Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2018-10-19 09:40:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 5990.32 | 764.41 | 848.50 |
Net Site Energy | 5990.32 | 764.41 | 848.50 |
Total Source Energy | 13022.27 | 1661.75 | 1844.54 |
Net Source Energy | 13022.27 | 1661.75 | 1844.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 425.54 | 1560.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 606.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.06 | 0.00 | 0.00 | 0.00 | 0.00 | 810.48 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1295.71 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3134.31 | 2856.00 | 0.00 | 0.00 | 0.00 | 5588.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1560.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 425.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 168.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 606.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 55.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 13.06 | 0.00 | 0.00 | 0.00 | 0.00 | 810.48 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1295.71 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.97 | 404.54 | 0.00 | 0.00 | 0.00 | 0.79 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 443.96 | 404.54 | 0.00 | 0.00 | 0.00 | 0.79 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.35 | 364.45 | 0.00 | 0.00 | 0.00 | 0.71 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.96 | 364.45 | 0.00 | 0.00 | 0.00 | 0.71 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3134.31 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3134.31 | 100.00 |
Total On-Site and Utility Electric Sources | 3134.31 | 100.00 |
Total Electricity End Uses | 3134.31 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5588.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5588.99 | 100.00 |
Total Water End Uses | 5588.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 123.25 |
Time Setpoint Not Met During Occupied Cooling | 73.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3838.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-DEC-01:00 | 09-DEC-08:30 | - | - | - | 25-JUN-17:15 |
Heating | 178038.21 | 319979.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7980.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20217.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19230.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1805.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 88159.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 238392.13 | 408138.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 319979.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 6974.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1006.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 20217.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19230.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1805.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 88159.50 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1347.68 | 1691.35 | 0.00 | 0.00 | 0.00 |
Cooling | 940.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 533.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1920.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 176.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 41.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1404.55 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9926.36 | 3095.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 190.89 | 239.57 | 0.00 | 0.00 | 0.00 |
Cooling | 133.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 272.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 198.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1406.02 | 438.52 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 190.89 | 239.57 | 0.00 | 0.00 | 0.00 |
Cooling | 133.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 75.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 272.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 198.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1406.02 | 438.52 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.66 | 83.66 | 168.36 | |
Exterior Lighting Total | 10720.10 | 168.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 318712.45 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 254969.96 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3887.38 | 2478.79 | 1408.59 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3684.09 | 2331.29 | 1352.79 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5271.71 | 3365.13 | 1906.58 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3354.42 | 2048.68 | 1305.74 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2420.09 | 1430.07 | 990.02 | 0.59 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2432.99 | 1434.73 | 998.25 | 0.59 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2659.02 | 1616.75 | 1042.27 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2733.18 | 1670.03 | 1063.15 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4950.17 | 3209.82 | 1740.35 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4645.28 | 2987.93 | 1657.34 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4730.04 | 3042.65 | 1687.40 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3696.78 | 2314.54 | 1382.24 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2787.43 | 1699.73 | 1087.71 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2765.36 | 1684.21 | 1081.15 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3381.17 | 2114.73 | 1266.43 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3411.40 | 2136.63 | 1274.77 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5022.00 | 3237.24 | 1784.76 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4735.20 | 3029.07 | 1706.13 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4591.56 | 2918.47 | 1673.09 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3800.25 | 2367.74 | 1432.52 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2877.67 | 1752.30 | 1125.37 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2855.82 | 1736.98 | 1118.84 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3466.03 | 2162.69 | 1303.34 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3482.07 | 2174.30 | 1307.77 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5072.40 | 3255.58 | 1816.82 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4798.67 | 3056.01 | 1742.65 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4627.16 | 2927.04 | 1700.12 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3852.08 | 2389.44 | 1462.64 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2921.93 | 1775.25 | 1146.67 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2900.12 | 1760.00 | 1140.12 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3506.82 | 2182.20 | 1324.62 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3520.88 | 2192.37 | 1328.51 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5145.80 | 3294.04 | 1851.76 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4876.88 | 3098.28 | 1778.60 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4703.77 | 2968.46 | 1735.31 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3926.14 | 2429.91 | 1496.23 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2988.53 | 1815.43 | 1173.10 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2966.79 | 1800.24 | 1166.54 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3570.36 | 2219.88 | 1350.48 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3584.12 | 2229.82 | 1354.30 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5122.82 | 3265.17 | 1857.65 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4855.04 | 3070.67 | 1784.37 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4685.66 | 2943.96 | 1741.70 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3900.89 | 2401.87 | 1499.02 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2958.72 | 1789.00 | 1169.72 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2937.04 | 1773.93 | 1163.11 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3539.64 | 2191.19 | 1348.45 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3553.40 | 2201.10 | 1352.30 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5130.10 | 3259.80 | 1870.30 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4864.54 | 3067.25 | 1797.28 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4697.22 | 2942.33 | 1754.88 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3943.14 | 2419.70 | 1523.44 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2960.23 | 1785.33 | 1174.90 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2938.61 | 1770.34 | 1168.26 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3539.62 | 2185.41 | 1354.21 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3553.39 | 2195.31 | 1358.07 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5153.68 | 3267.35 | 1886.33 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4890.11 | 3076.52 | 1813.59 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4723.47 | 2952.34 | 1771.14 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4078.04 | 2496.60 | 1581.44 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2979.08 | 1794.29 | 1184.79 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2957.57 | 1779.41 | 1178.16 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3555.76 | 2191.82 | 1363.94 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3569.57 | 2201.74 | 1367.83 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5294.95 | 3360.16 | 1934.78 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5026.99 | 3166.19 | 1860.80 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4832.24 | 3021.46 | 1810.78 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4358.30 | 2666.36 | 1691.94 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3095.33 | 1871.39 | 1223.94 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3073.58 | 1856.30 | 1217.28 | 0.60 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3641.25 | 2247.73 | 1393.52 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3654.08 | 2257.14 | 1396.94 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6081.21 | 3914.54 | 2166.67 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5681.31 | 3629.45 | 2051.85 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5595.00 | 3561.57 | 2033.43 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5069.94 | 3154.25 | 1915.69 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3532.95 | 2171.46 | 1361.50 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3604.80 | 2209.24 | 1395.56 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4548.17 | 2895.34 | 1652.83 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4561.52 | 2905.10 | 1656.42 | 0.64 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3887.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3684.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5271.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3354.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2420.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2432.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2659.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2733.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4950.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4645.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4730.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3696.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2787.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2765.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3381.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3411.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5022.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4735.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4591.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3800.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2877.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2855.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3466.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3482.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5072.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4798.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4627.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3852.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2921.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2900.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3506.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3520.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5145.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4876.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4703.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3926.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2988.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2966.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3570.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3584.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5122.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4855.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4685.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3900.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2958.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2937.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3539.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3553.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5130.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4864.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4697.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3943.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2960.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2938.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3539.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3553.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5153.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4890.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4723.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4078.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2979.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2957.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3555.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3569.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5294.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5026.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4832.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4358.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3095.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3073.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3641.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3654.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6081.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5681.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5595.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5069.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3532.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3604.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4548.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4561.52 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 5102.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 5111.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 6247.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 5110.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 3884.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 3884.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 3873.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 3882.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 5139.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 5150.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 5155.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 5142.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 3623.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 3623.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 3615.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 3617.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 5245.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 5265.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 5235.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 5253.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 3647.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 3646.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 3627.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 3627.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 5396.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 5421.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 5381.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 5406.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 3730.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 3729.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 3704.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 3704.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 5505.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 5534.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 5488.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 5516.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 3784.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 3784.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 3756.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 3756.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 5671.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 5704.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 5652.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 5684.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 3902.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 3902.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 3870.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 3870.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 5798.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 5832.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 5777.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 5811.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 3986.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 3986.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 3953.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 3952.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 5926.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 5961.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 5904.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 5939.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 4076.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 4076.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 4041.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 4041.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 6226.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 6259.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 6203.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 6236.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 4326.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 4325.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 4293.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 4292.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 7199.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 7240.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 7177.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 7218.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 5357.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 5357.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 5313.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 5313.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 245.36 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 229.62 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 330.16 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 194.94 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.94 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 129.94 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 149.68 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 155.61 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 323.44 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 299.50 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.43 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 226.41 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 161.50 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 159.79 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 203.18 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 205.62 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.72 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.30 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 286.94 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 230.60 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.32 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 164.62 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 207.45 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.75 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 325.43 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.48 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 286.60 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.74 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.10 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.41 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.83 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 209.96 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 328.62 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 307.09 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 290.13 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 235.18 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 171.93 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 170.25 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 212.36 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.47 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 324.51 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.12 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 286.53 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 231.21 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.47 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.81 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.64 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 209.75 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 323.11 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 301.95 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.56 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 232.09 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 167.60 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 165.96 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 207.53 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.63 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 323.23 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 302.26 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 285.97 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.21 | 238.86 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 168.18 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 166.55 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 207.81 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.91 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 332.82 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 311.51 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 292.79 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.23 | 254.56 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 176.32 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 174.66 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 213.45 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 214.63 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 391.37 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 361.66 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 352.01 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 306.64 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 208.01 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 207.99 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 284.87 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 285.96 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0069 | 1768.07 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2223.21 | 2667.85 | 0.183 | 0.219 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
G NW APARTMENT | 2080.53 | 2496.63 | 0.171 | 0.205 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
OFFICE | 2991.50 | 3589.80 | 0.246 | 0.295 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
G NE APARTMENT | 1491.92 | 1790.31 | 0.123 | 0.147 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17 | 0.01534 |
G N1 APARTMENT | 1045.59 | 1254.71 | 0.086 | 0.103 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
G N2 APARTMENT | 1026.90 | 1232.28 | 0.084 | 0.101 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
G S1 APARTMENT | 1356.22 | 1627.47 | 0.111 | 0.134 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
