Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2018-10-19 09:40:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4136.08 | 527.80 | 585.86 |
Net Site Energy | 4136.08 | 527.80 | 585.86 |
Total Source Energy | 10984.20 | 1401.68 | 1555.86 |
Net Source Energy | 10984.20 | 1401.68 | 1555.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 14.85 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 659.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 640.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | 2235.35 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 995.45 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3120.83 | 1015.24 | 0.00 | 0.00 | 0.00 | 7013.87 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 659.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 640.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 44.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | 2235.35 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 995.45 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 196.03 | 143.80 | 0.00 | 0.00 | 0.00 | 0.99 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 442.05 | 143.80 | 0.00 | 0.00 | 0.00 | 0.99 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 176.60 | 129.55 | 0.00 | 0.00 | 0.00 | 0.90 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.24 | 129.55 | 0.00 | 0.00 | 0.00 | 0.90 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3120.83 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3120.83 | 100.00 |
Total On-Site and Utility Electric Sources | 3120.83 | 100.00 |
Total Electricity End Uses | 3120.83 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7013.87 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7013.87 | 100.00 |
Total Water End Uses | 7013.87 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 40.50 |
Time Setpoint Not Met During Occupied Cooling | 294.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1081.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-19:00 | 27-DEC-07:30 | - | - | - | 14-JUN-17:15 |
Heating | 0.00 | 59159.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61623.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20322.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1422.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2273.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 82933.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 172060.80 | 142092.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 59159.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 61623.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 20322.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1422.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2273.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 82933.34 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 47.03 | 21.46 | 0.00 | 0.00 | 0.00 |
Cooling | 2088.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2029.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 140.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1079.07 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9883.68 | 1100.52 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 6.66 | 3.04 | 0.00 | 0.00 | 0.00 |
Cooling | 295.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 152.84 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.97 | 155.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 6.66 | 3.04 | 0.00 | 0.00 | 0.00 |
Cooling | 295.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 152.84 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.97 | 155.88 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.77 | 83.77 | 168.57 | |
Exterior Lighting Total | 10720.10 | 168.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 249683.30 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 199746.64 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3249.68 | 2140.77 | 1108.91 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3218.01 | 2121.90 | 1096.12 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4223.95 | 2796.49 | 1427.45 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2488.28 | 1645.63 | 842.65 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1921.73 | 1251.37 | 670.37 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1906.25 | 1240.97 | 665.28 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1970.73 | 1265.14 | 705.59 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2036.19 | 1309.46 | 726.72 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3965.11 | 2626.31 | 1338.79 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3915.59 | 2595.20 | 1320.39 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3612.81 | 2380.92 | 1231.89 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3107.16 | 2063.61 | 1043.55 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2392.07 | 1567.90 | 824.16 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2379.58 | 1559.52 | 820.06 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2454.33 | 1593.36 | 860.97 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2471.69 | 1606.29 | 865.40 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3967.89 | 2630.85 | 1337.04 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3924.39 | 2603.80 | 1320.58 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3412.66 | 2248.73 | 1163.92 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3135.87 | 2085.55 | 1050.32 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2423.14 | 1590.36 | 832.79 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2410.87 | 1582.11 | 828.76 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2485.63 | 1616.00 | 869.63 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2490.29 | 1620.36 | 869.93 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3978.02 | 2639.66 | 1338.35 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3934.90 | 2612.89 | 1322.01 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3410.37 | 2249.12 | 1161.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3149.32 | 2096.56 | 1052.77 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2442.83 | 1604.77 | 838.07 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2430.72 | 1596.62 | 834.10 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2503.58 | 1629.25 | 874.33 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2506.01 | 1632.11 | 873.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4020.32 | 2669.74 | 1350.57 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3978.56 | 2643.88 | 1334.68 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3457.37 | 2282.36 | 1175.00 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3194.58 | 2128.63 | 1065.96 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2492.03 | 1638.79 | 853.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2480.05 | 1630.73 | 849.31 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2550.25 | 1661.69 | 888.56 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2552.12 | 1664.17 | 887.95 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3972.31 | 2638.86 | 1333.46 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3929.39 | 2612.23 | 1317.15 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3416.79 | 2256.37 | 1160.43 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3148.43 | 2098.90 | 1049.53 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2450.64 | 1611.80 | 838.85 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2438.82 | 1603.85 | 834.97 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2508.70 | 1634.42 | 874.28 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2514.76 | 1638.51 | 876.25 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3957.58 | 2630.17 | 1327.41 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3914.99 | 2603.79 | 1311.21 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3408.31 | 2251.83 | 1156.48 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3136.20 | 2091.86 | 1044.34 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2441.88 | 1606.63 | 835.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2430.19 | 1598.77 | 831.42 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2498.64 | 1628.32 | 870.32 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2504.70 | 1632.41 | 872.29 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3963.16 | 2635.03 | 1328.14 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3920.80 | 2608.80 | 1312.00 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3418.62 | 2259.84 | 1158.78 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3142.91 | 2097.45 | 1045.46 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2452.52 | 1614.43 | 838.09 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2440.97 | 1606.66 | 834.31 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2507.45 | 1634.89 | 872.56 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2513.52 | 1638.99 | 874.53 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4089.45 | 2720.99 | 1368.45 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4047.73 | 2695.17 | 1352.56 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3526.19 | 2332.14 | 1194.05 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3278.03 | 2178.02 | 1100.01 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2569.27 | 1693.50 | 875.77 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2557.77 | 1685.77 | 872.00 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2596.17 | 1695.38 | 900.79 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2601.78 | 1699.16 | 902.62 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4985.04 | 3319.03 | 1666.01 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4878.09 | 3251.28 | 1626.81 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4361.67 | 2896.86 | 1464.81 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4055.89 | 2689.85 | 1366.04 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3200.15 | 2104.73 | 1095.41 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3196.55 | 2100.93 | 1095.62 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3492.06 | 2300.04 | 1192.02 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3496.99 | 2303.35 | 1193.64 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3249.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3218.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4223.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2488.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1921.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1906.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1970.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2036.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3965.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3915.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3612.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3107.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2392.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2379.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2454.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2471.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3967.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3924.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3412.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3135.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2423.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2410.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2485.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2490.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3978.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3934.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3410.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3149.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2442.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2430.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2503.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2506.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4020.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3978.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3457.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3194.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2492.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2480.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2550.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2552.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3972.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3929.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3416.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3148.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2450.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2438.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2508.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2514.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3957.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3914.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3408.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3136.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2441.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2430.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2498.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2504.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3963.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3920.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3418.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3142.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2452.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2440.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2507.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2513.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4089.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4047.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3526.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3278.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2569.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2557.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2596.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2601.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4985.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4878.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4361.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4055.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3200.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3196.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3492.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3496.99 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2219.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2216.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2965.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2213.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1639.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1639.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1638.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1646.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2173.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2168.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2195.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2165.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1466.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1466.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1474.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1475.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2144.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2140.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2144.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2137.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1422.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1421.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1426.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1426.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2156.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2154.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2154.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2151.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1421.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1421.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1423.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1423.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2148.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2146.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2146.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2144.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1404.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1404.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1407.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1407.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2210.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2209.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2208.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2208.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1455.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1455.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1456.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1456.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2246.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2246.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2245.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2245.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1483.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1483.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1483.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1483.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2286.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2286.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2286.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2286.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1516.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1516.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1516.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1516.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2439.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2437.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2439.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2437.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1652.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1652.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1654.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1654.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2990.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2995.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2991.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2995.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2256.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2256.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2248.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2248.82 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 265.53 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 263.80 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 347.26 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.05 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 151.43 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 150.08 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 149.12 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 154.87 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 329.48 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 326.15 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 295.33 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.45 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 192.32 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 191.22 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 191.75 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.66 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 330.22 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 327.43 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.14 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.46 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.34 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.26 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.79 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.57 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.48 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.73 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.29 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 263.01 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.28 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.22 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.58 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.17 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 335.52 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.88 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.74 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.31 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.79 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 200.73 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 200.86 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.40 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.54 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.80 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.40 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 263.48 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.30 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.26 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.34 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.88 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 330.46 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 327.76 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.87 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 262.61 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.66 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.63 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.58 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.12 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 331.16 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.47 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.97 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 263.40 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.72 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.70 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.47 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.01 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 342.50 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 339.87 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 289.28 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 272.70 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 209.10 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.08 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.40 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.90 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 419.77 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 411.89 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 363.69 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 336.26 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.26 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 258.49 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.58 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.02 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0054 | 1385.13 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2187.91 | 2625.49 | 0.198 | 0.237 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
G NW APARTMENT | 2173.65 | 2608.39 | 0.196 | 0.236 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
OFFICE | 2861.36 | 3433.63 | 0.258 | 0.310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 35.44 | 0.00682 |
G NE APARTMENT | 1681.28 | 2017.54 | 0.152 | 0.182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 34.14 | 0.00682 |
G N1 APARTMENT | 1247.73 | 1497.27 | 0.113 | 0.135 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G N2 APARTMENT | 1236.57 | 1483.88 | 0.112 | 0.134 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G S1 APARTMENT | 1228.67 | 1474.41 | 0.111 | 0.133 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
