | 19-JUL-01:15 | 46306.80 | 18-JAN-07:15 |
WaterSystems:PlantLoopHeatingDemand | 617.66 | 295.81 | 19-JUL-01:15 | 46306.80 | 18-JAN-07:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 8028.39 | 6575.13 | 27-FEB-03:00 | 612354.12 | 06-JUN-16:15 |
EnergyTransfer:Building | 2812.44 | 4566.28 | 11-FEB-21:00 | 259793.60 | 06-JUN-16:15 |
EnergyTransfer:Zone:G SW APARTMENT | 29.43 | 0.00 | 18-DEC-04:45 | 3514.10 | 01-OCT-15:15 |
Heating:EnergyTransfer | 39.95 | 0.00 | 03-FEB-20:30 | 58973.60 | 09-FEB-20:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.69 | 0.00 | 01-JAN-08:45 | 840.07 | 09-FEB-20:30 |
Cooling:EnergyTransfer | 2772.49 | 0.00 | 01-JAN-15:00 | 259793.60 | 06-JUN-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 28.74 | 0.00 | 01-JAN-00:15 | 3514.10 | 01-OCT-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 24.59 | 0.00 | 03-DEC-16:00 | 3511.90 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.42 | 0.00 | 01-JAN-19:45 | 854.50 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 23.17 | 0.00 | 01-JAN-00:15 | 3511.90 | 07-JUN-16:30 |
EnergyTransfer:Zone:OFFICE | 34.70 | 0.04 | 15-NOV-22:15 | 4054.46 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.29 | 0.00 | 01-JAN-08:45 | 479.11 | 02-JAN-07:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 34.41 | 0.00 | 01-JAN-00:15 | 4054.46 | 28-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 24.00 | 0.00 | 01-MAR-06:45 | 2859.52 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.08 | 0.00 | 01-JAN-09:30 | 864.56 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 22.92 | 0.00 | 01-JAN-00:15 | 2859.52 | 07-JUN-16:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 17.00 | 0.02 | 10-JAN-02:45 | 2001.05 | 07-JUN-17:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.55 | 0.00 | 01-JAN-09:45 | 656.56 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 16.45 | 0.00 | 01-JAN-00:15 | 2001.05 | 07-JUN-17:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 16.99 | 0.05 | 25-FEB-04:15 | 1989.98 | 07-JUN-17:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.54 | 0.00 | 01-JAN-09:45 | 657.65 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 16.45 | 0.00 | 01-JAN-00:15 | 1989.98 | 07-JUN-17:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 22.27 | 0.00 | 20-MAR-00:30 | 2154.34 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 603.16 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 22.15 | 0.00 | 01-JAN-13:30 | 2154.34 | 27-NOV-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 22.56 | 0.06 | 15-DEC-13:45 | 2182.62 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 572.99 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 22.44 | 0.00 | 01-JAN-13:30 | 2182.62 | 27-NOV-13:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 43.02 | 0.07 | 08-DEC-03:00 | 4299.13 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 500.09 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 42.61 | 0.00 | 01-JAN-13:30 | 4299.13 | 27-APR-15:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 34.86 | 0.01 | 20-DEC-01:00 | 4267.46 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 1.11 | 0.00 | 01-JAN-23:00 | 621.69 | 22-DEC-08:15 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 33.75 | 0.00 | 01-JAN-00:15 | 4267.46 | 05-MAY-16:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 44.05 | 0.00 | 27-NOV-02:00 | 3882.65 | 01-OCT-14:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 384.83 | 29-DEC-06:15 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 43.77 | 0.00 | 01-JAN-05:00 | 3882.65 | 01-OCT-14:00 |
EnergyTransfer:Zone:F2 NE APARTMENT | 34.34 | 0.02 | 03-MAR-07:00 | 3506.23 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 0.78 | 0.00 | 01-JAN-08:00 | 652.50 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 33.56 | 0.00 | 01-JAN-00:15 | 3506.23 | 06-JUN-16:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 25.55 | 0.04 | 26-JAN-01:00 | 2474.53 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 490.61 | 01-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 25.18 | 0.00 | 01-JAN-03:45 | 2474.53 | 07-JUN-16:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 25.55 | 0.11 | 26-JAN-01:00 | 2466.35 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 491.95 | 01-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 25.18 | 0.00 | 01-JAN-03:45 | 2466.35 | 07-JUN-16:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 34.26 | 0.08 | 25-JAN-10:15 | 2896.22 | 27-NOV-13:00 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 176.96 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 34.19 | 0.00 | 01-JAN-13:30 | 2896.22 | 27-NOV-13:00 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 34.35 | 0.24 | 25-JAN-10:15 | 2905.24 | 27-NOV-13:00 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 157.77 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 34.28 | 0.00 | 01-JAN-13:30 | 2905.24 | 27-NOV-13:00 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 44.55 | 0.02 | 07-FEB-04:15 | 4312.54 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 527.17 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 44.20 | 0.00 | 01-JAN-13:30 | 4312.54 | 27-APR-15:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 36.02 | 0.04 | 01-DEC-05:30 | 4279.83 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 0.94 | 0.00 | 01-JAN-22:45 | 640.20 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 35.08 | 0.00 | 01-JAN-00:15 | 4279.83 | 05-MAY-16:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 44.53 | 0.02 | 27-DEC-00:30 | 3737.22 | 01-OCT-14:15 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 536.16 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 44.30 | 0.00 | 01-JAN-13:30 | 3737.22 | 01-OCT-14:15 |
EnergyTransfer:Zone:F3 NE APARTMENT | 35.60 | 0.01 | 06-FEB-23:15 | 3540.07 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 0.66 | 0.00 | 01-JAN-07:45 | 674.85 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 34.94 | 0.00 | 01-JAN-00:15 | 3540.07 | 06-JUN-16:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 27.01 | 0.23 | 11-JAN-24:00 | 2512.03 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 383.26 | 01-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 26.69 | 0.00 | 01-JAN-13:15 | 2512.03 | 05-MAY-17:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 27.01 | 0.19 | 31-DEC-13:45 | 2501.77 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 386.17 | 01-JAN-16:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 26.70 | 0.00 | 01-JAN-13:30 | 2501.77 | 05-MAY-17:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 36.20 | 0.02 | 24-JAN-11:15 | 2942.86 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 170.93 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 36.14 | 0.00 | 01-JAN-13:30 | 2942.86 | 27-NOV-12:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 36.22 | 0.01 | 01-MAR-09:30 | 2947.26 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 170.46 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 36.17 | 0.00 | 01-JAN-13:30 | 2947.26 | 27-NOV-12:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 44.94 | 0.20 | 22-DEC-02:15 | 4333.39 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 657.96 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 44.60 | 0.00 | 01-JAN-13:45 | 4333.39 | 27-APR-15:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 36.38 | 0.08 | 07-DEC-06:45 | 4300.18 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 0.91 | 0.00 | 01-JAN-08:00 | 750.92 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 35.47 | 0.00 | 01-JAN-00:15 | 4300.18 | 05-MAY-16:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 44.83 | 0.01 | 21-NOV-04:45 | 3781.66 | 15-APR-13:45 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 686.57 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 44.60 | 0.00 | 01-JAN-13:45 | 3781.66 | 15-APR-13:45 |
EnergyTransfer:Zone:F4 NE APARTMENT | 35.99 | 0.03 | 19-DEC-21:30 | 3570.87 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 0.64 | 0.00 | 01-JAN-07:30 | 783.88 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 35.35 | 0.00 | 01-JAN-00:15 | 3570.87 | 06-JUN-16:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 27.47 | 0.04 | 12-JAN-00:45 | 2552.83 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 416.52 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 27.16 | 0.00 | 01-JAN-13:30 | 2552.83 | 05-MAY-17:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 27.47 | 0.02 | 26-JAN-00:45 | 2542.54 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 419.38 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 27.17 | 0.00 | 01-JAN-13:30 | 2542.54 | 05-MAY-17:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 36.73 | 0.13 | 16-DEC-19:00 | 2973.32 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 301.61 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 36.67 | 0.00 | 01-JAN-13:45 | 2973.32 | 27-NOV-12:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 36.73 | 0.20 | 26-DEC-10:45 | 2976.53 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 303.77 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 36.68 | 0.00 | 01-JAN-13:45 | 2976.53 | 27-NOV-12:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 45.69 | 0.02 | 24-NOV-04:15 | 4377.98 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 765.63 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 45.35 | 0.00 | 01-JAN-13:45 | 4377.98 | 27-APR-15:30 |
EnergyTransfer:Zone:M NW APARTMENT | 37.12 | 0.02 | 10-NOV-22:00 | 4351.30 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.91 | 0.00 | 01-JAN-07:45 | 845.62 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 36.22 | 0.00 | 01-JAN-00:15 | 4351.30 | 05-MAY-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 45.58 | 0.00 | 25-DEC-01:15 | 3837.71 | 15-APR-13:45 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 795.93 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 45.34 | 0.00 | 01-JAN-13:45 | 3837.71 | 15-APR-13:45 |
EnergyTransfer:Zone:M NE APARTMENT | 36.74 | 0.01 | 02-FEB-23:30 | 3625.43 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.63 | 0.00 | 01-JAN-00:15 | 877.76 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 36.11 | 0.00 | 01-JAN-00:30 | 3625.43 | 06-JUN-16:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 28.26 | 0.07 | 03-JAN-11:15 | 2606.71 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 500.26 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 27.95 | 0.00 | 01-JAN-13:15 | 2606.71 | 05-MAY-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 28.26 | 0.11 | 31-DEC-13:30 | 2596.48 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 502.92 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 27.96 | 0.00 | 01-JAN-13:30 | 2596.48 | 05-MAY-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 37.57 | 0.21 | 19-JAN-11:45 | 3021.41 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 403.81 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 37.51 | 0.00 | 01-JAN-13:45 | 3021.41 | 27-NOV-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 37.58 | 0.05 | 03-FEB-19:00 | 3023.99 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 406.22 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 37.52 | 0.00 | 01-JAN-13:45 | 3023.99 | 27-NOV-12:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 44.76 | 0.04 | 25-DEC-07:30 | 4349.87 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 930.42 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 44.39 | 0.00 | 01-JAN-13:45 | 4349.87 | 27-APR-15:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 36.40 | 0.03 | 20-DEC-23:30 | 4332.64 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 0.95 | 0.00 | 01-JAN-08:00 | 1004.28 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 35.44 | 0.00 | 01-JAN-00:15 | 4332.64 | 05-MAY-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 44.64 | 0.07 | 11-DEC-01:30 | 3821.00 | 15-APR-13:45 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 959.32 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 44.39 | 0.00 | 01-JAN-13:45 | 3821.00 | 15-APR-13:45 |
EnergyTransfer:Zone:F6 NE APARTMENT | 36.01 | 0.01 | 08-JAN-19:45 | 3606.13 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 0.67 | 0.00 | 01-JAN-07:30 | 1035.78 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 35.34 | 0.00 | 01-JAN-00:15 | 3606.13 | 05-MAY-16:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 27.52 | 0.08 | 03-JAN-11:15 | 2591.28 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 656.94 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 27.20 | 0.00 | 01-JAN-13:15 | 2591.28 | 05-MAY-17:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 27.52 | 0.07 | 01-JAN-17:00 | 2581.07 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 659.52 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 27.20 | 0.00 | 01-JAN-13:30 | 2581.07 | 05-MAY-17:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 36.62 | 0.29 | 30-DEC-13:15 | 2994.16 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 568.71 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 36.56 | 0.00 | 01-JAN-13:45 | 2994.16 | 27-NOV-12:45 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 36.63 | 0.05 | 06-DEC-18:15 | 2996.70 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 570.98 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 36.56 | 0.00 | 01-JAN-13:45 | 2996.70 | 27-NOV-12:45 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 44.38 | 0.02 | 17-JAN-09:15 | 4347.43 | 27-APR-15:15 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 1063.46 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 44.00 | 0.00 | 01-JAN-13:45 | 4347.43 | 27-APR-15:15 |
EnergyTransfer:Zone:F7 NW APARTMENT | 36.19 | 0.01 | 23-DEC-02:15 | 4333.23 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 1.00 | 0.00 | 01-JAN-23:00 | 1133.54 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 35.19 | 0.00 | 01-JAN-00:15 | 4333.23 | 05-MAY-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 44.27 | 0.15 | 14-JAN-01:30 | 3828.20 | 15-APR-13:45 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.26 | 0.00 | 01-JAN-00:15 | 1091.07 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 44.00 | 0.00 | 01-JAN-13:45 | 3828.20 | 15-APR-13:45 |
EnergyTransfer:Zone:F7 NE APARTMENT | 35.80 | 0.04 | 10-DEC-00:30 | 3623.60 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 0.71 | 0.00 | 01-JAN-07:30 | 1162.79 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 35.09 | 0.00 | 01-JAN-00:15 | 3623.60 | 05-MAY-16:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 27.29 | 0.03 | 26-JAN-13:45 | 2598.10 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 784.11 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 26.95 | 0.00 | 01-JAN-13:15 | 2598.10 | 05-MAY-17:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 27.29 | 0.11 | 03-JAN-11:15 | 2587.92 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 786.47 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 26.96 | 0.00 | 01-JAN-13:15 | 2587.92 | 05-MAY-17:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 36.25 | 0.02 | 13-DEC-09:15 | 2991.23 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 699.85 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 36.18 | 0.00 | 01-JAN-13:45 | 2991.23 | 27-NOV-12:45 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 36.25 | 0.27 | 13-DEC-09:15 | 2993.65 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 702.00 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 36.18 | 0.00 | 01-JAN-13:45 | 2993.65 | 27-NOV-12:45 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 44.28 | 0.03 | 01-DEC-04:45 | 4361.39 | 27-APR-15:15 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 1183.20 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 43.87 | 0.00 | 01-JAN-13:45 | 4361.39 | 27-APR-15:15 |
EnergyTransfer:Zone:F8 NW APARTMENT | 36.24 | 0.06 | 03-MAR-07:30 | 4347.04 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 1.05 | 0.00 | 01-JAN-23:00 | 1248.73 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 35.19 | 0.00 | 01-JAN-00:15 | 4347.04 | 05-MAY-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 44.16 | 0.01 | 01-MAR-07:00 | 3849.95 | 15-APR-13:45 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1207.47 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 43.88 | 0.00 | 01-JAN-13:45 | 3849.95 | 15-APR-13:45 |