G S2 APARTMENT | 1409.97 | 1691.97 | 0.116 | 0.139 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F2 SW APARTMENT | 2930.60 | 3516.72 | 0.241 | 0.289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F2 NW APARTMENT | 2713.66 | 3256.39 | 0.223 | 0.267 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
F2 SE APARTMENT | 2740.17 | 3288.20 | 0.225 | 0.270 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F2 NE APARTMENT | 2051.30 | 2461.56 | 0.168 | 0.202 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F2 N1 APARTMENT | 1463.37 | 1756.04 | 0.120 | 0.144 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F2 N2 APARTMENT | 1447.82 | 1737.39 | 0.119 | 0.143 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F2 S1 APARTMENT | 1841.00 | 2209.20 | 0.151 | 0.181 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F2 S2 APARTMENT | 1863.05 | 2235.67 | 0.153 | 0.184 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F3 SW APARTMENT | 2942.10 | 3530.53 | 0.242 | 0.290 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F3 NW APARTMENT | 2738.98 | 3286.77 | 0.225 | 0.270 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 28.26 | 0.01534 |
F3 SE APARTMENT | 2599.74 | 3119.69 | 0.213 | 0.256 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F3 NE APARTMENT | 2089.27 | 2507.12 | 0.172 | 0.206 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F3 N1 APARTMENT | 1506.96 | 1808.35 | 0.124 | 0.148 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F3 N2 APARTMENT | 1491.61 | 1789.93 | 0.122 | 0.147 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F3 S1 APARTMENT | 1879.68 | 2255.62 | 0.154 | 0.185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F3 S2 APARTMENT | 1891.39 | 2269.67 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F4 SW APARTMENT | 2948.52 | 3538.23 | 0.242 | 0.291 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F4 NW APARTMENT | 2749.59 | 3299.51 | 0.226 | 0.271 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
F4 SE APARTMENT | 2596.57 | 3115.89 | 0.213 | 0.256 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F4 NE APARTMENT | 2099.49 | 2519.38 | 0.172 | 0.207 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F4 N1 APARTMENT | 1523.07 | 1827.69 | 0.125 | 0.150 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F4 N2 APARTMENT | 1507.82 | 1809.38 | 0.124 | 0.149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F4 S1 APARTMENT | 1892.14 | 2270.57 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F4 S2 APARTMENT | 1902.39 | 2282.87 | 0.156 | 0.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
M SW APARTMENT | 2977.33 | 3572.80 | 0.244 | 0.293 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
M NW APARTMENT | 2782.27 | 3338.73 | 0.228 | 0.274 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
M SE APARTMENT | 2628.49 | 3154.19 | 0.216 | 0.259 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
M NE APARTMENT | 2130.68 | 2556.81 | 0.175 | 0.210 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
M N1 APARTMENT | 1557.77 | 1869.32 | 0.128 | 0.153 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
M N2 APARTMENT | 1542.58 | 1851.10 | 0.127 | 0.152 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
M S1 APARTMENT | 1924.12 | 2308.94 | 0.158 | 0.190 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
M S2 APARTMENT | 1934.14 | 2320.97 | 0.159 | 0.191 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F6 SW APARTMENT | 2940.07 | 3528.09 | 0.241 | 0.290 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F6 NW APARTMENT | 2746.32 | 3295.58 | 0.226 | 0.271 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
F6 SE APARTMENT | 2595.82 | 3114.99 | 0.213 | 0.256 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F6 NE APARTMENT | 2094.62 | 2513.54 | 0.172 | 0.206 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F6 N1 APARTMENT | 1526.45 | 1831.74 | 0.125 | 0.150 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F6 N2 APARTMENT | 1511.40 | 1813.68 | 0.124 | 0.149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F6 S1 APARTMENT | 1890.39 | 2268.47 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F6 S2 APARTMENT | 1900.38 | 2280.46 | 0.156 | 0.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F7 SW APARTMENT | 2927.41 | 3512.90 | 0.240 | 0.288 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F7 NW APARTMENT | 2735.65 | 3282.78 | 0.225 | 0.270 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
F7 SE APARTMENT | 2587.06 | 3104.47 | 0.212 | 0.255 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F7 NE APARTMENT | 2083.23 | 2499.87 | 0.171 | 0.205 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F7 N1 APARTMENT | 1518.58 | 1822.30 | 0.125 | 0.150 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F7 N2 APARTMENT | 1503.64 | 1804.37 | 0.123 | 0.148 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F7 S1 APARTMENT | 1880.26 | 2256.31 | 0.154 | 0.185 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F7 S2 APARTMENT | 1890.24 | 2268.29 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F8 SW APARTMENT | 2928.45 | 3514.14 | 0.240 | 0.289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F8 NW APARTMENT | 2738.45 | 3286.14 | 0.225 | 0.270 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
F8 SE APARTMENT | 2590.69 | 3108.82 | 0.213 | 0.255 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
F8 NE APARTMENT | 2084.47 | 2501.37 | 0.171 | 0.205 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.57 | 0.01534 |
F8 N1 APARTMENT | 1523.81 | 1828.58 | 0.125 | 0.150 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F8 N2 APARTMENT | 1508.98 | 1810.78 | 0.124 | 0.149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F8 S1 APARTMENT | 1882.80 | 2259.35 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F8 S2 APARTMENT | 1892.79 | 2271.35 | 0.155 | 0.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F9 SW APARTMENT | 3015.34 | 3618.41 | 0.248 | 0.297 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 28.92 | 0.01534 |
F9 NW APARTMENT | 2822.25 | 3386.71 | 0.232 | 0.278 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
F9 SE APARTMENT | 2652.45 | 3182.94 | 0.218 | 0.261 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
F9 NE APARTMENT | 2115.90 | 2539.08 | 0.174 | 0.209 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 27.97 | 0.01534 |
F9 N1 APARTMENT | 1597.54 | 1917.05 | 0.131 | 0.157 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F9 N2 APARTMENT | 1582.51 | 1899.02 | 0.130 | 0.156 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
F9 S1 APARTMENT | 1933.92 | 2320.71 | 0.159 | 0.191 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20 | 0.01534 |
F9 S2 APARTMENT | 1944.57 | 2333.48 | 0.160 | 0.192 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
T SW APARTMENT | 3545.48 | 4254.58 | 0.291 | 0.349 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.72 | 0.01534 |
T NW APARTMENT | 3276.52 | 3931.83 | 0.269 | 0.323 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.19 | 0.01534 |
T SE APARTMENT | 3188.90 | 3826.69 | 0.262 | 0.314 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93 | 0.01534 |
T NE APARTMENT | 2517.46 | 3020.95 | 0.207 | 0.248 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 28.36 | 0.01534 |
T N1 APARTMENT | 1857.61 | 2229.13 | 0.153 | 0.183 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.86 | 0.01534 |
T N2 APARTMENT | 1837.19 | 2204.63 | 0.151 | 0.181 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
T S1 APARTMENT | 2580.97 | 3097.17 | 0.212 | 0.254 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
T S2 APARTMENT | 2590.83 | 3109.00 | 0.213 | 0.255 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 3101.81 | 3722.17 | 0.145 | 0.174 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G NW APARTMENT | 3109.24 | 3731.09 | 0.145 | 0.174 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
OFFICE | 3501.50 | 4201.80 | 0.163 | 0.196 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -26.20 | 0.00036 |
G NE APARTMENT | 3108.62 | 3730.35 | 0.145 | 0.174 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G N1 APARTMENT | 2072.05 | 2486.46 | 0.097 | 0.116 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G N2 APARTMENT | 2072.02 | 2486.43 | 0.097 | 0.116 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G S1 APARTMENT | 2062.45 | 2474.94 | 0.096 | 0.115 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
G S2 APARTMENT | 2069.57 | 2483.49 | 0.097 | 0.116 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
F2 SW APARTMENT | 3133.07 | 3759.68 | 0.146 | 0.175 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 NW APARTMENT | 3142.35 | 3770.82 | 0.147 | 0.176 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 SE APARTMENT | 3146.88 | 3776.25 | 0.147 | 0.176 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 NE APARTMENT | 3135.61 | 3762.74 | 0.146 | 0.176 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 N1 APARTMENT | 1851.40 | 2221.68 | 0.086 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 N2 APARTMENT | 1851.26 | 2221.51 | 0.086 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 S1 APARTMENT | 1844.60 | 2213.52 | 0.086 | 0.103 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F2 S2 APARTMENT | 1845.70 | 2214.84 | 0.086 | 0.103 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 SW APARTMENT | 3222.69 | 3867.23 | 0.150 | 0.180 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 NW APARTMENT | 3239.93 | 3887.91 | 0.151 | 0.181 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 SE APARTMENT | 3214.34 | 3857.21 | 0.150 | 0.180 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 NE APARTMENT | 3229.52 | 3875.43 | 0.151 | 0.181 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 N1 APARTMENT | 1871.03 | 2245.24 | 0.087 | 0.105 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 N2 APARTMENT | 1870.81 | 2244.97 | 0.087 | 0.105 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 S1 APARTMENT | 1854.53 | 2225.43 | 0.087 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F3 S2 APARTMENT | 1854.48 | 2225.37 | 0.087 | 0.104 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 SW APARTMENT | 3350.03 | 4020.04 | 0.156 | 0.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 NW APARTMENT | 3371.87 | 4046.24 | 0.157 | 0.189 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 SE APARTMENT | 3337.29 | 4004.75 | 0.156 | 0.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 NE APARTMENT | 3358.94 | 4030.73 | 0.157 | 0.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 N1 APARTMENT | 1941.30 | 2329.55 | 0.091 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 N2 APARTMENT | 1941.01 | 2329.21 | 0.091 | 0.109 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 S1 APARTMENT | 1919.88 | 2303.86 | 0.090 | 0.107 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F4 S2 APARTMENT | 1919.62 | 2303.54 | 0.090 | 0.107 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M SW APARTMENT | 3442.92 | 4131.51 | 0.161 | 0.193 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M NW APARTMENT | 3466.85 | 4160.21 | 0.162 | 0.194 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M SE APARTMENT | 3428.12 | 4113.74 | 0.160 | 0.192 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M NE APARTMENT | 3452.03 | 4142.44 | 0.161 | 0.193 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M N1 APARTMENT | 1987.15 | 2384.58 | 0.093 | 0.111 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M N2 APARTMENT | 1986.83 | 2384.19 | 0.093 | 0.111 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M S1 APARTMENT | 1963.54 | 2356.25 | 0.092 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
M S2 APARTMENT | 1963.22 | 2355.86 | 0.092 | 0.110 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 SW APARTMENT | 3583.33 | 4300.00 | 0.167 | 0.201 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 NW APARTMENT | 3610.48 | 4332.58 | 0.168 | 0.202 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 SE APARTMENT | 3567.00 | 4280.40 | 0.166 | 0.200 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 NE APARTMENT | 3594.16 | 4312.99 | 0.168 | 0.201 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 N1 APARTMENT | 2086.97 | 2504.37 | 0.097 | 0.117 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 N2 APARTMENT | 2086.61 | 2503.94 | 0.097 | 0.117 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 S1 APARTMENT | 2060.10 | 2472.11 | 0.096 | 0.115 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F6 S2 APARTMENT | 2059.74 | 2471.69 | 0.096 | 0.115 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 SW APARTMENT | 3690.45 | 4428.55 | 0.172 | 0.207 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 NW APARTMENT | 3719.31 | 4463.17 | 0.173 | 0.208 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 SE APARTMENT | 3672.89 | 4407.46 | 0.171 | 0.206 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 NE APARTMENT | 3701.75 | 4442.10 | 0.173 | 0.207 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 N1 APARTMENT | 2158.37 | 2590.04 | 0.101 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 N2 APARTMENT | 2157.98 | 2589.58 | 0.101 | 0.121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 S1 APARTMENT | 2129.77 | 2555.72 | 0.099 | 0.119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F7 S2 APARTMENT | 2129.38 | 2555.26 | 0.099 | 0.119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 SW APARTMENT | 3798.60 | 4558.32 | 0.177 | 0.213 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 NW APARTMENT | 3828.52 | 4594.22 | 0.179 | 0.214 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 SE APARTMENT | 3779.98 | 4535.98 | 0.176 | 0.212 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 NE APARTMENT | 3809.92 | 4571.90 | 0.178 | 0.213 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 N1 APARTMENT | 2234.27 | 2681.13 | 0.104 | 0.125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 N2 APARTMENT | 2233.87 | 2680.64 | 0.104 | 0.125 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 S1 APARTMENT | 2204.60 | 2645.52 | 0.103 | 0.123 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F8 S2 APARTMENT | 2204.19 | 2645.03 | 0.103 | 0.123 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 SW APARTMENT | 4052.20 | 4862.64 | 0.189 | 0.227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 NW APARTMENT | 4080.01 | 4896.01 | 0.190 | 0.228 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 SE APARTMENT | 4032.51 | 4839.02 | 0.188 | 0.226 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 NE APARTMENT | 4060.34 | 4872.41 | 0.189 | 0.227 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 N1 APARTMENT | 2445.29 | 2934.35 | 0.114 | 0.137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 N2 APARTMENT | 2444.86 | 2933.84 | 0.114 | 0.137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 S1 APARTMENT | 2417.35 | 2900.82 | 0.113 | 0.135 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
F9 S2 APARTMENT | 2416.92 | 2900.31 | 0.113 | 0.135 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T SW APARTMENT | 4875.41 | 5850.49 | 0.227 | 0.273 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T NW APARTMENT | 4910.02 | 5892.03 | 0.229 | 0.275 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T SE APARTMENT | 4856.43 | 5827.71 | 0.227 | 0.272 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T NE APARTMENT | 4891.06 | 5869.27 | 0.228 | 0.274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T N1 APARTMENT | 3317.57 | 3981.09 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T N2 APARTMENT | 3317.13 | 3980.56 | 0.155 | 0.186 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T S1 APARTMENT | 3280.21 | 3936.25 | 0.153 | 0.184 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
T S2 APARTMENT | 3279.77 | 3935.72 | 0.153 | 0.184 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -26.20 | 0.00036 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.22 | 0.22 | 0.17 | 0.17 |
AIRLOOP G NW | 0.20 | 0.20 | 0.17 | 0.17 |
AIRLOOP OFFICE | 0.29 | 0.29 | 0.20 | 0.20 |
AIRLOOP G NE | 0.15 | 0.15 | 0.17 | 0.17 |
AIRLOOP G N1 | 0.10 | 0.10 | 0.12 | 0.12 |
AIRLOOP G N2 | 0.10 | 0.10 | 0.12 | 0.12 |
AIRLOOP G S1 | 0.13 | 0.13 | 0.12 | 0.12 |
AIRLOOP G S2 | 0.14 | 0.14 | 0.12 | 0.12 |
AIRLOOP F2 SW | 0.29 | 0.29 | 0.18 | 0.18 |
AIRLOOP F2 NW | 0.27 | 0.27 | 0.18 | 0.18 |
AIRLOOP F2 SE | 0.27 | 0.27 | 0.18 | 0.18 |
AIRLOOP F2 NE | 0.20 | 0.20 | 0.18 | 0.18 |
AIRLOOP F2 N1 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F2 N2 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F2 S1 | 0.18 | 0.18 | 0.10 | 0.10 |
AIRLOOP F2 S2 | 0.18 | 0.18 | 0.10 | 0.10 |
AIRLOOP F3 SW | 0.29 | 0.29 | 0.18 | 0.18 |
AIRLOOP F3 NW | 0.27 | 0.27 | 0.18 | 0.18 |
AIRLOOP F3 SE | 0.26 | 0.26 | 0.18 | 0.18 |
AIRLOOP F3 NE | 0.21 | 0.21 | 0.18 | 0.18 |
AIRLOOP F3 N1 | 0.15 | 0.15 | 0.10 | 0.10 |
AIRLOOP F3 N2 | 0.15 | 0.15 | 0.10 | 0.10 |
AIRLOOP F3 S1 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F3 S2 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F4 SW | 0.29 | 0.29 | 0.19 | 0.19 |
AIRLOOP F4 NW | 0.27 | 0.27 | 0.19 | 0.19 |
AIRLOOP F4 SE | 0.26 | 0.26 | 0.19 | 0.19 |
AIRLOOP F4 NE | 0.21 | 0.21 | 0.19 | 0.19 |
AIRLOOP F4 N1 | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP F4 N2 | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP F4 S1 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP F4 S2 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP M SW | 0.29 | 0.29 | 0.19 | 0.19 |
AIRLOOP M NW | 0.27 | 0.27 | 0.19 | 0.19 |
AIRLOOP M SE | 0.26 | 0.26 | 0.19 | 0.19 |
AIRLOOP M NE | 0.21 | 0.21 | 0.19 | 0.19 |
AIRLOOP M N1 | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP M N2 | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP M S1 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP M S2 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP F6 SW | 0.29 | 0.29 | 0.20 | 0.20 |
AIRLOOP F6 NW | 0.27 | 0.27 | 0.20 | 0.20 |
AIRLOOP F6 SE | 0.26 | 0.26 | 0.20 | 0.20 |
AIRLOOP F6 NE | 0.21 | 0.21 | 0.20 | 0.20 |
AIRLOOP F6 N1 | 0.15 | 0.15 | 0.12 | 0.12 |
AIRLOOP F6 N2 | 0.15 | 0.15 | 0.12 | 0.12 |
AIRLOOP F6 S1 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F6 S2 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F7 SW | 0.29 | 0.29 | 0.21 | 0.21 |
AIRLOOP F7 NW | 0.27 | 0.27 | 0.21 | 0.21 |
AIRLOOP F7 SE | 0.25 | 0.25 | 0.21 | 0.21 |
AIRLOOP F7 NE | 0.21 | 0.21 | 0.21 | 0.21 |
AIRLOOP F7 N1 | 0.15 | 0.15 | 0.12 | 0.12 |
AIRLOOP F7 N2 | 0.15 | 0.15 | 0.12 | 0.12 |
AIRLOOP F7 S1 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F7 S2 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F8 SW | 0.29 | 0.29 | 0.21 | 0.21 |
AIRLOOP F8 NW | 0.27 | 0.27 | 0.21 | 0.21 |
AIRLOOP F8 SE | 0.26 | 0.26 | 0.21 | 0.21 |
AIRLOOP F8 NE | 0.21 | 0.21 | 0.21 | 0.21 |
AIRLOOP F8 N1 | 0.15 | 0.15 | 0.13 | 0.13 |
AIRLOOP F8 N2 | 0.15 | 0.15 | 0.13 | 0.13 |
AIRLOOP F8 S1 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F8 S2 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F9 SW | 0.30 | 0.30 | 0.23 | 0.23 |
AIRLOOP F9 NW | 0.28 | 0.28 | 0.23 | 0.23 |
AIRLOOP F9 SE | 0.26 | 0.26 | 0.23 | 0.23 |
AIRLOOP F9 NE | 0.21 | 0.21 | 0.23 | 0.23 |
AIRLOOP F9 N1 | 0.16 | 0.16 | 0.14 | 0.14 |
AIRLOOP F9 N2 | 0.16 | 0.16 | 0.14 | 0.14 |
AIRLOOP F9 S1 | 0.19 | 0.19 | 0.14 | 0.14 |
AIRLOOP F9 S2 | 0.19 | 0.19 | 0.14 | 0.14 |
AIRLOOP T SW | 0.35 | 0.35 | 0.27 | 0.27 |
AIRLOOP T NW | 0.32 | 0.32 | 0.27 | 0.27 |
AIRLOOP T SE | 0.31 | 0.31 | 0.27 | 0.27 |
AIRLOOP T NE | 0.25 | 0.25 | 0.27 | 0.27 |
AIRLOOP T N1 | 0.18 | 0.18 | 0.19 | 0.19 |
AIRLOOP T N2 | 0.18 | 0.18 | 0.19 | 0.19 |
AIRLOOP T S1 | 0.25 | 0.25 | 0.18 | 0.18 |
AIRLOOP T S2 | 0.26 | 0.26 | 0.18 | 0.18 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3804.25 | 6687.00 | 2184.75 |
G NW APARTMENT | 4239.25 | 7054.00 | 2841.75 |
OFFICE | 1027.50 | 1233.75 | 247.50 |
G NE APARTMENT | 4262.75 | 7060.00 | 2851.50 |
G N1 APARTMENT | 3366.25 | 7323.25 | 2241.25 |
G N2 APARTMENT | 3369.50 | 7324.50 | 2244.25 |
G S1 APARTMENT | 3070.50 | 6830.50 | 1619.25 |
G S2 APARTMENT | 3077.75 | 6783.00 | 1602.00 |
F2 SW APARTMENT | 3830.50 | 5591.75 | 1370.50 |
F2 NW APARTMENT | 4111.25 | 6200.75 | 1964.00 |
F2 SE APARTMENT | 3869.75 | 5437.00 | 1259.00 |
F2 NE APARTMENT | 4125.50 | 6245.50 | 1978.50 |
F2 N1 APARTMENT | 3257.25 | 6428.75 | 1338.50 |
F2 N2 APARTMENT | 3257.75 | 6436.25 | 1340.50 |
F2 S1 APARTMENT | 3231.50 | 5554.50 | 844.00 |
F2 S2 APARTMENT | 3245.00 | 5533.50 | 839.00 |
F3 SW APARTMENT | 3891.00 | 5417.00 | 1305.00 |
F3 NW APARTMENT | 4139.00 | 6076.25 | 1890.00 |
F3 SE APARTMENT | 3888.00 | 5424.50 | 1266.50 |
F3 NE APARTMENT | 4150.00 | 6122.00 | 1901.00 |
F3 N1 APARTMENT | 3294.75 | 6208.75 | 1216.50 |
F3 N2 APARTMENT | 3288.00 | 6221.25 | 1217.75 |
F3 S1 APARTMENT | 3376.75 | 5305.25 | 775.25 |
F3 S2 APARTMENT | 3379.25 | 5298.75 | 775.25 |
F4 SW APARTMENT | 3930.00 | 5424.75 | 1330.25 |
F4 NW APARTMENT | 4174.00 | 6065.00 | 1918.25 |
F4 SE APARTMENT | 3900.50 | 5468.25 | 1310.50 |
F4 NE APARTMENT | 4183.50 | 6124.75 | 1941.25 |
F4 N1 APARTMENT | 3333.25 | 6159.25 | 1220.00 |
F4 N2 APARTMENT | 3329.50 | 6174.25 | 1222.25 |
F4 S1 APARTMENT | 3419.00 | 5273.00 | 779.25 |
F4 S2 APARTMENT | 3417.25 | 5272.75 | 779.75 |
M SW APARTMENT | 3920.50 | 5443.00 | 1329.50 |
M NW APARTMENT | 4161.75 | 6064.75 | 1902.75 |
M SE APARTMENT | 3885.50 | 5494.00 | 1308.25 |
M NE APARTMENT | 4170.25 | 6129.25 | 1926.00 |
M N1 APARTMENT | 3333.00 | 6136.50 | 1195.00 |
M N2 APARTMENT | 3327.25 | 6149.50 | 1195.25 |
M S1 APARTMENT | 3412.50 | 5283.75 | 773.25 |
M S2 APARTMENT | 3410.75 | 5282.00 | 774.25 |
F6 SW APARTMENT | 3875.25 | 5606.50 | 1423.25 |
F6 NW APARTMENT | 4192.75 | 6203.25 | 2047.75 |
F6 SE APARTMENT | 3866.25 | 5663.00 | 1416.50 |
F6 NE APARTMENT | 4212.25 | 6258.75 | 2088.25 |
F6 N1 APARTMENT | 3322.75 | 6295.75 | 1312.50 |
F6 N2 APARTMENT | 3317.50 | 6305.00 | 1314.25 |
F6 S1 APARTMENT | 3330.25 | 5437.25 | 828.25 |
F6 S2 APARTMENT | 3326.50 | 5439.75 | 828.25 |
F7 SW APARTMENT | 3855.50 | 5739.25 | 1488.25 |
F7 NW APARTMENT | 4200.50 | 6296.25 | 2132.25 |
F7 SE APARTMENT | 3845.50 | 5791.25 | 1480.50 |
F7 NE APARTMENT | 4212.00 | 6345.00 | 2166.25 |
F7 N1 APARTMENT | 3312.25 | 6403.75 | 1377.50 |
F7 N2 APARTMENT | 3309.25 | 6414.00 | 1379.25 |
F7 S1 APARTMENT | 3273.00 | 5561.50 | 867.50 |
F7 S2 APARTMENT | 3271.50 | 5565.75 | 868.00 |
F8 SW APARTMENT | 3844.75 | 5854.25 | 1553.00 |
F8 NW APARTMENT | 4214.25 | 6365.25 | 2206.50 |
F8 SE APARTMENT | 3838.50 | 5906.75 | 1551.00 |
F8 NE APARTMENT | 4233.00 | 6396.75 | 2231.50 |
F8 N1 APARTMENT | 3318.25 | 6496.75 | 1441.00 |
F8 N2 APARTMENT | 3314.00 | 6503.75 | 1442.50 |
F8 S1 APARTMENT | 3219.50 | 5680.75 | 910.00 |
F8 S2 APARTMENT | 3219.50 | 5683.25 | 910.75 |
F9 SW APARTMENT | 3937.75 | 5971.00 | 1736.25 |
F9 NW APARTMENT | 4348.50 | 6446.50 | 2403.50 |
F9 SE APARTMENT | 3932.25 | 6030.50 | 1734.00 |
F9 NE APARTMENT | 4351.75 | 6457.50 | 2394.00 |
F9 N1 APARTMENT | 3406.75 | 6587.75 | 1590.25 |
F9 N2 APARTMENT | 3408.50 | 6593.00 | 1592.50 |
F9 S1 APARTMENT | 3220.00 | 5876.25 | 1047.25 |
F9 S2 APARTMENT | 3219.50 | 5874.25 | 1048.50 |
T SW APARTMENT | 4795.00 | 6267.75 | 2821.50 |
T NW APARTMENT | 5067.75 | 6711.25 | 3394.50 |
T SE APARTMENT | 4818.50 | 6322.25 | 2855.25 |
T NE APARTMENT | 5100.75 | 6744.50 | 3407.25 |
T N1 APARTMENT | 4335.75 | 6839.00 | 2733.50 |
T N2 APARTMENT | 4336.25 | 6833.00 | 2729.75 |
T S1 APARTMENT | 4057.25 | 6191.50 | 2092.25 |
T S2 APARTMENT | 4063.75 | 6195.00 | 2095.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6242.75 | 7478.00 | 3838.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 2.25 | 2.25 | 2.25 | 2.25 |
G NW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
OFFICE | 2.75 | 0.00 | 0.75 | 0.00 |
G NE APARTMENT | 4.25 | 1.00 | 4.25 | 1.00 |
G N1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
G N2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G S1 APARTMENT | 0.75 | 16.50 | 0.75 | 16.50 |
G S2 APARTMENT | 1.25 | 14.75 | 1.25 | 14.75 |
F2 SW APARTMENT | 3.50 | 0.25 | 3.50 | 0.25 |
F2 NW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F2 SE APARTMENT | 2.00 | 1.75 | 2.00 | 1.75 |
F2 NE APARTMENT | 0.75 | 11.50 | 0.75 | 11.50 |
F2 N1 APARTMENT | 2.50 | 3.00 | 2.50 | 3.00 |
F2 N2 APARTMENT | 3.00 | 3.75 | 3.00 | 3.75 |
F2 S1 APARTMENT | 1.50 | 13.00 | 1.50 | 13.00 |
F2 S2 APARTMENT | 1.50 | 12.00 | 1.50 | 12.00 |
F3 SW APARTMENT | 2.00 | 0.25 | 2.00 | 0.25 |
F3 NW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F3 SE APARTMENT | 1.75 | 7.00 | 1.75 | 7.00 |
F3 NE APARTMENT | 1.50 | 17.25 | 1.50 | 17.25 |
F3 N1 APARTMENT | 3.75 | 7.75 | 3.75 | 7.75 |
F3 N2 APARTMENT | 3.00 | 9.75 | 3.00 | 9.75 |
F3 S1 APARTMENT | 1.00 | 18.50 | 1.00 | 18.50 |
F3 S2 APARTMENT | 1.50 | 17.50 | 1.50 | 17.50 |
F4 SW APARTMENT | 3.00 | 0.25 | 3.00 | 0.25 |
F4 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F4 SE APARTMENT | 1.25 | 8.75 | 1.25 | 8.75 |
F4 NE APARTMENT | 1.25 | 20.00 | 1.25 | 20.00 |
F4 N1 APARTMENT | 1.25 | 11.25 | 1.25 | 11.25 |
F4 N2 APARTMENT | 1.50 | 14.50 | 1.50 | 14.50 |
F4 S1 APARTMENT | 1.75 | 20.00 | 1.75 | 20.00 |
F4 S2 APARTMENT | 0.75 | 19.25 | 0.75 | 19.25 |
M SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
M NW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M SE APARTMENT | 0.75 | 9.00 | 0.75 | 9.00 |
M NE APARTMENT | 1.25 | 20.75 | 1.25 | 20.75 |
M N1 APARTMENT | 2.75 | 13.25 | 2.75 | 13.25 |
M N2 APARTMENT | 2.25 | 16.25 | 2.25 | 16.25 |
M S1 APARTMENT | 1.50 | 21.75 | 1.50 | 21.75 |
M S2 APARTMENT | 1.00 | 20.25 | 1.00 | 20.25 |
F6 SW APARTMENT | 1.00 | 0.50 | 1.00 | 0.50 |
F6 NW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F6 SE APARTMENT | 0.25 | 9.00 | 0.25 | 9.00 |
F6 NE APARTMENT | 2.50 | 21.25 | 2.50 | 21.25 |
