Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2018-10-19 09:40:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 6579.21 | 839.56 | 931.91 |
Net Site Energy | 6579.21 | 839.56 | 931.91 |
Total Source Energy | 13680.19 | 1745.71 | 1937.73 |
Net Source Energy | 13680.19 | 1745.71 | 1937.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 544.10 | 1951.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 416.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 655.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 494.48 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1483.57 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3143.70 | 3435.51 | 0.00 | 0.00 | 0.00 | 5272.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1951.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 544.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 67.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 167.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 655.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 494.48 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1483.57 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 82.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 199.47 | 486.62 | 0.00 | 0.00 | 0.00 | 0.75 |
Other | 160.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 445.29 | 486.62 | 0.00 | 0.00 | 0.00 | 0.75 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 179.70 | 438.40 | 0.00 | 0.00 | 0.00 | 0.67 |
Other | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 401.16 | 438.40 | 0.00 | 0.00 | 0.00 | 0.67 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3143.70 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3143.70 | 100.00 |
Total On-Site and Utility Electric Sources | 3143.70 | 100.00 |
Total Electricity End Uses | 3143.70 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5272.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5272.99 | 100.00 |
Total Water End Uses | 5272.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 109.00 |
Time Setpoint Not Met During Occupied Cooling | 25.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4098.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 09:37 |
RunPeriod | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 23.8959 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 8.5250 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 17.0500 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 14.4236 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 14.4236 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 8.5250 | 263.6661 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 14.0302 | 39.48 | 8.6219 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 14.5420 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 9.3775 | 26.3666 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JAN-23:00 | 29-JAN-08:15 | - | - | - | 11-JUL-17:30 |
Heating | 139844.76 | 221268.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9687.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 29146.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20785.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1443.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 95799.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 212165.24 | 317067.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 221268.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 8336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1350.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 29146.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 20785.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1443.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 95799.50 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1723.16 | 2115.89 | 0.00 | 0.00 | 0.00 |
Cooling | 498.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1318.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 529.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3582.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2075.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 143.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 18.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1608.19 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9956.10 | 3724.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 244.08 | 299.71 | 0.00 | 0.00 | 0.00 |
Cooling | 70.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 74.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 227.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1410.23 | 527.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 244.08 | 299.71 | 0.00 | 0.00 | 0.00 |
Cooling | 70.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 74.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 507.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 227.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1410.23 | 527.50 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.42_SHGC_0.45 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.493 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.493 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.493 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.493 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 11.5174 | 88.25 | 1016.39 | GeneralLights | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.93 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 11.9479 | 88.25 | 1054.39 | GeneralLights-plugin | LTG_OFF_SCH | 56.26 | 168.00 | 55.46 | 0.0000 | Y | 10.98 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 8.5250 | 77.66 | 662.04 | GeneralLights-plugin | LTG_COR_SCH | 149.10 | 168.00 | 149.10 | 0.0000 | N | 18.53 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 2.9063 | 88.25 | 256.47 | GeneralLights-plugin | LTG_APT_SCH | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.49 |
Interior Lighting Total | 7.3426 | 14974.03 | 109947.72 | 416.41 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10720.10 | AstronomicalClock | - | 83.06 | 83.06 | 167.13 | |
Exterior Lighting Total | 10720.10 | 167.13 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 253505.19 | 0.80 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 202804.15 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3321.35 | 2582.08 | 739.27 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2312.85 | 1812.32 | 500.53 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4658.89 | 3623.19 | 1035.70 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2157.41 | 1712.59 | 444.82 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1441.61 | 1169.69 | 271.91 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1437.68 | 1168.03 | 269.65 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2548.65 | 1975.51 | 573.14 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2624.50 | 2034.02 | 590.48 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4424.22 | 3437.60 | 986.62 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3209.61 | 2507.62 | 701.99 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4525.10 | 3507.25 | 1017.85 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2563.62 | 2020.97 | 542.65 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1744.24 | 1388.34 | 355.90 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1723.24 | 1372.20 | 351.03 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3439.33 | 2664.76 | 774.58 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3469.18 | 2687.77 | 781.41 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4447.24 | 3457.72 | 989.52 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3258.29 | 2545.70 | 712.59 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4322.34 | 3353.21 | 969.13 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2615.20 | 2063.04 | 552.17 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1808.65 | 1439.32 | 369.32 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1788.03 | 1423.48 | 364.55 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3492.08 | 2706.85 | 785.23 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3507.91 | 2719.06 | 788.85 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4447.08 | 3459.37 | 987.71 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3268.82 | 2554.69 | 714.12 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4303.23 | 3340.23 | 963.00 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2619.28 | 2067.87 | 551.41 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1821.26 | 1450.14 | 371.12 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1800.65 | 1434.30 | 366.35 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3501.07 | 2714.85 | 786.22 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3515.00 | 2725.59 | 789.41 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4475.81 | 3482.98 | 992.83 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3301.71 | 2581.47 | 720.24 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4331.61 | 3363.56 | 968.05 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2650.74 | 2093.53 | 557.21 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1858.89 | 1479.98 | 378.91 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1838.32 | 1464.16 | 374.15 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3536.05 | 2742.71 | 793.35 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3549.67 | 2753.21 | 796.46 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4415.38 | 3437.62 | 977.76 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3244.27 | 2538.56 | 705.72 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4273.40 | 3319.89 | 953.51 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2594.37 | 2051.18 | 543.19 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1808.02 | 1441.68 | 366.34 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1787.53 | 1425.93 | 361.60 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3480.71 | 2700.77 | 779.94 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3494.29 | 2711.24 | 783.05 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4388.88 | 3418.27 | 970.61 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3221.04 | 2521.79 | 699.25 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4248.77 | 3301.97 | 946.80 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2571.38 | 2034.45 | 536.93 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1789.79 | 1428.36 | 361.43 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1769.38 | 1412.67 | 356.71 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3458.56 | 2684.34 | 774.22 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.12 | 2694.80 | 777.32 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4379.36 | 3411.92 | 967.45 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3215.70 | 2518.68 | 697.02 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4240.65 | 3296.67 | 943.98 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2565.15 | 2030.56 | 534.59 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1789.86 | 1429.03 | 360.83 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1769.56 | 1413.42 | 356.14 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3452.78 | 2680.48 | 772.31 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3466.35 | 2690.94 | 775.41 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4469.29 | 3482.19 | 987.10 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3312.41 | 2593.97 | 718.44 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4314.83 | 3354.80 | 960.03 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2594.71 | 2054.23 | 540.48 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1878.10 | 1497.40 | 380.70 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1856.97 | 1481.16 | 375.82 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3515.55 | 2729.44 | 786.11 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3530.78 | 2741.19 | 789.60 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5312.15 | 4129.05 | 1183.09 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3915.30 | 3059.09 | 856.20 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5060.75 | 3931.15 | 1129.60 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3028.56 | 2383.52 | 645.04 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2085.92 | 1654.19 | 431.73 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2043.06 | 1621.23 | 421.83 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4462.20 | 3460.15 | 1002.05 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4477.19 | 3471.71 | 1005.48 | 0.78 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3321.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2312.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4658.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2157.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1441.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1437.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2548.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2624.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4424.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3209.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4525.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2563.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1744.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1723.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3439.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3469.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4447.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3258.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4322.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2615.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1808.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1788.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3492.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3507.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4447.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3268.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4303.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2619.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1821.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1800.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3501.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3515.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4475.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3301.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4331.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2650.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1858.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1838.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3536.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3549.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4415.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3244.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4273.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2594.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1808.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1787.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3480.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3494.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4388.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3221.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4248.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2571.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1789.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1769.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3458.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4379.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3215.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4240.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2565.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1789.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1769.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3452.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3466.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4469.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3312.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4314.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2594.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1878.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1856.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3515.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3530.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5312.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3915.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5060.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3028.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2085.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2043.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4462.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4477.19 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 5502.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 5512.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 6951.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 5510.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 4507.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 4507.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 4495.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 4504.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 4786.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 4780.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 4807.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 4778.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 3625.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 3625.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 3634.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 3636.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 4612.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 4608.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 4611.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 4605.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 3450.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 3450.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 3455.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 3455.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 4585.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 4582.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 4581.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 4578.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 3416.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 3416.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 3421.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 3421.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 4554.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 4550.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 4550.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 4546.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 3382.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 3382.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 3388.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 3388.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 4604.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 4600.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 4600.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 4596.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 3425.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 3425.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 3430.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 3430.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 4628.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 4624.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 4624.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 4619.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 3445.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 3445.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 3451.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 3451.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 4671.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 4665.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 4666.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 4660.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 3485.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 3485.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 3492.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 3492.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 4948.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 4938.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 4944.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 4933.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 3745.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 3745.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 3756.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 3756.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 6347.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 6348.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 6343.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 6343.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 5226.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 5226.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 5223.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 5223.42 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.36 | 1120.11 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.17 | 192.50 | 1120.11 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 376.64 | 1120.11 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 182.12 | 1120.11 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.58 | 1120.11 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.12 | 130.58 | 1120.11 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.18 | 204.42 | 1120.11 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 210.55 | 1120.11 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 359.49 | 1120.11 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 266.20 | 1120.11 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.30 | 1120.11 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 214.17 | 1120.11 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 151.47 | 1120.11 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.13 | 149.78 | 1120.11 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 276.76 | 1120.11 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.17 | 1120.11 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 361.72 | 1120.11 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.90 | 1120.11 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 349.28 | 1120.11 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 218.70 | 1120.11 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.87 | 1120.11 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 155.22 | 1120.11 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.24 | 1120.11 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.52 | 1120.11 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 361.99 | 1120.11 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 270.58 | 1120.11 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 348.01 | 1120.11 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 219.29 | 1120.11 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 158.06 | 1120.11 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.40 | 1120.11 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 282.13 | 1120.11 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.26 | 1120.11 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.53 | 1120.11 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 273.45 | 1120.11 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 350.53 | 1120.11 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.20 | 222.05 | 1120.11 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 161.22 | 1120.11 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 159.57 | 1120.11 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.09 | 1120.11 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 286.19 | 1120.11 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 359.84 | 1120.11 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 269.03 | 1120.11 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 346.01 | 1120.11 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 217.66 | 1120.11 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 157.26 | 1120.11 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 155.61 | 1120.11 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.74 | 1120.11 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.83 | 1120.11 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 357.87 | 1120.11 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.33 | 1120.11 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 344.19 | 1120.11 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 215.96 | 1120.11 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 155.90 | 1120.11 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 154.26 | 1120.11 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.05 | 1120.11 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.14 | 1120.11 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 357.25 | 1120.11 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 267.05 | 1120.11 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 343.68 | 1120.11 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 215.60 | 1120.11 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 156.00 | 1120.11 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 154.37 | 1120.11 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 278.67 | 1120.11 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 279.77 | 1120.11 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.66 | 1120.11 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 274.98 | 1120.11 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 349.82 | 1120.11 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.19 | 218.12 | 1120.11 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.15 | 163.18 | 1120.11 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.14 | 161.48 | 1120.11 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 283.83 | 1120.11 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 285.06 | 1120.11 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 431.71 | 1120.11 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 322.06 | 1120.11 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 410.28 | 1120.11 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.22 | 251.55 | 1120.11 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 178.87 | 1120.11 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.16 | 175.43 | 1120.11 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.44 | 1120.11 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 361.65 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.0055 | 1406.33 | 255050.01 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2519.32 | 3023.19 | 0.200 | 0.240 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
