Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2018-10-19 09:40:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4407.35 562.42 624.28
Net Site Energy 4407.35 562.42 624.28
Total Source Energy 12079.41 1541.43 1710.99
Net Source Energy 12079.41 1541.43 1710.99


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 4.73 2.88 0.00 0.00 0.00 0.00
Cooling 908.06 0.00 0.00 0.00 0.00 0.00
Interior Lighting 416.41 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 168.51 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 770.14 0.00 0.00 0.00 0.00 0.00
Pumps 52.12 0.00 0.00 0.00 0.00 0.00
Heat Rejection 33.55 0.00 0.00 0.00 0.00 3290.19
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 899.03 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3505.44 901.91 0.00 0.00 0.00 8068.70
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 2.88 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 4.73 0.00 0.00 0.00 0.00 0.00
Cooling General 908.06 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 348.50 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 67.92 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 168.51 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1131.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 770.14 0.00 0.00 0.00 0.00 0.00
Pumps General 52.12 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 33.55 0.00 0.00 0.00 0.00 3290.19
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 899.03 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 82.85 0.00 0.00 0.00 0.00 0.00
HVAC 250.51 127.75 0.00 0.00 0.00 1.14
Other 160.21 0.00 0.00 0.00 0.00 0.00
Total 496.53 127.75 0.00 0.00 0.00 1.14


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 74.64 0.00 0.00 0.00 0.00 0.00
HVAC 225.69 115.09 0.00 0.00 0.00 1.03
Other 144.34 0.00 0.00 0.00 0.00 0.00
Total 447.32 115.09 0.00 0.00 0.00 1.03


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3505.44 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3505.44 100.00
     
Total On-Site and Utility Electric Sources 3505.44 100.00
Total Electricity End Uses 3505.44 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8068.70 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8068.70 100.00
Total Water End Uses 8068.70 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 10.75
Time Setpoint Not Met During Occupied Cooling 640.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 627.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
RunPeriod Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 23.8959 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 8.5250   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 17.0500   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 14.4236 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 14.4236 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 14.4236 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 8.5250   263.6661
Total 7836.48     23884.04   3855.02 1150.39 14.0302 39.48 8.6219
Conditioned Total 7059.89     21517.16   3752.84 1125.85 14.5420 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 9.3775   26.3666
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-JUN-19:30 17-DEC-07:30 - - - 28-JUN-17:30
Heating 0.00 27346.18 0.00 0.00 0.00 0.00
Cooling 71861.98 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25049.15 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24420.97 0.00 0.00 0.00 0.00 0.00
Pumps 1697.55 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2260.76 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 78424.24 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 186660.91 105770.42 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 27346.18 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 71861.98 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 20603.34 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 4445.81 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10720.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49704.83 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 24420.97 0.00 0.00 0.00 0.00 0.00
Pumps General 1697.55 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 2260.76 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 78424.24 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 14.98 3.12 0.00 0.00 0.00
Cooling 2875.83 0.00 0.00 0.00 0.00
Interior Lighting 1318.78 0.00 0.00 0.00 0.00
Exterior Lighting 533.68 0.00 0.00 0.00 0.00
Interior Equipment 3582.17 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2439.03 0.00 0.00 0.00 0.00
Pumps 165.06 0.00 0.00 0.00 0.00
Heat Rejection 106.25 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 974.55 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 11101.74 977.67 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.12 0.44 0.00 0.00 0.00
Cooling 407.35 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.59 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 345.48 0.00 0.00 0.00 0.00
Pumps 23.38 0.00 0.00 0.00 0.00
Heat Rejection 15.05 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 138.04 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1572.51 138.48 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.12 0.44 0.00 0.00 0.00
Cooling 407.35 0.00 0.00 0.00 0.00
Interior Lighting 186.80 0.00 0.00 0.00 0.00
Exterior Lighting 75.59 0.00 0.00 0.00 0.00
Interior Equipment 507.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 345.48 0.00 0.00 0.00 0.00
Pumps 23.38 0.00 0.00 0.00 0.00
Heat Rejection 15.05 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 138.04 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1572.51 138.48 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.55 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.55 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.72_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 4.600 0.293 0.130     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.72_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 4.600 0.293 0.130     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.72_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 4.600 0.293 0.130     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 4.600 0.293 0.130              
North Total or Average           423.59 4.600 0.293 0.130              
Non-North Total or Average           726.80 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
OFFICE_LIGHTS_HARDWIRED OFFICE 11.9479 88.25 1054.39 GeneralLights LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 11.5174 88.25 1016.39 GeneralLights LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 1.93
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 8.5250 77.66 662.04 GeneralLights LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
OFFICE_LIGHTS_PLUGIN OFFICE 11.9479 88.25 1054.39 GeneralLights-plugin LTG_OFF_SCH 56.26 168.00 55.46 0.0000 Y 10.98
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 8.5250 77.66 662.04 GeneralLights-plugin LTG_COR_SCH 149.10 168.00 149.10 0.0000 N 18.53
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 2.9063 88.25 256.47 GeneralLights-plugin LTG_APT_SCH 10.10 168.00 10.10 0.0000 Y 0.49
Interior Lighting Total   7.3426 14974.03 109947.72               416.41


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10720.10 AstronomicalClock -   83.74 83.74 168.51
Exterior Lighting Total 10720.10           168.51



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 299343.48 0.80    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 239474.78      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4243.04 2984.76 1258.28 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4183.96 2946.65 1237.31 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   5085.53 3591.12 1494.41 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3334.17 2363.95 970.22 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2349.11 1643.81 705.30 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2334.02 1633.15 700.87 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2535.29 1753.96 781.33 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2601.05 1800.76 800.29 0.69 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4853.94 3430.15 1423.79 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4784.33 3382.77 1401.56 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4373.99 3101.35 1272.64 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3891.60 2766.56 1125.04 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2730.89 1921.22 809.66 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2719.23 1912.97 806.26 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2956.60 2060.46 896.14 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2979.47 2076.71 902.77 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4837.17 3425.54 1411.64 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4769.50 3379.55 1389.95 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4163.72 2959.75 1203.97 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3903.00 2781.77 1121.23 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2748.34 1937.76 810.57 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2736.99 1929.73 807.26 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2979.61 2080.95 898.66 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2989.72 2088.13 901.59 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4842.12 3434.47 1407.65 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4774.99 3389.91 1385.08 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4152.90 2957.48 1195.43 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3912.13 2793.59 1118.54 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2768.72 1955.34 813.38 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2757.58 1947.45 810.13 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2999.64 2098.30 901.35 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3007.87 2104.14 903.73 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4881.49 3466.77 1414.73 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4814.58 3422.38 1392.20 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4203.87 2995.16 1208.71 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3955.20 2828.47 1126.72 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2819.79 1994.05 825.74 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2808.82 1986.28 822.54 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3049.35 2136.18 913.17 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3057.28 2141.81 915.47 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4839.40 3439.66 1399.74 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4764.82 3391.00 1373.82 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4161.69 2969.01 1192.68 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3909.83 2800.05 1109.77 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2782.20 1969.65 812.55 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2771.44 1962.02 809.42 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3012.82 2112.38 900.44 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3020.68 2117.96 902.72 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4824.90 3432.74 1392.16 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4749.51 3383.53 1365.98 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4151.50 2965.08 1186.43 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3897.85 2794.84 1103.01 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2776.35 1967.44 808.91 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2765.74 1959.91 805.83 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3006.73 2109.96 896.77 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3014.55 2115.52 899.04 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4831.34 3440.30 1391.04 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4755.22 3390.58 1364.64 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4161.15 2974.86 1186.29 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3905.68 2803.33 1102.35 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2790.32 1979.06 811.25 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2779.86 1971.65 808.21 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3019.82 2120.99 898.83 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3027.62 2126.53 901.09 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4952.70 3530.07 1422.63 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4882.70 3483.55 1399.14 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4240.41 3033.76 1206.64 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3975.99 2855.89 1120.10 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2913.73 2068.07 845.66 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2903.36 2060.72 842.64 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3118.74 2191.44 927.30 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3126.40 2196.88 929.52 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5820.94 4144.76 1676.19 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5708.25 4067.27 1640.98 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5093.90 3621.54 1472.35 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4642.57 3323.94 1318.63 0.72 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3515.81 2493.40 1022.41 0.71 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3565.58 2512.02 1053.56 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3988.37 2810.42 1177.95 0.70 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3995.68 2815.59 1180.09 0.70 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4243.04 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   4183.96 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   5085.53 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   3334.17 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2349.11 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2334.02 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2535.29 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2601.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4853.94 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4784.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4373.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3891.60 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2730.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2719.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2956.60 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2979.47 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4837.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4769.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4163.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3903.00 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2748.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2736.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2979.61 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2989.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4842.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4774.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4152.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3912.13 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2768.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2757.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2999.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3007.87 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4881.49 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   4814.58 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4203.87 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   3955.20 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2819.79 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2808.82 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3049.35 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3057.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4839.40 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4764.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4161.69 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3909.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2782.20 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2771.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3012.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3020.68 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4824.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4749.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4151.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3897.85 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2776.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2765.74 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3006.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3014.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4831.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4755.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4161.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3905.68 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2790.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2779.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3019.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3027.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4952.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4882.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4240.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3975.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2913.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2903.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3118.74 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3126.40 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5820.94 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   5708.25 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   5093.90 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   4642.57 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3515.81 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3565.58 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3988.37 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3995.68 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   2082.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   2093.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   2763.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   2087.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   1491.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   1491.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   1478.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   1486.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   2009.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   2019.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   2030.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   2013.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1314.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1314.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1307.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1309.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   1978.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   1987.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   1977.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   1982.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1267.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1267.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1259.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1259.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   1987.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   1995.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   1983.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   1990.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1262.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1262.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1255.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1254.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   1979.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   1984.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   1976.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   1981.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1245.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1245.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1240.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1239.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   2038.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   2043.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   2035.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   2040.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1291.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1291.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1286.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1286.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   2073.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   2077.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   2071.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   2075.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1317.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1317.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1313.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1313.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   2110.78 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   2113.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   2109.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   2111.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   1346.83 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   1346.81 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   1344.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   1344.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   2240.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   2240.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   2239.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   2239.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   1460.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   1460.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   1461.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   1461.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   2692.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   2695.76 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   2692.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   2695.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   1952.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   1952.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   1948.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   1948.16 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.27 1120.11 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 342.05 1120.11 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 414.20 1120.11 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.24 274.00 1120.11 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 186.02 1120.11 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.16 184.74 1120.11 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.17 194.73 1120.11 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.18 200.34 1120.11 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 400.14 1120.11 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 395.46 1120.11 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 362.02 1120.11 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 322.65 1120.11 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 219.36 1120.11 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.19 218.37 1120.11 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 231.92 1120.11 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 233.88 1120.11 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 399.95 1120.11 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 395.44 1120.11 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.23 1120.11 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 324.85 1120.11 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 221.57 1120.11 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 220.60 1120.11 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 234.60 1120.11 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 235.46 1120.11 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 401.31 1120.11 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 396.68 1120.11 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 345.23 1120.11 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 326.55 1120.11 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 223.85 1120.11 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 222.90 1120.11 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 236.84 1120.11 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.55 1120.11 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 405.45 1120.11 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 400.84 1120.11 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 349.53 1120.11 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 331.00 1120.11 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 228.65 1120.11 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 227.71 1120.11 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 241.54 1120.11 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 242.21 1120.11 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 402.02 1120.11 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 397.23 1120.11 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.55 1120.11 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 327.74 1120.11 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.81 1120.11 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 224.89 1120.11 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.78 1120.11 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.45 1120.11 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 401.35 1120.11 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 396.49 1120.11 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 346.24 1120.11 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 327.27 1120.11 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 225.64 1120.11 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 224.74 1120.11 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 238.58 1120.11 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 239.25 1120.11 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 402.42 1120.11 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 397.50 1120.11 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.31 347.57 1120.11 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 328.45 1120.11 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 227.13 1120.11 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.20 226.24 1120.11 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 240.00 1120.11 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 240.66 1120.11 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 413.77 1120.11 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 408.91 1120.11 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.32 354.85 1120.11 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.30 334.95 1120.11 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.96 1120.11 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.21 237.08 1120.11 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 248.35 1120.11 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.22 249.00 1120.11 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.56 622.50 0.44 487.75 1120.11 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 479.03 1120.11 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.56 622.50 0.38 422.78 1120.11 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 390.63 1120.11 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 288.85 1120.11 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.26 287.39 1120.11 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.19 1120.11 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.56 622.50 0.29 323.81 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.0065 1660.62 255050.01 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2978.07 3573.69 0.257 0.308 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47 0.00558
G NW APARTMENT 2950.25 3540.30 0.254 0.305 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 38.27 0.00558
OFFICE 3572.68 4287.21 0.308 0.370 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 38.07 0.00558
G NE APARTMENT 2363.34 2836.01 0.204 0.245 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 36.74 0.00558
G N1 APARTMENT 1604.47 1925.36 0.138 0.166 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61 0.00558
G N2 APARTMENT 1593.42 1912.11 0.137 0.165 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61 0.00558
G S1 APARTMENT 1679.56 2015.47 0.145 0.174 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
G S2 APARTMENT 1728.01 2073.62 0.149 0.179 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F2 SW APARTMENT 3451.37 4141.64 0.298 0.357 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
F2 NW APARTMENT 3410.96 4093.15 0.294 0.353 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 38.27 0.00558
F2 SE APARTMENT 3122.55 3747.06 0.269 0.323 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 38.07 0.00558
F2 NE APARTMENT 2782.96 3339.55 0.240 0.288 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F2 N1 APARTMENT 1892.04 2270.45 0.163 0.196 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F2 N2 APARTMENT 1883.46 2260.15 0.162 0.195 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F2 S1 APARTMENT 2000.38 2400.46 0.173 0.207 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F2 S2 APARTMENT 2017.25 2420.71 0.174 0.209 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F3 SW APARTMENT 3449.75 4139.71 0.298 0.357 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
F3 NW APARTMENT 3410.80 4092.96 0.294 0.353 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 38.27 0.00558
F3 SE APARTMENT 2977.78 3573.33 0.257 0.308 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 38.07 0.00558
F3 NE APARTMENT 2801.98 3362.38 0.242 0.290 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F3 N1 APARTMENT 1911.09 2293.30 0.165 0.198 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F3 N2 APARTMENT 1902.72 2283.27 0.164 0.197 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F3 S1 APARTMENT 2023.47 2428.16 0.175 0.209 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F3 S2 APARTMENT 2030.93 2437.11 0.175 0.210 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F4 SW APARTMENT 3461.49 4153.78 0.299 0.358 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
F4 NW APARTMENT 3421.53 4105.84 0.295 0.354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
F4 SE APARTMENT 2977.75 3573.31 0.257 0.308 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 38.07 0.00558
F4 NE APARTMENT 2816.67 3380.00 0.243 0.292 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F4 N1 APARTMENT 1930.74 2316.89 0.167 0.200 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F4 N2 APARTMENT 1922.53 2307.04 0.166 0.199 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F4 S1 APARTMENT 2042.85 2451.42 0.176 0.211 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F4 S2 APARTMENT 2048.92 2458.71 0.177 0.212 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
M SW APARTMENT 3497.20 4196.64 0.302 0.362 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
M NW APARTMENT 3457.43 4148.92 0.298 0.358 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
M SE APARTMENT 3014.92 3617.91 0.260 0.312 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
M NE APARTMENT 2855.03 3426.04 0.246 0.296 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
M N1 APARTMENT 1972.16 2366.60 0.170 0.204 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
M N2 APARTMENT 1964.07 2356.88 0.169 0.203 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
M S1 APARTMENT 2083.34 2500.01 0.180 0.216 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
M S2 APARTMENT 2089.19 2507.03 0.180 0.216 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F6 SW APARTMENT 3467.69 4161.23 0.299 0.359 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47 0.00558
F6 NW APARTMENT 3426.32 4111.58 0.296 0.355 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
F6 SE APARTMENT 2989.22 3587.07 0.258 0.309 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
F6 NE APARTMENT 2826.94 3392.33 0.244 0.293 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F6 N1 APARTMENT 1947.72 2337.26 0.168 0.202 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F6 N2 APARTMENT 1939.77 2327.72 0.167 0.201 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F6 S1 APARTMENT 2059.54 2471.45 0.178 0.213 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F6 S2 APARTMENT 2065.34 2478.41 0.178 0.214 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F7 SW APARTMENT 3461.93 4154.31 0.299 0.358 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47 0.00558
F7 NW APARTMENT 3419.98 4103.97 0.295 0.354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
F7 SE APARTMENT 2986.54 3583.85 0.258 0.309 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
F7 NE APARTMENT 2822.91 3387.50 0.243 0.292 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F7 N1 APARTMENT 1946.25 2335.50 0.168 0.201 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F7 N2 APARTMENT 1938.42 2326.10 0.167 0.201 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F7 S1 APARTMENT 2057.86 2469.43 0.177 0.213 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F7 S2 APARTMENT 2063.63 2476.36 0.178 0.214 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F8 SW APARTMENT 3471.15 4165.38 0.299 0.359 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47 0.00558
F8 NW APARTMENT 3428.67 4114.40 0.296 0.355 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
F8 SE APARTMENT 2998.05 3597.66 0.259 0.310 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
F8 NE APARTMENT 2833.06 3399.67 0.244 0.293 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F8 N1 APARTMENT 1959.11 2350.93 0.169 0.203 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F8 N2 APARTMENT 1951.38 2341.66 0.168 0.202 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F8 S1 APARTMENT 2070.07 2484.09 0.179 0.214 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F8 S2 APARTMENT 2075.83 2490.99 0.179 0.215 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 40.63 0.00558
F9 SW APARTMENT 3569.05 4282.86 0.308 0.369 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
F9 NW APARTMENT 3527.08 4232.50 0.304 0.365 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 38.61 0.00558
F9 SE APARTMENT 3060.81 3672.97 0.264 0.317 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 38.41 0.00558
F9 NE APARTMENT 2889.20 3467.03 0.249 0.299 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 37.24 0.00558
F9 N1 APARTMENT 2052.52 2463.02 0.177 0.212 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F9 N2 APARTMENT 2044.85 2453.82 0.176 0.212 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
F9 S1 APARTMENT 2142.11 2570.54 0.185 0.222 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558
F9 S2 APARTMENT 2147.77 2577.32 0.185 0.222 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558
T SW APARTMENT 4207.20 5048.64 0.363 0.435 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 39.74 0.00558
T NW APARTMENT 4131.98 4958.38 0.356 0.428 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
T SE APARTMENT 3646.82 4376.18 0.315 0.377 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558
T NE APARTMENT 3369.49 4043.39 0.291 0.349 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 38.07 0.00558
T N1 APARTMENT 2491.46 2989.75 0.215 0.258 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
T N2 APARTMENT 2478.85 2974.62 0.214 0.257 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 40.60 0.00558
T S1 APARTMENT 2787.64 3345.17 0.240 0.289 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558
T S2 APARTMENT 2793.03 3351.63 0.241 0.289 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 40.80 0.00558


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1250.01 1500.02 0.061 0.074 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 0.50 0.00432
G NW APARTMENT 1258.97 1510.77 0.062 0.074 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 0.50 0.00432
OFFICE 1586.96 1904.35 0.078 0.093 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 18:45:00 0.50 0.00432
G NE APARTMENT 1254.13 1504.96 0.061 0.074 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 0.50 0.00432
G N1 APARTMENT 750.07 900.08 0.037 0.044 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
G N2 APARTMENT 749.99 899.99 0.037 0.044 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
G S1 APARTMENT 739.11 886.93 0.036 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
G S2 APARTMENT 746.15 895.38 0.037 0.044 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
F2 SW APARTMENT 1188.55 1426.26 0.058 0.070 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 NW APARTMENT 1196.54 1435.85 0.059 0.070 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 SE APARTMENT 1205.73 1446.88 0.059 0.071 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 NE APARTMENT 1191.63 1429.96 0.058 0.070 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 N1 APARTMENT 600.40 720.49 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 N2 APARTMENT 600.32 720.38 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 S1 APARTMENT 594.70 713.64 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F2 S2 APARTMENT 596.18 715.42 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 SW APARTMENT 1162.42 1394.90 0.057 0.068 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 NW APARTMENT 1169.48 1403.38 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 SE APARTMENT 1160.88 1393.06 0.057 0.068 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 NE APARTMENT 1165.27 1398.32 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 N1 APARTMENT 560.43 672.52 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 N2 APARTMENT 560.36 672.43 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 S1 APARTMENT 553.83 664.60 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F3 S2 APARTMENT 554.03 664.84 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 SW APARTMENT 1169.76 1403.71 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 NW APARTMENT 1176.10 1411.32 0.058 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 SE APARTMENT 1166.55 1399.86 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 NE APARTMENT 1172.57 1407.09 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 N1 APARTMENT 556.31 667.57 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 N2 APARTMENT 556.25 667.50 0.027 0.033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 S1 APARTMENT 550.20 660.24 0.027 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F4 S2 APARTMENT 550.18 660.22 0.027 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M SW APARTMENT 1162.88 1395.45 0.057 0.068 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M NW APARTMENT 1167.39 1400.86 0.057 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M SE APARTMENT 1160.04 1392.04 0.057 0.068 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M NE APARTMENT 1164.51 1397.42 0.057 0.068 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M N1 APARTMENT 541.86 650.23 0.027 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M N2 APARTMENT 541.81 650.17 0.027 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M S1 APARTMENT 537.54 645.04 0.026 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
M S2 APARTMENT 537.49 644.99 0.026 0.032 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 SW APARTMENT 1212.64 1455.17 0.059 0.071 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 NW APARTMENT 1217.04 1460.45 0.060 0.072 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 SE APARTMENT 1210.36 1452.44 0.059 0.071 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 NE APARTMENT 1214.76 1457.71 0.060 0.071 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 N1 APARTMENT 580.97 697.16 0.028 0.034 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 N2 APARTMENT 580.93 697.11 0.028 0.034 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 S1 APARTMENT 576.73 692.07 0.028 0.034 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F6 S2 APARTMENT 576.69 692.02 0.028 0.034 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 SW APARTMENT 1242.08 1490.49 0.061 0.073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 NW APARTMENT 1245.41 1494.50 0.061 0.073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 SE APARTMENT 1240.35 1488.42 0.061 0.073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 NE APARTMENT 1243.69 1492.43 0.061 0.073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 N1 APARTMENT 602.67 723.20 0.030 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 N2 APARTMENT 602.64 723.17 0.030 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 S1 APARTMENT 599.48 719.38 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F7 S2 APARTMENT 599.45 719.34 0.029 0.035 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 SW APARTMENT 1273.90 1528.69 0.062 0.075 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 NW APARTMENT 1276.11 1531.33 0.063 0.075 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 SE APARTMENT 1272.70 1527.23 0.062 0.075 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 NE APARTMENT 1274.90 1529.88 0.062 0.075 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 N1 APARTMENT 627.86 753.43 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 N2 APARTMENT 627.84 753.41 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 S1 APARTMENT 625.80 750.96 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F8 S2 APARTMENT 625.78 750.93 0.031 0.037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 SW APARTMENT 1383.63 1660.35 0.068 0.081 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 NW APARTMENT 1383.31 1659.98 0.068 0.081 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 SE APARTMENT 1382.90 1659.48 0.068 0.081 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 NE APARTMENT 1382.59 1659.10 0.068 0.081 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 N1 APARTMENT 724.38 869.25 0.036 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 N2 APARTMENT 724.36 869.24 0.036 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 S1 APARTMENT 724.63 869.55 0.036 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
F9 S2 APARTMENT 724.61 869.54 0.036 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T SW APARTMENT 1765.98 2119.18 0.087 0.104 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T NW APARTMENT 1768.60 2122.31 0.087 0.104 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T SE APARTMENT 1765.70 2118.84 0.087 0.104 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T NE APARTMENT 1768.31 2121.98 0.087 0.104 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T N1 APARTMENT 1139.76 1367.71 0.056 0.067 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T N2 APARTMENT 1139.75 1367.71 0.056 0.067 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T S1 APARTMENT 1136.38 1363.66 0.056 0.067 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432
T S2 APARTMENT 1136.38 1363.65 0.056 0.067 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 0.50 0.00432