EnergyTransfer:Zone:F8 NE APARTMENT | 35.84 | 0.01 | 10-JAN-20:30 | 3652.92 | 05-MAY-16:30 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 0.75 | 0.00 | 01-JAN-07:30 | 1274.63 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 35.09 | 0.00 | 01-JAN-00:15 | 3652.92 | 05-MAY-16:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 27.32 | 0.15 | 25-DEC-15:30 | 2618.03 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 898.19 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 26.96 | 0.00 | 01-JAN-13:15 | 2618.03 | 05-MAY-17:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 27.32 | 0.05 | 27-DEC-12:30 | 2607.90 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 900.22 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 26.97 | 0.00 | 01-JAN-13:15 | 2607.90 | 05-MAY-17:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 36.14 | 0.25 | 09-DEC-12:45 | 2999.65 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 818.16 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 36.06 | 0.00 | 01-JAN-13:45 | 2999.65 | 27-NOV-12:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 36.14 | 0.08 | 27-FEB-19:45 | 3004.39 | 27-NOV-12:45 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 820.03 | 09-FEB-20:30 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 36.07 | 0.00 | 01-JAN-13:45 | 3004.39 | 27-NOV-12:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 44.97 | 0.03 | 23-NOV-06:45 | 4486.98 | 27-APR-15:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1244.11 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 44.49 | 0.00 | 01-JAN-11:15 | 4486.98 | 27-APR-15:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 37.21 | 0.01 | 02-FEB-15:00 | 4479.12 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 1.21 | 0.00 | 04-JAN-08:45 | 1300.83 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 36.01 | 0.00 | 01-JAN-00:15 | 4479.12 | 05-MAY-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 44.82 | 0.03 | 19-FEB-01:30 | 3963.62 | 15-APR-14:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 0.34 | 0.00 | 01-JAN-00:15 | 1263.30 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 44.49 | 0.00 | 01-JAN-13:45 | 3963.62 | 15-APR-14:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 36.76 | 0.01 | 24-JAN-23:15 | 3784.79 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 0.88 | 0.00 | 01-JAN-08:00 | 1322.99 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 35.88 | 0.00 | 01-JAN-00:15 | 3784.79 | 06-JUN-16:15 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 28.09 | 0.08 | 16-JAN-15:15 | 2724.32 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 956.98 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 27.66 | 0.00 | 01-JAN-12:45 | 2724.32 | 05-MAY-17:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 28.09 | 0.00 | 14-JAN-03:45 | 2714.49 | 05-MAY-17:15 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 958.77 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 27.67 | 0.00 | 01-JAN-12:45 | 2714.49 | 05-MAY-17:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 36.70 | 0.03 | 09-FEB-21:15 | 3049.07 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 887.23 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 36.60 | 0.00 | 01-JAN-13:45 | 3049.07 | 27-NOV-13:30 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 36.71 | 0.01 | 10-FEB-13:30 | 3054.35 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 888.75 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 36.61 | 0.00 | 01-JAN-13:45 | 3054.35 | 27-NOV-13:30 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 47.51 | 0.05 | 21-OCT-04:45 | 5316.61 | 28-MAR-15:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.48 | 0.00 | 01-JAN-09:45 | 1697.34 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 46.03 | 0.00 | 01-JAN-00:15 | 5316.61 | 28-MAR-15:30 |
EnergyTransfer:Zone:T NW APARTMENT | 40.43 | 0.02 | 25-NOV-21:15 | 5219.93 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.45 | 0.00 | 04-JAN-14:00 | 1717.92 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 37.99 | 0.00 | 01-JAN-00:15 | 5219.93 | 07-JUN-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 47.07 | 0.01 | 15-DEC-22:00 | 4699.58 | 01-OCT-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.21 | 0.00 | 01-JAN-08:45 | 1704.82 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 45.86 | 0.00 | 01-JAN-00:15 | 4699.58 | 01-OCT-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 39.69 | 0.32 | 18-OCT-06:15 | 4462.91 | 06-JUN-16:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.03 | 0.00 | 05-JAN-09:00 | 1727.56 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 37.66 | 0.00 | 01-JAN-00:15 | 4462.91 | 06-JUN-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 30.32 | 0.01 | 19-JAN-21:30 | 3321.73 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.88 | 0.00 | 01-JAN-09:45 | 1399.53 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 29.44 | 0.00 | 01-JAN-00:15 | 3321.73 | 07-JUN-16:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 30.32 | 0.05 | 15-DEC-03:00 | 3316.73 | 07-JUN-16:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.87 | 0.00 | 01-JAN-09:45 | 1400.37 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 29.45 | 0.00 | 01-JAN-00:15 | 3316.73 | 07-JUN-16:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 38.25 | 0.02 | 17-FEB-01:45 | 3816.86 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1370.16 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 37.90 | 0.00 | 01-JAN-02:30 | 3816.86 | 27-NOV-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 38.26 | 0.04 | 26-JAN-06:00 | 3820.97 | 27-NOV-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1370.88 | 09-FEB-20:15 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 37.91 | 0.00 | 01-JAN-02:30 | 3820.97 | 27-NOV-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 617.66 | 295.81 | 19-JUL-01:15 | 46302.07 | 18-JAN-07:15 |
WaterSystems:EnergyTransfer | 617.66 | 295.81 | 19-JUL-01:15 | 46302.07 | 18-JAN-07:15 |
sub cat:WaterSystems:EnergyTransfer | 617.66 | 295.81 | 19-JUL-01:15 | 46302.07 | 18-JAN-07:15 |
EnergyTransfer:HVAC | 4598.29 | 0.00 | 08-JAN-18:45 | 348859.93 | 01-JUL-17:15 |
CoolingCoils:EnergyTransfer | 4592.61 | 0.00 | 01-JAN-00:15 | 348859.93 | 01-JUL-17:15 |
HeatingCoils:EnergyTransfer | 5.69 | 0.00 | 01-JAN-11:00 | 46661.00 | 09-FEB-20:15 |
PlantLoopHeatingDemand:HVAC | 4.40 | 0.00 | 01-JAN-11:00 | 35844.88 | 09-FEB-20:15 |
HeatingCoils:PlantLoopHeatingDemand | 4.40 | 0.00 | 01-JAN-11:00 | 35844.88 | 09-FEB-20:15 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.687 | -28.740 | 0.000 | 0.000 | 3.600 | 2.413 | 12.213 | 28.855 | 0.000 | 0.636 | 0.000 | 0.000 | -5.693 | 0.000 | -3.030 | -10.941 |
G NW APARTMENT | 1.424 | -23.169 | 0.000 | 0.000 | 3.632 | 2.413 | 12.213 | 19.418 | 0.000 | 0.634 | 0.000 | 0.000 | -5.599 | 0.000 | -2.492 | -8.474 |
OFFICE | 0.292 | -34.412 | 0.000 | 0.000 | 0.504 | 21.954 | 7.547 | 28.552 | 0.000 | 0.469 | 0.001 | 0.000 | -5.644 | 0.000 | -0.174 | -19.088 |
G NE APARTMENT | 1.076 | -22.923 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 19.122 | 0.000 | 0.634 | 0.000 | 0.000 | -5.310 | 0.000 | -2.490 | -8.376 |
G N1 APARTMENT | 0.546 | -16.450 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 9.302 | 0.000 | 0.448 | 0.000 | 0.000 | -3.375 | 0.000 | -2.210 | -6.527 |
G N2 APARTMENT | 0.541 | -16.451 | 0.000 | 0.000 | 3.640 | 2.413 | 12.213 | 9.301 | 0.000 | 0.448 | 0.000 | 0.000 | -3.372 | 0.000 | -2.209 | -6.524 |
G S1 APARTMENT | 0.113 | -22.153 | 0.000 | 0.000 | 3.594 | 2.413 | 12.213 | 18.862 | 0.000 | 0.448 | 0.000 | 0.000 | -3.443 | 0.000 | -2.888 | -9.157 |
G S2 APARTMENT | 0.117 | -22.437 | 0.000 | 0.000 | 3.593 | 2.413 | 12.213 | 18.850 | 0.000 | 0.448 | 0.000 | 0.000 | -3.449 | 0.000 | -2.905 | -8.842 |
F2 SW APARTMENT | 0.415 | -42.604 | 0.000 | 0.000 | 3.548 | 2.413 | 12.213 | 28.064 | 0.000 | 0.849 | 5.004 | 0.000 | -6.359 | 0.000 | -3.544 | -0.000 |
F2 NW APARTMENT | 1.109 | -33.748 | 0.000 | 0.000 | 3.584 | 2.413 | 12.213 | 18.750 | 0.000 | 0.847 | 4.136 | 0.000 | -6.244 | 0.000 | -3.059 | -0.000 |
F2 SE APARTMENT | 0.288 | -43.766 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 27.869 | 0.000 | 0.849 | 6.418 | 0.000 | -6.251 | 0.000 | -3.583 | -0.001 |
F2 NE APARTMENT | 0.781 | -33.560 | 0.000 | 0.000 | 3.593 | 2.413 | 12.213 | 18.450 | 0.000 | 0.847 | 4.233 | 0.000 | -5.918 | 0.000 | -3.052 | -0.001 |
F2 N1 APARTMENT | 0.370 | -25.179 | 0.000 | 0.000 | 3.586 | 2.413 | 12.213 | 8.870 | 0.000 | 0.580 | 3.776 | 0.000 | -3.825 | 0.000 | -2.804 | -0.000 |
F2 N2 APARTMENT | 0.367 | -25.184 | 0.000 | 0.000 | 3.586 | 2.413 | 12.213 | 8.869 | 0.000 | 0.580 | 3.779 | 0.000 | -3.822 | 0.000 | -2.803 | -0.000 |
F2 S1 APARTMENT | 0.070 | -34.185 | 0.000 | 0.000 | 3.540 | 2.413 | 12.213 | 18.345 | 0.000 | 0.581 | 4.289 | 0.000 | -3.843 | 0.000 | -3.422 | -0.001 |
F2 S2 APARTMENT | 0.071 | -34.281 | 0.000 | 0.000 | 3.540 | 2.413 | 12.213 | 18.342 | 0.000 | 0.581 | 4.391 | 0.000 | -3.845 | 0.000 | -3.425 | -0.000 |
F3 SW APARTMENT | 0.349 | -44.198 | 0.000 | 0.000 | 3.541 | 2.413 | 12.213 | 27.814 | 0.000 | 0.984 | 7.079 | 0.000 | -6.485 | 0.000 | -3.710 | -0.000 |
F3 NW APARTMENT | 0.944 | -35.076 | 0.000 | 0.000 | 3.573 | 2.413 | 12.213 | 18.565 | 0.000 | 0.982 | 6.056 | 0.000 | -6.406 | 0.000 | -3.265 | -0.000 |
F3 SE APARTMENT | 0.234 | -44.297 | 0.000 | 0.000 | 3.544 | 2.413 | 12.213 | 27.677 | 0.000 | 0.984 | 7.292 | 0.000 | -6.339 | 0.000 | -3.721 | -0.000 |
F3 NE APARTMENT | 0.662 | -34.938 | 0.000 | 0.000 | 3.581 | 2.413 | 12.213 | 18.277 | 0.000 | 0.982 | 6.142 | 0.000 | -6.072 | 0.000 | -3.259 | -0.000 |
F3 N1 APARTMENT | 0.313 | -26.692 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 8.783 | 0.000 | 0.667 | 5.705 | 0.000 | -3.946 | 0.000 | -3.027 | -0.000 |
F3 N2 APARTMENT | 0.310 | -26.697 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 8.783 | 0.000 | 0.667 | 5.708 | 0.000 | -3.943 | 0.000 | -3.025 | -0.000 |
F3 S1 APARTMENT | 0.055 | -36.144 | 0.000 | 0.000 | 3.531 | 2.413 | 12.213 | 18.186 | 0.000 | 0.667 | 6.586 | 0.000 | -3.925 | 0.000 | -3.582 | -0.000 |
F3 S2 APARTMENT | 0.055 | -36.165 | 0.000 | 0.000 | 3.531 | 2.413 | 12.213 | 18.186 | 0.000 | 0.667 | 6.608 | 0.000 | -3.925 | 0.000 | -3.583 | -0.000 |
F4 SW APARTMENT | 0.342 | -44.598 | 0.000 | 0.000 | 3.539 | 2.413 | 12.213 | 27.654 | 0.000 | 1.080 | 7.674 | 0.000 | -6.532 | 0.000 | -3.786 | -0.000 |
F4 NW APARTMENT | 0.914 | -35.467 | 0.000 | 0.000 | 3.569 | 2.413 | 12.213 | 18.459 | 0.000 | 1.078 | 6.652 | 0.000 | -6.474 | 0.000 | -3.356 | -0.000 |
F4 SE APARTMENT | 0.231 | -44.594 | 0.000 | 0.000 | 3.542 | 2.413 | 12.213 | 27.538 | 0.000 | 1.080 | 7.750 | 0.000 | -6.380 | 0.000 | -3.793 | -0.000 |
F4 NE APARTMENT | 0.638 | -35.348 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 18.180 | 0.000 | 1.078 | 6.737 | 0.000 | -6.137 | 0.000 | -3.351 | -0.000 |
F4 N1 APARTMENT | 0.303 | -27.163 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 8.741 | 0.000 | 0.726 | 6.321 | 0.000 | -3.998 | 0.000 | -3.121 | -0.000 |
F4 N2 APARTMENT | 0.301 | -27.168 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 8.740 | 0.000 | 0.726 | 6.324 | 0.000 | -3.995 | 0.000 | -3.119 | -0.000 |
F4 S1 APARTMENT | 0.055 | -36.671 | 0.000 | 0.000 | 3.529 | 2.413 | 12.213 | 18.090 | 0.000 | 0.726 | 7.245 | 0.000 | -3.956 | 0.000 | -3.646 | -0.000 |
F4 S2 APARTMENT | 0.056 | -36.677 | 0.000 | 0.000 | 3.530 | 2.413 | 12.213 | 18.090 | 0.000 | 0.726 | 7.252 | 0.000 | -3.955 | 0.000 | -3.647 | -0.000 |
M SW APARTMENT | 0.342 | -45.351 | 0.000 | 0.000 | 3.537 | 2.413 | 12.213 | 27.505 | 0.000 | 1.156 | 8.635 | 0.000 | -6.580 | 0.000 | -3.869 | -0.000 |
M NW APARTMENT | 0.907 | -36.215 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 18.355 | 0.000 | 1.153 | 7.591 | 0.000 | -6.535 | 0.000 | -3.448 | -0.000 |
M SE APARTMENT | 0.234 | -45.343 | 0.000 | 0.000 | 3.541 | 2.413 | 12.213 | 27.399 | 0.000 | 1.156 | 8.690 | 0.000 | -6.427 | 0.000 | -3.876 | -0.001 |
M NE APARTMENT | 0.635 | -36.107 | 0.000 | 0.000 | 3.574 | 2.413 | 12.213 | 18.084 | 0.000 | 1.153 | 7.675 | 0.000 | -6.195 | 0.000 | -3.445 | -0.000 |
M N1 APARTMENT | 0.305 | -27.951 | 0.000 | 0.000 | 3.562 | 2.413 | 12.213 | 8.695 | 0.000 | 0.772 | 7.243 | 0.000 | -4.042 | 0.000 | -3.211 | -0.000 |
M N2 APARTMENT | 0.303 | -27.955 | 0.000 | 0.000 | 3.562 | 2.413 | 12.213 | 8.694 | 0.000 | 0.772 | 7.246 | 0.000 | -4.039 | 0.000 | -3.210 | -0.000 |
M S1 APARTMENT | 0.059 | -37.513 | 0.000 | 0.000 | 3.528 | 2.413 | 12.213 | 18.001 | 0.000 | 0.773 | 8.232 | 0.000 | -3.985 | 0.000 | -3.720 | -0.000 |
M S2 APARTMENT | 0.059 | -37.517 | 0.000 | 0.000 | 3.528 | 2.413 | 12.213 | 18.000 | 0.000 | 0.773 | 8.236 | 0.000 | -3.984 | 0.000 | -3.720 | -0.000 |
F6 SW APARTMENT | 0.363 | -44.394 | 0.000 | 0.000 | 3.539 | 2.413 | 12.213 | 27.440 | 0.000 | 1.226 | 7.675 | 0.000 | -6.567 | 0.000 | -3.907 | -0.000 |
F6 NW APARTMENT | 0.954 | -35.443 | 0.000 | 0.000 | 3.570 | 2.413 | 12.213 | 18.333 | 0.000 | 1.222 | 6.709 | 0.000 | -6.513 | 0.000 | -3.458 | -0.000 |
F6 SE APARTMENT | 0.250 | -44.390 | 0.000 | 0.000 | 3.543 | 2.413 | 12.213 | 27.345 | 0.000 | 1.226 | 7.730 | 0.000 | -6.414 | 0.000 | -3.915 | -0.000 |
F6 NE APARTMENT | 0.672 | -35.339 | 0.000 | 0.000 | 3.578 | 2.413 | 12.213 | 18.073 | 0.000 | 1.222 | 6.795 | 0.000 | -6.173 | 0.000 | -3.454 | -0.000 |
F6 N1 APARTMENT | 0.321 | -27.197 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 8.700 | 0.000 | 0.816 | 6.405 | 0.000 | -4.028 | 0.000 | -3.208 | -0.000 |
F6 N2 APARTMENT | 0.318 | -27.203 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 8.699 | 0.000 | 0.816 | 6.409 | 0.000 | -4.025 | 0.000 | -3.206 | -0.000 |
F6 S1 APARTMENT | 0.063 | -36.558 | 0.000 | 0.000 | 3.530 | 2.413 | 12.213 | 17.963 | 0.000 | 0.817 | 7.286 | 0.000 | -3.979 | 0.000 | -3.748 | -0.000 |
F6 S2 APARTMENT | 0.063 | -36.563 | 0.000 | 0.000 | 3.530 | 2.413 | 12.213 | 17.963 | 0.000 | 0.817 | 7.290 | 0.000 | -3.978 | 0.000 | -3.748 | -0.000 |
F7 SW APARTMENT | 0.383 | -44.001 | 0.000 | 0.000 | 3.541 | 2.413 | 12.213 | 27.362 | 0.000 | 1.283 | 7.336 | 0.000 | -6.570 | 0.000 | -3.959 | -0.000 |
F7 NW APARTMENT | 0.996 | -35.191 | 0.000 | 0.000 | 3.573 | 2.413 | 12.213 | 18.295 | 0.000 | 1.280 | 6.416 | 0.000 | -6.507 | 0.000 | -3.486 | -0.000 |
F7 SE APARTMENT | 0.264 | -44.002 | 0.000 | 0.000 | 3.544 | 2.413 | 12.213 | 27.275 | 0.000 | 1.283 | 7.392 | 0.000 | -6.415 | 0.000 | -3.968 | -0.000 |
F7 NE APARTMENT | 0.709 | -35.090 | 0.000 | 0.000 | 3.580 | 2.413 | 12.213 | 18.042 | 0.000 | 1.279 | 6.502 | 0.000 | -6.166 | 0.000 | -3.482 | -0.000 |
F7 N1 APARTMENT | 0.336 | -26.954 | 0.000 | 0.000 | 3.569 | 2.413 | 12.213 | 8.691 | 0.000 | 0.852 | 6.129 | 0.000 | -4.024 | 0.000 | -3.224 | -0.000 |
F7 N2 APARTMENT | 0.334 | -26.960 | 0.000 | 0.000 | 3.569 | 2.413 | 12.213 | 8.690 | 0.000 | 0.852 | 6.133 | 0.000 | -4.021 | 0.000 | -3.222 | -0.000 |
F7 S1 APARTMENT | 0.068 | -36.177 | 0.000 | 0.000 | 3.531 | 2.413 | 12.213 | 17.918 | 0.000 | 0.852 | 6.955 | 0.000 | -3.981 | 0.000 | -3.791 | -0.000 |
F7 S2 APARTMENT | 0.068 | -36.182 | 0.000 | 0.000 | 3.531 | 2.413 | 12.213 | 17.917 | 0.000 | 0.852 | 6.959 | 0.000 | -3.980 | 0.000 | -3.791 | -0.000 |
F8 SW APARTMENT | 0.405 | -43.873 | 0.000 | 0.000 | 3.542 | 2.413 | 12.213 | 27.282 | 0.000 | 1.343 | 7.266 | 0.000 | -6.575 | 0.000 | -4.016 | -0.000 |
F8 NW APARTMENT | 1.047 | -35.194 | 0.000 | 0.000 | 3.575 | 2.413 | 12.213 | 18.250 | 0.000 | 1.339 | 6.384 | 0.000 | -6.505 | 0.000 | -3.521 | -0.000 |
F8 SE APARTMENT | 0.283 | -43.879 | 0.000 | 0.000 | 3.546 | 2.413 | 12.213 | 27.203 | 0.000 | 1.342 | 7.325 | 0.000 | -6.420 | 0.000 | -4.025 | -0.001 |
F8 NE APARTMENT | 0.749 | -35.094 | 0.000 | 0.000 | 3.583 | 2.413 | 12.213 | 18.004 | 0.000 | 1.339 | 6.474 | 0.000 | -6.164 | 0.000 | -3.516 | -0.000 |
F8 N1 APARTMENT | 0.357 | -26.963 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 8.676 | 0.000 | 0.892 | 6.107 | 0.000 | -4.021 | 0.000 | -3.246 | -0.000 |
F8 N2 APARTMENT | 0.355 | -26.969 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 8.675 | 0.000 | 0.892 | 6.112 | 0.000 | -4.018 | 0.000 | -3.245 | -0.000 |
F8 S1 APARTMENT | 0.076 | -36.062 | 0.000 | 0.000 | 3.532 | 2.413 | 12.213 | 17.870 | 0.000 | 0.893 | 6.891 | 0.000 | -3.985 | 0.000 | -3.840 | -0.000 |
F8 S2 APARTMENT | 0.076 | -36.067 | 0.000 | 0.000 | 3.532 | 2.413 | 12.213 | 17.870 | 0.000 | 0.893 | 6.895 | 0.000 | -3.984 | 0.000 | -3.841 | -0.000 |
F9 SW APARTMENT | 0.478 | -44.494 | 0.000 | 0.000 | 3.545 | 2.413 | 12.213 | 27.187 | 0.000 | 1.389 | 7.871 | 0.000 | -6.570 | 0.000 | -4.032 | -0.000 |
F9 NW APARTMENT | 1.206 | -36.006 | 0.000 | 0.000 | 3.578 | 2.413 | 12.213 | 18.183 | 0.000 | 1.385 | 7.037 | 0.000 | -6.498 | 0.000 | -3.512 | -0.000 |
F9 SE APARTMENT | 0.336 | -44.487 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 27.115 | 0.000 | 1.389 | 7.934 | 0.000 | -6.416 | 0.000 | -4.045 | -0.000 |
F9 NE APARTMENT | 0.876 | -35.881 | 0.000 | 0.000 | 3.586 | 2.413 | 12.213 | 17.946 | 0.000 | 1.385 | 7.135 | 0.000 | -6.161 | 0.000 | -3.512 | -0.000 |
F9 N1 APARTMENT | 0.424 | -27.663 | 0.000 | 0.000 | 3.575 | 2.413 | 12.213 | 8.647 | 0.000 | 0.920 | 6.705 | 0.000 | -4.012 | 0.000 | -3.223 | -0.000 |
F9 N2 APARTMENT | 0.421 | -27.670 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 8.646 | 0.000 | 0.920 | 6.712 | 0.000 | -4.009 | 0.000 | -3.222 | -0.000 |
F9 S1 APARTMENT | 0.100 | -36.602 | 0.000 | 0.000 | 3.535 | 2.413 | 12.213 | 17.816 | 0.000 | 0.922 | 7.436 | 0.000 | -3.984 | 0.000 | -3.849 | -0.000 |
F9 S2 APARTMENT | 0.100 | -36.612 | 0.000 | 0.000 | 3.536 | 2.413 | 12.213 | 17.816 | 0.000 | 0.922 | 7.445 | 0.000 | -3.982 | 0.000 | -3.849 | -0.000 |
T SW APARTMENT | 1.480 | -46.025 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 26.573 | 0.000 | 1.428 | 8.447 | 0.000 | -6.126 | 0.000 | -3.981 | -0.001 |