G NW APARTMENT | 1800.47 | 2160.56 | 0.143 | 0.172 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
OFFICE | 3522.74 | 4227.29 | 0.280 | 0.336 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40 | 0.00698 |
G NE APARTMENT | 1368.55 | 1642.26 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
G N1 APARTMENT | 933.23 | 1119.88 | 0.074 | 0.089 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
G N2 APARTMENT | 915.67 | 1098.81 | 0.073 | 0.087 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
G S1 APARTMENT | 1911.94 | 2294.33 | 0.152 | 0.183 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
G S2 APARTMENT | 1969.27 | 2363.13 | 0.157 | 0.188 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F2 SW APARTMENT | 3362.34 | 4034.80 | 0.267 | 0.321 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F2 NW APARTMENT | 2489.75 | 2987.70 | 0.198 | 0.238 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 22.86 | 0.00698 |
F2 SE APARTMENT | 3416.68 | 4100.02 | 0.272 | 0.326 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F2 NE APARTMENT | 2003.17 | 2403.80 | 0.159 | 0.191 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F2 N1 APARTMENT | 1416.65 | 1699.98 | 0.113 | 0.135 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F2 N2 APARTMENT | 1400.88 | 1681.06 | 0.111 | 0.134 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F2 S1 APARTMENT | 2588.48 | 3106.18 | 0.206 | 0.247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F2 S2 APARTMENT | 2611.04 | 3133.25 | 0.208 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F3 SW APARTMENT | 3383.18 | 4059.82 | 0.269 | 0.323 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F3 NW APARTMENT | 2524.38 | 3029.26 | 0.201 | 0.241 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 23.14 | 0.00698 |
F3 SE APARTMENT | 3266.81 | 3920.17 | 0.260 | 0.312 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F3 NE APARTMENT | 2045.48 | 2454.58 | 0.163 | 0.195 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F3 N1 APARTMENT | 1467.19 | 1760.63 | 0.117 | 0.140 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F3 N2 APARTMENT | 1451.70 | 1742.04 | 0.115 | 0.139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F3 S1 APARTMENT | 2630.41 | 3156.49 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F3 S2 APARTMENT | 2642.37 | 3170.85 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F4 SW APARTMENT | 3385.65 | 4062.78 | 0.269 | 0.323 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F4 NW APARTMENT | 2530.69 | 3036.82 | 0.201 | 0.242 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F4 SE APARTMENT | 3254.92 | 3905.91 | 0.259 | 0.311 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F4 NE APARTMENT | 2051.01 | 2461.21 | 0.163 | 0.196 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F4 N1 APARTMENT | 1478.29 | 1773.95 | 0.118 | 0.141 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F4 N2 APARTMENT | 1462.80 | 1755.36 | 0.116 | 0.140 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F4 S1 APARTMENT | 2638.76 | 3166.51 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F4 S2 APARTMENT | 2649.28 | 3179.14 | 0.211 | 0.253 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
M SW APARTMENT | 3409.49 | 4091.39 | 0.271 | 0.325 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
M NW APARTMENT | 2557.60 | 3069.12 | 0.203 | 0.244 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
M SE APARTMENT | 3278.48 | 3934.18 | 0.261 | 0.313 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
M NE APARTMENT | 2076.82 | 2492.19 | 0.165 | 0.198 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
M N1 APARTMENT | 1507.89 | 1809.46 | 0.120 | 0.144 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
M N2 APARTMENT | 1492.42 | 1790.90 | 0.119 | 0.142 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
M S1 APARTMENT | 2666.47 | 3199.77 | 0.212 | 0.255 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
M S2 APARTMENT | 2676.77 | 3212.12 | 0.213 | 0.256 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F6 SW APARTMENT | 3365.61 | 4038.73 | 0.268 | 0.321 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F6 NW APARTMENT | 2516.19 | 3019.42 | 0.200 | 0.240 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F6 SE APARTMENT | 3236.25 | 3883.50 | 0.257 | 0.309 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F6 NE APARTMENT | 2035.82 | 2442.98 | 0.162 | 0.194 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F6 N1 APARTMENT | 1470.81 | 1764.97 | 0.117 | 0.140 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F6 N2 APARTMENT | 1455.41 | 1746.49 | 0.116 | 0.139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F6 S1 APARTMENT | 2625.72 | 3150.87 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F6 S2 APARTMENT | 2635.99 | 3163.19 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F7 SW APARTMENT | 3347.16 | 4016.59 | 0.266 | 0.319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F7 NW APARTMENT | 2500.30 | 3000.36 | 0.199 | 0.239 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F7 SE APARTMENT | 3219.19 | 3863.03 | 0.256 | 0.307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F7 NE APARTMENT | 2019.88 | 2423.85 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F7 N1 APARTMENT | 1458.10 | 1749.72 | 0.116 | 0.139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F7 N2 APARTMENT | 1442.76 | 1731.31 | 0.115 | 0.138 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F7 S1 APARTMENT | 2609.94 | 3131.93 | 0.208 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F7 S2 APARTMENT | 2620.18 | 3144.22 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F8 SW APARTMENT | 3341.39 | 4009.67 | 0.266 | 0.319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F8 NW APARTMENT | 2497.72 | 2997.26 | 0.199 | 0.238 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F8 SE APARTMENT | 3214.46 | 3857.35 | 0.256 | 0.307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F8 NE APARTMENT | 2016.49 | 2419.78 | 0.160 | 0.192 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F8 N1 APARTMENT | 1459.05 | 1750.85 | 0.116 | 0.139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F8 N2 APARTMENT | 1443.78 | 1732.54 | 0.115 | 0.138 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F8 S1 APARTMENT | 2606.43 | 3127.71 | 0.207 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F8 S2 APARTMENT | 2616.68 | 3140.02 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F9 SW APARTMENT | 3410.72 | 4092.86 | 0.271 | 0.326 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F9 NW APARTMENT | 2571.87 | 3086.25 | 0.205 | 0.245 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F9 SE APARTMENT | 3271.88 | 3926.25 | 0.260 | 0.312 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F9 NE APARTMENT | 2040.10 | 2448.12 | 0.162 | 0.195 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F9 N1 APARTMENT | 1526.16 | 1831.39 | 0.121 | 0.146 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F9 N2 APARTMENT | 1510.27 | 1812.32 | 0.120 | 0.144 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F9 S1 APARTMENT | 2654.68 | 3185.61 | 0.211 | 0.253 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F9 S2 APARTMENT | 2666.19 | 3199.43 | 0.212 | 0.254 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
T SW APARTMENT | 4037.79 | 4845.35 | 0.321 | 0.385 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 26.94 | 0.00698 |
T NW APARTMENT | 3012.23 | 3614.67 | 0.240 | 0.288 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
T SE APARTMENT | 3837.35 | 4604.82 | 0.305 | 0.366 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40 | 0.00698 |
T NE APARTMENT | 2352.72 | 2823.26 | 0.187 | 0.225 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 25.05 | 0.00698 |
T N1 APARTMENT | 1672.97 | 2007.56 | 0.133 | 0.160 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:45:00 | 21.61 | 0.00698 |
T N2 APARTMENT | 1640.71 | 1968.86 | 0.131 | 0.157 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:45:00 | 21.61 | 0.00698 |
T S1 APARTMENT | 3371.19 | 4045.43 | 0.268 | 0.322 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
T S2 APARTMENT | 3382.52 | 4059.03 | 0.269 | 0.323 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2990.42 | 3588.50 | 0.135 | 0.162 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G NW APARTMENT | 2998.67 | 3598.40 | 0.136 | 0.163 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
OFFICE | 3437.56 | 4125.07 | 0.155 | 0.186 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -41.90 | 0.00006 |
G NE APARTMENT | 2997.18 | 3596.62 | 0.135 | 0.163 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N1 APARTMENT | 2149.00 | 2578.80 | 0.097 | 0.117 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N2 APARTMENT | 2148.97 | 2578.76 | 0.097 | 0.117 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S1 APARTMENT | 2139.32 | 2567.18 | 0.097 | 0.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S2 APARTMENT | 2146.52 | 2575.83 | 0.097 | 0.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
F2 SW APARTMENT | 2385.01 | 2862.02 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 NW APARTMENT | 2380.22 | 2856.27 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 SE APARTMENT | 2403.10 | 2883.73 | 0.109 | 0.130 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 NE APARTMENT | 2377.88 | 2853.46 | 0.107 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 N1 APARTMENT | 1403.40 | 1684.08 | 0.063 | 0.076 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 N2 APARTMENT | 1403.35 | 1684.03 | 0.063 | 0.076 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 S1 APARTMENT | 1411.19 | 1693.42 | 0.064 | 0.077 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 S2 APARTMENT | 1412.36 | 1694.83 | 0.064 | 0.077 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 SW APARTMENT | 2237.80 | 2685.37 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 NW APARTMENT | 2234.78 | 2681.74 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 SE APARTMENT | 2237.06 | 2684.47 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 NE APARTMENT | 2232.00 | 2678.40 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 N1 APARTMENT | 1255.10 | 1506.12 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 N2 APARTMENT | 1255.04 | 1506.05 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 S1 APARTMENT | 1259.45 | 1511.34 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 S2 APARTMENT | 1259.57 | 1511.48 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 SW APARTMENT | 2214.88 | 2657.86 | 0.100 | 0.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 NW APARTMENT | 2212.27 | 2654.72 | 0.100 | 0.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 SE APARTMENT | 2211.98 | 2654.38 | 0.100 | 0.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 NE APARTMENT | 2209.17 | 2651.00 | 0.100 | 0.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 N1 APARTMENT | 1226.88 | 1472.26 | 0.055 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 N2 APARTMENT | 1226.82 | 1472.18 | 0.055 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 S1 APARTMENT | 1230.67 | 1476.81 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 S2 APARTMENT | 1230.63 | 1476.75 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M SW APARTMENT | 2188.85 | 2626.63 | 0.099 | 0.119 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M NW APARTMENT | 2185.12 | 2622.14 | 0.099 | 0.119 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M SE APARTMENT | 2185.52 | 2622.62 | 0.099 | 0.119 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M NE APARTMENT | 2181.76 | 2618.11 | 0.099 | 0.118 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M N1 APARTMENT | 1197.81 | 1437.37 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M N2 APARTMENT | 1197.74 | 1437.29 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M S1 APARTMENT | 1202.73 | 1443.28 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M S2 APARTMENT | 1202.67 | 1443.20 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 SW APARTMENT | 2230.89 | 2677.07 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 NW APARTMENT | 2227.62 | 2673.15 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 SE APARTMENT | 2227.31 | 2672.77 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 NE APARTMENT | 2224.04 | 2668.85 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 N1 APARTMENT | 1234.28 | 1481.13 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 N2 APARTMENT | 1234.20 | 1481.04 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 S1 APARTMENT | 1238.68 | 1486.41 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 S2 APARTMENT | 1238.60 | 1486.32 | 0.056 | 0.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 SW APARTMENT | 2251.45 | 2701.74 | 0.102 | 0.122 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 NW APARTMENT | 2247.61 | 2697.14 | 0.102 | 0.122 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 SE APARTMENT | 2247.68 | 2697.21 | 0.102 | 0.122 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 NE APARTMENT | 2243.84 | 2692.61 | 0.101 | 0.122 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 N1 APARTMENT | 1251.40 | 1501.68 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 N2 APARTMENT | 1251.32 | 1501.58 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 S1 APARTMENT | 1256.33 | 1507.60 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 S2 APARTMENT | 1256.25 | 1507.51 | 0.057 | 0.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 SW APARTMENT | 2287.44 | 2744.93 | 0.103 | 0.124 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 NW APARTMENT | 2282.75 | 2739.31 | 0.103 | 0.124 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 SE APARTMENT | 2283.51 | 2740.21 | 0.103 | 0.124 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 NE APARTMENT | 2278.81 | 2734.57 | 0.103 | 0.124 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 N1 APARTMENT | 1284.81 | 1541.77 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 N2 APARTMENT | 1284.73 | 1541.67 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 S1 APARTMENT | 1290.57 | 1548.69 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 S2 APARTMENT | 1290.49 | 1548.59 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 SW APARTMENT | 2522.41 | 3026.89 | 0.114 | 0.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 NW APARTMENT | 2513.87 | 3016.65 | 0.114 | 0.136 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 SE APARTMENT | 2518.28 | 3021.94 | 0.114 | 0.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 NE APARTMENT | 2509.74 | 3011.69 | 0.113 | 0.136 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 N1 APARTMENT | 1504.50 | 1805.40 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 N2 APARTMENT | 1504.42 | 1805.30 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 S1 APARTMENT | 1513.70 | 1816.44 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 S2 APARTMENT | 1513.62 | 1816.34 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T SW APARTMENT | 3705.38 | 4446.45 | 0.168 | 0.201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T NW APARTMENT | 3706.12 | 4447.34 | 0.168 | 0.201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T SE APARTMENT | 3701.36 | 4441.63 | 0.167 | 0.201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T NE APARTMENT | 3702.09 | 4442.51 | 0.167 | 0.201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T N1 APARTMENT | 2757.25 | 3308.70 | 0.125 | 0.150 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T N2 APARTMENT | 2757.16 | 3308.59 | 0.125 | 0.150 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T S1 APARTMENT | 2754.59 | 3305.51 | 0.125 | 0.149 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T S2 APARTMENT | 2754.50 | 3305.40 | 0.125 | 0.149 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.24 | 0.24 | 0.16 | 0.16 |
AIRLOOP G NW | 0.17 | 0.17 | 0.16 | 0.16 |
AIRLOOP OFFICE | 0.34 | 0.34 | 0.19 | 0.19 |
AIRLOOP G NE | 0.13 | 0.13 | 0.16 | 0.16 |
AIRLOOP G N1 | 0.09 | 0.09 | 0.12 | 0.12 |
AIRLOOP G N2 | 0.09 | 0.09 | 0.12 | 0.12 |
AIRLOOP G S1 | 0.18 | 0.18 | 0.12 | 0.12 |
AIRLOOP G S2 | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F2 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F2 NW | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP F2 SE | 0.33 | 0.33 | 0.13 | 0.13 |
AIRLOOP F2 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F2 N1 | 0.14 | 0.14 | 0.08 | 0.08 |
AIRLOOP F2 N2 | 0.13 | 0.13 | 0.08 | 0.08 |
AIRLOOP F2 S1 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F2 S2 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F3 SW | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP F3 NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F3 SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP F3 NE | 0.20 | 0.20 | 0.12 | 0.12 |
AIRLOOP F3 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F3 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F3 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F3 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F4 SW | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP F4 NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F4 SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP F4 NE | 0.20 | 0.20 | 0.12 | 0.12 |
AIRLOOP F4 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F4 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F4 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F4 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP M SW | 0.33 | 0.33 | 0.12 | 0.12 |
AIRLOOP M NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP M SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP M NE | 0.20 | 0.20 | 0.12 | 0.12 |
AIRLOOP M N1 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP M N2 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP M S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP M S2 | 0.26 | 0.26 | 0.07 | 0.07 |
AIRLOOP F6 SW | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP F6 NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F6 SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP F6 NE | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F6 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F6 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F6 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F6 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F7 SW | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP F7 NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F7 SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP F7 NE | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F7 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F7 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F7 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F7 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F8 SW | 0.32 | 0.32 | 0.12 | 0.12 |
AIRLOOP F8 NW | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP F8 SE | 0.31 | 0.31 | 0.12 | 0.12 |
AIRLOOP F8 NE | 0.19 | 0.19 | 0.12 | 0.12 |
AIRLOOP F8 N1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F8 N2 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP F8 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F8 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F9 SW | 0.33 | 0.33 | 0.14 | 0.14 |
AIRLOOP F9 NW | 0.25 | 0.25 | 0.14 | 0.14 |
AIRLOOP F9 SE | 0.31 | 0.31 | 0.14 | 0.14 |
AIRLOOP F9 NE | 0.19 | 0.19 | 0.14 | 0.14 |
AIRLOOP F9 N1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F9 N2 | 0.14 | 0.14 | 0.08 | 0.08 |
AIRLOOP F9 S1 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F9 S2 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP T SW | 0.39 | 0.39 | 0.20 | 0.20 |
AIRLOOP T NW | 0.29 | 0.29 | 0.20 | 0.20 |
AIRLOOP T SE | 0.37 | 0.37 | 0.20 | 0.20 |
AIRLOOP T NE | 0.22 | 0.22 | 0.20 | 0.20 |
AIRLOOP T N1 | 0.16 | 0.16 | 0.15 | 0.15 |
AIRLOOP T N2 | 0.16 | 0.16 | 0.15 | 0.15 |
AIRLOOP T S1 | 0.32 | 0.32 | 0.15 | 0.15 |
AIRLOOP T S2 | 0.32 | 0.32 | 0.15 | 0.15 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4178.50 | 6600.50 | 3063.00 |
G NW APARTMENT | 4312.25 | 7378.50 | 3675.75 |
OFFICE | 1245.75 | 1394.75 | 731.75 |
G NE APARTMENT | 4429.25 | 7228.75 | 3621.00 |
G N1 APARTMENT | 3411.50 | 7570.25 | 2979.00 |
G N2 APARTMENT | 3411.25 | 7555.25 | 2972.50 |
G S1 APARTMENT | 3292.00 | 6667.50 | 2286.50 |
G S2 APARTMENT | 3299.25 | 6600.25 | 2253.25 |
F2 SW APARTMENT | 4124.75 | 5569.75 | 2143.25 |
F2 NW APARTMENT | 4056.25 | 6511.75 | 2743.25 |
F2 SE APARTMENT | 4250.25 | 5420.75 | 2022.50 |
F2 NE APARTMENT | 4095.25 | 6395.25 | 2652.75 |
F2 N1 APARTMENT | 2291.00 | 6734.50 | 1181.00 |
F2 N2 APARTMENT | 2302.50 | 6711.00 | 1179.25 |
F2 S1 APARTMENT | 2642.50 | 5443.75 | 747.25 |
F2 S2 APARTMENT | 2661.50 | 5419.50 | 737.25 |
F3 SW APARTMENT | 4073.25 | 5413.50 | 1914.75 |
F3 NW APARTMENT | 3931.75 | 6286.50 | 2501.25 |
F3 SE APARTMENT | 4189.75 | 5333.50 | 1885.25 |
F3 NE APARTMENT | 3969.00 | 6189.75 | 2422.75 |
F3 N1 APARTMENT | 2116.25 | 6427.25 | 852.25 |
F3 N2 APARTMENT | 2121.50 | 6408.00 | 851.25 |
F3 S1 APARTMENT | 2607.25 | 5185.25 | 479.25 |
F3 S2 APARTMENT | 2618.75 | 5173.25 | 477.00 |
F4 SW APARTMENT | 4080.50 | 5391.50 | 1875.25 |
F4 NW APARTMENT | 3924.00 | 6204.00 | 2462.25 |
F4 SE APARTMENT | 4183.25 | 5323.50 | 1857.50 |
F4 NE APARTMENT | 3966.25 | 6133.00 | 2385.00 |
F4 N1 APARTMENT | 2118.75 | 6301.00 | 803.25 |
F4 N2 APARTMENT | 2127.25 | 6286.25 | 802.25 |
F4 S1 APARTMENT | 2642.50 | 5140.00 | 433.50 |
F4 S2 APARTMENT | 2653.50 | 5130.00 | 432.50 |
M SW APARTMENT | 4044.75 | 5385.75 | 1827.25 |
M NW APARTMENT | 3869.50 | 6192.25 | 2394.25 |
M SE APARTMENT | 4146.50 | 5317.25 | 1809.25 |
M NE APARTMENT | 3917.50 | 6117.75 | 2321.25 |
M N1 APARTMENT | 2067.75 | 6259.00 | 724.25 |
M N2 APARTMENT | 2079.75 | 6247.25 | 723.75 |
M S1 APARTMENT | 2630.50 | 5114.50 | 393.50 |
M S2 APARTMENT | 2636.75 | 5104.75 | 392.75 |
F6 SW APARTMENT | 4037.50 | 5467.00 | 1928.25 |
F6 NW APARTMENT | 3910.75 | 6327.25 | 2530.25 |
F6 SE APARTMENT | 4147.75 | 5396.50 | 1910.50 |
F6 NE APARTMENT | 3968.50 | 6229.00 | 2451.25 |
F6 N1 APARTMENT | 2094.75 | 6380.75 | 839.50 |
F6 N2 APARTMENT | 2102.50 | 6366.00 | 838.50 |
F6 S1 APARTMENT | 2570.25 | 5203.00 | 456.00 |
F6 S2 APARTMENT | 2583.75 | 5195.50 | 455.25 |
F7 SW APARTMENT | 4032.75 | 5525.00 | 1985.75 |
F7 NW APARTMENT | 3925.75 | 6423.50 | 2608.00 |
F7 SE APARTMENT | 4137.00 | 5454.50 | 1963.75 |
F7 NE APARTMENT | 3986.75 | 6325.25 | 2519.00 |
F7 N1 APARTMENT | 2098.75 | 6490.25 | 900.00 |
F7 N2 APARTMENT | 2110.00 | 6470.00 | 900.75 |
F7 S1 APARTMENT | 2544.75 | 5271.00 | 496.25 |
F7 S2 APARTMENT | 2553.25 | 5259.50 | 495.25 |
F8 SW APARTMENT | 4031.50 | 5593.50 | 2055.75 |
F8 NW APARTMENT | 3968.75 | 6508.00 | 2690.75 |
F8 SE APARTMENT | 4146.25 | 5515.25 | 2031.50 |
F8 NE APARTMENT | 4019.75 | 6424.75 | 2592.75 |
F8 N1 APARTMENT | 2136.00 | 6598.75 | 985.50 |
F8 N2 APARTMENT | 2145.75 | 6581.75 | 986.00 |
F8 S1 APARTMENT | 2551.00 | 5357.25 | 565.50 |
F8 S2 APARTMENT | 2561.25 | 5344.75 | 563.75 |
F9 SW APARTMENT | 4226.00 | 5727.75 | 2376.00 |
F9 NW APARTMENT | 4234.25 | 6642.00 | 3002.25 |
F9 SE APARTMENT | 4341.75 | 5633.00 | 2333.75 |
F9 NE APARTMENT | 4273.25 | 6532.00 | 2905.25 |
F9 N1 APARTMENT | 2518.75 | 6738.00 | 1404.00 |
F9 N2 APARTMENT | 2524.25 | 6723.75 | 1401.25 |
