Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2018-10-19 09:40:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4733.69 | 604.06 | 670.51 |
Net Site Energy | 4733.69 | 604.06 | 670.51 |
Total Source Energy | 11418.90 | 1457.15 | 1617.43 |
Net Source Energy | 11418.90 | 1457.15 | 1617.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 173.35 | 577.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 455.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 578.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.61 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1137.55 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3018.52 | 1715.18 | 0.00 | 0.00 | 0.00 | 5997.13 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 577.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 173.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 455.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 578.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 53.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.61 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1137.55 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 181.56 | 242.95 | 0.00 | 0.00 | 0.00 | 0.85 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 427.56 | 242.95 | 0.00 | 0.00 | 0.00 | 0.85 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 163.57 | 218.87 | 0.00 | 0.00 | 0.00 | 0.77 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 385.19 | 218.87 | 0.00 | 0.00 | 0.00 | 0.77 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3018.52 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3018.52 | 100.00 |
Total On-Site and Utility Electric Sources | 3018.52 | 100.00 |
Total Electricity End Uses | 3018.52 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5997.13 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5997.13 | 100.00 |
Total Water End Uses | 5997.13 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 176.50 |
Time Setpoint Not Met During Occupied Cooling | 224.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2665.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-19:00 | 06-FEB-06:00 | - | - | - | 22-JUL-06:00 |
Heating | 0.00 | 205249.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79480.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1729.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3202.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85551.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 189190.54 | 290801.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 205249.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 79480.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 20603.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 4445.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 18358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1729.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 3202.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85551.83 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 548.99 | 626.15 | 0.00 | 0.00 | 0.00 |
Cooling | 1442.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1833.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 169.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1233.10 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9559.64 | 1859.25 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 77.76 | 88.69 | 0.00 | 0.00 | 0.00 |
Cooling | 204.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 259.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 9.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 174.66 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1354.08 | 263.35 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 77.76 | 88.69 | 0.00 | 0.00 | 0.00 |
Cooling | 204.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 259.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 9.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 174.66 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1354.08 | 263.35 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.52_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.52_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.67 | 83.67 | 168.37 | |
Exterior Lighting Total | 10720.10 | 168.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 305019.01 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 244015.21 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3710.95 | 2534.03 | 1176.92 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3496.34 | 2371.10 | 1125.24 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5045.40 | 3463.51 | 1581.89 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2874.95 | 1908.00 | 966.94 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2146.32 | 1371.79 | 774.53 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2125.39 | 1356.27 | 769.11 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2550.83 | 1666.26 | 884.57 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2620.20 | 1719.47 | 900.73 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4684.07 | 3254.21 | 1429.86 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4408.57 | 3042.10 | 1366.48 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4510.08 | 3116.04 | 1394.04 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3683.74 | 2498.48 | 1185.26 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2746.45 | 1808.61 | 937.84 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2729.06 | 1795.52 | 933.54 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3223.29 | 2164.01 | 1059.29 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3249.57 | 2184.21 | 1065.36 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4745.97 | 3283.16 | 1462.81 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4484.65 | 3082.47 | 1402.17 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4360.41 | 2982.73 | 1377.69 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3774.23 | 2551.06 | 1223.17 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2827.92 | 1860.60 | 967.32 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2810.67 | 1847.63 | 963.04 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3291.60 | 2206.28 | 1085.32 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3304.58 | 2216.27 | 1088.31 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4792.77 | 3305.32 | 1487.46 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4535.26 | 3107.94 | 1427.33 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4389.02 | 2991.51 | 1397.51 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3822.80 | 2575.87 | 1246.94 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2869.82 | 1885.61 | 984.21 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2852.63 | 1872.70 | 979.93 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3327.31 | 2226.10 | 1101.21 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3338.41 | 2234.64 | 1103.77 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4863.38 | 3348.38 | 1515.00 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4609.52 | 3154.02 | 1455.49 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4459.56 | 3034.91 | 1424.66 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3894.71 | 2620.73 | 1273.97 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2935.01 | 1929.37 | 1005.64 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2917.88 | 1916.51 | 1001.37 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3387.14 | 2265.71 | 1121.43 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3397.98 | 2274.05 | 1123.93 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4840.00 | 3320.98 | 1519.02 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4586.70 | 3127.47 | 1459.23 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4438.28 | 3009.71 | 1428.57 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3870.08 | 2593.76 | 1276.32 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2906.80 | 1903.63 | 1003.17 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2889.74 | 1890.87 | 998.87 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3355.49 | 2236.44 | 1119.05 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3366.31 | 2244.75 | 1121.56 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4846.66 | 3317.88 | 1528.78 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4595.07 | 3125.99 | 1469.09 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4446.74 | 3008.43 | 1438.31 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3876.47 | 2591.49 | 1284.99 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2909.40 | 1901.70 | 1007.70 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2892.41 | 1889.02 | 1003.40 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3354.36 | 2231.14 | 1123.22 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3365.18 | 2239.43 | 1125.75 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4870.89 | 3329.13 | 1541.76 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4621.04 | 3138.79 | 1482.26 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4471.64 | 3020.54 | 1451.10 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3904.85 | 2605.68 | 1299.16 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2930.30 | 1913.91 | 1016.39 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2913.40 | 1901.30 | 1012.10 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3371.00 | 2239.84 | 1131.16 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3381.83 | 2248.14 | 1133.70 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5019.77 | 3436.32 | 1583.45 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4770.58 | 3246.28 | 1524.30 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4590.06 | 3104.35 | 1485.71 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3984.60 | 2660.07 | 1324.52 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3057.48 | 2006.00 | 1051.48 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3040.37 | 1993.21 | 1047.16 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3468.35 | 2310.05 | 1158.30 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3480.38 | 2319.26 | 1161.12 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5890.43 | 4094.32 | 1796.11 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5516.60 | 3809.94 | 1706.65 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5422.47 | 3734.93 | 1687.54 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4678.47 | 3179.16 | 1499.31 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3574.10 | 2386.20 | 1187.90 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3571.05 | 2384.04 | 1187.01 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4414.82 | 3030.81 | 1384.01 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4425.29 | 3038.95 | 1386.34 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3710.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3496.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5045.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2874.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2146.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2125.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2550.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2620.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4684.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4408.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4510.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3683.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2746.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2729.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3223.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3249.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4745.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4484.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4360.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3774.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2827.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2810.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3291.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3304.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4792.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4535.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4389.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3822.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2869.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2852.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3327.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3338.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4863.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4609.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4459.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3894.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2935.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2917.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3387.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3397.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4840.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4586.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4438.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3870.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2906.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2889.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3355.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3366.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4846.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4595.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4446.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3876.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2909.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2892.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3354.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3365.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4870.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4621.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4471.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3904.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2930.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2913.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3371.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3381.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5019.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4770.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4590.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3984.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3057.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3040.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3468.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3480.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5890.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5516.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5422.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4678.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3574.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3571.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4414.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4425.29 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 3505.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 3515.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 4404.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 3511.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2607.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2607.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2593.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2602.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 3642.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 3655.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 3658.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 3646.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 2506.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 2506.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 2495.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 2497.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 3752.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 3771.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 3744.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 3760.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 2542.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 2542.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 2524.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 2524.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 3881.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 3903.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 3869.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 3890.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 2613.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 2612.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 2591.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 2591.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 3972.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 3994.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 3958.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 3980.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 2655.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 2655.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 2633.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 2633.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 4118.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 4142.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 4103.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 4128.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 2759.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 2759.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 2734.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 2734.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 4228.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 4253.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 4212.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 4238.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 2832.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 2832.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 2807.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 2806.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 4336.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 4362.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 4320.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 4346.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2907.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2907.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2881.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2881.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 4564.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 4588.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 4547.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 4571.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 3094.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 3094.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 3069.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 3069.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 5224.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 5253.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 5208.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 5237.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 3792.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 3792.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 3759.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 3759.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 229.43 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.67 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 315.36 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.62 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 114.82 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.10 | 113.25 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 142.44 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 147.92 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 300.71 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.76 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 285.88 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.43 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 157.96 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.64 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 191.74 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 193.79 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.38 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.60 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 271.08 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.55 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 162.26 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 160.94 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 195.28 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.30 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.68 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.25 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 271.04 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.14 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.24 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 162.94 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.73 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.60 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.27 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 288.16 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 274.68 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 235.95 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.23 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.93 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 200.29 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 201.14 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.83 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.81 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 271.47 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.57 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.24 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 163.95 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.93 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.78 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.93 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.08 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 270.78 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.78 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.71 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 163.43 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.05 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.90 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.56 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.87 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 271.49 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.42 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.65 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.38 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 196.63 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 197.47 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 313.95 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 295.29 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.51 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 237.47 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.69 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 173.40 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.45 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.39 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 379.44 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 351.23 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 343.03 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 289.28 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.70 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.50 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 276.33 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 277.16 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0066 | 1692.11 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2178.46 | 2614.15 | 0.171 | 0.205 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36 | 0.01410 |
G NW APARTMENT | 2028.89 | 2434.67 | 0.159 | 0.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
OFFICE | 2994.49 | 3593.39 | 0.235 | 0.282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 30.58 | 0.01410 |
G NE APARTMENT | 1601.05 | 1921.27 | 0.125 | 0.151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 28.97 | 0.01410 |
G N1 APARTMENT | 1090.26 | 1308.31 | 0.085 | 0.103 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
G N2 APARTMENT | 1075.36 | 1290.44 | 0.084 | 0.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
G S1 APARTMENT | 1352.51 | 1623.01 | 0.106 | 0.127 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
G S2 APARTMENT | 1404.61 | 1685.53 | 0.110 | 0.132 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F2 SW APARTMENT | 2855.23 | 3426.28 | 0.224 | 0.268 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F2 NW APARTMENT | 2656.39 | 3187.66 | 0.208 | 0.250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F2 SE APARTMENT | 2714.46 | 3257.35 | 0.213 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F2 NE APARTMENT | 2149.93 | 2579.91 | 0.168 | 0.202 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