T NW APARTMENT | 2.446 | -37.988 | 0.000 | 0.000 | 3.601 | 2.413 | 12.213 | 17.634 | 0.000 | 1.424 | 7.898 | 0.000 | -6.108 | 0.000 | -3.533 | -0.000 |
T SE APARTMENT | 1.213 | -45.854 | 0.000 | 0.000 | 3.583 | 2.413 | 12.213 | 26.524 | 0.000 | 1.429 | 8.471 | 0.000 | -5.989 | 0.000 | -4.002 | -0.000 |
T NE APARTMENT | 2.031 | -37.655 | 0.000 | 0.000 | 3.609 | 2.413 | 12.213 | 17.442 | 0.000 | 1.425 | 7.910 | 0.000 | -5.815 | 0.000 | -3.572 | -0.000 |
T N1 APARTMENT | 0.878 | -29.437 | 0.000 | 0.000 | 3.599 | 2.413 | 12.213 | 8.436 | 0.000 | 0.945 | 7.933 | 0.000 | -3.762 | 0.000 | -3.219 | -0.000 |
T N2 APARTMENT | 0.874 | -29.445 | 0.000 | 0.000 | 3.600 | 2.413 | 12.213 | 8.433 | 0.000 | 0.945 | 7.944 | 0.000 | -3.757 | 0.000 | -3.220 | -0.000 |
T S1 APARTMENT | 0.354 | -37.895 | 0.000 | 0.000 | 3.568 | 2.413 | 12.213 | 17.504 | 0.000 | 0.948 | 8.437 | 0.000 | -3.758 | 0.000 | -3.783 | -0.000 |
T S2 APARTMENT | 0.354 | -37.904 | 0.000 | 0.000 | 3.568 | 2.413 | 12.213 | 17.502 | 0.000 | 0.948 | 8.446 | 0.000 | -3.756 | 0.000 | -3.783 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 6.111 | 0.000 | 14.314 | 0.001 | 0.000 | -1.405 | 0.000 | -10.929 | -26.621 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.967 | 0.000 | 0.074 | 0.000 | 0.000 | -0.868 | 0.000 | -0.054 | -20.649 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.921 | 0.000 | 0.087 | 0.000 | 0.000 | -0.903 | 0.000 | -0.068 | -20.566 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.885 | 0.000 | 0.095 | 0.000 | 0.000 | -0.923 | 0.000 | -0.079 | -20.508 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 2.813 | 0.000 | 0.092 | 0.000 | 0.000 | -0.968 | 0.000 | -0.095 | -38.901 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.859 | 0.000 | 0.110 | 0.000 | 0.000 | -0.929 | 0.000 | -0.092 | -20.477 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.862 | 0.000 | 0.117 | 0.000 | 0.000 | -0.920 | 0.000 | -0.095 | -20.493 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.854 | 0.000 | 0.123 | 0.000 | 0.000 | -0.920 | 0.000 | -0.099 | -20.487 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.836 | 0.000 | 0.124 | 0.000 | 0.000 | -0.923 | 0.000 | -0.103 | -20.464 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 2.682 | 0.000 | 0.096 | 0.000 | 0.000 | -0.895 | 0.000 | -0.118 | -28.231 |
Total Facility | 39.952 | -2772.456 | 0.000 | 0.000 | 282.125 | 416.414 | 980.287 | 1484.049 | 0.000 | 90.996 | 494.045 | 0.000 | -415.618 | 0.000 | -284.465 | -315.343 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 01-OCT-15:15 | 0.00 | -3514.12 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 4239.32 | 0.00 | 28.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1374.01 |
G NW APARTMENT | 07-JUN-16:30 | 0.00 | -3517.91 | 0.00 | 0.00 | 82.47 | 144.04 | 588.62 | 3808.57 | 0.00 | 103.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1209.09 |
OFFICE | 28-SEP-13:30 | 0.00 | -4054.45 | 0.00 | 0.00 | 64.73 | 1622.33 | 544.91 | 3343.85 | 0.00 | 81.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1602.49 |
G NE APARTMENT | 07-JUN-16:30 | 0.00 | -2859.82 | 0.00 | 0.00 | 84.63 | 144.04 | 588.62 | 2188.16 | 0.00 | 105.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -251.01 |
G N1 APARTMENT | 07-JUN-17:00 | 0.00 | -2001.35 | 0.00 | 0.00 | 83.53 | 144.04 | 588.62 | 1443.61 | 0.00 | 54.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -312.60 |
G N2 APARTMENT | 07-JUN-17:00 | 0.00 | -1990.29 | 0.00 | 0.00 | 83.58 | 144.04 | 588.62 | 1444.29 | 0.00 | 54.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -324.42 |
G S1 APARTMENT | 27-NOV-13:30 | 0.00 | -2153.57 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3511.30 | 0.00 | 122.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1938.35 |
G S2 APARTMENT | 27-NOV-13:30 | 0.00 | -2181.85 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3510.28 | 0.00 | 122.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1909.05 |
F2 SW APARTMENT | 27-APR-15:30 | 0.00 | -4298.99 | 0.00 | 0.00 | 48.87 | 100.83 | 470.89 | 3897.53 | 0.00 | 261.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -480.68 |
F2 NW APARTMENT | 05-MAY-16:30 | 0.00 | -4269.20 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3465.38 | 0.00 | 282.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -296.29 |
F2 SE APARTMENT | 01-OCT-14:00 | 0.00 | -3882.51 | 0.00 | 0.00 | 40.65 | 28.81 | 382.60 | 3419.24 | 0.00 | 49.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38.41 |
F2 NE APARTMENT | 06-JUN-16:10 | 0.00 | -3508.70 | 0.00 | 0.00 | 84.70 | 144.04 | 588.62 | 2225.98 | 0.00 | 234.68 | 230.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 07-JUN-16:30 | 0.00 | -2474.97 | 0.00 | 0.00 | 84.56 | 144.04 | 588.62 | 1463.54 | 0.00 | 91.21 | 103.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 07-JUN-16:30 | 0.00 | -2466.71 | 0.00 | 0.00 | 84.57 | 144.04 | 588.62 | 1463.81 | 0.00 | 91.22 | 94.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 27-NOV-13:00 | 0.00 | -2895.38 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3610.84 | 0.00 | 86.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1277.64 |
F2 S2 APARTMENT | 27-NOV-13:00 | 0.00 | -2904.39 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3610.60 | 0.00 | 86.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.39 |
F3 SW APARTMENT | 27-APR-15:30 | 0.00 | -4312.35 | 0.00 | 0.00 | 48.77 | 100.83 | 470.89 | 3848.10 | 0.00 | 308.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -464.42 |
F3 NW APARTMENT | 05-MAY-16:30 | 0.00 | -4283.67 | 0.00 | 0.00 | 84.43 | 144.04 | 588.62 | 3442.22 | 0.00 | 333.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -308.67 |
F3 SE APARTMENT | 01-OCT-14:15 | 0.00 | -3737.13 | 0.00 | 0.00 | 40.12 | 50.41 | 400.26 | 3281.23 | 0.00 | 55.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.69 |
F3 NE APARTMENT | 06-JUN-16:10 | 0.00 | -3542.38 | 0.00 | 0.00 | 84.65 | 144.04 | 588.62 | 2238.59 | 0.00 | 277.44 | 209.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2512.64 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1217.09 | 0.00 | 181.54 | 189.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2502.38 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1217.38 | 0.00 | 181.54 | 178.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 27-NOV-12:45 | 0.00 | -2942.29 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3658.87 | 0.00 | 45.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1237.35 |
F3 S2 APARTMENT | 27-NOV-12:45 | 0.00 | -2946.70 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 3658.62 | 0.00 | 44.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1232.43 |
F4 SW APARTMENT | 27-APR-15:30 | 0.00 | -4333.15 | 0.00 | 0.00 | 48.77 | 100.83 | 470.89 | 3813.98 | 0.00 | 343.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -445.25 |
F4 NW APARTMENT | 05-MAY-17:05 | 0.00 | -4310.52 | 0.00 | 0.00 | 141.48 | 194.45 | 588.62 | 2958.28 | 0.00 | 335.54 | 92.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 SE APARTMENT | 15-APR-13:45 | 0.00 | -3781.74 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2894.38 | 0.00 | 382.68 | 52.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 NE APARTMENT | 06-JUN-16:10 | 0.00 | -3573.07 | 0.00 | 0.00 | 84.54 | 144.04 | 588.62 | 2245.74 | 0.00 | 309.46 | 200.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2553.42 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1223.91 | 0.00 | 202.65 | 201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2543.13 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1224.20 | 0.00 | 202.65 | 191.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 27-NOV-12:45 | 0.00 | -2972.77 | 0.00 | 0.00 | 40.72 | 28.81 | 406.15 | 3652.01 | 0.00 | 43.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1198.64 |
F4 S2 APARTMENT | 27-NOV-12:45 | 0.00 | -2975.98 | 0.00 | 0.00 | 40.71 | 28.81 | 406.15 | 3651.75 | 0.00 | 43.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1194.83 |
M SW APARTMENT | 27-APR-15:30 | 0.00 | -4377.72 | 0.00 | 0.00 | 48.78 | 100.83 | 470.89 | 3785.99 | 0.00 | 373.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -402.17 |
M NW APARTMENT | 05-MAY-17:05 | 0.00 | -4366.08 | 0.00 | 0.00 | 141.40 | 194.45 | 588.62 | 2949.79 | 0.00 | 364.08 | 127.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 15-APR-13:45 | 0.00 | -3837.80 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2884.47 | 0.00 | 415.34 | 85.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 06-JUN-16:10 | 0.00 | -3627.55 | 0.00 | 0.00 | 84.47 | 144.04 | 588.62 | 2249.78 | 0.00 | 335.69 | 224.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2607.27 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1228.34 | 0.00 | 219.94 | 234.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2597.04 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1228.63 | 0.00 | 219.94 | 223.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 27-NOV-12:45 | 0.00 | -3020.85 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3646.14 | 0.00 | 44.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1145.05 |
M S2 APARTMENT | 27-NOV-12:45 | 0.00 | -3023.43 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3645.89 | 0.00 | 43.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1141.83 |
F6 SW APARTMENT | 27-APR-15:30 | 0.00 | -4349.58 | 0.00 | 0.00 | 48.78 | 100.83 | 470.89 | 3765.63 | 0.00 | 398.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.04 |
F6 NW APARTMENT | 05-MAY-17:05 | 0.00 | -4336.29 | 0.00 | 0.00 | 141.27 | 194.45 | 588.62 | 2944.82 | 0.00 | 388.29 | 78.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 SE APARTMENT | 15-APR-13:45 | 0.00 | -3821.08 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2878.93 | 0.00 | 443.23 | 46.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 NE APARTMENT | 06-JUN-16:10 | 0.00 | -3606.85 | 0.00 | 0.00 | 84.35 | 144.04 | 588.62 | 2254.86 | 0.00 | 357.99 | 176.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2591.82 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1233.65 | 0.00 | 234.74 | 198.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2581.62 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1233.95 | 0.00 | 234.74 | 188.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 27-NOV-12:45 | 0.00 | -2993.60 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3642.71 | 0.00 | 43.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1168.72 |
F6 S2 APARTMENT | 27-NOV-12:45 | 0.00 | -2996.14 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3642.52 | 0.00 | 43.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1165.81 |
F7 SW APARTMENT | 27-APR-15:15 | 0.00 | -4347.05 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3772.79 | 0.00 | 433.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -480.14 |
F7 NW APARTMENT | 05-MAY-17:15 | 0.00 | -4336.59 | 0.00 | 0.00 | 141.18 | 194.45 | 588.62 | 2939.42 | 0.00 | 410.60 | 62.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 SE APARTMENT | 15-APR-13:45 | 0.00 | -3828.29 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2873.05 | 0.00 | 467.82 | 35.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 NE APARTMENT | 05-MAY-16:30 | 0.00 | -3623.88 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1988.60 | 0.00 | 456.38 | 361.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2598.62 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1237.40 | 0.00 | 247.79 | 188.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2588.44 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1237.70 | 0.00 | 247.79 | 178.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 27-NOV-12:45 | 0.00 | -2990.68 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3638.91 | 0.00 | 43.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1167.66 |
F7 S2 APARTMENT | 27-NOV-12:45 | 0.00 | -2993.10 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3638.72 | 0.00 | 43.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1164.86 |
F8 SW APARTMENT | 27-APR-15:15 | 0.00 | -4360.99 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3755.49 | 0.00 | 454.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -469.42 |
F8 NW APARTMENT | 05-MAY-17:15 | 0.00 | -4350.39 | 0.00 | 0.00 | 141.12 | 194.45 | 588.62 | 2933.85 | 0.00 | 429.85 | 62.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 SE APARTMENT | 15-APR-13:45 | 0.00 | -3850.05 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2867.14 | 0.00 | 489.95 | 40.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 NE APARTMENT | 05-MAY-16:30 | 0.00 | -3653.20 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 1992.93 | 0.00 | 477.96 | 364.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2618.55 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1240.01 | 0.00 | 259.49 | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2608.42 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1240.32 | 0.00 | 259.49 | 183.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 27-NOV-12:45 | 0.00 | -2999.10 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3635.40 | 0.00 | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1156.03 |
F8 S2 APARTMENT | 27-NOV-12:45 | 0.00 | -3003.83 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3635.21 | 0.00 | 43.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1151.01 |
F9 SW APARTMENT | 27-APR-15:30 | 0.00 | -4486.63 | 0.00 | 0.00 | 48.86 | 100.83 | 470.89 | 3710.36 | 0.00 | 459.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -303.92 |
F9 NW APARTMENT | 05-MAY-17:15 | 0.00 | -4482.57 | 0.00 | 0.00 | 141.24 | 194.45 | 588.62 | 2923.66 | 0.00 | 447.79 | 186.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SE APARTMENT | 15-APR-14:00 | 0.00 | -3963.80 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 2805.73 | 0.00 | 533.92 | 171.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 06-JUN-16:10 | 0.00 | -3786.69 | 0.00 | 0.00 | 84.42 | 144.04 | 588.62 | 2259.36 | 0.00 | 412.45 | 297.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 05-MAY-17:10 | 0.00 | -2724.83 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1238.69 | 0.00 | 270.15 | 291.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 05-MAY-17:10 | 0.00 | -2715.00 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 1238.98 | 0.00 | 270.15 | 280.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 27-NOV-13:30 | 0.00 | -3048.03 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3436.87 | 0.00 | 118.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.52 |
F9 S2 APARTMENT | 27-NOV-13:30 | 0.00 | -3053.31 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3436.73 | 0.00 | 118.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -960.15 |
T SW APARTMENT | 28-MAR-15:30 | 0.00 | -5316.82 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 4142.29 | 0.00 | 0.00 | 553.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 07-JUN-16:30 | 0.00 | -5225.22 | 0.00 | 0.00 | 82.96 | 144.04 | 588.62 | 3648.97 | 0.00 | 272.06 | 488.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 01-OCT-13:30 | 0.00 | -4699.44 | 0.00 | 0.00 | 40.44 | 28.81 | 382.60 | 3471.69 | 0.00 | 86.48 | 689.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 06-JUN-16:10 | 0.00 | -4463.47 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 2198.84 | 0.00 | 430.04 | 1017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 07-JUN-16:30 | 0.00 | -3323.20 | 0.00 | 0.00 | 84.36 | 144.04 | 588.62 | 1445.71 | 0.00 | 166.18 | 894.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 07-JUN-16:30 | 0.00 | -3317.38 | 0.00 | 0.00 | 84.48 | 144.04 | 588.62 | 1446.91 | 0.00 | 166.39 | 886.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 27-NOV-13:30 | 0.00 | -3815.60 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3394.18 | 0.00 | 118.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -155.47 |
T S2 APARTMENT | 27-NOV-13:30 | 0.00 | -3819.71 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3394.00 | 0.00 | 118.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151.18 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-JUN-16:10 | 0.00 | -259946.64 | 0.00 | 0.00 | 6667.06 | 18221.75 | 47207.76 | 174614.87 | 0.00 | 29919.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16684.74 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-FEB-20:25 | 840.05 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 293.08 | 0.00 | -878.02 | 0.00 | -1174.46 | 0.00 |
G NW APARTMENT | 22-DEC-07:55 | 1097.02 | 0.00 | 0.00 | 0.00 | 159.12 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -251.79 | 0.00 | -1013.36 | -467.21 |
OFFICE | 02-JAN-07:00 | 479.09 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 36.86 | 0.00 | -1024.22 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 09-FEB-20:20 | 864.54 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 250.09 | 0.00 | -859.52 | 0.00 | -1174.46 | 0.00 |
G N1 APARTMENT | 22-DEC-07:55 | 1029.76 | 0.00 | 0.00 | 0.00 | 157.66 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -161.08 | 0.00 | -998.81 | -503.76 |
G N2 APARTMENT | 22-DEC-07:55 | 1038.67 | 0.00 | 0.00 | 0.00 | 157.72 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -160.88 | 0.00 | -998.19 | -513.55 |