F9 S1 APARTMENT | 2801.00 | 5511.75 | 949.25 |
F9 S2 APARTMENT | 2815.00 | 5501.25 | 948.25 |
T SW APARTMENT | 5237.50 | 6169.25 | 3541.50 |
T NW APARTMENT | 5154.00 | 6790.50 | 3983.75 |
T SE APARTMENT | 5296.75 | 6087.75 | 3488.75 |
T NE APARTMENT | 5212.75 | 6740.00 | 3930.50 |
T N1 APARTMENT | 4525.50 | 6956.50 | 3490.25 |
T N2 APARTMENT | 4533.75 | 6944.50 | 3485.25 |
T S1 APARTMENT | 4624.75 | 5993.50 | 2923.00 |
T S2 APARTMENT | 4636.50 | 5980.00 | 2919.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6704.75 | 7663.75 | 4098.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
G NW APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
OFFICE | 1.00 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
G N1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G N2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
G S1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F2 SW APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
F2 NW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F2 SE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F2 NE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F2 N1 APARTMENT | 1.00 | 1.75 | 1.00 | 1.75 |
F2 N2 APARTMENT | 0.50 | 2.00 | 0.50 | 2.00 |
F2 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F2 S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F3 SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F3 NW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F3 SE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F3 NE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F3 N1 APARTMENT | 0.75 | 3.50 | 0.75 | 3.50 |
F3 N2 APARTMENT | 0.75 | 3.75 | 0.75 | 3.75 |
F3 S1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
F3 S2 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F4 SW APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
F4 NW APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F4 SE APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F4 NE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F4 N1 APARTMENT | 1.25 | 4.25 | 1.25 | 4.25 |
F4 N2 APARTMENT | 0.50 | 4.50 | 0.50 | 4.50 |
F4 S1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F4 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M SW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M NW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NE APARTMENT | 1.00 | 0.25 | 1.00 | 0.25 |
M N1 APARTMENT | 0.50 | 4.50 | 0.50 | 4.50 |
M N2 APARTMENT | 1.00 | 5.25 | 1.00 | 5.25 |
M S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F6 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F6 NW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F6 SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F6 NE APARTMENT | 1.75 | 0.50 | 1.75 | 0.50 |
F6 N1 APARTMENT | 0.75 | 5.50 | 0.75 | 5.50 |
F6 N2 APARTMENT | 1.75 | 6.00 | 1.75 | 6.00 |
F6 S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F6 S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F7 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F7 NW APARTMENT | 2.25 | 0.75 | 2.25 | 0.75 |
F7 SE APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F7 NE APARTMENT | 0.75 | 0.50 | 0.75 | 0.50 |
F7 N1 APARTMENT | 1.25 | 6.00 | 1.25 | 6.00 |
F7 N2 APARTMENT | 0.50 | 6.25 | 0.50 | 6.25 |
F7 S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F7 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F8 SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F8 NW APARTMENT | 1.50 | 0.75 | 1.50 | 0.75 |
F8 SE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F8 NE APARTMENT | 1.50 | 0.75 | 1.50 | 0.75 |
F8 N1 APARTMENT | 1.50 | 5.75 | 1.50 | 5.75 |
F8 N2 APARTMENT | 1.25 | 6.25 | 1.25 | 6.25 |
F8 S1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
F8 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F9 SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F9 NW APARTMENT | 2.00 | 0.50 | 2.00 | 0.50 |
F9 SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F9 NE APARTMENT | 2.75 | 1.75 | 2.75 | 1.75 |
F9 N1 APARTMENT | 0.75 | 4.75 | 0.75 | 4.75 |
F9 N2 APARTMENT | 1.00 | 5.00 | 1.00 | 5.00 |
F9 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F9 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T N1 APARTMENT | 2.00 | 22.00 | 2.00 | 22.00 |
T N2 APARTMENT | 1.75 | 25.00 | 1.75 | 25.00 |
T S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 110.00 | 25.00 | 109.00 | 25.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.063 | 0.000 | 0.192 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.063 | 0.000 | 0.185 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.520 | 0.061 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.063 | 0.000 | 0.187 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.038 | 0.000 | 0.181 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.038 | 0.000 | 0.181 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.038 | 0.000 | 0.189 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.038 | 0.000 | 0.190 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.091 | 0.000 | 0.213 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.091 | 0.000 | 0.210 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.091 | 0.000 | 0.214 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.091 | 0.000 | 0.212 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.055 | 0.000 | 0.207 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.055 | 0.000 | 0.207 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.055 | 0.000 | 0.213 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.055 | 0.000 | 0.213 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.108 | 0.000 | 0.226 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.108 | 0.000 | 0.224 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.108 | 0.000 | 0.227 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.108 | 0.000 | 0.225 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.065 | 0.000 | 0.222 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.065 | 0.000 | 0.222 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.065 | 0.000 | 0.226 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.065 | 0.000 | 0.226 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.121 | 0.000 | 0.225 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.121 | 0.000 | 0.224 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.121 | 0.000 | 0.225 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.121 | 0.000 | 0.224 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.073 | 0.000 | 0.221 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.073 | 0.000 | 0.221 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.073 | 0.000 | 0.224 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.073 | 0.000 | 0.224 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.233 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.232 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.233 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.233 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.079 | 0.000 | 0.230 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.079 | 0.000 | 0.230 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.079 | 0.000 | 0.232 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.079 | 0.000 | 0.233 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.240 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.239 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.241 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.240 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.084 | 0.000 | 0.236 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.084 | 0.000 | 0.237 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.085 | 0.000 | 0.239 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.085 | 0.000 | 0.239 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.148 | 0.000 | 0.246 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.148 | 0.000 | 0.245 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.148 | 0.000 | 0.247 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.148 | 0.000 | 0.246 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.089 | 0.000 | 0.242 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.089 | 0.000 | 0.242 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.089 | 0.000 | 0.245 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.089 | 0.000 | 0.245 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.252 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.251 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.253 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.155 | 0.000 | 0.251 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.094 | 0.000 | 0.248 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.094 | 0.000 | 0.248 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.094 | 0.000 | 0.251 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.094 | 0.000 | 0.251 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.258 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.256 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.258 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.257 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.098 | 0.000 | 0.254 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.098 | 0.000 | 0.254 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.098 | 0.000 | 0.257 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.098 | 0.000 | 0.257 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.261 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.260 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.262 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.261 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.101 | 0.000 | 0.258 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.101 | 0.000 | 0.258 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.101 | 0.000 | 0.261 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.101 | 0.000 | 0.261 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.503 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4197 |
Defaulted Fields | 814 |
Fields with Defaults | 11307 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
Electricity:Building | 1547.51 | 26803.46 | 01-JAN-03:15 | 79071.91 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity | 416.41 | 7980.64 | 01-JAN-00:15 | 25049.15 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 348.50 | 6974.01 | 01-JAN-00:15 | 20603.34 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 29.50 | 508.27 | 01-JAN-00:15 | 2167.24 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 21.95 | 379.58 | 01-JAN-00:15 | 1622.33 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 37.06 | 1175.12 | 01-JAN-00:15 | 1175.12 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 14.63 | 238.08 | 01-JAN-03:15 | 783.07 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 2.41 | 14.40 | 01-JAN-00:15 | 230.46 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 177.27 | 1611.36 | 01-JAN-00:15 | 10825.51 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 18.53 | 587.56 | 01-JAN-00:15 | 587.56 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 67.92 | 1006.63 | 01-JAN-00:15 | 4445.81 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1131.09 | 18822.82 | 01-JAN-03:15 | 56933.81 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 7.55 | 128.69 | 01-JAN-00:15 | 544.91 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 158.74 | 1023.79 | 01-JAN-00:15 | 10237.95 | 01-JAN-07:15 |
Fans:Electricity | 655.48 | 20785.11 | 01-JAN-00:15 | 20785.11 | 01-JAN-06:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1377.71 | 21165.63 | 06-JUN-02:15 | 161387.04 | 29-JAN-00:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
ElectricityPurchased:Plant | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
Cogeneration:ElectricityPurchased | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
ElectricityNet:Plant | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
Cogeneration:ElectricityNet | 3143.70 | 48006.02 | 06-JUN-02:45 | 212165.24 | 28-JAN-24:00 |
ExteriorLights:Electricity | 167.13 | 0.00 | 01-JAN-11:30 | 10720.10 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 167.13 | 0.00 | 01-JAN-11:30 | 10720.10 | 01-JAN-00:15 |
General:Fans:Electricity | 655.48 | 20785.11 | 01-JAN-00:15 | 20785.11 | 01-JAN-06:15 |
Cooling:Electricity | 157.30 | 0.00 | 01-JAN-00:15 | 60059.47 | 21-JUL-14:15 |
Heating:Electricity | 544.10 | 0.00 | 11-APR-17:15 | 140174.76 | 29-JAN-00:15 |
Electricity:Plant | 51.36 | 36.93 | 07-MAY-18:45 | 3477.59 | 29-JUL-16:30 |
HeatRejection:Electricity | 5.93 | 0.00 | 01-JAN-00:15 | 2034.33 | 29-JUL-16:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 45.43 | 36.93 | 07-MAY-18:45 | 1443.26 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.62 | 0.00 | 01-JAN-00:15 | 37.57 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 973.17 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 3435.51 | 9260.51 | 22-MAR-22:30 | 317067.56 | 29-JAN-08:15 |
Gas:Plant | 3435.51 | 9260.51 | 22-MAR-22:30 | 317067.56 | 29-JAN-08:15 |
WaterSystems:Gas | 1483.57 | 9260.51 | 01-JAN-00:15 | 96868.71 | 18-MAR-07:00 |
Water Heater:WaterSystems:Gas | 1483.57 | 9260.51 | 01-JAN-00:15 | 96868.71 | 18-MAR-07:00 |
Heating:Gas | 1951.93 | 0.00 | 20-MAR-13:00 | 246772.37 | 29-JAN-00:30 |
Boiler:Heating:Gas | 1951.93 | 0.00 | 20-MAR-13:00 | 246772.37 | 29-JAN-00:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 605.52 | 0.00 | 01-JAN-00:15 | 260989.96 | 30-JUN-12:30 |
PlantLoopCoolingDemand:HVAC | 605.52 | 0.00 | 01-JAN-00:15 | 260989.96 | 30-JUN-12:30 |
CoolingCoils:PlantLoopCoolingDemand | 605.52 | 0.00 | 01-JAN-00:15 | 260989.96 | 30-JUN-12:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5272.99 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:30 |
Water:Plant | 5272.99 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:30 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5272.99 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:30 |
MainsWater:Plant | 5272.99 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:30 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 494.48 | 0.00 | 01-JAN-00:15 | 0.00 | 21-JUL-16:00 |
HeatRejection:MainsWater | 494.48 | 0.00 | 01-JAN-00:15 | 0.00 | 21-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 2722.60 | 645.72 | 24-AUG-01:15 | 249230.42 | 29-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 1130.27 | 645.72 | 24-AUG-01:15 | 71347.09 | 01-JAN-07:15 |
WaterSystems:PlantLoopHeatingDemand | 1130.27 | 645.72 | 24-AUG-01:15 | 71347.09 | 01-JAN-07:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 6903.27 | 8268.15 | 08-AUG-02:00 | 795761.46 | 28-JAN-24:00 |
EnergyTransfer:Building | 1642.72 | 3668.66 | 18-JUN-17:00 | 241439.85 | 29-JAN-00:15 |
EnergyTransfer:Zone:G SW APARTMENT | 22.26 | 0.03 | 24-AUG-11:00 | 2748.36 | 29-JAN-00:15 |
Heating:EnergyTransfer | 1017.02 | 0.00 | 22-MAR-15:15 | 241439.85 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 17.18 | 0.00 | 09-FEB-11:30 | 2748.36 | 29-JAN-00:15 |
Cooling:EnergyTransfer | 625.70 | 0.00 | 01-JAN-00:15 | 180606.69 | 11-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 5.08 | 0.00 | 01-JAN-00:15 | 2406.49 | 11-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 23.26 | 0.01 | 24-AUG-20:15 | 2812.47 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 20.17 | 0.00 | 22-MAR-14:30 | 2812.47 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 3.09 | 0.00 | 01-JAN-00:15 | 1877.74 | 11-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 26.65 | 0.01 | 06-OCT-21:30 | 3271.51 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 15.75 | 0.00 | 20-JAN-12:00 | 2888.39 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 10.90 | 0.00 | 01-JAN-00:15 | 3271.51 | 10-AUG-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 23.16 | 0.00 | 30-JUL-20:15 | 2820.21 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 19.68 | 0.00 | 20-MAR-09:15 | 2820.21 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 3.49 | 0.00 | 01-JAN-00:15 | 1499.12 | 11-JUL-05:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 15.55 | 0.01 | 16-JUN-12:15 | 1859.48 | 12-JAN-08:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 12.28 | 0.00 | 18-MAR-16:15 | 1859.48 | 12-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.27 | 0.00 | 01-JAN-00:15 | 1079.02 | 11-JUL-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 15.54 | 0.01 | 03-JUL-16:00 | 1859.40 | 12-JAN-08:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 12.25 | 0.00 | 18-MAR-16:15 | 1859.40 | 12-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.29 | 0.00 | 01-JAN-00:15 | 1074.48 | 11-JUL-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 14.84 | 0.01 | 06-MAY-14:15 | 1897.36 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 9.38 | 0.00 | 23-JAN-12:45 | 1831.30 | 12-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 5.47 | 0.00 | 01-JAN-00:15 | 1897.36 | 21-JUL-14:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 14.81 | 0.00 | 10-JUN-10:15 | 1944.00 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 9.22 | 0.00 | 23-JAN-12:30 | 1821.59 | 12-JAN-08:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 5.58 | 0.00 | 01-JAN-00:15 | 1944.00 | 21-JUL-14:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 23.35 | 0.09 | 14-JUL-20:15 | 3198.47 | 11-AUG-16:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 13.73 | 0.00 | 09-FEB-11:15 | 3036.51 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 9.62 | 0.00 | 01-JAN-00:15 | 3198.47 | 11-AUG-16:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 22.33 | 0.03 | 06-OCT-06:00 | 3161.71 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 17.19 | 0.00 | 18-MAR-15:00 | 3161.71 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 5.14 | 0.00 | 01-JAN-00:15 | 2606.26 | 11-JUL-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 24.47 | 0.05 | 08-NOV-11:15 | 3302.48 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 12.92 | 0.00 | 05-FEB-11:15 | 3043.21 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 11.56 | 0.00 | 01-JAN-00:15 | 3302.48 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 22.87 | 0.03 | 18-MAR-18:15 | 3175.45 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 16.62 | 0.00 | 18-MAR-11:00 | 3175.45 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 6.24 | 0.00 | 01-JAN-00:15 | 2080.54 | 13-JUN-06:45 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 13.08 | 0.03 | 19-JUN-14:00 | 1797.63 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 7.85 | 0.00 | 21-JAN-21:00 | 1797.63 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 5.23 | 0.00 | 01-JAN-00:15 | 1407.14 | 11-JUL-16:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 13.11 | 0.00 | 31-MAY-11:30 | 1797.81 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 7.82 | 0.00 | 21-JAN-21:00 | 1797.81 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 5.28 | 0.00 | 01-JAN-00:15 | 1392.06 | 11-JUL-16:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 15.62 | 0.02 | 09-OCT-03:30 | 2554.13 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 5.52 | 0.00 | 16-JAN-12:45 | 1672.31 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 10.10 | 0.00 | 01-JAN-00:15 | 2554.13 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 15.72 | 0.06 | 15-JUL-10:00 | 2577.04 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 5.48 | 0.00 | 16-JAN-12:45 | 1671.69 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 10.24 | 0.00 | 01-JAN-00:15 | 2577.04 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 23.44 | 0.10 | 08-AUG-03:15 | 3254.55 | 11-AUG-16:15 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 12.86 | 0.00 | 23-JAN-12:45 | 3223.70 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 10.58 | 0.00 | 01-JAN-00:15 | 3254.55 | 11-AUG-16:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 22.04 | 0.20 | 16-JUN-20:30 | 3354.49 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 16.28 | 0.00 | 18-MAR-11:45 | 3354.49 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 5.76 | 0.00 | 01-JAN-00:15 | 2647.12 | 11-JUL-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 24.55 | 0.12 | 25-SEP-04:45 | 3340.32 | 22-JUL-12:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 12.49 | 0.00 | 23-JAN-12:45 | 3237.05 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 12.05 | 0.00 | 01-JAN-00:15 | 3340.32 | 22-JUL-12:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 22.66 | 0.09 | 18-JUL-20:45 | 3370.71 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 15.74 | 0.00 | 17-MAR-19:00 | 3370.71 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 6.92 | 0.00 | 01-JAN-00:15 | 2165.50 | 13-JUN-06:45 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 12.69 | 0.05 | 04-JUN-13:45 | 1864.61 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 6.78 | 0.00 | 19-JAN-18:45 | 1864.61 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 5.92 | 0.00 | 01-JAN-00:15 | 1464.07 | 29-JUN-19:45 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 12.73 | 0.04 | 13-FEB-17:15 | 1864.82 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 6.75 | 0.00 | 19-JAN-18:45 | 1864.82 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 5.97 | 0.00 | 01-JAN-00:15 | 1455.90 | 29-JUN-19:30 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 16.12 | 0.03 | 09-MAY-17:45 | 2625.38 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 4.62 | 0.00 | 16-JAN-12:30 | 1731.39 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 11.50 | 0.00 | 01-JAN-00:15 | 2625.38 | 21-JUL-14:15 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 16.21 | 0.14 | 11-FEB-01:00 | 2642.01 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 4.61 | 0.00 | 16-JAN-12:30 | 1731.28 | 29-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 11.60 | 0.00 | 01-JAN-00:15 | 2642.01 | 21-JUL-14:15 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 23.73 | 0.06 | 12-AUG-18:45 | 3434.25 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 12.94 | 0.00 | 23-JAN-13:00 | 3434.25 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 10.79 | 0.00 | 01-JAN-00:15 | 3277.62 | 11-JUL-17:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 22.36 | 0.36 | 04-JUN-14:15 | 3568.53 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 16.42 | 0.00 | 18-MAR-11:15 | 3568.53 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 5.94 | 0.00 | 01-JAN-00:15 | 2655.32 | 11-JUL-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 24.82 | 0.24 | 06-APR-07:00 | 3451.00 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 12.64 | 0.00 | 23-JAN-12:15 | 3451.00 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 12.19 | 0.00 | 01-JAN-00:15 | 3356.10 | 22-JUL-12:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 23.00 | 0.01 | 16-JUL-12:00 | 3586.53 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 15.88 | 0.00 | 10-MAR-08:00 | 3586.53 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 7.12 | 0.00 | 01-JAN-00:15 | 2201.96 | 13-JUN-07:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 12.88 | 0.01 | 12-MAY-19:00 | 1982.71 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 6.70 | 0.00 | 17-JAN-19:00 | 1982.71 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 6.18 | 0.00 | 01-JAN-00:15 | 1489.40 | 29-JUN-19:30 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 12.91 | 0.00 | 05-AUG-11:00 | 1982.95 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 6.68 | 0.00 | 17-JAN-19:00 | 1982.95 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 6.24 | 0.00 | 01-JAN-00:15 | 1474.99 | 29-JUN-19:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 16.44 | 0.41 | 28-JUN-12:30 | 2646.86 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 4.54 | 0.00 | 16-JAN-12:30 | 1843.74 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 11.91 | 0.00 | 01-JAN-00:15 | 2646.86 | 21-JUL-14:15 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 16.52 | 0.30 | 16-JUL-14:30 | 2662.72 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 4.53 | 0.00 | 16-JAN-12:30 | 1843.85 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 11.99 | 0.00 | 01-JAN-00:15 | 2662.72 | 21-JUL-14:15 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 23.78 | 0.10 | 14-OCT-01:00 | 3601.52 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 12.93 | 0.00 | 23-JAN-12:30 | 3601.52 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 10.85 | 0.00 | 01-JAN-00:15 | 3319.06 | 11-JUL-17:30 |
EnergyTransfer:Zone:M NW APARTMENT | 22.41 | 0.22 | 12-APR-09:30 | 3738.32 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 16.38 | 0.00 | 17-MAR-19:00 | 3738.32 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 6.03 | 0.00 | 01-JAN-00:15 | 2682.02 | 11-JUL-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 24.87 | 0.04 | 12-FEB-18:30 | 3619.82 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 12.63 | 0.00 | 23-JAN-12:00 | 3619.82 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 12.24 | 0.00 | 01-JAN-00:15 | 3392.28 | 22-JUL-12:00 |