F2 N1 APARTMENT | 1499.95 | 1799.95 | 0.118 | 0.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
F2 N2 APARTMENT | 1487.37 | 1784.85 | 0.117 | 0.140 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 29.49 | 0.01410 |
F2 S1 APARTMENT | 1820.61 | 2184.74 | 0.143 | 0.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F2 S2 APARTMENT | 1840.14 | 2208.17 | 0.144 | 0.173 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F3 SW APARTMENT | 2871.03 | 3445.24 | 0.225 | 0.270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F3 NW APARTMENT | 2683.35 | 3220.02 | 0.210 | 0.252 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F3 SE APARTMENT | 2573.87 | 3088.64 | 0.202 | 0.242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F3 NE APARTMENT | 2188.95 | 2626.75 | 0.172 | 0.206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
F3 N1 APARTMENT | 1540.67 | 1848.81 | 0.121 | 0.145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F3 N2 APARTMENT | 1528.21 | 1833.85 | 0.120 | 0.144 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F3 S1 APARTMENT | 1854.26 | 2225.11 | 0.145 | 0.174 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F3 S2 APARTMENT | 1863.92 | 2236.71 | 0.146 | 0.175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F4 SW APARTMENT | 2883.32 | 3459.99 | 0.226 | 0.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F4 NW APARTMENT | 2698.92 | 3238.70 | 0.211 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F4 SE APARTMENT | 2573.41 | 3088.09 | 0.202 | 0.242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F4 NE APARTMENT | 2204.09 | 2644.91 | 0.173 | 0.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
F4 N1 APARTMENT | 1559.53 | 1871.43 | 0.122 | 0.147 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F4 N2 APARTMENT | 1547.13 | 1856.55 | 0.121 | 0.145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F4 S1 APARTMENT | 1868.00 | 2241.60 | 0.146 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F4 S2 APARTMENT | 1876.28 | 2251.53 | 0.147 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
M SW APARTMENT | 2917.44 | 3500.93 | 0.229 | 0.274 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
M NW APARTMENT | 2736.02 | 3283.22 | 0.214 | 0.257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
M SE APARTMENT | 2607.94 | 3129.53 | 0.204 | 0.245 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
M NE APARTMENT | 2240.20 | 2688.24 | 0.176 | 0.211 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
M N1 APARTMENT | 1597.39 | 1916.87 | 0.125 | 0.150 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
M N2 APARTMENT | 1585.05 | 1902.06 | 0.124 | 0.149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
M S1 APARTMENT | 1901.79 | 2282.15 | 0.149 | 0.179 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
M S2 APARTMENT | 1909.86 | 2291.84 | 0.150 | 0.180 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F6 SW APARTMENT | 2884.71 | 3461.65 | 0.226 | 0.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F6 NW APARTMENT | 2704.20 | 3245.04 | 0.212 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F6 SE APARTMENT | 2577.49 | 3092.99 | 0.202 | 0.242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F6 NE APARTMENT | 2208.11 | 2649.74 | 0.173 | 0.208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
F6 N1 APARTMENT | 1568.98 | 1882.78 | 0.123 | 0.148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F6 N2 APARTMENT | 1556.75 | 1868.09 | 0.122 | 0.146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F6 S1 APARTMENT | 1869.87 | 2243.84 | 0.147 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F6 S2 APARTMENT | 1877.91 | 2253.49 | 0.147 | 0.177 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F7 SW APARTMENT | 2876.18 | 3451.41 | 0.225 | 0.270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F7 NW APARTMENT | 2697.31 | 3236.77 | 0.211 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F7 SE APARTMENT | 2570.84 | 3085.01 | 0.201 | 0.242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F7 NE APARTMENT | 2200.60 | 2640.71 | 0.172 | 0.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.29 | 0.01410 |
F7 N1 APARTMENT | 1563.95 | 1876.74 | 0.123 | 0.147 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F7 N2 APARTMENT | 1551.79 | 1862.15 | 0.122 | 0.146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F7 S1 APARTMENT | 1861.50 | 2233.79 | 0.146 | 0.175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F7 S2 APARTMENT | 1869.52 | 2243.43 | 0.146 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F8 SW APARTMENT | 2882.05 | 3458.47 | 0.226 | 0.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F8 NW APARTMENT | 2704.73 | 3245.68 | 0.212 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F8 SE APARTMENT | 2577.64 | 3093.16 | 0.202 | 0.242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F8 NE APARTMENT | 2206.66 | 2647.99 | 0.173 | 0.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.57 | 0.01410 |
F8 N1 APARTMENT | 1572.83 | 1887.40 | 0.123 | 0.148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F8 N2 APARTMENT | 1560.75 | 1872.90 | 0.122 | 0.147 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F8 S1 APARTMENT | 1866.94 | 2240.32 | 0.146 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F8 S2 APARTMENT | 1874.97 | 2249.96 | 0.147 | 0.176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F9 SW APARTMENT | 2980.71 | 3576.85 | 0.234 | 0.280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 31.21 | 0.01410 |
F9 NW APARTMENT | 2803.66 | 3364.39 | 0.220 | 0.264 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 30.51 | 0.01410 |
F9 SE APARTMENT | 2653.73 | 3184.47 | 0.208 | 0.250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
F9 NE APARTMENT | 2254.53 | 2705.44 | 0.177 | 0.212 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.57 | 0.01410 |
F9 N1 APARTMENT | 1658.70 | 1990.43 | 0.130 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F9 N2 APARTMENT | 1646.43 | 1975.72 | 0.129 | 0.155 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.77 | 0.01410 |
F9 S1 APARTMENT | 1931.69 | 2318.03 | 0.151 | 0.182 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
F9 S2 APARTMENT | 1940.61 | 2328.73 | 0.152 | 0.182 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
T SW APARTMENT | 3602.45 | 4322.94 | 0.282 | 0.339 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 31.88 | 0.01410 |
T NW APARTMENT | 3334.59 | 4001.51 | 0.261 | 0.314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36 | 0.01410 |
T SE APARTMENT | 3256.71 | 3908.06 | 0.255 | 0.306 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 31.82 | 0.01410 |
T NE APARTMENT | 2746.40 | 3295.67 | 0.215 | 0.258 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 29.84 | 0.01410 |
T N1 APARTMENT | 2000.55 | 2400.66 | 0.157 | 0.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10 | 0.01410 |
T N2 APARTMENT | 1998.60 | 2398.32 | 0.157 | 0.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10 | 0.01410 |
T S1 APARTMENT | 2623.69 | 3148.43 | 0.206 | 0.247 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
T S2 APARTMENT | 2631.59 | 3157.91 | 0.206 | 0.247 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.92 | 0.01410 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2104.20 | 2525.04 | 0.094 | 0.112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G NW APARTMENT | 2112.65 | 2535.18 | 0.094 | 0.113 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
OFFICE | 2462.25 | 2954.70 | 0.110 | 0.132 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -10.70 | 0.00150 |
G NE APARTMENT | 2109.76 | 2531.71 | 0.094 | 0.113 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G N1 APARTMENT | 1344.96 | 1613.95 | 0.060 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G N2 APARTMENT | 1344.87 | 1613.85 | 0.060 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G S1 APARTMENT | 1333.54 | 1600.24 | 0.059 | 0.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
G S2 APARTMENT | 1340.64 | 1608.77 | 0.060 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70 | 0.00150 |
F2 SW APARTMENT | 2220.15 | 2664.18 | 0.099 | 0.119 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 NW APARTMENT | 2231.35 | 2677.62 | 0.099 | 0.119 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 SE APARTMENT | 2234.12 | 2680.95 | 0.099 | 0.119 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 NE APARTMENT | 2224.13 | 2668.96 | 0.099 | 0.119 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 N1 APARTMENT | 1259.63 | 1511.56 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 N2 APARTMENT | 1259.46 | 1511.35 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 S1 APARTMENT | 1250.64 | 1500.76 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F2 S2 APARTMENT | 1251.84 | 1502.21 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 SW APARTMENT | 2313.55 | 2776.27 | 0.103 | 0.124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 NW APARTMENT | 2329.11 | 2794.93 | 0.104 | 0.124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 SE APARTMENT | 2306.49 | 2767.79 | 0.103 | 0.123 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 NE APARTMENT | 2319.75 | 2783.70 | 0.103 | 0.124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 N1 APARTMENT | 1290.36 | 1548.44 | 0.057 | 0.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 N2 APARTMENT | 1290.14 | 1548.17 | 0.057 | 0.069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 S1 APARTMENT | 1275.27 | 1530.32 | 0.057 | 0.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F3 S2 APARTMENT | 1275.25 | 1530.30 | 0.057 | 0.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 SW APARTMENT | 2422.74 | 2907.28 | 0.108 | 0.129 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 NW APARTMENT | 2440.92 | 2929.10 | 0.109 | 0.130 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 SE APARTMENT | 2412.21 | 2894.65 | 0.107 | 0.129 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 NE APARTMENT | 2430.17 | 2916.20 | 0.108 | 0.130 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 N1 APARTMENT | 1349.94 | 1619.93 | 0.060 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 N2 APARTMENT | 1349.68 | 1619.61 | 0.060 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 S1 APARTMENT | 1331.92 | 1598.30 | 0.059 | 0.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F4 S2 APARTMENT | 1331.69 | 1598.02 | 0.059 | 0.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M SW APARTMENT | 2499.30 | 2999.15 | 0.111 | 0.133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M NW APARTMENT | 2518.16 | 3021.79 | 0.112 | 0.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M SE APARTMENT | 2487.55 | 2985.07 | 0.111 | 0.133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M NE APARTMENT | 2506.41 | 3007.69 | 0.112 | 0.134 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M N1 APARTMENT | 1385.77 | 1662.92 | 0.062 | 0.074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M N2 APARTMENT | 1385.48 | 1662.57 | 0.062 | 0.074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M S1 APARTMENT | 1366.97 | 1640.36 | 0.061 | 0.073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
M S2 APARTMENT | 1366.68 | 1640.02 | 0.061 | 0.073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 SW APARTMENT | 2622.57 | 3147.09 | 0.117 | 0.140 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 NW APARTMENT | 2643.53 | 3172.24 | 0.118 | 0.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 SE APARTMENT | 2610.04 | 3132.04 | 0.116 | 0.139 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 NE APARTMENT | 2631.01 | 3157.21 | 0.117 | 0.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 N1 APARTMENT | 1473.66 | 1768.40 | 0.066 | 0.079 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 N2 APARTMENT | 1473.36 | 1768.03 | 0.066 | 0.079 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 S1 APARTMENT | 1452.75 | 1743.30 | 0.065 | 0.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F6 S2 APARTMENT | 1452.44 | 1742.93 | 0.065 | 0.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 SW APARTMENT | 2715.62 | 3258.74 | 0.121 | 0.145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 NW APARTMENT | 2737.35 | 3284.82 | 0.122 | 0.146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 SE APARTMENT | 2702.46 | 3242.95 | 0.120 | 0.144 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 NE APARTMENT | 2724.21 | 3269.05 | 0.121 | 0.146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 N1 APARTMENT | 1535.62 | 1842.75 | 0.068 | 0.082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 N2 APARTMENT | 1535.30 | 1842.36 | 0.068 | 0.082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 S1 APARTMENT | 1513.93 | 1816.72 | 0.067 | 0.081 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F7 S2 APARTMENT | 1513.61 | 1816.33 | 0.067 | 0.081 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 SW APARTMENT | 2807.09 | 3368.51 | 0.125 | 0.150 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 NW APARTMENT | 2829.21 | 3395.05 | 0.126 | 0.151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 SE APARTMENT | 2793.42 | 3352.11 | 0.124 | 0.149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 NE APARTMENT | 2815.55 | 3378.66 | 0.125 | 0.150 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 N1 APARTMENT | 1599.06 | 1918.87 | 0.071 | 0.085 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 N2 APARTMENT | 1598.73 | 1918.47 | 0.071 | 0.085 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 S1 APARTMENT | 1576.98 | 1892.37 | 0.070 | 0.084 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F8 S2 APARTMENT | 1576.64 | 1891.97 | 0.070 | 0.084 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 SW APARTMENT | 2999.96 | 3599.95 | 0.134 | 0.160 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 NW APARTMENT | 3020.32 | 3624.38 | 0.134 | 0.161 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 SE APARTMENT | 2985.73 | 3582.87 | 0.133 | 0.159 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 NE APARTMENT | 3006.11 | 3607.33 | 0.134 | 0.161 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 N1 APARTMENT | 1756.90 | 2108.28 | 0.078 | 0.094 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 N2 APARTMENT | 1756.55 | 2107.86 | 0.078 | 0.094 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 S1 APARTMENT | 1736.19 | 2083.43 | 0.077 | 0.093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
F9 S2 APARTMENT | 1735.84 | 2083.01 | 0.077 | 0.093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T SW APARTMENT | 3557.92 | 4269.50 | 0.158 | 0.190 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T NW APARTMENT | 3582.92 | 4299.50 | 0.159 | 0.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T SE APARTMENT | 3544.47 | 4253.36 | 0.158 | 0.189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T NE APARTMENT | 3569.48 | 4283.38 | 0.159 | 0.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T N1 APARTMENT | 2347.38 | 2816.86 | 0.104 | 0.125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T N2 APARTMENT | 2347.03 | 2816.44 | 0.104 | 0.125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T S1 APARTMENT | 2319.51 | 2783.42 | 0.103 | 0.124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
T S2 APARTMENT | 2319.16 | 2783.00 | 0.103 | 0.124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -10.70 | 0.00150 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.20 | 0.20 | 0.11 | 0.11 |
AIRLOOP G NW | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP OFFICE | 0.28 | 0.28 | 0.13 | 0.13 |
AIRLOOP G NE | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP G N1 | 0.10 | 0.10 | 0.07 | 0.07 |
AIRLOOP G N2 | 0.10 | 0.10 | 0.07 | 0.07 |
AIRLOOP G S1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP G S2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F2 SW | 0.27 | 0.27 | 0.12 | 0.12 |
AIRLOOP F2 NW | 0.25 | 0.25 | 0.12 | 0.12 |
AIRLOOP F2 SE | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F2 NE | 0.20 | 0.20 | 0.12 | 0.12 |
AIRLOOP F2 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F2 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F2 S1 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F2 S2 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F3 SW | 0.27 | 0.27 | 0.12 | 0.12 |
AIRLOOP F3 NW | 0.25 | 0.25 | 0.12 | 0.12 |
AIRLOOP F3 SE | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F3 NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP F3 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F3 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F3 S1 | 0.17 | 0.17 | 0.07 | 0.07 |
AIRLOOP F3 S2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F4 SW | 0.27 | 0.27 | 0.13 | 0.13 |
AIRLOOP F4 NW | 0.25 | 0.25 | 0.13 | 0.13 |
AIRLOOP F4 SE | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F4 NE | 0.21 | 0.21 | 0.13 | 0.13 |
AIRLOOP F4 N1 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F4 N2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F4 S1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F4 S2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP M SW | 0.27 | 0.27 | 0.13 | 0.13 |
AIRLOOP M NW | 0.26 | 0.26 | 0.13 | 0.13 |
AIRLOOP M SE | 0.25 | 0.25 | 0.13 | 0.13 |
AIRLOOP M NE | 0.21 | 0.21 | 0.13 | 0.13 |
AIRLOOP M N1 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP M N2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP M S1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP M S2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F6 SW | 0.27 | 0.27 | 0.14 | 0.14 |
AIRLOOP F6 NW | 0.25 | 0.25 | 0.14 | 0.14 |
AIRLOOP F6 SE | 0.24 | 0.24 | 0.14 | 0.14 |
AIRLOOP F6 NE | 0.21 | 0.21 | 0.14 | 0.14 |
AIRLOOP F6 N1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F6 N2 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F6 S1 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F6 S2 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F7 SW | 0.27 | 0.27 | 0.15 | 0.15 |
AIRLOOP F7 NW | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP F7 SE | 0.24 | 0.24 | 0.14 | 0.14 |
AIRLOOP F7 NE | 0.21 | 0.21 | 0.15 | 0.15 |
AIRLOOP F7 N1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F7 N2 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F7 S1 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F7 S2 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F8 SW | 0.27 | 0.27 | 0.15 | 0.15 |
AIRLOOP F8 NW | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP F8 SE | 0.24 | 0.24 | 0.15 | 0.15 |
AIRLOOP F8 NE | 0.21 | 0.21 | 0.15 | 0.15 |
AIRLOOP F8 N1 | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F8 N2 | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F8 S1 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F8 S2 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F9 SW | 0.28 | 0.28 | 0.16 | 0.16 |
AIRLOOP F9 NW | 0.26 | 0.26 | 0.16 | 0.16 |
AIRLOOP F9 SE | 0.25 | 0.25 | 0.16 | 0.16 |
AIRLOOP F9 NE | 0.21 | 0.21 | 0.16 | 0.16 |
AIRLOOP F9 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F9 N2 | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F9 S1 | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP F9 S2 | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP T SW | 0.34 | 0.34 | 0.19 | 0.19 |
AIRLOOP T NW | 0.31 | 0.31 | 0.19 | 0.19 |
AIRLOOP T SE | 0.31 | 0.31 | 0.19 | 0.19 |
AIRLOOP T NE | 0.26 | 0.26 | 0.19 | 0.19 |
AIRLOOP T N1 | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP T N2 | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP T S1 | 0.25 | 0.25 | 0.12 | 0.12 |
AIRLOOP T S2 | 0.25 | 0.25 | 0.12 | 0.12 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3351.25 | 6306.75 | 1497.50 |
G NW APARTMENT | 3411.25 | 6876.25 | 1899.50 |
OFFICE | 1023.75 | 943.00 | 12.25 |
G NE APARTMENT | 3397.75 | 6924.50 | 1908.75 |
G N1 APARTMENT | 2907.00 | 7133.00 | 1630.00 |
G N2 APARTMENT | 2905.75 | 7132.75 | 1631.00 |
G S1 APARTMENT | 3017.00 | 6539.00 | 1342.00 |
G S2 APARTMENT | 3031.25 | 6500.75 | 1337.00 |
F2 SW APARTMENT | 3810.25 | 4929.25 | 912.50 |
F2 NW APARTMENT | 3514.50 | 5850.75 | 1208.00 |
F2 SE APARTMENT | 3906.25 | 4781.75 | 876.25 |
F2 NE APARTMENT | 3485.00 | 5944.00 | 1223.25 |
F2 N1 APARTMENT | 3050.50 | 6157.25 | 1040.25 |
F2 N2 APARTMENT | 3048.25 | 6161.25 | 1039.75 |
F2 S1 APARTMENT | 3628.00 | 4946.25 | 873.00 |
F2 S2 APARTMENT | 3641.25 | 4921.50 | 871.75 |
F3 SW APARTMENT | 3943.00 | 4773.50 | 901.50 |
F3 NW APARTMENT | 3605.50 | 5677.75 | 1180.25 |
F3 SE APARTMENT | 3988.50 | 4748.25 | 906.75 |
F3 NE APARTMENT | 3573.00 | 5750.50 | 1180.50 |
F3 N1 APARTMENT | 3169.25 | 5912.00 | 994.25 |
F3 N2 APARTMENT | 3165.00 | 5923.00 | 995.50 |
F3 S1 APARTMENT | 3846.50 | 4649.50 | 848.75 |
F3 S2 APARTMENT | 3852.75 | 4639.50 | 848.00 |
F4 SW APARTMENT | 3994.75 | 4754.25 | 916.25 |
F4 NW APARTMENT | 3666.75 | 5619.00 | 1201.50 |
F4 SE APARTMENT | 4026.75 | 4742.50 | 927.00 |
F4 NE APARTMENT | 3637.25 | 5686.50 | 1197.00 |
F4 N1 APARTMENT | 3240.25 | 5818.25 | 999.50 |
F4 N2 APARTMENT | 3238.00 | 5827.25 | 999.00 |
F4 S1 APARTMENT | 3917.25 | 4578.25 | 854.25 |
F4 S2 APARTMENT | 3919.50 | 4578.00 | 854.25 |
M SW APARTMENT | 3991.25 | 4762.75 | 912.25 |
M NW APARTMENT | 3675.00 | 5607.75 | 1185.50 |
M SE APARTMENT | 4019.00 | 4753.75 | 922.25 |
M NE APARTMENT | 3637.75 | 5677.25 | 1184.25 |
M N1 APARTMENT | 3263.00 | 5775.50 | 987.00 |
M N2 APARTMENT | 3259.50 | 5788.75 | 986.25 |
M S1 APARTMENT | 3928.00 | 4559.75 | 846.25 |
M S2 APARTMENT | 3928.75 | 4558.75 | 847.00 |
F6 SW APARTMENT | 3906.25 | 4911.00 | 982.25 |
F6 NW APARTMENT | 3645.25 | 5772.75 | 1289.25 |
F6 SE APARTMENT | 3930.00 | 4916.75 | 987.75 |
F6 NE APARTMENT | 3602.00 | 5835.75 | 1283.75 |
F6 N1 APARTMENT | 3183.50 | 5937.75 | 1032.75 |
F6 N2 APARTMENT | 3179.25 | 5945.25 | 1032.50 |
F6 S1 APARTMENT | 3821.25 | 4771.50 | 894.50 |
F6 S2 APARTMENT | 3824.50 | 4771.25 | 894.75 |
F7 SW APARTMENT | 3846.75 | 5015.75 | 1025.50 |
F7 NW APARTMENT | 3628.75 | 5877.25 | 1345.25 |
F7 SE APARTMENT | 3864.75 | 5021.75 | 1023.25 |
F7 NE APARTMENT | 3578.25 | 5932.50 | 1330.75 |
F7 N1 APARTMENT | 3137.00 | 6028.00 | 1054.25 |
F7 N2 APARTMENT | 3131.50 | 6039.25 | 1056.00 |
F7 S1 APARTMENT | 3749.75 | 4904.00 | 919.25 |
F7 S2 APARTMENT | 3752.25 | 4902.00 | 920.25 |
F8 SW APARTMENT | 3807.25 | 5116.00 | 1066.25 |
F8 NW APARTMENT | 3612.00 | 5962.25 | 1391.00 |
F8 SE APARTMENT | 3812.75 | 5116.75 | 1058.50 |
F8 NE APARTMENT | 3570.50 | 6017.50 | 1376.75 |
F8 N1 APARTMENT | 3111.50 | 6109.00 | 1075.75 |
F8 N2 APARTMENT | 3106.25 | 6115.50 | 1078.00 |
F8 S1 APARTMENT | 3679.00 | 5012.00 | 937.25 |
F8 S2 APARTMENT | 3679.00 | 5006.25 | 937.25 |
F9 SW APARTMENT | 3791.75 | 5250.00 | 1131.25 |
F9 NW APARTMENT | 3665.50 | 6039.25 | 1488.50 |
F9 SE APARTMENT | 3783.00 | 5233.50 | 1121.00 |
F9 NE APARTMENT | 3627.25 | 6094.75 | 1472.25 |
F9 N1 APARTMENT | 3139.75 | 6177.25 | 1134.25 |
F9 N2 APARTMENT | 3134.75 | 6186.25 | 1133.75 |
F9 S1 APARTMENT | 3590.25 | 5139.75 | 955.75 |
F9 S2 APARTMENT | 3590.25 | 5136.75 | 956.25 |
T SW APARTMENT | 4251.75 | 5674.00 | 1828.25 |
T NW APARTMENT | 4217.25 | 6323.75 | 2218.75 |
T SE APARTMENT | 4268.75 | 5678.75 | 1854.50 |
T NE APARTMENT | 4193.25 | 6395.00 | 2259.75 |
T N1 APARTMENT | 3674.75 | 6445.25 | 1780.00 |
T N2 APARTMENT | 3670.75 | 6455.75 | 1780.75 |
T S1 APARTMENT | 3873.25 | 5508.75 | 1429.75 |
T S2 APARTMENT | 3874.00 | 5510.75 | 1432.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5457.50 | 7265.50 | 2665.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 6.25 | 22.25 | 6.25 | 22.25 |
G NW APARTMENT | 2.50 | 7.50 | 2.50 | 7.50 |
OFFICE | 2.75 | 0.00 | 0.50 | 0.00 |
G NE APARTMENT | 4.25 | 22.50 | 4.25 | 22.50 |
G N1 APARTMENT | 6.50 | 43.00 | 6.50 | 43.00 |
G N2 APARTMENT | 6.75 | 46.00 | 6.75 | 46.00 |
G S1 APARTMENT | 2.25 | 70.25 | 2.25 | 70.25 |
G S2 APARTMENT | 2.75 | 58.75 | 2.75 | 58.75 |
F2 SW APARTMENT | 3.25 | 24.25 | 3.25 | 24.25 |
F2 NW APARTMENT | 0.75 | 9.75 | 0.75 | 9.75 |
F2 SE APARTMENT | 2.25 | 17.00 | 2.25 | 17.00 |
F2 NE APARTMENT | 3.00 | 21.50 | 3.00 | 21.50 |
F2 N1 APARTMENT | 5.25 | 55.75 | 5.25 | 55.75 |
F2 N2 APARTMENT | 5.00 | 56.00 | 5.00 | 56.00 |
F2 S1 APARTMENT | 2.25 | 79.00 | 2.25 | 79.00 |
F2 S2 APARTMENT | 1.50 | 74.25 | 1.50 | 74.25 |
F3 SW APARTMENT | 1.75 | 37.25 | 1.75 | 37.25 |
F3 NW APARTMENT | 0.50 | 21.25 | 0.50 | 21.25 |
F3 SE APARTMENT | 4.00 | 47.75 | 4.00 | 47.75 |
F3 NE APARTMENT | 3.75 | 42.00 | 3.75 | 42.00 |
F3 N1 APARTMENT | 7.00 | 86.00 | 7.00 | 86.00 |
F3 N2 APARTMENT | 6.50 | 89.75 | 6.50 | 89.75 |
F3 S1 APARTMENT | 2.75 | 108.25 | 2.75 | 108.25 |
F3 S2 APARTMENT | 3.25 | 105.00 | 3.25 | 105.00 |
F4 SW APARTMENT | 1.00 | 40.75 | 1.00 | 40.75 |
F4 NW APARTMENT | 0.50 | 24.00 | 0.50 | 24.00 |
F4 SE APARTMENT | 4.00 | 57.50 | 4.00 | 57.50 |
F4 NE APARTMENT | 1.75 | 50.75 | 1.75 | 50.75 |
F4 N1 APARTMENT | 6.25 | 95.50 | 6.25 | 95.50 |
F4 N2 APARTMENT | 4.50 | 98.75 | 4.50 | 98.75 |
F4 S1 APARTMENT | 3.00 | 115.25 | 3.00 | 115.25 |
F4 S2 APARTMENT | 1.75 | 113.00 | 1.75 | 113.00 |
M SW APARTMENT | 2.25 | 43.75 | 2.25 | 43.75 |
M NW APARTMENT | 0.75 | 26.50 | 0.75 | 26.50 |
M SE APARTMENT | 1.75 | 59.50 | 1.75 | 59.50 |
M NE APARTMENT | 2.25 | 56.25 | 2.25 | 56.25 |
M N1 APARTMENT | 6.00 | 100.25 | 6.00 | 100.25 |
M N2 APARTMENT | 5.25 | 104.00 | 5.25 | 104.00 |
M S1 APARTMENT | 2.00 | 120.50 | 2.00 | 120.50 |
M S2 APARTMENT | 1.50 | 117.75 | 1.50 | 117.75 |
F6 SW APARTMENT | 1.75 | 45.75 | 1.75 | 45.75 |
F6 NW APARTMENT | 1.25 | 28.25 | 1.25 | 28.25 |
F6 SE APARTMENT | 1.00 | 61.00 | 1.00 | 61.00 |
F6 NE APARTMENT | 2.50 | 59.75 | 2.50 | 59.75 |
F6 N1 APARTMENT | 5.50 | 102.00 | 5.50 | 102.00 |
F6 N2 APARTMENT | 4.50 | 106.50 | 4.50 | 106.50 |
F6 S1 APARTMENT | 2.25 | 122.75 | 2.25 | 122.75 |
F6 S2 APARTMENT | 4.00 | 121.00 | 4.00 | 121.00 |
F7 SW APARTMENT | 1.50 | 46.25 | 1.50 | 46.25 |
F7 NW APARTMENT | 0.00 | 29.00 | 0.00 | 29.00 |
F7 SE APARTMENT | 1.50 | 61.75 | 1.50 | 61.75 |
