Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2018-10-19 09:40:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4477.69 | 571.39 | 634.24 |
Net Site Energy | 4477.69 | 571.39 | 634.24 |
Total Source Energy | 12291.14 | 1568.45 | 1740.98 |
Net Source Energy | 12291.14 | 1568.45 | 1740.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 10.11 | 13.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1107.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 604.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.43 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 894.05 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3570.48 | 907.21 | 0.00 | 0.00 | 0.00 | 7555.94 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 13.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 10.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1107.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 604.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 56.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 55.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.43 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 894.05 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 259.74 | 128.50 | 0.00 | 0.00 | 0.00 | 1.07 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 505.74 | 128.50 | 0.00 | 0.00 | 0.00 | 1.07 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 234.00 | 115.77 | 0.00 | 0.00 | 0.00 | 0.96 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 455.62 | 115.77 | 0.00 | 0.00 | 0.00 | 0.96 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3570.48 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3570.48 | 100.00 |
Total On-Site and Utility Electric Sources | 3570.48 | 100.00 |
Total Electricity End Uses | 3570.48 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7555.94 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7555.94 | 100.00 |
Total Water End Uses | 7555.94 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 18.75 |
Time Setpoint Not Met During Occupied Cooling | 565.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3841.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-19:00 | 05-FEB-07:15 | - | - | - | 09-SEP-17:15 |
Heating | 0.00 | 100597.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84175.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1860.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3451.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 79131.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 195062.84 | 179729.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 100597.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 84175.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1860.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 3451.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 79131.82 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 32.01 | 14.27 | 0.00 | 0.00 | 0.00 |
Cooling | 3507.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1913.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 179.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 174.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 969.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 11307.72 | 983.42 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.53 | 2.02 | 0.00 | 0.00 | 0.00 |
Cooling | 496.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 270.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 137.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1601.68 | 139.30 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.53 | 2.02 | 0.00 | 0.00 | 0.00 |
Cooling | 496.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 270.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 137.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1601.68 | 139.30 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.55 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.55 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.72_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 4.600 | 0.293 | 0.130 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.72_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 4.600 | 0.293 | 0.130 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.72_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 4.600 | 0.293 | 0.130 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 423.59 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 726.80 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.69 | 83.69 | 168.41 | |
Exterior Lighting Total | 10720.10 | 168.41 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 328744.51 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 262995.61 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4563.88 | 3111.56 | 1452.33 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4297.11 | 2908.93 | 1388.18 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5878.40 | 3986.43 | 1891.97 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3688.42 | 2452.89 | 1235.53 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2416.46 | 1504.00 | 912.46 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2399.94 | 1491.91 | 908.03 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3038.39 | 1958.97 | 1079.42 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3106.59 | 2010.88 | 1095.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5208.47 | 3584.96 | 1623.51 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4908.76 | 3355.31 | 1553.45 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4924.55 | 3372.44 | 1552.12 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4234.91 | 2848.98 | 1385.93 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2832.21 | 1802.02 | 1030.19 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2819.34 | 1792.46 | 1026.88 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3485.83 | 2286.54 | 1199.30 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3510.09 | 2305.09 | 1205.01 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5229.11 | 3585.55 | 1643.55 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4941.72 | 3365.77 | 1575.96 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4742.64 | 3217.40 | 1525.25 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4285.20 | 2873.52 | 1411.68 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2877.69 | 1829.59 | 1048.10 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2864.95 | 1820.13 | 1044.81 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3519.71 | 2304.62 | 1215.09 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3530.77 | 2313.08 | 1217.69 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5250.32 | 3590.49 | 1659.83 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4967.87 | 3374.76 | 1593.10 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4744.89 | 3208.19 | 1536.70 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4314.05 | 2885.18 | 1428.88 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2909.18 | 1848.29 | 1060.90 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2896.54 | 1838.92 | 1057.62 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3540.03 | 2314.30 | 1225.74 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3549.13 | 2321.25 | 1227.88 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5299.91 | 3619.41 | 1680.50 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5022.30 | 3407.56 | 1614.75 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4794.68 | 3237.54 | 1557.14 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4370.47 | 2919.86 | 1450.62 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2967.41 | 1887.74 | 1079.67 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2954.87 | 1878.45 | 1076.42 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3587.83 | 2345.92 | 1241.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3596.63 | 2352.65 | 1243.98 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5260.45 | 3581.16 | 1679.29 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4984.97 | 3371.24 | 1613.72 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4758.17 | 3202.05 | 1556.12 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4336.22 | 2886.55 | 1449.68 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2934.90 | 1860.27 | 1074.63 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2922.48 | 1851.10 | 1071.37 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3548.68 | 2312.17 | 1236.51 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3557.43 | 2318.85 | 1238.58 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5251.79 | 3567.63 | 1684.16 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4979.44 | 3360.34 | 1619.11 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4752.39 | 3191.09 | 1561.30 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4333.24 | 2878.05 | 1455.19 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2933.17 | 1856.14 | 1077.03 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2920.85 | 1847.06 | 1073.78 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3540.03 | 2302.12 | 1237.91 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3548.77 | 2308.79 | 1239.98 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5262.02 | 3569.34 | 1692.68 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4992.36 | 3364.27 | 1628.09 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4764.71 | 3194.69 | 1570.03 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4353.82 | 2887.02 | 1466.80 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2949.97 | 1866.04 | 1083.93 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2937.77 | 1857.06 | 1080.71 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3549.61 | 2306.27 | 1243.34 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3558.35 | 2312.93 | 1245.42 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5379.36 | 3653.76 | 1725.60 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5112.77 | 3450.96 | 1661.81 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4832.22 | 3240.89 | 1591.34 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4416.77 | 2929.78 | 1486.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3066.27 | 1949.83 | 1116.43 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3054.17 | 1940.90 | 1113.27 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3629.65 | 2363.94 | 1265.71 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3639.31 | 2371.30 | 1268.01 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6227.30 | 4299.89 | 1927.40 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5903.58 | 4052.75 | 1850.84 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5551.15 | 3785.31 | 1765.83 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5022.58 | 3384.49 | 1638.09 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3746.82 | 2449.66 | 1297.16 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3747.64 | 2450.39 | 1297.25 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4494.04 | 3020.53 | 1473.51 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4504.97 | 3028.97 | 1475.99 | 0.67 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4563.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4297.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5878.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3688.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2416.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2399.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3038.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3106.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5208.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4908.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4924.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4234.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2832.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2819.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3485.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3510.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5229.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4941.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4742.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4285.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2877.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2864.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3519.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3530.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5250.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4967.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4744.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4314.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2909.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2896.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3540.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3549.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5299.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5022.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4794.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4370.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2967.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2954.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3587.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3596.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5260.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4984.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4758.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4336.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2934.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2922.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3548.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3557.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5251.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4979.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4752.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4333.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2933.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2920.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3540.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3548.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5262.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4992.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4764.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4353.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2949.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2937.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3549.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3558.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5379.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5112.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4832.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4416.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3066.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3054.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3629.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3639.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6227.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5903.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5551.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5022.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3746.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3747.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4494.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4504.97 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 1705.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 1700.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2346.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 1700.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1197.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1197.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1200.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1208.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 1642.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 1637.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 1668.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 1637.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1618.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1614.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1621.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1614.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1627.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1625.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1627.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1625.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1619.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1618.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1620.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1618.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 1677.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 1677.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 1677.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 1677.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 1711.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 1712.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 1711.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 1712.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 1747.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 1749.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 1747.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 1749.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1110.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 1858.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 1859.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 1858.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 1859.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1186.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1186.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1185.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1185.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2230.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2236.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2230.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2236.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 1590.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 1590.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 1584.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 1584.65 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.37 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 261.45 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 358.83 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 216.80 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 120.58 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.11 | 119.35 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.90 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.20 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.07 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.19 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.54 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.53 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 149.79 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 148.82 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.13 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.02 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 327.07 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.20 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.67 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.98 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 151.98 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 151.02 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.35 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.21 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 326.77 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.32 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 288.93 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 257.37 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.42 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 152.47 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.86 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 199.57 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 329.06 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 308.01 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 291.27 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 260.26 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 157.06 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.11 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.70 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 202.38 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.61 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.75 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 287.10 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 256.29 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.93 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.00 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.93 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 198.61 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 322.73 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.14 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.49 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.93 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.23 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 152.31 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.61 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.29 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 322.46 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.10 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.41 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 255.09 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.98 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 153.07 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.77 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.45 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 330.65 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 310.52 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 289.71 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 259.04 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 162.26 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 161.35 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 202.39 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.14 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 395.74 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 371.13 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 344.54 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 304.59 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.79 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.87 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.00 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.87 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0072 | 1823.72 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2670.80 | 3204.96 | 0.209 | 0.251 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 33.27 | 0.01651 |
G NW APARTMENT | 2481.67 | 2978.00 | 0.195 | 0.233 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
OFFICE | 3406.07 | 4087.29 | 0.267 | 0.320 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 32.08 | 0.01651 |
G NE APARTMENT | 2057.81 | 2469.37 | 0.161 | 0.194 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
G N1 APARTMENT | 1144.59 | 1373.51 | 0.090 | 0.108 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
G N2 APARTMENT | 1132.93 | 1359.51 | 0.089 | 0.107 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 31.41 | 0.01651 |
G S1 APARTMENT | 1565.27 | 1878.33 | 0.123 | 0.147 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70 | 0.01651 |
G S2 APARTMENT | 1615.54 | 1938.65 | 0.127 | 0.152 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70 | 0.01651 |
F2 SW APARTMENT | 3113.95 | 3736.74 | 0.244 | 0.293 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F2 NW APARTMENT | 2896.83 | 3476.20 | 0.227 | 0.272 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F2 SE APARTMENT | 2919.14 | 3502.96 | 0.229 | 0.275 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F2 NE APARTMENT | 2425.40 | 2910.48 | 0.190 | 0.228 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