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.31 0.31 0.07 0.07
AIRLOOP G NW 0.31 0.31 0.07 0.07
AIRLOOP OFFICE 0.37 0.37 0.09 0.09
AIRLOOP G NE 0.24 0.24 0.07 0.07
AIRLOOP G N1 0.17 0.17 0.04 0.04
AIRLOOP G N2 0.16 0.16 0.04 0.04
AIRLOOP G S1 0.17 0.17 0.04 0.04
AIRLOOP G S2 0.18 0.18 0.04 0.04
AIRLOOP F2 SW 0.36 0.36 0.07 0.07
AIRLOOP F2 NW 0.35 0.35 0.07 0.07
AIRLOOP F2 SE 0.32 0.32 0.07 0.07
AIRLOOP F2 NE 0.29 0.29 0.07 0.07
AIRLOOP F2 N1 0.20 0.20 0.04 0.04
AIRLOOP F2 N2 0.19 0.19 0.04 0.04
AIRLOOP F2 S1 0.21 0.21 0.03 0.03
AIRLOOP F2 S2 0.21 0.21 0.04 0.04
AIRLOOP F3 SW 0.36 0.36 0.07 0.07
AIRLOOP F3 NW 0.35 0.35 0.07 0.07
AIRLOOP F3 SE 0.31 0.31 0.07 0.07
AIRLOOP F3 NE 0.29 0.29 0.07 0.07
AIRLOOP F3 N1 0.20 0.20 0.03 0.03
AIRLOOP F3 N2 0.20 0.20 0.03 0.03
AIRLOOP F3 S1 0.21 0.21 0.03 0.03
AIRLOOP F3 S2 0.21 0.21 0.03 0.03
AIRLOOP F4 SW 0.36 0.36 0.07 0.07
AIRLOOP F4 NW 0.35 0.35 0.07 0.07
AIRLOOP F4 SE 0.31 0.31 0.07 0.07
AIRLOOP F4 NE 0.29 0.29 0.07 0.07
AIRLOOP F4 N1 0.20 0.20 0.03 0.03
AIRLOOP F4 N2 0.20 0.20 0.03 0.03
AIRLOOP F4 S1 0.21 0.21 0.03 0.03
AIRLOOP F4 S2 0.21 0.21 0.03 0.03
AIRLOOP M SW 0.36 0.36 0.07 0.07
AIRLOOP M NW 0.36 0.36 0.07 0.07
AIRLOOP M SE 0.31 0.31 0.07 0.07
AIRLOOP M NE 0.30 0.30 0.07 0.07
AIRLOOP M N1 0.20 0.20 0.03 0.03
AIRLOOP M N2 0.20 0.20 0.03 0.03
AIRLOOP M S1 0.22 0.22 0.03 0.03
AIRLOOP M S2 0.22 0.22 0.03 0.03
AIRLOOP F6 SW 0.36 0.36 0.07 0.07
AIRLOOP F6 NW 0.35 0.35 0.07 0.07
AIRLOOP F6 SE 0.31 0.31 0.07 0.07
AIRLOOP F6 NE 0.29 0.29 0.07 0.07
AIRLOOP F6 N1 0.20 0.20 0.03 0.03
AIRLOOP F6 N2 0.20 0.20 0.03 0.03
AIRLOOP F6 S1 0.21 0.21 0.03 0.03
AIRLOOP F6 S2 0.21 0.21 0.03 0.03
AIRLOOP F7 SW 0.36 0.36 0.07 0.07
AIRLOOP F7 NW 0.35 0.35 0.07 0.07
AIRLOOP F7 SE 0.31 0.31 0.07 0.07
AIRLOOP F7 NE 0.29 0.29 0.07 0.07
AIRLOOP F7 N1 0.20 0.20 0.04 0.04
AIRLOOP F7 N2 0.20 0.20 0.04 0.04
AIRLOOP F7 S1 0.21 0.21 0.04 0.04
AIRLOOP F7 S2 0.21 0.21 0.04 0.04
AIRLOOP F8 SW 0.36 0.36 0.07 0.07
AIRLOOP F8 NW 0.35 0.35 0.08 0.08
AIRLOOP F8 SE 0.31 0.31 0.07 0.07
AIRLOOP F8 NE 0.29 0.29 0.07 0.07
AIRLOOP F8 N1 0.20 0.20 0.04 0.04
AIRLOOP F8 N2 0.20 0.20 0.04 0.04
AIRLOOP F8 S1 0.21 0.21 0.04 0.04
AIRLOOP F8 S2 0.21 0.21 0.04 0.04
AIRLOOP F9 SW 0.37 0.37 0.08 0.08
AIRLOOP F9 NW 0.37 0.37 0.08 0.08
AIRLOOP F9 SE 0.32 0.32 0.08 0.08
AIRLOOP F9 NE 0.30 0.30 0.08 0.08
AIRLOOP F9 N1 0.21 0.21 0.04 0.04
AIRLOOP F9 N2 0.21 0.21 0.04 0.04
AIRLOOP F9 S1 0.22 0.22 0.04 0.04
AIRLOOP F9 S2 0.22 0.22 0.04 0.04
AIRLOOP T SW 0.44 0.44 0.10 0.10
AIRLOOP T NW 0.43 0.43 0.10 0.10
AIRLOOP T SE 0.38 0.38 0.10 0.10
AIRLOOP T NE 0.35 0.35 0.10 0.10
AIRLOOP T N1 0.26 0.26 0.07 0.07
AIRLOOP T N2 0.26 0.26 0.07 0.07
AIRLOOP T S1 0.29 0.29 0.07 0.07
AIRLOOP T S2 0.29 0.29 0.07 0.07



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3222.25 3860.50 403.25
G NW APARTMENT 2953.25 4943.50 425.00
OFFICE 1060.75 233.00 4.00
G NE APARTMENT 2955.75 4827.50 415.50
G N1 APARTMENT 2769.00 5369.00 547.25
G N2 APARTMENT 2769.25 5367.50 547.25
G S1 APARTMENT 2953.75 4165.00 480.50
G S2 APARTMENT 2971.00 4094.75 473.00
F2 SW APARTMENT 4140.25 1879.00 296.25
F2 NW APARTMENT 3420.50 3676.25 318.00
F2 SE APARTMENT 4338.00 1703.50 271.00
F2 NE APARTMENT 3428.75 3631.75 302.75
F2 N1 APARTMENT 3128.00 3977.75 408.00
F2 N2 APARTMENT 3128.00 3976.50 407.00
F2 S1 APARTMENT 3949.00 1638.75 349.75
F2 S2 APARTMENT 3967.75 1616.75 347.00
F3 SW APARTMENT 4422.25 1513.00 293.25
F3 NW APARTMENT 3518.00 3304.75 318.25
F3 SE APARTMENT 4483.25 1510.75 281.50
F3 NE APARTMENT 3548.50 3325.25 302.75
F3 N1 APARTMENT 3266.25 3546.00 400.00
F3 N2 APARTMENT 3265.00 3555.00 399.75
F3 S1 APARTMENT 4317.00 1143.75 333.75
F3 S2 APARTMENT 4319.75 1141.00 332.00
F4 SW APARTMENT 4430.25 1469.25 295.75
F4 NW APARTMENT 3525.50 3215.50 319.25
F4 SE APARTMENT 4466.75 1496.75 287.75
F4 NE APARTMENT 3550.00 3250.00 307.50
F4 N1 APARTMENT 3297.50 3399.50 397.25
F4 N2 APARTMENT 3298.00 3404.50 397.00
F4 S1 APARTMENT 4367.00 1052.00 323.50
F4 S2 APARTMENT 4366.75 1050.75 322.00
M SW APARTMENT 4455.50 1439.75 294.25
M NW APARTMENT 3548.75 3157.75 317.50
M SE APARTMENT 4484.00 1465.00 285.75
M NE APARTMENT 3575.00 3193.75 304.00
M N1 APARTMENT 3343.75 3295.75 386.25
M N2 APARTMENT 3342.50 3300.75 385.00
M S1 APARTMENT 4412.25 999.00 313.25
M S2 APARTMENT 4412.00 999.50 311.50
F6 SW APARTMENT 4263.75 1630.50 311.25
F6 NW APARTMENT 3433.25 3346.00 332.75
F6 SE APARTMENT 4295.75 1636.25 301.50
F6 NE APARTMENT 3460.50 3382.00 322.25
F6 N1 APARTMENT 3235.75 3490.50 404.00
F6 N2 APARTMENT 3233.50 3501.25 403.75
F6 S1 APARTMENT 4211.00 1175.00 335.50
F6 S2 APARTMENT 4213.25 1177.50 334.25
F7 SW APARTMENT 4147.50 1756.25 320.50
F7 NW APARTMENT 3370.75 3473.50 341.25
F7 SE APARTMENT 4173.00 1765.25 311.75
F7 NE APARTMENT 3398.75 3485.00 328.50
F7 N1 APARTMENT 3182.00 3620.00 414.50
F7 N2 APARTMENT 3179.50 3628.00 413.50
F7 S1 APARTMENT 4096.00 1301.50 348.50
F7 S2 APARTMENT 4099.25 1302.50 348.25
F8 SW APARTMENT 4054.75 1865.25 324.50
F8 NW APARTMENT 3333.00 3567.25 345.00
F8 SE APARTMENT 4087.25 1873.50 314.00
F8 NE APARTMENT 3366.75 3570.00 331.25
F8 N1 APARTMENT 3134.75 3718.75 416.00
F8 N2 APARTMENT 3134.50 3724.75 414.25
F8 S1 APARTMENT 4000.50 1410.00 353.00
F8 S2 APARTMENT 4004.25 1412.75 352.75
F9 SW APARTMENT 3989.75 2053.75 322.25
F9 NW APARTMENT 3348.50 3681.25 338.25
F9 SE APARTMENT 4021.25 2034.50 309.75
F9 NE APARTMENT 3373.50 3660.25 327.00
F9 N1 APARTMENT 3138.75 3817.50 403.75
F9 N2 APARTMENT 3139.75 3822.00 402.75
F9 S1 APARTMENT 3885.00 1642.00 348.25
F9 S2 APARTMENT 3886.75 1645.50 348.25
T SW APARTMENT 4399.25 2898.50 362.00
T NW APARTMENT 3693.00 3843.75 403.75
T SE APARTMENT 4517.25 2808.00 349.00
T NE APARTMENT 3788.50 3835.50 394.25
T N1 APARTMENT 3498.25 4053.25 423.25
T N2 APARTMENT 3502.00 4041.00 415.25
T S1 APARTMENT 4309.00 2660.00 375.00
T S2 APARTMENT 4317.75 2662.00 375.00
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5444.50 5420.75 627.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 68.50 0.00 68.50
G NW APARTMENT 0.00 74.25 0.00 74.25
OFFICE 0.25 28.00 0.00 25.50
G NE APARTMENT 0.00 32.00 0.00 32.00
G N1 APARTMENT 2.00 83.00 2.00 83.00
G N2 APARTMENT 4.25 82.75 4.25 82.75
G S1 APARTMENT 0.00 227.75 0.00 227.75
G S2 APARTMENT 0.00 197.00 0.00 197.00
F2 SW APARTMENT 0.00 87.75 0.00 87.75
F2 NW APARTMENT 0.00 69.00 0.00 69.00
F2 SE APARTMENT 0.00 75.50 0.00 75.50
F2 NE APARTMENT 0.00 30.50 0.00 30.50
F2 N1 APARTMENT 0.50 83.00 0.50 83.00
F2 N2 APARTMENT 0.50 84.75 0.50 84.75
F2 S1 APARTMENT 0.00 352.00 0.00 352.00
F2 S2 APARTMENT 0.00 338.50 0.00 338.50
F3 SW APARTMENT 0.00 124.00 0.00 124.00
F3 NW APARTMENT 0.00 75.25 0.00 75.25
F3 SE APARTMENT 0.00 141.75 0.00 141.75
F3 NE APARTMENT 0.00 38.00 0.00 38.00
F3 N1 APARTMENT 0.25 99.50 0.25 99.50
F3 N2 APARTMENT 0.25 100.75 0.25 100.75
F3 S1 APARTMENT 0.00 404.00 0.00 404.00
F3 S2 APARTMENT 0.00 399.50 0.00 399.50
F4 SW APARTMENT 0.00 130.00 0.00 130.00
F4 NW APARTMENT 0.00 80.75 0.00 80.75
F4 SE APARTMENT 0.00 152.75 0.00 152.75
F4 NE APARTMENT 0.00 45.25 0.00 45.25
F4 N1 APARTMENT 0.50 104.50 0.50 104.50
F4 N2 APARTMENT 0.50 105.25 0.50 105.25
F4 S1 APARTMENT 0.00 404.25 0.00 404.25
F4 S2 APARTMENT 0.00 402.00 0.00 402.00
M SW APARTMENT 0.00 129.75 0.00 129.75
M NW APARTMENT 0.00 83.00 0.00 83.00
M SE APARTMENT 0.00 141.25 0.00 141.25
M NE APARTMENT 0.00 53.00 0.00 53.00
M N1 APARTMENT 0.50 107.50 0.50 107.50
M N2 APARTMENT 0.50 107.50 0.50 107.50
M S1 APARTMENT 0.00 392.00 0.00 392.00
M S2 APARTMENT 0.00 389.75 0.00 389.75
F6 SW APARTMENT 0.00 122.25 0.00 122.25
F6 NW APARTMENT 0.00 88.25 0.00 88.25
F6 SE APARTMENT 0.00 135.75 0.00 135.75
F6 NE APARTMENT 0.00 60.75 0.00 60.75
F6 N1 APARTMENT 1.00 111.00 1.00 111.00
F6 N2 APARTMENT 1.00 111.50 1.00 111.50
F6 S1 APARTMENT 0.00 382.00 0.00 382.00
F6 S2 APARTMENT 0.00 381.25 0.00 381.25
F7 SW APARTMENT 0.00 117.25 0.00 117.25
F7 NW APARTMENT 0.00 88.25 0.00 88.25
F7 SE APARTMENT 0.00 131.75 0.00 131.75
F7 NE APARTMENT 0.00 67.75 0.00 67.75
F7 N1 APARTMENT 0.00 113.75 0.00 113.75
F7 N2 APARTMENT 0.75 116.00 0.75 116.00
F7 S1 APARTMENT 0.00 370.00 0.00 370.00
F7 S2 APARTMENT 0.00 366.50 0.00 366.50
F8 SW APARTMENT 0.00 111.75 0.00 111.75
F8 NW APARTMENT 0.00 89.25 0.00 89.25
F8 SE APARTMENT 0.00 127.25 0.00 127.25
F8 NE APARTMENT 0.00 73.50 0.00 73.50
F8 N1 APARTMENT 0.75 116.25 0.75 116.25
F8 N2 APARTMENT 0.50 117.00 0.50 117.00
F8 S1 APARTMENT 0.00 347.75 0.00 347.75
F8 S2 APARTMENT 0.00 341.75 0.00 341.75
F9 SW APARTMENT 0.00 99.50 0.00 99.50
F9 NW APARTMENT 0.00 84.75 0.00 84.75
F9 SE APARTMENT 0.00 122.75 0.00 122.75
F9 NE APARTMENT 0.00 86.75 0.00 86.75
F9 N1 APARTMENT 0.00 110.00 0.00 110.00
F9 N2 APARTMENT 0.00 111.50 0.00 111.50
F9 S1 APARTMENT 0.00 283.25 0.00 283.25
F9 S2 APARTMENT 0.00 281.50 0.00 281.50
T SW APARTMENT 0.00 98.50 0.00 98.50
T NW APARTMENT 0.00 78.25 0.00 78.25
T SE APARTMENT 0.00 87.25 0.00 87.25
T NE APARTMENT 0.00 69.00 0.00 69.00
T N1 APARTMENT 0.00 117.75 0.00 117.75
T N2 APARTMENT 0.00 94.00 0.00 94.00
T S1 APARTMENT 0.00 183.00 0.00 183.00
T S2 APARTMENT 0.00 181.50 0.00 181.50
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 11.00 642.50 10.75 640.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.347
G NW APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.320
OFFICE 0.94 1.00 268.96 0.521 0.083 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.355 0.079 0.000 0.321
G N1 APARTMENT 1.71 2.50 268.96 0.355 0.048 0.000 0.309
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.048 0.000 0.309
G S1 APARTMENT 1.71 2.50 268.96 0.356 0.048 0.000 0.344
G S2 APARTMENT 1.71 2.50 268.97 0.356 0.048 0.000 0.344
F2 SW APARTMENT 1.71 2.50 268.96 0.356 0.114 0.000 0.393
F2 NW APARTMENT 1.71 2.50 268.96 0.355 0.114 0.000 0.367
F2 SE APARTMENT 1.71 2.50 268.96 0.356 0.114 0.000 0.393
F2 NE APARTMENT 1.71 2.50 268.96 0.355 0.114 0.000 0.366
F2 N1 APARTMENT 1.71 2.50 268.96 0.355 0.069 0.000 0.359
F2 N2 APARTMENT 1.71 2.50 268.97 0.355 0.069 0.000 0.359
F2 S1 APARTMENT 1.71 2.50 268.96 0.356 0.069 0.000 0.392
F2 S2 APARTMENT 1.71 2.50 268.97 0.356 0.069 0.000 0.392
F3 SW APARTMENT 1.71 2.50 268.96 0.356 0.135 0.000 0.419
F3 NW APARTMENT 1.71 2.50 268.96 0.355 0.135 0.000 0.392
F3 SE APARTMENT 1.71 2.50 268.96 0.356 0.135 0.000 0.420
F3 NE APARTMENT 1.71 2.50 268.96 0.355 0.135 0.000 0.391
F3 N1 APARTMENT 1.71 2.50 268.96 0.356 0.081 0.000 0.386
F3 N2 APARTMENT 1.71 2.50 268.97 0.356 0.081 0.000 0.386
F3 S1 APARTMENT 1.71 2.50 268.96 0.356 0.081 0.000 0.419
F3 S2 APARTMENT 1.71 2.50 268.97 0.356 0.081 0.000 0.419
F4 SW APARTMENT 1.71 2.50 268.96 0.356 0.151 0.000 0.440
F4 NW APARTMENT 1.71 2.50 268.96 0.355 0.151 0.000 0.410
F4 SE APARTMENT 1.71 2.50 268.96 0.356 0.151 0.000 0.440
F4 NE APARTMENT 1.71 2.50 268.96 0.355 0.151 0.000 0.409
F4 N1 APARTMENT 1.71 2.50 268.96 0.356 0.091 0.000 0.405
F4 N2 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.405
F4 S1 APARTMENT 1.71 2.50 268.96 0.356 0.091 0.000 0.440
F4 S2 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.440
M SW APARTMENT 1.71 2.50 268.96 0.356 0.164 0.000 0.458
M NW APARTMENT 1.71 2.50 268.96 0.355 0.164 0.000 0.426
M SE APARTMENT 1.71 2.50 268.96 0.356 0.164 0.000 0.458
M NE APARTMENT 1.71 2.50 268.96 0.355 0.164 0.000 0.425
M N1 APARTMENT 1.71 2.50 268.96 0.356 0.099 0.000 0.421
M N2 APARTMENT 1.71 2.50 268.97 0.356 0.099 0.000 0.421
M S1 APARTMENT 1.71 2.50 268.96 0.356 0.099 0.000 0.458
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.099 0.000 0.458
F6 SW APARTMENT 1.71 2.50 268.96 0.356 0.175 0.000 0.477
F6 NW APARTMENT 1.71 2.50 268.96 0.355 0.175 0.000 0.441
F6 SE APARTMENT 1.71 2.50 268.96 0.356 0.175 0.000 0.477
F6 NE APARTMENT 1.71 2.50 268.96 0.355 0.175 0.000 0.441
F6 N1 APARTMENT 1.71 2.50 268.96 0.356 0.105 0.000 0.437
F6 N2 APARTMENT 1.71 2.50 268.97 0.356 0.105 0.000 0.437
F6 S1 APARTMENT 1.71 2.50 268.96 0.356 0.106 0.000 0.477
F6 S2 APARTMENT 1.71 2.50 268.97 0.356 0.106 0.000 0.477
F7 SW APARTMENT 1.71 2.50 268.96 0.356 0.185 0.000 0.491
F7 NW APARTMENT 1.71 2.50 268.96 0.355 0.185 0.000 0.453
F7 SE APARTMENT 1.71 2.50 268.96 0.356 0.185 0.000 0.491
F7 NE APARTMENT 1.71 2.50 268.96 0.355 0.185 0.000 0.453
F7 N1 APARTMENT 1.71 2.50 268.96 0.356 0.111 0.000 0.449
F7 N2 APARTMENT 1.71 2.50 268.97 0.356 0.111 0.000 0.449
F7 S1 APARTMENT 1.71 2.50 268.96 0.356 0.112 0.000 0.491
F7 S2 APARTMENT 1.71 2.50 268.97 0.356 0.112 0.000 0.491
F8 SW APARTMENT 1.71 2.50 268.96 0.356 0.194 0.000 0.504
F8 NW APARTMENT 1.71 2.50 268.96 0.355 0.194 0.000 0.464
F8 SE APARTMENT 1.71 2.50 268.96 0.356 0.194 0.000 0.504
F8 NE APARTMENT 1.71 2.50 268.96 0.355 0.194 0.000 0.463
F8 N1 APARTMENT 1.71 2.50 268.96 0.355 0.117 0.000 0.459
F8 N2 APARTMENT 1.71 2.50 268.97 0.355 0.117 0.000 0.459
F8 S1 APARTMENT 1.71 2.50 268.96 0.356 0.117 0.000 0.504
F8 S2 APARTMENT 1.71 2.50 268.97 0.356 0.117 0.000 0.504
F9 SW APARTMENT 1.71 2.50 268.96 0.356 0.202 0.000 0.516
F9 NW APARTMENT 1.71 2.50 268.96 0.355 0.202 0.000 0.473
F9 SE APARTMENT 1.71 2.50 268.96 0.356 0.202 0.000 0.516
F9 NE APARTMENT 1.71 2.50 268.96 0.355 0.202 0.000 0.473
F9 N1 APARTMENT 1.71 2.50 268.96 0.355 0.122 0.000 0.468
F9 N2 APARTMENT 1.71 2.50 268.97 0.355 0.122 0.000 0.468
F9 S1 APARTMENT 1.71 2.50 268.96 0.356 0.122 0.000 0.515
F9 S2 APARTMENT 1.71 2.50 268.97 0.356 0.122 0.000 0.515
T SW APARTMENT 1.71 2.50 268.96 0.355 0.209 0.000 0.526
T NW APARTMENT 1.71 2.50 268.96 0.355 0.209 0.000 0.483
T SE APARTMENT 1.71 2.50 268.96 0.355 0.209 0.000 0.526
T NE APARTMENT 1.71 2.50 268.96 0.355 0.209 0.000 0.484
T N1 APARTMENT 1.71 2.50 268.96 0.355 0.126 0.000 0.478
T N2 APARTMENT 1.71 2.50 268.97 0.355 0.126 0.000 0.478
T S1 APARTMENT 1.71 2.50 268.96 0.356 0.126 0.000 0.525
T S2 APARTMENT 1.71 2.50 268.97 0.356 0.126 0.000 0.525
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.510 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.349 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.349 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.348 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.346 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.346 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.347 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.347 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4197
Defaulted Fields 814
Fields with Defaults 11307
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
Electricity:Building 1547.51 26803.46 01-JAN-03:15 79071.91 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity 416.41 7980.64 01-JAN-00:15 25049.15 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 348.50 6974.01 01-JAN-00:15 20603.34 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:OFFICE 29.50 508.27 01-JAN-00:15 2167.24 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 21.95 379.58 01-JAN-00:15 1622.33 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 37.06 1175.12 01-JAN-00:15 1175.12 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 14.63 238.08 01-JAN-03:15 783.07 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 2.41 14.40 01-JAN-00:15 230.46 01-JAN-19:15
Electricity:Zone:T CORRIDOR 177.27 1611.36 01-JAN-00:15 10825.51 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 18.53 587.56 01-JAN-00:15 587.56 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 67.92 1006.63 01-JAN-00:15 4445.81 01-JAN-19:15
InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1131.09 18822.82 01-JAN-03:15 56933.81 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 7.55 128.69 01-JAN-00:15 544.91 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 158.74 1023.79 01-JAN-00:15 10237.95 01-JAN-07:15
Fans:Electricity 770.14 24420.97 02-JAN-14:30 24420.97 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1703.75 24801.50 09-JAN-03:15 102266.84 28-JUN-16:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
ElectricityPurchased:Plant 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
Cogeneration:ElectricityPurchased 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
ElectricityNet:Plant 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
Cogeneration:ElectricityNet 3505.44 62361.99 09-JAN-03:15 186660.91 16-JUN-19:30
ExteriorLights:Electricity 168.51 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:ExteriorLights:Electricity 168.51 0.00 01-JAN-07:30 10720.10 01-JAN-00:15
General:Fans:Electricity 770.14 24420.97 02-JAN-14:30 24420.97 01-JAN-00:15
Cooling:Electricity 908.06 0.00 01-JAN-00:15 76799.83 28-JUN-15:15
Heating:Electricity 4.73 0.00 01-JAN-12:00 16309.45 07-DEC-05:00
Electricity:Plant 85.67 36.93 02-JAN-18:45 4617.90 17-JUN-16:00
HeatRejection:Electricity 33.55 0.00 01-JAN-00:15 2920.35 17-JUN-16:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 52.12 36.93 02-JAN-18:45 1697.55 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.62 0.00 01-JAN-00:15 37.57 01-JAN-19:30
WIRED_INT_EQUIP 973.17 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 901.91 9260.51 01-JAN-00:15 105770.42 17-DEC-07:30
Gas:Plant 901.91 9260.51 01-JAN-00:15 105770.42 17-DEC-07:30
WaterSystems:Gas 899.03 9260.51 01-JAN-00:15 81305.76 25-JAN-08:00
Water Heater:WaterSystems:Gas 899.03 9260.51 01-JAN-00:15 81305.76 25-JAN-08:00
Heating:Gas 2.88 0.00 01-JAN-00:15 54020.71 07-DEC-05:00
Boiler:Heating:Gas 2.88 0.00 01-JAN-00:15 54020.71 07-DEC-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 3685.13 0.00 01-JAN-00:15 348718.55 13-JUL-18:45
PlantLoopCoolingDemand:HVAC 3685.13 0.00 01-JAN-00:15 348718.55 13-JUL-18:45
CoolingCoils:PlantLoopCoolingDemand 3685.13 0.00 01-JAN-00:15 348718.55 13-JUL-18:45