F7 NE APARTMENT | 1.25 | 62.50 | 1.25 | 62.50 |
F7 N1 APARTMENT | 4.75 | 103.00 | 4.75 | 103.00 |
F7 N2 APARTMENT | 5.00 | 108.00 | 5.00 | 108.00 |
F7 S1 APARTMENT | 3.25 | 125.00 | 3.25 | 125.00 |
F7 S2 APARTMENT | 2.00 | 122.25 | 2.00 | 122.25 |
F8 SW APARTMENT | 2.75 | 47.50 | 2.75 | 47.50 |
F8 NW APARTMENT | 0.50 | 30.00 | 0.50 | 30.00 |
F8 SE APARTMENT | 2.75 | 64.50 | 2.75 | 64.50 |
F8 NE APARTMENT | 2.00 | 65.75 | 2.00 | 65.75 |
F8 N1 APARTMENT | 5.25 | 105.00 | 5.25 | 105.00 |
F8 N2 APARTMENT | 6.00 | 111.25 | 6.00 | 111.25 |
F8 S1 APARTMENT | 4.75 | 126.50 | 4.75 | 126.50 |
F8 S2 APARTMENT | 4.75 | 122.75 | 4.75 | 122.75 |
F9 SW APARTMENT | 1.50 | 49.00 | 1.50 | 49.00 |
F9 NW APARTMENT | 0.00 | 31.75 | 0.00 | 31.75 |
F9 SE APARTMENT | 1.00 | 62.50 | 1.00 | 62.50 |
F9 NE APARTMENT | 1.50 | 71.00 | 1.50 | 71.00 |
F9 N1 APARTMENT | 6.25 | 103.50 | 6.25 | 103.50 |
F9 N2 APARTMENT | 6.75 | 107.25 | 6.75 | 107.25 |
F9 S1 APARTMENT | 3.50 | 128.00 | 3.50 | 128.00 |
F9 S2 APARTMENT | 3.00 | 126.00 | 3.00 | 126.00 |
T SW APARTMENT | 0.25 | 34.75 | 0.25 | 34.75 |
T NW APARTMENT | 0.00 | 24.00 | 0.00 | 24.00 |
T SE APARTMENT | 0.00 | 49.50 | 0.00 | 49.50 |
T NE APARTMENT | 0.25 | 50.75 | 0.25 | 50.75 |
T N1 APARTMENT | 4.00 | 99.50 | 4.00 | 99.50 |
T N2 APARTMENT | 2.75 | 99.50 | 2.75 | 99.50 |
T S1 APARTMENT | 2.00 | 70.75 | 2.00 | 70.75 |
T S2 APARTMENT | 1.50 | 70.00 | 1.50 | 70.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 178.75 | 224.00 | 176.50 | 224.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.123 | 0.000 | 0.341 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.123 | 0.000 | 0.329 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.135 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.123 | 0.000 | 0.329 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.074 | 0.000 | 0.323 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.074 | 0.000 | 0.323 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.074 | 0.000 | 0.338 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.074 | 0.000 | 0.339 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.177 | 0.000 | 0.412 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.177 | 0.000 | 0.397 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.177 | 0.000 | 0.413 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.177 | 0.000 | 0.397 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.107 | 0.000 | 0.393 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.393 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.107 | 0.000 | 0.410 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.107 | 0.000 | 0.410 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.210 | 0.000 | 0.464 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.209 | 0.000 | 0.447 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.210 | 0.000 | 0.465 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.209 | 0.000 | 0.447 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.443 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.126 | 0.000 | 0.443 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.462 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.126 | 0.000 | 0.463 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.234 | 0.000 | 0.487 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.234 | 0.000 | 0.468 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.234 | 0.000 | 0.487 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.234 | 0.000 | 0.468 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.141 | 0.000 | 0.465 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.141 | 0.000 | 0.465 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.141 | 0.000 | 0.485 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.141 | 0.000 | 0.485 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.515 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.495 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.516 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.254 | 0.000 | 0.495 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.153 | 0.000 | 0.492 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.153 | 0.000 | 0.492 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.154 | 0.000 | 0.514 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.154 | 0.000 | 0.514 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.272 | 0.000 | 0.540 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.272 | 0.000 | 0.517 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.272 | 0.000 | 0.540 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.272 | 0.000 | 0.517 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.164 | 0.000 | 0.514 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.514 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.164 | 0.000 | 0.538 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.538 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.287 | 0.000 | 0.560 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.287 | 0.000 | 0.537 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.287 | 0.000 | 0.561 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.287 | 0.000 | 0.537 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.173 | 0.000 | 0.533 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.173 | 0.000 | 0.533 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.173 | 0.000 | 0.559 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.173 | 0.000 | 0.559 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.301 | 0.000 | 0.581 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.301 | 0.000 | 0.556 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.301 | 0.000 | 0.581 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.301 | 0.000 | 0.556 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.181 | 0.000 | 0.553 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.181 | 0.000 | 0.553 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.182 | 0.000 | 0.579 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.182 | 0.000 | 0.579 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.314 | 0.000 | 0.601 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.313 | 0.000 | 0.575 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.314 | 0.000 | 0.601 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.313 | 0.000 | 0.575 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.189 | 0.000 | 0.572 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.189 | 0.000 | 0.572 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.189 | 0.000 | 0.599 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.189 | 0.000 | 0.599 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.325 | 0.000 | 0.615 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.325 | 0.000 | 0.588 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.325 | 0.000 | 0.615 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.325 | 0.000 | 0.588 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.196 | 0.000 | 0.585 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.196 | 0.000 | 0.585 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.196 | 0.000 | 0.613 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.196 | 0.000 | 0.613 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.498 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.339 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 578.96 | 18358.63 | 01-JAN-00:15 | 18358.63 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1228.58 | 18739.16 | 17-APR-02:30 | 98784.73 | 03-AUG-20:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
ElectricityPurchased:Plant | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
Cogeneration:ElectricityPurchased | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
ElectricityNet:Plant | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
Cogeneration:ElectricityNet | 3018.52 | 56299.65 | 17-APR-02:30 | 189190.54 | 03-AUG-20:00 |
ExteriorLights:Electricity | 168.37 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.37 | 0.00 | 01-JAN-07:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 578.96 | 18358.63 | 01-JAN-00:15 | 18358.63 | 01-JAN-00:15 |
Cooling:Electricity | 455.45 | 0.00 | 01-JAN-00:15 | 79480.53 | 03-AUG-20:00 |
Heating:Electricity | 173.35 | 0.00 | 01-MAR-10:45 | 55120.45 | 06-FEB-01:00 |
Electricity:Plant | 74.06 | 36.93 | 02-MAR-21:15 | 4931.73 | 06-JUL-12:45 |
HeatRejection:Electricity | 20.46 | 0.00 | 01-JAN-00:15 | 3202.70 | 06-JUL-12:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 53.60 | 36.93 | 02-MAR-21:15 | 1729.03 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1715.18 | 9260.51 | 17-JAN-15:00 | 290801.53 | 06-FEB-07:00 |
Gas:Plant | 1715.18 | 9260.51 | 17-JAN-15:00 | 290801.53 | 06-FEB-07:00 |
WaterSystems:Gas | 1137.55 | 9260.51 | 01-JAN-00:15 | 88184.73 | 10-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1137.55 | 9260.51 | 01-JAN-00:15 | 88184.73 | 10-FEB-08:00 |
Heating:Gas | 577.63 | 0.00 | 17-JAN-12:15 | 227557.46 | 06-FEB-01:15 |
Boiler:Heating:Gas | 577.63 | 0.00 | 17-JAN-12:15 | 227557.46 | 06-FEB-01:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 1982.49 | 0.00 | 01-JAN-00:15 | 396353.14 | 03-AUG-19:00 |
PlantLoopCoolingDemand:HVAC | 1982.49 | 0.00 | 01-JAN-00:15 | 396353.14 | 03-AUG-19:00 |
CoolingCoils:PlantLoopCoolingDemand | 1982.49 | 0.00 | 01-JAN-00:15 | 396353.14 | 03-AUG-19:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5997.13 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-07:00 |
Water:Plant | 5997.13 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-07:00 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5997.13 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-07:00 |
MainsWater:Plant | 5997.13 | 0.00 | 01-JAN-02:15 | 0.00 | 22-JUL-07:00 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1218.61 | 0.00 | 01-JAN-00:15 | 0.00 | 19-JUN-12:00 |
HeatRejection:MainsWater | 1218.61 | 0.00 | 01-JAN-00:15 | 0.00 | 19-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1358.17 | 457.30 | 10-AUG-01:15 | 223263.09 | 06-FEB-07:00 |
PlantLoopHeatingDemand:Plant | 864.38 | 457.30 | 10-AUG-01:15 | 59933.11 | 08-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 864.38 | 457.30 | 10-AUG-01:15 | 59933.11 | 08-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4956.80 | 5032.98 | 27-SEP-03:00 | 589331.87 | 06-FEB-01:00 |
EnergyTransfer:Building | 1428.86 | 3092.66 | 05-MAY-16:45 | 195693.09 | 26-JUN-15:30 |
EnergyTransfer:Zone:G SW APARTMENT | 14.75 | 0.03 | 16-JAN-11:30 | 2670.31 | 30-AUG-15:15 |
Heating:EnergyTransfer | 369.36 | 0.00 | 17-JAN-17:15 | 166047.03 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 4.40 | 0.00 | 02-JAN-11:00 | 1808.72 | 06-FEB-05:00 |
Cooling:EnergyTransfer | 1059.50 | 0.00 | 01-JAN-00:15 | 195693.09 | 26-JUN-15:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 10.35 | 0.00 | 01-JAN-00:15 | 2670.31 | 30-AUG-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 14.30 | 0.03 | 15-OCT-04:15 | 2300.70 | 12-JUL-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.85 | 0.00 | 17-JAN-13:30 | 2010.89 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 7.45 | 0.00 | 01-JAN-00:15 | 2300.70 | 12-JUL-17:15 |
EnergyTransfer:Zone:OFFICE | 20.41 | 0.03 | 09-JAN-08:15 | 3349.89 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:OFFICE | 4.54 | 0.00 | 02-JAN-09:45 | 1875.37 | 06-FEB-07:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 15.87 | 0.00 | 01-JAN-00:15 | 3349.89 | 01-SEP-13:00 |
EnergyTransfer:Zone:G NE APARTMENT | 14.07 | 0.00 | 15-OCT-01:15 | 1997.52 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.61 | 0.00 | 17-JAN-17:15 | 1997.52 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 7.46 | 0.00 | 01-JAN-00:15 | 1744.92 | 14-JUL-09:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.43 | 0.01 | 27-MAR-19:00 | 1290.39 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.23 | 0.00 | 12-JAN-17:15 | 1197.81 | 06-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.19 | 0.00 | 01-JAN-00:15 | 1290.39 | 23-JUN-16:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.43 | 0.02 | 09-MAY-16:30 | 1276.79 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.23 | 0.00 | 12-JAN-17:15 | 1188.10 | 06-FEB-08:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.20 | 0.00 | 01-JAN-00:15 | 1276.79 | 23-JUN-16:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.19 | 0.02 | 26-SEP-12:00 | 1908.02 | 30-AUG-11:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.40 | 0.00 | 01-JAN-10:00 | 971.13 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.79 | 0.00 | 01-JAN-00:15 | 1908.02 | 30-AUG-11:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.29 | 0.00 | 02-MAY-16:45 | 1948.50 | 30-AUG-11:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.34 | 0.00 | 01-JAN-09:45 | 967.56 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 9.95 | 0.00 | 01-JAN-00:15 | 1948.50 | 30-AUG-11:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 20.20 | 0.10 | 27-SEP-05:45 | 3373.23 | 30-AUG-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 3.46 | 0.00 | 02-JAN-10:45 | 1979.28 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 16.74 | 0.00 | 01-JAN-00:15 | 3373.23 | 30-AUG-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 17.99 | 0.04 | 24-MAY-03:30 | 2998.44 | 12-JUL-17:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 6.24 | 0.00 | 12-JAN-15:30 | 2300.32 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 11.75 | 0.00 | 01-JAN-00:15 | 2998.44 | 12-JUL-17:15 |
EnergyTransfer:Zone:F2 SE APARTMENT | 20.64 | 0.09 | 18-JAN-21:00 | 3145.83 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 3.10 | 0.00 | 02-JAN-10:30 | 1950.30 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 17.54 | 0.00 | 01-JAN-00:15 | 3145.83 | 01-SEP-13:00 |
EnergyTransfer:Zone:F2 NE APARTMENT | 17.72 | 0.11 | 30-MAR-11:30 | 2344.33 | 14-JUL-09:30 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 5.99 | 0.00 | 17-JAN-10:15 | 2273.68 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 11.73 | 0.00 | 01-JAN-00:15 | 2344.33 | 14-JUL-09:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 12.10 | 0.00 | 11-FEB-11:00 | 1777.63 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 2.12 | 0.00 | 03-JAN-18:15 | 1243.14 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 9.99 | 0.00 | 01-JAN-00:15 | 1777.63 | 23-JUN-16:45 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 12.09 | 0.02 | 15-FEB-21:45 | 1764.47 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 2.11 | 0.00 | 03-JAN-18:15 | 1241.49 | 06-FEB-01:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 9.98 | 0.00 | 01-JAN-00:15 | 1764.47 | 23-JUN-16:45 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 16.45 | 0.03 | 20-NOV-06:15 | 2421.15 | 30-AUG-11:45 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.76 | 0.00 | 01-JAN-09:30 | 953.62 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 15.69 | 0.00 | 01-JAN-00:15 | 2421.15 | 30-AUG-11:45 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 16.51 | 0.01 | 04-NOV-17:00 | 2437.80 | 30-AUG-11:45 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.75 | 0.00 | 01-JAN-09:30 | 951.66 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 15.76 | 0.00 | 01-JAN-00:15 | 2437.80 | 30-AUG-11:45 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 21.11 | 0.04 | 21-FEB-21:15 | 3389.67 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 3.57 | 0.00 | 02-JAN-10:45 | 2104.67 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 17.54 | 0.00 | 01-JAN-00:15 | 3389.67 | 01-SEP-14:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 18.82 | 0.06 | 19-APR-02:30 | 3051.57 | 12-JUL-17:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 6.40 | 0.00 | 12-JAN-16:15 | 2456.81 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 12.41 | 0.00 | 01-JAN-00:15 | 3051.57 | 12-JUL-17:00 |
EnergyTransfer:Zone:F3 SE APARTMENT | 21.08 | 0.06 | 22-APR-23:45 | 3127.05 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 3.41 | 0.00 | 02-JAN-10:30 | 2073.57 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 17.67 | 0.00 | 01-JAN-00:15 | 3127.05 | 30-AUG-12:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 18.55 | 0.00 | 17-NOV-14:00 | 2477.07 | 26-JUN-15:30 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 6.16 | 0.00 | 17-JAN-10:45 | 2426.10 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 12.39 | 0.00 | 01-JAN-00:15 | 2477.07 | 26-JUN-15:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 12.84 | 0.01 | 06-JUN-11:00 | 1837.91 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 2.07 | 0.00 | 03-JAN-18:15 | 1303.96 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 10.77 | 0.00 | 01-JAN-00:15 | 1837.91 | 23-JUN-16:45 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 12.82 | 0.00 | 30-OCT-15:15 | 1824.80 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 2.06 | 0.00 | 03-JAN-18:15 | 1302.12 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 10.76 | 0.00 | 01-JAN-00:15 | 1824.80 | 23-JUN-16:45 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 17.62 | 0.03 | 15-OCT-19:00 | 2574.96 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.73 | 0.00 | 01-JAN-09:30 | 993.85 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 16.88 | 0.00 | 01-JAN-00:15 | 2574.96 | 30-AUG-12:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 17.63 | 0.01 | 21-OCT-19:15 | 2586.68 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.73 | 0.00 | 01-JAN-09:30 | 992.32 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 16.90 | 0.00 | 01-JAN-00:15 | 2586.68 | 30-AUG-12:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 21.44 | 0.04 | 04-JAN-15:30 | 3404.47 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 3.90 | 0.00 | 02-JAN-10:45 | 2263.73 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 17.55 | 0.00 | 01-JAN-00:15 | 3404.47 | 01-SEP-14:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 19.34 | 0.01 | 26-MAY-04:45 | 3077.39 | 12-JUL-17:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 6.83 | 0.00 | 17-JAN-12:45 | 2617.66 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 12.51 | 0.00 | 01-JAN-00:15 | 3077.39 | 12-JUL-17:00 |
EnergyTransfer:Zone:F4 SE APARTMENT | 21.34 | 0.03 | 14-FEB-22:00 | 3133.30 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 3.77 | 0.00 | 02-JAN-10:30 | 2232.91 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 17.57 | 0.00 | 01-JAN-00:15 | 3133.30 | 30-AUG-12:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 19.08 | 0.07 | 09-JUN-08:00 | 2585.03 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 6.59 | 0.00 | 17-JAN-10:45 | 2585.03 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 12.48 | 0.00 | 01-JAN-00:15 | 2521.40 | 26-JUN-15:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 13.15 | 0.00 | 12-MAY-13:15 | 1866.04 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 2.22 | 0.00 | 03-JAN-18:15 | 1391.14 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 10.94 | 0.00 | 01-JAN-00:15 | 1866.04 | 23-JUN-16:45 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 13.14 | 0.02 | 04-OCT-20:30 | 1852.97 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 2.21 | 0.00 | 03-JAN-15:30 | 1389.22 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 10.93 | 0.00 | 01-JAN-00:15 | 1852.97 | 23-JUN-16:45 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 17.88 | 0.06 | 04-FEB-06:00 | 2591.89 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.82 | 0.00 | 01-JAN-09:45 | 1083.73 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 17.07 | 0.00 | 01-JAN-00:15 | 2591.89 | 30-AUG-12:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 17.88 | 0.02 | 19-MAY-17:00 | 2603.09 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.82 | 0.00 | 01-JAN-09:45 | 1082.31 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 17.06 | 0.00 | 01-JAN-00:15 | 2603.09 | 30-AUG-12:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 21.77 | 0.04 | 07-JUN-02:30 | 3437.47 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 4.16 | 0.00 | 02-JAN-10:45 | 2385.65 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 17.62 | 0.00 | 01-JAN-00:15 | 3437.47 | 01-SEP-14:30 |
EnergyTransfer:Zone:M NW APARTMENT | 19.81 | 0.07 | 08-NOV-13:45 | 3124.85 | 12-JUL-17:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 7.12 | 0.00 | 17-JAN-12:45 | 2737.06 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 12.70 | 0.00 | 01-JAN-00:15 | 3124.85 | 12-JUL-17:00 |
EnergyTransfer:Zone:M SE APARTMENT | 21.65 | 0.04 | 26-NOV-15:15 | 3164.18 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 4.03 | 0.00 | 02-JAN-10:30 | 2354.57 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 17.62 | 0.00 | 01-JAN-00:15 | 3164.18 | 30-AUG-12:00 |
EnergyTransfer:Zone:M NE APARTMENT | 19.54 | 0.12 | 17-APR-00:15 | 2703.37 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 6.87 | 0.00 | 17-JAN-10:45 | 2703.37 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 12.67 | 0.00 | 01-JAN-00:15 | 2572.38 | 26-JUN-15:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 13.51 | 0.01 | 05-JUN-18:15 | 1913.33 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.31 | 0.00 | 03-JAN-11:15 | 1452.94 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 11.21 | 0.00 | 01-JAN-00:15 | 1913.33 | 23-JUN-16:45 |
EnergyTransfer:Zone:M N2 APARTMENT | 13.50 | 0.00 | 26-MAY-06:45 | 1900.30 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.30 | 0.00 | 03-JAN-11:15 | 1450.99 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 11.20 | 0.00 | 01-JAN-00:15 | 1900.30 | 23-JUN-16:45 |
EnergyTransfer:Zone:M S1 APARTMENT | 18.12 | 0.13 | 23-MAY-09:15 | 2627.07 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.88 | 0.00 | 01-JAN-09:45 | 1154.02 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 17.24 | 0.00 | 01-JAN-00:15 | 2627.07 | 30-AUG-12:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 18.12 | 0.01 | 23-OCT-11:00 | 2638.13 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.88 | 0.00 | 01-JAN-09:45 | 1152.71 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 17.24 | 0.00 | 01-JAN-00:15 | 2638.13 | 30-AUG-12:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 21.43 | 0.00 | 19-DEC-04:15 | 3401.35 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 4.75 | 0.00 | 02-JAN-10:45 | 2545.22 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 16.68 | 0.00 | 01-JAN-00:15 | 3401.35 | 01-SEP-14:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 20.01 | 0.06 | 22-SEP-08:00 | 3095.07 | 12-JUL-17:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 7.95 | 0.00 | 17-JAN-13:00 | 2899.32 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 12.06 | 0.00 | 01-JAN-00:15 | 3095.07 | 12-JUL-17:00 |
EnergyTransfer:Zone:F6 SE APARTMENT | 21.28 | 0.03 | 10-MAR-19:00 | 3128.88 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 4.61 | 0.00 | 02-JAN-10:45 | 2512.73 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 16.67 | 0.00 | 01-JAN-00:15 | 3128.88 | 01-SEP-13:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 19.74 | 0.08 | 24-OCT-02:00 | 2865.11 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 7.70 | 0.00 | 17-JAN-12:45 | 2865.11 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 12.04 | 0.00 | 01-JAN-00:15 | 2545.98 | 26-JUN-15:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 13.29 | 0.04 | 15-OCT-08:45 | 1886.15 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 2.75 | 0.00 | 03-JAN-18:15 | 1562.36 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 10.54 | 0.00 | 01-JAN-00:15 | 1886.15 | 23-JUN-16:45 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 13.28 | 0.00 | 29-JUN-20:15 | 1873.20 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 2.75 | 0.00 | 03-JAN-18:15 | 1560.42 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 10.53 | 0.00 | 01-JAN-00:15 | 1873.20 | 23-JUN-16:45 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 17.37 | 0.05 | 03-SEP-06:30 | 2593.13 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 1.10 | 0.00 | 01-JAN-10:15 | 1251.48 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 16.27 | 0.00 | 01-JAN-00:15 | 2593.13 | 30-AUG-12:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 17.37 | 0.07 | 19-MAY-15:45 | 2604.15 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 1.11 | 0.00 | 01-JAN-10:15 | 1250.13 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 16.27 | 0.00 | 01-JAN-00:15 | 2604.15 | 30-AUG-12:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 21.35 | 0.09 | 12-FEB-16:15 | 3389.17 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 5.24 | 0.00 | 02-JAN-10:45 | 2674.18 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 16.11 | 0.00 | 01-JAN-00:15 | 3389.17 | 01-SEP-14:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 20.30 | 0.01 | 19-FEB-12:45 | 3091.79 | 12-JUL-17:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 8.58 | 0.00 | 17-JAN-13:00 | 3026.96 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 11.72 | 0.00 | 01-JAN-00:15 | 3091.79 | 12-JUL-17:00 |