F2 N1 APARTMENT | 1421.80 | 1706.16 | 0.111 | 0.134 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F2 N2 APARTMENT | 1412.59 | 1695.10 | 0.111 | 0.133 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F2 S1 APARTMENT | 1871.21 | 2245.45 | 0.147 | 0.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F2 S2 APARTMENT | 1889.17 | 2267.00 | 0.148 | 0.178 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F3 SW APARTMENT | 3104.41 | 3725.29 | 0.243 | 0.292 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F3 NW APARTMENT | 2896.86 | 3476.23 | 0.227 | 0.272 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F3 SE APARTMENT | 2758.93 | 3310.71 | 0.216 | 0.260 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F3 NE APARTMENT | 2439.09 | 2926.91 | 0.191 | 0.229 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
F3 N1 APARTMENT | 1442.60 | 1731.12 | 0.113 | 0.136 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F3 N2 APARTMENT | 1433.50 | 1720.20 | 0.112 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F3 S1 APARTMENT | 1882.73 | 2259.28 | 0.148 | 0.177 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F3 S2 APARTMENT | 1890.94 | 2269.13 | 0.148 | 0.178 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F4 SW APARTMENT | 3101.57 | 3721.88 | 0.243 | 0.292 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F4 NW APARTMENT | 2897.96 | 3477.55 | 0.227 | 0.273 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F4 SE APARTMENT | 2742.42 | 3290.90 | 0.215 | 0.258 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F4 NE APARTMENT | 2442.78 | 2931.33 | 0.191 | 0.230 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
F4 N1 APARTMENT | 1456.26 | 1747.51 | 0.114 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F4 N2 APARTMENT | 1447.25 | 1736.70 | 0.113 | 0.136 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F4 S1 APARTMENT | 1887.59 | 2265.11 | 0.148 | 0.178 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F4 S2 APARTMENT | 1894.34 | 2273.21 | 0.148 | 0.178 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
M SW APARTMENT | 3123.29 | 3747.95 | 0.245 | 0.294 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
M NW APARTMENT | 2923.45 | 3508.14 | 0.229 | 0.275 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
M SE APARTMENT | 2764.59 | 3317.51 | 0.217 | 0.260 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
M NE APARTMENT | 2470.16 | 2964.20 | 0.194 | 0.232 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
M N1 APARTMENT | 1490.78 | 1788.93 | 0.117 | 0.140 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
M N2 APARTMENT | 1481.84 | 1778.21 | 0.116 | 0.139 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
M S1 APARTMENT | 1914.47 | 2297.36 | 0.150 | 0.180 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
M S2 APARTMENT | 1920.99 | 2305.19 | 0.151 | 0.181 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F6 SW APARTMENT | 3080.95 | 3697.14 | 0.241 | 0.290 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F6 NW APARTMENT | 2883.00 | 3459.60 | 0.226 | 0.271 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F6 SE APARTMENT | 2724.92 | 3269.91 | 0.214 | 0.256 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F6 NE APARTMENT | 2432.54 | 2919.05 | 0.191 | 0.229 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
F6 N1 APARTMENT | 1461.13 | 1753.36 | 0.115 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F6 N2 APARTMENT | 1452.32 | 1742.78 | 0.114 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F6 S1 APARTMENT | 1878.69 | 2254.43 | 0.147 | 0.177 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F6 S2 APARTMENT | 1885.18 | 2262.21 | 0.148 | 0.177 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F7 SW APARTMENT | 3063.14 | 3675.77 | 0.240 | 0.288 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F7 NW APARTMENT | 2867.75 | 3441.30 | 0.225 | 0.270 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F7 SE APARTMENT | 2709.63 | 3251.55 | 0.212 | 0.255 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F7 NE APARTMENT | 2419.61 | 2903.53 | 0.190 | 0.228 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 31.19 | 0.01651 |
F7 N1 APARTMENT | 1454.41 | 1745.29 | 0.114 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F7 N2 APARTMENT | 1445.69 | 1734.83 | 0.113 | 0.136 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F7 S1 APARTMENT | 1866.21 | 2239.45 | 0.146 | 0.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F7 S2 APARTMENT | 1872.67 | 2247.21 | 0.147 | 0.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F8 SW APARTMENT | 3060.56 | 3672.67 | 0.240 | 0.288 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F8 NW APARTMENT | 2867.33 | 3440.80 | 0.225 | 0.270 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F8 SE APARTMENT | 2708.89 | 3250.67 | 0.212 | 0.255 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F8 NE APARTMENT | 2421.08 | 2905.29 | 0.190 | 0.228 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 31.49 | 0.01651 |
F8 N1 APARTMENT | 1461.52 | 1753.83 | 0.115 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F8 N2 APARTMENT | 1452.90 | 1743.48 | 0.114 | 0.137 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F8 S1 APARTMENT | 1867.72 | 2241.26 | 0.146 | 0.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F8 S2 APARTMENT | 1874.18 | 2249.01 | 0.147 | 0.176 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F9 SW APARTMENT | 3138.27 | 3765.92 | 0.246 | 0.295 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
F9 NW APARTMENT | 2947.24 | 3536.69 | 0.231 | 0.277 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 32.60 | 0.01651 |
F9 SE APARTMENT | 2749.66 | 3299.60 | 0.216 | 0.259 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 32.28 | 0.01651 |
F9 NE APARTMENT | 2458.56 | 2950.28 | 0.193 | 0.231 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 31.49 | 0.01651 |
F9 N1 APARTMENT | 1540.14 | 1848.17 | 0.121 | 0.145 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F9 N2 APARTMENT | 1531.56 | 1837.87 | 0.120 | 0.144 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
F9 S1 APARTMENT | 1921.03 | 2305.24 | 0.151 | 0.181 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
F9 S2 APARTMENT | 1928.17 | 2313.80 | 0.151 | 0.181 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
T SW APARTMENT | 3755.97 | 4507.16 | 0.294 | 0.353 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 33.43 | 0.01651 |
T NW APARTMENT | 3522.39 | 4226.87 | 0.276 | 0.331 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 32.95 | 0.01651 |
T SE APARTMENT | 3270.03 | 3924.04 | 0.256 | 0.308 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:30:00 | 32.48 | 0.01651 |
T NE APARTMENT | 2890.85 | 3469.01 | 0.227 | 0.272 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 31.79 | 0.01651 |
T N1 APARTMENT | 2000.74 | 2400.89 | 0.157 | 0.188 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
T N2 APARTMENT | 2001.53 | 2401.83 | 0.157 | 0.188 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
T S1 APARTMENT | 2553.26 | 3063.91 | 0.200 | 0.240 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
T S2 APARTMENT | 2561.47 | 3073.76 | 0.201 | 0.241 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.80 | 0.01651 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 988.52 | 1186.22 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
G NW APARTMENT | 984.19 | 1181.03 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
OFFICE | 1318.38 | 1582.05 | 0.059 | 0.070 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 4.60 | 0.00526 |
G NE APARTMENT | 984.19 | 1181.03 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
G N1 APARTMENT | 558.80 | 670.56 | 0.025 | 0.030 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
G N2 APARTMENT | 558.80 | 670.56 | 0.025 | 0.030 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
G S1 APARTMENT | 561.37 | 673.64 | 0.025 | 0.030 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
G S2 APARTMENT | 568.48 | 682.17 | 0.025 | 0.030 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
F2 SW APARTMENT | 934.95 | 1121.94 | 0.042 | 0.050 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 NW APARTMENT | 930.80 | 1116.96 | 0.041 | 0.050 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 SE APARTMENT | 957.19 | 1148.63 | 0.043 | 0.051 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 NE APARTMENT | 930.80 | 1116.96 | 0.041 | 0.050 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 N1 APARTMENT | 428.19 | 513.83 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 N2 APARTMENT | 428.19 | 513.83 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 S1 APARTMENT | 434.72 | 521.66 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F2 S2 APARTMENT | 436.35 | 523.62 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 SW APARTMENT | 914.69 | 1097.63 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 NW APARTMENT | 911.65 | 1093.98 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 SE APARTMENT | 917.52 | 1101.02 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 NE APARTMENT | 911.65 | 1093.98 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 N1 APARTMENT | 395.42 | 474.51 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 N2 APARTMENT | 395.42 | 474.51 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 S1 APARTMENT | 399.00 | 478.79 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F3 S2 APARTMENT | 399.29 | 479.15 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 SW APARTMENT | 922.29 | 1106.75 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 NW APARTMENT | 920.70 | 1104.84 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 SE APARTMENT | 922.64 | 1107.17 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 NE APARTMENT | 920.70 | 1104.84 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 N1 APARTMENT | 392.99 | 471.59 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 N2 APARTMENT | 392.99 | 471.59 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 S1 APARTMENT | 394.87 | 473.84 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F4 S2 APARTMENT | 394.92 | 473.90 | 0.018 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M SW APARTMENT | 916.20 | 1099.44 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M NW APARTMENT | 914.86 | 1097.83 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M SE APARTMENT | 916.24 | 1099.49 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M NE APARTMENT | 914.86 | 1097.83 | 0.041 | 0.049 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M N1 APARTMENT | 382.12 | 458.55 | 0.017 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M N2 APARTMENT | 382.12 | 458.55 | 0.017 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M S1 APARTMENT | 383.67 | 460.41 | 0.017 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
M S2 APARTMENT | 383.68 | 460.42 | 0.017 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 SW APARTMENT | 964.49 | 1157.39 | 0.043 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 NW APARTMENT | 964.87 | 1157.84 | 0.043 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 SE APARTMENT | 964.49 | 1157.39 | 0.043 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 NE APARTMENT | 964.87 | 1157.84 | 0.043 | 0.052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 N1 APARTMENT | 419.62 | 503.54 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 N2 APARTMENT | 419.62 | 503.54 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 S1 APARTMENT | 419.41 | 503.30 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F6 S2 APARTMENT | 419.42 | 503.30 | 0.019 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 SW APARTMENT | 993.67 | 1192.41 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 NW APARTMENT | 994.71 | 1193.65 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 SE APARTMENT | 993.67 | 1192.41 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 NE APARTMENT | 994.71 | 1193.65 | 0.044 | 0.053 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 N1 APARTMENT | 442.26 | 530.71 | 0.020 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 N2 APARTMENT | 442.26 | 530.71 | 0.020 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 S1 APARTMENT | 441.37 | 529.64 | 0.020 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F7 S2 APARTMENT | 441.37 | 529.64 | 0.020 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 SW APARTMENT | 1023.82 | 1228.59 | 0.046 | 0.055 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 NW APARTMENT | 1025.34 | 1230.40 | 0.046 | 0.055 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 SE APARTMENT | 1023.82 | 1228.59 | 0.046 | 0.055 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 NE APARTMENT | 1025.34 | 1230.40 | 0.046 | 0.055 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 N1 APARTMENT | 466.83 | 560.20 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 N2 APARTMENT | 466.83 | 560.20 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 S1 APARTMENT | 465.44 | 558.52 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F8 S2 APARTMENT | 465.44 | 558.52 | 0.021 | 0.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 SW APARTMENT | 1117.83 | 1341.40 | 0.050 | 0.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 NW APARTMENT | 1118.59 | 1342.31 | 0.050 | 0.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 SE APARTMENT | 1117.83 | 1341.40 | 0.050 | 0.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 NE APARTMENT | 1118.59 | 1342.31 | 0.050 | 0.060 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 N1 APARTMENT | 549.51 | 659.41 | 0.024 | 0.029 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 N2 APARTMENT | 549.51 | 659.41 | 0.024 | 0.029 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 S1 APARTMENT | 548.66 | 658.39 | 0.024 | 0.029 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
F9 S2 APARTMENT | 548.66 | 658.39 | 0.024 | 0.029 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T SW APARTMENT | 1432.91 | 1719.49 | 0.064 | 0.077 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T NW APARTMENT | 1437.22 | 1724.66 | 0.064 | 0.077 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T SE APARTMENT | 1432.91 | 1719.49 | 0.064 | 0.077 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T NE APARTMENT | 1437.22 | 1724.66 | 0.064 | 0.077 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T N1 APARTMENT | 891.46 | 1069.76 | 0.040 | 0.048 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T N2 APARTMENT | 891.46 | 1069.76 | 0.040 | 0.048 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T S1 APARTMENT | 886.35 | 1063.62 | 0.039 | 0.047 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
T S2 APARTMENT | 886.35 | 1063.62 | 0.039 | 0.047 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4.60 | 0.00526 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.25 | 0.25 | 0.05 | 0.05 |
AIRLOOP G NW | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP OFFICE | 0.32 | 0.32 | 0.07 | 0.07 |
AIRLOOP G NE | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP G N1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP G N2 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP G S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP G S2 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F2 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F2 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F2 SE | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F2 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F2 N1 | 0.13 | 0.13 | 0.03 | 0.03 |
AIRLOOP F2 N2 | 0.13 | 0.13 | 0.03 | 0.03 |
AIRLOOP F2 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F2 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F3 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F3 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F3 SE | 0.26 | 0.26 | 0.05 | 0.05 |
AIRLOOP F3 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F3 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F3 N2 | 0.13 | 0.13 | 0.03 | 0.03 |
AIRLOOP F3 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F3 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F4 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F4 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F4 SE | 0.26 | 0.26 | 0.05 | 0.05 |
AIRLOOP F4 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F4 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F4 N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F4 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F4 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP M SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP M NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP M SE | 0.26 | 0.26 | 0.05 | 0.05 |
AIRLOOP M NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP M N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F6 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F6 SE | 0.26 | 0.26 | 0.05 | 0.05 |
AIRLOOP F6 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F6 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F6 N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F6 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F6 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F7 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F7 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F7 SE | 0.25 | 0.25 | 0.05 | 0.05 |
AIRLOOP F7 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F7 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F7 N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F7 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F7 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F8 SW | 0.29 | 0.29 | 0.05 | 0.05 |
AIRLOOP F8 NW | 0.27 | 0.27 | 0.05 | 0.05 |
AIRLOOP F8 SE | 0.25 | 0.25 | 0.05 | 0.05 |
AIRLOOP F8 NE | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F8 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F8 N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F8 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F8 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F9 SW | 0.30 | 0.30 | 0.06 | 0.06 |
AIRLOOP F9 NW | 0.28 | 0.28 | 0.06 | 0.06 |
AIRLOOP F9 SE | 0.26 | 0.26 | 0.06 | 0.06 |
AIRLOOP F9 NE | 0.23 | 0.23 | 0.06 | 0.06 |
AIRLOOP F9 N1 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F9 N2 | 0.14 | 0.14 | 0.03 | 0.03 |
AIRLOOP F9 S1 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP F9 S2 | 0.18 | 0.18 | 0.03 | 0.03 |
AIRLOOP T SW | 0.35 | 0.35 | 0.08 | 0.08 |
AIRLOOP T NW | 0.33 | 0.33 | 0.08 | 0.08 |
AIRLOOP T SE | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP T NE | 0.27 | 0.27 | 0.08 | 0.08 |
AIRLOOP T N1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP T N2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP T S1 | 0.24 | 0.24 | 0.05 | 0.05 |
AIRLOOP T S2 | 0.24 | 0.24 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 6265.00 | 5203.75 | 3203.75 |
G NW APARTMENT | 6004.75 | 5936.00 | 3406.75 |
OFFICE | 1779.75 | 210.75 | 42.75 |
G NE APARTMENT | 6012.75 | 5827.75 | 3301.25 |
G N1 APARTMENT | 5969.25 | 6047.75 | 3388.50 |
G N2 APARTMENT | 5968.75 | 6033.25 | 3374.00 |
G S1 APARTMENT | 6202.75 | 5317.25 | 3262.00 |
G S2 APARTMENT | 6213.75 | 5269.50 | 3247.50 |
F2 SW APARTMENT | 6902.75 | 2791.00 | 1744.50 |
F2 NW APARTMENT | 6304.75 | 4137.75 | 2111.75 |
F2 SE APARTMENT | 6965.50 | 2530.00 | 1564.00 |
F2 NE APARTMENT | 6285.00 | 4152.25 | 2071.25 |
F2 N1 APARTMENT | 6207.00 | 4290.75 | 2121.50 |
F2 N2 APARTMENT | 6204.75 | 4290.50 | 2121.50 |
F2 S1 APARTMENT | 6936.00 | 2625.00 | 1716.00 |
F2 S2 APARTMENT | 6945.50 | 2607.25 | 1709.75 |
F3 SW APARTMENT | 7079.25 | 2583.00 | 1700.50 |
F3 NW APARTMENT | 6417.25 | 3848.75 | 1983.25 |
F3 SE APARTMENT | 7063.25 | 2482.00 | 1598.75 |
F3 NE APARTMENT | 6413.00 | 3818.00 | 1916.50 |
F3 N1 APARTMENT | 6339.75 | 3875.75 | 1917.75 |
F3 N2 APARTMENT | 6337.00 | 3880.25 | 1920.00 |
F3 S1 APARTMENT | 7178.00 | 2327.75 | 1662.00 |
F3 S2 APARTMENT | 7181.25 | 2325.25 | 1663.00 |
F4 SW APARTMENT | 7095.00 | 2604.00 | 1731.00 |
F4 NW APARTMENT | 6444.25 | 3838.00 | 1994.25 |
F4 SE APARTMENT | 7064.75 | 2524.75 | 1636.25 |
F4 NE APARTMENT | 6430.50 | 3798.25 | 1922.75 |
F4 N1 APARTMENT | 6376.75 | 3806.25 | 1896.75 |
F4 N2 APARTMENT | 6373.75 | 3809.00 | 1896.00 |
F4 S1 APARTMENT | 7216.75 | 2312.75 | 1674.50 |
F4 S2 APARTMENT | 7215.50 | 2315.25 | 1676.25 |
M SW APARTMENT | 7102.00 | 2597.75 | 1725.25 |
M NW APARTMENT | 6457.25 | 3800.50 | 1970.25 |
M SE APARTMENT | 7070.25 | 2526.00 | 1633.75 |
M NE APARTMENT | 6444.75 | 3764.00 | 1899.00 |
M N1 APARTMENT | 6405.00 | 3749.00 | 1866.00 |
M N2 APARTMENT | 6402.25 | 3753.25 | 1865.25 |
M S1 APARTMENT | 7236.00 | 2290.00 | 1663.00 |
M S2 APARTMENT | 7235.25 | 2292.75 | 1664.75 |
F6 SW APARTMENT | 7015.00 | 2795.25 | 1832.25 |
F6 NW APARTMENT | 6395.00 | 4013.50 | 2103.50 |
F6 SE APARTMENT | 6978.50 | 2718.00 | 1742.25 |
F6 NE APARTMENT | 6394.00 | 3992.50 | 2034.25 |
F6 N1 APARTMENT | 6340.25 | 3933.75 | 1970.00 |
F6 N2 APARTMENT | 6337.25 | 3939.00 | 1971.25 |
F6 S1 APARTMENT | 7142.25 | 2446.50 | 1733.00 |
F6 S2 APARTMENT | 7141.00 | 2448.50 | 1733.00 |
F7 SW APARTMENT | 6951.50 | 2932.50 | 1902.50 |
F7 NW APARTMENT | 6361.50 | 4149.50 | 2182.00 |
F7 SE APARTMENT | 6925.75 | 2851.75 | 1810.00 |
F7 NE APARTMENT | 6361.50 | 4131.50 | 2111.50 |
F7 N1 APARTMENT | 6305.50 | 4036.75 | 2018.00 |
F7 N2 APARTMENT | 6305.50 | 4042.00 | 2018.00 |
F7 S1 APARTMENT | 7086.50 | 2554.50 | 1778.00 |
F7 S2 APARTMENT | 7082.50 | 2555.75 | 1779.25 |
F8 SW APARTMENT | 6900.50 | 3032.00 | 1943.25 |
F8 NW APARTMENT | 6337.50 | 4238.25 | 2227.75 |
F8 SE APARTMENT | 6881.75 | 2956.00 | 1852.00 |
F8 NE APARTMENT | 6330.00 | 4224.50 | 2158.00 |
F8 N1 APARTMENT | 6283.50 | 4116.00 | 2050.25 |
F8 N2 APARTMENT | 6280.00 | 4118.00 | 2052.25 |
F8 S1 APARTMENT | 7030.75 | 2644.75 | 1805.50 |
F8 S2 APARTMENT | 7027.75 | 2648.75 | 1807.25 |
F9 SW APARTMENT | 6832.75 | 3127.50 | 1938.75 |
F9 NW APARTMENT | 6310.25 | 4278.50 | 2205.50 |
F9 SE APARTMENT | 6813.50 | 3058.50 | 1844.00 |
F9 NE APARTMENT | 6287.75 | 4262.00 | 2138.75 |
F9 N1 APARTMENT | 6254.75 | 4178.00 | 2055.00 |
F9 N2 APARTMENT | 6251.00 | 4178.75 | 2054.25 |
F9 S1 APARTMENT | 6942.25 | 2769.50 | 1808.25 |
F9 S2 APARTMENT | 6939.75 | 2771.75 | 1808.75 |
T SW APARTMENT | 6740.25 | 3931.50 | 2422.50 |
T NW APARTMENT | 6315.75 | 4807.25 | 2659.50 |
T SE APARTMENT | 6741.75 | 3930.00 | 2407.25 |
T NE APARTMENT | 6303.50 | 4807.75 | 2611.25 |
T N1 APARTMENT | 6260.25 | 4706.50 | 2469.00 |
T N2 APARTMENT | 6260.25 | 4710.75 | 2471.25 |
T S1 APARTMENT | 6799.25 | 3622.75 | 2269.00 |
T S2 APARTMENT | 6799.00 | 3633.50 | 2279.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 7434.75 | 6460.00 | 3841.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 9.25 | 0.00 | 9.25 |
G NW APARTMENT | 0.25 | 3.25 | 0.25 | 3.25 |
OFFICE | 1.25 | 0.25 | 0.00 | 0.00 |
G NE APARTMENT | 0.00 | 20.50 | 0.00 | 20.50 |
G N1 APARTMENT | 1.50 | 124.75 | 1.50 | 124.75 |
G N2 APARTMENT | 2.50 | 138.75 | 2.50 | 138.75 |
G S1 APARTMENT | 1.00 | 96.50 | 1.00 | 96.50 |
G S2 APARTMENT | 1.00 | 83.25 | 1.00 | 83.25 |
F2 SW APARTMENT | 0.00 | 17.50 | 0.00 | 17.50 |
F2 NW APARTMENT | 0.25 | 1.75 | 0.25 | 1.75 |
F2 SE APARTMENT | 0.50 | 47.75 | 0.50 | 47.75 |
F2 NE APARTMENT | 0.00 | 13.75 | 0.00 | 13.75 |
F2 N1 APARTMENT | 0.50 | 146.00 | 0.50 | 146.00 |
F2 N2 APARTMENT | 0.75 | 160.00 | 0.75 | 160.00 |
F2 S1 APARTMENT | 0.00 | 195.75 | 0.00 | 195.75 |
F2 S2 APARTMENT | 0.00 | 187.75 | 0.00 | 187.75 |
F3 SW APARTMENT | 0.25 | 22.50 | 0.25 | 22.50 |
F3 NW APARTMENT | 0.25 | 1.75 | 0.25 | 1.75 |
F3 SE APARTMENT | 0.25 | 97.75 | 0.25 | 97.75 |
F3 NE APARTMENT | 0.25 | 24.50 | 0.25 | 24.50 |
F3 N1 APARTMENT | 0.50 | 207.75 | 0.50 | 207.75 |
F3 N2 APARTMENT | 0.50 | 225.50 | 0.50 | 225.50 |
F3 S1 APARTMENT | 0.00 | 249.25 | 0.00 | 249.25 |
F3 S2 APARTMENT | 0.00 | 245.50 | 0.00 | 245.50 |
F4 SW APARTMENT | 0.00 | 23.00 | 0.00 | 23.00 |
F4 NW APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
F4 SE APARTMENT | 0.00 | 105.25 | 0.00 | 105.25 |
F4 NE APARTMENT | 0.50 | 27.25 | 0.50 | 27.25 |
F4 N1 APARTMENT | 0.50 | 224.50 | 0.50 | 224.50 |
F4 N2 APARTMENT | 0.00 | 237.50 | 0.00 | 237.50 |
F4 S1 APARTMENT | 0.00 | 257.25 | 0.00 | 257.25 |
F4 S2 APARTMENT | 0.00 | 255.75 | 0.00 | 255.75 |
M SW APARTMENT | 0.00 | 22.75 | 0.00 | 22.75 |
M NW APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
M SE APARTMENT | 0.75 | 104.75 | 0.75 | 104.75 |
M NE APARTMENT | 0.00 | 28.75 | 0.00 | 28.75 |
M N1 APARTMENT | 0.25 | 231.50 | 0.25 | 231.50 |
M N2 APARTMENT | 0.00 | 249.25 | 0.00 | 249.25 |
M S1 APARTMENT | 0.00 | 259.50 | 0.00 | 259.50 |
M S2 APARTMENT | 0.00 | 256.25 | 0.00 | 256.25 |
F6 SW APARTMENT | 0.00 | 24.00 | 0.00 | 24.00 |
F6 NW APARTMENT | 0.00 | 3.00 | 0.00 | 3.00 |
F6 SE APARTMENT | 0.00 | 106.50 | 0.00 | 106.50 |
F6 NE APARTMENT | 0.25 | 29.75 | 0.25 | 29.75 |
F6 N1 APARTMENT | 0.50 | 240.75 | 0.50 | 240.75 |
F6 N2 APARTMENT | 0.50 | 258.25 | 0.50 | 258.25 |
F6 S1 APARTMENT | 0.00 | 267.75 | 0.00 | 267.75 |
F6 S2 APARTMENT | 0.00 | 265.25 | 0.00 | 265.25 |
F7 SW APARTMENT | 0.00 | 25.00 | 0.00 | 25.00 |
F7 NW APARTMENT | 0.00 | 4.00 | 0.00 | 4.00 |
F7 SE APARTMENT | 0.25 | 105.50 | 0.25 | 105.50 |
F7 NE APARTMENT | 0.00 | 32.00 | 0.00 | 32.00 |
F7 N1 APARTMENT | 0.75 | 246.00 | 0.75 | 246.00 |
