Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Great Falls Intl Arpt MT USA TMY3 WMO#=727750

Simulation Timestamp: 2018-10-19 09:40:08


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 5182.98 661.39 734.14
Net Site Energy 5182.98 661.39 734.14
Total Source Energy 11871.33 1514.88 1681.52
Net Source Energy 11871.33 1514.88 1681.52


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 263.76 902.48 0.00 0.00 0.00 0.00
Cooling 245.02 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.22 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 702.48 0.00 0.00 0.00 0.00 0.00
Pumps 45.41 0.00 0.00 0.00 0.00 0.00
Heat Rejection 8.68 0.00 0.00 0.00 0.00 864.78
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1278.59 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3001.91 2181.08 0.00 0.00 0.00 5643.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 902.48 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 263.76 0.00 0.00 0.00 0.00 0.00
Cooling General 245.02 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.22 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 702.48 0.00 0.00 0.00 0.00 0.00
Pumps General 45.41 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 8.68 0.00 0.00 0.00 0.00 864.78
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1278.59 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.81 0.00 0.00 0.00 0.00 0.00
HVAC 179.23 308.94 0.00 0.00 0.00 0.80
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 425.21 308.94 0.00 0.00 0.00 0.80


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.60 0.00 0.00 0.00 0.00 0.00
HVAC 161.47 278.32 0.00 0.00 0.00 0.72
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 383.07 278.32 0.00 0.00 0.00 0.72


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3001.91 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3001.91 100.00
     
Total On-Site and Utility Electric Sources 3001.91 100.00
Total Electricity End Uses 3001.91 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5643.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5643.30 100.00
Total Water End Uses 5643.30 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 143.00
Time Setpoint Not Met During Occupied Cooling 147.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2316.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Latitude [deg] 47.47
Longitude [deg] -111.4
Elevation [m] 1117.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 05-JAN-19:00 06-JAN-06:45 - - - 17-JUL-17:45
Heating 73815.64 231254.76 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51564.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 22275.35 0.00 0.00 0.00 0.00 0.00
Pumps 1453.23 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 87362.79 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 185892.94 318617.55 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 231254.76 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 51564.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 22275.35 0.00 0.00 0.00 0.00 0.00
Pumps General 1453.23 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 87362.79 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 835.33 978.29 0.00 0.00 0.00
Cooling 775.99 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 532.77 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2224.74 0.00 0.00 0.00 0.00
Pumps 143.83 0.00 0.00 0.00 0.00
Heat Rejection 27.49 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1386.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9507.04 2364.29 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 118.32 138.57 0.00 0.00 0.00
Cooling 109.91 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.46 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 315.12 0.00 0.00 0.00 0.00
Pumps 20.37 0.00 0.00 0.00 0.00
Heat Rejection 3.89 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 196.32 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1346.63 334.89 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 118.32 138.57 0.00 0.00 0.00
Cooling 109.91 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.46 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 315.12 0.00 0.00 0.00 0.00
Pumps 20.37 0.00 0.00 0.00 0.00
Heat Rejection 3.89 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 196.32 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1346.63 334.89 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB -27.60 0.00 -27.60 Wetbulb [C] 2.70 230.00
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 33.40 16.00 16.30 Wetbulb [C] 4.90 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.36 0.00 0.00 3.36 3.36 2.653 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.653 0.426 0.308              
North Total or Average           423.59 2.653 0.426 0.308              
Non-North Total or Average           726.80 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.60 83.60 168.22
Exterior Lighting Total 10720.10           168.22



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 255302.01 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 204241.61      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3321.43 2275.47 1045.96 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   2949.73 2029.06 920.67 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4577.95 3120.77 1457.18 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2081.33 1451.43 629.90 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1401.26 982.07 419.19 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1382.83 969.98 412.85 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2254.65 1527.00 727.66 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2330.41 1578.49 751.91 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4333.48 2969.14 1364.34 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3817.10 2623.83 1193.27 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4220.88 2879.05 1341.82 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2777.95 1932.30 845.66 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1970.77 1369.60 601.17 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1948.47 1354.58 593.89 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2964.33 2014.00 950.33 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2994.12 2034.22 959.90 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4338.86 2977.99 1360.88 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3842.03 2645.89 1196.14 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4016.05 2745.17 1270.88 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2824.91 1969.13 855.78 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2023.57 1408.16 615.42 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2001.49 1393.28 608.21 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3011.76 2049.21 962.55 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3027.15 2059.66 967.49 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4340.46 2982.97 1357.50 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3857.98 2659.91 1198.07 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4004.06 2740.82 1263.23 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2850.73 1986.09 864.64 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2040.22 1421.62 618.60 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2018.24 1406.81 611.44 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3024.55 2060.16 964.39 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3037.94 2069.24 968.70 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4373.53 3008.55 1364.98 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3896.13 2688.92 1207.22 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4047.10 2771.69 1275.41 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2889.37 2015.33 874.04 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2083.34 1452.51 630.82 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2061.46 1437.75 623.71 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3064.80 2089.34 975.46 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3077.88 2098.22 979.66 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4315.91 2972.23 1343.68 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3840.33 2653.84 1186.49 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3996.27 2739.80 1256.46 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2836.62 1982.01 854.60 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2035.60 1421.90 613.70 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2013.91 1407.26 606.65 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3014.15 2056.52 957.64 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3027.21 2065.38 961.83 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4292.82 2958.96 1333.85 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3819.94 2642.41 1177.53 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3979.05 2730.42 1248.63 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2817.98 1971.56 846.42 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2020.84 1413.32 607.52 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1999.30 1398.78 600.52 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2996.62 2045.99 950.63 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3009.66 2054.84 954.82 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4288.38 2958.09 1330.29 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3818.16 2643.33 1174.83 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3978.66 2732.22 1246.44 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2816.33 1972.42 843.91 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2024.36 1416.91 607.45 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2002.99 1402.48 600.51 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2996.17 2046.93 949.24 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3009.25 2055.81 953.44 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4410.10 3042.56 1367.54 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3935.64 2724.88 1210.76 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4061.64 2790.51 1271.13 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2848.25 1995.97 852.28 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2130.01 1489.31 640.70 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2108.40 1474.71 633.69 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3065.43 2095.16 970.27 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3080.16 2105.16 975.00 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5444.80 3736.06 1708.74 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4746.24 3270.83 1475.41 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4976.68 3415.03 1561.65 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3521.11 2448.04 1073.07 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2774.22 1901.55 872.67 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2774.49 1900.02 874.46 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4141.10 2826.61 1314.50 0.68 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4155.52 2836.38 1319.14 0.68 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3321.43 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   2949.73 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4577.95 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2081.33 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1401.26 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1382.83 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2254.65 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2330.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4333.48 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3817.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4220.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2777.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1970.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1948.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2964.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2994.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4338.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3842.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4016.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2824.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2023.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2001.49 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3011.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3027.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4340.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3857.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4004.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2850.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2040.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2018.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3024.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3037.94 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4373.53 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   3896.13 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4047.10 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   2889.37 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2083.34 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2061.46 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3064.80 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3077.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4315.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3840.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3996.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2836.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2035.60 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2013.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3014.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3027.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4292.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3819.94 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3979.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2817.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2020.84 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1999.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2996.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3009.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4288.38 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3818.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3978.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2816.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2024.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2002.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2996.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3009.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4410.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3935.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4061.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2848.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2130.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2108.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3065.43 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3080.16 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5444.80 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   4746.24 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4976.68 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   3521.11 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2774.22 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2774.49 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4141.10 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4155.52 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   4534.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   4551.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   5645.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   4557.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   3509.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   3509.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   3490.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   3498.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   4373.81 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   4380.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   4403.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   4386.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   3123.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   3124.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   3120.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   3121.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   4357.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   4363.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   4363.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   4367.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   3065.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   3065.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   3060.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   3060.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   4415.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   4420.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   4417.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   4421.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   3086.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   3086.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   3082.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   3082.45 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   4450.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   4451.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   4450.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   4451.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   3090.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   3090.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   3089.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   3089.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   4551.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   4552.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   4550.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   4551.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   3164.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   3164.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   3165.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   3165.06 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   4621.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   4620.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   4619.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   4618.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   3211.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   3211.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   3213.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   3213.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   4699.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   4695.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   4696.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   4692.78 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   3268.80 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   3268.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   3273.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   3273.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   4961.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   4952.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   4957.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   4948.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   3496.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   3496.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   3506.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   3505.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   5962.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   5961.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   5958.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   5957.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   4570.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   4570.58 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   4568.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   4568.76 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 289.74 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 259.97 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 390.55 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 185.29 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 126.26 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.11 124.70 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.73 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.39 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 380.10 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 337.48 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 363.90 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 248.24 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 176.61 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 174.66 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 250.97 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.59 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 381.51 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 340.61 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.81 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.27 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 181.75 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 179.83 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.68 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 257.04 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 382.36 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 341.86 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.44 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.73 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 183.61 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 181.69 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 257.22 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.39 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 385.84 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.79 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 350.30 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.68 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 187.70 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 185.79 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 261.09 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 262.24 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 381.27 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 341.38 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.30 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 254.48 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 183.82 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 181.92 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.92 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 258.07 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 379.67 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 340.02 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.20 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.23 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 182.78 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 180.89 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.63 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.78 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.34 379.67 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 340.25 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.54 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 253.44 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 183.30 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 181.43 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 255.82 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.97 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 390.73 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 350.92 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 353.20 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 256.59 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 192.74 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 190.85 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.23 262.12 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 263.42 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 477.02 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 419.88 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.39 434.59 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.28 313.84 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.80 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.25 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 356.96 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 358.23 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0056 1416.30 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2407.53 2889.03 0.216 0.259 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
G NW APARTMENT 2160.14 2592.17 0.193 0.232 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 28.36 0.00627
OFFICE 3245.23 3894.27 0.291 0.349 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.20 0.00627
G NE APARTMENT 1493.24 1791.88 0.134 0.160 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 28.52 0.00627
G N1 APARTMENT 1049.12 1258.94 0.094 0.113 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
G N2 APARTMENT 1029.64 1235.57 0.092 0.111 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
G S1 APARTMENT 1559.88 1871.86 0.140 0.168 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
G S2 APARTMENT 1615.18 1938.21 0.145 0.174 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
F2 SW APARTMENT 3158.31 3789.97 0.283 0.339 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F2 NW APARTMENT 2804.16 3365.00 0.251 0.301 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 28.36 0.00627
F2 SE APARTMENT 3023.75 3628.50 0.271 0.325 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.20 0.00627
F2 NE APARTMENT 2062.67 2475.20 0.185 0.222 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 28.52 0.00627
F2 N1 APARTMENT 1467.45 1760.94 0.131 0.158 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F2 N2 APARTMENT 1451.30 1741.56 0.130 0.156 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F2 S1 APARTMENT 2085.38 2502.45 0.187 0.224 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F2 S2 APARTMENT 2107.12 2528.55 0.189 0.226 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F3 SW APARTMENT 3170.09 3804.11 0.284 0.341 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F3 NW APARTMENT 2830.17 3396.20 0.253 0.304 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 28.36 0.00627
F3 SE APARTMENT 2881.75 3458.10 0.258 0.310 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.20 0.00627
F3 NE APARTMENT 2104.49 2525.38 0.188 0.226 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 28.52 0.00627
F3 N1 APARTMENT 1510.19 1812.23 0.135 0.162 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F3 N2 APARTMENT 1494.19 1793.03 0.134 0.161 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F3 S1 APARTMENT 2124.54 2549.45 0.190 0.228 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F3 S2 APARTMENT 2135.78 2562.93 0.191 0.229 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F4 SW APARTMENT 3177.14 3812.57 0.284 0.341 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F4 NW APARTMENT 2840.63 3408.75 0.254 0.305 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
F4 SE APARTMENT 2878.71 3454.45 0.258 0.309 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.20 0.00627
F4 NE APARTMENT 2116.64 2539.97 0.190 0.227 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
F4 N1 APARTMENT 1525.63 1830.76 0.137 0.164 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F4 N2 APARTMENT 1509.69 1811.63 0.135 0.162 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F4 S1 APARTMENT 2137.30 2564.76 0.191 0.230 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F4 S2 APARTMENT 2147.07 2576.48 0.192 0.231 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
M SW APARTMENT 3206.08 3847.29 0.287 0.344 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
M NW APARTMENT 2873.24 3447.89 0.257 0.309 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
M SE APARTMENT 2910.77 3492.93 0.261 0.313 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
M NE APARTMENT 2149.43 2579.32 0.192 0.231 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
M N1 APARTMENT 1559.64 1871.56 0.140 0.168 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
M N2 APARTMENT 1543.76 1852.51 0.138 0.166 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
M S1 APARTMENT 2169.49 2603.39 0.194 0.233 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
M S2 APARTMENT 2179.04 2614.85 0.195 0.234 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F6 SW APARTMENT 3168.11 3801.73 0.284 0.340 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F6 NW APARTMENT 2836.61 3403.93 0.254 0.305 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
F6 SE APARTMENT 2877.56 3453.07 0.258 0.309 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
F6 NE APARTMENT 2114.56 2537.48 0.189 0.227 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
F6 N1 APARTMENT 1527.37 1832.85 0.137 0.164 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F6 N2 APARTMENT 1511.62 1813.95 0.135 0.162 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F6 S1 APARTMENT 2134.86 2561.83 0.191 0.229 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F6 S2 APARTMENT 2144.39 2573.27 0.192 0.230 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F7 SW APARTMENT 3154.83 3785.80 0.282 0.339 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F7 NW APARTMENT 2825.31 3390.37 0.253 0.304 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
F7 SE APARTMENT 2868.44 3442.12 0.257 0.308 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
F7 NE APARTMENT 2104.22 2525.06 0.188 0.226 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
F7 N1 APARTMENT 1518.72 1822.46 0.136 0.163 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F7 N2 APARTMENT 1503.07 1803.68 0.135 0.161 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F7 S1 APARTMENT 2124.13 2548.95 0.190 0.228 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F7 S2 APARTMENT 2133.65 2560.38 0.191 0.229 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F8 SW APARTMENT 3154.81 3785.78 0.282 0.339 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F8 NW APARTMENT 2827.21 3392.65 0.253 0.304 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
F8 SE APARTMENT 2871.27 3445.53 0.257 0.308 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
F8 NE APARTMENT 2105.98 2527.18 0.189 0.226 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
F8 N1 APARTMENT 1523.10 1827.73 0.136 0.164 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F8 N2 APARTMENT 1507.57 1809.08 0.135 0.162 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F8 S1 APARTMENT 2125.67 2550.81 0.190 0.228 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F8 S2 APARTMENT 2135.23 2562.27 0.191 0.229 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F9 SW APARTMENT 3246.69 3896.03 0.291 0.349 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 29.96 0.00627
F9 NW APARTMENT 2915.93 3499.12 0.261 0.313 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 28.96 0.00627
F9 SE APARTMENT 2934.90 3521.88 0.263 0.315 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
F9 NE APARTMENT 2132.16 2558.60 0.191 0.229 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.12 0.00627
F9 N1 APARTMENT 1601.49 1921.79 0.143 0.172 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F9 N2 APARTMENT 1585.77 1902.93 0.142 0.170 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
F9 S1 APARTMENT 2178.07 2613.69 0.195 0.234 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
F9 S2 APARTMENT 2188.83 2626.60 0.196 0.235 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
T SW APARTMENT 3963.80 4756.56 0.355 0.426 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 32.68 0.00627
T NW APARTMENT 3488.94 4186.72 0.312 0.375 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36 0.00627
T SE APARTMENT 3611.24 4333.49 0.323 0.388 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.20 0.00627
T NE APARTMENT 2607.84 3129.41 0.233 0.280 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 30.12 0.00627
T N1 APARTMENT 1975.93 2371.11 0.177 0.212 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 32.92 0.00627
T N2 APARTMENT 1971.39 2365.66 0.177 0.212 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 33.16 0.00627
T S1 APARTMENT 2966.09 3559.31 0.266 0.319 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
T S2 APARTMENT 2976.62 3571.94 0.267 0.320 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2689.26 3227.12 0.137 0.164 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
G NW APARTMENT 2703.84 3244.61 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
OFFICE 3093.10 3711.72 0.157 0.189 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -27.60 0.00034
G NE APARTMENT 2709.22 3251.07 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
G N1 APARTMENT 1823.09 2187.70 0.093 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
G N2 APARTMENT 1823.20 2187.85 0.093 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
G S1 APARTMENT 1806.35 2167.62 0.092 0.110 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
G S2 APARTMENT 1813.63 2176.36 0.092 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
F2 SW APARTMENT 2553.75 3064.50 0.130 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 NW APARTMENT 2559.58 3071.49 0.130 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 SE APARTMENT 2578.84 3094.61 0.131 0.157 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 NE APARTMENT 2564.07 3076.88 0.130 0.157 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 N1 APARTMENT 1496.74 1796.09 0.076 0.091 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 N2 APARTMENT 1496.84 1796.21 0.076 0.091 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 S1 APARTMENT 1493.49 1792.19 0.076 0.091 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F2 S2 APARTMENT 1494.84 1793.81 0.076 0.091 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 SW APARTMENT 2539.78 3047.73 0.129 0.155 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 NW APARTMENT 2545.33 3054.40 0.130 0.155 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 SE APARTMENT 2544.70 3053.64 0.129 0.155 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 NE APARTMENT 2548.19 3057.83 0.130 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 N1 APARTMENT 1447.37 1736.85 0.074 0.088 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 N2 APARTMENT 1447.44 1736.93 0.074 0.088 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 S1 APARTMENT 1442.71 1731.26 0.073 0.088 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F3 S2 APARTMENT 1442.96 1731.55 0.073 0.088 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 SW APARTMENT 2588.92 3106.71 0.132 0.158 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 NW APARTMENT 2592.97 3111.56 0.132 0.158 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 SE APARTMENT 2590.58 3108.69 0.132 0.158 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 NE APARTMENT 2594.43 3113.31 0.132 0.158 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 N1 APARTMENT 1465.04 1758.04 0.075 0.089 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 N2 APARTMENT 1465.07 1758.08 0.075 0.089 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 S1 APARTMENT 1461.65 1753.98 0.074 0.089 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F4 S2 APARTMENT 1461.70 1754.04 0.074 0.089 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M SW APARTMENT 2618.21 3141.85 0.133 0.160 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M NW APARTMENT 2619.58 3143.49 0.133 0.160 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M SE APARTMENT 2618.47 3142.16 0.133 0.160 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M NE APARTMENT 2619.82 3143.78 0.133 0.160 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M N1 APARTMENT 1468.09 1761.70 0.075 0.090 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M N2 APARTMENT 1468.09 1761.71 0.075 0.090 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M S1 APARTMENT 1467.38 1760.86 0.075 0.090 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
M S2 APARTMENT 1467.39 1760.87 0.075 0.090 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 SW APARTMENT 2704.00 3244.80 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 NW APARTMENT 2704.53 3245.43 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 SE APARTMENT 2703.17 3243.81 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 NE APARTMENT 2703.70 3244.44 0.138 0.165 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 N1 APARTMENT 1531.48 1837.77 0.078 0.094 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 N2 APARTMENT 1531.46 1837.75 0.078 0.094 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 S1 APARTMENT 1531.58 1837.90 0.078 0.094 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F6 S2 APARTMENT 1531.56 1837.87 0.078 0.094 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 SW APARTMENT 2763.25 3315.90 0.141 0.169 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 NW APARTMENT 2762.07 3314.49 0.141 0.169 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 SE APARTMENT 2761.47 3313.76 0.140 0.169 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 NE APARTMENT 2760.29 3312.35 0.140 0.169 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 N1 APARTMENT 1571.04 1885.25 0.080 0.096 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 N2 APARTMENT 1571.00 1885.20 0.080 0.096 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 S1 APARTMENT 1572.88 1887.45 0.080 0.096 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F7 S2 APARTMENT 1572.84 1887.41 0.080 0.096 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 SW APARTMENT 2829.21 3395.05 0.144 0.173 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 NW APARTMENT 2826.15 3391.38 0.144 0.173 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 SE APARTMENT 2826.57 3391.88 0.144 0.173 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 NE APARTMENT 2823.51 3388.21 0.144 0.172 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 N1 APARTMENT 1619.30 1943.16 0.082 0.099 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 N2 APARTMENT 1619.24 1943.09 0.082 0.099 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 S1 APARTMENT 1623.04 1947.65 0.083 0.099 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F8 S2 APARTMENT 1622.98 1947.58 0.083 0.099 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 SW APARTMENT 3050.95 3661.14 0.155 0.186 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 NW APARTMENT 3042.89 3651.47 0.155 0.186 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 SE APARTMENT 3047.49 3656.99 0.155 0.186 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 NE APARTMENT 3039.43 3647.32 0.155 0.186 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 N1 APARTMENT 1811.56 2173.87 0.092 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 N2 APARTMENT 1811.48 2173.78 0.092 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 S1 APARTMENT 1819.95 2183.94 0.093 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
F9 S2 APARTMENT 1819.87 2183.84 0.093 0.111 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T SW APARTMENT 3897.38 4676.85 0.198 0.238 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T NW APARTMENT 3896.82 4676.19 0.198 0.238 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T SE APARTMENT 3893.54 4672.24 0.198 0.238 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T NE APARTMENT 3892.98 4671.58 0.198 0.238 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T N1 APARTMENT 2720.25 3264.29 0.138 0.166 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T N2 APARTMENT 2720.15 3264.19 0.138 0.166 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T S1 APARTMENT 2718.70 3262.44 0.138 0.166 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034
T S2 APARTMENT 2718.61 3262.33 0.138 0.166 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -27.60 0.00034