EnergyTransfer:Zone:F7 SE APARTMENT | 21.20 | 0.02 | 20-MAY-02:15 | 3119.79 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 5.09 | 0.00 | 02-JAN-10:45 | 2640.66 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 16.11 | 0.00 | 01-JAN-00:15 | 3119.79 | 01-SEP-13:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 20.03 | 0.01 | 28-SEP-03:00 | 2992.49 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 8.32 | 0.00 | 17-JAN-13:00 | 2992.49 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 11.71 | 0.00 | 01-JAN-00:15 | 2545.02 | 26-JUN-15:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 13.27 | 0.02 | 04-JUN-20:00 | 1884.11 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 3.09 | 0.00 | 03-JAN-18:30 | 1645.52 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 10.19 | 0.00 | 01-JAN-00:15 | 1884.11 | 23-JUN-16:45 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 13.27 | 0.00 | 29-JUN-05:45 | 1871.23 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 3.09 | 0.00 | 03-JAN-18:30 | 1643.61 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 10.18 | 0.00 | 01-JAN-00:15 | 1871.23 | 23-JUN-16:45 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 16.97 | 0.02 | 22-OCT-20:45 | 2582.27 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 1.29 | 0.00 | 01-JAN-12:15 | 1331.13 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 15.68 | 0.00 | 01-JAN-00:15 | 2582.27 | 30-AUG-12:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 16.97 | 0.03 | 15-MAY-09:15 | 2593.25 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 1.29 | 0.00 | 01-JAN-11:00 | 1329.77 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 15.67 | 0.00 | 01-JAN-00:15 | 2593.25 | 30-AUG-12:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 21.43 | 0.05 | 13-MAR-20:45 | 3387.44 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 5.72 | 0.00 | 02-JAN-11:00 | 2795.39 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 15.70 | 0.00 | 01-JAN-00:15 | 3387.44 | 01-SEP-14:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 20.73 | 0.06 | 02-NOV-11:00 | 3146.25 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 9.20 | 0.00 | 17-JAN-13:15 | 3146.25 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 11.53 | 0.00 | 01-JAN-00:15 | 3103.19 | 12-JUL-17:00 |
EnergyTransfer:Zone:F8 SE APARTMENT | 21.26 | 0.01 | 22-MAR-18:30 | 3120.63 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 5.57 | 0.00 | 02-JAN-10:45 | 2760.78 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 15.69 | 0.00 | 01-JAN-00:15 | 3120.63 | 01-SEP-13:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 20.44 | 0.02 | 27-SEP-02:00 | 3111.74 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 8.92 | 0.00 | 17-JAN-13:45 | 3111.74 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 11.52 | 0.00 | 01-JAN-00:15 | 2560.58 | 26-JUN-15:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 13.41 | 0.01 | 12-MAY-10:15 | 1896.66 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 3.44 | 0.00 | 03-JAN-18:45 | 1742.69 | 03-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 9.97 | 0.00 | 01-JAN-00:15 | 1896.66 | 23-JUN-16:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 13.40 | 0.03 | 04-OCT-20:45 | 1883.85 | 23-JUN-16:45 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 3.44 | 0.00 | 03-JAN-18:45 | 1754.89 | 03-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 9.96 | 0.00 | 01-JAN-00:15 | 1883.85 | 23-JUN-16:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 16.74 | 0.04 | 19-SEP-20:00 | 2580.81 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 1.51 | 0.00 | 01-JAN-12:30 | 1406.64 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 15.23 | 0.00 | 01-JAN-00:15 | 2580.81 | 30-AUG-12:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 16.73 | 0.02 | 15-FEB-10:30 | 2591.78 | 30-AUG-12:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 1.51 | 0.00 | 01-JAN-12:30 | 1405.29 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 15.23 | 0.00 | 01-JAN-00:15 | 2591.78 | 30-AUG-12:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 22.15 | 0.04 | 07-MAY-12:45 | 3449.63 | 01-SEP-14:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 6.67 | 0.00 | 02-JAN-11:00 | 3000.70 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 15.48 | 0.00 | 01-JAN-00:15 | 3449.63 | 01-SEP-14:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 22.00 | 0.01 | 12-MAY-13:45 | 3346.56 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 10.40 | 0.00 | 17-JAN-13:45 | 3346.56 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 11.60 | 0.00 | 01-JAN-00:15 | 3233.24 | 12-JUL-16:45 |
EnergyTransfer:Zone:F9 SE APARTMENT | 21.94 | 0.10 | 04-MAY-20:00 | 3198.14 | 06-SEP-12:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 6.48 | 0.00 | 02-JAN-10:45 | 2965.55 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 15.45 | 0.00 | 01-JAN-00:15 | 3198.14 | 06-SEP-12:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 21.66 | 0.07 | 27-SEP-03:15 | 3313.72 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 10.08 | 0.00 | 17-JAN-15:15 | 3313.72 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 11.58 | 0.00 | 01-JAN-00:15 | 2621.49 | 26-JUN-15:30 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 14.17 | 0.02 | 20-SEP-12:15 | 2001.50 | 03-MAY-15:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 4.26 | 0.00 | 05-JAN-21:00 | 2001.50 | 03-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 9.91 | 0.00 | 01-JAN-00:15 | 1991.28 | 23-JUN-16:45 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 14.16 | 0.02 | 19-MAY-08:30 | 2015.07 | 03-MAY-15:15 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 4.25 | 0.00 | 05-JAN-21:00 | 2015.07 | 03-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 9.90 | 0.00 | 01-JAN-00:15 | 1978.34 | 23-JUN-16:45 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 16.82 | 0.07 | 06-JUN-23:45 | 2637.97 | 30-AUG-12:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 1.99 | 0.00 | 02-JAN-10:30 | 1537.07 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 14.83 | 0.00 | 01-JAN-00:15 | 2637.97 | 30-AUG-12:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 16.81 | 0.00 | 16-OCT-20:30 | 2649.20 | 30-AUG-12:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 1.99 | 0.00 | 02-JAN-10:30 | 1535.46 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 14.82 | 0.00 | 01-JAN-00:15 | 2649.20 | 30-AUG-12:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 26.77 | 0.03 | 30-JUN-18:45 | 4132.33 | 06-SEP-14:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 11.43 | 0.00 | 02-JAN-11:00 | 3973.01 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 15.34 | 0.00 | 01-JAN-00:15 | 4132.33 | 06-SEP-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 26.65 | 0.00 | 09-APR-03:15 | 4154.60 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 14.86 | 0.00 | 17-JAN-12:45 | 4154.60 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 11.79 | 0.00 | 01-JAN-00:15 | 3820.16 | 12-JUL-16:45 |
EnergyTransfer:Zone:T SE APARTMENT | 26.37 | 0.02 | 06-APR-04:00 | 3948.68 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 11.16 | 0.00 | 02-JAN-10:45 | 3948.68 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 15.21 | 0.00 | 01-JAN-00:15 | 3881.06 | 06-SEP-12:00 |
EnergyTransfer:Zone:T NE APARTMENT | 26.04 | 0.04 | 28-OCT-14:15 | 4132.05 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 14.42 | 0.00 | 17-JAN-12:30 | 4132.05 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 11.62 | 0.00 | 01-JAN-00:15 | 3087.19 | 26-JUN-15:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.77 | 0.02 | 14-OCT-10:15 | 2646.76 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.95 | 0.00 | 17-JAN-11:45 | 2646.76 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 9.82 | 0.00 | 01-JAN-00:15 | 2435.58 | 29-MAY-13:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.75 | 0.07 | 06-JUN-22:30 | 2645.76 | 06-FEB-01:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.95 | 0.00 | 17-JAN-11:45 | 2645.76 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 9.80 | 0.00 | 01-JAN-00:15 | 2442.18 | 29-MAY-13:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.11 | 0.11 | 08-MAR-00:45 | 3355.68 | 30-AUG-12:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 5.24 | 0.00 | 02-JAN-10:30 | 2446.47 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 13.86 | 0.00 | 01-JAN-00:15 | 3355.68 | 30-AUG-12:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.11 | 0.03 | 18-MAY-22:30 | 3369.39 | 30-AUG-12:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 5.25 | 0.00 | 02-JAN-10:30 | 2445.30 | 06-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 13.86 | 0.00 | 01-JAN-00:15 | 3369.39 | 30-AUG-12:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1326.24 | 457.30 | 10-AUG-01:15 | 222153.45 | 06-FEB-07:15 |
WaterSystems:EnergyTransfer | 864.38 | 457.30 | 10-AUG-01:15 | 59926.98 | 08-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 864.38 | 457.30 | 10-AUG-01:15 | 59926.98 | 08-FEB-08:00 |
EnergyTransfer:HVAC | 2201.70 | 0.00 | 02-MAR-21:15 | 317193.71 | 03-AUG-19:00 |
CoolingCoils:EnergyTransfer | 1558.78 | 0.00 | 01-JAN-00:15 | 317193.71 | 03-AUG-19:00 |
HeatingCoils:EnergyTransfer | 642.92 | 0.00 | 01-MAR-10:45 | 236991.23 | 06-FEB-01:00 |
PlantLoopHeatingDemand:HVAC | 493.79 | 0.00 | 01-MAR-10:45 | 183873.33 | 06-FEB-01:00 |
HeatingCoils:PlantLoopHeatingDemand | 493.79 | 0.00 | 01-MAR-10:45 | 183873.33 | 06-FEB-01:00 |
Boilers:EnergyTransfer | 461.86 | 0.00 | 17-JAN-12:15 | 182045.97 | 06-FEB-01:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 4.399 | -10.350 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 19.703 | 0.000 | 0.295 | 0.000 | 0.000 | -9.880 | 0.000 | -7.369 | -15.243 |
G NW APARTMENT | 6.849 | -7.451 | 0.000 | 0.000 | 3.852 | 2.413 | 12.213 | 10.222 | 0.000 | 0.293 | 0.000 | 0.000 | -10.121 | 0.000 | -6.968 | -11.301 |
OFFICE | 4.539 | -15.869 | 0.000 | 0.000 | 0.525 | 21.954 | 7.547 | 19.529 | 0.000 | 0.113 | 0.000 | 0.000 | -9.915 | 0.000 | -4.158 | -24.265 |
G NE APARTMENT | 6.612 | -7.457 | 0.000 | 0.000 | 3.862 | 2.413 | 12.213 | 10.018 | 0.000 | 0.293 | 0.000 | 0.000 | -9.909 | 0.000 | -6.954 | -11.091 |
G N1 APARTMENT | 3.235 | -6.194 | 0.000 | 0.000 | 3.865 | 2.413 | 12.213 | 3.811 | 0.000 | 0.242 | 0.000 | 0.000 | -6.320 | 0.000 | -5.135 | -8.129 |
G N2 APARTMENT | 3.234 | -6.196 | 0.000 | 0.000 | 3.866 | 2.413 | 12.213 | 3.810 | 0.000 | 0.242 | 0.000 | 0.000 | -6.317 | 0.000 | -5.134 | -8.130 |
G S1 APARTMENT | 1.397 | -9.793 | 0.000 | 0.000 | 3.820 | 2.413 | 12.213 | 13.373 | 0.000 | 0.244 | 0.000 | 0.000 | -6.040 | 0.000 | -5.598 | -12.029 |
G S2 APARTMENT | 1.342 | -9.945 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 13.361 | 0.000 | 0.246 | 0.000 | 0.000 | -6.048 | 0.000 | -5.631 | -11.768 |
F2 SW APARTMENT | 3.464 | -16.735 | 0.000 | 0.000 | 3.755 | 2.413 | 12.213 | 19.003 | 0.000 | 0.387 | 0.000 | 0.000 | -10.632 | 0.000 | -10.163 | -3.704 |
F2 NW APARTMENT | 6.237 | -11.753 | 0.000 | 0.000 | 3.805 | 2.413 | 12.213 | 9.749 | 0.000 | 0.383 | 0.000 | 0.000 | -10.816 | 0.000 | -9.636 | -2.594 |
F2 SE APARTMENT | 3.098 | -17.538 | 0.000 | 0.000 | 3.753 | 2.413 | 12.213 | 18.879 | 0.000 | 0.391 | 0.000 | 0.000 | -10.588 | 0.000 | -10.260 | -2.360 |
F2 NE APARTMENT | 5.989 | -11.734 | 0.000 | 0.000 | 3.815 | 2.413 | 12.213 | 9.560 | 0.000 | 0.381 | 0.000 | 0.000 | -10.574 | 0.000 | -9.619 | -2.445 |
F2 N1 APARTMENT | 2.116 | -9.986 | 0.000 | 0.000 | 3.813 | 2.413 | 12.213 | 3.564 | 0.000 | 0.308 | 0.000 | 0.000 | -6.816 | 0.000 | -7.057 | -0.567 |
F2 N2 APARTMENT | 2.111 | -9.980 | 0.000 | 0.000 | 3.814 | 2.413 | 12.213 | 3.564 | 0.000 | 0.307 | 0.000 | 0.000 | -6.813 | 0.000 | -7.055 | -0.573 |
F2 S1 APARTMENT | 0.764 | -15.688 | 0.000 | 0.000 | 3.741 | 2.413 | 12.213 | 12.931 | 0.000 | 0.311 | 0.000 | 0.000 | -6.519 | 0.000 | -7.677 | -2.489 |
F2 S2 APARTMENT | 0.754 | -15.757 | 0.000 | 0.000 | 3.739 | 2.413 | 12.213 | 12.927 | 0.000 | 0.312 | 0.000 | 0.000 | -6.523 | 0.000 | -7.688 | -2.390 |
F3 SW APARTMENT | 3.570 | -17.539 | 0.000 | 0.000 | 3.747 | 2.413 | 12.213 | 18.736 | 0.000 | 0.493 | 0.000 | 0.000 | -10.843 | 0.000 | -11.664 | -1.126 |
F3 NW APARTMENT | 6.403 | -12.414 | 0.000 | 0.000 | 3.797 | 2.413 | 12.213 | 9.584 | 0.000 | 0.490 | 0.001 | 0.000 | -11.043 | 0.000 | -11.098 | -0.345 |
F3 SE APARTMENT | 3.406 | -17.670 | 0.000 | 0.000 | 3.751 | 2.413 | 12.213 | 18.659 | 0.000 | 0.493 | 0.000 | 0.000 | -10.740 | 0.000 | -11.691 | -0.833 |
F3 NE APARTMENT | 6.161 | -12.389 | 0.000 | 0.000 | 3.806 | 2.413 | 12.213 | 9.404 | 0.000 | 0.485 | 0.000 | 0.000 | -10.792 | 0.000 | -11.077 | -0.224 |
F3 N1 APARTMENT | 2.066 | -10.772 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 3.490 | 0.000 | 0.394 | 1.483 | 0.000 | -6.983 | 0.000 | -8.103 | -0.000 |
F3 N2 APARTMENT | 2.061 | -10.763 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 3.489 | 0.000 | 0.393 | 1.474 | 0.000 | -6.979 | 0.000 | -8.101 | -0.000 |
F3 S1 APARTMENT | 0.732 | -16.883 | 0.000 | 0.000 | 3.725 | 2.413 | 12.213 | 12.754 | 0.000 | 0.396 | 0.078 | 0.000 | -6.672 | 0.000 | -8.757 | -0.001 |
F3 S2 APARTMENT | 0.729 | -16.897 | 0.000 | 0.000 | 3.724 | 2.413 | 12.213 | 12.752 | 0.000 | 0.397 | 0.101 | 0.000 | -6.671 | 0.000 | -8.762 | -0.000 |
F4 SW APARTMENT | 3.898 | -17.546 | 0.000 | 0.000 | 3.747 | 2.413 | 12.213 | 18.575 | 0.000 | 0.534 | 0.001 | 0.000 | -10.943 | 0.000 | -12.535 | -0.355 |
F4 NW APARTMENT | 6.832 | -12.505 | 0.000 | 0.000 | 3.795 | 2.413 | 12.213 | 9.491 | 0.000 | 0.530 | 0.349 | 0.000 | -11.164 | 0.000 | -11.954 | -0.000 |
F4 SE APARTMENT | 3.771 | -17.572 | 0.000 | 0.000 | 3.752 | 2.413 | 12.213 | 18.512 | 0.000 | 0.533 | 0.001 | 0.000 | -10.826 | 0.000 | -12.550 | -0.245 |
F4 NE APARTMENT | 6.592 | -12.484 | 0.000 | 0.000 | 3.804 | 2.413 | 12.213 | 9.316 | 0.000 | 0.524 | 0.465 | 0.000 | -10.908 | 0.000 | -11.934 | -0.001 |
F4 N1 APARTMENT | 2.216 | -10.938 | 0.000 | 0.000 | 3.794 | 2.413 | 12.213 | 3.451 | 0.000 | 0.422 | 2.145 | 0.000 | -7.072 | 0.000 | -8.644 | -0.000 |
F4 N2 APARTMENT | 2.210 | -10.930 | 0.000 | 0.000 | 3.795 | 2.413 | 12.213 | 3.451 | 0.000 | 0.421 | 2.137 | 0.000 | -7.069 | 0.000 | -8.642 | -0.000 |
F4 S1 APARTMENT | 0.817 | -17.067 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 12.647 | 0.000 | 0.425 | 0.874 | 0.000 | -6.741 | 0.000 | -9.303 | -0.000 |
F4 S2 APARTMENT | 0.815 | -17.062 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 12.646 | 0.000 | 0.426 | 0.873 | 0.000 | -6.740 | 0.000 | -9.306 | -0.000 |
M SW APARTMENT | 4.155 | -17.616 | 0.000 | 0.000 | 3.748 | 2.413 | 12.213 | 18.448 | 0.000 | 0.565 | 0.542 | 0.000 | -11.022 | 0.000 | -13.446 | -0.000 |
M NW APARTMENT | 7.119 | -12.695 | 0.000 | 0.000 | 3.795 | 2.413 | 12.213 | 9.419 | 0.000 | 0.562 | 1.268 | 0.000 | -11.261 | 0.000 | -12.832 | -0.001 |
M SE APARTMENT | 4.026 | -17.624 | 0.000 | 0.000 | 3.753 | 2.413 | 12.213 | 18.393 | 0.000 | 0.564 | 0.620 | 0.000 | -10.902 | 0.000 | -13.456 | -0.000 |
M NE APARTMENT | 6.870 | -12.675 | 0.000 | 0.000 | 3.804 | 2.413 | 12.213 | 9.247 | 0.000 | 0.554 | 1.384 | 0.000 | -11.001 | 0.000 | -12.809 | -0.000 |
M N1 APARTMENT | 2.307 | -11.205 | 0.000 | 0.000 | 3.792 | 2.413 | 12.213 | 3.423 | 0.000 | 0.444 | 3.008 | 0.000 | -7.141 | 0.000 | -9.254 | -0.000 |
M N2 APARTMENT | 2.303 | -11.198 | 0.000 | 0.000 | 3.793 | 2.413 | 12.213 | 3.422 | 0.000 | 0.443 | 3.000 | 0.000 | -7.138 | 0.000 | -9.252 | -0.000 |
M S1 APARTMENT | 0.881 | -17.243 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 12.565 | 0.000 | 0.448 | 1.736 | 0.000 | -6.794 | 0.000 | -9.941 | -0.000 |
M S2 APARTMENT | 0.881 | -17.237 | 0.000 | 0.000 | 3.722 | 2.413 | 12.213 | 12.564 | 0.000 | 0.449 | 1.731 | 0.000 | -6.792 | 0.000 | -9.943 | -0.000 |
F6 SW APARTMENT | 4.753 | -16.678 | 0.000 | 0.000 | 3.756 | 2.413 | 12.213 | 18.385 | 0.000 | 0.591 | 0.000 | 0.000 | -11.017 | 0.000 | -14.161 | -0.256 |
F6 NW APARTMENT | 7.954 | -12.059 | 0.000 | 0.000 | 3.803 | 2.413 | 12.213 | 9.398 | 0.000 | 0.588 | 0.461 | 0.000 | -11.268 | 0.000 | -13.502 | -0.001 |
F6 SE APARTMENT | 4.614 | -16.669 | 0.000 | 0.000 | 3.762 | 2.413 | 12.213 | 18.335 | 0.000 | 0.590 | 0.000 | 0.000 | -10.896 | 0.000 | -14.172 | -0.189 |
F6 NE APARTMENT | 7.696 | -12.042 | 0.000 | 0.000 | 3.812 | 2.413 | 12.213 | 9.230 | 0.000 | 0.578 | 0.583 | 0.000 | -11.005 | 0.000 | -13.477 | -0.000 |
F6 N1 APARTMENT | 2.748 | -10.538 | 0.000 | 0.000 | 3.802 | 2.413 | 12.213 | 3.422 | 0.000 | 0.463 | 2.304 | 0.000 | -7.144 | 0.000 | -9.682 | -0.000 |
F6 N2 APARTMENT | 2.746 | -10.531 | 0.000 | 0.000 | 3.802 | 2.413 | 12.213 | 3.421 | 0.000 | 0.462 | 2.295 | 0.000 | -7.141 | 0.000 | -9.680 | -0.000 |
F6 S1 APARTMENT | 1.103 | -16.270 | 0.000 | 0.000 | 3.732 | 2.413 | 12.213 | 12.523 | 0.000 | 0.466 | 1.024 | 0.000 | -6.787 | 0.000 | -10.416 | -0.000 |
F6 S2 APARTMENT | 1.105 | -16.266 | 0.000 | 0.000 | 3.732 | 2.413 | 12.213 | 12.522 | 0.000 | 0.467 | 1.019 | 0.000 | -6.785 | 0.000 | -10.419 | -0.000 |
F7 SW APARTMENT | 5.239 | -16.114 | 0.000 | 0.000 | 3.763 | 2.413 | 12.213 | 18.323 | 0.000 | 0.612 | 0.000 | 0.000 | -11.025 | 0.000 | -14.788 | -0.636 |
F7 NW APARTMENT | 8.583 | -11.721 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 9.372 | 0.000 | 0.609 | 0.106 | 0.000 | -11.288 | 0.000 | -14.095 | -0.001 |
F7 SE APARTMENT | 5.091 | -16.105 | 0.000 | 0.000 | 3.768 | 2.413 | 12.213 | 18.277 | 0.000 | 0.611 | 0.000 | 0.000 | -10.903 | 0.000 | -14.796 | -0.568 |
F7 NE APARTMENT | 8.316 | -11.711 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 9.207 | 0.000 | 0.598 | 0.234 | 0.000 | -11.022 | 0.000 | -14.065 | -0.000 |
F7 N1 APARTMENT | 3.087 | -10.186 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 3.417 | 0.000 | 0.477 | 1.986 | 0.000 | -7.154 | 0.000 | -10.061 | -0.000 |
F7 N2 APARTMENT | 3.085 | -10.181 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 3.416 | 0.000 | 0.476 | 1.979 | 0.000 | -7.151 | 0.000 | -10.059 | -0.000 |
F7 S1 APARTMENT | 1.293 | -15.679 | 0.000 | 0.000 | 3.739 | 2.413 | 12.213 | 12.483 | 0.000 | 0.481 | 0.676 | 0.000 | -6.789 | 0.000 | -10.831 | -0.000 |
F7 S2 APARTMENT | 1.293 | -15.672 | 0.000 | 0.000 | 3.739 | 2.413 | 12.213 | 12.482 | 0.000 | 0.482 | 0.670 | 0.000 | -6.787 | 0.000 | -10.833 | -0.000 |
F8 SW APARTMENT | 5.722 | -15.704 | 0.000 | 0.000 | 3.768 | 2.413 | 12.213 | 18.269 | 0.000 | 0.635 | 0.000 | 0.000 | -11.034 | 0.000 | -15.377 | -0.905 |
F8 NW APARTMENT | 9.200 | -11.531 | 0.000 | 0.000 | 3.813 | 2.413 | 12.213 | 9.348 | 0.000 | 0.631 | 0.000 | 0.000 | -11.310 | 0.000 | -14.656 | -0.121 |
F8 SE APARTMENT | 5.566 | -15.692 | 0.000 | 0.000 | 3.773 | 2.413 | 12.213 | 18.226 | 0.000 | 0.633 | 0.000 | 0.000 | -10.911 | 0.000 | -15.384 | -0.837 |
F8 NE APARTMENT | 8.922 | -11.519 | 0.000 | 0.000 | 3.822 | 2.413 | 12.213 | 9.185 | 0.000 | 0.620 | 0.008 | 0.000 | -11.041 | 0.000 | -14.622 | -0.000 |
F8 N1 APARTMENT | 3.442 | -9.968 | 0.000 | 0.000 | 3.814 | 2.413 | 12.213 | 3.411 | 0.000 | 0.494 | 1.777 | 0.000 | -7.165 | 0.000 | -10.430 | -0.000 |
F8 N2 APARTMENT | 3.439 | -9.960 | 0.000 | 0.000 | 3.814 | 2.413 | 12.213 | 3.410 | 0.000 | 0.493 | 1.768 | 0.000 | -7.162 | 0.000 | -10.427 | -0.000 |
F8 S1 APARTMENT | 1.507 | -15.234 | 0.000 | 0.000 | 3.746 | 2.413 | 12.213 | 12.448 | 0.000 | 0.497 | 0.425 | 0.000 | -6.789 | 0.000 | -11.227 | -0.000 |
F8 S2 APARTMENT | 1.507 | -15.227 | 0.000 | 0.000 | 3.746 | 2.413 | 12.213 | 12.447 | 0.000 | 0.498 | 0.420 | 0.000 | -6.788 | 0.000 | -11.230 | -0.000 |
F9 SW APARTMENT | 6.669 | -15.483 | 0.000 | 0.000 | 3.775 | 2.413 | 12.213 | 18.233 | 0.000 | 0.662 | 0.000 | 0.000 | -11.014 | 0.000 | -15.900 | -1.568 |
F9 NW APARTMENT | 10.395 | -11.603 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 9.329 | 0.000 | 0.658 | 0.000 | 0.000 | -11.309 | 0.000 | -15.165 | -0.748 |
F9 SE APARTMENT | 6.483 | -15.453 | 0.000 | 0.000 | 3.780 | 2.413 | 12.213 | 18.192 | 0.000 | 0.660 | 0.000 | 0.000 | -10.891 | 0.000 | -15.906 | -1.491 |
F9 NE APARTMENT | 10.075 | -11.579 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 9.168 | 0.000 | 0.644 | 0.001 | 0.000 | -11.038 | 0.000 | -15.126 | -0.596 |
F9 N1 APARTMENT | 4.260 | -9.912 | 0.000 | 0.000 | 3.818 | 2.413 | 12.213 | 3.406 | 0.000 | 0.517 | 1.211 | 0.000 | -7.159 | 0.000 | -10.767 | -0.000 |
F9 N2 APARTMENT | 4.254 | -9.903 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 3.405 | 0.000 | 0.516 | 1.203 | 0.000 | -7.156 | 0.000 | -10.765 | -0.000 |
F9 S1 APARTMENT | 1.989 | -14.829 | 0.000 | 0.000 | 3.756 | 2.413 | 12.213 | 12.426 | 0.000 | 0.519 | 0.000 | 0.000 | -6.769 | 0.000 | -11.573 | -0.146 |
F9 S2 APARTMENT | 1.988 | -14.822 | 0.000 | 0.000 | 3.756 | 2.413 | 12.213 | 12.425 | 0.000 | 0.520 | 0.000 | 0.000 | -6.767 | 0.000 | -11.576 | -0.150 |
T SW APARTMENT | 11.428 | -15.341 | 0.000 | 0.000 | 3.803 | 2.413 | 12.213 | 17.988 | 0.000 | 0.684 | 0.000 | 0.000 | -10.556 | 0.000 | -16.267 | -6.365 |
T NW APARTMENT | 14.859 | -11.786 | 0.000 | 0.000 | 3.833 | 2.413 | 12.213 | 9.145 | 0.000 | 0.675 | 0.000 | 0.000 | -10.928 | 0.000 | -15.599 | -4.826 |
T SE APARTMENT | 11.160 | -15.207 | 0.000 | 0.000 | 3.809 | 2.413 | 12.213 | 17.964 | 0.000 | 0.684 | 0.000 | 0.000 | -10.449 | 0.000 | -16.269 | -6.318 |
T NE APARTMENT | 14.423 | -11.621 | 0.000 | 0.000 | 3.843 | 2.413 | 12.213 | 9.010 | 0.000 | 0.667 | 0.000 | 0.000 | -10.682 | 0.000 | -15.566 | -4.701 |
T N1 APARTMENT | 7.950 | -9.815 | 0.000 | 0.000 | 3.836 | 2.413 | 12.213 | 3.347 | 0.000 | 0.526 | 0.000 | 0.000 | -6.901 | 0.000 | -11.029 | -2.540 |
T N2 APARTMENT | 7.949 | -9.804 | 0.000 | 0.000 | 3.837 | 2.413 | 12.213 | 3.345 | 0.000 | 0.526 | 0.000 | 0.000 | -6.897 | 0.000 | -11.030 | -2.552 |
T S1 APARTMENT | 5.245 | -13.862 | 0.000 | 0.000 | 3.789 | 2.413 | 12.213 | 12.296 | 0.000 | 0.555 | 0.000 | 0.000 | -6.511 | 0.000 | -11.792 | -4.346 |
T S2 APARTMENT | 5.247 | -13.862 | 0.000 | 0.000 | 3.789 | 2.413 | 12.213 | 12.293 | 0.000 | 0.556 | 0.000 | 0.000 | -6.507 | 0.000 | -11.795 | -4.347 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 4.214 | 0.000 | 0.652 | 18.327 | 0.000 | -2.284 | 0.000 | -39.439 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.920 | 0.000 | 0.010 | 0.000 | 0.000 | -1.383 | 0.000 | -1.109 | -17.967 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.877 | 0.000 | 0.011 | 0.000 | 0.000 | -1.440 | 0.000 | -1.349 | -17.628 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.852 | 0.000 | 0.011 | 0.000 | 0.000 | -1.468 | 0.000 | -1.524 | -17.400 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.821 | 0.000 | 0.009 | 0.000 | 0.000 | -1.511 | 0.000 | -1.733 | -35.645 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.832 | 0.000 | 0.013 | 0.000 | 0.000 | -1.480 | 0.000 | -1.765 | -17.130 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.832 | 0.000 | 0.014 | 0.000 | 0.000 | -1.470 | 0.000 | -1.848 | -17.058 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.828 | 0.000 | 0.014 | 0.000 | 0.000 | -1.469 | 0.000 | -1.929 | -16.975 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.825 | 0.000 | 0.014 | 0.000 | 0.000 | -1.464 | 0.000 | -1.998 | -16.906 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.775 | 0.000 | 0.006 | 0.000 | 0.000 | -1.425 | 0.000 | -2.121 | -24.701 |
Total Facility | 369.347 | -1059.485 | 0.000 | 0.000 | 299.704 | 416.414 | 980.287 | 902.145 | 0.000 | 39.511 | 61.750 | 0.000 | -721.356 | 0.000 | -940.489 | -347.832 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-15:15 | 0.00 | -2670.27 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3635.00 | 0.00 | 34.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1620.13 |
G NW APARTMENT | 12-JUL-17:15 | 0.00 | -2302.88 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2656.02 | 0.00 | 292.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1570.07 |
OFFICE | 01-SEP-13:00 | 0.00 | -3349.76 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3155.26 | 0.00 | 73.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2111.82 |
G NE APARTMENT | 14-JUL-09:30 | 0.00 | -1744.69 | 0.00 | 0.00 | 40.59 | 28.81 | 406.15 | 2453.66 | 0.00 | 46.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1230.99 |
G N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1290.98 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 561.59 | 0.00 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -430.69 |
G N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1277.45 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 561.93 | 0.00 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.57 |
G S1 APARTMENT | 30-AUG-11:45 | 0.00 | -1907.34 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2931.97 | 0.00 | 169.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1669.80 |
G S2 APARTMENT | 30-AUG-11:45 | 0.00 | -1947.83 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2931.16 | 0.00 | 169.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1628.51 |
F2 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3373.12 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3595.10 | 0.00 | 49.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -892.36 |
F2 NW APARTMENT | 12-JUL-17:15 | 0.00 | -3001.76 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2609.59 | 0.00 | 383.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -915.94 |
F2 SE APARTMENT | 01-SEP-13:00 | 0.00 | -3145.59 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3110.36 | 0.00 | 105.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -528.68 |
F2 NE APARTMENT | 14-JUL-09:30 | 0.00 | -2344.06 | 0.00 | 0.00 | 40.76 | 28.81 | 406.15 | 2424.25 | 0.00 | 67.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -623.30 |
F2 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1791.85 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 544.73 | 0.00 | 438.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8.51 |
F2 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1778.54 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 544.95 | 0.00 | 438.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.84 |
F2 S1 APARTMENT | 30-AUG-11:45 | 0.00 | -2420.43 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2895.98 | 0.00 | 197.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1148.67 |
F2 S2 APARTMENT | 30-AUG-11:45 | 0.00 | -2437.08 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2895.72 | 0.00 | 197.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1131.77 |
F3 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3389.45 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3764.51 | 0.00 | 117.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -983.77 |
F3 NW APARTMENT | 12-JUL-17:00 | 0.00 | -3055.12 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2620.55 | 0.00 | 507.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -890.10 |
F3 SE APARTMENT | 30-AUG-12:00 | 0.00 | -3126.31 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3250.88 | 0.00 | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -887.27 |
F3 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2479.01 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 761.30 | 0.00 | 810.08 | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1853.93 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 540.99 | 0.00 | 494.30 | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1840.65 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 541.21 | 0.00 | 494.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12.05 |