F6 N1 APARTMENT | 3.75 | 14.00 | 3.75 | 14.00 |
F6 N2 APARTMENT | 3.25 | 18.00 | 3.25 | 18.00 |
F6 S1 APARTMENT | 1.75 | 21.50 | 1.75 | 21.50 |
F6 S2 APARTMENT | 1.75 | 21.50 | 1.75 | 21.50 |
F7 SW APARTMENT | 0.75 | 0.50 | 0.75 | 0.50 |
F7 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F7 SE APARTMENT | 1.25 | 10.25 | 1.25 | 10.25 |
F7 NE APARTMENT | 1.75 | 20.00 | 1.75 | 20.00 |
F7 N1 APARTMENT | 3.75 | 15.75 | 3.75 | 15.75 |
F7 N2 APARTMENT | 4.50 | 20.25 | 4.50 | 20.25 |
F7 S1 APARTMENT | 3.00 | 21.00 | 3.00 | 21.00 |
F7 S2 APARTMENT | 2.25 | 20.00 | 2.25 | 20.00 |
F8 SW APARTMENT | 1.25 | 0.25 | 1.25 | 0.25 |
F8 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F8 SE APARTMENT | 2.75 | 11.00 | 2.75 | 11.00 |
F8 NE APARTMENT | 0.75 | 14.50 | 0.75 | 14.50 |
F8 N1 APARTMENT | 4.25 | 16.25 | 4.25 | 16.25 |
F8 N2 APARTMENT | 2.75 | 22.00 | 2.75 | 22.00 |
F8 S1 APARTMENT | 2.50 | 22.25 | 2.50 | 22.25 |
F8 S2 APARTMENT | 2.75 | 21.50 | 2.75 | 21.50 |
F9 SW APARTMENT | 0.75 | 0.25 | 0.75 | 0.25 |
F9 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F9 SE APARTMENT | 1.00 | 9.75 | 1.00 | 9.75 |
F9 NE APARTMENT | 0.50 | 9.50 | 0.50 | 9.50 |
F9 N1 APARTMENT | 3.50 | 14.00 | 3.50 | 14.00 |
F9 N2 APARTMENT | 2.00 | 15.75 | 2.00 | 15.75 |
F9 S1 APARTMENT | 2.00 | 23.25 | 2.00 | 23.25 |
F9 S2 APARTMENT | 3.25 | 22.25 | 3.25 | 22.25 |
T SW APARTMENT | 0.00 | 2.00 | 0.00 | 2.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.00 | 13.75 | 0.00 | 13.75 |
T NE APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
T N1 APARTMENT | 1.75 | 25.00 | 1.75 | 25.00 |
T N2 APARTMENT | 2.50 | 19.50 | 2.50 | 19.50 |
T S1 APARTMENT | 0.50 | 16.25 | 0.50 | 16.25 |
T S2 APARTMENT | 1.50 | 16.50 | 1.50 | 16.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 125.00 | 73.50 | 123.25 | 73.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.296 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.278 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.161 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.145 | 0.000 | 0.279 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.087 | 0.000 | 0.274 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.087 | 0.000 | 0.274 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.087 | 0.000 | 0.293 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.087 | 0.000 | 0.293 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.208 | 0.000 | 0.358 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.208 | 0.000 | 0.332 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.208 | 0.000 | 0.359 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.208 | 0.000 | 0.332 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.125 | 0.000 | 0.329 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.125 | 0.000 | 0.329 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.126 | 0.000 | 0.356 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.126 | 0.000 | 0.356 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.246 | 0.000 | 0.403 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.246 | 0.000 | 0.371 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.246 | 0.000 | 0.403 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.246 | 0.000 | 0.371 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.149 | 0.000 | 0.368 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.149 | 0.000 | 0.368 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.149 | 0.000 | 0.401 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.149 | 0.000 | 0.401 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.275 | 0.000 | 0.424 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.275 | 0.000 | 0.388 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.275 | 0.000 | 0.424 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.275 | 0.000 | 0.388 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.166 | 0.000 | 0.386 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.166 | 0.000 | 0.386 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.166 | 0.000 | 0.423 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.166 | 0.000 | 0.423 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.299 | 0.000 | 0.448 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.299 | 0.000 | 0.409 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.299 | 0.000 | 0.449 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.299 | 0.000 | 0.409 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.180 | 0.000 | 0.407 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.180 | 0.000 | 0.407 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.181 | 0.000 | 0.447 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.181 | 0.000 | 0.447 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.320 | 0.000 | 0.469 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.319 | 0.000 | 0.427 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.320 | 0.000 | 0.469 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.319 | 0.000 | 0.427 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.193 | 0.000 | 0.425 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.193 | 0.000 | 0.425 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.193 | 0.000 | 0.468 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.193 | 0.000 | 0.468 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.338 | 0.000 | 0.487 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.338 | 0.000 | 0.442 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.338 | 0.000 | 0.487 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.338 | 0.000 | 0.442 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.204 | 0.000 | 0.440 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.204 | 0.000 | 0.440 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.204 | 0.000 | 0.486 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.204 | 0.000 | 0.486 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.505 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.458 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.505 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.458 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.213 | 0.000 | 0.455 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.213 | 0.000 | 0.455 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.214 | 0.000 | 0.503 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.214 | 0.000 | 0.503 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.369 | 0.000 | 0.522 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.369 | 0.000 | 0.473 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.369 | 0.000 | 0.522 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.369 | 0.000 | 0.473 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.222 | 0.000 | 0.470 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.222 | 0.000 | 0.470 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.223 | 0.000 | 0.520 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.223 | 0.000 | 0.521 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.383 | 0.000 | 0.534 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.383 | 0.000 | 0.482 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.383 | 0.000 | 0.534 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.383 | 0.000 | 0.483 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.231 | 0.000 | 0.480 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.231 | 0.000 | 0.480 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.231 | 0.000 | 0.532 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.231 | 0.000 | 0.532 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 606.47 | 19230.90 | 01-JAN-00:15 | 19230.90 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1349.73 | 19611.43 | 15-APR-02:45 | 197668.55 | 09-DEC-02:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
ElectricityPurchased:Plant | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
Cogeneration:ElectricityPurchased | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
ElectricityNet:Plant | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
Cogeneration:ElectricityNet | 3134.31 | 57171.91 | 15-APR-02:45 | 238392.13 | 09-DEC-02:00 |
ExteriorLights:Electricity | 168.36 | 0.00 | 01-JAN-08:00 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 168.36 | 0.00 | 01-JAN-08:00 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 606.47 | 19230.90 | 01-JAN-00:15 | 19230.90 | 01-JAN-00:15 |
Cooling:Electricity | 296.90 | 0.00 | 01-JAN-00:15 | 81933.32 | 04-AUG-15:45 |
Heating:Electricity | 425.54 | 0.00 | 18-MAR-15:15 | 178038.21 | 09-DEC-02:00 |
Electricity:Plant | 68.72 | 36.93 | 19-MAR-16:15 | 5151.48 | 26-JUL-14:45 |
HeatRejection:Electricity | 13.06 | 0.00 | 01-JAN-00:15 | 3346.48 | 26-JUL-14:45 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 55.66 | 36.93 | 19-MAR-16:15 | 1805.00 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 2856.00 | 9260.51 | 19-MAR-22:30 | 408138.57 | 09-DEC-08:30 |
Gas:Plant | 2856.00 | 9260.51 | 19-MAR-22:30 | 408138.57 | 09-DEC-08:30 |
WaterSystems:Gas | 1295.71 | 9260.51 | 01-JAN-00:15 | 93795.20 | 17-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1295.71 | 9260.51 | 01-JAN-00:15 | 93795.20 | 17-FEB-08:00 |
Heating:Gas | 1560.29 | 0.00 | 24-FEB-13:45 | 322077.71 | 19-JAN-05:00 |
Boiler:Heating:Gas | 1560.29 | 0.00 | 24-FEB-13:45 | 322077.71 | 19-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 1265.28 | 0.00 | 01-JAN-00:15 | 399879.37 | 03-AUG-08:30 |
PlantLoopCoolingDemand:HVAC | 1265.28 | 0.00 | 01-JAN-00:15 | 399879.37 | 03-AUG-08:30 |
CoolingCoils:PlantLoopCoolingDemand | 1265.28 | 0.00 | 01-JAN-00:15 | 399879.37 | 03-AUG-08:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5588.99 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUN-17:15 |
Water:Plant | 5588.99 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5588.99 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUN-17:15 |
MainsWater:Plant | 5588.99 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 810.48 | 0.00 | 01-JAN-00:15 | 0.00 | 04-AUG-15:00 |
HeatRejection:MainsWater | 810.48 | 0.00 | 01-JAN-00:15 | 0.00 | 04-AUG-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 2271.56 | 527.80 | 21-AUG-01:15 | 317900.47 | 09-DEC-09:00 |
PlantLoopHeatingDemand:Plant | 985.92 | 527.80 | 21-AUG-01:15 | 67608.03 | 19-FEB-07:45 |
WaterSystems:PlantLoopHeatingDemand | 985.92 | 527.80 | 21-AUG-01:15 | 67608.03 | 19-FEB-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 6673.41 | 5501.37 | 10-MAY-02:00 | 1071846.38 | 09-DEC-09:00 |
EnergyTransfer:Building | 1774.84 | 2747.22 | 20-MAY-16:45 | 345641.36 | 09-DEC-02:00 |
EnergyTransfer:Zone:G SW APARTMENT | 19.53 | 0.06 | 25-OCT-11:45 | 3665.84 | 09-DEC-09:00 |
Heating:EnergyTransfer | 1055.06 | 0.00 | 18-MAR-17:30 | 345641.36 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 12.31 | 0.00 | 02-JAN-12:15 | 3665.84 | 09-DEC-09:00 |
Cooling:EnergyTransfer | 719.78 | 0.00 | 01-JAN-00:15 | 189500.83 | 02-SEP-16:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.22 | 0.00 | 01-JAN-00:15 | 2763.29 | 07-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 21.29 | 0.03 | 30-SEP-09:15 | 3715.66 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 16.20 | 0.00 | 20-FEB-16:15 | 3715.66 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 5.09 | 0.00 | 01-JAN-00:15 | 2239.15 | 25-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 23.62 | 0.12 | 24-MAR-00:45 | 3776.49 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:OFFICE | 11.74 | 0.00 | 02-JAN-09:45 | 3776.49 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 11.88 | 0.00 | 01-JAN-00:15 | 3457.63 | 07-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 21.05 | 0.02 | 11-OCT-04:15 | 3699.46 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 16.09 | 0.00 | 24-FEB-10:45 | 3699.46 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.95 | 0.00 | 01-JAN-00:15 | 1681.12 | 02-JUL-09:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 13.55 | 0.02 | 17-JUN-21:00 | 2323.47 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 9.32 | 0.00 | 24-FEB-17:15 | 2323.47 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.23 | 0.00 | 01-JAN-00:15 | 1299.37 | 02-JUL-19:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 13.54 | 0.03 | 25-OCT-08:45 | 2323.24 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 9.33 | 0.00 | 24-FEB-17:15 | 2323.24 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.22 | 0.00 | 01-JAN-00:15 | 1299.64 | 02-JUL-19:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 12.63 | 0.00 | 12-MAY-19:15 | 2261.96 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 5.73 | 0.00 | 02-JAN-10:15 | 2261.96 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 6.90 | 0.00 | 01-JAN-00:15 | 1883.55 | 05-SEP-12:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.63 | 0.01 | 04-MAY-23:15 | 2256.40 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 5.63 | 0.00 | 02-JAN-10:15 | 2256.40 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.01 | 0.00 | 01-JAN-00:15 | 1924.30 | 05-SEP-12:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 23.10 | 0.03 | 07-NOV-15:15 | 4273.59 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 11.56 | 0.00 | 02-JAN-12:15 | 4273.59 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 11.55 | 0.00 | 01-JAN-00:15 | 3495.32 | 07-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 24.39 | 0.02 | 23-MAR-18:45 | 4391.56 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 16.27 | 0.00 | 20-FEB-15:30 | 4391.56 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 8.12 | 0.00 | 01-JAN-00:15 | 2948.92 | 25-JUN-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 23.13 | 0.09 | 14-APR-10:15 | 4207.18 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 11.03 | 0.00 | 02-JAN-10:45 | 4207.18 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 12.10 | 0.00 | 01-JAN-00:15 | 3245.27 | 07-SEP-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 24.25 | 0.02 | 20-MAR-03:30 | 4371.81 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 16.11 | 0.00 | 24-FEB-09:45 | 4371.81 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 8.14 | 0.00 | 01-JAN-00:15 | 2189.96 | 26-JUN-17:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 14.60 | 0.04 | 03-APR-17:45 | 2534.92 | 23-MAR-14:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 7.77 | 0.00 | 11-JAN-18:30 | 2534.92 | 23-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 6.82 | 0.00 | 01-JAN-00:15 | 1692.36 | 28-JUN-19:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 14.59 | 0.02 | 21-MAY-14:00 | 2531.99 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 7.77 | 0.00 | 11-JAN-18:30 | 2531.99 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 6.82 | 0.00 | 01-JAN-00:15 | 1681.34 | 28-JUN-19:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 15.26 | 0.03 | 22-JUN-10:30 | 2430.96 | 05-SEP-12:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 4.28 | 0.00 | 02-JAN-10:00 | 2386.30 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 10.98 | 0.00 | 01-JAN-00:15 | 2430.96 | 05-SEP-12:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 15.29 | 0.00 | 11-JUL-16:45 | 2449.40 | 05-SEP-12:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 4.26 | 0.00 | 02-JAN-10:00 | 2382.30 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 11.03 | 0.00 | 01-JAN-00:15 | 2449.40 | 05-SEP-12:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 24.14 | 0.00 | 24-APR-01:45 | 4654.68 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 12.09 | 0.00 | 02-JAN-12:30 | 4654.68 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 12.05 | 0.00 | 01-JAN-00:15 | 3515.01 | 07-SEP-15:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 25.48 | 0.01 | 10-APR-09:30 | 4792.26 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 16.88 | 0.00 | 20-FEB-15:30 | 4792.26 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 8.60 | 0.00 | 01-JAN-00:15 | 2994.34 | 25-JUN-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 24.01 | 0.09 | 25-FEB-04:15 | 4628.56 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 11.92 | 0.00 | 02-JAN-12:15 | 4628.56 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 12.09 | 0.00 | 01-JAN-00:15 | 3287.80 | 09-SEP-11:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 25.34 | 0.02 | 26-MAR-03:00 | 4770.96 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 16.73 | 0.00 | 24-FEB-09:45 | 4770.96 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 8.61 | 0.00 | 01-JAN-00:15 | 2263.50 | 28-JUN-19:00 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 15.23 | 0.03 | 22-APR-09:45 | 2954.71 | 23-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.79 | 0.00 | 11-JAN-18:15 | 2954.71 | 23-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.44 | 0.00 | 01-JAN-00:15 | 1763.71 | 31-MAY-18:30 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 15.22 | 0.02 | 24-AUG-11:30 | 2949.47 | 23-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.79 | 0.00 | 11-JAN-18:15 | 2949.47 | 23-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.43 | 0.00 | 01-JAN-00:15 | 1754.67 | 31-MAY-18:30 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 16.10 | 0.01 | 16-JAN-18:15 | 2562.04 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 4.29 | 0.00 | 01-JAN-10:30 | 2562.04 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 11.81 | 0.00 | 01-JAN-00:15 | 2527.52 | 05-SEP-12:30 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 16.11 | 0.19 | 11-MAY-15:30 | 2561.40 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 4.29 | 0.00 | 01-JAN-10:30 | 2561.40 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 11.82 | 0.00 | 01-JAN-00:15 | 2542.34 | 05-SEP-12:30 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 24.96 | 0.03 | 11-JUL-02:00 | 5003.71 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 12.99 | 0.00 | 02-JAN-13:15 | 5003.71 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 11.97 | 0.00 | 01-JAN-00:15 | 3553.79 | 02-SEP-15:00 |
EnergyTransfer:Zone:F4 NW APARTMENT | 26.49 | 0.02 | 24-MAR-12:30 | 5147.43 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 17.88 | 0.00 | 20-FEB-15:45 | 5147.43 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 8.61 | 0.00 | 01-JAN-00:15 | 3021.30 | 25-JUN-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 24.81 | 0.05 | 23-AUG-09:30 | 4984.05 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 12.88 | 0.00 | 02-JAN-12:30 | 4984.05 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 11.93 | 0.00 | 01-JAN-00:15 | 3307.17 | 09-SEP-11:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 26.34 | 0.04 | 31-MAR-20:30 | 5125.10 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 17.72 | 0.00 | 24-FEB-10:00 | 5125.10 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 8.62 | 0.00 | 01-JAN-00:15 | 2305.49 | 28-JUN-19:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 15.77 | 0.00 | 03-JUL-05:45 | 3138.27 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 8.23 | 0.00 | 11-JAN-18:15 | 3138.27 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 7.54 | 0.00 | 01-JAN-00:15 | 1805.01 | 31-MAY-18:30 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 15.76 | 0.00 | 17-APR-15:45 | 3134.67 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 8.24 | 0.00 | 11-JAN-18:15 | 3134.67 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 7.53 | 0.00 | 01-JAN-00:15 | 1789.77 | 31-MAY-18:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 16.51 | 0.01 | 22-JUN-10:15 | 2757.76 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 4.65 | 0.00 | 01-JAN-10:30 | 2757.76 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 11.86 | 0.00 | 01-JAN-00:15 | 2561.76 | 05-SEP-12:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 16.50 | 0.01 | 06-JUN-15:45 | 2758.01 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 4.65 | 0.00 | 01-JAN-10:30 | 2758.01 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 11.85 | 0.00 | 01-JAN-00:15 | 2576.02 | 05-SEP-12:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 25.64 | 0.02 | 02-NOV-11:30 | 5282.59 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 13.68 | 0.00 | 02-JAN-13:15 | 5282.59 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 11.96 | 0.00 | 01-JAN-00:15 | 3614.00 | 02-SEP-15:00 |
EnergyTransfer:Zone:M NW APARTMENT | 27.27 | 0.00 | 04-NOV-12:15 | 5426.22 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 18.58 | 0.00 | 20-FEB-16:15 | 5426.22 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 8.69 | 0.00 | 01-JAN-00:15 | 3064.45 | 25-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 25.47 | 0.03 | 19-MAR-20:45 | 5263.35 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 13.57 | 0.00 | 02-JAN-13:00 | 5263.35 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 11.90 | 0.00 | 01-JAN-00:15 | 3358.52 | 09-SEP-11:30 |
EnergyTransfer:Zone:M NE APARTMENT | 27.11 | 0.10 | 11-SEP-06:45 | 5403.18 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 18.41 | 0.00 | 24-FEB-10:00 | 5403.18 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 8.70 | 0.00 | 01-JAN-00:15 | 2360.09 | 28-JUN-19:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 16.21 | 0.00 | 19-SEP-15:30 | 3421.96 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 8.52 | 0.00 | 11-JAN-18:15 | 3421.96 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 7.69 | 0.00 | 01-JAN-00:15 | 1851.57 | 31-MAY-18:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 16.20 | 0.04 | 07-JUN-10:30 | 3418.73 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 8.52 | 0.00 | 11-JAN-18:15 | 3418.73 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 7.68 | 0.00 | 01-JAN-00:15 | 1836.37 | 31-MAY-18:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 16.84 | 0.02 | 01-JUL-05:45 | 2915.10 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 4.92 | 0.00 | 01-JAN-10:30 | 2915.10 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 11.92 | 0.00 | 01-JAN-00:15 | 2598.66 | 05-SEP-12:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 16.83 | 0.06 | 18-APR-06:00 | 2915.53 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 4.92 | 0.00 | 01-JAN-10:30 | 2915.53 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 11.91 | 0.00 | 01-JAN-00:15 | 2612.85 | 05-SEP-12:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 26.17 | 0.08 | 08-APR-09:45 | 5585.96 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 14.93 | 0.00 | 02-JAN-13:30 | 5585.96 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 11.24 | 0.00 | 01-JAN-00:15 | 3599.38 | 02-SEP-15:00 |
EnergyTransfer:Zone:F6 NW APARTMENT | 28.19 | 0.03 | 11-APR-13:15 | 5728.73 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 20.02 | 0.00 | 24-FEB-14:45 | 5728.73 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 8.17 | 0.00 | 01-JAN-00:15 | 3031.92 | 25-JUN-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 25.99 | 0.03 | 21-OCT-09:15 | 5566.25 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 14.82 | 0.00 | 02-JAN-13:45 | 5566.25 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 11.17 | 0.00 | 01-JAN-00:15 | 3334.87 | 09-SEP-11:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 28.00 | 0.02 | 28-OCT-14:30 | 5705.13 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 19.84 | 0.00 | 24-FEB-20:00 | 5705.13 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 8.17 | 0.00 | 01-JAN-00:15 | 2344.86 | 28-JUN-19:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 16.59 | 0.02 | 17-APR-18:15 | 3763.71 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 9.43 | 0.00 | 11-JAN-18:15 | 3763.71 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.15 | 0.00 | 01-JAN-00:15 | 1823.01 | 31-MAY-18:30 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 16.58 | 0.01 | 17-APR-15:45 | 3760.72 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 9.44 | 0.00 | 11-JAN-18:15 | 3760.72 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.14 | 0.00 | 01-JAN-00:15 | 1807.92 | 31-MAY-18:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 16.71 | 0.02 | 24-MAY-08:30 | 3112.59 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 5.59 | 0.00 | 02-JAN-10:15 | 3112.59 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 11.12 | 0.00 | 01-JAN-00:15 | 2556.36 | 05-SEP-12:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 16.70 | 0.09 | 14-MAR-17:45 | 3113.05 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 5.59 | 0.00 | 02-JAN-10:15 | 3113.05 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 11.11 | 0.00 | 01-JAN-00:15 | 2570.70 | 05-SEP-12:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 26.73 | 0.03 | 23-APR-20:30 | 5839.37 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 15.93 | 0.00 | 02-JAN-13:45 | 5839.37 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 10.80 | 0.00 | 01-JAN-00:15 | 3604.53 | 02-SEP-15:00 |