G S1 APARTMENT | 09-FEB-20:20 | 603.16 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 163.10 | 0.00 | -543.60 | 0.00 | -1142.01 | 0.00 |
G S2 APARTMENT | 09-FEB-20:20 | 572.98 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 196.31 | 0.00 | -546.63 | 0.00 | -1142.01 | 0.00 |
F2 SW APARTMENT | 09-FEB-20:25 | 510.05 | 0.00 | 0.00 | 0.00 | 164.98 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 905.36 | 0.00 | -943.92 | 0.00 | -1390.81 | 0.00 |
F2 NW APARTMENT | 22-DEC-08:00 | 931.14 | 0.00 | 0.00 | 0.00 | 155.25 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -314.34 | 0.00 | -1077.65 | -170.62 |
F2 SE APARTMENT | 29-DEC-06:10 | 422.05 | 0.00 | 0.00 | 0.00 | 162.99 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1190.03 | 0.00 | -667.08 | 0.00 | -1526.68 | 0.00 |
F2 NE APARTMENT | 09-FEB-20:25 | 652.98 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 741.14 | 0.00 | -922.70 | 0.00 | -1390.76 | 0.00 |
F2 N1 APARTMENT | 24-JAN-10:45 | 738.32 | 0.00 | 0.00 | 0.00 | 45.16 | 28.81 | 406.15 | 114.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1021.63 | -311.69 |
F2 N2 APARTMENT | 24-JAN-10:45 | 718.44 | 0.00 | 0.00 | 0.00 | 45.13 | 28.81 | 406.15 | 114.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1022.46 | -290.27 |
F2 S1 APARTMENT | 09-FEB-20:25 | 223.11 | 0.00 | 0.00 | 0.00 | 164.91 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 785.42 | 0.00 | -583.72 | 0.00 | -1344.06 | 0.00 |
F2 S2 APARTMENT | 09-FEB-20:25 | 217.37 | 0.00 | 0.00 | 0.00 | 164.84 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 792.55 | 0.00 | -584.99 | 0.00 | -1344.11 | 0.00 |
F3 SW APARTMENT | 09-FEB-20:25 | 535.20 | 0.00 | 0.00 | 0.00 | 164.99 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1042.82 | 0.00 | -957.62 | 0.00 | -1539.71 | 0.00 |
F3 NW APARTMENT | 22-DEC-08:00 | 794.58 | 0.00 | 0.00 | 0.00 | 153.42 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 56.18 | 0.00 | -346.63 | 0.00 | -1133.77 | 0.00 |
F3 SE APARTMENT | 09-FEB-20:25 | 538.52 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1037.93 | 0.00 | -956.11 | 0.00 | -1539.68 | 0.00 |
F3 NE APARTMENT | 09-FEB-20:25 | 675.32 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 883.41 | 0.00 | -938.39 | 0.00 | -1539.67 | 0.00 |
F3 N1 APARTMENT | 22-DEC-08:05 | 523.52 | 0.00 | 0.00 | 0.00 | 73.85 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 103.46 | 0.00 | -150.11 | 0.00 | -982.41 | 0.00 |
F3 N2 APARTMENT | 22-DEC-08:05 | 513.48 | 0.00 | 0.00 | 0.00 | 73.86 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 112.53 | 0.00 | -149.50 | 0.00 | -982.07 | 0.00 |
F3 S1 APARTMENT | 09-FEB-20:25 | 220.73 | 0.00 | 0.00 | 0.00 | 164.91 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 937.35 | 0.00 | -593.12 | 0.00 | -1484.19 | 0.00 |
F3 S2 APARTMENT | 09-FEB-20:25 | 220.87 | 0.00 | 0.00 | 0.00 | 164.90 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 937.23 | 0.00 | -593.15 | 0.00 | -1484.19 | 0.00 |
F4 SW APARTMENT | 09-FEB-20:25 | 659.72 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1039.54 | 0.00 | -958.46 | 0.00 | -1660.13 | 0.00 |
F4 NW APARTMENT | 09-FEB-20:25 | 751.66 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 934.60 | 0.00 | -945.48 | 0.00 | -1660.13 | 0.00 |
F4 SE APARTMENT | 09-FEB-20:25 | 687.10 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1009.00 | 0.00 | -955.32 | 0.00 | -1660.13 | 0.00 |
F4 NE APARTMENT | 09-FEB-20:25 | 784.02 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 898.54 | 0.00 | -941.79 | 0.00 | -1660.13 | 0.00 |
F4 N1 APARTMENT | 09-FEB-20:25 | 417.38 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 847.74 | 0.00 | -586.63 | 0.00 | -1597.83 | 0.00 |
F4 N2 APARTMENT | 22-DEC-08:05 | 447.69 | 0.00 | 0.00 | 0.00 | 73.74 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 227.50 | 0.00 | -161.62 | 0.00 | -1019.01 | 0.00 |
F4 S1 APARTMENT | 09-FEB-20:25 | 307.49 | 0.00 | 0.00 | 0.00 | 165.00 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 963.90 | 0.00 | -592.89 | 0.00 | -1597.84 | 0.00 |
F4 S2 APARTMENT | 09-FEB-20:25 | 309.51 | 0.00 | 0.00 | 0.00 | 165.00 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 961.76 | 0.00 | -592.76 | 0.00 | -1597.84 | 0.00 |
M SW APARTMENT | 09-FEB-20:25 | 766.35 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1038.44 | 0.00 | -960.26 | 0.00 | -1763.88 | 0.00 |
M NW APARTMENT | 09-FEB-20:25 | 845.93 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 947.02 | 0.00 | -948.42 | 0.00 | -1763.87 | 0.00 |
M SE APARTMENT | 09-FEB-20:25 | 796.11 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 1005.40 | 0.00 | -956.98 | 0.00 | -1763.87 | 0.00 |
M NE APARTMENT | 09-FEB-20:25 | 877.84 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 911.51 | 0.00 | -944.82 | 0.00 | -1763.87 | 0.00 |
M N1 APARTMENT | 09-FEB-20:25 | 500.45 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 864.92 | 0.00 | -588.75 | 0.00 | -1695.96 | 0.00 |
M N2 APARTMENT | 09-FEB-20:25 | 503.11 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 862.09 | 0.00 | -588.58 | 0.00 | -1695.96 | 0.00 |
M S1 APARTMENT | 09-FEB-20:25 | 404.80 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 965.75 | 0.00 | -593.94 | 0.00 | -1695.96 | 0.00 |
M S2 APARTMENT | 09-FEB-20:25 | 407.19 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 963.23 | 0.00 | -593.80 | 0.00 | -1695.96 | 0.00 |
F6 SW APARTMENT | 09-FEB-20:25 | 930.55 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 961.56 | 0.00 | -955.10 | 0.00 | -1856.36 | 0.00 |
F6 NW APARTMENT | 09-FEB-20:25 | 1004.36 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 876.59 | 0.00 | -943.94 | 0.00 | -1856.36 | 0.00 |
F6 SE APARTMENT | 09-FEB-20:25 | 959.34 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 929.58 | 0.00 | -951.90 | 0.00 | -1856.36 | 0.00 |
F6 NE APARTMENT | 09-FEB-20:25 | 1035.76 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 841.57 | 0.00 | -940.31 | 0.00 | -1856.36 | 0.00 |
F6 N1 APARTMENT | 24-JAN-10:45 | 664.37 | 0.00 | 0.00 | 0.00 | 44.36 | 28.81 | 406.15 | 50.87 | 0.00 | 0.00 | 35.63 | 0.00 | 0.00 | 0.00 | -1230.18 | 0.00 |
F6 N2 APARTMENT | 09-FEB-20:25 | 659.53 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 790.52 | 0.00 | -585.83 | 0.00 | -1783.56 | 0.00 |
F6 S1 APARTMENT | 09-FEB-20:25 | 568.79 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 886.15 | 0.00 | -590.74 | 0.00 | -1783.56 | 0.00 |
F6 S2 APARTMENT | 09-FEB-20:25 | 571.06 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 883.75 | 0.00 | -590.60 | 0.00 | -1783.56 | 0.00 |
F7 SW APARTMENT | 09-FEB-20:25 | 1063.45 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 910.20 | 0.00 | -952.36 | 0.00 | -1940.64 | 0.00 |
F7 NW APARTMENT | 09-FEB-20:25 | 1133.52 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 829.23 | 0.00 | -941.45 | 0.00 | -1940.64 | 0.00 |
F7 SE APARTMENT | 09-FEB-20:20 | 1091.05 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 879.51 | 0.00 | -949.27 | 0.00 | -1940.64 | 0.00 |
F7 NE APARTMENT | 09-FEB-20:20 | 1162.77 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 796.58 | 0.00 | -938.05 | 0.00 | -1940.64 | 0.00 |
F7 N1 APARTMENT | 24-JAN-10:45 | 929.36 | 0.00 | 0.00 | 0.00 | 44.61 | 28.81 | 406.15 | 48.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1259.64 | -197.64 |
F7 N2 APARTMENT | 24-JAN-10:45 | 917.54 | 0.00 | 0.00 | 0.00 | 44.59 | 28.81 | 406.15 | 47.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1260.13 | -184.74 |
F7 S1 APARTMENT | 09-FEB-20:25 | 699.85 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 833.36 | 0.00 | -589.10 | 0.00 | -1863.45 | 0.00 |
F7 S2 APARTMENT | 09-FEB-20:25 | 701.99 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 831.09 | 0.00 | -588.97 | 0.00 | -1863.45 | 0.00 |
F8 SW APARTMENT | 09-FEB-20:20 | 1183.17 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 866.37 | 0.00 | -950.26 | 0.00 | -2018.62 | 0.00 |
F8 NW APARTMENT | 09-FEB-20:20 | 1248.70 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 790.28 | 0.00 | -939.70 | 0.00 | -2018.62 | 0.00 |
F8 SE APARTMENT | 09-FEB-20:20 | 1207.45 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 839.35 | 0.00 | -947.52 | 0.00 | -2018.62 | 0.00 |
F8 NE APARTMENT | 09-FEB-20:20 | 1274.60 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 761.32 | 0.00 | -936.64 | 0.00 | -2018.62 | 0.00 |
F8 N1 APARTMENT | 24-JAN-10:45 | 1063.83 | 0.00 | 0.00 | 0.00 | 44.86 | 28.81 | 406.15 | 46.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1290.53 | -299.95 |
F8 N2 APARTMENT | 24-JAN-10:45 | 1068.44 | 0.00 | 0.00 | 0.00 | 44.84 | 28.81 | 406.15 | 46.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1290.59 | -303.85 |
F8 S1 APARTMENT | 09-FEB-20:20 | 818.14 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 787.78 | 0.00 | -587.83 | 0.00 | -1937.44 | 0.00 |
F8 S2 APARTMENT | 09-FEB-20:20 | 820.02 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 785.79 | 0.00 | -587.71 | 0.00 | -1937.44 | 0.00 |
F9 SW APARTMENT | 09-FEB-20:15 | 1244.05 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 808.26 | 0.00 | -933.05 | 0.00 | -2038.60 | 0.00 |
F9 NW APARTMENT | 09-FEB-20:15 | 1300.76 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 741.71 | 0.00 | -923.22 | 0.00 | -2038.60 | 0.00 |
F9 SE APARTMENT | 09-FEB-20:15 | 1263.24 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 786.86 | 0.00 | -930.85 | 0.00 | -2038.60 | 0.00 |
F9 NE APARTMENT | 09-FEB-20:15 | 1322.93 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 716.88 | 0.00 | -920.55 | 0.00 | -2038.60 | 0.00 |
F9 N1 APARTMENT | 22-DEC-08:00 | 1062.37 | 0.00 | 0.00 | 0.00 | 152.95 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -242.91 | 0.00 | -1260.07 | -188.57 |
F9 N2 APARTMENT | 22-DEC-08:00 | 1053.45 | 0.00 | 0.00 | 0.00 | 153.11 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -242.05 | 0.00 | -1259.91 | -180.83 |
F9 S1 APARTMENT | 09-FEB-20:15 | 887.19 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 725.73 | 0.00 | -577.02 | 0.00 | -1955.25 | 0.00 |
F9 S2 APARTMENT | 09-FEB-20:15 | 888.71 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 724.12 | 0.00 | -576.92 | 0.00 | -1955.25 | 0.00 |
T SW APARTMENT | 09-FEB-20:15 | 1697.27 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 375.64 | 0.00 | -885.44 | 0.00 | -2106.81 | 0.00 |
T NW APARTMENT | 09-FEB-20:15 | 1717.83 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 344.41 | 0.00 | -874.78 | 0.00 | -2106.81 | 0.00 |
T SE APARTMENT | 09-FEB-20:15 | 1704.74 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 366.79 | 0.00 | -884.07 | 0.00 | -2106.81 | 0.00 |
T NE APARTMENT | 09-FEB-20:15 | 1727.47 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 333.18 | 0.00 | -873.19 | 0.00 | -2106.81 | 0.00 |
T N1 APARTMENT | 09-FEB-20:15 | 1399.46 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 243.36 | 0.00 | -542.11 | 0.00 | -2020.05 | 0.00 |
T N2 APARTMENT | 09-FEB-20:15 | 1400.31 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 242.43 | 0.00 | -542.03 | 0.00 | -2020.05 | 0.00 |
T S1 APARTMENT | 09-FEB-20:15 | 1370.09 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 284.99 | 0.00 | -554.37 | 0.00 | -2020.05 | 0.00 |
T S2 APARTMENT | 09-FEB-20:15 | 1370.82 | 0.00 | 0.00 | 0.00 | 165.01 | 230.46 | 523.87 | 0.00 | 0.00 | 0.00 | 284.19 | 0.00 | -554.30 | 0.00 | -2020.05 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-FEB-20:15 | 58970.59 | 0.00 | 0.00 | 0.00 | 13030.82 | 25049.15 | 41923.99 | 0.00 | 0.00 | 0.00 | 57155.12 | 0.00 | -61415.63 | 0.00 | -134714.04 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Sec1.1A-General InformationData | |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 5.50 |
Number of hours cooling loads not met | 456.50 |
Number of hours not met | 462.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 22204.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 1.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Cooling | 1315.56 | 97251.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.70 | 2063.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.63 | 3835.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 807.36 | 25601.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 816.51 | 79739.68 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 56867.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3989.90 | 816.51 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3989.90 |
Natural Gas | 0.00 | 816.51 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4806.42 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 0.23 |
Space Cooling | 167.88 |
Fans-Interior | 103.03 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 40.54 |
Subtotal | 509.14 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 104.19 |
Miscellaneous | 0.00 |
Subtotal | 104.19 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.66 |
Space Heating | 0.04 |
Space Cooling | 27.37 |
Fans-Interior | 16.80 |
Service Water Heating | 16.99 |
Receptacle Equipment | 23.53 |
Miscellaneous | 6.61 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.298914 |
G NW APARTMENT DIRECT AIR | 0.302933 |
OFFICE DIRECT AIR | 0.359543 |
G NE APARTMENT DIRECT AIR | 0.254081 |
G N1 APARTMENT DIRECT AIR | 0.178058 |
G N2 APARTMENT DIRECT AIR | 0.177210 |
G S1 APARTMENT DIRECT AIR | 0.170675 |
G S2 APARTMENT DIRECT AIR | 0.174820 |
F2 SW APARTMENT DIRECT AIR | 0.360550 |
F2 NW APARTMENT DIRECT AIR | 0.364920 |
F2 SE APARTMENT DIRECT AIR | 0.329128 |
F2 NE APARTMENT DIRECT AIR | 0.309531 |
F2 N1 APARTMENT DIRECT AIR | 0.219831 |
F2 N2 APARTMENT DIRECT AIR | 0.219149 |
F2 S1 APARTMENT DIRECT AIR | 0.211660 |
F2 S2 APARTMENT DIRECT AIR | 0.212733 |
F3 SW APARTMENT DIRECT AIR | 0.360872 |
F3 NW APARTMENT DIRECT AIR | 0.365515 |
F3 SE APARTMENT DIRECT AIR | 0.316108 |
F3 NE APARTMENT DIRECT AIR | 0.311875 |
F3 N1 APARTMENT DIRECT AIR | 0.221509 |
F3 N2 APARTMENT DIRECT AIR | 0.220835 |
F3 S1 APARTMENT DIRECT AIR | 0.213566 |
F3 S2 APARTMENT DIRECT AIR | 0.213873 |
F4 SW APARTMENT DIRECT AIR | 0.362762 |
F4 NW APARTMENT DIRECT AIR | 0.367352 |
F4 SE APARTMENT DIRECT AIR | 0.317144 |
F4 NE APARTMENT DIRECT AIR | 0.313944 |
F4 N1 APARTMENT DIRECT AIR | 0.223492 |
F4 N2 APARTMENT DIRECT AIR | 0.222825 |
F4 S1 APARTMENT DIRECT AIR | 0.215597 |
F4 S2 APARTMENT DIRECT AIR | 0.215783 |
M SW APARTMENT DIRECT AIR | 0.366862 |
M NW APARTMENT DIRECT AIR | 0.371484 |
M SE APARTMENT DIRECT AIR | 0.321633 |
M NE APARTMENT DIRECT AIR | 0.318230 |
M N1 APARTMENT DIRECT AIR | 0.227649 |
M N2 APARTMENT DIRECT AIR | 0.226987 |
M S1 APARTMENT DIRECT AIR | 0.219701 |
M S2 APARTMENT DIRECT AIR | 0.219861 |
F6 SW APARTMENT DIRECT AIR | 0.364526 |
F6 NW APARTMENT DIRECT AIR | 0.369000 |
F6 SE APARTMENT DIRECT AIR | 0.319805 |
F6 NE APARTMENT DIRECT AIR | 0.315950 |
F6 N1 APARTMENT DIRECT AIR | 0.225339 |
F6 N2 APARTMENT DIRECT AIR | 0.224684 |
F6 S1 APARTMENT DIRECT AIR | 0.217513 |
F6 S2 APARTMENT DIRECT AIR | 0.217663 |
F7 SW APARTMENT DIRECT AIR | 0.364429 |
F7 NW APARTMENT DIRECT AIR | 0.368875 |
F7 SE APARTMENT DIRECT AIR | 0.320140 |
F7 NE APARTMENT DIRECT AIR | 0.315985 |
F7 N1 APARTMENT DIRECT AIR | 0.225304 |
F7 N2 APARTMENT DIRECT AIR | 0.224655 |
F7 S1 APARTMENT DIRECT AIR | 0.217494 |
F7 S2 APARTMENT DIRECT AIR | 0.217637 |
F8 SW APARTMENT DIRECT AIR | 0.365794 |
F8 NW APARTMENT DIRECT AIR | 0.370192 |
F8 SE APARTMENT DIRECT AIR | 0.321843 |
F8 NE APARTMENT DIRECT AIR | 0.317384 |
F8 N1 APARTMENT DIRECT AIR | 0.226705 |
F8 N2 APARTMENT DIRECT AIR | 0.226061 |
F8 S1 APARTMENT DIRECT AIR | 0.218881 |
F8 S2 APARTMENT DIRECT AIR | 0.219023 |
F9 SW APARTMENT DIRECT AIR | 0.377391 |
F9 NW APARTMENT DIRECT AIR | 0.381897 |
F9 SE APARTMENT DIRECT AIR | 0.332454 |
F9 NE APARTMENT DIRECT AIR | 0.329188 |
F9 N1 APARTMENT DIRECT AIR | 0.237398 |
F9 N2 APARTMENT DIRECT AIR | 0.236757 |
F9 S1 APARTMENT DIRECT AIR | 0.228271 |
F9 S2 APARTMENT DIRECT AIR | 0.228145 |
T SW APARTMENT DIRECT AIR | 0.445446 |
T NW APARTMENT DIRECT AIR | 0.447036 |
T SE APARTMENT DIRECT AIR | 0.397278 |
T NE APARTMENT DIRECT AIR | 0.388837 |
T N1 APARTMENT DIRECT AIR | 0.290406 |
T N2 APARTMENT DIRECT AIR | 0.289194 |
T S1 APARTMENT DIRECT AIR | 0.296066 |
T S2 APARTMENT DIRECT AIR | 0.296169 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.298914 |
AIRLOOP G NW MAIN BRANCH | 0.302933 |
AIRLOOP OFFICE MAIN BRANCH | 0.359543 |
AIRLOOP G NE MAIN BRANCH | 0.254081 |
AIRLOOP G N1 MAIN BRANCH | 0.178058 |
AIRLOOP G N2 MAIN BRANCH | 0.177210 |
AIRLOOP G S1 MAIN BRANCH | 0.170675 |
AIRLOOP G S2 MAIN BRANCH | 0.174820 |
AIRLOOP F2 SW MAIN BRANCH | 0.360550 |
AIRLOOP F2 NW MAIN BRANCH | 0.364920 |
AIRLOOP F2 SE MAIN BRANCH | 0.329128 |
AIRLOOP F2 NE MAIN BRANCH | 0.309531 |
AIRLOOP F2 N1 MAIN BRANCH | 0.219831 |
AIRLOOP F2 N2 MAIN BRANCH | 0.219149 |
AIRLOOP F2 S1 MAIN BRANCH | 0.211660 |
AIRLOOP F2 S2 MAIN BRANCH | 0.212733 |
AIRLOOP F3 SW MAIN BRANCH | 0.360872 |
AIRLOOP F3 NW MAIN BRANCH | 0.365515 |
AIRLOOP F3 SE MAIN BRANCH | 0.316108 |
AIRLOOP F3 NE MAIN BRANCH | 0.311875 |
AIRLOOP F3 N1 MAIN BRANCH | 0.221509 |
AIRLOOP F3 N2 MAIN BRANCH | 0.220835 |
AIRLOOP F3 S1 MAIN BRANCH | 0.213566 |
AIRLOOP F3 S2 MAIN BRANCH | 0.213873 |