EnergyTransfer:Zone:M NE APARTMENT | 23.06 | 0.03 | 21-AUG-14:15 | 3757.43 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 15.85 | 0.00 | 10-MAR-07:45 | 3757.43 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 7.21 | 0.00 | 01-JAN-00:15 | 2230.73 | 13-JUN-07:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 12.87 | 0.00 | 30-MAY-15:15 | 2071.72 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 6.53 | 0.00 | 17-JAN-19:00 | 2071.72 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 6.35 | 0.00 | 01-JAN-00:15 | 1524.44 | 29-JUN-19:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 12.92 | 0.01 | 08-JUN-13:30 | 2071.97 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 6.51 | 0.00 | 17-JAN-19:00 | 2071.97 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 6.41 | 0.00 | 01-JAN-00:15 | 1509.55 | 29-JUN-19:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 16.54 | 0.11 | 15-MAR-23:30 | 2682.73 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 4.42 | 0.00 | 16-JAN-12:30 | 1932.31 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 12.12 | 0.00 | 01-JAN-00:15 | 2682.73 | 21-JUL-14:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 16.62 | 0.20 | 24-MAR-06:45 | 2698.47 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 4.42 | 0.00 | 16-JAN-12:30 | 1932.49 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 12.20 | 0.00 | 01-JAN-00:15 | 2698.47 | 21-JUL-14:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 23.90 | 0.04 | 23-JAN-13:30 | 3806.75 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 13.74 | 0.00 | 23-JAN-12:45 | 3806.75 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 10.15 | 0.00 | 01-JAN-00:15 | 3288.62 | 11-JUL-17:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 22.89 | 0.05 | 06-OCT-06:15 | 3945.43 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 17.34 | 0.00 | 18-MAR-11:15 | 3945.43 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 5.56 | 0.00 | 01-JAN-00:15 | 2635.07 | 11-JUL-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 24.92 | 0.02 | 08-AUG-03:00 | 3826.00 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 13.42 | 0.00 | 23-JAN-12:15 | 3826.00 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 11.50 | 0.00 | 01-JAN-00:15 | 3359.61 | 22-JUL-12:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 23.48 | 0.01 | 18-JUL-19:15 | 3965.43 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 16.78 | 0.00 | 10-MAR-08:00 | 3965.43 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 6.70 | 0.00 | 01-JAN-00:15 | 2190.18 | 13-JUN-07:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 13.07 | 0.02 | 21-AUG-18:30 | 2206.94 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.18 | 0.00 | 17-JAN-19:00 | 2206.94 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 5.89 | 0.00 | 01-JAN-00:15 | 1488.27 | 29-JUN-19:30 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 13.11 | 0.01 | 28-SEP-06:30 | 2207.20 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.16 | 0.00 | 17-JAN-19:00 | 2207.20 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 5.95 | 0.00 | 01-JAN-00:15 | 1472.75 | 29-JUN-19:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 16.28 | 0.14 | 11-OCT-09:00 | 2646.26 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 4.90 | 0.00 | 16-JAN-12:30 | 2065.18 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 11.39 | 0.00 | 01-JAN-00:15 | 2646.26 | 21-JUL-14:15 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 16.35 | 0.12 | 16-JUN-10:00 | 2662.23 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 4.89 | 0.00 | 16-JAN-12:30 | 2065.38 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 11.46 | 0.00 | 01-JAN-00:15 | 2662.23 | 21-JUL-14:15 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 23.99 | 0.03 | 08-OCT-08:00 | 3972.93 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 14.29 | 0.00 | 23-JAN-12:45 | 3972.93 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 9.71 | 0.00 | 01-JAN-00:15 | 3280.57 | 11-JUL-17:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 23.22 | 0.05 | 18-APR-01:30 | 4111.87 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 17.94 | 0.00 | 18-MAR-11:30 | 4111.87 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 5.27 | 0.00 | 01-JAN-00:15 | 2615.67 | 11-JUL-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 24.99 | 0.03 | 22-MAY-13:45 | 3992.91 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 13.95 | 0.00 | 23-JAN-12:15 | 3992.91 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 11.04 | 0.00 | 01-JAN-00:15 | 3350.94 | 22-JUL-12:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 23.76 | 0.00 | 16-JUL-20:15 | 4132.56 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 17.38 | 0.00 | 10-MAR-08:00 | 4132.56 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 6.38 | 0.00 | 01-JAN-00:15 | 2172.92 | 13-JUN-07:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 13.18 | 0.00 | 18-JUL-12:45 | 2311.41 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 7.57 | 0.00 | 19-JAN-18:45 | 2311.41 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 5.62 | 0.00 | 01-JAN-00:15 | 1476.62 | 29-JUN-19:30 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 13.21 | 0.00 | 02-JUN-15:15 | 2311.69 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 7.55 | 0.00 | 19-JAN-18:45 | 2311.69 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 5.67 | 0.00 | 01-JAN-00:15 | 1461.10 | 29-JUN-19:30 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 16.13 | 0.05 | 02-NOV-21:30 | 2633.16 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 5.20 | 0.00 | 16-JAN-12:30 | 2169.49 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 10.93 | 0.00 | 01-JAN-00:15 | 2633.16 | 21-JUL-14:15 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 16.20 | 0.05 | 17-OCT-20:30 | 2649.26 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 5.20 | 0.00 | 16-JAN-12:30 | 2169.70 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 11.00 | 0.00 | 01-JAN-00:15 | 2649.26 | 21-JUL-14:15 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 24.22 | 0.09 | 24-SEP-23:45 | 4132.64 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 14.92 | 0.00 | 23-JAN-12:45 | 4132.64 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 9.30 | 0.00 | 01-JAN-00:15 | 3281.80 | 11-JUL-17:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 23.68 | 0.05 | 24-SEP-12:00 | 4271.58 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 18.64 | 0.00 | 18-MAR-12:00 | 4271.58 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 5.04 | 0.00 | 01-JAN-00:15 | 2610.74 | 11-JUL-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 25.20 | 0.11 | 09-OCT-07:45 | 4153.26 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 14.58 | 0.00 | 23-JAN-12:30 | 4153.26 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 10.63 | 0.00 | 01-JAN-00:15 | 3351.50 | 22-JUL-12:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 24.19 | 0.04 | 16-AUG-12:00 | 4292.87 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 18.06 | 0.00 | 18-MAR-08:00 | 4292.87 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 6.13 | 0.00 | 01-JAN-00:15 | 2165.80 | 13-JUN-07:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 13.44 | 0.01 | 03-JUL-18:00 | 2415.70 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 8.07 | 0.00 | 19-JAN-18:45 | 2415.70 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 5.38 | 0.00 | 01-JAN-00:15 | 1476.96 | 29-JUN-19:30 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 13.48 | 0.01 | 05-JUN-15:00 | 2415.99 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 8.04 | 0.00 | 19-JAN-18:45 | 2415.99 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 5.43 | 0.00 | 01-JAN-00:15 | 1463.56 | 29-JUN-19:30 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 16.10 | 0.15 | 16-OCT-22:15 | 2630.02 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 5.61 | 0.00 | 16-JAN-12:45 | 2274.06 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 10.49 | 0.00 | 01-JAN-00:15 | 2630.02 | 21-JUL-14:15 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 16.17 | 0.13 | 23-JAN-19:15 | 2646.27 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 5.60 | 0.00 | 16-JAN-12:45 | 2274.30 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 10.57 | 0.00 | 01-JAN-00:15 | 2646.27 | 21-JUL-14:15 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 25.84 | 0.11 | 26-JUN-03:15 | 4409.96 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 17.14 | 0.00 | 09-FEB-11:30 | 4409.96 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 8.70 | 0.00 | 01-JAN-00:15 | 3353.73 | 11-JUL-17:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 25.86 | 0.27 | 22-APR-13:45 | 4548.36 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 21.06 | 0.00 | 18-MAR-15:00 | 4548.36 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 4.79 | 0.00 | 01-JAN-00:15 | 2687.44 | 11-JUL-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 26.75 | 0.03 | 08-AUG-03:30 | 4431.71 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 16.76 | 0.00 | 05-FEB-12:00 | 4431.71 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 9.98 | 0.00 | 01-JAN-00:15 | 3392.49 | 22-JUL-12:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 26.28 | 0.03 | 11-AUG-09:30 | 4570.72 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 20.44 | 0.00 | 18-MAR-11:15 | 4570.72 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 5.84 | 0.00 | 01-JAN-00:15 | 2161.83 | 13-JUN-07:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 15.16 | 0.03 | 09-AUG-19:15 | 2633.21 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 10.12 | 0.00 | 21-JAN-21:15 | 2633.21 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 5.04 | 0.00 | 01-JAN-00:15 | 1543.10 | 29-JUN-19:30 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 15.19 | 0.03 | 09-JUN-18:45 | 2633.54 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 10.10 | 0.00 | 21-JAN-21:15 | 2633.54 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 5.09 | 0.00 | 01-JAN-00:15 | 1535.94 | 29-JUN-19:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 16.97 | 0.01 | 07-MAR-04:45 | 2665.28 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 7.30 | 0.00 | 16-JAN-13:00 | 2491.76 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 9.67 | 0.00 | 01-JAN-00:15 | 2665.28 | 21-JUL-14:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 17.04 | 0.07 | 26-JUL-16:00 | 2683.64 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 7.29 | 0.00 | 16-JAN-13:00 | 2492.05 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 9.75 | 0.00 | 01-JAN-00:15 | 2683.64 | 21-JUL-14:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 35.84 | 0.04 | 11-MAY-23:00 | 5391.40 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 28.13 | 0.00 | 09-FEB-11:30 | 5391.40 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 7.71 | 0.00 | 01-JAN-00:15 | 3912.66 | 20-JUN-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 36.07 | 0.01 | 22-MAY-22:45 | 5481.27 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 31.92 | 0.00 | 18-MAR-12:30 | 5481.27 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 4.15 | 0.00 | 01-JAN-00:15 | 3181.46 | 11-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 36.37 | 0.01 | 19-SEP-10:30 | 5414.07 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 27.66 | 0.00 | 09-FEB-11:15 | 5414.07 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 8.71 | 0.00 | 01-JAN-00:15 | 4003.67 | 22-JUL-12:00 |
EnergyTransfer:Zone:T NE APARTMENT | 36.36 | 0.09 | 24-JUL-08:00 | 5504.17 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 31.26 | 0.00 | 18-MAR-11:30 | 5504.17 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 5.09 | 0.00 | 01-JAN-00:15 | 2484.57 | 22-JUL-12:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 25.07 | 0.00 | 17-AUG-18:30 | 3563.44 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 20.84 | 0.00 | 18-MAR-11:00 | 3563.44 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 4.23 | 0.00 | 01-JAN-00:15 | 1736.01 | 29-JUN-19:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 25.09 | 0.01 | 17-JUN-15:00 | 3563.92 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 20.80 | 0.00 | 18-MAR-11:00 | 3563.92 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 4.29 | 0.00 | 01-JAN-00:15 | 1701.04 | 29-JUN-19:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 25.40 | 0.02 | 25-JUN-23:15 | 3467.09 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 17.53 | 0.00 | 23-JAN-13:00 | 3467.09 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 7.88 | 0.00 | 01-JAN-00:15 | 3393.01 | 21-JUL-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 25.45 | 0.24 | 27-OCT-14:30 | 3467.55 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 17.51 | 0.00 | 23-JAN-13:00 | 3467.55 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 7.95 | 0.00 | 01-JAN-00:15 | 3406.55 | 21-JUL-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 2691.59 | 645.72 | 24-AUG-01:15 | 247456.84 | 29-JAN-08:00 |
WaterSystems:EnergyTransfer | 1130.26 | 645.72 | 24-AUG-01:15 | 71339.79 | 01-JAN-07:15 |
sub cat:WaterSystems:EnergyTransfer | 1130.26 | 645.72 | 24-AUG-01:15 | 71339.79 | 01-JAN-07:15 |
EnergyTransfer:HVAC | 2568.96 | 0.00 | 07-MAY-18:45 | 338328.82 | 29-JAN-00:15 |
CoolingCoils:EnergyTransfer | 466.56 | 0.00 | 01-JAN-00:15 | 204002.17 | 30-JUN-12:30 |
HeatingCoils:EnergyTransfer | 2102.40 | 0.00 | 11-APR-17:15 | 338328.82 | 29-JAN-00:15 |
PlantLoopHeatingDemand:HVAC | 1592.33 | 0.00 | 11-APR-17:15 | 198403.99 | 29-JAN-00:15 |
HeatingCoils:PlantLoopHeatingDemand | 1592.33 | 0.00 | 11-APR-17:15 | 198403.99 | 29-JAN-00:15 |
Boilers:EnergyTransfer | 1561.33 | 0.00 | 20-MAR-13:00 | 197417.90 | 29-JAN-00:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 17.177 | -5.080 | 0.000 | 0.000 | 3.907 | 2.413 | 12.213 | 14.099 | 0.000 | 0.022 | 0.000 | 0.000 | -20.551 | 0.000 | -6.309 | -17.891 |
G NW APARTMENT | 20.170 | -3.087 | 0.000 | 0.000 | 3.946 | 2.413 | 12.213 | 5.741 | 0.000 | 0.022 | 0.000 | 0.000 | -21.893 | 0.000 | -5.915 | -13.610 |
OFFICE | 15.751 | -10.901 | 0.000 | 0.000 | 0.546 | 21.954 | 7.547 | 15.717 | 0.000 | 0.003 | 0.000 | 0.000 | -20.259 | 0.000 | -3.552 | -26.806 |
G NE APARTMENT | 19.677 | -3.486 | 0.000 | 0.000 | 3.945 | 2.413 | 12.213 | 7.214 | 0.000 | 0.022 | 0.000 | 0.000 | -21.398 | 0.000 | -6.012 | -14.588 |
G N1 APARTMENT | 12.277 | -3.269 | 0.000 | 0.000 | 3.955 | 2.413 | 12.213 | 2.234 | 0.000 | 0.021 | 0.000 | 0.000 | -13.579 | 0.000 | -4.344 | -11.921 |
G N2 APARTMENT | 12.251 | -3.292 | 0.000 | 0.000 | 3.955 | 2.413 | 12.213 | 2.230 | 0.000 | 0.021 | 0.000 | 0.000 | -13.581 | 0.000 | -4.354 | -11.856 |
G S1 APARTMENT | 9.377 | -5.465 | 0.000 | 0.000 | 3.903 | 2.413 | 12.213 | 10.950 | 0.000 | 0.020 | 0.000 | 0.000 | -12.483 | 0.000 | -4.793 | -16.134 |
G S2 APARTMENT | 9.223 | -5.583 | 0.000 | 0.000 | 3.900 | 2.413 | 12.213 | 10.938 | 0.000 | 0.020 | 0.000 | 0.000 | -12.491 | 0.000 | -4.818 | -15.816 |
F2 SW APARTMENT | 13.726 | -9.622 | 0.000 | 0.000 | 3.852 | 2.413 | 12.213 | 13.621 | 0.000 | 0.026 | 0.000 | 0.000 | -21.343 | 0.000 | -8.419 | -6.467 |
F2 NW APARTMENT | 17.189 | -5.143 | 0.000 | 0.000 | 3.899 | 2.413 | 12.213 | 5.359 | 0.000 | 0.026 | 0.000 | 0.000 | -22.630 | 0.000 | -8.085 | -5.241 |
F2 SE APARTMENT | 12.916 | -11.557 | 0.000 | 0.000 | 3.847 | 2.413 | 12.213 | 15.198 | 0.000 | 0.026 | 0.000 | 0.000 | -21.006 | 0.000 | -8.477 | -5.573 |
F2 NE APARTMENT | 16.624 | -6.242 | 0.000 | 0.000 | 3.901 | 2.413 | 12.213 | 6.834 | 0.000 | 0.026 | 0.000 | 0.000 | -22.117 | 0.000 | -8.144 | -5.507 |
F2 N1 APARTMENT | 7.850 | -5.233 | 0.000 | 0.000 | 3.907 | 2.413 | 12.213 | 2.022 | 0.000 | 0.024 | 0.000 | 0.000 | -14.095 | 0.000 | -5.868 | -3.234 |
F2 N2 APARTMENT | 7.824 | -5.282 | 0.000 | 0.000 | 3.907 | 2.413 | 12.213 | 2.019 | 0.000 | 0.024 | 0.000 | 0.000 | -14.097 | 0.000 | -5.877 | -3.144 |
F2 S1 APARTMENT | 5.517 | -10.100 | 0.000 | 0.000 | 3.841 | 2.413 | 12.213 | 10.648 | 0.000 | 0.024 | 0.000 | 0.000 | -12.971 | 0.000 | -6.315 | -5.270 |
F2 S2 APARTMENT | 5.480 | -10.236 | 0.000 | 0.000 | 3.840 | 2.413 | 12.213 | 10.643 | 0.000 | 0.024 | 0.000 | 0.000 | -12.975 | 0.000 | -6.322 | -5.080 |
F3 SW APARTMENT | 12.857 | -10.582 | 0.000 | 0.000 | 3.845 | 2.413 | 12.213 | 13.451 | 0.000 | 0.033 | 0.000 | 0.000 | -21.591 | 0.000 | -9.555 | -3.084 |
F3 NW APARTMENT | 16.284 | -5.756 | 0.000 | 0.000 | 3.889 | 2.413 | 12.213 | 5.235 | 0.000 | 0.033 | 0.000 | 0.000 | -22.892 | 0.000 | -9.237 | -2.181 |
F3 SE APARTMENT | 12.494 | -12.053 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 15.039 | 0.000 | 0.033 | 0.000 | 0.000 | -21.204 | 0.000 | -9.588 | -3.190 |
F3 NE APARTMENT | 15.743 | -6.917 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 6.709 | 0.000 | 0.033 | 0.000 | 0.000 | -22.371 | 0.000 | -9.284 | -2.432 |
F3 N1 APARTMENT | 6.776 | -5.917 | 0.000 | 0.000 | 3.893 | 2.413 | 12.213 | 1.957 | 0.000 | 0.030 | 0.000 | 0.000 | -14.275 | 0.000 | -6.663 | -0.426 |
F3 N2 APARTMENT | 6.754 | -5.973 | 0.000 | 0.000 | 3.893 | 2.413 | 12.213 | 1.954 | 0.000 | 0.030 | 0.000 | 0.000 | -14.277 | 0.000 | -6.670 | -0.336 |
F3 S1 APARTMENT | 4.620 | -11.505 | 0.000 | 0.000 | 3.830 | 2.413 | 12.213 | 10.531 | 0.000 | 0.031 | 0.000 | 0.000 | -13.135 | 0.000 | -7.084 | -1.914 |
F3 S2 APARTMENT | 4.610 | -11.603 | 0.000 | 0.000 | 3.829 | 2.413 | 12.213 | 10.528 | 0.000 | 0.031 | 0.000 | 0.000 | -13.137 | 0.000 | -7.088 | -1.796 |
F4 SW APARTMENT | 12.944 | -10.789 | 0.000 | 0.000 | 3.845 | 2.413 | 12.213 | 13.350 | 0.000 | 0.035 | 0.000 | 0.000 | -21.722 | 0.000 | -10.151 | -2.138 |
F4 NW APARTMENT | 16.421 | -5.942 | 0.000 | 0.000 | 3.887 | 2.413 | 12.213 | 5.169 | 0.000 | 0.035 | 0.000 | 0.000 | -23.039 | 0.000 | -9.854 | -1.302 |
F4 SE APARTMENT | 12.636 | -12.188 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 14.936 | 0.000 | 0.035 | 0.000 | 0.000 | -21.322 | 0.000 | -10.176 | -2.390 |
F4 NE APARTMENT | 15.884 | -7.115 | 0.000 | 0.000 | 3.890 | 2.413 | 12.213 | 6.641 | 0.000 | 0.035 | 0.000 | 0.000 | -22.513 | 0.000 | -9.892 | -1.555 |
F4 N1 APARTMENT | 6.698 | -6.179 | 0.000 | 0.000 | 3.888 | 2.413 | 12.213 | 1.924 | 0.000 | 0.031 | 0.400 | 0.000 | -14.376 | 0.000 | -7.012 | -0.000 |
F4 N2 APARTMENT | 6.677 | -6.237 | 0.000 | 0.000 | 3.888 | 2.413 | 12.213 | 1.921 | 0.000 | 0.031 | 0.491 | 0.000 | -14.378 | 0.000 | -7.018 | -0.000 |
F4 S1 APARTMENT | 4.536 | -11.906 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 10.462 | 0.000 | 0.032 | 0.001 | 0.000 | -13.219 | 0.000 | -7.400 | -0.960 |
F4 S2 APARTMENT | 4.528 | -11.988 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 10.460 | 0.000 | 0.032 | 0.002 | 0.000 | -13.221 | 0.000 | -7.403 | -0.861 |
M SW APARTMENT | 12.928 | -10.855 | 0.000 | 0.000 | 3.845 | 2.413 | 12.213 | 13.270 | 0.000 | 0.036 | 0.000 | 0.000 | -21.833 | 0.000 | -10.857 | -1.160 |
M NW APARTMENT | 16.384 | -6.030 | 0.000 | 0.000 | 3.886 | 2.413 | 12.213 | 5.121 | 0.000 | 0.037 | 0.000 | 0.000 | -23.162 | 0.000 | -10.549 | -0.312 |
M SE APARTMENT | 12.629 | -12.241 | 0.000 | 0.000 | 3.844 | 2.413 | 12.213 | 14.851 | 0.000 | 0.036 | 0.000 | 0.000 | -21.426 | 0.000 | -10.882 | -1.435 |
M NE APARTMENT | 15.848 | -7.207 | 0.000 | 0.000 | 3.889 | 2.413 | 12.213 | 6.589 | 0.000 | 0.036 | 0.000 | 0.000 | -22.632 | 0.000 | -10.586 | -0.564 |
M N1 APARTMENT | 6.525 | -6.350 | 0.000 | 0.000 | 3.886 | 2.413 | 12.213 | 1.900 | 0.000 | 0.032 | 1.313 | 0.000 | -14.458 | 0.000 | -7.474 | -0.000 |
M N2 APARTMENT | 6.507 | -6.411 | 0.000 | 0.000 | 3.885 | 2.413 | 12.213 | 1.898 | 0.000 | 0.032 | 1.403 | 0.000 | -14.460 | 0.000 | -7.480 | -0.000 |
M S1 APARTMENT | 4.421 | -12.120 | 0.000 | 0.000 | 3.827 | 2.413 | 12.213 | 10.408 | 0.000 | 0.034 | 0.000 | 0.000 | -13.288 | 0.000 | -7.869 | -0.037 |
M S2 APARTMENT | 4.417 | -12.204 | 0.000 | 0.000 | 3.826 | 2.413 | 12.213 | 10.405 | 0.000 | 0.034 | 0.059 | 0.000 | -13.290 | 0.000 | -7.873 | -0.000 |
F6 SW APARTMENT | 13.744 | -10.154 | 0.000 | 0.000 | 3.850 | 2.413 | 12.213 | 13.230 | 0.000 | 0.037 | 0.000 | 0.000 | -21.865 | 0.000 | -11.441 | -2.026 |
F6 NW APARTMENT | 17.335 | -5.558 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 5.111 | 0.000 | 0.038 | 0.000 | 0.000 | -23.200 | 0.000 | -11.094 | -1.150 |
F6 SE APARTMENT | 13.419 | -11.503 | 0.000 | 0.000 | 3.849 | 2.413 | 12.213 | 14.808 | 0.000 | 0.037 | 0.000 | 0.000 | -21.457 | 0.000 | -11.470 | -2.309 |
F6 NE APARTMENT | 16.782 | -6.698 | 0.000 | 0.000 | 3.895 | 2.413 | 12.213 | 6.575 | 0.000 | 0.037 | 0.000 | 0.000 | -22.667 | 0.000 | -11.138 | -1.413 |
F6 N1 APARTMENT | 7.175 | -5.892 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 1.899 | 0.000 | 0.033 | 0.557 | 0.000 | -14.480 | 0.000 | -7.812 | -0.001 |
F6 N2 APARTMENT | 7.155 | -5.951 | 0.000 | 0.000 | 3.892 | 2.413 | 12.213 | 1.896 | 0.000 | 0.033 | 0.648 | 0.000 | -14.482 | 0.000 | -7.818 | -0.000 |
F6 S1 APARTMENT | 4.897 | -11.385 | 0.000 | 0.000 | 3.832 | 2.413 | 12.213 | 10.379 | 0.000 | 0.035 | 0.000 | 0.000 | -13.306 | 0.000 | -8.244 | -0.833 |
F6 S2 APARTMENT | 4.889 | -11.464 | 0.000 | 0.000 | 3.831 | 2.413 | 12.213 | 10.376 | 0.000 | 0.035 | 0.000 | 0.000 | -13.307 | 0.000 | -8.249 | -0.737 |
F7 SW APARTMENT | 14.285 | -9.706 | 0.000 | 0.000 | 3.854 | 2.413 | 12.213 | 13.191 | 0.000 | 0.038 | 0.000 | 0.000 | -21.906 | 0.000 | -11.955 | -2.426 |
F7 NW APARTMENT | 17.944 | -5.272 | 0.000 | 0.000 | 3.897 | 2.413 | 12.213 | 5.098 | 0.000 | 0.038 | 0.000 | 0.000 | -23.243 | 0.000 | -11.579 | -1.509 |
F7 SE APARTMENT | 13.951 | -11.038 | 0.000 | 0.000 | 3.853 | 2.413 | 12.213 | 14.765 | 0.000 | 0.038 | 0.000 | 0.000 | -21.495 | 0.000 | -11.986 | -2.713 |
F7 NE APARTMENT | 17.375 | -6.384 | 0.000 | 0.000 | 3.900 | 2.413 | 12.213 | 6.559 | 0.000 | 0.038 | 0.000 | 0.000 | -22.710 | 0.000 | -11.627 | -1.778 |
F7 N1 APARTMENT | 7.569 | -5.615 | 0.000 | 0.000 | 3.898 | 2.413 | 12.213 | 1.896 | 0.000 | 0.034 | 0.212 | 0.000 | -14.505 | 0.000 | -8.113 | -0.000 |
F7 N2 APARTMENT | 7.545 | -5.669 | 0.000 | 0.000 | 3.897 | 2.413 | 12.213 | 1.893 | 0.000 | 0.033 | 0.302 | 0.000 | -14.507 | 0.000 | -8.120 | -0.000 |
F7 S1 APARTMENT | 5.204 | -10.927 | 0.000 | 0.000 | 3.836 | 2.413 | 12.213 | 10.352 | 0.000 | 0.035 | 0.000 | 0.000 | -13.328 | 0.000 | -8.575 | -1.224 |
F7 S2 APARTMENT | 5.196 | -11.004 | 0.000 | 0.000 | 3.836 | 2.413 | 12.213 | 10.349 | 0.000 | 0.035 | 0.000 | 0.000 | -13.329 | 0.000 | -8.579 | -1.129 |
F8 SW APARTMENT | 14.918 | -9.305 | 0.000 | 0.000 | 3.857 | 2.413 | 12.213 | 13.158 | 0.000 | 0.039 | 0.000 | 0.000 | -21.937 | 0.000 | -12.429 | -2.927 |
F8 NW APARTMENT | 18.638 | -5.043 | 0.000 | 0.000 | 3.902 | 2.413 | 12.213 | 5.088 | 0.000 | 0.039 | 0.000 | 0.000 | -23.278 | 0.000 | -12.026 | -1.946 |
F8 SE APARTMENT | 14.576 | -10.626 | 0.000 | 0.000 | 3.857 | 2.413 | 12.213 | 14.728 | 0.000 | 0.039 | 0.000 | 0.000 | -21.524 | 0.000 | -12.464 | -3.211 |
F8 NE APARTMENT | 18.060 | -6.133 | 0.000 | 0.000 | 3.905 | 2.413 | 12.213 | 6.546 | 0.000 | 0.039 | 0.000 | 0.000 | -22.743 | 0.000 | -12.078 | -2.221 |
F8 N1 APARTMENT | 8.066 | -5.377 | 0.000 | 0.000 | 3.903 | 2.413 | 12.213 | 1.893 | 0.000 | 0.034 | 0.000 | 0.000 | -14.523 | 0.000 | -8.395 | -0.226 |
F8 N2 APARTMENT | 8.043 | -5.432 | 0.000 | 0.000 | 3.903 | 2.413 | 12.213 | 1.890 | 0.000 | 0.034 | 0.000 | 0.000 | -14.525 | 0.000 | -8.403 | -0.135 |
F8 S1 APARTMENT | 5.609 | -10.489 | 0.000 | 0.000 | 3.840 | 2.413 | 12.213 | 10.329 | 0.000 | 0.036 | 0.000 | 0.000 | -13.343 | 0.000 | -8.884 | -1.725 |
F8 S2 APARTMENT | 5.600 | -10.566 | 0.000 | 0.000 | 3.840 | 2.413 | 12.213 | 10.326 | 0.000 | 0.036 | 0.000 | 0.000 | -13.345 | 0.000 | -8.889 | -1.628 |
F9 SW APARTMENT | 17.141 | -8.697 | 0.000 | 0.000 | 3.864 | 2.413 | 12.213 | 13.149 | 0.000 | 0.040 | 0.000 | 0.000 | -21.902 | 0.000 | -12.854 | -5.367 |
F9 NW APARTMENT | 21.063 | -4.792 | 0.000 | 0.000 | 3.908 | 2.413 | 12.213 | 5.091 | 0.000 | 0.040 | 0.000 | 0.000 | -23.248 | 0.000 | -12.428 | -4.260 |
F9 SE APARTMENT | 16.761 | -9.985 | 0.000 | 0.000 | 3.863 | 2.413 | 12.213 | 14.719 | 0.000 | 0.040 | 0.000 | 0.000 | -21.492 | 0.000 | -12.897 | -5.636 |
F9 NE APARTMENT | 20.442 | -5.841 | 0.000 | 0.000 | 3.911 | 2.413 | 12.213 | 6.548 | 0.000 | 0.040 | 0.000 | 0.000 | -22.713 | 0.000 | -12.484 | -4.529 |
F9 N1 APARTMENT | 10.120 | -5.040 | 0.000 | 0.000 | 3.910 | 2.413 | 12.213 | 1.897 | 0.000 | 0.035 | 0.000 | 0.000 | -14.496 | 0.000 | -8.650 | -2.403 |
F9 N2 APARTMENT | 10.096 | -5.089 | 0.000 | 0.000 | 3.910 | 2.413 | 12.213 | 1.894 | 0.000 | 0.035 | 0.000 | 0.000 | -14.498 | 0.000 | -8.658 | -2.317 |
F9 S1 APARTMENT | 7.301 | -9.666 | 0.000 | 0.000 | 3.848 | 2.413 | 12.213 | 10.324 | 0.000 | 0.037 | 0.000 | 0.000 | -13.315 | 0.000 | -9.162 | -3.993 |
F9 S2 APARTMENT | 7.293 | -9.748 | 0.000 | 0.000 | 3.848 | 2.413 | 12.213 | 10.321 | 0.000 | 0.037 | 0.000 | 0.000 | -13.316 | 0.000 | -9.168 | -3.892 |
T SW APARTMENT | 28.127 | -7.713 | 0.000 | 0.000 | 3.898 | 2.413 | 12.213 | 13.046 | 0.000 | 0.040 | 0.000 | 0.000 | -21.237 | 0.000 | -13.174 | -17.612 |
T NW APARTMENT | 31.924 | -4.150 | 0.000 | 0.000 | 3.931 | 2.413 | 12.213 | 5.027 | 0.000 | 0.041 | 0.000 | 0.000 | -22.647 | 0.000 | -12.786 | -15.965 |
T SE APARTMENT | 27.659 | -8.707 | 0.000 | 0.000 | 3.898 | 2.413 | 12.213 | 14.656 | 0.000 | 0.040 | 0.000 | 0.000 | -20.871 | 0.000 | -13.192 | -18.108 |
T NE APARTMENT | 31.261 | -5.095 | 0.000 | 0.000 | 3.937 | 2.413 | 12.213 | 6.515 | 0.000 | 0.041 | 0.000 | 0.000 | -22.135 | 0.000 | -12.792 | -16.358 |
T N1 APARTMENT | 20.835 | -4.235 | 0.000 | 0.000 | 3.936 | 2.413 | 12.213 | 1.893 | 0.000 | 0.032 | 0.000 | 0.000 | -14.092 | 0.000 | -8.853 | -14.142 |
T N2 APARTMENT | 20.801 | -4.286 | 0.000 | 0.000 | 3.936 | 2.413 | 12.213 | 1.889 | 0.000 | 0.031 | 0.000 | 0.000 | -14.092 | 0.000 | -8.859 | -14.046 |
T S1 APARTMENT | 17.528 | -7.876 | 0.000 | 0.000 | 3.883 | 2.413 | 12.213 | 10.274 | 0.000 | 0.037 | 0.000 | 0.000 | -12.937 | 0.000 | -9.369 | -16.167 |