EnergyTransfer:Zone:F7 NW APARTMENT | 28.97 | 0.05 | 09-OCT-15:15 | 5978.90 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 21.10 | 0.00 | 24-FEB-14:45 | 5978.90 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 7.87 | 0.00 | 01-JAN-00:15 | 3025.67 | 25-JUN-17:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 26.54 | 0.08 | 19-MAR-24:00 | 5819.15 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 15.81 | 0.00 | 03-JAN-11:00 | 5819.15 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 10.74 | 0.00 | 01-JAN-00:15 | 3335.74 | 09-SEP-11:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 28.77 | 0.03 | 23-SEP-23:30 | 5954.86 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 20.91 | 0.00 | 18-MAR-14:30 | 5954.86 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 7.85 | 0.00 | 01-JAN-00:15 | 2350.07 | 28-JUN-19:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 16.95 | 0.04 | 24-AUG-15:45 | 4049.47 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 10.11 | 0.00 | 11-JAN-18:30 | 4049.47 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 6.85 | 0.00 | 01-JAN-00:15 | 1819.16 | 31-MAY-18:30 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 16.95 | 0.01 | 16-JUN-08:15 | 4046.07 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 10.11 | 0.00 | 11-JAN-18:30 | 4046.07 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 6.84 | 0.00 | 01-JAN-00:15 | 1804.15 | 31-MAY-18:30 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 16.74 | 0.02 | 12-JUL-08:00 | 3275.17 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 6.12 | 0.00 | 02-JAN-10:30 | 3275.17 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 10.61 | 0.00 | 01-JAN-00:15 | 2534.02 | 05-SEP-12:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 16.74 | 0.04 | 12-JUL-08:00 | 3275.63 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 6.13 | 0.00 | 02-JAN-10:30 | 3275.63 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 10.61 | 0.00 | 01-JAN-00:15 | 2548.60 | 05-SEP-12:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 27.38 | 0.02 | 15-APR-05:45 | 6079.09 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 16.91 | 0.00 | 02-JAN-13:45 | 6079.09 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 10.47 | 0.00 | 01-JAN-00:15 | 3611.97 | 02-SEP-15:00 |
EnergyTransfer:Zone:F8 NW APARTMENT | 29.82 | 0.03 | 11-MAY-24:00 | 6212.16 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 22.16 | 0.00 | 24-FEB-15:00 | 6212.16 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 7.67 | 0.00 | 01-JAN-00:15 | 3032.94 | 25-JUN-17:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 27.19 | 0.03 | 01-OCT-23:00 | 6058.32 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 16.78 | 0.00 | 03-JAN-12:30 | 6058.32 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 10.41 | 0.00 | 01-JAN-00:15 | 3348.38 | 09-SEP-11:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 29.60 | 0.02 | 08-NOV-23:45 | 6187.70 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 21.97 | 0.00 | 18-MAR-14:30 | 6187.70 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 7.63 | 0.00 | 01-JAN-00:15 | 2384.41 | 18-APR-15:30 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 17.44 | 0.05 | 22-JUN-10:30 | 4306.86 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 10.80 | 0.00 | 11-JAN-18:30 | 4306.86 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 6.64 | 0.00 | 01-JAN-00:15 | 1828.82 | 31-MAY-18:30 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 17.43 | 0.02 | 19-SEP-15:15 | 4303.60 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 10.80 | 0.00 | 11-JAN-18:30 | 4303.60 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 6.63 | 0.00 | 01-JAN-00:15 | 1813.91 | 31-MAY-18:30 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 16.90 | 0.01 | 20-MAY-15:30 | 3435.11 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 6.69 | 0.00 | 02-JAN-10:30 | 3435.11 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 10.22 | 0.00 | 01-JAN-00:15 | 2593.54 | 05-SEP-12:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 16.90 | 0.00 | 26-FEB-05:45 | 3435.53 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 6.69 | 0.00 | 02-JAN-10:30 | 3435.53 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 10.21 | 0.00 | 01-JAN-00:15 | 2605.63 | 05-SEP-12:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 29.09 | 0.00 | 09-NOV-08:45 | 6446.05 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 18.85 | 0.00 | 02-JAN-14:15 | 6446.05 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 10.24 | 0.00 | 01-JAN-00:15 | 3717.08 | 02-SEP-15:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 31.86 | 0.02 | 04-JUN-13:00 | 6558.69 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 24.26 | 0.00 | 24-FEB-15:15 | 6558.69 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 7.61 | 0.00 | 01-JAN-00:15 | 3125.20 | 25-JUN-17:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 28.86 | 0.02 | 11-JUL-23:45 | 6423.47 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 18.69 | 0.00 | 03-JAN-12:45 | 6423.47 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 10.16 | 0.00 | 01-JAN-00:15 | 3416.82 | 09-SEP-11:30 |
EnergyTransfer:Zone:F9 NE APARTMENT | 31.58 | 0.02 | 27-SEP-20:30 | 6532.98 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 24.06 | 0.00 | 18-MAR-15:00 | 6532.98 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 7.52 | 0.00 | 01-JAN-00:15 | 2535.61 | 28-JUN-18:45 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 18.93 | 0.04 | 26-MAY-20:15 | 4571.38 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 12.43 | 0.00 | 11-JAN-18:45 | 4571.38 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.51 | 0.00 | 01-JAN-00:15 | 1912.57 | 31-MAY-18:30 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 18.93 | 0.09 | 04-MAY-24:00 | 4568.36 | 23-MAR-14:15 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 12.43 | 0.00 | 11-JAN-18:45 | 4568.36 | 23-MAR-14:15 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.50 | 0.00 | 01-JAN-00:15 | 1897.55 | 31-MAY-18:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 17.83 | 0.10 | 04-SEP-09:45 | 3721.31 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 8.02 | 0.00 | 02-JAN-11:00 | 3721.31 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 9.81 | 0.00 | 01-JAN-00:15 | 2612.24 | 05-SEP-12:45 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 17.83 | 0.02 | 19-JUN-11:15 | 3721.59 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 8.02 | 0.00 | 02-JAN-11:00 | 3721.59 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 9.80 | 0.00 | 01-JAN-00:15 | 2628.41 | 05-SEP-12:45 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 37.19 | 0.01 | 17-MAY-09:15 | 7499.10 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 26.86 | 0.00 | 02-JAN-14:00 | 7499.10 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 10.34 | 0.00 | 01-JAN-00:15 | 4418.59 | 07-SEP-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 39.43 | 0.04 | 30-APR-06:45 | 7573.46 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 31.58 | 0.00 | 24-FEB-14:30 | 7573.46 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 7.85 | 0.00 | 01-JAN-00:15 | 3686.57 | 05-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 36.59 | 0.01 | 02-JUN-22:30 | 7471.78 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 26.56 | 0.00 | 03-JAN-12:45 | 7471.78 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 10.03 | 0.00 | 01-JAN-00:15 | 4130.36 | 07-SEP-13:15 |
EnergyTransfer:Zone:T NE APARTMENT | 38.81 | 0.02 | 09-OCT-15:45 | 7545.12 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 31.25 | 0.00 | 18-MAR-13:15 | 7545.12 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.57 | 0.00 | 01-JAN-00:15 | 2978.80 | 28-JUN-10:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 25.57 | 0.01 | 22-APR-20:15 | 4838.36 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 19.12 | 0.00 | 24-FEB-14:45 | 4838.36 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.46 | 0.00 | 01-JAN-00:15 | 2291.46 | 11-AUG-15:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 25.58 | 0.01 | 07-MAY-05:15 | 4837.88 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 19.12 | 0.00 | 24-FEB-14:45 | 4837.88 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.45 | 0.00 | 01-JAN-00:15 | 2289.40 | 11-AUG-15:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 23.98 | 0.00 | 12-JUL-00:30 | 4751.18 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 14.80 | 0.00 | 02-JAN-11:15 | 4751.18 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 9.18 | 0.00 | 01-JAN-00:15 | 3370.71 | 07-SEP-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 23.99 | 0.01 | 12-JUL-01:15 | 4750.86 | 09-DEC-02:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 14.81 | 0.00 | 02-JAN-11:15 | 4750.86 | 09-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 9.18 | 0.00 | 01-JAN-00:15 | 3381.41 | 07-SEP-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 2233.65 | 527.80 | 21-AUG-01:15 | 317689.55 | 19-JAN-06:15 |
WaterSystems:EnergyTransfer | 985.91 | 527.80 | 21-AUG-01:15 | 67601.12 | 19-FEB-07:45 |
sub cat:WaterSystems:EnergyTransfer | 985.91 | 527.80 | 21-AUG-01:15 | 67601.12 | 19-FEB-07:45 |
EnergyTransfer:HVAC | 2664.92 | 0.00 | 19-MAR-16:15 | 436302.53 | 09-DEC-02:00 |
CoolingCoils:EnergyTransfer | 992.40 | 0.00 | 01-JAN-00:15 | 319713.71 | 03-AUG-08:30 |
HeatingCoils:EnergyTransfer | 1672.52 | 0.00 | 18-MAR-15:15 | 436302.53 | 09-DEC-02:00 |
PlantLoopHeatingDemand:HVAC | 1285.65 | 0.00 | 18-MAR-15:15 | 259002.82 | 19-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 1285.65 | 0.00 | 18-MAR-15:15 | 259002.82 | 19-JAN-05:00 |
Boilers:EnergyTransfer | 1247.75 | 0.00 | 24-FEB-13:45 | 257662.17 | 19-JAN-05:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 12.312 | -7.221 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 17.729 | 0.000 | 0.182 | 0.000 | 0.000 | -14.709 | 0.000 | -9.900 | -16.893 |
G NW APARTMENT | 16.197 | -5.093 | 0.000 | 0.000 | 3.896 | 2.413 | 12.213 | 8.901 | 0.000 | 0.174 | 0.000 | 0.000 | -15.635 | 0.000 | -9.575 | -13.490 |
OFFICE | 11.742 | -11.878 | 0.000 | 0.000 | 0.538 | 21.954 | 7.547 | 17.321 | 0.000 | 0.072 | 0.000 | 0.000 | -14.633 | 0.000 | -6.937 | -25.726 |
G NE APARTMENT | 16.092 | -4.954 | 0.000 | 0.000 | 3.904 | 2.413 | 12.213 | 8.548 | 0.000 | 0.174 | 0.000 | 0.000 | -15.424 | 0.000 | -9.592 | -13.372 |
G N1 APARTMENT | 9.323 | -4.230 | 0.000 | 0.000 | 3.906 | 2.413 | 12.213 | 3.146 | 0.000 | 0.146 | 0.000 | 0.000 | -9.891 | 0.000 | -6.670 | -10.355 |
G N2 APARTMENT | 9.326 | -4.218 | 0.000 | 0.000 | 3.906 | 2.413 | 12.213 | 3.144 | 0.000 | 0.146 | 0.000 | 0.000 | -9.889 | 0.000 | -6.672 | -10.369 |
G S1 APARTMENT | 5.725 | -6.902 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 12.087 | 0.000 | 0.153 | 0.000 | 0.000 | -8.969 | 0.000 | -7.017 | -13.578 |
G S2 APARTMENT | 5.628 | -7.005 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 12.075 | 0.000 | 0.153 | 0.000 | 0.000 | -8.976 | 0.000 | -7.047 | -13.326 |
F2 SW APARTMENT | 11.556 | -11.548 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 17.039 | 0.000 | 0.243 | 0.000 | 0.000 | -15.613 | 0.000 | -13.819 | -6.302 |
F2 NW APARTMENT | 16.268 | -8.119 | 0.000 | 0.000 | 3.857 | 2.413 | 12.213 | 8.470 | 0.000 | 0.229 | 0.000 | 0.000 | -16.541 | 0.000 | -13.323 | -5.468 |
F2 SE APARTMENT | 11.025 | -12.102 | 0.000 | 0.000 | 3.818 | 2.413 | 12.213 | 16.677 | 0.000 | 0.242 | 0.000 | 0.000 | -15.456 | 0.000 | -13.890 | -4.940 |
F2 NE APARTMENT | 16.110 | -8.142 | 0.000 | 0.000 | 3.870 | 2.413 | 12.213 | 8.134 | 0.000 | 0.227 | 0.000 | 0.000 | -16.283 | 0.000 | -13.291 | -5.251 |
F2 N1 APARTMENT | 7.772 | -6.824 | 0.000 | 0.000 | 3.865 | 2.413 | 12.213 | 2.925 | 0.000 | 0.187 | 0.000 | 0.000 | -10.511 | 0.000 | -9.186 | -2.853 |
F2 N2 APARTMENT | 7.772 | -6.817 | 0.000 | 0.000 | 3.866 | 2.413 | 12.213 | 2.924 | 0.000 | 0.187 | 0.000 | 0.000 | -10.508 | 0.000 | -9.184 | -2.866 |
F2 S1 APARTMENT | 4.284 | -10.979 | 0.000 | 0.000 | 3.811 | 2.413 | 12.213 | 11.649 | 0.000 | 0.201 | 0.000 | 0.000 | -9.521 | 0.000 | -9.723 | -4.347 |
F2 S2 APARTMENT | 4.264 | -11.030 | 0.000 | 0.000 | 3.810 | 2.413 | 12.213 | 11.645 | 0.000 | 0.201 | 0.000 | 0.000 | -9.524 | 0.000 | -9.733 | -4.258 |
F3 SW APARTMENT | 12.085 | -12.052 | 0.000 | 0.000 | 3.814 | 2.413 | 12.213 | 16.772 | 0.000 | 0.326 | 0.000 | 0.000 | -15.906 | 0.000 | -16.005 | -3.659 |
F3 NW APARTMENT | 16.883 | -8.598 | 0.000 | 0.000 | 3.852 | 2.413 | 12.213 | 8.321 | 0.000 | 0.303 | 0.000 | 0.000 | -16.870 | 0.000 | -15.450 | -3.067 |
F3 SE APARTMENT | 11.918 | -12.089 | 0.000 | 0.000 | 3.819 | 2.413 | 12.213 | 16.451 | 0.000 | 0.323 | 0.000 | 0.000 | -15.687 | 0.000 | -16.016 | -3.345 |
F3 NE APARTMENT | 16.730 | -8.612 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 7.992 | 0.000 | 0.299 | 0.000 | 0.000 | -16.596 | 0.000 | -15.412 | -2.891 |
F3 N1 APARTMENT | 7.785 | -7.441 | 0.000 | 0.000 | 3.856 | 2.413 | 12.213 | 2.858 | 0.000 | 0.252 | 0.000 | 0.000 | -10.732 | 0.000 | -10.598 | -0.606 |
F3 N2 APARTMENT | 7.788 | -7.431 | 0.000 | 0.000 | 3.857 | 2.413 | 12.213 | 2.857 | 0.000 | 0.252 | 0.000 | 0.000 | -10.728 | 0.000 | -10.595 | -0.625 |
F3 S1 APARTMENT | 4.290 | -11.809 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 11.472 | 0.000 | 0.273 | 0.000 | 0.000 | -9.716 | 0.000 | -11.198 | -1.738 |
F3 S2 APARTMENT | 4.290 | -11.816 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 11.470 | 0.000 | 0.273 | 0.000 | 0.000 | -9.715 | 0.000 | -11.202 | -1.725 |
F4 SW APARTMENT | 12.989 | -11.974 | 0.000 | 0.000 | 3.815 | 2.413 | 12.213 | 16.613 | 0.000 | 0.355 | 0.000 | 0.000 | -16.063 | 0.000 | -17.471 | -2.890 |
F4 NW APARTMENT | 17.879 | -8.607 | 0.000 | 0.000 | 3.852 | 2.413 | 12.213 | 8.238 | 0.000 | 0.329 | 0.000 | 0.000 | -17.060 | 0.000 | -16.895 | -2.362 |
F4 SE APARTMENT | 12.879 | -11.927 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 16.303 | 0.000 | 0.351 | 0.000 | 0.000 | -15.827 | 0.000 | -17.470 | -2.756 |
F4 NE APARTMENT | 17.722 | -8.620 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 7.913 | 0.000 | 0.324 | 0.000 | 0.000 | -16.778 | 0.000 | -16.854 | -2.197 |
F4 N1 APARTMENT | 8.234 | -7.536 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 2.824 | 0.000 | 0.272 | 0.085 | 0.000 | -10.860 | 0.000 | -11.499 | -0.000 |
F4 N2 APARTMENT | 8.235 | -7.525 | 0.000 | 0.000 | 3.855 | 2.413 | 12.213 | 2.823 | 0.000 | 0.271 | 0.066 | 0.000 | -10.855 | 0.000 | -11.496 | -0.000 |
F4 S1 APARTMENT | 4.651 | -11.858 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 11.366 | 0.000 | 0.295 | 0.000 | 0.000 | -9.817 | 0.000 | -12.119 | -0.943 |
F4 S2 APARTMENT | 4.651 | -11.848 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 11.365 | 0.000 | 0.295 | 0.001 | 0.000 | -9.815 | 0.000 | -12.121 | -0.952 |
M SW APARTMENT | 13.675 | -11.960 | 0.000 | 0.000 | 3.817 | 2.413 | 12.213 | 16.489 | 0.000 | 0.377 | 0.000 | 0.000 | -16.190 | 0.000 | -18.813 | -2.021 |
M NW APARTMENT | 18.578 | -8.693 | 0.000 | 0.000 | 3.853 | 2.413 | 12.213 | 8.173 | 0.000 | 0.350 | 0.000 | 0.000 | -17.214 | 0.000 | -18.207 | -1.466 |
M SE APARTMENT | 13.570 | -11.899 | 0.000 | 0.000 | 3.823 | 2.413 | 12.213 | 16.184 | 0.000 | 0.373 | 0.000 | 0.000 | -15.947 | 0.000 | -18.810 | -1.921 |
M NE APARTMENT | 18.409 | -8.704 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 7.851 | 0.000 | 0.344 | 0.000 | 0.000 | -16.926 | 0.000 | -18.163 | -1.301 |
M N1 APARTMENT | 8.518 | -7.687 | 0.000 | 0.000 | 3.853 | 2.413 | 12.213 | 2.797 | 0.000 | 0.287 | 0.925 | 0.000 | -10.962 | 0.000 | -12.358 | -0.000 |
M N2 APARTMENT | 8.519 | -7.676 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 2.797 | 0.000 | 0.287 | 0.905 | 0.000 | -10.958 | 0.000 | -12.355 | -0.000 |
M S1 APARTMENT | 4.919 | -11.923 | 0.000 | 0.000 | 3.799 | 2.413 | 12.213 | 11.285 | 0.000 | 0.312 | 0.000 | 0.000 | -9.897 | 0.000 | -13.008 | -0.113 |
M S2 APARTMENT | 4.921 | -11.911 | 0.000 | 0.000 | 3.800 | 2.413 | 12.213 | 11.284 | 0.000 | 0.312 | 0.000 | 0.000 | -9.895 | 0.000 | -13.010 | -0.128 |
F6 SW APARTMENT | 14.931 | -11.241 | 0.000 | 0.000 | 3.825 | 2.413 | 12.213 | 16.426 | 0.000 | 0.395 | 0.000 | 0.000 | -16.225 | 0.000 | -19.899 | -2.838 |
F6 NW APARTMENT | 20.018 | -8.167 | 0.000 | 0.000 | 3.860 | 2.413 | 12.213 | 8.152 | 0.000 | 0.367 | 0.000 | 0.000 | -17.271 | 0.000 | -19.266 | -2.319 |
F6 SE APARTMENT | 14.818 | -11.174 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 16.125 | 0.000 | 0.391 | 0.000 | 0.000 | -15.977 | 0.000 | -19.898 | -2.743 |
F6 NE APARTMENT | 19.836 | -8.165 | 0.000 | 0.000 | 3.871 | 2.413 | 12.213 | 7.833 | 0.000 | 0.360 | 0.000 | 0.000 | -16.980 | 0.000 | -19.223 | -2.158 |
F6 N1 APARTMENT | 9.434 | -7.152 | 0.000 | 0.000 | 3.861 | 2.413 | 12.213 | 2.796 | 0.000 | 0.300 | 0.153 | 0.000 | -10.996 | 0.000 | -13.021 | -0.000 |
F6 N2 APARTMENT | 9.436 | -7.143 | 0.000 | 0.000 | 3.862 | 2.413 | 12.213 | 2.795 | 0.000 | 0.299 | 0.134 | 0.000 | -10.992 | 0.000 | -13.018 | -0.000 |
F6 S1 APARTMENT | 5.589 | -11.118 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 11.243 | 0.000 | 0.326 | 0.001 | 0.000 | -9.915 | 0.000 | -13.702 | -0.857 |
F6 S2 APARTMENT | 5.592 | -11.105 | 0.000 | 0.000 | 3.808 | 2.413 | 12.213 | 11.242 | 0.000 | 0.326 | 0.001 | 0.000 | -9.913 | 0.000 | -13.703 | -0.873 |
F7 SW APARTMENT | 15.926 | -10.802 | 0.000 | 0.000 | 3.831 | 2.413 | 12.213 | 16.365 | 0.000 | 0.411 | 0.000 | 0.000 | -16.267 | 0.000 | -20.858 | -3.231 |
F7 NW APARTMENT | 21.100 | -7.868 | 0.000 | 0.000 | 3.865 | 2.413 | 12.213 | 8.129 | 0.000 | 0.380 | 0.000 | 0.000 | -17.334 | 0.000 | -20.203 | -2.696 |
F7 SE APARTMENT | 15.805 | -10.735 | 0.000 | 0.000 | 3.838 | 2.413 | 12.213 | 16.067 | 0.000 | 0.406 | 0.000 | 0.000 | -16.016 | 0.000 | -20.858 | -3.133 |
F7 NE APARTMENT | 20.913 | -7.854 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 7.811 | 0.000 | 0.374 | 0.000 | 0.000 | -17.041 | 0.000 | -20.164 | -2.541 |
F7 N1 APARTMENT | 10.105 | -6.848 | 0.000 | 0.000 | 3.866 | 2.413 | 12.213 | 2.791 | 0.000 | 0.310 | 0.000 | 0.000 | -11.033 | 0.000 | -13.610 | -0.207 |
F7 N2 APARTMENT | 10.110 | -6.843 | 0.000 | 0.000 | 3.867 | 2.413 | 12.213 | 2.790 | 0.000 | 0.310 | 0.000 | 0.000 | -11.029 | 0.000 | -13.607 | -0.223 |
F7 S1 APARTMENT | 6.121 | -10.615 | 0.000 | 0.000 | 3.815 | 2.413 | 12.213 | 11.203 | 0.000 | 0.338 | 0.000 | 0.000 | -9.938 | 0.000 | -14.314 | -1.235 |
F7 S2 APARTMENT | 6.129 | -10.606 | 0.000 | 0.000 | 3.815 | 2.413 | 12.213 | 11.202 | 0.000 | 0.338 | 0.000 | 0.000 | -9.936 | 0.000 | -14.316 | -1.252 |
F8 SW APARTMENT | 16.909 | -10.472 | 0.000 | 0.000 | 3.837 | 2.413 | 12.213 | 16.313 | 0.000 | 0.428 | 0.000 | 0.000 | -16.304 | 0.000 | -21.748 | -3.588 |
F8 NW APARTMENT | 22.156 | -7.666 | 0.000 | 0.000 | 3.870 | 2.413 | 12.213 | 8.107 | 0.000 | 0.396 | 0.000 | 0.000 | -17.389 | 0.000 | -21.074 | -3.025 |
F8 SE APARTMENT | 16.783 | -10.408 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 16.017 | 0.000 | 0.423 | 0.000 | 0.000 | -16.050 | 0.000 | -21.749 | -3.485 |
F8 NE APARTMENT | 21.970 | -7.627 | 0.000 | 0.000 | 3.880 | 2.413 | 12.213 | 7.789 | 0.000 | 0.390 | 0.000 | 0.000 | -17.096 | 0.000 | -21.045 | -2.886 |
F8 N1 APARTMENT | 10.799 | -6.639 | 0.000 | 0.000 | 3.871 | 2.413 | 12.213 | 2.786 | 0.000 | 0.322 | 0.000 | 0.000 | -11.066 | 0.000 | -14.167 | -0.532 |
F8 N2 APARTMENT | 10.799 | -6.630 | 0.000 | 0.000 | 3.872 | 2.413 | 12.213 | 2.785 | 0.000 | 0.322 | 0.000 | 0.000 | -11.062 | 0.000 | -14.165 | -0.546 |
F8 S1 APARTMENT | 6.688 | -10.217 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 11.169 | 0.000 | 0.351 | 0.000 | 0.000 | -9.957 | 0.000 | -14.890 | -1.592 |
F8 S2 APARTMENT | 6.693 | -10.207 | 0.000 | 0.000 | 3.821 | 2.413 | 12.213 | 11.168 | 0.000 | 0.351 | 0.000 | 0.000 | -9.954 | 0.000 | -14.892 | -1.607 |
F9 SW APARTMENT | 18.849 | -10.236 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 16.286 | 0.000 | 0.449 | 0.000 | 0.000 | -16.295 | 0.000 | -22.539 | -4.984 |
F9 NW APARTMENT | 24.257 | -7.607 | 0.000 | 0.000 | 3.874 | 2.413 | 12.213 | 8.097 | 0.000 | 0.415 | 0.000 | 0.000 | -17.400 | 0.000 | -21.860 | -4.403 |
F9 SE APARTMENT | 18.694 | -10.161 | 0.000 | 0.000 | 3.851 | 2.413 | 12.213 | 15.992 | 0.000 | 0.444 | 0.000 | 0.000 | -16.040 | 0.000 | -22.545 | -4.861 |
F9 NE APARTMENT | 24.057 | -7.523 | 0.000 | 0.000 | 3.883 | 2.413 | 12.213 | 7.779 | 0.000 | 0.411 | 0.000 | 0.000 | -17.109 | 0.000 | -21.845 | -4.279 |
F9 N1 APARTMENT | 12.429 | -6.505 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 2.786 | 0.000 | 0.340 | 0.000 | 0.000 | -11.067 | 0.000 | -14.668 | -1.816 |
F9 N2 APARTMENT | 12.431 | -6.498 | 0.000 | 0.000 | 3.876 | 2.413 | 12.213 | 2.785 | 0.000 | 0.339 | 0.000 | 0.000 | -11.064 | 0.000 | -14.666 | -1.829 |
F9 S1 APARTMENT | 8.020 | -9.813 | 0.000 | 0.000 | 3.829 | 2.413 | 12.213 | 11.154 | 0.000 | 0.370 | 0.000 | 0.000 | -9.944 | 0.000 | -15.393 | -2.848 |
F9 S2 APARTMENT | 8.024 | -9.803 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 11.152 | 0.000 | 0.370 | 0.000 | 0.000 | -9.942 | 0.000 | -15.395 | -2.861 |
T SW APARTMENT | 26.855 | -10.339 | 0.000 | 0.000 | 3.871 | 2.413 | 12.213 | 16.097 | 0.000 | 0.459 | 0.000 | 0.000 | -15.751 | 0.000 | -23.156 | -12.662 |
T NW APARTMENT | 31.581 | -7.849 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 7.958 | 0.000 | 0.424 | 0.000 | 0.000 | -16.910 | 0.000 | -22.506 | -11.215 |
T SE APARTMENT | 26.564 | -10.027 | 0.000 | 0.000 | 3.877 | 2.413 | 12.213 | 15.827 | 0.000 | 0.453 | 0.000 | 0.000 | -15.525 | 0.000 | -23.179 | -12.617 |
T NE APARTMENT | 31.246 | -7.567 | 0.000 | 0.000 | 3.901 | 2.413 | 12.213 | 7.665 | 0.000 | 0.420 | 0.000 | 0.000 | -16.647 | 0.000 | -22.512 | -11.133 |
T N1 APARTMENT | 19.115 | -6.457 | 0.000 | 0.000 | 3.895 | 2.413 | 12.213 | 2.747 | 0.000 | 0.346 | 0.000 | 0.000 | -10.739 | 0.000 | -15.037 | -8.495 |
T N2 APARTMENT | 19.121 | -6.454 | 0.000 | 0.000 | 3.896 | 2.413 | 12.213 | 2.745 | 0.000 | 0.347 | 0.000 | 0.000 | -10.735 | 0.000 | -15.041 | -8.505 |
T S1 APARTMENT | 14.804 | -9.179 | 0.000 | 0.000 | 3.858 | 2.413 | 12.213 | 11.059 | 0.000 | 0.383 | 0.000 | 0.000 | -9.645 | 0.000 | -15.759 | -10.147 |
T S2 APARTMENT | 14.812 | -9.175 | 0.000 | 0.000 | 3.859 | 2.413 | 12.213 | 11.055 | 0.000 | 0.383 | 0.000 | 0.000 | -9.641 | 0.000 | -15.764 | -10.155 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 3.791 | 0.000 | 0.455 | 40.441 | 0.000 | -3.345 | 0.000 | -59.871 | -0.002 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.710 | 0.000 | 0.006 | 0.000 | 0.000 | -2.023 | 0.000 | -1.767 | -16.455 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.668 | 0.000 | 0.007 | 0.000 | 0.000 | -2.103 | 0.000 | -2.137 | -15.964 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.645 | 0.000 | 0.007 | 0.000 | 0.000 | -2.141 | 0.000 | -2.405 | -15.635 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.617 | 0.000 | 0.005 | 0.000 | 0.000 | -2.195 | 0.000 | -2.700 | -33.785 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.627 | 0.000 | 0.008 | 0.000 | 0.000 | -2.164 | 0.000 | -2.786 | -15.214 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.627 | 0.000 | 0.009 | 0.000 | 0.000 | -2.159 | 0.000 | -2.923 | -15.083 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.623 | 0.000 | 0.009 | 0.000 | 0.000 | -2.159 | 0.000 | -3.054 | -14.949 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.622 | 0.000 | 0.009 | 0.000 | 0.000 | -2.152 | 0.000 | -3.162 | -14.847 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.584 | 0.000 | 0.003 | 0.000 | 0.000 | -2.088 | 0.000 | -3.289 | -22.677 |
Total Facility | 1055.032 | -719.755 | 0.000 | 0.000 | 304.698 | 416.414 | 980.287 | 793.713 | 0.000 | 25.840 | 42.713 | 0.000 | -1085.819 | 0.000 | -1302.036 | -511.087 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 07-SEP-15:15 | 0.00 | -2763.28 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3867.49 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1741.33 |
G NW APARTMENT | 25-JUN-17:25 | 0.00 | -2240.10 | 0.00 | 0.00 | 141.61 | 194.45 | 588.62 | 2864.75 | 0.00 | 140.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1689.91 |
OFFICE | 07-SEP-13:30 | 0.00 | -3457.53 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3386.61 | 0.00 | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2185.03 |
G NE APARTMENT | 02-JUL-09:45 | 0.00 | -1681.21 | 0.00 | 0.00 | 40.69 | 28.81 | 406.15 | 2299.48 | 0.00 | 270.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1364.43 |
G N1 APARTMENT | 02-JUL-19:15 | 0.00 | -1300.39 | 0.00 | 0.00 | 141.83 | 230.46 | 523.87 | 419.92 | 0.00 | 287.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -303.36 |
G N2 APARTMENT | 02-JUL-19:15 | 0.00 | -1300.65 | 0.00 | 0.00 | 141.83 | 230.46 | 523.87 | 420.33 | 0.00 | 289.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -305.27 |
G S1 APARTMENT | 05-SEP-12:30 | 0.00 | -1883.53 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3159.23 | 0.00 | 219.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1952.79 |
G S2 APARTMENT | 05-SEP-12:30 | 0.00 | -1924.29 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3158.40 | 0.00 | 219.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1911.19 |
F2 SW APARTMENT | 07-SEP-15:15 | 0.00 | -3495.33 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3852.71 | 0.00 | 23.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1001.65 |
F2 NW APARTMENT | 25-JUN-17:25 | 0.00 | -2950.22 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2814.78 | 0.00 | 202.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.70 |
F2 SE APARTMENT | 07-SEP-13:30 | 0.00 | -3245.03 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 3357.11 | 0.00 | 33.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -597.94 |
F2 NE APARTMENT | 26-JUN-17:30 | 0.00 | -2190.19 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 967.91 | 0.00 | 82.13 | 215.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 28-JUN-19:15 | 0.00 | -1693.14 | 0.00 | 0.00 | 141.83 | 230.46 | 523.87 | 479.18 | 0.00 | 241.02 | 76.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 28-JUN-19:15 | 0.00 | -1682.12 | 0.00 | 0.00 | 141.83 | 230.46 | 523.87 | 479.32 | 0.00 | 240.69 | 65.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2431.02 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3118.51 | 0.00 | 264.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1410.21 |
F2 S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2449.46 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3118.21 | 0.00 | 264.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1391.46 |
F3 SW APARTMENT | 07-SEP-15:15 | 0.00 | -3515.02 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 3846.14 | 0.00 | 27.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -979.65 |
F3 NW APARTMENT | 25-JUN-17:20 | 0.00 | -2995.11 | 0.00 | 0.00 | 141.62 | 194.45 | 588.62 | 2793.57 | 0.00 | 238.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -961.58 |