AIRLOOP F4 SW MAIN BRANCH | 0.362762 |
AIRLOOP F4 NW MAIN BRANCH | 0.367352 |
AIRLOOP F4 SE MAIN BRANCH | 0.317144 |
AIRLOOP F4 NE MAIN BRANCH | 0.313944 |
AIRLOOP F4 N1 MAIN BRANCH | 0.223492 |
AIRLOOP F4 N2 MAIN BRANCH | 0.222825 |
AIRLOOP F4 S1 MAIN BRANCH | 0.215597 |
AIRLOOP F4 S2 MAIN BRANCH | 0.215783 |
AIRLOOP M SW MAIN BRANCH | 0.366862 |
AIRLOOP M NW MAIN BRANCH | 0.371484 |
AIRLOOP M SE MAIN BRANCH | 0.321633 |
AIRLOOP M NE MAIN BRANCH | 0.318230 |
AIRLOOP M N1 MAIN BRANCH | 0.227649 |
AIRLOOP M N2 MAIN BRANCH | 0.226987 |
AIRLOOP M S1 MAIN BRANCH | 0.219701 |
AIRLOOP M S2 MAIN BRANCH | 0.219861 |
AIRLOOP F6 SW MAIN BRANCH | 0.364526 |
AIRLOOP F6 NW MAIN BRANCH | 0.369000 |
AIRLOOP F6 SE MAIN BRANCH | 0.319805 |
AIRLOOP F6 NE MAIN BRANCH | 0.315950 |
AIRLOOP F6 N1 MAIN BRANCH | 0.225339 |
AIRLOOP F6 N2 MAIN BRANCH | 0.224684 |
AIRLOOP F6 S1 MAIN BRANCH | 0.217513 |
AIRLOOP F6 S2 MAIN BRANCH | 0.217663 |
AIRLOOP F7 SW MAIN BRANCH | 0.364429 |
AIRLOOP F7 NW MAIN BRANCH | 0.368875 |
AIRLOOP F7 SE MAIN BRANCH | 0.320140 |
AIRLOOP F7 NE MAIN BRANCH | 0.315985 |
AIRLOOP F7 N1 MAIN BRANCH | 0.225304 |
AIRLOOP F7 N2 MAIN BRANCH | 0.224655 |
AIRLOOP F7 S1 MAIN BRANCH | 0.217494 |
AIRLOOP F7 S2 MAIN BRANCH | 0.217637 |
AIRLOOP F8 SW MAIN BRANCH | 0.365794 |
AIRLOOP F8 NW MAIN BRANCH | 0.370192 |
AIRLOOP F8 SE MAIN BRANCH | 0.321843 |
AIRLOOP F8 NE MAIN BRANCH | 0.317384 |
AIRLOOP F8 N1 MAIN BRANCH | 0.226705 |
AIRLOOP F8 N2 MAIN BRANCH | 0.226061 |
AIRLOOP F8 S1 MAIN BRANCH | 0.218881 |
AIRLOOP F8 S2 MAIN BRANCH | 0.219023 |
AIRLOOP F9 SW MAIN BRANCH | 0.377391 |
AIRLOOP F9 NW MAIN BRANCH | 0.381897 |
AIRLOOP F9 SE MAIN BRANCH | 0.332454 |
AIRLOOP F9 NE MAIN BRANCH | 0.329188 |
AIRLOOP F9 N1 MAIN BRANCH | 0.237398 |
AIRLOOP F9 N2 MAIN BRANCH | 0.236757 |
AIRLOOP F9 S1 MAIN BRANCH | 0.228271 |
AIRLOOP F9 S2 MAIN BRANCH | 0.228145 |
AIRLOOP T SW MAIN BRANCH | 0.445446 |
AIRLOOP T NW MAIN BRANCH | 0.447036 |
AIRLOOP T SE MAIN BRANCH | 0.397278 |
AIRLOOP T NE MAIN BRANCH | 0.388837 |
AIRLOOP T N1 MAIN BRANCH | 0.290406 |
AIRLOOP T N2 MAIN BRANCH | 0.289194 |
AIRLOOP T S1 MAIN BRANCH | 0.296066 |
AIRLOOP T S2 MAIN BRANCH | 0.296169 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.298914 |
AIRLOOP G NW | 0.302933 |
AIRLOOP OFFICE | 0.359543 |
AIRLOOP G NE | 0.254081 |
AIRLOOP G N1 | 0.178058 |
AIRLOOP G N2 | 0.177210 |
AIRLOOP G S1 | 0.170675 |
AIRLOOP G S2 | 0.174820 |
AIRLOOP F2 SW | 0.360550 |
AIRLOOP F2 NW | 0.364920 |
AIRLOOP F2 SE | 0.329128 |
AIRLOOP F2 NE | 0.309531 |
AIRLOOP F2 N1 | 0.219831 |
AIRLOOP F2 N2 | 0.219149 |
AIRLOOP F2 S1 | 0.211660 |
AIRLOOP F2 S2 | 0.212733 |
AIRLOOP F3 SW | 0.360872 |
AIRLOOP F3 NW | 0.365515 |
AIRLOOP F3 SE | 0.316108 |
AIRLOOP F3 NE | 0.311875 |
AIRLOOP F3 N1 | 0.221509 |
AIRLOOP F3 N2 | 0.220835 |
AIRLOOP F3 S1 | 0.213566 |
AIRLOOP F3 S2 | 0.213873 |
AIRLOOP F4 SW | 0.362762 |
AIRLOOP F4 NW | 0.367352 |
AIRLOOP F4 SE | 0.317144 |
AIRLOOP F4 NE | 0.313944 |
AIRLOOP F4 N1 | 0.223492 |
AIRLOOP F4 N2 | 0.222825 |
AIRLOOP F4 S1 | 0.215597 |
AIRLOOP F4 S2 | 0.215783 |
AIRLOOP M SW | 0.366862 |
AIRLOOP M NW | 0.371484 |
AIRLOOP M SE | 0.321633 |
AIRLOOP M NE | 0.318230 |
AIRLOOP M N1 | 0.227649 |
AIRLOOP M N2 | 0.226987 |
AIRLOOP M S1 | 0.219701 |
AIRLOOP M S2 | 0.219861 |
AIRLOOP F6 SW | 0.364526 |
AIRLOOP F6 NW | 0.369000 |
AIRLOOP F6 SE | 0.319805 |
AIRLOOP F6 NE | 0.315950 |
AIRLOOP F6 N1 | 0.225339 |
AIRLOOP F6 N2 | 0.224684 |
AIRLOOP F6 S1 | 0.217513 |
AIRLOOP F6 S2 | 0.217663 |
AIRLOOP F7 SW | 0.364429 |
AIRLOOP F7 NW | 0.368875 |
AIRLOOP F7 SE | 0.320140 |
AIRLOOP F7 NE | 0.315985 |
AIRLOOP F7 N1 | 0.225304 |
AIRLOOP F7 N2 | 0.224655 |
AIRLOOP F7 S1 | 0.217494 |
AIRLOOP F7 S2 | 0.217637 |
AIRLOOP F8 SW | 0.365794 |
AIRLOOP F8 NW | 0.370192 |
AIRLOOP F8 SE | 0.321843 |
AIRLOOP F8 NE | 0.317384 |
AIRLOOP F8 N1 | 0.226705 |
AIRLOOP F8 N2 | 0.226061 |
AIRLOOP F8 S1 | 0.218881 |
AIRLOOP F8 S2 | 0.219023 |
AIRLOOP F9 SW | 0.377391 |
AIRLOOP F9 NW | 0.381897 |
AIRLOOP F9 SE | 0.332454 |
AIRLOOP F9 NE | 0.329188 |
AIRLOOP F9 N1 | 0.237398 |
AIRLOOP F9 N2 | 0.236757 |
AIRLOOP F9 S1 | 0.228271 |
AIRLOOP F9 S2 | 0.228145 |
AIRLOOP T SW | 0.445446 |
AIRLOOP T NW | 0.447036 |
AIRLOOP T SE | 0.397278 |
AIRLOOP T NE | 0.388837 |
AIRLOOP T N1 | 0.290406 |
AIRLOOP T N2 | 0.289194 |
AIRLOOP T S1 | 0.296066 |
AIRLOOP T S2 | 0.296169 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.298914 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.302933 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.359543 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.254081 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.178058 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.177210 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.170675 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.174820 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.360550 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.364920 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.329128 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.309531 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.219831 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.219149 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.211660 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.212733 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.360872 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.365515 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.316108 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.311875 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.221509 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.220835 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.213566 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.213873 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.362762 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.367352 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.317144 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.313944 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.223492 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.222825 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.215597 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.215783 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.366862 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.371484 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.321633 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.318230 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.227649 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.226987 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.219701 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.219861 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.364526 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.369000 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.319805 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.315950 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.225339 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.224684 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.217513 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.217663 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.364429 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.368875 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.320140 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.315985 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.225304 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.224655 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.217494 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.217637 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.365794 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.370192 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.321843 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.317384 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.226705 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.226061 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.218881 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.219023 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.377391 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.381897 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.332454 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.329188 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.237398 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.236757 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.228271 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.228145 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.445446 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.447036 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.397278 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.388837 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.290406 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.289194 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.296066 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.296169 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.298914 | 4719.02 | 3392.18 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.302933 | 4766.05 | 3430.38 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.359543 | 5756.58 | 4116.18 | 0.000126 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.254081 | 4065.21 | 2903.98 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.178058 | 3008.39 | 2096.68 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.177210 | 2996.57 | 2087.67 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.170675 | 2956.72 | 2040.86 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.174820 | 3014.41 | 2085.06 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.360550 | 5577.89 | 4043.95 | 0.000122 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.364920 | 5629.91 | 4085.75 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.329128 | 5165.73 | 3722.46 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.309531 | 4839.07 | 3490.98 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.219831 | 3602.50 | 2545.53 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.219149 | 3593.03 | 2538.31 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.211660 | 3530.44 | 2477.96 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.212733 | 3545.32 | 2489.35 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.360872 | 5586.89 | 4048.51 | 0.000122 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.365515 | 5642.66 | 4093.18 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.316108 | 4947.97 | 3567.53 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.311875 | 4875.91 | 3516.84 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.221509 | 3628.33 | 2563.97 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.220835 | 3618.95 | 2556.83 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.213566 | 3559.38 | 2498.84 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.213873 | 3563.69 | 2502.11 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.362762 | 5616.41 | 4069.31 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.367352 | 5671.45 | 4113.41 | 0.000124 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.317144 | 5007.86 | 3598.04 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.313944 | 4907.85 | 3539.52 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.223492 | 3657.77 | 2585.47 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.222825 | 3648.49 | 2578.40 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.215597 | 3589.46 | 2520.89 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.215783 | 3592.09 | 2522.88 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.366862 | 5675.84 | 4113.23 | 0.000124 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.371484 | 5731.32 | 4157.66 | 0.000125 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.321633 | 5072.66 | 3646.12 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.318230 | 4969.83 | 3585.41 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.227649 | 3717.07 | 2629.91 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.226987 | 3707.87 | 2622.90 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.219701 | 3647.96 | 2564.83 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.219861 | 3650.23 | 2566.55 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.364526 | 5645.98 | 4089.24 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.369000 | 5699.41 | 4132.12 | 0.000125 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.319805 | 5049.70 | 3627.44 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.315950 | 4940.68 | 3561.99 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.225339 | 3686.31 | 2605.79 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.224684 | 3677.21 | 2598.86 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.217513 | 3618.92 | 2541.98 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.217663 | 3621.06 | 2543.58 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.364429 | 5646.75 | 4088.76 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.368875 | 5699.79 | 4131.34 | 0.000125 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.320140 | 5056.38 | 3631.50 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.315985 | 4943.22 | 3562.89 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.225304 | 3687.01 | 2605.74 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.224655 | 3677.99 | 2598.86 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.217494 | 3619.83 | 2542.08 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.217637 | 3621.79 | 2543.59 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.365794 | 5667.50 | 4103.63 | 0.000124 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.370192 | 5719.88 | 4145.70 | 0.000125 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.321843 | 5081.77 | 3649.95 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.317384 | 4964.42 | 3578.12 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.226705 | 3703.31 | 2618.61 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.226061 | 3694.36 | 2611.79 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.218881 | 3640.12 | 2557.07 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.219023 | 3642.09 | 2558.58 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.377391 | 5829.44 | 4226.26 | 0.000127 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.381897 | 5883.32 | 4269.44 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.332454 | 5230.18 | 3762.33 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.329188 | 5159.08 | 3716.10 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.237398 | 3852.86 | 2732.07 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.236757 | 3843.95 | 2725.29 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.228271 | 3763.32 | 2653.47 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.228145 | 3769.68 | 2655.57 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.445446 | 6779.94 | 4947.51 | 0.000148 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.447036 | 6792.44 | 4959.90 | 0.000148 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.397278 | 6127.47 | 4446.00 | 0.000134 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.388837 | 6010.91 | 4357.09 | 0.000131 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.290406 | 4607.03 | 3302.86 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.289194 | 4608.09 | 3298.09 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.296066 | 4711.36 | 3374.25 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.296169 | 4712.76 | 3375.33 | 0.000103 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.298914 | 0.298914 | 0.298914 | 0.298914 | 4719.02 | 4719.02 | 1660.45 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.302933 | 0.302933 | 0.302933 | 0.302933 | 4766.05 | 4766.05 | 1660.53 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.359543 | 0.359543 | 0.359543 | 0.359543 | 5756.58 | 5756.58 | 2265.94 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.254081 | 0.254081 | 0.254081 | 0.254081 | 4065.21 | 4065.21 | 1662.50 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.178058 | 0.178058 | 0.178058 | 0.178058 | 3008.39 | 3008.39 | 1152.10 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.177210 | 0.177210 | 0.177210 | 0.177210 | 2996.57 | 2996.57 | 1152.15 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.170675 | 0.170675 | 0.170675 | 0.170675 | 2956.72 | 2956.72 | 1149.05 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.174820 | 0.174820 | 0.174820 | 0.174820 | 3014.41 | 3014.41 | 1156.00 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.360550 | 0.360550 | 0.360550 | 0.360550 | 5577.89 | 5577.89 | 1671.84 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.364920 | 0.364920 | 0.364920 | 0.364920 | 5629.91 | 5629.91 | 1671.14 