F3 S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2574.36 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2889.79 | 0.00 | 273.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1064.76 |
F3 S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2586.08 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2889.60 | 0.00 | 273.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1052.86 |
F4 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3404.25 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3747.78 | 0.00 | 130.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.63 |
F4 NW APARTMENT | 12-JUL-17:00 | 0.00 | -3081.21 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2605.98 | 0.00 | 549.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.83 |
F4 SE APARTMENT | 30-AUG-12:00 | 0.00 | -3132.58 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3239.79 | 0.00 | 299.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -882.84 |
F4 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2523.52 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 758.23 | 0.00 | 879.65 | 265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1883.33 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 538.70 | 0.00 | 535.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8.48 |
F4 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1870.09 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 538.91 | 0.00 | 535.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21.69 |
F4 S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2591.31 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2880.00 | 0.00 | 285.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1049.52 |
F4 S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2602.51 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2879.82 | 0.00 | 285.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1038.15 |
M SW APARTMENT | 01-SEP-14:30 | 0.00 | -3437.25 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3734.07 | 0.00 | 141.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -929.79 |
M NW APARTMENT | 12-JUL-17:00 | 0.00 | -3128.92 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2593.96 | 0.00 | 583.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -866.19 |
M SE APARTMENT | 30-AUG-12:00 | 0.00 | -3163.47 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3230.23 | 0.00 | 310.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -852.83 |
M NE APARTMENT | 26-JUN-15:30 | 0.00 | -2574.67 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 755.08 | 0.00 | 932.67 | 266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1932.17 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 536.27 | 0.00 | 568.94 | 9.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1918.96 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 536.49 | 0.00 | 568.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.62 |
M S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2626.49 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2871.85 | 0.00 | 294.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1015.48 |
M S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2637.55 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2871.67 | 0.00 | 294.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.24 |
F6 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3401.13 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3724.42 | 0.00 | 150.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.49 |
F6 NW APARTMENT | 12-JUL-17:00 | 0.00 | -3099.26 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2585.82 | 0.00 | 610.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.79 |
F6 SE APARTMENT | 01-SEP-13:00 | 0.00 | -3128.64 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3071.34 | 0.00 | 160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -561.24 |
F6 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2548.32 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 754.34 | 0.00 | 973.51 | 199.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1905.16 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 535.54 | 0.00 | 595.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.07 |
F6 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1892.03 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 535.76 | 0.00 | 594.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56.13 |
F6 S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2592.58 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2866.12 | 0.00 | 302.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1051.41 |
F6 S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2603.59 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2865.94 | 0.00 | 302.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1040.21 |
F7 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3388.94 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3715.58 | 0.00 | 158.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -976.90 |
F7 NW APARTMENT | 12-JUL-17:00 | 0.00 | -3096.11 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2578.28 | 0.00 | 634.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.66 |
F7 SE APARTMENT | 01-SEP-13:00 | 0.00 | -3119.54 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3065.80 | 0.00 | 169.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -573.36 |
F7 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2547.42 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 753.00 | 0.00 | 1008.14 | 165.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1903.67 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 534.48 | 0.00 | 617.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -66.03 |
F7 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1890.60 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 534.69 | 0.00 | 617.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79.02 |
F7 S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2581.73 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2860.82 | 0.00 | 308.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1063.53 |
F7 S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2592.70 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2860.64 | 0.00 | 308.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1052.37 |
F8 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3387.21 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3707.25 | 0.00 | 166.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -977.46 |
F8 NW APARTMENT | 12-JUL-17:00 | 0.00 | -3107.64 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2571.30 | 0.00 | 654.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -935.67 |
F8 SE APARTMENT | 06-SEP-12:00 | 0.00 | -3121.39 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2638.39 | 0.00 | 540.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.15 |
F8 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2563.06 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 751.37 | 0.00 | 1039.13 | 151.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -1917.02 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 533.24 | 0.00 | 637.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.23 |
F8 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -1904.02 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 533.46 | 0.00 | 637.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.13 |
F8 S1 APARTMENT | 30-AUG-12:00 | 0.00 | -2580.28 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2855.98 | 0.00 | 314.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1065.78 |
F8 S2 APARTMENT | 30-AUG-12:00 | 0.00 | -2591.24 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2855.80 | 0.00 | 314.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1054.63 |
F9 SW APARTMENT | 01-SEP-14:30 | 0.00 | -3449.39 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3698.22 | 0.00 | 172.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -912.72 |
F9 NW APARTMENT | 12-JUL-16:45 | 0.00 | -3237.98 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2592.19 | 0.00 | 740.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -912.17 |
F9 SE APARTMENT | 06-SEP-12:00 | 0.00 | -3203.11 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2630.72 | 0.00 | 561.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -464.47 |
F9 NE APARTMENT | 26-JUN-15:30 | 0.00 | -2624.09 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 747.36 | 0.00 | 1061.81 | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 23-JUN-16:38 | 0.00 | -2014.08 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 530.49 | 0.00 | 658.08 | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 23-JUN-16:38 | 0.00 | -2000.94 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 530.70 | 0.00 | 657.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4.91 |
F9 S1 APARTMENT | 30-AUG-12:15 | 0.00 | -2637.79 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2846.88 | 0.00 | 321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -989.05 |
F9 S2 APARTMENT | 30-AUG-12:15 | 0.00 | -2649.02 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2846.70 | 0.00 | 321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -977.64 |
T SW APARTMENT | 06-SEP-14:30 | 0.00 | -4135.17 | 0.00 | 0.00 | 40.76 | 50.41 | 400.26 | 3729.54 | 0.00 | 474.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -560.43 |
T NW APARTMENT | 12-JUL-16:45 | 0.00 | -3825.84 | 0.00 | 0.00 | 84.77 | 144.04 | 588.62 | 2552.61 | 0.00 | 780.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.18 |
T SE APARTMENT | 06-SEP-12:00 | 0.00 | -3887.06 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 2582.63 | 0.00 | 585.67 | 243.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 26-JUN-15:30 | 0.00 | -3090.28 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 725.64 | 0.00 | 1158.09 | 585.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-MAY-13:30 | 0.00 | -2435.68 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 694.87 | 0.00 | 824.23 | 464.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-MAY-13:30 | 0.00 | -2442.30 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 694.67 | 0.00 | 824.22 | 471.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 30-AUG-12:15 | 0.00 | -3355.38 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2818.46 | 0.00 | 325.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -246.74 |
T S2 APARTMENT | 30-AUG-12:15 | 0.00 | -3369.09 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2818.18 | 0.00 | 325.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -232.75 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-15:30 | 0.00 | -195866.52 | 0.00 | 0.00 | 3928.51 | 16050.79 | 38103.94 | 87911.86 | 0.00 | 70060.30 | 0.00 | 0.00 | 0.00 | 0.00 | -76.61 | -20112.28 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-FEB-05:00 | 1808.65 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1415.89 | 0.00 | -699.43 | -149.89 |
G NW APARTMENT | 06-FEB-01:00 | 2010.40 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1440.43 | 0.00 | -835.04 | -203.88 |
OFFICE | 06-FEB-07:00 | 1875.37 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1405.73 | 0.00 | -657.44 | -320.47 |
G NE APARTMENT | 06-FEB-01:00 | 1997.00 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1432.96 | 0.00 | -835.04 | -197.95 |
G N1 APARTMENT | 25-APR-08:55 | 1671.97 | 0.00 | 0.00 | 0.00 | 46.13 | 28.81 | 394.37 | 311.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1458.74 | -994.11 |
G N2 APARTMENT | 25-APR-08:55 | 1695.67 | 0.00 | 0.00 | 0.00 | 46.04 | 28.81 | 394.37 | 310.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1458.83 | -1016.22 |
G S1 APARTMENT | 06-MAR-15:55 | 1648.05 | 0.00 | 0.00 | 0.00 | 46.03 | 50.41 | 400.26 | 506.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1387.81 | -1263.58 |
G S2 APARTMENT | 06-MAR-15:55 | 1463.87 | 0.00 | 0.00 | 0.00 | 45.85 | 50.41 | 400.26 | 504.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1393.53 | -1071.70 |
F2 SW APARTMENT | 06-FEB-05:00 | 1979.22 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 34.22 | 0.00 | -1464.30 | 0.00 | -1005.71 | 0.00 |
F2 NW APARTMENT | 06-FEB-01:00 | 2299.83 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1496.66 | 0.00 | -1200.71 | -71.41 |
F2 SE APARTMENT | 06-FEB-05:00 | 1950.25 | 0.00 | 0.00 | 0.00 | 189.67 | 43.21 | 223.68 | 0.00 | 0.00 | 0.00 | 53.37 | 0.00 | -1454.47 | 0.00 | -1005.71 | 0.00 |
F2 NE APARTMENT | 06-FEB-01:00 | 2273.16 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1484.40 | 0.00 | -1200.71 | -57.01 |
F2 N1 APARTMENT | 06-MAR-15:55 | 1973.24 | 0.00 | 0.00 | 0.00 | 45.99 | 50.41 | 400.26 | 92.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1733.43 | -828.59 |
F2 N2 APARTMENT | 06-MAR-15:55 | 1962.20 | 0.00 | 0.00 | 0.00 | 46.02 | 50.41 | 400.26 | 92.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1733.33 | -818.16 |
F2 S1 APARTMENT | 06-MAR-16:00 | 1394.94 | 0.00 | 0.00 | 0.00 | 44.39 | 50.41 | 400.26 | 472.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1733.74 | -628.44 |
F2 S2 APARTMENT | 06-MAR-16:00 | 1394.44 | 0.00 | 0.00 | 0.00 | 44.38 | 50.41 | 400.26 | 472.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1733.80 | -627.89 |
F3 SW APARTMENT | 06-FEB-01:00 | 2104.24 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 361.57 | 0.00 | -1512.67 | 0.00 | -1422.09 | 0.00 |
F3 NW APARTMENT | 06-FEB-01:00 | 2456.30 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 17.15 | 0.00 | -1520.31 | 0.00 | -1422.09 | 0.00 |
F3 SE APARTMENT | 06-FEB-01:00 | 2073.14 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 377.78 | 0.00 | -1497.78 | 0.00 | -1422.09 | 0.00 |
F3 NE APARTMENT | 06-FEB-01:00 | 2425.58 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 33.01 | 0.00 | -1505.45 | 0.00 | -1422.09 | 0.00 |
F3 N1 APARTMENT | 06-MAR-15:55 | 2331.97 | 0.00 | 0.00 | 0.00 | 45.55 | 50.41 | 400.26 | 79.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1964.65 | -943.28 |
F3 N2 APARTMENT | 06-MAR-15:55 | 2313.52 | 0.00 | 0.00 | 0.00 | 45.59 | 50.41 | 400.26 | 80.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1964.52 | -925.63 |
F3 S1 APARTMENT | 10-NOV-07:00 | 1771.56 | 0.00 | 0.00 | 0.00 | 163.27 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -238.22 | 0.00 | -1972.94 | -142.35 |
F3 S2 APARTMENT | 10-NOV-07:00 | 1731.01 | 0.00 | 0.00 | 0.00 | 163.20 | 100.83 | 317.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -238.42 | 0.00 | -1973.86 | -100.61 |
F4 SW APARTMENT | 06-FEB-01:00 | 2263.28 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 382.87 | 0.00 | -1524.98 | 0.00 | -1590.11 | 0.00 |
F4 NW APARTMENT | 06-FEB-01:00 | 2617.13 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 39.07 | 0.00 | -1535.04 | 0.00 | -1590.12 | 0.00 |
F4 SE APARTMENT | 06-FEB-01:00 | 2232.45 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 397.26 | 0.00 | -1508.55 | 0.00 | -1590.11 | 0.00 |
F4 NE APARTMENT | 06-FEB-01:00 | 2584.48 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 55.24 | 0.00 | -1518.56 | 0.00 | -1590.12 | 0.00 |
F4 N1 APARTMENT | 03-MAY-14:15 | 2055.25 | 0.00 | 0.00 | 0.00 | 42.24 | 50.41 | 400.26 | 194.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2315.24 | -427.51 |
F4 N2 APARTMENT | 03-MAY-14:15 | 2047.20 | 0.00 | 0.00 | 0.00 | 42.27 | 50.41 | 400.26 | 194.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2315.15 | -419.97 |
F4 S1 APARTMENT | 10-NOV-07:15 | 1160.80 | 0.00 | 0.00 | 0.00 | 138.54 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 548.05 | 0.00 | -216.85 | 0.00 | -2106.78 | 0.00 |
F4 S2 APARTMENT | 10-NOV-07:15 | 1152.09 | 0.00 | 0.00 | 0.00 | 138.54 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 557.00 | 0.00 | -216.85 | 0.00 | -2107.01 | 0.00 |
M SW APARTMENT | 06-FEB-01:00 | 2385.19 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 409.40 | 0.00 | -1534.82 | 0.00 | -1728.72 | 0.00 |
M NW APARTMENT | 06-FEB-01:00 | 2736.52 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 69.52 | 0.00 | -1546.27 | 0.00 | -1728.72 | 0.00 |
M SE APARTMENT | 06-FEB-01:00 | 2354.11 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 422.99 | 0.00 | -1517.33 | 0.00 | -1728.72 | 0.00 |
M NE APARTMENT | 06-FEB-01:00 | 2702.82 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 85.73 | 0.00 | -1528.78 | 0.00 | -1728.72 | 0.00 |
M N1 APARTMENT | 03-MAY-14:15 | 2121.84 | 0.00 | 0.00 | 0.00 | 42.20 | 50.41 | 400.26 | 189.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2490.58 | -313.71 |
M N2 APARTMENT | 03-MAY-14:15 | 2113.56 | 0.00 | 0.00 | 0.00 | 42.24 | 50.41 | 400.26 | 189.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2490.49 | -305.96 |
M S1 APARTMENT | 10-NOV-07:15 | 1347.44 | 0.00 | 0.00 | 0.00 | 138.54 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 510.13 | 0.00 | -218.78 | 0.00 | -2253.56 | 0.00 |
M S2 APARTMENT | 10-NOV-07:15 | 1339.27 | 0.00 | 0.00 | 0.00 | 138.54 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 518.49 | 0.00 | -218.76 | 0.00 | -2253.77 | 0.00 |
F6 SW APARTMENT | 06-FEB-01:00 | 2544.74 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 374.81 | 0.00 | -1540.24 | 0.00 | -1848.26 | 0.00 |
F6 NW APARTMENT | 06-FEB-01:00 | 2898.77 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 33.61 | 0.00 | -1553.06 | 0.00 | -1848.26 | 0.00 |
F6 SE APARTMENT | 06-FEB-01:00 | 2512.24 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 389.04 | 0.00 | -1521.97 | 0.00 | -1848.26 | 0.00 |
F6 NE APARTMENT | 06-FEB-01:00 | 2864.54 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 49.57 | 0.00 | -1534.80 | 0.00 | -1848.27 | 0.00 |
F6 N1 APARTMENT | 03-MAY-14:15 | 2080.29 | 0.00 | 0.00 | 0.00 | 42.70 | 50.41 | 400.26 | 191.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2644.36 | -120.61 |
F6 N2 APARTMENT | 03-MAY-14:15 | 2072.43 | 0.00 | 0.00 | 0.00 | 42.74 | 50.41 | 400.26 | 191.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2644.28 | -113.31 |
F6 S1 APARTMENT | 10-NOV-07:15 | 2092.09 | 0.00 | 0.00 | 0.00 | 138.64 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.15 | 0.00 | -2374.17 | -115.63 |
F6 S2 APARTMENT | 10-NOV-07:15 | 2092.82 | 0.00 | 0.00 | 0.00 | 138.63 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.14 | 0.00 | -2374.26 | -116.28 |
F7 SW APARTMENT | 06-FEB-01:00 | 2673.69 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 356.96 | 0.00 | -1545.34 | 0.00 | -1954.26 | 0.00 |
F7 NW APARTMENT | 06-FEB-01:00 | 3026.39 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 | -1559.27 | 0.00 | -1954.27 | 0.00 |
F7 SE APARTMENT | 06-FEB-01:00 | 2640.16 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 371.62 | 0.00 | -1526.47 | 0.00 | -1954.26 | 0.00 |
F7 NE APARTMENT | 06-FEB-01:00 | 2991.91 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 33.79 | 0.00 | -1540.39 | 0.00 | -1954.27 | 0.00 |
F7 N1 APARTMENT | 03-MAY-14:15 | 2067.70 | 0.00 | 0.00 | 0.00 | 43.10 | 50.41 | 400.26 | 192.71 | 0.00 | 0.00 | 29.29 | 0.00 | 0.00 | 0.00 | -2783.48 | 0.00 |
F7 N2 APARTMENT | 03-MAY-14:15 | 2059.47 | 0.00 | 0.00 | 0.00 | 43.14 | 50.41 | 400.26 | 193.21 | 0.00 | 0.00 | 36.90 | 0.00 | 0.00 | 0.00 | -2783.40 | 0.00 |
F7 S1 APARTMENT | 10-NOV-07:15 | 2372.71 | 0.00 | 0.00 | 0.00 | 139.40 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -215.31 | 0.00 | -2488.32 | -284.72 |
F7 S2 APARTMENT | 10-NOV-07:15 | 2374.04 | 0.00 | 0.00 | 0.00 | 139.39 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -215.30 | 0.00 | -2488.37 | -285.99 |
F8 SW APARTMENT | 06-FEB-01:00 | 2794.88 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 335.81 | 0.00 | -1549.56 | 0.00 | -2050.08 | 0.00 |
F8 NW APARTMENT | 06-FEB-01:00 | 3145.67 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1564.46 | 0.00 | -2050.08 | -0.08 |
F8 SE APARTMENT | 06-FEB-01:00 | 2760.27 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 351.06 | 0.00 | -1530.20 | 0.00 | -2050.08 | 0.00 |
F8 NE APARTMENT | 06-FEB-01:00 | 3111.14 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 15.06 | 0.00 | -1545.07 | 0.00 | -2050.08 | 0.00 |
F8 N1 APARTMENT | 03-MAY-14:10 | 2443.03 | 0.00 | 0.00 | 0.00 | 43.44 | 50.41 | 400.26 | 194.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2940.22 | -191.01 |
F8 N2 APARTMENT | 03-MAY-14:10 | 2478.16 | 0.00 | 0.00 | 0.00 | 43.49 | 50.41 | 400.26 | 194.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2939.09 | -227.90 |
F8 S1 APARTMENT | 10-NOV-07:15 | 2369.67 | 0.00 | 0.00 | 0.00 | 140.14 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.40 | 0.00 | -2599.41 | -173.23 |
F8 S2 APARTMENT | 10-NOV-07:15 | 2370.85 | 0.00 | 0.00 | 0.00 | 140.13 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.40 | 0.00 | -2599.45 | -174.35 |
F9 SW APARTMENT | 06-FEB-01:00 | 3000.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 218.40 | 0.00 | -1549.63 | 0.00 | -2137.90 | 0.00 |
F9 NW APARTMENT | 06-FEB-01:00 | 3345.95 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1565.87 | 0.00 | -2137.90 | -111.14 |
F9 SE APARTMENT | 06-FEB-01:00 | 2965.01 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 233.75 | 0.00 | -1529.82 | 0.00 | -2137.90 | 0.00 |
F9 NE APARTMENT | 03-MAY-14:10 | 3408.45 | 0.00 | 0.00 | 0.00 | 44.76 | 50.41 | 400.26 | 341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3166.98 | -1077.90 |
F9 N1 APARTMENT | 03-MAY-14:10 | 3032.86 | 0.00 | 0.00 | 0.00 | 43.91 | 50.41 | 400.26 | 197.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3048.76 | -676.52 |
F9 N2 APARTMENT | 03-MAY-14:10 | 3069.72 | 0.00 | 0.00 | 0.00 | 43.96 | 50.41 | 400.26 | 198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3047.54 | -715.31 |
F9 S1 APARTMENT | 10-NOV-07:15 | 2382.23 | 0.00 | 0.00 | 0.00 | 141.76 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -207.05 | 0.00 | -2702.79 | -90.37 |
F9 S2 APARTMENT | 10-NOV-07:15 | 2384.32 | 0.00 | 0.00 | 0.00 | 141.75 | 93.62 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -207.03 | 0.00 | -2702.84 | -92.43 |
T SW APARTMENT | 06-FEB-01:00 | 3972.34 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1511.86 | 0.00 | -2219.07 | -710.36 |
T NW APARTMENT | 06-FEB-01:00 | 4153.89 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1532.72 | 0.00 | -2219.07 | -871.05 |
T SE APARTMENT | 06-FEB-01:00 | 3948.00 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1492.17 | 0.00 | -2219.07 | -705.71 |
T NE APARTMENT | 06-FEB-01:00 | 4131.31 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1512.74 | 0.00 | -2219.07 | -868.45 |
T N1 APARTMENT | 03-MAY-14:25 | 3521.96 | 0.00 | 0.00 | 0.00 | 44.03 | 50.41 | 400.26 | 179.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3161.15 | -1034.69 |
T N2 APARTMENT | 03-MAY-14:25 | 3560.13 | 0.00 | 0.00 | 0.00 | 44.08 | 50.41 | 400.26 | 179.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3159.93 | -1074.84 |
T S1 APARTMENT | 24-MAY-13:00 | 2641.57 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 9.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2964.08 | -144.53 |
T S2 APARTMENT | 24-MAY-13:00 | 2643.02 | 0.00 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 9.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2964.13 | -145.97 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-01:00 | 166012.13 | 0.00 | 0.00 | 0.00 | 14984.04 | 7980.64 | 21105.27 | 0.00 | 0.00 | 0.00 | 1595.85 | 0.00 | -99881.17 | 0.00 | -111796.76 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Sec1.1A-General InformationData | |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 176.50 |
Number of hours cooling loads not met | 224.00 |
Number of hours not met | 400.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 25049.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.37 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 173.35 | 0.00 | 577.63 | 205249.71 | 0.00 | 0.00 |
Space Cooling | 455.45 | 79480.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.60 | 1729.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.46 | 3202.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 578.96 | 18358.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1137.55 | 85551.83 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 49704.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3018.52 | 1715.18 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3018.52 |
Natural Gas | 0.00 | 1715.18 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 4733.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 22.12 |
Space Cooling | 58.12 |
Fans-Interior | 73.88 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 33.59 |
Subtotal | 385.19 |
Natural Gas [MJ/m2] | |
Space Heating | 73.71 |
Service Water Heating | 145.16 |
Miscellaneous | 0.00 |
Subtotal | 218.87 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.80 |
Space Heating | 15.86 |
Space Cooling | 9.62 |
Fans-Interior | 12.23 |
Service Water Heating | 24.03 |
Receptacle Equipment | 23.89 |
Miscellaneous | 5.56 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.204826 |
G NW APARTMENT DIRECT AIR | 0.190760 |
OFFICE DIRECT AIR | 0.281549 |
G NE APARTMENT DIRECT AIR | 0.150540 |
G N1 APARTMENT DIRECT AIR | 0.102506 |
G N2 APARTMENT DIRECT AIR | 0.101105 |
G S1 APARTMENT DIRECT AIR | 0.127164 |
G S2 APARTMENT DIRECT AIR | 0.132062 |
F2 SW APARTMENT DIRECT AIR | 0.268465 |
F2 NW APARTMENT DIRECT AIR | 0.249762 |
F2 SE APARTMENT DIRECT AIR | 0.255228 |
F2 NE APARTMENT DIRECT AIR | 0.202151 |
F2 N1 APARTMENT DIRECT AIR | 0.141026 |
F2 N2 APARTMENT DIRECT AIR | 0.139843 |
F2 S1 APARTMENT DIRECT AIR | 0.171177 |
F2 S2 APARTMENT DIRECT AIR | 0.173013 |
F3 SW APARTMENT DIRECT AIR | 0.269956 |
F3 NW APARTMENT DIRECT AIR | 0.252301 |
F3 SE APARTMENT DIRECT AIR | 0.242014 |
F3 NE APARTMENT DIRECT AIR | 0.205824 |
F3 N1 APARTMENT DIRECT AIR | 0.144857 |
F3 N2 APARTMENT DIRECT AIR | 0.143685 |
F3 S1 APARTMENT DIRECT AIR | 0.174343 |
F3 S2 APARTMENT DIRECT AIR | 0.175252 |