G S2 APARTMENT | 1276.09 | 1531.31 | 0.115 | 0.138 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F2 SW APARTMENT | 2714.82 | 3257.78 | 0.245 | 0.294 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F2 NW APARTMENT | 2687.39 | 3224.87 | 0.243 | 0.291 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F2 SE APARTMENT | 2433.46 | 2920.15 | 0.220 | 0.264 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F2 NE APARTMENT | 2129.51 | 2555.41 | 0.192 | 0.231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F2 N1 APARTMENT | 1584.61 | 1901.53 | 0.143 | 0.172 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F2 N2 APARTMENT | 1575.57 | 1890.69 | 0.142 | 0.171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F2 S1 APARTMENT | 1579.99 | 1895.99 | 0.143 | 0.171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F2 S2 APARTMENT | 1595.66 | 1914.79 | 0.144 | 0.173 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F3 SW APARTMENT | 2720.91 | 3265.09 | 0.246 | 0.295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F3 NW APARTMENT | 2697.89 | 3237.46 | 0.244 | 0.292 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F3 SE APARTMENT | 2291.80 | 2750.15 | 0.207 | 0.248 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F3 NE APARTMENT | 2154.38 | 2585.26 | 0.195 | 0.233 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F3 N1 APARTMENT | 1609.49 | 1931.39 | 0.145 | 0.174 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F3 N2 APARTMENT | 1600.61 | 1920.73 | 0.145 | 0.173 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F3 S1 APARTMENT | 1604.99 | 1925.98 | 0.145 | 0.174 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F3 S2 APARTMENT | 1611.45 | 1933.74 | 0.146 | 0.175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F4 SW APARTMENT | 2731.32 | 3277.58 | 0.247 | 0.296 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F4 NW APARTMENT | 2708.60 | 3250.32 | 0.245 | 0.293 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F4 SE APARTMENT | 2293.06 | 2751.68 | 0.207 | 0.248 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F4 NE APARTMENT | 2167.15 | 2600.58 | 0.196 | 0.235 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F4 N1 APARTMENT | 1625.55 | 1950.65 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F4 N2 APARTMENT | 1616.77 | 1940.12 | 0.146 | 0.175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F4 S1 APARTMENT | 1619.73 | 1943.68 | 0.146 | 0.175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F4 S2 APARTMENT | 1624.59 | 1949.51 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
M SW APARTMENT | 2764.59 | 3317.51 | 0.250 | 0.300 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
M NW APARTMENT | 2742.87 | 3291.44 | 0.248 | 0.297 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
M SE APARTMENT | 2329.67 | 2795.60 | 0.210 | 0.252 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
M NE APARTMENT | 2202.55 | 2643.06 | 0.199 | 0.239 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
M N1 APARTMENT | 1662.65 | 1995.17 | 0.150 | 0.180 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M N2 APARTMENT | 1653.96 | 1984.75 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M S1 APARTMENT | 1655.03 | 1986.03 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
M S2 APARTMENT | 1659.49 | 1991.39 | 0.150 | 0.180 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F6 SW APARTMENT | 2731.77 | 3278.13 | 0.247 | 0.296 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F6 NW APARTMENT | 2709.23 | 3251.08 | 0.245 | 0.294 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F6 SE APARTMENT | 2302.17 | 2762.60 | 0.208 | 0.249 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F6 NE APARTMENT | 2170.98 | 2605.18 | 0.196 | 0.235 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F6 N1 APARTMENT | 1633.91 | 1960.69 | 0.148 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F6 N2 APARTMENT | 1625.35 | 1950.42 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F6 S1 APARTMENT | 1626.04 | 1951.25 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F6 S2 APARTMENT | 1630.44 | 1956.53 | 0.147 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F7 SW APARTMENT | 2722.91 | 3267.49 | 0.246 | 0.295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F7 NW APARTMENT | 2700.64 | 3240.76 | 0.244 | 0.293 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F7 SE APARTMENT | 2297.79 | 2757.35 | 0.207 | 0.249 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F7 NE APARTMENT | 2163.88 | 2596.65 | 0.195 | 0.234 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F7 N1 APARTMENT | 1628.66 | 1954.39 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F7 N2 APARTMENT | 1620.19 | 1944.22 | 0.146 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F7 S1 APARTMENT | 1619.79 | 1943.74 | 0.146 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F7 S2 APARTMENT | 1624.18 | 1949.02 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F8 SW APARTMENT | 2728.65 | 3274.38 | 0.246 | 0.296 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F8 NW APARTMENT | 2706.55 | 3247.86 | 0.244 | 0.293 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F8 SE APARTMENT | 2306.90 | 2768.29 | 0.208 | 0.250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F8 NE APARTMENT | 2170.39 | 2604.46 | 0.196 | 0.235 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F8 N1 APARTMENT | 1637.35 | 1964.82 | 0.148 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F8 N2 APARTMENT | 1628.97 | 1954.77 | 0.147 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F8 S1 APARTMENT | 1627.13 | 1952.55 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F8 S2 APARTMENT | 1631.53 | 1957.84 | 0.147 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F9 SW APARTMENT | 2822.14 | 3386.57 | 0.255 | 0.306 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F9 NW APARTMENT | 2800.47 | 3360.56 | 0.253 | 0.303 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F9 SE APARTMENT | 2383.56 | 2860.28 | 0.215 | 0.258 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F9 NE APARTMENT | 2246.96 | 2696.35 | 0.203 | 0.243 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 35.30 | 0.00682 |
F9 N1 APARTMENT | 1722.89 | 2067.46 | 0.156 | 0.187 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F9 N2 APARTMENT | 1714.54 | 2057.45 | 0.155 | 0.186 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F9 S1 APARTMENT | 1692.45 | 2030.94 | 0.153 | 0.183 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
F9 S2 APARTMENT | 1696.53 | 2035.83 | 0.153 | 0.184 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
T SW APARTMENT | 3458.85 | 4150.62 | 0.312 | 0.375 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
T NW APARTMENT | 3393.91 | 4072.69 | 0.306 | 0.368 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
T SE APARTMENT | 2996.70 | 3596.04 | 0.271 | 0.325 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
T NE APARTMENT | 2770.73 | 3324.88 | 0.250 | 0.300 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T N1 APARTMENT | 2136.21 | 2563.45 | 0.193 | 0.231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
T N2 APARTMENT | 2129.87 | 2555.84 | 0.192 | 0.231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T S1 APARTMENT | 2344.87 | 2813.84 | 0.212 | 0.254 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T S2 APARTMENT | 2348.45 | 2818.14 | 0.212 | 0.254 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1257.17 | 1508.60 | 0.065 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G NW APARTMENT | 1255.20 | 1506.24 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
OFFICE | 1598.51 | 1918.22 | 0.082 | 0.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.20 | 0.00281 |
G NE APARTMENT | 1252.30 | 1502.76 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N1 APARTMENT | 767.02 | 920.42 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N2 APARTMENT | 766.95 | 920.34 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S1 APARTMENT | 765.80 | 918.96 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S2 APARTMENT | 772.92 | 927.51 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
F2 SW APARTMENT | 1218.64 | 1462.37 | 0.063 | 0.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 NW APARTMENT | 1214.39 | 1457.27 | 0.062 | 0.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 SE APARTMENT | 1237.29 | 1484.75 | 0.063 | 0.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 NE APARTMENT | 1211.41 | 1453.69 | 0.062 | 0.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 N1 APARTMENT | 620.40 | 744.47 | 0.032 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 N2 APARTMENT | 620.32 | 744.38 | 0.032 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 S1 APARTMENT | 627.00 | 752.39 | 0.032 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 S2 APARTMENT | 628.38 | 754.05 | 0.032 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 SW APARTMENT | 1193.60 | 1432.32 | 0.061 | 0.073 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 NW APARTMENT | 1190.75 | 1428.89 | 0.061 | 0.073 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 SE APARTMENT | 1193.59 | 1432.31 | 0.061 | 0.073 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 NE APARTMENT | 1188.29 | 1425.95 | 0.061 | 0.073 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 N1 APARTMENT | 582.99 | 699.59 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 N2 APARTMENT | 582.93 | 699.52 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 S1 APARTMENT | 586.50 | 703.80 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 S2 APARTMENT | 586.67 | 704.00 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 SW APARTMENT | 1203.72 | 1444.47 | 0.062 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 NW APARTMENT | 1202.03 | 1442.44 | 0.062 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 SE APARTMENT | 1202.02 | 1442.43 | 0.062 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 NE APARTMENT | 1200.07 | 1440.08 | 0.062 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 N1 APARTMENT | 582.36 | 698.83 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 N2 APARTMENT | 582.31 | 698.77 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 S1 APARTMENT | 584.48 | 701.37 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 S2 APARTMENT | 584.46 | 701.35 | 0.030 | 0.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M SW APARTMENT | 1197.17 | 1436.61 | 0.061 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M NW APARTMENT | 1195.34 | 1434.41 | 0.061 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M SE APARTMENT | 1195.69 | 1434.82 | 0.061 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M NE APARTMENT | 1193.83 | 1432.59 | 0.061 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M N1 APARTMENT | 568.38 | 682.06 | 0.029 | 0.035 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M N2 APARTMENT | 568.34 | 682.01 | 0.029 | 0.035 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M S1 APARTMENT | 570.59 | 684.71 | 0.029 | 0.035 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M S2 APARTMENT | 570.55 | 684.66 | 0.029 | 0.035 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 SW APARTMENT | 1249.58 | 1499.50 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 NW APARTMENT | 1249.21 | 1499.05 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 SE APARTMENT | 1248.47 | 1498.17 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 NE APARTMENT | 1248.09 | 1497.71 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 N1 APARTMENT | 611.45 | 733.74 | 0.031 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 N2 APARTMENT | 611.42 | 733.70 | 0.031 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 S1 APARTMENT | 612.17 | 734.60 | 0.031 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 S2 APARTMENT | 612.14 | 734.56 | 0.031 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 SW APARTMENT | 1280.09 | 1536.10 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 NW APARTMENT | 1280.08 | 1536.09 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 SE APARTMENT | 1279.35 | 1535.22 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 NE APARTMENT | 1279.34 | 1535.20 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 N1 APARTMENT | 634.87 | 761.84 | 0.033 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 N2 APARTMENT | 634.85 | 761.81 | 0.033 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 S1 APARTMENT | 635.19 | 762.22 | 0.033 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 S2 APARTMENT | 635.17 | 762.20 | 0.033 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 SW APARTMENT | 1314.23 | 1577.08 | 0.067 | 0.081 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 NW APARTMENT | 1314.36 | 1577.24 | 0.067 | 0.081 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 SE APARTMENT | 1313.83 | 1576.60 | 0.067 | 0.081 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 NE APARTMENT | 1313.96 | 1576.75 | 0.067 | 0.081 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 N1 APARTMENT | 662.96 | 795.55 | 0.034 | 0.041 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 N2 APARTMENT | 662.94 | 795.53 | 0.034 | 0.041 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 S1 APARTMENT | 663.11 | 795.73 | 0.034 | 0.041 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 S2 APARTMENT | 663.10 | 795.71 | 0.034 | 0.041 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 SW APARTMENT | 1443.24 | 1731.89 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 NW APARTMENT | 1441.65 | 1729.98 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 SE APARTMENT | 1443.16 | 1731.79 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 NE APARTMENT | 1441.56 | 1729.87 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 N1 APARTMENT | 778.23 | 933.88 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 N2 APARTMENT | 778.23 | 933.88 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 S1 APARTMENT | 779.72 | 935.66 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 S2 APARTMENT | 779.71 | 935.66 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T SW APARTMENT | 1909.80 | 2291.76 | 0.098 | 0.118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T NW APARTMENT | 1913.87 | 2296.64 | 0.098 | 0.118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T SE APARTMENT | 1909.97 | 2291.97 | 0.098 | 0.118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T NE APARTMENT | 1914.04 | 2296.84 | 0.098 | 0.118 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T N1 APARTMENT | 1288.78 | 1546.53 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T N2 APARTMENT | 1288.78 | 1546.53 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T S1 APARTMENT | 1282.20 | 1538.64 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T S2 APARTMENT | 1282.21 | 1538.65 | 0.066 | 0.079 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP G NW | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP OFFICE | 0.31 | 0.31 | 0.10 | 0.10 |
AIRLOOP G NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP G N1 | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP G N2 | 0.13 | 0.13 | 0.05 | 0.05 |
AIRLOOP G S1 | 0.13 | 0.13 | 0.05 | 0.05 |
AIRLOOP G S2 | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F2 SW | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F2 NW | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP F2 SE | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP F2 NE | 0.23 | 0.23 | 0.07 | 0.07 |
AIRLOOP F2 N1 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F2 N2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F2 S1 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F2 S2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 SW | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP F3 NW | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP F3 SE | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F3 NE | 0.23 | 0.23 | 0.07 | 0.07 |
AIRLOOP F3 N1 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 N2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 S1 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 S2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F4 SW | 0.30 | 0.30 | 0.07 | 0.07 |
AIRLOOP F4 NW | 0.29 | 0.29 | 0.07 | 0.07 |
AIRLOOP F4 SE | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F4 NE | 0.23 | 0.23 | 0.07 | 0.07 |
AIRLOOP F4 N1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F4 N2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F4 S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F4 S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP M SW | 0.30 | 0.30 | 0.07 | 0.07 |
AIRLOOP M NW | 0.30 | 0.30 | 0.07 | 0.07 |
AIRLOOP M SE | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP M NE | 0.24 | 0.24 | 0.07 | 0.07 |
AIRLOOP M N1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP M S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F6 SW | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F6 NW | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F6 SE | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F6 NE | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP F6 N1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F6 N2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F6 S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F6 S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F7 SW | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F7 NW | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F7 SE | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F7 NE | 0.23 | 0.23 | 0.08 | 0.08 |
AIRLOOP F7 N1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F7 N2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F7 S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F7 S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F8 SW | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F8 NW | 0.29 | 0.29 | 0.08 | 0.08 |
AIRLOOP F8 SE | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F8 NE | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP F8 N1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F8 N2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F8 S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F8 S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F9 SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F9 NW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F9 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F9 NE | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F9 N1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F9 N2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F9 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F9 S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP T SW | 0.37 | 0.37 | 0.12 | 0.12 |
AIRLOOP T NW | 0.37 | 0.37 | 0.12 | 0.12 |
AIRLOOP T SE | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP T NE | 0.30 | 0.30 | 0.12 | 0.12 |
AIRLOOP T N1 | 0.23 | 0.23 | 0.08 | 0.08 |
AIRLOOP T N2 | 0.23 | 0.23 | 0.08 | 0.08 |
AIRLOOP T S1 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP T S2 | 0.25 | 0.25 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3490.75 | 4573.25 | 613.75 |
G NW APARTMENT | 3239.75 | 5481.25 | 680.75 |
OFFICE | 1065.50 | 429.00 | 3.50 |
G NE APARTMENT | 3273.50 | 5493.25 | 694.75 |
G N1 APARTMENT | 3061.25 | 5895.25 | 845.00 |
G N2 APARTMENT | 3062.25 | 5893.25 | 844.00 |
G S1 APARTMENT | 3290.50 | 4898.25 | 711.25 |
G S2 APARTMENT | 3311.75 | 4833.00 | 702.25 |
F2 SW APARTMENT | 4200.75 | 2657.75 | 371.75 |
F2 NW APARTMENT | 3639.00 | 4377.50 | 429.25 |
F2 SE APARTMENT | 4333.75 | 2427.75 | 320.00 |
F2 NE APARTMENT | 3672.50 | 4377.00 | 422.75 |
F2 N1 APARTMENT | 3479.75 | 4640.25 | 526.50 |
F2 N2 APARTMENT | 3479.75 | 4642.00 | 526.00 |
F2 S1 APARTMENT | 4201.50 | 2460.50 | 426.00 |
F2 S2 APARTMENT | 4207.25 | 2436.50 | 424.75 |
F3 SW APARTMENT | 4344.00 | 2295.25 | 365.00 |
F3 NW APARTMENT | 3731.00 | 4154.50 | 411.25 |
F3 SE APARTMENT | 4416.25 | 2261.50 | 330.50 |
F3 NE APARTMENT | 3752.50 | 4146.50 | 406.75 |
F3 N1 APARTMENT | 3596.00 | 4349.50 | 495.25 |
F3 N2 APARTMENT | 3593.25 | 4349.00 | 494.50 |
F3 S1 APARTMENT | 4434.00 | 1925.75 | 410.00 |
F3 S2 APARTMENT | 4436.75 | 1924.25 | 410.00 |
F4 SW APARTMENT | 4362.00 | 2248.25 | 369.00 |
F4 NW APARTMENT | 3746.75 | 4111.00 | 415.00 |
F4 SE APARTMENT | 4419.25 | 2247.25 | 340.50 |
F4 NE APARTMENT | 3769.50 | 4097.25 | 411.00 |
F4 N1 APARTMENT | 3632.50 | 4242.25 | 488.75 |
F4 N2 APARTMENT | 3632.00 | 4251.50 | 490.00 |
F4 S1 APARTMENT | 4486.25 | 1810.00 | 410.25 |
F4 S2 APARTMENT | 4486.00 | 1816.50 | 410.75 |
M SW APARTMENT | 4366.25 | 2236.00 | 365.50 |
M NW APARTMENT | 3762.75 | 4076.25 | 404.00 |
M SE APARTMENT | 4428.00 | 2241.75 | 337.00 |
M NE APARTMENT | 3782.00 | 4074.75 | 402.75 |
M N1 APARTMENT | 3661.00 | 4176.25 | 476.25 |
M N2 APARTMENT | 3658.75 | 4185.50 | 476.75 |
M S1 APARTMENT | 4513.25 | 1755.75 | 399.75 |
M S2 APARTMENT | 4512.75 | 1763.00 | 401.25 |
F6 SW APARTMENT | 4263.50 | 2442.00 | 382.25 |
F6 NW APARTMENT | 3696.25 | 4221.50 | 436.50 |
F6 SE APARTMENT | 4316.50 | 2435.50 | 357.50 |
F6 NE APARTMENT | 3717.00 | 4219.50 | 431.75 |
F6 N1 APARTMENT | 3588.25 | 4352.50 | 504.50 |
F6 N2 APARTMENT | 3585.25 | 4351.25 | 504.75 |
F6 S1 APARTMENT | 4396.50 | 1980.25 | 424.50 |
F6 S2 APARTMENT | 4394.00 | 1984.75 | 424.50 |
F7 SW APARTMENT | 4201.75 | 2609.50 | 398.00 |
F7 NW APARTMENT | 3657.75 | 4309.25 | 453.25 |
F7 SE APARTMENT | 4246.25 | 2574.50 | 368.00 |
F7 NE APARTMENT | 3685.00 | 4302.50 | 446.00 |
F7 N1 APARTMENT | 3548.50 | 4448.50 | 516.75 |
F7 N2 APARTMENT | 3545.25 | 4446.00 | 517.00 |
F7 S1 APARTMENT | 4323.25 | 2152.75 | 438.00 |
F7 S2 APARTMENT | 4322.25 | 2156.50 | 438.00 |
F8 SW APARTMENT | 4145.50 | 2752.50 | 406.25 |
F8 NW APARTMENT | 3627.25 | 4365.50 | 459.50 |
F8 SE APARTMENT | 4184.00 | 2702.75 | 378.50 |
F8 NE APARTMENT | 3666.75 | 4387.75 | 458.00 |
F8 N1 APARTMENT | 3525.50 | 4503.25 | 522.25 |
F8 N2 APARTMENT | 3520.50 | 4505.75 | 521.75 |
F8 S1 APARTMENT | 4246.50 | 2328.25 | 443.50 |
F8 S2 APARTMENT | 4243.00 | 2336.25 | 443.75 |
F9 SW APARTMENT | 4055.50 | 2970.75 | 401.50 |
F9 NW APARTMENT | 3605.25 | 4442.75 | 454.50 |
F9 SE APARTMENT | 4087.25 | 2882.00 | 374.50 |
F9 NE APARTMENT | 3649.75 | 4461.00 | 448.00 |
F9 N1 APARTMENT | 3500.75 | 4555.00 | 511.25 |
F9 N2 APARTMENT | 3500.00 | 4558.50 | 512.50 |
F9 S1 APARTMENT | 4120.50 | 2593.50 | 438.25 |
F9 S2 APARTMENT | 4119.75 | 2596.75 | 438.75 |
T SW APARTMENT | 4269.75 | 3608.50 | 517.25 |
T NW APARTMENT | 3798.50 | 4660.50 | 688.50 |
T SE APARTMENT | 4341.25 | 3529.00 | 517.25 |
T NE APARTMENT | 3847.50 | 4647.25 | 687.25 |
T N1 APARTMENT | 3568.50 | 4818.50 | 610.00 |
T N2 APARTMENT | 3570.75 | 4818.50 | 611.25 |
T S1 APARTMENT | 4159.25 | 3408.00 | 501.25 |
T S2 APARTMENT | 4166.75 | 3404.75 | 500.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5293.75 | 5943.00 | 1081.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.75 | 18.75 | 3.75 | 18.75 |
G NW APARTMENT | 2.00 | 22.50 | 2.00 | 22.50 |
OFFICE | 2.50 | 0.25 | 0.00 | 0.00 |
G NE APARTMENT | 4.25 | 34.50 | 4.25 | 34.50 |
G N1 APARTMENT | 3.50 | 36.00 | 3.50 | 36.00 |
G N2 APARTMENT | 5.00 | 36.25 | 5.00 | 36.25 |
G S1 APARTMENT | 0.00 | 136.75 | 0.00 | 136.75 |
G S2 APARTMENT | 0.00 | 111.00 | 0.00 | 111.00 |
F2 SW APARTMENT | 0.75 | 15.75 | 0.75 | 15.75 |
F2 NW APARTMENT | 0.50 | 16.50 | 0.50 | 16.50 |
F2 SE APARTMENT | 0.25 | 19.50 | 0.25 | 19.50 |
F2 NE APARTMENT | 1.25 | 28.50 | 1.25 | 28.50 |
F2 N1 APARTMENT | 0.00 | 23.50 | 0.00 | 23.50 |
F2 N2 APARTMENT | 0.25 | 23.25 | 0.25 | 23.25 |
F2 S1 APARTMENT | 0.00 | 160.00 | 0.00 | 160.00 |
F2 S2 APARTMENT | 0.00 | 151.25 | 0.00 | 151.25 |
F3 SW APARTMENT | 0.00 | 21.50 | 0.00 | 21.50 |
F3 NW APARTMENT | 0.50 | 18.75 | 0.50 | 18.75 |
F3 SE APARTMENT | 0.00 | 70.25 | 0.00 | 70.25 |
F3 NE APARTMENT | 1.75 | 37.50 | 1.75 | 37.50 |
F3 N1 APARTMENT | 0.25 | 29.25 | 0.25 | 29.25 |
F3 N2 APARTMENT | 0.25 | 30.25 | 0.25 | 30.25 |
F3 S1 APARTMENT | 0.00 | 182.25 | 0.00 | 182.25 |
F3 S2 APARTMENT | 0.00 | 181.00 | 0.00 | 181.00 |
F4 SW APARTMENT | 0.00 | 22.75 | 0.00 | 22.75 |
F4 NW APARTMENT | 0.00 | 19.00 | 0.00 | 19.00 |
F4 SE APARTMENT | 0.00 | 74.25 | 0.00 | 74.25 |
F4 NE APARTMENT | 1.50 | 41.50 | 1.50 | 41.50 |
F4 N1 APARTMENT | 0.25 | 32.25 | 0.25 | 32.25 |
F4 N2 APARTMENT | 0.25 | 33.00 | 0.25 | 33.00 |
F4 S1 APARTMENT | 0.00 | 179.75 | 0.00 | 179.75 |
F4 S2 APARTMENT | 0.00 | 180.25 | 0.00 | 180.25 |
M SW APARTMENT | 0.00 | 23.00 | 0.00 | 23.00 |
M NW APARTMENT | 0.00 | 19.50 | 0.00 | 19.50 |
M SE APARTMENT | 0.25 | 71.25 | 0.25 | 71.25 |
M NE APARTMENT | 1.50 | 44.25 | 1.50 | 44.25 |
M N1 APARTMENT | 0.00 | 33.00 | 0.00 | 33.00 |
M N2 APARTMENT | 0.25 | 34.00 | 0.25 | 34.00 |
M S1 APARTMENT | 0.00 | 172.50 | 0.00 | 172.50 |
M S2 APARTMENT | 0.00 | 173.50 | 0.00 | 173.50 |
F6 SW APARTMENT | 0.25 | 24.25 | 0.25 | 24.25 |
F6 NW APARTMENT | 0.50 | 19.75 | 0.50 | 19.75 |
F6 SE APARTMENT | 0.25 | 69.75 | 0.25 | 69.75 |
F6 NE APARTMENT | 1.00 | 47.75 | 1.00 | 47.75 |
F6 N1 APARTMENT | 0.25 | 34.50 | 0.25 | 34.50 |
F6 N2 APARTMENT | 0.25 | 35.75 | 0.25 | 35.75 |
F6 S1 APARTMENT | 0.00 | 166.50 | 0.00 | 166.50 |
F6 S2 APARTMENT | 0.00 | 167.00 | 0.00 | 167.00 |
F7 SW APARTMENT | 0.50 | 23.00 | 0.50 | 23.00 |
F7 NW APARTMENT | 0.00 | 20.25 | 0.00 | 20.25 |
F7 SE APARTMENT | 0.00 | 65.50 | 0.00 | 65.50 |
F7 NE APARTMENT | 1.75 | 49.25 | 1.75 | 49.25 |
F7 N1 APARTMENT | 0.75 | 36.50 | 0.75 | 36.50 |
F7 N2 APARTMENT | 1.00 | 37.25 | 1.00 | 37.25 |
F7 S1 APARTMENT | 0.00 | 161.25 | 0.00 | 161.25 |
F7 S2 APARTMENT | 0.00 | 159.50 | 0.00 | 159.50 |
F8 SW APARTMENT | 0.00 | 21.00 | 0.00 | 21.00 |
F8 NW APARTMENT | 0.50 | 20.25 | 0.50 | 20.25 |
F8 SE APARTMENT | 0.50 | 59.75 | 0.50 | 59.75 |
F8 NE APARTMENT | 1.25 | 52.50 | 1.25 | 52.50 |
F8 N1 APARTMENT | 0.25 | 37.75 | 0.25 | 37.75 |
F8 N2 APARTMENT | 0.50 | 39.25 | 0.50 | 39.25 |
F8 S1 APARTMENT | 0.00 | 152.75 | 0.00 | 152.75 |
F8 S2 APARTMENT | 0.00 | 151.75 | 0.00 | 151.75 |