F3 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3287.19 | 0.00 | 0.00 | 40.76 | 28.81 | 406.15 | 3370.03 | 0.00 | 602.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1160.78 |
F3 NE APARTMENT | 28-JUN-19:00 | 0.00 | -2264.79 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 601.79 | 0.00 | 397.19 | 346.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1764.61 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 465.45 | 0.00 | 359.76 | 19.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1755.56 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 465.63 | 0.00 | 359.76 | 10.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2527.61 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3096.00 | 0.00 | 293.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1319.87 |
F3 S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2542.43 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3095.75 | 0.00 | 293.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1304.80 |
F4 SW APARTMENT | 02-SEP-15:00 | 0.00 | -3553.80 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3646.29 | 0.00 | 679.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1263.00 |
F4 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3022.47 | 0.00 | 0.00 | 141.58 | 194.45 | 588.62 | 2779.80 | 0.00 | 265.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -947.49 |
F4 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3306.58 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3347.21 | 0.00 | 654.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1171.08 |
F4 NE APARTMENT | 28-JUN-19:00 | 0.00 | -2306.89 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 600.30 | 0.00 | 428.59 | 358.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1806.01 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 463.20 | 0.00 | 385.40 | 37.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1790.77 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 463.38 | 0.00 | 384.65 | 23.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2561.87 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3080.12 | 0.00 | 314.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1291.23 |
F4 S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2576.13 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3079.88 | 0.00 | 314.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1276.72 |
M SW APARTMENT | 02-SEP-15:00 | 0.00 | -3614.02 | 0.00 | 0.00 | 40.76 | 50.41 | 400.26 | 3626.46 | 0.00 | 726.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1230.38 |
M NW APARTMENT | 25-JUN-17:20 | 0.00 | -3065.97 | 0.00 | 0.00 | 141.55 | 194.45 | 588.62 | 2768.70 | 0.00 | 287.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.90 |
M SE APARTMENT | 09-SEP-11:30 | 0.00 | -3357.94 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3329.41 | 0.00 | 698.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1145.28 |
M NE APARTMENT | 28-JUN-19:00 | 0.00 | -2361.60 | 0.00 | 0.00 | 141.83 | 230.46 | 547.42 | 598.34 | 0.00 | 453.82 | 389.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1852.67 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 461.20 | 0.00 | 406.44 | 65.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1837.46 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 461.39 | 0.00 | 405.64 | 50.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2598.79 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3067.29 | 0.00 | 332.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1258.64 |
M S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2612.98 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3067.05 | 0.00 | 332.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1244.21 |
F6 SW APARTMENT | 02-SEP-15:00 | 0.00 | -3599.40 | 0.00 | 0.00 | 40.76 | 50.41 | 400.26 | 3612.31 | 0.00 | 765.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1270.17 |
F6 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3033.85 | 0.00 | 0.00 | 141.48 | 194.45 | 588.62 | 2761.47 | 0.00 | 306.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -958.23 |
F6 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3334.30 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 3316.65 | 0.00 | 732.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1191.03 |
F6 NE APARTMENT | 28-JUN-19:00 | 0.00 | -2346.42 | 0.00 | 0.00 | 141.83 | 230.46 | 547.42 | 598.45 | 0.00 | 474.85 | 353.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1824.12 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 460.81 | 0.00 | 423.38 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1809.02 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 460.99 | 0.00 | 422.53 | 5.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2556.49 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3057.67 | 0.00 | 346.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1305.51 |
F6 S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2570.83 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3057.42 | 0.00 | 346.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1290.93 |
F7 SW APARTMENT | 02-SEP-15:00 | 0.00 | -3604.55 | 0.00 | 0.00 | 40.76 | 50.41 | 400.26 | 3599.84 | 0.00 | 799.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1285.97 |
F7 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3027.84 | 0.00 | 0.00 | 141.45 | 194.45 | 588.62 | 2754.84 | 0.00 | 322.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.84 |
F7 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3335.18 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 3305.36 | 0.00 | 763.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1209.27 |
F7 NE APARTMENT | 28-JUN-19:00 | 0.00 | -2351.68 | 0.00 | 0.00 | 141.83 | 230.46 | 547.42 | 597.86 | 0.00 | 492.77 | 341.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1820.30 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 460.05 | 0.00 | 438.14 | 2.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1805.29 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 460.23 | 0.00 | 437.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.89 |
F7 S1 APARTMENT | 05-SEP-12:30 | 0.00 | -2534.16 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3049.22 | 0.00 | 358.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1331.38 |
F7 S2 APARTMENT | 05-SEP-12:30 | 0.00 | -2548.74 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 3048.97 | 0.00 | 358.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1316.55 |
F8 SW APARTMENT | 02-SEP-15:00 | 0.00 | -3611.99 | 0.00 | 0.00 | 40.76 | 50.41 | 400.26 | 3588.96 | 0.00 | 828.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1296.52 |
F8 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3035.20 | 0.00 | 0.00 | 141.44 | 194.45 | 588.62 | 2748.79 | 0.00 | 336.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -975.03 |
F8 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3347.83 | 0.00 | 0.00 | 40.74 | 28.81 | 406.15 | 3295.42 | 0.00 | 791.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1214.44 |
F8 NE APARTMENT | 18-APR-15:30 | 0.00 | -2387.44 | 0.00 | 0.00 | 48.90 | 100.83 | 470.89 | 1012.34 | 0.00 | 1047.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -292.69 |
F8 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1830.00 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 459.09 | 0.00 | 451.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.04 |
F8 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1815.09 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 459.27 | 0.00 | 450.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14.21 |
F8 S1 APARTMENT | 05-SEP-12:45 | 0.00 | -2593.81 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2990.45 | 0.00 | 493.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1348.08 |
F8 S2 APARTMENT | 05-SEP-12:45 | 0.00 | -2605.90 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2990.20 | 0.00 | 493.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1335.47 |
F9 SW APARTMENT | 02-SEP-15:15 | 0.00 | -3717.21 | 0.00 | 0.00 | 48.91 | 100.83 | 470.89 | 3501.38 | 0.00 | 889.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1294.41 |
F9 NW APARTMENT | 25-JUN-17:20 | 0.00 | -3126.63 | 0.00 | 0.00 | 141.56 | 194.45 | 588.62 | 2740.99 | 0.00 | 350.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -889.79 |
F9 SE APARTMENT | 09-SEP-11:30 | 0.00 | -3416.23 | 0.00 | 0.00 | 40.76 | 28.81 | 406.15 | 3286.72 | 0.00 | 828.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.77 |
F9 NE APARTMENT | 28-JUN-18:45 | 0.00 | -2537.62 | 0.00 | 0.00 | 141.83 | 230.46 | 547.42 | 651.00 | 0.00 | 588.94 | 377.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 31-MAY-18:30 | 0.00 | -1913.84 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 456.52 | 0.00 | 464.41 | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 31-MAY-18:30 | 0.00 | -1898.81 | 0.00 | 0.00 | 141.82 | 230.46 | 547.42 | 456.70 | 0.00 | 463.43 | 58.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 05-SEP-12:45 | 0.00 | -2612.49 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2984.77 | 0.00 | 518.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1348.65 |
F9 S2 APARTMENT | 05-SEP-12:45 | 0.00 | -2628.66 | 0.00 | 0.00 | 40.75 | 28.81 | 388.49 | 2984.47 | 0.00 | 518.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1332.17 |
T SW APARTMENT | 07-SEP-14:30 | 0.00 | -4418.63 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 4021.82 | 0.00 | 90.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -184.64 |
T NW APARTMENT | 05-JUL-17:15 | 0.00 | -3690.49 | 0.00 | 0.00 | 141.82 | 194.45 | 588.62 | 2583.79 | 0.00 | 290.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -108.62 |
T SE APARTMENT | 07-SEP-13:15 | 0.00 | -4130.09 | 0.00 | 0.00 | 40.75 | 28.81 | 382.60 | 3397.53 | 0.00 | 29.85 | 250.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 28-JUN-10:00 | 0.00 | -2978.43 | 0.00 | 0.00 | 40.73 | 28.81 | 406.15 | 1981.97 | 0.00 | 527.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6.46 |
T N1 APARTMENT | 11-AUG-15:00 | 0.00 | -2293.50 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 646.83 | 0.00 | 754.75 | 400.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 11-AUG-15:00 | 0.00 | -2291.47 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 646.86 | 0.00 | 754.75 | 398.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 07-SEP-13:30 | 0.00 | -3370.53 | 0.00 | 0.00 | 39.66 | 28.81 | 382.60 | 2892.76 | 0.00 | 34.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7.82 |
T S2 APARTMENT | 07-SEP-13:30 | 0.00 | -3381.23 | 0.00 | 0.00 | 39.65 | 28.81 | 382.60 | 2892.56 | 0.00 | 34.53 | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-SEP-16:30 | 0.00 | -189588.89 | 0.00 | 0.00 | 6696.28 | 18221.75 | 47141.46 | 86105.09 | 0.00 | 47520.55 | 0.00 | 0.00 | 0.00 | 0.00 | -42.19 | -16054.05 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-DEC-08:53 | 3666.19 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1686.50 | 0.00 | -1683.97 | -801.39 |
G NW APARTMENT | 09-DEC-08:53 | 3716.01 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1717.07 | 0.00 | -1683.97 | -820.64 |
OFFICE | 09-DEC-08:53 | 3776.50 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1666.86 | 0.00 | -1683.96 | -933.95 |
G NE APARTMENT | 09-DEC-08:53 | 3699.83 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1694.95 | 0.00 | -1683.98 | -826.57 |
G N1 APARTMENT | 09-DEC-08:53 | 2323.81 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1048.00 | 0.00 | -1015.73 | -765.74 |
G N2 APARTMENT | 09-DEC-08:53 | 2323.58 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1048.00 | 0.00 | -1015.73 | -765.51 |
G S1 APARTMENT | 09-DEC-08:53 | 2262.29 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.60 | 0.00 | -1015.73 | -734.63 |
G S2 APARTMENT | 09-DEC-08:53 | 2256.71 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.72 | 0.00 | -1015.73 | -728.93 |
F2 SW APARTMENT | 09-DEC-02:00 | 4272.97 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1877.52 | 0.00 | -2577.26 | -263.60 |
F2 NW APARTMENT | 09-DEC-02:00 | 4390.92 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1917.35 | 0.00 | -2577.26 | -341.71 |
F2 SE APARTMENT | 09-DEC-02:00 | 4206.57 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1849.29 | 0.00 | -2577.26 | -225.42 |
F2 NE APARTMENT | 09-DEC-02:00 | 4371.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1887.65 | 0.00 | -2577.27 | -351.65 |
F2 N1 APARTMENT | 23-MAR-13:55 | 2813.45 | 0.00 | 0.00 | 0.00 | 46.91 | 28.81 | 382.60 | 261.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2930.81 | -602.32 |
F2 N2 APARTMENT | 23-MAR-13:55 | 2817.31 | 0.00 | 0.00 | 0.00 | 46.90 | 28.81 | 382.60 | 261.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2930.82 | -605.92 |
F2 S1 APARTMENT | 09-DEC-02:00 | 2385.86 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1128.78 | 0.00 | -1554.54 | -147.95 |
F2 S2 APARTMENT | 09-DEC-02:00 | 2381.86 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1128.87 | 0.00 | -1554.54 | -143.86 |
F3 SW APARTMENT | 09-DEC-02:00 | 4654.07 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1904.95 | 0.00 | -3052.10 | -142.43 |
F3 NW APARTMENT | 09-DEC-02:00 | 4791.63 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1947.75 | 0.00 | -3052.10 | -237.18 |
F3 SE APARTMENT | 09-DEC-02:00 | 4627.95 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1872.79 | 0.00 | -3052.10 | -148.46 |
F3 NE APARTMENT | 09-DEC-02:00 | 4770.34 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1915.62 | 0.00 | -3052.11 | -248.01 |
F3 N1 APARTMENT | 23-MAR-13:55 | 3294.52 | 0.00 | 0.00 | 0.00 | 46.81 | 28.81 | 382.60 | 253.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3430.62 | -576.00 |
F3 N2 APARTMENT | 23-MAR-13:55 | 3298.25 | 0.00 | 0.00 | 0.00 | 46.79 | 28.81 | 382.60 | 253.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3430.63 | -579.48 |
F3 S1 APARTMENT | 09-DEC-02:00 | 2561.60 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1144.77 | 0.00 | -1840.95 | -21.29 |
F3 S2 APARTMENT | 09-DEC-02:00 | 2560.96 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1144.78 | 0.00 | -1840.95 | -20.64 |
F4 SW APARTMENT | 09-DEC-02:00 | 5003.10 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1921.11 | 0.00 | -3412.30 | -115.09 |
F4 NW APARTMENT | 09-DEC-02:00 | 5146.79 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1965.67 | 0.00 | -3412.31 | -214.23 |
F4 SE APARTMENT | 09-DEC-02:00 | 4983.44 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1887.35 | 0.00 | -3412.31 | -129.19 |
F4 NE APARTMENT | 09-DEC-02:00 | 5124.47 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1932.23 | 0.00 | -3412.32 | -225.34 |
F4 N1 APARTMENT | 23-MAR-14:10 | 3565.00 | 0.00 | 0.00 | 0.00 | 46.71 | 50.41 | 400.26 | 243.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3673.98 | -631.81 |
F4 N2 APARTMENT | 23-MAR-14:10 | 3567.13 | 0.00 | 0.00 | 0.00 | 46.70 | 50.41 | 400.26 | 243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3673.99 | -633.75 |
F4 S1 APARTMENT | 09-DEC-02:00 | 2757.31 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 | -1154.13 | 0.00 | -2058.21 | 0.00 |
F4 S2 APARTMENT | 09-DEC-02:00 | 2757.56 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 9.37 | 0.00 | -1154.13 | 0.00 | -2058.21 | 0.00 |
M SW APARTMENT | 09-DEC-02:00 | 5281.97 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1933.52 | 0.00 | -3709.31 | -84.55 |
M NW APARTMENT | 09-DEC-02:00 | 5425.59 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1979.29 | 0.00 | -3709.32 | -182.39 |
M SE APARTMENT | 09-DEC-02:00 | 5262.74 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1898.86 | 0.00 | -3709.32 | -99.98 |
M NE APARTMENT | 09-DEC-02:00 | 5402.57 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1945.00 | 0.00 | -3709.33 | -193.66 |
M N1 APARTMENT | 23-MAR-14:10 | 3855.43 | 0.00 | 0.00 | 0.00 | 46.70 | 50.41 | 400.26 | 240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3986.68 | -606.39 |
M N2 APARTMENT | 23-MAR-14:10 | 3857.31 | 0.00 | 0.00 | 0.00 | 46.69 | 50.41 | 400.26 | 240.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3986.68 | -608.10 |
M S1 APARTMENT | 09-DEC-02:00 | 2914.64 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 38.67 | 0.00 | -1161.35 | 0.00 | -2237.36 | 0.00 |
M S2 APARTMENT | 09-DEC-02:00 | 2915.07 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 38.22 | 0.00 | -1161.34 | 0.00 | -2237.36 | 0.00 |
F6 SW APARTMENT | 09-DEC-02:00 | 5585.35 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1941.21 | 0.00 | -3965.34 | -124.20 |
F6 NW APARTMENT | 09-DEC-02:00 | 5728.10 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1987.95 | 0.00 | -3965.35 | -220.21 |
F6 SE APARTMENT | 09-DEC-02:00 | 5565.64 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.99 | 0.00 | -3965.35 | -139.71 |
F6 NE APARTMENT | 09-DEC-02:00 | 5704.51 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1953.10 | 0.00 | -3965.36 | -231.46 |
F6 N1 APARTMENT | 23-MAR-14:10 | 4036.34 | 0.00 | 0.00 | 0.00 | 46.98 | 50.41 | 400.26 | 240.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4259.83 | -515.14 |
F6 N2 APARTMENT | 23-MAR-14:10 | 4038.92 | 0.00 | 0.00 | 0.00 | 46.97 | 50.41 | 400.26 | 240.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4259.84 | -517.51 |
F6 S1 APARTMENT | 23-MAR-14:10 | 3166.43 | 0.00 | 0.00 | 0.00 | 41.22 | 50.41 | 400.26 | 2081.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4312.45 | -1427.35 |
F6 S2 APARTMENT | 23-MAR-14:10 | 3152.30 | 0.00 | 0.00 | 0.00 | 41.19 | 50.41 | 400.26 | 2081.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4313.18 | -1412.15 |
F7 SW APARTMENT | 09-DEC-02:00 | 5838.75 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1948.10 | 0.00 | -4192.27 | -143.79 |
F7 NW APARTMENT | 09-DEC-02:00 | 5978.28 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1995.60 | 0.00 | -4192.28 | -235.80 |
F7 SE APARTMENT | 09-DEC-02:00 | 5818.54 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1912.45 | 0.00 | -4192.28 | -159.22 |
F7 NE APARTMENT | 09-DEC-02:00 | 5954.25 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1960.33 | 0.00 | -4192.29 | -247.04 |
F7 N1 APARTMENT | 23-MAR-14:10 | 4220.76 | 0.00 | 0.00 | 0.00 | 47.15 | 50.41 | 400.26 | 240.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4505.38 | -454.08 |
F7 N2 APARTMENT | 23-MAR-14:10 | 4222.40 | 0.00 | 0.00 | 0.00 | 47.14 | 50.41 | 400.26 | 240.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4505.39 | -455.53 |
F7 S1 APARTMENT | 23-MAR-14:10 | 3805.36 | 0.00 | 0.00 | 0.00 | 41.57 | 50.41 | 400.26 | 2076.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4547.08 | -1827.26 |
F7 S2 APARTMENT | 23-MAR-14:10 | 3790.86 | 0.00 | 0.00 | 0.00 | 41.54 | 50.41 | 400.26 | 2076.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4547.79 | -1811.71 |
F8 SW APARTMENT | 09-DEC-02:00 | 6078.47 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1953.66 | 0.00 | -4397.29 | -172.92 |
F8 NW APARTMENT | 09-DEC-02:00 | 6211.53 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2001.87 | 0.00 | -4397.30 | -257.77 |
F8 SE APARTMENT | 09-DEC-02:00 | 6057.71 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1917.71 | 0.00 | -4397.30 | -188.11 |
F8 NE APARTMENT | 09-DEC-02:00 | 6187.09 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1966.28 | 0.00 | -4397.30 | -268.91 |
F8 N1 APARTMENT | 23-MAR-14:10 | 4396.20 | 0.00 | 0.00 | 0.00 | 47.29 | 50.41 | 400.26 | 240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4730.12 | -404.82 |
F8 N2 APARTMENT | 23-MAR-14:10 | 4397.15 | 0.00 | 0.00 | 0.00 | 47.28 | 50.41 | 400.26 | 240.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4730.13 | -405.59 |
F8 S1 APARTMENT | 23-MAR-14:10 | 4371.87 | 0.00 | 0.00 | 0.00 | 41.89 | 50.41 | 400.26 | 2072.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4762.18 | -2175.18 |
F8 S2 APARTMENT | 23-MAR-14:10 | 4360.09 | 0.00 | 0.00 | 0.00 | 41.86 | 50.41 | 400.26 | 2072.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4762.77 | -2162.53 |
F9 SW APARTMENT | 09-DEC-02:00 | 6445.41 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1954.00 | 0.00 | -4585.12 | -351.70 |
F9 NW APARTMENT | 09-DEC-02:00 | 6558.05 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.02 | 0.00 | -4585.12 | -415.30 |
F9 SE APARTMENT | 09-DEC-02:00 | 6422.85 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1917.94 | 0.00 | -4585.13 | -365.18 |
F9 NE APARTMENT | 09-DEC-02:00 | 6532.36 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1967.29 | 0.00 | -4585.13 | -425.34 |
F9 N1 APARTMENT | 23-MAR-14:10 | 4572.75 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 241.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4938.54 | -374.12 |
F9 N2 APARTMENT | 23-MAR-14:10 | 4569.74 | 0.00 | 0.00 | 0.00 | 47.42 | 50.41 | 400.26 | 241.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4938.54 | -370.93 |
F9 S1 APARTMENT | 23-MAR-14:10 | 4982.33 | 0.00 | 0.00 | 0.00 | 42.30 | 50.41 | 400.26 | 2071.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4959.54 | -2587.46 |
F9 S2 APARTMENT | 23-MAR-14:10 | 4968.01 | 0.00 | 0.00 | 0.00 | 42.27 | 50.41 | 400.26 | 2071.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4960.21 | -2572.11 |
T SW APARTMENT | 09-DEC-02:00 | 7498.37 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1915.65 | 0.00 | -4758.66 | -1269.47 |
T NW APARTMENT | 09-DEC-02:00 | 7572.73 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1963.29 | 0.00 | -4758.67 | -1296.18 |
T SE APARTMENT | 09-DEC-02:00 | 7471.06 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1880.76 | 0.00 | -4758.67 | -1277.05 |
T NE APARTMENT | 09-DEC-02:00 | 7544.41 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1928.57 | 0.00 | -4758.67 | -1302.57 |
T N1 APARTMENT | 09-DEC-02:00 | 4837.70 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1199.14 | 0.00 | -2870.43 | -1213.54 |
T N2 APARTMENT | 09-DEC-02:00 | 4837.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1199.15 | 0.00 | -2870.42 | -1213.05 |
T S1 APARTMENT | 09-DEC-02:00 | 4750.53 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1150.17 | 0.00 | -2870.41 | -1175.36 |
T S2 APARTMENT | 09-DEC-02:00 | 4750.21 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1150.18 | 0.00 | -2870.41 | -1175.03 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-DEC-02:00 | 345596.79 | 0.00 | 0.00 | 0.00 | 14983.85 | 7980.64 | 19245.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -126478.19 | 0.00 | -239681.33 | -21647.01 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Sec1.1A-General InformationData | |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 123.25 |
Number of hours cooling loads not met | 73.50 |
Number of hours not met | 196.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 7980.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.36 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 425.54 | 178038.21 | 1560.29 | 319979.07 | 0.00 | 0.00 |
Space Cooling | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.66 | 1805.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 606.47 | 19230.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1295.71 | 88159.50 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 20217.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3134.31 | 2856.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3134.31 |
Natural Gas | 0.00 | 2856.00 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 5990.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 54.30 |
Space Cooling | 37.89 |
Fans-Interior | 77.39 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 32.91 |
Subtotal | 399.96 |
Natural Gas [MJ/m2] | |
Space Heating | 199.11 |
Service Water Heating | 165.34 |
Miscellaneous | 0.00 |
Subtotal | 364.45 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.95 |
Space Heating | 33.15 |
Space Cooling | 4.96 |
Fans-Interior | 10.12 |
Service Water Heating | 21.63 |
Receptacle Equipment | 18.88 |
Miscellaneous | 4.31 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.219053 |
G NW APARTMENT DIRECT AIR | 0.204997 |
OFFICE DIRECT AIR | 0.294756 |
G NE APARTMENT DIRECT AIR | 0.174036 |
G N1 APARTMENT DIRECT AIR | 0.116007 |
G N2 APARTMENT DIRECT AIR | 0.116005 |
G S1 APARTMENT DIRECT AIR | 0.133628 |
G S2 APARTMENT DIRECT AIR | 0.138923 |
F2 SW APARTMENT DIRECT AIR | 0.288759 |
F2 NW APARTMENT DIRECT AIR | 0.267387 |
F2 SE APARTMENT DIRECT AIR | 0.270005 |
F2 NE APARTMENT DIRECT AIR | 0.202129 |
F2 N1 APARTMENT DIRECT AIR | 0.144185 |
F2 N2 APARTMENT DIRECT AIR | 0.142654 |
F2 S1 APARTMENT DIRECT AIR | 0.181395 |
F2 S2 APARTMENT DIRECT AIR | 0.183568 |
F3 SW APARTMENT DIRECT AIR | 0.289899 |
F3 NW APARTMENT DIRECT AIR | 0.269888 |
F3 SE APARTMENT DIRECT AIR | 0.256175 |
F3 NE APARTMENT DIRECT AIR | 0.205876 |
F3 N1 APARTMENT DIRECT AIR | 0.148482 |
F3 N2 APARTMENT DIRECT AIR | 0.146970 |
F3 S1 APARTMENT DIRECT AIR | 0.185209 |
F3 S2 APARTMENT DIRECT AIR | 0.186363 |
F4 SW APARTMENT DIRECT AIR | 0.290536 |
F4 NW APARTMENT DIRECT AIR | 0.270936 |
F4 SE APARTMENT DIRECT AIR | 0.255868 |
F4 NE APARTMENT DIRECT AIR | 0.206887 |
F4 N1 APARTMENT DIRECT AIR | 0.150072 |
F4 N2 APARTMENT DIRECT AIR | 0.148569 |
F4 S1 APARTMENT DIRECT AIR | 0.186440 |
F4 S2 APARTMENT DIRECT AIR | 0.187449 |
M SW APARTMENT DIRECT AIR | 0.293379 |
M NW APARTMENT DIRECT AIR | 0.274160 |
M SE APARTMENT DIRECT AIR | 0.259017 |
M NE APARTMENT DIRECT AIR | 0.209964 |
M N1 APARTMENT DIRECT AIR | 0.153491 |
M N2 APARTMENT DIRECT AIR | 0.151995 |
M S1 APARTMENT DIRECT AIR | 0.189592 |
M S2 APARTMENT DIRECT AIR | 0.190580 |
F6 SW APARTMENT DIRECT AIR | 0.289711 |
F6 NW APARTMENT DIRECT AIR | 0.270620 |
F6 SE APARTMENT DIRECT AIR | 0.255802 |
F6 NE APARTMENT DIRECT AIR | 0.206414 |
F6 N1 APARTMENT DIRECT AIR | 0.150406 |
F6 N2 APARTMENT DIRECT AIR | 0.148924 |
