Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2018-10-19 09:40:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 5990.32 764.41 848.50
Net Site Energy 5990.32 764.41 848.50
Total Source Energy 13022.27 1661.75 1844.54
Net Source Energy 13022.27 1661.75 1844.54


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 425.54 1560.29 0.00 0.00 0.00 0.00
Cooling 296.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.36 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 606.47 0.00 0.00 0.00 0.00 0.00
Pumps 55.66 0.00 0.00 0.00 0.00 0.00
Heat Rejection 13.06 0.00 0.00 0.00 0.00 810.48
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1295.71 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3134.31 2856.00 0.00 0.00 0.00 5588.99
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 1560.29 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 425.54 0.00 0.00 0.00 0.00 0.00
Cooling General 296.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.36 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 606.47 0.00 0.00 0.00 0.00 0.00
Pumps General 55.66 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 13.06 0.00 0.00 0.00 0.00 810.48
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1295.71 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.83 0.00 0.00 0.00 0.00 0.00
HVAC 197.97 404.54 0.00 0.00 0.00 0.79
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 443.96 404.54 0.00 0.00 0.00 0.79


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.62 0.00 0.00 0.00 0.00 0.00
HVAC 178.35 364.45 0.00 0.00 0.00 0.71
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 399.96 364.45 0.00 0.00 0.00 0.71


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3134.31 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3134.31 100.00
     
Total On-Site and Utility Electric Sources 3134.31 100.00
Total Electricity End Uses 3134.31 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5588.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5588.99 100.00
Total Water End Uses 5588.99 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 123.25
Time Setpoint Not Met During Occupied Cooling 73.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 3838.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Rochester International Arpt MN USA TMY3 WMO#=726440
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [m] 398.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-DEC-01:00 09-DEC-08:30 - - - 25-JUN-17:15
Heating 178038.21 319979.07 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7980.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 20217.84 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19230.90 0.00 0.00 0.00 0.00 0.00
Pumps 1805.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 88159.50 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 238392.13 408138.57 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 319979.07 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 6974.01 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1006.63 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 20217.84 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 19230.90 0.00 0.00 0.00 0.00 0.00
Pumps General 1805.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 88159.50 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 1347.68 1691.35 0.00 0.00 0.00
Cooling 940.27 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.19 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1920.68 0.00 0.00 0.00 0.00
Pumps 176.28 0.00 0.00 0.00 0.00
Heat Rejection 41.35 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1404.55 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9926.36 3095.91 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 190.89 239.57 0.00 0.00 0.00
Cooling 133.19 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.52 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 272.05 0.00 0.00 0.00 0.00
Pumps 24.97 0.00 0.00 0.00 0.00
Heat Rejection 5.86 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 198.95 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1406.02 438.52 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 190.89 239.57 0.00 0.00 0.00
Cooling 133.19 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.52 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 272.05 0.00 0.00 0.00 0.00
Pumps 24.97 0.00 0.00 0.00 0.00
Heat Rejection 5.86 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 198.95 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1406.02 438.52 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -26.20 0.00 -26.20 Wetbulb [C] 5.70 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 31.20 10.60 23.10 Wetbulb [C] 6.70 200.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.36 0.00 0.00 3.36 3.36 2.653 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.653 0.426 0.308              
North Total or Average           423.59 2.653 0.426 0.308              
Non-North Total or Average           726.80 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.66 83.66 168.36
Exterior Lighting Total 10720.10           168.36



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 318712.45 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 254969.96      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3887.38 2478.79 1408.59 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3684.09 2331.29 1352.79 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   5271.71 3365.13 1906.58 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3354.42 2048.68 1305.74 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2420.09 1430.07 990.02 0.59 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2432.99 1434.73 998.25 0.59 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2659.02 1616.75 1042.27 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2733.18 1670.03 1063.15 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4950.17 3209.82 1740.35 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4645.28 2987.93 1657.34 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4730.04 3042.65 1687.40 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3696.78 2314.54 1382.24 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2787.43 1699.73 1087.71 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2765.36 1684.21 1081.15 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3381.17 2114.73 1266.43 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3411.40 2136.63 1274.77 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5022.00 3237.24 1784.76 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4735.20 3029.07 1706.13 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4591.56 2918.47 1673.09 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3800.25 2367.74 1432.52 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2877.67 1752.30 1125.37 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2855.82 1736.98 1118.84 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3466.03 2162.69 1303.34 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3482.07 2174.30 1307.77 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5072.40 3255.58 1816.82 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4798.67 3056.01 1742.65 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4627.16 2927.04 1700.12 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3852.08 2389.44 1462.64 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2921.93 1775.25 1146.67 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2900.12 1760.00 1140.12 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3506.82 2182.20 1324.62 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3520.88 2192.37 1328.51 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5145.80 3294.04 1851.76 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4876.88 3098.28 1778.60 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4703.77 2968.46 1735.31 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3926.14 2429.91 1496.23 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2988.53 1815.43 1173.10 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2966.79 1800.24 1166.54 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3570.36 2219.88 1350.48 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3584.12 2229.82 1354.30 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5122.82 3265.17 1857.65 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4855.04 3070.67 1784.37 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4685.66 2943.96 1741.70 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3900.89 2401.87 1499.02 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2958.72 1789.00 1169.72 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2937.04 1773.93 1163.11 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3539.64 2191.19 1348.45 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3553.40 2201.10 1352.30 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5130.10 3259.80 1870.30 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4864.54 3067.25 1797.28 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4697.22 2942.33 1754.88 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3943.14 2419.70 1523.44 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2960.23 1785.33 1174.90 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2938.61 1770.34 1168.26 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3539.62 2185.41 1354.21 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3553.39 2195.31 1358.07 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5153.68 3267.35 1886.33 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4890.11 3076.52 1813.59 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4723.47 2952.34 1771.14 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4078.04 2496.60 1581.44 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2979.08 1794.29 1184.79 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2957.57 1779.41 1178.16 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3555.76 2191.82 1363.94 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3569.57 2201.74 1367.83 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5294.95 3360.16 1934.78 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5026.99 3166.19 1860.80 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4832.24 3021.46 1810.78 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4358.30 2666.36 1691.94 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3095.33 1871.39 1223.94 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3073.58 1856.30 1217.28 0.60 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3641.25 2247.73 1393.52 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3654.08 2257.14 1396.94 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   6081.21 3914.54 2166.67 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5681.31 3629.45 2051.85 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5595.00 3561.57 2033.43 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5069.94 3154.25 1915.69 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3532.95 2171.46 1361.50 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3604.80 2209.24 1395.56 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4548.17 2895.34 1652.83 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4561.52 2905.10 1656.42 0.64 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3887.38 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   3684.09 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   5271.71 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   3354.42 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2420.09 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2432.99 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2659.02 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2733.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4950.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4645.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4730.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3696.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2787.43 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2765.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3381.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3411.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5022.00 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4735.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4591.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3800.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2877.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2855.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3466.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3482.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5072.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4798.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4627.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3852.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2921.93 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2900.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3506.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3520.88 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5145.80 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   4876.88 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4703.77 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   3926.14 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2988.53 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2966.79 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3570.36 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3584.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5122.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4855.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4685.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3900.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2958.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2937.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3539.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3553.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5130.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4864.54 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4697.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3943.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2960.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2938.61 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3539.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3553.39 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5153.68 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4890.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4723.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4078.04 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2979.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2957.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3555.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3569.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5294.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5026.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4832.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4358.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3095.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3073.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3641.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3654.08 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   6081.21 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   5681.31 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   5595.00 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   5069.94 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3532.95 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3604.80 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4548.17 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4561.52 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   5102.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   5111.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   6247.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   5110.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   3884.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   3884.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   3873.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   3882.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   5139.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   5150.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   5155.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   5142.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   3623.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   3623.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   3615.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   3617.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   5245.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   5265.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   5235.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   5253.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   3647.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   3646.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   3627.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   3627.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   5396.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   5421.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   5381.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   5406.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   3730.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   3729.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   3704.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   3704.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   5505.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   5534.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   5488.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   5516.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   3784.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   3784.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   3756.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   3756.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   5671.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   5704.06 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   5652.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   5684.76 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   3902.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   3902.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   3870.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   3870.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   5798.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   5832.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   5777.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   5811.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   3986.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   3986.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   3953.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   3952.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   5926.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   5961.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   5904.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   5939.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   4076.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   4076.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   4041.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   4041.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   6226.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   6259.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   6203.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   6236.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   4326.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   4325.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   4293.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   4292.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   7199.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   7240.76 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   7177.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   7218.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   5357.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   5357.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   5313.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   5313.01 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 245.36 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 229.62 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 330.16 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.94 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.94 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.12 129.94 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.13 149.68 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 155.61 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.44 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 299.50 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.43 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.41 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 161.50 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.14 159.79 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 203.18 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 205.62 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.72 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.30 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 286.94 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 230.60 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.32 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 164.62 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 207.45 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.75 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 325.43 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 303.48 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 286.60 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.74 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.10 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.41 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.83 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 209.96 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.62 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 307.09 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 290.13 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 235.18 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 171.93 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 170.25 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 212.36 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 213.47 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.51 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 303.12 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 286.53 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.21 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.47 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.81 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.64 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 209.75 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.11 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 301.95 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 285.56 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 232.09 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 167.60 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 165.96 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 207.53 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.63 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.23 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 302.26 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 285.97 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.86 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 168.18 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.15 166.55 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 207.81 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.91 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 332.82 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 311.51 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 292.79 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.56 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 176.32 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 174.66 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 213.45 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 214.63 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 391.37 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 361.66 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 352.01 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.27 306.64 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 208.01 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 207.99 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.25 284.87 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 285.96 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0069 1768.07 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2223.21 2667.85 0.183 0.219 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
G NW APARTMENT 2080.53 2496.63 0.171 0.205 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
OFFICE 2991.50 3589.80 0.246 0.295 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
G NE APARTMENT 1491.92 1790.31 0.123 0.147 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17 0.01534
G N1 APARTMENT 1045.59 1254.71 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
G N2 APARTMENT 1026.90 1232.28 0.084 0.101 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
G S1 APARTMENT 1356.22 1627.47 0.111 0.134 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
G S2 APARTMENT 1409.97 1691.97 0.116 0.139 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F2 SW APARTMENT 2930.60 3516.72 0.241 0.289 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F2 NW APARTMENT 2713.66 3256.39 0.223 0.267 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
F2 SE APARTMENT 2740.17 3288.20 0.225 0.270 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F2 NE APARTMENT 2051.30 2461.56 0.168 0.202 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F2 N1 APARTMENT 1463.37 1756.04 0.120 0.144 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F2 N2 APARTMENT 1447.82 1737.39 0.119 0.143 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F2 S1 APARTMENT 1841.00 2209.20 0.151 0.181 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F2 S2 APARTMENT 1863.05 2235.67 0.153 0.184 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F3 SW APARTMENT 2942.10 3530.53 0.242 0.290 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F3 NW APARTMENT 2738.98 3286.77 0.225 0.270 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.26 0.01534
F3 SE APARTMENT 2599.74 3119.69 0.213 0.256 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F3 NE APARTMENT 2089.27 2507.12 0.172 0.206 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F3 N1 APARTMENT 1506.96 1808.35 0.124 0.148 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F3 N2 APARTMENT 1491.61 1789.93 0.122 0.147 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F3 S1 APARTMENT 1879.68 2255.62 0.154 0.185 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F3 S2 APARTMENT 1891.39 2269.67 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F4 SW APARTMENT 2948.52 3538.23 0.242 0.291 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F4 NW APARTMENT 2749.59 3299.51 0.226 0.271 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
F4 SE APARTMENT 2596.57 3115.89 0.213 0.256 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F4 NE APARTMENT 2099.49 2519.38 0.172 0.207 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F4 N1 APARTMENT 1523.07 1827.69 0.125 0.150 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F4 N2 APARTMENT 1507.82 1809.38 0.124 0.149 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F4 S1 APARTMENT 1892.14 2270.57 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F4 S2 APARTMENT 1902.39 2282.87 0.156 0.187 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
M SW APARTMENT 2977.33 3572.80 0.244 0.293 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
M NW APARTMENT 2782.27 3338.73 0.228 0.274 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
M SE APARTMENT 2628.49 3154.19 0.216 0.259 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
M NE APARTMENT 2130.68 2556.81 0.175 0.210 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
M N1 APARTMENT 1557.77 1869.32 0.128 0.153 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
M N2 APARTMENT 1542.58 1851.10 0.127 0.152 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
M S1 APARTMENT 1924.12 2308.94 0.158 0.190 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
M S2 APARTMENT 1934.14 2320.97 0.159 0.191 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F6 SW APARTMENT 2940.07 3528.09 0.241 0.290 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F6 NW APARTMENT 2746.32 3295.58 0.226 0.271 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
F6 SE APARTMENT 2595.82 3114.99 0.213 0.256 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F6 NE APARTMENT 2094.62 2513.54 0.172 0.206 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F6 N1 APARTMENT 1526.45 1831.74 0.125 0.150 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F6 N2 APARTMENT 1511.40 1813.68 0.124 0.149 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F6 S1 APARTMENT 1890.39 2268.47 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F6 S2 APARTMENT 1900.38 2280.46 0.156 0.187 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F7 SW APARTMENT 2927.41 3512.90 0.240 0.288 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F7 NW APARTMENT 2735.65 3282.78 0.225 0.270 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
F7 SE APARTMENT 2587.06 3104.47 0.212 0.255 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F7 NE APARTMENT 2083.23 2499.87 0.171 0.205 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F7 N1 APARTMENT 1518.58 1822.30 0.125 0.150 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F7 N2 APARTMENT 1503.64 1804.37 0.123 0.148 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F7 S1 APARTMENT 1880.26 2256.31 0.154 0.185 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F7 S2 APARTMENT 1890.24 2268.29 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F8 SW APARTMENT 2928.45 3514.14 0.240 0.289 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F8 NW APARTMENT 2738.45 3286.14 0.225 0.270 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
F8 SE APARTMENT 2590.69 3108.82 0.213 0.255 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
F8 NE APARTMENT 2084.47 2501.37 0.171 0.205 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 27.57 0.01534
F8 N1 APARTMENT 1523.81 1828.58 0.125 0.150 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F8 N2 APARTMENT 1508.98 1810.78 0.124 0.149 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F8 S1 APARTMENT 1882.80 2259.35 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F8 S2 APARTMENT 1892.79 2271.35 0.155 0.187 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F9 SW APARTMENT 3015.34 3618.41 0.248 0.297 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 28.92 0.01534
F9 NW APARTMENT 2822.25 3386.71 0.232 0.278 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
F9 SE APARTMENT 2652.45 3182.94 0.218 0.261 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
F9 NE APARTMENT 2115.90 2539.08 0.174 0.209 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 27.97 0.01534
F9 N1 APARTMENT 1597.54 1917.05 0.131 0.157 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F9 N2 APARTMENT 1582.51 1899.02 0.130 0.156 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
F9 S1 APARTMENT 1933.92 2320.71 0.159 0.191 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 31.20 0.01534
F9 S2 APARTMENT 1944.57 2333.48 0.160 0.192 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
T SW APARTMENT 3545.48 4254.58 0.291 0.349 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 30.72 0.01534
T NW APARTMENT 3276.52 3931.83 0.269 0.323 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 29.19 0.01534
T SE APARTMENT 3188.90 3826.69 0.262 0.314 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93 0.01534
T NE APARTMENT 2517.46 3020.95 0.207 0.248 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 28.36 0.01534
T N1 APARTMENT 1857.61 2229.13 0.153 0.183 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 27.86 0.01534
T N2 APARTMENT 1837.19 2204.63 0.151 0.181 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
T S1 APARTMENT 2580.97 3097.17 0.212 0.254 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
T S2 APARTMENT 2590.83 3109.00 0.213 0.255 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 3101.81 3722.17 0.145 0.174 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G NW APARTMENT 3109.24 3731.09 0.145 0.174 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
OFFICE 3501.50 4201.80 0.163 0.196 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -26.20 0.00036
G NE APARTMENT 3108.62 3730.35 0.145 0.174 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G N1 APARTMENT 2072.05 2486.46 0.097 0.116 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G N2 APARTMENT 2072.02 2486.43 0.097 0.116 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G S1 APARTMENT 2062.45 2474.94 0.096 0.115 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
G S2 APARTMENT 2069.57 2483.49 0.097 0.116 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
F2 SW APARTMENT 3133.07 3759.68 0.146 0.175 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 NW APARTMENT 3142.35 3770.82 0.147 0.176 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 SE APARTMENT 3146.88 3776.25 0.147 0.176 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 NE APARTMENT 3135.61 3762.74 0.146 0.176 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 N1 APARTMENT 1851.40 2221.68 0.086 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 N2 APARTMENT 1851.26 2221.51 0.086 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 S1 APARTMENT 1844.60 2213.52 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F2 S2 APARTMENT 1845.70 2214.84 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 SW APARTMENT 3222.69 3867.23 0.150 0.180 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 NW APARTMENT 3239.93 3887.91 0.151 0.181 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 SE APARTMENT 3214.34 3857.21 0.150 0.180 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 NE APARTMENT 3229.52 3875.43 0.151 0.181 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 N1 APARTMENT 1871.03 2245.24 0.087 0.105 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 N2 APARTMENT 1870.81 2244.97 0.087 0.105 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 S1 APARTMENT 1854.53 2225.43 0.087 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F3 S2 APARTMENT 1854.48 2225.37 0.087 0.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 SW APARTMENT 3350.03 4020.04 0.156 0.188 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 NW APARTMENT 3371.87 4046.24 0.157 0.189 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 SE APARTMENT 3337.29 4004.75 0.156 0.187 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 NE APARTMENT 3358.94 4030.73 0.157 0.188 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 N1 APARTMENT 1941.30 2329.55 0.091 0.109 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 N2 APARTMENT 1941.01 2329.21 0.091 0.109 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 S1 APARTMENT 1919.88 2303.86 0.090 0.107 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F4 S2 APARTMENT 1919.62 2303.54 0.090 0.107 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M SW APARTMENT 3442.92 4131.51 0.161 0.193 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M NW APARTMENT 3466.85 4160.21 0.162 0.194 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M SE APARTMENT 3428.12 4113.74 0.160 0.192 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M NE APARTMENT 3452.03 4142.44 0.161 0.193 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M N1 APARTMENT 1987.15 2384.58 0.093 0.111 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M N2 APARTMENT 1986.83 2384.19 0.093 0.111 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M S1 APARTMENT 1963.54 2356.25 0.092 0.110 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
M S2 APARTMENT 1963.22 2355.86 0.092 0.110 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 SW APARTMENT 3583.33 4300.00 0.167 0.201 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 NW APARTMENT 3610.48 4332.58 0.168 0.202 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 SE APARTMENT 3567.00 4280.40 0.166 0.200 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 NE APARTMENT 3594.16 4312.99 0.168 0.201 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 N1 APARTMENT 2086.97 2504.37 0.097 0.117 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 N2 APARTMENT 2086.61 2503.94 0.097 0.117 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 S1 APARTMENT 2060.10 2472.11 0.096 0.115 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F6 S2 APARTMENT 2059.74 2471.69 0.096 0.115 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 SW APARTMENT 3690.45 4428.55 0.172 0.207 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 NW APARTMENT 3719.31 4463.17 0.173 0.208 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 SE APARTMENT 3672.89 4407.46 0.171 0.206 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 NE APARTMENT 3701.75 4442.10 0.173 0.207 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 N1 APARTMENT 2158.37 2590.04 0.101 0.121 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 N2 APARTMENT 2157.98 2589.58 0.101 0.121 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 S1 APARTMENT 2129.77 2555.72 0.099 0.119 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F7 S2 APARTMENT 2129.38 2555.26 0.099 0.119 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 SW APARTMENT 3798.60 4558.32 0.177 0.213 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 NW APARTMENT 3828.52 4594.22 0.179 0.214 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 SE APARTMENT 3779.98 4535.98 0.176 0.212 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 NE APARTMENT 3809.92 4571.90 0.178 0.213 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 N1 APARTMENT 2234.27 2681.13 0.104 0.125 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 N2 APARTMENT 2233.87 2680.64 0.104 0.125 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 S1 APARTMENT 2204.60 2645.52 0.103 0.123 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F8 S2 APARTMENT 2204.19 2645.03 0.103 0.123 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 SW APARTMENT 4052.20 4862.64 0.189 0.227 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 NW APARTMENT 4080.01 4896.01 0.190 0.228 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 SE APARTMENT 4032.51 4839.02 0.188 0.226 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 NE APARTMENT 4060.34 4872.41 0.189 0.227 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 N1 APARTMENT 2445.29 2934.35 0.114 0.137 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 N2 APARTMENT 2444.86 2933.84 0.114 0.137 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 S1 APARTMENT 2417.35 2900.82 0.113 0.135 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
F9 S2 APARTMENT 2416.92 2900.31 0.113 0.135 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T SW APARTMENT 4875.41 5850.49 0.227 0.273 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T NW APARTMENT 4910.02 5892.03 0.229 0.275 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T SE APARTMENT 4856.43 5827.71 0.227 0.272 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T NE APARTMENT 4891.06 5869.27 0.228 0.274 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T N1 APARTMENT 3317.57 3981.09 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T N2 APARTMENT 3317.13 3980.56 0.155 0.186 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T S1 APARTMENT 3280.21 3936.25 0.153 0.184 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036
T S2 APARTMENT 3279.77 3935.72 0.153 0.184 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.20 0.00036