F9 SW APARTMENT | 0.00 | 17.75 | 0.00 | 17.75 |
F9 NW APARTMENT | 0.00 | 19.75 | 0.00 | 19.75 |
F9 SE APARTMENT | 0.50 | 35.00 | 0.50 | 35.00 |
F9 NE APARTMENT | 0.50 | 36.75 | 0.50 | 36.75 |
F9 N1 APARTMENT | 0.50 | 33.00 | 0.50 | 33.00 |
F9 N2 APARTMENT | 2.00 | 34.00 | 2.00 | 34.00 |
F9 S1 APARTMENT | 0.00 | 127.50 | 0.00 | 127.50 |
F9 S2 APARTMENT | 0.00 | 125.25 | 0.00 | 125.25 |
T SW APARTMENT | 0.00 | 9.75 | 0.00 | 9.75 |
T NW APARTMENT | 0.00 | 16.25 | 0.00 | 16.25 |
T SE APARTMENT | 0.00 | 26.00 | 0.00 | 26.00 |
T NE APARTMENT | 0.00 | 8.50 | 0.00 | 8.50 |
T N1 APARTMENT | 0.00 | 18.25 | 0.00 | 18.25 |
T N2 APARTMENT | 1.25 | 16.00 | 1.25 | 16.00 |
T S1 APARTMENT | 1.00 | 74.25 | 1.00 | 74.25 |
T S2 APARTMENT | 1.00 | 74.25 | 1.00 | 74.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 43.00 | 295.00 | 40.50 | 294.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.091 | 0.000 | 0.348 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.091 | 0.000 | 0.332 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.099 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.091 | 0.000 | 0.331 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.055 | 0.000 | 0.324 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.055 | 0.000 | 0.324 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.055 | 0.000 | 0.344 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.055 | 0.000 | 0.345 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.407 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.130 | 0.000 | 0.392 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.408 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.130 | 0.000 | 0.391 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.079 | 0.000 | 0.387 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.079 | 0.000 | 0.387 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.079 | 0.000 | 0.406 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.079 | 0.000 | 0.406 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.449 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.154 | 0.000 | 0.434 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.449 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.154 | 0.000 | 0.433 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.093 | 0.000 | 0.430 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.093 | 0.000 | 0.430 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.093 | 0.000 | 0.448 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.093 | 0.000 | 0.448 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.173 | 0.000 | 0.467 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.172 | 0.000 | 0.451 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.173 | 0.000 | 0.467 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.172 | 0.000 | 0.450 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.104 | 0.000 | 0.448 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.104 | 0.000 | 0.448 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.104 | 0.000 | 0.466 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.104 | 0.000 | 0.466 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.188 | 0.000 | 0.490 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.187 | 0.000 | 0.473 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.188 | 0.000 | 0.490 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.187 | 0.000 | 0.473 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.113 | 0.000 | 0.470 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.113 | 0.000 | 0.470 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.113 | 0.000 | 0.489 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.113 | 0.000 | 0.489 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.200 | 0.000 | 0.510 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.200 | 0.000 | 0.492 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.200 | 0.000 | 0.510 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.200 | 0.000 | 0.491 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.121 | 0.000 | 0.489 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.121 | 0.000 | 0.489 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.121 | 0.000 | 0.509 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.121 | 0.000 | 0.509 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.212 | 0.000 | 0.526 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.212 | 0.000 | 0.507 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.212 | 0.000 | 0.526 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.212 | 0.000 | 0.507 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.128 | 0.000 | 0.504 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.128 | 0.000 | 0.504 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.128 | 0.000 | 0.525 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.128 | 0.000 | 0.525 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.222 | 0.000 | 0.544 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.222 | 0.000 | 0.524 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.222 | 0.000 | 0.545 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.222 | 0.000 | 0.524 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.134 | 0.000 | 0.521 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.134 | 0.000 | 0.521 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.134 | 0.000 | 0.543 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.134 | 0.000 | 0.544 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.231 | 0.000 | 0.560 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.231 | 0.000 | 0.539 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.231 | 0.000 | 0.560 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.231 | 0.000 | 0.539 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.139 | 0.000 | 0.536 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.139 | 0.000 | 0.536 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.559 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.140 | 0.000 | 0.559 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.571 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.551 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.572 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.240 | 0.000 | 0.551 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.548 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.145 | 0.000 | 0.548 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.145 | 0.000 | 0.570 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.145 | 0.000 | 0.570 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.506 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 640.88 | 20322.08 | 12-JAN-22:30 | 20322.08 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1335.91 | 20702.61 | 07-MAR-03:30 | 85481.08 | 26-JUL-17:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
ElectricityPurchased:Plant | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
Cogeneration:ElectricityPurchased | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
ElectricityNet:Plant | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
Cogeneration:ElectricityNet | 3120.83 | 58263.09 | 07-MAR-03:30 | 172060.80 | 17-JUL-20:00 |
ExteriorLights:Electricity | 168.57 | 0.00 | 01-JAN-07:15 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.57 | 0.00 | 01-JAN-07:15 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 640.88 | 20322.08 | 12-JAN-22:30 | 20322.08 | 01-JAN-00:15 |
Cooling:Electricity | 659.36 | 0.00 | 01-JAN-00:45 | 64061.41 | 15-JUN-15:30 |
Heating:Electricity | 14.85 | 0.00 | 01-JAN-09:30 | 26280.44 | 10-APR-17:00 |
Electricity:Plant | 68.84 | 36.93 | 16-JAN-10:45 | 3900.85 | 20-JUL-16:15 |
HeatRejection:Electricity | 24.64 | 0.00 | 01-JAN-01:00 | 2478.79 | 20-JUL-16:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 44.21 | 36.93 | 16-JAN-10:45 | 1422.06 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1015.24 | 9260.51 | 01-JAN-00:15 | 142092.63 | 27-DEC-07:30 |
Gas:Plant | 1015.24 | 9260.51 | 01-JAN-00:15 | 142092.63 | 27-DEC-07:30 |
WaterSystems:Gas | 995.45 | 9260.51 | 01-JAN-00:15 | 83866.65 | 07-FEB-08:00 |
Water Heater:WaterSystems:Gas | 995.45 | 9260.51 | 01-JAN-00:15 | 83866.65 | 07-FEB-08:00 |
Heating:Gas | 19.80 | 0.00 | 01-JAN-00:15 | 63834.18 | 27-DEC-06:15 |
Boiler:Heating:Gas | 19.80 | 0.00 | 01-JAN-00:15 | 63834.18 | 27-DEC-06:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 2697.06 | 0.00 | 01-JAN-00:45 | 304693.33 | 20-JUL-16:15 |
PlantLoopCoolingDemand:HVAC | 2697.06 | 0.00 | 01-JAN-00:45 | 304693.33 | 20-JUL-16:15 |
CoolingCoils:PlantLoopCoolingDemand | 2697.06 | 0.00 | 01-JAN-00:45 | 304693.33 | 20-JUL-16:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 7013.87 | 0.00 | 01-JAN-03:30 | 0.00 | 14-JUN-17:15 |
Water:Plant | 7013.87 | 0.00 | 01-JAN-03:30 | 0.00 | 14-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-03:00 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 7013.87 | 0.00 | 01-JAN-03:30 | 0.00 | 14-JUN-17:15 |
MainsWater:Plant | 7013.87 | 0.00 | 01-JAN-03:30 | 0.00 | 14-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-03:00 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-03:00 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-03:00 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 2235.35 | 0.00 | 01-JAN-01:00 | 0.00 | 14-JUN-16:15 |
HeatRejection:MainsWater | 2235.35 | 0.00 | 01-JAN-01:00 | 0.00 | 14-JUN-16:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 795.42 | 391.07 | 31-JUL-01:15 | 114085.18 | 10-APR-17:00 |
PlantLoopHeatingDemand:Plant | 755.20 | 391.07 | 31-JUL-01:15 | 53294.57 | 30-JAN-07:15 |
WaterSystems:PlantLoopHeatingDemand | 755.20 | 391.07 | 31-JUL-01:15 | 53294.57 | 30-JAN-07:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4625.22 | 5597.82 | 02-MAY-03:00 | 424514.20 | 05-JUN-17:15 |
EnergyTransfer:Building | 1722.05 | 3581.43 | 25-AUG-05:45 | 174532.02 | 05-JUN-17:00 |
EnergyTransfer:Zone:G SW APARTMENT | 16.52 | 0.01 | 22-FEB-22:45 | 2528.66 | 29-SEP-15:15 |
Heating:EnergyTransfer | 50.48 | 0.00 | 02-JAN-23:45 | 112307.63 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.60 | 0.00 | 01-JAN-00:15 | 671.81 | 27-DEC-06:00 |
Cooling:EnergyTransfer | 1671.57 | 0.00 | 03-JAN-18:15 | 174532.02 | 05-JUN-17:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 15.92 | 0.00 | 01-JAN-14:00 | 2528.66 | 29-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.73 | 0.00 | 11-APR-20:45 | 2370.62 | 12-JUN-17:45 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.60 | 0.00 | 01-JAN-00:15 | 979.79 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 12.12 | 0.00 | 01-JAN-00:30 | 2370.62 | 12-JUN-17:45 |
EnergyTransfer:Zone:OFFICE | 22.79 | 0.04 | 23-OCT-00:15 | 3133.75 | 29-SEP-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.48 | 0.00 | 01-JAN-00:15 | 764.45 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 22.31 | 0.00 | 01-JAN-06:45 | 3133.75 | 29-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 13.75 | 0.01 | 09-DEC-00:30 | 1767.79 | 17-JUN-18:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.38 | 0.00 | 01-JAN-08:30 | 967.14 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 12.38 | 0.00 | 01-JAN-00:15 | 1767.79 | 17-JUN-18:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 10.08 | 0.05 | 02-NOV-13:30 | 1327.67 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.62 | 0.00 | 01-JAN-00:15 | 992.92 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 9.47 | 0.00 | 01-JAN-14:00 | 1327.67 | 09-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 10.09 | 0.04 | 02-NOV-13:30 | 1315.87 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.62 | 0.00 | 01-JAN-00:15 | 983.50 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 9.48 | 0.00 | 01-JAN-14:00 | 1315.87 | 09-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 13.62 | 0.00 | 05-MAY-08:45 | 1533.82 | 30-SEP-11:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 725.53 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 13.55 | 0.00 | 03-JAN-13:30 | 1533.82 | 30-SEP-11:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 13.82 | 0.00 | 06-MAR-17:45 | 1582.19 | 30-SEP-11:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 623.70 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 13.75 | 0.00 | 02-JAN-16:00 | 1582.19 | 30-SEP-11:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 26.16 | 0.00 | 23-APR-01:45 | 3104.05 | 29-SEP-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 513.22 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 25.86 | 0.00 | 01-JAN-15:15 | 3104.05 | 29-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 19.68 | 0.01 | 24-JAN-02:30 | 2905.14 | 17-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 908.45 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 18.66 | 0.00 | 01-JAN-10:45 | 2905.14 | 17-JUN-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 27.56 | 0.01 | 03-DEC-01:30 | 2779.74 | 01-OCT-12:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 480.81 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 27.37 | 0.00 | 01-JAN-14:00 | 2779.74 | 01-OCT-12:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 19.96 | 0.01 | 25-DEC-13:00 | 2295.21 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 0.81 | 0.00 | 01-JAN-00:15 | 939.55 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 19.15 | 0.00 | 01-JAN-11:45 | 2295.21 | 10-JUN-09:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 15.38 | 0.22 | 14-MAR-14:30 | 1701.34 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 992.68 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 15.10 | 0.00 | 01-JAN-14:00 | 1701.34 | 09-JUN-17:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 15.39 | 0.09 | 23-SEP-19:30 | 1691.87 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 958.26 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 15.11 | 0.00 | 01-JAN-14:00 | 1691.87 | 09-JUN-17:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 22.24 | 0.03 | 06-OCT-12:15 | 1995.73 | 28-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 458.93 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 22.18 | 0.00 | 02-JAN-16:30 | 1995.73 | 28-OCT-14:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 22.34 | 0.01 | 26-MAR-12:15 | 2009.52 | 28-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 431.33 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 22.29 | 0.00 | 02-JAN-16:30 | 2009.52 | 28-OCT-14:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 27.78 | 0.06 | 16-JAN-20:45 | 3124.63 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 684.37 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 27.52 | 0.00 | 01-JAN-15:00 | 3124.63 | 22-OCT-14:45 |
EnergyTransfer:Zone:F3 NW APARTMENT | 20.71 | 0.00 | 23-FEB-00:15 | 2906.97 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 0.86 | 0.00 | 01-JAN-00:15 | 1043.22 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 19.84 | 0.00 | 01-JAN-11:00 | 2906.97 | 09-JUN-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 28.26 | 0.69 | 19-MAR-16:45 | 2713.67 | 01-OCT-10:15 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 579.05 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 28.09 | 0.00 | 01-JAN-14:00 | 2713.67 | 01-OCT-10:15 |
EnergyTransfer:Zone:F3 NE APARTMENT | 21.04 | 0.04 | 25-JAN-01:30 | 2350.01 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 0.69 | 0.00 | 01-JAN-00:15 | 1030.03 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 20.35 | 0.00 | 01-JAN-12:00 | 2350.01 | 10-JUN-09:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 16.66 | 0.03 | 23-SEP-19:45 | 1741.81 | 20-APR-18:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1065.97 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 16.43 | 0.00 | 01-JAN-14:00 | 1741.81 | 20-APR-18:00 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 16.67 | 0.04 | 07-OCT-14:00 | 1740.25 | 20-APR-18:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1046.64 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 16.44 | 0.00 | 01-JAN-14:00 | 1740.25 | 20-APR-18:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 24.34 | 0.02 | 09-DEC-16:30 | 2031.10 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 667.79 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 24.30 | 0.00 | 02-JAN-16:45 | 2031.10 | 03-NOV-14:30 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 24.38 | 0.04 | 14-OCT-10:30 | 2035.03 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 653.22 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 24.33 | 0.00 | 02-JAN-16:45 | 2035.03 | 03-NOV-14:30 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 28.06 | 0.08 | 03-MAR-23:00 | 3132.08 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 707.34 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 27.79 | 0.00 | 01-JAN-14:15 | 3132.08 | 22-OCT-14:45 |
EnergyTransfer:Zone:F4 NW APARTMENT | 20.95 | 0.00 | 07-FEB-04:15 | 2914.82 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 1007.70 | 06-APR-14:15 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 20.10 | 0.00 | 01-JAN-11:00 | 2914.82 | 09-JUN-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 28.40 | 0.01 | 22-APR-23:30 | 2717.80 | 01-OCT-10:15 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 787.07 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 28.22 | 0.00 | 01-JAN-14:15 | 2717.80 | 01-OCT-10:15 |
EnergyTransfer:Zone:F4 NE APARTMENT | 21.29 | 0.03 | 17-DEC-17:45 | 2357.91 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 0.67 | 0.00 | 01-JAN-00:15 | 1013.32 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 20.62 | 0.00 | 01-JAN-12:00 | 2357.91 | 10-JUN-09:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 17.03 | 0.05 | 08-NOV-17:00 | 1786.02 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 1049.85 | 06-APR-14:15 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 16.82 | 0.00 | 01-JAN-14:15 | 1786.02 | 09-MAY-20:00 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 17.04 | 0.05 | 24-OCT-14:15 | 1780.77 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 1032.00 | 06-APR-14:15 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 16.82 | 0.00 | 01-JAN-14:15 | 1780.77 | 09-MAY-20:00 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 24.86 | 0.05 | 06-MAR-09:45 | 2050.42 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 773.17 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 24.81 | 0.00 | 02-JAN-16:30 | 2050.42 | 03-NOV-14:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 24.88 | 0.02 | 23-SEP-19:30 | 2052.58 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 772.40 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 24.82 | 0.00 | 02-JAN-16:30 | 2052.58 | 03-NOV-14:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 28.42 | 0.05 | 29-JUN-08:15 | 3163.81 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 1039.17 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 28.13 | 0.00 | 01-JAN-14:15 | 3163.81 | 22-OCT-14:45 |
EnergyTransfer:Zone:M NW APARTMENT | 21.40 | 0.00 | 28-NOV-13:30 | 2946.42 | 19-MAY-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.88 | 0.00 | 01-JAN-00:15 | 1258.31 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 20.52 | 0.00 | 01-JAN-11:00 | 2946.42 | 19-MAY-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 28.74 | 0.35 | 22-APR-22:30 | 2757.70 | 01-OCT-10:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 1110.00 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 28.55 | 0.00 | 01-JAN-14:15 | 2757.70 | 01-OCT-10:15 |
EnergyTransfer:Zone:M NE APARTMENT | 21.74 | 0.03 | 31-JAN-19:45 | 2390.40 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.69 | 0.00 | 01-JAN-00:15 | 1323.04 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.05 | 0.00 | 01-JAN-12:00 | 2390.40 | 10-JUN-09:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 17.54 | 0.00 | 12-JUN-06:00 | 1859.36 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1303.66 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 17.31 | 0.00 | 01-JAN-14:15 | 1859.36 | 09-MAY-20:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 17.55 | 0.27 | 10-APR-08:45 | 1854.24 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1302.28 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 17.32 | 0.00 | 01-JAN-14:15 | 1854.24 | 09-MAY-20:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 25.38 | 0.01 | 08-SEP-06:00 | 2089.13 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 1068.62 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 25.31 | 0.00 | 02-JAN-16:30 | 2089.13 | 03-NOV-14:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 25.39 | 0.06 | 25-MAR-11:15 | 2090.83 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 1067.53 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 25.32 | 0.00 | 02-JAN-16:15 | 2090.83 | 03-NOV-14:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 27.30 | 0.13 | 13-FEB-12:45 | 3123.83 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 1403.25 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 26.96 | 0.00 | 01-JAN-14:15 | 3123.83 | 22-OCT-14:45 |
EnergyTransfer:Zone:F6 NW APARTMENT | 20.80 | 0.00 | 23-DEC-10:45 | 2915.28 | 19-MAY-17:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 1.04 | 0.00 | 01-JAN-00:15 | 1613.64 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 19.76 | 0.00 | 01-JAN-11:00 | 2915.28 | 19-MAY-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 27.60 | 0.05 | 29-NOV-17:00 | 2723.35 | 01-OCT-10:30 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1467.76 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 27.38 | 0.00 | 01-JAN-14:15 | 2723.35 | 01-OCT-10:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 21.11 | 0.02 | 22-JAN-14:45 | 2354.35 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 0.83 | 0.00 | 01-JAN-00:15 | 1667.72 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 20.28 | 0.00 | 01-JAN-12:00 | 2354.35 | 10-JUN-09:15 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 16.89 | 0.39 | 30-DEC-01:30 | 1860.26 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1628.70 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 16.61 | 0.00 | 01-JAN-14:15 | 1860.26 | 09-MAY-20:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 16.89 | 0.17 | 25-SEP-08:30 | 1851.49 | 09-MAY-20:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 1626.91 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 16.62 | 0.00 | 01-JAN-14:15 | 1851.49 | 09-MAY-20:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 24.28 | 0.12 | 21-APR-06:45 | 2054.81 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1407.77 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 24.20 | 0.00 | 02-JAN-16:00 | 2054.81 | 03-NOV-14:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 24.29 | 0.01 | 26-MAR-12:00 | 2058.77 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 1406.44 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 24.21 | 0.00 | 02-JAN-16:00 | 2058.77 | 03-NOV-14:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 26.68 | 0.08 | 26-FEB-00:45 | 3109.86 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1700.50 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 26.31 | 0.00 | 01-JAN-14:15 | 3109.86 | 22-OCT-14:45 |
EnergyTransfer:Zone:F7 NW APARTMENT | 20.60 | 0.00 | 30-NOV-20:30 | 2908.12 | 19-MAY-17:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 1901.28 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 19.41 | 0.00 | 01-JAN-10:45 | 2908.12 | 19-MAY-17:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 26.98 | 0.11 | 29-NOV-16:45 | 2717.26 | 01-OCT-10:30 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.26 | 0.00 | 01-JAN-00:15 | 1757.22 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 26.72 | 0.00 | 01-JAN-14:15 | 2717.26 | 01-OCT-10:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 20.89 | 0.06 | 13-NOV-20:45 | 2344.10 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 0.98 | 0.00 | 01-JAN-00:15 | 1949.08 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 19.91 | 0.00 | 01-JAN-12:00 | 2344.10 | 10-JUN-09:15 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 16.61 | 0.13 | 30-DEC-06:45 | 1893.92 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 1893.92 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 16.28 | 0.00 | 01-JAN-14:15 | 1853.38 | 09-MAY-20:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 16.61 | 0.11 | 26-APR-08:15 | 1891.83 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 1891.83 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 16.28 | 0.00 | 01-JAN-14:15 | 1844.71 | 09-MAY-20:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 23.69 | 0.01 | 13-OCT-09:45 | 2045.35 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 1680.95 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 23.60 | 0.00 | 01-JAN-15:15 | 2045.35 | 03-NOV-14:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 23.70 | 0.18 | 10-FEB-15:45 | 2049.27 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 1679.40 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 23.61 | 0.00 | 01-JAN-15:00 | 2049.27 | 03-NOV-14:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 26.25 | 0.02 | 13-FEB-10:00 | 3110.89 | 22-OCT-14:45 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 1957.45 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 25.83 | 0.00 | 01-JAN-14:15 | 3110.89 | 22-OCT-14:45 |