F6 S1 APARTMENT DIRECT AIR | 0.186271 |
F6 S2 APARTMENT DIRECT AIR | 0.187256 |
F7 SW APARTMENT DIRECT AIR | 0.288466 |
F7 NW APARTMENT DIRECT AIR | 0.269571 |
F7 SE APARTMENT DIRECT AIR | 0.254941 |
F7 NE APARTMENT DIRECT AIR | 0.207200 |
F7 N1 APARTMENT DIRECT AIR | 0.149632 |
F7 N2 APARTMENT DIRECT AIR | 0.148160 |
F7 S1 APARTMENT DIRECT AIR | 0.185274 |
F7 S2 APARTMENT DIRECT AIR | 0.186257 |
F8 SW APARTMENT DIRECT AIR | 0.288570 |
F8 NW APARTMENT DIRECT AIR | 0.269850 |
F8 SE APARTMENT DIRECT AIR | 0.255301 |
F8 NE APARTMENT DIRECT AIR | 0.213252 |
F8 N1 APARTMENT DIRECT AIR | 0.150149 |
F8 N2 APARTMENT DIRECT AIR | 0.148687 |
F8 S1 APARTMENT DIRECT AIR | 0.185525 |
F8 S2 APARTMENT DIRECT AIR | 0.186510 |
F9 SW APARTMENT DIRECT AIR | 0.297135 |
F9 NW APARTMENT DIRECT AIR | 0.278110 |
F9 SE APARTMENT DIRECT AIR | 0.261390 |
F9 NE APARTMENT DIRECT AIR | 0.227266 |
F9 N1 APARTMENT DIRECT AIR | 0.157415 |
F9 N2 APARTMENT DIRECT AIR | 0.155934 |
F9 S1 APARTMENT DIRECT AIR | 0.190564 |
F9 S2 APARTMENT DIRECT AIR | 0.191614 |
T SW APARTMENT DIRECT AIR | 0.349408 |
T NW APARTMENT DIRECT AIR | 0.322882 |
T SE APARTMENT DIRECT AIR | 0.314267 |
T NE APARTMENT DIRECT AIR | 0.273755 |
T N1 APARTMENT DIRECT AIR | 0.185708 |
T N2 APARTMENT DIRECT AIR | 0.185684 |
T S1 APARTMENT DIRECT AIR | 0.254328 |
T S2 APARTMENT DIRECT AIR | 0.255299 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.219053 |
AIRLOOP G NW MAIN BRANCH | 0.204997 |
AIRLOOP OFFICE MAIN BRANCH | 0.294756 |
AIRLOOP G NE MAIN BRANCH | 0.174036 |
AIRLOOP G N1 MAIN BRANCH | 0.116007 |
AIRLOOP G N2 MAIN BRANCH | 0.116005 |
AIRLOOP G S1 MAIN BRANCH | 0.133628 |
AIRLOOP G S2 MAIN BRANCH | 0.138923 |
AIRLOOP F2 SW MAIN BRANCH | 0.288759 |
AIRLOOP F2 NW MAIN BRANCH | 0.267387 |
AIRLOOP F2 SE MAIN BRANCH | 0.270005 |
AIRLOOP F2 NE MAIN BRANCH | 0.202129 |
AIRLOOP F2 N1 MAIN BRANCH | 0.144185 |
AIRLOOP F2 N2 MAIN BRANCH | 0.142654 |
AIRLOOP F2 S1 MAIN BRANCH | 0.181395 |
AIRLOOP F2 S2 MAIN BRANCH | 0.183568 |
AIRLOOP F3 SW MAIN BRANCH | 0.289899 |
AIRLOOP F3 NW MAIN BRANCH | 0.269888 |
AIRLOOP F3 SE MAIN BRANCH | 0.256175 |
AIRLOOP F3 NE MAIN BRANCH | 0.205876 |
AIRLOOP F3 N1 MAIN BRANCH | 0.148482 |
AIRLOOP F3 N2 MAIN BRANCH | 0.146970 |
AIRLOOP F3 S1 MAIN BRANCH | 0.185209 |
AIRLOOP F3 S2 MAIN BRANCH | 0.186363 |
AIRLOOP F4 SW MAIN BRANCH | 0.290536 |
AIRLOOP F4 NW MAIN BRANCH | 0.270936 |
AIRLOOP F4 SE MAIN BRANCH | 0.255868 |
AIRLOOP F4 NE MAIN BRANCH | 0.206887 |
AIRLOOP F4 N1 MAIN BRANCH | 0.150072 |
AIRLOOP F4 N2 MAIN BRANCH | 0.148569 |
AIRLOOP F4 S1 MAIN BRANCH | 0.186440 |
AIRLOOP F4 S2 MAIN BRANCH | 0.187449 |
AIRLOOP M SW MAIN BRANCH | 0.293379 |
AIRLOOP M NW MAIN BRANCH | 0.274160 |
AIRLOOP M SE MAIN BRANCH | 0.259017 |
AIRLOOP M NE MAIN BRANCH | 0.209964 |
AIRLOOP M N1 MAIN BRANCH | 0.153491 |
AIRLOOP M N2 MAIN BRANCH | 0.151995 |
AIRLOOP M S1 MAIN BRANCH | 0.189592 |
AIRLOOP M S2 MAIN BRANCH | 0.190580 |
AIRLOOP F6 SW MAIN BRANCH | 0.289711 |
AIRLOOP F6 NW MAIN BRANCH | 0.270620 |
AIRLOOP F6 SE MAIN BRANCH | 0.255802 |
AIRLOOP F6 NE MAIN BRANCH | 0.206414 |
AIRLOOP F6 N1 MAIN BRANCH | 0.150406 |
AIRLOOP F6 N2 MAIN BRANCH | 0.148924 |
AIRLOOP F6 S1 MAIN BRANCH | 0.186271 |
AIRLOOP F6 S2 MAIN BRANCH | 0.187256 |
AIRLOOP F7 SW MAIN BRANCH | 0.288466 |
AIRLOOP F7 NW MAIN BRANCH | 0.269571 |
AIRLOOP F7 SE MAIN BRANCH | 0.254941 |
AIRLOOP F7 NE MAIN BRANCH | 0.207200 |
AIRLOOP F7 N1 MAIN BRANCH | 0.149632 |
AIRLOOP F7 N2 MAIN BRANCH | 0.148160 |
AIRLOOP F7 S1 MAIN BRANCH | 0.185274 |
AIRLOOP F7 S2 MAIN BRANCH | 0.186257 |
AIRLOOP F8 SW MAIN BRANCH | 0.288570 |
AIRLOOP F8 NW MAIN BRANCH | 0.269850 |
AIRLOOP F8 SE MAIN BRANCH | 0.255301 |
AIRLOOP F8 NE MAIN BRANCH | 0.213252 |
AIRLOOP F8 N1 MAIN BRANCH | 0.150149 |
AIRLOOP F8 N2 MAIN BRANCH | 0.148687 |
AIRLOOP F8 S1 MAIN BRANCH | 0.185525 |
AIRLOOP F8 S2 MAIN BRANCH | 0.186510 |
AIRLOOP F9 SW MAIN BRANCH | 0.297135 |
AIRLOOP F9 NW MAIN BRANCH | 0.278110 |
AIRLOOP F9 SE MAIN BRANCH | 0.261390 |
AIRLOOP F9 NE MAIN BRANCH | 0.227266 |
AIRLOOP F9 N1 MAIN BRANCH | 0.157415 |
AIRLOOP F9 N2 MAIN BRANCH | 0.155934 |
AIRLOOP F9 S1 MAIN BRANCH | 0.190564 |
AIRLOOP F9 S2 MAIN BRANCH | 0.191614 |
AIRLOOP T SW MAIN BRANCH | 0.349408 |
AIRLOOP T NW MAIN BRANCH | 0.322882 |
AIRLOOP T SE MAIN BRANCH | 0.314267 |
AIRLOOP T NE MAIN BRANCH | 0.273755 |
AIRLOOP T N1 MAIN BRANCH | 0.185708 |
AIRLOOP T N2 MAIN BRANCH | 0.185684 |
AIRLOOP T S1 MAIN BRANCH | 0.254328 |
AIRLOOP T S2 MAIN BRANCH | 0.255299 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.219053 |
AIRLOOP G NW | 0.204997 |
AIRLOOP OFFICE | 0.294756 |
AIRLOOP G NE | 0.174036 |
AIRLOOP G N1 | 0.116007 |
AIRLOOP G N2 | 0.116005 |
AIRLOOP G S1 | 0.133628 |
AIRLOOP G S2 | 0.138923 |
AIRLOOP F2 SW | 0.288759 |
AIRLOOP F2 NW | 0.267387 |
AIRLOOP F2 SE | 0.270005 |
AIRLOOP F2 NE | 0.202129 |
AIRLOOP F2 N1 | 0.144185 |
AIRLOOP F2 N2 | 0.142654 |
AIRLOOP F2 S1 | 0.181395 |
AIRLOOP F2 S2 | 0.183568 |
AIRLOOP F3 SW | 0.289899 |
AIRLOOP F3 NW | 0.269888 |
AIRLOOP F3 SE | 0.256175 |
AIRLOOP F3 NE | 0.205876 |
AIRLOOP F3 N1 | 0.148482 |
AIRLOOP F3 N2 | 0.146970 |
AIRLOOP F3 S1 | 0.185209 |
AIRLOOP F3 S2 | 0.186363 |
AIRLOOP F4 SW | 0.290536 |
AIRLOOP F4 NW | 0.270936 |
AIRLOOP F4 SE | 0.255868 |
AIRLOOP F4 NE | 0.206887 |
AIRLOOP F4 N1 | 0.150072 |
AIRLOOP F4 N2 | 0.148569 |
AIRLOOP F4 S1 | 0.186440 |
AIRLOOP F4 S2 | 0.187449 |
AIRLOOP M SW | 0.293379 |
AIRLOOP M NW | 0.274160 |
AIRLOOP M SE | 0.259017 |
AIRLOOP M NE | 0.209964 |
AIRLOOP M N1 | 0.153491 |
AIRLOOP M N2 | 0.151995 |
AIRLOOP M S1 | 0.189592 |
AIRLOOP M S2 | 0.190580 |
AIRLOOP F6 SW | 0.289711 |
AIRLOOP F6 NW | 0.270620 |
AIRLOOP F6 SE | 0.255802 |
AIRLOOP F6 NE | 0.206414 |
AIRLOOP F6 N1 | 0.150406 |
AIRLOOP F6 N2 | 0.148924 |
AIRLOOP F6 S1 | 0.186271 |
AIRLOOP F6 S2 | 0.187256 |
AIRLOOP F7 SW | 0.288466 |
AIRLOOP F7 NW | 0.269571 |
AIRLOOP F7 SE | 0.254941 |
AIRLOOP F7 NE | 0.207200 |
AIRLOOP F7 N1 | 0.149632 |
AIRLOOP F7 N2 | 0.148160 |
AIRLOOP F7 S1 | 0.185274 |
AIRLOOP F7 S2 | 0.186257 |
AIRLOOP F8 SW | 0.288570 |
AIRLOOP F8 NW | 0.269850 |
AIRLOOP F8 SE | 0.255301 |
AIRLOOP F8 NE | 0.213252 |
AIRLOOP F8 N1 | 0.150149 |
AIRLOOP F8 N2 | 0.148687 |
AIRLOOP F8 S1 | 0.185525 |
AIRLOOP F8 S2 | 0.186510 |
AIRLOOP F9 SW | 0.297135 |
AIRLOOP F9 NW | 0.278110 |
AIRLOOP F9 SE | 0.261390 |
AIRLOOP F9 NE | 0.227266 |
AIRLOOP F9 N1 | 0.157415 |
AIRLOOP F9 N2 | 0.155934 |
AIRLOOP F9 S1 | 0.190564 |
AIRLOOP F9 S2 | 0.191614 |
AIRLOOP T SW | 0.349408 |
AIRLOOP T NW | 0.322882 |
AIRLOOP T SE | 0.314267 |
AIRLOOP T NE | 0.273755 |
AIRLOOP T N1 | 0.185708 |
AIRLOOP T N2 | 0.185684 |
AIRLOOP T S1 | 0.254328 |
AIRLOOP T S2 | 0.255299 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.219053 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.204997 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.294756 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.174036 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.116007 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.116005 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.133628 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.138923 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.288759 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.267387 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.270005 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.202129 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.144185 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.142654 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.181395 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.183568 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.289899 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.269888 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.256175 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.205876 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.148482 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.146970 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.185209 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.186363 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.290536 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.270936 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.255868 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.206887 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.150072 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.148569 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.186440 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.187449 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.293379 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.274160 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.259017 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.209964 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.153491 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.151995 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.189592 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.190580 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.289711 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.270620 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.255802 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.206414 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.150406 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.148924 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.186271 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.187256 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.288466 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.269571 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.254941 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.207200 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.149632 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.148160 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.185274 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.186257 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.288570 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.269850 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.255301 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.213252 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.150149 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.148687 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.185525 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.186510 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.297135 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.278110 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.261390 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.227266 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.157415 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.155934 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.190564 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.191614 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.349408 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.322882 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.314267 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.273755 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.185708 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.185684 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.254328 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.255299 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.219053 | 3887.38 | 2478.79 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.204997 | 3684.09 | 2331.29 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.294756 | 5271.71 | 3365.13 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.174036 | 3354.42 | 2048.68 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.116007 | 2420.09 | 1430.07 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.116005 | 2432.99 | 1434.73 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.133628 | 2659.02 | 1616.75 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.138923 | 2733.18 | 1670.03 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.288759 | 4950.17 | 3209.82 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.267387 | 4645.28 | 2987.93 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.270005 | 4730.04 | 3042.65 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.202129 | 3696.78 | 2314.54 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.144185 | 2787.43 | 1699.73 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.142654 | 2765.36 | 1684.21 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.181395 | 3381.17 | 2114.73 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.183568 | 3411.40 | 2136.63 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.289899 | 5022.00 | 3237.24 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.269888 | 4735.20 | 3029.07 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.256175 | 4591.56 | 2918.47 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.205876 | 3800.25 | 2367.74 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.148482 | 2877.67 | 1752.30 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.146970 | 2855.82 | 1736.98 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.185209 | 3466.03 | 2162.69 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.186363 | 3482.07 | 2174.30 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.290536 | 5072.40 | 3255.58 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.270936 | 4798.67 | 3056.01 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.255868 | 4627.16 | 2927.04 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.206887 | 3852.08 | 2389.44 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.150072 | 2921.93 | 1775.25 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.148569 | 2900.12 | 1760.00 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.186440 | 3506.82 | 2182.20 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.187449 | 3520.88 | 2192.37 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.293379 | 5145.80 | 3294.04 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.274160 | 4876.88 | 3098.28 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.259017 | 4703.77 | 2968.46 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.209964 | 3926.14 | 2429.91 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.153491 | 2988.53 | 1815.43 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.151995 | 2966.79 | 1800.24 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.189592 | 3570.36 | 2219.88 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.190580 | 3584.12 | 2229.82 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.289711 | 5122.82 | 3265.17 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.270620 | 4855.04 | 3070.67 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.255802 | 4685.66 | 2943.96 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.206414 | 3900.89 | 2401.87 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.150406 | 2958.72 | 1789.00 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.148924 | 2937.04 | 1773.93 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.186271 | 3539.64 | 2191.19 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.187256 | 3553.40 | 2201.10 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.288466 | 5130.10 | 3259.80 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.269571 | 4864.54 | 3067.25 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.254941 | 4697.22 | 2942.33 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.207200 | 3943.14 | 2419.70 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.149632 | 2960.23 | 1785.33 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.148160 | 2938.61 | 1770.34 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.185274 | 3539.62 | 2185.41 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.186257 | 3553.39 | 2195.31 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.288570 | 5153.68 | 3267.35 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.269850 | 4890.11 | 3076.52 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.255301 | 4723.47 | 2952.34 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.213252 | 4078.04 | 2496.60 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.150149 | 2979.08 | 1794.29 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.148687 | 2957.57 | 1779.41 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.185525 | 3555.76 | 2191.82 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.186510 | 3569.57 | 2201.74 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.297135 | 5294.95 | 3360.16 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.278110 | 5026.99 | 3166.19 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.261390 | 4832.24 | 3021.46 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.227266 | 4358.30 | 2666.36 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.157415 | 3095.33 | 1871.39 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.155934 | 3073.58 | 1856.30 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.190564 | 3641.25 | 2247.73 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.191614 | 3654.08 | 2257.14 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.349408 | 6081.21 | 3914.54 | 0.000133 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.322882 | 5681.31 | 3629.45 | 0.000124 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.314267 | 5595.00 | 3561.57 | 0.000122 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.273755 | 5069.94 | 3154.25 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.185708 | 3532.95 | 2171.46 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.185684 | 3604.80 | 2209.24 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.254328 | 4548.17 | 2895.34 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.255299 | 4561.52 | 2905.10 | 0.000100 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.219053 | 0.219053 | 0.219053 | 0.219053 | 3887.38 | 3887.38 | 5102.65 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.204997 | 0.204997 | 0.204997 | 0.204997 | 3684.09 | 3684.09 | 5111.44 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.294756 | 0.294756 | 0.294756 | 0.294756 | 5271.71 | 5271.71 | 6247.01 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.174036 | 0.174036 | 0.174036 | 0.174036 | 3354.42 | 3354.42 | 5110.71 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.116007 | 0.116007 | 0.116007 | 0.116007 | 2420.09 | 2420.09 | 3884.95 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.116005 | 0.116005 | 0.116005 | 0.116005 | 2432.99 | 2432.99 | 3884.92 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.133628 | 0.133628 | 0.133628 | 0.133628 | 2659.02 | 2659.02 | 3873.60 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.138923 | 0.138923 | 0.138923 | 0.138923 | 2733.18 | 2733.18 | 3882.02 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.288759 | 0.288759 | 0.288759 | 0.288759 | 4950.17 | 4950.17 | 5139.56 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.267387 | 0.267387 | 0.267387 | 0.267387 | 4645.28 | 4645.28 | 5150.53 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.270005 | 0.270005 | 0.270005 | 0.270005 | 4730.04 | 4730.04 | 5155.88 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.202129 | 0.202129 | 0.202129 | 0.202129 | 3696.78 | 3696.78 | 5142.56 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.144185 | 0.144185 | 0.144185 | 0.144185 | 2787.43 | 2787.43 | 3623.99 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.142654 | 0.142654 | 0.142654 | 0.142654 | 2765.36 | 2765.36 | 3623.82 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.181395 | 0.181395 | 0.181395 | 0.181395 | 3381.17 | 3381.17 | 3615.94 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.183568 | 0.183568 | 0.183568 | 0.183568 | 3411.40 | 3411.40 | 3617.25 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.289899 | 0.289899 | 0.289899 | 0.289899 | 5022.00 | 5022.00 | 5245.52 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.269888 | 0.269888 | 0.269888 | 0.269888 | 4735.20 | 4735.20 | 5265.90 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.256175 | 0.256175 | 0.256175 | 0.256175 | 4591.56 | 4591.56 | 5235.64 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.205876 | 0.205876 | 0.205876 | 0.205876 | 3800.25 | 3800.25 | 5253.60 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.148482 | 0.148482 | 0.148482 | 0.148482 | 2877.67 | 2877.67 | 3647.19 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.146970 | 0.146970 | 0.146970 | 0.146970 | 2855.82 | 2855.82 | 3646.93 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.185209 | 0.185209 | 0.185209 | 0.185209 | 3466.03 | 3466.03 | 3627.68 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.186363 | 0.186363 | 0.186363 | 0.186363 | 3482.07 | 3482.07 | 3627.62 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.290536 | 0.290536 | 0.290536 | 0.290536 | 5072.40 | 5072.40 | 5396.09 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.270936 | 0.270936 | 0.270936 | 0.270936 | 4798.67 | 4798.67 | 5421.91 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.255868 | 0.255868 | 0.255868 | 0.255868 | 4627.16 | 4627.16 | 5381.03 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.206887 | 0.206887 | 0.206887 | 0.206887 | 3852.08 | 3852.08 | 5406.62 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.150072 | 0.150072 | 0.150072 | 0.150072 | 2921.93 | 2921.93 | 3730.27 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.148569 | 0.148569 | 0.148569 | 0.148569 | 2900.12 | 2900.12 | 3729.94 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.186440 | 0.186440 | 0.186440 | 0.186440 | 3506.82 | 3506.82 | 3704.95 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.187449 | 0.187449 | 0.187449 | 0.187449 | 3520.88 | 3520.88 | 3704.64 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.293379 | 0.293379 | 0.293379 | 0.293379 | 5145.80 | 5145.80 | 5505.93 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.274160 | 0.274160 | 0.274160 | 0.274160 | 4876.88 | 4876.88 | 5534.21 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.259017 | 0.259017 | 0.259017 | 0.259017 | 4703.77 | 4703.77 | 5488.42 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.209964 | 0.209964 | 0.209964 | 0.209964 | 3926.14 | 3926.14 | 5516.70 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.153491 | 0.153491 | 0.153491 | 0.153491 | 2988.53 | 2988.53 | 3784.49 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.151995 | 0.151995 | 0.151995 | 0.151995 | 2966.79 | 2966.79 | 3784.11 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.189592 | 0.189592 | 0.189592 | 0.189592 | 3570.36 | 3570.36 | 3756.57 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.190580 | 0.190580 | 0.190580 | 0.190580 | 3584.12 | 3584.12 | 3756.19 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.289711 | 0.289711 | 0.289711 | 0.289711 | 5122.82 | 5122.82 | 5671.96 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.270620 | 0.270620 | 0.270620 | 0.270620 | 4855.04 | 4855.04 | 5704.06 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.255802 | 0.255802 | 0.255802 | 0.255802 | 4685.66 | 4685.66 | 5652.65 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.206414 | 0.206414 | 0.206414 | 0.206414 | 3900.89 | 3900.89 | 5684.76 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.150406 | 0.150406 | 0.150406 | 0.150406 | 2958.72 | 2958.72 | 3902.53 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.148924 | 0.148924 | 0.148924 | 0.148924 | 2937.04 | 2937.04 | 3902.11 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.186271 | 0.186271 | 0.186271 | 0.186271 | 3539.64 | 3539.64 | 3870.75 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.187256 | 0.187256 | 0.187256 | 0.187256 | 3553.40 | 3553.40 | 3870.32 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.288466 | 0.288466 | 0.288466 | 0.288466 | 5130.10 | 5130.10 | 5798.62 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.269571 | 0.269571 | 0.269571 | 0.269571 | 4864.54 | 4864.54 | 5832.74 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.254941 | 0.254941 | 0.254941 | 0.254941 | 4697.22 | 4697.22 | 5777.85 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.207200 | 0.207200 | 0.207200 | 0.207200 | 3943.14 | 3943.14 | 5811.98 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.149632 | 0.149632 | 0.149632 | 0.149632 | 2960.23 | 2960.23 | 3986.95 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.148160 | 0.148160 | 0.148160 | 0.148160 | 2938.61 | 2938.61 | 3986.49 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.185274 | 0.185274 | 0.185274 | 0.185274 | 3539.62 | 3539.62 | 3953.13 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.186257 | 0.186257 | 0.186257 | 0.186257 | 3553.39 | 3553.39 | 3952.68 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.288570 | 0.288570 | 0.288570 | 0.288570 | 5153.68 | 5153.68 | 5926.49 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.269850 | 0.269850 | 0.269850 | 0.269850 | 4890.11 | 4890.11 | 5961.88 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.255301 | 0.255301 | 0.255301 | 0.255301 | 4723.47 | 4723.47 | 5904.48 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.213252 | 0.213252 | 0.213252 | 0.213252 | 4078.04 | 4078.04 | 5939.88 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.150149 | 0.150149 | 0.150149 | 0.150149 | 2979.08 | 2979.08 | 4076.71 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.148687 | 0.148687 | 0.148687 | 0.148687 | 2957.57 | 2957.57 | 4076.23 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.185525 | 0.185525 | 0.185525 | 0.185525 | 3555.76 | 3555.76 | 4041.61 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.186510 | 0.186510 | 0.186510 | 0.186510 | 3569.57 | 3569.57 | 4041.14 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.297135 | 0.297135 | 0.297135 | 0.297135 | 5294.95 | 5294.95 | 6226.38 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.278110 | 0.278110 | 0.278110 | 0.278110 | 5026.99 | 5026.99 | 6259.27 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.261390 | 0.261390 | 0.261390 | 0.261390 | 4832.24 | 4832.24 | 6203.10 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.227266 | 0.227266 | 0.227266 | 0.227266 | 4358.30 | 4358.30 | 6236.00 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.157415 | 0.157415 | 0.157415 | 0.157415 | 3095.33 | 3095.33 | 4326.24 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.155934 | 0.155934 | 0.155934 | 0.155934 | 3073.58 | 3073.58 | 4325.73 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.190564 | 0.190564 | 0.190564 | 0.190564 | 3641.25 | 3641.25 | 4293.20 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.191614 | 0.191614 | 0.191614 | 0.191614 | 3654.08 | 3654.08 | 4292.69 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.349408 | 0.349408 | 0.349408 | 0.349408 | 6081.21 | 6081.21 | 7199.82 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.322882 | 0.322882 | 0.322882 | 0.322882 | 5681.31 | 5681.31 | 7240.76 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.314267 | 0.314267 | 0.314267 | 0.314267 | 5595.00 | 5595.00 | 7177.38 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.273755 | 0.273755 | 0.273755 | 0.273755 | 5069.94 | 5069.94 | 7218.33 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.185708 | 0.185708 | 0.185708 | 0.185708 | 3532.95 | 3532.95 | 5357.72 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.185684 | 0.185684 | 0.185684 | 0.185684 | 3604.80 | 3604.80 | 5357.20 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.254328 | 0.254328 | 0.254328 | 0.254328 | 4548.17 | 4548.17 | 5313.53 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.255299 | 0.255299 | 0.255299 | 0.255299 | 4561.52 | 4561.52 | 5313.01 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.219053 |