T S2 APARTMENT | 17.509 | -7.945 | 0.000 | 0.000 | 3.883 | 2.413 | 12.213 | 10.269 | 0.000 | 0.037 | 0.000 | 0.000 | -12.937 | 0.000 | -9.374 | -16.068 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 3.280 | 0.000 | 0.020 | 73.585 | 0.000 | -4.615 | 0.000 | -90.798 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.295 | 0.000 | 0.000 | 0.000 | 0.000 | -2.760 | 0.000 | -0.921 | -16.143 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.260 | 0.000 | 0.000 | 0.000 | 0.000 | -2.852 | 0.000 | -1.118 | -15.819 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.242 | 0.000 | 0.000 | 0.000 | 0.000 | -2.889 | 0.000 | -1.260 | -15.622 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.059 | 0.000 | 1.221 | 0.000 | 0.000 | 0.000 | 0.000 | -2.938 | 0.000 | -1.411 | -33.931 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.229 | 0.000 | 0.000 | 0.000 | 0.000 | -2.910 | 0.000 | -1.463 | -15.386 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.230 | 0.000 | 0.000 | 0.000 | 0.000 | -2.904 | 0.000 | -1.537 | -15.319 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.228 | 0.000 | 0.000 | 0.000 | 0.000 | -2.902 | 0.000 | -1.606 | -15.250 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 0.000 | 1.230 | 0.000 | 0.000 | 0.000 | 0.000 | -2.884 | 0.000 | -1.663 | -15.213 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.529 | 7.937 | 1.209 | 0.000 | 0.000 | 0.000 | 0.000 | -2.781 | 0.000 | -1.722 | -23.172 |
Total Facility | 1016.986 | -625.702 | 0.000 | 0.000 | 307.022 | 416.414 | 980.287 | 664.449 | 0.000 | 2.645 | 78.974 | 0.000 | -1460.059 | 0.000 | -824.815 | -556.199 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-AUG-16:15 | 0.00 | -2406.72 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3115.34 | 0.00 | 134.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1660.74 |
G NW APARTMENT | 11-JUL-17:30 | 0.00 | -1877.50 | 0.00 | 0.00 | 141.57 | 194.45 | 588.62 | 2517.41 | 0.00 | 205.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1770.00 |
OFFICE | 10-AUG-13:30 | 0.00 | -3271.26 | 0.00 | 0.00 | 65.20 | 1622.33 | 544.91 | 3711.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20.23 | -2652.78 |
G NE APARTMENT | 11-JUL-05:30 | 0.00 | -1499.52 | 0.00 | 0.00 | 163.00 | 100.83 | 317.85 | 3231.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.05 | -2263.29 |
G N1 APARTMENT | 11-JUL-17:30 | 0.00 | -1078.88 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 359.03 | 0.00 | 208.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.99 |
G N2 APARTMENT | 11-JUL-17:30 | 0.00 | -1074.34 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 359.08 | 0.00 | 208.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -418.57 |
G S1 APARTMENT | 21-JUL-14:15 | 0.00 | -1896.94 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2831.96 | 0.00 | 196.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1622.54 |
G S2 APARTMENT | 21-JUL-14:15 | 0.00 | -1943.56 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2831.06 | 0.00 | 196.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1575.01 |
F2 SW APARTMENT | 11-AUG-16:15 | 0.00 | -3198.78 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3071.03 | 0.00 | 172.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.31 |
F2 NW APARTMENT | 11-JUL-17:30 | 0.00 | -2605.87 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2481.75 | 0.00 | 271.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1072.58 |
F2 SE APARTMENT | 21-JUL-14:15 | 0.00 | -3301.89 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 3117.28 | 0.00 | 218.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -524.94 |
F2 NE APARTMENT | 13-JUN-06:40 | 0.00 | -2081.16 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2695.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.15 | -1217.87 |
F2 N1 APARTMENT | 11-JUL-16:15 | 0.00 | -1406.91 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 426.27 | 0.00 | 244.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.65 |
F2 N2 APARTMENT | 11-JUL-16:15 | 0.00 | -1391.83 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 426.06 | 0.00 | 242.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94.07 |
F2 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2553.65 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2811.91 | 0.00 | 212.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -962.59 |
F2 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2576.56 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2811.56 | 0.00 | 212.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -939.33 |
F3 SW APARTMENT | 11-AUG-16:15 | 0.00 | -3254.86 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3051.67 | 0.00 | 194.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -809.13 |
F3 NW APARTMENT | 11-JUL-17:30 | 0.00 | -2646.71 | 0.00 | 0.00 | 141.61 | 194.45 | 588.62 | 2467.43 | 0.00 | 299.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1044.60 |
F3 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3339.64 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3444.26 | 0.00 | 280.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -860.69 |
F3 NE APARTMENT | 13-JUN-06:40 | 0.00 | -2166.13 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2691.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13.22 | -1127.18 |
F3 N1 APARTMENT | 29-JUN-19:45 | 0.00 | -1464.27 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 542.14 | 0.00 | 69.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.31 |
F3 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1456.18 | 0.00 | 0.00 | 141.81 | 230.46 | 523.87 | 551.68 | 0.00 | 76.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -68.50 |
F3 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2624.92 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2801.34 | 0.00 | 223.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.72 |
F3 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2641.54 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2801.07 | 0.00 | 223.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -874.84 |
F4 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3277.14 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2671.05 | 0.00 | 288.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.35 |
F4 NW APARTMENT | 11-JUL-17:30 | 0.00 | -2654.89 | 0.00 | 0.00 | 141.44 | 194.45 | 588.62 | 2457.88 | 0.00 | 318.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.00 |
F4 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3355.42 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3431.79 | 0.00 | 294.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -846.16 |
F4 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2202.67 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2634.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.95 |
F4 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1489.71 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 548.37 | 0.00 | 80.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35.39 |
F4 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1475.29 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 548.51 | 0.00 | 80.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49.50 |
F4 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2646.42 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2793.49 | 0.00 | 232.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -870.71 |
F4 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2662.28 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2793.24 | 0.00 | 232.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -854.61 |
M SW APARTMENT | 11-JUL-17:30 | 0.00 | -3318.55 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2662.04 | 0.00 | 304.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -573.20 |
M NW APARTMENT | 11-JUL-17:30 | 0.00 | -2681.46 | 0.00 | 0.00 | 141.32 | 194.45 | 588.62 | 2449.81 | 0.00 | 333.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1025.92 |
M SE APARTMENT | 22-JUL-12:00 | 0.00 | -3391.58 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3420.88 | 0.00 | 305.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -810.19 |
M NE APARTMENT | 13-JUN-07:00 | 0.00 | -2231.43 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2633.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1016.86 |
M N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1524.77 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 545.51 | 0.00 | 83.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.10 |
M N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1509.87 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 545.65 | 0.00 | 82.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14.62 |
M S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2682.29 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2786.59 | 0.00 | 238.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.63 |
M S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2698.03 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2786.35 | 0.00 | 238.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -818.64 |
F6 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3288.10 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2656.31 | 0.00 | 318.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -611.18 |
F6 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2634.49 | 0.00 | 0.00 | 141.78 | 194.45 | 588.62 | 2379.22 | 0.00 | 364.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1034.06 |
F6 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3358.90 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3413.09 | 0.00 | 314.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -844.35 |
F6 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2190.86 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2634.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1058.00 |
F6 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1488.60 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 544.26 | 0.00 | 84.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36.77 |
F6 N2 APARTMENT | 29-JUN-19:15 | 0.00 | -1473.19 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 489.71 | 0.00 | 89.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1.94 |
F6 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2645.85 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2781.65 | 0.00 | 244.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.66 |
F6 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2661.81 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2781.39 | 0.00 | 244.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -855.43 |
F7 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3280.05 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2650.81 | 0.00 | 329.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -624.78 |
F7 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2615.08 | 0.00 | 0.00 | 141.68 | 194.45 | 588.62 | 2374.45 | 0.00 | 373.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1058.08 |
F7 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3350.23 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3405.65 | 0.00 | 322.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -853.49 |
F7 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2173.59 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2634.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1075.20 |
F7 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1476.96 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 542.79 | 0.00 | 86.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48.28 |
F7 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1461.43 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 542.92 | 0.00 | 85.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.32 |
F7 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2632.76 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2776.89 | 0.00 | 249.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -884.63 |
F7 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2648.85 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2776.63 | 0.00 | 249.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -868.28 |
F8 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3281.26 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2645.72 | 0.00 | 338.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.76 |
F8 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2610.15 | 0.00 | 0.00 | 141.62 | 194.45 | 588.62 | 2369.95 | 0.00 | 382.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1066.86 |
F8 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3350.79 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3398.73 | 0.00 | 329.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -852.81 |
F8 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2166.47 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2633.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.96 |
F8 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1477.30 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 541.21 | 0.00 | 87.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47.22 |
F8 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1463.91 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 541.34 | 0.00 | 86.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60.28 |
F8 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2629.62 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2772.42 | 0.00 | 253.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -887.24 |
F8 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2645.87 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2772.16 | 0.00 | 253.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -870.73 |
F9 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3353.18 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2639.01 | 0.00 | 346.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -557.03 |
F9 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2686.83 | 0.00 | 0.00 | 141.70 | 194.45 | 588.62 | 2364.06 | 0.00 | 395.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -997.41 |
F9 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3391.77 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3391.26 | 0.00 | 335.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -810.27 |
F9 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2162.49 | 0.00 | 0.00 | 138.55 | 93.62 | 382.60 | 2633.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1085.51 |
F9 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1543.46 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 538.18 | 0.00 | 87.61 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1536.30 | 0.00 | 0.00 | 141.80 | 230.46 | 523.87 | 538.28 | 0.00 | 87.55 | 14.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2664.89 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2767.66 | 0.00 | 256.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -850.58 |
F9 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2683.24 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2767.37 | 0.00 | 256.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -831.93 |
T SW APARTMENT | 20-JUN-16:15 | 0.00 | -3912.38 | 0.00 | 0.00 | 84.76 | 144.04 | 588.62 | 3153.58 | 0.00 | 186.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -244.94 |
T NW APARTMENT | 11-JUL-17:15 | 0.00 | -3180.73 | 0.00 | 0.00 | 141.81 | 194.45 | 588.62 | 2330.80 | 0.00 | 411.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -486.66 |
T SE APARTMENT | 22-JUL-12:00 | 0.00 | -4002.88 | 0.00 | 0.00 | 40.75 | 28.81 | 406.15 | 3346.69 | 0.00 | 340.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -159.79 |
T NE APARTMENT | 22-JUL-12:00 | 0.00 | -2483.95 | 0.00 | 0.00 | 40.52 | 28.81 | 406.15 | 1091.84 | 0.00 | 320.07 | 596.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-JUN-19:15 | 0.00 | -1736.55 | 0.00 | 0.00 | 140.98 | 230.46 | 523.87 | 474.46 | 0.00 | 80.79 | 285.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUN-19:15 | 0.00 | -1701.57 | 0.00 | 0.00 | 140.70 | 230.46 | 523.87 | 474.44 | 0.00 | 77.45 | 254.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 21-JUL-14:15 | 0.00 | -3392.52 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2740.39 | 0.00 | 259.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98.55 |
T S2 APARTMENT | 21-JUL-14:15 | 0.00 | -3406.06 | 0.00 | 0.00 | 40.75 | 50.41 | 400.26 | 2740.13 | 0.00 | 259.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.75 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-16:15 | 0.00 | -180580.13 | 0.00 | 0.00 | 6690.15 | 18221.75 | 47207.76 | 114057.36 | 0.00 | 23177.74 | 0.00 | 0.00 | 0.00 | 0.00 | -161.80 | -28612.82 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-JAN-00:15 | 2747.89 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1745.11 | 0.00 | -1118.78 | -352.95 |
G NW APARTMENT | 29-JAN-00:15 | 2811.93 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1755.72 | 0.00 | -1118.79 | -406.35 |
OFFICE | 28-JAN-24:00 | 2888.38 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1757.31 | 0.00 | -1148.06 | -491.27 |
G NE APARTMENT | 29-JAN-00:15 | 2819.66 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1765.40 | 0.00 | -1118.80 | -404.40 |
G N1 APARTMENT | 12-JAN-08:30 | 1860.01 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1197.36 | 0.00 | 0.00 | -1168.31 |
G N2 APARTMENT | 12-JAN-08:30 | 1859.92 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1197.36 | 0.00 | 0.00 | -1168.23 |
G S1 APARTMENT | 12-JAN-08:30 | 1831.76 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1200.51 | 0.00 | 0.00 | -1136.92 |
G S2 APARTMENT | 12-JAN-08:30 | 1822.04 | 0.00 | 0.00 | 0.00 | 73.97 | 43.21 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1200.62 | 0.00 | 0.00 | -1127.09 |
F2 SW APARTMENT | 29-JAN-00:15 | 3036.06 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1802.91 | 0.00 | -1608.46 | -93.64 |
F2 NW APARTMENT | 29-JAN-00:15 | 3161.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1823.43 | 0.00 | -1608.47 | -198.22 |
F2 SE APARTMENT | 29-JAN-00:15 | 3042.75 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1820.20 | 0.00 | -1608.46 | -83.05 |
F2 NE APARTMENT | 29-JAN-00:15 | 3174.87 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1840.41 | 0.00 | -1608.48 | -194.92 |
F2 N1 APARTMENT | 29-JAN-00:30 | 1797.16 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.25 | 0.00 | -944.80 | -201.05 |
F2 N2 APARTMENT | 29-JAN-00:30 | 1797.34 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.25 | 0.00 | -944.80 | -201.23 |
F2 S1 APARTMENT | 29-JAN-00:30 | 1671.94 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1096.65 | 0.00 | -944.78 | -99.46 |
F2 S2 APARTMENT | 29-JAN-00:30 | 1671.32 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1096.66 | 0.00 | -944.78 | -98.83 |
F3 SW APARTMENT | 29-JAN-00:15 | 3223.22 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 38.84 | 0.00 | -1826.25 | 0.00 | -1904.77 | 0.00 |
F3 NW APARTMENT | 29-JAN-00:15 | 3353.93 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1851.68 | 0.00 | -1904.78 | -66.42 |
F3 SE APARTMENT | 29-JAN-00:15 | 3236.56 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 46.03 | 0.00 | -1846.78 | 0.00 | -1904.77 | 0.00 |
F3 NE APARTMENT | 29-JAN-00:15 | 3370.12 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1872.00 | 0.00 | -1904.79 | -62.27 |
F3 N1 APARTMENT | 29-JAN-00:30 | 1864.13 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.08 | 0.00 | -1118.85 | -74.14 |
F3 N2 APARTMENT | 29-JAN-00:30 | 1864.34 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.08 | 0.00 | -1118.85 | -74.36 |
F3 S1 APARTMENT | 29-JAN-00:30 | 1731.01 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 30.20 | 0.00 | -1111.34 | 0.00 | -1118.83 | 0.00 |
F3 S2 APARTMENT | 29-JAN-00:30 | 1730.90 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 30.32 | 0.00 | -1111.34 | 0.00 | -1118.83 | 0.00 |
F4 SW APARTMENT | 29-JAN-00:15 | 3433.75 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 66.93 | 0.00 | -1840.11 | 0.00 | -2129.52 | 0.00 |
F4 NW APARTMENT | 28-JAN-24:00 | 3567.86 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1870.21 | 0.00 | -2185.29 | -79.44 |
F4 SE APARTMENT | 29-JAN-00:15 | 3450.49 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 72.73 | 0.00 | -1862.64 | 0.00 | -2129.52 | 0.00 |
F4 NE APARTMENT | 28-JAN-24:00 | 3585.80 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1893.11 | 0.00 | -2185.30 | -74.46 |
F4 N1 APARTMENT | 29-JAN-00:15 | 1982.31 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.73 | 0.00 | -1284.50 | -12.03 |
F4 N2 APARTMENT | 29-JAN-00:15 | 1982.54 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.73 | 0.00 | -1284.50 | -12.26 |
F4 S1 APARTMENT | 29-JAN-00:15 | 1843.43 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 94.62 | 0.00 | -1122.53 | 0.00 | -1284.47 | 0.00 |
F4 S2 APARTMENT | 29-JAN-00:15 | 1843.54 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 94.50 | 0.00 | -1122.52 | 0.00 | -1284.47 | 0.00 |
M SW APARTMENT | 28-JAN-24:00 | 3600.92 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 59.40 | 0.00 | -1851.97 | 0.00 | -2375.43 | 0.00 |
M NW APARTMENT | 28-JAN-24:00 | 3737.62 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1883.22 | 0.00 | -2375.45 | -46.03 |
M SE APARTMENT | 28-JAN-24:00 | 3619.21 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 65.60 | 0.00 | -1876.45 | 0.00 | -2375.43 | 0.00 |
M NE APARTMENT | 28-JAN-24:00 | 3756.67 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1907.54 | 0.00 | -2375.46 | -40.74 |
M N1 APARTMENT | 29-JAN-00:15 | 2071.30 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 19.81 | 0.00 | -1163.79 | 0.00 | -1396.27 | 0.00 |
M N2 APARTMENT | 29-JAN-00:15 | 2071.55 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 19.56 | 0.00 | -1163.79 | 0.00 | -1396.27 | 0.00 |
M S1 APARTMENT | 29-JAN-00:15 | 1931.99 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 124.66 | 0.00 | -1129.36 | 0.00 | -1396.25 | 0.00 |
M S2 APARTMENT | 29-JAN-00:15 | 1932.17 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 124.48 | 0.00 | -1129.36 | 0.00 | -1396.25 | 0.00 |
F6 SW APARTMENT | 28-JAN-24:00 | 3806.12 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 25.00 | 0.00 | -1858.85 | 0.00 | -2539.34 | 0.00 |
F6 NW APARTMENT | 28-JAN-24:00 | 3944.70 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1891.74 | 0.00 | -2539.36 | -80.67 |
F6 SE APARTMENT | 28-JAN-24:00 | 3825.35 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 31.29 | 0.00 | -1884.38 | 0.00 | -2539.35 | 0.00 |
F6 NE APARTMENT | 28-JAN-24:00 | 3964.63 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1917.09 | 0.00 | -2539.38 | -75.23 |
F6 N1 APARTMENT | 29-JAN-00:15 | 2206.50 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.67 | 0.00 | -1492.62 | -13.15 |
F6 N2 APARTMENT | 29-JAN-00:15 | 2206.76 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.66 | 0.00 | -1492.62 | -13.42 |
F6 S1 APARTMENT | 29-JAN-00:15 | 2064.83 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 92.33 | 0.00 | -1133.53 | 0.00 | -1492.59 | 0.00 |
F6 S2 APARTMENT | 29-JAN-00:15 | 2065.03 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 92.13 | 0.00 | -1133.53 | 0.00 | -1492.59 | 0.00 |
F7 SW APARTMENT | 28-JAN-24:00 | 3972.28 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 | -1865.16 | 0.00 | -2684.61 | 0.00 |
F7 NW APARTMENT | 28-JAN-24:00 | 4111.11 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1899.34 | 0.00 | -2684.63 | -94.21 |
F7 SE APARTMENT | 28-JAN-24:00 | 3992.24 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 | -1891.52 | 0.00 | -2684.62 | 0.00 |
F7 NE APARTMENT | 28-JAN-24:00 | 4131.73 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1925.52 | 0.00 | -2684.65 | -88.64 |
F7 N1 APARTMENT | 29-JAN-00:15 | 2310.95 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.86 | 0.00 | -1578.01 | -27.02 |
F7 N2 APARTMENT | 29-JAN-00:15 | 2311.22 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.86 | 0.00 | -1578.01 | -27.30 |
F7 S1 APARTMENT | 29-JAN-00:15 | 2169.12 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 77.26 | 0.00 | -1137.36 | 0.00 | -1577.98 | 0.00 |
F7 S2 APARTMENT | 29-JAN-00:15 | 2169.34 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 77.05 | 0.00 | -1137.36 | 0.00 | -1577.98 | 0.00 |
F8 SW APARTMENT | 28-JAN-24:00 | 4131.96 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1870.37 | 0.00 | -2815.85 | -12.83 |
F8 NW APARTMENT | 28-JAN-24:00 | 4270.79 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.58 | 0.00 | -2815.87 | -116.42 |
F8 SE APARTMENT | 28-JAN-24:00 | 4152.56 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.41 | 0.00 | -2815.85 | -6.38 |
F8 NE APARTMENT | 28-JAN-24:00 | 4292.02 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1932.44 | 0.00 | -2815.88 | -110.77 |
F8 N1 APARTMENT | 29-JAN-00:15 | 2415.22 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1179.08 | 0.00 | -1655.15 | -49.94 |
F8 N2 APARTMENT | 29-JAN-00:15 | 2415.51 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1179.08 | 0.00 | -1655.15 | -50.23 |
F8 S1 APARTMENT | 29-JAN-00:15 | 2273.69 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 52.94 | 0.00 | -1140.47 | 0.00 | -1655.11 | 0.00 |
F8 S2 APARTMENT | 29-JAN-00:15 | 2273.92 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 52.70 | 0.00 | -1140.46 | 0.00 | -1655.11 | 0.00 |
F9 SW APARTMENT | 28-JAN-24:00 | 4409.24 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1871.15 | 0.00 | -2936.07 | -169.11 |
F9 NW APARTMENT | 28-JAN-24:00 | 4547.53 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1907.09 | 0.00 | -2936.09 | -271.43 |
F9 SE APARTMENT | 28-JAN-24:00 | 4430.97 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1898.67 | 0.00 | -2936.07 | -163.31 |