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.26 0.26 0.16 0.16
AIRLOOP G NW 0.23 0.23 0.17 0.17
AIRLOOP OFFICE 0.35 0.35 0.19 0.19
AIRLOOP G NE 0.16 0.16 0.17 0.17
AIRLOOP G N1 0.11 0.11 0.11 0.11
AIRLOOP G N2 0.11 0.11 0.11 0.11
AIRLOOP G S1 0.17 0.17 0.11 0.11
AIRLOOP G S2 0.17 0.17 0.11 0.11
AIRLOOP F2 SW 0.34 0.34 0.16 0.16
AIRLOOP F2 NW 0.30 0.30 0.16 0.16
AIRLOOP F2 SE 0.32 0.32 0.16 0.16
AIRLOOP F2 NE 0.22 0.22 0.16 0.16
AIRLOOP F2 N1 0.16 0.16 0.09 0.09
AIRLOOP F2 N2 0.16 0.16 0.09 0.09
AIRLOOP F2 S1 0.22 0.22 0.09 0.09
AIRLOOP F2 S2 0.23 0.23 0.09 0.09
AIRLOOP F3 SW 0.34 0.34 0.16 0.16
AIRLOOP F3 NW 0.30 0.30 0.16 0.16
AIRLOOP F3 SE 0.31 0.31 0.16 0.16
AIRLOOP F3 NE 0.23 0.23 0.16 0.16
AIRLOOP F3 N1 0.16 0.16 0.09 0.09
AIRLOOP F3 N2 0.16 0.16 0.09 0.09
AIRLOOP F3 S1 0.23 0.23 0.09 0.09
AIRLOOP F3 S2 0.23 0.23 0.09 0.09
AIRLOOP F4 SW 0.34 0.34 0.16 0.16
AIRLOOP F4 NW 0.31 0.31 0.16 0.16
AIRLOOP F4 SE 0.31 0.31 0.16 0.16
AIRLOOP F4 NE 0.23 0.23 0.16 0.16
AIRLOOP F4 N1 0.16 0.16 0.09 0.09
AIRLOOP F4 N2 0.16 0.16 0.09 0.09
AIRLOOP F4 S1 0.23 0.23 0.09 0.09
AIRLOOP F4 S2 0.23 0.23 0.09 0.09
AIRLOOP M SW 0.34 0.34 0.16 0.16
AIRLOOP M NW 0.31 0.31 0.16 0.16
AIRLOOP M SE 0.31 0.31 0.16 0.16
AIRLOOP M NE 0.23 0.23 0.16 0.16
AIRLOOP M N1 0.17 0.17 0.09 0.09
AIRLOOP M N2 0.17 0.17 0.09 0.09
AIRLOOP M S1 0.23 0.23 0.09 0.09
AIRLOOP M S2 0.23 0.23 0.09 0.09
AIRLOOP F6 SW 0.34 0.34 0.17 0.17
AIRLOOP F6 NW 0.30 0.30 0.17 0.17
AIRLOOP F6 SE 0.31 0.31 0.17 0.17
AIRLOOP F6 NE 0.23 0.23 0.17 0.17
AIRLOOP F6 N1 0.16 0.16 0.09 0.09
AIRLOOP F6 N2 0.16 0.16 0.09 0.09
AIRLOOP F6 S1 0.23 0.23 0.09 0.09
AIRLOOP F6 S2 0.23 0.23 0.09 0.09
AIRLOOP F7 SW 0.34 0.34 0.17 0.17
AIRLOOP F7 NW 0.30 0.30 0.17 0.17
AIRLOOP F7 SE 0.31 0.31 0.17 0.17
AIRLOOP F7 NE 0.23 0.23 0.17 0.17
AIRLOOP F7 N1 0.16 0.16 0.10 0.10
AIRLOOP F7 N2 0.16 0.16 0.10 0.10
AIRLOOP F7 S1 0.23 0.23 0.10 0.10
AIRLOOP F7 S2 0.23 0.23 0.10 0.10
AIRLOOP F8 SW 0.34 0.34 0.17 0.17
AIRLOOP F8 NW 0.30 0.30 0.17 0.17
AIRLOOP F8 SE 0.31 0.31 0.17 0.17
AIRLOOP F8 NE 0.23 0.23 0.17 0.17
AIRLOOP F8 N1 0.16 0.16 0.10 0.10
AIRLOOP F8 N2 0.16 0.16 0.10 0.10
AIRLOOP F8 S1 0.23 0.23 0.10 0.10
AIRLOOP F8 S2 0.23 0.23 0.10 0.10
AIRLOOP F9 SW 0.35 0.35 0.19 0.19
AIRLOOP F9 NW 0.31 0.31 0.19 0.19
AIRLOOP F9 SE 0.32 0.32 0.19 0.19
AIRLOOP F9 NE 0.23 0.23 0.19 0.19
AIRLOOP F9 N1 0.17 0.17 0.11 0.11
AIRLOOP F9 N2 0.17 0.17 0.11 0.11
AIRLOOP F9 S1 0.23 0.23 0.11 0.11
AIRLOOP F9 S2 0.24 0.24 0.11 0.11
AIRLOOP T SW 0.43 0.43 0.24 0.24
AIRLOOP T NW 0.37 0.37 0.24 0.24
AIRLOOP T SE 0.39 0.39 0.24 0.24
AIRLOOP T NE 0.28 0.28 0.24 0.24
AIRLOOP T N1 0.21 0.21 0.17 0.17
AIRLOOP T N2 0.21 0.21 0.17 0.17
AIRLOOP T S1 0.32 0.32 0.17 0.17
AIRLOOP T S2 0.32 0.32 0.17 0.17



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2279.00 6122.50 861.75
G NW APARTMENT 2351.50 6766.50 1344.75
OFFICE 789.00 1208.00 161.25
G NE APARTMENT 2482.50 6819.50 1386.00
G N1 APARTMENT 1550.75 7045.50 847.25
G N2 APARTMENT 1554.00 7043.25 849.00
G S1 APARTMENT 1670.75 6265.75 465.00
G S2 APARTMENT 1695.00 6213.00 455.25
F2 SW APARTMENT 2626.25 5052.50 530.50
F2 NW APARTMENT 2447.75 6122.25 902.50
F2 SE APARTMENT 2753.25 4896.00 496.25
F2 NE APARTMENT 2528.50 6219.50 912.25
F2 N1 APARTMENT 1664.50 6375.25 377.00
F2 N2 APARTMENT 1667.50 6383.50 376.25
F2 S1 APARTMENT 2174.75 4875.75 177.75
F2 S2 APARTMENT 2196.25 4845.75 176.25
F3 SW APARTMENT 2688.25 4917.25 491.00
F3 NW APARTMENT 2471.25 6032.25 854.75
F3 SE APARTMENT 2752.00 4873.50 488.00
F3 NE APARTMENT 2531.75 6118.25 866.25
F3 N1 APARTMENT 1699.50 6234.50 315.75
F3 N2 APARTMENT 1705.50 6238.25 316.25
F3 S1 APARTMENT 2315.25 4598.00 146.50
F3 S2 APARTMENT 2322.00 4584.50 146.00
F4 SW APARTMENT 2693.50 4936.75 498.25
F4 NW APARTMENT 2489.50 6029.75 866.50
F4 SE APARTMENT 2754.25 4911.50 497.25
F4 NE APARTMENT 2548.25 6108.00 874.75
F4 N1 APARTMENT 1720.50 6203.50 313.75
F4 N2 APARTMENT 1723.25 6205.50 314.50
F4 S1 APARTMENT 2337.50 4570.00 144.00
F4 S2 APARTMENT 2346.50 4565.25 144.00
M SW APARTMENT 2686.50 4962.25 496.25
M NW APARTMENT 2489.50 6038.50 856.25
M SE APARTMENT 2746.25 4948.25 495.00
M NE APARTMENT 2545.00 6111.75 860.75
M N1 APARTMENT 1727.75 6192.25 301.50
M N2 APARTMENT 1735.25 6195.75 302.75
M S1 APARTMENT 2344.50 4573.50 138.50
M S2 APARTMENT 2350.50 4567.75 138.75
F6 SW APARTMENT 2609.50 5122.25 544.25
F6 NW APARTMENT 2463.50 6140.50 921.25
F6 SE APARTMENT 2662.75 5111.50 543.25
F6 NE APARTMENT 2522.50 6217.25 929.75
F6 N1 APARTMENT 1669.25 6301.00 342.25
F6 N2 APARTMENT 1674.25 6308.75 343.25
F6 S1 APARTMENT 2216.75 4773.50 155.00
F6 S2 APARTMENT 2223.25 4765.75 155.50
F7 SW APARTMENT 2567.00 5247.00 572.50
F7 NW APARTMENT 2445.50 6217.50 956.75
F7 SE APARTMENT 2619.00 5224.00 574.75
F7 NE APARTMENT 2512.50 6292.25 964.00
F7 N1 APARTMENT 1645.50 6365.25 368.25
F7 N2 APARTMENT 1649.50 6370.25 369.50
F7 S1 APARTMENT 2133.75 4916.25 168.00
F7 S2 APARTMENT 2141.50 4912.75 167.50
F8 SW APARTMENT 2531.50 5362.50 601.50
F8 NW APARTMENT 2451.75 6266.75 993.75
F8 SE APARTMENT 2594.50 5326.00 603.50
F8 NE APARTMENT 2508.75 6347.50 996.25
F8 N1 APARTMENT 1640.00 6427.75 398.50
F8 N2 APARTMENT 1644.75 6433.00 398.00
F8 S1 APARTMENT 2075.75 5051.50 183.75
F8 S2 APARTMENT 2085.00 5042.50 184.25
F9 SW APARTMENT 2564.75 5509.00 706.50
F9 NW APARTMENT 2565.50 6335.75 1132.75
F9 SE APARTMENT 2626.50 5477.00 703.75
F9 NE APARTMENT 2636.50 6407.25 1149.25
F9 N1 APARTMENT 1768.75 6499.75 549.25
F9 N2 APARTMENT 1774.50 6503.00 551.00
F9 S1 APARTMENT 2054.50 5243.75 261.50
F9 S2 APARTMENT 2065.50 5234.25 262.00
T SW APARTMENT 3380.75 5823.00 1591.00
T NW APARTMENT 3506.50 6515.50 2158.00
T SE APARTMENT 3458.50 5748.75 1583.00
T NE APARTMENT 3590.75 6578.50 2169.25
T N1 APARTMENT 2597.25 6688.75 1401.50
T N2 APARTMENT 2606.00 6685.75 1402.25
T S1 APARTMENT 2669.00 5614.25 924.00
T S2 APARTMENT 2678.00 5604.50 923.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5021.00 7208.75 2316.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.25 38.00 3.25 38.00
G NW APARTMENT 2.75 10.75 2.75 10.75
OFFICE 2.25 9.75 0.25 9.75
G NE APARTMENT 4.00 16.25 4.00 16.25
G N1 APARTMENT 4.00 36.50 4.00 36.50
G N2 APARTMENT 3.25 39.00 3.25 39.00
G S1 APARTMENT 5.00 43.00 5.00 43.00
G S2 APARTMENT 4.25 35.25 4.25 35.25
F2 SW APARTMENT 2.25 17.00 2.25 17.00
F2 NW APARTMENT 0.50 7.25 0.50 7.25
F2 SE APARTMENT 1.00 2.75 1.00 2.75
F2 NE APARTMENT 2.00 19.50 2.00 19.50
F2 N1 APARTMENT 4.00 22.75 4.00 22.75
F2 N2 APARTMENT 3.50 24.75 3.50 24.75
F2 S1 APARTMENT 2.25 39.75 2.25 39.75
F2 S2 APARTMENT 2.25 36.75 2.25 36.75
F3 SW APARTMENT 1.00 22.75 1.00 22.75
F3 NW APARTMENT 0.25 8.25 0.25 8.25
F3 SE APARTMENT 0.25 16.25 0.25 16.25
F3 NE APARTMENT 2.75 26.75 2.75 26.75
F3 N1 APARTMENT 4.75 27.00 4.75 27.00
F3 N2 APARTMENT 5.00 30.50 5.00 30.50
F3 S1 APARTMENT 2.50 42.25 2.50 42.25
F3 S2 APARTMENT 2.25 41.75 2.25 41.75
F4 SW APARTMENT 0.00 25.75 0.00 25.75
F4 NW APARTMENT 1.50 9.00 1.50 9.00
F4 SE APARTMENT 1.00 20.75 1.00 20.75
F4 NE APARTMENT 4.50 29.50 4.50 29.50
F4 N1 APARTMENT 4.50 29.50 4.50 29.50
F4 N2 APARTMENT 4.50 34.50 4.50 34.50
F4 S1 APARTMENT 2.25 43.50 2.25 43.50
F4 S2 APARTMENT 2.25 42.25 2.25 42.25
M SW APARTMENT 0.75 28.25 0.75 28.25
M NW APARTMENT 0.00 10.00 0.00 10.00
M SE APARTMENT 0.25 21.00 0.25 21.00
M NE APARTMENT 1.75 33.50 1.75 33.50
M N1 APARTMENT 3.50 32.25 3.50 32.25
M N2 APARTMENT 5.00 37.75 5.00 37.75
M S1 APARTMENT 3.00 43.75 3.00 43.75
M S2 APARTMENT 2.25 42.50 2.25 42.50
F6 SW APARTMENT 1.75 30.00 1.75 30.00
F6 NW APARTMENT 0.75 10.50 0.75 10.50
F6 SE APARTMENT 0.50 22.75 0.50 22.75
F6 NE APARTMENT 2.75 39.50 2.75 39.50
F6 N1 APARTMENT 6.25 35.50 6.25 35.50
F6 N2 APARTMENT 5.25 40.25 5.25 40.25
F6 S1 APARTMENT 2.50 44.25 2.50 44.25
F6 S2 APARTMENT 3.00 43.00 3.00 43.00
F7 SW APARTMENT 0.75 31.75 0.75 31.75
F7 NW APARTMENT 0.25 10.75 0.25 10.75
F7 SE APARTMENT 1.50 23.25 1.50 23.25
F7 NE APARTMENT 2.00 43.00 2.00 43.00
F7 N1 APARTMENT 4.50 37.75 4.50 37.75
F7 N2 APARTMENT 3.25 42.25 3.25 42.25
F7 S1 APARTMENT 4.00 44.25 4.00 44.25
F7 S2 APARTMENT 4.50 42.75 4.50 42.75
F8 SW APARTMENT 0.50 32.25 0.50 32.25
F8 NW APARTMENT 0.00 12.00 0.00 12.00
F8 SE APARTMENT 0.50 23.00 0.50 23.00
F8 NE APARTMENT 1.25 47.00 1.25 47.00
F8 N1 APARTMENT 4.75 39.50 4.75 39.50
F8 N2 APARTMENT 3.75 43.75 3.75 43.75
F8 S1 APARTMENT 2.75 42.75 2.75 42.75
F8 S2 APARTMENT 3.25 41.75 3.25 41.75
F9 SW APARTMENT 0.75 27.00 0.75 27.00
F9 NW APARTMENT 0.00 11.25 0.00 11.25
F9 SE APARTMENT 0.75 22.00 0.75 22.00
F9 NE APARTMENT 1.00 59.50 1.00 59.50
F9 N1 APARTMENT 2.25 32.75 2.25 32.75
F9 N2 APARTMENT 3.25 34.75 3.25 34.75
F9 S1 APARTMENT 2.75 37.00 2.75 37.00
F9 S2 APARTMENT 4.75 35.00 4.75 35.00
T SW APARTMENT 0.00 15.50 0.00 15.50
T NW APARTMENT 0.00 17.75 0.00 17.75
T SE APARTMENT 0.00 14.00 0.00 14.00
T NE APARTMENT 0.25 36.50 0.25 36.50
T N1 APARTMENT 2.75 32.00 2.75 32.00
T N2 APARTMENT 1.50 29.50 1.50 29.50
T S1 APARTMENT 0.50 16.00 0.50 16.00
T S2 APARTMENT 0.50 16.00 0.50 16.00
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 144.75 147.50 143.00 147.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.353 0.133 0.000 0.260
G NW APARTMENT 1.71 2.50 268.96 0.353 0.132 0.000 0.254
OFFICE 0.94 1.00 268.96 0.518 0.151 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.353 0.132 0.000 0.254
G N1 APARTMENT 1.71 2.50 268.96 0.353 0.080 0.000 0.249
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.249
G S1 APARTMENT 1.71 2.50 268.96 0.353 0.080 0.000 0.258
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.080 0.000 0.258
F2 SW APARTMENT 1.71 2.50 268.96 0.353 0.191 0.000 0.312
F2 NW APARTMENT 1.71 2.50 268.96 0.353 0.190 0.000 0.307
F2 SE APARTMENT 1.71 2.50 268.96 0.353 0.191 0.000 0.313
F2 NE APARTMENT 1.71 2.50 268.96 0.353 0.190 0.000 0.307
F2 N1 APARTMENT 1.71 2.50 268.96 0.353 0.115 0.000 0.303
F2 N2 APARTMENT 1.71 2.50 268.97 0.353 0.115 0.000 0.303
F2 S1 APARTMENT 1.71 2.50 268.96 0.354 0.115 0.000 0.311
F2 S2 APARTMENT 1.71 2.50 268.97 0.354 0.115 0.000 0.311
F3 SW APARTMENT 1.71 2.50 268.96 0.353 0.226 0.000 0.346
F3 NW APARTMENT 1.71 2.50 268.96 0.353 0.225 0.000 0.342
F3 SE APARTMENT 1.71 2.50 268.96 0.353 0.226 0.000 0.347
F3 NE APARTMENT 1.71 2.50 268.96 0.353 0.225 0.000 0.342
F3 N1 APARTMENT 1.71 2.50 268.96 0.353 0.136 0.000 0.339
F3 N2 APARTMENT 1.71 2.50 268.97 0.353 0.136 0.000 0.339
F3 S1 APARTMENT 1.71 2.50 268.96 0.354 0.136 0.000 0.345
F3 S2 APARTMENT 1.71 2.50 268.97 0.354 0.136 0.000 0.345
F4 SW APARTMENT 1.71 2.50 268.96 0.353 0.252 0.000 0.361
F4 NW APARTMENT 1.71 2.50 268.96 0.353 0.252 0.000 0.358
F4 SE APARTMENT 1.71 2.50 268.96 0.353 0.252 0.000 0.362
F4 NE APARTMENT 1.71 2.50 268.96 0.353 0.252 0.000 0.358
F4 N1 APARTMENT 1.71 2.50 268.96 0.353 0.152 0.000 0.355
F4 N2 APARTMENT 1.71 2.50 268.97 0.353 0.152 0.000 0.355
F4 S1 APARTMENT 1.71 2.50 268.96 0.354 0.152 0.000 0.360
F4 S2 APARTMENT 1.71 2.50 268.97 0.354 0.152 0.000 0.361
M SW APARTMENT 1.71 2.50 268.96 0.353 0.274 0.000 0.382
M NW APARTMENT 1.71 2.50 268.96 0.353 0.274 0.000 0.378
M SE APARTMENT 1.71 2.50 268.96 0.353 0.274 0.000 0.382
M NE APARTMENT 1.71 2.50 268.96 0.353 0.274 0.000 0.378
M N1 APARTMENT 1.71 2.50 268.96 0.353 0.165 0.000 0.376
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.165 0.000 0.376
M S1 APARTMENT 1.71 2.50 268.96 0.354 0.165 0.000 0.381
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.165 0.000 0.381
F6 SW APARTMENT 1.71 2.50 268.96 0.353 0.293 0.000 0.399
F6 NW APARTMENT 1.71 2.50 268.96 0.353 0.292 0.000 0.396
F6 SE APARTMENT 1.71 2.50 268.96 0.353 0.293 0.000 0.400
F6 NE APARTMENT 1.71 2.50 268.96 0.353 0.292 0.000 0.396
F6 N1 APARTMENT 1.71 2.50 268.96 0.353 0.176 0.000 0.393
F6 N2 APARTMENT 1.71 2.50 268.97 0.353 0.176 0.000 0.393
F6 S1 APARTMENT 1.71 2.50 268.96 0.354 0.177 0.000 0.398
F6 S2 APARTMENT 1.71 2.50 268.97 0.354 0.177 0.000 0.398
F7 SW APARTMENT 1.71 2.50 268.96 0.353 0.309 0.000 0.413
F7 NW APARTMENT 1.71 2.50 268.96 0.353 0.309 0.000 0.410
F7 SE APARTMENT 1.71 2.50 268.96 0.353 0.309 0.000 0.414
F7 NE APARTMENT 1.71 2.50 268.96 0.353 0.309 0.000 0.410
F7 N1 APARTMENT 1.71 2.50 268.96 0.353 0.186 0.000 0.407
F7 N2 APARTMENT 1.71 2.50 268.97 0.353 0.186 0.000 0.407
F7 S1 APARTMENT 1.71 2.50 268.96 0.354 0.187 0.000 0.413
F7 S2 APARTMENT 1.71 2.50 268.97 0.354 0.187 0.000 0.413
F8 SW APARTMENT 1.71 2.50 268.96 0.353 0.324 0.000 0.429
F8 NW APARTMENT 1.71 2.50 268.96 0.353 0.324 0.000 0.425
F8 SE APARTMENT 1.71 2.50 268.96 0.353 0.324 0.000 0.429
F8 NE APARTMENT 1.71 2.50 268.96 0.353 0.324 0.000 0.425
F8 N1 APARTMENT 1.71 2.50 268.96 0.353 0.195 0.000 0.422
F8 N2 APARTMENT 1.71 2.50 268.97 0.353 0.195 0.000 0.422
F8 S1 APARTMENT 1.71 2.50 268.96 0.353 0.196 0.000 0.428
F8 S2 APARTMENT 1.71 2.50 268.97 0.353 0.196 0.000 0.428
F9 SW APARTMENT 1.71 2.50 268.96 0.353 0.338 0.000 0.442
F9 NW APARTMENT 1.71 2.50 268.96 0.353 0.338 0.000 0.438
F9 SE APARTMENT 1.71 2.50 268.96 0.353 0.338 0.000 0.443
F9 NE APARTMENT 1.71 2.50 268.96 0.353 0.337 0.000 0.439
F9 N1 APARTMENT 1.71 2.50 268.96 0.353 0.204 0.000 0.436
F9 N2 APARTMENT 1.71 2.50 268.97 0.353 0.204 0.000 0.436
F9 S1 APARTMENT 1.71 2.50 268.96 0.353 0.204 0.000 0.441
F9 S2 APARTMENT 1.71 2.50 268.97 0.353 0.204 0.000 0.441
T SW APARTMENT 1.71 2.50 268.96 0.353 0.350 0.000 0.451
T NW APARTMENT 1.71 2.50 268.96 0.353 0.350 0.000 0.449
T SE APARTMENT 1.71 2.50 268.96 0.353 0.350 0.000 0.452
T NE APARTMENT 1.71 2.50 268.96 0.353 0.350 0.000 0.449
T N1 APARTMENT 1.71 2.50 268.96 0.353 0.211 0.000 0.446
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.211 0.000 0.446
T S1 APARTMENT 1.71 2.50 268.96 0.353 0.211 0.000 0.451
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.211 0.000 0.451
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.503 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.341 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 702.48 22275.35 24-JAN-02:15 22275.35 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1232.08 22655.87 26-MAY-02:45 113893.96 10-JAN-23:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
ElectricityPurchased:Plant 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
Cogeneration:ElectricityPurchased 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
ElectricityNet:Plant 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
Cogeneration:ElectricityNet 3001.91 60216.36 26-MAY-02:45 185892.94 05-JAN-20:00
ExteriorLights:Electricity 168.22 0.00 01-JAN-08:30 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.22 0.00 01-JAN-08:30 10720.10 01-JAN-00:15
General:Fans:Electricity 702.48 22275.35 24-JAN-02:15 22275.35 01-JAN-00:15
Cooling:Electricity 245.02 0.00 01-JAN-00:15 65477.56 17-JUL-16:00
Heating:Electricity 263.76 0.00 20-FEB-15:30 91080.75 10-JAN-23:15
Electricity:Plant 54.09 36.93 01-APR-17:30 3742.71 07-SEP-15:45
HeatRejection:Electricity 8.68 0.00 01-JAN-00:15 2289.48 07-SEP-15:45
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 45.41 36.93 01-APR-17:30 1453.23 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 2181.08 9260.51 20-FEB-24:00 318617.55 06-JAN-06:45
Gas:Plant 2181.08 9260.51 20-FEB-24:00 318617.55 06-JAN-06:45
WaterSystems:Gas 1278.59 9260.51 01-JAN-00:15 92610.36 20-FEB-08:00
Water Heater:WaterSystems:Gas 1278.59 9260.51 01-JAN-00:15 92610.36 20-FEB-08:00
Heating:Gas 902.48 0.00 01-JAN-13:00 245754.71 10-JAN-23:15
Boiler:Heating:Gas 902.48 0.00 01-JAN-13:00 245754.71 10-JAN-23:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 964.33 0.00 01-JAN-00:15 292918.16 07-SEP-15:45
PlantLoopCoolingDemand:HVAC 964.33 0.00 01-JAN-00:15 292918.16 07-SEP-15:45
CoolingCoils:PlantLoopCoolingDemand 964.33 0.00 01-JAN-00:15 292918.16 07-SEP-15:45