EnergyTransfer:Zone:F8 NW APARTMENT | 20.60 | 0.01 | 26-OCT-03:30 | 2912.09 | 19-MAY-17:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 1.37 | 0.00 | 01-JAN-00:15 | 2151.88 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 19.24 | 0.00 | 01-JAN-10:45 | 2912.09 | 19-MAY-17:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 26.55 | 0.03 | 04-MAR-01:00 | 2724.34 | 01-OCT-10:30 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 2008.06 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 26.25 | 0.00 | 01-JAN-14:15 | 2724.34 | 01-OCT-10:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 20.86 | 0.00 | 20-NOV-10:45 | 2348.10 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 1.14 | 0.00 | 01-JAN-00:15 | 2194.11 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 19.72 | 0.00 | 01-JAN-11:45 | 2348.10 | 10-JUN-09:15 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 16.50 | 0.06 | 23-SEP-20:45 | 2124.94 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 2124.94 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 16.11 | 0.00 | 01-JAN-14:15 | 1861.09 | 09-MAY-20:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 16.51 | 0.41 | 06-OCT-11:30 | 2122.52 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 2122.52 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 16.12 | 0.00 | 01-JAN-14:15 | 1852.54 | 09-MAY-20:00 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 23.26 | 0.14 | 09-OCT-05:45 | 2049.26 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 1918.24 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 23.15 | 0.00 | 01-JAN-15:00 | 2049.26 | 03-NOV-14:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 23.27 | 0.14 | 20-FEB-20:15 | 2053.15 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 1916.40 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 23.16 | 0.00 | 01-JAN-15:00 | 2053.15 | 03-NOV-14:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 26.05 | 0.00 | 28-FEB-19:30 | 3207.35 | 22-OCT-15:15 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 0.55 | 0.00 | 01-JAN-00:15 | 2169.49 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 25.50 | 0.00 | 01-JAN-14:15 | 3207.35 | 22-OCT-15:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 21.18 | 0.01 | 20-DEC-19:45 | 2985.56 | 27-JUN-17:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 1.75 | 0.00 | 01-JAN-00:15 | 2363.98 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 19.43 | 0.00 | 01-JAN-10:15 | 2985.56 | 27-JUN-17:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 26.34 | 0.01 | 04-MAR-04:00 | 2772.26 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 0.41 | 0.00 | 01-JAN-00:15 | 2214.88 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 25.92 | 0.00 | 01-JAN-14:15 | 2772.26 | 29-SEP-12:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 21.36 | 0.01 | 19-MAR-19:00 | 2442.19 | 10-JUN-09:15 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 1.46 | 0.00 | 01-JAN-00:15 | 2400.55 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 19.90 | 0.00 | 01-JAN-04:00 | 2442.19 | 10-JUN-09:15 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 16.73 | 0.05 | 21-MAR-22:00 | 2322.92 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.54 | 0.00 | 01-JAN-00:15 | 2322.92 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 16.19 | 0.00 | 01-JAN-14:15 | 1947.34 | 09-MAY-20:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 16.74 | 0.17 | 29-OCT-18:30 | 2319.96 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.55 | 0.00 | 01-JAN-00:15 | 2319.96 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 16.20 | 0.00 | 01-JAN-14:15 | 1938.82 | 09-MAY-20:00 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 22.93 | 0.06 | 27-OCT-21:00 | 2118.07 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 2118.07 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 22.79 | 0.00 | 01-JAN-14:15 | 2108.07 | 03-NOV-14:30 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 22.95 | 0.16 | 03-FEB-15:30 | 2115.72 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 2115.72 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 22.80 | 0.00 | 01-JAN-14:15 | 2105.44 | 03-NOV-14:30 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 28.30 | 0.01 | 31-JAN-09:45 | 3865.88 | 22-OCT-15:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 2.42 | 0.00 | 01-JAN-06:45 | 3115.91 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 25.87 | 0.00 | 01-JAN-00:15 | 3865.88 | 22-OCT-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 24.66 | 0.05 | 05-DEC-11:30 | 3650.52 | 27-JUN-17:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 4.43 | 0.00 | 02-JAN-23:45 | 3225.40 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 20.23 | 0.00 | 01-JAN-00:15 | 3650.52 | 27-JUN-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 28.03 | 0.01 | 11-FEB-24:00 | 3422.93 | 01-OCT-11:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 2.13 | 0.00 | 01-JAN-00:15 | 3217.25 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.91 | 0.00 | 01-JAN-02:30 | 3422.93 | 01-OCT-11:15 |
EnergyTransfer:Zone:T NE APARTMENT | 24.05 | 0.01 | 19-FEB-03:00 | 3321.25 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 3.82 | 0.00 | 01-JAN-08:45 | 3321.25 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 20.23 | 0.00 | 01-JAN-00:15 | 2954.87 | 05-JUN-17:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 18.07 | 0.01 | 10-DEC-01:00 | 3141.35 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.80 | 0.00 | 01-JAN-00:15 | 3141.35 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.27 | 0.00 | 01-JAN-03:30 | 2343.60 | 17-JUN-18:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 18.09 | 0.00 | 03-JAN-21:00 | 3143.05 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.81 | 0.00 | 01-JAN-00:15 | 3143.05 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.28 | 0.00 | 01-JAN-03:30 | 2338.36 | 17-JUN-18:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 23.10 | 0.03 | 15-OCT-04:15 | 3023.03 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 3023.03 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 22.42 | 0.00 | 01-JAN-14:30 | 2795.84 | 22-OCT-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 23.12 | 0.01 | 11-DEC-16:15 | 3025.13 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 3025.13 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 22.44 | 0.00 | 01-JAN-14:30 | 2799.63 | 22-OCT-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 771.01 | 391.07 | 31-JUL-01:15 | 101089.11 | 27-DEC-06:15 |
WaterSystems:EnergyTransfer | 755.19 | 391.07 | 31-JUL-01:15 | 53289.12 | 30-JAN-07:15 |
sub cat:WaterSystems:EnergyTransfer | 755.19 | 391.07 | 31-JUL-01:15 | 53289.12 | 30-JAN-07:15 |
EnergyTransfer:HVAC | 2132.17 | 0.00 | 16-JAN-10:45 | 241632.72 | 20-JUL-16:15 |
CoolingCoils:EnergyTransfer | 2079.91 | 0.00 | 01-JAN-00:45 | 241632.72 | 20-JUL-16:15 |
HeatingCoils:EnergyTransfer | 52.25 | 0.00 | 01-JAN-09:30 | 103009.80 | 10-APR-17:00 |
PlantLoopHeatingDemand:HVAC | 40.23 | 0.00 | 01-JAN-09:30 | 78856.25 | 10-APR-17:00 |
HeatingCoils:PlantLoopHeatingDemand | 40.23 | 0.00 | 01-JAN-09:30 | 78856.25 | 10-APR-17:00 |
Boilers:EnergyTransfer | 15.81 | 0.00 | 01-JAN-00:15 | 51067.35 | 27-DEC-06:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.600 | -15.921 | 0.000 | 0.000 | 3.680 | 2.413 | 12.213 | 23.120 | 0.000 | 0.477 | 0.000 | 0.000 | -7.543 | 0.000 | -4.631 | -14.408 |
G NW APARTMENT | 1.604 | -12.122 | 0.000 | 0.000 | 3.737 | 2.413 | 12.213 | 13.098 | 0.000 | 0.473 | 0.000 | 0.000 | -7.532 | 0.000 | -4.040 | -9.844 |
OFFICE | 0.481 | -22.313 | 0.000 | 0.000 | 0.506 | 21.954 | 7.547 | 23.160 | 0.000 | 0.324 | 0.000 | 0.000 | -7.401 | 0.000 | -1.443 | -22.814 |
G NE APARTMENT | 1.377 | -12.377 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 12.975 | 0.000 | 0.472 | 0.000 | 0.000 | -7.125 | 0.000 | -4.014 | -9.686 |
G N1 APARTMENT | 0.618 | -9.465 | 0.000 | 0.000 | 3.754 | 2.413 | 12.213 | 4.680 | 0.000 | 0.345 | 0.000 | 0.000 | -4.583 | 0.000 | -3.237 | -6.736 |
G N2 APARTMENT | 0.619 | -9.475 | 0.000 | 0.000 | 3.755 | 2.413 | 12.213 | 4.677 | 0.000 | 0.345 | 0.000 | 0.000 | -4.579 | 0.000 | -3.237 | -6.731 |
G S1 APARTMENT | 0.067 | -13.550 | 0.000 | 0.000 | 3.676 | 2.413 | 12.213 | 14.848 | 0.000 | 0.346 | 0.000 | 0.000 | -4.568 | 0.000 | -3.918 | -11.527 |
G S2 APARTMENT | 0.071 | -13.749 | 0.000 | 0.000 | 3.673 | 2.413 | 12.213 | 14.836 | 0.000 | 0.347 | 0.000 | 0.000 | -4.575 | 0.000 | -3.945 | -11.283 |
F2 SW APARTMENT | 0.292 | -25.863 | 0.000 | 0.000 | 3.592 | 2.413 | 12.213 | 22.134 | 0.000 | 0.647 | 0.000 | 0.000 | -8.258 | 0.000 | -6.043 | -1.127 |
F2 NW APARTMENT | 1.016 | -18.663 | 0.000 | 0.000 | 3.673 | 2.413 | 12.213 | 12.419 | 0.000 | 0.641 | 0.000 | 0.000 | -8.182 | 0.000 | -5.415 | -0.115 |
F2 SE APARTMENT | 0.195 | -27.367 | 0.000 | 0.000 | 3.593 | 2.413 | 12.213 | 22.189 | 0.000 | 0.646 | 0.275 | 0.000 | -8.071 | 0.000 | -6.086 | -0.000 |
F2 NE APARTMENT | 0.814 | -19.147 | 0.000 | 0.000 | 3.689 | 2.413 | 12.213 | 12.317 | 0.000 | 0.640 | 0.148 | 0.000 | -7.717 | 0.000 | -5.369 | -0.000 |
F2 N1 APARTMENT | 0.284 | -15.098 | 0.000 | 0.000 | 3.680 | 2.413 | 12.213 | 4.341 | 0.000 | 0.457 | 1.133 | 0.000 | -5.050 | 0.000 | -4.373 | -0.000 |
F2 N2 APARTMENT | 0.285 | -15.108 | 0.000 | 0.000 | 3.681 | 2.413 | 12.213 | 4.340 | 0.000 | 0.457 | 1.136 | 0.000 | -5.045 | 0.000 | -4.372 | -0.000 |
F2 S1 APARTMENT | 0.051 | -22.184 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 14.227 | 0.000 | 0.459 | 0.001 | 0.000 | -5.010 | 0.000 | -5.121 | -0.623 |
F2 S2 APARTMENT | 0.052 | -22.291 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 14.224 | 0.000 | 0.459 | 0.000 | 0.000 | -5.012 | 0.000 | -5.128 | -0.506 |
F3 SW APARTMENT | 0.265 | -27.517 | 0.000 | 0.000 | 3.579 | 2.413 | 12.213 | 21.720 | 0.000 | 0.786 | 1.696 | 0.000 | -8.419 | 0.000 | -6.736 | -0.000 |
F3 NW APARTMENT | 0.865 | -19.840 | 0.000 | 0.000 | 3.657 | 2.413 | 12.213 | 12.158 | 0.000 | 0.779 | 2.238 | 0.000 | -8.376 | 0.000 | -6.107 | -0.000 |
F3 SE APARTMENT | 0.170 | -28.085 | 0.000 | 0.000 | 3.586 | 2.413 | 12.213 | 21.831 | 0.000 | 0.783 | 2.015 | 0.000 | -8.188 | 0.000 | -6.737 | -0.000 |
F3 NE APARTMENT | 0.692 | -20.351 | 0.000 | 0.000 | 3.674 | 2.413 | 12.213 | 12.072 | 0.000 | 0.776 | 2.465 | 0.000 | -7.897 | 0.000 | -6.057 | -0.000 |
F3 N1 APARTMENT | 0.233 | -16.432 | 0.000 | 0.000 | 3.656 | 2.413 | 12.213 | 4.237 | 0.000 | 0.560 | 3.267 | 0.000 | -5.205 | 0.000 | -4.943 | 0.000 |
F3 N2 APARTMENT | 0.232 | -16.439 | 0.000 | 0.000 | 3.658 | 2.413 | 12.213 | 4.236 | 0.000 | 0.560 | 3.268 | 0.000 | -5.199 | 0.000 | -4.941 | 0.000 |
F3 S1 APARTMENT | 0.048 | -24.296 | 0.000 | 0.000 | 3.558 | 2.413 | 12.213 | 13.966 | 0.000 | 0.561 | 2.331 | 0.000 | -5.121 | 0.000 | -5.672 | -0.000 |
F3 S2 APARTMENT | 0.048 | -24.328 | 0.000 | 0.000 | 3.559 | 2.413 | 12.213 | 13.964 | 0.000 | 0.561 | 2.365 | 0.000 | -5.120 | 0.000 | -5.675 | -0.000 |
F4 SW APARTMENT | 0.269 | -27.790 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 21.454 | 0.000 | 0.862 | 2.522 | 0.000 | -8.481 | 0.000 | -7.039 | -0.000 |
F4 NW APARTMENT | 0.853 | -20.097 | 0.000 | 0.000 | 3.653 | 2.413 | 12.213 | 12.001 | 0.000 | 0.854 | 3.000 | 0.000 | -8.466 | 0.000 | -6.424 | -0.000 |
F4 SE APARTMENT | 0.176 | -28.221 | 0.000 | 0.000 | 3.585 | 2.413 | 12.213 | 21.584 | 0.000 | 0.859 | 2.671 | 0.000 | -8.242 | 0.000 | -7.039 | -0.001 |
F4 NE APARTMENT | 0.673 | -20.620 | 0.000 | 0.000 | 3.669 | 2.413 | 12.213 | 11.925 | 0.000 | 0.851 | 3.230 | 0.000 | -7.979 | 0.000 | -6.376 | -0.000 |
F4 N1 APARTMENT | 0.218 | -16.815 | 0.000 | 0.000 | 3.647 | 2.413 | 12.213 | 4.181 | 0.000 | 0.611 | 3.977 | 0.000 | -5.280 | 0.000 | -5.165 | 0.000 |
F4 N2 APARTMENT | 0.216 | -16.821 | 0.000 | 0.000 | 3.649 | 2.413 | 12.213 | 4.180 | 0.000 | 0.611 | 3.978 | 0.000 | -5.275 | 0.000 | -5.163 | 0.000 |
F4 S1 APARTMENT | 0.054 | -24.810 | 0.000 | 0.000 | 3.555 | 2.413 | 12.213 | 13.798 | 0.000 | 0.612 | 3.193 | 0.000 | -5.165 | 0.000 | -5.864 | -0.000 |
F4 S2 APARTMENT | 0.055 | -24.821 | 0.000 | 0.000 | 3.555 | 2.413 | 12.213 | 13.797 | 0.000 | 0.612 | 3.205 | 0.000 | -5.163 | 0.000 | -5.865 | -0.000 |
M SW APARTMENT | 0.291 | -28.130 | 0.000 | 0.000 | 3.577 | 2.413 | 12.213 | 21.240 | 0.000 | 0.923 | 3.459 | 0.000 | -8.533 | 0.000 | -7.452 | -0.000 |
M NW APARTMENT | 0.879 | -20.520 | 0.000 | 0.000 | 3.651 | 2.413 | 12.213 | 11.876 | 0.000 | 0.914 | 3.918 | 0.000 | -8.533 | 0.000 | -6.813 | -0.000 |
M SE APARTMENT | 0.193 | -28.549 | 0.000 | 0.000 | 3.585 | 2.413 | 12.213 | 21.381 | 0.000 | 0.920 | 3.585 | 0.000 | -8.291 | 0.000 | -7.450 | -0.000 |
M NE APARTMENT | 0.691 | -21.052 | 0.000 | 0.000 | 3.667 | 2.413 | 12.213 | 11.806 | 0.000 | 0.911 | 4.153 | 0.000 | -8.040 | 0.000 | -6.763 | 0.000 |
M N1 APARTMENT | 0.233 | -17.311 | 0.000 | 0.000 | 3.643 | 2.413 | 12.213 | 4.136 | 0.000 | 0.651 | 4.826 | 0.000 | -5.334 | 0.000 | -5.469 | 0.000 |
M N2 APARTMENT | 0.232 | -17.319 | 0.000 | 0.000 | 3.644 | 2.413 | 12.213 | 4.135 | 0.000 | 0.651 | 4.826 | 0.000 | -5.328 | 0.000 | -5.467 | 0.000 |
M S1 APARTMENT | 0.065 | -25.312 | 0.000 | 0.000 | 3.554 | 2.413 | 12.213 | 13.664 | 0.000 | 0.652 | 4.131 | 0.000 | -5.200 | 0.000 | -6.180 | -0.000 |
M S2 APARTMENT | 0.066 | -25.319 | 0.000 | 0.000 | 3.554 | 2.413 | 12.213 | 13.663 | 0.000 | 0.652 | 4.138 | 0.000 | -5.198 | 0.000 | -6.181 | -0.000 |
F6 SW APARTMENT | 0.333 | -26.963 | 0.000 | 0.000 | 3.585 | 2.413 | 12.213 | 21.105 | 0.000 | 0.974 | 2.615 | 0.000 | -8.513 | 0.000 | -7.762 | -0.000 |
F6 NW APARTMENT | 1.036 | -19.764 | 0.000 | 0.000 | 3.662 | 2.413 | 12.213 | 11.820 | 0.000 | 0.964 | 3.216 | 0.000 | -8.502 | 0.000 | -7.058 | -0.000 |
F6 SE APARTMENT | 0.227 | -27.376 | 0.000 | 0.000 | 3.593 | 2.413 | 12.213 | 21.255 | 0.000 | 0.971 | 2.736 | 0.000 | -8.269 | 0.000 | -7.762 | -0.000 |
F6 NE APARTMENT | 0.834 | -20.276 | 0.000 | 0.000 | 3.678 | 2.413 | 12.213 | 11.757 | 0.000 | 0.961 | 3.437 | 0.000 | -8.008 | 0.000 | -7.009 | 0.000 |
F6 N1 APARTMENT | 0.277 | -16.609 | 0.000 | 0.000 | 3.655 | 2.413 | 12.213 | 4.126 | 0.000 | 0.684 | 4.191 | 0.000 | -5.314 | 0.000 | -5.635 | 0.000 |
F6 N2 APARTMENT | 0.275 | -16.615 | 0.000 | 0.000 | 3.656 | 2.413 | 12.213 | 4.124 | 0.000 | 0.684 | 4.192 | 0.000 | -5.308 | 0.000 | -5.634 | 0.000 |
F6 S1 APARTMENT | 0.078 | -24.200 | 0.000 | 0.000 | 3.560 | 2.413 | 12.213 | 13.578 | 0.000 | 0.686 | 3.272 | 0.000 | -5.191 | 0.000 | -6.409 | -0.000 |
F6 S2 APARTMENT | 0.078 | -24.210 | 0.000 | 0.000 | 3.561 | 2.413 | 12.213 | 13.577 | 0.000 | 0.686 | 3.282 | 0.000 | -5.189 | 0.000 | -6.410 | -0.000 |
F7 SW APARTMENT | 0.373 | -26.307 | 0.000 | 0.000 | 3.591 | 2.413 | 12.213 | 20.980 | 0.000 | 1.018 | 2.244 | 0.000 | -8.505 | 0.000 | -8.020 | -0.000 |
F7 NW APARTMENT | 1.191 | -19.406 | 0.000 | 0.000 | 3.671 | 2.413 | 12.213 | 11.763 | 0.000 | 1.007 | 2.906 | 0.000 | -8.487 | 0.000 | -7.271 | -0.000 |
F7 SE APARTMENT | 0.263 | -26.720 | 0.000 | 0.000 | 3.599 | 2.413 | 12.213 | 21.136 | 0.000 | 1.015 | 2.364 | 0.000 | -8.261 | 0.000 | -8.022 | -0.000 |
F7 NE APARTMENT | 0.978 | -19.910 | 0.000 | 0.000 | 3.686 | 2.413 | 12.213 | 11.705 | 0.000 | 1.003 | 3.126 | 0.000 | -7.992 | 0.000 | -7.222 | 0.000 |
F7 N1 APARTMENT | 0.328 | -16.277 | 0.000 | 0.000 | 3.664 | 2.413 | 12.213 | 4.112 | 0.000 | 0.712 | 3.914 | 0.000 | -5.301 | 0.000 | -5.777 | 0.000 |
F7 N2 APARTMENT | 0.326 | -16.284 | 0.000 | 0.000 | 3.665 | 2.413 | 12.213 | 4.110 | 0.000 | 0.712 | 3.916 | 0.000 | -5.296 | 0.000 | -5.775 | 0.000 |
F7 S1 APARTMENT | 0.091 | -23.597 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 13.498 | 0.000 | 0.715 | 2.885 | 0.000 | -5.189 | 0.000 | -6.595 | -0.000 |
F7 S2 APARTMENT | 0.091 | -23.607 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 13.497 | 0.000 | 0.715 | 2.895 | 0.000 | -5.187 | 0.000 | -6.597 | -0.000 |
F8 SW APARTMENT | 0.423 | -25.829 | 0.000 | 0.000 | 3.598 | 2.413 | 12.213 | 20.870 | 0.000 | 1.066 | 2.018 | 0.000 | -8.498 | 0.000 | -8.274 | -0.000 |
F8 NW APARTMENT | 1.367 | -19.235 | 0.000 | 0.000 | 3.678 | 2.413 | 12.213 | 11.711 | 0.000 | 1.055 | 2.760 | 0.000 | -8.476 | 0.000 | -7.485 | -0.000 |
F8 SE APARTMENT | 0.308 | -26.245 | 0.000 | 0.000 | 3.606 | 2.413 | 12.213 | 21.030 | 0.000 | 1.063 | 2.143 | 0.000 | -8.253 | 0.000 | -8.277 | -0.000 |
F8 NE APARTMENT | 1.138 | -19.724 | 0.000 | 0.000 | 3.693 | 2.413 | 12.213 | 11.656 | 0.000 | 1.050 | 2.978 | 0.000 | -7.980 | 0.000 | -7.435 | 0.000 |
F8 N1 APARTMENT | 0.391 | -16.106 | 0.000 | 0.000 | 3.672 | 2.413 | 12.213 | 4.097 | 0.000 | 0.746 | 3.790 | 0.000 | -5.290 | 0.000 | -5.926 | 0.000 |
F8 N2 APARTMENT | 0.392 | -16.117 | 0.000 | 0.000 | 3.674 | 2.413 | 12.213 | 4.096 | 0.000 | 0.746 | 3.792 | 0.000 | -5.285 | 0.000 | -5.924 | 0.000 |
F8 S1 APARTMENT | 0.106 | -23.150 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 13.429 | 0.000 | 0.750 | 2.638 | 0.000 | -5.186 | 0.000 | -6.784 | -0.000 |
F8 S2 APARTMENT | 0.107 | -23.162 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 13.427 | 0.000 | 0.750 | 2.650 | 0.000 | -5.184 | 0.000 | -6.786 | -0.001 |
F9 SW APARTMENT | 0.548 | -25.500 | 0.000 | 0.000 | 3.608 | 2.413 | 12.213 | 20.789 | 0.000 | 1.108 | 1.758 | 0.000 | -8.467 | 0.000 | -8.469 | -0.000 |
F9 NW APARTMENT | 1.746 | -19.433 | 0.000 | 0.000 | 3.685 | 2.413 | 12.213 | 11.669 | 0.000 | 1.095 | 2.725 | 0.000 | -8.456 | 0.000 | -7.657 | -0.000 |
F9 SE APARTMENT | 0.413 | -25.923 | 0.000 | 0.000 | 3.616 | 2.413 | 12.213 | 20.949 | 0.000 | 1.105 | 1.912 | 0.000 | -8.222 | 0.000 | -8.476 | -0.000 |
F9 NE APARTMENT | 1.461 | -19.896 | 0.000 | 0.000 | 3.700 | 2.413 | 12.213 | 11.618 | 0.000 | 1.092 | 2.972 | 0.000 | -7.961 | 0.000 | -7.612 | -0.000 |
F9 N1 APARTMENT | 0.542 | -16.186 | 0.000 | 0.000 | 3.682 | 2.413 | 12.213 | 4.086 | 0.000 | 0.775 | 3.778 | 0.000 | -5.267 | 0.000 | -6.036 | 0.000 |
F9 N2 APARTMENT | 0.545 | -16.198 | 0.000 | 0.000 | 3.684 | 2.413 | 12.213 | 4.084 | 0.000 | 0.775 | 3.782 | 0.000 | -5.262 | 0.000 | -6.036 | -0.000 |
F9 S1 APARTMENT | 0.141 | -22.788 | 0.000 | 0.000 | 3.583 | 2.413 | 12.213 | 13.377 | 0.000 | 0.781 | 2.363 | 0.000 | -5.165 | 0.000 | -6.919 | -0.000 |
F9 S2 APARTMENT | 0.142 | -22.804 | 0.000 | 0.000 | 3.584 | 2.413 | 12.213 | 13.376 | 0.000 | 0.781 | 2.380 | 0.000 | -5.163 | 0.000 | -6.922 | -0.000 |
T SW APARTMENT | 2.422 | -25.873 | 0.000 | 0.000 | 3.661 | 2.413 | 12.213 | 20.472 | 0.000 | 1.138 | 0.076 | 0.000 | -7.991 | 0.000 | -8.531 | -0.000 |
T NW APARTMENT | 4.433 | -20.227 | 0.000 | 0.000 | 3.707 | 2.413 | 12.213 | 11.384 | 0.000 | 1.125 | 0.893 | 0.000 | -8.086 | 0.000 | -7.854 | -0.001 |
T SE APARTMENT | 2.126 | -25.907 | 0.000 | 0.000 | 3.668 | 2.413 | 12.213 | 20.645 | 0.000 | 1.137 | 0.030 | 0.000 | -7.772 | 0.000 | -8.553 | -0.000 |
T NE APARTMENT | 3.822 | -20.230 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 11.389 | 0.000 | 1.125 | 1.013 | 0.000 | -7.651 | 0.000 | -7.816 | -0.000 |
T N1 APARTMENT | 1.803 | -16.268 | 0.000 | 0.000 | 3.710 | 2.413 | 12.213 | 3.996 | 0.000 | 0.797 | 2.495 | 0.000 | -5.022 | 0.000 | -6.137 | -0.000 |
T N2 APARTMENT | 1.812 | -16.278 | 0.000 | 0.000 | 3.711 | 2.413 | 12.213 | 3.991 | 0.000 | 0.797 | 2.496 | 0.000 | -5.015 | 0.000 | -6.140 | -0.000 |
T S1 APARTMENT | 0.682 | -22.416 | 0.000 | 0.000 | 3.643 | 2.413 | 12.213 | 13.218 | 0.000 | 0.809 | 1.279 | 0.000 | -4.903 | 0.000 | -6.938 | -0.000 |
T S2 APARTMENT | 0.685 | -22.435 | 0.000 | 0.000 | 3.643 | 2.413 | 12.213 | 13.214 | 0.000 | 0.809 | 1.301 | 0.000 | -4.900 | 0.000 | -6.943 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 5.481 | 0.000 | 3.855 | 0.001 | 0.000 | -1.815 | 0.000 | -21.481 | -4.570 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.517 | 0.000 | 0.046 | 0.000 | 0.000 | -1.067 | 0.000 | -0.418 | -19.607 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.452 | 0.000 | 0.052 | 0.000 | 0.000 | -1.107 | 0.000 | -0.514 | -19.413 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.411 | 0.000 | 0.056 | 0.000 | 0.000 | -1.128 | 0.000 | -0.584 | -19.285 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 2.366 | 0.000 | 0.051 | 0.000 | 0.000 | -1.159 | 0.000 | -0.675 | -37.642 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.372 | 0.000 | 0.065 | 0.000 | 0.000 | -1.134 | 0.000 | -0.677 | -19.155 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.365 | 0.000 | 0.070 | 0.000 | 0.000 | -1.125 | 0.000 | -0.707 | -19.133 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.355 | 0.000 | 0.073 | 0.000 | 0.000 | -1.122 | 0.000 | -0.737 | -19.098 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.345 | 0.000 | 0.073 | 0.000 | 0.000 | -1.120 | 0.000 | -0.762 | -19.065 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 2.274 | 0.000 | 0.047 | 0.000 | 0.000 | -1.088 | 0.000 | -0.816 | -26.883 |
Total Facility | 50.477 | -1671.540 | 0.000 | 0.000 | 287.913 | 416.414 | 980.287 | 1054.244 | 0.000 | 65.420 | 186.366 | 0.000 | -542.117 | 0.000 | -528.212 | -299.260 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-SEP-15:15 | 0.00 | -2528.74 | 0.00 | 0.00 | 48.64 | 100.83 | 470.89 | 3485.61 | 0.00 | 16.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1593.38 |
G NW APARTMENT | 12-JUN-17:30 | 0.00 | -2374.22 | 0.00 | 0.00 | 141.38 | 194.45 | 588.62 | 2752.36 | 0.00 | 65.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1367.96 |
OFFICE | 29-SEP-13:30 | 0.00 | -3133.26 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 2666.66 | 0.00 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1791.63 |
G NE APARTMENT | 17-JUN-18:15 | 0.00 | -1768.15 | 0.00 | 0.00 | 140.92 | 230.46 | 547.42 | 931.11 | 0.00 | 112.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -194.54 |
G N1 APARTMENT | 09-JUN-17:20 | 0.00 | -1330.13 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 819.39 | 0.00 | 65.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -479.39 |
G N2 APARTMENT | 09-JUN-17:20 | 0.00 | -1318.36 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 819.68 | 0.00 | 65.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491.46 |
G S1 APARTMENT | 30-SEP-11:15 | 0.00 | -1533.89 | 0.00 | 0.00 | 40.29 | 28.81 | 406.15 | 2659.85 | 0.00 | 31.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1633.16 |
G S2 APARTMENT | 30-SEP-11:15 | 0.00 | -1582.26 | 0.00 | 0.00 | 40.39 | 28.81 | 406.15 | 2659.90 | 0.00 | 35.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1587.99 |
F2 SW APARTMENT | 29-SEP-15:15 | 0.00 | -3104.13 | 0.00 | 0.00 | 48.85 | 100.83 | 470.89 | 3432.11 | 0.00 | 23.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -972.10 |
F2 NW APARTMENT | 17-JUN-17:30 | 0.00 | -2907.12 | 0.00 | 0.00 | 139.45 | 194.45 | 588.62 | 2627.63 | 0.00 | 122.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.12 |
F2 SE APARTMENT | 01-OCT-12:30 | 0.00 | -2779.56 | 0.00 | 0.00 | 40.74 | 28.81 | 388.49 | 3046.12 | 0.00 | 32.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -757.57 |
F2 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2295.20 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1890.17 | 0.00 | 325.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -396.14 |
F2 N1 APARTMENT | 09-JUN-17:20 | 0.00 | -1705.04 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 794.51 | 0.00 | 93.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.98 |
F2 N2 APARTMENT | 09-JUN-17:20 | 0.00 | -1695.52 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 794.66 | 0.00 | 93.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.64 |
F2 S1 APARTMENT | 28-OCT-14:30 | 0.00 | -1995.67 | 0.00 | 0.00 | 40.53 | 50.41 | 400.26 | 2212.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.06 | -601.41 |
F2 S2 APARTMENT | 28-OCT-14:30 | 0.00 | -2009.45 | 0.00 | 0.00 | 40.56 | 50.41 | 400.26 | 2213.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -105.76 | -589.02 |
F3 SW APARTMENT | 22-OCT-14:45 | 0.00 | -3124.47 | 0.00 | 0.00 | 40.70 | 50.41 | 400.26 | 3391.38 | 0.00 | 186.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -945.18 |
F3 NW APARTMENT | 09-JUN-17:30 | 0.00 | -2907.21 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2366.61 | 0.00 | 183.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.65 |
F3 SE APARTMENT | 01-OCT-10:15 | 0.00 | -2713.99 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3482.51 | 0.00 | 35.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1286.09 |
F3 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2350.04 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1858.55 | 0.00 | 367.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.38 |
F3 N1 APARTMENT | 20-APR-18:00 | 0.00 | -1740.07 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 89.19 | 0.00 | 625.37 | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 20-APR-18:00 | 0.00 | -1738.51 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 89.22 | 0.00 | 625.37 | 99.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2031.06 | 0.00 | 0.00 | 40.25 | 50.41 | 400.26 | 2342.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.44 | -694.44 |
F3 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2035.00 | 0.00 | 0.00 | 40.26 | 50.41 | 400.26 | 2342.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -106.87 | -691.14 |
F4 SW APARTMENT | 22-OCT-14:45 | 0.00 | -3131.92 | 0.00 | 0.00 | 40.67 | 50.41 | 400.26 | 3377.55 | 0.00 | 186.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -923.95 |
F4 NW APARTMENT | 09-JUN-17:30 | 0.00 | -2915.07 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2337.43 | 0.00 | 204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -551.70 |
F4 SE APARTMENT | 01-OCT-10:15 | 0.00 | -2718.13 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3481.38 | 0.00 | 34.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1279.29 |