F9 NE APARTMENT | 28-JAN-24:00 | 4569.83 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1934.43 | 0.00 | -2936.11 | -266.36 |
F9 N1 APARTMENT | 29-JAN-00:15 | 2632.69 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.06 | 0.00 | -1725.81 | -195.76 |
F9 N2 APARTMENT | 29-JAN-00:15 | 2633.02 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.06 | 0.00 | -1725.81 | -196.09 |
F9 S1 APARTMENT | 29-JAN-00:15 | 2491.35 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.66 | 0.00 | -1725.78 | -93.86 |
F9 S2 APARTMENT | 29-JAN-00:15 | 2491.64 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.66 | 0.00 | -1725.78 | -94.15 |
T SW APARTMENT | 28-JAN-24:00 | 5390.59 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1836.57 | 0.00 | -3047.13 | -1073.97 |
T NW APARTMENT | 28-JAN-24:00 | 5480.34 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1872.32 | 0.00 | -3047.15 | -1127.94 |
T SE APARTMENT | 28-JAN-24:00 | 5413.23 | 0.00 | 0.00 | 0.00 | 189.67 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1863.77 | 0.00 | -3047.13 | -1069.41 |
T NE APARTMENT | 28-JAN-24:00 | 5503.15 | 0.00 | 0.00 | 0.00 | 189.66 | 36.01 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1899.43 | 0.00 | -3047.17 | -1123.63 |
T N1 APARTMENT | 29-JAN-00:15 | 3562.76 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1157.27 | 0.00 | -1791.17 | -1083.26 |
T N2 APARTMENT | 29-JAN-00:15 | 3563.24 | 0.00 | 0.00 | 0.00 | 189.66 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1157.26 | 0.00 | -1791.17 | -1083.75 |
T S1 APARTMENT | 29-JAN-00:15 | 3466.57 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.72 | 0.00 | -1791.13 | -1023.67 |
T S2 APARTMENT | 29-JAN-00:15 | 3467.03 | 0.00 | 0.00 | 0.00 | 189.67 | 14.40 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.71 | 0.00 | -1791.13 | -1024.14 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JAN-00:15 | 241400.42 | 0.00 | 0.00 | 0.00 | 14983.68 | 7980.64 | 21105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -122450.09 | 0.00 | -149628.08 | -13391.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Sec1.1A-General InformationData | |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 109.00 |
Number of hours cooling loads not met | 25.00 |
Number of hours not met | 134.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 416.41 | 9687.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.13 | 10720.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 544.10 | 139844.76 | 1951.93 | 221268.06 | 0.00 | 0.00 |
Space Cooling | 157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.43 | 1443.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 655.48 | 20785.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1483.57 | 95799.50 | 0.00 | 0.00 |
Receptacle Equipment | 1131.09 | 29146.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3143.70 | 3435.51 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1131.09 | 3143.70 |
Natural Gas | 0.00 | 3435.51 |
Additional | 0.00 | 0.00 |
Total | 1131.09 | 6579.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 53.14 |
Space Heating | 69.43 |
Space Cooling | 20.07 |
Fans-Interior | 83.64 |
Service Water Heating | 0.00 |
Receptacle Equipment | 144.34 |
Miscellaneous | 30.54 |
Subtotal | 401.16 |
Natural Gas [MJ/m2] | |
Space Heating | 249.08 |
Service Water Heating | 189.32 |
Miscellaneous | -0.00 |
Subtotal | 438.40 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.33 |
Space Heating | 37.94 |
Space Cooling | 2.39 |
Fans-Interior | 9.96 |
Service Water Heating | 22.55 |
Receptacle Equipment | 17.19 |
Miscellaneous | 3.64 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.240478 |
G NW APARTMENT DIRECT AIR | 0.171863 |
OFFICE DIRECT AIR | 0.336255 |
G NE APARTMENT DIRECT AIR | 0.162588 |
G N1 APARTMENT DIRECT AIR | 0.116577 |
G N2 APARTMENT DIRECT AIR | 0.116575 |
G S1 APARTMENT DIRECT AIR | 0.182502 |
G S2 APARTMENT DIRECT AIR | 0.187975 |
F2 SW APARTMENT DIRECT AIR | 0.320945 |
F2 NW APARTMENT DIRECT AIR | 0.237658 |
F2 SE APARTMENT DIRECT AIR | 0.326133 |
F2 NE APARTMENT DIRECT AIR | 0.191209 |
F2 N1 APARTMENT DIRECT AIR | 0.135228 |
F2 N2 APARTMENT DIRECT AIR | 0.133723 |
F2 S1 APARTMENT DIRECT AIR | 0.247080 |
F2 S2 APARTMENT DIRECT AIR | 0.249233 |
F3 SW APARTMENT DIRECT AIR | 0.322935 |
F3 NW APARTMENT DIRECT AIR | 0.240963 |
F3 SE APARTMENT DIRECT AIR | 0.311826 |
F3 NE APARTMENT DIRECT AIR | 0.195248 |
F3 N1 APARTMENT DIRECT AIR | 0.140052 |
F3 N2 APARTMENT DIRECT AIR | 0.138573 |
F3 S1 APARTMENT DIRECT AIR | 0.251081 |
F3 S2 APARTMENT DIRECT AIR | 0.252224 |
F4 SW APARTMENT DIRECT AIR | 0.323170 |
F4 NW APARTMENT DIRECT AIR | 0.241564 |
F4 SE APARTMENT DIRECT AIR | 0.310691 |
F4 NE APARTMENT DIRECT AIR | 0.195775 |
F4 N1 APARTMENT DIRECT AIR | 0.141111 |
F4 N2 APARTMENT DIRECT AIR | 0.139632 |
F4 S1 APARTMENT DIRECT AIR | 0.251878 |
F4 S2 APARTMENT DIRECT AIR | 0.252883 |
M SW APARTMENT DIRECT AIR | 0.325445 |
M NW APARTMENT DIRECT AIR | 0.244132 |
M SE APARTMENT DIRECT AIR | 0.312940 |
M NE APARTMENT DIRECT AIR | 0.198239 |
M N1 APARTMENT DIRECT AIR | 0.143936 |
M N2 APARTMENT DIRECT AIR | 0.142460 |
M S1 APARTMENT DIRECT AIR | 0.254524 |
M S2 APARTMENT DIRECT AIR | 0.255506 |
F6 SW APARTMENT DIRECT AIR | 0.321256 |
F6 NW APARTMENT DIRECT AIR | 0.240179 |
F6 SE APARTMENT DIRECT AIR | 0.308908 |
F6 NE APARTMENT DIRECT AIR | 0.194325 |
F6 N1 APARTMENT DIRECT AIR | 0.140396 |
F6 N2 APARTMENT DIRECT AIR | 0.138927 |
F6 S1 APARTMENT DIRECT AIR | 0.250634 |
F6 S2 APARTMENT DIRECT AIR | 0.251614 |
F7 SW APARTMENT DIRECT AIR | 0.319495 |
F7 NW APARTMENT DIRECT AIR | 0.238662 |
F7 SE APARTMENT DIRECT AIR | 0.307280 |
F7 NE APARTMENT DIRECT AIR | 0.192803 |
F7 N1 APARTMENT DIRECT AIR | 0.139184 |
F7 N2 APARTMENT DIRECT AIR | 0.137719 |
F7 S1 APARTMENT DIRECT AIR | 0.249127 |
F7 S2 APARTMENT DIRECT AIR | 0.250105 |
F8 SW APARTMENT DIRECT AIR | 0.318944 |
F8 NW APARTMENT DIRECT AIR | 0.238416 |
F8 SE APARTMENT DIRECT AIR | 0.306828 |
F8 NE APARTMENT DIRECT AIR | 0.192479 |
F8 N1 APARTMENT DIRECT AIR | 0.139274 |
F8 N2 APARTMENT DIRECT AIR | 0.137817 |
F8 S1 APARTMENT DIRECT AIR | 0.248792 |
F8 S2 APARTMENT DIRECT AIR | 0.249770 |
F9 SW APARTMENT DIRECT AIR | 0.325561 |
F9 NW APARTMENT DIRECT AIR | 0.245494 |
F9 SE APARTMENT DIRECT AIR | 0.312308 |
F9 NE APARTMENT DIRECT AIR | 0.194733 |
F9 N1 APARTMENT DIRECT AIR | 0.145680 |
F9 N2 APARTMENT DIRECT AIR | 0.144163 |
F9 S1 APARTMENT DIRECT AIR | 0.253397 |
F9 S2 APARTMENT DIRECT AIR | 0.254496 |
T SW APARTMENT DIRECT AIR | 0.385416 |
T NW APARTMENT DIRECT AIR | 0.287525 |
T SE APARTMENT DIRECT AIR | 0.366283 |
T NE APARTMENT DIRECT AIR | 0.224572 |
T N1 APARTMENT DIRECT AIR | 0.159694 |
T N2 APARTMENT DIRECT AIR | 0.156615 |
T S1 APARTMENT DIRECT AIR | 0.321790 |
T S2 APARTMENT DIRECT AIR | 0.322872 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.240478 |
AIRLOOP G NW MAIN BRANCH | 0.171863 |
AIRLOOP OFFICE MAIN BRANCH | 0.336255 |
AIRLOOP G NE MAIN BRANCH | 0.162588 |
AIRLOOP G N1 MAIN BRANCH | 0.116577 |
AIRLOOP G N2 MAIN BRANCH | 0.116575 |
AIRLOOP G S1 MAIN BRANCH | 0.182502 |
AIRLOOP G S2 MAIN BRANCH | 0.187975 |
AIRLOOP F2 SW MAIN BRANCH | 0.320945 |
AIRLOOP F2 NW MAIN BRANCH | 0.237658 |
AIRLOOP F2 SE MAIN BRANCH | 0.326133 |
AIRLOOP F2 NE MAIN BRANCH | 0.191209 |
AIRLOOP F2 N1 MAIN BRANCH | 0.135228 |
AIRLOOP F2 N2 MAIN BRANCH | 0.133723 |
AIRLOOP F2 S1 MAIN BRANCH | 0.247080 |
AIRLOOP F2 S2 MAIN BRANCH | 0.249233 |
AIRLOOP F3 SW MAIN BRANCH | 0.322935 |
AIRLOOP F3 NW MAIN BRANCH | 0.240963 |
AIRLOOP F3 SE MAIN BRANCH | 0.311826 |
AIRLOOP F3 NE MAIN BRANCH | 0.195248 |
AIRLOOP F3 N1 MAIN BRANCH | 0.140052 |
AIRLOOP F3 N2 MAIN BRANCH | 0.138573 |
AIRLOOP F3 S1 MAIN BRANCH | 0.251081 |
AIRLOOP F3 S2 MAIN BRANCH | 0.252224 |
AIRLOOP F4 SW MAIN BRANCH | 0.323170 |
AIRLOOP F4 NW MAIN BRANCH | 0.241564 |
AIRLOOP F4 SE MAIN BRANCH | 0.310691 |
AIRLOOP F4 NE MAIN BRANCH | 0.195775 |
AIRLOOP F4 N1 MAIN BRANCH | 0.141111 |
AIRLOOP F4 N2 MAIN BRANCH | 0.139632 |
AIRLOOP F4 S1 MAIN BRANCH | 0.251878 |
AIRLOOP F4 S2 MAIN BRANCH | 0.252883 |
AIRLOOP M SW MAIN BRANCH | 0.325445 |
AIRLOOP M NW MAIN BRANCH | 0.244132 |
AIRLOOP M SE MAIN BRANCH | 0.312940 |
AIRLOOP M NE MAIN BRANCH | 0.198239 |
AIRLOOP M N1 MAIN BRANCH | 0.143936 |
AIRLOOP M N2 MAIN BRANCH | 0.142460 |
AIRLOOP M S1 MAIN BRANCH | 0.254524 |
AIRLOOP M S2 MAIN BRANCH | 0.255506 |
AIRLOOP F6 SW MAIN BRANCH | 0.321256 |
AIRLOOP F6 NW MAIN BRANCH | 0.240179 |
AIRLOOP F6 SE MAIN BRANCH | 0.308908 |
AIRLOOP F6 NE MAIN BRANCH | 0.194325 |
AIRLOOP F6 N1 MAIN BRANCH | 0.140396 |
AIRLOOP F6 N2 MAIN BRANCH | 0.138927 |
AIRLOOP F6 S1 MAIN BRANCH | 0.250634 |
AIRLOOP F6 S2 MAIN BRANCH | 0.251614 |
AIRLOOP F7 SW MAIN BRANCH | 0.319495 |
AIRLOOP F7 NW MAIN BRANCH | 0.238662 |
AIRLOOP F7 SE MAIN BRANCH | 0.307280 |
AIRLOOP F7 NE MAIN BRANCH | 0.192803 |
AIRLOOP F7 N1 MAIN BRANCH | 0.139184 |
AIRLOOP F7 N2 MAIN BRANCH | 0.137719 |
AIRLOOP F7 S1 MAIN BRANCH | 0.249127 |
AIRLOOP F7 S2 MAIN BRANCH | 0.250105 |
AIRLOOP F8 SW MAIN BRANCH | 0.318944 |
AIRLOOP F8 NW MAIN BRANCH | 0.238416 |
AIRLOOP F8 SE MAIN BRANCH | 0.306828 |
AIRLOOP F8 NE MAIN BRANCH | 0.192479 |
AIRLOOP F8 N1 MAIN BRANCH | 0.139274 |
AIRLOOP F8 N2 MAIN BRANCH | 0.137817 |
AIRLOOP F8 S1 MAIN BRANCH | 0.248792 |
AIRLOOP F8 S2 MAIN BRANCH | 0.249770 |
AIRLOOP F9 SW MAIN BRANCH | 0.325561 |
AIRLOOP F9 NW MAIN BRANCH | 0.245494 |
AIRLOOP F9 SE MAIN BRANCH | 0.312308 |
AIRLOOP F9 NE MAIN BRANCH | 0.194733 |
AIRLOOP F9 N1 MAIN BRANCH | 0.145680 |
AIRLOOP F9 N2 MAIN BRANCH | 0.144163 |
AIRLOOP F9 S1 MAIN BRANCH | 0.253397 |
AIRLOOP F9 S2 MAIN BRANCH | 0.254496 |
AIRLOOP T SW MAIN BRANCH | 0.385416 |
AIRLOOP T NW MAIN BRANCH | 0.287525 |
AIRLOOP T SE MAIN BRANCH | 0.366283 |
AIRLOOP T NE MAIN BRANCH | 0.224572 |
AIRLOOP T N1 MAIN BRANCH | 0.159694 |
AIRLOOP T N2 MAIN BRANCH | 0.156615 |
AIRLOOP T S1 MAIN BRANCH | 0.321790 |
AIRLOOP T S2 MAIN BRANCH | 0.322872 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.240478 |
AIRLOOP G NW | 0.171863 |
AIRLOOP OFFICE | 0.336255 |
AIRLOOP G NE | 0.162588 |
AIRLOOP G N1 | 0.116577 |
AIRLOOP G N2 | 0.116575 |
AIRLOOP G S1 | 0.182502 |
AIRLOOP G S2 | 0.187975 |
AIRLOOP F2 SW | 0.320945 |
AIRLOOP F2 NW | 0.237658 |
AIRLOOP F2 SE | 0.326133 |
AIRLOOP F2 NE | 0.191209 |
AIRLOOP F2 N1 | 0.135228 |
AIRLOOP F2 N2 | 0.133723 |
AIRLOOP F2 S1 | 0.247080 |
AIRLOOP F2 S2 | 0.249233 |
AIRLOOP F3 SW | 0.322935 |
AIRLOOP F3 NW | 0.240963 |
AIRLOOP F3 SE | 0.311826 |
AIRLOOP F3 NE | 0.195248 |
AIRLOOP F3 N1 | 0.140052 |
AIRLOOP F3 N2 | 0.138573 |
AIRLOOP F3 S1 | 0.251081 |
AIRLOOP F3 S2 | 0.252224 |
AIRLOOP F4 SW | 0.323170 |
AIRLOOP F4 NW | 0.241564 |
AIRLOOP F4 SE | 0.310691 |
AIRLOOP F4 NE | 0.195775 |
AIRLOOP F4 N1 | 0.141111 |
AIRLOOP F4 N2 | 0.139632 |
AIRLOOP F4 S1 | 0.251878 |
AIRLOOP F4 S2 | 0.252883 |
AIRLOOP M SW | 0.325445 |
AIRLOOP M NW | 0.244132 |
AIRLOOP M SE | 0.312940 |
AIRLOOP M NE | 0.198239 |
AIRLOOP M N1 | 0.143936 |
AIRLOOP M N2 | 0.142460 |
AIRLOOP M S1 | 0.254524 |
AIRLOOP M S2 | 0.255506 |
AIRLOOP F6 SW | 0.321256 |
AIRLOOP F6 NW | 0.240179 |
AIRLOOP F6 SE | 0.308908 |
AIRLOOP F6 NE | 0.194325 |
AIRLOOP F6 N1 | 0.140396 |
AIRLOOP F6 N2 | 0.138927 |
AIRLOOP F6 S1 | 0.250634 |
AIRLOOP F6 S2 | 0.251614 |
AIRLOOP F7 SW | 0.319495 |
AIRLOOP F7 NW | 0.238662 |
AIRLOOP F7 SE | 0.307280 |
AIRLOOP F7 NE | 0.192803 |
AIRLOOP F7 N1 | 0.139184 |
AIRLOOP F7 N2 | 0.137719 |
AIRLOOP F7 S1 | 0.249127 |
AIRLOOP F7 S2 | 0.250105 |
AIRLOOP F8 SW | 0.318944 |
AIRLOOP F8 NW | 0.238416 |
AIRLOOP F8 SE | 0.306828 |
AIRLOOP F8 NE | 0.192479 |
AIRLOOP F8 N1 | 0.139274 |
AIRLOOP F8 N2 | 0.137817 |
AIRLOOP F8 S1 | 0.248792 |
AIRLOOP F8 S2 | 0.249770 |
AIRLOOP F9 SW | 0.325561 |
AIRLOOP F9 NW | 0.245494 |
AIRLOOP F9 SE | 0.312308 |
AIRLOOP F9 NE | 0.194733 |
AIRLOOP F9 N1 | 0.145680 |
AIRLOOP F9 N2 | 0.144163 |
AIRLOOP F9 S1 | 0.253397 |
AIRLOOP F9 S2 | 0.254496 |
AIRLOOP T SW | 0.385416 |
AIRLOOP T NW | 0.287525 |
AIRLOOP T SE | 0.366283 |
AIRLOOP T NE | 0.224572 |
AIRLOOP T N1 | 0.159694 |
AIRLOOP T N2 | 0.156615 |
AIRLOOP T S1 | 0.321790 |
AIRLOOP T S2 | 0.322872 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.240478 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.171863 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.336255 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.162588 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.116577 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.116575 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.182502 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.187975 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.320945 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.237658 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.326133 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.191209 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.135228 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.133723 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.247080 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.249233 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.322935 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.240963 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.311826 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.195248 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.140052 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.138573 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.251081 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.252224 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.323170 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.241564 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.310691 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.195775 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.141111 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.139632 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.251878 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.252883 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.325445 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.244132 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.312940 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.198239 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.143936 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.142460 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.254524 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.255506 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.321256 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.240179 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.308908 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.194325 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.140396 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.138927 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.250634 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.251614 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.319495 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.238662 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.307280 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.192803 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.139184 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.137719 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.249127 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.250105 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.318944 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.238416 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.306828 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.192479 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.139274 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.137817 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.248792 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.249770 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.325561 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.245494 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.312308 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.194733 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.145680 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.144163 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.253397 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.254496 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.385416 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.287525 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.366283 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.224572 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.159694 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.156615 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.321790 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.322872 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.240478 | 3321.35 | 2582.08 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.171863 | 2312.85 | 1812.32 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.336255 | 4658.89 | 3623.19 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.162588 | 2157.41 | 1712.59 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.116577 | 1441.61 | 1169.69 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.116575 | 1437.68 | 1168.03 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.182502 | 2548.65 | 1975.51 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.187975 | 2624.50 | 2034.02 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.320945 | 4424.22 | 3437.60 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.237658 | 3209.61 | 2507.62 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.326133 | 4525.10 | 3507.25 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.191209 | 2563.62 | 2020.97 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.135228 | 1744.24 | 1388.34 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.133723 | 1723.24 | 1372.20 | 0.000038 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.247080 | 3439.33 | 2664.76 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.249233 | 3469.18 | 2687.77 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.322935 | 4447.24 | 3457.72 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.240963 | 3258.29 | 2545.70 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.311826 | 4322.34 | 3353.21 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.195248 | 2615.20 | 2063.04 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.140052 | 1808.65 | 1439.32 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.138573 | 1788.03 | 1423.48 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.251081 | 3492.08 | 2706.85 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.252224 | 3507.91 | 2719.06 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.323170 | 4447.08 | 3459.37 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.241564 | 3268.82 | 2554.69 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.310691 | 4303.23 | 3340.23 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.195775 | 2619.28 | 2067.87 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.141111 | 1821.26 | 1450.14 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.139632 | 1800.65 | 1434.30 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.251878 | 3501.07 | 2714.85 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.252883 | 3515.00 | 2725.59 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.325445 | 4475.81 | 3482.98 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.244132 | 3301.71 | 2581.47 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.312940 | 4331.61 | 3363.56 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.198239 | 2650.74 | 2093.53 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.143936 | 1858.89 | 1479.98 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.142460 | 1838.32 | 1464.16 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.254524 | 3536.05 | 2742.71 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.255506 | 3549.67 | 2753.21 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.321256 | 4415.38 | 3437.62 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.240179 | 3244.27 | 2538.56 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.308908 | 4273.40 | 3319.89 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.194325 | 2594.37 | 2051.18 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.140396 | 1808.02 | 1441.68 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.138927 | 1787.53 | 1425.93 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.250634 | 3480.71 | 2700.77 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.251614 | 3494.29 | 2711.24 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.319495 | 4388.88 | 3418.27 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.238662 | 3221.04 | 2521.79 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.307280 | 4248.77 | 3301.97 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.192803 | 2571.38 | 2034.45 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.139184 | 1789.79 | 1428.36 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.137719 | 1769.38 | 1412.67 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.249127 | 3458.56 | 2684.34 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.250105 | 3472.12 | 2694.80 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.318944 | 4379.36 | 3411.92 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.238416 | 3215.70 | 2518.68 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.306828 | 4240.65 | 3296.67 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.192479 | 2565.15 | 2030.56 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.139274 | 1789.86 | 1429.03 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.137817 | 1769.56 | 1413.42 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.248792 | 3452.78 | 2680.48 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.249770 | 3466.35 | 2690.94 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.325561 | 4469.29 | 3482.19 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.245494 | 3312.41 | 2593.97 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.312308 | 4314.83 | 3354.80 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.194733 | 2594.71 | 2054.23 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.145680 | 1878.10 | 1497.40 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.144163 | 1856.97 | 1481.16 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.253397 | 3515.55 | 2729.44 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.254496 | 3530.78 | 2741.19 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.385416 | 5312.15 | 4129.05 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.287525 | 3915.30 | 3059.09 | 0.000086 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.366283 | 5060.75 | 3931.15 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.224572 | 3028.56 | 2383.52 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.159694 | 2085.92 | 1654.19 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.156615 | 2043.06 | 1621.23 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.321790 | 4462.20 | 3460.15 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.322872 | 4477.19 | 3471.71 | 0.000098 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.240478 | 0.240478 | 0.240478 | 0.240478 | 3321.35 | 3321.35 | 5502.40 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.171863 | 0.171863 | 0.171863 | 0.171863 | 2312.85 | 2312.85 | 5512.16 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.336255 | 0.336255 | 0.336255 | 0.336255 | 4658.89 | 4658.89 | 6951.70 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.162588 | 0.162588 | 0.162588 | 0.162588 | 2157.41 | 2157.41 | 5510.40 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.116577 | 0.116577 | 0.116577 | 0.116577 | 1441.61 | 1441.61 | 4507.40 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.116575 | 0.116575 | 0.116575 | 0.116575 | 1437.68 | 1437.68 | 4507.37 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.182502 | 0.182502 | 0.182502 | 0.182502 | 2548.65 | 2548.65 | 4495.96 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.187975 | 0.187975 | 0.187975 | 0.187975 | 2624.50 | 2624.50 | 4504.48 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.320945 | 0.320945 | 0.320945 | 0.320945 | 4424.22 | 4424.22 | 4786.49 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.237658 | 0.237658 | 0.237658 | 0.237658 | 3209.61 | 3209.61 | 4780.83 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.326133 | 0.326133 | 0.326133 | 0.326133 | 4525.10 | 4525.10 | 4807.88 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.191209 | 0.191209 | 0.191209 | 0.191209 | 2563.62 | 2563.62 | 4778.05 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.135228 | 0.135228 | 0.135228 | 0.135228 | 1744.24 | 1744.24 | 3625.72 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.133723 | 0.133723 | 0.133723 | 0.133723 | 1723.24 | 1723.24 | 3625.66 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.247080 | 0.247080 | 0.247080 | 0.247080 | 3439.33 | 3439.33 | 3634.92 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.249233 | 0.249233 | 0.249233 | 0.249233 | 3469.18 | 3469.18 | 3636.30 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.322935 | 0.322935 | 0.322935 | 0.322935 | 4447.24 | 4447.24 | 4612.41 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.240963 | 0.240963 | 