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 5643.30 0.00 01-JAN-02:15 0.00 17-JUL-17:45
Water:Plant 5643.30 0.00 01-JAN-02:15 0.00 17-JUL-17:45
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 5643.30 0.00 01-JAN-02:15 0.00 17-JUL-17:45
MainsWater:Plant 5643.30 0.00 01-JAN-02:15 0.00 17-JUL-17:45
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 864.78 0.00 01-JAN-00:15 0.00 17-JUL-16:00
HeatRejection:MainsWater 864.78 0.00 01-JAN-00:15 0.00 17-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 1737.77 527.52 20-AUG-01:45 249934.32 06-JAN-07:15
PlantLoopHeatingDemand:Plant 972.78 527.52 20-AUG-01:45 66040.54 20-FEB-08:00
WaterSystems:PlantLoopHeatingDemand 972.78 527.52 20-AUG-01:45 66040.54 20-FEB-08:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 4852.74 6616.08 03-MAY-01:15 704041.57 10-JAN-23:00
EnergyTransfer:Building 1415.17 3438.43 01-APR-17:30 209205.43 17-NOV-13:30
EnergyTransfer:Zone:G SW APARTMENT 15.69 0.02 21-OCT-04:15 2621.40 11-JAN-08:15
Heating:EnergyTransfer 636.74 0.00 28-FEB-15:30 209205.43 17-NOV-13:30
Heating:EnergyTransfer:Zone:G SW APARTMENT 7.84 0.00 01-JAN-10:00 2621.40 11-JAN-08:15
Cooling:EnergyTransfer 778.43 0.00 04-JAN-01:45 186562.64 19-MAY-16:45
Cooling:EnergyTransfer:Zone:G SW APARTMENT 7.85 0.00 01-JAN-00:15 2589.52 30-AUG-15:30
EnergyTransfer:Zone:G NW APARTMENT 16.42 0.09 01-JUN-02:00 2652.11 11-JAN-08:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 11.63 0.00 14-JAN-15:30 2652.11 11-JAN-08:15
Cooling:EnergyTransfer:Zone:G NW APARTMENT 4.79 0.00 01-JAN-00:15 2339.17 20-JUL-18:30
EnergyTransfer:Zone:OFFICE 20.84 0.03 13-DEC-10:00 3394.15 01-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 7.56 0.00 01-JAN-09:45 2681.41 11-JAN-08:00
Cooling:EnergyTransfer:Zone:OFFICE 13.28 0.00 01-JAN-00:15 3394.15 01-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 16.42 0.01 21-AUG-08:30 2652.11 11-JAN-08:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 11.31 0.00 20-FEB-14:30 2652.11 11-JAN-08:15
Cooling:EnergyTransfer:Zone:G NE APARTMENT 5.10 0.00 01-JAN-00:15 1631.80 23-JUN-09:15
EnergyTransfer:Zone:G N1 APARTMENT 10.48 0.03 02-JUL-08:30 1734.12 27-JAN-08:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 6.16 0.00 01-JAN-18:45 1734.12 27-JAN-08:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.31 0.00 01-JAN-00:15 1103.62 20-JUL-18:30
EnergyTransfer:Zone:G N2 APARTMENT 10.49 0.04 29-SEP-13:30 1733.00 27-JAN-08:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 6.16 0.00 01-JAN-18:45 1733.00 27-JAN-08:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.32 0.00 01-JAN-00:15 1088.16 20-JUL-18:30
EnergyTransfer:Zone:G S1 APARTMENT 11.13 0.00 27-FEB-13:45 1784.40 30-AUG-12:45
Heating:EnergyTransfer:Zone:G S1 APARTMENT 3.16 0.00 01-JAN-00:15 1692.32 11-JAN-08:15
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.98 0.00 01-JAN-03:45 1784.40 30-AUG-12:45
EnergyTransfer:Zone:G S2 APARTMENT 11.19 0.05 29-JUL-09:15 1843.22 30-AUG-12:45
Heating:EnergyTransfer:Zone:G S2 APARTMENT 3.09 0.00 01-JAN-00:15 1686.45 11-JAN-08:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 8.10 0.00 01-JAN-04:00 1843.22 30-AUG-12:45
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 19.16 0.01 16-FEB-11:15 3376.20 30-AUG-15:30
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 6.38 0.00 01-JAN-00:15 2611.59 06-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 12.78 0.00 01-JAN-03:45 3376.20 30-AUG-15:30
EnergyTransfer:Zone:F2 NW APARTMENT 18.31 0.00 31-MAY-00:15 3020.69 20-JUL-18:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 10.79 0.00 01-JAN-18:15 2686.16 11-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 7.52 0.00 01-JAN-00:15 3020.69 20-JUL-18:30
EnergyTransfer:Zone:F2 SE APARTMENT 19.75 0.00 23-SEP-05:00 3287.16 30-AUG-13:30
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 5.91 0.00 01-JAN-00:15 2567.16 11-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 13.85 0.00 01-JAN-03:45 3287.16 30-AUG-13:30
EnergyTransfer:Zone:F2 NE APARTMENT 18.48 0.05 23-NOV-22:45 2693.28 11-JAN-01:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 10.46 0.00 01-JAN-18:15 2693.28 11-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 8.02 0.00 01-JAN-00:15 2213.96 23-JUN-09:00
EnergyTransfer:Zone:F2 N1 APARTMENT 11.29 0.01 20-MAR-09:45 1849.98 17-NOV-13:45
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 4.47 0.00 01-JAN-16:15 1849.98 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 6.83 0.00 01-JAN-00:15 1568.96 20-JUL-18:30
EnergyTransfer:Zone:F2 N2 APARTMENT 11.29 0.01 02-AUG-17:00 1852.15 17-NOV-13:45
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 4.46 0.00 01-JAN-16:15 1852.15 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 6.83 0.00 01-JAN-00:15 1551.07 20-JUL-18:30
EnergyTransfer:Zone:F2 S1 APARTMENT 15.03 0.05 28-MAY-11:15 2353.74 31-AUG-13:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 2.01 0.00 01-JAN-00:15 1440.66 11-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 13.02 0.00 04-JAN-00:30 2353.74 31-AUG-13:00
EnergyTransfer:Zone:F2 S2 APARTMENT 15.11 0.29 11-MAR-06:00 2375.97 31-AUG-13:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 2.00 0.00 01-JAN-00:15 1437.95 11-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 13.11 0.00 04-JAN-00:30 2375.97 31-AUG-13:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 19.80 0.03 24-OCT-01:00 3402.13 19-MAY-16:45
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 6.41 0.00 01-JAN-00:15 2691.77 06-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 13.40 0.00 01-JAN-05:30 3402.13 19-MAY-16:45
EnergyTransfer:Zone:F3 NW APARTMENT 18.85 0.07 18-OCT-05:45 3011.80 20-JUL-18:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 10.87 0.00 01-JAN-18:15 2850.36 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 7.98 0.00 01-JAN-00:15 3011.80 20-JUL-18:30
EnergyTransfer:Zone:F3 SE APARTMENT 20.14 0.03 21-APR-22:30 3135.80 30-AUG-13:30
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 6.20 0.00 01-JAN-00:15 2685.02 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 13.94 0.00 01-JAN-05:30 3135.80 30-AUG-13:30
EnergyTransfer:Zone:F3 NE APARTMENT 19.01 0.01 17-MAR-16:00 2852.77 05-JAN-16:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 10.54 0.00 01-JAN-18:15 2852.77 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 8.47 0.00 01-JAN-00:15 2272.12 23-JUN-09:30
EnergyTransfer:Zone:F3 N1 APARTMENT 11.75 0.02 23-MAR-09:30 2145.66 17-NOV-13:45
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 4.28 0.00 01-JAN-14:15 2145.66 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 7.48 0.00 01-JAN-00:45 1611.35 30-JUN-19:15
EnergyTransfer:Zone:F3 N2 APARTMENT 11.76 0.01 16-JUL-06:30 2148.57 17-NOV-13:45
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 4.27 0.00 01-JAN-14:00 2148.57 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 7.48 0.00 01-JAN-00:45 1593.54 30-JUN-19:15
EnergyTransfer:Zone:F3 S1 APARTMENT 16.03 0.03 24-NOV-14:15 2395.35 31-AUG-13:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 1.89 0.00 01-JAN-00:15 1580.22 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 14.13 0.00 04-JAN-01:45 2395.35 31-AUG-13:00
EnergyTransfer:Zone:F3 S2 APARTMENT 16.07 0.02 24-NOV-15:15 2406.93 31-AUG-13:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 1.89 0.00 01-JAN-00:15 1576.87 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 14.17 0.00 04-JAN-01:45 2406.93 31-AUG-13:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 20.14 0.07 11-SEP-23:00 3409.89 19-MAY-16:45
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 6.83 0.00 01-JAN-00:15 2886.95 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 13.32 0.00 01-JAN-05:15 3409.89 19-MAY-16:45
EnergyTransfer:Zone:F4 NW APARTMENT 19.42 0.01 23-OCT-06:45 3052.45 05-JAN-16:00
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 11.41 0.00 01-JAN-18:15 3052.45 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 8.00 0.00 01-JAN-00:15 3021.06 20-JUL-18:30
EnergyTransfer:Zone:F4 SE APARTMENT 20.44 0.01 16-NOV-13:00 3125.04 30-AUG-13:15
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 6.67 0.00 01-JAN-00:15 2886.37 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 13.77 0.00 01-JAN-05:15 3125.04 30-AUG-13:15
EnergyTransfer:Zone:F4 NE APARTMENT 19.57 0.00 14-MAR-14:45 3052.72 05-JAN-16:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 11.06 0.00 01-JAN-18:15 3052.72 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 8.50 0.00 01-JAN-00:15 2295.12 23-JUN-09:15
EnergyTransfer:Zone:F4 N1 APARTMENT 12.06 0.01 31-MAY-08:15 2418.99 17-NOV-13:45
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 4.46 0.00 01-JAN-00:15 2418.99 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 7.59 0.00 01-JAN-00:30 1625.19 30-JUN-19:15
EnergyTransfer:Zone:F4 N2 APARTMENT 12.06 0.02 27-JUN-11:15 2421.79 17-NOV-13:45
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 4.46 0.00 01-JAN-00:15 2421.79 17-NOV-13:45
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 7.60 0.00 01-JAN-00:30 1607.47 30-JUN-19:15
EnergyTransfer:Zone:F4 S1 APARTMENT 16.24 0.10 06-JUN-09:15 2411.17 31-AUG-12:45
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 2.00 0.00 01-JAN-00:15 1845.21 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 14.24 0.00 04-JAN-01:45 2411.17 31-AUG-12:45
EnergyTransfer:Zone:F4 S2 APARTMENT 16.26 0.02 28-APR-13:15 2417.34 31-AUG-12:45
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 2.00 0.00 01-JAN-00:15 1850.16 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 14.26 0.00 04-JAN-01:45 2417.34 31-AUG-12:45
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 20.43 0.11 14-JAN-21:15 3438.07 19-MAY-16:45
Heating:EnergyTransfer:Zone:M SW APARTMENT 7.17 0.00 01-JAN-00:15 3039.84 05-JAN-16:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 13.26 0.00 01-JAN-05:00 3438.07 19-MAY-16:45
EnergyTransfer:Zone:M NW APARTMENT 19.85 0.01 11-MAR-17:00 3204.79 05-JAN-16:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 11.78 0.00 01-JAN-18:15 3204.79 05-JAN-16:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 8.08 0.00 01-JAN-00:15 3048.61 20-JUL-18:30
EnergyTransfer:Zone:M SE APARTMENT 20.70 0.01 11-SEP-01:30 3155.71 30-AUG-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 7.00 0.00 01-JAN-00:15 3038.70 05-JAN-16:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 13.69 0.00 01-JAN-05:00 3155.71 30-AUG-13:30
EnergyTransfer:Zone:M NE APARTMENT 19.98 0.00 13-MAR-18:45 3203.48 05-JAN-16:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 11.41 0.00 01-JAN-18:15 3203.48 05-JAN-16:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 8.57 0.00 01-JAN-00:15 2325.81 23-JUN-09:15
EnergyTransfer:Zone:M N1 APARTMENT 12.31 0.05 25-FEB-10:45 2667.04 17-NOV-13:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 4.57 0.00 01-JAN-00:15 2667.04 17-NOV-13:30
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 7.74 0.00 01-JAN-00:30 1660.15 30-JUN-19:15
EnergyTransfer:Zone:M N2 APARTMENT 12.31 0.02 22-JUL-08:15 2668.21 17-NOV-13:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 4.56 0.00 01-JAN-00:15 2668.21 17-NOV-13:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 7.75 0.00 01-JAN-00:30 1642.53 30-JUN-19:15
EnergyTransfer:Zone:M S1 APARTMENT 16.37 0.17 12-FEB-10:15 2447.59 31-AUG-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 2.09 0.00 01-JAN-00:15 1987.15 17-NOV-13:30
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 14.28 0.00 04-JAN-01:30 2447.59 31-AUG-12:45
EnergyTransfer:Zone:M S2 APARTMENT 16.39 0.03 16-FEB-22:45 2456.25 31-AUG-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 2.09 0.00 01-JAN-00:15 1989.22 17-NOV-13:30
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 14.30 0.00 04-JAN-01:30 2456.25 31-AUG-12:45
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 20.41 0.00 14-JAN-14:45 3393.11 19-MAY-16:45
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 7.98 0.00 01-JAN-00:15 3231.38 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 12.42 0.00 01-JAN-03:45 3393.11 19-MAY-16:45
EnergyTransfer:Zone:F6 NW APARTMENT 20.45 0.02 18-OCT-01:30 3396.11 05-JAN-16:00
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 12.88 0.00 01-JAN-18:15 3396.11 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 7.57 0.00 01-JAN-00:15 3008.97 30-JUN-19:15
EnergyTransfer:Zone:F6 SE APARTMENT 20.64 0.01 04-DEC-15:00 3229.32 05-JAN-16:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 7.81 0.00 01-JAN-00:15 3229.32 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 12.83 0.00 01-JAN-03:45 3113.66 30-AUG-13:30
EnergyTransfer:Zone:F6 NE APARTMENT 20.54 0.00 02-OCT-13:15 3393.78 05-JAN-16:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 12.49 0.00 01-JAN-18:15 3393.78 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 8.05 0.00 01-JAN-00:15 2282.38 23-JUN-09:15
EnergyTransfer:Zone:F6 N1 APARTMENT 12.39 0.13 10-SEP-14:45 2927.81 17-NOV-13:30
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 5.21 0.00 01-JAN-16:15 2927.81 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 7.19 0.00 01-JAN-00:15 1620.66 30-JUN-19:15
EnergyTransfer:Zone:F6 N2 APARTMENT 12.39 0.00 30-MAY-09:15 2928.78 17-NOV-13:30
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 5.20 0.00 01-JAN-16:15 2928.78 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 7.19 0.00 01-JAN-00:15 1603.20 30-JUN-19:15
EnergyTransfer:Zone:F6 S1 APARTMENT 15.76 0.11 23-JAN-18:30 2406.75 31-AUG-12:45
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 2.41 0.00 01-JAN-00:15 2234.52 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 13.35 0.00 04-JAN-00:30 2406.75 31-AUG-12:45
EnergyTransfer:Zone:F6 S2 APARTMENT 15.77 0.05 17-MAR-11:15 2416.69 31-AUG-12:45
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 2.41 0.00 01-JAN-00:15 2235.81 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 13.37 0.00 04-JAN-00:30 2416.69 31-AUG-12:45
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 20.54 0.00 11-JUL-04:00 3387.59 05-JAN-16:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 8.64 0.00 01-JAN-00:15 3387.59 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 11.90 0.00 01-JAN-01:00 3375.08 19-MAY-16:45
EnergyTransfer:Zone:F7 NW APARTMENT 21.00 0.01 17-APR-02:30 3549.35 05-JAN-16:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 13.71 0.00 01-JAN-18:30 3549.35 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 7.29 0.00 01-JAN-00:15 3005.14 30-JUN-19:15
EnergyTransfer:Zone:F7 SE APARTMENT 20.74 0.03 01-OCT-00:45 3384.58 05-JAN-16:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 8.45 0.00 01-JAN-00:15 3384.58 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 12.29 0.00 01-JAN-01:00 3098.07 30-AUG-13:30
EnergyTransfer:Zone:F7 NE APARTMENT 21.05 0.04 08-NOV-09:00 3546.17 05-JAN-16:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 13.30 0.00 01-JAN-18:30 3546.17 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 7.75 0.00 01-JAN-00:15 2266.60 23-JUN-09:15
EnergyTransfer:Zone:F7 N1 APARTMENT 12.54 0.02 26-AUG-08:45 3172.75 17-NOV-13:30
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 5.68 0.00 01-JAN-16:15 3172.75 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 6.86 0.00 01-JAN-00:15 1609.20 23-JUN-19:45
EnergyTransfer:Zone:F7 N2 APARTMENT 12.54 0.01 31-AUG-20:30 3173.28 17-NOV-13:30
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 5.67 0.00 01-JAN-16:15 3173.28 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 6.87 0.00 01-JAN-00:15 1593.29 23-JUN-19:45
EnergyTransfer:Zone:F7 S1 APARTMENT 15.41 0.00 07-SEP-11:30 2489.28 17-NOV-13:30
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 2.67 0.00 01-JAN-00:15 2489.28 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 12.74 0.00 03-JAN-24:00 2392.04 31-AUG-12:45
EnergyTransfer:Zone:F7 S2 APARTMENT 15.44 0.07 25-NOV-22:15 2496.16 17-NOV-13:30
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 2.67 0.00 01-JAN-00:15 2496.16 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 12.76 0.00 03-JAN-24:00 2401.99 31-AUG-12:45
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 20.78 0.01 11-SEP-12:45 3536.01 05-JAN-16:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 9.31 0.00 01-JAN-00:15 3536.01 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 11.47 0.00 01-JAN-01:00 3370.16 19-MAY-16:45
EnergyTransfer:Zone:F8 NW APARTMENT 21.64 0.02 02-APR-17:45 3728.49 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 14.53 0.00 01-JAN-18:45 3728.49 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 7.10 0.00 01-JAN-00:15 2998.77 30-JUN-19:15
EnergyTransfer:Zone:F8 SE APARTMENT 20.96 0.02 31-MAY-10:00 3532.13 05-JAN-16:00
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 9.11 0.00 01-JAN-00:15 3532.13 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 11.85 0.00 01-JAN-01:00 3095.47 30-AUG-13:30
EnergyTransfer:Zone:F8 NE APARTMENT 21.65 0.01 29-MAY-19:45 3733.85 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 14.10 0.00 01-JAN-18:45 3733.85 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 7.54 0.00 01-JAN-00:15 2264.61 23-JUN-09:15
EnergyTransfer:Zone:F8 N1 APARTMENT 12.80 0.05 10-SEP-14:30 3399.27 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 6.19 0.00 01-JAN-16:45 3399.27 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 6.62 0.00 01-JAN-00:15 1615.11 23-JUN-19:45
EnergyTransfer:Zone:F8 N2 APARTMENT 12.80 0.01 11-MAR-20:45 3399.61 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 6.18 0.00 01-JAN-17:00 3399.61 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 6.62 0.00 01-JAN-00:15 1599.34 23-JUN-19:45
EnergyTransfer:Zone:F8 S1 APARTMENT 15.19 0.05 18-AUG-16:30 2775.38 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 2.98 0.00 01-JAN-00:15 2775.38 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 12.22 0.00 03-JAN-06:00 2390.36 31-AUG-12:45
EnergyTransfer:Zone:F8 S2 APARTMENT 15.21 0.12 03-MAR-06:30 2777.93 17-NOV-13:30
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 2.98 0.00 01-JAN-00:15 2777.93 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 12.23 0.00 03-JAN-06:00 2400.35 31-AUG-12:45
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 21.84 0.02 08-JUN-09:15 3772.60 05-JAN-16:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 10.80 0.00 01-JAN-00:15 3772.60 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 11.04 0.00 01-JAN-00:45 3458.81 19-MAY-16:45
EnergyTransfer:Zone:F9 NW APARTMENT 23.33 0.03 11-SEP-04:00 3954.58 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 16.31 0.00 12-FEB-18:15 3954.58 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 7.02 0.00 01-JAN-00:15 3089.42 30-JUN-19:15
EnergyTransfer:Zone:F9 SE APARTMENT 21.93 0.01 20-AUG-02:00 3767.88 05-JAN-16:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 10.55 0.00 01-JAN-00:15 3767.88 05-JAN-16:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 11.38 0.00 01-JAN-00:45 3155.68 30-AUG-13:30
EnergyTransfer:Zone:F9 NE APARTMENT 23.24 0.04 16-OCT-01:45 3942.91 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 15.82 0.00 20-FEB-17:15 3942.91 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 7.42 0.00 01-JAN-00:15 2288.25 23-JUN-09:15
EnergyTransfer:Zone:F9 N1 APARTMENT 13.84 0.04 21-APR-23:15 3640.73 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 7.47 0.00 01-JAN-17:15 3640.73 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 6.36 0.00 01-JAN-00:15 1698.49 23-JUN-19:45
EnergyTransfer:Zone:F9 N2 APARTMENT 13.85 0.03 07-SEP-11:00 3640.76 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 7.47 0.00 01-JAN-17:15 3640.76 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 6.37 0.00 01-JAN-00:15 1682.48 23-JUN-19:45
EnergyTransfer:Zone:F9 S1 APARTMENT 15.30 0.07 15-FEB-08:45 3107.11 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 3.79 0.00 01-JAN-00:15 3107.11 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 11.51 0.00 03-JAN-03:30 2430.94 31-AUG-13:00
EnergyTransfer:Zone:F9 S2 APARTMENT 15.31 0.03 12-MAR-04:30 3109.21 17-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 3.79 0.00 01-JAN-00:15 3109.21 17-NOV-13:30
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 11.52 0.00 03-JAN-03:30 2442.08 31-AUG-13:00
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 29.94 0.08 27-MAR-20:00 4589.70 05-JAN-16:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 18.60 0.00 01-JAN-10:45 4589.70 05-JAN-16:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 11.34 0.00 01-JAN-00:15 4215.06 30-AUG-15:30
EnergyTransfer:Zone:T NW APARTMENT 30.95 0.00 20-OCT-18:00 4738.95 05-JAN-16:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 23.52 0.00 23-FEB-15:45 4738.95 05-JAN-16:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 7.43 0.00 01-JAN-00:15 3706.06 14-JUL-18:00
EnergyTransfer:Zone:T SE APARTMENT 29.33 0.02 12-MAY-02:15 4594.72 05-JAN-16:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 18.09 0.00 01-JAN-10:00 4594.72 05-JAN-16:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 11.24 0.00 01-JAN-00:15 3865.40 30-AUG-13:30
EnergyTransfer:Zone:T NE APARTMENT 30.15 0.01 05-APR-16:00 4744.52 05-JAN-16:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 22.73 0.00 25-FEB-18:15 4744.52 05-JAN-16:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 7.42 0.00 01-JAN-00:15 2826.92 23-JUN-09:30
EnergyTransfer:Zone:T N1 APARTMENT 19.66 0.11 24-NOV-12:00 3809.79 17-NOV-13:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 13.60 0.00 01-JAN-18:45 3809.79 17-NOV-13:30
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 6.06 0.00 01-JAN-00:15 2217.99 23-JUN-16:00
EnergyTransfer:Zone:T N2 APARTMENT 19.66 0.01 16-OCT-06:00 3808.70 17-NOV-13:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 13.59 0.00 01-JAN-18:45 3808.70 17-NOV-13:30
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 6.07 0.00 01-JAN-00:15 2217.39 23-JUN-16:00
EnergyTransfer:Zone:T S1 APARTMENT 19.60 0.01 19-DEC-14:00 3352.67 17-NOV-13:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 9.38 0.00 01-JAN-09:30 3352.67 17-NOV-13:45
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.22 0.00 01-JAN-00:30 3247.97 30-AUG-13:15
EnergyTransfer:Zone:T S2 APARTMENT 19.63 0.00 10-MAR-13:15 3352.04 17-NOV-13:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 9.38 0.00 01-JAN-09:30 3352.04 17-NOV-13:45
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.24 0.00 01-JAN-00:30 3259.39 30-AUG-13:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 1694.01 527.52 20-AUG-01:45 250499.95 06-JAN-07:15
WaterSystems:EnergyTransfer 972.77 527.52 20-AUG-01:45 66033.79 20-FEB-08:00
sub cat:WaterSystems:EnergyTransfer 972.77 527.52 20-AUG-01:45 66033.79 20-FEB-08:00
EnergyTransfer:HVAC 1743.55 0.00 01-APR-17:30 288476.89 10-JAN-23:15
CoolingCoils:EnergyTransfer 739.42 0.00 01-JAN-00:15 230418.87 07-SEP-15:45
HeatingCoils:EnergyTransfer 1004.13 0.00 20-FEB-15:30 288476.89 10-JAN-23:15
PlantLoopHeatingDemand:HVAC 764.99 0.00 20-FEB-15:30 197788.05 10-JAN-23:15
HeatingCoils:PlantLoopHeatingDemand 764.99 0.00 20-FEB-15:30 197788.05 10-JAN-23:15
Boilers:EnergyTransfer 721.24 0.00 01-JAN-13:00 196603.77 10-JAN-23:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 7.836 -7.853 0.000 0.000 3.857 2.413 12.213 20.833 0.000 0.138 0.000 0.000 -14.291 0.000 -7.878 -17.267
G NW APARTMENT 11.631 -4.789 0.000 0.000 3.899 2.413 12.213 9.267 0.000 0.138 0.000 0.000 -14.913 0.000 -7.463 -12.396
OFFICE 7.556 -13.284 0.000 0.000 0.531 21.954 7.547 20.970 0.000 0.072 0.000 0.000 -14.115 0.000 -5.118 -26.113
G NE APARTMENT 11.314 -5.102 0.000 0.000 3.915 2.413 12.213 9.378 0.000 0.138 0.000 0.000 -14.513 0.000 -7.461 -12.295
G N1 APARTMENT 6.163 -4.313 0.000 0.000 3.917 2.413 12.213 3.048 0.000 0.109 0.000 0.000 -9.317 0.000 -5.257 -8.976
G N2 APARTMENT 6.164 -4.324 0.000 0.000 3.918 2.413 12.213 3.046 0.000 0.109 0.000 0.000 -9.314 0.000 -5.258 -8.967
G S1 APARTMENT 3.156 -7.977 0.000 0.000 3.852 2.413 12.213 14.814 0.000 0.109 0.001 0.000 -8.729 0.000 -5.752 -14.098
G S2 APARTMENT 3.092 -8.102 0.000 0.000 3.849 2.413 12.213 14.800 0.000 0.109 0.001 0.000 -8.738 0.000 -5.780 -13.856
F2 SW APARTMENT 6.380 -12.782 0.000 0.000 3.790 2.413 12.213 20.092 0.000 0.185 0.001 0.000 -15.199 0.000 -10.896 -6.195
F2 NW APARTMENT 10.788 -7.521 0.000 0.000 3.859 2.413 12.213 8.839 0.000 0.184 0.000 0.000 -15.707 0.000 -10.351 -4.716
F2 SE APARTMENT 5.906 -13.845 0.000 0.000 3.788 2.413 12.213 20.271 0.000 0.185 0.001 0.000 -14.941 0.000 -10.995 -4.995
F2 NE APARTMENT 10.455 -8.022 0.000 0.000 3.876 2.413 12.213 8.966 0.000 0.184 0.000 0.000 -15.247 0.000 -10.330 -4.508
F2 N1 APARTMENT 4.467 -6.826 0.000 0.000 3.873 2.413 12.213 2.833 0.000 0.142 0.000 0.000 -9.858 0.000 -7.244 -2.013
F2 N2 APARTMENT 4.460 -6.833 0.000 0.000 3.874 2.413 12.213 2.831 0.000 0.142 0.000 0.000 -9.854 0.000 -7.243 -2.002
F2 S1 APARTMENT 2.010 -13.021 0.000 0.000 3.768 2.413 12.213 14.318 0.000 0.142 0.001 0.000 -9.305 0.000 -7.906 -4.632
F2 S2 APARTMENT 1.998 -13.109 0.000 0.000 3.766 2.413 12.213 14.313 0.000 0.142 0.000 0.000 -9.309 0.000 -7.917 -4.511
F3 SW APARTMENT 6.407 -13.396 0.000 0.000 3.783 2.413 12.213 19.801 0.000 0.229 0.001 0.000 -15.476 0.000 -12.575 -3.398
F3 NW APARTMENT 10.873 -7.976 0.000 0.000 3.854 2.413 12.213 8.689 0.000 0.229 0.000 0.000 -15.981 0.000 -11.975 -2.339
F3 SE APARTMENT 6.203 -13.939 0.000 0.000 3.788 2.413 12.213 20.025 0.000 0.229 0.000 0.000 -15.147 0.000 -12.633 -3.151
F3 NE APARTMENT 10.538 -8.474 0.000 0.000 3.870 2.413 12.213 8.827 0.000 0.228 0.000 0.000 -15.499 0.000 -11.949 -2.166
F3 N1 APARTMENT 4.277 -7.477 0.000 0.000 3.862 2.413 12.213 2.767 0.000 0.179 0.160 0.000 -10.044 0.000 -8.350 -0.000
F3 N2 APARTMENT 4.272 -7.484 0.000 0.000 3.863 2.413 12.213 2.766 0.000 0.178 0.167 0.000 -10.039 0.000 -8.349 -0.000
F3 S1 APARTMENT 1.894 -14.134 0.000 0.000 3.751 2.413 12.213 14.114 0.000 0.178 0.000 0.000 -9.500 0.000 -9.065 -1.864
F3 S2 APARTMENT 1.892 -14.173 0.000 0.000 3.751 2.413 12.213 14.111 0.000 0.179 0.000 0.000 -9.500 0.000 -9.071 -1.813
F4 SW APARTMENT 6.827 -13.316 0.000 0.000 3.785 2.413 12.213 19.629 0.000 0.250 0.000 0.000 -15.613 0.000 -13.642 -2.545
F4 NW APARTMENT 11.413 -8.004 0.000 0.000 3.854 2.413 12.213 8.607 0.000 0.250 0.000 0.000 -16.131 0.000 -13.023 -1.592
F4 SE APARTMENT 6.667 -13.768 0.000 0.000 3.791 2.413 12.213 19.866 0.000 0.250 0.000 0.000 -15.262 0.000 -13.694 -2.475
F4 NE APARTMENT 11.063 -8.503 0.000 0.000 3.870 2.413 12.213 8.751 0.000 0.248 0.000 0.000 -15.637 0.000 -12.992 -1.425
F4 N1 APARTMENT 4.465 -7.593 0.000 0.000 3.859 2.413 12.213 2.734 0.000 0.193 0.867 0.000 -10.146 0.000 -9.006 -0.000
F4 N2 APARTMENT 4.458 -7.600 0.000 0.000 3.861 2.413 12.213 2.733 0.000 0.193 0.876 0.000 -10.141 0.000 -9.005 -0.000
F4 S1 APARTMENT 2.000 -14.237 0.000 0.000 3.750 2.413 12.213 13.993 0.000 0.194 0.001 0.000 -9.594 0.000 -9.739 -0.993
F4 S2 APARTMENT 2.002 -14.260 0.000 0.000 3.750 2.413 12.213 13.991 0.000 0.194 0.001 0.000 -9.593 0.000 -9.744 -0.965
M SW APARTMENT 7.165 -13.260 0.000 0.000 3.787 2.413 12.213 19.496 0.000 0.266 0.001 0.000 -15.724 0.000 -14.668 -1.688
M NW APARTMENT 11.776 -8.077 0.000 0.000 3.855 2.413 12.213 8.542 0.000 0.266 0.000 0.000 -16.256 0.000 -14.019 -0.713
M SE APARTMENT 7.001 -13.694 0.000 0.000 3.793 2.413 12.213 19.739 0.000 0.266 0.001 0.000 -15.362 0.000 -14.721 -1.648
M NE APARTMENT 11.406 -8.574 0.000 0.000 3.871 2.413 12.213 8.689 0.000 0.264 0.000 0.000 -15.752 0.000 -13.985 -0.545
M N1 APARTMENT 4.568 -7.738 0.000 0.000 3.858 2.413 12.213 2.708 0.000 0.205 1.675 0.000 -10.228 0.000 -9.674 -0.000
M N2 APARTMENT 4.563 -7.747 0.000 0.000 3.859 2.413 12.213 2.707 0.000 0.204 1.684 0.000 -10.224 0.000 -9.673 -0.000
M S1 APARTMENT 2.086 -14.282 0.000 0.000 3.750 2.413 12.213 13.901 0.000 0.205 0.002 0.000 -9.666 0.000 -10.436 -0.184
M S2 APARTMENT 2.089 -14.303 0.000 0.000 3.750 2.413 12.213 13.898 0.000 0.206 0.001 0.000 -9.665 0.000 -10.441 -0.160
F6 SW APARTMENT 7.981 -12.425 0.000 0.000 3.798 2.413 12.213 19.429 0.000 0.279 0.000 0.000 -15.740 0.000 -15.489 -2.460
F6 NW APARTMENT 12.875 -7.572 0.000 0.000 3.864 2.413 12.213 8.526 0.000 0.279 0.000 0.000 -16.282 0.000 -14.805 -1.510
F6 SE APARTMENT 7.806 -12.830 0.000 0.000 3.804 2.413 12.213 19.676 0.000 0.280 0.000 0.000 -15.373 0.000 -15.549 -2.440
F6 NE APARTMENT 12.488 -8.052 0.000 0.000 3.880 2.413 12.213 8.677 0.000 0.277 0.000 0.000 -15.775 0.000 -14.768 -1.353
F6 N1 APARTMENT 5.207 -7.187 0.000 0.000 3.868 2.413 12.213 2.710 0.000 0.214 0.975 0.000 -10.240 0.000 -10.172 -0.000
F6 N2 APARTMENT 5.199 -7.193 0.000 0.000 3.869 2.413 12.213 2.708 0.000 0.214 0.984 0.000 -10.236 0.000 -10.171 -0.000
F6 S1 APARTMENT 2.407 -13.349 0.000 0.000 3.762 2.413 12.213 13.853 0.000 0.215 0.000 0.000 -9.673 0.000 -10.973 -0.868
F6 S2 APARTMENT 2.407 -13.367 0.000 0.000 3.763 2.413 12.213 13.850 0.000 0.215 0.002 0.000 -9.671 0.000 -10.978 -0.844
F7 SW APARTMENT 8.637 -11.898 0.000 0.000 3.806 2.413 12.213 19.366 0.000 0.291 0.000 0.000 -15.767 0.000 -16.200 -2.861
F7 NW APARTMENT 13.705 -7.294 0.000 0.000 3.871 2.413 12.213 8.505 0.000 0.291 0.000 0.000 -16.321 0.000 -15.496 -1.887
F7 SE APARTMENT 8.448 -12.287 0.000 0.000 3.812 2.413 12.213 19.615 0.000 0.291 0.000 0.000 -15.395 0.000 -16.263 -2.848
F7 NE APARTMENT 13.295 -7.752 0.000 0.000 3.885 2.413 12.213 8.659 0.000 0.287 0.000 0.000 -15.809 0.000 -15.455 -1.736
F7 N1 APARTMENT 5.678 -6.857 0.000 0.000 3.875 2.413 12.213 2.707 0.000 0.222 0.619 0.000 -10.260 0.000 -10.609 -0.000
F7 N2 APARTMENT 5.674 -6.866 0.000 0.000 3.876 2.413 12.213 2.705 0.000 0.221 0.627 0.000 -10.256 0.000 -10.607 -0.000
F7 S1 APARTMENT 2.671 -12.743 0.000 0.000 3.772 2.413 12.213 13.808 0.000 0.223 0.000 0.000 -9.685 0.000 -11.431 -1.242
F7 S2 APARTMENT 2.673 -12.763 0.000 0.000 3.772 2.413 12.213 13.806 0.000 0.223 0.001 0.000 -9.684 0.000 -11.437 -1.217
F8 SW APARTMENT 9.313 -11.467 0.000 0.000 3.813 2.413 12.213 19.313 0.000 0.304 0.000 0.000 -15.788 0.000 -16.865 -3.248
F8 NW APARTMENT 14.533 -7.103 0.000 0.000 3.876 2.413 12.213 8.485 0.000 0.304 0.000 0.000 -16.356 0.000 -16.148 -2.217
F8 SE APARTMENT 9.110 -11.848 0.000 0.000 3.819 2.413 12.213 19.564 0.000 0.305 0.000 0.000 -15.413 0.000 -16.931 -3.233
F8 NE APARTMENT 14.104 -7.542 0.000 0.000 3.890 2.413 12.213 8.641 0.000 0.300 0.000 0.000 -15.841 0.000 -16.105 -2.072
F8 N1 APARTMENT 6.186 -6.615 0.000 0.000 3.881 2.413 12.213 2.703 0.000 0.232 0.298 0.000 -10.278 0.000 -11.032 -0.000
F8 N2 APARTMENT 6.180 -6.623 0.000 0.000 3.882 2.413 12.213 2.702 0.000 0.231 0.308 0.000 -10.274 0.000 -11.031 -0.000
F8 S1 APARTMENT 2.975 -12.216 0.000 0.000 3.781 2.413 12.213 13.772 0.000 0.234 0.000 0.000 -9.693 0.000 -11.866 -1.614
F8 S2 APARTMENT 2.976 -12.234 0.000 0.000 3.781 2.413 12.213 13.770 0.000 0.234 0.000 0.000 -9.692 0.000 -11.872 -1.589
F9 SW APARTMENT 10.804 -11.037 0.000 0.000 3.822 2.413 12.213 19.293 0.000 0.317 0.001 0.000 -15.765 0.000 -17.438 -4.622
F9 NW APARTMENT 16.311 -7.018 0.000 0.000 3.880 2.413 12.213 8.480 0.000 0.316 0.000 0.000 -16.355 0.000 -16.732 -3.509
F9 SE APARTMENT 10.551 -11.382 0.000 0.000 3.828 2.413 12.213 19.545 0.000 0.317 0.001 0.000 -15.387 0.000 -17.510 -4.589
F9 NE APARTMENT 15.824 -7.419 0.000 0.000 3.895 2.413 12.213 8.637 0.000 0.312 0.000 0.000 -15.837 0.000 -16.687 -3.350
F9 N1 APARTMENT 7.475 -6.364 0.000 0.000 3.886 2.413 12.213 2.706 0.000 0.242 0.000 0.000 -10.269 0.000 -11.407 -0.894
F9 N2 APARTMENT 7.470 -6.375 0.000 0.000 3.887 2.413 12.213 2.704 0.000 0.242 0.000 0.000 -10.266 0.000 -11.406 -0.882
F9 S1 APARTMENT 3.792 -11.506 0.000 0.000 3.794 2.413 12.213 13.760 0.000 0.245 0.002 0.000 -9.667 0.000 -12.223 -2.821
F9 S2 APARTMENT 3.791 -11.522 0.000 0.000 3.794 2.413 12.213 13.757 0.000 0.245 0.002 0.000 -9.666 0.000 -12.231 -2.795
T SW APARTMENT 18.602 -11.342 0.000 0.000 3.858 2.413 12.213 19.062 0.000 0.326 0.000 0.000 -15.147 0.000 -17.920 -12.064
T NW APARTMENT 23.519 -7.425 0.000 0.000 3.897 2.413 12.213 8.312 0.000 0.324 0.000 0.000 -15.848 0.000 -17.298 -10.106
T SE APARTMENT 18.091 -11.239 0.000 0.000 3.864 2.413 12.213 19.343 0.000 0.326 0.000 0.000 -14.805 0.000 -18.003 -12.202
T NE APARTMENT 22.724 -7.421 0.000 0.000 3.913 2.413 12.213 8.505 0.000 0.323 0.000 0.000 -15.367 0.000 -17.253 -10.050
T N1 APARTMENT 13.598 -6.063 0.000 0.000 3.904 2.413 12.213 2.657 0.000 0.250 0.000 0.000 -9.937 0.000 -11.759 -7.275
T N2 APARTMENT 13.594 -6.066 0.000 0.000 3.905 2.413 12.213 2.653 0.000 0.251 0.000 0.000 -9.932 0.000 -11.763 -7.267
T S1 APARTMENT 9.382 -10.219 0.000 0.000 3.838 2.413 12.213 13.644 0.000 0.252 0.000 0.000 -9.315 0.000 -12.519 -9.689
T S2 APARTMENT 9.383 -10.242 0.000 0.000 3.838 2.413 12.213 13.639 0.000 0.252 0.000 0.000 -9.312 0.000 -12.529 -9.657
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 4.312 0.000 0.728 33.006 0.000 -3.291 0.000 -53.284 -0.000
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.920 0.000 0.009 0.000 0.000 -1.954 0.000 -1.331 -17.174
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.876 0.000 0.010 0.000 0.000 -2.024 0.000 -1.611 -16.779
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.852 0.000 0.011 0.000 0.000 -2.058 0.000 -1.816 -16.518
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 1.823 0.000 0.009 0.000 0.000 -2.106 0.000 -2.046 -34.739
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.835 0.000 0.012 0.000 0.000 -2.076 0.000 -2.102 -16.198
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.836 0.000 0.013 0.000 0.000 -2.068 0.000 -2.203 -16.107
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.833 0.000 0.014 0.000 0.000 -2.067 0.000 -2.300 -16.009
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 1.833 0.000 0.014 0.000 0.000 -2.059 0.000 -2.379 -15.939
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 1.793 0.000 0.007 0.000 0.000 -1.991 0.000 -2.484 -23.791
Total Facility 636.717 -778.433 0.000 0.000 303.697 416.414 980.287 924.865 0.000 19.044 42.270 0.000 -1033.600 0.000 -1023.765 -487.474