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.22 0.22 0.17 0.17
AIRLOOP G NW 0.20 0.20 0.17 0.17
AIRLOOP OFFICE 0.29 0.29 0.20 0.20
AIRLOOP G NE 0.15 0.15 0.17 0.17
AIRLOOP G N1 0.10 0.10 0.12 0.12
AIRLOOP G N2 0.10 0.10 0.12 0.12
AIRLOOP G S1 0.13 0.13 0.12 0.12
AIRLOOP G S2 0.14 0.14 0.12 0.12
AIRLOOP F2 SW 0.29 0.29 0.18 0.18
AIRLOOP F2 NW 0.27 0.27 0.18 0.18
AIRLOOP F2 SE 0.27 0.27 0.18 0.18
AIRLOOP F2 NE 0.20 0.20 0.18 0.18
AIRLOOP F2 N1 0.14 0.14 0.10 0.10
AIRLOOP F2 N2 0.14 0.14 0.10 0.10
AIRLOOP F2 S1 0.18 0.18 0.10 0.10
AIRLOOP F2 S2 0.18 0.18 0.10 0.10
AIRLOOP F3 SW 0.29 0.29 0.18 0.18
AIRLOOP F3 NW 0.27 0.27 0.18 0.18
AIRLOOP F3 SE 0.26 0.26 0.18 0.18
AIRLOOP F3 NE 0.21 0.21 0.18 0.18
AIRLOOP F3 N1 0.15 0.15 0.10 0.10
AIRLOOP F3 N2 0.15 0.15 0.10 0.10
AIRLOOP F3 S1 0.19 0.19 0.10 0.10
AIRLOOP F3 S2 0.19 0.19 0.10 0.10
AIRLOOP F4 SW 0.29 0.29 0.19 0.19
AIRLOOP F4 NW 0.27 0.27 0.19 0.19
AIRLOOP F4 SE 0.26 0.26 0.19 0.19
AIRLOOP F4 NE 0.21 0.21 0.19 0.19
AIRLOOP F4 N1 0.15 0.15 0.11 0.11
AIRLOOP F4 N2 0.15 0.15 0.11 0.11
AIRLOOP F4 S1 0.19 0.19 0.11 0.11
AIRLOOP F4 S2 0.19 0.19 0.11 0.11
AIRLOOP M SW 0.29 0.29 0.19 0.19
AIRLOOP M NW 0.27 0.27 0.19 0.19
AIRLOOP M SE 0.26 0.26 0.19 0.19
AIRLOOP M NE 0.21 0.21 0.19 0.19
AIRLOOP M N1 0.15 0.15 0.11 0.11
AIRLOOP M N2 0.15 0.15 0.11 0.11
AIRLOOP M S1 0.19 0.19 0.11 0.11
AIRLOOP M S2 0.19 0.19 0.11 0.11
AIRLOOP F6 SW 0.29 0.29 0.20 0.20
AIRLOOP F6 NW 0.27 0.27 0.20 0.20
AIRLOOP F6 SE 0.26 0.26 0.20 0.20
AIRLOOP F6 NE 0.21 0.21 0.20 0.20
AIRLOOP F6 N1 0.15 0.15 0.12 0.12
AIRLOOP F6 N2 0.15 0.15 0.12 0.12
AIRLOOP F6 S1 0.19 0.19 0.12 0.12
AIRLOOP F6 S2 0.19 0.19 0.12 0.12
AIRLOOP F7 SW 0.29 0.29 0.21 0.21
AIRLOOP F7 NW 0.27 0.27 0.21 0.21
AIRLOOP F7 SE 0.25 0.25 0.21 0.21
AIRLOOP F7 NE 0.21 0.21 0.21 0.21
AIRLOOP F7 N1 0.15 0.15 0.12 0.12
AIRLOOP F7 N2 0.15 0.15 0.12 0.12
AIRLOOP F7 S1 0.19 0.19 0.12 0.12
AIRLOOP F7 S2 0.19 0.19 0.12 0.12
AIRLOOP F8 SW 0.29 0.29 0.21 0.21
AIRLOOP F8 NW 0.27 0.27 0.21 0.21
AIRLOOP F8 SE 0.26 0.26 0.21 0.21
AIRLOOP F8 NE 0.21 0.21 0.21 0.21
AIRLOOP F8 N1 0.15 0.15 0.13 0.13
AIRLOOP F8 N2 0.15 0.15 0.13 0.13
AIRLOOP F8 S1 0.19 0.19 0.12 0.12
AIRLOOP F8 S2 0.19 0.19 0.12 0.12
AIRLOOP F9 SW 0.30 0.30 0.23 0.23
AIRLOOP F9 NW 0.28 0.28 0.23 0.23
AIRLOOP F9 SE 0.26 0.26 0.23 0.23
AIRLOOP F9 NE 0.21 0.21 0.23 0.23
AIRLOOP F9 N1 0.16 0.16 0.14 0.14
AIRLOOP F9 N2 0.16 0.16 0.14 0.14
AIRLOOP F9 S1 0.19 0.19 0.14 0.14
AIRLOOP F9 S2 0.19 0.19 0.14 0.14
AIRLOOP T SW 0.35 0.35 0.27 0.27
AIRLOOP T NW 0.32 0.32 0.27 0.27
AIRLOOP T SE 0.31 0.31 0.27 0.27
AIRLOOP T NE 0.25 0.25 0.27 0.27
AIRLOOP T N1 0.18 0.18 0.19 0.19
AIRLOOP T N2 0.18 0.18 0.19 0.19
AIRLOOP T S1 0.25 0.25 0.18 0.18
AIRLOOP T S2 0.26 0.26 0.18 0.18