0.240963 | 0.240963 | 3258.29 | 3258.29 | 4608.83 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.311826 | 0.311826 | 0.311826 | 0.311826 | 4322.34 | 4322.34 | 4611.53 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.195248 | 0.195248 | 0.195248 | 0.195248 | 2615.20 | 2615.20 | 4605.55 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.140052 | 0.140052 | 0.140052 | 0.140052 | 1808.65 | 1808.65 | 3450.35 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.138573 | 0.138573 | 0.138573 | 0.138573 | 1788.03 | 1788.03 | 3450.28 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.251081 | 0.251081 | 0.251081 | 0.251081 | 3492.08 | 3492.08 | 3455.49 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.252224 | 0.252224 | 0.252224 | 0.252224 | 3507.91 | 3507.91 | 3455.63 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.323170 | 0.323170 | 0.323170 | 0.323170 | 4447.08 | 4447.08 | 4585.30 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.241564 | 0.241564 | 0.241564 | 0.241564 | 3268.82 | 3268.82 | 4582.21 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.310691 | 0.310691 | 0.310691 | 0.310691 | 4303.23 | 4303.23 | 4581.87 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.195775 | 0.195775 | 0.195775 | 0.195775 | 2619.28 | 2619.28 | 4578.54 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.141111 | 0.141111 | 0.141111 | 0.141111 | 1821.26 | 1821.26 | 3416.97 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.139632 | 0.139632 | 0.139632 | 0.139632 | 1800.65 | 1800.65 | 3416.90 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.251878 | 0.251878 | 0.251878 | 0.251878 | 3501.07 | 3501.07 | 3421.46 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.252883 | 0.252883 | 0.252883 | 0.252883 | 3515.00 | 3515.00 | 3421.40 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.325445 | 0.325445 | 0.325445 | 0.325445 | 4475.81 | 4475.81 | 4554.52 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.244132 | 0.244132 | 0.244132 | 0.244132 | 3301.71 | 3301.71 | 4550.10 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.312940 | 0.312940 | 0.312940 | 0.312940 | 4331.61 | 4331.61 | 4550.58 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.198239 | 0.198239 | 0.198239 | 0.198239 | 2650.74 | 2650.74 | 4546.13 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.143936 | 0.143936 | 0.143936 | 0.143936 | 1858.89 | 1858.89 | 3382.60 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.142460 | 0.142460 | 0.142460 | 0.142460 | 1838.32 | 1838.32 | 3382.51 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.254524 | 0.254524 | 0.254524 | 0.254524 | 3536.05 | 3536.05 | 3388.42 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.255506 | 0.255506 | 0.255506 | 0.255506 | 3549.67 | 3549.67 | 3388.34 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.321256 | 0.321256 | 0.321256 | 0.321256 | 4415.38 | 4415.38 | 4604.23 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.240179 | 0.240179 | 0.240179 | 0.240179 | 3244.27 | 3244.27 | 4600.37 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.308908 | 0.308908 | 0.308908 | 0.308908 | 4273.40 | 4273.40 | 4600.00 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.194325 | 0.194325 | 0.194325 | 0.194325 | 2594.37 | 2594.37 | 4596.13 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.140396 | 0.140396 | 0.140396 | 0.140396 | 1808.02 | 1808.02 | 3425.72 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.138927 | 0.138927 | 0.138927 | 0.138927 | 1787.53 | 1787.53 | 3425.63 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.250634 | 0.250634 | 0.250634 | 0.250634 | 3480.71 | 3480.71 | 3430.92 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.251614 | 0.251614 | 0.251614 | 0.251614 | 3494.29 | 3494.29 | 3430.83 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.319495 | 0.319495 | 0.319495 | 0.319495 | 4388.88 | 4388.88 | 4628.54 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.238662 | 0.238662 | 0.238662 | 0.238662 | 3221.04 | 3221.04 | 4624.01 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.307280 | 0.307280 | 0.307280 | 0.307280 | 4248.77 | 4248.77 | 4624.08 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.192803 | 0.192803 | 0.192803 | 0.192803 | 2571.38 | 2571.38 | 4619.54 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.139184 | 0.139184 | 0.139184 | 0.139184 | 1789.79 | 1789.79 | 3445.97 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.137719 | 0.137719 | 0.137719 | 0.137719 | 1769.38 | 1769.38 | 3445.87 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.249127 | 0.249127 | 0.249127 | 0.249127 | 3458.56 | 3458.56 | 3451.80 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.250105 | 0.250105 | 0.250105 | 0.250105 | 3472.12 | 3472.12 | 3451.71 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.318944 | 0.318944 | 0.318944 | 0.318944 | 4379.36 | 4379.36 | 4671.11 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.238416 | 0.238416 | 0.238416 | 0.238416 | 3215.70 | 3215.70 | 4665.56 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.306828 | 0.306828 | 0.306828 | 0.306828 | 4240.65 | 4240.65 | 4666.45 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.192479 | 0.192479 | 0.192479 | 0.192479 | 2565.15 | 2565.15 | 4660.90 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.139274 | 0.139274 | 0.139274 | 0.139274 | 1789.86 | 1789.86 | 3485.47 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.137817 | 0.137817 | 0.137817 | 0.137817 | 1769.56 | 1769.56 | 3485.38 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.248792 | 0.248792 | 0.248792 | 0.248792 | 3452.78 | 3452.78 | 3492.29 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.249770 | 0.249770 | 0.249770 | 0.249770 | 3466.35 | 3466.35 | 3492.19 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.325561 | 0.325561 | 0.325561 | 0.325561 | 4469.29 | 4469.29 | 4948.96 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.245494 | 0.245494 | 0.245494 | 0.245494 | 3312.41 | 3312.41 | 4938.86 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.312308 | 0.312308 | 0.312308 | 0.312308 | 4314.83 | 4314.83 | 4944.08 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.194733 | 0.194733 | 0.194733 | 0.194733 | 2594.71 | 2594.71 | 4933.98 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.145680 | 0.145680 | 0.145680 | 0.145680 | 1878.10 | 1878.10 | 3745.27 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.144163 | 0.144163 | 0.144163 | 0.144163 | 1856.97 | 1856.97 | 3745.16 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.253397 | 0.253397 | 0.253397 | 0.253397 | 3515.55 | 3515.55 | 3756.15 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.254496 | 0.254496 | 0.254496 | 0.254496 | 3530.78 | 3530.78 | 3756.04 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.385416 | 0.385416 | 0.385416 | 0.385416 | 5312.15 | 5312.15 | 6347.84 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.287525 | 0.287525 | 0.287525 | 0.287525 | 3915.30 | 3915.30 | 6348.72 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.366283 | 0.366283 | 0.366283 | 0.366283 | 5060.75 | 5060.75 | 6343.09 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.224572 | 0.224572 | 0.224572 | 0.224572 | 3028.56 | 3028.56 | 6343.96 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.159694 | 0.159694 | 0.159694 | 0.159694 | 2085.92 | 2085.92 | 5226.67 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.156615 | 0.156615 | 0.156615 | 0.156615 | 2043.06 | 2043.06 | 5226.56 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.321790 | 0.321790 | 0.321790 | 0.321790 | 4462.20 | 4462.20 | 5223.52 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.322872 | 0.322872 | 0.322872 | 0.322872 | 4477.19 | 4477.19 | 5223.42 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.240478 |
AIRLOOP G NW SUPPLY FAN | 0.171863 |
AIRLOOP OFFICE SUPPLY FAN | 0.336255 |
AIRLOOP G NE SUPPLY FAN | 0.162588 |
AIRLOOP G N1 SUPPLY FAN | 0.116577 |
AIRLOOP G N2 SUPPLY FAN | 0.116575 |
AIRLOOP G S1 SUPPLY FAN | 0.182502 |
AIRLOOP G S2 SUPPLY FAN | 0.187975 |
AIRLOOP F2 SW SUPPLY FAN | 0.320945 |
AIRLOOP F2 NW SUPPLY FAN | 0.237658 |
AIRLOOP F2 SE SUPPLY FAN | 0.326133 |
AIRLOOP F2 NE SUPPLY FAN | 0.191209 |
AIRLOOP F2 N1 SUPPLY FAN | 0.135228 |
AIRLOOP F2 N2 SUPPLY FAN | 0.133723 |
AIRLOOP F2 S1 SUPPLY FAN | 0.247080 |
AIRLOOP F2 S2 SUPPLY FAN | 0.249233 |
AIRLOOP F3 SW SUPPLY FAN | 0.322935 |
AIRLOOP F3 NW SUPPLY FAN | 0.240963 |
AIRLOOP F3 SE SUPPLY FAN | 0.311826 |
AIRLOOP F3 NE SUPPLY FAN | 0.195248 |
AIRLOOP F3 N1 SUPPLY FAN | 0.140052 |
AIRLOOP F3 N2 SUPPLY FAN | 0.138573 |
AIRLOOP F3 S1 SUPPLY FAN | 0.251081 |
AIRLOOP F3 S2 SUPPLY FAN | 0.252224 |
AIRLOOP F4 SW SUPPLY FAN | 0.323170 |
AIRLOOP F4 NW SUPPLY FAN | 0.241564 |
AIRLOOP F4 SE SUPPLY FAN | 0.310691 |
AIRLOOP F4 NE SUPPLY FAN | 0.195775 |
AIRLOOP F4 N1 SUPPLY FAN | 0.141111 |
AIRLOOP F4 N2 SUPPLY FAN | 0.139632 |
AIRLOOP F4 S1 SUPPLY FAN | 0.251878 |
AIRLOOP F4 S2 SUPPLY FAN | 0.252883 |
AIRLOOP M SW SUPPLY FAN | 0.325445 |
AIRLOOP M NW SUPPLY FAN | 0.244132 |
AIRLOOP M SE SUPPLY FAN | 0.312940 |
AIRLOOP M NE SUPPLY FAN | 0.198239 |
AIRLOOP M N1 SUPPLY FAN | 0.143936 |
AIRLOOP M N2 SUPPLY FAN | 0.142460 |
AIRLOOP M S1 SUPPLY FAN | 0.254524 |
AIRLOOP M S2 SUPPLY FAN | 0.255506 |
AIRLOOP F6 SW SUPPLY FAN | 0.321256 |
AIRLOOP F6 NW SUPPLY FAN | 0.240179 |
AIRLOOP F6 SE SUPPLY FAN | 0.308908 |
AIRLOOP F6 NE SUPPLY FAN | 0.194325 |
AIRLOOP F6 N1 SUPPLY FAN | 0.140396 |
AIRLOOP F6 N2 SUPPLY FAN | 0.138927 |
AIRLOOP F6 S1 SUPPLY FAN | 0.250634 |
AIRLOOP F6 S2 SUPPLY FAN | 0.251614 |
AIRLOOP F7 SW SUPPLY FAN | 0.319495 |
AIRLOOP F7 NW SUPPLY FAN | 0.238662 |
AIRLOOP F7 SE SUPPLY FAN | 0.307280 |
AIRLOOP F7 NE SUPPLY FAN | 0.192803 |
AIRLOOP F7 N1 SUPPLY FAN | 0.139184 |
AIRLOOP F7 N2 SUPPLY FAN | 0.137719 |
AIRLOOP F7 S1 SUPPLY FAN | 0.249127 |
AIRLOOP F7 S2 SUPPLY FAN | 0.250105 |
AIRLOOP F8 SW SUPPLY FAN | 0.318944 |
AIRLOOP F8 NW SUPPLY FAN | 0.238416 |
AIRLOOP F8 SE SUPPLY FAN | 0.306828 |
AIRLOOP F8 NE SUPPLY FAN | 0.192479 |
AIRLOOP F8 N1 SUPPLY FAN | 0.139274 |
AIRLOOP F8 N2 SUPPLY FAN | 0.137817 |
AIRLOOP F8 S1 SUPPLY FAN | 0.248792 |
AIRLOOP F8 S2 SUPPLY FAN | 0.249770 |
AIRLOOP F9 SW SUPPLY FAN | 0.325561 |
AIRLOOP F9 NW SUPPLY FAN | 0.245494 |
AIRLOOP F9 SE SUPPLY FAN | 0.312308 |
AIRLOOP F9 NE SUPPLY FAN | 0.194733 |
AIRLOOP F9 N1 SUPPLY FAN | 0.145680 |
AIRLOOP F9 N2 SUPPLY FAN | 0.144163 |
AIRLOOP F9 S1 SUPPLY FAN | 0.253397 |
AIRLOOP F9 S2 SUPPLY FAN | 0.254496 |
AIRLOOP T SW SUPPLY FAN | 0.385416 |
AIRLOOP T NW SUPPLY FAN | 0.287525 |
AIRLOOP T SE SUPPLY FAN | 0.366283 |
AIRLOOP T NE SUPPLY FAN | 0.224572 |
AIRLOOP T N1 SUPPLY FAN | 0.159694 |
AIRLOOP T N2 SUPPLY FAN | 0.156615 |
AIRLOOP T S1 SUPPLY FAN | 0.321790 |
AIRLOOP T S2 SUPPLY FAN | 0.322872 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.240478 | 3321.35 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.171863 | 2312.85 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.336255 | 4658.89 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.162588 | 2157.41 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.116577 | 1441.61 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.116575 | 1437.68 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.182502 | 2548.65 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.187975 | 2624.50 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.320945 | 4424.22 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.237658 | 3209.61 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.326133 | 4525.10 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.191209 | 2563.62 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.135228 | 1744.24 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.133723 | 1723.24 | 0.000038 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.247080 | 3439.33 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.249233 | 3469.18 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.322935 | 4447.24 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.240963 | 3258.29 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.311826 | 4322.34 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.195248 | 2615.20 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.140052 | 1808.65 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.138573 | 1788.03 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.251081 | 3492.08 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.252224 | 3507.91 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.323170 | 4447.08 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.241564 | 3268.82 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.310691 | 4303.23 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.195775 | 2619.28 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.141111 | 1821.26 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.139632 | 1800.65 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.251878 | 3501.07 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.252883 | 3515.00 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.325445 | 4475.81 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.244132 | 3301.71 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.312940 | 4331.61 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.198239 | 2650.74 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.143936 | 1858.89 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.142460 | 1838.32 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.254524 | 3536.05 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.255506 | 3549.67 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.321256 | 4415.38 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.240179 | 3244.27 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.308908 | 4273.40 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.194325 | 2594.37 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.140396 | 1808.02 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.138927 | 1787.53 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.250634 | 3480.71 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.251614 | 3494.29 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.319495 | 4388.88 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.238662 | 3221.04 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.307280 | 4248.77 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.192803 | 2571.38 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.139184 | 1789.79 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.137719 | 1769.38 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.249127 | 3458.56 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.250105 | 3472.12 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.318944 | 4379.36 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.238416 | 3215.70 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.306828 | 4240.65 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.192479 | 2565.15 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.139274 | 1789.86 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.137817 | 1769.56 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.248792 | 3452.78 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.249770 | 3466.35 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.325561 | 4469.29 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.245494 | 3312.41 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.312308 | 4314.83 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.194733 | 2594.71 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.145680 | 1878.10 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.144163 | 1856.97 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.253397 | 3515.55 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.254496 | 3530.78 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.385416 | 5312.15 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.287525 | 3915.30 | 0.000086 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.366283 | 5060.75 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.224572 | 3028.56 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.159694 | 2085.92 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.156615 | 2043.06 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.321790 | 4462.20 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.322872 | 4477.19 | 0.000098 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 5502.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 5512.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 6951.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 5510.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 4507.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 4507.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 4495.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 4504.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 4786.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 4780.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 4807.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 4778.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 3625.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 3625.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 3634.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 3636.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 4612.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 4608.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 4611.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 4605.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 3450.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 3450.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 3455.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 3455.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 4585.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 4582.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 4581.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 4578.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 3416.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 3416.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 3421.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 3421.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 4554.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 4550.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 4550.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 4546.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 3382.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 3382.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 3388.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 3388.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 4604.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 4600.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 4600.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 4596.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 3425.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 3425.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 3430.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 3430.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 4628.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 4624.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 4624.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 4619.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 3445.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 3445.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 3451.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 3451.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 4671.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 4665.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 4666.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 4660.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 3485.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 3485.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 3492.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 3492.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 4948.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 4938.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 4944.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 4933.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 3745.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 3745.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 3756.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 3756.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 6347.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 6348.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 6343.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 6343.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 5226.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 5226.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 5223.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 5223.42 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005514 | 6.20 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005514 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005514 | 2661.80 | 7.12 | 8130.20 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005514 | 1406.33 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2018-10-19 09:40:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.74 | -10.3 |
April | 22.42 | 0.73 |
May | 23.15 | 10.60 |
June | 24.11 | 15.96 |
July | 24.18 | 16.86 |
August | 24.03 | 14.24 |
September | 23.07 | 6.72 |
October | 21.80 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.61 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.18 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.87 | 0.73 |
May | 22.48 | 10.60 |
June | 23.94 | 15.96 |
July | 24.06 | 16.86 |
August | 23.67 | 14.24 |
September | 22.37 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.39 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.06 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.81 | -10.3 |
April | 22.42 | 0.73 |
May | 23.30 | 10.60 |
June | 24.21 | 15.96 |
July | 24.27 | 16.86 |
August | 24.10 | 14.24 |
September | 23.06 | 6.72 |
October | 21.87 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.84 | 0.73 |
May | 22.73 | 10.60 |
June | 23.99 | 15.96 |
July | 24.11 | 16.86 |
August | 23.75 | 14.24 |
September | 22.46 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.43 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.11 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.76 | 0.73 |
May | 22.27 | 10.60 |
June | 23.81 | 15.96 |
July | 23.99 | 16.86 |
August | 23.61 | 14.24 |
September | 22.41 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.34 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.99 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.76 | 0.73 |
May | 22.30 | 10.60 |
June | 23.82 | 15.96 |
July | 23.99 | 16.86 |
August | 23.62 | 14.24 |
September | 22.43 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.35 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.99 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.75 | -10.3 |
April | 22.40 | 0.73 |
May | 23.12 | 10.60 |
June | 24.07 | 15.96 |
July | 24.16 | 16.86 |
August | 24.07 | 14.24 |
September | 23.28 | 6.72 |
October | 21.86 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.63 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.16 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.75 | -10.3 |
April | 22.42 | 0.73 |
May | 23.17 | 10.60 |
June | 24.09 | 15.96 |
July | 24.18 | 16.86 |
August | 24.10 | 14.24 |
September | 23.32 | 6.72 |
October | 21.87 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.65 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.18 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.35 | -17.6 |
February | 13.17 | -15.4 |
March | 14.62 | -10.3 |
April | 17.87 | 0.73 |
May | 20.97 | 10.60 |
June | 23.35 | 15.96 |
July | 23.77 | 16.86 |
August | 22.84 | 14.24 |
September | 20.26 | 6.72 |
October | 16.40 | -3.1 |
November | 12.59 | -17.6 |
December | 11.98 | -19.3 |
Annual Sum or Average | 17.54 | -1.4 |
Minimum of Months | 11.98 | -19.3 |
Maximum of Months | 23.77 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.84 | -10.3 |
April | 23.00 | 0.73 |
May | 24.06 | 10.60 |
June | 24.34 | 15.96 |
July | 24.35 | 16.86 |
August | 24.29 | 14.24 |
September | 23.54 | 6.72 |
October | 21.97 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.86 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.17 | 0.73 |
May | 23.57 | 10.60 |
June | 24.25 | 15.96 |
July | 24.30 | 16.86 |
August | 24.06 | 14.24 |
September | 22.73 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.61 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.91 | -10.3 |
April | 23.06 | 0.73 |
May | 24.14 | 10.60 |
June | 24.37 | 15.96 |
July | 24.38 | 16.86 |
August | 24.32 | 14.24 |
September | 23.65 | 6.72 |
October | 22.06 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.90 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.38 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.12 | 0.73 |
May | 23.68 | 10.60 |
June | 24.27 | 15.96 |
July | 24.31 | 16.86 |
August | 24.08 | 14.24 |
September | 22.78 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.63 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.98 | 0.73 |
May | 23.40 | 10.60 |
June | 24.17 | 15.96 |
July | 24.24 | 16.86 |