F4 SW APARTMENT DIRECT AIR | 0.271115 |
F4 NW APARTMENT DIRECT AIR | 0.253768 |
F4 SE APARTMENT DIRECT AIR | 0.241975 |
F4 NE APARTMENT DIRECT AIR | 0.207250 |
F4 N1 APARTMENT DIRECT AIR | 0.146631 |
F4 N2 APARTMENT DIRECT AIR | 0.145465 |
F4 S1 APARTMENT DIRECT AIR | 0.175637 |
F4 S2 APARTMENT DIRECT AIR | 0.176415 |
M SW APARTMENT DIRECT AIR | 0.274326 |
M NW APARTMENT DIRECT AIR | 0.257259 |
M SE APARTMENT DIRECT AIR | 0.245225 |
M NE APARTMENT DIRECT AIR | 0.210648 |
M N1 APARTMENT DIRECT AIR | 0.150192 |
M N2 APARTMENT DIRECT AIR | 0.149031 |
M S1 APARTMENT DIRECT AIR | 0.178816 |
M S2 APARTMENT DIRECT AIR | 0.179574 |
F6 SW APARTMENT DIRECT AIR | 0.271251 |
F6 NW APARTMENT DIRECT AIR | 0.254270 |
F6 SE APARTMENT DIRECT AIR | 0.242364 |
F6 NE APARTMENT DIRECT AIR | 0.207633 |
F6 N1 APARTMENT DIRECT AIR | 0.147522 |
F6 N2 APARTMENT DIRECT AIR | 0.146371 |
F6 S1 APARTMENT DIRECT AIR | 0.175815 |
F6 S2 APARTMENT DIRECT AIR | 0.176571 |
F7 SW APARTMENT DIRECT AIR | 0.270451 |
F7 NW APARTMENT DIRECT AIR | 0.253623 |
F7 SE APARTMENT DIRECT AIR | 0.241741 |
F7 NE APARTMENT DIRECT AIR | 0.206928 |
F7 N1 APARTMENT DIRECT AIR | 0.147050 |
F7 N2 APARTMENT DIRECT AIR | 0.145906 |
F7 S1 APARTMENT DIRECT AIR | 0.175029 |
F7 S2 APARTMENT DIRECT AIR | 0.175784 |
F8 SW APARTMENT DIRECT AIR | 0.271006 |
F8 NW APARTMENT DIRECT AIR | 0.254323 |
F8 SE APARTMENT DIRECT AIR | 0.242382 |
F8 NE APARTMENT DIRECT AIR | 0.207499 |
F8 N1 APARTMENT DIRECT AIR | 0.147885 |
F8 N2 APARTMENT DIRECT AIR | 0.146750 |
F8 S1 APARTMENT DIRECT AIR | 0.175541 |
F8 S2 APARTMENT DIRECT AIR | 0.176297 |
F9 SW APARTMENT DIRECT AIR | 0.280285 |
F9 NW APARTMENT DIRECT AIR | 0.263626 |
F9 SE APARTMENT DIRECT AIR | 0.249538 |
F9 NE APARTMENT DIRECT AIR | 0.212003 |
F9 N1 APARTMENT DIRECT AIR | 0.155959 |
F9 N2 APARTMENT DIRECT AIR | 0.154806 |
F9 S1 APARTMENT DIRECT AIR | 0.181631 |
F9 S2 APARTMENT DIRECT AIR | 0.182469 |
T SW APARTMENT DIRECT AIR | 0.338757 |
T NW APARTMENT DIRECT AIR | 0.313569 |
T SE APARTMENT DIRECT AIR | 0.306246 |
T NE APARTMENT DIRECT AIR | 0.258260 |
T N1 APARTMENT DIRECT AIR | 0.188108 |
T N2 APARTMENT DIRECT AIR | 0.187924 |
T S1 APARTMENT DIRECT AIR | 0.246701 |
T S2 APARTMENT DIRECT AIR | 0.247443 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.204826 |
AIRLOOP G NW MAIN BRANCH | 0.190760 |
AIRLOOP OFFICE MAIN BRANCH | 0.281549 |
AIRLOOP G NE MAIN BRANCH | 0.150540 |
AIRLOOP G N1 MAIN BRANCH | 0.102506 |
AIRLOOP G N2 MAIN BRANCH | 0.101105 |
AIRLOOP G S1 MAIN BRANCH | 0.127164 |
AIRLOOP G S2 MAIN BRANCH | 0.132062 |
AIRLOOP F2 SW MAIN BRANCH | 0.268465 |
AIRLOOP F2 NW MAIN BRANCH | 0.249762 |
AIRLOOP F2 SE MAIN BRANCH | 0.255228 |
AIRLOOP F2 NE MAIN BRANCH | 0.202151 |
AIRLOOP F2 N1 MAIN BRANCH | 0.141026 |
AIRLOOP F2 N2 MAIN BRANCH | 0.139843 |
AIRLOOP F2 S1 MAIN BRANCH | 0.171177 |
AIRLOOP F2 S2 MAIN BRANCH | 0.173013 |
AIRLOOP F3 SW MAIN BRANCH | 0.269956 |
AIRLOOP F3 NW MAIN BRANCH | 0.252301 |
AIRLOOP F3 SE MAIN BRANCH | 0.242014 |
AIRLOOP F3 NE MAIN BRANCH | 0.205824 |
AIRLOOP F3 N1 MAIN BRANCH | 0.144857 |
AIRLOOP F3 N2 MAIN BRANCH | 0.143685 |
AIRLOOP F3 S1 MAIN BRANCH | 0.174343 |
AIRLOOP F3 S2 MAIN BRANCH | 0.175252 |
AIRLOOP F4 SW MAIN BRANCH | 0.271115 |
AIRLOOP F4 NW MAIN BRANCH | 0.253768 |
AIRLOOP F4 SE MAIN BRANCH | 0.241975 |
AIRLOOP F4 NE MAIN BRANCH | 0.207250 |
AIRLOOP F4 N1 MAIN BRANCH | 0.146631 |
AIRLOOP F4 N2 MAIN BRANCH | 0.145465 |
AIRLOOP F4 S1 MAIN BRANCH | 0.175637 |
AIRLOOP F4 S2 MAIN BRANCH | 0.176415 |
AIRLOOP M SW MAIN BRANCH | 0.274326 |
AIRLOOP M NW MAIN BRANCH | 0.257259 |
AIRLOOP M SE MAIN BRANCH | 0.245225 |
AIRLOOP M NE MAIN BRANCH | 0.210648 |
AIRLOOP M N1 MAIN BRANCH | 0.150192 |
AIRLOOP M N2 MAIN BRANCH | 0.149031 |
AIRLOOP M S1 MAIN BRANCH | 0.178816 |
AIRLOOP M S2 MAIN BRANCH | 0.179574 |
AIRLOOP F6 SW MAIN BRANCH | 0.271251 |
AIRLOOP F6 NW MAIN BRANCH | 0.254270 |
AIRLOOP F6 SE MAIN BRANCH | 0.242364 |
AIRLOOP F6 NE MAIN BRANCH | 0.207633 |
AIRLOOP F6 N1 MAIN BRANCH | 0.147522 |
AIRLOOP F6 N2 MAIN BRANCH | 0.146371 |
AIRLOOP F6 S1 MAIN BRANCH | 0.175815 |
AIRLOOP F6 S2 MAIN BRANCH | 0.176571 |
AIRLOOP F7 SW MAIN BRANCH | 0.270451 |
AIRLOOP F7 NW MAIN BRANCH | 0.253623 |
AIRLOOP F7 SE MAIN BRANCH | 0.241741 |
AIRLOOP F7 NE MAIN BRANCH | 0.206928 |
AIRLOOP F7 N1 MAIN BRANCH | 0.147050 |
AIRLOOP F7 N2 MAIN BRANCH | 0.145906 |
AIRLOOP F7 S1 MAIN BRANCH | 0.175029 |
AIRLOOP F7 S2 MAIN BRANCH | 0.175784 |
AIRLOOP F8 SW MAIN BRANCH | 0.271006 |
AIRLOOP F8 NW MAIN BRANCH | 0.254323 |
AIRLOOP F8 SE MAIN BRANCH | 0.242382 |
AIRLOOP F8 NE MAIN BRANCH | 0.207499 |
AIRLOOP F8 N1 MAIN BRANCH | 0.147885 |
AIRLOOP F8 N2 MAIN BRANCH | 0.146750 |
AIRLOOP F8 S1 MAIN BRANCH | 0.175541 |
AIRLOOP F8 S2 MAIN BRANCH | 0.176297 |
AIRLOOP F9 SW MAIN BRANCH | 0.280285 |
AIRLOOP F9 NW MAIN BRANCH | 0.263626 |
AIRLOOP F9 SE MAIN BRANCH | 0.249538 |
AIRLOOP F9 NE MAIN BRANCH | 0.212003 |
AIRLOOP F9 N1 MAIN BRANCH | 0.155959 |
AIRLOOP F9 N2 MAIN BRANCH | 0.154806 |
AIRLOOP F9 S1 MAIN BRANCH | 0.181631 |
AIRLOOP F9 S2 MAIN BRANCH | 0.182469 |
AIRLOOP T SW MAIN BRANCH | 0.338757 |
AIRLOOP T NW MAIN BRANCH | 0.313569 |
AIRLOOP T SE MAIN BRANCH | 0.306246 |
AIRLOOP T NE MAIN BRANCH | 0.258260 |
AIRLOOP T N1 MAIN BRANCH | 0.188108 |
AIRLOOP T N2 MAIN BRANCH | 0.187924 |
AIRLOOP T S1 MAIN BRANCH | 0.246701 |
AIRLOOP T S2 MAIN BRANCH | 0.247443 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.204826 |
AIRLOOP G NW | 0.190760 |
AIRLOOP OFFICE | 0.281549 |
AIRLOOP G NE | 0.150540 |
AIRLOOP G N1 | 0.102506 |
AIRLOOP G N2 | 0.101105 |
AIRLOOP G S1 | 0.127164 |
AIRLOOP G S2 | 0.132062 |
AIRLOOP F2 SW | 0.268465 |
AIRLOOP F2 NW | 0.249762 |
AIRLOOP F2 SE | 0.255228 |
AIRLOOP F2 NE | 0.202151 |
AIRLOOP F2 N1 | 0.141026 |
AIRLOOP F2 N2 | 0.139843 |
AIRLOOP F2 S1 | 0.171177 |
AIRLOOP F2 S2 | 0.173013 |
AIRLOOP F3 SW | 0.269956 |
AIRLOOP F3 NW | 0.252301 |
AIRLOOP F3 SE | 0.242014 |
AIRLOOP F3 NE | 0.205824 |
AIRLOOP F3 N1 | 0.144857 |
AIRLOOP F3 N2 | 0.143685 |
AIRLOOP F3 S1 | 0.174343 |
AIRLOOP F3 S2 | 0.175252 |
AIRLOOP F4 SW | 0.271115 |
AIRLOOP F4 NW | 0.253768 |
AIRLOOP F4 SE | 0.241975 |
AIRLOOP F4 NE | 0.207250 |
AIRLOOP F4 N1 | 0.146631 |
AIRLOOP F4 N2 | 0.145465 |
AIRLOOP F4 S1 | 0.175637 |
AIRLOOP F4 S2 | 0.176415 |
AIRLOOP M SW | 0.274326 |
AIRLOOP M NW | 0.257259 |
AIRLOOP M SE | 0.245225 |
AIRLOOP M NE | 0.210648 |
AIRLOOP M N1 | 0.150192 |
AIRLOOP M N2 | 0.149031 |
AIRLOOP M S1 | 0.178816 |
AIRLOOP M S2 | 0.179574 |
AIRLOOP F6 SW | 0.271251 |
AIRLOOP F6 NW | 0.254270 |
AIRLOOP F6 SE | 0.242364 |
AIRLOOP F6 NE | 0.207633 |
AIRLOOP F6 N1 | 0.147522 |
AIRLOOP F6 N2 | 0.146371 |
AIRLOOP F6 S1 | 0.175815 |
AIRLOOP F6 S2 | 0.176571 |
AIRLOOP F7 SW | 0.270451 |
AIRLOOP F7 NW | 0.253623 |
AIRLOOP F7 SE | 0.241741 |
AIRLOOP F7 NE | 0.206928 |
AIRLOOP F7 N1 | 0.147050 |
AIRLOOP F7 N2 | 0.145906 |
AIRLOOP F7 S1 | 0.175029 |
AIRLOOP F7 S2 | 0.175784 |
AIRLOOP F8 SW | 0.271006 |
AIRLOOP F8 NW | 0.254323 |
AIRLOOP F8 SE | 0.242382 |
AIRLOOP F8 NE | 0.207499 |
AIRLOOP F8 N1 | 0.147885 |
AIRLOOP F8 N2 | 0.146750 |
AIRLOOP F8 S1 | 0.175541 |
AIRLOOP F8 S2 | 0.176297 |
AIRLOOP F9 SW | 0.280285 |
AIRLOOP F9 NW | 0.263626 |
AIRLOOP F9 SE | 0.249538 |
AIRLOOP F9 NE | 0.212003 |
AIRLOOP F9 N1 | 0.155959 |
AIRLOOP F9 N2 | 0.154806 |
AIRLOOP F9 S1 | 0.181631 |
AIRLOOP F9 S2 | 0.182469 |
AIRLOOP T SW | 0.338757 |
AIRLOOP T NW | 0.313569 |
AIRLOOP T SE | 0.306246 |
AIRLOOP T NE | 0.258260 |
AIRLOOP T N1 | 0.188108 |
AIRLOOP T N2 | 0.187924 |
AIRLOOP T S1 | 0.246701 |
AIRLOOP T S2 | 0.247443 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.204826 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.190760 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.281549 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.150540 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.102506 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.101105 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.127164 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.132062 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.268465 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.249762 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.255228 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.202151 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.141026 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.139843 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.171177 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.173013 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.269956 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.252301 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.242014 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.205824 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.144857 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.143685 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.174343 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.175252 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.271115 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.253768 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.241975 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.207250 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.146631 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.145465 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.175637 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.176415 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.274326 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.257259 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.245225 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.210648 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.150192 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.149031 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.178816 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.179574 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.271251 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.254270 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.242364 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.207633 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.147522 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.146371 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.175815 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.176571 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.270451 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.253623 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.241741 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.206928 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.147050 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.145906 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.175029 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.175784 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.271006 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.254323 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.242382 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.207499 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.147885 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.146750 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.175541 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.176297 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.280285 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.263626 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.249538 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.212003 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.155959 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.154806 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.181631 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.182469 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.338757 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.313569 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.306246 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.258260 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.188108 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.187924 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.246701 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.247443 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.204826 | 3710.95 | 2534.03 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.190760 | 3496.34 | 2371.10 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.281549 | 5045.40 | 3463.51 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.150540 | 2874.95 | 1908.00 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.102506 | 2146.32 | 1371.79 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.101105 | 2125.39 | 1356.27 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.127164 | 2550.83 | 1666.26 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.132062 | 2620.20 | 1719.47 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.268465 | 4684.07 | 3254.21 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.249762 | 4408.57 | 3042.10 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.255228 | 4510.08 | 3116.04 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.202151 | 3683.74 | 2498.48 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.141026 | 2746.45 | 1808.61 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.139843 | 2729.06 | 1795.52 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.171177 | 3223.29 | 2164.01 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.173013 | 3249.57 | 2184.21 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.269956 | 4745.97 | 3283.16 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.252301 | 4484.65 | 3082.47 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.242014 | 4360.41 | 2982.73 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.205824 | 3774.23 | 2551.06 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.144857 | 2827.92 | 1860.60 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.143685 | 2810.67 | 1847.63 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.174343 | 3291.60 | 2206.28 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.175252 | 3304.58 | 2216.27 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.271115 | 4792.77 | 3305.32 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.253768 | 4535.26 | 3107.94 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.241975 | 4389.02 | 2991.51 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.207250 | 3822.80 | 2575.87 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.146631 | 2869.82 | 1885.61 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.145465 | 2852.63 | 1872.70 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.175637 | 3327.31 | 2226.10 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.176415 | 3338.41 | 2234.64 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.274326 | 4863.38 | 3348.38 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.257259 | 4609.52 | 3154.02 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.245225 | 4459.56 | 3034.91 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.210648 | 3894.71 | 2620.73 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.150192 | 2935.01 | 1929.37 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.149031 | 2917.88 | 1916.51 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.178816 | 3387.14 | 2265.71 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.179574 | 3397.98 | 2274.05 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.271251 | 4840.00 | 3320.98 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.254270 | 4586.70 | 3127.47 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.242364 | 4438.28 | 3009.71 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.207633 | 3870.08 | 2593.76 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.147522 | 2906.80 | 1903.63 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.146371 | 2889.74 | 1890.87 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.175815 | 3355.49 | 2236.44 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.176571 | 3366.31 | 2244.75 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.270451 | 4846.66 | 3317.88 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.253623 | 4595.07 | 3125.99 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.241741 | 4446.74 | 3008.43 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.206928 | 3876.47 | 2591.49 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.147050 | 2909.40 | 1901.70 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.145906 | 2892.41 | 1889.02 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.175029 | 3354.36 | 2231.14 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.175784 | 3365.18 | 2239.43 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.271006 | 4870.89 | 3329.13 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.254323 | 4621.04 | 3138.79 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.242382 | 4471.64 | 3020.54 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.207499 | 3904.85 | 2605.68 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.147885 | 2930.30 | 1913.91 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.146750 | 2913.40 | 1901.30 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.175541 | 3371.00 | 2239.84 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.176297 | 3381.83 | 2248.14 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.280285 | 5019.77 | 3436.32 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.263626 | 4770.58 | 3246.28 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.249538 | 4590.06 | 3104.35 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.212003 | 3984.60 | 2660.07 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.155959 | 3057.48 | 2006.00 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.154806 | 3040.37 | 1993.21 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.181631 | 3468.35 | 2310.05 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.182469 | 3480.38 | 2319.26 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.338757 | 5890.43 | 4094.32 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.313569 | 5516.60 | 3809.94 | 0.000121 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.306246 | 5422.47 | 3734.93 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.258260 | 4678.47 | 3179.16 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.188108 | 3574.10 | 2386.20 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.187924 | 3571.05 | 2384.04 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.246701 | 4414.82 | 3030.81 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.247443 | 4425.29 | 3038.95 | 0.000097 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.204826 | 0.204826 | 0.204826 | 0.204826 | 3710.95 | 3710.95 | 3505.19 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.190760 | 0.190760 | 0.190760 | 0.190760 | 3496.34 | 3496.34 | 3515.18 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.281549 | 0.281549 | 0.281549 | 0.281549 | 5045.40 | 5045.40 | 4404.70 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.150540 | 0.150540 | 0.150540 | 0.150540 | 2874.95 | 2874.95 | 3511.76 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.102506 | 0.102506 | 0.102506 | 0.102506 | 2146.32 | 2146.32 | 2607.38 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.101105 | 0.101105 | 0.101105 | 0.101105 | 2125.39 | 2125.39 | 2607.29 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.127164 | 0.127164 | 0.127164 | 0.127164 | 2550.83 | 2550.83 | 2593.88 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.132062 | 0.132062 | 0.132062 | 0.132062 | 2620.20 | 2620.20 | 2602.28 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.268465 | 0.268465 | 0.268465 | 0.268465 | 4684.07 | 4684.07 | 3642.24 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.249762 | 0.249762 | 0.249762 | 0.249762 | 4408.57 | 4408.57 | 3655.48 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.255228 | 0.255228 | 0.255228 | 0.255228 | 4510.08 | 4510.08 | 3658.77 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.202151 | 0.202151 | 0.202151 | 0.202151 | 3683.74 | 3683.74 | 3646.95 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.141026 | 0.141026 | 0.141026 | 0.141026 | 2746.45 | 2746.45 | 2506.44 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.139843 | 0.139843 | 0.139843 | 0.139843 | 2729.06 | 2729.06 | 2506.24 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.171177 | 0.171177 | 0.171177 | 0.171177 | 3223.29 | 3223.29 | 2495.81 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.173013 | 0.173013 | 0.173013 | 0.173013 | 3249.57 | 3249.57 | 2497.24 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.269956 | 0.269956 | 0.269956 | 0.269956 | 4745.97 | 4745.97 | 3752.68 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.252301 | 0.252301 | 0.252301 | 0.252301 | 4484.65 | 4484.65 | 3771.07 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.242014 | 0.242014 | 0.242014 | 0.242014 | 4360.41 | 4360.41 | 3744.32 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.205824 | 0.205824 | 0.205824 | 0.205824 | 3774.23 | 3774.23 | 3760.00 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.144857 | 0.144857 | 0.144857 | 0.144857 | 2827.92 | 2827.92 | 2542.78 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.143685 | 0.143685 | 0.143685 | 0.143685 | 2810.67 | 2810.67 | 2542.51 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.174343 | 0.174343 | 0.174343 | 0.174343 | 3291.60 | 3291.60 | 2524.92 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.175252 | 0.175252 | 0.175252 | 0.175252 | 3304.58 | 3304.58 | 2524.91 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.271115 | 0.271115 | 0.271115 | 0.271115 | 4792.77 | 4792.77 | 3881.77 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.253768 | 0.253768 | 0.253768 | 0.253768 | 4535.26 | 4535.26 | 3903.27 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.241975 | 0.241975 | 0.241975 | 0.241975 | 4389.02 | 4389.02 | 3869.33 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.207250 | 0.207250 | 0.207250 | 0.207250 | 3822.80 | 3822.80 | 3890.56 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.146631 | 0.146631 | 0.146631 | 0.146631 | 2869.82 | 2869.82 | 2613.22 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.145465 | 0.145465 | 0.145465 | 0.145465 | 2852.63 | 2852.63 | 2612.91 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.175637 | 0.175637 | 0.175637 | 0.175637 | 3327.31 | 3327.31 | 2591.91 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.176415 | 0.176415 | 0.176415 | 0.176415 | 3338.41 | 3338.41 | 2591.63 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.274326 | 0.274326 | 0.274326 | 0.274326 | 4863.38 | 4863.38 | 3972.30 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.257259 | 0.257259 | 0.257259 | 0.257259 | 4609.52 | 4609.52 | 3994.60 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.245225 | 0.245225 | 0.245225 | 0.245225 | 4459.56 | 4459.56 | 3958.41 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.210648 | 0.210648 | 0.210648 | 0.210648 | 3894.71 | 3894.71 | 3980.71 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.150192 | 0.150192 | 0.150192 | 0.150192 | 2935.01 | 2935.01 | 2655.58 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.149031 | 0.149031 | 0.149031 | 0.149031 | 2917.88 | 2917.88 | 2655.24 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.178816 | 0.178816 | 0.178816 | 0.178816 | 3387.14 | 3387.14 | 2633.35 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.179574 | 0.179574 | 0.179574 | 0.179574 | 3397.98 | 3397.98 | 2633.01 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.271251 | 0.271251 | 0.271251 | 0.271251 | 4840.00 | 4840.00 | 4118.06 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.254270 | 0.254270 | 0.254270 | 0.254270 | 4586.70 | 4586.70 | 4142.85 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.242364 | 0.242364 | 0.242364 | 0.242364 | 4438.28 | 4438.28 | 4103.24 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.207633 | 0.207633 | 0.207633 | 0.207633 | 3870.08 | 3870.08 | 4128.04 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.147522 | 0.147522 | 0.147522 | 0.147522 | 2906.80 | 2906.80 | 2759.51 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.146371 | 0.146371 | 0.146371 | 0.146371 | 2889.74 | 2889.74 | 2759.15 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.175815 | 0.175815 | 0.175815 | 0.175815 | 3355.49 | 3355.49 | 2734.78 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.176571 | 0.176571 | 0.176571 | 0.176571 | 3366.31 | 3366.31 | 2734.42 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.270451 | 0.270451 | 0.270451 | 0.270451 | 4846.66 | 4846.66 | 4228.09 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.253623 | 0.253623 | 0.253623 | 0.253623 | 4595.07 | 4595.07 | 4253.78 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.241741 | 0.241741 | 0.241741 | 0.241741 | 4446.74 | 4446.74 | 4212.53 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.206928 | 0.206928 | 0.206928 | 0.206928 | 3876.47 | 3876.47 | 4238.25 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.147050 | 0.147050 | 0.147050 | 0.147050 | 2909.40 | 2909.40 | 2832.78 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.145906 | 0.145906 | 0.145906 | 0.145906 | 2892.41 | 2892.41 | 2832.40 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.175029 | 0.175029 | 0.175029 | 0.175029 | 3354.36 | 3354.36 | 2807.12 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.175784 | 0.175784 | 0.175784 | 0.175784 | 3365.18 | 3365.18 | 2806.74 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.271006 | 0.271006 | 0.271006 | 0.271006 | 4870.89 | 4870.89 | 4336.25 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.254323 | 0.254323 | 0.254323 | 0.254323 | 4621.04 | 4621.04 | 4362.40 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.242382 | 0.242382 | 0.242382 | 0.242382 | 4471.64 | 4471.64 | 4320.08 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.207499 | 0.207499 | 0.207499 | 0.207499 | 3904.85 | 3904.85 | 4346.25 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.147885 | 0.147885 | 0.147885 | 0.147885 | 2930.30 | 2930.30 | 2907.78 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.146750 | 0.146750 | 0.146750 | 0.146750 | 2913.40 | 2913.40 | 2907.39 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.175541 | 0.175541 | 0.175541 | 0.175541 | 3371.00 | 3371.00 | 2881.67 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.176297 | 0.176297 | 0.176297 | 0.176297 | 3381.83 | 3381.83 | 2881.28 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.280285 | 0.280285 | 0.280285 | 0.280285 | 5019.77 | 5019.77 | 4564.31 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.263626 | 0.263626 | 0.263626 | 0.263626 | 4770.58 | 4770.58 | 4588.39 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.249538 | 0.249538 | 0.249538 | 0.249538 | 4590.06 | 4590.06 | 4547.48 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.212003 | 0.212003 | 0.212003 | 0.212003 | 3984.60 | 3984.60 | 4571.59 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.155959 | 0.155959 | 0.155959 | 0.155959 | 3057.48 | 3057.48 | 3094.43 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.154806 | 0.154806 | 0.154806 | 0.154806 | 3040.37 | 3040.37 | 3094.02 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.181631 | 0.181631 | 0.181631 | 0.181631 | 3468.35 | 3468.35 | 3069.94 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.182469 | 0.182469 | 0.182469 | 0.182469 | 3480.38 | 3480.38 | 3069.53 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.338757 | 0.338757 | 0.338757 | 0.338757 | 5890.43 | 5890.43 | 5224.09 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.313569 | 0.313569 | 0.313569 | 0.313569 | 5516.60 | 5516.60 | 5253.66 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.306246 | 0.306246 | 0.306246 | 0.306246 | 5422.47 | 5422.47 | 5208.19 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.258260 | 0.258260 | 0.258260 | 0.258260 | 4678.47 | 4678.47 | 5237.77 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.188108 | 0.188108 | 0.188108 | 0.188108 | 3574.10 | 3574.10 | 3792.68 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.187924 | 0.187924 | 0.187924 | 0.187924 | 3571.05 | 3571.05 | 3792.27 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.246701 | 0.246701 | 0.246701 | 0.246701 | 4414.82 | 4414.82 | 3759.72 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.247443 | 0.247443 | 0.247443 | 0.247443 | 4425.29 | 4425.29 | 3759.31 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.204826 |