F7 N2 APARTMENT | 0.75 | 263.00 | 0.75 | 263.00 |
F7 S1 APARTMENT | 0.00 | 268.75 | 0.00 | 268.75 |
F7 S2 APARTMENT | 0.00 | 265.75 | 0.00 | 265.75 |
F8 SW APARTMENT | 0.25 | 25.25 | 0.25 | 25.25 |
F8 NW APARTMENT | 0.00 | 4.50 | 0.00 | 4.50 |
F8 SE APARTMENT | 0.50 | 103.00 | 0.50 | 103.00 |
F8 NE APARTMENT | 0.00 | 32.25 | 0.00 | 32.25 |
F8 N1 APARTMENT | 1.25 | 252.25 | 1.25 | 252.25 |
F8 N2 APARTMENT | 1.00 | 265.25 | 1.00 | 265.25 |
F8 S1 APARTMENT | 0.00 | 268.50 | 0.00 | 268.50 |
F8 S2 APARTMENT | 0.00 | 266.50 | 0.00 | 266.50 |
F9 SW APARTMENT | 0.00 | 20.25 | 0.00 | 20.25 |
F9 NW APARTMENT | 0.00 | 4.50 | 0.00 | 4.50 |
F9 SE APARTMENT | 0.00 | 93.50 | 0.00 | 93.50 |
F9 NE APARTMENT | 0.00 | 31.25 | 0.00 | 31.25 |
F9 N1 APARTMENT | 1.00 | 219.25 | 1.00 | 219.25 |
F9 N2 APARTMENT | 0.75 | 232.50 | 0.75 | 232.50 |
F9 S1 APARTMENT | 0.00 | 241.00 | 0.00 | 241.00 |
F9 S2 APARTMENT | 0.25 | 238.25 | 0.25 | 238.25 |
T SW APARTMENT | 0.00 | 15.25 | 0.00 | 15.25 |
T NW APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
T SE APARTMENT | 0.00 | 62.25 | 0.00 | 62.25 |
T NE APARTMENT | 0.00 | 16.00 | 0.00 | 16.00 |
T N1 APARTMENT | 0.75 | 70.25 | 0.75 | 70.25 |
T N2 APARTMENT | 0.50 | 67.50 | 0.50 | 67.50 |
T S1 APARTMENT | 0.00 | 115.25 | 0.00 | 115.25 |
T S2 APARTMENT | 0.00 | 115.00 | 0.00 | 115.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 20.00 | 565.25 | 18.75 | 565.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.075 | 0.000 | 0.389 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.075 | 0.000 | 0.377 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.521 | 0.085 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.075 | 0.000 | 0.377 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.045 | 0.000 | 0.367 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.367 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.045 | 0.000 | 0.386 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.045 | 0.000 | 0.387 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.108 | 0.000 | 0.448 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.107 | 0.000 | 0.439 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.108 | 0.000 | 0.449 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.107 | 0.000 | 0.439 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.065 | 0.000 | 0.433 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.433 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.065 | 0.000 | 0.446 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.065 | 0.000 | 0.446 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.127 | 0.000 | 0.488 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.127 | 0.000 | 0.480 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.127 | 0.000 | 0.488 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.127 | 0.000 | 0.480 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.077 | 0.000 | 0.475 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.077 | 0.000 | 0.475 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.077 | 0.000 | 0.486 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.077 | 0.000 | 0.486 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.142 | 0.000 | 0.514 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.142 | 0.000 | 0.508 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.142 | 0.000 | 0.514 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.142 | 0.000 | 0.507 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.086 | 0.000 | 0.503 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.086 | 0.000 | 0.503 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.086 | 0.000 | 0.513 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.086 | 0.000 | 0.513 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.155 | 0.000 | 0.537 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.155 | 0.000 | 0.531 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.155 | 0.000 | 0.537 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.155 | 0.000 | 0.530 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.093 | 0.000 | 0.526 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.093 | 0.000 | 0.526 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.093 | 0.000 | 0.536 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.093 | 0.000 | 0.536 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.165 | 0.000 | 0.558 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.165 | 0.000 | 0.552 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.165 | 0.000 | 0.558 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.165 | 0.000 | 0.552 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.100 | 0.000 | 0.548 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.100 | 0.000 | 0.547 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.100 | 0.000 | 0.557 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.100 | 0.000 | 0.557 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.175 | 0.000 | 0.577 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.174 | 0.000 | 0.570 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.175 | 0.000 | 0.577 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.174 | 0.000 | 0.570 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.105 | 0.000 | 0.566 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.105 | 0.000 | 0.566 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.105 | 0.000 | 0.575 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.105 | 0.000 | 0.575 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.183 | 0.000 | 0.595 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.183 | 0.000 | 0.588 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.183 | 0.000 | 0.595 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.183 | 0.000 | 0.588 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.110 | 0.000 | 0.584 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.110 | 0.000 | 0.584 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.110 | 0.000 | 0.593 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.110 | 0.000 | 0.593 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.191 | 0.000 | 0.611 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.191 | 0.000 | 0.604 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.191 | 0.000 | 0.611 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.191 | 0.000 | 0.604 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.115 | 0.000 | 0.600 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.115 | 0.000 | 0.600 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.115 | 0.000 | 0.609 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.115 | 0.000 | 0.609 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.198 | 0.000 | 0.623 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.198 | 0.000 | 0.618 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.198 | 0.000 | 0.623 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.198 | 0.000 | 0.618 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.119 | 0.000 | 0.614 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.119 | 0.000 | 0.615 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.119 | 0.000 | 0.622 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.119 | 0.000 | 0.622 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 604.09 | 19155.52 | 01-JAN-00:15 | 19155.52 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1742.51 | 19536.05 | 16-FEB-03:15 | 106192.26 | 10-SEP-15:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
ElectricityPurchased:Plant | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
Cogeneration:ElectricityPurchased | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
ElectricityNet:Plant | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
Cogeneration:ElectricityNet | 3570.48 | 57096.53 | 16-FEB-03:15 | 195062.84 | 10-AUG-20:00 |
ExteriorLights:Electricity | 168.41 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.41 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 604.09 | 19155.52 | 01-JAN-00:15 | 19155.52 | 01-JAN-00:15 |
Cooling:Electricity | 1107.49 | 0.00 | 01-JAN-06:15 | 86232.69 | 10-SEP-15:15 |
Heating:Electricity | 10.11 | 0.00 | 01-JAN-00:15 | 28235.03 | 05-FEB-07:15 |
Electricity:Plant | 112.06 | 36.93 | 01-JAN-06:45 | 5312.47 | 28-APR-16:00 |
HeatRejection:Electricity | 55.24 | 0.00 | 01-JAN-06:45 | 3451.82 | 28-APR-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 56.82 | 36.93 | 01-JAN-06:45 | 1860.65 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 907.21 | 9260.51 | 01-JAN-00:15 | 179729.28 | 05-FEB-07:15 |
Gas:Plant | 907.21 | 9260.51 | 01-JAN-00:15 | 179729.28 | 05-FEB-07:15 |
WaterSystems:Gas | 894.05 | 9260.51 | 01-JAN-00:15 | 80070.66 | 22-JAN-08:00 |
Water Heater:WaterSystems:Gas | 894.05 | 9260.51 | 01-JAN-00:15 | 80070.66 | 22-JAN-08:00 |
Heating:Gas | 13.16 | 0.00 | 01-JAN-00:15 | 100597.46 | 05-FEB-07:15 |
Boiler:Heating:Gas | 13.16 | 0.00 | 01-JAN-00:15 | 100597.46 | 05-FEB-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 4974.32 | 0.00 | 01-JAN-06:15 | 428359.87 | 10-AUG-20:15 |
PlantLoopCoolingDemand:HVAC | 4974.32 | 0.00 | 01-JAN-06:15 | 428359.87 | 10-AUG-20:15 |
CoolingCoils:PlantLoopCoolingDemand | 4974.32 | 0.00 | 01-JAN-06:15 | 428359.87 | 10-AUG-20:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 7555.94 | 0.00 | 03-JAN-04:00 | 0.00 | 09-SEP-17:15 |
Water:Plant | 7555.94 | 0.00 | 03-JAN-04:00 | 0.00 | 09-SEP-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 7555.94 | 0.00 | 03-JAN-04:00 | 0.00 | 09-SEP-17:15 |
MainsWater:Plant | 7555.94 | 0.00 | 03-JAN-04:00 | 0.00 | 09-SEP-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:30 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 2777.43 | 0.00 | 01-JAN-06:45 | 0.00 | 30-AUG-16:15 |
HeatRejection:MainsWater | 2777.43 | 0.00 | 01-JAN-06:45 | 0.00 | 30-AUG-16:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 704.03 | 362.54 | 24-JUL-01:15 | 129453.45 | 05-FEB-07:15 |
PlantLoopHeatingDemand:Plant | 677.27 | 362.54 | 24-JUL-01:15 | 46852.93 | 24-JAN-07:15 |
WaterSystems:PlantLoopHeatingDemand | 677.27 | 362.54 | 24-JUL-01:15 | 46852.93 | 24-JAN-07:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 6766.07 | 5617.16 | 04-MAR-03:45 | 516123.60 | 10-SEP-16:15 |
EnergyTransfer:Building | 2110.70 | 3447.73 | 15-FEB-22:15 | 191304.41 | 30-AUG-16:15 |
EnergyTransfer:Zone:G SW APARTMENT | 21.52 | 0.01 | 11-MAR-19:00 | 3090.24 | 30-AUG-15:30 |
Heating:EnergyTransfer | 40.01 | 0.00 | 01-JAN-12:45 | 63984.04 | 05-FEB-07:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.81 | 0.00 | 01-JAN-09:30 | 1066.97 | 20-DEC-07:30 |
Cooling:EnergyTransfer | 2070.68 | 0.00 | 08-JAN-09:30 | 191304.41 | 30-AUG-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 20.71 | 0.00 | 01-JAN-00:15 | 3090.24 | 30-AUG-15:30 |
EnergyTransfer:Zone:G NW APARTMENT | 17.67 | 0.00 | 05-DEC-11:15 | 2836.41 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.41 | 0.00 | 01-JAN-11:45 | 1252.26 | 05-FEB-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 16.26 | 0.00 | 01-JAN-00:15 | 2836.41 | 12-JUN-17:15 |
EnergyTransfer:Zone:OFFICE | 27.13 | 0.03 | 25-FEB-02:45 | 3438.98 | 01-SEP-11:00 |
Heating:EnergyTransfer:Zone:OFFICE | 0.60 | 0.00 | 01-JAN-07:30 | 1273.85 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 26.53 | 0.00 | 01-JAN-00:15 | 3438.98 | 01-SEP-11:00 |
EnergyTransfer:Zone:G NE APARTMENT | 17.58 | 0.06 | 09-NOV-24:00 | 2137.21 | 28-JUN-10:30 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.19 | 0.00 | 01-JAN-05:15 | 1174.38 | 20-DEC-07:30 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 16.39 | 0.00 | 01-JAN-00:15 | 2137.21 | 28-JUN-10:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 12.51 | 0.01 | 28-OCT-18:30 | 1418.14 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 775.06 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 12.04 | 0.00 | 01-JAN-08:00 | 1418.14 | 12-JUN-17:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 12.52 | 0.01 | 23-NOV-15:30 | 1406.22 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 775.15 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 12.05 | 0.00 | 01-JAN-07:45 | 1406.22 | 12-JUN-17:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 16.65 | 0.00 | 08-DEC-21:15 | 2053.87 | 01-JAN-14:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 549.13 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 16.53 | 0.00 | 01-JAN-06:15 | 2053.87 | 01-JAN-14:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 16.90 | 0.02 | 15-APR-17:45 | 2100.41 | 01-JAN-14:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 500.36 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 16.78 | 0.00 | 01-JAN-06:15 | 2100.41 | 01-JAN-14:00 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 31.81 | 0.06 | 11-FEB-02:45 | 3788.31 | 06-NOV-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 871.28 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 31.45 | 0.00 | 01-JAN-06:15 | 3788.31 | 06-NOV-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 25.32 | 0.00 | 29-OCT-04:30 | 3315.58 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 1034.23 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 24.47 | 0.00 | 01-JAN-04:30 | 3315.58 | 12-JUN-17:15 |
EnergyTransfer:Zone:F2 SE APARTMENT | 33.18 | 0.16 | 12-APR-01:15 | 3379.29 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 877.48 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 32.90 | 0.00 | 01-JAN-06:15 | 3379.29 | 06-NOV-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 25.38 | 0.02 | 23-JAN-14:15 | 2577.30 | 13-JUN-09:45 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 0.69 | 0.00 | 01-JAN-00:15 | 1055.73 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 24.69 | 0.00 | 01-JAN-02:30 | 2577.30 | 13-JUN-09:45 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 19.49 | 0.04 | 12-MAR-05:00 | 1751.45 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 612.33 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 19.32 | 0.00 | 01-JAN-09:15 | 1751.45 | 12-JUN-17:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 19.49 | 0.03 | 20-NOV-18:45 | 1742.09 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 613.52 | 10-MAR-13:45 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 19.32 | 0.00 | 01-JAN-09:15 | 1742.09 | 12-JUN-17:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 26.08 | 0.02 | 31-MAR-05:45 | 2598.18 | 02-DEC-13:15 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 255.80 | 05-FEB-04:15 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 26.03 | 0.00 | 01-JAN-06:15 | 2598.18 | 02-DEC-13:15 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 26.19 | 0.01 | 17-JAN-08:45 | 2617.34 | 02-DEC-13:15 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 107.04 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 26.15 | 0.00 | 01-JAN-06:15 | 2617.34 | 02-DEC-13:15 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 33.39 | 0.00 | 06-FEB-23:45 | 3833.16 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 859.14 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 33.08 | 0.00 | 01-JAN-06:15 | 3833.16 | 06-NOV-15:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 26.69 | 0.02 | 07-DEC-05:15 | 3334.26 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 1042.45 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 25.95 | 0.00 | 01-JAN-06:15 | 3334.26 | 12-JUN-17:15 |
EnergyTransfer:Zone:F3 SE APARTMENT | 33.62 | 0.08 | 02-APR-01:15 | 3345.82 | 10-DEC-13:45 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 874.89 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 33.39 | 0.00 | 01-JAN-06:15 | 3345.82 | 10-DEC-13:45 |
EnergyTransfer:Zone:F3 NE APARTMENT | 26.75 | 0.04 | 20-NOV-03:30 | 2585.47 | 13-JUN-09:45 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 1062.13 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 26.16 | 0.00 | 01-JAN-06:15 | 2585.47 | 13-JUN-09:45 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 21.03 | 0.00 | 28-OCT-19:00 | 1784.74 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 663.43 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 20.91 | 0.00 | 01-JAN-09:15 | 1784.74 | 12-JUN-17:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 21.03 | 0.02 | 22-DEC-12:15 | 1775.40 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 666.41 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 20.91 | 0.00 | 01-JAN-09:15 | 1775.40 | 12-JUN-17:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 28.06 | 0.05 | 04-APR-07:00 | 2642.02 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 114.70 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 28.03 | 0.00 | 01-JAN-06:15 | 2642.02 | 02-DEC-13:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 28.09 | 0.00 | 20-MAR-10:15 | 2651.00 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 115.93 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 28.06 | 0.00 | 01-JAN-06:15 | 2651.00 | 02-DEC-13:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 33.56 | 0.08 | 07-DEC-04:45 | 3845.08 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.32 | 0.00 | 01-JAN-00:15 | 908.94 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 33.24 | 0.00 | 01-JAN-06:15 | 3845.08 | 06-NOV-15:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 26.99 | 0.00 | 04-MAR-06:45 | 3341.23 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 0.75 | 0.00 | 01-JAN-00:15 | 1098.38 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 26.24 | 0.00 | 01-JAN-06:15 | 3341.23 | 12-JUN-17:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 33.64 | 0.01 | 02-MAR-02:15 | 3351.81 | 01-JAN-14:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.24 | 0.00 | 01-JAN-00:15 | 928.32 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 33.41 | 0.00 | 01-JAN-06:15 | 3351.81 | 01-JAN-14:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 27.05 | 0.02 | 10-NOV-02:45 | 2598.26 | 08-JUL-11:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 0.61 | 0.00 | 01-JAN-00:15 | 1115.42 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 26.45 | 0.00 | 01-JAN-06:15 | 2598.26 | 08-JUL-11:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 21.44 | 0.02 | 27-NOV-21:45 | 1805.60 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 769.35 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 21.31 | 0.00 | 01-JAN-09:15 | 1805.60 | 12-JUN-17:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 21.44 | 0.01 | 14-NOV-10:00 | 1796.32 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 776.65 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 21.31 | 0.00 | 01-JAN-09:15 | 1796.32 | 12-JUN-17:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 28.41 | 0.06 | 08-APR-06:45 | 2655.68 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 124.17 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 28.38 | 0.00 | 01-JAN-06:15 | 2655.68 | 02-DEC-13:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 28.42 | 0.02 | 17-NOV-20:15 | 2663.05 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 125.07 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 28.39 | 0.00 | 01-JAN-06:15 | 2663.05 | 02-DEC-13:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 34.03 | 0.18 | 08-MAR-03:30 | 3879.12 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 957.19 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 33.70 | 0.00 | 01-JAN-06:15 | 3879.12 | 06-NOV-15:30 |
EnergyTransfer:Zone:M NW APARTMENT | 27.58 | 0.06 | 21-MAR-19:30 | 3369.95 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.78 | 0.00 | 01-JAN-00:15 | 1146.69 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 26.80 | 0.00 | 01-JAN-06:15 | 3369.95 | 12-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 34.09 | 0.03 | 31-JAN-21:15 | 3367.99 | 01-JAN-14:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 977.52 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 33.84 | 0.00 | 01-JAN-06:15 | 3367.99 | 01-JAN-14:00 |
EnergyTransfer:Zone:M NE APARTMENT | 27.63 | 0.04 | 05-MAR-05:15 | 2628.48 | 13-JUN-09:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.63 | 0.00 | 01-JAN-00:15 | 1161.43 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 27.00 | 0.00 | 01-JAN-06:15 | 2628.48 | 13-JUN-09:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 22.07 | 0.00 | 16-APR-06:30 | 1848.39 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 846.38 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 21.94 | 0.00 | 01-JAN-09:15 | 1848.39 | 12-JUN-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 22.07 | 0.05 | 29-NOV-21:30 | 1839.15 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 850.71 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 21.94 | 0.00 | 01-JAN-09:15 | 1839.15 | 12-JUN-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 28.99 | 0.01 | 15-FEB-08:00 | 2689.79 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 131.23 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 28.95 | 0.00 | 01-JAN-06:15 | 2689.79 | 02-DEC-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 29.00 | 0.00 | 09-NOV-20:00 | 2696.89 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 132.09 | 16-FEB-06:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 28.97 | 0.00 | 01-JAN-06:15 | 2696.89 | 02-DEC-13:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 32.96 | 0.08 | 09-FEB-11:15 | 3839.32 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1057.81 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 32.58 | 0.00 | 01-JAN-06:15 | 3839.32 | 06-NOV-15:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 26.87 | 0.02 | 18-OCT-04:45 | 3330.81 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 0.90 | 0.00 | 01-JAN-00:15 | 1237.69 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 25.96 | 0.00 | 01-JAN-06:15 | 3330.81 | 12-JUN-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 33.01 | 0.03 | 08-APR-13:30 | 3321.48 | 06-NOV-14:15 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 1076.15 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 32.72 | 0.00 | 01-JAN-06:15 | 3321.48 | 06-NOV-14:15 |
EnergyTransfer:Zone:F6 NE APARTMENT | 26.90 | 0.00 | 20-NOV-04:45 | 2591.26 | 13-JUN-09:45 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 1250.93 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 26.15 | 0.00 | 01-JAN-06:15 | 2591.26 | 13-JUN-09:45 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 21.33 | 0.00 | 10-APR-11:15 | 1818.74 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 986.38 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 21.15 | 0.00 | 01-JAN-09:15 | 1818.74 | 12-JUN-17:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 21.33 | 0.01 | 27-NOV-21:00 | 1809.61 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 992.03 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 21.15 | 0.00 | 01-JAN-09:15 | 1809.61 | 12-JUN-17:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 27.92 | 0.02 | 02-JAN-21:15 | 2649.96 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 200.82 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 27.88 | 0.00 | 01-JAN-06:15 | 2649.96 | 02-DEC-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 27.94 | 0.01 | 13-NOV-20:45 | 2657.01 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 195.01 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 27.89 | 0.00 | 01-JAN-06:15 | 2657.01 | 02-DEC-13:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 32.43 | 0.01 | 02-FEB-21:15 | 3825.61 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.42 | 0.00 | 01-JAN-00:15 | 1136.18 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 32.01 | 0.00 | 01-JAN-06:15 | 3825.61 | 06-NOV-15:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 26.62 | 0.06 | 23-MAR-22:45 | 3316.58 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 1.01 | 0.00 | 01-JAN-00:15 | 1308.34 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 25.60 | 0.00 | 01-JAN-05:00 | 3316.58 | 12-JUN-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 32.48 | 0.07 | 02-MAR-01:45 | 3311.17 | 06-NOV-14:15 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 1151.92 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 32.15 | 0.00 | 01-JAN-06:15 | 3311.17 | 06-NOV-14:15 |
EnergyTransfer:Zone:F7 NE APARTMENT | 26.63 | 0.01 | 11-DEC-09:00 | 2580.10 | 13-JUN-09:45 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 1320.68 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 25.78 | 0.00 | 01-JAN-06:15 | 2580.10 | 13-JUN-09:45 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 21.04 | 0.05 | 08-APR-18:15 | 1814.22 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1077.21 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 20.81 | 0.00 | 01-JAN-09:00 | 1814.22 | 12-JUN-17:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 21.04 | 0.05 | 10-APR-11:15 | 1805.16 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 1077.87 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 20.81 | 0.00 | 01-JAN-09:00 | 1805.16 | 12-JUN-17:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 27.41 | 0.00 | 21-FEB-07:00 | 2636.06 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 391.79 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 27.36 | 0.00 | 01-JAN-06:15 | 2636.06 | 02-DEC-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 27.42 | 0.00 | 05-FEB-04:30 | 2643.07 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 385.35 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 27.37 | 0.00 | 01-JAN-06:15 | 2643.07 | 02-DEC-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 32.18 | 0.09 | 21-MAR-14:45 | 3825.31 | 06-NOV-15:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 1209.37 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 31.71 | 0.00 | 01-JAN-06:15 | 3825.31 | 06-NOV-15:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 26.61 | 0.02 | 14-NOV-19:00 | 3316.42 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 1.13 | 0.00 | 01-JAN-00:15 | 1381.46 | 05-FEB-08:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 25.49 | 0.00 | 01-JAN-05:00 | 3316.42 | 12-JUN-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 32.22 | 0.03 | 12-MAR-18:15 | 3314.98 | 06-NOV-14:15 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 1221.92 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 31.84 | 0.00 | 01-JAN-06:15 | 3314.98 | 06-NOV-14:15 |