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 8068.70 0.00 01-JAN-02:30 0.00 28-JUN-17:30
Water:Plant 8068.70 0.00 01-JAN-02:30 0.00 28-JUN-17:30
WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 8068.70 0.00 01-JAN-02:30 0.00 28-JUN-17:30
MainsWater:Plant 8068.70 0.00 01-JAN-02:30 0.00 28-JUN-17:30
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:30 0.00 01-JAN-07:15
HeatRejection:Water 3290.19 0.00 01-JAN-00:15 0.00 16-JUN-16:00
HeatRejection:MainsWater 3290.19 0.00 01-JAN-00:15 0.00 16-JUN-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 693.51 344.92 25-JUL-01:15 85061.42 07-DEC-06:15
PlantLoopHeatingDemand:Plant 681.09 344.92 25-JUL-01:15 48967.99 20-JAN-07:15
WaterSystems:PlantLoopHeatingDemand 681.09 344.92 25-JUL-01:15 48967.99 20-JAN-07:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 5765.03 5980.57 18-FEB-02:15 508424.07 28-JUN-17:30
EnergyTransfer:Building 2233.08 3977.63 08-MAR-19:30 215585.48 22-JUL-17:30
EnergyTransfer:Zone:G SW APARTMENT 24.65 0.01 19-MAR-06:00 3278.77 01-NOV-15:15
Heating:EnergyTransfer 56.29 0.00 27-JAN-13:45 37935.08 07-DEC-05:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 1.00 0.00 01-JAN-08:30 680.76 07-DEC-05:00
Cooling:EnergyTransfer 2176.79 0.00 02-JAN-18:30 215585.48 22-JUL-17:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 23.65 0.00 01-JAN-00:15 3278.77 01-NOV-15:15
EnergyTransfer:Zone:G NW APARTMENT 19.76 0.00 31-JAN-03:15 3160.46 28-JUN-17:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.98 0.00 01-JAN-20:45 941.84 07-DEC-05:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 17.78 0.00 01-JAN-00:15 3160.46 28-JUN-17:30
EnergyTransfer:Zone:OFFICE 31.40 0.01 19-MAR-00:45 3820.06 28-SEP-10:00
Heating:EnergyTransfer:Zone:OFFICE 0.57 0.00 01-JAN-08:00 726.33 07-DEC-06:00
Cooling:EnergyTransfer:Zone:OFFICE 30.83 0.00 01-JAN-00:15 3820.06 28-SEP-10:00
EnergyTransfer:Zone:G NE APARTMENT 19.52 0.02 14-MAR-24:00 2517.75 28-JUN-08:45
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.49 0.00 01-JAN-08:45 951.85 07-DEC-05:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 18.03 0.00 01-JAN-00:15 2517.75 28-JUN-08:45
EnergyTransfer:Zone:G N1 APARTMENT 13.19 0.01 30-APR-04:45 1684.11 19-JUN-19:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.72 0.00 01-JAN-11:00 641.12 07-DEC-16:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 12.48 0.00 01-JAN-00:15 1684.11 19-JUN-19:00
EnergyTransfer:Zone:G N2 APARTMENT 13.21 0.03 21-OCT-03:45 1671.71 19-JUN-19:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.71 0.00 01-JAN-11:00 643.82 07-DEC-16:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 12.50 0.00 01-JAN-00:15 1671.71 19-JUN-19:00
EnergyTransfer:Zone:G S1 APARTMENT 18.45 0.01 12-NOV-03:45 2009.42 02-NOV-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.17 0.00 01-JAN-00:15 423.45 10-FEB-12:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 18.28 0.00 02-JAN-10:30 2009.42 02-NOV-13:30
EnergyTransfer:Zone:G S2 APARTMENT 18.71 0.03 28-MAY-01:00 2059.80 02-NOV-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.18 0.00 01-JAN-00:15 367.50 10-FEB-12:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 18.53 0.00 02-JAN-10:30 2059.80 02-NOV-13:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 34.89 0.03 05-FEB-01:30 3875.81 01-NOV-15:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.54 0.00 01-JAN-00:15 402.05 16-MAR-07:45
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 34.35 0.00 02-JAN-10:30 3875.81 01-NOV-15:15
EnergyTransfer:Zone:F2 NW APARTMENT 26.59 0.00 18-JAN-03:00 3631.92 28-JUN-17:45
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 1.45 0.00 01-JAN-16:15 834.00 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 25.14 0.00 01-JAN-00:15 3631.92 28-JUN-17:45
EnergyTransfer:Zone:F2 SE APARTMENT 36.73 0.00 04-MAR-17:00 3466.27 28-SEP-10:15
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.35 0.00 01-JAN-00:15 347.34 07-NOV-09:15
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 36.38 0.00 02-JAN-18:00 3466.27 28-SEP-10:15
EnergyTransfer:Zone:F2 NE APARTMENT 26.74 0.01 19-MAR-02:30 2970.48 28-JUN-08:30
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.95 0.00 01-JAN-08:30 845.76 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 25.79 0.00 01-JAN-00:15 2970.48 28-JUN-08:30
EnergyTransfer:Zone:F2 N1 APARTMENT 19.06 0.07 17-DEC-13:30 1995.00 20-JUN-18:45
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.41 0.00 01-JAN-00:15 498.73 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 18.65 0.00 01-JAN-01:00 1995.00 20-JUN-18:45
EnergyTransfer:Zone:F2 N2 APARTMENT 19.09 0.05 23-MAR-10:00 1985.63 20-JUN-18:45
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.41 0.00 01-JAN-00:15 501.80 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 18.68 0.00 01-JAN-00:45 1985.63 20-JUN-18:45
EnergyTransfer:Zone:F2 S1 APARTMENT 27.84 0.11 25-NOV-15:15 2427.33 02-NOV-13:30
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.11 0.00 01-JAN-00:15 157.71 10-FEB-13:45
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 27.73 0.00 02-JAN-10:30 2427.33 02-NOV-13:30
EnergyTransfer:Zone:F2 S2 APARTMENT 27.97 0.09 01-MAR-13:00 2444.97 02-NOV-13:30
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.12 0.00 01-JAN-00:15 161.46 10-FEB-13:45
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 27.86 0.00 02-JAN-10:30 2444.97 02-NOV-13:30
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 36.36 0.06 21-APR-01:30 3880.04 01-NOV-15:15
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.45 0.00 01-JAN-00:15 447.56 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 35.91 0.00 02-JAN-10:30 3880.04 01-NOV-15:15
EnergyTransfer:Zone:F3 NW APARTMENT 27.52 0.03 15-NOV-05:30 3628.96 22-JUL-17:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 1.24 0.00 01-JAN-16:15 794.42 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 26.28 0.00 01-JAN-00:15 3628.96 22-JUL-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 37.23 0.01 27-JAN-01:45 3303.70 09-OCT-10:45
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.29 0.00 01-JAN-00:15 328.29 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 36.94 0.00 02-JAN-18:15 3303.70 09-OCT-10:45
EnergyTransfer:Zone:F3 NE APARTMENT 27.86 0.01 28-OCT-00:45 2975.03 28-JUN-08:30
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.83 0.00 01-JAN-08:30 804.21 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 27.04 0.00 01-JAN-00:15 2975.03 28-JUN-08:30
EnergyTransfer:Zone:F3 N1 APARTMENT 20.33 0.03 07-DEC-00:45 2003.30 19-JUN-19:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.34 0.00 01-JAN-00:15 421.77 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 19.99 0.00 01-JAN-03:30 2003.30 19-JUN-19:00
EnergyTransfer:Zone:F3 N2 APARTMENT 20.35 0.14 22-DEC-17:45 1994.19 19-JUN-19:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.34 0.00 01-JAN-00:15 425.64 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 20.02 0.00 01-JAN-02:15 1994.19 19-JUN-19:00
EnergyTransfer:Zone:F3 S1 APARTMENT 29.87 0.15 22-MAR-09:45 2531.09 28-DEC-11:15
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.10 0.00 01-JAN-00:15 169.87 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 29.77 0.00 02-JAN-10:30 2531.09 28-DEC-11:15
EnergyTransfer:Zone:F3 S2 APARTMENT 29.92 0.07 17-JAN-09:45 2539.76 28-DEC-11:15
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.10 0.00 01-JAN-00:15 171.44 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 29.82 0.00 02-JAN-10:30 2539.76 28-DEC-11:15
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 36.57 0.00 13-OCT-00:15 3883.69 01-NOV-15:15
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.46 0.00 01-JAN-00:15 452.80 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 36.10 0.00 02-JAN-10:30 3883.69 01-NOV-15:15
EnergyTransfer:Zone:F4 NW APARTMENT 27.79 0.01 07-NOV-03:15 3647.56 22-JUL-17:30
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 1.22 0.00 01-JAN-16:15 807.25 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 26.57 0.00 01-JAN-00:15 3647.56 22-JUL-17:30
EnergyTransfer:Zone:F4 SE APARTMENT 37.32 0.05 09-JAN-01:15 3302.33 09-OCT-10:45
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.30 0.00 01-JAN-00:15 344.94 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 37.02 0.00 02-JAN-18:15 3302.33 09-OCT-10:45
EnergyTransfer:Zone:F4 NE APARTMENT 28.18 0.01 21-NOV-02:00 2977.29 28-JUN-08:30
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.82 0.00 01-JAN-08:30 814.34 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 27.36 0.00 01-JAN-00:15 2977.29 28-JUN-08:30
EnergyTransfer:Zone:F4 N1 APARTMENT 20.74 0.05 28-OCT-12:00 2015.50 19-JUN-19:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.33 0.00 01-JAN-00:15 409.64 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 20.41 0.00 01-JAN-04:15 2015.50 19-JUN-19:00
EnergyTransfer:Zone:F4 N2 APARTMENT 20.77 0.00 08-JAN-12:45 2006.63 19-JUN-19:00
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.33 0.00 01-JAN-00:15 413.73 07-DEC-16:00
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 20.43 0.00 01-JAN-03:45 2006.63 19-JUN-19:00
EnergyTransfer:Zone:F4 S1 APARTMENT 30.29 0.45 30-MAR-10:45 2575.58 28-DEC-11:15
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.11 0.00 01-JAN-00:15 176.82 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 30.18 0.00 02-JAN-10:30 2575.58 28-DEC-11:15
EnergyTransfer:Zone:F4 S2 APARTMENT 30.32 0.03 22-NOV-12:30 2583.14 28-DEC-11:15
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.11 0.00 01-JAN-00:15 178.71 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 30.21 0.00 02-JAN-10:30 2583.14 28-DEC-11:15
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 37.03 0.00 12-DEC-13:45 3912.03 01-NOV-15:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.48 0.00 01-JAN-00:15 471.05 08-MAR-09:45
Cooling:EnergyTransfer:Zone:M SW APARTMENT 36.55 0.00 02-JAN-10:30 3912.03 01-NOV-15:15
EnergyTransfer:Zone:M NW APARTMENT 28.35 0.00 26-JAN-04:00 3690.32 22-JUL-17:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 1.24 0.00 01-JAN-16:15 814.71 07-DEC-05:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 27.11 0.00 01-JAN-00:15 3690.32 22-JUL-17:30
EnergyTransfer:Zone:M SE APARTMENT 37.79 0.00 09-JAN-00:30 3337.08 09-OCT-10:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.32 0.00 01-JAN-00:15 366.38 08-MAR-09:45
Cooling:EnergyTransfer:Zone:M SE APARTMENT 37.47 0.00 02-JAN-18:15 3337.08 09-OCT-10:45
EnergyTransfer:Zone:M NE APARTMENT 28.75 0.01 15-NOV-02:15 3007.56 28-JUN-08:30
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.84 0.00 01-JAN-08:30 823.56 07-DEC-05:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 27.91 0.00 01-JAN-00:15 3007.56 28-JUN-08:30
EnergyTransfer:Zone:M N1 APARTMENT 21.37 0.26 16-DEC-14:30 2053.43 19-JUN-19:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.35 0.00 01-JAN-00:15 400.77 07-DEC-16:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 21.02 0.00 01-JAN-04:45 2053.43 19-JUN-19:00
EnergyTransfer:Zone:M N2 APARTMENT 21.39 0.02 02-JAN-10:15 2044.79 19-JUN-19:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.34 0.00 01-JAN-00:15 405.01 07-DEC-16:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 21.05 0.00 01-JAN-04:15 2044.79 19-JUN-19:00
EnergyTransfer:Zone:M S1 APARTMENT 30.91 0.74 28-JAN-09:15 2606.40 28-DEC-11:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.12 0.00 01-JAN-00:15 191.60 08-MAR-09:45
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 30.79 0.00 02-JAN-10:30 2606.40 28-DEC-11:15
EnergyTransfer:Zone:M S2 APARTMENT 30.94 0.52 22-NOV-14:00 2613.78 28-DEC-11:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.12 0.00 01-JAN-00:15 193.62 08-MAR-09:45
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 30.82 0.00 02-JAN-10:30 2613.78 28-DEC-11:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 35.98 0.01 14-FEB-01:30 3872.98 01-NOV-15:15
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.54 0.00 01-JAN-00:15 497.78 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 35.44 0.00 02-JAN-10:30 3872.98 01-NOV-15:15
EnergyTransfer:Zone:F6 NW APARTMENT 27.73 0.02 15-FEB-05:45 3653.16 22-JUL-17:30
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 1.35 0.00 01-JAN-16:30 872.12 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 26.38 0.00 01-JAN-00:15 3653.16 22-JUL-17:30
EnergyTransfer:Zone:F6 SE APARTMENT 36.71 0.00 19-FEB-10:15 3290.28 09-OCT-10:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.36 0.00 01-JAN-00:15 393.23 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 36.35 0.00 02-JAN-10:30 3290.28 09-OCT-10:45
EnergyTransfer:Zone:F6 NE APARTMENT 28.09 0.01 10-NOV-05:30 2965.41 28-JUN-08:30
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.92 0.00 01-JAN-08:30 879.76 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 27.17 0.00 01-JAN-00:15 2965.41 28-JUN-08:30
EnergyTransfer:Zone:F6 N1 APARTMENT 20.73 0.55 07-DEC-13:15 2019.55 19-JUN-19:00
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.38 0.00 01-JAN-00:15 492.94 03-FEB-13:45
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 20.35 0.00 01-JAN-01:45 2019.55 19-JUN-19:00
EnergyTransfer:Zone:F6 N2 APARTMENT 20.75 0.01 03-MAR-14:45 2011.17 19-JUN-19:00
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.38 0.00 01-JAN-00:15 498.86 03-FEB-13:45
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 20.37 0.00 01-JAN-01:15 2011.17 19-JUN-19:00
EnergyTransfer:Zone:F6 S1 APARTMENT 29.84 0.12 29-MAR-17:30 2556.80 28-DEC-11:15
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.13 0.00 01-JAN-00:15 209.90 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 29.71 0.00 02-JAN-10:30 2556.80 28-DEC-11:15
EnergyTransfer:Zone:F6 S2 APARTMENT 29.87 0.04 16-NOV-15:45 2563.96 28-DEC-11:15
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.13 0.00 01-JAN-00:15 212.44 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 29.74 0.00 02-JAN-10:30 2563.96 28-DEC-11:15
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 35.43 0.01 18-JAN-01:00 3856.83 01-NOV-15:15
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.58 0.00 01-JAN-00:15 510.78 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 34.84 0.00 02-JAN-10:30 3856.83 01-NOV-15:15
EnergyTransfer:Zone:F7 NW APARTMENT 27.53 0.01 22-NOV-23:15 3638.20 22-JUL-17:45
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 1.46 0.00 01-JAN-16:30 916.77 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 26.08 0.00 01-JAN-00:15 3638.20 22-JUL-17:45
EnergyTransfer:Zone:F7 SE APARTMENT 36.15 0.00 03-FEB-23:30 3266.59 09-OCT-10:45
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.39 0.00 01-JAN-00:15 410.38 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 35.76 0.00 02-JAN-10:30 3266.59 09-OCT-10:45
EnergyTransfer:Zone:F7 NE APARTMENT 27.86 0.00 02-DEC-23:00 2952.89 28-JUN-08:30
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 1.00 0.00 01-JAN-08:30 923.52 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 26.86 0.00 01-JAN-00:15 2952.89 28-JUN-08:30
EnergyTransfer:Zone:F7 N1 APARTMENT 20.49 0.06 23-OCT-12:45 2013.43 22-JUL-17:30
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.42 0.00 01-JAN-00:15 661.75 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 20.07 0.00 01-JAN-01:00 2013.43 22-JUL-17:30
EnergyTransfer:Zone:F7 N2 APARTMENT 20.52 0.18 01-JAN-07:00 2005.38 22-JUL-17:30
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.42 0.00 01-JAN-00:15 664.61 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 20.10 0.00 01-JAN-01:00 2005.38 22-JUL-17:30
EnergyTransfer:Zone:F7 S1 APARTMENT 29.31 0.52 22-MAR-10:15 2525.95 28-DEC-11:15
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.14 0.00 01-JAN-00:15 238.91 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 29.17 0.00 02-JAN-10:30 2525.95 28-DEC-11:15
EnergyTransfer:Zone:F7 S2 APARTMENT 29.34 0.16 15-NOV-18:30 2532.92 28-DEC-11:15
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.14 0.00 01-JAN-00:15 233.49 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 29.20 0.00 02-JAN-10:30 2532.92 28-DEC-11:15
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 35.10 0.02 05-JAN-04:00 3855.78 01-NOV-15:15
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.63 0.00 01-JAN-00:15 517.59 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 34.47 0.00 01-JAN-05:15 3855.78 01-NOV-15:15
EnergyTransfer:Zone:F8 NW APARTMENT 27.56 0.05 09-FEB-03:00 3640.56 22-JUL-17:45
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 1.57 0.00 01-JAN-22:45 962.23 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 25.99 0.00 01-JAN-00:15 3640.56 22-JUL-17:45
EnergyTransfer:Zone:F8 SE APARTMENT 35.81 0.00 22-FEB-23:45 3270.61 05-OCT-09:15
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.43 0.00 01-JAN-00:15 506.20 10-FEB-12:30
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 35.38 0.00 01-JAN-04:45 3270.61 05-OCT-09:15
EnergyTransfer:Zone:F8 NE APARTMENT 27.85 0.00 22-OCT-22:15 2956.77 28-JUN-08:30
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 1.09 0.00 01-JAN-08:45 992.38 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 26.76 0.00 01-JAN-00:15 2956.77 28-JUN-08:30
EnergyTransfer:Zone:F8 N1 APARTMENT 20.46 0.02 20-NOV-02:45 2028.79 22-JUL-17:45
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.47 0.00 01-JAN-00:15 836.29 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 20.00 0.00 01-JAN-00:45 2028.79 22-JUL-17:45
EnergyTransfer:Zone:F8 N2 APARTMENT 20.49 0.01 10-FEB-03:30 2021.02 22-JUL-17:45
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.46 0.00 01-JAN-00:15 838.61 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 20.02 0.00 01-JAN-00:30 2021.02 22-JUL-17:45
EnergyTransfer:Zone:F8 S1 APARTMENT 29.00 0.16 14-FEB-16:30 2491.13 28-DEC-11:15
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.16 0.00 01-JAN-00:15 380.11 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 28.83 0.00 02-JAN-10:30 2491.13 28-DEC-11:15
EnergyTransfer:Zone:F8 S2 APARTMENT 29.03 0.09 25-NOV-14:00 2497.94 28-DEC-11:15
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.16 0.00 01-JAN-00:15 411.30 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 28.86 0.00 02-JAN-10:30 2497.94 28-DEC-11:15
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 35.28 0.01 07-DEC-01:30 3936.46 01-NOV-15:15
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.77 0.00 01-JAN-00:15 671.06 08-MAR-09:45
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 34.51 0.00 01-JAN-04:15 3936.46 01-NOV-15:15
EnergyTransfer:Zone:F9 NW APARTMENT 28.34 0.01 26-OCT-00:45 3742.59 22-JUL-17:45
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 1.85 0.00 01-JAN-22:45 1053.54 07-DEC-05:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 26.49 0.00 01-JAN-00:15 3742.59 22-JUL-17:45
EnergyTransfer:Zone:F9 SE APARTMENT 35.92 0.01 23-FEB-00:45 3320.78 28-SEP-10:15
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.52 0.00 01-JAN-00:15 668.19 10-FEB-12:30
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 35.41 0.00 01-JAN-03:30 3320.78 28-SEP-10:15
EnergyTransfer:Zone:F9 NE APARTMENT 28.46 0.01 09-JAN-21:15 3009.60 28-JUN-08:30
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 1.27 0.00 01-JAN-09:00 1180.60 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 27.19 0.00 01-JAN-00:15 3009.60 28-JUN-08:30
EnergyTransfer:Zone:F9 N1 APARTMENT 20.98 0.08 13-NOV-24:00 2128.53 22-JUL-17:45
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.58 0.00 01-JAN-00:15 1068.24 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 20.39 0.00 01-JAN-00:30 2128.53 22-JUL-17:45
EnergyTransfer:Zone:F9 N2 APARTMENT 21.00 0.06 06-FEB-12:30 2120.80 22-JUL-17:45
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.58 0.00 01-JAN-10:30 1067.33 03-FEB-16:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 20.42 0.00 01-JAN-00:15 2120.80 22-JUL-17:45
EnergyTransfer:Zone:F9 S1 APARTMENT 29.06 0.08 09-FEB-12:30 2535.40 02-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.20 0.00 01-JAN-00:15 428.56 10-FEB-12:30
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 28.86 0.00 02-JAN-10:30 2535.40 02-NOV-13:30
EnergyTransfer:Zone:F9 S2 APARTMENT 29.09 0.03 11-FEB-02:00 2541.22 02-NOV-13:30
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.20 0.00 01-JAN-00:15 429.65 10-FEB-12:30
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 28.89 0.00 02-JAN-10:30 2541.22 02-NOV-13:30
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 38.56 0.20 03-MAY-02:45 4595.63 05-OCT-15:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 2.30 0.00 01-JAN-09:00 1435.63 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 36.26 0.00 01-JAN-00:15 4595.63 05-OCT-15:15
EnergyTransfer:Zone:T NW APARTMENT 32.21 0.11 13-DEC-18:15 4403.31 22-JUL-17:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 3.71 0.00 01-JAN-15:30 1734.03 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 28.50 0.00 01-JAN-00:15 4403.31 22-JUL-17:30
EnergyTransfer:Zone:T SE APARTMENT 38.61 0.14 18-MAR-00:30 4010.46 28-SEP-10:45
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.83 0.00 01-JAN-08:30 1450.96 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 36.78 0.00 01-JAN-00:15 4010.46 28-SEP-10:45
EnergyTransfer:Zone:T NE APARTMENT 31.68 0.31 07-JAN-14:30 3526.02 22-JUL-18:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 2.92 0.00 02-JAN-08:30 1750.65 07-DEC-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 28.76 0.00 01-JAN-00:15 3526.02 22-JUL-18:00
EnergyTransfer:Zone:T N1 APARTMENT 22.89 0.01 26-NOV-09:30 2605.11 22-JUL-17:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 1.19 0.00 01-JAN-18:00 1373.03 22-NOV-12:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 21.70 0.00 01-JAN-00:15 2605.11 22-JUL-17:30
EnergyTransfer:Zone:T N2 APARTMENT 22.94 0.02 13-NOV-05:30 2637.39 11-JUL-17:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 1.19 0.00 01-JAN-11:45 1347.82 22-NOV-12:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 21.75 0.00 01-JAN-00:15 2637.39 11-JUL-17:30
EnergyTransfer:Zone:T S1 APARTMENT 30.33 0.01 22-DEC-04:30 3178.49 02-NOV-13:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.58 0.00 01-JAN-00:15 1042.66 10-FEB-12:30
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 29.75 0.00 01-JAN-01:00 3178.49 02-NOV-13:45
EnergyTransfer:Zone:T S2 APARTMENT 30.38 0.01 10-NOV-00:30 3179.01 02-NOV-13:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.58 0.00 01-JAN-00:15 1043.82 10-FEB-12:30
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 29.79 0.00 01-JAN-01:00 3179.01 02-NOV-13:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 683.38 344.92 25-JUL-01:15 85436.27 07-DEC-06:15
WaterSystems:EnergyTransfer 681.08 344.92 25-JUL-01:15 48962.98 20-JAN-07:15
sub cat:WaterSystems:EnergyTransfer 681.08 344.92 25-JUL-01:15 48962.98 20-JAN-07:15
EnergyTransfer:HVAC 2848.56 0.00 02-JAN-18:45 276721.03 13-JUL-18:45
CoolingCoils:EnergyTransfer 2832.45 0.00 01-JAN-00:15 276721.03 13-JUL-18:45
HeatingCoils:EnergyTransfer 16.12 0.00 01-JAN-12:00 59147.91 07-DEC-05:00
PlantLoopHeatingDemand:HVAC 12.42 0.00 01-JAN-12:00 45141.81 07-DEC-05:00
HeatingCoils:PlantLoopHeatingDemand 12.42 0.00 01-JAN-12:00 45141.81 07-DEC-05:00
Boilers:EnergyTransfer 2.30 0.00 01-JAN-00:15 43216.57 07-DEC-05:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.999 -23.654 0.000 0.000 3.646 2.413 12.213 28.355 0.000 0.774 0.001 0.000 -7.554 0.000 -4.468 -12.723
G NW APARTMENT 1.979 -17.784 0.000 0.000 3.693 2.413 12.213 16.925 0.000 0.766 0.000 0.000 -7.587 0.000 -3.695 -8.922
OFFICE 0.570 -30.830 0.000 0.000 0.504 21.954 7.547 28.718 0.000 0.624 0.000 0.000 -7.344 0.000 -0.839 -20.903
G NE APARTMENT 1.490 -18.028 0.000 0.000 3.705 2.413 12.213 17.164 0.000 0.767 0.000 0.000 -7.036 0.000 -3.685 -9.003
G N1 APARTMENT 0.716 -12.476 0.000 0.000 3.709 2.413 12.213 6.660 0.000 0.521 0.000 0.000 -4.555 0.000 -3.012 -6.187
G N2 APARTMENT 0.710 -12.497 0.000 0.000 3.709 2.413 12.213 6.657 0.000 0.520 0.000 0.000 -4.552 0.000 -3.012 -6.162
G S1 APARTMENT 0.167 -18.282 0.000 0.000 3.638 2.413 12.213 18.258 0.000 0.523 0.002 0.000 -4.553 0.000 -4.004 -10.374
G S2 APARTMENT 0.176 -18.535 0.000 0.000 3.636 2.413 12.213 18.248 0.000 0.524 0.001 0.000 -4.560 0.000 -4.027 -10.088
F2 SW APARTMENT 0.535 -34.352 0.000 0.000 3.565 2.413 12.213 27.334 0.000 1.069 1.073 0.000 -8.332 0.000 -5.518 -0.001
F2 NW APARTMENT 1.454 -25.141 0.000 0.000 3.621 2.413 12.213 16.201 0.000 1.057 1.340 0.000 -8.344 0.000 -4.816 -0.000
F2 SE APARTMENT 0.352 -36.376 0.000 0.000 3.567 2.413 12.213 27.856 0.000 1.071 2.538 0.000 -8.078 0.000 -5.555 -0.000
F2 NE APARTMENT 0.950 -25.786 0.000 0.000 3.635 2.413 12.213 16.455 0.000 1.059 1.552 0.000 -7.712 0.000 -4.778 -0.000
F2 N1 APARTMENT 0.412 -18.650 0.000 0.000 3.627 2.413 12.213 6.322 0.000 0.703 2.068 0.000 -5.076 0.000 -4.031 -0.000
F2 N2 APARTMENT 0.407 -18.678 0.000 0.000 3.628 2.413 12.213 6.320 0.000 0.703 2.096 0.000 -5.072 0.000 -4.030 -0.000
F2 S1 APARTMENT 0.114 -27.726 0.000 0.000 3.551 2.413 12.213 17.628 0.000 0.704 1.110 0.000 -5.031 0.000 -4.976 -0.000
F2 S2 APARTMENT 0.116 -27.855 0.000 0.000 3.551 2.413 12.213 17.626 0.000 0.705 1.245 0.000 -5.033 0.000 -4.980 -0.000
F3 SW APARTMENT 0.452 -35.912 0.000 0.000 3.554 2.413 12.213 26.865 0.000 1.244 3.684 0.000 -8.514 0.000 -5.999 -0.000
F3 NW APARTMENT 1.238 -26.281 0.000 0.000 3.604 2.413 12.213 15.901 0.000 1.231 3.578 0.000 -8.570 0.000 -5.327 -0.000
F3 SE APARTMENT 0.293 -36.941 0.000 0.000 3.559 2.413 12.213 27.445 0.000 1.245 3.993 0.000 -8.216 0.000 -6.003 -0.000
F3 NE APARTMENT 0.826 -27.036 0.000 0.000 3.617 2.413 12.213 16.178 0.000 1.232 3.765 0.000 -7.924 0.000 -5.285 -0.000
F3 N1 APARTMENT 0.339 -19.994 0.000 0.000 3.603 2.413 12.213 6.218 0.000 0.812 4.145 0.000 -5.247 0.000 -4.502 -0.000
F3 N2 APARTMENT 0.335 -20.019 0.000 0.000 3.604 2.413 12.213 6.217 0.000 0.812 4.168 0.000 -5.242 0.000 -4.500 -0.000
F3 S1 APARTMENT 0.098 -29.767 0.000 0.000 3.538 2.413 12.213 17.349 0.000 0.813 3.888 0.000 -5.152 0.000 -5.392 -0.000
F3 S2 APARTMENT 0.099 -29.816 0.000 0.000 3.538 2.413 12.213 17.348 0.000 0.813 3.937 0.000 -5.152 0.000 -5.392 -0.000
F4 SW APARTMENT 0.462 -36.103 0.000 0.000 3.553 2.413 12.213 26.549 0.000 1.375 4.463 0.000 -8.591 0.000 -6.335 -0.000
F4 NW APARTMENT 1.220 -26.570 0.000 0.000 3.601 2.413 12.213 15.714 0.000 1.360 4.361 0.000 -8.665 0.000 -5.647 -0.000
F4 SE APARTMENT 0.303 -37.016 0.000 0.000 3.559 2.413 12.213 27.153 0.000 1.376 4.617 0.000 -8.283 0.000 -6.335 -0.000
F4 NE APARTMENT 0.820 -27.356 0.000 0.000 3.614 2.413 12.213 16.007 0.000 1.362 4.545 0.000 -8.013 0.000 -5.604 -0.000
F4 N1 APARTMENT 0.334 -20.410 0.000 0.000 3.596 2.413 12.213 6.163 0.000 0.894 4.897 0.000 -5.322 0.000 -4.777 -0.000
F4 N2 APARTMENT 0.331 -20.434 0.000 0.000 3.597 2.413 12.213 6.162 0.000 0.894 4.919 0.000 -5.318 0.000 -4.775 -0.000
F4 S1 APARTMENT 0.105 -30.180 0.000 0.000 3.536 2.413 12.213 17.165 0.000 0.896 4.719 0.000 -5.204 0.000 -5.662 -0.000
F4 S2 APARTMENT 0.106 -30.212 0.000 0.000 3.536 2.413 12.213 17.164 0.000 0.896 4.750 0.000 -5.203 0.000 -5.663 -0.000
M SW APARTMENT 0.482 -36.551 0.000 0.000 3.552 2.413 12.213 26.287 0.000 1.481 5.408 0.000 -8.658 0.000 -6.628 -0.001
M NW APARTMENT 1.239 -27.110 0.000 0.000 3.599 2.413 12.213 15.559 0.000 1.464 5.283 0.000 -8.740 0.000 -5.919 -0.000
M SE APARTMENT 0.319 -37.466 0.000 0.000 3.558 2.413 12.213 26.907 0.000 1.482 5.549 0.000 -8.348 0.000 -6.627 -0.000
M NE APARTMENT 0.837 -27.913 0.000 0.000 3.611 2.413 12.213 15.863 0.000 1.466 5.469 0.000 -8.084 0.000 -5.876 -0.000
M N1 APARTMENT 0.347 -21.025 0.000 0.000 3.592 2.413 12.213 6.116 0.000 0.959 5.771 0.000 -5.379 0.000 -5.006 0.000
M N2 APARTMENT 0.343 -21.048 0.000 0.000 3.592 2.413 12.213 6.115 0.000 0.959 5.793 0.000 -5.375 0.000 -5.004 0.000
M S1 APARTMENT 0.116 -30.791 0.000 0.000 3.535 2.413 12.213 17.013 0.000 0.963 5.686 0.000 -5.249 0.000 -5.898 -0.000
M S2 APARTMENT 0.117 -30.819 0.000 0.000 3.535 2.413 12.213 17.012 0.000 0.963 5.713 0.000 -5.248 0.000 -5.898 -0.000
F6 SW APARTMENT 0.535 -35.440 0.000 0.000 3.558 2.413 12.213 26.108 0.000 1.594 4.516 0.000 -8.654 0.000 -6.842 -0.000
F6 NW APARTMENT 1.351 -26.380 0.000 0.000 3.607 2.413 12.213 15.474 0.000 1.574 4.521 0.000 -8.713 0.000 -6.061 -0.000
F6 SE APARTMENT 0.357 -36.350 0.000 0.000 3.564 2.413 12.213 26.739 0.000 1.595 4.655 0.000 -8.343 0.000 -6.843 -0.000
F6 NE APARTMENT 0.917 -27.172 0.000 0.000 3.621 2.413 12.213 15.793 0.000 1.576 4.712 0.000 -8.057 0.000 -6.015 -0.000
F6 N1 APARTMENT 0.380 -20.349 0.000 0.000 3.601 2.413 12.213 6.105 0.000 1.036 5.061 0.000 -5.363 0.000 -5.095 -0.000
F6 N2 APARTMENT 0.377 -20.375 0.000 0.000 3.601 2.413 12.213 6.103 0.000 1.036 5.083 0.000 -5.359 0.000 -5.093 -0.000
F6 S1 APARTMENT 0.129 -29.715 0.000 0.000 3.539 2.413 12.213 16.909 0.000 1.041 4.785 0.000 -5.252 0.000 -6.063 -0.001
F6 S2 APARTMENT 0.130 -29.743 0.000 0.000 3.540 2.413 12.213 16.908 0.000 1.041 4.812 0.000 -5.251 0.000 -6.063 -0.000
F7 SW APARTMENT 0.582 -34.844 0.000 0.000 3.562 2.413 12.213 25.940 0.000 1.676 4.160 0.000 -8.663 0.000 -7.039 -0.000
F7 NW APARTMENT 1.456 -26.078 0.000 0.000 3.614 2.413 12.213 15.391 0.000 1.654 4.235 0.000 -8.700 0.000 -6.197 -0.000
F7 SE APARTMENT 0.391 -35.755 0.000 0.000 3.569 2.413 12.213 26.581 0.000 1.677 4.302 0.000 -8.350 0.000 -7.041 -0.000
F7 NE APARTMENT 0.999 -26.861 0.000 0.000 3.628 2.413 12.213 15.721 0.000 1.655 4.427 0.000 -8.045 0.000 -6.150 -0.000
F7 N1 APARTMENT 0.418 -20.074 0.000 0.000 3.608 2.413 12.213 6.089 0.000 1.087 4.788 0.000 -5.355 0.000 -5.186 -0.000
F7 N2 APARTMENT 0.416 -20.102 0.000 0.000 3.608 2.413 12.213 6.087 0.000 1.087 4.812 0.000 -5.351 0.000 -5.183 -0.000
F7 S1 APARTMENT 0.144 -29.167 0.000 0.000 3.543 2.413 12.213 16.812 0.000 1.094 4.425 0.000 -5.262 0.000 -6.214 -0.000
F7 S2 APARTMENT 0.145 -29.196 0.000 0.000 3.543 2.413 12.213 16.811 0.000 1.094 4.452 0.000 -5.261 0.000 -6.214 -0.000
F8 SW APARTMENT 0.634 -34.467 0.000 0.000 3.566 2.413 12.213 25.788 0.000 1.745 4.007 0.000 -8.673 0.000 -7.226 -0.000
F8 NW APARTMENT 1.575 -25.987 0.000 0.000 3.621 2.413 12.213 15.314 0.000 1.722 4.151 0.000 -8.693 0.000 -6.328 -0.000
F8 SE APARTMENT 0.430 -35.382 0.000 0.000 3.573 2.413 12.213 26.436 0.000 1.746 4.157 0.000 -8.359 0.000 -7.227 -0.000
F8 NE APARTMENT 1.091 -26.757 0.000 0.000 3.634 2.413 12.213 15.651 0.000 1.723 4.350 0.000 -8.038 0.000 -6.281 -0.000
F8 N1 APARTMENT 0.466 -19.996 0.000 0.000 3.614 2.413 12.213 6.072 0.000 1.129 4.713 0.000 -5.349 0.000 -5.274 -0.000
F8 N2 APARTMENT 0.464 -20.024 0.000 0.000 3.615 2.413 12.213 6.070 0.000 1.129 4.737 0.000 -5.345 0.000 -5.272 -0.000
F8 S1 APARTMENT 0.162 -28.834 0.000 0.000 3.546 2.413 12.213 16.724 0.000 1.139 4.267 0.000 -5.272 0.000 -6.358 -0.000
F8 S2 APARTMENT 0.163 -28.863 0.000 0.000 3.546 2.413 12.213 16.723 0.000 1.139 4.294 0.000 -5.270 0.000 -6.358 -0.000
F9 SW APARTMENT 0.772 -34.510 0.000 0.000 3.572 2.413 12.213 25.655 0.000 1.809 4.123 0.000 -8.665 0.000 -7.381 -0.000
F9 NW APARTMENT 1.853 -26.487 0.000 0.000 3.628 2.413 12.213 15.241 0.000 1.783 4.453 0.000 -8.675 0.000 -6.422 -0.000
F9 SE APARTMENT 0.518 -35.406 0.000 0.000 3.580 2.413 12.213 26.307 0.000 1.809 4.298 0.000 -8.348 0.000 -7.383 -0.000
F9 NE APARTMENT 1.269 -27.188 0.000 0.000 3.641 2.413 12.213 15.587 0.000 1.784 4.684 0.000 -8.024 0.000 -6.379 -0.000
F9 N1 APARTMENT 0.581 -20.394 0.000 0.000 3.622 2.413 12.213 6.054 0.000 1.168 5.004 0.000 -5.332 0.000 -5.327 -0.000
F9 N2 APARTMENT 0.577 -20.421 0.000 0.000 3.623 2.413 12.213 6.052 0.000 1.168 5.029 0.000 -5.328 0.000 -5.326 -0.000
F9 S1 APARTMENT 0.202 -28.855 0.000 0.000 3.553 2.413 12.213 16.650 0.000 1.182 4.377 0.000 -5.269 0.000 -6.466 -0.000
F9 S2 APARTMENT 0.203 -28.887 0.000 0.000 3.553 2.413 12.213 16.649 0.000 1.182 4.408 0.000 -5.267 0.000 -6.467 -0.000
T SW APARTMENT 2.298 -36.264 0.000 0.000 3.622 2.413 12.213 25.235 0.000 1.865 4.198 0.000 -8.211 0.000 -7.369 -0.000
T NW APARTMENT 3.707 -28.498 0.000 0.000 3.658 2.413 12.213 14.870 0.000 1.839 4.632 0.000 -8.299 0.000 -6.536 -0.000
T SE APARTMENT 1.825 -36.780 0.000 0.000 3.631 2.413 12.213 25.911 0.000 1.867 4.230 0.000 -7.917 0.000 -7.393 -0.000
T NE APARTMENT 2.917 -28.759 0.000 0.000 3.672 2.413 12.213 15.275 0.000 1.840 4.667 0.000 -7.708 0.000 -6.531 -0.000
T N1 APARTMENT 1.192 -21.696 0.000 0.000 3.657 2.413 12.213 5.920 0.000 1.202 5.574 0.000 -5.084 0.000 -5.391 -0.000
T N2 APARTMENT 1.188 -21.751 0.000 0.000 3.658 2.413 12.213 5.918 0.000 1.203 5.630 0.000 -5.078 0.000 -5.393 -0.000
T S1 APARTMENT 0.581 -29.752 0.000 0.000 3.603 2.413 12.213 16.437 0.000 1.223 4.756 0.000 -5.031 0.000 -6.443 -0.000
T S2 APARTMENT 0.584 -29.792 0.000 0.000 3.603 2.413 12.213 16.434 0.000 1.224 4.794 0.000 -5.028 0.000 -6.445 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 6.578 0.000 10.904 0.001 0.000 -1.778 0.000 -18.342 -15.891
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 3.071 0.000 0.101 0.000 0.000 -1.110 0.000 -0.255 -20.336
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.989 0.000 0.118 0.000 0.000 -1.156 0.000 -0.316 -20.165
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.934 0.000 0.129 0.000 0.000 -1.180 0.000 -0.360 -20.051
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 37.059 0.000 2.847 0.000 0.125 0.000 0.000 -1.241 0.000 -0.422 -38.368
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.878 0.000 0.149 0.000 0.000 -1.190 0.000 -0.418 -19.947
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.868 0.000 0.159 0.000 0.000 -1.181 0.000 -0.436 -19.938
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.850 0.000 0.166 0.000 0.000 -1.180 0.000 -0.455 -19.910
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 0.000 2.831 0.000 0.169 0.000 0.000 -1.183 0.000 -0.472 -19.874
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 18.529 7.937 2.700 0.000 0.128 0.000 0.000 -1.159 0.000 -0.506 -27.629
Total Facility 56.285 -2176.771 0.000 0.000 284.665 416.414 980.287 1348.281 0.000 108.363 309.406 0.000 -548.715 0.000 -471.740 -306.482