AIRLOOP G NW SUPPLY FAN | 0.190760 |
AIRLOOP OFFICE SUPPLY FAN | 0.281549 |
AIRLOOP G NE SUPPLY FAN | 0.150540 |
AIRLOOP G N1 SUPPLY FAN | 0.102506 |
AIRLOOP G N2 SUPPLY FAN | 0.101105 |
AIRLOOP G S1 SUPPLY FAN | 0.127164 |
AIRLOOP G S2 SUPPLY FAN | 0.132062 |
AIRLOOP F2 SW SUPPLY FAN | 0.268465 |
AIRLOOP F2 NW SUPPLY FAN | 0.249762 |
AIRLOOP F2 SE SUPPLY FAN | 0.255228 |
AIRLOOP F2 NE SUPPLY FAN | 0.202151 |
AIRLOOP F2 N1 SUPPLY FAN | 0.141026 |
AIRLOOP F2 N2 SUPPLY FAN | 0.139843 |
AIRLOOP F2 S1 SUPPLY FAN | 0.171177 |
AIRLOOP F2 S2 SUPPLY FAN | 0.173013 |
AIRLOOP F3 SW SUPPLY FAN | 0.269956 |
AIRLOOP F3 NW SUPPLY FAN | 0.252301 |
AIRLOOP F3 SE SUPPLY FAN | 0.242014 |
AIRLOOP F3 NE SUPPLY FAN | 0.205824 |
AIRLOOP F3 N1 SUPPLY FAN | 0.144857 |
AIRLOOP F3 N2 SUPPLY FAN | 0.143685 |
AIRLOOP F3 S1 SUPPLY FAN | 0.174343 |
AIRLOOP F3 S2 SUPPLY FAN | 0.175252 |
AIRLOOP F4 SW SUPPLY FAN | 0.271115 |
AIRLOOP F4 NW SUPPLY FAN | 0.253768 |
AIRLOOP F4 SE SUPPLY FAN | 0.241975 |
AIRLOOP F4 NE SUPPLY FAN | 0.207250 |
AIRLOOP F4 N1 SUPPLY FAN | 0.146631 |
AIRLOOP F4 N2 SUPPLY FAN | 0.145465 |
AIRLOOP F4 S1 SUPPLY FAN | 0.175637 |
AIRLOOP F4 S2 SUPPLY FAN | 0.176415 |
AIRLOOP M SW SUPPLY FAN | 0.274326 |
AIRLOOP M NW SUPPLY FAN | 0.257259 |
AIRLOOP M SE SUPPLY FAN | 0.245225 |
AIRLOOP M NE SUPPLY FAN | 0.210648 |
AIRLOOP M N1 SUPPLY FAN | 0.150192 |
AIRLOOP M N2 SUPPLY FAN | 0.149031 |
AIRLOOP M S1 SUPPLY FAN | 0.178816 |
AIRLOOP M S2 SUPPLY FAN | 0.179574 |
AIRLOOP F6 SW SUPPLY FAN | 0.271251 |
AIRLOOP F6 NW SUPPLY FAN | 0.254270 |
AIRLOOP F6 SE SUPPLY FAN | 0.242364 |
AIRLOOP F6 NE SUPPLY FAN | 0.207633 |
AIRLOOP F6 N1 SUPPLY FAN | 0.147522 |
AIRLOOP F6 N2 SUPPLY FAN | 0.146371 |
AIRLOOP F6 S1 SUPPLY FAN | 0.175815 |
AIRLOOP F6 S2 SUPPLY FAN | 0.176571 |
AIRLOOP F7 SW SUPPLY FAN | 0.270451 |
AIRLOOP F7 NW SUPPLY FAN | 0.253623 |
AIRLOOP F7 SE SUPPLY FAN | 0.241741 |
AIRLOOP F7 NE SUPPLY FAN | 0.206928 |
AIRLOOP F7 N1 SUPPLY FAN | 0.147050 |
AIRLOOP F7 N2 SUPPLY FAN | 0.145906 |
AIRLOOP F7 S1 SUPPLY FAN | 0.175029 |
AIRLOOP F7 S2 SUPPLY FAN | 0.175784 |
AIRLOOP F8 SW SUPPLY FAN | 0.271006 |
AIRLOOP F8 NW SUPPLY FAN | 0.254323 |
AIRLOOP F8 SE SUPPLY FAN | 0.242382 |
AIRLOOP F8 NE SUPPLY FAN | 0.207499 |
AIRLOOP F8 N1 SUPPLY FAN | 0.147885 |
AIRLOOP F8 N2 SUPPLY FAN | 0.146750 |
AIRLOOP F8 S1 SUPPLY FAN | 0.175541 |
AIRLOOP F8 S2 SUPPLY FAN | 0.176297 |
AIRLOOP F9 SW SUPPLY FAN | 0.280285 |
AIRLOOP F9 NW SUPPLY FAN | 0.263626 |
AIRLOOP F9 SE SUPPLY FAN | 0.249538 |
AIRLOOP F9 NE SUPPLY FAN | 0.212003 |
AIRLOOP F9 N1 SUPPLY FAN | 0.155959 |
AIRLOOP F9 N2 SUPPLY FAN | 0.154806 |
AIRLOOP F9 S1 SUPPLY FAN | 0.181631 |
AIRLOOP F9 S2 SUPPLY FAN | 0.182469 |
AIRLOOP T SW SUPPLY FAN | 0.338757 |
AIRLOOP T NW SUPPLY FAN | 0.313569 |
AIRLOOP T SE SUPPLY FAN | 0.306246 |
AIRLOOP T NE SUPPLY FAN | 0.258260 |
AIRLOOP T N1 SUPPLY FAN | 0.188108 |
AIRLOOP T N2 SUPPLY FAN | 0.187924 |
AIRLOOP T S1 SUPPLY FAN | 0.246701 |
AIRLOOP T S2 SUPPLY FAN | 0.247443 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.204826 | 3710.95 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.190760 | 3496.34 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.281549 | 5045.40 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.150540 | 2874.95 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.102506 | 2146.32 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.101105 | 2125.39 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.127164 | 2550.83 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.132062 | 2620.20 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.268465 | 4684.07 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.249762 | 4408.57 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.255228 | 4510.08 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.202151 | 3683.74 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.141026 | 2746.45 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.139843 | 2729.06 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.171177 | 3223.29 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.173013 | 3249.57 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.269956 | 4745.97 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.252301 | 4484.65 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.242014 | 4360.41 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.205824 | 3774.23 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.144857 | 2827.92 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.143685 | 2810.67 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.174343 | 3291.60 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.175252 | 3304.58 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.271115 | 4792.77 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.253768 | 4535.26 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.241975 | 4389.02 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.207250 | 3822.80 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.146631 | 2869.82 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.145465 | 2852.63 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.175637 | 3327.31 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.176415 | 3338.41 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.274326 | 4863.38 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.257259 | 4609.52 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.245225 | 4459.56 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.210648 | 3894.71 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.150192 | 2935.01 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.149031 | 2917.88 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.178816 | 3387.14 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.179574 | 3397.98 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.271251 | 4840.00 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.254270 | 4586.70 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.242364 | 4438.28 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.207633 | 3870.08 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.147522 | 2906.80 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.146371 | 2889.74 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.175815 | 3355.49 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.176571 | 3366.31 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.270451 | 4846.66 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.253623 | 4595.07 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.241741 | 4446.74 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.206928 | 3876.47 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.147050 | 2909.40 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.145906 | 2892.41 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.175029 | 3354.36 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.175784 | 3365.18 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.271006 | 4870.89 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.254323 | 4621.04 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.242382 | 4471.64 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.207499 | 3904.85 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.147885 | 2930.30 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.146750 | 2913.40 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.175541 | 3371.00 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.176297 | 3381.83 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.280285 | 5019.77 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.263626 | 4770.58 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.249538 | 4590.06 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.212003 | 3984.60 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.155959 | 3057.48 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.154806 | 3040.37 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.181631 | 3468.35 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.182469 | 3480.38 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.338757 | 5890.43 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.313569 | 5516.60 | 0.000121 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.306246 | 5422.47 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.258260 | 4678.47 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.188108 | 3574.10 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.187924 | 3571.05 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.246701 | 4414.82 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.247443 | 4425.29 | 0.000097 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 3505.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 3515.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 4404.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 3511.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2607.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2607.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2593.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2602.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 3642.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 3655.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 3658.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 3646.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 2506.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 2506.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 2495.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 2497.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 3752.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 3771.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 3744.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 3760.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 2542.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 2542.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 2524.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 2524.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 3881.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 3903.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 3869.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 3890.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 2613.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 2612.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 2591.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 2591.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 3972.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 3994.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 3958.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 3980.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 2655.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 2655.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 2633.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 2633.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 4118.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 4142.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 4103.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 4128.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 2759.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 2759.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 2734.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 2734.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 4228.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 4253.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 4212.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 4238.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 2832.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 2832.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 2807.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 2806.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 4336.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 4362.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 4320.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 4346.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2907.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2907.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2881.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2881.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 4564.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 4588.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 4547.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 4571.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 3094.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 3094.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 3069.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 3069.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 5224.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 5253.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 5208.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 5237.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 3792.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 3792.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 3759.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 3759.31 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.006634 | 7.46 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.006634 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.006634 | 3202.70 | 8.43 | 9933.65 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.006634 | 1692.11 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 1.17 |
February | 21.85 | -0.2 |
March | 22.14 | 5.58 |
April | 22.64 | 10.94 |
May | 23.29 | 16.05 |
June | 24.26 | 21.71 |
July | 24.40 | 25.05 |
August | 24.39 | 24.79 |
September | 24.17 | 19.96 |
October | 23.47 | 14.02 |
November | 22.18 | 7.31 |
December | 21.87 | 3.33 |
Annual Sum or Average | 23.04 | 12.55 |
Minimum of Months | 21.78 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.80 | 5.58 |
April | 22.29 | 10.94 |
May | 23.18 | 16.05 |
June | 24.26 | 21.71 |
July | 24.40 | 25.05 |
August | 24.38 | 24.79 |
September | 24.06 | 19.96 |
October | 22.75 | 14.02 |
November | 21.81 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.84 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 1.17 |
February | 21.92 | -0.2 |
March | 22.25 | 5.58 |
April | 22.77 | 10.94 |
May | 23.61 | 16.05 |
June | 24.38 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.32 | 19.96 |
October | 23.57 | 14.02 |
November | 22.36 | 7.31 |
December | 21.99 | 3.33 |
Annual Sum or Average | 23.16 | 12.55 |
Minimum of Months | 21.89 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.76 | 5.58 |
April | 22.22 | 10.94 |
May | 23.10 | 16.05 |
June | 24.25 | 21.71 |
July | 24.40 | 25.05 |
August | 24.39 | 24.79 |
September | 24.04 | 19.96 |
October | 22.62 | 14.02 |
November | 21.79 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.81 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.74 | 5.58 |
April | 22.10 | 10.94 |
May | 22.92 | 16.05 |
June | 24.20 | 21.71 |
July | 24.41 | 25.05 |
August | 24.38 | 24.79 |
September | 23.99 | 19.96 |
October | 22.54 | 14.02 |
November | 21.79 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.77 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.74 | 5.58 |
April | 22.09 | 10.94 |
May | 22.91 | 16.05 |
June | 24.20 | 21.71 |
July | 24.41 | 25.05 |
August | 24.38 | 24.79 |
September | 23.99 | 19.96 |
October | 22.52 | 14.02 |
November | 21.79 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.77 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 1.17 |
February | 21.86 | -0.2 |
March | 22.13 | 5.58 |
April | 22.56 | 10.94 |
May | 23.16 | 16.05 |
June | 24.23 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.18 | 19.96 |
October | 23.52 | 14.02 |
November | 22.29 | 7.31 |
December | 21.92 | 3.33 |
Annual Sum or Average | 23.04 | 12.55 |
Minimum of Months | 21.80 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 1.17 |
February | 21.87 | -0.2 |
March | 22.15 | 5.58 |
April | 22.60 | 10.94 |
May | 23.20 | 16.05 |
June | 24.23 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.54 | 14.02 |
November | 22.32 | 7.31 |
December | 21.94 | 3.33 |
Annual Sum or Average | 23.06 | 12.55 |
Minimum of Months | 21.81 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.10 | 1.17 |
February | 16.93 | -0.2 |
March | 18.59 | 5.58 |
April | 20.33 | 10.94 |
May | 22.24 | 16.05 |
June | 24.79 | 21.71 |
July | 25.90 | 25.05 |
August | 25.95 | 24.79 |
September | 24.32 | 19.96 |
October | 21.78 | 14.02 |
November | 19.08 | 7.31 |
December | 17.75 | 3.33 |
Annual Sum or Average | 21.25 | 12.55 |
Minimum of Months | 16.93 | -0.2 |
Maximum of Months | 25.95 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 1.17 |
February | 22.00 | -0.2 |
March | 22.55 | 5.58 |
April | 23.34 | 10.94 |
May | 24.02 | 16.05 |
June | 24.34 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.28 | 19.96 |
October | 24.10 | 14.02 |
November | 22.60 | 7.31 |
December | 22.03 | 3.33 |
Annual Sum or Average | 23.33 | 12.55 |
Minimum of Months | 21.87 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.71 | -0.2 |
March | 21.94 | 5.58 |
April | 22.85 | 10.94 |
May | 23.91 | 16.05 |
June | 24.34 | 21.71 |
July | 24.40 | 25.05 |
August | 24.39 | 24.79 |
September | 24.18 | 19.96 |
October | 23.40 | 14.02 |
November | 21.99 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.05 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 1.17 |
February | 22.02 | -0.2 |
March | 22.57 | 5.58 |
April | 23.41 | 10.94 |
May | 24.09 | 16.05 |
June | 24.35 | 21.71 |
July | 24.40 | 25.05 |
August | 24.40 | 24.79 |
September | 24.30 | 19.96 |
October | 24.11 | 14.02 |
November | 22.68 | 7.31 |
December | 22.07 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.89 | -0.2 |
Maximum of Months | 24.40 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.88 | 5.58 |
April | 22.78 | 10.94 |
May | 23.88 | 16.05 |
June | 24.34 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.18 | 19.96 |
October | 23.25 | 14.02 |
November | 21.97 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.02 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.88 | 5.58 |
April | 22.69 | 10.94 |
May | 23.78 | 16.05 |
June | 24.31 | 21.71 |
July | 24.42 | 25.05 |
August | 24.40 | 24.79 |
September | 24.14 | 19.96 |
October | 23.24 | 14.02 |
November | 22.04 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.01 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.87 | 5.58 |
April | 22.68 | 10.94 |
May | 23.78 | 16.05 |
June | 24.31 | 21.71 |
July | 24.42 | 25.05 |
August | 24.40 | 24.79 |
September | 24.14 | 19.96 |
October | 23.22 | 14.02 |
November | 22.04 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.00 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 1.17 |
February | 22.12 | -0.2 |
March | 22.69 | 5.58 |
April | 23.39 | 10.94 |
May | 23.96 | 16.05 |
June | 24.31 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.29 | 19.96 |
October | 24.15 | 14.02 |
November | 22.86 | 7.31 |
December | 22.23 | 3.33 |
Annual Sum or Average | 23.41 | 12.55 |
Minimum of Months | 21.97 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 1.17 |
February | 22.13 | -0.2 |
March | 22.70 | 5.58 |
April | 23.40 | 10.94 |
May | 23.97 | 16.05 |
June | 24.32 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.29 | 19.96 |
October | 24.15 | 14.02 |
November | 22.87 | 7.31 |
December | 22.24 | 3.33 |
Annual Sum or Average | 23.41 | 12.55 |
Minimum of Months | 21.98 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.90 | -0.2 |
March | 22.82 | 5.58 |
April | 23.95 | 10.94 |
May | 25.24 | 16.05 |
June | 26.29 | 21.71 |
July | 26.64 | 25.05 |
August | 26.68 | 24.79 |
September | 26.04 | 19.96 |
October | 24.97 | 14.02 |
November | 22.93 | 7.31 |
December | 22.05 | 3.33 |
Annual Sum or Average | 24.28 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 26.68 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 1.17 |
February | 22.02 | -0.2 |
March | 22.62 | 5.58 |
April | 23.45 | 10.94 |
May | 24.10 | 16.05 |
June | 24.34 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.29 | 19.96 |
October | 24.14 | 14.02 |
November | 22.67 | 7.31 |
December | 22.06 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.88 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.71 | -0.2 |
March | 21.98 | 5.58 |
April | 22.98 | 10.94 |
May | 24.03 | 16.05 |
June | 24.33 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.19 | 19.96 |
October | 23.52 | 14.02 |
November | 22.05 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.09 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 1.17 |
February | 22.01 | -0.2 |
March | 22.58 | 5.58 |
April | 23.45 | 10.94 |
May | 24.12 | 16.05 |
June | 24.34 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.30 | 19.96 |
October | 24.12 | 14.02 |
November | 22.69 | 7.31 |
December | 22.06 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.87 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.91 | 5.58 |
April | 22.91 | 10.94 |
May | 24.00 | 16.05 |
June | 24.34 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.38 | 14.02 |
November | 22.02 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.06 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.94 | 5.58 |
April | 22.89 | 10.94 |
May | 23.95 | 16.05 |
June | 24.31 | 21.71 |
July | 24.43 | 25.05 |
August | 24.40 | 24.79 |
September | 24.15 | 19.96 |
October | 23.43 | 14.02 |
November | 22.15 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.07 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.93 | 5.58 |
April | 22.88 | 10.94 |
May | 23.95 | 16.05 |
June | 24.31 | 21.71 |
July | 24.43 | 25.05 |
August | 24.40 | 24.79 |
September | 24.15 | 19.96 |
October | 23.41 | 14.02 |
November | 22.15 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.07 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.20 | -0.2 |
March | 22.85 | 5.58 |
April | 23.57 | 10.94 |
May | 24.07 | 16.05 |
June | 24.31 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.30 | 19.96 |
October | 24.20 | 14.02 |
November | 22.99 | 7.31 |
December | 22.31 | 3.33 |
Annual Sum or Average | 23.48 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.21 | -0.2 |
March | 22.85 | 5.58 |
April | 23.57 | 10.94 |
May | 24.08 | 16.05 |
June | 24.32 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.30 | 19.96 |
October | 24.20 | 14.02 |
November | 22.99 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.48 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 1.17 |
February | 22.35 | -0.2 |
March | 23.26 | 5.58 |
April | 24.43 | 10.94 |
May | 25.70 | 16.05 |
June | 26.45 | 21.71 |
July | 26.75 | 25.05 |
August | 26.78 | 24.79 |
September | 26.20 | 19.96 |
October | 25.38 | 14.02 |
November | 23.34 | 7.31 |
December | 22.44 | 3.33 |
Annual Sum or Average | 24.61 | 12.55 |
Minimum of Months | 22.10 | -0.2 |
Maximum of Months | 26.78 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 1.17 |
February | 22.01 | -0.2 |
March | 22.60 | 5.58 |
April | 23.46 | 10.94 |
May | 24.14 | 16.05 |
June | 24.33 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 24.13 | 14.02 |
November | 22.67 | 7.31 |