EnergyTransfer:Zone:F8 NE APARTMENT | 26.62 | 0.02 | 14-NOV-05:30 | 2582.41 | 28-JUN-10:30 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1391.21 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 25.66 | 0.00 | 01-JAN-06:15 | 2582.41 | 28-JUN-10:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 20.99 | 0.02 | 18-NOV-20:00 | 1824.60 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1178.46 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 20.70 | 0.00 | 01-JAN-09:00 | 1824.60 | 12-JUN-17:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 20.99 | 0.01 | 16-APR-09:45 | 1815.63 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1176.87 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 20.70 | 0.00 | 01-JAN-09:00 | 1815.63 | 12-JUN-17:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 27.14 | 0.00 | 09-APR-09:15 | 2636.10 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 564.33 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 27.08 | 0.00 | 01-JAN-06:15 | 2636.10 | 02-DEC-13:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 27.16 | 0.01 | 24-MAR-21:00 | 2643.07 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 556.97 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 27.09 | 0.00 | 01-JAN-06:15 | 2643.07 | 02-DEC-13:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 32.52 | 0.01 | 10-FEB-02:45 | 3864.01 | 06-NOV-15:15 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 0.58 | 0.00 | 01-JAN-00:15 | 1343.67 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 31.94 | 0.00 | 01-JAN-06:15 | 3864.01 | 06-NOV-15:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 27.31 | 0.01 | 20-JAN-11:45 | 3402.31 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 1.35 | 0.00 | 01-JAN-00:15 | 1546.13 | 05-FEB-08:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 25.95 | 0.00 | 01-JAN-04:45 | 3402.31 | 12-JUN-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 32.54 | 0.01 | 16-MAR-01:45 | 3349.83 | 06-NOV-14:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 0.47 | 0.00 | 01-JAN-00:15 | 1357.46 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 32.07 | 0.00 | 01-JAN-06:15 | 3349.83 | 06-NOV-14:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 27.27 | 0.00 | 07-DEC-24:00 | 2621.49 | 28-JUN-10:30 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 1.15 | 0.00 | 01-JAN-00:15 | 1549.38 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 26.12 | 0.00 | 01-JAN-04:45 | 2621.49 | 28-JUN-10:30 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 21.51 | 0.02 | 01-DEC-16:45 | 1903.99 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 1300.78 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 21.12 | 0.00 | 01-JAN-06:15 | 1903.99 | 12-JUN-17:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 21.51 | 0.00 | 07-DEC-22:00 | 1896.25 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 1302.20 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 21.12 | 0.00 | 01-JAN-06:15 | 1896.25 | 12-JUN-17:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 27.37 | 0.03 | 21-NOV-07:00 | 2680.83 | 02-DEC-13:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 763.89 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 27.28 | 0.00 | 01-JAN-06:15 | 2680.83 | 02-DEC-13:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 27.39 | 0.01 | 11-APR-09:45 | 2688.31 | 02-DEC-13:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 755.92 | 20-MAR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 27.29 | 0.00 | 01-JAN-06:15 | 2688.31 | 02-DEC-13:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 34.57 | 0.02 | 15-NOV-24:00 | 4560.64 | 06-NOV-14:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.71 | 0.00 | 01-JAN-00:15 | 2108.53 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 32.86 | 0.00 | 01-JAN-02:00 | 4560.64 | 06-NOV-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 29.87 | 0.01 | 24-JAN-21:45 | 4134.98 | 12-JUN-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.74 | 0.00 | 01-JAN-00:15 | 2236.72 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 27.13 | 0.00 | 01-JAN-00:30 | 4134.98 | 12-JUN-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 34.29 | 0.04 | 12-DEC-09:00 | 3968.94 | 06-NOV-14:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.48 | 0.00 | 01-JAN-00:15 | 2120.36 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 32.81 | 0.00 | 01-JAN-02:00 | 3968.94 | 06-NOV-14:15 |
EnergyTransfer:Zone:T NE APARTMENT | 29.43 | 0.01 | 02-MAR-19:15 | 3219.01 | 08-JUL-11:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.33 | 0.00 | 01-JAN-00:15 | 2243.94 | 05-FEB-07:15 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 27.09 | 0.00 | 01-JAN-00:30 | 3219.01 | 08-JUL-11:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 23.20 | 0.13 | 21-FEB-02:15 | 2464.98 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.06 | 0.00 | 01-JAN-00:15 | 1480.45 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 22.14 | 0.00 | 01-JAN-06:15 | 2464.98 | 12-JUN-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 23.21 | 0.01 | 05-MAR-01:00 | 2443.83 | 12-JUN-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.07 | 0.00 | 01-JAN-00:15 | 1477.49 | 23-DEC-11:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 22.15 | 0.00 | 01-JAN-06:15 | 2443.83 | 12-JUN-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 28.47 | 0.08 | 02-MAR-04:15 | 3261.31 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.50 | 0.00 | 01-JAN-00:15 | 1148.69 | 28-DEC-21:15 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 27.98 | 0.00 | 01-JAN-06:15 | 3261.31 | 02-DEC-13:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 28.49 | 0.03 | 05-MAR-06:00 | 3268.06 | 02-DEC-13:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.50 | 0.00 | 01-JAN-00:15 | 1151.93 | 28-DEC-21:15 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 27.99 | 0.00 | 01-JAN-06:15 | 3268.06 | 02-DEC-13:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 687.76 | 362.54 | 24-JUL-01:15 | 127058.01 | 05-FEB-07:15 |
WaterSystems:EnergyTransfer | 677.26 | 362.54 | 24-JUL-01:15 | 46848.14 | 24-JAN-07:15 |
sub cat:WaterSystems:EnergyTransfer | 677.26 | 362.54 | 24-JUL-01:15 | 46848.14 | 24-JAN-07:15 |
EnergyTransfer:HVAC | 3967.61 | 0.00 | 01-JAN-06:45 | 344274.85 | 10-AUG-20:15 |
CoolingCoils:EnergyTransfer | 3932.83 | 0.00 | 01-JAN-06:15 | 344274.85 | 10-AUG-20:15 |
HeatingCoils:EnergyTransfer | 34.78 | 0.00 | 01-JAN-00:15 | 107767.96 | 05-FEB-07:15 |
PlantLoopHeatingDemand:HVAC | 26.76 | 0.00 | 01-JAN-00:15 | 82868.65 | 05-FEB-07:15 |
HeatingCoils:PlantLoopHeatingDemand | 26.76 | 0.00 | 01-JAN-00:15 | 82868.65 | 05-FEB-07:15 |
Boilers:EnergyTransfer | 10.49 | 0.00 | 01-JAN-00:15 | 80477.97 | 05-FEB-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.815 | -20.709 | 0.000 | 0.000 | 3.629 | 2.413 | 12.213 | 23.105 | 0.000 | 0.684 | 0.000 | 0.000 | -5.415 | 0.000 | -4.066 | -12.669 |
G NW APARTMENT | 1.415 | -16.259 | 0.000 | 0.000 | 3.663 | 2.413 | 12.213 | 14.478 | 0.000 | 0.681 | 0.000 | 0.000 | -5.379 | 0.000 | -3.517 | -9.707 |
OFFICE | 0.605 | -26.527 | 0.000 | 0.000 | 0.504 | 21.954 | 7.547 | 23.057 | 0.000 | 0.318 | 0.000 | 0.000 | -5.422 | 0.000 | -0.802 | -21.234 |
G NE APARTMENT | 1.190 | -16.390 | 0.000 | 0.000 | 3.673 | 2.413 | 12.213 | 14.500 | 0.000 | 0.680 | 0.000 | 0.000 | -5.159 | 0.000 | -3.492 | -9.629 |
G N1 APARTMENT | 0.471 | -12.043 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 6.231 | 0.000 | 0.547 | 0.000 | 0.000 | -3.252 | 0.000 | -2.905 | -7.354 |
G N2 APARTMENT | 0.474 | -12.050 | 0.000 | 0.000 | 3.679 | 2.413 | 12.213 | 6.229 | 0.000 | 0.546 | 0.000 | 0.000 | -3.249 | 0.000 | -2.903 | -7.353 |
G S1 APARTMENT | 0.118 | -16.533 | 0.000 | 0.000 | 3.625 | 2.413 | 12.213 | 14.940 | 0.000 | 0.551 | 0.000 | 0.000 | -3.275 | 0.000 | -3.633 | -10.419 |
G S2 APARTMENT | 0.122 | -16.782 | 0.000 | 0.000 | 3.623 | 2.413 | 12.213 | 14.929 | 0.000 | 0.552 | 0.000 | 0.000 | -3.283 | 0.000 | -3.657 | -10.130 |
F2 SW APARTMENT | 0.366 | -31.445 | 0.000 | 0.000 | 3.571 | 2.413 | 12.213 | 22.095 | 0.000 | 0.879 | 1.130 | 0.000 | -6.085 | 0.000 | -5.136 | -0.000 |
F2 NW APARTMENT | 0.854 | -24.466 | 0.000 | 0.000 | 3.616 | 2.413 | 12.213 | 13.737 | 0.000 | 0.873 | 1.380 | 0.000 | -6.034 | 0.000 | -4.586 | -0.000 |
F2 SE APARTMENT | 0.282 | -32.896 | 0.000 | 0.000 | 3.570 | 2.413 | 12.213 | 22.167 | 0.000 | 0.875 | 2.586 | 0.000 | -6.021 | 0.000 | -5.189 | -0.000 |
F2 NE APARTMENT | 0.686 | -24.688 | 0.000 | 0.000 | 3.625 | 2.413 | 12.213 | 13.732 | 0.000 | 0.872 | 1.480 | 0.000 | -5.778 | 0.000 | -4.555 | -0.000 |
F2 N1 APARTMENT | 0.171 | -19.318 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 5.830 | 0.000 | 0.674 | 1.994 | 0.000 | -3.717 | 0.000 | -3.882 | -0.000 |
F2 N2 APARTMENT | 0.169 | -19.321 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 5.828 | 0.000 | 0.673 | 1.995 | 0.000 | -3.714 | 0.000 | -3.880 | -0.000 |
F2 S1 APARTMENT | 0.041 | -26.033 | 0.000 | 0.000 | 3.560 | 2.413 | 12.213 | 14.278 | 0.000 | 0.678 | 1.160 | 0.000 | -3.692 | 0.000 | -4.617 | -0.000 |
F2 S2 APARTMENT | 0.043 | -26.148 | 0.000 | 0.000 | 3.559 | 2.413 | 12.213 | 14.276 | 0.000 | 0.679 | 1.284 | 0.000 | -3.695 | 0.000 | -4.623 | -0.000 |
F3 SW APARTMENT | 0.310 | -33.078 | 0.000 | 0.000 | 3.563 | 2.413 | 12.213 | 21.644 | 0.000 | 1.028 | 3.745 | 0.000 | -6.235 | 0.000 | -5.602 | -0.000 |
F3 NW APARTMENT | 0.739 | -25.947 | 0.000 | 0.000 | 3.607 | 2.413 | 12.213 | 13.440 | 0.000 | 1.022 | 3.800 | 0.000 | -6.216 | 0.000 | -5.069 | 0.000 |
F3 SE APARTMENT | 0.229 | -33.393 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 21.738 | 0.000 | 1.019 | 3.953 | 0.000 | -6.125 | 0.000 | -5.612 | -0.000 |
F3 NE APARTMENT | 0.591 | -26.161 | 0.000 | 0.000 | 3.615 | 2.413 | 12.213 | 13.425 | 0.000 | 1.019 | 3.876 | 0.000 | -5.952 | 0.000 | -5.038 | 0.000 |
F3 N1 APARTMENT | 0.123 | -20.911 | 0.000 | 0.000 | 3.607 | 2.413 | 12.213 | 5.694 | 0.000 | 0.775 | 4.264 | 0.000 | -3.859 | 0.000 | -4.319 | 0.000 |
F3 N2 APARTMENT | 0.123 | -20.912 | 0.000 | 0.000 | 3.608 | 2.413 | 12.213 | 5.692 | 0.000 | 0.774 | 4.262 | 0.000 | -3.856 | 0.000 | -4.317 | 0.000 |
F3 S1 APARTMENT | 0.030 | -28.029 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 13.983 | 0.000 | 0.785 | 3.868 | 0.000 | -3.793 | 0.000 | -5.018 | -0.000 |
F3 S2 APARTMENT | 0.030 | -28.062 | 0.000 | 0.000 | 3.549 | 2.413 | 12.213 | 13.982 | 0.000 | 0.785 | 3.903 | 0.000 | -3.793 | 0.000 | -5.020 | -0.000 |
F4 SW APARTMENT | 0.317 | -33.241 | 0.000 | 0.000 | 3.563 | 2.413 | 12.213 | 21.341 | 0.000 | 1.113 | 4.490 | 0.000 | -6.294 | 0.000 | -5.915 | -0.001 |
F4 NW APARTMENT | 0.753 | -26.239 | 0.000 | 0.000 | 3.606 | 2.413 | 12.213 | 13.254 | 0.000 | 1.106 | 4.566 | 0.000 | -6.295 | 0.000 | -5.376 | 0.000 |
F4 SE APARTMENT | 0.236 | -33.406 | 0.000 | 0.000 | 3.566 | 2.413 | 12.213 | 21.436 | 0.000 | 1.103 | 4.532 | 0.000 | -6.175 | 0.000 | -5.919 | -0.000 |
F4 NE APARTMENT | 0.605 | -26.448 | 0.000 | 0.000 | 3.614 | 2.413 | 12.213 | 13.232 | 0.000 | 1.103 | 4.638 | 0.000 | -6.026 | 0.000 | -5.343 | 0.000 |
F4 N1 APARTMENT | 0.126 | -21.314 | 0.000 | 0.000 | 3.604 | 2.413 | 12.213 | 5.615 | 0.000 | 0.829 | 5.017 | 0.000 | -3.923 | 0.000 | -4.580 | 0.000 |
F4 N2 APARTMENT | 0.125 | -21.314 | 0.000 | 0.000 | 3.604 | 2.413 | 12.213 | 5.614 | 0.000 | 0.828 | 5.015 | 0.000 | -3.920 | 0.000 | -4.577 | 0.000 |
F4 S1 APARTMENT | 0.031 | -28.375 | 0.000 | 0.000 | 3.547 | 2.413 | 12.213 | 13.788 | 0.000 | 0.841 | 4.646 | 0.000 | -3.833 | 0.000 | -5.272 | -0.000 |
F4 S2 APARTMENT | 0.032 | -28.391 | 0.000 | 0.000 | 3.548 | 2.413 | 12.213 | 13.787 | 0.000 | 0.842 | 4.662 | 0.000 | -3.832 | 0.000 | -5.273 | -0.000 |
M SW APARTMENT | 0.330 | -33.695 | 0.000 | 0.000 | 3.563 | 2.413 | 12.213 | 21.091 | 0.000 | 1.180 | 5.444 | 0.000 | -6.349 | 0.000 | -6.189 | -0.000 |
M NW APARTMENT | 0.778 | -26.801 | 0.000 | 0.000 | 3.606 | 2.413 | 12.213 | 13.098 | 0.000 | 1.172 | 5.527 | 0.000 | -6.364 | 0.000 | -5.642 | 0.000 |
M SE APARTMENT | 0.250 | -33.838 | 0.000 | 0.000 | 3.567 | 2.413 | 12.213 | 21.183 | 0.000 | 1.169 | 5.462 | 0.000 | -6.227 | 0.000 | -6.191 | -0.000 |
M NE APARTMENT | 0.629 | -27.003 | 0.000 | 0.000 | 3.613 | 2.413 | 12.213 | 13.070 | 0.000 | 1.168 | 5.597 | 0.000 | -6.091 | 0.000 | -5.610 | 0.000 |
M N1 APARTMENT | 0.136 | -21.937 | 0.000 | 0.000 | 3.602 | 2.413 | 12.213 | 5.549 | 0.000 | 0.871 | 5.935 | 0.000 | -3.976 | 0.000 | -4.806 | 0.000 |
M N2 APARTMENT | 0.135 | -21.938 | 0.000 | 0.000 | 3.602 | 2.413 | 12.213 | 5.548 | 0.000 | 0.869 | 5.934 | 0.000 | -3.973 | 0.000 | -4.803 | 0.000 |
M S1 APARTMENT | 0.036 | -28.953 | 0.000 | 0.000 | 3.547 | 2.413 | 12.213 | 13.628 | 0.000 | 0.885 | 5.597 | 0.000 | -3.869 | 0.000 | -5.496 | -0.000 |
M S2 APARTMENT | 0.037 | -28.966 | 0.000 | 0.000 | 3.547 | 2.413 | 12.213 | 13.627 | 0.000 | 0.886 | 5.608 | 0.000 | -3.868 | 0.000 | -5.497 | -0.000 |
F6 SW APARTMENT | 0.373 | -32.581 | 0.000 | 0.000 | 3.568 | 2.413 | 12.213 | 20.920 | 0.000 | 1.253 | 4.546 | 0.000 | -6.338 | 0.000 | -6.366 | -0.000 |
F6 NW APARTMENT | 0.902 | -25.963 | 0.000 | 0.000 | 3.612 | 2.413 | 12.213 | 13.011 | 0.000 | 1.245 | 4.695 | 0.000 | -6.350 | 0.000 | -5.777 | 0.000 |
F6 SE APARTMENT | 0.288 | -32.716 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 21.010 | 0.000 | 1.241 | 4.561 | 0.000 | -6.214 | 0.000 | -6.367 | -0.000 |
F6 NE APARTMENT | 0.744 | -26.153 | 0.000 | 0.000 | 3.620 | 2.413 | 12.213 | 12.979 | 0.000 | 1.240 | 4.764 | 0.000 | -6.075 | 0.000 | -5.744 | 0.000 |
F6 N1 APARTMENT | 0.182 | -21.146 | 0.000 | 0.000 | 3.608 | 2.413 | 12.213 | 5.520 | 0.000 | 0.922 | 5.152 | 0.000 | -3.968 | 0.000 | -4.896 | 0.000 |
F6 N2 APARTMENT | 0.181 | -21.147 | 0.000 | 0.000 | 3.609 | 2.413 | 12.213 | 5.518 | 0.000 | 0.921 | 5.150 | 0.000 | -3.965 | 0.000 | -4.893 | 0.000 |
F6 S1 APARTMENT | 0.042 | -27.881 | 0.000 | 0.000 | 3.551 | 2.413 | 12.213 | 13.518 | 0.000 | 0.936 | 4.701 | 0.000 | -3.864 | 0.000 | -5.628 | -0.000 |
F6 S2 APARTMENT | 0.043 | -27.894 | 0.000 | 0.000 | 3.551 | 2.413 | 12.213 | 13.517 | 0.000 | 0.937 | 4.712 | 0.000 | -3.863 | 0.000 | -5.629 | -0.000 |
F7 SW APARTMENT | 0.417 | -32.013 | 0.000 | 0.000 | 3.572 | 2.413 | 12.213 | 20.762 | 0.000 | 1.307 | 4.212 | 0.000 | -6.342 | 0.000 | -6.540 | -0.000 |
F7 NW APARTMENT | 1.012 | -25.603 | 0.000 | 0.000 | 3.617 | 2.413 | 12.213 | 12.924 | 0.000 | 1.298 | 4.400 | 0.000 | -6.353 | 0.000 | -5.920 | 0.000 |
F7 SE APARTMENT | 0.331 | -32.145 | 0.000 | 0.000 | 3.576 | 2.413 | 12.213 | 20.849 | 0.000 | 1.294 | 4.226 | 0.000 | -6.216 | 0.000 | -6.540 | -0.000 |
F7 NE APARTMENT | 0.850 | -25.783 | 0.000 | 0.000 | 3.624 | 2.413 | 12.213 | 12.889 | 0.000 | 1.291 | 4.466 | 0.000 | -6.077 | 0.000 | -5.887 | 0.000 |
F7 N1 APARTMENT | 0.229 | -20.813 | 0.000 | 0.000 | 3.613 | 2.413 | 12.213 | 5.488 | 0.000 | 0.957 | 4.868 | 0.000 | -3.970 | 0.000 | -4.999 | 0.000 |
F7 N2 APARTMENT | 0.228 | -20.813 | 0.000 | 0.000 | 3.614 | 2.413 | 12.213 | 5.486 | 0.000 | 0.956 | 4.867 | 0.000 | -3.967 | 0.000 | -4.996 | 0.000 |
F7 S1 APARTMENT | 0.050 | -27.356 | 0.000 | 0.000 | 3.554 | 2.413 | 12.213 | 13.416 | 0.000 | 0.974 | 4.366 | 0.000 | -3.866 | 0.000 | -5.763 | -0.000 |
F7 S2 APARTMENT | 0.051 | -27.368 | 0.000 | 0.000 | 3.555 | 2.413 | 12.213 | 13.415 | 0.000 | 0.974 | 4.376 | 0.000 | -3.865 | 0.000 | -5.764 | -0.000 |
F8 SW APARTMENT | 0.468 | -31.709 | 0.000 | 0.000 | 3.575 | 2.413 | 12.213 | 20.617 | 0.000 | 1.357 | 4.128 | 0.000 | -6.350 | 0.000 | -6.712 | -0.000 |
F8 NW APARTMENT | 1.127 | -25.485 | 0.000 | 0.000 | 3.620 | 2.413 | 12.213 | 12.842 | 0.000 | 1.347 | 4.355 | 0.000 | -6.363 | 0.000 | -6.069 | 0.000 |
F8 SE APARTMENT | 0.379 | -31.837 | 0.000 | 0.000 | 3.579 | 2.413 | 12.213 | 20.702 | 0.000 | 1.344 | 4.142 | 0.000 | -6.222 | 0.000 | -6.711 | -0.001 |
F8 NE APARTMENT | 0.961 | -25.657 | 0.000 | 0.000 | 3.628 | 2.413 | 12.213 | 12.804 | 0.000 | 1.340 | 4.417 | 0.000 | -6.085 | 0.000 | -6.033 | 0.000 |
F8 N1 APARTMENT | 0.283 | -20.704 | 0.000 | 0.000 | 3.617 | 2.413 | 12.213 | 5.456 | 0.000 | 0.990 | 4.820 | 0.000 | -3.976 | 0.000 | -5.111 | 0.000 |
F8 N2 APARTMENT | 0.282 | -20.703 | 0.000 | 0.000 | 3.618 | 2.413 | 12.213 | 5.454 | 0.000 | 0.988 | 4.817 | 0.000 | -3.973 | 0.000 | -5.108 | 0.000 |
F8 S1 APARTMENT | 0.061 | -27.081 | 0.000 | 0.000 | 3.558 | 2.413 | 12.213 | 13.324 | 0.000 | 1.009 | 4.274 | 0.000 | -3.871 | 0.000 | -5.899 | -0.000 |
F8 S2 APARTMENT | 0.062 | -27.093 | 0.000 | 0.000 | 3.558 | 2.413 | 12.213 | 13.323 | 0.000 | 1.010 | 4.284 | 0.000 | -3.870 | 0.000 | -5.900 | -0.000 |
F9 SW APARTMENT | 0.582 | -31.942 | 0.000 | 0.000 | 3.580 | 2.413 | 12.213 | 20.486 | 0.000 | 1.400 | 4.476 | 0.000 | -6.355 | 0.000 | -6.854 | -0.000 |
F9 NW APARTMENT | 1.353 | -25.953 | 0.000 | 0.000 | 3.624 | 2.413 | 12.213 | 12.760 | 0.000 | 1.390 | 4.775 | 0.000 | -6.377 | 0.000 | -6.199 | 0.000 |
F9 SE APARTMENT | 0.474 | -32.065 | 0.000 | 0.000 | 3.584 | 2.413 | 12.213 | 20.568 | 0.000 | 1.386 | 4.504 | 0.000 | -6.224 | 0.000 | -6.853 | -0.000 |
F9 NE APARTMENT | 1.155 | -26.115 | 0.000 | 0.000 | 3.632 | 2.413 | 12.213 | 12.721 | 0.000 | 1.381 | 4.853 | 0.000 | -6.095 | 0.000 | -6.159 | 0.000 |
F9 N1 APARTMENT | 0.390 | -21.116 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 5.423 | 0.000 | 1.024 | 5.220 | 0.000 | -3.981 | 0.000 | -5.209 | 0.000 |
F9 N2 APARTMENT | 0.389 | -21.116 | 0.000 | 0.000 | 3.622 | 2.413 | 12.213 | 5.422 | 0.000 | 1.023 | 5.218 | 0.000 | -3.977 | 0.000 | -5.206 | 0.000 |
F9 S1 APARTMENT | 0.090 | -27.280 | 0.000 | 0.000 | 3.563 | 2.413 | 12.213 | 13.243 | 0.000 | 1.043 | 4.593 | 0.000 | -3.871 | 0.000 | -6.006 | -0.000 |
F9 S2 APARTMENT | 0.092 | -27.293 | 0.000 | 0.000 | 3.563 | 2.413 | 12.213 | 13.242 | 0.000 | 1.044 | 4.603 | 0.000 | -3.870 | 0.000 | -6.006 | -0.000 |
T SW APARTMENT | 1.714 | -32.854 | 0.000 | 0.000 | 3.607 | 2.413 | 12.213 | 20.105 | 0.000 | 1.433 | 4.288 | 0.000 | -6.065 | 0.000 | -6.854 | -0.000 |
T NW APARTMENT | 2.737 | -27.131 | 0.000 | 0.000 | 3.639 | 2.413 | 12.213 | 12.431 | 0.000 | 1.421 | 4.723 | 0.000 | -6.147 | 0.000 | -6.299 | -0.000 |
T SE APARTMENT | 1.481 | -32.807 | 0.000 | 0.000 | 3.613 | 2.413 | 12.213 | 20.194 | 0.000 | 1.423 | 4.276 | 0.000 | -5.943 | 0.000 | -6.863 | -0.000 |
T NE APARTMENT | 2.332 | -27.093 | 0.000 | 0.000 | 3.649 | 2.413 | 12.213 | 12.424 | 0.000 | 1.419 | 4.795 | 0.000 | -5.891 | 0.000 | -6.260 | -0.000 |
T N1 APARTMENT | 1.063 | -22.139 | 0.000 | 0.000 | 3.640 | 2.413 | 12.213 | 5.304 | 0.000 | 1.083 | 5.514 | 0.000 | -3.821 | 0.000 | -5.270 | -0.000 |
T N2 APARTMENT | 1.065 | -22.147 | 0.000 | 0.000 | 3.641 | 2.413 | 12.213 | 5.302 | 0.000 | 1.083 | 5.516 | 0.000 | -3.816 | 0.000 | -5.270 | -0.000 |
T S1 APARTMENT | 0.498 | -27.974 | 0.000 | 0.000 | 3.594 | 2.413 | 12.213 | 13.044 | 0.000 | 1.095 | 4.817 | 0.000 | -3.717 | 0.000 | -5.983 | -0.000 |
T S2 APARTMENT | 0.502 | -27.990 | 0.000 | 0.000 | 3.594 | 2.413 | 12.213 | 13.042 | 0.000 | 1.095 | 4.829 | 0.000 | -3.714 | 0.000 | -5.985 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 5.206 | 0.000 | 5.514 | 0.000 | 0.000 | -1.283 | 0.000 | -15.818 | -12.148 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.407 | 0.000 | 0.037 | 0.000 | 0.000 | -0.856 | 0.000 | -0.249 | -19.869 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.331 | 0.000 | 0.041 | 0.000 | 0.000 | -0.900 | 0.000 | -0.310 | -19.692 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.281 | 0.000 | 0.044 | 0.000 | 0.000 | -0.924 | 0.000 | -0.354 | -19.577 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 2.202 | 0.000 | 0.038 | 0.000 | 0.000 | -0.987 | 0.000 | -0.421 | -37.890 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.231 | 0.000 | 0.051 | 0.000 | 0.000 | -0.933 | 0.000 | -0.410 | -19.468 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.222 | 0.000 | 0.055 | 0.000 | 0.000 | -0.924 | 0.000 | -0.427 | -19.455 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.206 | 0.000 | 0.057 | 0.000 | 0.000 | -0.924 | 0.000 | -0.446 | -19.423 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 2.188 | 0.000 | 0.057 | 0.000 | 0.000 | -0.930 | 0.000 | -0.464 | -19.380 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 2.069 | 0.000 | 0.032 | 0.000 | 0.000 | -0.929 | 0.000 | -0.519 | -27.120 |
Total Facility | 40.013 | -2070.621 | 0.000 | 0.000 | 284.716 | 416.414 | 980.287 | 1100.665 | 0.000 | 86.738 | 313.649 | 0.000 | -405.468 | 0.000 | -443.877 | -302.525 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-15:30 | 0.00 | -3090.16 | 0.00 | 0.00 | 48.79 | 100.83 | 470.89 | 3724.75 | 0.00 | 45.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1300.87 |
G NW APARTMENT | 12-JUN-17:10 | 0.00 | -2837.54 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2899.56 | 0.00 | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1009.04 |
OFFICE | 01-SEP-11:00 | 0.00 | -3438.94 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3064.95 | 0.00 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1877.90 |
G NE APARTMENT | 28-JUN-10:30 | 0.00 | -2136.78 | 0.00 | 0.00 | 40.52 | 28.81 | 412.03 | 2401.51 | 0.00 | 22.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -768.93 |
G N1 APARTMENT | 12-JUN-17:15 | 0.00 | -1418.94 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 940.86 | 0.00 | 13.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.05 |
G N2 APARTMENT | 12-JUN-17:15 | 0.00 | -1407.04 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 941.08 | 0.00 | 13.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -472.17 |
G S1 APARTMENT | 01-JAN-14:00 | 0.00 | -2053.48 | 0.00 | 0.00 | 40.59 | 28.81 | 388.49 | 3200.35 | 0.00 | 115.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1720.48 |
G S2 APARTMENT | 01-JAN-14:00 | 0.00 | -2100.00 | 0.00 | 0.00 | 40.74 | 28.81 | 388.49 | 3201.68 | 0.00 | 122.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1682.15 |
F2 SW APARTMENT | 06-NOV-15:15 | 0.00 | -3788.04 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 4098.79 | 0.00 | 17.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -820.02 |
F2 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3316.54 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2873.58 | 0.00 | 31.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -513.64 |
F2 SE APARTMENT | 06-NOV-13:30 | 0.00 | -3378.05 | 0.00 | 0.00 | 40.55 | 28.81 | 388.49 | 3432.17 | 0.00 | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -517.07 |
F2 NE APARTMENT | 13-JUN-09:45 | 0.00 | -2576.58 | 0.00 | 0.00 | 40.52 | 28.81 | 406.15 | 2401.46 | 0.00 | 47.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -347.43 |
F2 N1 APARTMENT | 12-JUN-17:10 | 0.00 | -1752.34 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 926.57 | 0.00 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -118.15 |
F2 N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1743.00 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 926.69 | 0.00 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -127.61 |
F2 S1 APARTMENT | 02-DEC-13:15 | 0.00 | -2598.11 | 0.00 | 0.00 | 40.29 | 28.81 | 388.49 | 3231.81 | 0.00 | 25.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1116.59 |
F2 S2 APARTMENT | 02-DEC-13:15 | 0.00 | -2617.27 | 0.00 | 0.00 | 40.32 | 28.81 | 388.49 | 3231.98 | 0.00 | 26.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1098.56 |
F3 SW APARTMENT | 06-NOV-15:30 | 0.00 | -3833.05 | 0.00 | 0.00 | 40.55 | 50.41 | 400.26 | 3968.56 | 0.00 | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -647.42 |
F3 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3335.24 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2859.20 | 0.00 | 37.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -486.28 |
F3 SE APARTMENT | 10-DEC-13:45 | 0.00 | -3345.34 | 0.00 | 0.00 | 40.50 | 28.81 | 388.49 | 3368.52 | 0.00 | 23.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -504.74 |
F3 NE APARTMENT | 13-JUN-09:45 | 0.00 | -2584.62 | 0.00 | 0.00 | 40.37 | 28.81 | 406.15 | 2366.40 | 0.00 | 55.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -312.17 |
F3 N1 APARTMENT | 12-JUN-17:10 | 0.00 | -1785.63 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 920.99 | 0.00 | 22.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -82.73 |