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3804.25 6687.00 2184.75
G NW APARTMENT 4239.25 7054.00 2841.75
OFFICE 1027.50 1233.75 247.50
G NE APARTMENT 4262.75 7060.00 2851.50
G N1 APARTMENT 3366.25 7323.25 2241.25
G N2 APARTMENT 3369.50 7324.50 2244.25
G S1 APARTMENT 3070.50 6830.50 1619.25
G S2 APARTMENT 3077.75 6783.00 1602.00
F2 SW APARTMENT 3830.50 5591.75 1370.50
F2 NW APARTMENT 4111.25 6200.75 1964.00
F2 SE APARTMENT 3869.75 5437.00 1259.00
F2 NE APARTMENT 4125.50 6245.50 1978.50
F2 N1 APARTMENT 3257.25 6428.75 1338.50
F2 N2 APARTMENT 3257.75 6436.25 1340.50
F2 S1 APARTMENT 3231.50 5554.50 844.00
F2 S2 APARTMENT 3245.00 5533.50 839.00
F3 SW APARTMENT 3891.00 5417.00 1305.00
F3 NW APARTMENT 4139.00 6076.25 1890.00
F3 SE APARTMENT 3888.00 5424.50 1266.50
F3 NE APARTMENT 4150.00 6122.00 1901.00
F3 N1 APARTMENT 3294.75 6208.75 1216.50
F3 N2 APARTMENT 3288.00 6221.25 1217.75
F3 S1 APARTMENT 3376.75 5305.25 775.25
F3 S2 APARTMENT 3379.25 5298.75 775.25
F4 SW APARTMENT 3930.00 5424.75 1330.25
F4 NW APARTMENT 4174.00 6065.00 1918.25
F4 SE APARTMENT 3900.50 5468.25 1310.50
F4 NE APARTMENT 4183.50 6124.75 1941.25
F4 N1 APARTMENT 3333.25 6159.25 1220.00
F4 N2 APARTMENT 3329.50 6174.25 1222.25
F4 S1 APARTMENT 3419.00 5273.00 779.25
F4 S2 APARTMENT 3417.25 5272.75 779.75
M SW APARTMENT 3920.50 5443.00 1329.50
M NW APARTMENT 4161.75 6064.75 1902.75
M SE APARTMENT 3885.50 5494.00 1308.25
M NE APARTMENT 4170.25 6129.25 1926.00
M N1 APARTMENT 3333.00 6136.50 1195.00
M N2 APARTMENT 3327.25 6149.50 1195.25
M S1 APARTMENT 3412.50 5283.75 773.25
M S2 APARTMENT 3410.75 5282.00 774.25
F6 SW APARTMENT 3875.25 5606.50 1423.25
F6 NW APARTMENT 4192.75 6203.25 2047.75
F6 SE APARTMENT 3866.25 5663.00 1416.50
F6 NE APARTMENT 4212.25 6258.75 2088.25
F6 N1 APARTMENT 3322.75 6295.75 1312.50
F6 N2 APARTMENT 3317.50 6305.00 1314.25
F6 S1 APARTMENT 3330.25 5437.25 828.25
F6 S2 APARTMENT 3326.50 5439.75 828.25
F7 SW APARTMENT 3855.50 5739.25 1488.25
F7 NW APARTMENT 4200.50 6296.25 2132.25
F7 SE APARTMENT 3845.50 5791.25 1480.50
F7 NE APARTMENT 4212.00 6345.00 2166.25
F7 N1 APARTMENT 3312.25 6403.75 1377.50
F7 N2 APARTMENT 3309.25 6414.00 1379.25
F7 S1 APARTMENT 3273.00 5561.50 867.50
F7 S2 APARTMENT 3271.50 5565.75 868.00
F8 SW APARTMENT 3844.75 5854.25 1553.00
F8 NW APARTMENT 4214.25 6365.25 2206.50
F8 SE APARTMENT 3838.50 5906.75 1551.00
F8 NE APARTMENT 4233.00 6396.75 2231.50
F8 N1 APARTMENT 3318.25 6496.75 1441.00
F8 N2 APARTMENT 3314.00 6503.75 1442.50
F8 S1 APARTMENT 3219.50 5680.75 910.00
F8 S2 APARTMENT 3219.50 5683.25 910.75
F9 SW APARTMENT 3937.75 5971.00 1736.25
F9 NW APARTMENT 4348.50 6446.50 2403.50
F9 SE APARTMENT 3932.25 6030.50 1734.00
F9 NE APARTMENT 4351.75 6457.50 2394.00
F9 N1 APARTMENT 3406.75 6587.75 1590.25
F9 N2 APARTMENT 3408.50 6593.00 1592.50
F9 S1 APARTMENT 3220.00 5876.25 1047.25
F9 S2 APARTMENT 3219.50 5874.25 1048.50
T SW APARTMENT 4795.00 6267.75 2821.50
T NW APARTMENT 5067.75 6711.25 3394.50
T SE APARTMENT 4818.50 6322.25 2855.25
T NE APARTMENT 5100.75 6744.50 3407.25
T N1 APARTMENT 4335.75 6839.00 2733.50
T N2 APARTMENT 4336.25 6833.00 2729.75
T S1 APARTMENT 4057.25 6191.50 2092.25
T S2 APARTMENT 4063.75 6195.00 2095.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 6242.75 7478.00 3838.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 2.25 2.25 2.25 2.25
G NW APARTMENT 2.75 0.00 2.75 0.00
OFFICE 2.75 0.00 0.75 0.00
G NE APARTMENT 4.25 1.00 4.25 1.00
G N1 APARTMENT 4.75 0.00 4.75 0.00
G N2 APARTMENT 3.75 0.00 3.75 0.00
G S1 APARTMENT 0.75 16.50 0.75 16.50
G S2 APARTMENT 1.25 14.75 1.25 14.75
F2 SW APARTMENT 3.50 0.25 3.50 0.25
F2 NW APARTMENT 1.50 0.00 1.50 0.00
F2 SE APARTMENT 2.00 1.75 2.00 1.75
F2 NE APARTMENT 0.75 11.50 0.75 11.50
F2 N1 APARTMENT 2.50 3.00 2.50 3.00
F2 N2 APARTMENT 3.00 3.75 3.00 3.75
F2 S1 APARTMENT 1.50 13.00 1.50 13.00
F2 S2 APARTMENT 1.50 12.00 1.50 12.00
F3 SW APARTMENT 2.00 0.25 2.00 0.25
F3 NW APARTMENT 1.25 0.00 1.25 0.00
F3 SE APARTMENT 1.75 7.00 1.75 7.00
F3 NE APARTMENT 1.50 17.25 1.50 17.25
F3 N1 APARTMENT 3.75 7.75 3.75 7.75
F3 N2 APARTMENT 3.00 9.75 3.00 9.75
F3 S1 APARTMENT 1.00 18.50 1.00 18.50
F3 S2 APARTMENT 1.50 17.50 1.50 17.50
F4 SW APARTMENT 3.00 0.25 3.00 0.25
F4 NW APARTMENT 0.75 0.00 0.75 0.00
F4 SE APARTMENT 1.25 8.75 1.25 8.75
F4 NE APARTMENT 1.25 20.00 1.25 20.00
F4 N1 APARTMENT 1.25 11.25 1.25 11.25
F4 N2 APARTMENT 1.50 14.50 1.50 14.50
F4 S1 APARTMENT 1.75 20.00 1.75 20.00
F4 S2 APARTMENT 0.75 19.25 0.75 19.25
M SW APARTMENT 2.00 0.00 2.00 0.00
M NW APARTMENT 0.50 0.00 0.50 0.00
M SE APARTMENT 0.75 9.00 0.75 9.00
M NE APARTMENT 1.25 20.75 1.25 20.75
M N1 APARTMENT 2.75 13.25 2.75 13.25
M N2 APARTMENT 2.25 16.25 2.25 16.25
M S1 APARTMENT 1.50 21.75 1.50 21.75
M S2 APARTMENT 1.00 20.25 1.00 20.25
F6 SW APARTMENT 1.00 0.50 1.00 0.50
F6 NW APARTMENT 1.00 0.00 1.00 0.00
F6 SE APARTMENT 0.25 9.00 0.25 9.00
F6 NE APARTMENT 2.50 21.25 2.50 21.25
F6 N1 APARTMENT 3.75 14.00 3.75 14.00
F6 N2 APARTMENT 3.25 18.00 3.25 18.00
F6 S1 APARTMENT 1.75 21.50 1.75 21.50
F6 S2 APARTMENT 1.75 21.50 1.75 21.50
F7 SW APARTMENT 0.75 0.50 0.75 0.50
F7 NW APARTMENT 0.75 0.00 0.75 0.00
F7 SE APARTMENT 1.25 10.25 1.25 10.25
F7 NE APARTMENT 1.75 20.00 1.75 20.00
F7 N1 APARTMENT 3.75 15.75 3.75 15.75
F7 N2 APARTMENT 4.50 20.25 4.50 20.25
F7 S1 APARTMENT 3.00 21.00 3.00 21.00
F7 S2 APARTMENT 2.25 20.00 2.25 20.00
F8 SW APARTMENT 1.25 0.25 1.25 0.25
F8 NW APARTMENT 0.75 0.00 0.75 0.00
F8 SE APARTMENT 2.75 11.00 2.75 11.00
F8 NE APARTMENT 0.75 14.50 0.75 14.50
F8 N1 APARTMENT 4.25 16.25 4.25 16.25
F8 N2 APARTMENT 2.75 22.00 2.75 22.00
F8 S1 APARTMENT 2.50 22.25 2.50 22.25
F8 S2 APARTMENT 2.75 21.50 2.75 21.50
F9 SW APARTMENT 0.75 0.25 0.75 0.25
F9 NW APARTMENT 0.75 0.00 0.75 0.00
F9 SE APARTMENT 1.00 9.75 1.00 9.75
F9 NE APARTMENT 0.50 9.50 0.50 9.50
F9 N1 APARTMENT 3.50 14.00 3.50 14.00
F9 N2 APARTMENT 2.00 15.75 2.00 15.75
F9 S1 APARTMENT 2.00 23.25 2.00 23.25
F9 S2 APARTMENT 3.25 22.25 3.25 22.25
T SW APARTMENT 0.00 2.00 0.00 2.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 13.75 0.00 13.75
T NE APARTMENT 0.00 8.75 0.00 8.75
T N1 APARTMENT 1.75 25.00 1.75 25.00
T N2 APARTMENT 2.50 19.50 2.50 19.50
T S1 APARTMENT 0.50 16.25 0.50 16.25
T S2 APARTMENT 1.50 16.50 1.50 16.50
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 125.00 73.50 123.25 73.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.354 0.145 0.000 0.296
G NW APARTMENT 1.71 2.50 268.96 0.354 0.145 0.000 0.278
OFFICE 0.94 1.00 268.96 0.519 0.161 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.354 0.145 0.000 0.279
G N1 APARTMENT 1.71 2.50 268.96 0.354 0.087 0.000 0.274
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.087 0.000 0.274
G S1 APARTMENT 1.71 2.50 268.96 0.354 0.087 0.000 0.293
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.087 0.000 0.293
F2 SW APARTMENT 1.71 2.50 268.96 0.354 0.208 0.000 0.358
F2 NW APARTMENT 1.71 2.50 268.96 0.354 0.208 0.000 0.332
F2 SE APARTMENT 1.71 2.50 268.96 0.354 0.208 0.000 0.359
F2 NE APARTMENT 1.71 2.50 268.96 0.354 0.208 0.000 0.332
F2 N1 APARTMENT 1.71 2.50 268.96 0.354 0.125 0.000 0.329
F2 N2 APARTMENT 1.71 2.50 268.97 0.354 0.125 0.000 0.329
F2 S1 APARTMENT 1.71 2.50 268.96 0.354 0.126 0.000 0.356
F2 S2 APARTMENT 1.71 2.50 268.97 0.354 0.126 0.000 0.356
F3 SW APARTMENT 1.71 2.50 268.96 0.354 0.246 0.000 0.403
F3 NW APARTMENT 1.71 2.50 268.96 0.354 0.246 0.000 0.371
F3 SE APARTMENT 1.71 2.50 268.96 0.354 0.246 0.000 0.403
F3 NE APARTMENT 1.71 2.50 268.96 0.354 0.246 0.000 0.371
F3 N1 APARTMENT 1.71 2.50 268.96 0.354 0.149 0.000 0.368
F3 N2 APARTMENT 1.71 2.50 268.97 0.354 0.149 0.000 0.368
F3 S1 APARTMENT 1.71 2.50 268.96 0.354 0.149 0.000 0.401
F3 S2 APARTMENT 1.71 2.50 268.97 0.354 0.149 0.000 0.401
F4 SW APARTMENT 1.71 2.50 268.96 0.354 0.275 0.000 0.424
F4 NW APARTMENT 1.71 2.50 268.96 0.354 0.275 0.000 0.388
F4 SE APARTMENT 1.71 2.50 268.96 0.354 0.275 0.000 0.424
F4 NE APARTMENT 1.71 2.50 268.96 0.354 0.275 0.000 0.388
F4 N1 APARTMENT 1.71 2.50 268.96 0.354 0.166 0.000 0.386
F4 N2 APARTMENT 1.71 2.50 268.97 0.354 0.166 0.000 0.386
F4 S1 APARTMENT 1.71 2.50 268.96 0.354 0.166 0.000 0.423
F4 S2 APARTMENT 1.71 2.50 268.97 0.354 0.166 0.000 0.423
M SW APARTMENT 1.71 2.50 268.96 0.354 0.299 0.000 0.448
M NW APARTMENT 1.71 2.50 268.96 0.354 0.299 0.000 0.409
M SE APARTMENT 1.71 2.50 268.96 0.354 0.299 0.000 0.449
M NE APARTMENT 1.71 2.50 268.96 0.354 0.299 0.000 0.409
M N1 APARTMENT 1.71 2.50 268.96 0.354 0.180 0.000 0.407
M N2 APARTMENT 1.71 2.50 268.97 0.354 0.180 0.000 0.407
M S1 APARTMENT 1.71 2.50 268.96 0.354 0.181 0.000 0.447
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.181 0.000 0.447
F6 SW APARTMENT 1.71 2.50 268.96 0.354 0.320 0.000 0.469
F6 NW APARTMENT 1.71 2.50 268.96 0.354 0.319 0.000 0.427
F6 SE APARTMENT 1.71 2.50 268.96 0.354 0.320 0.000 0.469
F6 NE APARTMENT 1.71 2.50 268.96 0.354 0.319 0.000 0.427
F6 N1 APARTMENT 1.71 2.50 268.96 0.354 0.193 0.000 0.425
F6 N2 APARTMENT 1.71 2.50 268.97 0.354 0.193 0.000 0.425
F6 S1 APARTMENT 1.71 2.50 268.96 0.354 0.193 0.000 0.468
F6 S2 APARTMENT 1.71 2.50 268.97 0.354 0.193 0.000 0.468
F7 SW APARTMENT 1.71 2.50 268.96 0.354 0.338 0.000 0.487
F7 NW APARTMENT 1.71 2.50 268.96 0.354 0.338 0.000 0.442
F7 SE APARTMENT 1.71 2.50 268.96 0.354 0.338 0.000 0.487
F7 NE APARTMENT 1.71 2.50 268.96 0.354 0.338 0.000 0.442
F7 N1 APARTMENT 1.71 2.50 268.96 0.354 0.204 0.000 0.440
F7 N2 APARTMENT 1.71 2.50 268.97 0.354 0.204 0.000 0.440
F7 S1 APARTMENT 1.71 2.50 268.96 0.354 0.204 0.000 0.486
F7 S2 APARTMENT 1.71 2.50 268.97 0.354 0.204 0.000 0.486
F8 SW APARTMENT 1.71 2.50 268.96 0.354 0.354 0.000 0.505
F8 NW APARTMENT 1.71 2.50 268.96 0.354 0.354 0.000 0.458
F8 SE APARTMENT 1.71 2.50 268.96 0.354 0.354 0.000 0.505
F8 NE APARTMENT 1.71 2.50 268.96 0.354 0.354 0.000 0.458
F8 N1 APARTMENT 1.71 2.50 268.96 0.354 0.213 0.000 0.455
F8 N2 APARTMENT 1.71 2.50 268.97 0.354 0.213 0.000 0.455
F8 S1 APARTMENT 1.71 2.50 268.96 0.354 0.214 0.000 0.503
F8 S2 APARTMENT 1.71 2.50 268.97 0.354 0.214 0.000 0.503
F9 SW APARTMENT 1.71 2.50 268.96 0.354 0.369 0.000 0.522
F9 NW APARTMENT 1.71 2.50 268.96 0.354 0.369 0.000 0.473
F9 SE APARTMENT 1.71 2.50 268.96 0.354 0.369 0.000 0.522
F9 NE APARTMENT 1.71 2.50 268.96 0.354 0.369 0.000 0.473
F9 N1 APARTMENT 1.71 2.50 268.96 0.354 0.222 0.000 0.470
F9 N2 APARTMENT 1.71 2.50 268.97 0.354 0.222 0.000 0.470
F9 S1 APARTMENT 1.71 2.50 268.96 0.354 0.223 0.000 0.520
F9 S2 APARTMENT 1.71 2.50 268.97 0.354 0.223 0.000 0.521
T SW APARTMENT 1.71 2.50 268.96 0.354 0.383 0.000 0.534
T NW APARTMENT 1.71 2.50 268.96 0.354 0.383 0.000 0.482
T SE APARTMENT 1.71 2.50 268.96 0.354 0.383 0.000 0.534
T NE APARTMENT 1.71 2.50 268.96 0.354 0.383 0.000 0.483
T N1 APARTMENT 1.71 2.50 268.96 0.354 0.231 0.000 0.480
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.231 0.000 0.480
T S1 APARTMENT 1.71 2.50 268.96 0.354 0.231 0.000 0.532
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.231 0.000 0.532
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 606.47 19230.90 01-JAN-00:15 19230.90 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1349.73 19611.43 15-APR-02:45 197668.55 09-DEC-02:00
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
ElectricityPurchased:Plant 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
Cogeneration:ElectricityPurchased 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
ElectricityNet:Plant 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
Cogeneration:ElectricityNet 3134.31 57171.91 15-APR-02:45 238392.13 09-DEC-02:00
ExteriorLights:Electricity 168.36 0.00 01-JAN-08:00 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.36 0.00 01-JAN-08:00 10720.10 01-JAN-00:15
General:Fans:Electricity 606.47 19230.90 01-JAN-00:15 19230.90 01-JAN-00:15
Cooling:Electricity 296.90 0.00 01-JAN-00:15 81933.32 04-AUG-15:45
Heating:Electricity 425.54 0.00 18-MAR-15:15 178038.21 09-DEC-02:00
Electricity:Plant 68.72 36.93 19-MAR-16:15 5151.48 26-JUL-14:45
HeatRejection:Electricity 13.06 0.00 01-JAN-00:15 3346.48 26-JUL-14:45
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 55.66 36.93 19-MAR-16:15 1805.00 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 2856.00 9260.51 19-MAR-22:30 408138.57 09-DEC-08:30
Gas:Plant 2856.00 9260.51 19-MAR-22:30 408138.57 09-DEC-08:30
WaterSystems:Gas 1295.71 9260.51 01-JAN-00:15 93795.20 17-FEB-08:00
Water Heater:WaterSystems:Gas 1295.71 9260.51 01-JAN-00:15 93795.20 17-FEB-08:00
Heating:Gas 1560.29 0.00 24-FEB-13:45 322077.71 19-JAN-05:00
Boiler:Heating:Gas 1560.29 0.00 24-FEB-13:45 322077.71 19-JAN-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 1265.28 0.00 01-JAN-00:15 399879.37 03-AUG-08:30
PlantLoopCoolingDemand:HVAC 1265.28 0.00 01-JAN-00:15 399879.37 03-AUG-08:30
CoolingCoils:PlantLoopCoolingDemand 1265.28 0.00 01-JAN-00:15 399879.37 03-AUG-08:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 5588.99 0.00 01-JAN-02:15 0.00 25-JUN-17:15
Water:Plant 5588.99 0.00 01-JAN-02:15 0.00 25-JUN-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 5588.99 0.00 01-JAN-02:15 0.00 25-JUN-17:15
MainsWater:Plant 5588.99 0.00 01-JAN-02:15 0.00 25-JUN-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 810.48 0.00 01-JAN-00:15 0.00 04-AUG-15:00
HeatRejection:MainsWater 810.48 0.00 01-JAN-00:15 0.00 04-AUG-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 2271.56 527.80 21-AUG-01:15 317900.47 09-DEC-09:00
PlantLoopHeatingDemand:Plant 985.92 527.80 21-AUG-01:15 67608.03 19-FEB-07:45
WaterSystems:PlantLoopHeatingDemand 985.92 527.80 21-AUG-01:15 67608.03 19-FEB-07:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 6673.41 5501.37 10-MAY-02:00 1071846.38 09-DEC-09:00
EnergyTransfer:Building 1774.84 2747.22 20-MAY-16:45 345641.36 09-DEC-02:00
EnergyTransfer:Zone:G SW APARTMENT 19.53 0.06 25-OCT-11:45 3665.84 09-DEC-09:00
Heating:EnergyTransfer 1055.06 0.00 18-MAR-17:30 345641.36 09-DEC-02:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 12.31 0.00 02-JAN-12:15 3665.84 09-DEC-09:00
Cooling:EnergyTransfer 719.78 0.00 01-JAN-00:15 189500.83 02-SEP-16:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 7.22 0.00 01-JAN-00:15 2763.29 07-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 21.29 0.03 30-SEP-09:15 3715.66 09-DEC-09:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 16.20 0.00 20-FEB-16:15 3715.66 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 5.09 0.00 01-JAN-00:15 2239.15 25-JUN-17:30
EnergyTransfer:Zone:OFFICE 23.62 0.12 24-MAR-00:45 3776.49 09-DEC-09:00
Heating:EnergyTransfer:Zone:OFFICE 11.74 0.00 02-JAN-09:45 3776.49 09-DEC-09:00
Cooling:EnergyTransfer:Zone:OFFICE 11.88 0.00 01-JAN-00:15 3457.63 07-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 21.05 0.02 11-OCT-04:15 3699.46 09-DEC-09:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 16.09 0.00 24-FEB-10:45 3699.46 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 4.95 0.00 01-JAN-00:15 1681.12 02-JUL-09:45
EnergyTransfer:Zone:G N1 APARTMENT 13.55 0.02 17-JUN-21:00 2323.47 09-DEC-09:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 9.32 0.00 24-FEB-17:15 2323.47 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.23 0.00 01-JAN-00:15 1299.37 02-JUL-19:15
EnergyTransfer:Zone:G N2 APARTMENT 13.54 0.03 25-OCT-08:45 2323.24 09-DEC-09:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 9.33 0.00 24-FEB-17:15 2323.24 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.22 0.00 01-JAN-00:15 1299.64 02-JUL-19:15
EnergyTransfer:Zone:G S1 APARTMENT 12.63 0.00 12-MAY-19:15 2261.96 09-DEC-09:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 5.73 0.00 02-JAN-10:15 2261.96 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 6.90 0.00 01-JAN-00:15 1883.55 05-SEP-12:30
EnergyTransfer:Zone:G S2 APARTMENT 12.63 0.01 04-MAY-23:15 2256.40 09-DEC-09:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 5.63 0.00 02-JAN-10:15 2256.40 09-DEC-09:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.01 0.00 01-JAN-00:15 1924.30 05-SEP-12:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 23.10 0.03 07-NOV-15:15 4273.59 09-DEC-02:00
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 11.56 0.00 02-JAN-12:15 4273.59 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 11.55 0.00 01-JAN-00:15 3495.32 07-SEP-15:15
EnergyTransfer:Zone:F2 NW APARTMENT 24.39 0.02 23-MAR-18:45 4391.56 09-DEC-02:00
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 16.27 0.00 20-FEB-15:30 4391.56 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 8.12 0.00 01-JAN-00:15 2948.92 25-JUN-17:30
EnergyTransfer:Zone:F2 SE APARTMENT 23.13 0.09 14-APR-10:15 4207.18 09-DEC-02:00
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 11.03 0.00 02-JAN-10:45 4207.18 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 12.10 0.00 01-JAN-00:15 3245.27 07-SEP-13:30
EnergyTransfer:Zone:F2 NE APARTMENT 24.25 0.02 20-MAR-03:30 4371.81 09-DEC-02:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 16.11 0.00 24-FEB-09:45 4371.81 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 8.14 0.00 01-JAN-00:15 2189.96 26-JUN-17:30
EnergyTransfer:Zone:F2 N1 APARTMENT 14.60 0.04 03-APR-17:45 2534.92 23-MAR-14:00
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 7.77 0.00 11-JAN-18:30 2534.92 23-MAR-14:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 6.82 0.00 01-JAN-00:15 1692.36 28-JUN-19:15
EnergyTransfer:Zone:F2 N2 APARTMENT 14.59 0.02 21-MAY-14:00 2531.99 09-DEC-02:00
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 7.77 0.00 11-JAN-18:30 2531.99 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 6.82 0.00 01-JAN-00:15 1681.34 28-JUN-19:15
EnergyTransfer:Zone:F2 S1 APARTMENT 15.26 0.03 22-JUN-10:30 2430.96 05-SEP-12:30
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 4.28 0.00 02-JAN-10:00 2386.30 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 10.98 0.00 01-JAN-00:15 2430.96 05-SEP-12:30
EnergyTransfer:Zone:F2 S2 APARTMENT 15.29 0.00 11-JUL-16:45 2449.40 05-SEP-12:30
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 4.26 0.00 02-JAN-10:00 2382.30 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 11.03 0.00 01-JAN-00:15 2449.40 05-SEP-12:30
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 24.14 0.00 24-APR-01:45 4654.68 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 12.09 0.00 02-JAN-12:30 4654.68 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 12.05 0.00 01-JAN-00:15 3515.01 07-SEP-15:15
EnergyTransfer:Zone:F3 NW APARTMENT 25.48 0.01 10-APR-09:30 4792.26 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 16.88 0.00 20-FEB-15:30 4792.26 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 8.60 0.00 01-JAN-00:15 2994.34 25-JUN-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 24.01 0.09 25-FEB-04:15 4628.56 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 11.92 0.00 02-JAN-12:15 4628.56 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 12.09 0.00 01-JAN-00:15 3287.80 09-SEP-11:30
EnergyTransfer:Zone:F3 NE APARTMENT 25.34 0.02 26-MAR-03:00 4770.96 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 16.73 0.00 24-FEB-09:45 4770.96 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 8.61 0.00 01-JAN-00:15 2263.50 28-JUN-19:00
EnergyTransfer:Zone:F3 N1 APARTMENT 15.23 0.03 22-APR-09:45 2954.71 23-MAR-14:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 7.79 0.00 11-JAN-18:15 2954.71 23-MAR-14:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 7.44 0.00 01-JAN-00:15 1763.71 31-MAY-18:30
EnergyTransfer:Zone:F3 N2 APARTMENT 15.22 0.02 24-AUG-11:30 2949.47 23-MAR-14:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 7.79 0.00 11-JAN-18:15 2949.47 23-MAR-14:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 7.43 0.00 01-JAN-00:15 1754.67 31-MAY-18:30
EnergyTransfer:Zone:F3 S1 APARTMENT 16.10 0.01 16-JAN-18:15 2562.04 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 4.29 0.00 01-JAN-10:30 2562.04 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 11.81 0.00 01-JAN-00:15 2527.52 05-SEP-12:30
EnergyTransfer:Zone:F3 S2 APARTMENT 16.11 0.19 11-MAY-15:30 2561.40 09-DEC-02:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 4.29 0.00 01-JAN-10:30 2561.40 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 11.82 0.00 01-JAN-00:15 2542.34 05-SEP-12:30
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 24.96 0.03 11-JUL-02:00 5003.71 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 12.99 0.00 02-JAN-13:15 5003.71 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 11.97 0.00 01-JAN-00:15 3553.79 02-SEP-15:00
EnergyTransfer:Zone:F4 NW APARTMENT 26.49 0.02 24-MAR-12:30 5147.43 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 17.88 0.00 20-FEB-15:45 5147.43 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 8.61 0.00 01-JAN-00:15 3021.30 25-JUN-17:30
EnergyTransfer:Zone:F4 SE APARTMENT 24.81 0.05 23-AUG-09:30 4984.05 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 12.88 0.00 02-JAN-12:30 4984.05 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 11.93 0.00 01-JAN-00:15 3307.17 09-SEP-11:30
EnergyTransfer:Zone:F4 NE APARTMENT 26.34 0.04 31-MAR-20:30 5125.10 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 17.72 0.00 24-FEB-10:00 5125.10 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 8.62 0.00 01-JAN-00:15 2305.49 28-JUN-19:00
EnergyTransfer:Zone:F4 N1 APARTMENT 15.77 0.00 03-JUL-05:45 3138.27 23-MAR-14:15
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 8.23 0.00 11-JAN-18:15 3138.27 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 7.54 0.00 01-JAN-00:15 1805.01 31-MAY-18:30
EnergyTransfer:Zone:F4 N2 APARTMENT 15.76 0.00 17-APR-15:45 3134.67 23-MAR-14:15
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 8.24 0.00 11-JAN-18:15 3134.67 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 7.53 0.00 01-JAN-00:15 1789.77 31-MAY-18:30
EnergyTransfer:Zone:F4 S1 APARTMENT 16.51 0.01 22-JUN-10:15 2757.76 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 4.65 0.00 01-JAN-10:30 2757.76 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 11.86 0.00 01-JAN-00:15 2561.76 05-SEP-12:30
EnergyTransfer:Zone:F4 S2 APARTMENT 16.50 0.01 06-JUN-15:45 2758.01 09-DEC-02:00
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 4.65 0.00 01-JAN-10:30 2758.01 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 11.85 0.00 01-JAN-00:15 2576.02 05-SEP-12:30
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 25.64 0.02 02-NOV-11:30 5282.59 09-DEC-02:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 13.68 0.00 02-JAN-13:15 5282.59 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 11.96 0.00 01-JAN-00:15 3614.00 02-SEP-15:00
EnergyTransfer:Zone:M NW APARTMENT 27.27 0.00 04-NOV-12:15 5426.22 09-DEC-02:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 18.58 0.00 20-FEB-16:15 5426.22 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 8.69 0.00 01-JAN-00:15 3064.45 25-JUN-17:30
EnergyTransfer:Zone:M SE APARTMENT 25.47 0.03 19-MAR-20:45 5263.35 09-DEC-02:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 13.57 0.00 02-JAN-13:00 5263.35 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 11.90 0.00 01-JAN-00:15 3358.52 09-SEP-11:30
EnergyTransfer:Zone:M NE APARTMENT 27.11 0.10 11-SEP-06:45 5403.18 09-DEC-02:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 18.41 0.00 24-FEB-10:00 5403.18 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 8.70 0.00 01-JAN-00:15 2360.09 28-JUN-19:00
EnergyTransfer:Zone:M N1 APARTMENT 16.21 0.00 19-SEP-15:30 3421.96 23-MAR-14:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 8.52 0.00 11-JAN-18:15 3421.96 23-MAR-14:15
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 7.69 0.00 01-JAN-00:15 1851.57 31-MAY-18:30
EnergyTransfer:Zone:M N2 APARTMENT 16.20 0.04 07-JUN-10:30 3418.73 23-MAR-14:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 8.52 0.00 11-JAN-18:15 3418.73 23-MAR-14:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 7.68 0.00 01-JAN-00:15 1836.37 31-MAY-18:30
EnergyTransfer:Zone:M S1 APARTMENT 16.84 0.02 01-JUL-05:45 2915.10 09-DEC-02:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 4.92 0.00 01-JAN-10:30 2915.10 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 11.92 0.00 01-JAN-00:15 2598.66 05-SEP-12:30
EnergyTransfer:Zone:M S2 APARTMENT 16.83 0.06 18-APR-06:00 2915.53 09-DEC-02:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 4.92 0.00 01-JAN-10:30 2915.53 09-DEC-02:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 11.91 0.00 01-JAN-00:15 2612.85 05-SEP-12:30
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 26.17 0.08 08-APR-09:45 5585.96 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 14.93 0.00 02-JAN-13:30 5585.96 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 11.24 0.00 01-JAN-00:15 3599.38 02-SEP-15:00
EnergyTransfer:Zone:F6 NW APARTMENT 28.19 0.03 11-APR-13:15 5728.73 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 20.02 0.00 24-FEB-14:45 5728.73 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 8.17 0.00 01-JAN-00:15 3031.92 25-JUN-17:30
EnergyTransfer:Zone:F6 SE APARTMENT 25.99 0.03 21-OCT-09:15 5566.25 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 14.82 0.00 02-JAN-13:45 5566.25 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 11.17 0.00 01-JAN-00:15 3334.87 09-SEP-11:30
EnergyTransfer:Zone:F6 NE APARTMENT 28.00 0.02 28-OCT-14:30 5705.13 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 19.84 0.00 24-FEB-20:00 5705.13 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 8.17 0.00 01-JAN-00:15 2344.86 28-JUN-19:00
EnergyTransfer:Zone:F6 N1 APARTMENT 16.59 0.02 17-APR-18:15 3763.71 23-MAR-14:15
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 9.43 0.00 11-JAN-18:15 3763.71 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 7.15 0.00 01-JAN-00:15 1823.01 31-MAY-18:30
EnergyTransfer:Zone:F6 N2 APARTMENT 16.58 0.01 17-APR-15:45 3760.72 23-MAR-14:15
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 9.44 0.00 11-JAN-18:15 3760.72 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 7.14 0.00 01-JAN-00:15 1807.92 31-MAY-18:30
EnergyTransfer:Zone:F6 S1 APARTMENT 16.71 0.02 24-MAY-08:30 3112.59 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 5.59 0.00 02-JAN-10:15 3112.59 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 11.12 0.00 01-JAN-00:15 2556.36 05-SEP-12:30
EnergyTransfer:Zone:F6 S2 APARTMENT 16.70 0.09 14-MAR-17:45 3113.05 09-DEC-02:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 5.59 0.00 02-JAN-10:15 3113.05 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 11.11 0.00 01-JAN-00:15 2570.70 05-SEP-12:30
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 26.73 0.03 23-APR-20:30 5839.37 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 15.93 0.00 02-JAN-13:45 5839.37 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 10.80 0.00 01-JAN-00:15 3604.53 02-SEP-15:00
EnergyTransfer:Zone:F7 NW APARTMENT 28.97 0.05 09-OCT-15:15 5978.90 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 21.10 0.00 24-FEB-14:45 5978.90 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 7.87 0.00 01-JAN-00:15 3025.67 25-JUN-17:30
EnergyTransfer:Zone:F7 SE APARTMENT 26.54 0.08 19-MAR-24:00 5819.15 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 15.81 0.00 03-JAN-11:00 5819.15 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 10.74 0.00 01-JAN-00:15 3335.74 09-SEP-11:30
EnergyTransfer:Zone:F7 NE APARTMENT 28.77 0.03 23-SEP-23:30 5954.86 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 20.91 0.00 18-MAR-14:30 5954.86 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 7.85 0.00 01-JAN-00:15 2350.07 28-JUN-19:00
EnergyTransfer:Zone:F7 N1 APARTMENT 16.95 0.04 24-AUG-15:45 4049.47 23-MAR-14:15
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 10.11 0.00 11-JAN-18:30 4049.47 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 6.85 0.00 01-JAN-00:15 1819.16 31-MAY-18:30
EnergyTransfer:Zone:F7 N2 APARTMENT 16.95 0.01 16-JUN-08:15 4046.07 23-MAR-14:15
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 10.11 0.00 11-JAN-18:30 4046.07 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 6.84 0.00 01-JAN-00:15 1804.15 31-MAY-18:30
EnergyTransfer:Zone:F7 S1 APARTMENT 16.74 0.02 12-JUL-08:00 3275.17 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 6.12 0.00 02-JAN-10:30 3275.17 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 10.61 0.00 01-JAN-00:15 2534.02 05-SEP-12:30
EnergyTransfer:Zone:F7 S2 APARTMENT 16.74 0.04 12-JUL-08:00 3275.63 09-DEC-02:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 6.13 0.00 02-JAN-10:30 3275.63 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 10.61 0.00 01-JAN-00:15 2548.60 05-SEP-12:30
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 27.38 0.02 15-APR-05:45 6079.09 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 16.91 0.00 02-JAN-13:45 6079.09 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 10.47 0.00 01-JAN-00:15 3611.97 02-SEP-15:00
EnergyTransfer:Zone:F8 NW APARTMENT 29.82 0.03 11-MAY-24:00 6212.16 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 22.16 0.00 24-FEB-15:00 6212.16 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 7.67 0.00 01-JAN-00:15 3032.94 25-JUN-17:30
EnergyTransfer:Zone:F8 SE APARTMENT 27.19 0.03 01-OCT-23:00 6058.32 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 16.78 0.00 03-JAN-12:30 6058.32 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 10.41 0.00 01-JAN-00:15 3348.38 09-SEP-11:30
EnergyTransfer:Zone:F8 NE APARTMENT 29.60 0.02 08-NOV-23:45 6187.70 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 21.97 0.00 18-MAR-14:30 6187.70 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 7.63 0.00 01-JAN-00:15 2384.41 18-APR-15:30
EnergyTransfer:Zone:F8 N1 APARTMENT 17.44 0.05 22-JUN-10:30 4306.86 23-MAR-14:15
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 10.80 0.00 11-JAN-18:30 4306.86 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 6.64 0.00 01-JAN-00:15 1828.82 31-MAY-18:30
EnergyTransfer:Zone:F8 N2 APARTMENT 17.43 0.02 19-SEP-15:15 4303.60 23-MAR-14:15
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 10.80 0.00 11-JAN-18:30 4303.60 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 6.63 0.00 01-JAN-00:15 1813.91 31-MAY-18:30
EnergyTransfer:Zone:F8 S1 APARTMENT 16.90 0.01 20-MAY-15:30 3435.11 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 6.69 0.00 02-JAN-10:30 3435.11 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 10.22 0.00 01-JAN-00:15 2593.54 05-SEP-12:45
EnergyTransfer:Zone:F8 S2 APARTMENT 16.90 0.00 26-FEB-05:45 3435.53 09-DEC-02:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 6.69 0.00 02-JAN-10:30 3435.53 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 10.21 0.00 01-JAN-00:15 2605.63 05-SEP-12:45
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 29.09 0.00 09-NOV-08:45 6446.05 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 18.85 0.00 02-JAN-14:15 6446.05 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 10.24 0.00 01-JAN-00:15 3717.08 02-SEP-15:15
EnergyTransfer:Zone:F9 NW APARTMENT 31.86 0.02 04-JUN-13:00 6558.69 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 24.26 0.00 24-FEB-15:15 6558.69 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 7.61 0.00 01-JAN-00:15 3125.20 25-JUN-17:30
EnergyTransfer:Zone:F9 SE APARTMENT 28.86 0.02 11-JUL-23:45 6423.47 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 18.69 0.00 03-JAN-12:45 6423.47 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 10.16 0.00 01-JAN-00:15 3416.82 09-SEP-11:30
EnergyTransfer:Zone:F9 NE APARTMENT 31.58 0.02 27-SEP-20:30 6532.98 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 24.06 0.00 18-MAR-15:00 6532.98 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 7.52 0.00 01-JAN-00:15 2535.61 28-JUN-18:45
EnergyTransfer:Zone:F9 N1 APARTMENT 18.93 0.04 26-MAY-20:15 4571.38 23-MAR-14:15
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 12.43 0.00 11-JAN-18:45 4571.38 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 6.51 0.00 01-JAN-00:15 1912.57 31-MAY-18:30
EnergyTransfer:Zone:F9 N2 APARTMENT 18.93 0.09 04-MAY-24:00 4568.36 23-MAR-14:15
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 12.43 0.00 11-JAN-18:45 4568.36 23-MAR-14:15
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 6.50 0.00 01-JAN-00:15 1897.55 31-MAY-18:30
EnergyTransfer:Zone:F9 S1 APARTMENT 17.83 0.10 04-SEP-09:45 3721.31 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 8.02 0.00 02-JAN-11:00 3721.31 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 9.81 0.00 01-JAN-00:15 2612.24 05-SEP-12:45
EnergyTransfer:Zone:F9 S2 APARTMENT 17.83 0.02 19-JUN-11:15 3721.59 09-DEC-02:00
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 8.02 0.00 02-JAN-11:00 3721.59 09-DEC-02:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 9.80 0.00 01-JAN-00:15 2628.41 05-SEP-12:45
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 37.19 0.01 17-MAY-09:15 7499.10 09-DEC-02:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 26.86 0.00 02-JAN-14:00 7499.10 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 10.34 0.00 01-JAN-00:15 4418.59 07-SEP-14:30
EnergyTransfer:Zone:T NW APARTMENT 39.43 0.04 30-APR-06:45 7573.46 09-DEC-02:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 31.58 0.00 24-FEB-14:30 7573.46 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 7.85 0.00 01-JAN-00:15 3686.57 05-JUL-17:15
EnergyTransfer:Zone:T SE APARTMENT 36.59 0.01 02-JUN-22:30 7471.78 09-DEC-02:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 26.56 0.00 03-JAN-12:45 7471.78 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 10.03 0.00 01-JAN-00:15 4130.36 07-SEP-13:15
EnergyTransfer:Zone:T NE APARTMENT 38.81 0.02 09-OCT-15:45 7545.12 09-DEC-02:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 31.25 0.00 18-MAR-13:15 7545.12 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 7.57 0.00 01-JAN-00:15 2978.80 28-JUN-10:00
EnergyTransfer:Zone:T N1 APARTMENT 25.57 0.01 22-APR-20:15 4838.36 09-DEC-02:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 19.12 0.00 24-FEB-14:45 4838.36 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 6.46 0.00 01-JAN-00:15 2291.46 11-AUG-15:00
EnergyTransfer:Zone:T N2 APARTMENT 25.58 0.01 07-MAY-05:15 4837.88 09-DEC-02:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 19.12 0.00 24-FEB-14:45 4837.88 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 6.45 0.00 01-JAN-00:15 2289.40 11-AUG-15:00
EnergyTransfer:Zone:T S1 APARTMENT 23.98 0.00 12-JUL-00:30 4751.18 09-DEC-02:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 14.80 0.00 02-JAN-11:15 4751.18 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 9.18 0.00 01-JAN-00:15 3370.71 07-SEP-13:30
EnergyTransfer:Zone:T S2 APARTMENT 23.99 0.01 12-JUL-01:15 4750.86 09-DEC-02:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 14.81 0.00 02-JAN-11:15 4750.86 09-DEC-02:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 9.18 0.00 01-JAN-00:15 3381.41 07-SEP-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 2233.65 527.80 21-AUG-01:15 317689.55 19-JAN-06:15
WaterSystems:EnergyTransfer 985.91 527.80 21-AUG-01:15 67601.12 19-FEB-07:45
sub cat:WaterSystems:EnergyTransfer 985.91 527.80 21-AUG-01:15 67601.12 19-FEB-07:45
EnergyTransfer:HVAC 2664.92 0.00 19-MAR-16:15 436302.53 09-DEC-02:00
CoolingCoils:EnergyTransfer 992.40 0.00 01-JAN-00:15 319713.71 03-AUG-08:30
HeatingCoils:EnergyTransfer 1672.52 0.00 18-MAR-15:15 436302.53 09-DEC-02:00
PlantLoopHeatingDemand:HVAC 1285.65 0.00 18-MAR-15:15 259002.82 19-JAN-05:00
HeatingCoils:PlantLoopHeatingDemand 1285.65 0.00 18-MAR-15:15 259002.82 19-JAN-05:00
Boilers:EnergyTransfer 1247.75 0.00 24-FEB-13:45 257662.17 19-JAN-05:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 12.312 -7.221 0.000 0.000 3.874 2.413 12.213 17.729 0.000 0.182 0.000 0.000 -14.709 0.000 -9.900 -16.893
G NW APARTMENT 16.197 -5.093 0.000 0.000 3.896 2.413 12.213 8.901 0.000 0.174 0.000 0.000 -15.635 0.000 -9.575 -13.490
OFFICE 11.742 -11.878 0.000 0.000 0.538 21.954 7.547 17.321 0.000 0.072 0.000 0.000 -14.633 0.000 -6.937 -25.726
G NE APARTMENT 16.092 -4.954 0.000 0.000 3.904 2.413 12.213 8.548 0.000 0.174 0.000 0.000 -15.424 0.000 -9.592 -13.372
G N1 APARTMENT 9.323 -4.230 0.000 0.000 3.906 2.413 12.213 3.146 0.000 0.146 0.000 0.000 -9.891 0.000 -6.670 -10.355
G N2 APARTMENT 9.326 -4.218 0.000 0.000 3.906 2.413 12.213 3.144 0.000 0.146 0.000 0.000 -9.889 0.000 -6.672 -10.369
G S1 APARTMENT 5.725 -6.902 0.000 0.000 3.874 2.413 12.213 12.087 0.000 0.153 0.000 0.000 -8.969 0.000 -7.017 -13.578
G S2 APARTMENT 5.628 -7.005 0.000 0.000 3.872 2.413 12.213 12.075 0.000 0.153 0.000 0.000 -8.976 0.000 -7.047 -13.326
F2 SW APARTMENT 11.556 -11.548 0.000 0.000 3.819 2.413 12.213 17.039 0.000 0.243 0.000 0.000 -15.613 0.000 -13.819 -6.302
F2 NW APARTMENT 16.268 -8.119 0.000 0.000 3.857 2.413 12.213 8.470 0.000 0.229 0.000 0.000 -16.541 0.000 -13.323 -5.468
F2 SE APARTMENT 11.025 -12.102 0.000 0.000 3.818 2.413 12.213 16.677 0.000 0.242 0.000 0.000 -15.456 0.000 -13.890 -4.940
F2 NE APARTMENT 16.110 -8.142 0.000 0.000 3.870 2.413 12.213 8.134 0.000 0.227 0.000 0.000 -16.283 0.000 -13.291 -5.251
F2 N1 APARTMENT 7.772 -6.824 0.000 0.000 3.865 2.413 12.213 2.925 0.000 0.187 0.000 0.000 -10.511 0.000 -9.186 -2.853
F2 N2 APARTMENT 7.772 -6.817 0.000 0.000 3.866 2.413 12.213 2.924 0.000 0.187 0.000 0.000 -10.508 0.000 -9.184 -2.866
F2 S1 APARTMENT 4.284 -10.979 0.000 0.000 3.811 2.413 12.213 11.649 0.000 0.201 0.000 0.000 -9.521 0.000 -9.723 -4.347
F2 S2 APARTMENT 4.264 -11.030 0.000 0.000 3.810 2.413 12.213 11.645 0.000 0.201 0.000 0.000 -9.524 0.000 -9.733 -4.258
F3 SW APARTMENT 12.085 -12.052 0.000 0.000 3.814 2.413 12.213 16.772 0.000 0.326 0.000 0.000 -15.906 0.000 -16.005 -3.659
F3 NW APARTMENT 16.883 -8.598 0.000 0.000 3.852 2.413 12.213 8.321 0.000 0.303 0.000 0.000 -16.870 0.000 -15.450 -3.067
F3 SE APARTMENT 11.918 -12.089 0.000 0.000 3.819 2.413 12.213 16.451 0.000 0.323 0.000 0.000 -15.687 0.000 -16.016 -3.345
F3 NE APARTMENT 16.730 -8.612 0.000 0.000 3.864 2.413 12.213 7.992 0.000 0.299 0.000 0.000 -16.596 0.000 -15.412 -2.891
F3 N1 APARTMENT 7.785 -7.441 0.000 0.000 3.856 2.413 12.213 2.858 0.000 0.252 0.000 0.000 -10.732 0.000 -10.598 -0.606
F3 N2 APARTMENT 7.788 -7.431 0.000 0.000 3.857 2.413 12.213 2.857 0.000 0.252 0.000 0.000 -10.728 0.000 -10.595 -0.625
F3 S1 APARTMENT 4.290 -11.809 0.000 0.000 3.800 2.413 12.213 11.472 0.000 0.273 0.000 0.000 -9.716 0.000 -11.198 -1.738
F3 S2 APARTMENT 4.290 -11.816 0.000 0.000 3.800 2.413 12.213 11.470 0.000 0.273 0.000 0.000 -9.715 0.000 -11.202 -1.725
F4 SW APARTMENT 12.989 -11.974 0.000 0.000 3.815 2.413 12.213 16.613 0.000 0.355 0.000 0.000 -16.063 0.000 -17.471 -2.890
F4 NW APARTMENT 17.879 -8.607 0.000 0.000 3.852 2.413 12.213 8.238 0.000 0.329 0.000 0.000 -17.060 0.000 -16.895 -2.362
F4 SE APARTMENT 12.879 -11.927 0.000 0.000 3.821 2.413 12.213 16.303 0.000 0.351 0.000 0.000 -15.827 0.000 -17.470 -2.756
F4 NE APARTMENT 17.722 -8.620 0.000 0.000 3.864 2.413 12.213 7.913 0.000 0.324 0.000 0.000 -16.778 0.000 -16.854 -2.197
F4 N1 APARTMENT 8.234 -7.536 0.000 0.000 3.854 2.413 12.213 2.824 0.000 0.272 0.085 0.000 -10.860 0.000 -11.499 -0.000
F4 N2 APARTMENT 8.235 -7.525 0.000 0.000 3.855 2.413 12.213 2.823 0.000 0.271 0.066 0.000 -10.855 0.000 -11.496 -0.000
F4 S1 APARTMENT 4.651 -11.858 0.000 0.000 3.799 2.413 12.213 11.366 0.000 0.295 0.000 0.000 -9.817 0.000 -12.119 -0.943
F4 S2 APARTMENT 4.651 -11.848 0.000 0.000 3.799 2.413 12.213 11.365 0.000 0.295 0.001 0.000 -9.815 0.000 -12.121 -0.952
M SW APARTMENT 13.675 -11.960 0.000 0.000 3.817 2.413 12.213 16.489 0.000 0.377 0.000 0.000 -16.190 0.000 -18.813 -2.021
M NW APARTMENT 18.578 -8.693 0.000 0.000 3.853 2.413 12.213 8.173 0.000 0.350 0.000 0.000 -17.214 0.000 -18.207 -1.466
M SE APARTMENT 13.570 -11.899 0.000 0.000 3.823 2.413 12.213 16.184 0.000 0.373 0.000 0.000 -15.947 0.000 -18.810 -1.921
M NE APARTMENT 18.409 -8.704 0.000 0.000 3.864 2.413 12.213 7.851 0.000 0.344 0.000 0.000 -16.926 0.000 -18.163 -1.301
M N1 APARTMENT 8.518 -7.687 0.000 0.000 3.853 2.413 12.213 2.797 0.000 0.287 0.925 0.000 -10.962 0.000 -12.358 -0.000
M N2 APARTMENT 8.519 -7.676 0.000 0.000 3.854 2.413 12.213 2.797 0.000 0.287 0.905 0.000 -10.958 0.000 -12.355 -0.000
M S1 APARTMENT 4.919 -11.923 0.000 0.000 3.799 2.413 12.213 11.285 0.000 0.312 0.000 0.000 -9.897 0.000 -13.008 -0.113
M S2 APARTMENT 4.921 -11.911 0.000 0.000 3.800 2.413 12.213 11.284 0.000 0.312 0.000 0.000 -9.895 0.000 -13.010 -0.128
F6 SW APARTMENT 14.931 -11.241 0.000 0.000 3.825 2.413 12.213 16.426 0.000 0.395 0.000 0.000 -16.225 0.000 -19.899 -2.838
F6 NW APARTMENT 20.018 -8.167 0.000 0.000 3.860 2.413 12.213 8.152 0.000 0.367 0.000 0.000 -17.271 0.000 -19.266 -2.319
F6 SE APARTMENT 14.818 -11.174 0.000 0.000 3.832 2.413 12.213 16.125 0.000 0.391 0.000 0.000 -15.977 0.000 -19.898 -2.743
F6 NE APARTMENT 19.836 -8.165 0.000 0.000 3.871 2.413 12.213 7.833 0.000 0.360 0.000 0.000 -16.980 0.000 -19.223 -2.158
F6 N1 APARTMENT 9.434 -7.152 0.000 0.000 3.861 2.413 12.213 2.796 0.000 0.300 0.153 0.000 -10.996 0.000 -13.021 -0.000
F6 N2 APARTMENT 9.436 -7.143 0.000 0.000 3.862 2.413 12.213 2.795 0.000 0.299 0.134 0.000 -10.992 0.000 -13.018 -0.000
F6 S1 APARTMENT 5.589 -11.118 0.000 0.000 3.808 2.413 12.213 11.243 0.000 0.326 0.001 0.000 -9.915 0.000 -13.702 -0.857
F6 S2 APARTMENT 5.592 -11.105 0.000 0.000 3.808 2.413 12.213 11.242 0.000 0.326 0.001 0.000 -9.913 0.000 -13.703 -0.873
F7 SW APARTMENT 15.926 -10.802 0.000 0.000 3.831 2.413 12.213 16.365 0.000 0.411 0.000 0.000 -16.267 0.000 -20.858 -3.231
F7 NW APARTMENT 21.100 -7.868 0.000 0.000 3.865 2.413 12.213 8.129 0.000 0.380 0.000 0.000 -17.334 0.000 -20.203 -2.696
F7 SE APARTMENT 15.805 -10.735 0.000 0.000 3.838 2.413 12.213 16.067 0.000 0.406 0.000 0.000 -16.016 0.000 -20.858 -3.133
F7 NE APARTMENT 20.913 -7.854 0.000 0.000 3.876 2.413 12.213 7.811 0.000 0.374 0.000 0.000 -17.041 0.000 -20.164 -2.541
F7 N1 APARTMENT 10.105 -6.848 0.000 0.000 3.866 2.413 12.213 2.791 0.000 0.310 0.000 0.000 -11.033 0.000 -13.610 -0.207
F7 N2 APARTMENT 10.110 -6.843 0.000 0.000 3.867 2.413 12.213 2.790 0.000 0.310 0.000 0.000 -11.029 0.000 -13.607 -0.223
F7 S1 APARTMENT 6.121 -10.615 0.000 0.000 3.815 2.413 12.213 11.203 0.000 0.338 0.000 0.000 -9.938 0.000 -14.314 -1.235
F7 S2 APARTMENT 6.129 -10.606 0.000 0.000 3.815 2.413 12.213 11.202 0.000 0.338 0.000 0.000 -9.936 0.000 -14.316 -1.252
F8 SW APARTMENT 16.909 -10.472 0.000 0.000 3.837 2.413 12.213 16.313 0.000 0.428 0.000 0.000 -16.304 0.000 -21.748 -3.588
F8 NW APARTMENT 22.156 -7.666 0.000 0.000 3.870 2.413 12.213 8.107 0.000 0.396 0.000 0.000 -17.389 0.000 -21.074 -3.025
F8 SE APARTMENT 16.783 -10.408 0.000 0.000 3.844 2.413 12.213 16.017 0.000 0.423 0.000 0.000 -16.050 0.000 -21.749 -3.485
F8 NE APARTMENT 21.970 -7.627 0.000 0.000 3.880 2.413 12.213 7.789 0.000 0.390 0.000 0.000 -17.096 0.000 -21.045 -2.886
F8 N1 APARTMENT 10.799 -6.639 0.000 0.000 3.871 2.413 12.213 2.786 0.000 0.322 0.000 0.000 -11.066 0.000 -14.167 -0.532
F8 N2 APARTMENT 10.799 -6.630 0.000 0.000 3.872 2.413 12.213 2.785 0.000 0.322 0.000 0.000 -11.062 0.000 -14.165 -0.546
F8 S1 APARTMENT 6.688 -10.217 0.000 0.000 3.821 2.413 12.213 11.169 0.000 0.351 0.000 0.000 -9.957 0.000 -14.890 -1.592
F8 S2 APARTMENT 6.693 -10.207 0.000 0.000 3.821 2.413 12.213 11.168 0.000 0.351 0.000 0.000 -9.954 0.000 -14.892 -1.607
F9 SW APARTMENT 18.849 -10.236 0.000 0.000 3.844 2.413 12.213 16.286 0.000 0.449 0.000 0.000 -16.295 0.000 -22.539 -4.984
F9 NW APARTMENT 24.257 -7.607 0.000 0.000 3.874 2.413 12.213 8.097 0.000 0.415 0.000 0.000 -17.400 0.000 -21.860 -4.403
F9 SE APARTMENT 18.694 -10.161 0.000 0.000 3.851 2.413 12.213 15.992 0.000 0.444 0.000 0.000 -16.040 0.000 -22.545 -4.861
F9 NE APARTMENT 24.057 -7.523 0.000 0.000 3.883 2.413 12.213 7.779 0.000 0.411 0.000 0.000 -17.109 0.000 -21.845 -4.279
F9 N1 APARTMENT 12.429 -6.505 0.000 0.000 3.876 2.413 12.213 2.786 0.000 0.340 0.000 0.000 -11.067 0.000 -14.668 -1.816
F9 N2 APARTMENT 12.431 -6.498 0.000 0.000 3.876 2.413 12.213 2.785 0.000 0.339 0.000 0.000 -11.064 0.000 -14.666 -1.829
F9 S1 APARTMENT 8.020 -9.813 0.000 0.000 3.829 2.413 12.213 11.154 0.000 0.370 0.000 0.000 -9.944 0.000 -15.393 -2.848
F9 S2 APARTMENT 8.024 -9.803 0.000 0.000 3.830 2.413 12.213 11.152 0.000 0.370 0.000 0.000 -9.942 0.000 -15.395 -2.861
T SW APARTMENT 26.855 -10.339 0.000 0.000 3.871 2.413 12.213 16.097 0.000 0.459 0.000 0.000 -15.751 0.000 -23.156 -12.662
T NW APARTMENT 31.581 -7.849 0.000 0.000 3.892 2.413 12.213 7.958 0.000 0.424 0.000 0.000 -16.910 0.000 -22.506 -11.215
T SE APARTMENT 26.564 -10.027 0.000 0.000 3.877 2.413 12.213 15.827 0.000 0.453 0.000 0.000 -15.525 0.000 -23.179 -12.617
T NE APARTMENT 31.246 -7.567 0.000 0.000 3.901 2.413 12.213 7.665 0.000 0.420 0.000 0.000 -16.647 0.000 -22.512 -11.133
T N1 APARTMENT 19.115 -6.457 0.000 0.000 3.895 2.413 12.213 2.747 0.000 0.346 0.000 0.000 -10.739 0.000 -15.037 -8.495
T N2 APARTMENT 19.121 -6.454 0.000 0.000 3.896 2.413 12.213 2.745 0.000 0.347 0.000 0.000 -10.735 0.000 -15.041 -8.505
T S1 APARTMENT 14.804 -9.179 0.000 0.000 3.858 2.413 12.213 11.059 0.000 0.383 0.000 0.000 -9.645 0.000 -15.759 -10.147
T S2 APARTMENT 14.812 -9.175 0.000 0.000 3.859 2.413 12.213 11.055 0.000 0.383 0.000 0.000 -9.641 0.000 -15.764 -10.155
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 3.791 0.000 0.455 40.441 0.000 -3.345 0.000 -59.871 -0.002
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.710 0.000 0.006 0.000 0.000 -2.023 0.000 -1.767 -16.455
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.668 0.000 0.007 0.000 0.000 -2.103 0.000 -2.137 -15.964
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.645 0.000 0.007 0.000 0.000 -2.141 0.000 -2.405 -15.635
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 1.617 0.000 0.005 0.000 0.000 -2.195 0.000 -2.700 -33.785
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.627 0.000 0.008 0.000 0.000 -2.164 0.000 -2.786 -15.214
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.627 0.000 0.009 0.000 0.000 -2.159 0.000 -2.923 -15.083
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.623 0.000 0.009 0.000 0.000 -2.159 0.000 -3.054 -14.949
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.622 0.000 0.009 0.000 0.000 -2.152 0.000 -3.162 -14.847
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 1.584 0.000 0.003 0.000 0.000 -2.088 0.000 -3.289 -22.677
Total Facility 1055.032 -719.755 0.000 0.000 304.698 416.414 980.287 793.713 0.000 25.840 42.713 0.000 -1085.819 0.000 -1302.036 -511.087