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 01-NOV-15:15 0.00 -3278.66 0.00 0.00 48.90 100.83 470.89 4754.22 0.00 26.95 0.00 0.00 0.00 0.00 0.00 -2123.13
G NW APARTMENT 28-JUN-17:20 0.00 -3171.05 0.00 0.00 132.85 194.45 588.62 3748.57 0.00 145.30 0.00 0.00 0.00 0.00 0.00 -1638.74
OFFICE 28-SEP-10:00 0.00 -3820.23 0.00 0.00 64.91 1622.33 544.91 4267.99 0.00 33.99 0.00 0.00 0.00 0.00 0.00 -2713.90
G NE APARTMENT 28-JUN-08:45 0.00 -2518.00 0.00 0.00 40.75 28.81 394.37 2976.70 0.00 57.09 0.00 0.00 0.00 0.00 0.00 -979.72
G N1 APARTMENT 19-JUN-19:00 0.00 -1684.17 0.00 0.00 140.06 230.46 547.42 854.74 0.00 85.55 0.00 0.00 0.00 0.00 0.00 -174.05
G N2 APARTMENT 19-JUN-19:00 0.00 -1671.77 0.00 0.00 140.04 230.46 547.42 854.97 0.00 85.53 0.00 0.00 0.00 0.00 0.00 -186.66
G S1 APARTMENT 02-NOV-13:30 0.00 -2008.88 0.00 0.00 40.75 28.81 382.60 3196.72 0.00 272.34 0.00 0.00 0.00 0.00 0.00 -1912.34
G S2 APARTMENT 02-NOV-13:30 0.00 -2059.25 0.00 0.00 40.75 28.81 382.60 3195.74 0.00 274.34 0.00 0.00 0.00 0.00 0.00 -1862.99
F2 SW APARTMENT 01-NOV-15:15 0.00 -3875.82 0.00 0.00 48.04 100.83 470.89 4614.66 0.00 35.68 0.00 0.00 0.00 0.00 0.00 -1394.28
F2 NW APARTMENT 22-JUL-17:20 0.00 -3639.01 0.00 0.00 139.62 194.45 588.62 3116.58 0.00 349.07 0.00 0.00 0.00 0.00 0.00 -749.32
F2 SE APARTMENT 28-SEP-10:15 0.00 -3467.00 0.00 0.00 40.42 28.81 412.03 4230.44 0.00 49.48 0.00 0.00 0.00 0.00 0.00 -1294.18
F2 NE APARTMENT 28-JUN-08:30 0.00 -2970.80 0.00 0.00 40.75 28.81 394.37 2922.20 0.00 101.24 0.00 0.00 0.00 0.00 0.00 -516.57
F2 N1 APARTMENT 20-JUN-18:45 0.00 -1995.17 0.00 0.00 141.15 230.46 547.42 906.93 0.00 114.23 55.00 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 20-JUN-18:45 0.00 -1985.80 0.00 0.00 141.13 230.46 547.42 907.05 0.00 114.21 45.53 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 02-NOV-13:30 0.00 -2426.79 0.00 0.00 40.50 28.81 382.60 3018.51 0.00 305.30 0.00 0.00 0.00 0.00 0.00 -1348.93
F2 S2 APARTMENT 02-NOV-13:30 0.00 -2444.43 0.00 0.00 40.52 28.81 382.60 3018.52 0.00 307.24 0.00 0.00 0.00 0.00 0.00 -1333.26
F3 SW APARTMENT 01-NOV-15:15 0.00 -3880.07 0.00 0.00 47.79 100.83 470.89 4537.47 0.00 41.26 0.00 0.00 0.00 0.00 0.00 -1318.18
F3 NW APARTMENT 22-JUL-17:20 0.00 -3642.48 0.00 0.00 139.60 194.45 588.62 3042.14 0.00 412.54 0.00 0.00 0.00 0.00 0.00 -734.87
F3 SE APARTMENT 09-OCT-10:45 0.00 -3303.82 0.00 0.00 40.75 28.81 412.03 3702.84 0.00 226.13 0.00 0.00 0.00 0.00 0.00 -1106.74
F3 NE APARTMENT 28-JUN-08:30 0.00 -2975.31 0.00 0.00 40.74 28.81 394.37 2882.04 0.00 119.42 0.00 0.00 0.00 0.00 0.00 -490.07
F3 N1 APARTMENT 20-JUN-18:45 0.00 -2003.37 0.00 0.00 140.84 230.46 547.42 894.67 0.00 134.38 55.60 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 20-JUN-18:45 0.00 -1994.30 0.00 0.00 140.82 230.46 547.42 894.78 0.00 134.36 46.46 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 28-DEC-11:15 0.00 -2531.24 0.00 0.00 40.75 28.81 412.03 3318.75 0.00 0.00 0.00 0.00 0.00 0.00 -14.14 -1254.96
F3 S2 APARTMENT 28-DEC-11:15 0.00 -2539.91 0.00 0.00 40.75 28.81 412.03 3318.61 0.00 0.00 0.00 0.00 0.00 0.00 -14.14 -1246.16
F4 SW APARTMENT 01-NOV-15:15 0.00 -3883.71 0.00 0.00 47.86 100.83 470.89 4483.48 0.00 46.15 0.00 0.00 0.00 0.00 0.00 -1265.49
F4 NW APARTMENT 22-JUL-17:20 0.00 -3661.43 0.00 0.00 139.63 194.45 588.62 2990.59 0.00 460.45 0.00 0.00 0.00 0.00 0.00 -712.31
F4 SE APARTMENT 09-OCT-10:45 0.00 -3302.45 0.00 0.00 40.75 28.81 412.03 3669.19 0.00 235.71 0.00 0.00 0.00 0.00 0.00 -1084.04
F4 NE APARTMENT 28-JUN-08:30 0.00 -2977.55 0.00 0.00 40.74 28.81 394.37 2851.93 0.00 133.15 0.00 0.00 0.00 0.00 0.00 -471.45
F4 N1 APARTMENT 19-JUN-19:00 0.00 -2015.50 0.00 0.00 139.07 230.46 547.42 822.36 0.00 159.63 116.56 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 19-JUN-19:00 0.00 -2006.62 0.00 0.00 139.02 230.46 547.42 822.31 0.00 159.55 107.87 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 28-DEC-11:15 0.00 -2575.74 0.00 0.00 40.75 28.81 412.03 3311.91 0.00 0.00 0.00 0.00 0.00 0.00 -15.84 -1201.93
F4 S2 APARTMENT 28-DEC-11:15 0.00 -2583.30 0.00 0.00 40.75 28.81 412.03 3311.79 0.00 0.00 0.00 0.00 0.00 0.00 -15.84 -1194.24
M SW APARTMENT 01-NOV-15:15 0.00 -3912.04 0.00 0.00 47.97 100.83 470.89 4439.50 0.00 50.38 0.00 0.00 0.00 0.00 0.00 -1197.54
M NW APARTMENT 22-JUL-17:20 0.00 -3699.21 0.00 0.00 139.54 194.45 588.62 2949.63 0.00 499.32 0.00 0.00 0.00 0.00 0.00 -672.35
M SE APARTMENT 09-OCT-10:45 0.00 -3337.21 0.00 0.00 40.75 28.81 412.03 3640.66 0.00 245.32 0.00 0.00 0.00 0.00 0.00 -1030.36
M NE APARTMENT 28-JUN-08:30 0.00 -3007.81 0.00 0.00 40.74 28.81 394.37 2826.47 0.00 144.39 0.00 0.00 0.00 0.00 0.00 -426.96
M N1 APARTMENT 19-JUN-19:00 0.00 -2053.42 0.00 0.00 138.99 230.46 547.42 817.82 0.00 172.96 145.76 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 19-JUN-19:00 0.00 -2044.77 0.00 0.00 138.93 230.46 547.42 817.72 0.00 172.86 137.40 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 28-DEC-11:15 0.00 -2606.57 0.00 0.00 40.75 28.81 412.03 3305.94 0.00 0.00 0.00 0.00 0.00 0.00 -17.25 -1163.71
M S2 APARTMENT 28-DEC-11:15 0.00 -2613.95 0.00 0.00 40.75 28.81 412.03 3305.82 0.00 0.00 0.00 0.00 0.00 0.00 -17.25 -1156.22
F6 SW APARTMENT 01-NOV-15:15 0.00 -3872.97 0.00 0.00 48.09 100.83 470.89 4403.88 0.00 54.08 0.00 0.00 0.00 0.00 0.00 -1204.80
F6 NW APARTMENT 22-JUL-17:20 0.00 -3655.35 0.00 0.00 139.31 194.45 588.62 2917.36 0.00 531.76 0.00 0.00 0.00 0.00 0.00 -716.15
F6 SE APARTMENT 09-OCT-10:45 0.00 -3290.41 0.00 0.00 40.75 28.81 412.03 3617.93 0.00 252.41 0.00 0.00 0.00 0.00 0.00 -1061.53
F6 NE APARTMENT 28-JUN-08:30 0.00 -2965.66 0.00 0.00 40.73 28.81 394.37 2806.31 0.00 153.84 0.00 0.00 0.00 0.00 0.00 -458.40
F6 N1 APARTMENT 22-JUL-17:20 0.00 -2021.30 0.00 0.00 139.11 194.45 588.62 972.06 0.00 320.22 0.00 0.00 0.00 0.00 0.00 -193.16
F6 N2 APARTMENT 22-JUL-17:20 0.00 -2013.30 0.00 0.00 139.05 194.45 588.62 971.97 0.00 320.09 0.00 0.00 0.00 0.00 0.00 -200.88
F6 S1 APARTMENT 28-DEC-11:15 0.00 -2556.97 0.00 0.00 40.75 28.81 412.03 3302.04 0.00 0.00 0.00 0.00 0.00 0.00 -18.47 -1208.20
F6 S2 APARTMENT 28-DEC-11:15 0.00 -2564.13 0.00 0.00 40.75 28.81 412.03 3301.92 0.00 0.00 0.00 0.00 0.00 0.00 -18.47 -1200.92
F7 SW APARTMENT 01-NOV-15:15 0.00 -3856.81 0.00 0.00 48.19 100.83 470.89 4371.96 0.00 57.35 0.00 0.00 0.00 0.00 0.00 -1192.42
F7 NW APARTMENT 22-JUL-17:20 0.00 -3640.11 0.00 0.00 139.14 194.45 588.62 2889.52 0.00 560.28 0.00 0.00 0.00 0.00 0.00 -731.90
F7 SE APARTMENT 09-OCT-10:45 0.00 -3266.72 0.00 0.00 40.75 28.81 412.03 3597.08 0.00 258.40 0.00 0.00 0.00 0.00 0.00 -1070.35
F7 NE APARTMENT 28-JUN-08:30 0.00 -2953.13 0.00 0.00 40.73 28.81 394.37 2788.05 0.00 162.20 0.00 0.00 0.00 0.00 0.00 -461.03
F7 N1 APARTMENT 22-JUL-17:20 0.00 -2018.05 0.00 0.00 138.92 194.45 588.62 967.79 0.00 337.41 0.00 0.00 0.00 0.00 0.00 -209.14
F7 N2 APARTMENT 22-JUL-17:20 0.00 -2009.36 0.00 0.00 138.86 194.45 588.62 967.67 0.00 337.25 0.00 0.00 0.00 0.00 0.00 -217.48
F7 S1 APARTMENT 28-DEC-11:15 0.00 -2526.12 0.00 0.00 40.75 28.81 412.03 3298.06 0.00 0.00 0.00 0.00 0.00 0.00 -19.56 -1233.97
F7 S2 APARTMENT 28-DEC-11:15 0.00 -2533.09 0.00 0.00 40.75 28.81 412.03 3297.95 0.00 0.00 0.00 0.00 0.00 0.00 -19.56 -1226.89
F8 SW APARTMENT 01-NOV-15:15 0.00 -3855.74 0.00 0.00 48.33 100.83 470.89 4343.84 0.00 60.49 0.00 0.00 0.00 0.00 0.00 -1168.64
F8 NW APARTMENT 22-JUL-17:20 0.00 -3642.40 0.00 0.00 139.00 194.45 588.62 2864.96 0.00 585.88 0.00 0.00 0.00 0.00 0.00 -730.51
F8 SE APARTMENT 05-OCT-09:15 0.00 -3270.90 0.00 0.00 40.68 28.81 406.15 3958.24 0.00 229.25 0.00 0.00 0.00 0.00 0.00 -1392.23
F8 NE APARTMENT 28-JUN-08:30 0.00 -2956.99 0.00 0.00 40.72 28.81 394.37 2771.16 0.00 169.67 0.00 0.00 0.00 0.00 0.00 -447.73
F8 N1 APARTMENT 22-JUL-17:45 0.00 -2029.07 0.00 0.00 138.09 194.45 588.62 990.06 0.00 359.37 0.00 0.00 0.00 0.00 0.00 -241.52
F8 N2 APARTMENT 22-JUL-17:45 0.00 -2021.31 0.00 0.00 138.03 194.45 588.62 989.99 0.00 359.25 0.00 0.00 0.00 0.00 0.00 -249.03
F8 S1 APARTMENT 28-DEC-11:15 0.00 -2491.31 0.00 0.00 40.75 28.81 412.03 3294.46 0.00 0.00 0.00 0.00 0.00 0.00 -20.55 -1264.20
F8 S2 APARTMENT 28-DEC-11:15 0.00 -2498.12 0.00 0.00 40.75 28.81 412.03 3294.36 0.00 0.00 0.00 0.00 0.00 0.00 -20.55 -1257.28
F9 SW APARTMENT 01-NOV-15:15 0.00 -3936.37 0.00 0.00 48.64 100.83 470.89 4320.15 0.00 64.32 0.00 0.00 0.00 0.00 0.00 -1068.46
F9 NW APARTMENT 22-JUL-17:20 0.00 -3744.25 0.00 0.00 139.08 194.45 588.62 2840.88 0.00 610.09 0.00 0.00 0.00 0.00 0.00 -628.87
F9 SE APARTMENT 28-SEP-10:15 0.00 -3321.49 0.00 0.00 40.56 28.81 412.03 4012.11 0.00 86.66 0.00 0.00 0.00 0.00 0.00 -1258.68
F9 NE APARTMENT 28-JUN-08:30 0.00 -3009.82 0.00 0.00 40.74 28.81 394.37 2754.62 0.00 176.63 0.00 0.00 0.00 0.00 0.00 -385.35
F9 N1 APARTMENT 22-JUL-17:45 0.00 -2128.82 0.00 0.00 138.30 194.45 588.62 985.03 0.00 374.65 0.00 0.00 0.00 0.00 0.00 -152.22
F9 N2 APARTMENT 22-JUL-17:45 0.00 -2121.09 0.00 0.00 138.25 194.45 588.62 984.96 0.00 374.52 0.00 0.00 0.00 0.00 0.00 -159.71
F9 S1 APARTMENT 02-NOV-13:30 0.00 -2534.75 0.00 0.00 40.71 28.81 382.60 2666.37 0.00 494.71 0.00 0.00 0.00 0.00 0.00 -1078.45
F9 S2 APARTMENT 02-NOV-13:30 0.00 -2540.56 0.00 0.00 40.71 28.81 382.60 2666.38 0.00 495.74 0.00 0.00 0.00 0.00 0.00 -1073.68
T SW APARTMENT 05-OCT-15:15 0.00 -4595.46 0.00 0.00 47.31 100.83 470.89 4324.64 0.00 39.37 0.00 0.00 0.00 0.00 0.00 -387.58
T NW APARTMENT 22-JUL-17:30 0.00 -4404.37 0.00 0.00 141.01 194.45 588.62 2792.21 0.00 639.79 48.29 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 28-SEP-10:45 0.00 -4010.79 0.00 0.00 40.55 28.81 412.03 4022.74 0.00 88.63 0.00 0.00 0.00 0.00 0.00 -581.96
T NE APARTMENT 22-JUL-18:00 0.00 -3526.45 0.00 0.00 141.22 194.45 588.62 1397.75 0.00 676.07 528.34 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 22-JUL-17:20 0.00 -2615.15 0.00 0.00 140.00 194.45 588.62 942.95 0.00 383.95 365.18 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 11-JUL-17:30 0.00 -2638.79 0.00 0.00 139.95 194.45 588.62 965.83 0.00 292.66 457.28 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 02-NOV-13:45 0.00 -3177.70 0.00 0.00 40.75 28.81 382.60 2521.22 0.00 623.40 0.00 0.00 0.00 0.00 0.00 -419.07
T S2 APARTMENT 02-NOV-13:45 0.00 -3178.22 0.00 0.00 40.75 28.81 382.60 2521.17 0.00 623.40 0.00 0.00 0.00 0.00 0.00 -418.50
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-JUL-17:20 0.00 -215965.55 0.00 0.00 11107.29 22204.40 47141.46 118819.00 0.00 34012.10 0.00 0.00 0.00 0.00 0.00 -17318.71