F3 N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1776.31 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 921.12 | 0.00 | 22.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.17 |
F3 S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2641.75 | 0.00 | 0.00 | 40.08 | 28.81 | 406.15 | 3279.39 | 0.00 | 15.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1128.64 |
F3 S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2650.73 | 0.00 | 0.00 | 40.09 | 28.81 | 406.15 | 3279.40 | 0.00 | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1119.98 |
F4 SW APARTMENT | 06-NOV-15:30 | 0.00 | -3844.97 | 0.00 | 0.00 | 40.54 | 50.41 | 400.26 | 3949.27 | 0.00 | 22.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -618.50 |
F4 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3342.22 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2847.60 | 0.00 | 41.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -472.00 |
F4 SE APARTMENT | 01-JAN-14:00 | 0.00 | -3351.10 | 0.00 | 0.00 | 40.76 | 28.81 | 388.49 | 3364.39 | 0.00 | 136.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.41 |
F4 NE APARTMENT | 08-JUL-11:00 | 0.00 | -2597.48 | 0.00 | 0.00 | 40.50 | 28.81 | 412.03 | 2292.11 | 0.00 | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -209.31 |
F4 N1 APARTMENT | 12-JUN-17:10 | 0.00 | -1806.40 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 916.70 | 0.00 | 25.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.27 |
F4 N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1797.14 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 916.83 | 0.00 | 25.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.65 |
F4 S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2655.41 | 0.00 | 0.00 | 40.08 | 28.81 | 406.15 | 3255.48 | 0.00 | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1090.48 |
F4 S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2662.78 | 0.00 | 0.00 | 40.09 | 28.81 | 406.15 | 3255.49 | 0.00 | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1083.41 |
M SW APARTMENT | 06-NOV-15:30 | 0.00 | -3879.01 | 0.00 | 0.00 | 40.58 | 50.41 | 400.26 | 3933.04 | 0.00 | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -570.23 |
M NW APARTMENT | 12-JUN-17:10 | 0.00 | -3370.95 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2836.93 | 0.00 | 45.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -436.08 |
M SE APARTMENT | 01-JAN-14:00 | 0.00 | -3367.24 | 0.00 | 0.00 | 40.76 | 28.81 | 388.49 | 3349.87 | 0.00 | 137.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -577.85 |
M NE APARTMENT | 13-JUN-09:45 | 0.00 | -2627.61 | 0.00 | 0.00 | 40.43 | 28.81 | 406.15 | 2322.13 | 0.00 | 66.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -236.57 |
M N1 APARTMENT | 12-JUN-17:10 | 0.00 | -1849.08 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 912.61 | 0.00 | 27.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15.62 |
M N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1839.87 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 912.74 | 0.00 | 27.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24.96 |
M S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2689.52 | 0.00 | 0.00 | 40.15 | 28.81 | 406.15 | 3235.81 | 0.00 | 16.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1038.14 |
M S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2696.62 | 0.00 | 0.00 | 40.15 | 28.81 | 406.15 | 3235.82 | 0.00 | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1031.35 |
F6 SW APARTMENT | 06-NOV-15:30 | 0.00 | -3839.22 | 0.00 | 0.00 | 40.61 | 50.41 | 400.26 | 3920.26 | 0.00 | 26.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -598.91 |
F6 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3331.83 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2829.11 | 0.00 | 48.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -470.35 |
F6 SE APARTMENT | 06-NOV-14:15 | 0.00 | -3321.07 | 0.00 | 0.00 | 40.36 | 28.81 | 382.60 | 3075.82 | 0.00 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -226.30 |
F6 NE APARTMENT | 13-JUN-09:45 | 0.00 | -2590.38 | 0.00 | 0.00 | 40.44 | 28.81 | 406.15 | 2306.21 | 0.00 | 71.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -262.29 |
F6 N1 APARTMENT | 12-JUN-17:05 | 0.00 | -1819.38 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 910.10 | 0.00 | 29.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.66 |
F6 N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1810.27 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 910.23 | 0.00 | 29.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53.86 |
F6 S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2649.69 | 0.00 | 0.00 | 40.20 | 28.81 | 406.15 | 3219.67 | 0.00 | 17.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1062.64 |
F6 S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2656.74 | 0.00 | 0.00 | 40.21 | 28.81 | 406.15 | 3219.69 | 0.00 | 17.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1055.93 |
F7 SW APARTMENT | 06-NOV-15:30 | 0.00 | -3825.50 | 0.00 | 0.00 | 40.64 | 50.41 | 400.26 | 3908.20 | 0.00 | 28.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.06 |
F7 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3317.61 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2821.36 | 0.00 | 50.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -479.42 |
F7 SE APARTMENT | 06-NOV-14:15 | 0.00 | -3310.77 | 0.00 | 0.00 | 40.40 | 28.81 | 382.60 | 3070.03 | 0.00 | 20.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -231.94 |
F7 NE APARTMENT | 13-JUN-09:45 | 0.00 | -2579.22 | 0.00 | 0.00 | 40.46 | 28.81 | 406.15 | 2291.33 | 0.00 | 74.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -262.47 |
F7 N1 APARTMENT | 12-JUN-17:05 | 0.00 | -1815.08 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 907.42 | 0.00 | 30.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47.85 |
F7 N2 APARTMENT | 12-JUN-17:05 | 0.00 | -1805.99 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 907.55 | 0.00 | 30.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57.06 |
F7 S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2635.78 | 0.00 | 0.00 | 40.27 | 28.81 | 406.15 | 3204.97 | 0.00 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1063.09 |
F7 S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2642.78 | 0.00 | 0.00 | 40.28 | 28.81 | 406.15 | 3205.00 | 0.00 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1056.45 |
F8 SW APARTMENT | 06-NOV-15:30 | 0.00 | -3825.21 | 0.00 | 0.00 | 40.70 | 50.41 | 400.26 | 3897.32 | 0.00 | 29.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -592.90 |
F8 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3317.46 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2813.78 | 0.00 | 53.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -474.31 |
F8 SE APARTMENT | 06-NOV-14:15 | 0.00 | -3314.58 | 0.00 | 0.00 | 40.47 | 28.81 | 382.60 | 3064.96 | 0.00 | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224.18 |
F8 NE APARTMENT | 28-JUN-10:30 | 0.00 | -2581.76 | 0.00 | 0.00 | 40.60 | 28.81 | 412.03 | 2318.35 | 0.00 | 54.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.93 |
F8 N1 APARTMENT | 12-JUN-17:05 | 0.00 | -1825.78 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 904.67 | 0.00 | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35.81 |
F8 N2 APARTMENT | 12-JUN-17:05 | 0.00 | -1816.77 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 904.80 | 0.00 | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.95 |
F8 S1 APARTMENT | 02-DEC-13:00 | 0.00 | -2635.81 | 0.00 | 0.00 | 40.37 | 28.81 | 406.15 | 3192.03 | 0.00 | 21.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1052.68 |
F8 S2 APARTMENT | 02-DEC-13:00 | 0.00 | -2642.78 | 0.00 | 0.00 | 40.38 | 28.81 | 406.15 | 3192.06 | 0.00 | 21.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.10 |
F9 SW APARTMENT | 06-NOV-15:15 | 0.00 | -3863.78 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3984.99 | 0.00 | 30.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -643.16 |
F9 NW APARTMENT | 12-JUN-17:10 | 0.00 | -3403.33 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2803.82 | 0.00 | 55.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -380.57 |
F9 SE APARTMENT | 06-NOV-14:00 | 0.00 | -3349.28 | 0.00 | 0.00 | 40.43 | 28.81 | 388.49 | 3183.76 | 0.00 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -312.25 |
F9 NE APARTMENT | 28-JUN-10:30 | 0.00 | -2620.83 | 0.00 | 0.00 | 40.65 | 28.81 | 412.03 | 2311.18 | 0.00 | 57.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.00 |
F9 N1 APARTMENT | 12-JUN-17:10 | 0.00 | -1905.04 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 900.42 | 0.00 | 33.29 | 46.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 12-JUN-17:10 | 0.00 | -1897.30 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 900.54 | 0.00 | 33.29 | 38.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 02-DEC-13:15 | 0.00 | -2680.80 | 0.00 | 0.00 | 40.50 | 28.81 | 388.49 | 3085.08 | 0.00 | 32.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -894.68 |
F9 S2 APARTMENT | 02-DEC-13:15 | 0.00 | -2688.28 | 0.00 | 0.00 | 40.51 | 28.81 | 388.49 | 3085.13 | 0.00 | 33.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -887.77 |
T SW APARTMENT | 06-NOV-14:30 | 0.00 | -4560.21 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 4132.70 | 0.00 | 26.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.92 |
T NW APARTMENT | 12-JUN-16:30 | 0.00 | -4135.12 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3075.43 | 0.00 | 45.26 | 197.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 06-NOV-14:15 | 0.00 | -3968.54 | 0.00 | 0.00 | 40.28 | 28.81 | 382.60 | 3008.31 | 0.00 | 23.16 | 485.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 08-JUL-11:30 | 0.00 | -3218.18 | 0.00 | 0.00 | 40.51 | 28.81 | 406.15 | 1998.98 | 0.00 | 48.62 | 695.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 12-JUN-17:10 | 0.00 | -2466.09 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 880.97 | 0.00 | 34.45 | 625.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 12-JUN-17:10 | 0.00 | -2444.93 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 881.40 | 0.00 | 34.45 | 604.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 02-DEC-13:00 | 0.00 | -3260.84 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3153.41 | 0.00 | 41.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -409.97 |
T S2 APARTMENT | 02-DEC-13:00 | 0.00 | -3267.59 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3153.26 | 0.00 | 41.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -403.06 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-AUG-16:10 | 0.00 | -191377.84 | 0.00 | 0.00 | 6689.93 | 18221.75 | 47207.76 | 125476.21 | 0.00 | 11310.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17528.10 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 20-DEC-07:30 | 1067.14 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 405.37 | 0.00 | -1915.56 | 0.00 | -194.40 | 0.00 |
G NW APARTMENT | 05-FEB-08:15 | 1252.39 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1220.88 | 0.00 | -300.44 | -236.75 |
OFFICE | 05-FEB-07:15 | 1273.85 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 17.97 | 0.00 | -1513.02 | 0.00 | -287.07 | 0.00 |
G NE APARTMENT | 21-DEC-15:40 | 1193.76 | 0.00 | 0.00 | 0.00 | 46.48 | 50.41 | 400.26 | 72.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1016.69 | -746.54 |
G N1 APARTMENT | 28-OCT-10:15 | 1167.33 | 0.00 | 0.00 | 0.00 | 44.25 | 28.81 | 412.03 | 155.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1215.79 | -592.60 |
G N2 APARTMENT | 28-OCT-10:15 | 1192.35 | 0.00 | 0.00 | 0.00 | 44.22 | 28.81 | 412.03 | 155.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1215.65 | -617.22 |
G S1 APARTMENT | 16-FEB-06:15 | 716.98 | 0.00 | 0.00 | 0.00 | 177.43 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -384.74 | 0.00 | -927.19 | -1.16 |
G S2 APARTMENT | 10-MAR-12:20 | 662.60 | 0.00 | 0.00 | 0.00 | 47.36 | 28.81 | 406.15 | 247.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.82 | -365.44 |
F2 SW APARTMENT | 05-FEB-07:15 | 871.38 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 485.93 | 0.00 | -1581.89 | 0.00 | -412.87 | 0.00 |
F2 NW APARTMENT | 10-MAR-12:15 | 1038.93 | 0.00 | 0.00 | 0.00 | 44.47 | 28.81 | 406.15 | 297.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1383.16 | -432.48 |
F2 SE APARTMENT | 05-FEB-07:15 | 877.58 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 479.13 | 0.00 | -1581.29 | 0.00 | -412.87 | 0.00 |
F2 NE APARTMENT | 10-MAR-12:15 | 1146.75 | 0.00 | 0.00 | 0.00 | 44.47 | 28.81 | 406.15 | 310.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1378.25 | -558.30 |
F2 N1 APARTMENT | 10-MAR-12:15 | 1141.29 | 0.00 | 0.00 | 0.00 | 44.60 | 28.81 | 406.15 | 174.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1333.72 | -461.47 |
F2 N2 APARTMENT | 10-MAR-12:15 | 1139.54 | 0.00 | 0.00 | 0.00 | 44.61 | 28.81 | 406.15 | 174.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1333.68 | -459.85 |
F2 S1 APARTMENT | 05-FEB-04:15 | 511.56 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 117.91 | 0.00 | -893.32 | 0.00 | -192.70 | 0.00 |
F2 S2 APARTMENT | 16-FEB-06:20 | 140.79 | 0.00 | 0.00 | 0.00 | 185.89 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 918.20 | 0.00 | -420.80 | 0.00 | -1242.76 | 0.00 |
F3 SW APARTMENT | 05-FEB-07:15 | 859.24 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 606.97 | 0.00 | -1614.56 | 0.00 | -489.10 | 0.00 |
F3 NW APARTMENT | 10-MAR-12:15 | 1180.51 | 0.00 | 0.00 | 0.00 | 44.13 | 28.81 | 406.15 | 261.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1516.51 | -404.68 |
F3 SE APARTMENT | 05-FEB-07:15 | 875.00 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 590.32 | 0.00 | -1613.67 | 0.00 | -489.10 | 0.00 |
F3 NE APARTMENT | 10-MAR-12:15 | 1294.29 | 0.00 | 0.00 | 0.00 | 44.14 | 28.81 | 406.15 | 270.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1511.32 | -532.29 |
F3 N1 APARTMENT | 10-MAR-12:15 | 1333.91 | 0.00 | 0.00 | 0.00 | 44.01 | 28.81 | 406.15 | 147.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1459.78 | -500.45 |
F3 N2 APARTMENT | 10-MAR-12:15 | 1332.04 | 0.00 | 0.00 | 0.00 | 44.02 | 28.81 | 406.15 | 147.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1459.74 | -498.71 |
F3 S1 APARTMENT | 16-FEB-06:20 | 145.26 | 0.00 | 0.00 | 0.00 | 185.52 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1031.64 | 0.00 | -431.55 | 0.00 | -1349.55 | 0.00 |
F3 S2 APARTMENT | 16-FEB-06:20 | 146.66 | 0.00 | 0.00 | 0.00 | 185.49 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1030.95 | 0.00 | -431.57 | 0.00 | -1350.21 | 0.00 |
F4 SW APARTMENT | 05-FEB-07:15 | 909.05 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 635.01 | 0.00 | -1634.50 | 0.00 | -547.01 | 0.00 |
F4 NW APARTMENT | 10-MAR-12:15 | 1381.74 | 0.00 | 0.00 | 0.00 | 44.14 | 28.81 | 406.15 | 243.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1619.98 | -483.94 |
F4 SE APARTMENT | 05-FEB-07:15 | 928.43 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 614.55 | 0.00 | -1633.41 | 0.00 | -547.01 | 0.00 |
F4 NE APARTMENT | 10-MAR-12:15 | 1372.18 | 0.00 | 0.00 | 0.00 | 44.18 | 28.81 | 406.15 | 248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1618.42 | -481.69 |
F4 N1 APARTMENT | 07-DEC-10:00 | 1451.43 | 0.00 | 0.00 | 0.00 | 43.08 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32.93 | 0.00 | -1566.08 | -318.68 |
F4 N2 APARTMENT | 07-DEC-10:00 | 1450.33 | 0.00 | 0.00 | 0.00 | 43.13 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32.18 | 0.00 | -1565.50 | -318.95 |
F4 S1 APARTMENT | 16-FEB-06:20 | 152.99 | 0.00 | 0.00 | 0.00 | 186.35 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1076.47 | 0.00 | -431.69 | 0.00 | -1402.80 | 0.00 |
F4 S2 APARTMENT | 16-FEB-06:20 | 154.13 | 0.00 | 0.00 | 0.00 | 186.35 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1074.55 | 0.00 | -431.38 | 0.00 | -1402.33 | 0.00 |
M SW APARTMENT | 05-FEB-07:15 | 957.30 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 649.95 | 0.00 | -1649.87 | 0.00 | -594.82 | 0.00 |
M NW APARTMENT | 07-DEC-10:00 | 1599.75 | 0.00 | 0.00 | 0.00 | 43.38 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.33 | 0.00 | -1731.54 | -290.43 |
M SE APARTMENT | 05-FEB-07:15 | 977.64 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 628.47 | 0.00 | -1648.74 | 0.00 | -594.82 | 0.00 |
M NE APARTMENT | 10-MAR-12:15 | 1405.75 | 0.00 | 0.00 | 0.00 | 44.23 | 28.81 | 406.15 | 233.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1711.82 | -406.75 |
M N1 APARTMENT | 07-DEC-10:00 | 1477.70 | 0.00 | 0.00 | 0.00 | 42.97 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.11 | 0.00 | -1663.60 | -237.14 |
M N2 APARTMENT | 07-DEC-10:00 | 1506.43 | 0.00 | 0.00 | 0.00 | 43.03 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.33 | 0.00 | -1662.60 | -267.71 |
M S1 APARTMENT | 16-FEB-06:20 | 160.22 | 0.00 | 0.00 | 0.00 | 186.56 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1127.72 | 0.00 | -432.52 | 0.00 | -1460.66 | 0.00 |
M S2 APARTMENT | 16-FEB-06:20 | 161.35 | 0.00 | 0.00 | 0.00 | 186.57 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1125.44 | 0.00 | -432.15 | 0.00 | -1459.90 | 0.00 |
F6 SW APARTMENT | 05-FEB-07:15 | 1057.93 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 600.34 | 0.00 | -1659.63 | 0.00 | -636.09 | 0.00 |
F6 NW APARTMENT | 23-DEC-10:55 | 1803.80 | 0.00 | 0.00 | 0.00 | 46.07 | 28.81 | 406.15 | 72.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1760.99 | -596.65 |
F6 SE APARTMENT | 05-FEB-07:15 | 1076.28 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 580.87 | 0.00 | -1658.50 | 0.00 | -636.09 | 0.00 |
F6 NE APARTMENT | 10-MAR-12:30 | 1411.95 | 0.00 | 0.00 | 0.00 | 44.53 | 28.81 | 406.15 | 180.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1770.50 | -301.35 |
F6 N1 APARTMENT | 23-DEC-10:55 | 1814.75 | 0.00 | 0.00 | 0.00 | 45.72 | 28.81 | 406.15 | 27.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1691.01 | -632.09 |
F6 N2 APARTMENT | 23-DEC-10:55 | 1830.76 | 0.00 | 0.00 | 0.00 | 45.72 | 28.81 | 406.15 | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1690.78 | -648.30 |
F6 S1 APARTMENT | 16-FEB-06:20 | 229.53 | 0.00 | 0.00 | 0.00 | 188.44 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1052.26 | 0.00 | -423.31 | 0.00 | -1465.60 | 0.00 |
F6 S2 APARTMENT | 16-FEB-06:20 | 237.17 | 0.00 | 0.00 | 0.00 | 188.45 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 1044.23 | 0.00 | -422.96 | 0.00 | -1465.57 | 0.00 |
F7 SW APARTMENT | 05-FEB-07:15 | 1136.31 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 567.34 | 0.00 | -1668.38 | 0.00 | -672.72 | 0.00 |
F7 NW APARTMENT | 23-DEC-10:55 | 1830.42 | 0.00 | 0.00 | 0.00 | 46.29 | 28.81 | 406.15 | 69.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1839.61 | -541.28 |
F7 SE APARTMENT | 05-FEB-07:15 | 1152.06 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 550.51 | 0.00 | -1667.30 | 0.00 | -672.72 | 0.00 |
F7 NE APARTMENT | 10-MAR-12:30 | 1411.02 | 0.00 | 0.00 | 0.00 | 44.79 | 28.81 | 406.15 | 174.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1846.94 | -218.66 |
F7 N1 APARTMENT | 23-DEC-10:55 | 1933.20 | 0.00 | 0.00 | 0.00 | 45.93 | 28.81 | 406.15 | 24.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1762.96 | -675.84 |
F7 N2 APARTMENT | 23-DEC-10:55 | 1933.17 | 0.00 | 0.00 | 0.00 | 45.93 | 28.81 | 406.15 | 24.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1762.94 | -675.79 |
F7 S1 APARTMENT | 16-FEB-06:20 | 455.74 | 0.00 | 0.00 | 0.00 | 189.20 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 867.04 | 0.00 | -418.41 | 0.00 | -1512.25 | 0.00 |
F7 S2 APARTMENT | 16-FEB-06:20 | 462.91 | 0.00 | 0.00 | 0.00 | 189.20 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 859.48 | 0.00 | -418.05 | 0.00 | -1512.22 | 0.00 |
F8 SW APARTMENT | 05-FEB-07:15 | 1209.51 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 534.51 | 0.00 | -1675.61 | 0.00 | -705.86 | 0.00 |
F8 NW APARTMENT | 23-DEC-10:55 | 1835.93 | 0.00 | 0.00 | 0.00 | 46.45 | 28.81 | 406.15 | 65.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1912.48 | -470.31 |
F8 SE APARTMENT | 05-FEB-07:15 | 1222.07 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 520.86 | 0.00 | -1674.52 | 0.00 | -705.86 | 0.00 |
F8 NE APARTMENT | 10-MAR-12:25 | 1656.07 | 0.00 | 0.00 | 0.00 | 45.04 | 28.81 | 406.15 | 170.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1940.54 | -366.15 |
F8 N1 APARTMENT | 23-DEC-10:55 | 1944.76 | 0.00 | 0.00 | 0.00 | 46.08 | 28.81 | 406.15 | 21.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1832.42 | -615.09 |
F8 N2 APARTMENT | 23-DEC-10:55 | 1942.55 | 0.00 | 0.00 | 0.00 | 46.08 | 28.81 | 406.15 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1832.40 | -612.87 |
F8 S1 APARTMENT | 20-MAR-17:00 | 564.09 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 91.50 | 0.00 | 0.00 | 726.81 | 0.00 | 0.00 | 0.00 | -2213.69 | 0.00 |
F8 S2 APARTMENT | 20-MAR-17:00 | 556.73 | 0.00 | 0.00 | 0.00 | 98.63 | 144.04 | 588.62 | 91.27 | 0.00 | 0.00 | 734.40 | 0.00 | 0.00 | 0.00 | -2213.69 | 0.00 |
F9 SW APARTMENT | 05-FEB-07:15 | 1343.83 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 431.72 | 0.00 | -1676.74 | 0.00 | -736.26 | 0.00 |
F9 NW APARTMENT | 10-MAR-12:25 | 1947.68 | 0.00 | 0.00 | 0.00 | 45.31 | 28.81 | 406.15 | 186.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2001.56 | -613.32 |
F9 SE APARTMENT | 16-FEB-06:15 | 1450.32 | 0.00 | 0.00 | 0.00 | 174.53 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 65.90 | 0.00 | -691.79 | 0.00 | -1417.64 | 0.00 |
F9 NE APARTMENT | 10-MAR-12:25 | 2147.57 | 0.00 | 0.00 | 0.00 | 45.53 | 28.81 | 406.15 | 173.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1992.41 | -809.44 |
F9 N1 APARTMENT | 23-DEC-10:55 | 1927.72 | 0.00 | 0.00 | 0.00 | 46.31 | 28.81 | 406.15 | 21.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.50 | -532.72 |
F9 N2 APARTMENT | 23-DEC-10:55 | 1926.62 | 0.00 | 0.00 | 0.00 | 46.31 | 28.81 | 406.15 | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.48 | -531.66 |
F9 S1 APARTMENT | 16-FEB-06:15 | 780.46 | 0.00 | 0.00 | 0.00 | 170.84 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 441.60 | 0.00 | -437.08 | 0.00 | -1374.50 | 0.00 |
F9 S2 APARTMENT | 16-FEB-06:15 | 782.82 | 0.00 | 0.00 | 0.00 | 170.95 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 438.11 | 0.00 | -436.39 | 0.00 | -1374.17 | 0.00 |
T SW APARTMENT | 05-FEB-07:10 | 2108.79 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1644.16 | 0.00 | -764.38 | -337.70 |
T NW APARTMENT | 05-FEB-07:10 | 2237.00 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1667.90 | 0.00 | -764.38 | -442.17 |
T SE APARTMENT | 05-FEB-07:10 | 2120.63 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1643.55 | 0.00 | -764.38 | -350.14 |
T NE APARTMENT | 05-FEB-07:10 | 2244.23 | 0.00 | 0.00 | 0.00 | 161.22 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1667.52 | 0.00 | -764.38 | -449.77 |
T N1 APARTMENT | 07-DEC-09:55 | 2079.20 | 0.00 | 0.00 | 0.00 | 45.23 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.56 | 0.00 | -2041.99 | -476.05 |
T N2 APARTMENT | 07-DEC-09:55 | 2080.97 | 0.00 | 0.00 | 0.00 | 45.21 | 28.81 | 394.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30.09 | 0.00 | -2042.19 | -477.08 |
T S1 APARTMENT | 28-DEC-21:15 | 1148.01 | 0.00 | 0.00 | 0.00 | 189.67 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 437.14 | 0.00 | -284.08 | 0.00 | -2149.51 | 0.00 |
T S2 APARTMENT | 28-DEC-21:15 | 1151.25 | 0.00 | 0.00 | 0.00 | 189.67 | 158.44 | 500.33 | 0.00 | 0.00 | 0.00 | 433.80 | 0.00 | -283.98 | 0.00 | -2149.51 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-FEB-07:15 | 63733.15 | 0.00 | 0.00 | 0.00 | 12736.44 | 14239.10 | 30866.16 | 0.00 | 0.00 | 0.00 | 38429.34 | 0.00 | -107442.61 | 0.00 | -52561.56 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sec1.1A-General InformationData | |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 18.75 |
Number of hours cooling loads not met | 565.00 |
Number of hours not met | 583.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.41 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 10.11 | 0.00 | 13.16 | 100597.46 | 0.00 | 0.00 |
Space Cooling | 1107.49 | 84175.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.82 | 1860.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.24 | 3451.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 604.09 | 19155.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 894.05 | 79131.82 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3570.48 | 907.21 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3570.48 |
Natural Gas | 0.00 | 907.21 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4477.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 1.29 |
Space Cooling | 141.32 |
Fans-Interior | 77.09 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 38.45 |
Subtotal | 455.62 |
Natural Gas [MJ/m2] | |
Space Heating | 1.68 |
Service Water Heating | 114.09 |
Miscellaneous | -0.00 |
Subtotal | 115.77 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 9.30 |
Space Heating | 0.52 |
Space Cooling | 24.73 |
Fans-Interior | 13.49 |
Service Water Heating | 19.97 |
Receptacle Equipment | 25.26 |
Miscellaneous | 6.73 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.251203 |