F4 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2357.97 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1836.71 | 0.00 | 395.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.23 |
F4 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1783.18 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 593.60 | 309.52 | 0.00 | -16.08 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1777.94 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 593.60 | 304.13 | 0.00 | -15.93 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 10-NOV-14:55 | 0.00 | -2088.71 | 0.00 | 0.00 | 42.18 | 28.81 | 382.60 | 1577.14 | 0.00 | 0.00 | 207.70 | 0.00 | 0.00 | 0.00 | -149.72 | 0.00 |
F4 S2 APARTMENT | 10-NOV-14:55 | 0.00 | -2085.74 | 0.00 | 0.00 | 42.18 | 28.81 | 382.60 | 1577.14 | 0.00 | 0.00 | 204.73 | 0.00 | 0.00 | 0.00 | -149.72 | 0.00 |
M SW APARTMENT | 22-OCT-14:45 | 0.00 | -3163.65 | 0.00 | 0.00 | 40.68 | 50.41 | 400.26 | 3365.77 | 0.00 | 188.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -881.98 |
M NW APARTMENT | 19-MAY-17:30 | 0.00 | -2946.48 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2197.58 | 0.00 | 306.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -482.83 |
M SE APARTMENT | 01-OCT-10:15 | 0.00 | -2758.06 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3479.73 | 0.00 | 33.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1236.76 |
M NE APARTMENT | 10-JUN-09:15 | 0.00 | -2390.48 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1818.91 | 0.00 | 418.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.81 |
M N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1856.33 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 634.85 | 341.03 | 0.00 | -15.70 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1851.20 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 634.85 | 335.76 | 0.00 | -15.55 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 10-NOV-14:55 | 0.00 | -2161.09 | 0.00 | 0.00 | 42.49 | 28.81 | 382.60 | 1560.23 | 0.00 | 0.00 | 309.98 | 0.00 | 0.00 | 0.00 | -163.03 | 0.00 |
M S2 APARTMENT | 10-NOV-14:55 | 0.00 | -2158.17 | 0.00 | 0.00 | 42.50 | 28.81 | 382.60 | 1560.23 | 0.00 | 0.00 | 307.07 | 0.00 | 0.00 | 0.00 | -163.03 | 0.00 |
F6 SW APARTMENT | 22-OCT-14:45 | 0.00 | -3123.68 | 0.00 | 0.00 | 40.69 | 50.41 | 400.26 | 3357.29 | 0.00 | 189.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.49 |
F6 NW APARTMENT | 19-MAY-17:30 | 0.00 | -2915.32 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2180.35 | 0.00 | 327.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -517.10 |
F6 SE APARTMENT | 01-OCT-10:30 | 0.00 | -2723.17 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3429.85 | 0.00 | 96.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1285.26 |
F6 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2354.45 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1806.18 | 0.00 | 437.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -364.58 |
F6 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1857.13 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 668.88 | 306.12 | 0.00 | -14.01 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1848.37 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 668.10 | 298.00 | 0.00 | -13.87 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 10-NOV-14:55 | 0.00 | -2167.15 | 0.00 | 0.00 | 42.96 | 28.81 | 382.60 | 1549.04 | 0.00 | 0.00 | 338.71 | 0.00 | 0.00 | 0.00 | -174.96 | 0.00 |
F6 S2 APARTMENT | 10-NOV-14:55 | 0.00 | -2171.34 | 0.00 | 0.00 | 42.96 | 28.81 | 382.60 | 1549.04 | 0.00 | 0.00 | 342.84 | 0.00 | 0.00 | 0.00 | -174.91 | 0.00 |
F7 SW APARTMENT | 22-OCT-14:45 | 0.00 | -3109.71 | 0.00 | 0.00 | 40.71 | 50.41 | 400.26 | 3349.09 | 0.00 | 190.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -921.33 |
F7 NW APARTMENT | 19-MAY-17:30 | 0.00 | -2908.14 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2165.23 | 0.00 | 345.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.98 |
F7 SE APARTMENT | 01-OCT-10:30 | 0.00 | -2717.11 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3429.50 | 0.00 | 95.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1289.62 |
F7 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2344.21 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1794.64 | 0.00 | 452.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.99 |
F7 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1850.20 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 692.50 | 274.67 | 0.00 | -13.11 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1841.54 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 691.68 | 266.69 | 0.00 | -12.98 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2045.33 | 0.00 | 0.00 | 40.39 | 50.41 | 400.26 | 2323.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -115.06 | -654.06 |
F7 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2049.25 | 0.00 | 0.00 | 40.41 | 50.41 | 400.26 | 2323.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -114.19 | -651.17 |
F8 SW APARTMENT | 22-OCT-14:45 | 0.00 | -3110.74 | 0.00 | 0.00 | 40.73 | 50.41 | 400.26 | 3341.55 | 0.00 | 192.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.53 |
F8 NW APARTMENT | 19-MAY-17:20 | 0.00 | -2912.10 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2151.80 | 0.00 | 360.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.54 |
F8 SE APARTMENT | 01-OCT-10:30 | 0.00 | -2724.21 | 0.00 | 0.00 | 40.75 | 28.81 | 412.03 | 3429.01 | 0.00 | 94.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1281.02 |
F8 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2348.22 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1784.11 | 0.00 | 466.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.13 |
F8 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1857.86 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 713.42 | 260.99 | 0.00 | -12.70 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1849.31 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 712.57 | 253.16 | 0.00 | -12.56 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2049.25 | 0.00 | 0.00 | 40.52 | 50.41 | 400.26 | 2321.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -113.20 | -649.79 |
F8 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2053.13 | 0.00 | 0.00 | 40.54 | 50.41 | 400.26 | 2321.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -112.30 | -647.00 |
F9 SW APARTMENT | 22-OCT-15:15 | 0.00 | -3207.14 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3170.15 | 0.00 | 215.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -799.26 |
F9 NW APARTMENT | 27-JUN-17:20 | 0.00 | -2990.43 | 0.00 | 0.00 | 141.12 | 194.45 | 588.62 | 2603.61 | 0.00 | 116.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -654.36 |
F9 SE APARTMENT | 29-SEP-12:00 | 0.00 | -2771.38 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 2406.74 | 0.00 | 423.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -534.14 |
F9 NE APARTMENT | 10-JUN-09:15 | 0.00 | -2442.32 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 1773.55 | 0.00 | 488.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -295.17 |
F9 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1943.95 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 739.19 | 322.46 | 0.00 | -13.85 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1935.44 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 0.00 | 0.00 | 738.39 | 314.61 | 0.00 | -13.70 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 03-NOV-14:45 | 0.00 | -2108.08 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2195.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -85.71 | -493.07 |
F9 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2105.41 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2319.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -105.30 | -600.48 |
T SW APARTMENT | 22-OCT-15:15 | 0.00 | -3865.65 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3123.78 | 0.00 | 218.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97.69 |
T NW APARTMENT | 27-JUN-17:10 | 0.00 | -3652.98 | 0.00 | 0.00 | 141.67 | 194.45 | 588.62 | 2583.69 | 0.00 | 111.55 | 33.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 01-OCT-11:15 | 0.00 | -3423.44 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3115.81 | 0.00 | 11.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -180.00 |
T NE APARTMENT | 05-JUN-17:00 | 0.00 | -2954.65 | 0.00 | 0.00 | 84.01 | 144.04 | 588.62 | 1151.68 | 0.00 | 536.82 | 449.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 17-JUN-18:15 | 0.00 | -2344.00 | 0.00 | 0.00 | 140.07 | 230.46 | 547.42 | 676.55 | 0.00 | 175.16 | 574.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 17-JUN-18:15 | 0.00 | -2338.76 | 0.00 | 0.00 | 140.45 | 230.46 | 547.42 | 677.95 | 0.00 | 175.86 | 566.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 22-OCT-13:15 | 0.00 | -2796.05 | 0.00 | 0.00 | 40.35 | 28.81 | 382.60 | 2454.46 | 0.00 | 58.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -169.12 |
T S2 APARTMENT | 22-OCT-13:15 | 0.00 | -2799.85 | 0.00 | 0.00 | 40.34 | 28.81 | 382.60 | 2454.27 | 0.00 | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164.87 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUN-17:00 | 0.00 | -174527.88 | 0.00 | 0.00 | 6633.61 | 18221.75 | 47207.76 | 99464.77 | 0.00 | 31984.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28984.15 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-APR-14:00 | 1205.99 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1396.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2047.57 | -1006.89 |
G NW APARTMENT | 06-APR-14:00 | 1922.19 | 0.00 | 0.00 | 0.00 | 42.27 | 28.81 | 382.60 | 947.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2023.86 | -1299.63 |
OFFICE | 27-DEC-07:25 | 764.45 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1055.51 | 0.00 | -125.94 | -157.56 |
G NE APARTMENT | 06-APR-14:00 | 1758.01 | 0.00 | 0.00 | 0.00 | 42.49 | 28.81 | 382.60 | 418.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2021.05 | -608.94 |
G N1 APARTMENT | 06-APR-14:00 | 1740.87 | 0.00 | 0.00 | 0.00 | 43.05 | 28.81 | 382.60 | 264.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.45 | -529.40 |
G N2 APARTMENT | 06-APR-14:00 | 1745.72 | 0.00 | 0.00 | 0.00 | 43.00 | 28.81 | 382.60 | 263.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.46 | -533.64 |
G S1 APARTMENT | 06-APR-14:00 | 1976.52 | 0.00 | 0.00 | 0.00 | 41.27 | 28.81 | 382.60 | 721.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1933.13 | -1217.90 |
G S2 APARTMENT | 06-APR-14:00 | 1655.22 | 0.00 | 0.00 | 0.00 | 40.96 | 28.81 | 382.60 | 718.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1940.00 | -886.24 |
F2 SW APARTMENT | 27-DEC-06:00 | 513.21 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 215.69 | 0.00 | -1072.21 | 0.00 | -193.09 | 0.00 |
F2 NW APARTMENT | 06-APR-14:00 | 1573.49 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 802.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2786.70 | -41.82 |
F2 SE APARTMENT | 27-DEC-06:00 | 480.81 | 0.00 | 0.00 | 0.00 | 189.67 | 93.62 | 253.11 | 0.00 | 0.00 | 0.00 | 246.92 | 0.00 | -1071.03 | 0.00 | -193.09 | 0.00 |
F2 NE APARTMENT | 11-MAR-16:00 | 1685.32 | 0.00 | 0.00 | 0.00 | 41.82 | 50.41 | 400.26 | 71.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1843.63 | -406.02 |
F2 N1 APARTMENT | 06-APR-14:00 | 2118.72 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 201.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2643.51 | -128.43 |
F2 N2 APARTMENT | 06-APR-14:00 | 2088.08 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 200.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2643.47 | -97.36 |
F2 S1 APARTMENT | 06-APR-14:00 | 1013.45 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 615.45 | 0.00 | 0.00 | 575.51 | 0.00 | 0.00 | 0.00 | -2656.57 | 0.00 |
F2 S2 APARTMENT | 06-APR-14:00 | 927.55 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 614.87 | 0.00 | 0.00 | 663.36 | 0.00 | 0.00 | 0.00 | -2657.94 | 0.00 |
F3 SW APARTMENT | 06-APR-14:00 | 1107.38 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 1140.35 | 0.00 | 0.00 | 564.57 | 0.00 | 0.00 | 0.00 | -3264.46 | 0.00 |
F3 NW APARTMENT | 06-APR-14:00 | 1955.90 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 753.00 | 0.00 | 0.00 | 87.56 | 0.00 | 0.00 | 0.00 | -3248.62 | 0.00 |
F3 SE APARTMENT | 06-APR-14:00 | 1007.14 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 680.65 | 0.00 | 0.00 | 1120.73 | 0.00 | 0.00 | 0.00 | -3260.68 | 0.00 |
F3 NE APARTMENT | 06-APR-14:00 | 1861.63 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 293.05 | 0.00 | 0.00 | 638.48 | 0.00 | 0.00 | 0.00 | -3245.31 | 0.00 |
F3 N1 APARTMENT | 06-APR-14:00 | 2050.87 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 182.74 | 0.00 | 0.00 | 405.38 | 0.00 | 0.00 | 0.00 | -3091.15 | 0.00 |
F3 N2 APARTMENT | 06-APR-14:00 | 2034.82 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 182.35 | 0.00 | 0.00 | 421.79 | 0.00 | 0.00 | 0.00 | -3091.12 | 0.00 |
F3 S1 APARTMENT | 06-APR-14:00 | 1585.15 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 575.89 | 0.00 | 0.00 | 480.83 | 0.00 | 0.00 | 0.00 | -3094.03 | 0.00 |
F3 S2 APARTMENT | 06-APR-14:00 | 1540.51 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 575.55 | 0.00 | 0.00 | 526.49 | 0.00 | 0.00 | 0.00 | -3094.71 | 0.00 |
F4 SW APARTMENT | 06-APR-14:15 | 1071.98 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1166.16 | 0.00 | 0.00 | 577.47 | 0.00 | 0.00 | 0.00 | -3307.03 | 0.00 |
F4 NW APARTMENT | 06-APR-14:15 | 1922.18 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 807.96 | 0.00 | 0.00 | 68.97 | 0.00 | 0.00 | 0.00 | -3290.54 | 0.00 |
F4 SE APARTMENT | 06-APR-14:15 | 1114.95 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 614.77 | 0.00 | 0.00 | 1079.32 | 0.00 | 0.00 | 0.00 | -3300.46 | 0.00 |
F4 NE APARTMENT | 06-APR-14:15 | 1868.80 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 256.05 | 0.00 | 0.00 | 670.90 | 0.00 | 0.00 | 0.00 | -3287.17 | 0.00 |
F4 N1 APARTMENT | 06-APR-14:15 | 2036.40 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 159.78 | 0.00 | 0.00 | 443.01 | 0.00 | 0.00 | 0.00 | -3130.61 | 0.00 |
F4 N2 APARTMENT | 06-APR-14:15 | 2021.49 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 159.41 | 0.00 | 0.00 | 458.26 | 0.00 | 0.00 | 0.00 | -3130.58 | 0.00 |
F4 S1 APARTMENT | 06-APR-14:15 | 1608.95 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 523.66 | 0.00 | 0.00 | 509.10 | 0.00 | 0.00 | 0.00 | -3133.14 | 0.00 |
F4 S2 APARTMENT | 06-APR-14:15 | 1571.85 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 523.36 | 0.00 | 0.00 | 547.06 | 0.00 | 0.00 | 0.00 | -3133.69 | 0.00 |
M SW APARTMENT | 06-APR-14:15 | 1670.40 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1134.14 | 0.00 | 0.00 | 275.13 | 0.00 | 0.00 | 0.00 | -3571.09 | 0.00 |
M NW APARTMENT | 06-APR-14:15 | 2073.30 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 785.93 | 0.00 | 0.00 | 216.87 | 0.00 | 0.00 | 0.00 | -3567.52 | 0.00 |
M SE APARTMENT | 06-APR-14:15 | 1701.96 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 593.95 | 0.00 | 0.00 | 778.85 | 0.00 | 0.00 | 0.00 | -3566.18 | 0.00 |
M NE APARTMENT | 06-APR-14:15 | 2005.87 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 244.92 | 0.00 | 0.00 | 822.07 | 0.00 | 0.00 | 0.00 | -3564.28 | 0.00 |
M N1 APARTMENT | 06-APR-14:15 | 2148.10 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 152.83 | 0.00 | 0.00 | 601.63 | 0.00 | 0.00 | 0.00 | -3393.97 | 0.00 |
M N2 APARTMENT | 06-APR-14:15 | 2133.05 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 152.45 | 0.00 | 0.00 | 617.02 | 0.00 | 0.00 | 0.00 | -3393.95 | 0.00 |
M S1 APARTMENT | 06-APR-14:15 | 1849.80 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 507.06 | 0.00 | 0.00 | 545.88 | 0.00 | 0.00 | 0.00 | -3394.16 | 0.00 |
M S2 APARTMENT | 06-APR-14:15 | 1838.83 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 506.76 | 0.00 | 0.00 | 557.18 | 0.00 | 0.00 | 0.00 | -3394.19 | 0.00 |
F6 SW APARTMENT | 06-APR-14:15 | 1983.96 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1112.34 | 0.00 | 0.00 | 222.33 | 0.00 | 0.00 | 0.00 | -3810.05 | 0.00 |
F6 NW APARTMENT | 06-APR-14:15 | 2246.74 | 0.00 | 0.00 | 0.00 | 40.93 | 50.41 | 400.26 | 773.44 | 0.00 | 0.00 | 297.31 | 0.00 | 0.00 | 0.00 | -3809.10 | 0.00 |
F6 SE APARTMENT | 06-APR-14:15 | 1931.23 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 580.46 | 0.00 | 0.00 | 804.37 | 0.00 | 0.00 | 0.00 | -3807.48 | 0.00 |
F6 NE APARTMENT | 06-APR-14:15 | 2169.24 | 0.00 | 0.00 | 0.00 | 40.86 | 50.41 | 400.26 | 239.73 | 0.00 | 0.00 | 905.77 | 0.00 | 0.00 | 0.00 | -3806.28 | 0.00 |
F6 N1 APARTMENT | 06-APR-14:15 | 2336.46 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 149.31 | 0.00 | 0.00 | 647.05 | 0.00 | 0.00 | 0.00 | -3624.24 | 0.00 |
F6 N2 APARTMENT | 06-APR-14:15 | 2319.14 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 148.89 | 0.00 | 0.00 | 664.77 | 0.00 | 0.00 | 0.00 | -3624.22 | 0.00 |
F6 S1 APARTMENT | 06-APR-14:15 | 2032.44 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 496.02 | 0.00 | 0.00 | 604.57 | 0.00 | 0.00 | 0.00 | -3624.45 | 0.00 |
F6 S2 APARTMENT | 06-APR-14:15 | 2020.61 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 495.69 | 0.00 | 0.00 | 616.75 | 0.00 | 0.00 | 0.00 | -3624.47 | 0.00 |
F7 SW APARTMENT | 06-APR-14:15 | 2161.33 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1093.92 | 0.00 | 0.00 | 281.00 | 0.00 | 0.00 | 0.00 | -4027.67 | 0.00 |
F7 NW APARTMENT | 06-APR-14:15 | 2328.31 | 0.00 | 0.00 | 0.00 | 41.24 | 50.41 | 400.26 | 763.25 | 0.00 | 0.00 | 442.66 | 0.00 | 0.00 | 0.00 | -4026.14 | 0.00 |
F7 SE APARTMENT | 06-APR-14:15 | 2094.36 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 568.76 | 0.00 | 0.00 | 870.71 | 0.00 | 0.00 | 0.00 | -4025.26 | 0.00 |
F7 NE APARTMENT | 06-APR-14:15 | 2249.94 | 0.00 | 0.00 | 0.00 | 41.16 | 50.41 | 400.26 | 236.31 | 0.00 | 0.00 | 1045.61 | 0.00 | 0.00 | 0.00 | -4023.69 | 0.00 |
F7 N1 APARTMENT | 06-APR-14:10 | 2471.11 | 0.00 | 0.00 | 0.00 | 40.92 | 50.41 | 400.26 | 146.54 | 0.00 | 0.00 | 772.27 | 0.00 | 0.00 | 0.00 | -3881.51 | 0.00 |
F7 N2 APARTMENT | 06-APR-14:10 | 2440.11 | 0.00 | 0.00 | 0.00 | 40.87 | 50.41 | 400.26 | 145.92 | 0.00 | 0.00 | 804.53 | 0.00 | 0.00 | 0.00 | -3882.11 | 0.00 |
F7 S1 APARTMENT | 06-APR-14:15 | 2180.02 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 486.60 | 0.00 | 0.00 | 673.52 | 0.00 | 0.00 | 0.00 | -3831.56 | 0.00 |
F7 S2 APARTMENT | 06-APR-14:15 | 2167.42 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 486.25 | 0.00 | 0.00 | 686.50 | 0.00 | 0.00 | 0.00 | -3831.59 | 0.00 |
F8 SW APARTMENT | 06-APR-14:15 | 2317.93 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 1078.24 | 0.00 | 0.00 | 339.34 | 0.00 | 0.00 | 0.00 | -4226.93 | 0.00 |
F8 NW APARTMENT | 06-APR-14:10 | 2669.77 | 0.00 | 0.00 | 0.00 | 41.48 | 50.41 | 400.26 | 754.28 | 0.00 | 0.00 | 372.80 | 0.00 | 0.00 | 0.00 | -4289.00 | 0.00 |
F8 SE APARTMENT | 06-APR-14:15 | 2240.19 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 558.73 | 0.00 | 0.00 | 934.31 | 0.00 | 0.00 | 0.00 | -4224.65 | 0.00 |
F8 NE APARTMENT | 06-APR-14:10 | 2590.44 | 0.00 | 0.00 | 0.00 | 41.40 | 50.41 | 400.26 | 233.04 | 0.00 | 0.00 | 961.94 | 0.00 | 0.00 | 0.00 | -4277.49 | 0.00 |
F8 N1 APARTMENT | 06-APR-14:10 | 2872.51 | 0.00 | 0.00 | 0.00 | 41.10 | 50.41 | 400.26 | 144.33 | 0.00 | 0.00 | 557.10 | 0.00 | 0.00 | 0.00 | -4065.71 | 0.00 |
F8 N2 APARTMENT | 06-APR-14:10 | 2841.92 | 0.00 | 0.00 | 0.00 | 41.05 | 50.41 | 400.26 | 143.72 | 0.00 | 0.00 | 588.97 | 0.00 | 0.00 | 0.00 | -4066.34 | 0.00 |
F8 S1 APARTMENT | 06-APR-14:15 | 2309.72 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 478.53 | 0.00 | 0.00 | 741.54 | 0.00 | 0.00 | 0.00 | -4021.21 | 0.00 |
F8 S2 APARTMENT | 06-APR-14:15 | 2296.67 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 478.17 | 0.00 | 0.00 | 754.98 | 0.00 | 0.00 | 0.00 | -4021.24 | 0.00 |
F9 SW APARTMENT | 06-APR-14:10 | 2513.58 | 0.00 | 0.00 | 0.00 | 40.80 | 50.41 | 400.26 | 1066.62 | 0.00 | 0.00 | 420.30 | 0.00 | 0.00 | 0.00 | -4491.97 | 0.00 |
F9 NW APARTMENT | 06-APR-14:10 | 3104.68 | 0.00 | 0.00 | 0.00 | 41.74 | 50.41 | 400.26 | 748.37 | 0.00 | 0.00 | 120.85 | 0.00 | 0.00 | 0.00 | -4466.31 | 0.00 |
F9 SE APARTMENT | 06-APR-14:15 | 2392.15 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 550.86 | 0.00 | 0.00 | 975.47 | 0.00 | 0.00 | 0.00 | -4409.90 | 0.00 |
F9 NE APARTMENT | 06-APR-14:10 | 3015.84 | 0.00 | 0.00 | 0.00 | 41.64 | 50.41 | 400.26 | 231.30 | 0.00 | 0.00 | 716.90 | 0.00 | 0.00 | 0.00 | -4456.35 | 0.00 |
F9 N1 APARTMENT | 06-APR-14:10 | 3291.22 | 0.00 | 0.00 | 0.00 | 41.30 | 50.41 | 400.26 | 143.24 | 0.00 | 0.00 | 310.90 | 0.00 | 0.00 | 0.00 | -4237.34 | 0.00 |
F9 N2 APARTMENT | 06-APR-14:10 | 3257.54 | 0.00 | 0.00 | 0.00 | 41.25 | 50.41 | 400.26 | 142.55 | 0.00 | 0.00 | 346.09 | 0.00 | 0.00 | 0.00 | -4238.11 | 0.00 |
F9 S1 APARTMENT | 06-APR-14:10 | 2610.00 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 472.19 | 0.00 | 0.00 | 675.73 | 0.00 | 0.00 | 0.00 | -4249.34 | 0.00 |
F9 S2 APARTMENT | 06-APR-14:10 | 2569.04 | 0.00 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 471.76 | 0.00 | 0.00 | 717.56 | 0.00 | 0.00 | 0.00 | -4249.78 | 0.00 |
T SW APARTMENT | 10-APR-16:53 | 3115.86 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 141.76 | 0.00 | 0.00 | 937.15 | 0.00 | 0.00 | 0.00 | -5026.05 | 0.00 |
T NW APARTMENT | 10-APR-16:53 | 3225.35 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 143.26 | 0.00 | 0.00 | 826.16 | 0.00 | 0.00 | 0.00 | -5026.05 | 0.00 |
T SE APARTMENT | 10-APR-16:53 | 3217.20 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 1111.28 | 0.00 | -133.71 | 0.00 | -5026.05 | 0.00 |
T NE APARTMENT | 10-APR-16:53 | 3321.20 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 1005.93 | 0.00 | -132.37 | 0.00 | -5026.05 | 0.00 |
T N1 APARTMENT | 06-APR-14:25 | 3287.48 | 0.00 | 0.00 | 0.00 | 41.38 | 50.41 | 400.26 | 130.30 | 0.00 | 0.00 | 79.96 | 0.00 | 0.00 | 0.00 | -3989.79 | 0.00 |
T N2 APARTMENT | 06-APR-14:25 | 3260.59 | 0.00 | 0.00 | 0.00 | 41.32 | 50.41 | 400.26 | 129.63 | 0.00 | 0.00 | 108.51 | 0.00 | 0.00 | 0.00 | -3990.72 | 0.00 |
T S1 APARTMENT | 10-APR-16:53 | 3022.98 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 1009.28 | 0.00 | -85.23 | 0.00 | -4778.33 | 0.00 |
T S2 APARTMENT | 10-APR-16:53 | 3025.09 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 0.00 | 0.00 | 0.00 | 1007.12 | 0.00 | -85.17 | 0.00 | -4778.33 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-APR-17:00 | 114007.80 | 0.00 | 0.00 | 0.00 | 7777.73 | 18221.75 | 47207.76 | 3407.31 | 0.00 | 0.00 | 118705.12 | 0.00 | -6147.23 | 0.00 | -303180.23 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Sec1.1A-General InformationData | |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 40.50 |
Number of hours cooling loads not met | 294.75 |
Number of hours not met | 335.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.57 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 14.85 | 0.00 | 19.80 | 59159.29 | 0.00 | 0.00 |
Space Cooling | 659.36 | 61623.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.21 | 1422.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.64 | 2273.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 640.88 | 20322.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 995.45 | 82933.34 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3120.83 | 1015.24 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3120.83 |
Natural Gas | 0.00 | 1015.24 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4136.08 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 1.90 |
Space Cooling | 84.14 |
Fans-Interior | 81.78 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 32.95 |
Subtotal | 398.24 |
Natural Gas [MJ/m2] | |
Space Heating | 2.53 |
Service Water Heating | 127.03 |
Miscellaneous | 0.00 |
Subtotal | 129.55 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 10.07 |
Space Heating | 0.84 |
Space Cooling | 15.94 |
Fans-Interior | 15.49 |
Service Water Heating | 24.07 |
Receptacle Equipment | 27.35 |
Miscellaneous | 6.24 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.237061 |
G NW APARTMENT DIRECT AIR | 0.235517 |
OFFICE DIRECT AIR | 0.310027 |
G NE APARTMENT DIRECT AIR | 0.182169 |
G N1 APARTMENT DIRECT AIR | 0.135193 |
G N2 APARTMENT DIRECT AIR | 0.133984 |
G S1 APARTMENT DIRECT AIR | 0.133128 |
G S2 APARTMENT DIRECT AIR | 0.138266 |
F2 SW APARTMENT DIRECT AIR | 0.294151 |
F2 NW APARTMENT DIRECT AIR | 0.291180 |
F2 SE APARTMENT DIRECT AIR | 0.263666 |
F2 NE APARTMENT DIRECT AIR | 0.230733 |
F2 N1 APARTMENT DIRECT AIR | 0.171694 |
F2 N2 APARTMENT DIRECT AIR | 0.170715 |
F2 S1 APARTMENT DIRECT AIR | 0.171193 |
F2 S2 APARTMENT DIRECT AIR | 0.172891 |
F3 SW APARTMENT DIRECT AIR | 0.294810 |
F3 NW APARTMENT DIRECT AIR | 0.292316 |
F3 SE APARTMENT DIRECT AIR | 0.248316 |
F3 NE APARTMENT DIRECT AIR | 0.233427 |
F3 N1 APARTMENT DIRECT AIR | 0.174390 |
F3 N2 APARTMENT DIRECT AIR | 0.173428 |
F3 S1 APARTMENT DIRECT AIR | 0.173901 |
F3 S2 APARTMENT DIRECT AIR | 0.174602 |
F4 SW APARTMENT DIRECT AIR | 0.295938 |
F4 NW APARTMENT DIRECT AIR | 0.293476 |
F4 SE APARTMENT DIRECT AIR | 0.248453 |
F4 NE APARTMENT DIRECT AIR | 0.234810 |
F4 N1 APARTMENT DIRECT AIR | 0.176129 |
F4 N2 APARTMENT DIRECT AIR | 0.175178 |
F4 S1 APARTMENT DIRECT AIR | 0.175499 |
F4 S2 APARTMENT DIRECT AIR | 0.176025 |
M SW APARTMENT DIRECT AIR | 0.299542 |
M NW APARTMENT DIRECT AIR | 0.297189 |
M SE APARTMENT DIRECT AIR | 0.252418 |
M NE APARTMENT DIRECT AIR | 0.238645 |
M N1 APARTMENT DIRECT AIR | 0.180149 |
M N2 APARTMENT DIRECT AIR | 0.179208 |
M S1 APARTMENT DIRECT AIR | 0.179323 |