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 07-DEC-05:00 680.70 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 360.56 0.00 -1347.99 0.00 -149.82 0.00
G NW APARTMENT 07-DEC-05:00 941.76 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 86.81 0.00 -1335.30 0.00 -149.82 0.00
OFFICE 07-DEC-06:00 726.33 0.00 0.00 0.00 0.00 379.58 128.69 0.00 0.00 0.00 253.65 0.00 -1339.15 0.00 -149.11 0.00
G NE APARTMENT 07-DEC-05:00 951.76 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 70.12 0.00 -1328.61 0.00 -149.82 0.00
G N1 APARTMENT 06-DEC-14:40 903.24 0.00 0.00 0.00 46.31 28.81 382.60 0.00 0.00 0.00 0.00 0.00 -5.16 0.00 -885.37 -470.43
G N2 APARTMENT 06-DEC-14:40 897.32 0.00 0.00 0.00 46.29 28.81 382.60 0.00 0.00 0.00 0.00 0.00 -5.33 0.00 -885.75 -463.94
G S1 APARTMENT 10-FEB-13:45 628.73 0.00 0.00 0.00 44.72 28.81 388.49 45.15 0.00 0.00 0.00 0.00 0.00 0.00 -954.18 -181.72
G S2 APARTMENT 10-FEB-13:45 468.04 0.00 0.00 0.00 44.49 28.81 388.49 42.04 0.00 0.00 0.00 0.00 0.00 0.00 -961.15 -10.72
F2 SW APARTMENT 16-MAR-07:40 439.62 0.00 0.00 0.00 63.57 43.21 388.49 0.00 0.00 0.00 864.37 0.00 -140.13 0.00 -1659.13 0.00
F2 NW APARTMENT 07-DEC-05:00 833.93 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 302.11 0.00 -1377.10 0.00 -215.49 0.00
F2 SE APARTMENT 07-NOV-09:10 379.94 0.00 0.00 0.00 40.75 28.81 394.37 110.31 0.00 0.00 596.00 0.00 0.00 0.00 -1550.18 0.00
F2 NE APARTMENT 07-DEC-05:00 845.69 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 286.19 0.00 -1372.95 0.00 -215.49 0.00
F2 N1 APARTMENT 09-DEC-10:45 677.01 0.00 0.00 0.00 45.37 28.81 406.15 12.95 0.00 0.00 0.00 0.00 0.00 0.00 -928.28 -242.00
F2 N2 APARTMENT 09-DEC-10:45 651.55 0.00 0.00 0.00 45.33 28.81 406.15 12.29 0.00 0.00 0.00 0.00 0.00 0.00 -929.23 -214.89
F2 S1 APARTMENT 08-MAR-09:40 180.88 0.00 0.00 0.00 40.75 28.81 394.37 588.42 0.00 0.00 432.82 0.00 0.00 0.00 -1666.05 0.00
F2 S2 APARTMENT 08-MAR-09:40 184.18 0.00 0.00 0.00 40.75 28.81 394.37 588.18 0.00 0.00 430.33 0.00 0.00 0.00 -1666.62 0.00
F3 SW APARTMENT 08-MAR-09:40 488.65 0.00 0.00 0.00 40.75 28.81 394.37 637.78 0.00 0.00 302.90 0.00 0.00 0.00 -1893.26 0.00
F3 NW APARTMENT 07-DEC-05:00 794.36 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 402.68 0.00 -1398.29 0.00 -255.30 0.00
F3 SE APARTMENT 08-MAR-09:40 361.67 0.00 0.00 0.00 40.75 28.81 394.37 1066.28 0.00 0.00 39.51 0.00 0.00 0.00 -1931.39 0.00
F3 NE APARTMENT 07-DEC-05:00 804.15 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 390.98 0.00 -1396.38 0.00 -255.30 0.00
F3 N1 APARTMENT 09-DEC-10:45 533.13 0.00 0.00 0.00 44.94 28.81 406.15 0.00 0.00 0.00 0.00 0.00 -1.30 0.00 -1002.64 -9.09
F3 N2 APARTMENT 09-DEC-10:45 509.88 0.00 0.00 0.00 44.90 28.81 406.15 0.00 0.00 0.00 15.72 0.00 -1.95 0.00 -1003.50 0.00
F3 S1 APARTMENT 08-MAR-09:40 195.69 0.00 0.00 0.00 40.75 28.81 394.37 536.03 0.00 0.00 620.90 0.00 0.00 0.00 -1816.56 0.00
F3 S2 APARTMENT 08-MAR-09:40 197.36 0.00 0.00 0.00 40.75 28.81 394.37 536.11 0.00 0.00 618.96 0.00 0.00 0.00 -1816.36 0.00
F4 SW APARTMENT 08-MAR-09:40 495.83 0.00 0.00 0.00 40.75 28.81 394.37 599.18 0.00 0.00 465.95 0.00 0.00 0.00 -2024.89 0.00
F4 NW APARTMENT 07-DEC-05:00 807.18 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 433.36 0.00 -1411.55 0.00 -285.55 0.00
F4 SE APARTMENT 08-MAR-09:40 381.22 0.00 0.00 0.00 40.75 28.81 394.37 1009.64 0.00 0.00 190.75 0.00 0.00 0.00 -2045.54 0.00
F4 NE APARTMENT 07-DEC-05:00 814.28 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 426.19 0.00 -1411.48 0.00 -285.55 0.00
F4 N1 APARTMENT 10-FEB-13:45 766.90 0.00 0.00 0.00 43.52 28.81 388.49 0.00 0.00 0.00 13.31 0.00 -35.01 0.00 -1206.01 0.00
F4 N2 APARTMENT 10-FEB-13:45 690.33 0.00 0.00 0.00 43.52 28.81 388.49 0.00 0.00 0.00 91.33 0.00 -35.15 0.00 -1207.32 0.00
F4 S1 APARTMENT 08-MAR-09:40 203.94 0.00 0.00 0.00 40.75 28.81 394.37 503.62 0.00 0.00 768.46 0.00 0.00 0.00 -1939.94 0.00
F4 S2 APARTMENT 08-MAR-09:40 205.98 0.00 0.00 0.00 40.75 28.81 394.37 503.80 0.00 0.00 764.75 0.00 0.00 0.00 -1938.46 0.00
M SW APARTMENT 08-MAR-09:40 516.65 0.00 0.00 0.00 40.75 28.81 394.37 570.19 0.00 0.00 575.98 0.00 0.00 0.00 -2126.75 0.00
M NW APARTMENT 07-DEC-05:00 814.65 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 461.27 0.00 -1421.94 0.00 -310.53 0.00
M SE APARTMENT 08-MAR-09:40 405.45 0.00 0.00 0.00 40.75 28.81 394.37 966.66 0.00 0.00 305.05 0.00 0.00 0.00 -2141.09 0.00
M NE APARTMENT 07-DEC-05:00 823.50 0.00 0.00 0.00 189.67 43.21 223.68 0.00 0.00 0.00 453.94 0.00 -1423.47 0.00 -310.53 0.00
M N1 APARTMENT 11-MAR-16:15 680.35 0.00 0.00 0.00 51.03 100.83 470.89 0.00 0.00 0.00 603.08 0.00 -64.05 0.00 -1842.12 0.00
M N2 APARTMENT 11-MAR-16:15 705.89 0.00 0.00 0.00 51.07 100.83 470.89 0.00 0.00 0.00 576.16 0.00 -63.52 0.00 -1841.32 0.00
M S1 APARTMENT 08-MAR-09:40 220.50 0.00 0.00 0.00 40.75 28.81 394.37 479.48 0.00 0.00 872.82 0.00 0.00 0.00 -2036.73 0.00
M S2 APARTMENT 08-MAR-09:40 222.69 0.00 0.00 0.00 40.75 28.81 394.37 479.69 0.00 0.00 868.53 0.00 0.00 0.00 -2034.84 0.00
F6 SW APARTMENT 08-MAR-09:40 546.19 0.00 0.00 0.00 40.75 28.81 394.37 552.09 0.00 0.00 617.15 0.00 0.00 0.00 -2179.37 0.00
F6 NW APARTMENT 09-DEC-10:45 947.85 0.00 0.00 0.00 45.42 28.81 406.15 0.00 0.00 0.00 0.00 0.00 -10.51 0.00 -1196.67 -221.05
F6 SE APARTMENT 08-MAR-09:40 436.05 0.00 0.00 0.00 40.75 28.81 394.37 937.25 0.00 0.00 352.14 0.00 0.00 0.00 -2189.36 0.00
F6 NE APARTMENT 03-FEB-13:45 1327.59 0.00 0.00 0.00 42.82 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -13.97 0.00 -1696.19 -77.54
F6 N1 APARTMENT 11-MAR-16:15 1131.04 0.00 0.00 0.00 51.52 100.83 470.89 0.00 0.00 0.00 244.13 0.00 -62.79 0.00 -1935.62 0.00
F6 N2 APARTMENT 11-MAR-16:15 1157.43 0.00 0.00 0.00 51.56 100.83 470.89 0.00 0.00 0.00 216.36 0.00 -62.24 0.00 -1934.84 0.00
F6 S1 APARTMENT 08-MAR-09:40 241.58 0.00 0.00 0.00 40.75 28.81 394.37 463.05 0.00 0.00 912.81 0.00 0.00 0.00 -2081.36 0.00
F6 S2 APARTMENT 08-MAR-09:40 244.33 0.00 0.00 0.00 40.75 28.81 394.37 463.30 0.00 0.00 906.88 0.00 0.00 0.00 -2078.43 0.00
F7 SW APARTMENT 08-MAR-09:40 557.98 0.00 0.00 0.00 40.77 28.81 394.37 537.01 0.00 0.00 681.29 0.00 0.00 0.00 -2240.23 0.00
F7 NW APARTMENT 03-JAN-09:45 1119.67 0.00 0.00 0.00 44.89 28.81 394.37 0.00 0.00 0.00 0.00 0.00 -155.63 0.00 -1349.16 -82.96
F7 SE APARTMENT 08-MAR-09:40 453.23 0.00 0.00 0.00 40.76 28.81 394.37 913.06 0.00 0.00 413.48 0.00 0.00 0.00 -2243.72 0.00
F7 NE APARTMENT 03-FEB-13:45 1632.57 0.00 0.00 0.00 43.24 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -15.02 0.00 -1759.58 -318.50
F7 N1 APARTMENT 11-MAR-16:15 1519.10 0.00 0.00 0.00 51.88 100.83 470.89 0.00 0.00 0.00 0.00 0.00 -62.53 0.00 -2021.86 -58.31
F7 N2 APARTMENT 11-MAR-16:15 1544.19 0.00 0.00 0.00 51.92 100.83 470.89 0.00 0.00 0.00 0.00 0.00 -62.06 0.00 -2021.17 -84.61
F7 S1 APARTMENT 08-MAR-09:40 268.34 0.00 0.00 0.00 40.75 28.81 394.37 449.29 0.00 0.00 930.60 0.00 0.00 0.00 -2112.16 0.00
F7 S2 APARTMENT 08-MAR-09:40 268.02 0.00 0.00 0.00 40.75 28.81 394.37 449.57 0.00 0.00 933.61 0.00 0.00 0.00 -2115.13 0.00
F8 SW APARTMENT 08-MAR-09:40 564.78 0.00 0.00 0.00 40.97 28.81 394.37 526.55 0.00 0.00 726.68 0.00 0.00 0.00 -2282.16 0.00
F8 NW APARTMENT 03-FEB-13:45 1285.99 0.00 0.00 0.00 43.69 28.81 388.49 464.96 0.00 0.00 0.00 0.00 0.00 0.00 -1833.74 -378.20
F8 SE APARTMENT 10-FEB-12:30 506.51 0.00 0.00 0.00 47.38 28.81 406.15 0.00 0.00 0.00 926.21 0.00 -110.76 0.00 -1804.29 0.00
F8 NE APARTMENT 03-FEB-13:45 1577.86 0.00 0.00 0.00 43.64 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -14.73 0.00 -1827.65 -196.42
F8 N1 APARTMENT 03-FEB-13:45 1569.04 0.00 0.00 0.00 43.32 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -12.40 0.00 -1749.98 -267.26
F8 N2 APARTMENT 03-FEB-13:45 1585.42 0.00 0.00 0.00 43.29 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -12.90 0.00 -1750.01 -283.09
F8 S1 APARTMENT 08-MAR-09:45 627.33 0.00 0.00 0.00 40.75 28.81 394.37 437.85 0.00 0.00 384.33 0.00 0.00 0.00 -1913.44 0.00
F8 S2 APARTMENT 08-MAR-09:45 713.26 0.00 0.00 0.00 40.75 28.81 394.37 438.18 0.00 0.00 296.94 0.00 0.00 0.00 -1912.32 0.00
F9 SW APARTMENT 08-MAR-09:45 884.66 0.00 0.00 0.00 41.59 28.81 394.37 526.91 0.00 0.00 201.50 0.00 0.00 0.00 -2077.84 0.00
F9 NW APARTMENT 08-MAR-09:45 1403.70 0.00 0.00 0.00 43.32 28.81 394.37 246.58 0.00 0.00 0.00 0.00 0.00 0.00 -1870.78 -246.01
F9 SE APARTMENT 08-MAR-09:45 671.44 0.00 0.00 0.00 41.51 28.81 394.37 889.24 0.00 0.00 50.21 0.00 0.00 0.00 -2075.58 0.00
F9 NE APARTMENT 03-FEB-13:45 1555.89 0.00 0.00 0.00 44.17 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -9.01 0.00 -1891.08 -117.27
F9 N1 APARTMENT 11-MAR-16:15 1592.44 0.00 0.00 0.00 52.23 100.83 470.89 0.00 0.00 0.00 40.07 0.00 -64.98 0.00 -2191.48 0.00
F9 N2 APARTMENT 11-MAR-16:15 1591.39 0.00 0.00 0.00 52.26 100.83 470.89 0.00 0.00 0.00 40.62 0.00 -64.58 0.00 -2191.41 0.00
F9 S1 APARTMENT 11-MAR-16:15 755.50 0.00 0.00 0.00 49.24 100.83 470.89 255.90 0.00 0.00 591.63 0.00 0.00 0.00 -2223.99 0.00
F9 S2 APARTMENT 11-MAR-16:15 773.95 0.00 0.00 0.00 49.26 100.83 470.89 256.14 0.00 0.00 572.57 0.00 0.00 0.00 -2223.64 0.00
T SW APARTMENT 08-MAR-09:45 1531.83 0.00 0.00 0.00 42.85 28.81 394.37 548.60 0.00 0.00 0.00 0.00 0.00 0.00 -2124.60 -421.86
T NW APARTMENT 22-NOV-06:45 1751.41 0.00 0.00 0.00 170.17 100.83 317.85 0.00 0.00 0.00 237.89 0.00 -556.75 0.00 -2021.41 0.00
T SE APARTMENT 22-NOV-06:45 1540.79 0.00 0.00 0.00 168.84 100.83 317.85 0.00 0.00 0.00 477.30 0.00 -579.67 0.00 -2025.94 0.00
T NE APARTMENT 03-FEB-13:45 1805.46 0.00 0.00 0.00 42.98 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -44.51 0.00 -1958.73 -262.49
T N1 APARTMENT 03-FEB-13:45 1697.36 0.00 0.00 0.00 43.37 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -16.53 0.00 -1871.59 -269.90
T N2 APARTMENT 03-FEB-13:45 1729.80 0.00 0.00 0.00 43.23 28.81 388.49 0.00 0.00 0.00 0.00 0.00 -18.88 0.00 -1871.92 -299.53
T S1 APARTMENT 08-MAR-09:45 1306.66 0.00 0.00 0.00 42.00 28.81 394.37 442.50 0.00 0.00 0.00 0.00 0.00 0.00 -2032.50 -181.84
T S2 APARTMENT 08-MAR-09:45 1302.38 0.00 0.00 0.00 42.01 28.81 394.37 442.64 0.00 0.00 0.00 0.00 0.00 0.00 -2032.55 -177.66
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-FEB-13:45 47625.91 0.00 0.00 0.00 3498.75 10361.29 31389.06 418.19 0.00 0.00 16284.66 0.00 -3939.73 0.00 -105638.13 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Sec1.1A-General Information