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 30-AUG-15:30 0.00 -2589.40 0.00 0.00 48.14 100.83 470.89 4027.25 0.00 166.04 0.00 0.00 0.00 0.00 0.00 -2223.74
G NW APARTMENT 20-JUL-18:23 0.00 -2344.48 0.00 0.00 141.81 230.46 547.42 2856.48 0.00 325.26 0.00 0.00 0.00 0.00 0.00 -1756.94
OFFICE 01-SEP-13:30 0.00 -3393.91 0.00 0.00 65.20 1622.33 544.91 3570.71 0.00 42.03 0.00 0.00 0.00 0.00 0.00 -2451.27
G NE APARTMENT 20-JUL-18:23 0.00 -1633.54 0.00 0.00 141.81 230.46 547.42 912.96 0.00 327.15 0.00 0.00 0.00 0.00 0.00 -526.26
G N1 APARTMENT 20-JUL-18:23 0.00 -1104.35 0.00 0.00 141.63 230.46 547.42 744.53 0.00 287.50 0.00 0.00 0.00 0.00 0.00 -847.17
G N2 APARTMENT 20-JUL-18:23 0.00 -1088.80 0.00 0.00 141.59 230.46 547.42 744.82 0.00 286.93 0.00 0.00 0.00 0.00 0.00 -862.41
G S1 APARTMENT 30-AUG-12:45 0.00 -1784.49 0.00 0.00 40.50 28.81 388.49 3368.03 0.00 31.37 0.00 0.00 0.00 0.00 0.00 -2072.72
G S2 APARTMENT 30-AUG-12:45 0.00 -1843.31 0.00 0.00 40.55 28.81 388.49 3367.33 0.00 32.69 0.00 0.00 0.00 0.00 0.00 -2014.55
F2 SW APARTMENT 30-AUG-15:30 0.00 -3376.05 0.00 0.00 48.44 100.83 470.89 3991.96 0.00 198.35 0.00 0.00 0.00 0.00 0.00 -1434.42
F2 NW APARTMENT 20-JUL-18:23 0.00 -3031.84 0.00 0.00 141.81 230.46 547.42 2796.49 0.00 434.77 0.00 0.00 0.00 0.00 0.00 -1119.11
F2 SE APARTMENT 30-AUG-13:30 0.00 -3287.02 0.00 0.00 40.75 28.81 382.60 3551.77 0.00 167.61 0.00 0.00 0.00 0.00 0.00 -884.52
F2 NE APARTMENT 23-JUN-09:00 0.00 -2214.38 0.00 0.00 40.75 28.81 394.37 2638.01 0.00 181.80 0.00 0.00 0.00 0.00 0.00 -1069.36
F2 N1 APARTMENT 20-JUL-18:23 0.00 -1573.46 0.00 0.00 141.81 230.46 547.42 722.81 0.00 385.18 0.00 0.00 0.00 0.00 0.00 -454.22
F2 N2 APARTMENT 20-JUL-18:23 0.00 -1555.44 0.00 0.00 141.81 230.46 547.42 723.00 0.00 384.40 0.00 0.00 0.00 0.00 0.00 -471.65
F2 S1 APARTMENT 31-AUG-13:00 0.00 -2352.64 0.00 0.00 40.75 28.81 388.49 2503.85 0.00 347.52 0.00 0.00 0.00 0.00 0.00 -956.78
F2 S2 APARTMENT 31-AUG-13:00 0.00 -2374.87 0.00 0.00 40.75 28.81 388.49 2503.66 0.00 349.07 0.00 0.00 0.00 0.00 0.00 -935.91
F3 SW APARTMENT 19-MAY-16:38 0.00 -3409.11 0.00 0.00 84.76 144.04 588.62 2669.71 0.00 793.67 0.00 0.00 0.00 0.00 0.00 -871.67
F3 NW APARTMENT 20-JUL-18:23 0.00 -3021.43 0.00 0.00 141.81 230.46 547.42 2770.78 0.00 490.52 0.00 0.00 0.00 0.00 0.00 -1159.56
F3 SE APARTMENT 30-AUG-13:15 0.00 -3135.72 0.00 0.00 40.68 28.81 382.60 3578.73 0.00 128.78 0.00 0.00 0.00 0.00 0.00 -1023.88
F3 NE APARTMENT 23-JUN-09:30 0.00 -2271.96 0.00 0.00 40.45 28.81 406.15 2482.38 0.00 346.22 0.00 0.00 0.00 0.00 0.00 -1032.03
F3 N1 APARTMENT 30-JUN-19:15 0.00 -1609.79 0.00 0.00 141.82 230.46 523.87 802.81 0.00 283.47 0.00 0.00 0.00 0.00 0.00 -372.63
F3 N2 APARTMENT 30-JUN-19:15 0.00 -1591.99 0.00 0.00 141.82 230.46 523.87 803.06 0.00 283.00 0.00 0.00 0.00 0.00 0.00 -390.22
F3 S1 APARTMENT 31-AUG-13:00 0.00 -2394.14 0.00 0.00 40.75 28.81 388.49 2477.49 0.00 393.15 0.00 0.00 0.00 0.00 0.00 -934.55
F3 S2 APARTMENT 31-AUG-13:00 0.00 -2405.71 0.00 0.00 40.75 28.81 388.49 2477.37 0.00 394.01 0.00 0.00 0.00 0.00 0.00 -923.72
F4 SW APARTMENT 19-MAY-16:38 0.00 -3417.19 0.00 0.00 84.76 144.04 588.62 2656.30 0.00 857.58 0.00 0.00 0.00 0.00 0.00 -914.11
F4 NW APARTMENT 20-JUL-18:23 0.00 -3031.47 0.00 0.00 141.81 230.46 547.42 2753.43 0.00 533.42 0.00 0.00 0.00 0.00 0.00 -1175.07
F4 SE APARTMENT 30-AUG-13:15 0.00 -3125.06 0.00 0.00 40.66 28.81 382.60 3568.25 0.00 133.35 0.00 0.00 0.00 0.00 0.00 -1028.60
F4 NE APARTMENT 23-JUN-09:15 0.00 -2295.35 0.00 0.00 40.68 28.81 406.15 2551.08 0.00 301.66 0.00 0.00 0.00 0.00 0.00 -1033.02
F4 N1 APARTMENT 30-JUN-19:15 0.00 -1623.53 0.00 0.00 141.81 230.46 523.87 797.64 0.00 302.32 0.00 0.00 0.00 0.00 0.00 -372.58
F4 N2 APARTMENT 30-JUN-19:15 0.00 -1605.82 0.00 0.00 141.81 230.46 523.87 797.90 0.00 301.81 0.00 0.00 0.00 0.00 0.00 -390.04
F4 S1 APARTMENT 31-AUG-12:45 0.00 -2410.25 0.00 0.00 40.75 28.81 388.49 2628.42 0.00 322.40 0.00 0.00 0.00 0.00 0.00 -998.61
F4 S2 APARTMENT 31-AUG-12:45 0.00 -2416.43 0.00 0.00 40.75 28.81 388.49 2628.31 0.00 322.40 0.00 0.00 0.00 0.00 0.00 -992.32
M SW APARTMENT 19-MAY-16:38 0.00 -3445.75 0.00 0.00 84.76 144.04 588.62 2645.95 0.00 910.07 0.00 0.00 0.00 0.00 0.00 -927.68
M NW APARTMENT 20-JUL-18:23 0.00 -3059.71 0.00 0.00 141.81 230.46 547.42 2739.72 0.00 566.36 0.00 0.00 0.00 0.00 0.00 -1166.05
M SE APARTMENT 30-AUG-13:15 0.00 -3155.72 0.00 0.00 40.66 28.81 382.60 3559.31 0.00 138.58 0.00 0.00 0.00 0.00 0.00 -994.24
M NE APARTMENT 23-JUN-09:15 0.00 -2326.04 0.00 0.00 40.67 28.81 406.15 2542.89 0.00 318.26 0.00 0.00 0.00 0.00 0.00 -1010.73
M N1 APARTMENT 30-JUN-19:15 0.00 -1658.38 0.00 0.00 141.81 230.46 523.87 793.22 0.00 317.81 0.00 0.00 0.00 0.00 0.00 -348.80
M N2 APARTMENT 30-JUN-19:15 0.00 -1640.78 0.00 0.00 141.81 230.46 523.87 793.48 0.00 317.28 0.00 0.00 0.00 0.00 0.00 -366.12
M S1 APARTMENT 31-AUG-12:45 0.00 -2446.61 0.00 0.00 40.75 28.81 388.49 2614.02 0.00 342.80 0.00 0.00 0.00 0.00 0.00 -968.25
M S2 APARTMENT 31-AUG-12:45 0.00 -2455.27 0.00 0.00 40.75 28.81 388.49 2613.91 0.00 343.26 0.00 0.00 0.00 0.00 0.00 -959.93
F6 SW APARTMENT 19-MAY-16:38 0.00 -3400.96 0.00 0.00 84.76 144.04 588.62 2639.81 0.00 952.55 0.00 0.00 0.00 0.00 0.00 -1008.81
F6 NW APARTMENT 20-JUL-18:23 0.00 -3014.01 0.00 0.00 141.81 230.46 547.42 2730.45 0.00 592.25 0.00 0.00 0.00 0.00 0.00 -1228.38
F6 SE APARTMENT 30-AUG-13:15 0.00 -3113.54 0.00 0.00 40.66 28.81 382.60 3553.40 0.00 142.18 0.00 0.00 0.00 0.00 0.00 -1034.11
F6 NE APARTMENT 23-JUN-09:15 0.00 -2282.60 0.00 0.00 40.65 28.81 406.15 2538.00 0.00 330.77 0.00 0.00 0.00 0.00 0.00 -1061.77
F6 N1 APARTMENT 30-JUN-19:15 0.00 -1618.86 0.00 0.00 141.81 230.46 523.87 790.83 0.00 329.50 0.00 0.00 0.00 0.00 0.00 -397.62
F6 N2 APARTMENT 19-JUL-18:08 0.00 -1602.27 0.00 0.00 137.34 230.46 547.42 219.35 0.00 276.12 191.58 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 31-AUG-12:45 0.00 -2405.73 0.00 0.00 40.75 28.81 388.49 2603.73 0.00 358.04 0.00 0.00 0.00 0.00 0.00 -1014.09
F6 S2 APARTMENT 31-AUG-12:45 0.00 -2415.67 0.00 0.00 40.75 28.81 388.49 2603.62 0.00 358.77 0.00 0.00 0.00 0.00 0.00 -1004.76
F7 SW APARTMENT 19-MAY-16:38 0.00 -3383.14 0.00 0.00 84.76 144.04 588.62 2633.95 0.00 988.22 0.00 0.00 0.00 0.00 0.00 -1056.44
F7 NW APARTMENT 30-JUN-19:15 0.00 -3002.57 0.00 0.00 141.81 230.46 523.87 2231.41 0.00 394.67 0.00 0.00 0.00 0.00 0.00 -519.66
F7 SE APARTMENT 30-AUG-13:30 0.00 -3097.94 0.00 0.00 40.51 28.81 382.60 3492.43 0.00 193.78 0.00 0.00 0.00 0.00 0.00 -1040.19
F7 NE APARTMENT 23-JUN-09:15 0.00 -2266.82 0.00 0.00 40.65 28.81 406.15 2533.19 0.00 341.64 0.00 0.00 0.00 0.00 0.00 -1083.61
F7 N1 APARTMENT 19-JUL-18:08 0.00 -1613.01 0.00 0.00 137.28 230.46 547.42 218.52 0.00 283.72 195.61 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 19-JUL-18:08 0.00 -1596.57 0.00 0.00 137.23 230.46 547.42 218.72 0.00 281.43 181.32 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 31-AUG-12:45 0.00 -2390.98 0.00 0.00 40.75 28.81 388.49 2594.76 0.00 370.86 0.00 0.00 0.00 0.00 0.00 -1032.69
F7 S2 APARTMENT 31-AUG-12:45 0.00 -2400.93 0.00 0.00 40.75 28.81 388.49 2594.65 0.00 371.60 0.00 0.00 0.00 0.00 0.00 -1023.37
F8 SW APARTMENT 19-MAY-16:38 0.00 -3378.42 0.00 0.00 84.76 144.04 588.62 2628.90 0.00 1020.78 0.00 0.00 0.00 0.00 0.00 -1088.68
F8 NW APARTMENT 20-JUL-18:08 0.00 -2998.64 0.00 0.00 141.81 230.46 547.42 2682.78 0.00 771.96 0.00 0.00 0.00 0.00 0.00 -1375.79
F8 SE APARTMENT 30-AUG-13:30 0.00 -3095.34 0.00 0.00 40.52 28.81 382.60 3485.38 0.00 198.85 0.00 0.00 0.00 0.00 0.00 -1040.83
F8 NE APARTMENT 23-JUN-09:15 0.00 -2264.83 0.00 0.00 40.65 28.81 406.15 2528.60 0.00 351.11 0.00 0.00 0.00 0.00 0.00 -1090.48
F8 N1 APARTMENT 19-JUL-18:08 0.00 -1620.56 0.00 0.00 137.22 230.46 547.42 217.69 0.00 288.87 198.90 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 19-JUL-18:08 0.00 -1604.23 0.00 0.00 137.17 230.46 547.42 217.89 0.00 286.48 184.81 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 31-AUG-12:45 0.00 -2389.27 0.00 0.00 40.75 28.81 388.49 2586.92 0.00 382.33 0.00 0.00 0.00 0.00 0.00 -1038.02
F8 S2 APARTMENT 31-AUG-12:45 0.00 -2399.26 0.00 0.00 40.75 28.81 388.49 2586.80 0.00 383.09 0.00 0.00 0.00 0.00 0.00 -1028.68
F9 SW APARTMENT 19-MAY-16:38 0.00 -3467.34 0.00 0.00 84.76 144.04 588.62 2622.87 0.00 1060.30 0.00 0.00 0.00 0.00 0.00 -1033.25
F9 NW APARTMENT 20-JUL-18:08 0.00 -3087.86 0.00 0.00 141.81 230.46 547.42 2673.91 0.00 797.37 0.00 0.00 0.00 0.00 0.00 -1303.11
F9 SE APARTMENT 30-AUG-13:30 0.00 -3155.54 0.00 0.00 40.64 28.81 382.60 3478.98 0.00 209.18 0.00 0.00 0.00 0.00 0.00 -984.66
F9 NE APARTMENT 19-JUL-18:00 0.00 -2293.57 0.00 0.00 141.81 194.45 588.62 464.47 0.00 660.59 243.63 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 19-JUL-18:08 0.00 -1706.37 0.00 0.00 137.44 230.46 547.42 215.61 0.00 303.71 271.73 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 19-JUL-18:08 0.00 -1689.79 0.00 0.00 137.39 230.46 547.42 215.83 0.00 301.40 257.30 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 31-AUG-13:00 0.00 -2429.46 0.00 0.00 40.75 28.81 388.49 2416.18 0.00 530.00 0.00 0.00 0.00 0.00 0.00 -974.76
F9 S2 APARTMENT 31-AUG-13:00 0.00 -2440.59 0.00 0.00 40.75 28.81 388.49 2416.05 0.00 531.07 0.00 0.00 0.00 0.00 0.00 -964.58
T SW APARTMENT 30-AUG-15:30 0.00 -4214.90 0.00 0.00 48.69 100.83 470.89 3872.87 0.00 268.70 0.00 0.00 0.00 0.00 0.00 -547.09
T NW APARTMENT 14-JUL-18:00 0.00 -3706.36 0.00 0.00 137.54 194.45 588.62 3047.73 0.00 183.71 0.00 0.00 0.00 0.00 0.00 -445.69
T SE APARTMENT 30-AUG-13:30 0.00 -3865.25 0.00 0.00 40.69 28.81 382.60 3430.14 0.00 217.13 0.00 0.00 0.00 0.00 0.00 -234.11
T NE APARTMENT 23-JUN-09:30 0.00 -2826.65 0.00 0.00 40.71 28.81 406.15 2415.99 0.00 494.11 0.00 0.00 0.00 0.00 0.00 -559.11
T N1 APARTMENT 23-JUN-16:00 0.00 -2214.74 0.00 0.00 48.90 100.83 470.89 510.03 0.00 654.94 429.14 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 23-JUN-16:00 0.00 -2214.15 0.00 0.00 48.90 100.83 470.89 510.19 0.00 656.52 426.82 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 30-AUG-13:15 0.00 -3248.00 0.00 0.00 40.37 28.81 382.60 3198.03 0.00 125.03 0.00 0.00 0.00 0.00 0.00 -526.84
T S2 APARTMENT 30-AUG-13:15 0.00 -3259.42 0.00 0.00 40.36 28.81 382.60 3197.64 0.00 124.38 0.00 0.00 0.00 0.00 0.00 -514.36
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-MAY-16:38 0.00 -186739.11 0.00 0.00 6695.84 18221.75 47207.76 91799.91 0.00 63421.80 0.00 0.00 0.00 0.00 -75.51 -40532.43