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.329128 | 0.329128 | 0.329128 | 0.329128 | 5165.73 | 5165.73 | 1699.62 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.309531 | 0.309531 | 0.309531 | 0.309531 | 4839.07 | 4839.07 | 1674.21 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.219831 | 0.219831 | 0.219831 | 0.219831 | 3602.50 | 3602.50 | 1061.92 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.219149 | 0.219149 | 0.219149 | 0.219149 | 3593.03 | 3593.03 | 1062.00 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.211660 | 0.211660 | 0.211660 | 0.211660 | 3530.44 | 3530.44 | 1064.25 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.212733 | 0.212733 | 0.212733 | 0.212733 | 3545.32 | 3545.32 | 1066.02 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.360872 | 0.360872 | 0.360872 | 0.360872 | 5586.89 | 5586.89 | 1622.43 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.365515 | 0.365515 | 0.365515 | 0.365515 | 5642.66 | 5642.66 | 1622.42 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.316108 | 0.316108 | 0.316108 | 0.316108 | 4947.97 | 4947.97 | 1628.79 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.311875 | 0.311875 | 0.311875 | 0.311875 | 4875.91 | 4875.91 | 1625.98 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.221509 | 0.221509 | 0.221509 | 0.221509 | 3628.33 | 3628.33 | 1031.58 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.220835 | 0.220835 | 0.220835 | 0.220835 | 3618.95 | 3618.95 | 1031.58 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.213566 | 0.213566 | 0.213566 | 0.213566 | 3559.38 | 3559.38 | 1031.58 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.213873 | 0.213873 | 0.213873 | 0.213873 | 3563.69 | 3563.69 | 1031.58 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.362762 | 0.362762 | 0.362762 | 0.362762 | 5616.41 | 5616.41 | 1608.81 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.367352 | 0.367352 | 0.367352 | 0.367352 | 5671.45 | 5671.45 | 1609.21 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.317144 | 0.317144 | 0.317144 | 0.317144 | 5007.86 | 5007.86 | 1613.03 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.313944 | 0.313944 | 0.313944 | 0.313944 | 4907.85 | 4907.85 | 1613.12 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.223492 | 0.223492 | 0.223492 | 0.223492 | 3657.77 | 3657.77 | 1031.58 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.222825 | 0.222825 | 0.222825 | 0.222825 | 3648.49 | 3648.49 | 1031.58 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.215597 | 0.215597 | 0.215597 | 0.215597 | 3589.46 | 3589.46 | 1031.58 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.215783 | 0.215783 | 0.215783 | 0.215783 | 3592.09 | 3592.09 | 1031.58 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.366862 | 0.366862 | 0.366862 | 0.366862 | 5675.84 | 5675.84 | 1578.81 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.371484 | 0.371484 | 0.371484 | 0.371484 | 5731.32 | 5731.32 | 1578.18 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.321633 | 0.321633 | 0.321633 | 0.321633 | 5072.66 | 5072.66 | 1583.02 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.318230 | 0.318230 | 0.318230 | 0.318230 | 4969.83 | 4969.83 | 1582.34 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.227649 | 0.227649 | 0.227649 | 0.227649 | 3717.07 | 3717.07 | 1031.58 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.226987 | 0.226987 | 0.226987 | 0.226987 | 3707.87 | 3707.87 | 1031.58 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.219701 | 0.219701 | 0.219701 | 0.219701 | 3647.96 | 3647.96 | 1031.58 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.219861 | 0.219861 | 0.219861 | 0.219861 | 3650.23 | 3650.23 | 1031.58 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.364526 | 0.364526 | 0.364526 | 0.364526 | 5645.98 | 5645.98 | 1619.22 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.369000 | 0.369000 | 0.369000 | 0.369000 | 5699.41 | 5699.41 | 1619.59 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.319805 | 0.319805 | 0.319805 | 0.319805 | 5049.70 | 5049.70 | 1623.63 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.315950 | 0.315950 | 0.315950 | 0.315950 | 4940.68 | 4940.68 | 1623.98 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.225339 | 0.225339 | 0.225339 | 0.225339 | 3686.31 | 3686.31 | 1031.58 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.224684 | 0.224684 | 0.224684 | 0.224684 | 3677.21 | 3677.21 | 1031.58 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.217513 | 0.217513 | 0.217513 | 0.217513 | 3618.92 | 3618.92 | 1031.58 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.217663 | 0.217663 | 0.217663 | 0.217663 | 3621.06 | 3621.06 | 1031.58 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.364429 | 0.364429 | 0.364429 | 0.364429 | 5646.75 | 5646.75 | 1636.36 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.368875 | 0.368875 | 0.368875 | 0.368875 | 5699.79 | 5699.79 | 1636.50 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.320140 | 0.320140 | 0.320140 | 0.320140 | 5056.38 | 5056.38 | 1640.94 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.315985 | 0.315985 | 0.315985 | 0.315985 | 4943.22 | 4943.22 | 1641.07 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.225304 | 0.225304 | 0.225304 | 0.225304 | 3687.01 | 3687.01 | 1031.58 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.224655 | 0.224655 | 0.224655 | 0.224655 | 3677.99 | 3677.99 | 1031.58 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.217494 | 0.217494 | 0.217494 | 0.217494 | 3619.83 | 3619.83 | 1031.58 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.217637 | 0.217637 | 0.217637 | 0.217637 | 3621.79 | 3621.79 | 1031.58 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.365794 | 0.365794 | 0.365794 | 0.365794 | 5667.50 | 5667.50 | 1656.48 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.370192 | 0.370192 | 0.370192 | 0.370192 | 5719.88 | 5719.88 | 1656.16 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.321843 | 0.321843 | 0.321843 | 0.321843 | 5081.77 | 5081.77 | 1661.21 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.317384 | 0.317384 | 0.317384 | 0.317384 | 4964.42 | 4964.42 | 1660.88 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.226705 | 0.226705 | 0.226705 | 0.226705 | 3703.31 | 3703.31 | 1035.07 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.226061 | 0.226061 | 0.226061 | 0.226061 | 3694.36 | 3694.36 | 1035.19 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.218881 | 0.218881 | 0.218881 | 0.218881 | 3640.12 | 3640.12 | 1034.58 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.219023 | 0.219023 | 0.219023 | 0.219023 | 3642.09 | 3642.09 | 1034.70 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.377391 | 0.377391 | 0.377391 | 0.377391 | 5829.44 | 5829.44 | 1764.40 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.381897 | 0.381897 | 0.381897 | 0.381897 | 5883.32 | 5883.32 | 1761.39 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.332454 | 0.332454 | 0.332454 | 0.332454 | 5230.18 | 5230.18 | 1769.31 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.329188 | 0.329188 | 0.329188 | 0.329188 | 5159.08 | 5159.08 | 1766.28 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.237398 | 0.237398 | 0.237398 | 0.237398 | 3852.86 | 3852.86 | 1132.72 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.236757 | 0.236757 | 0.236757 | 0.236757 | 3843.95 | 3843.95 | 1132.84 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.228271 | 0.228271 | 0.228271 | 0.228271 | 3763.32 | 3763.32 | 1134.63 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.228145 | 0.228145 | 0.228145 | 0.228145 | 3769.68 | 3769.68 | 1134.75 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.445446 | 0.445446 | 0.445446 | 0.445446 | 6779.94 | 6779.94 | 2122.87 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.447036 | 0.447036 | 0.447036 | 0.447036 | 6792.44 | 6792.44 | 2125.36 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.397278 | 0.397278 | 0.397278 | 0.397278 | 6127.47 | 6127.47 | 2127.45 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.388837 | 0.388837 | 0.388837 | 0.388837 | 6010.91 | 6010.91 | 2129.93 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.290406 | 0.290406 | 0.290406 | 0.290406 | 4607.03 | 4607.03 | 1549.45 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.289194 | 0.289194 | 0.289194 | 0.289194 | 4608.09 | 4608.09 | 1549.58 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.296066 | 0.296066 | 0.296066 | 0.296066 | 4711.36 | 4711.36 | 1544.14 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.296169 | 0.296169 | 0.296169 | 0.296169 | 4712.76 | 4712.76 | 1544.27 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.298914 |
AIRLOOP G NW SUPPLY FAN | 0.302933 |
AIRLOOP OFFICE SUPPLY FAN | 0.359543 |
AIRLOOP G NE SUPPLY FAN | 0.254081 |
AIRLOOP G N1 SUPPLY FAN | 0.178058 |
AIRLOOP G N2 SUPPLY FAN | 0.177210 |
AIRLOOP G S1 SUPPLY FAN | 0.170675 |
AIRLOOP G S2 SUPPLY FAN | 0.174820 |
AIRLOOP F2 SW SUPPLY FAN | 0.360550 |
AIRLOOP F2 NW SUPPLY FAN | 0.364920 |
AIRLOOP F2 SE SUPPLY FAN | 0.329128 |
AIRLOOP F2 NE SUPPLY FAN | 0.309531 |
AIRLOOP F2 N1 SUPPLY FAN | 0.219831 |
AIRLOOP F2 N2 SUPPLY FAN | 0.219149 |
AIRLOOP F2 S1 SUPPLY FAN | 0.211660 |
AIRLOOP F2 S2 SUPPLY FAN | 0.212733 |
AIRLOOP F3 SW SUPPLY FAN | 0.360872 |
AIRLOOP F3 NW SUPPLY FAN | 0.365515 |
AIRLOOP F3 SE SUPPLY FAN | 0.316108 |
AIRLOOP F3 NE SUPPLY FAN | 0.311875 |
AIRLOOP F3 N1 SUPPLY FAN | 0.221509 |
AIRLOOP F3 N2 SUPPLY FAN | 0.220835 |
AIRLOOP F3 S1 SUPPLY FAN | 0.213566 |
AIRLOOP F3 S2 SUPPLY FAN | 0.213873 |
AIRLOOP F4 SW SUPPLY FAN | 0.362762 |
AIRLOOP F4 NW SUPPLY FAN | 0.367352 |
AIRLOOP F4 SE SUPPLY FAN | 0.317144 |
AIRLOOP F4 NE SUPPLY FAN | 0.313944 |
AIRLOOP F4 N1 SUPPLY FAN | 0.223492 |
AIRLOOP F4 N2 SUPPLY FAN | 0.222825 |
AIRLOOP F4 S1 SUPPLY FAN | 0.215597 |
AIRLOOP F4 S2 SUPPLY FAN | 0.215783 |
AIRLOOP M SW SUPPLY FAN | 0.366862 |
AIRLOOP M NW SUPPLY FAN | 0.371484 |
AIRLOOP M SE SUPPLY FAN | 0.321633 |
AIRLOOP M NE SUPPLY FAN | 0.318230 |
AIRLOOP M N1 SUPPLY FAN | 0.227649 |
AIRLOOP M N2 SUPPLY FAN | 0.226987 |
AIRLOOP M S1 SUPPLY FAN | 0.219701 |
AIRLOOP M S2 SUPPLY FAN | 0.219861 |
AIRLOOP F6 SW SUPPLY FAN | 0.364526 |
AIRLOOP F6 NW SUPPLY FAN | 0.369000 |
AIRLOOP F6 SE SUPPLY FAN | 0.319805 |
AIRLOOP F6 NE SUPPLY FAN | 0.315950 |
AIRLOOP F6 N1 SUPPLY FAN | 0.225339 |
AIRLOOP F6 N2 SUPPLY FAN | 0.224684 |
AIRLOOP F6 S1 SUPPLY FAN | 0.217513 |
AIRLOOP F6 S2 SUPPLY FAN | 0.217663 |
AIRLOOP F7 SW SUPPLY FAN | 0.364429 |
AIRLOOP F7 NW SUPPLY FAN | 0.368875 |
AIRLOOP F7 SE SUPPLY FAN | 0.320140 |
AIRLOOP F7 NE SUPPLY FAN | 0.315985 |
AIRLOOP F7 N1 SUPPLY FAN | 0.225304 |
AIRLOOP F7 N2 SUPPLY FAN | 0.224655 |
AIRLOOP F7 S1 SUPPLY FAN | 0.217494 |
AIRLOOP F7 S2 SUPPLY FAN | 0.217637 |
AIRLOOP F8 SW SUPPLY FAN | 0.365794 |
AIRLOOP F8 NW SUPPLY FAN | 0.370192 |
AIRLOOP F8 SE SUPPLY FAN | 0.321843 |
AIRLOOP F8 NE SUPPLY FAN | 0.317384 |
AIRLOOP F8 N1 SUPPLY FAN | 0.226705 |
AIRLOOP F8 N2 SUPPLY FAN | 0.226061 |
AIRLOOP F8 S1 SUPPLY FAN | 0.218881 |
AIRLOOP F8 S2 SUPPLY FAN | 0.219023 |
AIRLOOP F9 SW SUPPLY FAN | 0.377391 |
AIRLOOP F9 NW SUPPLY FAN | 0.381897 |
AIRLOOP F9 SE SUPPLY FAN | 0.332454 |
AIRLOOP F9 NE SUPPLY FAN | 0.329188 |
AIRLOOP F9 N1 SUPPLY FAN | 0.237398 |
AIRLOOP F9 N2 SUPPLY FAN | 0.236757 |
AIRLOOP F9 S1 SUPPLY FAN | 0.228271 |
AIRLOOP F9 S2 SUPPLY FAN | 0.228145 |
AIRLOOP T SW SUPPLY FAN | 0.445446 |
AIRLOOP T NW SUPPLY FAN | 0.447036 |
AIRLOOP T SE SUPPLY FAN | 0.397278 |
AIRLOOP T NE SUPPLY FAN | 0.388837 |
AIRLOOP T N1 SUPPLY FAN | 0.290406 |
AIRLOOP T N2 SUPPLY FAN | 0.289194 |
AIRLOOP T S1 SUPPLY FAN | 0.296066 |
AIRLOOP T S2 SUPPLY FAN | 0.296169 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.298914 | 4719.02 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.302933 | 4766.05 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.359543 | 5756.58 | 0.000126 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.254081 | 4065.21 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.178058 | 3008.39 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.177210 | 2996.57 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.170675 | 2956.72 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.174820 | 3014.41 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.360550 | 5577.89 | 0.000122 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.364920 | 5629.91 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.329128 | 5165.73 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.309531 | 4839.07 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.219831 | 3602.50 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.219149 | 3593.03 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.211660 | 3530.44 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.212733 | 3545.32 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.360872 | 5586.89 | 0.000122 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.365515 | 5642.66 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.316108 | 4947.97 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.311875 | 4875.91 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.221509 | 3628.33 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.220835 | 3618.95 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.213566 | 3559.38 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.213873 | 3563.69 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.362762 | 5616.41 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.367352 | 5671.45 | 0.000124 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.317144 | 5007.86 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.313944 | 4907.85 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.223492 | 3657.77 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.222825 | 3648.49 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.215597 | 3589.46 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.215783 | 3592.09 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.366862 | 5675.84 | 0.000124 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.371484 | 5731.32 | 0.000125 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.321633 | 5072.66 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.318230 | 4969.83 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.227649 | 3717.07 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.226987 | 3707.87 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.219701 | 3647.96 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.219861 | 3650.23 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.364526 | 5645.98 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.369000 | 5699.41 | 0.000125 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.319805 | 5049.70 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.315950 | 4940.68 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.225339 | 3686.31 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.224684 | 3677.21 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.217513 | 3618.92 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.217663 | 3621.06 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.364429 | 5646.75 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.368875 | 5699.79 | 0.000125 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.320140 | 5056.38 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.315985 | 4943.22 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.225304 | 3687.01 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.224655 | 3677.99 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.217494 | 3619.83 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.217637 | 3621.79 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.365794 | 5667.50 | 0.000124 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.370192 | 5719.88 | 0.000125 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.321843 | 5081.77 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.317384 | 4964.42 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.226705 | 3703.31 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.226061 | 3694.36 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.218881 | 3640.12 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.219023 | 3642.09 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.377391 | 5829.44 | 0.000127 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.381897 | 5883.32 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.332454 | 5230.18 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.329188 | 5159.08 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.237398 | 3852.86 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.236757 | 3843.95 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.228271 | 3763.32 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.228145 | 3769.68 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.445446 | 6779.94 | 0.000148 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.447036 | 6792.44 | 0.000148 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.397278 | 6127.47 | 0.000134 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.388837 | 6010.91 | 0.000131 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.290406 | 4607.03 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.289194 | 4608.09 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.296066 | 4711.36 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.296169 | 4712.76 | 0.000103 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 1660.