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 07-SEP-15:15 0.00 -2763.28 0.00 0.00 48.90 100.83 470.89 3867.49 0.00 16.50 0.00 0.00 0.00 0.00 0.00 -1741.33
G NW APARTMENT 25-JUN-17:25 0.00 -2240.10 0.00 0.00 141.61 194.45 588.62 2864.75 0.00 140.58 0.00 0.00 0.00 0.00 0.00 -1689.91
OFFICE 07-SEP-13:30 0.00 -3457.53 0.00 0.00 65.20 1622.33 544.91 3386.61 0.00 23.51 0.00 0.00 0.00 0.00 0.00 -2185.03
G NE APARTMENT 02-JUL-09:45 0.00 -1681.21 0.00 0.00 40.69 28.81 406.15 2299.48 0.00 270.52 0.00 0.00 0.00 0.00 0.00 -1364.43
G N1 APARTMENT 02-JUL-19:15 0.00 -1300.39 0.00 0.00 141.83 230.46 523.87 419.92 0.00 287.68 0.00 0.00 0.00 0.00 0.00 -303.36
G N2 APARTMENT 02-JUL-19:15 0.00 -1300.65 0.00 0.00 141.83 230.46 523.87 420.33 0.00 289.43 0.00 0.00 0.00 0.00 0.00 -305.27
G S1 APARTMENT 05-SEP-12:30 0.00 -1883.53 0.00 0.00 40.75 28.81 388.49 3159.23 0.00 219.04 0.00 0.00 0.00 0.00 0.00 -1952.79
G S2 APARTMENT 05-SEP-12:30 0.00 -1924.29 0.00 0.00 40.75 28.81 388.49 3158.40 0.00 219.03 0.00 0.00 0.00 0.00 0.00 -1911.19
F2 SW APARTMENT 07-SEP-15:15 0.00 -3495.33 0.00 0.00 48.90 100.83 470.89 3852.71 0.00 23.65 0.00 0.00 0.00 0.00 0.00 -1001.65
F2 NW APARTMENT 25-JUN-17:25 0.00 -2950.22 0.00 0.00 141.82 194.45 588.62 2814.78 0.00 202.25 0.00 0.00 0.00 0.00 0.00 -991.70
F2 SE APARTMENT 07-SEP-13:30 0.00 -3245.03 0.00 0.00 40.75 28.81 382.60 3357.11 0.00 33.70 0.00 0.00 0.00 0.00 0.00 -597.94
F2 NE APARTMENT 26-JUN-17:30 0.00 -2190.19 0.00 0.00 141.81 194.45 588.62 967.91 0.00 82.13 215.27 0.00 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 28-JUN-19:15 0.00 -1693.14 0.00 0.00 141.83 230.46 523.87 479.18 0.00 241.02 76.79 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 28-JUN-19:15 0.00 -1682.12 0.00 0.00 141.83 230.46 523.87 479.32 0.00 240.69 65.96 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 05-SEP-12:30 0.00 -2431.02 0.00 0.00 40.75 28.81 388.49 3118.51 0.00 264.67 0.00 0.00 0.00 0.00 0.00 -1410.21
F2 S2 APARTMENT 05-SEP-12:30 0.00 -2449.46 0.00 0.00 40.75 28.81 388.49 3118.21 0.00 264.67 0.00 0.00 0.00 0.00 0.00 -1391.46
F3 SW APARTMENT 07-SEP-15:15 0.00 -3515.02 0.00 0.00 48.90 100.83 470.89 3846.14 0.00 27.91 0.00 0.00 0.00 0.00 0.00 -979.65
F3 NW APARTMENT 25-JUN-17:20 0.00 -2995.11 0.00 0.00 141.62 194.45 588.62 2793.57 0.00 238.43 0.00 0.00 0.00 0.00 0.00 -961.58
F3 SE APARTMENT 09-SEP-11:30 0.00 -3287.19 0.00 0.00 40.76 28.81 406.15 3370.03 0.00 602.23 0.00 0.00 0.00 0.00 0.00 -1160.78
F3 NE APARTMENT 28-JUN-19:00 0.00 -2264.79 0.00 0.00 141.82 230.46 547.42 601.79 0.00 397.19 346.11 0.00 0.00 0.00 0.00 0.00
F3 N1 APARTMENT 31-MAY-18:30 0.00 -1764.61 0.00 0.00 141.82 230.46 547.42 465.45 0.00 359.76 19.70 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 31-MAY-18:30 0.00 -1755.56 0.00 0.00 141.82 230.46 547.42 465.63 0.00 359.76 10.47 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 05-SEP-12:30 0.00 -2527.61 0.00 0.00 40.75 28.81 388.49 3096.00 0.00 293.43 0.00 0.00 0.00 0.00 0.00 -1319.87
F3 S2 APARTMENT 05-SEP-12:30 0.00 -2542.43 0.00 0.00 40.75 28.81 388.49 3095.75 0.00 293.43 0.00 0.00 0.00 0.00 0.00 -1304.80
F4 SW APARTMENT 02-SEP-15:00 0.00 -3553.80 0.00 0.00 40.75 50.41 400.26 3646.29 0.00 679.09 0.00 0.00 0.00 0.00 0.00 -1263.00
F4 NW APARTMENT 25-JUN-17:20 0.00 -3022.47 0.00 0.00 141.58 194.45 588.62 2779.80 0.00 265.52 0.00 0.00 0.00 0.00 0.00 -947.49
F4 SE APARTMENT 09-SEP-11:30 0.00 -3306.58 0.00 0.00 40.75 28.81 406.15 3347.21 0.00 654.75 0.00 0.00 0.00 0.00 0.00 -1171.08
F4 NE APARTMENT 28-JUN-19:00 0.00 -2306.89 0.00 0.00 141.82 230.46 547.42 600.30 0.00 428.59 358.30 0.00 0.00 0.00 0.00 0.00
F4 N1 APARTMENT 31-MAY-18:30 0.00 -1806.01 0.00 0.00 141.82 230.46 547.42 463.20 0.00 385.40 37.71 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 31-MAY-18:30 0.00 -1790.77 0.00 0.00 141.82 230.46 547.42 463.38 0.00 384.65 23.04 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 05-SEP-12:30 0.00 -2561.87 0.00 0.00 40.75 28.81 388.49 3080.12 0.00 314.93 0.00 0.00 0.00 0.00 0.00 -1291.23
F4 S2 APARTMENT 05-SEP-12:30 0.00 -2576.13 0.00 0.00 40.75 28.81 388.49 3079.88 0.00 314.93 0.00 0.00 0.00 0.00 0.00 -1276.72
M SW APARTMENT 02-SEP-15:00 0.00 -3614.02 0.00 0.00 40.76 50.41 400.26 3626.46 0.00 726.51 0.00 0.00 0.00 0.00 0.00 -1230.38
M NW APARTMENT 25-JUN-17:20 0.00 -3065.97 0.00 0.00 141.55 194.45 588.62 2768.70 0.00 287.55 0.00 0.00 0.00 0.00 0.00 -914.90
M SE APARTMENT 09-SEP-11:30 0.00 -3357.94 0.00 0.00 40.74 28.81 406.15 3329.41 0.00 698.11 0.00 0.00 0.00 0.00 0.00 -1145.28
M NE APARTMENT 28-JUN-19:00 0.00 -2361.60 0.00 0.00 141.83 230.46 547.42 598.34 0.00 453.82 389.74 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 31-MAY-18:30 0.00 -1852.67 0.00 0.00 141.82 230.46 547.42 461.20 0.00 406.44 65.33 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 31-MAY-18:30 0.00 -1837.46 0.00 0.00 141.82 230.46 547.42 461.39 0.00 405.64 50.74 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 05-SEP-12:30 0.00 -2598.79 0.00 0.00 40.75 28.81 388.49 3067.29 0.00 332.10 0.00 0.00 0.00 0.00 0.00 -1258.64
M S2 APARTMENT 05-SEP-12:30 0.00 -2612.98 0.00 0.00 40.75 28.81 388.49 3067.05 0.00 332.10 0.00 0.00 0.00 0.00 0.00 -1244.21
F6 SW APARTMENT 02-SEP-15:00 0.00 -3599.40 0.00 0.00 40.76 50.41 400.26 3612.31 0.00 765.83 0.00 0.00 0.00 0.00 0.00 -1270.17
F6 NW APARTMENT 25-JUN-17:20 0.00 -3033.85 0.00 0.00 141.48 194.45 588.62 2761.47 0.00 306.06 0.00 0.00 0.00 0.00 0.00 -958.23
F6 SE APARTMENT 09-SEP-11:30 0.00 -3334.30 0.00 0.00 40.73 28.81 406.15 3316.65 0.00 732.99 0.00 0.00 0.00 0.00 0.00 -1191.03
F6 NE APARTMENT 28-JUN-19:00 0.00 -2346.42 0.00 0.00 141.83 230.46 547.42 598.45 0.00 474.85 353.41 0.00 0.00 0.00 0.00 0.00
F6 N1 APARTMENT 31-MAY-18:30 0.00 -1824.12 0.00 0.00 141.82 230.46 547.42 460.81 0.00 423.38 20.23 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 31-MAY-18:30 0.00 -1809.02 0.00 0.00 141.82 230.46 547.42 460.99 0.00 422.53 5.80 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 05-SEP-12:30 0.00 -2556.49 0.00 0.00 40.75 28.81 388.49 3057.67 0.00 346.29 0.00 0.00 0.00 0.00 0.00 -1305.51
F6 S2 APARTMENT 05-SEP-12:30 0.00 -2570.83 0.00 0.00 40.75 28.81 388.49 3057.42 0.00 346.29 0.00 0.00 0.00 0.00 0.00 -1290.93
F7 SW APARTMENT 02-SEP-15:00 0.00 -3604.55 0.00 0.00 40.76 50.41 400.26 3599.84 0.00 799.25 0.00 0.00 0.00 0.00 0.00 -1285.97
F7 NW APARTMENT 25-JUN-17:20 0.00 -3027.84 0.00 0.00 141.45 194.45 588.62 2754.84 0.00 322.33 0.00 0.00 0.00 0.00 0.00 -973.84
F7 SE APARTMENT 09-SEP-11:30 0.00 -3335.18 0.00 0.00 40.73 28.81 406.15 3305.36 0.00 763.40 0.00 0.00 0.00 0.00 0.00 -1209.27
F7 NE APARTMENT 28-JUN-19:00 0.00 -2351.68 0.00 0.00 141.83 230.46 547.42 597.86 0.00 492.77 341.36 0.00 0.00 0.00 0.00 0.00
F7 N1 APARTMENT 31-MAY-18:30 0.00 -1820.30 0.00 0.00 141.82 230.46 547.42 460.05 0.00 438.14 2.41 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 31-MAY-18:30 0.00 -1805.29 0.00 0.00 141.82 230.46 547.42 460.23 0.00 437.25 0.00 0.00 0.00 0.00 0.00 -11.89
F7 S1 APARTMENT 05-SEP-12:30 0.00 -2534.16 0.00 0.00 40.75 28.81 388.49 3049.22 0.00 358.28 0.00 0.00 0.00 0.00 0.00 -1331.38
F7 S2 APARTMENT 05-SEP-12:30 0.00 -2548.74 0.00 0.00 40.75 28.81 388.49 3048.97 0.00 358.28 0.00 0.00 0.00 0.00 0.00 -1316.55
F8 SW APARTMENT 02-SEP-15:00 0.00 -3611.99 0.00 0.00 40.76 50.41 400.26 3588.96 0.00 828.11 0.00 0.00 0.00 0.00 0.00 -1296.52
F8 NW APARTMENT 25-JUN-17:20 0.00 -3035.20 0.00 0.00 141.44 194.45 588.62 2748.79 0.00 336.93 0.00 0.00 0.00 0.00 0.00 -975.03
F8 SE APARTMENT 09-SEP-11:30 0.00 -3347.83 0.00 0.00 40.74 28.81 406.15 3295.42 0.00 791.16 0.00 0.00 0.00 0.00 0.00 -1214.44
F8 NE APARTMENT 18-APR-15:30 0.00 -2387.44 0.00 0.00 48.90 100.83 470.89 1012.34 0.00 1047.16 0.00 0.00 0.00 0.00 0.00 -292.69
F8 N1 APARTMENT 31-MAY-18:30 0.00 -1830.00 0.00 0.00 141.82 230.46 547.42 459.09 0.00 451.25 0.00 0.00 0.00 0.00 0.00 -0.04
F8 N2 APARTMENT 31-MAY-18:30 0.00 -1815.09 0.00 0.00 141.82 230.46 547.42 459.27 0.00 450.32 0.00 0.00 0.00 0.00 0.00 -14.21
F8 S1 APARTMENT 05-SEP-12:45 0.00 -2593.81 0.00 0.00 40.75 28.81 388.49 2990.45 0.00 493.39 0.00 0.00 0.00 0.00 0.00 -1348.08
F8 S2 APARTMENT 05-SEP-12:45 0.00 -2605.90 0.00 0.00 40.75 28.81 388.49 2990.20 0.00 493.12 0.00 0.00 0.00 0.00 0.00 -1335.47
F9 SW APARTMENT 02-SEP-15:15 0.00 -3717.21 0.00 0.00 48.91 100.83 470.89 3501.38 0.00 889.61 0.00 0.00 0.00 0.00 0.00 -1294.41
F9 NW APARTMENT 25-JUN-17:20 0.00 -3126.63 0.00 0.00 141.56 194.45 588.62 2740.99 0.00 350.81 0.00 0.00 0.00 0.00 0.00 -889.79
F9 SE APARTMENT 09-SEP-11:30 0.00 -3416.23 0.00 0.00 40.76 28.81 406.15 3286.72 0.00 828.58 0.00 0.00 0.00 0.00 0.00 -1174.77
F9 NE APARTMENT 28-JUN-18:45 0.00 -2537.62 0.00 0.00 141.83 230.46 547.42 651.00 0.00 588.94 377.97 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 31-MAY-18:30 0.00 -1913.84 0.00 0.00 141.82 230.46 547.42 456.52 0.00 464.41 73.21 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 31-MAY-18:30 0.00 -1898.81 0.00 0.00 141.82 230.46 547.42 456.70 0.00 463.43 58.99 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 05-SEP-12:45 0.00 -2612.49 0.00 0.00 40.75 28.81 388.49 2984.77 0.00 518.32 0.00 0.00 0.00 0.00 0.00 -1348.65
F9 S2 APARTMENT 05-SEP-12:45 0.00 -2628.66 0.00 0.00 40.75 28.81 388.49 2984.47 0.00 518.31 0.00 0.00 0.00 0.00 0.00 -1332.17
T SW APARTMENT 07-SEP-14:30 0.00 -4418.63 0.00 0.00 40.75 50.41 400.26 4021.82 0.00 90.02 0.00 0.00 0.00 0.00 0.00 -184.64
T NW APARTMENT 05-JUL-17:15 0.00 -3690.49 0.00 0.00 141.82 194.45 588.62 2583.79 0.00 290.42 0.00 0.00 0.00 0.00 0.00 -108.62
T SE APARTMENT 07-SEP-13:15 0.00 -4130.09 0.00 0.00 40.75 28.81 382.60 3397.53 0.00 29.85 250.55 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 28-JUN-10:00 0.00 -2978.43 0.00 0.00 40.73 28.81 406.15 1981.97 0.00 527.24 0.00 0.00 0.00 0.00 0.00 -6.46
T N1 APARTMENT 11-AUG-15:00 0.00 -2293.50 0.00 0.00 40.75 50.41 400.26 646.83 0.00 754.75 400.50 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 11-AUG-15:00 0.00 -2291.47 0.00 0.00 40.75 50.41 400.26 646.86 0.00 754.75 398.44 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 07-SEP-13:30 0.00 -3370.53 0.00 0.00 39.66 28.81 382.60 2892.76 0.00 34.52 0.00 0.00 0.00 0.00 0.00 -7.82
T S2 APARTMENT 07-SEP-13:30 0.00 -3381.23 0.00 0.00 39.65 28.81 382.60 2892.56 0.00 34.53 3.07 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-SEP-16:30 0.00 -189588.89 0.00 0.00 6696.28 18221.75 47141.46 86105.09 0.00 47520.55 0.00 0.00 0.00 0.00 -42.19 -16054.05