Data
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 10.75
Number of hours cooling loads not met 640.00
Number of hours not met 650.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 416.41 25049.15 0.00 0.00 0.00 0.00
Exterior Lighting 168.51 10720.10 0.00 0.00 0.00 0.00
Space Heating 4.73 0.00 2.88 27346.18 0.00 0.00
Space Cooling 908.06 71861.98 0.00 0.00 0.00 0.00
Pumps 52.12 1697.55 0.00 0.00 0.00 0.00
Heat Rejection 33.55 2260.76 0.00 0.00 0.00 0.00
Fans-Interior 770.14 24420.97 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 899.03 78424.24 0.00 0.00
Receptacle Equipment 1131.09 49704.83 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3505.44   901.91   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1131.09 3505.44
Natural Gas 0.00 901.91
Additional 0.00 0.00
Total 1131.09 4407.35


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 53.14
Space Heating 0.60
Space Cooling 115.88
Fans-Interior 98.28
Service Water Heating 0.00
Receptacle Equipment 144.34
Miscellaneous 35.09
Subtotal 447.32


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.37
Service Water Heating 114.72
Miscellaneous -0.00
Subtotal 115.09


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 9.45
Space Heating 0.17
Space Cooling 20.60
Fans-Interior 17.47
Service Water Heating 20.40
Receptacle Equipment 25.66
Miscellaneous 6.24



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.308247
G NW APARTMENT DIRECT AIR 0.305369
OFFICE DIRECT AIR 0.369788
G NE APARTMENT DIRECT AIR 0.244620
G N1 APARTMENT DIRECT AIR 0.166075
G N2 APARTMENT DIRECT AIR 0.164931
G S1 APARTMENT DIRECT AIR 0.173846
G S2 APARTMENT DIRECT AIR 0.178861
F2 SW APARTMENT DIRECT AIR 0.357233
F2 NW APARTMENT DIRECT AIR 0.353052
F2 SE APARTMENT DIRECT AIR 0.323198
F2 NE APARTMENT DIRECT AIR 0.288049
F2 N1 APARTMENT DIRECT AIR 0.195840
F2 N2 APARTMENT DIRECT AIR 0.194951
F2 S1 APARTMENT DIRECT AIR 0.207052
F2 S2 APARTMENT DIRECT AIR 0.208798
F3 SW APARTMENT DIRECT AIR 0.357064
F3 NW APARTMENT DIRECT AIR 0.353034
F3 SE APARTMENT DIRECT AIR 0.308211
F3 NE APARTMENT DIRECT AIR 0.290016
F3 N1 APARTMENT DIRECT AIR 0.197810
F3 N2 APARTMENT DIRECT AIR 0.196945
F3 S1 APARTMENT DIRECT AIR 0.209441
F3 S2 APARTMENT DIRECT AIR 0.210212
F4 SW APARTMENT DIRECT AIR 0.358276
F4 NW APARTMENT DIRECT AIR 0.354141
F4 SE APARTMENT DIRECT AIR 0.308207
F4 NE APARTMENT DIRECT AIR 0.291535
F4 N1 APARTMENT DIRECT AIR 0.199845
F4 N2 APARTMENT DIRECT AIR 0.198995
F4 S1 APARTMENT DIRECT AIR 0.211446
F4 S2 APARTMENT DIRECT AIR 0.212074
M SW APARTMENT DIRECT AIR 0.361971
M NW APARTMENT DIRECT AIR 0.357856
M SE APARTMENT DIRECT AIR 0.312053
M NE APARTMENT DIRECT AIR 0.295504
M N1 APARTMENT DIRECT AIR 0.204131
M N2 APARTMENT DIRECT AIR 0.203294
M S1 APARTMENT DIRECT AIR 0.215637
M S2 APARTMENT DIRECT AIR 0.216242
F6 SW APARTMENT DIRECT AIR 0.358915
F6 NW APARTMENT DIRECT AIR 0.354634
F6 SE APARTMENT DIRECT AIR 0.309392
F6 NE APARTMENT DIRECT AIR 0.292596
F6 N1 APARTMENT DIRECT AIR 0.201601
F6 N2 APARTMENT DIRECT AIR 0.200778
F6 S1 APARTMENT DIRECT AIR 0.213173
F6 S2 APARTMENT DIRECT AIR 0.213773
F7 SW APARTMENT DIRECT AIR 0.358318
F7 NW APARTMENT DIRECT AIR 0.353977
F7 SE APARTMENT DIRECT AIR 0.309113
F7 NE APARTMENT DIRECT AIR 0.292178
F7 N1 APARTMENT DIRECT AIR 0.201449
F7 N2 APARTMENT DIRECT AIR 0.200638
F7 S1 APARTMENT DIRECT AIR 0.212998
F7 S2 APARTMENT DIRECT AIR 0.213595
F8 SW APARTMENT DIRECT AIR 0.359271
F8 NW APARTMENT DIRECT AIR 0.354876
F8 SE APARTMENT DIRECT AIR 0.310304
F8 NE APARTMENT DIRECT AIR 0.293227
F8 N1 APARTMENT DIRECT AIR 0.202779
F8 N2 APARTMENT DIRECT AIR 0.201980
F8 S1 APARTMENT DIRECT AIR 0.214261
F8 S2 APARTMENT DIRECT AIR 0.214857
F9 SW APARTMENT DIRECT AIR 0.369403
F9 NW APARTMENT DIRECT AIR 0.365061
F9 SE APARTMENT DIRECT AIR 0.316799
F9 NE APARTMENT DIRECT AIR 0.299036
F9 N1 APARTMENT DIRECT AIR 0.212448
F9 N2 APARTMENT DIRECT AIR 0.211654
F9 S1 APARTMENT DIRECT AIR 0.221718
F9 S2 APARTMENT DIRECT AIR 0.222303
T SW APARTMENT DIRECT AIR 0.435450
T NW APARTMENT DIRECT AIR 0.427665
T SE APARTMENT DIRECT AIR 0.377450
T NE APARTMENT DIRECT AIR 0.348745
T N1 APARTMENT DIRECT AIR 0.257880
T N2 APARTMENT DIRECT AIR 0.256570
T S1 APARTMENT DIRECT AIR 0.288532
T S2 APARTMENT DIRECT AIR 0.289089


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.308247
AIRLOOP G NW MAIN BRANCH 0.305369
AIRLOOP OFFICE MAIN BRANCH 0.369788
AIRLOOP G NE MAIN BRANCH 0.244620
AIRLOOP G N1 MAIN BRANCH 0.166075
AIRLOOP G N2 MAIN BRANCH 0.164931
AIRLOOP G S1 MAIN BRANCH 0.173846
AIRLOOP G S2 MAIN BRANCH 0.178861
AIRLOOP F2 SW MAIN BRANCH 0.357233
AIRLOOP F2 NW MAIN BRANCH 0.353052
AIRLOOP F2 SE MAIN BRANCH 0.323198
AIRLOOP F2 NE MAIN BRANCH 0.288049
AIRLOOP F2 N1 MAIN BRANCH 0.195840
AIRLOOP F2 N2 MAIN BRANCH 0.194951
AIRLOOP F2 S1 MAIN BRANCH 0.207052
AIRLOOP F2 S2 MAIN BRANCH 0.208798
AIRLOOP F3 SW MAIN BRANCH 0.357064
AIRLOOP F3 NW MAIN BRANCH 0.353034
AIRLOOP F3 SE MAIN BRANCH 0.308211
AIRLOOP F3 NE MAIN BRANCH 0.290016
AIRLOOP F3 N1 MAIN BRANCH 0.197810
AIRLOOP F3 N2 MAIN BRANCH 0.196945
AIRLOOP F3 S1 MAIN BRANCH 0.209441
AIRLOOP F3 S2 MAIN BRANCH 0.210212
AIRLOOP F4 SW MAIN BRANCH 0.358276
AIRLOOP F4 NW MAIN BRANCH 0.354141
AIRLOOP F4 SE MAIN BRANCH 0.308207
AIRLOOP F4 NE MAIN BRANCH 0.291535
AIRLOOP F4 N1 MAIN BRANCH 0.199845
AIRLOOP F4 N2 MAIN BRANCH 0.198995
AIRLOOP F4 S1 MAIN BRANCH 0.211446
AIRLOOP F4 S2 MAIN BRANCH 0.212074
AIRLOOP M SW MAIN BRANCH 0.361971
AIRLOOP M NW MAIN BRANCH 0.357856
AIRLOOP M SE MAIN BRANCH 0.312053
AIRLOOP M NE MAIN BRANCH 0.295504
AIRLOOP M N1 MAIN BRANCH 0.204131
AIRLOOP M N2 MAIN BRANCH 0.203294
AIRLOOP M S1 MAIN BRANCH 0.215637
AIRLOOP M S2 MAIN BRANCH 0.216242
AIRLOOP F6 SW MAIN BRANCH 0.358915
AIRLOOP F6 NW MAIN BRANCH 0.354634
AIRLOOP F6 SE MAIN BRANCH 0.309392
AIRLOOP F6 NE MAIN BRANCH 0.292596
AIRLOOP F6 N1 MAIN BRANCH 0.201601
AIRLOOP F6 N2 MAIN BRANCH 0.200778
AIRLOOP F6 S1 MAIN BRANCH 0.213173
AIRLOOP F6 S2 MAIN BRANCH 0.213773
AIRLOOP F7 SW MAIN BRANCH 0.358318
AIRLOOP F7 NW MAIN BRANCH 0.353977
AIRLOOP F7 SE MAIN BRANCH 0.309113
AIRLOOP F7 NE MAIN BRANCH 0.292178
AIRLOOP F7 N1 MAIN BRANCH 0.201449
AIRLOOP F7 N2 MAIN BRANCH 0.200638
AIRLOOP F7 S1 MAIN BRANCH 0.212998
AIRLOOP F7 S2 MAIN BRANCH 0.213595
AIRLOOP F8 SW MAIN BRANCH 0.359271
AIRLOOP F8 NW MAIN BRANCH 0.354876
AIRLOOP F8 SE MAIN BRANCH 0.310304
AIRLOOP F8 NE MAIN BRANCH 0.293227
AIRLOOP F8 N1 MAIN BRANCH 0.202779
AIRLOOP F8 N2 MAIN BRANCH 0.201980
AIRLOOP F8 S1 MAIN BRANCH 0.214261
AIRLOOP F8 S2 MAIN BRANCH 0.214857
AIRLOOP F9 SW MAIN BRANCH 0.369403
AIRLOOP F9 NW MAIN BRANCH 0.365061
AIRLOOP F9 SE MAIN BRANCH 0.316799
AIRLOOP F9 NE MAIN BRANCH 0.299036
AIRLOOP F9 N1 MAIN BRANCH 0.212448
AIRLOOP F9 N2 MAIN BRANCH 0.211654
AIRLOOP F9 S1 MAIN BRANCH 0.221718
AIRLOOP F9 S2 MAIN BRANCH 0.222303
AIRLOOP T SW MAIN BRANCH 0.435450
AIRLOOP T NW MAIN BRANCH 0.427665
AIRLOOP T SE MAIN BRANCH 0.377450
AIRLOOP T NE MAIN BRANCH 0.348745
AIRLOOP T N1 MAIN BRANCH 0.257880
AIRLOOP T N2 MAIN BRANCH 0.256570
AIRLOOP T S1 MAIN BRANCH 0.288532
AIRLOOP T S2 MAIN BRANCH 0.289089


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.308247
AIRLOOP G NW 0.305369
AIRLOOP OFFICE 0.369788
AIRLOOP G NE 0.244620
AIRLOOP G N1 0.166075
AIRLOOP G N2 0.164931
AIRLOOP G S1 0.173846
AIRLOOP G S2 0.178861
AIRLOOP F2 SW 0.357233
AIRLOOP F2 NW 0.353052
AIRLOOP F2 SE 0.323198
AIRLOOP F2 NE 0.288049
AIRLOOP F2 N1 0.195840
AIRLOOP F2 N2 0.194951
AIRLOOP F2 S1 0.207052
AIRLOOP F2 S2 0.208798
AIRLOOP F3 SW 0.357064
AIRLOOP F3 NW 0.353034
AIRLOOP F3 SE 0.308211
AIRLOOP F3 NE 0.290016
AIRLOOP F3 N1 0.197810
AIRLOOP F3 N2 0.196945
AIRLOOP F3 S1 0.209441
AIRLOOP F3 S2 0.210212
AIRLOOP F4 SW 0.358276
AIRLOOP F4 NW 0.354141
AIRLOOP F4 SE 0.308207
AIRLOOP F4 NE 0.291535
AIRLOOP F4 N1 0.199845
AIRLOOP F4 N2 0.198995
AIRLOOP F4 S1 0.211446
AIRLOOP F4 S2 0.212074
AIRLOOP M SW 0.361971
AIRLOOP M NW 0.357856
AIRLOOP M SE 0.312053
AIRLOOP M NE 0.295504
AIRLOOP M N1 0.204131
AIRLOOP M N2 0.203294
AIRLOOP M S1 0.215637
AIRLOOP M S2 0.216242
AIRLOOP F6 SW 0.358915
AIRLOOP F6 NW 0.354634
AIRLOOP F6 SE 0.309392
AIRLOOP F6 NE 0.292596
AIRLOOP F6 N1 0.201601
AIRLOOP F6 N2 0.200778
AIRLOOP F6 S1 0.213173
AIRLOOP F6 S2 0.213773
AIRLOOP F7 SW 0.358318
AIRLOOP F7 NW 0.353977
AIRLOOP F7 SE 0.309113
AIRLOOP F7 NE 0.292178
AIRLOOP F7 N1 0.201449
AIRLOOP F7 N2 0.200638
AIRLOOP F7 S1 0.212998
AIRLOOP F7 S2 0.213595
AIRLOOP F8 SW 0.359271
AIRLOOP F8 NW 0.354876
AIRLOOP F8 SE 0.310304
AIRLOOP F8 NE 0.293227
AIRLOOP F8 N1 0.202779
AIRLOOP F8 N2 0.201980
AIRLOOP F8 S1 0.214261
AIRLOOP F8 S2 0.214857
AIRLOOP F9 SW 0.369403
AIRLOOP F9 NW 0.365061
AIRLOOP F9 SE 0.316799
AIRLOOP F9 NE 0.299036
AIRLOOP F9 N1 0.212448
AIRLOOP F9 N2 0.211654
AIRLOOP F9 S1 0.221718
AIRLOOP F9 S2 0.222303
AIRLOOP T SW 0.435450
AIRLOOP T NW 0.427665
AIRLOOP T SE 0.377450
AIRLOOP T NE 0.348745
AIRLOOP T N1 0.257880
AIRLOOP T N2 0.256570
AIRLOOP T S1 0.288532
AIRLOOP T S2 0.289089


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.308247 0.025952
AIRLOOP G NW OA CONTROLLER 0.305369 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.369788 0.038103
AIRLOOP G NE OA CONTROLLER 0.244620 0.025952
AIRLOOP G N1 OA CONTROLLER 0.166075 0.025952
AIRLOOP G N2 OA CONTROLLER 0.164931 0.025952
AIRLOOP G S1 OA CONTROLLER 0.173846 0.025952
AIRLOOP G S2 OA CONTROLLER 0.178861 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.357233 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.353052 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.323198 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.288049 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.195840 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.194951 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.207052 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.208798 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.357064 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.353034 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.308211 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.290016 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.197810 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.196945 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.209441 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.210212 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.358276 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.354141 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.308207 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.291535 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.199845 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.198995 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.211446 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.212074 0.025952
AIRLOOP M SW OA CONTROLLER 0.361971 0.025952
AIRLOOP M NW OA CONTROLLER 0.357856 0.025952
AIRLOOP M SE OA CONTROLLER 0.312053 0.025952
AIRLOOP M NE OA CONTROLLER 0.295504 0.025952
AIRLOOP M N1 OA CONTROLLER 0.204131 0.025952
AIRLOOP M N2 OA CONTROLLER 0.203294 0.025952
AIRLOOP M S1 OA CONTROLLER 0.215637 0.025952
AIRLOOP M S2 OA CONTROLLER 0.216242 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.358915 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.354634 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.309392 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.292596 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.201601 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.200778 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.213173 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.213773 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.358318 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.353977 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.309113 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.292178 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.201449 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.200638 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.212998 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.213595 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.359271 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.354876 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.310304 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.293227 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.202779 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.201980 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.214261 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.214857 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.369403 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.365061 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.316799 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.299036 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.212448 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.211654 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.221718 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.222303 0.025952
AIRLOOP T SW OA CONTROLLER 0.435450 0.025952
AIRLOOP T NW OA CONTROLLER 0.427665 0.025952
AIRLOOP T SE OA CONTROLLER 0.377450 0.025952
AIRLOOP T NE OA CONTROLLER 0.348745 0.025952
AIRLOOP T N1 OA CONTROLLER 0.257880 0.025952
AIRLOOP T N2 OA CONTROLLER 0.256570 0.025952
AIRLOOP T S1 OA CONTROLLER 0.288532 0.025952
AIRLOOP T S2 OA CONTROLLER 0.289089 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.308247 4243.04 2984.76 0.000093
HEAT PUMP COOLING MODE AIRLOOP G NW 0.305369 4183.96 2946.65 0.000091
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.369788 5085.53 3591.12 0.000111
HEAT PUMP COOLING MODE AIRLOOP G NE 0.244620 3334.17 2363.95 0.000073
HEAT PUMP COOLING MODE AIRLOOP G N1 0.166075 2349.11 1643.81 0.000051
HEAT PUMP COOLING MODE AIRLOOP G N2 0.164931 2334.02 1633.15 0.000051
HEAT PUMP COOLING MODE AIRLOOP G S1 0.173846 2535.29 1753.96 0.000055
HEAT PUMP COOLING MODE AIRLOOP G S2 0.178861 2601.05 1800.76 0.000057
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.357233 4853.94 3430.15 0.000106
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.353052 4784.33 3382.77 0.000105
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.323198 4373.99 3101.35 0.000096
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.288049 3891.60 2766.56 0.000085
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.195840 2730.89 1921.22 0.000060
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.194951 2719.23 1912.97 0.000059
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.207052 2956.60 2060.46 0.000065
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.208798 2979.47 2076.71 0.000065
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.357064 4837.17 3425.54 0.000106
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.353034 4769.50 3379.55 0.000104
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.308211 4163.72 2959.75 0.000091
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.290016 3903.00 2781.77 0.000085
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.197810 2748.34 1937.76 0.000060
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.196945 2736.99 1929.73 0.000060
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.209441 2979.61 2080.95 0.000065
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.210212 2989.72 2088.13 0.000065
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.358276 4842.12 3434.47 0.000106
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.354141 4774.99 3389.91 0.000104
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.308207 4152.90 2957.48 0.000091
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.291535 3912.13 2793.59 0.000085
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.199845 2768.72 1955.34 0.000060
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.198995 2757.58 1947.45 0.000060
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.211446 2999.64 2098.30 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.212074 3007.87 2104.14 0.000066
HEAT PUMP COOLING MODE AIRLOOP M SW 0.361971 4881.49 3466.77 0.000107
HEAT PUMP COOLING MODE AIRLOOP M NW 0.357856 4814.58 3422.38 0.000105
HEAT PUMP COOLING MODE AIRLOOP M SE 0.312053 4203.87 2995.16 0.000092
HEAT PUMP COOLING MODE AIRLOOP M NE 0.295504 3955.20 2828.47 0.000086
HEAT PUMP COOLING MODE AIRLOOP M N1 0.204131 2819.79 1994.05 0.000062
HEAT PUMP COOLING MODE AIRLOOP M N2 0.203294 2808.82 1986.28 0.000061
HEAT PUMP COOLING MODE AIRLOOP M S1 0.215637 3049.35 2136.18 0.000067
HEAT PUMP COOLING MODE AIRLOOP M S2 0.216242 3057.28 2141.81 0.000067
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.358915 4839.40 3439.66 0.000106
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.354634 4764.82 3391.00 0.000104
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.309392 4161.69 2969.01 0.000091
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.292596 3909.83 2800.05 0.000085
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.201601 2782.20 1969.65 0.000061
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.200778 2771.44 1962.02 0.000061
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.213173 3012.82 2112.38 0.000066
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.213773 3020.68 2117.96 0.000066
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.358318 4824.90 3432.74 0.000105
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.353977 4749.51 3383.53 0.000104
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.309113 4151.50 2965.08 0.000091
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.292178 3897.85 2794.84 0.000085
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.201449 2776.35 1967.44 0.000061
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.200638 2765.74 1959.91 0.000060
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.212998 3006.73 2109.96 0.000066
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.213595 3014.55 2115.52 0.000066
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.359271 4831.34 3440.30 0.000106
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.354876 4755.22 3390.58 0.000104
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.310304 4161.15 2974.86 0.000091
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.293227 3905.68 2803.33 0.000085
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.202779 2790.32 1979.06 0.000061
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.201980 2779.86 1971.65 0.000061
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.214261 3019.82 2120.99 0.000066
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.214857 3027.62 2126.53 0.000066
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.369403 4952.70 3530.07 0.000108
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.365061 4882.70 3483.55 0.000107
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.316799 4240.41 3033.76 0.000093
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.299036 3975.99 2855.89 0.000087
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.212448 2913.73 2068.07 0.000064
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.211654 2903.36 2060.72 0.000063
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.221718 3118.74 2191.44 0.000068
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.222303 3126.40 2196.88 0.000068
HEAT PUMP COOLING MODE AIRLOOP T SW 0.435450 5820.94 4144.76 0.000127
HEAT PUMP COOLING MODE AIRLOOP T NW 0.427665 5708.25 4067.27 0.000125
HEAT PUMP COOLING MODE AIRLOOP T SE 0.377450 5093.90 3621.54 0.000111
HEAT PUMP COOLING MODE AIRLOOP T NE 0.348745 4642.57 3323.94 0.000101
HEAT PUMP COOLING MODE AIRLOOP T N1 0.257880 3515.81 2493.40 0.000077
HEAT PUMP COOLING MODE AIRLOOP T N2 0.256570 3565.58 2512.02 0.000078
HEAT PUMP COOLING MODE AIRLOOP T S1 0.288532 3988.37 2810.42 0.000087
HEAT PUMP COOLING MODE AIRLOOP T S2 0.289089 3995.68 2815.59 0.000087