AIRLOOP G NW SUPPLY FAN | 0.204997 |
AIRLOOP OFFICE SUPPLY FAN | 0.294756 |
AIRLOOP G NE SUPPLY FAN | 0.174036 |
AIRLOOP G N1 SUPPLY FAN | 0.116007 |
AIRLOOP G N2 SUPPLY FAN | 0.116005 |
AIRLOOP G S1 SUPPLY FAN | 0.133628 |
AIRLOOP G S2 SUPPLY FAN | 0.138923 |
AIRLOOP F2 SW SUPPLY FAN | 0.288759 |
AIRLOOP F2 NW SUPPLY FAN | 0.267387 |
AIRLOOP F2 SE SUPPLY FAN | 0.270005 |
AIRLOOP F2 NE SUPPLY FAN | 0.202129 |
AIRLOOP F2 N1 SUPPLY FAN | 0.144185 |
AIRLOOP F2 N2 SUPPLY FAN | 0.142654 |
AIRLOOP F2 S1 SUPPLY FAN | 0.181395 |
AIRLOOP F2 S2 SUPPLY FAN | 0.183568 |
AIRLOOP F3 SW SUPPLY FAN | 0.289899 |
AIRLOOP F3 NW SUPPLY FAN | 0.269888 |
AIRLOOP F3 SE SUPPLY FAN | 0.256175 |
AIRLOOP F3 NE SUPPLY FAN | 0.205876 |
AIRLOOP F3 N1 SUPPLY FAN | 0.148482 |
AIRLOOP F3 N2 SUPPLY FAN | 0.146970 |
AIRLOOP F3 S1 SUPPLY FAN | 0.185209 |
AIRLOOP F3 S2 SUPPLY FAN | 0.186363 |
AIRLOOP F4 SW SUPPLY FAN | 0.290536 |
AIRLOOP F4 NW SUPPLY FAN | 0.270936 |
AIRLOOP F4 SE SUPPLY FAN | 0.255868 |
AIRLOOP F4 NE SUPPLY FAN | 0.206887 |
AIRLOOP F4 N1 SUPPLY FAN | 0.150072 |
AIRLOOP F4 N2 SUPPLY FAN | 0.148569 |
AIRLOOP F4 S1 SUPPLY FAN | 0.186440 |
AIRLOOP F4 S2 SUPPLY FAN | 0.187449 |
AIRLOOP M SW SUPPLY FAN | 0.293379 |
AIRLOOP M NW SUPPLY FAN | 0.274160 |
AIRLOOP M SE SUPPLY FAN | 0.259017 |
AIRLOOP M NE SUPPLY FAN | 0.209964 |
AIRLOOP M N1 SUPPLY FAN | 0.153491 |
AIRLOOP M N2 SUPPLY FAN | 0.151995 |
AIRLOOP M S1 SUPPLY FAN | 0.189592 |
AIRLOOP M S2 SUPPLY FAN | 0.190580 |
AIRLOOP F6 SW SUPPLY FAN | 0.289711 |
AIRLOOP F6 NW SUPPLY FAN | 0.270620 |
AIRLOOP F6 SE SUPPLY FAN | 0.255802 |
AIRLOOP F6 NE SUPPLY FAN | 0.206414 |
AIRLOOP F6 N1 SUPPLY FAN | 0.150406 |
AIRLOOP F6 N2 SUPPLY FAN | 0.148924 |
AIRLOOP F6 S1 SUPPLY FAN | 0.186271 |
AIRLOOP F6 S2 SUPPLY FAN | 0.187256 |
AIRLOOP F7 SW SUPPLY FAN | 0.288466 |
AIRLOOP F7 NW SUPPLY FAN | 0.269571 |
AIRLOOP F7 SE SUPPLY FAN | 0.254941 |
AIRLOOP F7 NE SUPPLY FAN | 0.207200 |
AIRLOOP F7 N1 SUPPLY FAN | 0.149632 |
AIRLOOP F7 N2 SUPPLY FAN | 0.148160 |
AIRLOOP F7 S1 SUPPLY FAN | 0.185274 |
AIRLOOP F7 S2 SUPPLY FAN | 0.186257 |
AIRLOOP F8 SW SUPPLY FAN | 0.288570 |
AIRLOOP F8 NW SUPPLY FAN | 0.269850 |
AIRLOOP F8 SE SUPPLY FAN | 0.255301 |
AIRLOOP F8 NE SUPPLY FAN | 0.213252 |
AIRLOOP F8 N1 SUPPLY FAN | 0.150149 |
AIRLOOP F8 N2 SUPPLY FAN | 0.148687 |
AIRLOOP F8 S1 SUPPLY FAN | 0.185525 |
AIRLOOP F8 S2 SUPPLY FAN | 0.186510 |
AIRLOOP F9 SW SUPPLY FAN | 0.297135 |
AIRLOOP F9 NW SUPPLY FAN | 0.278110 |
AIRLOOP F9 SE SUPPLY FAN | 0.261390 |
AIRLOOP F9 NE SUPPLY FAN | 0.227266 |
AIRLOOP F9 N1 SUPPLY FAN | 0.157415 |
AIRLOOP F9 N2 SUPPLY FAN | 0.155934 |
AIRLOOP F9 S1 SUPPLY FAN | 0.190564 |
AIRLOOP F9 S2 SUPPLY FAN | 0.191614 |
AIRLOOP T SW SUPPLY FAN | 0.349408 |
AIRLOOP T NW SUPPLY FAN | 0.322882 |
AIRLOOP T SE SUPPLY FAN | 0.314267 |
AIRLOOP T NE SUPPLY FAN | 0.273755 |
AIRLOOP T N1 SUPPLY FAN | 0.185708 |
AIRLOOP T N2 SUPPLY FAN | 0.185684 |
AIRLOOP T S1 SUPPLY FAN | 0.254328 |
AIRLOOP T S2 SUPPLY FAN | 0.255299 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.219053 | 3887.38 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.204997 | 3684.09 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.294756 | 5271.71 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.174036 | 3354.42 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.116007 | 2420.09 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.116005 | 2432.99 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.133628 | 2659.02 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.138923 | 2733.18 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.288759 | 4950.17 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.267387 | 4645.28 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.270005 | 4730.04 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.202129 | 3696.78 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.144185 | 2787.43 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.142654 | 2765.36 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.181395 | 3381.17 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.183568 | 3411.40 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.289899 | 5022.00 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.269888 | 4735.20 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.256175 | 4591.56 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.205876 | 3800.25 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.148482 | 2877.67 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.146970 | 2855.82 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.185209 | 3466.03 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.186363 | 3482.07 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.290536 | 5072.40 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.270936 | 4798.67 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.255868 | 4627.16 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.206887 | 3852.08 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.150072 | 2921.93 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.148569 | 2900.12 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.186440 | 3506.82 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.187449 | 3520.88 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.293379 | 5145.80 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.274160 | 4876.88 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.259017 | 4703.77 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.209964 | 3926.14 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.153491 | 2988.53 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.151995 | 2966.79 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.189592 | 3570.36 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.190580 | 3584.12 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.289711 | 5122.82 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.270620 | 4855.04 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.255802 | 4685.66 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.206414 | 3900.89 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.150406 | 2958.72 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.148924 | 2937.04 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.186271 | 3539.64 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.187256 | 3553.40 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.288466 | 5130.10 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.269571 | 4864.54 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.254941 | 4697.22 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.207200 | 3943.14 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.149632 | 2960.23 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.148160 | 2938.61 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.185274 | 3539.62 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.186257 | 3553.39 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.288570 | 5153.68 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.269850 | 4890.11 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.255301 | 4723.47 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.213252 | 4078.04 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.150149 | 2979.08 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.148687 | 2957.57 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.185525 | 3555.76 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.186510 | 3569.57 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.297135 | 5294.95 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.278110 | 5026.99 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.261390 | 4832.24 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.227266 | 4358.30 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.157415 | 3095.33 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.155934 | 3073.58 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.190564 | 3641.25 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.191614 | 3654.08 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.349408 | 6081.21 | 0.000133 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.322882 | 5681.31 | 0.000124 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.314267 | 5595.00 | 0.000122 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.273755 | 5069.94 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.185708 | 3532.95 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.185684 | 3604.80 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.254328 | 4548.17 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.255299 | 4561.52 | 0.000100 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 5102.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 5111.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 6247.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 5110.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 3884.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 3884.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 3873.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 3882.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 5139.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 5150.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 5155.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 5142.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 3623.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 3623.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 3615.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 3617.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 5245.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 5265.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 5235.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 5253.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 3647.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 3646.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 3627.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 3627.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 5396.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 5421.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 5381.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 5406.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 3730.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 3729.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 3704.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 3704.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 5505.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 5534.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 5488.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 5516.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 3784.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 3784.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 3756.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 3756.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 5671.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 5704.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 5652.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 5684.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 3902.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 3902.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 3870.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 3870.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 5798.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 5832.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 5777.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 5811.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 3986.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 3986.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 3953.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 3952.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 5926.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 5961.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 5904.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 5939.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 4076.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 4076.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 4041.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 4041.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 6226.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 6259.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 6203.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 6236.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 4326.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 4325.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 4293.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 4292.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 7199.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 7240.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 7177.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 7218.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 5357.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 5357.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 5313.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 5313.01 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.006932 | 7.80 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.006932 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.006932 | 3346.48 | 9.23 | 9900.66 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.006932 | 1768.07 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.76 | -7.7 |
March | 21.86 | 0.33 |
April | 22.36 | 7.02 |
May | 23.06 | 14.19 |
June | 24.08 | 19.16 |
July | 24.24 | 20.92 |
August | 24.23 | 20.05 |
September | 23.79 | 15.39 |
October | 22.43 | 7.43 |
November | 21.95 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.77 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.12 | 7.02 |
May | 22.85 | 14.19 |
June | 24.07 | 19.16 |
July | 24.23 | 20.92 |
August | 24.20 | 20.05 |
September | 23.54 | 15.39 |
October | 21.91 | 7.43 |
November | 21.77 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.63 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.23 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -12.6 |
February | 21.79 | -7.7 |
March | 21.98 | 0.33 |
April | 22.52 | 7.02 |
May | 23.43 | 14.19 |
June | 24.14 | 19.16 |
July | 24.36 | 20.92 |
August | 24.33 | 20.05 |
September | 23.84 | 15.39 |
October | 22.52 | 7.43 |
November | 22.01 | -0.0 |
December | 21.74 | -7.6 |
Annual Sum or Average | 22.87 | 6.46 |
Minimum of Months | 21.73 | -12.6 |
Maximum of Months | 24.36 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 22.07 | 7.02 |
May | 22.83 | 14.19 |
June | 24.07 | 19.16 |
July | 24.24 | 20.92 |
August | 24.19 | 20.05 |
September | 23.53 | 15.39 |
October | 21.83 | 7.43 |
November | 21.74 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.61 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.71 | 0.33 |
April | 22.01 | 7.02 |
May | 22.62 | 14.19 |
June | 24.02 | 19.16 |
July | 24.18 | 20.92 |
August | 24.13 | 20.05 |
September | 23.53 | 15.39 |
October | 21.84 | 7.43 |
November | 21.76 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.58 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.18 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.71 | 0.33 |
April | 22.01 | 7.02 |
May | 22.62 | 14.19 |
June | 24.02 | 19.16 |
July | 24.18 | 20.92 |
August | 24.13 | 20.05 |
September | 23.53 | 15.39 |
October | 21.83 | 7.43 |
November | 21.76 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.58 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.18 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.86 | 0.33 |
April | 22.29 | 7.02 |
May | 22.92 | 14.19 |
June | 24.07 | 19.16 |
July | 24.20 | 20.92 |
August | 24.21 | 20.05 |
September | 23.87 | 15.39 |
October | 22.51 | 7.43 |
November | 22.00 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 22.77 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.21 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.87 | 0.33 |
April | 22.31 | 7.02 |
May | 22.97 | 14.19 |
June | 24.09 | 19.16 |
July | 24.21 | 20.92 |
August | 24.21 | 20.05 |
September | 23.89 | 15.39 |
October | 22.54 | 7.43 |
November | 22.01 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 22.78 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.21 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.78 | -12.6 |
February | 15.04 | -7.7 |
March | 17.20 | 0.33 |
April | 19.27 | 7.02 |
May | 21.71 | 14.19 |
June | 24.20 | 19.16 |
July | 24.86 | 20.92 |
August | 24.64 | 20.05 |
September | 23.12 | 15.39 |
October | 19.51 | 7.43 |
November | 17.10 | -0.0 |
December | 14.96 | -7.6 |
Annual Sum or Average | 19.64 | 6.46 |
Minimum of Months | 13.78 | -12.6 |
Maximum of Months | 24.86 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 22.05 | 0.33 |
April | 22.75 | 7.02 |
May | 23.90 | 14.19 |
June | 24.28 | 19.16 |
July | 24.32 | 20.92 |
August | 24.33 | 20.05 |
September | 24.01 | 15.39 |
October | 22.96 | 7.43 |
November | 22.24 | -0.0 |
December | 21.74 | -7.6 |
Annual Sum or Average | 23.02 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.38 | 7.02 |
May | 23.67 | 14.19 |
June | 24.26 | 19.16 |
July | 24.32 | 20.92 |
August | 24.31 | 20.05 |
September | 23.75 | 15.39 |
October | 22.10 | 7.43 |
November | 21.91 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.32 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 22.06 | 0.33 |
April | 22.74 | 7.02 |
May | 23.99 | 14.19 |
June | 24.30 | 19.16 |
July | 24.34 | 20.92 |
August | 24.35 | 20.05 |
September | 24.06 | 15.39 |
October | 23.00 | 7.43 |
November | 22.25 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 23.04 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.29 | 7.02 |
May | 23.61 | 14.19 |
June | 24.25 | 19.16 |
July | 24.32 | 20.92 |
August | 24.31 | 20.05 |
September | 23.69 | 15.39 |
October | 21.95 | 7.43 |
November | 21.84 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.76 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.32 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.76 | 0.33 |
April | 22.26 | 7.02 |
May | 23.47 | 14.19 |
June | 24.25 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.75 | 15.39 |
October | 22.04 | 7.43 |
November | 21.91 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.76 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.26 | 7.02 |
May | 23.46 | 14.19 |
June | 24.25 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.74 | 15.39 |
October | 22.03 | 7.43 |
November | 21.91 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.76 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.86 | -7.7 |
March | 22.10 | 0.33 |
April | 22.74 | 7.02 |
May | 23.84 | 14.19 |
June | 24.28 | 19.16 |
July | 24.29 | 20.92 |
August | 24.31 | 20.05 |
September | 24.10 | 15.39 |
October | 23.20 | 7.43 |
November | 22.36 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.06 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.87 | -7.7 |
March | 22.11 | 0.33 |
April | 22.74 | 7.02 |
May | 23.85 | 14.19 |
June | 24.29 | 19.16 |
July | 24.30 | 20.92 |
August | 24.31 | 20.05 |
September | 24.11 | 15.39 |
October | 23.22 | 7.43 |
November | 22.37 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.06 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -12.6 |
February | 21.08 | -7.7 |
March | 21.91 | 0.33 |
April | 23.17 | 7.02 |
May | 24.90 | 14.19 |
June | 26.08 | 19.16 |
July | 26.33 | 20.92 |
August | 26.20 | 20.05 |
September | 25.41 | 15.39 |
October | 23.25 | 7.43 |
November | 21.89 | -0.0 |
December | 20.81 | -7.6 |
Annual Sum or Average | 23.48 | 6.46 |
Minimum of Months | 20.52 | -12.6 |
Maximum of Months | 26.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 22.06 | 0.33 |
April | 22.78 | 7.02 |
May | 24.00 | 14.19 |
June | 24.29 | 19.16 |
July | 24.32 | 20.92 |
August | 24.33 | 20.05 |
September | 24.01 | 15.39 |
October | 23.03 | 7.43 |
November | 22.32 | -0.0 |
December | 21.74 | -7.6 |
Annual Sum or Average | 23.04 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.78 | 0.33 |
April | 22.42 | 7.02 |
May | 23.81 | 14.19 |
June | 24.28 | 19.16 |
July | 24.32 | 20.92 |
August | 24.31 | 20.05 |
September | 23.75 | 15.39 |
October | 22.13 | 7.43 |
November | 21.96 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.83 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.32 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.81 | -7.7 |
March | 22.03 | 0.33 |
April | 22.72 | 7.02 |
May | 24.02 | 14.19 |
June | 24.29 | 19.16 |
July | 24.32 | 20.92 |
August | 24.34 | 20.05 |
September | 24.02 | 15.39 |
October | 23.00 | 7.43 |
November | 22.28 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 23.03 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.34 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.33 | 7.02 |
May | 23.75 | 14.19 |
June | 24.27 | 19.16 |
July | 24.31 | 20.92 |
August | 24.31 | 20.05 |
September | 23.69 | 15.39 |
October | 21.97 | 7.43 |
November | 21.88 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.79 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.34 | 7.02 |
May | 23.68 | 14.19 |
June | 24.28 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.78 | 15.39 |
October | 22.11 | 7.43 |
November | 21.98 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.33 | 7.02 |
May | 23.67 | 14.19 |
June | 24.28 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.77 | 15.39 |
October | 22.09 | 7.43 |
November | 21.97 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.80 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.89 | -7.7 |
March | 22.15 | 0.33 |
April | 22.83 | 7.02 |
May | 23.99 | 14.19 |
June | 24.30 | 19.16 |
July | 24.29 | 20.92 |
August | 24.31 | 20.05 |
September | 24.12 | 15.39 |
October | 23.36 | 7.43 |
November | 22.45 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.11 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.89 | -7.7 |
March | 22.15 | 0.33 |
April | 22.82 | 7.02 |
May | 24.00 | 14.19 |
June | 24.30 | 19.16 |
July | 24.29 | 20.92 |
August | 24.31 | 20.05 |
September | 24.12 | 15.39 |
October | 23.36 | 7.43 |
November | 22.45 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.11 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | -12.6 |
February | 21.58 | -7.7 |
March | 22.33 | 0.33 |
April | 23.59 | 7.02 |
May | 25.40 | 14.19 |
June | 26.29 | 19.16 |
July | 26.47 | 20.92 |
August | 26.35 | 20.05 |
September | 25.61 | 15.39 |
October | 23.64 | 7.43 |
November | 22.34 | -0.0 |
December | 21.28 | -7.6 |
Annual Sum or Average | 23.84 | 6.46 |
Minimum of Months | 21.06 | -12.6 |
Maximum of Months | 26.47 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.81 | -7.7 |
March | 22.03 | 0.33 |
April | 22.77 | 7.02 |
May | 24.02 | 14.19 |
June | 24.29 | 19.16 |
July | 24.31 | 20.92 |
August | 24.32 | 20.05 |
September | 23.99 | 15.39 |
October | 23.00 | 7.43 |
November | 22.32 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 23.03 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.32 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.43 | 7.02 |
May | 23.84 | 14.19 |
June | 24.27 | 19.16 |
July | 24.31 | 20.92 |
August | 24.30 | 20.05 |
September | 23.73 | 15.39 |
October | 22.12 | 7.43 |
November | 21.97 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.83 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.80 | -7.7 |
March | 22.00 | 0.33 |
April | 22.70 | 7.02 |
May | 24.02 | 14.19 |
June | 24.29 | 19.16 |
July | 24.32 | 20.92 |