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 09-DEC-08:53 3666.19 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1686.50 0.00 -1683.97 -801.39
G NW APARTMENT 09-DEC-08:53 3716.01 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1717.07 0.00 -1683.97 -820.64
OFFICE 09-DEC-08:53 3776.50 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 0.00 0.00 -1666.86 0.00 -1683.96 -933.95
G NE APARTMENT 09-DEC-08:53 3699.83 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1694.95 0.00 -1683.98 -826.57
G N1 APARTMENT 09-DEC-08:53 2323.81 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1048.00 0.00 -1015.73 -765.74
G N2 APARTMENT 09-DEC-08:53 2323.58 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1048.00 0.00 -1015.73 -765.51
G S1 APARTMENT 09-DEC-08:53 2262.29 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1017.60 0.00 -1015.73 -734.63
G S2 APARTMENT 09-DEC-08:53 2256.71 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1017.72 0.00 -1015.73 -728.93
F2 SW APARTMENT 09-DEC-02:00 4272.97 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1877.52 0.00 -2577.26 -263.60
F2 NW APARTMENT 09-DEC-02:00 4390.92 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1917.35 0.00 -2577.26 -341.71
F2 SE APARTMENT 09-DEC-02:00 4206.57 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1849.29 0.00 -2577.26 -225.42
F2 NE APARTMENT 09-DEC-02:00 4371.17 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1887.65 0.00 -2577.27 -351.65
F2 N1 APARTMENT 23-MAR-13:55 2813.45 0.00 0.00 0.00 46.91 28.81 382.60 261.36 0.00 0.00 0.00 0.00 0.00 0.00 -2930.81 -602.32
F2 N2 APARTMENT 23-MAR-13:55 2817.31 0.00 0.00 0.00 46.90 28.81 382.60 261.11 0.00 0.00 0.00 0.00 0.00 0.00 -2930.82 -605.92
F2 S1 APARTMENT 09-DEC-02:00 2385.86 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1128.78 0.00 -1554.54 -147.95
F2 S2 APARTMENT 09-DEC-02:00 2381.86 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1128.87 0.00 -1554.54 -143.86
F3 SW APARTMENT 09-DEC-02:00 4654.07 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1904.95 0.00 -3052.10 -142.43
F3 NW APARTMENT 09-DEC-02:00 4791.63 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1947.75 0.00 -3052.10 -237.18
F3 SE APARTMENT 09-DEC-02:00 4627.95 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1872.79 0.00 -3052.10 -148.46
F3 NE APARTMENT 09-DEC-02:00 4770.34 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1915.62 0.00 -3052.11 -248.01
F3 N1 APARTMENT 23-MAR-13:55 3294.52 0.00 0.00 0.00 46.81 28.81 382.60 253.88 0.00 0.00 0.00 0.00 0.00 0.00 -3430.62 -576.00
F3 N2 APARTMENT 23-MAR-13:55 3298.25 0.00 0.00 0.00 46.79 28.81 382.60 253.65 0.00 0.00 0.00 0.00 0.00 0.00 -3430.63 -579.48
F3 S1 APARTMENT 09-DEC-02:00 2561.60 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1144.77 0.00 -1840.95 -21.29
F3 S2 APARTMENT 09-DEC-02:00 2560.96 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1144.78 0.00 -1840.95 -20.64
F4 SW APARTMENT 09-DEC-02:00 5003.10 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1921.11 0.00 -3412.30 -115.09
F4 NW APARTMENT 09-DEC-02:00 5146.79 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1965.67 0.00 -3412.31 -214.23
F4 SE APARTMENT 09-DEC-02:00 4983.44 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1887.35 0.00 -3412.31 -129.19
F4 NE APARTMENT 09-DEC-02:00 5124.47 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1932.23 0.00 -3412.32 -225.34
F4 N1 APARTMENT 23-MAR-14:10 3565.00 0.00 0.00 0.00 46.71 50.41 400.26 243.40 0.00 0.00 0.00 0.00 0.00 0.00 -3673.98 -631.81
F4 N2 APARTMENT 23-MAR-14:10 3567.13 0.00 0.00 0.00 46.70 50.41 400.26 243.22 0.00 0.00 0.00 0.00 0.00 0.00 -3673.99 -633.75
F4 S1 APARTMENT 09-DEC-02:00 2757.31 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 9.63 0.00 -1154.13 0.00 -2058.21 0.00
F4 S2 APARTMENT 09-DEC-02:00 2757.56 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 9.37 0.00 -1154.13 0.00 -2058.21 0.00
M SW APARTMENT 09-DEC-02:00 5281.97 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1933.52 0.00 -3709.31 -84.55
M NW APARTMENT 09-DEC-02:00 5425.59 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1979.29 0.00 -3709.32 -182.39
M SE APARTMENT 09-DEC-02:00 5262.74 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1898.86 0.00 -3709.32 -99.98
M NE APARTMENT 09-DEC-02:00 5402.57 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1945.00 0.00 -3709.33 -193.66
M N1 APARTMENT 23-MAR-14:10 3855.43 0.00 0.00 0.00 46.70 50.41 400.26 240.27 0.00 0.00 0.00 0.00 0.00 0.00 -3986.68 -606.39
M N2 APARTMENT 23-MAR-14:10 3857.31 0.00 0.00 0.00 46.69 50.41 400.26 240.10 0.00 0.00 0.00 0.00 0.00 0.00 -3986.68 -608.10
M S1 APARTMENT 09-DEC-02:00 2914.64 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 38.67 0.00 -1161.35 0.00 -2237.36 0.00
M S2 APARTMENT 09-DEC-02:00 2915.07 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 38.22 0.00 -1161.34 0.00 -2237.36 0.00
F6 SW APARTMENT 09-DEC-02:00 5585.35 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1941.21 0.00 -3965.34 -124.20
F6 NW APARTMENT 09-DEC-02:00 5728.10 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1987.95 0.00 -3965.35 -220.21
F6 SE APARTMENT 09-DEC-02:00 5565.64 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1905.99 0.00 -3965.35 -139.71
F6 NE APARTMENT 09-DEC-02:00 5704.51 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1953.10 0.00 -3965.36 -231.46
F6 N1 APARTMENT 23-MAR-14:10 4036.34 0.00 0.00 0.00 46.98 50.41 400.26 240.98 0.00 0.00 0.00 0.00 0.00 0.00 -4259.83 -515.14
F6 N2 APARTMENT 23-MAR-14:10 4038.92 0.00 0.00 0.00 46.97 50.41 400.26 240.79 0.00 0.00 0.00 0.00 0.00 0.00 -4259.84 -517.51
F6 S1 APARTMENT 23-MAR-14:10 3166.43 0.00 0.00 0.00 41.22 50.41 400.26 2081.48 0.00 0.00 0.00 0.00 0.00 0.00 -4312.45 -1427.35
F6 S2 APARTMENT 23-MAR-14:10 3152.30 0.00 0.00 0.00 41.19 50.41 400.26 2081.18 0.00 0.00 0.00 0.00 0.00 0.00 -4313.18 -1412.15
F7 SW APARTMENT 09-DEC-02:00 5838.75 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1948.10 0.00 -4192.27 -143.79
F7 NW APARTMENT 09-DEC-02:00 5978.28 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1995.60 0.00 -4192.28 -235.80
F7 SE APARTMENT 09-DEC-02:00 5818.54 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1912.45 0.00 -4192.28 -159.22
F7 NE APARTMENT 09-DEC-02:00 5954.25 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1960.33 0.00 -4192.29 -247.04
F7 N1 APARTMENT 23-MAR-14:10 4220.76 0.00 0.00 0.00 47.15 50.41 400.26 240.88 0.00 0.00 0.00 0.00 0.00 0.00 -4505.38 -454.08
F7 N2 APARTMENT 23-MAR-14:10 4222.40 0.00 0.00 0.00 47.14 50.41 400.26 240.70 0.00 0.00 0.00 0.00 0.00 0.00 -4505.39 -455.53
F7 S1 APARTMENT 23-MAR-14:10 3805.36 0.00 0.00 0.00 41.57 50.41 400.26 2076.73 0.00 0.00 0.00 0.00 0.00 0.00 -4547.08 -1827.26
F7 S2 APARTMENT 23-MAR-14:10 3790.86 0.00 0.00 0.00 41.54 50.41 400.26 2076.43 0.00 0.00 0.00 0.00 0.00 0.00 -4547.79 -1811.71
F8 SW APARTMENT 09-DEC-02:00 6078.47 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1953.66 0.00 -4397.29 -172.92
F8 NW APARTMENT 09-DEC-02:00 6211.53 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -2001.87 0.00 -4397.30 -257.77
F8 SE APARTMENT 09-DEC-02:00 6057.71 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1917.71 0.00 -4397.30 -188.11
F8 NE APARTMENT 09-DEC-02:00 6187.09 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1966.28 0.00 -4397.30 -268.91
F8 N1 APARTMENT 23-MAR-14:10 4396.20 0.00 0.00 0.00 47.29 50.41 400.26 240.78 0.00 0.00 0.00 0.00 0.00 0.00 -4730.12 -404.82
F8 N2 APARTMENT 23-MAR-14:10 4397.15 0.00 0.00 0.00 47.28 50.41 400.26 240.61 0.00 0.00 0.00 0.00 0.00 0.00 -4730.13 -405.59
F8 S1 APARTMENT 23-MAR-14:10 4371.87 0.00 0.00 0.00 41.89 50.41 400.26 2072.92 0.00 0.00 0.00 0.00 0.00 0.00 -4762.18 -2175.18
F8 S2 APARTMENT 23-MAR-14:10 4360.09 0.00 0.00 0.00 41.86 50.41 400.26 2072.67 0.00 0.00 0.00 0.00 0.00 0.00 -4762.77 -2162.53
F9 SW APARTMENT 09-DEC-02:00 6445.41 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1954.00 0.00 -4585.12 -351.70
F9 NW APARTMENT 09-DEC-02:00 6558.05 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -2003.02 0.00 -4585.12 -415.30
F9 SE APARTMENT 09-DEC-02:00 6422.85 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1917.94 0.00 -4585.13 -365.18
F9 NE APARTMENT 09-DEC-02:00 6532.36 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1967.29 0.00 -4585.13 -425.34
F9 N1 APARTMENT 23-MAR-14:10 4572.75 0.00 0.00 0.00 47.42 50.41 400.26 241.81 0.00 0.00 0.00 0.00 0.00 0.00 -4938.54 -374.12
F9 N2 APARTMENT 23-MAR-14:10 4569.74 0.00 0.00 0.00 47.42 50.41 400.26 241.65 0.00 0.00 0.00 0.00 0.00 0.00 -4938.54 -370.93
F9 S1 APARTMENT 23-MAR-14:10 4982.33 0.00 0.00 0.00 42.30 50.41 400.26 2071.68 0.00 0.00 0.00 0.00 0.00 0.00 -4959.54 -2587.46
F9 S2 APARTMENT 23-MAR-14:10 4968.01 0.00 0.00 0.00 42.27 50.41 400.26 2071.36 0.00 0.00 0.00 0.00 0.00 0.00 -4960.21 -2572.11
T SW APARTMENT 09-DEC-02:00 7498.37 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1915.65 0.00 -4758.66 -1269.47
T NW APARTMENT 09-DEC-02:00 7572.73 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1963.29 0.00 -4758.67 -1296.18
T SE APARTMENT 09-DEC-02:00 7471.06 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1880.76 0.00 -4758.67 -1277.05
T NE APARTMENT 09-DEC-02:00 7544.41 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1928.57 0.00 -4758.67 -1302.57
T N1 APARTMENT 09-DEC-02:00 4837.70 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1199.14 0.00 -2870.43 -1213.54
T N2 APARTMENT 09-DEC-02:00 4837.22 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1199.15 0.00 -2870.42 -1213.05
T S1 APARTMENT 09-DEC-02:00 4750.53 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1150.17 0.00 -2870.41 -1175.36
T S2 APARTMENT 09-DEC-02:00 4750.21 0.00 0.00 0.00 189.67 14.40 241.33 0.00 0.00 0.00 0.00 0.00 -1150.18 0.00 -2870.41 -1175.03
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-DEC-02:00 345596.79 0.00 0.00 0.00 14983.85 7980.64 19245.24 0.00 0.00 0.00 0.00 0.00 -126478.19 0.00 -239681.33 -21647.01