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-JAN-08:15 2622.03 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1455.66 0.00 -577.01 -1095.02
G NW APARTMENT 11-JAN-08:15 2652.77 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1447.67 0.00 -577.01 -1133.76
OFFICE 11-JAN-08:00 2681.52 0.00 0.00 0.00 0.00 379.58 194.98 0.00 0.00 0.00 0.00 0.00 -1531.32 0.00 -549.68 -1175.08
G NE APARTMENT 11-JAN-08:15 2652.88 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -1444.38 0.00 -577.01 -1137.15
G N1 APARTMENT 27-JAN-08:30 1734.64 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -991.07 0.00 -276.37 -972.87
G N2 APARTMENT 27-JAN-08:30 1733.52 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -991.08 0.00 -276.37 -971.74
G S1 APARTMENT 11-JAN-08:15 1692.87 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -891.23 0.00 -348.04 -959.28
G S2 APARTMENT 11-JAN-08:15 1687.00 0.00 0.00 0.00 73.97 43.21 388.49 0.00 0.00 0.00 0.00 0.00 -891.32 0.00 -348.04 -953.31
F2 SW APARTMENT 06-JAN-04:00 2611.30 0.00 0.00 0.00 189.67 14.40 223.68 0.00 0.00 0.00 0.00 0.00 -1803.90 0.00 -856.53 -378.62
F2 NW APARTMENT 11-JAN-01:00 2685.52 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1974.57 0.00 -629.58 -550.32
F2 SE APARTMENT 11-JAN-01:00 2566.56 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1979.83 0.00 -629.58 -426.11
F2 NE APARTMENT 11-JAN-01:00 2692.56 0.00 0.00 0.00 189.67 14.40 264.88 0.00 0.00 0.00 0.00 0.00 -1976.00 0.00 -629.59 -555.92
F2 N1 APARTMENT 17-NOV-13:25 2512.05 0.00 0.00 0.00 45.96 28.81 388.49 94.12 0.00 0.00 0.00 0.00 0.00 0.00 -2337.73 -731.70
F2 N2 APARTMENT 17-NOV-13:25 2508.16 0.00 0.00 0.00 45.98 28.81 388.49 94.26 0.00 0.00 0.00 0.00 0.00 0.00 -2337.68 -728.01
F2 S1 APARTMENT 17-NOV-13:30 1872.16 0.00 0.00 0.00 42.83 28.81 388.49 148.64 0.00 0.00 0.00 0.00 0.00 0.00 -2340.08 -140.84
F2 S2 APARTMENT 17-NOV-13:30 1881.97 0.00 0.00 0.00 42.73 28.81 388.49 147.54 0.00 0.00 0.00 0.00 0.00 0.00 -2340.34 -149.19
F3 SW APARTMENT 17-NOV-13:25 3088.81 0.00 0.00 0.00 44.12 28.81 388.49 214.58 0.00 0.00 0.00 0.00 0.00 0.00 -2871.99 -892.82
F3 NW APARTMENT 17-NOV-13:25 2899.29 0.00 0.00 0.00 46.25 28.81 388.49 172.28 0.00 0.00 0.00 0.00 0.00 0.00 -2852.80 -682.31
F3 SE APARTMENT 17-NOV-13:25 3070.17 0.00 0.00 0.00 44.24 28.81 388.49 198.60 0.00 0.00 0.00 0.00 0.00 0.00 -2867.20 -863.11
F3 NE APARTMENT 05-JAN-16:00 2852.40 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1572.73 0.00 -1736.14 -41.63
F3 N1 APARTMENT 17-NOV-13:25 2936.77 0.00 0.00 0.00 45.80 28.81 388.49 87.10 0.00 0.00 0.00 0.00 0.00 0.00 -2727.17 -759.79
F3 N2 APARTMENT 17-NOV-13:25 2930.63 0.00 0.00 0.00 45.82 28.81 388.49 87.26 0.00 0.00 0.00 0.00 0.00 0.00 -2727.11 -753.89
F3 S1 APARTMENT 17-NOV-13:30 2227.45 0.00 0.00 0.00 42.31 28.81 388.49 133.86 0.00 0.00 0.00 0.00 0.00 0.00 -2729.47 -91.44
F3 S2 APARTMENT 17-NOV-13:30 2231.04 0.00 0.00 0.00 42.28 28.81 388.49 133.57 0.00 0.00 0.00 0.00 0.00 0.00 -2729.56 -94.62
F4 SW APARTMENT 17-NOV-13:25 3519.88 0.00 0.00 0.00 44.37 28.81 388.49 209.99 0.00 0.00 0.00 0.00 0.00 0.00 -3179.86 -1011.67
F4 NW APARTMENT 17-NOV-13:25 3173.90 0.00 0.00 0.00 46.42 28.81 388.49 168.25 0.00 0.00 0.00 0.00 0.00 0.00 -3169.92 -635.95
F4 SE APARTMENT 17-NOV-13:25 3463.27 0.00 0.00 0.00 44.57 28.81 388.49 196.94 0.00 0.00 0.00 0.00 0.00 0.00 -3177.06 -945.01
F4 NE APARTMENT 05-JAN-16:00 3052.33 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1589.92 0.00 -1941.10 -19.39
F4 N1 APARTMENT 17-NOV-13:25 3227.99 0.00 0.00 0.00 45.86 28.81 388.49 84.09 0.00 0.00 0.00 0.00 0.00 0.00 -3029.72 -745.51
F4 N2 APARTMENT 17-NOV-13:25 3223.83 0.00 0.00 0.00 45.88 28.81 388.49 84.25 0.00 0.00 0.00 0.00 0.00 0.00 -3029.66 -741.59
F4 S1 APARTMENT 17-NOV-13:25 2778.83 0.00 0.00 0.00 42.39 28.81 388.49 128.73 0.00 0.00 0.00 0.00 0.00 0.00 -3071.86 -295.37
F4 S2 APARTMENT 17-NOV-13:25 2785.52 0.00 0.00 0.00 42.38 28.81 388.49 128.75 0.00 0.00 0.00 0.00 0.00 0.00 -3072.05 -301.89
M SW APARTMENT 17-NOV-13:25 3691.64 0.00 0.00 0.00 44.58 28.81 388.49 207.50 0.00 0.00 0.00 0.00 0.00 0.00 -3445.80 -915.21
M NW APARTMENT 17-NOV-13:25 3397.56 0.00 0.00 0.00 46.50 28.81 388.49 164.23 0.00 0.00 0.00 0.00 0.00 0.00 -3436.40 -589.20
M SE APARTMENT 17-NOV-13:25 3643.71 0.00 0.00 0.00 44.78 28.81 388.49 195.04 0.00 0.00 0.00 0.00 0.00 0.00 -3443.15 -857.68
M NE APARTMENT 17-NOV-13:25 3236.87 0.00 0.00 0.00 46.90 28.81 388.49 151.54 0.00 0.00 0.00 0.00 0.00 0.00 -3434.01 -418.60
M N1 APARTMENT 17-NOV-13:25 3478.76 0.00 0.00 0.00 45.87 28.81 388.49 81.37 0.00 0.00 0.00 0.00 0.00 0.00 -3283.99 -739.30
M N2 APARTMENT 17-NOV-13:25 3471.96 0.00 0.00 0.00 45.89 28.81 388.49 81.52 0.00 0.00 0.00 0.00 0.00 0.00 -3283.93 -732.73
M S1 APARTMENT 17-NOV-13:25 3143.15 0.00 0.00 0.00 42.54 28.81 388.49 126.39 0.00 0.00 0.00 0.00 0.00 0.00 -3319.33 -410.05
M S2 APARTMENT 17-NOV-13:25 3145.38 0.00 0.00 0.00 42.55 28.81 388.49 126.49 0.00 0.00 0.00 0.00 0.00 0.00 -3319.41 -412.30
F6 SW APARTMENT 17-NOV-13:25 3819.29 0.00 0.00 0.00 45.10 28.81 388.49 213.26 0.00 0.00 0.00 0.00 0.00 0.00 -3676.91 -818.04
F6 NW APARTMENT 17-NOV-13:25 3519.40 0.00 0.00 0.00 46.86 28.81 388.49 166.96 0.00 0.00 0.00 0.00 0.00 0.00 -3668.34 -482.17
F6 SE APARTMENT 17-NOV-13:25 3774.15 0.00 0.00 0.00 45.28 28.81 388.49 200.36 0.00 0.00 0.00 0.00 0.00 0.00 -3674.71 -762.38
F6 NE APARTMENT 05-JAN-16:00 3393.37 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1611.83 0.00 -2255.87 -23.77
F6 N1 APARTMENT 17-NOV-13:25 3558.75 0.00 0.00 0.00 46.23 28.81 388.49 83.24 0.00 0.00 0.00 0.00 0.00 0.00 -3505.92 -599.59
F6 N2 APARTMENT 17-NOV-13:25 3553.69 0.00 0.00 0.00 46.24 28.81 388.49 83.34 0.00 0.00 0.00 0.00 0.00 0.00 -3505.88 -594.69
F6 S1 APARTMENT 17-NOV-13:25 3837.26 0.00 0.00 0.00 43.13 28.81 388.49 130.41 0.00 0.00 0.00 0.00 0.00 0.00 -3524.53 -903.57
F6 S2 APARTMENT 17-NOV-13:25 3837.23 0.00 0.00 0.00 43.13 28.81 388.49 130.48 0.00 0.00 0.00 0.00 0.00 0.00 -3524.61 -903.53
F7 SW APARTMENT 17-NOV-13:25 3945.03 0.00 0.00 0.00 45.49 28.81 388.49 216.98 0.00 0.00 0.00 0.00 0.00 0.00 -3885.13 -739.66
F7 NW APARTMENT 17-NOV-13:25 3664.59 0.00 0.00 0.00 47.09 28.81 388.49 167.83 0.00 0.00 0.00 0.00 0.00 0.00 -3877.37 -419.45
F7 SE APARTMENT 17-NOV-13:25 3907.11 0.00 0.00 0.00 45.65 28.81 388.49 203.84 0.00 0.00 0.00 0.00 0.00 0.00 -3883.28 -690.62
F7 NE APARTMENT 05-JAN-16:00 3545.75 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1619.43 0.00 -2385.05 -39.36
F7 N1 APARTMENT 17-NOV-13:25 3682.69 0.00 0.00 0.00 46.47 28.81 388.49 84.17 0.00 0.00 0.00 0.00 0.00 0.00 -3705.72 -524.89
F7 N2 APARTMENT 17-NOV-13:25 3678.53 0.00 0.00 0.00 46.48 28.81 388.49 84.23 0.00 0.00 0.00 0.00 0.00 0.00 -3705.69 -520.83
F7 S1 APARTMENT 17-NOV-13:25 4307.17 0.00 0.00 0.00 43.64 28.81 388.49 134.11 0.00 0.00 0.00 0.00 0.00 0.00 -3713.51 -1188.71
F7 S2 APARTMENT 17-NOV-13:25 4312.51 0.00 0.00 0.00 43.64 28.81 388.49 134.16 0.00 0.00 0.00 0.00 0.00 0.00 -3713.59 -1194.01
F8 SW APARTMENT 17-NOV-13:25 4063.74 0.00 0.00 0.00 45.83 28.81 388.49 220.44 0.00 0.00 0.00 0.00 0.00 0.00 -4075.84 -671.47
F8 NW APARTMENT 17-NOV-13:25 3804.54 0.00 0.00 0.00 47.28 28.81 388.49 168.35 0.00 0.00 0.00 0.00 0.00 0.00 -4068.83 -368.62
F8 SE APARTMENT 17-NOV-13:25 4036.55 0.00 0.00 0.00 45.98 28.81 388.49 207.20 0.00 0.00 0.00 0.00 0.00 0.00 -4074.30 -632.73
F8 NE APARTMENT 17-NOV-13:25 3734.88 0.00 0.00 0.00 47.42 28.81 388.49 153.44 0.00 0.00 0.00 0.00 0.00 0.00 -4068.39 -284.64
F8 N1 APARTMENT 15-SEP-08:10 3817.49 0.00 0.00 0.00 43.75 28.81 394.37 22.46 0.00 0.00 0.00 0.00 0.00 0.00 -3180.56 -1126.33
F8 N2 APARTMENT 17-NOV-13:25 3797.22 0.00 0.00 0.00 46.68 28.81 388.49 85.11 0.00 0.00 0.00 0.00 0.00 0.00 -3888.66 -457.65
F8 S1 APARTMENT 17-NOV-13:25 4364.26 0.00 0.00 0.00 44.14 28.81 388.49 138.27 0.00 0.00 0.00 0.00 0.00 0.00 -3895.60 -1068.38
F8 S2 APARTMENT 17-NOV-13:25 4366.04 0.00 0.00 0.00 44.14 28.81 388.49 138.31 0.00 0.00 0.00 0.00 0.00 0.00 -3895.66 -1070.13
F9 SW APARTMENT 17-NOV-13:25 4170.39 0.00 0.00 0.00 46.22 28.81 388.49 226.49 0.00 0.00 0.00 0.00 0.00 0.00 -4252.62 -607.78
F9 NW APARTMENT 17-NOV-13:25 3955.55 0.00 0.00 0.00 47.42 28.81 388.49 169.88 0.00 0.00 0.00 0.00 0.00 0.00 -4246.62 -343.52
F9 SE APARTMENT 17-NOV-13:25 4125.19 0.00 0.00 0.00 46.37 28.81 388.49 213.08 0.00 0.00 0.00 0.00 0.00 0.00 -4251.13 -550.80
F9 NE APARTMENT 17-NOV-13:25 3943.93 0.00 0.00 0.00 47.42 28.81 388.49 153.97 0.00 0.00 0.00 0.00 0.00 0.00 -4246.68 -315.94
F9 N1 APARTMENT 15-SEP-08:10 4045.34 0.00 0.00 0.00 43.88 28.81 394.37 22.94 0.00 0.00 0.00 0.00 0.00 0.00 -3314.01 -1221.33
F9 N2 APARTMENT 15-SEP-08:10 4001.45 0.00 0.00 0.00 43.87 28.81 394.37 22.76 0.00 0.00 0.00 0.00 0.00 0.00 -3313.83 -1177.43
F9 S1 APARTMENT 17-NOV-13:25 4400.38 0.00 0.00 0.00 44.77 28.81 388.49 144.79 0.00 0.00 0.00 0.00 0.00 0.00 -4064.43 -942.82
F9 S2 APARTMENT 17-NOV-13:25 4402.90 0.00 0.00 0.00 44.77 28.81 388.49 144.81 0.00 0.00 0.00 0.00 0.00 0.00 -4064.49 -945.27
T SW APARTMENT 05-JAN-16:00 4589.11 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1420.54 0.00 -2707.54 -959.13
T NW APARTMENT 05-JAN-16:00 4738.36 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1557.92 0.00 -2707.55 -970.98
T SE APARTMENT 05-JAN-16:00 4594.14 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1457.19 0.00 -2707.54 -927.49
T NE APARTMENT 05-JAN-16:00 4743.96 0.00 0.00 0.00 47.42 50.41 400.26 0.00 0.00 0.00 0.00 0.00 -1594.93 0.00 -2707.57 -939.56
T N1 APARTMENT 15-SEP-08:25 4161.15 0.00 0.00 0.00 44.33 28.81 394.37 62.64 0.00 0.00 0.00 0.00 0.00 0.00 -3608.37 -1082.93
T N2 APARTMENT 15-SEP-08:25 4166.64 0.00 0.00 0.00 44.19 28.81 394.37 60.62 0.00 0.00 0.00 0.00 0.00 0.00 -3608.57 -1086.07
T S1 APARTMENT 17-NOV-13:25 4805.64 0.00 0.00 0.00 44.12 28.81 388.49 140.02 0.00 0.00 0.00 0.00 0.00 0.00 -4231.66 -1175.42
T S2 APARTMENT 17-NOV-13:25 4811.39 0.00 0.00 0.00 44.11 28.81 388.49 139.91 0.00 0.00 0.00 0.00 0.00 0.00 -4231.83 -1180.87
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-NOV-13:25 261846.88 0.00 0.00 0.00 3667.77 10361.29 31389.06 12444.84 0.00 0.00 0.00 0.00 0.00 0.00 -266417.64 -53292.20