G NW APARTMENT DIRECT AIR | 0.233413 |
OFFICE DIRECT AIR | 0.320355 |
G NE APARTMENT DIRECT AIR | 0.193551 |
G N1 APARTMENT DIRECT AIR | 0.107651 |
G N2 APARTMENT DIRECT AIR | 0.106554 |
G S1 APARTMENT DIRECT AIR | 0.147219 |
G S2 APARTMENT DIRECT AIR | 0.151947 |
F2 SW APARTMENT DIRECT AIR | 0.292889 |
F2 NW APARTMENT DIRECT AIR | 0.272466 |
F2 SE APARTMENT DIRECT AIR | 0.274566 |
F2 NE APARTMENT DIRECT AIR | 0.228129 |
F2 N1 APARTMENT DIRECT AIR | 0.133724 |
F2 N2 APARTMENT DIRECT AIR | 0.132858 |
F2 S1 APARTMENT DIRECT AIR | 0.175995 |
F2 S2 APARTMENT DIRECT AIR | 0.177683 |
F3 SW APARTMENT DIRECT AIR | 0.291996 |
F3 NW APARTMENT DIRECT AIR | 0.272472 |
F3 SE APARTMENT DIRECT AIR | 0.259502 |
F3 NE APARTMENT DIRECT AIR | 0.229421 |
F3 N1 APARTMENT DIRECT AIR | 0.135682 |
F3 N2 APARTMENT DIRECT AIR | 0.134826 |
F3 S1 APARTMENT DIRECT AIR | 0.177080 |
F3 S2 APARTMENT DIRECT AIR | 0.177852 |
F4 SW APARTMENT DIRECT AIR | 0.291733 |
F4 NW APARTMENT DIRECT AIR | 0.272579 |
F4 SE APARTMENT DIRECT AIR | 0.257952 |
F4 NE APARTMENT DIRECT AIR | 0.229771 |
F4 N1 APARTMENT DIRECT AIR | 0.136968 |
F4 N2 APARTMENT DIRECT AIR | 0.136120 |
F4 S1 APARTMENT DIRECT AIR | 0.177539 |
F4 S2 APARTMENT DIRECT AIR | 0.178174 |
M SW APARTMENT DIRECT AIR | 0.293779 |
M NW APARTMENT DIRECT AIR | 0.274980 |
M SE APARTMENT DIRECT AIR | 0.260041 |
M NE APARTMENT DIRECT AIR | 0.232349 |
M N1 APARTMENT DIRECT AIR | 0.140215 |
M N2 APARTMENT DIRECT AIR | 0.139374 |
M S1 APARTMENT DIRECT AIR | 0.180068 |
M S2 APARTMENT DIRECT AIR | 0.180682 |
F6 SW APARTMENT DIRECT AIR | 0.289799 |
F6 NW APARTMENT DIRECT AIR | 0.271177 |
F6 SE APARTMENT DIRECT AIR | 0.256312 |
F6 NE APARTMENT DIRECT AIR | 0.228812 |
F6 N1 APARTMENT DIRECT AIR | 0.137427 |
F6 N2 APARTMENT DIRECT AIR | 0.136598 |
F6 S1 APARTMENT DIRECT AIR | 0.176704 |
F6 S2 APARTMENT DIRECT AIR | 0.177314 |
F7 SW APARTMENT DIRECT AIR | 0.288126 |
F7 NW APARTMENT DIRECT AIR | 0.269745 |
F7 SE APARTMENT DIRECT AIR | 0.254876 |
F7 NE APARTMENT DIRECT AIR | 0.227598 |
F7 N1 APARTMENT DIRECT AIR | 0.136796 |
F7 N2 APARTMENT DIRECT AIR | 0.135975 |
F7 S1 APARTMENT DIRECT AIR | 0.175531 |
F7 S2 APARTMENT DIRECT AIR | 0.176139 |
F8 SW APARTMENT DIRECT AIR | 0.287886 |
F8 NW APARTMENT DIRECT AIR | 0.269707 |
F8 SE APARTMENT DIRECT AIR | 0.254808 |
F8 NE APARTMENT DIRECT AIR | 0.227736 |
F8 N1 APARTMENT DIRECT AIR | 0.137465 |
F8 N2 APARTMENT DIRECT AIR | 0.136654 |
F8 S1 APARTMENT DIRECT AIR | 0.175673 |
F8 S2 APARTMENT DIRECT AIR | 0.176281 |
F9 SW APARTMENT DIRECT AIR | 0.295197 |
F9 NW APARTMENT DIRECT AIR | 0.277225 |
F9 SE APARTMENT DIRECT AIR | 0.258645 |
F9 NE APARTMENT DIRECT AIR | 0.231264 |
F9 N1 APARTMENT DIRECT AIR | 0.144860 |
F9 N2 APARTMENT DIRECT AIR | 0.144053 |
F9 S1 APARTMENT DIRECT AIR | 0.180689 |
F9 S2 APARTMENT DIRECT AIR | 0.181360 |
T SW APARTMENT DIRECT AIR | 0.353305 |
T NW APARTMENT DIRECT AIR | 0.331335 |
T SE APARTMENT DIRECT AIR | 0.307598 |
T NE APARTMENT DIRECT AIR | 0.271931 |
T N1 APARTMENT DIRECT AIR | 0.188188 |
T N2 APARTMENT DIRECT AIR | 0.188262 |
T S1 APARTMENT DIRECT AIR | 0.240158 |
T S2 APARTMENT DIRECT AIR | 0.240929 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.251203 |
AIRLOOP G NW MAIN BRANCH | 0.233413 |
AIRLOOP OFFICE MAIN BRANCH | 0.320355 |
AIRLOOP G NE MAIN BRANCH | 0.193551 |
AIRLOOP G N1 MAIN BRANCH | 0.107651 |
AIRLOOP G N2 MAIN BRANCH | 0.106554 |
AIRLOOP G S1 MAIN BRANCH | 0.147219 |
AIRLOOP G S2 MAIN BRANCH | 0.151947 |
AIRLOOP F2 SW MAIN BRANCH | 0.292889 |
AIRLOOP F2 NW MAIN BRANCH | 0.272466 |
AIRLOOP F2 SE MAIN BRANCH | 0.274566 |
AIRLOOP F2 NE MAIN BRANCH | 0.228129 |
AIRLOOP F2 N1 MAIN BRANCH | 0.133724 |
AIRLOOP F2 N2 MAIN BRANCH | 0.132858 |
AIRLOOP F2 S1 MAIN BRANCH | 0.175995 |
AIRLOOP F2 S2 MAIN BRANCH | 0.177683 |
AIRLOOP F3 SW MAIN BRANCH | 0.291996 |
AIRLOOP F3 NW MAIN BRANCH | 0.272472 |
AIRLOOP F3 SE MAIN BRANCH | 0.259502 |
AIRLOOP F3 NE MAIN BRANCH | 0.229421 |
AIRLOOP F3 N1 MAIN BRANCH | 0.135682 |
AIRLOOP F3 N2 MAIN BRANCH | 0.134826 |
AIRLOOP F3 S1 MAIN BRANCH | 0.177080 |
AIRLOOP F3 S2 MAIN BRANCH | 0.177852 |
AIRLOOP F4 SW MAIN BRANCH | 0.291733 |
AIRLOOP F4 NW MAIN BRANCH | 0.272579 |
AIRLOOP F4 SE MAIN BRANCH | 0.257952 |
AIRLOOP F4 NE MAIN BRANCH | 0.229771 |
AIRLOOP F4 N1 MAIN BRANCH | 0.136968 |
AIRLOOP F4 N2 MAIN BRANCH | 0.136120 |
AIRLOOP F4 S1 MAIN BRANCH | 0.177539 |
AIRLOOP F4 S2 MAIN BRANCH | 0.178174 |
AIRLOOP M SW MAIN BRANCH | 0.293779 |
AIRLOOP M NW MAIN BRANCH | 0.274980 |
AIRLOOP M SE MAIN BRANCH | 0.260041 |
AIRLOOP M NE MAIN BRANCH | 0.232349 |
AIRLOOP M N1 MAIN BRANCH | 0.140215 |
AIRLOOP M N2 MAIN BRANCH | 0.139374 |
AIRLOOP M S1 MAIN BRANCH | 0.180068 |
AIRLOOP M S2 MAIN BRANCH | 0.180682 |
AIRLOOP F6 SW MAIN BRANCH | 0.289799 |
AIRLOOP F6 NW MAIN BRANCH | 0.271177 |
AIRLOOP F6 SE MAIN BRANCH | 0.256312 |
AIRLOOP F6 NE MAIN BRANCH | 0.228812 |
AIRLOOP F6 N1 MAIN BRANCH | 0.137427 |
AIRLOOP F6 N2 MAIN BRANCH | 0.136598 |
AIRLOOP F6 S1 MAIN BRANCH | 0.176704 |
AIRLOOP F6 S2 MAIN BRANCH | 0.177314 |
AIRLOOP F7 SW MAIN BRANCH | 0.288126 |
AIRLOOP F7 NW MAIN BRANCH | 0.269745 |
AIRLOOP F7 SE MAIN BRANCH | 0.254876 |
AIRLOOP F7 NE MAIN BRANCH | 0.227598 |
AIRLOOP F7 N1 MAIN BRANCH | 0.136796 |
AIRLOOP F7 N2 MAIN BRANCH | 0.135975 |
AIRLOOP F7 S1 MAIN BRANCH | 0.175531 |
AIRLOOP F7 S2 MAIN BRANCH | 0.176139 |
AIRLOOP F8 SW MAIN BRANCH | 0.287886 |
AIRLOOP F8 NW MAIN BRANCH | 0.269707 |
AIRLOOP F8 SE MAIN BRANCH | 0.254808 |
AIRLOOP F8 NE MAIN BRANCH | 0.227736 |
AIRLOOP F8 N1 MAIN BRANCH | 0.137465 |
AIRLOOP F8 N2 MAIN BRANCH | 0.136654 |
AIRLOOP F8 S1 MAIN BRANCH | 0.175673 |
AIRLOOP F8 S2 MAIN BRANCH | 0.176281 |
AIRLOOP F9 SW MAIN BRANCH | 0.295197 |
AIRLOOP F9 NW MAIN BRANCH | 0.277225 |
AIRLOOP F9 SE MAIN BRANCH | 0.258645 |
AIRLOOP F9 NE MAIN BRANCH | 0.231264 |
AIRLOOP F9 N1 MAIN BRANCH | 0.144860 |
AIRLOOP F9 N2 MAIN BRANCH | 0.144053 |
AIRLOOP F9 S1 MAIN BRANCH | 0.180689 |
AIRLOOP F9 S2 MAIN BRANCH | 0.181360 |
AIRLOOP T SW MAIN BRANCH | 0.353305 |
AIRLOOP T NW MAIN BRANCH | 0.331335 |
AIRLOOP T SE MAIN BRANCH | 0.307598 |
AIRLOOP T NE MAIN BRANCH | 0.271931 |
AIRLOOP T N1 MAIN BRANCH | 0.188188 |
AIRLOOP T N2 MAIN BRANCH | 0.188262 |
AIRLOOP T S1 MAIN BRANCH | 0.240158 |
AIRLOOP T S2 MAIN BRANCH | 0.240929 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.251203 |
AIRLOOP G NW | 0.233413 |
AIRLOOP OFFICE | 0.320355 |
AIRLOOP G NE | 0.193551 |
AIRLOOP G N1 | 0.107651 |
AIRLOOP G N2 | 0.106554 |
AIRLOOP G S1 | 0.147219 |
AIRLOOP G S2 | 0.151947 |
AIRLOOP F2 SW | 0.292889 |
AIRLOOP F2 NW | 0.272466 |
AIRLOOP F2 SE | 0.274566 |
AIRLOOP F2 NE | 0.228129 |
AIRLOOP F2 N1 | 0.133724 |
AIRLOOP F2 N2 | 0.132858 |
AIRLOOP F2 S1 | 0.175995 |
AIRLOOP F2 S2 | 0.177683 |
AIRLOOP F3 SW | 0.291996 |
AIRLOOP F3 NW | 0.272472 |
AIRLOOP F3 SE | 0.259502 |
AIRLOOP F3 NE | 0.229421 |
AIRLOOP F3 N1 | 0.135682 |
AIRLOOP F3 N2 | 0.134826 |
AIRLOOP F3 S1 | 0.177080 |
AIRLOOP F3 S2 | 0.177852 |
AIRLOOP F4 SW | 0.291733 |
AIRLOOP F4 NW | 0.272579 |
AIRLOOP F4 SE | 0.257952 |
AIRLOOP F4 NE | 0.229771 |
AIRLOOP F4 N1 | 0.136968 |
AIRLOOP F4 N2 | 0.136120 |
AIRLOOP F4 S1 | 0.177539 |
AIRLOOP F4 S2 | 0.178174 |
AIRLOOP M SW | 0.293779 |
AIRLOOP M NW | 0.274980 |
AIRLOOP M SE | 0.260041 |
AIRLOOP M NE | 0.232349 |
AIRLOOP M N1 | 0.140215 |
AIRLOOP M N2 | 0.139374 |
AIRLOOP M S1 | 0.180068 |
AIRLOOP M S2 | 0.180682 |
AIRLOOP F6 SW | 0.289799 |
AIRLOOP F6 NW | 0.271177 |
AIRLOOP F6 SE | 0.256312 |
AIRLOOP F6 NE | 0.228812 |
AIRLOOP F6 N1 | 0.137427 |
AIRLOOP F6 N2 | 0.136598 |
AIRLOOP F6 S1 | 0.176704 |
AIRLOOP F6 S2 | 0.177314 |
AIRLOOP F7 SW | 0.288126 |
AIRLOOP F7 NW | 0.269745 |
AIRLOOP F7 SE | 0.254876 |
AIRLOOP F7 NE | 0.227598 |
AIRLOOP F7 N1 | 0.136796 |
AIRLOOP F7 N2 | 0.135975 |
AIRLOOP F7 S1 | 0.175531 |
AIRLOOP F7 S2 | 0.176139 |
AIRLOOP F8 SW | 0.287886 |
AIRLOOP F8 NW | 0.269707 |
AIRLOOP F8 SE | 0.254808 |
AIRLOOP F8 NE | 0.227736 |
AIRLOOP F8 N1 | 0.137465 |
AIRLOOP F8 N2 | 0.136654 |
AIRLOOP F8 S1 | 0.175673 |
AIRLOOP F8 S2 | 0.176281 |
AIRLOOP F9 SW | 0.295197 |
AIRLOOP F9 NW | 0.277225 |
AIRLOOP F9 SE | 0.258645 |
AIRLOOP F9 NE | 0.231264 |
AIRLOOP F9 N1 | 0.144860 |
AIRLOOP F9 N2 | 0.144053 |
AIRLOOP F9 S1 | 0.180689 |
AIRLOOP F9 S2 | 0.181360 |
AIRLOOP T SW | 0.353305 |
AIRLOOP T NW | 0.331335 |
AIRLOOP T SE | 0.307598 |
AIRLOOP T NE | 0.271931 |
AIRLOOP T N1 | 0.188188 |
AIRLOOP T N2 | 0.188262 |
AIRLOOP T S1 | 0.240158 |
AIRLOOP T S2 | 0.240929 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.251203 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.233413 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.320355 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.193551 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.107651 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.106554 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.147219 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.151947 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.292889 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.272466 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.274566 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.228129 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.133724 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.132858 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.175995 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.177683 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.291996 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.272472 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.259502 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.229421 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.135682 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.134826 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.177080 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.177852 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.291733 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.272579 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.257952 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.229771 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.136968 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.136120 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.177539 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.178174 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.293779 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.274980 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.260041 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.232349 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.140215 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.139374 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.180068 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.180682 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.289799 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.271177 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.256312 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.228812 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.137427 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.136598 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.176704 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.177314 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.288126 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.269745 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.254876 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.227598 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.136796 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.135975 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.175531 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.176139 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.287886 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.269707 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.254808 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.227736 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.137465 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.136654 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.175673 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.176281 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.295197 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.277225 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.258645 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.231264 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.144860 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.144053 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.180689 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.181360 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.353305 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.331335 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.307598 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.271931 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.188188 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.188262 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.240158 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.240929 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.251203 | 4563.88 | 3111.56 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.233413 | 4297.11 | 2908.93 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.320355 | 5878.40 | 3986.43 | 0.000128 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.193551 | 3688.42 | 2452.89 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.107651 | 2416.46 | 1504.00 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.106554 | 2399.94 | 1491.91 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.147219 | 3038.39 | 1958.97 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.151947 | 3106.59 | 2010.88 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.292889 | 5208.47 | 3584.96 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.272466 | 4908.76 | 3355.31 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.274566 | 4924.55 | 3372.44 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.228129 | 4234.91 | 2848.98 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.133724 | 2832.21 | 1802.02 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.132858 | 2819.34 | 1792.46 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.175995 | 3485.83 | 2286.54 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.177683 | 3510.09 | 2305.09 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.291996 | 5229.11 | 3585.55 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.272472 | 4941.72 | 3365.77 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.259502 | 4742.64 | 3217.40 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.229421 | 4285.20 | 2873.52 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.135682 | 2877.69 | 1829.59 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.134826 | 2864.95 | 1820.13 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.177080 | 3519.71 | 2304.62 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.177852 | 3530.77 | 2313.08 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.291733 | 5250.32 | 3590.49 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.272579 | 4967.87 | 3374.76 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.257952 | 4744.89 | 3208.19 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.229771 | 4314.05 | 2885.18 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.136968 | 2909.18 | 1848.29 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.136120 | 2896.54 | 1838.92 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.177539 | 3540.03 | 2314.30 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.178174 | 3549.13 | 2321.25 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.293779 | 5299.91 | 3619.41 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.274980 | 5022.30 | 3407.56 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.260041 | 4794.68 | 3237.54 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.232349 | 4370.47 | 2919.86 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.140215 | 2967.41 | 1887.74 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.139374 | 2954.87 | 1878.45 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.180068 | 3587.83 | 2345.92 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.180682 | 3596.63 | 2352.65 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.289799 | 5260.45 | 3581.16 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.271177 | 4984.97 | 3371.24 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.256312 | 4758.17 | 3202.05 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.228812 | 4336.22 | 2886.55 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.137427 | 2934.90 | 1860.27 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.136598 | 2922.48 | 1851.10 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.176704 | 3548.68 | 2312.17 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.177314 | 3557.43 | 2318.85 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.288126 | 5251.79 | 3567.63 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.269745 | 4979.44 | 3360.34 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.254876 | 4752.39 | 3191.09 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.227598 | 4333.24 | 2878.05 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.136796 | 2933.17 | 1856.14 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.135975 | 2920.85 | 1847.06 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.175531 | 3540.03 | 2302.12 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.176139 | 3548.77 | 2308.79 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.287886 | 5262.02 | 3569.34 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.269707 | 4992.36 | 3364.27 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.254808 | 4764.71 | 3194.69 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.227736 | 4353.82 | 2887.02 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.137465 | 2949.97 | 1866.04 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.136654 | 2937.77 | 1857.06 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.175673 | 3549.61 | 2306.27 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.176281 | 3558.35 | 2312.93 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.295197 | 5379.36 | 3653.76 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.277225 | 5112.77 | 3450.96 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.258645 | 4832.22 | 3240.89 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.231264 | 4416.77 | 2929.78 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.144860 | 3066.27 | 1949.83 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.144053 | 3054.17 | 1940.90 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.180689 | 3629.65 | 2363.94 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.181360 | 3639.31 | 2371.30 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.353305 | 6227.30 | 4299.89 | 0.000136 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.331335 | 5903.58 | 4052.75 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.307598 | 5551.15 | 3785.31 | 0.000121 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.271931 | 5022.58 | 3384.49 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.188188 | 3746.82 | 2449.66 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.188262 | 3747.64 | 2450.39 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.240158 | 4494.04 | 3020.53 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.240929 | 4504.97 | 3028.97 | 0.000098 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.251203 | 0.251203 | 0.251203 | 0.251203 | 4563.88 | 4563.88 | 1705.49 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.233413 | 0.233413 | 0.233413 | 0.233413 | 4297.11 | 4297.11 | 1700.37 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.320355 | 0.320355 | 0.320355 | 0.320355 | 5878.40 | 5878.40 | 2346.75 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.193551 | 0.193551 | 0.193551 | 0.193551 | 3688.42 | 3688.42 | 1700.37 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.107651 | 0.107651 | 0.107651 | 0.107651 | 2416.46 | 2416.46 | 1197.34 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.106554 | 0.106554 | 0.106554 | 0.106554 | 2399.94 | 2399.94 | 1197.34 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.147219 | 0.147219 | 0.147219 | 0.147219 | 3038.39 | 3038.39 | 1200.38 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.151947 | 0.151947 | 0.151947 | 0.151947 | 3106.59 | 3106.59 | 1208.79 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.292889 | 0.292889 | 0.292889 | 0.292889 | 5208.47 | 5208.47 | 1642.13 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.272466 | 0.272466 | 0.272466 | 0.272466 | 4908.76 | 4908.76 | 1637.22 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.274566 | 0.274566 | 0.274566 | 0.274566 | 4924.55 | 4924.55 | 1668.43 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.228129 | 0.228129 | 0.228129 | 0.228129 | 4234.91 | 4234.91 | 1637.22 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.133724 | 0.133724 | 0.133724 | 0.133724 | 2832.21 | 2832.21 | 1110.74 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.132858 | 0.132858 | 0.132858 | 0.132858 | 2819.34 | 2819.34 | 1110.74 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.175995 | 0.175995 | 0.175995 | 0.175995 | 3485.83 | 3485.83 | 1110.74 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.177683 | 0.177683 | 0.177683 | 0.177683 | 3510.09 | 3510.09 | 1110.74 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.291996 | 0.291996 | 0.291996 | 0.291996 | 5229.11 | 5229.11 | 1618.17 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.272472 | 0.272472 | 0.272472 | 0.272472 | 4941.72 | 4941.72 | 1614.57 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.259502 | 0.259502 | 0.259502 | 0.259502 | 4742.64 | 4742.64 | 1621.51 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.229421 | 0.229421 | 0.229421 | 0.229421 | 4285.20 | 4285.20 | 1614.57 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.135682 | 0.135682 | 0.135682 | 0.135682 | 2877.69 | 2877.69 | 1110.74 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.134826 | 0.134826 | 0.134826 | 0.134826 | 2864.95 | 2864.95 | 1110.74 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.177080 | 0.177080 | 0.177080 | 0.177080 | 3519.71 | 3519.71 | 1110.74 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.177852 | 0.177852 | 0.177852 | 0.177852 | 3530.77 | 3530.77 | 1110.74 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.291733 | 0.291733 | 0.291733 | 0.291733 | 5250.32 | 5250.32 | 1627.15 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.272579 | 0.272579 | 0.272579 | 0.272579 | 4967.87 | 4967.87 | 1625.28 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.257952 | 0.257952 | 0.257952 | 0.257952 | 4744.89 | 4744.89 | 1627.56 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.229771 | 0.229771 | 0.229771 | 0.229771 | 4314.05 | 4314.05 | 1625.28 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.136968 | 0.136968 | 0.136968 | 0.136968 | 2909.18 | 2909.18 | 1110.74 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.136120 | 0.136120 | 0.136120 | 0.136120 | 2896.54 | 2896.54 | 1110.74 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.177539 | 0.177539 | 0.177539 | 0.177539 | 3540.03 | 3540.03 | 1110.74 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.178174 | 0.178174 | 0.178174 | 0.178174 | 3549.13 | 3549.13 | 1110.74 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.293779 | 0.293779 | 0.293779 | 0.293779 | 5299.91 | 5299.91 | 1619.95 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.274980 | 0.274980 | 0.274980 | 0.274980 | 5022.30 | 5022.30 | 1618.36 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.260041 | 0.260041 | 0.260041 | 0.260041 | 4794.68 | 4794.68 | 1620.00 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.232349 | 0.232349 | 0.232349 | 0.232349 | 4370.47 | 4370.47 | 1618.36 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.140215 | 0.140215 | 0.140215 | 0.140215 | 2967.41 | 2967.41 | 1110.74 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.139374 | 0.139374 | 0.139374 | 0.139374 | 2954.87 | 2954.87 | 1110.74 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.180068 | 0.180068 | 0.180068 | 0.180068 | 3587.83 | 3587.83 | 1110.74 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.180682 | 0.180682 | 0.180682 | 0.180682 | 3596.63 | 3596.63 | 1110.74 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.289799 | 0.289799 | 0.289799 | 0.289799 | 5260.45 | 5260.45 | 1677.05 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.271177 | 0.271177 | 0.271177 | 0.271177 | 4984.97 | 4984.97 | 1677.50 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.256312 | 0.256312 | 0.256312 | 0.256312 | 4758.17 | 4758.17 | 1677.06 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.228812 | 0.228812 | 0.228812 | 0.228812 | 4336.22 | 4336.22 | 1677.50 