M S2 APARTMENT DIRECT AIR | 0.179806 |
F6 SW APARTMENT DIRECT AIR | 0.295986 |
F6 NW APARTMENT DIRECT AIR | 0.293544 |
F6 SE APARTMENT DIRECT AIR | 0.249439 |
F6 NE APARTMENT DIRECT AIR | 0.235224 |
F6 N1 APARTMENT DIRECT AIR | 0.177036 |
F6 N2 APARTMENT DIRECT AIR | 0.176107 |
F6 S1 APARTMENT DIRECT AIR | 0.176182 |
F6 S2 APARTMENT DIRECT AIR | 0.176659 |
F7 SW APARTMENT DIRECT AIR | 0.295025 |
F7 NW APARTMENT DIRECT AIR | 0.292612 |
F7 SE APARTMENT DIRECT AIR | 0.248964 |
F7 NE APARTMENT DIRECT AIR | 0.234454 |
F7 N1 APARTMENT DIRECT AIR | 0.176466 |
F7 N2 APARTMENT DIRECT AIR | 0.175548 |
F7 S1 APARTMENT DIRECT AIR | 0.175504 |
F7 S2 APARTMENT DIRECT AIR | 0.175980 |
F8 SW APARTMENT DIRECT AIR | 0.295647 |
F8 NW APARTMENT DIRECT AIR | 0.293252 |
F8 SE APARTMENT DIRECT AIR | 0.249951 |
F8 NE APARTMENT DIRECT AIR | 0.235159 |
F8 N1 APARTMENT DIRECT AIR | 0.177408 |
F8 N2 APARTMENT DIRECT AIR | 0.176500 |
F8 S1 APARTMENT DIRECT AIR | 0.176299 |
F8 S2 APARTMENT DIRECT AIR | 0.176776 |
F9 SW APARTMENT DIRECT AIR | 0.305776 |
F9 NW APARTMENT DIRECT AIR | 0.303429 |
F9 SE APARTMENT DIRECT AIR | 0.258257 |
F9 NE APARTMENT DIRECT AIR | 0.243457 |
F9 N1 APARTMENT DIRECT AIR | 0.186676 |
F9 N2 APARTMENT DIRECT AIR | 0.185772 |
F9 S1 APARTMENT DIRECT AIR | 0.183377 |
F9 S2 APARTMENT DIRECT AIR | 0.183819 |
T SW APARTMENT DIRECT AIR | 0.374762 |
T NW APARTMENT DIRECT AIR | 0.367726 |
T SE APARTMENT DIRECT AIR | 0.324688 |
T NE APARTMENT DIRECT AIR | 0.300205 |
T N1 APARTMENT DIRECT AIR | 0.231458 |
T N2 APARTMENT DIRECT AIR | 0.230771 |
T S1 APARTMENT DIRECT AIR | 0.254066 |
T S2 APARTMENT DIRECT AIR | 0.254454 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.237061 |
AIRLOOP G NW MAIN BRANCH | 0.235517 |
AIRLOOP OFFICE MAIN BRANCH | 0.310027 |
AIRLOOP G NE MAIN BRANCH | 0.182169 |
AIRLOOP G N1 MAIN BRANCH | 0.135193 |
AIRLOOP G N2 MAIN BRANCH | 0.133984 |
AIRLOOP G S1 MAIN BRANCH | 0.133128 |
AIRLOOP G S2 MAIN BRANCH | 0.138266 |
AIRLOOP F2 SW MAIN BRANCH | 0.294151 |
AIRLOOP F2 NW MAIN BRANCH | 0.291180 |
AIRLOOP F2 SE MAIN BRANCH | 0.263666 |
AIRLOOP F2 NE MAIN BRANCH | 0.230733 |
AIRLOOP F2 N1 MAIN BRANCH | 0.171694 |
AIRLOOP F2 N2 MAIN BRANCH | 0.170715 |
AIRLOOP F2 S1 MAIN BRANCH | 0.171193 |
AIRLOOP F2 S2 MAIN BRANCH | 0.172891 |
AIRLOOP F3 SW MAIN BRANCH | 0.294810 |
AIRLOOP F3 NW MAIN BRANCH | 0.292316 |
AIRLOOP F3 SE MAIN BRANCH | 0.248316 |
AIRLOOP F3 NE MAIN BRANCH | 0.233427 |
AIRLOOP F3 N1 MAIN BRANCH | 0.174390 |
AIRLOOP F3 N2 MAIN BRANCH | 0.173428 |
AIRLOOP F3 S1 MAIN BRANCH | 0.173901 |
AIRLOOP F3 S2 MAIN BRANCH | 0.174602 |
AIRLOOP F4 SW MAIN BRANCH | 0.295938 |
AIRLOOP F4 NW MAIN BRANCH | 0.293476 |
AIRLOOP F4 SE MAIN BRANCH | 0.248453 |
AIRLOOP F4 NE MAIN BRANCH | 0.234810 |
AIRLOOP F4 N1 MAIN BRANCH | 0.176129 |
AIRLOOP F4 N2 MAIN BRANCH | 0.175178 |
AIRLOOP F4 S1 MAIN BRANCH | 0.175499 |
AIRLOOP F4 S2 MAIN BRANCH | 0.176025 |
AIRLOOP M SW MAIN BRANCH | 0.299542 |
AIRLOOP M NW MAIN BRANCH | 0.297189 |
AIRLOOP M SE MAIN BRANCH | 0.252418 |
AIRLOOP M NE MAIN BRANCH | 0.238645 |
AIRLOOP M N1 MAIN BRANCH | 0.180149 |
AIRLOOP M N2 MAIN BRANCH | 0.179208 |
AIRLOOP M S1 MAIN BRANCH | 0.179323 |
AIRLOOP M S2 MAIN BRANCH | 0.179806 |
AIRLOOP F6 SW MAIN BRANCH | 0.295986 |
AIRLOOP F6 NW MAIN BRANCH | 0.293544 |
AIRLOOP F6 SE MAIN BRANCH | 0.249439 |
AIRLOOP F6 NE MAIN BRANCH | 0.235224 |
AIRLOOP F6 N1 MAIN BRANCH | 0.177036 |
AIRLOOP F6 N2 MAIN BRANCH | 0.176107 |
AIRLOOP F6 S1 MAIN BRANCH | 0.176182 |
AIRLOOP F6 S2 MAIN BRANCH | 0.176659 |
AIRLOOP F7 SW MAIN BRANCH | 0.295025 |
AIRLOOP F7 NW MAIN BRANCH | 0.292612 |
AIRLOOP F7 SE MAIN BRANCH | 0.248964 |
AIRLOOP F7 NE MAIN BRANCH | 0.234454 |
AIRLOOP F7 N1 MAIN BRANCH | 0.176466 |
AIRLOOP F7 N2 MAIN BRANCH | 0.175548 |
AIRLOOP F7 S1 MAIN BRANCH | 0.175504 |
AIRLOOP F7 S2 MAIN BRANCH | 0.175980 |
AIRLOOP F8 SW MAIN BRANCH | 0.295647 |
AIRLOOP F8 NW MAIN BRANCH | 0.293252 |
AIRLOOP F8 SE MAIN BRANCH | 0.249951 |
AIRLOOP F8 NE MAIN BRANCH | 0.235159 |
AIRLOOP F8 N1 MAIN BRANCH | 0.177408 |
AIRLOOP F8 N2 MAIN BRANCH | 0.176500 |
AIRLOOP F8 S1 MAIN BRANCH | 0.176299 |
AIRLOOP F8 S2 MAIN BRANCH | 0.176776 |
AIRLOOP F9 SW MAIN BRANCH | 0.305776 |
AIRLOOP F9 NW MAIN BRANCH | 0.303429 |
AIRLOOP F9 SE MAIN BRANCH | 0.258257 |
AIRLOOP F9 NE MAIN BRANCH | 0.243457 |
AIRLOOP F9 N1 MAIN BRANCH | 0.186676 |
AIRLOOP F9 N2 MAIN BRANCH | 0.185772 |
AIRLOOP F9 S1 MAIN BRANCH | 0.183377 |
AIRLOOP F9 S2 MAIN BRANCH | 0.183819 |
AIRLOOP T SW MAIN BRANCH | 0.374762 |
AIRLOOP T NW MAIN BRANCH | 0.367726 |
AIRLOOP T SE MAIN BRANCH | 0.324688 |
AIRLOOP T NE MAIN BRANCH | 0.300205 |
AIRLOOP T N1 MAIN BRANCH | 0.231458 |
AIRLOOP T N2 MAIN BRANCH | 0.230771 |
AIRLOOP T S1 MAIN BRANCH | 0.254066 |
AIRLOOP T S2 MAIN BRANCH | 0.254454 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.237061 |
AIRLOOP G NW | 0.235517 |
AIRLOOP OFFICE | 0.310027 |
AIRLOOP G NE | 0.182169 |
AIRLOOP G N1 | 0.135193 |
AIRLOOP G N2 | 0.133984 |
AIRLOOP G S1 | 0.133128 |
AIRLOOP G S2 | 0.138266 |
AIRLOOP F2 SW | 0.294151 |
AIRLOOP F2 NW | 0.291180 |
AIRLOOP F2 SE | 0.263666 |
AIRLOOP F2 NE | 0.230733 |
AIRLOOP F2 N1 | 0.171694 |
AIRLOOP F2 N2 | 0.170715 |
AIRLOOP F2 S1 | 0.171193 |
AIRLOOP F2 S2 | 0.172891 |
AIRLOOP F3 SW | 0.294810 |
AIRLOOP F3 NW | 0.292316 |
AIRLOOP F3 SE | 0.248316 |
AIRLOOP F3 NE | 0.233427 |
AIRLOOP F3 N1 | 0.174390 |
AIRLOOP F3 N2 | 0.173428 |
AIRLOOP F3 S1 | 0.173901 |
AIRLOOP F3 S2 | 0.174602 |
AIRLOOP F4 SW | 0.295938 |
AIRLOOP F4 NW | 0.293476 |
AIRLOOP F4 SE | 0.248453 |
AIRLOOP F4 NE | 0.234810 |
AIRLOOP F4 N1 | 0.176129 |
AIRLOOP F4 N2 | 0.175178 |
AIRLOOP F4 S1 | 0.175499 |
AIRLOOP F4 S2 | 0.176025 |
AIRLOOP M SW | 0.299542 |
AIRLOOP M NW | 0.297189 |
AIRLOOP M SE | 0.252418 |
AIRLOOP M NE | 0.238645 |
AIRLOOP M N1 | 0.180149 |
AIRLOOP M N2 | 0.179208 |
AIRLOOP M S1 | 0.179323 |
AIRLOOP M S2 | 0.179806 |
AIRLOOP F6 SW | 0.295986 |
AIRLOOP F6 NW | 0.293544 |
AIRLOOP F6 SE | 0.249439 |
AIRLOOP F6 NE | 0.235224 |
AIRLOOP F6 N1 | 0.177036 |
AIRLOOP F6 N2 | 0.176107 |
AIRLOOP F6 S1 | 0.176182 |
AIRLOOP F6 S2 | 0.176659 |
AIRLOOP F7 SW | 0.295025 |
AIRLOOP F7 NW | 0.292612 |
AIRLOOP F7 SE | 0.248964 |
AIRLOOP F7 NE | 0.234454 |
AIRLOOP F7 N1 | 0.176466 |
AIRLOOP F7 N2 | 0.175548 |
AIRLOOP F7 S1 | 0.175504 |
AIRLOOP F7 S2 | 0.175980 |
AIRLOOP F8 SW | 0.295647 |
AIRLOOP F8 NW | 0.293252 |
AIRLOOP F8 SE | 0.249951 |
AIRLOOP F8 NE | 0.235159 |
AIRLOOP F8 N1 | 0.177408 |
AIRLOOP F8 N2 | 0.176500 |
AIRLOOP F8 S1 | 0.176299 |
AIRLOOP F8 S2 | 0.176776 |
AIRLOOP F9 SW | 0.305776 |
AIRLOOP F9 NW | 0.303429 |
AIRLOOP F9 SE | 0.258257 |
AIRLOOP F9 NE | 0.243457 |
AIRLOOP F9 N1 | 0.186676 |
AIRLOOP F9 N2 | 0.185772 |
AIRLOOP F9 S1 | 0.183377 |
AIRLOOP F9 S2 | 0.183819 |
AIRLOOP T SW | 0.374762 |
AIRLOOP T NW | 0.367726 |
AIRLOOP T SE | 0.324688 |
AIRLOOP T NE | 0.300205 |
AIRLOOP T N1 | 0.231458 |
AIRLOOP T N2 | 0.230771 |
AIRLOOP T S1 | 0.254066 |
AIRLOOP T S2 | 0.254454 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.237061 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.235517 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.310027 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.182169 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.135193 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.133984 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.133128 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.138266 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.294151 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.291180 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.263666 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.230733 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.171694 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.170715 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.171193 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.172891 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.294810 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.292316 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.248316 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.233427 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.174390 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.173428 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.173901 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.174602 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.295938 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.293476 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.248453 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.234810 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.176129 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.175178 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.175499 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.176025 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.299542 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.297189 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.252418 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.238645 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.180149 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.179208 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.179323 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.179806 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.295986 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.293544 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.249439 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.235224 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.177036 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.176107 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.176182 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.176659 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.295025 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.292612 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.248964 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.234454 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.176466 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.175548 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.175504 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.175980 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.295647 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.293252 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.249951 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.235159 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.177408 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.176500 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.176299 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.176776 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.305776 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.303429 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.258257 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.243457 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.186676 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.185772 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.183377 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.183819 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.374762 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.367726 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.324688 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.300205 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.231458 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.230771 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.254066 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.254454 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.237061 | 3249.68 | 2140.77 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.235517 | 3218.01 | 2121.90 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.310027 | 4223.95 | 2796.49 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.182169 | 2488.28 | 1645.63 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.135193 | 1921.73 | 1251.37 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.133984 | 1906.25 | 1240.97 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.133128 | 1970.73 | 1265.14 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.138266 | 2036.19 | 1309.46 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.294151 | 3965.11 | 2626.31 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.291180 | 3915.59 | 2595.20 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.263666 | 3612.81 | 2380.92 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.230733 | 3107.16 | 2063.61 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.171694 | 2392.07 | 1567.90 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.170715 | 2379.58 | 1559.52 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.171193 | 2454.33 | 1593.36 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.172891 | 2471.69 | 1606.29 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.294810 | 3967.89 | 2630.85 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.292316 | 3924.39 | 2603.80 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.248316 | 3412.66 | 2248.73 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.233427 | 3135.87 | 2085.55 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.174390 | 2423.14 | 1590.36 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.173428 | 2410.87 | 1582.11 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.173901 | 2485.63 | 1616.00 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.174602 | 2490.29 | 1620.36 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.295938 | 3978.02 | 2639.66 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.293476 | 3934.90 | 2612.89 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.248453 | 3410.37 | 2249.12 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.234810 | 3149.32 | 2096.56 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.176129 | 2442.83 | 1604.77 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.175178 | 2430.72 | 1596.62 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.175499 | 2503.58 | 1629.25 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.176025 | 2506.01 | 1632.11 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.299542 | 4020.32 | 2669.74 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.297189 | 3978.56 | 2643.88 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.252418 | 3457.37 | 2282.36 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.238645 | 3194.58 | 2128.63 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.180149 | 2492.03 | 1638.79 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.179208 | 2480.05 | 1630.73 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.179323 | 2550.25 | 1661.69 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.179806 | 2552.12 | 1664.17 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.295986 | 3972.31 | 2638.86 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.293544 | 3929.39 | 2612.23 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.249439 | 3416.79 | 2256.37 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.235224 | 3148.43 | 2098.90 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.177036 | 2450.64 | 1611.80 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.176107 | 2438.82 | 1603.85 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.176182 | 2508.70 | 1634.42 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.176659 | 2514.76 | 1638.51 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.295025 | 3957.58 | 2630.17 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.292612 | 3914.99 | 2603.79 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.248964 | 3408.31 | 2251.83 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.234454 | 3136.20 | 2091.86 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.176466 | 2441.88 | 1606.63 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.175548 | 2430.19 | 1598.77 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.175504 | 2498.64 | 1628.32 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.175980 | 2504.70 | 1632.41 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.295647 | 3963.16 | 2635.03 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.293252 | 3920.80 | 2608.80 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.249951 | 3418.62 | 2259.84 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.235159 | 3142.91 | 2097.45 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.177408 | 2452.52 | 1614.43 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.176500 | 2440.97 | 1606.66 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.176299 | 2507.45 | 1634.89 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.176776 | 2513.52 | 1638.99 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.305776 | 4089.45 | 2720.99 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.303429 | 4047.73 | 2695.17 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.258257 | 3526.19 | 2332.14 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.243457 | 3278.03 | 2178.02 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.186676 | 2569.27 | 1693.50 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.185772 | 2557.77 | 1685.77 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.183377 | 2596.17 | 1695.38 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.183819 | 2601.78 | 1699.16 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.374762 | 4985.04 | 3319.03 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.367726 | 4878.09 | 3251.28 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.324688 | 4361.67 | 2896.86 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.300205 | 4055.89 | 2689.85 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.231458 | 3200.15 | 2104.73 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.230771 | 3196.55 | 2100.93 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.254066 | 3492.06 | 2300.04 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.254454 | 3496.99 | 2303.35 | 0.000076 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.237061 | 0.237061 | 0.237061 | 0.237061 | 3249.68 | 3249.68 | 2219.23 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.235517 | 0.235517 | 0.235517 | 0.235517 | 3218.01 | 3218.01 | 2216.91 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.310027 | 0.310027 | 0.310027 | 0.310027 | 4223.95 | 4223.95 | 2965.88 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.182169 | 0.182169 | 0.182169 | 0.182169 | 2488.28 | 2488.28 | 2213.47 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.135193 | 0.135193 | 0.135193 | 0.135193 | 1921.73 | 1921.73 | 1639.63 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.133984 | 0.133984 | 0.133984 | 0.133984 | 1906.25 | 1906.25 | 1639.54 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.133128 | 0.133128 | 0.133128 | 0.133128 | 1970.73 | 1970.73 | 1638.19 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.138266 | 0.138266 | 0.138266 | 0.138266 | 2036.19 | 2036.19 | 1646.61 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.294151 | 0.294151 | 0.294151 | 0.294151 | 3965.11 | 3965.11 | 2173.66 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.291180 | 0.291180 | 0.291180 | 0.291180 | 3915.59 | 3915.59 | 2168.64 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.263666 | 0.263666 | 0.263666 | 0.263666 | 3612.81 | 3612.81 | 2195.72 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.230733 | 0.230733 | 0.230733 | 0.230733 | 3107.16 | 3107.16 | 2165.11 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.171694 | 0.171694 | 0.171694 | 0.171694 | 2392.07 | 2392.07 | 1466.23 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.170715 | 0.170715 | 0.170715 | 0.170715 | 2379.58 | 2379.58 | 1466.14 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.171193 | 0.171193 | 0.171193 | 0.171193 | 2454.33 | 2454.33 | 1474.04 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.172891 | 0.172891 | 0.172891 | 0.172891 | 2471.69 | 2471.69 | 1475.67 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.294810 | 0.294810 | 0.294810 | 0.294810 | 3967.89 | 3967.89 | 2144.04 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.292316 | 0.292316 | 0.292316 | 0.292316 | 3924.39 | 3924.39 | 2140.67 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.248316 | 0.248316 | 0.248316 | 0.248316 | 3412.66 | 3412.66 | 2144.04 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.233427 | 0.233427 | 0.233427 | 0.233427 | 3135.87 | 3135.87 | 2137.76 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.174390 | 0.174390 | 0.174390 | 0.174390 | 2423.14 | 2423.14 | 1422.00 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.173428 | 0.173428 | 0.173428 | 0.173428 | 2410.87 | 2410.87 | 1421.92 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.173901 | 0.173901 | 0.173901 | 0.173901 | 2485.63 | 2485.63 | 1426.15 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.174602 | 0.174602 | 0.174602 | 0.174602 | 2490.29 | 2490.29 | 1426.35 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.295938 | 0.295938 | 0.295938 | 0.295938 | 3978.02 | 3978.02 | 2156.01 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.293476 | 0.293476 | 0.293476 | 0.293476 | 3934.90 | 3934.90 | 2154.01 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.248453 | 0.248453 | 0.248453 | 0.248453 | 3410.37 | 3410.37 | 2154.00 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.234810 | 0.234810 | 0.234810 | 0.234810 | 3149.32 | 3149.32 | 2151.69 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.176129 | 0.176129 | 0.176129 | 0.176129 | 2442.83 | 2442.83 | 1421.25 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.175178 | 0.175178 | 0.175178 | 0.175178 | 2430.72 | 2430.72 | 1421.18 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.175499 | 0.175499 | 0.175499 | 0.175499 | 2503.58 | 2503.58 | 1423.75 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.176025 | 0.176025 | 0.176025 | 0.176025 | 2506.01 | 2506.01 | 1423.73 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.299542 | 0.299542 | 0.299542 | 0.299542 | 4020.32 | 4020.32 | 2148.27 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.297189 | 0.297189 | 0.297189 | 0.297189 | 3978.56 | 3978.56 | 2146.10 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.252418 | 0.252418 | 0.252418 | 0.252418 | 3457.37 | 3457.37 | 2146.51 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.238645 | 0.238645 | 0.238645 | 0.238645 | 3194.58 | 3194.58 | 2144.31 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.180149 | 0.180149 | 0.180149 | 0.180149 | 2492.03 | 2492.03 | 1404.72 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.179208 | 0.179208 | 0.179208 | 0.179208 | 2480.05 | 2480.05 | 1404.67 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.179323 | 0.179323 | 0.179323 | 0.179323 | 2550.25 | 2550.25 | 1407.33 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.179806 | 0.179806 | 0.179806 | 0.179806 | 2552.12 | 2552.12 | 1407.29 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.295986 | 0.295986 | 0.295986 | 0.295986 | 3972.31 | 3972.31 | 2210.24 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.293544 | 0.293544 | 0.293544 | 0.293544 | 3929.39 | 3929.39 | 2209.79 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.249439 | 0.249439 | 0.249439 | 0.249439 | 3416.79 | 3416.79 | 2208.93 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.235224 | 0.235224 | 0.235224 | 0.235224 | 3148.43 | 3148.43 | 2208.48 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.177036 | 0.177036 | 0.177036 | 0.177036 | 2450.64 | 2450.64 | 1455.64 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.176107 | 0.176107 | 0.176107 | 0.176107 | 2438.82 | 2438.82 | 1455.61 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.176182 | 0.176182 | 0.176182 | 0.176182 | 2508.70 | 2508.70 | 1456.49 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.176659 | 0.176659 | 0.176659 | 0.176659 | 2514.76 | 2514.76 | 1456.46 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.295025 | 0.295025 | 0.295025 | 0.295025 | 3957.58 | 3957.58 | 2246.31 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.292612 | 0.292612 | 0.292612 | 0.292612 | 3914.99 | 3914.99 | 2246.30 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.248964 | 0.248964 | 0.248964 | 0.248964 | 3408.31 | 3408.31 | 2245.43 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.234454 | 0.234454 | 0.234454 | 0.234454 | 3136.20 | 3136.20 | 2245.42 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.176466 | 0.176466 | 0.176466 | 0.176466 | 2441.88 | 2441.88 | 1483.33 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.175548 | 0.175548 | 0.175548 | 0.175548 | 2430.19 | 2430.19 | 1483.31 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.175504 | 0.175504 | 0.175504 | 0.175504 | 2498.64 | 2498.64 | 1483.71 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.175980 | 0.175980 | 0.175980 | 0.175980 | 2504.70 | 2504.70 | 1483.69 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.295647 | 0.295647 | 0.295647 | 0.295647 | 3963.16 | 3963.16 | 2286.68 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.293252 | 0.293252 | 0.293252 | 0.293252 | 3920.80 | 3920.80 | 2286.84 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.249951 | 0.249951 | 0.249951 | 0.249951 | 3418.62 | 3418.62 | 2286.21 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.235159 | 0.235159 | 0.235159 | 0.235159 | 3142.91 | 3142.91 | 2286.37 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.177408 | 0.177408 | 0.177408 | 0.177408 | 2452.52 | 2452.52 | 1516.55 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.176500 | 0.176500 | 0.176500 | 0.176500 | 2440.97 | 2440.97 | 1516.54 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.176299 | 0.176299 | 0.176299 | 0.176299 | 2507.45 | 2507.45 | 1516.73 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.176776 | 0.176776 | 0.176776 | 0.176776 | 2513.52 | 2513.52 | 1516.72 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.305776 | 0.305776 | 0.305776 | 0.305776 | 4089.45 | 4089.45 | 2439.24 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.303429 | 0.303429 | 0.303429 | 0.303429 | 4047.73 | 4047.73 | 2437.35 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.258257 | 0.258257 | 0.258257 | 0.258257 | 3526.19 | 3526.19 | 2439.14 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.243457 | 0.243457 | 0.243457 | 0.243457 | 3278.03 | 3278.03 | 2437.25 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.186676 | 0.186676 | 0.186676 | 0.186676 | 2569.27 | 2569.27 | 1652.87 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.185772 | 0.185772 | 0.185772 | 0.185772 | 2557.77 | 2557.77 | 1652.86 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.183377 | 0.183377 | 0.183377 | 0.183377 | 2596.17 | 2596.17 | 1654.62 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.183819 | 0.183819 | 0.183819 | 0.183819 | 2601.78 | 2601.78 | 1654.62 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.374762 | 0.374762 | 0.374762 | 0.374762 | 4985.04 | 4985.04 | 2990.95 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.367726 | 0.367726 | 0.367726 | 0.367726 | 4878.09 | 4878.09 | 2995.76 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.324688 | 0.324688 | 0.324688 | 0.324688 | 4361.67 | 4361.67 | 2991.15 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.300205 | 0.300205 | 0.300205 | 0.300205 | 4055.89 | 4055.89 | 2995.96 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.231458 | 0.231458 | 0.231458 | 0.231458 | 3200.15 | 3200.15 | 2256.59 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.230771 | 0.230771 | 0.230771 | 0.230771 | 3196.55 | 3196.55 | 2256.60 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.254066 | 0.254066 | 0.254066 | 0.254066 | 3492.06 | 3492.06 | 2248.82 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.254454 | 0.254454 | 0.254454 | 0.254454 | 3496.99 | 3496.99 | 2248.82 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.237061 |