August | 24.00 | 14.24 |
September | 22.77 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.57 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.98 | 0.73 |
May | 23.42 | 10.60 |
June | 24.17 | 15.96 |
July | 24.25 | 16.86 |
August | 24.01 | 14.24 |
September | 22.79 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.58 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.25 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.92 | -10.3 |
April | 23.11 | 0.73 |
May | 24.11 | 10.60 |
June | 24.32 | 15.96 |
July | 24.33 | 16.86 |
August | 24.31 | 14.24 |
September | 23.77 | 6.72 |
October | 22.15 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.93 | -10.3 |
April | 23.12 | 0.73 |
May | 24.13 | 10.60 |
June | 24.33 | 15.96 |
July | 24.34 | 16.86 |
August | 24.31 | 14.24 |
September | 23.79 | 6.72 |
October | 22.17 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.92 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.34 | -17.6 |
February | 20.81 | -15.4 |
March | 21.46 | -10.3 |
April | 23.17 | 0.73 |
May | 25.06 | 10.60 |
June | 26.13 | 15.96 |
July | 26.19 | 16.86 |
August | 25.74 | 14.24 |
September | 24.16 | 6.72 |
October | 21.82 | -3.1 |
November | 20.59 | -17.6 |
December | 20.17 | -19.3 |
Annual Sum or Average | 22.98 | -1.4 |
Minimum of Months | 20.17 | -19.3 |
Maximum of Months | 26.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.86 | -10.3 |
April | 23.10 | 0.73 |
May | 24.16 | 10.60 |
June | 24.35 | 15.96 |
July | 24.36 | 16.86 |
August | 24.30 | 14.24 |
September | 23.61 | 6.72 |
October | 22.03 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.89 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.27 | 0.73 |
May | 23.81 | 10.60 |
June | 24.26 | 15.96 |
July | 24.31 | 16.86 |
August | 24.10 | 14.24 |
September | 22.85 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.91 | -10.3 |
April | 23.11 | 0.73 |
May | 24.19 | 10.60 |
June | 24.36 | 15.96 |
July | 24.37 | 16.86 |
August | 24.32 | 14.24 |
September | 23.67 | 6.72 |
October | 22.08 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.37 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.24 | 0.73 |
May | 23.85 | 10.60 |
June | 24.28 | 15.96 |
July | 24.33 | 16.86 |
August | 24.12 | 14.24 |
September | 22.90 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.12 | 0.73 |
May | 23.74 | 10.60 |
June | 24.19 | 15.96 |
July | 24.27 | 16.86 |
August | 24.07 | 14.24 |
September | 22.94 | 6.72 |
October | 21.74 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.64 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.11 | 0.73 |
May | 23.75 | 10.60 |
June | 24.20 | 15.96 |
July | 24.27 | 16.86 |
August | 24.08 | 14.24 |
September | 22.95 | 6.72 |
October | 21.74 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.64 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.99 | -10.3 |
April | 23.27 | 0.73 |
May | 24.24 | 10.60 |
June | 24.33 | 15.96 |
July | 24.34 | 16.86 |
August | 24.32 | 14.24 |
September | 23.87 | 6.72 |
October | 22.26 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.96 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 22.00 | -10.3 |
April | 23.28 | 0.73 |
May | 24.25 | 10.60 |
June | 24.33 | 15.96 |
July | 24.34 | 16.86 |
August | 24.32 | 14.24 |
September | 23.88 | 6.72 |
October | 22.27 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.96 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.10 | -17.6 |
February | 21.55 | -15.4 |
March | 22.14 | -10.3 |
April | 23.78 | 0.73 |
May | 25.68 | 10.60 |
June | 26.42 | 15.96 |
July | 26.44 | 16.86 |
August | 26.03 | 14.24 |
September | 24.57 | 6.72 |
October | 22.34 | -3.1 |
November | 21.37 | -17.6 |
December | 20.97 | -19.3 |
Annual Sum or Average | 23.54 | -1.4 |
Minimum of Months | 20.97 | -19.3 |
Maximum of Months | 26.44 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.86 | -10.3 |
April | 23.10 | 0.73 |
May | 24.17 | 10.60 |
June | 24.35 | 15.96 |
July | 24.36 | 16.86 |
August | 24.30 | 14.24 |
September | 23.62 | 6.72 |
October | 22.03 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.89 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.29 | 0.73 |
May | 23.86 | 10.60 |
June | 24.26 | 15.96 |
July | 24.32 | 16.86 |
August | 24.12 | 14.24 |
September | 22.90 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.91 | -10.3 |
April | 23.10 | 0.73 |
May | 24.20 | 10.60 |
June | 24.36 | 15.96 |
July | 24.38 | 16.86 |
August | 24.32 | 14.24 |
September | 23.67 | 6.72 |
October | 22.08 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.38 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.26 | 0.73 |
May | 23.90 | 10.60 |
June | 24.27 | 15.96 |
July | 24.34 | 16.86 |
August | 24.14 | 14.24 |
September | 22.96 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.68 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.16 | 0.73 |
May | 23.85 | 10.60 |
June | 24.20 | 15.96 |
July | 24.29 | 16.86 |
August | 24.10 | 14.24 |
September | 23.03 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.16 | 0.73 |
May | 23.86 | 10.60 |
June | 24.20 | 15.96 |
July | 24.29 | 16.86 |
August | 24.11 | 14.24 |
September | 23.05 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.73 | -15.4 |
March | 22.00 | -10.3 |
April | 23.29 | 0.73 |
May | 24.27 | 10.60 |
June | 24.33 | 15.96 |
July | 24.35 | 16.86 |
August | 24.32 | 14.24 |
September | 23.90 | 6.72 |
October | 22.29 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.97 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.73 | -15.4 |
March | 22.01 | -10.3 |
April | 23.30 | 0.73 |
May | 24.27 | 10.60 |
June | 24.33 | 15.96 |
July | 24.35 | 16.86 |
August | 24.33 | 14.24 |
September | 23.91 | 6.72 |
October | 22.30 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.97 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -17.6 |
February | 21.75 | -15.4 |
March | 22.33 | -10.3 |
April | 23.97 | 0.73 |
May | 25.89 | 10.60 |
June | 26.53 | 15.96 |
July | 26.55 | 16.86 |
August | 26.16 | 14.24 |
September | 24.75 | 6.72 |
October | 22.51 | -3.1 |
November | 21.56 | -17.6 |
December | 21.16 | -19.3 |
Annual Sum or Average | 23.72 | -1.4 |
Minimum of Months | 21.16 | -19.3 |
Maximum of Months | 26.55 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.86 | -10.3 |
April | 23.09 | 0.73 |
May | 24.17 | 10.60 |
June | 24.34 | 15.96 |
July | 24.36 | 16.86 |
August | 24.30 | 14.24 |
September | 23.63 | 6.72 |
October | 22.03 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.89 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.30 | 0.73 |
May | 23.87 | 10.60 |
June | 24.25 | 15.96 |
July | 24.32 | 16.86 |
August | 24.12 | 14.24 |
September | 22.93 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.68 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.91 | -10.3 |
April | 23.10 | 0.73 |
May | 24.19 | 10.60 |
June | 24.35 | 15.96 |
July | 24.38 | 16.86 |
August | 24.31 | 14.24 |
September | 23.68 | 6.72 |
October | 22.08 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.38 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.27 | 0.73 |
May | 23.90 | 10.60 |
June | 24.26 | 15.96 |
July | 24.34 | 16.86 |
August | 24.14 | 14.24 |
September | 22.99 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.68 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.19 | 0.73 |
May | 23.87 | 10.60 |
June | 24.19 | 15.96 |
July | 24.29 | 16.86 |
August | 24.11 | 14.24 |
September | 23.08 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.18 | 0.73 |
May | 23.88 | 10.60 |
June | 24.19 | 15.96 |
July | 24.29 | 16.86 |
August | 24.11 | 14.24 |
September | 23.10 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.73 | -15.4 |
March | 22.01 | -10.3 |
April | 23.30 | 0.73 |
May | 24.27 | 10.60 |
June | 24.32 | 15.96 |
July | 24.35 | 16.86 |
August | 24.32 | 14.24 |
September | 23.91 | 6.72 |
October | 22.30 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.97 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.73 | -15.4 |
March | 22.02 | -10.3 |
April | 23.30 | 0.73 |
May | 24.27 | 10.60 |
June | 24.33 | 15.96 |
July | 24.35 | 16.86 |
August | 24.32 | 14.24 |
September | 23.92 | 6.72 |
October | 22.31 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.98 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | -17.6 |
February | 22.42 | -15.4 |
March | 23.00 | -10.3 |
April | 24.60 | 0.73 |
May | 26.52 | 10.60 |
June | 27.13 | 15.96 |
July | 27.16 | 16.86 |
August | 26.77 | 14.24 |
September | 25.40 | 6.72 |
October | 23.18 | -3.1 |
November | 22.25 | -17.6 |
December | 21.86 | -19.3 |
Annual Sum or Average | 24.37 | -1.4 |
Minimum of Months | 21.86 | -19.3 |
Maximum of Months | 27.16 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.85 | -10.3 |
April | 23.04 | 0.73 |
May | 24.13 | 10.60 |
June | 24.32 | 15.96 |
July | 24.35 | 16.86 |
August | 24.28 | 14.24 |
September | 23.57 | 6.72 |
October | 21.99 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.24 | 0.73 |
May | 23.78 | 10.60 |
June | 24.21 | 15.96 |
July | 24.31 | 16.86 |
August | 24.07 | 14.24 |
September | 22.83 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.65 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.88 | -10.3 |
April | 23.04 | 0.73 |
May | 24.15 | 10.60 |
June | 24.33 | 15.96 |
July | 24.37 | 16.86 |
August | 24.29 | 14.24 |
September | 23.61 | 6.72 |
October | 22.03 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.88 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.37 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.21 | 0.73 |
May | 23.83 | 10.60 |
June | 24.23 | 15.96 |
July | 24.32 | 16.86 |
August | 24.09 | 14.24 |
September | 22.89 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.65 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.13 | 0.73 |
May | 23.79 | 10.60 |
June | 24.15 | 15.96 |
July | 24.27 | 16.86 |
August | 24.06 | 14.24 |
September | 22.98 | 6.72 |
October | 21.74 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.64 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.12 | 0.73 |
May | 23.80 | 10.60 |
June | 24.16 | 15.96 |
July | 24.27 | 16.86 |
August | 24.06 | 14.24 |
September | 22.99 | 6.72 |
October | 21.74 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.64 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.97 | -10.3 |
April | 23.24 | 0.73 |
May | 24.24 | 10.60 |
June | 24.30 | 15.96 |
July | 24.34 | 16.86 |
August | 24.31 | 14.24 |
September | 23.85 | 6.72 |
October | 22.25 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.95 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.98 | -10.3 |
April | 23.24 | 0.73 |
May | 24.24 | 10.60 |
June | 24.31 | 15.96 |
July | 24.34 | 16.86 |
August | 24.31 | 14.24 |
September | 23.86 | 6.72 |
October | 22.26 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.95 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -17.6 |
February | 21.75 | -15.4 |
March | 22.30 | -10.3 |
April | 23.90 | 0.73 |
May | 25.84 | 10.60 |
June | 26.49 | 15.96 |
July | 26.53 | 16.86 |
August | 26.12 | 14.24 |
September | 24.69 | 6.72 |
October | 22.47 | -3.1 |
November | 21.58 | -17.6 |
December | 21.17 | -19.3 |
Annual Sum or Average | 23.69 | -1.4 |
Minimum of Months | 21.17 | -19.3 |
Maximum of Months | 26.53 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.83 | -10.3 |
April | 22.99 | 0.73 |
May | 24.10 | 10.60 |
June | 24.30 | 15.96 |
July | 24.35 | 16.86 |
August | 24.26 | 14.24 |
September | 23.51 | 6.72 |
October | 21.95 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.85 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.20 | 0.73 |
May | 23.71 | 10.60 |
June | 24.19 | 15.96 |
July | 24.29 | 16.86 |
August | 24.03 | 14.24 |
September | 22.74 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.62 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.87 | -10.3 |
April | 23.00 | 0.73 |
May | 24.12 | 10.60 |
June | 24.32 | 15.96 |
July | 24.36 | 16.86 |
August | 24.28 | 14.24 |
September | 23.56 | 6.72 |
October | 21.99 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.16 | 0.73 |
May | 23.77 | 10.60 |
June | 24.20 | 15.96 |
July | 24.31 | 16.86 |
August | 24.05 | 14.24 |
September | 22.80 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.63 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.08 | 0.73 |
May | 23.71 | 10.60 |
June | 24.12 | 15.96 |
July | 24.25 | 16.86 |
August | 24.02 | 14.24 |
September | 22.88 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.61 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.25 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.08 | 0.73 |
May | 23.72 | 10.60 |
June | 24.13 | 15.96 |
July | 24.26 | 16.86 |
August | 24.02 | 14.24 |
September | 22.90 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.62 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.26 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.95 | -10.3 |
April | 23.19 | 0.73 |
May | 24.20 | 10.60 |
June | 24.29 | 15.96 |
July | 24.33 | 16.86 |
August | 24.29 | 14.24 |
September | 23.80 | 6.72 |
October | 22.20 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.93 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.96 | -10.3 |
April | 23.20 | 0.73 |
May | 24.21 | 10.60 |
June | 24.29 | 15.96 |
July | 24.33 | 16.86 |
August | 24.30 | 14.24 |
September | 23.81 | 6.72 |
October | 22.21 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.93 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -17.6 |
February | 21.62 | -15.4 |
March | 22.16 | -10.3 |
April | 23.74 | 0.73 |
May | 25.68 | 10.60 |
June | 26.37 | 15.96 |
July | 26.43 | 16.86 |
August | 25.99 | 14.24 |
September | 24.51 | 6.72 |
October | 22.32 | -3.1 |
November | 21.46 | -17.6 |
December | 21.04 | -19.3 |
Annual Sum or Average | 23.55 | -1.4 |
Minimum of Months | 21.04 | -19.3 |
Maximum of Months | 26.43 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.82 | -10.3 |
April | 22.95 | 0.73 |
May | 24.07 | 10.60 |
June | 24.29 | 15.96 |
July | 24.34 | 16.86 |
August | 24.24 | 14.24 |
September | 23.46 | 6.72 |
October | 21.92 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.83 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.16 | 0.73 |
May | 23.64 | 10.60 |
June | 24.16 | 15.96 |
July | 24.28 | 16.86 |
August | 23.99 | 14.24 |
September | 22.65 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.60 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.85 | -10.3 |
April | 22.97 | 0.73 |
May | 24.09 | 10.60 |
June | 24.31 | 15.96 |
July | 24.36 | 16.86 |
August | 24.26 | 14.24 |
September | 23.50 | 6.72 |
October | 21.96 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.85 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.13 | 0.73 |
May | 23.71 | 10.60 |
June | 24.18 | 15.96 |
July | 24.30 | 16.86 |
August | 24.01 | 14.24 |
September | 22.70 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.61 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.05 | 0.73 |
May | 23.63 | 10.60 |
June | 24.10 | 15.96 |
July | 24.24 | 16.86 |
August | 23.98 | 14.24 |
September | 22.77 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.59 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.05 | 0.73 |
May | 23.64 | 10.60 |
June | 24.10 | 15.96 |
July | 24.24 | 16.86 |
August | 23.98 | 14.24 |
September | 22.78 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.59 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.93 | -10.3 |
April | 23.15 | 0.73 |
May | 24.17 | 10.60 |
June | 24.27 | 15.96 |
July | 24.33 | 16.86 |
August | 24.28 | 14.24 |
September | 23.74 | 6.72 |
October | 22.15 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.93 | -10.3 |
April | 23.15 | 0.73 |
May | 24.18 | 10.60 |
June | 24.28 | 15.96 |
July | 24.33 | 16.86 |
August | 24.28 | 14.24 |
September | 23.75 | 6.72 |
October | 22.16 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.91 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | -17.6 |
February | 21.53 | -15.4 |
March | 22.06 | -10.3 |
April | 23.64 | 0.73 |
May | 25.58 | 10.60 |
June | 26.33 | 15.96 |
July | 26.41 | 16.86 |
August | 25.94 | 14.24 |
September | 24.37 | 6.72 |
October | 22.21 | -3.1 |
November | 21.38 | -17.6 |
December | 20.96 | -19.3 |
Annual Sum or Average | 23.47 | -1.4 |
Minimum of Months | 20.96 | -19.3 |
Maximum of Months | 26.41 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.81 | -10.3 |
April | 22.88 | 0.73 |
May | 24.00 | 10.60 |
June | 24.27 | 15.96 |
July | 24.33 | 16.86 |
August | 24.21 | 14.24 |
September | 23.34 | 6.72 |
October | 21.87 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.80 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.12 | 0.73 |
May | 23.53 | 10.60 |
June | 24.14 | 15.96 |
July | 24.27 | 16.86 |
August | 23.93 | 14.24 |
September | 22.51 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.57 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.83 | -10.3 |
April | 22.90 | 0.73 |
May | 24.04 | 10.60 |
June | 24.29 | 15.96 |
July | 24.36 | 16.86 |
August | 24.23 | 14.24 |
September | 23.38 | 6.72 |
October | 21.90 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.10 | 0.73 |
May | 23.63 | 10.60 |
June | 24.15 | 15.96 |
July | 24.29 | 16.86 |
August | 23.94 | 14.24 |
September | 22.55 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.58 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.02 | 0.73 |
May | 23.52 | 10.60 |
June | 24.07 | 15.96 |
July | 24.23 | 16.86 |
August | 23.91 | 14.24 |
September | 22.59 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.55 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.23 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.02 | 0.73 |
May | 23.54 | 10.60 |
June | 24.08 | 15.96 |
July | 24.23 | 16.86 |
August | 23.91 | 14.24 |
September | 22.61 | 6.72 |
October | 21.72 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.56 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.23 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.89 | -10.3 |
April | 23.06 | 0.73 |
May | 24.11 | 10.60 |
June | 24.26 | 15.96 |
July | 24.32 | 16.86 |
August | 24.26 | 14.24 |
September | 23.61 | 6.72 |
October | 22.07 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.89 | -10.3 |
April | 23.07 | 0.73 |
May | 24.11 | 10.60 |
June | 24.26 | 15.96 |
July | 24.32 | 16.86 |
August | 24.26 | 14.24 |
September | 23.62 | 6.72 |
October | 22.07 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | -17.6 |
February | 21.25 | -15.4 |
March | 21.82 | -10.3 |
April | 23.46 | 0.73 |
May | 25.44 | 10.60 |
June | 26.33 | 15.96 |
July | 26.42 | 16.86 |
August | 25.87 | 14.24 |
September | 24.12 | 6.72 |
October | 21.98 | -3.1 |
November | 21.08 | -17.6 |
December | 20.66 | -19.3 |
Annual Sum or Average | 23.28 | -1.4 |
Minimum of Months | 20.66 | -19.3 |
Maximum of Months | 26.42 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.85 | -10.3 |
April | 22.66 | 0.73 |
May | 23.56 | 10.60 |
June | 24.16 | 15.96 |
July | 24.27 | 16.86 |
August | 24.01 | 14.24 |
September | 22.91 | 6.72 |
October | 21.83 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.68 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.71 | -10.3 |
April | 22.16 | 0.73 |
May | 23.22 | 10.60 |
June | 24.01 | 15.96 |
July | 24.18 | 16.86 |
August | 23.70 | 14.24 |
September | 22.33 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.49 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.18 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.87 | -10.3 |
April | 22.68 | 0.73 |
May | 23.63 | 10.60 |
June | 24.18 | 15.96 |
July | 24.29 | 16.86 |
August | 24.04 | 14.24 |
September | 22.96 | 6.72 |
October | 21.85 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.70 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.71 | -10.3 |
April | 22.14 | 0.73 |
May | 23.31 | 10.60 |
June | 23.99 | 15.96 |
July | 24.17 | 16.86 |
August | 23.68 | 14.24 |
September | 22.35 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.49 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.17 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.06 | 0.73 |
May | 23.17 | 10.60 |
June | 23.95 | 15.96 |
July | 24.13 | 16.86 |
August | 23.65 | 14.24 |
September | 22.31 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.13 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.05 | 0.73 |
May | 23.18 | 10.60 |
June | 23.95 | 15.96 |
July | 24.13 | 16.86 |
August | 23.65 | 14.24 |
September | 22.31 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.13 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.92 | -10.3 |
April | 22.76 | 0.73 |
May | 23.72 | 10.60 |
June | 24.18 | 15.96 |
July | 24.28 | 16.86 |
August | 24.11 | 14.24 |
September | 23.15 | 6.72 |
October | 21.94 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.75 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.93 | -10.3 |
April | 22.76 | 0.73 |
May | 23.73 | 10.60 |
June | 24.19 | 15.96 |
July | 24.28 | 16.86 |
August | 24.11 | 14.24 |
September | 23.15 | 6.72 |
October | 21.94 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.75 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2018-10-19 09:40:12
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.81 | -17.6 |
February | 20.38 | -15.4 |
March | 21.30 | -10.3 |
April | 23.39 | 0.73 |
May | 25.61 | 10.60 |
June | 26.86 | 15.96 |
July | 26.97 | 16.86 |
August | 26.16 | 14.24 |
September | 23.95 | 6.72 |
October | 21.57 | -3.1 |
November | 20.04 | -17.6 |
December | 19.61 | -19.3 |
Annual Sum or Average | 22.99 | -1.4 |
Minimum of Months | 19.61 | -19.3 |
Maximum of Months | 26.97 | 16.86 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:12
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.330807E+12 | 212165.244 | 28-JAN-23:00 | 9687.493 | 29146.786 | 20785.106 | 139844.757 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.275646E+12 | 181916.998 | 23-FEB-18:00 | 22204.399 | 56867.515 | 20785.106 | 68750.732 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.270900E+12 | 147395.837 | 02-MAR-07:00 | 14239.096 | 40658.501 | 20785.106 | 58936.037 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.227255E+12 | 141022.346 | 02-APR-19:00 | 25049.151 | 49704.829 | 20785.106 | 32374.331 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.221765E+12 | 141023.760 | 31-MAY-17:15 | 22204.399 | 56867.515 | 20785.106 | 0.000 | 37357.518 | 0.000 | 1443.258 | 1220.328 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.231845E+12 | 160896.699 | 20-JUN-17:15 | 22204.399 | 56867.515 | 20785.106 | 0.000 | 56603.269 | 0.000 | 1443.258 | 1847.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.248951E+12 | 163016.961 | 11-JUL-17:15 | 22204.399 | 56867.515 | 20785.106 | 0.000 | 58650.281 | 0.000 | 1443.258 | 1920.766 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.234383E+12 | 160656.534 | 11-AUG-17:15 | 22204.399 | 56867.515 | 20785.106 | 0.000 | 56386.568 | 0.000 | 1443.258 | 1824.052 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.212999E+12 | 124580.558 | 08-SEP-17:15 | 22204.399 | 56867.515 | 20785.106 | 0.000 | 21346.171 | 0.000 | 1443.258 | 788.473 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.255827E+12 | 144518.302 | 30-OCT-19:00 | 25049.151 | 49704.829 | 20785.106 | 35870.287 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.299231E+12 | 165590.040 | 27-NOV-18:00 | 22204.399 | 56867.515 | 20785.106 | 52423.774 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.334095E+12 | 175181.031 | 15-DEC-17:00 | 18221.747 | 56933.809 | 20785.106 | 65928.569 | 0.000 | 10720.100 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.314370E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.212999E+12 | 124580.558 | 9687.493 | 29146.786 | 20785.106 | 0.000 | 0.000 | 0.000 | 1443.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.334095E+12 | 212165.244 | 25049.151 | 56933.809 | 20785.106 | 139844.757 | 58650.281 | 10720.100 | 1443.258 | 1920.766 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 09:40:12
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.530012E+12 | 317067.558 | 29-JAN-08:15 | 0.000 | 0.000 | 0.000 | 317067.558 | 95799.498 | 95799.498 | 221268.060 |
February | 0.415445E+12 | 312146.566 | 24-FEB-08:00 | 0.000 | 0.000 | 0.000 | 312146.566 | 94509.378 | 94509.378 | 217637.188 |
March | 0.363470E+12 | 284814.468 | 02-MAR-07:00 | 0.000 | 0.000 | 0.000 | 284814.468 | 96848.250 | 96848.250 | 187966.219 |
April | 0.200030E+12 | 250714.235 | 02-APR-06:00 | 0.000 | 0.000 | 0.000 | 250714.235 | 96848.005 | 96848.005 | 153866.230 |
May | 0.132126E+12 | 116486.430 | 27-MAY-07:45 | 0.000 | 0.000 | 0.000 | 116486.430 | 93543.817 | 93543.817 | 22942.613 |
June | 0.121621E+12 | 95362.514 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 95362.514 | 95362.514 | 95362.514 | 0.000 |
July | 0.121024E+12 | 93134.745 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 93134.745 | 93134.745 | 93134.745 | 0.000 |
August | 0.118047E+12 | 91480.430 | 01-AUG-06:00 | 0.000 | 0.000 | 0.000 | 91480.430 | 91480.430 | 91480.430 | 0.000 |
September | 0.127170E+12 | 148223.112 | 28-SEP-06:00 | 0.000 | 0.000 | 0.000 | 148223.112 | 91121.540 | 91121.540 | 57101.572 |
October | 0.285880E+12 | 261284.082 | 31-OCT-07:15 | 0.000 | 0.000 | 0.000 | 261284.082 | 91646.596 | 91646.596 | 169637.486 |
November | 0.468362E+12 | 299230.905 | 29-NOV-07:00 | 0.000 | 0.000 | 0.000 | 299230.905 | 94616.098 | 94616.098 | 204614.807 |
December | 0.552318E+12 | 309979.907 | 15-DEC-09:45 | 0.000 | 0.000 | 0.000 | 309979.907 | 87625.421 | 87625.421 | 222354.486 |
Annual Sum or Average | 0.343551E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.118047E+12 | 91480.430 | 0.000 | 0.000 | 0.000 | 91480.430 | 87625.421 | 87625.421 | 0.000 | |
Maximum of Months | 0.552318E+12 | 317067.558 | 0.000 | 0.000 | 0.000 | 317067.558 | 96848.250 | 96848.250 | 222354.486 |