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.137427 | 0.137427 | 0.137427 | 0.137427 | 2934.90 | 2934.90 | 1110.74 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.136598 | 0.136598 | 0.136598 | 0.136598 | 2922.48 | 2922.48 | 1110.74 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.176704 | 0.176704 | 0.176704 | 0.176704 | 3548.68 | 3548.68 | 1110.74 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.177314 | 0.177314 | 0.177314 | 0.177314 | 3557.43 | 3557.43 | 1110.74 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.288126 | 0.288126 | 0.288126 | 0.288126 | 5251.79 | 5251.79 | 1711.56 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.269745 | 0.269745 | 0.269745 | 0.269745 | 4979.44 | 4979.44 | 1712.79 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.254876 | 0.254876 | 0.254876 | 0.254876 | 4752.39 | 4752.39 | 1711.56 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.227598 | 0.227598 | 0.227598 | 0.227598 | 4333.24 | 4333.24 | 1712.79 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.136796 | 0.136796 | 0.136796 | 0.136796 | 2933.17 | 2933.17 | 1110.74 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.135975 | 0.135975 | 0.135975 | 0.135975 | 2920.85 | 2920.85 | 1110.74 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.175531 | 0.175531 | 0.175531 | 0.175531 | 3540.03 | 3540.03 | 1110.74 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.176139 | 0.176139 | 0.176139 | 0.176139 | 3548.77 | 3548.77 | 1110.74 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.287886 | 0.287886 | 0.287886 | 0.287886 | 5262.02 | 5262.02 | 1747.21 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.269707 | 0.269707 | 0.269707 | 0.269707 | 4992.36 | 4992.36 | 1749.00 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.254808 | 0.254808 | 0.254808 | 0.254808 | 4764.71 | 4764.71 | 1747.21 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.227736 | 0.227736 | 0.227736 | 0.227736 | 4353.82 | 4353.82 | 1749.00 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.137465 | 0.137465 | 0.137465 | 0.137465 | 2949.97 | 2949.97 | 1110.74 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.136654 | 0.136654 | 0.136654 | 0.136654 | 2937.77 | 2937.77 | 1110.74 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.175673 | 0.175673 | 0.175673 | 0.175673 | 3549.61 | 3549.61 | 1110.74 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.176281 | 0.176281 | 0.176281 | 0.176281 | 3558.35 | 3558.35 | 1110.74 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.295197 | 0.295197 | 0.295197 | 0.295197 | 5379.36 | 5379.36 | 1858.38 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.277225 | 0.277225 | 0.277225 | 0.277225 | 5112.77 | 5112.77 | 1859.28 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.258645 | 0.258645 | 0.258645 | 0.258645 | 4832.22 | 4832.22 | 1858.38 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.231264 | 0.231264 | 0.231264 | 0.231264 | 4416.77 | 4416.77 | 1859.28 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.144860 | 0.144860 | 0.144860 | 0.144860 | 3066.27 | 3066.27 | 1186.34 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.144053 | 0.144053 | 0.144053 | 0.144053 | 3054.17 | 3054.17 | 1186.34 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.180689 | 0.180689 | 0.180689 | 0.180689 | 3629.65 | 3629.65 | 1185.33 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.181360 | 0.181360 | 0.181360 | 0.181360 | 3639.31 | 3639.31 | 1185.33 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.353305 | 0.353305 | 0.353305 | 0.353305 | 6227.30 | 6227.30 | 2230.96 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.331335 | 0.331335 | 0.331335 | 0.331335 | 5903.58 | 5903.58 | 2236.06 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.307598 | 0.307598 | 0.307598 | 0.307598 | 5551.15 | 5551.15 | 2230.96 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.271931 | 0.271931 | 0.271931 | 0.271931 | 5022.58 | 5022.58 | 2236.06 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.188188 | 0.188188 | 0.188188 | 0.188188 | 3746.82 | 3746.82 | 1590.70 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.188262 | 0.188262 | 0.188262 | 0.188262 | 3747.64 | 3747.64 | 1590.70 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.240158 | 0.240158 | 0.240158 | 0.240158 | 4494.04 | 4494.04 | 1584.65 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.240929 | 0.240929 | 0.240929 | 0.240929 | 4504.97 | 4504.97 | 1584.65 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.251203 |
AIRLOOP G NW SUPPLY FAN | 0.233413 |
AIRLOOP OFFICE SUPPLY FAN | 0.320355 |
AIRLOOP G NE SUPPLY FAN | 0.193551 |
AIRLOOP G N1 SUPPLY FAN | 0.107651 |
AIRLOOP G N2 SUPPLY FAN | 0.106554 |
AIRLOOP G S1 SUPPLY FAN | 0.147219 |
AIRLOOP G S2 SUPPLY FAN | 0.151947 |
AIRLOOP F2 SW SUPPLY FAN | 0.292889 |
AIRLOOP F2 NW SUPPLY FAN | 0.272466 |
AIRLOOP F2 SE SUPPLY FAN | 0.274566 |
AIRLOOP F2 NE SUPPLY FAN | 0.228129 |
AIRLOOP F2 N1 SUPPLY FAN | 0.133724 |
AIRLOOP F2 N2 SUPPLY FAN | 0.132858 |
AIRLOOP F2 S1 SUPPLY FAN | 0.175995 |
AIRLOOP F2 S2 SUPPLY FAN | 0.177683 |
AIRLOOP F3 SW SUPPLY FAN | 0.291996 |
AIRLOOP F3 NW SUPPLY FAN | 0.272472 |
AIRLOOP F3 SE SUPPLY FAN | 0.259502 |
AIRLOOP F3 NE SUPPLY FAN | 0.229421 |
AIRLOOP F3 N1 SUPPLY FAN | 0.135682 |
AIRLOOP F3 N2 SUPPLY FAN | 0.134826 |
AIRLOOP F3 S1 SUPPLY FAN | 0.177080 |
AIRLOOP F3 S2 SUPPLY FAN | 0.177852 |
AIRLOOP F4 SW SUPPLY FAN | 0.291733 |
AIRLOOP F4 NW SUPPLY FAN | 0.272579 |
AIRLOOP F4 SE SUPPLY FAN | 0.257952 |
AIRLOOP F4 NE SUPPLY FAN | 0.229771 |
AIRLOOP F4 N1 SUPPLY FAN | 0.136968 |
AIRLOOP F4 N2 SUPPLY FAN | 0.136120 |
AIRLOOP F4 S1 SUPPLY FAN | 0.177539 |
AIRLOOP F4 S2 SUPPLY FAN | 0.178174 |
AIRLOOP M SW SUPPLY FAN | 0.293779 |
AIRLOOP M NW SUPPLY FAN | 0.274980 |
AIRLOOP M SE SUPPLY FAN | 0.260041 |
AIRLOOP M NE SUPPLY FAN | 0.232349 |
AIRLOOP M N1 SUPPLY FAN | 0.140215 |
AIRLOOP M N2 SUPPLY FAN | 0.139374 |
AIRLOOP M S1 SUPPLY FAN | 0.180068 |
AIRLOOP M S2 SUPPLY FAN | 0.180682 |
AIRLOOP F6 SW SUPPLY FAN | 0.289799 |
AIRLOOP F6 NW SUPPLY FAN | 0.271177 |
AIRLOOP F6 SE SUPPLY FAN | 0.256312 |
AIRLOOP F6 NE SUPPLY FAN | 0.228812 |
AIRLOOP F6 N1 SUPPLY FAN | 0.137427 |
AIRLOOP F6 N2 SUPPLY FAN | 0.136598 |
AIRLOOP F6 S1 SUPPLY FAN | 0.176704 |
AIRLOOP F6 S2 SUPPLY FAN | 0.177314 |
AIRLOOP F7 SW SUPPLY FAN | 0.288126 |
AIRLOOP F7 NW SUPPLY FAN | 0.269745 |
AIRLOOP F7 SE SUPPLY FAN | 0.254876 |
AIRLOOP F7 NE SUPPLY FAN | 0.227598 |
AIRLOOP F7 N1 SUPPLY FAN | 0.136796 |
AIRLOOP F7 N2 SUPPLY FAN | 0.135975 |
AIRLOOP F7 S1 SUPPLY FAN | 0.175531 |
AIRLOOP F7 S2 SUPPLY FAN | 0.176139 |
AIRLOOP F8 SW SUPPLY FAN | 0.287886 |
AIRLOOP F8 NW SUPPLY FAN | 0.269707 |
AIRLOOP F8 SE SUPPLY FAN | 0.254808 |
AIRLOOP F8 NE SUPPLY FAN | 0.227736 |
AIRLOOP F8 N1 SUPPLY FAN | 0.137465 |
AIRLOOP F8 N2 SUPPLY FAN | 0.136654 |
AIRLOOP F8 S1 SUPPLY FAN | 0.175673 |
AIRLOOP F8 S2 SUPPLY FAN | 0.176281 |
AIRLOOP F9 SW SUPPLY FAN | 0.295197 |
AIRLOOP F9 NW SUPPLY FAN | 0.277225 |
AIRLOOP F9 SE SUPPLY FAN | 0.258645 |
AIRLOOP F9 NE SUPPLY FAN | 0.231264 |
AIRLOOP F9 N1 SUPPLY FAN | 0.144860 |
AIRLOOP F9 N2 SUPPLY FAN | 0.144053 |
AIRLOOP F9 S1 SUPPLY FAN | 0.180689 |
AIRLOOP F9 S2 SUPPLY FAN | 0.181360 |
AIRLOOP T SW SUPPLY FAN | 0.353305 |
AIRLOOP T NW SUPPLY FAN | 0.331335 |
AIRLOOP T SE SUPPLY FAN | 0.307598 |
AIRLOOP T NE SUPPLY FAN | 0.271931 |
AIRLOOP T N1 SUPPLY FAN | 0.188188 |
AIRLOOP T N2 SUPPLY FAN | 0.188262 |
AIRLOOP T S1 SUPPLY FAN | 0.240158 |
AIRLOOP T S2 SUPPLY FAN | 0.240929 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.251203 | 4563.88 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.233413 | 4297.11 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.320355 | 5878.40 | 0.000128 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.193551 | 3688.42 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.107651 | 2416.46 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.106554 | 2399.94 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.147219 | 3038.39 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.151947 | 3106.59 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.292889 | 5208.47 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.272466 | 4908.76 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.274566 | 4924.55 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.228129 | 4234.91 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.133724 | 2832.21 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.132858 | 2819.34 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.175995 | 3485.83 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.177683 | 3510.09 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.291996 | 5229.11 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.272472 | 4941.72 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.259502 | 4742.64 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.229421 | 4285.20 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.135682 | 2877.69 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.134826 | 2864.95 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.177080 | 3519.71 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.177852 | 3530.77 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.291733 | 5250.32 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.272579 | 4967.87 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.257952 | 4744.89 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.229771 | 4314.05 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.136968 | 2909.18 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.136120 | 2896.54 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.177539 | 3540.03 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.178174 | 3549.13 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.293779 | 5299.91 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.274980 | 5022.30 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.260041 | 4794.68 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.232349 | 4370.47 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.140215 | 2967.41 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.139374 | 2954.87 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.180068 | 3587.83 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.180682 | 3596.63 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.289799 | 5260.45 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.271177 | 4984.97 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.256312 | 4758.17 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.228812 | 4336.22 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.137427 | 2934.90 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.136598 | 2922.48 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.176704 | 3548.68 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.177314 | 3557.43 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.288126 | 5251.79 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.269745 | 4979.44 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.254876 | 4752.39 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.227598 | 4333.24 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.136796 | 2933.17 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.135975 | 2920.85 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.175531 | 3540.03 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.176139 | 3548.77 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.287886 | 5262.02 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.269707 | 4992.36 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.254808 | 4764.71 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.227736 | 4353.82 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.137465 | 2949.97 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.136654 | 2937.77 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.175673 | 3549.61 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.176281 | 3558.35 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.295197 | 5379.36 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.277225 | 5112.77 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.258645 | 4832.22 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.231264 | 4416.77 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.144860 | 3066.27 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.144053 | 3054.17 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.180689 | 3629.65 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.181360 | 3639.31 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.353305 | 6227.30 | 0.000136 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.331335 | 5903.58 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.307598 | 5551.15 | 0.000121 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.271931 | 5022.58 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.188188 | 3746.82 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.188262 | 3747.64 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.240158 | 4494.04 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.240929 | 4504.97 | 0.000098 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 1705.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 1700.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2346.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 1700.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1197.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1197.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1200.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1208.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 1642.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 1637.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 1668.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 1637.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1618.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1614.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1621.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1614.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1627.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1625.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1627.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1625.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1619.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1618.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1620.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1618.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 1677.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 1677.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 1677.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 1677.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 1711.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 1712.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 1711.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 1712.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 1747.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 1749.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 1747.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 1749.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1110.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 1858.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 1859.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 1858.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 1859.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1186.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1186.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1185.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1185.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2230.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2236.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2230.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2236.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 1590.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 1590.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 1584.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 1584.65 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.007150 | 8.04 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.007150 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.007150 | 3451.82 | 9.09 | 10702.47 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.007150 | 1823.72 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 13.57 |
February | 23.37 | 15.49 |
March | 23.41 | 17.07 |
April | 24.02 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.26 | 24.23 |
November | 23.88 | 18.91 |
December | 23.42 | 15.68 |
Annual Sum or Average | 23.97 | 21.89 |
Minimum of Months | 23.22 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 13.57 |
February | 22.89 | 15.49 |
March | 23.18 | 17.07 |
April | 23.96 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.19 | 24.23 |
November | 23.48 | 18.91 |
December | 22.87 | 15.68 |
Annual Sum or Average | 23.76 | 21.89 |
Minimum of Months | 22.55 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.26 | 13.57 |
February | 23.53 | 15.49 |
March | 23.64 | 17.07 |
April | 24.16 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 23.95 | 18.91 |
December | 23.49 | 15.68 |
Annual Sum or Average | 24.03 | 21.89 |
Minimum of Months | 23.26 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 13.57 |
February | 22.83 | 15.49 |
March | 23.17 | 17.07 |
April | 23.94 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.41 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.18 | 24.23 |
November | 23.46 | 18.91 |
December | 22.80 | 15.68 |
Annual Sum or Average | 23.74 | 21.89 |
Minimum of Months | 22.48 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 13.57 |
February | 22.67 | 15.49 |
March | 23.00 | 17.07 |
April | 23.81 | 21.23 |
May | 24.40 | 26.90 |
June | 24.41 | 27.61 |
July | 24.44 | 27.94 |
August | 24.42 | 27.43 |
September | 24.41 | 26.23 |
October | 24.15 | 24.23 |
November | 23.31 | 18.91 |
December | 22.70 | 15.68 |
Annual Sum or Average | 23.68 | 21.89 |
Minimum of Months | 22.35 | 13.57 |
Maximum of Months | 24.44 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 13.57 |
February | 22.67 | 15.49 |
March | 23.00 | 17.07 |
April | 23.81 | 21.23 |
May | 24.40 | 26.90 |
June | 24.41 | 27.61 |
July | 24.45 | 27.94 |
August | 24.42 | 27.43 |
September | 24.41 | 26.23 |
October | 24.15 | 24.23 |
November | 23.31 | 18.91 |
December | 22.70 | 15.68 |
Annual Sum or Average | 23.68 | 21.89 |
Minimum of Months | 22.35 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 13.57 |
February | 23.37 | 15.49 |
March | 23.39 | 17.07 |
April | 23.96 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.28 | 24.23 |
November | 23.93 | 18.91 |
December | 23.49 | 15.68 |
Annual Sum or Average | 23.98 | 21.89 |
Minimum of Months | 23.28 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 13.57 |
February | 23.39 | 15.49 |
March | 23.41 | 17.07 |
April | 23.97 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.28 | 24.23 |
November | 23.95 | 18.91 |
December | 23.51 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 23.29 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | 13.57 |
February | 21.42 | 15.49 |
March | 22.03 | 17.07 |
April | 23.81 | 21.23 |
May | 25.96 | 26.90 |
June | 26.78 | 27.61 |
July | 26.88 | 27.94 |
August | 26.73 | 27.43 |
September | 26.25 | 26.23 |
October | 25.09 | 24.23 |
November | 22.89 | 18.91 |
December | 21.49 | 15.68 |
Annual Sum or Average | 24.18 | 21.89 |
Minimum of Months | 20.67 | 13.57 |
Maximum of Months | 26.88 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 13.57 |
February | 23.87 | 15.49 |
March | 23.85 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.36 | 24.23 |
November | 24.26 | 18.91 |
December | 23.89 | 15.68 |
Annual Sum or Average | 24.19 | 21.89 |
Minimum of Months | 23.76 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | 13.57 |
February | 23.33 | 15.49 |
March | 23.60 | 17.07 |
April | 24.25 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.30 | 24.23 |
November | 23.94 | 18.91 |
December | 23.24 | 15.68 |
Annual Sum or Average | 23.97 | 21.89 |
Minimum of Months | 22.91 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.79 | 13.57 |
February | 23.91 | 15.49 |
March | 23.90 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.37 | 24.23 |
November | 24.28 | 18.91 |
December | 23.90 | 15.68 |
Annual Sum or Average | 24.21 | 21.89 |
Minimum of Months | 23.79 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 13.57 |
February | 23.29 | 15.49 |
March | 23.58 | 17.07 |
April | 24.25 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.28 | 24.23 |
November | 23.92 | 18.91 |
December | 23.15 | 15.68 |
Annual Sum or Average | 23.94 | 21.89 |
Minimum of Months | 22.84 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 13.57 |
February | 23.21 | 15.49 |
March | 23.50 | 17.07 |
April | 24.19 | 21.23 |
May | 24.41 | 26.90 |
June | 24.42 | 27.61 |
July | 24.44 | 27.94 |
August | 24.42 | 27.43 |
September | 24.41 | 26.23 |
October | 24.28 | 24.23 |
November | 23.86 | 18.91 |
December | 23.14 | 15.68 |
Annual Sum or Average | 23.92 | 21.89 |
Minimum of Months | 22.77 | 13.57 |
Maximum of Months | 24.44 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 13.57 |
February | 23.20 | 15.49 |
March | 23.50 | 17.07 |
April | 24.19 | 21.23 |
May | 24.41 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.42 | 27.43 |
September | 24.42 | 26.23 |
October | 24.28 | 24.23 |
November | 23.85 | 18.91 |
December | 23.13 | 15.68 |
Annual Sum or Average | 23.92 | 21.89 |
Minimum of Months | 22.77 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.94 | 13.57 |
February | 23.96 | 15.49 |
March | 23.90 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.41 | 24.23 |
November | 24.33 | 18.91 |
December | 24.04 | 15.68 |
Annual Sum or Average | 24.24 | 21.89 |
Minimum of Months | 23.90 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.94 | 13.57 |
February | 23.97 | 15.49 |
March | 23.91 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.41 | 24.23 |
November | 24.33 | 18.91 |
December | 24.04 | 15.68 |
Annual Sum or Average | 24.24 | 21.89 |
Minimum of Months | 23.91 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.31 | 13.57 |
February | 24.70 | 15.49 |
March | 24.91 | 17.07 |
April | 25.83 | 21.23 |
May | 26.44 | 26.90 |
June | 26.67 | 27.61 |
July | 26.70 | 27.94 |
August | 26.66 | 27.43 |
September | 26.54 | 26.23 |
October | 26.22 | 24.23 |
November | 25.48 | 18.91 |
December | 24.68 | 15.68 |
Annual Sum or Average | 25.77 | 21.89 |
Minimum of Months | 24.31 | 13.57 |
Maximum of Months | 26.70 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.85 | 13.57 |
February | 23.94 | 15.49 |
March | 23.90 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.36 | 24.23 |
November | 24.30 | 18.91 |
December | 23.96 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.85 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 13.57 |
February | 23.41 | 15.49 |
March | 23.66 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.31 | 24.23 |
November | 24.03 | 18.91 |
December | 23.33 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 22.98 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.84 | 13.57 |
February | 23.93 | 15.49 |
March | 23.91 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.39 | 24.23 |
November | 24.31 | 18.91 |
December | 23.94 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.84 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 13.57 |
February | 23.38 | 15.49 |
March | 23.65 | 17.07 |
April | 24.28 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.29 | 24.23 |
November | 24.01 | 18.91 |
December | 23.23 | 15.68 |
Annual Sum or Average | 23.98 | 21.89 |
Minimum of Months | 22.92 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | 13.57 |
February | 23.34 | 15.49 |
March | 23.62 | 17.07 |
April | 24.25 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 23.99 | 18.91 |
December | 23.29 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 22.91 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 13.57 |
February | 23.34 | 15.49 |
March | 23.62 | 17.07 |
April | 24.25 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 23.99 | 18.91 |
December | 23.28 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 22.90 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.06 | 13.57 |
February | 24.06 | 15.49 |
March | 23.99 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.14 | 15.68 |
Annual Sum or Average | 24.28 | 21.89 |
Minimum of Months | 23.99 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.06 | 13.57 |
February | 24.06 | 15.49 |
March | 23.99 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.14 | 15.68 |
Annual Sum or Average | 24.28 | 21.89 |
Minimum of Months | 23.99 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.77 | 13.57 |
February | 25.14 | 15.49 |
March | 25.30 | 17.07 |
April | 26.15 | 21.23 |
May | 26.62 | 26.90 |
June | 26.73 | 27.61 |
July | 26.74 | 27.94 |
August | 26.70 | 27.43 |