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Sec1.1A-General Information

Data
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 143.00
Number of hours cooling loads not met 147.50
Number of hours not met 290.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.22 10720.10 0.00 0.00 0.00 0.00
Space Heating 263.76 73815.64 902.48 231254.76 0.00 0.00
Space Cooling 245.02 0.00 0.00 0.00 0.00 0.00
Pumps 45.41 1453.23 0.00 0.00 0.00 0.00
Heat Rejection 8.68 0.00 0.00 0.00 0.00 0.00
Fans-Interior 702.48 22275.35 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1278.59 87362.79 0.00 0.00
Receptacle Equipment 1131.09 51564.86 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3001.91   2181.08   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3001.91
Natural Gas 0.00 2181.08
Additional 0.00 0.00
Total 1131.09 5182.98


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 33.66
Space Cooling 31.27
Fans-Interior 89.64
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 31.03
Subtotal 383.07


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 115.16
Service Water Heating 163.16
Miscellaneous 0.00
Subtotal 278.32


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 8.03
Space Heating 22.50
Space Cooling 4.73
Fans-Interior 13.55
Service Water Heating 24.67
Receptacle Equipment 21.82
Miscellaneous 4.69



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.258674
G NW APARTMENT DIRECT AIR 0.232095
OFFICE DIRECT AIR 0.348674
G NE APARTMENT DIRECT AIR 0.165424
G N1 APARTMENT DIRECT AIR 0.112723
G N2 APARTMENT DIRECT AIR 0.111326
G S1 APARTMENT DIRECT AIR 0.167600
G S2 APARTMENT DIRECT AIR 0.173541
F2 SW APARTMENT DIRECT AIR 0.339339
F2 NW APARTMENT DIRECT AIR 0.301290
F2 SE APARTMENT DIRECT AIR 0.324879
F2 NE APARTMENT DIRECT AIR 0.221619
F2 N1 APARTMENT DIRECT AIR 0.157670
F2 N2 APARTMENT DIRECT AIR 0.155935
F2 S1 APARTMENT DIRECT AIR 0.224061
F2 S2 APARTMENT DIRECT AIR 0.226397
F3 SW APARTMENT DIRECT AIR 0.340604
F3 NW APARTMENT DIRECT AIR 0.304082
F3 SE APARTMENT DIRECT AIR 0.309621
F3 NE APARTMENT DIRECT AIR 0.226111
F3 N1 APARTMENT DIRECT AIR 0.162262
F3 N2 APARTMENT DIRECT AIR 0.160543
F3 S1 APARTMENT DIRECT AIR 0.228268
F3 S2 APARTMENT DIRECT AIR 0.229475
F4 SW APARTMENT DIRECT AIR 0.341360
F4 NW APARTMENT DIRECT AIR 0.305205
F4 SE APARTMENT DIRECT AIR 0.309293
F4 NE APARTMENT DIRECT AIR 0.227415
F4 N1 APARTMENT DIRECT AIR 0.163921
F4 N2 APARTMENT DIRECT AIR 0.162208
F4 S1 APARTMENT DIRECT AIR 0.229638
F4 S2 APARTMENT DIRECT AIR 0.230688
M SW APARTMENT DIRECT AIR 0.344468
M NW APARTMENT DIRECT AIR 0.308709
M SE APARTMENT DIRECT AIR 0.312737
M NE APARTMENT DIRECT AIR 0.230938
M N1 APARTMENT DIRECT AIR 0.167574
M N2 APARTMENT DIRECT AIR 0.165868
M S1 APARTMENT DIRECT AIR 0.233097
M S2 APARTMENT DIRECT AIR 0.234123
F6 SW APARTMENT DIRECT AIR 0.340388
F6 NW APARTMENT DIRECT AIR 0.304773
F6 SE APARTMENT DIRECT AIR 0.309168
F6 NE APARTMENT DIRECT AIR 0.227191
F6 N1 APARTMENT DIRECT AIR 0.164107
F6 N2 APARTMENT DIRECT AIR 0.162415
F6 S1 APARTMENT DIRECT AIR 0.229375
F6 S2 APARTMENT DIRECT AIR 0.230399
F7 SW APARTMENT DIRECT AIR 0.338962
F7 NW APARTMENT DIRECT AIR 0.303558
F7 SE APARTMENT DIRECT AIR 0.308187
F7 NE APARTMENT DIRECT AIR 0.226079
F7 N1 APARTMENT DIRECT AIR 0.163177
F7 N2 APARTMENT DIRECT AIR 0.161496
F7 S1 APARTMENT DIRECT AIR 0.228221
F7 S2 APARTMENT DIRECT AIR 0.229245
F8 SW APARTMENT DIRECT AIR 0.338959
F8 NW APARTMENT DIRECT AIR 0.303762
F8 SE APARTMENT DIRECT AIR 0.308491
F8 NE APARTMENT DIRECT AIR 0.226268
F8 N1 APARTMENT DIRECT AIR 0.163648
F8 N2 APARTMENT DIRECT AIR 0.161979
F8 S1 APARTMENT DIRECT AIR 0.228388
F8 S2 APARTMENT DIRECT AIR 0.229414
F9 SW APARTMENT DIRECT AIR 0.348830
F9 NW APARTMENT DIRECT AIR 0.313294
F9 SE APARTMENT DIRECT AIR 0.315327
F9 NE APARTMENT DIRECT AIR 0.229080
F9 N1 APARTMENT DIRECT AIR 0.172070
F9 N2 APARTMENT DIRECT AIR 0.170381
F9 S1 APARTMENT DIRECT AIR 0.234017
F9 S2 APARTMENT DIRECT AIR 0.235173
T SW APARTMENT DIRECT AIR 0.425870
T NW APARTMENT DIRECT AIR 0.374854
T SE APARTMENT DIRECT AIR 0.387991
T NE APARTMENT DIRECT AIR 0.280186
T N1 APARTMENT DIRECT AIR 0.212298
T N2 APARTMENT DIRECT AIR 0.211810
T S1 APARTMENT DIRECT AIR 0.318683
T S2 APARTMENT DIRECT AIR 0.319814


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.258674
AIRLOOP G NW MAIN BRANCH 0.232095
AIRLOOP OFFICE MAIN BRANCH 0.348674
AIRLOOP G NE MAIN BRANCH 0.165424
AIRLOOP G N1 MAIN BRANCH 0.112723
AIRLOOP G N2 MAIN BRANCH 0.111326
AIRLOOP G S1 MAIN BRANCH 0.167600
AIRLOOP G S2 MAIN BRANCH 0.173541
AIRLOOP F2 SW MAIN BRANCH 0.339339
AIRLOOP F2 NW MAIN BRANCH 0.301290
AIRLOOP F2 SE MAIN BRANCH 0.324879
AIRLOOP F2 NE MAIN BRANCH 0.221619
AIRLOOP F2 N1 MAIN BRANCH 0.157670
AIRLOOP F2 N2 MAIN BRANCH 0.155935
AIRLOOP F2 S1 MAIN BRANCH 0.224061
AIRLOOP F2 S2 MAIN BRANCH 0.226397
AIRLOOP F3 SW MAIN BRANCH 0.340604
AIRLOOP F3 NW MAIN BRANCH 0.304082
AIRLOOP F3 SE MAIN BRANCH 0.309621
AIRLOOP F3 NE MAIN BRANCH 0.226111
AIRLOOP F3 N1 MAIN BRANCH 0.162262
AIRLOOP F3 N2 MAIN BRANCH 0.160543
AIRLOOP F3 S1 MAIN BRANCH 0.228268
AIRLOOP F3 S2 MAIN BRANCH 0.229475
AIRLOOP F4 SW MAIN BRANCH 0.341360
AIRLOOP F4 NW MAIN BRANCH 0.305205
AIRLOOP F4 SE MAIN BRANCH 0.309293
AIRLOOP F4 NE MAIN BRANCH 0.227415
AIRLOOP F4 N1 MAIN BRANCH 0.163921
AIRLOOP F4 N2 MAIN BRANCH 0.162208
AIRLOOP F4 S1 MAIN BRANCH 0.229638
AIRLOOP F4 S2 MAIN BRANCH 0.230688
AIRLOOP M SW MAIN BRANCH 0.344468
AIRLOOP M NW MAIN BRANCH 0.308709
AIRLOOP M SE MAIN BRANCH 0.312737
AIRLOOP M NE MAIN BRANCH 0.230938
AIRLOOP M N1 MAIN BRANCH 0.167574
AIRLOOP M N2 MAIN BRANCH 0.165868
AIRLOOP M S1 MAIN BRANCH 0.233097
AIRLOOP M S2 MAIN BRANCH 0.234123
AIRLOOP F6 SW MAIN BRANCH 0.340388
AIRLOOP F6 NW MAIN BRANCH 0.304773
AIRLOOP F6 SE MAIN BRANCH 0.309168
AIRLOOP F6 NE MAIN BRANCH 0.227191
AIRLOOP F6 N1 MAIN BRANCH 0.164107
AIRLOOP F6 N2 MAIN BRANCH 0.162415
AIRLOOP F6 S1 MAIN BRANCH 0.229375
AIRLOOP F6 S2 MAIN BRANCH 0.230399
AIRLOOP F7 SW MAIN BRANCH 0.338962
AIRLOOP F7 NW MAIN BRANCH 0.303558
AIRLOOP F7 SE MAIN BRANCH 0.308187
AIRLOOP F7 NE MAIN BRANCH 0.226079
AIRLOOP F7 N1 MAIN BRANCH 0.163177
AIRLOOP F7 N2 MAIN BRANCH 0.161496
AIRLOOP F7 S1 MAIN BRANCH 0.228221
AIRLOOP F7 S2 MAIN BRANCH 0.229245
AIRLOOP F8 SW MAIN BRANCH 0.338959
AIRLOOP F8 NW MAIN BRANCH 0.303762
AIRLOOP F8 SE MAIN BRANCH 0.308491
AIRLOOP F8 NE MAIN BRANCH 0.226268
AIRLOOP F8 N1 MAIN BRANCH 0.163648
AIRLOOP F8 N2 MAIN BRANCH 0.161979
AIRLOOP F8 S1 MAIN BRANCH 0.228388
AIRLOOP F8 S2 MAIN BRANCH 0.229414
AIRLOOP F9 SW MAIN BRANCH 0.348830
AIRLOOP F9 NW MAIN BRANCH 0.313294
AIRLOOP F9 SE MAIN BRANCH 0.315327
AIRLOOP F9 NE MAIN BRANCH 0.229080
AIRLOOP F9 N1 MAIN BRANCH 0.172070
AIRLOOP F9 N2 MAIN BRANCH 0.170381
AIRLOOP F9 S1 MAIN BRANCH 0.234017
AIRLOOP F9 S2 MAIN BRANCH 0.235173
AIRLOOP T SW MAIN BRANCH 0.425870
AIRLOOP T NW MAIN BRANCH 0.374854
AIRLOOP T SE MAIN BRANCH 0.387991
AIRLOOP T NE MAIN BRANCH 0.280186
AIRLOOP T N1 MAIN BRANCH 0.212298
AIRLOOP T N2 MAIN BRANCH 0.211810
AIRLOOP T S1 MAIN BRANCH 0.318683
AIRLOOP T S2 MAIN BRANCH 0.319814


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.258674
AIRLOOP G NW 0.232095
AIRLOOP OFFICE 0.348674
AIRLOOP G NE 0.165424
AIRLOOP G N1 0.112723
AIRLOOP G N2 0.111326
AIRLOOP G S1 0.167600
AIRLOOP G S2 0.173541
AIRLOOP F2 SW 0.339339
AIRLOOP F2 NW 0.301290
AIRLOOP F2 SE 0.324879
AIRLOOP F2 NE 0.221619
AIRLOOP F2 N1 0.157670
AIRLOOP F2 N2 0.155935
AIRLOOP F2 S1 0.224061
AIRLOOP F2 S2 0.226397
AIRLOOP F3 SW 0.340604
AIRLOOP F3 NW 0.304082
AIRLOOP F3 SE 0.309621
AIRLOOP F3 NE 0.226111
AIRLOOP F3 N1 0.162262
AIRLOOP F3 N2 0.160543
AIRLOOP F3 S1 0.228268
AIRLOOP F3 S2 0.229475
AIRLOOP F4 SW 0.341360
AIRLOOP F4 NW 0.305205
AIRLOOP F4 SE 0.309293
AIRLOOP F4 NE 0.227415
AIRLOOP F4 N1 0.163921
AIRLOOP F4 N2 0.162208
AIRLOOP F4 S1 0.229638
AIRLOOP F4 S2 0.230688
AIRLOOP M SW 0.344468
AIRLOOP M NW 0.308709
AIRLOOP M SE 0.312737
AIRLOOP M NE 0.230938
AIRLOOP M N1 0.167574
AIRLOOP M N2 0.165868
AIRLOOP M S1 0.233097
AIRLOOP M S2 0.234123
AIRLOOP F6 SW 0.340388
AIRLOOP F6 NW 0.304773
AIRLOOP F6 SE 0.309168
AIRLOOP F6 NE 0.227191
AIRLOOP F6 N1 0.164107
AIRLOOP F6 N2 0.162415
AIRLOOP F6 S1 0.229375
AIRLOOP F6 S2 0.230399
AIRLOOP F7 SW 0.338962
AIRLOOP F7 NW 0.303558
AIRLOOP F7 SE 0.308187
AIRLOOP F7 NE 0.226079
AIRLOOP F7 N1 0.163177
AIRLOOP F7 N2 0.161496
AIRLOOP F7 S1 0.228221
AIRLOOP F7 S2 0.229245
AIRLOOP F8 SW 0.338959
AIRLOOP F8 NW 0.303762
AIRLOOP F8 SE 0.308491
AIRLOOP F8 NE 0.226268
AIRLOOP F8 N1 0.163648
AIRLOOP F8 N2 0.161979
AIRLOOP F8 S1 0.228388
AIRLOOP F8 S2 0.229414
AIRLOOP F9 SW 0.348830
AIRLOOP F9 NW 0.313294
AIRLOOP F9 SE 0.315327
AIRLOOP F9 NE 0.229080
AIRLOOP F9 N1 0.172070
AIRLOOP F9 N2 0.170381
AIRLOOP F9 S1 0.234017
AIRLOOP F9 S2 0.235173
AIRLOOP T SW 0.425870
AIRLOOP T NW 0.374854
AIRLOOP T SE 0.387991
AIRLOOP T NE 0.280186
AIRLOOP T N1 0.212298
AIRLOOP T N2 0.211810
AIRLOOP T S1 0.318683
AIRLOOP T S2 0.319814


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.258674 0.025952
AIRLOOP G NW OA CONTROLLER 0.232095 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.348674 0.038103
AIRLOOP G NE OA CONTROLLER 0.165424 0.025952
AIRLOOP G N1 OA CONTROLLER 0.112723 0.025952
AIRLOOP G N2 OA CONTROLLER 0.111326 0.025952
AIRLOOP G S1 OA CONTROLLER 0.167600 0.025952
AIRLOOP G S2 OA CONTROLLER 0.173541 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.339339 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.301290 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.324879 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.221619 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.157670 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.155935 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.224061 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.226397 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.340604 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.304082 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.309621 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.226111 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.162262 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.160543 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.228268 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.229475 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.341360 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.305205 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.309293 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.227415 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.163921 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.162208 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.229638 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.230688 0.025952
AIRLOOP M SW OA CONTROLLER 0.344468 0.025952
AIRLOOP M NW OA CONTROLLER 0.308709 0.025952
AIRLOOP M SE OA CONTROLLER 0.312737 0.025952
AIRLOOP M NE OA CONTROLLER 0.230938 0.025952
AIRLOOP M N1 OA CONTROLLER 0.167574 0.025952
AIRLOOP M N2 OA CONTROLLER 0.165868 0.025952
AIRLOOP M S1 OA CONTROLLER 0.233097 0.025952
AIRLOOP M S2 OA CONTROLLER 0.234123 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.340388 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.304773 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.309168 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.227191 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.164107 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.162415 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.229375 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.230399 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.338962 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.303558 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.308187 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.226079 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.163177 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.161496 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.228221 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.229245 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.338959 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.303762 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.308491 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.226268 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.163648 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.161979 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.228388 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.229414 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.348830 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.313294 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.315327 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.229080 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.172070 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.170381 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.234017 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.235173 0.025952
AIRLOOP T SW OA CONTROLLER 0.425870 0.025952
AIRLOOP T NW OA CONTROLLER 0.374854 0.025952
AIRLOOP T SE OA CONTROLLER 0.387991 0.025952
AIRLOOP T NE OA CONTROLLER 0.280186 0.025952
AIRLOOP T N1 OA CONTROLLER 0.212298 0.025952
AIRLOOP T N2 OA CONTROLLER 0.211810 0.025952
AIRLOOP T S1 OA CONTROLLER 0.318683 0.025952
AIRLOOP T S2 OA CONTROLLER 0.319814 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.258674 3321.43 2275.47 0.000073
HEAT PUMP COOLING MODE AIRLOOP G NW 0.232095 2949.73 2029.06 0.000064
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.348674 4577.95 3120.77 0.000100
HEAT PUMP COOLING MODE AIRLOOP G NE 0.165424 2081.33 1451.43 0.000045
HEAT PUMP COOLING MODE AIRLOOP G N1 0.112723 1401.26 982.07 0.000031
HEAT PUMP COOLING MODE AIRLOOP G N2 0.111326 1382.83 969.98 0.000030
HEAT PUMP COOLING MODE AIRLOOP G S1 0.167600 2254.65 1527.00 0.000049
HEAT PUMP COOLING MODE AIRLOOP G S2 0.173541 2330.41 1578.49 0.000051
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.339339 4333.48 2969.14 0.000095
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.301290 3817.10 2623.83 0.000083
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.324879 4220.88 2879.05 0.000092
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.221619 2777.95 1932.30 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.157670 1970.77 1369.60 0.000043
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.155935 1948.47 1354.58 0.000043
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.224061 2964.33 2014.00 0.000065
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.226397 2994.12 2034.22 0.000065
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.340604 4338.86 2977.99 0.000095
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.304082 3842.03 2645.89 0.000084
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.309621 4016.05 2745.17 0.000088
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.226111 2824.91 1969.13 0.000062
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.162262 2023.57 1408.16 0.000044
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.160543 2001.49 1393.28 0.000044
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.228268 3011.76 2049.21 0.000066
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.229475 3027.15 2059.66 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.341360 4340.46 2982.97 0.000095
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.305205 3857.98 2659.91 0.000084
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.309293 4004.06 2740.82 0.000087
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.227415 2850.73 1986.09 0.000062
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.163921 2040.22 1421.62 0.000045
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.162208 2018.24 1406.81 0.000044
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.229638 3024.55 2060.16 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.230688 3037.94 2069.24 0.000066
HEAT PUMP COOLING MODE AIRLOOP M SW 0.344468 4373.53 3008.55 0.000096
HEAT PUMP COOLING MODE AIRLOOP M NW 0.308709 3896.13 2688.92 0.000085
HEAT PUMP COOLING MODE AIRLOOP M SE 0.312737 4047.10 2771.69 0.000088
HEAT PUMP COOLING MODE AIRLOOP M NE 0.230938 2889.37 2015.33 0.000063
HEAT PUMP COOLING MODE AIRLOOP M N1 0.167574 2083.34 1452.51 0.000046
HEAT PUMP COOLING MODE AIRLOOP M N2 0.165868 2061.46 1437.75 0.000045
HEAT PUMP COOLING MODE AIRLOOP M S1 0.233097 3064.80 2089.34 0.000067
HEAT PUMP COOLING MODE AIRLOOP M S2 0.234123 3077.88 2098.22 0.000067
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.340388 4315.91 2972.23 0.000094
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.304773 3840.33 2653.84 0.000084
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.309168 3996.27 2739.80 0.000087
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.227191 2836.62 1982.01 0.000062
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.164107 2035.60 1421.90 0.000044
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.162415 2013.91 1407.26 0.000044
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.229375 3014.15 2056.52 0.000066
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.230399 3027.21 2065.38 0.000066
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.338962 4292.82 2958.96 0.000094
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.303558 3819.94 2642.41 0.000083
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.308187 3979.05 2730.42 0.000087
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.226079 2817.98 1971.56 0.000062
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.163177 2020.84 1413.32 0.000044
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.161496 1999.30 1398.78 0.000044
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.228221 2996.62 2045.99 0.000065
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.229245 3009.66 2054.84 0.000066
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.338959 4288.38 2958.09 0.000094
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.303762 3818.16 2643.33 0.000083
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.308491 3978.66 2732.22 0.000087
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.226268 2816.33 1972.42 0.000062
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.163648 2024.36 1416.91 0.000044
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.161979 2002.99 1402.48 0.000044
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.228388 2996.17 2046.93 0.000065
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.229414 3009.25 2055.81 0.000066
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.348830 4410.10 3042.56 0.000096
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.313294 3935.64 2724.88 0.000086
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.315327 4061.64 2790.51 0.000089
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.229080 2848.25 1995.97 0.000062
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.172070 2130.01 1489.31 0.000047
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.170381 2108.40 1474.71 0.000046
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.234017 3065.43 2095.16 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.235173 3080.16 2105.16 0.000067
HEAT PUMP COOLING MODE AIRLOOP T SW 0.425870 5444.80 3736.06 0.000119
HEAT PUMP COOLING MODE AIRLOOP T NW 0.374854 4746.24 3270.83 0.000104
HEAT PUMP COOLING MODE AIRLOOP T SE 0.387991 4976.68 3415.03 0.000109
HEAT PUMP COOLING MODE AIRLOOP T NE 0.280186 3521.11 2448.04 0.000077
HEAT PUMP COOLING MODE AIRLOOP T N1 0.212298 2774.22 1901.55 0.000061
HEAT PUMP COOLING MODE AIRLOOP T N2 0.211810 2774.49 1900.02 0.000061
HEAT PUMP COOLING MODE AIRLOOP T S1 0.318683 4141.10 2826.61 0.000090
HEAT PUMP COOLING MODE AIRLOOP T S2 0.319814 4155.52 2836.38 0.000091