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Sec1.1A-General Information

Data
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 123.25
Number of hours cooling loads not met 73.50
Number of hours not met 196.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 7980.64 0.00 0.00 0.00 0.00
Exterior Lighting 168.36 10720.10 0.00 0.00 0.00 0.00
Space Heating 425.54 178038.21 1560.29 319979.07 0.00 0.00
Space Cooling 296.90 0.00 0.00 0.00 0.00 0.00
Pumps 55.66 1805.00 0.00 0.00 0.00 0.00
Heat Rejection 13.06 0.00 0.00 0.00 0.00 0.00
Fans-Interior 606.47 19230.90 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1295.71 88159.50 0.00 0.00
Receptacle Equipment 1131.09 20217.84 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3134.31   2856.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3134.31
Natural Gas 0.00 2856.00
Additional 0.00 0.00
Total 1131.09 5990.32


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 54.30
Space Cooling 37.89
Fans-Interior 77.39
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 32.91
Subtotal 399.96


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 199.11
Service Water Heating 165.34
Miscellaneous 0.00
Subtotal 364.45


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.95
Space Heating 33.15
Space Cooling 4.96
Fans-Interior 10.12
Service Water Heating 21.63
Receptacle Equipment 18.88
Miscellaneous 4.31



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.219053
G NW APARTMENT DIRECT AIR 0.204997
OFFICE DIRECT AIR 0.294756
G NE APARTMENT DIRECT AIR 0.174036
G N1 APARTMENT DIRECT AIR 0.116007
G N2 APARTMENT DIRECT AIR 0.116005
G S1 APARTMENT DIRECT AIR 0.133628
G S2 APARTMENT DIRECT AIR 0.138923
F2 SW APARTMENT DIRECT AIR 0.288759
F2 NW APARTMENT DIRECT AIR 0.267387
F2 SE APARTMENT DIRECT AIR 0.270005
F2 NE APARTMENT DIRECT AIR 0.202129
F2 N1 APARTMENT DIRECT AIR 0.144185
F2 N2 APARTMENT DIRECT AIR 0.142654
F2 S1 APARTMENT DIRECT AIR 0.181395
F2 S2 APARTMENT DIRECT AIR 0.183568
F3 SW APARTMENT DIRECT AIR 0.289899
F3 NW APARTMENT DIRECT AIR 0.269888
F3 SE APARTMENT DIRECT AIR 0.256175
F3 NE APARTMENT DIRECT AIR 0.205876
F3 N1 APARTMENT DIRECT AIR 0.148482
F3 N2 APARTMENT DIRECT AIR 0.146970
F3 S1 APARTMENT DIRECT AIR 0.185209
F3 S2 APARTMENT DIRECT AIR 0.186363
F4 SW APARTMENT DIRECT AIR 0.290536
F4 NW APARTMENT DIRECT AIR 0.270936
F4 SE APARTMENT DIRECT AIR 0.255868
F4 NE APARTMENT DIRECT AIR 0.206887
F4 N1 APARTMENT DIRECT AIR 0.150072
F4 N2 APARTMENT DIRECT AIR 0.148569
F4 S1 APARTMENT DIRECT AIR 0.186440
F4 S2 APARTMENT DIRECT AIR 0.187449
M SW APARTMENT DIRECT AIR 0.293379
M NW APARTMENT DIRECT AIR 0.274160
M SE APARTMENT DIRECT AIR 0.259017
M NE APARTMENT DIRECT AIR 0.209964
M N1 APARTMENT DIRECT AIR 0.153491
M N2 APARTMENT DIRECT AIR 0.151995
M S1 APARTMENT DIRECT AIR 0.189592
M S2 APARTMENT DIRECT AIR 0.190580
F6 SW APARTMENT DIRECT AIR 0.289711
F6 NW APARTMENT DIRECT AIR 0.270620
F6 SE APARTMENT DIRECT AIR 0.255802
F6 NE APARTMENT DIRECT AIR 0.206414
F6 N1 APARTMENT DIRECT AIR 0.150406
F6 N2 APARTMENT DIRECT AIR 0.148924
F6 S1 APARTMENT DIRECT AIR 0.186271
F6 S2 APARTMENT DIRECT AIR 0.187256
F7 SW APARTMENT DIRECT AIR 0.288466
F7 NW APARTMENT DIRECT AIR 0.269571
F7 SE APARTMENT DIRECT AIR 0.254941
F7 NE APARTMENT DIRECT AIR 0.207200
F7 N1 APARTMENT DIRECT AIR 0.149632
F7 N2 APARTMENT DIRECT AIR 0.148160
F7 S1 APARTMENT DIRECT AIR 0.185274
F7 S2 APARTMENT DIRECT AIR 0.186257
F8 SW APARTMENT DIRECT AIR 0.288570
F8 NW APARTMENT DIRECT AIR 0.269850
F8 SE APARTMENT DIRECT AIR 0.255301
F8 NE APARTMENT DIRECT AIR 0.213252
F8 N1 APARTMENT DIRECT AIR 0.150149
F8 N2 APARTMENT DIRECT AIR 0.148687
F8 S1 APARTMENT DIRECT AIR 0.185525
F8 S2 APARTMENT DIRECT AIR 0.186510
F9 SW APARTMENT DIRECT AIR 0.297135
F9 NW APARTMENT DIRECT AIR 0.278110
F9 SE APARTMENT DIRECT AIR 0.261390
F9 NE APARTMENT DIRECT AIR 0.227266
F9 N1 APARTMENT DIRECT AIR 0.157415
F9 N2 APARTMENT DIRECT AIR 0.155934
F9 S1 APARTMENT DIRECT AIR 0.190564
F9 S2 APARTMENT DIRECT AIR 0.191614
T SW APARTMENT DIRECT AIR 0.349408
T NW APARTMENT DIRECT AIR 0.322882
T SE APARTMENT DIRECT AIR 0.314267
T NE APARTMENT DIRECT AIR 0.273755
T N1 APARTMENT DIRECT AIR 0.185708
T N2 APARTMENT DIRECT AIR 0.185684
T S1 APARTMENT DIRECT AIR 0.254328
T S2 APARTMENT DIRECT AIR 0.255299


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.219053
AIRLOOP G NW MAIN BRANCH 0.204997
AIRLOOP OFFICE MAIN BRANCH 0.294756
AIRLOOP G NE MAIN BRANCH 0.174036
AIRLOOP G N1 MAIN BRANCH 0.116007
AIRLOOP G N2 MAIN BRANCH 0.116005
AIRLOOP G S1 MAIN BRANCH 0.133628
AIRLOOP G S2 MAIN BRANCH 0.138923
AIRLOOP F2 SW MAIN BRANCH 0.288759
AIRLOOP F2 NW MAIN BRANCH 0.267387
AIRLOOP F2 SE MAIN BRANCH 0.270005
AIRLOOP F2 NE MAIN BRANCH 0.202129
AIRLOOP F2 N1 MAIN BRANCH 0.144185
AIRLOOP F2 N2 MAIN BRANCH 0.142654
AIRLOOP F2 S1 MAIN BRANCH 0.181395
AIRLOOP F2 S2 MAIN BRANCH 0.183568
AIRLOOP F3 SW MAIN BRANCH 0.289899
AIRLOOP F3 NW MAIN BRANCH 0.269888
AIRLOOP F3 SE MAIN BRANCH 0.256175
AIRLOOP F3 NE MAIN BRANCH 0.205876
AIRLOOP F3 N1 MAIN BRANCH 0.148482
AIRLOOP F3 N2 MAIN BRANCH 0.146970
AIRLOOP F3 S1 MAIN BRANCH 0.185209
AIRLOOP F3 S2 MAIN BRANCH 0.186363
AIRLOOP F4 SW MAIN BRANCH 0.290536
AIRLOOP F4 NW MAIN BRANCH 0.270936
AIRLOOP F4 SE MAIN BRANCH 0.255868
AIRLOOP F4 NE MAIN BRANCH 0.206887
AIRLOOP F4 N1 MAIN BRANCH 0.150072
AIRLOOP F4 N2 MAIN BRANCH 0.148569
AIRLOOP F4 S1 MAIN BRANCH 0.186440
AIRLOOP F4 S2 MAIN BRANCH 0.187449
AIRLOOP M SW MAIN BRANCH 0.293379
AIRLOOP M NW MAIN BRANCH 0.274160
AIRLOOP M SE MAIN BRANCH 0.259017
AIRLOOP M NE MAIN BRANCH 0.209964
AIRLOOP M N1 MAIN BRANCH 0.153491
AIRLOOP M N2 MAIN BRANCH 0.151995
AIRLOOP M S1 MAIN BRANCH 0.189592
AIRLOOP M S2 MAIN BRANCH 0.190580
AIRLOOP F6 SW MAIN BRANCH 0.289711
AIRLOOP F6 NW MAIN BRANCH 0.270620
AIRLOOP F6 SE MAIN BRANCH 0.255802
AIRLOOP F6 NE MAIN BRANCH 0.206414
AIRLOOP F6 N1 MAIN BRANCH 0.150406
AIRLOOP F6 N2 MAIN BRANCH 0.148924
AIRLOOP F6 S1 MAIN BRANCH 0.186271
AIRLOOP F6 S2 MAIN BRANCH 0.187256
AIRLOOP F7 SW MAIN BRANCH 0.288466
AIRLOOP F7 NW MAIN BRANCH 0.269571
AIRLOOP F7 SE MAIN BRANCH 0.254941
AIRLOOP F7 NE MAIN BRANCH 0.207200
AIRLOOP F7 N1 MAIN BRANCH 0.149632
AIRLOOP F7 N2 MAIN BRANCH 0.148160
AIRLOOP F7 S1 MAIN BRANCH 0.185274
AIRLOOP F7 S2 MAIN BRANCH 0.186257
AIRLOOP F8 SW MAIN BRANCH 0.288570
AIRLOOP F8 NW MAIN BRANCH 0.269850
AIRLOOP F8 SE MAIN BRANCH 0.255301
AIRLOOP F8 NE MAIN BRANCH 0.213252
AIRLOOP F8 N1 MAIN BRANCH 0.150149
AIRLOOP F8 N2 MAIN BRANCH 0.148687
AIRLOOP F8 S1 MAIN BRANCH 0.185525
AIRLOOP F8 S2 MAIN BRANCH 0.186510
AIRLOOP F9 SW MAIN BRANCH 0.297135
AIRLOOP F9 NW MAIN BRANCH 0.278110
AIRLOOP F9 SE MAIN BRANCH 0.261390
AIRLOOP F9 NE MAIN BRANCH 0.227266
AIRLOOP F9 N1 MAIN BRANCH 0.157415
AIRLOOP F9 N2 MAIN BRANCH 0.155934
AIRLOOP F9 S1 MAIN BRANCH 0.190564
AIRLOOP F9 S2 MAIN BRANCH 0.191614
AIRLOOP T SW MAIN BRANCH 0.349408
AIRLOOP T NW MAIN BRANCH 0.322882
AIRLOOP T SE MAIN BRANCH 0.314267
AIRLOOP T NE MAIN BRANCH 0.273755
AIRLOOP T N1 MAIN BRANCH 0.185708
AIRLOOP T N2 MAIN BRANCH 0.185684
AIRLOOP T S1 MAIN BRANCH 0.254328
AIRLOOP T S2 MAIN BRANCH 0.255299


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.219053
AIRLOOP G NW 0.204997
AIRLOOP OFFICE 0.294756
AIRLOOP G NE 0.174036
AIRLOOP G N1 0.116007
AIRLOOP G N2 0.116005
AIRLOOP G S1 0.133628
AIRLOOP G S2 0.138923
AIRLOOP F2 SW 0.288759
AIRLOOP F2 NW 0.267387
AIRLOOP F2 SE 0.270005
AIRLOOP F2 NE 0.202129
AIRLOOP F2 N1 0.144185
AIRLOOP F2 N2 0.142654
AIRLOOP F2 S1 0.181395
AIRLOOP F2 S2 0.183568
AIRLOOP F3 SW 0.289899
AIRLOOP F3 NW 0.269888
AIRLOOP F3 SE 0.256175
AIRLOOP F3 NE 0.205876
AIRLOOP F3 N1 0.148482
AIRLOOP F3 N2 0.146970
AIRLOOP F3 S1 0.185209
AIRLOOP F3 S2 0.186363
AIRLOOP F4 SW 0.290536
AIRLOOP F4 NW 0.270936
AIRLOOP F4 SE 0.255868
AIRLOOP F4 NE 0.206887
AIRLOOP F4 N1 0.150072
AIRLOOP F4 N2 0.148569
AIRLOOP F4 S1 0.186440
AIRLOOP F4 S2 0.187449
AIRLOOP M SW 0.293379
AIRLOOP M NW 0.274160
AIRLOOP M SE 0.259017
AIRLOOP M NE 0.209964
AIRLOOP M N1 0.153491
AIRLOOP M N2 0.151995
AIRLOOP M S1 0.189592
AIRLOOP M S2 0.190580
AIRLOOP F6 SW 0.289711
AIRLOOP F6 NW 0.270620
AIRLOOP F6 SE 0.255802
AIRLOOP F6 NE 0.206414
AIRLOOP F6 N1 0.150406
AIRLOOP F6 N2 0.148924
AIRLOOP F6 S1 0.186271
AIRLOOP F6 S2 0.187256
AIRLOOP F7 SW 0.288466
AIRLOOP F7 NW 0.269571
AIRLOOP F7 SE 0.254941
AIRLOOP F7 NE 0.207200
AIRLOOP F7 N1 0.149632
AIRLOOP F7 N2 0.148160
AIRLOOP F7 S1 0.185274
AIRLOOP F7 S2 0.186257
AIRLOOP F8 SW 0.288570
AIRLOOP F8 NW 0.269850
AIRLOOP F8 SE 0.255301
AIRLOOP F8 NE 0.213252
AIRLOOP F8 N1 0.150149
AIRLOOP F8 N2 0.148687
AIRLOOP F8 S1 0.185525
AIRLOOP F8 S2 0.186510
AIRLOOP F9 SW 0.297135
AIRLOOP F9 NW 0.278110
AIRLOOP F9 SE 0.261390
AIRLOOP F9 NE 0.227266
AIRLOOP F9 N1 0.157415
AIRLOOP F9 N2 0.155934
AIRLOOP F9 S1 0.190564
AIRLOOP F9 S2 0.191614
AIRLOOP T SW 0.349408
AIRLOOP T NW 0.322882
AIRLOOP T SE 0.314267
AIRLOOP T NE 0.273755
AIRLOOP T N1 0.185708
AIRLOOP T N2 0.185684
AIRLOOP T S1 0.254328
AIRLOOP T S2 0.255299


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.219053 0.025952
AIRLOOP G NW OA CONTROLLER 0.204997 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.294756 0.038103
AIRLOOP G NE OA CONTROLLER 0.174036 0.025952
AIRLOOP G N1 OA CONTROLLER 0.116007 0.025952
AIRLOOP G N2 OA CONTROLLER 0.116005 0.025952
AIRLOOP G S1 OA CONTROLLER 0.133628 0.025952
AIRLOOP G S2 OA CONTROLLER 0.138923 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.288759 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.267387 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.270005 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.202129 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.144185 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.142654 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.181395 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.183568 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.289899 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.269888 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.256175 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.205876 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.148482 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.146970 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.185209 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.186363 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.290536 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.270936 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.255868 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.206887 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.150072 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.148569 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.186440 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.187449 0.025952
AIRLOOP M SW OA CONTROLLER 0.293379 0.025952
AIRLOOP M NW OA CONTROLLER 0.274160 0.025952
AIRLOOP M SE OA CONTROLLER 0.259017 0.025952
AIRLOOP M NE OA CONTROLLER 0.209964 0.025952
AIRLOOP M N1 OA CONTROLLER 0.153491 0.025952
AIRLOOP M N2 OA CONTROLLER 0.151995 0.025952
AIRLOOP M S1 OA CONTROLLER 0.189592 0.025952
AIRLOOP M S2 OA CONTROLLER 0.190580 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.289711 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.270620 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.255802 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.206414 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.150406 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.148924 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.186271 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.187256 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.288466 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.269571 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.254941 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.207200 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.149632 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.148160 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.185274 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.186257 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.288570 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.269850 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.255301 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.213252 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.150149 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.148687 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.185525 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.186510 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.297135 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.278110 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.261390 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.227266 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.157415 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.155934 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.190564 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.191614 0.025952
AIRLOOP T SW OA CONTROLLER 0.349408 0.025952
AIRLOOP T NW OA CONTROLLER 0.322882 0.025952
AIRLOOP T SE OA CONTROLLER 0.314267 0.025952
AIRLOOP T NE OA CONTROLLER 0.273755 0.025952
AIRLOOP T N1 OA CONTROLLER 0.185708 0.025952
AIRLOOP T N2 OA CONTROLLER 0.185684 0.025952
AIRLOOP T S1 OA CONTROLLER 0.254328 0.025952
AIRLOOP T S2 OA CONTROLLER 0.255299 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.219053 3887.38 2478.79 0.000085
HEAT PUMP COOLING MODE AIRLOOP G NW 0.204997 3684.09 2331.29 0.000080
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.294756 5271.71 3365.13 0.000115
HEAT PUMP COOLING MODE AIRLOOP G NE 0.174036 3354.42 2048.68 0.000073
HEAT PUMP COOLING MODE AIRLOOP G N1 0.116007 2420.09 1430.07 0.000053
HEAT PUMP COOLING MODE AIRLOOP G N2 0.116005 2432.99 1434.73 0.000053
HEAT PUMP COOLING MODE AIRLOOP G S1 0.133628 2659.02 1616.75 0.000058
HEAT PUMP COOLING MODE AIRLOOP G S2 0.138923 2733.18 1670.03 0.000060
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.288759 4950.17 3209.82 0.000108
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.267387 4645.28 2987.93 0.000101
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.270005 4730.04 3042.65 0.000103
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.202129 3696.78 2314.54 0.000081
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.144185 2787.43 1699.73 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.142654 2765.36 1684.21 0.000060
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.181395 3381.17 2114.73 0.000074
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.183568 3411.40 2136.63 0.000075
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.289899 5022.00 3237.24 0.000110
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.269888 4735.20 3029.07 0.000103
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.256175 4591.56 2918.47 0.000100
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.205876 3800.25 2367.74 0.000083
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.148482 2877.67 1752.30 0.000063
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.146970 2855.82 1736.98 0.000062
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.185209 3466.03 2162.69 0.000076
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.186363 3482.07 2174.30 0.000076
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.290536 5072.40 3255.58 0.000111
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.270936 4798.67 3056.01 0.000105
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.255868 4627.16 2927.04 0.000101
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.206887 3852.08 2389.44 0.000084
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.150072 2921.93 1775.25 0.000064
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.148569 2900.12 1760.00 0.000063
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.186440 3506.82 2182.20 0.000077
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.187449 3520.88 2192.37 0.000077
HEAT PUMP COOLING MODE AIRLOOP M SW 0.293379 5145.80 3294.04 0.000112
HEAT PUMP COOLING MODE AIRLOOP M NW 0.274160 4876.88 3098.28 0.000107
HEAT PUMP COOLING MODE AIRLOOP M SE 0.259017 4703.77 2968.46 0.000103
HEAT PUMP COOLING MODE AIRLOOP M NE 0.209964 3926.14 2429.91 0.000086
HEAT PUMP COOLING MODE AIRLOOP M N1 0.153491 2988.53 1815.43 0.000065
HEAT PUMP COOLING MODE AIRLOOP M N2 0.151995 2966.79 1800.24 0.000065
HEAT PUMP COOLING MODE AIRLOOP M S1 0.189592 3570.36 2219.88 0.000078
HEAT PUMP COOLING MODE AIRLOOP M S2 0.190580 3584.12 2229.82 0.000078
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.289711 5122.82 3265.17 0.000112
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.270620 4855.04 3070.67 0.000106
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.255802 4685.66 2943.96 0.000102
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.206414 3900.89 2401.87 0.000085
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.150406 2958.72 1789.00 0.000065
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.148924 2937.04 1773.93 0.000064
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.186271 3539.64 2191.19 0.000077
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.187256 3553.40 2201.10 0.000078
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.288466 5130.10 3259.80 0.000112
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.269571 4864.54 3067.25 0.000106
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.254941 4697.22 2942.33 0.000103
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.207200 3943.14 2419.70 0.000086
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.149632 2960.23 1785.33 0.000065
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.148160 2938.61 1770.34 0.000064
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.185274 3539.62 2185.41 0.000077
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.186257 3553.39 2195.31 0.000078
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.288570 5153.68 3267.35 0.000113
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.269850 4890.11 3076.52 0.000107
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.255301 4723.47 2952.34 0.000103
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.213252 4078.04 2496.60 0.000089
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.150149 2979.08 1794.29 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.148687 2957.57 1779.41 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.185525 3555.76 2191.82 0.000078
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.186510 3569.57 2201.74 0.000078
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.297135 5294.95 3360.16 0.000116
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.278110 5026.99 3166.19 0.000110
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.261390 4832.24 3021.46 0.000106
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.227266 4358.30 2666.36 0.000095
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.157415 3095.33 1871.39 0.000068
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.155934 3073.58 1856.30 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.190564 3641.25 2247.73 0.000080
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.191614 3654.08 2257.14 0.000080
HEAT PUMP COOLING MODE AIRLOOP T SW 0.349408 6081.21 3914.54 0.000133
HEAT PUMP COOLING MODE AIRLOOP T NW 0.322882 5681.31 3629.45 0.000124
HEAT PUMP COOLING MODE AIRLOOP T SE 0.314267 5595.00 3561.57 0.000122
HEAT PUMP COOLING MODE AIRLOOP T NE 0.273755 5069.94 3154.25 0.000111
HEAT PUMP COOLING MODE AIRLOOP T N1 0.185708 3532.95 2171.46 0.000077
HEAT PUMP COOLING MODE AIRLOOP T N2 0.185684 3604.80 2209.24 0.000079
HEAT PUMP COOLING MODE AIRLOOP T S1 0.254328 4548.17 2895.34 0.000099
HEAT PUMP COOLING MODE AIRLOOP T S2 0.255299 4561.52 2905.10 0.000100