August | 24.33 | 20.05 |
September | 24.00 | 15.39 |
October | 22.95 | 7.43 |
November | 22.29 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 23.02 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.35 | 7.02 |
May | 23.78 | 14.19 |
June | 24.26 | 19.16 |
July | 24.31 | 20.92 |
August | 24.30 | 20.05 |
September | 23.67 | 15.39 |
October | 21.97 | 7.43 |
November | 21.89 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.79 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.37 | 7.02 |
May | 23.74 | 14.19 |
June | 24.28 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.77 | 15.39 |
October | 22.12 | 7.43 |
November | 22.00 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.81 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.36 | 7.02 |
May | 23.74 | 14.19 |
June | 24.28 | 19.16 |
July | 24.28 | 20.92 |
August | 24.26 | 20.05 |
September | 23.76 | 15.39 |
October | 22.10 | 7.43 |
November | 21.99 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.81 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.88 | -7.7 |
March | 22.15 | 0.33 |
April | 22.84 | 7.02 |
May | 24.03 | 14.19 |
June | 24.30 | 19.16 |
July | 24.29 | 20.92 |
August | 24.30 | 20.05 |
September | 24.11 | 15.39 |
October | 23.37 | 7.43 |
November | 22.46 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.11 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.88 | -7.7 |
March | 22.15 | 0.33 |
April | 22.83 | 7.02 |
May | 24.03 | 14.19 |
June | 24.30 | 19.16 |
July | 24.29 | 20.92 |
August | 24.30 | 20.05 |
September | 24.11 | 15.39 |
October | 23.37 | 7.43 |
November | 22.46 | -0.0 |
December | 21.78 | -7.6 |
Annual Sum or Average | 23.11 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | -12.6 |
February | 21.71 | -7.7 |
March | 22.45 | 0.33 |
April | 23.73 | 7.02 |
May | 25.57 | 14.19 |
June | 26.40 | 19.16 |
July | 26.56 | 20.92 |
August | 26.44 | 20.05 |
September | 25.70 | 15.39 |
October | 23.76 | 7.43 |
November | 22.49 | -0.0 |
December | 21.41 | -7.6 |
Annual Sum or Average | 23.96 | 6.46 |
Minimum of Months | 21.19 | -12.6 |
Maximum of Months | 26.56 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.81 | -7.7 |
March | 22.01 | 0.33 |
April | 22.74 | 7.02 |
May | 24.00 | 14.19 |
June | 24.28 | 19.16 |
July | 24.31 | 20.92 |
August | 24.31 | 20.05 |
September | 23.98 | 15.39 |
October | 22.97 | 7.43 |
November | 22.32 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 23.02 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.42 | 7.02 |
May | 23.83 | 14.19 |
June | 24.27 | 19.16 |
July | 24.30 | 20.92 |
August | 24.30 | 20.05 |
September | 23.71 | 15.39 |
October | 22.11 | 7.43 |
November | 21.98 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.82 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.79 | -7.7 |
March | 21.98 | 0.33 |
April | 22.68 | 7.02 |
May | 24.00 | 14.19 |
June | 24.28 | 19.16 |
July | 24.31 | 20.92 |
August | 24.32 | 20.05 |
September | 23.98 | 15.39 |
October | 22.92 | 7.43 |
November | 22.28 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 23.01 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.32 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.34 | 7.02 |
May | 23.77 | 14.19 |
June | 24.26 | 19.16 |
July | 24.30 | 20.92 |
August | 24.29 | 20.05 |
September | 23.66 | 15.39 |
October | 21.96 | 7.43 |
November | 21.90 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.78 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.37 | 7.02 |
May | 23.75 | 14.19 |
June | 24.28 | 19.16 |
July | 24.27 | 20.92 |
August | 24.26 | 20.05 |
September | 23.77 | 15.39 |
October | 22.13 | 7.43 |
November | 22.02 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.82 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.77 | 0.33 |
April | 22.37 | 7.02 |
May | 23.74 | 14.19 |
June | 24.28 | 19.16 |
July | 24.27 | 20.92 |
August | 24.26 | 20.05 |
September | 23.76 | 15.39 |
October | 22.11 | 7.43 |
November | 22.01 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.81 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.88 | -7.7 |
March | 22.13 | 0.33 |
April | 22.83 | 7.02 |
May | 24.02 | 14.19 |
June | 24.30 | 19.16 |
July | 24.28 | 20.92 |
August | 24.29 | 20.05 |
September | 24.10 | 15.39 |
October | 23.36 | 7.43 |
November | 22.46 | -0.0 |
December | 21.77 | -7.6 |
Annual Sum or Average | 23.10 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -12.6 |
February | 21.88 | -7.7 |
March | 22.13 | 0.33 |
April | 22.82 | 7.02 |
May | 24.03 | 14.19 |
June | 24.30 | 19.16 |
July | 24.28 | 20.92 |
August | 24.29 | 20.05 |
September | 24.11 | 15.39 |
October | 23.36 | 7.43 |
November | 22.46 | -0.0 |
December | 21.77 | -7.6 |
Annual Sum or Average | 23.10 | 6.46 |
Minimum of Months | 21.74 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | -12.6 |
February | 22.35 | -7.7 |
March | 23.08 | 0.33 |
April | 24.35 | 7.02 |
May | 26.18 | 14.19 |
June | 27.00 | 19.16 |
July | 27.16 | 20.92 |
August | 27.03 | 20.05 |
September | 26.30 | 15.39 |
October | 24.37 | 7.43 |
November | 23.13 | -0.0 |
December | 22.05 | -7.6 |
Annual Sum or Average | 24.58 | 6.46 |
Minimum of Months | 21.81 | -12.6 |
Maximum of Months | 27.16 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.79 | -7.7 |
March | 21.96 | 0.33 |
April | 22.67 | 7.02 |
May | 23.93 | 14.19 |
June | 24.25 | 19.16 |
July | 24.29 | 20.92 |
August | 24.29 | 20.05 |
September | 23.92 | 15.39 |
October | 22.85 | 7.43 |
November | 22.28 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.98 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.29 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.36 | 7.02 |
May | 23.74 | 14.19 |
June | 24.24 | 19.16 |
July | 24.29 | 20.92 |
August | 24.28 | 20.05 |
September | 23.63 | 15.39 |
October | 22.04 | 7.43 |
November | 21.94 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.79 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.29 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.78 | -7.7 |
March | 21.93 | 0.33 |
April | 22.62 | 7.02 |
May | 23.93 | 14.19 |
June | 24.26 | 19.16 |
July | 24.29 | 20.92 |
August | 24.30 | 20.05 |
September | 23.92 | 15.39 |
October | 22.79 | 7.43 |
November | 22.24 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.96 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.30 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.30 | 7.02 |
May | 23.68 | 14.19 |
June | 24.23 | 19.16 |
July | 24.28 | 20.92 |
August | 24.27 | 20.05 |
September | 23.58 | 15.39 |
October | 21.91 | 7.43 |
November | 21.87 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.75 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.76 | 0.33 |
April | 22.32 | 7.02 |
May | 23.65 | 14.19 |
June | 24.26 | 19.16 |
July | 24.25 | 20.92 |
August | 24.23 | 20.05 |
September | 23.68 | 15.39 |
October | 22.05 | 7.43 |
November | 21.98 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.78 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.32 | 7.02 |
May | 23.65 | 14.19 |
June | 24.26 | 19.16 |
July | 24.25 | 20.92 |
August | 24.23 | 20.05 |
September | 23.67 | 15.39 |
October | 22.04 | 7.43 |
November | 21.97 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.78 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -12.6 |
February | 21.85 | -7.7 |
March | 22.08 | 0.33 |
April | 22.76 | 7.02 |
May | 23.95 | 14.19 |
June | 24.28 | 19.16 |
July | 24.26 | 20.92 |
August | 24.27 | 20.05 |
September | 24.05 | 15.39 |
October | 23.24 | 7.43 |
November | 22.43 | -0.0 |
December | 21.76 | -7.6 |
Annual Sum or Average | 23.06 | 6.46 |
Minimum of Months | 21.73 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -12.6 |
February | 21.85 | -7.7 |
March | 22.08 | 0.33 |
April | 22.75 | 7.02 |
May | 23.95 | 14.19 |
June | 24.28 | 19.16 |
July | 24.26 | 20.92 |
August | 24.27 | 20.05 |
September | 24.05 | 15.39 |
October | 23.23 | 7.43 |
November | 22.43 | -0.0 |
December | 21.76 | -7.6 |
Annual Sum or Average | 23.06 | 6.46 |
Minimum of Months | 21.73 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -12.6 |
February | 21.64 | -7.7 |
March | 22.36 | 0.33 |
April | 23.64 | 7.02 |
May | 25.49 | 14.19 |
June | 26.36 | 19.16 |
July | 26.53 | 20.92 |
August | 26.40 | 20.05 |
September | 25.61 | 15.39 |
October | 23.64 | 7.43 |
November | 22.42 | -0.0 |
December | 21.34 | -7.6 |
Annual Sum or Average | 23.89 | 6.46 |
Minimum of Months | 21.12 | -12.6 |
Maximum of Months | 26.53 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.78 | -7.7 |
March | 21.93 | 0.33 |
April | 22.62 | 7.02 |
May | 23.87 | 14.19 |
June | 24.24 | 19.16 |
July | 24.28 | 20.92 |
August | 24.28 | 20.05 |
September | 23.87 | 15.39 |
October | 22.76 | 7.43 |
November | 22.24 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.95 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.33 | 7.02 |
May | 23.67 | 14.19 |
June | 24.22 | 19.16 |
July | 24.27 | 20.92 |
August | 24.26 | 20.05 |
September | 23.57 | 15.39 |
October | 21.99 | 7.43 |
November | 21.92 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.76 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.27 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.90 | 0.33 |
April | 22.57 | 7.02 |
May | 23.87 | 14.19 |
June | 24.23 | 19.16 |
July | 24.28 | 20.92 |
August | 24.28 | 20.05 |
September | 23.87 | 15.39 |
October | 22.70 | 7.43 |
November | 22.20 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.93 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.28 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 22.27 | 7.02 |
May | 23.61 | 14.19 |
June | 24.21 | 19.16 |
July | 24.27 | 20.92 |
August | 24.25 | 20.05 |
September | 23.52 | 15.39 |
October | 21.88 | 7.43 |
November | 21.84 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.73 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.27 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.29 | 7.02 |
May | 23.58 | 14.19 |
June | 24.24 | 19.16 |
July | 24.23 | 20.92 |
August | 24.22 | 20.05 |
September | 23.61 | 15.39 |
October | 22.00 | 7.43 |
November | 21.95 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.75 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.28 | 7.02 |
May | 23.58 | 14.19 |
June | 24.23 | 19.16 |
July | 24.23 | 20.92 |
August | 24.22 | 20.05 |
September | 23.61 | 15.39 |
October | 21.99 | 7.43 |
November | 21.95 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.75 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.23 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.84 | -7.7 |
March | 22.04 | 0.33 |
April | 22.70 | 7.02 |
May | 23.90 | 14.19 |
June | 24.26 | 19.16 |
July | 24.25 | 20.92 |
August | 24.26 | 20.05 |
September | 24.01 | 15.39 |
October | 23.13 | 7.43 |
November | 22.40 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.03 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.83 | -7.7 |
March | 22.04 | 0.33 |
April | 22.70 | 7.02 |
May | 23.90 | 14.19 |
June | 24.26 | 19.16 |
July | 24.25 | 20.92 |
August | 24.26 | 20.05 |
September | 24.01 | 15.39 |
October | 23.13 | 7.43 |
November | 22.40 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.03 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | -12.6 |
February | 21.48 | -7.7 |
March | 22.19 | 0.33 |
April | 23.48 | 7.02 |
May | 25.32 | 14.19 |
June | 26.24 | 19.16 |
July | 26.43 | 20.92 |
August | 26.29 | 20.05 |
September | 25.46 | 15.39 |
October | 23.45 | 7.43 |
November | 22.25 | -0.0 |
December | 21.19 | -7.6 |
Annual Sum or Average | 23.74 | 6.46 |
Minimum of Months | 20.96 | -12.6 |
Maximum of Months | 26.43 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.90 | 0.33 |
April | 22.58 | 7.02 |
May | 23.82 | 14.19 |
June | 24.22 | 19.16 |
July | 24.27 | 20.92 |
August | 24.27 | 20.05 |
September | 23.83 | 15.39 |
October | 22.68 | 7.43 |
November | 22.20 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.92 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.27 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.30 | 7.02 |
May | 23.60 | 14.19 |
June | 24.20 | 19.16 |
July | 24.26 | 20.92 |
August | 24.25 | 20.05 |
September | 23.52 | 15.39 |
October | 21.96 | 7.43 |
November | 21.89 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.74 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.76 | -7.7 |
March | 21.88 | 0.33 |
April | 22.54 | 7.02 |
May | 23.82 | 14.19 |
June | 24.21 | 19.16 |
July | 24.27 | 20.92 |
August | 24.27 | 20.05 |
September | 23.83 | 15.39 |
October | 22.61 | 7.43 |
November | 22.16 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.90 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.27 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 22.25 | 7.02 |
May | 23.55 | 14.19 |
June | 24.18 | 19.16 |
July | 24.26 | 20.92 |
August | 24.24 | 20.05 |
September | 23.48 | 15.39 |
October | 21.86 | 7.43 |
November | 21.82 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.71 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.26 | 7.02 |
May | 23.52 | 14.19 |
June | 24.21 | 19.16 |
July | 24.22 | 20.92 |
August | 24.20 | 20.05 |
September | 23.55 | 15.39 |
October | 21.96 | 7.43 |
November | 21.93 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.73 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.22 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.26 | 7.02 |
May | 23.52 | 14.19 |
June | 24.21 | 19.16 |
July | 24.22 | 20.92 |
August | 24.20 | 20.05 |
September | 23.55 | 15.39 |
October | 21.95 | 7.43 |
November | 21.92 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.73 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.22 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 22.00 | 0.33 |
April | 22.66 | 7.02 |
May | 23.85 | 14.19 |
June | 24.24 | 19.16 |
July | 24.24 | 20.92 |
August | 24.24 | 20.05 |
September | 23.97 | 15.39 |
October | 23.03 | 7.43 |
November | 22.37 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.00 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 22.00 | 0.33 |
April | 22.66 | 7.02 |
May | 23.85 | 14.19 |
June | 24.24 | 19.16 |
July | 24.24 | 20.92 |
August | 24.24 | 20.05 |
September | 23.97 | 15.39 |
October | 23.03 | 7.43 |
November | 22.37 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 23.00 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.87 | -12.6 |
February | 21.38 | -7.7 |
March | 22.10 | 0.33 |
April | 23.39 | 7.02 |
May | 25.23 | 14.19 |
June | 26.20 | 19.16 |
July | 26.41 | 20.92 |
August | 26.26 | 20.05 |
September | 25.38 | 15.39 |
October | 23.34 | 7.43 |
November | 22.14 | -0.0 |
December | 21.10 | -7.6 |
Annual Sum or Average | 23.66 | 6.46 |
Minimum of Months | 20.87 | -12.6 |
Maximum of Months | 26.41 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.77 | -7.7 |
March | 21.88 | 0.33 |
April | 22.54 | 7.02 |
May | 23.75 | 14.19 |
June | 24.18 | 19.16 |
July | 24.26 | 20.92 |
August | 24.25 | 20.05 |
September | 23.75 | 15.39 |
October | 22.58 | 7.43 |
November | 22.14 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.88 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.28 | 7.02 |
May | 23.53 | 14.19 |
June | 24.16 | 19.16 |
July | 24.25 | 20.92 |
August | 24.23 | 20.05 |
September | 23.46 | 15.39 |
October | 21.93 | 7.43 |
November | 21.86 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.72 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.25 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.75 | -7.7 |
March | 21.85 | 0.33 |
April | 22.50 | 7.02 |
May | 23.75 | 14.19 |
June | 24.18 | 19.16 |
July | 24.26 | 20.92 |
August | 24.26 | 20.05 |
September | 23.75 | 15.39 |
October | 22.52 | 7.43 |
November | 22.10 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.87 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.26 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.72 | 0.33 |
April | 22.24 | 7.02 |
May | 23.49 | 14.19 |
June | 24.15 | 19.16 |
July | 24.25 | 20.92 |
August | 24.22 | 20.05 |
September | 23.42 | 15.39 |
October | 21.85 | 7.43 |
November | 21.80 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.69 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.25 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.24 | 7.02 |
May | 23.45 | 14.19 |
June | 24.18 | 19.16 |
July | 24.21 | 20.92 |
August | 24.19 | 20.05 |
September | 23.47 | 15.39 |
October | 21.93 | 7.43 |
November | 21.90 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.70 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.21 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.24 | 7.02 |
May | 23.45 | 14.19 |
June | 24.18 | 19.16 |
July | 24.21 | 20.92 |
August | 24.18 | 20.05 |
September | 23.47 | 15.39 |
October | 21.92 | 7.43 |
November | 21.89 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.70 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.21 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.81 | -7.7 |
March | 21.97 | 0.33 |
April | 22.61 | 7.02 |
May | 23.78 | 14.19 |
June | 24.21 | 19.16 |
July | 24.23 | 20.92 |
August | 24.23 | 20.05 |
September | 23.89 | 15.39 |
October | 22.89 | 7.43 |
November | 22.30 | -0.0 |
December | 21.74 | -7.6 |
Annual Sum or Average | 22.95 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.23 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.81 | -7.7 |
March | 21.96 | 0.33 |
April | 22.61 | 7.02 |
May | 23.78 | 14.19 |
June | 24.21 | 19.16 |
July | 24.23 | 20.92 |
August | 24.23 | 20.05 |
September | 23.89 | 15.39 |
October | 22.88 | 7.43 |
November | 22.30 | -0.0 |
December | 21.74 | -7.6 |
Annual Sum or Average | 22.95 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.23 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -12.6 |
February | 21.17 | -7.7 |
March | 21.93 | 0.33 |
April | 23.28 | 7.02 |
May | 25.15 | 14.19 |
June | 26.20 | 19.16 |
July | 26.45 | 20.92 |
August | 26.27 | 20.05 |
September | 25.28 | 15.39 |
October | 23.17 | 7.43 |
November | 21.93 | -0.0 |
December | 20.88 | -7.6 |
Annual Sum or Average | 23.54 | 6.46 |
Minimum of Months | 20.63 | -12.6 |
Maximum of Months | 26.45 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.79 | -7.7 |
March | 21.89 | 0.33 |
April | 22.48 | 7.02 |
May | 23.49 | 14.19 |
June | 24.03 | 19.16 |
July | 24.18 | 20.92 |
August | 24.13 | 20.05 |
September | 23.51 | 15.39 |
October | 22.46 | 7.43 |
November | 22.05 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.79 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.18 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.75 | 0.33 |
April | 22.28 | 7.02 |
May | 23.33 | 14.19 |
June | 24.01 | 19.16 |
July | 24.17 | 20.92 |
August | 24.10 | 20.05 |
September | 23.27 | 15.39 |
October | 21.96 | 7.43 |
November | 21.85 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.66 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.17 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -12.6 |
February | 21.77 | -7.7 |
March | 21.87 | 0.33 |
April | 22.45 | 7.02 |
May | 23.50 | 14.19 |
June | 24.03 | 19.16 |
July | 24.20 | 20.92 |
August | 24.13 | 20.05 |
September | 23.52 | 15.39 |
October | 22.42 | 7.43 |
November | 22.01 | -0.0 |
December | 21.71 | -7.6 |
Annual Sum or Average | 22.78 | 6.46 |
Minimum of Months | 21.71 | -12.6 |
Maximum of Months | 24.20 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.73 | 0.33 |
April | 22.26 | 7.02 |
May | 23.30 | 14.19 |
June | 24.00 | 19.16 |
July | 24.18 | 20.92 |
August | 24.08 | 20.05 |
September | 23.26 | 15.39 |
October | 21.86 | 7.43 |
November | 21.80 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.64 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.18 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.24 | 7.02 |
May | 23.26 | 14.19 |
June | 24.02 | 19.16 |
July | 24.14 | 20.92 |
August | 24.06 | 20.05 |
September | 23.26 | 15.39 |
October | 21.90 | 7.43 |
November | 21.86 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.64 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.14 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -12.6 |
February | 21.70 | -7.7 |
March | 21.74 | 0.33 |
April | 22.23 | 7.02 |
May | 23.26 | 14.19 |
June | 24.02 | 19.16 |
July | 24.13 | 20.92 |
August | 24.05 | 20.05 |
September | 23.26 | 15.39 |
October | 21.89 | 7.43 |
November | 21.85 | -0.0 |
December | 21.70 | -7.6 |
Annual Sum or Average | 22.63 | 6.46 |
Minimum of Months | 21.70 | -12.6 |
Maximum of Months | 24.13 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 21.96 | 0.33 |
April | 22.53 | 7.02 |
May | 23.56 | 14.19 |
June | 24.08 | 19.16 |
July | 24.17 | 20.92 |
August | 24.13 | 20.05 |
September | 23.63 | 15.39 |
October | 22.62 | 7.43 |
November | 22.17 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 22.85 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.17 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 21.82 | -7.7 |
March | 21.96 | 0.33 |
April | 22.52 | 7.02 |
May | 23.56 | 14.19 |
June | 24.08 | 19.16 |
July | 24.17 | 20.92 |
August | 24.13 | 20.05 |
September | 23.64 | 15.39 |
October | 22.61 | 7.43 |
November | 22.17 | -0.0 |
December | 21.75 | -7.6 |
Annual Sum or Average | 22.85 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 24.17 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.05 | -12.6 |
February | 20.77 | -7.7 |
March | 21.86 | 0.33 |
April | 23.46 | 7.02 |
May | 25.52 | 14.19 |
June | 26.77 | 19.16 |
July | 27.13 | 20.92 |
August | 26.84 | 20.05 |
September | 25.55 | 15.39 |
October | 23.22 | 7.43 |
November | 21.71 | -0.0 |
December | 20.46 | -7.6 |
Annual Sum or Average | 23.63 | 6.46 |
Minimum of Months | 20.05 | -12.6 |
Maximum of Months | 27.13 | 20.92 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:11
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.320446E+12 | 219199.929 | 18-JAN-19:00 | 25049.151 | 51564.864 | 19230.898 | 109815.304 | 0.000 | 10720.100 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.263489E+12 | 191742.859 | 01-FEB-20:00 | 25049.151 | 49704.829 | 19230.898 | 84287.312 | 0.000 | 10720.100 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.254434E+12 | 148769.929 | 05-MAR-18:00 | 22204.399 | 56867.515 | 19230.898 | 36796.130 | 0.000 | 10720.100 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.225753E+12 | 176245.881 | 16-APR-17:00 | 22204.399 | 56867.515 | 19230.898 | 0.000 | 72367.751 | 0.000 | 1804.998 | 2624.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.220943E+12 | 169959.014 | 31-MAY-18:30 | 25049.151 | 51564.864 | 19230.898 | 0.000 | 68795.245 | 0.000 | 1804.998 | 2499.244 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.264879E+12 | 183025.478 | 24-JUN-17:30 | 22204.399 | 56867.515 | 19230.898 | 0.000 | 78894.545 | 0.000 | 1804.998 | 2877.235 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.290959E+12 | 184755.997 | 25-JUL-19:45 | 25049.151 | 49704.829 | 19230.898 | 0.000 | 74374.529 | 10720.100 | 1804.998 | 2925.921 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.277205E+12 | 185857.601 | 02-AUG-19:30 | 25049.151 | 49704.829 | 19230.898 | 0.000 | 75394.101 | 10720.100 | 1804.998 | 3007.952 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.238129E+12 | 175141.213 | 11-SEP-17:30 | 22204.399 | 56867.515 | 19230.898 | 0.000 | 71232.487 | 0.000 | 1804.998 | 2655.028 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.219414E+12 | 118915.113 | 02-OCT-17:00 | 22204.399 | 56867.515 | 19230.898 | 0.000 | 6626.309 | 10720.100 | 1804.998 | 315.006 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.255162E+12 | 163574.544 | 25-NOV-18:15 | 22204.399 | 56867.515 | 19230.898 | 51600.998 | 0.000 | 10720.100 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.303499E+12 | 238392.128 | 09-DEC-01:00 | 7980.643 | 20217.842 | 19230.898 | 178038.208 | 0.000 | 10720.100 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.313431E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.219414E+12 | 118915.113 | 7980.643 | 20217.842 | 19230.898 | 0.000 | 0.000 | 0.000 | 1804.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.320446E+12 | 238392.128 | 25049.151 | 56867.515 | 19230.898 | 178038.208 | 78894.545 | 10720.100 | 1804.998 | 3007.952 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:11
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.560312E+12 | 403455.744 | 19-JAN-08:15 | 0.000 | 0.000 | 0.000 | 403455.744 | 92043.006 | 92043.006 | 311412.738 |
February | 0.406992E+12 | 400035.333 | 02-FEB-08:30 | 0.000 | 0.000 | 0.000 | 400035.333 | 91723.363 | 91723.363 | 308311.971 |
March | 0.301582E+12 | 324795.538 | 06-MAR-07:30 | 0.000 | 0.000 | 0.000 | 324795.538 | 93320.149 | 93320.149 | 231475.389 |
April | 0.179268E+12 | 237887.077 | 03-APR-05:00 | 0.000 | 0.000 | 0.000 | 237887.077 | 89176.547 | 89176.547 | 148710.530 |
May | 0.112962E+12 | 127306.829 | 02-MAY-05:45 | 0.000 | 0.000 | 0.000 | 127306.829 | 86244.178 | 86244.178 | 41062.650 |
June | 0.100744E+12 | 86975.268 | 01-JUN-06:45 | 0.000 | 0.000 | 0.000 | 86975.268 | 86975.268 | 86975.268 | 0.000 |
July | 0.983256E+11 | 84631.788 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 84631.788 | 84631.788 | 84631.788 | 0.000 |
August | 0.956936E+11 | 83128.421 | 01-AUG-06:45 | 0.000 | 0.000 | 0.000 | 83128.421 | 83128.421 | 83128.421 | 0.000 |
September | 0.969953E+11 | 132385.697 | 30-SEP-06:15 | 0.000 | 0.000 | 0.000 | 132385.697 | 82944.608 | 82944.608 | 49441.089 |
October | 0.132403E+12 | 152066.046 | 24-OCT-06:30 | 0.000 | 0.000 | 0.000 | 152066.046 | 85346.505 | 85346.505 | 66719.541 |
November | 0.303113E+12 | 317219.311 | 26-NOV-08:15 | 0.000 | 0.000 | 0.000 | 317219.311 | 87724.571 | 87724.571 | 229494.740 |
December | 0.467614E+12 | 408138.570 | 09-DEC-08:30 | 0.000 | 0.000 | 0.000 | 408138.570 | 88159.495 | 88159.495 | 319979.074 |
Annual Sum or Average | 0.285600E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.956936E+11 | 83128.421 | 0.000 | 0.000 | 0.000 | 83128.421 | 82944.608 | 82944.608 | 0.000 | |
Maximum of Months | 0.560312E+12 | 408138.570 | 0.000 | 0.000 | 0.000 | 408138.570 | 93320.149 | 93320.149 | 319979.074 |