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.258674 0.258674 0.258674 0.258674 3321.43 3321.43 4534.09 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.232095 0.232095 0.232095 0.232095 2949.73 2949.73 4551.33 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.348674 0.348674 0.348674 0.348674 4577.95 4577.95 5645.56 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.165424 0.165424 0.165424 0.165424 2081.33 2081.33 4557.69 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.112723 0.112723 0.112723 0.112723 1401.26 1401.26 3509.82 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.111326 0.111326 0.111326 0.111326 1382.83 1382.83 3509.96 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.167600 0.167600 0.167600 0.167600 2254.65 2254.65 3490.03 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.173541 0.173541 0.173541 0.173541 2330.41 2330.41 3498.64 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.339339 0.339339 0.339339 0.339339 4333.48 4333.48 4373.81 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.301290 0.301290 0.301290 0.301290 3817.10 3817.10 4380.70 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.324879 0.324879 0.324879 0.324879 4220.88 4220.88 4403.48 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.221619 0.221619 0.221619 0.221619 2777.95 2777.95 4386.02 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.157670 0.157670 0.157670 0.157670 1970.77 1970.77 3123.89 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.155935 0.155935 0.155935 0.155935 1948.47 1948.47 3124.01 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.224061 0.224061 0.224061 0.224061 2964.33 2964.33 3120.05 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.226397 0.226397 0.226397 0.226397 2994.12 2994.12 3121.65 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.340604 0.340604 0.340604 0.340604 4338.86 4338.86 4357.28 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.304082 0.304082 0.304082 0.304082 3842.03 3842.03 4363.85 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.309621 0.309621 0.309621 0.309621 4016.05 4016.05 4363.10 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.226111 0.226111 0.226111 0.226111 2824.91 2824.91 4367.23 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.162262 0.162262 0.162262 0.162262 2023.57 2023.57 3065.51 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.160543 0.160543 0.160543 0.160543 2001.49 2001.49 3065.59 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.228268 0.228268 0.228268 0.228268 3011.76 3011.76 3060.00 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.229475 0.229475 0.229475 0.229475 3027.15 3027.15 3060.29 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.341360 0.341360 0.341360 0.341360 4340.46 4340.46 4415.39 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.305205 0.305205 0.305205 0.305205 3857.98 3857.98 4420.18 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.309293 0.309293 0.309293 0.309293 4004.06 4004.06 4417.35 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.227415 0.227415 0.227415 0.227415 2850.73 2850.73 4421.90 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.163921 0.163921 0.163921 0.163921 2040.22 2040.22 3086.39 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.162208 0.162208 0.162208 0.162208 2018.24 2018.24 3086.43 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.229638 0.229638 0.229638 0.229638 3024.55 3024.55 3082.39 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.230688 0.230688 0.230688 0.230688 3037.94 3037.94 3082.45 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.344468 0.344468 0.344468 0.344468 4373.53 4373.53 4450.02 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.308709 0.308709 0.308709 0.308709 3896.13 3896.13 4451.64 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.312737 0.312737 0.312737 0.312737 4047.10 4047.10 4450.33 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.230938 0.230938 0.230938 0.230938 2889.37 2889.37 4451.92 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.167574 0.167574 0.167574 0.167574 2083.34 2083.34 3090.00 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.165868 0.165868 0.165868 0.165868 2061.46 2061.46 3090.01 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.233097 0.233097 0.233097 0.233097 3064.80 3064.80 3089.17 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.234123 0.234123 0.234123 0.234123 3077.88 3077.88 3089.18 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.340388 0.340388 0.340388 0.340388 4315.91 4315.91 4551.47 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.304773 0.304773 0.304773 0.304773 3840.33 3840.33 4552.09 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.309168 0.309168 0.309168 0.309168 3996.27 3996.27 4550.49 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.227191 0.227191 0.227191 0.227191 2836.62 2836.62 4551.11 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.164107 0.164107 0.164107 0.164107 2035.60 2035.60 3164.95 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.162415 0.162415 0.162415 0.162415 2013.91 2013.91 3164.93 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.229375 0.229375 0.229375 0.229375 3014.15 3014.15 3165.08 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.230399 0.230399 0.230399 0.230399 3027.21 3027.21 3165.06 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.338962 0.338962 0.338962 0.338962 4292.82 4292.82 4621.52 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.303558 0.303558 0.303558 0.303558 3819.94 3819.94 4620.14 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.308187 0.308187 0.308187 0.308187 3979.05 3979.05 4619.42 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.226079 0.226079 0.226079 0.226079 2817.98 2817.98 4618.03 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.163177 0.163177 0.163177 0.163177 2020.84 2020.84 3211.74 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.161496 0.161496 0.161496 0.161496 1999.30 1999.30 3211.69 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.228221 0.228221 0.228221 0.228221 2996.62 2996.62 3213.91 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.229245 0.229245 0.229245 0.229245 3009.66 3009.66 3213.86 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.338959 0.338959 0.338959 0.338959 4288.38 4288.38 4699.52 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.303762 0.303762 0.303762 0.303762 3818.16 3818.16 4695.90 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.308491 0.308491 0.308491 0.308491 3978.66 3978.66 4696.40 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.226268 0.226268 0.226268 0.226268 2816.33 2816.33 4692.78 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.163648 0.163648 0.163648 0.163648 2024.36 2024.36 3268.80 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.161979 0.161979 0.161979 0.161979 2002.99 2002.99 3268.73 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.228388 0.228388 0.228388 0.228388 2996.17 2996.17 3273.23 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.229414 0.229414 0.229414 0.229414 3009.25 3009.25 3273.16 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.348830 0.348830 0.348830 0.348830 4410.10 4410.10 4961.73 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.313294 0.313294 0.313294 0.313294 3935.64 3935.64 4952.20 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.315327 0.315327 0.315327 0.315327 4061.64 4061.64 4957.64 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.229080 0.229080 0.229080 0.229080 2848.25 2848.25 4948.11 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.172070 0.172070 0.172070 0.172070 2130.01 2130.01 3496.16 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.170381 0.170381 0.170381 0.170381 2108.40 2108.40 3496.07 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.234017 0.234017 0.234017 0.234017 3065.43 3065.43 3506.07 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.235173 0.235173 0.235173 0.235173 3080.16 3080.16 3505.98 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.425870 0.425870 0.425870 0.425870 5444.80 5444.80 5962.64 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.374854 0.374854 0.374854 0.374854 4746.24 4746.24 5961.99 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.387991 0.387991 0.387991 0.387991 4976.68 4976.68 5958.10 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.280186 0.280186 0.280186 0.280186 3521.11 3521.11 5957.44 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.212298 0.212298 0.212298 0.212298 2774.22 2774.22 4570.69 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.211810 0.211810 0.211810 0.211810 2774.49 2774.49 4570.58 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.318683 0.318683 0.318683 0.318683 4141.10 4141.10 4568.86 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.319814 0.319814 0.319814 0.319814 4155.52 4155.52 4568.76 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.258674
AIRLOOP G NW SUPPLY FAN 0.232095
AIRLOOP OFFICE SUPPLY FAN 0.348674
AIRLOOP G NE SUPPLY FAN 0.165424
AIRLOOP G N1 SUPPLY FAN 0.112723
AIRLOOP G N2 SUPPLY FAN 0.111326
AIRLOOP G S1 SUPPLY FAN 0.167600
AIRLOOP G S2 SUPPLY FAN 0.173541
AIRLOOP F2 SW SUPPLY FAN 0.339339
AIRLOOP F2 NW SUPPLY FAN 0.301290
AIRLOOP F2 SE SUPPLY FAN 0.324879
AIRLOOP F2 NE SUPPLY FAN 0.221619
AIRLOOP F2 N1 SUPPLY FAN 0.157670
AIRLOOP F2 N2 SUPPLY FAN 0.155935
AIRLOOP F2 S1 SUPPLY FAN 0.224061
AIRLOOP F2 S2 SUPPLY FAN 0.226397
AIRLOOP F3 SW SUPPLY FAN 0.340604
AIRLOOP F3 NW SUPPLY FAN 0.304082
AIRLOOP F3 SE SUPPLY FAN 0.309621
AIRLOOP F3 NE SUPPLY FAN 0.226111
AIRLOOP F3 N1 SUPPLY FAN 0.162262
AIRLOOP F3 N2 SUPPLY FAN 0.160543
AIRLOOP F3 S1 SUPPLY FAN 0.228268
AIRLOOP F3 S2 SUPPLY FAN 0.229475
AIRLOOP F4 SW SUPPLY FAN 0.341360
AIRLOOP F4 NW SUPPLY FAN 0.305205
AIRLOOP F4 SE SUPPLY FAN 0.309293
AIRLOOP F4 NE SUPPLY FAN 0.227415
AIRLOOP F4 N1 SUPPLY FAN 0.163921
AIRLOOP F4 N2 SUPPLY FAN 0.162208
AIRLOOP F4 S1 SUPPLY FAN 0.229638
AIRLOOP F4 S2 SUPPLY FAN 0.230688
AIRLOOP M SW SUPPLY FAN 0.344468
AIRLOOP M NW SUPPLY FAN 0.308709
AIRLOOP M SE SUPPLY FAN 0.312737
AIRLOOP M NE SUPPLY FAN 0.230938
AIRLOOP M N1 SUPPLY FAN 0.167574
AIRLOOP M N2 SUPPLY FAN 0.165868
AIRLOOP M S1 SUPPLY FAN 0.233097
AIRLOOP M S2 SUPPLY FAN 0.234123
AIRLOOP F6 SW SUPPLY FAN 0.340388
AIRLOOP F6 NW SUPPLY FAN 0.304773
AIRLOOP F6 SE SUPPLY FAN 0.309168
AIRLOOP F6 NE SUPPLY FAN 0.227191
AIRLOOP F6 N1 SUPPLY FAN 0.164107
AIRLOOP F6 N2 SUPPLY FAN 0.162415
AIRLOOP F6 S1 SUPPLY FAN 0.229375
AIRLOOP F6 S2 SUPPLY FAN 0.230399
AIRLOOP F7 SW SUPPLY FAN 0.338962
AIRLOOP F7 NW SUPPLY FAN 0.303558
AIRLOOP F7 SE SUPPLY FAN 0.308187
AIRLOOP F7 NE SUPPLY FAN 0.226079
AIRLOOP F7 N1 SUPPLY FAN 0.163177
AIRLOOP F7 N2 SUPPLY FAN 0.161496
AIRLOOP F7 S1 SUPPLY FAN 0.228221
AIRLOOP F7 S2 SUPPLY FAN 0.229245
AIRLOOP F8 SW SUPPLY FAN 0.338959
AIRLOOP F8 NW SUPPLY FAN 0.303762
AIRLOOP F8 SE SUPPLY FAN 0.308491
AIRLOOP F8 NE SUPPLY FAN 0.226268
AIRLOOP F8 N1 SUPPLY FAN 0.163648
AIRLOOP F8 N2 SUPPLY FAN 0.161979
AIRLOOP F8 S1 SUPPLY FAN 0.228388
AIRLOOP F8 S2 SUPPLY FAN 0.229414
AIRLOOP F9 SW SUPPLY FAN 0.348830
AIRLOOP F9 NW SUPPLY FAN 0.313294
AIRLOOP F9 SE SUPPLY FAN 0.315327
AIRLOOP F9 NE SUPPLY FAN 0.229080
AIRLOOP F9 N1 SUPPLY FAN 0.172070
AIRLOOP F9 N2 SUPPLY FAN 0.170381
AIRLOOP F9 S1 SUPPLY FAN 0.234017
AIRLOOP F9 S2 SUPPLY FAN 0.235173
AIRLOOP T SW SUPPLY FAN 0.425870
AIRLOOP T NW SUPPLY FAN 0.374854
AIRLOOP T SE SUPPLY FAN 0.387991
AIRLOOP T NE SUPPLY FAN 0.280186
AIRLOOP T N1 SUPPLY FAN 0.212298
AIRLOOP T N2 SUPPLY FAN 0.211810
AIRLOOP T S1 SUPPLY FAN 0.318683
AIRLOOP T S2 SUPPLY FAN 0.319814


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.258674 3321.43 0.000073
HEAT PUMP HEATING MODE AIRLOOP G NW 0.232095 2949.73 0.000064
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.348674 4577.95 0.000100
HEAT PUMP HEATING MODE AIRLOOP G NE 0.165424 2081.33 0.000045
HEAT PUMP HEATING MODE AIRLOOP G N1 0.112723 1401.26 0.000031
HEAT PUMP HEATING MODE AIRLOOP G N2 0.111326 1382.83 0.000030
HEAT PUMP HEATING MODE AIRLOOP G S1 0.167600 2254.65 0.000049
HEAT PUMP HEATING MODE AIRLOOP G S2 0.173541 2330.41 0.000051
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.339339 4333.48 0.000095
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.301290 3817.10 0.000083
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.324879 4220.88 0.000092
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.221619 2777.95 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.157670 1970.77 0.000043
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.155935 1948.47 0.000043
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.224061 2964.33 0.000065
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.226397 2994.12 0.000065
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.340604 4338.86 0.000095
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.304082 3842.03 0.000084
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.309621 4016.05 0.000088
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.226111 2824.91 0.000062
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.162262 2023.57 0.000044
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.160543 2001.49 0.000044
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.228268 3011.76 0.000066
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.229475 3027.15 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.341360 4340.46 0.000095
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.305205 3857.98 0.000084
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.309293 4004.06 0.000087
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.227415 2850.73 0.000062
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.163921 2040.22 0.000045
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.162208 2018.24 0.000044
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.229638 3024.55 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.230688 3037.94 0.000066
HEAT PUMP HEATING MODE AIRLOOP M SW 0.344468 4373.53 0.000096
HEAT PUMP HEATING MODE AIRLOOP M NW 0.308709 3896.13 0.000085
HEAT PUMP HEATING MODE AIRLOOP M SE 0.312737 4047.10 0.000088
HEAT PUMP HEATING MODE AIRLOOP M NE 0.230938 2889.37 0.000063
HEAT PUMP HEATING MODE AIRLOOP M N1 0.167574 2083.34 0.000046
HEAT PUMP HEATING MODE AIRLOOP M N2 0.165868 2061.46 0.000045
HEAT PUMP HEATING MODE AIRLOOP M S1 0.233097 3064.80 0.000067
HEAT PUMP HEATING MODE AIRLOOP M S2 0.234123 3077.88 0.000067
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.340388 4315.91 0.000094
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.304773 3840.33 0.000084
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.309168 3996.27 0.000087
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.227191 2836.62 0.000062
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.164107 2035.60 0.000044
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.162415 2013.91 0.000044
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.229375 3014.15 0.000066
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.230399 3027.21 0.000066
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.338962 4292.82 0.000094
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.303558 3819.94 0.000083
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.308187 3979.05 0.000087
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.226079 2817.98 0.000062
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.163177 2020.84 0.000044
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.161496 1999.30 0.000044
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.228221 2996.62 0.000065
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.229245 3009.66 0.000066
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.338959 4288.38 0.000094
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.303762 3818.16 0.000083
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.308491 3978.66 0.000087
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.226268 2816.33 0.000062
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.163648 2024.36 0.000044
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.161979 2002.99 0.000044
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.228388 2996.17 0.000065
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.229414 3009.25 0.000066
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.348830 4410.10 0.000096
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.313294 3935.64 0.000086
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.315327 4061.64 0.000089
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.229080 2848.25 0.000062
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.172070 2130.01 0.000047
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.170381 2108.40 0.000046
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.234017 3065.43 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.235173 3080.16 0.000067
HEAT PUMP HEATING MODE AIRLOOP T SW 0.425870 5444.80 0.000119
HEAT PUMP HEATING MODE AIRLOOP T NW 0.374854 4746.24 0.000104
HEAT PUMP HEATING MODE AIRLOOP T SE 0.387991 4976.68 0.000109
HEAT PUMP HEATING MODE AIRLOOP T NE 0.280186 3521.11 0.000077
HEAT PUMP HEATING MODE AIRLOOP T N1 0.212298 2774.22 0.000061
HEAT PUMP HEATING MODE AIRLOOP T N2 0.211810 2774.49 0.000061
HEAT PUMP HEATING MODE AIRLOOP T S1 0.318683 4141.10 0.000090
HEAT PUMP HEATING MODE AIRLOOP T S2 0.319814 4155.52 0.000091


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 4534.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 4551.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 5645.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 4557.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 3509.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 3509.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 3490.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 3498.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 4373.81
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 4380.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 4403.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 4386.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 3123.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 3124.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 3120.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 3121.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 4357.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 4363.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 4363.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 4367.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 3065.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 3065.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 3060.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 3060.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 4415.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 4420.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 4417.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 4421.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 3086.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 3086.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 3082.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 3082.45
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 4450.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 4451.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 4450.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 4451.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 3090.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 3090.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 3089.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 3089.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 4551.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 4552.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 4550.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 4551.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 3164.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 3164.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 3165.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 3165.06
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 4621.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 4620.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 4619.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 4618.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 3211.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 3211.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 3213.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 3213.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 4699.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 4695.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 4696.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 4692.78
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 3268.80
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 3268.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 3273.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 3273.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 4961.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 4952.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 4957.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 4948.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 3496.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 3496.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 3506.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 3505.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 5962.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 5961.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 5958.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 5957.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 4570.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 4570.58
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 4568.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 4568.76


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.005553 6.25


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.005553


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.005553 2680.67 8.07 7267.99


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.005553 1416.30



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:08

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 -8.8
February 22.02 -2.2
March 22.12 0.30
April 22.51 6.67
May 22.94 10.10
June 24.00 16.46
July 24.28 20.57
August 24.23 19.17
September 23.80 14.69
October 22.90 8.64
November 22.22 2.84
December 21.78 -4.1
     
Annual Sum or Average 22.89 7.07
Minimum of Months 21.78 -8.8
Maximum of Months 24.28 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.06 6.67
May 22.66 10.10
June 23.93 16.46
July 24.26 20.57
August 24.14 19.17
September 23.45 14.69
October 22.17 8.64
November 21.76 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.61 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.26 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -8.8
February 22.09 -2.2
March 22.21 0.30
April 22.61 6.67
May 23.10 10.10
June 24.07 16.46
July 24.32 20.57
August 24.29 19.17
September 23.88 14.69
October 22.92 8.64
November 22.31 2.84
December 21.89 -4.1
     
Annual Sum or Average 22.96 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.71 -2.2
March 21.72 0.30
April 22.01 6.67
May 22.54 10.10
June 23.88 16.46
July 24.25 20.57
August 24.14 19.17
September 23.39 14.69
October 22.05 8.64
November 21.72 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.57 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.25 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.70 -2.2
March 21.71 0.30
April 21.87 6.67
May 22.36 10.10
June 23.79 16.46
July 24.21 20.57
August 24.08 19.17
September 23.35 14.69
October 22.04 8.64
November 21.74 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.52 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.21 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.70 -2.2
March 21.71 0.30
April 21.87 6.67
May 22.36 10.10
June 23.79 16.46
July 24.21 20.57
August 24.08 19.17
September 23.35 14.69
October 22.03 8.64
November 21.73 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.52 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.21 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -8.8
February 22.07 -2.2
March 22.15 0.30
April 22.46 6.67
May 22.79 10.10
June 23.97 16.46
July 24.26 20.57
August 24.24 19.17
September 23.91 14.69
October 23.04 8.64
November 22.34 2.84
December 21.82 -4.1
     
Annual Sum or Average 22.91 7.07
Minimum of Months 21.81 -8.8
Maximum of Months 24.26 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -8.8
February 22.08 -2.2
March 22.17 0.30
April 22.49 6.67
May 22.83 10.10
June 23.99 16.46
July 24.27 20.57
August 24.25 19.17
September 23.93 14.69
October 23.07 8.64
November 22.37 2.84
December 21.84 -4.1
     
Annual Sum or Average 22.93 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 24.27 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.16 -8.8
February 16.90 -2.2
March 17.74 0.30
April 19.54 6.67
May 20.73 10.10
June 23.69 16.46
July 25.07 20.57
August 24.57 19.17
September 23.03 14.69
October 20.28 8.64
November 18.26 2.84
December 16.27 -4.1
     
Annual Sum or Average 20.12 7.07
Minimum of Months 15.16 -8.8
Maximum of Months 25.07 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.22 -2.2
March 22.45 0.30
April 23.09 6.67
May 23.54 10.10
June 24.26 16.46
July 24.36 20.57
August 24.33 19.17
September 23.99 14.69
October 23.54 8.64
November 22.63 2.84
December 21.84 -4.1
     
Annual Sum or Average 23.18 7.07
Minimum of Months 21.84 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.76 -2.2
March 21.83 0.30
April 22.48 6.67
May 23.23 10.10
June 24.20 16.46
July 24.35 20.57
August 24.27 19.17
September 23.59 14.69
October 22.58 8.64
November 21.84 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.80 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.24 -2.2
March 22.52 0.30
April 23.15 6.67
May 23.59 10.10
June 24.29 16.46
July 24.37 20.57
August 24.36 19.17
September 24.04 14.69
October 23.59 8.64
November 22.67 2.84
December 21.86 -4.1
     
Annual Sum or Average 23.22 7.07
Minimum of Months 21.86 -8.8
Maximum of Months 24.37 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.78 0.30
April 22.41 6.67
May 23.12 10.10
June 24.17 16.46
July 24.35 20.57
August 24.29 19.17
September 23.52 14.69
October 22.38 8.64
November 21.77 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.75 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.25 6.67
May 22.99 10.10
June 24.14 16.46
July 24.32 20.57
August 24.25 19.17
September 23.52 14.69
October 22.48 8.64
November 21.84 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.73 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.25 6.67
May 22.98 10.10
June 24.13 16.46
July 24.32 20.57
August 24.25 19.17
September 23.52 14.69
October 22.47 8.64
November 21.84 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.73 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 -8.8
February 22.37 -2.2
March 22.65 0.30
April 23.18 6.67
May 23.50 10.10
June 24.24 16.46
July 24.34 20.57
August 24.34 19.17
September 24.11 14.69
October 23.78 8.64
November 22.92 2.84
December 21.99 -4.1
     
Annual Sum or Average 23.29 7.07
Minimum of Months 21.98 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 -8.8
February 22.38 -2.2
March 22.66 0.30
April 23.20 6.67
May 23.50 10.10
June 24.25 16.46
July 24.35 20.57
August 24.35 19.17
September 24.12 14.69
October 23.79 8.64
November 22.93 2.84
December 22.00 -4.1
     
Annual Sum or Average 23.30 7.07
Minimum of Months 21.98 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 -8.8
February 21.90 -2.2
March 22.47 0.30
April 23.50 6.67
May 24.26 10.10
June 25.92 16.46
July 26.43 20.57
August 26.22 19.17
September 25.27 14.69
October 23.92 8.64
November 22.54 2.84
December 21.43 -4.1
     
Annual Sum or Average 23.76 7.07
Minimum of Months 21.08 -8.8
Maximum of Months 26.43 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 -8.8
February 22.23 -2.2
March 22.51 0.30
April 23.19 6.67
May 23.61 10.10
June 24.27 16.46
July 24.36 20.57
August 24.33 19.17
September 23.98 14.69
October 23.64 8.64
November 22.69 2.84
December 21.84 -4.1
     
Annual Sum or Average 23.21 7.07
Minimum of Months 21.84 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.77 -2.2
March 21.83 0.30
April 22.58 6.67
May 23.32 10.10
June 24.22 16.46
July 24.35 20.57
August 24.27 19.17
September 23.55 14.69
October 22.67 8.64
November 21.86 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.82 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.22 -2.2
March 22.53 0.30
April 23.19 6.67
May 23.60 10.10
June 24.27 16.46
July 24.37 20.57
August 24.35 19.17
September 23.99 14.69
October 23.62 8.64
November 22.67 2.84
December 21.82 -4.1
     
Annual Sum or Average 23.21 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 24.37 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.51 6.67
May 23.22 10.10
June 24.19 16.46
July 24.35 20.57
August 24.29 19.17
September 23.49 14.69
October 22.47 8.64
November 21.79 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.77 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.41 6.67
May 23.14 10.10
June 24.17 16.46
July 24.33 20.57
August 24.26 19.17
September 23.52 14.69
October 22.65 8.64
November 21.88 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.78 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.40 6.67
May 23.13 10.10
June 24.17 16.46
July 24.33 20.57
August 24.26 19.17
September 23.51 14.69
October 22.63 8.64
November 21.88 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.78 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 -8.8
February 22.42 -2.2
March 22.78 0.30
April 23.36 6.67
May 23.62 10.10
June 24.26 16.46
July 24.34 20.57
August 24.35 19.17
September 24.12 14.69
October 23.93 8.64
November 23.05 2.84
December 22.03 -4.1
     
Annual Sum or Average 23.36 7.07
Minimum of Months 22.03 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 -8.8
February 22.43 -2.2
March 22.78 0.30
April 23.37 6.67
May 23.62 10.10
June 24.27 16.46
July 24.34 20.57
August 24.35 19.17
September 24.12 14.69
October 23.93 8.64
November 23.06 2.84
December 22.03 -4.1
     