September | 26.61 | 26.23 |
October | 26.43 | 24.23 |
November | 25.86 | 18.91 |
December | 25.11 | 15.68 |
Annual Sum or Average | 26.02 | 21.89 |
Minimum of Months | 24.77 | 13.57 |
Maximum of Months | 26.74 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.86 | 13.57 |
February | 23.94 | 15.49 |
March | 23.89 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.36 | 24.23 |
November | 24.31 | 18.91 |
December | 23.96 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.86 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 13.57 |
February | 23.42 | 15.49 |
March | 23.66 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.30 | 24.23 |
November | 24.05 | 18.91 |
December | 23.34 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 22.98 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.84 | 13.57 |
February | 23.92 | 15.49 |
March | 23.90 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.39 | 24.23 |
November | 24.31 | 18.91 |
December | 23.93 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.84 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 13.57 |
February | 23.39 | 15.49 |
March | 23.65 | 17.07 |
April | 24.28 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.29 | 24.23 |
November | 24.03 | 18.91 |
December | 23.24 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 22.92 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.94 | 13.57 |
February | 23.38 | 15.49 |
March | 23.64 | 17.07 |
April | 24.26 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 24.02 | 18.91 |
December | 23.32 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 22.94 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 13.57 |
February | 23.37 | 15.49 |
March | 23.64 | 17.07 |
April | 24.26 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 24.02 | 18.91 |
December | 23.31 | 15.68 |
Annual Sum or Average | 24.00 | 21.89 |
Minimum of Months | 22.93 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.07 | 13.57 |
February | 24.07 | 15.49 |
March | 24.00 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.15 | 15.68 |
Annual Sum or Average | 24.29 | 21.89 |
Minimum of Months | 24.00 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.07 | 13.57 |
February | 24.07 | 15.49 |
March | 24.00 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.15 | 15.68 |
Annual Sum or Average | 24.29 | 21.89 |
Minimum of Months | 24.00 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.93 | 13.57 |
February | 25.30 | 15.49 |
March | 25.44 | 17.07 |
April | 26.28 | 21.23 |
May | 26.73 | 26.90 |
June | 26.82 | 27.61 |
July | 26.83 | 27.94 |
August | 26.78 | 27.43 |
September | 26.69 | 26.23 |
October | 26.54 | 24.23 |
November | 26.01 | 18.91 |
December | 25.26 | 15.68 |
Annual Sum or Average | 26.14 | 21.89 |
Minimum of Months | 24.93 | 13.57 |
Maximum of Months | 26.83 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.85 | 13.57 |
February | 23.93 | 15.49 |
March | 23.88 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.36 | 24.23 |
November | 24.31 | 18.91 |
December | 23.96 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.85 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 13.57 |
February | 23.43 | 15.49 |
March | 23.66 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.30 | 24.23 |
November | 24.05 | 18.91 |
December | 23.34 | 15.68 |
Annual Sum or Average | 24.01 | 21.89 |
Minimum of Months | 22.98 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.83 | 13.57 |
February | 23.91 | 15.49 |
March | 23.89 | 17.07 |
April | 24.32 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.39 | 24.23 |
November | 24.31 | 18.91 |
December | 23.93 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.83 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 13.57 |
February | 23.40 | 15.49 |
March | 23.65 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.29 | 24.23 |
November | 24.04 | 18.91 |
December | 23.24 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 22.92 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 13.57 |
February | 23.40 | 15.49 |
March | 23.65 | 17.07 |
April | 24.26 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 24.04 | 18.91 |
December | 23.34 | 15.68 |
Annual Sum or Average | 24.01 | 21.89 |
Minimum of Months | 22.96 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.95 | 13.57 |
February | 23.39 | 15.49 |
March | 23.65 | 17.07 |
April | 24.26 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.30 | 24.23 |
November | 24.04 | 18.91 |
December | 23.33 | 15.68 |
Annual Sum or Average | 24.01 | 21.89 |
Minimum of Months | 22.95 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.57 |
February | 24.07 | 15.49 |
March | 23.99 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.15 | 15.68 |
Annual Sum or Average | 24.29 | 21.89 |
Minimum of Months | 23.99 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 13.57 |
February | 24.07 | 15.49 |
March | 24.00 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.38 | 18.91 |
December | 24.15 | 15.68 |
Annual Sum or Average | 24.29 | 21.89 |
Minimum of Months | 24.00 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.55 | 13.57 |
February | 25.91 | 15.49 |
March | 26.05 | 17.07 |
April | 26.88 | 21.23 |
May | 27.32 | 26.90 |
June | 27.40 | 27.61 |
July | 27.41 | 27.94 |
August | 27.37 | 27.43 |
September | 27.28 | 26.23 |
October | 27.13 | 24.23 |
November | 26.62 | 18.91 |
December | 25.88 | 15.68 |
Annual Sum or Average | 26.74 | 21.89 |
Minimum of Months | 25.55 | 13.57 |
Maximum of Months | 27.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.79 | 13.57 |
February | 23.88 | 15.49 |
March | 23.84 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.35 | 24.23 |
November | 24.29 | 18.91 |
December | 23.91 | 15.68 |
Annual Sum or Average | 24.20 | 21.89 |
Minimum of Months | 23.79 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | 13.57 |
February | 23.37 | 15.49 |
March | 23.60 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.28 | 24.23 |
November | 24.00 | 18.91 |
December | 23.25 | 15.68 |
Annual Sum or Average | 23.97 | 21.89 |
Minimum of Months | 22.91 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 13.57 |
February | 23.86 | 15.49 |
March | 23.84 | 17.07 |
April | 24.31 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.38 | 24.23 |
November | 24.29 | 18.91 |
December | 23.87 | 15.68 |
Annual Sum or Average | 24.20 | 21.89 |
Minimum of Months | 23.77 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 13.57 |
February | 23.34 | 15.49 |
March | 23.59 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.27 | 24.23 |
November | 23.98 | 18.91 |
December | 23.16 | 15.68 |
Annual Sum or Average | 23.96 | 21.89 |
Minimum of Months | 22.84 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 13.57 |
February | 23.34 | 15.49 |
March | 23.59 | 17.07 |
April | 24.24 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.29 | 24.23 |
November | 23.98 | 18.91 |
December | 23.25 | 15.68 |
Annual Sum or Average | 23.98 | 21.89 |
Minimum of Months | 22.88 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 13.57 |
February | 23.33 | 15.49 |
March | 23.58 | 17.07 |
April | 24.24 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.29 | 24.23 |
November | 23.98 | 18.91 |
December | 23.24 | 15.68 |
Annual Sum or Average | 23.98 | 21.89 |
Minimum of Months | 22.87 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 13.57 |
February | 24.03 | 15.49 |
March | 23.95 | 17.07 |
April | 24.30 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.37 | 18.91 |
December | 24.11 | 15.68 |
Annual Sum or Average | 24.27 | 21.89 |
Minimum of Months | 23.95 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 13.57 |
February | 24.03 | 15.49 |
March | 23.95 | 17.07 |
April | 24.30 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.37 | 18.91 |
December | 24.11 | 15.68 |
Annual Sum or Average | 24.27 | 21.89 |
Minimum of Months | 23.95 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.86 | 13.57 |
February | 25.24 | 15.49 |
March | 25.38 | 17.07 |
April | 26.26 | 21.23 |
May | 26.72 | 26.90 |
June | 26.81 | 27.61 |
July | 26.82 | 27.94 |
August | 26.77 | 27.43 |
September | 26.68 | 26.23 |
October | 26.51 | 24.23 |
November | 25.98 | 18.91 |
December | 25.20 | 15.68 |
Annual Sum or Average | 26.11 | 21.89 |
Minimum of Months | 24.86 | 13.57 |
Maximum of Months | 26.82 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 13.57 |
February | 23.84 | 15.49 |
March | 23.80 | 17.07 |
April | 24.30 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.35 | 24.23 |
November | 24.28 | 18.91 |
December | 23.87 | 15.68 |
Annual Sum or Average | 24.18 | 21.89 |
Minimum of Months | 23.74 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 13.57 |
February | 23.32 | 15.49 |
March | 23.56 | 17.07 |
April | 24.26 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.27 | 24.23 |
November | 23.96 | 18.91 |
December | 23.19 | 15.68 |
Annual Sum or Average | 23.95 | 21.89 |
Minimum of Months | 22.85 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.72 | 13.57 |
February | 23.82 | 15.49 |
March | 23.81 | 17.07 |
April | 24.30 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.37 | 24.23 |
November | 24.28 | 18.91 |
December | 23.83 | 15.68 |
Annual Sum or Average | 24.18 | 21.89 |
Minimum of Months | 23.72 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 13.57 |
February | 23.29 | 15.49 |
March | 23.55 | 17.07 |
April | 24.25 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.26 | 24.23 |
November | 23.94 | 18.91 |
December | 23.10 | 15.68 |
Annual Sum or Average | 23.94 | 21.89 |
Minimum of Months | 22.79 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 13.57 |
February | 23.29 | 15.49 |
March | 23.54 | 17.07 |
April | 24.23 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.28 | 24.23 |
November | 23.94 | 18.91 |
December | 23.19 | 15.68 |
Annual Sum or Average | 23.96 | 21.89 |
Minimum of Months | 22.82 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 13.57 |
February | 23.29 | 15.49 |
March | 23.54 | 17.07 |
April | 24.23 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.43 | 26.23 |
October | 24.28 | 24.23 |
November | 23.94 | 18.91 |
December | 23.18 | 15.68 |
Annual Sum or Average | 23.95 | 21.89 |
Minimum of Months | 22.81 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 13.57 |
February | 23.99 | 15.49 |
March | 23.91 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.36 | 18.91 |
December | 24.08 | 15.68 |
Annual Sum or Average | 24.26 | 21.89 |
Minimum of Months | 23.91 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.99 | 13.57 |
February | 23.99 | 15.49 |
March | 23.91 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.43 | 24.23 |
November | 24.36 | 18.91 |
December | 24.07 | 15.68 |
Annual Sum or Average | 24.26 | 21.89 |
Minimum of Months | 23.91 | 13.57 |
Maximum of Months | 24.43 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.71 | 13.57 |
February | 25.10 | 15.49 |
March | 25.24 | 17.07 |
April | 26.16 | 21.23 |
May | 26.64 | 26.90 |
June | 26.73 | 27.61 |
July | 26.74 | 27.94 |
August | 26.69 | 27.43 |
September | 26.60 | 26.23 |
October | 26.42 | 24.23 |
November | 25.86 | 18.91 |
December | 25.05 | 15.68 |
Annual Sum or Average | 26.00 | 21.89 |
Minimum of Months | 24.71 | 13.57 |
Maximum of Months | 26.74 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 13.57 |
February | 23.81 | 15.49 |
March | 23.77 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.34 | 24.23 |
November | 24.27 | 18.91 |
December | 23.83 | 15.68 |
Annual Sum or Average | 24.17 | 21.89 |
Minimum of Months | 23.69 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 13.57 |
February | 23.29 | 15.49 |
March | 23.53 | 17.07 |
April | 24.25 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.26 | 24.23 |
November | 23.92 | 18.91 |
December | 23.14 | 15.68 |
Annual Sum or Average | 23.93 | 21.89 |
Minimum of Months | 22.81 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 13.57 |
February | 23.78 | 15.49 |
March | 23.77 | 17.07 |
April | 24.29 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.37 | 24.23 |
November | 24.27 | 18.91 |
December | 23.79 | 15.68 |
Annual Sum or Average | 24.16 | 21.89 |
Minimum of Months | 23.67 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 13.57 |
February | 23.26 | 15.49 |
March | 23.52 | 17.07 |
April | 24.24 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.24 | 24.23 |
November | 23.90 | 18.91 |
December | 23.06 | 15.68 |
Annual Sum or Average | 23.92 | 21.89 |
Minimum of Months | 22.75 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 13.57 |
February | 23.25 | 15.49 |
March | 23.50 | 17.07 |
April | 24.21 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.27 | 24.23 |
November | 23.90 | 18.91 |
December | 23.14 | 15.68 |
Annual Sum or Average | 23.94 | 21.89 |
Minimum of Months | 22.77 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 13.57 |
February | 23.25 | 15.49 |
March | 23.50 | 17.07 |
April | 24.21 | 21.23 |
May | 24.43 | 26.90 |
June | 24.42 | 27.61 |
July | 24.45 | 27.94 |
August | 24.43 | 27.43 |
September | 24.43 | 26.23 |
October | 24.27 | 24.23 |
November | 23.90 | 18.91 |
December | 23.13 | 15.68 |
Annual Sum or Average | 23.93 | 21.89 |
Minimum of Months | 22.77 | 13.57 |
Maximum of Months | 24.45 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 13.57 |
February | 23.96 | 15.49 |
March | 23.87 | 17.07 |
April | 24.28 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.42 | 24.23 |
November | 24.35 | 18.91 |
December | 24.04 | 15.68 |
Annual Sum or Average | 24.24 | 21.89 |
Minimum of Months | 23.87 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 13.57 |
February | 23.96 | 15.49 |
March | 23.87 | 17.07 |
April | 24.28 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.42 | 24.23 |
November | 24.35 | 18.91 |
December | 24.04 | 15.68 |
Annual Sum or Average | 24.24 | 21.89 |
Minimum of Months | 23.87 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.62 | 13.57 |
February | 25.03 | 15.49 |
March | 25.18 | 17.07 |
April | 26.13 | 21.23 |
May | 26.64 | 26.90 |
June | 26.73 | 27.61 |
July | 26.74 | 27.94 |
August | 26.70 | 27.43 |
September | 26.60 | 26.23 |
October | 26.40 | 24.23 |
November | 25.81 | 18.91 |
December | 24.98 | 15.68 |
Annual Sum or Average | 25.97 | 21.89 |
Minimum of Months | 24.62 | 13.57 |
Maximum of Months | 26.74 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 13.57 |
February | 23.76 | 15.49 |
March | 23.73 | 17.07 |
April | 24.28 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.33 | 24.23 |
November | 24.24 | 18.91 |
December | 23.77 | 15.68 |
Annual Sum or Average | 24.15 | 21.89 |
Minimum of Months | 23.62 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.77 | 13.57 |
February | 23.26 | 15.49 |
March | 23.49 | 17.07 |
April | 24.23 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.24 | 24.23 |
November | 23.87 | 18.91 |
December | 23.09 | 15.68 |
Annual Sum or Average | 23.91 | 21.89 |
Minimum of Months | 22.77 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.60 | 13.57 |
February | 23.73 | 15.49 |
March | 23.73 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.35 | 24.23 |
November | 24.24 | 18.91 |
December | 23.73 | 15.68 |
Annual Sum or Average | 24.14 | 21.89 |
Minimum of Months | 23.60 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 13.57 |
February | 23.22 | 15.49 |
March | 23.47 | 17.07 |
April | 24.23 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.23 | 24.23 |
November | 23.85 | 18.91 |
December | 23.00 | 15.68 |
Annual Sum or Average | 23.89 | 21.89 |
Minimum of Months | 22.70 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 13.57 |
February | 23.22 | 15.49 |
March | 23.46 | 17.07 |
April | 24.20 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.44 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.25 | 24.23 |
November | 23.85 | 18.91 |
December | 23.07 | 15.68 |
Annual Sum or Average | 23.91 | 21.89 |
Minimum of Months | 22.73 | 13.57 |
Maximum of Months | 24.44 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 13.57 |
February | 23.21 | 15.49 |
March | 23.46 | 17.07 |
April | 24.20 | 21.23 |
May | 24.42 | 26.90 |
June | 24.42 | 27.61 |
July | 24.44 | 27.94 |
August | 24.43 | 27.43 |
September | 24.42 | 26.23 |
October | 24.25 | 24.23 |
November | 23.85 | 18.91 |
December | 23.06 | 15.68 |
Annual Sum or Average | 23.91 | 21.89 |
Minimum of Months | 22.72 | 13.57 |
Maximum of Months | 24.44 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 13.57 |
February | 23.90 | 15.49 |
March | 23.82 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.41 | 24.23 |
November | 24.33 | 18.91 |
December | 23.97 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.82 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 13.57 |
February | 23.90 | 15.49 |
March | 23.82 | 17.07 |
April | 24.27 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.41 | 27.43 |
September | 24.42 | 26.23 |
October | 24.40 | 24.23 |
November | 24.33 | 18.91 |
December | 23.97 | 15.68 |
Annual Sum or Average | 24.22 | 21.89 |
Minimum of Months | 23.82 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.51 | 13.57 |
February | 24.96 | 15.49 |
March | 25.12 | 17.07 |
April | 26.15 | 21.23 |
May | 26.73 | 26.90 |
June | 26.84 | 27.61 |
July | 26.85 | 27.94 |
August | 26.79 | 27.43 |
September | 26.68 | 26.23 |
October | 26.44 | 24.23 |
November | 25.76 | 18.91 |
December | 24.88 | 15.68 |
Annual Sum or Average | 25.98 | 21.89 |
Minimum of Months | 24.51 | 13.57 |
Maximum of Months | 26.85 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 13.57 |
February | 23.57 | 15.49 |
March | 23.56 | 17.07 |
April | 24.17 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.27 | 24.23 |
November | 24.02 | 18.91 |
December | 23.53 | 15.68 |
Annual Sum or Average | 24.04 | 21.89 |
Minimum of Months | 23.35 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 13.57 |
February | 23.18 | 15.49 |
March | 23.37 | 17.07 |
April | 24.13 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.19 | 24.23 |
November | 23.69 | 18.91 |
December | 23.02 | 15.68 |
Annual Sum or Average | 23.86 | 21.89 |
Minimum of Months | 22.76 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 13.57 |
February | 23.54 | 15.49 |
March | 23.57 | 17.07 |
April | 24.17 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.28 | 24.23 |
November | 24.01 | 18.91 |
December | 23.50 | 15.68 |
Annual Sum or Average | 24.04 | 21.89 |
Minimum of Months | 23.34 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 13.57 |
February | 23.13 | 15.49 |
March | 23.35 | 17.07 |
April | 24.12 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.40 | 26.23 |
October | 24.17 | 24.23 |
November | 23.66 | 18.91 |
December | 22.93 | 15.68 |
Annual Sum or Average | 23.84 | 21.89 |
Minimum of Months | 22.67 | 13.57 |
Maximum of Months | 24.40 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 13.57 |
February | 23.11 | 15.49 |
March | 23.34 | 17.07 |
April | 24.10 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.42 | 27.94 |
August | 24.41 | 27.43 |
September | 24.41 | 26.23 |
October | 24.19 | 24.23 |
November | 23.65 | 18.91 |
December | 22.96 | 15.68 |
Annual Sum or Average | 23.84 | 21.89 |
Minimum of Months | 22.67 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 13.57 |
February | 23.11 | 15.49 |
March | 23.34 | 17.07 |
April | 24.10 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.42 | 27.94 |
August | 24.41 | 27.43 |
September | 24.41 | 26.23 |
October | 24.18 | 24.23 |
November | 23.65 | 18.91 |
December | 22.95 | 15.68 |
Annual Sum or Average | 23.84 | 21.89 |
Minimum of Months | 22.67 | 13.57 |
Maximum of Months | 24.42 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.51 | 13.57 |
February | 23.67 | 15.49 |
March | 23.65 | 17.07 |
April | 24.18 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.31 | 24.23 |
November | 24.14 | 18.91 |
December | 23.69 | 15.68 |
Annual Sum or Average | 24.10 | 21.89 |
Minimum of Months | 23.51 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.51 | 13.57 |
February | 23.67 | 15.49 |
March | 23.65 | 17.07 |
April | 24.18 | 21.23 |
May | 24.40 | 26.90 |
June | 24.40 | 27.61 |
July | 24.40 | 27.94 |
August | 24.40 | 27.43 |
September | 24.41 | 26.23 |
October | 24.31 | 24.23 |
November | 24.14 | 18.91 |
December | 23.68 | 15.68 |
Annual Sum or Average | 24.10 | 21.89 |
Minimum of Months | 23.51 | 13.57 |
Maximum of Months | 24.41 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.73 | 13.57 |
February | 25.26 | 15.49 |
March | 25.50 | 17.07 |
April | 26.74 | 21.23 |
May | 27.58 | 26.90 |
June | 27.75 | 27.61 |
July | 27.74 | 27.94 |
August | 27.66 | 27.43 |
September | 27.47 | 26.23 |
October | 27.11 | 24.23 |
November | 26.13 | 18.91 |
December | 25.15 | 15.68 |
Annual Sum or Average | 26.57 | 21.89 |
Minimum of Months | 24.73 | 13.57 |
Maximum of Months | 27.75 | 27.94 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.231867E+12 | 152510.249 | 19-JAN-16:15 | 16050.792 | 44912.182 | 19155.517 | 0.000 | 66887.339 | 0.000 | 1860.651 | 2826.554 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.217620E+12 | 161143.394 | 27-FEB-17:15 | 18221.747 | 56933.809 | 19155.517 | 0.000 | 61194.596 | 0.000 | 1860.651 | 2628.770 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.244893E+12 | 172656.476 | 28-MAR-16:15 | 18221.747 | 56933.809 | 19155.517 | 0.000 | 72268.538 | 0.000 | 1860.651 | 3067.910 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.267494E+12 | 188302.809 | 29-APR-18:00 | 25049.151 | 51564.864 | 19155.517 | 0.000 | 75843.039 | 10720.100 | 1860.651 | 3094.873 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.352063E+12 | 185060.184 | 23-MAY-17:15 | 22204.399 | 56867.515 | 19155.517 | 0.000 | 80401.017 | 0.000 | 1860.651 | 3425.449 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.346491E+12 | 183051.652 | 28-JUN-17:30 | 22204.399 | 56867.515 | 19155.517 | 0.000 | 78386.720 | 0.000 | 1860.651 | 3430.961 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.368671E+12 | 187110.696 | 22-JUL-17:15 | 22204.399 | 56867.515 | 19155.517 | 0.000 | 82425.161 | 0.000 | 1860.651 | 3451.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.365779E+12 | 195062.843 | 10-AUG-19:00 | 25049.151 | 49704.829 | 19155.517 | 0.000 | 84175.206 | 10720.100 | 1860.651 | 3451.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.346704E+12 | 191315.892 | 12-SEP-18:00 | 25049.151 | 51564.864 | 19155.517 | 0.000 | 78654.949 | 10720.100 | 1860.651 | 3296.047 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.327850E+12 | 191681.914 | 08-OCT-18:00 | 25049.151 | 51564.864 | 19155.517 | 0.000 | 79047.938 | 10720.100 | 1860.651 | 3269.079 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.255206E+12 | 181810.568 | 07-NOV-18:30 | 22204.399 | 56867.515 | 19155.517 | 0.000 | 66755.646 | 10720.100 | 1860.651 | 3100.851 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.245846E+12 | 168482.005 | 15-DEC-18:15 | 22204.399 | 56867.515 | 19155.517 | 0.000 | 53975.474 | 10720.100 | 1860.651 | 2552.713 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.357048E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.217620E+12 | 152510.249 | 16050.792 | 44912.182 | 19155.517 | 0.000 | 53975.474 | 0.000 | 1860.651 | 2552.713 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.368671E+12 | 195062.843 | 25049.151 | 56933.809 | 19155.517 | 0.000 | 84175.206 | 10720.100 | 1860.651 | 3451.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.891285E+11 | 121593.422 | 10-JAN-07:15 | 0.000 | 0.000 | 0.000 | 121593.422 | 79136.664 | 79136.664 | 42456.759 |
February | 0.823044E+11 | 179729.284 | 05-FEB-07:15 | 0.000 | 0.000 | 0.000 | 179729.284 | 79131.819 | 79131.819 | 100597.464 |
March | 0.851199E+11 | 111167.491 | 11-MAR-09:00 | 0.000 | 0.000 | 0.000 | 111167.491 | 74323.954 | 74323.954 | 36843.537 |
April | 0.749565E+11 | 78140.879 | 01-APR-06:45 | 0.000 | 0.000 | 0.000 | 78140.879 | 78140.879 | 78140.879 | 0.000 |
May | 0.720493E+11 | 76513.918 | 01-MAY-06:30 | 0.000 | 0.000 | 0.000 | 76513.918 | 76513.918 | 76513.918 | 0.000 |
June | 0.655206E+11 | 72605.711 | 04-JUN-06:45 | 0.000 | 0.000 | 0.000 | 72605.711 | 72605.711 | 72605.711 | 0.000 |
July | 0.655564E+11 | 69438.975 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 69438.975 | 69438.975 | 69438.975 | 0.000 |
August | 0.662628E+11 | 71323.039 | 31-AUG-06:30 | 0.000 | 0.000 | 0.000 | 71323.039 | 71323.039 | 71323.039 | 0.000 |
September | 0.673080E+11 | 75881.270 | 30-SEP-06:00 | 0.000 | 0.000 | 0.000 | 75881.270 | 75881.270 | 75881.270 | 0.000 |
October | 0.746018E+11 | 77276.143 | 29-OCT-06:00 | 0.000 | 0.000 | 0.000 | 77276.143 | 77276.143 | 77276.143 | 0.000 |
November | 0.773699E+11 | 78626.986 | 29-NOV-07:30 | 0.000 | 0.000 | 0.000 | 78626.986 | 78626.986 | 78626.986 | 0.000 |
December | 0.870332E+11 | 144561.388 | 20-DEC-06:00 | 0.000 | 0.000 | 0.000 | 144561.388 | 77385.227 | 77385.227 | 67176.161 |
Annual Sum or Average | 0.907211E+12 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.655206E+11 | 69438.975 | 0.000 | 0.000 | 0.000 | 69438.975 | 69438.975 | 69438.975 | 0.000 | |
Maximum of Months | 0.891285E+11 | 179729.284 | 0.000 | 0.000 | 0.000 | 179729.284 | 79136.664 | 79136.664 | 100597.464 |