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.308247 0.308247 0.308247 0.308247 4243.04 4243.04 2082.56 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.305369 0.305369 0.305369 0.305369 4183.96 4183.96 2093.15 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.369788 0.369788 0.369788 0.369788 5085.53 5085.53 2763.96 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.244620 0.244620 0.244620 0.244620 3334.17 3334.17 2087.42 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.166075 0.166075 0.166075 0.166075 2349.11 2349.11 1491.36 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.164931 0.164931 0.164931 0.164931 2334.02 2334.02 1491.27 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.173846 0.173846 0.173846 0.173846 2535.29 2535.29 1478.41 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.178861 0.178861 0.178861 0.178861 2601.05 2601.05 1486.73 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.357233 0.357233 0.357233 0.357233 4853.94 4853.94 2009.86 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.353052 0.353052 0.353052 0.353052 4784.33 4784.33 2019.31 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.323198 0.323198 0.323198 0.323198 4373.99 4373.99 2030.18 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.288049 0.288049 0.288049 0.288049 3891.60 3891.60 2013.51 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.195840 0.195840 0.195840 0.195840 2730.89 2730.89 1314.37 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.194951 0.194951 0.194951 0.194951 2719.23 2719.23 1314.27 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.207052 0.207052 0.207052 0.207052 2956.60 2956.60 1307.62 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.208798 0.208798 0.208798 0.208798 2979.47 2979.47 1309.38 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.357064 0.357064 0.357064 0.357064 4837.17 4837.17 1978.95 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.353034 0.353034 0.353034 0.353034 4769.50 4769.50 1987.31 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.308211 0.308211 0.308211 0.308211 4163.72 4163.72 1977.14 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.290016 0.290016 0.290016 0.290016 3903.00 3903.00 1982.33 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.197810 0.197810 0.197810 0.197810 2748.34 2748.34 1267.10 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.196945 0.196945 0.196945 0.196945 2736.99 2736.99 1267.01 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.209441 0.209441 0.209441 0.209441 2979.61 2979.61 1259.30 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.210212 0.210212 0.210212 0.210212 2989.72 2989.72 1259.53 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.358276 0.358276 0.358276 0.358276 4842.12 4842.12 1987.64 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.354141 0.354141 0.354141 0.354141 4774.99 4774.99 1995.13 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.308207 0.308207 0.308207 0.308207 4152.90 4152.90 1983.84 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.291535 0.291535 0.291535 0.291535 3912.13 3912.13 1990.96 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.199845 0.199845 0.199845 0.199845 2768.72 2768.72 1262.23 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.198995 0.198995 0.198995 0.198995 2757.58 2757.58 1262.15 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.211446 0.211446 0.211446 0.211446 2999.64 2999.64 1255.00 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.212074 0.212074 0.212074 0.212074 3007.87 3007.87 1254.98 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.361971 0.361971 0.361971 0.361971 4881.49 4881.49 1979.49 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.357856 0.357856 0.357856 0.357856 4814.58 4814.58 1984.83 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.312053 0.312053 0.312053 0.312053 4203.87 4203.87 1976.14 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.295504 0.295504 0.295504 0.295504 3955.20 3955.20 1981.43 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.204131 0.204131 0.204131 0.204131 2819.79 2819.79 1245.13 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.203294 0.203294 0.203294 0.203294 2808.82 2808.82 1245.07 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.215637 0.215637 0.215637 0.215637 3049.35 3049.35 1240.02 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.216242 0.216242 0.216242 0.216242 3057.28 3057.28 1239.97 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.358915 0.358915 0.358915 0.358915 4839.40 4839.40 2038.34 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.354634 0.354634 0.354634 0.354634 4764.82 4764.82 2043.54 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.309392 0.309392 0.309392 0.309392 4161.69 4161.69 2035.65 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.292596 0.292596 0.292596 0.292596 3909.83 3909.83 2040.85 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.201601 0.201601 0.201601 0.201601 2782.20 2782.20 1291.38 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.200778 0.200778 0.200778 0.200778 2771.44 2771.44 1291.33 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.213173 0.213173 0.213173 0.213173 3012.82 3012.82 1286.37 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.213773 0.213773 0.213773 0.213773 3020.68 3020.68 1286.32 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.358318 0.358318 0.358318 0.358318 4824.90 4824.90 2073.15 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.353977 0.353977 0.353977 0.353977 4749.51 4749.51 2077.09 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.309113 0.309113 0.309113 0.309113 4151.50 4151.50 2071.11 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.292178 0.292178 0.292178 0.292178 3897.85 3897.85 2075.05 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.201449 0.201449 0.201449 0.201449 2776.35 2776.35 1317.05 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.200638 0.200638 0.200638 0.200638 2765.74 2765.74 1317.01 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.212998 0.212998 0.212998 0.212998 3006.73 3006.73 1313.28 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.213595 0.213595 0.213595 0.213595 3014.55 3014.55 1313.24 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.359271 0.359271 0.359271 0.359271 4831.34 4831.34 2110.78 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.354876 0.354876 0.354876 0.354876 4755.22 4755.22 2113.39 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.310304 0.310304 0.310304 0.310304 4161.15 4161.15 2109.35 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.293227 0.293227 0.293227 0.293227 3905.68 3905.68 2111.96 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.202779 0.202779 0.202779 0.202779 2790.32 2790.32 1346.83 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.201980 0.201980 0.201980 0.201980 2779.86 2779.86 1346.81 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.214261 0.214261 0.214261 0.214261 3019.82 3019.82 1344.40 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.214857 0.214857 0.214857 0.214857 3027.62 3027.62 1344.37 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.369403 0.369403 0.369403 0.369403 4952.70 4952.70 2240.53 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.365061 0.365061 0.365061 0.365061 4882.70 4882.70 2240.16 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.316799 0.316799 0.316799 0.316799 4240.41 4240.41 2239.67 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.299036 0.299036 0.299036 0.299036 3975.99 3975.99 2239.30 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.212448 0.212448 0.212448 0.212448 2913.73 2913.73 1460.96 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.211654 0.211654 0.211654 0.211654 2903.36 2903.36 1460.95 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.221718 0.221718 0.221718 0.221718 3118.74 3118.74 1461.26 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.222303 0.222303 0.222303 0.222303 3126.40 3126.40 1461.25 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.435450 0.435450 0.435450 0.435450 5820.94 5820.94 2692.67 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.427665 0.427665 0.427665 0.427665 5708.25 5708.25 2695.76 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.377450 0.377450 0.377450 0.377450 5093.90 5093.90 2692.34 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.348745 0.348745 0.348745 0.348745 4642.57 4642.57 2695.43 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.257880 0.257880 0.257880 0.257880 3515.81 3515.81 1952.16 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.256570 0.256570 0.256570 0.256570 3565.58 3565.58 1952.16 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.288532 0.288532 0.288532 0.288532 3988.37 3988.37 1948.17 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.289089 0.289089 0.289089 0.289089 3995.68 3995.68 1948.16 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.308247
AIRLOOP G NW SUPPLY FAN 0.305369
AIRLOOP OFFICE SUPPLY FAN 0.369788
AIRLOOP G NE SUPPLY FAN 0.244620
AIRLOOP G N1 SUPPLY FAN 0.166075
AIRLOOP G N2 SUPPLY FAN 0.164931
AIRLOOP G S1 SUPPLY FAN 0.173846
AIRLOOP G S2 SUPPLY FAN 0.178861
AIRLOOP F2 SW SUPPLY FAN 0.357233
AIRLOOP F2 NW SUPPLY FAN 0.353052
AIRLOOP F2 SE SUPPLY FAN 0.323198
AIRLOOP F2 NE SUPPLY FAN 0.288049
AIRLOOP F2 N1 SUPPLY FAN 0.195840
AIRLOOP F2 N2 SUPPLY FAN 0.194951
AIRLOOP F2 S1 SUPPLY FAN 0.207052
AIRLOOP F2 S2 SUPPLY FAN 0.208798
AIRLOOP F3 SW SUPPLY FAN 0.357064
AIRLOOP F3 NW SUPPLY FAN 0.353034
AIRLOOP F3 SE SUPPLY FAN 0.308211
AIRLOOP F3 NE SUPPLY FAN 0.290016
AIRLOOP F3 N1 SUPPLY FAN 0.197810
AIRLOOP F3 N2 SUPPLY FAN 0.196945
AIRLOOP F3 S1 SUPPLY FAN 0.209441
AIRLOOP F3 S2 SUPPLY FAN 0.210212
AIRLOOP F4 SW SUPPLY FAN 0.358276
AIRLOOP F4 NW SUPPLY FAN 0.354141
AIRLOOP F4 SE SUPPLY FAN 0.308207
AIRLOOP F4 NE SUPPLY FAN 0.291535
AIRLOOP F4 N1 SUPPLY FAN 0.199845
AIRLOOP F4 N2 SUPPLY FAN 0.198995
AIRLOOP F4 S1 SUPPLY FAN 0.211446
AIRLOOP F4 S2 SUPPLY FAN 0.212074
AIRLOOP M SW SUPPLY FAN 0.361971
AIRLOOP M NW SUPPLY FAN 0.357856
AIRLOOP M SE SUPPLY FAN 0.312053
AIRLOOP M NE SUPPLY FAN 0.295504
AIRLOOP M N1 SUPPLY FAN 0.204131
AIRLOOP M N2 SUPPLY FAN 0.203294
AIRLOOP M S1 SUPPLY FAN 0.215637
AIRLOOP M S2 SUPPLY FAN 0.216242
AIRLOOP F6 SW SUPPLY FAN 0.358915
AIRLOOP F6 NW SUPPLY FAN 0.354634
AIRLOOP F6 SE SUPPLY FAN 0.309392
AIRLOOP F6 NE SUPPLY FAN 0.292596
AIRLOOP F6 N1 SUPPLY FAN 0.201601
AIRLOOP F6 N2 SUPPLY FAN 0.200778
AIRLOOP F6 S1 SUPPLY FAN 0.213173
AIRLOOP F6 S2 SUPPLY FAN 0.213773
AIRLOOP F7 SW SUPPLY FAN 0.358318
AIRLOOP F7 NW SUPPLY FAN 0.353977
AIRLOOP F7 SE SUPPLY FAN 0.309113
AIRLOOP F7 NE SUPPLY FAN 0.292178
AIRLOOP F7 N1 SUPPLY FAN 0.201449
AIRLOOP F7 N2 SUPPLY FAN 0.200638
AIRLOOP F7 S1 SUPPLY FAN 0.212998
AIRLOOP F7 S2 SUPPLY FAN 0.213595
AIRLOOP F8 SW SUPPLY FAN 0.359271
AIRLOOP F8 NW SUPPLY FAN 0.354876
AIRLOOP F8 SE SUPPLY FAN 0.310304
AIRLOOP F8 NE SUPPLY FAN 0.293227
AIRLOOP F8 N1 SUPPLY FAN 0.202779
AIRLOOP F8 N2 SUPPLY FAN 0.201980
AIRLOOP F8 S1 SUPPLY FAN 0.214261
AIRLOOP F8 S2 SUPPLY FAN 0.214857
AIRLOOP F9 SW SUPPLY FAN 0.369403
AIRLOOP F9 NW SUPPLY FAN 0.365061
AIRLOOP F9 SE SUPPLY FAN 0.316799
AIRLOOP F9 NE SUPPLY FAN 0.299036
AIRLOOP F9 N1 SUPPLY FAN 0.212448
AIRLOOP F9 N2 SUPPLY FAN 0.211654
AIRLOOP F9 S1 SUPPLY FAN 0.221718
AIRLOOP F9 S2 SUPPLY FAN 0.222303
AIRLOOP T SW SUPPLY FAN 0.435450
AIRLOOP T NW SUPPLY FAN 0.427665
AIRLOOP T SE SUPPLY FAN 0.377450
AIRLOOP T NE SUPPLY FAN 0.348745
AIRLOOP T N1 SUPPLY FAN 0.257880
AIRLOOP T N2 SUPPLY FAN 0.256570
AIRLOOP T S1 SUPPLY FAN 0.288532
AIRLOOP T S2 SUPPLY FAN 0.289089


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.308247 4243.04 0.000093
HEAT PUMP HEATING MODE AIRLOOP G NW 0.305369 4183.96 0.000091
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.369788 5085.53 0.000111
HEAT PUMP HEATING MODE AIRLOOP G NE 0.244620 3334.17 0.000073
HEAT PUMP HEATING MODE AIRLOOP G N1 0.166075 2349.11 0.000051
HEAT PUMP HEATING MODE AIRLOOP G N2 0.164931 2334.02 0.000051
HEAT PUMP HEATING MODE AIRLOOP G S1 0.173846 2535.29 0.000055
HEAT PUMP HEATING MODE AIRLOOP G S2 0.178861 2601.05 0.000057
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.357233 4853.94 0.000106
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.353052 4784.33 0.000105
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.323198 4373.99 0.000096
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.288049 3891.60 0.000085
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.195840 2730.89 0.000060
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.194951 2719.23 0.000059
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.207052 2956.60 0.000065
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.208798 2979.47 0.000065
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.357064 4837.17 0.000106
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.353034 4769.50 0.000104
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.308211 4163.72 0.000091
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.290016 3903.00 0.000085
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.197810 2748.34 0.000060
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.196945 2736.99 0.000060
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.209441 2979.61 0.000065
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.210212 2989.72 0.000065
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.358276 4842.12 0.000106
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.354141 4774.99 0.000104
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.308207 4152.90 0.000091
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.291535 3912.13 0.000085
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.199845 2768.72 0.000060
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.198995 2757.58 0.000060
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.211446 2999.64 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.212074 3007.87 0.000066
HEAT PUMP HEATING MODE AIRLOOP M SW 0.361971 4881.49 0.000107
HEAT PUMP HEATING MODE AIRLOOP M NW 0.357856 4814.58 0.000105
HEAT PUMP HEATING MODE AIRLOOP M SE 0.312053 4203.87 0.000092
HEAT PUMP HEATING MODE AIRLOOP M NE 0.295504 3955.20 0.000086
HEAT PUMP HEATING MODE AIRLOOP M N1 0.204131 2819.79 0.000062
HEAT PUMP HEATING MODE AIRLOOP M N2 0.203294 2808.82 0.000061
HEAT PUMP HEATING MODE AIRLOOP M S1 0.215637 3049.35 0.000067
HEAT PUMP HEATING MODE AIRLOOP M S2 0.216242 3057.28 0.000067
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.358915 4839.40 0.000106
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.354634 4764.82 0.000104
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.309392 4161.69 0.000091
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.292596 3909.83 0.000085
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.201601 2782.20 0.000061
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.200778 2771.44 0.000061
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.213173 3012.82 0.000066
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.213773 3020.68 0.000066
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.358318 4824.90 0.000105
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.353977 4749.51 0.000104
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.309113 4151.50 0.000091
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.292178 3897.85 0.000085
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.201449 2776.35 0.000061
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.200638 2765.74 0.000060
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.212998 3006.73 0.000066
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.213595 3014.55 0.000066
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.359271 4831.34 0.000106
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.354876 4755.22 0.000104
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.310304 4161.15 0.000091
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.293227 3905.68 0.000085
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.202779 2790.32 0.000061
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.201980 2779.86 0.000061
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.214261 3019.82 0.000066
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.214857 3027.62 0.000066
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.369403 4952.70 0.000108
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.365061 4882.70 0.000107
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.316799 4240.41 0.000093
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.299036 3975.99 0.000087
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.212448 2913.73 0.000064
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.211654 2903.36 0.000063
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.221718 3118.74 0.000068
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.222303 3126.40 0.000068
HEAT PUMP HEATING MODE AIRLOOP T SW 0.435450 5820.94 0.000127
HEAT PUMP HEATING MODE AIRLOOP T NW 0.427665 5708.25 0.000125
HEAT PUMP HEATING MODE AIRLOOP T SE 0.377450 5093.90 0.000111
HEAT PUMP HEATING MODE AIRLOOP T NE 0.348745 4642.57 0.000101
HEAT PUMP HEATING MODE AIRLOOP T N1 0.257880 3515.81 0.000077
HEAT PUMP HEATING MODE AIRLOOP T N2 0.256570 3565.58 0.000078
HEAT PUMP HEATING MODE AIRLOOP T S1 0.288532 3988.37 0.000087
HEAT PUMP HEATING MODE AIRLOOP T S2 0.289089 3995.68 0.000087


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 2082.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 2093.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 2763.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 2087.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 1491.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 1491.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 1478.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 1486.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 2009.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 2019.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 2030.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 2013.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1314.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1314.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1307.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1309.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 1978.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 1987.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 1977.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 1982.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1267.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1267.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1259.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1259.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 1987.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 1995.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 1983.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 1990.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1262.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1262.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1255.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1254.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 1979.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 1984.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 1976.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 1981.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1245.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1245.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1240.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1239.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 2038.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 2043.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 2035.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 2040.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1291.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1291.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1286.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1286.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 2073.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 2077.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 2071.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 2075.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1317.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1317.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1313.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1313.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 2110.78
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 2113.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 2109.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 2111.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 1346.83
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 1346.81
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 1344.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 1344.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 2240.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 2240.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 2239.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 2239.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 1460.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 1460.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 1461.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 1461.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 2692.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 2695.76
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 2692.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 2695.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 1952.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 1952.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 1948.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 1948.16


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.006511 7.32


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.006511


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.006511 3143.11 9.11 8847.69


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.006511 1660.62



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2018-10-19 09:40:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.53 14.83
February 23.16 12.72
March 23.38 15.42
April 24.19 23.31
May 24.32 26.31
June 24.42 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.07 20.87
November 23.59 15.43
December 23.20 11.86
     
Annual Sum or Average 23.93 21.71
Minimum of Months 23.16 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.85 14.83
February 22.49 12.72
March 23.03 15.42
April 24.16 23.31
May 24.34 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.86 20.87
November 23.01 15.43
December 22.40 11.86
     
Annual Sum or Average 23.65 21.71
Minimum of Months 22.40 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.46 14.83
February 23.12 12.72
March 23.50 15.42
April 24.26 23.31
May 24.37 26.31
June 24.40 31.20
July 24.40 30.42
August 24.41 29.82
September 24.41 27.75
October 24.10 20.87
November 23.60 15.43
December 23.13 11.86
     
Annual Sum or Average 23.93 21.71
Minimum of Months 23.12 11.86
Maximum of Months 24.41 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.83 14.83
February 22.45 12.72
March 23.03 15.42
April 24.18 23.31
May 24.34 26.31
June 24.41 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.87 20.87
November 22.93 15.43
December 22.35 11.86
     
Annual Sum or Average 23.64 21.71
Minimum of Months 22.35 11.86
Maximum of Months 24.41 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.65 14.83
February 22.28 12.72
March 22.82 15.42
April 24.10 23.31
May 24.31 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.78 20.87
November 22.79 15.43
December 22.22 11.86
     
Annual Sum or Average 23.56 21.71
Minimum of Months 22.22 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.65 14.83
February 22.28 12.72
March 22.82 15.42
April 24.09 23.31
May 24.31 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.78 20.87
November 22.78 15.43
December 22.22 11.86
     
Annual Sum or Average 23.55 21.71
Minimum of Months 22.22 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.64 14.83
February 23.20 12.72
March 23.36 15.42
April 24.16 23.31
May 24.31 26.31
June 24.40 31.20
July 24.40 30.42
August 24.43 29.82
September 24.48 27.75
October 24.12 20.87
November 23.64 15.43
December 23.30 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 23.20 11.86
Maximum of Months 24.48 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.65 14.83
February 23.23 12.72
March 23.38 15.42
April 24.17 23.31
May 24.31 26.31
June 24.40 31.20
July 24.40 30.42
August 24.43 29.82
September 24.47 27.75
October 24.13 20.87
November 23.66 15.43
December 23.31 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 23.23 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.67 14.83
February 20.52 12.72
March 21.79 15.42
April 24.97 23.31
May 26.06 26.31
June 28.13 31.20
July 27.82 30.42
August 27.61 29.82
September 26.99 27.75
October 24.09 20.87
November 21.88 15.43
December 20.51 11.86
     
Annual Sum or Average 24.36 21.71
Minimum of Months 20.51 11.86
Maximum of Months 28.13 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 14.83
February 23.95 12.72
March 23.99 15.42
April 24.36 23.31
May 24.38 26.31
June 24.42 31.20
July 24.40 30.42
August 24.41 29.82
September 24.41 27.75
October 24.32 20.87
November 24.14 15.43
December 23.83 11.86
     
Annual Sum or Average 24.23 21.71
Minimum of Months 23.83 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.52 14.83
February 23.28 12.72
March 23.63 15.42
April 24.34 23.31
May 24.39 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.16 20.87
November 23.64 15.43
December 22.92 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 22.92 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.12 14.83
February 23.94 12.72
March 24.02 15.42
April 24.38 23.31
May 24.39 26.31
June 24.40 31.20
July 24.40 30.42
August 24.40 29.82
September 24.42 27.75
October 24.34 20.87
November 24.12 15.43
December 23.83 11.86
     
Annual Sum or Average 24.23 21.71
Minimum of Months 23.83 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.45 14.83
February 23.18 12.72
March 23.61 15.42
April 24.35 23.31
May 24.39 26.31
June 24.42 31.20
July 24.40 30.42
August 24.40 29.82
September 24.40 27.75
October 24.16 20.87
November 23.52 15.43
December 22.85 11.86
     
Annual Sum or Average 23.93 21.71
Minimum of Months 22.85 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.43 14.83
February 23.16 12.72
March 23.52 15.42
April 24.32 23.31
May 24.38 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.13 20.87
November 23.51 15.43
December 22.82 11.86
     
Annual Sum or Average 23.91 21.71
Minimum of Months 22.82 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.42 14.83
February 23.15 12.72
March 23.52 15.42
April 24.33 23.31
May 24.38 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.13 20.87
November 23.50 15.43
December 22.82 11.86
     
Annual Sum or Average 23.91 21.71
Minimum of Months 22.82 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 14.83
February 24.04 12.72
March 24.04 15.42
April 24.35 23.31
May 24.37 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.47 27.75
October 24.41 20.87
November 24.23 15.43
December 24.02 11.86
     
Annual Sum or Average 24.29 21.71
Minimum of Months 24.02 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.29 14.83
February 24.05 12.72
March 24.05 15.42
April 24.35 23.31
May 24.37 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.47 27.75
October 24.41 20.87
November 24.23 15.43
December 24.03 11.86
     