AIRLOOP G NW SUPPLY FAN | 0.235517 |
AIRLOOP OFFICE SUPPLY FAN | 0.310027 |
AIRLOOP G NE SUPPLY FAN | 0.182169 |
AIRLOOP G N1 SUPPLY FAN | 0.135193 |
AIRLOOP G N2 SUPPLY FAN | 0.133984 |
AIRLOOP G S1 SUPPLY FAN | 0.133128 |
AIRLOOP G S2 SUPPLY FAN | 0.138266 |
AIRLOOP F2 SW SUPPLY FAN | 0.294151 |
AIRLOOP F2 NW SUPPLY FAN | 0.291180 |
AIRLOOP F2 SE SUPPLY FAN | 0.263666 |
AIRLOOP F2 NE SUPPLY FAN | 0.230733 |
AIRLOOP F2 N1 SUPPLY FAN | 0.171694 |
AIRLOOP F2 N2 SUPPLY FAN | 0.170715 |
AIRLOOP F2 S1 SUPPLY FAN | 0.171193 |
AIRLOOP F2 S2 SUPPLY FAN | 0.172891 |
AIRLOOP F3 SW SUPPLY FAN | 0.294810 |
AIRLOOP F3 NW SUPPLY FAN | 0.292316 |
AIRLOOP F3 SE SUPPLY FAN | 0.248316 |
AIRLOOP F3 NE SUPPLY FAN | 0.233427 |
AIRLOOP F3 N1 SUPPLY FAN | 0.174390 |
AIRLOOP F3 N2 SUPPLY FAN | 0.173428 |
AIRLOOP F3 S1 SUPPLY FAN | 0.173901 |
AIRLOOP F3 S2 SUPPLY FAN | 0.174602 |
AIRLOOP F4 SW SUPPLY FAN | 0.295938 |
AIRLOOP F4 NW SUPPLY FAN | 0.293476 |
AIRLOOP F4 SE SUPPLY FAN | 0.248453 |
AIRLOOP F4 NE SUPPLY FAN | 0.234810 |
AIRLOOP F4 N1 SUPPLY FAN | 0.176129 |
AIRLOOP F4 N2 SUPPLY FAN | 0.175178 |
AIRLOOP F4 S1 SUPPLY FAN | 0.175499 |
AIRLOOP F4 S2 SUPPLY FAN | 0.176025 |
AIRLOOP M SW SUPPLY FAN | 0.299542 |
AIRLOOP M NW SUPPLY FAN | 0.297189 |
AIRLOOP M SE SUPPLY FAN | 0.252418 |
AIRLOOP M NE SUPPLY FAN | 0.238645 |
AIRLOOP M N1 SUPPLY FAN | 0.180149 |
AIRLOOP M N2 SUPPLY FAN | 0.179208 |
AIRLOOP M S1 SUPPLY FAN | 0.179323 |
AIRLOOP M S2 SUPPLY FAN | 0.179806 |
AIRLOOP F6 SW SUPPLY FAN | 0.295986 |
AIRLOOP F6 NW SUPPLY FAN | 0.293544 |
AIRLOOP F6 SE SUPPLY FAN | 0.249439 |
AIRLOOP F6 NE SUPPLY FAN | 0.235224 |
AIRLOOP F6 N1 SUPPLY FAN | 0.177036 |
AIRLOOP F6 N2 SUPPLY FAN | 0.176107 |
AIRLOOP F6 S1 SUPPLY FAN | 0.176182 |
AIRLOOP F6 S2 SUPPLY FAN | 0.176659 |
AIRLOOP F7 SW SUPPLY FAN | 0.295025 |
AIRLOOP F7 NW SUPPLY FAN | 0.292612 |
AIRLOOP F7 SE SUPPLY FAN | 0.248964 |
AIRLOOP F7 NE SUPPLY FAN | 0.234454 |
AIRLOOP F7 N1 SUPPLY FAN | 0.176466 |
AIRLOOP F7 N2 SUPPLY FAN | 0.175548 |
AIRLOOP F7 S1 SUPPLY FAN | 0.175504 |
AIRLOOP F7 S2 SUPPLY FAN | 0.175980 |
AIRLOOP F8 SW SUPPLY FAN | 0.295647 |
AIRLOOP F8 NW SUPPLY FAN | 0.293252 |
AIRLOOP F8 SE SUPPLY FAN | 0.249951 |
AIRLOOP F8 NE SUPPLY FAN | 0.235159 |
AIRLOOP F8 N1 SUPPLY FAN | 0.177408 |
AIRLOOP F8 N2 SUPPLY FAN | 0.176500 |
AIRLOOP F8 S1 SUPPLY FAN | 0.176299 |
AIRLOOP F8 S2 SUPPLY FAN | 0.176776 |
AIRLOOP F9 SW SUPPLY FAN | 0.305776 |
AIRLOOP F9 NW SUPPLY FAN | 0.303429 |
AIRLOOP F9 SE SUPPLY FAN | 0.258257 |
AIRLOOP F9 NE SUPPLY FAN | 0.243457 |
AIRLOOP F9 N1 SUPPLY FAN | 0.186676 |
AIRLOOP F9 N2 SUPPLY FAN | 0.185772 |
AIRLOOP F9 S1 SUPPLY FAN | 0.183377 |
AIRLOOP F9 S2 SUPPLY FAN | 0.183819 |
AIRLOOP T SW SUPPLY FAN | 0.374762 |
AIRLOOP T NW SUPPLY FAN | 0.367726 |
AIRLOOP T SE SUPPLY FAN | 0.324688 |
AIRLOOP T NE SUPPLY FAN | 0.300205 |
AIRLOOP T N1 SUPPLY FAN | 0.231458 |
AIRLOOP T N2 SUPPLY FAN | 0.230771 |
AIRLOOP T S1 SUPPLY FAN | 0.254066 |
AIRLOOP T S2 SUPPLY FAN | 0.254454 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.237061 | 3249.68 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.235517 | 3218.01 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.310027 | 4223.95 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.182169 | 2488.28 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.135193 | 1921.73 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.133984 | 1906.25 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.133128 | 1970.73 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.138266 | 2036.19 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.294151 | 3965.11 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.291180 | 3915.59 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.263666 | 3612.81 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.230733 | 3107.16 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.171694 | 2392.07 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.170715 | 2379.58 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.171193 | 2454.33 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.172891 | 2471.69 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.294810 | 3967.89 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.292316 | 3924.39 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.248316 | 3412.66 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.233427 | 3135.87 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.174390 | 2423.14 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.173428 | 2410.87 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.173901 | 2485.63 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.174602 | 2490.29 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.295938 | 3978.02 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.293476 | 3934.90 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.248453 | 3410.37 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.234810 | 3149.32 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.176129 | 2442.83 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.175178 | 2430.72 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.175499 | 2503.58 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.176025 | 2506.01 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.299542 | 4020.32 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.297189 | 3978.56 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.252418 | 3457.37 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.238645 | 3194.58 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.180149 | 2492.03 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.179208 | 2480.05 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.179323 | 2550.25 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.179806 | 2552.12 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.295986 | 3972.31 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.293544 | 3929.39 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.249439 | 3416.79 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.235224 | 3148.43 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.177036 | 2450.64 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.176107 | 2438.82 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.176182 | 2508.70 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.176659 | 2514.76 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.295025 | 3957.58 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.292612 | 3914.99 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.248964 | 3408.31 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.234454 | 3136.20 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.176466 | 2441.88 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.175548 | 2430.19 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.175504 | 2498.64 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.175980 | 2504.70 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.295647 | 3963.16 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.293252 | 3920.80 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.249951 | 3418.62 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.235159 | 3142.91 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.177408 | 2452.52 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.176500 | 2440.97 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.176299 | 2507.45 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.176776 | 2513.52 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.305776 | 4089.45 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.303429 | 4047.73 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.258257 | 3526.19 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.243457 | 3278.03 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.186676 | 2569.27 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.185772 | 2557.77 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.183377 | 2596.17 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.183819 | 2601.78 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.374762 | 4985.04 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.367726 | 4878.09 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.324688 | 4361.67 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.300205 | 4055.89 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.231458 | 3200.15 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.230771 | 3196.55 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.254066 | 3492.06 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.254454 | 3496.99 | 0.000076 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2219.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2216.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2965.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2213.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1639.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1639.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1638.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1646.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2173.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2168.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2195.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2165.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1466.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1466.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1474.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1475.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2144.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2140.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2144.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2137.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1422.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1421.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1426.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1426.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2156.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2154.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2154.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2151.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1421.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1421.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1423.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1423.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2148.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2146.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2146.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2144.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1404.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1404.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1407.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1407.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2210.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2209.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2208.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2208.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1455.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1455.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1456.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1456.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2246.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2246.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2245.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2245.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1483.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1483.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1483.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1483.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2286.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2286.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2286.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2286.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1516.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1516.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1516.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1516.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2439.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2437.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2439.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2437.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1652.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1652.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1654.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1654.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2990.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2995.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2991.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2995.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2256.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2256.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2248.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2248.82 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005431 | 6.11 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005431 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005431 | 2621.67 | 7.96 | 7048.30 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005431 | 1385.13 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 8.14 |
February | 23.05 | 10.27 |
March | 23.21 | 12.55 |
April | 23.90 | 19.23 |
May | 24.24 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.35 | 23.38 |
October | 24.09 | 18.30 |
November | 23.35 | 11.18 |
December | 22.83 | 6.79 |
Annual Sum or Average | 23.76 | 17.98 |
Minimum of Months | 22.83 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 8.14 |
February | 22.26 | 10.27 |
March | 22.67 | 12.55 |
April | 23.79 | 19.23 |
May | 24.25 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.34 | 23.38 |
October | 23.85 | 18.30 |
November | 22.52 | 11.18 |
December | 21.94 | 6.79 |
Annual Sum or Average | 23.40 | 17.98 |
Minimum of Months | 21.94 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 8.14 |
February | 23.10 | 10.27 |
March | 23.33 | 12.55 |
April | 24.05 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.10 | 18.30 |
November | 23.27 | 11.18 |
December | 22.76 | 6.79 |
Annual Sum or Average | 23.78 | 17.98 |
Minimum of Months | 22.76 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 8.14 |
February | 22.20 | 10.27 |
March | 22.62 | 12.55 |
April | 23.81 | 19.23 |
May | 24.26 | 23.84 |
June | 24.39 | 27.86 |
July | 24.42 | 27.54 |
August | 24.39 | 26.28 |
September | 24.34 | 23.38 |
October | 23.77 | 18.30 |
November | 22.39 | 11.18 |
December | 21.85 | 6.79 |
Annual Sum or Average | 23.37 | 17.98 |
Minimum of Months | 21.85 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 8.14 |
February | 22.10 | 10.27 |
March | 22.43 | 12.55 |
April | 23.65 | 19.23 |
May | 24.20 | 23.84 |
June | 24.39 | 27.86 |
July | 24.41 | 27.54 |
August | 24.38 | 26.28 |
September | 24.32 | 23.38 |
October | 23.70 | 18.30 |
November | 22.31 | 11.18 |
December | 21.84 | 6.79 |
Annual Sum or Average | 23.31 | 17.98 |
Minimum of Months | 21.84 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 8.14 |
February | 22.10 | 10.27 |
March | 22.43 | 12.55 |
April | 23.65 | 19.23 |
May | 24.20 | 23.84 |
June | 24.39 | 27.86 |
July | 24.41 | 27.54 |
August | 24.38 | 26.28 |
September | 24.32 | 23.38 |
October | 23.69 | 18.30 |
November | 22.30 | 11.18 |
December | 21.84 | 6.79 |
Annual Sum or Average | 23.30 | 17.98 |
Minimum of Months | 21.84 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 8.14 |
February | 23.10 | 10.27 |
March | 23.18 | 12.55 |
April | 23.82 | 19.23 |
May | 24.20 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.06 | 18.30 |
November | 23.41 | 11.18 |
December | 22.91 | 6.79 |
Annual Sum or Average | 23.77 | 17.98 |
Minimum of Months | 22.91 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 8.14 |
February | 23.14 | 10.27 |
March | 23.21 | 12.55 |
April | 23.85 | 19.23 |
May | 24.21 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.08 | 18.30 |
November | 23.43 | 11.18 |
December | 22.94 | 6.79 |
Annual Sum or Average | 23.79 | 17.98 |
Minimum of Months | 22.94 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.90 | 8.14 |
February | 20.62 | 10.27 |
March | 21.40 | 12.55 |
April | 23.53 | 19.23 |
May | 24.98 | 23.84 |
June | 26.67 | 27.86 |
July | 26.67 | 27.54 |
August | 26.33 | 26.28 |
September | 25.71 | 23.38 |
October | 23.48 | 18.30 |
November | 21.10 | 11.18 |
December | 19.60 | 6.79 |
Annual Sum or Average | 23.35 | 17.98 |
Minimum of Months | 19.60 | 6.79 |
Maximum of Months | 26.67 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 8.14 |
February | 23.79 | 10.27 |
March | 23.97 | 12.55 |
April | 24.25 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.38 | 23.38 |
October | 24.36 | 18.30 |
November | 23.97 | 11.18 |
December | 23.48 | 6.79 |
Annual Sum or Average | 24.11 | 17.98 |
Minimum of Months | 23.48 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 8.14 |
February | 22.82 | 10.27 |
March | 23.40 | 12.55 |
April | 24.17 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.25 | 18.30 |
November | 23.18 | 11.18 |
December | 22.22 | 6.79 |
Annual Sum or Average | 23.70 | 17.98 |
Minimum of Months | 22.22 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 8.14 |
February | 23.82 | 10.27 |
March | 23.99 | 12.55 |
April | 24.29 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.36 | 18.30 |
November | 23.96 | 11.18 |
December | 23.50 | 6.79 |
Annual Sum or Average | 24.12 | 17.98 |
Minimum of Months | 23.50 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 8.14 |
February | 22.74 | 10.27 |
March | 23.33 | 12.55 |
April | 24.18 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.21 | 18.30 |
November | 23.02 | 11.18 |
December | 22.11 | 6.79 |
Annual Sum or Average | 23.65 | 17.98 |
Minimum of Months | 22.11 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.29 | 8.14 |
February | 22.73 | 10.27 |
March | 23.26 | 12.55 |
April | 24.11 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.20 | 18.30 |
November | 23.06 | 11.18 |
December | 22.17 | 6.79 |
Annual Sum or Average | 23.65 | 17.98 |
Minimum of Months | 22.17 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 8.14 |
February | 22.73 | 10.27 |
March | 23.25 | 12.55 |
April | 24.11 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.20 | 18.30 |
November | 23.04 | 11.18 |
December | 22.16 | 6.79 |
Annual Sum or Average | 23.64 | 17.98 |
Minimum of Months | 22.16 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.80 | 8.14 |
February | 23.93 | 10.27 |
March | 24.01 | 12.55 |
April | 24.22 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.38 | 18.30 |
November | 24.07 | 11.18 |
December | 23.72 | 6.79 |
Annual Sum or Average | 24.18 | 17.98 |
Minimum of Months | 23.72 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.81 | 8.14 |
February | 23.94 | 10.27 |
March | 24.02 | 12.55 |
April | 24.23 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.38 | 18.30 |
November | 24.07 | 11.18 |
December | 23.73 | 6.79 |
Annual Sum or Average | 24.18 | 17.98 |
Minimum of Months | 23.73 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 8.14 |
February | 24.16 | 10.27 |
March | 24.65 | 12.55 |
April | 25.67 | 19.23 |
May | 26.22 | 23.84 |
June | 26.74 | 27.86 |
July | 26.72 | 27.54 |
August | 26.63 | 26.28 |
September | 26.49 | 23.38 |
October | 25.78 | 18.30 |
November | 24.53 | 11.18 |
December | 23.54 | 6.79 |
Annual Sum or Average | 25.41 | 17.98 |
Minimum of Months | 23.54 | 6.79 |
Maximum of Months | 26.74 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 8.14 |
February | 23.90 | 10.27 |
March | 24.06 | 12.55 |
April | 24.27 | 19.23 |
May | 24.36 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.38 | 23.38 |
October | 24.37 | 18.30 |
November | 24.06 | 11.18 |
December | 23.63 | 6.79 |
Annual Sum or Average | 24.16 | 17.98 |
Minimum of Months | 23.63 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 8.14 |
February | 22.99 | 10.27 |
March | 23.57 | 12.55 |
April | 24.20 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.29 | 18.30 |
November | 23.38 | 11.18 |
December | 22.33 | 6.79 |
Annual Sum or Average | 23.77 | 17.98 |
Minimum of Months | 22.33 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.66 | 8.14 |
February | 23.88 | 10.27 |
March | 24.03 | 12.55 |
April | 24.28 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.41 | 23.38 |
October | 24.37 | 18.30 |
November | 24.01 | 11.18 |
December | 23.58 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.58 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 8.14 |
February | 22.92 | 10.27 |
March | 23.51 | 12.55 |
April | 24.21 | 19.23 |
May | 24.37 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.40 | 26.28 |
September | 24.38 | 23.38 |
October | 24.26 | 18.30 |
November | 23.22 | 11.18 |
December | 22.21 | 6.79 |
Annual Sum or Average | 23.72 | 17.98 |
Minimum of Months | 22.21 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 8.14 |
February | 22.98 | 10.27 |
March | 23.51 | 12.55 |
April | 24.17 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.26 | 18.30 |
November | 23.34 | 11.18 |
December | 22.35 | 6.79 |
Annual Sum or Average | 23.76 | 17.98 |
Minimum of Months | 22.35 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 8.14 |
February | 22.98 | 10.27 |
March | 23.50 | 12.55 |
April | 24.17 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.25 | 18.30 |
November | 23.32 | 11.18 |
December | 22.35 | 6.79 |
Annual Sum or Average | 23.75 | 17.98 |
Minimum of Months | 22.35 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 8.14 |
February | 24.08 | 10.27 |
March | 24.14 | 12.55 |
April | 24.26 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.18 | 11.18 |
December | 23.90 | 6.79 |
Annual Sum or Average | 24.25 | 17.98 |
Minimum of Months | 23.90 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 8.14 |
February | 24.08 | 10.27 |
March | 24.14 | 12.55 |
April | 24.26 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.18 | 11.18 |
December | 23.90 | 6.79 |
Annual Sum or Average | 24.25 | 17.98 |
Minimum of Months | 23.90 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.22 | 8.14 |
February | 24.67 | 10.27 |
March | 25.15 | 12.55 |
April | 26.01 | 19.23 |
May | 26.46 | 23.84 |
June | 26.81 | 27.86 |
July | 26.78 | 27.54 |
August | 26.69 | 26.28 |
September | 26.59 | 23.38 |
October | 26.11 | 18.30 |
November | 25.03 | 11.18 |
December | 24.05 | 6.79 |
Annual Sum or Average | 25.72 | 17.98 |
Minimum of Months | 24.05 | 6.79 |
Maximum of Months | 26.81 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 8.14 |