Annual Sum or Average 23.36 7.07
Minimum of Months 22.03 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.60 -8.8
February 22.36 -2.2
March 22.94 0.30
April 23.99 6.67
May 24.73 10.10
June 26.17 16.46
July 26.58 20.57
August 26.39 19.17
September 25.44 14.69
October 24.36 8.64
November 22.97 2.84
December 21.87 -4.1
     
Annual Sum or Average 24.12 7.07
Minimum of Months 21.60 -8.8
Maximum of Months 26.58 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.20 -2.2
March 22.49 0.30
April 23.18 6.67
May 23.61 10.10
June 24.26 16.46
July 24.36 20.57
August 24.33 19.17
September 23.94 14.69
October 23.63 8.64
November 22.67 2.84
December 21.82 -4.1
     
Annual Sum or Average 23.20 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.76 -2.2
March 21.83 0.30
April 22.58 6.67
May 23.32 10.10
June 24.21 16.46
July 24.34 20.57
August 24.27 19.17
September 23.52 14.69
October 22.68 8.64
November 21.86 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.82 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 -8.8
February 22.20 -2.2
March 22.50 0.30
April 23.17 6.67
May 23.59 10.10
June 24.26 16.46
July 24.36 20.57
August 24.35 19.17
September 23.95 14.69
October 23.61 8.64
November 22.64 2.84
December 21.81 -4.1
     
Annual Sum or Average 23.19 7.07
Minimum of Months 21.81 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.51 6.67
May 23.23 10.10
June 24.18 16.46
July 24.35 20.57
August 24.28 19.17
September 23.46 14.69
October 22.48 8.64
November 21.78 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.77 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.45 6.67
May 23.18 10.10
June 24.18 16.46
July 24.33 20.57
August 24.26 19.17
September 23.50 14.69
October 22.71 8.64
November 21.89 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.79 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.44 6.67
May 23.17 10.10
June 24.18 16.46
July 24.33 20.57
August 24.26 19.17
September 23.49 14.69
October 22.68 8.64
November 21.89 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.79 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 -8.8
February 22.41 -2.2
March 22.78 0.30
April 23.39 6.67
May 23.63 10.10
June 24.26 16.46
July 24.34 20.57
August 24.35 19.17
September 24.11 14.69
October 23.95 8.64
November 23.07 2.84
December 22.02 -4.1
     
Annual Sum or Average 23.37 7.07
Minimum of Months 22.02 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 -8.8
February 22.41 -2.2
March 22.79 0.30
April 23.39 6.67
May 23.63 10.10
June 24.26 16.46
July 24.34 20.57
August 24.35 19.17
September 24.11 14.69
October 23.95 8.64
November 23.06 2.84
December 22.02 -4.1
     
Annual Sum or Average 23.37 7.07
Minimum of Months 22.02 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -8.8
February 22.49 -2.2
March 23.09 0.30
April 24.15 6.67
May 24.89 10.10
June 26.27 16.46
July 26.67 20.57
August 26.48 19.17
September 25.52 14.69
October 24.51 8.64
November 23.11 2.84
December 22.00 -4.1
     
Annual Sum or Average 24.25 7.07
Minimum of Months 21.74 -8.8
Maximum of Months 26.67 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 -8.8
February 22.19 -2.2
March 22.47 0.30
April 23.16 6.67
May 23.59 10.10
June 24.25 16.46
July 24.36 20.57
August 24.32 19.17
September 23.92 14.69
October 23.61 8.64
November 22.65 2.84
December 21.82 -4.1
     
Annual Sum or Average 23.19 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.76 -2.2
March 21.82 0.30
April 22.57 6.67
May 23.32 10.10
June 24.20 16.46
July 24.34 20.57
August 24.26 19.17
September 23.50 14.69
October 22.67 8.64
November 21.86 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.81 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 -8.8
February 22.18 -2.2
March 22.48 0.30
April 23.15 6.67
May 23.57 10.10
June 24.25 16.46
July 24.36 20.57
August 24.34 19.17
September 23.93 14.69
October 23.59 8.64
November 22.62 2.84
December 21.80 -4.1
     
Annual Sum or Average 23.18 7.07
Minimum of Months 21.80 -8.8
Maximum of Months 24.36 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.50 6.67
May 23.22 10.10
June 24.17 16.46
July 24.35 20.57
August 24.28 19.17
September 23.44 14.69
October 22.48 8.64
November 21.79 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.77 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.75 -2.2
March 21.79 0.30
April 22.46 6.67
May 23.19 10.10
June 24.18 16.46
July 24.33 20.57
August 24.25 19.17
September 23.49 14.69
October 22.73 8.64
November 21.90 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.80 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.75 -2.2
March 21.79 0.30
April 22.46 6.67
May 23.18 10.10
June 24.18 16.46
July 24.33 20.57
August 24.26 19.17
September 23.48 14.69
October 22.70 8.64
November 21.89 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.79 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 -8.8
February 22.40 -2.2
March 22.78 0.30
April 23.39 6.67
May 23.63 10.10
June 24.26 16.46
July 24.34 20.57
August 24.34 19.17
September 24.09 14.69
October 23.95 8.64
November 23.06 2.84
December 22.01 -4.1
     
Annual Sum or Average 23.36 7.07
Minimum of Months 22.01 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 -8.8
February 22.40 -2.2
March 22.79 0.30
April 23.40 6.67
May 23.63 10.10
June 24.26 16.46
July 24.34 20.57
August 24.34 19.17
September 24.09 14.69
October 23.95 8.64
November 23.06 2.84
December 22.01 -4.1
     
Annual Sum or Average 23.36 7.07
Minimum of Months 22.01 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 -8.8
February 23.13 -2.2
March 23.71 0.30
April 24.78 6.67
May 25.50 10.10
June 26.87 16.46
July 27.27 20.57
August 27.08 19.17
September 26.11 14.69
October 25.13 8.64
November 23.74 2.84
December 22.66 -4.1
     
Annual Sum or Average 24.87 7.07
Minimum of Months 22.39 -8.8
Maximum of Months 27.27 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.83 -8.8
February 22.15 -2.2
March 22.39 0.30
April 23.08 6.67
May 23.52 10.10
June 24.21 16.46
July 24.34 20.57
August 24.31 19.17
September 23.86 14.69
October 23.52 8.64
November 22.57 2.84
December 21.79 -4.1
     
Annual Sum or Average 23.14 7.07
Minimum of Months 21.79 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.75 -2.2
March 21.80 0.30
April 22.48 6.67
May 23.24 10.10
June 24.16 16.46
July 24.33 20.57
August 24.23 19.17
September 23.42 14.69
October 22.55 8.64
November 21.82 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.77 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -8.8
February 22.14 -2.2
March 22.40 0.30
April 23.07 6.67
May 23.50 10.10
June 24.22 16.46
July 24.35 20.57
August 24.33 19.17
September 23.86 14.69
October 23.49 8.64
November 22.53 2.84
December 21.78 -4.1
     
Annual Sum or Average 23.13 7.07
Minimum of Months 21.78 -8.8
Maximum of Months 24.35 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.41 6.67
May 23.14 10.10
June 24.13 16.46
July 24.33 20.57
August 24.25 19.17
September 23.36 14.69
October 22.36 8.64
November 21.76 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.73 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.77 0.30
April 22.36 6.67
May 23.11 10.10
June 24.13 16.46
July 24.31 20.57
August 24.22 19.17
September 23.40 14.69
October 22.60 8.64
November 21.86 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.75 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.77 0.30
April 22.35 6.67
May 23.10 10.10
June 24.13 16.46
July 24.31 20.57
August 24.22 19.17
September 23.39 14.69
October 22.58 8.64
November 21.85 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.74 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 -8.8
February 22.35 -2.2
March 22.70 0.30
April 23.30 6.67
May 23.55 10.10
June 24.22 16.46
July 24.33 20.57
August 24.33 19.17
September 24.03 14.69
October 23.87 8.64
November 22.97 2.84
December 21.96 -4.1
     
Annual Sum or Average 23.30 7.07
Minimum of Months 21.96 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 -8.8
February 22.35 -2.2
March 22.70 0.30
April 23.30 6.67
May 23.55 10.10
June 24.23 16.46
July 24.33 20.57
August 24.33 19.17
September 24.03 14.69
October 23.87 8.64
November 22.97 2.84
December 21.96 -4.1
     
Annual Sum or Average 23.30 7.07
Minimum of Months 21.96 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -8.8
February 22.42 -2.2
March 23.00 0.30
April 24.06 6.67
May 24.80 10.10
June 26.21 16.46
July 26.65 20.57
August 26.44 19.17
September 25.42 14.69
October 24.40 8.64
November 23.03 2.84
December 21.94 -4.1
     
Annual Sum or Average 24.18 7.07
Minimum of Months 21.68 -8.8
Maximum of Months 26.65 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -8.8
February 22.12 -2.2
March 22.33 0.30
April 23.01 6.67
May 23.47 10.10
June 24.19 16.46
July 24.34 20.57
August 24.29 19.17
September 23.81 14.69
October 23.44 8.64
November 22.50 2.84
December 21.78 -4.1
     
Annual Sum or Average 23.10 7.07
Minimum of Months 21.78 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.79 0.30
April 22.41 6.67
May 23.18 10.10
June 24.12 16.46
July 24.32 20.57
August 24.21 19.17
September 23.37 14.69
October 22.46 8.64
November 21.80 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.74 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -8.8
February 22.12 -2.2
March 22.35 0.30
April 23.01 6.67
May 23.45 10.10
June 24.19 16.46
July 24.34 20.57
August 24.31 19.17
September 23.82 14.69
October 23.42 8.64
November 22.47 2.84
December 21.76 -4.1
     
Annual Sum or Average 23.09 7.07
Minimum of Months 21.76 -8.8
Maximum of Months 24.34 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.75 0.30
April 22.35 6.67
May 23.09 10.10
June 24.09 16.46
July 24.32 20.57
August 24.22 19.17
September 23.31 14.69
October 22.29 8.64
November 21.75 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.70 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.28 6.67
May 23.05 10.10
June 24.10 16.46
July 24.30 20.57
August 24.20 19.17
September 23.34 14.69
October 22.50 8.64
November 21.83 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.71 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.76 0.30
April 22.28 6.67
May 23.05 10.10
June 24.10 16.46
July 24.30 20.57
August 24.20 19.17
September 23.34 14.69
October 22.48 8.64
November 21.83 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.71 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.96 -8.8
February 22.31 -2.2
March 22.63 0.30
April 23.22 6.67
May 23.50 10.10
June 24.20 16.46
July 24.32 20.57
August 24.32 19.17
September 23.97 14.69
October 23.80 8.64
November 22.90 2.84
December 21.92 -4.1
     
Annual Sum or Average 23.26 7.07
Minimum of Months 21.92 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.96 -8.8
February 22.31 -2.2
March 22.63 0.30
April 23.23 6.67
May 23.50 10.10
June 24.20 16.46
July 24.32 20.57
August 24.32 19.17
September 23.97 14.69
October 23.80 8.64
November 22.90 2.84
December 21.92 -4.1
     
Annual Sum or Average 23.26 7.07
Minimum of Months 21.92 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.52 -8.8
February 22.25 -2.2
March 22.83 0.30
April 23.87 6.67
May 24.64 10.10
June 26.08 16.46
July 26.55 20.57
August 26.34 19.17
September 25.27 14.69
October 24.21 8.64
November 22.85 2.84
December 21.79 -4.1
     
Annual Sum or Average 24.03 7.07
Minimum of Months 21.52 -8.8
Maximum of Months 26.55 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -8.8
February 22.10 -2.2
March 22.28 0.30
April 22.95 6.67
May 23.43 10.10
June 24.16 16.46
July 24.33 20.57
August 24.28 19.17
September 23.76 14.69
October 23.36 8.64
November 22.45 2.84
December 21.76 -4.1
     
Annual Sum or Average 23.06 7.07
Minimum of Months 21.76 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.74 -2.2
March 21.78 0.30
April 22.36 6.67
May 23.14 10.10
June 24.09 16.46
July 24.31 20.57
August 24.19 19.17
September 23.33 14.69
October 22.39 8.64
November 21.79 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.72 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -8.8
February 22.09 -2.2
March 22.30 0.30
April 22.96 6.67
May 23.41 10.10
June 24.17 16.46
July 24.33 20.57
August 24.30 19.17
September 23.77 14.69
October 23.34 8.64
November 22.41 2.84
December 21.75 -4.1
     
Annual Sum or Average 23.06 7.07
Minimum of Months 21.75 -8.8
Maximum of Months 24.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.74 0.30
April 22.30 6.67
May 23.04 10.10
June 24.06 16.46
July 24.32 20.57
August 24.20 19.17
September 23.27 14.69
October 22.23 8.64
November 21.74 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.67 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.75 0.30
April 22.23 6.67
May 23.01 10.10
June 24.06 16.46
July 24.29 20.57
August 24.18 19.17
September 23.29 14.69
October 22.42 8.64
November 21.81 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.69 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.29 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.75 0.30
April 22.23 6.67
May 23.00 10.10
June 24.06 16.46
July 24.29 20.57
August 24.18 19.17
September 23.29 14.69
October 22.40 8.64
November 21.81 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.68 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.29 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 -8.8
February 22.27 -2.2
March 22.57 0.30
April 23.15 6.67
May 23.45 10.10
June 24.17 16.46
July 24.31 20.57
August 24.30 19.17
September 23.92 14.69
October 23.72 8.64
November 22.83 2.84
December 21.89 -4.1
     
Annual Sum or Average 23.21 7.07
Minimum of Months 21.89 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 -8.8
February 22.27 -2.2
March 22.57 0.30
April 23.16 6.67
May 23.45 10.10
June 24.18 16.46
July 24.31 20.57
August 24.30 19.17
September 23.92 14.69
October 23.72 8.64
November 22.83 2.84
December 21.89 -4.1
     
Annual Sum or Average 23.22 7.07
Minimum of Months 21.89 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.42 -8.8
February 22.16 -2.2
March 22.73 0.30
April 23.76 6.67
May 24.56 10.10
June 26.03 16.46
July 26.53 20.57
August 26.30 19.17
September 25.19 14.69
October 24.08 8.64
November 22.74 2.84
December 21.70 -4.1
     
Annual Sum or Average 23.94 7.07
Minimum of Months 21.42 -8.8
Maximum of Months 26.53 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 -8.8
February 22.06 -2.2
March 22.22 0.30
April 22.87 6.67
May 23.38 10.10
June 24.12 16.46
July 24.32 20.57
August 24.26 19.17
September 23.70 14.69
October 23.24 8.64
November 22.36 2.84
December 21.75 -4.1
     
Annual Sum or Average 23.01 7.07
Minimum of Months 21.75 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.77 0.30
April 22.32 6.67
May 23.10 10.10
June 24.04 16.46
July 24.30 20.57
August 24.17 19.17
September 23.29 14.69
October 22.32 8.64
November 21.77 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.69 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -8.8
February 22.06 -2.2
March 22.24 0.30
April 22.89 6.67
May 23.37 10.10
June 24.13 16.46
July 24.32 20.57
August 24.28 19.17
September 23.71 14.69
October 23.22 8.64
November 22.33 2.84
December 21.74 -4.1
     
Annual Sum or Average 23.01 7.07
Minimum of Months 21.74 -8.8
Maximum of Months 24.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.71 -2.2
March 21.73 0.30
April 22.26 6.67
May 23.01 10.10
June 24.01 16.46
July 24.31 20.57
August 24.18 19.17
September 23.22 14.69
October 22.16 8.64
November 21.73 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.65 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.31 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.74 0.30
April 22.19 6.67
May 22.98 10.10
June 24.01 16.46
July 24.28 20.57
August 24.15 19.17
September 23.25 14.69
October 22.32 8.64
November 21.79 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.66 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.28 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.74 0.30
April 22.19 6.67
May 22.97 10.10
June 24.01 16.46
July 24.28 20.57
August 24.15 19.17
September 23.24 14.69
October 22.31 8.64
November 21.78 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.66 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.28 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 -8.8
February 22.22 -2.2
March 22.47 0.30
April 23.04 6.67
May 23.41 10.10
June 24.14 16.46
July 24.30 20.57
August 24.28 19.17
September 23.83 14.69
October 23.56 8.64
November 22.70 2.84
December 21.85 -4.1
     
Annual Sum or Average 23.15 7.07
Minimum of Months 21.85 -8.8
Maximum of Months 24.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 -8.8
February 22.22 -2.2
March 22.47 0.30
April 23.05 6.67
May 23.41 10.10
June 24.14 16.46
July 24.30 20.57
August 24.28 19.17
September 23.84 14.69
October 23.57 8.64
November 22.70 2.84
December 21.85 -4.1
     
Annual Sum or Average 23.15 7.07
Minimum of Months 21.85 -8.8
Maximum of Months 24.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.19 -8.8
February 21.97 -2.2
March 22.53 0.30
April 23.62 6.67
May 24.48 10.10
June 26.00 16.46
July 26.57 20.57
August 26.30 19.17
September 25.10 14.69
October 23.88 8.64
November 22.53 2.84
December 21.49 -4.1
     
Annual Sum or Average 23.81 7.07
Minimum of Months 21.19 -8.8
Maximum of Months 26.57 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -8.8
February 22.04 -2.2
March 22.19 0.30
April 22.68 6.67
May 23.23 10.10
June 23.90 16.46
July 24.23 20.57
August 24.14 19.17
September 23.50 14.69
October 22.90 8.64
November 22.27 2.84
December 21.78 -4.1
     
Annual Sum or Average 22.89 7.07
Minimum of Months 21.78 -8.8
Maximum of Months 24.23 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.76 -2.2
March 21.84 0.30
April 22.33 6.67
May 23.02 10.10
June 23.83 16.46
July 24.20 20.57
August 24.03 19.17
September 23.18 14.69
October 22.29 8.64
November 21.79 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.65 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.20 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 -8.8
February 22.05 -2.2
March 22.20 0.30
April 22.71 6.67
May 23.23 10.10
June 23.93 16.46
July 24.24 20.57
August 24.16 19.17
September 23.51 14.69
October 22.89 8.64
November 22.23 2.84
December 21.77 -4.1
     
Annual Sum or Average 22.90 7.07
Minimum of Months 21.77 -8.8
Maximum of Months 24.24 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.72 -2.2
March 21.78 0.30
April 22.29 6.67
May 22.96 10.10
June 23.80 16.46
July 24.20 20.57
August 24.02 19.17
September 23.11 14.69
October 22.15 8.64
November 21.73 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.60 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.20 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.78 0.30
April 22.23 6.67
May 22.93 10.10
June 23.79 16.46
July 24.19 20.57
August 24.00 19.17
September 23.12 14.69
October 22.21 8.64
November 21.78 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.60 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.19 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -8.8
February 21.73 -2.2
March 21.78 0.30
April 22.23 6.67
May 22.93 10.10
June 23.79 16.46
July 24.18 20.57
August 24.01 19.17
September 23.12 14.69
October 22.21 8.64
November 21.78 2.84
December 21.70 -4.1
     
Annual Sum or Average 22.60 7.07
Minimum of Months 21.70 -8.8
Maximum of Months 24.18 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.15 -2.2
March 22.31 0.30
April 22.79 6.67
May 23.28 10.10
June 23.95 16.46
July 24.24 20.57
August 24.18 19.17
September 23.61 14.69
October 23.14 8.64
November 22.48 2.84
December 21.87 -4.1
     
Annual Sum or Average 22.99 7.07
Minimum of Months 21.86 -8.8
Maximum of Months 24.24 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -8.8
February 22.15 -2.2
March 22.31 0.30
April 22.80 6.67
May 23.29 10.10
June 23.95 16.46
July 24.24 20.57
August 24.19 19.17
September 23.61 14.69
October 23.14 8.64
November 22.48 2.84
December 21.87 -4.1
     
Annual Sum or Average 22.99 7.07
Minimum of Months 21.86 -8.8
Maximum of Months 24.24 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:08

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.69 -8.8
February 21.75 -2.2
March 22.38 0.30
April 23.71 6.67
May 24.80 10.10
June 26.49 16.46
July 27.24 20.57
August 26.84 19.17
September 25.39 14.69
October 23.86 8.64
November 22.35 2.84
December 21.13 -4.1
     
Annual Sum or Average 23.90 7.07
Minimum of Months 20.69 -8.8
Maximum of Months 27.24 20.57



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:08

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.297319E+12 185892.936 05-JAN-19:00 25049.151 51564.864 22275.346 73815.635 0.000 10720.100 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.237230E+12 157694.425 04-FEB-18:00 22204.399 56867.515 22275.346 43027.950 0.000 10720.100 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.243131E+12 145101.685 03-MAR-20:00 25049.151 49704.829 22275.346 34953.461 0.000 10720.100 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.216544E+12 131932.657 01-APR-17:15 22204.399 56867.515 22275.346 27986.535 0.000 0.000 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.228744E+12 166964.555 19-MAY-17:15 22204.399 56867.515 22275.346 0.000 61086.701 0.000 1453.226 1931.732 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.245642E+12 167508.421 24-JUN-17:45 22204.399 56867.515 22275.346 0.000 61758.985 0.000 1453.226 1803.062 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.284402E+12 170401.690 17-JUL-17:15 22204.399 56867.515 22275.346 0.000 64339.206 0.000 1453.226 2116.362 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.272220E+12 170815.141 06-AUG-17:15 22204.399 56867.515 22275.346 0.000 64827.690 0.000 1453.226 2041.329 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.238775E+12 170215.841 02-SEP-17:15 22204.399 56867.515 22275.346 0.000 64191.456 0.000 1453.226 2078.263 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.226771E+12 141234.864 18-OCT-16:15 18221.747 56933.809 22275.346 0.000 39847.865 0.000 1453.226 1354.568 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.237659E+12 149334.110 26-NOV-18:00 22204.399 56867.515 22275.346 34667.635 0.000 10720.100 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.273470E+12 160958.956 31-DEC-07:00 14239.096 40592.208 22275.346 71066.841 0.000 10720.100 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.300191E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.216544E+12 131932.657   14239.096 40592.208 22275.346 0.000 0.000 0.000 1453.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.297319E+12 185892.936   25049.151 56933.809 22275.346 73815.635 64827.690 10720.100 1453.226 2116.362 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:08

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.408550E+12 318617.549 06-JAN-06:45 0.000 0.000 0.000 318617.549 87362.788 87362.788 231254.761
February 0.262293E+12 278020.181 04-FEB-08:15 0.000 0.000 0.000 278020.181 91397.847 91397.847 186622.335
March 0.218772E+12 259220.214 06-MAR-06:45 0.000 0.000 0.000 259220.214 88368.614 88368.614 170851.599
April 0.136762E+12 168219.111 29-APR-06:15 0.000 0.000 0.000 168219.111 87871.947 87871.947 80347.164
May 0.129397E+12 173997.258 08-MAY-05:45 0.000 0.000 0.000 173997.258 85202.416 85202.416 88794.842
June 0.996738E+11 86490.137 01-JUN-06:00 0.000 0.000 0.000 86490.137 86490.137 86490.137 0.000
July 0.978559E+11 84376.229 01-JUL-06:00 0.000 0.000 0.000 84376.229 84376.229 84376.229 0.000
August 0.956117E+11 83040.009 01-AUG-06:45 0.000 0.000 0.000 83040.009 83040.009 83040.009 0.000
September 0.967012E+11 108819.257 20-SEP-06:15 0.000 0.000 0.000 108819.257 82345.281 82345.281 26473.976
October 0.114173E+12 162309.508 10-OCT-06:15 0.000 0.000 0.000 162309.508 83372.659 83372.659 78936.849
November 0.195771E+12 242569.667 27-NOV-07:15 0.000 0.000 0.000 242569.667 86794.104 86794.104 155775.563
December 0.325518E+12 316076.380 31-DEC-08:15 0.000 0.000 0.000 316076.380 89879.636 89879.636 226196.744
                     
Annual Sum or Average 0.218108E+13     0.000 0.000 0.000        
Minimum of Months 0.956117E+11 83040.009   0.000 0.000 0.000 83040.009 82345.281 82345.281 0.000
Maximum of Months 0.408550E+12 318617.549   0.000 0.000 0.000 318617.549 91397.847 91397.847 231254.761