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.219053 0.219053 0.219053 0.219053 3887.38 3887.38 5102.65 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.204997 0.204997 0.204997 0.204997 3684.09 3684.09 5111.44 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.294756 0.294756 0.294756 0.294756 5271.71 5271.71 6247.01 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.174036 0.174036 0.174036 0.174036 3354.42 3354.42 5110.71 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.116007 0.116007 0.116007 0.116007 2420.09 2420.09 3884.95 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.116005 0.116005 0.116005 0.116005 2432.99 2432.99 3884.92 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.133628 0.133628 0.133628 0.133628 2659.02 2659.02 3873.60 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.138923 0.138923 0.138923 0.138923 2733.18 2733.18 3882.02 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.288759 0.288759 0.288759 0.288759 4950.17 4950.17 5139.56 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.267387 0.267387 0.267387 0.267387 4645.28 4645.28 5150.53 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.270005 0.270005 0.270005 0.270005 4730.04 4730.04 5155.88 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.202129 0.202129 0.202129 0.202129 3696.78 3696.78 5142.56 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.144185 0.144185 0.144185 0.144185 2787.43 2787.43 3623.99 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.142654 0.142654 0.142654 0.142654 2765.36 2765.36 3623.82 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.181395 0.181395 0.181395 0.181395 3381.17 3381.17 3615.94 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.183568 0.183568 0.183568 0.183568 3411.40 3411.40 3617.25 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.289899 0.289899 0.289899 0.289899 5022.00 5022.00 5245.52 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.269888 0.269888 0.269888 0.269888 4735.20 4735.20 5265.90 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.256175 0.256175 0.256175 0.256175 4591.56 4591.56 5235.64 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.205876 0.205876 0.205876 0.205876 3800.25 3800.25 5253.60 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.148482 0.148482 0.148482 0.148482 2877.67 2877.67 3647.19 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.146970 0.146970 0.146970 0.146970 2855.82 2855.82 3646.93 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.185209 0.185209 0.185209 0.185209 3466.03 3466.03 3627.68 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.186363 0.186363 0.186363 0.186363 3482.07 3482.07 3627.62 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.290536 0.290536 0.290536 0.290536 5072.40 5072.40 5396.09 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.270936 0.270936 0.270936 0.270936 4798.67 4798.67 5421.91 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.255868 0.255868 0.255868 0.255868 4627.16 4627.16 5381.03 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.206887 0.206887 0.206887 0.206887 3852.08 3852.08 5406.62 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.150072 0.150072 0.150072 0.150072 2921.93 2921.93 3730.27 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.148569 0.148569 0.148569 0.148569 2900.12 2900.12 3729.94 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.186440 0.186440 0.186440 0.186440 3506.82 3506.82 3704.95 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.187449 0.187449 0.187449 0.187449 3520.88 3520.88 3704.64 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.293379 0.293379 0.293379 0.293379 5145.80 5145.80 5505.93 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.274160 0.274160 0.274160 0.274160 4876.88 4876.88 5534.21 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.259017 0.259017 0.259017 0.259017 4703.77 4703.77 5488.42 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.209964 0.209964 0.209964 0.209964 3926.14 3926.14 5516.70 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.153491 0.153491 0.153491 0.153491 2988.53 2988.53 3784.49 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.151995 0.151995 0.151995 0.151995 2966.79 2966.79 3784.11 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.189592 0.189592 0.189592 0.189592 3570.36 3570.36 3756.57 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.190580 0.190580 0.190580 0.190580 3584.12 3584.12 3756.19 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.289711 0.289711 0.289711 0.289711 5122.82 5122.82 5671.96 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.270620 0.270620 0.270620 0.270620 4855.04 4855.04 5704.06 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.255802 0.255802 0.255802 0.255802 4685.66 4685.66 5652.65 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.206414 0.206414 0.206414 0.206414 3900.89 3900.89 5684.76 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.150406 0.150406 0.150406 0.150406 2958.72 2958.72 3902.53 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.148924 0.148924 0.148924 0.148924 2937.04 2937.04 3902.11 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.186271 0.186271 0.186271 0.186271 3539.64 3539.64 3870.75 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.187256 0.187256 0.187256 0.187256 3553.40 3553.40 3870.32 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.288466 0.288466 0.288466 0.288466 5130.10 5130.10 5798.62 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.269571 0.269571 0.269571 0.269571 4864.54 4864.54 5832.74 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.254941 0.254941 0.254941 0.254941 4697.22 4697.22 5777.85 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.207200 0.207200 0.207200 0.207200 3943.14 3943.14 5811.98 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.149632 0.149632 0.149632 0.149632 2960.23 2960.23 3986.95 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.148160 0.148160 0.148160 0.148160 2938.61 2938.61 3986.49 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.185274 0.185274 0.185274 0.185274 3539.62 3539.62 3953.13 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.186257 0.186257 0.186257 0.186257 3553.39 3553.39 3952.68 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.288570 0.288570 0.288570 0.288570 5153.68 5153.68 5926.49 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.269850 0.269850 0.269850 0.269850 4890.11 4890.11 5961.88 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.255301 0.255301 0.255301 0.255301 4723.47 4723.47 5904.48 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.213252 0.213252 0.213252 0.213252 4078.04 4078.04 5939.88 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.150149 0.150149 0.150149 0.150149 2979.08 2979.08 4076.71 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.148687 0.148687 0.148687 0.148687 2957.57 2957.57 4076.23 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.185525 0.185525 0.185525 0.185525 3555.76 3555.76 4041.61 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.186510 0.186510 0.186510 0.186510 3569.57 3569.57 4041.14 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.297135 0.297135 0.297135 0.297135 5294.95 5294.95 6226.38 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.278110 0.278110 0.278110 0.278110 5026.99 5026.99 6259.27 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.261390 0.261390 0.261390 0.261390 4832.24 4832.24 6203.10 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.227266 0.227266 0.227266 0.227266 4358.30 4358.30 6236.00 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.157415 0.157415 0.157415 0.157415 3095.33 3095.33 4326.24 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.155934 0.155934 0.155934 0.155934 3073.58 3073.58 4325.73 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.190564 0.190564 0.190564 0.190564 3641.25 3641.25 4293.20 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.191614 0.191614 0.191614 0.191614 3654.08 3654.08 4292.69 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.349408 0.349408 0.349408 0.349408 6081.21 6081.21 7199.82 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.322882 0.322882 0.322882 0.322882 5681.31 5681.31 7240.76 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.314267 0.314267 0.314267 0.314267 5595.00 5595.00 7177.38 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.273755 0.273755 0.273755 0.273755 5069.94 5069.94 7218.33 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.185708 0.185708 0.185708 0.185708 3532.95 3532.95 5357.72 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.185684 0.185684 0.185684 0.185684 3604.80 3604.80 5357.20 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.254328 0.254328 0.254328 0.254328 4548.17 4548.17 5313.53 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.255299 0.255299 0.255299 0.255299 4561.52 4561.52 5313.01 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.219053
AIRLOOP G NW SUPPLY FAN 0.204997
AIRLOOP OFFICE SUPPLY FAN 0.294756
AIRLOOP G NE SUPPLY FAN 0.174036
AIRLOOP G N1 SUPPLY FAN 0.116007
AIRLOOP G N2 SUPPLY FAN 0.116005
AIRLOOP G S1 SUPPLY FAN 0.133628
AIRLOOP G S2 SUPPLY FAN 0.138923
AIRLOOP F2 SW SUPPLY FAN 0.288759
AIRLOOP F2 NW SUPPLY FAN 0.267387
AIRLOOP F2 SE SUPPLY FAN 0.270005
AIRLOOP F2 NE SUPPLY FAN 0.202129
AIRLOOP F2 N1 SUPPLY FAN 0.144185
AIRLOOP F2 N2 SUPPLY FAN 0.142654
AIRLOOP F2 S1 SUPPLY FAN 0.181395
AIRLOOP F2 S2 SUPPLY FAN 0.183568
AIRLOOP F3 SW SUPPLY FAN 0.289899
AIRLOOP F3 NW SUPPLY FAN 0.269888
AIRLOOP F3 SE SUPPLY FAN 0.256175
AIRLOOP F3 NE SUPPLY FAN 0.205876
AIRLOOP F3 N1 SUPPLY FAN 0.148482
AIRLOOP F3 N2 SUPPLY FAN 0.146970
AIRLOOP F3 S1 SUPPLY FAN 0.185209
AIRLOOP F3 S2 SUPPLY FAN 0.186363
AIRLOOP F4 SW SUPPLY FAN 0.290536
AIRLOOP F4 NW SUPPLY FAN 0.270936
AIRLOOP F4 SE SUPPLY FAN 0.255868
AIRLOOP F4 NE SUPPLY FAN 0.206887
AIRLOOP F4 N1 SUPPLY FAN 0.150072
AIRLOOP F4 N2 SUPPLY FAN 0.148569
AIRLOOP F4 S1 SUPPLY FAN 0.186440
AIRLOOP F4 S2 SUPPLY FAN 0.187449
AIRLOOP M SW SUPPLY FAN 0.293379
AIRLOOP M NW SUPPLY FAN 0.274160
AIRLOOP M SE SUPPLY FAN 0.259017
AIRLOOP M NE SUPPLY FAN 0.209964
AIRLOOP M N1 SUPPLY FAN 0.153491
AIRLOOP M N2 SUPPLY FAN 0.151995
AIRLOOP M S1 SUPPLY FAN 0.189592
AIRLOOP M S2 SUPPLY FAN 0.190580
AIRLOOP F6 SW SUPPLY FAN 0.289711
AIRLOOP F6 NW SUPPLY FAN 0.270620
AIRLOOP F6 SE SUPPLY FAN 0.255802
AIRLOOP F6 NE SUPPLY FAN 0.206414
AIRLOOP F6 N1 SUPPLY FAN 0.150406
AIRLOOP F6 N2 SUPPLY FAN 0.148924
AIRLOOP F6 S1 SUPPLY FAN 0.186271
AIRLOOP F6 S2 SUPPLY FAN 0.187256
AIRLOOP F7 SW SUPPLY FAN 0.288466
AIRLOOP F7 NW SUPPLY FAN 0.269571
AIRLOOP F7 SE SUPPLY FAN 0.254941
AIRLOOP F7 NE SUPPLY FAN 0.207200
AIRLOOP F7 N1 SUPPLY FAN 0.149632
AIRLOOP F7 N2 SUPPLY FAN 0.148160
AIRLOOP F7 S1 SUPPLY FAN 0.185274
AIRLOOP F7 S2 SUPPLY FAN 0.186257
AIRLOOP F8 SW SUPPLY FAN 0.288570
AIRLOOP F8 NW SUPPLY FAN 0.269850
AIRLOOP F8 SE SUPPLY FAN 0.255301
AIRLOOP F8 NE SUPPLY FAN 0.213252
AIRLOOP F8 N1 SUPPLY FAN 0.150149
AIRLOOP F8 N2 SUPPLY FAN 0.148687
AIRLOOP F8 S1 SUPPLY FAN 0.185525
AIRLOOP F8 S2 SUPPLY FAN 0.186510
AIRLOOP F9 SW SUPPLY FAN 0.297135
AIRLOOP F9 NW SUPPLY FAN 0.278110
AIRLOOP F9 SE SUPPLY FAN 0.261390
AIRLOOP F9 NE SUPPLY FAN 0.227266
AIRLOOP F9 N1 SUPPLY FAN 0.157415
AIRLOOP F9 N2 SUPPLY FAN 0.155934
AIRLOOP F9 S1 SUPPLY FAN 0.190564
AIRLOOP F9 S2 SUPPLY FAN 0.191614
AIRLOOP T SW SUPPLY FAN 0.349408
AIRLOOP T NW SUPPLY FAN 0.322882
AIRLOOP T SE SUPPLY FAN 0.314267
AIRLOOP T NE SUPPLY FAN 0.273755
AIRLOOP T N1 SUPPLY FAN 0.185708
AIRLOOP T N2 SUPPLY FAN 0.185684
AIRLOOP T S1 SUPPLY FAN 0.254328
AIRLOOP T S2 SUPPLY FAN 0.255299


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.219053 3887.38 0.000085
HEAT PUMP HEATING MODE AIRLOOP G NW 0.204997 3684.09 0.000080
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.294756 5271.71 0.000115
HEAT PUMP HEATING MODE AIRLOOP G NE 0.174036 3354.42 0.000073
HEAT PUMP HEATING MODE AIRLOOP G N1 0.116007 2420.09 0.000053
HEAT PUMP HEATING MODE AIRLOOP G N2 0.116005 2432.99 0.000053
HEAT PUMP HEATING MODE AIRLOOP G S1 0.133628 2659.02 0.000058
HEAT PUMP HEATING MODE AIRLOOP G S2 0.138923 2733.18 0.000060
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.288759 4950.17 0.000108
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.267387 4645.28 0.000101
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.270005 4730.04 0.000103
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.202129 3696.78 0.000081
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.144185 2787.43 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.142654 2765.36 0.000060
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.181395 3381.17 0.000074
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.183568 3411.40 0.000075
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.289899 5022.00 0.000110
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.269888 4735.20 0.000103
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.256175 4591.56 0.000100
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.205876 3800.25 0.000083
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.148482 2877.67 0.000063
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.146970 2855.82 0.000062
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.185209 3466.03 0.000076
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.186363 3482.07 0.000076
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.290536 5072.40 0.000111
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.270936 4798.67 0.000105
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.255868 4627.16 0.000101
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.206887 3852.08 0.000084
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.150072 2921.93 0.000064
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.148569 2900.12 0.000063
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.186440 3506.82 0.000077
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.187449 3520.88 0.000077
HEAT PUMP HEATING MODE AIRLOOP M SW 0.293379 5145.80 0.000112
HEAT PUMP HEATING MODE AIRLOOP M NW 0.274160 4876.88 0.000107
HEAT PUMP HEATING MODE AIRLOOP M SE 0.259017 4703.77 0.000103
HEAT PUMP HEATING MODE AIRLOOP M NE 0.209964 3926.14 0.000086
HEAT PUMP HEATING MODE AIRLOOP M N1 0.153491 2988.53 0.000065
HEAT PUMP HEATING MODE AIRLOOP M N2 0.151995 2966.79 0.000065
HEAT PUMP HEATING MODE AIRLOOP M S1 0.189592 3570.36 0.000078
HEAT PUMP HEATING MODE AIRLOOP M S2 0.190580 3584.12 0.000078
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.289711 5122.82 0.000112
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.270620 4855.04 0.000106
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.255802 4685.66 0.000102
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.206414 3900.89 0.000085
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.150406 2958.72 0.000065
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.148924 2937.04 0.000064
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.186271 3539.64 0.000077
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.187256 3553.40 0.000078
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.288466 5130.10 0.000112
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.269571 4864.54 0.000106
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.254941 4697.22 0.000103
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.207200 3943.14 0.000086
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.149632 2960.23 0.000065
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.148160 2938.61 0.000064
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.185274 3539.62 0.000077
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.186257 3553.39 0.000078
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.288570 5153.68 0.000113
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.269850 4890.11 0.000107
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.255301 4723.47 0.000103
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.213252 4078.04 0.000089
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.150149 2979.08 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.148687 2957.57 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.185525 3555.76 0.000078
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.186510 3569.57 0.000078
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.297135 5294.95 0.000116
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.278110 5026.99 0.000110
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.261390 4832.24 0.000106
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.227266 4358.30 0.000095
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.157415 3095.33 0.000068
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.155934 3073.58 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.190564 3641.25 0.000080
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.191614 3654.08 0.000080
HEAT PUMP HEATING MODE AIRLOOP T SW 0.349408 6081.21 0.000133
HEAT PUMP HEATING MODE AIRLOOP T NW 0.322882 5681.31 0.000124
HEAT PUMP HEATING MODE AIRLOOP T SE 0.314267 5595.00 0.000122
HEAT PUMP HEATING MODE AIRLOOP T NE 0.273755 5069.94 0.000111
HEAT PUMP HEATING MODE AIRLOOP T N1 0.185708 3532.95 0.000077
HEAT PUMP HEATING MODE AIRLOOP T N2 0.185684 3604.80 0.000079
HEAT PUMP HEATING MODE AIRLOOP T S1 0.254328 4548.17 0.000099
HEAT PUMP HEATING MODE AIRLOOP T S2 0.255299 4561.52 0.000100


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 5102.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 5111.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 6247.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 5110.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 3884.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 3884.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 3873.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 3882.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 5139.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 5150.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 5155.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 5142.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 3623.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 3623.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 3615.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 3617.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 5245.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 5265.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 5235.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 5253.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 3647.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 3646.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 3627.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 3627.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 5396.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 5421.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 5381.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 5406.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 3730.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 3729.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 3704.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 3704.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 5505.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 5534.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 5488.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 5516.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 3784.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 3784.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 3756.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 3756.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 5671.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 5704.06
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 5652.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 5684.76
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 3902.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 3902.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 3870.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 3870.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 5798.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 5832.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 5777.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 5811.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 3986.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 3986.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 3953.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 3952.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 5926.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 5961.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 5904.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 5939.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 4076.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 4076.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 4041.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 4041.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 6226.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 6259.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 6203.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 6236.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 4326.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 4325.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 4293.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 4292.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 7199.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 7240.76
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 7177.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 7218.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 5357.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 5357.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 5313.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 5313.01


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.006932 7.80


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.006932


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.006932 3346.48 9.23 9900.66


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.006932 1768.07



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.76 -7.7
March 21.86 0.33
April 22.36 7.02
May 23.06 14.19
June 24.08 19.16
July 24.24 20.92
August 24.23 20.05
September 23.79 15.39
October 22.43 7.43
November 21.95 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.77 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.12 7.02
May 22.85 14.19
June 24.07 19.16
July 24.23 20.92
August 24.20 20.05
September 23.54 15.39
October 21.91 7.43
November 21.77 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.63 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.23 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -12.6
February 21.79 -7.7
March 21.98 0.33
April 22.52 7.02
May 23.43 14.19
June 24.14 19.16
July 24.36 20.92
August 24.33 20.05
September 23.84 15.39
October 22.52 7.43
November 22.01 -0.0
December 21.74 -7.6
     
Annual Sum or Average 22.87 6.46
Minimum of Months 21.73 -12.6
Maximum of Months 24.36 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 22.07 7.02
May 22.83 14.19
June 24.07 19.16
July 24.24 20.92
August 24.19 20.05
September 23.53 15.39
October 21.83 7.43
November 21.74 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.61 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.71 0.33
April 22.01 7.02
May 22.62 14.19
June 24.02 19.16
July 24.18 20.92
August 24.13 20.05
September 23.53 15.39
October 21.84 7.43
November 21.76 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.58 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.18 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.71 0.33
April 22.01 7.02
May 22.62 14.19
June 24.02 19.16
July 24.18 20.92
August 24.13 20.05
September 23.53 15.39
October 21.83 7.43
November 21.76 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.58 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.18 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.86 0.33
April 22.29 7.02
May 22.92 14.19
June 24.07 19.16
July 24.20 20.92
August 24.21 20.05
September 23.87 15.39
October 22.51 7.43
November 22.00 -0.0
December 21.73 -7.6
     
Annual Sum or Average 22.77 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.21 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.87 0.33
April 22.31 7.02
May 22.97 14.19
June 24.09 19.16
July 24.21 20.92
August 24.21 20.05
September 23.89 15.39
October 22.54 7.43
November 22.01 -0.0
December 21.73 -7.6
     
Annual Sum or Average 22.78 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.21 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.78 -12.6
February 15.04 -7.7
March 17.20 0.33
April 19.27 7.02
May 21.71 14.19
June 24.20 19.16
July 24.86 20.92
August 24.64 20.05
September 23.12 15.39
October 19.51 7.43
November 17.10 -0.0
December 14.96 -7.6
     
Annual Sum or Average 19.64 6.46
Minimum of Months 13.78 -12.6
Maximum of Months 24.86 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 22.05 0.33
April 22.75 7.02
May 23.90 14.19
June 24.28 19.16
July 24.32 20.92
August 24.33 20.05
September 24.01 15.39
October 22.96 7.43
November 22.24 -0.0
December 21.74 -7.6
     
Annual Sum or Average 23.02 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.38 7.02
May 23.67 14.19
June 24.26 19.16
July 24.32 20.92
August 24.31 20.05
September 23.75 15.39
October 22.10 7.43
November 21.91 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.32 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 22.06 0.33
April 22.74 7.02
May 23.99 14.19
June 24.30 19.16
July 24.34 20.92
August 24.35 20.05
September 24.06 15.39
October 23.00 7.43
November 22.25 -0.0
December 21.73 -7.6
     
Annual Sum or Average 23.04 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.29 7.02
May 23.61 14.19
June 24.25 19.16
July 24.32 20.92
August 24.31 20.05
September 23.69 15.39
October 21.95 7.43
November 21.84 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.76 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.32 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.76 0.33
April 22.26 7.02
May 23.47 14.19
June 24.25 19.16
July 24.28 20.92
August 24.27 20.05
September 23.75 15.39
October 22.04 7.43
November 21.91 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.76 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.26 7.02
May 23.46 14.19
June 24.25 19.16
July 24.28 20.92
August 24.27 20.05
September 23.74 15.39
October 22.03 7.43
November 21.91 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.76 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.86 -7.7
March 22.10 0.33
April 22.74 7.02
May 23.84 14.19
June 24.28 19.16
July 24.29 20.92
August 24.31 20.05
September 24.10 15.39
October 23.20 7.43
November 22.36 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.06 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.87 -7.7
March 22.11 0.33
April 22.74 7.02
May 23.85 14.19
June 24.29 19.16
July 24.30 20.92
August 24.31 20.05
September 24.11 15.39
October 23.22 7.43
November 22.37 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.06 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -12.6
February 21.08 -7.7
March 21.91 0.33
April 23.17 7.02
May 24.90 14.19
June 26.08 19.16
July 26.33 20.92
August 26.20 20.05
September 25.41 15.39
October 23.25 7.43
November 21.89 -0.0
December 20.81 -7.6
     