Annual Sum or Average 24.29 21.71
Minimum of Months 24.03 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.92 14.83
February 24.42 12.72
March 24.87 15.42
April 26.22 23.31
May 26.51 26.31
June 27.11 31.20
July 26.97 30.42
August 26.91 29.82
September 26.74 27.75
October 25.90 20.87
November 25.02 15.43
December 24.27 11.86
     
Annual Sum or Average 25.83 21.71
Minimum of Months 24.27 11.86
Maximum of Months 27.11 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 14.83
February 24.08 12.72
March 24.07 15.42
April 24.36 23.31
May 24.38 26.31
June 24.42 31.20
July 24.40 30.42
August 24.41 29.82
September 24.41 27.75
October 24.34 20.87
November 24.20 15.43
December 23.94 11.86
     
Annual Sum or Average 24.27 21.71
Minimum of Months 23.94 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 14.83
February 23.52 12.72
March 23.75 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.77 15.43
December 23.08 11.86
     
Annual Sum or Average 24.03 21.71
Minimum of Months 23.08 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 14.83
February 24.03 12.72
March 24.06 15.42
April 24.38 23.31
May 24.39 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.36 20.87
November 24.16 15.43
December 23.90 11.86
     
Annual Sum or Average 24.26 21.71
Minimum of Months 23.90 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.60 14.83
February 23.42 12.72
March 23.73 15.42
April 24.37 23.31
May 24.39 26.31
June 24.42 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.67 15.43
December 23.01 11.86
     
Annual Sum or Average 24.00 21.71
Minimum of Months 23.01 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.66 14.83
February 23.50 12.72
March 23.71 15.42
April 24.34 23.31
May 24.38 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.19 20.87
November 23.71 15.43
December 23.06 11.86
     
Annual Sum or Average 24.02 21.71
Minimum of Months 23.06 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.65 14.83
February 23.49 12.72
March 23.71 15.42
April 24.34 23.31
May 24.38 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.70 15.43
December 23.05 11.86
     
Annual Sum or Average 24.02 21.71
Minimum of Months 23.05 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 14.83
February 24.19 12.72
March 24.15 15.42
April 24.36 23.31
May 24.38 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.47 27.75
October 24.44 20.87
November 24.31 15.43
December 24.16 11.86
     
Annual Sum or Average 24.34 21.71
Minimum of Months 24.15 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.38 14.83
February 24.19 12.72
March 24.15 15.42
April 24.36 23.31
May 24.38 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.47 27.75
October 24.44 20.87
November 24.31 15.43
December 24.16 11.86
     
Annual Sum or Average 24.34 21.71
Minimum of Months 24.15 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.40 14.83
February 25.01 12.72
March 25.33 15.42
April 26.46 23.31
May 26.67 26.31
June 27.09 31.20
July 26.96 30.42
August 26.90 29.82
September 26.76 27.75
October 26.18 20.87
November 25.47 15.43
December 24.80 11.86
     
Annual Sum or Average 26.09 21.71
Minimum of Months 24.80 11.86
Maximum of Months 27.09 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 14.83
February 24.10 12.72
March 24.07 15.42
April 24.36 23.31
May 24.38 26.31
June 24.42 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.34 20.87
November 24.20 15.43
December 23.96 11.86
     
Annual Sum or Average 24.27 21.71
Minimum of Months 23.96 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.70 14.83
February 23.58 12.72
March 23.76 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.79 15.43
December 23.13 11.86
     
Annual Sum or Average 24.05 21.71
Minimum of Months 23.13 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 14.83
February 24.04 12.72
March 24.05 15.42
April 24.38 23.31
May 24.39 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.36 20.87
November 24.16 15.43
December 23.91 11.86
     
Annual Sum or Average 24.26 21.71
Minimum of Months 23.91 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.63 14.83
February 23.48 12.72
March 23.75 15.42
April 24.37 23.31
May 24.39 26.31
June 24.43 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.69 15.43
December 23.06 11.86
     
Annual Sum or Average 24.02 21.71
Minimum of Months 23.06 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.72 14.83
February 23.60 12.72
March 23.76 15.42
April 24.34 23.31
May 24.38 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.76 15.43
December 23.14 11.86
     
Annual Sum or Average 24.05 21.71
Minimum of Months 23.14 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 14.83
February 23.60 12.72
March 23.76 15.42
April 24.34 23.31
May 24.38 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.75 15.43
December 23.13 11.86
     
Annual Sum or Average 24.05 21.71
Minimum of Months 23.13 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 14.83
February 24.22 12.72
March 24.16 15.42
April 24.36 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.44 20.87
November 24.32 15.43
December 24.18 11.86
     
Annual Sum or Average 24.35 21.71
Minimum of Months 24.16 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 14.83
February 24.22 12.72
March 24.16 15.42
April 24.36 23.31
May 24.38 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.44 20.87
November 24.32 15.43
December 24.18 11.86
     
Annual Sum or Average 24.35 21.71
Minimum of Months 24.16 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.58 14.83
February 25.23 12.72
March 25.50 15.42
April 26.58 23.31
May 26.78 26.31
June 27.17 31.20
July 27.03 30.42
August 26.97 29.82
September 26.84 27.75
October 26.30 20.87
November 25.64 15.43
December 25.00 11.86
     
Annual Sum or Average 26.22 21.71
Minimum of Months 25.00 11.86
Maximum of Months 27.17 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 14.83
February 24.11 12.72
March 24.07 15.42
April 24.36 23.31
May 24.38 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.34 20.87
November 24.20 15.43
December 23.97 11.86
     
Annual Sum or Average 24.28 21.71
Minimum of Months 23.97 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.72 14.83
February 23.60 12.72
March 23.77 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.80 15.43
December 23.16 11.86
     
Annual Sum or Average 24.06 21.71
Minimum of Months 23.16 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 14.83
February 24.05 12.72
March 24.05 15.42
April 24.38 23.31
May 24.39 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.35 20.87
November 24.16 15.43
December 23.92 11.86
     
Annual Sum or Average 24.26 21.71
Minimum of Months 23.92 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.65 14.83
February 23.51 12.72
March 23.75 15.42
April 24.37 23.31
May 24.39 26.31
June 24.43 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.20 20.87
November 23.70 15.43
December 23.09 11.86
     
Annual Sum or Average 24.03 21.71
Minimum of Months 23.09 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.75 14.83
February 23.66 12.72
March 23.78 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.21 20.87
November 23.79 15.43
December 23.20 11.86
     
Annual Sum or Average 24.07 21.71
Minimum of Months 23.20 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 14.83
February 23.65 12.72
March 23.78 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.42 30.42
August 24.40 29.82
September 24.40 27.75
October 24.21 20.87
November 23.78 15.43
December 23.19 11.86
     
Annual Sum or Average 24.06 21.71
Minimum of Months 23.19 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 14.83
February 24.23 12.72
March 24.17 15.42
April 24.36 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.44 20.87
November 24.32 15.43
December 24.20 11.86
     
Annual Sum or Average 24.35 21.71
Minimum of Months 24.17 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 14.83
February 24.23 12.72
March 24.17 15.42
April 24.36 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.44 20.87
November 24.32 15.43
December 24.20 11.86
     
Annual Sum or Average 24.35 21.71
Minimum of Months 24.17 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.21 14.83
February 25.87 12.72
March 26.11 15.42
April 27.17 23.31
May 27.37 26.31
June 27.75 31.20
July 27.61 30.42
August 27.55 29.82
September 27.43 27.75
October 26.90 20.87
November 26.26 15.43
December 25.65 11.86
     
Annual Sum or Average 26.83 21.71
Minimum of Months 25.65 11.86
Maximum of Months 27.75 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.17 14.83
February 24.06 12.72
March 24.02 15.42
April 24.36 23.31
May 24.38 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.32 20.87
November 24.17 15.43
December 23.92 11.86
     
Annual Sum or Average 24.25 21.71
Minimum of Months 23.92 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.64 14.83
February 23.49 12.72
March 23.69 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.17 20.87
November 23.72 15.43
December 23.07 11.86
     
Annual Sum or Average 24.02 21.71
Minimum of Months 23.07 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.13 14.83
February 23.98 12.72
March 24.00 15.42
April 24.37 23.31
May 24.39 26.31
June 24.40 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.34 20.87
November 24.12 15.43
December 23.88 11.86
     
Annual Sum or Average 24.24 21.71
Minimum of Months 23.88 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.56 14.83
February 23.39 12.72
March 23.67 15.42
April 24.36 23.31
May 24.39 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.17 20.87
November 23.62 15.43
December 23.00 11.86
     
Annual Sum or Average 23.99 21.71
Minimum of Months 23.00 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 14.83
February 23.55 12.72
March 23.69 15.42
April 24.34 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.18 20.87
November 23.71 15.43
December 23.10 11.86
     
Annual Sum or Average 24.03 21.71
Minimum of Months 23.10 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.66 14.83
February 23.54 12.72
March 23.69 15.42
April 24.34 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.18 20.87
November 23.70 15.43
December 23.10 11.86
     
Annual Sum or Average 24.02 21.71
Minimum of Months 23.10 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 14.83
February 24.19 12.72
March 24.12 15.42
April 24.35 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.42 20.87
November 24.29 15.43
December 24.16 11.86
     
Annual Sum or Average 24.33 21.71
Minimum of Months 24.12 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.36 14.83
February 24.19 12.72
March 24.12 15.42
April 24.35 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.46 27.75
October 24.42 20.87
November 24.29 15.43
December 24.16 11.86
     
Annual Sum or Average 24.33 21.71
Minimum of Months 24.12 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.54 14.83
February 25.18 12.72
March 25.44 15.42
April 26.56 23.31
May 26.77 26.31
June 27.17 31.20
July 27.02 30.42
August 26.96 29.82
September 26.83 27.75
October 26.27 20.87
November 25.59 15.43
December 24.97 11.86
     
Annual Sum or Average 26.20 21.71
Minimum of Months 24.97 11.86
Maximum of Months 27.17 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.15 14.83
February 24.01 12.72
March 23.98 15.42
April 24.35 23.31
May 24.38 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.31 20.87
November 24.14 15.43
December 23.89 11.86
     
Annual Sum or Average 24.24 21.71
Minimum of Months 23.89 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.58 14.83
February 23.39 12.72
March 23.62 15.42
April 24.34 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.14 20.87
November 23.66 15.43
December 23.01 11.86
     
Annual Sum or Average 23.99 21.71
Minimum of Months 23.01 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.10 14.83
February 23.93 12.72
March 23.96 15.42
April 24.37 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.32 20.87
November 24.09 15.43
December 23.84 11.86
     
Annual Sum or Average 24.22 21.71
Minimum of Months 23.84 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 14.83
February 23.30 12.72
March 23.61 15.42
April 24.35 23.31
May 24.39 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.40 27.75
October 24.15 20.87
November 23.55 15.43
December 22.94 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 22.94 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.61 14.83
February 23.45 12.72
March 23.63 15.42
April 24.33 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.15 20.87
November 23.65 15.43
December 23.04 11.86
     
Annual Sum or Average 23.99 21.71
Minimum of Months 23.04 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.60 14.83
February 23.45 12.72
March 23.63 15.42
April 24.33 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.15 20.87
November 23.64 15.43
December 23.03 11.86
     
Annual Sum or Average 23.99 21.71
Minimum of Months 23.03 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 14.83
February 24.16 12.72
March 24.09 15.42
April 24.35 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.45 27.75
October 24.40 20.87
November 24.26 15.43
December 24.13 11.86
     
Annual Sum or Average 24.32 21.71
Minimum of Months 24.09 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.34 14.83
February 24.15 12.72
March 24.09 15.42
April 24.35 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.45 27.75
October 24.40 20.87
November 24.26 15.43
December 24.13 11.86
     
Annual Sum or Average 24.32 21.71
Minimum of Months 24.09 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.39 14.83
February 25.01 12.72
March 25.29 15.42
April 26.47 23.31
May 26.69 26.31
June 27.09 31.20
July 26.95 30.42
August 26.89 29.82
September 26.75 27.75
October 26.15 20.87
November 25.44 15.43
December 24.82 11.86
     
Annual Sum or Average 26.08 21.71
Minimum of Months 24.82 11.86
Maximum of Months 27.09 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.12 14.83
February 23.96 12.72
March 23.94 15.42
April 24.35 23.31
May 24.38 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.29 20.87
November 24.11 15.43
December 23.85 11.86
     
Annual Sum or Average 24.22 21.71
Minimum of Months 23.85 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.52 14.83
February 23.31 12.72
March 23.57 15.42
April 24.34 23.31
May 24.39 26.31
June 24.46 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 24.12 20.87
November 23.61 15.43
December 22.95 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 22.95 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.07 14.83
February 23.88 12.72
March 23.92 15.42
April 24.36 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.43 27.75
October 24.31 20.87
November 24.06 15.43
December 23.81 11.86
     
Annual Sum or Average 24.21 21.71
Minimum of Months 23.81 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.44 14.83
February 23.22 12.72
March 23.55 15.42
April 24.35 23.31
May 24.39 26.31
June 24.44 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 24.13 20.87
November 23.50 15.43
December 22.88 11.86
     
Annual Sum or Average 23.93 21.71
Minimum of Months 22.88 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.55 14.83
February 23.36 12.72
March 23.56 15.42
April 24.33 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.13 20.87
November 23.59 15.43
December 22.97 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 22.97 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.54 14.83
February 23.36 12.72
March 23.56 15.42
April 24.33 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.13 20.87
November 23.58 15.43
December 22.97 11.86
     
Annual Sum or Average 23.96 21.71
Minimum of Months 22.97 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 14.83
February 24.12 12.72
March 24.05 15.42
April 24.34 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.45 27.75
October 24.39 20.87
November 24.24 15.43
December 24.10 11.86
     
Annual Sum or Average 24.30 21.71
Minimum of Months 24.05 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 14.83
February 24.12 12.72
March 24.05 15.42
April 24.35 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.45 27.75
October 24.39 20.87
November 24.24 15.43
December 24.10 11.86
     
Annual Sum or Average 24.30 21.71
Minimum of Months 24.05 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.30 14.83
February 24.90 12.72
March 25.20 15.42
April 26.45 23.31
May 26.68 26.31
June 27.10 31.20
July 26.96 30.42
August 26.89 29.82
September 26.75 27.75
October 26.11 20.87
November 25.36 15.43
December 24.72 11.86
     
Annual Sum or Average 26.04 21.71
Minimum of Months 24.72 11.86
Maximum of Months 27.10 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.07 14.83
February 23.88 12.72
March 23.88 15.42
April 24.34 23.31
May 24.38 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.27 20.87
November 24.06 15.43
December 23.78 11.86
     
Annual Sum or Average 24.19 21.71
Minimum of Months 23.78 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.44 14.83
February 23.19 12.72
March 23.50 15.42
April 24.33 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 24.08 20.87
November 23.54 15.43
December 22.87 11.86
     
Annual Sum or Average 23.92 21.71
Minimum of Months 22.87 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.02 14.83
February 23.79 12.72
March 23.86 15.42
April 24.36 23.31
May 24.38 26.31
June 24.41 31.20
July 24.40 30.42
August 24.41 29.82
September 24.42 27.75
October 24.28 20.87
November 24.01 15.43
December 23.73 11.86
     
Annual Sum or Average 24.18 21.71
Minimum of Months 23.73 11.86
Maximum of Months 24.42 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.36 14.83
February 23.11 12.72
March 23.49 15.42
April 24.35 23.31
May 24.39 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 24.10 20.87
November 23.42 15.43
December 22.79 11.86
     
Annual Sum or Average 23.89 21.71
Minimum of Months 22.79 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.46 14.83
February 23.23 12.72
March 23.49 15.42
April 24.32 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.09 20.87
November 23.51 15.43
December 22.87 11.86
     
Annual Sum or Average 23.92 21.71
Minimum of Months 22.87 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.45 14.83
February 23.23 12.72
March 23.49 15.42
April 24.33 23.31
May 24.38 26.31
June 24.46 31.20
July 24.42 30.42
August 24.40 29.82
September 24.39 27.75
October 24.09 20.87
November 23.50 15.43
December 22.87 11.86
     
Annual Sum or Average 23.92 21.71
Minimum of Months 22.87 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 14.83
February 24.04 12.72
March 23.99 15.42
April 24.34 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.44 27.75
October 24.35 20.87
November 24.19 15.43
December 24.02 11.86
     
Annual Sum or Average 24.27 21.71
Minimum of Months 23.99 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 14.83
February 24.04 12.72
March 23.99 15.42
April 24.34 23.31
May 24.37 26.31
June 24.41 31.20
July 24.40 30.42
August 24.42 29.82
September 24.44 27.75
October 24.35 20.87
November 24.18 15.43
December 24.02 11.86
     
Annual Sum or Average 24.27 21.71
Minimum of Months 23.99 11.86
Maximum of Months 24.44 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.17 14.83
February 24.74 12.72
March 25.10 15.42
April 26.49 23.31
May 26.76 26.31
June 27.23 31.20
July 27.08 30.42
August 27.01 29.82
September 26.84 27.75
October 26.09 20.87
November 25.24 15.43
December 24.55 11.86
     
Annual Sum or Average 26.03 21.71
Minimum of Months 24.55 11.86
Maximum of Months 27.23 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.63 14.83
February 23.48 12.72
March 23.57 15.42
April 24.26 23.31
May 24.35 26.31
June 24.43 31.20
July 24.40 30.42
August 24.41 29.82
September 24.40 27.75
October 24.10 20.87
November 23.71 15.43
December 23.36 11.86
     
Annual Sum or Average 24.01 21.71
Minimum of Months 23.36 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.15 14.83
February 22.99 12.72
March 23.30 15.42
April 24.24 23.31
May 24.36 26.31
June 24.46 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.91 20.87
November 23.30 15.43
December 22.75 11.86
     
Annual Sum or Average 23.81 21.71
Minimum of Months 22.75 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.59 14.83
February 23.41 12.72
March 23.55 15.42
April 24.28 23.31
May 24.36 26.31
June 24.40 31.20
July 24.40 30.42
August 24.41 29.82
September 24.41 27.75
October 24.10 20.87
November 23.66 15.43
December 23.33 11.86
     
Annual Sum or Average 24.00 21.71
Minimum of Months 23.33 11.86
Maximum of Months 24.41 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.12 14.83
February 22.91 12.72
March 23.30 15.42
April 24.26 23.31
May 24.36 26.31
June 24.45 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.93 20.87
November 23.20 15.43
December 22.70 11.86
     
Annual Sum or Average 23.79 21.71
Minimum of Months 22.70 11.86
Maximum of Months 24.45 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 14.83
February 22.96 12.72
March 23.27 15.42
April 24.24 23.31
May 24.36 26.31
June 24.47 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.92 20.87
November 23.24 15.43
December 22.68 11.86
     
Annual Sum or Average 23.79 21.71
Minimum of Months 22.68 11.86
Maximum of Months 24.47 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.13 14.83
February 22.96 12.72
March 23.27 15.42
April 24.24 23.31
May 24.36 26.31
June 24.46 31.20
July 24.41 30.42
August 24.40 29.82
September 24.39 27.75
October 23.92 20.87
November 23.23 15.43
December 22.67 11.86
     
Annual Sum or Average 23.79 21.71
Minimum of Months 22.67 11.86
Maximum of Months 24.46 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 14.83
February 23.66 12.72
March 23.68 15.42
April 24.27 23.31
May 24.34 26.31
June 24.40 31.20
July 24.40 30.42
August 24.41 29.82
September 24.43 27.75
October 24.19 20.87
November 23.86 15.43
December 23.55 11.86
     
Annual Sum or Average 24.09 21.71
Minimum of Months 23.55 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 14.83
February 23.66 12.72
March 23.68 15.42
April 24.27 23.31
May 24.34 26.31
June 24.40 31.20
July 24.40 30.42
August 24.41 29.82
September 24.43 27.75
October 24.19 20.87
November 23.85 15.43
December 23.54 11.86
     
Annual Sum or Average 24.09 21.71
Minimum of Months 23.54 11.86
Maximum of Months 24.43 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2018-10-19 09:40:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.32 14.83
February 24.85 12.72
March 25.37 15.42
April 27.15 23.31
May 27.54 26.31
June 28.22 31.20
July 28.05 30.42
August 27.94 29.82
September 27.67 27.75
October 26.53 20.87
November 25.44 15.43
December 24.59 11.86
     
Annual Sum or Average 26.56 21.71
Minimum of Months 24.59 11.86
Maximum of Months 28.22 31.20



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:11

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.253561E+12 158613.452 31-JAN-18:15 22204.399 56867.515 24420.975 0.000 40235.446 10720.100 1697.548 1321.833 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.210048E+12 131659.958 24-FEB-18:15 22204.399 56867.515 24420.975 0.000 13965.709 10720.100 1697.548 638.076 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.242471E+12 163121.301 18-MAR-17:30 22204.399 56867.515 24420.975 0.000 54979.731 0.000 1697.548 1805.244 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.297707E+12 178264.745 14-APR-17:30 22204.399 56867.515 24420.975 0.000 69739.737 0.000 1697.548 2188.683 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.326098E+12 182337.922 31-MAY-17:30 22204.399 56867.515 24420.975 0.000 73784.531 0.000 1697.548 2217.065 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.347719E+12 186660.914 16-JUN-19:30 25049.151 49704.829 24420.975 0.000 71861.983 10720.100 1697.548 2260.757 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.361125E+12 185430.477 20-JUL-17:15 22204.399 56867.515 24420.975 0.000 76405.138 0.000 1697.548 2689.266 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.356011E+12 185316.091 25-AUG-17:15 22204.399 56867.515 24420.975 0.000 76488.495 0.000 1697.548 2491.523 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.334173E+12 183900.892 08-SEP-17:15 22204.399 56867.515 24420.975 0.000 74843.898 0.000 1697.548 2720.921 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.288840E+12 178566.753 06-OCT-17:00 22204.399 56867.515 24420.975 0.000 59478.991 10720.100 1697.548 2031.337 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.243309E+12 165256.282 01-NOV-16:45 18221.747 56933.809 24420.975 0.000 60761.638 0.000 1697.548 2072.123 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.244380E+12 142684.326 22-DEC-17:30 18221.747 56933.809 24420.975 0.000 28428.869 10720.100 1697.548 1112.837 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.350544E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.210048E+12 131659.958   18221.747 49704.829 24420.975 0.000 13965.709 0.000 1697.548 638.076 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.361125E+12 186660.914   25049.151 56933.809 24420.975 0.000 76488.495 10720.100 1697.548 2720.921 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 09:40:11

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.907477E+11 102796.054 01-JAN-07:15 0.000 0.000 0.000 102796.054 75028.870 75028.870 27767.184
February 0.807615E+11 81235.575 02-FEB-07:45 0.000 0.000 0.000 81235.575 81235.575 81235.575 0.000
March 0.852066E+11 80341.884 03-MAR-07:45 0.000 0.000 0.000 80341.884 80341.884 80341.884 0.000
April 0.759477E+11 78607.652 02-APR-06:45 0.000 0.000 0.000 78607.652 78607.652 78607.652 0.000
May 0.712227E+11 76636.880 01-MAY-06:45 0.000 0.000 0.000 76636.880 76636.880 76636.880 0.000
June 0.632265E+11 68778.479 04-JUN-06:00 0.000 0.000 0.000 68778.479 68778.479 68778.479 0.000
July 0.624484E+11 56563.379 11-JUL-06:45 0.000 0.000 0.000 56563.379 56563.379 56563.379 0.000
August 0.633171E+11 63989.279 27-AUG-06:00 0.000 0.000 0.000 63989.279 63989.279 63989.279 0.000
September 0.655347E+11 75580.302 30-SEP-06:00 0.000 0.000 0.000 75580.302 75580.302 75580.302 0.000
October 0.744813E+11 77610.423 31-OCT-06:00 0.000 0.000 0.000 77610.423 77610.423 77610.423 0.000
November 0.790426E+11 79221.540 27-NOV-07:30 0.000 0.000 0.000 79221.540 79221.540 79221.540 0.000
December 0.899754E+11 105770.419 17-DEC-07:30 0.000 0.000 0.000 105770.419 78424.236 78424.236 27346.183
                     
Annual Sum or Average 0.901912E+12     0.000 0.000 0.000        
Minimum of Months 0.624484E+11 56563.379   0.000 0.000 0.000 56563.379 56563.379 56563.379 0.000
Maximum of Months 0.907477E+11 105770.419   0.000 0.000 0.000 105770.419 81235.575 81235.575 27767.184