December | 22.05 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.87 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 1.17 |
February | 21.71 | -0.2 |
March | 21.98 | 5.58 |
April | 22.99 | 10.94 |
May | 24.07 | 16.05 |
June | 24.33 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.22 | 19.96 |
October | 23.54 | 14.02 |
November | 22.07 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 1.17 |
February | 21.99 | -0.2 |
March | 22.55 | 5.58 |
April | 23.45 | 10.94 |
May | 24.14 | 16.05 |
June | 24.33 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.31 | 19.96 |
October | 24.11 | 14.02 |
November | 22.67 | 7.31 |
December | 22.04 | 3.33 |
Annual Sum or Average | 23.36 | 12.55 |
Minimum of Months | 21.85 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.91 | 5.58 |
April | 22.93 | 10.94 |
May | 24.05 | 16.05 |
June | 24.33 | 21.71 |
July | 24.42 | 25.05 |
August | 24.40 | 24.79 |
September | 24.22 | 19.96 |
October | 23.40 | 14.02 |
November | 22.04 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.07 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.96 | 5.58 |
April | 22.95 | 10.94 |
May | 24.02 | 16.05 |
June | 24.31 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.49 | 14.02 |
November | 22.19 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.95 | 5.58 |
April | 22.94 | 10.94 |
May | 24.02 | 16.05 |
June | 24.31 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.47 | 14.02 |
November | 22.19 | 7.31 |
December | 21.71 | 3.33 |
Annual Sum or Average | 23.09 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.21 | -0.2 |
March | 22.87 | 5.58 |
April | 23.61 | 10.94 |
May | 24.12 | 16.05 |
June | 24.31 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.32 | 19.96 |
October | 24.20 | 14.02 |
November | 23.00 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.49 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.21 | -0.2 |
March | 22.87 | 5.58 |
April | 23.61 | 10.94 |
May | 24.12 | 16.05 |
June | 24.31 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.32 | 19.96 |
October | 24.20 | 14.02 |
November | 23.01 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.49 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 1.17 |
February | 22.49 | -0.2 |
March | 23.40 | 5.58 |
April | 24.60 | 10.94 |
May | 25.89 | 16.05 |
June | 26.54 | 21.71 |
July | 26.84 | 25.05 |
August | 26.87 | 24.79 |
September | 26.31 | 19.96 |
October | 25.53 | 14.02 |
November | 23.49 | 7.31 |
December | 22.57 | 3.33 |
Annual Sum or Average | 24.74 | 12.55 |
Minimum of Months | 22.23 | -0.2 |
Maximum of Months | 26.87 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 1.17 |
February | 22.00 | -0.2 |
March | 22.58 | 5.58 |
April | 23.44 | 10.94 |
May | 24.13 | 16.05 |
June | 24.32 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.31 | 19.96 |
October | 24.12 | 14.02 |
November | 22.66 | 7.31 |
December | 22.04 | 3.33 |
Annual Sum or Average | 23.36 | 12.55 |
Minimum of Months | 21.86 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 1.17 |
February | 21.71 | -0.2 |
March | 21.97 | 5.58 |
April | 22.98 | 10.94 |
May | 24.07 | 16.05 |
June | 24.32 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.22 | 19.96 |
October | 23.52 | 14.02 |
November | 22.07 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 1.17 |
February | 21.98 | -0.2 |
March | 22.53 | 5.58 |
April | 23.43 | 10.94 |
May | 24.13 | 16.05 |
June | 24.32 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.31 | 19.96 |
October | 24.10 | 14.02 |
November | 22.66 | 7.31 |
December | 22.03 | 3.33 |
Annual Sum or Average | 23.35 | 12.55 |
Minimum of Months | 21.85 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.91 | 5.58 |
April | 22.92 | 10.94 |
May | 24.05 | 16.05 |
June | 24.32 | 21.71 |
July | 24.42 | 25.05 |
August | 24.40 | 24.79 |
September | 24.22 | 19.96 |
October | 23.39 | 14.02 |
November | 22.04 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.07 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.97 | 5.58 |
April | 22.96 | 10.94 |
May | 24.03 | 16.05 |
June | 24.30 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.49 | 14.02 |
November | 22.21 | 7.31 |
December | 21.71 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.97 | 5.58 |
April | 22.95 | 10.94 |
May | 24.03 | 16.05 |
June | 24.30 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.19 | 19.96 |
October | 23.48 | 14.02 |
November | 22.21 | 7.31 |
December | 21.71 | 3.33 |
Annual Sum or Average | 23.10 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.21 | -0.2 |
March | 22.87 | 5.58 |
April | 23.61 | 10.94 |
May | 24.12 | 16.05 |
June | 24.30 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.32 | 19.96 |
October | 24.19 | 14.02 |
November | 23.00 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.49 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.21 | -0.2 |
March | 22.86 | 5.58 |
April | 23.61 | 10.94 |
May | 24.12 | 16.05 |
June | 24.30 | 21.71 |
July | 24.42 | 25.05 |
August | 24.42 | 24.79 |
September | 24.32 | 19.96 |
October | 24.19 | 14.02 |
November | 23.01 | 7.31 |
December | 22.32 | 3.33 |
Annual Sum or Average | 23.49 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 1.17 |
February | 23.12 | -0.2 |
March | 24.03 | 5.58 |
April | 25.22 | 10.94 |
May | 26.51 | 16.05 |
June | 27.13 | 21.71 |
July | 27.44 | 25.05 |
August | 27.47 | 24.79 |
September | 26.92 | 19.96 |
October | 26.13 | 14.02 |
November | 24.12 | 7.31 |
December | 23.21 | 3.33 |
Annual Sum or Average | 25.36 | 12.55 |
Minimum of Months | 22.88 | -0.2 |
Maximum of Months | 27.47 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 1.17 |
February | 21.96 | -0.2 |
March | 22.49 | 5.58 |
April | 23.36 | 10.94 |
May | 24.07 | 16.05 |
June | 24.30 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.29 | 19.96 |
October | 24.06 | 14.02 |
November | 22.59 | 7.31 |
December | 21.99 | 3.33 |
Annual Sum or Average | 23.32 | 12.55 |
Minimum of Months | 21.84 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.93 | 5.58 |
April | 22.88 | 10.94 |
May | 24.00 | 16.05 |
June | 24.30 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.19 | 19.96 |
October | 23.40 | 14.02 |
November | 22.01 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.06 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 1.17 |
February | 21.94 | -0.2 |
March | 22.44 | 5.58 |
April | 23.34 | 10.94 |
May | 24.08 | 16.05 |
June | 24.30 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.30 | 19.96 |
October | 24.04 | 14.02 |
November | 22.59 | 7.31 |
December | 21.99 | 3.33 |
Annual Sum or Average | 23.31 | 12.55 |
Minimum of Months | 21.82 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.87 | 5.58 |
April | 22.81 | 10.94 |
May | 23.98 | 16.05 |
June | 24.30 | 21.71 |
July | 24.42 | 25.05 |
August | 24.40 | 24.79 |
September | 24.18 | 19.96 |
October | 23.26 | 14.02 |
November | 21.98 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.03 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.92 | 5.58 |
April | 22.84 | 10.94 |
May | 23.96 | 16.05 |
June | 24.28 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.16 | 19.96 |
October | 23.36 | 14.02 |
November | 22.13 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.06 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.91 | 5.58 |
April | 22.83 | 10.94 |
May | 23.96 | 16.05 |
June | 24.28 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.16 | 19.96 |
October | 23.34 | 14.02 |
November | 22.13 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.05 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 1.17 |
February | 22.15 | -0.2 |
March | 22.76 | 5.58 |
April | 23.52 | 10.94 |
May | 24.07 | 16.05 |
June | 24.28 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.30 | 19.96 |
October | 24.15 | 14.02 |
November | 22.92 | 7.31 |
December | 22.25 | 3.33 |
Annual Sum or Average | 23.44 | 12.55 |
Minimum of Months | 21.98 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 1.17 |
February | 22.15 | -0.2 |
March | 22.76 | 5.58 |
April | 23.52 | 10.94 |
May | 24.07 | 16.05 |
June | 24.28 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.30 | 19.96 |
October | 24.15 | 14.02 |
November | 22.92 | 7.31 |
December | 22.26 | 3.33 |
Annual Sum or Average | 23.44 | 12.55 |
Minimum of Months | 21.98 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 1.17 |
February | 22.42 | -0.2 |
March | 23.31 | 5.58 |
April | 24.49 | 10.94 |
May | 25.84 | 16.05 |
June | 26.50 | 21.71 |
July | 26.84 | 25.05 |
August | 26.86 | 24.79 |
September | 26.28 | 19.96 |
October | 25.43 | 14.02 |
November | 23.40 | 7.31 |
December | 22.50 | 3.33 |
Annual Sum or Average | 24.68 | 12.55 |
Minimum of Months | 22.17 | -0.2 |
Maximum of Months | 26.86 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 1.17 |
February | 21.94 | -0.2 |
March | 22.43 | 5.58 |
April | 23.28 | 10.94 |
May | 24.03 | 16.05 |
June | 24.29 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.28 | 19.96 |
October | 24.02 | 14.02 |
November | 22.53 | 7.31 |
December | 21.96 | 3.33 |
Annual Sum or Average | 23.29 | 12.55 |
Minimum of Months | 21.82 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.90 | 5.58 |
April | 22.80 | 10.94 |
May | 23.95 | 16.05 |
June | 24.29 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.17 | 19.96 |
October | 23.30 | 14.02 |
November | 21.97 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.03 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 1.17 |
February | 21.92 | -0.2 |
March | 22.38 | 5.58 |
April | 23.27 | 10.94 |
May | 24.03 | 16.05 |
June | 24.29 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.28 | 19.96 |
October | 23.99 | 14.02 |
November | 22.53 | 7.31 |
December | 21.96 | 3.33 |
Annual Sum or Average | 23.28 | 12.55 |
Minimum of Months | 21.81 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.84 | 5.58 |
April | 22.74 | 10.94 |
May | 23.93 | 16.05 |
June | 24.29 | 21.71 |
July | 24.42 | 25.05 |
August | 24.39 | 24.79 |
September | 24.16 | 19.96 |
October | 23.16 | 14.02 |
November | 21.94 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.01 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.89 | 5.58 |
April | 22.75 | 10.94 |
May | 23.91 | 16.05 |
June | 24.26 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.13 | 19.96 |
October | 23.25 | 14.02 |
November | 22.08 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.03 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.88 | 5.58 |
April | 22.74 | 10.94 |
May | 23.91 | 16.05 |
June | 24.26 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.13 | 19.96 |
October | 23.23 | 14.02 |
November | 22.08 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.02 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 1.17 |
February | 22.10 | -0.2 |
March | 22.68 | 5.58 |
April | 23.44 | 10.94 |
May | 24.03 | 16.05 |
June | 24.26 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.29 | 19.96 |
October | 24.12 | 14.02 |
November | 22.85 | 7.31 |
December | 22.21 | 3.33 |
Annual Sum or Average | 23.40 | 12.55 |
Minimum of Months | 21.94 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 1.17 |
February | 22.10 | -0.2 |
March | 22.68 | 5.58 |
April | 23.44 | 10.94 |
May | 24.03 | 16.05 |
June | 24.26 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.29 | 19.96 |
October | 24.11 | 14.02 |
November | 22.86 | 7.31 |
December | 22.21 | 3.33 |
Annual Sum or Average | 23.40 | 12.55 |
Minimum of Months | 21.95 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 1.17 |
February | 22.26 | -0.2 |
March | 23.13 | 5.58 |
April | 24.31 | 10.94 |
May | 25.69 | 16.05 |
June | 26.40 | 21.71 |
July | 26.76 | 25.05 |
August | 26.78 | 24.79 |
September | 26.17 | 19.96 |
October | 25.26 | 14.02 |
November | 23.22 | 7.31 |
December | 22.35 | 3.33 |
Annual Sum or Average | 24.54 | 12.55 |
Minimum of Months | 22.02 | -0.2 |
Maximum of Months | 26.78 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 1.17 |
February | 21.91 | -0.2 |
March | 22.37 | 5.58 |
April | 23.22 | 10.94 |
May | 23.99 | 16.05 |
June | 24.28 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.26 | 19.96 |
October | 23.97 | 14.02 |
November | 22.48 | 7.31 |
December | 21.94 | 3.33 |
Annual Sum or Average | 23.26 | 12.55 |
Minimum of Months | 21.81 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.88 | 5.58 |
April | 22.74 | 10.94 |
May | 23.91 | 16.05 |
June | 24.28 | 21.71 |
July | 24.41 | 25.05 |
August | 24.38 | 24.79 |
September | 24.15 | 19.96 |
October | 23.22 | 14.02 |
November | 21.94 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.01 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 1.17 |
February | 21.90 | -0.2 |
March | 22.34 | 5.58 |
April | 23.20 | 10.94 |
May | 23.99 | 16.05 |
June | 24.28 | 21.71 |
July | 24.41 | 25.05 |
August | 24.41 | 24.79 |
September | 24.27 | 19.96 |
October | 23.94 | 14.02 |
November | 22.48 | 7.31 |
December | 21.93 | 3.33 |
Annual Sum or Average | 23.25 | 12.55 |
Minimum of Months | 21.80 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.83 | 5.58 |
April | 22.67 | 10.94 |
May | 23.87 | 16.05 |
June | 24.28 | 21.71 |
July | 24.42 | 25.05 |
August | 24.39 | 24.79 |
September | 24.13 | 19.96 |
October | 23.08 | 14.02 |
November | 21.91 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.98 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.87 | 5.58 |
April | 22.68 | 10.94 |
May | 23.87 | 16.05 |
June | 24.25 | 21.71 |
July | 24.44 | 25.05 |
August | 24.39 | 24.79 |
September | 24.11 | 19.96 |
October | 23.16 | 14.02 |
November | 22.03 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.00 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.86 | 5.58 |
April | 22.68 | 10.94 |
May | 23.86 | 16.05 |
June | 24.25 | 21.71 |
July | 24.44 | 25.05 |
August | 24.40 | 24.79 |
September | 24.11 | 19.96 |
October | 23.14 | 14.02 |
November | 22.03 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 23.00 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 1.17 |
February | 22.06 | -0.2 |
March | 22.61 | 5.58 |
April | 23.36 | 10.94 |
May | 23.99 | 16.05 |
June | 24.25 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.27 | 19.96 |
October | 24.08 | 14.02 |
November | 22.79 | 7.31 |
December | 22.16 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.92 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 1.17 |
February | 22.06 | -0.2 |
March | 22.61 | 5.58 |
April | 23.36 | 10.94 |
May | 23.99 | 16.05 |
June | 24.25 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.28 | 19.96 |
October | 24.08 | 14.02 |
November | 22.79 | 7.31 |
December | 22.16 | 3.33 |
Annual Sum or Average | 23.37 | 12.55 |
Minimum of Months | 21.92 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 1.17 |
February | 22.16 | -0.2 |
March | 23.03 | 5.58 |
April | 24.20 | 10.94 |
May | 25.62 | 16.05 |
June | 26.38 | 21.71 |
July | 26.76 | 25.05 |
August | 26.78 | 24.79 |
September | 26.14 | 19.96 |
October | 25.16 | 14.02 |
November | 23.11 | 7.31 |
December | 22.25 | 3.33 |
Annual Sum or Average | 24.47 | 12.55 |
Minimum of Months | 21.93 | -0.2 |
Maximum of Months | 26.78 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 1.17 |
February | 21.89 | -0.2 |
March | 22.31 | 5.58 |
April | 23.14 | 10.94 |
May | 23.94 | 16.05 |
June | 24.27 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.25 | 19.96 |
October | 23.89 | 14.02 |
November | 22.41 | 7.31 |
December | 21.90 | 3.33 |
Annual Sum or Average | 23.22 | 12.55 |
Minimum of Months | 21.79 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.86 | 5.58 |
April | 22.69 | 10.94 |
May | 23.85 | 16.05 |
June | 24.27 | 21.71 |
July | 24.41 | 25.05 |
August | 24.38 | 24.79 |
September | 24.12 | 19.96 |
October | 23.13 | 14.02 |
November | 21.91 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.99 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 1.17 |
February | 21.88 | -0.2 |
March | 22.28 | 5.58 |
April | 23.13 | 10.94 |
May | 23.93 | 16.05 |
June | 24.27 | 21.71 |
July | 24.41 | 25.05 |
August | 24.40 | 24.79 |
September | 24.25 | 19.96 |
October | 23.85 | 14.02 |
November | 22.41 | 7.31 |
December | 21.90 | 3.33 |
Annual Sum or Average | 23.22 | 12.55 |
Minimum of Months | 21.79 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.81 | 5.58 |
April | 22.62 | 10.94 |
May | 23.81 | 16.05 |
June | 24.27 | 21.71 |
July | 24.42 | 25.05 |
August | 24.39 | 24.79 |
September | 24.10 | 19.96 |
October | 22.99 | 14.02 |
November | 21.88 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.96 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.85 | 5.58 |
April | 22.63 | 10.94 |
May | 23.82 | 16.05 |
June | 24.24 | 21.71 |
July | 24.44 | 25.05 |
August | 24.39 | 24.79 |
September | 24.08 | 19.96 |
October | 23.06 | 14.02 |
November | 21.97 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.97 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.84 | 5.58 |
April | 22.62 | 10.94 |
May | 23.81 | 16.05 |
June | 24.24 | 21.71 |
July | 24.44 | 25.05 |
August | 24.39 | 24.79 |
September | 24.08 | 19.96 |
October | 23.04 | 14.02 |
November | 21.97 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.97 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 1.17 |
February | 22.00 | -0.2 |
March | 22.51 | 5.58 |
April | 23.26 | 10.94 |
May | 23.94 | 16.05 |
June | 24.24 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.26 | 19.96 |
October | 24.01 | 14.02 |
November | 22.68 | 7.31 |
December | 22.09 | 3.33 |
Annual Sum or Average | 23.32 | 12.55 |
Minimum of Months | 21.88 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 1.17 |
February | 22.01 | -0.2 |
March | 22.50 | 5.58 |
April | 23.27 | 10.94 |
May | 23.95 | 16.05 |
June | 24.24 | 21.71 |
July | 24.43 | 25.05 |
August | 24.42 | 24.79 |
September | 24.26 | 19.96 |
October | 24.01 | 14.02 |
November | 22.68 | 7.31 |
December | 22.09 | 3.33 |
Annual Sum or Average | 23.32 | 12.55 |
Minimum of Months | 21.88 | -0.2 |
Maximum of Months | 24.43 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 1.17 |
February | 21.98 | -0.2 |
March | 22.89 | 5.58 |
April | 24.09 | 10.94 |
May | 25.57 | 16.05 |
June | 26.42 | 21.71 |
July | 26.85 | 25.05 |
August | 26.86 | 24.79 |
September | 26.14 | 19.96 |
October | 25.03 | 14.02 |
November | 22.93 | 7.31 |
December | 22.08 | 3.33 |
Annual Sum or Average | 24.40 | 12.55 |
Minimum of Months | 21.76 | -0.2 |
Maximum of Months | 26.86 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 1.17 |
February | 21.92 | -0.2 |
March | 22.24 | 5.58 |
April | 22.96 | 10.94 |
May | 23.75 | 16.05 |
June | 24.22 | 21.71 |
July | 24.41 | 25.05 |
August | 24.38 | 24.79 |
September | 24.15 | 19.96 |
October | 23.52 | 14.02 |
November | 22.29 | 7.31 |
December | 21.91 | 3.33 |
Annual Sum or Average | 23.14 | 12.55 |
Minimum of Months | 21.82 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 1.17 |
February | 21.71 | -0.2 |
March | 21.92 | 5.58 |
April | 22.66 | 10.94 |
May | 23.67 | 16.05 |
June | 24.22 | 21.71 |
July | 24.41 | 25.05 |
August | 24.37 | 24.79 |
September | 24.01 | 19.96 |
October | 22.95 | 14.02 |
November | 21.90 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.94 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 1.17 |
February | 21.91 | -0.2 |
March | 22.22 | 5.58 |
April | 22.96 | 10.94 |
May | 23.74 | 16.05 |
June | 24.22 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.15 | 19.96 |
October | 23.48 | 14.02 |
November | 22.30 | 7.31 |
December | 21.90 | 3.33 |
Annual Sum or Average | 23.13 | 12.55 |
Minimum of Months | 21.81 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.88 | 5.58 |
April | 22.59 | 10.94 |
May | 23.62 | 16.05 |
June | 24.21 | 21.71 |
July | 24.42 | 25.05 |
August | 24.37 | 24.79 |
September | 23.99 | 19.96 |
October | 22.83 | 14.02 |
November | 21.87 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.91 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.42 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.87 | 5.58 |
April | 22.57 | 10.94 |
May | 23.64 | 16.05 |
June | 24.20 | 21.71 |
July | 24.44 | 25.05 |
August | 24.37 | 24.79 |
September | 23.98 | 19.96 |
October | 22.86 | 14.02 |
November | 21.91 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.92 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 1.17 |
February | 21.70 | -0.2 |
March | 21.87 | 5.58 |
April | 22.56 | 10.94 |
May | 23.63 | 16.05 |
June | 24.20 | 21.71 |
July | 24.44 | 25.05 |
August | 24.37 | 24.79 |
September | 23.97 | 19.96 |
October | 22.84 | 14.02 |
November | 21.91 | 7.31 |
December | 21.70 | 3.33 |
Annual Sum or Average | 22.92 | 12.55 |
Minimum of Months | 21.70 | -0.2 |
Maximum of Months | 24.44 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 1.17 |
February | 21.99 | -0.2 |
March | 22.35 | 5.58 |
April | 23.07 | 10.94 |
May | 23.80 | 16.05 |
June | 24.19 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.18 | 19.96 |
October | 23.65 | 14.02 |
November | 22.48 | 7.31 |
December | 22.01 | 3.33 |
Annual Sum or Average | 23.21 | 12.55 |
Minimum of Months | 21.88 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 1.17 |
February | 21.99 | -0.2 |
March | 22.35 | 5.58 |
April | 23.07 | 10.94 |
May | 23.80 | 16.05 |
June | 24.19 | 21.71 |
July | 24.41 | 25.05 |
August | 24.39 | 24.79 |
September | 24.18 | 19.96 |
October | 23.65 | 14.02 |
November | 22.48 | 7.31 |
December | 22.01 | 3.33 |
Annual Sum or Average | 23.21 | 12.55 |
Minimum of Months | 21.88 | -0.2 |
Maximum of Months | 24.41 | 25.05 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:08
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 1.17 |
February | 21.83 | -0.2 |
March | 22.98 | 5.58 |
April | 24.34 | 10.94 |
May | 26.01 | 16.05 |
June | 27.13 | 21.71 |
July | 27.71 | 25.05 |
August | 27.68 | 24.79 |
September | 26.68 | 19.96 |
October | 25.21 | 14.02 |
November | 22.94 | 7.31 |
December | 21.98 | 3.33 |
Annual Sum or Average | 24.69 | 12.55 |
Minimum of Months | 21.64 | -0.2 |
Maximum of Months | 27.71 | 25.05 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.253990E+12 | 151347.878 | 14-JAN-17:15 | 18221.747 | 56867.515 | 18358.633 | 44305.431 | 0.000 | 10720.100 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.226323E+12 | 150509.533 | 05-FEB-18:00 | 22204.399 | 56867.515 | 18358.633 | 39483.965 | 0.000 | 10720.100 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.222642E+12 | 135988.801 | 16-MAR-17:00 | 22204.399 | 56867.515 | 18358.633 | 24963.233 | 0.000 | 10720.100 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.205176E+12 | 148653.236 | 07-APR-16:30 | 18221.747 | 56933.809 | 18358.633 | 0.000 | 50364.571 | 0.000 | 1729.033 | 1897.001 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.223156E+12 | 163576.837 | 30-MAY-16:45 | 18221.747 | 56933.809 | 18358.633 | 0.000 | 64870.765 | 0.000 | 1729.033 | 2314.408 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.271657E+12 | 181381.135 | 15-JUN-17:15 | 22204.399 | 56867.515 | 18358.633 | 0.000 | 78012.824 | 0.000 | 1729.033 | 3063.095 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.344648E+12 | 187323.824 | 21-JUL-19:30 | 25049.151 | 49704.829 | 18358.633 | 0.000 | 77752.399 | 10720.100 | 1729.033 | 3064.108 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.331383E+12 | 189190.543 | 03-AUG-19:00 | 25049.151 | 49704.829 | 18358.633 | 0.000 | 79480.526 | 10720.100 | 1729.033 | 3202.700 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.256360E+12 | 184561.242 | 07-SEP-18:30 | 25049.151 | 51564.864 | 18358.633 | 0.000 | 73224.314 | 10720.100 | 1729.033 | 2900.533 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.222771E+12 | 147955.880 | 04-OCT-16:15 | 18221.747 | 56933.809 | 18358.633 | 0.000 | 49412.560 | 0.000 | 1729.033 | 2151.794 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.217666E+12 | 132649.618 | 22-NOV-18:00 | 22204.399 | 56867.515 | 18358.633 | 21624.050 | 0.000 | 10720.100 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.242745E+12 | 142205.703 | 31-DEC-20:00 | 25049.151 | 49704.829 | 18358.633 | 35698.385 | 0.000 | 10720.100 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.301852E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.205176E+12 | 132649.618 | 18221.747 | 49704.829 | 18358.633 | 0.000 | 0.000 | 0.000 | 1729.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.344648E+12 | 189190.543 | 25049.151 | 56933.809 | 18358.633 | 44305.431 | 79480.526 | 10720.100 | 1729.033 | 3202.700 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:08
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.284179E+12 | 259740.247 | 14-JAN-07:00 | 0.000 | 0.000 | 0.000 | 259740.247 | 87684.615 | 87684.615 | 172055.632 |
February | 0.250981E+12 | 290801.533 | 06-FEB-06:00 | 0.000 | 0.000 | 0.000 | 290801.533 | 85551.827 | 85551.827 | 205249.706 |
March | 0.166868E+12 | 211532.947 | 22-MAR-06:00 | 0.000 | 0.000 | 0.000 | 211532.947 | 86907.799 | 86907.799 | 124625.148 |
April | 0.111841E+12 | 141329.760 | 02-APR-05:00 | 0.000 | 0.000 | 0.000 | 141329.760 | 83868.477 | 83868.477 | 57461.282 |
May | 0.953906E+11 | 84031.199 | 01-MAY-06:00 | 0.000 | 0.000 | 0.000 | 84031.199 | 84031.199 | 84031.199 | 0.000 |
June | 0.857857E+11 | 81477.150 | 03-JUN-06:45 | 0.000 | 0.000 | 0.000 | 81477.150 | 81477.150 | 81477.150 | 0.000 |
July | 0.840224E+11 | 79781.192 | 02-JUL-06:45 | 0.000 | 0.000 | 0.000 | 79781.192 | 79781.192 | 79781.192 | 0.000 |
August | 0.828628E+11 | 79156.813 | 31-AUG-06:00 | 0.000 | 0.000 | 0.000 | 79156.813 | 79156.813 | 79156.813 | 0.000 |
September | 0.826319E+11 | 80388.411 | 30-SEP-06:45 | 0.000 | 0.000 | 0.000 | 80388.411 | 80388.411 | 80388.411 | 0.000 |
October | 0.910307E+11 | 92185.516 | 28-OCT-07:00 | 0.000 | 0.000 | 0.000 | 92185.516 | 81133.433 | 81133.433 | 11052.083 |
November | 0.149530E+12 | 196215.956 | 22-NOV-06:45 | 0.000 | 0.000 | 0.000 | 196215.956 | 78010.031 | 78010.031 | 118205.926 |
December | 0.230055E+12 | 235060.403 | 31-DEC-21:00 | 0.000 | 0.000 | 0.000 | 235060.403 | 64385.740 | 64385.740 | 170674.663 |
Annual Sum or Average | 0.171518E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.826319E+11 | 79156.813 | 0.000 | 0.000 | 0.000 | 79156.813 | 64385.740 | 64385.740 | 0.000 | |
Maximum of Months | 0.284179E+12 | 290801.533 | 0.000 | 0.000 | 0.000 | 290801.533 | 87684.615 | 87684.615 | 205249.706 |