Annual Sum or Average 23.48 6.46
Minimum of Months 20.52 -12.6
Maximum of Months 26.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 22.06 0.33
April 22.78 7.02
May 24.00 14.19
June 24.29 19.16
July 24.32 20.92
August 24.33 20.05
September 24.01 15.39
October 23.03 7.43
November 22.32 -0.0
December 21.74 -7.6
     
Annual Sum or Average 23.04 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.78 0.33
April 22.42 7.02
May 23.81 14.19
June 24.28 19.16
July 24.32 20.92
August 24.31 20.05
September 23.75 15.39
October 22.13 7.43
November 21.96 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.83 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.32 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.81 -7.7
March 22.03 0.33
April 22.72 7.02
May 24.02 14.19
June 24.29 19.16
July 24.32 20.92
August 24.34 20.05
September 24.02 15.39
October 23.00 7.43
November 22.28 -0.0
December 21.73 -7.6
     
Annual Sum or Average 23.03 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.34 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.33 7.02
May 23.75 14.19
June 24.27 19.16
July 24.31 20.92
August 24.31 20.05
September 23.69 15.39
October 21.97 7.43
November 21.88 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.79 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.34 7.02
May 23.68 14.19
June 24.28 19.16
July 24.28 20.92
August 24.27 20.05
September 23.78 15.39
October 22.11 7.43
November 21.98 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.33 7.02
May 23.67 14.19
June 24.28 19.16
July 24.28 20.92
August 24.27 20.05
September 23.77 15.39
October 22.09 7.43
November 21.97 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.80 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.89 -7.7
March 22.15 0.33
April 22.83 7.02
May 23.99 14.19
June 24.30 19.16
July 24.29 20.92
August 24.31 20.05
September 24.12 15.39
October 23.36 7.43
November 22.45 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.11 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.89 -7.7
March 22.15 0.33
April 22.82 7.02
May 24.00 14.19
June 24.30 19.16
July 24.29 20.92
August 24.31 20.05
September 24.12 15.39
October 23.36 7.43
November 22.45 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.11 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 -12.6
February 21.58 -7.7
March 22.33 0.33
April 23.59 7.02
May 25.40 14.19
June 26.29 19.16
July 26.47 20.92
August 26.35 20.05
September 25.61 15.39
October 23.64 7.43
November 22.34 -0.0
December 21.28 -7.6
     
Annual Sum or Average 23.84 6.46
Minimum of Months 21.06 -12.6
Maximum of Months 26.47 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.81 -7.7
March 22.03 0.33
April 22.77 7.02
May 24.02 14.19
June 24.29 19.16
July 24.31 20.92
August 24.32 20.05
September 23.99 15.39
October 23.00 7.43
November 22.32 -0.0
December 21.73 -7.6
     
Annual Sum or Average 23.03 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.32 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.43 7.02
May 23.84 14.19
June 24.27 19.16
July 24.31 20.92
August 24.30 20.05
September 23.73 15.39
October 22.12 7.43
November 21.97 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.83 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.80 -7.7
March 22.00 0.33
April 22.70 7.02
May 24.02 14.19
June 24.29 19.16
July 24.32 20.92
August 24.33 20.05
September 24.00 15.39
October 22.95 7.43
November 22.29 -0.0
December 21.72 -7.6
     
Annual Sum or Average 23.02 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.35 7.02
May 23.78 14.19
June 24.26 19.16
July 24.31 20.92
August 24.30 20.05
September 23.67 15.39
October 21.97 7.43
November 21.89 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.79 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.37 7.02
May 23.74 14.19
June 24.28 19.16
July 24.28 20.92
August 24.27 20.05
September 23.77 15.39
October 22.12 7.43
November 22.00 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.81 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.36 7.02
May 23.74 14.19
June 24.28 19.16
July 24.28 20.92
August 24.26 20.05
September 23.76 15.39
October 22.10 7.43
November 21.99 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.81 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.88 -7.7
March 22.15 0.33
April 22.84 7.02
May 24.03 14.19
June 24.30 19.16
July 24.29 20.92
August 24.30 20.05
September 24.11 15.39
October 23.37 7.43
November 22.46 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.11 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.88 -7.7
March 22.15 0.33
April 22.83 7.02
May 24.03 14.19
June 24.30 19.16
July 24.29 20.92
August 24.30 20.05
September 24.11 15.39
October 23.37 7.43
November 22.46 -0.0
December 21.78 -7.6
     
Annual Sum or Average 23.11 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.19 -12.6
February 21.71 -7.7
March 22.45 0.33
April 23.73 7.02
May 25.57 14.19
June 26.40 19.16
July 26.56 20.92
August 26.44 20.05
September 25.70 15.39
October 23.76 7.43
November 22.49 -0.0
December 21.41 -7.6
     
Annual Sum or Average 23.96 6.46
Minimum of Months 21.19 -12.6
Maximum of Months 26.56 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.81 -7.7
March 22.01 0.33
April 22.74 7.02
May 24.00 14.19
June 24.28 19.16
July 24.31 20.92
August 24.31 20.05
September 23.98 15.39
October 22.97 7.43
November 22.32 -0.0
December 21.73 -7.6
     
Annual Sum or Average 23.02 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.42 7.02
May 23.83 14.19
June 24.27 19.16
July 24.30 20.92
August 24.30 20.05
September 23.71 15.39
October 22.11 7.43
November 21.98 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.82 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.79 -7.7
March 21.98 0.33
April 22.68 7.02
May 24.00 14.19
June 24.28 19.16
July 24.31 20.92
August 24.32 20.05
September 23.98 15.39
October 22.92 7.43
November 22.28 -0.0
December 21.72 -7.6
     
Annual Sum or Average 23.01 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.32 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.34 7.02
May 23.77 14.19
June 24.26 19.16
July 24.30 20.92
August 24.29 20.05
September 23.66 15.39
October 21.96 7.43
November 21.90 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.78 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.37 7.02
May 23.75 14.19
June 24.28 19.16
July 24.27 20.92
August 24.26 20.05
September 23.77 15.39
October 22.13 7.43
November 22.02 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.82 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.77 0.33
April 22.37 7.02
May 23.74 14.19
June 24.28 19.16
July 24.27 20.92
August 24.26 20.05
September 23.76 15.39
October 22.11 7.43
November 22.01 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.81 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.88 -7.7
March 22.13 0.33
April 22.83 7.02
May 24.02 14.19
June 24.30 19.16
July 24.28 20.92
August 24.29 20.05
September 24.10 15.39
October 23.36 7.43
November 22.46 -0.0
December 21.77 -7.6
     
Annual Sum or Average 23.10 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -12.6
February 21.88 -7.7
March 22.13 0.33
April 22.82 7.02
May 24.03 14.19
June 24.30 19.16
July 24.28 20.92
August 24.29 20.05
September 24.11 15.39
October 23.36 7.43
November 22.46 -0.0
December 21.77 -7.6
     
Annual Sum or Average 23.10 6.46
Minimum of Months 21.74 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -12.6
February 22.35 -7.7
March 23.08 0.33
April 24.35 7.02
May 26.18 14.19
June 27.00 19.16
July 27.16 20.92
August 27.03 20.05
September 26.30 15.39
October 24.37 7.43
November 23.13 -0.0
December 22.05 -7.6
     
Annual Sum or Average 24.58 6.46
Minimum of Months 21.81 -12.6
Maximum of Months 27.16 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.79 -7.7
March 21.96 0.33
April 22.67 7.02
May 23.93 14.19
June 24.25 19.16
July 24.29 20.92
August 24.29 20.05
September 23.92 15.39
October 22.85 7.43
November 22.28 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.98 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.29 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.36 7.02
May 23.74 14.19
June 24.24 19.16
July 24.29 20.92
August 24.28 20.05
September 23.63 15.39
October 22.04 7.43
November 21.94 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.79 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.29 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.78 -7.7
March 21.93 0.33
April 22.62 7.02
May 23.93 14.19
June 24.26 19.16
July 24.29 20.92
August 24.30 20.05
September 23.92 15.39
October 22.79 7.43
November 22.24 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.96 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.30 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.30 7.02
May 23.68 14.19
June 24.23 19.16
July 24.28 20.92
August 24.27 20.05
September 23.58 15.39
October 21.91 7.43
November 21.87 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.75 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.76 0.33
April 22.32 7.02
May 23.65 14.19
June 24.26 19.16
July 24.25 20.92
August 24.23 20.05
September 23.68 15.39
October 22.05 7.43
November 21.98 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.78 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.32 7.02
May 23.65 14.19
June 24.26 19.16
July 24.25 20.92
August 24.23 20.05
September 23.67 15.39
October 22.04 7.43
November 21.97 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.78 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -12.6
February 21.85 -7.7
March 22.08 0.33
April 22.76 7.02
May 23.95 14.19
June 24.28 19.16
July 24.26 20.92
August 24.27 20.05
September 24.05 15.39
October 23.24 7.43
November 22.43 -0.0
December 21.76 -7.6
     
Annual Sum or Average 23.06 6.46
Minimum of Months 21.73 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -12.6
February 21.85 -7.7
March 22.08 0.33
April 22.75 7.02
May 23.95 14.19
June 24.28 19.16
July 24.26 20.92
August 24.27 20.05
September 24.05 15.39
October 23.23 7.43
November 22.43 -0.0
December 21.76 -7.6
     
Annual Sum or Average 23.06 6.46
Minimum of Months 21.73 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -12.6
February 21.64 -7.7
March 22.36 0.33
April 23.64 7.02
May 25.49 14.19
June 26.36 19.16
July 26.53 20.92
August 26.40 20.05
September 25.61 15.39
October 23.64 7.43
November 22.42 -0.0
December 21.34 -7.6
     
Annual Sum or Average 23.89 6.46
Minimum of Months 21.12 -12.6
Maximum of Months 26.53 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.78 -7.7
March 21.93 0.33
April 22.62 7.02
May 23.87 14.19
June 24.24 19.16
July 24.28 20.92
August 24.28 20.05
September 23.87 15.39
October 22.76 7.43
November 22.24 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.95 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.33 7.02
May 23.67 14.19
June 24.22 19.16
July 24.27 20.92
August 24.26 20.05
September 23.57 15.39
October 21.99 7.43
November 21.92 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.76 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.27 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.90 0.33
April 22.57 7.02
May 23.87 14.19
June 24.23 19.16
July 24.28 20.92
August 24.28 20.05
September 23.87 15.39
October 22.70 7.43
November 22.20 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.93 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.28 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 22.27 7.02
May 23.61 14.19
June 24.21 19.16
July 24.27 20.92
August 24.25 20.05
September 23.52 15.39
October 21.88 7.43
November 21.84 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.73 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.27 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.29 7.02
May 23.58 14.19
June 24.24 19.16
July 24.23 20.92
August 24.22 20.05
September 23.61 15.39
October 22.00 7.43
November 21.95 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.75 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.28 7.02
May 23.58 14.19
June 24.23 19.16
July 24.23 20.92
August 24.22 20.05
September 23.61 15.39
October 21.99 7.43
November 21.95 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.75 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.23 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.84 -7.7
March 22.04 0.33
April 22.70 7.02
May 23.90 14.19
June 24.26 19.16
July 24.25 20.92
August 24.26 20.05
September 24.01 15.39
October 23.13 7.43
November 22.40 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.03 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.83 -7.7
March 22.04 0.33
April 22.70 7.02
May 23.90 14.19
June 24.26 19.16
July 24.25 20.92
August 24.26 20.05
September 24.01 15.39
October 23.13 7.43
November 22.40 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.03 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.96 -12.6
February 21.48 -7.7
March 22.19 0.33
April 23.48 7.02
May 25.32 14.19
June 26.24 19.16
July 26.43 20.92
August 26.29 20.05
September 25.46 15.39
October 23.45 7.43
November 22.25 -0.0
December 21.19 -7.6
     
Annual Sum or Average 23.74 6.46
Minimum of Months 20.96 -12.6
Maximum of Months 26.43 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.90 0.33
April 22.58 7.02
May 23.82 14.19
June 24.22 19.16
July 24.27 20.92
August 24.27 20.05
September 23.83 15.39
October 22.68 7.43
November 22.20 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.92 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.27 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.30 7.02
May 23.60 14.19
June 24.20 19.16
July 24.26 20.92
August 24.25 20.05
September 23.52 15.39
October 21.96 7.43
November 21.89 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.74 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.76 -7.7
March 21.88 0.33
April 22.54 7.02
May 23.82 14.19
June 24.21 19.16
July 24.27 20.92
August 24.27 20.05
September 23.83 15.39
October 22.61 7.43
November 22.16 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.90 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.27 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 22.25 7.02
May 23.55 14.19
June 24.18 19.16
July 24.26 20.92
August 24.24 20.05
September 23.48 15.39
October 21.86 7.43
November 21.82 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.71 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.26 7.02
May 23.52 14.19
June 24.21 19.16
July 24.22 20.92
August 24.20 20.05
September 23.55 15.39
October 21.96 7.43
November 21.93 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.73 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.22 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.26 7.02
May 23.52 14.19
June 24.21 19.16
July 24.22 20.92
August 24.20 20.05
September 23.55 15.39
October 21.95 7.43
November 21.92 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.73 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.22 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 22.00 0.33
April 22.66 7.02
May 23.85 14.19
June 24.24 19.16
July 24.24 20.92
August 24.24 20.05
September 23.97 15.39
October 23.03 7.43
November 22.37 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.00 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 22.00 0.33
April 22.66 7.02
May 23.85 14.19
June 24.24 19.16
July 24.24 20.92
August 24.24 20.05
September 23.97 15.39
October 23.03 7.43
November 22.37 -0.0
December 21.75 -7.6
     
Annual Sum or Average 23.00 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.87 -12.6
February 21.38 -7.7
March 22.10 0.33
April 23.39 7.02
May 25.23 14.19
June 26.20 19.16
July 26.41 20.92
August 26.26 20.05
September 25.38 15.39
October 23.34 7.43
November 22.14 -0.0
December 21.10 -7.6
     
Annual Sum or Average 23.66 6.46
Minimum of Months 20.87 -12.6
Maximum of Months 26.41 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.77 -7.7
March 21.88 0.33
April 22.54 7.02
May 23.75 14.19
June 24.18 19.16
July 24.26 20.92
August 24.25 20.05
September 23.75 15.39
October 22.58 7.43
November 22.14 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.88 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.28 7.02
May 23.53 14.19
June 24.16 19.16
July 24.25 20.92
August 24.23 20.05
September 23.46 15.39
October 21.93 7.43
November 21.86 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.72 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.25 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.75 -7.7
March 21.85 0.33
April 22.50 7.02
May 23.75 14.19
June 24.18 19.16
July 24.26 20.92
August 24.26 20.05
September 23.75 15.39
October 22.52 7.43
November 22.10 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.87 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.26 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.72 0.33
April 22.24 7.02
May 23.49 14.19
June 24.15 19.16
July 24.25 20.92
August 24.22 20.05
September 23.42 15.39
October 21.85 7.43
November 21.80 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.69 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.25 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.24 7.02
May 23.45 14.19
June 24.18 19.16
July 24.21 20.92
August 24.19 20.05
September 23.47 15.39
October 21.93 7.43
November 21.90 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.70 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.21 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.24 7.02
May 23.45 14.19
June 24.18 19.16
July 24.21 20.92
August 24.18 20.05
September 23.47 15.39
October 21.92 7.43
November 21.89 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.70 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.21 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.81 -7.7
March 21.97 0.33
April 22.61 7.02
May 23.78 14.19
June 24.21 19.16
July 24.23 20.92
August 24.23 20.05
September 23.89 15.39
October 22.89 7.43
November 22.30 -0.0
December 21.74 -7.6
     
Annual Sum or Average 22.95 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.23 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.81 -7.7
March 21.96 0.33
April 22.61 7.02
May 23.78 14.19
June 24.21 19.16
July 24.23 20.92
August 24.23 20.05
September 23.89 15.39
October 22.88 7.43
November 22.30 -0.0
December 21.74 -7.6
     
Annual Sum or Average 22.95 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.23 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 -12.6
February 21.17 -7.7
March 21.93 0.33
April 23.28 7.02
May 25.15 14.19
June 26.20 19.16
July 26.45 20.92
August 26.27 20.05
September 25.28 15.39
October 23.17 7.43
November 21.93 -0.0
December 20.88 -7.6
     
Annual Sum or Average 23.54 6.46
Minimum of Months 20.63 -12.6
Maximum of Months 26.45 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.79 -7.7
March 21.89 0.33
April 22.48 7.02
May 23.49 14.19
June 24.03 19.16
July 24.18 20.92
August 24.13 20.05
September 23.51 15.39
October 22.46 7.43
November 22.05 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.79 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.18 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.75 0.33
April 22.28 7.02
May 23.33 14.19
June 24.01 19.16
July 24.17 20.92
August 24.10 20.05
September 23.27 15.39
October 21.96 7.43
November 21.85 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.66 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.17 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -12.6
February 21.77 -7.7
March 21.87 0.33
April 22.45 7.02
May 23.50 14.19
June 24.03 19.16
July 24.20 20.92
August 24.13 20.05
September 23.52 15.39
October 22.42 7.43
November 22.01 -0.0
December 21.71 -7.6
     
Annual Sum or Average 22.78 6.46
Minimum of Months 21.71 -12.6
Maximum of Months 24.20 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.73 0.33
April 22.26 7.02
May 23.30 14.19
June 24.00 19.16
July 24.18 20.92
August 24.08 20.05
September 23.26 15.39
October 21.86 7.43
November 21.80 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.64 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.18 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.24 7.02
May 23.26 14.19
June 24.02 19.16
July 24.14 20.92
August 24.06 20.05
September 23.26 15.39
October 21.90 7.43
November 21.86 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.64 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.14 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -12.6
February 21.70 -7.7
March 21.74 0.33
April 22.23 7.02
May 23.26 14.19
June 24.02 19.16
July 24.13 20.92
August 24.05 20.05
September 23.26 15.39
October 21.89 7.43
November 21.85 -0.0
December 21.70 -7.6
     
Annual Sum or Average 22.63 6.46
Minimum of Months 21.70 -12.6
Maximum of Months 24.13 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 21.96 0.33
April 22.53 7.02
May 23.56 14.19
June 24.08 19.16
July 24.17 20.92
August 24.13 20.05
September 23.63 15.39
October 22.62 7.43
November 22.17 -0.0
December 21.75 -7.6
     
Annual Sum or Average 22.85 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.17 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 21.82 -7.7
March 21.96 0.33
April 22.52 7.02
May 23.56 14.19
June 24.08 19.16
July 24.17 20.92
August 24.13 20.05
September 23.64 15.39
October 22.61 7.43
November 22.17 -0.0
December 21.75 -7.6
     
Annual Sum or Average 22.85 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 24.17 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.05 -12.6
February 20.77 -7.7
March 21.86 0.33
April 23.46 7.02
May 25.52 14.19
June 26.77 19.16
July 27.13 20.92
August 26.84 20.05
September 25.55 15.39
October 23.22 7.43
November 21.71 -0.0
December 20.46 -7.6
     
Annual Sum or Average 23.63 6.46
Minimum of Months 20.05 -12.6
Maximum of Months 27.13 20.92



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:11

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.320446E+12 219199.929 18-JAN-19:00 25049.151 51564.864 19230.898 109815.304 0.000 10720.100 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.263489E+12 191742.859 01-FEB-20:00 25049.151 49704.829 19230.898 84287.312 0.000 10720.100 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.254434E+12 148769.929 05-MAR-18:00 22204.399 56867.515 19230.898 36796.130 0.000 10720.100 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.225753E+12 176245.881 16-APR-17:00 22204.399 56867.515 19230.898 0.000 72367.751 0.000 1804.998 2624.431 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.220943E+12 169959.014 31-MAY-18:30 25049.151 51564.864 19230.898 0.000 68795.245 0.000 1804.998 2499.244 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.264879E+12 183025.478 24-JUN-17:30 22204.399 56867.515 19230.898 0.000 78894.545 0.000 1804.998 2877.235 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.290959E+12 184755.997 25-JUL-19:45 25049.151 49704.829 19230.898 0.000 74374.529 10720.100 1804.998 2925.921 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.277205E+12 185857.601 02-AUG-19:30 25049.151 49704.829 19230.898 0.000 75394.101 10720.100 1804.998 3007.952 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.238129E+12 175141.213 11-SEP-17:30 22204.399 56867.515 19230.898 0.000 71232.487 0.000 1804.998 2655.028 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.219414E+12 118915.113 02-OCT-17:00 22204.399 56867.515 19230.898 0.000 6626.309 10720.100 1804.998 315.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.255162E+12 163574.544 25-NOV-18:15 22204.399 56867.515 19230.898 51600.998 0.000 10720.100 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.303499E+12 238392.128 09-DEC-01:00 7980.643 20217.842 19230.898 178038.208 0.000 10720.100 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.313431E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.219414E+12 118915.113   7980.643 20217.842 19230.898 0.000 0.000 0.000 1804.998 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.320446E+12 238392.128   25049.151 56867.515 19230.898 178038.208 78894.545 10720.100 1804.998 3007.952 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:11

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.560312E+12 403455.744 19-JAN-08:15 0.000 0.000 0.000 403455.744 92043.006 92043.006 311412.738
February 0.406992E+12 400035.333 02-FEB-08:30 0.000 0.000 0.000 400035.333 91723.363 91723.363 308311.971
March 0.301582E+12 324795.538 06-MAR-07:30 0.000 0.000 0.000 324795.538 93320.149 93320.149 231475.389
April 0.179268E+12 237887.077 03-APR-05:00 0.000 0.000 0.000 237887.077 89176.547 89176.547 148710.530
May 0.112962E+12 127306.829 02-MAY-05:45 0.000 0.000 0.000 127306.829 86244.178 86244.178 41062.650
June 0.100744E+12 86975.268 01-JUN-06:45 0.000 0.000 0.000 86975.268 86975.268 86975.268 0.000
July 0.983256E+11 84631.788 01-JUL-06:00 0.000 0.000 0.000 84631.788 84631.788 84631.788 0.000
August 0.956936E+11 83128.421 01-AUG-06:45 0.000 0.000 0.000 83128.421 83128.421 83128.421 0.000
September 0.969953E+11 132385.697 30-SEP-06:15 0.000 0.000 0.000 132385.697 82944.608 82944.608 49441.089
October 0.132403E+12 152066.046 24-OCT-06:30 0.000 0.000 0.000 152066.046 85346.505 85346.505 66719.541
November 0.303113E+12 317219.311 26-NOV-08:15 0.000 0.000 0.000 317219.311 87724.571 87724.571 229494.740
December 0.467614E+12 408138.570 09-DEC-08:30 0.000 0.000 0.000 408138.570 88159.495 88159.495 319979.074
                     
Annual Sum or Average 0.285600E+13     0.000 0.000 0.000        
Minimum of Months 0.956936E+11 83128.421   0.000 0.000 0.000 83128.421 82944.608 82944.608 0.000
Maximum of Months 0.560312E+12 408138.570   0.000 0.000 0.000 408138.570 93320.149 93320.149 319979.074