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 1660.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2265.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 1662.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1152.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1152.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1149.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1156.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 1671.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 1671.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 1699.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 1674.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1061.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1062.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1064.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1066.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1622.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1622.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1628.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1625.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1608.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1609.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1613.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1613.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1578.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1578.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1583.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1582.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 1619.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 1619.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 1623.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 1623.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 1636.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 1636.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 1640.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 1641.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1031.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 1656.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 1656.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 1661.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 1660.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1035.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1035.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1034.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1034.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 1764.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 1761.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 1769.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 1766.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1132.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1132.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1134.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1134.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2122.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2125.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2127.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2129.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 1549.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 1549.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 1544.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 1544.27 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.007946 | 8.94 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.007946 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.007946 | 3835.78 | 10.36 | 11599.72 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.007946 | 2026.59 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 13.39 |
February | 23.56 | 16.97 |
March | 24.19 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.35 | 25.09 |
November | 24.04 | 19.63 |
December | 23.35 | 14.52 |
Annual Sum or Average | 24.08 | 24.88 |
Minimum of Months | 23.06 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 13.39 |
February | 23.20 | 16.97 |
March | 24.13 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.33 | 25.09 |
November | 23.80 | 19.63 |
December | 22.65 | 14.52 |
Annual Sum or Average | 23.91 | 24.88 |
Minimum of Months | 22.37 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.39 |
February | 23.68 | 16.97 |
March | 24.28 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.09 | 19.63 |
December | 23.32 | 14.52 |
Annual Sum or Average | 24.11 | 24.88 |
Minimum of Months | 23.13 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 13.39 |
February | 23.19 | 16.97 |
March | 24.12 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.33 | 25.09 |
November | 23.76 | 19.63 |
December | 22.56 | 14.52 |
Annual Sum or Average | 23.89 | 24.88 |
Minimum of Months | 22.28 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 13.39 |
February | 23.07 | 16.97 |
March | 24.06 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.43 | 33.60 |
July | 24.43 | 31.67 |
August | 24.41 | 30.03 |
September | 24.40 | 28.75 |
October | 24.32 | 25.09 |
November | 23.73 | 19.63 |
December | 22.49 | 14.52 |
Annual Sum or Average | 23.86 | 24.88 |
Minimum of Months | 22.19 | 13.39 |
Maximum of Months | 24.43 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 13.39 |
February | 23.07 | 16.97 |
March | 24.06 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.43 | 33.60 |
July | 24.43 | 31.67 |
August | 24.41 | 30.03 |
September | 24.40 | 28.75 |
October | 24.32 | 25.09 |
November | 23.72 | 19.63 |
December | 22.48 | 14.52 |
Annual Sum or Average | 23.86 | 24.88 |
Minimum of Months | 22.19 | 13.39 |
Maximum of Months | 24.43 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 13.39 |
February | 23.59 | 16.97 |
March | 24.17 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.43 | 33.60 |
July | 24.45 | 31.67 |
August | 24.45 | 30.03 |
September | 24.47 | 28.75 |
October | 24.35 | 25.09 |
November | 24.06 | 19.63 |
December | 23.43 | 14.52 |
Annual Sum or Average | 24.11 | 24.88 |
Minimum of Months | 23.11 | 13.39 |
Maximum of Months | 24.47 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.39 |
February | 23.61 | 16.97 |
March | 24.17 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.42 | 33.60 |
July | 24.44 | 31.67 |
August | 24.44 | 30.03 |
September | 24.46 | 28.75 |
October | 24.35 | 25.09 |
November | 24.07 | 19.63 |
December | 23.45 | 14.52 |
Annual Sum or Average | 24.11 | 24.88 |
Minimum of Months | 23.13 | 13.39 |
Maximum of Months | 24.46 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.57 | 13.39 |
February | 22.19 | 16.97 |
March | 24.48 | 22.37 |
April | 26.96 | 29.13 |
May | 28.21 | 32.98 |
June | 28.73 | 33.60 |
July | 28.12 | 31.67 |
August | 27.60 | 30.03 |
September | 27.22 | 28.75 |
October | 25.71 | 25.09 |
November | 23.57 | 19.63 |
December | 21.22 | 14.52 |
Annual Sum or Average | 25.39 | 24.88 |
Minimum of Months | 20.57 | 13.39 |
Maximum of Months | 28.73 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.78 | 13.39 |
February | 24.09 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.34 | 19.63 |
December | 24.02 | 14.52 |
Annual Sum or Average | 24.28 | 24.88 |
Minimum of Months | 23.78 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 13.39 |
February | 23.78 | 16.97 |
March | 24.31 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.22 | 19.63 |
December | 23.33 | 14.52 |
Annual Sum or Average | 24.11 | 24.88 |
Minimum of Months | 22.87 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.79 | 13.39 |
February | 24.11 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.34 | 19.63 |
December | 24.02 | 14.52 |
Annual Sum or Average | 24.28 | 24.88 |
Minimum of Months | 23.79 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 13.39 |
February | 23.76 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.21 | 19.63 |
December | 23.21 | 14.52 |
Annual Sum or Average | 24.09 | 24.88 |
Minimum of Months | 22.76 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 13.39 |
February | 23.75 | 16.97 |
March | 24.30 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.20 | 19.63 |
December | 23.27 | 14.52 |
Annual Sum or Average | 24.09 | 24.88 |
Minimum of Months | 22.76 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 13.39 |
February | 23.75 | 16.97 |
March | 24.30 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.20 | 19.63 |
December | 23.26 | 14.52 |
Annual Sum or Average | 24.09 | 24.88 |
Minimum of Months | 22.75 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.91 | 13.39 |
February | 24.14 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.43 | 31.67 |
August | 24.43 | 30.03 |
September | 24.45 | 28.75 |
October | 24.42 | 25.09 |
November | 24.35 | 19.63 |
December | 24.13 | 14.52 |
Annual Sum or Average | 24.32 | 24.88 |
Minimum of Months | 23.91 | 13.39 |
Maximum of Months | 24.45 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.92 | 13.39 |
February | 24.14 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.43 | 30.03 |
September | 24.45 | 28.75 |
October | 24.42 | 25.09 |
November | 24.35 | 19.63 |
December | 24.13 | 14.52 |
Annual Sum or Average | 24.32 | 24.88 |
Minimum of Months | 23.92 | 13.39 |
Maximum of Months | 24.45 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 13.39 |
February | 25.02 | 16.97 |
March | 26.08 | 22.37 |
April | 26.88 | 29.13 |
May | 27.24 | 32.98 |
June | 27.33 | 33.60 |
July | 27.16 | 31.67 |
August | 26.98 | 30.03 |
September | 26.84 | 28.75 |
October | 26.49 | 25.09 |
November | 25.75 | 19.63 |
December | 24.54 | 14.52 |
Annual Sum or Average | 26.20 | 24.88 |
Minimum of Months | 24.04 | 13.39 |
Maximum of Months | 27.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 13.39 |
February | 24.16 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.35 | 19.63 |
December | 24.13 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.93 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 13.39 |
February | 23.90 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.53 | 14.52 |
Annual Sum or Average | 24.16 | 24.88 |
Minimum of Months | 23.06 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 13.39 |
February | 24.14 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.35 | 19.63 |
December | 24.09 | 14.52 |
Annual Sum or Average | 24.30 | 24.88 |
Minimum of Months | 23.88 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.94 | 13.39 |
February | 23.88 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.26 | 19.63 |
December | 23.42 | 14.52 |
Annual Sum or Average | 24.14 | 24.88 |
Minimum of Months | 22.94 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 13.39 |
February | 23.91 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.26 | 19.63 |
December | 23.54 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.02 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.39 |
February | 23.91 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.26 | 19.63 |
December | 23.53 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.01 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.39 |
February | 24.21 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.43 | 30.03 |
September | 24.45 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.23 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.08 | 13.39 |
Maximum of Months | 24.45 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.39 |
February | 24.21 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.43 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.23 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.08 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.55 | 13.39 |
February | 25.44 | 16.97 |
March | 26.34 | 22.37 |
April | 27.01 | 29.13 |
May | 27.28 | 32.98 |
June | 27.29 | 33.60 |
July | 27.14 | 31.67 |
August | 26.99 | 30.03 |
September | 26.87 | 28.75 |
October | 26.66 | 25.09 |
November | 26.08 | 19.63 |
December | 25.04 | 14.52 |
Annual Sum or Average | 26.39 | 24.88 |
Minimum of Months | 24.55 | 13.39 |
Maximum of Months | 27.29 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | 13.39 |
February | 24.17 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.15 | 14.52 |
Annual Sum or Average | 24.32 | 24.88 |
Minimum of Months | 23.97 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 13.39 |
February | 23.92 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.60 | 14.52 |
Annual Sum or Average | 24.17 | 24.88 |
Minimum of Months | 23.14 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.92 | 13.39 |
February | 24.15 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.11 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.92 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 13.39 |
February | 23.91 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.50 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.02 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 13.39 |
February | 23.95 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.64 | 14.52 |
Annual Sum or Average | 24.18 | 24.88 |
Minimum of Months | 23.14 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.39 |
February | 23.95 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.63 | 14.52 |
Annual Sum or Average | 24.18 | 24.88 |
Minimum of Months | 23.13 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.13 | 13.39 |
February | 24.22 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.43 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.25 | 14.52 |
Annual Sum or Average | 24.36 | 24.88 |
Minimum of Months | 24.13 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.12 | 13.39 |
February | 24.22 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.25 | 14.52 |
Annual Sum or Average | 24.36 | 24.88 |
Minimum of Months | 24.12 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.77 | 13.39 |
February | 25.61 | 16.97 |
March | 26.47 | 22.37 |
April | 27.10 | 29.13 |
May | 27.37 | 32.98 |
June | 27.36 | 33.60 |
July | 27.21 | 31.67 |
August | 27.07 | 30.03 |
September | 26.95 | 28.75 |
October | 26.77 | 25.09 |
November | 26.23 | 19.63 |
December | 25.25 | 14.52 |
Annual Sum or Average | 26.52 | 24.88 |
Minimum of Months | 24.77 | 13.39 |
Maximum of Months | 27.37 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.01 | 13.39 |
February | 24.18 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.17 | 14.52 |
Annual Sum or Average | 24.32 | 24.88 |
Minimum of Months | 24.01 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 13.39 |
February | 23.95 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.29 | 19.63 |
December | 23.65 | 14.52 |
Annual Sum or Average | 24.18 | 24.88 |
Minimum of Months | 23.21 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 13.39 |
February | 24.16 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.13 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.96 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.08 | 13.39 |
February | 23.94 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.29 | 19.63 |
December | 23.55 | 14.52 |
Annual Sum or Average | 24.17 | 24.88 |
Minimum of Months | 23.08 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 13.39 |
February | 23.99 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.29 | 19.63 |
December | 23.70 | 14.52 |
Annual Sum or Average | 24.19 | 24.88 |
Minimum of Months | 23.23 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 13.39 |
February | 23.99 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.29 | 19.63 |
December | 23.70 | 14.52 |
Annual Sum or Average | 24.19 | 24.88 |
Minimum of Months | 23.22 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.16 | 13.39 |
February | 24.23 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.27 | 14.52 |
Annual Sum or Average | 24.36 | 24.88 |
Minimum of Months | 24.16 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.16 | 13.39 |
February | 24.23 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.38 | 19.63 |
December | 24.27 | 14.52 |
Annual Sum or Average | 24.36 | 24.88 |
Minimum of Months | 24.16 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.44 | 13.39 |
February | 26.24 | 16.97 |
March | 27.07 | 22.37 |
April | 27.69 | 29.13 |
May | 27.95 | 32.98 |
June | 27.94 | 33.60 |
July | 27.79 | 31.67 |
August | 27.65 | 30.03 |
September | 27.53 | 28.75 |
October | 27.37 | 25.09 |
November | 26.85 | 19.63 |
December | 25.90 | 14.52 |
Annual Sum or Average | 27.12 | 24.88 |
Minimum of Months | 25.44 | 13.39 |
Maximum of Months | 27.95 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | 13.39 |