February | 23.92 | 10.27 |
March | 24.08 | 12.55 |
April | 24.27 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.37 | 18.30 |
November | 24.07 | 11.18 |
December | 23.65 | 6.79 |
Annual Sum or Average | 24.17 | 17.98 |
Minimum of Months | 23.65 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.58 | 8.14 |
February | 23.03 | 10.27 |
March | 23.61 | 12.55 |
April | 24.20 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.29 | 18.30 |
November | 23.43 | 11.18 |
December | 22.38 | 6.79 |
Annual Sum or Average | 23.79 | 17.98 |
Minimum of Months | 22.38 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.68 | 8.14 |
February | 23.88 | 10.27 |
March | 24.04 | 12.55 |
April | 24.28 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.41 | 23.38 |
October | 24.37 | 18.30 |
November | 24.01 | 11.18 |
December | 23.59 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.59 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.36 | 8.14 |
February | 22.96 | 10.27 |
March | 23.55 | 12.55 |
April | 24.21 | 19.23 |
May | 24.37 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.27 | 18.30 |
November | 23.28 | 11.18 |
December | 22.25 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 22.25 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 8.14 |
February | 23.07 | 10.27 |
March | 23.59 | 12.55 |
April | 24.18 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.44 | 11.18 |
December | 22.44 | 6.79 |
Annual Sum or Average | 23.80 | 17.98 |
Minimum of Months | 22.44 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 8.14 |
February | 23.07 | 10.27 |
March | 23.59 | 12.55 |
April | 24.18 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.43 | 11.18 |
December | 22.43 | 6.79 |
Annual Sum or Average | 23.80 | 17.98 |
Minimum of Months | 22.43 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 8.14 |
February | 24.10 | 10.27 |
March | 24.17 | 12.55 |
April | 24.26 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.20 | 11.18 |
December | 23.94 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.94 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 8.14 |
February | 24.10 | 10.27 |
March | 24.17 | 12.55 |
April | 24.26 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.20 | 11.18 |
December | 23.94 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.94 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.42 | 8.14 |
February | 24.86 | 10.27 |
March | 25.34 | 12.55 |
April | 26.14 | 19.23 |
May | 26.57 | 23.84 |
June | 26.90 | 27.86 |
July | 26.86 | 27.54 |
August | 26.78 | 26.28 |
September | 26.68 | 23.38 |
October | 26.24 | 18.30 |
November | 25.23 | 11.18 |
December | 24.25 | 6.79 |
Annual Sum or Average | 25.86 | 17.98 |
Minimum of Months | 24.25 | 6.79 |
Maximum of Months | 26.90 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 8.14 |
February | 23.91 | 10.27 |
March | 24.07 | 12.55 |
April | 24.26 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.37 | 18.30 |
November | 24.07 | 11.18 |
December | 23.66 | 6.79 |
Annual Sum or Average | 24.17 | 17.98 |
Minimum of Months | 23.66 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 8.14 |
February | 23.05 | 10.27 |
March | 23.60 | 12.55 |
April | 24.19 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.29 | 18.30 |
November | 23.45 | 11.18 |
December | 22.41 | 6.79 |
Annual Sum or Average | 23.80 | 17.98 |
Minimum of Months | 22.41 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 8.14 |
February | 23.88 | 10.27 |
March | 24.03 | 12.55 |
April | 24.27 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.41 | 23.38 |
October | 24.37 | 18.30 |
November | 24.02 | 11.18 |
December | 23.60 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.60 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 8.14 |
February | 22.98 | 10.27 |
March | 23.55 | 12.55 |
April | 24.20 | 19.23 |
May | 24.37 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.27 | 18.30 |
November | 23.30 | 11.18 |
December | 22.28 | 6.79 |
Annual Sum or Average | 23.75 | 17.98 |
Minimum of Months | 22.28 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 8.14 |
February | 23.11 | 10.27 |
March | 23.62 | 12.55 |
April | 24.18 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.49 | 11.18 |
December | 22.50 | 6.79 |
Annual Sum or Average | 23.82 | 17.98 |
Minimum of Months | 22.50 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 8.14 |
February | 23.11 | 10.27 |
March | 23.61 | 12.55 |
April | 24.18 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.47 | 11.18 |
December | 22.49 | 6.79 |
Annual Sum or Average | 23.81 | 17.98 |
Minimum of Months | 22.49 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.05 | 8.14 |
February | 24.11 | 10.27 |
March | 24.17 | 12.55 |
April | 24.26 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.21 | 11.18 |
December | 23.96 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.96 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.05 | 8.14 |
February | 24.11 | 10.27 |
March | 24.17 | 12.55 |
April | 24.26 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.41 | 18.30 |
November | 24.21 | 11.18 |
December | 23.95 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.95 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.07 | 8.14 |
February | 25.49 | 10.27 |
March | 25.95 | 12.55 |
April | 26.73 | 19.23 |
May | 27.16 | 23.84 |
June | 27.49 | 27.86 |
July | 27.45 | 27.54 |
August | 27.37 | 26.28 |
September | 27.28 | 23.38 |
October | 26.85 | 18.30 |
November | 25.87 | 11.18 |
December | 24.90 | 6.79 |
Annual Sum or Average | 26.47 | 17.98 |
Minimum of Months | 24.90 | 6.79 |
Maximum of Months | 27.49 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.68 | 8.14 |
February | 23.84 | 10.27 |
March | 24.00 | 12.55 |
April | 24.23 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.36 | 18.30 |
November | 24.02 | 11.18 |
December | 23.58 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.58 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 8.14 |
February | 22.92 | 10.27 |
March | 23.49 | 12.55 |
April | 24.15 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.33 | 11.18 |
December | 22.32 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 22.32 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.60 | 8.14 |
February | 23.81 | 10.27 |
March | 23.97 | 12.55 |
April | 24.24 | 19.23 |
May | 24.36 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.36 | 18.30 |
November | 23.96 | 11.18 |
December | 23.52 | 6.79 |
Annual Sum or Average | 24.12 | 17.98 |
Minimum of Months | 23.52 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 8.14 |
February | 22.85 | 10.27 |
March | 23.43 | 12.55 |
April | 24.17 | 19.23 |
May | 24.36 | 23.84 |
June | 24.41 | 27.86 |
July | 24.42 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.24 | 18.30 |
November | 23.18 | 11.18 |
December | 22.19 | 6.79 |
Annual Sum or Average | 23.70 | 17.98 |
Minimum of Months | 22.19 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.59 | 8.14 |
February | 22.98 | 10.27 |
March | 23.50 | 12.55 |
April | 24.14 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.25 | 18.30 |
November | 23.37 | 11.18 |
December | 22.39 | 6.79 |
Annual Sum or Average | 23.76 | 17.98 |
Minimum of Months | 22.39 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.56 | 8.14 |
February | 22.98 | 10.27 |
March | 23.50 | 12.55 |
April | 24.14 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.25 | 18.30 |
November | 23.36 | 11.18 |
December | 22.38 | 6.79 |
Annual Sum or Average | 23.76 | 17.98 |
Minimum of Months | 22.38 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 8.14 |
February | 24.06 | 10.27 |
March | 24.11 | 12.55 |
April | 24.23 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.43 | 23.38 |
October | 24.40 | 18.30 |
November | 24.17 | 11.18 |
December | 23.90 | 6.79 |
Annual Sum or Average | 24.24 | 17.98 |
Minimum of Months | 23.90 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 8.14 |
February | 24.06 | 10.27 |
March | 24.11 | 12.55 |
April | 24.23 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.44 | 23.38 |
October | 24.40 | 18.30 |
November | 24.17 | 11.18 |
December | 23.90 | 6.79 |
Annual Sum or Average | 24.23 | 17.98 |
Minimum of Months | 23.90 | 6.79 |
Maximum of Months | 24.44 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.36 | 8.14 |
February | 24.78 | 10.27 |
March | 25.25 | 12.55 |
April | 26.09 | 19.23 |
May | 26.55 | 23.84 |
June | 26.89 | 27.86 |
July | 26.85 | 27.54 |
August | 26.76 | 26.28 |
September | 26.66 | 23.38 |
October | 26.22 | 18.30 |
November | 25.17 | 11.18 |
December | 24.19 | 6.79 |
Annual Sum or Average | 25.82 | 17.98 |
Minimum of Months | 24.19 | 6.79 |
Maximum of Months | 26.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.61 | 8.14 |
February | 23.78 | 10.27 |
March | 23.94 | 12.55 |
April | 24.20 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.35 | 18.30 |
November | 23.98 | 11.18 |
December | 23.52 | 6.79 |
Annual Sum or Average | 24.11 | 17.98 |
Minimum of Months | 23.52 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 8.14 |
February | 22.83 | 10.27 |
March | 23.39 | 12.55 |
April | 24.12 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.26 | 18.30 |
November | 23.25 | 11.18 |
December | 22.26 | 6.79 |
Annual Sum or Average | 23.70 | 17.98 |
Minimum of Months | 22.26 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 8.14 |
February | 23.75 | 10.27 |
March | 23.91 | 12.55 |
April | 24.22 | 19.23 |
May | 24.36 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.35 | 18.30 |
November | 23.93 | 11.18 |
December | 23.46 | 6.79 |
Annual Sum or Average | 24.09 | 17.98 |
Minimum of Months | 23.46 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 8.14 |
February | 22.76 | 10.27 |
March | 23.34 | 12.55 |
April | 24.14 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.42 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.22 | 18.30 |
November | 23.08 | 11.18 |
December | 22.14 | 6.79 |
Annual Sum or Average | 23.66 | 17.98 |
Minimum of Months | 22.14 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 8.14 |
February | 22.88 | 10.27 |
March | 23.40 | 12.55 |
April | 24.11 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.23 | 18.30 |
November | 23.28 | 11.18 |
December | 22.31 | 6.79 |
Annual Sum or Average | 23.72 | 17.98 |
Minimum of Months | 22.31 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 8.14 |
February | 22.88 | 10.27 |
March | 23.40 | 12.55 |
April | 24.11 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.23 | 18.30 |
November | 23.26 | 11.18 |
December | 22.30 | 6.79 |
Annual Sum or Average | 23.72 | 17.98 |
Minimum of Months | 22.30 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 8.14 |
February | 24.01 | 10.27 |
March | 24.06 | 12.55 |
April | 24.21 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.43 | 23.38 |
October | 24.39 | 18.30 |
November | 24.14 | 11.18 |
December | 23.85 | 6.79 |
Annual Sum or Average | 24.21 | 17.98 |
Minimum of Months | 23.85 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 8.14 |
February | 24.01 | 10.27 |
March | 24.06 | 12.55 |
April | 24.21 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.43 | 23.38 |
October | 24.39 | 18.30 |
November | 24.14 | 11.18 |
December | 23.85 | 6.79 |
Annual Sum or Average | 24.21 | 17.98 |
Minimum of Months | 23.85 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 8.14 |
February | 24.61 | 10.27 |
March | 25.07 | 12.55 |
April | 25.97 | 19.23 |
May | 26.46 | 23.84 |
June | 26.81 | 27.86 |
July | 26.77 | 27.54 |
August | 26.68 | 26.28 |
September | 26.58 | 23.38 |
October | 26.11 | 18.30 |
November | 25.00 | 11.18 |
December | 24.02 | 6.79 |
Annual Sum or Average | 25.69 | 17.98 |
Minimum of Months | 24.02 | 6.79 |
Maximum of Months | 26.81 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 8.14 |
February | 23.72 | 10.27 |
March | 23.88 | 12.55 |
April | 24.18 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.34 | 18.30 |
November | 23.94 | 11.18 |
December | 23.45 | 6.79 |
Annual Sum or Average | 24.08 | 17.98 |
Minimum of Months | 23.45 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 8.14 |
February | 22.75 | 10.27 |
March | 23.30 | 12.55 |
April | 24.10 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.24 | 18.30 |
November | 23.16 | 11.18 |
December | 22.20 | 6.79 |
Annual Sum or Average | 23.67 | 17.98 |
Minimum of Months | 22.20 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.45 | 8.14 |
February | 23.69 | 10.27 |
March | 23.86 | 12.55 |
April | 24.20 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.34 | 18.30 |
November | 23.89 | 11.18 |
December | 23.40 | 6.79 |
Annual Sum or Average | 24.06 | 17.98 |
Minimum of Months | 23.40 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 8.14 |
February | 22.69 | 10.27 |
March | 23.25 | 12.55 |
April | 24.12 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.42 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.20 | 18.30 |
November | 23.00 | 11.18 |
December | 22.09 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.09 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 8.14 |
February | 22.79 | 10.27 |
March | 23.31 | 12.55 |
April | 24.09 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.22 | 18.30 |
November | 23.18 | 11.18 |
December | 22.24 | 6.79 |
Annual Sum or Average | 23.68 | 17.98 |
Minimum of Months | 22.24 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.36 | 8.14 |
February | 22.79 | 10.27 |
March | 23.30 | 12.55 |
April | 24.09 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.21 | 18.30 |
November | 23.16 | 11.18 |
December | 22.23 | 6.79 |
Annual Sum or Average | 23.67 | 17.98 |
Minimum of Months | 22.23 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 8.14 |
February | 23.96 | 10.27 |
March | 24.01 | 12.55 |
April | 24.19 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.43 | 23.38 |
October | 24.38 | 18.30 |
November | 24.10 | 11.18 |
December | 23.79 | 6.79 |
Annual Sum or Average | 24.19 | 17.98 |
Minimum of Months | 23.79 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.86 | 8.14 |
February | 23.96 | 10.27 |
March | 24.01 | 12.55 |
April | 24.19 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.43 | 23.38 |
October | 24.38 | 18.30 |
November | 24.10 | 11.18 |
December | 23.79 | 6.79 |
Annual Sum or Average | 24.19 | 17.98 |
Minimum of Months | 23.79 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 8.14 |
February | 24.49 | 10.27 |
March | 24.95 | 12.55 |
April | 25.92 | 19.23 |
May | 26.44 | 23.84 |
June | 26.81 | 27.86 |
July | 26.78 | 27.54 |
August | 26.68 | 26.28 |
September | 26.57 | 23.38 |
October | 26.07 | 18.30 |
November | 24.89 | 11.18 |
December | 23.91 | 6.79 |
Annual Sum or Average | 25.63 | 17.98 |
Minimum of Months | 23.91 | 6.79 |
Maximum of Months | 26.81 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 8.14 |
February | 23.61 | 10.27 |
March | 23.78 | 12.55 |
April | 24.15 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.33 | 18.30 |
November | 23.86 | 11.18 |
December | 23.33 | 6.79 |
Annual Sum or Average | 24.03 | 17.98 |
Minimum of Months | 23.33 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.24 | 8.14 |
February | 22.67 | 10.27 |
March | 23.19 | 12.55 |
April | 24.07 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.22 | 18.30 |
November | 23.05 | 11.18 |
December | 22.15 | 6.79 |
Annual Sum or Average | 23.63 | 17.98 |
Minimum of Months | 22.15 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 8.14 |
February | 23.58 | 10.27 |
March | 23.76 | 12.55 |
April | 24.17 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.32 | 18.30 |
November | 23.81 | 11.18 |
December | 23.28 | 6.79 |
Annual Sum or Average | 24.02 | 17.98 |
Minimum of Months | 23.28 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 8.14 |
February | 22.60 | 10.27 |
March | 23.14 | 12.55 |
April | 24.09 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.17 | 18.30 |
November | 22.88 | 11.18 |
December | 22.04 | 6.79 |
Annual Sum or Average | 23.58 | 17.98 |
Minimum of Months | 22.04 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 8.14 |
February | 22.68 | 10.27 |
March | 23.18 | 12.55 |
April | 24.06 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.19 | 18.30 |
November | 23.03 | 11.18 |
December | 22.15 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.15 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 8.14 |
February | 22.68 | 10.27 |
March | 23.18 | 12.55 |
April | 24.06 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.19 | 18.30 |
November | 23.02 | 11.18 |
December | 22.14 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.14 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.72 | 8.14 |
February | 23.86 | 10.27 |
March | 23.91 | 12.55 |
April | 24.16 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.36 | 18.30 |
November | 24.02 | 11.18 |
December | 23.65 | 6.79 |
Annual Sum or Average | 24.13 | 17.98 |
Minimum of Months | 23.65 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.72 | 8.14 |
February | 23.86 | 10.27 |
March | 23.91 | 12.55 |
April | 24.16 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.36 | 18.30 |
November | 24.02 | 11.18 |
December | 23.65 | 6.79 |
Annual Sum or Average | 24.13 | 17.98 |
Minimum of Months | 23.65 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.83 | 8.14 |
February | 24.31 | 10.27 |
March | 24.78 | 12.55 |
April | 25.90 | 19.23 |
May | 26.49 | 23.84 |
June | 26.92 | 27.86 |
July | 26.88 | 27.54 |
August | 26.77 | 26.28 |
September | 26.62 | 23.38 |
October | 26.03 | 18.30 |
November | 24.70 | 11.18 |
December | 23.70 | 6.79 |
Annual Sum or Average | 25.58 | 17.98 |
Minimum of Months | 23.70 | 6.79 |
Maximum of Months | 26.92 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.23 | 10.27 |
March | 23.38 | 12.55 |
April | 24.00 | 19.23 |
May | 24.28 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.34 | 23.38 |
October | 24.19 | 18.30 |
November | 23.46 | 11.18 |
December | 22.97 | 6.79 |
Annual Sum or Average | 23.84 | 17.98 |
Minimum of Months | 22.97 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 8.14 |
February | 22.61 | 10.27 |
March | 22.96 | 12.55 |
April | 23.92 | 19.23 |
May | 24.28 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.33 | 23.38 |
October | 24.03 | 18.30 |
November | 22.87 | 11.18 |
December | 22.25 | 6.79 |
Annual Sum or Average | 23.57 | 17.98 |
Minimum of Months | 22.25 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 8.14 |
February | 23.21 | 10.27 |
March | 23.39 | 12.55 |
April | 24.03 | 19.23 |
May | 24.31 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.36 | 23.38 |
October | 24.16 | 18.30 |
November | 23.42 | 11.18 |
December | 22.96 | 6.79 |
Annual Sum or Average | 23.83 | 17.98 |
Minimum of Months | 22.96 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 8.14 |
February | 22.56 | 10.27 |
March | 22.95 | 12.55 |
April | 23.95 | 19.23 |
May | 24.30 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.34 | 23.38 |
October | 23.97 | 18.30 |
November | 22.75 | 11.18 |
December | 22.10 | 6.79 |
Annual Sum or Average | 23.52 | 17.98 |
Minimum of Months | 22.10 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 8.14 |
February | 22.55 | 10.27 |
March | 22.91 | 12.55 |
April | 23.91 | 19.23 |
May | 24.27 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.32 | 23.38 |
October | 24.02 | 18.30 |
November | 22.79 | 11.18 |
December | 22.14 | 6.79 |
Annual Sum or Average | 23.53 | 17.98 |
Minimum of Months | 22.14 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.20 | 8.14 |
February | 22.55 | 10.27 |
March | 22.91 | 12.55 |
April | 23.91 | 19.23 |
May | 24.27 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.32 | 23.38 |
October | 24.02 | 18.30 |
November | 22.78 | 11.18 |
December | 22.13 | 6.79 |
Annual Sum or Average | 23.53 | 17.98 |
Minimum of Months | 22.13 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 8.14 |
February | 23.41 | 10.27 |
March | 23.50 | 12.55 |
April | 24.02 | 19.23 |
May | 24.28 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.37 | 23.38 |
October | 24.25 | 18.30 |
November | 23.61 | 11.18 |
December | 23.14 | 6.79 |
Annual Sum or Average | 23.91 | 17.98 |
Minimum of Months | 23.14 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 8.14 |
February | 23.40 | 10.27 |
March | 23.50 | 12.55 |
April | 24.02 | 19.23 |
May | 24.28 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.37 | 23.38 |
October | 24.24 | 18.30 |
November | 23.61 | 11.18 |
December | 23.14 | 6.79 |
Annual Sum or Average | 23.91 | 17.98 |
Minimum of Months | 23.14 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:17
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.78 | 8.14 |
February | 24.35 | 10.27 |
March | 24.89 | 12.55 |
April | 26.37 | 19.23 |
May | 27.18 | 23.84 |
June | 27.82 | 27.86 |
July | 27.79 | 27.54 |
August | 27.61 | 26.28 |
September | 27.31 | 23.38 |
October | 26.42 | 18.30 |
November | 24.72 | 11.18 |
December | 23.58 | 6.79 |
Annual Sum or Average | 25.99 | 17.98 |
Minimum of Months | 23.58 | 6.79 |
Maximum of Months | 27.82 | 27.86 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:17
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.221720E+12 | 123965.794 | 02-JAN-18:15 | 22204.399 | 56867.515 | 20322.080 | 0.000 | 10887.635 | 10720.100 | 1422.056 | 396.374 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.199686E+12 | 129919.711 | 20-FEB-18:15 | 22204.399 | 56867.515 | 20322.080 | 0.000 | 16621.958 | 10720.100 | 1422.056 | 615.968 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.219484E+12 | 142203.164 | 14-MAR-17:15 | 22204.399 | 56867.515 | 20322.080 | 0.000 | 38992.665 | 0.000 | 1422.056 | 1248.814 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.249050E+12 | 166075.200 | 21-APR-19:30 | 25049.151 | 49704.829 | 20322.080 | 0.000 | 56265.373 | 10720.100 | 1422.056 | 1646.039 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.286695E+12 | 166454.780 | 27-MAY-19:15 | 25049.151 | 49704.829 | 20322.080 | 0.000 | 56398.302 | 10720.100 | 1422.056 | 1892.691 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.307967E+12 | 170699.538 | 19-JUN-19:30 | 25049.151 | 49704.829 | 20322.080 | 0.000 | 60441.163 | 10720.100 | 1422.056 | 2094.588 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.330114E+12 | 172060.798 | 17-JUL-19:00 | 25049.151 | 49704.829 | 20322.080 | 0.000 | 61623.927 | 10720.100 | 1422.056 | 2273.083 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.314640E+12 | 170633.223 | 07-AUG-18:00 | 25049.151 | 51564.864 | 20322.080 | 0.000 | 58484.893 | 10720.100 | 1422.056 | 2055.466 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.291957E+12 | 167060.769 | 15-SEP-18:30 | 25049.151 | 51564.864 | 20322.080 | 0.000 | 55021.227 | 10720.100 | 1422.056 | 1946.678 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.257615E+12 | 167466.101 | 04-OCT-17:45 | 22204.399 | 56867.515 | 20322.080 | 0.000 | 52749.096 | 10720.100 | 1422.056 | 2034.966 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.218912E+12 | 132600.551 | 03-NOV-16:15 | 18221.747 | 56933.809 | 20322.080 | 0.000 | 33237.638 | 0.000 | 1422.056 | 1314.917 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.222992E+12 | 123000.158 | 07-DEC-18:00 | 22204.399 | 56867.515 | 20322.080 | 0.000 | 9970.489 | 10720.100 | 1422.056 | 347.631 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.312083E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.199686E+12 | 123000.158 | 18221.747 | 49704.829 | 20322.080 | 0.000 | 9970.489 | 0.000 | 1422.056 | 347.631 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.330114E+12 | 172060.798 | 25049.151 | 56933.809 | 20322.080 | 0.000 | 61623.927 | 10720.100 | 1422.056 | 2273.083 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:17
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.102867E+12 | 130846.030 | 27-JAN-07:45 | 0.000 | 0.000 | 0.000 | 130846.030 | 83854.880 | 83854.880 | 46991.150 |
February | 0.916185E+11 | 122948.240 | 02-FEB-06:00 | 0.000 | 0.000 | 0.000 | 122948.240 | 80148.585 | 80148.585 | 42799.656 |
March | 0.951894E+11 | 109179.837 | 02-MAR-07:30 | 0.000 | 0.000 | 0.000 | 109179.837 | 83038.893 | 83038.893 | 26140.944 |
April | 0.853551E+11 | 81506.640 | 02-APR-06:45 | 0.000 | 0.000 | 0.000 | 81506.640 | 81506.640 | 81506.640 | 0.000 |
May | 0.809973E+11 | 79473.733 | 01-MAY-06:00 | 0.000 | 0.000 | 0.000 | 79473.733 | 79473.733 | 79473.733 | 0.000 |
June | 0.723494E+11 | 77189.888 | 05-JUN-06:00 | 0.000 | 0.000 | 0.000 | 77189.888 | 77189.888 | 77189.888 | 0.000 |
July | 0.711767E+11 | 75763.954 | 11-JUL-06:00 | 0.000 | 0.000 | 0.000 | 75763.954 | 75763.954 | 75763.954 | 0.000 |
August | 0.712052E+11 | 75885.391 | 25-AUG-06:00 | 0.000 | 0.000 | 0.000 | 75885.391 | 75885.391 | 75885.391 | 0.000 |
September | 0.724190E+11 | 77341.751 | 28-SEP-06:00 | 0.000 | 0.000 | 0.000 | 77341.751 | 77341.751 | 77341.751 | 0.000 |
October | 0.811183E+11 | 79429.009 | 30-OCT-06:00 | 0.000 | 0.000 | 0.000 | 79429.009 | 79429.009 | 79429.009 | 0.000 |
November | 0.873252E+11 | 113818.082 | 28-NOV-06:00 | 0.000 | 0.000 | 0.000 | 113818.082 | 79554.230 | 79554.230 | 34263.853 |
December | 0.103623E+12 | 142092.631 | 27-DEC-07:30 | 0.000 | 0.000 | 0.000 | 142092.631 | 82933.344 | 82933.344 | 59159.287 |
Annual Sum or Average | 0.101524E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.711767E+11 | 75763.954 | 0.000 | 0.000 | 0.000 | 75763.954 | 75763.954 | 75763.954 | 0.000 | |
Maximum of Months | 0.103623E+12 | 142092.631 | 0.000 | 0.000 | 0.000 | 142092.631 | 83854.880 | 83854.880 | 59159.287 |