February | 24.15 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.14 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.97 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.39 |
February | 23.90 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.58 | 14.52 |
Annual Sum or Average | 24.17 | 24.88 |
Minimum of Months | 23.13 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.92 | 13.39 |
February | 24.13 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.10 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.92 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.39 |
February | 23.89 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.48 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.01 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.15 | 13.39 |
February | 23.94 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.63 | 14.52 |
Annual Sum or Average | 24.18 | 24.88 |
Minimum of Months | 23.15 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 13.39 |
February | 23.94 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.28 | 19.63 |
December | 23.62 | 14.52 |
Annual Sum or Average | 24.18 | 24.88 |
Minimum of Months | 23.14 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.13 | 13.39 |
February | 24.21 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.24 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.13 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.13 | 13.39 |
February | 24.21 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.43 | 25.09 |
November | 24.37 | 19.63 |
December | 24.24 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.13 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.78 | 13.39 |
February | 25.59 | 16.97 |
March | 26.46 | 22.37 |
April | 27.10 | 29.13 |
May | 27.37 | 32.98 |
June | 27.35 | 33.60 |
July | 27.20 | 31.67 |
August | 27.06 | 30.03 |
September | 26.93 | 28.75 |
October | 26.77 | 25.09 |
November | 26.23 | 19.63 |
December | 25.25 | 14.52 |
Annual Sum or Average | 26.51 | 24.88 |
Minimum of Months | 24.78 | 13.39 |
Maximum of Months | 27.37 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 13.39 |
February | 24.14 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.12 | 14.52 |
Annual Sum or Average | 24.31 | 24.88 |
Minimum of Months | 23.95 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.07 | 13.39 |
February | 23.87 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.53 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.07 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 13.39 |
February | 24.12 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.36 | 19.63 |
December | 24.08 | 14.52 |
Annual Sum or Average | 24.30 | 24.88 |
Minimum of Months | 23.89 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 13.39 |
February | 23.86 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.43 | 14.52 |
Annual Sum or Average | 24.14 | 24.88 |
Minimum of Months | 22.95 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 13.39 |
February | 23.90 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.58 | 14.52 |
Annual Sum or Average | 24.16 | 24.88 |
Minimum of Months | 23.09 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.07 | 13.39 |
February | 23.90 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.57 | 14.52 |
Annual Sum or Average | 24.16 | 24.88 |
Minimum of Months | 23.07 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.11 | 13.39 |
February | 24.20 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.42 | 25.09 |
November | 24.37 | 19.63 |
December | 24.23 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.11 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.11 | 13.39 |
February | 24.20 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.44 | 28.75 |
October | 24.42 | 25.09 |
November | 24.37 | 19.63 |
December | 24.23 | 14.52 |
Annual Sum or Average | 24.35 | 24.88 |
Minimum of Months | 24.11 | 13.39 |
Maximum of Months | 24.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.64 | 13.39 |
February | 25.47 | 16.97 |
March | 26.37 | 22.37 |
April | 27.02 | 29.13 |
May | 27.30 | 32.98 |
June | 27.28 | 33.60 |
July | 27.13 | 31.67 |
August | 26.98 | 30.03 |
September | 26.86 | 28.75 |
October | 26.68 | 25.09 |
November | 26.14 | 19.63 |
December | 25.12 | 14.52 |
Annual Sum or Average | 26.42 | 24.88 |
Minimum of Months | 24.64 | 13.39 |
Maximum of Months | 27.30 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.92 | 13.39 |
February | 24.12 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.35 | 19.63 |
December | 24.10 | 14.52 |
Annual Sum or Average | 24.30 | 24.88 |
Minimum of Months | 23.92 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.39 |
February | 23.84 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.48 | 14.52 |
Annual Sum or Average | 24.14 | 24.88 |
Minimum of Months | 23.01 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.86 | 13.39 |
February | 24.10 | 16.97 |
March | 24.36 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.35 | 19.63 |
December | 24.06 | 14.52 |
Annual Sum or Average | 24.29 | 24.88 |
Minimum of Months | 23.86 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 13.39 |
February | 23.83 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.38 | 14.52 |
Annual Sum or Average | 24.12 | 24.88 |
Minimum of Months | 22.89 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 13.39 |
February | 23.87 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.52 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.02 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.39 |
February | 23.87 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.27 | 19.63 |
December | 23.51 | 14.52 |
Annual Sum or Average | 24.15 | 24.88 |
Minimum of Months | 23.01 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.09 | 13.39 |
February | 24.19 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.43 | 28.75 |
October | 24.42 | 25.09 |
November | 24.37 | 19.63 |
December | 24.21 | 14.52 |
Annual Sum or Average | 24.34 | 24.88 |
Minimum of Months | 24.09 | 13.39 |
Maximum of Months | 24.43 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.09 | 13.39 |
February | 24.19 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.43 | 28.75 |
October | 24.42 | 25.09 |
November | 24.37 | 19.63 |
December | 24.21 | 14.52 |
Annual Sum or Average | 24.34 | 24.88 |
Minimum of Months | 24.09 | 13.39 |
Maximum of Months | 24.43 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.56 | 13.39 |
February | 25.41 | 16.97 |
March | 26.35 | 22.37 |
April | 27.02 | 29.13 |
May | 27.31 | 32.98 |
June | 27.29 | 33.60 |
July | 27.14 | 31.67 |
August | 26.99 | 30.03 |
September | 26.86 | 28.75 |
October | 26.68 | 25.09 |
November | 26.11 | 19.63 |
December | 25.04 | 14.52 |
Annual Sum or Average | 26.40 | 24.88 |
Minimum of Months | 24.56 | 13.39 |
Maximum of Months | 27.31 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.85 | 13.39 |
February | 24.09 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.35 | 19.63 |
December | 24.04 | 14.52 |
Annual Sum or Average | 24.29 | 24.88 |
Minimum of Months | 23.85 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 13.39 |
February | 23.80 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.26 | 19.63 |
December | 23.40 | 14.52 |
Annual Sum or Average | 24.13 | 24.88 |
Minimum of Months | 22.95 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.80 | 13.39 |
February | 24.07 | 16.97 |
March | 24.35 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.39 | 25.09 |
November | 24.35 | 19.63 |
December | 24.00 | 14.52 |
Annual Sum or Average | 24.28 | 24.88 |
Minimum of Months | 23.80 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 13.39 |
February | 23.80 | 16.97 |
March | 24.33 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.38 | 25.09 |
November | 24.26 | 19.63 |
December | 23.30 | 14.52 |
Annual Sum or Average | 24.11 | 24.88 |
Minimum of Months | 22.83 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 13.39 |
February | 23.83 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.26 | 19.63 |
December | 23.42 | 14.52 |
Annual Sum or Average | 24.13 | 24.88 |
Minimum of Months | 22.93 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 13.39 |
February | 23.83 | 16.97 |
March | 24.32 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.41 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.26 | 19.63 |
December | 23.41 | 14.52 |
Annual Sum or Average | 24.13 | 24.88 |
Minimum of Months | 22.92 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.02 | 13.39 |
February | 24.16 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.42 | 28.75 |
October | 24.41 | 25.09 |
November | 24.36 | 19.63 |
December | 24.17 | 14.52 |
Annual Sum or Average | 24.33 | 24.88 |
Minimum of Months | 24.02 | 13.39 |
Maximum of Months | 24.42 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.02 | 13.39 |
February | 24.16 | 16.97 |
March | 24.34 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.42 | 31.67 |
August | 24.42 | 30.03 |
September | 24.42 | 28.75 |
October | 24.41 | 25.09 |
November | 24.36 | 19.63 |
December | 24.17 | 14.52 |
Annual Sum or Average | 24.33 | 24.88 |
Minimum of Months | 24.02 | 13.39 |
Maximum of Months | 24.42 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.41 | 13.39 |
February | 25.34 | 16.97 |
March | 26.38 | 22.37 |
April | 27.12 | 29.13 |
May | 27.44 | 32.98 |
June | 27.43 | 33.60 |
July | 27.26 | 31.67 |
August | 27.10 | 30.03 |
September | 26.95 | 28.75 |
October | 26.73 | 25.09 |
November | 26.08 | 19.63 |
December | 24.90 | 14.52 |
Annual Sum or Average | 26.43 | 24.88 |
Minimum of Months | 24.41 | 13.39 |
Maximum of Months | 27.44 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.43 | 13.39 |
February | 23.80 | 16.97 |
March | 24.28 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.36 | 25.09 |
November | 24.20 | 19.63 |
December | 23.59 | 14.52 |
Annual Sum or Average | 24.17 | 24.88 |
Minimum of Months | 23.43 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 13.39 |
February | 23.54 | 16.97 |
March | 24.25 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.36 | 25.09 |
November | 24.05 | 19.63 |
December | 23.09 | 14.52 |
Annual Sum or Average | 24.05 | 24.88 |
Minimum of Months | 22.87 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 13.39 |
February | 23.78 | 16.97 |
March | 24.29 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.37 | 25.09 |
November | 24.18 | 19.63 |
December | 23.55 | 14.52 |
Annual Sum or Average | 24.16 | 24.88 |
Minimum of Months | 23.40 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 13.39 |
February | 23.56 | 16.97 |
March | 24.26 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.35 | 25.09 |
November | 24.02 | 19.63 |
December | 23.03 | 14.52 |
Annual Sum or Average | 24.03 | 24.88 |
Minimum of Months | 22.79 | 13.39 |
Maximum of Months | 24.40 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 13.39 |
February | 23.58 | 16.97 |
March | 24.24 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.35 | 25.09 |
November | 24.06 | 19.63 |
December | 23.08 | 14.52 |
Annual Sum or Average | 24.04 | 24.88 |
Minimum of Months | 22.78 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 13.39 |
February | 23.57 | 16.97 |
March | 24.24 | 22.37 |
April | 24.39 | 29.13 |
May | 24.40 | 32.98 |
June | 24.41 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.40 | 28.75 |
October | 24.35 | 25.09 |
November | 24.06 | 19.63 |
December | 23.07 | 14.52 |
Annual Sum or Average | 24.04 | 24.88 |
Minimum of Months | 22.78 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.56 | 13.39 |
February | 23.90 | 16.97 |
March | 24.29 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.41 | 28.75 |
October | 24.39 | 25.09 |
November | 24.24 | 19.63 |
December | 23.74 | 14.52 |
Annual Sum or Average | 24.21 | 24.88 |
Minimum of Months | 23.56 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.56 | 13.39 |
February | 23.90 | 16.97 |
March | 24.29 | 22.37 |
April | 24.40 | 29.13 |
May | 24.40 | 32.98 |
June | 24.40 | 33.60 |
July | 24.40 | 31.67 |
August | 24.40 | 30.03 |
September | 24.41 | 28.75 |
October | 24.39 | 25.09 |
November | 24.24 | 19.63 |
December | 23.73 | 14.52 |
Annual Sum or Average | 24.21 | 24.88 |
Minimum of Months | 23.56 | 13.39 |
Maximum of Months | 24.41 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.50 | 13.39 |
February | 25.59 | 16.97 |
March | 26.96 | 22.37 |
April | 27.99 | 29.13 |
May | 28.48 | 32.98 |
June | 28.51 | 33.60 |
July | 28.26 | 31.67 |
August | 28.03 | 30.03 |
September | 27.78 | 28.75 |
October | 27.38 | 25.09 |
November | 26.40 | 19.63 |
December | 24.95 | 14.52 |
Annual Sum or Average | 27.07 | 24.88 |
Minimum of Months | 24.50 | 13.39 |
Maximum of Months | 28.51 | 33.60 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:17
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.235902E+12 | 129407.374 | 12-JAN-17:45 | 18221.747 | 56933.809 | 25601.197 | 0.000 | 13943.308 | 10720.100 | 2063.513 | 775.257 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.231128E+12 | 161302.870 | 22-FEB-18:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 40940.703 | 10720.100 | 2063.513 | 1759.808 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.306650E+12 | 182977.958 | 28-MAR-17:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 72262.411 | 0.000 | 2063.513 | 2833.288 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.350396E+12 | 195234.301 | 26-APR-17:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 83973.716 | 0.000 | 2063.513 | 3378.325 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.396073E+12 | 201748.952 | 17-MAY-17:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 90030.913 | 0.000 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.397346E+12 | 207771.157 | 22-JUN-17:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 96053.117 | 0.000 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.416712E+12 | 208969.319 | 01-JUL-17:15 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 97251.279 | 0.000 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.409815E+12 | 204410.294 | 27-AUG-18:00 | 25049.151 | 51564.864 | 25601.197 | 0.000 | 84561.076 | 10720.100 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.378818E+12 | 201730.575 | 14-SEP-18:30 | 25049.151 | 51564.864 | 25601.197 | 0.000 | 81881.357 | 10720.100 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.344007E+12 | 186823.776 | 02-OCT-16:15 | 18221.747 | 56933.809 | 25601.197 | 0.000 | 79644.615 | 0.000 | 2063.513 | 3210.591 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.279384E+12 | 172804.858 | 04-NOV-17:45 | 22204.399 | 56867.515 | 25601.197 | 0.000 | 52016.843 | 10720.100 | 2063.513 | 2185.402 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.243671E+12 | 141480.109 | 28-DEC-17:30 | 18221.747 | 56933.809 | 25601.197 | 0.000 | 25555.929 | 10720.100 | 2063.513 | 1235.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.398990E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.231128E+12 | 129407.374 | 18221.747 | 51564.864 | 25601.197 | 0.000 | 13943.308 | 0.000 | 2063.513 | 775.257 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.416712E+12 | 208969.319 | 25049.151 | 56933.809 | 25601.197 | 0.000 | 97251.279 | 10720.100 | 2063.513 | 3835.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:17
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.853218E+11 | 79739.685 | 10-JAN-07:00 | 0.000 | 0.000 | 0.000 | 79739.685 | 79739.685 | 79739.685 | 0.000 |
February | 0.754516E+11 | 79603.175 | 02-FEB-07:00 | 0.000 | 0.000 | 0.000 | 79603.175 | 79603.175 | 79603.175 | 0.000 |
March | 0.780819E+11 | 78340.988 | 04-MAR-07:45 | 0.000 | 0.000 | 0.000 | 78340.988 | 78340.988 | 78340.988 | 0.000 |
April | 0.679267E+11 | 76198.075 | 05-APR-06:45 | 0.000 | 0.000 | 0.000 | 76198.075 | 76198.075 | 76198.075 | 0.000 |
May | 0.620914E+11 | 64901.096 | 05-MAY-06:45 | 0.000 | 0.000 | 0.000 | 64901.096 | 64901.096 | 64901.096 | 0.000 |
June | 0.541121E+11 | 40848.915 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 40848.915 | 40848.915 | 40848.915 | 0.000 |
July | 0.534031E+11 | 40310.895 | 02-JUL-06:00 | 0.000 | 0.000 | 0.000 | 40310.895 | 40310.895 | 40310.895 | 0.000 |
August | 0.552099E+11 | 40742.165 | 31-AUG-06:00 | 0.000 | 0.000 | 0.000 | 40742.165 | 40742.165 | 40742.165 | 0.000 |
September | 0.588811E+11 | 63839.986 | 30-SEP-06:00 | 0.000 | 0.000 | 0.000 | 63839.986 | 63839.986 | 63839.986 | 0.000 |
October | 0.687532E+11 | 76040.068 | 29-OCT-06:00 | 0.000 | 0.000 | 0.000 | 76040.068 | 76040.068 | 76040.068 | 0.000 |
November | 0.743755E+11 | 78096.610 | 28-NOV-07:00 | 0.000 | 0.000 | 0.000 | 78096.610 | 78096.610 | 78096.610 | 0.000 |
December | 0.829048E+11 | 79383.223 | 25-DEC-07:00 | 0.000 | 0.000 | 0.000 | 79383.223 | 79383.223 | 79383.223 | 0.000 |
Annual Sum or Average | 0.816513E+12 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.534031E+11 | 40310.895 | 0.000 | 0.000 | 0.000 | 40310.895 | 40310.895 | 40310.895 | 0.000 | |
Maximum of Months | 0.853218E+11 | 79739.685 | 0.000 | 0.000 | 0.000 | 79739.685 | 79739.685 | 79739.685 | 0.000 |